Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:20
Tabular Output Report in Format: HTML
Building: OutPatient HealthCare
Environment: Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Simulation Timestamp: 2015-09-13 14:21:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 6058.27 | 1592.60 | 1592.60 |
Net Site Energy | 6058.27 | 1592.60 | 1592.60 |
Total Source Energy | 18349.10 | 4823.62 | 4823.62 |
Net Source Energy | 18349.10 | 4823.62 | 4823.62 |
Site=>Source Conversion Factor | |
Electricity | 3.546 |
Natural Gas | 1.092 |
District Cooling | 1.182 |
District Heating | 3.640 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.158 |
Fuel Oil #2 | 1.050 |
Propane | 1.151 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3804.01 |
Net Conditioned Building Area | 3804.01 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 640.94 | 956.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 662.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 558.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 131.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1853.61 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 565.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 346.46 | 0.00 | 0.00 | 0.00 | 0.00 | 128.88 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 132.32 | 0.00 | 0.00 | 0.00 | 478.84 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4781.37 | 1276.90 | 0.00 | 0.00 | 0.00 | 607.73 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 956.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 640.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 662.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 558.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 131.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 1853.61 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 524.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Zone Exhaust Fans | 40.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 346.46 | 0.00 | 0.00 | 0.00 | 0.00 | 128.88 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 132.32 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.84 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 181.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 588.23 | 286.15 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 487.28 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1256.93 | 335.67 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 181.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 588.23 | 286.15 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 487.28 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1256.93 | 335.67 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 4781.37 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 4781.37 | 100.00 |
Total On-Site and Utility Electric Sources | 4781.37 | 100.00 |
Total Electricity End Uses | 4781.37 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 607.73 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 607.73 | 100.00 |
Total Water End Uses | 607.73 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 32.50 |
Time Setpoint Not Met During Occupied Cooling | 2229.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7640.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |OVERALL HVAC AIR SYSTEM LOADS
| AHU-1 | AHU-2 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:20 |
RunPeriod | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Weather File | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Latitude [deg] | 43.62 |
Longitude [deg] | -116.2 |
Elevation [m] | 701.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | |
Gross Roof Area [m2] | 1373.29 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
FLOOR 1 ANESTHESIA | 10.03 | Yes | Yes | 30.58 | 1.00 | 8.36 | 2.23 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 BIO HAZ | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 CAFE | 39.02 | Yes | Yes | 118.93 | 1.00 | 18.58 | 8.92 | 8.8535 | 0.93 | 10.7600 |
FLOOR 1 CLEAN | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 CLEAN WORK | 15.33 | Yes | Yes | 46.72 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 DICTATION | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 DRESSING ROOM | 4.18 | Yes | Yes | 12.74 | 1.00 | 8.36 | 2.32 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 ELECTRICAL ROOM | 9.10 | Yes | Yes | 27.75 | 1.00 | 6.50 | 0.00 | 14.7559 | 53.8200 | |
FLOOR 1 ELEVATOR PUMP ROOM | 8.45 | Yes | Yes | 25.77 | 1.00 | 18.58 | 0.00 | 14.7559 | 5754.6154 | |
FLOOR 1 HUMID | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 IT HALL | 13.01 | Yes | Yes | 39.64 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 IT ROOM | 10.41 | Yes | Yes | 31.71 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 LOBBY | 57.79 | Yes | Yes | 176.13 | 1.00 | 20.44 | 8.92 | 12.7884 | 9.29 | 11.8400 |
FLOOR 1 LOBBY HALL | 22.30 | Yes | Yes | 67.96 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 LOBBY TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 LOCKER ROOM | 61.32 | Yes | Yes | 186.89 | 1.00 | 20.44 | 5.57 | 7.8698 | 6.19 | 32.2900 |
FLOOR 1 LOCKER ROOM HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 LOUNGE | 33.45 | Yes | Yes | 101.94 | 1.00 | 0.00 | 0.00 | 7.8698 | 6.19 | 32.2900 |
FLOOR 1 MED GAS | 5.20 | Yes | Yes | 15.86 | 1.00 | 13.94 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 MRI CONTROL ROOM | 15.61 | Yes | Yes | 47.57 | 1.00 | 4.65 | 0.00 | 3.9349 | 4.64 | 107.6400 |
FLOOR 1 MRI HALL | 13.66 | Yes | Yes | 41.63 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 MRI ROOM | 40.88 | Yes | Yes | 124.59 | 1.00 | 0.00 | 0.00 | 3.9349 | 4.64 | 107.6400 |
FLOOR 1 MRI TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 NOURISHMENT | 16.91 | Yes | Yes | 51.54 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 1 NURSE HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 NURSE JANITOR | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 NURSE STATION | 24.25 | Yes | Yes | 73.91 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 1 NURSE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 OFFICE | 44.87 | Yes | Yes | 136.77 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 OPERATING ROOM 1 | 42.74 | Yes | Yes | 130.26 | 1.00 | 39.95 | 8.92 | 21.6419 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 2 | 44.59 | Yes | Yes | 135.92 | 1.00 | 22.30 | 6.69 | 21.6419 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 3 | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 21.6419 | 4.64 | 118.3600 |
FLOOR 1 PACU | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 7.8698 | 4.64 | 32.2900 |
FLOOR 1 PRE-OP HALL | 49.05 | Yes | Yes | 149.51 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 PRE-OP ROOM 1 | 17.56 | Yes | Yes | 53.52 | 1.00 | 3.72 | 0.00 | 6.8861 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP ROOM 2 | 31.40 | Yes | Yes | 95.71 | 1.00 | 0.00 | 0.00 | 6.8861 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 PROCEDURE ROOM | 26.48 | Yes | Yes | 80.70 | 1.00 | 17.65 | 5.57 | 26.5606 | 4.64 | 32.2900 |
FLOOR 1 RECEPTION | 47.29 | Yes | Yes | 144.13 | 1.00 | 12.08 | 3.34 | 12.7884 | 3.10 | 11.8400 |
FLOOR 1 RECEPTION HALL | 11.89 | Yes | Yes | 36.25 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 RECOVERY ROOM | 50.17 | Yes | Yes | 152.91 | 1.00 | 41.81 | 8.92 | 7.8698 | 4.64 | 32.2900 |
FLOOR 1 SCHEDULING | 11.06 | Yes | Yes | 33.70 | 1.00 | 6.50 | 0.74 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 SCRUB | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 SOIL | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 SOIL HOLD | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 SOIL WORK | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 STEP DOWN | 27.87 | Yes | Yes | 84.95 | 1.00 | 34.37 | 6.69 | 7.8698 | 4.64 | 32.2900 |
FLOOR 1 STERILE HALL | 57.23 | Yes | Yes | 174.43 | 1.00 | 7.43 | 2.23 | 9.8372 | 4.3100 | |
FLOOR 1 STERILE STORAGE | 36.79 | Yes | Yes | 112.13 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 STORAGE | 85.47 | Yes | Yes | 260.51 | 1.00 | 58.53 | 8.36 | 8.8535 | 1.0800 | |
FLOOR 1 SUB-STERILE | 18.21 | Yes | Yes | 55.50 | 1.00 | 13.01 | 2.97 | 9.8372 | 4.3100 | |
FLOOR 1 UTILITY HALL | 23.78 | Yes | Yes | 72.49 | 1.00 | 14.86 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 UTILITY JANITOR | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 UTILITY ROOM | 33.45 | Yes | Yes | 101.94 | 1.00 | 16.72 | 2.23 | 8.8535 | 1.0800 | |
FLOOR 1 VESTIBULE | 6.69 | Yes | Yes | 20.39 | 1.00 | 7.43 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 CONFERENCE | 31.22 | Yes | Yes | 95.14 | 1.00 | 37.16 | 8.92 | 12.7884 | 1.86 | 10.7600 |
FLOOR 2 CONFERENCE TOILET | 5.95 | Yes | Yes | 18.12 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 2 DICTATION | 6.50 | Yes | Yes | 19.82 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 EXAM 1 | 33.45 | Yes | Yes | 101.94 | 1.00 | 39.02 | 8.92 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 2 | 50.17 | Yes | Yes | 152.91 | 1.00 | 16.72 | 3.72 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 3 | 66.89 | Yes | Yes | 203.88 | 1.00 | 22.30 | 5.95 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 4 | 7.80 | Yes | Yes | 23.79 | 1.00 | 6.50 | 2.23 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 5 | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 6 | 20.90 | Yes | Yes | 63.71 | 1.00 | 13.94 | 4.18 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 7 | 73.58 | Yes | Yes | 224.27 | 1.00 | 22.30 | 5.57 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 8 | 25.08 | Yes | Yes | 76.46 | 1.00 | 16.72 | 5.57 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 9 | 36.79 | Yes | Yes | 112.13 | 1.00 | 11.15 | 2.79 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM HALL 1 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 3 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 4 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 5 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 6 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 LOUNGE | 7.43 | Yes | Yes | 22.65 | 1.00 | 0.00 | 0.00 | 7.8698 | 6.19 | 32.2900 |
FLOOR 2 NURSE STATION 1 | 13.94 | Yes | Yes | 42.48 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 2 NURSE STATION 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 2 OFFICE | 52.03 | Yes | Yes | 158.57 | 1.00 | 37.16 | 8.92 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 OFFICE HALL | 41.25 | Yes | Yes | 125.73 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 RECEPTION | 91.42 | Yes | Yes | 278.64 | 1.00 | 45.52 | 16.72 | 12.7884 | 3.10 | 11.8400 |
FLOOR 2 RECEPTION HALL | 52.40 | Yes | Yes | 159.71 | 1.00 | 6.50 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 RECEPTION TOILET | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 2 SCHEDULING 1 | 30.10 | Yes | Yes | 91.75 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 SCHEDULING 2 | 31.77 | Yes | Yes | 96.84 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 STORAGE 1 | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 STORAGE 2 | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 STORAGE 3 | 13.38 | Yes | Yes | 40.78 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 UTILITY | 11.71 | Yes | Yes | 35.68 | 1.00 | 8.36 | 2.23 | 8.8535 | 1.0800 | |
FLOOR 2 WORK | 157.01 | Yes | Yes | 478.55 | 1.00 | 24.15 | 5.57 | 10.8210 | 18.58 | 9.7803 |
FLOOR 2 WORK HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 WORK TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 2 X-RAY | 83.61 | Yes | Yes | 254.85 | 1.00 | 0.00 | 0.00 | 3.9349 | 4.64 | 107.6400 |
FLOOR 3 DRESSING ROOM | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 3 ELEVATOR HALL | 34.37 | Yes | Yes | 104.77 | 1.00 | 3.72 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 3 HUMID | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 3 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 LOCKER | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 7.8698 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE | 70.51 | Yes | Yes | 214.92 | 1.00 | 21.37 | 5.57 | 7.8698 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE TOILET | 17.84 | Yes | Yes | 54.37 | 1.00 | 11.15 | 4.18 | 8.8535 | 4.3100 | |
FLOOR 3 MECHANICAL | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 14.7559 | 53.8200 | |
FLOOR 3 MECHANICAL HALL | 27.87 | Yes | Yes | 84.95 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 3 OFFICE | 282.05 | Yes | Yes | 859.70 | 1.00 | 68.75 | 19.51 | 10.8210 | 18.58 | 11.8400 |
FLOOR 3 OFFICE HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 3 OFFICE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 3 PHYSICAL THERAPY 1 | 120.77 | Yes | Yes | 368.12 | 1.00 | 78.97 | 28.99 | 8.8535 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY 2 | 55.00 | Yes | Yes | 167.64 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY TOILET | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 3 STORAGE 1 | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 STORAGE 2 | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 TREATMENT | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 11.8400 |
FLOOR 3 UNDEVELOPED 1 | 210.70 | Yes | Yes | 642.23 | 1.00 | 66.89 | 25.64 | 8.8535 | 11.8400 | |
FLOOR 3 UNDEVELOPED 2 | 107.02 | Yes | Yes | 326.21 | 1.00 | 52.03 | 13.38 | 8.8535 | 11.8400 | |
FLOOR 3 UTILITY | 20.07 | Yes | Yes | 61.16 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 WORK | 53.33 | Yes | Yes | 162.54 | 1.00 | 38.09 | 8.92 | 10.8210 | 18.58 | 11.8400 |
NE STAIR | 15.61 | Yes | Yes | 142.72 | 1.00 | 97.55 | 12.02 | 9.8372 | 4.3100 | |
NW ELEVATOR | 13.01 | Yes | Yes | 118.93 | 1.00 | 75.25 | 0.00 | 9.8372 | 4.3100 | |
NW STAIR | 17.84 | Yes | Yes | 163.10 | 1.00 | 111.48 | 11.15 | 9.8372 | 4.3100 | |
SW STAIR | 8.92 | Yes | Yes | 81.55 | 1.00 | 55.74 | 1.11 | 9.8372 | 4.3100 | |
Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 10.7639 | 9.08 | 32.0039 | |||
Conditioned Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 10.7639 | 9.08 | 32.0039 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 2.30 | 120.00 |
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 36.70 | 16.70 | 17.90 | Wetbulb [C] | 4.20 | 330.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
481E71 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
FLOOR 1 ANESTHESIA SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 0.00 | 180.00 | |
FLOOR 1 BIO HAZ SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
5F762C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
FLOOR 1 CAFE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 39.02 | 90.00 | 180.00 | |
FLOOR 1 CLEAN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 CLEAN WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.33 | 180.00 | 180.00 | |
FLOOR 1 DICTATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 0.00 | 180.00 | |
84FB73 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
FLOOR 1 DRESSING ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 4.18 | 0.00 | 180.00 | |
7F5C82 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 ELECTRICAL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 9.10 | 0.00 | 180.00 | |
C732B0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 0.00 | 90.00 | N |
E02487 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 1 ELEVATOR PUMP ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.45 | 180.00 | 180.00 | |
FLOOR 1 HUMID SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
FLOOR 1 IT HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 180.00 | 180.00 | |
FLOOR 1 IT ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.41 | 90.00 | 180.00 | |
FE5A3C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.79 | 90.00 | 180.00 | |
FLOOR 1 LOBBY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 22.30 | 0.00 | 180.00 | |
9D87EC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
F629C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
FLOOR 1 LOCKER ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 61.32 | 270.00 | 180.00 | |
FLOOR 1 LOCKER ROOM HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 180.00 | 180.00 | |
FLOOR 1 LOUNGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
E85BB5 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 0.00 | 90.00 | N |
577FC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 MED GAS SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 180.00 | 180.00 | |
FLOOR 1 MED GAS ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.20 | 180.00 | 0.00 | |
C114C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.65 | 0.00 | 90.00 | N |
FLOOR 1 MRI CONTROL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 180.00 | 180.00 | |
FLOOR 1 MRI HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.66 | 180.00 | 180.00 | |
FLOOR 1 MRI ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 40.88 | 90.00 | 180.00 | |
ADB8D0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
FLOOR 1 MRI TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 90.00 | 180.00 | |
FLOOR 1 NOURISHMENT SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.91 | 270.00 | 180.00 | |
FLOOR 1 NURSE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 270.00 | 180.00 | |
FLOOR 1 NURSE JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 NURSE STATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 24.25 | 180.00 | 180.00 | |
FLOOR 1 NURSE TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 OFFICE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.87 | 0.00 | 180.00 | |
879583 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
E326E4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 42.74 | 0.00 | 180.00 | |
1D96D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.59 | 0.00 | 180.00 | |
FLOOR 1 OPERATING ROOM 3 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.22 | 0.00 | 180.00 | |
FLOOR 1 PACU SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 180.00 | 180.00 | |
FLOOR 1 PRE-OP HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 49.05 | 180.00 | 180.00 | |
84418A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.56 | 90.00 | 180.00 | |
FLOOR 1 PRE-OP ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 31.40 | 0.00 | 180.00 | |
1535AC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 270.00 | 180.00 | |
6D2616 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 17.65 | 0.00 | 90.00 | N |
FLOOR 1 PROCEDURE ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 26.48 | 270.00 | 180.00 | |
A5A6A3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 180.00 | 90.00 | S |
FLOOR 1 RECEPTION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 47.29 | 270.00 | 180.00 | |
FLOOR 1 RECEPTION HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.89 | 0.00 | 180.00 | |
28B002 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 41.81 | 180.00 | 90.00 | S |
FLOOR 1 RECOVERY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 50.17 | 90.00 | 180.00 | |
EA6DC8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
FLOOR 1 SCHEDULING SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.06 | 90.00 | 180.00 | |
FLOOR 1 SCRUB SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 7.80 | 90.00 | 180.00 | |
FLOOR 1 SOIL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 SOIL HOLD SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
FLOOR 1 SOIL WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.72 | 0.00 | 180.00 | |
B40F89 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 270.00 | 90.00 | W |
997723 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 180.00 | 90.00 | S |
FLOOR 1 STEP DOWN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 27.87 | 270.00 | 180.00 | |
CEC7BD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 180.00 | 90.00 | S |
FLOOR 1 STERILE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.23 | 270.00 | 180.00 | |
FLOOR 1 NURSE STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 36.79 | 0.00 | 180.00 | |
8E5BB9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 270.00 | 90.00 | W |
859BC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 0.00 | 90.00 | N |
FLOOR 1 STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 85.47 | 270.00 | 180.00 | |
FLOOR 1 STORGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 85.47 | 270.00 | 0.00 | |
61E610 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.01 | 90.00 | 90.00 | E |
FLOOR 1 SUB-STERILE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 18.21 | 180.00 | 180.00 | |
529072 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 23.78 | 90.00 | 180.00 | |
FLOOR 1 UTILITY HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.89 | 180.00 | 0.00 | |
FLOOR 1 UTILITY JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 3.90 | 90.00 | 180.00 | |
D95F04 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
3330D8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 270.00 | 90.00 | W |
FLOOR 1 VESTIBULE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 6.69 | 90.00 | 180.00 | |
208CCF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 90.00 | 90.00 | E |
AEF992 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 26.01 | 180.00 | 90.00 | S |
54D065 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
1775A6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
97F00A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 180.00 | 90.00 | S |
A497E9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 180.00 | 90.00 | S |
88A75F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
B4E619 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
9EC269 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.94 | 0.00 | 90.00 | N |
B316F7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 0.00 | 90.00 | N |
9621FD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 0.00 | 90.00 | N |
42CEE1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
4979C8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
8CA0BF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
6C95E7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
F209CC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
155BD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
C5EA55 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
8177BA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
5E657E | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
4B1439 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 90.00 | 90.00 | E |
4ABC66 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 30.66 | 180.00 | 90.00 | S |
5B04CF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
8D1BC4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
4B55FA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
9C3A6A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
C52EE0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
1C33AD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
6CC177 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 DRESSING ROOM ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 3.90 | 270.00 | 0.00 | |
F7D24D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
FLOOR 3 ELEVATOR HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 34.37 | 0.00 | 0.00 | |
FLOOR 3 HUMID ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 270.00 | 0.00 | |
FC22D1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
DD2E2D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 3 JANITOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.85 | 0.00 | 0.00 | |
FLOOR 3 LOCKER ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.15 | 0.00 | 0.00 | |
68A2D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 70.51 | 270.00 | 0.00 | |
CE3FEF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 0.00 | 0.00 | |
CE618F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
FLOOR 3 MECHANICAL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 32.52 | 0.00 | 0.00 | |
FLOOR 3 MECHANICAL HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 27.87 | 0.00 | 0.00 | |
5ADC59 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 68.75 | 0.00 | 90.00 | N |
FLOOR 3 OFFICE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 282.05 | 180.00 | 0.00 | |
D4F411 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 77.48 | 270.00 | 0.00 | |
B35AD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.02 | 270.00 | 0.00 | |
D22917 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 90.00 | 90.00 | E |
C1BC97 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.39 | 180.00 | 90.00 | S |
FLOOR 3 PHYICAL THERAPY 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 120.77 | 180.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 55.00 | 90.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 90.00 | 0.00 | |
FLOOR 3 STORAGE 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 180.00 | 0.00 | |
FLOOR 3 STORAGE 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 180.00 | 0.00 | |
FLOOR 3 TREATMENT ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 44.22 | 90.00 | 0.00 | |
8DA7DB | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.02 | 180.00 | 90.00 | S |
38B339 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
FLOOR 3 UNDEVELOPED 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 210.70 | 0.00 | 0.00 | |
BE5F2F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
1DEE26 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 180.00 | 90.00 | S |
FLOOR 3 UNDEVELOPED 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 107.02 | 180.00 | 0.00 | |
FLOOR 3 UTILITY ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
C86329 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 38.09 | 90.00 | 90.00 | E |
FLOOR 3 WORK ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 53.33 | 90.00 | 0.00 | |
DFC6F0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 90.00 | 90.00 | E |
88E360 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
E7B55F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
NE STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 0.00 | 180.00 | |
NE STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 15.61 | 0.00 | 0.00 | |
FB3814 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 180.00 | 90.00 | S |
FCD12D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 55.74 | 270.00 | 90.00 | W |
NW ELEVATOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 90.00 | 180.00 | |
NW ELEVATOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 13.01 | 90.00 | 0.00 | |
5507DC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
2E2D0C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
AF0124 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
NW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.84 | 270.00 | 180.00 | |
NW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 270.00 | 0.00 | |
850EA7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 33.45 | 180.00 | 90.00 | S |
270BCE | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
SW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.92 | 270.00 | 180.00 | |
SW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 8.92 | 180.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
78F987 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 481E71 | 180.00 | 90.00 | S | ||
D8037E | WINDOW_U_0.48_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | 5F762C | 180.00 | 90.00 | S | ||
4A8120 | WINDOW_U_0.48_SHGC_0.40 | 2.32 | 0.00 | 0.00 | 2.32 | 2.32 | 2.653 | 0.426 | 0.308 | No | 84FB73 | 0.00 | 90.00 | N | ||
AAE778 | WINDOW_U_0.48_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | FE5A3C | 270.00 | 90.00 | W | ||
3AAD8B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
8128A9 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
9B1541 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
CF850A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
A6BA23 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
D10D28 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
591336 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
38B811 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
C044D6 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
1D94BE | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
18748E | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
137A56 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | A5A6A3 | 180.00 | 90.00 | S | ||
8D508E | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
B2D381 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
1DA13A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
44E54A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
757D10 | WINDOW_U_0.48_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | EA6DC8 | 180.00 | 90.00 | S | ||
E33BAE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | B40F89 | 270.00 | 90.00 | W | ||
24167A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
2C0938 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
8600DD | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | CEC7BD | 180.00 | 90.00 | S | ||
A1ED60 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
E8D997 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
88E1FC | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
F83F33 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | 61E610 | 90.00 | 90.00 | E | ||
B1F5EE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | D95F04 | 90.00 | 90.00 | E | ||
F52F3D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 208CCF | 90.00 | 90.00 | E | ||
80885D | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | AEF992 | 180.00 | 90.00 | S | ||
FEEF06 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 54D065 | 180.00 | 90.00 | S | ||
2BE8DE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
513E2A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
BA5CD9 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
1AD478 | WINDOW_U_0.48_SHGC_0.40 | 3.72 | 0.00 | 0.00 | 3.72 | 3.72 | 2.653 | 0.426 | 0.308 | No | 97F00A | 180.00 | 90.00 | S | ||
27F0AC | WINDOW_U_0.48_SHGC_0.40 | 5.95 | 0.00 | 0.00 | 5.95 | 5.95 | 2.653 | 0.426 | 0.308 | No | A497E9 | 180.00 | 90.00 | S | ||
724114 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 88A75F | 180.00 | 90.00 | S | ||
D538C4 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
5635BC | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
831C1D | WINDOW_U_0.48_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | 9EC269 | 0.00 | 90.00 | N | ||
9BB95F | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
C0778D | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
7D2D69 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
2EF63B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
C417C0 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 42CEE1 | 0.00 | 90.00 | N | ||
EB042B | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
4C1F71 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
D23C8B | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
B4E4BE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
EEF55D | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
E55A57 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
93D018 | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 5B04CF | 270.00 | 90.00 | W | ||
DD9F5D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B55FA | 90.00 | 90.00 | E | ||
15B02B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
820282 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
9BA05A | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
C639E8 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
A2790A | WINDOW_U_0.48_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | CE3FEF | 0.00 | 90.00 | N | ||
79FCEE | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
EDE617 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
C61F0D | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
7248C5 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
29FA28 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
F0B23F | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
EEC10E | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
944FCE | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
C41399 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
95BA33 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
F27282 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
3DB407 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
3DADE2 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
DF3E2C | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
5031C8 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
C087D0 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
D2CA75 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
B0FB49 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
FE9BC9 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
9DF7DE | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
D0BE44 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
6B5226 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | BE5F2F | 270.00 | 90.00 | W | ||
8F59F7 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
44F571 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
6BD844 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
86D536 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
BAF71D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
3833A2 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
2111A1 | WINDOW_U_0.48_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | DFC6F0 | 90.00 | 90.00 | E | ||
9BC521 | WINDOW_U_0.48_SHGC_0.40 | 5.71 | 0.00 | 0.00 | 5.71 | 5.71 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
142781 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
E74902 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
93BBC3 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
C635A6 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | 850EA7 | 180.00 | 90.00 | S | ||
Total or Average | 308.29 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 97.22 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 211.08 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
71E924 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 8E5BB9 |
5E66D1 | OPAQUEDOOR | 8.100 | 8.100 | 5.95 | 529072 |
E14DAE | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | D95F04 |
84A1D5 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 3330D8 |
9CB8E5 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 88E360 |
EDE769 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 5507DC |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 126365.84 | 0.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 141529.00 | 107025.45 | 34503.55 | 0.76 | 3.23 | |||
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 208367.62 | 162560.04 | 45807.58 | 0.78 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 135920.5 | 2.76 | 9.41 | N/A | 10.62 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 199476.3 | 2.73 | 9.30 | N/A | 10.52 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | Coil:Heating:Water | 1873.21 | 1855.90 | - |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | Coil:Heating:Water | 203.72 | 174.06 | - |
FLOOR 1 CAFE VAV BOX REHEAT COIL | Coil:Heating:Water | 9575.29 | 5523.60 | - |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | Coil:Heating:Water | 1183.41 | 1172.48 | - |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 1478.16 | 1464.51 | - |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Water | 725.43 | 418.47 | - |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 518.16 | 464.16 | - |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 1352.11 | 779.98 | - |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 7968.13 | 4596.49 | - |
FLOOR 1 HUMID VAV BOX REHEAT COIL | Coil:Heating:Water | 358.19 | 206.62 | - |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 549.61 | 317.05 | - |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 600.63 | 346.48 | - |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | Coil:Heating:Water | 8470.88 | 4886.51 | - |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1162.69 | 670.71 | - |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1170.75 | 1159.94 | - |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 6631.77 | 3825.60 | - |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1698.29 | 979.68 | - |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Water | 3230.82 | 1863.73 | - |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | Coil:Heating:Water | 560.28 | 555.10 | - |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 3873.85 | 2234.67 | - |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 716.48 | 413.31 | - |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9513.32 | 5487.85 | - |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1170.75 | 1159.94 | - |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 1646.42 | 949.76 | - |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2027.84 | 1169.78 | - |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 252.88 | 145.87 | - |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | Coil:Heating:Water | 2225.68 | 1283.90 | - |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1170.75 | 1159.94 | - |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Water | 2391.87 | 1379.77 | - |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23434.68 | 23218.21 | - |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24268.77 | 24044.59 | - |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20639.98 | 20449.32 | - |
FLOOR 1 PACU VAV BOX REHEAT COIL | Coil:Heating:Water | 1404.91 | 1391.93 | - |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2038.66 | 1176.02 | - |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2458.59 | 2435.87 | - |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4396.84 | 4356.22 | - |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1170.75 | 1159.94 | - |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9268.48 | 9182.86 | - |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Water | 5477.17 | 3159.56 | - |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 532.20 | 307.00 | - |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 8308.40 | 8231.65 | - |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | Coil:Heating:Water | 915.44 | 528.08 | - |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | Coil:Heating:Water | 391.59 | 225.89 | - |
FLOOR 1 SOIL VAV BOX REHEAT COIL | Coil:Heating:Water | 2731.76 | 2706.53 | - |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | Coil:Heating:Water | 1214.12 | 1202.90 | - |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 3902.52 | 3866.47 | - |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | Coil:Heating:Water | 5326.08 | 5276.88 | - |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2346.45 | 1353.57 | - |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 1205.85 | 695.60 | - |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 5018.78 | 4720.25 | - |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | Coil:Heating:Water | 1838.52 | 1321.58 | - |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2090.55 | 1853.18 | - |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 186.59 | 112.85 | - |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 2534.47 | 2100.23 | - |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | Coil:Heating:Water | 1117.79 | 842.22 | - |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2483.41 | 1.00 | |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1364.39 | 1.00 | |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Electric | 187.54 | 1.00 | |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8223.17 | 1.00 | |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6907.22 | 1.00 | |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9209.63 | 1.00 | |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1760.76 | 1.00 | |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6625.75 | 1.00 | |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2893.65 | 1.00 | |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10130.59 | 1.00 | |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3553.52 | 1.00 | |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5065.30 | 1.00 | |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 459.46 | 1.00 | |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 428.82 | 1.00 | |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 413.48 | 1.00 | |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 417.83 | 1.00 | |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 438.72 | 1.00 | |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 440.85 | 1.00 | |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 591.59 | 1.00 | |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 301.53 | 1.00 | |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 501.15 | 1.00 | |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 609.12 | 1.00 | |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2590.48 | 1.00 | |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 987.18 | 1.00 | |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Electric | 5001.84 | 1.00 | |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1308.92 | 1.00 | |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 2686.14 | 1.00 | |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 712.08 | 1.00 | |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 781.44 | 1.00 | |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 130.67 | 1.00 | |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 229.48 | 1.00 | |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 292.14 | 1.00 | |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 714.83 | 1.00 | |
FLOOR 2 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 3562.06 | 1.00 | |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1821.10 | 1.00 | |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1151.20 | 1.00 | |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | Coil:Heating:Electric | 6883.17 | 1.00 | |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 178.76 | 1.00 | |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1312.81 | 1.00 | |
FLOOR 3 HUMID VAV BOX REHEAT COIL | Coil:Heating:Electric | 394.71 | 1.00 | |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 577.80 | 1.00 | |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | Coil:Heating:Electric | 598.14 | 1.00 | |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 3409.05 | 1.00 | |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 4093.17 | 1.00 | |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | Coil:Heating:Electric | 2992.27 | 1.00 | |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1507.96 | 1.00 | |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 8674.02 | 1.00 | |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 2985.95 | 1.00 | |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1151.20 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 25297.42 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8149.69 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1790.76 | 1.00 | |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 882.98 | 1.00 | |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 436.29 | 1.00 | |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 6767.70 | 1.00 | |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7944.71 | 1.00 | |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4744.93 | 1.00 | |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 881.60 | 1.00 | |
FLOOR 3 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 2956.56 | 1.00 | |
NE STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 4008.10 | 1.00 | |
NW ELEVATOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2276.72 | 1.00 | |
NW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 4053.83 | 1.00 | |
SW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1819.32 | 1.00 | |
AHU-1_HEATC | Coil:Heating:Water | 52833.40 | 47825.44 | - |
AHU-1_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
AHU-1_EXTRAWATERHEATC | Coil:Heating:Water | 52833.40 | 47825.44 | - |
AHU-2_HEATC | Coil:Heating:Water | 164213.42 | 137183.52 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
FLOOR 1 ANESTHESIA EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 54.61 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 LOBBY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.16 | 127.44 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.42 | 323.16 | 778.12 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 NURSE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 PRE-OP TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL HOLD EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 35.39 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL WORK EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.14 | 113.76 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 CONFERENCE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.05 | 40.45 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 RECEPTION TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 WORK TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 X-RAY EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.85 | 661.02 | 778.13 | 1.00 | Zone Exhaust Fans |
FLOOR 3 LOUNGE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.15 | 121.35 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 OFFICE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 53.09 | 803.55 | 1.00 | Zone Exhaust Fans |
AHU-1_FAN | Fan:VariableVolume | 0.60 | 1389.42 | 7.56 | 17495.40 | 2313.39 | 1.00 | Fan Energy |
AHU-2_FAN | Fan:VariableVolume | 0.60 | 1389.42 | 11.95 | 27476.40 | 2298.46 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0001 | 8.07 | 127739.32 | 0.30 |
HEATSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 179352.00 | 0.0027 | 692.36 | 255487.18 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.20 | 0.81 | 0.78 | 0.28 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 135920.46 | 2.76 | 9.41 | 10.62 | 8.0443 | 3.02 | 10.31 | 6.0546 | 3.25 | 11.09 | 3.8333 | 3.36 | 11.47 | 1.7298 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 199476.26 | 2.73 | 9.30 | 10.52 | 12.7155 | 2.99 | 10.20 | 9.4219 | 3.22 | 11.00 | 5.8848 | 3.34 | 11.39 | 2.6527 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 775.45 | 775.45 | 0.062 | 0.068 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
FLOOR 1 CAFE | 4340.89 | 4340.89 | 0.347 | 0.347 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
FLOOR 1 CLEAN | 537.06 | 537.06 | 0.043 | 0.043 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.52 | 0.00627 |
FLOOR 1 CLEAN WORK | 670.82 | 670.82 | 0.054 | 0.054 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.46 | 0.00627 |
FLOOR 1 DICTATION | 340.93 | 340.93 | 0.026 | 0.026 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 DRESSING ROOM | 235.21 | 235.21 | 0.019 | 0.019 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 36.37 | 0.00627 |
FLOOR 1 HUMID | 167.77 | 167.77 | 0.013 | 0.013 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 IT ROOM | 272.63 | 272.63 | 0.022 | 0.022 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 35.48 | 0.00627 |
FLOOR 1 LOBBY | 3844.87 | 3844.87 | 0.307 | 0.307 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 1 LOCKER ROOM | 3009.81 | 3009.81 | 0.241 | 0.241 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 36.37 | 0.00627 |
FLOOR 1 LOUNGE | 1466.29 | 1466.29 | 0.117 | 0.117 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.41 | 0.00627 |
FLOOR 1 MRI CONTROL ROOM | 1758.12 | 1758.12 | 0.141 | 0.141 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 1 MRI ROOM | 4317.43 | 4317.43 | 0.345 | 0.345 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 1 NOURISHMENT | 747.19 | 747.19 | 0.060 | 0.060 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 26.99 | 0.00627 |
FLOOR 1 NURSE STATION | 1010.06 | 1010.06 | 0.081 | 0.081 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 26.99 | 0.00627 |
FLOOR 1 OFFICE | 1085.70 | 1085.70 | 0.087 | 0.087 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 26.99 | 0.00627 |
FLOOR 1 OPERATING ROOM 1 | 6899.39 | 6899.39 | 0.850 | 0.850 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 33.97 | 0.00627 |
FLOOR 1 OPERATING ROOM 2 | 7144.90 | 7144.90 | 0.880 | 0.880 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 30.77 | 0.00627 |
FLOOR 1 OPERATING ROOM 3 | 5832.73 | 5832.73 | 0.679 | 0.749 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 07:20:00 | 22.45 | 0.00627 |
FLOOR 1 PACU | 500.51 | 500.51 | 0.040 | 0.051 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 26.46 | 0.00627 |
FLOOR 1 PRE-OP ROOM 1 | 627.58 | 627.58 | 0.050 | 0.089 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 1 PRE-OP ROOM 2 | 1068.96 | 1068.96 | 0.085 | 0.160 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 25.93 | 0.00627 |
FLOOR 1 PROCEDURE ROOM | 1852.33 | 1852.33 | 0.148 | 0.336 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 36.20 | 0.00627 |
FLOOR 1 RECEPTION | 2485.31 | 2485.31 | 0.199 | 0.199 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 36.70 | 0.00627 |
FLOOR 1 RECOVERY ROOM | 3770.62 | 3770.62 | 0.301 | 0.301 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
FLOOR 1 SCHEDULING | 415.54 | 415.54 | 0.033 | 0.033 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 1 SOIL | 530.98 | 530.98 | 0.042 | 0.099 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 27.99 | 0.00627 |
FLOOR 1 SOIL HOLD | 227.85 | 227.85 | 0.018 | 0.044 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 35.70 | 0.00627 |
FLOOR 1 SOIL WORK | 716.80 | 716.80 | 0.057 | 0.142 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 27.99 | 0.00627 |
FLOOR 1 STEP DOWN | 2417.20 | 2417.20 | 0.193 | 0.193 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 35.48 | 0.00627 |
FLOOR 2 CONFERENCE | 3234.44 | 3234.44 | 0.305 | 0.305 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 36.70 | 0.00627 |
FLOOR 2 DICTATION | 252.07 | 252.07 | 0.023 | 0.023 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM 1 | 3214.21 | 3214.21 | 0.303 | 0.303 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 33.25 | 0.00627 |
FLOOR 2 EXAM 2 | 2610.47 | 2610.47 | 0.246 | 0.255 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 36.70 | 0.00627 |
FLOOR 2 EXAM 3 | 3581.73 | 3581.73 | 0.338 | 0.340 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 36.70 | 0.00627 |
FLOOR 2 EXAM 4 | 688.24 | 688.24 | 0.065 | 0.065 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 36.70 | 0.00627 |
FLOOR 2 EXAM 5 | 2589.74 | 2589.74 | 0.244 | 0.244 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.19 | 0.00627 |
FLOOR 2 EXAM 6 | 1131.00 | 1131.00 | 0.107 | 0.107 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 2 EXAM 7 | 3213.64 | 3213.64 | 0.303 | 0.374 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 2 EXAM 8 | 1388.91 | 1388.91 | 0.131 | 0.131 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 36.37 | 0.00627 |
FLOOR 2 EXAM 9 | 1729.25 | 1729.25 | 0.163 | 0.187 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 2 LOUNGE | 392.89 | 392.89 | 0.037 | 0.037 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 25.40 | 0.00627 |
FLOOR 2 NURSE STATION 1 | 652.94 | 652.94 | 0.062 | 0.062 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 25.40 | 0.00627 |
FLOOR 2 NURSE STATION 2 | 793.61 | 793.61 | 0.075 | 0.075 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 25.40 | 0.00627 |
FLOOR 2 OFFICE | 3375.68 | 3375.68 | 0.319 | 0.319 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.19 | 0.00627 |
FLOOR 2 RECEPTION | 6515.63 | 6515.63 | 0.615 | 0.615 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 35.03 | 0.00627 |
FLOOR 2 SCHEDULING 1 | 927.92 | 927.92 | 0.088 | 0.088 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 25.40 | 0.00627 |
FLOOR 2 SCHEDULING 2 | 1018.29 | 1018.29 | 0.096 | 0.096 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 25.40 | 0.00627 |
FLOOR 2 WORK | 4641.63 | 4641.63 | 0.438 | 0.438 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 36.37 | 0.00627 |
FLOOR 2 X-RAY | 8967.62 | 8967.62 | 0.846 | 0.846 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 3 DRESSING ROOM | 206.11 | 206.11 | 0.019 | 0.019 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 HUMID | 514.35 | 514.35 | 0.049 | 0.049 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 LOCKER | 779.37 | 779.37 | 0.074 | 0.074 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 LOUNGE | 4441.63 | 4441.63 | 0.419 | 0.419 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 OFFICE | 11302.89 | 11302.89 | 1.067 | 1.067 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 PHYSICAL THERAPY 1 | 9887.36 | 9887.36 | 0.933 | 0.933 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 36.70 | 0.00627 |
FLOOR 3 PHYSICAL THERAPY 2 | 3185.37 | 3185.37 | 0.301 | 0.301 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 36.70 | 0.00627 |
FLOOR 3 TREATMENT | 2645.23 | 2645.23 | 0.250 | 0.250 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 3 WORK | 3852.67 | 3852.67 | 0.364 | 0.364 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.61 | 0.00627 |
FLOOR 1 BIO HAZ | 94.38 | 94.38 | 0.007 | 0.007 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 ELECTRICAL ROOM | 613.79 | 613.79 | 0.049 | 0.049 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | 34.53 | 0.00627 |
FLOOR 1 ELEVATOR PUMP ROOM | 3735.71 | 3735.71 | 0.289 | 0.289 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 IT HALL | 255.28 | 255.28 | 0.020 | 0.020 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 LOBBY HALL | 547.83 | 547.83 | 0.042 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 LOBBY TOILET | 443.56 | 443.56 | 0.035 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 LOCKER ROOM HALL | 793.95 | 793.95 | 0.062 | 0.062 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 MED GAS | 228.67 | 228.67 | 0.018 | 0.018 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 36.70 | 0.00627 |
FLOOR 1 MRI HALL | 335.61 | 335.61 | 0.026 | 0.026 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 MRI TOILET | 156.13 | 156.13 | 0.012 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 35.87 | 0.00627 |
FLOOR 1 NURSE HALL | 951.04 | 951.04 | 0.074 | 0.074 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 NURSE JANITOR | 117.46 | 117.46 | 0.009 | 0.009 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 NURSE TOILET | 138.33 | 138.33 | 0.011 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 PRE-OP HALL | 955.61 | 955.61 | 0.074 | 0.074 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 PRE-OP TOILET | 206.02 | 206.02 | 0.016 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 1 RECEPTION HALL | 248.61 | 248.61 | 0.019 | 0.019 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 SCRUB | 177.76 | 177.76 | 0.014 | 0.014 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 25.93 | 0.00627 |
FLOOR 1 STERILE HALL | 1065.16 | 1065.16 | 0.085 | 0.085 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 36.42 | 0.00627 |
FLOOR 1 STERILE STORAGE | 563.70 | 563.70 | 0.044 | 0.044 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 STORAGE | 2278.27 | 2278.27 | 0.182 | 0.182 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 34.81 | 0.00627 |
FLOOR 1 SUB-STERILE | 834.60 | 834.60 | 0.067 | 0.067 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.19 | 0.00627 |
FLOOR 1 UTILITY HALL | 949.00 | 949.00 | 0.076 | 0.076 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.41 | 0.00627 |
FLOOR 1 UTILITY JANITOR | 86.40 | 86.40 | 0.007 | 0.007 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 1 UTILITY ROOM | 1150.53 | 1150.53 | 0.092 | 0.092 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 32.02 | 0.00627 |
FLOOR 1 VESTIBULE | 507.43 | 507.43 | 0.041 | 0.041 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 32.97 | 0.00627 |
FLOOR 2 CONFERENCE TOILET | 202.97 | 202.97 | 0.019 | 0.050 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM HALL 1 | 596.10 | 596.10 | 0.054 | 0.054 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM HALL 2 | 578.74 | 578.74 | 0.053 | 0.053 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM HALL 3 | 557.89 | 557.89 | 0.051 | 0.051 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM HALL 4 | 563.33 | 563.33 | 0.051 | 0.051 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM HALL 5 | 591.24 | 591.24 | 0.054 | 0.054 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 EXAM HALL 6 | 594.40 | 594.40 | 0.054 | 0.054 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 JANITOR | 434.56 | 434.56 | 0.041 | 0.041 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 32.97 | 0.00627 |
FLOOR 2 OFFICE HALL | 1286.46 | 1286.46 | 0.121 | 0.121 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 25.93 | 0.00627 |
FLOOR 2 RECEPTION HALL | 1767.74 | 1767.74 | 0.161 | 0.161 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 RECEPTION TOILET | 382.63 | 382.63 | 0.035 | 0.099 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 STORAGE 1 | 175.72 | 175.72 | 0.016 | 0.016 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 STORAGE 2 | 309.88 | 309.88 | 0.028 | 0.028 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 STORAGE 3 | 394.28 | 394.28 | 0.036 | 0.036 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 UTILITY | 735.23 | 735.23 | 0.069 | 0.069 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 31.19 | 0.00627 |
FLOOR 2 WORK HALL | 2460.33 | 2460.33 | 0.224 | 0.224 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 20.72 | 0.00627 |
FLOOR 2 WORK TOILET | 212.99 | 212.99 | 0.020 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 3 ELEVATOR HALL | 988.60 | 988.60 | 0.093 | 0.093 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 3 JANITOR | 253.34 | 253.34 | 0.024 | 0.024 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 32.97 | 0.00627 |
FLOOR 3 LOUNGE TOILET | 796.94 | 796.94 | 0.075 | 0.151 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 36.53 | 0.00627 |
FLOOR 3 MECHANICAL | 3899.45 | 3899.45 | 0.368 | 0.368 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 31.61 | 0.00627 |
FLOOR 3 MECHANICAL HALL | 1187.77 | 1187.77 | 0.112 | 0.112 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 36.70 | 0.00627 |
FLOOR 3 OFFICE HALL | 2613.55 | 2613.55 | 0.247 | 0.247 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 36.37 | 0.00627 |
FLOOR 3 OFFICE TOILET | 195.13 | 195.13 | 0.018 | 0.042 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
FLOOR 3 PHYSICAL THERAPY TOILET | 299.40 | 299.40 | 0.028 | 0.066 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 STORAGE 1 | 345.21 | 345.21 | 0.033 | 0.033 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 36.70 | 0.00627 |
FLOOR 3 STORAGE 2 | 300.53 | 300.53 | 0.028 | 0.028 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 36.70 | 0.00627 |
FLOOR 3 UNDEVELOPED 1 | 10353.36 | 10353.36 | 0.977 | 0.977 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 35.70 | 0.00627 |
FLOOR 3 UNDEVELOPED 2 | 5477.42 | 5477.42 | 0.517 | 0.517 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 35.87 | 0.00627 |
FLOOR 3 UTILITY | 587.74 | 587.74 | 0.055 | 0.055 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 36.70 | 0.00627 |
NE STAIR | 1959.88 | 1959.88 | 0.185 | 0.185 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 36.70 | 0.00627 |
NW ELEVATOR | 1269.11 | 1269.11 | 0.120 | 0.120 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.69 | 0.00627 |
NW STAIR | 2133.02 | 2133.02 | 0.201 | 0.201 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 33.81 | 0.00627 |
SW STAIR | 1083.89 | 1083.89 | 0.102 | 0.102 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 34.81 | 0.00627 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 295.14 | 295.14 | 0.014 | 0.015 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 CAFE | 483.61 | 483.61 | 0.022 | 0.184 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.000 | 0.018 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.000 | 0.023 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.000 | 0.005 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 DRESSING ROOM | 299.81 | 299.81 | 0.014 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.000 | 0.002 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 IT ROOM | 10.54 | 10.54 | 0.000 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:50:00 | -16.30 | 0.00098 |
FLOOR 1 LOBBY | 1038.82 | 1038.82 | 0.047 | 0.047 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 LOCKER ROOM | 1.41 | 1.41 | 0.000 | 0.042 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -16.30 | 0.00098 |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.000 | 0.023 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.000 | 0.024 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.000 | 0.062 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.000 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.000 | 0.020 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.000 | 0.019 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 OPERATING ROOM 1 | 2.54 | 2.54 | 0.000 | 0.239 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | -16.30 | 0.00098 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 0.00 | 0.000 | 0.249 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 0.00 | 0.000 | 0.247 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 PACU | 0.00 | 0.00 | 0.000 | 0.032 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.000 | 0.052 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.000 | 0.093 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 PROCEDURE ROOM | 272.74 | 272.74 | 0.012 | 0.108 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 RECEPTION | 49.01 | 49.01 | 0.002 | 0.050 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -16.30 | 0.00098 |
FLOOR 1 RECOVERY ROOM | 1025.91 | 1025.91 | 0.047 | 0.161 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 SCHEDULING | 114.40 | 114.40 | 0.005 | 0.005 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.000 | 0.018 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 SOIL HOLD | 2.01 | 2.01 | 0.000 | 0.008 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -16.30 | 0.00098 |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.000 | 0.025 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 STEP DOWN | 966.71 | 966.71 | 0.044 | 0.090 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 CONFERENCE | 1554.55 | 1554.55 | 0.072 | 0.072 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.000 | 0.003 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 EXAM 1 | 1630.48 | 1630.48 | 0.075 | 0.075 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 2 | 670.41 | 670.41 | 0.031 | 0.076 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 3 | 915.62 | 915.62 | 0.042 | 0.102 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 4 | 385.48 | 385.48 | 0.018 | 0.018 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 5 | 1179.61 | 1179.61 | 0.054 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 6 | 676.54 | 676.54 | 0.031 | 0.032 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 7 | 556.06 | 556.06 | 0.025 | 0.112 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 8 | 735.30 | 735.30 | 0.034 | 0.038 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM 9 | 377.16 | 377.16 | 0.017 | 0.056 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.000 | 0.005 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.000 | 0.011 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.000 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 OFFICE | 1978.12 | 1978.12 | 0.091 | 0.091 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 RECEPTION | 2334.22 | 2334.22 | 0.107 | 0.107 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.000 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.000 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 WORK | 1082.45 | 1082.45 | 0.050 | 0.068 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 X-RAY | 0.00 | 0.00 | 0.000 | 0.127 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 3 DRESSING ROOM | 143.78 | 143.78 | 0.007 | 0.007 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 HUMID | 314.72 | 314.72 | 0.014 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 LOCKER | 329.85 | 329.85 | 0.015 | 0.015 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 LOUNGE | 1244.61 | 1244.61 | 0.056 | 0.056 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 OFFICE | 6800.14 | 6800.14 | 0.310 | 0.310 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 PHYSICAL THERAPY 1 | 4683.16 | 4683.16 | 0.215 | 0.215 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 PHYSICAL THERAPY 2 | 1498.71 | 1498.71 | 0.068 | 0.084 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 TREATMENT | 1126.69 | 1126.69 | 0.051 | 0.067 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 WORK | 2286.39 | 2286.39 | 0.105 | 0.105 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 BIO HAZ | 104.04 | 104.04 | 0.005 | 0.005 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 ELECTRICAL ROOM | 39.21 | 39.21 | 0.002 | 0.002 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 ELEVATOR PUMP ROOM | 322.37 | 322.37 | 0.015 | 0.015 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 IT HALL | 23.34 | 23.34 | 0.001 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.000 | 0.007 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 LOBBY TOILET | 222.53 | 222.53 | 0.010 | 0.010 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.000 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 MED GAS | 440.79 | 440.79 | 0.020 | 0.020 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 MRI HALL | 12.63 | 12.63 | 0.001 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -16.30 | 0.00098 |
FLOOR 1 MRI TOILET | 172.47 | 172.47 | 0.008 | 0.008 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 NURSE HALL | 85.61 | 85.61 | 0.004 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.000 | 0.003 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.000 | 0.015 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 PRE-OP TOILET | 228.22 | 228.22 | 0.011 | 0.011 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 SCRUB | 85.57 | 85.57 | 0.004 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 STERILE HALL | 311.16 | 311.16 | 0.014 | 0.017 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.000 | 0.022 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 1 STORAGE | 3359.03 | 3359.03 | 0.154 | 0.154 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 SUB-STERILE | 643.41 | 643.41 | 0.030 | 0.030 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 UTILITY HALL | 1178.96 | 1178.96 | 0.054 | 0.054 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 UTILITY JANITOR | 47.25 | 47.25 | 0.002 | 0.002 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 UTILITY ROOM | 1208.07 | 1208.07 | 0.055 | 0.055 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 1 VESTIBULE | 428.90 | 428.90 | 0.020 | 0.020 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 CONFERENCE TOILET | 85.11 | 85.11 | 0.004 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM HALL 1 | 368.05 | 368.05 | 0.017 | 0.017 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM HALL 2 | 234.13 | 234.13 | 0.011 | 0.011 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM HALL 3 | 243.40 | 243.40 | 0.011 | 0.011 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM HALL 4 | 167.09 | 167.09 | 0.008 | 0.008 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM HALL 5 | 171.46 | 171.46 | 0.008 | 0.008 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 EXAM HALL 6 | 207.07 | 207.07 | 0.010 | 0.010 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 JANITOR | 472.96 | 472.96 | 0.022 | 0.022 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 OFFICE HALL | 564.91 | 564.91 | 0.026 | 0.026 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.016 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | -16.30 | 0.00098 | |
FLOOR 2 RECEPTION TOILET | 64.14 | 64.14 | 0.003 | 0.003 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 STORAGE 1 | 75.93 | 75.93 | 0.004 | 0.004 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 STORAGE 2 | 92.43 | 92.43 | 0.004 | 0.007 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 STORAGE 3 | 102.56 | 102.56 | 0.005 | 0.008 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 UTILITY | 572.92 | 572.92 | 0.026 | 0.026 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 2 WORK HALL | 18.13 | 18.13 | 0.001 | 0.024 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -16.30 | 0.00098 |
FLOOR 2 WORK TOILET | 278.27 | 278.27 | 0.013 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 ELEVATOR HALL | 1058.51 | 1058.51 | 0.048 | 0.048 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 JANITOR | 462.44 | 462.44 | 0.021 | 0.021 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 LOUNGE TOILET | 852.32 | 852.32 | 0.039 | 0.039 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 MECHANICAL | 415.88 | 415.88 | 0.019 | 0.019 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 MECHANICAL HALL | 1210.93 | 1210.93 | 0.056 | 0.056 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 OFFICE HALL | 2406.59 | 2406.59 | 0.110 | 0.110 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 OFFICE TOILET | 305.62 | 305.62 | 0.014 | 0.014 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 PHYSICAL THERAPY TOILET | 276.97 | 276.97 | 0.013 | 0.013 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 STORAGE 1 | 404.33 | 404.33 | 0.019 | 0.019 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 STORAGE 2 | 350.14 | 350.14 | 0.016 | 0.016 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 UNDEVELOPED 1 | 5941.96 | 5941.96 | 0.271 | 0.271 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 UNDEVELOPED 2 | 3821.13 | 3821.13 | 0.175 | 0.175 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
FLOOR 3 UTILITY | 708.96 | 708.96 | 0.033 | 0.033 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
NE STAIR | 3211.01 | 3211.01 | 0.148 | 0.148 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
NW ELEVATOR | 1827.92 | 1827.92 | 0.084 | 0.084 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
NW STAIR | 3249.50 | 3249.50 | 0.150 | 0.150 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
SW STAIR | 1459.23 | 1459.23 | 0.067 | 0.067 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -16.30 | 0.00098 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AHU-1 | 7.56 | 7.56 | 2.39 | 2.39 |
AHU-2 | 11.95 | 11.95 | 3.46 | 3.46 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
AHU-2_OA_CONTROLLER | DifferentialDryBulb | 5.31 | 11.95 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FLOOR 1 ANESTHESIA | 3652.00 | 7823.00 | 3652.00 |
FLOOR 1 CAFE | 1257.50 | 7135.33 | 971.17 |
FLOOR 1 CLEAN | 1133.00 | 7830.00 | 1133.00 |
FLOOR 1 CLEAN WORK | 2426.50 | 7830.00 | 2426.50 |
FLOOR 1 DICTATION | 273.33 | 7830.00 | 273.33 |
FLOOR 1 DRESSING ROOM | 2974.83 | 7827.67 | 2974.67 |
FLOOR 1 HUMID | 68.50 | 7830.00 | 68.50 |
FLOOR 1 IT ROOM | 700.67 | 7830.00 | 700.67 |
FLOOR 1 LOBBY | 1054.50 | 7504.83 | 862.83 |
FLOOR 1 LOCKER ROOM | 242.33 | 7809.50 | 240.17 |
FLOOR 1 LOUNGE | 159.00 | 7826.17 | 157.17 |
FLOOR 1 MRI CONTROL ROOM | 167.67 | 7642.00 | 163.33 |
FLOOR 1 MRI ROOM | 44.33 | 7391.33 | 40.67 |
FLOOR 1 NOURISHMENT | 143.50 | 7828.00 | 143.50 |
FLOOR 1 NURSE STATION | 341.50 | 7828.17 | 341.50 |
FLOOR 1 OFFICE | 179.67 | 7830.00 | 179.67 |
FLOOR 1 OPERATING ROOM 1 | 6326.67 | 7830.00 | 6326.67 |
FLOOR 1 OPERATING ROOM 2 | 6827.17 | 7830.00 | 6827.17 |
FLOOR 1 OPERATING ROOM 3 | 7326.17 | 7830.00 | 7326.17 |
FLOOR 1 PACU | 3182.33 | 7830.00 | 3182.33 |
FLOOR 1 PRE-OP ROOM 1 | 3683.33 | 7830.00 | 3683.33 |
FLOOR 1 PRE-OP ROOM 2 | 3418.67 | 7830.00 | 3418.67 |
FLOOR 1 PROCEDURE ROOM | 3951.33 | 7830.00 | 3951.33 |
FLOOR 1 RECEPTION | 343.50 | 7753.00 | 339.83 |
FLOOR 1 RECOVERY ROOM | 3441.83 | 7815.50 | 3441.83 |
FLOOR 1 SCHEDULING | 762.33 | 7828.83 | 762.33 |
FLOOR 1 SOIL | 3931.17 | 7830.00 | 3931.17 |
FLOOR 1 SOIL HOLD | 4079.83 | 7830.00 | 4079.83 |
FLOOR 1 SOIL WORK | 4053.33 | 7830.00 | 4053.33 |
FLOOR 1 STEP DOWN | 3670.50 | 7815.50 | 3667.50 |
FLOOR 2 CONFERENCE | 2269.00 | 7568.50 | 2216.33 |
FLOOR 2 DICTATION | 969.33 | 7830.00 | 969.33 |
FLOOR 2 EXAM 1 | 4360.33 | 7801.00 | 4349.67 |
FLOOR 2 EXAM 2 | 3301.67 | 7830.00 | 3301.67 |
FLOOR 2 EXAM 3 | 3587.00 | 7830.00 | 3587.00 |
FLOOR 2 EXAM 4 | 4006.17 | 7825.83 | 4006.17 |
FLOOR 2 EXAM 5 | 4233.50 | 7829.50 | 4233.50 |
FLOOR 2 EXAM 6 | 4087.33 | 7829.33 | 4087.33 |
FLOOR 2 EXAM 7 | 3753.00 | 7830.00 | 3753.00 |
FLOOR 2 EXAM 8 | 3801.67 | 7828.67 | 3801.67 |
FLOOR 2 EXAM 9 | 3347.50 | 7830.00 | 3347.50 |
FLOOR 2 LOUNGE | 646.83 | 7830.00 | 646.83 |
FLOOR 2 NURSE STATION 1 | 490.50 | 7830.00 | 490.50 |
FLOOR 2 NURSE STATION 2 | 435.67 | 7829.83 | 435.67 |
FLOOR 2 OFFICE | 2426.33 | 7827.50 | 2426.33 |
FLOOR 2 RECEPTION | 1340.17 | 7518.00 | 1211.17 |
FLOOR 2 SCHEDULING 1 | 357.00 | 7830.00 | 357.00 |
FLOOR 2 SCHEDULING 2 | 370.67 | 7830.00 | 370.67 |
FLOOR 2 WORK | 665.17 | 7819.17 | 665.17 |
FLOOR 2 X-RAY | 276.50 | 6713.17 | 3.50 |
FLOOR 3 DRESSING ROOM | 2525.17 | 7829.83 | 2525.17 |
FLOOR 3 HUMID | 2103.67 | 7826.17 | 2103.67 |
FLOOR 3 LOCKER | 1732.83 | 7796.67 | 1730.50 |
FLOOR 3 LOUNGE | 1601.50 | 7660.17 | 1553.17 |
FLOOR 3 OFFICE | 2110.17 | 7707.00 | 2083.00 |
FLOOR 3 PHYSICAL THERAPY 1 | 4403.00 | 7748.00 | 4377.50 |
FLOOR 3 PHYSICAL THERAPY 2 | 4102.67 | 7822.83 | 4102.33 |
FLOOR 3 TREATMENT | 3711.33 | 7817.67 | 3710.17 |
FLOOR 3 WORK | 3109.00 | 7706.50 | 3101.17 |
FLOOR 1 BIO HAZ | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.00 | 0.00 | 0.00 |
NE STAIR | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 0.00 | 0.00 | 0.00 |
NW STAIR | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.00 | 0.00 | 0.00 |
Facility | 7679.33 | 7830.00 | 7640.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FLOOR 1 ANESTHESIA | 7.33 | 30.83 | 7.33 | 30.83 |
FLOOR 1 CAFE | 0.83 | 263.67 | 0.83 | 263.67 |
FLOOR 1 CLEAN | 0.00 | 2.67 | 0.00 | 2.67 |
FLOOR 1 CLEAN WORK | 0.00 | 2.50 | 0.00 | 2.50 |
FLOOR 1 DICTATION | 0.00 | 2.50 | 0.00 | 2.50 |
FLOOR 1 DRESSING ROOM | 0.67 | 2.67 | 0.67 | 2.67 |
FLOOR 1 HUMID | 0.00 | 2.67 | 0.00 | 2.67 |
FLOOR 1 IT ROOM | 0.00 | 2.67 | 0.00 | 2.67 |
FLOOR 1 LOBBY | 0.67 | 5.83 | 0.67 | 5.83 |
FLOOR 1 LOCKER ROOM | 0.00 | 5.00 | 0.00 | 5.00 |
FLOOR 1 LOUNGE | 0.00 | 5.17 | 0.00 | 5.17 |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 426.00 | 0.00 | 426.00 |
FLOOR 1 MRI ROOM | 0.00 | 1433.00 | 0.00 | 1433.00 |
FLOOR 1 NOURISHMENT | 0.00 | 2.83 | 0.00 | 2.83 |
FLOOR 1 NURSE STATION | 0.00 | 2.83 | 0.00 | 2.83 |
FLOOR 1 OFFICE | 0.00 | 2.83 | 0.00 | 2.83 |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 863.17 | 0.00 | 863.17 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 655.00 | 0.00 | 655.00 |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 1678.83 | 0.00 | 1678.83 |
FLOOR 1 PACU | 0.17 | 2.50 | 0.17 | 2.50 |
FLOOR 1 PRE-OP ROOM 1 | 3.33 | 1.33 | 3.33 | 1.33 |
FLOOR 1 PRE-OP ROOM 2 | 0.50 | 0.33 | 0.50 | 0.33 |
FLOOR 1 PROCEDURE ROOM | 13.17 | 0.00 | 13.17 | 0.00 |
FLOOR 1 RECEPTION | 0.00 | 35.33 | 0.00 | 35.33 |
FLOOR 1 RECOVERY ROOM | 5.83 | 38.50 | 5.83 | 38.50 |
FLOOR 1 SCHEDULING | 0.00 | 2.83 | 0.00 | 2.83 |
FLOOR 1 SOIL | 1.33 | 0.00 | 1.33 | 0.00 |
FLOOR 1 SOIL HOLD | 6.00 | 0.00 | 6.00 | 0.00 |
FLOOR 1 SOIL WORK | 3.33 | 0.00 | 3.33 | 0.00 |
FLOOR 1 STEP DOWN | 7.67 | 15.50 | 7.67 | 15.50 |
FLOOR 2 CONFERENCE | 1.00 | 56.17 | 1.00 | 56.17 |
FLOOR 2 DICTATION | 2.33 | 2.50 | 2.33 | 2.50 |
FLOOR 2 EXAM 1 | 14.83 | 24.50 | 14.83 | 24.50 |
FLOOR 2 EXAM 2 | 0.00 | 18.17 | 0.00 | 18.17 |
FLOOR 2 EXAM 3 | 0.00 | 16.17 | 0.00 | 16.17 |
FLOOR 2 EXAM 4 | 17.67 | 52.67 | 17.67 | 52.67 |
FLOOR 2 EXAM 5 | 1.67 | 9.33 | 1.67 | 9.33 |
FLOOR 2 EXAM 6 | 0.00 | 25.67 | 0.00 | 25.67 |
FLOOR 2 EXAM 7 | 0.00 | 8.00 | 0.00 | 8.00 |
FLOOR 2 EXAM 8 | 0.00 | 26.67 | 0.00 | 26.67 |
FLOOR 2 EXAM 9 | 0.00 | 12.83 | 0.00 | 12.83 |
FLOOR 2 LOUNGE | 0.00 | 24.67 | 0.00 | 24.67 |
FLOOR 2 NURSE STATION 1 | 0.00 | 40.00 | 0.00 | 40.00 |
FLOOR 2 NURSE STATION 2 | 0.00 | 49.83 | 0.00 | 49.83 |
FLOOR 2 OFFICE | 12.17 | 8.00 | 12.17 | 8.00 |
FLOOR 2 RECEPTION | 0.83 | 52.33 | 0.83 | 52.33 |
FLOOR 2 SCHEDULING 1 | 0.17 | 20.83 | 0.17 | 20.83 |
FLOOR 2 SCHEDULING 2 | 0.33 | 20.67 | 0.33 | 20.67 |
FLOOR 2 WORK | 2.83 | 36.17 | 2.83 | 36.17 |
FLOOR 2 X-RAY | 0.00 | 1870.17 | 0.00 | 1870.17 |
FLOOR 3 DRESSING ROOM | 7.33 | 17.00 | 7.33 | 17.00 |
FLOOR 3 HUMID | 6.67 | 23.83 | 6.67 | 23.83 |
FLOOR 3 LOCKER | 1.50 | 40.67 | 1.50 | 40.67 |
FLOOR 3 LOUNGE | 1.50 | 60.67 | 1.50 | 60.67 |
FLOOR 3 OFFICE | 14.17 | 48.33 | 14.17 | 48.33 |
FLOOR 3 PHYSICAL THERAPY 1 | 8.50 | 53.33 | 8.50 | 53.33 |
FLOOR 3 PHYSICAL THERAPY 2 | 0.00 | 28.00 | 0.00 | 28.00 |
FLOOR 3 TREATMENT | 0.00 | 30.17 | 0.00 | 30.17 |
FLOOR 3 WORK | 21.00 | 17.67 | 21.00 | 17.67 |
FLOOR 1 BIO HAZ | 14.50 | 1.33 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 2.83 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 5.00 | 104.50 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 1.50 | 0.83 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 2.83 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 31.17 | 2.17 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 1.33 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 20.50 | 2.50 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 2.33 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 45.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.17 | 1.33 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 1.17 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 38.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.17 | 2.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 53.50 | 0.33 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 1.33 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.67 | 1.33 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 1.50 | 2.33 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 1.17 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 27.83 | 5.17 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 1.17 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 9.50 | 1.50 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 3.00 | 1.33 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 4.83 | 1.33 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 2408.67 | 606.67 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 9.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 15.33 | 10.33 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 12.83 | 6.50 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 15.17 | 2.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 14.67 | 2.83 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 11.00 | 5.50 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 13.00 | 4.83 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 1.17 | 8.33 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 10.33 | 2.50 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 3.00 | 8.33 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 3.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 21.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 14.50 | 1.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 10.33 | 2.17 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 18.83 | 0.17 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 2.83 | 11.33 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 27.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 16.00 | 35.83 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 12.33 | 15.33 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 33.83 | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 57.17 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 11.83 | 25.50 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 12.50 | 39.33 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 40.50 | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 16.83 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 1.67 | 6.83 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 10.17 | 18.50 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 16.17 | 47.67 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 16.17 | 52.83 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 15.17 | 10.17 | 0.00 | 0.00 |
NE STAIR | 21.17 | 36.67 | 0.00 | 0.00 |
NW ELEVATOR | 21.83 | 17.00 | 0.00 | 0.00 |
NW STAIR | 23.50 | 35.17 | 0.00 | 0.00 |
SW STAIR | 19.83 | 41.17 | 0.00 | 0.00 |
Facility | 2466.50 | 2678.50 | 32.50 | 2229.83 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-13 14:21:42
AirTerminal:SingleDuct:VAV:ReheatMaximum Air Flow Rate [m3/s] | Maximum Reheat Water Flow Rate [m3/s] | Reheat Coil Sizing Air Volume Flow Rate [m3/s] | |
FLOOR 1 ANESTHESIA VAV BOX COMPONENT | 0.067956 | 0.000040 | 0.067956 |
FLOOR 1 BIO HAZ VAV BOX COMPONENT | 0.007390 | 0.000003 | 0.004805 |
FLOOR 1 CAFE VAV BOX COMPONENT | 0.347372 | 0.000062 | 0.104212 |
FLOOR 1 CLEAN VAV BOX COMPONENT | 0.042932 | 0.000025 | 0.042932 |
FLOOR 1 CLEAN WORK VAV BOX COMPONENT | 0.053625 | 0.000032 | 0.053625 |
FLOOR 1 DICTATION VAV BOX COMPONENT | 0.026317 | 0.000005 | 0.007895 |
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT | 0.018798 | 0.000008 | 0.013834 |
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT | 0.049052 | 0.000009 | 0.014716 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT | 0.289067 | 0.000051 | 0.086720 |
FLOOR 1 HUMID VAV BOX COMPONENT | 0.012994 | 0.000002 | 0.003898 |
FLOOR 1 IT HALL VAV BOX COMPONENT | 0.019939 | 0.000004 | 0.005982 |
FLOOR 1 IT ROOM VAV BOX COMPONENT | 0.021790 | 0.000004 | 0.006537 |
FLOOR 1 LOBBY VAV BOX COMPONENT | 0.307306 | 0.000055 | 0.092192 |
FLOOR 1 LOBBY HALL VAV BOX COMPONENT | 0.042180 | 0.000008 | 0.012654 |
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT | 0.240587 | 0.000043 | 0.072176 |
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT | 0.061611 | 0.000011 | 0.018483 |
FLOOR 1 LOUNGE VAV BOX COMPONENT | 0.117207 | 0.000021 | 0.035162 |
FLOOR 1 MED GAS VAV BOX COMPONENT | 0.020326 | 0.000012 | 0.020326 |
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT | 0.140535 | 0.000025 | 0.042161 |
FLOOR 1 MRI HALL VAV BOX COMPONENT | 0.025992 | 0.000005 | 0.007798 |
FLOOR 1 MRI ROOM VAV BOX COMPONENT | 0.345124 | 0.000061 | 0.103537 |
FLOOR 1 MRI TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 NOURISHMENT VAV BOX COMPONENT | 0.059729 | 0.000011 | 0.017919 |
FLOOR 1 NURSE HALL VAV BOX COMPONENT | 0.073566 | 0.000013 | 0.022070 |
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT | 0.009174 | 0.000002 | 0.002752 |
FLOOR 1 NURSE STATION VAV BOX COMPONENT | 0.080743 | 0.000014 | 0.024223 |
FLOOR 1 NURSE TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 OFFICE VAV BOX COMPONENT | 0.086772 | 0.000015 | 0.026032 |
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT | 0.850163 | 0.000505 | 0.850163 |
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT | 0.880422 | 0.000522 | 0.880422 |
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT | 0.748776 | 0.000444 | 0.748776 |
FLOOR 1 PACU VAV BOX COMPONENT | 0.050967 | 0.000030 | 0.050967 |
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT | 0.073958 | 0.000013 | 0.022188 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT | 0.089192 | 0.000053 | 0.089192 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT | 0.159508 | 0.000095 | 0.159508 |
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT | 0.336241 | 0.000200 | 0.336241 |
FLOOR 1 RECEPTION VAV BOX COMPONENT | 0.198701 | 0.000035 | 0.059610 |
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT | 0.019307 | 0.000003 | 0.005792 |
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT | 0.301412 | 0.000179 | 0.301412 |
FLOOR 1 SCHEDULING VAV BOX COMPONENT | 0.033210 | 0.000006 | 0.009963 |
FLOOR 1 SCRUB VAV BOX COMPONENT | 0.014206 | 0.000003 | 0.004262 |
FLOOR 1 SOIL VAV BOX COMPONENT | 0.099103 | 0.000059 | 0.099103 |
FLOOR 1 SOIL HOLD VAV BOX COMPONENT | 0.044046 | 0.000026 | 0.044046 |
FLOOR 1 SOIL WORK VAV BOX COMPONENT | 0.141575 | 0.000084 | 0.141575 |
FLOOR 1 STEP DOWN VAV BOX COMPONENT | 0.193219 | 0.000115 | 0.193219 |
FLOOR 1 STERILE HALL VAV BOX COMPONENT | 0.085124 | 0.000015 | 0.025537 |
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT | 0.043746 | 0.000008 | 0.013124 |
FLOOR 1 STORAGE VAV BOX COMPONENT | 0.182071 | 0.000091 | 0.154108 |
FLOOR 1 SUB-STERILE VAV BOX COMPONENT | 0.066698 | 0.000018 | 0.029555 |
FLOOR 1 UTILITY HALL VAV BOX COMPONENT | 0.075841 | 0.000032 | 0.054251 |
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT | 0.006769 | 0.000001 | 0.002194 |
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT | 0.091946 | 0.000033 | 0.055454 |
FLOOR 1 VESTIBULE VAV BOX COMPONENT | 0.040551 | 0.000012 | 0.019774 |
FLOOR 2 CONFERENCE VAV BOX COMPONENT | 0.305411 | ||
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT | 0.050338 | ||
FLOOR 2 DICTATION VAV BOX COMPONENT | 0.023064 | ||
FLOOR 2 EXAM 1 VAV BOX COMPONENT | 0.303386 | ||
FLOOR 2 EXAM 2 VAV BOX COMPONENT | 0.254836 | ||
FLOOR 2 EXAM 3 VAV BOX COMPONENT | 0.339781 | ||
FLOOR 2 EXAM 4 VAV BOX COMPONENT | 0.064962 | ||
FLOOR 2 EXAM 5 VAV BOX COMPONENT | 0.244451 | ||
FLOOR 2 EXAM 6 VAV BOX COMPONENT | 0.106759 | ||
FLOOR 2 EXAM 7 VAV BOX COMPONENT | 0.373759 | ||
FLOOR 2 EXAM 8 VAV BOX COMPONENT | 0.131104 | ||
FLOOR 2 EXAM 9 VAV BOX COMPONENT | 0.186879 | ||
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT | 0.054321 | ||
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT | 0.052736 | ||
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT | 0.050850 | ||
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT | 0.051385 | ||
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT | 0.053954 | ||
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT | 0.054215 | ||
FLOOR 2 JANITOR VAV BOX COMPONENT | 0.041007 | ||
FLOOR 2 LOUNGE VAV BOX COMPONENT | 0.037083 | ||
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT | 0.061631 | ||
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT | 0.074910 | ||
FLOOR 2 OFFICE VAV BOX COMPONENT | 0.318578 | ||
FLOOR 2 OFFICE HALL VAV BOX COMPONENT | 0.121403 | ||
FLOOR 2 RECEPTION VAV BOX COMPONENT | 0.615128 | ||
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT | 0.160971 | ||
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT | 0.099103 | ||
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT | 0.087572 | ||
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT | 0.096101 | ||
FLOOR 2 STORAGE 1 VAV BOX COMPONENT | 0.016070 | ||
FLOOR 2 STORAGE 2 VAV BOX COMPONENT | 0.028222 | ||
FLOOR 2 STORAGE 3 VAV BOX COMPONENT | 0.035927 | ||
FLOOR 2 UTILITY VAV BOX COMPONENT | 0.069383 | ||
FLOOR 2 WORK VAV BOX COMPONENT | 0.438063 | ||
FLOOR 2 WORK HALL VAV BOX COMPONENT | 0.223959 | ||
FLOOR 2 WORK TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 2 X-RAY VAV BOX COMPONENT | 0.846494 | ||
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT | 0.019451 | ||
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT | 0.093294 | ||
FLOOR 3 HUMID VAV BOX COMPONENT | 0.048541 | ||
FLOOR 3 JANITOR VAV BOX COMPONENT | 0.023908 | ||
FLOOR 3 LOCKER VAV BOX COMPONENT | 0.073560 | ||
FLOOR 3 LOUNGE VAV BOX COMPONENT | 0.419247 | ||
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT | 0.151014 | ||
FLOOR 3 MECHANICAL VAV BOX COMPONENT | 0.367990 | ||
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT | 0.112087 | ||
FLOOR 3 OFFICE VAV BOX COMPONENT | 1.07 | ||
FLOOR 3 OFFICE HALL VAV BOX COMPONENT | 0.246640 | ||
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT | 0.933325 | ||
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT | 0.300675 | ||
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT | 0.066069 | ||
FLOOR 3 STORAGE 1 VAV BOX COMPONENT | 0.032577 | ||
FLOOR 3 STORAGE 2 VAV BOX COMPONENT | 0.028360 | ||
FLOOR 3 TREATMENT VAV BOX COMPONENT | 0.249688 | ||
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT | 0.977043 | ||
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT | 0.516902 | ||
FLOOR 3 UTILITY VAV BOX COMPONENT | 0.055464 | ||
FLOOR 3 WORK VAV BOX COMPONENT | 0.363599 | ||
NE STAIR VAV BOX COMPONENT | 0.184950 | ||
NW ELEVATOR VAV BOX COMPONENT | 0.119764 | ||
NW STAIR VAV BOX COMPONENT | 0.201289 | ||
SW STAIR VAV BOX COMPONENT | 0.102285 |
Design Coil Load [W] | Maximum Water Flow Rate [m3/s] | U-Factor Times Area Value [W/K] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | 1873.21 | 0.000040 | 40.39 |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | 132.45 | 0.000003 | 4.39 |
FLOOR 1 CAFE VAV BOX REHEAT COIL | 2872.59 | 0.000062 | 206.45 |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | 1183.41 | 0.000025 | 25.52 |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | 1478.16 | 0.000032 | 31.87 |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | 217.63 | 0.000005 | 15.64 |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | 381.32 | 0.000008 | 11.17 |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | 405.63 | 0.000009 | 29.15 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | 2390.44 | 0.000051 | 171.80 |
FLOOR 1 HUMID VAV BOX REHEAT COIL | 107.46 | 0.000002 | 7.72 |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | 164.88 | 0.000004 | 11.85 |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | 180.19 | 0.000004 | 12.95 |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | 2541.26 | 0.000055 | 182.64 |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | 348.81 | 0.000008 | 25.07 |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | 1170.75 | 0.000025 | 25.24 |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | 1989.53 | 0.000043 | 142.99 |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | 509.49 | 0.000011 | 36.62 |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | 969.24 | 0.000021 | 69.66 |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | 560.28 | 0.000012 | 12.08 |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | 1162.16 | 0.000025 | 83.52 |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | 214.94 | 0.000005 | 15.45 |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | 2853.99 | 0.000061 | 205.12 |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | 1170.75 | 0.000025 | 25.24 |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | 493.93 | 0.000011 | 35.50 |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | 608.35 | 0.000013 | 43.72 |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | 75.86 | 0.000002 | 5.45 |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | 667.70 | 0.000014 | 47.99 |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | 1170.75 | 0.000025 | 25.24 |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | 717.56 | 0.000015 | 51.57 |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | 23434.68 | 0.000505 | 505.28 |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | 24268.77 | 0.000522 | 523.26 |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | 20639.98 | 0.000444 | 445.02 |
FLOOR 1 PACU VAV BOX REHEAT COIL | 1404.91 | 0.000030 | 30.29 |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | 611.60 | 0.000013 | 43.96 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | 2458.59 | 0.000053 | 53.01 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | 4396.84 | 0.000095 | 94.80 |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | 1170.75 | 0.000025 | 25.24 |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | 9268.48 | 0.000200 | 199.84 |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | 1643.15 | 0.000035 | 118.09 |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | 159.66 | 0.000003 | 11.47 |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | 8308.40 | 0.000179 | 179.14 |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | 274.63 | 0.000006 | 19.74 |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | 117.48 | 0.000003 | 8.44 |
FLOOR 1 SOIL VAV BOX REHEAT COIL | 2731.76 | 0.000059 | 58.90 |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | 1214.12 | 0.000026 | 26.18 |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | 3902.52 | 0.000084 | 84.14 |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | 5326.08 | 0.000115 | 114.84 |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | 703.93 | 0.000015 | 50.59 |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | 361.75 | 0.000008 | 26.00 |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | 4247.98 | 0.000091 | 108.21 |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | 814.67 | 0.000018 | 39.64 |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | 1495.43 | 0.000032 | 45.07 |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | 60.48 | 0.000001 | 4.02 |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | 1528.59 | 0.000033 | 54.65 |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | 545.06 | 0.000012 | 24.10 |
AHU-1_HEATC | 52833.40 | 0.001137 | 850.20 |
AHU-1_EXTRAWATERHEATC | 52833.40 | 0.001137 | 850.20 |
AHU-2_HEATC | 164213.42 | 0.003535 | 2567.27 |
Nominal Capacity [W] | |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | 2483.41 |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | 1364.39 |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | 187.54 |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | 8223.17 |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | 6907.22 |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | 9209.63 |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | 1760.76 |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | 6625.75 |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | 2893.65 |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | 10130.59 |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | 3553.52 |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | 5065.30 |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | 459.46 |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | 428.82 |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | 413.48 |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | 417.83 |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | 438.72 |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | 440.85 |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | 591.59 |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | 301.53 |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | 501.15 |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | 609.12 |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | 2590.48 |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | 987.18 |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | 5001.84 |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | 1308.92 |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | 2686.14 |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | 712.08 |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | 781.44 |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | 130.67 |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | 229.48 |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | 292.14 |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | 714.83 |
FLOOR 2 WORK VAV BOX REHEAT COIL | 3562.06 |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | 1821.10 |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | 1151.20 |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | 6883.17 |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | 178.76 |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | 1312.81 |
FLOOR 3 HUMID VAV BOX REHEAT COIL | 394.71 |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | 577.80 |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | 598.14 |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | 3409.05 |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | 4093.17 |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | 2992.27 |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | 1507.96 |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | 8674.02 |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | 2985.95 |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | 1151.20 |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | 25297.42 |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | 8149.69 |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | 1790.76 |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | 882.98 |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | 436.29 |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | 6767.70 |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | 7944.71 |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | 4744.93 |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | 881.60 |
FLOOR 3 WORK VAV BOX REHEAT COIL | 2956.56 |
NE STAIR VAV BOX REHEAT COIL | 4008.10 |
NW ELEVATOR VAV BOX REHEAT COIL | 2276.72 |
NW STAIR VAV BOX REHEAT COIL | 4053.83 |
SW STAIR VAV BOX REHEAT COIL | 1819.32 |
Maximum Flow Rate [m3/s] | |
AHU-1 AIR LOOP MAIN BRANCH | 7.56 |
AHU-2 AIR LOOP MAIN BRANCH | 11.95 |
Design Supply Air Flow Rate [m3/s] | |
AHU-1 | 7.56 |
AHU-2 | 11.95 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AHU-1_OA_CONTROLLER | 7.56 | 2.07 |
AHU-2_OA_CONTROLLER | 11.95 | 5.31 |
Rated High Speed Air Flow Rate [m3/s] | Rated High Speed Total Cooling Capacity (gross) [W] | Rated High Speed Sensible Heat Ratio | Rated Low Speed Air Flow Rate [m3/s] | Rated Low Speed Total Cooling Capacity (gross) [W] | |
AHU-1_COOLC DXCOIL | 7.56 | 141529.00 | 0.756209 | 2.52 | 47171.62 |
AHU-2_COOLC DXCOIL | 11.95 | 208367.62 | 0.780160 | 3.98 | 69448.93 |
Maximum Flow Rate [m3/s] | |
AHU-1_FAN | 7.56 |
AHU-2_FAN | 11.95 |
Maximum Actuated Flow [m3/s] | |
AHU-1_HEATC_CONTROLLER | 0.001137 |
AHU-1_EXTRAWATERHEATC_CONTROLLER | 0.001137 |
AHU-2_HEATC_CONTROLLER | 0.003535 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000063 | 0.047375 |
HEATSYS1 | 0.002710 | 2.03 |
Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 0.002710 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000063 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SWHSYS1 PUMP | 0.000063 | 8.07 |
HEATSYS1 PUMP | 0.002710 | 692.36 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ANESTHESIA
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.56 | -1.7 |
February | 19.65 | 2.70 |
March | 19.79 | 6.07 |
April | 19.67 | 11.58 |
May | 19.65 | 14.61 |
June | 19.71 | 19.78 |
July | 19.63 | 24.54 |
August | 19.79 | 21.22 |
September | 19.84 | 17.37 |
October | 19.85 | 11.70 |
November | 19.64 | 4.05 |
December | 19.59 | 1.86 |
Annual Sum or Average | 19.70 | 11.20 |
Minimum of Months | 19.56 | -1.7 |
Maximum of Months | 19.85 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 BIO HAZ
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.11 | -1.7 |
February | 20.26 | 2.70 |
March | 20.49 | 6.07 |
April | 20.67 | 11.58 |
May | 20.87 | 14.61 |
June | 21.47 | 19.78 |
July | 21.62 | 24.54 |
August | 21.52 | 21.22 |
September | 21.13 | 17.37 |
October | 20.59 | 11.70 |
November | 20.31 | 4.05 |
December | 20.20 | 1.86 |
Annual Sum or Average | 20.77 | 11.20 |
Minimum of Months | 20.11 | -1.7 |
Maximum of Months | 21.62 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CAFE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.57 | -1.7 |
February | 20.90 | 2.70 |
March | 21.14 | 6.07 |
April | 21.23 | 11.58 |
May | 21.23 | 14.61 |
June | 21.54 | 19.78 |
July | 21.55 | 24.54 |
August | 21.74 | 21.22 |
September | 21.67 | 17.37 |
October | 21.32 | 11.70 |
November | 20.87 | 4.05 |
December | 20.70 | 1.86 |
Annual Sum or Average | 21.21 | 11.20 |
Minimum of Months | 20.57 | -1.7 |
Maximum of Months | 21.74 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.35 | -1.7 |
February | 20.46 | 2.70 |
March | 20.63 | 6.07 |
April | 20.40 | 11.58 |
May | 20.33 | 14.61 |
June | 20.47 | 19.78 |
July | 20.23 | 24.54 |
August | 20.53 | 21.22 |
September | 20.53 | 17.37 |
October | 20.50 | 11.70 |
November | 20.47 | 4.05 |
December | 20.42 | 1.86 |
Annual Sum or Average | 20.44 | 11.20 |
Minimum of Months | 20.23 | -1.7 |
Maximum of Months | 20.63 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN WORK
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.06 | -1.7 |
February | 20.16 | 2.70 |
March | 20.33 | 6.07 |
April | 20.13 | 11.58 |
May | 20.09 | 14.61 |
June | 20.22 | 19.78 |
July | 20.00 | 24.54 |
August | 20.27 | 21.22 |
September | 20.26 | 17.37 |
October | 20.23 | 11.70 |
November | 20.16 | 4.05 |
December | 20.12 | 1.86 |
Annual Sum or Average | 20.17 | 11.20 |
Minimum of Months | 20.00 | -1.7 |
Maximum of Months | 20.33 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DICTATION
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.39 | -1.7 |
February | 21.50 | 2.70 |
March | 21.64 | 6.07 |
April | 21.52 | 11.58 |
May | 21.51 | 14.61 |
June | 21.72 | 19.78 |
July | 21.62 | 24.54 |
August | 21.79 | 21.22 |
September | 21.73 | 17.37 |
October | 21.59 | 11.70 |
November | 21.54 | 4.05 |
December | 21.47 | 1.86 |
Annual Sum or Average | 21.59 | 11.20 |
Minimum of Months | 21.39 | -1.7 |
Maximum of Months | 21.79 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DRESSING ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | -1.7 |
February | 19.72 | 2.70 |
March | 20.05 | 6.07 |
April | 20.46 | 11.58 |
May | 20.73 | 14.61 |
June | 21.37 | 19.78 |
July | 21.63 | 24.54 |
August | 21.39 | 21.22 |
September | 20.96 | 17.37 |
October | 20.32 | 11.70 |
November | 19.77 | 4.05 |
December | 19.62 | 1.86 |
Annual Sum or Average | 20.47 | 11.20 |
Minimum of Months | 19.58 | -1.7 |
Maximum of Months | 21.63 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELECTRICAL ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | -1.7 |
February | 21.15 | 2.70 |
March | 21.38 | 6.07 |
April | 21.52 | 11.58 |
May | 21.60 | 14.61 |
June | 21.92 | 19.78 |
July | 22.01 | 24.54 |
August | 21.99 | 21.22 |
September | 21.82 | 17.37 |
October | 21.50 | 11.70 |
November | 21.17 | 4.05 |
December | 21.03 | 1.86 |
Annual Sum or Average | 21.50 | 11.20 |
Minimum of Months | 20.92 | -1.7 |
Maximum of Months | 22.01 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELEVATOR PUMP ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | -1.7 |
February | 21.29 | 2.70 |
March | 21.51 | 6.07 |
April | 21.42 | 11.58 |
May | 21.49 | 14.61 |
June | 21.63 | 19.78 |
July | 21.44 | 24.54 |
August | 21.68 | 21.22 |
September | 21.51 | 17.37 |
October | 21.40 | 11.70 |
November | 21.30 | 4.05 |
December | 21.19 | 1.86 |
Annual Sum or Average | 21.42 | 11.20 |
Minimum of Months | 21.15 | -1.7 |
Maximum of Months | 21.68 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 HUMID
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | -1.7 |
February | 21.78 | 2.70 |
March | 21.91 | 6.07 |
April | 21.80 | 11.58 |
May | 21.78 | 14.61 |
June | 22.00 | 19.78 |
July | 21.92 | 24.54 |
August | 22.07 | 21.22 |
September | 22.02 | 17.37 |
October | 21.87 | 11.70 |
November | 21.82 | 4.05 |
December | 21.75 | 1.86 |
Annual Sum or Average | 21.86 | 11.20 |
Minimum of Months | 21.65 | -1.7 |
Maximum of Months | 22.07 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -1.7 |
February | 20.78 | 2.70 |
March | 20.97 | 6.07 |
April | 20.99 | 11.58 |
May | 21.07 | 14.61 |
June | 21.45 | 19.78 |
July | 21.44 | 24.54 |
August | 21.52 | 21.22 |
September | 21.33 | 17.37 |
October | 21.01 | 11.70 |
November | 20.83 | 4.05 |
December | 20.73 | 1.86 |
Annual Sum or Average | 21.06 | 11.20 |
Minimum of Months | 20.63 | -1.7 |
Maximum of Months | 21.52 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.86 | -1.7 |
February | 21.02 | 2.70 |
March | 21.24 | 6.07 |
April | 21.28 | 11.58 |
May | 21.40 | 14.61 |
June | 21.79 | 19.78 |
July | 21.82 | 24.54 |
August | 21.85 | 21.22 |
September | 21.61 | 17.37 |
October | 21.26 | 11.70 |
November | 21.07 | 4.05 |
December | 20.96 | 1.86 |
Annual Sum or Average | 21.35 | 11.20 |
Minimum of Months | 20.86 | -1.7 |
Maximum of Months | 21.85 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.36 | -1.7 |
February | 20.73 | 2.70 |
March | 21.08 | 6.07 |
April | 21.37 | 11.58 |
May | 21.54 | 14.61 |
June | 22.03 | 19.78 |
July | 22.12 | 24.54 |
August | 22.13 | 21.22 |
September | 21.80 | 17.37 |
October | 21.24 | 11.70 |
November | 20.73 | 4.05 |
December | 20.51 | 1.86 |
Annual Sum or Average | 21.31 | 11.20 |
Minimum of Months | 20.36 | -1.7 |
Maximum of Months | 22.13 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | -1.7 |
February | 21.61 | 2.70 |
March | 21.82 | 6.07 |
April | 21.90 | 11.58 |
May | 21.91 | 14.61 |
June | 22.25 | 19.78 |
July | 22.29 | 24.54 |
August | 22.36 | 21.22 |
September | 22.28 | 17.37 |
October | 21.95 | 11.70 |
November | 21.63 | 4.05 |
December | 21.47 | 1.86 |
Annual Sum or Average | 21.90 | 11.20 |
Minimum of Months | 21.30 | -1.7 |
Maximum of Months | 22.36 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | -1.7 |
February | 19.70 | 2.70 |
March | 19.86 | 6.07 |
April | 19.76 | 11.58 |
May | 19.84 | 14.61 |
June | 19.96 | 19.78 |
July | 19.83 | 24.54 |
August | 19.98 | 21.22 |
September | 19.82 | 17.37 |
October | 19.77 | 11.70 |
November | 19.67 | 4.05 |
December | 19.63 | 1.86 |
Annual Sum or Average | 19.79 | 11.20 |
Minimum of Months | 19.63 | -1.7 |
Maximum of Months | 19.98 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | -1.7 |
February | 21.35 | 2.70 |
March | 21.60 | 6.07 |
April | 21.65 | 11.58 |
May | 21.73 | 14.61 |
June | 22.06 | 19.78 |
July | 22.07 | 24.54 |
August | 22.10 | 21.22 |
September | 21.94 | 17.37 |
October | 21.66 | 11.70 |
November | 21.41 | 4.05 |
December | 21.29 | 1.86 |
Annual Sum or Average | 21.67 | 11.20 |
Minimum of Months | 21.15 | -1.7 |
Maximum of Months | 22.10 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | -1.7 |
February | 21.33 | 2.70 |
March | 21.52 | 6.07 |
April | 21.49 | 11.58 |
May | 21.52 | 14.61 |
June | 21.85 | 19.78 |
July | 21.83 | 24.54 |
August | 21.94 | 21.22 |
September | 21.83 | 17.37 |
October | 21.56 | 11.70 |
November | 21.40 | 4.05 |
December | 21.29 | 1.86 |
Annual Sum or Average | 21.56 | 11.20 |
Minimum of Months | 21.15 | -1.7 |
Maximum of Months | 21.94 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOUNGE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | -1.7 |
February | 21.61 | 2.70 |
March | 21.79 | 6.07 |
April | 21.75 | 11.58 |
May | 21.79 | 14.61 |
June | 22.06 | 19.78 |
July | 22.02 | 24.54 |
August | 22.10 | 21.22 |
September | 21.99 | 17.37 |
October | 21.77 | 11.70 |
November | 21.65 | 4.05 |
December | 21.57 | 1.86 |
Annual Sum or Average | 21.80 | 11.20 |
Minimum of Months | 21.49 | -1.7 |
Maximum of Months | 22.10 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MED GAS
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | -1.7 |
February | 19.56 | 2.70 |
March | 19.74 | 6.07 |
April | 20.06 | 11.58 |
May | 20.43 | 14.61 |
June | 21.29 | 19.78 |
July | 21.76 | 24.54 |
August | 21.36 | 21.22 |
September | 20.63 | 17.37 |
October | 19.82 | 11.70 |
November | 19.56 | 4.05 |
December | 19.51 | 1.86 |
Annual Sum or Average | 20.27 | 11.20 |
Minimum of Months | 19.50 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI CONTROL ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | -1.7 |
February | 22.08 | 2.70 |
March | 22.28 | 6.07 |
April | 22.37 | 11.58 |
May | 22.41 | 14.61 |
June | 22.65 | 19.78 |
July | 22.67 | 24.54 |
August | 22.67 | 21.22 |
September | 22.57 | 17.37 |
October | 22.36 | 11.70 |
November | 22.11 | 4.05 |
December | 22.01 | 1.86 |
Annual Sum or Average | 22.34 | 11.20 |
Minimum of Months | 21.89 | -1.7 |
Maximum of Months | 22.67 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | -1.7 |
February | 21.24 | 2.70 |
March | 21.47 | 6.07 |
April | 21.55 | 11.58 |
May | 21.61 | 14.61 |
June | 21.96 | 19.78 |
July | 21.99 | 24.54 |
August | 22.04 | 21.22 |
September | 21.90 | 17.37 |
October | 21.56 | 11.70 |
November | 21.30 | 4.05 |
December | 21.16 | 1.86 |
Annual Sum or Average | 21.57 | 11.20 |
Minimum of Months | 21.01 | -1.7 |
Maximum of Months | 22.04 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.42 | -1.7 |
February | 22.59 | 2.70 |
March | 22.72 | 6.07 |
April | 22.68 | 11.58 |
May | 22.63 | 14.61 |
June | 22.77 | 19.78 |
July | 22.70 | 24.54 |
August | 22.81 | 21.22 |
September | 22.84 | 17.37 |
October | 22.75 | 11.70 |
November | 22.61 | 4.05 |
December | 22.54 | 1.86 |
Annual Sum or Average | 22.67 | 11.20 |
Minimum of Months | 22.42 | -1.7 |
Maximum of Months | 22.84 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | -1.7 |
February | 19.50 | 2.70 |
March | 19.59 | 6.07 |
April | 19.51 | 11.58 |
May | 19.54 | 14.61 |
June | 19.58 | 19.78 |
July | 19.48 | 24.54 |
August | 19.59 | 21.22 |
September | 19.52 | 17.37 |
October | 19.49 | 11.70 |
November | 19.48 | 4.05 |
December | 19.47 | 1.86 |
Annual Sum or Average | 19.52 | 11.20 |
Minimum of Months | 19.47 | -1.7 |
Maximum of Months | 19.59 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NOURISHMENT
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | -1.7 |
February | 21.68 | 2.70 |
March | 21.82 | 6.07 |
April | 21.69 | 11.58 |
May | 21.67 | 14.61 |
June | 21.86 | 19.78 |
July | 21.75 | 24.54 |
August | 21.93 | 21.22 |
September | 21.87 | 17.37 |
October | 21.75 | 11.70 |
November | 21.71 | 4.05 |
December | 21.65 | 1.86 |
Annual Sum or Average | 21.75 | 11.20 |
Minimum of Months | 21.57 | -1.7 |
Maximum of Months | 21.93 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | -1.7 |
February | 20.98 | 2.70 |
March | 21.15 | 6.07 |
April | 21.11 | 11.58 |
May | 21.09 | 14.61 |
June | 21.40 | 19.78 |
July | 21.37 | 24.54 |
August | 21.55 | 21.22 |
September | 21.49 | 17.37 |
October | 21.24 | 11.70 |
November | 21.04 | 4.05 |
December | 20.95 | 1.86 |
Annual Sum or Average | 21.18 | 11.20 |
Minimum of Months | 20.80 | -1.7 |
Maximum of Months | 21.55 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE JANITOR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.42 | -1.7 |
February | 21.58 | 2.70 |
March | 21.74 | 6.07 |
April | 21.66 | 11.58 |
May | 21.65 | 14.61 |
June | 21.95 | 19.78 |
July | 21.90 | 24.54 |
August | 22.04 | 21.22 |
September | 21.97 | 17.37 |
October | 21.74 | 11.70 |
November | 21.64 | 4.05 |
December | 21.56 | 1.86 |
Annual Sum or Average | 21.74 | 11.20 |
Minimum of Months | 21.42 | -1.7 |
Maximum of Months | 22.04 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE STATION
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | -1.7 |
February | 21.49 | 2.70 |
March | 21.64 | 6.07 |
April | 21.54 | 11.58 |
May | 21.52 | 14.61 |
June | 21.73 | 19.78 |
July | 21.63 | 24.54 |
August | 21.83 | 21.22 |
September | 21.77 | 17.37 |
October | 21.61 | 11.70 |
November | 21.52 | 4.05 |
December | 21.44 | 1.86 |
Annual Sum or Average | 21.59 | 11.20 |
Minimum of Months | 21.36 | -1.7 |
Maximum of Months | 21.83 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | -1.7 |
February | 19.51 | 2.70 |
March | 19.59 | 6.07 |
April | 19.51 | 11.58 |
May | 19.53 | 14.61 |
June | 19.57 | 19.78 |
July | 19.47 | 24.54 |
August | 19.58 | 21.22 |
September | 19.51 | 17.37 |
October | 19.49 | 11.70 |
November | 19.49 | 4.05 |
December | 19.48 | 1.86 |
Annual Sum or Average | 19.52 | 11.20 |
Minimum of Months | 19.47 | -1.7 |
Maximum of Months | 19.59 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OFFICE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | -1.7 |
February | 21.55 | 2.70 |
March | 21.73 | 6.07 |
April | 21.73 | 11.58 |
May | 21.74 | 14.61 |
June | 22.03 | 19.78 |
July | 22.02 | 24.54 |
August | 22.12 | 21.22 |
September | 22.03 | 17.37 |
October | 21.77 | 11.70 |
November | 21.60 | 4.05 |
December | 21.49 | 1.86 |
Annual Sum or Average | 21.77 | 11.20 |
Minimum of Months | 21.36 | -1.7 |
Maximum of Months | 22.12 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.34 | -1.7 |
February | 18.36 | 2.70 |
March | 18.43 | 6.07 |
April | 18.41 | 11.58 |
May | 18.39 | 14.61 |
June | 18.36 | 19.78 |
July | 18.34 | 24.54 |
August | 18.35 | 21.22 |
September | 18.39 | 17.37 |
October | 18.45 | 11.70 |
November | 18.37 | 4.05 |
December | 18.35 | 1.86 |
Annual Sum or Average | 18.38 | 11.20 |
Minimum of Months | 18.34 | -1.7 |
Maximum of Months | 18.45 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.31 | -1.7 |
February | 18.33 | 2.70 |
March | 18.38 | 6.07 |
April | 18.39 | 11.58 |
May | 18.38 | 14.61 |
June | 18.37 | 19.78 |
July | 18.34 | 24.54 |
August | 18.35 | 21.22 |
September | 18.37 | 17.37 |
October | 18.39 | 11.70 |
November | 18.33 | 4.05 |
December | 18.32 | 1.86 |
Annual Sum or Average | 18.35 | 11.20 |
Minimum of Months | 18.31 | -1.7 |
Maximum of Months | 18.39 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 3
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.49 | -1.7 |
February | 18.51 | 2.70 |
March | 18.54 | 6.07 |
April | 18.46 | 11.58 |
May | 18.42 | 14.61 |
June | 18.38 | 19.78 |
July | 18.34 | 24.54 |
August | 18.37 | 21.22 |
September | 18.42 | 17.37 |
October | 18.50 | 11.70 |
November | 18.50 | 4.05 |
December | 18.50 | 1.86 |
Annual Sum or Average | 18.45 | 11.20 |
Minimum of Months | 18.34 | -1.7 |
Maximum of Months | 18.54 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PACU
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.78 | -1.7 |
February | 19.83 | 2.70 |
March | 19.96 | 6.07 |
April | 19.79 | 11.58 |
May | 19.79 | 14.61 |
June | 19.85 | 19.78 |
July | 19.69 | 24.54 |
August | 19.90 | 21.22 |
September | 19.86 | 17.37 |
October | 19.87 | 11.70 |
November | 19.82 | 4.05 |
December | 19.80 | 1.86 |
Annual Sum or Average | 19.83 | 11.20 |
Minimum of Months | 19.69 | -1.7 |
Maximum of Months | 19.96 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | -1.7 |
February | 20.94 | 2.70 |
March | 21.16 | 6.07 |
April | 21.22 | 11.58 |
May | 21.27 | 14.61 |
June | 21.66 | 19.78 |
July | 21.66 | 24.54 |
August | 21.79 | 21.22 |
September | 21.65 | 17.37 |
October | 21.29 | 11.70 |
November | 21.01 | 4.05 |
December | 20.86 | 1.86 |
Annual Sum or Average | 21.27 | 11.20 |
Minimum of Months | 20.70 | -1.7 |
Maximum of Months | 21.79 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.53 | -1.7 |
February | 19.59 | 2.70 |
March | 19.72 | 6.07 |
April | 19.64 | 11.58 |
May | 19.67 | 14.61 |
June | 19.77 | 19.78 |
July | 19.66 | 24.54 |
August | 19.83 | 21.22 |
September | 19.73 | 17.37 |
October | 19.67 | 11.70 |
November | 19.58 | 4.05 |
December | 19.54 | 1.86 |
Annual Sum or Average | 19.66 | 11.20 |
Minimum of Months | 19.53 | -1.7 |
Maximum of Months | 19.83 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.66 | -1.7 |
February | 19.70 | 2.70 |
March | 19.82 | 6.07 |
April | 19.67 | 11.58 |
May | 19.68 | 14.61 |
June | 19.73 | 19.78 |
July | 19.59 | 24.54 |
August | 19.77 | 21.22 |
September | 19.71 | 17.37 |
October | 19.72 | 11.70 |
November | 19.68 | 4.05 |
December | 19.67 | 1.86 |
Annual Sum or Average | 19.70 | 11.20 |
Minimum of Months | 19.59 | -1.7 |
Maximum of Months | 19.82 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | -1.7 |
February | 19.50 | 2.70 |
March | 19.58 | 6.07 |
April | 19.51 | 11.58 |
May | 19.55 | 14.61 |
June | 19.62 | 19.78 |
July | 19.54 | 24.54 |
August | 19.64 | 21.22 |
September | 19.54 | 17.37 |
October | 19.50 | 11.70 |
November | 19.48 | 4.05 |
December | 19.47 | 1.86 |
Annual Sum or Average | 19.53 | 11.20 |
Minimum of Months | 19.47 | -1.7 |
Maximum of Months | 19.64 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PROCEDURE ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | -1.7 |
February | 19.51 | 2.70 |
March | 19.59 | 6.07 |
April | 19.52 | 11.58 |
May | 19.54 | 14.61 |
June | 19.58 | 19.78 |
July | 19.49 | 24.54 |
August | 19.59 | 21.22 |
September | 19.52 | 17.37 |
October | 19.49 | 11.70 |
November | 19.49 | 4.05 |
December | 19.48 | 1.86 |
Annual Sum or Average | 19.52 | 11.20 |
Minimum of Months | 19.48 | -1.7 |
Maximum of Months | 19.59 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.03 | -1.7 |
February | 21.35 | 2.70 |
March | 21.55 | 6.07 |
April | 21.61 | 11.58 |
May | 21.62 | 14.61 |
June | 21.93 | 19.78 |
July | 21.96 | 24.54 |
August | 22.08 | 21.22 |
September | 22.00 | 17.37 |
October | 21.69 | 11.70 |
November | 21.35 | 4.05 |
December | 21.19 | 1.86 |
Annual Sum or Average | 21.61 | 11.20 |
Minimum of Months | 21.03 | -1.7 |
Maximum of Months | 22.08 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | -1.7 |
February | 21.21 | 2.70 |
March | 21.40 | 6.07 |
April | 21.42 | 11.58 |
May | 21.44 | 14.61 |
June | 21.80 | 19.78 |
July | 21.79 | 24.54 |
August | 21.92 | 21.22 |
September | 21.82 | 17.37 |
October | 21.50 | 11.70 |
November | 21.27 | 4.05 |
December | 21.13 | 1.86 |
Annual Sum or Average | 21.47 | 11.20 |
Minimum of Months | 20.98 | -1.7 |
Maximum of Months | 21.92 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECOVERY ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.57 | -1.7 |
February | 19.65 | 2.70 |
March | 19.80 | 6.07 |
April | 19.69 | 11.58 |
May | 19.65 | 14.61 |
June | 19.72 | 19.78 |
July | 19.64 | 24.54 |
August | 19.80 | 21.22 |
September | 19.85 | 17.37 |
October | 19.85 | 11.70 |
November | 19.64 | 4.05 |
December | 19.59 | 1.86 |
Annual Sum or Average | 19.70 | 11.20 |
Minimum of Months | 19.57 | -1.7 |
Maximum of Months | 19.85 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCHEDULING
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | -1.7 |
February | 20.92 | 2.70 |
March | 21.13 | 6.07 |
April | 21.23 | 11.58 |
May | 21.28 | 14.61 |
June | 21.63 | 19.78 |
July | 21.69 | 24.54 |
August | 21.79 | 21.22 |
September | 21.68 | 17.37 |
October | 21.32 | 11.70 |
November | 20.96 | 4.05 |
December | 20.77 | 1.86 |
Annual Sum or Average | 21.25 | 11.20 |
Minimum of Months | 20.58 | -1.7 |
Maximum of Months | 21.79 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCRUB
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.43 | -1.7 |
February | 20.67 | 2.70 |
March | 20.99 | 6.07 |
April | 21.18 | 11.58 |
May | 21.23 | 14.61 |
June | 21.64 | 19.78 |
July | 21.71 | 24.54 |
August | 21.74 | 21.22 |
September | 21.57 | 17.37 |
October | 21.18 | 11.70 |
November | 20.70 | 4.05 |
December | 20.55 | 1.86 |
Annual Sum or Average | 21.13 | 11.20 |
Minimum of Months | 20.43 | -1.7 |
Maximum of Months | 21.74 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | -1.7 |
February | 19.55 | 2.70 |
March | 19.63 | 6.07 |
April | 19.53 | 11.58 |
May | 19.55 | 14.61 |
June | 19.59 | 19.78 |
July | 19.48 | 24.54 |
August | 19.59 | 21.22 |
September | 19.53 | 17.37 |
October | 19.53 | 11.70 |
November | 19.53 | 4.05 |
December | 19.52 | 1.86 |
Annual Sum or Average | 19.55 | 11.20 |
Minimum of Months | 19.48 | -1.7 |
Maximum of Months | 19.63 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL HOLD
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | -1.7 |
February | 19.53 | 2.70 |
March | 19.63 | 6.07 |
April | 19.54 | 11.58 |
May | 19.56 | 14.61 |
June | 19.62 | 19.78 |
July | 19.51 | 24.54 |
August | 19.62 | 21.22 |
September | 19.55 | 17.37 |
October | 19.53 | 11.70 |
November | 19.52 | 4.05 |
December | 19.50 | 1.86 |
Annual Sum or Average | 19.55 | 11.20 |
Minimum of Months | 19.50 | -1.7 |
Maximum of Months | 19.63 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL WORK
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | -1.7 |
February | 19.52 | 2.70 |
March | 19.61 | 6.07 |
April | 19.52 | 11.58 |
May | 19.54 | 14.61 |
June | 19.58 | 19.78 |
July | 19.48 | 24.54 |
August | 19.59 | 21.22 |
September | 19.52 | 17.37 |
October | 19.51 | 11.70 |
November | 19.51 | 4.05 |
December | 19.49 | 1.86 |
Annual Sum or Average | 19.53 | 11.20 |
Minimum of Months | 19.48 | -1.7 |
Maximum of Months | 19.61 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STEP DOWN
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | -1.7 |
February | 19.57 | 2.70 |
March | 19.71 | 6.07 |
April | 19.65 | 11.58 |
May | 19.67 | 14.61 |
June | 19.76 | 19.78 |
July | 19.69 | 24.54 |
August | 19.82 | 21.22 |
September | 19.78 | 17.37 |
October | 19.72 | 11.70 |
November | 19.55 | 4.05 |
December | 19.51 | 1.86 |
Annual Sum or Average | 19.66 | 11.20 |
Minimum of Months | 19.50 | -1.7 |
Maximum of Months | 19.82 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -1.7 |
February | 20.91 | 2.70 |
March | 21.13 | 6.07 |
April | 21.23 | 11.58 |
May | 21.25 | 14.61 |
June | 21.62 | 19.78 |
July | 21.68 | 24.54 |
August | 21.76 | 21.22 |
September | 21.65 | 17.37 |
October | 21.30 | 11.70 |
November | 20.94 | 4.05 |
December | 20.79 | 1.86 |
Annual Sum or Average | 21.24 | 11.20 |
Minimum of Months | 20.64 | -1.7 |
Maximum of Months | 21.76 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE STORAGE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | -1.7 |
February | 21.45 | 2.70 |
March | 21.62 | 6.07 |
April | 21.56 | 11.58 |
May | 21.55 | 14.61 |
June | 21.88 | 19.78 |
July | 21.85 | 24.54 |
August | 21.98 | 21.22 |
September | 21.91 | 17.37 |
October | 21.64 | 11.70 |
November | 21.52 | 4.05 |
December | 21.42 | 1.86 |
Annual Sum or Average | 21.64 | 11.20 |
Minimum of Months | 21.28 | -1.7 |
Maximum of Months | 21.98 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STORAGE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | -1.7 |
February | 19.59 | 2.70 |
March | 19.79 | 6.07 |
April | 20.19 | 11.58 |
May | 20.61 | 14.61 |
June | 21.50 | 19.78 |
July | 21.89 | 24.54 |
August | 21.51 | 21.22 |
September | 20.77 | 17.37 |
October | 19.93 | 11.70 |
November | 19.60 | 4.05 |
December | 19.53 | 1.86 |
Annual Sum or Average | 20.37 | 11.20 |
Minimum of Months | 19.52 | -1.7 |
Maximum of Months | 21.89 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SUB-STERILE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.67 | -1.7 |
February | 19.89 | 2.70 |
March | 20.28 | 6.07 |
April | 20.72 | 11.58 |
May | 20.85 | 14.61 |
June | 21.38 | 19.78 |
July | 21.59 | 24.54 |
August | 21.45 | 21.22 |
September | 21.16 | 17.37 |
October | 20.60 | 11.70 |
November | 19.90 | 4.05 |
December | 19.74 | 1.86 |
Annual Sum or Average | 20.61 | 11.20 |
Minimum of Months | 19.67 | -1.7 |
Maximum of Months | 21.59 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.53 | -1.7 |
February | 19.61 | 2.70 |
March | 19.82 | 6.07 |
April | 20.16 | 11.58 |
May | 20.54 | 14.61 |
June | 21.35 | 19.78 |
July | 21.73 | 24.54 |
August | 21.41 | 21.22 |
September | 20.76 | 17.37 |
October | 20.00 | 11.70 |
November | 19.63 | 4.05 |
December | 19.54 | 1.86 |
Annual Sum or Average | 20.35 | 11.20 |
Minimum of Months | 19.53 | -1.7 |
Maximum of Months | 21.73 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY JANITOR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -1.7 |
February | 20.69 | 2.70 |
March | 20.98 | 6.07 |
April | 21.17 | 11.58 |
May | 21.25 | 14.61 |
June | 21.70 | 19.78 |
July | 21.79 | 24.54 |
August | 21.79 | 21.22 |
September | 21.58 | 17.37 |
October | 21.16 | 11.70 |
November | 20.74 | 4.05 |
December | 20.59 | 1.86 |
Annual Sum or Average | 21.16 | 11.20 |
Minimum of Months | 20.47 | -1.7 |
Maximum of Months | 21.79 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | -1.7 |
February | 19.78 | 2.70 |
March | 20.10 | 6.07 |
April | 20.53 | 11.58 |
May | 20.76 | 14.61 |
June | 21.45 | 19.78 |
July | 21.74 | 24.54 |
August | 21.53 | 21.22 |
September | 21.13 | 17.37 |
October | 20.39 | 11.70 |
November | 19.81 | 4.05 |
December | 19.67 | 1.86 |
Annual Sum or Average | 20.55 | 11.20 |
Minimum of Months | 19.61 | -1.7 |
Maximum of Months | 21.74 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 VESTIBULE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.91 | -1.7 |
February | 14.62 | 2.70 |
March | 15.33 | 6.07 |
April | 17.84 | 11.58 |
May | 18.60 | 14.61 |
June | 21.26 | 19.78 |
July | 22.72 | 24.54 |
August | 21.87 | 21.22 |
September | 19.93 | 17.37 |
October | 17.39 | 11.70 |
November | 14.88 | 4.05 |
December | 14.14 | 1.86 |
Annual Sum or Average | 17.64 | 11.20 |
Minimum of Months | 12.91 | -1.7 |
Maximum of Months | 22.72 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.16 | -1.7 |
February | 20.59 | 2.70 |
March | 20.86 | 6.07 |
April | 21.08 | 11.58 |
May | 21.05 | 14.61 |
June | 21.27 | 19.78 |
July | 21.42 | 24.54 |
August | 21.46 | 21.22 |
September | 21.36 | 17.37 |
October | 21.07 | 11.70 |
November | 20.52 | 4.05 |
December | 20.29 | 1.86 |
Annual Sum or Average | 20.93 | 11.20 |
Minimum of Months | 20.16 | -1.7 |
Maximum of Months | 21.46 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | -1.7 |
February | 19.69 | 2.70 |
March | 19.83 | 6.07 |
April | 19.69 | 11.58 |
May | 19.65 | 14.61 |
June | 19.63 | 19.78 |
July | 19.51 | 24.54 |
August | 19.65 | 21.22 |
September | 19.61 | 17.37 |
October | 19.68 | 11.70 |
November | 19.67 | 4.05 |
December | 19.64 | 1.86 |
Annual Sum or Average | 19.66 | 11.20 |
Minimum of Months | 19.51 | -1.7 |
Maximum of Months | 19.83 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 DICTATION
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.21 | -1.7 |
February | 21.45 | 2.70 |
March | 21.64 | 6.07 |
April | 21.56 | 11.58 |
May | 21.48 | 14.61 |
June | 21.57 | 19.78 |
July | 21.43 | 24.54 |
August | 21.62 | 21.22 |
September | 21.53 | 17.37 |
October | 21.52 | 11.70 |
November | 21.43 | 4.05 |
December | 21.35 | 1.86 |
Annual Sum or Average | 21.48 | 11.20 |
Minimum of Months | 21.21 | -1.7 |
Maximum of Months | 21.64 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | -1.7 |
February | 19.56 | 2.70 |
March | 19.71 | 6.07 |
April | 19.65 | 11.58 |
May | 19.66 | 14.61 |
June | 19.76 | 19.78 |
July | 19.74 | 24.54 |
August | 19.82 | 21.22 |
September | 19.66 | 17.37 |
October | 19.59 | 11.70 |
November | 19.53 | 4.05 |
December | 19.50 | 1.86 |
Annual Sum or Average | 19.64 | 11.20 |
Minimum of Months | 19.50 | -1.7 |
Maximum of Months | 19.82 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.84 | -1.7 |
February | 19.99 | 2.70 |
March | 20.18 | 6.07 |
April | 20.01 | 11.58 |
May | 19.93 | 14.61 |
June | 19.94 | 19.78 |
July | 19.83 | 24.54 |
August | 20.01 | 21.22 |
September | 19.95 | 17.37 |
October | 20.05 | 11.70 |
November | 19.96 | 4.05 |
December | 19.90 | 1.86 |
Annual Sum or Average | 19.97 | 11.20 |
Minimum of Months | 19.83 | -1.7 |
Maximum of Months | 20.18 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 3
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.81 | -1.7 |
February | 19.94 | 2.70 |
March | 20.11 | 6.07 |
April | 19.90 | 11.58 |
May | 19.83 | 14.61 |
June | 19.82 | 19.78 |
July | 19.73 | 24.54 |
August | 19.89 | 21.22 |
September | 19.84 | 17.37 |
October | 19.97 | 11.70 |
November | 19.90 | 4.05 |
December | 19.86 | 1.86 |
Annual Sum or Average | 19.88 | 11.20 |
Minimum of Months | 19.73 | -1.7 |
Maximum of Months | 20.11 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 4
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.65 | -1.7 |
February | 19.80 | 2.70 |
March | 19.97 | 6.07 |
April | 19.79 | 11.58 |
May | 19.71 | 14.61 |
June | 19.76 | 19.78 |
July | 19.72 | 24.54 |
August | 19.86 | 21.22 |
September | 19.84 | 17.37 |
October | 19.95 | 11.70 |
November | 19.76 | 4.05 |
December | 19.70 | 1.86 |
Annual Sum or Average | 19.79 | 11.20 |
Minimum of Months | 19.65 | -1.7 |
Maximum of Months | 19.97 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 5
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | -1.7 |
February | 19.58 | 2.70 |
March | 19.72 | 6.07 |
April | 19.67 | 11.58 |
May | 19.68 | 14.61 |
June | 19.75 | 19.78 |
July | 19.70 | 24.54 |
August | 19.75 | 21.22 |
September | 19.62 | 17.37 |
October | 19.59 | 11.70 |
November | 19.55 | 4.05 |
December | 19.52 | 1.86 |
Annual Sum or Average | 19.64 | 11.20 |
Minimum of Months | 19.52 | -1.7 |
Maximum of Months | 19.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 6
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | -1.7 |
February | 19.71 | 2.70 |
March | 19.89 | 6.07 |
April | 19.88 | 11.58 |
May | 19.92 | 14.61 |
June | 20.08 | 19.78 |
July | 20.00 | 24.54 |
August | 20.03 | 21.22 |
September | 19.83 | 17.37 |
October | 19.78 | 11.70 |
November | 19.70 | 4.05 |
December | 19.63 | 1.86 |
Annual Sum or Average | 19.84 | 11.20 |
Minimum of Months | 19.61 | -1.7 |
Maximum of Months | 20.08 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 7
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.73 | -1.7 |
February | 19.83 | 2.70 |
March | 19.98 | 6.07 |
April | 19.87 | 11.58 |
May | 19.86 | 14.61 |
June | 19.87 | 19.78 |
July | 19.72 | 24.54 |
August | 19.85 | 21.22 |
September | 19.76 | 17.37 |
October | 19.80 | 11.70 |
November | 19.81 | 4.05 |
December | 19.76 | 1.86 |
Annual Sum or Average | 19.82 | 11.20 |
Minimum of Months | 19.72 | -1.7 |
Maximum of Months | 19.98 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 8
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.65 | -1.7 |
February | 19.77 | 2.70 |
March | 19.96 | 6.07 |
April | 19.93 | 11.58 |
May | 19.97 | 14.61 |
June | 20.10 | 19.78 |
July | 20.00 | 24.54 |
August | 20.05 | 21.22 |
September | 19.86 | 17.37 |
October | 19.83 | 11.70 |
November | 19.76 | 4.05 |
December | 19.69 | 1.86 |
Annual Sum or Average | 19.88 | 11.20 |
Minimum of Months | 19.65 | -1.7 |
Maximum of Months | 20.10 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 9
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.81 | -1.7 |
February | 19.94 | 2.70 |
March | 20.12 | 6.07 |
April | 20.03 | 11.58 |
May | 20.02 | 14.61 |
June | 20.06 | 19.78 |
July | 19.91 | 24.54 |
August | 20.04 | 21.22 |
September | 19.92 | 17.37 |
October | 19.94 | 11.70 |
November | 19.92 | 4.05 |
December | 19.86 | 1.86 |
Annual Sum or Average | 19.96 | 11.20 |
Minimum of Months | 19.81 | -1.7 |
Maximum of Months | 20.12 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -1.7 |
February | 20.86 | 2.70 |
March | 21.15 | 6.07 |
April | 21.26 | 11.58 |
May | 21.24 | 14.61 |
June | 21.44 | 19.78 |
July | 21.46 | 24.54 |
August | 21.62 | 21.22 |
September | 21.45 | 17.37 |
October | 21.21 | 11.70 |
November | 20.80 | 4.05 |
December | 20.63 | 1.86 |
Annual Sum or Average | 21.13 | 11.20 |
Minimum of Months | 20.46 | -1.7 |
Maximum of Months | 21.62 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | -1.7 |
February | 21.04 | 2.70 |
March | 21.27 | 6.07 |
April | 21.28 | 11.58 |
May | 21.19 | 14.61 |
June | 21.32 | 19.78 |
July | 21.27 | 24.54 |
August | 21.46 | 21.22 |
September | 21.38 | 17.37 |
October | 21.29 | 11.70 |
November | 20.99 | 4.05 |
December | 20.86 | 1.86 |
Annual Sum or Average | 21.17 | 11.20 |
Minimum of Months | 20.67 | -1.7 |
Maximum of Months | 21.46 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 3
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | -1.7 |
February | 20.99 | 2.70 |
March | 21.20 | 6.07 |
April | 21.16 | 11.58 |
May | 21.05 | 14.61 |
June | 21.16 | 19.78 |
July | 21.11 | 24.54 |
August | 21.30 | 21.22 |
September | 21.25 | 17.37 |
October | 21.21 | 11.70 |
November | 20.94 | 4.05 |
December | 20.82 | 1.86 |
Annual Sum or Average | 21.07 | 11.20 |
Minimum of Months | 20.65 | -1.7 |
Maximum of Months | 21.30 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 4
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | -1.7 |
February | 20.93 | 2.70 |
March | 21.23 | 6.07 |
April | 21.29 | 11.58 |
May | 21.33 | 14.61 |
June | 21.55 | 19.78 |
July | 21.46 | 24.54 |
August | 21.51 | 21.22 |
September | 21.27 | 17.37 |
October | 21.12 | 11.70 |
November | 20.94 | 4.05 |
December | 20.82 | 1.86 |
Annual Sum or Average | 21.18 | 11.20 |
Minimum of Months | 20.65 | -1.7 |
Maximum of Months | 21.55 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 5
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | -1.7 |
February | 21.00 | 2.70 |
March | 21.32 | 6.07 |
April | 21.40 | 11.58 |
May | 21.45 | 14.61 |
June | 21.69 | 19.78 |
July | 21.61 | 24.54 |
August | 21.65 | 21.22 |
September | 21.40 | 17.37 |
October | 21.23 | 11.70 |
November | 21.02 | 4.05 |
December | 20.88 | 1.86 |
Annual Sum or Average | 21.28 | 11.20 |
Minimum of Months | 20.69 | -1.7 |
Maximum of Months | 21.69 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 6
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -1.7 |
February | 20.94 | 2.70 |
March | 21.26 | 6.07 |
April | 21.36 | 11.58 |
May | 21.40 | 14.61 |
June | 21.65 | 19.78 |
July | 21.58 | 24.54 |
August | 21.61 | 21.22 |
September | 21.36 | 17.37 |
October | 21.18 | 11.70 |
November | 20.95 | 4.05 |
December | 20.81 | 1.86 |
Annual Sum or Average | 21.23 | 11.20 |
Minimum of Months | 20.62 | -1.7 |
Maximum of Months | 21.65 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 JANITOR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.08 | -1.7 |
February | 20.37 | 2.70 |
March | 20.75 | 6.07 |
April | 21.00 | 11.58 |
May | 21.21 | 14.61 |
June | 21.65 | 19.78 |
July | 21.81 | 24.54 |
August | 21.72 | 21.22 |
September | 21.23 | 17.37 |
October | 20.83 | 11.70 |
November | 20.41 | 4.05 |
December | 20.20 | 1.86 |
Annual Sum or Average | 20.94 | 11.20 |
Minimum of Months | 20.08 | -1.7 |
Maximum of Months | 21.81 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 LOUNGE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | -1.7 |
February | 21.67 | 2.70 |
March | 21.85 | 6.07 |
April | 21.80 | 11.58 |
May | 21.73 | 14.61 |
June | 21.81 | 19.78 |
July | 21.70 | 24.54 |
August | 21.84 | 21.22 |
September | 21.74 | 17.37 |
October | 21.73 | 11.70 |
November | 21.66 | 4.05 |
December | 21.58 | 1.86 |
Annual Sum or Average | 21.72 | 11.20 |
Minimum of Months | 21.47 | -1.7 |
Maximum of Months | 21.85 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | -1.7 |
February | 21.72 | 2.70 |
March | 21.95 | 6.07 |
April | 21.94 | 11.58 |
May | 21.91 | 14.61 |
June | 22.04 | 19.78 |
July | 21.97 | 24.54 |
August | 22.04 | 21.22 |
September | 21.89 | 17.37 |
October | 21.82 | 11.70 |
November | 21.72 | 4.05 |
December | 21.63 | 1.86 |
Annual Sum or Average | 21.84 | 11.20 |
Minimum of Months | 21.49 | -1.7 |
Maximum of Months | 22.04 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | -1.7 |
February | 21.76 | 2.70 |
March | 22.00 | 6.07 |
April | 22.00 | 11.58 |
May | 21.98 | 14.61 |
June | 22.12 | 19.78 |
July | 22.06 | 24.54 |
August | 22.11 | 21.22 |
September | 21.95 | 17.37 |
October | 21.87 | 11.70 |
November | 21.77 | 4.05 |
December | 21.67 | 1.86 |
Annual Sum or Average | 21.90 | 11.20 |
Minimum of Months | 21.52 | -1.7 |
Maximum of Months | 22.12 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.81 | -1.7 |
February | 20.15 | 2.70 |
March | 20.69 | 6.07 |
April | 21.14 | 11.58 |
May | 21.24 | 14.61 |
June | 21.57 | 19.78 |
July | 21.74 | 24.54 |
August | 21.59 | 21.22 |
September | 21.27 | 17.37 |
October | 20.87 | 11.70 |
November | 20.16 | 4.05 |
December | 19.92 | 1.86 |
Annual Sum or Average | 20.85 | 11.20 |
Minimum of Months | 19.81 | -1.7 |
Maximum of Months | 21.74 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -1.7 |
February | 20.84 | 2.70 |
March | 21.22 | 6.07 |
April | 21.43 | 11.58 |
May | 21.45 | 14.61 |
June | 21.70 | 19.78 |
July | 21.71 | 24.54 |
August | 21.72 | 21.22 |
September | 21.48 | 17.37 |
October | 21.24 | 11.70 |
November | 20.84 | 4.05 |
December | 20.69 | 1.86 |
Annual Sum or Average | 21.24 | 11.20 |
Minimum of Months | 20.53 | -1.7 |
Maximum of Months | 21.72 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -1.7 |
February | 21.03 | 2.70 |
March | 21.32 | 6.07 |
April | 21.62 | 11.58 |
May | 21.65 | 14.61 |
June | 21.95 | 19.78 |
July | 22.07 | 24.54 |
August | 22.09 | 21.22 |
September | 21.86 | 17.37 |
October | 21.50 | 11.70 |
November | 20.96 | 4.05 |
December | 20.74 | 1.86 |
Annual Sum or Average | 21.45 | 11.20 |
Minimum of Months | 20.55 | -1.7 |
Maximum of Months | 22.09 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.22 | -1.7 |
February | 21.53 | 2.70 |
March | 21.74 | 6.07 |
April | 21.74 | 11.58 |
May | 21.67 | 14.61 |
June | 21.79 | 19.78 |
July | 21.70 | 24.54 |
August | 21.85 | 21.22 |
September | 21.74 | 17.37 |
October | 21.67 | 11.70 |
November | 21.51 | 4.05 |
December | 21.40 | 1.86 |
Annual Sum or Average | 21.63 | 11.20 |
Minimum of Months | 21.22 | -1.7 |
Maximum of Months | 21.85 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.65 | -1.7 |
February | 19.73 | 2.70 |
March | 19.87 | 6.07 |
April | 19.73 | 11.58 |
May | 19.68 | 14.61 |
June | 19.66 | 19.78 |
July | 19.51 | 24.54 |
August | 19.67 | 21.22 |
September | 19.63 | 17.37 |
October | 19.70 | 11.70 |
November | 19.70 | 4.05 |
December | 19.67 | 1.86 |
Annual Sum or Average | 19.68 | 11.20 |
Minimum of Months | 19.51 | -1.7 |
Maximum of Months | 19.87 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | -1.7 |
February | 21.85 | 2.70 |
March | 22.04 | 6.07 |
April | 22.02 | 11.58 |
May | 21.97 | 14.61 |
June | 22.08 | 19.78 |
July | 22.00 | 24.54 |
August | 22.10 | 21.22 |
September | 21.99 | 17.37 |
October | 21.93 | 11.70 |
November | 21.85 | 4.05 |
December | 21.77 | 1.86 |
Annual Sum or Average | 21.94 | 11.20 |
Minimum of Months | 21.63 | -1.7 |
Maximum of Months | 22.10 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | -1.7 |
February | 21.83 | 2.70 |
March | 22.01 | 6.07 |
April | 22.02 | 11.58 |
May | 21.96 | 14.61 |
June | 22.07 | 19.78 |
July | 22.01 | 24.54 |
August | 22.11 | 21.22 |
September | 22.00 | 17.37 |
October | 21.93 | 11.70 |
November | 21.81 | 4.05 |
December | 21.71 | 1.86 |
Annual Sum or Average | 21.92 | 11.20 |
Minimum of Months | 21.56 | -1.7 |
Maximum of Months | 22.11 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -1.7 |
February | 20.84 | 2.70 |
March | 21.04 | 6.07 |
April | 20.98 | 11.58 |
May | 20.88 | 14.61 |
June | 21.00 | 19.78 |
July | 20.93 | 24.54 |
August | 21.11 | 21.22 |
September | 21.05 | 17.37 |
October | 21.02 | 11.70 |
November | 20.84 | 4.05 |
December | 20.77 | 1.86 |
Annual Sum or Average | 20.92 | 11.20 |
Minimum of Months | 20.59 | -1.7 |
Maximum of Months | 21.11 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | -1.7 |
February | 20.99 | 2.70 |
March | 21.29 | 6.07 |
April | 21.39 | 11.58 |
May | 21.42 | 14.61 |
June | 21.65 | 19.78 |
July | 21.59 | 24.54 |
August | 21.63 | 21.22 |
September | 21.39 | 17.37 |
October | 21.22 | 11.70 |
November | 21.00 | 4.05 |
December | 20.87 | 1.86 |
Annual Sum or Average | 21.26 | 11.20 |
Minimum of Months | 20.70 | -1.7 |
Maximum of Months | 21.65 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 3
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.76 | -1.7 |
February | 21.09 | 2.70 |
March | 21.41 | 6.07 |
April | 21.51 | 11.58 |
May | 21.55 | 14.61 |
June | 21.80 | 19.78 |
July | 21.73 | 24.54 |
August | 21.76 | 21.22 |
September | 21.52 | 17.37 |
October | 21.33 | 11.70 |
November | 21.11 | 4.05 |
December | 20.96 | 1.86 |
Annual Sum or Average | 21.38 | 11.20 |
Minimum of Months | 20.76 | -1.7 |
Maximum of Months | 21.80 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 UTILITY
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | -1.7 |
February | 19.91 | 2.70 |
March | 20.35 | 6.07 |
April | 20.81 | 11.58 |
May | 20.92 | 14.61 |
June | 21.33 | 19.78 |
July | 21.50 | 24.54 |
August | 21.33 | 21.22 |
September | 20.95 | 17.37 |
October | 20.50 | 11.70 |
November | 19.90 | 4.05 |
December | 19.75 | 1.86 |
Annual Sum or Average | 20.58 | 11.20 |
Minimum of Months | 19.68 | -1.7 |
Maximum of Months | 21.50 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | -1.7 |
February | 21.43 | 2.70 |
March | 21.77 | 6.07 |
April | 21.92 | 11.58 |
May | 21.98 | 14.61 |
June | 22.23 | 19.78 |
July | 22.28 | 24.54 |
August | 22.25 | 21.22 |
September | 22.00 | 17.37 |
October | 21.76 | 11.70 |
November | 21.45 | 4.05 |
December | 21.30 | 1.86 |
Annual Sum or Average | 21.79 | 11.20 |
Minimum of Months | 21.08 | -1.7 |
Maximum of Months | 22.28 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | -1.7 |
February | 21.59 | 2.70 |
March | 21.84 | 6.07 |
April | 21.91 | 11.58 |
May | 21.89 | 14.61 |
June | 22.07 | 19.78 |
July | 22.04 | 24.54 |
August | 22.10 | 21.22 |
September | 21.94 | 17.37 |
October | 21.79 | 11.70 |
November | 21.58 | 4.05 |
December | 21.45 | 1.86 |
Annual Sum or Average | 21.79 | 11.20 |
Minimum of Months | 21.25 | -1.7 |
Maximum of Months | 22.10 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.53 | -1.7 |
February | 19.59 | 2.70 |
March | 19.74 | 6.07 |
April | 19.68 | 11.58 |
May | 19.70 | 14.61 |
June | 19.77 | 19.78 |
July | 19.65 | 24.54 |
August | 19.78 | 21.22 |
September | 19.64 | 17.37 |
October | 19.63 | 11.70 |
November | 19.57 | 4.05 |
December | 19.53 | 1.86 |
Annual Sum or Average | 19.65 | 11.20 |
Minimum of Months | 19.53 | -1.7 |
Maximum of Months | 19.78 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 X-RAY
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.91 | -1.7 |
February | 23.09 | 2.70 |
March | 23.16 | 6.07 |
April | 22.92 | 11.58 |
May | 22.77 | 14.61 |
June | 22.64 | 19.78 |
July | 22.53 | 24.54 |
August | 22.64 | 21.22 |
September | 22.65 | 17.37 |
October | 22.90 | 11.70 |
November | 23.05 | 4.05 |
December | 23.03 | 1.86 |
Annual Sum or Average | 22.86 | 11.20 |
Minimum of Months | 22.53 | -1.7 |
Maximum of Months | 23.16 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 DRESSING ROOM
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -1.7 |
February | 20.77 | 2.70 |
March | 21.05 | 6.07 |
April | 21.10 | 11.58 |
May | 21.16 | 14.61 |
June | 21.26 | 19.78 |
July | 21.23 | 24.54 |
August | 21.28 | 21.22 |
September | 21.07 | 17.37 |
October | 20.96 | 11.70 |
November | 20.77 | 4.05 |
December | 20.63 | 1.86 |
Annual Sum or Average | 20.98 | 11.20 |
Minimum of Months | 20.50 | -1.7 |
Maximum of Months | 21.28 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 ELEVATOR HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.02 | -1.7 |
February | 20.40 | 2.70 |
March | 20.88 | 6.07 |
April | 21.29 | 11.58 |
May | 21.48 | 14.61 |
June | 21.89 | 19.78 |
July | 22.09 | 24.54 |
August | 21.91 | 21.22 |
September | 21.45 | 17.37 |
October | 20.95 | 11.70 |
November | 20.41 | 4.05 |
December | 20.18 | 1.86 |
Annual Sum or Average | 21.09 | 11.20 |
Minimum of Months | 20.02 | -1.7 |
Maximum of Months | 22.09 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 HUMID
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | -1.7 |
February | 20.87 | 2.70 |
March | 21.15 | 6.07 |
April | 21.22 | 11.58 |
May | 21.27 | 14.61 |
June | 21.38 | 19.78 |
July | 21.36 | 24.54 |
August | 21.41 | 21.22 |
September | 21.19 | 17.37 |
October | 21.07 | 11.70 |
November | 20.87 | 4.05 |
December | 20.72 | 1.86 |
Annual Sum or Average | 21.09 | 11.20 |
Minimum of Months | 20.58 | -1.7 |
Maximum of Months | 21.41 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 JANITOR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.57 | -1.7 |
February | 19.72 | 2.70 |
March | 20.04 | 6.07 |
April | 20.42 | 11.58 |
May | 20.70 | 14.61 |
June | 21.28 | 19.78 |
July | 21.61 | 24.54 |
August | 21.35 | 21.22 |
September | 20.72 | 17.37 |
October | 20.14 | 11.70 |
November | 19.73 | 4.05 |
December | 19.60 | 1.86 |
Annual Sum or Average | 20.41 | 11.20 |
Minimum of Months | 19.57 | -1.7 |
Maximum of Months | 21.61 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOCKER
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -1.7 |
February | 20.91 | 2.70 |
March | 21.25 | 6.07 |
April | 21.40 | 11.58 |
May | 21.50 | 14.61 |
June | 21.70 | 19.78 |
July | 21.73 | 24.54 |
August | 21.68 | 21.22 |
September | 21.39 | 17.37 |
October | 21.20 | 11.70 |
November | 20.91 | 4.05 |
December | 20.75 | 1.86 |
Annual Sum or Average | 21.25 | 11.20 |
Minimum of Months | 20.60 | -1.7 |
Maximum of Months | 21.73 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -1.7 |
February | 20.98 | 2.70 |
March | 21.35 | 6.07 |
April | 21.58 | 11.58 |
May | 21.68 | 14.61 |
June | 21.94 | 19.78 |
July | 22.04 | 24.54 |
August | 21.90 | 21.22 |
September | 21.57 | 17.37 |
October | 21.33 | 11.70 |
November | 20.97 | 4.05 |
December | 20.82 | 1.86 |
Annual Sum or Average | 21.40 | 11.20 |
Minimum of Months | 20.64 | -1.7 |
Maximum of Months | 22.04 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | -1.7 |
February | 19.51 | 2.70 |
March | 19.60 | 6.07 |
April | 19.53 | 11.58 |
May | 19.56 | 14.61 |
June | 19.63 | 19.78 |
July | 19.54 | 24.54 |
August | 19.61 | 21.22 |
September | 19.52 | 17.37 |
October | 19.49 | 11.70 |
November | 19.49 | 4.05 |
December | 19.47 | 1.86 |
Annual Sum or Average | 19.54 | 11.20 |
Minimum of Months | 19.47 | -1.7 |
Maximum of Months | 19.63 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | -1.7 |
February | 21.50 | 2.70 |
March | 21.73 | 6.07 |
April | 22.12 | 11.58 |
May | 22.28 | 14.61 |
June | 22.41 | 19.78 |
July | 22.68 | 24.54 |
August | 22.39 | 21.22 |
September | 22.21 | 17.37 |
October | 21.98 | 11.70 |
November | 21.46 | 4.05 |
December | 21.31 | 1.86 |
Annual Sum or Average | 21.93 | 11.20 |
Minimum of Months | 21.09 | -1.7 |
Maximum of Months | 22.68 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.00 | -1.7 |
February | 20.37 | 2.70 |
March | 20.85 | 6.07 |
April | 21.25 | 11.58 |
May | 21.41 | 14.61 |
June | 21.71 | 19.78 |
July | 21.90 | 24.54 |
August | 21.72 | 21.22 |
September | 21.37 | 17.37 |
October | 20.97 | 11.70 |
November | 20.38 | 4.05 |
December | 20.13 | 1.86 |
Annual Sum or Average | 21.01 | 11.20 |
Minimum of Months | 20.00 | -1.7 |
Maximum of Months | 21.90 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.20 | -1.7 |
February | 20.60 | 2.70 |
March | 21.04 | 6.07 |
April | 21.39 | 11.58 |
May | 21.56 | 14.61 |
June | 21.91 | 19.78 |
July | 22.06 | 24.54 |
August | 21.88 | 21.22 |
September | 21.47 | 17.37 |
October | 21.08 | 11.70 |
November | 20.61 | 4.05 |
December | 20.38 | 1.86 |
Annual Sum or Average | 21.19 | 11.20 |
Minimum of Months | 20.20 | -1.7 |
Maximum of Months | 22.06 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE HALL
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.24 | -1.7 |
February | 20.68 | 2.70 |
March | 21.10 | 6.07 |
April | 21.46 | 11.58 |
May | 21.58 | 14.61 |
June | 21.88 | 19.78 |
July | 22.04 | 24.54 |
August | 21.92 | 21.22 |
September | 21.57 | 17.37 |
October | 21.17 | 11.70 |
November | 20.66 | 4.05 |
December | 20.44 | 1.86 |
Annual Sum or Average | 21.23 | 11.20 |
Minimum of Months | 20.24 | -1.7 |
Maximum of Months | 22.04 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | -1.7 |
February | 19.53 | 2.70 |
March | 19.65 | 6.07 |
April | 19.58 | 11.58 |
May | 19.61 | 14.61 |
June | 19.69 | 19.78 |
July | 19.62 | 24.54 |
August | 19.70 | 21.22 |
September | 19.57 | 17.37 |
October | 19.53 | 11.70 |
November | 19.50 | 4.05 |
December | 19.48 | 1.86 |
Annual Sum or Average | 19.58 | 11.20 |
Minimum of Months | 19.48 | -1.7 |
Maximum of Months | 19.70 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | -1.7 |
February | 19.64 | 2.70 |
March | 19.78 | 6.07 |
April | 19.64 | 11.58 |
May | 19.60 | 14.61 |
June | 19.68 | 19.78 |
July | 19.67 | 24.54 |
August | 19.75 | 21.22 |
September | 19.66 | 17.37 |
October | 19.68 | 11.70 |
November | 19.60 | 4.05 |
December | 19.56 | 1.86 |
Annual Sum or Average | 19.65 | 11.20 |
Minimum of Months | 19.54 | -1.7 |
Maximum of Months | 19.78 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | -1.7 |
February | 19.68 | 2.70 |
March | 19.84 | 6.07 |
April | 19.71 | 11.58 |
May | 19.71 | 14.61 |
June | 19.75 | 19.78 |
July | 19.70 | 24.54 |
August | 19.77 | 21.22 |
September | 19.65 | 17.37 |
October | 19.66 | 11.70 |
November | 19.65 | 4.05 |
December | 19.61 | 1.86 |
Annual Sum or Average | 19.70 | 11.20 |
Minimum of Months | 19.61 | -1.7 |
Maximum of Months | 19.84 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY TOILET
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.56 | -1.7 |
February | 19.62 | 2.70 |
March | 19.74 | 6.07 |
April | 19.63 | 11.58 |
May | 19.63 | 14.61 |
June | 19.64 | 19.78 |
July | 19.53 | 24.54 |
August | 19.64 | 21.22 |
September | 19.57 | 17.37 |
October | 19.59 | 11.70 |
November | 19.60 | 4.05 |
December | 19.56 | 1.86 |
Annual Sum or Average | 19.61 | 11.20 |
Minimum of Months | 19.53 | -1.7 |
Maximum of Months | 19.74 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.71 | -1.7 |
February | 19.84 | 2.70 |
March | 20.05 | 6.07 |
April | 20.03 | 11.58 |
May | 20.05 | 14.61 |
June | 20.15 | 19.78 |
July | 20.10 | 24.54 |
August | 20.15 | 21.22 |
September | 19.97 | 17.37 |
October | 19.91 | 11.70 |
November | 19.82 | 4.05 |
December | 19.75 | 1.86 |
Annual Sum or Average | 19.96 | 11.20 |
Minimum of Months | 19.71 | -1.7 |
Maximum of Months | 20.15 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.11 | -1.7 |
February | 20.46 | 2.70 |
March | 20.88 | 6.07 |
April | 21.18 | 11.58 |
May | 21.34 | 14.61 |
June | 21.64 | 19.78 |
July | 21.75 | 24.54 |
August | 21.63 | 21.22 |
September | 21.26 | 17.37 |
October | 20.90 | 11.70 |
November | 20.48 | 4.05 |
December | 20.26 | 1.86 |
Annual Sum or Average | 21.00 | 11.20 |
Minimum of Months | 20.11 | -1.7 |
Maximum of Months | 21.75 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 TREATMENT
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.66 | -1.7 |
February | 19.77 | 2.70 |
March | 19.96 | 6.07 |
April | 19.82 | 11.58 |
May | 19.81 | 14.61 |
June | 19.83 | 19.78 |
July | 19.76 | 24.54 |
August | 19.85 | 21.22 |
September | 19.72 | 17.37 |
October | 19.76 | 11.70 |
November | 19.74 | 4.05 |
December | 19.69 | 1.86 |
Annual Sum or Average | 19.78 | 11.20 |
Minimum of Months | 19.66 | -1.7 |
Maximum of Months | 19.96 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 1
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.02 | -1.7 |
February | 20.51 | 2.70 |
March | 20.88 | 6.07 |
April | 21.33 | 11.58 |
May | 21.41 | 14.61 |
June | 21.71 | 19.78 |
July | 21.94 | 24.54 |
August | 21.84 | 21.22 |
September | 21.55 | 17.37 |
October | 21.08 | 11.70 |
November | 20.44 | 4.05 |
December | 20.19 | 1.86 |
Annual Sum or Average | 21.08 | 11.20 |
Minimum of Months | 20.02 | -1.7 |
Maximum of Months | 21.94 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 2
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | -1.7 |
February | 20.42 | 2.70 |
March | 20.83 | 6.07 |
April | 21.38 | 11.58 |
May | 21.48 | 14.61 |
June | 21.88 | 19.78 |
July | 22.20 | 24.54 |
August | 22.03 | 21.22 |
September | 21.70 | 17.37 |
October | 21.11 | 11.70 |
November | 20.37 | 4.05 |
December | 20.10 | 1.86 |
Annual Sum or Average | 21.12 | 11.20 |
Minimum of Months | 19.92 | -1.7 |
Maximum of Months | 22.20 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UTILITY
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.00 | -1.7 |
February | 20.30 | 2.70 |
March | 20.68 | 6.07 |
April | 20.94 | 11.58 |
May | 21.08 | 14.61 |
June | 21.34 | 19.78 |
July | 21.44 | 24.54 |
August | 21.37 | 21.22 |
September | 21.03 | 17.37 |
October | 20.71 | 11.70 |
November | 20.31 | 4.05 |
December | 20.13 | 1.86 |
Annual Sum or Average | 20.78 | 11.20 |
Minimum of Months | 20.00 | -1.7 |
Maximum of Months | 21.44 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 WORK
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.66 | -1.7 |
February | 19.97 | 2.70 |
March | 20.45 | 6.07 |
April | 20.93 | 11.58 |
May | 21.07 | 14.61 |
June | 21.42 | 19.78 |
July | 21.68 | 24.54 |
August | 21.42 | 21.22 |
September | 21.04 | 17.37 |
October | 20.59 | 11.70 |
November | 19.94 | 4.05 |
December | 19.71 | 1.86 |
Annual Sum or Average | 20.66 | 11.20 |
Minimum of Months | 19.66 | -1.7 |
Maximum of Months | 21.68 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: NE STAIR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | -1.7 |
February | 19.54 | 2.70 |
March | 19.76 | 6.07 |
April | 20.20 | 11.58 |
May | 20.52 | 14.61 |
June | 21.29 | 19.78 |
July | 21.81 | 24.54 |
August | 21.24 | 21.22 |
September | 20.57 | 17.37 |
October | 19.90 | 11.70 |
November | 19.55 | 4.05 |
December | 19.48 | 1.86 |
Annual Sum or Average | 20.28 | 11.20 |
Minimum of Months | 19.48 | -1.7 |
Maximum of Months | 21.81 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: NW ELEVATOR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | -1.7 |
February | 19.87 | 2.70 |
March | 20.25 | 6.07 |
April | 20.65 | 11.58 |
May | 20.90 | 14.61 |
June | 21.50 | 19.78 |
July | 21.83 | 24.54 |
August | 21.65 | 21.22 |
September | 21.10 | 17.37 |
October | 20.44 | 11.70 |
November | 19.86 | 4.05 |
December | 19.68 | 1.86 |
Annual Sum or Average | 20.62 | 11.20 |
Minimum of Months | 19.64 | -1.7 |
Maximum of Months | 21.83 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: NW STAIR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | -1.7 |
February | 19.56 | 2.70 |
March | 19.81 | 6.07 |
April | 20.29 | 11.58 |
May | 20.71 | 14.61 |
June | 21.56 | 19.78 |
July | 22.05 | 24.54 |
August | 21.50 | 21.22 |
September | 20.69 | 17.37 |
October | 19.93 | 11.70 |
November | 19.56 | 4.05 |
December | 19.49 | 1.86 |
Annual Sum or Average | 20.39 | 11.20 |
Minimum of Months | 19.49 | -1.7 |
Maximum of Months | 22.05 | 24.54 |
Report: MONTHLY INDOOR TEMP
For: SW STAIR
Timestamp: 2015-09-13 14:21:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.72 | -1.7 |
February | 20.08 | 2.70 |
March | 20.43 | 6.07 |
April | 20.91 | 11.58 |
May | 21.06 | 14.61 |
June | 21.62 | 19.78 |
July | 22.04 | 24.54 |
August | 21.87 | 21.22 |
September | 21.49 | 17.37 |
October | 20.81 | 11.70 |
November | 20.05 | 4.05 |
December | 19.83 | 1.86 |
Annual Sum or Average | 20.83 | 11.20 |
Minimum of Months | 19.72 | -1.7 |
Maximum of Months | 22.04 | 24.54 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-1
Timestamp: 2015-09-13 14:21:42
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.145920E+12 | 0.436229E+11 |
February | 0.119803E+12 | 0.646859E+11 |
March | 0.135382E+12 | 0.979548E+11 |
April | 0.109220E+12 | 0.133726E+12 |
May | 0.100798E+12 | 0.161169E+12 |
June | 0.878089E+11 | 0.191386E+12 |
July | 0.766760E+11 | 0.225933E+12 |
August | 0.852317E+11 | 0.205174E+12 |
September | 0.929483E+11 | 0.173797E+12 |
October | 0.122897E+12 | 0.137626E+12 |
November | 0.126584E+12 | 0.798617E+11 |
December | 0.138560E+12 | 0.647455E+11 |
Annual Sum or Average | 0.134183E+13 | 0.157968E+13 |
Minimum of Months | 0.766760E+11 | 0.436229E+11 |
Maximum of Months | 0.145920E+12 | 0.225933E+12 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-2
Timestamp: 2015-09-13 14:21:42
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.143248E+12 | 0.000 |
February | 0.876053E+11 | 0.100947E+09 |
March | 0.786676E+11 | 0.598337E+10 |
April | 0.541295E+11 | 0.481986E+11 |
May | 0.488169E+11 | 0.764900E+11 |
June | 0.470124E+11 | 0.165307E+12 |
July | 0.485416E+11 | 0.226434E+12 |
August | 0.484957E+11 | 0.186262E+12 |
September | 0.463049E+11 | 0.114995E+12 |
October | 0.565713E+11 | 0.385679E+11 |
November | 0.867414E+11 | 0.421725E+10 |
December | 0.114232E+12 | 0.000 |
Annual Sum or Average | 0.860366E+12 | 0.866556E+12 |
Minimum of Months | 0.463049E+11 | 0.000 |
Maximum of Months | 0.143248E+12 | 0.226434E+12 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2015-09-13 14:21:42
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.180936E+12 | 0.166849E+12 |
February | 0.155552E+12 | 0.992087E+11 |
March | 0.183388E+12 | 0.853482E+11 |
April | 0.170073E+12 | 0.620065E+11 |
May | 0.175634E+12 | 0.561666E+11 |
June | 0.200911E+12 | 0.492688E+11 |
July | 0.217645E+12 | 0.557033E+11 |
August | 0.210721E+12 | 0.494799E+11 |
September | 0.185976E+12 | 0.473774E+11 |
October | 0.186997E+12 | 0.590416E+11 |
November | 0.168628E+12 | 0.966924E+11 |
December | 0.179126E+12 | 0.129066E+12 |
Annual Sum or Average | 0.221559E+13 | 0.956209E+12 |
Minimum of Months | 0.155552E+12 | 0.473774E+11 |
Maximum of Months | 0.217645E+12 | 0.166849E+12 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-13 14:21:42
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.399078E+12 | 275839.226 | 13-JAN-08:09 | 36851.394 | 99795.995 | 17803.267 | 91925.459 | 0.000 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.352383E+12 | 235153.158 | 01-FEB-17:49 | 36851.394 | 111837.204 | 24694.161 | 22125.493 | 14683.118 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.408844E+12 | 269833.117 | 31-MAR-15:30 | 36851.394 | 111837.204 | 31424.985 | 19467.141 | 56017.685 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.377713E+12 | 276245.149 | 13-APR-16:19 | 36851.394 | 111837.204 | 34749.845 | 18397.773 | 67430.001 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.393624E+12 | 292950.176 | 04-MAY-16:49 | 36851.394 | 111837.204 | 36671.308 | 19933.621 | 86442.851 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.414895E+12 | 314201.320 | 23-JUN-16:00 | 36851.394 | 111837.204 | 44859.069 | 13331.859 | 103491.339 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.427128E+12 | 353016.062 | 21-JUL-16:10 | 36851.394 | 111837.204 | 46832.457 | 27349.222 | 111459.294 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.434235E+12 | 346607.712 | 08-AUG-16:40 | 36851.394 | 111837.204 | 46068.868 | 28600.684 | 107466.513 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.394374E+12 | 297061.103 | 08-SEP-16:00 | 36851.394 | 111837.204 | 37461.820 | 19972.903 | 85206.495 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.403511E+12 | 281137.568 | 02-OCT-16:19 | 36851.394 | 111837.204 | 31590.621 | 19671.710 | 71190.780 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.381277E+12 | 249348.120 | 01-NOV-12:00 | 36851.394 | 111837.204 | 23466.038 | 28471.686 | 33492.507 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.394304E+12 | 238826.205 | 22-DEC-17:10 | 36851.394 | 111837.204 | 26019.585 | 21519.969 | 11020.123 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.478137E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.352383E+12 | 235153.158 | 36851.394 | 99795.995 | 17803.267 | 13331.859 | 0.000 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.434235E+12 | 353016.062 | 36851.394 | 111837.204 | 46832.457 | 91925.459 | 111459.294 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2015-09-13 14:21:42
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [J] | GAS:BUILDING {Maximum}[W] | GAS:BUILDING {TIMESTAMP} | |
January | 0.202389E+12 | 148688.60 | 02-JAN-09:09 | 0.158619E+11 | 9905.77 | 02-JAN-06:10 |
February | 0.183577E+12 | 148688.60 | 01-FEB-09:09 | 0.143713E+11 | 9905.77 | 01-FEB-06:10 |
March | 0.212124E+12 | 148688.60 | 01-MAR-09:09 | 0.163897E+11 | 9905.77 | 01-MAR-06:10 |
April | 0.196088E+12 | 148688.60 | 03-APR-08:09 | 0.153698E+11 | 9905.77 | 03-APR-05:10 |
May | 0.207257E+12 | 148688.60 | 01-MAY-08:09 | 0.161258E+11 | 9905.77 | 01-MAY-05:10 |
June | 0.204231E+12 | 148688.60 | 01-JUN-08:09 | 0.158049E+11 | 9905.77 | 01-JUN-05:10 |
July | 0.199114E+12 | 148688.60 | 03-JUL-08:09 | 0.156907E+11 | 9905.77 | 03-JUL-05:10 |
August | 0.212124E+12 | 148688.60 | 01-AUG-08:09 | 0.163897E+11 | 9905.77 | 01-AUG-05:10 |
September | 0.196088E+12 | 148688.60 | 01-SEP-08:09 | 0.153698E+11 | 9905.77 | 01-SEP-05:10 |
October | 0.202389E+12 | 148688.60 | 02-OCT-08:09 | 0.158619E+11 | 9905.77 | 02-OCT-05:10 |
November | 0.197772E+12 | 148688.60 | 01-NOV-08:09 | 0.154482E+11 | 9905.77 | 01-NOV-05:10 |
December | 0.199114E+12 | 148688.60 | 01-DEC-09:09 | 0.156907E+11 | 9905.77 | 01-DEC-06:10 |
Annual Sum or Average | 0.241227E+13 | 0.188374E+12 | ||||
Minimum of Months | 0.183577E+12 | 148688.60 | 0.143713E+11 | 9905.77 | ||
Maximum of Months | 0.212124E+12 | 148688.60 | 0.163897E+11 | 9905.77 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2015-09-13 14:21:42
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.465507E+11 | 0.00 | 0.138790E+11 | 0.155839E+12 | 0.00 | 0.444958E+11 | 0.187342E+10 | 0.820780E+11 | 0.122545E+11 | 0.00 | 0.421075E+11 | 0.00 | 0.00 | 0.00 |
February | 0.423275E+11 | 0.00 | 0.115625E+11 | 0.141249E+12 | 0.00 | 0.413387E+11 | 0.169231E+10 | 0.612639E+11 | 0.176732E+11 | 0.00 | 0.352761E+11 | 0.00 | 0.00 | 0.00 |
March | 0.500442E+11 | 0.00 | 0.114570E+11 | 0.162080E+12 | 0.00 | 0.483493E+11 | 0.187430E+10 | 0.620121E+11 | 0.277847E+11 | 0.00 | 0.452423E+11 | 0.00 | 0.00 | 0.00 |
April | 0.451430E+11 | 0.00 | 0.973845E+10 | 0.150945E+12 | 0.00 | 0.463014E+11 | 0.181334E+10 | 0.481813E+11 | 0.476180E+11 | 0.00 | 0.279728E+11 | 0.00 | 0.00 | 0.00 |
May | 0.482974E+11 | 0.00 | 0.885908E+10 | 0.158960E+12 | 0.00 | 0.486297E+11 | 0.187386E+10 | 0.449160E+11 | 0.622229E+11 | 0.00 | 0.198651E+11 | 0.00 | 0.00 | 0.00 |
June | 0.480542E+11 | 0.00 | 0.793950E+10 | 0.156177E+12 | 0.00 | 0.496110E+11 | 0.181336E+10 | 0.375070E+11 | 0.967933E+11 | 0.00 | 0.170000E+11 | 0.00 | 0.00 | 0.00 |
July | 0.453862E+11 | 0.00 | 0.849728E+10 | 0.153727E+12 | 0.00 | 0.507627E+11 | 0.187218E+10 | 0.310878E+11 | 0.127488E+12 | 0.00 | 0.830622E+10 | 0.00 | 0.00 | 0.00 |
August | 0.500442E+11 | 0.00 | 0.951735E+10 | 0.162080E+12 | 0.00 | 0.518764E+11 | 0.187180E+10 | 0.371307E+11 | 0.107518E+12 | 0.00 | 0.141958E+11 | 0.00 | 0.00 | 0.00 |
September | 0.451430E+11 | 0.00 | 0.104972E+11 | 0.150945E+12 | 0.00 | 0.472310E+11 | 0.181334E+10 | 0.432264E+11 | 0.763302E+11 | 0.00 | 0.191884E+11 | 0.00 | 0.00 | 0.00 |
October | 0.465507E+11 | 0.00 | 0.122510E+11 | 0.155839E+12 | 0.00 | 0.478562E+11 | 0.187342E+10 | 0.554307E+11 | 0.461847E+11 | 0.00 | 0.375258E+11 | 0.00 | 0.00 | 0.00 |
November | 0.457252E+11 | 0.00 | 0.130650E+11 | 0.152047E+12 | 0.00 | 0.444003E+11 | 0.181291E+10 | 0.645562E+11 | 0.225608E+11 | 0.00 | 0.371103E+11 | 0.00 | 0.00 | 0.00 |
December | 0.453862E+11 | 0.00 | 0.141906E+11 | 0.153727E+12 | 0.00 | 0.449608E+11 | 0.187342E+10 | 0.735469E+11 | 0.179474E+11 | 0.00 | 0.426710E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558652E+12 | 0.00 | 0.131454E+12 | 0.185361E+13 | 0.00 | 0.565813E+12 | 0.220577E+11 | 0.640937E+12 | 0.662376E+12 | 0.00 | 0.346461E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.423275E+11 | 0.00 | 0.793950E+10 | 0.141249E+12 | 0.00 | 0.413387E+11 | 0.169231E+10 | 0.310878E+11 | 0.122545E+11 | 0.00 | 0.830622E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.500442E+11 | 0.00 | 0.141906E+11 | 0.162080E+12 | 0.00 | 0.518764E+11 | 0.187430E+10 | 0.820780E+11 | 0.127488E+12 | 0.00 | 0.452423E+11 | 0.00 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2015-09-13 14:21:42
INTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.158619E+11 | 0.00 | 0.166849E+12 | 0.00 | 0.122298E+11 | 0.00 |
February | 0.143713E+11 | 0.00 | 0.992087E+11 | 0.00 | 0.112433E+11 | 0.00 |
March | 0.163897E+11 | 0.00 | 0.853482E+11 | 0.00 | 0.130053E+11 | 0.00 |
April | 0.153698E+11 | 0.00 | 0.620065E+11 | 0.00 | 0.113301E+11 | 0.00 |
May | 0.161258E+11 | 0.00 | 0.561666E+11 | 0.00 | 0.113927E+11 | 0.00 |
June | 0.158049E+11 | 0.00 | 0.492688E+11 | 0.00 | 0.106101E+11 | 0.00 |
July | 0.156907E+11 | 0.00 | 0.557033E+11 | 0.00 | 0.959859E+10 | 0.00 |
August | 0.163897E+11 | 0.00 | 0.494799E+11 | 0.00 | 0.103740E+11 | 0.00 |
September | 0.153698E+11 | 0.00 | 0.473774E+11 | 0.00 | 0.964616E+10 | 0.00 |
October | 0.158619E+11 | 0.00 | 0.590416E+11 | 0.00 | 0.104592E+11 | 0.00 |
November | 0.154482E+11 | 0.00 | 0.966924E+11 | 0.00 | 0.109197E+11 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.129066E+12 | 0.00 | 0.115102E+11 | 0.00 |
Annual Sum or Average | 0.188374E+12 | 0.00 | 0.956209E+12 | 0.00 | 0.132319E+12 | 0.00 |
Minimum of Months | 0.143713E+11 | 0.00 | 0.473774E+11 | 0.00 | 0.959859E+10 | 0.00 |
Maximum of Months | 0.163897E+11 | 0.00 | 0.166849E+12 | 0.00 | 0.130053E+11 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY
For: Meter
Timestamp: 2015-09-13 14:21:42
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36851.39 | 02-JAN-07:10 | 0.00 | 8375.00 | 01-JAN-00:10 | 111837.20 | 02-JAN-09:09 | 0.00 | 29992.58 | 26-JAN-15:50 | 700.43 | 01-JAN-08:09 | 141142.43 | 14-JAN-06:10 |
February | 36851.39 | 01-FEB-07:10 | 0.00 | 8375.00 | 01-FEB-00:10 | 111837.20 | 01-FEB-09:09 | 0.00 | 32149.45 | 09-FEB-15:30 | 700.43 | 01-FEB-00:10 | 114984.87 | 27-FEB-05:10 |
March | 36851.39 | 01-MAR-07:10 | 0.00 | 8375.00 | 01-MAR-00:10 | 111837.20 | 01-MAR-09:09 | 0.00 | 34661.67 | 29-MAR-15:50 | 700.43 | 01-MAR-00:10 | 112189.94 | 06-MAR-05:10 |
April | 36851.39 | 03-APR-06:10 | 0.00 | 8375.00 | 01-APR-00:10 | 111837.20 | 03-APR-08:09 | 0.00 | 35704.25 | 25-APR-15:50 | 700.43 | 01-APR-00:10 | 100846.53 | 10-APR-04:10 |
May | 36851.39 | 01-MAY-06:10 | 0.00 | 8375.00 | 01-MAY-00:10 | 111837.20 | 01-MAY-08:09 | 0.00 | 36671.31 | 04-MAY-16:49 | 700.43 | 01-MAY-00:10 | 97818.89 | 30-MAY-04:10 |
June | 36851.39 | 01-JUN-06:10 | 0.00 | 8375.00 | 01-JUN-00:10 | 111837.20 | 01-JUN-08:09 | 0.00 | 44859.07 | 23-JUN-16:00 | 700.43 | 01-JUN-00:10 | 81108.01 | 05-JUN-04:10 |
July | 36851.39 | 03-JUL-06:10 | 0.00 | 8375.00 | 01-JUL-00:10 | 111837.20 | 03-JUL-08:09 | 0.00 | 46848.10 | 21-JUL-16:00 | 700.43 | 01-JUL-00:10 | 75412.00 | 05-JUL-04:10 |
August | 36851.39 | 01-AUG-06:10 | 0.00 | 8375.00 | 01-AUG-00:10 | 111837.20 | 01-AUG-08:09 | 0.00 | 46106.74 | 08-AUG-16:19 | 700.43 | 01-AUG-00:10 | 80930.66 | 28-AUG-04:10 |
September | 36851.39 | 01-SEP-06:10 | 0.00 | 8375.00 | 01-SEP-00:10 | 111837.20 | 01-SEP-08:09 | 0.00 | 37804.26 | 08-SEP-16:30 | 700.43 | 01-SEP-00:10 | 83320.01 | 11-SEP-04:10 |
October | 36851.39 | 02-OCT-06:10 | 0.00 | 8375.00 | 01-OCT-00:10 | 111837.20 | 02-OCT-08:09 | 0.00 | 35069.09 | 05-OCT-15:30 | 700.43 | 01-OCT-07:10 | 104860.97 | 10-OCT-04:10 |
November | 36851.39 | 01-NOV-06:10 | 0.00 | 8375.00 | 01-NOV-00:10 | 111837.20 | 01-NOV-08:09 | 0.00 | 32286.70 | 02-NOV-15:30 | 700.43 | 01-NOV-00:10 | 117678.27 | 27-NOV-05:10 |
December | 36851.39 | 01-DEC-07:10 | 0.00 | 8375.00 | 01-DEC-00:10 | 111837.20 | 01-DEC-09:09 | 0.00 | 30618.99 | 08-DEC-15:30 | 700.43 | 01-DEC-00:10 | 116315.13 | 11-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 36851.39 | 0.00 | 8375.00 | 111837.20 | 0.00 | 29992.58 | 700.43 | 75412.00 | ||||||
Maximum of Months | 36851.39 | 0.00 | 8375.00 | 111837.20 | 0.00 | 46848.10 | 700.43 | 141142.43 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-13 14:21:42
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.399078E+12 | 275839.226 | 13-JAN-08:09 | 36851.394 | 99795.995 | 17803.267 | 91925.459 | 0.000 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.352383E+12 | 235153.158 | 01-FEB-17:49 | 36851.394 | 111837.204 | 24694.161 | 22125.493 | 14683.118 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.408844E+12 | 269833.117 | 31-MAR-15:30 | 36851.394 | 111837.204 | 31424.985 | 19467.141 | 56017.685 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.377713E+12 | 276245.149 | 13-APR-16:19 | 36851.394 | 111837.204 | 34749.845 | 18397.773 | 67430.001 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.393624E+12 | 292950.176 | 04-MAY-16:49 | 36851.394 | 111837.204 | 36671.308 | 19933.621 | 86442.851 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.414895E+12 | 314201.320 | 23-JUN-16:00 | 36851.394 | 111837.204 | 44859.069 | 13331.859 | 103491.339 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.427128E+12 | 353016.062 | 21-JUL-16:10 | 36851.394 | 111837.204 | 46832.457 | 27349.222 | 111459.294 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.434235E+12 | 346607.712 | 08-AUG-16:40 | 36851.394 | 111837.204 | 46068.868 | 28600.684 | 107466.513 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.394374E+12 | 297061.103 | 08-SEP-16:00 | 36851.394 | 111837.204 | 37461.820 | 19972.903 | 85206.495 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.403511E+12 | 281137.568 | 02-OCT-16:19 | 36851.394 | 111837.204 | 31590.621 | 19671.710 | 71190.780 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.381277E+12 | 249348.120 | 01-NOV-12:00 | 36851.394 | 111837.204 | 23466.038 | 28471.686 | 33492.507 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.394304E+12 | 238826.205 | 22-DEC-17:10 | 36851.394 | 111837.204 | 26019.585 | 21519.969 | 11020.123 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.478137E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.352383E+12 | 235153.158 | 36851.394 | 99795.995 | 17803.267 | 13331.859 | 0.000 | 0.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.434235E+12 | 353016.062 | 36851.394 | 111837.204 | 46832.457 | 91925.459 | 111459.294 | 8375.000 | 700.433 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-13 14:21:42
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.194941E+12 | 222557.026 | 13-JAN-08:00 | 0.000 | 9905.768 | 0.000 | 212651.258 | 16553.040 | 16553.040 | 196098.218 |
February | 0.124823E+12 | 199799.274 | 25-FEB-06:49 | 0.000 | 2971.730 | 0.000 | 196827.544 | 1488.000 | 1488.000 | 195339.544 |
March | 0.114743E+12 | 179088.698 | 27-MAR-06:00 | 0.000 | 9905.768 | 0.000 | 169182.930 | 1488.000 | 1488.000 | 167694.930 |
April | 0.887064E+11 | 168540.438 | 08-APR-05:49 | 0.000 | 2971.730 | 0.000 | 165568.707 | 1488.000 | 1488.000 | 164080.707 |
May | 0.836851E+11 | 128324.168 | 13-MAY-05:00 | 0.000 | 2971.730 | 0.000 | 125352.438 | 1488.000 | 1488.000 | 123864.438 |
June | 0.756837E+11 | 89041.677 | 03-JUN-05:40 | 0.000 | 2971.730 | 0.000 | 86069.947 | 1488.000 | 1488.000 | 84581.947 |
July | 0.809926E+11 | 56019.585 | 17-JUL-04:30 | 0.000 | 4952.884 | 0.000 | 51066.701 | 1488.000 | 1488.000 | 49578.701 |
August | 0.762436E+11 | 86653.365 | 17-AUG-05:30 | 0.000 | 9905.768 | 0.000 | 76747.597 | 1488.000 | 1488.000 | 75259.597 |
September | 0.723933E+11 | 93917.480 | 21-SEP-05:40 | 0.000 | 9905.768 | 0.000 | 84011.712 | 1488.000 | 1488.000 | 82523.712 |
October | 0.853627E+11 | 132609.662 | 24-OCT-05:40 | 0.000 | 9905.768 | 0.000 | 122703.894 | 1488.000 | 1488.000 | 121215.894 |
November | 0.123060E+12 | 195161.660 | 13-NOV-06:40 | 0.000 | 9905.768 | 0.000 | 185255.892 | 1488.000 | 1488.000 | 183767.892 |
December | 0.156267E+12 | 203805.884 | 11-DEC-06:40 | 0.000 | 9905.768 | 0.000 | 193900.116 | 1488.000 | 1488.000 | 192412.116 |
Annual Sum or Average | 0.127690E+13 | 0.000 | 0.000 | |||||||
Minimum of Months | 0.723933E+11 | 56019.585 | 0.000 | 2971.730 | 0.000 | 51066.701 | 1488.000 | 1488.000 | 49578.701 | |
Maximum of Months | 0.194941E+12 | 222557.026 | 0.000 | 9905.768 | 0.000 | 212651.258 | 16553.040 | 16553.040 | 196098.218 |