Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Simulation Timestamp: 2015-09-14 08:44:23
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3061.62 | 762.82 | 821.89 |
Net Site Energy | 3061.62 | 762.82 | 821.89 |
Total Source Energy | 7407.83 | 1845.69 | 1988.63 |
Net Source Energy | 7407.83 | 1845.69 | 1988.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 149.02 | 47.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 262.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 305.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 629.65 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1963.05 | 1098.58 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 149.02 | 47.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 262.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 305.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 629.65 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 192.55 | 181.76 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 526.98 | 294.91 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 178.71 | 168.70 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 489.10 | 273.71 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1963.05 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1963.05 | 100.00 |
Total On-Site and Utility Electric Sources | 1963.05 | 100.00 |
Total Electricity End Uses | 1963.05 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 186.00 |
Time Setpoint Not Met During Occupied Cooling | 3732.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5414.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Weather File | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Latitude [deg] | 43.62 |
Longitude [deg] | -116.2 |
Elevation [m] | 701.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 2.30 | 120.00 |
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 16.70 | 17.90 | Wetbulb [C] | 4.20 | 330.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 8.38 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 175.82 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7111.00 | 5666.28 | 1444.72 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20111.54 | 15502.76 | 4608.79 | 0.77 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9777.16 | 7225.59 | 2551.57 | 0.74 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14236.72 | 11284.15 | 2952.57 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6779.3 | 3.16 | 10.77 | 11.40 | 10.55 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19239.9 | 2.91 | 9.92 | 10.52 | 9.90 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9392.9 | 3.26 | 11.12 | 11.78 | 11.07 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13580.3 | 3.16 | 10.79 | 11.42 | 10.59 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.60 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 40752.70 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1008.89 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1008.89 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1323.23 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1204.34 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1008.82 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.53 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.60 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2881.58 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1008.89 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 4035.57 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3198.33 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4035.57 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1398.82 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1283.94 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4035.29 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1008.82 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4035.29 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1191.80 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.53 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.60 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 3445.19 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1008.89 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4035.57 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3198.33 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 4035.57 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1086.05 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1420.58 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 4035.29 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1008.82 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4035.29 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1008.82 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.53 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 295.60 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 4929.64 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1729.02 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 4189.58 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 3399.06 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 5053.39 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1493.02 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1329.33 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 4992.32 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1415.27 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 4844.58 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1668.36 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 457.80 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4154.18 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 17412.14 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 9324.07 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 7032.57 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.43 | 496.20 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.12 | 1280.36 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.49 | 574.44 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.85 | 964.41 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10442.08 | 12530.49 | 0.936 | 1.123 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
RESTROOMFLR1 | 712.34 | 854.81 | 0.064 | 0.077 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 30.81 | 0.00627 |
MEETINGROOMFLR1 | 4598.22 | 5517.86 | 0.412 | 0.495 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
GUESTROOM101 | 598.17 | 717.80 | 0.057 | 0.068 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM102 | 462.28 | 554.73 | 0.044 | 0.053 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM103 | 1585.20 | 1902.24 | 0.197 | 0.237 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM104 | 1434.61 | 1721.53 | 0.179 | 0.214 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM105 | 1871.76 | 2246.12 | 0.233 | 0.280 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.86 | 0.00627 |
EMPLOYEELOUNGEFLR1 | 5806.36 | 6967.63 | 0.520 | 0.624 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
EXERCISECENTERFLR1 | 1348.16 | 1617.79 | 0.121 | 0.145 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 28.22 | 0.00627 |
FRONTOFFICEFLR1 | 3977.68 | 4773.22 | 0.356 | 0.427 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM201 | 933.76 | 1120.51 | 0.089 | 0.106 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
GUESTROOM202_205 | 6213.34 | 7456.00 | 0.774 | 0.928 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM206_208 | 5104.82 | 6125.78 | 0.636 | 0.763 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM209_212 | 5807.07 | 6968.49 | 0.723 | 0.868 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM213 | 1704.61 | 2045.54 | 0.212 | 0.255 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM214 | 1676.22 | 2011.46 | 0.209 | 0.250 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM215_218 | 9045.19 | 10854.22 | 0.858 | 1.030 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM219 | 5833.62 | 7000.35 | 0.726 | 0.872 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM220_223 | 5610.70 | 6732.84 | 0.699 | 0.838 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM224 | 1678.14 | 2013.77 | 0.209 | 0.251 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM301 | 802.51 | 963.02 | 0.076 | 0.091 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 33.11 | 0.00627 |
GUESTROOM302_305 | 2221.96 | 2666.36 | 0.211 | 0.253 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM306_308 | 2017.50 | 2421.01 | 0.191 | 0.230 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM309_312 | 5834.88 | 7001.86 | 0.727 | 0.872 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM313 | 765.04 | 918.05 | 0.073 | 0.087 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 32.07 | 0.00627 |
GUESTROOM314 | 1605.33 | 1926.39 | 0.200 | 0.240 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 33.69 | 0.00627 |
GUESTROOM315_318 | 6310.62 | 7572.74 | 0.786 | 0.943 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM319 | 937.25 | 1124.70 | 0.089 | 0.107 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM320_323 | 5444.81 | 6533.78 | 0.678 | 0.814 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM324 | 614.05 | 736.86 | 0.058 | 0.070 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 33.28 | 0.00627 |
GUESTROOM401 | 2192.14 | 2630.57 | 0.273 | 0.328 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 33.94 | 0.00627 |
GUESTROOM402_405 | 3310.89 | 3973.07 | 0.314 | 0.377 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 33.94 | 0.00627 |
GUESTROOM406_408 | 2989.11 | 3586.93 | 0.284 | 0.340 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.53 | 0.00627 |
GUESTROOM409_412 | 7179.63 | 8615.55 | 0.894 | 1.073 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 33.94 | 0.00627 |
GUESTROOM413 | 1156.28 | 1387.54 | 0.110 | 0.132 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.53 | 0.00627 |
GUESTROOM414 | 934.02 | 1120.83 | 0.089 | 0.106 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 36.45 | 0.00627 |
GUESTROOM415_418 | 6788.49 | 8146.19 | 0.845 | 1.014 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 34.11 | 0.00627 |
GUESTROOM419 | 1866.99 | 2240.39 | 0.232 | 0.279 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 34.53 | 0.00627 |
GUESTROOM420_423 | 6640.53 | 7968.63 | 0.827 | 0.992 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 34.11 | 0.00627 |
GUESTROOM424 | 1906.43 | 2287.71 | 0.237 | 0.285 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 34.53 | 0.00627 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
CORRIDORFLR1 | 19436.18 | 23323.42 | 1.740 | 2.088 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
CORRIDORFLR2 | 3142.42 | 3770.90 | 0.281 | 0.338 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 34.36 | 0.00627 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
CORRIDORFLR3 | 1872.77 | 2247.33 | 0.168 | 0.201 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 33.53 | 0.00627 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 | |
CORRIDORFLR4 | 3035.67 | 3642.80 | 0.272 | 0.326 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 36.20 | 0.00627 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 0.00627 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1865.27 | 2238.33 | 0.057 | 0.236 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -16.30 | 0.00098 |
RESTROOMFLR1 | 57.69 | 69.22 | 0.002 | 0.002 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -16.30 | 0.00098 |
MEETINGROOMFLR1 | 653.62 | 784.34 | 0.020 | 0.126 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -16.30 | 0.00098 |
GUESTROOM101 | 26.98 | 32.37 | 0.001 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -16.30 | 0.00098 |
GUESTROOM102 | 59.13 | 70.95 | 0.002 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -16.30 | 0.00098 |
GUESTROOM103 | 628.29 | 753.94 | 0.019 | 0.023 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -16.30 | 0.00098 |
GUESTROOM104 | 529.25 | 635.10 | 0.016 | 0.019 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -16.30 | 0.00098 |
GUESTROOM105 | 352.86 | 423.43 | 0.011 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | -16.30 | 0.00098 |
EMPLOYEELOUNGEFLR1 | 331.85 | 398.22 | 0.010 | 0.051 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -16.30 | 0.00098 |
EXERCISECENTERFLR1 | 193.07 | 231.69 | 0.006 | 0.043 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -16.30 | 0.00098 |
FRONTOFFICEFLR1 | 1152.26 | 1382.71 | 0.035 | 0.056 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -16.30 | 0.00098 |
GUESTROOM201 | 295.94 | 355.13 | 0.008 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -16.30 | 0.00098 |
GUESTROOM202_205 | 1367.86 | 1641.43 | 0.042 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -16.30 | 0.00098 |
GUESTROOM206_208 | 1024.47 | 1229.36 | 0.031 | 0.043 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -16.30 | 0.00098 |
GUESTROOM209_212 | 1104.55 | 1325.45 | 0.034 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -16.30 | 0.00098 |
GUESTROOM213 | 691.28 | 829.54 | 0.021 | 0.025 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -16.30 | 0.00098 |
GUESTROOM214 | 595.58 | 714.70 | 0.018 | 0.022 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 10:15:00 | -16.30 | 0.00098 |
GUESTROOM215_218 | 269.22 | 323.07 | 0.008 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -16.30 | 0.00098 |
GUESTROOM219 | 321.10 | 385.32 | 0.010 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -16.30 | 0.00098 |
GUESTROOM220_223 | 975.15 | 1170.17 | 0.030 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -16.30 | 0.00098 |
GUESTROOM224 | 518.80 | 622.55 | 0.016 | 0.019 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -16.30 | 0.00098 |
GUESTROOM301 | 381.18 | 457.41 | 0.011 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -16.30 | 0.00098 |
GUESTROOM302_305 | 710.69 | 852.83 | 0.020 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -16.30 | 0.00098 |
GUESTROOM306_308 | 567.78 | 681.34 | 0.016 | 0.043 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -16.30 | 0.00098 |
GUESTROOM309_312 | 1350.03 | 1620.03 | 0.041 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -16.30 | 0.00098 |
GUESTROOM313 | 458.81 | 550.58 | 0.013 | 0.016 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 21:15:00 | -16.30 | 0.00098 |
GUESTROOM314 | 709.44 | 851.33 | 0.022 | 0.026 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 15:15:00 | -16.30 | 0.00098 |
GUESTROOM315_318 | 1427.60 | 1713.12 | 0.044 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -16.30 | 0.00098 |
GUESTROOM319 | 92.97 | 111.56 | 0.003 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -16.30 | 0.00098 |
GUESTROOM320_323 | 1228.16 | 1473.80 | 0.038 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -16.30 | 0.00098 |
GUESTROOM324 | 257.59 | 309.11 | 0.007 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -16.30 | 0.00098 |
GUESTROOM401 | 966.45 | 1159.74 | 0.030 | 0.036 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -16.30 | 0.00098 |
GUESTROOM402_405 | 1706.40 | 2047.69 | 0.049 | 0.058 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 21:15:00 | -16.30 | 0.00098 |
GUESTROOM406_408 | 1417.94 | 1701.53 | 0.040 | 0.048 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -16.30 | 0.00098 |
GUESTROOM409_412 | 2313.54 | 2776.24 | 0.071 | 0.085 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 19:15:00 | -16.30 | 0.00098 |
GUESTROOM413 | 797.95 | 957.54 | 0.023 | 0.027 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -16.30 | 0.00098 |
GUESTROOM414 | 661.58 | 793.89 | 0.019 | 0.023 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 20:15:00 | -16.30 | 0.00098 |
GUESTROOM415_418 | 2262.78 | 2715.33 | 0.069 | 0.083 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -16.30 | 0.00098 |
GUESTROOM419 | 705.02 | 846.02 | 0.022 | 0.026 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | -16.30 | 0.00098 |
GUESTROOM420_423 | 2139.66 | 2567.59 | 0.066 | 0.079 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -16.30 | 0.00098 |
GUESTROOM424 | 915.93 | 1099.11 | 0.028 | 0.034 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 23:15:00 | -16.30 | 0.00098 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
CORRIDORFLR1 | 32319.75 | 38783.70 | 0.989 | 1.187 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -16.30 | 0.00098 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
CORRIDORFLR2 | 1055.93 | 1267.12 | 0.032 | 0.039 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -16.30 | 0.00098 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
CORRIDORFLR3 | 1525.59 | 1830.70 | 0.047 | 0.056 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -16.30 | 0.00098 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
CORRIDORFLR4 | 2762.64 | 3315.17 | 0.085 | 0.102 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -16.30 | 0.00098 |
FRONTSTAIRSFLR4 | 153.93 | 184.72 | 0.003 | 0.006 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -16.30 | 0.00098 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.43 | 0.43 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.12 | 1.12 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.49 | 0.49 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.85 | 0.85 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 1.12 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1036.50 | 6880.50 | 445.00 |
RESTROOMFLR1 | 174.25 | 7407.50 | 21.25 |
MEETINGROOMFLR1 | 786.50 | 2723.75 | 2.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 922.50 | 8760.00 | 922.50 |
GUESTROOM104 | 280.75 | 8760.00 | 280.75 |
GUESTROOM105 | 0.50 | 8542.00 | 0.50 |
EMPLOYEELOUNGEFLR1 | 2991.50 | 2121.25 | 226.00 |
EXERCISECENTERFLR1 | 1102.00 | 2910.00 | 4.50 |
FRONTOFFICEFLR1 | 675.50 | 6284.00 | 71.75 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 315.75 | 8655.25 | 315.75 |
GUESTROOM206_208 | 218.00 | 8637.75 | 218.00 |
GUESTROOM209_212 | 159.50 | 8722.75 | 159.50 |
GUESTROOM213 | 1013.00 | 8744.75 | 1013.00 |
GUESTROOM214 | 214.25 | 8479.00 | 214.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3863.75 | 4248.75 | 514.75 |
GUESTROOM220_223 | 36.50 | 8301.00 | 36.50 |
GUESTROOM224 | 250.50 | 8432.75 | 250.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 330.50 | 8722.25 | 330.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 720.50 | 8479.25 | 720.50 |
GUESTROOM315_318 | 42.50 | 8190.00 | 42.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 171.00 | 8437.50 | 171.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 3081.00 | 8337.00 | 3045.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1270.25 | 8016.25 | 1129.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1058.75 | 7670.00 | 646.50 |
GUESTROOM419 | 947.00 | 7851.00 | 785.00 |
GUESTROOM420_423 | 1119.00 | 7703.50 | 732.75 |
GUESTROOM424 | 1901.25 | 7940.50 | 1721.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6853.25 | 8760.00 | 5414.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 35.75 | 880.25 | 35.75 | 880.25 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 3.75 | 23.75 | 3.75 | 23.75 |
GUESTROOM104 | 1.25 | 24.00 | 1.25 | 24.00 |
GUESTROOM105 | 0.00 | 35.25 | 0.00 | 35.25 |
EMPLOYEELOUNGEFLR1 | 195.25 | 1285.75 | 162.00 | 822.50 |
EXERCISECENTERFLR1 | 0.50 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.25 | 11.50 | 0.25 | 11.50 |
GUESTROOM206_208 | 0.25 | 22.00 | 0.25 | 22.00 |
GUESTROOM209_212 | 0.25 | 10.00 | 0.25 | 10.00 |
GUESTROOM213 | 4.00 | 12.00 | 4.00 | 12.00 |
GUESTROOM214 | 1.50 | 14.25 | 1.50 | 14.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2524.50 | 0.00 | 2524.50 |
GUESTROOM220_223 | 0.00 | 10.25 | 0.00 | 10.25 |
GUESTROOM224 | 1.75 | 14.00 | 1.75 | 14.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1.50 | 10.25 | 1.50 | 10.25 |
GUESTROOM313 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 3.75 | 13.75 | 3.75 | 13.75 |
GUESTROOM315_318 | 0.00 | 12.00 | 0.00 | 12.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1.00 | 8.50 | 1.00 | 8.50 |
GUESTROOM324 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 6.25 | 37.75 | 6.25 | 37.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 4.50 | 26.75 | 4.50 | 26.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 3.75 | 20.25 | 3.75 | 20.25 |
GUESTROOM419 | 3.50 | 25.50 | 3.50 | 25.50 |
GUESTROOM420_423 | 4.75 | 19.50 | 4.75 | 19.50 |
GUESTROOM424 | 5.50 | 24.25 | 5.50 | 24.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 1.00 | 2721.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 226.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.25 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 332.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 214.75 | 4601.75 | 186.00 | 3732.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:23
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.427446 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.12 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.845896 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 295.60 |
CORRIDORFLR1 PTAC HEATING COIL | 40752.70 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1008.89 |
102 PTAC HEATING COIL | 1008.89 |
103 PTAC HEATING COIL | 1323.23 |
104 PTAC HEATING COIL | 1204.34 |
105 PTAC HEATING COIL | 1008.82 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 295.53 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 295.60 |
CORRIDORFLR2 PTAC HEATING COIL | 2881.58 |
201 PTAC HEATING COIL | 1008.89 |
202_205 PTAC HEATING COIL | 4035.57 |
206_208 PTAC HEATING COIL | 3198.33 |
209_212 PTAC HEATING COIL | 4035.57 |
213 PTAC HEATING COIL | 1398.82 |
214 PTAC HEATING COIL | 1283.94 |
215_218 PTAC HEATING COIL | 4035.29 |
219 PTAC HEATING COIL | 1008.82 |
220_223 PTAC HEATING COIL | 4035.29 |
224 PTAC HEATING COIL | 1191.80 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 295.53 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 295.60 |
CORRIDORFLR3 PTAC HEATING COIL | 3445.19 |
301 PTAC HEATING COIL | 1008.89 |
302_305 PTAC HEATING COIL | 4035.57 |
306_308 PTAC HEATING COIL | 3198.33 |
309_312 PTAC HEATING COIL | 4035.57 |
313 PTAC HEATING COIL | 1086.05 |
314 PTAC HEATING COIL | 1420.58 |
315_318 PTAC HEATING COIL | 4035.29 |
319 PTAC HEATING COIL | 1008.82 |
320_323 PTAC HEATING COIL | 4035.29 |
324 PTAC HEATING COIL | 1008.82 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 295.53 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 295.60 |
CORRIDORFLR4 PTAC HEATING COIL | 4929.64 |
401 PTAC HEATING COIL | 1729.02 |
402_405 PTAC HEATING COIL | 4189.58 |
406_408 PTAC HEATING COIL | 3399.06 |
409_412 PTAC HEATING COIL | 5053.39 |
413 PTAC HEATING COIL | 1493.02 |
414 PTAC HEATING COIL | 1329.33 |
415_418 PTAC HEATING COIL | 4992.32 |
419 PTAC HEATING COIL | 1415.27 |
420_423 PTAC HEATING COIL | 4844.58 |
424 PTAC HEATING COIL | 1668.36 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 457.80 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.796833 | 0.427446 | 7111.00 |
SAC_FRONTLOUNGE COOLING COIL | 0.770839 | 1.12 | 20111.54 |
SAC_MEETINGROOM COOLING COIL | 0.739028 | 0.494846 | 9777.16 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.792609 | 0.845896 | 14236.72 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.12 |
RESTROOMFLR1 DIRECT AIR | 0.076543 |
MEETINGROOMFLR1 DIRECT AIR | 0.494846 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.624422 |
EXERCISECENTERFLR1 DIRECT AIR | 0.144932 |
FRONTOFFICEFLR1 DIRECT AIR | 0.427446 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.427446 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.12 |
SAC_MEETINGROOM MAIN BRANCH | 0.494846 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.845896 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.427446 |
SAC_FRONTLOUNGE | 1.12 |
SAC_MEETINGROOM | 0.494846 |
SAC_EXC_EMPLGE_RESTRM | 0.845896 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.427446 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.12 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.494846 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.845896 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.427446 | 0.427446 | 0.427446 | 0.427446 | 4154.18 | 7111.00 | 1.00 |
SAC_FRONTLOUNGE | 1.12 | 1.12 | 1.12 | 1.12 | 17412.14 | 20111.54 | 1.00 |
SAC_MEETINGROOM | 0.494846 | 0.494846 | 0.494846 | 0.494846 | 9324.07 | 9777.16 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.845896 | 0.845896 | 0.845896 | 0.845896 | 7032.57 | 14236.72 | 0.171335 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4154.18 |
SAC_FRONTLOUNGE HEATING COIL | 17412.14 |
SAC_MEETINGROOM HEATING COIL | 9324.07 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 7032.57 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.494846 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.42 | -1.7 |
February | 18.66 | 2.70 |
March | 19.46 | 6.07 |
April | 21.14 | 11.58 |
May | 22.30 | 14.61 |
June | 23.72 | 19.78 |
July | 25.28 | 24.54 |
August | 24.31 | 21.22 |
September | 23.31 | 17.37 |
October | 21.61 | 11.70 |
November | 19.36 | 4.05 |
December | 18.18 | 1.86 |
Annual Sum or Average | 21.24 | 11.20 |
Minimum of Months | 17.42 | -1.7 |
Maximum of Months | 25.28 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | -1.7 |
February | 22.60 | 2.70 |
March | 23.10 | 6.07 |
April | 23.91 | 11.58 |
May | 24.38 | 14.61 |
June | 25.41 | 19.78 |
July | 26.37 | 24.54 |
August | 25.75 | 21.22 |
September | 24.87 | 17.37 |
October | 23.89 | 11.70 |
November | 22.79 | 4.05 |
December | 22.36 | 1.86 |
Annual Sum or Average | 23.95 | 11.20 |
Minimum of Months | 21.88 | -1.7 |
Maximum of Months | 26.37 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.52 | -1.7 |
February | 17.74 | 2.70 |
March | 18.54 | 6.07 |
April | 20.30 | 11.58 |
May | 21.48 | 14.61 |
June | 22.95 | 19.78 |
July | 24.52 | 24.54 |
August | 23.58 | 21.22 |
September | 22.53 | 17.37 |
October | 20.75 | 11.70 |
November | 18.43 | 4.05 |
December | 17.26 | 1.86 |
Annual Sum or Average | 20.40 | 11.20 |
Minimum of Months | 16.52 | -1.7 |
Maximum of Months | 24.52 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -1.7 |
February | 21.16 | 2.70 |
March | 21.39 | 6.07 |
April | 22.24 | 11.58 |
May | 22.72 | 14.61 |
June | 23.32 | 19.78 |
July | 23.72 | 24.54 |
August | 23.44 | 21.22 |
September | 23.11 | 17.37 |
October | 22.13 | 11.70 |
November | 21.35 | 4.05 |
December | 21.13 | 1.86 |
Annual Sum or Average | 22.24 | 11.20 |
Minimum of Months | 21.11 | -1.7 |
Maximum of Months | 23.72 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | -1.7 |
February | 22.17 | 2.70 |
March | 22.41 | 6.07 |
April | 22.92 | 11.58 |
May | 23.22 | 14.61 |
June | 23.48 | 19.78 |
July | 23.68 | 24.54 |
August | 23.59 | 21.22 |
September | 23.41 | 17.37 |
October | 22.97 | 11.70 |
November | 22.34 | 4.05 |
December | 22.07 | 1.86 |
Annual Sum or Average | 22.85 | 11.20 |
Minimum of Months | 21.85 | -1.7 |
Maximum of Months | 23.68 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.40 | -1.7 |
February | 21.93 | 2.70 |
March | 22.46 | 6.07 |
April | 23.27 | 11.58 |
May | 23.60 | 14.61 |
June | 23.79 | 19.78 |
July | 23.88 | 24.54 |
August | 23.84 | 21.22 |
September | 23.74 | 17.37 |
October | 23.29 | 11.70 |
November | 22.17 | 4.05 |
December | 21.66 | 1.86 |
Annual Sum or Average | 22.92 | 11.20 |
Minimum of Months | 21.40 | -1.7 |
Maximum of Months | 23.88 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.97 | -1.7 |
February | 24.53 | 2.70 |
March | 24.96 | 6.07 |
April | 25.75 | 11.58 |
May | 26.16 | 14.61 |
June | 26.66 | 19.78 |
July | 27.03 | 24.54 |
August | 26.83 | 21.22 |
September | 26.45 | 17.37 |
October | 25.77 | 11.70 |
November | 24.75 | 4.05 |
December | 24.27 | 1.86 |
Annual Sum or Average | 25.60 | 11.20 |
Minimum of Months | 23.97 | -1.7 |
Maximum of Months | 27.03 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.19 | -1.7 |
February | 19.87 | 2.70 |
March | 20.63 | 6.07 |
April | 21.92 | 11.58 |
May | 22.49 | 14.61 |
June | 23.00 | 19.78 |
July | 23.27 | 24.54 |
August | 23.12 | 21.22 |
September | 22.86 | 17.37 |
October | 21.92 | 11.70 |
November | 20.22 | 4.05 |
December | 19.57 | 1.86 |
Annual Sum or Average | 21.51 | 11.20 |
Minimum of Months | 19.19 | -1.7 |
Maximum of Months | 23.27 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.01 | -1.7 |
February | 19.54 | 2.70 |
March | 20.26 | 6.07 |
April | 21.60 | 11.58 |
May | 22.21 | 14.61 |
June | 22.83 | 19.78 |
July | 23.20 | 24.54 |
August | 22.98 | 21.22 |
September | 22.63 | 17.37 |
October | 21.57 | 11.70 |
November | 19.89 | 4.05 |
December | 19.29 | 1.86 |
Annual Sum or Average | 21.26 | 11.20 |
Minimum of Months | 19.01 | -1.7 |
Maximum of Months | 23.20 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -1.7 |
February | 20.87 | 2.70 |
March | 21.05 | 6.07 |
April | 21.44 | 11.58 |
May | 21.61 | 14.61 |
June | 21.70 | 19.78 |
July | 21.75 | 24.54 |
August | 21.73 | 21.22 |
September | 21.69 | 17.37 |
October | 21.45 | 11.70 |
November | 21.01 | 4.05 |
December | 20.77 | 1.86 |
Annual Sum or Average | 21.31 | 11.20 |
Minimum of Months | 20.62 | -1.7 |
Maximum of Months | 21.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | -1.7 |
February | 21.12 | 2.70 |
March | 21.35 | 6.07 |
April | 21.64 | 11.58 |
May | 21.71 | 14.61 |
June | 21.75 | 19.78 |
July | 21.75 | 24.54 |
August | 21.75 | 21.22 |
September | 21.74 | 17.37 |
October | 21.63 | 11.70 |
November | 21.23 | 4.05 |
December | 20.99 | 1.86 |
Annual Sum or Average | 21.46 | 11.20 |
Minimum of Months | 20.81 | -1.7 |
Maximum of Months | 21.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | -1.7 |
February | 21.52 | 2.70 |
March | 21.64 | 6.07 |
April | 21.74 | 11.58 |
May | 21.75 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.73 | 11.70 |
November | 21.56 | 4.05 |
December | 21.42 | 1.86 |
Annual Sum or Average | 21.64 | 11.20 |
Minimum of Months | 21.26 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.43 | -1.7 |
February | 22.54 | 2.70 |
March | 22.59 | 6.07 |
April | 22.69 | 11.58 |
May | 22.74 | 14.61 |
June | 22.53 | 19.78 |
July | 22.31 | 24.54 |
August | 22.48 | 21.22 |
September | 22.70 | 17.37 |
October | 22.79 | 11.70 |
November | 22.63 | 4.05 |
December | 22.58 | 1.86 |
Annual Sum or Average | 22.58 | 11.20 |
Minimum of Months | 22.31 | -1.7 |
Maximum of Months | 22.79 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 50.51 | -1.7 |
February | 51.02 | 2.70 |
March | 51.44 | 6.07 |
April | 52.12 | 11.58 |
May | 52.57 | 14.61 |
June | 53.13 | 19.78 |
July | 53.65 | 24.54 |
August | 53.29 | 21.22 |
September | 52.84 | 17.37 |
October | 52.17 | 11.70 |
November | 51.23 | 4.05 |
December | 50.78 | 1.86 |
Annual Sum or Average | 52.07 | 11.20 |
Minimum of Months | 50.51 | -1.7 |
Maximum of Months | 53.65 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.59 | -1.7 |
February | 69.12 | 2.70 |
March | 69.49 | 6.07 |
April | 70.22 | 11.58 |
May | 70.87 | 14.61 |
June | 71.44 | 19.78 |
July | 72.19 | 24.54 |
August | 71.71 | 21.22 |
September | 71.22 | 17.37 |
October | 70.45 | 11.70 |
November | 69.46 | 4.05 |
December | 68.85 | 1.86 |
Annual Sum or Average | 70.31 | 11.20 |
Minimum of Months | 68.59 | -1.7 |
Maximum of Months | 72.19 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.72 | -1.7 |
February | 22.99 | 2.70 |
March | 23.20 | 6.07 |
April | 23.56 | 11.58 |
May | 23.74 | 14.61 |
June | 23.84 | 19.78 |
July | 23.89 | 24.54 |
August | 23.86 | 21.22 |
September | 23.83 | 17.37 |
October | 23.61 | 11.70 |
November | 23.13 | 4.05 |
December | 22.94 | 1.86 |
Annual Sum or Average | 23.44 | 11.20 |
Minimum of Months | 22.72 | -1.7 |
Maximum of Months | 23.89 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | -1.7 |
February | 22.49 | 2.70 |
March | 23.00 | 6.07 |
April | 23.57 | 11.58 |
May | 23.80 | 14.61 |
June | 23.86 | 19.78 |
July | 23.89 | 24.54 |
August | 23.88 | 21.22 |
September | 23.86 | 17.37 |
October | 23.64 | 11.70 |
November | 22.73 | 4.05 |
December | 22.27 | 1.86 |
Annual Sum or Average | 23.25 | 11.20 |
Minimum of Months | 21.93 | -1.7 |
Maximum of Months | 23.89 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.50 | -1.7 |
February | 17.82 | 2.70 |
March | 18.79 | 6.07 |
April | 20.81 | 11.58 |
May | 22.31 | 14.61 |
June | 24.09 | 19.78 |
July | 25.89 | 24.54 |
August | 24.60 | 21.22 |
September | 23.18 | 17.37 |
October | 21.16 | 11.70 |
November | 18.68 | 4.05 |
December | 17.36 | 1.86 |
Annual Sum or Average | 20.95 | 11.20 |
Minimum of Months | 16.50 | -1.7 |
Maximum of Months | 25.89 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | -1.7 |
February | 20.50 | 2.70 |
March | 21.22 | 6.07 |
April | 22.54 | 11.58 |
May | 23.40 | 14.61 |
June | 24.41 | 19.78 |
July | 25.37 | 24.54 |
August | 24.72 | 21.22 |
September | 23.91 | 17.37 |
October | 22.72 | 11.70 |
November | 21.03 | 4.05 |
December | 20.15 | 1.86 |
Annual Sum or Average | 22.47 | 11.20 |
Minimum of Months | 19.58 | -1.7 |
Maximum of Months | 25.37 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.63 | -1.7 |
February | 18.24 | 2.70 |
March | 19.27 | 6.07 |
April | 21.45 | 11.58 |
May | 22.87 | 14.61 |
June | 24.57 | 19.78 |
July | 26.43 | 24.54 |
August | 25.22 | 21.22 |
September | 24.03 | 17.37 |
October | 21.95 | 11.70 |
November | 19.08 | 4.05 |
December | 17.62 | 1.86 |
Annual Sum or Average | 21.46 | 11.20 |
Minimum of Months | 16.63 | -1.7 |
Maximum of Months | 26.43 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | -1.7 |
February | 21.92 | 2.70 |
March | 22.59 | 6.07 |
April | 23.52 | 11.58 |
May | 23.78 | 14.61 |
June | 23.88 | 19.78 |
July | 23.98 | 24.54 |
August | 23.93 | 21.22 |
September | 23.85 | 17.37 |
October | 23.55 | 11.70 |
November | 22.24 | 4.05 |
December | 21.66 | 1.86 |
Annual Sum or Average | 23.02 | 11.20 |
Minimum of Months | 21.31 | -1.7 |
Maximum of Months | 23.98 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.20 | -1.7 |
February | 16.77 | 2.70 |
March | 17.80 | 6.07 |
April | 20.17 | 11.58 |
May | 21.64 | 14.61 |
June | 23.46 | 19.78 |
July | 25.36 | 24.54 |
August | 24.18 | 21.22 |
September | 22.88 | 17.37 |
October | 20.62 | 11.70 |
November | 17.61 | 4.05 |
December | 16.17 | 1.86 |
Annual Sum or Average | 20.17 | 11.20 |
Minimum of Months | 15.20 | -1.7 |
Maximum of Months | 25.36 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -1.7 |
February | 19.06 | 2.70 |
March | 19.64 | 6.07 |
April | 21.52 | 11.58 |
May | 22.38 | 14.61 |
June | 23.03 | 19.78 |
July | 23.31 | 24.54 |
August | 23.14 | 21.22 |
September | 22.81 | 17.37 |
October | 21.27 | 11.70 |
November | 19.46 | 4.05 |
December | 18.94 | 1.86 |
Annual Sum or Average | 21.13 | 11.20 |
Minimum of Months | 18.90 | -1.7 |
Maximum of Months | 23.31 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.75 | -1.7 |
February | 21.04 | 2.70 |
March | 21.24 | 6.07 |
April | 21.62 | 11.58 |
May | 21.72 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.75 | 21.22 |
September | 21.74 | 17.37 |
October | 21.59 | 11.70 |
November | 21.15 | 4.05 |
December | 20.93 | 1.86 |
Annual Sum or Average | 21.42 | 11.20 |
Minimum of Months | 20.75 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | -1.7 |
February | 21.12 | 2.70 |
March | 21.31 | 6.07 |
April | 21.65 | 11.58 |
May | 21.73 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.75 | 21.22 |
September | 21.75 | 17.37 |
October | 21.63 | 11.70 |
November | 21.22 | 4.05 |
December | 21.00 | 1.86 |
Annual Sum or Average | 21.46 | 11.20 |
Minimum of Months | 20.81 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | -1.7 |
February | 21.15 | 2.70 |
March | 21.34 | 6.07 |
April | 21.64 | 11.58 |
May | 21.73 | 14.61 |
June | 21.75 | 19.78 |
July | 21.75 | 24.54 |
August | 21.75 | 21.22 |
September | 21.74 | 17.37 |
October | 21.63 | 11.70 |
November | 21.25 | 4.05 |
December | 21.03 | 1.86 |
Annual Sum or Average | 21.47 | 11.20 |
Minimum of Months | 20.83 | -1.7 |
Maximum of Months | 21.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | -1.7 |
February | 20.85 | 2.70 |
March | 21.06 | 6.07 |
April | 21.51 | 11.58 |
May | 21.66 | 14.61 |
June | 21.73 | 19.78 |
July | 21.75 | 24.54 |
August | 21.75 | 21.22 |
September | 21.72 | 17.37 |
October | 21.49 | 11.70 |
November | 20.99 | 4.05 |
December | 20.74 | 1.86 |
Annual Sum or Average | 21.32 | 11.20 |
Minimum of Months | 20.58 | -1.7 |
Maximum of Months | 21.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.85 | -1.7 |
February | 21.20 | 2.70 |
March | 21.45 | 6.07 |
April | 21.71 | 11.58 |
May | 21.74 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.70 | 11.70 |
November | 21.30 | 4.05 |
December | 21.05 | 1.86 |
Annual Sum or Average | 21.50 | 11.20 |
Minimum of Months | 20.85 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.62 | -1.7 |
February | 23.05 | 2.70 |
March | 23.22 | 6.07 |
April | 23.32 | 11.58 |
May | 23.33 | 14.61 |
June | 23.33 | 19.78 |
July | 23.33 | 24.54 |
August | 23.33 | 21.22 |
September | 23.33 | 17.37 |
October | 23.32 | 11.70 |
November | 23.10 | 4.05 |
December | 22.96 | 1.86 |
Annual Sum or Average | 23.19 | 11.20 |
Minimum of Months | 22.62 | -1.7 |
Maximum of Months | 23.33 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 30.14 | -1.7 |
February | 30.75 | 2.70 |
March | 31.28 | 6.07 |
April | 32.29 | 11.58 |
May | 32.87 | 14.61 |
June | 33.42 | 19.78 |
July | 34.01 | 24.54 |
August | 33.59 | 21.22 |
September | 33.14 | 17.37 |
October | 32.35 | 11.70 |
November | 31.09 | 4.05 |
December | 30.45 | 1.86 |
Annual Sum or Average | 32.12 | 11.20 |
Minimum of Months | 30.14 | -1.7 |
Maximum of Months | 34.01 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | -1.7 |
February | 21.83 | 2.70 |
March | 21.98 | 6.07 |
April | 22.35 | 11.58 |
May | 22.53 | 14.61 |
June | 22.89 | 19.78 |
July | 23.29 | 24.54 |
August | 22.98 | 21.22 |
September | 22.65 | 17.37 |
October | 22.29 | 11.70 |
November | 21.90 | 4.05 |
December | 21.79 | 1.86 |
Annual Sum or Average | 22.36 | 11.20 |
Minimum of Months | 21.77 | -1.7 |
Maximum of Months | 23.29 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | -1.7 |
February | 21.34 | 2.70 |
March | 21.57 | 6.07 |
April | 21.74 | 11.58 |
May | 21.75 | 14.61 |
June | 21.76 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.73 | 11.70 |
November | 21.40 | 4.05 |
December | 21.20 | 1.86 |
Annual Sum or Average | 21.56 | 11.20 |
Minimum of Months | 21.01 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | -1.7 |
February | 21.17 | 2.70 |
March | 21.44 | 6.07 |
April | 21.72 | 11.58 |
May | 21.74 | 14.61 |
June | 21.76 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.71 | 11.70 |
November | 21.27 | 4.05 |
December | 21.02 | 1.86 |
Annual Sum or Average | 21.49 | 11.20 |
Minimum of Months | 20.83 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.34 | -1.7 |
February | 19.56 | 2.70 |
March | 20.51 | 6.07 |
April | 22.36 | 11.58 |
May | 23.46 | 14.61 |
June | 24.78 | 19.78 |
July | 26.01 | 24.54 |
August | 25.11 | 21.22 |
September | 24.05 | 17.37 |
October | 22.47 | 11.70 |
November | 20.21 | 4.05 |
December | 19.09 | 1.86 |
Annual Sum or Average | 22.18 | 11.20 |
Minimum of Months | 18.34 | -1.7 |
Maximum of Months | 26.01 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.96 | -1.7 |
February | 16.77 | 2.70 |
March | 18.07 | 6.07 |
April | 20.83 | 11.58 |
May | 22.74 | 14.61 |
June | 24.98 | 19.78 |
July | 27.22 | 24.54 |
August | 25.54 | 21.22 |
September | 23.75 | 17.37 |
October | 21.16 | 11.70 |
November | 17.83 | 4.05 |
December | 16.14 | 1.86 |
Annual Sum or Average | 20.85 | 11.20 |
Minimum of Months | 14.96 | -1.7 |
Maximum of Months | 27.22 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.67 | -1.7 |
February | 17.38 | 2.70 |
March | 18.57 | 6.07 |
April | 21.12 | 11.58 |
May | 22.74 | 14.61 |
June | 24.67 | 19.78 |
July | 26.71 | 24.54 |
August | 25.35 | 21.22 |
September | 23.98 | 17.37 |
October | 21.57 | 11.70 |
November | 18.29 | 4.05 |
December | 16.72 | 1.86 |
Annual Sum or Average | 21.08 | 11.20 |
Minimum of Months | 15.67 | -1.7 |
Maximum of Months | 26.71 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -1.7 |
February | 21.14 | 2.70 |
March | 21.48 | 6.07 |
April | 22.77 | 11.58 |
May | 23.34 | 14.61 |
June | 23.73 | 19.78 |
July | 23.88 | 24.54 |
August | 23.80 | 21.22 |
September | 23.60 | 17.37 |
October | 22.63 | 11.70 |
November | 21.42 | 4.05 |
December | 21.12 | 1.86 |
Annual Sum or Average | 22.51 | 11.20 |
Minimum of Months | 21.11 | -1.7 |
Maximum of Months | 23.88 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.89 | -1.7 |
February | 15.56 | 2.70 |
March | 16.77 | 6.07 |
April | 19.66 | 11.58 |
May | 21.41 | 14.61 |
June | 23.56 | 19.78 |
July | 25.71 | 24.54 |
August | 24.33 | 21.22 |
September | 22.80 | 17.37 |
October | 20.01 | 11.70 |
November | 16.47 | 4.05 |
December | 14.92 | 1.86 |
Annual Sum or Average | 19.61 | 11.20 |
Minimum of Months | 13.89 | -1.7 |
Maximum of Months | 25.71 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -1.7 |
February | 18.91 | 2.70 |
March | 19.19 | 6.07 |
April | 21.00 | 11.58 |
May | 21.98 | 14.61 |
June | 22.87 | 19.78 |
July | 23.27 | 24.54 |
August | 23.01 | 21.22 |
September | 22.51 | 17.37 |
October | 20.61 | 11.70 |
November | 19.14 | 4.05 |
December | 18.89 | 1.86 |
Annual Sum or Average | 20.87 | 11.20 |
Minimum of Months | 18.89 | -1.7 |
Maximum of Months | 23.27 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -1.7 |
February | 18.98 | 2.70 |
March | 19.49 | 6.07 |
April | 21.44 | 11.58 |
May | 22.30 | 14.61 |
June | 23.03 | 19.78 |
July | 23.30 | 24.54 |
August | 23.13 | 21.22 |
September | 22.76 | 17.37 |
October | 21.06 | 11.70 |
November | 19.30 | 4.05 |
December | 18.90 | 1.86 |
Annual Sum or Average | 21.06 | 11.20 |
Minimum of Months | 18.89 | -1.7 |
Maximum of Months | 23.30 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -1.7 |
February | 19.05 | 2.70 |
March | 19.68 | 6.07 |
April | 21.60 | 11.58 |
May | 22.39 | 14.61 |
June | 23.04 | 19.78 |
July | 23.30 | 24.54 |
August | 23.14 | 21.22 |
September | 22.79 | 17.37 |
October | 21.23 | 11.70 |
November | 19.39 | 4.05 |
December | 18.92 | 1.86 |
Annual Sum or Average | 21.13 | 11.20 |
Minimum of Months | 18.90 | -1.7 |
Maximum of Months | 23.30 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | -1.7 |
February | 21.04 | 2.70 |
March | 21.24 | 6.07 |
April | 21.60 | 11.58 |
May | 21.71 | 14.61 |
June | 21.74 | 19.78 |
July | 21.75 | 24.54 |
August | 21.75 | 21.22 |
September | 21.73 | 17.37 |
October | 21.57 | 11.70 |
November | 21.15 | 4.05 |
December | 20.91 | 1.86 |
Annual Sum or Average | 21.41 | 11.20 |
Minimum of Months | 20.73 | -1.7 |
Maximum of Months | 21.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -1.7 |
February | 18.97 | 2.70 |
March | 19.47 | 6.07 |
April | 21.34 | 11.58 |
May | 22.20 | 14.61 |
June | 22.96 | 19.78 |
July | 23.30 | 24.54 |
August | 23.11 | 21.22 |
September | 22.73 | 17.37 |
October | 21.15 | 11.70 |
November | 19.37 | 4.05 |
December | 18.91 | 1.86 |
Annual Sum or Average | 21.04 | 11.20 |
Minimum of Months | 18.89 | -1.7 |
Maximum of Months | 23.30 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | -1.7 |
February | 20.98 | 2.70 |
March | 21.26 | 6.07 |
April | 21.65 | 11.58 |
May | 21.72 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.62 | 11.70 |
November | 21.10 | 4.05 |
December | 20.83 | 1.86 |
Annual Sum or Average | 21.40 | 11.20 |
Minimum of Months | 20.65 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | -1.7 |
February | 21.36 | 2.70 |
March | 21.58 | 6.07 |
April | 21.74 | 11.58 |
May | 21.75 | 14.61 |
June | 21.76 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.73 | 11.70 |
November | 21.41 | 4.05 |
December | 21.21 | 1.86 |
Annual Sum or Average | 21.57 | 11.20 |
Minimum of Months | 21.01 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | -1.7 |
February | 22.35 | 2.70 |
March | 23.08 | 6.07 |
April | 24.51 | 11.58 |
May | 25.24 | 14.61 |
June | 25.96 | 19.78 |
July | 26.56 | 24.54 |
August | 26.11 | 21.22 |
September | 25.56 | 17.37 |
October | 24.45 | 11.70 |
November | 22.75 | 4.05 |
December | 21.97 | 1.86 |
Annual Sum or Average | 24.18 | 11.20 |
Minimum of Months | 21.56 | -1.7 |
Maximum of Months | 26.56 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.93 | -1.7 |
February | 21.01 | 2.70 |
March | 21.96 | 6.07 |
April | 23.00 | 11.58 |
May | 23.23 | 14.61 |
June | 23.31 | 19.78 |
July | 23.33 | 24.54 |
August | 23.33 | 21.22 |
September | 23.29 | 17.37 |
October | 22.97 | 11.70 |
November | 21.31 | 4.05 |
December | 20.57 | 1.86 |
Annual Sum or Average | 22.28 | 11.20 |
Minimum of Months | 19.93 | -1.7 |
Maximum of Months | 23.33 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.85 | -1.7 |
February | 21.19 | 2.70 |
March | 21.45 | 6.07 |
April | 21.71 | 11.58 |
May | 21.74 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.75 | 21.22 |
September | 21.75 | 17.37 |
October | 21.69 | 11.70 |
November | 21.27 | 4.05 |
December | 21.04 | 1.86 |
Annual Sum or Average | 21.50 | 11.20 |
Minimum of Months | 20.85 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | -1.7 |
February | 19.25 | 2.70 |
March | 20.21 | 6.07 |
April | 22.04 | 11.58 |
May | 22.69 | 14.61 |
June | 23.15 | 19.78 |
July | 23.32 | 24.54 |
August | 23.21 | 21.22 |
September | 22.97 | 17.37 |
October | 21.87 | 11.70 |
November | 19.78 | 4.05 |
December | 19.05 | 1.86 |
Annual Sum or Average | 21.38 | 11.20 |
Minimum of Months | 18.91 | -1.7 |
Maximum of Months | 23.32 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.99 | -1.7 |
February | 18.35 | 2.70 |
March | 19.52 | 6.07 |
April | 21.93 | 11.58 |
May | 23.29 | 14.61 |
June | 24.90 | 19.78 |
July | 26.32 | 24.54 |
August | 25.24 | 21.22 |
September | 23.97 | 17.37 |
October | 21.93 | 11.70 |
November | 19.10 | 4.05 |
December | 17.81 | 1.86 |
Annual Sum or Average | 21.63 | 11.20 |
Minimum of Months | 16.99 | -1.7 |
Maximum of Months | 26.32 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.74 | -1.7 |
February | 15.73 | 2.70 |
March | 17.24 | 6.07 |
April | 20.45 | 11.58 |
May | 22.61 | 14.61 |
June | 25.13 | 19.78 |
July | 27.60 | 24.54 |
August | 25.71 | 21.22 |
September | 23.69 | 17.37 |
October | 20.70 | 11.70 |
November | 16.88 | 4.05 |
December | 15.04 | 1.86 |
Annual Sum or Average | 20.40 | 11.20 |
Minimum of Months | 13.74 | -1.7 |
Maximum of Months | 27.60 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.18 | -1.7 |
February | 16.05 | 2.70 |
March | 17.53 | 6.07 |
April | 20.59 | 11.58 |
May | 22.49 | 14.61 |
June | 24.78 | 19.78 |
July | 27.06 | 24.54 |
August | 25.45 | 21.22 |
September | 23.77 | 17.37 |
October | 20.81 | 11.70 |
November | 16.96 | 4.05 |
December | 15.29 | 1.86 |
Annual Sum or Average | 20.44 | 11.20 |
Minimum of Months | 14.18 | -1.7 |
Maximum of Months | 27.06 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -1.7 |
February | 21.14 | 2.70 |
March | 21.43 | 6.07 |
April | 22.35 | 11.58 |
May | 22.84 | 14.61 |
June | 23.45 | 19.78 |
July | 23.92 | 24.54 |
August | 23.56 | 21.22 |
September | 23.10 | 17.37 |
October | 22.09 | 11.70 |
November | 21.26 | 4.05 |
December | 21.11 | 1.86 |
Annual Sum or Average | 22.29 | 11.20 |
Minimum of Months | 21.11 | -1.7 |
Maximum of Months | 23.92 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.83 | -1.7 |
February | 14.66 | 2.70 |
March | 16.08 | 6.07 |
April | 19.26 | 11.58 |
May | 21.21 | 14.61 |
June | 23.66 | 19.78 |
July | 26.00 | 24.54 |
August | 24.40 | 21.22 |
September | 22.58 | 17.37 |
October | 19.38 | 11.70 |
November | 15.50 | 4.05 |
December | 13.92 | 1.86 |
Annual Sum or Average | 19.15 | 11.20 |
Minimum of Months | 12.83 | -1.7 |
Maximum of Months | 26.00 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -1.7 |
February | 20.55 | 2.70 |
March | 20.75 | 6.07 |
April | 21.33 | 11.58 |
May | 21.59 | 14.61 |
June | 21.70 | 19.78 |
July | 21.76 | 24.54 |
August | 21.73 | 21.22 |
September | 21.64 | 17.37 |
October | 21.19 | 11.70 |
November | 20.70 | 4.05 |
December | 20.50 | 1.86 |
Annual Sum or Average | 21.16 | 11.20 |
Minimum of Months | 20.48 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -1.7 |
February | 18.97 | 2.70 |
March | 19.41 | 6.07 |
April | 20.95 | 11.58 |
May | 21.76 | 14.61 |
June | 22.66 | 19.78 |
July | 23.15 | 24.54 |
August | 22.78 | 21.22 |
September | 22.21 | 17.37 |
October | 20.45 | 11.70 |
November | 19.11 | 4.05 |
December | 18.90 | 1.86 |
Annual Sum or Average | 20.78 | 11.20 |
Minimum of Months | 18.89 | -1.7 |
Maximum of Months | 23.15 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -1.7 |
February | 19.01 | 2.70 |
March | 19.50 | 6.07 |
April | 21.02 | 11.58 |
May | 21.81 | 14.61 |
June | 22.67 | 19.78 |
July | 23.14 | 24.54 |
August | 22.78 | 21.22 |
September | 22.22 | 17.37 |
October | 20.54 | 11.70 |
November | 19.15 | 4.05 |
December | 18.91 | 1.86 |
Annual Sum or Average | 20.81 | 11.20 |
Minimum of Months | 18.89 | -1.7 |
Maximum of Months | 23.14 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -1.7 |
February | 20.95 | 2.70 |
March | 21.21 | 6.07 |
April | 21.60 | 11.58 |
May | 21.71 | 14.61 |
June | 21.74 | 19.78 |
July | 21.76 | 24.54 |
August | 21.75 | 21.22 |
September | 21.72 | 17.37 |
October | 21.53 | 11.70 |
November | 21.05 | 4.05 |
December | 20.77 | 1.86 |
Annual Sum or Average | 21.37 | 11.20 |
Minimum of Months | 20.60 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -1.7 |
February | 18.98 | 2.70 |
March | 19.41 | 6.07 |
April | 20.96 | 11.58 |
May | 21.77 | 14.61 |
June | 22.66 | 19.78 |
July | 23.17 | 24.54 |
August | 22.82 | 21.22 |
September | 22.27 | 17.37 |
October | 20.62 | 11.70 |
November | 19.17 | 4.05 |
December | 18.90 | 1.86 |
Annual Sum or Average | 20.81 | 11.20 |
Minimum of Months | 18.89 | -1.7 |
Maximum of Months | 23.17 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -1.7 |
February | 19.07 | 2.70 |
March | 19.80 | 6.07 |
April | 21.46 | 11.58 |
May | 22.17 | 14.61 |
June | 22.87 | 19.78 |
July | 23.23 | 24.54 |
August | 22.96 | 21.22 |
September | 22.56 | 17.37 |
October | 21.21 | 11.70 |
November | 19.41 | 4.05 |
December | 18.94 | 1.86 |
Annual Sum or Average | 21.06 | 11.20 |
Minimum of Months | 18.90 | -1.7 |
Maximum of Months | 23.23 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | -1.7 |
February | 21.19 | 2.70 |
March | 21.49 | 6.07 |
April | 21.71 | 11.58 |
May | 21.74 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.69 | 11.70 |
November | 21.22 | 4.05 |
December | 20.93 | 1.86 |
Annual Sum or Average | 21.48 | 11.20 |
Minimum of Months | 20.74 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.18 | -1.7 |
February | 20.09 | 2.70 |
March | 20.95 | 6.07 |
April | 22.57 | 11.58 |
May | 23.42 | 14.61 |
June | 24.44 | 19.78 |
July | 25.24 | 24.54 |
August | 24.57 | 21.22 |
September | 23.72 | 17.37 |
October | 22.29 | 11.70 |
November | 20.39 | 4.05 |
December | 19.61 | 1.86 |
Annual Sum or Average | 22.22 | 11.20 |
Minimum of Months | 19.18 | -1.7 |
Maximum of Months | 25.24 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | -1.7 |
February | 21.12 | 2.70 |
March | 21.44 | 6.07 |
April | 21.71 | 11.58 |
May | 21.74 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.75 | 17.37 |
October | 21.67 | 11.70 |
November | 21.18 | 4.05 |
December | 20.87 | 1.86 |
Annual Sum or Average | 21.45 | 11.20 |
Minimum of Months | 20.70 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.71 | -1.7 |
February | 21.15 | 2.70 |
March | 21.46 | 6.07 |
April | 21.71 | 11.58 |
May | 21.73 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.75 | 21.22 |
September | 21.75 | 17.37 |
October | 21.68 | 11.70 |
November | 21.19 | 4.05 |
December | 20.89 | 1.86 |
Annual Sum or Average | 21.46 | 11.20 |
Minimum of Months | 20.71 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | -1.7 |
February | 20.86 | 2.70 |
March | 21.24 | 6.07 |
April | 21.66 | 11.58 |
May | 21.72 | 14.61 |
June | 21.75 | 19.78 |
July | 21.76 | 24.54 |
August | 21.76 | 21.22 |
September | 21.74 | 17.37 |
October | 21.60 | 11.70 |
November | 20.99 | 4.05 |
December | 20.67 | 1.86 |
Annual Sum or Average | 21.36 | 11.20 |
Minimum of Months | 20.54 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.29 | -1.7 |
February | 17.80 | 2.70 |
March | 19.14 | 6.07 |
April | 21.69 | 11.58 |
May | 23.16 | 14.61 |
June | 24.94 | 19.78 |
July | 26.49 | 24.54 |
August | 25.24 | 21.22 |
September | 23.76 | 17.37 |
October | 21.48 | 11.70 |
November | 18.46 | 4.05 |
December | 17.15 | 1.86 |
Annual Sum or Average | 21.32 | 11.20 |
Minimum of Months | 16.29 | -1.7 |
Maximum of Months | 26.49 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:23
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.70 | -1.7 |
February | 14.88 | 2.70 |
March | 16.62 | 6.07 |
April | 20.11 | 11.58 |
May | 22.44 | 14.61 |
June | 25.21 | 19.78 |
July | 27.84 | 24.54 |
August | 25.75 | 21.22 |
September | 23.47 | 17.37 |
October | 20.13 | 11.70 |
November | 15.96 | 4.05 |
December | 14.07 | 1.86 |
Annual Sum or Average | 19.96 | 11.20 |
Minimum of Months | 12.70 | -1.7 |
Maximum of Months | 27.84 | 24.54 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:23
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.185162E+12 | 152533.393 | 13-JAN-07:00 | 17938.631 | 34285.948 | 9443.399 | 86546.277 | 123.026 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.145957E+12 | 119707.876 | 27-FEB-07:15 | 20847.837 | 39740.848 | 9441.395 | 45165.565 | 316.118 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.153399E+12 | 115884.531 | 15-MAR-06:15 | 20847.837 | 39740.848 | 9441.395 | 41138.952 | 519.386 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.149906E+12 | 107402.762 | 09-APR-06:15 | 20847.837 | 39740.848 | 9441.395 | 31750.102 | 1426.467 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.158965E+12 | 96101.283 | 27-MAY-07:00 | 25182.171 | 43578.554 | 10015.831 | 0.000 | 17316.614 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.167375E+12 | 107356.313 | 21-JUN-19:15 | 27551.975 | 28549.175 | 9590.655 | 0.000 | 41656.395 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.186773E+12 | 111806.321 | 21-JUL-17:30 | 26252.371 | 28657.799 | 9685.844 | 0.000 | 47202.194 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.176391E+12 | 107539.596 | 04-AUG-17:15 | 26252.371 | 28657.799 | 9637.508 | 0.000 | 42983.806 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.159363E+12 | 99420.042 | 01-SEP-07:00 | 25182.171 | 43578.554 | 10015.831 | 0.000 | 20635.373 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.153555E+12 | 104150.988 | 24-OCT-06:00 | 20847.837 | 39740.848 | 9441.395 | 27743.121 | 2181.674 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.156858E+12 | 126864.983 | 15-NOV-07:15 | 20847.837 | 39740.848 | 9441.395 | 52384.809 | 253.982 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.169343E+12 | 132223.830 | 11-DEC-07:15 | 20847.837 | 39740.848 | 9441.395 | 57778.985 | 218.653 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.196305E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.145957E+12 | 96101.283 | 17938.631 | 28549.175 | 9441.395 | 0.000 | 123.026 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.186773E+12 | 152533.393 | 27551.975 | 43578.554 | 10015.831 | 86546.277 | 47202.194 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:23
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.111784E+12 | 111790.655 | 21-JAN-09:15 | 1416.780 | 40096.028 | 0.000 | 70277.847 | 70277.847 | 70277.847 | 1416.780 |
February | 0.944837E+11 | 109459.594 | 17-FEB-09:15 | 197.045 | 40096.028 | 0.000 | 69166.520 | 69166.520 | 69166.520 | 197.045 |
March | 0.998169E+11 | 105193.451 | 17-MAR-08:15 | 0.000 | 40096.028 | 0.000 | 65097.422 | 65097.422 | 65097.422 | 0.000 |
April | 0.910071E+11 | 105340.067 | 08-APR-08:15 | 524.916 | 40096.028 | 0.000 | 64719.122 | 64719.122 | 64719.122 | 524.916 |
May | 0.894377E+11 | 96346.506 | 27-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 56250.478 | 56250.478 | 56250.478 | 0.000 |
June | 0.828379E+11 | 92579.153 | 09-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 52483.125 | 52483.125 | 52483.125 | 0.000 |
July | 0.829019E+11 | 85268.525 | 04-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 45172.497 | 45172.497 | 45172.497 | 0.000 |
August | 0.821042E+11 | 83872.973 | 12-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 43776.945 | 43776.945 | 43776.945 | 0.000 |
September | 0.805255E+11 | 88664.252 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 48568.224 | 48568.224 | 48568.224 | 0.000 |
October | 0.868986E+11 | 91926.406 | 13-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 51830.378 | 51830.378 | 51830.378 | 0.000 |
November | 0.936989E+11 | 102687.700 | 24-NOV-09:15 | 1035.913 | 40096.028 | 0.000 | 61555.759 | 61555.759 | 61555.759 | 1035.913 |
December | 0.103080E+12 | 111355.467 | 29-DEC-09:15 | 3187.469 | 40096.028 | 0.000 | 68071.970 | 68071.970 | 68071.970 | 3187.469 |
Annual Sum or Average | 0.109858E+13 | 0.000 | ||||||||
Minimum of Months | 0.805255E+11 | 83872.973 | 0.000 | 40096.028 | 0.000 | 43776.945 | 43776.945 | 43776.945 | 0.000 | |
Maximum of Months | 0.111784E+12 | 111790.655 | 3187.469 | 40096.028 | 0.000 | 70277.847 | 70277.847 | 70277.847 | 3187.469 |