Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Simulation Timestamp: 2015-09-14 08:44:18
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3300.41 | 822.31 | 885.99 |
Net Site Energy | 3300.41 | 822.31 | 885.99 |
Total Source Energy | 8041.63 | 2003.60 | 2158.77 |
Net Source Energy | 8041.63 | 2003.60 | 2158.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 310.79 | 99.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 287.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 298.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 636.85 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2143.06 | 1157.35 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 310.79 | 99.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 287.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 298.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 636.85 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 240.86 | 197.54 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 575.30 | 310.69 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 223.55 | 183.34 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 533.95 | 288.36 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2143.06 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2143.06 | 100.00 |
Total On-Site and Utility Electric Sources | 2143.06 | 100.00 |
Total Electricity End Uses | 2143.06 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 566.75 |
Time Setpoint Not Met During Occupied Cooling | 3679.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6375.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Weather File | Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Latitude [deg] | 41.98 |
Longitude [deg] | -87.9 |
Elevation [m] | 201.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | -20.00 | 0.00 | -20.00 | Wetbulb [C] | 4.90 | 270.00 |
CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 10.50 | 23.70 | Wetbulb [C] | 5.20 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 8.38 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 175.82 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8036.45 | 5831.75 | 2204.70 | 0.73 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 24582.48 | 16918.71 | 7663.77 | 0.69 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11392.64 | 7702.37 | 3690.27 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15596.65 | 11526.49 | 4070.16 | 0.74 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7734.3 | 3.28 | 11.20 | 11.87 | 11.20 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 23775.0 | 3.04 | 10.36 | 11.00 | 10.57 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11036.0 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14983.7 | 3.26 | 11.12 | 11.78 | 11.07 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.85 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 49165.44 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1130.94 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1130.94 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1679.37 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1530.03 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1148.62 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.77 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 513.30 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 3985.40 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1130.94 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 4523.76 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3585.24 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4523.76 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1781.30 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1586.21 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4523.44 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1142.24 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4523.44 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1393.50 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 723.65 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 571.44 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 4595.47 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1153.45 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4523.76 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3585.24 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 4523.76 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1462.99 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1676.54 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 4531.47 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1130.86 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4523.44 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1130.86 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 916.09 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 868.07 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 6184.91 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1917.88 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 4801.10 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 3904.06 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 5701.93 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1898.00 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1532.56 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 5591.28 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1622.48 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 5435.78 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1871.61 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 1156.22 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4656.71 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 19518.51 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 10452.02 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 7910.65 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.95 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.67 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 1.30 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 1.21 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.02 | 1.73 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.39 | 451.68 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.04 | 1184.63 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.46 | 532.57 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.79 | 900.01 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10254.32 | 12305.19 | 0.866 | 1.039 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.57 | 0.01496 |
RESTROOMFLR1 | 700.28 | 840.34 | 0.059 | 0.071 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.78 | 0.01496 |
MEETINGROOMFLR1 | 4525.37 | 5430.44 | 0.382 | 0.459 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.57 | 0.01496 |
GUESTROOM101 | 571.35 | 685.62 | 0.051 | 0.061 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM102 | 437.45 | 524.94 | 0.039 | 0.047 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM103 | 1546.08 | 1855.30 | 0.181 | 0.218 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM104 | 1402.15 | 1682.58 | 0.164 | 0.197 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.10 | 0.01496 |
GUESTROOM105 | 1832.86 | 2199.44 | 0.215 | 0.258 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
EMPLOYEELOUNGEFLR1 | 5710.60 | 6852.72 | 0.482 | 0.579 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
EXERCISECENTERFLR1 | 1380.31 | 1656.37 | 0.117 | 0.140 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.52 | 0.01496 |
FRONTOFFICEFLR1 | 3842.98 | 4611.58 | 0.324 | 0.389 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM201 | 922.48 | 1106.98 | 0.082 | 0.099 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.57 | 0.01496 |
GUESTROOM202_205 | 6142.91 | 7371.49 | 0.721 | 0.865 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM206_208 | 5032.97 | 6039.56 | 0.590 | 0.709 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.57 | 0.01496 |
GUESTROOM209_212 | 5738.84 | 6886.60 | 0.673 | 0.808 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM213 | 1670.63 | 2004.75 | 0.196 | 0.235 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM214 | 1644.60 | 1973.52 | 0.193 | 0.232 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM215_218 | 8824.67 | 10589.60 | 0.789 | 0.947 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM219 | 5746.55 | 6895.86 | 0.674 | 0.809 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM220_223 | 5502.47 | 6602.97 | 0.646 | 0.775 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM224 | 1648.43 | 1978.11 | 0.193 | 0.232 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM301 | 794.53 | 953.43 | 0.071 | 0.085 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.83 | 0.01496 |
GUESTROOM302_305 | 2148.27 | 2577.92 | 0.192 | 0.230 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM306_308 | 1940.12 | 2328.14 | 0.173 | 0.208 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM309_312 | 5767.36 | 6920.83 | 0.677 | 0.812 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM313 | 728.05 | 873.66 | 0.065 | 0.078 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.30 | 0.01496 |
GUESTROOM314 | 1576.69 | 1892.03 | 0.185 | 0.222 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.10 | 0.01496 |
GUESTROOM315_318 | 6195.40 | 7434.48 | 0.727 | 0.872 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM319 | 899.94 | 1079.92 | 0.080 | 0.097 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM320_323 | 5341.61 | 6409.94 | 0.627 | 0.752 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 29.70 | 0.01496 |
GUESTROOM324 | 582.61 | 699.13 | 0.052 | 0.062 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 30.10 | 0.01496 |
GUESTROOM401 | 2160.58 | 2592.70 | 0.254 | 0.304 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.25 | 0.01496 |
GUESTROOM402_405 | 3134.95 | 3761.94 | 0.280 | 0.336 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.25 | 0.01496 |
GUESTROOM406_408 | 2824.62 | 3389.54 | 0.252 | 0.303 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.25 | 0.01496 |
GUESTROOM409_412 | 7009.90 | 8411.88 | 0.822 | 0.987 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.25 | 0.01496 |
GUESTROOM413 | 1071.77 | 1286.12 | 0.096 | 0.115 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.04 | 0.01496 |
GUESTROOM414 | 850.29 | 1020.35 | 0.076 | 0.091 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.30 | 0.01496 |
GUESTROOM415_418 | 6578.15 | 7893.79 | 0.772 | 0.926 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 30.49 | 0.01496 |
GUESTROOM419 | 1806.65 | 2167.98 | 0.212 | 0.254 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 30.88 | 0.01496 |
GUESTROOM420_423 | 6434.10 | 7720.92 | 0.755 | 0.906 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 30.49 | 0.01496 |
GUESTROOM424 | 1846.66 | 2215.99 | 0.217 | 0.260 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 30.88 | 0.01496 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
CORRIDORFLR1 | 17982.47 | 21578.96 | 1.518 | 1.822 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.78 | 0.01496 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
CORRIDORFLR2 | 3066.35 | 3679.61 | 0.259 | 0.310 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.83 | 0.01496 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
CORRIDORFLR3 | 1818.35 | 2182.02 | 0.153 | 0.184 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 31.57 | 0.01496 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 | |
CORRIDORFLR4 | 2811.18 | 3373.42 | 0.237 | 0.285 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.30 | 0.01496 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.01496 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2130.28 | 2556.34 | 0.061 | 0.236 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -20.00 | 0.00065 |
RESTROOMFLR1 | 87.78 | 105.34 | 0.003 | 0.003 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -20.00 | 0.00065 |
MEETINGROOMFLR1 | 762.16 | 914.59 | 0.022 | 0.126 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -20.00 | 0.00065 |
GUESTROOM101 | 66.43 | 79.71 | 0.002 | 0.013 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -20.00 | 0.00065 |
GUESTROOM102 | 99.78 | 119.73 | 0.003 | 0.013 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -20.00 | 0.00065 |
GUESTROOM103 | 845.97 | 1015.17 | 0.024 | 0.029 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -20.00 | 0.00065 |
GUESTROOM104 | 721.57 | 865.88 | 0.021 | 0.025 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -20.00 | 0.00065 |
GUESTROOM105 | 403.72 | 484.47 | 0.012 | 0.014 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -20.00 | 0.00065 |
EMPLOYEELOUNGEFLR1 | 380.37 | 456.44 | 0.011 | 0.051 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -20.00 | 0.00065 |
EXERCISECENTERFLR1 | 233.42 | 280.11 | 0.007 | 0.043 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -20.00 | 0.00065 |
FRONTOFFICEFLR1 | 1359.64 | 1631.57 | 0.039 | 0.056 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -20.00 | 0.00065 |
GUESTROOM201 | 349.36 | 419.23 | 0.009 | 0.013 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -20.00 | 0.00065 |
GUESTROOM202_205 | 1514.58 | 1817.49 | 0.044 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -20.00 | 0.00065 |
GUESTROOM206_208 | 1153.45 | 1384.15 | 0.033 | 0.043 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -20.00 | 0.00065 |
GUESTROOM209_212 | 1263.24 | 1515.89 | 0.036 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -20.00 | 0.00065 |
GUESTROOM213 | 930.92 | 1117.10 | 0.027 | 0.032 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -20.00 | 0.00065 |
GUESTROOM214 | 768.38 | 922.06 | 0.022 | 0.027 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -20.00 | 0.00065 |
GUESTROOM215_218 | 377.31 | 452.77 | 0.010 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | -20.00 | 0.00065 |
GUESTROOM219 | 398.40 | 478.08 | 0.012 | 0.014 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -20.00 | 0.00065 |
GUESTROOM220_223 | 1092.40 | 1310.88 | 0.032 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -20.00 | 0.00065 |
GUESTROOM224 | 607.79 | 729.35 | 0.018 | 0.021 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -20.00 | 0.00065 |
GUESTROOM301 | 437.62 | 525.15 | 0.012 | 0.014 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | -20.00 | 0.00065 |
GUESTROOM302_305 | 841.57 | 1009.88 | 0.023 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -20.00 | 0.00065 |
GUESTROOM306_308 | 684.50 | 821.39 | 0.018 | 0.043 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -20.00 | 0.00065 |
GUESTROOM309_312 | 1513.67 | 1816.40 | 0.044 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -20.00 | 0.00065 |
GUESTROOM313 | 695.57 | 834.69 | 0.019 | 0.022 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -20.00 | 0.00065 |
GUESTROOM314 | 843.65 | 1012.38 | 0.024 | 0.029 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:30:00 | -20.00 | 0.00065 |
GUESTROOM315_318 | 1562.37 | 1874.85 | 0.045 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -20.00 | 0.00065 |
GUESTROOM319 | 146.64 | 175.97 | 0.004 | 0.013 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -20.00 | 0.00065 |
GUESTROOM320_323 | 1345.25 | 1614.30 | 0.039 | 0.054 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -20.00 | 0.00065 |
GUESTROOM324 | 324.31 | 389.17 | 0.009 | 0.013 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
GUESTROOM401 | 1044.73 | 1253.68 | 0.030 | 0.036 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -20.00 | 0.00065 |
GUESTROOM402_405 | 1906.58 | 2287.89 | 0.051 | 0.061 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 21:30:00 | -20.00 | 0.00065 |
GUESTROOM406_408 | 1593.54 | 1912.25 | 0.043 | 0.051 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -20.00 | 0.00065 |
GUESTROOM409_412 | 2537.60 | 3045.12 | 0.073 | 0.088 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -20.00 | 0.00065 |
GUESTROOM413 | 1058.09 | 1269.70 | 0.028 | 0.034 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -20.00 | 0.00065 |
GUESTROOM414 | 753.58 | 904.30 | 0.020 | 0.024 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 21:00:00 | -20.00 | 0.00065 |
GUESTROOM415_418 | 2445.55 | 2934.66 | 0.071 | 0.085 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -20.00 | 0.00065 |
GUESTROOM419 | 798.61 | 958.33 | 0.023 | 0.028 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -20.00 | 0.00065 |
GUESTROOM420_423 | 2315.97 | 2779.16 | 0.067 | 0.080 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -20.00 | 0.00065 |
GUESTROOM424 | 1006.21 | 1207.45 | 0.029 | 0.035 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | -20.00 | 0.00065 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | -20.00 | 0.00065 | |
CORRIDORFLR1 | 39050.91 | 46861.09 | 1.125 | 1.350 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -20.00 | 0.00065 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | -20.00 | 0.00065 | |
REARSTAIRSFLR2 | 154.89 | 185.87 | 0.003 | 0.006 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
CORRIDORFLR2 | 1751.49 | 2101.78 | 0.051 | 0.061 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -20.00 | 0.00065 |
FRONTSTAIRSFLR2 | 436.93 | 524.31 | 0.009 | 0.010 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
REARSTAIRSFLR3 | 310.03 | 372.04 | 0.006 | 0.007 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
CORRIDORFLR3 | 2259.90 | 2711.88 | 0.065 | 0.078 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
FRONTSTAIRSFLR3 | 597.32 | 716.79 | 0.012 | 0.014 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
REARSTAIRSFLR4 | 557.27 | 668.72 | 0.011 | 0.013 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
CORRIDORFLR4 | 3584.47 | 4301.36 | 0.103 | 0.124 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
FRONTSTAIRSFLR4 | 797.46 | 956.95 | 0.016 | 0.019 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -20.00 | 0.00065 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.39 | 0.39 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.04 | 1.04 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.46 | 0.46 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.79 | 0.79 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 1.04 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 3347.00 | 6890.00 | 2138.00 |
RESTROOMFLR1 | 1313.75 | 6674.00 | 534.50 |
MEETINGROOMFLR1 | 1613.25 | 2786.25 | 314.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 2537.50 | 8691.25 | 2532.00 |
GUESTROOM104 | 1615.00 | 8569.25 | 1612.75 |
GUESTROOM105 | 282.25 | 8176.00 | 215.75 |
EMPLOYEELOUNGEFLR1 | 3141.75 | 2132.75 | 351.75 |
EXERCISECENTERFLR1 | 1783.25 | 2892.25 | 75.75 |
FRONTOFFICEFLR1 | 2203.50 | 5590.50 | 741.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1316.75 | 8183.75 | 1192.50 |
GUESTROOM206_208 | 1135.50 | 8152.00 | 998.25 |
GUESTROOM209_212 | 946.25 | 8347.75 | 887.25 |
GUESTROOM213 | 2579.25 | 8480.00 | 2541.00 |
GUESTROOM214 | 1521.75 | 8182.25 | 1428.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3560.25 | 4616.00 | 539.25 |
GUESTROOM220_223 | 610.00 | 8007.75 | 476.50 |
GUESTROOM224 | 1478.75 | 8106.75 | 1376.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1393.75 | 8391.50 | 1338.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 2315.25 | 8189.50 | 2214.75 |
GUESTROOM315_318 | 742.25 | 7914.75 | 540.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1074.75 | 8145.50 | 976.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 3940.50 | 7993.50 | 3566.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 2763.75 | 7769.50 | 2184.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2470.75 | 7649.00 | 1750.75 |
GUESTROOM419 | 2440.25 | 7757.00 | 1987.75 |
GUESTROOM420_423 | 2528.50 | 7673.75 | 1832.00 |
GUESTROOM424 | 3227.50 | 7827.00 | 2781.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7580.75 | 8760.00 | 6375.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
RESTROOMFLR1 | 373.50 | 894.50 | 373.50 | 894.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 18.00 | 39.00 | 18.00 | 39.00 |
GUESTROOM104 | 13.25 | 40.00 | 13.25 | 40.00 |
GUESTROOM105 | 0.75 | 47.00 | 0.75 | 47.00 |
EMPLOYEELOUNGEFLR1 | 434.75 | 1485.00 | 317.75 | 1017.25 |
EXERCISECENTERFLR1 | 1.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 16.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 10.25 | 30.50 | 10.25 | 30.50 |
GUESTROOM206_208 | 8.50 | 38.25 | 8.50 | 38.25 |
GUESTROOM209_212 | 8.25 | 29.50 | 8.25 | 29.50 |
GUESTROOM213 | 15.00 | 30.25 | 15.00 | 30.25 |
GUESTROOM214 | 12.50 | 30.25 | 12.50 | 30.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2428.75 | 0.00 | 2428.75 |
GUESTROOM220_223 | 5.25 | 28.25 | 5.25 | 28.25 |
GUESTROOM224 | 13.50 | 30.25 | 13.50 | 30.25 |
GUESTROOM301 | 28.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 15.50 | 29.75 | 15.50 | 29.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 19.25 | 29.75 | 19.25 | 29.75 |
GUESTROOM315_318 | 6.75 | 29.25 | 6.75 | 29.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 12.00 | 26.50 | 12.00 | 26.50 |
GUESTROOM324 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 29.00 | 50.25 | 29.00 | 50.25 |
GUESTROOM402_405 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 20.00 | 36.25 | 20.00 | 36.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 18.50 | 33.50 | 18.50 | 33.50 |
GUESTROOM419 | 18.25 | 36.00 | 18.25 | 36.00 |
GUESTROOM420_423 | 20.00 | 33.00 | 20.00 | 33.00 |
GUESTROOM424 | 18.50 | 35.25 | 18.50 | 35.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 5.50 | 2879.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 11.50 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 11.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.25 | 266.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 14.50 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 16.75 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 36.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 17.25 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 18.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 341.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 18.25 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 593.00 | 4607.00 | 566.75 | 3679.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:18
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.010215 |
REARSTAIRSFLR3 UNITHEATER | 0.007248 |
FRONTSTAIRSFLR3 UNITHEATER | 0.013963 |
REARSTAIRSFLR4 UNITHEATER | 0.013027 |
FRONTSTAIRSFLR4 UNITHEATER | 0.018641 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.010215 |
REARSTAIRSFLR3UNITHEATERFAN | 0.007248 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.013963 |
REARSTAIRSFLR4UNITHEATERFAN | 0.013027 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.018641 |
SAC_FRONTOFFICE SUPPLY FAN | 0.389096 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.04 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.789408 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 313.85 |
CORRIDORFLR1 PTAC HEATING COIL | 49165.44 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1130.94 |
102 PTAC HEATING COIL | 1130.94 |
103 PTAC HEATING COIL | 1679.37 |
104 PTAC HEATING COIL | 1530.03 |
105 PTAC HEATING COIL | 1148.62 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 313.77 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 513.30 |
CORRIDORFLR2 PTAC HEATING COIL | 3985.40 |
201 PTAC HEATING COIL | 1130.94 |
202_205 PTAC HEATING COIL | 4523.76 |
206_208 PTAC HEATING COIL | 3585.24 |
209_212 PTAC HEATING COIL | 4523.76 |
213 PTAC HEATING COIL | 1781.30 |
214 PTAC HEATING COIL | 1586.21 |
215_218 PTAC HEATING COIL | 4523.44 |
219 PTAC HEATING COIL | 1142.24 |
220_223 PTAC HEATING COIL | 4523.44 |
224 PTAC HEATING COIL | 1393.50 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 723.65 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 571.44 |
CORRIDORFLR3 PTAC HEATING COIL | 4595.47 |
301 PTAC HEATING COIL | 1153.45 |
302_305 PTAC HEATING COIL | 4523.76 |
306_308 PTAC HEATING COIL | 3585.24 |
309_312 PTAC HEATING COIL | 4523.76 |
313 PTAC HEATING COIL | 1462.99 |
314 PTAC HEATING COIL | 1676.54 |
315_318 PTAC HEATING COIL | 4531.47 |
319 PTAC HEATING COIL | 1130.86 |
320_323 PTAC HEATING COIL | 4523.44 |
324 PTAC HEATING COIL | 1130.86 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 916.09 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 868.07 |
CORRIDORFLR4 PTAC HEATING COIL | 6184.91 |
401 PTAC HEATING COIL | 1917.88 |
402_405 PTAC HEATING COIL | 4801.10 |
406_408 PTAC HEATING COIL | 3904.06 |
409_412 PTAC HEATING COIL | 5701.93 |
413 PTAC HEATING COIL | 1898.00 |
414 PTAC HEATING COIL | 1532.56 |
415_418 PTAC HEATING COIL | 5591.28 |
419 PTAC HEATING COIL | 1622.48 |
420_423 PTAC HEATING COIL | 5435.78 |
424 PTAC HEATING COIL | 1871.61 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 1156.22 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.725662 | 0.389096 | 8036.45 |
SAC_FRONTLOUNGE COOLING COIL | 0.688243 | 1.04 | 24582.48 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.458782 | 11392.64 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.739036 | 0.789408 | 15596.65 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.04 |
RESTROOMFLR1 DIRECT AIR | 0.070890 |
MEETINGROOMFLR1 DIRECT AIR | 0.458782 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.578716 |
EXERCISECENTERFLR1 DIRECT AIR | 0.139802 |
FRONTOFFICEFLR1 DIRECT AIR | 0.389096 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.389096 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.04 |
SAC_MEETINGROOM MAIN BRANCH | 0.458782 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.789408 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.389096 |
SAC_FRONTLOUNGE | 1.04 |
SAC_MEETINGROOM | 0.458782 |
SAC_EXC_EMPLGE_RESTRM | 0.789408 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.389096 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.04 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.458782 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.789408 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.389096 | 0.389096 | 0.389096 | 0.389096 | 4656.71 | 8036.45 | 1.00 |
SAC_FRONTLOUNGE | 1.04 | 1.04 | 1.04 | 1.04 | 19518.51 | 24582.48 | 1.00 |
SAC_MEETINGROOM | 0.458782 | 0.458782 | 0.458782 | 0.458782 | 10452.02 | 11392.64 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.789408 | 0.789408 | 0.789408 | 0.789408 | 7910.65 | 15596.65 | 0.177097 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4656.71 |
SAC_FRONTLOUNGE HEATING COIL | 19518.51 |
SAC_MEETINGROOM HEATING COIL | 10452.02 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 7910.65 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.458782 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.65 | -4.6 |
February | 15.37 | -2.5 |
March | 17.28 | 3.82 |
April | 19.91 | 9.95 |
May | 22.22 | 15.31 |
June | 23.83 | 21.11 |
July | 25.02 | 24.13 |
August | 24.26 | 21.78 |
September | 23.23 | 18.14 |
October | 20.34 | 10.98 |
November | 17.67 | 4.73 |
December | 15.49 | -3.7 |
Annual Sum or Average | 19.96 | 9.99 |
Minimum of Months | 14.65 | -4.6 |
Maximum of Months | 25.02 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.45 | -4.6 |
February | 21.61 | -2.5 |
March | 22.38 | 3.82 |
April | 23.49 | 9.95 |
May | 24.47 | 15.31 |
June | 25.59 | 21.11 |
July | 26.51 | 24.13 |
August | 25.87 | 21.78 |
September | 25.00 | 18.14 |
October | 23.60 | 10.98 |
November | 22.56 | 4.73 |
December | 21.48 | -3.7 |
Annual Sum or Average | 23.68 | 9.99 |
Minimum of Months | 21.45 | -4.6 |
Maximum of Months | 26.51 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.86 | -4.6 |
February | 14.60 | -2.5 |
March | 16.46 | 3.82 |
April | 19.12 | 9.95 |
May | 21.47 | 15.31 |
June | 23.17 | 21.11 |
July | 24.35 | 24.13 |
August | 23.57 | 21.78 |
September | 22.49 | 18.14 |
October | 19.55 | 10.98 |
November | 16.91 | 4.73 |
December | 14.69 | -3.7 |
Annual Sum or Average | 19.21 | 9.99 |
Minimum of Months | 13.86 | -4.6 |
Maximum of Months | 24.35 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -4.6 |
February | 21.14 | -2.5 |
March | 21.25 | 3.82 |
April | 21.94 | 9.95 |
May | 22.70 | 15.31 |
June | 23.42 | 21.11 |
July | 23.75 | 24.13 |
August | 23.60 | 21.78 |
September | 23.15 | 18.14 |
October | 21.94 | 10.98 |
November | 21.52 | 4.73 |
December | 21.12 | -3.7 |
Annual Sum or Average | 22.23 | 9.99 |
Minimum of Months | 21.12 | -4.6 |
Maximum of Months | 23.75 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.43 | -4.6 |
February | 21.63 | -2.5 |
March | 22.13 | 3.82 |
April | 22.68 | 9.95 |
May | 23.20 | 15.31 |
June | 23.59 | 21.11 |
July | 23.75 | 24.13 |
August | 23.66 | 21.78 |
September | 23.46 | 18.14 |
October | 22.82 | 10.98 |
November | 22.28 | 4.73 |
December | 21.56 | -3.7 |
Annual Sum or Average | 22.69 | 9.99 |
Minimum of Months | 21.43 | -4.6 |
Maximum of Months | 23.75 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.27 | -4.6 |
February | 21.37 | -2.5 |
March | 21.83 | 3.82 |
April | 22.65 | 9.95 |
May | 23.59 | 15.31 |
June | 23.82 | 21.11 |
July | 23.87 | 24.13 |
August | 23.85 | 21.78 |
September | 23.76 | 18.14 |
October | 23.12 | 10.98 |
November | 22.13 | 4.73 |
December | 21.27 | -3.7 |
Annual Sum or Average | 22.72 | 9.99 |
Minimum of Months | 21.27 | -4.6 |
Maximum of Months | 23.87 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.53 | -4.6 |
February | 23.73 | -2.5 |
March | 24.39 | 3.82 |
April | 25.25 | 9.95 |
May | 26.15 | 15.31 |
June | 26.68 | 21.11 |
July | 26.95 | 24.13 |
August | 26.76 | 21.78 |
September | 26.43 | 18.14 |
October | 25.54 | 10.98 |
November | 24.59 | 4.73 |
December | 23.67 | -3.7 |
Annual Sum or Average | 25.31 | 9.99 |
Minimum of Months | 23.53 | -4.6 |
Maximum of Months | 26.95 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.02 | -4.6 |
February | 19.15 | -2.5 |
March | 19.85 | 3.82 |
April | 21.14 | 9.95 |
May | 22.48 | 15.31 |
June | 23.15 | 21.11 |
July | 23.30 | 24.13 |
August | 23.26 | 21.78 |
September | 22.93 | 18.14 |
October | 21.60 | 10.98 |
November | 20.27 | 4.73 |
December | 19.00 | -3.7 |
Annual Sum or Average | 21.27 | 9.99 |
Minimum of Months | 19.00 | -4.6 |
Maximum of Months | 23.30 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.95 | -4.6 |
February | 19.05 | -2.5 |
March | 19.56 | 3.82 |
April | 20.83 | 9.95 |
May | 22.21 | 15.31 |
June | 23.02 | 21.11 |
July | 23.26 | 24.13 |
August | 23.17 | 21.78 |
September | 22.73 | 18.14 |
October | 21.23 | 10.98 |
November | 20.00 | 4.73 |
December | 18.93 | -3.7 |
Annual Sum or Average | 21.09 | 9.99 |
Minimum of Months | 18.93 | -4.6 |
Maximum of Months | 23.26 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -4.6 |
February | 20.59 | -2.5 |
March | 20.84 | 3.82 |
April | 21.20 | 9.95 |
May | 21.65 | 15.31 |
June | 21.75 | 21.11 |
July | 21.75 | 24.13 |
August | 21.75 | 21.78 |
September | 21.72 | 18.14 |
October | 21.40 | 10.98 |
November | 20.96 | 4.73 |
December | 20.54 | -3.7 |
Annual Sum or Average | 21.23 | 9.99 |
Minimum of Months | 20.53 | -4.6 |
Maximum of Months | 21.75 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -4.6 |
February | 20.71 | -2.5 |
March | 21.08 | 3.82 |
April | 21.38 | 9.95 |
May | 21.72 | 15.31 |
June | 21.75 | 21.11 |
July | 21.76 | 24.13 |
August | 21.75 | 21.78 |
September | 21.75 | 18.14 |
October | 21.58 | 10.98 |
November | 21.10 | 4.73 |
December | 20.65 | -3.7 |
Annual Sum or Average | 21.32 | 9.99 |
Minimum of Months | 20.62 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | -4.6 |
February | 21.13 | -2.5 |
March | 21.49 | 3.82 |
April | 21.63 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.72 | 10.98 |
November | 21.44 | 4.73 |
December | 21.07 | -3.7 |
Annual Sum or Average | 21.52 | 9.99 |
Minimum of Months | 20.99 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | -4.6 |
February | 22.28 | -2.5 |
March | 22.62 | 3.82 |
April | 22.71 | 9.95 |
May | 22.71 | 15.31 |
June | 22.67 | 21.11 |
July | 22.51 | 24.13 |
August | 22.67 | 21.78 |
September | 22.80 | 18.14 |
October | 22.79 | 10.98 |
November | 22.67 | 4.73 |
December | 22.19 | -3.7 |
Annual Sum or Average | 22.56 | 9.99 |
Minimum of Months | 22.07 | -4.6 |
Maximum of Months | 22.80 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 49.70 | -4.6 |
February | 49.97 | -2.5 |
March | 50.69 | 3.82 |
April | 51.54 | 9.95 |
May | 52.43 | 15.31 |
June | 52.96 | 21.11 |
July | 53.36 | 24.13 |
August | 53.13 | 21.78 |
September | 52.76 | 18.14 |
October | 51.73 | 10.98 |
November | 50.77 | 4.73 |
December | 49.99 | -3.7 |
Annual Sum or Average | 51.60 | 9.99 |
Minimum of Months | 49.70 | -4.6 |
Maximum of Months | 53.36 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 67.27 | -4.6 |
February | 67.49 | -2.5 |
March | 68.21 | 3.82 |
April | 69.38 | 9.95 |
May | 70.64 | 15.31 |
June | 71.15 | 21.11 |
July | 71.81 | 24.13 |
August | 71.56 | 21.78 |
September | 71.15 | 18.14 |
October | 69.65 | 10.98 |
November | 68.41 | 4.73 |
December | 67.69 | -3.7 |
Annual Sum or Average | 69.55 | 9.99 |
Minimum of Months | 67.27 | -4.6 |
Maximum of Months | 71.81 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | -4.6 |
February | 22.49 | -2.5 |
March | 22.96 | 3.82 |
April | 23.34 | 9.95 |
May | 23.65 | 15.31 |
June | 23.86 | 21.11 |
July | 23.89 | 24.13 |
August | 23.88 | 21.78 |
September | 23.82 | 18.14 |
October | 23.46 | 10.98 |
November | 23.05 | 4.73 |
December | 22.40 | -3.7 |
Annual Sum or Average | 23.26 | 9.99 |
Minimum of Months | 22.27 | -4.6 |
Maximum of Months | 23.89 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | -4.6 |
February | 21.69 | -2.5 |
March | 22.38 | 3.82 |
April | 23.07 | 9.95 |
May | 23.72 | 15.31 |
June | 23.88 | 21.11 |
July | 23.89 | 24.13 |
August | 23.89 | 21.78 |
September | 23.86 | 18.14 |
October | 23.42 | 10.98 |
November | 22.54 | 4.73 |
December | 21.55 | -3.7 |
Annual Sum or Average | 22.96 | 9.99 |
Minimum of Months | 21.55 | -4.6 |
Maximum of Months | 23.89 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.50 | -4.6 |
February | 14.23 | -2.5 |
March | 16.46 | 3.82 |
April | 19.54 | 9.95 |
May | 22.26 | 15.31 |
June | 24.24 | 21.11 |
July | 25.61 | 24.13 |
August | 24.66 | 21.78 |
September | 23.35 | 18.14 |
October | 19.93 | 10.98 |
November | 16.99 | 4.73 |
December | 14.40 | -3.7 |
Annual Sum or Average | 19.62 | 9.99 |
Minimum of Months | 13.50 | -4.6 |
Maximum of Months | 25.61 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.98 | -4.6 |
February | 18.42 | -2.5 |
March | 19.82 | 3.82 |
April | 21.63 | 9.95 |
May | 23.34 | 15.31 |
June | 24.47 | 21.11 |
July | 25.18 | 24.13 |
August | 24.69 | 21.78 |
September | 23.98 | 18.14 |
October | 22.03 | 10.98 |
November | 20.16 | 4.73 |
December | 18.48 | -3.7 |
Annual Sum or Average | 21.70 | 9.99 |
Minimum of Months | 17.98 | -4.6 |
Maximum of Months | 25.18 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.25 | -4.6 |
February | 14.09 | -2.5 |
March | 16.57 | 3.82 |
April | 19.80 | 9.95 |
May | 22.75 | 15.31 |
June | 24.62 | 21.11 |
July | 26.03 | 24.13 |
August | 25.14 | 21.78 |
September | 23.92 | 18.14 |
October | 20.31 | 10.98 |
November | 16.94 | 4.73 |
December | 14.18 | -3.7 |
Annual Sum or Average | 19.83 | 9.99 |
Minimum of Months | 13.25 | -4.6 |
Maximum of Months | 26.03 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | -4.6 |
February | 21.27 | -2.5 |
March | 21.81 | 3.82 |
April | 22.73 | 9.95 |
May | 23.76 | 15.31 |
June | 23.91 | 21.11 |
July | 24.05 | 24.13 |
August | 23.93 | 21.78 |
September | 23.87 | 18.14 |
October | 23.24 | 10.98 |
November | 22.10 | 4.73 |
December | 21.15 | -3.7 |
Annual Sum or Average | 22.76 | 9.99 |
Minimum of Months | 21.15 | -4.6 |
Maximum of Months | 24.05 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.94 | -4.6 |
February | 12.88 | -2.5 |
March | 15.29 | 3.82 |
April | 18.58 | 9.95 |
May | 21.62 | 15.31 |
June | 23.68 | 21.11 |
July | 25.09 | 24.13 |
August | 24.14 | 21.78 |
September | 22.83 | 18.14 |
October | 19.09 | 10.98 |
November | 15.75 | 4.73 |
December | 12.91 | -3.7 |
Annual Sum or Average | 18.68 | 9.99 |
Minimum of Months | 11.94 | -4.6 |
Maximum of Months | 25.09 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.88 | -4.6 |
February | 18.94 | -2.5 |
March | 19.24 | 3.82 |
April | 20.53 | 9.95 |
May | 22.34 | 15.31 |
June | 23.18 | 21.11 |
July | 23.32 | 24.13 |
August | 23.29 | 21.78 |
September | 22.90 | 18.14 |
October | 20.74 | 10.98 |
November | 19.76 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 21.01 | 9.99 |
Minimum of Months | 18.88 | -4.6 |
Maximum of Months | 23.32 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -4.6 |
February | 20.72 | -2.5 |
March | 21.06 | 3.82 |
April | 21.36 | 9.95 |
May | 21.73 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.56 | 10.98 |
November | 21.11 | 4.73 |
December | 20.63 | -3.7 |
Annual Sum or Average | 21.32 | 9.99 |
Minimum of Months | 20.63 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | -4.6 |
February | 20.76 | -2.5 |
March | 21.12 | 3.82 |
April | 21.41 | 9.95 |
May | 21.74 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.60 | 10.98 |
November | 21.16 | 4.73 |
December | 20.67 | -3.7 |
Annual Sum or Average | 21.35 | 9.99 |
Minimum of Months | 20.66 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | -4.6 |
February | 20.77 | -2.5 |
March | 21.14 | 3.82 |
April | 21.42 | 9.95 |
May | 21.74 | 15.31 |
June | 21.75 | 21.11 |
July | 21.76 | 24.13 |
August | 21.75 | 21.78 |
September | 21.75 | 18.14 |
October | 21.62 | 10.98 |
November | 21.18 | 4.73 |
December | 20.68 | -3.7 |
Annual Sum or Average | 21.36 | 9.99 |
Minimum of Months | 20.67 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -4.6 |
February | 20.57 | -2.5 |
March | 20.83 | 3.82 |
April | 21.20 | 9.95 |
May | 21.68 | 15.31 |
June | 21.75 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.74 | 18.14 |
October | 21.42 | 10.98 |
November | 20.94 | 4.73 |
December | 20.51 | -3.7 |
Annual Sum or Average | 21.23 | 9.99 |
Minimum of Months | 20.51 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -4.6 |
February | 20.72 | -2.5 |
March | 21.15 | 3.82 |
April | 21.44 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.64 | 10.98 |
November | 21.14 | 4.73 |
December | 20.65 | -3.7 |
Annual Sum or Average | 21.35 | 9.99 |
Minimum of Months | 20.63 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -4.6 |
February | 22.21 | -2.5 |
March | 23.01 | 3.82 |
April | 23.23 | 9.95 |
May | 23.33 | 15.31 |
June | 23.33 | 21.11 |
July | 23.33 | 24.13 |
August | 23.33 | 21.78 |
September | 23.33 | 18.14 |
October | 23.31 | 10.98 |
November | 22.83 | 4.73 |
December | 22.10 | -3.7 |
Annual Sum or Average | 22.93 | 9.99 |
Minimum of Months | 21.82 | -4.6 |
Maximum of Months | 23.33 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 28.98 | -4.6 |
February | 29.28 | -2.5 |
March | 30.13 | 3.82 |
April | 31.41 | 9.95 |
May | 32.74 | 15.31 |
June | 33.32 | 21.11 |
July | 33.84 | 24.13 |
August | 33.53 | 21.78 |
September | 33.12 | 18.14 |
October | 31.69 | 10.98 |
November | 30.32 | 4.73 |
December | 29.32 | -3.7 |
Annual Sum or Average | 31.49 | 9.99 |
Minimum of Months | 28.98 | -4.6 |
Maximum of Months | 33.84 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -4.6 |
February | 21.76 | -2.5 |
March | 21.85 | 3.82 |
April | 22.16 | 9.95 |
May | 22.48 | 15.31 |
June | 22.91 | 21.11 |
July | 23.41 | 24.13 |
August | 23.05 | 21.78 |
September | 22.70 | 18.14 |
October | 22.17 | 10.98 |
November | 21.94 | 4.73 |
December | 21.75 | -3.7 |
Annual Sum or Average | 22.33 | 9.99 |
Minimum of Months | 21.73 | -4.6 |
Maximum of Months | 23.41 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | -4.6 |
February | 20.91 | -2.5 |
March | 21.34 | 3.82 |
April | 21.55 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.71 | 10.98 |
November | 21.28 | 4.73 |
December | 20.82 | -3.7 |
Annual Sum or Average | 21.43 | 9.99 |
Minimum of Months | 20.79 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -4.6 |
February | 20.73 | -2.5 |
March | 21.15 | 3.82 |
April | 21.44 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.65 | 10.98 |
November | 21.14 | 4.73 |
December | 20.65 | -3.7 |
Annual Sum or Average | 21.35 | 9.99 |
Minimum of Months | 20.64 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.31 | -4.6 |
February | 16.83 | -2.5 |
March | 18.71 | 3.82 |
April | 21.08 | 9.95 |
May | 23.40 | 15.31 |
June | 24.86 | 21.11 |
July | 25.76 | 24.13 |
August | 25.13 | 21.78 |
September | 24.18 | 18.14 |
October | 21.52 | 10.98 |
November | 19.04 | 4.73 |
December | 16.86 | -3.7 |
Annual Sum or Average | 21.16 | 9.99 |
Minimum of Months | 16.31 | -4.6 |
Maximum of Months | 25.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.40 | -4.6 |
February | 12.17 | -2.5 |
March | 15.14 | 3.82 |
April | 19.04 | 9.95 |
May | 22.67 | 15.31 |
June | 25.10 | 21.11 |
July | 26.79 | 24.13 |
August | 25.61 | 21.78 |
September | 23.99 | 18.14 |
October | 19.55 | 10.98 |
November | 15.70 | 4.73 |
December | 12.31 | -3.7 |
Annual Sum or Average | 19.16 | 9.99 |
Minimum of Months | 11.40 | -4.6 |
Maximum of Months | 26.79 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.22 | -4.6 |
February | 13.07 | -2.5 |
March | 15.75 | 3.82 |
April | 19.28 | 9.95 |
May | 22.61 | 15.31 |
June | 24.72 | 21.11 |
July | 26.25 | 24.13 |
August | 25.27 | 21.78 |
September | 23.90 | 18.14 |
October | 19.79 | 10.98 |
November | 16.15 | 4.73 |
December | 13.12 | -3.7 |
Annual Sum or Average | 19.38 | 9.99 |
Minimum of Months | 12.22 | -4.6 |
Maximum of Months | 26.25 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -4.6 |
February | 21.12 | -2.5 |
March | 21.26 | 3.82 |
April | 22.06 | 9.95 |
May | 23.27 | 15.31 |
June | 23.81 | 21.11 |
July | 23.91 | 24.13 |
August | 23.87 | 21.78 |
September | 23.65 | 18.14 |
October | 22.18 | 10.98 |
November | 21.59 | 4.73 |
December | 21.11 | -3.7 |
Annual Sum or Average | 22.42 | 9.99 |
Minimum of Months | 21.11 | -4.6 |
Maximum of Months | 23.91 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.50 | -4.6 |
February | 11.52 | -2.5 |
March | 14.17 | 3.82 |
April | 17.84 | 9.95 |
May | 21.37 | 15.31 |
June | 23.81 | 21.11 |
July | 25.37 | 24.13 |
August | 24.32 | 21.78 |
September | 22.78 | 18.14 |
October | 18.31 | 10.98 |
November | 14.67 | 4.73 |
December | 11.50 | -3.7 |
Annual Sum or Average | 18.05 | 9.99 |
Minimum of Months | 10.50 | -4.6 |
Maximum of Months | 25.37 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.84 | -4.6 |
February | 18.90 | -2.5 |
March | 19.05 | 3.82 |
April | 20.23 | 9.95 |
May | 21.96 | 15.31 |
June | 23.09 | 21.11 |
July | 23.30 | 24.13 |
August | 23.24 | 21.78 |
September | 22.67 | 18.14 |
October | 20.12 | 10.98 |
November | 19.49 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.82 | 9.99 |
Minimum of Months | 18.84 | -4.6 |
Maximum of Months | 23.30 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -4.6 |
February | 18.92 | -2.5 |
March | 19.19 | 3.82 |
April | 20.48 | 9.95 |
May | 22.25 | 15.31 |
June | 23.20 | 21.11 |
July | 23.32 | 24.13 |
August | 23.29 | 21.78 |
September | 22.85 | 18.14 |
October | 20.57 | 10.98 |
November | 19.67 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.97 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.32 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -4.6 |
February | 18.94 | -2.5 |
March | 19.27 | 3.82 |
April | 20.60 | 9.95 |
May | 22.35 | 15.31 |
June | 23.20 | 21.11 |
July | 23.32 | 24.13 |
August | 23.29 | 21.78 |
September | 22.87 | 18.14 |
October | 20.75 | 10.98 |
November | 19.74 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 21.02 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.32 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.61 | -4.6 |
February | 20.70 | -2.5 |
March | 21.06 | 3.82 |
April | 21.36 | 9.95 |
May | 21.72 | 15.31 |
June | 21.75 | 21.11 |
July | 21.76 | 24.13 |
August | 21.75 | 21.78 |
September | 21.75 | 18.14 |
October | 21.55 | 10.98 |
November | 21.10 | 4.73 |
December | 20.61 | -3.7 |
Annual Sum or Average | 21.31 | 9.99 |
Minimum of Months | 20.61 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -4.6 |
February | 18.91 | -2.5 |
March | 19.14 | 3.82 |
April | 20.39 | 9.95 |
May | 22.16 | 15.31 |
June | 23.15 | 21.11 |
July | 23.31 | 24.13 |
August | 23.28 | 21.78 |
September | 22.82 | 18.14 |
October | 20.51 | 10.98 |
November | 19.63 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.93 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.31 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -4.6 |
February | 20.60 | -2.5 |
March | 20.96 | 3.82 |
April | 21.31 | 9.95 |
May | 21.73 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.52 | 10.98 |
November | 20.99 | 4.73 |
December | 20.53 | -3.7 |
Annual Sum or Average | 21.27 | 9.99 |
Minimum of Months | 20.53 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | -4.6 |
February | 20.91 | -2.5 |
March | 21.36 | 3.82 |
April | 21.56 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.71 | 10.98 |
November | 21.28 | 4.73 |
December | 20.80 | -3.7 |
Annual Sum or Average | 21.43 | 9.99 |
Minimum of Months | 20.77 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.27 | -4.6 |
February | 20.67 | -2.5 |
March | 21.84 | 3.82 |
April | 23.47 | 9.95 |
May | 25.16 | 15.31 |
June | 25.96 | 21.11 |
July | 26.44 | 24.13 |
August | 26.11 | 21.78 |
September | 25.59 | 18.14 |
October | 23.74 | 10.98 |
November | 22.03 | 4.73 |
December | 20.60 | -3.7 |
Annual Sum or Average | 23.50 | 9.99 |
Minimum of Months | 20.27 | -4.6 |
Maximum of Months | 26.44 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | -4.6 |
February | 19.69 | -2.5 |
March | 20.98 | 3.82 |
April | 22.11 | 9.95 |
May | 23.22 | 15.31 |
June | 23.33 | 21.11 |
July | 23.33 | 24.13 |
August | 23.33 | 21.78 |
September | 23.31 | 18.14 |
October | 22.66 | 10.98 |
November | 21.06 | 4.73 |
December | 19.38 | -3.7 |
Annual Sum or Average | 21.83 | 9.99 |
Minimum of Months | 19.38 | -4.6 |
Maximum of Months | 23.33 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | -4.6 |
February | 20.79 | -2.5 |
March | 21.21 | 3.82 |
April | 21.47 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.65 | 10.98 |
November | 21.17 | 4.73 |
December | 20.68 | -3.7 |
Annual Sum or Average | 21.37 | 9.99 |
Minimum of Months | 20.67 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | -4.6 |
February | 18.97 | -2.5 |
March | 19.44 | 3.82 |
April | 20.82 | 9.95 |
May | 22.61 | 15.31 |
June | 23.23 | 21.11 |
July | 23.32 | 24.13 |
August | 23.31 | 21.78 |
September | 23.04 | 18.14 |
October | 21.31 | 10.98 |
November | 19.94 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 21.16 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.32 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.94 | -4.6 |
February | 15.48 | -2.5 |
March | 17.56 | 3.82 |
April | 20.36 | 9.95 |
May | 23.22 | 15.31 |
June | 24.99 | 21.11 |
July | 26.02 | 24.13 |
August | 25.29 | 21.78 |
September | 24.14 | 18.14 |
October | 20.81 | 10.98 |
November | 17.96 | 4.73 |
December | 15.45 | -3.7 |
Annual Sum or Average | 20.55 | 9.99 |
Minimum of Months | 14.94 | -4.6 |
Maximum of Months | 26.02 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.34 | -4.6 |
February | 10.98 | -2.5 |
March | 14.17 | 3.82 |
April | 18.44 | 9.95 |
May | 22.53 | 15.31 |
June | 25.24 | 21.11 |
July | 27.09 | 24.13 |
August | 25.80 | 21.78 |
September | 23.98 | 18.14 |
October | 18.95 | 10.98 |
November | 14.77 | 4.73 |
December | 11.06 | -3.7 |
Annual Sum or Average | 18.65 | 9.99 |
Minimum of Months | 10.34 | -4.6 |
Maximum of Months | 27.09 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.93 | -4.6 |
February | 11.76 | -2.5 |
March | 14.66 | 3.82 |
April | 18.60 | 9.95 |
May | 22.35 | 15.31 |
June | 24.83 | 21.11 |
July | 26.53 | 24.13 |
August | 25.39 | 21.78 |
September | 23.72 | 18.14 |
October | 18.97 | 10.98 |
November | 15.08 | 4.73 |
December | 11.69 | -3.7 |
Annual Sum or Average | 18.75 | 9.99 |
Minimum of Months | 10.93 | -4.6 |
Maximum of Months | 26.53 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -4.6 |
February | 21.12 | -2.5 |
March | 21.24 | 3.82 |
April | 21.98 | 9.95 |
May | 22.81 | 15.31 |
June | 23.63 | 21.11 |
July | 24.01 | 24.13 |
August | 23.75 | 21.78 |
September | 23.23 | 18.14 |
October | 21.85 | 10.98 |
November | 21.41 | 4.73 |
December | 21.11 | -3.7 |
Annual Sum or Average | 22.28 | 9.99 |
Minimum of Months | 21.11 | -4.6 |
Maximum of Months | 24.01 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.42 | -4.6 |
February | 10.55 | -2.5 |
March | 13.44 | 3.82 |
April | 17.40 | 9.95 |
May | 21.16 | 15.31 |
June | 23.89 | 21.11 |
July | 25.60 | 24.13 |
August | 24.39 | 21.78 |
September | 22.58 | 18.14 |
October | 17.70 | 10.98 |
November | 13.86 | 4.73 |
December | 10.40 | -3.7 |
Annual Sum or Average | 17.57 | 9.99 |
Minimum of Months | 9.42 | -4.6 |
Maximum of Months | 25.60 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -4.6 |
February | 20.51 | -2.5 |
March | 20.65 | 3.82 |
April | 21.06 | 9.95 |
May | 21.66 | 15.31 |
June | 21.75 | 21.11 |
July | 21.77 | 24.13 |
August | 21.76 | 21.78 |
September | 21.72 | 18.14 |
October | 21.20 | 10.98 |
November | 20.80 | 4.73 |
December | 20.47 | -3.7 |
Annual Sum or Average | 21.15 | 9.99 |
Minimum of Months | 20.46 | -4.6 |
Maximum of Months | 21.77 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -4.6 |
February | 18.91 | -2.5 |
March | 19.16 | 3.82 |
April | 20.33 | 9.95 |
May | 21.73 | 15.31 |
June | 22.95 | 21.11 |
July | 23.25 | 24.13 |
August | 23.12 | 21.78 |
September | 22.41 | 18.14 |
October | 20.16 | 10.98 |
November | 19.46 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.78 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.25 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -4.6 |
February | 18.92 | -2.5 |
March | 19.21 | 3.82 |
April | 20.39 | 9.95 |
May | 21.79 | 15.31 |
June | 22.95 | 21.11 |
July | 23.25 | 24.13 |
August | 23.11 | 21.78 |
September | 22.42 | 18.14 |
October | 20.25 | 10.98 |
November | 19.50 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.81 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.25 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -4.6 |
February | 20.66 | -2.5 |
March | 21.04 | 3.82 |
April | 21.34 | 9.95 |
May | 21.74 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.56 | 10.98 |
November | 21.04 | 4.73 |
December | 20.53 | -3.7 |
Annual Sum or Average | 21.29 | 9.99 |
Minimum of Months | 20.53 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -4.6 |
February | 18.91 | -2.5 |
March | 19.13 | 3.82 |
April | 20.29 | 9.95 |
May | 21.74 | 15.31 |
June | 22.93 | 21.11 |
July | 23.25 | 24.13 |
August | 23.12 | 21.78 |
September | 22.45 | 18.14 |
October | 20.18 | 10.98 |
November | 19.48 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.78 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.25 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -4.6 |
February | 18.94 | -2.5 |
March | 19.30 | 3.82 |
April | 20.51 | 9.95 |
May | 22.12 | 15.31 |
June | 23.03 | 21.11 |
July | 23.28 | 24.13 |
August | 23.19 | 21.78 |
September | 22.70 | 18.14 |
October | 20.66 | 10.98 |
November | 19.69 | 4.73 |
December | 18.89 | -3.7 |
Annual Sum or Average | 20.95 | 9.99 |
Minimum of Months | 18.89 | -4.6 |
Maximum of Months | 23.28 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -4.6 |
February | 20.75 | -2.5 |
March | 21.26 | 3.82 |
April | 21.48 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.67 | 10.98 |
November | 21.14 | 4.73 |
December | 20.59 | -3.7 |
Annual Sum or Average | 21.36 | 9.99 |
Minimum of Months | 20.59 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.00 | -4.6 |
February | 18.48 | -2.5 |
March | 19.82 | 3.82 |
April | 21.61 | 9.95 |
May | 23.37 | 15.31 |
June | 24.49 | 21.11 |
July | 25.11 | 24.13 |
August | 24.58 | 21.78 |
September | 23.79 | 18.14 |
October | 21.67 | 10.98 |
November | 19.88 | 4.73 |
December | 18.29 | -3.7 |
Annual Sum or Average | 21.61 | 9.99 |
Minimum of Months | 18.00 | -4.6 |
Maximum of Months | 25.11 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | -4.6 |
February | 20.71 | -2.5 |
March | 21.19 | 3.82 |
April | 21.45 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.65 | 10.98 |
November | 21.10 | 4.73 |
December | 20.56 | -3.7 |
Annual Sum or Average | 21.34 | 9.99 |
Minimum of Months | 20.56 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -4.6 |
February | 20.73 | -2.5 |
March | 21.23 | 3.82 |
April | 21.46 | 9.95 |
May | 21.75 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.66 | 10.98 |
November | 21.12 | 4.73 |
December | 20.57 | -3.7 |
Annual Sum or Average | 21.35 | 9.99 |
Minimum of Months | 20.57 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -4.6 |
February | 20.58 | -2.5 |
March | 20.95 | 3.82 |
April | 21.31 | 9.95 |
May | 21.74 | 15.31 |
June | 21.76 | 21.11 |
July | 21.76 | 24.13 |
August | 21.76 | 21.78 |
September | 21.75 | 18.14 |
October | 21.55 | 10.98 |
November | 20.95 | 4.73 |
December | 20.49 | -3.7 |
Annual Sum or Average | 21.26 | 9.99 |
Minimum of Months | 20.49 | -4.6 |
Maximum of Months | 21.76 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.31 | -4.6 |
February | 14.93 | -2.5 |
March | 17.19 | 3.82 |
April | 20.16 | 9.95 |
May | 23.11 | 15.31 |
June | 25.01 | 21.11 |
July | 26.14 | 24.13 |
August | 25.27 | 21.78 |
September | 23.93 | 18.14 |
October | 20.43 | 10.98 |
November | 17.45 | 4.73 |
December | 14.75 | -3.7 |
Annual Sum or Average | 20.25 | 9.99 |
Minimum of Months | 14.31 | -4.6 |
Maximum of Months | 26.14 | 24.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:18
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.69 | -4.6 |
February | 10.31 | -2.5 |
March | 13.54 | 3.82 |
April | 18.07 | 9.95 |
May | 22.36 | 15.31 |
June | 25.27 | 21.11 |
July | 27.24 | 24.13 |
August | 25.81 | 21.78 |
September | 23.76 | 18.14 |
October | 18.40 | 10.98 |
November | 14.10 | 4.73 |
December | 10.19 | -3.7 |
Annual Sum or Average | 18.27 | 9.99 |
Minimum of Months | 9.69 | -4.6 |
Maximum of Months | 27.24 | 24.13 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:18
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.222022E+12 | 204887.945 | 27-JAN-07:15 | 17938.631 | 34285.948 | 9314.310 | 139152.943 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.183753E+12 | 182638.169 | 06-FEB-07:15 | 20847.837 | 39740.848 | 9269.826 | 112691.084 | 80.460 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.165701E+12 | 128210.671 | 05-MAR-07:15 | 20847.837 | 39740.848 | 9243.209 | 58188.805 | 181.859 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.155389E+12 | 112208.997 | 05-APR-06:15 | 20847.837 | 39740.848 | 9239.764 | 41754.773 | 617.662 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.161007E+12 | 103143.286 | 28-MAY-07:00 | 25182.171 | 43578.554 | 9772.336 | 0.000 | 24602.113 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.174303E+12 | 108784.117 | 16-JUN-07:00 | 25182.171 | 43578.554 | 9772.336 | 0.000 | 30242.944 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.197509E+12 | 112705.189 | 16-JUL-19:30 | 27551.975 | 28549.175 | 9329.161 | 0.000 | 43078.764 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.184928E+12 | 111622.132 | 04-AUG-07:00 | 25182.171 | 43578.554 | 9772.336 | 0.000 | 33080.958 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.164244E+12 | 102643.922 | 16-SEP-07:00 | 25182.171 | 43578.554 | 9772.336 | 0.000 | 24102.748 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.152198E+12 | 103956.562 | 24-OCT-06:15 | 20847.837 | 39740.848 | 9239.764 | 28192.636 | 1739.364 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.170803E+12 | 169028.936 | 26-NOV-07:15 | 20847.837 | 39740.848 | 9256.810 | 99060.515 | 114.813 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.211200E+12 | 179176.095 | 19-DEC-07:15 | 20847.837 | 39740.848 | 9266.224 | 105028.455 | 96.618 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.214306E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.152198E+12 | 102643.922 | 17938.631 | 28549.175 | 9239.764 | 0.000 | 0.000 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.222022E+12 | 204887.945 | 27551.975 | 43578.554 | 9772.336 | 139152.943 | 43078.764 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:18
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.123526E+12 | 129487.384 | 27-JAN-09:15 | 20762.394 | 40096.028 | 0.000 | 68628.962 | 68628.962 | 68628.962 | 20762.394 |
February | 0.107923E+12 | 110106.838 | 05-FEB-12:00 | 17725.238 | 40096.028 | 0.000 | 52285.572 | 52285.572 | 52285.572 | 17725.238 |
March | 0.106161E+12 | 111254.661 | 17-MAR-08:15 | 691.551 | 40096.028 | 0.000 | 70467.082 | 70467.082 | 70467.082 | 691.551 |
April | 0.947708E+11 | 107240.815 | 14-APR-08:15 | 0.000 | 40096.028 | 0.000 | 67144.787 | 67144.787 | 67144.787 | 0.000 |
May | 0.904714E+11 | 99281.153 | 19-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 59185.125 | 59185.125 | 59185.125 | 0.000 |
June | 0.833777E+11 | 88090.561 | 09-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 47994.533 | 47994.533 | 47994.533 | 0.000 |
July | 0.834395E+11 | 88191.615 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 48095.586 | 48095.586 | 48095.586 | 0.000 |
August | 0.825604E+11 | 84444.249 | 04-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 44348.221 | 44348.221 | 44348.221 | 0.000 |
September | 0.809187E+11 | 84817.241 | 23-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 44721.213 | 44721.213 | 44721.213 | 0.000 |
October | 0.883600E+11 | 89202.583 | 27-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 49106.555 | 49106.555 | 49106.555 | 0.000 |
November | 0.979475E+11 | 102407.081 | 25-NOV-12:00 | 14054.205 | 40096.028 | 0.000 | 48256.848 | 48256.848 | 48256.848 | 14054.205 |
December | 0.117897E+12 | 117002.759 | 30-DEC-09:15 | 11413.520 | 40096.028 | 0.000 | 65493.211 | 65493.211 | 65493.211 | 11413.520 |
Annual Sum or Average | 0.115735E+13 | 0.000 | ||||||||
Minimum of Months | 0.809187E+11 | 84444.249 | 0.000 | 40096.028 | 0.000 | 44348.221 | 44348.221 | 44348.221 | 0.000 | |
Maximum of Months | 0.123526E+12 | 129487.384 | 20762.394 | 40096.028 | 0.000 | 70467.082 | 70467.082 | 70467.082 | 20762.394 |