Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: RIYADH - SAU IWEC Data WMO#=404380
Simulation Timestamp: 2015-09-14 08:44:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3129.07 | 779.62 | 840.00 |
Net Site Energy | 3129.07 | 779.62 | 840.00 |
Total Source Energy | 8168.23 | 2035.15 | 2192.76 |
Net Source Energy | 8168.23 | 2035.15 | 2192.76 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 5.26 | 0.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 725.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 316.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 413.63 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2293.00 | 836.07 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 5.26 | 0.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 725.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 316.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 413.63 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 281.08 | 111.29 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 615.56 | 224.44 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 260.88 | 103.29 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 571.31 | 208.31 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2293.00 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2293.00 | 100.00 |
Total On-Site and Utility Electric Sources | 2293.00 | 100.00 |
Total Electricity End Uses | 2293.00 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 83.25 |
Time Setpoint Not Met During Occupied Cooling | 6197.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4811.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | RIYADH - SAU IWEC Data WMO#=404380 |
Weather File | RIYADH - SAU IWEC Data WMO#=404380 |
Latitude [deg] | 24.70 |
Longitude [deg] | 46.80 |
Elevation [m] | 612.00 |
Time Zone | 3.00 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00 | 5.90 | Wetbulb [C] | 1.60 | 320.00 |
RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 13.50 | 18.70 | Wetbulb [C] | 4.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_1.16_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_1.16_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 8.38 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 175.82 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9210.80 | 7052.30 | 2158.50 | 0.77 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 26579.93 | 19178.45 | 7401.48 | 0.72 | 3.50 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12859.01 | 8913.00 | 3946.01 | 0.69 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17118.76 | 12785.11 | 4333.65 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8817.7 | 3.21 | 10.95 | 11.60 | 10.83 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 25594.4 | 2.98 | 10.18 | 10.80 | 10.29 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12428.6 | 3.34 | 11.41 | 12.10 | 11.52 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16429.0 | 3.24 | 11.07 | 11.73 | 11.00 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.79 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 15197.57 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 478.52 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 478.52 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 678.30 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.72 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.79 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 1923.70 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 678.30 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 2713.20 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2150.30 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 2713.20 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 743.84 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 1913.93 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 2713.01 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.72 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.79 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 1923.70 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 678.30 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 2713.20 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2150.30 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 2713.20 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 678.30 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 717.52 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 2713.01 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 478.48 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 2713.01 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.72 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.79 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2276.51 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1038.01 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 2713.20 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2150.30 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 2713.20 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 678.30 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 678.25 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 2713.01 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 733.87 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 2713.01 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 845.69 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 298.72 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 2792.94 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 11706.54 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 6268.77 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 4682.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.51 | 587.94 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 1.27 | 1446.68 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.55 | 642.94 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.89 | 1012.90 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 11926.64 | 14311.97 | 1.057 | 1.269 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 43.12 | 0.00412 |
RESTROOMFLR1 | 935.25 | 1122.30 | 0.083 | 0.099 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 41.97 | 0.00412 |
MEETINGROOMFLR1 | 5202.37 | 6242.84 | 0.462 | 0.554 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
GUESTROOM101 | 866.26 | 1039.51 | 0.081 | 0.098 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM102 | 714.67 | 857.61 | 0.067 | 0.080 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM103 | 1953.94 | 2344.72 | 0.241 | 0.289 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
GUESTROOM104 | 1751.07 | 2101.29 | 0.216 | 0.259 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 44.00 | 0.00412 |
GUESTROOM105 | 2058.15 | 2469.77 | 0.254 | 0.304 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
EMPLOYEELOUNGEFLR1 | 5882.04 | 7058.45 | 0.522 | 0.626 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
EXERCISECENTERFLR1 | 1533.79 | 1840.55 | 0.136 | 0.163 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 42.31 | 0.00412 |
FRONTOFFICEFLR1 | 4764.04 | 5716.85 | 0.422 | 0.506 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 41.10 | 0.00412 |
GUESTROOM201 | 1463.68 | 1756.42 | 0.137 | 0.165 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM202_205 | 7035.02 | 8442.02 | 0.867 | 1.040 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM206_208 | 5730.85 | 6877.02 | 0.706 | 0.847 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM209_212 | 6619.88 | 7943.86 | 0.816 | 0.979 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM213 | 2039.14 | 2446.97 | 0.251 | 0.301 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM214 | 1960.71 | 2352.85 | 0.242 | 0.290 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
GUESTROOM215_218 | 9382.92 | 11259.50 | 0.881 | 1.057 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM219 | 5877.99 | 7053.59 | 0.724 | 0.869 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM220_223 | 6215.57 | 7458.68 | 0.766 | 0.919 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM224 | 1921.13 | 2305.36 | 0.237 | 0.284 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM301 | 1370.22 | 1644.27 | 0.129 | 0.154 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM302_305 | 3076.38 | 3691.66 | 0.289 | 0.346 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM306_308 | 2697.19 | 3236.63 | 0.253 | 0.304 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM309_312 | 6686.08 | 8023.30 | 0.824 | 0.988 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 42.85 | 0.00412 |
GUESTROOM313 | 1100.91 | 1321.09 | 0.103 | 0.124 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
GUESTROOM314 | 1944.48 | 2333.37 | 0.240 | 0.287 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
GUESTROOM315_318 | 6918.48 | 8302.17 | 0.852 | 1.023 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM319 | 1096.21 | 1315.46 | 0.103 | 0.123 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM320_323 | 6099.26 | 7319.11 | 0.751 | 0.902 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM324 | 865.46 | 1038.56 | 0.081 | 0.097 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 41.43 | 0.00412 |
GUESTROOM401 | 2861.79 | 3434.14 | 0.352 | 0.423 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
GUESTROOM402_405 | 4406.90 | 5288.28 | 0.414 | 0.496 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
GUESTROOM406_408 | 3859.05 | 4630.86 | 0.362 | 0.435 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
GUESTROOM409_412 | 8279.79 | 9935.75 | 1.020 | 1.224 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 43.59 | 0.00412 |
GUESTROOM413 | 1567.61 | 1881.13 | 0.147 | 0.177 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
GUESTROOM414 | 1348.86 | 1618.63 | 0.127 | 0.152 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 44.20 | 0.00412 |
GUESTROOM415_418 | 7718.23 | 9261.88 | 0.951 | 1.141 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 42.11 | 0.00412 |
GUESTROOM419 | 2153.58 | 2584.29 | 0.265 | 0.318 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 44.20 | 0.00412 |
GUESTROOM420_423 | 7580.04 | 9096.05 | 0.934 | 1.121 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:45:00 | 42.11 | 0.00412 |
GUESTROOM424 | 2309.19 | 2771.03 | 0.284 | 0.341 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
CORRIDORFLR1 | 25596.69 | 30716.03 | 2.266 | 2.719 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 40.96 | 0.00412 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
CORRIDORFLR2 | 3747.58 | 4497.10 | 0.332 | 0.398 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
CORRIDORFLR3 | 2533.89 | 3040.66 | 0.224 | 0.269 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 42.58 | 0.00412 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 | |
CORRIDORFLR4 | 3892.58 | 4671.10 | 0.345 | 0.414 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 44.20 | 0.00412 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 0.00412 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1275.62 | 1530.75 | 0.039 | 0.236 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | 5.90 | 0.00619 |
MEETINGROOMFLR1 | 407.34 | 488.81 | 0.012 | 0.126 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 5.90 | 0.00619 |
GUESTROOM101 | 0.00 | 0.00 | 0.000 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
GUESTROOM102 | 0.00 | 0.00 | 0.000 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
GUESTROOM103 | 361.84 | 434.20 | 0.011 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 5.90 | 0.00619 |
GUESTROOM104 | 280.40 | 336.48 | 0.009 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | 5.90 | 0.00619 |
GUESTROOM105 | 226.37 | 271.64 | 0.007 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | 5.90 | 0.00619 |
EMPLOYEELOUNGEFLR1 | 200.77 | 240.92 | 0.006 | 0.051 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5.90 | 0.00619 |
EXERCISECENTERFLR1 | 95.82 | 114.99 | 0.003 | 0.043 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 5.90 | 0.00619 |
FRONTOFFICEFLR1 | 683.97 | 820.76 | 0.021 | 0.056 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | 5.90 | 0.00619 |
GUESTROOM201 | 172.03 | 206.43 | 0.005 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 11:15:00 | 5.90 | 0.00619 |
GUESTROOM202_205 | 1056.16 | 1267.39 | 0.032 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | 5.90 | 0.00619 |
GUESTROOM206_208 | 766.17 | 919.41 | 0.023 | 0.043 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
GUESTROOM209_212 | 789.13 | 946.96 | 0.024 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
GUESTROOM213 | 424.90 | 509.88 | 0.013 | 0.015 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | 5.90 | 0.00619 |
GUESTROOM214 | 334.32 | 401.19 | 0.010 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | 5.90 | 0.00619 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.000 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
GUESTROOM219 | 196.81 | 236.17 | 0.006 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
GUESTROOM220_223 | 670.30 | 804.36 | 0.020 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 5.90 | 0.00619 |
GUESTROOM224 | 309.54 | 371.44 | 0.009 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 5.90 | 0.00619 |
GUESTROOM301 | 234.35 | 281.22 | 0.007 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | 5.90 | 0.00619 |
GUESTROOM302_305 | 379.42 | 455.31 | 0.011 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | 5.90 | 0.00619 |
GUESTROOM306_308 | 292.26 | 350.72 | 0.008 | 0.043 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 5.90 | 0.00619 |
GUESTROOM309_312 | 982.06 | 1178.47 | 0.030 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | 5.90 | 0.00619 |
GUESTROOM313 | 179.85 | 215.82 | 0.005 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 20:00:00 | 5.90 | 0.00619 |
GUESTROOM314 | 402.98 | 483.58 | 0.012 | 0.015 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 15:30:00 | 5.90 | 0.00619 |
GUESTROOM315_318 | 1009.15 | 1210.98 | 0.031 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 13:45:00 | 5.90 | 0.00619 |
GUESTROOM319 | 0.00 | 0.00 | 0.000 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
GUESTROOM320_323 | 854.02 | 1024.82 | 0.026 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | 5.90 | 0.00619 |
GUESTROOM324 | 60.45 | 72.55 | 0.002 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 18:15:00 | 5.90 | 0.00619 |
GUESTROOM401 | 670.04 | 804.05 | 0.020 | 0.024 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 5.90 | 0.00619 |
GUESTROOM402_405 | 857.94 | 1029.53 | 0.024 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 21:30:00 | 5.90 | 0.00619 |
GUESTROOM406_408 | 709.03 | 850.84 | 0.020 | 0.043 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 5.90 | 0.00619 |
GUESTROOM409_412 | 1445.26 | 1734.31 | 0.044 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | 5.90 | 0.00619 |
GUESTROOM413 | 338.59 | 406.31 | 0.010 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5.90 | 0.00619 |
GUESTROOM414 | 223.37 | 268.05 | 0.006 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | 5.90 | 0.00619 |
GUESTROOM415_418 | 1373.73 | 1648.48 | 0.042 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | 5.90 | 0.00619 |
GUESTROOM419 | 416.61 | 499.93 | 0.013 | 0.015 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 18:30:00 | 5.90 | 0.00619 |
GUESTROOM420_423 | 1275.67 | 1530.80 | 0.039 | 0.054 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 5.90 | 0.00619 |
GUESTROOM424 | 509.79 | 611.74 | 0.015 | 0.019 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 5.90 | 0.00619 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
CORRIDORFLR1 | 11999.89 | 14399.87 | 0.364 | 0.437 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5.90 | 0.00619 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
CORRIDORFLR2 | 417.50 | 501.00 | 0.013 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | 5.90 | 0.00619 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
CORRIDORFLR3 | 745.91 | 895.09 | 0.023 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 5.90 | 0.00619 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
CORRIDORFLR4 | 1344.17 | 1613.00 | 0.041 | 0.049 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 5.90 | 0.00619 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.51 | 0.51 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 1.27 | 1.27 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.55 | 0.55 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.89 | 0.89 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1926.75 | 3613.75 | 31.50 |
RESTROOMFLR1 | 534.25 | 4841.50 | 0.00 |
MEETINGROOMFLR1 | 1835.50 | 964.50 | 8.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 9.00 | 8416.25 | 7.50 |
GUESTROOM104 | 7.50 | 7955.50 | 2.00 |
GUESTROOM105 | 6.00 | 7703.75 | 0.00 |
EMPLOYEELOUNGEFLR1 | 2897.25 | 1940.00 | 146.00 |
EXERCISECENTERFLR1 | 2261.50 | 850.25 | 0.00 |
FRONTOFFICEFLR1 | 1493.50 | 3577.50 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 53.75 | 7714.75 | 0.00 |
GUESTROOM206_208 | 76.25 | 7667.25 | 0.00 |
GUESTROOM209_212 | 19.75 | 8079.25 | 0.00 |
GUESTROOM213 | 30.00 | 8004.25 | 6.25 |
GUESTROOM214 | 65.25 | 7526.00 | 0.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 6234.25 | 3917.50 | 2115.75 |
GUESTROOM220_223 | 61.75 | 7464.00 | 0.00 |
GUESTROOM224 | 75.75 | 7529.75 | 0.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 23.50 | 8139.00 | 2.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 97.50 | 7516.75 | 2.25 |
GUESTROOM315_318 | 104.50 | 7349.00 | 0.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 22.00 | 7619.50 | 0.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1215.75 | 6744.50 | 263.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1063.50 | 6691.75 | 7.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1314.25 | 6629.25 | 0.75 |
GUESTROOM419 | 958.25 | 6832.25 | 0.00 |
GUESTROOM420_423 | 1285.75 | 6665.00 | 1.25 |
GUESTROOM424 | 1098.00 | 6805.50 | 10.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6924.25 | 8756.00 | 4811.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 2158.75 | 0.00 | 2158.75 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 178.25 | 0.00 | 178.25 |
GUESTROOM104 | 0.00 | 77.50 | 0.00 | 77.50 |
GUESTROOM105 | 0.00 | 84.25 | 0.00 | 84.25 |
EMPLOYEELOUNGEFLR1 | 125.50 | 1081.25 | 83.00 | 472.00 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 58.50 | 0.00 | 58.50 |
GUESTROOM206_208 | 0.00 | 102.00 | 0.00 | 102.00 |
GUESTROOM209_212 | 0.00 | 56.00 | 0.00 | 56.00 |
GUESTROOM213 | 0.00 | 150.00 | 0.00 | 150.00 |
GUESTROOM214 | 0.00 | 102.00 | 0.00 | 102.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 5196.75 | 0.00 | 5196.75 |
GUESTROOM220_223 | 0.00 | 49.50 | 0.00 | 49.50 |
GUESTROOM224 | 0.00 | 66.75 | 0.00 | 66.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 56.00 | 0.00 | 56.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 108.00 | 0.00 | 108.00 |
GUESTROOM315_318 | 0.00 | 52.50 | 0.00 | 52.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 49.00 | 0.00 | 49.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 600.75 | 0.00 | 600.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 166.50 | 0.00 | 166.50 |
GUESTROOM413 | 0.00 | 0.50 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 63.00 | 0.00 | 63.00 |
GUESTROOM419 | 0.00 | 173.25 | 0.00 | 173.25 |
GUESTROOM420_423 | 0.00 | 63.00 | 0.00 | 63.00 |
GUESTROOM424 | 0.25 | 300.00 | 0.25 | 300.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.75 | 6718.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 3093.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 1612.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 2250.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 126.50 | 7673.00 | 83.25 | 6197.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:36
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.506481 |
SAC_FRONTLOUNGE SUPPLY FAN | 1.27 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.888420 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 298.79 |
CORRIDORFLR1 PTAC HEATING COIL | 15197.57 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 478.52 |
102 PTAC HEATING COIL | 478.52 |
103 PTAC HEATING COIL | 678.30 |
104 PTAC HEATING COIL | 678.25 |
105 PTAC HEATING COIL | 678.25 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 298.72 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 298.79 |
CORRIDORFLR2 PTAC HEATING COIL | 1923.70 |
201 PTAC HEATING COIL | 678.30 |
202_205 PTAC HEATING COIL | 2713.20 |
206_208 PTAC HEATING COIL | 2150.30 |
209_212 PTAC HEATING COIL | 2713.20 |
213 PTAC HEATING COIL | 743.84 |
214 PTAC HEATING COIL | 678.25 |
215_218 PTAC HEATING COIL | 1913.93 |
219 PTAC HEATING COIL | 678.25 |
220_223 PTAC HEATING COIL | 2713.01 |
224 PTAC HEATING COIL | 678.25 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 298.72 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 298.79 |
CORRIDORFLR3 PTAC HEATING COIL | 1923.70 |
301 PTAC HEATING COIL | 678.30 |
302_305 PTAC HEATING COIL | 2713.20 |
306_308 PTAC HEATING COIL | 2150.30 |
309_312 PTAC HEATING COIL | 2713.20 |
313 PTAC HEATING COIL | 678.30 |
314 PTAC HEATING COIL | 717.52 |
315_318 PTAC HEATING COIL | 2713.01 |
319 PTAC HEATING COIL | 478.48 |
320_323 PTAC HEATING COIL | 2713.01 |
324 PTAC HEATING COIL | 678.25 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 298.72 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 298.79 |
CORRIDORFLR4 PTAC HEATING COIL | 2276.51 |
401 PTAC HEATING COIL | 1038.01 |
402_405 PTAC HEATING COIL | 2713.20 |
406_408 PTAC HEATING COIL | 2150.30 |
409_412 PTAC HEATING COIL | 2713.20 |
413 PTAC HEATING COIL | 678.30 |
414 PTAC HEATING COIL | 678.25 |
415_418 PTAC HEATING COIL | 2713.01 |
419 PTAC HEATING COIL | 733.87 |
420_423 PTAC HEATING COIL | 2713.01 |
424 PTAC HEATING COIL | 845.69 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 298.72 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.765656 | 0.506481 | 9210.80 |
SAC_FRONTLOUNGE COOLING COIL | 0.721539 | 1.27 | 26579.93 |
SAC_MEETINGROOM COOLING COIL | 0.693133 | 0.553856 | 12859.01 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.746848 | 0.888420 | 17118.76 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 1.27 |
RESTROOMFLR1 DIRECT AIR | 0.099419 |
MEETINGROOMFLR1 DIRECT AIR | 0.553856 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.625872 |
EXERCISECENTERFLR1 DIRECT AIR | 0.163129 |
FRONTOFFICEFLR1 DIRECT AIR | 0.506481 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.506481 |
SAC_FRONTLOUNGE MAIN BRANCH | 1.27 |
SAC_MEETINGROOM MAIN BRANCH | 0.553856 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.888420 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.506481 |
SAC_FRONTLOUNGE | 1.27 |
SAC_MEETINGROOM | 0.553856 |
SAC_EXC_EMPLGE_RESTRM | 0.888420 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.506481 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 1.27 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.553856 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.888420 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.506481 | 0.506481 | 0.506481 | 0.506481 | 2792.94 | 9210.80 | 1.00 |
SAC_FRONTLOUNGE | 1.27 | 1.27 | 1.27 | 1.27 | 11706.54 | 26579.93 | 1.00 |
SAC_MEETINGROOM | 0.553856 | 0.553856 | 0.553856 | 0.553856 | 6268.77 | 12859.01 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.888420 | 0.888420 | 0.888420 | 0.888420 | 4682.29 | 17118.76 | 0.183617 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 2792.94 |
SAC_FRONTLOUNGE HEATING COIL | 11706.54 |
SAC_MEETINGROOM HEATING COIL | 6268.77 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 4682.29 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.553856 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.46 | 14.02 |
February | 23.17 | 16.67 |
March | 23.99 | 20.28 |
April | 25.56 | 25.86 |
May | 27.40 | 32.05 |
June | 28.60 | 35.24 |
July | 29.08 | 36.21 |
August | 29.05 | 36.44 |
September | 28.19 | 33.05 |
October | 26.87 | 27.59 |
November | 25.39 | 21.57 |
December | 22.58 | 14.93 |
Annual Sum or Average | 26.04 | 26.21 |
Minimum of Months | 22.46 | 14.02 |
Maximum of Months | 29.08 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.02 | 14.02 |
February | 24.53 | 16.67 |
March | 25.16 | 20.28 |
April | 26.41 | 25.86 |
May | 27.97 | 32.05 |
June | 28.89 | 35.24 |
July | 29.21 | 36.21 |
August | 29.23 | 36.44 |
September | 28.33 | 33.05 |
October | 26.97 | 27.59 |
November | 25.60 | 21.57 |
December | 24.21 | 14.93 |
Annual Sum or Average | 26.72 | 26.21 |
Minimum of Months | 24.02 | 14.02 |
Maximum of Months | 29.23 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 14.02 |
February | 22.49 | 16.67 |
March | 23.34 | 20.28 |
April | 24.90 | 25.86 |
May | 26.79 | 32.05 |
June | 27.97 | 35.24 |
July | 28.46 | 36.21 |
August | 28.43 | 36.44 |
September | 27.51 | 33.05 |
October | 26.20 | 27.59 |
November | 24.66 | 21.57 |
December | 21.86 | 14.93 |
Annual Sum or Average | 25.37 | 26.21 |
Minimum of Months | 21.69 | 14.02 |
Maximum of Months | 28.46 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 14.02 |
February | 23.44 | 16.67 |
March | 23.77 | 20.28 |
April | 23.89 | 25.86 |
May | 23.89 | 32.05 |
June | 23.89 | 35.24 |
July | 23.89 | 36.21 |
August | 23.89 | 36.44 |
September | 23.89 | 33.05 |
October | 23.89 | 27.59 |
November | 23.81 | 21.57 |
December | 23.20 | 14.93 |
Annual Sum or Average | 23.71 | 26.21 |
Minimum of Months | 23.11 | 14.02 |
Maximum of Months | 23.89 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.03 | 14.02 |
February | 23.25 | 16.67 |
March | 23.42 | 20.28 |
April | 23.53 | 25.86 |
May | 23.71 | 32.05 |
June | 23.78 | 35.24 |
July | 23.79 | 36.21 |
August | 23.81 | 36.44 |
September | 23.72 | 33.05 |
October | 23.62 | 27.59 |
November | 23.47 | 21.57 |
December | 23.12 | 14.93 |
Annual Sum or Average | 23.52 | 26.21 |
Minimum of Months | 23.03 | 14.02 |
Maximum of Months | 23.81 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.36 | 14.02 |
February | 23.56 | 16.67 |
March | 23.74 | 20.28 |
April | 23.86 | 25.86 |
May | 23.89 | 32.05 |
June | 23.89 | 35.24 |
July | 23.89 | 36.21 |
August | 23.89 | 36.44 |
September | 23.89 | 33.05 |
October | 23.88 | 27.59 |
November | 23.79 | 21.57 |
December | 23.42 | 14.93 |
Annual Sum or Average | 23.76 | 26.21 |
Minimum of Months | 23.36 | 14.02 |
Maximum of Months | 23.89 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.83 | 14.02 |
February | 26.20 | 16.67 |
March | 26.56 | 20.28 |
April | 27.06 | 25.86 |
May | 27.67 | 32.05 |
June | 27.98 | 35.24 |
July | 28.04 | 36.21 |
August | 28.08 | 36.44 |
September | 27.79 | 33.05 |
October | 27.34 | 27.59 |
November | 26.74 | 21.57 |
December | 25.93 | 14.93 |
Annual Sum or Average | 27.11 | 26.21 |
Minimum of Months | 25.83 | 14.02 |
Maximum of Months | 28.08 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 14.02 |
February | 22.65 | 16.67 |
March | 23.06 | 20.28 |
April | 23.31 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.17 | 21.57 |
December | 22.33 | 14.93 |
Annual Sum or Average | 23.06 | 26.21 |
Minimum of Months | 22.18 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 14.02 |
February | 22.42 | 16.67 |
March | 22.90 | 20.28 |
April | 23.27 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.31 | 27.59 |
November | 23.05 | 21.57 |
December | 22.05 | 14.93 |
Annual Sum or Average | 22.96 | 26.21 |
Minimum of Months | 21.89 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 14.02 |
February | 21.69 | 16.67 |
March | 21.72 | 20.28 |
April | 21.75 | 25.86 |
May | 21.76 | 32.05 |
June | 21.77 | 35.24 |
July | 21.80 | 36.21 |
August | 21.79 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.63 | 14.93 |
Annual Sum or Average | 21.73 | 26.21 |
Minimum of Months | 21.61 | 14.02 |
Maximum of Months | 21.80 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 14.02 |
February | 21.74 | 16.67 |
March | 21.74 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.77 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.71 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.71 | 14.02 |
Maximum of Months | 21.77 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.75 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.75 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.09 | 14.02 |
February | 23.08 | 16.67 |
March | 23.01 | 20.28 |
April | 22.65 | 25.86 |
May | 22.22 | 32.05 |
June | 21.94 | 35.24 |
July | 21.85 | 36.21 |
August | 21.85 | 36.44 |
September | 22.10 | 33.05 |
October | 22.50 | 27.59 |
November | 22.91 | 21.57 |
December | 23.11 | 14.93 |
Annual Sum or Average | 22.52 | 26.21 |
Minimum of Months | 21.85 | 14.02 |
Maximum of Months | 23.11 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.48 | 14.02 |
February | 51.82 | 16.67 |
March | 52.22 | 20.28 |
April | 52.98 | 25.86 |
May | 53.89 | 32.05 |
June | 54.33 | 35.24 |
July | 54.43 | 36.21 |
August | 54.52 | 36.44 |
September | 54.15 | 33.05 |
October | 53.43 | 27.59 |
November | 52.64 | 21.57 |
December | 51.55 | 14.93 |
Annual Sum or Average | 53.13 | 26.21 |
Minimum of Months | 51.48 | 14.02 |
Maximum of Months | 54.52 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 70.02 | 14.02 |
February | 70.41 | 16.67 |
March | 70.78 | 20.28 |
April | 71.62 | 25.86 |
May | 72.76 | 32.05 |
June | 73.23 | 35.24 |
July | 73.35 | 36.21 |
August | 73.53 | 36.44 |
September | 73.15 | 33.05 |
October | 72.35 | 27.59 |
November | 71.63 | 21.57 |
December | 70.17 | 14.93 |
Annual Sum or Average | 71.92 | 26.21 |
Minimum of Months | 70.02 | 14.02 |
Maximum of Months | 73.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.67 | 14.02 |
February | 23.78 | 16.67 |
March | 23.88 | 20.28 |
April | 23.89 | 25.86 |
May | 23.89 | 32.05 |
June | 23.89 | 35.24 |
July | 23.89 | 36.21 |
August | 23.89 | 36.44 |
September | 23.89 | 33.05 |
October | 23.89 | 27.59 |
November | 23.88 | 21.57 |
December | 23.70 | 14.93 |
Annual Sum or Average | 23.84 | 26.21 |
Minimum of Months | 23.67 | 14.02 |
Maximum of Months | 23.89 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.75 | 14.02 |
February | 23.84 | 16.67 |
March | 23.89 | 20.28 |
April | 23.89 | 25.86 |
May | 23.89 | 32.05 |
June | 23.89 | 35.24 |
July | 23.89 | 36.21 |
August | 23.89 | 36.44 |
September | 23.89 | 33.05 |
October | 23.89 | 27.59 |
November | 23.89 | 21.57 |
December | 23.77 | 14.93 |
Annual Sum or Average | 23.86 | 26.21 |
Minimum of Months | 23.75 | 14.02 |
Maximum of Months | 23.89 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.48 | 14.02 |
February | 22.53 | 16.67 |
March | 23.87 | 20.28 |
April | 26.10 | 25.86 |
May | 28.65 | 32.05 |
June | 30.21 | 35.24 |
July | 30.66 | 36.21 |
August | 30.45 | 36.44 |
September | 29.01 | 33.05 |
October | 26.95 | 27.59 |
November | 24.90 | 21.57 |
December | 21.81 | 14.93 |
Annual Sum or Average | 26.40 | 26.21 |
Minimum of Months | 21.48 | 14.02 |
Maximum of Months | 30.66 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 14.02 |
February | 23.47 | 16.67 |
March | 24.22 | 20.28 |
April | 25.49 | 25.86 |
May | 26.90 | 32.05 |
June | 27.78 | 35.24 |
July | 28.03 | 36.21 |
August | 27.94 | 36.44 |
September | 27.16 | 33.05 |
October | 25.99 | 27.59 |
November | 24.74 | 21.57 |
December | 23.02 | 14.93 |
Annual Sum or Average | 25.64 | 26.21 |
Minimum of Months | 22.84 | 14.02 |
Maximum of Months | 28.03 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.87 | 14.02 |
February | 23.75 | 16.67 |
March | 24.72 | 20.28 |
April | 26.59 | 25.86 |
May | 28.83 | 32.05 |
June | 30.24 | 35.24 |
July | 30.78 | 36.21 |
August | 30.75 | 36.44 |
September | 29.75 | 33.05 |
October | 28.18 | 27.59 |
November | 26.50 | 21.57 |
December | 23.01 | 14.93 |
Annual Sum or Average | 27.18 | 26.21 |
Minimum of Months | 22.87 | 14.02 |
Maximum of Months | 30.78 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.65 | 14.02 |
February | 23.81 | 16.67 |
March | 23.88 | 20.28 |
April | 23.98 | 25.86 |
May | 24.42 | 32.05 |
June | 24.94 | 35.24 |
July | 25.19 | 36.21 |
August | 25.15 | 36.44 |
September | 24.59 | 33.05 |
October | 24.10 | 27.59 |
November | 23.89 | 21.57 |
December | 23.67 | 14.93 |
Annual Sum or Average | 24.28 | 26.21 |
Minimum of Months | 23.65 | 14.02 |
Maximum of Months | 25.19 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 14.02 |
February | 22.74 | 16.67 |
March | 23.78 | 20.28 |
April | 25.67 | 25.86 |
May | 27.96 | 32.05 |
June | 29.37 | 35.24 |
July | 29.92 | 36.21 |
August | 29.89 | 36.44 |
September | 28.81 | 33.05 |
October | 27.23 | 27.59 |
November | 25.43 | 21.57 |
December | 21.91 | 14.93 |
Annual Sum or Average | 26.22 | 26.21 |
Minimum of Months | 21.71 | 14.02 |
Maximum of Months | 29.92 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.50 | 14.02 |
February | 22.38 | 16.67 |
March | 23.02 | 20.28 |
April | 23.32 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.16 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 22.93 | 26.21 |
Minimum of Months | 21.50 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | 14.02 |
February | 21.74 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.70 | 14.93 |
Annual Sum or Average | 21.74 | 26.21 |
Minimum of Months | 21.68 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 14.02 |
February | 21.74 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.77 | 35.24 |
July | 21.77 | 36.21 |
August | 21.77 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.71 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.69 | 14.02 |
Maximum of Months | 21.77 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 14.02 |
February | 21.74 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.71 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.71 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 14.02 |
February | 21.72 | 16.67 |
March | 21.74 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.77 | 35.24 |
July | 21.80 | 36.21 |
August | 21.78 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.65 | 14.93 |
Annual Sum or Average | 21.74 | 26.21 |
Minimum of Months | 21.63 | 14.02 |
Maximum of Months | 21.80 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.77 | 35.24 |
July | 21.78 | 36.21 |
August | 21.77 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.73 | 14.02 |
Maximum of Months | 21.78 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 14.02 |
February | 23.33 | 16.67 |
March | 23.33 | 20.28 |
April | 23.33 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.33 | 21.57 |
December | 23.33 | 14.93 |
Annual Sum or Average | 23.33 | 26.21 |
Minimum of Months | 23.33 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 32.21 | 14.02 |
February | 32.61 | 16.67 |
March | 33.01 | 20.28 |
April | 33.74 | 25.86 |
May | 34.72 | 32.05 |
June | 35.36 | 35.24 |
July | 35.57 | 36.21 |
August | 35.58 | 36.44 |
September | 35.00 | 33.05 |
October | 34.18 | 27.59 |
November | 33.46 | 21.57 |
December | 32.31 | 14.93 |
Annual Sum or Average | 33.99 | 26.21 |
Minimum of Months | 32.21 | 14.02 |
Maximum of Months | 35.58 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 14.02 |
February | 22.32 | 16.67 |
March | 22.56 | 20.28 |
April | 23.08 | 25.86 |
May | 23.95 | 32.05 |
June | 24.66 | 35.24 |
July | 24.90 | 36.21 |
August | 24.89 | 36.44 |
September | 24.17 | 33.05 |
October | 23.30 | 27.59 |
November | 22.61 | 21.57 |
December | 22.26 | 14.93 |
Annual Sum or Average | 23.41 | 26.21 |
Minimum of Months | 22.18 | 14.02 |
Maximum of Months | 24.90 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.75 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.75 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.77 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.73 | 14.02 |
Maximum of Months | 21.77 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 14.02 |
February | 23.41 | 16.67 |
March | 24.40 | 20.28 |
April | 26.01 | 25.86 |
May | 27.78 | 32.05 |
June | 28.86 | 35.24 |
July | 29.16 | 36.21 |
August | 29.04 | 36.44 |
September | 28.05 | 33.05 |
October | 26.58 | 27.59 |
November | 25.06 | 21.57 |
December | 22.79 | 14.93 |
Annual Sum or Average | 26.16 | 26.21 |
Minimum of Months | 22.55 | 14.02 |
Maximum of Months | 29.16 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.45 | 14.02 |
February | 22.81 | 16.67 |
March | 24.48 | 20.28 |
April | 27.24 | 25.86 |
May | 30.45 | 32.05 |
June | 32.35 | 35.24 |
July | 32.86 | 36.21 |
August | 32.61 | 36.44 |
September | 30.88 | 33.05 |
October | 28.31 | 27.59 |
November | 25.82 | 21.57 |
December | 21.87 | 14.93 |
Annual Sum or Average | 27.62 | 26.21 |
Minimum of Months | 21.45 | 14.02 |
Maximum of Months | 32.86 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 14.02 |
February | 23.63 | 16.67 |
March | 24.74 | 20.28 |
April | 26.81 | 25.86 |
May | 29.22 | 32.05 |
June | 30.71 | 35.24 |
July | 31.27 | 36.21 |
August | 31.23 | 36.44 |
September | 30.17 | 33.05 |
October | 28.47 | 27.59 |
November | 26.64 | 21.57 |
December | 22.77 | 14.93 |
Annual Sum or Average | 27.37 | 26.21 |
Minimum of Months | 22.60 | 14.02 |
Maximum of Months | 31.27 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 14.02 |
February | 23.41 | 16.67 |
March | 23.75 | 20.28 |
April | 23.89 | 25.86 |
May | 23.99 | 32.05 |
June | 24.29 | 35.24 |
July | 24.46 | 36.21 |
August | 24.41 | 36.44 |
September | 24.06 | 33.05 |
October | 23.91 | 27.59 |
November | 23.84 | 21.57 |
December | 22.98 | 14.93 |
Annual Sum or Average | 23.83 | 26.21 |
Minimum of Months | 22.88 | 14.02 |
Maximum of Months | 24.46 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.27 | 14.02 |
February | 22.55 | 16.67 |
March | 23.83 | 20.28 |
April | 25.96 | 25.86 |
May | 28.46 | 32.05 |
June | 29.96 | 35.24 |
July | 30.53 | 36.21 |
August | 30.50 | 36.44 |
September | 29.34 | 33.05 |
October | 27.61 | 27.59 |
November | 25.61 | 21.57 |
December | 21.53 | 14.93 |
Annual Sum or Average | 26.45 | 26.21 |
Minimum of Months | 21.27 | 14.02 |
Maximum of Months | 30.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.86 | 14.02 |
February | 21.96 | 16.67 |
March | 22.82 | 20.28 |
April | 23.29 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.32 | 27.59 |
November | 23.03 | 21.57 |
December | 21.16 | 14.93 |
Annual Sum or Average | 22.76 | 26.21 |
Minimum of Months | 20.86 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 14.02 |
February | 22.38 | 16.67 |
March | 23.03 | 20.28 |
April | 23.32 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.15 | 21.57 |
December | 21.67 | 14.93 |
Annual Sum or Average | 22.92 | 26.21 |
Minimum of Months | 21.44 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 14.02 |
February | 22.42 | 16.67 |
March | 23.03 | 20.28 |
April | 23.32 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.14 | 21.57 |
December | 21.75 | 14.93 |
Annual Sum or Average | 22.93 | 26.21 |
Minimum of Months | 21.55 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 14.02 |
February | 21.73 | 16.67 |
March | 21.74 | 20.28 |
April | 21.75 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.68 | 14.93 |
Annual Sum or Average | 21.74 | 26.21 |
Minimum of Months | 21.67 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 14.02 |
February | 22.47 | 16.67 |
March | 23.04 | 20.28 |
April | 23.32 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.22 | 21.57 |
December | 21.84 | 14.93 |
Annual Sum or Average | 22.96 | 26.21 |
Minimum of Months | 21.66 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.77 | 35.24 |
July | 21.78 | 36.21 |
August | 21.77 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.69 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.69 | 14.02 |
Maximum of Months | 21.78 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.75 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.75 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.55 | 14.02 |
February | 25.15 | 16.67 |
March | 25.69 | 20.28 |
April | 26.48 | 25.86 |
May | 27.31 | 32.05 |
June | 27.91 | 35.24 |
July | 28.11 | 36.21 |
August | 28.05 | 36.44 |
September | 27.49 | 33.05 |
October | 26.76 | 27.59 |
November | 26.01 | 21.57 |
December | 24.65 | 14.93 |
Annual Sum or Average | 26.52 | 26.21 |
Minimum of Months | 24.55 | 14.02 |
Maximum of Months | 28.11 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.04 | 14.02 |
February | 23.23 | 16.67 |
March | 23.31 | 20.28 |
April | 23.33 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.33 | 21.57 |
December | 23.04 | 14.93 |
Annual Sum or Average | 23.27 | 26.21 |
Minimum of Months | 23.04 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.76 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.73 | 14.02 |
Maximum of Months | 21.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 14.02 |
February | 22.71 | 16.67 |
March | 23.16 | 20.28 |
April | 23.33 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.33 | 27.59 |
November | 23.25 | 21.57 |
December | 22.18 | 14.93 |
Annual Sum or Average | 23.06 | 26.21 |
Minimum of Months | 22.11 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.10 | 14.02 |
February | 23.20 | 16.67 |
March | 24.42 | 20.28 |
April | 26.27 | 25.86 |
May | 28.23 | 32.05 |
June | 29.41 | 35.24 |
July | 29.72 | 36.21 |
August | 29.59 | 36.44 |
September | 28.50 | 33.05 |
October | 26.87 | 27.59 |
November | 25.15 | 21.57 |
December | 22.39 | 14.93 |
Annual Sum or Average | 26.34 | 26.21 |
Minimum of Months | 22.10 | 14.02 |
Maximum of Months | 29.72 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | 14.02 |
February | 22.66 | 16.67 |
March | 24.51 | 20.28 |
April | 27.53 | 25.86 |
May | 31.00 | 32.05 |
June | 33.01 | 35.24 |
July | 33.53 | 36.21 |
August | 33.29 | 36.44 |
September | 31.45 | 33.05 |
October | 28.68 | 27.59 |
November | 25.96 | 21.57 |
December | 21.55 | 14.93 |
Annual Sum or Average | 27.88 | 26.21 |
Minimum of Months | 21.09 | 14.02 |
Maximum of Months | 33.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 14.02 |
February | 23.35 | 16.67 |
March | 24.71 | 20.28 |
April | 27.11 | 25.86 |
May | 29.84 | 32.05 |
June | 31.41 | 35.24 |
July | 31.96 | 36.21 |
August | 31.98 | 36.44 |
September | 30.74 | 33.05 |
October | 28.76 | 27.59 |
November | 26.58 | 21.57 |
December | 22.24 | 14.93 |
Annual Sum or Average | 27.58 | 26.21 |
Minimum of Months | 22.02 | 14.02 |
Maximum of Months | 31.98 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 14.02 |
February | 22.88 | 16.67 |
March | 23.39 | 20.28 |
April | 23.98 | 25.86 |
May | 24.46 | 32.05 |
June | 24.91 | 35.24 |
July | 25.08 | 36.21 |
August | 25.03 | 36.44 |
September | 24.60 | 33.05 |
October | 24.12 | 27.59 |
November | 23.49 | 21.57 |
December | 22.48 | 14.93 |
Annual Sum or Average | 23.91 | 26.21 |
Minimum of Months | 22.38 | 14.02 |
Maximum of Months | 25.08 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | 14.02 |
February | 22.30 | 16.67 |
March | 23.77 | 20.28 |
April | 26.21 | 25.86 |
May | 29.00 | 32.05 |
June | 30.57 | 35.24 |
July | 31.13 | 36.21 |
August | 31.15 | 36.44 |
September | 29.82 | 33.05 |
October | 27.82 | 27.59 |
November | 25.47 | 21.57 |
December | 21.08 | 14.93 |
Annual Sum or Average | 26.61 | 26.21 |
Minimum of Months | 20.79 | 14.02 |
Maximum of Months | 31.15 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 14.02 |
February | 21.65 | 16.67 |
March | 21.71 | 20.28 |
April | 21.76 | 25.86 |
May | 21.84 | 32.05 |
June | 22.06 | 35.24 |
July | 22.12 | 36.21 |
August | 22.04 | 36.44 |
September | 21.85 | 33.05 |
October | 21.77 | 27.59 |
November | 21.75 | 21.57 |
December | 21.51 | 14.93 |
Annual Sum or Average | 21.79 | 26.21 |
Minimum of Months | 21.47 | 14.02 |
Maximum of Months | 22.12 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 14.02 |
February | 21.80 | 16.67 |
March | 22.65 | 20.28 |
April | 23.25 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.28 | 27.59 |
November | 22.73 | 21.57 |
December | 21.12 | 14.93 |
Annual Sum or Average | 22.70 | 26.21 |
Minimum of Months | 20.90 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 14.02 |
February | 21.81 | 16.67 |
March | 22.64 | 20.28 |
April | 23.24 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.27 | 27.59 |
November | 22.71 | 21.57 |
December | 21.14 | 14.93 |
Annual Sum or Average | 22.70 | 26.21 |
Minimum of Months | 20.95 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 14.02 |
February | 21.74 | 16.67 |
March | 21.74 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.79 | 35.24 |
July | 21.80 | 36.21 |
August | 21.80 | 36.44 |
September | 21.77 | 33.05 |
October | 21.76 | 27.59 |
November | 21.75 | 21.57 |
December | 21.69 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.69 | 14.02 |
Maximum of Months | 21.80 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 14.02 |
February | 21.96 | 16.67 |
March | 22.70 | 20.28 |
April | 23.25 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.30 | 27.59 |
November | 22.88 | 21.57 |
December | 21.34 | 14.93 |
Annual Sum or Average | 22.77 | 26.21 |
Minimum of Months | 21.16 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 14.02 |
February | 22.29 | 16.67 |
March | 22.87 | 20.28 |
April | 23.29 | 25.86 |
May | 23.33 | 32.05 |
June | 23.33 | 35.24 |
July | 23.33 | 36.21 |
August | 23.33 | 36.44 |
September | 23.33 | 33.05 |
October | 23.32 | 27.59 |
November | 23.01 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 22.90 | 26.21 |
Minimum of Months | 21.65 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.77 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.73 | 14.02 |
Maximum of Months | 21.77 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 14.02 |
February | 23.34 | 16.67 |
March | 24.09 | 20.28 |
April | 25.21 | 25.86 |
May | 26.33 | 32.05 |
June | 27.06 | 35.24 |
July | 27.27 | 36.21 |
August | 27.20 | 36.44 |
September | 26.47 | 33.05 |
October | 25.46 | 27.59 |
November | 24.32 | 21.57 |
December | 22.67 | 14.93 |
Annual Sum or Average | 25.17 | 26.21 |
Minimum of Months | 22.57 | 14.02 |
Maximum of Months | 27.27 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.02 |
February | 21.75 | 16.67 |
March | 21.75 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.79 | 35.24 |
July | 21.81 | 36.21 |
August | 21.79 | 36.44 |
September | 21.77 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.73 | 14.02 |
Maximum of Months | 21.81 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.02 |
February | 21.75 | 16.67 |
March | 21.74 | 20.28 |
April | 21.76 | 25.86 |
May | 21.76 | 32.05 |
June | 21.76 | 35.24 |
July | 21.77 | 36.21 |
August | 21.76 | 36.44 |
September | 21.76 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.73 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.73 | 14.02 |
Maximum of Months | 21.77 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 14.02 |
February | 21.75 | 16.67 |
March | 21.74 | 20.28 |
April | 21.76 | 25.86 |
May | 21.77 | 32.05 |
June | 21.82 | 35.24 |
July | 21.88 | 36.21 |
August | 21.84 | 36.44 |
September | 21.77 | 33.05 |
October | 21.76 | 27.59 |
November | 21.76 | 21.57 |
December | 21.70 | 14.93 |
Annual Sum or Average | 21.77 | 26.21 |
Minimum of Months | 21.70 | 14.02 |
Maximum of Months | 21.88 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 14.02 |
February | 23.04 | 16.67 |
March | 24.34 | 20.28 |
April | 26.39 | 25.86 |
May | 28.61 | 32.05 |
June | 29.87 | 35.24 |
July | 30.18 | 36.21 |
August | 30.08 | 36.44 |
September | 28.84 | 33.05 |
October | 26.96 | 27.59 |
November | 24.96 | 21.57 |
December | 22.07 | 14.93 |
Annual Sum or Average | 26.45 | 26.21 |
Minimum of Months | 21.81 | 14.02 |
Maximum of Months | 30.18 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | 14.02 |
February | 22.45 | 16.67 |
March | 24.45 | 20.28 |
April | 27.72 | 25.86 |
May | 31.48 | 32.05 |
June | 33.54 | 35.24 |
July | 34.06 | 36.21 |
August | 33.89 | 36.44 |
September | 31.87 | 33.05 |
October | 28.83 | 27.59 |
November | 25.81 | 21.57 |
December | 21.16 | 14.93 |
Annual Sum or Average | 28.02 | 26.21 |
Minimum of Months | 20.70 | 14.02 |
Maximum of Months | 34.06 | 36.44 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:36
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.155629E+12 | 91955.767 | 07-JAN-08:00 | 25182.171 | 43578.554 | 10390.879 | 0.000 | 12796.050 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.146156E+12 | 98624.471 | 25-FEB-08:00 | 25182.171 | 43578.554 | 10390.879 | 0.000 | 19464.755 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.170193E+12 | 103616.114 | 31-MAR-19:15 | 27551.975 | 28549.175 | 9821.572 | 0.000 | 33497.279 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.182134E+12 | 106109.216 | 29-APR-17:15 | 26252.371 | 28657.799 | 9905.613 | 0.000 | 41285.321 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.213446E+12 | 118487.032 | 19-MAY-17:15 | 26252.371 | 28657.799 | 9988.572 | 0.000 | 53580.177 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.222540E+12 | 126649.232 | 16-JUN-17:15 | 26252.371 | 28657.799 | 10033.547 | 0.000 | 61697.402 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.234018E+12 | 127127.369 | 22-JUL-17:15 | 26252.371 | 28657.799 | 10044.775 | 0.000 | 62164.312 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.235263E+12 | 124688.063 | 06-AUG-16:15 | 18353.904 | 29675.143 | 10390.879 | 0.000 | 66260.024 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.212102E+12 | 117287.362 | 03-SEP-17:15 | 26252.371 | 28657.799 | 9971.953 | 0.000 | 52397.127 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.195573E+12 | 108619.046 | 06-OCT-17:45 | 26252.371 | 28657.799 | 9893.452 | 0.000 | 39619.311 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.167458E+12 | 98876.844 | 10-NOV-08:00 | 25182.171 | 43578.554 | 10390.879 | 0.000 | 19717.128 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.158489E+12 | 96313.599 | 01-DEC-08:00 | 25182.171 | 43578.554 | 10390.879 | 0.000 | 17153.882 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.229300E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.146156E+12 | 91955.767 | 18353.904 | 28549.175 | 9821.572 | 0.000 | 12796.050 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.235263E+12 | 127127.369 | 27551.975 | 43578.554 | 10390.879 | 0.000 | 66260.024 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:36
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.810026E+11 | 83221.101 | 14-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 43125.073 | 43125.073 | 43125.073 | 0.000 |
February | 0.717198E+11 | 83387.815 | 03-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 43291.787 | 43291.787 | 43291.787 | 0.000 |
March | 0.758792E+11 | 81684.654 | 04-MAR-09:30 | 0.000 | 40096.028 | 0.000 | 41588.626 | 41588.626 | 41588.626 | 0.000 |
April | 0.687658E+11 | 80386.974 | 07-APR-08:15 | 0.000 | 40096.028 | 0.000 | 40290.946 | 40290.946 | 40290.946 | 0.000 |
May | 0.662040E+11 | 78912.797 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 38816.769 | 38816.769 | 38816.769 | 0.000 |
June | 0.606176E+11 | 77305.482 | 01-JUN-08:00 | 0.000 | 40096.028 | 0.000 | 37209.453 | 37209.453 | 37209.453 | 0.000 |
July | 0.612992E+11 | 77125.318 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 37029.290 | 37029.290 | 37029.290 | 0.000 |
August | 0.626111E+11 | 77264.252 | 19-AUG-08:30 | 0.000 | 40096.028 | 0.000 | 37168.224 | 37168.224 | 37168.224 | 0.000 |
September | 0.639742E+11 | 78911.974 | 23-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 38815.946 | 38815.946 | 38815.946 | 0.000 |
October | 0.709698E+11 | 80397.868 | 28-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 40301.840 | 40301.840 | 40301.840 | 0.000 |
November | 0.733188E+11 | 82089.844 | 22-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 41993.815 | 41993.815 | 41993.815 | 0.000 |
December | 0.797030E+11 | 83370.894 | 30-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 43274.866 | 43274.866 | 43274.866 | 0.000 |
Annual Sum or Average | 0.836065E+12 | 0.000 | ||||||||
Minimum of Months | 0.606176E+11 | 77125.318 | 0.000 | 40096.028 | 0.000 | 37029.290 | 37029.290 | 37029.290 | 0.000 | |
Maximum of Months | 0.810026E+11 | 83387.815 | 0.000 | 40096.028 | 0.000 | 43291.787 | 43291.787 | 43291.787 | 0.000 |