Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Duluth International Arpt MN USA TMY3 WMO#=727450
Simulation Timestamp: 2015-09-14 08:44:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3581.74 | 892.41 | 961.52 |
Net Site Energy | 3581.74 | 892.41 | 961.52 |
Total Source Energy | 8597.50 | 2142.10 | 2308.00 |
Net Source Energy | 8597.50 | 2142.10 | 2308.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 532.46 | 170.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 185.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 299.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 725.92 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2263.51 | 1318.23 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 532.46 | 170.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 185.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 299.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 725.92 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 273.21 | 240.73 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 607.64 | 353.88 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.57 | 223.43 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 563.96 | 328.44 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2263.51 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2263.51 | 100.00 |
Total On-Site and Utility Electric Sources | 2263.51 | 100.00 |
Total Electricity End Uses | 2263.51 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1164.50 |
Time Setpoint Not Met During Occupied Cooling | 2853.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6235.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Duluth International Arpt MN USA TMY3 WMO#=727450 |
Weather File | Duluth International Arpt MN USA TMY3 WMO#=727450 |
Latitude [deg] | 46.83 |
Longitude [deg] | -92.2 |
Elevation [m] | 433.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -28.60 | 0.00 | -28.60 | Wetbulb [C] | 4.60 | 310.00 |
DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 10.90 | 21.00 | Wetbulb [C] | 5.20 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.295 | 0.309 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.670 | 0.479 | 0.381 | ||||||||||||
North Total or Average | 8.38 | 2.670 | 0.479 | 0.381 | ||||||||||||
Non-North Total or Average | 175.82 | 2.670 | 0.479 | 0.381 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6993.25 | 5379.29 | 1613.96 | 0.77 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21340.87 | 15650.52 | 5690.35 | 0.73 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10316.85 | 7284.70 | 3032.15 | 0.71 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13953.41 | 10882.43 | 3070.98 | 0.78 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6691.6 | 3.20 | 10.93 | 11.58 | 10.80 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20517.6 | 2.97 | 10.12 | 10.73 | 10.19 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9954.6 | 3.32 | 11.33 | 12.01 | 11.39 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13332.6 | 3.19 | 10.87 | 11.51 | 10.70 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 305.27 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 59694.03 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1235.19 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1235.19 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1956.10 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1773.92 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1330.50 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 560.48 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 719.08 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 4581.18 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1235.19 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 5093.71 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3999.00 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4940.75 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 2041.05 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1749.87 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4940.40 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1318.28 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4940.40 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1560.05 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 1035.14 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 891.77 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 5193.99 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1304.16 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4940.75 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3915.71 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 5080.02 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1724.65 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1829.25 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 5131.35 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1235.10 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4940.40 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1235.10 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 1244.73 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 1202.81 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 6748.34 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 2058.33 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 5377.47 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 4388.97 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 6272.54 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 2162.96 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1678.97 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 6145.67 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1776.36 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 5986.91 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 2028.61 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 1507.17 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 5085.95 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 21317.65 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 11415.45 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 8667.49 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.86 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.02 | 1.45 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 1.18 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.02 | 1.84 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.02 | 1.76 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.03 | 2.33 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.39 | 451.14 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.06 | 1208.79 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.47 | 541.34 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.80 | 912.03 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10178.22 | 12213.86 | 0.884 | 1.060 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
RESTROOMFLR1 | 639.35 | 767.22 | 0.055 | 0.067 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 25.77 | 0.01308 |
MEETINGROOMFLR1 | 4474.37 | 5369.24 | 0.389 | 0.466 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM101 | 534.66 | 641.60 | 0.049 | 0.059 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 26.58 | 0.01308 |
GUESTROOM102 | 407.03 | 488.43 | 0.037 | 0.045 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM103 | 1476.05 | 1771.26 | 0.178 | 0.214 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM104 | 1336.81 | 1604.17 | 0.161 | 0.193 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM105 | 1812.09 | 2174.51 | 0.219 | 0.262 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
EMPLOYEELOUNGEFLR1 | 5685.50 | 6822.60 | 0.494 | 0.592 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
EXERCISECENTERFLR1 | 1354.91 | 1625.89 | 0.118 | 0.141 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.20 | 0.01308 |
FRONTOFFICEFLR1 | 3733.71 | 4480.46 | 0.324 | 0.389 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM201 | 777.45 | 932.94 | 0.071 | 0.086 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 27.13 | 0.01308 |
GUESTROOM202_205 | 6035.00 | 7242.00 | 0.728 | 0.873 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 26.58 | 0.01308 |
GUESTROOM206_208 | 4984.58 | 5981.49 | 0.601 | 0.721 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM209_212 | 5620.82 | 6744.98 | 0.678 | 0.814 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM213 | 1584.70 | 1901.64 | 0.191 | 0.229 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM214 | 1572.87 | 1887.44 | 0.190 | 0.228 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM215_218 | 8744.63 | 10493.55 | 0.804 | 0.964 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM219 | 5715.18 | 6858.22 | 0.689 | 0.827 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM220_223 | 5425.43 | 6510.51 | 0.654 | 0.785 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM224 | 1591.22 | 1909.47 | 0.192 | 0.230 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM301 | 627.11 | 752.53 | 0.058 | 0.069 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 27.13 | 0.01308 |
GUESTROOM302_305 | 1987.51 | 2385.02 | 0.183 | 0.219 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM306_308 | 1850.73 | 2220.87 | 0.170 | 0.204 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM309_312 | 5615.38 | 6738.46 | 0.677 | 0.813 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 26.86 | 0.01308 |
GUESTROOM313 | 629.78 | 755.74 | 0.058 | 0.069 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 26.58 | 0.01308 |
GUESTROOM314 | 1489.67 | 1787.60 | 0.180 | 0.216 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM315_318 | 6098.83 | 7318.60 | 0.736 | 0.883 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM319 | 867.17 | 1040.61 | 0.080 | 0.096 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM320_323 | 5240.31 | 6288.37 | 0.632 | 0.758 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM324 | 516.29 | 619.55 | 0.047 | 0.057 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:15:00 | 25.47 | 0.01308 |
GUESTROOM401 | 1918.60 | 2302.32 | 0.231 | 0.278 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 27.67 | 0.01308 |
GUESTROOM402_405 | 2771.53 | 3325.83 | 0.255 | 0.306 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 27.40 | 0.01308 |
GUESTROOM406_408 | 2579.75 | 3095.70 | 0.237 | 0.284 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 27.40 | 0.01308 |
GUESTROOM409_412 | 6638.94 | 7966.73 | 0.801 | 0.961 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 27.67 | 0.01308 |
GUESTROOM413 | 904.75 | 1085.70 | 0.083 | 0.100 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 27.40 | 0.01308 |
GUESTROOM414 | 665.62 | 798.74 | 0.061 | 0.073 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 26.69 | 0.01308 |
GUESTROOM415_418 | 6238.03 | 7485.64 | 0.752 | 0.903 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 25.88 | 0.01308 |
GUESTROOM419 | 1696.63 | 2035.96 | 0.205 | 0.246 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 26.28 | 0.01308 |
GUESTROOM420_423 | 6089.70 | 7307.64 | 0.735 | 0.881 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 25.88 | 0.01308 |
GUESTROOM424 | 1697.32 | 2036.78 | 0.205 | 0.246 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 26.28 | 0.01308 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
CORRIDORFLR1 | 14605.54 | 17526.65 | 1.267 | 1.521 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 26.58 | 0.01308 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
CORRIDORFLR2 | 2884.18 | 3461.02 | 0.250 | 0.300 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 28.33 | 0.01308 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
CORRIDORFLR3 | 1596.03 | 1915.23 | 0.138 | 0.166 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 27.40 | 0.01308 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 | |
CORRIDORFLR4 | 2284.83 | 2741.79 | 0.198 | 0.238 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 29.04 | 0.01308 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 29.20 | 0.01308 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2468.30 | 2961.97 | 0.073 | 0.236 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -28.60 | 0.00028 |
RESTROOMFLR1 | 119.27 | 143.12 | 0.004 | 0.004 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -28.60 | 0.00028 |
MEETINGROOMFLR1 | 883.68 | 1060.42 | 0.026 | 0.126 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -28.60 | 0.00028 |
GUESTROOM101 | 109.40 | 131.28 | 0.003 | 0.013 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -28.60 | 0.00028 |
GUESTROOM102 | 145.46 | 174.55 | 0.004 | 0.013 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -28.60 | 0.00028 |
GUESTROOM103 | 979.09 | 1174.90 | 0.029 | 0.035 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -28.60 | 0.00028 |
GUESTROOM104 | 827.31 | 992.77 | 0.025 | 0.029 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -28.60 | 0.00028 |
GUESTROOM105 | 457.80 | 549.35 | 0.014 | 0.016 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -28.60 | 0.00028 |
EMPLOYEELOUNGEFLR1 | 438.79 | 526.55 | 0.013 | 0.051 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -28.60 | 0.00028 |
EXERCISECENTERFLR1 | 282.01 | 338.41 | 0.008 | 0.043 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -28.60 | 0.00028 |
FRONTOFFICEFLR1 | 1541.42 | 1849.71 | 0.046 | 0.056 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -28.60 | 0.00028 |
GUESTROOM201 | 379.55 | 455.46 | 0.010 | 0.013 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -28.60 | 0.00028 |
GUESTROOM202_205 | 1640.76 | 1968.91 | 0.049 | 0.058 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -28.60 | 0.00028 |
GUESTROOM206_208 | 1268.74 | 1522.49 | 0.038 | 0.045 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -28.60 | 0.00028 |
GUESTROOM209_212 | 1388.94 | 1666.73 | 0.041 | 0.054 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -28.60 | 0.00028 |
GUESTROOM213 | 1049.87 | 1259.85 | 0.031 | 0.037 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -28.60 | 0.00028 |
GUESTROOM214 | 807.27 | 968.72 | 0.024 | 0.029 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -28.60 | 0.00028 |
GUESTROOM215_218 | 477.83 | 573.39 | 0.013 | 0.054 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -28.60 | 0.00028 |
GUESTROOM219 | 447.61 | 537.13 | 0.013 | 0.016 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -28.60 | 0.00028 |
GUESTROOM220_223 | 1201.24 | 1441.49 | 0.036 | 0.054 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -28.60 | 0.00028 |
GUESTROOM224 | 649.09 | 778.90 | 0.019 | 0.023 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -28.60 | 0.00028 |
GUESTROOM301 | 464.90 | 557.88 | 0.013 | 0.015 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -28.60 | 0.00028 |
GUESTROOM302_305 | 944.99 | 1133.99 | 0.026 | 0.054 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -28.60 | 0.00028 |
GUESTROOM306_308 | 787.36 | 944.84 | 0.022 | 0.043 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:30:00 | -28.60 | 0.00028 |
GUESTROOM309_312 | 1629.35 | 1955.22 | 0.048 | 0.058 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:30:00 | -28.60 | 0.00028 |
GUESTROOM313 | 815.31 | 978.37 | 0.022 | 0.027 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | -28.60 | 0.00028 |
GUESTROOM314 | 873.42 | 1048.10 | 0.026 | 0.031 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:15:00 | -28.60 | 0.00028 |
GUESTROOM315_318 | 1672.31 | 2006.77 | 0.050 | 0.060 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -28.60 | 0.00028 |
GUESTROOM319 | 178.65 | 214.39 | 0.005 | 0.013 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -28.60 | 0.00028 |
GUESTROOM320_323 | 1444.99 | 1733.98 | 0.043 | 0.054 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -28.60 | 0.00028 |
GUESTROOM324 | 360.26 | 432.31 | 0.010 | 0.013 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -28.60 | 0.00028 |
GUESTROOM401 | 1064.28 | 1277.13 | 0.032 | 0.038 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | -28.60 | 0.00028 |
GUESTROOM402_405 | 1993.62 | 2392.34 | 0.055 | 0.066 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -28.60 | 0.00028 |
GUESTROOM406_408 | 1685.96 | 2023.15 | 0.046 | 0.056 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | -28.60 | 0.00028 |
GUESTROOM409_412 | 2623.12 | 3147.74 | 0.078 | 0.093 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | -28.60 | 0.00028 |
GUESTROOM413 | 1180.56 | 1416.67 | 0.033 | 0.039 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -28.60 | 0.00028 |
GUESTROOM414 | 777.28 | 932.74 | 0.021 | 0.026 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -28.60 | 0.00028 |
GUESTROOM415_418 | 2517.58 | 3021.09 | 0.075 | 0.090 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -28.60 | 0.00028 |
GUESTROOM419 | 829.34 | 995.21 | 0.025 | 0.030 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | -28.60 | 0.00028 |
GUESTROOM420_423 | 2385.28 | 2862.33 | 0.071 | 0.085 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -28.60 | 0.00028 |
GUESTROOM424 | 1039.55 | 1247.46 | 0.031 | 0.037 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -28.60 | 0.00028 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -28.60 | 0.00028 | |
CORRIDORFLR1 | 47477.62 | 56973.14 | 1.406 | 1.688 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -28.60 | 0.00028 |
FRONTSTAIRSFLR1 | 239.38 | 287.26 | 0.005 | 0.006 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -28.60 | 0.00028 |
REARSTAIRSFLR2 | 386.49 | 463.79 | 0.008 | 0.009 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
CORRIDORFLR2 | 1971.45 | 2365.74 | 0.059 | 0.070 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -28.60 | 0.00028 |
FRONTSTAIRSFLR2 | 649.98 | 779.97 | 0.013 | 0.016 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
REARSTAIRSFLR3 | 530.43 | 636.52 | 0.011 | 0.013 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
CORRIDORFLR3 | 2482.16 | 2978.59 | 0.074 | 0.088 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
FRONTSTAIRSFLR3 | 824.67 | 989.60 | 0.017 | 0.020 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
REARSTAIRSFLR4 | 789.68 | 947.62 | 0.016 | 0.019 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
CORRIDORFLR4 | 3777.48 | 4532.98 | 0.112 | 0.135 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
FRONTSTAIRSFLR4 | 1043.40 | 1252.09 | 0.021 | 0.025 | DULUTH INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -28.60 | 0.00028 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.39 | 0.39 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.06 | 1.06 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.47 | 0.47 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.80 | 0.80 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 3407.75 | 6845.50 | 2277.75 |
RESTROOMFLR1 | 1587.50 | 7348.50 | 1201.25 |
MEETINGROOMFLR1 | 1333.25 | 3207.75 | 333.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 3485.50 | 8748.00 | 3485.50 |
GUESTROOM104 | 2759.00 | 8722.50 | 2759.00 |
GUESTROOM105 | 749.25 | 8465.50 | 747.50 |
EMPLOYEELOUNGEFLR1 | 2877.00 | 2452.25 | 459.75 |
EXERCISECENTERFLR1 | 1331.50 | 3514.00 | 141.50 |
FRONTOFFICEFLR1 | 2300.50 | 6412.00 | 1513.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 2100.00 | 8456.50 | 2080.00 |
GUESTROOM206_208 | 1882.25 | 8441.00 | 1859.50 |
GUESTROOM209_212 | 1635.75 | 8561.25 | 1624.25 |
GUESTROOM213 | 3466.75 | 8692.00 | 3462.25 |
GUESTROOM214 | 2610.75 | 8519.00 | 2601.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 2793.75 | 4965.75 | 176.75 |
GUESTROOM220_223 | 1064.25 | 8295.25 | 1037.75 |
GUESTROOM224 | 2537.75 | 8457.75 | 2527.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 2168.75 | 8582.25 | 2156.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 3239.75 | 8539.50 | 3229.50 |
GUESTROOM315_318 | 1244.00 | 8215.50 | 1200.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1750.50 | 8408.00 | 1730.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 4492.75 | 8346.75 | 4404.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 3281.75 | 8135.25 | 3068.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2925.00 | 7950.00 | 2615.50 |
GUESTROOM419 | 3028.50 | 8110.50 | 2903.75 |
GUESTROOM420_423 | 2979.75 | 7981.00 | 2687.50 |
GUESTROOM424 | 3811.50 | 8196.50 | 3706.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7475.50 | 8760.00 | 6235.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
RESTROOMFLR1 | 960.00 | 586.25 | 960.00 | 586.25 |
MEETINGROOMFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
GUESTROOM101 | 1.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 1.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 28.00 | 27.75 | 28.00 | 27.75 |
GUESTROOM104 | 24.75 | 28.00 | 24.75 | 28.00 |
GUESTROOM105 | 5.50 | 36.75 | 5.50 | 36.75 |
EMPLOYEELOUNGEFLR1 | 775.00 | 1231.50 | 536.75 | 845.50 |
EXERCISECENTERFLR1 | 0.75 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.50 | 0.00 | 0.50 | 0.00 |
GUESTROOM201 | 55.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 19.00 | 20.00 | 19.00 | 20.00 |
GUESTROOM206_208 | 15.50 | 28.00 | 15.50 | 28.00 |
GUESTROOM209_212 | 16.00 | 17.75 | 16.00 | 17.75 |
GUESTROOM213 | 10.50 | 17.50 | 10.50 | 17.50 |
GUESTROOM214 | 19.00 | 17.00 | 19.00 | 17.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 1790.50 | 0.00 | 1790.50 |
GUESTROOM220_223 | 15.00 | 15.50 | 15.00 | 15.50 |
GUESTROOM224 | 23.75 | 18.50 | 23.75 | 18.50 |
GUESTROOM301 | 110.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 22.25 | 17.75 | 22.25 | 17.75 |
GUESTROOM313 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 23.75 | 15.50 | 23.75 | 15.50 |
GUESTROOM315_318 | 17.00 | 17.75 | 17.00 | 17.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 23.25 | 14.00 | 23.25 | 14.00 |
GUESTROOM324 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 29.75 | 26.25 | 29.75 | 26.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 28.00 | 27.25 | 28.00 | 27.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 30.00 | 21.25 | 30.00 | 21.25 |
GUESTROOM419 | 22.75 | 23.75 | 22.75 | 23.75 |
GUESTROOM420_423 | 31.00 | 21.25 | 31.00 | 21.25 |
GUESTROOM424 | 18.50 | 22.50 | 18.50 | 22.50 |
REARSTAIRSFLR1 | 13.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 9.00 | 1881.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 16.75 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 18.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 51.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 17.50 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 23.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 23.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 24.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 50.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 22.50 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1213.50 | 3522.50 | 1164.50 | 2853.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.009289 |
FRONTSTAIRSFLR2 UNITHEATER | 0.015621 |
REARSTAIRSFLR3 UNITHEATER | 0.012748 |
FRONTSTAIRSFLR3 UNITHEATER | 0.019818 |
REARSTAIRSFLR4 UNITHEATER | 0.018977 |
FRONTSTAIRSFLR4 UNITHEATER | 0.025073 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.009289 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.015621 |
REARSTAIRSFLR3UNITHEATERFAN | 0.012748 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.019818 |
REARSTAIRSFLR4UNITHEATERFAN | 0.018977 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.025073 |
SAC_FRONTOFFICE SUPPLY FAN | 0.388630 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.06 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.799952 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 305.27 |
CORRIDORFLR1 PTAC HEATING COIL | 59694.03 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1235.19 |
102 PTAC HEATING COIL | 1235.19 |
103 PTAC HEATING COIL | 1956.10 |
104 PTAC HEATING COIL | 1773.92 |
105 PTAC HEATING COIL | 1330.50 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 560.48 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 719.08 |
CORRIDORFLR2 PTAC HEATING COIL | 4581.18 |
201 PTAC HEATING COIL | 1235.19 |
202_205 PTAC HEATING COIL | 5093.71 |
206_208 PTAC HEATING COIL | 3999.00 |
209_212 PTAC HEATING COIL | 4940.75 |
213 PTAC HEATING COIL | 2041.05 |
214 PTAC HEATING COIL | 1749.87 |
215_218 PTAC HEATING COIL | 4940.40 |
219 PTAC HEATING COIL | 1318.28 |
220_223 PTAC HEATING COIL | 4940.40 |
224 PTAC HEATING COIL | 1560.05 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 1035.14 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 891.77 |
CORRIDORFLR3 PTAC HEATING COIL | 5193.99 |
301 PTAC HEATING COIL | 1304.16 |
302_305 PTAC HEATING COIL | 4940.75 |
306_308 PTAC HEATING COIL | 3915.71 |
309_312 PTAC HEATING COIL | 5080.02 |
313 PTAC HEATING COIL | 1724.65 |
314 PTAC HEATING COIL | 1829.25 |
315_318 PTAC HEATING COIL | 5131.35 |
319 PTAC HEATING COIL | 1235.10 |
320_323 PTAC HEATING COIL | 4940.40 |
324 PTAC HEATING COIL | 1235.10 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 1244.73 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 1202.81 |
CORRIDORFLR4 PTAC HEATING COIL | 6748.34 |
401 PTAC HEATING COIL | 2058.33 |
402_405 PTAC HEATING COIL | 5377.47 |
406_408 PTAC HEATING COIL | 4388.97 |
409_412 PTAC HEATING COIL | 6272.54 |
413 PTAC HEATING COIL | 2162.96 |
414 PTAC HEATING COIL | 1678.97 |
415_418 PTAC HEATING COIL | 6145.67 |
419 PTAC HEATING COIL | 1776.36 |
420_423 PTAC HEATING COIL | 5986.91 |
424 PTAC HEATING COIL | 2028.61 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 1507.17 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.769212 | 0.388630 | 6993.25 |
SAC_FRONTLOUNGE COOLING COIL | 0.733359 | 1.06 | 21340.87 |
SAC_MEETINGROOM COOLING COIL | 0.706098 | 0.466339 | 10316.85 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.779912 | 0.799952 | 13953.41 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.06 |
RESTROOMFLR1 DIRECT AIR | 0.066536 |
MEETINGROOMFLR1 DIRECT AIR | 0.466339 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.592340 |
EXERCISECENTERFLR1 DIRECT AIR | 0.141077 |
FRONTOFFICEFLR1 DIRECT AIR | 0.388630 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.388630 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.06 |
SAC_MEETINGROOM MAIN BRANCH | 0.466339 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.799952 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.388630 |
SAC_FRONTLOUNGE | 1.06 |
SAC_MEETINGROOM | 0.466339 |
SAC_EXC_EMPLGE_RESTRM | 0.799952 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.388630 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.06 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.466339 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.799952 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.388630 | 0.388630 | 0.388630 | 0.388630 | 5085.95 | 6993.25 | 1.00 |
SAC_FRONTLOUNGE | 1.06 | 1.06 | 1.06 | 1.06 | 21317.65 | 21340.87 | 1.00 |
SAC_MEETINGROOM | 0.466339 | 0.466339 | 0.466339 | 0.466339 | 11415.45 | 10316.85 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.799952 | 0.799952 | 0.799952 | 0.799952 | 8667.49 | 13953.41 | 0.176357 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 5085.95 |
SAC_FRONTLOUNGE HEATING COIL | 21317.65 |
SAC_MEETINGROOM HEATING COIL | 11415.45 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 8667.49 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.466339 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.04 | -13.0 |
February | 13.84 | -8.2 |
March | 15.28 | -2.6 |
April | 18.38 | 4.03 |
May | 21.08 | 12.37 |
June | 22.37 | 16.19 |
July | 23.05 | 17.83 |
August | 22.76 | 17.50 |
September | 21.20 | 12.89 |
October | 18.48 | 6.03 |
November | 15.19 | -4.5 |
December | 12.57 | -11.1 |
Annual Sum or Average | 18.04 | 4.02 |
Minimum of Months | 12.04 | -13.0 |
Maximum of Months | 23.05 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | -13.0 |
February | 21.31 | -8.2 |
March | 21.70 | -2.6 |
April | 22.75 | 4.03 |
May | 24.03 | 12.37 |
June | 24.73 | 16.19 |
July | 25.07 | 17.83 |
August | 24.88 | 17.50 |
September | 24.03 | 12.89 |
October | 22.90 | 6.03 |
November | 21.51 | -4.5 |
December | 21.21 | -11.1 |
Annual Sum or Average | 22.95 | 4.02 |
Minimum of Months | 21.17 | -13.0 |
Maximum of Months | 25.07 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.17 | -13.0 |
February | 13.08 | -8.2 |
March | 14.49 | -2.6 |
April | 17.50 | 4.03 |
May | 20.35 | 12.37 |
June | 21.64 | 16.19 |
July | 22.33 | 17.83 |
August | 22.08 | 17.50 |
September | 20.47 | 12.89 |
October | 17.66 | 6.03 |
November | 14.39 | -4.5 |
December | 11.78 | -11.1 |
Annual Sum or Average | 17.27 | 4.02 |
Minimum of Months | 11.17 | -13.0 |
Maximum of Months | 22.33 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -13.0 |
February | 21.12 | -8.2 |
March | 21.22 | -2.6 |
April | 21.63 | 4.03 |
May | 22.88 | 12.37 |
June | 23.29 | 16.19 |
July | 23.50 | 17.83 |
August | 23.59 | 17.50 |
September | 22.92 | 12.89 |
October | 21.73 | 6.03 |
November | 21.13 | -4.5 |
December | 21.11 | -11.1 |
Annual Sum or Average | 22.11 | 4.02 |
Minimum of Months | 21.11 | -13.0 |
Maximum of Months | 23.59 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | -13.0 |
February | 21.29 | -8.2 |
March | 21.75 | -2.6 |
April | 22.37 | 4.03 |
May | 23.15 | 12.37 |
June | 23.42 | 16.19 |
July | 23.56 | 17.83 |
August | 23.59 | 17.50 |
September | 23.21 | 12.89 |
October | 22.49 | 6.03 |
November | 21.63 | -4.5 |
December | 21.02 | -11.1 |
Annual Sum or Average | 22.37 | 4.02 |
Minimum of Months | 20.91 | -13.0 |
Maximum of Months | 23.59 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | -13.0 |
February | 21.23 | -8.2 |
March | 21.48 | -2.6 |
April | 22.24 | 4.03 |
May | 23.37 | 12.37 |
June | 23.64 | 16.19 |
July | 23.74 | 17.83 |
August | 23.76 | 17.50 |
September | 23.43 | 12.89 |
October | 22.32 | 6.03 |
November | 21.28 | -4.5 |
December | 21.17 | -11.1 |
Annual Sum or Average | 22.41 | 4.02 |
Minimum of Months | 21.16 | -13.0 |
Maximum of Months | 23.76 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.07 | -13.0 |
February | 23.42 | -8.2 |
March | 23.89 | -2.6 |
April | 24.87 | 4.03 |
May | 25.92 | 12.37 |
June | 26.26 | 16.19 |
July | 26.47 | 17.83 |
August | 26.42 | 17.50 |
September | 25.91 | 12.89 |
October | 24.89 | 6.03 |
November | 23.75 | -4.5 |
December | 23.19 | -11.1 |
Annual Sum or Average | 24.85 | 4.02 |
Minimum of Months | 23.07 | -13.0 |
Maximum of Months | 26.47 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.95 | -8.2 |
March | 19.26 | -2.6 |
April | 20.39 | 4.03 |
May | 22.13 | 12.37 |
June | 22.65 | 16.19 |
July | 22.92 | 17.83 |
August | 22.97 | 17.50 |
September | 22.17 | 12.89 |
October | 20.51 | 6.03 |
November | 19.03 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.74 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.97 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.92 | -8.2 |
March | 19.12 | -2.6 |
April | 20.03 | 4.03 |
May | 21.82 | 12.37 |
June | 22.41 | 16.19 |
July | 22.71 | 17.83 |
August | 22.74 | 17.50 |
September | 21.84 | 12.89 |
October | 20.16 | 6.03 |
November | 18.93 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.55 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.74 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -13.0 |
February | 20.50 | -8.2 |
March | 20.59 | -2.6 |
April | 20.96 | 4.03 |
May | 21.51 | 12.37 |
June | 21.65 | 16.19 |
July | 21.71 | 17.83 |
August | 21.72 | 17.50 |
September | 21.54 | 12.89 |
October | 21.04 | 6.03 |
November | 20.53 | -4.5 |
December | 20.47 | -11.1 |
Annual Sum or Average | 21.06 | 4.02 |
Minimum of Months | 20.47 | -13.0 |
Maximum of Months | 21.72 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -13.0 |
February | 20.55 | -8.2 |
March | 20.76 | -2.6 |
April | 21.28 | 4.03 |
May | 21.64 | 12.37 |
June | 21.71 | 16.19 |
July | 21.73 | 17.83 |
August | 21.74 | 17.50 |
September | 21.66 | 12.89 |
October | 21.25 | 6.03 |
November | 20.65 | -4.5 |
December | 20.49 | -11.1 |
Annual Sum or Average | 21.17 | 4.02 |
Minimum of Months | 20.48 | -13.0 |
Maximum of Months | 21.74 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.68 | -13.0 |
February | 20.89 | -8.2 |
March | 21.22 | -2.6 |
April | 21.62 | 4.03 |
May | 21.74 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.74 | 12.89 |
October | 21.58 | 6.03 |
November | 21.07 | -4.5 |
December | 20.73 | -11.1 |
Annual Sum or Average | 21.38 | 4.02 |
Minimum of Months | 20.68 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | -13.0 |
February | 21.84 | -8.2 |
March | 22.30 | -2.6 |
April | 22.47 | 4.03 |
May | 22.68 | 12.37 |
June | 22.71 | 16.19 |
July | 22.71 | 17.83 |
August | 22.84 | 17.50 |
September | 22.82 | 12.89 |
October | 22.67 | 6.03 |
November | 22.17 | -4.5 |
December | 21.54 | -11.1 |
Annual Sum or Average | 22.35 | 4.02 |
Minimum of Months | 21.44 | -13.0 |
Maximum of Months | 22.84 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 48.96 | -13.0 |
February | 49.53 | -8.2 |
March | 50.20 | -2.6 |
April | 51.28 | 4.03 |
May | 52.12 | 12.37 |
June | 52.58 | 16.19 |
July | 52.80 | 17.83 |
August | 52.63 | 17.50 |
September | 52.08 | 12.89 |
October | 51.15 | 6.03 |
November | 50.02 | -4.5 |
December | 49.15 | -11.1 |
Annual Sum or Average | 51.05 | 4.02 |
Minimum of Months | 48.96 | -13.0 |
Maximum of Months | 52.80 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 66.48 | -13.0 |
February | 67.04 | -8.2 |
March | 67.59 | -2.6 |
April | 69.01 | 4.03 |
May | 70.16 | 12.37 |
June | 70.73 | 16.19 |
July | 71.11 | 17.83 |
August | 70.86 | 17.50 |
September | 70.10 | 12.89 |
October | 68.94 | 6.03 |
November | 67.62 | -4.5 |
December | 66.71 | -11.1 |
Annual Sum or Average | 68.87 | 4.02 |
Minimum of Months | 66.48 | -13.0 |
Maximum of Months | 71.11 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | -13.0 |
February | 22.08 | -8.2 |
March | 22.58 | -2.6 |
April | 23.05 | 4.03 |
May | 23.54 | 12.37 |
June | 23.74 | 16.19 |
July | 23.81 | 17.83 |
August | 23.85 | 17.50 |
September | 23.63 | 12.89 |
October | 23.17 | 6.03 |
November | 22.42 | -4.5 |
December | 21.79 | -11.1 |
Annual Sum or Average | 22.95 | 4.02 |
Minimum of Months | 21.68 | -13.0 |
Maximum of Months | 23.85 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | -13.0 |
February | 21.35 | -8.2 |
March | 21.82 | -2.6 |
April | 22.71 | 4.03 |
May | 23.55 | 12.37 |
June | 23.79 | 16.19 |
July | 23.85 | 17.83 |
August | 23.88 | 17.50 |
September | 23.67 | 12.89 |
October | 22.81 | 6.03 |
November | 21.59 | -4.5 |
December | 21.25 | -11.1 |
Annual Sum or Average | 22.63 | 4.02 |
Minimum of Months | 21.18 | -13.0 |
Maximum of Months | 23.88 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.75 | -13.0 |
February | 12.41 | -8.2 |
March | 14.11 | -2.6 |
April | 17.63 | 4.03 |
May | 20.94 | 12.37 |
June | 22.53 | 16.19 |
July | 23.31 | 17.83 |
August | 22.87 | 17.50 |
September | 20.99 | 12.89 |
October | 17.90 | 6.03 |
November | 14.13 | -4.5 |
December | 11.31 | -11.1 |
Annual Sum or Average | 17.43 | 4.02 |
Minimum of Months | 10.75 | -13.0 |
Maximum of Months | 23.31 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.50 | -13.0 |
February | 17.43 | -8.2 |
March | 18.47 | -2.6 |
April | 20.64 | 4.03 |
May | 22.61 | 12.37 |
June | 23.52 | 16.19 |
July | 23.96 | 17.83 |
August | 23.73 | 17.50 |
September | 22.68 | 12.89 |
October | 20.76 | 6.03 |
November | 18.43 | -4.5 |
December | 16.83 | -11.1 |
Annual Sum or Average | 20.48 | 4.02 |
Minimum of Months | 16.50 | -13.0 |
Maximum of Months | 23.96 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.41 | -13.0 |
February | 12.34 | -8.2 |
March | 14.08 | -2.6 |
April | 18.02 | 4.03 |
May | 21.43 | 12.37 |
June | 22.95 | 16.19 |
July | 23.76 | 17.83 |
August | 23.38 | 17.50 |
September | 21.47 | 12.89 |
October | 18.05 | 6.03 |
November | 13.91 | -4.5 |
December | 10.92 | -11.1 |
Annual Sum or Average | 17.59 | 4.02 |
Minimum of Months | 10.41 | -13.0 |
Maximum of Months | 23.76 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -13.0 |
February | 21.14 | -8.2 |
March | 21.33 | -2.6 |
April | 22.30 | 4.03 |
May | 23.55 | 12.37 |
June | 23.81 | 16.19 |
July | 23.88 | 17.83 |
August | 23.88 | 17.50 |
September | 23.62 | 12.89 |
October | 22.34 | 6.03 |
November | 21.16 | -4.5 |
December | 21.11 | -11.1 |
Annual Sum or Average | 22.44 | 4.02 |
Minimum of Months | 21.11 | -13.0 |
Maximum of Months | 23.88 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.66 | -13.0 |
February | 11.08 | -8.2 |
March | 12.83 | -2.6 |
April | 16.61 | 4.03 |
May | 20.30 | 12.37 |
June | 21.84 | 16.19 |
July | 22.70 | 17.83 |
August | 22.36 | 17.50 |
September | 20.34 | 12.89 |
October | 16.74 | 6.03 |
November | 12.62 | -4.5 |
December | 9.38 | -11.1 |
Annual Sum or Average | 16.31 | 4.02 |
Minimum of Months | 8.66 | -13.0 |
Maximum of Months | 22.70 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.85 | -13.0 |
February | 18.89 | -8.2 |
March | 19.00 | -2.6 |
April | 19.61 | 4.03 |
May | 21.95 | 12.37 |
June | 22.64 | 16.19 |
July | 22.98 | 17.83 |
August | 23.08 | 17.50 |
September | 21.87 | 12.89 |
October | 19.65 | 6.03 |
November | 18.89 | -4.5 |
December | 18.88 | -11.1 |
Annual Sum or Average | 20.53 | 4.02 |
Minimum of Months | 18.85 | -13.0 |
Maximum of Months | 23.08 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -13.0 |
February | 20.56 | -8.2 |
March | 20.74 | -2.6 |
April | 21.21 | 4.03 |
May | 21.67 | 12.37 |
June | 21.74 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.69 | 12.89 |
October | 21.23 | 6.03 |
November | 20.64 | -4.5 |
December | 20.50 | -11.1 |
Annual Sum or Average | 21.17 | 4.02 |
Minimum of Months | 20.49 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -13.0 |
February | 20.58 | -8.2 |
March | 20.79 | -2.6 |
April | 21.28 | 4.03 |
May | 21.69 | 12.37 |
June | 21.74 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.70 | 12.89 |
October | 21.28 | 6.03 |
November | 20.68 | -4.5 |
December | 20.52 | -11.1 |
Annual Sum or Average | 21.19 | 4.02 |
Minimum of Months | 20.50 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -13.0 |
February | 20.58 | -8.2 |
March | 20.80 | -2.6 |
April | 21.29 | 4.03 |
May | 21.68 | 12.37 |
June | 21.74 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.70 | 12.89 |
October | 21.31 | 6.03 |
November | 20.69 | -4.5 |
December | 20.52 | -11.1 |
Annual Sum or Average | 21.20 | 4.02 |
Minimum of Months | 20.51 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -13.0 |
February | 20.49 | -8.2 |
March | 20.58 | -2.6 |
April | 20.97 | 4.03 |
May | 21.57 | 12.37 |
June | 21.69 | 16.19 |
July | 21.73 | 17.83 |
August | 21.75 | 17.50 |
September | 21.59 | 12.89 |
October | 21.02 | 6.03 |
November | 20.51 | -4.5 |
December | 20.47 | -11.1 |
Annual Sum or Average | 21.07 | 4.02 |
Minimum of Months | 20.47 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -13.0 |
February | 20.55 | -8.2 |
March | 20.78 | -2.6 |
April | 21.38 | 4.03 |
May | 21.70 | 12.37 |
June | 21.74 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.70 | 12.89 |
October | 21.31 | 6.03 |
November | 20.65 | -4.5 |
December | 20.49 | -11.1 |
Annual Sum or Average | 21.19 | 4.02 |
Minimum of Months | 20.48 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | -13.0 |
February | 21.53 | -8.2 |
March | 22.45 | -2.6 |
April | 23.18 | 4.03 |
May | 23.33 | 12.37 |
June | 23.33 | 16.19 |
July | 23.33 | 17.83 |
August | 23.33 | 17.50 |
September | 23.33 | 12.89 |
October | 23.15 | 6.03 |
November | 22.14 | -4.5 |
December | 20.91 | -11.1 |
Annual Sum or Average | 22.56 | 4.02 |
Minimum of Months | 20.70 | -13.0 |
Maximum of Months | 23.33 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 28.11 | -13.0 |
February | 28.79 | -8.2 |
March | 29.40 | -2.6 |
April | 30.92 | 4.03 |
May | 32.32 | 12.37 |
June | 32.89 | 16.19 |
July | 33.18 | 17.83 |
August | 33.00 | 17.50 |
September | 32.26 | 12.89 |
October | 30.81 | 6.03 |
November | 29.29 | -4.5 |
December | 28.34 | -11.1 |
Annual Sum or Average | 30.79 | 4.02 |
Minimum of Months | 28.11 | -13.0 |
Maximum of Months | 33.18 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | -13.0 |
February | 21.73 | -8.2 |
March | 21.78 | -2.6 |
April | 21.93 | 4.03 |
May | 22.36 | 12.37 |
June | 22.69 | 16.19 |
July | 22.80 | 17.83 |
August | 22.71 | 17.50 |
September | 22.40 | 12.89 |
October | 21.95 | 6.03 |
November | 21.74 | -4.5 |
December | 21.68 | -11.1 |
Annual Sum or Average | 22.12 | 4.02 |
Minimum of Months | 21.66 | -13.0 |
Maximum of Months | 22.80 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -13.0 |
February | 20.69 | -8.2 |
March | 21.02 | -2.6 |
April | 21.53 | 4.03 |
May | 21.73 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.73 | 12.89 |
October | 21.45 | 6.03 |
November | 20.82 | -4.5 |
December | 20.58 | -11.1 |
Annual Sum or Average | 21.28 | 4.02 |
Minimum of Months | 20.55 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -13.0 |
February | 20.56 | -8.2 |
March | 20.80 | -2.6 |
April | 21.39 | 4.03 |
May | 21.71 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.71 | 12.89 |
October | 21.31 | 6.03 |
November | 20.66 | -4.5 |
December | 20.50 | -11.1 |
Annual Sum or Average | 21.20 | 4.02 |
Minimum of Months | 20.48 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.65 | -13.0 |
February | 15.69 | -8.2 |
March | 16.92 | -2.6 |
April | 19.84 | 4.03 |
May | 22.51 | 12.37 |
June | 23.65 | 16.19 |
July | 24.23 | 17.83 |
August | 23.91 | 17.50 |
September | 22.48 | 12.89 |
October | 19.87 | 6.03 |
November | 16.83 | -4.5 |
December | 14.94 | -11.1 |
Annual Sum or Average | 19.65 | 4.02 |
Minimum of Months | 14.65 | -13.0 |
Maximum of Months | 24.23 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.95 | -13.0 |
February | 10.26 | -8.2 |
March | 12.16 | -2.6 |
April | 16.75 | 4.03 |
May | 21.10 | 12.37 |
June | 23.06 | 16.19 |
July | 24.05 | 17.83 |
August | 23.46 | 17.50 |
September | 21.08 | 12.89 |
October | 16.99 | 6.03 |
November | 12.17 | -4.5 |
December | 9.27 | -11.1 |
Annual Sum or Average | 16.64 | 4.02 |
Minimum of Months | 8.95 | -13.0 |
Maximum of Months | 24.05 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.61 | -13.0 |
February | 11.32 | -8.2 |
March | 13.10 | -2.6 |
April | 17.28 | 4.03 |
May | 21.16 | 12.37 |
June | 22.86 | 16.19 |
July | 23.76 | 17.83 |
August | 23.35 | 17.50 |
September | 21.15 | 12.89 |
October | 17.30 | 6.03 |
November | 12.90 | -4.5 |
December | 10.00 | -11.1 |
Annual Sum or Average | 17.01 | 4.02 |
Minimum of Months | 9.61 | -13.0 |
Maximum of Months | 23.76 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -13.0 |
February | 21.11 | -8.2 |
March | 21.14 | -2.6 |
April | 21.39 | 4.03 |
May | 22.91 | 12.37 |
June | 23.42 | 16.19 |
July | 23.66 | 17.83 |
August | 23.74 | 17.50 |
September | 22.89 | 12.89 |
October | 21.46 | 6.03 |
November | 21.11 | -4.5 |
December | 21.11 | -11.1 |
Annual Sum or Average | 22.09 | 4.02 |
Minimum of Months | 21.11 | -13.0 |
Maximum of Months | 23.74 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 6.98 | -13.0 |
February | 9.59 | -8.2 |
March | 11.51 | -2.6 |
April | 15.55 | 4.03 |
May | 19.88 | 12.37 |
June | 21.68 | 16.19 |
July | 22.67 | 17.83 |
August | 22.31 | 17.50 |
September | 19.85 | 12.89 |
October | 15.67 | 6.03 |
November | 11.22 | -4.5 |
December | 7.75 | -11.1 |
Annual Sum or Average | 15.42 | 4.02 |
Minimum of Months | 6.98 | -13.0 |
Maximum of Months | 22.67 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.79 | -13.0 |
February | 18.89 | -8.2 |
March | 18.93 | -2.6 |
April | 19.20 | 4.03 |
May | 21.46 | 12.37 |
June | 22.31 | 16.19 |
July | 22.76 | 17.83 |
August | 22.85 | 17.50 |
September | 21.27 | 12.89 |
October | 19.26 | 6.03 |
November | 18.89 | -4.5 |
December | 18.85 | -11.1 |
Annual Sum or Average | 20.30 | 4.02 |
Minimum of Months | 18.79 | -13.0 |
Maximum of Months | 22.85 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 18.97 | -2.6 |
April | 19.50 | 4.03 |
May | 21.86 | 12.37 |
June | 22.55 | 16.19 |
July | 22.92 | 17.83 |
August | 23.05 | 17.50 |
September | 21.67 | 12.89 |
October | 19.48 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.47 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 23.05 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 19.01 | -2.6 |
April | 19.70 | 4.03 |
May | 22.00 | 12.37 |
June | 22.61 | 16.19 |
July | 22.94 | 17.83 |
August | 23.06 | 17.50 |
September | 21.79 | 12.89 |
October | 19.60 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.53 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 23.06 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -13.0 |
February | 20.55 | -8.2 |
March | 20.73 | -2.6 |
April | 21.21 | 4.03 |
May | 21.66 | 12.37 |
June | 21.73 | 16.19 |
July | 21.74 | 17.83 |
August | 21.75 | 17.50 |
September | 21.67 | 12.89 |
October | 21.22 | 6.03 |
November | 20.62 | -4.5 |
December | 20.49 | -11.1 |
Annual Sum or Average | 21.16 | 4.02 |
Minimum of Months | 20.49 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 18.94 | -2.6 |
April | 19.35 | 4.03 |
May | 21.63 | 12.37 |
June | 22.41 | 16.19 |
July | 22.83 | 17.83 |
August | 22.92 | 17.50 |
September | 21.54 | 12.89 |
October | 19.43 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.39 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.92 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -13.0 |
February | 20.51 | -8.2 |
March | 20.64 | -2.6 |
April | 21.21 | 4.03 |
May | 21.65 | 12.37 |
June | 21.73 | 16.19 |
July | 21.74 | 17.83 |
August | 21.75 | 17.50 |
September | 21.65 | 12.89 |
October | 21.13 | 6.03 |
November | 20.53 | -4.5 |
December | 20.47 | -11.1 |
Annual Sum or Average | 21.13 | 4.02 |
Minimum of Months | 20.47 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | -13.0 |
February | 20.67 | -8.2 |
March | 21.03 | -2.6 |
April | 21.56 | 4.03 |
May | 21.73 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.73 | 12.89 |
October | 21.47 | 6.03 |
November | 20.81 | -4.5 |
December | 20.56 | -11.1 |
Annual Sum or Average | 21.28 | 4.02 |
Minimum of Months | 20.54 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.24 | -13.0 |
February | 20.04 | -8.2 |
March | 20.86 | -2.6 |
April | 22.74 | 4.03 |
May | 24.62 | 12.37 |
June | 25.33 | 16.19 |
July | 25.66 | 17.83 |
August | 25.52 | 17.50 |
September | 24.51 | 12.89 |
October | 22.56 | 6.03 |
November | 20.62 | -4.5 |
December | 19.46 | -11.1 |
Annual Sum or Average | 22.61 | 4.02 |
Minimum of Months | 19.24 | -13.0 |
Maximum of Months | 25.66 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.95 | -13.0 |
February | 19.14 | -8.2 |
March | 19.93 | -2.6 |
April | 21.76 | 4.03 |
May | 23.02 | 12.37 |
June | 23.26 | 16.19 |
July | 23.30 | 17.83 |
August | 23.33 | 17.50 |
September | 23.07 | 12.89 |
October | 21.58 | 6.03 |
November | 19.49 | -4.5 |
December | 18.98 | -11.1 |
Annual Sum or Average | 21.33 | 4.02 |
Minimum of Months | 18.95 | -13.0 |
Maximum of Months | 23.33 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -13.0 |
February | 20.60 | -8.2 |
March | 20.90 | -2.6 |
April | 21.44 | 4.03 |
May | 21.71 | 12.37 |
June | 21.74 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.70 | 12.89 |
October | 21.34 | 6.03 |
November | 20.70 | -4.5 |
December | 20.52 | -11.1 |
Annual Sum or Average | 21.22 | 4.02 |
Minimum of Months | 20.50 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 19.01 | -2.6 |
April | 19.99 | 4.03 |
May | 22.16 | 12.37 |
June | 22.78 | 16.19 |
July | 23.03 | 17.83 |
August | 23.10 | 17.50 |
September | 22.15 | 12.89 |
October | 19.95 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.66 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 23.10 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.33 | -13.0 |
February | 14.35 | -8.2 |
March | 15.62 | -2.6 |
April | 18.84 | 4.03 |
May | 22.17 | 12.37 |
June | 23.55 | 16.19 |
July | 24.24 | 17.83 |
August | 23.88 | 17.50 |
September | 22.06 | 12.89 |
October | 18.82 | 6.03 |
November | 15.48 | -4.5 |
December | 13.60 | -11.1 |
Annual Sum or Average | 18.85 | 4.02 |
Minimum of Months | 13.33 | -13.0 |
Maximum of Months | 24.24 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.22 | -13.0 |
February | 9.24 | -8.2 |
March | 11.05 | -2.6 |
April | 15.89 | 4.03 |
May | 20.81 | 12.37 |
June | 22.98 | 16.19 |
July | 24.08 | 17.83 |
August | 23.45 | 17.50 |
September | 20.72 | 12.89 |
October | 16.11 | 6.03 |
November | 11.07 | -4.5 |
December | 8.47 | -11.1 |
Annual Sum or Average | 16.05 | 4.02 |
Minimum of Months | 8.22 | -13.0 |
Maximum of Months | 24.08 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.76 | -13.0 |
February | 10.14 | -8.2 |
March | 11.99 | -2.6 |
April | 16.30 | 4.03 |
May | 20.74 | 12.37 |
June | 22.71 | 16.19 |
July | 23.67 | 17.83 |
August | 23.24 | 17.50 |
September | 20.61 | 12.89 |
October | 16.23 | 6.03 |
November | 11.65 | -4.5 |
December | 9.06 | -11.1 |
Annual Sum or Average | 16.29 | 4.02 |
Minimum of Months | 8.76 | -13.0 |
Maximum of Months | 23.67 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -13.0 |
February | 21.11 | -8.2 |
March | 21.16 | -2.6 |
April | 21.41 | 4.03 |
May | 22.58 | 12.37 |
June | 23.06 | 16.19 |
July | 23.31 | 17.83 |
August | 23.33 | 17.50 |
September | 22.38 | 12.89 |
October | 21.33 | 6.03 |
November | 21.11 | -4.5 |
December | 21.11 | -11.1 |
Annual Sum or Average | 21.92 | 4.02 |
Minimum of Months | 21.11 | -13.0 |
Maximum of Months | 23.33 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 5.77 | -13.0 |
February | 8.54 | -8.2 |
March | 10.72 | -2.6 |
April | 14.92 | 4.03 |
May | 19.56 | 12.37 |
June | 21.54 | 16.19 |
July | 22.56 | 17.83 |
August | 22.17 | 17.50 |
September | 19.39 | 12.89 |
October | 14.92 | 6.03 |
November | 10.18 | -4.5 |
December | 6.57 | -11.1 |
Annual Sum or Average | 14.77 | 4.02 |
Minimum of Months | 5.77 | -13.0 |
Maximum of Months | 22.56 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -13.0 |
February | 20.47 | -8.2 |
March | 20.52 | -2.6 |
April | 20.76 | 4.03 |
May | 21.49 | 12.37 |
June | 21.65 | 16.19 |
July | 21.70 | 17.83 |
August | 21.73 | 17.50 |
September | 21.45 | 12.89 |
October | 20.76 | 6.03 |
November | 20.47 | -4.5 |
December | 20.46 | -11.1 |
Annual Sum or Average | 21.00 | 4.02 |
Minimum of Months | 20.46 | -13.0 |
Maximum of Months | 21.73 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 18.99 | -2.6 |
April | 19.47 | 4.03 |
May | 21.43 | 12.37 |
June | 22.12 | 16.19 |
July | 22.52 | 17.83 |
August | 22.65 | 17.50 |
September | 21.04 | 12.89 |
October | 19.29 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.27 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.65 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 19.02 | -2.6 |
April | 19.59 | 4.03 |
May | 21.50 | 12.37 |
June | 22.16 | 16.19 |
July | 22.53 | 17.83 |
August | 22.65 | 17.50 |
September | 21.12 | 12.89 |
October | 19.35 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.30 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.65 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -13.0 |
February | 20.53 | -8.2 |
March | 20.69 | -2.6 |
April | 21.22 | 4.03 |
May | 21.67 | 12.37 |
June | 21.73 | 16.19 |
July | 21.74 | 17.83 |
August | 21.75 | 17.50 |
September | 21.66 | 12.89 |
October | 21.14 | 6.03 |
November | 20.53 | -4.5 |
December | 20.47 | -11.1 |
Annual Sum or Average | 21.14 | 4.02 |
Minimum of Months | 20.47 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 18.97 | -2.6 |
April | 19.38 | 4.03 |
May | 21.32 | 12.37 |
June | 22.07 | 16.19 |
July | 22.51 | 17.83 |
August | 22.59 | 17.50 |
September | 21.05 | 12.89 |
October | 19.29 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.24 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.59 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -13.0 |
February | 18.89 | -8.2 |
March | 19.01 | -2.6 |
April | 19.69 | 4.03 |
May | 21.66 | 12.37 |
June | 22.40 | 16.19 |
July | 22.71 | 17.83 |
August | 22.80 | 17.50 |
September | 21.54 | 12.89 |
October | 19.55 | 6.03 |
November | 18.89 | -4.5 |
December | 18.89 | -11.1 |
Annual Sum or Average | 20.42 | 4.02 |
Minimum of Months | 18.89 | -13.0 |
Maximum of Months | 22.80 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -13.0 |
February | 20.57 | -8.2 |
March | 20.88 | -2.6 |
April | 21.50 | 4.03 |
May | 21.72 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.71 | 12.89 |
October | 21.32 | 6.03 |
November | 20.60 | -4.5 |
December | 20.48 | -11.1 |
Annual Sum or Average | 21.21 | 4.02 |
Minimum of Months | 20.48 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.97 | -13.0 |
February | 17.87 | -8.2 |
March | 18.87 | -2.6 |
April | 20.80 | 4.03 |
May | 22.80 | 12.37 |
June | 23.60 | 16.19 |
July | 23.95 | 17.83 |
August | 23.76 | 17.50 |
September | 22.53 | 12.89 |
October | 20.47 | 6.03 |
November | 18.42 | -4.5 |
December | 17.20 | -11.1 |
Annual Sum or Average | 20.62 | 4.02 |
Minimum of Months | 16.97 | -13.0 |
Maximum of Months | 23.95 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -13.0 |
February | 20.55 | -8.2 |
March | 20.81 | -2.6 |
April | 21.46 | 4.03 |
May | 21.72 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.70 | 12.89 |
October | 21.27 | 6.03 |
November | 20.58 | -4.5 |
December | 20.48 | -11.1 |
Annual Sum or Average | 21.19 | 4.02 |
Minimum of Months | 20.48 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -13.0 |
February | 20.56 | -8.2 |
March | 20.86 | -2.6 |
April | 21.48 | 4.03 |
May | 21.72 | 12.37 |
June | 21.75 | 16.19 |
July | 21.75 | 17.83 |
August | 21.75 | 17.50 |
September | 21.70 | 12.89 |
October | 21.29 | 6.03 |
November | 20.58 | -4.5 |
December | 20.48 | -11.1 |
Annual Sum or Average | 21.20 | 4.02 |
Minimum of Months | 20.48 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -13.0 |
February | 20.50 | -8.2 |
March | 20.64 | -2.6 |
April | 21.25 | 4.03 |
May | 21.68 | 12.37 |
June | 21.73 | 16.19 |
July | 21.74 | 17.83 |
August | 21.75 | 17.50 |
September | 21.66 | 12.89 |
October | 21.08 | 6.03 |
November | 20.49 | -4.5 |
December | 20.47 | -11.1 |
Annual Sum or Average | 21.12 | 4.02 |
Minimum of Months | 20.47 | -13.0 |
Maximum of Months | 21.75 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.71 | -13.0 |
February | 13.83 | -8.2 |
March | 15.28 | -2.6 |
April | 18.59 | 4.03 |
May | 22.02 | 12.37 |
June | 23.46 | 16.19 |
July | 24.13 | 17.83 |
August | 23.73 | 17.50 |
September | 21.76 | 12.89 |
October | 18.41 | 6.03 |
November | 14.90 | -4.5 |
December | 13.01 | -11.1 |
Annual Sum or Average | 18.51 | 4.02 |
Minimum of Months | 12.71 | -13.0 |
Maximum of Months | 24.13 | 17.83 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 7.85 | -13.0 |
February | 8.73 | -8.2 |
March | 10.56 | -2.6 |
April | 15.35 | 4.03 |
May | 20.55 | 12.37 |
June | 22.86 | 16.19 |
July | 23.96 | 17.83 |
August | 23.30 | 17.50 |
September | 20.33 | 12.89 |
October | 15.45 | 6.03 |
November | 10.38 | -4.5 |
December | 8.09 | -11.1 |
Annual Sum or Average | 15.66 | 4.02 |
Minimum of Months | 7.85 | -13.0 |
Maximum of Months | 23.96 | 17.83 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:19
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.276965E+12 | 230449.649 | 09-JAN-07:15 | 20847.837 | 39740.848 | 9362.349 | 156302.502 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.209743E+12 | 208135.562 | 05-FEB-07:15 | 20847.837 | 39740.848 | 9327.774 | 133983.396 | 39.594 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.192107E+12 | 167928.062 | 23-MAR-06:15 | 20847.837 | 39740.848 | 9300.604 | 97908.118 | 122.543 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.150068E+12 | 115410.740 | 12-APR-06:15 | 20847.837 | 39740.848 | 9278.404 | 44923.422 | 612.117 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.157081E+12 | 105728.901 | 01-MAY-06:15 | 20847.837 | 39740.848 | 9278.404 | 33274.594 | 2579.105 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.161794E+12 | 107561.894 | 30-JUN-07:00 | 25182.171 | 43578.554 | 9819.748 | 0.000 | 28973.308 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.171903E+12 | 107596.705 | 16-JUL-19:00 | 27551.975 | 28549.175 | 9353.762 | 0.000 | 37945.679 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.169279E+12 | 103377.492 | 26-AUG-07:00 | 25182.171 | 43578.554 | 9819.748 | 0.000 | 24788.906 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.151381E+12 | 98674.406 | 01-SEP-07:00 | 25182.171 | 43578.554 | 9819.748 | 0.000 | 20085.820 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.157438E+12 | 115279.660 | 26-OCT-06:15 | 20847.837 | 39740.848 | 9278.404 | 40864.752 | 351.706 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.201578E+12 | 195193.056 | 28-NOV-07:15 | 20847.837 | 39740.848 | 9318.871 | 121023.542 | 65.846 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.264173E+12 | 219935.438 | 19-DEC-07:15 | 20847.837 | 39740.848 | 9341.473 | 145807.073 | 2.094 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.226351E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.150068E+12 | 98674.406 | 20847.837 | 28549.175 | 9278.404 | 0.000 | 0.000 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.276965E+12 | 230449.649 | 27551.975 | 43578.554 | 9819.748 | 156302.502 | 37945.679 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:19
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.146113E+12 | 135185.010 | 27-JAN-09:15 | 19931.160 | 40096.028 | 0.000 | 75157.822 | 75157.822 | 75157.822 | 19931.160 |
February | 0.122602E+12 | 123944.768 | 19-FEB-09:15 | 12672.377 | 40096.028 | 0.000 | 71176.364 | 71176.364 | 71176.364 | 12672.377 |
March | 0.123410E+12 | 124904.647 | 18-MAR-08:15 | 9614.443 | 40096.028 | 0.000 | 75194.176 | 75194.176 | 75194.176 | 9614.443 |
April | 0.104976E+12 | 114372.056 | 14-APR-08:15 | 0.000 | 40096.028 | 0.000 | 74276.028 | 74276.028 | 74276.028 | 0.000 |
May | 0.999273E+11 | 113073.040 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 72977.012 | 72977.012 | 72977.012 | 0.000 |
June | 0.926357E+11 | 104717.418 | 02-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 64621.390 | 64621.390 | 64621.390 | 0.000 |
July | 0.928647E+11 | 101681.386 | 08-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 61585.358 | 61585.358 | 61585.358 | 0.000 |
August | 0.914298E+11 | 98257.850 | 25-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 58161.822 | 58161.822 | 58161.822 | 0.000 |
September | 0.893487E+11 | 105193.300 | 03-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 65097.272 | 65097.272 | 65097.272 | 0.000 |
October | 0.992009E+11 | 104352.585 | 20-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 64256.557 | 64256.557 | 64256.557 | 0.000 |
November | 0.116453E+12 | 116384.532 | 17-NOV-09:15 | 10271.592 | 40096.028 | 0.000 | 66016.911 | 66016.911 | 66016.911 | 10271.592 |
December | 0.139273E+12 | 134284.347 | 25-DEC-09:15 | 24520.959 | 40096.028 | 0.000 | 69667.360 | 69667.360 | 69667.360 | 24520.959 |
Annual Sum or Average | 0.131823E+13 | 0.000 | ||||||||
Minimum of Months | 0.893487E+11 | 98257.850 | 0.000 | 40096.028 | 0.000 | 58161.822 | 58161.822 | 58161.822 | 0.000 | |
Maximum of Months | 0.146113E+12 | 135185.010 | 24520.959 | 40096.028 | 0.000 | 75194.176 | 75194.176 | 75194.176 | 24520.959 |