Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Duluth International Arpt MN USA TMY3 WMO#=727450

Simulation Timestamp: 2015-09-14 08:44:19


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3581.74 892.41 961.52
Net Site Energy 3581.74 892.41 961.52
Total Source Energy 8597.50 2142.10 2308.00
Net Source Energy 8597.50 2142.10 2308.00


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 532.46 170.83 0.00 0.00 0.00 0.00
Cooling 185.03 0.00 0.00 0.00 0.00 0.00
Interior Lighting 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.70 0.00 0.00 0.00 0.00 0.00
Interior Equipment 601.95 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 299.99 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 725.92 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2263.51 1318.23 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 532.46 170.83 0.00 0.00 0.00 0.00
Cooling General 185.03 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.70 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 573.47 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 299.99 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 725.92 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 172.84 0.00 0.00 0.00 0.00 0.00
HVAC 273.21 240.73 0.00 0.00 0.00 0.69
Other 161.59 113.15 0.00 0.00 0.00 0.00
Total 607.64 353.88 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.41 0.00 0.00 0.00 0.00 0.00
HVAC 253.57 223.43 0.00 0.00 0.00 0.64
Other 149.98 105.02 0.00 0.00 0.00 0.00
Total 563.96 328.44 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2263.51 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2263.51 100.00
     
Total On-Site and Utility Electric Sources 2263.51 100.00
Total Electricity End Uses 2263.51 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1164.50
Time Setpoint Not Met During Occupied Cooling 2853.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 6235.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
RunPeriod Duluth International Arpt MN USA TMY3 WMO#=727450
Weather File Duluth International Arpt MN USA TMY3 WMO#=727450
Latitude [deg] 46.83
Longitude [deg] -92.2
Elevation [m] 433.00
Time Zone -6.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Window Opening Area [m2] 184.20 8.38 72.38 6.62 96.82
Window-Wall Ratio [%] 10.87 3.95 11.39 3.13 15.24


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Window Opening Area [m2] 179.26 8.38 67.45 6.62 96.82
Window-Wall Ratio [%] 12.01 3.95 12.11 5.68 15.95


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 8.3610   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 6.9675   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 11.1480   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 15.3285 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 12.5415 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 18.1154 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 20.9024   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 16.7220 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 8.3610 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2155.0206
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 12.5415 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 15.3285 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 8.3610   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 11.1480   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
Total 4013.58     11621.73   1694.58 184.20 11.2819 15.53 28.2097
Conditioned Total 3725.09     10741.65   1492.32 179.26 11.5457 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 7.8766 26.23 260.8031
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -28.60 0.00 -28.60 Wetbulb [C] 4.60 310.00
DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 29.20 10.90 21.00 Wetbulb [C] 5.20 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 0.00 90.00 N
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 90.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 270.00 90.00 W
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 270.00 90.00 W
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 90.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 270.00 90.00 W
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 90.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 90.00 90.00 E
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 90.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 90.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 90.00 90.00 E
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 90.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 90.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 180.00 90.00 S
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 90.00 90.00 E
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 180.00 90.00 S
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.295 0.309 8.36 90.00 90.00 E
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 0.00 90.00 N
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 180.00 90.00 S
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 270.00 90.00 W
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 0.00 90.00 N
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 270.00 90.00 W
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 270.00 90.00 W
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 35.12 270.00 90.00 W
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 270.00 90.00 W
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 270.00 90.00 W
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 90.00 90.00 E
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 90.00 90.00 E
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 90.00 90.00 E
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 0.00 90.00 N
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 180.00 90.00 S
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 90.00 90.00 E
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 180.00 90.00 S
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.295 0.309 8.36 90.00 90.00 E
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 0.00 90.00 N
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 180.00 90.00 S
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 270.00 90.00 W
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 0.00 90.00 N
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 270.00 90.00 W
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 270.00 90.00 W
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 35.12 270.00 90.00 W
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 270.00 90.00 W
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 270.00 90.00 W
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 90.00 90.00 E
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 90.00 90.00 E
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 90.00 90.00 E
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 0.00 90.00 N
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 180.00 90.00 S
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 90.00 90.00 E
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.219 0.228 20.07 270.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 180.00 90.00 S
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.295 0.309 8.36 90.00 90.00 E
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 0.00 90.00 N
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.219 0.228 125.42 270.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 180.00 90.00 S
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 270.00 90.00 W
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.219 0.228 20.07 270.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 0.00 90.00 N
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 270.00 90.00 W
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.219 0.228 32.61 270.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 270.00 90.00 W
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.219 0.228 130.45 270.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 35.12 270.00 90.00 W
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.219 0.228 105.36 270.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 270.00 90.00 W
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.219 0.228 130.45 270.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 270.00 90.00 W
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.219 0.228 32.61 270.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.219 0.228 32.61 270.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 90.00 90.00 E
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.219 0.228 130.44 270.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 5.02 90.00 90.00 E
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.219 0.228 15.05 270.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.219 0.228 32.61 270.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 43.48 90.00 90.00 E
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.219 0.228 130.44 270.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 10.87 90.00 90.00 E
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.219 0.228 32.61 270.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 4.18 90.00 90.00 E
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.219 0.228 12.54 270.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.295 0.309 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.295 0.309 22.58 0.00 90.00 N
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.219 0.228 20.07 270.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.69 0.00 0.00 2.69 2.69 2.670 0.479 0.381     No W_CORRIDORFLR1_2_0_0 180.00 90.00 S
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 4.44 0.00 0.00 4.44 4.44 2.670 0.479 0.381     No W_CORRIDORFLR1_16_0_0 0.00 90.00 N
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.69 0.00 0.00 2.69 2.69 2.670 0.479 0.381     No W_CORRIDORFLR1_20_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM101_5_0_0 270.00 90.00 W
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM102_5_0_0 270.00 90.00 W
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM103_5_0_0 270.00 90.00 W
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM104_3_0_0 90.00 90.00 E
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM105_3_0_0 90.00 90.00 E
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_EMPLOYEELOUNGEFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_EXERCISECENTERFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR2_2_0_0 180.00 90.00 S
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR2_15_0_0 0.00 90.00 N
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM201_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM213_5_0_0 270.00 90.00 W
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM214_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM219_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM224_3_0_0 90.00 90.00 E
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR3_2_0_0 180.00 90.00 S
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR3_15_0_0 0.00 90.00 N
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM301_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM313_5_0_0 270.00 90.00 W
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM314_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM319_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM324_3_0_0 90.00 90.00 E
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR4_2_0_0 180.00 90.00 S
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR4_15_0_0 0.00 90.00 N
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM401_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM413_5_0_0 270.00 90.00 W
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM414_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM419_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM424_3_0_0 90.00 90.00 E
Total or Average           184.20 2.670 0.479 0.381              
North Total or Average           8.38 2.670 0.479 0.381              
Non-North Total or Average           175.82 2.670 0.479 0.381              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   6993.25 5379.29 1613.96 0.77 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   21340.87 15650.52 5690.35 0.73 3.50    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   10316.85 7284.70 3032.15 0.71 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   13953.41 10882.43 3070.98 0.78 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6691.6 3.20 10.93 11.58 10.80
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 20517.6 2.97 10.12 10.73 10.19
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 9954.6 3.32 11.33 12.01 11.39
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13332.6 3.19 10.87 11.51 10.70
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   305.27 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   59694.03 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1235.19 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1235.19 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1956.10 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1773.92 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1330.50 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   560.48 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   719.08 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   4581.18 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1235.19 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   5093.71 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3999.00 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4940.75 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   2041.05 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1749.87 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4940.40 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1318.28 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4940.40 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1560.05 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   1035.14 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   891.77 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   5193.99 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1304.16 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   4940.75 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3915.71 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   5080.02 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1724.65 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1829.25 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   5131.35 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1235.10 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4940.40 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1235.10 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   1244.73 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   1202.81 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   6748.34 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   2058.33 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   5377.47 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   4388.97 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   6272.54 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   2162.96 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1678.97 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   6145.67 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1776.36 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   5986.91 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   2028.61 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   1507.17 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   5085.95 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   21317.65 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   11415.45 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   8667.49 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.86 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.02 1.45 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 1.18 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.02 1.84 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.02 1.76 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.03 2.33 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.54 622.50 0.39 451.14 1160.84 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.55 622.50 1.06 1208.79 1140.11 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.54 622.50 0.47 541.34 1160.84 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.55 622.50 0.80 912.03 1140.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.51 0.27
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 10178.22 12213.86 0.884 1.060 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
RESTROOMFLR1 639.35 767.22 0.055 0.067 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 25.77 0.01308
MEETINGROOMFLR1 4474.37 5369.24 0.389 0.466 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM101 534.66 641.60 0.049 0.059 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 26.58 0.01308
GUESTROOM102 407.03 488.43 0.037 0.045 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM103 1476.05 1771.26 0.178 0.214 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM104 1336.81 1604.17 0.161 0.193 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM105 1812.09 2174.51 0.219 0.262 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
EMPLOYEELOUNGEFLR1 5685.50 6822.60 0.494 0.592 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
EXERCISECENTERFLR1 1354.91 1625.89 0.118 0.141 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 23.20 0.01308
FRONTOFFICEFLR1 3733.71 4480.46 0.324 0.389 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM201 777.45 932.94 0.071 0.086 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 27.13 0.01308
GUESTROOM202_205 6035.00 7242.00 0.728 0.873 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 26.58 0.01308
GUESTROOM206_208 4984.58 5981.49 0.601 0.721 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM209_212 5620.82 6744.98 0.678 0.814 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM213 1584.70 1901.64 0.191 0.229 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM214 1572.87 1887.44 0.190 0.228 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM215_218 8744.63 10493.55 0.804 0.964 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM219 5715.18 6858.22 0.689 0.827 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM220_223 5425.43 6510.51 0.654 0.785 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM224 1591.22 1909.47 0.192 0.230 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM301 627.11 752.53 0.058 0.069 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 27.13 0.01308
GUESTROOM302_305 1987.51 2385.02 0.183 0.219 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM306_308 1850.73 2220.87 0.170 0.204 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM309_312 5615.38 6738.46 0.677 0.813 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 26.86 0.01308
GUESTROOM313 629.78 755.74 0.058 0.069 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 26.58 0.01308
GUESTROOM314 1489.67 1787.60 0.180 0.216 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM315_318 6098.83 7318.60 0.736 0.883 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM319 867.17 1040.61 0.080 0.096 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM320_323 5240.31 6288.37 0.632 0.758 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM324 516.29 619.55 0.047 0.057 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 25.47 0.01308
GUESTROOM401 1918.60 2302.32 0.231 0.278 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 27.67 0.01308
GUESTROOM402_405 2771.53 3325.83 0.255 0.306 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 27.40 0.01308
GUESTROOM406_408 2579.75 3095.70 0.237 0.284 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 27.40 0.01308
GUESTROOM409_412 6638.94 7966.73 0.801 0.961 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 27.67 0.01308
GUESTROOM413 904.75 1085.70 0.083 0.100 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 27.40 0.01308
GUESTROOM414 665.62 798.74 0.061 0.073 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 26.69 0.01308
GUESTROOM415_418 6238.03 7485.64 0.752 0.903 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 25.88 0.01308
GUESTROOM419 1696.63 2035.96 0.205 0.246 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 26.28 0.01308
GUESTROOM420_423 6089.70 7307.64 0.735 0.881 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 25.88 0.01308
GUESTROOM424 1697.32 2036.78 0.205 0.246 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 26.28 0.01308
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
CORRIDORFLR1 14605.54 17526.65 1.267 1.521 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 26.58 0.01308
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
CORRIDORFLR2 2884.18 3461.02 0.250 0.300 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 28.33 0.01308
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
CORRIDORFLR3 1596.03 1915.23 0.138 0.166 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 27.40 0.01308
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308
CORRIDORFLR4 2284.83 2741.79 0.198 0.238 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 29.04 0.01308
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   29.20 0.01308


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 2468.30 2961.97 0.073 0.236 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -28.60 0.00028
RESTROOMFLR1 119.27 143.12 0.004 0.004 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -28.60 0.00028
MEETINGROOMFLR1 883.68 1060.42 0.026 0.126 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -28.60 0.00028
GUESTROOM101 109.40 131.28 0.003 0.013 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -28.60 0.00028
GUESTROOM102 145.46 174.55 0.004 0.013 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -28.60 0.00028
GUESTROOM103 979.09 1174.90 0.029 0.035 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -28.60 0.00028
GUESTROOM104 827.31 992.77 0.025 0.029 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:45:00 -28.60 0.00028
GUESTROOM105 457.80 549.35 0.014 0.016 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:45:00 -28.60 0.00028
EMPLOYEELOUNGEFLR1 438.79 526.55 0.013 0.051 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -28.60 0.00028
EXERCISECENTERFLR1 282.01 338.41 0.008 0.043 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -28.60 0.00028
FRONTOFFICEFLR1 1541.42 1849.71 0.046 0.056 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -28.60 0.00028
GUESTROOM201 379.55 455.46 0.010 0.013 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:00:00 -28.60 0.00028
GUESTROOM202_205 1640.76 1968.91 0.049 0.058 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -28.60 0.00028
GUESTROOM206_208 1268.74 1522.49 0.038 0.045 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -28.60 0.00028
GUESTROOM209_212 1388.94 1666.73 0.041 0.054 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -28.60 0.00028
GUESTROOM213 1049.87 1259.85 0.031 0.037 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -28.60 0.00028
GUESTROOM214 807.27 968.72 0.024 0.029 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -28.60 0.00028
GUESTROOM215_218 477.83 573.39 0.013 0.054 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -28.60 0.00028
GUESTROOM219 447.61 537.13 0.013 0.016 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -28.60 0.00028
GUESTROOM220_223 1201.24 1441.49 0.036 0.054 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -28.60 0.00028
GUESTROOM224 649.09 778.90 0.019 0.023 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -28.60 0.00028
GUESTROOM301 464.90 557.88 0.013 0.015 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -28.60 0.00028
GUESTROOM302_305 944.99 1133.99 0.026 0.054 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -28.60 0.00028
GUESTROOM306_308 787.36 944.84 0.022 0.043 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:30:00 -28.60 0.00028
GUESTROOM309_312 1629.35 1955.22 0.048 0.058 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:30:00 -28.60 0.00028
GUESTROOM313 815.31 978.37 0.022 0.027 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:45:00 -28.60 0.00028
GUESTROOM314 873.42 1048.10 0.026 0.031 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:15:00 -28.60 0.00028
GUESTROOM315_318 1672.31 2006.77 0.050 0.060 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -28.60 0.00028
GUESTROOM319 178.65 214.39 0.005 0.013 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -28.60 0.00028
GUESTROOM320_323 1444.99 1733.98 0.043 0.054 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -28.60 0.00028
GUESTROOM324 360.26 432.31 0.010 0.013 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -28.60 0.00028
GUESTROOM401 1064.28 1277.13 0.032 0.038 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:15:00 -28.60 0.00028
GUESTROOM402_405 1993.62 2392.34 0.055 0.066 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 21:45:00 -28.60 0.00028
GUESTROOM406_408 1685.96 2023.15 0.046 0.056 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:45:00 -28.60 0.00028
GUESTROOM409_412 2623.12 3147.74 0.078 0.093 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 20:15:00 -28.60 0.00028
GUESTROOM413 1180.56 1416.67 0.033 0.039 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -28.60 0.00028
GUESTROOM414 777.28 932.74 0.021 0.026 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 21:45:00 -28.60 0.00028
GUESTROOM415_418 2517.58 3021.09 0.075 0.090 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:00:00 -28.60 0.00028
GUESTROOM419 829.34 995.21 0.025 0.030 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:45:00 -28.60 0.00028
GUESTROOM420_423 2385.28 2862.33 0.071 0.085 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -28.60 0.00028
GUESTROOM424 1039.55 1247.46 0.031 0.037 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -28.60 0.00028
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB   -28.60 0.00028
CORRIDORFLR1 47477.62 56973.14 1.406 1.688 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -28.60 0.00028
FRONTSTAIRSFLR1 239.38 287.26 0.005 0.006 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -28.60 0.00028
REARSTAIRSFLR2 386.49 463.79 0.008 0.009 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
CORRIDORFLR2 1971.45 2365.74 0.059 0.070 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -28.60 0.00028
FRONTSTAIRSFLR2 649.98 779.97 0.013 0.016 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
REARSTAIRSFLR3 530.43 636.52 0.011 0.013 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
CORRIDORFLR3 2482.16 2978.59 0.074 0.088 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
FRONTSTAIRSFLR3 824.67 989.60 0.017 0.020 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
REARSTAIRSFLR4 789.68 947.62 0.016 0.019 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
CORRIDORFLR4 3777.48 4532.98 0.112 0.135 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028
FRONTSTAIRSFLR4 1043.40 1252.09 0.021 0.025 DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -28.60 0.00028


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.39 0.39 0.06 0.06
SAC_FRONTLOUNGE 1.06 1.06 0.24 0.24
SAC_MEETINGROOM 0.47 0.47 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.80 0.80 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 3407.75 6845.50 2277.75
RESTROOMFLR1 1587.50 7348.50 1201.25
MEETINGROOMFLR1 1333.25 3207.75 333.75
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 3485.50 8748.00 3485.50
GUESTROOM104 2759.00 8722.50 2759.00
GUESTROOM105 749.25 8465.50 747.50
EMPLOYEELOUNGEFLR1 2877.00 2452.25 459.75
EXERCISECENTERFLR1 1331.50 3514.00 141.50
FRONTOFFICEFLR1 2300.50 6412.00 1513.50
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 2100.00 8456.50 2080.00
GUESTROOM206_208 1882.25 8441.00 1859.50
GUESTROOM209_212 1635.75 8561.25 1624.25
GUESTROOM213 3466.75 8692.00 3462.25
GUESTROOM214 2610.75 8519.00 2601.75
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 2793.75 4965.75 176.75
GUESTROOM220_223 1064.25 8295.25 1037.75
GUESTROOM224 2537.75 8457.75 2527.50
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 2168.75 8582.25 2156.75
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 3239.75 8539.50 3229.50
GUESTROOM315_318 1244.00 8215.50 1200.50
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 1750.50 8408.00 1730.50
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 4492.75 8346.75 4404.50
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 3281.75 8135.25 3068.00
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 2925.00 7950.00 2615.50
GUESTROOM419 3028.50 8110.50 2903.75
GUESTROOM420_423 2979.75 7981.00 2687.50
GUESTROOM424 3811.50 8196.50 3706.25
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7475.50 8760.00 6235.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.25 0.00 0.25 0.00
RESTROOMFLR1 960.00 586.25 960.00 586.25
MEETINGROOMFLR1 0.25 0.00 0.25 0.00
GUESTROOM101 1.00 0.00 0.00 0.00
GUESTROOM102 1.00 0.00 0.00 0.00
GUESTROOM103 28.00 27.75 28.00 27.75
GUESTROOM104 24.75 28.00 24.75 28.00
GUESTROOM105 5.50 36.75 5.50 36.75
EMPLOYEELOUNGEFLR1 775.00 1231.50 536.75 845.50
EXERCISECENTERFLR1 0.75 0.00 0.00 0.00
FRONTOFFICEFLR1 0.50 0.00 0.50 0.00
GUESTROOM201 55.75 0.00 0.00 0.00
GUESTROOM202_205 19.00 20.00 19.00 20.00
GUESTROOM206_208 15.50 28.00 15.50 28.00
GUESTROOM209_212 16.00 17.75 16.00 17.75
GUESTROOM213 10.50 17.50 10.50 17.50
GUESTROOM214 19.00 17.00 19.00 17.00
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 1790.50 0.00 1790.50
GUESTROOM220_223 15.00 15.50 15.00 15.50
GUESTROOM224 23.75 18.50 23.75 18.50
GUESTROOM301 110.00 0.00 0.00 0.00
GUESTROOM302_305 0.50 0.00 0.00 0.00
GUESTROOM306_308 0.75 0.00 0.00 0.00
GUESTROOM309_312 22.25 17.75 22.25 17.75
GUESTROOM313 0.25 0.00 0.00 0.00
GUESTROOM314 23.75 15.50 23.75 15.50
GUESTROOM315_318 17.00 17.75 17.00 17.75
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 23.25 14.00 23.25 14.00
GUESTROOM324 0.50 0.00 0.00 0.00
GUESTROOM401 29.75 26.25 29.75 26.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.25 0.00 0.00 0.00
GUESTROOM409_412 28.00 27.25 28.00 27.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 30.00 21.25 30.00 21.25
GUESTROOM419 22.75 23.75 22.75 23.75
GUESTROOM420_423 31.00 21.25 31.00 21.25
GUESTROOM424 18.50 22.50 18.50 22.50
REARSTAIRSFLR1 13.50 0.00 0.00 0.00
CORRIDORFLR1 9.00 1881.50 0.00 0.00
FRONTSTAIRSFLR1 16.75 0.00 0.00 0.00
REARSTAIRSFLR2 18.25 0.00 0.00 0.00
CORRIDORFLR2 0.00 51.00 0.00 0.00
FRONTSTAIRSFLR2 17.50 0.00 0.00 0.00
REARSTAIRSFLR3 23.25 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 23.00 0.00 0.00 0.00
REARSTAIRSFLR4 24.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 50.00 0.00 0.00
FRONTSTAIRSFLR4 22.50 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 1213.50 3522.50 1164.50 2853.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:19

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.009289
FRONTSTAIRSFLR2 UNITHEATER 0.015621
REARSTAIRSFLR3 UNITHEATER 0.012748
FRONTSTAIRSFLR3 UNITHEATER 0.019818
REARSTAIRSFLR4 UNITHEATER 0.018977
FRONTSTAIRSFLR4 UNITHEATER 0.025073


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.009289
FRONTSTAIRSFLR2UNITHEATERFAN 0.015621
REARSTAIRSFLR3UNITHEATERFAN 0.012748
FRONTSTAIRSFLR3UNITHEATERFAN 0.019818
REARSTAIRSFLR4UNITHEATERFAN 0.018977
FRONTSTAIRSFLR4UNITHEATERFAN 0.025073
SAC_FRONTOFFICE SUPPLY FAN 0.388630
SAC_FRONTLOUNGE SUPPLY FAN 1.06
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.799952


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 305.27
CORRIDORFLR1 PTAC HEATING COIL 59694.03
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1235.19
102 PTAC HEATING COIL 1235.19
103 PTAC HEATING COIL 1956.10
104 PTAC HEATING COIL 1773.92
105 PTAC HEATING COIL 1330.50
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 560.48
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 719.08
CORRIDORFLR2 PTAC HEATING COIL 4581.18
201 PTAC HEATING COIL 1235.19
202_205 PTAC HEATING COIL 5093.71
206_208 PTAC HEATING COIL 3999.00
209_212 PTAC HEATING COIL 4940.75
213 PTAC HEATING COIL 2041.05
214 PTAC HEATING COIL 1749.87
215_218 PTAC HEATING COIL 4940.40
219 PTAC HEATING COIL 1318.28
220_223 PTAC HEATING COIL 4940.40
224 PTAC HEATING COIL 1560.05
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 1035.14
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 891.77
CORRIDORFLR3 PTAC HEATING COIL 5193.99
301 PTAC HEATING COIL 1304.16
302_305 PTAC HEATING COIL 4940.75
306_308 PTAC HEATING COIL 3915.71
309_312 PTAC HEATING COIL 5080.02
313 PTAC HEATING COIL 1724.65
314 PTAC HEATING COIL 1829.25
315_318 PTAC HEATING COIL 5131.35
319 PTAC HEATING COIL 1235.10
320_323 PTAC HEATING COIL 4940.40
324 PTAC HEATING COIL 1235.10
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 1244.73
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 1202.81
CORRIDORFLR4 PTAC HEATING COIL 6748.34
401 PTAC HEATING COIL 2058.33
402_405 PTAC HEATING COIL 5377.47
406_408 PTAC HEATING COIL 4388.97
409_412 PTAC HEATING COIL 6272.54
413 PTAC HEATING COIL 2162.96
414 PTAC HEATING COIL 1678.97
415_418 PTAC HEATING COIL 6145.67
419 PTAC HEATING COIL 1776.36
420_423 PTAC HEATING COIL 5986.91
424 PTAC HEATING COIL 2028.61
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 1507.17


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.769212 0.388630 6993.25
SAC_FRONTLOUNGE COOLING COIL 0.733359 1.06 21340.87
SAC_MEETINGROOM COOLING COIL 0.706098 0.466339 10316.85
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.779912 0.799952 13953.41


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 1.06
RESTROOMFLR1 DIRECT AIR 0.066536
MEETINGROOMFLR1 DIRECT AIR 0.466339
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.592340
EXERCISECENTERFLR1 DIRECT AIR 0.141077
FRONTOFFICEFLR1 DIRECT AIR 0.388630


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.388630
SAC_FRONTLOUNGE MAIN BRANCH 1.06
SAC_MEETINGROOM MAIN BRANCH 0.466339
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.799952


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.388630
SAC_FRONTLOUNGE 1.06
SAC_MEETINGROOM 0.466339
SAC_EXC_EMPLGE_RESTRM 0.799952


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.388630 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 1.06 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.466339 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.799952 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.388630 0.388630 0.388630 0.388630 5085.95 6993.25 1.00
SAC_FRONTLOUNGE 1.06 1.06 1.06 1.06 21317.65 21340.87 1.00
SAC_MEETINGROOM 0.466339 0.466339 0.466339 0.466339 11415.45 10316.85 1.00
SAC_EXC_EMPLGE_RESTRM 0.799952 0.799952 0.799952 0.799952 8667.49 13953.41 0.176357


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 5085.95
SAC_FRONTLOUNGE HEATING COIL 21317.65
SAC_MEETINGROOM HEATING COIL 11415.45
SAC_EXC_EMPLGE_RESTRM HEATING COIL 8667.49


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.466339


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.04 -13.0
February 13.84 -8.2
March 15.28 -2.6
April 18.38 4.03
May 21.08 12.37
June 22.37 16.19
July 23.05 17.83
August 22.76 17.50
September 21.20 12.89
October 18.48 6.03
November 15.19 -4.5
December 12.57 -11.1
     
Annual Sum or Average 18.04 4.02
Minimum of Months 12.04 -13.0
Maximum of Months 23.05 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 -13.0
February 21.31 -8.2
March 21.70 -2.6
April 22.75 4.03
May 24.03 12.37
June 24.73 16.19
July 25.07 17.83
August 24.88 17.50
September 24.03 12.89
October 22.90 6.03
November 21.51 -4.5
December 21.21 -11.1
     
Annual Sum or Average 22.95 4.02
Minimum of Months 21.17 -13.0
Maximum of Months 25.07 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.17 -13.0
February 13.08 -8.2
March 14.49 -2.6
April 17.50 4.03
May 20.35 12.37
June 21.64 16.19
July 22.33 17.83
August 22.08 17.50
September 20.47 12.89
October 17.66 6.03
November 14.39 -4.5
December 11.78 -11.1
     
Annual Sum or Average 17.27 4.02
Minimum of Months 11.17 -13.0
Maximum of Months 22.33 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -13.0
February 21.12 -8.2
March 21.22 -2.6
April 21.63 4.03
May 22.88 12.37
June 23.29 16.19
July 23.50 17.83
August 23.59 17.50
September 22.92 12.89
October 21.73 6.03
November 21.13 -4.5
December 21.11 -11.1
     
Annual Sum or Average 22.11 4.02
Minimum of Months 21.11 -13.0
Maximum of Months 23.59 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.91 -13.0
February 21.29 -8.2
March 21.75 -2.6
April 22.37 4.03
May 23.15 12.37
June 23.42 16.19
July 23.56 17.83
August 23.59 17.50
September 23.21 12.89
October 22.49 6.03
November 21.63 -4.5
December 21.02 -11.1
     
Annual Sum or Average 22.37 4.02
Minimum of Months 20.91 -13.0
Maximum of Months 23.59 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.16 -13.0
February 21.23 -8.2
March 21.48 -2.6
April 22.24 4.03
May 23.37 12.37
June 23.64 16.19
July 23.74 17.83
August 23.76 17.50
September 23.43 12.89
October 22.32 6.03
November 21.28 -4.5
December 21.17 -11.1
     
Annual Sum or Average 22.41 4.02
Minimum of Months 21.16 -13.0
Maximum of Months 23.76 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.07 -13.0
February 23.42 -8.2
March 23.89 -2.6
April 24.87 4.03
May 25.92 12.37
June 26.26 16.19
July 26.47 17.83
August 26.42 17.50
September 25.91 12.89
October 24.89 6.03
November 23.75 -4.5
December 23.19 -11.1
     
Annual Sum or Average 24.85 4.02
Minimum of Months 23.07 -13.0
Maximum of Months 26.47 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.95 -8.2
March 19.26 -2.6
April 20.39 4.03
May 22.13 12.37
June 22.65 16.19
July 22.92 17.83
August 22.97 17.50
September 22.17 12.89
October 20.51 6.03
November 19.03 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.74 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.97 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.92 -8.2
March 19.12 -2.6
April 20.03 4.03
May 21.82 12.37
June 22.41 16.19
July 22.71 17.83
August 22.74 17.50
September 21.84 12.89
October 20.16 6.03
November 18.93 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.55 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.74 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -13.0
February 20.50 -8.2
March 20.59 -2.6
April 20.96 4.03
May 21.51 12.37
June 21.65 16.19
July 21.71 17.83
August 21.72 17.50
September 21.54 12.89
October 21.04 6.03
November 20.53 -4.5
December 20.47 -11.1
     
Annual Sum or Average 21.06 4.02
Minimum of Months 20.47 -13.0
Maximum of Months 21.72 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -13.0
February 20.55 -8.2
March 20.76 -2.6
April 21.28 4.03
May 21.64 12.37
June 21.71 16.19
July 21.73 17.83
August 21.74 17.50
September 21.66 12.89
October 21.25 6.03
November 20.65 -4.5
December 20.49 -11.1
     
Annual Sum or Average 21.17 4.02
Minimum of Months 20.48 -13.0
Maximum of Months 21.74 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.68 -13.0
February 20.89 -8.2
March 21.22 -2.6
April 21.62 4.03
May 21.74 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.74 12.89
October 21.58 6.03
November 21.07 -4.5
December 20.73 -11.1
     
Annual Sum or Average 21.38 4.02
Minimum of Months 20.68 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.44 -13.0
February 21.84 -8.2
March 22.30 -2.6
April 22.47 4.03
May 22.68 12.37
June 22.71 16.19
July 22.71 17.83
August 22.84 17.50
September 22.82 12.89
October 22.67 6.03
November 22.17 -4.5
December 21.54 -11.1
     
Annual Sum or Average 22.35 4.02
Minimum of Months 21.44 -13.0
Maximum of Months 22.84 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 48.96 -13.0
February 49.53 -8.2
March 50.20 -2.6
April 51.28 4.03
May 52.12 12.37
June 52.58 16.19
July 52.80 17.83
August 52.63 17.50
September 52.08 12.89
October 51.15 6.03
November 50.02 -4.5
December 49.15 -11.1
     
Annual Sum or Average 51.05 4.02
Minimum of Months 48.96 -13.0
Maximum of Months 52.80 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 66.48 -13.0
February 67.04 -8.2
March 67.59 -2.6
April 69.01 4.03
May 70.16 12.37
June 70.73 16.19
July 71.11 17.83
August 70.86 17.50
September 70.10 12.89
October 68.94 6.03
November 67.62 -4.5
December 66.71 -11.1
     
Annual Sum or Average 68.87 4.02
Minimum of Months 66.48 -13.0
Maximum of Months 71.11 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 -13.0
February 22.08 -8.2
March 22.58 -2.6
April 23.05 4.03
May 23.54 12.37
June 23.74 16.19
July 23.81 17.83
August 23.85 17.50
September 23.63 12.89
October 23.17 6.03
November 22.42 -4.5
December 21.79 -11.1
     
Annual Sum or Average 22.95 4.02
Minimum of Months 21.68 -13.0
Maximum of Months 23.85 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 -13.0
February 21.35 -8.2
March 21.82 -2.6
April 22.71 4.03
May 23.55 12.37
June 23.79 16.19
July 23.85 17.83
August 23.88 17.50
September 23.67 12.89
October 22.81 6.03
November 21.59 -4.5
December 21.25 -11.1
     
Annual Sum or Average 22.63 4.02
Minimum of Months 21.18 -13.0
Maximum of Months 23.88 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.75 -13.0
February 12.41 -8.2
March 14.11 -2.6
April 17.63 4.03
May 20.94 12.37
June 22.53 16.19
July 23.31 17.83
August 22.87 17.50
September 20.99 12.89
October 17.90 6.03
November 14.13 -4.5
December 11.31 -11.1
     
Annual Sum or Average 17.43 4.02
Minimum of Months 10.75 -13.0
Maximum of Months 23.31 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.50 -13.0
February 17.43 -8.2
March 18.47 -2.6
April 20.64 4.03
May 22.61 12.37
June 23.52 16.19
July 23.96 17.83
August 23.73 17.50
September 22.68 12.89
October 20.76 6.03
November 18.43 -4.5
December 16.83 -11.1
     
Annual Sum or Average 20.48 4.02
Minimum of Months 16.50 -13.0
Maximum of Months 23.96 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.41 -13.0
February 12.34 -8.2
March 14.08 -2.6
April 18.02 4.03
May 21.43 12.37
June 22.95 16.19
July 23.76 17.83
August 23.38 17.50
September 21.47 12.89
October 18.05 6.03
November 13.91 -4.5
December 10.92 -11.1
     
Annual Sum or Average 17.59 4.02
Minimum of Months 10.41 -13.0
Maximum of Months 23.76 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -13.0
February 21.14 -8.2
March 21.33 -2.6
April 22.30 4.03
May 23.55 12.37
June 23.81 16.19
July 23.88 17.83
August 23.88 17.50
September 23.62 12.89
October 22.34 6.03
November 21.16 -4.5
December 21.11 -11.1
     
Annual Sum or Average 22.44 4.02
Minimum of Months 21.11 -13.0
Maximum of Months 23.88 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.66 -13.0
February 11.08 -8.2
March 12.83 -2.6
April 16.61 4.03
May 20.30 12.37
June 21.84 16.19
July 22.70 17.83
August 22.36 17.50
September 20.34 12.89
October 16.74 6.03
November 12.62 -4.5
December 9.38 -11.1
     
Annual Sum or Average 16.31 4.02
Minimum of Months 8.66 -13.0
Maximum of Months 22.70 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.85 -13.0
February 18.89 -8.2
March 19.00 -2.6
April 19.61 4.03
May 21.95 12.37
June 22.64 16.19
July 22.98 17.83
August 23.08 17.50
September 21.87 12.89
October 19.65 6.03
November 18.89 -4.5
December 18.88 -11.1
     
Annual Sum or Average 20.53 4.02
Minimum of Months 18.85 -13.0
Maximum of Months 23.08 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -13.0
February 20.56 -8.2
March 20.74 -2.6
April 21.21 4.03
May 21.67 12.37
June 21.74 16.19
July 21.75 17.83
August 21.75 17.50
September 21.69 12.89
October 21.23 6.03
November 20.64 -4.5
December 20.50 -11.1
     
Annual Sum or Average 21.17 4.02
Minimum of Months 20.49 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 -13.0
February 20.58 -8.2
March 20.79 -2.6
April 21.28 4.03
May 21.69 12.37
June 21.74 16.19
July 21.75 17.83
August 21.75 17.50
September 21.70 12.89
October 21.28 6.03
November 20.68 -4.5
December 20.52 -11.1
     
Annual Sum or Average 21.19 4.02
Minimum of Months 20.50 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.51 -13.0
February 20.58 -8.2
March 20.80 -2.6
April 21.29 4.03
May 21.68 12.37
June 21.74 16.19
July 21.75 17.83
August 21.75 17.50
September 21.70 12.89
October 21.31 6.03
November 20.69 -4.5
December 20.52 -11.1
     
Annual Sum or Average 21.20 4.02
Minimum of Months 20.51 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -13.0
February 20.49 -8.2
March 20.58 -2.6
April 20.97 4.03
May 21.57 12.37
June 21.69 16.19
July 21.73 17.83
August 21.75 17.50
September 21.59 12.89
October 21.02 6.03
November 20.51 -4.5
December 20.47 -11.1
     
Annual Sum or Average 21.07 4.02
Minimum of Months 20.47 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -13.0
February 20.55 -8.2
March 20.78 -2.6
April 21.38 4.03
May 21.70 12.37
June 21.74 16.19
July 21.75 17.83
August 21.75 17.50
September 21.70 12.89
October 21.31 6.03
November 20.65 -4.5
December 20.49 -11.1
     
Annual Sum or Average 21.19 4.02
Minimum of Months 20.48 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.70 -13.0
February 21.53 -8.2
March 22.45 -2.6
April 23.18 4.03
May 23.33 12.37
June 23.33 16.19
July 23.33 17.83
August 23.33 17.50
September 23.33 12.89
October 23.15 6.03
November 22.14 -4.5
December 20.91 -11.1
     
Annual Sum or Average 22.56 4.02
Minimum of Months 20.70 -13.0
Maximum of Months 23.33 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 28.11 -13.0
February 28.79 -8.2
March 29.40 -2.6
April 30.92 4.03
May 32.32 12.37
June 32.89 16.19
July 33.18 17.83
August 33.00 17.50
September 32.26 12.89
October 30.81 6.03
November 29.29 -4.5
December 28.34 -11.1
     
Annual Sum or Average 30.79 4.02
Minimum of Months 28.11 -13.0
Maximum of Months 33.18 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.66 -13.0
February 21.73 -8.2
March 21.78 -2.6
April 21.93 4.03
May 22.36 12.37
June 22.69 16.19
July 22.80 17.83
August 22.71 17.50
September 22.40 12.89
October 21.95 6.03
November 21.74 -4.5
December 21.68 -11.1
     
Annual Sum or Average 22.12 4.02
Minimum of Months 21.66 -13.0
Maximum of Months 22.80 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.55 -13.0
February 20.69 -8.2
March 21.02 -2.6
April 21.53 4.03
May 21.73 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.73 12.89
October 21.45 6.03
November 20.82 -4.5
December 20.58 -11.1
     
Annual Sum or Average 21.28 4.02
Minimum of Months 20.55 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -13.0
February 20.56 -8.2
March 20.80 -2.6
April 21.39 4.03
May 21.71 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.71 12.89
October 21.31 6.03
November 20.66 -4.5
December 20.50 -11.1
     
Annual Sum or Average 21.20 4.02
Minimum of Months 20.48 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.65 -13.0
February 15.69 -8.2
March 16.92 -2.6
April 19.84 4.03
May 22.51 12.37
June 23.65 16.19
July 24.23 17.83
August 23.91 17.50
September 22.48 12.89
October 19.87 6.03
November 16.83 -4.5
December 14.94 -11.1
     
Annual Sum or Average 19.65 4.02
Minimum of Months 14.65 -13.0
Maximum of Months 24.23 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.95 -13.0
February 10.26 -8.2
March 12.16 -2.6
April 16.75 4.03
May 21.10 12.37
June 23.06 16.19
July 24.05 17.83
August 23.46 17.50
September 21.08 12.89
October 16.99 6.03
November 12.17 -4.5
December 9.27 -11.1
     
Annual Sum or Average 16.64 4.02
Minimum of Months 8.95 -13.0
Maximum of Months 24.05 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 9.61 -13.0
February 11.32 -8.2
March 13.10 -2.6
April 17.28 4.03
May 21.16 12.37
June 22.86 16.19
July 23.76 17.83
August 23.35 17.50
September 21.15 12.89
October 17.30 6.03
November 12.90 -4.5
December 10.00 -11.1
     
Annual Sum or Average 17.01 4.02
Minimum of Months 9.61 -13.0
Maximum of Months 23.76 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -13.0
February 21.11 -8.2
March 21.14 -2.6
April 21.39 4.03
May 22.91 12.37
June 23.42 16.19
July 23.66 17.83
August 23.74 17.50
September 22.89 12.89
October 21.46 6.03
November 21.11 -4.5
December 21.11 -11.1
     
Annual Sum or Average 22.09 4.02
Minimum of Months 21.11 -13.0
Maximum of Months 23.74 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 6.98 -13.0
February 9.59 -8.2
March 11.51 -2.6
April 15.55 4.03
May 19.88 12.37
June 21.68 16.19
July 22.67 17.83
August 22.31 17.50
September 19.85 12.89
October 15.67 6.03
November 11.22 -4.5
December 7.75 -11.1
     
Annual Sum or Average 15.42 4.02
Minimum of Months 6.98 -13.0
Maximum of Months 22.67 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.79 -13.0
February 18.89 -8.2
March 18.93 -2.6
April 19.20 4.03
May 21.46 12.37
June 22.31 16.19
July 22.76 17.83
August 22.85 17.50
September 21.27 12.89
October 19.26 6.03
November 18.89 -4.5
December 18.85 -11.1
     
Annual Sum or Average 20.30 4.02
Minimum of Months 18.79 -13.0
Maximum of Months 22.85 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 18.97 -2.6
April 19.50 4.03
May 21.86 12.37
June 22.55 16.19
July 22.92 17.83
August 23.05 17.50
September 21.67 12.89
October 19.48 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.47 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 23.05 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 19.01 -2.6
April 19.70 4.03
May 22.00 12.37
June 22.61 16.19
July 22.94 17.83
August 23.06 17.50
September 21.79 12.89
October 19.60 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.53 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 23.06 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -13.0
February 20.55 -8.2
March 20.73 -2.6
April 21.21 4.03
May 21.66 12.37
June 21.73 16.19
July 21.74 17.83
August 21.75 17.50
September 21.67 12.89
October 21.22 6.03
November 20.62 -4.5
December 20.49 -11.1
     
Annual Sum or Average 21.16 4.02
Minimum of Months 20.49 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 18.94 -2.6
April 19.35 4.03
May 21.63 12.37
June 22.41 16.19
July 22.83 17.83
August 22.92 17.50
September 21.54 12.89
October 19.43 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.39 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.92 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -13.0
February 20.51 -8.2
March 20.64 -2.6
April 21.21 4.03
May 21.65 12.37
June 21.73 16.19
July 21.74 17.83
August 21.75 17.50
September 21.65 12.89
October 21.13 6.03
November 20.53 -4.5
December 20.47 -11.1
     
Annual Sum or Average 21.13 4.02
Minimum of Months 20.47 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.54 -13.0
February 20.67 -8.2
March 21.03 -2.6
April 21.56 4.03
May 21.73 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.73 12.89
October 21.47 6.03
November 20.81 -4.5
December 20.56 -11.1
     
Annual Sum or Average 21.28 4.02
Minimum of Months 20.54 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.24 -13.0
February 20.04 -8.2
March 20.86 -2.6
April 22.74 4.03
May 24.62 12.37
June 25.33 16.19
July 25.66 17.83
August 25.52 17.50
September 24.51 12.89
October 22.56 6.03
November 20.62 -4.5
December 19.46 -11.1
     
Annual Sum or Average 22.61 4.02
Minimum of Months 19.24 -13.0
Maximum of Months 25.66 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.95 -13.0
February 19.14 -8.2
March 19.93 -2.6
April 21.76 4.03
May 23.02 12.37
June 23.26 16.19
July 23.30 17.83
August 23.33 17.50
September 23.07 12.89
October 21.58 6.03
November 19.49 -4.5
December 18.98 -11.1
     
Annual Sum or Average 21.33 4.02
Minimum of Months 18.95 -13.0
Maximum of Months 23.33 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 -13.0
February 20.60 -8.2
March 20.90 -2.6
April 21.44 4.03
May 21.71 12.37
June 21.74 16.19
July 21.75 17.83
August 21.75 17.50
September 21.70 12.89
October 21.34 6.03
November 20.70 -4.5
December 20.52 -11.1
     
Annual Sum or Average 21.22 4.02
Minimum of Months 20.50 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 19.01 -2.6
April 19.99 4.03
May 22.16 12.37
June 22.78 16.19
July 23.03 17.83
August 23.10 17.50
September 22.15 12.89
October 19.95 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.66 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 23.10 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.33 -13.0
February 14.35 -8.2
March 15.62 -2.6
April 18.84 4.03
May 22.17 12.37
June 23.55 16.19
July 24.24 17.83
August 23.88 17.50
September 22.06 12.89
October 18.82 6.03
November 15.48 -4.5
December 13.60 -11.1
     
Annual Sum or Average 18.85 4.02
Minimum of Months 13.33 -13.0
Maximum of Months 24.24 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.22 -13.0
February 9.24 -8.2
March 11.05 -2.6
April 15.89 4.03
May 20.81 12.37
June 22.98 16.19
July 24.08 17.83
August 23.45 17.50
September 20.72 12.89
October 16.11 6.03
November 11.07 -4.5
December 8.47 -11.1
     
Annual Sum or Average 16.05 4.02
Minimum of Months 8.22 -13.0
Maximum of Months 24.08 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.76 -13.0
February 10.14 -8.2
March 11.99 -2.6
April 16.30 4.03
May 20.74 12.37
June 22.71 16.19
July 23.67 17.83
August 23.24 17.50
September 20.61 12.89
October 16.23 6.03
November 11.65 -4.5
December 9.06 -11.1
     
Annual Sum or Average 16.29 4.02
Minimum of Months 8.76 -13.0
Maximum of Months 23.67 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -13.0
February 21.11 -8.2
March 21.16 -2.6
April 21.41 4.03
May 22.58 12.37
June 23.06 16.19
July 23.31 17.83
August 23.33 17.50
September 22.38 12.89
October 21.33 6.03
November 21.11 -4.5
December 21.11 -11.1
     
Annual Sum or Average 21.92 4.02
Minimum of Months 21.11 -13.0
Maximum of Months 23.33 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 5.77 -13.0
February 8.54 -8.2
March 10.72 -2.6
April 14.92 4.03
May 19.56 12.37
June 21.54 16.19
July 22.56 17.83
August 22.17 17.50
September 19.39 12.89
October 14.92 6.03
November 10.18 -4.5
December 6.57 -11.1
     
Annual Sum or Average 14.77 4.02
Minimum of Months 5.77 -13.0
Maximum of Months 22.56 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.46 -13.0
February 20.47 -8.2
March 20.52 -2.6
April 20.76 4.03
May 21.49 12.37
June 21.65 16.19
July 21.70 17.83
August 21.73 17.50
September 21.45 12.89
October 20.76 6.03
November 20.47 -4.5
December 20.46 -11.1
     
Annual Sum or Average 21.00 4.02
Minimum of Months 20.46 -13.0
Maximum of Months 21.73 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 18.99 -2.6
April 19.47 4.03
May 21.43 12.37
June 22.12 16.19
July 22.52 17.83
August 22.65 17.50
September 21.04 12.89
October 19.29 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.27 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.65 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 19.02 -2.6
April 19.59 4.03
May 21.50 12.37
June 22.16 16.19
July 22.53 17.83
August 22.65 17.50
September 21.12 12.89
October 19.35 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.30 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.65 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -13.0
February 20.53 -8.2
March 20.69 -2.6
April 21.22 4.03
May 21.67 12.37
June 21.73 16.19
July 21.74 17.83
August 21.75 17.50
September 21.66 12.89
October 21.14 6.03
November 20.53 -4.5
December 20.47 -11.1
     
Annual Sum or Average 21.14 4.02
Minimum of Months 20.47 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 18.97 -2.6
April 19.38 4.03
May 21.32 12.37
June 22.07 16.19
July 22.51 17.83
August 22.59 17.50
September 21.05 12.89
October 19.29 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.24 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.59 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -13.0
February 18.89 -8.2
March 19.01 -2.6
April 19.69 4.03
May 21.66 12.37
June 22.40 16.19
July 22.71 17.83
August 22.80 17.50
September 21.54 12.89
October 19.55 6.03
November 18.89 -4.5
December 18.89 -11.1
     
Annual Sum or Average 20.42 4.02
Minimum of Months 18.89 -13.0
Maximum of Months 22.80 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -13.0
February 20.57 -8.2
March 20.88 -2.6
April 21.50 4.03
May 21.72 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.71 12.89
October 21.32 6.03
November 20.60 -4.5
December 20.48 -11.1
     
Annual Sum or Average 21.21 4.02
Minimum of Months 20.48 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.97 -13.0
February 17.87 -8.2
March 18.87 -2.6
April 20.80 4.03
May 22.80 12.37
June 23.60 16.19
July 23.95 17.83
August 23.76 17.50
September 22.53 12.89
October 20.47 6.03
November 18.42 -4.5
December 17.20 -11.1
     
Annual Sum or Average 20.62 4.02
Minimum of Months 16.97 -13.0
Maximum of Months 23.95 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -13.0
February 20.55 -8.2
March 20.81 -2.6
April 21.46 4.03
May 21.72 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.70 12.89
October 21.27 6.03
November 20.58 -4.5
December 20.48 -11.1
     
Annual Sum or Average 21.19 4.02
Minimum of Months 20.48 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -13.0
February 20.56 -8.2
March 20.86 -2.6
April 21.48 4.03
May 21.72 12.37
June 21.75 16.19
July 21.75 17.83
August 21.75 17.50
September 21.70 12.89
October 21.29 6.03
November 20.58 -4.5
December 20.48 -11.1
     
Annual Sum or Average 21.20 4.02
Minimum of Months 20.48 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -13.0
February 20.50 -8.2
March 20.64 -2.6
April 21.25 4.03
May 21.68 12.37
June 21.73 16.19
July 21.74 17.83
August 21.75 17.50
September 21.66 12.89
October 21.08 6.03
November 20.49 -4.5
December 20.47 -11.1
     
Annual Sum or Average 21.12 4.02
Minimum of Months 20.47 -13.0
Maximum of Months 21.75 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.71 -13.0
February 13.83 -8.2
March 15.28 -2.6
April 18.59 4.03
May 22.02 12.37
June 23.46 16.19
July 24.13 17.83
August 23.73 17.50
September 21.76 12.89
October 18.41 6.03
November 14.90 -4.5
December 13.01 -11.1
     
Annual Sum or Average 18.51 4.02
Minimum of Months 12.71 -13.0
Maximum of Months 24.13 17.83



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2015-09-14 08:44:19

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 7.85 -13.0
February 8.73 -8.2
March 10.56 -2.6
April 15.35 4.03
May 20.55 12.37
June 22.86 16.19
July 23.96 17.83
August 23.30 17.50
September 20.33 12.89
October 15.45 6.03
November 10.38 -4.5
December 8.09 -11.1
     
Annual Sum or Average 15.66 4.02
Minimum of Months 7.85 -13.0
Maximum of Months 23.96 17.83



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:19

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.276965E+12 230449.649 09-JAN-07:15 20847.837 39740.848 9362.349 156302.502 0.000 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.209743E+12 208135.562 05-FEB-07:15 20847.837 39740.848 9327.774 133983.396 39.594 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.192107E+12 167928.062 23-MAR-06:15 20847.837 39740.848 9300.604 97908.118 122.543 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.150068E+12 115410.740 12-APR-06:15 20847.837 39740.848 9278.404 44923.422 612.117 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.157081E+12 105728.901 01-MAY-06:15 20847.837 39740.848 9278.404 33274.594 2579.105 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.161794E+12 107561.894 30-JUN-07:00 25182.171 43578.554 9819.748 0.000 28973.308 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.171903E+12 107596.705 16-JUL-19:00 27551.975 28549.175 9353.762 0.000 37945.679 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.169279E+12 103377.492 26-AUG-07:00 25182.171 43578.554 9819.748 0.000 24788.906 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.151381E+12 98674.406 01-SEP-07:00 25182.171 43578.554 9819.748 0.000 20085.820 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.157438E+12 115279.660 26-OCT-06:15 20847.837 39740.848 9278.404 40864.752 351.706 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.201578E+12 195193.056 28-NOV-07:15 20847.837 39740.848 9318.871 121023.542 65.846 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.264173E+12 219935.438 19-DEC-07:15 20847.837 39740.848 9341.473 145807.073 2.094 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.226351E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.150068E+12 98674.406   20847.837 28549.175 9278.404 0.000 0.000 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.276965E+12 230449.649   27551.975 43578.554 9819.748 156302.502 37945.679 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:19

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.146113E+12 135185.010 27-JAN-09:15 19931.160 40096.028 0.000 75157.822 75157.822 75157.822 19931.160
February 0.122602E+12 123944.768 19-FEB-09:15 12672.377 40096.028 0.000 71176.364 71176.364 71176.364 12672.377
March 0.123410E+12 124904.647 18-MAR-08:15 9614.443 40096.028 0.000 75194.176 75194.176 75194.176 9614.443
April 0.104976E+12 114372.056 14-APR-08:15 0.000 40096.028 0.000 74276.028 74276.028 74276.028 0.000
May 0.999273E+11 113073.040 05-MAY-08:15 0.000 40096.028 0.000 72977.012 72977.012 72977.012 0.000
June 0.926357E+11 104717.418 02-JUN-08:15 0.000 40096.028 0.000 64621.390 64621.390 64621.390 0.000
July 0.928647E+11 101681.386 08-JUL-08:15 0.000 40096.028 0.000 61585.358 61585.358 61585.358 0.000
August 0.914298E+11 98257.850 25-AUG-08:15 0.000 40096.028 0.000 58161.822 58161.822 58161.822 0.000
September 0.893487E+11 105193.300 03-SEP-08:15 0.000 40096.028 0.000 65097.272 65097.272 65097.272 0.000
October 0.992009E+11 104352.585 20-OCT-08:15 0.000 40096.028 0.000 64256.557 64256.557 64256.557 0.000
November 0.116453E+12 116384.532 17-NOV-09:15 10271.592 40096.028 0.000 66016.911 66016.911 66016.911 10271.592
December 0.139273E+12 134284.347 25-DEC-09:15 24520.959 40096.028 0.000 69667.360 69667.360 69667.360 24520.959
                     
Annual Sum or Average 0.131823E+13         0.000        
Minimum of Months 0.893487E+11 98257.850   0.000 40096.028 0.000 58161.822 58161.822 58161.822 0.000
Maximum of Months 0.146113E+12 135185.010   24520.959 40096.028 0.000 75194.176 75194.176 75194.176 24520.959