Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:43
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Simulation Timestamp: 2015-09-14 08:44:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3131.47 | 780.22 | 840.64 |
Net Site Energy | 3131.47 | 780.22 | 840.64 |
Total Source Energy | 7679.16 | 1913.29 | 2061.47 |
Net Source Energy | 7679.16 | 1913.29 | 2061.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 164.13 | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 350.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 296.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 597.85 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2056.96 | 1074.51 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 164.13 | 55.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 350.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 296.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 597.85 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 217.73 | 175.30 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 552.19 | 288.45 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 202.08 | 162.70 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 512.50 | 267.72 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2056.96 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2056.96 | 100.00 |
Total On-Site and Utility Electric Sources | 2056.96 | 100.00 |
Total Electricity End Uses | 2056.96 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 277.25 |
Time Setpoint Not Met During Occupied Cooling | 4092.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6106.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:43 |
RunPeriod | Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
Weather File | Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
Latitude [deg] | 39.17 |
Longitude [deg] | -76.7 |
Elevation [m] | 45.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00 | -10.60 | Wetbulb [C] | 3.90 | 290.00 |
BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 10.40 | 23.90 | Wetbulb [C] | 4.60 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 8.38 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 175.82 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8165.09 | 5855.03 | 2310.05 | 0.72 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 24579.22 | 16737.47 | 7841.75 | 0.68 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11105.93 | 7508.53 | 3597.40 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15809.22 | 11531.16 | 4278.06 | 0.73 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7867.0 | 3.30 | 11.26 | 11.93 | 11.28 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 23794.6 | 3.05 | 10.40 | 11.04 | 10.63 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10758.3 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15207.3 | 3.28 | 11.18 | 11.85 | 11.17 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.72 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 36836.09 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 512.05 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 997.40 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1257.99 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1139.08 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 997.33 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.65 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.72 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2839.58 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 997.40 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3989.60 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3161.90 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3989.60 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1338.82 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1222.00 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3989.32 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 997.33 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3989.32 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1110.24 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.65 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.72 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 3388.17 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 997.40 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3989.60 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3161.90 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3989.60 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1014.98 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1352.18 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3989.32 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 997.33 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3989.32 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 997.33 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 452.58 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.72 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 4667.65 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1535.68 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3989.60 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 3161.90 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 4511.66 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1361.52 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1201.87 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 4424.39 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1267.71 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 4280.72 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1513.36 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 452.58 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4106.85 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 17213.78 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 9217.85 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 6923.16 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.38 | 445.54 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.01 | 1150.94 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 519.17 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.78 | 883.72 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10149.68 | 12179.61 | 0.841 | 1.010 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.94 | 0.01446 |
RESTROOMFLR1 | 702.03 | 842.44 | 0.058 | 0.070 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.90 | 0.01446 |
MEETINGROOMFLR1 | 4494.25 | 5393.10 | 0.373 | 0.447 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
GUESTROOM101 | 563.12 | 675.75 | 0.049 | 0.059 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM102 | 428.31 | 513.97 | 0.038 | 0.045 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM103 | 1540.34 | 1848.41 | 0.177 | 0.213 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM104 | 1415.48 | 1698.57 | 0.163 | 0.196 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM105 | 1834.70 | 2201.64 | 0.211 | 0.254 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.23 | 0.01446 |
EMPLOYEELOUNGEFLR1 | 5734.29 | 6881.14 | 0.475 | 0.570 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
EXERCISECENTERFLR1 | 1357.34 | 1628.81 | 0.112 | 0.135 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.68 | 0.01446 |
FRONTOFFICEFLR1 | 3861.91 | 4634.29 | 0.320 | 0.384 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM201 | 912.67 | 1095.21 | 0.080 | 0.096 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
GUESTROOM202_205 | 6067.09 | 7280.51 | 0.699 | 0.838 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM206_208 | 4959.64 | 5951.57 | 0.571 | 0.685 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
GUESTROOM209_212 | 5670.40 | 6804.48 | 0.653 | 0.784 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
GUESTROOM213 | 1663.33 | 1996.00 | 0.192 | 0.230 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM214 | 1654.85 | 1985.82 | 0.191 | 0.229 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM215_218 | 8848.25 | 10617.89 | 0.776 | 0.932 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.23 | 0.01446 |
GUESTROOM219 | 5765.35 | 6918.42 | 0.664 | 0.797 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM220_223 | 5482.65 | 6579.18 | 0.631 | 0.758 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM224 | 1651.73 | 1982.07 | 0.190 | 0.228 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM301 | 786.33 | 943.60 | 0.069 | 0.083 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.94 | 0.01446 |
GUESTROOM302_305 | 2092.86 | 2511.44 | 0.184 | 0.220 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM306_308 | 1881.09 | 2257.31 | 0.165 | 0.198 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
GUESTROOM309_312 | 5695.96 | 6835.15 | 0.656 | 0.787 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM313 | 725.70 | 870.84 | 0.064 | 0.076 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 32.42 | 0.01446 |
GUESTROOM314 | 1589.27 | 1907.12 | 0.183 | 0.220 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 32.01 | 0.01446 |
GUESTROOM315_318 | 6182.26 | 7418.71 | 0.712 | 0.854 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM319 | 902.68 | 1083.22 | 0.079 | 0.095 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM320_323 | 5326.79 | 6392.15 | 0.613 | 0.736 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM324 | 592.35 | 710.82 | 0.052 | 0.062 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 31.62 | 0.01446 |
GUESTROOM401 | 2156.55 | 2587.86 | 0.248 | 0.298 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.36 | 0.01446 |
GUESTROOM402_405 | 3120.95 | 3745.14 | 0.274 | 0.329 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.36 | 0.01446 |
GUESTROOM406_408 | 2798.25 | 3357.90 | 0.246 | 0.295 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.36 | 0.01446 |
GUESTROOM409_412 | 6985.11 | 8382.13 | 0.804 | 0.965 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.36 | 0.01446 |
GUESTROOM413 | 1083.62 | 1300.35 | 0.095 | 0.114 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 33.15 | 0.01446 |
GUESTROOM414 | 887.26 | 1064.72 | 0.078 | 0.093 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 34.40 | 0.01446 |
GUESTROOM415_418 | 6628.48 | 7954.18 | 0.763 | 0.916 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 32.27 | 0.01446 |
GUESTROOM419 | 1826.00 | 2191.20 | 0.210 | 0.252 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 32.53 | 0.01446 |
GUESTROOM420_423 | 6484.97 | 7781.96 | 0.747 | 0.896 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 32.27 | 0.01446 |
GUESTROOM424 | 1877.05 | 2252.46 | 0.216 | 0.259 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 32.53 | 0.01446 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
CORRIDORFLR1 | 18991.73 | 22790.07 | 1.574 | 1.889 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.90 | 0.01446 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
CORRIDORFLR2 | 3104.25 | 3725.10 | 0.257 | 0.308 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 32.94 | 0.01446 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
CORRIDORFLR3 | 1850.38 | 2220.46 | 0.153 | 0.184 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.68 | 0.01446 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 | |
CORRIDORFLR4 | 2896.96 | 3476.35 | 0.240 | 0.288 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01446 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01446 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1644.51 | 1973.41 | 0.047 | 0.236 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -10.60 | 0.00152 |
RESTROOMFLR1 | 32.25 | 38.70 | 0.001 | 0.001 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -10.60 | 0.00152 |
MEETINGROOMFLR1 | 571.16 | 685.40 | 0.016 | 0.126 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -10.60 | 0.00152 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
GUESTROOM102 | 32.75 | 39.31 | 0.001 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -10.60 | 0.00152 |
GUESTROOM103 | 613.39 | 736.07 | 0.017 | 0.021 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -10.60 | 0.00152 |
GUESTROOM104 | 514.33 | 617.20 | 0.015 | 0.017 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.60 | 0.00152 |
GUESTROOM105 | 313.09 | 375.71 | 0.009 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -10.60 | 0.00152 |
EMPLOYEELOUNGEFLR1 | 285.31 | 342.37 | 0.008 | 0.051 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.60 | 0.00152 |
EXERCISECENTERFLR1 | 156.77 | 188.13 | 0.004 | 0.043 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -10.60 | 0.00152 |
FRONTOFFICEFLR1 | 1024.37 | 1229.25 | 0.029 | 0.056 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -10.60 | 0.00152 |
GUESTROOM201 | 231.34 | 277.61 | 0.006 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 11:15:00 | -10.60 | 0.00152 |
GUESTROOM202_205 | 1227.66 | 1473.20 | 0.035 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -10.60 | 0.00152 |
GUESTROOM206_208 | 913.96 | 1096.75 | 0.026 | 0.043 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
GUESTROOM209_212 | 978.36 | 1174.03 | 0.028 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -10.60 | 0.00152 |
GUESTROOM213 | 680.74 | 816.89 | 0.019 | 0.023 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -10.60 | 0.00152 |
GUESTROOM214 | 583.43 | 700.12 | 0.017 | 0.020 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -10.60 | 0.00152 |
GUESTROOM215_218 | 148.10 | 177.72 | 0.004 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -10.60 | 0.00152 |
GUESTROOM219 | 282.51 | 339.02 | 0.008 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -10.60 | 0.00152 |
GUESTROOM220_223 | 835.24 | 1002.29 | 0.024 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -10.60 | 0.00152 |
GUESTROOM224 | 490.29 | 588.35 | 0.014 | 0.017 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -10.60 | 0.00152 |
GUESTROOM301 | 307.42 | 368.90 | 0.008 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -10.60 | 0.00152 |
GUESTROOM302_305 | 572.07 | 686.49 | 0.015 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -10.60 | 0.00152 |
GUESTROOM306_308 | 455.16 | 546.19 | 0.012 | 0.043 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -10.60 | 0.00152 |
GUESTROOM309_312 | 1203.37 | 1444.05 | 0.034 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.60 | 0.00152 |
GUESTROOM313 | 441.36 | 529.63 | 0.012 | 0.014 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -10.60 | 0.00152 |
GUESTROOM314 | 691.91 | 830.29 | 0.020 | 0.024 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | -10.60 | 0.00152 |
GUESTROOM315_318 | 1248.24 | 1497.89 | 0.035 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.60 | 0.00152 |
GUESTROOM319 | 63.40 | 76.08 | 0.002 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -10.60 | 0.00152 |
GUESTROOM320_323 | 1061.81 | 1274.18 | 0.030 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -10.60 | 0.00152 |
GUESTROOM324 | 224.26 | 269.11 | 0.006 | 0.013 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -10.60 | 0.00152 |
GUESTROOM401 | 844.80 | 1013.76 | 0.024 | 0.029 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -10.60 | 0.00152 |
GUESTROOM402_405 | 1413.59 | 1696.31 | 0.037 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 21:15:00 | -10.60 | 0.00152 |
GUESTROOM406_408 | 1175.49 | 1410.58 | 0.031 | 0.043 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -10.60 | 0.00152 |
GUESTROOM409_412 | 2019.98 | 2423.97 | 0.057 | 0.069 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -10.60 | 0.00152 |
GUESTROOM413 | 730.14 | 876.16 | 0.019 | 0.023 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.60 | 0.00152 |
GUESTROOM414 | 597.12 | 716.55 | 0.016 | 0.019 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 20:00:00 | -10.60 | 0.00152 |
GUESTROOM415_418 | 1947.37 | 2336.84 | 0.055 | 0.066 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -10.60 | 0.00152 |
GUESTROOM419 | 621.52 | 745.83 | 0.018 | 0.021 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -10.60 | 0.00152 |
GUESTROOM420_423 | 1827.65 | 2193.18 | 0.052 | 0.062 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 18:30:00 | -10.60 | 0.00152 |
GUESTROOM424 | 826.23 | 991.47 | 0.023 | 0.028 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -10.60 | 0.00152 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
CORRIDORFLR1 | 29197.57 | 35037.09 | 0.826 | 0.991 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -10.60 | 0.00152 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
CORRIDORFLR2 | 1132.90 | 1359.48 | 0.032 | 0.039 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -10.60 | 0.00152 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
CORRIDORFLR3 | 1590.03 | 1908.04 | 0.045 | 0.054 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -10.60 | 0.00152 |
FRONTSTAIRSFLR3 | 50.25 | 60.30 | 0.001 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -10.60 | 0.00152 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | -10.60 | 0.00152 | |
CORRIDORFLR4 | 2656.28 | 3187.54 | 0.075 | 0.090 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -10.60 | 0.00152 |
FRONTSTAIRSFLR4 | 208.07 | 249.68 | 0.004 | 0.006 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -10.60 | 0.00152 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.38 | 0.38 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.01 | 1.01 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.45 | 0.45 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.78 | 0.78 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialEnthalpy | 0.24 | 1.01 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 3267.75 | 6500.00 | 1644.00 |
RESTROOMFLR1 | 1210.50 | 6285.50 | 234.25 |
MEETINGROOMFLR1 | 1746.25 | 2625.25 | 341.25 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 1499.50 | 8660.50 | 1494.75 |
GUESTROOM104 | 785.25 | 8425.75 | 774.75 |
GUESTROOM105 | 98.00 | 8051.25 | 37.50 |
EMPLOYEELOUNGEFLR1 | 3189.00 | 2060.50 | 315.75 |
EXERCISECENTERFLR1 | 2008.50 | 2570.00 | 54.25 |
FRONTOFFICEFLR1 | 2283.25 | 5164.75 | 357.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 730.25 | 8079.25 | 584.75 |
GUESTROOM206_208 | 605.00 | 8056.00 | 451.25 |
GUESTROOM209_212 | 472.25 | 8248.50 | 410.25 |
GUESTROOM213 | 1488.75 | 8383.00 | 1457.00 |
GUESTROOM214 | 729.50 | 8051.00 | 627.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 4110.25 | 4196.50 | 742.00 |
GUESTROOM220_223 | 342.25 | 7913.50 | 144.25 |
GUESTROOM224 | 743.75 | 8002.75 | 629.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 742.50 | 8304.50 | 683.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 1310.25 | 8058.75 | 1189.50 |
GUESTROOM315_318 | 456.25 | 7866.75 | 164.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 562.25 | 8034.50 | 419.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 3266.50 | 7902.75 | 2797.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1989.25 | 7690.25 | 1320.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1710.75 | 7525.75 | 909.00 |
GUESTROOM419 | 1652.75 | 7679.50 | 1078.00 |
GUESTROOM420_423 | 1780.75 | 7551.25 | 997.75 |
GUESTROOM424 | 2426.25 | 7734.75 | 1850.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7487.50 | 8759.00 | 6106.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 95.25 | 1079.50 | 95.25 | 1079.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 8.25 | 42.75 | 8.25 | 42.75 |
GUESTROOM104 | 5.75 | 43.50 | 5.75 | 43.50 |
GUESTROOM105 | 0.00 | 52.50 | 0.00 | 52.50 |
EMPLOYEELOUNGEFLR1 | 264.50 | 1308.25 | 206.25 | 870.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 2.25 | 35.75 | 2.25 | 35.75 |
GUESTROOM206_208 | 1.50 | 41.50 | 1.50 | 41.50 |
GUESTROOM209_212 | 1.25 | 34.75 | 1.25 | 34.75 |
GUESTROOM213 | 9.00 | 35.25 | 9.00 | 35.25 |
GUESTROOM214 | 4.50 | 36.25 | 4.50 | 36.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2972.25 | 0.00 | 2972.25 |
GUESTROOM220_223 | 0.25 | 34.50 | 0.25 | 34.50 |
GUESTROOM224 | 5.75 | 36.50 | 5.75 | 36.50 |
GUESTROOM301 | 5.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 5.00 | 34.75 | 5.00 | 34.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 9.00 | 35.25 | 9.00 | 35.25 |
GUESTROOM315_318 | 1.25 | 36.00 | 1.25 | 36.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 4.75 | 33.50 | 4.75 | 33.50 |
GUESTROOM324 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 17.00 | 54.25 | 17.00 | 54.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 8.00 | 41.25 | 8.00 | 41.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 8.25 | 37.00 | 8.25 | 37.00 |
GUESTROOM419 | 8.50 | 40.00 | 8.50 | 40.00 |
GUESTROOM420_423 | 9.00 | 36.50 | 9.00 | 36.50 |
GUESTROOM424 | 13.50 | 39.25 | 13.50 | 39.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 11.50 | 3464.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 432.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.25 | 24.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 4.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 503.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 10.75 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 314.00 | 5096.25 | 277.25 | 4092.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:16
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.383812 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.01 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.775121 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 319.72 |
CORRIDORFLR1 PTAC HEATING COIL | 36836.09 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 512.05 |
102 PTAC HEATING COIL | 997.40 |
103 PTAC HEATING COIL | 1257.99 |
104 PTAC HEATING COIL | 1139.08 |
105 PTAC HEATING COIL | 997.33 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 319.65 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 319.72 |
CORRIDORFLR2 PTAC HEATING COIL | 2839.58 |
201 PTAC HEATING COIL | 997.40 |
202_205 PTAC HEATING COIL | 3989.60 |
206_208 PTAC HEATING COIL | 3161.90 |
209_212 PTAC HEATING COIL | 3989.60 |
213 PTAC HEATING COIL | 1338.82 |
214 PTAC HEATING COIL | 1222.00 |
215_218 PTAC HEATING COIL | 3989.32 |
219 PTAC HEATING COIL | 997.33 |
220_223 PTAC HEATING COIL | 3989.32 |
224 PTAC HEATING COIL | 1110.24 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 319.65 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 319.72 |
CORRIDORFLR3 PTAC HEATING COIL | 3388.17 |
301 PTAC HEATING COIL | 997.40 |
302_305 PTAC HEATING COIL | 3989.60 |
306_308 PTAC HEATING COIL | 3161.90 |
309_312 PTAC HEATING COIL | 3989.60 |
313 PTAC HEATING COIL | 1014.98 |
314 PTAC HEATING COIL | 1352.18 |
315_318 PTAC HEATING COIL | 3989.32 |
319 PTAC HEATING COIL | 997.33 |
320_323 PTAC HEATING COIL | 3989.32 |
324 PTAC HEATING COIL | 997.33 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 452.58 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 319.72 |
CORRIDORFLR4 PTAC HEATING COIL | 4667.65 |
401 PTAC HEATING COIL | 1535.68 |
402_405 PTAC HEATING COIL | 3989.60 |
406_408 PTAC HEATING COIL | 3161.90 |
409_412 PTAC HEATING COIL | 4511.66 |
413 PTAC HEATING COIL | 1361.52 |
414 PTAC HEATING COIL | 1201.87 |
415_418 PTAC HEATING COIL | 4424.39 |
419 PTAC HEATING COIL | 1267.71 |
420_423 PTAC HEATING COIL | 4280.72 |
424 PTAC HEATING COIL | 1513.36 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 452.58 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.717081 | 0.383812 | 8165.09 |
SAC_FRONTLOUNGE COOLING COIL | 0.680960 | 1.01 | 24579.22 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.447236 | 11105.93 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.729395 | 0.775121 | 15809.22 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.01 |
RESTROOMFLR1 DIRECT AIR | 0.069758 |
MEETINGROOMFLR1 DIRECT AIR | 0.447236 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.570418 |
EXERCISECENTERFLR1 DIRECT AIR | 0.134945 |
FRONTOFFICEFLR1 DIRECT AIR | 0.383812 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.383812 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.01 |
SAC_MEETINGROOM MAIN BRANCH | 0.447236 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.775121 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.383812 |
SAC_FRONTLOUNGE | 1.01 |
SAC_MEETINGROOM | 0.447236 |
SAC_EXC_EMPLGE_RESTRM | 0.775121 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.383812 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.01 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.447236 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.775121 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.383812 | 0.383812 | 0.383812 | 0.383812 | 4106.85 | 8165.09 | 1.00 |
SAC_FRONTLOUNGE | 1.01 | 1.01 | 1.01 | 1.01 | 17213.78 | 24579.22 | 1.00 |
SAC_MEETINGROOM | 0.447236 | 0.447236 | 0.447236 | 0.447236 | 9217.85 | 11105.93 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.775121 | 0.775121 | 0.775121 | 0.775121 | 6923.16 | 15809.22 | 0.174095 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4106.85 |
SAC_FRONTLOUNGE HEATING COIL | 17213.78 |
SAC_MEETINGROOM HEATING COIL | 9217.85 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 6923.16 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.447236 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.49 | -0.5 |
February | 16.96 | 2.24 |
March | 19.27 | 8.00 |
April | 21.26 | 13.18 |
May | 22.91 | 18.32 |
June | 24.57 | 22.93 |
July | 25.32 | 25.34 |
August | 25.11 | 24.28 |
September | 23.86 | 20.44 |
October | 21.49 | 12.66 |
November | 20.07 | 8.91 |
December | 17.50 | 2.07 |
Annual Sum or Average | 21.26 | 13.21 |
Minimum of Months | 16.49 | -0.5 |
Maximum of Months | 25.32 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | -0.5 |
February | 22.16 | 2.24 |
March | 23.14 | 8.00 |
April | 23.91 | 13.18 |
May | 25.01 | 18.32 |
June | 26.08 | 22.93 |
July | 26.72 | 25.34 |
August | 26.46 | 24.28 |
September | 25.53 | 20.44 |
October | 23.93 | 12.66 |
November | 23.34 | 8.91 |
December | 22.22 | 2.07 |
Annual Sum or Average | 24.20 | 13.21 |
Minimum of Months | 21.76 | -0.5 |
Maximum of Months | 26.72 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.66 | -0.5 |
February | 16.12 | 2.24 |
March | 18.44 | 8.00 |
April | 20.49 | 13.18 |
May | 22.19 | 18.32 |
June | 23.85 | 22.93 |
July | 24.64 | 25.34 |
August | 24.39 | 24.28 |
September | 23.16 | 20.44 |
October | 20.70 | 12.66 |
November | 19.24 | 8.91 |
December | 16.69 | 2.07 |
Annual Sum or Average | 20.49 | 13.21 |
Minimum of Months | 15.66 | -0.5 |
Maximum of Months | 24.64 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | -0.5 |
February | 21.23 | 2.24 |
March | 21.60 | 8.00 |
April | 22.35 | 13.18 |
May | 23.08 | 18.32 |
June | 23.65 | 22.93 |
July | 23.85 | 25.34 |
August | 23.80 | 24.28 |
September | 23.46 | 20.44 |
October | 22.23 | 12.66 |
November | 21.63 | 8.91 |
December | 21.28 | 2.07 |
Annual Sum or Average | 22.45 | 13.21 |
Minimum of Months | 21.13 | -0.5 |
Maximum of Months | 23.85 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | -0.5 |
February | 21.99 | 2.24 |
March | 22.48 | 8.00 |
April | 23.02 | 13.18 |
May | 23.39 | 18.32 |
June | 23.64 | 22.93 |
July | 23.76 | 25.34 |
August | 23.72 | 24.28 |
September | 23.57 | 20.44 |
October | 23.01 | 12.66 |
November | 22.63 | 8.91 |
December | 22.03 | 2.07 |
Annual Sum or Average | 22.93 | 13.21 |
Minimum of Months | 21.81 | -0.5 |
Maximum of Months | 23.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.41 | -0.5 |
February | 21.69 | 2.24 |
March | 22.53 | 8.00 |
April | 23.39 | 13.18 |
May | 23.69 | 18.32 |
June | 23.86 | 22.93 |
July | 23.89 | 25.34 |
August | 23.88 | 24.28 |
September | 23.82 | 20.44 |
October | 23.33 | 12.66 |
November | 22.78 | 8.91 |
December | 21.79 | 2.07 |
Annual Sum or Average | 23.01 | 13.21 |
Minimum of Months | 21.41 | -0.5 |
Maximum of Months | 23.89 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.95 | -0.5 |
February | 24.22 | 2.24 |
March | 25.05 | 8.00 |
April | 25.84 | 13.18 |
May | 26.38 | 18.32 |
June | 26.83 | 22.93 |
July | 27.04 | 25.34 |
August | 26.97 | 24.28 |
September | 26.63 | 20.44 |
October | 25.85 | 12.66 |
November | 25.27 | 8.91 |
December | 24.32 | 2.07 |
Annual Sum or Average | 25.70 | 13.21 |
Minimum of Months | 23.95 | -0.5 |
Maximum of Months | 27.04 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.21 | -0.5 |
February | 19.63 | 2.24 |
March | 20.81 | 8.00 |
April | 22.12 | 13.18 |
May | 22.82 | 18.32 |
June | 23.26 | 22.93 |
July | 23.33 | 25.34 |
August | 23.31 | 24.28 |
September | 23.15 | 20.44 |
October | 22.01 | 12.66 |
November | 21.11 | 8.91 |
December | 19.74 | 2.07 |
Annual Sum or Average | 21.72 | 13.21 |
Minimum of Months | 19.21 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.05 | -0.5 |
February | 19.40 | 2.24 |
March | 20.46 | 8.00 |
April | 21.79 | 13.18 |
May | 22.60 | 18.32 |
June | 23.18 | 22.93 |
July | 23.32 | 25.34 |
August | 23.28 | 24.28 |
September | 23.01 | 20.44 |
October | 21.69 | 12.66 |
November | 20.73 | 8.91 |
December | 19.52 | 2.07 |
Annual Sum or Average | 21.51 | 13.21 |
Minimum of Months | 19.05 | -0.5 |
Maximum of Months | 23.32 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -0.5 |
February | 20.78 | 2.24 |
March | 21.13 | 8.00 |
April | 21.52 | 13.18 |
May | 21.69 | 18.32 |
June | 21.75 | 22.93 |
July | 21.76 | 25.34 |
August | 21.75 | 24.28 |
September | 21.74 | 20.44 |
October | 21.50 | 12.66 |
November | 21.28 | 8.91 |
December | 20.81 | 2.07 |
Annual Sum or Average | 21.36 | 13.21 |
Minimum of Months | 20.62 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | -0.5 |
February | 21.00 | 2.24 |
March | 21.38 | 8.00 |
April | 21.66 | 13.18 |
May | 21.73 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.63 | 12.66 |
November | 21.46 | 8.91 |
December | 20.96 | 2.07 |
Annual Sum or Average | 21.47 | 13.21 |
Minimum of Months | 20.79 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | -0.5 |
February | 21.41 | 2.24 |
March | 21.65 | 8.00 |
April | 21.74 | 13.18 |
May | 21.75 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.73 | 12.66 |
November | 21.69 | 8.91 |
December | 21.34 | 2.07 |
Annual Sum or Average | 21.63 | 13.21 |
Minimum of Months | 21.23 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | -0.5 |
February | 22.51 | 2.24 |
March | 22.62 | 8.00 |
April | 22.79 | 13.18 |
May | 22.72 | 18.32 |
June | 22.51 | 22.93 |
July | 22.39 | 25.34 |
August | 22.46 | 24.28 |
September | 22.69 | 20.44 |
October | 22.75 | 12.66 |
November | 22.70 | 8.91 |
December | 22.45 | 2.07 |
Annual Sum or Average | 22.58 | 13.21 |
Minimum of Months | 22.39 | -0.5 |
Maximum of Months | 22.79 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 50.33 | -0.5 |
February | 50.56 | 2.24 |
March | 51.34 | 8.00 |
April | 52.06 | 13.18 |
May | 52.69 | 18.32 |
June | 53.28 | 22.93 |
July | 53.55 | 25.34 |
August | 53.48 | 24.28 |
September | 52.96 | 20.44 |
October | 52.11 | 12.66 |
November | 51.53 | 8.91 |
December | 50.65 | 2.07 |
Annual Sum or Average | 52.05 | 13.21 |
Minimum of Months | 50.33 | -0.5 |
Maximum of Months | 53.55 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.01 | -0.5 |
February | 68.12 | 2.24 |
March | 69.14 | 8.00 |
April | 70.08 | 13.18 |
May | 70.98 | 18.32 |
June | 71.72 | 22.93 |
July | 72.16 | 25.34 |
August | 72.15 | 24.28 |
September | 71.38 | 20.44 |
October | 70.29 | 12.66 |
November | 69.59 | 8.91 |
December | 68.48 | 2.07 |
Annual Sum or Average | 70.19 | 13.21 |
Minimum of Months | 68.01 | -0.5 |
Maximum of Months | 72.16 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.67 | -0.5 |
February | 22.86 | 2.24 |
March | 23.22 | 8.00 |
April | 23.60 | 13.18 |
May | 23.78 | 18.32 |
June | 23.88 | 22.93 |
July | 23.89 | 25.34 |
August | 23.89 | 24.28 |
September | 23.87 | 20.44 |
October | 23.57 | 12.66 |
November | 23.33 | 8.91 |
December | 22.82 | 2.07 |
Annual Sum or Average | 23.45 | 13.21 |
Minimum of Months | 22.67 | -0.5 |
Maximum of Months | 23.89 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | -0.5 |
February | 22.20 | 2.24 |
March | 22.96 | 8.00 |
April | 23.65 | 13.18 |
May | 23.83 | 18.32 |
June | 23.89 | 22.93 |
July | 23.89 | 25.34 |
August | 23.89 | 24.28 |
September | 23.89 | 20.44 |
October | 23.57 | 12.66 |
November | 23.19 | 8.91 |
December | 22.22 | 2.07 |
Annual Sum or Average | 23.26 | 13.21 |
Minimum of Months | 21.84 | -0.5 |
Maximum of Months | 23.89 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.41 | -0.5 |
February | 16.01 | 2.24 |
March | 18.65 | 8.00 |
April | 21.05 | 13.18 |
May | 23.13 | 18.32 |
June | 25.16 | 22.93 |
July | 26.03 | 25.34 |
August | 25.72 | 24.28 |
September | 24.08 | 20.44 |
October | 21.19 | 12.66 |
November | 19.53 | 8.91 |
December | 16.62 | 2.07 |
Annual Sum or Average | 21.07 | 13.21 |
Minimum of Months | 15.41 | -0.5 |
Maximum of Months | 26.03 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.08 | -0.5 |
February | 19.54 | 2.24 |
March | 21.16 | 8.00 |
April | 22.67 | 13.18 |
May | 23.82 | 18.32 |
June | 24.95 | 22.93 |
July | 25.42 | 25.34 |
August | 25.25 | 24.28 |
September | 24.37 | 20.44 |
October | 22.74 | 12.66 |
November | 21.68 | 8.91 |
December | 19.83 | 2.07 |
Annual Sum or Average | 22.56 | 13.21 |
Minimum of Months | 19.08 | -0.5 |
Maximum of Months | 25.42 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.43 | -0.5 |
February | 16.10 | 2.24 |
March | 19.02 | 8.00 |
April | 21.57 | 13.18 |
May | 23.55 | 18.32 |
June | 25.54 | 22.93 |
July | 26.43 | 25.34 |
August | 26.20 | 24.28 |
September | 24.62 | 20.44 |
October | 21.75 | 12.66 |
November | 19.97 | 8.91 |
December | 16.70 | 2.07 |
Annual Sum or Average | 21.44 | 13.21 |
Minimum of Months | 15.43 | -0.5 |
Maximum of Months | 26.43 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | -0.5 |
February | 21.63 | 2.24 |
March | 22.60 | 8.00 |
April | 23.63 | 13.18 |
May | 23.85 | 18.32 |
June | 23.93 | 22.93 |
July | 24.04 | 25.34 |
August | 23.98 | 24.28 |
September | 23.92 | 20.44 |
October | 23.48 | 12.66 |
November | 22.91 | 8.91 |
December | 21.73 | 2.07 |
Annual Sum or Average | 23.09 | 13.21 |
Minimum of Months | 21.30 | -0.5 |
Maximum of Months | 24.04 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.13 | -0.5 |
February | 14.80 | 2.24 |
March | 17.71 | 8.00 |
April | 20.41 | 13.18 |
May | 22.49 | 18.32 |
June | 24.51 | 22.93 |
July | 25.44 | 25.34 |
August | 25.17 | 24.28 |
September | 23.60 | 20.44 |
October | 20.54 | 12.66 |
November | 18.64 | 8.91 |
December | 15.41 | 2.07 |
Annual Sum or Average | 20.27 | 13.21 |
Minimum of Months | 14.13 | -0.5 |
Maximum of Months | 25.44 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.93 | -0.5 |
February | 19.11 | 2.24 |
March | 19.93 | 8.00 |
April | 21.79 | 13.18 |
May | 22.77 | 18.32 |
June | 23.28 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.16 | 20.44 |
October | 21.46 | 12.66 |
November | 20.07 | 8.91 |
December | 19.24 | 2.07 |
Annual Sum or Average | 21.38 | 13.21 |
Minimum of Months | 18.93 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.75 | -0.5 |
February | 20.96 | 2.24 |
March | 21.33 | 8.00 |
April | 21.68 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.62 | 12.66 |
November | 21.43 | 8.91 |
December | 20.95 | 2.07 |
Annual Sum or Average | 21.46 | 13.21 |
Minimum of Months | 20.75 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | -0.5 |
February | 21.01 | 2.24 |
March | 21.39 | 8.00 |
April | 21.70 | 13.18 |
May | 21.75 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.65 | 12.66 |
November | 21.49 | 8.91 |
December | 21.00 | 2.07 |
Annual Sum or Average | 21.49 | 13.21 |
Minimum of Months | 20.80 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | -0.5 |
February | 21.03 | 2.24 |
March | 21.41 | 8.00 |
April | 21.69 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.66 | 12.66 |
November | 21.52 | 8.91 |
December | 21.02 | 2.07 |
Annual Sum or Average | 21.49 | 13.21 |
Minimum of Months | 20.81 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -0.5 |
February | 20.76 | 2.24 |
March | 21.14 | 8.00 |
April | 21.58 | 13.18 |
May | 21.72 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.53 | 12.66 |
November | 21.28 | 8.91 |
December | 20.79 | 2.07 |
Annual Sum or Average | 21.37 | 13.21 |
Minimum of Months | 20.59 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | -0.5 |
February | 21.05 | 2.24 |
March | 21.46 | 8.00 |
April | 21.72 | 13.18 |
May | 21.75 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.68 | 12.66 |
November | 21.54 | 8.91 |
December | 21.00 | 2.07 |
Annual Sum or Average | 21.50 | 13.21 |
Minimum of Months | 20.81 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | -0.5 |
February | 22.82 | 2.24 |
March | 23.21 | 8.00 |
April | 23.33 | 13.18 |
May | 23.33 | 18.32 |
June | 23.33 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.33 | 20.44 |
October | 23.31 | 12.66 |
November | 23.27 | 8.91 |
December | 22.70 | 2.07 |
Annual Sum or Average | 23.16 | 13.21 |
Minimum of Months | 22.55 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 29.69 | -0.5 |
February | 29.95 | 2.24 |
March | 31.10 | 8.00 |
April | 32.26 | 13.18 |
May | 33.03 | 18.32 |
June | 33.69 | 22.93 |
July | 34.02 | 25.34 |
August | 33.93 | 24.28 |
September | 33.35 | 20.44 |
October | 32.25 | 12.66 |
November | 31.46 | 8.91 |
December | 30.18 | 2.07 |
Annual Sum or Average | 32.09 | 13.21 |
Minimum of Months | 29.69 | -0.5 |
Maximum of Months | 34.02 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | -0.5 |
February | 21.81 | 2.24 |
March | 21.97 | 8.00 |
April | 22.30 | 13.18 |
May | 22.72 | 18.32 |
June | 23.11 | 22.93 |
July | 23.45 | 25.34 |
August | 23.31 | 24.28 |
September | 22.92 | 20.44 |
October | 22.28 | 12.66 |
November | 22.03 | 8.91 |
December | 21.82 | 2.07 |
Annual Sum or Average | 22.46 | 13.21 |
Minimum of Months | 21.77 | -0.5 |
Maximum of Months | 23.45 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | -0.5 |
February | 21.23 | 2.24 |
March | 21.58 | 8.00 |
April | 21.74 | 13.18 |
May | 21.75 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.71 | 12.66 |
November | 21.63 | 8.91 |
December | 21.14 | 2.07 |
Annual Sum or Average | 21.57 | 13.21 |
Minimum of Months | 20.99 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | -0.5 |
February | 21.04 | 2.24 |
March | 21.46 | 8.00 |
April | 21.73 | 13.18 |
May | 21.75 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.68 | 12.66 |
November | 21.53 | 8.91 |
December | 20.99 | 2.07 |
Annual Sum or Average | 21.50 | 13.21 |
Minimum of Months | 20.80 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.62 | -0.5 |
February | 18.29 | 2.24 |
March | 20.43 | 8.00 |
April | 22.51 | 13.18 |
May | 24.00 | 18.32 |
June | 25.49 | 22.93 |
July | 26.07 | 25.34 |
August | 25.84 | 24.28 |
September | 24.66 | 20.44 |
October | 22.48 | 12.66 |
November | 21.04 | 8.91 |
December | 18.60 | 2.07 |
Annual Sum or Average | 22.27 | 13.21 |
Minimum of Months | 17.62 | -0.5 |
Maximum of Months | 26.07 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.57 | -0.5 |
February | 14.48 | 2.24 |
March | 17.90 | 8.00 |
April | 21.13 | 13.18 |
May | 23.73 | 18.32 |
June | 26.28 | 22.93 |
July | 27.36 | 25.34 |
August | 27.01 | 24.28 |
September | 24.83 | 20.44 |
October | 21.17 | 12.66 |
November | 18.97 | 8.91 |
December | 15.15 | 2.07 |
Annual Sum or Average | 21.00 | 13.21 |
Minimum of Months | 13.57 | -0.5 |
Maximum of Months | 27.36 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.45 | -0.5 |
February | 15.21 | 2.24 |
March | 18.37 | 8.00 |
April | 21.29 | 13.18 |
May | 23.53 | 18.32 |
June | 25.74 | 22.93 |
July | 26.69 | 25.34 |
August | 26.45 | 24.28 |
September | 24.68 | 20.44 |
October | 21.40 | 12.66 |
November | 19.32 | 8.91 |
December | 15.80 | 2.07 |
Annual Sum or Average | 21.11 | 13.21 |
Minimum of Months | 14.45 | -0.5 |
Maximum of Months | 26.69 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -0.5 |
February | 21.19 | 2.24 |
March | 21.66 | 8.00 |
April | 22.92 | 13.18 |
May | 23.56 | 18.32 |
June | 23.87 | 22.93 |
July | 23.90 | 25.34 |
August | 23.89 | 24.28 |
September | 23.81 | 20.44 |
October | 22.72 | 12.66 |
November | 21.72 | 8.91 |
December | 21.28 | 2.07 |
Annual Sum or Average | 22.64 | 13.21 |
Minimum of Months | 21.12 | -0.5 |
Maximum of Months | 23.90 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.82 | -0.5 |
February | 13.60 | 2.24 |
March | 16.78 | 8.00 |
April | 19.95 | 13.18 |
May | 22.42 | 18.32 |
June | 24.77 | 22.93 |
July | 25.79 | 25.34 |
August | 25.49 | 24.28 |
September | 23.68 | 20.44 |
October | 20.00 | 12.66 |
November | 17.68 | 8.91 |
December | 14.18 | 2.07 |
Annual Sum or Average | 19.79 | 13.21 |
Minimum of Months | 12.82 | -0.5 |
Maximum of Months | 25.79 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -0.5 |
February | 18.99 | 2.24 |
March | 19.53 | 8.00 |
April | 21.27 | 13.18 |
May | 22.53 | 18.32 |
June | 23.25 | 22.93 |
July | 23.33 | 25.34 |
August | 23.31 | 24.28 |
September | 23.04 | 20.44 |
October | 20.93 | 12.66 |
November | 19.48 | 8.91 |
December | 19.07 | 2.07 |
Annual Sum or Average | 21.15 | 13.21 |
Minimum of Months | 18.89 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | -0.5 |
February | 19.06 | 2.24 |
March | 19.84 | 8.00 |
April | 21.71 | 13.18 |
May | 22.74 | 18.32 |
June | 23.29 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.16 | 20.44 |
October | 21.29 | 12.66 |
November | 19.82 | 8.91 |
December | 19.16 | 2.07 |
Annual Sum or Average | 21.31 | 13.21 |
Minimum of Months | 18.91 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.92 | -0.5 |
February | 19.11 | 2.24 |
March | 20.00 | 8.00 |
April | 21.85 | 13.18 |
May | 22.78 | 18.32 |
June | 23.29 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.16 | 20.44 |
October | 21.42 | 12.66 |
November | 20.01 | 8.91 |
December | 19.21 | 2.07 |
Annual Sum or Average | 21.38 | 13.21 |
Minimum of Months | 18.92 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | -0.5 |
February | 20.95 | 2.24 |
March | 21.32 | 8.00 |
April | 21.66 | 13.18 |
May | 21.74 | 18.32 |
June | 21.75 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.61 | 12.66 |
November | 21.43 | 8.91 |
December | 20.94 | 2.07 |
Annual Sum or Average | 21.45 | 13.21 |
Minimum of Months | 20.73 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | -0.5 |
February | 19.04 | 2.24 |
March | 19.77 | 8.00 |
April | 21.58 | 13.18 |
May | 22.66 | 18.32 |
June | 23.28 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.13 | 20.44 |
October | 21.32 | 12.66 |
November | 19.88 | 8.91 |
December | 19.17 | 2.07 |
Annual Sum or Average | 21.29 | 13.21 |
Minimum of Months | 18.91 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | -0.5 |
February | 20.86 | 2.24 |
March | 21.30 | 8.00 |
April | 21.67 | 13.18 |
May | 21.73 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.61 | 12.66 |
November | 21.38 | 8.91 |
December | 20.83 | 2.07 |
Annual Sum or Average | 21.42 | 13.21 |
Minimum of Months | 20.65 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | -0.5 |
February | 21.25 | 2.24 |
March | 21.59 | 8.00 |
April | 21.75 | 13.18 |
May | 21.75 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.72 | 12.66 |
November | 21.64 | 8.91 |
December | 21.14 | 2.07 |
Annual Sum or Average | 21.57 | 13.21 |
Minimum of Months | 20.99 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -0.5 |
February | 21.56 | 2.24 |
March | 23.02 | 8.00 |
April | 24.58 | 13.18 |
May | 25.52 | 18.32 |
June | 26.29 | 22.93 |
July | 26.56 | 25.34 |
August | 26.44 | 24.28 |
September | 25.87 | 20.44 |
October | 24.42 | 12.66 |
November | 23.33 | 8.91 |
December | 21.72 | 2.07 |
Annual Sum or Average | 24.22 | 13.21 |
Minimum of Months | 21.12 | -0.5 |
Maximum of Months | 26.56 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.88 | -0.5 |
February | 20.59 | 2.24 |
March | 22.00 | 8.00 |
April | 23.10 | 13.18 |
May | 23.27 | 18.32 |
June | 23.33 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.33 | 20.44 |
October | 22.89 | 12.66 |
November | 22.20 | 8.91 |
December | 20.49 | 2.07 |
Annual Sum or Average | 22.32 | 13.21 |
Minimum of Months | 19.88 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.84 | -0.5 |
February | 21.10 | 2.24 |
March | 21.49 | 8.00 |
April | 21.72 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.68 | 12.66 |
November | 21.53 | 8.91 |
December | 21.01 | 2.07 |
Annual Sum or Average | 21.51 | 13.21 |
Minimum of Months | 20.84 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.96 | -0.5 |
February | 19.24 | 2.24 |
March | 20.40 | 8.00 |
April | 22.20 | 13.18 |
May | 22.93 | 18.32 |
June | 23.31 | 22.93 |
July | 23.33 | 25.34 |
August | 23.33 | 24.28 |
September | 23.22 | 20.44 |
October | 21.89 | 12.66 |
November | 20.60 | 8.91 |
December | 19.36 | 2.07 |
Annual Sum or Average | 21.58 | 13.21 |
Minimum of Months | 18.96 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.27 | -0.5 |
February | 17.05 | 2.24 |
March | 19.53 | 8.00 |
April | 22.13 | 13.18 |
May | 23.97 | 18.32 |
June | 25.73 | 22.93 |
July | 26.39 | 25.34 |
August | 26.13 | 24.28 |
September | 24.72 | 20.44 |
October | 21.99 | 12.66 |
November | 20.13 | 8.91 |
December | 17.36 | 2.07 |
Annual Sum or Average | 21.81 | 13.21 |
Minimum of Months | 16.27 | -0.5 |
Maximum of Months | 26.39 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.35 | -0.5 |
February | 13.42 | 2.24 |
March | 17.15 | 8.00 |
April | 20.80 | 13.18 |
May | 23.73 | 18.32 |
June | 26.56 | 22.93 |
July | 27.73 | 25.34 |
August | 27.36 | 24.28 |
September | 24.92 | 20.44 |
October | 20.76 | 12.66 |
November | 18.21 | 8.91 |
December | 14.06 | 2.07 |
Annual Sum or Average | 20.62 | 13.21 |
Minimum of Months | 12.35 | -0.5 |
Maximum of Months | 27.73 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.10 | -0.5 |
February | 14.00 | 2.24 |
March | 17.45 | 8.00 |
April | 20.83 | 13.18 |
May | 23.49 | 18.32 |
June | 25.99 | 22.93 |
July | 27.06 | 25.34 |
August | 26.74 | 24.28 |
September | 24.69 | 20.44 |
October | 20.75 | 12.66 |
November | 18.26 | 8.91 |
December | 14.53 | 2.07 |
Annual Sum or Average | 20.61 | 13.21 |
Minimum of Months | 13.10 | -0.5 |
Maximum of Months | 27.06 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -0.5 |
February | 21.19 | 2.24 |
March | 21.59 | 8.00 |
April | 22.45 | 13.18 |
May | 23.23 | 18.32 |
June | 23.83 | 22.93 |
July | 24.07 | 25.34 |
August | 23.97 | 24.28 |
September | 23.57 | 20.44 |
October | 22.27 | 12.66 |
November | 21.48 | 8.91 |
December | 21.23 | 2.07 |
Annual Sum or Average | 22.51 | 13.21 |
Minimum of Months | 21.11 | -0.5 |
Maximum of Months | 24.07 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.84 | -0.5 |
February | 12.76 | 2.24 |
March | 16.17 | 8.00 |
April | 19.61 | 13.18 |
May | 22.40 | 18.32 |
June | 24.97 | 22.93 |
July | 26.10 | 25.34 |
August | 25.72 | 24.28 |
September | 23.66 | 20.44 |
October | 19.47 | 12.66 |
November | 16.90 | 8.91 |
December | 13.25 | 2.07 |
Annual Sum or Average | 19.44 | 13.21 |
Minimum of Months | 11.84 | -0.5 |
Maximum of Months | 26.10 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -0.5 |
February | 20.61 | 2.24 |
March | 20.92 | 8.00 |
April | 21.48 | 13.18 |
May | 21.69 | 18.32 |
June | 21.76 | 22.93 |
July | 21.77 | 25.34 |
August | 21.76 | 24.28 |
September | 21.74 | 20.44 |
October | 21.35 | 12.66 |
November | 20.97 | 8.91 |
December | 20.63 | 2.07 |
Annual Sum or Average | 21.27 | 13.21 |
Minimum of Months | 20.48 | -0.5 |
Maximum of Months | 21.77 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -0.5 |
February | 19.05 | 2.24 |
March | 19.72 | 8.00 |
April | 21.20 | 13.18 |
May | 22.36 | 18.32 |
June | 23.15 | 22.93 |
July | 23.32 | 25.34 |
August | 23.27 | 24.28 |
September | 22.88 | 20.44 |
October | 20.79 | 12.66 |
November | 19.52 | 8.91 |
December | 19.09 | 2.07 |
Annual Sum or Average | 21.11 | 13.21 |
Minimum of Months | 18.89 | -0.5 |
Maximum of Months | 23.32 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -0.5 |
February | 19.07 | 2.24 |
March | 19.80 | 8.00 |
April | 21.28 | 13.18 |
May | 22.38 | 18.32 |
June | 23.15 | 22.93 |
July | 23.32 | 25.34 |
August | 23.27 | 24.28 |
September | 22.88 | 20.44 |
October | 20.86 | 12.66 |
November | 19.61 | 8.91 |
December | 19.11 | 2.07 |
Annual Sum or Average | 21.14 | 13.21 |
Minimum of Months | 18.90 | -0.5 |
Maximum of Months | 23.32 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -0.5 |
February | 20.91 | 2.24 |
March | 21.34 | 8.00 |
April | 21.68 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.61 | 12.66 |
November | 21.42 | 8.91 |
December | 20.86 | 2.07 |
Annual Sum or Average | 21.44 | 13.21 |
Minimum of Months | 20.64 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -0.5 |
February | 19.04 | 2.24 |
March | 19.70 | 8.00 |
April | 21.20 | 13.18 |
May | 22.34 | 18.32 |
June | 23.16 | 22.93 |
July | 23.32 | 25.34 |
August | 23.28 | 24.28 |
September | 22.90 | 20.44 |
October | 20.89 | 12.66 |
November | 19.60 | 8.91 |
December | 19.11 | 2.07 |
Annual Sum or Average | 21.13 | 13.21 |
Minimum of Months | 18.89 | -0.5 |
Maximum of Months | 23.32 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.93 | -0.5 |
February | 19.13 | 2.24 |
March | 20.04 | 8.00 |
April | 21.67 | 13.18 |
May | 22.58 | 18.32 |
June | 23.22 | 22.93 |
July | 23.33 | 25.34 |
August | 23.30 | 24.28 |
September | 23.03 | 20.44 |
October | 21.34 | 12.66 |
November | 20.01 | 8.91 |
December | 19.22 | 2.07 |
Annual Sum or Average | 21.33 | 13.21 |
Minimum of Months | 18.93 | -0.5 |
Maximum of Months | 23.33 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | -0.5 |
February | 21.11 | 2.24 |
March | 21.54 | 8.00 |
April | 21.74 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.69 | 12.66 |
November | 21.56 | 8.91 |
December | 20.95 | 2.07 |
Annual Sum or Average | 21.51 | 13.21 |
Minimum of Months | 20.77 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.88 | -0.5 |
February | 19.45 | 2.24 |
March | 21.03 | 8.00 |
April | 22.68 | 13.18 |
May | 23.87 | 18.32 |
June | 24.90 | 22.93 |
July | 25.28 | 25.34 |
August | 25.05 | 24.28 |
September | 24.23 | 20.44 |
October | 22.38 | 12.66 |
November | 21.14 | 8.91 |
December | 19.47 | 2.07 |
Annual Sum or Average | 22.38 | 13.21 |
Minimum of Months | 18.88 | -0.5 |
Maximum of Months | 25.28 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | -0.5 |
February | 21.04 | 2.24 |
March | 21.49 | 8.00 |
April | 21.73 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.68 | 12.66 |
November | 21.52 | 8.91 |
December | 20.92 | 2.07 |
Annual Sum or Average | 21.49 | 13.21 |
Minimum of Months | 20.72 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | -0.5 |
February | 21.08 | 2.24 |
March | 21.52 | 8.00 |
April | 21.74 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.75 | 20.44 |
October | 21.68 | 12.66 |
November | 21.53 | 8.91 |
December | 20.93 | 2.07 |
Annual Sum or Average | 21.50 | 13.21 |
Minimum of Months | 20.74 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.57 | -0.5 |
February | 20.82 | 2.24 |
March | 21.32 | 8.00 |
April | 21.70 | 13.18 |
May | 21.74 | 18.32 |
June | 21.76 | 22.93 |
July | 21.76 | 25.34 |
August | 21.76 | 24.28 |
September | 21.76 | 20.44 |
October | 21.61 | 12.66 |
November | 21.36 | 8.91 |
December | 20.77 | 2.07 |
Annual Sum or Average | 21.41 | 13.21 |
Minimum of Months | 20.57 | -0.5 |
Maximum of Months | 21.76 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.68 | -0.5 |
February | 16.60 | 2.24 |
March | 19.23 | 8.00 |
April | 21.93 | 13.18 |
May | 23.95 | 18.32 |
June | 25.83 | 22.93 |
July | 26.55 | 25.34 |
August | 26.21 | 24.28 |
September | 24.64 | 20.44 |
October | 21.63 | 12.66 |
November | 19.66 | 8.91 |
December | 16.77 | 2.07 |
Annual Sum or Average | 21.58 | 13.21 |
Minimum of Months | 15.68 | -0.5 |
Maximum of Months | 26.55 | 25.34 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:16
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.55 | -0.5 |
February | 12.76 | 2.24 |
March | 16.61 | 8.00 |
April | 20.50 | 13.18 |
May | 23.70 | 18.32 |
June | 26.69 | 22.93 |
July | 27.95 | 25.34 |
August | 27.51 | 24.28 |
September | 24.85 | 20.44 |
October | 20.27 | 12.66 |
November | 17.53 | 8.91 |
December | 13.22 | 2.07 |
Annual Sum or Average | 20.30 | 13.21 |
Minimum of Months | 11.55 | -0.5 |
Maximum of Months | 27.95 | 25.34 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:16
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.189633E+12 | 157994.383 | 18-JAN-07:15 | 20847.837 | 39740.848 | 9201.505 | 83880.554 | 127.526 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.158991E+12 | 149800.599 | 06-FEB-07:15 | 20847.837 | 39740.848 | 9197.885 | 79860.500 | 145.416 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.154234E+12 | 130327.442 | 19-MAR-06:15 | 20847.837 | 39740.848 | 9180.631 | 56143.428 | 218.586 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.148907E+12 | 102096.289 | 17-APR-06:15 | 20847.837 | 39740.848 | 9180.631 | 30438.258 | 1880.602 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.170250E+12 | 106072.717 | 30-MAY-19:30 | 27551.975 | 28549.175 | 9247.792 | 0.000 | 36527.662 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.181891E+12 | 117461.999 | 30-JUN-07:00 | 25182.171 | 43578.554 | 9699.799 | 0.000 | 38993.362 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.200253E+12 | 117726.785 | 21-JUL-07:00 | 25182.171 | 43578.554 | 9699.799 | 0.000 | 39258.148 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.194726E+12 | 113894.530 | 18-AUG-07:00 | 25182.171 | 43578.554 | 9699.799 | 0.000 | 35425.893 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.174483E+12 | 111584.254 | 03-SEP-07:00 | 25182.171 | 43578.554 | 9699.799 | 0.000 | 33115.617 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.155630E+12 | 107124.293 | 31-OCT-06:15 | 20847.837 | 39740.848 | 9180.631 | 31833.489 | 1325.376 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.147664E+12 | 109880.590 | 23-NOV-07:15 | 20847.837 | 39740.848 | 9180.631 | 39339.786 | 763.375 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.180298E+12 | 159124.247 | 25-DEC-07:15 | 17938.631 | 34285.948 | 9213.792 | 93393.002 | 96.761 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.205696E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.147664E+12 | 102096.289 | 17938.631 | 28549.175 | 9180.631 | 0.000 | 96.761 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.200253E+12 | 159124.247 | 27551.975 | 43578.554 | 9699.799 | 93393.002 | 39258.148 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:16
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.111454E+12 | 108079.729 | 14-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 67983.701 | 67983.701 | 67983.701 | 0.000 |
February | 0.971298E+11 | 109333.139 | 11-FEB-09:15 | 847.538 | 40096.028 | 0.000 | 68389.572 | 68389.572 | 68389.572 | 847.538 |
March | 0.974503E+11 | 106250.434 | 17-MAR-08:15 | 0.000 | 40096.028 | 0.000 | 66154.406 | 66154.406 | 66154.406 | 0.000 |
April | 0.875492E+11 | 92433.252 | 14-APR-08:15 | 0.000 | 40096.028 | 0.000 | 52337.224 | 52337.224 | 52337.224 | 0.000 |
May | 0.860842E+11 | 91681.140 | 13-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 51585.112 | 51585.112 | 51585.112 | 0.000 |
June | 0.796464E+11 | 85331.586 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 45235.558 | 45235.558 | 45235.558 | 0.000 |
July | 0.798761E+11 | 83370.933 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 43274.905 | 43274.905 | 43274.905 | 0.000 |
August | 0.792947E+11 | 82321.202 | 26-AUG-08:00 | 0.000 | 40096.028 | 0.000 | 42225.174 | 42225.174 | 42225.174 | 0.000 |
September | 0.780306E+11 | 83721.999 | 29-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 43625.971 | 43625.971 | 43625.971 | 0.000 |
October | 0.849786E+11 | 85445.524 | 27-OCT-09:30 | 1536.880 | 40096.028 | 0.000 | 43812.615 | 43812.615 | 43812.615 | 1536.880 |
November | 0.878948E+11 | 91618.145 | 04-NOV-08:15 | 0.000 | 40096.028 | 0.000 | 51522.117 | 51522.117 | 51522.117 | 0.000 |
December | 0.105118E+12 | 106848.015 | 25-DEC-12:30 | 18019.793 | 40096.028 | 0.000 | 48732.193 | 48732.193 | 48732.193 | 18019.793 |
Annual Sum or Average | 0.107451E+13 | 0.000 | ||||||||
Minimum of Months | 0.780306E+11 | 82321.202 | 0.000 | 40096.028 | 0.000 | 42225.174 | 42225.174 | 42225.174 | 0.000 | |
Maximum of Months | 0.111454E+12 | 109333.139 | 18019.793 | 40096.028 | 0.000 | 68389.572 | 68389.572 | 68389.572 | 18019.793 |