Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2015-09-14 08:44:56


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3217.65 801.69 863.78
Net Site Energy 3217.65 801.69 863.78
Total Source Energy 8397.65 2092.31 2254.35
Net Source Energy 8397.65 2092.31 2254.35


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 1.21 0.22 0.00 0.00 0.00 0.00
Cooling 807.94 0.00 0.00 0.00 0.00 0.00
Interior Lighting 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.92 0.00 0.00 0.00 0.00 0.00
Interior Equipment 601.95 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 301.64 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 438.90 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2357.04 860.61 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 1.21 0.22 0.00 0.00 0.00 0.00
Cooling General 807.94 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.92 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 573.47 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 301.64 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 438.90 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 172.90 0.00 0.00 0.00 0.00 0.00
HVAC 298.26 117.88 0.00 0.00 0.00 0.69
Other 161.59 113.15 0.00 0.00 0.00 0.00
Total 632.75 231.03 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.47 0.00 0.00 0.00 0.00 0.00
HVAC 276.82 109.41 0.00 0.00 0.00 0.64
Other 149.98 105.02 0.00 0.00 0.00 0.00
Total 587.27 214.42 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2357.04 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2357.04 100.00
     
Total On-Site and Utility Electric Sources 2357.04 100.00
Total Electricity End Uses 2357.04 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 64.50
Time Setpoint Not Met During Occupied Cooling 6465.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 6910.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
RunPeriod Miami Intl Ap FL USA TMY3 WMO#=722020
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Window Opening Area [m2] 184.20 8.38 72.38 6.62 96.82
Window-Wall Ratio [%] 10.87 3.95 11.39 3.13 15.24


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Window Opening Area [m2] 179.26 8.38 67.45 6.62 96.82
Window-Wall Ratio [%] 12.01 3.95 12.11 5.68 15.95


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 8.3610   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 6.9675   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 11.1480   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 15.3285 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 12.5415 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 18.1154 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 20.9024   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 16.7220 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 8.3610 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2155.0206
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 12.5415 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 15.3285 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 8.3610   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 11.1480   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
Total 4013.58     11621.73   1694.58 184.20 11.2819 15.53 28.2097
Conditioned Total 3725.09     10741.65   1492.32 179.26 11.5457 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 7.8766 26.23 260.8031
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 180.00 90.00 S
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 90.00 90.00 E
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 180.00 90.00 S
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 90.00 90.00 E
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 0.00 90.00 N
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 270.00 90.00 W
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 90.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 180.00 90.00 S
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 270.00 90.00 W
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 66.43 270.00 90.00 W
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 90.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 270.00 90.00 W
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 32.70 270.00 90.00 W
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 90.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 270.00 90.00 W
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 270.00 90.00 W
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 270.00 90.00 W
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 270.00 90.00 W
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 90.00 90.00 E
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 90.00 90.00 E
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 90.00 90.00 E
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 39.86 90.00 90.00 E
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 90.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 90.00 90.00 E
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 90.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 90.00 90.00 E
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 53.14 90.00 90.00 E
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 90.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 90.00 90.00 E
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 0.00 90.00 N
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 5.11 90.00 90.00 E
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 90.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 180.00 90.00 S
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 90.00 90.00 E
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 180.00 90.00 S
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.704 0.787 8.36 90.00 90.00 E
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 0.00 90.00 N
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 180.00 90.00 S
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 270.00 90.00 W
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 0.00 90.00 N
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 270.00 90.00 W
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 270.00 90.00 W
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 35.12 270.00 90.00 W
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 270.00 90.00 W
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 270.00 90.00 W
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 90.00 90.00 E
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 90.00 90.00 E
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 90.00 90.00 E
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 0.00 90.00 N
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 180.00 90.00 S
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 90.00 90.00 E
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 180.00 90.00 S
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.704 0.787 8.36 90.00 90.00 E
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 0.00 90.00 N
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 180.00 90.00 S
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 270.00 90.00 W
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 0.00 90.00 N
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 270.00 90.00 W
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 270.00 90.00 W
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 35.12 270.00 90.00 W
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 270.00 90.00 W
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 270.00 90.00 W
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 90.00 90.00 E
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 90.00 90.00 E
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 90.00 90.00 E
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 0.00 90.00 N
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 180.00 90.00 S
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 90.00 90.00 E
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 180.00 90.00 S
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.704 0.787 8.36 90.00 90.00 E
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 0.00 90.00 N
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 270.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 180.00 90.00 S
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 270.00 90.00 W
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 0.00 90.00 N
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 270.00 90.00 W
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 270.00 90.00 W
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 35.12 270.00 90.00 W
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 270.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 270.00 90.00 W
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 270.00 90.00 W
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 90.00 90.00 E
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 90.00 90.00 E
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 270.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 90.00 90.00 E
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 90.00 90.00 E
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 4.18 90.00 90.00 E
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 270.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 0.00 90.00 N
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 5.778 0.306 0.155     No W_CORRIDORFLR1_2_0_0 180.00 90.00 S
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 4.44 0.00 0.00 4.44 4.44 5.778 0.306 0.155     No W_CORRIDORFLR1_16_0_0 0.00 90.00 N
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 5.778 0.306 0.155     No W_CORRIDORFLR1_20_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_1.16_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM101_5_0_0 270.00 90.00 W
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM102_5_0_0 270.00 90.00 W
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM103_5_0_0 270.00 90.00 W
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM104_3_0_0 90.00 90.00 E
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM105_3_0_0 90.00 90.00 E
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_EMPLOYEELOUNGEFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_EXERCISECENTERFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR2_2_0_0 180.00 90.00 S
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR2_15_0_0 0.00 90.00 N
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM201_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 5.778 0.306 0.155     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM213_5_0_0 270.00 90.00 W
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM214_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM219_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM224_3_0_0 90.00 90.00 E
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR3_2_0_0 180.00 90.00 S
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR3_15_0_0 0.00 90.00 N
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM301_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 5.778 0.306 0.155     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM313_5_0_0 270.00 90.00 W
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM314_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM319_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM324_3_0_0 90.00 90.00 E
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR4_2_0_0 180.00 90.00 S
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR4_15_0_0 0.00 90.00 N
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM401_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 5.778 0.306 0.155     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM413_5_0_0 270.00 90.00 W
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM414_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM419_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_1.16_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM424_3_0_0 90.00 90.00 E
Total or Average           184.20 5.778 0.306 0.155              
North Total or Average           8.38 5.778 0.306 0.155              
Non-North Total or Average           175.82 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   9286.73 6572.29 2714.44 0.71 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   26830.81 18139.86 8690.95 0.68 3.50    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   11848.70 8010.71 3837.99 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   16758.51 11998.11 4760.40 0.72 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 8958.7 3.32 11.32 12.00 11.38
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 25991.0 3.06 10.43 11.07 10.68
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 11477.8 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 16149.1 3.30 11.27 11.94 11.30
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.02 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   13188.01 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   514.12 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   514.12 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   682.49 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   320.94 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.02 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   1935.59 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   682.49 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   2729.97 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   2163.60 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   2729.97 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   682.49 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   2056.32 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   2729.78 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   320.94 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.02 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   1935.59 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   682.49 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   2729.97 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   2163.60 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   2729.97 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   682.49 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   2729.78 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   514.08 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   2729.78 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   320.94 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.02 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   2044.94 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   888.83 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   2729.97 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   2163.60 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   2729.97 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   682.49 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   2729.78 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   682.45 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   2729.78 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   735.23 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   320.94 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   2810.21 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   11778.92 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   6307.52 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   4711.23 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.54 622.50 0.42 490.14 1160.84 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.55 622.50 1.08 1231.86 1140.11 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.54 622.50 0.48 553.89 1160.84 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.55 622.50 0.78 894.55 1140.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.51 0.27
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 10906.08 13087.29 0.900 1.080 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.09 0.01715
RESTROOMFLR1 801.15 961.38 0.066 0.079 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.34 0.01715
MEETINGROOMFLR1 4813.88 5776.65 0.398 0.477 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM101 708.82 850.58 0.062 0.074 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM102 566.97 680.36 0.050 0.059 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM103 1704.71 2045.65 0.196 0.235 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM104 1545.79 1854.94 0.177 0.213 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM105 1925.10 2310.12 0.221 0.265 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
EMPLOYEELOUNGEFLR1 5704.40 6845.28 0.471 0.565 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
EXERCISECENTERFLR1 1415.12 1698.14 0.117 0.140 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:15:00 29.80 0.01715
FRONTOFFICEFLR1 4265.34 5118.40 0.352 0.422 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
GUESTROOM201 1068.01 1281.61 0.093 0.112 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM202_205 6467.88 7761.45 0.742 0.890 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM206_208 5282.89 6339.47 0.606 0.727 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM209_212 6070.20 7284.24 0.696 0.836 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM213 1785.50 2142.60 0.205 0.246 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM214 1738.04 2085.65 0.199 0.239 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM215_218 8848.21 10617.85 0.773 0.928 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM219 5695.99 6835.19 0.653 0.784 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM220_223 5762.84 6915.41 0.661 0.793 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.41 0.01715
GUESTROOM224 1736.06 2083.27 0.199 0.239 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM301 947.44 1136.92 0.083 0.099 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM302_305 2487.80 2985.36 0.217 0.261 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM306_308 2211.86 2654.23 0.193 0.232 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM309_312 6095.67 7314.80 0.699 0.839 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM313 836.71 1004.06 0.073 0.088 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
GUESTROOM314 1672.47 2006.97 0.192 0.230 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM315_318 6411.91 7694.30 0.736 0.883 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM319 952.66 1143.19 0.083 0.100 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM320_323 5601.71 6722.06 0.643 0.771 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM324 671.30 805.56 0.059 0.070 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 31.66 0.01715
GUESTROOM401 2321.82 2786.19 0.266 0.320 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.40 0.01715
GUESTROOM402_405 3514.63 4217.55 0.307 0.369 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.40 0.01715
GUESTROOM406_408 3124.68 3749.61 0.273 0.328 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.40 0.01715
GUESTROOM409_412 7375.13 8850.16 0.846 1.015 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 32.40 0.01715
GUESTROOM413 1189.04 1426.84 0.104 0.125 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
GUESTROOM414 961.92 1154.31 0.084 0.101 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 32.33 0.01715
GUESTROOM415_418 6957.65 8349.18 0.798 0.958 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 31.99 0.01715
GUESTROOM419 1913.12 2295.75 0.219 0.263 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.16 0.01715
GUESTROOM420_423 6822.40 8186.88 0.783 0.939 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 31.99 0.01715
GUESTROOM424 1982.08 2378.49 0.227 0.273 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 32.16 0.01715
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
CORRIDORFLR1 18741.22 22489.47 1.547 1.857 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
CORRIDORFLR2 3147.91 3777.49 0.260 0.311 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.76 0.01715
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
CORRIDORFLR3 1923.36 2308.03 0.159 0.190 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 31.76 0.01715
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715
CORRIDORFLR4 2971.90 3566.28 0.245 0.294 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.20 0.01715
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB   33.20 0.01715


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1040.35 1248.42 0.029 0.236 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:15:00 8.70 0.00699
MEETINGROOMFLR1 316.87 380.24 0.009 0.126 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:00:00 8.70 0.00699
GUESTROOM101 0.00 0.00 0.000 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
GUESTROOM102 0.00 0.00 0.000 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
GUESTROOM103 315.39 378.47 0.009 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 8.70 0.00699
GUESTROOM104 243.74 292.49 0.007 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 8.70 0.00699
GUESTROOM105 180.74 216.89 0.005 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:30:00 8.70 0.00699
EMPLOYEELOUNGEFLR1 150.64 180.77 0.004 0.051 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70 0.00699
EXERCISECENTERFLR1 65.17 78.20 0.002 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:00:00 8.70 0.00699
FRONTOFFICEFLR1 553.41 664.09 0.016 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:30:00 8.70 0.00699
GUESTROOM201 113.31 135.97 0.003 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 8.70 0.00699
GUESTROOM202_205 907.77 1089.33 0.026 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:45:00 8.70 0.00699
GUESTROOM206_208 645.49 774.59 0.018 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 8.70 0.00699
GUESTROOM209_212 649.20 779.05 0.018 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 8.70 0.00699
GUESTROOM213 384.78 461.74 0.011 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 8.70 0.00699
GUESTROOM214 297.24 356.69 0.008 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:30:00 8.70 0.00699
GUESTROOM215_218 0.00 0.00 0.000 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
GUESTROOM219 150.43 180.51 0.004 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 8.70 0.00699
GUESTROOM220_223 548.38 658.05 0.015 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:15:00 8.70 0.00699
GUESTROOM224 274.74 329.69 0.008 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 8.70 0.00699
GUESTROOM301 167.18 200.62 0.004 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:45:00 8.70 0.00699
GUESTROOM302_305 253.30 303.96 0.007 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:30:00 8.70 0.00699
GUESTROOM306_308 187.07 224.49 0.005 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 14:30:00 8.70 0.00699
GUESTROOM309_312 836.42 1003.71 0.024 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:15:00 8.70 0.00699
GUESTROOM313 142.07 170.49 0.004 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 19:00:00 8.70 0.00699
GUESTROOM314 365.15 438.18 0.010 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:30:00 8.70 0.00699
GUESTROOM315_318 837.71 1005.26 0.024 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:45:00 8.70 0.00699
GUESTROOM319 0.00 0.00 0.000 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
GUESTROOM320_323 717.55 861.06 0.020 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 8.70 0.00699
GUESTROOM324 31.08 37.30 0.001 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:00:00 8.70 0.00699
GUESTROOM401 569.78 683.74 0.016 0.019 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 22:00:00 8.70 0.00699
GUESTROOM402_405 641.02 769.22 0.017 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 21:45:00 8.70 0.00699
GUESTROOM406_408 527.73 633.28 0.014 0.043 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 19:15:00 8.70 0.00699
GUESTROOM409_412 1219.61 1463.53 0.034 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 19:45:00 8.70 0.00699
GUESTROOM413 270.24 324.29 0.007 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:45:00 8.70 0.00699
GUESTROOM414 167.63 201.16 0.004 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 20:00:00 8.70 0.00699
GUESTROOM415_418 1147.05 1376.46 0.032 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:45:00 8.70 0.00699
GUESTROOM419 350.03 420.04 0.010 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 18:45:00 8.70 0.00699
GUESTROOM420_423 1059.42 1271.30 0.030 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 18:45:00 8.70 0.00699
GUESTROOM424 441.79 530.15 0.012 0.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:45:00 8.70 0.00699
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
CORRIDORFLR1 10407.95 12489.54 0.294 0.352 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8.70 0.00699
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
CORRIDORFLR2 394.19 473.03 0.011 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:45:00 8.70 0.00699
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
CORRIDORFLR3 715.99 859.19 0.020 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 8.70 0.00699
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
CORRIDORFLR4 1219.41 1463.29 0.034 0.041 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 23:45:00 8.70 0.00699
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.42 0.42 0.06 0.06
SAC_FRONTLOUNGE 1.08 1.08 0.24 0.24
SAC_MEETINGROOM 0.48 0.48 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.78 0.78 0.09 0.09



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 7171.75 4546.50 3749.00
RESTROOMFLR1 3858.25 2911.75 889.00
MEETINGROOMFLR1 3937.00 1490.50 1279.50
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 464.00 7822.75 367.75
GUESTROOM104 345.25 7249.00 123.50
GUESTROOM105 772.50 6814.50 22.75
EMPLOYEELOUNGEFLR1 3666.25 1883.75 534.50
EXERCISECENTERFLR1 4957.25 341.00 206.50
FRONTOFFICEFLR1 6387.50 1430.75 671.75
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 1170.50 6857.75 98.25
GUESTROOM206_208 1148.50 6807.50 53.50
GUESTROOM209_212 971.25 7182.75 289.00
GUESTROOM213 676.00 7206.75 157.00
GUESTROOM214 1003.00 6806.75 35.75
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 6553.50 3389.00 1978.50
GUESTROOM220_223 1307.50 6713.75 79.00
GUESTROOM224 1025.00 6777.50 15.00
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 1020.75 7393.00 434.25
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 1056.25 6826.75 41.00
GUESTROOM315_318 1436.75 6644.75 61.50
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 1191.25 6914.75 160.75
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 1810.00 6701.25 199.50
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1907.00 6510.25 71.50
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 2017.75 6352.25 41.25
GUESTROOM419 1734.00 6461.00 22.00
GUESTROOM420_423 1994.00 6375.50 48.00
GUESTROOM424 1742.25 6482.75 17.50
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 8220.00 8733.25 6910.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 0.00 2445.75 0.00 2445.75
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 0.00 89.25 0.00 89.25
GUESTROOM104 0.00 89.25 0.00 89.25
GUESTROOM105 0.00 89.75 0.00 89.75
EMPLOYEELOUNGEFLR1 103.75 1104.75 64.50 602.25
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 0.00 84.00 0.00 84.00
GUESTROOM206_208 0.00 88.00 0.00 88.00
GUESTROOM209_212 0.00 83.50 0.00 83.50
GUESTROOM213 0.00 84.50 0.00 84.50
GUESTROOM214 0.00 82.50 0.00 82.50
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 5569.00 0.00 5569.00
GUESTROOM220_223 0.00 80.50 0.00 80.50
GUESTROOM224 0.00 81.75 0.00 81.75
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.00 83.25 0.00 83.25
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.00 82.00 0.00 82.00
GUESTROOM315_318 0.00 81.25 0.00 81.25
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 79.00 0.00 79.00
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 0.00 205.25 0.00 205.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 0.00 89.25 0.00 89.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 83.50 0.00 83.50
GUESTROOM419 0.00 89.50 0.00 89.50
GUESTROOM420_423 0.00 83.25 0.00 83.25
GUESTROOM424 0.00 97.50 0.00 97.50
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 1.25 7635.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 2459.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 173.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 1654.25 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 105.00 8199.00 64.50 6465.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:56

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.422233
SAC_FRONTLOUNGE SUPPLY FAN 1.08
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.784619


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 321.02
CORRIDORFLR1 PTAC HEATING COIL 13188.01
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 514.12
102 PTAC HEATING COIL 514.12
103 PTAC HEATING COIL 682.49
104 PTAC HEATING COIL 682.45
105 PTAC HEATING COIL 682.45
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 320.94
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 321.02
CORRIDORFLR2 PTAC HEATING COIL 1935.59
201 PTAC HEATING COIL 682.49
202_205 PTAC HEATING COIL 2729.97
206_208 PTAC HEATING COIL 2163.60
209_212 PTAC HEATING COIL 2729.97
213 PTAC HEATING COIL 682.49
214 PTAC HEATING COIL 682.45
215_218 PTAC HEATING COIL 2056.32
219 PTAC HEATING COIL 682.45
220_223 PTAC HEATING COIL 2729.78
224 PTAC HEATING COIL 682.45
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 320.94
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 321.02
CORRIDORFLR3 PTAC HEATING COIL 1935.59
301 PTAC HEATING COIL 682.49
302_305 PTAC HEATING COIL 2729.97
306_308 PTAC HEATING COIL 2163.60
309_312 PTAC HEATING COIL 2729.97
313 PTAC HEATING COIL 682.49
314 PTAC HEATING COIL 682.45
315_318 PTAC HEATING COIL 2729.78
319 PTAC HEATING COIL 514.08
320_323 PTAC HEATING COIL 2729.78
324 PTAC HEATING COIL 682.45
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 320.94
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 321.02
CORRIDORFLR4 PTAC HEATING COIL 2044.94
401 PTAC HEATING COIL 888.83
402_405 PTAC HEATING COIL 2729.97
406_408 PTAC HEATING COIL 2163.60
409_412 PTAC HEATING COIL 2729.97
413 PTAC HEATING COIL 682.49
414 PTAC HEATING COIL 682.45
415_418 PTAC HEATING COIL 2729.78
419 PTAC HEATING COIL 682.45
420_423 PTAC HEATING COIL 2729.78
424 PTAC HEATING COIL 735.23
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 320.94


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.707708 0.422233 9286.73
SAC_FRONTLOUNGE COOLING COIL 0.676083 1.08 26830.81
SAC_MEETINGROOM COOLING COIL 0.676083 0.477147 11848.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.715941 0.784619 16758.51


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 1.08
RESTROOMFLR1 DIRECT AIR 0.079292
MEETINGROOMFLR1 DIRECT AIR 0.477147
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.565192
EXERCISECENTERFLR1 DIRECT AIR 0.140135
FRONTOFFICEFLR1 DIRECT AIR 0.422233


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.422233
SAC_FRONTLOUNGE MAIN BRANCH 1.08
SAC_MEETINGROOM MAIN BRANCH 0.477147
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.784619


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.422233
SAC_FRONTLOUNGE 1.08
SAC_MEETINGROOM 0.477147
SAC_EXC_EMPLGE_RESTRM 0.784619


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.422233 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 1.08 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.477147 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.784619 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.422233 0.422233 0.422233 0.422233 2810.21 9286.73 1.00
SAC_FRONTLOUNGE 1.08 1.08 1.08 1.08 11778.92 26830.81 1.00
SAC_MEETINGROOM 0.477147 0.477147 0.477147 0.477147 6307.52 11848.70 1.00
SAC_EXC_EMPLGE_RESTRM 0.784619 0.784619 0.784619 0.784619 4711.23 16758.51 0.178603


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 2810.21
SAC_FRONTLOUNGE HEATING COIL 11778.92
SAC_MEETINGROOM HEATING COIL 6307.52
SAC_EXC_EMPLGE_RESTRM HEATING COIL 4711.23


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.477147


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 19.42
February 23.96 20.87
March 24.16 21.57
April 25.12 24.11
May 25.82 26.41
June 26.24 27.68
July 26.40 28.13
August 26.31 27.97
September 26.44 27.49
October 26.06 26.35
November 25.05 23.59
December 24.01 20.30
     
Annual Sum or Average 25.29 24.51
Minimum of Months 23.89 19.42
Maximum of Months 26.44 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.03 19.42
February 25.33 20.87
March 25.55 21.57
April 26.20 24.11
May 26.96 26.41
June 27.42 27.68
July 27.62 28.13
August 27.52 27.97
September 27.39 27.49
October 26.96 26.35
November 26.15 23.59
December 25.29 20.30
     
Annual Sum or Average 26.46 24.51
Minimum of Months 25.03 19.42
Maximum of Months 27.62 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 19.42
February 23.37 20.87
March 23.59 21.57
April 24.55 24.11
May 25.26 26.41
June 25.61 27.68
July 25.75 28.13
August 25.71 27.97
September 25.80 27.49
October 25.45 26.35
November 24.45 23.59
December 23.40 20.30
     
Annual Sum or Average 24.69 24.51
Minimum of Months 23.20 19.42
Maximum of Months 25.80 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.65 19.42
February 23.70 20.87
March 23.76 21.57
April 23.88 24.11
May 23.89 26.41
June 23.89 27.68
July 23.89 28.13
August 23.89 27.97
September 23.89 27.49
October 23.89 26.35
November 23.83 23.59
December 23.68 20.30
     
Annual Sum or Average 23.82 24.51
Minimum of Months 23.65 19.42
Maximum of Months 23.89 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.39 19.42
February 23.45 20.87
March 23.51 21.57
April 23.63 24.11
May 23.69 26.41
June 23.71 27.68
July 23.73 28.13
August 23.74 27.97
September 23.71 27.49
October 23.67 26.35
November 23.57 23.59
December 23.45 20.30
     
Annual Sum or Average 23.60 24.51
Minimum of Months 23.39 19.42
Maximum of Months 23.74 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.71 19.42
February 23.73 20.87
March 23.79 21.57
April 23.88 24.11
May 23.89 26.41
June 23.89 27.68
July 23.89 28.13
August 23.89 27.97
September 23.89 27.49
October 23.89 26.35
November 23.84 23.59
December 23.74 20.30
     
Annual Sum or Average 23.84 24.51
Minimum of Months 23.71 19.42
Maximum of Months 23.89 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.38 19.42
February 26.53 20.87
March 26.70 21.57
April 27.03 24.11
May 27.21 26.41
June 27.30 27.68
July 27.38 28.13
August 27.33 27.97
September 27.28 27.49
October 27.13 26.35
November 26.81 23.59
December 26.50 20.30
     
Annual Sum or Average 26.97 24.51
Minimum of Months 26.38 19.42
Maximum of Months 27.38 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.99 19.42
February 23.08 20.87
March 23.15 21.57
April 23.32 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.25 23.59
December 23.05 20.30
     
Annual Sum or Average 23.24 24.51
Minimum of Months 22.99 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.82 19.42
February 22.97 20.87
March 23.07 21.57
April 23.31 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.20 23.59
December 22.92 20.30
     
Annual Sum or Average 23.19 24.51
Minimum of Months 22.82 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 19.42
February 21.73 20.87
March 21.72 21.57
April 21.75 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.75 23.59
December 21.73 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.72 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.76 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.90 19.42
February 22.80 20.87
March 22.72 21.57
April 22.54 24.11
May 22.38 26.41
June 22.28 27.68
July 22.21 28.13
August 22.29 27.97
September 22.30 27.49
October 22.44 26.35
November 22.66 23.59
December 22.85 20.30
     
Annual Sum or Average 22.53 24.51
Minimum of Months 22.21 19.42
Maximum of Months 22.90 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 52.03 19.42
February 51.99 20.87
March 52.22 21.57
April 52.67 24.11
May 52.95 26.41
June 53.28 27.68
July 53.47 28.13
August 53.23 27.97
September 53.26 27.49
October 52.95 26.35
November 52.46 23.59
December 52.06 20.30
     
Annual Sum or Average 52.72 24.51
Minimum of Months 51.99 19.42
Maximum of Months 53.47 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 70.64 19.42
February 70.25 20.87
March 70.47 21.57
April 71.12 24.11
May 71.45 26.41
June 71.99 27.68
July 72.36 28.13
August 72.09 27.97
September 72.07 27.49
October 71.70 26.35
November 71.00 23.59
December 70.63 20.30
     
Annual Sum or Average 71.32 24.51
Minimum of Months 70.25 19.42
Maximum of Months 72.36 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.84 19.42
February 23.84 20.87
March 23.86 21.57
April 23.89 24.11
May 23.89 26.41
June 23.89 27.68
July 23.89 28.13
August 23.89 27.97
September 23.89 27.49
October 23.89 26.35
November 23.88 23.59
December 23.83 20.30
     
Annual Sum or Average 23.87 24.51
Minimum of Months 23.83 19.42
Maximum of Months 23.89 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 19.42
February 23.85 20.87
March 23.87 21.57
April 23.89 24.11
May 23.89 26.41
June 23.89 27.68
July 23.89 28.13
August 23.89 27.97
September 23.89 27.49
October 23.89 26.35
November 23.88 23.59
December 23.85 20.30
     
Annual Sum or Average 23.88 24.51
Minimum of Months 23.85 19.42
Maximum of Months 23.89 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.48 19.42
February 23.70 20.87
March 24.12 21.57
April 25.49 24.11
May 26.57 26.41
June 27.23 27.68
July 27.44 28.13
August 27.16 27.97
September 27.04 27.49
October 26.35 26.35
November 25.02 23.59
December 23.69 20.30
     
Annual Sum or Average 25.62 24.51
Minimum of Months 23.48 19.42
Maximum of Months 27.44 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.00 19.42
February 24.14 20.87
March 24.43 21.57
April 25.19 24.11
May 25.75 26.41
June 26.12 27.68
July 26.25 28.13
August 26.06 27.97
September 26.01 27.49
October 25.61 26.35
November 24.86 23.59
December 24.10 20.30
     
Annual Sum or Average 25.22 24.51
Minimum of Months 24.00 19.42
Maximum of Months 26.25 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.60 19.42
February 24.56 20.87
March 24.78 21.57
April 25.97 24.11
May 26.77 26.41
June 27.36 27.68
July 27.60 28.13
August 27.45 27.97
September 27.60 27.49
October 27.14 26.35
November 25.89 23.59
December 24.69 20.30
     
Annual Sum or Average 26.21 24.51
Minimum of Months 24.56 19.42
Maximum of Months 27.60 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.87 19.42
February 23.85 20.87
March 23.87 21.57
April 23.94 24.11
May 24.08 26.41
June 24.26 27.68
July 24.34 28.13
August 24.30 27.97
September 24.26 27.49
October 24.07 26.35
November 23.93 23.59
December 23.86 20.30
     
Annual Sum or Average 24.06 24.51
Minimum of Months 23.85 19.42
Maximum of Months 24.34 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.60 19.42
February 23.73 20.87
March 23.98 21.57
April 25.17 24.11
May 26.00 26.41
June 26.48 27.68
July 26.68 28.13
August 26.60 27.97
September 26.70 27.49
October 26.27 26.35
November 25.04 23.59
December 23.80 20.30
     
Annual Sum or Average 25.34 24.51
Minimum of Months 23.60 19.42
Maximum of Months 26.70 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 19.42
February 22.99 20.87
March 23.08 21.57
April 23.32 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.23 23.59
December 22.93 20.30
     
Annual Sum or Average 23.20 24.51
Minimum of Months 22.89 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.75 23.59
December 21.75 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 19.42
February 21.74 20.87
March 21.73 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.75 23.59
December 21.74 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.73 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.76 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 19.42
February 23.33 20.87
March 23.33 21.57
April 23.33 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.33 23.59
December 23.33 20.30
     
Annual Sum or Average 23.33 24.51
Minimum of Months 23.33 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 32.89 19.42
February 32.76 20.87
March 32.96 21.57
April 33.47 24.11
May 33.81 26.41
June 34.20 27.68
July 34.40 28.13
August 34.23 27.97
September 34.20 27.49
October 33.86 26.35
November 33.29 23.59
December 32.90 20.30
     
Annual Sum or Average 33.58 24.51
Minimum of Months 32.76 19.42
Maximum of Months 34.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.57 19.42
February 22.64 20.87
March 22.78 21.57
April 23.04 24.11
May 23.48 26.41
June 23.88 27.68
July 23.99 28.13
August 23.90 27.97
September 23.81 27.49
October 23.44 26.35
November 23.02 23.59
December 22.66 20.30
     
Annual Sum or Average 23.27 24.51
Minimum of Months 22.57 19.42
Maximum of Months 23.99 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.76 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.76 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 19.42
February 24.27 20.87
March 24.63 21.57
April 25.62 24.11
May 26.31 26.41
June 26.80 27.68
July 26.97 28.13
August 26.71 27.97
September 26.65 27.49
October 26.14 26.35
November 25.19 23.59
December 24.24 20.30
     
Annual Sum or Average 25.65 24.51
Minimum of Months 24.14 19.42
Maximum of Months 26.97 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.01 19.42
February 24.19 20.87
March 24.70 21.57
April 26.43 24.11
May 27.72 26.41
June 28.65 27.68
July 28.98 28.13
August 28.55 27.97
September 28.41 27.49
October 27.52 26.35
November 25.85 23.59
December 24.26 20.30
     
Annual Sum or Average 26.62 24.51
Minimum of Months 24.01 19.42
Maximum of Months 28.98 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.58 19.42
February 24.55 20.87
March 24.81 21.57
April 26.12 24.11
May 26.98 26.41
June 27.61 27.68
July 27.88 28.13
August 27.70 27.97
September 27.84 27.49
October 27.34 26.35
November 25.99 23.59
December 24.68 20.30
     
Annual Sum or Average 26.35 24.51
Minimum of Months 24.55 19.42
Maximum of Months 27.88 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.69 19.42
February 23.71 20.87
March 23.77 21.57
April 23.89 24.11
May 23.89 26.41
June 23.90 27.68
July 23.93 28.13
August 23.92 27.97
September 23.91 27.49
October 23.89 26.35
November 23.84 23.59
December 23.69 20.30
     
Annual Sum or Average 23.84 24.51
Minimum of Months 23.69 19.42
Maximum of Months 23.93 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.57 19.42
February 23.73 20.87
March 24.04 21.57
April 25.39 24.11
May 26.29 26.41
June 26.83 27.68
July 27.07 28.13
August 26.95 27.97
September 27.04 27.49
October 26.56 26.35
November 25.19 23.59
December 23.80 20.30
     
Annual Sum or Average 25.55 24.51
Minimum of Months 23.57 19.42
Maximum of Months 27.07 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.65 19.42
February 22.84 20.87
March 22.97 21.57
April 23.31 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.17 23.59
December 22.71 20.30
     
Annual Sum or Average 23.14 24.51
Minimum of Months 22.65 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 19.42
February 23.01 20.87
March 23.10 21.57
April 23.33 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.24 23.59
December 22.93 20.30
     
Annual Sum or Average 23.21 24.51
Minimum of Months 22.89 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.89 19.42
February 23.02 20.87
March 23.11 21.57
April 23.32 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.23 23.59
December 22.94 20.30
     
Annual Sum or Average 23.21 24.51
Minimum of Months 22.89 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 19.42
February 21.75 20.87
March 21.74 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.75 23.59
December 21.74 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.74 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.93 19.42
February 23.02 20.87
March 23.09 21.57
April 23.33 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.24 23.59
December 22.96 20.30
     
Annual Sum or Average 23.21 24.51
Minimum of Months 22.93 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.76 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.51 19.42
February 25.54 20.87
March 25.76 21.57
April 26.29 24.11
May 26.60 26.41
June 26.83 27.68
July 26.94 28.13
August 26.81 27.97
September 26.79 27.49
October 26.54 26.35
November 26.02 23.59
December 25.53 20.30
     
Annual Sum or Average 26.27 24.51
Minimum of Months 25.51 19.42
Maximum of Months 26.94 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 19.42
February 23.29 20.87
March 23.31 21.57
April 23.33 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.32 23.59
December 23.29 20.30
     
Annual Sum or Average 23.32 24.51
Minimum of Months 23.29 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.07 19.42
February 23.12 20.87
March 23.20 21.57
April 23.33 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.27 23.59
December 23.07 20.30
     
Annual Sum or Average 23.26 24.51
Minimum of Months 23.07 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.08 19.42
February 24.25 20.87
March 24.68 21.57
April 25.82 24.11
May 26.58 26.41
June 27.12 27.68
July 27.32 28.13
August 27.01 27.97
September 26.94 27.49
October 26.38 26.35
November 25.30 23.59
December 24.20 20.30
     
Annual Sum or Average 25.82 24.51
Minimum of Months 24.08 19.42
Maximum of Months 27.32 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.98 19.42
February 24.18 20.87
March 24.74 21.57
April 26.63 24.11
May 27.99 26.41
June 29.00 27.68
July 29.38 28.13
August 28.89 27.97
September 28.75 27.49
October 27.78 26.35
November 25.98 23.59
December 24.25 20.30
     
Annual Sum or Average 26.81 24.51
Minimum of Months 23.98 19.42
Maximum of Months 29.38 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.39 19.42
February 24.48 20.87
March 24.83 21.57
April 26.32 24.11
May 27.30 26.41
June 28.00 27.68
July 28.34 28.13
August 28.07 27.97
September 28.19 27.49
October 27.56 26.35
November 26.05 23.59
December 24.55 20.30
     
Annual Sum or Average 26.52 24.51
Minimum of Months 24.39 19.42
Maximum of Months 28.34 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.32 19.42
February 23.47 20.87
March 23.62 21.57
April 23.97 24.11
May 24.13 26.41
June 24.21 27.68
July 24.33 28.13
August 24.24 27.97
September 24.21 27.49
October 24.07 26.35
November 23.78 23.59
December 23.43 20.30
     
Annual Sum or Average 23.90 24.51
Minimum of Months 23.32 19.42
Maximum of Months 24.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.36 19.42
February 23.66 20.87
March 24.04 21.57
April 25.54 24.11
May 26.56 26.41
June 27.15 27.68
July 27.45 28.13
August 27.24 27.97
September 27.32 27.49
October 26.72 26.35
November 25.22 23.59
December 23.65 20.30
     
Annual Sum or Average 25.67 24.51
Minimum of Months 23.36 19.42
Maximum of Months 27.45 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 19.42
February 21.72 20.87
March 21.70 21.57
April 21.76 24.11
May 21.77 26.41
June 21.78 27.68
July 21.80 28.13
August 21.79 27.97
September 21.78 27.49
October 21.76 26.35
November 21.75 23.59
December 21.70 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.70 19.42
Maximum of Months 21.80 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.51 19.42
February 22.76 20.87
March 22.93 21.57
April 23.30 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.13 23.59
December 22.65 20.30
     
Annual Sum or Average 23.11 24.51
Minimum of Months 22.51 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.50 19.42
February 22.75 20.87
March 22.93 21.57
April 23.29 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.12 23.59
December 22.65 20.30
     
Annual Sum or Average 23.10 24.51
Minimum of Months 22.50 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 19.42
February 21.75 20.87
March 21.74 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.75 23.59
December 21.74 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.74 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.61 19.42
February 22.80 20.87
March 22.95 21.57
April 23.30 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.14 23.59
December 22.72 20.30
     
Annual Sum or Average 23.13 24.51
Minimum of Months 22.61 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.82 19.42
February 22.93 20.87
March 23.06 21.57
April 23.31 24.11
May 23.33 26.41
June 23.33 27.68
July 23.33 28.13
August 23.33 27.97
September 23.33 27.49
October 23.33 26.35
November 23.19 23.59
December 22.87 20.30
     
Annual Sum or Average 23.18 24.51
Minimum of Months 22.82 19.42
Maximum of Months 23.33 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.78 19.42
February 24.00 20.87
March 24.31 21.57
April 25.00 24.11
May 25.45 26.41
June 25.68 27.68
July 25.82 28.13
August 25.62 27.97
September 25.58 27.49
October 25.22 26.35
November 24.56 23.59
December 23.87 20.30
     
Annual Sum or Average 24.91 24.51
Minimum of Months 23.78 19.42
Maximum of Months 25.82 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.76 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.76 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.75 20.87
March 21.75 21.57
April 21.76 24.11
May 21.76 26.41
June 21.76 27.68
July 21.77 28.13
August 21.76 27.97
September 21.76 27.49
October 21.76 26.35
November 21.76 23.59
December 21.75 20.30
     
Annual Sum or Average 21.76 24.51
Minimum of Months 21.75 19.42
Maximum of Months 21.77 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.87 19.42
February 24.17 20.87
March 24.65 21.57
April 25.90 24.11
May 26.75 26.41
June 27.31 27.68
July 27.57 28.13
August 27.17 27.97
September 27.09 27.49
October 26.42 26.35
November 25.25 23.59
December 24.04 20.30
     
Annual Sum or Average 25.86 24.51
Minimum of Months 23.87 19.42
Maximum of Months 27.57 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2015-09-14 08:44:56

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.76 19.42
February 24.08 20.87
March 24.70 21.57
April 26.72 24.11
May 28.18 26.41
June 29.23 27.68
July 29.68 28.13
August 29.09 27.97
September 28.94 27.49
October 27.86 26.35
November 25.95 23.59
December 24.07 20.30
     
Annual Sum or Average 26.87 24.51
Minimum of Months 23.76 19.42
Maximum of Months 29.68 28.13



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:56

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.172900E+12 108473.734 07-JAN-08:00 25182.171 43578.554 9870.871 0.000 29834.026 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.161403E+12 111467.270 11-FEB-08:00 25182.171 43578.554 9870.871 0.000 32827.562 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.184020E+12 111411.719 04-MAR-08:00 25182.171 43578.554 9870.871 0.000 32772.010 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.189080E+12 114187.452 14-APR-07:00 25182.171 43578.554 9870.871 0.000 35547.743 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.209983E+12 117442.720 20-MAY-07:00 25182.171 43578.554 9870.871 0.000 38803.011 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.211944E+12 122252.499 09-JUN-07:00 25182.171 43578.554 9870.871 0.000 43612.791 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.222104E+12 121914.753 14-JUL-07:00 25182.171 43578.554 9870.871 0.000 43275.045 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.220442E+12 123087.848 05-AUG-07:00 25182.171 43578.554 9870.871 0.000 44448.140 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.210957E+12 119797.893 09-SEP-07:00 25182.171 43578.554 9870.871 0.000 41158.184 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.208636E+12 118269.906 13-OCT-07:00 25182.171 43578.554 9870.871 0.000 39630.197 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.187281E+12 114978.361 10-NOV-08:00 25182.171 43578.554 9870.871 0.000 36338.653 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.178292E+12 114382.068 09-DEC-08:00 25182.171 43578.554 9870.871 0.000 35742.359 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.235704E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.161403E+12 108473.734   25182.171 43578.554 9870.871 0.000 29834.026 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.222104E+12 123087.848   25182.171 43578.554 9870.871 0.000 44448.140 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:56

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.763760E+11 81807.200 27-JAN-09:15 0.000 40096.028 0.000 41711.172 41711.172 41711.172 0.000
February 0.687204E+11 81884.843 11-FEB-09:15 0.000 40096.028 0.000 41788.815 41788.815 41788.815 0.000
March 0.749652E+11 81404.557 17-MAR-08:15 0.000 40096.028 0.000 41308.529 41308.529 41308.529 0.000
April 0.709347E+11 80835.269 14-APR-08:15 0.000 40096.028 0.000 40739.241 40739.241 40739.241 0.000
May 0.716521E+11 80463.199 05-MAY-08:15 0.000 40096.028 0.000 40367.170 40367.170 40367.170 0.000
June 0.680737E+11 80009.707 03-JUN-08:15 0.000 40096.028 0.000 39913.679 39913.679 39913.679 0.000
July 0.697947E+11 79695.886 21-JUL-08:15 0.000 40096.028 0.000 39599.858 39599.858 39599.858 0.000
August 0.701708E+11 79685.217 04-AUG-08:15 0.000 40096.028 0.000 39589.189 39589.189 39589.189 0.000
September 0.689523E+11 80372.826 22-SEP-08:15 0.000 40096.028 0.000 40276.798 40276.798 40276.798 0.000
October 0.729051E+11 80554.583 13-OCT-08:15 0.000 40096.028 0.000 40458.555 40458.555 40458.555 0.000
November 0.721569E+11 81309.058 25-NOV-09:15 0.000 40096.028 0.000 41213.030 41213.030 41213.030 0.000
December 0.759063E+11 81928.324 29-DEC-09:15 0.000 40096.028 0.000 41832.296 41832.296 41832.296 0.000
                     
Annual Sum or Average 0.860608E+12         0.000        
Minimum of Months 0.680737E+11 79685.217   0.000 40096.028 0.000 39589.189 39589.189 39589.189 0.000
Maximum of Months 0.763760E+11 81928.324   0.000 40096.028 0.000 41832.296 41832.296 41832.296 0.000