Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Boise Air Terminal Uo ID USA TMY3 WMO#=726810

Simulation Timestamp: 2015-09-14 08:44:23


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3061.62 762.82 821.89
Net Site Energy 3061.62 762.82 821.89
Total Source Energy 7407.83 1845.69 1988.63
Net Source Energy 7407.83 1845.69 1988.63


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 149.02 47.44 0.00 0.00 0.00 0.00
Cooling 262.45 0.00 0.00 0.00 0.00 0.00
Interior Lighting 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.71 0.00 0.00 0.00 0.00 0.00
Interior Equipment 601.95 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 305.55 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 629.65 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1963.05 1098.58 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 149.02 47.44 0.00 0.00 0.00 0.00
Cooling General 262.45 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.71 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 573.47 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 305.55 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 629.65 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 172.84 0.00 0.00 0.00 0.00 0.00
HVAC 192.55 181.76 0.00 0.00 0.00 0.69
Other 161.59 113.15 0.00 0.00 0.00 0.00
Total 526.98 294.91 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.41 0.00 0.00 0.00 0.00 0.00
HVAC 178.71 168.70 0.00 0.00 0.00 0.64
Other 149.98 105.02 0.00 0.00 0.00 0.00
Total 489.10 273.71 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1963.05 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1963.05 100.00
     
Total On-Site and Utility Electric Sources 1963.05 100.00
Total Electricity End Uses 1963.05 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 186.00
Time Setpoint Not Met During Occupied Cooling 3732.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 5414.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
RunPeriod Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Weather File Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Latitude [deg] 43.62
Longitude [deg] -116.2
Elevation [m] 701.00
Time Zone -7.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Window Opening Area [m2] 184.20 8.38 72.38 6.62 96.82
Window-Wall Ratio [%] 10.87 3.95 11.39 3.13 15.24


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Window Opening Area [m2] 179.26 8.38 67.45 6.62 96.82
Window-Wall Ratio [%] 12.01 3.95 12.11 5.68 15.95


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 8.3610   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 6.9675   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 11.1480   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 15.3285 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 12.5415 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 18.1154 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 20.9024   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 16.7220 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 8.3610 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2155.0206
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 12.5415 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 15.3285 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 8.3610   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 11.1480   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
Total 4013.58     11621.73   1694.58 184.20 11.2819 15.53 28.2097
Conditioned Total 3725.09     10741.65   1492.32 179.26 11.5457 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 7.8766 26.23 260.8031
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 2.30 120.00
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 36.70 16.70 17.90 Wetbulb [C] 4.20 330.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 0.00 90.00 N
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 90.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 270.00 90.00 W
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 270.00 90.00 W
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 90.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 270.00 90.00 W
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 90.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 90.00 90.00 E
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 90.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 90.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 90.00 90.00 E
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 90.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 90.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 90.00 90.00 E
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 0.00 90.00 N
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 270.00 90.00 W
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 270.00 90.00 W
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 90.00 90.00 E
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 0.00 90.00 N
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 270.00 90.00 W
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 270.00 90.00 W
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 90.00 90.00 E
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 0.00 90.00 N
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 270.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 270.00 90.00 W
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 270.00 90.00 W
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 270.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 270.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 90.00 90.00 E
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 270.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 180.00 90.00 S
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 0.00 90.00 N
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 270.00 90.00 W
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 270.00 90.00 W
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 270.00 90.00 W
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 90.00 90.00 E
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 90.00 90.00 E
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 180.00 90.00 S
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 0.00 90.00 N
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 270.00 90.00 W
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 90.00 90.00 E
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 180.00 90.00 S
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 0.00 90.00 N
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 270.00 90.00 W
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 90.00 90.00 E
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 180.00 90.00 S
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 0.00 90.00 N
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 270.00 90.00 W
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 90.00 90.00 E
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           8.38 2.653 0.426 0.308              
Non-North Total or Average           175.82 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7111.00 5666.28 1444.72 0.80 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   20111.54 15502.76 4608.79 0.77 3.50    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   9777.16 7225.59 2551.57 0.74 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   14236.72 11284.15 2952.57 0.79 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6779.3 3.16 10.77 11.40 10.55
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 19239.9 2.91 9.92 10.52 9.90
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 9392.9 3.26 11.12 11.78 11.07
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13580.3 3.16 10.79 11.42 10.59
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.60 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   40752.70 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1008.89 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1008.89 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1323.23 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1204.34 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1008.82 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.53 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.60 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   2881.58 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1008.89 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   4035.57 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3198.33 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4035.57 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1398.82 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1283.94 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4035.29 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1008.82 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4035.29 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1191.80 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.53 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.60 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   3445.19 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1008.89 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   4035.57 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3198.33 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   4035.57 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1086.05 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1420.58 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   4035.29 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1008.82 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4035.29 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1008.82 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.53 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   295.60 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   4929.64 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1729.02 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   4189.58 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   3399.06 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   5053.39 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   1493.02 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1329.33 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   4992.32 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1415.27 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   4844.58 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1668.36 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   457.80 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   4154.18 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   17412.14 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   9324.07 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   7032.57 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.54 622.50 0.43 496.20 1160.84 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.55 622.50 1.12 1280.36 1140.11 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.54 622.50 0.49 574.44 1160.84 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.55 622.50 0.85 964.41 1140.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.51 0.27
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 10442.08 12530.49 0.936 1.123 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.69 0.00627
RESTROOMFLR1 712.34 854.81 0.064 0.077 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 30.81 0.00627
MEETINGROOMFLR1 4598.22 5517.86 0.412 0.495 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.69 0.00627
GUESTROOM101 598.17 717.80 0.057 0.068 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM102 462.28 554.73 0.044 0.053 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM103 1585.20 1902.24 0.197 0.237 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM104 1434.61 1721.53 0.179 0.214 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM105 1871.76 2246.12 0.233 0.280 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.86 0.00627
EMPLOYEELOUNGEFLR1 5806.36 6967.63 0.520 0.624 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
EXERCISECENTERFLR1 1348.16 1617.79 0.121 0.145 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 09:15:00 28.22 0.00627
FRONTOFFICEFLR1 3977.68 4773.22 0.356 0.427 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM201 933.76 1120.51 0.089 0.106 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.69 0.00627
GUESTROOM202_205 6213.34 7456.00 0.774 0.928 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM206_208 5104.82 6125.78 0.636 0.763 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM209_212 5807.07 6968.49 0.723 0.868 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM213 1704.61 2045.54 0.212 0.255 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM214 1676.22 2011.46 0.209 0.250 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM215_218 9045.19 10854.22 0.858 1.030 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM219 5833.62 7000.35 0.726 0.872 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM220_223 5610.70 6732.84 0.699 0.838 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM224 1678.14 2013.77 0.209 0.251 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM301 802.51 963.02 0.076 0.091 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 33.11 0.00627
GUESTROOM302_305 2221.96 2666.36 0.211 0.253 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM306_308 2017.50 2421.01 0.191 0.230 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM309_312 5834.88 7001.86 0.727 0.872 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM313 765.04 918.05 0.073 0.087 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 32.07 0.00627
GUESTROOM314 1605.33 1926.39 0.200 0.240 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 33.69 0.00627
GUESTROOM315_318 6310.62 7572.74 0.786 0.943 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM319 937.25 1124.70 0.089 0.107 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM320_323 5444.81 6533.78 0.678 0.814 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM324 614.05 736.86 0.058 0.070 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 33.28 0.00627
GUESTROOM401 2192.14 2630.57 0.273 0.328 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 33.94 0.00627
GUESTROOM402_405 3310.89 3973.07 0.314 0.377 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 33.94 0.00627
GUESTROOM406_408 2989.11 3586.93 0.284 0.340 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.53 0.00627
GUESTROOM409_412 7179.63 8615.55 0.894 1.073 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 33.94 0.00627
GUESTROOM413 1156.28 1387.54 0.110 0.132 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.53 0.00627
GUESTROOM414 934.02 1120.83 0.089 0.106 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 36.45 0.00627
GUESTROOM415_418 6788.49 8146.19 0.845 1.014 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 34.11 0.00627
GUESTROOM419 1866.99 2240.39 0.232 0.279 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 34.53 0.00627
GUESTROOM420_423 6640.53 7968.63 0.827 0.992 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 11:45:00 34.11 0.00627
GUESTROOM424 1906.43 2287.71 0.237 0.285 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 34.53 0.00627
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
CORRIDORFLR1 19436.18 23323.42 1.740 2.088 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.69 0.00627
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
CORRIDORFLR2 3142.42 3770.90 0.281 0.338 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 34.36 0.00627
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
CORRIDORFLR3 1872.77 2247.33 0.168 0.201 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 33.53 0.00627
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627
CORRIDORFLR4 3035.67 3642.80 0.272 0.326 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 36.20 0.00627
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB   36.70 0.00627


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1865.27 2238.33 0.057 0.236 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 07:30:00 -16.30 0.00098
RESTROOMFLR1 57.69 69.22 0.002 0.002 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 07:45:00 -16.30 0.00098
MEETINGROOMFLR1 653.62 784.34 0.020 0.126 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 07:00:00 -16.30 0.00098
GUESTROOM101 26.98 32.37 0.001 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 07:45:00 -16.30 0.00098
GUESTROOM102 59.13 70.95 0.002 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 07:30:00 -16.30 0.00098
GUESTROOM103 628.29 753.94 0.019 0.023 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 07:45:00 -16.30 0.00098
GUESTROOM104 529.25 635.10 0.016 0.019 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -16.30 0.00098
GUESTROOM105 352.86 423.43 0.011 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 08:30:00 -16.30 0.00098
EMPLOYEELOUNGEFLR1 331.85 398.22 0.010 0.051 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -16.30 0.00098
EXERCISECENTERFLR1 193.07 231.69 0.006 0.043 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 06:00:00 -16.30 0.00098
FRONTOFFICEFLR1 1152.26 1382.71 0.035 0.056 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -16.30 0.00098
GUESTROOM201 295.94 355.13 0.008 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 -16.30 0.00098
GUESTROOM202_205 1367.86 1641.43 0.042 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 10:45:00 -16.30 0.00098
GUESTROOM206_208 1024.47 1229.36 0.031 0.043 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -16.30 0.00098
GUESTROOM209_212 1104.55 1325.45 0.034 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -16.30 0.00098
GUESTROOM213 691.28 829.54 0.021 0.025 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 -16.30 0.00098
GUESTROOM214 595.58 714.70 0.018 0.022 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 10:15:00 -16.30 0.00098
GUESTROOM215_218 269.22 323.07 0.008 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -16.30 0.00098
GUESTROOM219 321.10 385.32 0.010 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -16.30 0.00098
GUESTROOM220_223 975.15 1170.17 0.030 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -16.30 0.00098
GUESTROOM224 518.80 622.55 0.016 0.019 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -16.30 0.00098
GUESTROOM301 381.18 457.41 0.011 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 17:30:00 -16.30 0.00098
GUESTROOM302_305 710.69 852.83 0.020 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 17:15:00 -16.30 0.00098
GUESTROOM306_308 567.78 681.34 0.016 0.043 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:15:00 -16.30 0.00098
GUESTROOM309_312 1350.03 1620.03 0.041 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -16.30 0.00098
GUESTROOM313 458.81 550.58 0.013 0.016 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 21:15:00 -16.30 0.00098
GUESTROOM314 709.44 851.33 0.022 0.026 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:15:00 -16.30 0.00098
GUESTROOM315_318 1427.60 1713.12 0.044 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:00:00 -16.30 0.00098
GUESTROOM319 92.97 111.56 0.003 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:15:00 -16.30 0.00098
GUESTROOM320_323 1228.16 1473.80 0.038 0.054 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:00:00 -16.30 0.00098
GUESTROOM324 257.59 309.11 0.007 0.013 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -16.30 0.00098
GUESTROOM401 966.45 1159.74 0.030 0.036 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 21:45:00 -16.30 0.00098
GUESTROOM402_405 1706.40 2047.69 0.049 0.058 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 21:15:00 -16.30 0.00098
GUESTROOM406_408 1417.94 1701.53 0.040 0.048 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -16.30 0.00098
GUESTROOM409_412 2313.54 2776.24 0.071 0.085 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 19:15:00 -16.30 0.00098
GUESTROOM413 797.95 957.54 0.023 0.027 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -16.30 0.00098
GUESTROOM414 661.58 793.89 0.019 0.023 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 20:15:00 -16.30 0.00098
GUESTROOM415_418 2262.78 2715.33 0.069 0.083 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 17:15:00 -16.30 0.00098
GUESTROOM419 705.02 846.02 0.022 0.026 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 18:00:00 -16.30 0.00098
GUESTROOM420_423 2139.66 2567.59 0.066 0.079 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -16.30 0.00098
GUESTROOM424 915.93 1099.11 0.028 0.034 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 23:15:00 -16.30 0.00098
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
CORRIDORFLR1 32319.75 38783.70 0.989 1.187 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -16.30 0.00098
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
CORRIDORFLR2 1055.93 1267.12 0.032 0.039 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 09:45:00 -16.30 0.00098
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
CORRIDORFLR3 1525.59 1830.70 0.047 0.056 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -16.30 0.00098
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB   -16.30 0.00098
CORRIDORFLR4 2762.64 3315.17 0.085 0.102 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -16.30 0.00098
FRONTSTAIRSFLR4 153.93 184.72 0.003 0.006 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -16.30 0.00098


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.43 0.43 0.06 0.06
SAC_FRONTLOUNGE 1.12 1.12 0.24 0.24
SAC_MEETINGROOM 0.49 0.49 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.85 0.85 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 1.12 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 1036.50 6880.50 445.00
RESTROOMFLR1 174.25 7407.50 21.25
MEETINGROOMFLR1 786.50 2723.75 2.75
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 922.50 8760.00 922.50
GUESTROOM104 280.75 8760.00 280.75
GUESTROOM105 0.50 8542.00 0.50
EMPLOYEELOUNGEFLR1 2991.50 2121.25 226.00
EXERCISECENTERFLR1 1102.00 2910.00 4.50
FRONTOFFICEFLR1 675.50 6284.00 71.75
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 315.75 8655.25 315.75
GUESTROOM206_208 218.00 8637.75 218.00
GUESTROOM209_212 159.50 8722.75 159.50
GUESTROOM213 1013.00 8744.75 1013.00
GUESTROOM214 214.25 8479.00 214.25
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 3863.75 4248.75 514.75
GUESTROOM220_223 36.50 8301.00 36.50
GUESTROOM224 250.50 8432.75 250.50
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 330.50 8722.25 330.50
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 720.50 8479.25 720.50
GUESTROOM315_318 42.50 8190.00 42.50
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 171.00 8437.50 171.00
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 3081.00 8337.00 3045.25
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1270.25 8016.25 1129.50
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 1058.75 7670.00 646.50
GUESTROOM419 947.00 7851.00 785.00
GUESTROOM420_423 1119.00 7703.50 732.75
GUESTROOM424 1901.25 7940.50 1721.75
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 6853.25 8760.00 5414.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 35.75 880.25 35.75 880.25
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 3.75 23.75 3.75 23.75
GUESTROOM104 1.25 24.00 1.25 24.00
GUESTROOM105 0.00 35.25 0.00 35.25
EMPLOYEELOUNGEFLR1 195.25 1285.75 162.00 822.50
EXERCISECENTERFLR1 0.50 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.50 0.00 0.00 0.00
GUESTROOM202_205 0.25 11.50 0.25 11.50
GUESTROOM206_208 0.25 22.00 0.25 22.00
GUESTROOM209_212 0.25 10.00 0.25 10.00
GUESTROOM213 4.00 12.00 4.00 12.00
GUESTROOM214 1.50 14.25 1.50 14.25
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 2524.50 0.00 2524.50
GUESTROOM220_223 0.00 10.25 0.00 10.25
GUESTROOM224 1.75 14.00 1.75 14.00
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.25 0.00 0.00 0.00
GUESTROOM309_312 1.50 10.25 1.50 10.25
GUESTROOM313 0.50 0.00 0.00 0.00
GUESTROOM314 3.75 13.75 3.75 13.75
GUESTROOM315_318 0.00 12.00 0.00 12.00
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 1.00 8.50 1.00 8.50
GUESTROOM324 0.25 0.00 0.00 0.00
GUESTROOM401 6.25 37.75 6.25 37.75
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 4.50 26.75 4.50 26.75
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 3.75 20.25 3.75 20.25
GUESTROOM419 3.50 25.50 3.50 25.50
GUESTROOM420_423 4.75 19.50 4.75 19.50
GUESTROOM424 5.50 24.25 5.50 24.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 1.00 2721.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 226.25 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.25 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 332.25 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 214.75 4601.75 186.00 3732.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:23

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.427446
SAC_FRONTLOUNGE SUPPLY FAN 1.12
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.845896


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 295.60
CORRIDORFLR1 PTAC HEATING COIL 40752.70
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1008.89
102 PTAC HEATING COIL 1008.89
103 PTAC HEATING COIL 1323.23
104 PTAC HEATING COIL 1204.34
105 PTAC HEATING COIL 1008.82
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 295.53
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 295.60
CORRIDORFLR2 PTAC HEATING COIL 2881.58
201 PTAC HEATING COIL 1008.89
202_205 PTAC HEATING COIL 4035.57
206_208 PTAC HEATING COIL 3198.33
209_212 PTAC HEATING COIL 4035.57
213 PTAC HEATING COIL 1398.82
214 PTAC HEATING COIL 1283.94
215_218 PTAC HEATING COIL 4035.29
219 PTAC HEATING COIL 1008.82
220_223 PTAC HEATING COIL 4035.29
224 PTAC HEATING COIL 1191.80
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 295.53
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 295.60
CORRIDORFLR3 PTAC HEATING COIL 3445.19
301 PTAC HEATING COIL 1008.89
302_305 PTAC HEATING COIL 4035.57
306_308 PTAC HEATING COIL 3198.33
309_312 PTAC HEATING COIL 4035.57
313 PTAC HEATING COIL 1086.05
314 PTAC HEATING COIL 1420.58
315_318 PTAC HEATING COIL 4035.29
319 PTAC HEATING COIL 1008.82
320_323 PTAC HEATING COIL 4035.29
324 PTAC HEATING COIL 1008.82
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 295.53
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 295.60
CORRIDORFLR4 PTAC HEATING COIL 4929.64
401 PTAC HEATING COIL 1729.02
402_405 PTAC HEATING COIL 4189.58
406_408 PTAC HEATING COIL 3399.06
409_412 PTAC HEATING COIL 5053.39
413 PTAC HEATING COIL 1493.02
414 PTAC HEATING COIL 1329.33
415_418 PTAC HEATING COIL 4992.32
419 PTAC HEATING COIL 1415.27
420_423 PTAC HEATING COIL 4844.58
424 PTAC HEATING COIL 1668.36
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 457.80


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.796833 0.427446 7111.00
SAC_FRONTLOUNGE COOLING COIL 0.770839 1.12 20111.54
SAC_MEETINGROOM COOLING COIL 0.739028 0.494846 9777.16
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.792609 0.845896 14236.72


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 1.12
RESTROOMFLR1 DIRECT AIR 0.076543
MEETINGROOMFLR1 DIRECT AIR 0.494846
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.624422
EXERCISECENTERFLR1 DIRECT AIR 0.144932
FRONTOFFICEFLR1 DIRECT AIR 0.427446


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.427446
SAC_FRONTLOUNGE MAIN BRANCH 1.12
SAC_MEETINGROOM MAIN BRANCH 0.494846
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.845896


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.427446
SAC_FRONTLOUNGE 1.12
SAC_MEETINGROOM 0.494846
SAC_EXC_EMPLGE_RESTRM 0.845896


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.427446 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 1.12 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.494846 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.845896 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.427446 0.427446 0.427446 0.427446 4154.18 7111.00 1.00
SAC_FRONTLOUNGE 1.12 1.12 1.12 1.12 17412.14 20111.54 1.00
SAC_MEETINGROOM 0.494846 0.494846 0.494846 0.494846 9324.07 9777.16 1.00
SAC_EXC_EMPLGE_RESTRM 0.845896 0.845896 0.845896 0.845896 7032.57 14236.72 0.171335


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 4154.18
SAC_FRONTLOUNGE HEATING COIL 17412.14
SAC_MEETINGROOM HEATING COIL 9324.07
SAC_EXC_EMPLGE_RESTRM HEATING COIL 7032.57


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.494846


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.42 -1.7
February 18.66 2.70
March 19.46 6.07
April 21.14 11.58
May 22.30 14.61
June 23.72 19.78
July 25.28 24.54
August 24.31 21.22
September 23.31 17.37
October 21.61 11.70
November 19.36 4.05
December 18.18 1.86
     
Annual Sum or Average 21.24 11.20
Minimum of Months 17.42 -1.7
Maximum of Months 25.28 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.88 -1.7
February 22.60 2.70
March 23.10 6.07
April 23.91 11.58
May 24.38 14.61
June 25.41 19.78
July 26.37 24.54
August 25.75 21.22
September 24.87 17.37
October 23.89 11.70
November 22.79 4.05
December 22.36 1.86
     
Annual Sum or Average 23.95 11.20
Minimum of Months 21.88 -1.7
Maximum of Months 26.37 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.52 -1.7
February 17.74 2.70
March 18.54 6.07
April 20.30 11.58
May 21.48 14.61
June 22.95 19.78
July 24.52 24.54
August 23.58 21.22
September 22.53 17.37
October 20.75 11.70
November 18.43 4.05
December 17.26 1.86
     
Annual Sum or Average 20.40 11.20
Minimum of Months 16.52 -1.7
Maximum of Months 24.52 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -1.7
February 21.16 2.70
March 21.39 6.07
April 22.24 11.58
May 22.72 14.61
June 23.32 19.78
July 23.72 24.54
August 23.44 21.22
September 23.11 17.37
October 22.13 11.70
November 21.35 4.05
December 21.13 1.86
     
Annual Sum or Average 22.24 11.20
Minimum of Months 21.11 -1.7
Maximum of Months 23.72 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 -1.7
February 22.17 2.70
March 22.41 6.07
April 22.92 11.58
May 23.22 14.61
June 23.48 19.78
July 23.68 24.54
August 23.59 21.22
September 23.41 17.37
October 22.97 11.70
November 22.34 4.05
December 22.07 1.86
     
Annual Sum or Average 22.85 11.20
Minimum of Months 21.85 -1.7
Maximum of Months 23.68 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.40 -1.7
February 21.93 2.70
March 22.46 6.07
April 23.27 11.58
May 23.60 14.61
June 23.79 19.78
July 23.88 24.54
August 23.84 21.22
September 23.74 17.37
October 23.29 11.70
November 22.17 4.05
December 21.66 1.86
     
Annual Sum or Average 22.92 11.20
Minimum of Months 21.40 -1.7
Maximum of Months 23.88 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.97 -1.7
February 24.53 2.70
March 24.96 6.07
April 25.75 11.58
May 26.16 14.61
June 26.66 19.78
July 27.03 24.54
August 26.83 21.22
September 26.45 17.37
October 25.77 11.70
November 24.75 4.05
December 24.27 1.86
     
Annual Sum or Average 25.60 11.20
Minimum of Months 23.97 -1.7
Maximum of Months 27.03 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.19 -1.7
February 19.87 2.70
March 20.63 6.07
April 21.92 11.58
May 22.49 14.61
June 23.00 19.78
July 23.27 24.54
August 23.12 21.22
September 22.86 17.37
October 21.92 11.70
November 20.22 4.05
December 19.57 1.86
     
Annual Sum or Average 21.51 11.20
Minimum of Months 19.19 -1.7
Maximum of Months 23.27 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.01 -1.7
February 19.54 2.70
March 20.26 6.07
April 21.60 11.58
May 22.21 14.61
June 22.83 19.78
July 23.20 24.54
August 22.98 21.22
September 22.63 17.37
October 21.57 11.70
November 19.89 4.05
December 19.29 1.86
     
Annual Sum or Average 21.26 11.20
Minimum of Months 19.01 -1.7
Maximum of Months 23.20 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.62 -1.7
February 20.87 2.70
March 21.05 6.07
April 21.44 11.58
May 21.61 14.61
June 21.70 19.78
July 21.75 24.54
August 21.73 21.22
September 21.69 17.37
October 21.45 11.70
November 21.01 4.05
December 20.77 1.86
     
Annual Sum or Average 21.31 11.20
Minimum of Months 20.62 -1.7
Maximum of Months 21.75 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 -1.7
February 21.12 2.70
March 21.35 6.07
April 21.64 11.58
May 21.71 14.61
June 21.75 19.78
July 21.75 24.54
August 21.75 21.22
September 21.74 17.37
October 21.63 11.70
November 21.23 4.05
December 20.99 1.86
     
Annual Sum or Average 21.46 11.20
Minimum of Months 20.81 -1.7
Maximum of Months 21.75 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.26 -1.7
February 21.52 2.70
March 21.64 6.07
April 21.74 11.58
May 21.75 14.61
June 21.75 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.73 11.70
November 21.56 4.05
December 21.42 1.86
     
Annual Sum or Average 21.64 11.20
Minimum of Months 21.26 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.43 -1.7
February 22.54 2.70
March 22.59 6.07
April 22.69 11.58
May 22.74 14.61
June 22.53 19.78
July 22.31 24.54
August 22.48 21.22
September 22.70 17.37
October 22.79 11.70
November 22.63 4.05
December 22.58 1.86
     
Annual Sum or Average 22.58 11.20
Minimum of Months 22.31 -1.7
Maximum of Months 22.79 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 50.51 -1.7
February 51.02 2.70
March 51.44 6.07
April 52.12 11.58
May 52.57 14.61
June 53.13 19.78
July 53.65 24.54
August 53.29 21.22
September 52.84 17.37
October 52.17 11.70
November 51.23 4.05
December 50.78 1.86
     
Annual Sum or Average 52.07 11.20
Minimum of Months 50.51 -1.7
Maximum of Months 53.65 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 68.59 -1.7
February 69.12 2.70
March 69.49 6.07
April 70.22 11.58
May 70.87 14.61
June 71.44 19.78
July 72.19 24.54
August 71.71 21.22
September 71.22 17.37
October 70.45 11.70
November 69.46 4.05
December 68.85 1.86
     
Annual Sum or Average 70.31 11.20
Minimum of Months 68.59 -1.7
Maximum of Months 72.19 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.72 -1.7
February 22.99 2.70
March 23.20 6.07
April 23.56 11.58
May 23.74 14.61
June 23.84 19.78
July 23.89 24.54
August 23.86 21.22
September 23.83 17.37
October 23.61 11.70
November 23.13 4.05
December 22.94 1.86
     
Annual Sum or Average 23.44 11.20
Minimum of Months 22.72 -1.7
Maximum of Months 23.89 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.93 -1.7
February 22.49 2.70
March 23.00 6.07
April 23.57 11.58
May 23.80 14.61
June 23.86 19.78
July 23.89 24.54
August 23.88 21.22
September 23.86 17.37
October 23.64 11.70
November 22.73 4.05
December 22.27 1.86
     
Annual Sum or Average 23.25 11.20
Minimum of Months 21.93 -1.7
Maximum of Months 23.89 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.50 -1.7
February 17.82 2.70
March 18.79 6.07
April 20.81 11.58
May 22.31 14.61
June 24.09 19.78
July 25.89 24.54
August 24.60 21.22
September 23.18 17.37
October 21.16 11.70
November 18.68 4.05
December 17.36 1.86
     
Annual Sum or Average 20.95 11.20
Minimum of Months 16.50 -1.7
Maximum of Months 25.89 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.58 -1.7
February 20.50 2.70
March 21.22 6.07
April 22.54 11.58
May 23.40 14.61
June 24.41 19.78
July 25.37 24.54
August 24.72 21.22
September 23.91 17.37
October 22.72 11.70
November 21.03 4.05
December 20.15 1.86
     
Annual Sum or Average 22.47 11.20
Minimum of Months 19.58 -1.7
Maximum of Months 25.37 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.63 -1.7
February 18.24 2.70
March 19.27 6.07
April 21.45 11.58
May 22.87 14.61
June 24.57 19.78
July 26.43 24.54
August 25.22 21.22
September 24.03 17.37
October 21.95 11.70
November 19.08 4.05
December 17.62 1.86
     
Annual Sum or Average 21.46 11.20
Minimum of Months 16.63 -1.7
Maximum of Months 26.43 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.31 -1.7
February 21.92 2.70
March 22.59 6.07
April 23.52 11.58
May 23.78 14.61
June 23.88 19.78
July 23.98 24.54
August 23.93 21.22
September 23.85 17.37
October 23.55 11.70
November 22.24 4.05
December 21.66 1.86
     
Annual Sum or Average 23.02 11.20
Minimum of Months 21.31 -1.7
Maximum of Months 23.98 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.20 -1.7
February 16.77 2.70
March 17.80 6.07
April 20.17 11.58
May 21.64 14.61
June 23.46 19.78
July 25.36 24.54
August 24.18 21.22
September 22.88 17.37
October 20.62 11.70
November 17.61 4.05
December 16.17 1.86
     
Annual Sum or Average 20.17 11.20
Minimum of Months 15.20 -1.7
Maximum of Months 25.36 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -1.7
February 19.06 2.70
March 19.64 6.07
April 21.52 11.58
May 22.38 14.61
June 23.03 19.78
July 23.31 24.54
August 23.14 21.22
September 22.81 17.37
October 21.27 11.70
November 19.46 4.05
December 18.94 1.86
     
Annual Sum or Average 21.13 11.20
Minimum of Months 18.90 -1.7
Maximum of Months 23.31 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.75 -1.7
February 21.04 2.70
March 21.24 6.07
April 21.62 11.58
May 21.72 14.61
June 21.75 19.78
July 21.76 24.54
August 21.75 21.22
September 21.74 17.37
October 21.59 11.70
November 21.15 4.05
December 20.93 1.86
     
Annual Sum or Average 21.42 11.20
Minimum of Months 20.75 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 -1.7
February 21.12 2.70
March 21.31 6.07
April 21.65 11.58
May 21.73 14.61
June 21.75 19.78
July 21.76 24.54
August 21.75 21.22
September 21.75 17.37
October 21.63 11.70
November 21.22 4.05
December 21.00 1.86
     
Annual Sum or Average 21.46 11.20
Minimum of Months 20.81 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.83 -1.7
February 21.15 2.70
March 21.34 6.07
April 21.64 11.58
May 21.73 14.61
June 21.75 19.78
July 21.75 24.54
August 21.75 21.22
September 21.74 17.37
October 21.63 11.70
November 21.25 4.05
December 21.03 1.86
     
Annual Sum or Average 21.47 11.20
Minimum of Months 20.83 -1.7
Maximum of Months 21.75 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.58 -1.7
February 20.85 2.70
March 21.06 6.07
April 21.51 11.58
May 21.66 14.61
June 21.73 19.78
July 21.75 24.54
August 21.75 21.22
September 21.72 17.37
October 21.49 11.70
November 20.99 4.05
December 20.74 1.86
     
Annual Sum or Average 21.32 11.20
Minimum of Months 20.58 -1.7
Maximum of Months 21.75 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.85 -1.7
February 21.20 2.70
March 21.45 6.07
April 21.71 11.58
May 21.74 14.61
June 21.75 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.70 11.70
November 21.30 4.05
December 21.05 1.86
     
Annual Sum or Average 21.50 11.20
Minimum of Months 20.85 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.62 -1.7
February 23.05 2.70
March 23.22 6.07
April 23.32 11.58
May 23.33 14.61
June 23.33 19.78
July 23.33 24.54
August 23.33 21.22
September 23.33 17.37
October 23.32 11.70
November 23.10 4.05
December 22.96 1.86
     
Annual Sum or Average 23.19 11.20
Minimum of Months 22.62 -1.7
Maximum of Months 23.33 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 30.14 -1.7
February 30.75 2.70
March 31.28 6.07
April 32.29 11.58
May 32.87 14.61
June 33.42 19.78
July 34.01 24.54
August 33.59 21.22
September 33.14 17.37
October 32.35 11.70
November 31.09 4.05
December 30.45 1.86
     
Annual Sum or Average 32.12 11.20
Minimum of Months 30.14 -1.7
Maximum of Months 34.01 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -1.7
February 21.83 2.70
March 21.98 6.07
April 22.35 11.58
May 22.53 14.61
June 22.89 19.78
July 23.29 24.54
August 22.98 21.22
September 22.65 17.37
October 22.29 11.70
November 21.90 4.05
December 21.79 1.86
     
Annual Sum or Average 22.36 11.20
Minimum of Months 21.77 -1.7
Maximum of Months 23.29 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.01 -1.7
February 21.34 2.70
March 21.57 6.07
April 21.74 11.58
May 21.75 14.61
June 21.76 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.73 11.70
November 21.40 4.05
December 21.20 1.86
     
Annual Sum or Average 21.56 11.20
Minimum of Months 21.01 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.83 -1.7
February 21.17 2.70
March 21.44 6.07
April 21.72 11.58
May 21.74 14.61
June 21.76 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.71 11.70
November 21.27 4.05
December 21.02 1.86
     
Annual Sum or Average 21.49 11.20
Minimum of Months 20.83 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.34 -1.7
February 19.56 2.70
March 20.51 6.07
April 22.36 11.58
May 23.46 14.61
June 24.78 19.78
July 26.01 24.54
August 25.11 21.22
September 24.05 17.37
October 22.47 11.70
November 20.21 4.05
December 19.09 1.86
     
Annual Sum or Average 22.18 11.20
Minimum of Months 18.34 -1.7
Maximum of Months 26.01 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.96 -1.7
February 16.77 2.70
March 18.07 6.07
April 20.83 11.58
May 22.74 14.61
June 24.98 19.78
July 27.22 24.54
August 25.54 21.22
September 23.75 17.37
October 21.16 11.70
November 17.83 4.05
December 16.14 1.86
     
Annual Sum or Average 20.85 11.20
Minimum of Months 14.96 -1.7
Maximum of Months 27.22 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.67 -1.7
February 17.38 2.70
March 18.57 6.07
April 21.12 11.58
May 22.74 14.61
June 24.67 19.78
July 26.71 24.54
August 25.35 21.22
September 23.98 17.37
October 21.57 11.70
November 18.29 4.05
December 16.72 1.86
     
Annual Sum or Average 21.08 11.20
Minimum of Months 15.67 -1.7
Maximum of Months 26.71 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -1.7
February 21.14 2.70
March 21.48 6.07
April 22.77 11.58
May 23.34 14.61
June 23.73 19.78
July 23.88 24.54
August 23.80 21.22
September 23.60 17.37
October 22.63 11.70
November 21.42 4.05
December 21.12 1.86
     
Annual Sum or Average 22.51 11.20
Minimum of Months 21.11 -1.7
Maximum of Months 23.88 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.89 -1.7
February 15.56 2.70
March 16.77 6.07
April 19.66 11.58
May 21.41 14.61
June 23.56 19.78
July 25.71 24.54
August 24.33 21.22
September 22.80 17.37
October 20.01 11.70
November 16.47 4.05
December 14.92 1.86
     
Annual Sum or Average 19.61 11.20
Minimum of Months 13.89 -1.7
Maximum of Months 25.71 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -1.7
February 18.91 2.70
March 19.19 6.07
April 21.00 11.58
May 21.98 14.61
June 22.87 19.78
July 23.27 24.54
August 23.01 21.22
September 22.51 17.37
October 20.61 11.70
November 19.14 4.05
December 18.89 1.86
     
Annual Sum or Average 20.87 11.20
Minimum of Months 18.89 -1.7
Maximum of Months 23.27 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -1.7
February 18.98 2.70
March 19.49 6.07
April 21.44 11.58
May 22.30 14.61
June 23.03 19.78
July 23.30 24.54
August 23.13 21.22
September 22.76 17.37
October 21.06 11.70
November 19.30 4.05
December 18.90 1.86
     
Annual Sum or Average 21.06 11.20
Minimum of Months 18.89 -1.7
Maximum of Months 23.30 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -1.7
February 19.05 2.70
March 19.68 6.07
April 21.60 11.58
May 22.39 14.61
June 23.04 19.78
July 23.30 24.54
August 23.14 21.22
September 22.79 17.37
October 21.23 11.70
November 19.39 4.05
December 18.92 1.86
     
Annual Sum or Average 21.13 11.20
Minimum of Months 18.90 -1.7
Maximum of Months 23.30 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.73 -1.7
February 21.04 2.70
March 21.24 6.07
April 21.60 11.58
May 21.71 14.61
June 21.74 19.78
July 21.75 24.54
August 21.75 21.22
September 21.73 17.37
October 21.57 11.70
November 21.15 4.05
December 20.91 1.86
     
Annual Sum or Average 21.41 11.20
Minimum of Months 20.73 -1.7
Maximum of Months 21.75 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -1.7
February 18.97 2.70
March 19.47 6.07
April 21.34 11.58
May 22.20 14.61
June 22.96 19.78
July 23.30 24.54
August 23.11 21.22
September 22.73 17.37
October 21.15 11.70
November 19.37 4.05
December 18.91 1.86
     
Annual Sum or Average 21.04 11.20
Minimum of Months 18.89 -1.7
Maximum of Months 23.30 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.65 -1.7
February 20.98 2.70
March 21.26 6.07
April 21.65 11.58
May 21.72 14.61
June 21.75 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.62 11.70
November 21.10 4.05
December 20.83 1.86
     
Annual Sum or Average 21.40 11.20
Minimum of Months 20.65 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.01 -1.7
February 21.36 2.70
March 21.58 6.07
April 21.74 11.58
May 21.75 14.61
June 21.76 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.73 11.70
November 21.41 4.05
December 21.21 1.86
     
Annual Sum or Average 21.57 11.20
Minimum of Months 21.01 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.56 -1.7
February 22.35 2.70
March 23.08 6.07
April 24.51 11.58
May 25.24 14.61
June 25.96 19.78
July 26.56 24.54
August 26.11 21.22
September 25.56 17.37
October 24.45 11.70
November 22.75 4.05
December 21.97 1.86
     
Annual Sum or Average 24.18 11.20
Minimum of Months 21.56 -1.7
Maximum of Months 26.56 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.93 -1.7
February 21.01 2.70
March 21.96 6.07
April 23.00 11.58
May 23.23 14.61
June 23.31 19.78
July 23.33 24.54
August 23.33 21.22
September 23.29 17.37
October 22.97 11.70
November 21.31 4.05
December 20.57 1.86
     
Annual Sum or Average 22.28 11.20
Minimum of Months 19.93 -1.7
Maximum of Months 23.33 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.85 -1.7
February 21.19 2.70
March 21.45 6.07
April 21.71 11.58
May 21.74 14.61
June 21.75 19.78
July 21.76 24.54
August 21.75 21.22
September 21.75 17.37
October 21.69 11.70
November 21.27 4.05
December 21.04 1.86
     
Annual Sum or Average 21.50 11.20
Minimum of Months 20.85 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.91 -1.7
February 19.25 2.70
March 20.21 6.07
April 22.04 11.58
May 22.69 14.61
June 23.15 19.78
July 23.32 24.54
August 23.21 21.22
September 22.97 17.37
October 21.87 11.70
November 19.78 4.05
December 19.05 1.86
     
Annual Sum or Average 21.38 11.20
Minimum of Months 18.91 -1.7
Maximum of Months 23.32 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.99 -1.7
February 18.35 2.70
March 19.52 6.07
April 21.93 11.58
May 23.29 14.61
June 24.90 19.78
July 26.32 24.54
August 25.24 21.22
September 23.97 17.37
October 21.93 11.70
November 19.10 4.05
December 17.81 1.86
     
Annual Sum or Average 21.63 11.20
Minimum of Months 16.99 -1.7
Maximum of Months 26.32 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.74 -1.7
February 15.73 2.70
March 17.24 6.07
April 20.45 11.58
May 22.61 14.61
June 25.13 19.78
July 27.60 24.54
August 25.71 21.22
September 23.69 17.37
October 20.70 11.70
November 16.88 4.05
December 15.04 1.86
     
Annual Sum or Average 20.40 11.20
Minimum of Months 13.74 -1.7
Maximum of Months 27.60 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.18 -1.7
February 16.05 2.70
March 17.53 6.07
April 20.59 11.58
May 22.49 14.61
June 24.78 19.78
July 27.06 24.54
August 25.45 21.22
September 23.77 17.37
October 20.81 11.70
November 16.96 4.05
December 15.29 1.86
     
Annual Sum or Average 20.44 11.20
Minimum of Months 14.18 -1.7
Maximum of Months 27.06 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -1.7
February 21.14 2.70
March 21.43 6.07
April 22.35 11.58
May 22.84 14.61
June 23.45 19.78
July 23.92 24.54
August 23.56 21.22
September 23.10 17.37
October 22.09 11.70
November 21.26 4.05
December 21.11 1.86
     
Annual Sum or Average 22.29 11.20
Minimum of Months 21.11 -1.7
Maximum of Months 23.92 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.83 -1.7
February 14.66 2.70
March 16.08 6.07
April 19.26 11.58
May 21.21 14.61
June 23.66 19.78
July 26.00 24.54
August 24.40 21.22
September 22.58 17.37
October 19.38 11.70
November 15.50 4.05
December 13.92 1.86
     
Annual Sum or Average 19.15 11.20
Minimum of Months 12.83 -1.7
Maximum of Months 26.00 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -1.7
February 20.55 2.70
March 20.75 6.07
April 21.33 11.58
May 21.59 14.61
June 21.70 19.78
July 21.76 24.54
August 21.73 21.22
September 21.64 17.37
October 21.19 11.70
November 20.70 4.05
December 20.50 1.86
     
Annual Sum or Average 21.16 11.20
Minimum of Months 20.48 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -1.7
February 18.97 2.70
March 19.41 6.07
April 20.95 11.58
May 21.76 14.61
June 22.66 19.78
July 23.15 24.54
August 22.78 21.22
September 22.21 17.37
October 20.45 11.70
November 19.11 4.05
December 18.90 1.86
     
Annual Sum or Average 20.78 11.20
Minimum of Months 18.89 -1.7
Maximum of Months 23.15 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -1.7
February 19.01 2.70
March 19.50 6.07
April 21.02 11.58
May 21.81 14.61
June 22.67 19.78
July 23.14 24.54
August 22.78 21.22
September 22.22 17.37
October 20.54 11.70
November 19.15 4.05
December 18.91 1.86
     
Annual Sum or Average 20.81 11.20
Minimum of Months 18.89 -1.7
Maximum of Months 23.14 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.60 -1.7
February 20.95 2.70
March 21.21 6.07
April 21.60 11.58
May 21.71 14.61
June 21.74 19.78
July 21.76 24.54
August 21.75 21.22
September 21.72 17.37
October 21.53 11.70
November 21.05 4.05
December 20.77 1.86
     
Annual Sum or Average 21.37 11.20
Minimum of Months 20.60 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -1.7
February 18.98 2.70
March 19.41 6.07
April 20.96 11.58
May 21.77 14.61
June 22.66 19.78
July 23.17 24.54
August 22.82 21.22
September 22.27 17.37
October 20.62 11.70
November 19.17 4.05
December 18.90 1.86
     
Annual Sum or Average 20.81 11.20
Minimum of Months 18.89 -1.7
Maximum of Months 23.17 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -1.7
February 19.07 2.70
March 19.80 6.07
April 21.46 11.58
May 22.17 14.61
June 22.87 19.78
July 23.23 24.54
August 22.96 21.22
September 22.56 17.37
October 21.21 11.70
November 19.41 4.05
December 18.94 1.86
     
Annual Sum or Average 21.06 11.20
Minimum of Months 18.90 -1.7
Maximum of Months 23.23 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.74 -1.7
February 21.19 2.70
March 21.49 6.07
April 21.71 11.58
May 21.74 14.61
June 21.75 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.69 11.70
November 21.22 4.05
December 20.93 1.86
     
Annual Sum or Average 21.48 11.20
Minimum of Months 20.74 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.18 -1.7
February 20.09 2.70
March 20.95 6.07
April 22.57 11.58
May 23.42 14.61
June 24.44 19.78
July 25.24 24.54
August 24.57 21.22
September 23.72 17.37
October 22.29 11.70
November 20.39 4.05
December 19.61 1.86
     
Annual Sum or Average 22.22 11.20
Minimum of Months 19.18 -1.7
Maximum of Months 25.24 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.70 -1.7
February 21.12 2.70
March 21.44 6.07
April 21.71 11.58
May 21.74 14.61
June 21.75 19.78
July 21.76 24.54
August 21.76 21.22
September 21.75 17.37
October 21.67 11.70
November 21.18 4.05
December 20.87 1.86
     
Annual Sum or Average 21.45 11.20
Minimum of Months 20.70 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.71 -1.7
February 21.15 2.70
March 21.46 6.07
April 21.71 11.58
May 21.73 14.61
June 21.75 19.78
July 21.76 24.54
August 21.75 21.22
September 21.75 17.37
October 21.68 11.70
November 21.19 4.05
December 20.89 1.86
     
Annual Sum or Average 21.46 11.20
Minimum of Months 20.71 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.54 -1.7
February 20.86 2.70
March 21.24 6.07
April 21.66 11.58
May 21.72 14.61
June 21.75 19.78
July 21.76 24.54
August 21.76 21.22
September 21.74 17.37
October 21.60 11.70
November 20.99 4.05
December 20.67 1.86
     
Annual Sum or Average 21.36 11.20
Minimum of Months 20.54 -1.7
Maximum of Months 21.76 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.29 -1.7
February 17.80 2.70
March 19.14 6.07
April 21.69 11.58
May 23.16 14.61
June 24.94 19.78
July 26.49 24.54
August 25.24 21.22
September 23.76 17.37
October 21.48 11.70
November 18.46 4.05
December 17.15 1.86
     
Annual Sum or Average 21.32 11.20
Minimum of Months 16.29 -1.7
Maximum of Months 26.49 24.54



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2015-09-14 08:44:23

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.70 -1.7
February 14.88 2.70
March 16.62 6.07
April 20.11 11.58
May 22.44 14.61
June 25.21 19.78
July 27.84 24.54
August 25.75 21.22
September 23.47 17.37
October 20.13 11.70
November 15.96 4.05
December 14.07 1.86
     
Annual Sum or Average 19.96 11.20
Minimum of Months 12.70 -1.7
Maximum of Months 27.84 24.54



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:23

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.185162E+12 152533.393 13-JAN-07:00 17938.631 34285.948 9443.399 86546.277 123.026 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.145957E+12 119707.876 27-FEB-07:15 20847.837 39740.848 9441.395 45165.565 316.118 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.153399E+12 115884.531 15-MAR-06:15 20847.837 39740.848 9441.395 41138.952 519.386 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.149906E+12 107402.762 09-APR-06:15 20847.837 39740.848 9441.395 31750.102 1426.467 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.158965E+12 96101.283 27-MAY-07:00 25182.171 43578.554 10015.831 0.000 17316.614 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.167375E+12 107356.313 21-JUN-19:15 27551.975 28549.175 9590.655 0.000 41656.395 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.186773E+12 111806.321 21-JUL-17:30 26252.371 28657.799 9685.844 0.000 47202.194 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.176391E+12 107539.596 04-AUG-17:15 26252.371 28657.799 9637.508 0.000 42983.806 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.159363E+12 99420.042 01-SEP-07:00 25182.171 43578.554 10015.831 0.000 20635.373 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.153555E+12 104150.988 24-OCT-06:00 20847.837 39740.848 9441.395 27743.121 2181.674 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.156858E+12 126864.983 15-NOV-07:15 20847.837 39740.848 9441.395 52384.809 253.982 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.169343E+12 132223.830 11-DEC-07:15 20847.837 39740.848 9441.395 57778.985 218.653 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.196305E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.145957E+12 96101.283   17938.631 28549.175 9441.395 0.000 123.026 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.186773E+12 152533.393   27551.975 43578.554 10015.831 86546.277 47202.194 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:23

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.111784E+12 111790.655 21-JAN-09:15 1416.780 40096.028 0.000 70277.847 70277.847 70277.847 1416.780
February 0.944837E+11 109459.594 17-FEB-09:15 197.045 40096.028 0.000 69166.520 69166.520 69166.520 197.045
March 0.998169E+11 105193.451 17-MAR-08:15 0.000 40096.028 0.000 65097.422 65097.422 65097.422 0.000
April 0.910071E+11 105340.067 08-APR-08:15 524.916 40096.028 0.000 64719.122 64719.122 64719.122 524.916
May 0.894377E+11 96346.506 27-MAY-08:15 0.000 40096.028 0.000 56250.478 56250.478 56250.478 0.000
June 0.828379E+11 92579.153 09-JUN-08:15 0.000 40096.028 0.000 52483.125 52483.125 52483.125 0.000
July 0.829019E+11 85268.525 04-JUL-08:15 0.000 40096.028 0.000 45172.497 45172.497 45172.497 0.000
August 0.821042E+11 83872.973 12-AUG-08:15 0.000 40096.028 0.000 43776.945 43776.945 43776.945 0.000
September 0.805255E+11 88664.252 30-SEP-08:15 0.000 40096.028 0.000 48568.224 48568.224 48568.224 0.000
October 0.868986E+11 91926.406 13-OCT-08:15 0.000 40096.028 0.000 51830.378 51830.378 51830.378 0.000
November 0.936989E+11 102687.700 24-NOV-09:15 1035.913 40096.028 0.000 61555.759 61555.759 61555.759 1035.913
December 0.103080E+12 111355.467 29-DEC-09:15 3187.469 40096.028 0.000 68071.970 68071.970 68071.970 3187.469
                     
Annual Sum or Average 0.109858E+13         0.000        
Minimum of Months 0.805255E+11 83872.973   0.000 40096.028 0.000 43776.945 43776.945 43776.945 0.000
Maximum of Months 0.111784E+12 111790.655   3187.469 40096.028 0.000 70277.847 70277.847 70277.847 3187.469