Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2015-09-14 08:44:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3968.69 | 988.81 | 1065.39 |
Net Site Energy | 3968.69 | 988.81 | 1065.39 |
Total Source Energy | 9429.07 | 2349.29 | 2531.23 |
Net Source Energy | 9429.07 | 2349.29 | 2531.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 788.01 | 292.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 132.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 601.95 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 295.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 793.11 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2461.36 | 1507.33 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 788.01 | 292.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 132.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 578.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 295.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 793.11 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 172.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 326.43 | 291.49 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 161.59 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 660.75 | 404.64 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 160.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 302.97 | 270.54 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 149.98 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 613.26 | 375.56 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2461.36 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2461.36 | 100.00 |
Total On-Site and Utility Electric Sources | 2461.36 | 100.00 |
Total Electricity End Uses | 2461.36 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2171.25 |
Time Setpoint Not Met During Occupied Cooling | 2070.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6381.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.14 08:44 |
RunPeriod | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 90.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 211.83 | 635.46 | 211.83 | 635.46 |
Window Opening Area [m2] | 184.20 | 8.38 | 72.38 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 10.87 | 3.95 | 11.39 | 3.13 | 15.24 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 211.83 | 556.77 | 116.50 | 607.21 |
Window Opening Area [m2] | 179.26 | 8.38 | 67.45 | 6.62 | 96.82 |
Window-Wall Ratio [%] | 12.01 | 3.95 | 12.11 | 5.68 | 15.95 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 6.9675 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 11.1480 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 15.3285 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 12.5415 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 18.1154 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 20.9024 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 11.8403 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 16.7220 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 8.3610 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2155.0206 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 12.5415 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 15.3285 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 8.3610 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 11.1480 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 8.3610 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 6.9675 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 11.1480 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 11.8403 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 11.8403 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 11.8403 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 11.1480 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 8.3610 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 11.2819 | 15.53 | 28.2097 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 11.5457 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 7.8766 | 26.23 | 260.8031 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 0.00 | 90.00 | N |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 270.00 | 90.00 | W |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 90.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 270.00 | 90.00 | W |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 270.00 | 90.00 | W |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 90.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 270.00 | 90.00 | W |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 90.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 270.00 | 90.00 | W |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 90.00 | 90.00 | E |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 90.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 90.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 90.00 | 90.00 | E |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 90.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 90.00 | 90.00 | E |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 90.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 0.00 | 90.00 | N |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 90.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 90.00 | 90.00 | E |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 90.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 0.00 | 90.00 | N |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 270.00 | 90.00 | W |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.12 | 270.00 | 90.00 | W |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 270.00 | 90.00 | W |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 270.00 | 90.00 | W |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 90.00 | 90.00 | E |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 90.00 | 90.00 | E |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 90.00 | 90.00 | E |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 4.18 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 0.00 | 90.00 | N |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 180.00 | 90.00 | S |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 90.00 | 90.00 | E |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 20.07 | 270.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 8.36 | 90.00 | 90.00 | E |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 0.00 | 90.00 | N |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 125.42 | 270.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 180.00 | 90.00 | S |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 270.00 | 90.00 | W |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 20.07 | 270.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 0.00 | 90.00 | N |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.12 | 270.00 | 90.00 | W |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 105.36 | 270.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 270.00 | 90.00 | W |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.45 | 270.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 270.00 | 90.00 | W |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.44 | 270.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 90.00 | 90.00 | E |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 15.05 | 270.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 90.00 | 90.00 | E |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 130.44 | 270.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 90.00 | 90.00 | E |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 32.61 | 270.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 4.18 | 90.00 | 90.00 | E |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 12.54 | 270.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 90.00 | 90.00 | E |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 0.00 | 90.00 | N |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.219 | 0.228 | 20.07 | 270.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_2_0_0 | 180.00 | 90.00 | S | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_16_0_0 | 0.00 | 90.00 | N | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_20_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM101_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM102_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM103_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM104_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM105_3_0_0 | 90.00 | 90.00 | E | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EXERCISECENTERFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM201_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM213_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM214_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM219_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM224_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM301_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM313_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM314_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM319_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM324_3_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_2_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_15_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM401_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM413_5_0_0 | 270.00 | 90.00 | W | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM414_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM419_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM424_3_0_0 | 90.00 | 90.00 | E | ||
Total or Average | 184.20 | 2.670 | 0.479 | 0.381 | ||||||||||||
North Total or Average | 8.38 | 2.670 | 0.479 | 0.381 | ||||||||||||
Non-North Total or Average | 175.82 | 2.670 | 0.479 | 0.381 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.54 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.54 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.54 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6131.78 | 4897.18 | 1234.60 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16453.08 | 13140.34 | 3312.74 | 0.80 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7592.46 | 5933.16 | 1659.30 | 0.78 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12776.59 | 10204.09 | 2572.50 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.00 | 10.24 | 10.86 | 10.31 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.00 | 10.24 | 10.86 | 10.31 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.00 | 10.24 | 10.86 | 10.31 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5844.3 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15681.8 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7253.2 | 3.18 | 10.86 | 11.50 | 10.69 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12177.7 | 3.15 | 10.76 | 11.39 | 10.54 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 80442.97 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1496.83 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1496.83 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 2004.47 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1869.22 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1674.88 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 4245.08 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1496.83 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 6197.20 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 4882.97 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 5987.31 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1882.34 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1759.10 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 5986.89 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1544.56 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 5986.89 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1710.74 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 4645.60 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1554.25 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 5987.31 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 4745.15 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 6146.25 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1555.72 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1873.93 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 6261.60 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1496.72 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 5988.18 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1496.72 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 6625.42 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 2413.25 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 6843.69 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 5588.24 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 7707.36 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 2103.68 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1918.35 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 7639.98 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 2092.63 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 7484.03 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 2339.77 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 6345.62 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 25833.24 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 13833.51 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 10550.73 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:ConstantVolume | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.54 | 622.50 | 0.37 | 430.00 | 1160.84 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.99 | 1133.19 | 1140.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.54 | 622.50 | 0.44 | 507.52 | 1160.84 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.55 | 622.50 | 0.77 | 879.98 | 1140.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.51 | 0.27 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 9891.85 | 11870.22 | 0.828 | 0.994 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 23.80 | 0.00698 |
RESTROOMFLR1 | 606.62 | 727.94 | 0.051 | 0.061 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:45:00 | 22.58 | 0.00698 |
MEETINGROOMFLR1 | 4348.42 | 5218.11 | 0.364 | 0.437 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.19 | 0.00698 |
GUESTROOM101 | 493.64 | 592.36 | 0.044 | 0.053 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM102 | 367.80 | 441.36 | 0.033 | 0.039 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM103 | 1433.13 | 1719.76 | 0.167 | 0.200 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM104 | 1315.65 | 1578.78 | 0.153 | 0.184 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM105 | 1794.76 | 2153.72 | 0.209 | 0.251 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
EMPLOYEELOUNGEFLR1 | 5738.66 | 6886.39 | 0.481 | 0.577 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
EXERCISECENTERFLR1 | 1335.75 | 1602.90 | 0.112 | 0.134 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79 | 0.00698 |
FRONTOFFICEFLR1 | 3689.17 | 4427.01 | 0.309 | 0.370 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM201 | 658.48 | 790.18 | 0.058 | 0.070 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.19 | 0.00698 |
GUESTROOM202_205 | 5833.92 | 7000.71 | 0.679 | 0.815 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM206_208 | 4824.67 | 5789.60 | 0.561 | 0.674 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 23.80 | 0.00698 |
GUESTROOM209_212 | 5416.87 | 6500.25 | 0.630 | 0.756 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM213 | 1533.38 | 1840.05 | 0.178 | 0.214 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM214 | 1558.92 | 1870.71 | 0.181 | 0.218 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM215_218 | 8838.78 | 10606.53 | 0.783 | 0.940 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM219 | 5777.16 | 6932.59 | 0.672 | 0.807 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM220_223 | 5352.22 | 6422.67 | 0.623 | 0.747 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM224 | 1573.90 | 1888.68 | 0.183 | 0.220 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM301 | 498.15 | 597.78 | 0.044 | 0.053 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 24.19 | 0.00698 |
GUESTROOM302_305 | 1803.10 | 2163.72 | 0.160 | 0.192 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM306_308 | 1703.43 | 2044.12 | 0.151 | 0.181 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM309_312 | 5386.80 | 6464.16 | 0.627 | 0.752 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM313 | 583.56 | 700.28 | 0.052 | 0.062 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 23.42 | 0.00698 |
GUESTROOM314 | 1474.11 | 1768.94 | 0.172 | 0.206 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM315_318 | 6031.74 | 7238.09 | 0.702 | 0.842 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM319 | 861.97 | 1034.36 | 0.076 | 0.092 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM320_323 | 5157.70 | 6189.25 | 0.600 | 0.720 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM324 | 506.80 | 608.16 | 0.045 | 0.054 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 24.29 | 0.00698 |
GUESTROOM401 | 1704.52 | 2045.42 | 0.198 | 0.238 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
GUESTROOM402_405 | 2425.87 | 2911.05 | 0.215 | 0.258 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 24.57 | 0.00698 |
GUESTROOM406_408 | 2297.86 | 2757.44 | 0.204 | 0.244 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 24.57 | 0.00698 |
GUESTROOM409_412 | 6237.60 | 7485.12 | 0.726 | 0.871 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 24.57 | 0.00698 |
GUESTROOM413 | 810.62 | 972.74 | 0.072 | 0.086 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 24.57 | 0.00698 |
GUESTROOM414 | 615.83 | 738.99 | 0.055 | 0.066 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:15:00 | 25.31 | 0.00698 |
GUESTROOM415_418 | 5981.41 | 7177.69 | 0.696 | 0.835 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 24.67 | 0.00698 |
GUESTROOM419 | 1630.66 | 1956.79 | 0.190 | 0.228 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 25.05 | 0.00698 |
GUESTROOM420_423 | 5832.54 | 6999.05 | 0.679 | 0.814 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 10:45:00 | 24.67 | 0.00698 |
GUESTROOM424 | 1638.51 | 1966.21 | 0.191 | 0.229 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 25.05 | 0.00698 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR1 | 13478.12 | 16173.74 | 1.127 | 1.353 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR2 | 2902.60 | 3483.12 | 0.243 | 0.291 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 26.79 | 0.00698 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR3 | 1567.52 | 1881.02 | 0.131 | 0.157 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 26.38 | 0.00698 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR4 | 2076.57 | 2491.88 | 0.174 | 0.208 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 26.94 | 0.00698 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 3017.62 | 3621.14 | 0.086 | 0.236 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -41.90 | 0.00006 |
RESTROOMFLR1 | 184.50 | 221.40 | 0.005 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
MEETINGROOMFLR1 | 1095.16 | 1314.19 | 0.031 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90 | 0.00006 |
GUESTROOM101 | 183.02 | 219.63 | 0.005 | 0.013 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
GUESTROOM102 | 204.16 | 244.99 | 0.005 | 0.013 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
GUESTROOM103 | 815.14 | 978.17 | 0.023 | 0.028 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
GUESTROOM104 | 702.49 | 842.99 | 0.020 | 0.024 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
GUESTROOM105 | 540.55 | 648.65 | 0.015 | 0.019 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
EMPLOYEELOUNGEFLR1 | 548.68 | 658.41 | 0.016 | 0.051 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90 | 0.00006 |
EXERCISECENTERFLR1 | 375.01 | 450.01 | 0.011 | 0.043 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90 | 0.00006 |
FRONTOFFICEFLR1 | 1792.60 | 2151.12 | 0.051 | 0.062 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -41.90 | 0.00006 |
GUESTROOM201 | 385.59 | 462.71 | 0.010 | 0.013 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -41.90 | 0.00006 |
GUESTROOM202_205 | 1743.35 | 2092.02 | 0.050 | 0.060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -41.90 | 0.00006 |
GUESTROOM206_208 | 1357.89 | 1629.47 | 0.039 | 0.047 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
GUESTROOM209_212 | 1456.45 | 1747.73 | 0.042 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -41.90 | 0.00006 |
GUESTROOM213 | 713.37 | 856.05 | 0.020 | 0.025 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:30:00 | -41.90 | 0.00006 |
GUESTROOM214 | 610.73 | 732.87 | 0.017 | 0.021 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -41.90 | 0.00006 |
GUESTROOM215_218 | 582.75 | 699.30 | 0.015 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -41.90 | 0.00006 |
GUESTROOM219 | 431.95 | 518.34 | 0.012 | 0.015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -41.90 | 0.00006 |
GUESTROOM220_223 | 1304.47 | 1565.37 | 0.037 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
GUESTROOM224 | 570.43 | 684.51 | 0.016 | 0.020 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | -41.90 | 0.00006 |
GUESTROOM301 | 470.12 | 564.14 | 0.013 | 0.015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -41.90 | 0.00006 |
GUESTROOM302_305 | 1052.65 | 1263.19 | 0.028 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -41.90 | 0.00006 |
GUESTROOM306_308 | 892.00 | 1070.39 | 0.024 | 0.043 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -41.90 | 0.00006 |
GUESTROOM309_312 | 1700.88 | 2041.06 | 0.049 | 0.058 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:45:00 | -41.90 | 0.00006 |
GUESTROOM313 | 471.34 | 565.61 | 0.013 | 0.015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
GUESTROOM314 | 706.43 | 847.71 | 0.020 | 0.024 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 15:45:00 | -41.90 | 0.00006 |
GUESTROOM315_318 | 1797.26 | 2156.71 | 0.051 | 0.062 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -41.90 | 0.00006 |
GUESTROOM319 | 158.77 | 190.53 | 0.004 | 0.013 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -41.90 | 0.00006 |
GUESTROOM320_323 | 1569.40 | 1883.28 | 0.045 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -41.90 | 0.00006 |
GUESTROOM324 | 303.15 | 363.77 | 0.008 | 0.013 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
GUESTROOM401 | 1155.79 | 1386.95 | 0.033 | 0.040 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -41.90 | 0.00006 |
GUESTROOM402_405 | 2402.72 | 2883.27 | 0.064 | 0.077 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -41.90 | 0.00006 |
GUESTROOM406_408 | 2041.22 | 2449.46 | 0.054 | 0.065 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -41.90 | 0.00006 |
GUESTROOM409_412 | 3001.81 | 3602.17 | 0.086 | 0.103 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 20:00:00 | -41.90 | 0.00006 |
GUESTROOM413 | 927.98 | 1113.58 | 0.025 | 0.030 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
GUESTROOM414 | 773.59 | 928.31 | 0.021 | 0.025 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90 | 0.00006 |
GUESTROOM415_418 | 2945.90 | 3535.08 | 0.084 | 0.101 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -41.90 | 0.00006 |
GUESTROOM419 | 888.67 | 1066.41 | 0.025 | 0.031 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | -41.90 | 0.00006 |
GUESTROOM420_423 | 2815.94 | 3379.13 | 0.081 | 0.097 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -41.90 | 0.00006 |
GUESTROOM424 | 1094.62 | 1313.55 | 0.031 | 0.038 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR1 | 64046.29 | 76855.55 | 1.830 | 2.196 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR2 | 1013.80 | 1216.56 | 0.029 | 0.038 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR3 | 1445.82 | 1734.98 | 0.041 | 0.050 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR4 | 3095.67 | 3714.81 | 0.089 | 0.106 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.37 | 0.37 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.99 | 0.99 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.44 | 0.44 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.77 | 0.77 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 4007.25 | 7513.25 | 3706.75 |
RESTROOMFLR1 | 2816.50 | 8256.50 | 2806.25 |
MEETINGROOMFLR1 | 1128.25 | 3595.25 | 709.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 4404.00 | 8760.00 | 4404.00 |
GUESTROOM104 | 3806.75 | 8759.50 | 3806.75 |
GUESTROOM105 | 1881.50 | 8712.75 | 1881.50 |
EMPLOYEELOUNGEFLR1 | 2488.00 | 3129.00 | 730.50 |
EXERCISECENTERFLR1 | 1021.00 | 3995.50 | 478.25 |
FRONTOFFICEFLR1 | 3179.50 | 7324.25 | 2942.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 3394.00 | 8742.50 | 3394.00 |
GUESTROOM206_208 | 3131.25 | 8737.50 | 3131.25 |
GUESTROOM209_212 | 2710.00 | 8757.75 | 2710.00 |
GUESTROOM213 | 4281.50 | 8760.00 | 4281.50 |
GUESTROOM214 | 3289.75 | 8706.25 | 3289.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 2354.50 | 5310.00 | 49.25 |
GUESTROOM220_223 | 1839.75 | 8555.00 | 1839.75 |
GUESTROOM224 | 3350.75 | 8672.00 | 3350.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 3387.50 | 8757.25 | 3387.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 3985.25 | 8708.75 | 3985.25 |
GUESTROOM315_318 | 2145.50 | 8416.50 | 2145.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 2857.00 | 8635.25 | 2857.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 5036.00 | 8662.25 | 5036.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 4184.75 | 8468.75 | 4182.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 3846.50 | 8180.75 | 3777.50 |
GUESTROOM419 | 3974.25 | 8349.25 | 3970.00 |
GUESTROOM420_423 | 3898.75 | 8211.00 | 3842.25 |
GUESTROOM424 | 4444.25 | 8403.75 | 4440.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7447.50 | 8760.00 | 6381.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
RESTROOMFLR1 | 1924.00 | 343.25 | 1924.00 | 343.25 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 41.50 | 14.50 | 41.50 | 14.50 |
GUESTROOM104 | 37.00 | 16.50 | 37.00 | 16.50 |
GUESTROOM105 | 14.25 | 24.00 | 14.25 | 24.00 |
EMPLOYEELOUNGEFLR1 | 1398.25 | 702.00 | 963.25 | 473.50 |
EXERCISECENTERFLR1 | 1.25 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 1.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 32.75 | 3.00 | 32.75 | 3.00 |
GUESTROOM206_208 | 31.75 | 12.00 | 31.75 | 12.00 |
GUESTROOM209_212 | 31.00 | 2.00 | 31.00 | 2.00 |
GUESTROOM213 | 32.75 | 2.00 | 32.75 | 2.00 |
GUESTROOM214 | 32.00 | 5.25 | 32.00 | 5.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 1445.75 | 0.00 | 1445.75 |
GUESTROOM220_223 | 19.00 | 2.50 | 19.00 | 2.50 |
GUESTROOM224 | 34.00 | 5.75 | 34.00 | 5.75 |
GUESTROOM301 | 1.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 36.75 | 2.00 | 36.75 | 2.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 32.00 | 4.00 | 32.00 | 4.00 |
GUESTROOM315_318 | 26.75 | 3.50 | 26.75 | 3.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 34.00 | 1.75 | 34.00 | 1.75 |
GUESTROOM324 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 19.25 | 10.00 | 19.25 | 10.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 29.00 | 9.50 | 29.00 | 9.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 29.25 | 6.00 | 29.25 | 6.00 |
GUESTROOM419 | 21.50 | 11.00 | 21.50 | 11.00 |
GUESTROOM420_423 | 31.75 | 5.75 | 31.75 | 5.75 |
GUESTROOM424 | 16.50 | 10.25 | 16.50 | 10.25 |
REARSTAIRSFLR1 | 3.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 1.00 | 1328.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 11.25 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 12.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 32.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 19.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 86.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 68.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 167.25 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2237.00 | 2531.75 | 2171.25 | 2070.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-14 08:44:19
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.370421 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.993931 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.771834 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR1 PTAC HEATING COIL | 80442.97 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1496.83 |
102 PTAC HEATING COIL | 1496.83 |
103 PTAC HEATING COIL | 2004.47 |
104 PTAC HEATING COIL | 1869.22 |
105 PTAC HEATING COIL | 1674.88 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 316.32 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR2 PTAC HEATING COIL | 4245.08 |
201 PTAC HEATING COIL | 1496.83 |
202_205 PTAC HEATING COIL | 6197.20 |
206_208 PTAC HEATING COIL | 4882.97 |
209_212 PTAC HEATING COIL | 5987.31 |
213 PTAC HEATING COIL | 1882.34 |
214 PTAC HEATING COIL | 1759.10 |
215_218 PTAC HEATING COIL | 5986.89 |
219 PTAC HEATING COIL | 1544.56 |
220_223 PTAC HEATING COIL | 5986.89 |
224 PTAC HEATING COIL | 1710.74 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 316.32 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR3 PTAC HEATING COIL | 4645.60 |
301 PTAC HEATING COIL | 1554.25 |
302_305 PTAC HEATING COIL | 5987.31 |
306_308 PTAC HEATING COIL | 4745.15 |
309_312 PTAC HEATING COIL | 6146.25 |
313 PTAC HEATING COIL | 1555.72 |
314 PTAC HEATING COIL | 1873.93 |
315_318 PTAC HEATING COIL | 6261.60 |
319 PTAC HEATING COIL | 1496.72 |
320_323 PTAC HEATING COIL | 5988.18 |
324 PTAC HEATING COIL | 1496.72 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 316.32 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR4 PTAC HEATING COIL | 6625.42 |
401 PTAC HEATING COIL | 2413.25 |
402_405 PTAC HEATING COIL | 6843.69 |
406_408 PTAC HEATING COIL | 5588.24 |
409_412 PTAC HEATING COIL | 7707.36 |
413 PTAC HEATING COIL | 2103.68 |
414 PTAC HEATING COIL | 1918.35 |
415_418 PTAC HEATING COIL | 7639.98 |
419 PTAC HEATING COIL | 2092.63 |
420_423 PTAC HEATING COIL | 7484.03 |
424 PTAC HEATING COIL | 2339.77 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 316.32 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.798655 | 0.370421 | 6131.78 |
SAC_FRONTLOUNGE COOLING COIL | 0.798655 | 0.993931 | 16453.08 |
SAC_MEETINGROOM COOLING COIL | 0.781454 | 0.437202 | 7592.46 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.798655 | 0.771834 | 12776.59 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.993931 |
RESTROOMFLR1 DIRECT AIR | 0.060900 |
MEETINGROOMFLR1 DIRECT AIR | 0.437202 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.576770 |
EXERCISECENTERFLR1 DIRECT AIR | 0.134164 |
FRONTOFFICEFLR1 DIRECT AIR | 0.370421 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.370421 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.993931 |
SAC_MEETINGROOM MAIN BRANCH | 0.437202 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.771834 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.370421 |
SAC_FRONTLOUNGE | 0.993931 |
SAC_MEETINGROOM | 0.437202 |
SAC_EXC_EMPLGE_RESTRM | 0.771834 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.370421 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.993931 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.437202 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.771834 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.370421 | 0.370421 | 0.370421 | 0.370421 | 6345.62 | 6131.78 | 1.00 |
SAC_FRONTLOUNGE | 0.993931 | 0.993931 | 0.993931 | 0.993931 | 25833.24 | 16453.08 | 1.00 |
SAC_MEETINGROOM | 0.437202 | 0.437202 | 0.437202 | 0.437202 | 13833.51 | 7592.46 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.771834 | 0.771834 | 0.771834 | 0.771834 | 10550.73 | 12776.59 | 0.173825 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 6345.62 |
SAC_FRONTLOUNGE HEATING COIL | 25833.24 |
SAC_MEETINGROOM HEATING COIL | 13833.51 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 10550.73 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.437202 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.19 | -17.6 |
February | 15.85 | -15.4 |
March | 15.92 | -10.3 |
April | 17.64 | 0.73 |
May | 20.70 | 10.60 |
June | 22.61 | 15.96 |
July | 23.16 | 16.86 |
August | 22.36 | 14.24 |
September | 20.58 | 6.72 |
October | 17.18 | -3.1 |
November | 17.16 | -17.6 |
December | 15.36 | -19.3 |
Annual Sum or Average | 18.66 | -1.4 |
Minimum of Months | 15.19 | -19.3 |
Maximum of Months | 23.16 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | -17.6 |
February | 21.20 | -15.4 |
March | 21.33 | -10.3 |
April | 22.33 | 0.73 |
May | 23.60 | 10.60 |
June | 24.45 | 15.96 |
July | 24.75 | 16.86 |
August | 24.24 | 14.24 |
September | 23.15 | 6.72 |
October | 21.85 | -3.1 |
November | 21.19 | -17.6 |
December | 21.16 | -19.3 |
Annual Sum or Average | 22.54 | -1.4 |
Minimum of Months | 21.16 | -19.3 |
Maximum of Months | 24.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.29 | -17.6 |
February | 14.92 | -15.4 |
March | 14.95 | -10.3 |
April | 16.74 | 0.73 |
May | 19.77 | 10.60 |
June | 21.78 | 15.96 |
July | 22.30 | 16.86 |
August | 21.49 | 14.24 |
September | 19.57 | 6.72 |
October | 16.24 | -3.1 |
November | 16.23 | -17.6 |
December | 14.50 | -19.3 |
Annual Sum or Average | 17.75 | -1.4 |
Minimum of Months | 14.29 | -19.3 |
Maximum of Months | 22.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.11 | -10.3 |
April | 21.43 | 0.73 |
May | 22.62 | 10.60 |
June | 23.38 | 15.96 |
July | 23.40 | 16.86 |
August | 23.11 | 14.24 |
September | 21.83 | 6.72 |
October | 21.20 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 21.88 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | -17.6 |
February | 20.90 | -15.4 |
March | 21.22 | -10.3 |
April | 22.06 | 0.73 |
May | 22.83 | 10.60 |
June | 23.42 | 15.96 |
July | 23.47 | 16.86 |
August | 23.30 | 14.24 |
September | 22.61 | 6.72 |
October | 21.73 | -3.1 |
November | 20.83 | -17.6 |
December | 20.68 | -19.3 |
Annual Sum or Average | 21.99 | -1.4 |
Minimum of Months | 20.68 | -19.3 |
Maximum of Months | 23.47 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | -17.6 |
February | 21.17 | -15.4 |
March | 21.25 | -10.3 |
April | 21.95 | 0.73 |
May | 23.17 | 10.60 |
June | 23.68 | 15.96 |
July | 23.72 | 16.86 |
August | 23.52 | 14.24 |
September | 22.52 | 6.72 |
October | 21.50 | -3.1 |
November | 21.18 | -17.6 |
December | 21.15 | -19.3 |
Annual Sum or Average | 22.17 | -1.4 |
Minimum of Months | 21.15 | -19.3 |
Maximum of Months | 23.72 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | -17.6 |
February | 23.13 | -15.4 |
March | 23.43 | -10.3 |
April | 24.44 | 0.73 |
May | 25.56 | 10.60 |
June | 26.21 | 15.96 |
July | 26.30 | 16.86 |
August | 26.04 | 14.24 |
September | 25.16 | 6.72 |
October | 23.99 | -3.1 |
November | 23.30 | -17.6 |
December | 23.04 | -19.3 |
Annual Sum or Average | 24.47 | -1.4 |
Minimum of Months | 23.00 | -19.3 |
Maximum of Months | 26.30 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.93 | -10.3 |
April | 19.88 | 0.73 |
May | 21.65 | 10.60 |
June | 22.69 | 15.96 |
July | 22.79 | 16.86 |
August | 22.39 | 14.24 |
September | 20.80 | 6.72 |
October | 19.28 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.34 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.79 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.91 | -10.3 |
April | 19.65 | 0.73 |
May | 21.31 | 10.60 |
June | 22.44 | 15.96 |
July | 22.55 | 16.86 |
August | 22.09 | 14.24 |
September | 20.44 | 6.72 |
October | 19.15 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.18 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.55 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.50 | -10.3 |
April | 20.79 | 0.73 |
May | 21.40 | 10.60 |
June | 21.66 | 15.96 |
July | 21.70 | 16.86 |
August | 21.57 | 14.24 |
September | 21.13 | 6.72 |
October | 20.63 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 20.94 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.70 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.49 | -15.4 |
March | 20.59 | -10.3 |
April | 21.08 | 0.73 |
May | 21.65 | 10.60 |
June | 21.73 | 15.96 |
July | 21.74 | 16.86 |
August | 21.69 | 14.24 |
September | 21.41 | 6.72 |
October | 20.80 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.05 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | -17.6 |
February | 20.65 | -15.4 |
March | 20.94 | -10.3 |
April | 21.43 | 0.73 |
May | 21.73 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.75 | 14.24 |
September | 21.64 | 6.72 |
October | 21.15 | -3.1 |
November | 20.54 | -17.6 |
December | 20.52 | -19.3 |
Annual Sum or Average | 21.20 | -1.4 |
Minimum of Months | 20.52 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | -17.6 |
February | 21.19 | -15.4 |
March | 21.61 | -10.3 |
April | 22.19 | 0.73 |
May | 22.42 | 10.60 |
June | 22.69 | 15.96 |
July | 22.65 | 16.86 |
August | 22.71 | 14.24 |
September | 22.49 | 6.72 |
October | 22.03 | -3.1 |
November | 20.79 | -17.6 |
December | 20.81 | -19.3 |
Annual Sum or Average | 21.88 | -1.4 |
Minimum of Months | 20.79 | -19.3 |
Maximum of Months | 22.71 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 49.11 | -17.6 |
February | 49.41 | -15.4 |
March | 49.95 | -10.3 |
April | 50.85 | 0.73 |
May | 52.07 | 10.60 |
June | 52.69 | 15.96 |
July | 52.88 | 16.86 |
August | 52.53 | 14.24 |
September | 51.78 | 6.72 |
October | 50.51 | -3.1 |
November | 49.54 | -17.6 |
December | 49.11 | -19.3 |
Annual Sum or Average | 50.88 | -1.4 |
Minimum of Months | 49.11 | -19.3 |
Maximum of Months | 52.88 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 67.78 | -17.6 |
February | 67.99 | -15.4 |
March | 68.08 | -10.3 |
April | 68.66 | 0.73 |
May | 69.96 | 10.60 |
June | 70.86 | 15.96 |
July | 71.20 | 16.86 |
August | 70.81 | 14.24 |
September | 70.13 | 6.72 |
October | 68.62 | -3.1 |
November | 68.46 | -17.6 |
December | 67.94 | -19.3 |
Annual Sum or Average | 69.21 | -1.4 |
Minimum of Months | 67.78 | -19.3 |
Maximum of Months | 71.20 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.33 | -17.6 |
February | 21.60 | -15.4 |
March | 22.02 | -10.3 |
April | 22.74 | 0.73 |
May | 23.37 | 10.60 |
June | 23.77 | 15.96 |
July | 23.80 | 16.86 |
August | 23.70 | 14.24 |
September | 23.22 | 6.72 |
October | 22.46 | -3.1 |
November | 21.36 | -17.6 |
December | 21.28 | -19.3 |
Annual Sum or Average | 22.56 | -1.4 |
Minimum of Months | 21.28 | -19.3 |
Maximum of Months | 23.80 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | -17.6 |
February | 21.22 | -15.4 |
March | 21.41 | -10.3 |
April | 22.27 | 0.73 |
May | 23.38 | 10.60 |
June | 23.84 | 15.96 |
July | 23.85 | 16.86 |
August | 23.75 | 14.24 |
September | 23.05 | 6.72 |
October | 21.84 | -3.1 |
November | 21.12 | -17.6 |
December | 21.13 | -19.3 |
Annual Sum or Average | 22.34 | -1.4 |
Minimum of Months | 21.12 | -19.3 |
Maximum of Months | 23.85 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.24 | -17.6 |
February | 14.67 | -15.4 |
March | 14.60 | -10.3 |
April | 16.56 | 0.73 |
May | 20.34 | 10.60 |
June | 22.73 | 15.96 |
July | 23.38 | 16.86 |
August | 22.33 | 14.24 |
September | 20.20 | 6.72 |
October | 16.38 | -3.1 |
November | 16.35 | -17.6 |
December | 14.47 | -19.3 |
Annual Sum or Average | 18.04 | -1.4 |
Minimum of Months | 14.24 | -19.3 |
Maximum of Months | 23.38 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.96 | -17.6 |
February | 18.26 | -15.4 |
March | 18.50 | -10.3 |
April | 19.89 | 0.73 |
May | 22.29 | 10.60 |
June | 23.64 | 15.96 |
July | 23.98 | 16.86 |
August | 23.41 | 14.24 |
September | 22.03 | 6.72 |
October | 19.64 | -3.1 |
November | 19.03 | -17.6 |
December | 18.08 | -19.3 |
Annual Sum or Average | 20.57 | -1.4 |
Minimum of Months | 17.96 | -19.3 |
Maximum of Months | 23.98 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.93 | -17.6 |
February | 15.58 | -15.4 |
March | 15.39 | -10.3 |
April | 17.30 | 0.73 |
May | 21.06 | 10.60 |
June | 23.34 | 15.96 |
July | 24.00 | 16.86 |
August | 23.05 | 14.24 |
September | 20.99 | 6.72 |
October | 16.78 | -3.1 |
November | 17.40 | -17.6 |
December | 15.08 | -19.3 |
Annual Sum or Average | 18.76 | -1.4 |
Minimum of Months | 14.93 | -19.3 |
Maximum of Months | 24.00 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.19 | -10.3 |
April | 22.03 | 0.73 |
May | 23.48 | 10.60 |
June | 23.86 | 15.96 |
July | 23.88 | 16.86 |
August | 23.78 | 14.24 |
September | 22.94 | 6.72 |
October | 21.49 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 22.26 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.88 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.38 | -17.6 |
February | 14.03 | -15.4 |
March | 13.82 | -10.3 |
April | 15.85 | 0.73 |
May | 19.65 | 10.60 |
June | 22.12 | 15.96 |
July | 22.74 | 16.86 |
August | 21.74 | 14.24 |
September | 19.35 | 6.72 |
October | 15.23 | -3.1 |
November | 15.79 | -17.6 |
December | 13.60 | -19.3 |
Annual Sum or Average | 17.29 | -1.4 |
Minimum of Months | 13.38 | -19.3 |
Maximum of Months | 22.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.53 | 0.73 |
May | 21.53 | 10.60 |
June | 22.94 | 15.96 |
July | 23.01 | 16.86 |
August | 22.46 | 14.24 |
September | 20.18 | 6.72 |
October | 19.00 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.27 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 23.01 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.49 | -15.4 |
March | 20.55 | -10.3 |
April | 21.02 | 0.73 |
May | 21.65 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.70 | 14.24 |
September | 21.32 | 6.72 |
October | 20.73 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.03 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.50 | -15.4 |
March | 20.57 | -10.3 |
April | 21.08 | 0.73 |
May | 21.67 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.71 | 14.24 |
September | 21.37 | 6.72 |
October | 20.77 | -3.1 |
November | 20.47 | -17.6 |
December | 20.48 | -19.3 |
Annual Sum or Average | 21.05 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -17.6 |
February | 20.51 | -15.4 |
March | 20.58 | -10.3 |
April | 21.09 | 0.73 |
May | 21.67 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.70 | 14.24 |
September | 21.40 | 6.72 |
October | 20.79 | -3.1 |
November | 20.47 | -17.6 |
December | 20.48 | -19.3 |
Annual Sum or Average | 21.06 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.51 | -10.3 |
April | 20.84 | 0.73 |
May | 21.51 | 10.60 |
June | 21.73 | 15.96 |
July | 21.74 | 16.86 |
August | 21.65 | 14.24 |
September | 21.20 | 6.72 |
October | 20.63 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 20.98 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -17.6 |
February | 20.52 | -15.4 |
March | 20.65 | -10.3 |
April | 21.19 | 0.73 |
May | 21.71 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.74 | 14.24 |
September | 21.53 | 6.72 |
October | 20.87 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.10 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.23 | -17.6 |
February | 20.72 | -15.4 |
March | 21.66 | -10.3 |
April | 22.77 | 0.73 |
May | 23.32 | 10.60 |
June | 23.33 | 15.96 |
July | 23.33 | 16.86 |
August | 23.33 | 14.24 |
September | 23.26 | 6.72 |
October | 22.36 | -3.1 |
November | 20.36 | -17.6 |
December | 19.96 | -19.3 |
Annual Sum or Average | 22.06 | -1.4 |
Minimum of Months | 19.96 | -19.3 |
Maximum of Months | 23.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 29.55 | -17.6 |
February | 29.77 | -15.4 |
March | 29.88 | -10.3 |
April | 30.64 | 0.73 |
May | 32.20 | 10.60 |
June | 33.05 | 15.96 |
July | 33.27 | 16.86 |
August | 32.90 | 14.24 |
September | 31.98 | 6.72 |
October | 30.32 | -3.1 |
November | 30.13 | -17.6 |
December | 29.67 | -19.3 |
Annual Sum or Average | 31.12 | -1.4 |
Minimum of Months | 29.55 | -19.3 |
Maximum of Months | 33.27 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | -17.6 |
February | 21.68 | -15.4 |
March | 21.74 | -10.3 |
April | 21.88 | 0.73 |
May | 22.24 | 10.60 |
June | 22.54 | 15.96 |
July | 22.67 | 16.86 |
August | 22.49 | 14.24 |
September | 22.09 | 6.72 |
October | 21.78 | -3.1 |
November | 21.67 | -17.6 |
December | 21.63 | -19.3 |
Annual Sum or Average | 22.01 | -1.4 |
Minimum of Months | 21.63 | -19.3 |
Maximum of Months | 22.67 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -17.6 |
February | 20.56 | -15.4 |
March | 20.77 | -10.3 |
April | 21.34 | 0.73 |
May | 21.73 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.75 | 14.24 |
September | 21.58 | 6.72 |
October | 20.96 | -3.1 |
November | 20.48 | -17.6 |
December | 20.49 | -19.3 |
Annual Sum or Average | 21.14 | -1.4 |
Minimum of Months | 20.48 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -17.6 |
February | 20.52 | -15.4 |
March | 20.65 | -10.3 |
April | 21.18 | 0.73 |
May | 21.71 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.75 | 14.24 |
September | 21.52 | 6.72 |
October | 20.85 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.10 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.05 | -17.6 |
February | 17.41 | -15.4 |
March | 17.47 | -10.3 |
April | 19.11 | 0.73 |
May | 22.22 | 10.60 |
June | 23.96 | 15.96 |
July | 24.40 | 16.86 |
August | 23.64 | 14.24 |
September | 21.85 | 6.72 |
October | 18.71 | -3.1 |
November | 18.39 | -17.6 |
December | 17.11 | -19.3 |
Annual Sum or Average | 20.12 | -1.4 |
Minimum of Months | 17.05 | -19.3 |
Maximum of Months | 24.40 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.30 | -17.6 |
February | 13.79 | -15.4 |
March | 13.33 | -10.3 |
April | 15.69 | 0.73 |
May | 20.51 | 10.60 |
June | 23.50 | 15.96 |
July | 24.31 | 16.86 |
August | 23.03 | 14.24 |
September | 20.36 | 6.72 |
October | 15.38 | -3.1 |
November | 15.93 | -17.6 |
December | 13.37 | -19.3 |
Annual Sum or Average | 17.73 | -1.4 |
Minimum of Months | 13.30 | -19.3 |
Maximum of Months | 24.31 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.05 | -17.6 |
February | 14.72 | -15.4 |
March | 14.45 | -10.3 |
April | 16.53 | 0.73 |
May | 20.74 | 10.60 |
June | 23.34 | 15.96 |
July | 24.04 | 16.86 |
August | 22.95 | 14.24 |
September | 20.46 | 6.72 |
October | 15.88 | -3.1 |
November | 16.58 | -17.6 |
December | 14.14 | -19.3 |
Annual Sum or Average | 18.17 | -1.4 |
Minimum of Months | 14.05 | -19.3 |
Maximum of Months | 24.04 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.11 | -10.3 |
April | 21.39 | 0.73 |
May | 22.71 | 10.60 |
June | 23.66 | 15.96 |
July | 23.72 | 16.86 |
August | 23.35 | 14.24 |
September | 21.83 | 6.72 |
October | 21.13 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 21.95 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.72 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.97 | -17.6 |
February | 12.66 | -15.4 |
March | 12.47 | -10.3 |
April | 14.74 | 0.73 |
May | 19.08 | 10.60 |
June | 22.07 | 15.96 |
July | 22.74 | 16.86 |
August | 21.51 | 14.24 |
September | 18.44 | 6.72 |
October | 13.94 | -3.1 |
November | 14.51 | -17.6 |
December | 12.18 | -19.3 |
Annual Sum or Average | 16.38 | -1.4 |
Minimum of Months | 11.97 | -19.3 |
Maximum of Months | 22.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.19 | 0.73 |
May | 20.93 | 10.60 |
June | 22.70 | 15.96 |
July | 22.80 | 16.86 |
August | 22.05 | 14.24 |
September | 19.56 | 6.72 |
October | 18.89 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.06 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.80 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.39 | 0.73 |
May | 21.29 | 10.60 |
June | 22.85 | 15.96 |
July | 22.90 | 16.86 |
August | 22.25 | 14.24 |
September | 19.76 | 6.72 |
October | 18.92 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.16 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.90 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.54 | 0.73 |
May | 21.47 | 10.60 |
June | 22.87 | 15.96 |
July | 22.92 | 16.86 |
August | 22.31 | 14.24 |
September | 19.93 | 6.72 |
October | 18.95 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.21 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.92 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.49 | -15.4 |
March | 20.55 | -10.3 |
April | 21.02 | 0.73 |
May | 21.64 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.68 | 14.24 |
September | 21.31 | 6.72 |
October | 20.72 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.03 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.32 | 0.73 |
May | 21.11 | 10.60 |
June | 22.72 | 15.96 |
July | 22.86 | 16.86 |
August | 22.20 | 14.24 |
September | 19.93 | 6.72 |
October | 18.93 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.14 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.86 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.48 | -15.4 |
March | 20.57 | -10.3 |
April | 21.05 | 0.73 |
May | 21.67 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.72 | 14.24 |
September | 21.40 | 6.72 |
October | 20.73 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.05 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -17.6 |
February | 20.56 | -15.4 |
March | 20.77 | -10.3 |
April | 21.36 | 0.73 |
May | 21.73 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.75 | 14.24 |
September | 21.59 | 6.72 |
October | 20.98 | -3.1 |
November | 20.47 | -17.6 |
December | 20.49 | -19.3 |
Annual Sum or Average | 21.14 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.76 | -17.6 |
February | 21.03 | -15.4 |
March | 21.20 | -10.3 |
April | 22.35 | 0.73 |
May | 24.45 | 10.60 |
June | 25.57 | 15.96 |
July | 25.78 | 16.86 |
August | 25.27 | 14.24 |
September | 23.86 | 6.72 |
October | 21.76 | -3.1 |
November | 21.40 | -17.6 |
December | 20.85 | -19.3 |
Annual Sum or Average | 22.86 | -1.4 |
Minimum of Months | 20.76 | -19.3 |
Maximum of Months | 25.78 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | -17.6 |
February | 19.01 | -15.4 |
March | 19.34 | -10.3 |
April | 21.11 | 0.73 |
May | 23.01 | 10.60 |
June | 23.32 | 15.96 |
July | 23.32 | 16.86 |
August | 23.25 | 14.24 |
September | 22.29 | 6.72 |
October | 20.09 | -3.1 |
November | 18.89 | -17.6 |
December | 18.91 | -19.3 |
Annual Sum or Average | 20.96 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 23.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -17.6 |
February | 20.52 | -15.4 |
March | 20.67 | -10.3 |
April | 21.25 | 0.73 |
May | 21.72 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.74 | 14.24 |
September | 21.49 | 6.72 |
October | 20.85 | -3.1 |
November | 20.47 | -17.6 |
December | 20.48 | -19.3 |
Annual Sum or Average | 21.10 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.92 | -10.3 |
April | 19.75 | 0.73 |
May | 22.07 | 10.60 |
June | 23.07 | 15.96 |
July | 23.12 | 16.86 |
August | 22.73 | 14.24 |
September | 20.83 | 6.72 |
October | 19.16 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.44 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 23.12 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.73 | -17.6 |
February | 16.15 | -15.4 |
March | 16.19 | -10.3 |
April | 18.09 | 0.73 |
May | 21.82 | 10.60 |
June | 23.98 | 15.96 |
July | 24.48 | 16.86 |
August | 23.51 | 14.24 |
September | 21.13 | 6.72 |
October | 17.49 | -3.1 |
November | 17.13 | -17.6 |
December | 15.72 | -19.3 |
Annual Sum or Average | 19.30 | -1.4 |
Minimum of Months | 15.72 | -19.3 |
Maximum of Months | 24.48 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.10 | -17.6 |
February | 12.69 | -15.4 |
March | 12.13 | -10.3 |
April | 14.81 | 0.73 |
May | 20.16 | 10.60 |
June | 23.53 | 15.96 |
July | 24.42 | 16.86 |
August | 22.95 | 14.24 |
September | 19.80 | 6.72 |
October | 14.28 | -3.1 |
November | 14.79 | -17.6 |
December | 12.01 | -19.3 |
Annual Sum or Average | 16.99 | -1.4 |
Minimum of Months | 12.01 | -19.3 |
Maximum of Months | 24.42 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.12 | -17.6 |
February | 12.95 | -15.4 |
March | 12.85 | -10.3 |
April | 15.45 | 0.73 |
May | 20.22 | 10.60 |
June | 23.26 | 15.96 |
July | 23.97 | 16.86 |
August | 22.60 | 14.24 |
September | 19.39 | 6.72 |
October | 14.34 | -3.1 |
November | 14.44 | -17.6 |
December | 12.03 | -19.3 |
Annual Sum or Average | 16.99 | -1.4 |
Minimum of Months | 12.03 | -19.3 |
Maximum of Months | 23.97 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.11 | -10.3 |
April | 21.38 | 0.73 |
May | 22.36 | 10.60 |
June | 23.29 | 15.96 |
July | 23.34 | 16.86 |
August | 22.88 | 14.24 |
September | 21.52 | 6.72 |
October | 21.11 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 21.79 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.34 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.32 | -17.6 |
February | 11.16 | -15.4 |
March | 11.27 | -10.3 |
April | 14.00 | 0.73 |
May | 18.68 | 10.60 |
June | 21.96 | 15.96 |
July | 22.63 | 16.86 |
August | 21.17 | 14.24 |
September | 17.62 | 6.72 |
October | 12.82 | -3.1 |
November | 12.78 | -17.6 |
December | 10.47 | -19.3 |
Annual Sum or Average | 15.43 | -1.4 |
Minimum of Months | 10.32 | -19.3 |
Maximum of Months | 22.63 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -17.6 |
February | 20.47 | -15.4 |
March | 20.47 | -10.3 |
April | 20.71 | 0.73 |
May | 21.43 | 10.60 |
June | 21.71 | 15.96 |
July | 21.72 | 16.86 |
August | 21.56 | 14.24 |
September | 20.88 | 6.72 |
October | 20.51 | -3.1 |
November | 20.46 | -17.6 |
December | 20.46 | -19.3 |
Annual Sum or Average | 20.91 | -1.4 |
Minimum of Months | 20.46 | -19.3 |
Maximum of Months | 21.72 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.35 | 0.73 |
May | 20.85 | 10.60 |
June | 22.47 | 15.96 |
July | 22.52 | 16.86 |
August | 21.76 | 14.24 |
September | 19.43 | 6.72 |
October | 18.90 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 19.99 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.52 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.45 | 0.73 |
May | 20.96 | 10.60 |
June | 22.49 | 15.96 |
July | 22.54 | 16.86 |
August | 21.81 | 14.24 |
September | 19.52 | 6.72 |
October | 18.90 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.02 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.54 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.52 | -10.3 |
April | 20.99 | 0.73 |
May | 21.66 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.68 | 14.24 |
September | 21.23 | 6.72 |
October | 20.63 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.01 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.32 | 0.73 |
May | 20.80 | 10.60 |
June | 22.42 | 15.96 |
July | 22.55 | 16.86 |
August | 21.82 | 14.24 |
September | 19.58 | 6.72 |
October | 18.90 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.00 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.55 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.92 | -10.3 |
April | 19.59 | 0.73 |
May | 21.54 | 10.60 |
June | 22.79 | 15.96 |
July | 22.86 | 16.86 |
August | 22.32 | 14.24 |
September | 20.19 | 6.72 |
October | 18.98 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.24 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.86 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.63 | -10.3 |
April | 21.27 | 0.73 |
May | 21.72 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.74 | 14.24 |
September | 21.48 | 6.72 |
October | 20.78 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.09 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.02 | -17.6 |
February | 18.38 | -15.4 |
March | 18.85 | -10.3 |
April | 20.33 | 0.73 |
May | 22.55 | 10.60 |
June | 23.83 | 15.96 |
July | 24.02 | 16.86 |
August | 23.34 | 14.24 |
September | 21.60 | 6.72 |
October | 19.41 | -3.1 |
November | 18.56 | -17.6 |
December | 18.05 | -19.3 |
Annual Sum or Average | 20.59 | -1.4 |
Minimum of Months | 18.02 | -19.3 |
Maximum of Months | 24.02 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.61 | -10.3 |
April | 21.21 | 0.73 |
May | 21.72 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.74 | 14.24 |
September | 21.46 | 6.72 |
October | 20.75 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.08 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.62 | -10.3 |
April | 21.24 | 0.73 |
May | 21.72 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.74 | 14.24 |
September | 21.45 | 6.72 |
October | 20.75 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.08 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.53 | -10.3 |
April | 21.05 | 0.73 |
May | 21.68 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.72 | 14.24 |
September | 21.34 | 6.72 |
October | 20.64 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.03 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.50 | -17.6 |
February | 15.07 | -15.4 |
March | 15.45 | -10.3 |
April | 17.78 | 0.73 |
May | 21.61 | 10.60 |
June | 23.85 | 15.96 |
July | 24.33 | 16.86 |
August | 23.23 | 14.24 |
September | 20.65 | 6.72 |
October | 16.76 | -3.1 |
November | 15.78 | -17.6 |
December | 14.42 | -19.3 |
Annual Sum or Average | 18.64 | -1.4 |
Minimum of Months | 14.42 | -19.3 |
Maximum of Months | 24.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2015-09-14 08:44:19
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.47 | -17.6 |
February | 11.26 | -15.4 |
March | 11.09 | -10.3 |
April | 14.25 | 0.73 |
May | 19.83 | 10.60 |
June | 23.42 | 15.96 |
July | 24.27 | 16.86 |
August | 22.62 | 14.24 |
September | 19.08 | 6.72 |
October | 13.20 | -3.1 |
November | 12.95 | -17.6 |
December | 10.27 | -19.3 |
Annual Sum or Average | 16.08 | -1.4 |
Minimum of Months | 10.27 | -19.3 |
Maximum of Months | 24.27 | 16.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:19
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.290685E+12 | 240132.931 | 12-JAN-07:15 | 20847.837 | 39740.848 | 9183.550 | 166164.583 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.242753E+12 | 234222.561 | 27-FEB-07:15 | 20847.837 | 39740.848 | 9184.828 | 160247.308 | 5.627 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.229446E+12 | 211789.072 | 01-MAR-07:15 | 20847.837 | 39740.848 | 9170.401 | 137788.737 | 45.136 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.165150E+12 | 179945.769 | 03-APR-06:15 | 20847.837 | 39740.848 | 9155.997 | 110100.337 | 92.637 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.149361E+12 | 93380.050 | 27-MAY-06:15 | 17938.631 | 34285.948 | 9143.586 | 31233.687 | 770.085 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.153768E+12 | 97392.492 | 30-JUN-07:00 | 25182.171 | 43578.554 | 9651.107 | 0.000 | 18972.548 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.163145E+12 | 101492.747 | 22-JUL-07:00 | 25182.171 | 43578.554 | 9651.107 | 0.000 | 23072.802 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.157235E+12 | 103225.393 | 31-AUG-06:15 | 20847.837 | 39740.848 | 9143.586 | 30702.652 | 2782.357 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.146473E+12 | 115392.677 | 30-SEP-06:15 | 17938.631 | 34285.948 | 9143.586 | 49594.853 | 233.548 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.195683E+12 | 180125.266 | 22-OCT-06:15 | 20847.837 | 39740.848 | 9153.277 | 106072.326 | 114.866 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.268481E+12 | 211601.606 | 29-NOV-07:00 | 20847.837 | 39740.848 | 9169.729 | 137602.816 | 44.263 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.299183E+12 | 220427.882 | 15-DEC-07:15 | 17938.631 | 34285.948 | 9168.808 | 154831.492 | 6.890 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.246136E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.146473E+12 | 93380.050 | 17938.631 | 34285.948 | 9143.586 | 0.000 | 0.000 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.299183E+12 | 240132.931 | 25182.171 | 43578.554 | 9651.107 | 166164.583 | 23072.802 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-14 08:44:19
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.160502E+12 | 145248.205 | 13-JAN-09:30 | 30369.014 | 40096.028 | 0.000 | 74783.163 | 74783.163 | 74783.163 | 30369.014 |
February | 0.139902E+12 | 138852.032 | 25-FEB-09:15 | 25389.640 | 40096.028 | 0.000 | 73366.365 | 73366.365 | 73366.365 | 25389.640 |
March | 0.142728E+12 | 131022.095 | 04-MAR-09:30 | 19356.622 | 40096.028 | 0.000 | 71569.445 | 71569.445 | 71569.445 | 19356.622 |
April | 0.116080E+12 | 121432.675 | 07-APR-08:15 | 6141.066 | 40096.028 | 0.000 | 75195.581 | 75195.581 | 75195.581 | 6141.066 |
May | 0.107164E+12 | 116837.342 | 27-MAY-08:15 | 844.474 | 40096.028 | 0.000 | 75896.840 | 75896.840 | 75896.840 | 844.474 |
June | 0.100664E+12 | 115978.270 | 10-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 75882.242 | 75882.242 | 75882.242 | 0.000 |
July | 0.101505E+12 | 114539.575 | 08-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 74443.547 | 74443.547 | 74443.547 | 0.000 |
August | 0.100368E+12 | 109187.178 | 11-AUG-08:30 | 0.000 | 40096.028 | 0.000 | 69091.150 | 69091.150 | 69091.150 | 0.000 |
September | 0.101095E+12 | 116362.815 | 29-SEP-08:15 | 3312.497 | 40096.028 | 0.000 | 72954.291 | 72954.291 | 72954.291 | 3312.497 |
October | 0.123642E+12 | 127909.462 | 27-OCT-08:15 | 18344.587 | 40096.028 | 0.000 | 69468.847 | 69468.847 | 69468.847 | 18344.587 |
November | 0.150476E+12 | 134586.798 | 11-NOV-09:15 | 19835.761 | 40096.028 | 0.000 | 74655.009 | 74655.009 | 74655.009 | 19835.761 |
December | 0.163201E+12 | 145691.610 | 15-DEC-09:30 | 32674.993 | 40096.028 | 0.000 | 72920.589 | 72920.589 | 72920.589 | 32674.993 |
Annual Sum or Average | 0.150733E+13 | 0.000 | ||||||||
Minimum of Months | 0.100368E+12 | 109187.178 | 0.000 | 40096.028 | 0.000 | 69091.150 | 69091.150 | 69091.150 | 0.000 | |
Maximum of Months | 0.163201E+12 | 145691.610 | 32674.993 | 40096.028 | 0.000 | 75896.840 | 75896.840 | 75896.840 | 32674.993 |