Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Salem Mcnary Field OR USA TMY3 WMO#=726940
Simulation Timestamp: 2015-09-14 08:44:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2971.27 | 740.30 | 797.64 |
Net Site Energy | 2971.27 | 740.30 | 797.64 |
Total Source Energy | 7162.87 | 1784.66 | 1922.87 |
Net Source Energy | 7162.87 | 1784.66 | 1922.87 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 103.24 | 35.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 247.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 295.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 621.32 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1892.47 | 1078.80 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 103.24 | 35.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 247.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 295.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 621.32 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 173.58 | 176.46 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 508.03 | 289.60 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 161.11 | 163.77 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 471.52 | 268.79 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1892.47 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1892.47 | 100.00 |
Total On-Site and Utility Electric Sources | 1892.47 | 100.00 |
Total Electricity End Uses | 1892.47 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 123.25 |
Time Setpoint Not Met During Occupied Cooling | 3577.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4489.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Latitude [deg] | 44.90 |
Longitude [deg] | -123.0 |
Elevation [m] | 60.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00 | -5.60 | Wetbulb [C] | 2.10 | 0.00 |
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 15.40 | 19.40 | Wetbulb [C] | 4.30 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 8.38 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 175.82 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6290.86 | 4935.32 | 1355.54 | 0.78 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19678.41 | 14669.00 | 5009.40 | 0.75 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9556.94 | 6852.32 | 2704.62 | 0.72 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13176.91 | 10329.61 | 2847.30 | 0.78 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6007.3 | 3.18 | 10.84 | 11.48 | 10.66 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18889.0 | 2.95 | 10.05 | 10.66 | 10.09 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9208.1 | 3.30 | 11.26 | 11.93 | 11.28 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12583.9 | 3.18 | 10.84 | 11.48 | 10.67 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.16 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 29863.19 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 511.14 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 511.14 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 978.93 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.08 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.16 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2590.67 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 913.48 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3653.91 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2895.85 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3653.91 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1043.32 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 926.88 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3653.65 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3653.65 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.08 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.16 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2590.67 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 913.48 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3653.91 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2895.85 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3653.91 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 913.48 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1037.12 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3653.65 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3653.65 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.08 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.16 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 3598.79 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1327.69 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3653.91 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2895.85 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3848.62 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1028.18 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 913.41 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3772.37 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1064.04 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3653.65 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1249.78 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 319.08 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3761.30 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 15765.40 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 8442.26 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 6307.45 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.37 | 424.20 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.02 | 1159.14 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.45 | 521.34 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.76 | 871.17 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 10206.28 | 12247.54 | 0.847 | 1.017 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
RESTROOMFLR1 | 678.46 | 814.16 | 0.056 | 0.068 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 29.03 | 0.00850 |
MEETINGROOMFLR1 | 4505.77 | 5406.93 | 0.374 | 0.449 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
GUESTROOM101 | 556.09 | 667.31 | 0.049 | 0.059 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM102 | 424.50 | 509.40 | 0.037 | 0.045 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM103 | 1530.31 | 1836.37 | 0.177 | 0.212 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM104 | 1330.24 | 1596.29 | 0.153 | 0.184 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
GUESTROOM105 | 1785.83 | 2143.00 | 0.206 | 0.247 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
EMPLOYEELOUNGEFLR1 | 5678.74 | 6814.49 | 0.471 | 0.566 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
EXERCISECENTERFLR1 | 1315.14 | 1578.17 | 0.109 | 0.131 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.83 | 0.00850 |
FRONTOFFICEFLR1 | 3671.33 | 4405.59 | 0.305 | 0.365 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
GUESTROOM201 | 848.24 | 1017.88 | 0.075 | 0.089 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.37 | 0.00850 |
GUESTROOM202_205 | 6064.49 | 7277.39 | 0.700 | 0.839 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM206_208 | 4993.52 | 5992.23 | 0.576 | 0.691 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM209_212 | 5673.04 | 6807.65 | 0.654 | 0.785 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM213 | 1644.64 | 1973.56 | 0.190 | 0.228 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM214 | 1567.55 | 1881.06 | 0.181 | 0.217 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
GUESTROOM215_218 | 8690.29 | 10428.34 | 0.764 | 0.916 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
GUESTROOM219 | 5707.84 | 6849.41 | 0.658 | 0.790 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
GUESTROOM220_223 | 5325.58 | 6390.69 | 0.614 | 0.737 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
GUESTROOM224 | 1570.65 | 1884.78 | 0.181 | 0.217 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 28.60 | 0.00850 |
GUESTROOM301 | 707.39 | 848.87 | 0.062 | 0.075 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 30.76 | 0.00850 |
GUESTROOM302_305 | 2046.45 | 2455.74 | 0.180 | 0.216 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM306_308 | 1873.05 | 2247.66 | 0.165 | 0.198 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM309_312 | 5675.50 | 6810.60 | 0.655 | 0.786 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM313 | 695.54 | 834.64 | 0.061 | 0.073 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 29.99 | 0.00850 |
GUESTROOM314 | 1484.64 | 1781.57 | 0.171 | 0.205 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 29.76 | 0.00850 |
GUESTROOM315_318 | 5985.73 | 7182.88 | 0.690 | 0.828 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
GUESTROOM319 | 845.73 | 1014.88 | 0.074 | 0.089 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
GUESTROOM320_323 | 5129.63 | 6155.55 | 0.592 | 0.710 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
GUESTROOM324 | 502.73 | 603.28 | 0.044 | 0.053 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 29.18 | 0.00850 |
GUESTROOM401 | 2050.11 | 2460.13 | 0.236 | 0.284 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 31.45 | 0.00850 |
GUESTROOM402_405 | 2984.37 | 3581.24 | 0.262 | 0.315 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.14 | 0.00850 |
GUESTROOM406_408 | 2721.30 | 3265.57 | 0.239 | 0.287 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.14 | 0.00850 |
GUESTROOM409_412 | 6858.92 | 8230.70 | 0.791 | 0.949 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.14 | 0.00850 |
GUESTROOM413 | 1036.22 | 1243.47 | 0.091 | 0.109 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.14 | 0.00850 |
GUESTROOM414 | 779.86 | 935.83 | 0.069 | 0.082 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.30 | 0.00850 |
GUESTROOM415_418 | 6248.78 | 7498.54 | 0.721 | 0.865 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 29.76 | 0.00850 |
GUESTROOM419 | 1710.39 | 2052.47 | 0.197 | 0.237 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:30:00 | 30.53 | 0.00850 |
GUESTROOM420_423 | 6104.88 | 7325.85 | 0.704 | 0.845 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:15:00 | 30.14 | 0.00850 |
GUESTROOM424 | 1729.33 | 2075.19 | 0.199 | 0.239 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.30 | 0.00850 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
CORRIDORFLR1 | 17312.57 | 20775.08 | 1.436 | 1.723 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.60 | 0.00850 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
CORRIDORFLR2 | 2995.70 | 3594.85 | 0.248 | 0.298 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 32.07 | 0.00850 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
CORRIDORFLR3 | 1706.81 | 2048.17 | 0.142 | 0.170 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 31.45 | 0.00850 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 | |
CORRIDORFLR4 | 2660.11 | 3192.13 | 0.221 | 0.265 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.07 | 0.00850 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 33.30 | 0.00850 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1362.77 | 1635.32 | 0.039 | 0.236 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.60 | 0.00237 |
RESTROOMFLR1 | 1.47 | 1.77 | 0.000 | 0.000 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | -5.60 | 0.00237 |
MEETINGROOMFLR1 | 455.77 | 546.93 | 0.013 | 0.126 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -5.60 | 0.00237 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
GUESTROOM102 | 0.00 | 0.00 | 0.000 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
GUESTROOM103 | 450.07 | 540.09 | 0.013 | 0.015 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.60 | 0.00237 |
GUESTROOM104 | 357.85 | 429.43 | 0.010 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -5.60 | 0.00237 |
GUESTROOM105 | 256.97 | 308.36 | 0.007 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | -5.60 | 0.00237 |
EMPLOYEELOUNGEFLR1 | 229.78 | 275.73 | 0.007 | 0.051 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.60 | 0.00237 |
EXERCISECENTERFLR1 | 114.18 | 137.02 | 0.003 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.60 | 0.00237 |
FRONTOFFICEFLR1 | 800.19 | 960.23 | 0.023 | 0.056 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -5.60 | 0.00237 |
GUESTROOM201 | 168.82 | 202.58 | 0.004 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | -5.60 | 0.00237 |
GUESTROOM202_205 | 1060.33 | 1272.39 | 0.030 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -5.60 | 0.00237 |
GUESTROOM206_208 | 772.30 | 926.76 | 0.022 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.60 | 0.00237 |
GUESTROOM209_212 | 802.36 | 962.83 | 0.023 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.60 | 0.00237 |
GUESTROOM213 | 503.73 | 604.48 | 0.014 | 0.017 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -5.60 | 0.00237 |
GUESTROOM214 | 406.72 | 488.06 | 0.012 | 0.014 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | -5.60 | 0.00237 |
GUESTROOM215_218 | 3.56 | 4.27 | 0.000 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.60 | 0.00237 |
GUESTROOM219 | 212.63 | 255.15 | 0.006 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.60 | 0.00237 |
GUESTROOM220_223 | 683.97 | 820.77 | 0.019 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -5.60 | 0.00237 |
GUESTROOM224 | 365.19 | 438.23 | 0.010 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.60 | 0.00237 |
GUESTROOM301 | 237.72 | 285.27 | 0.006 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -5.60 | 0.00237 |
GUESTROOM302_305 | 425.63 | 510.75 | 0.011 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -5.60 | 0.00237 |
GUESTROOM306_308 | 330.32 | 396.38 | 0.009 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | -5.60 | 0.00237 |
GUESTROOM309_312 | 1020.81 | 1224.98 | 0.029 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:15:00 | -5.60 | 0.00237 |
GUESTROOM313 | 270.23 | 324.28 | 0.007 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | -5.60 | 0.00237 |
GUESTROOM314 | 498.59 | 598.31 | 0.014 | 0.017 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:15:00 | -5.60 | 0.00237 |
GUESTROOM315_318 | 1065.36 | 1278.43 | 0.030 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 13:45:00 | -5.60 | 0.00237 |
GUESTROOM319 | 14.53 | 17.44 | 0.000 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 12:45:00 | -5.60 | 0.00237 |
GUESTROOM320_323 | 898.31 | 1077.97 | 0.026 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -5.60 | 0.00237 |
GUESTROOM324 | 119.46 | 143.36 | 0.003 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | -5.60 | 0.00237 |
GUESTROOM401 | 740.70 | 888.84 | 0.021 | 0.025 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 21:30:00 | -5.60 | 0.00237 |
GUESTROOM402_405 | 1158.64 | 1390.37 | 0.031 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 21:00:00 | -5.60 | 0.00237 |
GUESTROOM406_408 | 958.09 | 1149.71 | 0.025 | 0.043 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.60 | 0.00237 |
GUESTROOM409_412 | 1744.35 | 2093.23 | 0.050 | 0.059 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 19:15:00 | -5.60 | 0.00237 |
GUESTROOM413 | 521.53 | 625.83 | 0.014 | 0.016 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 23:15:00 | -5.60 | 0.00237 |
GUESTROOM414 | 391.22 | 469.46 | 0.010 | 0.013 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 19:30:00 | -5.60 | 0.00237 |
GUESTROOM415_418 | 1680.92 | 2017.10 | 0.048 | 0.057 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -5.60 | 0.00237 |
GUESTROOM419 | 521.02 | 625.22 | 0.015 | 0.018 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 18:15:00 | -5.60 | 0.00237 |
GUESTROOM420_423 | 1573.48 | 1888.18 | 0.045 | 0.054 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.60 | 0.00237 |
GUESTROOM424 | 675.80 | 810.96 | 0.019 | 0.023 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.60 | 0.00237 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
CORRIDORFLR1 | 23628.19 | 28353.83 | 0.670 | 0.804 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -5.60 | 0.00237 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
CORRIDORFLR2 | 623.63 | 748.36 | 0.018 | 0.038 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -5.60 | 0.00237 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
CORRIDORFLR3 | 1020.91 | 1225.09 | 0.029 | 0.038 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -5.60 | 0.00237 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 | |
CORRIDORFLR4 | 1961.86 | 2354.23 | 0.056 | 0.067 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -5.60 | 0.00237 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | -5.60 | 0.00237 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.37 | 0.37 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.02 | 1.02 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.45 | 0.45 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.76 | 0.76 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 1.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1084.75 | 6719.75 | 146.50 |
RESTROOMFLR1 | 139.50 | 7448.75 | 15.00 |
MEETINGROOMFLR1 | 1160.50 | 2477.50 | 3.25 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 419.50 | 8758.25 | 419.50 |
GUESTROOM104 | 162.25 | 8759.00 | 162.25 |
GUESTROOM105 | 1.50 | 8567.50 | 1.50 |
EMPLOYEELOUNGEFLR1 | 3161.50 | 2132.00 | 271.25 |
EXERCISECENTERFLR1 | 1303.25 | 2437.00 | 4.00 |
FRONTOFFICEFLR1 | 728.00 | 6018.75 | 38.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 157.50 | 8614.75 | 157.50 |
GUESTROOM206_208 | 131.50 | 8576.25 | 131.00 |
GUESTROOM209_212 | 99.25 | 8675.75 | 99.25 |
GUESTROOM213 | 486.50 | 8737.75 | 486.50 |
GUESTROOM214 | 132.50 | 8570.25 | 132.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 4048.50 | 3824.25 | 265.75 |
GUESTROOM220_223 | 31.25 | 8306.75 | 31.25 |
GUESTROOM224 | 149.25 | 8505.00 | 149.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 167.00 | 8677.00 | 167.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 351.50 | 8596.50 | 351.50 |
GUESTROOM315_318 | 38.00 | 8183.25 | 38.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 109.50 | 8474.00 | 109.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 2070.50 | 8255.25 | 2017.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 691.00 | 7941.50 | 475.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 681.00 | 7704.00 | 277.50 |
GUESTROOM419 | 454.75 | 7904.75 | 337.25 |
GUESTROOM420_423 | 690.75 | 7740.75 | 318.00 |
GUESTROOM424 | 927.50 | 7996.25 | 821.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6183.75 | 8760.00 | 4489.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 14.50 | 575.25 | 14.50 | 575.25 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 4.50 | 39.25 | 4.50 | 39.25 |
GUESTROOM104 | 2.25 | 39.25 | 2.25 | 39.25 |
GUESTROOM105 | 0.00 | 60.00 | 0.00 | 60.00 |
EMPLOYEELOUNGEFLR1 | 122.00 | 1036.25 | 99.50 | 714.50 |
EXERCISECENTERFLR1 | 0.25 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.75 | 24.50 | 0.75 | 24.50 |
GUESTROOM206_208 | 0.00 | 34.50 | 0.00 | 34.50 |
GUESTROOM209_212 | 0.00 | 23.00 | 0.00 | 23.00 |
GUESTROOM213 | 4.50 | 24.00 | 4.50 | 24.00 |
GUESTROOM214 | 1.50 | 24.75 | 1.50 | 24.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2602.00 | 0.00 | 2602.00 |
GUESTROOM220_223 | 0.00 | 18.25 | 0.00 | 18.25 |
GUESTROOM224 | 1.50 | 25.00 | 1.50 | 25.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 2.25 | 23.00 | 2.25 | 23.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 4.50 | 22.75 | 4.50 | 22.75 |
GUESTROOM315_318 | 0.00 | 21.50 | 0.00 | 21.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1.50 | 16.50 | 1.50 | 16.50 |
GUESTROOM324 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 16.75 | 38.25 | 16.75 | 38.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 4.75 | 33.75 | 4.75 | 33.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 4.00 | 29.50 | 4.00 | 29.50 |
GUESTROOM419 | 4.00 | 33.00 | 4.00 | 33.00 |
GUESTROOM420_423 | 4.50 | 29.00 | 4.50 | 29.00 |
GUESTROOM424 | 7.75 | 31.75 | 7.75 | 31.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 4.50 | 2495.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 51.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 126.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 143.50 | 4464.00 | 123.25 | 3577.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:51
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.365422 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.02 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.764108 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 319.16 |
CORRIDORFLR1 PTAC HEATING COIL | 29863.19 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 511.14 |
102 PTAC HEATING COIL | 511.14 |
103 PTAC HEATING COIL | 978.93 |
104 PTAC HEATING COIL | 913.41 |
105 PTAC HEATING COIL | 913.41 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 319.08 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 319.16 |
CORRIDORFLR2 PTAC HEATING COIL | 2590.67 |
201 PTAC HEATING COIL | 913.48 |
202_205 PTAC HEATING COIL | 3653.91 |
206_208 PTAC HEATING COIL | 2895.85 |
209_212 PTAC HEATING COIL | 3653.91 |
213 PTAC HEATING COIL | 1043.32 |
214 PTAC HEATING COIL | 926.88 |
215_218 PTAC HEATING COIL | 3653.65 |
219 PTAC HEATING COIL | 913.41 |
220_223 PTAC HEATING COIL | 3653.65 |
224 PTAC HEATING COIL | 913.41 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 319.08 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 319.16 |
CORRIDORFLR3 PTAC HEATING COIL | 2590.67 |
301 PTAC HEATING COIL | 913.48 |
302_305 PTAC HEATING COIL | 3653.91 |
306_308 PTAC HEATING COIL | 2895.85 |
309_312 PTAC HEATING COIL | 3653.91 |
313 PTAC HEATING COIL | 913.48 |
314 PTAC HEATING COIL | 1037.12 |
315_318 PTAC HEATING COIL | 3653.65 |
319 PTAC HEATING COIL | 913.41 |
320_323 PTAC HEATING COIL | 3653.65 |
324 PTAC HEATING COIL | 913.41 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 319.08 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 319.16 |
CORRIDORFLR4 PTAC HEATING COIL | 3598.79 |
401 PTAC HEATING COIL | 1327.69 |
402_405 PTAC HEATING COIL | 3653.91 |
406_408 PTAC HEATING COIL | 2895.85 |
409_412 PTAC HEATING COIL | 3848.62 |
413 PTAC HEATING COIL | 1028.18 |
414 PTAC HEATING COIL | 913.41 |
415_418 PTAC HEATING COIL | 3772.37 |
419 PTAC HEATING COIL | 1064.04 |
420_423 PTAC HEATING COIL | 3653.65 |
424 PTAC HEATING COIL | 1249.78 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 319.08 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.784523 | 0.365422 | 6290.86 |
SAC_FRONTLOUNGE COOLING COIL | 0.745437 | 1.02 | 19678.41 |
SAC_MEETINGROOM COOLING COIL | 0.717000 | 0.449110 | 9556.94 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.783918 | 0.764108 | 13176.91 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.02 |
RESTROOMFLR1 DIRECT AIR | 0.067526 |
MEETINGROOMFLR1 DIRECT AIR | 0.449110 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.565631 |
EXERCISECENTERFLR1 DIRECT AIR | 0.130950 |
FRONTOFFICEFLR1 DIRECT AIR | 0.365422 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.365422 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.02 |
SAC_MEETINGROOM MAIN BRANCH | 0.449110 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.764108 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.365422 |
SAC_FRONTLOUNGE | 1.02 |
SAC_MEETINGROOM | 0.449110 |
SAC_EXC_EMPLGE_RESTRM | 0.764108 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.365422 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.02 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.449110 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.764108 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.365422 | 0.365422 | 0.365422 | 0.365422 | 3761.30 | 6290.86 | 1.00 |
SAC_FRONTLOUNGE | 1.02 | 1.02 | 1.02 | 1.02 | 15765.40 | 19678.41 | 1.00 |
SAC_MEETINGROOM | 0.449110 | 0.449110 | 0.449110 | 0.449110 | 8442.26 | 9556.94 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.764108 | 0.764108 | 0.764108 | 0.764108 | 6307.45 | 13176.91 | 0.171377 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3761.30 |
SAC_FRONTLOUNGE HEATING COIL | 15765.40 |
SAC_MEETINGROOM HEATING COIL | 8442.26 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 6307.45 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.449110 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.99 | 4.90 |
February | 18.05 | 5.21 |
March | 20.61 | 8.41 |
April | 20.64 | 10.40 |
May | 21.79 | 13.39 |
June | 23.01 | 17.41 |
July | 23.98 | 20.12 |
August | 23.89 | 19.46 |
September | 23.35 | 16.66 |
October | 21.55 | 11.27 |
November | 19.63 | 8.49 |
December | 18.19 | 4.55 |
Annual Sum or Average | 21.16 | 11.73 |
Minimum of Months | 18.05 | 4.55 |
Maximum of Months | 23.98 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.65 | 4.90 |
February | 22.55 | 5.21 |
March | 23.33 | 8.41 |
April | 23.62 | 10.40 |
May | 24.13 | 13.39 |
June | 24.89 | 17.41 |
July | 25.52 | 20.12 |
August | 25.34 | 19.46 |
September | 24.79 | 16.66 |
October | 23.74 | 11.27 |
November | 23.19 | 8.49 |
December | 22.51 | 4.55 |
Annual Sum or Average | 23.86 | 11.73 |
Minimum of Months | 22.51 | 4.55 |
Maximum of Months | 25.52 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.08 | 4.90 |
February | 17.24 | 5.21 |
March | 19.70 | 8.41 |
April | 19.82 | 10.40 |
May | 21.03 | 13.39 |
June | 22.31 | 17.41 |
July | 23.25 | 20.12 |
August | 23.15 | 19.46 |
September | 22.58 | 16.66 |
October | 20.73 | 11.27 |
November | 18.79 | 8.49 |
December | 17.35 | 4.55 |
Annual Sum or Average | 20.36 | 11.73 |
Minimum of Months | 17.24 | 4.55 |
Maximum of Months | 23.25 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 4.90 |
February | 21.30 | 5.21 |
March | 21.56 | 8.41 |
April | 21.89 | 10.40 |
May | 22.48 | 13.39 |
June | 22.97 | 17.41 |
July | 23.28 | 20.12 |
August | 23.24 | 19.46 |
September | 22.90 | 16.66 |
October | 21.99 | 11.27 |
November | 21.40 | 8.49 |
December | 21.24 | 4.55 |
Annual Sum or Average | 22.13 | 11.73 |
Minimum of Months | 21.19 | 4.55 |
Maximum of Months | 23.28 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 4.90 |
February | 22.21 | 5.21 |
March | 22.60 | 8.41 |
April | 22.75 | 10.40 |
May | 23.08 | 13.39 |
June | 23.41 | 17.41 |
July | 23.55 | 20.12 |
August | 23.54 | 19.46 |
September | 23.37 | 16.66 |
October | 22.87 | 11.27 |
November | 22.53 | 8.49 |
December | 22.18 | 4.55 |
Annual Sum or Average | 22.86 | 11.73 |
Minimum of Months | 22.18 | 4.55 |
Maximum of Months | 23.55 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 4.90 |
February | 21.96 | 5.21 |
March | 22.75 | 8.41 |
April | 23.09 | 10.40 |
May | 23.53 | 13.39 |
June | 23.75 | 17.41 |
July | 23.82 | 20.12 |
August | 23.82 | 19.46 |
September | 23.74 | 16.66 |
October | 23.22 | 11.27 |
November | 22.50 | 8.49 |
December | 21.85 | 4.55 |
Annual Sum or Average | 23.00 | 11.73 |
Minimum of Months | 21.85 | 4.55 |
Maximum of Months | 23.82 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.53 | 4.90 |
February | 24.53 | 5.21 |
March | 25.27 | 8.41 |
April | 25.55 | 10.40 |
May | 26.03 | 13.39 |
June | 26.46 | 17.41 |
July | 26.71 | 20.12 |
August | 26.65 | 19.46 |
September | 26.39 | 16.66 |
October | 25.68 | 11.27 |
November | 25.02 | 8.49 |
December | 24.44 | 4.55 |
Annual Sum or Average | 25.61 | 11.73 |
Minimum of Months | 24.44 | 4.55 |
Maximum of Months | 26.71 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.95 | 4.90 |
February | 20.04 | 5.21 |
March | 21.06 | 8.41 |
April | 21.54 | 10.40 |
May | 22.25 | 13.39 |
June | 22.84 | 17.41 |
July | 23.08 | 20.12 |
August | 23.07 | 19.46 |
September | 22.75 | 16.66 |
October | 21.73 | 11.27 |
November | 20.78 | 8.49 |
December | 19.94 | 4.55 |
Annual Sum or Average | 21.59 | 11.73 |
Minimum of Months | 19.94 | 4.55 |
Maximum of Months | 23.08 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | 4.90 |
February | 19.74 | 5.21 |
March | 20.69 | 8.41 |
April | 21.18 | 10.40 |
May | 21.94 | 13.39 |
June | 22.60 | 17.41 |
July | 22.91 | 20.12 |
August | 22.90 | 19.46 |
September | 22.50 | 16.66 |
October | 21.38 | 11.27 |
November | 20.40 | 8.49 |
December | 19.63 | 4.55 |
Annual Sum or Average | 21.30 | 11.73 |
Minimum of Months | 19.61 | 4.55 |
Maximum of Months | 22.91 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 4.90 |
February | 20.91 | 5.21 |
March | 21.23 | 8.41 |
April | 21.36 | 10.40 |
May | 21.59 | 13.39 |
June | 21.72 | 17.41 |
July | 21.74 | 20.12 |
August | 21.74 | 19.46 |
September | 21.71 | 16.66 |
October | 21.46 | 11.27 |
November | 21.16 | 8.49 |
December | 20.86 | 4.55 |
Annual Sum or Average | 21.37 | 11.73 |
Minimum of Months | 20.86 | 4.55 |
Maximum of Months | 21.74 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 4.90 |
February | 21.10 | 5.21 |
March | 21.44 | 8.41 |
April | 21.54 | 10.40 |
May | 21.69 | 13.39 |
June | 21.74 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.74 | 16.66 |
October | 21.59 | 11.27 |
November | 21.33 | 8.49 |
December | 21.03 | 4.55 |
Annual Sum or Average | 21.49 | 11.73 |
Minimum of Months | 21.03 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.50 | 4.90 |
February | 21.48 | 5.21 |
March | 21.68 | 8.41 |
April | 21.71 | 10.40 |
May | 21.74 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.75 | 16.66 |
October | 21.71 | 11.27 |
November | 21.65 | 8.49 |
December | 21.44 | 4.55 |
Annual Sum or Average | 21.66 | 11.73 |
Minimum of Months | 21.44 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 4.90 |
February | 22.59 | 5.21 |
March | 22.60 | 8.41 |
April | 22.56 | 10.40 |
May | 22.60 | 13.39 |
June | 22.62 | 17.41 |
July | 22.50 | 20.12 |
August | 22.59 | 19.46 |
September | 22.64 | 16.66 |
October | 22.65 | 11.27 |
November | 22.74 | 8.49 |
December | 22.61 | 4.55 |
Annual Sum or Average | 22.61 | 11.73 |
Minimum of Months | 22.50 | 4.55 |
Maximum of Months | 22.74 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.02 | 4.90 |
February | 50.83 | 5.21 |
March | 51.69 | 8.41 |
April | 51.83 | 10.40 |
May | 52.27 | 13.39 |
June | 52.71 | 17.41 |
July | 53.09 | 20.12 |
August | 53.02 | 19.46 |
September | 52.72 | 16.66 |
October | 51.97 | 11.27 |
November | 51.31 | 8.49 |
December | 50.77 | 4.55 |
Annual Sum or Average | 51.94 | 11.73 |
Minimum of Months | 50.77 | 4.55 |
Maximum of Months | 53.09 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.10 | 4.90 |
February | 68.56 | 5.21 |
March | 70.00 | 8.41 |
April | 69.97 | 10.40 |
May | 70.51 | 13.39 |
June | 71.00 | 17.41 |
July | 71.52 | 20.12 |
August | 71.48 | 19.46 |
September | 71.23 | 16.66 |
October | 70.36 | 11.27 |
November | 69.33 | 8.49 |
December | 68.61 | 4.55 |
Annual Sum or Average | 70.15 | 11.73 |
Minimum of Months | 68.56 | 4.55 |
Maximum of Months | 71.52 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.06 | 4.90 |
February | 23.03 | 5.21 |
March | 23.30 | 8.41 |
April | 23.37 | 10.40 |
May | 23.56 | 13.39 |
June | 23.77 | 17.41 |
July | 23.84 | 20.12 |
August | 23.85 | 19.46 |
September | 23.75 | 16.66 |
October | 23.46 | 11.27 |
November | 23.31 | 8.49 |
December | 23.01 | 4.55 |
Annual Sum or Average | 23.44 | 11.73 |
Minimum of Months | 23.01 | 4.55 |
Maximum of Months | 23.85 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 4.90 |
February | 22.48 | 5.21 |
March | 23.16 | 8.41 |
April | 23.32 | 10.40 |
May | 23.64 | 13.39 |
June | 23.85 | 17.41 |
July | 23.88 | 20.12 |
August | 23.89 | 19.46 |
September | 23.83 | 16.66 |
October | 23.46 | 11.27 |
November | 23.11 | 8.49 |
December | 22.45 | 4.55 |
Annual Sum or Average | 23.31 | 11.73 |
Minimum of Months | 22.45 | 4.55 |
Maximum of Months | 23.89 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.42 | 4.90 |
February | 17.39 | 5.21 |
March | 20.20 | 8.41 |
April | 20.35 | 10.40 |
May | 21.78 | 13.39 |
June | 23.29 | 17.41 |
July | 24.36 | 20.12 |
August | 24.14 | 19.46 |
September | 23.33 | 16.66 |
October | 21.29 | 11.27 |
November | 19.27 | 8.49 |
December | 17.56 | 4.55 |
Annual Sum or Average | 20.97 | 11.73 |
Minimum of Months | 17.39 | 4.55 |
Maximum of Months | 24.36 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 4.90 |
February | 20.29 | 5.21 |
March | 21.98 | 8.41 |
April | 22.17 | 10.40 |
May | 23.05 | 13.39 |
June | 23.94 | 17.41 |
July | 24.52 | 20.12 |
August | 24.41 | 19.46 |
September | 23.92 | 16.66 |
October | 22.67 | 11.27 |
November | 21.44 | 8.49 |
December | 20.32 | 4.55 |
Annual Sum or Average | 22.47 | 11.73 |
Minimum of Months | 20.29 | 4.55 |
Maximum of Months | 24.52 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.68 | 4.90 |
February | 17.47 | 5.21 |
March | 20.78 | 8.41 |
April | 20.77 | 10.40 |
May | 22.24 | 13.39 |
June | 23.72 | 17.41 |
July | 24.86 | 20.12 |
August | 24.76 | 19.46 |
September | 24.12 | 16.66 |
October | 21.91 | 11.27 |
November | 19.45 | 8.49 |
December | 17.60 | 4.55 |
Annual Sum or Average | 21.39 | 11.73 |
Minimum of Months | 17.47 | 4.55 |
Maximum of Months | 24.86 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.96 | 4.90 |
February | 21.95 | 5.21 |
March | 23.01 | 8.41 |
April | 23.24 | 10.40 |
May | 23.71 | 13.39 |
June | 23.88 | 17.41 |
July | 23.91 | 20.12 |
August | 23.89 | 19.46 |
September | 23.87 | 16.66 |
October | 23.45 | 11.27 |
November | 22.63 | 8.49 |
December | 21.85 | 4.55 |
Annual Sum or Average | 23.12 | 11.73 |
Minimum of Months | 21.85 | 4.55 |
Maximum of Months | 23.91 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.21 | 4.90 |
February | 16.19 | 5.21 |
March | 19.34 | 8.41 |
April | 19.49 | 10.40 |
May | 21.08 | 13.39 |
June | 22.69 | 17.41 |
July | 23.81 | 20.12 |
August | 23.69 | 19.46 |
September | 22.98 | 16.66 |
October | 20.61 | 11.27 |
November | 18.10 | 8.49 |
December | 16.27 | 4.55 |
Annual Sum or Average | 20.15 | 11.73 |
Minimum of Months | 16.19 | 4.55 |
Maximum of Months | 23.81 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.07 | 4.90 |
February | 19.27 | 5.21 |
March | 20.23 | 8.41 |
April | 20.86 | 10.40 |
May | 22.05 | 13.39 |
June | 22.91 | 17.41 |
July | 23.16 | 20.12 |
August | 23.16 | 19.46 |
September | 22.76 | 16.66 |
October | 21.03 | 11.27 |
November | 19.63 | 8.49 |
December | 19.11 | 4.55 |
Annual Sum or Average | 21.11 | 11.73 |
Minimum of Months | 19.07 | 4.55 |
Maximum of Months | 23.16 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | 4.90 |
February | 21.08 | 5.21 |
March | 21.40 | 8.41 |
April | 21.54 | 10.40 |
May | 21.72 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.75 | 16.66 |
October | 21.58 | 11.27 |
November | 21.31 | 8.49 |
December | 21.00 | 4.55 |
Annual Sum or Average | 21.48 | 11.73 |
Minimum of Months | 21.00 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 4.90 |
February | 21.14 | 5.21 |
March | 21.46 | 8.41 |
April | 21.59 | 10.40 |
May | 21.73 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.75 | 16.66 |
October | 21.62 | 11.27 |
November | 21.38 | 8.49 |
December | 21.06 | 4.55 |
Annual Sum or Average | 21.51 | 11.73 |
Minimum of Months | 21.06 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | 4.90 |
February | 21.17 | 5.21 |
March | 21.48 | 8.41 |
April | 21.59 | 10.40 |
May | 21.73 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.75 | 16.66 |
October | 21.64 | 11.27 |
November | 21.42 | 8.49 |
December | 21.09 | 4.55 |
Annual Sum or Average | 21.52 | 11.73 |
Minimum of Months | 21.09 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | 4.90 |
February | 20.89 | 5.21 |
March | 21.28 | 8.41 |
April | 21.41 | 10.40 |
May | 21.65 | 13.39 |
June | 21.74 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.74 | 16.66 |
October | 21.50 | 11.27 |
November | 21.15 | 8.49 |
December | 20.83 | 4.55 |
Annual Sum or Average | 21.38 | 11.73 |
Minimum of Months | 20.83 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 4.90 |
February | 21.15 | 5.21 |
March | 21.54 | 8.41 |
April | 21.61 | 10.40 |
May | 21.73 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.66 | 11.27 |
November | 21.42 | 8.49 |
December | 21.08 | 4.55 |
Annual Sum or Average | 21.54 | 11.73 |
Minimum of Months | 21.08 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 4.90 |
February | 23.05 | 5.21 |
March | 23.28 | 8.41 |
April | 23.31 | 10.40 |
May | 23.33 | 13.39 |
June | 23.33 | 17.41 |
July | 23.33 | 20.12 |
August | 23.33 | 19.46 |
September | 23.33 | 16.66 |
October | 23.32 | 11.27 |
November | 23.28 | 8.49 |
December | 22.97 | 4.55 |
Annual Sum or Average | 23.25 | 11.73 |
Minimum of Months | 22.97 | 4.55 |
Maximum of Months | 23.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 30.77 | 4.90 |
February | 30.39 | 5.21 |
March | 31.83 | 8.41 |
April | 31.94 | 10.40 |
May | 32.58 | 13.39 |
June | 33.09 | 17.41 |
July | 33.48 | 20.12 |
August | 33.41 | 19.46 |
September | 33.15 | 16.66 |
October | 32.25 | 11.27 |
November | 31.18 | 8.49 |
December | 30.37 | 4.55 |
Annual Sum or Average | 32.05 | 11.73 |
Minimum of Months | 30.37 | 4.55 |
Maximum of Months | 33.48 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 4.90 |
February | 21.87 | 5.21 |
March | 22.10 | 8.41 |
April | 22.22 | 10.40 |
May | 22.41 | 13.39 |
June | 22.65 | 17.41 |
July | 22.88 | 20.12 |
August | 22.78 | 19.46 |
September | 22.59 | 16.66 |
October | 22.24 | 11.27 |
November | 21.99 | 8.49 |
December | 21.85 | 4.55 |
Annual Sum or Average | 22.29 | 11.73 |
Minimum of Months | 21.85 | 4.55 |
Maximum of Months | 22.88 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | 4.90 |
February | 21.31 | 5.21 |
March | 21.61 | 8.41 |
April | 21.68 | 10.40 |
May | 21.75 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.69 | 11.27 |
November | 21.54 | 8.49 |
December | 21.23 | 4.55 |
Annual Sum or Average | 21.59 | 11.73 |
Minimum of Months | 21.23 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 4.90 |
February | 21.15 | 5.21 |
March | 21.54 | 8.41 |
April | 21.62 | 10.40 |
May | 21.74 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.66 | 11.27 |
November | 21.42 | 8.49 |
December | 21.07 | 4.55 |
Annual Sum or Average | 21.53 | 11.73 |
Minimum of Months | 21.07 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | 4.90 |
February | 19.26 | 5.21 |
March | 21.60 | 8.41 |
April | 21.81 | 10.40 |
May | 23.03 | 13.39 |
June | 24.20 | 17.41 |
July | 24.93 | 20.12 |
August | 24.78 | 19.46 |
September | 24.13 | 16.66 |
October | 22.45 | 11.27 |
November | 20.75 | 8.49 |
December | 19.25 | 4.55 |
Annual Sum or Average | 22.19 | 11.73 |
Minimum of Months | 19.25 | 4.55 |
Maximum of Months | 24.93 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.56 | 4.90 |
February | 16.26 | 5.21 |
March | 20.00 | 8.41 |
April | 20.17 | 10.40 |
May | 22.08 | 13.39 |
June | 24.00 | 17.41 |
July | 25.29 | 20.12 |
August | 25.01 | 19.46 |
September | 24.00 | 16.66 |
October | 21.36 | 11.27 |
November | 18.68 | 8.49 |
December | 16.40 | 4.55 |
Annual Sum or Average | 20.93 | 11.73 |
Minimum of Months | 16.26 | 4.55 |
Maximum of Months | 25.29 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.88 | 4.90 |
February | 16.67 | 5.21 |
March | 20.25 | 8.41 |
April | 20.32 | 10.40 |
May | 22.03 | 13.39 |
June | 23.71 | 17.41 |
July | 24.97 | 20.12 |
August | 24.85 | 19.46 |
September | 24.08 | 16.66 |
October | 21.49 | 11.27 |
November | 18.76 | 8.49 |
December | 16.77 | 4.55 |
Annual Sum or Average | 21.01 | 11.73 |
Minimum of Months | 16.67 | 4.55 |
Maximum of Months | 24.97 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | 4.90 |
February | 21.27 | 5.21 |
March | 21.88 | 8.41 |
April | 22.24 | 10.40 |
May | 23.07 | 13.39 |
June | 23.66 | 17.41 |
July | 23.81 | 20.12 |
August | 23.82 | 19.46 |
September | 23.60 | 16.66 |
October | 22.40 | 11.27 |
November | 21.41 | 8.49 |
December | 21.17 | 4.55 |
Annual Sum or Average | 22.46 | 11.73 |
Minimum of Months | 21.15 | 4.55 |
Maximum of Months | 23.82 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.06 | 4.90 |
February | 15.08 | 5.21 |
March | 18.50 | 8.41 |
April | 18.78 | 10.40 |
May | 20.72 | 13.39 |
June | 22.66 | 17.41 |
July | 23.95 | 20.12 |
August | 23.80 | 19.46 |
September | 22.89 | 16.66 |
October | 19.95 | 11.27 |
November | 17.07 | 8.49 |
December | 15.11 | 4.55 |
Annual Sum or Average | 19.58 | 11.73 |
Minimum of Months | 15.08 | 4.55 |
Maximum of Months | 23.95 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 4.90 |
February | 19.04 | 5.21 |
March | 19.65 | 8.41 |
April | 20.28 | 10.40 |
May | 21.57 | 13.39 |
June | 22.68 | 17.41 |
July | 23.04 | 20.12 |
August | 23.03 | 19.46 |
September | 22.45 | 16.66 |
October | 20.34 | 11.27 |
November | 19.12 | 8.49 |
December | 18.93 | 4.55 |
Annual Sum or Average | 20.76 | 11.73 |
Minimum of Months | 18.90 | 4.55 |
Maximum of Months | 23.04 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.96 | 4.90 |
February | 19.16 | 5.21 |
March | 19.97 | 8.41 |
April | 20.66 | 10.40 |
May | 21.91 | 13.39 |
June | 22.87 | 17.41 |
July | 23.15 | 20.12 |
August | 23.14 | 19.46 |
September | 22.65 | 16.66 |
October | 20.71 | 11.27 |
November | 19.36 | 8.49 |
December | 19.01 | 4.55 |
Annual Sum or Average | 20.97 | 11.73 |
Minimum of Months | 18.96 | 4.55 |
Maximum of Months | 23.15 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.01 | 4.90 |
February | 19.25 | 5.21 |
March | 20.17 | 8.41 |
April | 20.88 | 10.40 |
May | 22.04 | 13.39 |
June | 22.90 | 17.41 |
July | 23.15 | 20.12 |
August | 23.14 | 19.46 |
September | 22.69 | 16.66 |
October | 20.89 | 11.27 |
November | 19.52 | 8.49 |
December | 19.06 | 4.55 |
Annual Sum or Average | 21.07 | 11.73 |
Minimum of Months | 19.01 | 4.55 |
Maximum of Months | 23.15 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | 4.90 |
February | 21.07 | 5.21 |
March | 21.40 | 8.41 |
April | 21.53 | 10.40 |
May | 21.71 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.74 | 16.66 |
October | 21.57 | 11.27 |
November | 21.31 | 8.49 |
December | 20.99 | 4.55 |
Annual Sum or Average | 21.47 | 11.73 |
Minimum of Months | 20.99 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.98 | 4.90 |
February | 19.17 | 5.21 |
March | 20.10 | 8.41 |
April | 20.62 | 10.40 |
May | 21.82 | 13.39 |
June | 22.79 | 17.41 |
July | 23.11 | 20.12 |
August | 23.14 | 19.46 |
September | 22.69 | 16.66 |
October | 20.91 | 11.27 |
November | 19.44 | 8.49 |
December | 19.01 | 4.55 |
Annual Sum or Average | 20.99 | 11.73 |
Minimum of Months | 18.98 | 4.55 |
Maximum of Months | 23.14 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.97 | 4.90 |
February | 20.97 | 5.21 |
March | 21.40 | 8.41 |
April | 21.51 | 10.40 |
May | 21.70 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.56 | 11.27 |
November | 21.23 | 8.49 |
December | 20.89 | 4.55 |
Annual Sum or Average | 21.44 | 11.73 |
Minimum of Months | 20.89 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.32 | 4.90 |
February | 21.32 | 5.21 |
March | 21.62 | 8.41 |
April | 21.69 | 10.40 |
May | 21.75 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.69 | 11.27 |
November | 21.55 | 8.49 |
December | 21.23 | 4.55 |
Annual Sum or Average | 21.60 | 11.73 |
Minimum of Months | 21.23 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 4.90 |
February | 22.07 | 5.21 |
March | 23.74 | 8.41 |
April | 24.00 | 10.40 |
May | 24.90 | 13.39 |
June | 25.62 | 17.41 |
July | 26.04 | 20.12 |
August | 25.95 | 19.46 |
September | 25.57 | 16.66 |
October | 24.29 | 11.27 |
November | 22.97 | 8.49 |
December | 21.98 | 4.55 |
Annual Sum or Average | 24.14 | 11.73 |
Minimum of Months | 21.98 | 4.55 |
Maximum of Months | 26.04 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 4.90 |
February | 21.04 | 5.21 |
March | 22.34 | 8.41 |
April | 22.65 | 10.40 |
May | 23.15 | 13.39 |
June | 23.32 | 17.41 |
July | 23.33 | 20.12 |
August | 23.33 | 19.46 |
September | 23.31 | 16.66 |
October | 22.77 | 11.27 |
November | 21.90 | 8.49 |
December | 20.82 | 4.55 |
Annual Sum or Average | 22.43 | 11.73 |
Minimum of Months | 20.82 | 4.55 |
Maximum of Months | 23.33 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | 4.90 |
February | 21.17 | 5.21 |
March | 21.52 | 8.41 |
April | 21.61 | 10.40 |
May | 21.73 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.75 | 16.66 |
October | 21.63 | 11.27 |
November | 21.40 | 8.49 |
December | 21.08 | 4.55 |
Annual Sum or Average | 21.53 | 11.73 |
Minimum of Months | 21.08 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.34 | 4.90 |
February | 19.50 | 5.21 |
March | 20.83 | 8.41 |
April | 21.34 | 10.40 |
May | 22.34 | 13.39 |
June | 23.01 | 17.41 |
July | 23.21 | 20.12 |
August | 23.21 | 19.46 |
September | 22.93 | 16.66 |
October | 21.55 | 11.27 |
November | 20.18 | 8.49 |
December | 19.32 | 4.55 |
Annual Sum or Average | 21.41 | 11.73 |
Minimum of Months | 19.32 | 4.55 |
Maximum of Months | 23.21 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.76 | 4.90 |
February | 18.12 | 5.21 |
March | 20.85 | 8.41 |
April | 21.18 | 10.40 |
May | 22.75 | 13.39 |
June | 24.20 | 17.41 |
July | 25.07 | 20.12 |
August | 24.88 | 19.46 |
September | 24.05 | 16.66 |
October | 21.87 | 11.27 |
November | 19.76 | 8.49 |
December | 18.05 | 4.55 |
Annual Sum or Average | 21.65 | 11.73 |
Minimum of Months | 18.05 | 4.55 |
Maximum of Months | 25.07 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.62 | 4.90 |
February | 15.31 | 5.21 |
March | 19.39 | 8.41 |
April | 19.66 | 10.40 |
May | 21.85 | 13.39 |
June | 24.02 | 17.41 |
July | 25.47 | 20.12 |
August | 25.14 | 19.46 |
September | 23.97 | 16.66 |
October | 20.90 | 11.27 |
November | 17.90 | 8.49 |
December | 15.40 | 4.55 |
Annual Sum or Average | 20.50 | 11.73 |
Minimum of Months | 15.31 | 4.55 |
Maximum of Months | 25.47 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.57 | 4.90 |
February | 15.54 | 5.21 |
March | 19.29 | 8.41 |
April | 19.63 | 10.40 |
May | 21.62 | 13.39 |
June | 23.59 | 17.41 |
July | 25.08 | 20.12 |
August | 24.82 | 19.46 |
September | 23.79 | 16.66 |
October | 20.61 | 11.27 |
November | 17.65 | 8.49 |
December | 15.52 | 4.55 |
Annual Sum or Average | 20.34 | 11.73 |
Minimum of Months | 15.52 | 4.55 |
Maximum of Months | 25.08 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | 4.90 |
February | 21.24 | 5.21 |
March | 21.60 | 8.41 |
April | 21.96 | 10.40 |
May | 22.58 | 13.39 |
June | 23.19 | 17.41 |
July | 23.51 | 20.12 |
August | 23.41 | 19.46 |
September | 23.00 | 16.66 |
October | 21.91 | 11.27 |
November | 21.22 | 8.49 |
December | 21.13 | 4.55 |
Annual Sum or Average | 22.16 | 11.73 |
Minimum of Months | 21.13 | 4.55 |
Maximum of Months | 23.51 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.16 | 4.90 |
February | 14.31 | 5.21 |
March | 17.78 | 8.41 |
April | 18.30 | 10.40 |
May | 20.39 | 13.39 |
June | 22.53 | 17.41 |
July | 24.02 | 20.12 |
August | 23.73 | 19.46 |
September | 22.58 | 16.66 |
October | 19.23 | 11.27 |
November | 16.29 | 8.49 |
December | 14.25 | 4.55 |
Annual Sum or Average | 19.08 | 11.73 |
Minimum of Months | 14.25 | 4.55 |
Maximum of Months | 24.02 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.56 | 4.90 |
February | 20.67 | 5.21 |
March | 20.96 | 8.41 |
April | 21.21 | 10.40 |
May | 21.59 | 13.39 |
June | 21.73 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.69 | 16.66 |
October | 21.21 | 11.27 |
November | 20.79 | 8.49 |
December | 20.56 | 4.55 |
Annual Sum or Average | 21.21 | 11.73 |
Minimum of Months | 20.56 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.93 | 4.90 |
February | 19.11 | 5.21 |
March | 19.63 | 8.41 |
April | 20.31 | 10.40 |
May | 21.34 | 13.39 |
June | 22.36 | 17.41 |
July | 22.76 | 20.12 |
August | 22.70 | 19.46 |
September | 22.01 | 16.66 |
October | 20.17 | 11.27 |
November | 19.10 | 8.49 |
December | 18.93 | 4.55 |
Annual Sum or Average | 20.62 | 11.73 |
Minimum of Months | 18.93 | 4.55 |
Maximum of Months | 22.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.94 | 4.90 |
February | 19.14 | 5.21 |
March | 19.73 | 8.41 |
April | 20.42 | 10.40 |
May | 21.42 | 13.39 |
June | 22.37 | 17.41 |
July | 22.76 | 20.12 |
August | 22.70 | 19.46 |
September | 22.03 | 16.66 |
October | 20.26 | 11.27 |
November | 19.16 | 8.49 |
December | 18.94 | 4.55 |
Annual Sum or Average | 20.66 | 11.73 |
Minimum of Months | 18.94 | 4.55 |
Maximum of Months | 22.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | 4.90 |
February | 21.00 | 5.21 |
March | 21.38 | 8.41 |
April | 21.55 | 10.40 |
May | 21.72 | 13.39 |
June | 21.75 | 17.41 |
July | 21.75 | 20.12 |
August | 21.75 | 19.46 |
September | 21.74 | 16.66 |
October | 21.53 | 11.27 |
November | 21.25 | 8.49 |
December | 20.87 | 4.55 |
Annual Sum or Average | 21.44 | 11.73 |
Minimum of Months | 20.87 | 4.55 |
Maximum of Months | 21.75 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.94 | 4.90 |
February | 19.13 | 5.21 |
March | 19.79 | 8.41 |
April | 20.34 | 10.40 |
May | 21.37 | 13.39 |
June | 22.38 | 17.41 |
July | 22.79 | 20.12 |
August | 22.76 | 19.46 |
September | 22.16 | 16.66 |
October | 20.37 | 11.27 |
November | 19.16 | 8.49 |
December | 18.95 | 4.55 |
Annual Sum or Average | 20.69 | 11.73 |
Minimum of Months | 18.94 | 4.55 |
Maximum of Months | 22.79 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.04 | 4.90 |
February | 19.24 | 5.21 |
March | 20.25 | 8.41 |
April | 20.77 | 10.40 |
May | 21.78 | 13.39 |
June | 22.60 | 17.41 |
July | 22.94 | 20.12 |
August | 22.91 | 19.46 |
September | 22.46 | 16.66 |
October | 20.83 | 11.27 |
November | 19.51 | 8.49 |
December | 19.04 | 4.55 |
Annual Sum or Average | 20.96 | 11.73 |
Minimum of Months | 19.04 | 4.55 |
Maximum of Months | 22.94 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | 4.90 |
February | 21.14 | 5.21 |
March | 21.54 | 8.41 |
April | 21.65 | 10.40 |
May | 21.74 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.62 | 11.27 |
November | 21.39 | 8.49 |
December | 20.99 | 4.55 |
Annual Sum or Average | 21.52 | 11.73 |
Minimum of Months | 20.99 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.13 | 4.90 |
February | 19.95 | 5.21 |
March | 21.57 | 8.41 |
April | 22.01 | 10.40 |
May | 23.02 | 13.39 |
June | 23.92 | 17.41 |
July | 24.49 | 20.12 |
August | 24.28 | 19.46 |
September | 23.67 | 16.66 |
October | 22.07 | 11.27 |
November | 20.77 | 8.49 |
December | 19.75 | 4.55 |
Annual Sum or Average | 22.15 | 11.73 |
Minimum of Months | 19.75 | 4.55 |
Maximum of Months | 24.49 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.05 | 4.90 |
February | 21.09 | 5.21 |
March | 21.51 | 8.41 |
April | 21.63 | 10.40 |
May | 21.74 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.61 | 11.27 |
November | 21.35 | 8.49 |
December | 20.96 | 4.55 |
Annual Sum or Average | 21.50 | 11.73 |
Minimum of Months | 20.96 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.05 | 4.90 |
February | 21.11 | 5.21 |
March | 21.51 | 8.41 |
April | 21.64 | 10.40 |
May | 21.74 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.61 | 11.27 |
November | 21.36 | 8.49 |
December | 20.96 | 4.55 |
Annual Sum or Average | 21.50 | 11.73 |
Minimum of Months | 20.96 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 4.90 |
February | 20.90 | 5.21 |
March | 21.38 | 8.41 |
April | 21.53 | 10.40 |
May | 21.72 | 13.39 |
June | 21.75 | 17.41 |
July | 21.76 | 20.12 |
August | 21.76 | 19.46 |
September | 21.75 | 16.66 |
October | 21.53 | 11.27 |
November | 21.16 | 8.49 |
December | 20.77 | 4.55 |
Annual Sum or Average | 21.40 | 11.73 |
Minimum of Months | 20.77 | 4.55 |
Maximum of Months | 21.76 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.22 | 4.90 |
February | 17.69 | 5.21 |
March | 20.43 | 8.41 |
April | 20.94 | 10.40 |
May | 22.57 | 13.39 |
June | 24.10 | 17.41 |
July | 25.08 | 20.12 |
August | 24.77 | 19.46 |
September | 23.79 | 16.66 |
October | 21.37 | 11.27 |
November | 19.29 | 8.49 |
December | 17.51 | 4.55 |
Annual Sum or Average | 21.34 | 11.73 |
Minimum of Months | 17.51 | 4.55 |
Maximum of Months | 25.08 | 20.12 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:51
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.79 | 4.90 |
February | 14.61 | 5.21 |
March | 18.77 | 8.41 |
April | 19.25 | 10.40 |
May | 21.57 | 13.39 |
June | 23.89 | 17.41 |
July | 25.51 | 20.12 |
August | 25.04 | 19.46 |
September | 23.68 | 16.66 |
October | 20.24 | 11.27 |
November | 17.20 | 8.49 |
December | 14.60 | 4.55 |
Annual Sum or Average | 20.05 | 11.73 |
Minimum of Months | 14.60 | 4.55 |
Maximum of Months | 25.51 | 20.12 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:51
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.159473E+12 | 117877.950 | 24-JAN-07:15 | 20847.837 | 39740.848 | 9154.930 | 43516.550 | 421.671 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.146624E+12 | 126094.211 | 14-FEB-07:15 | 20847.837 | 39740.848 | 9154.930 | 51925.246 | 229.237 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.150869E+12 | 106040.166 | 06-MAR-07:15 | 20847.837 | 39740.848 | 9154.930 | 35055.837 | 1232.602 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.146656E+12 | 102084.345 | 13-APR-06:15 | 20847.837 | 39740.848 | 9154.930 | 30284.998 | 2047.619 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.155697E+12 | 96769.190 | 05-MAY-07:00 | 25182.171 | 43578.554 | 9676.274 | 0.000 | 18324.078 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.160785E+12 | 104710.075 | 24-JUN-17:15 | 26252.371 | 28657.799 | 9330.567 | 0.000 | 40461.226 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.175638E+12 | 107200.962 | 17-JUL-17:15 | 22761.323 | 28927.409 | 9356.552 | 0.000 | 46147.564 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.172282E+12 | 97991.399 | 12-AUG-07:00 | 25182.171 | 43578.554 | 9676.274 | 0.000 | 19546.287 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.159126E+12 | 98886.632 | 09-SEP-17:15 | 26252.371 | 28657.799 | 9301.841 | 0.000 | 34666.509 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.151938E+12 | 100149.224 | 16-OCT-06:30 | 20847.837 | 39740.848 | 9154.930 | 22943.907 | 3265.589 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.146265E+12 | 104738.419 | 02-NOV-06:15 | 20847.837 | 39740.848 | 9154.930 | 29139.231 | 1659.460 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.167116E+12 | 136700.289 | 20-DEC-07:15 | 20847.837 | 39740.848 | 9156.846 | 62576.352 | 182.292 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.189247E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.146265E+12 | 96769.190 | 20847.837 | 28657.799 | 9154.930 | 0.000 | 182.292 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.175638E+12 | 136700.289 | 26252.371 | 43578.554 | 9676.274 | 62576.352 | 46147.564 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:51
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.995204E+11 | 99725.684 | 13-JAN-09:15 | 62.797 | 40096.028 | 0.000 | 59566.859 | 59566.859 | 59566.859 | 62.797 |
February | 0.907821E+11 | 98729.513 | 24-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 58633.485 | 58633.485 | 58633.485 | 0.000 |
March | 0.949380E+11 | 106334.431 | 04-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 66238.403 | 66238.403 | 66238.403 | 0.000 |
April | 0.895138E+11 | 99337.396 | 21-APR-08:15 | 0.000 | 40096.028 | 0.000 | 59241.368 | 59241.368 | 59241.368 | 0.000 |
May | 0.893309E+11 | 96024.560 | 27-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 55928.532 | 55928.532 | 55928.532 | 0.000 |
June | 0.838800E+11 | 94386.429 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 54290.400 | 54290.400 | 54290.400 | 0.000 |
July | 0.852889E+11 | 85548.790 | 04-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 45452.762 | 45452.762 | 45452.762 | 0.000 |
August | 0.849026E+11 | 90664.990 | 04-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 50568.962 | 50568.962 | 50568.962 | 0.000 |
September | 0.828640E+11 | 91970.477 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 51874.449 | 51874.449 | 51874.449 | 0.000 |
October | 0.886352E+11 | 94632.379 | 28-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 54536.351 | 54536.351 | 54536.351 | 0.000 |
November | 0.891782E+11 | 98682.988 | 22-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 58586.960 | 58586.960 | 58586.960 | 0.000 |
December | 0.999686E+11 | 99627.105 | 21-DEC-12:00 | 11566.732 | 40096.028 | 0.000 | 47964.344 | 47964.344 | 47964.344 | 11566.732 |
Annual Sum or Average | 0.107880E+13 | 0.000 | ||||||||
Minimum of Months | 0.828640E+11 | 85548.790 | 0.000 | 40096.028 | 0.000 | 45452.762 | 45452.762 | 45452.762 | 0.000 | |
Maximum of Months | 0.999686E+11 | 106334.431 | 11566.732 | 40096.028 | 0.000 | 66238.403 | 66238.403 | 66238.403 | 11566.732 |