Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:43
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Burlington International Ap VT USA TMY3 WMO#=726170
Simulation Timestamp: 2015-09-14 08:44:10
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3338.39 | 831.77 | 896.19 |
Net Site Energy | 3338.39 | 831.77 | 896.19 |
Total Source Energy | 8047.82 | 2005.15 | 2160.43 |
Net Source Energy | 8047.82 | 2005.15 | 2160.43 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 361.41 | 119.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 671.30 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2126.26 | 1212.13 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 361.41 | 119.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 294.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 671.30 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 236.35 | 212.25 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 570.79 | 325.40 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 219.37 | 196.99 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 529.77 | 302.01 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2126.26 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2126.26 | 100.00 |
Total On-Site and Utility Electric Sources | 2126.26 | 100.00 |
Total Electricity End Uses | 2126.26 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 673.25 |
Time Setpoint Not Met During Occupied Cooling | 3184.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6203.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:43 |
RunPeriod | Burlington International Ap VT USA TMY3 WMO#=726170 |
Weather File | Burlington International Ap VT USA TMY3 WMO#=726170 |
Latitude [deg] | 44.47 |
Longitude [deg] | -73.2 |
Elevation [m] | 101.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -22.40 | 0.00 | -22.40 | Wetbulb [C] | 3.00 | 60.00 |
BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 10.70 | 21.70 | Wetbulb [C] | 4.50 | 170.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.324 | 0.340 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 8.38 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 175.82 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6889.06 | 5170.64 | 1718.42 | 0.75 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21531.17 | 15333.39 | 6197.78 | 0.71 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10478.87 | 7200.44 | 3278.43 | 0.69 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14112.56 | 10734.51 | 3378.05 | 0.76 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6608.2 | 3.24 | 11.05 | 11.70 | 10.97 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20758.5 | 3.00 | 10.23 | 10.85 | 10.37 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10136.1 | 3.36 | 11.45 | 12.14 | 11.58 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13519.2 | 3.22 | 10.99 | 11.64 | 10.87 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.60 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 52382.92 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1183.71 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1183.71 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1632.58 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1509.78 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1192.65 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.53 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.60 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 3736.47 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1183.71 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 4734.86 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3752.54 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4734.86 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1715.18 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1594.16 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4734.52 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1183.63 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4734.52 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1419.14 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 537.13 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 537.26 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 4337.11 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1183.71 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4734.86 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3752.54 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 4734.86 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1404.22 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1723.56 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 4743.09 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1183.63 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4734.52 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1183.63 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 585.30 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 550.64 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 6011.25 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1967.53 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 5057.89 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 4111.35 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 5950.67 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1868.65 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1608.38 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 5890.38 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1676.24 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 5733.27 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1930.45 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 822.87 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4874.01 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 20429.32 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 10939.75 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 8267.99 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.65 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.59 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 1.08 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.36 | 419.90 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.99 | 1134.01 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 511.95 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.76 | 871.47 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 9934.88 | 11921.86 | 0.829 | 0.995 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
RESTROOMFLR1 | 658.60 | 790.32 | 0.055 | 0.066 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.73 | 0.01255 |
MEETINGROOMFLR1 | 4402.60 | 5283.12 | 0.368 | 0.441 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
GUESTROOM101 | 519.09 | 622.91 | 0.046 | 0.055 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM102 | 388.85 | 466.63 | 0.034 | 0.041 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM103 | 1472.32 | 1766.78 | 0.171 | 0.205 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM104 | 1317.68 | 1581.21 | 0.153 | 0.183 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM105 | 1768.06 | 2121.68 | 0.205 | 0.246 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 27.23 | 0.01255 |
EMPLOYEELOUNGEFLR1 | 5651.97 | 6782.36 | 0.472 | 0.566 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
EXERCISECENTERFLR1 | 1324.40 | 1589.28 | 0.110 | 0.133 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.41 | 0.01255 |
FRONTOFFICEFLR1 | 3615.75 | 4338.90 | 0.301 | 0.362 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM201 | 802.69 | 963.23 | 0.071 | 0.085 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
GUESTROOM202_205 | 5928.13 | 7113.76 | 0.687 | 0.825 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM206_208 | 4860.92 | 5833.11 | 0.563 | 0.676 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
GUESTROOM209_212 | 5527.09 | 6632.51 | 0.641 | 0.769 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM213 | 1589.14 | 1906.96 | 0.184 | 0.221 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM214 | 1556.95 | 1868.34 | 0.180 | 0.217 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM215_218 | 8617.39 | 10340.87 | 0.761 | 0.913 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM219 | 5688.02 | 6825.62 | 0.659 | 0.791 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM220_223 | 5267.11 | 6320.54 | 0.611 | 0.733 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM224 | 1565.81 | 1878.97 | 0.182 | 0.218 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM301 | 665.15 | 798.18 | 0.059 | 0.071 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
GUESTROOM302_305 | 1937.96 | 2325.55 | 0.171 | 0.205 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM306_308 | 1766.96 | 2120.35 | 0.156 | 0.187 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM309_312 | 5541.36 | 6649.63 | 0.642 | 0.771 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM313 | 646.93 | 776.31 | 0.057 | 0.069 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 29.27 | 0.01255 |
GUESTROOM314 | 1480.06 | 1776.07 | 0.172 | 0.206 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM315_318 | 5943.33 | 7131.99 | 0.689 | 0.827 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM319 | 835.65 | 1002.78 | 0.074 | 0.089 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM320_323 | 5088.97 | 6106.76 | 0.590 | 0.708 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM324 | 502.54 | 603.04 | 0.044 | 0.053 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 27.64 | 0.01255 |
GUESTROOM401 | 1999.66 | 2399.59 | 0.232 | 0.278 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
GUESTROOM402_405 | 2874.67 | 3449.61 | 0.254 | 0.305 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
GUESTROOM406_408 | 2609.78 | 3131.73 | 0.230 | 0.277 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 30.02 | 0.01255 |
GUESTROOM409_412 | 6733.47 | 8080.16 | 0.781 | 0.937 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.23 | 0.01255 |
GUESTROOM413 | 973.79 | 1168.55 | 0.086 | 0.103 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 30.02 | 0.01255 |
GUESTROOM414 | 747.15 | 896.58 | 0.066 | 0.079 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.30 | 0.01255 |
GUESTROOM415_418 | 6250.00 | 7500.00 | 0.725 | 0.869 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 28.44 | 0.01255 |
GUESTROOM419 | 1713.72 | 2056.47 | 0.199 | 0.238 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 28.84 | 0.01255 |
GUESTROOM420_423 | 6108.01 | 7329.62 | 0.708 | 0.850 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 28.44 | 0.01255 |
GUESTROOM424 | 1735.49 | 2082.59 | 0.201 | 0.241 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 29.11 | 0.01255 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
CORRIDORFLR1 | 16338.67 | 19606.41 | 1.363 | 1.635 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.73 | 0.01255 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
CORRIDORFLR2 | 2939.08 | 3526.90 | 0.245 | 0.294 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.80 | 0.01255 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
CORRIDORFLR3 | 1675.70 | 2010.83 | 0.140 | 0.168 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.53 | 0.01255 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 | |
CORRIDORFLR4 | 2612.37 | 3134.85 | 0.218 | 0.261 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.30 | 0.01255 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.01255 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2118.28 | 2541.93 | 0.060 | 0.236 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -22.40 | 0.00051 |
RESTROOMFLR1 | 81.90 | 98.28 | 0.002 | 0.003 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -22.40 | 0.00051 |
MEETINGROOMFLR1 | 746.83 | 896.19 | 0.021 | 0.126 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -22.40 | 0.00051 |
GUESTROOM101 | 60.21 | 72.25 | 0.002 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -22.40 | 0.00051 |
GUESTROOM102 | 92.03 | 110.44 | 0.002 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -22.40 | 0.00051 |
GUESTROOM103 | 767.66 | 921.19 | 0.022 | 0.026 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -22.40 | 0.00051 |
GUESTROOM104 | 665.37 | 798.44 | 0.019 | 0.023 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -22.40 | 0.00051 |
GUESTROOM105 | 401.09 | 481.31 | 0.011 | 0.014 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -22.40 | 0.00051 |
EMPLOYEELOUNGEFLR1 | 380.15 | 456.18 | 0.011 | 0.051 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -22.40 | 0.00051 |
EXERCISECENTERFLR1 | 233.10 | 279.72 | 0.007 | 0.043 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -22.40 | 0.00051 |
FRONTOFFICEFLR1 | 1335.45 | 1602.54 | 0.038 | 0.056 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -22.40 | 0.00051 |
GUESTROOM201 | 331.86 | 398.24 | 0.009 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -22.40 | 0.00051 |
GUESTROOM202_205 | 1488.45 | 1786.15 | 0.042 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -22.40 | 0.00051 |
GUESTROOM206_208 | 1132.05 | 1358.46 | 0.032 | 0.043 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -22.40 | 0.00051 |
GUESTROOM209_212 | 1228.71 | 1474.45 | 0.035 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -22.40 | 0.00051 |
GUESTROOM213 | 836.49 | 1003.79 | 0.024 | 0.029 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -22.40 | 0.00051 |
GUESTROOM214 | 735.69 | 882.82 | 0.021 | 0.025 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -22.40 | 0.00051 |
GUESTROOM215_218 | 383.55 | 460.26 | 0.010 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | -22.40 | 0.00051 |
GUESTROOM219 | 379.20 | 455.04 | 0.011 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -22.40 | 0.00051 |
GUESTROOM220_223 | 1096.31 | 1315.58 | 0.031 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -22.40 | 0.00051 |
GUESTROOM224 | 589.84 | 707.80 | 0.017 | 0.020 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -22.40 | 0.00051 |
GUESTROOM301 | 421.34 | 505.60 | 0.011 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -22.40 | 0.00051 |
GUESTROOM302_305 | 831.20 | 997.45 | 0.022 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -22.40 | 0.00051 |
GUESTROOM306_308 | 677.31 | 812.78 | 0.018 | 0.043 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -22.40 | 0.00051 |
GUESTROOM309_312 | 1491.21 | 1789.45 | 0.043 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -22.40 | 0.00051 |
GUESTROOM313 | 607.63 | 729.16 | 0.016 | 0.019 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | -22.40 | 0.00051 |
GUESTROOM314 | 843.52 | 1012.22 | 0.024 | 0.029 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
GUESTROOM315_318 | 1581.44 | 1897.73 | 0.045 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -22.40 | 0.00051 |
GUESTROOM319 | 135.57 | 162.68 | 0.004 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -22.40 | 0.00051 |
GUESTROOM320_323 | 1364.53 | 1637.43 | 0.039 | 0.054 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -22.40 | 0.00051 |
GUESTROOM324 | 313.19 | 375.82 | 0.008 | 0.013 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -22.40 | 0.00051 |
GUESTROOM401 | 1046.78 | 1256.14 | 0.030 | 0.036 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -22.40 | 0.00051 |
GUESTROOM402_405 | 1964.71 | 2357.65 | 0.052 | 0.062 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 21:15:00 | -22.40 | 0.00051 |
GUESTROOM406_408 | 1642.76 | 1971.31 | 0.044 | 0.052 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -22.40 | 0.00051 |
GUESTROOM409_412 | 2587.60 | 3105.12 | 0.074 | 0.089 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -22.40 | 0.00051 |
GUESTROOM413 | 994.66 | 1193.59 | 0.026 | 0.032 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -22.40 | 0.00051 |
GUESTROOM414 | 777.81 | 933.37 | 0.021 | 0.025 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | -22.40 | 0.00051 |
GUESTROOM415_418 | 2537.52 | 3045.02 | 0.072 | 0.087 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -22.40 | 0.00051 |
GUESTROOM419 | 804.09 | 964.91 | 0.023 | 0.028 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -22.40 | 0.00051 |
GUESTROOM420_423 | 2406.60 | 2887.92 | 0.069 | 0.082 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -22.40 | 0.00051 |
GUESTROOM424 | 1015.92 | 1219.11 | 0.029 | 0.035 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -22.40 | 0.00051 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -22.40 | 0.00051 | |
CORRIDORFLR1 | 41593.51 | 49912.21 | 1.184 | 1.421 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -22.40 | 0.00051 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -22.40 | 0.00051 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | -22.40 | 0.00051 | |
CORRIDORFLR2 | 1432.53 | 1719.03 | 0.041 | 0.049 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -22.40 | 0.00051 |
FRONTSTAIRSFLR2 | 141.26 | 169.52 | 0.003 | 0.006 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
REARSTAIRSFLR3 | 17.11 | 20.53 | 0.000 | 0.006 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
CORRIDORFLR3 | 1933.04 | 2319.65 | 0.055 | 0.066 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
FRONTSTAIRSFLR3 | 304.79 | 365.74 | 0.006 | 0.007 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
REARSTAIRSFLR4 | 275.86 | 331.03 | 0.005 | 0.006 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
CORRIDORFLR4 | 3328.17 | 3993.81 | 0.095 | 0.114 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
FRONTSTAIRSFLR4 | 502.79 | 603.35 | 0.010 | 0.012 | BURLINGTON INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -22.40 | 0.00051 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.36 | 0.36 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.99 | 0.99 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.44 | 0.44 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.76 | 0.76 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.99 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 2793.00 | 7212.25 | 1940.75 |
RESTROOMFLR1 | 1027.00 | 7251.00 | 582.25 |
MEETINGROOMFLR1 | 1193.25 | 3030.75 | 201.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 2804.50 | 8738.00 | 2803.75 |
GUESTROOM104 | 1911.25 | 8703.00 | 1911.25 |
GUESTROOM105 | 312.25 | 8433.00 | 296.50 |
EMPLOYEELOUNGEFLR1 | 2977.25 | 2285.50 | 367.75 |
EXERCISECENTERFLR1 | 1328.00 | 3230.75 | 74.75 |
FRONTOFFICEFLR1 | 1716.50 | 6134.25 | 781.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1455.75 | 8388.25 | 1404.25 |
GUESTROOM206_208 | 1245.25 | 8374.50 | 1192.75 |
GUESTROOM209_212 | 1028.25 | 8511.50 | 1006.50 |
GUESTROOM213 | 2843.00 | 8639.50 | 2832.25 |
GUESTROOM214 | 1750.75 | 8453.50 | 1724.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3148.50 | 4662.25 | 273.25 |
GUESTROOM220_223 | 667.50 | 8224.75 | 609.50 |
GUESTROOM224 | 1721.25 | 8364.75 | 1689.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1547.25 | 8543.00 | 1528.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 2647.00 | 8466.50 | 2611.50 |
GUESTROOM315_318 | 786.25 | 8140.00 | 710.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1168.00 | 8351.75 | 1123.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 4151.25 | 8186.75 | 3973.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 2902.50 | 7973.50 | 2579.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2513.75 | 7816.50 | 2075.00 |
GUESTROOM419 | 2528.50 | 7955.25 | 2344.25 |
GUESTROOM420_423 | 2577.50 | 7833.25 | 2163.00 |
GUESTROOM424 | 3352.75 | 8026.00 | 3175.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7425.25 | 8760.00 | 6203.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.50 | 0.00 | 0.50 | 0.00 |
RESTROOMFLR1 | 464.75 | 695.00 | 464.75 | 695.00 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 22.75 | 31.50 | 22.75 | 31.50 |
GUESTROOM104 | 18.00 | 31.00 | 18.00 | 31.00 |
GUESTROOM105 | 1.00 | 40.75 | 1.00 | 40.75 |
EMPLOYEELOUNGEFLR1 | 538.50 | 1332.00 | 387.75 | 911.00 |
EXERCISECENTERFLR1 | 0.75 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 14.25 | 22.25 | 14.25 | 22.25 |
GUESTROOM206_208 | 12.50 | 29.25 | 12.50 | 29.25 |
GUESTROOM209_212 | 11.75 | 21.50 | 11.75 | 21.50 |
GUESTROOM213 | 23.25 | 22.25 | 23.25 | 22.25 |
GUESTROOM214 | 16.50 | 22.00 | 16.50 | 22.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2039.75 | 0.00 | 2039.75 |
GUESTROOM220_223 | 6.50 | 20.50 | 6.50 | 20.50 |
GUESTROOM224 | 17.50 | 21.75 | 17.50 | 21.75 |
GUESTROOM301 | 5.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 18.50 | 21.75 | 18.50 | 21.75 |
GUESTROOM313 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 23.50 | 21.75 | 23.50 | 21.75 |
GUESTROOM315_318 | 9.00 | 22.00 | 9.00 | 22.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 16.75 | 20.00 | 16.75 | 20.00 |
GUESTROOM324 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 24.00 | 33.50 | 24.00 | 33.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 24.00 | 29.00 | 24.00 | 29.00 |
GUESTROOM413 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 23.75 | 23.50 | 23.75 | 23.50 |
GUESTROOM419 | 23.50 | 28.25 | 23.50 | 28.25 |
GUESTROOM420_423 | 25.25 | 23.25 | 25.25 | 23.25 |
GUESTROOM424 | 20.75 | 27.00 | 20.75 | 27.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 6.00 | 2315.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 85.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 5.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 7.50 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 8.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 121.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 3.25 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 720.50 | 4001.75 | 673.25 | 3184.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:10
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.007041 |
REARSTAIRSFLR4 UNITHEATER | 0.006373 |
FRONTSTAIRSFLR4 UNITHEATER | 0.011615 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.007041 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006373 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.011615 |
SAC_FRONTOFFICE SUPPLY FAN | 0.361725 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.994653 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.764377 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 317.60 |
CORRIDORFLR1 PTAC HEATING COIL | 52382.92 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1183.71 |
102 PTAC HEATING COIL | 1183.71 |
103 PTAC HEATING COIL | 1632.58 |
104 PTAC HEATING COIL | 1509.78 |
105 PTAC HEATING COIL | 1192.65 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 317.53 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 317.60 |
CORRIDORFLR2 PTAC HEATING COIL | 3736.47 |
201 PTAC HEATING COIL | 1183.71 |
202_205 PTAC HEATING COIL | 4734.86 |
206_208 PTAC HEATING COIL | 3752.54 |
209_212 PTAC HEATING COIL | 4734.86 |
213 PTAC HEATING COIL | 1715.18 |
214 PTAC HEATING COIL | 1594.16 |
215_218 PTAC HEATING COIL | 4734.52 |
219 PTAC HEATING COIL | 1183.63 |
220_223 PTAC HEATING COIL | 4734.52 |
224 PTAC HEATING COIL | 1419.14 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 537.13 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 537.26 |
CORRIDORFLR3 PTAC HEATING COIL | 4337.11 |
301 PTAC HEATING COIL | 1183.71 |
302_305 PTAC HEATING COIL | 4734.86 |
306_308 PTAC HEATING COIL | 3752.54 |
309_312 PTAC HEATING COIL | 4734.86 |
313 PTAC HEATING COIL | 1404.22 |
314 PTAC HEATING COIL | 1723.56 |
315_318 PTAC HEATING COIL | 4743.09 |
319 PTAC HEATING COIL | 1183.63 |
320_323 PTAC HEATING COIL | 4734.52 |
324 PTAC HEATING COIL | 1183.63 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 585.30 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 550.64 |
CORRIDORFLR4 PTAC HEATING COIL | 6011.25 |
401 PTAC HEATING COIL | 1967.53 |
402_405 PTAC HEATING COIL | 5057.89 |
406_408 PTAC HEATING COIL | 4111.35 |
409_412 PTAC HEATING COIL | 5950.67 |
413 PTAC HEATING COIL | 1868.65 |
414 PTAC HEATING COIL | 1608.38 |
415_418 PTAC HEATING COIL | 5890.38 |
419 PTAC HEATING COIL | 1676.24 |
420_423 PTAC HEATING COIL | 5733.27 |
424 PTAC HEATING COIL | 1930.45 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 822.87 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.750558 | 0.361725 | 6889.06 |
SAC_FRONTLOUNGE COOLING COIL | 0.712149 | 0.994653 | 21531.17 |
SAC_MEETINGROOM COOLING COIL | 0.687139 | 0.441020 | 10478.87 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.760635 | 0.764377 | 14112.56 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.994653 |
RESTROOMFLR1 DIRECT AIR | 0.065876 |
MEETINGROOMFLR1 DIRECT AIR | 0.441020 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.565960 |
EXERCISECENTERFLR1 DIRECT AIR | 0.132540 |
FRONTOFFICEFLR1 DIRECT AIR | 0.361725 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.361725 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.994653 |
SAC_MEETINGROOM MAIN BRANCH | 0.441020 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.764377 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.361725 |
SAC_FRONTLOUNGE | 0.994653 |
SAC_MEETINGROOM | 0.441020 |
SAC_EXC_EMPLGE_RESTRM | 0.764377 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.361725 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.994653 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.441020 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.764377 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.361725 | 0.361725 | 0.361725 | 0.361725 | 4874.01 | 6889.06 | 1.00 |
SAC_FRONTLOUNGE | 0.994653 | 0.994653 | 0.994653 | 0.994653 | 20429.32 | 21531.17 | 1.00 |
SAC_MEETINGROOM | 0.441020 | 0.441020 | 0.441020 | 0.441020 | 10939.75 | 10478.87 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.764377 | 0.764377 | 0.764377 | 0.764377 | 8267.99 | 14112.56 | 0.173396 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4874.01 |
SAC_FRONTLOUNGE HEATING COIL | 20429.32 |
SAC_MEETINGROOM HEATING COIL | 10939.75 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 8267.99 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.441020 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.31 | -7.2 |
February | 14.61 | -5.6 |
March | 16.73 | -0.5 |
April | 19.49 | 7.83 |
May | 21.62 | 13.82 |
June | 23.40 | 19.28 |
July | 24.04 | 21.06 |
August | 23.70 | 19.79 |
September | 22.01 | 15.09 |
October | 19.97 | 8.66 |
November | 17.68 | 2.78 |
December | 15.67 | -1.5 |
Annual Sum or Average | 19.46 | 7.87 |
Minimum of Months | 14.31 | -7.2 |
Maximum of Months | 24.04 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | -7.2 |
February | 21.38 | -5.6 |
March | 22.01 | -0.5 |
April | 23.20 | 7.83 |
May | 24.07 | 13.82 |
June | 25.18 | 19.28 |
July | 25.64 | 21.06 |
August | 25.36 | 19.79 |
September | 24.35 | 15.09 |
October | 23.32 | 8.66 |
November | 22.27 | 2.78 |
December | 21.71 | -1.5 |
Annual Sum or Average | 23.32 | 7.87 |
Minimum of Months | 21.25 | -7.2 |
Maximum of Months | 25.64 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.56 | -7.2 |
February | 13.84 | -5.6 |
March | 15.89 | -0.5 |
April | 18.65 | 7.83 |
May | 20.84 | 13.82 |
June | 22.70 | 19.28 |
July | 23.34 | 21.06 |
August | 23.00 | 19.79 |
September | 21.27 | 15.09 |
October | 19.14 | 8.66 |
November | 16.84 | 2.78 |
December | 14.90 | -1.5 |
Annual Sum or Average | 18.69 | 7.87 |
Minimum of Months | 13.56 | -7.2 |
Maximum of Months | 23.34 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -7.2 |
February | 21.12 | -5.6 |
March | 21.19 | -0.5 |
April | 21.75 | 7.83 |
May | 22.54 | 13.82 |
June | 23.32 | 19.28 |
July | 23.51 | 21.06 |
August | 23.40 | 19.79 |
September | 22.63 | 15.09 |
October | 21.60 | 8.66 |
November | 21.18 | 2.78 |
December | 21.14 | -1.5 |
Annual Sum or Average | 22.05 | 7.87 |
Minimum of Months | 21.11 | -7.2 |
Maximum of Months | 23.51 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | -7.2 |
February | 21.40 | -5.6 |
March | 21.85 | -0.5 |
April | 22.55 | 7.83 |
May | 23.11 | 13.82 |
June | 23.54 | 19.28 |
July | 23.63 | 21.06 |
August | 23.58 | 19.79 |
September | 23.26 | 15.09 |
October | 22.69 | 8.66 |
November | 22.14 | 2.78 |
December | 21.70 | -1.5 |
Annual Sum or Average | 22.57 | 7.87 |
Minimum of Months | 21.31 | -7.2 |
Maximum of Months | 23.63 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.21 | -7.2 |
February | 21.26 | -5.6 |
March | 21.66 | -0.5 |
April | 22.58 | 7.83 |
May | 23.51 | 13.82 |
June | 23.79 | 19.28 |
July | 23.83 | 21.06 |
August | 23.82 | 19.79 |
September | 23.52 | 15.09 |
October | 22.77 | 8.66 |
November | 21.72 | 2.78 |
December | 21.38 | -1.5 |
Annual Sum or Average | 22.60 | 7.87 |
Minimum of Months | 21.21 | -7.2 |
Maximum of Months | 23.83 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.48 | -7.2 |
February | 23.57 | -5.6 |
March | 24.16 | -0.5 |
April | 25.17 | 7.83 |
May | 25.98 | 13.82 |
June | 26.54 | 19.28 |
July | 26.69 | 21.06 |
August | 26.62 | 19.79 |
September | 26.09 | 15.09 |
October | 25.32 | 8.66 |
November | 24.42 | 2.78 |
December | 23.84 | -1.5 |
Annual Sum or Average | 25.16 | 7.87 |
Minimum of Months | 23.48 | -7.2 |
Maximum of Months | 26.69 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -7.2 |
February | 18.99 | -5.6 |
March | 19.53 | -0.5 |
April | 20.96 | 7.83 |
May | 22.29 | 13.82 |
June | 23.07 | 19.28 |
July | 23.18 | 21.06 |
August | 23.11 | 19.79 |
September | 22.44 | 15.09 |
October | 21.14 | 8.66 |
November | 19.73 | 2.78 |
December | 19.21 | -1.5 |
Annual Sum or Average | 21.06 | 7.87 |
Minimum of Months | 18.90 | -7.2 |
Maximum of Months | 23.18 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.93 | -5.6 |
March | 19.34 | -0.5 |
April | 20.64 | 7.83 |
May | 21.98 | 13.82 |
June | 22.90 | 19.28 |
July | 23.06 | 21.06 |
August | 22.97 | 19.79 |
September | 22.15 | 15.09 |
October | 20.76 | 8.66 |
November | 19.45 | 2.78 |
December | 19.07 | -1.5 |
Annual Sum or Average | 20.86 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.06 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -7.2 |
February | 20.52 | -5.6 |
March | 20.70 | -0.5 |
April | 21.15 | 7.83 |
May | 21.58 | 13.82 |
June | 21.74 | 19.28 |
July | 21.75 | 21.06 |
August | 21.74 | 19.79 |
September | 21.59 | 15.09 |
October | 21.24 | 8.66 |
November | 20.79 | 2.78 |
December | 20.60 | -1.5 |
Annual Sum or Average | 21.16 | 7.87 |
Minimum of Months | 20.48 | -7.2 |
Maximum of Months | 21.75 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -7.2 |
February | 20.60 | -5.6 |
March | 20.90 | -0.5 |
April | 21.37 | 7.83 |
May | 21.69 | 13.82 |
June | 21.75 | 19.28 |
July | 21.75 | 21.06 |
August | 21.75 | 19.79 |
September | 21.67 | 15.09 |
October | 21.44 | 8.66 |
November | 20.98 | 2.78 |
December | 20.71 | -1.5 |
Annual Sum or Average | 21.26 | 7.87 |
Minimum of Months | 20.52 | -7.2 |
Maximum of Months | 21.75 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | -7.2 |
February | 20.98 | -5.6 |
March | 21.28 | -0.5 |
April | 21.63 | 7.83 |
May | 21.75 | 13.82 |
June | 21.75 | 19.28 |
July | 21.76 | 21.06 |
August | 21.75 | 19.79 |
September | 21.74 | 15.09 |
October | 21.69 | 8.66 |
November | 21.39 | 2.78 |
December | 21.12 | -1.5 |
Annual Sum or Average | 21.48 | 7.87 |
Minimum of Months | 20.88 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.83 | -7.2 |
February | 21.93 | -5.6 |
March | 22.23 | -0.5 |
April | 22.52 | 7.83 |
May | 22.68 | 13.82 |
June | 22.67 | 19.28 |
July | 22.58 | 21.06 |
August | 22.64 | 19.79 |
September | 22.80 | 15.09 |
October | 22.70 | 8.66 |
November | 22.54 | 2.78 |
December | 22.25 | -1.5 |
Annual Sum or Average | 22.45 | 7.87 |
Minimum of Months | 21.83 | -7.2 |
Maximum of Months | 22.80 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 49.61 | -7.2 |
February | 49.75 | -5.6 |
March | 50.51 | -0.5 |
April | 51.51 | 7.83 |
May | 52.24 | 13.82 |
June | 52.82 | 19.28 |
July | 53.04 | 21.06 |
August | 52.93 | 19.79 |
September | 52.31 | 15.09 |
October | 51.60 | 8.66 |
November | 50.80 | 2.78 |
December | 50.08 | -1.5 |
Annual Sum or Average | 51.44 | 7.87 |
Minimum of Months | 49.61 | -7.2 |
Maximum of Months | 53.04 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 67.27 | -7.2 |
February | 67.27 | -5.6 |
March | 68.24 | -0.5 |
April | 69.33 | 7.83 |
May | 70.36 | 13.82 |
June | 71.07 | 19.28 |
July | 71.45 | 21.06 |
August | 71.28 | 19.79 |
September | 70.49 | 15.09 |
October | 69.62 | 8.66 |
November | 68.59 | 2.78 |
December | 67.68 | -1.5 |
Annual Sum or Average | 69.40 | 7.87 |
Minimum of Months | 67.27 | -7.2 |
Maximum of Months | 71.45 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.09 | -7.2 |
February | 22.22 | -5.6 |
March | 22.64 | -0.5 |
April | 23.22 | 7.83 |
May | 23.60 | 13.82 |
June | 23.84 | 19.28 |
July | 23.86 | 21.06 |
August | 23.84 | 19.79 |
September | 23.72 | 15.09 |
October | 23.36 | 8.66 |
November | 22.93 | 2.78 |
December | 22.52 | -1.5 |
Annual Sum or Average | 23.16 | 7.87 |
Minimum of Months | 22.09 | -7.2 |
Maximum of Months | 23.86 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | -7.2 |
February | 21.44 | -5.6 |
March | 22.00 | -0.5 |
April | 22.97 | 7.83 |
May | 23.68 | 13.82 |
June | 23.87 | 19.28 |
July | 23.88 | 21.06 |
August | 23.87 | 19.79 |
September | 23.74 | 15.09 |
October | 23.23 | 8.66 |
November | 22.24 | 2.78 |
December | 21.69 | -1.5 |
Annual Sum or Average | 22.83 | 7.87 |
Minimum of Months | 21.29 | -7.2 |
Maximum of Months | 23.88 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.08 | -7.2 |
February | 13.38 | -5.6 |
March | 15.74 | -0.5 |
April | 18.98 | 7.83 |
May | 21.57 | 13.82 |
June | 23.76 | 19.28 |
July | 24.47 | 21.06 |
August | 23.97 | 19.79 |
September | 21.98 | 15.09 |
October | 19.52 | 8.66 |
November | 16.96 | 2.78 |
December | 14.74 | -1.5 |
Annual Sum or Average | 19.04 | 7.87 |
Minimum of Months | 13.08 | -7.2 |
Maximum of Months | 24.47 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.76 | -7.2 |
February | 17.95 | -5.6 |
March | 19.35 | -0.5 |
April | 21.39 | 7.83 |
May | 22.96 | 13.82 |
June | 24.18 | 19.28 |
July | 24.57 | 21.06 |
August | 24.32 | 19.79 |
September | 23.21 | 15.09 |
October | 21.73 | 8.66 |
November | 20.07 | 2.78 |
December | 18.71 | -1.5 |
Annual Sum or Average | 21.37 | 7.87 |
Minimum of Months | 17.76 | -7.2 |
Maximum of Months | 24.57 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.74 | -7.2 |
February | 13.16 | -5.6 |
March | 15.85 | -0.5 |
April | 19.36 | 7.83 |
May | 22.04 | 13.82 |
June | 24.17 | 19.28 |
July | 24.92 | 21.06 |
August | 24.48 | 19.79 |
September | 22.44 | 15.09 |
October | 19.86 | 8.66 |
November | 16.96 | 2.78 |
December | 14.45 | -1.5 |
Annual Sum or Average | 19.23 | 7.87 |
Minimum of Months | 12.74 | -7.2 |
Maximum of Months | 24.92 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -7.2 |
February | 21.15 | -5.6 |
March | 21.58 | -0.5 |
April | 22.72 | 7.83 |
May | 23.72 | 13.82 |
June | 23.90 | 19.28 |
July | 23.93 | 21.06 |
August | 23.89 | 19.79 |
September | 23.68 | 15.09 |
October | 22.93 | 8.66 |
November | 21.68 | 2.78 |
December | 21.28 | -1.5 |
Annual Sum or Average | 22.64 | 7.87 |
Minimum of Months | 21.11 | -7.2 |
Maximum of Months | 23.93 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.54 | -7.2 |
February | 11.93 | -5.6 |
March | 14.51 | -0.5 |
April | 18.05 | 7.83 |
May | 20.85 | 13.82 |
June | 23.16 | 19.28 |
July | 23.91 | 21.06 |
August | 23.46 | 19.79 |
September | 21.32 | 15.09 |
October | 18.52 | 8.66 |
November | 15.62 | 2.78 |
December | 13.23 | -1.5 |
Annual Sum or Average | 18.04 | 7.87 |
Minimum of Months | 11.54 | -7.2 |
Maximum of Months | 23.91 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.13 | -0.5 |
April | 20.34 | 7.83 |
May | 22.12 | 13.82 |
June | 23.17 | 19.28 |
July | 23.24 | 21.06 |
August | 23.16 | 19.79 |
September | 22.15 | 15.09 |
October | 20.14 | 8.66 |
November | 19.06 | 2.78 |
December | 18.92 | -1.5 |
Annual Sum or Average | 20.78 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.24 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -7.2 |
February | 20.60 | -5.6 |
March | 20.84 | -0.5 |
April | 21.33 | 7.83 |
May | 21.71 | 13.82 |
June | 21.75 | 19.28 |
July | 21.75 | 21.06 |
August | 21.75 | 19.79 |
September | 21.69 | 15.09 |
October | 21.40 | 8.66 |
November | 20.93 | 2.78 |
December | 20.70 | -1.5 |
Annual Sum or Average | 21.25 | 7.87 |
Minimum of Months | 20.52 | -7.2 |
Maximum of Months | 21.75 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -7.2 |
February | 20.63 | -5.6 |
March | 20.89 | -0.5 |
April | 21.38 | 7.83 |
May | 21.72 | 13.82 |
June | 21.75 | 19.28 |
July | 21.76 | 21.06 |
August | 21.75 | 19.79 |
September | 21.70 | 15.09 |
October | 21.46 | 8.66 |
November | 21.00 | 2.78 |
December | 20.74 | -1.5 |
Annual Sum or Average | 21.28 | 7.87 |
Minimum of Months | 20.55 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -7.2 |
February | 20.63 | -5.6 |
March | 20.90 | -0.5 |
April | 21.39 | 7.83 |
May | 21.72 | 13.82 |
June | 21.75 | 19.28 |
July | 21.75 | 21.06 |
August | 21.75 | 19.79 |
September | 21.70 | 15.09 |
October | 21.48 | 8.66 |
November | 21.03 | 2.78 |
December | 20.76 | -1.5 |
Annual Sum or Average | 21.29 | 7.87 |
Minimum of Months | 20.55 | -7.2 |
Maximum of Months | 21.75 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -7.2 |
February | 20.50 | -5.6 |
March | 20.69 | -0.5 |
April | 21.17 | 7.83 |
May | 21.64 | 13.82 |
June | 21.75 | 19.28 |
July | 21.75 | 21.06 |
August | 21.75 | 19.79 |
September | 21.62 | 15.09 |
October | 21.24 | 8.66 |
November | 20.75 | 2.78 |
December | 20.57 | -1.5 |
Annual Sum or Average | 21.16 | 7.87 |
Minimum of Months | 20.47 | -7.2 |
Maximum of Months | 21.75 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -7.2 |
February | 20.60 | -5.6 |
March | 20.94 | -0.5 |
April | 21.44 | 7.83 |
May | 21.73 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.71 | 15.09 |
October | 21.52 | 8.66 |
November | 21.02 | 2.78 |
December | 20.71 | -1.5 |
Annual Sum or Average | 21.29 | 7.87 |
Minimum of Months | 20.51 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | -7.2 |
February | 21.79 | -5.6 |
March | 22.54 | -0.5 |
April | 23.20 | 7.83 |
May | 23.33 | 13.82 |
June | 23.33 | 19.28 |
July | 23.33 | 21.06 |
August | 23.33 | 19.79 |
September | 23.33 | 15.09 |
October | 23.28 | 8.66 |
November | 22.94 | 2.78 |
December | 22.27 | -1.5 |
Annual Sum or Average | 22.86 | 7.87 |
Minimum of Months | 21.52 | -7.2 |
Maximum of Months | 23.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 28.93 | -7.2 |
February | 28.98 | -5.6 |
March | 29.97 | -0.5 |
April | 31.34 | 7.83 |
May | 32.51 | 13.82 |
June | 33.22 | 19.28 |
July | 33.48 | 21.06 |
August | 33.32 | 19.79 |
September | 32.56 | 15.09 |
October | 31.50 | 8.66 |
November | 30.28 | 2.78 |
December | 29.38 | -1.5 |
Annual Sum or Average | 31.30 | 7.87 |
Minimum of Months | 28.93 | -7.2 |
Maximum of Months | 33.48 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -7.2 |
February | 21.74 | -5.6 |
March | 21.80 | -0.5 |
April | 22.06 | 7.83 |
May | 22.37 | 13.82 |
June | 22.78 | 19.28 |
July | 22.96 | 21.06 |
August | 22.84 | 19.79 |
September | 22.46 | 15.09 |
October | 22.05 | 8.66 |
November | 21.81 | 2.78 |
December | 21.75 | -1.5 |
Annual Sum or Average | 22.20 | 7.87 |
Minimum of Months | 21.73 | -7.2 |
Maximum of Months | 22.96 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -7.2 |
February | 20.76 | -5.6 |
March | 21.09 | -0.5 |
April | 21.55 | 7.83 |
May | 21.75 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.73 | 15.09 |
October | 21.62 | 8.66 |
November | 21.17 | 2.78 |
December | 20.89 | -1.5 |
Annual Sum or Average | 21.38 | 7.87 |
Minimum of Months | 20.64 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -7.2 |
February | 20.61 | -5.6 |
March | 20.94 | -0.5 |
April | 21.46 | 7.83 |
May | 21.74 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.72 | 15.09 |
October | 21.53 | 8.66 |
November | 21.00 | 2.78 |
December | 20.72 | -1.5 |
Annual Sum or Average | 21.29 | 7.87 |
Minimum of Months | 20.52 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.96 | -7.2 |
February | 16.24 | -5.6 |
March | 18.07 | -0.5 |
April | 20.82 | 7.83 |
May | 22.91 | 13.82 |
June | 24.55 | 19.28 |
July | 25.03 | 21.06 |
August | 24.66 | 19.79 |
September | 23.17 | 15.09 |
October | 21.10 | 8.66 |
November | 18.91 | 2.78 |
December | 17.16 | -1.5 |
Annual Sum or Average | 20.74 | 7.87 |
Minimum of Months | 15.96 | -7.2 |
Maximum of Months | 25.03 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.76 | -7.2 |
February | 11.23 | -5.6 |
March | 14.20 | -0.5 |
April | 18.45 | 7.83 |
May | 21.83 | 13.82 |
June | 24.58 | 19.28 |
July | 25.46 | 21.06 |
August | 24.78 | 19.79 |
September | 22.29 | 15.09 |
October | 19.01 | 8.66 |
November | 15.64 | 2.78 |
December | 12.83 | -1.5 |
Annual Sum or Average | 18.46 | 7.87 |
Minimum of Months | 10.76 | -7.2 |
Maximum of Months | 25.46 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.64 | -7.2 |
February | 12.12 | -5.6 |
March | 14.95 | -0.5 |
April | 18.79 | 7.83 |
May | 21.82 | 13.82 |
June | 24.25 | 19.28 |
July | 25.06 | 21.06 |
August | 24.55 | 19.79 |
September | 22.23 | 15.09 |
October | 19.21 | 8.66 |
November | 16.06 | 2.78 |
December | 13.45 | -1.5 |
Annual Sum or Average | 18.71 | 7.87 |
Minimum of Months | 11.64 | -7.2 |
Maximum of Months | 25.06 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -7.2 |
February | 21.11 | -5.6 |
March | 21.20 | -0.5 |
April | 21.94 | 7.83 |
May | 23.13 | 13.82 |
June | 23.82 | 19.28 |
July | 23.85 | 21.06 |
August | 23.81 | 19.79 |
September | 23.12 | 15.09 |
October | 21.73 | 8.66 |
November | 21.17 | 2.78 |
December | 21.11 | -1.5 |
Annual Sum or Average | 22.27 | 7.87 |
Minimum of Months | 21.11 | -7.2 |
Maximum of Months | 23.85 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.03 | -7.2 |
February | 10.50 | -5.6 |
March | 13.25 | -0.5 |
April | 17.23 | 7.83 |
May | 20.49 | 13.82 |
June | 23.25 | 19.28 |
July | 24.09 | 21.06 |
August | 23.55 | 19.79 |
September | 20.99 | 15.09 |
October | 17.56 | 8.66 |
November | 14.38 | 2.78 |
December | 11.87 | -1.5 |
Annual Sum or Average | 17.30 | 7.87 |
Minimum of Months | 10.03 | -7.2 |
Maximum of Months | 24.09 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.88 | -7.2 |
February | 18.89 | -5.6 |
March | 18.98 | -0.5 |
April | 19.96 | 7.83 |
May | 21.66 | 13.82 |
June | 23.06 | 19.28 |
July | 23.17 | 21.06 |
August | 23.05 | 19.79 |
September | 21.72 | 15.09 |
October | 19.53 | 8.66 |
November | 18.92 | 2.78 |
December | 18.89 | -1.5 |
Annual Sum or Average | 20.57 | 7.87 |
Minimum of Months | 18.88 | -7.2 |
Maximum of Months | 23.17 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.07 | -0.5 |
April | 20.24 | 7.83 |
May | 22.01 | 13.82 |
June | 23.17 | 19.28 |
July | 23.24 | 21.06 |
August | 23.15 | 19.79 |
September | 22.02 | 15.09 |
October | 19.87 | 8.66 |
November | 18.99 | 2.78 |
December | 18.90 | -1.5 |
Annual Sum or Average | 20.71 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.24 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.15 | -0.5 |
April | 20.38 | 7.83 |
May | 22.13 | 13.82 |
June | 23.17 | 19.28 |
July | 23.24 | 21.06 |
August | 23.15 | 19.79 |
September | 22.11 | 15.09 |
October | 20.07 | 8.66 |
November | 19.04 | 2.78 |
December | 18.91 | -1.5 |
Annual Sum or Average | 20.77 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.24 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -7.2 |
February | 20.58 | -5.6 |
March | 20.83 | -0.5 |
April | 21.32 | 7.83 |
May | 21.70 | 13.82 |
June | 21.75 | 19.28 |
July | 21.75 | 21.06 |
August | 21.75 | 19.79 |
September | 21.67 | 15.09 |
October | 21.39 | 8.66 |
November | 20.92 | 2.78 |
December | 20.68 | -1.5 |
Annual Sum or Average | 21.24 | 7.87 |
Minimum of Months | 20.51 | -7.2 |
Maximum of Months | 21.75 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.06 | -0.5 |
April | 20.18 | 7.83 |
May | 21.87 | 13.82 |
June | 23.11 | 19.28 |
July | 23.22 | 21.06 |
August | 23.12 | 19.79 |
September | 21.97 | 15.09 |
October | 19.88 | 8.66 |
November | 18.99 | 2.78 |
December | 18.89 | -1.5 |
Annual Sum or Average | 20.68 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.22 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -7.2 |
February | 20.52 | -5.6 |
March | 20.80 | -0.5 |
April | 21.32 | 7.83 |
May | 21.71 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.66 | 15.09 |
October | 21.36 | 8.66 |
November | 20.82 | 2.78 |
December | 20.59 | -1.5 |
Annual Sum or Average | 21.21 | 7.87 |
Minimum of Months | 20.48 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -7.2 |
February | 20.75 | -5.6 |
March | 21.11 | -0.5 |
April | 21.57 | 7.83 |
May | 21.75 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.74 | 15.09 |
October | 21.62 | 8.66 |
November | 21.18 | 2.78 |
December | 20.88 | -1.5 |
Annual Sum or Average | 21.38 | 7.87 |
Minimum of Months | 20.62 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | -7.2 |
February | 20.27 | -5.6 |
March | 21.49 | -0.5 |
April | 23.33 | 7.83 |
May | 24.87 | 13.82 |
June | 25.84 | 19.28 |
July | 26.06 | 21.06 |
August | 25.88 | 19.79 |
September | 24.89 | 15.09 |
October | 23.37 | 8.66 |
November | 21.82 | 2.78 |
December | 20.74 | -1.5 |
Annual Sum or Average | 23.24 | 7.87 |
Minimum of Months | 20.10 | -7.2 |
Maximum of Months | 26.06 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.04 | -7.2 |
February | 19.28 | -5.6 |
March | 20.34 | -0.5 |
April | 22.09 | 7.83 |
May | 23.19 | 13.82 |
June | 23.33 | 19.28 |
July | 23.33 | 21.06 |
August | 23.32 | 19.79 |
September | 23.12 | 15.09 |
October | 22.27 | 8.66 |
November | 20.59 | 2.78 |
December | 19.68 | -1.5 |
Annual Sum or Average | 21.64 | 7.87 |
Minimum of Months | 19.04 | -7.2 |
Maximum of Months | 23.33 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -7.2 |
February | 20.66 | -5.6 |
March | 20.98 | -0.5 |
April | 21.47 | 7.83 |
May | 21.73 | 13.82 |
June | 21.75 | 19.28 |
July | 21.76 | 21.06 |
August | 21.75 | 19.79 |
September | 21.71 | 15.09 |
October | 21.51 | 8.66 |
November | 21.02 | 2.78 |
December | 20.75 | -1.5 |
Annual Sum or Average | 21.31 | 7.87 |
Minimum of Months | 20.55 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.24 | -0.5 |
April | 20.77 | 7.83 |
May | 22.46 | 13.82 |
June | 23.23 | 19.28 |
July | 23.28 | 21.06 |
August | 23.23 | 19.79 |
September | 22.44 | 15.09 |
October | 20.65 | 8.66 |
November | 19.20 | 2.78 |
December | 18.93 | -1.5 |
Annual Sum or Average | 20.95 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.28 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.52 | -7.2 |
February | 14.86 | -5.6 |
March | 16.83 | -0.5 |
April | 20.05 | 7.83 |
May | 22.63 | 13.82 |
June | 24.66 | 19.28 |
July | 25.21 | 21.06 |
August | 24.76 | 19.79 |
September | 22.90 | 15.09 |
October | 20.21 | 8.66 |
November | 17.64 | 2.78 |
December | 15.79 | -1.5 |
Annual Sum or Average | 20.03 | 7.87 |
Minimum of Months | 14.52 | -7.2 |
Maximum of Months | 25.21 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.50 | -7.2 |
February | 10.09 | -5.6 |
March | 13.13 | -0.5 |
April | 17.80 | 7.83 |
May | 21.59 | 13.82 |
June | 24.71 | 19.28 |
July | 25.67 | 21.06 |
August | 24.90 | 19.79 |
September | 22.07 | 15.09 |
October | 18.28 | 8.66 |
November | 14.55 | 2.78 |
December | 11.67 | -1.5 |
Annual Sum or Average | 17.87 | 7.87 |
Minimum of Months | 9.50 | -7.2 |
Maximum of Months | 25.67 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.24 | -7.2 |
February | 10.87 | -5.6 |
March | 13.76 | -0.5 |
April | 17.97 | 7.83 |
May | 21.46 | 13.82 |
June | 24.30 | 19.28 |
July | 25.20 | 21.06 |
August | 24.58 | 19.79 |
September | 21.81 | 15.09 |
October | 18.21 | 8.66 |
November | 14.74 | 2.78 |
December | 12.15 | -1.5 |
Annual Sum or Average | 17.98 | 7.87 |
Minimum of Months | 10.24 | -7.2 |
Maximum of Months | 25.20 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -7.2 |
February | 21.11 | -5.6 |
March | 21.21 | -0.5 |
April | 21.78 | 7.83 |
May | 22.65 | 13.82 |
June | 23.53 | 19.28 |
July | 23.70 | 21.06 |
August | 23.56 | 19.79 |
September | 22.70 | 15.09 |
October | 21.47 | 8.66 |
November | 21.14 | 2.78 |
December | 21.11 | -1.5 |
Annual Sum or Average | 22.09 | 7.87 |
Minimum of Months | 21.11 | -7.2 |
Maximum of Months | 23.70 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.85 | -7.2 |
February | 9.44 | -5.6 |
March | 12.38 | -0.5 |
April | 16.67 | 7.83 |
May | 20.21 | 13.82 |
June | 23.27 | 19.28 |
July | 24.19 | 21.06 |
August | 23.55 | 19.79 |
September | 20.63 | 15.09 |
October | 16.84 | 8.66 |
November | 13.45 | 2.78 |
December | 10.85 | -1.5 |
Annual Sum or Average | 16.74 | 7.87 |
Minimum of Months | 8.85 | -7.2 |
Maximum of Months | 24.19 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -7.2 |
February | 20.47 | -5.6 |
March | 20.58 | -0.5 |
April | 21.00 | 7.83 |
May | 21.59 | 13.82 |
June | 21.75 | 19.28 |
July | 21.76 | 21.06 |
August | 21.75 | 19.79 |
September | 21.51 | 15.09 |
October | 20.94 | 8.66 |
November | 20.55 | 2.78 |
December | 20.49 | -1.5 |
Annual Sum or Average | 21.07 | 7.87 |
Minimum of Months | 20.47 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.07 | -0.5 |
April | 20.04 | 7.83 |
May | 21.50 | 13.82 |
June | 22.87 | 19.28 |
July | 23.02 | 21.06 |
August | 22.88 | 19.79 |
September | 21.55 | 15.09 |
October | 19.55 | 8.66 |
November | 18.94 | 2.78 |
December | 18.89 | -1.5 |
Annual Sum or Average | 20.52 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.02 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.12 | -0.5 |
April | 20.11 | 7.83 |
May | 21.56 | 13.82 |
June | 22.86 | 19.28 |
July | 23.02 | 21.06 |
August | 22.88 | 19.79 |
September | 21.60 | 15.09 |
October | 19.65 | 8.66 |
November | 18.96 | 2.78 |
December | 18.89 | -1.5 |
Annual Sum or Average | 20.55 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.02 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -7.2 |
February | 20.55 | -5.6 |
March | 20.82 | -0.5 |
April | 21.34 | 7.83 |
May | 21.71 | 13.82 |
June | 21.75 | 19.28 |
July | 21.76 | 21.06 |
August | 21.75 | 19.79 |
September | 21.68 | 15.09 |
October | 21.37 | 8.66 |
November | 20.81 | 2.78 |
December | 20.60 | -1.5 |
Annual Sum or Average | 21.22 | 7.87 |
Minimum of Months | 20.48 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.06 | -0.5 |
April | 20.02 | 7.83 |
May | 21.48 | 13.82 |
June | 22.86 | 19.28 |
July | 23.03 | 21.06 |
August | 22.88 | 19.79 |
September | 21.59 | 15.09 |
October | 19.60 | 8.66 |
November | 18.95 | 2.78 |
December | 18.89 | -1.5 |
Annual Sum or Average | 20.52 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.03 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -7.2 |
February | 18.89 | -5.6 |
March | 19.17 | -0.5 |
April | 20.35 | 7.83 |
May | 21.93 | 13.82 |
June | 23.01 | 19.28 |
July | 23.13 | 21.06 |
August | 23.03 | 19.79 |
September | 21.95 | 15.09 |
October | 20.04 | 8.66 |
November | 19.04 | 2.78 |
December | 18.90 | -1.5 |
Annual Sum or Average | 20.71 | 7.87 |
Minimum of Months | 18.89 | -7.2 |
Maximum of Months | 23.13 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -7.2 |
February | 20.62 | -5.6 |
March | 21.01 | -0.5 |
April | 21.52 | 7.83 |
May | 21.74 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.72 | 15.09 |
October | 21.55 | 8.66 |
November | 20.94 | 2.78 |
December | 20.67 | -1.5 |
Annual Sum or Average | 21.30 | 7.87 |
Minimum of Months | 20.50 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.77 | -7.2 |
February | 18.03 | -5.6 |
March | 19.35 | -0.5 |
April | 21.37 | 7.83 |
May | 22.99 | 13.82 |
June | 24.25 | 19.28 |
July | 24.55 | 21.06 |
August | 24.27 | 19.79 |
September | 22.99 | 15.09 |
October | 21.21 | 8.66 |
November | 19.57 | 2.78 |
December | 18.47 | -1.5 |
Annual Sum or Average | 21.25 | 7.87 |
Minimum of Months | 17.77 | -7.2 |
Maximum of Months | 24.55 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -7.2 |
February | 20.59 | -5.6 |
March | 20.96 | -0.5 |
April | 21.49 | 7.83 |
May | 21.74 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.71 | 15.09 |
October | 21.51 | 8.66 |
November | 20.90 | 2.78 |
December | 20.63 | -1.5 |
Annual Sum or Average | 21.28 | 7.87 |
Minimum of Months | 20.49 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -7.2 |
February | 20.61 | -5.6 |
March | 20.99 | -0.5 |
April | 21.51 | 7.83 |
May | 21.74 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.71 | 15.09 |
October | 21.53 | 8.66 |
November | 20.91 | 2.78 |
December | 20.65 | -1.5 |
Annual Sum or Average | 21.29 | 7.87 |
Minimum of Months | 20.49 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -7.2 |
February | 20.50 | -5.6 |
March | 20.80 | -0.5 |
April | 21.34 | 7.83 |
May | 21.72 | 13.82 |
June | 21.76 | 19.28 |
July | 21.76 | 21.06 |
August | 21.76 | 19.79 |
September | 21.67 | 15.09 |
October | 21.35 | 8.66 |
November | 20.72 | 2.78 |
December | 20.54 | -1.5 |
Annual Sum or Average | 21.20 | 7.87 |
Minimum of Months | 20.47 | -7.2 |
Maximum of Months | 21.76 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.79 | -7.2 |
February | 14.24 | -5.6 |
March | 16.36 | -0.5 |
April | 19.76 | 7.83 |
May | 22.46 | 13.82 |
June | 24.63 | 19.28 |
July | 25.22 | 21.06 |
August | 24.70 | 19.79 |
September | 22.62 | 15.09 |
October | 19.79 | 8.66 |
November | 17.05 | 2.78 |
December | 15.15 | -1.5 |
Annual Sum or Average | 19.68 | 7.87 |
Minimum of Months | 13.79 | -7.2 |
Maximum of Months | 25.22 | 21.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:10
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.73 | -7.2 |
February | 9.43 | -5.6 |
March | 12.44 | -0.5 |
April | 17.32 | 7.83 |
May | 21.35 | 13.82 |
June | 24.69 | 19.28 |
July | 25.72 | 21.06 |
August | 24.85 | 19.79 |
September | 21.72 | 15.09 |
October | 17.64 | 8.66 |
November | 13.66 | 2.78 |
December | 10.83 | -1.5 |
Annual Sum or Average | 17.41 | 7.87 |
Minimum of Months | 8.73 | -7.2 |
Maximum of Months | 25.72 | 21.06 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:10
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.235064E+12 | 205917.147 | 27-JAN-07:15 | 17938.631 | 34285.948 | 9178.315 | 140318.141 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.201240E+12 | 191345.615 | 07-FEB-07:15 | 20847.837 | 39740.848 | 9159.804 | 121531.936 | 57.077 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.186394E+12 | 170893.012 | 07-MAR-07:15 | 20847.837 | 39740.848 | 9158.995 | 101021.401 | 115.817 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.151975E+12 | 132879.085 | 09-APR-06:15 | 20847.837 | 39740.848 | 9126.434 | 62964.392 | 191.462 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.154965E+12 | 97249.151 | 07-MAY-06:15 | 20847.837 | 39740.848 | 9126.434 | 23577.861 | 3948.058 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.167300E+12 | 115023.044 | 16-JUN-07:00 | 25182.171 | 43578.554 | 9638.387 | 0.000 | 36615.820 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.180233E+12 | 119851.570 | 21-JUL-07:00 | 25182.171 | 43578.554 | 9638.387 | 0.000 | 41444.346 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.175936E+12 | 108873.319 | 04-AUG-07:00 | 25182.171 | 43578.554 | 9638.387 | 0.000 | 30466.094 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.155227E+12 | 104126.468 | 02-SEP-07:00 | 25182.171 | 43578.554 | 9638.387 | 0.000 | 25719.243 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.151418E+12 | 119153.265 | 31-OCT-06:15 | 20847.837 | 39740.848 | 9126.434 | 44792.714 | 449.319 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.164637E+12 | 127039.915 | 13-NOV-07:15 | 20847.837 | 39740.848 | 9126.434 | 57079.318 | 237.365 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.201870E+12 | 193855.522 | 19-DEC-07:15 | 20847.837 | 39740.848 | 9154.304 | 119857.560 | 58.860 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.212626E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.151418E+12 | 97249.151 | 17938.631 | 34285.948 | 9126.434 | 0.000 | 0.000 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.235064E+12 | 205917.147 | 25182.171 | 43578.554 | 9638.387 | 140318.141 | 41444.346 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:10
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.131029E+12 | 126940.749 | 27-JAN-09:30 | 21837.504 | 40096.028 | 0.000 | 65007.217 | 65007.217 | 65007.217 | 21837.504 |
February | 0.116254E+12 | 125004.291 | 11-FEB-09:15 | 12090.018 | 40096.028 | 0.000 | 72818.245 | 72818.245 | 72818.245 | 12090.018 |
March | 0.116875E+12 | 112638.890 | 24-MAR-08:15 | 355.591 | 40096.028 | 0.000 | 72187.270 | 72187.270 | 72187.270 | 355.591 |
April | 0.989985E+11 | 110908.546 | 07-APR-08:15 | 3741.403 | 40096.028 | 0.000 | 67071.115 | 67071.115 | 67071.115 | 3741.403 |
May | 0.940950E+11 | 104466.478 | 12-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 64370.450 | 64370.450 | 64370.450 | 0.000 |
June | 0.869652E+11 | 102041.610 | 16-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 61945.582 | 61945.582 | 61945.582 | 0.000 |
July | 0.871933E+11 | 93041.593 | 28-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 52945.565 | 52945.565 | 52945.565 | 0.000 |
August | 0.861334E+11 | 87090.027 | 05-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 46993.999 | 46993.999 | 46993.999 | 0.000 |
September | 0.844690E+11 | 91328.417 | 29-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 51232.389 | 51232.389 | 51232.389 | 0.000 |
October | 0.925478E+11 | 98210.956 | 28-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 58114.928 | 58114.928 | 58114.928 | 0.000 |
November | 0.100595E+12 | 107208.223 | 25-NOV-09:15 | 3210.048 | 40096.028 | 0.000 | 63902.147 | 63902.147 | 63902.147 | 3210.048 |
December | 0.116976E+12 | 114713.662 | 09-DEC-09:15 | 5953.465 | 40096.028 | 0.000 | 68664.169 | 68664.169 | 68664.169 | 5953.465 |
Annual Sum or Average | 0.121213E+13 | 0.000 | ||||||||
Minimum of Months | 0.844690E+11 | 87090.027 | 0.000 | 40096.028 | 0.000 | 46993.999 | 46993.999 | 46993.999 | 0.000 | |
Maximum of Months | 0.131029E+12 | 126940.749 | 21837.504 | 40096.028 | 0.000 | 72818.245 | 72818.245 | 72818.245 | 21837.504 |