Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: San Francisco Intl Ap CA USA TMY3 WMO#=724940
Simulation Timestamp: 2015-09-14 08:44:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2835.08 | 706.37 | 761.08 |
Net Site Energy | 2835.08 | 706.37 | 761.08 |
Total Source Energy | 6852.51 | 1707.33 | 1839.55 |
Net Source Energy | 6852.51 | 1707.33 | 1839.55 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 18.79 | 7.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 258.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 291.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 591.45 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1814.34 | 1020.74 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 18.79 | 7.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 258.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 291.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 591.45 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 152.62 | 160.87 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 487.06 | 274.02 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.65 | 149.31 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 452.05 | 254.32 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1814.34 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1814.34 | 100.00 |
Total On-Site and Utility Electric Sources | 1814.34 | 100.00 |
Total Electricity End Uses | 1814.34 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2.75 |
Time Setpoint Not Met During Occupied Cooling | 3518.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3384.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Weather File | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Latitude [deg] | 37.62 |
Longitude [deg] | -122.4 |
Elevation [m] | 2.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 2.20 | 150.00 |
SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 8.50 | 17.20 | Wetbulb [C] | 5.90 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 8.38 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 175.82 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5802.88 | 4634.50 | 1168.38 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16545.64 | 12875.44 | 3670.20 | 0.78 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8093.87 | 6061.78 | 2032.09 | 0.75 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12185.52 | 9732.03 | 2453.49 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5530.9 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15813.1 | 3.19 | 10.88 | 11.52 | 10.72 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7765.6 | 3.24 | 11.06 | 11.71 | 10.98 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11614.3 | 3.15 | 10.76 | 11.39 | 10.54 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 18609.80 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 514.67 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 514.67 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 764.28 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2167.55 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 764.28 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3057.13 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2422.88 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3057.13 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 764.28 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 2058.52 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3056.91 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2167.55 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 764.28 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3057.13 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2422.88 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3057.13 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 764.28 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3056.91 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 514.63 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3056.91 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2322.90 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 934.70 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3057.13 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2422.88 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3057.13 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 764.28 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3056.91 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 764.23 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3056.91 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 828.26 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3146.98 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 13190.49 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 7063.41 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5275.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.35 | 406.93 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.94 | 1076.09 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.42 | 490.83 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.74 | 839.27 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 9540.90 | 11449.08 | 0.787 | 0.944 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 26.90 | 0.00771 |
RESTROOMFLR1 | 628.04 | 753.65 | 0.052 | 0.062 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 25.94 | 0.00771 |
MEETINGROOMFLR1 | 4271.57 | 5125.88 | 0.352 | 0.423 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM101 | 472.27 | 566.73 | 0.041 | 0.049 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 26.47 | 0.00771 |
GUESTROOM102 | 347.80 | 417.37 | 0.030 | 0.036 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM103 | 1422.15 | 1706.57 | 0.163 | 0.195 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM104 | 1292.66 | 1551.20 | 0.148 | 0.178 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 26.03 | 0.00771 |
GUESTROOM105 | 1741.65 | 2089.98 | 0.200 | 0.239 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
EMPLOYEELOUNGEFLR1 | 5537.53 | 6645.04 | 0.457 | 0.548 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 26.03 | 0.00771 |
EXERCISECENTERFLR1 | 1275.05 | 1530.07 | 0.105 | 0.126 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.62 | 0.00771 |
FRONTOFFICEFLR1 | 3546.03 | 4255.23 | 0.292 | 0.351 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM201 | 672.20 | 806.64 | 0.059 | 0.070 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 26.90 | 0.00771 |
GUESTROOM202_205 | 5617.14 | 6740.57 | 0.643 | 0.772 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM206_208 | 4593.89 | 5512.67 | 0.526 | 0.631 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM209_212 | 5256.55 | 6307.86 | 0.602 | 0.723 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM213 | 1492.65 | 1791.18 | 0.171 | 0.205 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM214 | 1489.81 | 1787.77 | 0.171 | 0.205 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM215_218 | 8271.47 | 9925.77 | 0.722 | 0.866 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM219 | 5538.20 | 6645.84 | 0.634 | 0.761 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM220_223 | 5112.56 | 6135.07 | 0.586 | 0.703 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM224 | 1495.87 | 1795.04 | 0.171 | 0.206 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM301 | 531.36 | 637.63 | 0.046 | 0.056 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 26.90 | 0.00771 |
GUESTROOM302_305 | 1632.24 | 1958.69 | 0.142 | 0.171 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM306_308 | 1483.29 | 1779.95 | 0.129 | 0.155 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM309_312 | 5239.46 | 6287.35 | 0.600 | 0.720 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM313 | 542.25 | 650.70 | 0.047 | 0.057 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 26.69 | 0.00771 |
GUESTROOM314 | 1403.99 | 1684.78 | 0.161 | 0.193 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 26.03 | 0.00771 |
GUESTROOM315_318 | 5744.73 | 6893.67 | 0.658 | 0.790 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM319 | 771.73 | 926.07 | 0.067 | 0.081 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM320_323 | 4914.70 | 5897.64 | 0.563 | 0.676 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 25.71 | 0.00771 |
GUESTROOM324 | 430.64 | 516.77 | 0.038 | 0.045 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 26.03 | 0.00771 |
GUESTROOM401 | 1827.09 | 2192.51 | 0.209 | 0.251 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 27.45 | 0.00771 |
GUESTROOM402_405 | 2394.45 | 2873.35 | 0.209 | 0.251 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 27.28 | 0.00771 |
GUESTROOM406_408 | 2168.24 | 2601.88 | 0.189 | 0.227 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 27.28 | 0.00771 |
GUESTROOM409_412 | 6257.72 | 7509.27 | 0.717 | 0.860 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 27.45 | 0.00771 |
GUESTROOM413 | 817.81 | 981.38 | 0.071 | 0.086 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 27.28 | 0.00771 |
GUESTROOM414 | 649.79 | 779.75 | 0.057 | 0.068 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 28.30 | 0.00771 |
GUESTROOM415_418 | 5991.22 | 7189.46 | 0.686 | 0.824 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 26.56 | 0.00771 |
GUESTROOM419 | 1637.44 | 1964.93 | 0.188 | 0.225 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 11:30:00 | 26.77 | 0.00771 |
GUESTROOM420_423 | 5856.69 | 7028.03 | 0.671 | 0.805 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 26.56 | 0.00771 |
GUESTROOM424 | 1636.32 | 1963.59 | 0.187 | 0.225 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 11:30:00 | 26.77 | 0.00771 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
CORRIDORFLR1 | 13953.12 | 16743.74 | 1.149 | 1.379 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.26 | 0.00771 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
CORRIDORFLR2 | 2716.78 | 3260.13 | 0.224 | 0.269 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 27.79 | 0.00771 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
CORRIDORFLR3 | 1450.73 | 1740.88 | 0.119 | 0.143 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 27.45 | 0.00771 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 | |
CORRIDORFLR4 | 2306.00 | 2767.20 | 0.190 | 0.228 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 28.30 | 0.00771 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 28.30 | 0.00771 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1022.28 | 1226.73 | 0.029 | 0.236 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | 3.80 | 0.00496 |
MEETINGROOMFLR1 | 325.04 | 390.04 | 0.009 | 0.126 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 3.80 | 0.00496 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
GUESTROOM102 | 0.00 | 0.00 | 0.000 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
GUESTROOM103 | 328.69 | 394.43 | 0.009 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 3.80 | 0.00496 |
GUESTROOM104 | 247.33 | 296.79 | 0.007 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | 3.80 | 0.00496 |
GUESTROOM105 | 183.75 | 220.50 | 0.005 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | 3.80 | 0.00496 |
EMPLOYEELOUNGEFLR1 | 152.83 | 183.39 | 0.004 | 0.051 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 3.80 | 0.00496 |
EXERCISECENTERFLR1 | 69.25 | 83.10 | 0.002 | 0.043 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 3.80 | 0.00496 |
FRONTOFFICEFLR1 | 580.37 | 696.44 | 0.016 | 0.056 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | 3.80 | 0.00496 |
GUESTROOM201 | 66.31 | 79.57 | 0.002 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:15:00 | 3.80 | 0.00496 |
GUESTROOM202_205 | 788.59 | 946.30 | 0.022 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | 3.80 | 0.00496 |
GUESTROOM206_208 | 546.24 | 655.49 | 0.015 | 0.043 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
GUESTROOM209_212 | 539.83 | 647.80 | 0.015 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
GUESTROOM213 | 348.52 | 418.22 | 0.010 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:30:00 | 3.80 | 0.00496 |
GUESTROOM214 | 248.32 | 297.98 | 0.007 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | 3.80 | 0.00496 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.000 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
GUESTROOM219 | 109.81 | 131.78 | 0.003 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 3.80 | 0.00496 |
GUESTROOM220_223 | 446.55 | 535.86 | 0.013 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 3.80 | 0.00496 |
GUESTROOM224 | 241.14 | 289.37 | 0.007 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | 3.80 | 0.00496 |
GUESTROOM301 | 117.15 | 140.58 | 0.003 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:15:00 | 3.80 | 0.00496 |
GUESTROOM302_305 | 176.06 | 211.27 | 0.005 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | 3.80 | 0.00496 |
GUESTROOM306_308 | 115.51 | 138.61 | 0.003 | 0.043 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 3.80 | 0.00496 |
GUESTROOM309_312 | 721.73 | 866.07 | 0.020 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:45:00 | 3.80 | 0.00496 |
GUESTROOM313 | 120.41 | 144.49 | 0.003 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 3.80 | 0.00496 |
GUESTROOM314 | 320.24 | 384.29 | 0.009 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:00:00 | 3.80 | 0.00496 |
GUESTROOM315_318 | 710.84 | 853.01 | 0.020 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | 3.80 | 0.00496 |
GUESTROOM319 | 0.00 | 0.00 | 0.000 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
GUESTROOM320_323 | 614.75 | 737.70 | 0.017 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:45:00 | 3.80 | 0.00496 |
GUESTROOM324 | 7.28 | 8.74 | 0.000 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:30:00 | 3.80 | 0.00496 |
GUESTROOM401 | 540.27 | 648.33 | 0.015 | 0.018 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | 3.80 | 0.00496 |
GUESTROOM402_405 | 675.89 | 811.07 | 0.018 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | 3.80 | 0.00496 |
GUESTROOM406_408 | 552.04 | 662.45 | 0.014 | 0.043 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | 3.80 | 0.00496 |
GUESTROOM409_412 | 1232.49 | 1478.99 | 0.035 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 | 3.80 | 0.00496 |
GUESTROOM413 | 287.91 | 345.50 | 0.008 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3.80 | 0.00496 |
GUESTROOM414 | 172.23 | 206.68 | 0.005 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 21:00:00 | 3.80 | 0.00496 |
GUESTROOM415_418 | 1162.78 | 1395.34 | 0.033 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | 3.80 | 0.00496 |
GUESTROOM419 | 352.00 | 422.40 | 0.010 | 0.013 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 3.80 | 0.00496 |
GUESTROOM420_423 | 1079.78 | 1295.74 | 0.030 | 0.054 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 3.80 | 0.00496 |
GUESTROOM424 | 451.59 | 541.91 | 0.013 | 0.015 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 3.80 | 0.00496 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
CORRIDORFLR1 | 14693.45 | 17632.14 | 0.414 | 0.497 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3.80 | 0.00496 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
CORRIDORFLR2 | 275.22 | 330.26 | 0.008 | 0.038 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 3.80 | 0.00496 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
CORRIDORFLR3 | 592.38 | 710.86 | 0.017 | 0.038 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 3.80 | 0.00496 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 | |
CORRIDORFLR4 | 1258.96 | 1510.75 | 0.035 | 0.043 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 3.80 | 0.00496 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 3.80 | 0.00496 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.35 | 0.35 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.94 | 0.94 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.42 | 0.42 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.74 | 0.74 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.94 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 712.50 | 6790.25 | 12.50 |
RESTROOMFLR1 | 0.25 | 8095.25 | 0.00 |
MEETINGROOMFLR1 | 1432.25 | 1654.75 | 3.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.75 | 8760.00 | 0.75 |
GUESTROOM104 | 0.00 | 8760.00 | 0.00 |
GUESTROOM105 | 0.00 | 8708.25 | 0.00 |
EMPLOYEELOUNGEFLR1 | 3200.00 | 2135.00 | 292.50 |
EXERCISECENTERFLR1 | 1169.50 | 1241.75 | 0.00 |
FRONTOFFICEFLR1 | 439.75 | 5535.25 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 8709.50 | 0.00 |
GUESTROOM206_208 | 0.00 | 8665.00 | 0.00 |
GUESTROOM209_212 | 0.00 | 8732.25 | 0.00 |
GUESTROOM213 | 0.00 | 8760.00 | 0.00 |
GUESTROOM214 | 0.00 | 8746.25 | 0.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 4818.00 | 3205.25 | 5.50 |
GUESTROOM220_223 | 0.00 | 8566.25 | 0.00 |
GUESTROOM224 | 0.00 | 8736.00 | 0.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 8732.25 | 0.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 8753.75 | 0.00 |
GUESTROOM315_318 | 0.00 | 8347.75 | 0.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 8705.50 | 0.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 299.25 | 8311.25 | 295.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 130.25 | 7723.50 | 0.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 258.75 | 7345.75 | 0.00 |
GUESTROOM419 | 21.75 | 7679.25 | 0.00 |
GUESTROOM420_423 | 211.00 | 7390.50 | 0.00 |
GUESTROOM424 | 15.25 | 7946.25 | 3.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 5630.25 | 8760.00 | 3384.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 314.25 | 0.00 | 314.25 |
MEETINGROOMFLR1 | 0.00 | 1.25 | 0.00 | 1.25 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 53.25 | 0.00 | 53.25 |
GUESTROOM104 | 0.00 | 54.50 | 0.00 | 54.50 |
GUESTROOM105 | 0.00 | 79.75 | 0.00 | 79.75 |
EMPLOYEELOUNGEFLR1 | 3.75 | 853.00 | 2.75 | 430.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 18.75 | 0.00 | 18.75 |
GUESTROOM206_208 | 0.00 | 44.00 | 0.00 | 44.00 |
GUESTROOM209_212 | 0.00 | 16.50 | 0.00 | 16.50 |
GUESTROOM213 | 0.00 | 14.25 | 0.00 | 14.25 |
GUESTROOM214 | 0.00 | 12.75 | 0.00 | 12.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2886.75 | 0.00 | 2886.75 |
GUESTROOM220_223 | 0.00 | 7.75 | 0.00 | 7.75 |
GUESTROOM224 | 0.00 | 12.50 | 0.00 | 12.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 16.50 | 0.00 | 16.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 9.75 | 0.00 | 9.75 |
GUESTROOM315_318 | 0.00 | 13.75 | 0.00 | 13.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 6.25 | 0.00 | 6.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 32.25 | 0.00 | 32.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 40.00 | 0.00 | 40.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 27.00 | 0.00 | 27.00 |
GUESTROOM419 | 0.00 | 35.00 | 0.00 | 35.00 |
GUESTROOM420_423 | 0.00 | 25.50 | 0.00 | 25.50 |
GUESTROOM424 | 0.00 | 28.50 | 0.00 | 28.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 2611.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 5.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 3.75 | 4738.50 | 2.75 | 3518.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:42
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.350552 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.943850 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.736127 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR1 PTAC HEATING COIL | 18609.80 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 514.67 |
102 PTAC HEATING COIL | 514.67 |
103 PTAC HEATING COIL | 764.28 |
104 PTAC HEATING COIL | 764.23 |
105 PTAC HEATING COIL | 764.23 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR2 PTAC HEATING COIL | 2167.55 |
201 PTAC HEATING COIL | 764.28 |
202_205 PTAC HEATING COIL | 3057.13 |
206_208 PTAC HEATING COIL | 2422.88 |
209_212 PTAC HEATING COIL | 3057.13 |
213 PTAC HEATING COIL | 764.28 |
214 PTAC HEATING COIL | 764.23 |
215_218 PTAC HEATING COIL | 2058.52 |
219 PTAC HEATING COIL | 764.23 |
220_223 PTAC HEATING COIL | 3056.91 |
224 PTAC HEATING COIL | 764.23 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR3 PTAC HEATING COIL | 2167.55 |
301 PTAC HEATING COIL | 764.28 |
302_305 PTAC HEATING COIL | 3057.13 |
306_308 PTAC HEATING COIL | 2422.88 |
309_312 PTAC HEATING COIL | 3057.13 |
313 PTAC HEATING COIL | 764.28 |
314 PTAC HEATING COIL | 764.23 |
315_318 PTAC HEATING COIL | 3056.91 |
319 PTAC HEATING COIL | 514.63 |
320_323 PTAC HEATING COIL | 3056.91 |
324 PTAC HEATING COIL | 764.23 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR4 PTAC HEATING COIL | 2322.90 |
401 PTAC HEATING COIL | 934.70 |
402_405 PTAC HEATING COIL | 3057.13 |
406_408 PTAC HEATING COIL | 2422.88 |
409_412 PTAC HEATING COIL | 3057.13 |
413 PTAC HEATING COIL | 764.28 |
414 PTAC HEATING COIL | 764.23 |
415_418 PTAC HEATING COIL | 3056.91 |
419 PTAC HEATING COIL | 764.23 |
420_423 PTAC HEATING COIL | 3056.91 |
424 PTAC HEATING COIL | 828.26 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.28 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.798655 | 0.350552 | 5802.88 |
SAC_FRONTLOUNGE COOLING COIL | 0.778177 | 0.943850 | 16545.64 |
SAC_MEETINGROOM COOLING COIL | 0.748935 | 0.422827 | 8093.87 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.798655 | 0.736127 | 12185.52 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.943850 |
RESTROOMFLR1 DIRECT AIR | 0.062078 |
MEETINGROOMFLR1 DIRECT AIR | 0.422827 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.547960 |
EXERCISECENTERFLR1 DIRECT AIR | 0.126090 |
FRONTOFFICEFLR1 DIRECT AIR | 0.350552 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.350552 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.943850 |
SAC_MEETINGROOM MAIN BRANCH | 0.422827 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.736127 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.350552 |
SAC_FRONTLOUNGE | 0.943850 |
SAC_MEETINGROOM | 0.422827 |
SAC_EXC_EMPLGE_RESTRM | 0.736127 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.350552 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.943850 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.422827 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.736127 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.350552 | 0.350552 | 0.350552 | 0.350552 | 3146.98 | 5802.88 | 1.00 |
SAC_FRONTLOUNGE | 0.943850 | 0.943850 | 0.943850 | 0.943850 | 13190.49 | 16545.64 | 1.00 |
SAC_MEETINGROOM | 0.422827 | 0.422827 | 0.422827 | 0.422827 | 7063.41 | 8093.87 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.736127 | 0.736127 | 0.736127 | 0.736127 | 5275.82 | 12185.52 | 0.171288 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3146.98 |
SAC_FRONTLOUNGE HEATING COIL | 13190.49 |
SAC_MEETINGROOM HEATING COIL | 7063.41 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5275.82 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.422827 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.37 | 9.60 |
February | 20.91 | 11.29 |
March | 20.96 | 12.66 |
April | 20.91 | 13.68 |
May | 21.21 | 15.00 |
June | 21.33 | 15.34 |
July | 21.62 | 15.94 |
August | 22.13 | 16.62 |
September | 22.24 | 16.72 |
October | 21.88 | 15.11 |
November | 21.61 | 12.79 |
December | 20.93 | 10.66 |
Annual Sum or Average | 21.34 | 13.79 |
Minimum of Months | 20.37 | 9.60 |
Maximum of Months | 22.24 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.35 | 9.60 |
February | 23.57 | 11.29 |
March | 23.74 | 12.66 |
April | 23.84 | 13.68 |
May | 24.08 | 15.00 |
June | 24.21 | 15.34 |
July | 24.27 | 15.94 |
August | 24.43 | 16.62 |
September | 24.45 | 16.72 |
October | 24.08 | 15.11 |
November | 23.71 | 12.79 |
December | 23.45 | 10.66 |
Annual Sum or Average | 23.93 | 13.79 |
Minimum of Months | 23.35 | 9.60 |
Maximum of Months | 24.45 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | 9.60 |
February | 20.11 | 11.29 |
March | 20.20 | 12.66 |
April | 20.18 | 13.68 |
May | 20.52 | 15.00 |
June | 20.64 | 15.34 |
July | 20.99 | 15.94 |
August | 21.46 | 16.62 |
September | 21.60 | 16.72 |
October | 21.15 | 15.11 |
November | 20.79 | 12.79 |
December | 20.09 | 10.66 |
Annual Sum or Average | 20.61 | 13.79 |
Minimum of Months | 19.52 | 9.60 |
Maximum of Months | 21.60 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 9.60 |
February | 21.82 | 11.29 |
March | 22.14 | 12.66 |
April | 22.38 | 13.68 |
May | 22.63 | 15.00 |
June | 22.66 | 15.34 |
July | 22.87 | 15.94 |
August | 22.88 | 16.62 |
September | 22.90 | 16.72 |
October | 22.60 | 15.11 |
November | 22.07 | 12.79 |
December | 21.61 | 10.66 |
Annual Sum or Average | 22.34 | 13.79 |
Minimum of Months | 21.44 | 9.60 |
Maximum of Months | 22.90 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.62 | 9.60 |
February | 22.80 | 11.29 |
March | 22.94 | 12.66 |
April | 23.06 | 13.68 |
May | 23.17 | 15.00 |
June | 23.20 | 15.34 |
July | 23.35 | 15.94 |
August | 23.38 | 16.62 |
September | 23.39 | 16.72 |
October | 23.21 | 15.11 |
November | 22.98 | 12.79 |
December | 22.73 | 10.66 |
Annual Sum or Average | 23.07 | 13.79 |
Minimum of Months | 22.62 | 9.60 |
Maximum of Months | 23.39 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.68 | 9.60 |
February | 23.08 | 11.29 |
March | 23.30 | 12.66 |
April | 23.45 | 13.68 |
May | 23.55 | 15.00 |
June | 23.57 | 15.34 |
July | 23.67 | 15.94 |
August | 23.68 | 16.62 |
September | 23.68 | 16.72 |
October | 23.56 | 15.11 |
November | 23.33 | 12.79 |
December | 22.93 | 10.66 |
Annual Sum or Average | 23.37 | 13.79 |
Minimum of Months | 22.68 | 9.60 |
Maximum of Months | 23.68 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.14 | 9.60 |
February | 25.45 | 11.29 |
March | 25.64 | 12.66 |
April | 25.81 | 13.68 |
May | 25.97 | 15.00 |
June | 26.05 | 15.34 |
July | 26.20 | 15.94 |
August | 26.22 | 16.62 |
September | 26.20 | 16.72 |
October | 25.96 | 15.11 |
November | 25.65 | 12.79 |
December | 25.32 | 10.66 |
Annual Sum or Average | 25.80 | 13.79 |
Minimum of Months | 25.14 | 9.60 |
Maximum of Months | 26.22 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.03 | 9.60 |
February | 21.54 | 11.29 |
March | 21.88 | 12.66 |
April | 22.17 | 13.68 |
May | 22.46 | 15.00 |
June | 22.50 | 15.34 |
July | 22.74 | 15.94 |
August | 22.78 | 16.62 |
September | 22.79 | 16.72 |
October | 22.43 | 15.11 |
November | 21.89 | 12.79 |
December | 21.32 | 10.66 |
Annual Sum or Average | 22.13 | 13.79 |
Minimum of Months | 21.03 | 9.60 |
Maximum of Months | 22.79 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | 9.60 |
February | 21.18 | 11.29 |
March | 21.53 | 12.66 |
April | 21.82 | 13.68 |
May | 22.14 | 15.00 |
June | 22.20 | 15.34 |
July | 22.46 | 15.94 |
August | 22.51 | 16.62 |
September | 22.52 | 16.72 |
October | 22.11 | 15.11 |
November | 21.53 | 12.79 |
December | 20.95 | 10.66 |
Annual Sum or Average | 21.80 | 13.79 |
Minimum of Months | 20.66 | 9.60 |
Maximum of Months | 22.52 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | 9.60 |
February | 21.42 | 11.29 |
March | 21.50 | 12.66 |
April | 21.56 | 13.68 |
May | 21.65 | 15.00 |
June | 21.65 | 15.34 |
July | 21.69 | 15.94 |
August | 21.70 | 16.62 |
September | 21.72 | 16.72 |
October | 21.64 | 15.11 |
November | 21.54 | 12.79 |
December | 21.36 | 10.66 |
Annual Sum or Average | 21.56 | 13.79 |
Minimum of Months | 21.25 | 9.60 |
Maximum of Months | 21.72 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 9.60 |
February | 21.58 | 11.29 |
March | 21.66 | 12.66 |
April | 21.70 | 13.68 |
May | 21.74 | 15.00 |
June | 21.72 | 15.34 |
July | 21.74 | 15.94 |
August | 21.74 | 16.62 |
September | 21.74 | 16.72 |
October | 21.72 | 15.11 |
November | 21.67 | 12.79 |
December | 21.53 | 10.66 |
Annual Sum or Average | 21.67 | 13.79 |
Minimum of Months | 21.44 | 9.60 |
Maximum of Months | 21.74 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 9.60 |
February | 21.73 | 11.29 |
March | 21.74 | 12.66 |
April | 21.75 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.75 | 15.11 |
November | 21.74 | 12.79 |
December | 21.73 | 10.66 |
Annual Sum or Average | 21.74 | 13.79 |
Minimum of Months | 21.69 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | 9.60 |
February | 22.71 | 11.29 |
March | 22.74 | 12.66 |
April | 22.74 | 13.68 |
May | 22.72 | 15.00 |
June | 22.67 | 15.34 |
July | 22.77 | 15.94 |
August | 22.78 | 16.62 |
September | 22.82 | 16.72 |
October | 22.84 | 15.11 |
November | 22.83 | 12.79 |
December | 22.75 | 10.66 |
Annual Sum or Average | 22.76 | 13.79 |
Minimum of Months | 22.67 | 9.60 |
Maximum of Months | 22.84 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.36 | 9.60 |
February | 51.57 | 11.29 |
March | 51.67 | 12.66 |
April | 51.74 | 13.68 |
May | 51.87 | 15.00 |
June | 51.95 | 15.34 |
July | 52.04 | 15.94 |
August | 52.13 | 16.62 |
September | 52.08 | 16.72 |
October | 51.95 | 15.11 |
November | 51.79 | 12.79 |
December | 51.50 | 10.66 |
Annual Sum or Average | 51.81 | 13.79 |
Minimum of Months | 51.36 | 9.60 |
Maximum of Months | 52.13 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.56 | 9.60 |
February | 69.74 | 11.29 |
March | 69.65 | 12.66 |
April | 69.52 | 13.68 |
May | 69.64 | 15.00 |
June | 69.71 | 15.34 |
July | 69.82 | 15.94 |
August | 70.06 | 16.62 |
September | 70.01 | 16.72 |
October | 70.02 | 15.11 |
November | 70.04 | 12.79 |
December | 69.75 | 10.66 |
Annual Sum or Average | 69.79 | 13.79 |
Minimum of Months | 69.52 | 9.60 |
Maximum of Months | 70.06 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.37 | 9.60 |
February | 23.46 | 11.29 |
March | 23.55 | 12.66 |
April | 23.62 | 13.68 |
May | 23.68 | 15.00 |
June | 23.68 | 15.34 |
July | 23.78 | 15.94 |
August | 23.80 | 16.62 |
September | 23.82 | 16.72 |
October | 23.73 | 15.11 |
November | 23.61 | 12.79 |
December | 23.44 | 10.66 |
Annual Sum or Average | 23.63 | 13.79 |
Minimum of Months | 23.37 | 9.60 |
Maximum of Months | 23.82 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 9.60 |
February | 23.47 | 11.29 |
March | 23.59 | 12.66 |
April | 23.70 | 13.68 |
May | 23.75 | 15.00 |
June | 23.78 | 15.34 |
July | 23.86 | 15.94 |
August | 23.88 | 16.62 |
September | 23.88 | 16.72 |
October | 23.81 | 15.11 |
November | 23.69 | 12.79 |
December | 23.42 | 10.66 |
Annual Sum or Average | 23.68 | 13.79 |
Minimum of Months | 23.28 | 9.60 |
Maximum of Months | 23.88 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.79 | 9.60 |
February | 20.31 | 11.29 |
March | 20.47 | 12.66 |
April | 20.65 | 13.68 |
May | 21.16 | 15.00 |
June | 21.35 | 15.34 |
July | 21.63 | 15.94 |
August | 22.08 | 16.62 |
September | 21.98 | 16.72 |
October | 21.56 | 15.11 |
November | 21.15 | 12.79 |
December | 20.26 | 10.66 |
Annual Sum or Average | 21.03 | 13.79 |
Minimum of Months | 19.79 | 9.60 |
Maximum of Months | 22.08 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 9.60 |
February | 22.13 | 11.29 |
March | 22.30 | 12.66 |
April | 22.48 | 13.68 |
May | 22.79 | 15.00 |
June | 22.91 | 15.34 |
July | 23.11 | 15.94 |
August | 23.32 | 16.62 |
September | 23.25 | 16.72 |
October | 22.96 | 15.11 |
November | 22.62 | 12.79 |
December | 22.03 | 10.66 |
Annual Sum or Average | 22.64 | 13.79 |
Minimum of Months | 21.76 | 9.60 |
Maximum of Months | 23.32 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | 9.60 |
February | 21.16 | 11.29 |
March | 21.20 | 12.66 |
April | 21.13 | 13.68 |
May | 21.50 | 15.00 |
June | 21.61 | 15.34 |
July | 21.96 | 15.94 |
August | 22.57 | 16.62 |
September | 22.67 | 16.72 |
October | 22.30 | 15.11 |
November | 22.04 | 12.79 |
December | 21.21 | 10.66 |
Annual Sum or Average | 21.66 | 13.79 |
Minimum of Months | 20.54 | 9.60 |
Maximum of Months | 22.67 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 9.60 |
February | 23.37 | 11.29 |
March | 23.55 | 12.66 |
April | 23.68 | 13.68 |
May | 23.78 | 15.00 |
June | 23.78 | 15.34 |
July | 23.86 | 15.94 |
August | 23.87 | 16.62 |
September | 23.88 | 16.72 |
October | 23.81 | 15.11 |
November | 23.65 | 12.79 |
December | 23.26 | 10.66 |
Annual Sum or Average | 23.62 | 13.79 |
Minimum of Months | 22.99 | 9.60 |
Maximum of Months | 23.88 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.14 | 9.60 |
February | 19.86 | 11.29 |
March | 20.01 | 12.66 |
April | 20.03 | 13.68 |
May | 20.46 | 15.00 |
June | 20.58 | 15.34 |
July | 21.01 | 15.94 |
August | 21.57 | 16.62 |
September | 21.70 | 16.72 |
October | 21.19 | 15.11 |
November | 20.74 | 12.79 |
December | 19.84 | 10.66 |
Annual Sum or Average | 20.52 | 13.79 |
Minimum of Months | 19.14 | 9.60 |
Maximum of Months | 21.70 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.93 | 9.60 |
February | 20.71 | 11.29 |
March | 21.30 | 12.66 |
April | 21.77 | 13.68 |
May | 22.25 | 15.00 |
June | 22.32 | 15.34 |
July | 22.70 | 15.94 |
August | 22.75 | 16.62 |
September | 22.75 | 16.72 |
October | 22.17 | 15.11 |
November | 21.29 | 12.79 |
December | 20.32 | 10.66 |
Annual Sum or Average | 21.69 | 13.79 |
Minimum of Months | 19.93 | 9.60 |
Maximum of Months | 22.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.39 | 9.60 |
February | 21.57 | 11.29 |
March | 21.67 | 12.66 |
April | 21.72 | 13.68 |
May | 21.75 | 15.00 |
June | 21.74 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.68 | 12.79 |
December | 21.50 | 10.66 |
Annual Sum or Average | 21.67 | 13.79 |
Minimum of Months | 21.39 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 9.60 |
February | 21.62 | 11.29 |
March | 21.70 | 12.66 |
April | 21.73 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.70 | 12.79 |
December | 21.57 | 10.66 |
Annual Sum or Average | 21.69 | 13.79 |
Minimum of Months | 21.47 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 9.60 |
February | 21.64 | 11.29 |
March | 21.70 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.74 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.71 | 12.79 |
December | 21.61 | 10.66 |
Annual Sum or Average | 21.70 | 13.79 |
Minimum of Months | 21.51 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | 9.60 |
February | 21.46 | 11.29 |
March | 21.56 | 12.66 |
April | 21.62 | 13.68 |
May | 21.70 | 15.00 |
June | 21.69 | 15.34 |
July | 21.73 | 15.94 |
August | 21.74 | 16.62 |
September | 21.74 | 16.72 |
October | 21.70 | 15.11 |
November | 21.60 | 12.79 |
December | 21.40 | 10.66 |
Annual Sum or Average | 21.60 | 13.79 |
Minimum of Months | 21.28 | 9.60 |
Maximum of Months | 21.74 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | 9.60 |
February | 21.68 | 11.29 |
March | 21.71 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.74 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.75 | 15.11 |
November | 21.73 | 12.79 |
December | 21.65 | 10.66 |
Annual Sum or Average | 21.71 | 13.79 |
Minimum of Months | 21.56 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 9.60 |
February | 23.33 | 11.29 |
March | 23.33 | 12.66 |
April | 23.33 | 13.68 |
May | 23.33 | 15.00 |
June | 23.33 | 15.34 |
July | 23.33 | 15.94 |
August | 23.33 | 16.62 |
September | 23.33 | 16.72 |
October | 23.33 | 15.11 |
November | 23.33 | 12.79 |
December | 23.33 | 10.66 |
Annual Sum or Average | 23.33 | 13.79 |
Minimum of Months | 23.32 | 9.60 |
Maximum of Months | 23.33 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 31.57 | 9.60 |
February | 31.87 | 11.29 |
March | 31.95 | 12.66 |
April | 31.98 | 13.68 |
May | 32.15 | 15.00 |
June | 32.20 | 15.34 |
July | 32.34 | 15.94 |
August | 32.51 | 16.62 |
September | 32.47 | 16.72 |
October | 32.36 | 15.11 |
November | 32.21 | 12.79 |
December | 31.79 | 10.66 |
Annual Sum or Average | 32.12 | 13.79 |
Minimum of Months | 31.57 | 9.60 |
Maximum of Months | 32.51 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 9.60 |
February | 22.15 | 11.29 |
March | 22.22 | 12.66 |
April | 22.27 | 13.68 |
May | 22.34 | 15.00 |
June | 22.37 | 15.34 |
July | 22.41 | 15.94 |
August | 22.45 | 16.62 |
September | 22.45 | 16.72 |
October | 22.33 | 15.11 |
November | 22.24 | 12.79 |
December | 22.10 | 10.66 |
Annual Sum or Average | 22.28 | 13.79 |
Minimum of Months | 22.05 | 9.60 |
Maximum of Months | 22.45 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 9.60 |
February | 21.72 | 11.29 |
March | 21.74 | 12.66 |
April | 21.75 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.75 | 15.11 |
November | 21.74 | 12.79 |
December | 21.71 | 10.66 |
Annual Sum or Average | 21.73 | 13.79 |
Minimum of Months | 21.64 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 9.60 |
February | 21.67 | 11.29 |
March | 21.71 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.75 | 15.11 |
November | 21.73 | 12.79 |
December | 21.63 | 10.66 |
Annual Sum or Average | 21.71 | 13.79 |
Minimum of Months | 21.54 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.35 | 9.60 |
February | 21.83 | 11.29 |
March | 22.04 | 12.66 |
April | 22.26 | 13.68 |
May | 22.65 | 15.00 |
June | 22.75 | 15.34 |
July | 23.02 | 15.94 |
August | 23.31 | 16.62 |
September | 23.22 | 16.72 |
October | 22.87 | 15.11 |
November | 22.47 | 12.79 |
December | 21.70 | 10.66 |
Annual Sum or Average | 22.46 | 13.79 |
Minimum of Months | 21.35 | 9.60 |
Maximum of Months | 23.31 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | 9.60 |
February | 20.26 | 11.29 |
March | 20.47 | 12.66 |
April | 20.68 | 13.68 |
May | 21.30 | 15.00 |
June | 21.49 | 15.34 |
July | 21.87 | 15.94 |
August | 22.43 | 16.62 |
September | 22.30 | 16.72 |
October | 21.83 | 15.11 |
November | 21.36 | 12.79 |
December | 20.20 | 10.66 |
Annual Sum or Average | 21.16 | 13.79 |
Minimum of Months | 19.61 | 9.60 |
Maximum of Months | 22.43 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.97 | 9.60 |
February | 20.70 | 11.29 |
March | 20.82 | 12.66 |
April | 20.83 | 13.68 |
May | 21.27 | 15.00 |
June | 21.39 | 15.34 |
July | 21.80 | 15.94 |
August | 22.43 | 16.62 |
September | 22.52 | 16.72 |
October | 22.06 | 15.11 |
November | 21.70 | 12.79 |
December | 20.70 | 10.66 |
Annual Sum or Average | 21.35 | 13.79 |
Minimum of Months | 19.97 | 9.60 |
Maximum of Months | 22.52 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 9.60 |
February | 22.18 | 11.29 |
March | 22.57 | 12.66 |
April | 22.86 | 13.68 |
May | 23.19 | 15.00 |
June | 23.21 | 15.34 |
July | 23.49 | 15.94 |
August | 23.55 | 16.62 |
September | 23.56 | 16.72 |
October | 23.18 | 15.11 |
November | 22.63 | 12.79 |
December | 21.93 | 10.66 |
Annual Sum or Average | 22.83 | 13.79 |
Minimum of Months | 21.62 | 9.60 |
Maximum of Months | 23.56 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.22 | 9.60 |
February | 19.12 | 11.29 |
March | 19.42 | 12.66 |
April | 19.55 | 13.68 |
May | 20.11 | 15.00 |
June | 20.25 | 15.34 |
July | 20.79 | 15.94 |
August | 21.39 | 16.62 |
September | 21.50 | 16.72 |
October | 20.81 | 15.11 |
November | 20.15 | 12.79 |
December | 19.01 | 10.66 |
Annual Sum or Average | 20.03 | 13.79 |
Minimum of Months | 18.22 | 9.60 |
Maximum of Months | 21.50 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.23 | 9.60 |
February | 19.92 | 11.29 |
March | 20.62 | 12.66 |
April | 21.19 | 13.68 |
May | 21.79 | 15.00 |
June | 21.90 | 15.34 |
July | 22.36 | 15.94 |
August | 22.43 | 16.62 |
September | 22.41 | 16.72 |
October | 21.64 | 15.11 |
November | 20.56 | 12.79 |
December | 19.50 | 10.66 |
Annual Sum or Average | 21.14 | 13.79 |
Minimum of Months | 19.23 | 9.60 |
Maximum of Months | 22.43 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | 9.60 |
February | 20.42 | 11.29 |
March | 21.15 | 12.66 |
April | 21.74 | 13.68 |
May | 22.26 | 15.00 |
June | 22.32 | 15.34 |
July | 22.74 | 15.94 |
August | 22.77 | 16.62 |
September | 22.77 | 16.72 |
October | 22.06 | 15.11 |
November | 20.98 | 12.79 |
December | 19.95 | 10.66 |
Annual Sum or Average | 21.57 | 13.79 |
Minimum of Months | 19.58 | 9.60 |
Maximum of Months | 22.77 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.82 | 9.60 |
February | 20.66 | 11.29 |
March | 21.34 | 12.66 |
April | 21.88 | 13.68 |
May | 22.35 | 15.00 |
June | 22.40 | 15.34 |
July | 22.77 | 15.94 |
August | 22.79 | 16.62 |
September | 22.79 | 16.72 |
October | 22.15 | 15.11 |
November | 21.16 | 12.79 |
December | 20.20 | 10.66 |
Annual Sum or Average | 21.70 | 13.79 |
Minimum of Months | 19.82 | 9.60 |
Maximum of Months | 22.79 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.41 | 9.60 |
February | 21.57 | 11.29 |
March | 21.66 | 12.66 |
April | 21.71 | 13.68 |
May | 21.74 | 15.00 |
June | 21.73 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.73 | 15.11 |
November | 21.67 | 12.79 |
December | 21.52 | 10.66 |
Annual Sum or Average | 21.67 | 13.79 |
Minimum of Months | 21.41 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.83 | 9.60 |
February | 20.60 | 11.29 |
March | 21.13 | 12.66 |
April | 21.52 | 13.68 |
May | 21.98 | 15.00 |
June | 22.04 | 15.34 |
July | 22.47 | 15.94 |
August | 22.58 | 16.62 |
September | 22.62 | 16.72 |
October | 22.00 | 15.11 |
November | 21.19 | 12.79 |
December | 20.27 | 10.66 |
Annual Sum or Average | 21.52 | 13.79 |
Minimum of Months | 19.83 | 9.60 |
Maximum of Months | 22.62 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.38 | 9.60 |
February | 21.55 | 11.29 |
March | 21.65 | 12.66 |
April | 21.70 | 13.68 |
May | 21.74 | 15.00 |
June | 21.72 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.67 | 12.79 |
December | 21.49 | 10.66 |
Annual Sum or Average | 21.66 | 13.79 |
Minimum of Months | 21.38 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 9.60 |
February | 21.73 | 11.29 |
March | 21.74 | 12.66 |
April | 21.75 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.75 | 15.11 |
November | 21.75 | 12.79 |
December | 21.72 | 10.66 |
Annual Sum or Average | 21.74 | 13.79 |
Minimum of Months | 21.65 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.46 | 9.60 |
February | 23.95 | 11.29 |
March | 24.17 | 12.66 |
April | 24.36 | 13.68 |
May | 24.64 | 15.00 |
June | 24.70 | 15.34 |
July | 24.92 | 15.94 |
August | 25.10 | 16.62 |
September | 25.04 | 16.72 |
October | 24.75 | 15.11 |
November | 24.39 | 12.79 |
December | 23.76 | 10.66 |
Annual Sum or Average | 24.44 | 13.79 |
Minimum of Months | 23.46 | 9.60 |
Maximum of Months | 25.10 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.32 | 9.60 |
February | 22.79 | 11.29 |
March | 23.02 | 12.66 |
April | 23.18 | 13.68 |
May | 23.26 | 15.00 |
June | 23.26 | 15.34 |
July | 23.32 | 15.94 |
August | 23.33 | 16.62 |
September | 23.33 | 16.72 |
October | 23.27 | 15.11 |
November | 23.10 | 12.79 |
December | 22.61 | 10.66 |
Annual Sum or Average | 23.07 | 13.79 |
Minimum of Months | 22.32 | 9.60 |
Maximum of Months | 23.33 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 9.60 |
February | 21.66 | 11.29 |
March | 21.71 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.75 | 15.11 |
November | 21.72 | 12.79 |
December | 21.61 | 10.66 |
Annual Sum or Average | 21.71 | 13.79 |
Minimum of Months | 21.52 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | 9.60 |
February | 21.35 | 11.29 |
March | 21.81 | 12.66 |
April | 22.19 | 13.68 |
May | 22.56 | 15.00 |
June | 22.56 | 15.34 |
July | 22.84 | 15.94 |
August | 22.89 | 16.62 |
September | 22.89 | 16.72 |
October | 22.50 | 15.11 |
November | 21.87 | 12.79 |
December | 21.04 | 10.66 |
Annual Sum or Average | 22.10 | 13.79 |
Minimum of Months | 20.70 | 9.60 |
Maximum of Months | 22.89 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | 9.60 |
February | 21.19 | 11.29 |
March | 21.53 | 12.66 |
April | 21.86 | 13.68 |
May | 22.38 | 15.00 |
June | 22.49 | 15.34 |
July | 22.84 | 15.94 |
August | 23.16 | 16.62 |
September | 23.05 | 16.72 |
October | 22.56 | 15.11 |
November | 21.99 | 12.79 |
December | 20.97 | 10.66 |
Annual Sum or Average | 22.05 | 13.79 |
Minimum of Months | 20.54 | 9.60 |
Maximum of Months | 23.16 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.98 | 9.60 |
February | 19.75 | 11.29 |
March | 20.06 | 12.66 |
April | 20.35 | 13.68 |
May | 21.05 | 15.00 |
June | 21.25 | 15.34 |
July | 21.69 | 15.94 |
August | 22.30 | 16.62 |
September | 22.15 | 16.72 |
October | 21.57 | 15.11 |
November | 20.99 | 12.79 |
December | 19.64 | 10.66 |
Annual Sum or Average | 20.82 | 13.79 |
Minimum of Months | 18.98 | 9.60 |
Maximum of Months | 22.30 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.94 | 9.60 |
February | 19.88 | 11.29 |
March | 20.22 | 12.66 |
April | 20.38 | 13.68 |
May | 20.95 | 15.00 |
June | 21.12 | 15.34 |
July | 21.58 | 15.94 |
August | 22.21 | 16.62 |
September | 22.25 | 16.72 |
October | 21.57 | 15.11 |
November | 21.01 | 12.79 |
December | 19.75 | 10.66 |
Annual Sum or Average | 20.82 | 13.79 |
Minimum of Months | 18.94 | 9.60 |
Maximum of Months | 22.25 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | 9.60 |
February | 21.72 | 11.29 |
March | 22.10 | 12.66 |
April | 22.38 | 13.68 |
May | 22.70 | 15.00 |
June | 22.68 | 15.34 |
July | 22.95 | 15.94 |
August | 23.00 | 16.62 |
September | 22.99 | 16.72 |
October | 22.56 | 15.11 |
November | 22.00 | 12.79 |
December | 21.47 | 10.66 |
Annual Sum or Average | 22.32 | 13.79 |
Minimum of Months | 21.31 | 9.60 |
Maximum of Months | 23.00 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.46 | 9.60 |
February | 18.48 | 11.29 |
March | 18.94 | 12.66 |
April | 19.20 | 13.68 |
May | 19.85 | 15.00 |
June | 20.04 | 15.34 |
July | 20.59 | 15.94 |
August | 21.17 | 16.62 |
September | 21.24 | 16.72 |
October | 20.36 | 15.11 |
November | 19.57 | 12.79 |
December | 18.28 | 10.66 |
Annual Sum or Average | 19.60 | 13.79 |
Minimum of Months | 17.46 | 9.60 |
Maximum of Months | 21.24 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | 9.60 |
February | 21.24 | 11.29 |
March | 21.43 | 12.66 |
April | 21.56 | 13.68 |
May | 21.70 | 15.00 |
June | 21.66 | 15.34 |
July | 21.72 | 15.94 |
August | 21.72 | 16.62 |
September | 21.73 | 16.72 |
October | 21.60 | 15.11 |
November | 21.43 | 12.79 |
December | 21.08 | 10.66 |
Annual Sum or Average | 21.48 | 13.79 |
Minimum of Months | 20.93 | 9.60 |
Maximum of Months | 21.73 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.20 | 9.60 |
February | 19.86 | 11.29 |
March | 20.58 | 12.66 |
April | 21.19 | 13.68 |
May | 21.73 | 15.00 |
June | 21.75 | 15.34 |
July | 22.21 | 15.94 |
August | 22.23 | 16.62 |
September | 22.21 | 16.72 |
October | 21.41 | 15.11 |
November | 20.29 | 12.79 |
December | 19.42 | 10.66 |
Annual Sum or Average | 21.01 | 13.79 |
Minimum of Months | 19.20 | 9.60 |
Maximum of Months | 22.23 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.29 | 9.60 |
February | 19.99 | 11.29 |
March | 20.68 | 12.66 |
April | 21.27 | 13.68 |
May | 21.77 | 15.00 |
June | 21.79 | 15.34 |
July | 22.22 | 15.94 |
August | 22.24 | 16.62 |
September | 22.22 | 16.72 |
October | 21.46 | 15.11 |
November | 20.41 | 12.79 |
December | 19.54 | 10.66 |
Annual Sum or Average | 21.08 | 13.79 |
Minimum of Months | 19.29 | 9.60 |
Maximum of Months | 22.24 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.42 | 9.60 |
February | 21.60 | 11.29 |
March | 21.67 | 12.66 |
April | 21.72 | 13.68 |
May | 21.74 | 15.00 |
June | 21.73 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.72 | 15.11 |
November | 21.68 | 12.79 |
December | 21.53 | 10.66 |
Annual Sum or Average | 21.67 | 13.79 |
Minimum of Months | 21.42 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 9.60 |
February | 20.08 | 11.29 |
March | 20.67 | 12.66 |
April | 21.11 | 13.68 |
May | 21.61 | 15.00 |
June | 21.62 | 15.34 |
July | 22.07 | 15.94 |
August | 22.16 | 16.62 |
September | 22.18 | 16.72 |
October | 21.49 | 15.11 |
November | 20.63 | 12.79 |
December | 19.72 | 10.66 |
Annual Sum or Average | 21.06 | 13.79 |
Minimum of Months | 19.39 | 9.60 |
Maximum of Months | 22.18 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.95 | 9.60 |
February | 20.69 | 11.29 |
March | 21.23 | 12.66 |
April | 21.63 | 13.68 |
May | 22.01 | 15.00 |
June | 22.00 | 15.34 |
July | 22.35 | 15.94 |
August | 22.43 | 16.62 |
September | 22.43 | 16.72 |
October | 21.96 | 15.11 |
November | 21.30 | 12.79 |
December | 20.35 | 10.66 |
Annual Sum or Average | 21.53 | 13.79 |
Minimum of Months | 19.95 | 9.60 |
Maximum of Months | 22.43 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | 9.60 |
February | 21.70 | 11.29 |
March | 21.72 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.73 | 12.79 |
December | 21.67 | 10.66 |
Annual Sum or Average | 21.72 | 13.79 |
Minimum of Months | 21.57 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.27 | 9.60 |
February | 21.84 | 11.29 |
March | 22.22 | 12.66 |
April | 22.53 | 13.68 |
May | 22.91 | 15.00 |
June | 23.01 | 15.34 |
July | 23.23 | 15.94 |
August | 23.37 | 16.62 |
September | 23.28 | 16.72 |
October | 22.79 | 15.11 |
November | 22.27 | 12.79 |
December | 21.55 | 10.66 |
Annual Sum or Average | 22.53 | 13.79 |
Minimum of Months | 21.27 | 9.60 |
Maximum of Months | 23.37 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 9.60 |
February | 21.68 | 11.29 |
March | 21.71 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.73 | 12.79 |
December | 21.64 | 10.66 |
Annual Sum or Average | 21.71 | 13.79 |
Minimum of Months | 21.54 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 9.60 |
February | 21.69 | 11.29 |
March | 21.72 | 12.66 |
April | 21.74 | 13.68 |
May | 21.75 | 15.00 |
June | 21.75 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.74 | 15.11 |
November | 21.73 | 12.79 |
December | 21.65 | 10.66 |
Annual Sum or Average | 21.71 | 13.79 |
Minimum of Months | 21.54 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.38 | 9.60 |
February | 21.60 | 11.29 |
March | 21.67 | 12.66 |
April | 21.72 | 13.68 |
May | 21.75 | 15.00 |
June | 21.73 | 15.34 |
July | 21.75 | 15.94 |
August | 21.75 | 16.62 |
September | 21.75 | 16.72 |
October | 21.73 | 15.11 |
November | 21.69 | 12.79 |
December | 21.51 | 10.66 |
Annual Sum or Average | 21.67 | 13.79 |
Minimum of Months | 21.38 | 9.60 |
Maximum of Months | 21.75 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 9.60 |
February | 20.85 | 11.29 |
March | 21.29 | 12.66 |
April | 21.69 | 13.68 |
May | 22.24 | 15.00 |
June | 22.41 | 15.34 |
July | 22.73 | 15.94 |
August | 23.03 | 16.62 |
September | 22.88 | 16.72 |
October | 22.25 | 15.11 |
November | 21.61 | 12.79 |
December | 20.54 | 10.66 |
Annual Sum or Average | 21.81 | 13.79 |
Minimum of Months | 20.10 | 9.60 |
Maximum of Months | 23.03 | 16.72 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.34 | 9.60 |
February | 19.24 | 11.29 |
March | 19.68 | 12.66 |
April | 20.07 | 13.68 |
May | 20.83 | 15.00 |
June | 21.08 | 15.34 |
July | 21.51 | 15.94 |
August | 22.10 | 16.62 |
September | 21.92 | 16.72 |
October | 21.19 | 15.11 |
November | 20.49 | 12.79 |
December | 19.04 | 10.66 |
Annual Sum or Average | 20.46 | 13.79 |
Minimum of Months | 18.34 | 9.60 |
Maximum of Months | 22.10 | 16.72 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:42
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.148036E+12 | 99402.545 | 24-JAN-07:15 | 20847.837 | 39740.848 | 9022.714 | 23221.021 | 2374.012 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.134267E+12 | 94021.812 | 02-FEB-07:15 | 20847.837 | 39740.848 | 9022.714 | 16256.730 | 3957.571 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.150719E+12 | 93023.360 | 23-MAR-06:15 | 20847.837 | 39740.848 | 9022.714 | 20325.107 | 3078.740 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.147364E+12 | 92861.042 | 01-APR-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 14578.656 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.155567E+12 | 95893.125 | 12-MAY-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 17610.739 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.152227E+12 | 99253.875 | 30-JUN-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 20971.489 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.158833E+12 | 94064.026 | 14-JUL-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 15781.640 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.161077E+12 | 96276.517 | 04-AUG-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 17994.131 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.156626E+12 | 98008.174 | 16-SEP-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 19725.788 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.155319E+12 | 94036.266 | 06-OCT-07:00 | 25182.171 | 43578.554 | 9513.548 | 0.000 | 15753.880 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.146016E+12 | 94486.765 | 30-NOV-07:30 | 20847.837 | 39740.848 | 9022.714 | 21247.062 | 3620.192 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.148293E+12 | 99526.779 | 26-DEC-07:15 | 20847.837 | 39740.848 | 9022.714 | 23253.673 | 2465.594 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.181434E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.134267E+12 | 92861.042 | 20847.837 | 39740.848 | 9022.714 | 0.000 | 2374.012 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.161077E+12 | 99526.779 | 25182.171 | 43578.554 | 9513.548 | 23253.673 | 20971.489 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:42
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.905616E+11 | 98755.125 | 21-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 58659.097 | 58659.097 | 58659.097 | 0.000 |
February | 0.810893E+11 | 90452.995 | 24-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 50356.966 | 50356.966 | 50356.966 | 0.000 |
March | 0.888066E+11 | 90734.045 | 04-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 50638.016 | 50638.016 | 50638.016 | 0.000 |
April | 0.846168E+11 | 87621.079 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 47525.051 | 47525.051 | 47525.051 | 0.000 |
May | 0.861022E+11 | 92390.710 | 13-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 52294.681 | 52294.681 | 52294.681 | 0.000 |
June | 0.820825E+11 | 87667.044 | 09-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 47571.015 | 47571.015 | 47571.015 | 0.000 |
July | 0.838691E+11 | 87875.251 | 08-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 47779.223 | 47779.223 | 47779.223 | 0.000 |
August | 0.837048E+11 | 86827.168 | 04-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 46731.140 | 46731.140 | 46731.140 | 0.000 |
September | 0.813925E+11 | 88043.889 | 08-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 47947.861 | 47947.861 | 47947.861 | 0.000 |
October | 0.852575E+11 | 90814.147 | 14-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 50718.119 | 50718.119 | 50718.119 | 0.000 |
November | 0.841362E+11 | 88474.246 | 12-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 48378.218 | 48378.218 | 48378.218 | 0.000 |
December | 0.891208E+11 | 91386.900 | 01-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 51290.872 | 51290.872 | 51290.872 | 0.000 |
Annual Sum or Average | 0.102074E+13 | 0.000 | ||||||||
Minimum of Months | 0.810893E+11 | 86827.168 | 0.000 | 40096.028 | 0.000 | 46731.140 | 46731.140 | 46731.140 | 0.000 | |
Maximum of Months | 0.905616E+11 | 98755.125 | 0.000 | 40096.028 | 0.000 | 58659.097 | 58659.097 | 58659.097 | 0.000 |