Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:43

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060

Simulation Timestamp: 2015-09-14 08:44:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3131.47 780.22 840.64
Net Site Energy 3131.47 780.22 840.64
Total Source Energy 7679.16 1913.29 2061.47
Net Source Energy 7679.16 1913.29 2061.47


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 164.13 55.17 0.00 0.00 0.00 0.00
Cooling 350.10 0.00 0.00 0.00 0.00 0.00
Interior Lighting 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.82 0.00 0.00 0.00 0.00 0.00
Interior Equipment 601.95 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 296.58 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 597.85 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2056.96 1074.51 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 164.13 55.17 0.00 0.00 0.00 0.00
Cooling General 350.10 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 578.13 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.82 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 573.47 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 296.58 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 597.85 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 172.87 0.00 0.00 0.00 0.00 0.00
HVAC 217.73 175.30 0.00 0.00 0.00 0.69
Other 161.59 113.15 0.00 0.00 0.00 0.00
Total 552.19 288.45 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 160.44 0.00 0.00 0.00 0.00 0.00
HVAC 202.08 162.70 0.00 0.00 0.00 0.64
Other 149.98 105.02 0.00 0.00 0.00 0.00
Total 512.50 267.72 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2056.96 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2056.96 100.00
     
Total On-Site and Utility Electric Sources 2056.96 100.00
Total Electricity End Uses 2056.96 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 277.25
Time Setpoint Not Met During Occupied Cooling 4092.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 6106.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:43
RunPeriod Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Weather File Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Latitude [deg] 39.17
Longitude [deg] -76.7
Elevation [m] 45.00
Time Zone -5.0
North Axis Angle [deg] 90.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 211.83 635.46 211.83 635.46
Window Opening Area [m2] 184.20 8.38 72.38 6.62 96.82
Window-Wall Ratio [%] 10.87 3.95 11.39 3.13 15.24


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 211.83 556.77 116.50 607.21
Window Opening Area [m2] 179.26 8.38 67.45 6.62 96.82
Window-Wall Ratio [%] 12.01 3.95 12.11 5.68 15.95


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 8.3610   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 6.9675   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 11.1480   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 15.3285 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 12.5415 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 18.1154 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 20.9024   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 11.8403 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 16.7220 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 8.3610 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2155.0206
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 12.5415 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 15.3285 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 8.3610   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 11.1480   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 8.3610   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 6.9675   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 11.1480   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 11.8403 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 11.8403 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 11.8403 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 11.8403 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 11.1480   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 8.3610   0.0000
Total 4013.58     11621.73   1694.58 184.20 11.2819 15.53 28.2097
Conditioned Total 3725.09     10741.65   1492.32 179.26 11.5457 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 7.8766 26.23 260.8031
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB -10.60 0.00 -10.60 Wetbulb [C] 3.90 290.00
BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 34.40 10.40 23.90 Wetbulb [C] 4.60 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 90.00 90.00 E
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 0.00 90.00 N
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 270.00 90.00 W
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 90.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 180.00 90.00 S
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 270.00 90.00 W
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 270.00 90.00 W
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 90.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 270.00 90.00 W
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 90.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 270.00 90.00 W
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 90.00 90.00 E
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 90.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 90.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 90.00 90.00 E
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 90.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 90.00 90.00 E
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 90.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 90.00 90.00 E
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 0.00 90.00 N
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 90.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 90.00 90.00 E
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 90.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 90.00 90.00 E
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 0.00 90.00 N
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 270.00 90.00 W
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 270.00 90.00 W
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 90.00 90.00 E
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 0.00 90.00 N
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 270.00 90.00 W
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 270.00 90.00 W
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 90.00 90.00 E
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 90.00 90.00 E
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 0.00 90.00 N
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 270.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 180.00 90.00 S
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 270.00 90.00 W
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 270.00 90.00 W
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 270.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 270.00 90.00 W
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 270.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 270.00 90.00 W
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 270.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 90.00 90.00 E
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 270.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 90.00 90.00 E
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 270.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 90.00 90.00 E
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 270.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 90.00 90.00 E
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 0.00 90.00 N
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 270.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 180.00 90.00 S
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 0.00 90.00 N
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 270.00 90.00 W
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 270.00 90.00 W
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 270.00 90.00 W
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 270.00 90.00 W
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 90.00 90.00 E
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 90.00 90.00 E
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 90.00 90.00 E
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 90.00 90.00 E
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 180.00 90.00 S
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 0.00 90.00 N
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 270.00 90.00 W
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 270.00 90.00 W
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 90.00 90.00 E
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 90.00 90.00 E
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 90.00 90.00 E
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 180.00 90.00 S
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 0.00 90.00 N
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 270.00 90.00 W
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 270.00 90.00 W
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 90.00 90.00 E
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 90.00 90.00 E
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 90.00 90.00 E
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 180.00 90.00 S
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 0.00 90.00 N
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 270.00 90.00 W
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 270.00 90.00 W
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 90.00 90.00 E
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 90.00 90.00 E
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 90.00 90.00 E
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           8.38 2.653 0.426 0.308              
Non-North Total or Average           175.82 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.54    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.54    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.54    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   8165.09 5855.03 2310.05 0.72 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   24579.22 16737.47 7841.75 0.68 3.50    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   11105.93 7508.53 3597.40 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   15809.22 11531.16 4278.06 0.73 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.00 10.24 10.86 10.31
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.00 10.24 10.86 10.31
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.00 10.24 10.86 10.31
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7867.0 3.30 11.26 11.93 11.28
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 23794.6 3.05 10.40 11.04 10.63
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 10758.3 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 15207.3 3.28 11.18 11.85 11.17
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   319.72 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   36836.09 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   512.05 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   997.40 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1257.99 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1139.08 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   997.33 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   319.65 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   319.72 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   2839.58 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   997.40 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   3989.60 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3161.90 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   3989.60 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1338.82 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1222.00 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   3989.32 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   997.33 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   3989.32 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1110.24 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   319.65 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   319.72 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   3388.17 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   997.40 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   3989.60 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3161.90 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   3989.60 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1014.98 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1352.18 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   3989.32 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   997.33 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   3989.32 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   997.33 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   452.58 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   319.72 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   4667.65 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1535.68 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   3989.60 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   3161.90 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   4511.66 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   1361.52 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1201.87 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   4424.39 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1267.71 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   4280.72 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1513.36 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   452.58 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   4106.85 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   17213.78 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   9217.85 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   6923.16 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:ConstantVolume 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.54 622.50 0.38 445.54 1160.84 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.55 622.50 1.01 1150.94 1140.11 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.54 622.50 0.45 519.17 1160.84 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.55 622.50 0.78 883.72 1140.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.51 0.27
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 10149.68 12179.61 0.841 1.010 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.94 0.01446
RESTROOMFLR1 702.03 842.44 0.058 0.070 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.90 0.01446
MEETINGROOMFLR1 4494.25 5393.10 0.373 0.447 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
GUESTROOM101 563.12 675.75 0.049 0.059 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM102 428.31 513.97 0.038 0.045 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM103 1540.34 1848.41 0.177 0.213 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM104 1415.48 1698.57 0.163 0.196 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM105 1834.70 2201.64 0.211 0.254 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.23 0.01446
EMPLOYEELOUNGEFLR1 5734.29 6881.14 0.475 0.570 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
EXERCISECENTERFLR1 1357.34 1628.81 0.112 0.135 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 28.68 0.01446
FRONTOFFICEFLR1 3861.91 4634.29 0.320 0.384 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM201 912.67 1095.21 0.080 0.096 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
GUESTROOM202_205 6067.09 7280.51 0.699 0.838 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM206_208 4959.64 5951.57 0.571 0.685 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
GUESTROOM209_212 5670.40 6804.48 0.653 0.784 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
GUESTROOM213 1663.33 1996.00 0.192 0.230 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM214 1654.85 1985.82 0.191 0.229 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM215_218 8848.25 10617.89 0.776 0.932 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.23 0.01446
GUESTROOM219 5765.35 6918.42 0.664 0.797 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM220_223 5482.65 6579.18 0.631 0.758 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM224 1651.73 1982.07 0.190 0.228 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM301 786.33 943.60 0.069 0.083 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.94 0.01446
GUESTROOM302_305 2092.86 2511.44 0.184 0.220 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM306_308 1881.09 2257.31 0.165 0.198 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
GUESTROOM309_312 5695.96 6835.15 0.656 0.787 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM313 725.70 870.84 0.064 0.076 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 32.42 0.01446
GUESTROOM314 1589.27 1907.12 0.183 0.220 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 32.01 0.01446
GUESTROOM315_318 6182.26 7418.71 0.712 0.854 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM319 902.68 1083.22 0.079 0.095 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM320_323 5326.79 6392.15 0.613 0.736 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM324 592.35 710.82 0.052 0.062 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 31.62 0.01446
GUESTROOM401 2156.55 2587.86 0.248 0.298 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.36 0.01446
GUESTROOM402_405 3120.95 3745.14 0.274 0.329 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.36 0.01446
GUESTROOM406_408 2798.25 3357.90 0.246 0.295 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.36 0.01446
GUESTROOM409_412 6985.11 8382.13 0.804 0.965 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.36 0.01446
GUESTROOM413 1083.62 1300.35 0.095 0.114 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 33.15 0.01446
GUESTROOM414 887.26 1064.72 0.078 0.093 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 34.40 0.01446
GUESTROOM415_418 6628.48 7954.18 0.763 0.916 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 32.27 0.01446
GUESTROOM419 1826.00 2191.20 0.210 0.252 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 32.53 0.01446
GUESTROOM420_423 6484.97 7781.96 0.747 0.896 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 11:15:00 32.27 0.01446
GUESTROOM424 1877.05 2252.46 0.216 0.259 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 11:30:00 32.53 0.01446
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
CORRIDORFLR1 18991.73 22790.07 1.574 1.889 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.90 0.01446
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
CORRIDORFLR2 3104.25 3725.10 0.257 0.308 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.94 0.01446
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
CORRIDORFLR3 1850.38 2220.46 0.153 0.184 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.68 0.01446
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446
CORRIDORFLR4 2896.96 3476.35 0.240 0.288 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01446
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB   34.40 0.01446


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1644.51 1973.41 0.047 0.236 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -10.60 0.00152
RESTROOMFLR1 32.25 38.70 0.001 0.001 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -10.60 0.00152
MEETINGROOMFLR1 571.16 685.40 0.016 0.126 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -10.60 0.00152
GUESTROOM101 0.00 0.00 0.000 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
GUESTROOM102 32.75 39.31 0.001 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -10.60 0.00152
GUESTROOM103 613.39 736.07 0.017 0.021 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -10.60 0.00152
GUESTROOM104 514.33 617.20 0.015 0.017 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.60 0.00152
GUESTROOM105 313.09 375.71 0.009 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -10.60 0.00152
EMPLOYEELOUNGEFLR1 285.31 342.37 0.008 0.051 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.60 0.00152
EXERCISECENTERFLR1 156.77 188.13 0.004 0.043 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -10.60 0.00152
FRONTOFFICEFLR1 1024.37 1229.25 0.029 0.056 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -10.60 0.00152
GUESTROOM201 231.34 277.61 0.006 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 -10.60 0.00152
GUESTROOM202_205 1227.66 1473.20 0.035 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -10.60 0.00152
GUESTROOM206_208 913.96 1096.75 0.026 0.043 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
GUESTROOM209_212 978.36 1174.03 0.028 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -10.60 0.00152
GUESTROOM213 680.74 816.89 0.019 0.023 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 11:00:00 -10.60 0.00152
GUESTROOM214 583.43 700.12 0.017 0.020 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -10.60 0.00152
GUESTROOM215_218 148.10 177.72 0.004 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -10.60 0.00152
GUESTROOM219 282.51 339.02 0.008 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -10.60 0.00152
GUESTROOM220_223 835.24 1002.29 0.024 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -10.60 0.00152
GUESTROOM224 490.29 588.35 0.014 0.017 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -10.60 0.00152
GUESTROOM301 307.42 368.90 0.008 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -10.60 0.00152
GUESTROOM302_305 572.07 686.49 0.015 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -10.60 0.00152
GUESTROOM306_308 455.16 546.19 0.012 0.043 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -10.60 0.00152
GUESTROOM309_312 1203.37 1444.05 0.034 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -10.60 0.00152
GUESTROOM313 441.36 529.63 0.012 0.014 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -10.60 0.00152
GUESTROOM314 691.91 830.29 0.020 0.024 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:15:00 -10.60 0.00152
GUESTROOM315_318 1248.24 1497.89 0.035 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -10.60 0.00152
GUESTROOM319 63.40 76.08 0.002 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -10.60 0.00152
GUESTROOM320_323 1061.81 1274.18 0.030 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -10.60 0.00152
GUESTROOM324 224.26 269.11 0.006 0.013 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -10.60 0.00152
GUESTROOM401 844.80 1013.76 0.024 0.029 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 21:45:00 -10.60 0.00152
GUESTROOM402_405 1413.59 1696.31 0.037 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 21:15:00 -10.60 0.00152
GUESTROOM406_408 1175.49 1410.58 0.031 0.043 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -10.60 0.00152
GUESTROOM409_412 2019.98 2423.97 0.057 0.069 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -10.60 0.00152
GUESTROOM413 730.14 876.16 0.019 0.023 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -10.60 0.00152
GUESTROOM414 597.12 716.55 0.016 0.019 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 20:00:00 -10.60 0.00152
GUESTROOM415_418 1947.37 2336.84 0.055 0.066 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -10.60 0.00152
GUESTROOM419 621.52 745.83 0.018 0.021 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 18:00:00 -10.60 0.00152
GUESTROOM420_423 1827.65 2193.18 0.052 0.062 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 18:30:00 -10.60 0.00152
GUESTROOM424 826.23 991.47 0.023 0.028 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 21:45:00 -10.60 0.00152
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
CORRIDORFLR1 29197.57 35037.09 0.826 0.991 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -10.60 0.00152
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
CORRIDORFLR2 1132.90 1359.48 0.032 0.039 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -10.60 0.00152
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
CORRIDORFLR3 1590.03 1908.04 0.045 0.054 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -10.60 0.00152
FRONTSTAIRSFLR3 50.25 60.30 0.001 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -10.60 0.00152
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB   -10.60 0.00152
CORRIDORFLR4 2656.28 3187.54 0.075 0.090 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -10.60 0.00152
FRONTSTAIRSFLR4 208.07 249.68 0.004 0.006 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -10.60 0.00152


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.38 0.38 0.06 0.06
SAC_FRONTLOUNGE 1.01 1.01 0.24 0.24
SAC_MEETINGROOM 0.45 0.45 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.78 0.78 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialEnthalpy 0.24 1.01 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 3267.75 6500.00 1644.00
RESTROOMFLR1 1210.50 6285.50 234.25
MEETINGROOMFLR1 1746.25 2625.25 341.25
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 1499.50 8660.50 1494.75
GUESTROOM104 785.25 8425.75 774.75
GUESTROOM105 98.00 8051.25 37.50
EMPLOYEELOUNGEFLR1 3189.00 2060.50 315.75
EXERCISECENTERFLR1 2008.50 2570.00 54.25
FRONTOFFICEFLR1 2283.25 5164.75 357.50
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 730.25 8079.25 584.75
GUESTROOM206_208 605.00 8056.00 451.25
GUESTROOM209_212 472.25 8248.50 410.25
GUESTROOM213 1488.75 8383.00 1457.00
GUESTROOM214 729.50 8051.00 627.00
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 4110.25 4196.50 742.00
GUESTROOM220_223 342.25 7913.50 144.25
GUESTROOM224 743.75 8002.75 629.75
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 742.50 8304.50 683.00
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 1310.25 8058.75 1189.50
GUESTROOM315_318 456.25 7866.75 164.25
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 562.25 8034.50 419.50
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 3266.50 7902.75 2797.75
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1989.25 7690.25 1320.25
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 1710.75 7525.75 909.00
GUESTROOM419 1652.75 7679.50 1078.00
GUESTROOM420_423 1780.75 7551.25 997.75
GUESTROOM424 2426.25 7734.75 1850.50
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7487.50 8759.00 6106.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 95.25 1079.50 95.25 1079.50
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.25 0.00 0.00 0.00
GUESTROOM103 8.25 42.75 8.25 42.75
GUESTROOM104 5.75 43.50 5.75 43.50
GUESTROOM105 0.00 52.50 0.00 52.50
EMPLOYEELOUNGEFLR1 264.50 1308.25 206.25 870.25
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.50 0.00 0.00 0.00
GUESTROOM202_205 2.25 35.75 2.25 35.75
GUESTROOM206_208 1.50 41.50 1.50 41.50
GUESTROOM209_212 1.25 34.75 1.25 34.75
GUESTROOM213 9.00 35.25 9.00 35.25
GUESTROOM214 4.50 36.25 4.50 36.25
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 2972.25 0.00 2972.25
GUESTROOM220_223 0.25 34.50 0.25 34.50
GUESTROOM224 5.75 36.50 5.75 36.50
GUESTROOM301 5.25 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.50 0.00 0.00 0.00
GUESTROOM309_312 5.00 34.75 5.00 34.75
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 9.00 35.25 9.00 35.25
GUESTROOM315_318 1.25 36.00 1.25 36.00
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 4.75 33.50 4.75 33.50
GUESTROOM324 0.25 0.00 0.00 0.00
GUESTROOM401 17.00 54.25 17.00 54.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.25 0.00 0.00 0.00
GUESTROOM409_412 8.00 41.25 8.00 41.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 8.25 37.00 8.25 37.00
GUESTROOM419 8.50 40.00 8.50 40.00
GUESTROOM420_423 9.00 36.50 9.00 36.50
GUESTROOM424 13.50 39.25 13.50 39.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 11.50 3464.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 432.75 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.25 24.50 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 4.50 0.00 0.00 0.00
CORRIDORFLR4 0.00 503.50 0.00 0.00
FRONTSTAIRSFLR4 10.75 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 314.00 5096.25 277.25 4092.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-14 08:44:16

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.383812
SAC_FRONTLOUNGE SUPPLY FAN 1.01
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.775121


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 319.72
CORRIDORFLR1 PTAC HEATING COIL 36836.09
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 512.05
102 PTAC HEATING COIL 997.40
103 PTAC HEATING COIL 1257.99
104 PTAC HEATING COIL 1139.08
105 PTAC HEATING COIL 997.33
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 319.65
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 319.72
CORRIDORFLR2 PTAC HEATING COIL 2839.58
201 PTAC HEATING COIL 997.40
202_205 PTAC HEATING COIL 3989.60
206_208 PTAC HEATING COIL 3161.90
209_212 PTAC HEATING COIL 3989.60
213 PTAC HEATING COIL 1338.82
214 PTAC HEATING COIL 1222.00
215_218 PTAC HEATING COIL 3989.32
219 PTAC HEATING COIL 997.33
220_223 PTAC HEATING COIL 3989.32
224 PTAC HEATING COIL 1110.24
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 319.65
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 319.72
CORRIDORFLR3 PTAC HEATING COIL 3388.17
301 PTAC HEATING COIL 997.40
302_305 PTAC HEATING COIL 3989.60
306_308 PTAC HEATING COIL 3161.90
309_312 PTAC HEATING COIL 3989.60
313 PTAC HEATING COIL 1014.98
314 PTAC HEATING COIL 1352.18
315_318 PTAC HEATING COIL 3989.32
319 PTAC HEATING COIL 997.33
320_323 PTAC HEATING COIL 3989.32
324 PTAC HEATING COIL 997.33
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 452.58
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 319.72
CORRIDORFLR4 PTAC HEATING COIL 4667.65
401 PTAC HEATING COIL 1535.68
402_405 PTAC HEATING COIL 3989.60
406_408 PTAC HEATING COIL 3161.90
409_412 PTAC HEATING COIL 4511.66
413 PTAC HEATING COIL 1361.52
414 PTAC HEATING COIL 1201.87
415_418 PTAC HEATING COIL 4424.39
419 PTAC HEATING COIL 1267.71
420_423 PTAC HEATING COIL 4280.72
424 PTAC HEATING COIL 1513.36
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 452.58


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.717081 0.383812 8165.09
SAC_FRONTLOUNGE COOLING COIL 0.680960 1.01 24579.22
SAC_MEETINGROOM COOLING COIL 0.676083 0.447236 11105.93
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.729395 0.775121 15809.22


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 1.01
RESTROOMFLR1 DIRECT AIR 0.069758
MEETINGROOMFLR1 DIRECT AIR 0.447236
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.570418
EXERCISECENTERFLR1 DIRECT AIR 0.134945
FRONTOFFICEFLR1 DIRECT AIR 0.383812


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.383812
SAC_FRONTLOUNGE MAIN BRANCH 1.01
SAC_MEETINGROOM MAIN BRANCH 0.447236
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.775121


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.383812
SAC_FRONTLOUNGE 1.01
SAC_MEETINGROOM 0.447236
SAC_EXC_EMPLGE_RESTRM 0.775121


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.383812 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 1.01 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.447236 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.775121 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.383812 0.383812 0.383812 0.383812 4106.85 8165.09 1.00
SAC_FRONTLOUNGE 1.01 1.01 1.01 1.01 17213.78 24579.22 1.00
SAC_MEETINGROOM 0.447236 0.447236 0.447236 0.447236 9217.85 11105.93 1.00
SAC_EXC_EMPLGE_RESTRM 0.775121 0.775121 0.775121 0.775121 6923.16 15809.22 0.174095


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 4106.85
SAC_FRONTLOUNGE HEATING COIL 17213.78
SAC_MEETINGROOM HEATING COIL 9217.85
SAC_EXC_EMPLGE_RESTRM HEATING COIL 6923.16


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.447236


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.49 -0.5
February 16.96 2.24
March 19.27 8.00
April 21.26 13.18
May 22.91 18.32
June 24.57 22.93
July 25.32 25.34
August 25.11 24.28
September 23.86 20.44
October 21.49 12.66
November 20.07 8.91
December 17.50 2.07
     
Annual Sum or Average 21.26 13.21
Minimum of Months 16.49 -0.5
Maximum of Months 25.32 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 -0.5
February 22.16 2.24
March 23.14 8.00
April 23.91 13.18
May 25.01 18.32
June 26.08 22.93
July 26.72 25.34
August 26.46 24.28
September 25.53 20.44
October 23.93 12.66
November 23.34 8.91
December 22.22 2.07
     
Annual Sum or Average 24.20 13.21
Minimum of Months 21.76 -0.5
Maximum of Months 26.72 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.66 -0.5
February 16.12 2.24
March 18.44 8.00
April 20.49 13.18
May 22.19 18.32
June 23.85 22.93
July 24.64 25.34
August 24.39 24.28
September 23.16 20.44
October 20.70 12.66
November 19.24 8.91
December 16.69 2.07
     
Annual Sum or Average 20.49 13.21
Minimum of Months 15.66 -0.5
Maximum of Months 24.64 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.13 -0.5
February 21.23 2.24
March 21.60 8.00
April 22.35 13.18
May 23.08 18.32
June 23.65 22.93
July 23.85 25.34
August 23.80 24.28
September 23.46 20.44
October 22.23 12.66
November 21.63 8.91
December 21.28 2.07
     
Annual Sum or Average 22.45 13.21
Minimum of Months 21.13 -0.5
Maximum of Months 23.85 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.81 -0.5
February 21.99 2.24
March 22.48 8.00
April 23.02 13.18
May 23.39 18.32
June 23.64 22.93
July 23.76 25.34
August 23.72 24.28
September 23.57 20.44
October 23.01 12.66
November 22.63 8.91
December 22.03 2.07
     
Annual Sum or Average 22.93 13.21
Minimum of Months 21.81 -0.5
Maximum of Months 23.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.41 -0.5
February 21.69 2.24
March 22.53 8.00
April 23.39 13.18
May 23.69 18.32
June 23.86 22.93
July 23.89 25.34
August 23.88 24.28
September 23.82 20.44
October 23.33 12.66
November 22.78 8.91
December 21.79 2.07
     
Annual Sum or Average 23.01 13.21
Minimum of Months 21.41 -0.5
Maximum of Months 23.89 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.95 -0.5
February 24.22 2.24
March 25.05 8.00
April 25.84 13.18
May 26.38 18.32
June 26.83 22.93
July 27.04 25.34
August 26.97 24.28
September 26.63 20.44
October 25.85 12.66
November 25.27 8.91
December 24.32 2.07
     
Annual Sum or Average 25.70 13.21
Minimum of Months 23.95 -0.5
Maximum of Months 27.04 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.21 -0.5
February 19.63 2.24
March 20.81 8.00
April 22.12 13.18
May 22.82 18.32
June 23.26 22.93
July 23.33 25.34
August 23.31 24.28
September 23.15 20.44
October 22.01 12.66
November 21.11 8.91
December 19.74 2.07
     
Annual Sum or Average 21.72 13.21
Minimum of Months 19.21 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.05 -0.5
February 19.40 2.24
March 20.46 8.00
April 21.79 13.18
May 22.60 18.32
June 23.18 22.93
July 23.32 25.34
August 23.28 24.28
September 23.01 20.44
October 21.69 12.66
November 20.73 8.91
December 19.52 2.07
     
Annual Sum or Average 21.51 13.21
Minimum of Months 19.05 -0.5
Maximum of Months 23.32 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.62 -0.5
February 20.78 2.24
March 21.13 8.00
April 21.52 13.18
May 21.69 18.32
June 21.75 22.93
July 21.76 25.34
August 21.75 24.28
September 21.74 20.44
October 21.50 12.66
November 21.28 8.91
December 20.81 2.07
     
Annual Sum or Average 21.36 13.21
Minimum of Months 20.62 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.79 -0.5
February 21.00 2.24
March 21.38 8.00
April 21.66 13.18
May 21.73 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.63 12.66
November 21.46 8.91
December 20.96 2.07
     
Annual Sum or Average 21.47 13.21
Minimum of Months 20.79 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.23 -0.5
February 21.41 2.24
March 21.65 8.00
April 21.74 13.18
May 21.75 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.73 12.66
November 21.69 8.91
December 21.34 2.07
     
Annual Sum or Average 21.63 13.21
Minimum of Months 21.23 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.41 -0.5
February 22.51 2.24
March 22.62 8.00
April 22.79 13.18
May 22.72 18.32
June 22.51 22.93
July 22.39 25.34
August 22.46 24.28
September 22.69 20.44
October 22.75 12.66
November 22.70 8.91
December 22.45 2.07
     
Annual Sum or Average 22.58 13.21
Minimum of Months 22.39 -0.5
Maximum of Months 22.79 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 50.33 -0.5
February 50.56 2.24
March 51.34 8.00
April 52.06 13.18
May 52.69 18.32
June 53.28 22.93
July 53.55 25.34
August 53.48 24.28
September 52.96 20.44
October 52.11 12.66
November 51.53 8.91
December 50.65 2.07
     
Annual Sum or Average 52.05 13.21
Minimum of Months 50.33 -0.5
Maximum of Months 53.55 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 68.01 -0.5
February 68.12 2.24
March 69.14 8.00
April 70.08 13.18
May 70.98 18.32
June 71.72 22.93
July 72.16 25.34
August 72.15 24.28
September 71.38 20.44
October 70.29 12.66
November 69.59 8.91
December 68.48 2.07
     
Annual Sum or Average 70.19 13.21
Minimum of Months 68.01 -0.5
Maximum of Months 72.16 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.67 -0.5
February 22.86 2.24
March 23.22 8.00
April 23.60 13.18
May 23.78 18.32
June 23.88 22.93
July 23.89 25.34
August 23.89 24.28
September 23.87 20.44
October 23.57 12.66
November 23.33 8.91
December 22.82 2.07
     
Annual Sum or Average 23.45 13.21
Minimum of Months 22.67 -0.5
Maximum of Months 23.89 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 -0.5
February 22.20 2.24
March 22.96 8.00
April 23.65 13.18
May 23.83 18.32
June 23.89 22.93
July 23.89 25.34
August 23.89 24.28
September 23.89 20.44
October 23.57 12.66
November 23.19 8.91
December 22.22 2.07
     
Annual Sum or Average 23.26 13.21
Minimum of Months 21.84 -0.5
Maximum of Months 23.89 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.41 -0.5
February 16.01 2.24
March 18.65 8.00
April 21.05 13.18
May 23.13 18.32
June 25.16 22.93
July 26.03 25.34
August 25.72 24.28
September 24.08 20.44
October 21.19 12.66
November 19.53 8.91
December 16.62 2.07
     
Annual Sum or Average 21.07 13.21
Minimum of Months 15.41 -0.5
Maximum of Months 26.03 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.08 -0.5
February 19.54 2.24
March 21.16 8.00
April 22.67 13.18
May 23.82 18.32
June 24.95 22.93
July 25.42 25.34
August 25.25 24.28
September 24.37 20.44
October 22.74 12.66
November 21.68 8.91
December 19.83 2.07
     
Annual Sum or Average 22.56 13.21
Minimum of Months 19.08 -0.5
Maximum of Months 25.42 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.43 -0.5
February 16.10 2.24
March 19.02 8.00
April 21.57 13.18
May 23.55 18.32
June 25.54 22.93
July 26.43 25.34
August 26.20 24.28
September 24.62 20.44
October 21.75 12.66
November 19.97 8.91
December 16.70 2.07
     
Annual Sum or Average 21.44 13.21
Minimum of Months 15.43 -0.5
Maximum of Months 26.43 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.30 -0.5
February 21.63 2.24
March 22.60 8.00
April 23.63 13.18
May 23.85 18.32
June 23.93 22.93
July 24.04 25.34
August 23.98 24.28
September 23.92 20.44
October 23.48 12.66
November 22.91 8.91
December 21.73 2.07
     
Annual Sum or Average 23.09 13.21
Minimum of Months 21.30 -0.5
Maximum of Months 24.04 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.13 -0.5
February 14.80 2.24
March 17.71 8.00
April 20.41 13.18
May 22.49 18.32
June 24.51 22.93
July 25.44 25.34
August 25.17 24.28
September 23.60 20.44
October 20.54 12.66
November 18.64 8.91
December 15.41 2.07
     
Annual Sum or Average 20.27 13.21
Minimum of Months 14.13 -0.5
Maximum of Months 25.44 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.93 -0.5
February 19.11 2.24
March 19.93 8.00
April 21.79 13.18
May 22.77 18.32
June 23.28 22.93
July 23.33 25.34
August 23.33 24.28
September 23.16 20.44
October 21.46 12.66
November 20.07 8.91
December 19.24 2.07
     
Annual Sum or Average 21.38 13.21
Minimum of Months 18.93 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.75 -0.5
February 20.96 2.24
March 21.33 8.00
April 21.68 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.62 12.66
November 21.43 8.91
December 20.95 2.07
     
Annual Sum or Average 21.46 13.21
Minimum of Months 20.75 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 -0.5
February 21.01 2.24
March 21.39 8.00
April 21.70 13.18
May 21.75 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.65 12.66
November 21.49 8.91
December 21.00 2.07
     
Annual Sum or Average 21.49 13.21
Minimum of Months 20.80 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 -0.5
February 21.03 2.24
March 21.41 8.00
April 21.69 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.66 12.66
November 21.52 8.91
December 21.02 2.07
     
Annual Sum or Average 21.49 13.21
Minimum of Months 20.81 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.59 -0.5
February 20.76 2.24
March 21.14 8.00
April 21.58 13.18
May 21.72 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.53 12.66
November 21.28 8.91
December 20.79 2.07
     
Annual Sum or Average 21.37 13.21
Minimum of Months 20.59 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 -0.5
February 21.05 2.24
March 21.46 8.00
April 21.72 13.18
May 21.75 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.68 12.66
November 21.54 8.91
December 21.00 2.07
     
Annual Sum or Average 21.50 13.21
Minimum of Months 20.81 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.55 -0.5
February 22.82 2.24
March 23.21 8.00
April 23.33 13.18
May 23.33 18.32
June 23.33 22.93
July 23.33 25.34
August 23.33 24.28
September 23.33 20.44
October 23.31 12.66
November 23.27 8.91
December 22.70 2.07
     
Annual Sum or Average 23.16 13.21
Minimum of Months 22.55 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 29.69 -0.5
February 29.95 2.24
March 31.10 8.00
April 32.26 13.18
May 33.03 18.32
June 33.69 22.93
July 34.02 25.34
August 33.93 24.28
September 33.35 20.44
October 32.25 12.66
November 31.46 8.91
December 30.18 2.07
     
Annual Sum or Average 32.09 13.21
Minimum of Months 29.69 -0.5
Maximum of Months 34.02 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 -0.5
February 21.81 2.24
March 21.97 8.00
April 22.30 13.18
May 22.72 18.32
June 23.11 22.93
July 23.45 25.34
August 23.31 24.28
September 22.92 20.44
October 22.28 12.66
November 22.03 8.91
December 21.82 2.07
     
Annual Sum or Average 22.46 13.21
Minimum of Months 21.77 -0.5
Maximum of Months 23.45 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.99 -0.5
February 21.23 2.24
March 21.58 8.00
April 21.74 13.18
May 21.75 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.71 12.66
November 21.63 8.91
December 21.14 2.07
     
Annual Sum or Average 21.57 13.21
Minimum of Months 20.99 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 -0.5
February 21.04 2.24
March 21.46 8.00
April 21.73 13.18
May 21.75 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.68 12.66
November 21.53 8.91
December 20.99 2.07
     
Annual Sum or Average 21.50 13.21
Minimum of Months 20.80 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.62 -0.5
February 18.29 2.24
March 20.43 8.00
April 22.51 13.18
May 24.00 18.32
June 25.49 22.93
July 26.07 25.34
August 25.84 24.28
September 24.66 20.44
October 22.48 12.66
November 21.04 8.91
December 18.60 2.07
     
Annual Sum or Average 22.27 13.21
Minimum of Months 17.62 -0.5
Maximum of Months 26.07 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.57 -0.5
February 14.48 2.24
March 17.90 8.00
April 21.13 13.18
May 23.73 18.32
June 26.28 22.93
July 27.36 25.34
August 27.01 24.28
September 24.83 20.44
October 21.17 12.66
November 18.97 8.91
December 15.15 2.07
     
Annual Sum or Average 21.00 13.21
Minimum of Months 13.57 -0.5
Maximum of Months 27.36 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.45 -0.5
February 15.21 2.24
March 18.37 8.00
April 21.29 13.18
May 23.53 18.32
June 25.74 22.93
July 26.69 25.34
August 26.45 24.28
September 24.68 20.44
October 21.40 12.66
November 19.32 8.91
December 15.80 2.07
     
Annual Sum or Average 21.11 13.21
Minimum of Months 14.45 -0.5
Maximum of Months 26.69 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -0.5
February 21.19 2.24
March 21.66 8.00
April 22.92 13.18
May 23.56 18.32
June 23.87 22.93
July 23.90 25.34
August 23.89 24.28
September 23.81 20.44
October 22.72 12.66
November 21.72 8.91
December 21.28 2.07
     
Annual Sum or Average 22.64 13.21
Minimum of Months 21.12 -0.5
Maximum of Months 23.90 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.82 -0.5
February 13.60 2.24
March 16.78 8.00
April 19.95 13.18
May 22.42 18.32
June 24.77 22.93
July 25.79 25.34
August 25.49 24.28
September 23.68 20.44
October 20.00 12.66
November 17.68 8.91
December 14.18 2.07
     
Annual Sum or Average 19.79 13.21
Minimum of Months 12.82 -0.5
Maximum of Months 25.79 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -0.5
February 18.99 2.24
March 19.53 8.00
April 21.27 13.18
May 22.53 18.32
June 23.25 22.93
July 23.33 25.34
August 23.31 24.28
September 23.04 20.44
October 20.93 12.66
November 19.48 8.91
December 19.07 2.07
     
Annual Sum or Average 21.15 13.21
Minimum of Months 18.89 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.91 -0.5
February 19.06 2.24
March 19.84 8.00
April 21.71 13.18
May 22.74 18.32
June 23.29 22.93
July 23.33 25.34
August 23.33 24.28
September 23.16 20.44
October 21.29 12.66
November 19.82 8.91
December 19.16 2.07
     
Annual Sum or Average 21.31 13.21
Minimum of Months 18.91 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.92 -0.5
February 19.11 2.24
March 20.00 8.00
April 21.85 13.18
May 22.78 18.32
June 23.29 22.93
July 23.33 25.34
August 23.33 24.28
September 23.16 20.44
October 21.42 12.66
November 20.01 8.91
December 19.21 2.07
     
Annual Sum or Average 21.38 13.21
Minimum of Months 18.92 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.73 -0.5
February 20.95 2.24
March 21.32 8.00
April 21.66 13.18
May 21.74 18.32
June 21.75 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.61 12.66
November 21.43 8.91
December 20.94 2.07
     
Annual Sum or Average 21.45 13.21
Minimum of Months 20.73 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.91 -0.5
February 19.04 2.24
March 19.77 8.00
April 21.58 13.18
May 22.66 18.32
June 23.28 22.93
July 23.33 25.34
August 23.33 24.28
September 23.13 20.44
October 21.32 12.66
November 19.88 8.91
December 19.17 2.07
     
Annual Sum or Average 21.29 13.21
Minimum of Months 18.91 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.65 -0.5
February 20.86 2.24
March 21.30 8.00
April 21.67 13.18
May 21.73 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.61 12.66
November 21.38 8.91
December 20.83 2.07
     
Annual Sum or Average 21.42 13.21
Minimum of Months 20.65 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.99 -0.5
February 21.25 2.24
March 21.59 8.00
April 21.75 13.18
May 21.75 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.72 12.66
November 21.64 8.91
December 21.14 2.07
     
Annual Sum or Average 21.57 13.21
Minimum of Months 20.99 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -0.5
February 21.56 2.24
March 23.02 8.00
April 24.58 13.18
May 25.52 18.32
June 26.29 22.93
July 26.56 25.34
August 26.44 24.28
September 25.87 20.44
October 24.42 12.66
November 23.33 8.91
December 21.72 2.07
     
Annual Sum or Average 24.22 13.21
Minimum of Months 21.12 -0.5
Maximum of Months 26.56 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.88 -0.5
February 20.59 2.24
March 22.00 8.00
April 23.10 13.18
May 23.27 18.32
June 23.33 22.93
July 23.33 25.34
August 23.33 24.28
September 23.33 20.44
October 22.89 12.66
November 22.20 8.91
December 20.49 2.07
     
Annual Sum or Average 22.32 13.21
Minimum of Months 19.88 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.84 -0.5
February 21.10 2.24
March 21.49 8.00
April 21.72 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.68 12.66
November 21.53 8.91
December 21.01 2.07
     
Annual Sum or Average 21.51 13.21
Minimum of Months 20.84 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.96 -0.5
February 19.24 2.24
March 20.40 8.00
April 22.20 13.18
May 22.93 18.32
June 23.31 22.93
July 23.33 25.34
August 23.33 24.28
September 23.22 20.44
October 21.89 12.66
November 20.60 8.91
December 19.36 2.07
     
Annual Sum or Average 21.58 13.21
Minimum of Months 18.96 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.27 -0.5
February 17.05 2.24
March 19.53 8.00
April 22.13 13.18
May 23.97 18.32
June 25.73 22.93
July 26.39 25.34
August 26.13 24.28
September 24.72 20.44
October 21.99 12.66
November 20.13 8.91
December 17.36 2.07
     
Annual Sum or Average 21.81 13.21
Minimum of Months 16.27 -0.5
Maximum of Months 26.39 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.35 -0.5
February 13.42 2.24
March 17.15 8.00
April 20.80 13.18
May 23.73 18.32
June 26.56 22.93
July 27.73 25.34
August 27.36 24.28
September 24.92 20.44
October 20.76 12.66
November 18.21 8.91
December 14.06 2.07
     
Annual Sum or Average 20.62 13.21
Minimum of Months 12.35 -0.5
Maximum of Months 27.73 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.10 -0.5
February 14.00 2.24
March 17.45 8.00
April 20.83 13.18
May 23.49 18.32
June 25.99 22.93
July 27.06 25.34
August 26.74 24.28
September 24.69 20.44
October 20.75 12.66
November 18.26 8.91
December 14.53 2.07
     
Annual Sum or Average 20.61 13.21
Minimum of Months 13.10 -0.5
Maximum of Months 27.06 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -0.5
February 21.19 2.24
March 21.59 8.00
April 22.45 13.18
May 23.23 18.32
June 23.83 22.93
July 24.07 25.34
August 23.97 24.28
September 23.57 20.44
October 22.27 12.66
November 21.48 8.91
December 21.23 2.07
     
Annual Sum or Average 22.51 13.21
Minimum of Months 21.11 -0.5
Maximum of Months 24.07 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.84 -0.5
February 12.76 2.24
March 16.17 8.00
April 19.61 13.18
May 22.40 18.32
June 24.97 22.93
July 26.10 25.34
August 25.72 24.28
September 23.66 20.44
October 19.47 12.66
November 16.90 8.91
December 13.25 2.07
     
Annual Sum or Average 19.44 13.21
Minimum of Months 11.84 -0.5
Maximum of Months 26.10 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -0.5
February 20.61 2.24
March 20.92 8.00
April 21.48 13.18
May 21.69 18.32
June 21.76 22.93
July 21.77 25.34
August 21.76 24.28
September 21.74 20.44
October 21.35 12.66
November 20.97 8.91
December 20.63 2.07
     
Annual Sum or Average 21.27 13.21
Minimum of Months 20.48 -0.5
Maximum of Months 21.77 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -0.5
February 19.05 2.24
March 19.72 8.00
April 21.20 13.18
May 22.36 18.32
June 23.15 22.93
July 23.32 25.34
August 23.27 24.28
September 22.88 20.44
October 20.79 12.66
November 19.52 8.91
December 19.09 2.07
     
Annual Sum or Average 21.11 13.21
Minimum of Months 18.89 -0.5
Maximum of Months 23.32 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -0.5
February 19.07 2.24
March 19.80 8.00
April 21.28 13.18
May 22.38 18.32
June 23.15 22.93
July 23.32 25.34
August 23.27 24.28
September 22.88 20.44
October 20.86 12.66
November 19.61 8.91
December 19.11 2.07
     
Annual Sum or Average 21.14 13.21
Minimum of Months 18.90 -0.5
Maximum of Months 23.32 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.64 -0.5
February 20.91 2.24
March 21.34 8.00
April 21.68 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.61 12.66
November 21.42 8.91
December 20.86 2.07
     
Annual Sum or Average 21.44 13.21
Minimum of Months 20.64 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -0.5
February 19.04 2.24
March 19.70 8.00
April 21.20 13.18
May 22.34 18.32
June 23.16 22.93
July 23.32 25.34
August 23.28 24.28
September 22.90 20.44
October 20.89 12.66
November 19.60 8.91
December 19.11 2.07
     
Annual Sum or Average 21.13 13.21
Minimum of Months 18.89 -0.5
Maximum of Months 23.32 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.93 -0.5
February 19.13 2.24
March 20.04 8.00
April 21.67 13.18
May 22.58 18.32
June 23.22 22.93
July 23.33 25.34
August 23.30 24.28
September 23.03 20.44
October 21.34 12.66
November 20.01 8.91
December 19.22 2.07
     
Annual Sum or Average 21.33 13.21
Minimum of Months 18.93 -0.5
Maximum of Months 23.33 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.77 -0.5
February 21.11 2.24
March 21.54 8.00
April 21.74 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.69 12.66
November 21.56 8.91
December 20.95 2.07
     
Annual Sum or Average 21.51 13.21
Minimum of Months 20.77 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.88 -0.5
February 19.45 2.24
March 21.03 8.00
April 22.68 13.18
May 23.87 18.32
June 24.90 22.93
July 25.28 25.34
August 25.05 24.28
September 24.23 20.44
October 22.38 12.66
November 21.14 8.91
December 19.47 2.07
     
Annual Sum or Average 22.38 13.21
Minimum of Months 18.88 -0.5
Maximum of Months 25.28 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.72 -0.5
February 21.04 2.24
March 21.49 8.00
April 21.73 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.68 12.66
November 21.52 8.91
December 20.92 2.07
     
Annual Sum or Average 21.49 13.21
Minimum of Months 20.72 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.74 -0.5
February 21.08 2.24
March 21.52 8.00
April 21.74 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.75 20.44
October 21.68 12.66
November 21.53 8.91
December 20.93 2.07
     
Annual Sum or Average 21.50 13.21
Minimum of Months 20.74 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.57 -0.5
February 20.82 2.24
March 21.32 8.00
April 21.70 13.18
May 21.74 18.32
June 21.76 22.93
July 21.76 25.34
August 21.76 24.28
September 21.76 20.44
October 21.61 12.66
November 21.36 8.91
December 20.77 2.07
     
Annual Sum or Average 21.41 13.21
Minimum of Months 20.57 -0.5
Maximum of Months 21.76 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.68 -0.5
February 16.60 2.24
March 19.23 8.00
April 21.93 13.18
May 23.95 18.32
June 25.83 22.93
July 26.55 25.34
August 26.21 24.28
September 24.64 20.44
October 21.63 12.66
November 19.66 8.91
December 16.77 2.07
     
Annual Sum or Average 21.58 13.21
Minimum of Months 15.68 -0.5
Maximum of Months 26.55 25.34



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2015-09-14 08:44:16

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.55 -0.5
February 12.76 2.24
March 16.61 8.00
April 20.50 13.18
May 23.70 18.32
June 26.69 22.93
July 27.95 25.34
August 27.51 24.28
September 24.85 20.44
October 20.27 12.66
November 17.53 8.91
December 13.22 2.07
     
Annual Sum or Average 20.30 13.21
Minimum of Months 11.55 -0.5
Maximum of Months 27.95 25.34



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:16

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.189633E+12 157994.383 18-JAN-07:15 20847.837 39740.848 9201.505 83880.554 127.526 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.158991E+12 149800.599 06-FEB-07:15 20847.837 39740.848 9197.885 79860.500 145.416 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.154234E+12 130327.442 19-MAR-06:15 20847.837 39740.848 9180.631 56143.428 218.586 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.148907E+12 102096.289 17-APR-06:15 20847.837 39740.848 9180.631 30438.258 1880.602 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.170250E+12 106072.717 30-MAY-19:30 27551.975 28549.175 9247.792 0.000 36527.662 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.181891E+12 117461.999 30-JUN-07:00 25182.171 43578.554 9699.799 0.000 38993.362 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.200253E+12 117726.785 21-JUL-07:00 25182.171 43578.554 9699.799 0.000 39258.148 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.194726E+12 113894.530 18-AUG-07:00 25182.171 43578.554 9699.799 0.000 35425.893 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.174483E+12 111584.254 03-SEP-07:00 25182.171 43578.554 9699.799 0.000 33115.617 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.155630E+12 107124.293 31-OCT-06:15 20847.837 39740.848 9180.631 31833.489 1325.376 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.147664E+12 109880.590 23-NOV-07:15 20847.837 39740.848 9180.631 39339.786 763.375 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.180298E+12 159124.247 25-DEC-07:15 17938.631 34285.948 9213.792 93393.002 96.761 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.205696E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.147664E+12 102096.289   17938.631 28549.175 9180.631 0.000 96.761 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.200253E+12 159124.247   27551.975 43578.554 9699.799 93393.002 39258.148 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-14 08:44:16

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.111454E+12 108079.729 14-JAN-09:15 0.000 40096.028 0.000 67983.701 67983.701 67983.701 0.000
February 0.971298E+11 109333.139 11-FEB-09:15 847.538 40096.028 0.000 68389.572 68389.572 68389.572 847.538
March 0.974503E+11 106250.434 17-MAR-08:15 0.000 40096.028 0.000 66154.406 66154.406 66154.406 0.000
April 0.875492E+11 92433.252 14-APR-08:15 0.000 40096.028 0.000 52337.224 52337.224 52337.224 0.000
May 0.860842E+11 91681.140 13-MAY-08:15 0.000 40096.028 0.000 51585.112 51585.112 51585.112 0.000
June 0.796464E+11 85331.586 03-JUN-08:15 0.000 40096.028 0.000 45235.558 45235.558 45235.558 0.000
July 0.798761E+11 83370.933 01-JUL-08:15 0.000 40096.028 0.000 43274.905 43274.905 43274.905 0.000
August 0.792947E+11 82321.202 26-AUG-08:00 0.000 40096.028 0.000 42225.174 42225.174 42225.174 0.000
September 0.780306E+11 83721.999 29-SEP-08:15 0.000 40096.028 0.000 43625.971 43625.971 43625.971 0.000
October 0.849786E+11 85445.524 27-OCT-09:30 1536.880 40096.028 0.000 43812.615 43812.615 43812.615 1536.880
November 0.878948E+11 91618.145 04-NOV-08:15 0.000 40096.028 0.000 51522.117 51522.117 51522.117 0.000
December 0.105118E+12 106848.015 25-DEC-12:30 18019.793 40096.028 0.000 48732.193 48732.193 48732.193 18019.793
                     
Annual Sum or Average 0.107451E+13         0.000        
Minimum of Months 0.780306E+11 82321.202   0.000 40096.028 0.000 42225.174 42225.174 42225.174 0.000
Maximum of Months 0.111454E+12 109333.139   18019.793 40096.028 0.000 68389.572 68389.572 68389.572 18019.793