Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Miami Intl Ap FL USA TMY3 WMO#=722020
Simulation Timestamp: 2015-09-14 08:44:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3217.65 | 801.69 | 863.78 |
Net Site Energy | 3217.65 | 801.69 | 863.78 |
Total Source Energy | 8397.65 | 2092.31 | 2254.35 |
Net Source Energy | 8397.65 | 2092.31 | 2254.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 1.21 | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 807.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 301.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 438.90 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2357.04 | 860.61 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 1.21 | 0.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 807.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 301.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 438.90 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 298.26 | 117.88 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 632.75 | 231.03 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 276.82 | 109.41 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 587.27 | 214.42 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2357.04 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2357.04 | 100.00 |
Total On-Site and Utility Electric Sources | 2357.04 | 100.00 |
Total Electricity End Uses | 2357.04 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 64.50 |
Time Setpoint Not Met During Occupied Cooling | 6465.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6910.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Weather File | Miami Intl Ap FL USA TMY3 WMO#=722020 |
Latitude [deg] | 25.82 |
Longitude [deg] | -80.3 |
Elevation [m] | 11.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00 | 8.70 | Wetbulb [C] | 3.80 | 340.00 |
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 6.70 | 25.30 | Wetbulb [C] | 4.50 | 140.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 8.38 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 175.82 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9286.73 | 6572.29 | 2714.44 | 0.71 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 26830.81 | 18139.86 | 8690.95 | 0.68 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11848.70 | 8010.71 | 3837.99 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16758.51 | 11998.11 | 4760.40 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8958.7 | 3.32 | 11.32 | 12.00 | 11.38 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 25991.0 | 3.06 | 10.43 | 11.07 | 10.68 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11477.8 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16149.1 | 3.30 | 11.27 | 11.94 | 11.30 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.02 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 13188.01 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 514.12 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 514.12 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 682.49 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.94 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.02 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 1935.59 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 682.49 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 2729.97 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2163.60 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 2729.97 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 682.49 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 2056.32 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 2729.78 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.94 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.02 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 1935.59 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 682.49 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 2729.97 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2163.60 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 2729.97 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 682.49 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 2729.78 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 514.08 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 2729.78 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.94 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.02 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2044.94 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 888.83 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 2729.97 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2163.60 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 2729.97 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 682.49 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 2729.78 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 682.45 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 2729.78 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 735.23 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 320.94 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 2810.21 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 11778.92 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 6307.52 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 4711.23 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.42 | 490.14 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.08 | 1231.86 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.48 | 553.89 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.78 | 894.55 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10906.08 | 13087.29 | 0.900 | 1.080 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.09 | 0.01715 |
RESTROOMFLR1 | 801.15 | 961.38 | 0.066 | 0.079 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.34 | 0.01715 |
MEETINGROOMFLR1 | 4813.88 | 5776.65 | 0.398 | 0.477 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM101 | 708.82 | 850.58 | 0.062 | 0.074 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM102 | 566.97 | 680.36 | 0.050 | 0.059 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM103 | 1704.71 | 2045.65 | 0.196 | 0.235 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM104 | 1545.79 | 1854.94 | 0.177 | 0.213 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM105 | 1925.10 | 2310.12 | 0.221 | 0.265 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
EMPLOYEELOUNGEFLR1 | 5704.40 | 6845.28 | 0.471 | 0.565 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
EXERCISECENTERFLR1 | 1415.12 | 1698.14 | 0.117 | 0.140 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 29.80 | 0.01715 |
FRONTOFFICEFLR1 | 4265.34 | 5118.40 | 0.352 | 0.422 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.41 | 0.01715 |
GUESTROOM201 | 1068.01 | 1281.61 | 0.093 | 0.112 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM202_205 | 6467.88 | 7761.45 | 0.742 | 0.890 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM206_208 | 5282.89 | 6339.47 | 0.606 | 0.727 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM209_212 | 6070.20 | 7284.24 | 0.696 | 0.836 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM213 | 1785.50 | 2142.60 | 0.205 | 0.246 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM214 | 1738.04 | 2085.65 | 0.199 | 0.239 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM215_218 | 8848.21 | 10617.85 | 0.773 | 0.928 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM219 | 5695.99 | 6835.19 | 0.653 | 0.784 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM220_223 | 5762.84 | 6915.41 | 0.661 | 0.793 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.41 | 0.01715 |
GUESTROOM224 | 1736.06 | 2083.27 | 0.199 | 0.239 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM301 | 947.44 | 1136.92 | 0.083 | 0.099 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM302_305 | 2487.80 | 2985.36 | 0.217 | 0.261 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM306_308 | 2211.86 | 2654.23 | 0.193 | 0.232 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM309_312 | 6095.67 | 7314.80 | 0.699 | 0.839 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM313 | 836.71 | 1004.06 | 0.073 | 0.088 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.93 | 0.01715 |
GUESTROOM314 | 1672.47 | 2006.97 | 0.192 | 0.230 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM315_318 | 6411.91 | 7694.30 | 0.736 | 0.883 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM319 | 952.66 | 1143.19 | 0.083 | 0.100 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM320_323 | 5601.71 | 6722.06 | 0.643 | 0.771 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM324 | 671.30 | 805.56 | 0.059 | 0.070 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 31.66 | 0.01715 |
GUESTROOM401 | 2321.82 | 2786.19 | 0.266 | 0.320 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.40 | 0.01715 |
GUESTROOM402_405 | 3514.63 | 4217.55 | 0.307 | 0.369 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.40 | 0.01715 |
GUESTROOM406_408 | 3124.68 | 3749.61 | 0.273 | 0.328 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.40 | 0.01715 |
GUESTROOM409_412 | 7375.13 | 8850.16 | 0.846 | 1.015 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 32.40 | 0.01715 |
GUESTROOM413 | 1189.04 | 1426.84 | 0.104 | 0.125 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.26 | 0.01715 |
GUESTROOM414 | 961.92 | 1154.31 | 0.084 | 0.101 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 32.33 | 0.01715 |
GUESTROOM415_418 | 6957.65 | 8349.18 | 0.798 | 0.958 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 31.99 | 0.01715 |
GUESTROOM419 | 1913.12 | 2295.75 | 0.219 | 0.263 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.16 | 0.01715 |
GUESTROOM420_423 | 6822.40 | 8186.88 | 0.783 | 0.939 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 31.99 | 0.01715 |
GUESTROOM424 | 1982.08 | 2378.49 | 0.227 | 0.273 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 32.16 | 0.01715 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
CORRIDORFLR1 | 18741.22 | 22489.47 | 1.547 | 1.857 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.59 | 0.01715 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
CORRIDORFLR2 | 3147.91 | 3777.49 | 0.260 | 0.311 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 31.76 | 0.01715 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
CORRIDORFLR3 | 1923.36 | 2308.03 | 0.159 | 0.190 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 31.76 | 0.01715 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 | |
CORRIDORFLR4 | 2971.90 | 3566.28 | 0.245 | 0.294 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.20 | 0.01715 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB | 33.20 | 0.01715 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1040.35 | 1248.42 | 0.029 | 0.236 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | 8.70 | 0.00699 |
MEETINGROOMFLR1 | 316.87 | 380.24 | 0.009 | 0.126 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 8.70 | 0.00699 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
GUESTROOM102 | 0.00 | 0.00 | 0.000 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
GUESTROOM103 | 315.39 | 378.47 | 0.009 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 8.70 | 0.00699 |
GUESTROOM104 | 243.74 | 292.49 | 0.007 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 8.70 | 0.00699 |
GUESTROOM105 | 180.74 | 216.89 | 0.005 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | 8.70 | 0.00699 |
EMPLOYEELOUNGEFLR1 | 150.64 | 180.77 | 0.004 | 0.051 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70 | 0.00699 |
EXERCISECENTERFLR1 | 65.17 | 78.20 | 0.002 | 0.043 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 8.70 | 0.00699 |
FRONTOFFICEFLR1 | 553.41 | 664.09 | 0.016 | 0.056 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | 8.70 | 0.00699 |
GUESTROOM201 | 113.31 | 135.97 | 0.003 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:15:00 | 8.70 | 0.00699 |
GUESTROOM202_205 | 907.77 | 1089.33 | 0.026 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | 8.70 | 0.00699 |
GUESTROOM206_208 | 645.49 | 774.59 | 0.018 | 0.043 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 8.70 | 0.00699 |
GUESTROOM209_212 | 649.20 | 779.05 | 0.018 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 8.70 | 0.00699 |
GUESTROOM213 | 384.78 | 461.74 | 0.011 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | 8.70 | 0.00699 |
GUESTROOM214 | 297.24 | 356.69 | 0.008 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | 8.70 | 0.00699 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.000 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
GUESTROOM219 | 150.43 | 180.51 | 0.004 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 8.70 | 0.00699 |
GUESTROOM220_223 | 548.38 | 658.05 | 0.015 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 8.70 | 0.00699 |
GUESTROOM224 | 274.74 | 329.69 | 0.008 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 8.70 | 0.00699 |
GUESTROOM301 | 167.18 | 200.62 | 0.004 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | 8.70 | 0.00699 |
GUESTROOM302_305 | 253.30 | 303.96 | 0.007 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | 8.70 | 0.00699 |
GUESTROOM306_308 | 187.07 | 224.49 | 0.005 | 0.043 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 14:30:00 | 8.70 | 0.00699 |
GUESTROOM309_312 | 836.42 | 1003.71 | 0.024 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | 8.70 | 0.00699 |
GUESTROOM313 | 142.07 | 170.49 | 0.004 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 8.70 | 0.00699 |
GUESTROOM314 | 365.15 | 438.18 | 0.010 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:30:00 | 8.70 | 0.00699 |
GUESTROOM315_318 | 837.71 | 1005.26 | 0.024 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:45:00 | 8.70 | 0.00699 |
GUESTROOM319 | 0.00 | 0.00 | 0.000 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
GUESTROOM320_323 | 717.55 | 861.06 | 0.020 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 8.70 | 0.00699 |
GUESTROOM324 | 31.08 | 37.30 | 0.001 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 8.70 | 0.00699 |
GUESTROOM401 | 569.78 | 683.74 | 0.016 | 0.019 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 8.70 | 0.00699 |
GUESTROOM402_405 | 641.02 | 769.22 | 0.017 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | 8.70 | 0.00699 |
GUESTROOM406_408 | 527.73 | 633.28 | 0.014 | 0.043 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | 8.70 | 0.00699 |
GUESTROOM409_412 | 1219.61 | 1463.53 | 0.034 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | 8.70 | 0.00699 |
GUESTROOM413 | 270.24 | 324.29 | 0.007 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 8.70 | 0.00699 |
GUESTROOM414 | 167.63 | 201.16 | 0.004 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 20:00:00 | 8.70 | 0.00699 |
GUESTROOM415_418 | 1147.05 | 1376.46 | 0.032 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | 8.70 | 0.00699 |
GUESTROOM419 | 350.03 | 420.04 | 0.010 | 0.013 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 8.70 | 0.00699 |
GUESTROOM420_423 | 1059.42 | 1271.30 | 0.030 | 0.054 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 8.70 | 0.00699 |
GUESTROOM424 | 441.79 | 530.15 | 0.012 | 0.015 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 8.70 | 0.00699 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
CORRIDORFLR1 | 10407.95 | 12489.54 | 0.294 | 0.352 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8.70 | 0.00699 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
CORRIDORFLR2 | 394.19 | 473.03 | 0.011 | 0.038 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | 8.70 | 0.00699 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
CORRIDORFLR3 | 715.99 | 859.19 | 0.020 | 0.038 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 8.70 | 0.00699 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 | |
CORRIDORFLR4 | 1219.41 | 1463.29 | 0.034 | 0.041 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 8.70 | 0.00699 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | MIAMI INTL AP ANN HTG 99.6% CONDNS DB | 8.70 | 0.00699 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.42 | 0.42 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.08 | 1.08 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.48 | 0.48 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.78 | 0.78 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 7171.75 | 4546.50 | 3749.00 |
RESTROOMFLR1 | 3858.25 | 2911.75 | 889.00 |
MEETINGROOMFLR1 | 3937.00 | 1490.50 | 1279.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 464.00 | 7822.75 | 367.75 |
GUESTROOM104 | 345.25 | 7249.00 | 123.50 |
GUESTROOM105 | 772.50 | 6814.50 | 22.75 |
EMPLOYEELOUNGEFLR1 | 3666.25 | 1883.75 | 534.50 |
EXERCISECENTERFLR1 | 4957.25 | 341.00 | 206.50 |
FRONTOFFICEFLR1 | 6387.50 | 1430.75 | 671.75 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1170.50 | 6857.75 | 98.25 |
GUESTROOM206_208 | 1148.50 | 6807.50 | 53.50 |
GUESTROOM209_212 | 971.25 | 7182.75 | 289.00 |
GUESTROOM213 | 676.00 | 7206.75 | 157.00 |
GUESTROOM214 | 1003.00 | 6806.75 | 35.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 6553.50 | 3389.00 | 1978.50 |
GUESTROOM220_223 | 1307.50 | 6713.75 | 79.00 |
GUESTROOM224 | 1025.00 | 6777.50 | 15.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1020.75 | 7393.00 | 434.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 1056.25 | 6826.75 | 41.00 |
GUESTROOM315_318 | 1436.75 | 6644.75 | 61.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1191.25 | 6914.75 | 160.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1810.00 | 6701.25 | 199.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1907.00 | 6510.25 | 71.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2017.75 | 6352.25 | 41.25 |
GUESTROOM419 | 1734.00 | 6461.00 | 22.00 |
GUESTROOM420_423 | 1994.00 | 6375.50 | 48.00 |
GUESTROOM424 | 1742.25 | 6482.75 | 17.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 8220.00 | 8733.25 | 6910.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 2445.75 | 0.00 | 2445.75 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 89.25 | 0.00 | 89.25 |
GUESTROOM104 | 0.00 | 89.25 | 0.00 | 89.25 |
GUESTROOM105 | 0.00 | 89.75 | 0.00 | 89.75 |
EMPLOYEELOUNGEFLR1 | 103.75 | 1104.75 | 64.50 | 602.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 84.00 | 0.00 | 84.00 |
GUESTROOM206_208 | 0.00 | 88.00 | 0.00 | 88.00 |
GUESTROOM209_212 | 0.00 | 83.50 | 0.00 | 83.50 |
GUESTROOM213 | 0.00 | 84.50 | 0.00 | 84.50 |
GUESTROOM214 | 0.00 | 82.50 | 0.00 | 82.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 5569.00 | 0.00 | 5569.00 |
GUESTROOM220_223 | 0.00 | 80.50 | 0.00 | 80.50 |
GUESTROOM224 | 0.00 | 81.75 | 0.00 | 81.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 83.25 | 0.00 | 83.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 82.00 | 0.00 | 82.00 |
GUESTROOM315_318 | 0.00 | 81.25 | 0.00 | 81.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 79.00 | 0.00 | 79.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 205.25 | 0.00 | 205.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 89.25 | 0.00 | 89.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 83.50 | 0.00 | 83.50 |
GUESTROOM419 | 0.00 | 89.50 | 0.00 | 89.50 |
GUESTROOM420_423 | 0.00 | 83.25 | 0.00 | 83.25 |
GUESTROOM424 | 0.00 | 97.50 | 0.00 | 97.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 1.25 | 7635.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 2459.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 173.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 1654.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 105.00 | 8199.00 | 64.50 | 6465.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:56
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.422233 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.08 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.784619 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.02 |
CORRIDORFLR1 PTAC HEATING COIL | 13188.01 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 514.12 |
102 PTAC HEATING COIL | 514.12 |
103 PTAC HEATING COIL | 682.49 |
104 PTAC HEATING COIL | 682.45 |
105 PTAC HEATING COIL | 682.45 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 320.94 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.02 |
CORRIDORFLR2 PTAC HEATING COIL | 1935.59 |
201 PTAC HEATING COIL | 682.49 |
202_205 PTAC HEATING COIL | 2729.97 |
206_208 PTAC HEATING COIL | 2163.60 |
209_212 PTAC HEATING COIL | 2729.97 |
213 PTAC HEATING COIL | 682.49 |
214 PTAC HEATING COIL | 682.45 |
215_218 PTAC HEATING COIL | 2056.32 |
219 PTAC HEATING COIL | 682.45 |
220_223 PTAC HEATING COIL | 2729.78 |
224 PTAC HEATING COIL | 682.45 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 320.94 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.02 |
CORRIDORFLR3 PTAC HEATING COIL | 1935.59 |
301 PTAC HEATING COIL | 682.49 |
302_305 PTAC HEATING COIL | 2729.97 |
306_308 PTAC HEATING COIL | 2163.60 |
309_312 PTAC HEATING COIL | 2729.97 |
313 PTAC HEATING COIL | 682.49 |
314 PTAC HEATING COIL | 682.45 |
315_318 PTAC HEATING COIL | 2729.78 |
319 PTAC HEATING COIL | 514.08 |
320_323 PTAC HEATING COIL | 2729.78 |
324 PTAC HEATING COIL | 682.45 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 320.94 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.02 |
CORRIDORFLR4 PTAC HEATING COIL | 2044.94 |
401 PTAC HEATING COIL | 888.83 |
402_405 PTAC HEATING COIL | 2729.97 |
406_408 PTAC HEATING COIL | 2163.60 |
409_412 PTAC HEATING COIL | 2729.97 |
413 PTAC HEATING COIL | 682.49 |
414 PTAC HEATING COIL | 682.45 |
415_418 PTAC HEATING COIL | 2729.78 |
419 PTAC HEATING COIL | 682.45 |
420_423 PTAC HEATING COIL | 2729.78 |
424 PTAC HEATING COIL | 735.23 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 320.94 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.707708 | 0.422233 | 9286.73 |
SAC_FRONTLOUNGE COOLING COIL | 0.676083 | 1.08 | 26830.81 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.477147 | 11848.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.715941 | 0.784619 | 16758.51 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.08 |
RESTROOMFLR1 DIRECT AIR | 0.079292 |
MEETINGROOMFLR1 DIRECT AIR | 0.477147 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.565192 |
EXERCISECENTERFLR1 DIRECT AIR | 0.140135 |
FRONTOFFICEFLR1 DIRECT AIR | 0.422233 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.422233 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.08 |
SAC_MEETINGROOM MAIN BRANCH | 0.477147 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.784619 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.422233 |
SAC_FRONTLOUNGE | 1.08 |
SAC_MEETINGROOM | 0.477147 |
SAC_EXC_EMPLGE_RESTRM | 0.784619 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.422233 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.08 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.477147 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.784619 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.422233 | 0.422233 | 0.422233 | 0.422233 | 2810.21 | 9286.73 | 1.00 |
SAC_FRONTLOUNGE | 1.08 | 1.08 | 1.08 | 1.08 | 11778.92 | 26830.81 | 1.00 |
SAC_MEETINGROOM | 0.477147 | 0.477147 | 0.477147 | 0.477147 | 6307.52 | 11848.70 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.784619 | 0.784619 | 0.784619 | 0.784619 | 4711.23 | 16758.51 | 0.178603 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 2810.21 |
SAC_FRONTLOUNGE HEATING COIL | 11778.92 |
SAC_MEETINGROOM HEATING COIL | 6307.52 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 4711.23 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.477147 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 19.42 |
February | 23.96 | 20.87 |
March | 24.16 | 21.57 |
April | 25.12 | 24.11 |
May | 25.82 | 26.41 |
June | 26.24 | 27.68 |
July | 26.40 | 28.13 |
August | 26.31 | 27.97 |
September | 26.44 | 27.49 |
October | 26.06 | 26.35 |
November | 25.05 | 23.59 |
December | 24.01 | 20.30 |
Annual Sum or Average | 25.29 | 24.51 |
Minimum of Months | 23.89 | 19.42 |
Maximum of Months | 26.44 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.03 | 19.42 |
February | 25.33 | 20.87 |
March | 25.55 | 21.57 |
April | 26.20 | 24.11 |
May | 26.96 | 26.41 |
June | 27.42 | 27.68 |
July | 27.62 | 28.13 |
August | 27.52 | 27.97 |
September | 27.39 | 27.49 |
October | 26.96 | 26.35 |
November | 26.15 | 23.59 |
December | 25.29 | 20.30 |
Annual Sum or Average | 26.46 | 24.51 |
Minimum of Months | 25.03 | 19.42 |
Maximum of Months | 27.62 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 19.42 |
February | 23.37 | 20.87 |
March | 23.59 | 21.57 |
April | 24.55 | 24.11 |
May | 25.26 | 26.41 |
June | 25.61 | 27.68 |
July | 25.75 | 28.13 |
August | 25.71 | 27.97 |
September | 25.80 | 27.49 |
October | 25.45 | 26.35 |
November | 24.45 | 23.59 |
December | 23.40 | 20.30 |
Annual Sum or Average | 24.69 | 24.51 |
Minimum of Months | 23.20 | 19.42 |
Maximum of Months | 25.80 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 19.42 |
February | 23.70 | 20.87 |
March | 23.76 | 21.57 |
April | 23.88 | 24.11 |
May | 23.89 | 26.41 |
June | 23.89 | 27.68 |
July | 23.89 | 28.13 |
August | 23.89 | 27.97 |
September | 23.89 | 27.49 |
October | 23.89 | 26.35 |
November | 23.83 | 23.59 |
December | 23.68 | 20.30 |
Annual Sum or Average | 23.82 | 24.51 |
Minimum of Months | 23.65 | 19.42 |
Maximum of Months | 23.89 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 19.42 |
February | 23.45 | 20.87 |
March | 23.51 | 21.57 |
April | 23.63 | 24.11 |
May | 23.69 | 26.41 |
June | 23.71 | 27.68 |
July | 23.73 | 28.13 |
August | 23.74 | 27.97 |
September | 23.71 | 27.49 |
October | 23.67 | 26.35 |
November | 23.57 | 23.59 |
December | 23.45 | 20.30 |
Annual Sum or Average | 23.60 | 24.51 |
Minimum of Months | 23.39 | 19.42 |
Maximum of Months | 23.74 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.71 | 19.42 |
February | 23.73 | 20.87 |
March | 23.79 | 21.57 |
April | 23.88 | 24.11 |
May | 23.89 | 26.41 |
June | 23.89 | 27.68 |
July | 23.89 | 28.13 |
August | 23.89 | 27.97 |
September | 23.89 | 27.49 |
October | 23.89 | 26.35 |
November | 23.84 | 23.59 |
December | 23.74 | 20.30 |
Annual Sum or Average | 23.84 | 24.51 |
Minimum of Months | 23.71 | 19.42 |
Maximum of Months | 23.89 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.38 | 19.42 |
February | 26.53 | 20.87 |
March | 26.70 | 21.57 |
April | 27.03 | 24.11 |
May | 27.21 | 26.41 |
June | 27.30 | 27.68 |
July | 27.38 | 28.13 |
August | 27.33 | 27.97 |
September | 27.28 | 27.49 |
October | 27.13 | 26.35 |
November | 26.81 | 23.59 |
December | 26.50 | 20.30 |
Annual Sum or Average | 26.97 | 24.51 |
Minimum of Months | 26.38 | 19.42 |
Maximum of Months | 27.38 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 19.42 |
February | 23.08 | 20.87 |
March | 23.15 | 21.57 |
April | 23.32 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.25 | 23.59 |
December | 23.05 | 20.30 |
Annual Sum or Average | 23.24 | 24.51 |
Minimum of Months | 22.99 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 19.42 |
February | 22.97 | 20.87 |
March | 23.07 | 21.57 |
April | 23.31 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.20 | 23.59 |
December | 22.92 | 20.30 |
Annual Sum or Average | 23.19 | 24.51 |
Minimum of Months | 22.82 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 19.42 |
February | 21.73 | 20.87 |
March | 21.72 | 21.57 |
April | 21.75 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.75 | 23.59 |
December | 21.73 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.72 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.76 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.90 | 19.42 |
February | 22.80 | 20.87 |
March | 22.72 | 21.57 |
April | 22.54 | 24.11 |
May | 22.38 | 26.41 |
June | 22.28 | 27.68 |
July | 22.21 | 28.13 |
August | 22.29 | 27.97 |
September | 22.30 | 27.49 |
October | 22.44 | 26.35 |
November | 22.66 | 23.59 |
December | 22.85 | 20.30 |
Annual Sum or Average | 22.53 | 24.51 |
Minimum of Months | 22.21 | 19.42 |
Maximum of Months | 22.90 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 52.03 | 19.42 |
February | 51.99 | 20.87 |
March | 52.22 | 21.57 |
April | 52.67 | 24.11 |
May | 52.95 | 26.41 |
June | 53.28 | 27.68 |
July | 53.47 | 28.13 |
August | 53.23 | 27.97 |
September | 53.26 | 27.49 |
October | 52.95 | 26.35 |
November | 52.46 | 23.59 |
December | 52.06 | 20.30 |
Annual Sum or Average | 52.72 | 24.51 |
Minimum of Months | 51.99 | 19.42 |
Maximum of Months | 53.47 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 70.64 | 19.42 |
February | 70.25 | 20.87 |
March | 70.47 | 21.57 |
April | 71.12 | 24.11 |
May | 71.45 | 26.41 |
June | 71.99 | 27.68 |
July | 72.36 | 28.13 |
August | 72.09 | 27.97 |
September | 72.07 | 27.49 |
October | 71.70 | 26.35 |
November | 71.00 | 23.59 |
December | 70.63 | 20.30 |
Annual Sum or Average | 71.32 | 24.51 |
Minimum of Months | 70.25 | 19.42 |
Maximum of Months | 72.36 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.84 | 19.42 |
February | 23.84 | 20.87 |
March | 23.86 | 21.57 |
April | 23.89 | 24.11 |
May | 23.89 | 26.41 |
June | 23.89 | 27.68 |
July | 23.89 | 28.13 |
August | 23.89 | 27.97 |
September | 23.89 | 27.49 |
October | 23.89 | 26.35 |
November | 23.88 | 23.59 |
December | 23.83 | 20.30 |
Annual Sum or Average | 23.87 | 24.51 |
Minimum of Months | 23.83 | 19.42 |
Maximum of Months | 23.89 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 19.42 |
February | 23.85 | 20.87 |
March | 23.87 | 21.57 |
April | 23.89 | 24.11 |
May | 23.89 | 26.41 |
June | 23.89 | 27.68 |
July | 23.89 | 28.13 |
August | 23.89 | 27.97 |
September | 23.89 | 27.49 |
October | 23.89 | 26.35 |
November | 23.88 | 23.59 |
December | 23.85 | 20.30 |
Annual Sum or Average | 23.88 | 24.51 |
Minimum of Months | 23.85 | 19.42 |
Maximum of Months | 23.89 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.48 | 19.42 |
February | 23.70 | 20.87 |
March | 24.12 | 21.57 |
April | 25.49 | 24.11 |
May | 26.57 | 26.41 |
June | 27.23 | 27.68 |
July | 27.44 | 28.13 |
August | 27.16 | 27.97 |
September | 27.04 | 27.49 |
October | 26.35 | 26.35 |
November | 25.02 | 23.59 |
December | 23.69 | 20.30 |
Annual Sum or Average | 25.62 | 24.51 |
Minimum of Months | 23.48 | 19.42 |
Maximum of Months | 27.44 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.00 | 19.42 |
February | 24.14 | 20.87 |
March | 24.43 | 21.57 |
April | 25.19 | 24.11 |
May | 25.75 | 26.41 |
June | 26.12 | 27.68 |
July | 26.25 | 28.13 |
August | 26.06 | 27.97 |
September | 26.01 | 27.49 |
October | 25.61 | 26.35 |
November | 24.86 | 23.59 |
December | 24.10 | 20.30 |
Annual Sum or Average | 25.22 | 24.51 |
Minimum of Months | 24.00 | 19.42 |
Maximum of Months | 26.25 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.60 | 19.42 |
February | 24.56 | 20.87 |
March | 24.78 | 21.57 |
April | 25.97 | 24.11 |
May | 26.77 | 26.41 |
June | 27.36 | 27.68 |
July | 27.60 | 28.13 |
August | 27.45 | 27.97 |
September | 27.60 | 27.49 |
October | 27.14 | 26.35 |
November | 25.89 | 23.59 |
December | 24.69 | 20.30 |
Annual Sum or Average | 26.21 | 24.51 |
Minimum of Months | 24.56 | 19.42 |
Maximum of Months | 27.60 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 19.42 |
February | 23.85 | 20.87 |
March | 23.87 | 21.57 |
April | 23.94 | 24.11 |
May | 24.08 | 26.41 |
June | 24.26 | 27.68 |
July | 24.34 | 28.13 |
August | 24.30 | 27.97 |
September | 24.26 | 27.49 |
October | 24.07 | 26.35 |
November | 23.93 | 23.59 |
December | 23.86 | 20.30 |
Annual Sum or Average | 24.06 | 24.51 |
Minimum of Months | 23.85 | 19.42 |
Maximum of Months | 24.34 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.60 | 19.42 |
February | 23.73 | 20.87 |
March | 23.98 | 21.57 |
April | 25.17 | 24.11 |
May | 26.00 | 26.41 |
June | 26.48 | 27.68 |
July | 26.68 | 28.13 |
August | 26.60 | 27.97 |
September | 26.70 | 27.49 |
October | 26.27 | 26.35 |
November | 25.04 | 23.59 |
December | 23.80 | 20.30 |
Annual Sum or Average | 25.34 | 24.51 |
Minimum of Months | 23.60 | 19.42 |
Maximum of Months | 26.70 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 19.42 |
February | 22.99 | 20.87 |
March | 23.08 | 21.57 |
April | 23.32 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.23 | 23.59 |
December | 22.93 | 20.30 |
Annual Sum or Average | 23.20 | 24.51 |
Minimum of Months | 22.89 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.75 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 19.42 |
February | 21.74 | 20.87 |
March | 21.73 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.75 | 23.59 |
December | 21.74 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.73 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.76 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 19.42 |
February | 23.33 | 20.87 |
March | 23.33 | 21.57 |
April | 23.33 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.33 | 23.59 |
December | 23.33 | 20.30 |
Annual Sum or Average | 23.33 | 24.51 |
Minimum of Months | 23.33 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 32.89 | 19.42 |
February | 32.76 | 20.87 |
March | 32.96 | 21.57 |
April | 33.47 | 24.11 |
May | 33.81 | 26.41 |
June | 34.20 | 27.68 |
July | 34.40 | 28.13 |
August | 34.23 | 27.97 |
September | 34.20 | 27.49 |
October | 33.86 | 26.35 |
November | 33.29 | 23.59 |
December | 32.90 | 20.30 |
Annual Sum or Average | 33.58 | 24.51 |
Minimum of Months | 32.76 | 19.42 |
Maximum of Months | 34.40 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 19.42 |
February | 22.64 | 20.87 |
March | 22.78 | 21.57 |
April | 23.04 | 24.11 |
May | 23.48 | 26.41 |
June | 23.88 | 27.68 |
July | 23.99 | 28.13 |
August | 23.90 | 27.97 |
September | 23.81 | 27.49 |
October | 23.44 | 26.35 |
November | 23.02 | 23.59 |
December | 22.66 | 20.30 |
Annual Sum or Average | 23.27 | 24.51 |
Minimum of Months | 22.57 | 19.42 |
Maximum of Months | 23.99 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.76 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.76 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.14 | 19.42 |
February | 24.27 | 20.87 |
March | 24.63 | 21.57 |
April | 25.62 | 24.11 |
May | 26.31 | 26.41 |
June | 26.80 | 27.68 |
July | 26.97 | 28.13 |
August | 26.71 | 27.97 |
September | 26.65 | 27.49 |
October | 26.14 | 26.35 |
November | 25.19 | 23.59 |
December | 24.24 | 20.30 |
Annual Sum or Average | 25.65 | 24.51 |
Minimum of Months | 24.14 | 19.42 |
Maximum of Months | 26.97 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.01 | 19.42 |
February | 24.19 | 20.87 |
March | 24.70 | 21.57 |
April | 26.43 | 24.11 |
May | 27.72 | 26.41 |
June | 28.65 | 27.68 |
July | 28.98 | 28.13 |
August | 28.55 | 27.97 |
September | 28.41 | 27.49 |
October | 27.52 | 26.35 |
November | 25.85 | 23.59 |
December | 24.26 | 20.30 |
Annual Sum or Average | 26.62 | 24.51 |
Minimum of Months | 24.01 | 19.42 |
Maximum of Months | 28.98 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.58 | 19.42 |
February | 24.55 | 20.87 |
March | 24.81 | 21.57 |
April | 26.12 | 24.11 |
May | 26.98 | 26.41 |
June | 27.61 | 27.68 |
July | 27.88 | 28.13 |
August | 27.70 | 27.97 |
September | 27.84 | 27.49 |
October | 27.34 | 26.35 |
November | 25.99 | 23.59 |
December | 24.68 | 20.30 |
Annual Sum or Average | 26.35 | 24.51 |
Minimum of Months | 24.55 | 19.42 |
Maximum of Months | 27.88 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.69 | 19.42 |
February | 23.71 | 20.87 |
March | 23.77 | 21.57 |
April | 23.89 | 24.11 |
May | 23.89 | 26.41 |
June | 23.90 | 27.68 |
July | 23.93 | 28.13 |
August | 23.92 | 27.97 |
September | 23.91 | 27.49 |
October | 23.89 | 26.35 |
November | 23.84 | 23.59 |
December | 23.69 | 20.30 |
Annual Sum or Average | 23.84 | 24.51 |
Minimum of Months | 23.69 | 19.42 |
Maximum of Months | 23.93 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 19.42 |
February | 23.73 | 20.87 |
March | 24.04 | 21.57 |
April | 25.39 | 24.11 |
May | 26.29 | 26.41 |
June | 26.83 | 27.68 |
July | 27.07 | 28.13 |
August | 26.95 | 27.97 |
September | 27.04 | 27.49 |
October | 26.56 | 26.35 |
November | 25.19 | 23.59 |
December | 23.80 | 20.30 |
Annual Sum or Average | 25.55 | 24.51 |
Minimum of Months | 23.57 | 19.42 |
Maximum of Months | 27.07 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.65 | 19.42 |
February | 22.84 | 20.87 |
March | 22.97 | 21.57 |
April | 23.31 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.17 | 23.59 |
December | 22.71 | 20.30 |
Annual Sum or Average | 23.14 | 24.51 |
Minimum of Months | 22.65 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 19.42 |
February | 23.01 | 20.87 |
March | 23.10 | 21.57 |
April | 23.33 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.24 | 23.59 |
December | 22.93 | 20.30 |
Annual Sum or Average | 23.21 | 24.51 |
Minimum of Months | 22.89 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 19.42 |
February | 23.02 | 20.87 |
March | 23.11 | 21.57 |
April | 23.32 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.23 | 23.59 |
December | 22.94 | 20.30 |
Annual Sum or Average | 23.21 | 24.51 |
Minimum of Months | 22.89 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 19.42 |
February | 21.75 | 20.87 |
March | 21.74 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.75 | 23.59 |
December | 21.74 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.74 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.93 | 19.42 |
February | 23.02 | 20.87 |
March | 23.09 | 21.57 |
April | 23.33 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.24 | 23.59 |
December | 22.96 | 20.30 |
Annual Sum or Average | 23.21 | 24.51 |
Minimum of Months | 22.93 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.76 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.51 | 19.42 |
February | 25.54 | 20.87 |
March | 25.76 | 21.57 |
April | 26.29 | 24.11 |
May | 26.60 | 26.41 |
June | 26.83 | 27.68 |
July | 26.94 | 28.13 |
August | 26.81 | 27.97 |
September | 26.79 | 27.49 |
October | 26.54 | 26.35 |
November | 26.02 | 23.59 |
December | 25.53 | 20.30 |
Annual Sum or Average | 26.27 | 24.51 |
Minimum of Months | 25.51 | 19.42 |
Maximum of Months | 26.94 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 19.42 |
February | 23.29 | 20.87 |
March | 23.31 | 21.57 |
April | 23.33 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.32 | 23.59 |
December | 23.29 | 20.30 |
Annual Sum or Average | 23.32 | 24.51 |
Minimum of Months | 23.29 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.07 | 19.42 |
February | 23.12 | 20.87 |
March | 23.20 | 21.57 |
April | 23.33 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.27 | 23.59 |
December | 23.07 | 20.30 |
Annual Sum or Average | 23.26 | 24.51 |
Minimum of Months | 23.07 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.08 | 19.42 |
February | 24.25 | 20.87 |
March | 24.68 | 21.57 |
April | 25.82 | 24.11 |
May | 26.58 | 26.41 |
June | 27.12 | 27.68 |
July | 27.32 | 28.13 |
August | 27.01 | 27.97 |
September | 26.94 | 27.49 |
October | 26.38 | 26.35 |
November | 25.30 | 23.59 |
December | 24.20 | 20.30 |
Annual Sum or Average | 25.82 | 24.51 |
Minimum of Months | 24.08 | 19.42 |
Maximum of Months | 27.32 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.98 | 19.42 |
February | 24.18 | 20.87 |
March | 24.74 | 21.57 |
April | 26.63 | 24.11 |
May | 27.99 | 26.41 |
June | 29.00 | 27.68 |
July | 29.38 | 28.13 |
August | 28.89 | 27.97 |
September | 28.75 | 27.49 |
October | 27.78 | 26.35 |
November | 25.98 | 23.59 |
December | 24.25 | 20.30 |
Annual Sum or Average | 26.81 | 24.51 |
Minimum of Months | 23.98 | 19.42 |
Maximum of Months | 29.38 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.39 | 19.42 |
February | 24.48 | 20.87 |
March | 24.83 | 21.57 |
April | 26.32 | 24.11 |
May | 27.30 | 26.41 |
June | 28.00 | 27.68 |
July | 28.34 | 28.13 |
August | 28.07 | 27.97 |
September | 28.19 | 27.49 |
October | 27.56 | 26.35 |
November | 26.05 | 23.59 |
December | 24.55 | 20.30 |
Annual Sum or Average | 26.52 | 24.51 |
Minimum of Months | 24.39 | 19.42 |
Maximum of Months | 28.34 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 19.42 |
February | 23.47 | 20.87 |
March | 23.62 | 21.57 |
April | 23.97 | 24.11 |
May | 24.13 | 26.41 |
June | 24.21 | 27.68 |
July | 24.33 | 28.13 |
August | 24.24 | 27.97 |
September | 24.21 | 27.49 |
October | 24.07 | 26.35 |
November | 23.78 | 23.59 |
December | 23.43 | 20.30 |
Annual Sum or Average | 23.90 | 24.51 |
Minimum of Months | 23.32 | 19.42 |
Maximum of Months | 24.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.36 | 19.42 |
February | 23.66 | 20.87 |
March | 24.04 | 21.57 |
April | 25.54 | 24.11 |
May | 26.56 | 26.41 |
June | 27.15 | 27.68 |
July | 27.45 | 28.13 |
August | 27.24 | 27.97 |
September | 27.32 | 27.49 |
October | 26.72 | 26.35 |
November | 25.22 | 23.59 |
December | 23.65 | 20.30 |
Annual Sum or Average | 25.67 | 24.51 |
Minimum of Months | 23.36 | 19.42 |
Maximum of Months | 27.45 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 19.42 |
February | 21.72 | 20.87 |
March | 21.70 | 21.57 |
April | 21.76 | 24.11 |
May | 21.77 | 26.41 |
June | 21.78 | 27.68 |
July | 21.80 | 28.13 |
August | 21.79 | 27.97 |
September | 21.78 | 27.49 |
October | 21.76 | 26.35 |
November | 21.75 | 23.59 |
December | 21.70 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.70 | 19.42 |
Maximum of Months | 21.80 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.51 | 19.42 |
February | 22.76 | 20.87 |
March | 22.93 | 21.57 |
April | 23.30 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.13 | 23.59 |
December | 22.65 | 20.30 |
Annual Sum or Average | 23.11 | 24.51 |
Minimum of Months | 22.51 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.50 | 19.42 |
February | 22.75 | 20.87 |
March | 22.93 | 21.57 |
April | 23.29 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.12 | 23.59 |
December | 22.65 | 20.30 |
Annual Sum or Average | 23.10 | 24.51 |
Minimum of Months | 22.50 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 19.42 |
February | 21.75 | 20.87 |
March | 21.74 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.75 | 23.59 |
December | 21.74 | 20.30 |
Annual Sum or Average | 21.75 | 24.51 |
Minimum of Months | 21.74 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.61 | 19.42 |
February | 22.80 | 20.87 |
March | 22.95 | 21.57 |
April | 23.30 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.14 | 23.59 |
December | 22.72 | 20.30 |
Annual Sum or Average | 23.13 | 24.51 |
Minimum of Months | 22.61 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.82 | 19.42 |
February | 22.93 | 20.87 |
March | 23.06 | 21.57 |
April | 23.31 | 24.11 |
May | 23.33 | 26.41 |
June | 23.33 | 27.68 |
July | 23.33 | 28.13 |
August | 23.33 | 27.97 |
September | 23.33 | 27.49 |
October | 23.33 | 26.35 |
November | 23.19 | 23.59 |
December | 22.87 | 20.30 |
Annual Sum or Average | 23.18 | 24.51 |
Minimum of Months | 22.82 | 19.42 |
Maximum of Months | 23.33 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.78 | 19.42 |
February | 24.00 | 20.87 |
March | 24.31 | 21.57 |
April | 25.00 | 24.11 |
May | 25.45 | 26.41 |
June | 25.68 | 27.68 |
July | 25.82 | 28.13 |
August | 25.62 | 27.97 |
September | 25.58 | 27.49 |
October | 25.22 | 26.35 |
November | 24.56 | 23.59 |
December | 23.87 | 20.30 |
Annual Sum or Average | 24.91 | 24.51 |
Minimum of Months | 23.78 | 19.42 |
Maximum of Months | 25.82 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.76 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.76 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.76 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 19.42 |
February | 21.75 | 20.87 |
March | 21.75 | 21.57 |
April | 21.76 | 24.11 |
May | 21.76 | 26.41 |
June | 21.76 | 27.68 |
July | 21.77 | 28.13 |
August | 21.76 | 27.97 |
September | 21.76 | 27.49 |
October | 21.76 | 26.35 |
November | 21.76 | 23.59 |
December | 21.75 | 20.30 |
Annual Sum or Average | 21.76 | 24.51 |
Minimum of Months | 21.75 | 19.42 |
Maximum of Months | 21.77 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 19.42 |
February | 24.17 | 20.87 |
March | 24.65 | 21.57 |
April | 25.90 | 24.11 |
May | 26.75 | 26.41 |
June | 27.31 | 27.68 |
July | 27.57 | 28.13 |
August | 27.17 | 27.97 |
September | 27.09 | 27.49 |
October | 26.42 | 26.35 |
November | 25.25 | 23.59 |
December | 24.04 | 20.30 |
Annual Sum or Average | 25.86 | 24.51 |
Minimum of Months | 23.87 | 19.42 |
Maximum of Months | 27.57 | 28.13 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:56
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.76 | 19.42 |
February | 24.08 | 20.87 |
March | 24.70 | 21.57 |
April | 26.72 | 24.11 |
May | 28.18 | 26.41 |
June | 29.23 | 27.68 |
July | 29.68 | 28.13 |
August | 29.09 | 27.97 |
September | 28.94 | 27.49 |
October | 27.86 | 26.35 |
November | 25.95 | 23.59 |
December | 24.07 | 20.30 |
Annual Sum or Average | 26.87 | 24.51 |
Minimum of Months | 23.76 | 19.42 |
Maximum of Months | 29.68 | 28.13 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:56
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.172900E+12 | 108473.734 | 07-JAN-08:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 29834.026 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.161403E+12 | 111467.270 | 11-FEB-08:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 32827.562 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.184020E+12 | 111411.719 | 04-MAR-08:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 32772.010 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.189080E+12 | 114187.452 | 14-APR-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 35547.743 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.209983E+12 | 117442.720 | 20-MAY-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 38803.011 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.211944E+12 | 122252.499 | 09-JUN-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 43612.791 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.222104E+12 | 121914.753 | 14-JUL-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 43275.045 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.220442E+12 | 123087.848 | 05-AUG-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 44448.140 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.210957E+12 | 119797.893 | 09-SEP-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 41158.184 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.208636E+12 | 118269.906 | 13-OCT-07:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 39630.197 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.187281E+12 | 114978.361 | 10-NOV-08:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 36338.653 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.178292E+12 | 114382.068 | 09-DEC-08:00 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 35742.359 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.235704E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.161403E+12 | 108473.734 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 29834.026 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.222104E+12 | 123087.848 | 25182.171 | 43578.554 | 9870.871 | 0.000 | 44448.140 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:56
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.763760E+11 | 81807.200 | 27-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 41711.172 | 41711.172 | 41711.172 | 0.000 |
February | 0.687204E+11 | 81884.843 | 11-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 41788.815 | 41788.815 | 41788.815 | 0.000 |
March | 0.749652E+11 | 81404.557 | 17-MAR-08:15 | 0.000 | 40096.028 | 0.000 | 41308.529 | 41308.529 | 41308.529 | 0.000 |
April | 0.709347E+11 | 80835.269 | 14-APR-08:15 | 0.000 | 40096.028 | 0.000 | 40739.241 | 40739.241 | 40739.241 | 0.000 |
May | 0.716521E+11 | 80463.199 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 40367.170 | 40367.170 | 40367.170 | 0.000 |
June | 0.680737E+11 | 80009.707 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 39913.679 | 39913.679 | 39913.679 | 0.000 |
July | 0.697947E+11 | 79695.886 | 21-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 39599.858 | 39599.858 | 39599.858 | 0.000 |
August | 0.701708E+11 | 79685.217 | 04-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 39589.189 | 39589.189 | 39589.189 | 0.000 |
September | 0.689523E+11 | 80372.826 | 22-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 40276.798 | 40276.798 | 40276.798 | 0.000 |
October | 0.729051E+11 | 80554.583 | 13-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 40458.555 | 40458.555 | 40458.555 | 0.000 |
November | 0.721569E+11 | 81309.058 | 25-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 41213.030 | 41213.030 | 41213.030 | 0.000 |
December | 0.759063E+11 | 81928.324 | 29-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 41832.296 | 41832.296 | 41832.296 | 0.000 |
Annual Sum or Average | 0.860608E+12 | 0.000 | ||||||||
Minimum of Months | 0.680737E+11 | 79685.217 | 0.000 | 40096.028 | 0.000 | 39589.189 | 39589.189 | 39589.189 | 0.000 | |
Maximum of Months | 0.763760E+11 | 81928.324 | 0.000 | 40096.028 | 0.000 | 41832.296 | 41832.296 | 41832.296 | 0.000 |