Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Simulation Timestamp: 2015-09-14 08:44:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3117.71 | 776.79 | 836.95 |
Net Site Energy | 3117.71 | 776.79 | 836.95 |
Total Source Energy | 7938.96 | 1978.02 | 2131.21 |
Net Source Energy | 7938.96 | 1978.02 | 2131.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 27.61 | 10.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 611.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 303.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 496.90 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2188.85 | 928.87 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 27.61 | 10.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 611.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 303.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 496.90 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.14 | 136.21 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 587.59 | 249.35 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 234.94 | 126.42 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 545.36 | 231.43 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2188.85 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2188.85 | 100.00 |
Total On-Site and Utility Electric Sources | 2188.85 | 100.00 |
Total Electricity End Uses | 2188.85 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 70.00 |
Time Setpoint Not Met During Occupied Cooling | 5468.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6253.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Houston Bush Intercontinental TX USA TMY3 WMO#=722430 |
Weather File | Houston Bush Intercontinental TX USA TMY3 WMO#=722430 |
Latitude [deg] | 30.00 |
Longitude [deg] | -95.4 |
Elevation [m] | 29.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00 | -1.60 | Wetbulb [C] | 2.80 | 0.00 |
HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 10.10 | 24.80 | Wetbulb [C] | 3.50 | 170.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 8.38 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 175.82 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9296.62 | 6645.68 | 2650.93 | 0.71 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 27340.95 | 18528.29 | 8812.67 | 0.68 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12051.31 | 8147.69 | 3903.62 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16818.16 | 12092.66 | 4725.50 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8959.8 | 3.30 | 11.27 | 11.95 | 11.31 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 26479.6 | 3.05 | 10.42 | 11.06 | 10.66 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11674.1 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16200.0 | 3.30 | 11.25 | 11.92 | 11.27 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.33 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 25590.95 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 850.89 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 850.89 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1026.11 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 915.24 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 850.82 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.25 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.33 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2413.16 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 850.89 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3403.54 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2697.42 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3403.54 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 995.92 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 884.82 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3403.30 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 850.82 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3403.30 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 850.82 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.25 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.33 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2413.16 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 850.89 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3403.54 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2697.42 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3403.54 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 850.89 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 969.02 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3403.30 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 850.82 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3403.30 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 850.82 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.25 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.33 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 3248.20 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1206.12 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3403.54 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2697.42 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3516.74 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 910.98 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 850.82 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3444.18 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 971.74 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3403.30 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1139.25 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.25 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3503.57 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 14685.13 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 7863.78 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5912.72 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.43 | 503.33 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.11 | 1263.44 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 563.36 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.80 | 907.45 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 11163.06 | 13395.68 | 0.923 | 1.108 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
RESTROOMFLR1 | 787.03 | 944.44 | 0.065 | 0.078 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 32.82 | 0.01519 |
MEETINGROOMFLR1 | 4886.08 | 5863.30 | 0.404 | 0.485 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
GUESTROOM101 | 724.00 | 868.80 | 0.063 | 0.076 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
GUESTROOM102 | 582.66 | 699.20 | 0.051 | 0.061 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
GUESTROOM103 | 1730.05 | 2076.06 | 0.199 | 0.239 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
GUESTROOM104 | 1562.89 | 1875.46 | 0.180 | 0.216 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 33.68 | 0.01519 |
GUESTROOM105 | 1947.16 | 2336.59 | 0.224 | 0.269 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 33.30 | 0.01519 |
EMPLOYEELOUNGEFLR1 | 5784.05 | 6940.87 | 0.479 | 0.574 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 33.68 | 0.01519 |
EXERCISECENTERFLR1 | 1447.21 | 1736.66 | 0.120 | 0.144 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 30.87 | 0.01519 |
FRONTOFFICEFLR1 | 4371.17 | 5245.40 | 0.361 | 0.434 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 33.30 | 0.01519 |
GUESTROOM201 | 942.27 | 1130.72 | 0.083 | 0.099 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM202_205 | 6220.55 | 7464.65 | 0.715 | 0.858 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM206_208 | 5138.74 | 6166.49 | 0.591 | 0.709 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM209_212 | 5858.69 | 7030.42 | 0.673 | 0.808 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM213 | 1711.25 | 2053.50 | 0.197 | 0.236 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
GUESTROOM214 | 1693.18 | 2031.82 | 0.195 | 0.234 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM215_218 | 8858.99 | 10630.79 | 0.776 | 0.931 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM219 | 5722.77 | 6867.32 | 0.658 | 0.789 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 33.30 | 0.01519 |
GUESTROOM220_223 | 5623.55 | 6748.25 | 0.646 | 0.776 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM224 | 1689.71 | 2027.65 | 0.194 | 0.233 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM301 | 815.56 | 978.67 | 0.071 | 0.086 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM302_305 | 2286.52 | 2743.82 | 0.200 | 0.240 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM306_308 | 2080.13 | 2496.15 | 0.182 | 0.219 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM309_312 | 5848.63 | 7018.36 | 0.672 | 0.807 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 34.33 | 0.01519 |
GUESTROOM313 | 773.73 | 928.47 | 0.068 | 0.081 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
GUESTROOM314 | 1620.64 | 1944.77 | 0.186 | 0.224 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 33.30 | 0.01519 |
GUESTROOM315_318 | 6267.24 | 7520.68 | 0.720 | 0.864 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM319 | 922.44 | 1106.93 | 0.081 | 0.097 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM320_323 | 5436.45 | 6523.74 | 0.625 | 0.750 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM324 | 635.74 | 762.89 | 0.056 | 0.067 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 32.92 | 0.01519 |
GUESTROOM401 | 2167.77 | 2601.32 | 0.249 | 0.299 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 34.99 | 0.01519 |
GUESTROOM402_405 | 3299.17 | 3959.01 | 0.289 | 0.347 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 34.99 | 0.01519 |
GUESTROOM406_408 | 2967.68 | 3561.22 | 0.260 | 0.312 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.79 | 0.01519 |
GUESTROOM409_412 | 7139.00 | 8566.80 | 0.821 | 0.985 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 34.99 | 0.01519 |
GUESTROOM413 | 1137.24 | 1364.69 | 0.100 | 0.120 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 34.79 | 0.01519 |
GUESTROOM414 | 916.70 | 1100.04 | 0.080 | 0.096 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 36.00 | 0.01519 |
GUESTROOM415_418 | 6719.06 | 8062.87 | 0.772 | 0.927 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.93 | 0.01519 |
GUESTROOM419 | 1845.64 | 2214.77 | 0.212 | 0.255 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 34.18 | 0.01519 |
GUESTROOM420_423 | 6583.84 | 7900.60 | 0.757 | 0.908 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.93 | 0.01519 |
GUESTROOM424 | 1916.02 | 2299.22 | 0.220 | 0.264 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 34.43 | 0.01519 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
CORRIDORFLR1 | 20447.69 | 24537.23 | 1.691 | 2.030 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 33.58 | 0.01519 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
CORRIDORFLR2 | 3054.27 | 3665.12 | 0.252 | 0.303 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 34.08 | 0.01519 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
CORRIDORFLR3 | 1801.89 | 2162.27 | 0.149 | 0.179 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.83 | 0.01519 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 | |
CORRIDORFLR4 | 2954.07 | 3544.88 | 0.244 | 0.293 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.00 | 0.01519 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB | 36.00 | 0.01519 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1823.64 | 2188.36 | 0.052 | 0.236 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | -1.60 | 0.00331 |
RESTROOMFLR1 | 33.06 | 39.67 | 0.001 | 0.001 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -1.60 | 0.00331 |
MEETINGROOMFLR1 | 615.27 | 738.32 | 0.017 | 0.126 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -1.60 | 0.00331 |
GUESTROOM101 | 3.32 | 3.98 | 0.000 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -1.60 | 0.00331 |
GUESTROOM102 | 39.06 | 46.88 | 0.001 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -1.60 | 0.00331 |
GUESTROOM103 | 543.01 | 651.61 | 0.015 | 0.018 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -1.60 | 0.00331 |
GUESTROOM104 | 450.64 | 540.76 | 0.013 | 0.015 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -1.60 | 0.00331 |
GUESTROOM105 | 321.28 | 385.53 | 0.009 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -1.60 | 0.00331 |
EMPLOYEELOUNGEFLR1 | 300.65 | 360.78 | 0.009 | 0.051 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -1.60 | 0.00331 |
EXERCISECENTERFLR1 | 174.67 | 209.60 | 0.005 | 0.043 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -1.60 | 0.00331 |
FRONTOFFICEFLR1 | 1037.16 | 1244.59 | 0.029 | 0.056 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -1.60 | 0.00331 |
GUESTROOM201 | 165.20 | 198.24 | 0.004 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -1.60 | 0.00331 |
GUESTROOM202_205 | 1129.10 | 1354.92 | 0.032 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -1.60 | 0.00331 |
GUESTROOM206_208 | 855.67 | 1026.80 | 0.024 | 0.043 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
GUESTROOM209_212 | 893.76 | 1072.52 | 0.025 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -1.60 | 0.00331 |
GUESTROOM213 | 517.85 | 621.42 | 0.015 | 0.018 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -1.60 | 0.00331 |
GUESTROOM214 | 425.28 | 510.34 | 0.012 | 0.014 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -1.60 | 0.00331 |
GUESTROOM215_218 | 103.69 | 124.42 | 0.003 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -1.60 | 0.00331 |
GUESTROOM219 | 242.92 | 291.50 | 0.007 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -1.60 | 0.00331 |
GUESTROOM220_223 | 764.56 | 917.47 | 0.022 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -1.60 | 0.00331 |
GUESTROOM224 | 379.50 | 455.40 | 0.011 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -1.60 | 0.00331 |
GUESTROOM301 | 222.61 | 267.13 | 0.006 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -1.60 | 0.00331 |
GUESTROOM302_305 | 465.02 | 558.03 | 0.012 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -1.60 | 0.00331 |
GUESTROOM306_308 | 390.20 | 468.23 | 0.010 | 0.043 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | -1.60 | 0.00331 |
GUESTROOM309_312 | 1065.06 | 1278.07 | 0.030 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 14:45:00 | -1.60 | 0.00331 |
GUESTROOM313 | 264.99 | 317.99 | 0.007 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 20:45:00 | -1.60 | 0.00331 |
GUESTROOM314 | 495.45 | 594.54 | 0.014 | 0.017 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | -1.60 | 0.00331 |
GUESTROOM315_318 | 1110.08 | 1332.10 | 0.031 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -1.60 | 0.00331 |
GUESTROOM319 | 28.89 | 34.67 | 0.001 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -1.60 | 0.00331 |
GUESTROOM320_323 | 943.96 | 1132.75 | 0.027 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -1.60 | 0.00331 |
GUESTROOM324 | 124.18 | 149.02 | 0.003 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | -1.60 | 0.00331 |
GUESTROOM401 | 693.01 | 831.61 | 0.020 | 0.024 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -1.60 | 0.00331 |
GUESTROOM402_405 | 1086.97 | 1304.37 | 0.029 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -1.60 | 0.00331 |
GUESTROOM406_408 | 922.79 | 1107.35 | 0.024 | 0.043 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -1.60 | 0.00331 |
GUESTROOM409_412 | 1682.27 | 2018.72 | 0.048 | 0.057 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | -1.60 | 0.00331 |
GUESTROOM413 | 477.60 | 573.12 | 0.013 | 0.015 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -1.60 | 0.00331 |
GUESTROOM414 | 354.19 | 425.03 | 0.009 | 0.013 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | -1.60 | 0.00331 |
GUESTROOM415_418 | 1621.89 | 1946.27 | 0.046 | 0.055 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -1.60 | 0.00331 |
GUESTROOM419 | 497.72 | 597.26 | 0.014 | 0.017 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -1.60 | 0.00331 |
GUESTROOM420_423 | 1516.90 | 1820.28 | 0.043 | 0.054 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -1.60 | 0.00331 |
GUESTROOM424 | 637.31 | 764.77 | 0.018 | 0.022 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -1.60 | 0.00331 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
CORRIDORFLR1 | 20254.62 | 24305.54 | 0.572 | 0.687 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -1.60 | 0.00331 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
CORRIDORFLR2 | 663.46 | 796.15 | 0.019 | 0.038 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -1.60 | 0.00331 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
CORRIDORFLR3 | 1011.74 | 1214.09 | 0.029 | 0.038 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -1.60 | 0.00331 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 | |
CORRIDORFLR4 | 1821.77 | 2186.13 | 0.052 | 0.062 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -1.60 | 0.00331 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB | -1.60 | 0.00331 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.43 | 0.43 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.11 | 1.11 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.49 | 0.49 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.80 | 0.80 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 5206.25 | 5322.75 | 2700.00 |
RESTROOMFLR1 | 2808.75 | 4663.50 | 701.25 |
MEETINGROOMFLR1 | 2978.00 | 1837.00 | 854.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 457.50 | 8275.50 | 454.00 |
GUESTROOM104 | 147.25 | 7896.25 | 114.00 |
GUESTROOM105 | 369.00 | 7447.25 | 18.75 |
EMPLOYEELOUNGEFLR1 | 3565.00 | 1926.00 | 481.25 |
EXERCISECENTERFLR1 | 3548.75 | 1136.50 | 159.00 |
FRONTOFFICEFLR1 | 4294.25 | 3206.50 | 607.25 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 607.00 | 7541.00 | 109.25 |
GUESTROOM206_208 | 566.50 | 7496.75 | 54.50 |
GUESTROOM209_212 | 419.75 | 7818.50 | 233.25 |
GUESTROOM213 | 344.75 | 7925.25 | 265.00 |
GUESTROOM214 | 423.25 | 7542.50 | 32.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 5674.00 | 3510.75 | 1395.00 |
GUESTROOM220_223 | 660.25 | 7388.25 | 50.25 |
GUESTROOM224 | 485.75 | 7478.25 | 20.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 498.75 | 7971.25 | 347.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 523.75 | 7571.75 | 85.50 |
GUESTROOM315_318 | 764.00 | 7298.25 | 36.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 533.00 | 7624.00 | 128.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1696.00 | 7365.00 | 768.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1347.75 | 7052.50 | 144.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1370.50 | 6878.75 | 61.00 |
GUESTROOM419 | 1125.00 | 7074.25 | 64.50 |
GUESTROOM420_423 | 1357.25 | 6922.75 | 75.00 |
GUESTROOM424 | 1275.00 | 7125.00 | 209.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7597.25 | 8742.50 | 6253.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 3.25 | 1788.75 | 3.25 | 1788.75 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 76.50 | 0.00 | 76.50 |
GUESTROOM104 | 0.00 | 74.00 | 0.00 | 74.00 |
GUESTROOM105 | 0.00 | 79.50 | 0.00 | 79.50 |
EMPLOYEELOUNGEFLR1 | 92.75 | 1219.50 | 68.00 | 669.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 64.25 | 0.00 | 64.25 |
GUESTROOM206_208 | 0.00 | 71.25 | 0.00 | 71.25 |
GUESTROOM209_212 | 0.00 | 63.25 | 0.00 | 63.25 |
GUESTROOM213 | 0.00 | 63.50 | 0.00 | 63.50 |
GUESTROOM214 | 0.00 | 63.25 | 0.00 | 63.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 4571.75 | 0.00 | 4571.75 |
GUESTROOM220_223 | 0.00 | 61.75 | 0.00 | 61.75 |
GUESTROOM224 | 0.00 | 63.00 | 0.00 | 63.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 63.00 | 0.00 | 63.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 62.25 | 0.00 | 62.25 |
GUESTROOM315_318 | 0.00 | 62.75 | 0.00 | 62.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 60.75 | 0.00 | 60.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1.25 | 142.75 | 1.25 | 142.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 72.00 | 0.00 | 72.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 64.75 | 0.00 | 64.75 |
GUESTROOM419 | 0.00 | 73.50 | 0.00 | 73.50 |
GUESTROOM420_423 | 0.00 | 64.50 | 0.00 | 64.50 |
GUESTROOM424 | 0.00 | 79.75 | 0.00 | 79.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 2.25 | 5798.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 1558.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 67.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 1110.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 94.75 | 6897.00 | 70.00 | 5468.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:29
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.433592 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.11 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.795930 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 320.33 |
CORRIDORFLR1 PTAC HEATING COIL | 25590.95 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 850.89 |
102 PTAC HEATING COIL | 850.89 |
103 PTAC HEATING COIL | 1026.11 |
104 PTAC HEATING COIL | 915.24 |
105 PTAC HEATING COIL | 850.82 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 320.25 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 320.33 |
CORRIDORFLR2 PTAC HEATING COIL | 2413.16 |
201 PTAC HEATING COIL | 850.89 |
202_205 PTAC HEATING COIL | 3403.54 |
206_208 PTAC HEATING COIL | 2697.42 |
209_212 PTAC HEATING COIL | 3403.54 |
213 PTAC HEATING COIL | 995.92 |
214 PTAC HEATING COIL | 884.82 |
215_218 PTAC HEATING COIL | 3403.30 |
219 PTAC HEATING COIL | 850.82 |
220_223 PTAC HEATING COIL | 3403.30 |
224 PTAC HEATING COIL | 850.82 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 320.25 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 320.33 |
CORRIDORFLR3 PTAC HEATING COIL | 2413.16 |
301 PTAC HEATING COIL | 850.89 |
302_305 PTAC HEATING COIL | 3403.54 |
306_308 PTAC HEATING COIL | 2697.42 |
309_312 PTAC HEATING COIL | 3403.54 |
313 PTAC HEATING COIL | 850.89 |
314 PTAC HEATING COIL | 969.02 |
315_318 PTAC HEATING COIL | 3403.30 |
319 PTAC HEATING COIL | 850.82 |
320_323 PTAC HEATING COIL | 3403.30 |
324 PTAC HEATING COIL | 850.82 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 320.25 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 320.33 |
CORRIDORFLR4 PTAC HEATING COIL | 3248.20 |
401 PTAC HEATING COIL | 1206.12 |
402_405 PTAC HEATING COIL | 3403.54 |
406_408 PTAC HEATING COIL | 2697.42 |
409_412 PTAC HEATING COIL | 3516.74 |
413 PTAC HEATING COIL | 910.98 |
414 PTAC HEATING COIL | 850.82 |
415_418 PTAC HEATING COIL | 3444.18 |
419 PTAC HEATING COIL | 971.74 |
420_423 PTAC HEATING COIL | 3403.30 |
424 PTAC HEATING COIL | 1139.25 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 320.25 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.714850 | 0.433592 | 9296.62 |
SAC_FRONTLOUNGE COOLING COIL | 0.677675 | 1.11 | 27340.95 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.485306 | 12051.31 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.719024 | 0.795930 | 16818.16 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.11 |
RESTROOMFLR1 DIRECT AIR | 0.078054 |
MEETINGROOMFLR1 DIRECT AIR | 0.485306 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.574269 |
EXERCISECENTERFLR1 DIRECT AIR | 0.143606 |
FRONTOFFICEFLR1 DIRECT AIR | 0.433592 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.433592 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.11 |
SAC_MEETINGROOM MAIN BRANCH | 0.485306 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.795930 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.433592 |
SAC_FRONTLOUNGE | 1.11 |
SAC_MEETINGROOM | 0.485306 |
SAC_EXC_EMPLGE_RESTRM | 0.795930 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.433592 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.11 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.485306 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.795930 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.433592 | 0.433592 | 0.433592 | 0.433592 | 3503.57 | 9296.62 | 1.00 |
SAC_FRONTLOUNGE | 1.11 | 1.11 | 1.11 | 1.11 | 14685.13 | 27340.95 | 1.00 |
SAC_MEETINGROOM | 0.485306 | 0.485306 | 0.485306 | 0.485306 | 7863.78 | 12051.31 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.795930 | 0.795930 | 0.795930 | 0.795930 | 5912.72 | 16818.16 | 0.180426 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3503.57 |
SAC_FRONTLOUNGE HEATING COIL | 14685.13 |
SAC_MEETINGROOM HEATING COIL | 7863.78 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5912.72 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.485306 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.30 | 10.50 |
February | 20.99 | 12.77 |
March | 22.14 | 16.20 |
April | 23.69 | 20.49 |
May | 24.99 | 24.03 |
June | 25.96 | 27.02 |
July | 26.42 | 28.27 |
August | 26.41 | 28.21 |
September | 26.13 | 26.44 |
October | 24.36 | 20.33 |
November | 23.00 | 17.10 |
December | 21.24 | 12.54 |
Annual Sum or Average | 23.81 | 20.36 |
Minimum of Months | 20.30 | 10.50 |
Maximum of Months | 26.42 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.40 | 10.50 |
February | 23.80 | 12.77 |
March | 24.44 | 16.20 |
April | 25.38 | 20.49 |
May | 26.33 | 24.03 |
June | 27.30 | 27.02 |
July | 27.66 | 28.27 |
August | 27.66 | 28.21 |
September | 27.07 | 26.44 |
October | 25.52 | 20.33 |
November | 24.72 | 17.10 |
December | 23.79 | 12.54 |
Annual Sum or Average | 25.60 | 20.36 |
Minimum of Months | 23.40 | 10.50 |
Maximum of Months | 27.66 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | 10.50 |
February | 20.28 | 12.77 |
March | 21.49 | 16.20 |
April | 23.06 | 20.49 |
May | 24.36 | 24.03 |
June | 25.28 | 27.02 |
July | 25.73 | 28.27 |
August | 25.69 | 28.21 |
September | 25.50 | 26.44 |
October | 23.66 | 20.33 |
November | 22.32 | 17.10 |
December | 20.50 | 12.54 |
Annual Sum or Average | 23.13 | 20.36 |
Minimum of Months | 19.54 | 10.50 |
Maximum of Months | 25.73 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | 10.50 |
February | 22.70 | 12.77 |
March | 23.18 | 16.20 |
April | 23.69 | 20.49 |
May | 23.86 | 24.03 |
June | 23.89 | 27.02 |
July | 23.89 | 28.27 |
August | 23.89 | 28.21 |
September | 23.89 | 26.44 |
October | 23.59 | 20.33 |
November | 23.28 | 17.10 |
December | 22.59 | 12.54 |
Annual Sum or Average | 23.40 | 20.36 |
Minimum of Months | 22.30 | 10.50 |
Maximum of Months | 23.89 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | 10.50 |
February | 22.87 | 12.77 |
March | 23.18 | 16.20 |
April | 23.49 | 20.49 |
May | 23.66 | 24.03 |
June | 23.73 | 27.02 |
July | 23.77 | 28.27 |
August | 23.77 | 28.21 |
September | 23.74 | 26.44 |
October | 23.48 | 20.33 |
November | 23.25 | 17.10 |
December | 22.85 | 12.54 |
Annual Sum or Average | 23.37 | 20.36 |
Minimum of Months | 22.67 | 10.50 |
Maximum of Months | 23.77 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 10.50 |
February | 22.95 | 12.77 |
March | 23.40 | 16.20 |
April | 23.74 | 20.49 |
May | 23.86 | 24.03 |
June | 23.89 | 27.02 |
July | 23.89 | 28.27 |
August | 23.89 | 28.21 |
September | 23.88 | 26.44 |
October | 23.74 | 20.33 |
November | 23.53 | 17.10 |
December | 22.97 | 12.54 |
Annual Sum or Average | 23.54 | 20.36 |
Minimum of Months | 22.70 | 10.50 |
Maximum of Months | 23.89 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.17 | 10.50 |
February | 25.47 | 12.77 |
March | 25.99 | 16.20 |
April | 26.52 | 20.49 |
May | 26.93 | 24.03 |
June | 27.20 | 27.02 |
July | 27.33 | 28.27 |
August | 27.30 | 28.21 |
September | 27.16 | 26.44 |
October | 26.58 | 20.33 |
November | 26.15 | 17.10 |
December | 25.48 | 12.54 |
Annual Sum or Average | 26.44 | 20.36 |
Minimum of Months | 25.17 | 10.50 |
Maximum of Months | 27.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 10.50 |
February | 21.66 | 12.77 |
March | 22.42 | 16.20 |
April | 23.05 | 20.49 |
May | 23.29 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.32 | 26.44 |
October | 23.00 | 20.33 |
November | 22.58 | 17.10 |
December | 21.64 | 12.54 |
Annual Sum or Average | 22.68 | 20.36 |
Minimum of Months | 21.16 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.84 | 10.50 |
February | 21.39 | 12.77 |
March | 22.18 | 16.20 |
April | 22.91 | 20.49 |
May | 23.24 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.29 | 26.44 |
October | 22.85 | 20.33 |
November | 22.37 | 17.10 |
December | 21.34 | 12.54 |
Annual Sum or Average | 22.54 | 20.36 |
Minimum of Months | 20.84 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | 10.50 |
February | 21.42 | 12.77 |
March | 21.59 | 16.20 |
April | 21.72 | 20.49 |
May | 21.75 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.73 | 20.33 |
November | 21.67 | 17.10 |
December | 21.46 | 12.54 |
Annual Sum or Average | 21.64 | 20.36 |
Minimum of Months | 21.31 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.48 | 10.50 |
February | 21.53 | 12.77 |
March | 21.68 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.72 | 17.10 |
December | 21.58 | 12.54 |
Annual Sum or Average | 21.69 | 20.36 |
Minimum of Months | 21.48 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | 10.50 |
February | 21.68 | 12.77 |
March | 21.74 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.75 | 17.10 |
December | 21.70 | 12.54 |
Annual Sum or Average | 21.74 | 20.36 |
Minimum of Months | 21.68 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.85 | 10.50 |
February | 22.87 | 12.77 |
March | 22.89 | 16.20 |
April | 22.84 | 20.49 |
May | 22.63 | 24.03 |
June | 22.37 | 27.02 |
July | 22.26 | 28.27 |
August | 22.29 | 28.21 |
September | 22.43 | 26.44 |
October | 22.75 | 20.33 |
November | 22.84 | 17.10 |
December | 22.85 | 12.54 |
Annual Sum or Average | 22.65 | 20.36 |
Minimum of Months | 22.26 | 10.50 |
Maximum of Months | 22.89 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 50.79 | 10.50 |
February | 51.05 | 12.77 |
March | 51.56 | 16.20 |
April | 52.19 | 20.49 |
May | 52.78 | 24.03 |
June | 53.29 | 27.02 |
July | 53.51 | 28.27 |
August | 53.53 | 28.21 |
September | 53.12 | 26.44 |
October | 52.37 | 20.33 |
November | 51.75 | 17.10 |
December | 51.08 | 12.54 |
Annual Sum or Average | 52.26 | 20.36 |
Minimum of Months | 50.79 | 10.50 |
Maximum of Months | 53.53 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.09 | 10.50 |
February | 69.39 | 12.77 |
March | 69.84 | 16.20 |
April | 70.66 | 20.49 |
May | 71.39 | 24.03 |
June | 72.11 | 27.02 |
July | 72.39 | 28.27 |
August | 72.52 | 28.21 |
September | 71.86 | 26.44 |
October | 71.05 | 20.33 |
November | 70.23 | 17.10 |
December | 69.50 | 12.54 |
Annual Sum or Average | 70.84 | 20.36 |
Minimum of Months | 69.09 | 10.50 |
Maximum of Months | 72.52 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 10.50 |
February | 23.45 | 12.77 |
March | 23.65 | 16.20 |
April | 23.84 | 20.49 |
May | 23.89 | 24.03 |
June | 23.89 | 27.02 |
July | 23.89 | 28.27 |
August | 23.89 | 28.21 |
September | 23.89 | 26.44 |
October | 23.80 | 20.33 |
November | 23.67 | 17.10 |
December | 23.43 | 12.54 |
Annual Sum or Average | 23.72 | 20.36 |
Minimum of Months | 23.33 | 10.50 |
Maximum of Months | 23.89 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.18 | 10.50 |
February | 23.32 | 12.77 |
March | 23.67 | 16.20 |
April | 23.86 | 20.49 |
May | 23.89 | 24.03 |
June | 23.89 | 27.02 |
July | 23.89 | 28.27 |
August | 23.89 | 28.21 |
September | 23.89 | 26.44 |
October | 23.83 | 20.33 |
November | 23.70 | 17.10 |
December | 23.33 | 12.54 |
Annual Sum or Average | 23.70 | 20.36 |
Minimum of Months | 23.18 | 10.50 |
Maximum of Months | 23.89 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.57 | 10.50 |
February | 20.48 | 12.77 |
March | 21.90 | 16.20 |
April | 23.91 | 20.49 |
May | 25.62 | 24.03 |
June | 26.93 | 27.02 |
July | 27.46 | 28.27 |
August | 27.29 | 28.21 |
September | 26.61 | 26.44 |
October | 24.27 | 20.33 |
November | 22.64 | 17.10 |
December | 20.62 | 12.54 |
Annual Sum or Average | 23.96 | 20.36 |
Minimum of Months | 19.57 | 10.50 |
Maximum of Months | 27.46 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 10.50 |
February | 22.17 | 12.77 |
March | 23.11 | 16.20 |
April | 24.22 | 20.49 |
May | 25.18 | 24.03 |
June | 25.91 | 27.02 |
July | 26.22 | 28.27 |
August | 26.13 | 28.21 |
September | 25.74 | 26.44 |
October | 24.43 | 20.33 |
November | 23.51 | 17.10 |
December | 22.25 | 12.54 |
Annual Sum or Average | 24.22 | 20.36 |
Minimum of Months | 21.65 | 10.50 |
Maximum of Months | 26.22 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | 10.50 |
February | 21.29 | 12.77 |
March | 22.59 | 16.20 |
April | 24.35 | 20.49 |
May | 25.81 | 24.03 |
June | 26.90 | 27.02 |
July | 27.41 | 28.27 |
August | 27.39 | 28.21 |
September | 27.00 | 26.44 |
October | 25.09 | 20.33 |
November | 23.56 | 17.10 |
December | 21.61 | 12.54 |
Annual Sum or Average | 24.48 | 20.36 |
Minimum of Months | 20.51 | 10.50 |
Maximum of Months | 27.41 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.97 | 10.50 |
February | 23.17 | 12.77 |
March | 23.66 | 16.20 |
April | 23.88 | 20.49 |
May | 23.94 | 24.03 |
June | 24.15 | 27.02 |
July | 24.29 | 28.27 |
August | 24.29 | 28.21 |
September | 24.10 | 26.44 |
October | 23.89 | 20.33 |
November | 23.74 | 17.10 |
December | 23.29 | 12.54 |
Annual Sum or Average | 23.78 | 20.36 |
Minimum of Months | 22.97 | 10.50 |
Maximum of Months | 24.29 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.24 | 10.50 |
February | 20.12 | 12.77 |
March | 21.55 | 16.20 |
April | 23.38 | 20.49 |
May | 24.87 | 24.03 |
June | 25.89 | 27.02 |
July | 26.39 | 28.27 |
August | 26.33 | 28.21 |
September | 26.06 | 26.44 |
October | 24.03 | 20.33 |
November | 22.49 | 17.10 |
December | 20.39 | 12.54 |
Annual Sum or Average | 23.41 | 20.36 |
Minimum of Months | 19.24 | 10.50 |
Maximum of Months | 26.39 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | 10.50 |
February | 21.29 | 12.77 |
March | 22.22 | 16.20 |
April | 23.08 | 20.49 |
May | 23.31 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 23.03 | 20.33 |
November | 22.43 | 17.10 |
December | 21.13 | 12.54 |
Annual Sum or Average | 22.53 | 20.36 |
Minimum of Months | 20.51 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 10.50 |
February | 21.54 | 12.77 |
March | 21.69 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.73 | 17.10 |
December | 21.59 | 12.54 |
Annual Sum or Average | 21.69 | 20.36 |
Minimum of Months | 21.47 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 10.50 |
February | 21.56 | 12.77 |
March | 21.70 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.73 | 17.10 |
December | 21.61 | 12.54 |
Annual Sum or Average | 21.70 | 20.36 |
Minimum of Months | 21.51 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 10.50 |
February | 21.58 | 12.77 |
March | 21.70 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.73 | 17.10 |
December | 21.62 | 12.54 |
Annual Sum or Average | 21.70 | 20.36 |
Minimum of Months | 21.53 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | 10.50 |
February | 21.44 | 12.77 |
March | 21.63 | 16.20 |
April | 21.74 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.70 | 17.10 |
December | 21.51 | 12.54 |
Annual Sum or Average | 21.66 | 20.36 |
Minimum of Months | 21.34 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | 10.50 |
February | 21.58 | 12.77 |
March | 21.72 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.76 | 20.33 |
November | 21.74 | 17.10 |
December | 21.64 | 12.54 |
Annual Sum or Average | 21.71 | 20.36 |
Minimum of Months | 21.56 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.22 | 10.50 |
February | 23.22 | 12.77 |
March | 23.32 | 16.20 |
April | 23.33 | 20.49 |
May | 23.33 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 23.33 | 20.33 |
November | 23.33 | 17.10 |
December | 23.26 | 12.54 |
Annual Sum or Average | 23.31 | 20.36 |
Minimum of Months | 23.22 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 31.48 | 10.50 |
February | 31.80 | 12.77 |
March | 32.36 | 16.20 |
April | 33.05 | 20.49 |
May | 33.60 | 24.03 |
June | 34.13 | 27.02 |
July | 34.37 | 28.27 |
August | 34.40 | 28.21 |
September | 33.98 | 26.44 |
October | 33.25 | 20.33 |
November | 32.65 | 17.10 |
December | 31.90 | 12.54 |
Annual Sum or Average | 33.09 | 20.36 |
Minimum of Months | 31.48 | 10.50 |
Maximum of Months | 34.40 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 10.50 |
February | 22.19 | 12.77 |
March | 22.41 | 16.20 |
April | 22.78 | 20.49 |
May | 23.17 | 24.03 |
June | 23.73 | 27.02 |
July | 23.98 | 28.27 |
August | 23.99 | 28.21 |
September | 23.54 | 26.44 |
October | 22.78 | 20.33 |
November | 22.49 | 17.10 |
December | 22.17 | 12.54 |
Annual Sum or Average | 22.95 | 20.36 |
Minimum of Months | 22.06 | 10.50 |
Maximum of Months | 23.99 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 10.50 |
February | 21.64 | 12.77 |
March | 21.74 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.75 | 17.10 |
December | 21.68 | 12.54 |
Annual Sum or Average | 21.73 | 20.36 |
Minimum of Months | 21.63 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 10.50 |
February | 21.57 | 12.77 |
March | 21.72 | 16.20 |
April | 21.76 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.76 | 20.33 |
November | 21.74 | 17.10 |
December | 21.64 | 12.54 |
Annual Sum or Average | 21.71 | 20.36 |
Minimum of Months | 21.55 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | 10.50 |
February | 22.00 | 12.77 |
March | 23.15 | 16.20 |
April | 24.49 | 20.49 |
May | 25.64 | 24.03 |
June | 26.45 | 27.02 |
July | 26.79 | 28.27 |
August | 26.70 | 28.21 |
September | 26.25 | 26.44 |
October | 24.76 | 20.33 |
November | 23.68 | 17.10 |
December | 22.13 | 12.54 |
Annual Sum or Average | 24.46 | 20.36 |
Minimum of Months | 21.34 | 10.50 |
Maximum of Months | 26.79 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | 10.50 |
February | 20.65 | 12.77 |
March | 22.35 | 16.20 |
April | 24.68 | 20.49 |
May | 26.67 | 24.03 |
June | 28.21 | 27.02 |
July | 28.83 | 28.27 |
August | 28.70 | 28.21 |
September | 27.82 | 26.44 |
October | 25.21 | 20.33 |
November | 23.30 | 17.10 |
December | 20.88 | 12.54 |
Annual Sum or Average | 24.76 | 20.36 |
Minimum of Months | 19.58 | 10.50 |
Maximum of Months | 28.83 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.04 | 10.50 |
February | 20.95 | 12.77 |
March | 22.41 | 16.20 |
April | 24.39 | 20.49 |
May | 25.99 | 24.03 |
June | 27.15 | 27.02 |
July | 27.68 | 28.27 |
August | 27.66 | 28.21 |
September | 27.20 | 26.44 |
October | 25.12 | 20.33 |
November | 23.43 | 17.10 |
December | 21.24 | 12.54 |
Annual Sum or Average | 24.46 | 20.36 |
Minimum of Months | 20.04 | 10.50 |
Maximum of Months | 27.68 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 10.50 |
February | 22.54 | 12.77 |
March | 23.16 | 16.20 |
April | 23.74 | 20.49 |
May | 23.88 | 24.03 |
June | 23.89 | 27.02 |
July | 23.91 | 28.27 |
August | 23.92 | 28.21 |
September | 23.89 | 26.44 |
October | 23.74 | 20.33 |
November | 23.34 | 17.10 |
December | 22.46 | 12.54 |
Annual Sum or Average | 23.38 | 20.36 |
Minimum of Months | 22.01 | 10.50 |
Maximum of Months | 23.92 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.48 | 10.50 |
February | 19.59 | 12.77 |
March | 21.27 | 16.20 |
April | 23.41 | 20.49 |
May | 25.10 | 24.03 |
June | 26.23 | 27.02 |
July | 26.75 | 28.27 |
August | 26.69 | 28.21 |
September | 26.33 | 26.44 |
October | 24.05 | 20.33 |
November | 22.27 | 17.10 |
December | 19.79 | 12.54 |
Annual Sum or Average | 23.35 | 20.36 |
Minimum of Months | 18.48 | 10.50 |
Maximum of Months | 26.75 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.99 | 10.50 |
February | 20.91 | 12.77 |
March | 21.83 | 16.20 |
April | 22.93 | 20.49 |
May | 23.29 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.32 | 26.44 |
October | 22.86 | 20.33 |
November | 22.08 | 17.10 |
December | 20.64 | 12.54 |
Annual Sum or Average | 22.33 | 20.36 |
Minimum of Months | 19.99 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.29 | 10.50 |
February | 21.14 | 12.77 |
March | 22.12 | 16.20 |
April | 23.04 | 20.49 |
May | 23.31 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 22.96 | 20.33 |
November | 22.30 | 17.10 |
December | 20.92 | 12.54 |
Annual Sum or Average | 22.46 | 20.36 |
Minimum of Months | 20.29 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.41 | 10.50 |
February | 21.21 | 12.77 |
March | 22.17 | 16.20 |
April | 23.04 | 20.49 |
May | 23.30 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 22.96 | 20.33 |
November | 22.34 | 17.10 |
December | 21.01 | 12.54 |
Annual Sum or Average | 22.49 | 20.36 |
Minimum of Months | 20.41 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 10.50 |
February | 21.54 | 12.77 |
March | 21.67 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.72 | 17.10 |
December | 21.58 | 12.54 |
Annual Sum or Average | 21.69 | 20.36 |
Minimum of Months | 21.47 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.34 | 10.50 |
February | 21.14 | 12.77 |
March | 22.09 | 16.20 |
April | 23.02 | 20.49 |
May | 23.30 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 23.02 | 20.33 |
November | 22.37 | 17.10 |
December | 21.01 | 12.54 |
Annual Sum or Average | 22.47 | 20.36 |
Minimum of Months | 20.34 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 10.50 |
February | 21.49 | 12.77 |
March | 21.68 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.72 | 17.10 |
December | 21.56 | 12.54 |
Annual Sum or Average | 21.68 | 20.36 |
Minimum of Months | 21.44 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 10.50 |
February | 21.65 | 12.77 |
March | 21.74 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.76 | 20.33 |
November | 21.75 | 17.10 |
December | 21.68 | 12.54 |
Annual Sum or Average | 21.73 | 20.36 |
Minimum of Months | 21.64 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 10.50 |
February | 24.07 | 12.77 |
March | 24.85 | 16.20 |
April | 25.69 | 20.49 |
May | 26.25 | 24.03 |
June | 26.64 | 27.02 |
July | 26.81 | 28.27 |
August | 26.78 | 28.21 |
September | 26.55 | 26.44 |
October | 25.80 | 20.33 |
November | 25.14 | 17.10 |
December | 24.11 | 12.54 |
Annual Sum or Average | 25.53 | 20.36 |
Minimum of Months | 23.57 | 10.50 |
Maximum of Months | 26.81 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.28 | 10.50 |
February | 22.49 | 12.77 |
March | 23.08 | 16.20 |
April | 23.31 | 20.49 |
May | 23.33 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 23.29 | 20.33 |
November | 23.15 | 17.10 |
December | 22.60 | 12.54 |
Annual Sum or Average | 23.07 | 20.36 |
Minimum of Months | 22.28 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | 10.50 |
February | 21.59 | 12.77 |
March | 21.72 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.74 | 17.10 |
December | 21.63 | 12.54 |
Annual Sum or Average | 21.71 | 20.36 |
Minimum of Months | 21.56 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 10.50 |
February | 21.51 | 12.77 |
March | 22.48 | 16.20 |
April | 23.15 | 20.49 |
May | 23.32 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.33 | 26.44 |
October | 23.12 | 20.33 |
November | 22.66 | 17.10 |
December | 21.50 | 12.54 |
Annual Sum or Average | 22.67 | 20.36 |
Minimum of Months | 20.91 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | 10.50 |
February | 21.52 | 12.77 |
March | 22.93 | 16.20 |
April | 24.56 | 20.49 |
May | 25.86 | 24.03 |
June | 26.75 | 27.02 |
July | 27.13 | 28.27 |
August | 27.04 | 28.21 |
September | 26.51 | 26.44 |
October | 24.82 | 20.33 |
November | 23.52 | 17.10 |
December | 21.61 | 12.54 |
Annual Sum or Average | 24.42 | 20.36 |
Minimum of Months | 20.66 | 10.50 |
Maximum of Months | 27.13 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.08 | 10.50 |
February | 20.30 | 12.77 |
March | 22.20 | 16.20 |
April | 24.78 | 20.49 |
May | 26.94 | 24.03 |
June | 28.58 | 27.02 |
July | 29.24 | 28.27 |
August | 29.13 | 28.21 |
September | 28.14 | 26.44 |
October | 25.33 | 20.33 |
November | 23.21 | 17.10 |
December | 20.51 | 12.54 |
Annual Sum or Average | 24.81 | 20.36 |
Minimum of Months | 19.08 | 10.50 |
Maximum of Months | 29.24 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.19 | 10.50 |
February | 20.36 | 12.77 |
March | 22.07 | 16.20 |
April | 24.43 | 20.49 |
May | 26.25 | 24.03 |
June | 27.59 | 27.02 |
July | 28.17 | 28.27 |
August | 28.14 | 28.21 |
September | 27.50 | 26.44 |
October | 25.03 | 20.33 |
November | 23.04 | 17.10 |
December | 20.53 | 12.54 |
Annual Sum or Average | 24.38 | 20.36 |
Minimum of Months | 19.19 | 10.50 |
Maximum of Months | 28.17 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 10.50 |
February | 22.28 | 12.77 |
March | 22.80 | 16.20 |
April | 23.51 | 20.49 |
May | 23.90 | 24.03 |
June | 24.15 | 27.02 |
July | 24.28 | 28.27 |
August | 24.29 | 28.21 |
September | 24.06 | 26.44 |
October | 23.40 | 20.33 |
November | 22.94 | 17.10 |
December | 22.15 | 12.54 |
Annual Sum or Average | 23.30 | 20.36 |
Minimum of Months | 21.76 | 10.50 |
Maximum of Months | 24.29 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.86 | 10.50 |
February | 19.16 | 12.77 |
March | 20.99 | 16.20 |
April | 23.44 | 20.49 |
May | 25.30 | 24.03 |
June | 26.59 | 27.02 |
July | 27.16 | 28.27 |
August | 27.08 | 28.21 |
September | 26.57 | 26.44 |
October | 23.93 | 20.33 |
November | 21.93 | 17.10 |
December | 19.26 | 12.54 |
Annual Sum or Average | 23.29 | 20.36 |
Minimum of Months | 17.86 | 10.50 |
Maximum of Months | 27.16 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 10.50 |
February | 21.32 | 12.77 |
March | 21.53 | 16.20 |
April | 21.72 | 20.49 |
May | 21.76 | 24.03 |
June | 21.77 | 27.02 |
July | 21.78 | 28.27 |
August | 21.80 | 28.21 |
September | 21.76 | 26.44 |
October | 21.73 | 20.33 |
November | 21.64 | 17.10 |
December | 21.34 | 12.54 |
Annual Sum or Average | 21.61 | 20.36 |
Minimum of Months | 21.12 | 10.50 |
Maximum of Months | 21.80 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.01 | 10.50 |
February | 20.87 | 12.77 |
March | 21.73 | 16.20 |
April | 22.79 | 20.49 |
May | 23.23 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.28 | 26.44 |
October | 22.58 | 20.33 |
November | 21.88 | 17.10 |
December | 20.60 | 12.54 |
Annual Sum or Average | 22.25 | 20.36 |
Minimum of Months | 20.01 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.08 | 10.50 |
February | 20.90 | 12.77 |
March | 21.75 | 16.20 |
April | 22.78 | 20.49 |
May | 23.22 | 24.03 |
June | 23.32 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.27 | 26.44 |
October | 22.57 | 20.33 |
November | 21.88 | 17.10 |
December | 20.64 | 12.54 |
Annual Sum or Average | 22.26 | 20.36 |
Minimum of Months | 20.08 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 10.50 |
February | 21.53 | 12.77 |
March | 21.67 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.72 | 17.10 |
December | 21.57 | 12.54 |
Annual Sum or Average | 21.69 | 20.36 |
Minimum of Months | 21.47 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 10.50 |
February | 20.92 | 12.77 |
March | 21.76 | 16.20 |
April | 22.81 | 20.49 |
May | 23.24 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.30 | 26.44 |
October | 22.69 | 20.33 |
November | 22.00 | 17.10 |
December | 20.73 | 12.54 |
Annual Sum or Average | 22.30 | 20.36 |
Minimum of Months | 20.10 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | 10.50 |
February | 21.20 | 12.77 |
March | 22.07 | 16.20 |
April | 22.95 | 20.49 |
May | 23.27 | 24.03 |
June | 23.33 | 27.02 |
July | 23.33 | 28.27 |
August | 23.33 | 28.21 |
September | 23.31 | 26.44 |
October | 22.85 | 20.33 |
November | 22.27 | 17.10 |
December | 21.09 | 12.54 |
Annual Sum or Average | 22.46 | 20.36 |
Minimum of Months | 20.50 | 10.50 |
Maximum of Months | 23.33 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 10.50 |
February | 21.61 | 12.77 |
March | 21.72 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.74 | 17.10 |
December | 21.64 | 12.54 |
Annual Sum or Average | 21.72 | 20.36 |
Minimum of Months | 21.59 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 10.50 |
February | 22.17 | 12.77 |
March | 23.07 | 16.20 |
April | 24.14 | 20.49 |
May | 24.90 | 24.03 |
June | 25.43 | 27.02 |
July | 25.65 | 28.27 |
August | 25.57 | 28.21 |
September | 25.25 | 26.44 |
October | 24.12 | 20.33 |
November | 23.29 | 17.10 |
December | 22.10 | 12.54 |
Annual Sum or Average | 23.94 | 20.36 |
Minimum of Months | 21.53 | 10.50 |
Maximum of Months | 25.65 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 10.50 |
February | 21.58 | 12.77 |
March | 21.71 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.77 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.74 | 17.10 |
December | 21.62 | 12.54 |
Annual Sum or Average | 21.71 | 20.36 |
Minimum of Months | 21.55 | 10.50 |
Maximum of Months | 21.77 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | 10.50 |
February | 21.60 | 12.77 |
March | 21.72 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.76 | 28.27 |
August | 21.76 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.74 | 17.10 |
December | 21.63 | 12.54 |
Annual Sum or Average | 21.71 | 20.36 |
Minimum of Months | 21.57 | 10.50 |
Maximum of Months | 21.76 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.43 | 10.50 |
February | 21.49 | 12.77 |
March | 21.69 | 16.20 |
April | 21.75 | 20.49 |
May | 21.76 | 24.03 |
June | 21.76 | 27.02 |
July | 21.77 | 28.27 |
August | 21.77 | 28.21 |
September | 21.76 | 26.44 |
October | 21.75 | 20.33 |
November | 21.72 | 17.10 |
December | 21.55 | 12.54 |
Annual Sum or Average | 21.69 | 20.36 |
Minimum of Months | 21.43 | 10.50 |
Maximum of Months | 21.77 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.34 | 10.50 |
February | 21.29 | 12.77 |
March | 22.75 | 16.20 |
April | 24.54 | 20.49 |
May | 25.96 | 24.03 |
June | 26.97 | 27.02 |
July | 27.39 | 28.27 |
August | 27.28 | 28.21 |
September | 26.62 | 26.44 |
October | 24.67 | 20.33 |
November | 23.24 | 17.10 |
December | 21.29 | 12.54 |
Annual Sum or Average | 24.38 | 20.36 |
Minimum of Months | 20.34 | 10.50 |
Maximum of Months | 27.39 | 28.27 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:29
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.57 | 10.50 |
February | 19.94 | 12.77 |
March | 21.94 | 16.20 |
April | 24.77 | 20.49 |
May | 27.06 | 24.03 |
June | 28.85 | 27.02 |
July | 29.56 | 28.27 |
August | 29.45 | 28.21 |
September | 28.30 | 26.44 |
October | 25.19 | 20.33 |
November | 22.87 | 17.10 |
December | 20.05 | 12.54 |
Annual Sum or Average | 24.74 | 20.36 |
Minimum of Months | 18.57 | 10.50 |
Maximum of Months | 29.56 | 28.27 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:29
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.155952E+12 | 117588.618 | 23-JAN-07:15 | 20847.837 | 39740.848 | 9374.638 | 43084.280 | 344.903 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.146111E+12 | 119307.885 | 12-FEB-07:15 | 20847.837 | 39740.848 | 9387.302 | 49112.379 | 211.406 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.164792E+12 | 108552.430 | 19-MAR-06:15 | 20847.837 | 39740.848 | 9374.638 | 33396.371 | 996.624 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.173751E+12 | 109912.178 | 29-APR-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 31205.340 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.196202E+12 | 112620.899 | 12-MAY-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 33914.061 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.207097E+12 | 120497.613 | 17-JUN-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 41790.776 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.221041E+12 | 121935.072 | 15-JUL-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 43228.234 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.220734E+12 | 123171.123 | 12-AUG-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 44464.285 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.201815E+12 | 117688.299 | 23-SEP-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 38981.462 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.179378E+12 | 112351.591 | 08-OCT-07:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 33644.753 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.163387E+12 | 106301.913 | 22-NOV-08:00 | 25182.171 | 43578.554 | 9938.000 | 0.000 | 27595.076 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.158586E+12 | 108516.317 | 26-DEC-07:15 | 20847.837 | 39740.848 | 9374.638 | 33482.609 | 874.273 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.218885E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.146111E+12 | 106301.913 | 20847.837 | 39740.848 | 9374.638 | 0.000 | 211.406 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.221041E+12 | 123171.123 | 25182.171 | 43578.554 | 9938.000 | 49112.379 | 44464.285 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:29
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.876062E+11 | 88694.667 | 21-JAN-09:15 | 46.688 | 40096.028 | 0.000 | 48551.951 | 48551.951 | 48551.951 | 46.688 |
February | 0.787084E+11 | 93314.131 | 11-FEB-10:15 | 9470.653 | 40096.028 | 0.000 | 43747.449 | 43747.449 | 43747.449 | 9470.653 |
March | 0.829354E+11 | 84571.743 | 03-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 44475.715 | 44475.715 | 44475.715 | 0.000 |
April | 0.767660E+11 | 83307.324 | 08-APR-08:15 | 0.000 | 40096.028 | 0.000 | 43211.296 | 43211.296 | 43211.296 | 0.000 |
May | 0.760127E+11 | 82123.978 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 42027.950 | 42027.950 | 42027.950 | 0.000 |
June | 0.709177E+11 | 80979.268 | 02-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 40883.240 | 40883.240 | 40883.240 | 0.000 |
July | 0.718334E+11 | 80263.472 | 04-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 40167.444 | 40167.444 | 40167.444 | 0.000 |
August | 0.721026E+11 | 80675.737 | 26-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 40579.709 | 40579.709 | 40579.709 | 0.000 |
September | 0.714878E+11 | 81431.617 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 41335.589 | 41335.589 | 41335.589 | 0.000 |
October | 0.770734E+11 | 81864.536 | 28-OCT-08:45 | 0.000 | 40096.028 | 0.000 | 41768.508 | 41768.508 | 41768.508 | 0.000 |
November | 0.782039E+11 | 83709.862 | 25-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 43613.834 | 43613.834 | 43613.834 | 0.000 |
December | 0.852195E+11 | 87756.467 | 29-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 47660.439 | 47660.439 | 47660.439 | 0.000 |
Annual Sum or Average | 0.928867E+12 | 0.000 | ||||||||
Minimum of Months | 0.709177E+11 | 80263.472 | 0.000 | 40096.028 | 0.000 | 40167.444 | 40167.444 | 40167.444 | 0.000 | |
Maximum of Months | 0.876062E+11 | 93314.131 | 9470.653 | 40096.028 | 0.000 | 48551.951 | 48551.951 | 48551.951 | 9470.653 |