Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2015-09-14 08:44:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2990.09 | 744.99 | 802.69 |
Net Site Energy | 2990.09 | 744.99 | 802.69 |
Total Source Energy | 7474.68 | 1862.35 | 2006.58 |
Net Source Energy | 7474.68 | 1862.35 | 2006.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 30.21 | 9.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 445.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 310.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 527.07 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2032.37 | 957.73 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 30.21 | 9.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 445.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 310.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 527.07 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 211.12 | 143.95 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 545.59 | 257.10 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.94 | 133.61 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 506.37 | 238.62 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2032.37 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2032.37 | 100.00 |
Total On-Site and Utility Electric Sources | 2032.37 | 100.00 |
Total Electricity End Uses | 2032.37 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 86.50 |
Time Setpoint Not Met During Occupied Cooling | 4955.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5232.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 8.38 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 175.82 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7613.24 | 6028.80 | 1584.44 | 0.79 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 22191.05 | 16641.24 | 5549.82 | 0.75 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10915.02 | 7857.06 | 3057.96 | 0.72 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15285.76 | 12045.67 | 3240.09 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7262.9 | 3.16 | 10.80 | 11.43 | 10.60 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 21288.3 | 2.94 | 10.03 | 10.64 | 10.06 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10512.7 | 3.29 | 11.24 | 11.91 | 11.26 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14589.9 | 3.17 | 10.82 | 11.45 | 10.63 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 25729.22 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 446.41 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 446.41 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 938.37 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 828.24 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2246.31 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 792.05 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2510.92 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 975.14 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 860.93 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 812.26 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2259.14 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 792.05 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2510.92 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 792.05 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 963.89 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 3367.88 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1258.86 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2510.92 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3587.28 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 953.69 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 799.01 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3520.35 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 998.27 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3391.25 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1175.26 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3261.33 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 13669.78 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 7320.07 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5483.20 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.45 | 524.05 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.16 | 1325.74 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.52 | 601.34 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.90 | 1022.37 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10194.43 | 12233.32 | 0.969 | 1.163 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
RESTROOMFLR1 | 741.84 | 890.21 | 0.070 | 0.085 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 35.30 | 0.00682 |
MEETINGROOMFLR1 | 4538.52 | 5446.22 | 0.432 | 0.518 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM101 | 593.10 | 711.72 | 0.060 | 0.072 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM102 | 453.49 | 544.18 | 0.046 | 0.055 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM103 | 1582.82 | 1899.39 | 0.209 | 0.251 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM104 | 1451.31 | 1741.58 | 0.192 | 0.230 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 35.44 | 0.00682 |
GUESTROOM105 | 1846.05 | 2215.26 | 0.244 | 0.293 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
EMPLOYEELOUNGEFLR1 | 5767.74 | 6921.28 | 0.548 | 0.658 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
EXERCISECENTERFLR1 | 1351.87 | 1622.25 | 0.128 | 0.154 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95 | 0.00682 |
FRONTOFFICEFLR1 | 3960.88 | 4753.06 | 0.376 | 0.451 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM201 | 898.22 | 1077.86 | 0.090 | 0.108 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM202_205 | 5912.43 | 7094.92 | 0.781 | 0.937 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM206_208 | 4810.81 | 5772.97 | 0.635 | 0.762 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM209_212 | 5540.31 | 6648.37 | 0.732 | 0.878 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM213 | 1643.14 | 1971.76 | 0.217 | 0.260 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM214 | 1640.21 | 1968.25 | 0.217 | 0.260 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM215_218 | 8778.84 | 10534.61 | 0.883 | 1.060 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM219 | 5754.00 | 6904.80 | 0.760 | 0.912 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM220_223 | 5364.43 | 6437.32 | 0.708 | 0.850 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 34.62 | 0.00682 |
GUESTROOM224 | 1632.36 | 1958.84 | 0.216 | 0.259 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM301 | 775.19 | 930.23 | 0.078 | 0.094 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM302_305 | 1991.46 | 2389.76 | 0.200 | 0.240 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM306_308 | 1769.04 | 2122.85 | 0.178 | 0.214 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM309_312 | 5546.85 | 6656.21 | 0.733 | 0.879 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
GUESTROOM313 | 713.92 | 856.71 | 0.072 | 0.086 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM314 | 1573.48 | 1888.18 | 0.208 | 0.249 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 37.52 | 0.00682 |
GUESTROOM315_318 | 6045.35 | 7254.42 | 0.798 | 0.958 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM319 | 877.81 | 1053.37 | 0.088 | 0.106 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM320_323 | 5194.43 | 6233.31 | 0.686 | 0.823 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM324 | 584.18 | 701.01 | 0.059 | 0.071 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 35.11 | 0.00682 |
GUESTROOM401 | 2148.86 | 2578.63 | 0.284 | 0.341 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
GUESTROOM402_405 | 3082.08 | 3698.50 | 0.310 | 0.372 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
GUESTROOM406_408 | 2725.13 | 3270.16 | 0.274 | 0.329 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
GUESTROOM409_412 | 6911.70 | 8294.04 | 0.913 | 1.095 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
GUESTROOM413 | 1100.39 | 1320.47 | 0.111 | 0.133 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
GUESTROOM414 | 946.04 | 1135.25 | 0.095 | 0.114 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
GUESTROOM415_418 | 6594.27 | 7913.12 | 0.871 | 1.045 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 35.76 | 0.00682 |
GUESTROOM419 | 1836.46 | 2203.76 | 0.243 | 0.291 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
GUESTROOM420_423 | 6455.00 | 7745.99 | 0.852 | 1.023 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:30:00 | 35.76 | 0.00682 |
GUESTROOM424 | 1924.94 | 2309.93 | 0.254 | 0.305 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10 | 0.00682 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR1 | 20359.40 | 24431.29 | 1.933 | 2.320 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR2 | 3119.58 | 3743.50 | 0.296 | 0.355 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR3 | 1855.29 | 2226.35 | 0.176 | 0.211 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR4 | 3032.92 | 3639.51 | 0.288 | 0.346 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1434.84 | 1721.80 | 0.047 | 0.236 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | -5.20 | 0.00281 |
RESTROOMFLR1 | 13.26 | 15.91 | 0.000 | 0.001 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.20 | 0.00281 |
MEETINGROOMFLR1 | 476.08 | 571.29 | 0.015 | 0.126 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -5.20 | 0.00281 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
GUESTROOM102 | 0.00 | 0.00 | 0.000 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
GUESTROOM103 | 467.36 | 560.84 | 0.015 | 0.018 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.20 | 0.00281 |
GUESTROOM104 | 375.61 | 450.74 | 0.012 | 0.015 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -5.20 | 0.00281 |
GUESTROOM105 | 268.78 | 322.53 | 0.009 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | -5.20 | 0.00281 |
EMPLOYEELOUNGEFLR1 | 242.56 | 291.07 | 0.008 | 0.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20 | 0.00281 |
EXERCISECENTERFLR1 | 123.94 | 148.73 | 0.004 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20 | 0.00281 |
FRONTOFFICEFLR1 | 838.36 | 1006.03 | 0.027 | 0.056 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -5.20 | 0.00281 |
GUESTROOM201 | 167.70 | 201.24 | 0.005 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | -5.20 | 0.00281 |
GUESTROOM202_205 | 1065.24 | 1278.29 | 0.035 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -5.20 | 0.00281 |
GUESTROOM206_208 | 774.23 | 929.08 | 0.025 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
GUESTROOM209_212 | 807.45 | 968.94 | 0.026 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.20 | 0.00281 |
GUESTROOM213 | 498.00 | 597.61 | 0.016 | 0.019 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | -5.20 | 0.00281 |
GUESTROOM214 | 402.85 | 483.42 | 0.013 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | -5.20 | 0.00281 |
GUESTROOM215_218 | 15.85 | 19.02 | 0.000 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
GUESTROOM219 | 215.71 | 258.86 | 0.007 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.20 | 0.00281 |
GUESTROOM220_223 | 691.85 | 830.22 | 0.022 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -5.20 | 0.00281 |
GUESTROOM224 | 362.30 | 434.75 | 0.012 | 0.014 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.20 | 0.00281 |
GUESTROOM301 | 235.18 | 282.22 | 0.007 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 17:45:00 | -5.20 | 0.00281 |
GUESTROOM302_305 | 424.37 | 509.24 | 0.013 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -5.20 | 0.00281 |
GUESTROOM306_308 | 329.10 | 394.92 | 0.010 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 14:45:00 | -5.20 | 0.00281 |
GUESTROOM309_312 | 1019.27 | 1223.12 | 0.033 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:30:00 | -5.20 | 0.00281 |
GUESTROOM313 | 260.28 | 312.34 | 0.008 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -5.20 | 0.00281 |
GUESTROOM314 | 488.66 | 586.39 | 0.016 | 0.019 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:45:00 | -5.20 | 0.00281 |
GUESTROOM315_318 | 1072.62 | 1287.14 | 0.035 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -5.20 | 0.00281 |
GUESTROOM319 | 14.85 | 17.82 | 0.000 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 12:45:00 | -5.20 | 0.00281 |
GUESTROOM320_323 | 903.35 | 1084.02 | 0.029 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -5.20 | 0.00281 |
GUESTROOM324 | 114.30 | 137.15 | 0.003 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 20:45:00 | -5.20 | 0.00281 |
GUESTROOM401 | 734.44 | 881.33 | 0.024 | 0.029 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | -5.20 | 0.00281 |
GUESTROOM402_405 | 1146.97 | 1376.36 | 0.035 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -5.20 | 0.00281 |
GUESTROOM406_408 | 948.88 | 1138.65 | 0.029 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -5.20 | 0.00281 |
GUESTROOM409_412 | 1730.96 | 2077.16 | 0.056 | 0.068 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | -5.20 | 0.00281 |
GUESTROOM413 | 506.70 | 608.04 | 0.015 | 0.018 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:45:00 | -5.20 | 0.00281 |
GUESTROOM414 | 377.82 | 453.39 | 0.011 | 0.014 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 20:30:00 | -5.20 | 0.00281 |
GUESTROOM415_418 | 1675.28 | 2010.34 | 0.054 | 0.065 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -5.20 | 0.00281 |
GUESTROOM419 | 517.30 | 620.77 | 0.017 | 0.020 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:15:00 | -5.20 | 0.00281 |
GUESTROOM420_423 | 1567.70 | 1881.24 | 0.051 | 0.061 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.20 | 0.00281 |
GUESTROOM424 | 664.80 | 797.76 | 0.022 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20 | 0.00281 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR1 | 20360.35 | 24432.42 | 0.661 | 0.793 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR2 | 603.66 | 724.39 | 0.020 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR3 | 990.39 | 1188.46 | 0.032 | 0.039 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR4 | 1914.35 | 2297.22 | 0.062 | 0.075 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.45 | 0.45 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.16 | 1.16 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.52 | 0.52 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.90 | 0.90 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 1.16 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 2657.25 | 5452.75 | 650.25 |
RESTROOMFLR1 | 1174.50 | 5702.25 | 52.75 |
MEETINGROOMFLR1 | 1819.25 | 1831.75 | 83.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 75.25 | 8674.25 | 75.25 |
GUESTROOM104 | 4.75 | 8429.75 | 4.75 |
GUESTROOM105 | 6.75 | 8008.50 | 2.50 |
EMPLOYEELOUNGEFLR1 | 3057.00 | 2008.00 | 224.75 |
EXERCISECENTERFLR1 | 2298.50 | 1805.50 | 19.00 |
FRONTOFFICEFLR1 | 2124.25 | 4554.50 | 64.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 29.50 | 8053.75 | 6.25 |
GUESTROOM206_208 | 36.25 | 8041.50 | 4.75 |
GUESTROOM209_212 | 23.25 | 8278.00 | 11.50 |
GUESTROOM213 | 41.00 | 8431.25 | 40.25 |
GUESTROOM214 | 7.75 | 7957.25 | 2.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 5187.50 | 3729.50 | 1160.50 |
GUESTROOM220_223 | 41.50 | 7849.50 | 3.75 |
GUESTROOM224 | 9.75 | 7910.25 | 1.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 26.50 | 8334.50 | 15.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 14.75 | 7948.75 | 8.00 |
GUESTROOM315_318 | 90.25 | 7745.00 | 3.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 24.25 | 7973.00 | 6.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1527.25 | 7710.25 | 1072.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 897.00 | 7397.75 | 158.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1000.25 | 7188.25 | 72.75 |
GUESTROOM419 | 710.25 | 7442.75 | 61.25 |
GUESTROOM420_423 | 998.00 | 7225.75 | 88.25 |
GUESTROOM424 | 920.75 | 7492.00 | 224.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7163.00 | 8759.75 | 5232.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 1518.75 | 0.00 | 1518.75 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 46.25 | 0.00 | 46.25 |
GUESTROOM104 | 0.00 | 44.50 | 0.00 | 44.50 |
GUESTROOM105 | 0.00 | 51.25 | 0.00 | 51.25 |
EMPLOYEELOUNGEFLR1 | 121.75 | 1126.00 | 86.25 | 587.50 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 37.00 | 0.00 | 37.00 |
GUESTROOM206_208 | 0.00 | 44.00 | 0.00 | 44.00 |
GUESTROOM209_212 | 0.00 | 34.00 | 0.00 | 34.00 |
GUESTROOM213 | 0.00 | 37.50 | 0.00 | 37.50 |
GUESTROOM214 | 0.00 | 37.00 | 0.00 | 37.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 3966.00 | 0.00 | 3966.00 |
GUESTROOM220_223 | 0.00 | 32.25 | 0.00 | 32.25 |
GUESTROOM224 | 0.00 | 36.50 | 0.00 | 36.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 34.25 | 0.00 | 34.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 36.75 | 0.00 | 36.75 |
GUESTROOM315_318 | 0.00 | 34.50 | 0.00 | 34.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 30.25 | 0.00 | 30.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.25 | 55.25 | 0.25 | 55.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 45.75 | 0.00 | 45.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 40.75 | 0.00 | 40.75 |
GUESTROOM419 | 0.00 | 43.75 | 0.00 | 43.75 |
GUESTROOM420_423 | 0.00 | 40.25 | 0.00 | 40.25 |
GUESTROOM424 | 0.00 | 44.00 | 0.00 | 44.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 4786.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 588.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 3.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 887.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 122.00 | 6314.25 | 86.50 | 4955.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:33
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.451444 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.16 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.896732 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR1 PTAC HEATING COIL | 25729.22 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 446.41 |
102 PTAC HEATING COIL | 446.41 |
103 PTAC HEATING COIL | 938.37 |
104 PTAC HEATING COIL | 828.24 |
105 PTAC HEATING COIL | 792.00 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 278.67 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR2 PTAC HEATING COIL | 2246.31 |
201 PTAC HEATING COIL | 792.05 |
202_205 PTAC HEATING COIL | 3168.22 |
206_208 PTAC HEATING COIL | 2510.92 |
209_212 PTAC HEATING COIL | 3168.22 |
213 PTAC HEATING COIL | 975.14 |
214 PTAC HEATING COIL | 860.93 |
215_218 PTAC HEATING COIL | 3167.99 |
219 PTAC HEATING COIL | 792.00 |
220_223 PTAC HEATING COIL | 3167.99 |
224 PTAC HEATING COIL | 812.26 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 278.67 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR3 PTAC HEATING COIL | 2259.14 |
301 PTAC HEATING COIL | 792.05 |
302_305 PTAC HEATING COIL | 3168.22 |
306_308 PTAC HEATING COIL | 2510.92 |
309_312 PTAC HEATING COIL | 3168.22 |
313 PTAC HEATING COIL | 792.05 |
314 PTAC HEATING COIL | 963.89 |
315_318 PTAC HEATING COIL | 3167.99 |
319 PTAC HEATING COIL | 792.00 |
320_323 PTAC HEATING COIL | 3167.99 |
324 PTAC HEATING COIL | 792.00 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 278.67 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR4 PTAC HEATING COIL | 3367.88 |
401 PTAC HEATING COIL | 1258.86 |
402_405 PTAC HEATING COIL | 3168.22 |
406_408 PTAC HEATING COIL | 2510.92 |
409_412 PTAC HEATING COIL | 3587.28 |
413 PTAC HEATING COIL | 953.69 |
414 PTAC HEATING COIL | 799.01 |
415_418 PTAC HEATING COIL | 3520.35 |
419 PTAC HEATING COIL | 998.27 |
420_423 PTAC HEATING COIL | 3391.25 |
424 PTAC HEATING COIL | 1175.26 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 278.67 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.791883 | 0.451444 | 7613.24 |
SAC_FRONTLOUNGE COOLING COIL | 0.749907 | 1.16 | 22191.05 |
SAC_MEETINGROOM COOLING COIL | 0.719839 | 0.518022 | 10915.02 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.788032 | 0.896732 | 15285.76 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.16 |
RESTROOMFLR1 DIRECT AIR | 0.084538 |
MEETINGROOMFLR1 DIRECT AIR | 0.518022 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.658057 |
EXERCISECENTERFLR1 DIRECT AIR | 0.154137 |
FRONTOFFICEFLR1 DIRECT AIR | 0.451444 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.451444 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.16 |
SAC_MEETINGROOM MAIN BRANCH | 0.518022 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.896732 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.451444 |
SAC_FRONTLOUNGE | 1.16 |
SAC_MEETINGROOM | 0.518022 |
SAC_EXC_EMPLGE_RESTRM | 0.896732 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.451444 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.16 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.518022 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.896732 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.451444 | 0.451444 | 0.451444 | 0.451444 | 3261.33 | 7613.24 | 1.00 |
SAC_FRONTLOUNGE | 1.16 | 1.16 | 1.16 | 1.16 | 13669.78 | 22191.05 | 1.00 |
SAC_MEETINGROOM | 0.518022 | 0.518022 | 0.518022 | 0.518022 | 7320.07 | 10915.02 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.896732 | 0.896732 | 0.896732 | 0.896732 | 5483.20 | 15285.76 | 0.171887 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3261.33 |
SAC_FRONTLOUNGE HEATING COIL | 13669.78 |
SAC_MEETINGROOM HEATING COIL | 7320.07 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5483.20 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.518022 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | 8.14 |
February | 20.99 | 10.27 |
March | 21.50 | 12.55 |
April | 23.43 | 19.23 |
May | 24.81 | 23.84 |
June | 26.07 | 27.86 |
July | 25.98 | 27.54 |
August | 25.71 | 26.28 |
September | 25.23 | 23.38 |
October | 23.64 | 18.30 |
November | 21.66 | 11.18 |
December | 20.64 | 6.79 |
Annual Sum or Average | 23.36 | 17.98 |
Minimum of Months | 20.48 | 6.79 |
Maximum of Months | 26.07 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.39 | 8.14 |
February | 23.68 | 10.27 |
March | 24.02 | 12.55 |
April | 25.14 | 19.23 |
May | 26.07 | 23.84 |
June | 27.02 | 27.86 |
July | 27.16 | 27.54 |
August | 26.77 | 26.28 |
September | 26.27 | 23.38 |
October | 25.09 | 18.30 |
November | 23.86 | 11.18 |
December | 23.29 | 6.79 |
Annual Sum or Average | 25.15 | 17.98 |
Minimum of Months | 23.29 | 6.79 |
Maximum of Months | 27.16 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 8.14 |
February | 20.14 | 10.27 |
March | 20.71 | 12.55 |
April | 22.69 | 19.23 |
May | 24.13 | 23.84 |
June | 25.38 | 27.86 |
July | 25.29 | 27.54 |
August | 25.00 | 26.28 |
September | 24.49 | 23.38 |
October | 22.95 | 18.30 |
November | 20.87 | 11.18 |
December | 19.74 | 6.79 |
Annual Sum or Average | 22.60 | 17.98 |
Minimum of Months | 19.63 | 6.79 |
Maximum of Months | 25.38 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 8.14 |
February | 22.06 | 10.27 |
March | 22.46 | 12.55 |
April | 23.33 | 19.23 |
May | 23.73 | 23.84 |
June | 23.87 | 27.86 |
July | 23.88 | 27.54 |
August | 23.86 | 26.28 |
September | 23.73 | 23.38 |
October | 23.25 | 18.30 |
November | 22.24 | 11.18 |
December | 21.59 | 6.79 |
Annual Sum or Average | 22.98 | 17.98 |
Minimum of Months | 21.59 | 6.79 |
Maximum of Months | 23.88 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.62 | 8.14 |
February | 22.77 | 10.27 |
March | 23.00 | 12.55 |
April | 23.40 | 19.23 |
May | 23.60 | 23.84 |
June | 23.72 | 27.86 |
July | 23.74 | 27.54 |
August | 23.70 | 26.28 |
September | 23.64 | 23.38 |
October | 23.47 | 18.30 |
November | 22.95 | 11.18 |
December | 22.54 | 6.79 |
Annual Sum or Average | 23.26 | 17.98 |
Minimum of Months | 22.54 | 6.79 |
Maximum of Months | 23.74 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.89 | 8.14 |
February | 23.12 | 10.27 |
March | 23.39 | 12.55 |
April | 23.73 | 19.23 |
May | 23.85 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.87 | 23.38 |
October | 23.77 | 18.30 |
November | 23.32 | 11.18 |
December | 22.77 | 6.79 |
Annual Sum or Average | 23.53 | 17.98 |
Minimum of Months | 22.77 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.26 | 8.14 |
February | 25.50 | 10.27 |
March | 25.84 | 12.55 |
April | 26.47 | 19.23 |
May | 26.90 | 23.84 |
June | 27.24 | 27.86 |
July | 27.25 | 27.54 |
August | 27.14 | 26.28 |
September | 26.98 | 23.38 |
October | 26.52 | 18.30 |
November | 25.77 | 11.18 |
December | 25.21 | 6.79 |
Annual Sum or Average | 26.34 | 17.98 |
Minimum of Months | 25.21 | 6.79 |
Maximum of Months | 27.25 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.20 | 8.14 |
February | 21.63 | 10.27 |
March | 22.16 | 12.55 |
April | 22.96 | 19.23 |
May | 23.27 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.29 | 23.38 |
October | 22.99 | 18.30 |
November | 21.97 | 11.18 |
December | 21.03 | 6.79 |
Annual Sum or Average | 22.54 | 17.98 |
Minimum of Months | 21.03 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 8.14 |
February | 21.29 | 10.27 |
March | 21.85 | 12.55 |
April | 22.79 | 19.23 |
May | 23.20 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.32 | 26.28 |
September | 23.22 | 23.38 |
October | 22.80 | 18.30 |
November | 21.64 | 11.18 |
December | 20.66 | 6.79 |
Annual Sum or Average | 22.36 | 17.98 |
Minimum of Months | 20.66 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.32 | 8.14 |
February | 21.45 | 10.27 |
March | 21.55 | 12.55 |
April | 21.71 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.75 | 26.28 |
September | 21.75 | 23.38 |
October | 21.73 | 18.30 |
November | 21.55 | 11.18 |
December | 21.31 | 6.79 |
Annual Sum or Average | 21.62 | 17.98 |
Minimum of Months | 21.31 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 8.14 |
February | 21.63 | 10.27 |
March | 21.69 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.67 | 11.18 |
December | 21.52 | 6.79 |
Annual Sum or Average | 21.69 | 17.98 |
Minimum of Months | 21.52 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 8.14 |
February | 21.74 | 10.27 |
March | 21.74 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.74 | 11.18 |
December | 21.70 | 6.79 |
Annual Sum or Average | 21.74 | 17.98 |
Minimum of Months | 21.70 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.75 | 8.14 |
February | 22.75 | 10.27 |
March | 22.79 | 12.55 |
April | 22.68 | 19.23 |
May | 22.45 | 23.84 |
June | 22.18 | 27.86 |
July | 22.19 | 27.54 |
August | 22.29 | 26.28 |
September | 22.43 | 23.38 |
October | 22.79 | 18.30 |
November | 22.79 | 11.18 |
December | 22.65 | 6.79 |
Annual Sum or Average | 22.56 | 17.98 |
Minimum of Months | 22.18 | 6.79 |
Maximum of Months | 22.79 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.48 | 8.14 |
February | 51.71 | 10.27 |
March | 51.98 | 12.55 |
April | 52.66 | 19.23 |
May | 53.15 | 23.84 |
June | 53.71 | 27.86 |
July | 53.76 | 27.54 |
August | 53.62 | 26.28 |
September | 53.43 | 23.38 |
October | 52.71 | 18.30 |
November | 51.92 | 11.18 |
December | 51.50 | 6.79 |
Annual Sum or Average | 52.64 | 17.98 |
Minimum of Months | 51.48 | 6.79 |
Maximum of Months | 53.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.69 | 8.14 |
February | 69.88 | 10.27 |
March | 70.08 | 12.55 |
April | 70.88 | 19.23 |
May | 71.44 | 23.84 |
June | 72.28 | 27.86 |
July | 72.43 | 27.54 |
August | 72.28 | 26.28 |
September | 72.18 | 23.38 |
October | 71.20 | 18.30 |
November | 70.20 | 11.18 |
December | 69.82 | 6.79 |
Annual Sum or Average | 71.03 | 17.98 |
Minimum of Months | 69.69 | 6.79 |
Maximum of Months | 72.43 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.38 | 8.14 |
February | 23.49 | 10.27 |
March | 23.63 | 12.55 |
April | 23.84 | 19.23 |
May | 23.89 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.89 | 23.38 |
October | 23.87 | 18.30 |
November | 23.57 | 11.18 |
December | 23.29 | 6.79 |
Annual Sum or Average | 23.71 | 17.98 |
Minimum of Months | 23.29 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 8.14 |
February | 23.48 | 10.27 |
March | 23.66 | 12.55 |
April | 23.86 | 19.23 |
May | 23.89 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.89 | 23.38 |
October | 23.88 | 18.30 |
November | 23.60 | 11.18 |
December | 23.19 | 6.79 |
Annual Sum or Average | 23.71 | 17.98 |
Minimum of Months | 23.19 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.56 | 8.14 |
February | 20.23 | 10.27 |
March | 21.08 | 12.55 |
April | 23.56 | 19.23 |
May | 25.44 | 23.84 |
June | 27.05 | 27.86 |
July | 26.91 | 27.54 |
August | 26.42 | 26.28 |
September | 25.55 | 23.38 |
October | 23.45 | 18.30 |
November | 20.89 | 11.18 |
December | 19.65 | 6.79 |
Annual Sum or Average | 23.33 | 17.98 |
Minimum of Months | 19.56 | 6.79 |
Maximum of Months | 27.05 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 8.14 |
February | 22.14 | 10.27 |
March | 22.69 | 12.55 |
April | 24.07 | 19.23 |
May | 25.12 | 23.84 |
June | 26.00 | 27.86 |
July | 25.93 | 27.54 |
August | 25.67 | 26.28 |
September | 25.18 | 23.38 |
October | 24.04 | 18.30 |
November | 22.56 | 11.18 |
December | 21.71 | 6.79 |
Annual Sum or Average | 23.91 | 17.98 |
Minimum of Months | 21.71 | 6.79 |
Maximum of Months | 26.00 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | 8.14 |
February | 21.21 | 10.27 |
March | 21.82 | 12.55 |
April | 24.12 | 19.23 |
May | 25.72 | 23.84 |
June | 27.19 | 27.86 |
July | 27.05 | 27.54 |
August | 26.75 | 26.28 |
September | 26.22 | 23.38 |
October | 24.32 | 18.30 |
November | 21.96 | 11.18 |
December | 20.77 | 6.79 |
Annual Sum or Average | 23.99 | 17.98 |
Minimum of Months | 20.59 | 6.79 |
Maximum of Months | 27.19 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 8.14 |
February | 23.36 | 10.27 |
March | 23.62 | 12.55 |
April | 23.86 | 19.23 |
May | 23.90 | 23.84 |
June | 24.04 | 27.86 |
July | 24.05 | 27.54 |
August | 23.96 | 26.28 |
September | 23.90 | 23.38 |
October | 23.88 | 18.30 |
November | 23.54 | 11.18 |
December | 22.98 | 6.79 |
Annual Sum or Average | 23.68 | 17.98 |
Minimum of Months | 22.98 | 6.79 |
Maximum of Months | 24.05 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.22 | 8.14 |
February | 19.87 | 10.27 |
March | 20.61 | 12.55 |
April | 23.04 | 19.23 |
May | 24.75 | 23.84 |
June | 26.21 | 27.86 |
July | 26.05 | 27.54 |
August | 25.72 | 26.28 |
September | 25.12 | 23.38 |
October | 23.26 | 18.30 |
November | 20.71 | 11.18 |
December | 19.31 | 6.79 |
Annual Sum or Average | 22.84 | 17.98 |
Minimum of Months | 19.22 | 6.79 |
Maximum of Months | 26.21 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.15 | 8.14 |
February | 20.90 | 10.27 |
March | 21.74 | 12.55 |
April | 22.96 | 19.23 |
May | 23.30 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.30 | 23.38 |
October | 22.97 | 18.30 |
November | 21.32 | 11.18 |
December | 19.92 | 6.79 |
Annual Sum or Average | 22.22 | 17.98 |
Minimum of Months | 19.92 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.48 | 8.14 |
February | 21.60 | 10.27 |
March | 21.69 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.65 | 11.18 |
December | 21.44 | 6.79 |
Annual Sum or Average | 21.68 | 17.98 |
Minimum of Months | 21.44 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 8.14 |
February | 21.64 | 10.27 |
March | 21.71 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.68 | 11.18 |
December | 21.50 | 6.79 |
Annual Sum or Average | 21.70 | 17.98 |
Minimum of Months | 21.50 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 8.14 |
February | 21.65 | 10.27 |
March | 21.71 | 12.55 |
April | 21.75 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.69 | 11.18 |
December | 21.54 | 6.79 |
Annual Sum or Average | 21.70 | 17.98 |
Minimum of Months | 21.54 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.35 | 8.14 |
February | 21.49 | 10.27 |
March | 21.61 | 12.55 |
April | 21.73 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.59 | 11.18 |
December | 21.32 | 6.79 |
Annual Sum or Average | 21.64 | 17.98 |
Minimum of Months | 21.32 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 8.14 |
February | 21.69 | 10.27 |
March | 21.73 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.70 | 11.18 |
December | 21.60 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.60 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.29 | 8.14 |
February | 23.30 | 10.27 |
March | 23.32 | 12.55 |
April | 23.33 | 19.23 |
May | 23.33 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.33 | 23.38 |
October | 23.33 | 18.30 |
November | 23.33 | 11.18 |
December | 23.27 | 6.79 |
Annual Sum or Average | 23.32 | 17.98 |
Minimum of Months | 23.27 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 31.67 | 8.14 |
February | 31.95 | 10.27 |
March | 32.26 | 12.55 |
April | 33.06 | 19.23 |
May | 33.58 | 23.84 |
June | 34.18 | 27.86 |
July | 34.25 | 27.54 |
August | 34.08 | 26.28 |
September | 33.89 | 23.38 |
October | 33.17 | 18.30 |
November | 32.23 | 11.18 |
December | 31.68 | 6.79 |
Annual Sum or Average | 33.00 | 17.98 |
Minimum of Months | 31.67 | 6.79 |
Maximum of Months | 34.25 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 8.14 |
February | 22.14 | 10.27 |
March | 22.26 | 12.55 |
April | 22.65 | 19.23 |
May | 23.06 | 23.84 |
June | 23.57 | 27.86 |
July | 23.80 | 27.54 |
August | 23.53 | 26.28 |
September | 23.23 | 23.38 |
October | 22.73 | 18.30 |
November | 22.21 | 11.18 |
December | 22.00 | 6.79 |
Annual Sum or Average | 22.77 | 17.98 |
Minimum of Months | 22.00 | 6.79 |
Maximum of Months | 23.80 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 8.14 |
February | 21.73 | 10.27 |
March | 21.74 | 12.55 |
April | 21.76 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.73 | 11.18 |
December | 21.66 | 6.79 |
Annual Sum or Average | 21.74 | 17.98 |
Minimum of Months | 21.66 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 8.14 |
February | 21.69 | 10.27 |
March | 21.73 | 12.55 |
April | 21.76 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.70 | 11.18 |
December | 21.57 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.57 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 8.14 |
February | 21.81 | 10.27 |
March | 22.50 | 12.55 |
April | 24.30 | 19.23 |
May | 25.60 | 23.84 |
June | 26.67 | 27.86 |
July | 26.53 | 27.54 |
August | 26.24 | 26.28 |
September | 25.67 | 23.38 |
October | 24.22 | 18.30 |
November | 22.29 | 11.18 |
December | 21.22 | 6.79 |
Annual Sum or Average | 24.04 | 17.98 |
Minimum of Months | 21.22 | 6.79 |
Maximum of Months | 26.67 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.28 | 8.14 |
February | 20.12 | 10.27 |
March | 21.18 | 12.55 |
April | 24.24 | 19.23 |
May | 26.50 | 23.84 |
June | 28.47 | 27.86 |
July | 28.27 | 27.54 |
August | 27.72 | 26.28 |
September | 26.73 | 23.38 |
October | 24.11 | 18.30 |
November | 20.92 | 11.18 |
December | 19.36 | 6.79 |
Annual Sum or Average | 23.93 | 17.98 |
Minimum of Months | 19.28 | 6.79 |
Maximum of Months | 28.47 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.01 | 8.14 |
February | 20.76 | 10.27 |
March | 21.51 | 12.55 |
April | 24.14 | 19.23 |
May | 25.91 | 23.84 |
June | 27.52 | 27.86 |
July | 27.36 | 27.54 |
August | 27.03 | 26.28 |
September | 26.44 | 23.38 |
October | 24.29 | 18.30 |
November | 21.56 | 11.18 |
December | 20.15 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 20.01 | 6.79 |
Maximum of Months | 27.52 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 8.14 |
February | 22.38 | 10.27 |
March | 22.92 | 12.55 |
April | 23.69 | 19.23 |
May | 23.87 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.88 | 23.38 |
October | 23.71 | 18.30 |
November | 22.66 | 11.18 |
December | 21.72 | 6.79 |
Annual Sum or Average | 23.20 | 17.98 |
Minimum of Months | 21.72 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.31 | 8.14 |
February | 19.15 | 10.27 |
March | 20.12 | 12.55 |
April | 23.05 | 19.23 |
May | 25.00 | 23.84 |
June | 26.62 | 27.86 |
July | 26.45 | 27.54 |
August | 26.08 | 26.28 |
September | 25.39 | 23.38 |
October | 23.22 | 18.30 |
November | 20.09 | 11.18 |
December | 18.33 | 6.79 |
Annual Sum or Average | 22.67 | 17.98 |
Minimum of Months | 18.31 | 6.79 |
Maximum of Months | 26.62 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | 8.14 |
February | 20.28 | 10.27 |
March | 21.20 | 12.55 |
April | 22.77 | 19.23 |
May | 23.25 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.27 | 23.38 |
October | 22.74 | 18.30 |
November | 20.68 | 11.18 |
December | 19.34 | 6.79 |
Annual Sum or Average | 21.92 | 17.98 |
Minimum of Months | 19.34 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | 8.14 |
February | 20.74 | 10.27 |
March | 21.66 | 12.55 |
April | 22.96 | 19.23 |
May | 23.30 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.30 | 23.38 |
October | 22.94 | 18.30 |
November | 21.13 | 11.18 |
December | 19.69 | 6.79 |
Annual Sum or Average | 22.14 | 17.98 |
Minimum of Months | 19.69 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.16 | 8.14 |
February | 20.92 | 10.27 |
March | 21.78 | 12.55 |
April | 22.97 | 19.23 |
May | 23.30 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.30 | 23.38 |
October | 22.95 | 18.30 |
November | 21.29 | 11.18 |
December | 19.89 | 6.79 |
Annual Sum or Average | 22.22 | 17.98 |
Minimum of Months | 19.89 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 8.14 |
February | 21.60 | 10.27 |
March | 21.67 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.75 | 18.30 |
November | 21.65 | 11.18 |
December | 21.45 | 6.79 |
Annual Sum or Average | 21.68 | 17.98 |
Minimum of Months | 21.45 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.09 | 8.14 |
February | 20.81 | 10.27 |
March | 21.60 | 12.55 |
April | 22.90 | 19.23 |
May | 23.29 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.31 | 23.38 |
October | 22.94 | 18.30 |
November | 21.27 | 11.18 |
December | 19.89 | 6.79 |
Annual Sum or Average | 22.18 | 17.98 |
Minimum of Months | 19.89 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 8.14 |
February | 21.60 | 10.27 |
March | 21.69 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.64 | 11.18 |
December | 21.44 | 6.79 |
Annual Sum or Average | 21.68 | 17.98 |
Minimum of Months | 21.44 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 8.14 |
February | 21.73 | 10.27 |
March | 21.74 | 12.55 |
April | 21.76 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.73 | 11.18 |
December | 21.66 | 6.79 |
Annual Sum or Average | 21.74 | 17.98 |
Minimum of Months | 21.66 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.59 | 8.14 |
February | 24.06 | 10.27 |
March | 24.56 | 12.55 |
April | 25.65 | 19.23 |
May | 26.28 | 23.84 |
June | 26.79 | 27.86 |
July | 26.75 | 27.54 |
August | 26.60 | 26.28 |
September | 26.36 | 23.38 |
October | 25.62 | 18.30 |
November | 24.37 | 11.18 |
December | 23.53 | 6.79 |
Annual Sum or Average | 25.35 | 17.98 |
Minimum of Months | 23.53 | 6.79 |
Maximum of Months | 26.79 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 8.14 |
February | 22.78 | 10.27 |
March | 23.07 | 12.55 |
April | 23.31 | 19.23 |
May | 23.33 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.33 | 23.38 |
October | 23.32 | 18.30 |
November | 22.92 | 11.18 |
December | 22.24 | 6.79 |
Annual Sum or Average | 23.06 | 17.98 |
Minimum of Months | 22.24 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 8.14 |
February | 21.69 | 10.27 |
March | 21.73 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.70 | 11.18 |
December | 21.57 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.57 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 8.14 |
February | 21.53 | 10.27 |
March | 22.21 | 12.55 |
April | 23.11 | 19.23 |
May | 23.32 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.32 | 23.38 |
October | 23.08 | 18.30 |
November | 21.81 | 11.18 |
December | 20.58 | 6.79 |
Annual Sum or Average | 22.49 | 17.98 |
Minimum of Months | 20.58 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.43 | 8.14 |
February | 21.19 | 10.27 |
March | 22.10 | 12.55 |
April | 24.33 | 19.23 |
May | 25.84 | 23.84 |
June | 27.05 | 27.86 |
July | 26.89 | 27.54 |
August | 26.56 | 26.28 |
September | 25.92 | 23.38 |
October | 24.19 | 18.30 |
November | 21.75 | 11.18 |
December | 20.35 | 6.79 |
Annual Sum or Average | 23.90 | 17.98 |
Minimum of Months | 20.35 | 6.79 |
Maximum of Months | 27.05 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.62 | 8.14 |
February | 19.61 | 10.27 |
March | 20.84 | 12.55 |
April | 24.29 | 19.23 |
May | 26.77 | 23.84 |
June | 28.92 | 27.86 |
July | 28.71 | 27.54 |
August | 28.12 | 26.28 |
September | 27.05 | 23.38 |
October | 24.12 | 18.30 |
November | 20.47 | 11.18 |
December | 18.65 | 6.79 |
Annual Sum or Average | 23.87 | 17.98 |
Minimum of Months | 18.62 | 6.79 |
Maximum of Months | 28.92 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.02 | 8.14 |
February | 20.00 | 10.27 |
March | 20.96 | 12.55 |
April | 24.14 | 19.23 |
May | 26.17 | 23.84 |
June | 28.05 | 27.86 |
July | 27.89 | 27.54 |
August | 27.47 | 26.28 |
September | 26.72 | 23.38 |
October | 24.16 | 18.30 |
November | 20.81 | 11.18 |
December | 19.05 | 6.79 |
Annual Sum or Average | 23.72 | 17.98 |
Minimum of Months | 19.02 | 6.79 |
Maximum of Months | 28.05 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 8.14 |
February | 22.02 | 10.27 |
March | 22.44 | 12.55 |
April | 23.33 | 19.23 |
May | 23.81 | 23.84 |
June | 24.16 | 27.86 |
July | 24.15 | 27.54 |
August | 24.05 | 26.28 |
September | 23.85 | 23.38 |
October | 23.25 | 18.30 |
November | 22.17 | 11.18 |
December | 21.55 | 6.79 |
Annual Sum or Average | 23.04 | 17.98 |
Minimum of Months | 21.55 | 6.79 |
Maximum of Months | 24.16 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.58 | 8.14 |
February | 18.58 | 10.27 |
March | 19.69 | 12.55 |
April | 23.05 | 19.23 |
May | 25.22 | 23.84 |
June | 27.10 | 27.86 |
July | 26.92 | 27.54 |
August | 26.46 | 26.28 |
September | 25.61 | 23.38 |
October | 23.07 | 18.30 |
November | 19.48 | 11.18 |
December | 17.53 | 6.79 |
Annual Sum or Average | 22.54 | 17.98 |
Minimum of Months | 17.53 | 6.79 |
Maximum of Months | 27.10 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 8.14 |
February | 21.33 | 10.27 |
March | 21.49 | 12.55 |
April | 21.71 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.72 | 18.30 |
November | 21.42 | 11.18 |
December | 21.06 | 6.79 |
Annual Sum or Average | 21.55 | 17.98 |
Minimum of Months | 21.06 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.66 | 8.14 |
February | 20.33 | 10.27 |
March | 21.09 | 12.55 |
April | 22.56 | 19.23 |
May | 23.16 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.32 | 26.28 |
September | 23.15 | 23.38 |
October | 22.45 | 18.30 |
November | 20.58 | 11.18 |
December | 19.52 | 6.79 |
Annual Sum or Average | 21.88 | 17.98 |
Minimum of Months | 19.52 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.77 | 8.14 |
February | 20.41 | 10.27 |
March | 21.14 | 12.55 |
April | 22.56 | 19.23 |
May | 23.15 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.32 | 26.28 |
September | 23.14 | 23.38 |
October | 22.45 | 18.30 |
November | 20.65 | 11.18 |
December | 19.62 | 6.79 |
Annual Sum or Average | 21.91 | 17.98 |
Minimum of Months | 19.62 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 8.14 |
February | 21.62 | 10.27 |
March | 21.69 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.65 | 11.18 |
December | 21.48 | 6.79 |
Annual Sum or Average | 21.69 | 17.98 |
Minimum of Months | 21.48 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.80 | 8.14 |
February | 20.45 | 10.27 |
March | 21.13 | 12.55 |
April | 22.57 | 19.23 |
May | 23.16 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.32 | 26.28 |
September | 23.19 | 23.38 |
October | 22.53 | 18.30 |
November | 20.76 | 11.18 |
December | 19.68 | 6.79 |
Annual Sum or Average | 21.94 | 17.98 |
Minimum of Months | 19.68 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.28 | 8.14 |
February | 20.99 | 10.27 |
March | 21.60 | 12.55 |
April | 22.79 | 19.23 |
May | 23.23 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.25 | 23.38 |
October | 22.73 | 18.30 |
November | 21.20 | 11.18 |
December | 20.12 | 6.79 |
Annual Sum or Average | 22.19 | 17.98 |
Minimum of Months | 20.12 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 8.14 |
February | 21.71 | 10.27 |
March | 21.74 | 12.55 |
April | 21.76 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.70 | 11.18 |
December | 21.63 | 6.79 |
Annual Sum or Average | 21.73 | 17.98 |
Minimum of Months | 21.63 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.42 | 8.14 |
February | 21.99 | 10.27 |
March | 22.61 | 12.55 |
April | 24.08 | 19.23 |
May | 24.96 | 23.84 |
June | 25.70 | 27.86 |
July | 25.61 | 27.54 |
August | 25.37 | 26.28 |
September | 24.93 | 23.38 |
October | 23.83 | 18.30 |
November | 22.25 | 11.18 |
December | 21.28 | 6.79 |
Annual Sum or Average | 23.68 | 17.98 |
Minimum of Months | 21.28 | 6.79 |
Maximum of Months | 25.70 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 8.14 |
February | 21.70 | 10.27 |
March | 21.73 | 12.55 |
April | 21.76 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.69 | 11.18 |
December | 21.60 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.60 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 8.14 |
February | 21.71 | 10.27 |
March | 21.74 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.69 | 11.18 |
December | 21.62 | 6.79 |
Annual Sum or Average | 21.73 | 17.98 |
Minimum of Months | 21.62 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 8.14 |
February | 21.64 | 10.27 |
March | 21.71 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.65 | 11.18 |
December | 21.47 | 6.79 |
Annual Sum or Average | 21.69 | 17.98 |
Minimum of Months | 21.47 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.03 | 8.14 |
February | 20.86 | 10.27 |
March | 21.83 | 12.55 |
April | 24.31 | 19.23 |
May | 25.96 | 23.84 |
June | 27.37 | 27.86 |
July | 27.21 | 27.54 |
August | 26.79 | 26.28 |
September | 26.01 | 23.38 |
October | 24.01 | 18.30 |
November | 21.36 | 11.18 |
December | 19.86 | 6.79 |
Annual Sum or Average | 23.81 | 17.98 |
Minimum of Months | 19.86 | 6.79 |
Maximum of Months | 27.37 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.00 | 8.14 |
February | 19.12 | 10.27 |
March | 20.46 | 12.55 |
April | 24.28 | 19.23 |
May | 26.92 | 23.84 |
June | 29.33 | 27.86 |
July | 29.11 | 27.54 |
August | 28.42 | 26.28 |
September | 27.22 | 23.38 |
October | 23.95 | 18.30 |
November | 19.94 | 11.18 |
December | 17.92 | 6.79 |
Annual Sum or Average | 23.74 | 17.98 |
Minimum of Months | 17.92 | 6.79 |
Maximum of Months | 29.33 | 27.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:33
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.151661E+12 | 104511.650 | 27-JAN-07:15 | 17938.631 | 34285.948 | 9572.585 | 42431.939 | 274.434 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.138678E+12 | 108207.546 | 02-FEB-07:15 | 20847.837 | 39740.848 | 9572.585 | 37255.432 | 782.730 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.154902E+12 | 102686.602 | 02-MAR-07:15 | 20847.837 | 39740.848 | 9572.585 | 31195.013 | 1322.206 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.162343E+12 | 100546.434 | 29-APR-07:00 | 25182.171 | 43578.554 | 10173.926 | 0.000 | 21603.671 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.181768E+12 | 105074.665 | 28-MAY-07:00 | 25182.171 | 43578.554 | 10173.926 | 0.000 | 26131.902 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.190793E+12 | 109186.777 | 05-JUN-19:15 | 27551.975 | 28549.175 | 9679.009 | 0.000 | 39210.505 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.204130E+12 | 112111.879 | 28-JUL-07:00 | 25182.171 | 43578.554 | 10173.926 | 0.000 | 33169.115 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.195704E+12 | 109462.514 | 04-AUG-07:00 | 25182.171 | 43578.554 | 10173.926 | 0.000 | 30519.750 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.181079E+12 | 108333.681 | 15-SEP-07:00 | 25182.171 | 43578.554 | 10173.926 | 0.000 | 29390.917 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.168843E+12 | 99427.125 | 04-OCT-19:15 | 27551.975 | 28549.175 | 9638.750 | 0.000 | 29491.112 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.149122E+12 | 98626.803 | 28-NOV-07:15 | 20847.837 | 39740.848 | 9572.585 | 26376.190 | 2081.230 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.153343E+12 | 110227.495 | 27-DEC-07:15 | 20847.837 | 39740.848 | 9572.585 | 39499.558 | 558.554 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.203237E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.138678E+12 | 98626.803 | 17938.631 | 28549.175 | 9572.585 | 0.000 | 274.434 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.204130E+12 | 112111.879 | 27551.975 | 43578.554 | 10173.926 | 42431.939 | 39210.505 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:33
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.899748E+11 | 92859.222 | 27-JAN-09:15 | 428.569 | 40096.028 | 0.000 | 52334.625 | 52334.625 | 52334.625 | 428.569 |
February | 0.807551E+11 | 92483.426 | 24-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 52387.398 | 52387.398 | 52387.398 | 0.000 |
March | 0.866398E+11 | 94051.177 | 04-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 53955.149 | 53955.149 | 53955.149 | 0.000 |
April | 0.799340E+11 | 85930.407 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 45834.379 | 45834.379 | 45834.379 | 0.000 |
May | 0.787144E+11 | 83170.936 | 06-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 43074.908 | 43074.908 | 43074.908 | 0.000 |
June | 0.729434E+11 | 81583.890 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 41487.862 | 41487.862 | 41487.862 | 0.000 |
July | 0.734582E+11 | 80754.642 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 40658.614 | 40658.614 | 40658.614 | 0.000 |
August | 0.735043E+11 | 81015.538 | 18-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 40919.510 | 40919.510 | 40919.510 | 0.000 |
September | 0.729358E+11 | 81555.538 | 16-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 41459.510 | 41459.510 | 41459.510 | 0.000 |
October | 0.787487E+11 | 82607.685 | 28-OCT-08:45 | 0.000 | 40096.028 | 0.000 | 42511.657 | 42511.657 | 42511.657 | 0.000 |
November | 0.810345E+11 | 84748.176 | 25-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 44652.148 | 44652.148 | 44652.148 | 0.000 |
December | 0.890852E+11 | 88313.131 | 27-DEC-10:15 | 3079.345 | 40096.028 | 0.000 | 45137.759 | 45137.759 | 45137.759 | 3079.345 |
Annual Sum or Average | 0.957728E+12 | 0.000 | ||||||||
Minimum of Months | 0.729358E+11 | 80754.642 | 0.000 | 40096.028 | 0.000 | 40658.614 | 40658.614 | 40658.614 | 0.000 | |
Maximum of Months | 0.899748E+11 | 94051.177 | 3079.345 | 40096.028 | 0.000 | 53955.149 | 53955.149 | 53955.149 | 3079.345 |