Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920
Simulation Timestamp: 2015-09-14 08:45:03
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2975.44 | 741.34 | 798.76 |
Net Site Energy | 2975.44 | 741.34 | 798.76 |
Total Source Energy | 7113.42 | 1772.34 | 1909.60 |
Net Source Energy | 7113.42 | 1772.34 | 1909.60 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 141.13 | 50.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 188.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 637.27 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1866.56 | 1108.88 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 141.13 | 50.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 188.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 290.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 637.27 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 166.66 | 184.53 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 501.08 | 297.68 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 154.68 | 171.27 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 465.06 | 276.28 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1866.56 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1866.56 | 100.00 |
Total On-Site and Utility Electric Sources | 1866.56 | 100.00 |
Total Electricity End Uses | 1866.56 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 163.00 |
Time Setpoint Not Met During Occupied Cooling | 3285.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4798.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Weather File | Vancouver Int'l BC CAN WYEC2-B-94238 WMO#=718920 |
Latitude [deg] | 49.18 |
Longitude [deg] | -123.2 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00 | -7.00 | Wetbulb [C] | 2.90 | 100.00 |
VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 7.60 | 18.20 | Wetbulb [C] | 3.60 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 8.38 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 175.82 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5641.25 | 4503.40 | 1137.85 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16804.97 | 12905.63 | 3899.34 | 0.77 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8252.66 | 6098.56 | 2154.11 | 0.74 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12312.54 | 9830.02 | 2482.52 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5377.1 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16082.8 | 3.21 | 10.94 | 11.59 | 10.81 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7928.4 | 3.26 | 11.12 | 11.78 | 11.07 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11735.8 | 3.15 | 10.76 | 11.39 | 10.54 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 32075.38 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 514.67 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 942.95 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1077.76 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 965.11 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 942.88 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2674.25 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 942.95 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3771.78 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2989.27 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3771.78 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1141.12 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1028.34 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3771.52 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 942.88 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3771.52 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 960.12 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2792.21 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 942.95 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3771.78 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2989.27 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3771.78 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 942.95 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1144.51 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3771.52 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 942.88 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3771.52 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 942.88 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 3963.76 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1384.87 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3771.78 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2989.27 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 4035.03 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1132.70 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 978.92 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3970.28 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1127.21 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3837.57 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1347.67 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3882.63 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 16273.98 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 8714.59 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 6525.28 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.34 | 395.22 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.93 | 1060.81 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 484.79 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.74 | 847.37 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 9404.29 | 11285.14 | 0.775 | 0.930 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 23.56 | 0.01029 |
RESTROOMFLR1 | 592.66 | 711.20 | 0.049 | 0.059 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 22.61 | 0.01029 |
MEETINGROOMFLR1 | 4218.60 | 5062.32 | 0.348 | 0.418 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM101 | 438.52 | 526.23 | 0.038 | 0.046 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
GUESTROOM102 | 312.85 | 375.42 | 0.027 | 0.033 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM103 | 1367.67 | 1641.20 | 0.157 | 0.188 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM104 | 1249.41 | 1499.29 | 0.143 | 0.172 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 22.68 | 0.01029 |
GUESTROOM105 | 1729.76 | 2075.71 | 0.198 | 0.238 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
EMPLOYEELOUNGEFLR1 | 5639.74 | 6767.69 | 0.465 | 0.558 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
EXERCISECENTERFLR1 | 1279.51 | 1535.41 | 0.105 | 0.127 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 20.82 | 0.01029 |
FRONTOFFICEFLR1 | 3443.65 | 4132.37 | 0.284 | 0.340 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM201 | 581.97 | 698.36 | 0.051 | 0.061 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM202_205 | 5599.99 | 6719.99 | 0.642 | 0.770 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
GUESTROOM206_208 | 4608.97 | 5530.76 | 0.528 | 0.634 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM209_212 | 5221.34 | 6265.61 | 0.598 | 0.718 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM213 | 1478.44 | 1774.13 | 0.169 | 0.203 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
GUESTROOM214 | 1482.26 | 1778.71 | 0.170 | 0.204 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM215_218 | 8511.28 | 10213.53 | 0.743 | 0.891 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM219 | 5669.15 | 6802.98 | 0.649 | 0.779 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM220_223 | 5097.56 | 6117.07 | 0.584 | 0.701 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM224 | 1489.93 | 1787.92 | 0.171 | 0.205 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM301 | 418.33 | 502.00 | 0.037 | 0.044 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM302_305 | 1570.25 | 1884.30 | 0.137 | 0.164 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
GUESTROOM306_308 | 1467.39 | 1760.86 | 0.128 | 0.154 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM309_312 | 5178.72 | 6214.47 | 0.593 | 0.712 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 23.37 | 0.01029 |
GUESTROOM313 | 524.91 | 629.89 | 0.046 | 0.055 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 23.18 | 0.01029 |
GUESTROOM314 | 1385.61 | 1662.73 | 0.159 | 0.190 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 22.68 | 0.01029 |
GUESTROOM315_318 | 5736.92 | 6884.30 | 0.657 | 0.789 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM319 | 786.32 | 943.58 | 0.069 | 0.082 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM320_323 | 4872.75 | 5847.30 | 0.558 | 0.670 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM324 | 417.78 | 501.33 | 0.036 | 0.044 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 22.40 | 0.01029 |
GUESTROOM401 | 1654.52 | 1985.43 | 0.190 | 0.227 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.94 | 0.01029 |
GUESTROOM402_405 | 2269.96 | 2723.95 | 0.198 | 0.238 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.94 | 0.01029 |
GUESTROOM406_408 | 2116.05 | 2539.26 | 0.185 | 0.222 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.94 | 0.01029 |
GUESTROOM409_412 | 6113.73 | 7336.48 | 0.700 | 0.840 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 23.94 | 0.01029 |
GUESTROOM413 | 777.94 | 933.53 | 0.068 | 0.081 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 23.75 | 0.01029 |
GUESTROOM414 | 568.35 | 682.02 | 0.050 | 0.060 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 23.44 | 0.01029 |
GUESTROOM415_418 | 5842.54 | 7011.05 | 0.669 | 0.803 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 22.97 | 0.01029 |
GUESTROOM419 | 1595.05 | 1914.06 | 0.183 | 0.219 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 23.25 | 0.01029 |
GUESTROOM420_423 | 5696.63 | 6835.96 | 0.653 | 0.783 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 22.97 | 0.01029 |
GUESTROOM424 | 1579.20 | 1895.05 | 0.181 | 0.217 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 23.25 | 0.01029 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
CORRIDORFLR1 | 12229.91 | 14675.89 | 1.008 | 1.209 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 24.54 | 0.01029 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
CORRIDORFLR2 | 2751.04 | 3301.25 | 0.227 | 0.272 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 24.54 | 0.01029 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
CORRIDORFLR3 | 1427.42 | 1712.91 | 0.118 | 0.141 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 24.09 | 0.01029 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 | |
CORRIDORFLR4 | 2131.46 | 2557.76 | 0.176 | 0.211 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 25.00 | 0.01029 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN CLG .4% CONDNS DB=>MWB | 25.00 | 0.01029 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1450.85 | 1741.02 | 0.041 | 0.236 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -7.00 | 0.00208 |
RESTROOMFLR1 | 13.66 | 16.39 | 0.000 | 0.000 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -7.00 | 0.00208 |
MEETINGROOMFLR1 | 496.03 | 595.24 | 0.014 | 0.126 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.00 | 0.00208 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
GUESTROOM102 | 0.97 | 1.17 | 0.000 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 06:45:00 | -7.00 | 0.00208 |
GUESTROOM103 | 510.60 | 612.72 | 0.014 | 0.017 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -7.00 | 0.00208 |
GUESTROOM104 | 416.75 | 500.11 | 0.012 | 0.014 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -7.00 | 0.00208 |
GUESTROOM105 | 280.07 | 336.09 | 0.008 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | -7.00 | 0.00208 |
EMPLOYEELOUNGEFLR1 | 252.97 | 303.57 | 0.007 | 0.051 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.00 | 0.00208 |
EXERCISECENTERFLR1 | 131.28 | 157.53 | 0.004 | 0.043 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -7.00 | 0.00208 |
FRONTOFFICEFLR1 | 890.55 | 1068.66 | 0.025 | 0.056 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.00 | 0.00208 |
GUESTROOM201 | 185.15 | 222.18 | 0.005 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | -7.00 | 0.00208 |
GUESTROOM202_205 | 1104.08 | 1324.89 | 0.031 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -7.00 | 0.00208 |
GUESTROOM206_208 | 808.52 | 970.22 | 0.023 | 0.043 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
GUESTROOM209_212 | 852.96 | 1023.55 | 0.024 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.00 | 0.00208 |
GUESTROOM213 | 563.40 | 676.08 | 0.016 | 0.019 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -7.00 | 0.00208 |
GUESTROOM214 | 469.45 | 563.34 | 0.013 | 0.016 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 10:15:00 | -7.00 | 0.00208 |
GUESTROOM215_218 | 57.43 | 68.92 | 0.002 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.00 | 0.00208 |
GUESTROOM219 | 237.47 | 284.97 | 0.007 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.00 | 0.00208 |
GUESTROOM220_223 | 736.58 | 883.89 | 0.021 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -7.00 | 0.00208 |
GUESTROOM224 | 412.60 | 495.12 | 0.012 | 0.014 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.00 | 0.00208 |
GUESTROOM301 | 255.31 | 306.37 | 0.007 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 17:45:00 | -7.00 | 0.00208 |
GUESTROOM302_305 | 461.38 | 553.65 | 0.012 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -7.00 | 0.00208 |
GUESTROOM306_308 | 359.08 | 430.90 | 0.009 | 0.043 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 13:45:00 | -7.00 | 0.00208 |
GUESTROOM309_312 | 1067.76 | 1281.31 | 0.030 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:30:00 | -7.00 | 0.00208 |
GUESTROOM313 | 325.90 | 391.08 | 0.009 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 20:15:00 | -7.00 | 0.00208 |
GUESTROOM314 | 566.26 | 679.51 | 0.016 | 0.019 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 15:30:00 | -7.00 | 0.00208 |
GUESTROOM315_318 | 1125.19 | 1350.22 | 0.032 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -7.00 | 0.00208 |
GUESTROOM319 | 30.92 | 37.10 | 0.001 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 12:45:00 | -7.00 | 0.00208 |
GUESTROOM320_323 | 952.12 | 1142.55 | 0.027 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -7.00 | 0.00208 |
GUESTROOM324 | 159.80 | 191.75 | 0.004 | 0.013 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 19:45:00 | -7.00 | 0.00208 |
GUESTROOM401 | 766.52 | 919.83 | 0.022 | 0.026 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 22:15:00 | -7.00 | 0.00208 |
GUESTROOM402_405 | 1220.37 | 1464.45 | 0.032 | 0.054 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -7.00 | 0.00208 |
GUESTROOM406_408 | 1009.18 | 1211.02 | 0.026 | 0.043 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -7.00 | 0.00208 |
GUESTROOM409_412 | 1812.40 | 2174.88 | 0.051 | 0.061 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 19:45:00 | -7.00 | 0.00208 |
GUESTROOM413 | 587.01 | 704.42 | 0.015 | 0.018 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -7.00 | 0.00208 |
GUESTROOM414 | 458.89 | 550.67 | 0.012 | 0.014 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 20:15:00 | -7.00 | 0.00208 |
GUESTROOM415_418 | 1758.55 | 2110.26 | 0.050 | 0.059 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -7.00 | 0.00208 |
GUESTROOM419 | 551.84 | 662.21 | 0.016 | 0.019 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 18:15:00 | -7.00 | 0.00208 |
GUESTROOM420_423 | 1647.96 | 1977.55 | 0.046 | 0.056 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -7.00 | 0.00208 |
GUESTROOM424 | 735.56 | 882.67 | 0.021 | 0.025 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.00 | 0.00208 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
CORRIDORFLR1 | 25395.28 | 30474.34 | 0.715 | 0.858 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -7.00 | 0.00208 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
CORRIDORFLR2 | 809.52 | 971.43 | 0.023 | 0.038 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -7.00 | 0.00208 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
CORRIDORFLR3 | 1227.82 | 1473.38 | 0.035 | 0.042 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -7.00 | 0.00208 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 | |
CORRIDORFLR4 | 2204.12 | 2644.94 | 0.062 | 0.075 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -7.00 | 0.00208 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | VANCOUVER INT'L ANN HTG 99.6% CONDNS DB | -7.00 | 0.00208 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.34 | 0.34 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.93 | 0.93 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.42 | 0.42 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.74 | 0.74 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.93 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1041.25 | 7228.25 | 187.75 |
RESTROOMFLR1 | 100.75 | 7587.25 | 1.25 |
MEETINGROOMFLR1 | 1111.25 | 2955.50 | 2.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 699.50 | 8760.00 | 699.50 |
GUESTROOM104 | 203.00 | 8760.00 | 203.00 |
GUESTROOM105 | 0.00 | 8604.00 | 0.00 |
EMPLOYEELOUNGEFLR1 | 3133.75 | 2137.00 | 244.75 |
EXERCISECENTERFLR1 | 1118.75 | 2988.25 | 1.00 |
FRONTOFFICEFLR1 | 546.50 | 6393.75 | 11.75 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 233.25 | 8645.75 | 233.25 |
GUESTROOM206_208 | 170.50 | 8613.75 | 170.50 |
GUESTROOM209_212 | 124.50 | 8685.25 | 124.50 |
GUESTROOM213 | 800.50 | 8754.50 | 800.50 |
GUESTROOM214 | 154.75 | 8658.25 | 154.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3515.25 | 3997.00 | 35.75 |
GUESTROOM220_223 | 25.75 | 8364.75 | 25.75 |
GUESTROOM224 | 180.25 | 8576.50 | 180.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 248.25 | 8688.25 | 248.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 609.25 | 8682.00 | 609.25 |
GUESTROOM315_318 | 34.50 | 8255.75 | 34.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 148.25 | 8511.25 | 148.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 2899.00 | 8383.00 | 2887.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1013.25 | 8126.00 | 868.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 795.00 | 7893.00 | 489.75 |
GUESTROOM419 | 609.00 | 8074.75 | 582.00 |
GUESTROOM420_423 | 833.00 | 7924.75 | 562.00 |
GUESTROOM424 | 1456.50 | 8152.25 | 1441.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6381.25 | 8760.00 | 4798.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 500.50 | 0.00 | 500.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 7.75 | 30.25 | 7.75 | 30.25 |
GUESTROOM104 | 1.50 | 33.50 | 1.50 | 33.50 |
GUESTROOM105 | 0.00 | 47.75 | 0.00 | 47.75 |
EMPLOYEELOUNGEFLR1 | 143.25 | 1184.00 | 130.75 | 852.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1.50 | 19.50 | 1.50 | 19.50 |
GUESTROOM206_208 | 0.75 | 31.00 | 0.75 | 31.00 |
GUESTROOM209_212 | 0.50 | 18.50 | 0.50 | 18.50 |
GUESTROOM213 | 10.25 | 18.25 | 10.25 | 18.25 |
GUESTROOM214 | 0.75 | 18.00 | 0.75 | 18.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2178.50 | 0.00 | 2178.50 |
GUESTROOM220_223 | 0.00 | 13.50 | 0.00 | 13.50 |
GUESTROOM224 | 1.00 | 18.50 | 1.00 | 18.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 3.50 | 19.00 | 3.50 | 19.00 |
GUESTROOM313 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 6.75 | 16.00 | 6.75 | 16.00 |
GUESTROOM315_318 | 0.00 | 17.50 | 0.00 | 17.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1.25 | 12.00 | 1.25 | 12.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 28.25 | 25.50 | 28.25 | 25.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 12.00 | 28.25 | 12.00 | 28.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 9.00 | 22.75 | 9.00 | 22.75 |
GUESTROOM419 | 9.00 | 26.25 | 9.00 | 26.25 |
GUESTROOM420_423 | 11.50 | 22.25 | 11.50 | 22.25 |
GUESTROOM424 | 17.00 | 23.25 | 17.00 | 23.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 1824.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 177.00 | 3952.50 | 163.00 | 3285.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:45:03
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.340457 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.930445 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.743232 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR1 PTAC HEATING COIL | 32075.38 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 514.67 |
102 PTAC HEATING COIL | 942.95 |
103 PTAC HEATING COIL | 1077.76 |
104 PTAC HEATING COIL | 965.11 |
105 PTAC HEATING COIL | 942.88 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR2 PTAC HEATING COIL | 2674.25 |
201 PTAC HEATING COIL | 942.95 |
202_205 PTAC HEATING COIL | 3771.78 |
206_208 PTAC HEATING COIL | 2989.27 |
209_212 PTAC HEATING COIL | 3771.78 |
213 PTAC HEATING COIL | 1141.12 |
214 PTAC HEATING COIL | 1028.34 |
215_218 PTAC HEATING COIL | 3771.52 |
219 PTAC HEATING COIL | 942.88 |
220_223 PTAC HEATING COIL | 3771.52 |
224 PTAC HEATING COIL | 960.12 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR3 PTAC HEATING COIL | 2792.21 |
301 PTAC HEATING COIL | 942.95 |
302_305 PTAC HEATING COIL | 3771.78 |
306_308 PTAC HEATING COIL | 2989.27 |
309_312 PTAC HEATING COIL | 3771.78 |
313 PTAC HEATING COIL | 942.95 |
314 PTAC HEATING COIL | 1144.51 |
315_318 PTAC HEATING COIL | 3771.52 |
319 PTAC HEATING COIL | 942.88 |
320_323 PTAC HEATING COIL | 3771.52 |
324 PTAC HEATING COIL | 942.88 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR4 PTAC HEATING COIL | 3963.76 |
401 PTAC HEATING COIL | 1384.87 |
402_405 PTAC HEATING COIL | 3771.78 |
406_408 PTAC HEATING COIL | 2989.27 |
409_412 PTAC HEATING COIL | 4035.03 |
413 PTAC HEATING COIL | 1132.70 |
414 PTAC HEATING COIL | 978.92 |
415_418 PTAC HEATING COIL | 3970.28 |
419 PTAC HEATING COIL | 1127.21 |
420_423 PTAC HEATING COIL | 3837.57 |
424 PTAC HEATING COIL | 1347.67 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.28 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.798299 | 0.340457 | 5641.25 |
SAC_FRONTLOUNGE COOLING COIL | 0.767965 | 0.930445 | 16804.97 |
SAC_MEETINGROOM COOLING COIL | 0.738980 | 0.417624 | 8252.66 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.798374 | 0.743232 | 12312.54 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.930445 |
RESTROOMFLR1 DIRECT AIR | 0.058585 |
MEETINGROOMFLR1 DIRECT AIR | 0.417624 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.558106 |
EXERCISECENTERFLR1 DIRECT AIR | 0.126542 |
FRONTOFFICEFLR1 DIRECT AIR | 0.340457 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.340457 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.930445 |
SAC_MEETINGROOM MAIN BRANCH | 0.417624 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.743232 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.340457 |
SAC_FRONTLOUNGE | 0.930445 |
SAC_MEETINGROOM | 0.417624 |
SAC_EXC_EMPLGE_RESTRM | 0.743232 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.340457 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.930445 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.417624 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.743232 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.340457 | 0.340457 | 0.340457 | 0.340457 | 3882.63 | 5641.25 | 1.00 |
SAC_FRONTLOUNGE | 0.930445 | 0.930445 | 0.930445 | 0.930445 | 16273.98 | 16804.97 | 1.00 |
SAC_MEETINGROOM | 0.417624 | 0.417624 | 0.417624 | 0.417624 | 8714.59 | 8252.66 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.743232 | 0.743232 | 0.743232 | 0.743232 | 6525.28 | 12312.54 | 0.170259 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3882.63 |
SAC_FRONTLOUNGE HEATING COIL | 16273.98 |
SAC_MEETINGROOM HEATING COIL | 8714.59 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 6525.28 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.417624 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.27 | 3.20 |
February | 19.33 | 5.10 |
March | 19.15 | 6.09 |
April | 20.36 | 8.68 |
May | 21.27 | 11.83 |
June | 22.33 | 15.06 |
July | 23.02 | 16.98 |
August | 22.92 | 17.08 |
September | 21.86 | 13.78 |
October | 20.19 | 9.83 |
November | 18.80 | 5.28 |
December | 17.46 | 3.63 |
Annual Sum or Average | 20.42 | 9.74 |
Minimum of Months | 17.46 | 3.20 |
Maximum of Months | 23.02 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 3.20 |
February | 22.75 | 5.10 |
March | 22.83 | 6.09 |
April | 23.36 | 8.68 |
May | 23.75 | 11.83 |
June | 24.28 | 15.06 |
July | 24.78 | 16.98 |
August | 24.70 | 17.08 |
September | 24.05 | 13.78 |
October | 23.37 | 9.83 |
November | 22.65 | 5.28 |
December | 22.13 | 3.63 |
Annual Sum or Average | 23.41 | 9.74 |
Minimum of Months | 22.13 | 3.20 |
Maximum of Months | 24.78 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.36 | 3.20 |
February | 18.40 | 5.10 |
March | 18.29 | 6.09 |
April | 19.50 | 8.68 |
May | 20.49 | 11.83 |
June | 21.59 | 15.06 |
July | 22.34 | 16.98 |
August | 22.20 | 17.08 |
September | 21.09 | 13.78 |
October | 19.31 | 9.83 |
November | 17.91 | 5.28 |
December | 16.63 | 3.63 |
Annual Sum or Average | 19.60 | 9.74 |
Minimum of Months | 16.63 | 3.20 |
Maximum of Months | 22.34 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | 3.20 |
February | 21.16 | 5.10 |
March | 21.28 | 6.09 |
April | 21.59 | 8.68 |
May | 22.19 | 11.83 |
June | 22.81 | 15.06 |
July | 23.11 | 16.98 |
August | 23.10 | 17.08 |
September | 22.44 | 13.78 |
October | 21.53 | 9.83 |
November | 21.20 | 5.28 |
December | 21.15 | 3.63 |
Annual Sum or Average | 21.90 | 9.74 |
Minimum of Months | 21.13 | 3.20 |
Maximum of Months | 23.11 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 3.20 |
February | 22.30 | 5.10 |
March | 22.40 | 6.09 |
April | 22.71 | 8.68 |
May | 23.09 | 11.83 |
June | 23.43 | 15.06 |
July | 23.61 | 16.98 |
August | 23.57 | 17.08 |
September | 23.25 | 13.78 |
October | 22.72 | 9.83 |
November | 22.29 | 5.28 |
December | 22.07 | 3.63 |
Annual Sum or Average | 22.80 | 9.74 |
Minimum of Months | 22.07 | 3.20 |
Maximum of Months | 23.61 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 3.20 |
February | 21.87 | 5.10 |
March | 22.15 | 6.09 |
April | 22.79 | 8.68 |
May | 23.38 | 11.83 |
June | 23.70 | 15.06 |
July | 23.79 | 16.98 |
August | 23.77 | 17.08 |
September | 23.50 | 13.78 |
October | 22.74 | 9.83 |
November | 21.91 | 5.28 |
December | 21.47 | 3.63 |
Annual Sum or Average | 22.72 | 9.74 |
Minimum of Months | 21.47 | 3.20 |
Maximum of Months | 23.79 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.20 | 3.20 |
February | 24.61 | 5.10 |
March | 24.78 | 6.09 |
April | 25.37 | 8.68 |
May | 25.90 | 11.83 |
June | 26.29 | 15.06 |
July | 26.56 | 16.98 |
August | 26.43 | 17.08 |
September | 26.00 | 13.78 |
October | 25.22 | 9.83 |
November | 24.54 | 5.28 |
December | 24.12 | 3.63 |
Annual Sum or Average | 25.34 | 9.74 |
Minimum of Months | 24.12 | 3.20 |
Maximum of Months | 26.56 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.44 | 3.20 |
February | 20.02 | 5.10 |
March | 20.33 | 6.09 |
April | 21.21 | 8.68 |
May | 22.05 | 11.83 |
June | 22.70 | 15.06 |
July | 22.97 | 16.98 |
August | 22.96 | 17.08 |
September | 22.31 | 13.78 |
October | 21.10 | 9.83 |
November | 20.00 | 5.28 |
December | 19.43 | 3.63 |
Annual Sum or Average | 21.22 | 9.74 |
Minimum of Months | 19.43 | 3.20 |
Maximum of Months | 22.97 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.15 | 3.20 |
February | 19.66 | 5.10 |
March | 19.96 | 6.09 |
April | 20.84 | 8.68 |
May | 21.70 | 11.83 |
June | 22.41 | 15.06 |
July | 22.74 | 16.98 |
August | 22.72 | 17.08 |
September | 21.99 | 13.78 |
October | 20.72 | 9.83 |
November | 19.70 | 5.28 |
December | 19.16 | 3.63 |
Annual Sum or Average | 20.90 | 9.74 |
Minimum of Months | 19.15 | 3.20 |
Maximum of Months | 22.74 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | 3.20 |
February | 20.94 | 5.10 |
March | 20.99 | 6.09 |
April | 21.23 | 8.68 |
May | 21.47 | 11.83 |
June | 21.66 | 15.06 |
July | 21.72 | 16.98 |
August | 21.73 | 17.08 |
September | 21.58 | 13.78 |
October | 21.23 | 9.83 |
November | 20.91 | 5.28 |
December | 20.72 | 3.63 |
Annual Sum or Average | 21.24 | 9.74 |
Minimum of Months | 20.72 | 3.20 |
Maximum of Months | 21.73 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.94 | 3.20 |
February | 21.15 | 5.10 |
March | 21.21 | 6.09 |
April | 21.45 | 8.68 |
May | 21.64 | 11.83 |
June | 21.72 | 15.06 |
July | 21.74 | 16.98 |
August | 21.75 | 17.08 |
September | 21.68 | 13.78 |
October | 21.43 | 9.83 |
November | 21.09 | 5.28 |
December | 20.91 | 3.63 |
Annual Sum or Average | 21.39 | 9.74 |
Minimum of Months | 20.91 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 3.20 |
February | 21.53 | 5.10 |
March | 21.56 | 6.09 |
April | 21.68 | 8.68 |
May | 21.74 | 11.83 |
June | 21.75 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.74 | 13.78 |
October | 21.68 | 9.83 |
November | 21.48 | 5.28 |
December | 21.35 | 3.63 |
Annual Sum or Average | 21.61 | 9.74 |
Minimum of Months | 21.35 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 3.20 |
February | 22.51 | 5.10 |
March | 22.53 | 6.09 |
April | 22.49 | 8.68 |
May | 22.61 | 11.83 |
June | 22.70 | 15.06 |
July | 22.62 | 16.98 |
August | 22.72 | 17.08 |
September | 22.73 | 13.78 |
October | 22.73 | 9.83 |
November | 22.58 | 5.28 |
December | 22.58 | 3.63 |
Annual Sum or Average | 22.61 | 9.74 |
Minimum of Months | 22.49 | 3.20 |
Maximum of Months | 22.73 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 50.69 | 3.20 |
February | 51.09 | 5.10 |
March | 51.15 | 6.09 |
April | 51.70 | 8.68 |
May | 52.13 | 11.83 |
June | 52.55 | 15.06 |
July | 52.81 | 16.98 |
August | 52.69 | 17.08 |
September | 52.20 | 13.78 |
October | 51.52 | 9.83 |
November | 50.93 | 5.28 |
December | 50.48 | 3.63 |
Annual Sum or Average | 51.67 | 9.74 |
Minimum of Months | 50.48 | 3.20 |
Maximum of Months | 52.81 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.78 | 3.20 |
February | 69.32 | 5.10 |
March | 69.24 | 6.09 |
April | 69.85 | 8.68 |
May | 70.28 | 11.83 |
June | 70.86 | 15.06 |
July | 71.19 | 16.98 |
August | 71.03 | 17.08 |
September | 70.38 | 13.78 |
October | 69.69 | 9.83 |
November | 69.03 | 5.28 |
December | 68.30 | 3.63 |
Annual Sum or Average | 69.83 | 9.74 |
Minimum of Months | 68.30 | 3.20 |
Maximum of Months | 71.19 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.90 | 3.20 |
February | 23.04 | 5.10 |
March | 23.10 | 6.09 |
April | 23.29 | 8.68 |
May | 23.55 | 11.83 |
June | 23.76 | 15.06 |
July | 23.83 | 16.98 |
August | 23.85 | 17.08 |
September | 23.68 | 13.78 |
October | 23.41 | 9.83 |
November | 23.06 | 5.28 |
December | 22.90 | 3.63 |
Annual Sum or Average | 23.37 | 9.74 |
Minimum of Months | 22.90 | 3.20 |
Maximum of Months | 23.85 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | 3.20 |
February | 22.51 | 5.10 |
March | 22.66 | 6.09 |
April | 23.16 | 8.68 |
May | 23.61 | 11.83 |
June | 23.84 | 15.06 |
July | 23.88 | 16.98 |
August | 23.89 | 17.08 |
September | 23.73 | 13.78 |
October | 23.31 | 9.83 |
November | 22.51 | 5.28 |
December | 22.06 | 3.63 |
Annual Sum or Average | 23.11 | 9.74 |
Minimum of Months | 22.06 | 3.20 |
Maximum of Months | 23.89 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.71 | 3.20 |
February | 18.71 | 5.10 |
March | 18.58 | 6.09 |
April | 19.88 | 8.68 |
May | 21.12 | 11.83 |
June | 22.48 | 15.06 |
July | 23.21 | 16.98 |
August | 23.02 | 17.08 |
September | 21.62 | 13.78 |
October | 19.85 | 9.83 |
November | 18.29 | 5.28 |
December | 16.83 | 3.63 |
Annual Sum or Average | 20.11 | 9.74 |
Minimum of Months | 16.83 | 3.20 |
Maximum of Months | 23.21 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.25 | 3.20 |
February | 20.93 | 5.10 |
March | 20.96 | 6.09 |
April | 21.88 | 8.68 |
May | 22.71 | 11.83 |
June | 23.49 | 15.06 |
July | 23.93 | 16.98 |
August | 23.82 | 17.08 |
September | 23.00 | 13.78 |
October | 21.84 | 9.83 |
November | 20.72 | 5.28 |
December | 19.81 | 3.63 |
Annual Sum or Average | 21.95 | 9.74 |
Minimum of Months | 19.81 | 3.20 |
Maximum of Months | 23.93 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.76 | 3.20 |
February | 19.10 | 5.10 |
March | 18.89 | 6.09 |
April | 20.43 | 8.68 |
May | 21.61 | 11.83 |
June | 22.90 | 15.06 |
July | 23.71 | 16.98 |
August | 23.57 | 17.08 |
September | 22.26 | 13.78 |
October | 20.16 | 9.83 |
November | 18.39 | 5.28 |
December | 16.71 | 3.63 |
Annual Sum or Average | 20.46 | 9.74 |
Minimum of Months | 16.71 | 3.20 |
Maximum of Months | 23.71 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 3.20 |
February | 22.08 | 5.10 |
March | 22.27 | 6.09 |
April | 23.03 | 8.68 |
May | 23.63 | 11.83 |
June | 23.86 | 15.06 |
July | 23.89 | 16.98 |
August | 23.89 | 17.08 |
September | 23.71 | 13.78 |
October | 22.97 | 9.83 |
November | 21.99 | 5.28 |
December | 21.42 | 3.63 |
Annual Sum or Average | 22.86 | 9.74 |
Minimum of Months | 21.42 | 3.20 |
Maximum of Months | 23.89 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.31 | 3.20 |
February | 17.60 | 5.10 |
March | 17.50 | 6.09 |
April | 19.07 | 8.68 |
May | 20.41 | 11.83 |
June | 21.80 | 15.06 |
July | 22.70 | 16.98 |
August | 22.51 | 17.08 |
September | 21.11 | 13.78 |
October | 18.76 | 9.83 |
November | 16.95 | 5.28 |
December | 15.39 | 3.63 |
Annual Sum or Average | 19.18 | 9.74 |
Minimum of Months | 15.39 | 3.20 |
Maximum of Months | 22.70 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | 3.20 |
February | 19.02 | 5.10 |
March | 19.44 | 6.09 |
April | 20.33 | 8.68 |
May | 21.73 | 11.83 |
June | 22.74 | 15.06 |
July | 23.06 | 16.98 |
August | 23.04 | 17.08 |
September | 22.00 | 13.78 |
October | 19.98 | 9.83 |
November | 19.11 | 5.28 |
December | 18.90 | 3.63 |
Annual Sum or Average | 20.70 | 9.74 |
Minimum of Months | 18.90 | 3.20 |
Maximum of Months | 23.06 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | 3.20 |
February | 21.08 | 5.10 |
March | 21.16 | 6.09 |
April | 21.40 | 8.68 |
May | 21.67 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.69 | 13.78 |
October | 21.38 | 9.83 |
November | 21.03 | 5.28 |
December | 20.87 | 3.63 |
Annual Sum or Average | 21.37 | 9.74 |
Minimum of Months | 20.87 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.94 | 3.20 |
February | 21.15 | 5.10 |
March | 21.23 | 6.09 |
April | 21.47 | 8.68 |
May | 21.69 | 11.83 |
June | 21.75 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.70 | 13.78 |
October | 21.45 | 9.83 |
November | 21.10 | 5.28 |
December | 20.93 | 3.63 |
Annual Sum or Average | 21.41 | 9.74 |
Minimum of Months | 20.93 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 3.20 |
February | 21.19 | 5.10 |
March | 21.26 | 6.09 |
April | 21.48 | 8.68 |
May | 21.69 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.70 | 13.78 |
October | 21.49 | 9.83 |
November | 21.14 | 5.28 |
December | 20.96 | 3.63 |
Annual Sum or Average | 21.43 | 9.74 |
Minimum of Months | 20.96 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.71 | 3.20 |
February | 20.93 | 5.10 |
March | 20.99 | 6.09 |
April | 21.27 | 8.68 |
May | 21.55 | 11.83 |
June | 21.72 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.63 | 13.78 |
October | 21.24 | 9.83 |
November | 20.88 | 5.28 |
December | 20.68 | 3.63 |
Annual Sum or Average | 21.26 | 9.74 |
Minimum of Months | 20.68 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.00 | 3.20 |
February | 21.24 | 5.10 |
March | 21.30 | 6.09 |
April | 21.55 | 8.68 |
May | 21.71 | 11.83 |
June | 21.75 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.72 | 13.78 |
October | 21.52 | 9.83 |
November | 21.16 | 5.28 |
December | 20.95 | 3.63 |
Annual Sum or Average | 21.45 | 9.74 |
Minimum of Months | 20.95 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.97 | 3.20 |
February | 23.16 | 5.10 |
March | 23.17 | 6.09 |
April | 23.30 | 8.68 |
May | 23.33 | 11.83 |
June | 23.33 | 15.06 |
July | 23.33 | 16.98 |
August | 23.33 | 17.08 |
September | 23.33 | 13.78 |
October | 23.31 | 9.83 |
November | 23.07 | 5.28 |
December | 22.94 | 3.63 |
Annual Sum or Average | 23.22 | 9.74 |
Minimum of Months | 22.94 | 3.20 |
Maximum of Months | 23.33 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 30.40 | 3.20 |
February | 30.96 | 5.10 |
March | 30.99 | 6.09 |
April | 31.75 | 8.68 |
May | 32.36 | 11.83 |
June | 32.90 | 15.06 |
July | 33.17 | 16.98 |
August | 33.07 | 17.08 |
September | 32.47 | 13.78 |
October | 31.56 | 9.83 |
November | 30.71 | 5.28 |
December | 30.02 | 3.63 |
Annual Sum or Average | 31.70 | 9.74 |
Minimum of Months | 30.02 | 3.20 |
Maximum of Months | 33.17 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.78 | 3.20 |
February | 21.84 | 5.10 |
March | 21.92 | 6.09 |
April | 22.10 | 8.68 |
May | 22.30 | 11.83 |
June | 22.49 | 15.06 |
July | 22.63 | 16.98 |
August | 22.61 | 17.08 |
September | 22.39 | 13.78 |
October | 22.07 | 9.83 |
November | 21.87 | 5.28 |
December | 21.77 | 3.63 |
Annual Sum or Average | 22.15 | 9.74 |
Minimum of Months | 21.77 | 3.20 |
Maximum of Months | 22.63 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 3.20 |
February | 21.34 | 5.10 |
March | 21.41 | 6.09 |
April | 21.62 | 8.68 |
May | 21.74 | 11.83 |
June | 21.75 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.73 | 13.78 |
October | 21.61 | 9.83 |
November | 21.29 | 5.28 |
December | 21.10 | 3.63 |
Annual Sum or Average | 21.52 | 9.74 |
Minimum of Months | 21.10 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | 3.20 |
February | 21.20 | 5.10 |
March | 21.28 | 6.09 |
April | 21.55 | 8.68 |
May | 21.72 | 11.83 |
June | 21.75 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.72 | 13.78 |
October | 21.52 | 9.83 |
November | 21.14 | 5.28 |
December | 20.93 | 3.63 |
Annual Sum or Average | 21.44 | 9.74 |
Minimum of Months | 20.93 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.27 | 3.20 |
February | 20.15 | 5.10 |
March | 20.19 | 6.09 |
April | 21.42 | 8.68 |
May | 22.57 | 11.83 |
June | 23.61 | 15.06 |
July | 24.15 | 16.98 |
August | 24.00 | 17.08 |
September | 22.88 | 13.78 |
October | 21.29 | 9.83 |
November | 19.82 | 5.28 |
December | 18.63 | 3.63 |
Annual Sum or Average | 21.50 | 9.74 |
Minimum of Months | 18.63 | 3.20 |
Maximum of Months | 24.15 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.62 | 3.20 |
February | 17.94 | 5.10 |
March | 17.82 | 6.09 |
April | 19.55 | 8.68 |
May | 21.24 | 11.83 |
June | 23.00 | 15.06 |
July | 23.89 | 16.98 |
August | 23.60 | 17.08 |
September | 21.79 | 13.78 |
October | 19.44 | 9.83 |
November | 17.36 | 5.28 |
December | 15.47 | 3.63 |
Annual Sum or Average | 19.82 | 9.74 |
Minimum of Months | 15.47 | 3.20 |
Maximum of Months | 23.89 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.90 | 3.20 |
February | 18.32 | 5.10 |
March | 18.18 | 6.09 |
April | 19.89 | 8.68 |
May | 21.32 | 11.83 |
June | 22.82 | 15.06 |
July | 23.72 | 16.98 |
August | 23.55 | 17.08 |
September | 22.01 | 13.78 |
October | 19.54 | 9.83 |
November | 17.57 | 5.28 |
December | 15.83 | 3.63 |
Annual Sum or Average | 19.98 | 9.74 |
Minimum of Months | 15.83 | 3.20 |
Maximum of Months | 23.72 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 3.20 |
February | 21.13 | 5.10 |
March | 21.37 | 6.09 |
April | 21.90 | 8.68 |
May | 22.84 | 11.83 |
June | 23.54 | 15.06 |
July | 23.75 | 16.98 |
August | 23.75 | 17.08 |
September | 23.07 | 13.78 |
October | 21.66 | 9.83 |
November | 21.15 | 5.28 |
December | 21.11 | 3.63 |
Annual Sum or Average | 22.21 | 9.74 |
Minimum of Months | 21.11 | 3.20 |
Maximum of Months | 23.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.10 | 3.20 |
February | 16.44 | 5.10 |
March | 16.46 | 6.09 |
April | 18.24 | 8.68 |
May | 19.94 | 11.83 |
June | 21.66 | 15.06 |
July | 22.70 | 16.98 |
August | 22.47 | 17.08 |
September | 20.71 | 13.78 |
October | 17.81 | 9.83 |
November | 15.78 | 5.28 |
December | 14.19 | 3.63 |
Annual Sum or Average | 18.47 | 9.74 |
Minimum of Months | 14.19 | 3.20 |
Maximum of Months | 22.70 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 3.20 |
February | 18.89 | 5.10 |
March | 19.12 | 6.09 |
April | 19.70 | 8.68 |
May | 21.15 | 11.83 |
June | 22.42 | 15.06 |
July | 22.86 | 16.98 |
August | 22.81 | 17.08 |
September | 21.48 | 13.78 |
October | 19.29 | 9.83 |
November | 18.90 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.37 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 22.86 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 3.20 |
February | 18.92 | 5.10 |
March | 19.29 | 6.09 |
April | 20.13 | 8.68 |
May | 21.60 | 11.83 |
June | 22.68 | 15.06 |
July | 23.04 | 16.98 |
August | 23.02 | 17.08 |
September | 21.87 | 13.78 |
October | 19.64 | 9.83 |
November | 18.95 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.59 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 23.04 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 3.20 |
February | 18.97 | 5.10 |
March | 19.42 | 6.09 |
April | 20.40 | 8.68 |
May | 21.78 | 11.83 |
June | 22.73 | 15.06 |
July | 23.06 | 16.98 |
August | 23.02 | 17.08 |
September | 21.98 | 13.78 |
October | 19.85 | 9.83 |
November | 19.02 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.68 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 23.06 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.87 | 3.20 |
February | 21.08 | 5.10 |
March | 21.16 | 6.09 |
April | 21.40 | 8.68 |
May | 21.64 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.67 | 13.78 |
October | 21.38 | 9.83 |
November | 21.03 | 5.28 |
December | 20.86 | 3.63 |
Annual Sum or Average | 21.36 | 9.74 |
Minimum of Months | 20.86 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 3.20 |
February | 18.95 | 5.10 |
March | 19.34 | 6.09 |
April | 20.16 | 8.68 |
May | 21.48 | 11.83 |
June | 22.53 | 15.06 |
July | 22.95 | 16.98 |
August | 22.92 | 17.08 |
September | 21.84 | 13.78 |
October | 19.77 | 9.83 |
November | 19.00 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.57 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 22.95 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 3.20 |
February | 21.03 | 5.10 |
March | 21.10 | 6.09 |
April | 21.41 | 8.68 |
May | 21.65 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.67 | 13.78 |
October | 21.36 | 9.83 |
November | 20.95 | 5.28 |
December | 20.74 | 3.63 |
Annual Sum or Average | 21.33 | 9.74 |
Minimum of Months | 20.74 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.14 | 3.20 |
February | 21.37 | 5.10 |
March | 21.43 | 6.09 |
April | 21.63 | 8.68 |
May | 21.74 | 11.83 |
June | 21.75 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.73 | 13.78 |
October | 21.62 | 9.83 |
November | 21.29 | 5.28 |
December | 21.12 | 3.63 |
Annual Sum or Average | 21.53 | 9.74 |
Minimum of Months | 21.12 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 3.20 |
February | 22.61 | 5.10 |
March | 22.73 | 6.09 |
April | 23.72 | 8.68 |
May | 24.62 | 11.83 |
June | 25.34 | 15.06 |
July | 25.68 | 16.98 |
August | 25.58 | 17.08 |
September | 24.78 | 13.78 |
October | 23.42 | 9.83 |
November | 22.32 | 5.28 |
December | 21.59 | 3.63 |
Annual Sum or Average | 23.70 | 9.74 |
Minimum of Months | 21.59 | 3.20 |
Maximum of Months | 25.68 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | 3.20 |
February | 21.18 | 5.10 |
March | 21.49 | 6.09 |
April | 22.41 | 8.68 |
May | 23.10 | 11.83 |
June | 23.31 | 15.06 |
July | 23.33 | 16.98 |
August | 23.33 | 17.08 |
September | 23.14 | 13.78 |
October | 22.31 | 9.83 |
November | 21.00 | 5.28 |
December | 20.36 | 3.63 |
Annual Sum or Average | 22.12 | 9.74 |
Minimum of Months | 20.36 | 3.20 |
Maximum of Months | 23.33 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | 3.20 |
February | 21.20 | 5.10 |
March | 21.29 | 6.09 |
April | 21.54 | 8.68 |
May | 21.71 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.71 | 13.78 |
October | 21.50 | 9.83 |
November | 21.13 | 5.28 |
December | 20.95 | 3.63 |
Annual Sum or Average | 21.44 | 9.74 |
Minimum of Months | 20.95 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.97 | 3.20 |
February | 19.36 | 5.10 |
March | 19.76 | 6.09 |
April | 20.90 | 8.68 |
May | 22.10 | 11.83 |
June | 22.87 | 15.06 |
July | 23.10 | 16.98 |
August | 23.12 | 17.08 |
September | 22.34 | 13.78 |
October | 20.70 | 9.83 |
November | 19.50 | 5.28 |
December | 18.95 | 3.63 |
Annual Sum or Average | 20.98 | 9.74 |
Minimum of Months | 18.95 | 3.20 |
Maximum of Months | 23.12 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.03 | 3.20 |
February | 19.01 | 5.10 |
March | 19.16 | 6.09 |
April | 20.67 | 8.68 |
May | 22.18 | 11.83 |
June | 23.51 | 15.06 |
July | 24.17 | 16.98 |
August | 23.97 | 17.08 |
September | 22.53 | 13.78 |
October | 20.43 | 9.83 |
November | 18.67 | 5.28 |
December | 17.37 | 3.63 |
Annual Sum or Average | 20.82 | 9.74 |
Minimum of Months | 17.37 | 3.20 |
Maximum of Months | 24.17 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.59 | 3.20 |
February | 17.01 | 5.10 |
March | 16.98 | 6.09 |
April | 18.93 | 8.68 |
May | 20.91 | 11.83 |
June | 22.93 | 15.06 |
July | 23.92 | 16.98 |
August | 23.59 | 17.08 |
September | 21.50 | 13.78 |
October | 18.75 | 9.83 |
November | 16.39 | 5.28 |
December | 14.40 | 3.63 |
Annual Sum or Average | 19.25 | 9.74 |
Minimum of Months | 14.40 | 3.20 |
Maximum of Months | 23.92 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.51 | 3.20 |
February | 17.01 | 5.10 |
March | 17.09 | 6.09 |
April | 19.05 | 8.68 |
May | 20.83 | 11.83 |
June | 22.66 | 15.06 |
July | 23.69 | 16.98 |
August | 23.40 | 17.08 |
September | 21.49 | 13.78 |
October | 18.53 | 9.83 |
November | 16.26 | 5.28 |
December | 14.56 | 3.63 |
Annual Sum or Average | 19.18 | 9.74 |
Minimum of Months | 14.56 | 3.20 |
Maximum of Months | 23.69 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 3.20 |
February | 21.13 | 5.10 |
March | 21.30 | 6.09 |
April | 21.73 | 8.68 |
May | 22.38 | 11.83 |
June | 23.03 | 15.06 |
July | 23.28 | 16.98 |
August | 23.26 | 17.08 |
September | 22.51 | 13.78 |
October | 21.39 | 9.83 |
November | 21.12 | 5.28 |
December | 21.11 | 3.63 |
Annual Sum or Average | 21.95 | 9.74 |
Minimum of Months | 21.11 | 3.20 |
Maximum of Months | 23.28 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.13 | 3.20 |
February | 15.56 | 5.10 |
March | 15.73 | 6.09 |
April | 17.66 | 8.68 |
May | 19.55 | 11.83 |
June | 21.50 | 15.06 |
July | 22.66 | 16.98 |
August | 22.30 | 17.08 |
September | 20.26 | 13.78 |
October | 17.08 | 9.83 |
November | 14.87 | 5.28 |
December | 13.32 | 3.63 |
Annual Sum or Average | 17.90 | 9.74 |
Minimum of Months | 13.32 | 3.20 |
Maximum of Months | 22.66 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | 3.20 |
February | 20.57 | 5.10 |
March | 20.69 | 6.09 |
April | 21.00 | 8.68 |
May | 21.43 | 11.83 |
June | 21.68 | 15.06 |
July | 21.73 | 16.98 |
August | 21.73 | 17.08 |
September | 21.48 | 13.78 |
October | 20.87 | 9.83 |
November | 20.58 | 5.28 |
December | 20.49 | 3.63 |
Annual Sum or Average | 21.06 | 9.74 |
Minimum of Months | 20.49 | 3.20 |
Maximum of Months | 21.73 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 3.20 |
February | 18.92 | 5.10 |
March | 19.19 | 6.09 |
April | 19.89 | 8.68 |
May | 21.04 | 11.83 |
June | 22.18 | 15.06 |
July | 22.58 | 16.98 |
August | 22.54 | 17.08 |
September | 21.26 | 13.78 |
October | 19.28 | 9.83 |
November | 18.91 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.31 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 22.58 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 3.20 |
February | 18.95 | 5.10 |
March | 19.26 | 6.09 |
April | 20.01 | 8.68 |
May | 21.14 | 11.83 |
June | 22.21 | 15.06 |
July | 22.59 | 16.98 |
August | 22.54 | 17.08 |
September | 21.31 | 13.78 |
October | 19.36 | 9.83 |
November | 18.92 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.35 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 22.59 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | 3.20 |
February | 20.98 | 5.10 |
March | 21.10 | 6.09 |
April | 21.41 | 8.68 |
May | 21.66 | 11.83 |
June | 21.73 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.66 | 13.78 |
October | 21.32 | 9.83 |
November | 20.90 | 5.28 |
December | 20.69 | 3.63 |
Annual Sum or Average | 21.30 | 9.74 |
Minimum of Months | 20.69 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 3.20 |
February | 18.93 | 5.10 |
March | 19.24 | 6.09 |
April | 19.92 | 8.68 |
May | 21.04 | 11.83 |
June | 22.14 | 15.06 |
July | 22.57 | 16.98 |
August | 22.52 | 17.08 |
September | 21.33 | 13.78 |
October | 19.40 | 9.83 |
November | 18.92 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.33 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 22.57 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 3.20 |
February | 19.04 | 5.10 |
March | 19.47 | 6.09 |
April | 20.35 | 8.68 |
May | 21.52 | 11.83 |
June | 22.44 | 15.06 |
July | 22.75 | 16.98 |
August | 22.75 | 17.08 |
September | 21.77 | 13.78 |
October | 19.92 | 9.83 |
November | 19.05 | 5.28 |
December | 18.89 | 3.63 |
Annual Sum or Average | 20.58 | 9.74 |
Minimum of Months | 18.89 | 3.20 |
Maximum of Months | 22.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | 3.20 |
February | 21.16 | 5.10 |
March | 21.28 | 6.09 |
April | 21.55 | 8.68 |
May | 21.70 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.70 | 13.78 |
October | 21.47 | 9.83 |
November | 21.03 | 5.28 |
December | 20.81 | 3.63 |
Annual Sum or Average | 21.40 | 9.74 |
Minimum of Months | 20.81 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 3.20 |
February | 20.33 | 5.10 |
March | 20.59 | 6.09 |
April | 21.67 | 8.68 |
May | 22.68 | 11.83 |
June | 23.54 | 15.06 |
July | 23.97 | 16.98 |
August | 23.79 | 17.08 |
September | 22.77 | 13.78 |
October | 21.22 | 9.83 |
November | 20.03 | 5.28 |
December | 19.36 | 3.63 |
Annual Sum or Average | 21.64 | 9.74 |
Minimum of Months | 19.36 | 3.20 |
Maximum of Months | 23.97 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 3.20 |
February | 21.11 | 5.10 |
March | 21.23 | 6.09 |
April | 21.54 | 8.68 |
May | 21.70 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.70 | 13.78 |
October | 21.45 | 9.83 |
November | 21.00 | 5.28 |
December | 20.77 | 3.63 |
Annual Sum or Average | 21.38 | 9.74 |
Minimum of Months | 20.77 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 3.20 |
February | 21.12 | 5.10 |
March | 21.25 | 6.09 |
April | 21.54 | 8.68 |
May | 21.70 | 11.83 |
June | 21.74 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.70 | 13.78 |
October | 21.45 | 9.83 |
November | 21.00 | 5.28 |
December | 20.78 | 3.63 |
Annual Sum or Average | 21.38 | 9.74 |
Minimum of Months | 20.78 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | 3.20 |
February | 20.88 | 5.10 |
March | 21.03 | 6.09 |
April | 21.42 | 8.68 |
May | 21.67 | 11.83 |
June | 21.73 | 15.06 |
July | 21.75 | 16.98 |
August | 21.75 | 17.08 |
September | 21.67 | 13.78 |
October | 21.30 | 9.83 |
November | 20.83 | 5.28 |
December | 20.60 | 3.63 |
Annual Sum or Average | 21.27 | 9.74 |
Minimum of Months | 20.60 | 3.20 |
Maximum of Months | 21.75 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.40 | 3.20 |
February | 18.49 | 5.10 |
March | 18.76 | 6.09 |
April | 20.38 | 8.68 |
May | 21.94 | 11.83 |
June | 23.38 | 15.06 |
July | 24.10 | 16.98 |
August | 23.79 | 17.08 |
September | 22.19 | 13.78 |
October | 19.97 | 9.83 |
November | 18.07 | 5.28 |
December | 16.83 | 3.63 |
Annual Sum or Average | 20.45 | 9.74 |
Minimum of Months | 16.83 | 3.20 |
Maximum of Months | 24.10 | 17.08 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:45:03
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.65 | 3.20 |
February | 16.21 | 5.10 |
March | 16.33 | 6.09 |
April | 18.44 | 8.68 |
May | 20.59 | 11.83 |
June | 22.80 | 15.06 |
July | 23.88 | 16.98 |
August | 23.41 | 17.08 |
September | 21.09 | 13.78 |
October | 18.10 | 9.83 |
November | 15.54 | 5.28 |
December | 13.58 | 3.63 |
Annual Sum or Average | 18.73 | 9.74 |
Minimum of Months | 13.58 | 3.20 |
Maximum of Months | 23.88 | 17.08 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:45:03
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.167478E+12 | 120836.363 | 16-JAN-07:15 | 20847.837 | 39740.848 | 9003.813 | 46726.468 | 321.284 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.140497E+12 | 111268.073 | 07-FEB-07:15 | 20847.837 | 39740.848 | 9003.813 | 36716.799 | 762.662 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.154440E+12 | 109477.781 | 21-MAR-06:15 | 20847.837 | 39740.848 | 9003.813 | 34836.443 | 852.727 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.144116E+12 | 98356.301 | 02-APR-06:15 | 20847.837 | 39740.848 | 9003.813 | 26122.777 | 2632.913 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.150898E+12 | 94242.408 | 28-MAY-07:00 | 25182.171 | 43578.554 | 9488.607 | 0.000 | 15984.964 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.153204E+12 | 96156.003 | 09-JUN-07:00 | 25182.171 | 43578.554 | 9488.607 | 0.000 | 17898.558 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.165942E+12 | 97785.098 | 22-JUL-07:00 | 25182.171 | 43578.554 | 9488.607 | 0.000 | 19527.654 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.164727E+12 | 97667.733 | 26-AUG-07:00 | 25182.171 | 43578.554 | 9488.607 | 0.000 | 19410.288 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.150782E+12 | 93874.224 | 15-SEP-07:00 | 25182.171 | 43578.554 | 9488.607 | 0.000 | 15616.779 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.148319E+12 | 103493.870 | 29-OCT-06:45 | 20847.837 | 39740.848 | 9003.813 | 27618.819 | 2086.439 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.156224E+12 | 124350.715 | 21-NOV-07:15 | 20847.837 | 39740.848 | 9003.813 | 50336.729 | 225.375 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.169932E+12 | 121848.119 | 11-DEC-07:15 | 20847.837 | 39740.848 | 9003.813 | 47824.572 | 234.936 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.186656E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.140497E+12 | 93874.224 | 20847.837 | 39740.848 | 9003.813 | 0.000 | 225.375 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.169932E+12 | 124350.715 | 25182.171 | 43578.554 | 9488.607 | 50336.729 | 19527.654 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:45:03
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.104514E+12 | 101605.662 | 06-JAN-09:15 | 715.393 | 40096.028 | 0.000 | 60794.241 | 60794.241 | 60794.241 | 715.393 |
February | 0.909428E+11 | 108431.097 | 24-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 68335.069 | 68335.069 | 68335.069 | 0.000 |
March | 0.993744E+11 | 101048.435 | 10-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 60952.407 | 60952.407 | 60952.407 | 0.000 |
April | 0.916886E+11 | 92382.226 | 14-APR-08:15 | 0.000 | 40096.028 | 0.000 | 52286.198 | 52286.198 | 52286.198 | 0.000 |
May | 0.908036E+11 | 93434.732 | 12-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 53338.704 | 53338.704 | 53338.704 | 0.000 |
June | 0.852890E+11 | 96558.427 | 16-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 56462.399 | 56462.399 | 56462.399 | 0.000 |
July | 0.867187E+11 | 92451.531 | 21-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 52355.503 | 52355.503 | 52355.503 | 0.000 |
August | 0.863034E+11 | 91982.372 | 18-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 51886.344 | 51886.344 | 51886.344 | 0.000 |
September | 0.844557E+11 | 89661.397 | 08-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 49565.369 | 49565.369 | 49565.369 | 0.000 |
October | 0.905473E+11 | 96810.443 | 27-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 56714.415 | 56714.415 | 56714.415 | 0.000 |
November | 0.950421E+11 | 101456.808 | 22-NOV-09:15 | 3235.318 | 40096.028 | 0.000 | 58125.462 | 58125.462 | 58125.462 | 3235.318 |
December | 0.103200E+12 | 103747.496 | 16-DEC-09:15 | 846.192 | 40096.028 | 0.000 | 62805.275 | 62805.275 | 62805.275 | 846.192 |
Annual Sum or Average | 0.110888E+13 | 0.000 | ||||||||
Minimum of Months | 0.844557E+11 | 89661.397 | 0.000 | 40096.028 | 0.000 | 49565.369 | 49565.369 | 49565.369 | 0.000 | |
Maximum of Months | 0.104514E+12 | 108431.097 | 3235.318 | 40096.028 | 0.000 | 68335.069 | 68335.069 | 68335.069 | 3235.318 |