Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Helena Regional Airport MT USA TMY3 WMO#=727720

Simulation Timestamp: 2015-09-14 08:44:21


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3183.70 793.23 854.66
Net Site Energy 3183.70 793.23 854.66
Total Source Energy 7633.24 1901.85 2049.14
Net Source Energy 7633.24 1901.85 2049.14


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 248.36 78.36 0.00 0.00 0.00 0.00
Cooling 205.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.69 0.00 0.00 0.00 0.00 0.00
Interior Equipment 601.95 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 308.16 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 676.11 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2007.74 1175.96 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 248.36 78.36 0.00 0.00 0.00 0.00
Cooling General 205.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.69 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 573.47 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 308.16 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 676.11 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 172.83 0.00 0.00 0.00 0.00 0.00
HVAC 204.55 202.54 0.00 0.00 0.00 0.69
Other 161.59 113.15 0.00 0.00 0.00 0.00
Total 538.98 315.69 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.41 0.00 0.00 0.00 0.00 0.00
HVAC 189.85 187.98 0.00 0.00 0.00 0.64
Other 149.98 105.02 0.00 0.00 0.00 0.00
Total 500.24 293.00 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2007.74 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2007.74 100.00
     
Total On-Site and Utility Electric Sources 2007.74 100.00
Total Electricity End Uses 2007.74 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 344.25
Time Setpoint Not Met During Occupied Cooling 3349.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 5905.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
RunPeriod Helena Regional Airport MT USA TMY3 WMO#=727720
Weather File Helena Regional Airport MT USA TMY3 WMO#=727720
Latitude [deg] 46.60
Longitude [deg] -112.0
Elevation [m] 1167.00
Time Zone -7.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Window Opening Area [m2] 184.20 8.38 72.38 6.62 96.82
Window-Wall Ratio [%] 10.87 3.95 11.39 3.13 15.24


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Window Opening Area [m2] 179.26 8.38 67.45 6.62 96.82
Window-Wall Ratio [%] 12.01 3.95 12.11 5.68 15.95


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 8.3610   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 6.9675   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 11.1480   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 15.3285 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 12.5415 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 18.1154 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 20.9024   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 16.7220 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 8.3610 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2155.0206
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 12.5415 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 15.3285 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 8.3610   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 11.1480   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
Total 4013.58     11621.73   1694.58 184.20 11.2819 15.53 28.2097
Conditioned Total 3725.09     10741.65   1492.32 179.26 11.5457 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 7.8766 26.23 260.8031
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB -26.30 0.00 -26.30 Wetbulb [C] 1.60 300.00
HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 33.70 16.10 16.40 Wetbulb [C] 4.90 290.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 0.00 90.00 N
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 90.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 270.00 90.00 W
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 270.00 90.00 W
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 90.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 270.00 90.00 W
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 90.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 90.00 90.00 E
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 90.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 90.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 90.00 90.00 E
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 90.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 90.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 180.00 90.00 S
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 90.00 90.00 E
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 180.00 90.00 S
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.324 0.340 8.36 90.00 90.00 E
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 0.00 90.00 N
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 180.00 90.00 S
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 270.00 90.00 W
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 0.00 90.00 N
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 270.00 90.00 W
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 270.00 90.00 W
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 35.12 270.00 90.00 W
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 270.00 90.00 W
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 270.00 90.00 W
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 90.00 90.00 E
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 90.00 90.00 E
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 90.00 90.00 E
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 0.00 90.00 N
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 180.00 90.00 S
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 90.00 90.00 E
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 180.00 90.00 S
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.324 0.340 8.36 90.00 90.00 E
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 0.00 90.00 N
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 180.00 90.00 S
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 270.00 90.00 W
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 0.00 90.00 N
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 270.00 90.00 W
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 270.00 90.00 W
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 35.12 270.00 90.00 W
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 270.00 90.00 W
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 270.00 90.00 W
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 90.00 90.00 E
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 90.00 90.00 E
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 90.00 90.00 E
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 0.00 90.00 N
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 180.00 90.00 S
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 90.00 90.00 E
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 180.00 90.00 S
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.324 0.340 8.36 90.00 90.00 E
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 0.00 90.00 N
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 270.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 180.00 90.00 S
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 270.00 90.00 W
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 0.00 90.00 N
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 270.00 90.00 W
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 270.00 90.00 W
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 35.12 270.00 90.00 W
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 270.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 270.00 90.00 W
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 270.00 90.00 W
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 90.00 90.00 E
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 5.02 90.00 90.00 E
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 270.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 43.48 90.00 90.00 E
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 10.87 90.00 90.00 E
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 4.18 90.00 90.00 E
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 270.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.324 0.340 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.324 0.340 22.58 0.00 90.00 N
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 180.00 90.00 S
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 0.00 90.00 N
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 270.00 90.00 W
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 270.00 90.00 W
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 270.00 90.00 W
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 90.00 90.00 E
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 90.00 90.00 E
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 180.00 90.00 S
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 0.00 90.00 N
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 270.00 90.00 W
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 90.00 90.00 E
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 180.00 90.00 S
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 0.00 90.00 N
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 270.00 90.00 W
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 90.00 90.00 E
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 180.00 90.00 S
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 0.00 90.00 N
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 270.00 90.00 W
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 90.00 90.00 E
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           8.38 2.653 0.426 0.308              
Non-North Total or Average           175.82 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7084.53 5658.10 1426.43 0.80 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   19157.67 15300.37 3857.30 0.80 3.50    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   9187.17 7072.52 2114.65 0.77 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   14532.51 11606.47 2926.05 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6752.4 3.15 10.76 11.39 10.54
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 18259.6 2.87 9.78 10.36 9.69
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8790.2 3.20 10.93 11.57 10.79
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13851.3 3.15 10.76 11.39 10.54
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   279.38 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   50598.74 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1097.35 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1097.35 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1540.20 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1407.36 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1171.29 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   279.32 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   279.38 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   3346.85 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1100.48 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   4631.96 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3615.43 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4389.40 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1608.30 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1480.28 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4389.09 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1135.65 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4389.09 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1375.23 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   279.32 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   279.38 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   3950.44 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1215.10 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   4389.40 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3478.75 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   4636.89 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1306.96 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1631.93 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   4705.14 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1097.27 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4445.23 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1097.27 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   497.94 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   279.38 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   5784.36 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   2038.95 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   5216.29 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   4250.68 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   6084.59 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   1814.05 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1631.66 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   5984.63 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1687.34 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   5826.40 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1948.07 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   534.74 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   4518.40 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   18938.78 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   10141.58 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   7685.92 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.64 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.54 622.50 0.43 496.81 1160.84 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.55 622.50 1.16 1319.47 1140.11 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.54 622.50 0.51 593.74 1160.84 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.55 622.50 0.88 1000.91 1140.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.51 0.27
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 10170.29 12204.35 0.964 1.157 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.84 0.00635
RESTROOMFLR1 674.66 809.59 0.064 0.077 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 28.63 0.00635
MEETINGROOMFLR1 4491.78 5390.14 0.426 0.511 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.84 0.00635
GUESTROOM101 551.21 661.46 0.055 0.066 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM102 419.34 503.20 0.042 0.051 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM103 1517.02 1820.42 0.200 0.240 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM104 1355.78 1626.94 0.179 0.214 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM105 1814.93 2177.92 0.239 0.287 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
EMPLOYEELOUNGEFLR1 5719.38 6863.25 0.542 0.651 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
EXERCISECENTERFLR1 1322.35 1586.82 0.125 0.150 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.84 0.00635
FRONTOFFICEFLR1 3764.06 4516.87 0.357 0.428 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
GUESTROOM201 842.96 1011.55 0.085 0.102 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 30.24 0.00635
GUESTROOM202_205 6050.71 7260.86 0.797 0.957 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM206_208 4976.12 5971.35 0.656 0.787 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.84 0.00635
GUESTROOM209_212 5647.45 6776.94 0.744 0.893 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.84 0.00635
GUESTROOM213 1628.99 1954.79 0.215 0.258 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM214 1593.90 1912.68 0.210 0.252 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM215_218 8807.56 10569.07 0.884 1.061 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
GUESTROOM219 5748.98 6898.78 0.757 0.909 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
GUESTROOM220_223 5424.31 6509.17 0.715 0.858 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
GUESTROOM224 1604.49 1925.38 0.211 0.254 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 29.39 0.00635
GUESTROOM301 704.35 845.22 0.071 0.085 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.64 0.00635
GUESTROOM302_305 2043.16 2451.79 0.205 0.246 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM306_308 1871.61 2245.93 0.188 0.225 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM309_312 5663.82 6796.59 0.746 0.896 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM313 684.95 821.93 0.069 0.083 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 29.23 0.00635
GUESTROOM314 1515.33 1818.39 0.200 0.240 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM315_318 6105.60 7326.72 0.804 0.965 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM319 878.08 1053.70 0.088 0.106 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM320_323 5245.30 6294.36 0.691 0.829 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM324 537.63 645.15 0.054 0.065 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 30.00 0.00635
GUESTROOM401 2063.17 2475.81 0.272 0.326 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 31.45 0.00635
GUESTROOM402_405 3035.51 3642.61 0.305 0.366 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.04 0.00635
GUESTROOM406_408 2761.44 3313.73 0.277 0.333 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.04 0.00635
GUESTROOM409_412 6906.70 8288.04 0.910 1.092 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.04 0.00635
GUESTROOM413 1038.81 1246.57 0.104 0.125 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.04 0.00635
GUESTROOM414 813.11 975.73 0.082 0.098 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.70 0.00635
GUESTROOM415_418 6449.21 7739.05 0.850 1.020 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 30.40 0.00635
GUESTROOM419 1766.38 2119.66 0.233 0.279 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 30.80 0.00635
GUESTROOM420_423 6302.93 7563.52 0.830 0.997 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 30.40 0.00635
GUESTROOM424 1781.82 2138.19 0.235 0.282 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.70 0.00635
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
CORRIDORFLR1 16917.50 20301.00 1.602 1.923 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.84 0.00635
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
CORRIDORFLR2 3004.16 3604.99 0.285 0.342 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 32.09 0.00635
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
CORRIDORFLR3 1726.73 2072.07 0.164 0.196 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 31.04 0.00635
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635
CORRIDORFLR4 2753.44 3304.13 0.261 0.313 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 33.22 0.00635
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN CLG .4% CONDNS DB=>MWB   33.70 0.00635


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 2260.85 2713.02 0.073 0.236 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 07:45:00 -26.30 0.00039
RESTROOMFLR1 93.83 112.60 0.003 0.004 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:30:00 -26.30 0.00039
MEETINGROOMFLR1 794.20 953.04 0.026 0.126 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 07:00:00 -26.30 0.00039
GUESTROOM101 76.89 92.26 0.002 0.013 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -26.30 0.00039
GUESTROOM102 104.61 125.53 0.003 0.013 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -26.30 0.00039
GUESTROOM103 715.27 858.33 0.023 0.028 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -26.30 0.00039
GUESTROOM104 604.62 725.54 0.020 0.024 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:30:00 -26.30 0.00039
GUESTROOM105 407.89 489.47 0.013 0.016 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:45:00 -26.30 0.00039
EMPLOYEELOUNGEFLR1 392.61 471.13 0.013 0.051 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -26.30 0.00039
EXERCISECENTERFLR1 242.72 291.26 0.008 0.043 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 06:00:00 -26.30 0.00039
FRONTOFFICEFLR1 1345.83 1614.99 0.044 0.056 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -26.30 0.00039
GUESTROOM201 375.48 450.57 0.011 0.014 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 -26.30 0.00039
GUESTROOM202_205 1587.07 1904.49 0.051 0.062 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 10:45:00 -26.30 0.00039
GUESTROOM206_208 1211.51 1453.81 0.039 0.047 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -26.30 0.00039
GUESTROOM209_212 1310.21 1572.25 0.042 0.054 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -26.30 0.00039
GUESTROOM213 772.03 926.43 0.025 0.030 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 -26.30 0.00039
GUESTROOM214 665.38 798.46 0.022 0.026 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 10:15:00 -26.30 0.00039
GUESTROOM215_218 418.09 501.71 0.013 0.054 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:30:00 -26.30 0.00039
GUESTROOM219 378.20 453.83 0.012 0.015 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -26.30 0.00039
GUESTROOM220_223 1142.47 1370.97 0.037 0.054 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -26.30 0.00039
GUESTROOM224 577.84 693.41 0.019 0.022 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -26.30 0.00039
GUESTROOM301 470.99 565.19 0.014 0.017 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 17:15:00 -26.30 0.00039
GUESTROOM302_305 934.50 1121.40 0.028 0.054 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 17:00:00 -26.30 0.00039
GUESTROOM306_308 765.61 918.73 0.023 0.043 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:15:00 -26.30 0.00039
GUESTROOM309_312 1591.18 1909.42 0.052 0.062 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -26.30 0.00039
GUESTROOM313 547.55 657.05 0.016 0.020 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 22:45:00 -26.30 0.00039
GUESTROOM314 791.76 950.11 0.026 0.031 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 15:15:00 -26.30 0.00039
GUESTROOM315_318 1648.22 1977.87 0.053 0.064 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:00:00 -26.30 0.00039
GUESTROOM319 136.64 163.97 0.004 0.013 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:15:00 -26.30 0.00039
GUESTROOM320_323 1431.63 1717.96 0.046 0.056 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:00:00 -26.30 0.00039
GUESTROOM324 315.13 378.16 0.009 0.013 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 17:30:00 -26.30 0.00039
GUESTROOM401 1130.90 1357.08 0.037 0.044 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 21:30:00 -26.30 0.00039
GUESTROOM402_405 2180.54 2616.65 0.066 0.079 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 21:00:00 -26.30 0.00039
GUESTROOM406_408 1825.31 2190.37 0.055 0.066 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 18:30:00 -26.30 0.00039
GUESTROOM409_412 2797.60 3357.12 0.091 0.109 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 19:15:00 -26.30 0.00039
GUESTROOM413 970.12 1164.14 0.029 0.035 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -26.30 0.00039
GUESTROOM414 818.16 981.80 0.025 0.030 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 20:45:00 -26.30 0.00039
GUESTROOM415_418 2714.46 3257.35 0.088 0.106 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 17:00:00 -26.30 0.00039
GUESTROOM419 837.93 1005.52 0.027 0.033 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 17:45:00 -26.30 0.00039
GUESTROOM420_423 2582.61 3099.13 0.084 0.101 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -26.30 0.00039
GUESTROOM424 1055.21 1266.26 0.034 0.041 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 22:15:00 -26.30 0.00039
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB   -26.30 0.00039
CORRIDORFLR1 40193.19 48231.83 1.301 1.561 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -26.30 0.00039
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB   -26.30 0.00039
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB   -26.30 0.00039
CORRIDORFLR2 1177.58 1413.09 0.038 0.046 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 09:45:00 -26.30 0.00039
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB   -26.30 0.00039
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB   -26.30 0.00039
CORRIDORFLR3 1680.55 2016.67 0.054 0.065 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -26.30 0.00039
FRONTSTAIRSFLR3 38.59 46.31 0.001 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 23:30:00 -26.30 0.00039
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB   -26.30 0.00039
CORRIDORFLR4 3208.83 3850.59 0.104 0.125 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -26.30 0.00039
FRONTSTAIRSFLR4 263.46 316.15 0.006 0.007 HELENA REGIONAL AIRPORT ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -26.30 0.00039


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.43 0.43 0.06 0.06
SAC_FRONTLOUNGE 1.16 1.16 0.24 0.24
SAC_MEETINGROOM 0.51 0.51 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.88 0.88 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 1.16 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 1571.50 7203.00 1060.75
RESTROOMFLR1 213.25 7676.25 173.00
MEETINGROOMFLR1 801.50 3038.75 23.75
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 1739.50 8760.00 1739.50
GUESTROOM104 736.25 8760.00 736.25
GUESTROOM105 59.00 8627.50 59.00
EMPLOYEELOUNGEFLR1 2974.00 2198.00 291.00
EXERCISECENTERFLR1 1022.25 3363.25 32.25
FRONTOFFICEFLR1 891.75 6739.25 369.25
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 779.75 8694.00 779.75
GUESTROOM206_208 604.50 8673.00 604.50
GUESTROOM209_212 488.75 8732.50 488.75
GUESTROOM213 1821.75 8755.00 1821.75
GUESTROOM214 599.25 8582.50 599.25
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 3278.25 4589.00 345.75
GUESTROOM220_223 211.50 8368.75 211.50
GUESTROOM224 689.25 8518.00 689.25
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 841.25 8729.50 841.25
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 1499.25 8586.75 1499.25
GUESTROOM315_318 267.25 8260.50 267.25
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 530.50 8502.25 530.50
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 3935.50 8403.00 3925.00
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 2193.50 8149.75 2094.75
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 1794.75 7899.75 1490.25
GUESTROOM419 1757.25 8062.00 1698.25
GUESTROOM420_423 1917.25 7925.25 1646.25
GUESTROOM424 2791.75 8114.25 2725.50
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7135.00 8760.00 5905.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.25 0.00 0.25 0.00
RESTROOMFLR1 152.00 690.25 152.00 690.25
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 7.00 18.50 7.00 18.50
GUESTROOM104 5.00 18.25 5.00 18.25
GUESTROOM105 0.00 27.50 0.00 27.50
EMPLOYEELOUNGEFLR1 318.75 1392.00 258.50 924.00
EXERCISECENTERFLR1 0.75 0.00 0.00 0.00
FRONTOFFICEFLR1 0.25 0.00 0.25 0.00
GUESTROOM201 1.00 0.00 0.00 0.00
GUESTROOM202_205 2.50 7.00 2.50 7.00
GUESTROOM206_208 1.75 16.25 1.75 16.25
GUESTROOM209_212 1.75 5.50 1.75 5.50
GUESTROOM213 5.25 7.50 5.25 7.50
GUESTROOM214 3.50 9.50 3.50 9.50
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 2107.25 0.00 2107.25
GUESTROOM220_223 1.00 5.00 1.00 5.00
GUESTROOM224 4.00 9.50 4.00 9.50
GUESTROOM301 0.25 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 4.50 5.50 4.50 5.50
GUESTROOM313 0.25 0.00 0.00 0.00
GUESTROOM314 5.00 8.25 5.00 8.25
GUESTROOM315_318 2.25 6.50 2.25 6.50
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 5.25 3.75 5.25 3.75
GUESTROOM324 0.75 0.00 0.00 0.00
GUESTROOM401 2.75 18.75 2.75 18.75
GUESTROOM402_405 0.50 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 8.25 18.25 8.25 18.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 11.25 14.00 11.25 14.00
GUESTROOM419 5.25 18.75 5.25 18.75
GUESTROOM420_423 11.25 13.75 11.25 13.75
GUESTROOM424 2.50 18.25 2.50 18.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 1.50 2142.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 20.50 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.50 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 3.50 0.00 0.00 0.00
CORRIDORFLR4 0.00 121.75 0.00 0.00
FRONTSTAIRSFLR4 3.25 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 377.75 4069.50 344.25 3349.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:21

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006920


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006920
SAC_FRONTOFFICE SUPPLY FAN 0.427976
SAC_FRONTLOUNGE SUPPLY FAN 1.16
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.877909


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 279.38
CORRIDORFLR1 PTAC HEATING COIL 50598.74
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1097.35
102 PTAC HEATING COIL 1097.35
103 PTAC HEATING COIL 1540.20
104 PTAC HEATING COIL 1407.36
105 PTAC HEATING COIL 1171.29
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 279.32
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 279.38
CORRIDORFLR2 PTAC HEATING COIL 3346.85
201 PTAC HEATING COIL 1100.48
202_205 PTAC HEATING COIL 4631.96
206_208 PTAC HEATING COIL 3615.43
209_212 PTAC HEATING COIL 4389.40
213 PTAC HEATING COIL 1608.30
214 PTAC HEATING COIL 1480.28
215_218 PTAC HEATING COIL 4389.09
219 PTAC HEATING COIL 1135.65
220_223 PTAC HEATING COIL 4389.09
224 PTAC HEATING COIL 1375.23
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 279.32
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 279.38
CORRIDORFLR3 PTAC HEATING COIL 3950.44
301 PTAC HEATING COIL 1215.10
302_305 PTAC HEATING COIL 4389.40
306_308 PTAC HEATING COIL 3478.75
309_312 PTAC HEATING COIL 4636.89
313 PTAC HEATING COIL 1306.96
314 PTAC HEATING COIL 1631.93
315_318 PTAC HEATING COIL 4705.14
319 PTAC HEATING COIL 1097.27
320_323 PTAC HEATING COIL 4445.23
324 PTAC HEATING COIL 1097.27
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 497.94
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 279.38
CORRIDORFLR4 PTAC HEATING COIL 5784.36
401 PTAC HEATING COIL 2038.95
402_405 PTAC HEATING COIL 5216.29
406_408 PTAC HEATING COIL 4250.68
409_412 PTAC HEATING COIL 6084.59
413 PTAC HEATING COIL 1814.05
414 PTAC HEATING COIL 1631.66
415_418 PTAC HEATING COIL 5984.63
419 PTAC HEATING COIL 1687.34
420_423 PTAC HEATING COIL 5826.40
424 PTAC HEATING COIL 1948.07
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 534.74


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.798655 0.427976 7084.53
SAC_FRONTLOUNGE COOLING COIL 0.798655 1.16 19157.67
SAC_MEETINGROOM COOLING COIL 0.769826 0.511477 9187.17
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.798655 0.877909 14532.51


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 1.16
RESTROOMFLR1 DIRECT AIR 0.076703
MEETINGROOMFLR1 DIRECT AIR 0.511477
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.650797
EXERCISECENTERFLR1 DIRECT AIR 0.150409
FRONTOFFICEFLR1 DIRECT AIR 0.427976


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.427976
SAC_FRONTLOUNGE MAIN BRANCH 1.16
SAC_MEETINGROOM MAIN BRANCH 0.511477
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.877909


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.427976
SAC_FRONTLOUNGE 1.16
SAC_MEETINGROOM 0.511477
SAC_EXC_EMPLGE_RESTRM 0.877909


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.427976 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 1.16 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.511477 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.877909 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.427976 0.427976 0.427976 0.427976 4518.40 7084.53 1.00
SAC_FRONTLOUNGE 1.16 1.16 1.16 1.16 18938.78 19157.67 1.00
SAC_MEETINGROOM 0.511477 0.511477 0.511477 0.511477 10141.58 9187.17 1.00
SAC_EXC_EMPLGE_RESTRM 0.877909 0.877909 0.877909 0.877909 7685.92 14532.51 0.171327


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 4518.40
SAC_FRONTLOUNGE HEATING COIL 18938.78
SAC_MEETINGROOM HEATING COIL 10141.58
SAC_EXC_EMPLGE_RESTRM HEATING COIL 7685.92


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.511477


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.72 -4.7
February 18.06 -3.7
March 18.73 2.15
April 19.68 6.19
May 21.25 11.83
June 23.12 17.35
July 24.09 20.52
August 23.69 18.54
September 22.74 14.70
October 20.80 6.26
November 18.87 1.12
December 17.24 -5.0
     
Annual Sum or Average 20.51 7.16
Minimum of Months 17.24 -5.0
Maximum of Months 24.09 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.83 -4.7
February 22.03 -3.7
March 22.66 2.15
April 23.24 6.19
May 24.00 11.83
June 24.93 17.35
July 25.61 20.52
August 25.21 18.54
September 24.53 14.70
October 23.33 6.26
November 22.53 1.12
December 21.78 -5.0
     
Annual Sum or Average 23.48 7.16
Minimum of Months 21.78 -5.0
Maximum of Months 25.61 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.77 -4.7
February 17.12 -3.7
March 17.81 2.15
April 18.78 6.19
May 20.41 11.83
June 22.32 17.35
July 23.34 20.52
August 22.89 18.54
September 21.92 14.70
October 19.84 6.26
November 17.93 1.12
December 16.34 -5.0
     
Annual Sum or Average 19.63 7.16
Minimum of Months 16.34 -5.0
Maximum of Months 23.34 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -4.7
February 21.12 -3.7
March 21.26 2.15
April 21.67 6.19
May 22.38 11.83
June 23.14 17.35
July 23.45 20.52
August 23.26 18.54
September 22.73 14.70
October 21.55 6.26
November 21.22 1.12
December 21.13 -5.0
     
Annual Sum or Average 22.01 7.16
Minimum of Months 21.11 -5.0
Maximum of Months 23.45 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 -4.7
February 21.93 -3.7
March 22.25 2.15
April 22.57 6.19
May 23.03 11.83
June 23.42 17.35
July 23.60 20.52
August 23.51 18.54
September 23.31 14.70
October 22.66 6.26
November 22.23 1.12
December 21.78 -5.0
     
Annual Sum or Average 22.68 7.16
Minimum of Months 21.78 -5.0
Maximum of Months 23.60 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.39 -4.7
February 21.51 -3.7
March 22.07 2.15
April 22.74 6.19
May 23.37 11.83
June 23.74 17.35
July 23.83 20.52
August 23.78 18.54
September 23.60 14.70
October 22.72 6.26
November 21.93 1.12
December 21.39 -5.0
     
Annual Sum or Average 22.68 7.16
Minimum of Months 21.39 -5.0
Maximum of Months 23.83 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.91 -4.7
February 24.16 -3.7
March 24.65 2.15
April 25.23 6.19
May 25.87 11.83
June 26.42 17.35
July 26.74 20.52
August 26.56 18.54
September 26.21 14.70
October 25.30 6.26
November 24.56 1.12
December 23.91 -5.0
     
Annual Sum or Average 25.30 7.16
Minimum of Months 23.91 -5.0
Maximum of Months 26.74 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.15 -4.7
February 19.37 -3.7
March 20.08 2.15
April 21.04 6.19
May 22.08 11.83
June 22.87 17.35
July 23.15 20.52
August 22.98 18.54
September 22.54 14.70
October 21.05 6.26
November 19.90 1.12
December 19.16 -5.0
     
Annual Sum or Average 21.12 7.16
Minimum of Months 19.15 -5.0
Maximum of Months 23.15 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.01 -4.7
February 19.16 -3.7
March 19.76 2.15
April 20.70 6.19
May 21.76 11.83
June 22.65 17.35
July 23.01 20.52
August 22.79 18.54
September 22.26 14.70
October 20.67 6.26
November 19.59 1.12
December 19.04 -5.0
     
Annual Sum or Average 20.87 7.16
Minimum of Months 19.01 -5.0
Maximum of Months 23.01 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.61 -4.7
February 20.67 -3.7
March 20.88 2.15
April 21.17 6.19
May 21.50 11.83
June 21.70 17.35
July 21.74 20.52
August 21.72 18.54
September 21.61 14.70
October 21.20 6.26
November 20.91 1.12
December 20.61 -5.0
     
Annual Sum or Average 21.20 7.16
Minimum of Months 20.61 -5.0
Maximum of Months 21.74 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 -4.7
February 20.87 -3.7
March 21.16 2.15
April 21.43 6.19
May 21.65 11.83
June 21.74 17.35
July 21.75 20.52
August 21.75 18.54
September 21.70 14.70
October 21.44 6.26
November 21.13 1.12
December 20.77 -5.0
     
Annual Sum or Average 21.35 7.16
Minimum of Months 20.77 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.22 -4.7
February 21.28 -3.7
March 21.54 2.15
April 21.66 6.19
May 21.74 11.83
June 21.75 17.35
July 21.76 20.52
August 21.75 18.54
September 21.75 14.70
October 21.67 6.26
November 21.50 1.12
December 21.17 -5.0
     
Annual Sum or Average 21.57 7.16
Minimum of Months 21.17 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.33 -4.7
February 22.36 -3.7
March 22.52 2.15
April 22.56 6.19
May 22.69 11.83
June 22.65 17.35
July 22.52 20.52
August 22.62 18.54
September 22.76 14.70
October 22.67 6.26
November 22.57 1.12
December 22.30 -5.0
     
Annual Sum or Average 22.55 7.16
Minimum of Months 22.30 -5.0
Maximum of Months 22.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 50.49 -4.7
February 50.72 -3.7
March 51.13 2.15
April 51.64 6.19
May 52.23 11.83
June 52.86 17.35
July 53.23 20.52
August 53.04 18.54
September 52.62 14.70
October 51.80 6.26
November 51.06 1.12
December 50.43 -5.0
     
Annual Sum or Average 51.78 7.16
Minimum of Months 50.43 -5.0
Maximum of Months 53.23 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 68.71 -4.7
February 68.91 -3.7
March 69.13 2.15
April 69.63 6.19
May 70.31 11.83
June 71.17 17.35
July 71.65 20.52
August 71.47 18.54
September 71.02 14.70
October 70.18 6.26
November 69.23 1.12
December 68.59 -5.0
     
Annual Sum or Average 70.00 7.16
Minimum of Months 68.59 -5.0
Maximum of Months 71.65 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.64 -4.7
February 22.74 -3.7
March 23.04 2.15
April 23.28 6.19
May 23.61 11.83
June 23.83 17.35
July 23.88 20.52
August 23.86 18.54
September 23.78 14.70
October 23.36 6.26
November 23.03 1.12
December 22.60 -5.0
     
Annual Sum or Average 23.31 7.16
Minimum of Months 22.60 -5.0
Maximum of Months 23.88 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.86 -4.7
February 22.04 -3.7
March 22.61 2.15
April 23.14 6.19
May 23.64 11.83
June 23.86 17.35
July 23.89 20.52
August 23.88 18.54
September 23.81 14.70
October 23.26 6.26
November 22.50 1.12
December 21.81 -5.0
     
Annual Sum or Average 23.03 7.16
Minimum of Months 21.81 -5.0
Maximum of Months 23.89 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.69 -4.7
February 17.03 -3.7
March 17.89 2.15
April 19.10 6.19
May 21.11 11.83
June 23.37 17.35
July 24.46 20.52
August 23.87 18.54
September 22.63 14.70
October 20.26 6.26
November 18.09 1.12
December 16.19 -5.0
     
Annual Sum or Average 20.08 7.16
Minimum of Months 16.19 -5.0
Maximum of Months 24.46 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.63 -4.7
February 19.92 -3.7
March 20.60 2.15
April 21.50 6.19
May 22.74 11.83
June 23.98 17.35
July 24.61 20.52
August 24.29 18.54
September 23.56 14.70
October 22.05 6.26
November 20.66 1.12
December 19.41 -5.0
     
Annual Sum or Average 21.92 7.16
Minimum of Months 19.41 -5.0
Maximum of Months 24.61 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.11 -4.7
February 17.54 -3.7
March 18.40 2.15
April 19.60 6.19
May 21.58 11.83
June 23.89 17.35
July 25.02 20.52
August 24.52 18.54
September 23.39 14.70
October 20.96 6.26
November 18.49 1.12
December 16.43 -5.0
     
Annual Sum or Average 20.59 7.16
Minimum of Months 16.43 -5.0
Maximum of Months 25.02 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.31 -4.7
February 21.50 -3.7
March 22.09 2.15
April 22.89 6.19
May 23.56 11.83
June 23.87 17.35
July 23.89 20.52
August 23.89 18.54
September 23.78 14.70
October 22.98 6.26
November 21.91 1.12
December 21.30 -5.0
     
Annual Sum or Average 22.75 7.16
Minimum of Months 21.30 -5.0
Maximum of Months 23.89 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.58 -4.7
February 16.02 -3.7
March 16.92 2.15
April 18.19 6.19
May 20.30 11.83
June 22.71 17.35
July 23.93 20.52
August 23.36 18.54
September 22.15 14.70
October 19.40 6.26
November 16.97 1.12
December 14.96 -5.0
     
Annual Sum or Average 19.23 7.16
Minimum of Months 14.96 -5.0
Maximum of Months 23.93 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -4.7
February 18.92 -3.7
March 19.28 2.15
April 20.30 6.19
May 21.73 11.83
June 22.94 17.35
July 23.23 20.52
August 23.03 18.54
September 22.36 14.70
October 20.01 6.26
November 19.13 1.12
December 18.91 -5.0
     
Annual Sum or Average 20.74 7.16
Minimum of Months 18.90 -5.0
Maximum of Months 23.23 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.72 -4.7
February 20.78 -3.7
March 21.07 2.15
April 21.37 6.19
May 21.64 11.83
June 21.75 17.35
July 21.75 20.52
August 21.75 18.54
September 21.71 14.70
October 21.33 6.26
November 21.04 1.12
December 20.70 -5.0
     
Annual Sum or Average 21.30 7.16
Minimum of Months 20.70 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.77 -4.7
February 20.84 -3.7
March 21.14 2.15
April 21.43 6.19
May 21.67 11.83
June 21.75 17.35
July 21.75 20.52
August 21.75 18.54
September 21.72 14.70
October 21.40 6.26
November 21.11 1.12
December 20.75 -5.0
     
Annual Sum or Average 21.34 7.16
Minimum of Months 20.75 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.79 -4.7
February 20.86 -3.7
March 21.17 2.15
April 21.44 6.19
May 21.67 11.83
June 21.75 17.35
July 21.75 20.52
August 21.75 18.54
September 21.72 14.70
October 21.43 6.26
November 21.15 1.12
December 20.77 -5.0
     
Annual Sum or Average 21.36 7.16
Minimum of Months 20.77 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.58 -4.7
February 20.65 -3.7
March 20.88 2.15
April 21.20 6.19
May 21.55 11.83
June 21.74 17.35
July 21.75 20.52
August 21.74 18.54
September 21.66 14.70
October 21.22 6.26
November 20.87 1.12
December 20.58 -5.0
     
Annual Sum or Average 21.20 7.16
Minimum of Months 20.58 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.84 -4.7
February 20.93 -3.7
March 21.25 2.15
April 21.52 6.19
May 21.70 11.83
June 21.75 17.35
July 21.76 20.52
August 21.76 18.54
September 21.74 14.70
October 21.54 6.26
November 21.19 1.12
December 20.79 -5.0
     
Annual Sum or Average 21.40 7.16
Minimum of Months 20.79 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.45 -4.7
February 22.66 -3.7
March 23.09 2.15
April 23.22 6.19
May 23.33 11.83
June 23.33 17.35
July 23.33 20.52
August 23.33 18.54
September 23.33 14.70
October 23.27 6.26
November 23.01 1.12
December 22.36 -5.0
     
Annual Sum or Average 23.06 7.16
Minimum of Months 22.36 -5.0
Maximum of Months 23.33 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 30.22 -4.7
February 30.45 -3.7
March 30.86 2.15
April 31.55 6.19
May 32.39 11.83
June 33.23 17.35
July 33.59 20.52
August 33.40 18.54
September 32.95 14.70
October 31.88 6.26
November 30.81 1.12
December 30.09 -5.0
     
Annual Sum or Average 31.79 7.16
Minimum of Months 30.09 -5.0
Maximum of Months 33.59 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -4.7
February 21.77 -3.7
March 21.87 2.15
April 22.10 6.19
May 22.37 11.83
June 22.77 17.35
July 22.99 20.52
August 22.85 18.54
September 22.59 14.70
October 22.08 6.26
November 21.84 1.12
December 21.76 -5.0
     
Annual Sum or Average 22.23 7.16
Minimum of Months 21.76 -5.0
Maximum of Months 22.99 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.96 -4.7
February 21.04 -3.7
March 21.39 2.15
April 21.62 6.19
May 21.72 11.83
June 21.75 17.35
July 21.76 20.52
August 21.76 18.54
September 21.74 14.70
October 21.60 6.26
November 21.31 1.12
December 20.92 -5.0
     
Annual Sum or Average 21.47 7.16
Minimum of Months 20.92 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 -4.7
February 20.89 -3.7
March 21.23 2.15
April 21.53 6.19
May 21.70 11.83
June 21.76 17.35
July 21.76 20.52
August 21.76 18.54
September 21.74 14.70
October 21.52 6.26
November 21.15 1.12
December 20.77 -5.0
     
Annual Sum or Average 21.39 7.16
Minimum of Months 20.77 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.45 -4.7
February 18.83 -3.7
March 19.71 2.15
April 20.93 6.19
May 22.58 11.83
June 24.27 17.35
July 25.08 20.52
August 24.62 18.54
September 23.67 14.70
October 21.57 6.26
November 19.71 1.12
December 18.10 -5.0
     
Annual Sum or Average 21.47 7.16
Minimum of Months 18.10 -5.0
Maximum of Months 25.08 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.30 -4.7
February 15.76 -3.7
March 16.95 2.15
April 18.58 6.19
May 21.22 11.83
June 24.14 17.35
July 25.47 20.52
August 24.72 18.54
September 23.16 14.70
October 19.98 6.26
November 17.10 1.12
December 14.58 -5.0
     
Annual Sum or Average 19.77 7.16
Minimum of Months 14.58 -5.0
Maximum of Months 25.47 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.14 -4.7
February 16.60 -3.7
March 17.60 2.15
April 19.00 6.19
May 21.27 11.83
June 23.91 17.35
July 25.17 20.52
August 24.58 18.54
September 23.24 14.70
October 20.33 6.26
November 17.60 1.12
December 15.40 -5.0
     
Annual Sum or Average 20.09 7.16
Minimum of Months 15.40 -5.0
Maximum of Months 25.17 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -4.7
February 21.11 -3.7
March 21.29 2.15
April 21.92 6.19
May 22.86 11.83
June 23.68 17.35
July 23.85 20.52
August 23.74 18.54
September 23.32 14.70
October 21.77 6.26
November 21.21 1.12
December 21.11 -5.0
     
Annual Sum or Average 22.25 7.16
Minimum of Months 21.11 -5.0
Maximum of Months 23.85 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.23 -4.7
February 14.71 -3.7
March 15.78 2.15
April 17.29 6.19
May 19.81 11.83
June 22.70 17.35
July 24.12 20.52
August 23.41 18.54
September 21.90 14.70
October 18.42 6.26
November 15.71 1.12
December 13.56 -5.0
     
Annual Sum or Average 18.49 7.16
Minimum of Months 13.56 -5.0
Maximum of Months 24.12 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.89 -3.7
March 19.04 2.15
April 19.77 6.19
May 21.22 11.83
June 22.71 17.35
July 23.15 20.52
August 22.84 18.54
September 21.91 14.70
October 19.43 6.26
November 18.94 1.12
December 18.89 -5.0
     
Annual Sum or Average 20.48 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 23.15 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.90 -3.7
March 19.20 2.15
April 20.18 6.19
May 21.62 11.83
June 22.90 17.35
July 23.23 20.52
August 23.00 18.54
September 22.21 14.70
October 19.75 6.26
November 19.03 1.12
December 18.90 -5.0
     
Annual Sum or Average 20.66 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 23.23 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.92 -3.7
March 19.31 2.15
April 20.38 6.19
May 21.77 11.83
June 22.93 17.35
July 23.23 20.52
August 23.01 18.54
September 22.29 14.70
October 19.93 6.26
November 19.10 1.12
December 18.90 -5.0
     
Annual Sum or Average 20.73 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 23.23 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.69 -4.7
February 20.77 -3.7
March 21.06 2.15
April 21.36 6.19
May 21.64 11.83
June 21.75 17.35
July 21.75 20.52
August 21.75 18.54
September 21.69 14.70
October 21.32 6.26
November 21.02 1.12
December 20.67 -5.0
     
Annual Sum or Average 21.29 7.16
Minimum of Months 20.67 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.90 -3.7
March 19.19 2.15
April 20.09 6.19
May 21.46 11.83
June 22.80 17.35
July 23.21 20.52
August 22.96 18.54
September 22.23 14.70
October 19.90 6.26
November 19.06 1.12
December 18.89 -5.0
     
Annual Sum or Average 20.64 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 23.21 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.65 -4.7
February 20.74 -3.7
March 21.05 2.15
April 21.38 6.19
May 21.64 11.83
June 21.75 17.35
July 21.76 20.52
August 21.75 18.54
September 21.71 14.70
October 21.37 6.26
November 20.96 1.12
December 20.62 -5.0
     
Annual Sum or Average 21.29 7.16
Minimum of Months 20.62 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.95 -4.7
February 21.04 -3.7
March 21.41 2.15
April 21.62 6.19
May 21.72 11.83
June 21.76 17.35
July 21.76 20.52
August 21.76 18.54
September 21.74 14.70
October 21.60 6.26
November 21.31 1.12
December 20.90 -5.0
     
Annual Sum or Average 21.47 7.16
Minimum of Months 20.90 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.58 -4.7
February 21.89 -3.7
March 22.53 2.15
April 23.48 6.19
May 24.64 11.83
June 25.73 17.35
July 26.14 20.52
August 25.87 18.54
September 25.26 14.70
October 23.67 6.26
November 22.36 1.12
December 21.39 -5.0
     
Annual Sum or Average 23.72 7.16
Minimum of Months 21.39 -5.0
Maximum of Months 26.14 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.76 -4.7
February 20.19 -3.7
March 21.27 2.15
April 22.29 6.19
May 23.03 11.83
June 23.32 17.35
July 23.33 20.52
August 23.33 18.54
September 23.22 14.70
October 22.23 6.26
November 20.85 1.12
December 19.69 -5.0
     
Annual Sum or Average 21.88 7.16
Minimum of Months 19.69 -5.0
Maximum of Months 23.33 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 -4.7
February 20.89 -3.7
March 21.25 2.15
April 21.54 6.19
May 21.70 11.83
June 21.75 17.35
July 21.76 20.52
August 21.75 18.54
September 21.73 14.70
October 21.48 6.26
November 21.15 1.12
December 20.77 -5.0
     
Annual Sum or Average 21.38 7.16
Minimum of Months 20.77 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.91 -4.7
February 18.96 -3.7
March 19.58 2.15
April 20.86 6.19
May 22.16 11.83
June 23.06 17.35
July 23.28 20.52
August 23.15 18.54
September 22.65 14.70
October 20.66 6.26
November 19.35 1.12
December 18.93 -5.0
     
Annual Sum or Average 20.97 7.16
Minimum of Months 18.91 -5.0
Maximum of Months 23.28 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.07 -4.7
February 17.51 -3.7
March 18.58 2.15
April 20.12 6.19
May 22.20 11.83
June 24.31 17.35
July 25.27 20.52
August 24.68 18.54
September 23.46 14.70
October 20.68 6.26
November 18.47 1.12
December 16.69 -5.0
     
Annual Sum or Average 20.77 7.16
Minimum of Months 16.69 -5.0
Maximum of Months 25.27 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.04 -4.7
February 14.58 -3.7
March 15.98 2.15
April 17.87 6.19
May 20.88 11.83
June 24.21 17.35
July 25.70 20.52
August 24.82 18.54
September 23.01 14.70
October 19.24 6.26
November 16.02 1.12
December 13.29 -5.0
     
Annual Sum or Average 19.16 7.16
Minimum of Months 13.29 -5.0
Maximum of Months 25.70 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.44 -4.7
February 15.02 -3.7
March 16.35 2.15
April 18.10 6.19
May 20.79 11.83
June 23.87 17.35
July 25.32 20.52
August 24.52 18.54
September 22.79 14.70
October 19.14 6.26
November 16.09 1.12
December 13.74 -5.0
     
Annual Sum or Average 19.20 7.16
Minimum of Months 13.74 -5.0
Maximum of Months 25.32 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -4.7
February 21.11 -3.7
March 21.27 2.15
April 21.76 6.19
May 22.47 11.83
June 23.28 17.35
July 23.59 20.52
August 23.35 18.54
September 22.76 14.70
October 21.53 6.26
November 21.15 1.12
December 21.11 -5.0
     
Annual Sum or Average 22.05 7.16
Minimum of Months 21.11 -5.0
Maximum of Months 23.59 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.96 -4.7
February 13.56 -3.7
March 14.91 2.15
April 16.66 6.19
May 19.44 11.83
June 22.65 17.35
July 24.23 20.52
August 23.32 18.54
September 21.47 14.70
October 17.52 6.26
November 14.62 1.12
December 12.30 -5.0
     
Annual Sum or Average 17.83 7.16
Minimum of Months 12.30 -5.0
Maximum of Months 24.23 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -4.7
February 20.49 -3.7
March 20.61 2.15
April 20.99 6.19
May 21.45 11.83
June 21.72 17.35
July 21.75 20.52
August 21.72 18.54
September 21.52 14.70
October 20.82 6.26
November 20.58 1.12
December 20.48 -5.0
     
Annual Sum or Average 21.05 7.16
Minimum of Months 20.48 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.91 -3.7
March 19.18 2.15
April 19.97 6.19
May 21.15 11.83
June 22.46 17.35
July 22.93 20.52
August 22.56 18.54
September 21.59 14.70
October 19.51 6.26
November 18.96 1.12
December 18.89 -5.0
     
Annual Sum or Average 20.43 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 22.93 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.92 -3.7
March 19.25 2.15
April 20.08 6.19
May 21.22 11.83
June 22.47 17.35
July 22.92 20.52
August 22.56 18.54
September 21.63 14.70
October 19.60 6.26
November 18.99 1.12
December 18.89 -5.0
     
Annual Sum or Average 20.46 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 22.92 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.58 -4.7
February 20.67 -3.7
March 21.00 2.15
April 21.38 6.19
May 21.65 11.83
June 21.75 17.35
July 21.75 20.52
August 21.75 18.54
September 21.67 14.70
October 21.24 6.26
November 20.90 1.12
December 20.57 -5.0
     
Annual Sum or Average 21.25 7.16
Minimum of Months 20.57 -5.0
Maximum of Months 21.75 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -4.7
February 18.91 -3.7
March 19.18 2.15
April 19.94 6.19
May 21.10 11.83
June 22.44 17.35
July 22.94 20.52
August 22.59 18.54
September 21.69 14.70
October 19.62 6.26
November 18.99 1.12
December 18.89 -5.0
     
Annual Sum or Average 20.44 7.16
Minimum of Months 18.89 -5.0
Maximum of Months 22.94 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -4.7
February 18.92 -3.7
March 19.37 2.15
April 20.40 6.19
May 21.59 11.83
June 22.71 17.35
July 23.08 20.52
August 22.82 18.54
September 22.10 14.70
October 20.06 6.26
November 19.11 1.12
December 18.90 -5.0
     
Annual Sum or Average 20.67 7.16
Minimum of Months 18.90 -5.0
Maximum of Months 23.08 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.70 -4.7
February 20.83 -3.7
March 21.28 2.15
April 21.58 6.19
May 21.70 11.83
June 21.75 17.35
July 21.76 20.52
August 21.75 18.54
September 21.72 14.70
October 21.47 6.26
November 21.08 1.12
December 20.65 -5.0
     
Annual Sum or Average 21.36 7.16
Minimum of Months 20.65 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.03 -4.7
February 19.44 -3.7
March 20.31 2.15
April 21.42 6.19
May 22.73 11.83
June 24.05 17.35
July 24.61 20.52
August 24.17 18.54
September 23.27 14.70
October 21.33 6.26
November 19.92 1.12
December 18.86 -5.0
     
Annual Sum or Average 21.61 7.16
Minimum of Months 18.86 -5.0
Maximum of Months 24.61 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.66 -4.7
February 20.79 -3.7
March 21.21 2.15
April 21.55 6.19
May 21.70 11.83
June 21.75 17.35
July 21.76 20.52
August 21.76 18.54
September 21.72 14.70
October 21.44 6.26
November 21.02 1.12
December 20.62 -5.0
     
Annual Sum or Average 21.33 7.16
Minimum of Months 20.62 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.67 -4.7
February 20.80 -3.7
March 21.24 2.15
April 21.57 6.19
May 21.70 11.83
June 21.75 17.35
July 21.76 20.52
August 21.75 18.54
September 21.71 14.70
October 21.44 6.26
November 21.04 1.12
December 20.63 -5.0
     
Annual Sum or Average 21.34 7.16
Minimum of Months 20.63 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.53 -4.7
February 20.62 -3.7
March 20.98 2.15
April 21.43 6.19
May 21.66 11.83
June 21.75 17.35
July 21.76 20.52
August 21.75 18.54
September 21.70 14.70
October 21.29 6.26
November 20.80 1.12
December 20.52 -5.0
     
Annual Sum or Average 21.24 7.16
Minimum of Months 20.52 -5.0
Maximum of Months 21.76 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.16 -4.7
February 16.74 -3.7
March 18.07 2.15
April 19.77 6.19
May 21.98 11.83
June 24.25 17.35
July 25.30 20.52
August 24.57 18.54
September 23.12 14.70
October 20.07 6.26
November 17.72 1.12
December 15.79 -5.0
     
Annual Sum or Average 20.31 7.16
Minimum of Months 15.79 -5.0
Maximum of Months 25.30 20.52



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2015-09-14 08:44:21

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.80 -4.7
February 13.50 -3.7
March 15.19 2.15
April 17.32 6.19
May 20.56 11.83
June 24.15 17.35
July 25.76 20.52
August 24.71 18.54
September 22.60 14.70
October 18.41 6.26
November 14.96 1.12
December 12.09 -5.0
     
Annual Sum or Average 18.53 7.16
Minimum of Months 12.09 -5.0
Maximum of Months 25.76 20.52



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:21

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.195700E+12 176797.228 16-JAN-07:15 20847.837 39740.848 9523.992 102364.706 123.732 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.166166E+12 174252.249 24-FEB-07:15 17938.631 34285.948 9524.109 108216.244 91.204 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.161035E+12 132180.255 16-MAR-06:15 20847.837 39740.848 9517.687 57648.580 229.191 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.151058E+12 140587.105 13-APR-06:15 20847.837 39740.848 9527.641 70274.539 188.127 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.155109E+12 97183.147 10-MAY-06:15 20847.837 39740.848 9517.687 23707.676 3360.987 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.161383E+12 101429.790 30-JUN-17:15 26252.371 28657.799 9712.162 0.000 36799.346 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.175406E+12 103790.550 21-JUL-17:15 26252.371 28657.799 9732.334 0.000 39139.934 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.169419E+12 99096.720 05-AUG-17:15 26252.371 28657.799 9678.977 0.000 34499.461 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.155926E+12 96461.481 03-SEP-07:00 25182.171 43578.554 10111.429 0.000 17581.214 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.153400E+12 112492.142 05-OCT-06:15 20847.837 39740.848 9517.687 37496.049 693.609 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.163017E+12 131695.198 15-NOV-07:15 20847.837 39740.848 9517.687 57159.757 232.957 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.200116E+12 163401.061 27-DEC-07:15 20847.837 39740.848 9531.780 88953.192 131.291 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.200774E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.151058E+12 96461.481   17938.631 28657.799 9517.687 0.000 91.204 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.200116E+12 176797.228   26252.371 43578.554 10111.429 108216.244 39139.934 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:21

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.117389E+12 116208.055 14-JAN-09:15 4612.467 40096.028 0.000 71499.561 71499.561 71499.561 4612.467
February 0.104381E+12 123398.373 24-FEB-09:15 14337.366 40096.028 0.000 68964.979 68964.979 68964.979 14337.366
March 0.106686E+12 111235.477 10-MAR-09:15 583.949 40096.028 0.000 70555.500 70555.500 70555.500 583.949
April 0.979782E+11 111636.070 07-APR-08:15 0.000 40096.028 0.000 71540.042 71540.042 71540.042 0.000
May 0.947138E+11 106934.970 19-MAY-08:15 0.000 40096.028 0.000 66838.942 66838.942 66838.942 0.000
June 0.876063E+11 103877.588 03-JUN-08:15 0.000 40096.028 0.000 63781.560 63781.560 63781.560 0.000
July 0.879127E+11 90755.753 04-JUL-08:15 0.000 40096.028 0.000 50659.725 50659.725 50659.725 0.000
August 0.868569E+11 94252.298 25-AUG-08:15 0.000 40096.028 0.000 54156.270 54156.270 54156.270 0.000
September 0.848812E+11 96693.862 15-SEP-08:15 0.000 40096.028 0.000 56597.834 56597.834 56597.834 0.000
October 0.929716E+11 100456.133 13-OCT-08:15 0.000 40096.028 0.000 60360.104 60360.104 60360.104 0.000
November 0.988737E+11 108099.583 24-NOV-09:15 739.434 40096.028 0.000 67264.120 67264.120 67264.120 739.434
December 0.115713E+12 115830.258 29-DEC-09:15 4397.705 40096.028 0.000 71336.525 71336.525 71336.525 4397.705
                     
Annual Sum or Average 0.117596E+13         0.000        
Minimum of Months 0.848812E+11 90755.753   0.000 40096.028 0.000 50659.725 50659.725 50659.725 0.000
Maximum of Months 0.117389E+12 123398.373   14337.366 40096.028 0.000 71540.042 71540.042 71540.042 14337.366