Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:22

Tabular Output Report in Format: HTML

Building: OutPatient HealthCare

Environment: RIYADH - SAU IWEC Data WMO#=404380

Simulation Timestamp: 2015-09-13 14:22:44


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 6730.51 1769.32 1769.32
Net Site Energy 6730.51 1769.32 1769.32
Total Source Energy 22071.31 5802.12 5802.12
Net Source Energy 22071.31 5802.12 5802.12


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.546
Natural Gas 1.092
District Cooling 1.182
District Heating 3.640
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.158
Fuel Oil #2 1.050
Propane 1.151
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3804.01
Net Conditioned Building Area 3804.01
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 703.73 450.69 0.00 0.00 0.00 0.00
Cooling 1794.41 0.00 0.00 0.00 0.00 0.00
Interior Lighting 558.65 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 131.76 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1853.61 188.37 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 634.24 0.00 0.00 0.00 0.00 0.00
Pumps 10.32 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 312.29 0.00 0.00 0.00 0.00 116.17
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 92.42 0.00 0.00 0.00 478.84
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 5999.02 731.49 0.00 0.00 0.00 595.01
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 450.69 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 703.73 0.00 0.00 0.00 0.00 0.00
Cooling General 1794.41 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 558.65 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 131.76 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 1853.61 188.37 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Fan Energy 593.39 0.00 0.00 0.00 0.00 0.00
  Zone Exhaust Fans 40.85 0.00 0.00 0.00 0.00 0.00
Pumps General 10.32 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 312.29 0.00 0.00 0.00 0.00 116.17
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 92.42 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 478.84
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 181.50 0.00 0.00 0.00 0.00 0.00
HVAC 908.25 142.77 0.00 0.00 0.00 0.16
Other 487.28 49.52 0.00 0.00 0.00 0.00
Total 1577.03 192.29 0.00 0.00 0.00 0.16


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 181.50 0.00 0.00 0.00 0.00 0.00
HVAC 908.25 142.77 0.00 0.00 0.00 0.16
Other 487.28 49.52 0.00 0.00 0.00 0.00
Total 1577.03 192.29 0.00 0.00 0.00 0.16


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 5999.02 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 5999.02 100.00
     
Total On-Site and Utility Electric Sources 5999.02 100.00
Total Electricity End Uses 5999.02 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 595.01 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 595.01 100.00
Total Water End Uses 595.01 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 14.17
Time Setpoint Not Met During Occupied Cooling 2203.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 6816.33


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

OVERALL HVAC AIR SYSTEM LOADS

| AHU-1 | AHU-2 |

OVERALL HVAC SYSTEM ENERGY

| Meter |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS

| Meter |

BUILDING ENERGY PERFORMANCE - ELECTRICITY

| Meter |

BUILDING ENERGY PERFORMANCE - NATURAL GAS

| Meter |

PEAK ENERGY END-USE - ELECTRICITY

| Meter |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:22
RunPeriod RIYADH - SAU IWEC Data WMO#=404380
Weather File RIYADH - SAU IWEC Data WMO#=404380
Latitude [deg] 24.70
Longitude [deg] 46.80
Elevation [m] 612.00
Time Zone 3.00
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 308.29 97.22 57.97 114.08 39.02
Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 308.29 97.22 57.97 114.08 39.02
Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1373.29
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
FLOOR 1 ANESTHESIA 10.03 Yes Yes 30.58 1.00 8.36 2.23 14.7559 4.64 21.5300
FLOOR 1 BIO HAZ 5.20 Yes Yes 15.86 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 CAFE 39.02 Yes Yes 118.93 1.00 18.58 8.92 8.8535 0.93 10.7600
FLOOR 1 CLEAN 11.71 Yes Yes 35.68 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 CLEAN WORK 15.33 Yes Yes 46.72 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 DICTATION 11.71 Yes Yes 35.68 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 DRESSING ROOM 4.18 Yes Yes 12.74 1.00 8.36 2.32 10.8210 18.58 11.8400
FLOOR 1 ELECTRICAL ROOM 9.10 Yes Yes 27.75 1.00 6.50 0.00 14.7559   53.8200
FLOOR 1 ELEVATOR PUMP ROOM 8.45 Yes Yes 25.77 1.00 18.58 0.00 14.7559   5754.6154
FLOOR 1 HUMID 5.02 Yes Yes 15.29 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 IT HALL 13.01 Yes Yes 39.64 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 IT ROOM 10.41 Yes Yes 31.71 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 LOBBY 57.79 Yes Yes 176.13 1.00 20.44 8.92 12.7884 9.29 11.8400
FLOOR 1 LOBBY HALL 22.30 Yes Yes 67.96 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 LOBBY TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 1 LOCKER ROOM 61.32 Yes Yes 186.89 1.00 20.44 5.57 7.8698 6.19 32.2900
FLOOR 1 LOCKER ROOM HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 LOUNGE 33.45 Yes Yes 101.94 1.00 0.00 0.00 7.8698 6.19 32.2900
FLOOR 1 MED GAS 5.20 Yes Yes 15.86 1.00 13.94 0.00 8.8535   1.0800
FLOOR 1 MRI CONTROL ROOM 15.61 Yes Yes 47.57 1.00 4.65 0.00 3.9349 4.64 107.6400
FLOOR 1 MRI HALL 13.66 Yes Yes 41.63 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 MRI ROOM 40.88 Yes Yes 124.59 1.00 0.00 0.00 3.9349 4.64 107.6400
FLOOR 1 MRI TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 1 NOURISHMENT 16.91 Yes Yes 51.54 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 1 NURSE HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 NURSE JANITOR 5.02 Yes Yes 15.29 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 NURSE STATION 24.25 Yes Yes 73.91 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 1 NURSE TOILET 5.02 Yes Yes 15.29 1.00 0.00 0.00 8.8535   4.3100
FLOOR 1 OFFICE 44.87 Yes Yes 136.77 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 OPERATING ROOM 1 42.74 Yes Yes 130.26 1.00 39.95 8.92 21.6419 4.64 118.3600
FLOOR 1 OPERATING ROOM 2 44.59 Yes Yes 135.92 1.00 22.30 6.69 21.6419 4.64 118.3600
FLOOR 1 OPERATING ROOM 3 44.22 Yes Yes 134.79 1.00 0.00 0.00 21.6419 4.64 118.3600
FLOOR 1 PACU 10.03 Yes Yes 30.58 1.00 0.00 0.00 7.8698 4.64 32.2900
FLOOR 1 PRE-OP HALL 49.05 Yes Yes 149.51 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 PRE-OP ROOM 1 17.56 Yes Yes 53.52 1.00 3.72 0.00 6.8861 9.29 21.5300
FLOOR 1 PRE-OP ROOM 2 31.40 Yes Yes 95.71 1.00 0.00 0.00 6.8861 9.29 21.5300
FLOOR 1 PRE-OP TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 1 PROCEDURE ROOM 26.48 Yes Yes 80.70 1.00 17.65 5.57 26.5606 4.64 32.2900
FLOOR 1 RECEPTION 47.29 Yes Yes 144.13 1.00 12.08 3.34 12.7884 3.10 11.8400
FLOOR 1 RECEPTION HALL 11.89 Yes Yes 36.25 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 RECOVERY ROOM 50.17 Yes Yes 152.91 1.00 41.81 8.92 7.8698 4.64 32.2900
FLOOR 1 SCHEDULING 11.06 Yes Yes 33.70 1.00 6.50 0.74 10.8210 18.58 11.8400
FLOOR 1 SCRUB 7.80 Yes Yes 23.79 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 SOIL 11.71 Yes Yes 35.68 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 SOIL HOLD 5.20 Yes Yes 15.86 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 SOIL WORK 16.72 Yes Yes 50.97 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 STEP DOWN 27.87 Yes Yes 84.95 1.00 34.37 6.69 7.8698 4.64 32.2900
FLOOR 1 STERILE HALL 57.23 Yes Yes 174.43 1.00 7.43 2.23 9.8372   4.3100
FLOOR 1 STERILE STORAGE 36.79 Yes Yes 112.13 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 STORAGE 85.47 Yes Yes 260.51 1.00 58.53 8.36 8.8535   1.0800
FLOOR 1 SUB-STERILE 18.21 Yes Yes 55.50 1.00 13.01 2.97 9.8372   4.3100
FLOOR 1 UTILITY HALL 23.78 Yes Yes 72.49 1.00 14.86 0.00 9.8372   4.3100
FLOOR 1 UTILITY JANITOR 3.90 Yes Yes 11.89 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 UTILITY ROOM 33.45 Yes Yes 101.94 1.00 16.72 2.23 8.8535   1.0800
FLOOR 1 VESTIBULE 6.69 Yes Yes 20.39 1.00 7.43 0.00 9.8372   4.3100
FLOOR 2 CONFERENCE 31.22 Yes Yes 95.14 1.00 37.16 8.92 12.7884 1.86 10.7600
FLOOR 2 CONFERENCE TOILET 5.95 Yes Yes 18.12 1.00 0.00 0.00 8.8535   4.3100
FLOOR 2 DICTATION 6.50 Yes Yes 19.82 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 2 EXAM 1 33.45 Yes Yes 101.94 1.00 39.02 8.92 14.7559 4.64 11.8400
FLOOR 2 EXAM 2 50.17 Yes Yes 152.91 1.00 16.72 3.72 14.7559 4.64 11.8400
FLOOR 2 EXAM 3 66.89 Yes Yes 203.88 1.00 22.30 5.95 14.7559 4.64 11.8400
FLOOR 2 EXAM 4 7.80 Yes Yes 23.79 1.00 6.50 2.23 14.7559 4.64 11.8400
FLOOR 2 EXAM 5 32.52 Yes Yes 99.11 1.00 23.23 5.95 14.7559 4.64 11.8400
FLOOR 2 EXAM 6 20.90 Yes Yes 63.71 1.00 13.94 4.18 14.7559 4.64 11.8400
FLOOR 2 EXAM 7 73.58 Yes Yes 224.27 1.00 22.30 5.57 14.7559 4.64 11.8400
FLOOR 2 EXAM 8 25.08 Yes Yes 76.46 1.00 16.72 5.57 14.7559 4.64 11.8400
FLOOR 2 EXAM 9 36.79 Yes Yes 112.13 1.00 11.15 2.79 14.7559 4.64 11.8400
FLOOR 2 EXAM HALL 1 16.72 Yes Yes 50.97 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 2 16.72 Yes Yes 50.97 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 3 16.72 Yes Yes 50.97 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 4 18.39 Yes Yes 56.07 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 5 18.39 Yes Yes 56.07 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 6 18.39 Yes Yes 56.07 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 8.8535   1.0800
FLOOR 2 LOUNGE 7.43 Yes Yes 22.65 1.00 0.00 0.00 7.8698 6.19 32.2900
FLOOR 2 NURSE STATION 1 13.94 Yes Yes 42.48 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 2 NURSE STATION 2 16.72 Yes Yes 50.97 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 2 OFFICE 52.03 Yes Yes 158.57 1.00 37.16 8.92 10.8210 18.58 11.8400
FLOOR 2 OFFICE HALL 41.25 Yes Yes 125.73 1.00 0.00 0.00 9.8372   4.3100
FLOOR 2 RECEPTION 91.42 Yes Yes 278.64 1.00 45.52 16.72 12.7884 3.10 11.8400
FLOOR 2 RECEPTION HALL 52.40 Yes Yes 159.71 1.00 6.50 0.00 9.8372   4.3100
FLOOR 2 RECEPTION TOILET 11.71 Yes Yes 35.68 1.00 0.00 0.00 8.8535   4.3100
FLOOR 2 SCHEDULING 1 30.10 Yes Yes 91.75 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 2 SCHEDULING 2 31.77 Yes Yes 96.84 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 2 STORAGE 1 5.20 Yes Yes 15.86 1.00 0.00 0.00 8.8535   1.0800
FLOOR 2 STORAGE 2 11.15 Yes Yes 33.98 1.00 0.00 0.00 8.8535   1.0800
FLOOR 2 STORAGE 3 13.38 Yes Yes 40.78 1.00 0.00 0.00 8.8535   1.0800
FLOOR 2 UTILITY 11.71 Yes Yes 35.68 1.00 8.36 2.23 8.8535   1.0800
FLOOR 2 WORK 157.01 Yes Yes 478.55 1.00 24.15 5.57 10.8210 18.58 9.7803
FLOOR 2 WORK HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 WORK TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 2 X-RAY 83.61 Yes Yes 254.85 1.00 0.00 0.00 3.9349 4.64 107.6400
FLOOR 3 DRESSING ROOM 3.90 Yes Yes 11.89 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 3 ELEVATOR HALL 34.37 Yes Yes 104.77 1.00 3.72 0.00 9.8372   4.3100
FLOOR 3 HUMID 10.03 Yes Yes 30.58 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 3 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 8.8535   1.0800
FLOOR 3 LOCKER 11.15 Yes Yes 33.98 1.00 0.00 0.00 7.8698 6.19 32.2900
FLOOR 3 LOUNGE 70.51 Yes Yes 214.92 1.00 21.37 5.57 7.8698 6.19 32.2900
FLOOR 3 LOUNGE TOILET 17.84 Yes Yes 54.37 1.00 11.15 4.18 8.8535   4.3100
FLOOR 3 MECHANICAL 32.52 Yes Yes 99.11 1.00 23.23 5.95 14.7559   53.8200
FLOOR 3 MECHANICAL HALL 27.87 Yes Yes 84.95 1.00 0.00 0.00 9.8372   4.3100
FLOOR 3 OFFICE 282.05 Yes Yes 859.70 1.00 68.75 19.51 10.8210 18.58 11.8400
FLOOR 3 OFFICE HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 9.8372   4.3100
FLOOR 3 OFFICE TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 3 PHYSICAL THERAPY 1 120.77 Yes Yes 368.12 1.00 78.97 28.99 8.8535 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY 2 55.00 Yes Yes 167.64 1.00 0.00 0.00 8.8535 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 Yes Yes 23.79 1.00 0.00 0.00 8.8535   4.3100
FLOOR 3 STORAGE 1 10.03 Yes Yes 30.58 1.00 0.00 0.00 8.8535   1.0800
FLOOR 3 STORAGE 2 7.80 Yes Yes 23.79 1.00 0.00 0.00 8.8535   1.0800
FLOOR 3 TREATMENT 44.22 Yes Yes 134.79 1.00 0.00 0.00 14.7559 4.64 11.8400
FLOOR 3 UNDEVELOPED 1 210.70 Yes Yes 642.23 1.00 66.89 25.64 8.8535   11.8400
FLOOR 3 UNDEVELOPED 2 107.02 Yes Yes 326.21 1.00 52.03 13.38 8.8535   11.8400
FLOOR 3 UTILITY 20.07 Yes Yes 61.16 1.00 0.00 0.00 8.8535   1.0800
FLOOR 3 WORK 53.33 Yes Yes 162.54 1.00 38.09 8.92 10.8210 18.58 11.8400
NE STAIR 15.61 Yes Yes 142.72 1.00 97.55 12.02 9.8372   4.3100
NW ELEVATOR 13.01 Yes Yes 118.93 1.00 75.25 0.00 9.8372   4.3100
NW STAIR 17.84 Yes Yes 163.10 1.00 111.48 11.15 9.8372   4.3100
SW STAIR 8.92 Yes Yes 81.55 1.00 55.74 1.11 9.8372   4.3100
Total 3804.01     11932.15   1553.34 308.29 10.7639 9.08 32.0039
Conditioned Total 3804.01     11932.15   1553.34 308.29 10.7639 9.08 32.0039
Unconditioned Total 0.00     0.00   0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
RIYADH ANN HTG 99.6% CONDNS DB 5.90 0.00 5.90 Wetbulb [C] 1.60 320.00
RIYADH ANN CLG .4% CONDNS DB=>MWB 44.20 13.50 18.70 Wetbulb [C] 4.50 0.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
481E71 NONRES_EXT_WALL 0.30 0.704 0.787 8.36 180.00 90.00 S
FLOOR 1 ANESTHESIA SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 10.03 0.00 180.00  
FLOOR 1 BIO HAZ SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.20 0.00 180.00  
5F762C NONRES_EXT_WALL 0.30 0.704 0.787 18.58 180.00 90.00 S
FLOOR 1 CAFE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 39.02 90.00 180.00  
FLOOR 1 CLEAN SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.71 90.00 180.00  
FLOOR 1 CLEAN WORK SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.33 180.00 180.00  
FLOOR 1 DICTATION SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.71 0.00 180.00  
84FB73 NONRES_EXT_WALL 0.30 0.704 0.787 8.36 0.00 90.00 N
FLOOR 1 DRESSING ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 4.18 0.00 180.00  
7F5C82 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 90.00 90.00 E
FLOOR 1 ELECTRICAL ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 9.10 0.00 180.00  
C732B0 NONRES_EXT_WALL 0.30 0.704 0.787 12.08 0.00 90.00 N
E02487 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 270.00 90.00 W
FLOOR 1 ELEVATOR PUMP ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 8.45 180.00 180.00  
FLOOR 1 HUMID SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 0.00 180.00  
FLOOR 1 IT HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 13.01 180.00 180.00  
FLOOR 1 IT ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 10.41 90.00 180.00  
FE5A3C NONRES_EXT_WALL 0.30 0.704 0.787 20.44 270.00 90.00 W
FLOOR 1 LOBBY SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 57.79 90.00 180.00  
FLOOR 1 LOBBY HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 22.30 0.00 180.00  
9D87EC NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 1 LOBBY TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 0.00 180.00  
F629C1 NONRES_EXT_WALL 0.30 0.704 0.787 20.44 0.00 90.00 N
FLOOR 1 LOCKER ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 61.32 270.00 180.00  
FLOOR 1 LOCKER ROOM HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 46.08 180.00 180.00  
FLOOR 1 LOUNGE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 33.45 180.00 180.00  
E85BB5 NONRES_EXT_WALL 0.30 0.704 0.787 7.43 0.00 90.00 N
577FC1 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 90.00 90.00 E
FLOOR 1 MED GAS SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.20 180.00 180.00  
FLOOR 1 MED GAS ROOF NONRES_ROOF 0.30 0.351 0.376 5.20 180.00 0.00  
C114C1 NONRES_EXT_WALL 0.30 0.704 0.787 4.65 0.00 90.00 N
FLOOR 1 MRI CONTROL ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.61 180.00 180.00  
FLOOR 1 MRI HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 13.66 180.00 180.00  
FLOOR 1 MRI ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 40.88 90.00 180.00  
ADB8D0 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
FLOOR 1 MRI TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 90.00 180.00  
FLOOR 1 NOURISHMENT SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 16.91 270.00 180.00  
FLOOR 1 NURSE HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 46.08 270.00 180.00  
FLOOR 1 NURSE JANITOR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 180.00 180.00  
FLOOR 1 NURSE STATION SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 24.25 180.00 180.00  
FLOOR 1 NURSE TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 180.00 180.00  
FLOOR 1 OFFICE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 44.87 0.00 180.00  
879583 NONRES_EXT_WALL 0.30 0.704 0.787 18.58 180.00 90.00 S
E326E4 NONRES_EXT_WALL 0.30 0.704 0.787 21.37 90.00 90.00 E
FLOOR 1 OPERATING ROOM 1 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 42.74 0.00 180.00  
1D96D7 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 90.00 90.00 E
FLOOR 1 OPERATING ROOM 2 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 44.59 0.00 180.00  
FLOOR 1 OPERATING ROOM 3 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 44.22 0.00 180.00  
FLOOR 1 PACU SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 10.03 180.00 180.00  
FLOOR 1 PRE-OP HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 49.05 180.00 180.00  
84418A NONRES_EXT_WALL 0.30 0.704 0.787 3.72 270.00 90.00 W
FLOOR 1 PRE-OP ROOM 1 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 17.56 90.00 180.00  
FLOOR 1 PRE-OP ROOM 2 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 31.40 0.00 180.00  
1535AC NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 1 PRE-OP TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 270.00 180.00  
6D2616 NONRES_EXT_WALL 0.30 0.704 0.787 17.65 0.00 90.00 N
FLOOR 1 PROCEDURE ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 26.48 270.00 180.00  
A5A6A3 NONRES_EXT_WALL 0.30 0.704 0.787 12.08 180.00 90.00 S
FLOOR 1 RECEPTION SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 47.29 270.00 180.00  
FLOOR 1 RECEPTION HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.89 0.00 180.00  
28B002 NONRES_EXT_WALL 0.30 0.704 0.787 41.81 180.00 90.00 S
FLOOR 1 RECOVERY ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 50.17 90.00 180.00  
EA6DC8 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 180.00 90.00 S
FLOOR 1 SCHEDULING SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.06 90.00 180.00  
FLOOR 1 SCRUB SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 7.80 90.00 180.00  
FLOOR 1 SOIL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.71 90.00 180.00  
FLOOR 1 SOIL HOLD SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.20 0.00 180.00  
FLOOR 1 SOIL WORK SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 16.72 0.00 180.00  
B40F89 NONRES_EXT_WALL 0.30 0.704 0.787 11.15 270.00 90.00 W
997723 NONRES_EXT_WALL 0.30 0.704 0.787 23.23 180.00 90.00 S
FLOOR 1 STEP DOWN SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 27.87 270.00 180.00  
CEC7BD NONRES_EXT_WALL 0.30 0.704 0.787 7.43 180.00 90.00 S
FLOOR 1 STERILE HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 57.23 270.00 180.00  
FLOOR 1 NURSE STORAGE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 36.79 0.00 180.00  
8E5BB9 NONRES_EXT_WALL 0.30 0.704 0.787 21.37 270.00 90.00 W
859BC1 NONRES_EXT_WALL 0.30 0.704 0.787 37.16 0.00 90.00 N
FLOOR 1 STORAGE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 85.47 270.00 180.00  
FLOOR 1 STORGE ROOF NONRES_ROOF 0.30 0.351 0.376 85.47 270.00 0.00  
61E610 NONRES_EXT_WALL 0.30 0.704 0.787 13.01 90.00 90.00 E
FLOOR 1 SUB-STERILE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 18.21 180.00 180.00  
529072 NONRES_EXT_WALL 0.30 0.704 0.787 14.86 90.00 90.00 E
FLOOR 1 UTILITY HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 23.78 90.00 180.00  
FLOOR 1 UTILITY HALL ROOF NONRES_ROOF 0.30 0.351 0.376 11.89 180.00 0.00  
FLOOR 1 UTILITY JANITOR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 3.90 90.00 180.00  
D95F04 NONRES_EXT_WALL 0.30 0.704 0.787 16.72 90.00 90.00 E
FLOOR 1 UTILITY ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 33.45 180.00 180.00  
3330D8 NONRES_EXT_WALL 0.30 0.704 0.787 7.43 270.00 90.00 W
FLOOR 1 VESTIBULE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 6.69 90.00 180.00  
208CCF NONRES_EXT_WALL 0.30 0.704 0.787 11.15 90.00 90.00 E
AEF992 NONRES_EXT_WALL 0.30 0.704 0.787 26.01 180.00 90.00 S
54D065 NONRES_EXT_WALL 0.30 0.704 0.787 11.15 180.00 90.00 S
1775A6 NONRES_EXT_WALL 0.30 0.704 0.787 27.87 270.00 90.00 W
97F00A NONRES_EXT_WALL 0.30 0.704 0.787 16.72 180.00 90.00 S
A497E9 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 180.00 90.00 S
88A75F NONRES_EXT_WALL 0.30 0.704 0.787 6.50 180.00 90.00 S
B4E619 NONRES_EXT_WALL 0.30 0.704 0.787 23.23 90.00 90.00 E
9EC269 NONRES_EXT_WALL 0.30 0.704 0.787 13.94 0.00 90.00 N
B316F7 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 0.00 90.00 N
9621FD NONRES_EXT_WALL 0.30 0.704 0.787 16.72 0.00 90.00 N
42CEE1 NONRES_EXT_WALL 0.30 0.704 0.787 11.15 0.00 90.00 N
4979C8 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 180.00 90.00 S
8CA0BF NONRES_EXT_WALL 0.30 0.704 0.787 5.57 180.00 90.00 S
6C95E7 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 180.00 90.00 S
F209CC NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
155BD6 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
C5EA55 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
8177BA NONRES_EXT_WALL 0.30 0.704 0.787 6.50 270.00 90.00 W
5E657E NONRES_EXT_WALL 0.30 0.704 0.787 8.36 0.00 90.00 N
4B1439 NONRES_EXT_WALL 0.30 0.704 0.787 37.16 90.00 90.00 E
4ABC66 NONRES_EXT_WALL 0.30 0.704 0.787 30.66 180.00 90.00 S
5B04CF NONRES_EXT_WALL 0.30 0.704 0.787 14.86 270.00 90.00 W
8D1BC4 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 180.00 90.00 S
4B55FA NONRES_EXT_WALL 0.30 0.704 0.787 8.36 90.00 90.00 E
9C3A6A NONRES_EXT_WALL 0.30 0.704 0.787 20.44 0.00 90.00 N
C52EE0 NONRES_EXT_WALL 0.30 0.704 0.787 3.72 0.00 90.00 N
1C33AD NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
6CC177 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 3 DRESSING ROOM ROOF NONRES_ROOF 0.30 0.351 0.376 3.90 270.00 0.00  
F7D24D NONRES_EXT_WALL 0.30 0.704 0.787 3.72 0.00 90.00 N
FLOOR 3 ELEVATOR HALL ROOF NONRES_ROOF 0.30 0.351 0.376 34.37 0.00 0.00  
FLOOR 3 HUMID ROOF NONRES_ROOF 0.30 0.351 0.376 10.03 270.00 0.00  
FC22D1 NONRES_EXT_WALL 0.30 0.704 0.787 8.36 0.00 90.00 N
DD2E2D NONRES_EXT_WALL 0.30 0.704 0.787 6.50 270.00 90.00 W
FLOOR 3 JANITOR ROOF NONRES_ROOF 0.30 0.351 0.376 5.85 0.00 0.00  
FLOOR 3 LOCKER ROOF NONRES_ROOF 0.30 0.351 0.376 11.15 0.00 0.00  
68A2D7 NONRES_EXT_WALL 0.30 0.704 0.787 21.37 0.00 90.00 N
FLOOR 3 LOUNGE ROOF NONRES_ROOF 0.30 0.351 0.376 70.51 270.00 0.00  
CE3FEF NONRES_EXT_WALL 0.30 0.704 0.787 11.15 0.00 90.00 N
FLOOR 3 LOUNGE TOILET ROOF NONRES_ROOF 0.30 0.351 0.376 17.84 0.00 0.00  
CE618F NONRES_EXT_WALL 0.30 0.704 0.787 23.23 90.00 90.00 E
FLOOR 3 MECHANICAL ROOF NONRES_ROOF 0.30 0.351 0.376 32.52 0.00 0.00  
FLOOR 3 MECHANICAL HALL ROOF NONRES_ROOF 0.30 0.351 0.376 27.87 0.00 0.00  
5ADC59 NONRES_EXT_WALL 0.30 0.704 0.787 68.75 0.00 90.00 N
FLOOR 3 OFFICE ROOF NONRES_ROOF 0.30 0.351 0.376 282.05 180.00 0.00  
D4F411 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 3 OFFICE HALL ROOF NONRES_ROOF 0.30 0.351 0.376 77.48 270.00 0.00  
B35AD6 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 3 OFFICE TOILET ROOF NONRES_ROOF 0.30 0.351 0.376 5.02 270.00 0.00  
D22917 NONRES_EXT_WALL 0.30 0.704 0.787 18.58 90.00 90.00 E
C1BC97 NONRES_EXT_WALL 0.30 0.704 0.787 60.39 180.00 90.00 S
FLOOR 3 PHYICAL THERAPY 1 ROOF NONRES_ROOF 0.30 0.351 0.376 120.77 180.00 0.00  
FLOOR 3 PHYSICAL THERAPY 2 ROOF NONRES_ROOF 0.30 0.351 0.376 55.00 90.00 0.00  
FLOOR 3 PHYSICAL THERAPY TOILET ROOF NONRES_ROOF 0.30 0.351 0.376 7.80 90.00 0.00  
FLOOR 3 STORAGE 1 ROOF NONRES_ROOF 0.30 0.351 0.376 10.03 180.00 0.00  
FLOOR 3 STORAGE 2 ROOF NONRES_ROOF 0.30 0.351 0.376 7.80 180.00 0.00  
FLOOR 3 TREATMENT ROOF NONRES_ROOF 0.30 0.351 0.376 44.22 90.00 0.00  
8DA7DB NONRES_EXT_WALL 0.30 0.704 0.787 39.02 180.00 90.00 S
38B339 NONRES_EXT_WALL 0.30 0.704 0.787 27.87 270.00 90.00 W
FLOOR 3 UNDEVELOPED 1 ROOF NONRES_ROOF 0.30 0.351 0.376 210.70 0.00 0.00  
BE5F2F NONRES_EXT_WALL 0.30 0.704 0.787 14.86 270.00 90.00 W
1DEE26 NONRES_EXT_WALL 0.30 0.704 0.787 37.16 180.00 90.00 S
FLOOR 3 UNDEVELOPED 2 ROOF NONRES_ROOF 0.30 0.351 0.376 107.02 180.00 0.00  
FLOOR 3 UTILITY ROOF NONRES_ROOF 0.30 0.351 0.376 20.07 0.00 0.00  
C86329 NONRES_EXT_WALL 0.30 0.704 0.787 38.09 90.00 90.00 E
FLOOR 3 WORK ROOF NONRES_ROOF 0.30 0.351 0.376 53.33 90.00 0.00  
DFC6F0 NONRES_EXT_WALL 0.30 0.704 0.787 19.51 90.00 90.00 E
88E360 NONRES_EXT_WALL 0.30 0.704 0.787 66.89 0.00 90.00 N
E7B55F NONRES_EXT_WALL 0.30 0.704 0.787 11.15 180.00 90.00 S
NE STAIR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.61 0.00 180.00  
NE STAIR ROOF NONRES_ROOF 0.30 0.351 0.376 15.61 0.00 0.00  
FB3814 NONRES_EXT_WALL 0.30 0.704 0.787 19.51 180.00 90.00 S
FCD12D NONRES_EXT_WALL 0.30 0.704 0.787 55.74 270.00 90.00 W
NW ELEVATOR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 13.01 90.00 180.00  
NW ELEVATOR ROOF NONRES_ROOF 0.30 0.351 0.376 13.01 90.00 0.00  
5507DC NONRES_EXT_WALL 0.30 0.704 0.787 22.30 270.00 90.00 W
2E2D0C NONRES_EXT_WALL 0.30 0.704 0.787 66.89 0.00 90.00 N
AF0124 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 90.00 90.00 E
NW STAIR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 17.84 270.00 180.00  
NW STAIR ROOF NONRES_ROOF 0.30 0.351 0.376 17.84 270.00 0.00  
850EA7 NONRES_EXT_WALL 0.30 0.704 0.787 33.45 180.00 90.00 S
270BCE NONRES_EXT_WALL 0.30 0.704 0.787 22.30 270.00 90.00 W
SW STAIR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 8.92 270.00 180.00  
SW STAIR ROOF NONRES_ROOF 0.30 0.351 0.376 8.92 180.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
78F987 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 481E71 180.00 90.00 S
D8037E WINDOW_U_1.08_SHGC_0.25 8.92 0.00 0.00 8.92 8.92 5.778 0.306 0.155     No 5F762C 180.00 90.00 S
4A8120 WINDOW_U_1.08_SHGC_0.25 2.32 0.00 0.00 2.32 2.32 5.778 0.306 0.155     No 84FB73 0.00 90.00 N
AAE778 WINDOW_U_1.08_SHGC_0.25 8.92 0.00 0.00 8.92 8.92 5.778 0.306 0.155     No FE5A3C 270.00 90.00 W
3AAD8B WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No F629C1 0.00 90.00 N
8128A9 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No F629C1 0.00 90.00 N
9B1541 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 879583 180.00 90.00 S
CF850A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 879583 180.00 90.00 S
A6BA23 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No E326E4 90.00 90.00 E
D10D28 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No E326E4 90.00 90.00 E
591336 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1D96D7 90.00 90.00 E
38B811 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1D96D7 90.00 90.00 E
C044D6 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1D96D7 90.00 90.00 E
1D94BE WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 6D2616 0.00 90.00 N
18748E WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 6D2616 0.00 90.00 N
137A56 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No A5A6A3 180.00 90.00 S
8D508E WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
B2D381 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
1DA13A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
44E54A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
757D10 WINDOW_U_1.08_SHGC_0.25 0.74 0.00 0.00 0.74 0.74 5.778 0.306 0.155     No EA6DC8 180.00 90.00 S
E33BAE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No B40F89 270.00 90.00 W
24167A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 997723 180.00 90.00 S
2C0938 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 997723 180.00 90.00 S
8600DD WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No CEC7BD 180.00 90.00 S
A1ED60 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 859BC1 0.00 90.00 N
E8D997 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 859BC1 0.00 90.00 N
88E1FC WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 859BC1 0.00 90.00 N
F83F33 WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No 61E610 90.00 90.00 E
B1F5EE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No D95F04 90.00 90.00 E
F52F3D WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 208CCF 90.00 90.00 E
80885D WINDOW_U_1.08_SHGC_0.25 6.69 0.00 0.00 6.69 6.69 5.778 0.306 0.155     No AEF992 180.00 90.00 S
FEEF06 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 54D065 180.00 90.00 S
2BE8DE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1775A6 270.00 90.00 W
513E2A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1775A6 270.00 90.00 W
BA5CD9 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1775A6 270.00 90.00 W
1AD478 WINDOW_U_1.08_SHGC_0.25 3.72 0.00 0.00 3.72 3.72 5.778 0.306 0.155     No 97F00A 180.00 90.00 S
27F0AC WINDOW_U_1.08_SHGC_0.25 5.95 0.00 0.00 5.95 5.95 5.778 0.306 0.155     No A497E9 180.00 90.00 S
724114 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 88A75F 180.00 90.00 S
D538C4 WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No B4E619 90.00 90.00 E
5635BC WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No B4E619 90.00 90.00 E
831C1D WINDOW_U_1.08_SHGC_0.25 4.18 0.00 0.00 4.18 4.18 5.778 0.306 0.155     No 9EC269 0.00 90.00 N
9BB95F WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No B316F7 0.00 90.00 N
C0778D WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No B316F7 0.00 90.00 N
7D2D69 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9621FD 0.00 90.00 N
2EF63B WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9621FD 0.00 90.00 N
C417C0 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 42CEE1 0.00 90.00 N
EB042B WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
4C1F71 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
D23C8B WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
B4E4BE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
EEF55D WINDOW_U_1.08_SHGC_0.25 6.69 0.00 0.00 6.69 6.69 5.778 0.306 0.155     No 4ABC66 180.00 90.00 S
E55A57 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 4ABC66 180.00 90.00 S
93D018 WINDOW_U_1.08_SHGC_0.25 6.69 0.00 0.00 6.69 6.69 5.778 0.306 0.155     No 5B04CF 270.00 90.00 W
DD9F5D WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B55FA 90.00 90.00 E
15B02B WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9C3A6A 0.00 90.00 N
820282 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9C3A6A 0.00 90.00 N
9BA05A WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 68A2D7 0.00 90.00 N
C639E8 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 68A2D7 0.00 90.00 N
A2790A WINDOW_U_1.08_SHGC_0.25 4.18 0.00 0.00 4.18 4.18 5.778 0.306 0.155     No CE3FEF 0.00 90.00 N
79FCEE WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No CE618F 90.00 90.00 E
EDE617 WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No CE618F 90.00 90.00 E
C61F0D WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
7248C5 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
29FA28 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
F0B23F WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
EEC10E WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
944FCE WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
C41399 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
95BA33 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No D22917 90.00 90.00 E
F27282 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No D22917 90.00 90.00 E
3DB407 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
3DADE2 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
DF3E2C WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
5031C8 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
C087D0 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 8DA7DB 180.00 90.00 S
D2CA75 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 8DA7DB 180.00 90.00 S
B0FB49 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No 8DA7DB 180.00 90.00 S
FE9BC9 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 38B339 270.00 90.00 W
9DF7DE WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 38B339 270.00 90.00 W
D0BE44 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 38B339 270.00 90.00 W
6B5226 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No BE5F2F 270.00 90.00 W
8F59F7 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No 1DEE26 180.00 90.00 S
44F571 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No 1DEE26 180.00 90.00 S
6BD844 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
86D536 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
BAF71D WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
3833A2 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
2111A1 WINDOW_U_1.08_SHGC_0.25 0.74 0.00 0.00 0.74 0.74 5.778 0.306 0.155     No DFC6F0 90.00 90.00 E
9BC521 WINDOW_U_1.08_SHGC_0.25 5.71 0.00 0.00 5.71 5.71 5.778 0.306 0.155     No 88E360 0.00 90.00 N
142781 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 88E360 0.00 90.00 N
E74902 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 2E2D0C 0.00 90.00 N
93BBC3 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 2E2D0C 0.00 90.00 N
C635A6 WINDOW_U_1.08_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No 850EA7 180.00 90.00 S
Total or Average           308.29 5.778 0.306 0.155              
North Total or Average           97.22 5.778 0.306 0.155              
Non-North Total or Average           211.08 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
71E924 OPAQUEDOOR 8.100 8.100 2.97 8E5BB9
5E66D1 OPAQUEDOOR 8.100 8.100 5.95 529072
E14DAE OPAQUEDOOR 8.100 8.100 2.97 D95F04
84A1D5 OPAQUEDOOR 8.100 8.100 2.97 3330D8
9CB8E5 OPAQUEDOOR 8.100 8.100 2.97 88E360
EDE769 OPAQUEDOOR 8.100 8.100 2.97 5507DC



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 61078.37 0.80    


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed   169360.63 122577.85 46782.78 0.72 3.23    
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed   247220.17 193031.53 54188.65 0.78 3.13    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed 163347.3 2.80 9.57 N/A 10.75
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed 236650.6 2.65 9.05 N/A 10.22
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Coil:Heating:Water 1893.38 1875.84 -
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Coil:Heating:Water 313.95 181.09 -
FLOOR 1 CAFE VAV BOX REHEAT COIL Coil:Heating:Water 9670.29 5578.07 -
FLOOR 1 CLEAN VAV BOX REHEAT COIL Coil:Heating:Water 1222.40 1211.08 -
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Coil:Heating:Water 1533.25 1519.05 -
FLOOR 1 DICTATION VAV BOX REHEAT COIL Coil:Heating:Water 768.66 443.38 -
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Water 940.44 542.47 -
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 1539.27 887.89 -
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL Coil:Heating:Water 8555.24 4934.88 -
FLOOR 1 HUMID VAV BOX REHEAT COIL Coil:Heating:Water 382.65 220.72 -
FLOOR 1 IT HALL VAV BOX REHEAT COIL Coil:Heating:Water 680.87 392.74 -
FLOOR 1 IT ROOM VAV BOX REHEAT COIL Coil:Heating:Water 686.88 396.21 -
FLOOR 1 LOBBY VAV BOX REHEAT COIL Coil:Heating:Water 9448.80 5450.31 -
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Coil:Heating:Water 1294.56 746.74 -
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1183.36 1172.40 -
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Coil:Heating:Water 7849.27 4527.66 -
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Coil:Heating:Water 1967.03 1134.63 -
FLOOR 1 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Water 3425.24 1975.77 -
FLOOR 1 MED GAS VAV BOX REHEAT COIL Coil:Heating:Water 935.45 650.42 -
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 4121.51 2377.39 -
FLOOR 1 MRI HALL VAV BOX REHEAT COIL Coil:Heating:Water 876.98 505.86 -
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL Coil:Heating:Water 9658.33 5571.17 -
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1183.36 1172.40 -
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Coil:Heating:Water 1702.71 982.17 -
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Coil:Heating:Water 2393.10 1380.40 -
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 283.28 163.40 -
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Coil:Heating:Water 2319.06 1337.69 -
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1183.36 1172.40 -
FLOOR 1 OFFICE VAV BOX REHEAT COIL Coil:Heating:Water 2610.16 1505.61 -
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 25262.37 25028.42 -
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 25401.01 25165.77 -
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL Coil:Heating:Water 20862.23 20669.03 -
FLOOR 1 PACU VAV BOX REHEAT COIL Coil:Heating:Water 1420.03 1406.88 -
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Coil:Heating:Water 2389.15 1378.12 -
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 2485.06 2462.05 -
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 4444.18 4403.02 -
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1183.36 1172.40 -
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Coil:Heating:Water 9368.28 9281.52 -
FLOOR 1 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Water 5760.92 3323.04 -
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Water 617.92 356.43 -
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 8866.41 8784.30 -
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Coil:Heating:Water 1060.84 611.92 -
FLOOR 1 SCRUB VAV BOX REHEAT COIL Coil:Heating:Water 419.93 242.22 -
FLOOR 1 SOIL VAV BOX REHEAT COIL Coil:Heating:Water 2761.18 2735.61 -
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Coil:Heating:Water 1227.19 1215.83 -
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Coil:Heating:Water 3944.54 3908.01 -
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Coil:Heating:Water 6357.95 6299.07 -
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Coil:Heating:Water 2612.93 1507.20 -
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 1383.56 798.08 -
FLOOR 1 STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 8766.17 5284.15 -
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Coil:Heating:Water 2241.82 1293.14 -
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Coil:Heating:Water 2827.64 1631.05 -
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 245.06 141.36 -
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 3187.84 1838.83 -
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Coil:Heating:Water 1272.96 734.27 -
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Coil:Heating:Electric   2712.32 1.00
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1379.08 1.00
FLOOR 2 DICTATION VAV BOX REHEAT COIL Coil:Heating:Electric   197.99 1.00
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Coil:Heating:Electric   9668.20 1.00
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Coil:Heating:Electric   7044.51 1.00
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Coil:Heating:Electric   9598.86 1.00
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Coil:Heating:Electric   1836.93 1.00
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Coil:Heating:Electric   7419.46 1.00
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Coil:Heating:Electric   3881.82 1.00
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Coil:Heating:Electric   10239.68 1.00
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Coil:Heating:Electric   4748.62 1.00
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Coil:Heating:Electric   5217.50 1.00
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Coil:Heating:Electric   496.31 1.00
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Coil:Heating:Electric   479.42 1.00
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Coil:Heating:Electric   467.14 1.00
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Coil:Heating:Electric   482.77 1.00
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Coil:Heating:Electric   507.27 1.00
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Coil:Heating:Electric   509.92 1.00
FLOOR 2 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric   504.33 1.00
FLOOR 2 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric   308.79 1.00
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Coil:Heating:Electric   518.28 1.00
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Coil:Heating:Electric   633.77 1.00
FLOOR 2 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric   2938.68 1.00
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1026.82 1.00
FLOOR 2 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Electric   5646.07 1.00
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1408.23 1.00
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   0.00 1.00
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Coil:Heating:Electric   735.88 1.00
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Coil:Heating:Electric   785.25 1.00
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric   145.02 1.00
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric   260.00 1.00
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Coil:Heating:Electric   331.66 1.00
FLOOR 2 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric   641.01 1.00
FLOOR 2 WORK VAV BOX REHEAT COIL Coil:Heating:Electric   4182.57 1.00
FLOOR 2 WORK HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1965.16 1.00
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1163.60 1.00
FLOOR 2 X-RAY VAV BOX REHEAT COIL Coil:Heating:Electric   6930.48 1.00
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Electric   187.00 1.00
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Coil:Heating:Electric   979.77 1.00
FLOOR 3 HUMID VAV BOX REHEAT COIL Coil:Heating:Electric   465.44 1.00
FLOOR 3 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric   438.77 1.00
FLOOR 3 LOCKER VAV BOX REHEAT COIL Coil:Heating:Electric   693.53 1.00
FLOOR 3 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric   4046.87 1.00
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   4137.24 1.00
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Coil:Heating:Electric   0.00 1.00
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1142.19 1.00
FLOOR 3 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric   11006.92 1.00
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric   2418.07 1.00
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1163.60 1.00
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Coil:Heating:Electric   27410.57 1.00
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Coil:Heating:Electric   9370.64 1.00
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1810.04 1.00
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric   1125.92 1.00
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric   294.41 1.00
FLOOR 3 TREATMENT VAV BOX REHEAT COIL Coil:Heating:Electric   7749.26 1.00
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Coil:Heating:Electric   9380.21 1.00
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Coil:Heating:Electric   5036.44 1.00
FLOOR 3 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric   589.21 1.00
FLOOR 3 WORK VAV BOX REHEAT COIL Coil:Heating:Electric   3375.34 1.00
NE STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   2714.19 1.00
NW ELEVATOR VAV BOX REHEAT COIL Coil:Heating:Electric   1688.40 1.00
NW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   3092.67 1.00
SW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   1270.70 1.00
AHU-1_HEATC Coil:Heating:Water 2744.43 2707.41 -
AHU-1_EXTRAELECHEATC Coil:Heating:Electric   10000000.00 1.00
AHU-1_EXTRAWATERHEATC Coil:Heating:Water 2744.43 2707.41 -
AHU-2_HEATC Coil:Heating:Water 43664.66 41558.70 -


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
FLOOR 1 ANESTHESIA EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.07 54.61 803.55 1.00 Zone Exhaust Fans
FLOOR 1 LOBBY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.16 127.44 803.55 1.00 Zone Exhaust Fans
FLOOR 1 MRI ROOM EXHAUST FAN Fan:ZoneExhaust 0.16 124.50 0.42 323.16 778.12 1.00 Zone Exhaust Fans
FLOOR 1 MRI TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 NURSE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 PRE-OP TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 SOIL EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.10 79.63 803.55 1.00 Zone Exhaust Fans
FLOOR 1 SOIL HOLD EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 35.39 803.55 1.00 Zone Exhaust Fans
FLOOR 1 SOIL WORK EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.14 113.76 803.55 1.00 Zone Exhaust Fans
FLOOR 2 CONFERENCE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.05 40.45 803.55 1.00 Zone Exhaust Fans
FLOOR 2 RECEPTION TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.10 79.63 803.55 1.00 Zone Exhaust Fans
FLOOR 2 WORK TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 2 X-RAY EXHAUST FAN Fan:ZoneExhaust 0.16 124.50 0.85 661.02 778.13 1.00 Zone Exhaust Fans
FLOOR 3 LOUNGE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.15 121.35 803.55 1.00 Zone Exhaust Fans
FLOOR 3 OFFICE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.07 53.09 803.55 1.00 Zone Exhaust Fans
AHU-1_FAN Fan:VariableVolume 0.60 1389.42 8.15 18847.45 2313.39 1.00 Fan Energy
AHU-2_FAN Fan:VariableVolume 0.60 1389.42 14.21 32660.22 2298.46 1.00 Fan Energy


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0001 8.07 127739.32 0.30
HEATSYS1 PUMP Pump:ConstantSpeed Intermittent 179352.00 0.0013 334.65 255487.18 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.76 58614.20 0.81 0.78 0.28


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed None 163347.27 2.80 9.57 10.75 8.7592 3.06 10.46 6.7291 3.28 11.20 4.3557 3.39 11.57 1.9582
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed None 236650.55 2.65 9.05 10.22 15.2772 2.90 9.91 11.3107 3.13 10.69 7.0579 3.24 11.06 3.1763
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {W/1000cfm} (773.3 {W/(m3/s)})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FLOOR 1 ANESTHESIA 819.64 819.64 0.065 0.068 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 1 CAFE 4384.05 4384.05 0.347 0.347 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
FLOOR 1 CLEAN 554.76 554.76 0.044 0.044 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 36.78 0.00412
FLOOR 1 CLEAN WORK 695.82 695.82 0.055 0.055 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 37.54 0.00412
FLOOR 1 DICTATION 360.30 360.30 0.028 0.028 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 DRESSING ROOM 426.92 426.92 0.034 0.034 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 44.20 0.00412
FLOOR 1 HUMID 179.01 179.01 0.014 0.014 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 IT ROOM 322.18 322.18 0.025 0.025 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 LOBBY 4288.79 4288.79 0.339 0.339 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 43.21 0.00412
FLOOR 1 LOCKER ROOM 3562.46 3562.46 0.282 0.282 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 43.21 0.00412
FLOOR 1 LOUNGE 1554.54 1554.54 0.123 0.123 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 37.92 0.00412
FLOOR 1 MRI CONTROL ROOM 1870.50 1870.50 0.148 0.148 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 42.67 0.00412
FLOOR 1 MRI ROOM 4383.17 4383.17 0.347 0.347 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 42.31 0.00412
FLOOR 1 NOURISHMENT 772.75 772.75 0.061 0.061 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 35.92 0.00412
FLOOR 1 NURSE STATION 1052.45 1052.45 0.083 0.083 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 35.92 0.00412
FLOOR 1 OFFICE 1184.79 1184.79 0.094 0.094 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 35.92 0.00412
FLOOR 1 OPERATING ROOM 1 7437.79 7437.79 0.907 0.907 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 41.10 0.00412
FLOOR 1 OPERATING ROOM 2 7478.40 7478.40 0.912 0.912 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 39.41 0.00412
FLOOR 1 OPERATING ROOM 3 5948.11 5948.11 0.685 0.749 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 07:20:00 32.68 0.00412
FLOOR 1 PACU 519.56 519.56 0.041 0.051 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:30:00 35.49 0.00412
FLOOR 1 PRE-OP ROOM 1 699.08 699.08 0.055 0.089 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:20:00 43.03 0.00412
FLOOR 1 PRE-OP ROOM 2 1115.63 1115.63 0.088 0.160 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:30:00 35.49 0.00412
FLOOR 1 PROCEDURE ROOM 2313.50 2313.50 0.183 0.336 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 43.80 0.00412
FLOOR 1 RECEPTION 2614.11 2614.11 0.207 0.207 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
FLOOR 1 RECOVERY ROOM 4024.03 4024.03 0.318 0.318 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 44.20 0.00412
FLOOR 1 SCHEDULING 481.55 481.55 0.038 0.038 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 44.20 0.00412
FLOOR 1 SOIL 549.28 549.28 0.043 0.099 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 36.78 0.00412
FLOOR 1 SOIL HOLD 250.43 250.43 0.020 0.044 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 12:20:00 42.80 0.00412
FLOOR 1 SOIL WORK 746.06 746.06 0.059 0.142 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 37.16 0.00412
FLOOR 1 STEP DOWN 2885.67 2885.67 0.228 0.228 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 43.53 0.00412
FLOOR 2 CONFERENCE 3532.85 3532.85 0.330 0.330 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 2 DICTATION 266.40 266.40 0.024 0.024 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM 1 3779.25 3779.25 0.353 0.353 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 43.39 0.00412
FLOOR 2 EXAM 2 2753.38 2753.38 0.257 0.257 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 44.20 0.00412
FLOOR 2 EXAM 3 3751.75 3751.75 0.350 0.350 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
FLOOR 2 EXAM 4 718.04 718.04 0.067 0.067 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 2 EXAM 5 2900.11 2900.11 0.271 0.271 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 40.08 0.00412
FLOOR 2 EXAM 6 1517.31 1517.31 0.142 0.142 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 43.39 0.00412
FLOOR 2 EXAM 7 3797.12 3797.12 0.355 0.374 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 43.53 0.00412
FLOOR 2 EXAM 8 1856.12 1856.12 0.173 0.173 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 43.39 0.00412
FLOOR 2 EXAM 9 2039.30 2039.30 0.190 0.190 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 43.39 0.00412
FLOOR 2 LOUNGE 402.34 402.34 0.038 0.038 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 35.06 0.00412
FLOOR 2 NURSE STATION 1 675.26 675.26 0.063 0.063 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 35.06 0.00412
FLOOR 2 NURSE STATION 2 825.72 825.72 0.077 0.077 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 35.06 0.00412
FLOOR 2 OFFICE 3829.60 3829.60 0.358 0.358 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 40.08 0.00412
FLOOR 2 RECEPTION 7355.11 7355.11 0.687 0.687 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 43.53 0.00412
FLOOR 2 SCHEDULING 1 958.92 958.92 0.090 0.090 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 35.06 0.00412
FLOOR 2 SCHEDULING 2 1061.97 1061.97 0.096 0.096 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 WORK 5450.27 5450.27 0.509 0.509 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 43.80 0.00412
FLOOR 2 X-RAY 9029.28 9029.28 0.843 0.843 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 41.19 0.00412
FLOOR 3 DRESSING ROOM 243.70 243.70 0.023 0.023 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
FLOOR 3 HUMID 606.57 606.57 0.057 0.057 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
FLOOR 3 LOCKER 903.71 903.71 0.084 0.084 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 3 LOUNGE 5272.68 5272.68 0.492 0.492 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 3 OFFICE 14342.88 14342.88 1.339 1.339 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 3 PHYSICAL THERAPY 1 10713.34 10713.34 1.001 1.001 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 44.20 0.00412
FLOOR 3 PHYSICAL THERAPY 2 3662.89 3662.89 0.342 0.342 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
FLOOR 3 TREATMENT 3029.12 3029.12 0.283 0.283 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 3 WORK 4398.39 4398.39 0.411 0.411 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 40.76 0.00412
FLOOR 1 BIO HAZ 146.37 146.37 0.011 0.011 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 ELECTRICAL ROOM 698.77 698.77 0.055 0.055 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 11:50:00 42.22 0.00412
FLOOR 1 ELEVATOR PUMP ROOM 3883.93 3883.93 0.307 0.307 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 42.09 0.00412
FLOOR 1 IT HALL 317.23 317.23 0.024 0.024 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 LOBBY HALL 608.19 608.19 0.046 0.046 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 LOBBY TOILET 533.85 533.85 0.042 0.042 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 41.64 0.00412
FLOOR 1 LOCKER ROOM HALL 922.08 922.08 0.071 0.071 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 MED GAS 424.68 424.68 0.034 0.034 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 13:20:00 43.75 0.00412
FLOOR 1 MRI HALL 410.93 410.93 0.031 0.031 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 MRI TOILET 236.66 236.66 0.019 0.042 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 43.53 0.00412
FLOOR 1 NURSE HALL 1126.64 1126.64 0.086 0.086 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 NURSE JANITOR 131.79 131.79 0.010 0.010 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 NURSE TOILET 155.05 155.05 0.012 0.042 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 PRE-OP HALL 1123.60 1123.60 0.086 0.086 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 PRE-OP TOILET 290.78 290.78 0.023 0.042 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 42.09 0.00412
FLOOR 1 RECEPTION HALL 289.40 289.40 0.022 0.022 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 SCRUB 195.82 195.82 0.015 0.015 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 STERILE HALL 1226.26 1226.26 0.094 0.094 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 STERILE STORAGE 648.42 648.42 0.050 0.050 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 STORAGE 3979.45 3979.45 0.315 0.315 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 43.66 0.00412
FLOOR 1 SUB-STERILE 1017.71 1017.71 0.080 0.080 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 40.08 0.00412
FLOOR 1 UTILITY HALL 1283.62 1283.62 0.101 0.101 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 40.42 0.00412
FLOOR 1 UTILITY JANITOR 114.02 114.02 0.009 0.009 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 1 UTILITY ROOM 1447.16 1447.16 0.114 0.114 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 40.08 0.00412
FLOOR 1 VESTIBULE 577.89 577.89 0.046 0.046 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 43.39 0.00412
FLOOR 2 CONFERENCE TOILET 228.33 228.33 0.021 0.050 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM HALL 1 669.82 669.82 0.060 0.060 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM HALL 2 647.09 647.09 0.058 0.058 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM HALL 3 630.57 630.57 0.057 0.057 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM HALL 4 651.66 651.66 0.059 0.059 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM HALL 5 684.77 684.77 0.062 0.062 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 EXAM HALL 6 688.34 688.34 0.062 0.062 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 JANITOR 657.32 657.32 0.061 0.061 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 41.86 0.00412
FLOOR 2 OFFICE HALL 1386.98 1386.98 0.125 0.125 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 RECEPTION HALL 1902.27 1902.27 0.171 0.171 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 RECEPTION TOILET 414.89 414.89 0.037 0.099 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 STORAGE 1 195.27 195.27 0.018 0.018 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 STORAGE 2 351.06 351.06 0.032 0.032 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 STORAGE 3 448.40 448.40 0.040 0.040 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 UTILITY 835.39 835.39 0.078 0.078 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 40.08 0.00412
FLOOR 2 WORK HALL 2654.73 2654.73 0.239 0.239 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 31.29 0.00412
FLOOR 2 WORK TOILET 325.37 325.37 0.030 0.042 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 41.64 0.00412
FLOOR 3 ELEVATOR HALL 1276.81 1276.81 0.119 0.119 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 3 JANITOR 459.83 459.83 0.043 0.043 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 42.31 0.00412
FLOOR 3 LOUNGE TOILET 1183.81 1183.81 0.111 0.151 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 44.20 0.00412
FLOOR 3 MECHANICAL 4234.85 4234.85 0.395 0.395 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 40.76 0.00412
FLOOR 3 MECHANICAL HALL 1488.61 1488.61 0.139 0.139 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 44.20 0.00412
FLOOR 3 OFFICE HALL 3151.17 3151.17 0.294 0.294 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 44.20 0.00412
FLOOR 3 OFFICE TOILET 307.87 307.87 0.029 0.042 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 42.31 0.00412
FLOOR 3 PHYSICAL THERAPY TOILET 371.02 371.02 0.035 0.066 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
FLOOR 3 STORAGE 1 440.22 440.22 0.041 0.041 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
FLOOR 3 STORAGE 2 383.70 383.70 0.036 0.036 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 44.20 0.00412
FLOOR 3 UNDEVELOPED 1 12224.07 12224.07 1.141 1.141 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 43.93 0.00412
FLOOR 3 UNDEVELOPED 2 6563.38 6563.38 0.613 0.613 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 43.93 0.00412
FLOOR 3 UTILITY 767.92 767.92 0.072 0.072 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 44.20 0.00412
NE STAIR 3537.30 3537.30 0.330 0.330 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 44.07 0.00412
NW ELEVATOR 2200.41 2200.41 0.205 0.205 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 42.09 0.00412
NW STAIR 4030.57 4030.57 0.376 0.376 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:10:00 43.21 0.00412
SW STAIR 1656.05 1656.05 0.155 0.155 RIYADH ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 42.67 0.00412


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FLOOR 1 ANESTHESIA 71.92 71.92 0.003 0.015 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 CAFE 23.86 23.86 0.001 0.184 RIYADH ANN HTG 99.6% CONDNS DB 1/21 07:10:00 5.90 0.00619
FLOOR 1 CLEAN 0.00 0.00 0.000 0.018 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 CLEAN WORK 0.00 0.00 0.000 0.023 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 DICTATION 0.00 0.00 0.000 0.005 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 DRESSING ROOM 165.29 165.29 0.008 0.008 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 HUMID 0.00 0.00 0.000 0.002 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 IT ROOM 0.00 0.00 0.000 0.004 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 LOBBY 184.67 184.67 0.008 0.032 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 LOCKER ROOM 0.00 0.00 0.000 0.042 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 LOUNGE 0.00 0.00 0.000 0.023 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 MRI CONTROL ROOM 0.00 0.00 0.000 0.024 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 MRI ROOM 0.00 0.00 0.000 0.062 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 NOURISHMENT 0.00 0.00 0.000 0.014 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 NURSE STATION 0.00 0.00 0.000 0.020 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 OFFICE 0.00 0.00 0.000 0.019 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 OPERATING ROOM 1 0.00 0.00 0.000 0.239 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 OPERATING ROOM 2 0.00 0.00 0.000 0.249 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 OPERATING ROOM 3 0.00 0.00 0.000 0.247 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 PACU 0.00 0.00 0.000 0.032 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 PRE-OP ROOM 1 0.00 0.00 0.000 0.052 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 PRE-OP ROOM 2 0.00 0.00 0.000 0.093 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 PROCEDURE ROOM 0.00 0.00 0.000 0.108 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 RECEPTION 0.00 0.00 0.000 0.050 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 RECOVERY ROOM 42.16 42.16 0.002 0.161 RIYADH ANN HTG 99.6% CONDNS DB 1/21 07:10:00 5.90 0.00619
FLOOR 1 SCHEDULING 0.00 0.00 0.000 0.005 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 SOIL 0.00 0.00 0.000 0.018 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 SOIL HOLD 0.00 0.00 0.000 0.008 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 SOIL WORK 0.00 0.00 0.000 0.025 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 STEP DOWN 351.68 351.68 0.016 0.090 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 CONFERENCE 888.53 888.53 0.040 0.049 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 DICTATION 0.00 0.00 0.000 0.003 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 EXAM 1 895.85 895.85 0.041 0.051 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM 2 19.63 19.63 0.001 0.076 RIYADH ANN HTG 99.6% CONDNS DB 1/21 07:10:00 5.90 0.00619
FLOOR 2 EXAM 3 24.23 24.23 0.001 0.102 RIYADH ANN HTG 99.6% CONDNS DB 1/21 07:10:00 5.90 0.00619
FLOOR 2 EXAM 4 224.56 224.56 0.010 0.012 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM 5 624.37 624.37 0.028 0.050 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM 6 275.95 275.95 0.012 0.032 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM 7 0.00 0.00 0.000 0.112 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 EXAM 8 216.99 216.99 0.010 0.038 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM 9 0.00 0.00 0.000 0.056 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 LOUNGE 0.00 0.00 0.000 0.005 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 NURSE STATION 1 0.00 0.00 0.000 0.011 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 NURSE STATION 2 0.00 0.00 0.000 0.014 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 OFFICE 1235.78 1235.78 0.056 0.056 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 RECEPTION 850.10 850.10 0.038 0.098 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 SCHEDULING 1 0.00 0.00 0.000 0.013 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 SCHEDULING 2 0.00 0.00 0.000 0.014 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 WORK 0.00 0.00 0.000 0.068 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 X-RAY 0.00 0.00 0.000 0.127 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 3 DRESSING ROOM 9.88 9.88 0.000 0.002 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 HUMID 9.08 9.08 0.000 0.004 RIYADH ANN HTG 99.6% CONDNS DB 1/21 07:40:00 5.90 0.00619
FLOOR 3 LOCKER 32.75 32.75 0.001 0.008 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5.90 0.00619
FLOOR 3 LOUNGE 95.48 95.48 0.004 0.048 RIYADH ANN HTG 99.6% CONDNS DB 1/21 07:40:00 5.90 0.00619
FLOOR 3 OFFICE 3463.19 3463.19 0.155 0.155 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 PHYSICAL THERAPY 1 3006.15 3006.15 0.136 0.184 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 PHYSICAL THERAPY 2 309.81 309.81 0.014 0.084 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 TREATMENT 110.93 110.93 0.005 0.067 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:10:00 5.90 0.00619
FLOOR 3 WORK 1557.30 1557.30 0.070 0.070 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 BIO HAZ 46.20 46.20 0.002 0.003 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 ELEVATOR PUMP ROOM 74.61 74.61 0.003 0.003 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 IT HALL 0.00 0.00 0.000 0.004 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 LOBBY HALL 0.00 0.00 0.000 0.007 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 LOBBY TOILET 112.88 112.88 0.005 0.005 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.000 0.014 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 MED GAS 306.21 306.21 0.014 0.014 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 MRI HALL 0.00 0.00 0.000 0.004 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 MRI TOILET 47.28 47.28 0.002 0.002 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 NURSE HALL 0.00 0.00 0.000 0.014 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 NURSE JANITOR 0.00 0.00 0.000 0.003 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 PRE-OP HALL 0.00 0.00 0.000 0.015 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 PRE-OP TOILET 110.13 110.13 0.005 0.005 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 RECEPTION HALL 0.00 0.00 0.000 0.004 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 SCRUB 17.04 17.04 0.001 0.002 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 STERILE HALL 0.00 0.00 0.000 0.017 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 STERILE STORAGE 0.00 0.00 0.000 0.022 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 1 STORAGE 2246.35 2246.35 0.101 0.101 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 SUB-STERILE 381.50 381.50 0.017 0.017 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 UTILITY HALL 655.78 655.78 0.030 0.030 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 UTILITY JANITOR 9.82 9.82 0.000 0.002 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 UTILITY ROOM 702.32 702.32 0.032 0.032 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 1 VESTIBULE 172.45 172.45 0.008 0.008 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 CONFERENCE TOILET 28.73 28.73 0.001 0.001 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM HALL 1 154.90 154.90 0.007 0.007 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM HALL 2 10.51 10.51 0.000 0.005 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM HALL 3 38.61 38.61 0.002 0.005 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 EXAM HALL 4 0.00 0.00 0.000 0.006 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 EXAM HALL 5 0.00 0.00 0.000 0.006 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 EXAM HALL 6 0.00 0.00 0.000 0.006 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 JANITOR 292.06 292.06 0.013 0.013 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 OFFICE HALL 192.82 192.82 0.009 0.013 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 RECEPTION HALL 0.00 0.00 0.000 0.016 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 STORAGE 1 21.41 21.41 0.001 0.003 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 STORAGE 2 0.00 0.00 0.000 0.007 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 STORAGE 3 0.00 0.00 0.000 0.008 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 UTILITY 382.84 382.84 0.017 0.017 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 2 WORK HALL 0.00 0.00 0.000 0.024 RIYADH ANN HTG 99.6% CONDNS DB   5.90 0.00619
FLOOR 2 WORK TOILET 182.34 182.34 0.008 0.008 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 ELEVATOR HALL 683.21 683.21 0.031 0.031 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 JANITOR 351.54 351.54 0.016 0.016 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 LOUNGE TOILET 526.71 526.71 0.024 0.024 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 MECHANICAL HALL 568.08 568.08 0.026 0.026 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 OFFICE HALL 1227.52 1227.52 0.056 0.056 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 OFFICE TOILET 237.67 237.67 0.011 0.011 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 PHYSICAL THERAPY TOILET 47.96 47.96 0.002 0.002 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 STORAGE 1 149.60 149.60 0.007 0.007 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 STORAGE 2 144.23 144.23 0.007 0.007 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 UNDEVELOPED 1 3738.56 3738.56 0.168 0.168 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 UNDEVELOPED 2 2594.48 2594.48 0.117 0.117 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
FLOOR 3 UTILITY 278.99 278.99 0.013 0.013 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
NE STAIR 2094.08 2094.08 0.095 0.095 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
NW ELEVATOR 1244.68 1244.68 0.056 0.056 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
NW STAIR 2080.29 2080.29 0.094 0.094 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619
SW STAIR 994.38 994.38 0.045 0.045 RIYADH ANN HTG 99.6% CONDNS DB 1/21 08:20:00 5.90 0.00619


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AHU-1 8.15 8.15 2.20 2.20
AHU-2 14.21 14.21 2.52 2.52



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FLOOR 1 ANESTHESIA 2688.83 7404.50 2462.67
FLOOR 1 CAFE 1386.67 5991.83 340.67
FLOOR 1 CLEAN 1087.50 7626.83 1004.67
FLOOR 1 CLEAN WORK 2002.33 7694.50 1956.17
FLOOR 1 DICTATION 227.17 7714.00 223.33
FLOOR 1 DRESSING ROOM 1861.17 7070.50 1406.17
FLOOR 1 HUMID 61.33 7674.83 49.00
FLOOR 1 IT ROOM 402.83 7625.50 357.17
FLOOR 1 LOBBY 1011.33 6701.17 321.67
FLOOR 1 LOCKER ROOM 520.50 7172.67 114.00
FLOOR 1 LOUNGE 332.33 7366.00 74.17
FLOOR 1 MRI CONTROL ROOM 588.67 6551.50 135.33
FLOOR 1 MRI ROOM 448.50 6406.83 49.83
FLOOR 1 NOURISHMENT 240.50 7516.00 85.17
FLOOR 1 NURSE STATION 333.33 7551.17 202.67
FLOOR 1 OFFICE 115.00 7599.67 62.50
FLOOR 1 OPERATING ROOM 1 4623.67 7606.17 4486.33
FLOOR 1 OPERATING ROOM 2 5475.33 7669.17 5389.17
FLOOR 1 OPERATING ROOM 3 6501.67 7764.50 6492.67
FLOOR 1 PACU 2669.83 7726.50 2641.67
FLOOR 1 PRE-OP ROOM 1 2563.50 7695.00 2512.67
FLOOR 1 PRE-OP ROOM 2 2747.83 7819.17 2747.83
FLOOR 1 PROCEDURE ROOM 3448.67 7657.83 3360.00
FLOOR 1 RECEPTION 546.50 7072.50 103.00
FLOOR 1 RECOVERY ROOM 2561.33 7360.67 2306.33
FLOOR 1 SCHEDULING 400.33 7515.33 283.50
FLOOR 1 SOIL 3655.67 7830.00 3655.67
FLOOR 1 SOIL HOLD 3443.17 7827.33 3443.17
FLOOR 1 SOIL WORK 3780.33 7830.00 3780.33
FLOOR 1 STEP DOWN 2881.67 7319.33 2539.00
FLOOR 2 CONFERENCE 1671.50 6742.50 1243.00
FLOOR 2 DICTATION 924.67 7830.00 924.67
FLOOR 2 EXAM 1 3586.33 7536.83 3407.67
FLOOR 2 EXAM 2 2902.50 7745.67 2890.67
FLOOR 2 EXAM 3 3277.17 7763.83 3271.33
FLOOR 2 EXAM 4 3232.17 7661.33 3190.00
FLOOR 2 EXAM 5 3284.67 7634.17 3225.33
FLOOR 2 EXAM 6 3387.50 7692.17 3357.33
FLOOR 2 EXAM 7 3264.00 7772.83 3258.83
FLOOR 2 EXAM 8 3306.00 7679.33 3269.50
FLOOR 2 EXAM 9 2845.83 7749.17 2834.17
FLOOR 2 LOUNGE 613.67 7823.00 613.67
FLOOR 2 NURSE STATION 1 463.33 7723.83 458.33
FLOOR 2 NURSE STATION 2 438.50 7684.17 430.33
FLOOR 2 OFFICE 1402.00 7333.50 1309.50
FLOOR 2 RECEPTION 975.17 6901.50 558.67
FLOOR 2 SCHEDULING 1 349.50 7814.33 349.50
FLOOR 2 SCHEDULING 2 375.67 7793.17 375.67
FLOOR 2 WORK 421.83 7433.67 371.33
FLOOR 2 X-RAY 442.17 6699.00 0.00
FLOOR 3 DRESSING ROOM 2236.83 7749.83 2231.67
FLOOR 3 HUMID 1877.17 7683.67 1861.50
FLOOR 3 LOCKER 1525.50 7461.17 1389.17
FLOOR 3 LOUNGE 1561.17 6964.83 1154.33
FLOOR 3 OFFICE 1628.50 7025.50 1295.33
FLOOR 3 PHYSICAL THERAPY 1 3811.83 7258.50 3496.67
FLOOR 3 PHYSICAL THERAPY 2 3976.83 7657.00 3912.17
FLOOR 3 TREATMENT 3680.83 7630.17 3599.17
FLOOR 3 WORK 2228.33 6623.33 1689.00
FLOOR 1 BIO HAZ 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00
FLOOR 1 MED GAS 0.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00
FLOOR 1 MRI TOILET 0.00 0.00 0.00
FLOOR 1 NURSE HALL 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.00 0.00
FLOOR 1 STERILE HALL 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00
FLOOR 1 STORAGE 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.00 0.00
FLOOR 1 VESTIBULE 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00
FLOOR 2 STORAGE 1 0.00 0.00 0.00
FLOOR 2 STORAGE 2 0.00 0.00 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00
FLOOR 2 UTILITY 0.00 0.00 0.00
FLOOR 2 WORK HALL 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 0.00 0.00 0.00
FLOOR 3 JANITOR 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 0.00 0.00 0.00
FLOOR 3 UTILITY 0.00 0.00 0.00
NE STAIR 0.00 0.00 0.00
NW ELEVATOR 0.00 0.00 0.00
NW STAIR 0.00 0.00 0.00
SW STAIR 0.00 0.00 0.00
Facility 7422.33 7830.00 6816.33
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FLOOR 1 ANESTHESIA 0.00 559.67 0.00 559.67
FLOOR 1 CAFE 0.00 910.00 0.00 910.00
FLOOR 1 CLEAN 0.00 367.50 0.00 367.50
FLOOR 1 CLEAN WORK 0.00 331.17 0.00 331.17
FLOOR 1 DICTATION 0.00 302.83 0.00 302.83
FLOOR 1 DRESSING ROOM 0.00 323.33 0.00 323.33
FLOOR 1 HUMID 0.00 317.33 0.00 317.33
FLOOR 1 IT ROOM 0.00 319.50 0.00 319.50
FLOOR 1 LOBBY 0.00 354.83 0.00 354.83
FLOOR 1 LOCKER ROOM 0.00 402.67 0.00 402.67
FLOOR 1 LOUNGE 0.00 475.67 0.00 475.67
FLOOR 1 MRI CONTROL ROOM 0.00 994.83 0.00 994.83
FLOOR 1 MRI ROOM 0.00 1709.17 0.00 1709.17
FLOOR 1 NOURISHMENT 0.00 380.17 0.00 380.17
FLOOR 1 NURSE STATION 0.00 359.00 0.00 359.00
FLOOR 1 OFFICE 0.00 353.00 0.00 353.00
FLOOR 1 OPERATING ROOM 1 0.00 1588.00 0.00 1588.00
FLOOR 1 OPERATING ROOM 2 0.00 1395.17 0.00 1395.17
FLOOR 1 OPERATING ROOM 3 0.00 1797.83 0.00 1797.83
FLOOR 1 PACU 0.00 296.83 0.00 296.83
FLOOR 1 PRE-OP ROOM 1 0.00 271.00 0.00 271.00
FLOOR 1 PRE-OP ROOM 2 0.00 186.17 0.00 186.17
FLOOR 1 PROCEDURE ROOM 0.83 184.83 0.83 184.83
FLOOR 1 RECEPTION 0.00 563.00 0.00 563.00
FLOOR 1 RECOVERY ROOM 0.00 530.17 0.00 530.17
FLOOR 1 SCHEDULING 0.00 327.00 0.00 327.00
FLOOR 1 SOIL 0.00 111.50 0.00 111.50
FLOOR 1 SOIL HOLD 0.00 138.33 0.00 138.33
FLOOR 1 SOIL WORK 0.00 91.50 0.00 91.50
FLOOR 1 STEP DOWN 0.00 384.50 0.00 384.50
FLOOR 2 CONFERENCE 0.00 413.67 0.00 413.67
FLOOR 2 DICTATION 4.00 155.00 4.00 155.00
FLOOR 2 EXAM 1 7.33 307.17 7.33 307.17
FLOOR 2 EXAM 2 0.00 327.67 0.00 327.67
FLOOR 2 EXAM 3 0.00 293.83 0.00 293.83
FLOOR 2 EXAM 4 7.17 328.17 7.17 328.17
FLOOR 2 EXAM 5 0.17 305.83 0.17 305.83
FLOOR 2 EXAM 6 0.00 315.00 0.00 315.00
FLOOR 2 EXAM 7 0.00 286.50 0.00 286.50
FLOOR 2 EXAM 8 0.00 318.17 0.00 318.17
FLOOR 2 EXAM 9 0.00 324.33 0.00 324.33
FLOOR 2 LOUNGE 0.00 344.17 0.00 344.17
FLOOR 2 NURSE STATION 1 0.00 408.50 0.00 408.50
FLOOR 2 NURSE STATION 2 0.00 422.33 0.00 422.33
FLOOR 2 OFFICE 3.17 314.50 3.17 314.50
FLOOR 2 RECEPTION 0.17 416.50 0.17 416.50
FLOOR 2 SCHEDULING 1 0.00 323.83 0.00 323.83
FLOOR 2 SCHEDULING 2 0.17 321.50 0.17 321.50
FLOOR 2 WORK 0.67 397.00 0.67 397.00
FLOOR 2 X-RAY 0.00 742.67 0.00 742.67
FLOOR 3 DRESSING ROOM 5.83 280.33 5.83 280.33
FLOOR 3 HUMID 5.00 308.83 5.00 308.83
FLOOR 3 LOCKER 0.00 400.00 0.00 400.00
FLOOR 3 LOUNGE 0.00 460.33 0.00 460.33
FLOOR 3 OFFICE 6.67 443.83 6.67 443.83
FLOOR 3 PHYSICAL THERAPY 1 3.67 427.67 3.67 427.67
FLOOR 3 PHYSICAL THERAPY 2 0.00 336.83 0.00 336.83
FLOOR 3 TREATMENT 0.00 339.50 0.00 339.50
FLOOR 3 WORK 11.67 407.00 11.67 407.00
FLOOR 1 BIO HAZ 0.67 226.83 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 443.33 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.50 475.50 0.00 0.00
FLOOR 1 IT HALL 0.00 228.67 0.00 0.00
FLOOR 1 LOBBY HALL 0.00 369.83 0.00 0.00
FLOOR 1 LOBBY TOILET 5.17 316.17 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 264.50 0.00 0.00
FLOOR 1 MED GAS 0.00 350.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 303.17 0.00 0.00
FLOOR 1 MRI TOILET 10.17 70.33 0.00 0.00
FLOOR 1 NURSE HALL 0.00 234.50 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 227.00 0.00 0.00
FLOOR 1 NURSE TOILET 10.33 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.00 279.33 0.00 0.00
FLOOR 1 PRE-OP TOILET 17.17 222.67 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 246.17 0.00 0.00
FLOOR 1 SCRUB 0.17 296.17 0.00 0.00
FLOOR 1 STERILE HALL 0.33 327.83 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 230.83 0.00 0.00
FLOOR 1 STORAGE 0.00 332.17 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 368.83 0.00 0.00
FLOOR 1 UTILITY HALL 0.00 387.67 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.33 279.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 327.50 0.00 0.00
FLOOR 1 VESTIBULE 764.00 2179.33 0.00 0.00
FLOOR 2 CONFERENCE TOILET 5.00 1.33 0.00 0.00
FLOOR 2 EXAM HALL 1 6.33 237.17 0.00 0.00
FLOOR 2 EXAM HALL 2 6.33 192.50 0.00 0.00
FLOOR 2 EXAM HALL 3 9.83 150.50 0.00 0.00
FLOOR 2 EXAM HALL 4 6.17 195.50 0.00 0.00
FLOOR 2 EXAM HALL 5 5.67 215.50 0.00 0.00
FLOOR 2 EXAM HALL 6 5.83 206.83 0.00 0.00
FLOOR 2 JANITOR 1.67 208.17 0.00 0.00
FLOOR 2 OFFICE HALL 5.00 215.00 0.00 0.00
FLOOR 2 RECEPTION HALL 2.33 208.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 3856.83 0.50 0.00 0.00
FLOOR 2 STORAGE 1 11.83 50.50 0.00 0.00
FLOOR 2 STORAGE 2 6.33 148.83 0.00 0.00
FLOOR 2 STORAGE 3 5.33 168.83 0.00 0.00
FLOOR 2 UTILITY 14.00 242.33 0.00 0.00
FLOOR 2 WORK HALL 1.00 259.67 0.00 0.00
FLOOR 2 WORK TOILET 13.00 81.67 0.00 0.00
FLOOR 3 ELEVATOR HALL 16.33 422.50 0.00 0.00
FLOOR 3 JANITOR 18.33 310.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 17.50 192.33 0.00 0.00
FLOOR 3 MECHANICAL 24.33 468.83 0.00 0.00
FLOOR 3 MECHANICAL HALL 12.33 344.33 0.00 0.00
FLOOR 3 OFFICE HALL 10.83 421.33 0.00 0.00
FLOOR 3 OFFICE TOILET 24.17 138.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 6.33 40.83 0.00 0.00
FLOOR 3 STORAGE 1 0.00 197.83 0.00 0.00
FLOOR 3 STORAGE 2 14.33 302.50 0.00 0.00
FLOOR 3 UNDEVELOPED 1 8.17 424.17 0.00 0.00
FLOOR 3 UNDEVELOPED 2 8.67 440.17 0.00 0.00
FLOOR 3 UTILITY 24.67 221.33 0.00 0.00
NE STAIR 26.33 385.67 0.00 0.00
NW ELEVATOR 23.17 287.17 0.00 0.00
NW STAIR 24.17 366.83 0.00 0.00
SW STAIR 22.00 358.83 0.00 0.00
Facility 3860.17 3036.50 14.17 2203.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:44

AirTerminal:SingleDuct:VAV:Reheat

Maximum Air Flow Rate [m3/s] Maximum Reheat Water Flow Rate [m3/s] Reheat Coil Sizing Air Volume Flow Rate [m3/s]
FLOOR 1 ANESTHESIA VAV BOX COMPONENT 0.067956 0.000041 0.067956
FLOOR 1 BIO HAZ VAV BOX COMPONENT 0.011268 0.000002 0.003380
FLOOR 1 CAFE VAV BOX COMPONENT 0.347081 0.000062 0.104124
FLOOR 1 CLEAN VAV BOX COMPONENT 0.043874 0.000026 0.043874
FLOOR 1 CLEAN WORK VAV BOX COMPONENT 0.055031 0.000033 0.055031
FLOOR 1 DICTATION VAV BOX COMPONENT 0.027588 0.000005 0.008277
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT 0.033754 0.000006 0.010126
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT 0.055247 0.000010 0.016574
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT 0.307060 0.000055 0.092118
FLOOR 1 HUMID VAV BOX COMPONENT 0.013734 0.000002 0.004120
FLOOR 1 IT HALL VAV BOX COMPONENT 0.024438 0.000004 0.007331
FLOOR 1 IT ROOM VAV BOX COMPONENT 0.024653 0.000004 0.007396
FLOOR 1 LOBBY VAV BOX COMPONENT 0.339131 0.000061 0.101739
FLOOR 1 LOBBY HALL VAV BOX COMPONENT 0.046464 0.000008 0.013939
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT 0.042473 0.000025 0.042473
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT 0.281722 0.000051 0.084517
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT 0.070600 0.000013 0.021180
FLOOR 1 LOUNGE VAV BOX COMPONENT 0.122937 0.000022 0.036881
FLOOR 1 MED GAS VAV BOX COMPONENT 0.033575 0.000008 0.013948
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT 0.147927 0.000027 0.044378
FLOOR 1 MRI HALL VAV BOX COMPONENT 0.031476 0.000006 0.009443
FLOOR 1 MRI ROOM VAV BOX COMPONENT 0.346652 0.000062 0.103996
FLOOR 1 MRI TOILET VAV BOX COMPONENT 0.042473 0.000025 0.042473
FLOOR 1 NOURISHMENT VAV BOX COMPONENT 0.061113 0.000011 0.018334
FLOOR 1 NURSE HALL VAV BOX COMPONENT 0.085892 0.000015 0.025768
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT 0.010167 0.000002 0.003050
FLOOR 1 NURSE STATION VAV BOX COMPONENT 0.083234 0.000015 0.024970
FLOOR 1 NURSE TOILET VAV BOX COMPONENT 0.042473 0.000025 0.042473
FLOOR 1 OFFICE VAV BOX COMPONENT 0.093683 0.000017 0.028105
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT 0.906704 0.000544 0.906704
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT 0.911680 0.000547 0.911680
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT 0.748776 0.000449 0.748776
FLOOR 1 PACU VAV BOX COMPONENT 0.050967 0.000031 0.050967
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT 0.085750 0.000015 0.025725
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT 0.089192 0.000054 0.089192
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT 0.159508 0.000096 0.159508
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT 0.042473 0.000025 0.042473
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT 0.336241 0.000202 0.336241
FLOOR 1 RECEPTION VAV BOX COMPONENT 0.206768 0.000037 0.062030
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT 0.022178 0.000004 0.006653
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT 0.318229 0.000191 0.318229
FLOOR 1 SCHEDULING VAV BOX COMPONENT 0.038075 0.000007 0.011422
FLOOR 1 SCRUB VAV BOX COMPONENT 0.015072 0.000003 0.004522
FLOOR 1 SOIL VAV BOX COMPONENT 0.099103 0.000059 0.099103
FLOOR 1 SOIL HOLD VAV BOX COMPONENT 0.044046 0.000026 0.044046
FLOOR 1 SOIL WORK VAV BOX COMPONENT 0.141575 0.000085 0.141575
FLOOR 1 STEP DOWN VAV BOX COMPONENT 0.228196 0.000137 0.228196
FLOOR 1 STERILE HALL VAV BOX COMPONENT 0.093782 0.000017 0.028135
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT 0.049658 0.000009 0.014897
FLOOR 1 STORAGE VAV BOX COMPONENT 0.314631 0.000061 0.101430
FLOOR 1 SUB-STERILE VAV BOX COMPONENT 0.080462 0.000014 0.024139
FLOOR 1 UTILITY HALL VAV BOX COMPONENT 0.101488 0.000018 0.030446
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT 0.008796 0.000002 0.002639
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT 0.114416 0.000021 0.034325
FLOOR 1 VESTIBULE VAV BOX COMPONENT 0.045688 0.000008 0.013707
FLOOR 2 CONFERENCE VAV BOX COMPONENT 0.330009    
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT 0.050338    
FLOOR 2 DICTATION VAV BOX COMPONENT 0.024090    
FLOOR 2 EXAM 1 VAV BOX COMPONENT 0.352899    
FLOOR 2 EXAM 2 VAV BOX COMPONENT 0.257132    
FLOOR 2 EXAM 3 VAV BOX COMPONENT 0.350368    
FLOOR 2 EXAM 4 VAV BOX COMPONENT 0.067050    
FLOOR 2 EXAM 5 VAV BOX COMPONENT 0.270818    
FLOOR 2 EXAM 6 VAV BOX COMPONENT 0.141691    
FLOOR 2 EXAM 7 VAV BOX COMPONENT 0.373759    
FLOOR 2 EXAM 8 VAV BOX COMPONENT 0.173329    
FLOOR 2 EXAM 9 VAV BOX COMPONENT 0.190444    
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT 0.060387    
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT 0.058331    
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT 0.056837    
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT 0.058739    
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT 0.061719    
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT 0.062042    
FLOOR 2 JANITOR VAV BOX COMPONENT 0.061361    
FLOOR 2 LOUNGE VAV BOX COMPONENT 0.037570    
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT 0.063059    
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT 0.077110    
FLOOR 2 OFFICE VAV BOX COMPONENT 0.357549    
FLOOR 2 OFFICE HALL VAV BOX COMPONENT 0.124933    
FLOOR 2 RECEPTION VAV BOX COMPONENT 0.686958    
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT 0.171339    
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT 0.099103    
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT 0.089535    
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT 0.095541    
FLOOR 2 STORAGE 1 VAV BOX COMPONENT 0.017645    
FLOOR 2 STORAGE 2 VAV BOX COMPONENT 0.031635    
FLOOR 2 STORAGE 3 VAV BOX COMPONENT 0.040353    
FLOOR 2 UTILITY VAV BOX COMPONENT 0.077991    
FLOOR 2 WORK VAV BOX COMPONENT 0.508893    
FLOOR 2 WORK HALL VAV BOX COMPONENT 0.239101    
FLOOR 2 WORK TOILET VAV BOX COMPONENT 0.042473    
FLOOR 2 X-RAY VAV BOX COMPONENT 0.843233    
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT 0.022753    
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT 0.119208    
FLOOR 3 HUMID VAV BOX COMPONENT 0.056631    
FLOOR 3 JANITOR VAV BOX COMPONENT 0.042930    
FLOOR 3 LOCKER VAV BOX COMPONENT 0.084382    
FLOOR 3 LOUNGE VAV BOX COMPONENT 0.492383    
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT 0.151014    
FLOOR 3 MECHANICAL VAV BOX COMPONENT 0.395382    
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT 0.138971    
FLOOR 3 OFFICE VAV BOX COMPONENT 1.34    
FLOOR 3 OFFICE HALL VAV BOX COMPONENT 0.294207    
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT 0.042473    
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT 1.00    
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT 0.342038    
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT 0.066069    
FLOOR 3 STORAGE 1 VAV BOX COMPONENT 0.041097    
FLOOR 3 STORAGE 2 VAV BOX COMPONENT 0.035821    
FLOOR 3 TREATMENT VAV BOX COMPONENT 0.282856    
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT 1.14    
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT 0.612784    
FLOOR 3 UTILITY VAV BOX COMPONENT 0.071690    
FLOOR 3 WORK VAV BOX COMPONENT 0.410678    
NE STAIR VAV BOX COMPONENT 0.330236    
NW ELEVATOR VAV BOX COMPONENT 0.205427    
NW STAIR VAV BOX COMPONENT 0.376285    
SW STAIR VAV BOX COMPONENT 0.154606    


Coil:Heating:Water

Design Coil Load [W] Maximum Water Flow Rate [m3/s] U-Factor Times Area Value [W/K]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL 1893.38 0.000041 40.82
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL 94.18 0.000002 6.77
FLOOR 1 CAFE VAV BOX REHEAT COIL 2901.09 0.000062 208.50
FLOOR 1 CLEAN VAV BOX REHEAT COIL 1222.40 0.000026 26.36
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL 1533.25 0.000033 33.06
FLOOR 1 DICTATION VAV BOX REHEAT COIL 230.60 0.000005 16.57
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL 282.13 0.000006 20.28
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL 461.78 0.000010 33.19
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL 2566.57 0.000055 184.46
FLOOR 1 HUMID VAV BOX REHEAT COIL 114.79 0.000002 8.25
FLOOR 1 IT HALL VAV BOX REHEAT COIL 204.26 0.000004 14.68
FLOOR 1 IT ROOM VAV BOX REHEAT COIL 206.06 0.000004 14.81
FLOOR 1 LOBBY VAV BOX REHEAT COIL 2834.64 0.000061 203.73
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL 388.37 0.000008 27.91
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL 1183.36 0.000025 25.51
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL 2354.78 0.000051 169.24
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL 590.11 0.000013 42.41
FLOOR 1 LOUNGE VAV BOX REHEAT COIL 1027.57 0.000022 73.85
FLOOR 1 MED GAS VAV BOX REHEAT COIL 388.62 0.000008 20.17
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL 1236.45 0.000027 88.86
FLOOR 1 MRI HALL VAV BOX REHEAT COIL 263.09 0.000006 18.91
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL 2897.50 0.000062 208.25
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL 1183.36 0.000025 25.51
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL 510.81 0.000011 36.71
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL 717.93 0.000015 51.60
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL 84.98 0.000002 6.11
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL 695.72 0.000015 50.00
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL 1183.36 0.000025 25.51
FLOOR 1 OFFICE VAV BOX REHEAT COIL 783.05 0.000017 56.28
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL 25262.37 0.000544 544.69
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL 25401.01 0.000547 547.68
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL 20862.23 0.000449 449.82
FLOOR 1 PACU VAV BOX REHEAT COIL 1420.03 0.000031 30.62
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL 716.74 0.000015 51.51
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL 2485.06 0.000054 53.58
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL 4444.18 0.000096 95.82
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL 1183.36 0.000025 25.51
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL 9368.28 0.000202 201.99
FLOOR 1 RECEPTION VAV BOX REHEAT COIL 1728.27 0.000037 124.21
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL 185.37 0.000004 13.32
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL 8866.41 0.000191 191.17
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL 318.25 0.000007 22.87
FLOOR 1 SCRUB VAV BOX REHEAT COIL 125.98 0.000003 9.05
FLOOR 1 SOIL VAV BOX REHEAT COIL 2761.18 0.000059 59.53
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL 1227.19 0.000026 26.46
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL 3944.54 0.000085 85.05
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL 6357.95 0.000137 137.09
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL 783.88 0.000017 56.34
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL 415.07 0.000009 29.83
FLOOR 1 STORAGE VAV BOX REHEAT COIL 2826.01 0.000061 189.01
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL 672.55 0.000014 48.34
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL 848.29 0.000018 60.97
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL 73.52 0.000002 5.28
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL 956.35 0.000021 68.73
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL 381.89 0.000008 27.45
AHU-1_HEATC 2744.43 0.000059 45.30
AHU-1_EXTRAWATERHEATC 2744.43 0.000059 45.30
AHU-2_HEATC 43664.66 0.000940 712.94


Coil:Heating:Electric

Nominal Capacity [W]
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL 2712.32
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL 1379.08
FLOOR 2 DICTATION VAV BOX REHEAT COIL 197.99
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL 9668.20
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL 7044.51
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL 9598.86
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL 1836.93
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL 7419.46
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL 3881.82
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL 10239.68
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL 4748.62
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL 5217.50
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL 496.31
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL 479.42
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL 467.14
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL 482.77
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL 507.27
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL 509.92
FLOOR 2 JANITOR VAV BOX REHEAT COIL 504.33
FLOOR 2 LOUNGE VAV BOX REHEAT COIL 308.79
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL 518.28
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL 633.77
FLOOR 2 OFFICE VAV BOX REHEAT COIL 2938.68
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL 1026.82
FLOOR 2 RECEPTION VAV BOX REHEAT COIL 5646.07
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL 1408.23
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL 0.000000
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL 735.88
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL 785.25
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL 145.02
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL 260.00
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL 331.66
FLOOR 2 UTILITY VAV BOX REHEAT COIL 641.01
FLOOR 2 WORK VAV BOX REHEAT COIL 4182.57
FLOOR 2 WORK HALL VAV BOX REHEAT COIL 1965.16
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL 1163.60
FLOOR 2 X-RAY VAV BOX REHEAT COIL 6930.48
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL 187.00
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL 979.77
FLOOR 3 HUMID VAV BOX REHEAT COIL 465.44
FLOOR 3 JANITOR VAV BOX REHEAT COIL 438.77
FLOOR 3 LOCKER VAV BOX REHEAT COIL 693.53
FLOOR 3 LOUNGE VAV BOX REHEAT COIL 4046.87
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL 4137.24
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL 0.000000
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL 1142.19
FLOOR 3 OFFICE VAV BOX REHEAT COIL 11006.92
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL 2418.07
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL 1163.60
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL 27410.57
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL 9370.64
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL 1810.04
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL 1125.92
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL 294.41
FLOOR 3 TREATMENT VAV BOX REHEAT COIL 7749.26
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL 9380.21
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL 5036.44
FLOOR 3 UTILITY VAV BOX REHEAT COIL 589.21
FLOOR 3 WORK VAV BOX REHEAT COIL 3375.34
NE STAIR VAV BOX REHEAT COIL 2714.19
NW ELEVATOR VAV BOX REHEAT COIL 1688.40
NW STAIR VAV BOX REHEAT COIL 3092.67
SW STAIR VAV BOX REHEAT COIL 1270.70


Branch

Maximum Flow Rate [m3/s]
AHU-1 AIR LOOP MAIN BRANCH 8.15
AHU-2 AIR LOOP MAIN BRANCH 14.21


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AHU-1 8.15
AHU-2 14.21


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AHU-1_OA_CONTROLLER 8.15 2.07
AHU-2_OA_CONTROLLER 14.21 4.53


Coil:Cooling:DX:TwoSpeed

Rated High Speed Air Flow Rate [m3/s] Rated High Speed Total Cooling Capacity (gross) [W] Rated High Speed Sensible Heat Ratio Rated Low Speed Air Flow Rate [m3/s] Rated Low Speed Total Cooling Capacity (gross) [W]
AHU-1_COOLC DXCOIL 8.15 169360.63 0.723768 2.72 56447.90
AHU-2_COOLC DXCOIL 14.21 247220.17 0.780808 4.74 82398.48


Fan:VariableVolume

Maximum Flow Rate [m3/s]
AHU-1_FAN 8.15
AHU-2_FAN 14.21


Controller:WaterCoil

Maximum Actuated Flow [m3/s]
AHU-1_HEATC_CONTROLLER 0.000059
AHU-1_EXTRAWATERHEATC_CONTROLLER 0.000059
AHU-2_HEATC_CONTROLLER 0.000940


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000063 0.047375
HEATSYS1 0.001310 0.982391


Boiler:HotWater

Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 0.001310


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000063


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SWHSYS1 PUMP 0.000063 8.07
HEATSYS1 PUMP 0.001310 334.65



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 ANESTHESIA

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.83 14.02
February 19.81 16.67
March 19.82 20.28
April 19.79 25.86
May 19.94 32.05
June 20.61 35.24
July 20.95 36.21
August 21.13 36.44
September 20.41 33.05
October 20.22 27.59
November 20.04 21.57
December 19.71 14.93
     
Annual Sum or Average 20.19 26.21
Minimum of Months 19.71 14.02
Maximum of Months 21.13 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 BIO HAZ

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.32 14.02
February 20.48 16.67
March 20.79 20.28
April 21.13 25.86
May 21.61 32.05
June 22.27 35.24
July 22.49 36.21
August 22.53 36.44
September 21.85 33.05
October 21.16 27.59
November 20.71 21.57
December 20.33 14.93
     
Annual Sum or Average 21.31 26.21
Minimum of Months 20.32 14.02
Maximum of Months 22.53 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 CAFE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.13 14.02
February 21.22 16.67
March 21.44 20.28
April 21.51 25.86
May 21.90 32.05
June 22.63 35.24
July 22.92 36.21
August 23.07 36.44
September 22.41 33.05
October 22.04 27.59
November 21.66 21.57
December 21.02 14.93
     
Annual Sum or Average 21.92 26.21
Minimum of Months 21.02 14.02
Maximum of Months 23.07 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 CLEAN

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.36 14.02
February 20.38 16.67
March 20.44 20.28
April 20.36 25.86
May 20.44 32.05
June 21.13 35.24
July 21.39 36.21
August 21.49 36.44
September 20.71 33.05
October 20.42 27.59
November 20.46 21.57
December 20.23 14.93
     
Annual Sum or Average 20.65 26.21
Minimum of Months 20.23 14.02
Maximum of Months 21.49 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 CLEAN WORK

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.10 14.02
February 20.13 16.67
March 20.19 20.28
April 20.13 25.86
May 20.22 32.05
June 20.86 35.24
July 21.10 36.21
August 21.20 36.44
September 20.45 33.05
October 20.18 27.59
November 20.19 21.57
December 19.99 14.93
     
Annual Sum or Average 20.40 26.21
Minimum of Months 19.99 14.02
Maximum of Months 21.20 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 DICTATION

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.49 14.02
February 21.51 16.67
March 21.61 20.28
April 21.55 25.86
May 21.63 32.05
June 22.15 35.24
July 22.31 36.21
August 22.45 36.44
September 21.91 33.05
October 21.62 27.59
November 21.61 21.57
December 21.45 14.93
     
Annual Sum or Average 21.78 26.21
Minimum of Months 21.45 14.02
Maximum of Months 22.45 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 DRESSING ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.84 14.02
February 20.13 16.67
March 20.62 20.28
April 21.21 25.86
May 21.96 32.05
June 22.74 35.24
July 23.09 36.21
August 23.06 36.44
September 22.13 33.05
October 21.31 27.59
November 20.62 21.57
December 19.84 14.93
     
Annual Sum or Average 21.39 26.21
Minimum of Months 19.84 14.02
Maximum of Months 23.09 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.23 14.02
February 21.37 16.67
March 21.60 20.28
April 21.81 25.86
May 22.17 32.05
June 22.86 35.24
July 23.19 36.21
August 23.19 36.44
September 22.44 33.05
October 21.93 27.59
November 21.62 21.57
December 21.16 14.93
     
Annual Sum or Average 22.05 26.21
Minimum of Months 21.16 14.02
Maximum of Months 23.19 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.20 14.02
February 21.28 16.67
March 21.48 20.28
April 21.50 25.86
May 21.76 32.05
June 22.44 35.24
July 22.70 36.21
August 22.79 36.44
September 21.90 33.05
October 21.55 27.59
November 21.44 21.57
December 21.06 14.93
     
Annual Sum or Average 21.76 26.21
Minimum of Months 21.06 14.02
Maximum of Months 22.79 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 HUMID

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 14.02
February 21.77 16.67
March 21.86 20.28
April 21.82 25.86
May 21.89 32.05
June 22.41 35.24
July 22.59 36.21
August 22.70 36.44
September 22.19 33.05
October 21.88 27.59
November 21.87 21.57
December 21.71 14.93
     
Annual Sum or Average 22.04 26.21
Minimum of Months 21.71 14.02
Maximum of Months 22.70 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 IT HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.79 14.02
February 20.89 16.67
March 21.07 20.28
April 21.18 25.86
May 21.43 32.05
June 22.01 35.24
July 22.19 36.21
August 22.29 36.44
September 21.70 33.05
October 21.24 27.59
November 21.05 21.57
December 20.78 14.93
     
Annual Sum or Average 21.39 26.21
Minimum of Months 20.78 14.02
Maximum of Months 22.29 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 IT ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 14.02
February 21.19 16.67
March 21.43 20.28
April 21.57 25.86
May 21.88 32.05
June 22.49 35.24
July 22.68 36.21
August 22.75 36.44
September 22.12 33.05
October 21.61 27.59
November 21.36 21.57
December 21.05 14.93
     
Annual Sum or Average 21.77 26.21
Minimum of Months 21.05 14.02
Maximum of Months 22.75 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOBBY

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.88 14.02
February 21.12 16.67
March 21.45 20.28
April 21.70 25.86
May 22.26 32.05
June 22.94 35.24
July 23.20 36.21
August 23.25 36.44
September 22.53 33.05
October 21.93 27.59
November 21.44 21.57
December 20.81 14.93
     
Annual Sum or Average 21.96 26.21
Minimum of Months 20.81 14.02
Maximum of Months 23.25 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOBBY HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 14.02
February 21.80 16.67
March 21.97 20.28
April 22.05 25.86
May 22.29 32.05
June 22.86 35.24
July 23.10 36.21
August 23.18 36.44
September 22.67 33.05
October 22.27 27.59
November 22.05 21.57
December 21.66 14.93
     
Annual Sum or Average 22.30 26.21
Minimum of Months 21.66 14.02
Maximum of Months 23.18 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOBBY TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.72 14.02
February 19.79 16.67
March 19.94 20.28
April 20.00 25.86
May 20.27 32.05
June 20.96 35.24
July 21.24 36.21
August 21.34 36.44
September 20.40 33.05
October 20.06 27.59
November 19.85 21.57
December 19.66 14.93
     
Annual Sum or Average 20.27 26.21
Minimum of Months 19.66 14.02
Maximum of Months 21.34 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOCKER ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.31 14.02
February 21.44 16.67
March 21.68 20.28
April 21.84 25.86
May 22.17 32.05
June 22.86 35.24
July 23.14 36.21
August 23.14 36.44
September 22.42 33.05
October 21.91 27.59
November 21.69 21.57
December 21.28 14.93
     
Annual Sum or Average 22.08 26.21
Minimum of Months 21.28 14.02
Maximum of Months 23.14 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.35 14.02
February 21.43 16.67
March 21.57 20.28
April 21.59 25.86
May 21.75 32.05
June 22.28 35.24
July 22.43 36.21
August 22.53 36.44
September 22.08 33.05
October 21.70 27.59
November 21.59 21.57
December 21.34 14.93
     
Annual Sum or Average 21.81 26.21
Minimum of Months 21.34 14.02
Maximum of Months 22.53 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOUNGE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.61 14.02
February 21.68 16.67
March 21.84 20.28
April 21.90 25.86
May 22.09 32.05
June 22.74 35.24
July 22.98 36.21
August 23.04 36.44
September 22.37 33.05
October 21.95 27.59
November 21.83 21.57
December 21.58 14.93
     
Annual Sum or Average 22.14 26.21
Minimum of Months 21.58 14.02
Maximum of Months 23.04 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MED GAS

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.63 14.02
February 19.89 16.67
March 20.45 20.28
April 21.21 25.86
May 22.20 32.05
June 23.05 35.24
July 23.37 36.21
August 23.34 36.44
September 22.37 33.05
October 21.33 27.59
November 20.20 21.57
December 19.63 14.93
     
Annual Sum or Average 21.40 26.21
Minimum of Months 19.63 14.02
Maximum of Months 23.37 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.04 14.02
February 22.15 16.67
March 22.34 20.28
April 22.57 25.86
May 22.91 32.05
June 23.57 35.24
July 23.91 36.21
August 23.85 36.44
September 23.12 33.05
October 22.67 27.59
November 22.40 21.57
December 21.96 14.93
     
Annual Sum or Average 22.79 26.21
Minimum of Months 21.96 14.02
Maximum of Months 23.91 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.25 14.02
February 21.40 16.67
March 21.61 20.28
April 21.74 25.86
May 22.01 32.05
June 22.56 35.24
July 22.79 36.21
August 22.85 36.44
September 22.29 33.05
October 21.86 27.59
November 21.63 21.57
December 21.25 14.93
     
Annual Sum or Average 21.94 26.21
Minimum of Months 21.25 14.02
Maximum of Months 22.85 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.57 14.02
February 22.62 16.67
March 22.68 20.28
April 22.77 25.86
May 22.92 32.05
June 23.57 35.24
July 23.92 36.21
August 23.86 36.44
September 23.19 33.05
October 22.88 27.59
November 22.80 21.57
December 22.44 14.93
     
Annual Sum or Average 23.02 26.21
Minimum of Months 22.44 14.02
Maximum of Months 23.92 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.49 14.02
February 19.51 16.67
March 19.60 20.28
April 19.56 25.86
May 19.66 32.05
June 20.03 35.24
July 20.22 36.21
August 20.29 36.44
September 19.69 33.05
October 19.54 27.59
November 19.51 21.57
December 19.47 14.93
     
Annual Sum or Average 19.72 26.21
Minimum of Months 19.47 14.02
Maximum of Months 20.29 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NOURISHMENT

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.66 14.02
February 21.68 16.67
March 21.78 20.28
April 21.72 25.86
May 21.80 32.05
June 22.38 35.24
July 22.59 36.21
August 22.71 36.44
September 22.09 33.05
October 21.78 27.59
November 21.78 21.57
December 21.61 14.93
     
Annual Sum or Average 21.97 26.21
Minimum of Months 21.61 14.02
Maximum of Months 22.71 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.07 14.02
February 21.12 16.67
March 21.21 20.28
April 21.20 25.86
May 21.36 32.05
June 21.92 35.24
July 22.11 36.21
August 22.29 36.44
September 21.79 33.05
October 21.46 27.59
November 21.33 21.57
December 21.01 14.93
     
Annual Sum or Average 21.49 26.21
Minimum of Months 21.01 14.02
Maximum of Months 22.29 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE JANITOR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.57 14.02
February 21.62 16.67
March 21.72 20.28
April 21.70 25.86
May 21.80 32.05
June 22.30 35.24
July 22.46 36.21
August 22.56 36.44
September 22.14 33.05
October 21.80 27.59
November 21.75 21.57
December 21.55 14.93
     
Annual Sum or Average 21.91 26.21
Minimum of Months 21.55 14.02
Maximum of Months 22.56 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE STATION

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.51 14.02
February 21.54 16.67
March 21.65 20.28
April 21.59 25.86
May 21.69 32.05
June 22.28 35.24
July 22.48 36.21
August 22.63 36.44
September 22.02 33.05
October 21.71 27.59
November 21.67 21.57
December 21.45 14.93
     
Annual Sum or Average 21.85 26.21
Minimum of Months 21.45 14.02
Maximum of Months 22.63 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.49 14.02
February 19.51 16.67
March 19.59 20.28
April 19.52 25.86
May 19.56 32.05
June 19.72 35.24
July 19.75 36.21
August 19.86 36.44
September 19.55 33.05
October 19.50 27.59
November 19.49 21.57
December 19.48 14.93
     
Annual Sum or Average 19.58 26.21
Minimum of Months 19.48 14.02
Maximum of Months 19.86 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OFFICE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.59 14.02
February 21.67 16.67
March 21.82 20.28
April 21.85 25.86
May 22.01 32.05
June 22.56 35.24
July 22.77 36.21
August 22.87 36.44
September 22.33 33.05
October 21.96 27.59
November 21.84 21.57
December 21.58 14.93
     
Annual Sum or Average 22.07 26.21
Minimum of Months 21.58 14.02
Maximum of Months 22.87 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.41 14.02
February 18.40 16.67
March 18.39 20.28
April 18.44 25.86
May 18.52 32.05
June 19.04 35.24
July 19.39 36.21
August 19.40 36.44
September 18.68 33.05
October 18.49 27.59
November 18.43 21.57
December 18.36 14.93
     
Annual Sum or Average 18.67 26.21
Minimum of Months 18.36 14.02
Maximum of Months 19.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.35 14.02
February 18.35 16.67
March 18.37 20.28
April 18.44 25.86
May 18.52 32.05
June 19.02 35.24
July 19.35 36.21
August 19.35 36.44
September 18.62 33.05
October 18.43 27.59
November 18.37 21.57
December 18.33 14.93
     
Annual Sum or Average 18.63 26.21
Minimum of Months 18.33 14.02
Maximum of Months 19.35 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.47 14.02
February 18.47 16.67
March 18.44 20.28
April 18.46 25.86
May 18.53 32.05
June 19.00 35.24
July 19.29 36.21
August 19.31 36.44
September 18.62 33.05
October 18.47 27.59
November 18.46 21.57
December 18.40 14.93
     
Annual Sum or Average 18.66 26.21
Minimum of Months 18.40 14.02
Maximum of Months 19.31 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PACU

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.82 14.02
February 19.84 16.67
March 19.90 20.28
April 19.84 25.86
May 19.94 32.05
June 20.50 35.24
July 20.70 36.21
August 20.85 36.44
September 20.10 33.05
October 19.88 27.59
November 19.88 21.57
December 19.75 14.93
     
Annual Sum or Average 20.08 26.21
Minimum of Months 19.75 14.02
Maximum of Months 20.85 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.09 14.02
February 21.20 16.67
March 21.37 20.28
April 21.43 25.86
May 21.66 32.05
June 22.23 35.24
July 22.41 36.21
August 22.54 36.44
September 22.01 33.05
October 21.59 27.59
November 21.42 21.57
December 21.08 14.93
     
Annual Sum or Average 21.67 26.21
Minimum of Months 21.08 14.02
Maximum of Months 22.54 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.64 14.02
February 19.68 16.67
March 19.79 20.28
April 19.78 25.86
May 19.93 32.05
June 20.52 35.24
July 20.77 36.21
August 20.91 36.44
September 20.12 33.05
October 19.84 27.59
November 19.74 21.57
December 19.59 14.93
     
Annual Sum or Average 20.03 26.21
Minimum of Months 19.59 14.02
Maximum of Months 20.91 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.68 14.02
February 19.70 16.67
March 19.77 20.28
April 19.70 25.86
May 19.79 32.05
June 20.23 35.24
July 20.41 36.21
August 20.55 36.44
September 19.88 33.05
October 19.71 27.59
November 19.72 21.57
December 19.63 14.93
     
Annual Sum or Average 19.90 26.21
Minimum of Months 19.63 14.02
Maximum of Months 20.55 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.50 14.02
February 19.53 16.67
March 19.64 20.28
April 19.64 25.86
May 19.82 32.05
June 20.36 35.24
July 20.58 36.21
August 20.76 36.44
September 19.95 33.05
October 19.68 27.59
November 19.54 21.57
December 19.48 14.93
     
Annual Sum or Average 19.88 26.21
Minimum of Months 19.48 14.02
Maximum of Months 20.76 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.49 14.02
February 19.51 16.67
March 19.59 20.28
April 19.53 25.86
May 19.60 32.05
June 19.94 35.24
July 20.08 36.21
August 20.19 36.44
September 19.62 33.05
October 19.50 27.59
November 19.49 21.57
December 19.48 14.93
     
Annual Sum or Average 19.67 26.21
Minimum of Months 19.48 14.02
Maximum of Months 20.19 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 RECEPTION

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.46 14.02
February 21.57 16.67
March 21.76 20.28
April 21.84 25.86
May 22.13 32.05
June 22.79 35.24
July 23.06 36.21
August 23.17 36.44
September 22.57 33.05
October 22.16 27.59
November 21.89 21.57
December 21.41 14.93
     
Annual Sum or Average 22.15 26.21
Minimum of Months 21.41 14.02
Maximum of Months 23.17 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 RECEPTION HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.24 14.02
February 21.33 16.67
March 21.47 20.28
April 21.51 25.86
May 21.71 32.05
June 22.25 35.24
July 22.43 36.21
August 22.55 36.44
September 22.08 33.05
October 21.69 27.59
November 21.54 21.57
December 21.22 14.93
     
Annual Sum or Average 21.75 26.21
Minimum of Months 21.22 14.02
Maximum of Months 22.55 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.80 14.02
February 19.78 16.67
March 19.80 20.28
April 19.77 25.86
May 19.91 32.05
June 20.57 35.24
July 20.91 36.21
August 21.10 36.44
September 20.36 33.05
October 20.16 27.59
November 20.00 21.57
December 19.69 14.93
     
Annual Sum or Average 20.16 26.21
Minimum of Months 19.69 14.02
Maximum of Months 21.10 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SCHEDULING

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.05 14.02
February 21.18 16.67
March 21.38 20.28
April 21.48 25.86
May 21.83 32.05
June 22.47 35.24
July 22.74 36.21
August 22.86 36.44
September 22.24 33.05
October 21.79 27.59
November 21.50 21.57
December 21.01 14.93
     
Annual Sum or Average 21.80 26.21
Minimum of Months 21.01 14.02
Maximum of Months 22.86 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SCRUB

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 14.02
February 21.08 16.67
March 21.28 20.28
April 21.45 25.86
May 21.76 32.05
June 22.34 35.24
July 22.58 36.21
August 22.67 36.44
September 22.10 33.05
October 21.64 27.59
November 21.34 21.57
December 20.86 14.93
     
Annual Sum or Average 21.67 26.21
Minimum of Months 20.86 14.02
Maximum of Months 22.67 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SOIL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.52 14.02
February 19.54 16.67
March 19.61 20.28
April 19.55 25.86
May 19.60 32.05
June 19.86 35.24
July 19.96 36.21
August 20.10 36.44
September 19.61 33.05
October 19.53 27.59
November 19.53 21.57
December 19.50 14.93
     
Annual Sum or Average 19.66 26.21
Minimum of Months 19.50 14.02
Maximum of Months 20.10 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SOIL HOLD

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.51 14.02
February 19.54 16.67
March 19.63 20.28
April 19.59 25.86
May 19.69 32.05
June 20.09 35.24
July 20.25 36.21
August 20.37 36.44
September 19.73 33.05
October 19.57 27.59
November 19.54 21.57
December 19.49 14.93
     
Annual Sum or Average 19.75 26.21
Minimum of Months 19.49 14.02
Maximum of Months 20.37 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SOIL WORK

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.50 14.02
February 19.52 16.67
March 19.60 20.28
April 19.53 25.86
May 19.58 32.05
June 19.81 35.24
July 19.89 36.21
August 20.03 36.44
September 19.59 33.05
October 19.51 27.59
November 19.51 21.57
December 19.48 14.93
     
Annual Sum or Average 19.63 26.21
Minimum of Months 19.48 14.02
Maximum of Months 20.03 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STEP DOWN

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.61 14.02
February 19.63 16.67
March 19.71 20.28
April 19.71 25.86
May 19.88 32.05
June 20.54 35.24
July 20.86 36.21
August 21.02 36.44
September 20.20 33.05
October 19.94 27.59
November 19.73 21.57
December 19.56 14.93
     
Annual Sum or Average 20.04 26.21
Minimum of Months 19.56 14.02
Maximum of Months 21.02 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STERILE HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.16 14.02
February 21.26 16.67
March 21.39 20.28
April 21.48 25.86
May 21.74 32.05
June 22.32 35.24
July 22.55 36.21
August 22.68 36.44
September 22.15 33.05
October 21.73 27.59
November 21.51 21.57
December 21.11 14.93
     
Annual Sum or Average 21.76 26.21
Minimum of Months 21.11 14.02
Maximum of Months 22.68 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STERILE STORAGE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.46 14.02
February 21.52 16.67
March 21.62 20.28
April 21.61 25.86
May 21.73 32.05
June 22.24 35.24
July 22.39 36.21
August 22.49 36.44
September 22.09 33.05
October 21.73 27.59
November 21.66 21.57
December 21.45 14.93
     
Annual Sum or Average 21.84 26.21
Minimum of Months 21.45 14.02
Maximum of Months 22.49 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STORAGE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.66 14.02
February 19.87 16.67
March 20.44 20.28
April 21.15 25.86
May 22.06 32.05
June 22.92 35.24
July 23.22 36.21
August 23.17 36.44
September 22.21 33.05
October 21.13 27.59
November 20.19 21.57
December 19.66 14.93
     
Annual Sum or Average 21.32 26.21
Minimum of Months 19.66 14.02
Maximum of Months 23.22 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SUB-STERILE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.18 14.02
February 20.45 16.67
March 20.84 20.28
April 21.26 25.86
May 21.79 32.05
June 22.48 35.24
July 22.86 36.21
August 22.85 36.44
September 22.07 33.05
October 21.48 27.59
November 20.88 21.57
December 20.09 14.93
     
Annual Sum or Average 21.44 26.21
Minimum of Months 20.09 14.02
Maximum of Months 22.86 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 UTILITY HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.80 14.02
February 20.02 16.67
March 20.52 20.28
April 21.26 25.86
May 22.00 32.05
June 22.80 35.24
July 23.14 36.21
August 23.10 36.44
September 22.20 33.05
October 21.23 27.59
November 20.40 21.57
December 19.80 14.93
     
Annual Sum or Average 21.36 26.21
Minimum of Months 19.80 14.02
Maximum of Months 23.14 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.85 14.02
February 21.00 16.67
March 21.22 20.28
April 21.43 25.86
May 21.77 32.05
June 22.37 35.24
July 22.60 36.21
August 22.68 36.44
September 22.09 33.05
October 21.60 27.59
November 21.26 21.57
December 20.80 14.93
     
Annual Sum or Average 21.64 26.21
Minimum of Months 20.80 14.02
Maximum of Months 22.68 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 UTILITY ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.09 14.02
February 20.34 16.67
March 20.78 20.28
April 21.31 25.86
May 21.93 32.05
June 22.64 35.24
July 22.98 36.21
August 22.97 36.44
September 22.21 33.05
October 21.52 27.59
November 20.79 21.57
December 20.05 14.93
     
Annual Sum or Average 21.47 26.21
Minimum of Months 20.05 14.02
Maximum of Months 22.98 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 VESTIBULE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.43 14.02
February 19.28 16.67
March 20.75 20.28
April 22.82 25.86
May 25.41 32.05
June 27.37 35.24
July 27.45 36.21
August 28.31 36.44
September 26.06 33.05
October 23.63 27.59
November 21.48 21.57
December 18.56 14.93
     
Annual Sum or Average 23.32 26.21
Minimum of Months 18.43 14.02
Maximum of Months 28.31 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 CONFERENCE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.71 14.02
February 20.80 16.67
March 20.94 20.28
April 21.10 25.86
May 21.65 32.05
June 22.19 35.24
July 22.38 36.21
August 22.69 36.44
September 22.05 33.05
October 21.56 27.59
November 21.06 21.57
December 20.64 14.93
     
Annual Sum or Average 21.48 26.21
Minimum of Months 20.64 14.02
Maximum of Months 22.69 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.57 14.02
February 19.56 16.67
March 19.60 20.28
April 19.53 25.86
May 19.57 32.05
June 19.66 35.24
July 19.60 36.21
August 19.78 36.44
September 19.58 33.05
October 19.52 27.59
November 19.50 21.57
December 19.56 14.93
     
Annual Sum or Average 19.59 26.21
Minimum of Months 19.50 14.02
Maximum of Months 19.78 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 DICTATION

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.29 14.02
February 21.31 16.67
March 21.38 20.28
April 21.29 25.86
May 21.42 32.05
June 21.74 35.24
July 21.74 36.21
August 22.00 36.44
September 21.59 33.05
October 21.38 27.59
November 21.31 21.57
December 21.28 14.93
     
Annual Sum or Average 21.48 26.21
Minimum of Months 21.28 14.02
Maximum of Months 22.00 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.50 14.02
February 19.52 16.67
March 19.61 20.28
April 19.57 25.86
May 19.72 32.05
June 20.08 35.24
July 20.08 36.21
August 20.37 36.44
September 19.86 33.05
October 19.59 27.59
November 19.50 21.57
December 19.49 14.93
     
Annual Sum or Average 19.74 26.21
Minimum of Months 19.49 14.02
Maximum of Months 20.37 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.83 14.02
February 19.80 16.67
March 19.81 20.28
April 19.72 25.86
May 19.88 32.05
June 20.29 35.24
July 20.31 36.21
August 20.69 36.44
September 20.13 33.05
October 19.84 27.59
November 19.73 21.57
December 19.80 14.93
     
Annual Sum or Average 19.99 26.21
Minimum of Months 19.72 14.02
Maximum of Months 20.69 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 3

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.76 14.02
February 19.72 16.67
March 19.73 20.28
April 19.65 25.86
May 19.77 32.05
June 20.12 35.24
July 20.12 36.21
August 20.49 36.44
September 19.97 33.05
October 19.74 27.59
November 19.66 21.57
December 19.73 14.93
     
Annual Sum or Average 19.87 26.21
Minimum of Months 19.65 14.02
Maximum of Months 20.49 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 4

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.73 14.02
February 19.68 16.67
March 19.69 20.28
April 19.64 25.86
May 19.79 32.05
June 20.17 35.24
July 20.23 36.21
August 20.63 36.44
September 20.13 33.05
October 19.93 27.59
November 19.76 21.57
December 19.69 14.93
     
Annual Sum or Average 19.93 26.21
Minimum of Months 19.64 14.02
Maximum of Months 20.63 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 5

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.50 14.02
February 19.52 16.67
March 19.61 20.28
April 19.58 25.86
May 19.75 32.05
June 20.17 35.24
July 20.25 36.21
August 20.49 36.44
September 19.82 33.05
October 19.56 27.59
November 19.50 21.57
December 19.49 14.93
     
Annual Sum or Average 19.77 26.21
Minimum of Months 19.49 14.02
Maximum of Months 20.49 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 6

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.54 14.02
February 19.55 16.67
March 19.65 20.28
April 19.64 25.86
May 19.87 32.05
June 20.38 35.24
July 20.41 36.21
August 20.64 36.44
September 19.91 33.05
October 19.61 27.59
November 19.53 21.57
December 19.52 14.93
     
Annual Sum or Average 19.86 26.21
Minimum of Months 19.52 14.02
Maximum of Months 20.64 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 7

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.68 14.02
February 19.68 16.67
March 19.73 20.28
April 19.67 25.86
May 19.83 32.05
June 20.25 35.24
July 20.23 36.21
August 20.50 36.44
September 19.89 33.05
October 19.64 27.59
November 19.59 21.57
December 19.67 14.93
     
Annual Sum or Average 19.87 26.21
Minimum of Months 19.59 14.02
Maximum of Months 20.50 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 8

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.54 14.02
February 19.56 16.67
March 19.65 20.28
April 19.64 25.86
May 19.85 32.05
June 20.36 35.24
July 20.39 36.21
August 20.61 36.44
September 19.90 33.05
October 19.60 27.59
November 19.53 21.57
December 19.54 14.93
     
Annual Sum or Average 19.85 26.21
Minimum of Months 19.53 14.02
Maximum of Months 20.61 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 9

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.77 14.02
February 19.78 16.67
March 19.84 20.28
April 19.78 25.86
May 20.00 32.05
June 20.50 35.24
July 20.51 36.21
August 20.78 36.44
September 20.09 33.05
October 19.75 27.59
November 19.69 21.57
December 19.76 14.93
     
Annual Sum or Average 20.02 26.21
Minimum of Months 19.69 14.02
Maximum of Months 20.78 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.87 14.02
February 20.98 16.67
March 21.08 20.28
April 21.13 25.86
May 21.50 32.05
June 21.94 35.24
July 22.01 36.21
August 22.32 36.44
September 21.80 33.05
October 21.42 27.59
November 21.12 21.57
December 20.85 14.93
     
Annual Sum or Average 21.42 26.21
Minimum of Months 20.85 14.02
Maximum of Months 22.32 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.99 14.02
February 21.04 16.67
March 21.09 20.28
April 21.07 25.86
May 21.36 32.05
June 21.76 35.24
July 21.81 36.21
August 22.14 36.44
September 21.67 33.05
October 21.37 27.59
November 21.16 21.57
December 20.96 14.93
     
Annual Sum or Average 21.37 26.21
Minimum of Months 20.96 14.02
Maximum of Months 22.14 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 3

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 14.02
February 20.96 16.67
March 21.00 20.28
April 20.95 25.86
May 21.17 32.05
June 21.55 35.24
July 21.58 36.21
August 21.91 36.44
September 21.49 33.05
October 21.26 27.59
November 21.09 21.57
December 20.89 14.93
     
Annual Sum or Average 21.23 26.21
Minimum of Months 20.89 14.02
Maximum of Months 21.91 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 4

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.71 14.02
February 20.86 16.67
March 21.06 20.28
April 21.19 25.86
May 21.56 32.05
June 22.01 35.24
July 22.04 36.21
August 22.22 36.44
September 21.62 33.05
October 21.17 27.59
November 20.92 21.57
December 20.76 14.93
     
Annual Sum or Average 21.35 26.21
Minimum of Months 20.71 14.02
Maximum of Months 22.22 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 5

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.77 14.02
February 20.94 16.67
March 21.16 20.28
April 21.30 25.86
May 21.69 32.05
June 22.14 35.24
July 22.19 36.21
August 22.35 36.44
September 21.76 33.05
October 21.29 27.59
November 21.02 21.57
December 20.83 14.93
     
Annual Sum or Average 21.46 26.21
Minimum of Months 20.77 14.02
Maximum of Months 22.35 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 6

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.71 14.02
February 20.89 16.67
March 21.11 20.28
April 21.25 25.86
May 21.66 32.05
June 22.12 35.24
July 22.17 36.21
August 22.33 36.44
September 21.73 33.05
October 21.25 27.59
November 20.96 21.57
December 20.78 14.93
     
Annual Sum or Average 21.42 26.21
Minimum of Months 20.71 14.02
Maximum of Months 22.33 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 JANITOR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.30 14.02
February 20.54 16.67
March 20.89 20.28
April 21.27 25.86
May 22.05 32.05
June 22.63 35.24
July 22.74 36.21
August 22.87 36.44
September 22.07 33.05
October 21.37 27.59
November 20.76 21.57
December 20.30 14.93
     
Annual Sum or Average 21.49 26.21
Minimum of Months 20.30 14.02
Maximum of Months 22.87 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 LOUNGE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.52 14.02
February 21.55 16.67
March 21.61 20.28
April 21.55 25.86
May 21.70 32.05
June 22.04 35.24
July 22.07 36.21
August 22.32 36.44
September 21.83 33.05
October 21.60 27.59
November 21.53 21.57
December 21.52 14.93
     
Annual Sum or Average 21.74 26.21
Minimum of Months 21.52 14.02
Maximum of Months 22.32 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 NURSE STATION 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.55 14.02
February 21.63 16.67
March 21.74 20.28
April 21.75 25.86
May 21.98 32.05
June 22.38 35.24
July 22.45 36.21
August 22.66 36.44
September 22.08 33.05
October 21.75 27.59
November 21.62 21.57
December 21.57 14.93
     
Annual Sum or Average 21.93 26.21
Minimum of Months 21.55 14.02
Maximum of Months 22.66 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 NURSE STATION 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.56 14.02
February 21.67 16.67
March 21.79 20.28
April 21.82 25.86
May 22.07 32.05
June 22.49 35.24
July 22.56 36.21
August 22.75 36.44
September 22.17 33.05
October 21.80 27.59
November 21.66 21.57
December 21.61 14.93
     
Annual Sum or Average 22.00 26.21
Minimum of Months 21.56 14.02
Maximum of Months 22.75 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 OFFICE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.33 14.02
February 20.61 16.67
March 20.92 20.28
April 21.31 25.86
May 21.92 32.05
June 22.44 35.24
July 22.68 36.21
August 22.78 36.44
September 22.06 33.05
October 21.47 27.59
November 20.86 21.57
December 20.25 14.93
     
Annual Sum or Average 21.47 26.21
Minimum of Months 20.25 14.02
Maximum of Months 22.78 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 OFFICE HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.83 14.02
February 21.01 16.67
March 21.20 20.28
April 21.39 25.86
May 21.78 32.05
June 22.19 35.24
July 22.30 36.21
August 22.46 36.44
September 21.91 33.05
October 21.48 27.59
November 21.12 21.57
December 20.82 14.93
     
Annual Sum or Average 21.54 26.21
Minimum of Months 20.82 14.02
Maximum of Months 22.46 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 RECEPTION

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.03 14.02
February 21.18 16.67
March 21.36 20.28
April 21.49 25.86
May 22.06 32.05
June 22.60 35.24
July 22.76 36.21
August 23.03 36.44
September 22.39 33.05
October 21.87 27.59
November 21.41 21.57
December 21.01 14.93
     
Annual Sum or Average 21.85 26.21
Minimum of Months 21.01 14.02
Maximum of Months 23.03 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 RECEPTION HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.36 14.02
February 21.43 16.67
March 21.49 20.28
April 21.46 25.86
May 21.70 32.05
June 22.07 35.24
July 22.12 36.21
August 22.36 36.44
September 21.90 33.05
October 21.60 27.59
November 21.45 21.57
December 21.36 14.93
     
Annual Sum or Average 21.69 26.21
Minimum of Months 21.36 14.02
Maximum of Months 22.36 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.04 14.02
February 17.89 16.67
March 17.68 20.28
April 17.50 25.86
May 17.77 32.05
June 18.32 35.24
July 18.45 36.21
August 18.75 36.44
September 18.06 33.05
October 17.66 27.59
November 17.65 21.57
December 17.96 14.93
     
Annual Sum or Average 17.98 26.21
Minimum of Months 17.50 14.02
Maximum of Months 18.75 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 SCHEDULING 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 14.02
February 21.76 16.67
March 21.84 20.28
April 21.82 25.86
May 21.98 32.05
June 22.32 35.24
July 22.39 36.21
August 22.58 36.44
September 22.11 33.05
October 21.84 27.59
November 21.75 21.57
December 21.72 14.93
     
Annual Sum or Average 21.99 26.21
Minimum of Months 21.70 14.02
Maximum of Months 22.58 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 SCHEDULING 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.67 14.02
February 21.72 16.67
March 21.79 20.28
April 21.77 25.86
May 21.98 32.05
June 22.34 35.24
July 22.41 36.21
August 22.64 36.44
September 22.14 33.05
October 21.85 27.59
November 21.73 21.57
December 21.67 14.93
     
Annual Sum or Average 21.98 26.21
Minimum of Months 21.67 14.02
Maximum of Months 22.64 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 STORAGE 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.73 14.02
February 20.76 16.67
March 20.80 20.28
April 20.76 25.86
May 20.94 32.05
June 21.30 35.24
July 21.32 36.21
August 21.61 36.44
September 21.24 33.05
October 21.01 27.59
November 20.86 21.57
December 20.72 14.93
     
Annual Sum or Average 21.01 26.21
Minimum of Months 20.72 14.02
Maximum of Months 21.61 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 STORAGE 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 14.02
February 20.94 16.67
March 21.12 20.28
April 21.24 25.86
May 21.60 32.05
June 22.04 35.24
July 22.08 36.21
August 22.25 36.44
September 21.69 33.05
October 21.25 27.59
November 21.00 21.57
December 20.84 14.93
     
Annual Sum or Average 21.41 26.21
Minimum of Months 20.80 14.02
Maximum of Months 22.25 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 STORAGE 3

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.83 14.02
February 21.01 16.67
March 21.22 20.28
April 21.36 25.86
May 21.74 32.05
June 22.18 35.24
July 22.23 36.21
August 22.37 36.44
September 21.82 33.05
October 21.35 27.59
November 21.08 21.57
December 20.91 14.93
     
Annual Sum or Average 21.51 26.21
Minimum of Months 20.83 14.02
Maximum of Months 22.37 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 UTILITY

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.03 14.02
February 20.26 16.67
March 20.60 20.28
April 21.10 25.86
May 21.72 32.05
June 22.20 35.24
July 22.42 36.21
August 22.49 36.44
September 21.83 33.05
October 21.23 27.59
November 20.47 21.57
December 19.97 14.93
     
Annual Sum or Average 21.20 26.21
Minimum of Months 19.97 14.02
Maximum of Months 22.49 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 WORK

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.28 14.02
February 21.49 16.67
March 21.71 20.28
April 21.91 25.86
May 22.33 32.05
June 22.80 35.24
July 22.94 36.21
August 23.08 36.44
September 22.43 33.05
October 21.95 27.59
November 21.60 21.57
December 21.34 14.93
     
Annual Sum or Average 22.07 26.21
Minimum of Months 21.28 14.02
Maximum of Months 23.08 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 WORK HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.42 14.02
February 21.55 16.67
March 21.68 20.28
April 21.74 25.86
May 22.04 32.05
June 22.41 35.24
July 22.49 36.21
August 22.67 36.44
September 22.18 33.05
October 21.82 27.59
November 21.60 21.57
December 21.46 14.93
     
Annual Sum or Average 21.92 26.21
Minimum of Months 21.42 14.02
Maximum of Months 22.67 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 WORK TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.55 14.02
February 19.59 16.67
March 19.68 20.28
April 19.67 25.86
May 19.89 32.05
June 20.20 35.24
July 20.19 36.21
August 20.40 36.44
September 19.91 33.05
October 19.67 27.59
November 19.54 21.57
December 19.53 14.93
     
Annual Sum or Average 19.82 26.21
Minimum of Months 19.53 14.02
Maximum of Months 20.40 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 X-RAY

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.59 14.02
February 22.52 16.67
March 22.41 20.28
April 22.31 25.86
May 22.44 32.05
June 22.90 35.24
July 23.01 36.21
August 23.25 36.44
September 22.63 33.05
October 22.32 27.59
November 22.35 21.57
December 22.58 14.93
     
Annual Sum or Average 22.61 26.21
Minimum of Months 22.31 14.02
Maximum of Months 23.25 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 DRESSING ROOM

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.67 14.02
February 20.78 16.67
March 20.92 20.28
April 20.95 25.86
May 21.23 32.05
June 21.59 35.24
July 21.61 36.21
August 21.86 36.44
September 21.26 33.05
October 20.92 27.59
November 20.73 21.57
December 20.67 14.93
     
Annual Sum or Average 21.10 26.21
Minimum of Months 20.67 14.02
Maximum of Months 21.86 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 14.02
February 20.82 16.67
March 21.16 20.28
April 21.53 25.86
May 22.24 32.05
June 22.78 35.24
July 22.93 36.21
August 23.12 36.44
September 22.30 33.05
October 21.59 27.59
November 20.97 21.57
December 20.52 14.93
     
Annual Sum or Average 21.71 26.21
Minimum of Months 20.47 14.02
Maximum of Months 23.12 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 HUMID

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.77 14.02
February 20.88 16.67
March 21.02 20.28
April 21.06 25.86
May 21.36 32.05
June 21.75 35.24
July 21.78 36.21
August 22.03 36.44
September 21.41 33.05
October 21.04 27.59
November 20.83 21.57
December 20.77 14.93
     
Annual Sum or Average 21.23 26.21
Minimum of Months 20.77 14.02
Maximum of Months 22.03 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 JANITOR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.80 14.02
February 20.07 16.67
March 20.48 20.28
April 21.05 25.86
May 22.07 32.05
June 22.65 35.24
July 22.78 36.21
August 22.95 36.44
September 22.05 33.05
October 21.20 27.59
November 20.32 21.57
December 19.80 14.93
     
Annual Sum or Average 21.28 26.21
Minimum of Months 19.80 14.02
Maximum of Months 22.95 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 LOCKER

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 14.02
February 20.97 16.67
March 21.18 20.28
April 21.32 25.86
May 21.76 32.05
June 22.26 35.24
July 22.35 36.21
August 22.56 36.44
September 21.78 33.05
October 21.28 27.59
November 20.96 21.57
December 20.83 14.93
     
Annual Sum or Average 21.51 26.21
Minimum of Months 20.81 14.02
Maximum of Months 22.56 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 LOUNGE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.82 14.02
February 21.02 16.67
March 21.27 20.28
April 21.49 25.86
May 22.07 32.05
June 22.65 35.24
July 22.78 36.21
August 22.98 36.44
September 22.11 33.05
October 21.49 27.59
November 21.05 21.57
December 20.85 14.93
     
Annual Sum or Average 21.72 26.21
Minimum of Months 20.82 14.02
Maximum of Months 22.98 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 14.02
February 19.50 16.67
March 19.58 20.28
April 19.54 25.86
May 19.66 32.05
June 19.97 35.24
July 19.98 36.21
August 20.18 36.44
September 19.65 33.05
October 19.50 27.59
November 19.48 21.57
December 19.47 14.93
     
Annual Sum or Average 19.67 26.21
Minimum of Months 19.47 14.02
Maximum of Months 20.18 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 MECHANICAL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.43 14.02
February 21.61 16.67
March 21.70 20.28
April 22.08 25.86
May 22.78 32.05
June 23.25 35.24
July 23.54 36.21
August 23.61 36.44
September 22.89 33.05
October 22.25 27.59
November 21.68 21.57
December 21.38 14.93
     
Annual Sum or Average 22.36 26.21
Minimum of Months 21.38 14.02
Maximum of Months 23.61 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.45 14.02
February 20.74 16.67
March 21.00 20.28
April 21.33 25.86
May 21.92 32.05
June 22.43 35.24
July 22.61 36.21
August 22.76 36.44
September 21.97 33.05
October 21.37 27.59
November 20.84 21.57
December 20.43 14.93
     
Annual Sum or Average 21.49 26.21
Minimum of Months 20.43 14.02
Maximum of Months 22.76 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 OFFICE

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.51 14.02
February 20.79 16.67
March 21.11 20.28
April 21.45 25.86
May 22.13 32.05
June 22.72 35.24
July 22.87 36.21
August 23.06 36.44
September 22.16 33.05
October 21.45 27.59
November 20.89 21.57
December 20.55 14.93
     
Annual Sum or Average 21.65 26.21
Minimum of Months 20.51 14.02
Maximum of Months 23.06 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 OFFICE HALL

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.72 14.02
February 20.98 16.67
March 21.24 20.28
April 21.51 25.86
May 22.10 32.05
June 22.63 35.24
July 22.76 36.21
August 23.00 36.44
September 22.22 33.05
October 21.60 27.59
November 21.09 21.57
December 20.75 14.93
     
Annual Sum or Average 21.72 26.21
Minimum of Months 20.72 14.02
Maximum of Months 23.00 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 OFFICE TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.51 14.02
February 19.55 16.67
March 19.65 20.28
April 19.65 25.86
May 19.89 32.05
June 20.21 35.24
July 20.21 36.21
August 20.46 36.44
September 19.90 33.05
October 19.65 27.59
November 19.52 21.57
December 19.49 14.93
     
Annual Sum or Average 19.81 26.21
Minimum of Months 19.49 14.02
Maximum of Months 20.46 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.56 14.02
February 19.56 16.67
March 19.61 20.28
April 19.56 25.86
May 19.70 32.05
June 20.09 35.24
July 20.14 36.21
August 20.53 36.44
September 19.99 33.05
October 19.74 27.59
November 19.61 21.57
December 19.54 14.93
     
Annual Sum or Average 19.80 26.21
Minimum of Months 19.54 14.02
Maximum of Months 20.53 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.55 14.02
February 19.56 16.67
March 19.64 20.28
April 19.58 25.86
May 19.69 32.05
June 20.03 35.24
July 20.02 36.21
August 20.31 36.44
September 19.77 33.05
October 19.56 27.59
November 19.52 21.57
December 19.54 14.93
     
Annual Sum or Average 19.73 26.21
Minimum of Months 19.52 14.02
Maximum of Months 20.31 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.52 14.02
February 19.53 16.67
March 19.60 20.28
April 19.54 25.86
May 19.59 32.05
June 19.74 35.24
July 19.70 36.21
August 19.89 36.44
September 19.58 33.05
October 19.51 27.59
November 19.49 21.57
December 19.51 14.93
     
Annual Sum or Average 19.60 26.21
Minimum of Months 19.49 14.02
Maximum of Months 19.89 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 STORAGE 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.67 14.02
February 19.70 16.67
March 19.78 20.28
April 19.76 25.86
May 19.96 32.05
June 20.35 35.24
July 20.36 36.21
August 20.62 36.44
September 20.02 33.05
October 19.73 27.59
November 19.62 21.57
December 19.65 14.93
     
Annual Sum or Average 19.94 26.21
Minimum of Months 19.62 14.02
Maximum of Months 20.62 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 STORAGE 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.46 14.02
February 20.74 16.67
March 21.01 20.28
April 21.27 25.86
May 21.81 32.05
June 22.32 35.24
July 22.43 36.21
August 22.62 36.44
September 21.83 33.05
October 21.26 27.59
November 20.81 21.57
December 20.50 14.93
     
Annual Sum or Average 21.43 26.21
Minimum of Months 20.46 14.02
Maximum of Months 22.62 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 TREATMENT

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.59 14.02
February 19.59 16.67
March 19.67 20.28
April 19.61 25.86
May 19.74 32.05
June 20.11 35.24
July 20.10 36.21
August 20.41 36.44
September 19.83 33.05
October 19.59 27.59
November 19.55 21.57
December 19.58 14.93
     
Annual Sum or Average 19.78 26.21
Minimum of Months 19.55 14.02
Maximum of Months 20.41 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.65 14.02
February 20.85 16.67
March 21.06 20.28
April 21.32 25.86
May 22.01 32.05
June 22.57 35.24
July 22.74 36.21
August 23.04 36.44
September 22.28 33.05
October 21.63 27.59
November 21.04 21.57
December 20.61 14.93
     
Annual Sum or Average 21.65 26.21
Minimum of Months 20.61 14.02
Maximum of Months 23.04 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.64 14.02
February 20.87 16.67
March 21.11 20.28
April 21.44 25.86
May 22.26 32.05
June 22.84 35.24
July 23.06 36.21
August 23.33 36.44
September 22.58 33.05
October 21.86 27.59
November 21.16 21.57
December 20.61 14.93
     
Annual Sum or Average 21.82 26.21
Minimum of Months 20.61 14.02
Maximum of Months 23.33 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 UTILITY

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.32 14.02
February 20.56 16.67
March 20.80 20.28
April 21.02 25.86
May 21.46 32.05
June 21.86 35.24
July 21.94 36.21
August 22.12 36.44
September 21.49 33.05
October 21.02 27.59
November 20.61 21.57
December 20.33 14.93
     
Annual Sum or Average 21.13 26.21
Minimum of Months 20.32 14.02
Maximum of Months 22.12 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 WORK

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.15 14.02
February 20.42 16.67
March 20.72 20.28
April 21.17 25.86
May 21.92 32.05
June 22.48 35.24
July 22.74 36.21
August 22.89 36.44
September 22.03 33.05
October 21.30 27.59
November 20.60 21.57
December 20.06 14.93
     
Annual Sum or Average 21.38 26.21
Minimum of Months 20.06 14.02
Maximum of Months 22.89 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: NE STAIR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.59 14.02
February 19.80 16.67
March 20.16 20.28
April 20.86 25.86
May 21.97 32.05
June 22.70 35.24
July 22.96 36.21
August 23.00 36.44
September 22.04 33.05
October 21.00 27.59
November 20.09 21.57
December 19.60 14.93
     
Annual Sum or Average 21.16 26.21
Minimum of Months 19.59 14.02
Maximum of Months 23.00 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: NW ELEVATOR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.10 14.02
February 20.37 16.67
March 20.71 20.28
April 21.15 25.86
May 22.07 32.05
June 22.62 35.24
July 22.78 36.21
August 22.92 36.44
September 22.24 33.05
October 21.46 27.59
November 20.61 21.57
December 20.08 14.93
     
Annual Sum or Average 21.43 26.21
Minimum of Months 20.08 14.02
Maximum of Months 22.92 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: NW STAIR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.58 14.02
February 19.78 16.67
March 20.19 20.28
April 20.96 25.86
May 22.12 32.05
June 22.82 35.24
July 23.04 36.21
August 23.07 36.44
September 22.11 33.05
October 21.00 27.59
November 20.02 21.57
December 19.60 14.93
     
Annual Sum or Average 21.20 26.21
Minimum of Months 19.58 14.02
Maximum of Months 23.07 36.44



Table of Contents

Report: MONTHLY INDOOR TEMP

For: SW STAIR

Timestamp: 2015-09-13 14:22:44

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.44 14.02
February 20.63 16.67
March 20.90 20.28
April 21.29 25.86
May 22.19 32.05
June 22.78 35.24
July 23.00 36.21
August 23.23 36.44
September 22.57 33.05
October 21.85 27.59
November 21.01 21.57
December 20.39 14.93
     
Annual Sum or Average 21.70 26.21
Minimum of Months 20.39 14.02
Maximum of Months 23.23 36.44



Table of Contents

Report: OVERALL HVAC AIR SYSTEM LOADS

For: AHU-1

Timestamp: 2015-09-13 14:22:44

AIR SYSTEM TOTAL HEATING ENERGY [J] AIR SYSTEM TOTAL COOLING ENERGY [J]
January 0.121402E+12 0.157021E+12
February 0.109071E+12 0.157950E+12
March 0.110699E+12 0.199987E+12
April 0.104033E+12 0.229072E+12
May 0.999228E+11 0.274394E+12
June 0.108117E+12 0.297236E+12
July 0.136308E+12 0.310227E+12
August 0.114977E+12 0.313286E+12
September 0.906439E+11 0.279350E+12
October 0.101258E+12 0.247694E+12
November 0.110730E+12 0.195657E+12
December 0.104880E+12 0.174220E+12
     
Annual Sum or Average 0.131204E+13 0.283609E+13
Minimum of Months 0.906439E+11 0.157021E+12
Maximum of Months 0.136308E+12 0.313286E+12



Table of Contents

Report: OVERALL HVAC AIR SYSTEM LOADS

For: AHU-2

Timestamp: 2015-09-13 14:22:44

AIR SYSTEM TOTAL HEATING ENERGY [J] AIR SYSTEM TOTAL COOLING ENERGY [J]
January 0.591689E+11 0.134144E+12
February 0.520613E+11 0.148680E+12
March 0.595482E+11 0.203620E+12
April 0.565930E+11 0.247378E+12
May 0.520017E+11 0.305138E+12
June 0.492922E+11 0.330543E+12
July 0.491549E+11 0.333341E+12
August 0.508303E+11 0.351248E+12
September 0.492879E+11 0.312482E+12
October 0.546284E+11 0.270103E+12
November 0.557977E+11 0.207651E+12
December 0.606197E+11 0.150996E+12
     
Annual Sum or Average 0.648984E+12 0.299532E+13
Minimum of Months 0.491549E+11 0.134144E+12
Maximum of Months 0.606197E+11 0.351248E+12



Table of Contents

Report: OVERALL HVAC SYSTEM ENERGY

For: Meter

Timestamp: 2015-09-13 14:22:44

ELECTRICITY:HVAC [J] HEATING:GAS [J]
January 0.225228E+12 0.478846E+11
February 0.214263E+12 0.417109E+11
March 0.248333E+12 0.444106E+11
April 0.267809E+12 0.412924E+11
May 0.308404E+12 0.380354E+11
June 0.351376E+12 0.264548E+11
July 0.396823E+12 0.189890E+11
August 0.382088E+12 0.235049E+11
September 0.306461E+12 0.349502E+11
October 0.282093E+12 0.377484E+11
November 0.252340E+12 0.360649E+11
December 0.209455E+12 0.596485E+11
     
Annual Sum or Average 0.344467E+13 0.450695E+12
Minimum of Months 0.209455E+12 0.189890E+11
Maximum of Months 0.396823E+12 0.596485E+11



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-13 14:22:44

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.441035E+12 285404.380 24-JAN-17:00 36851.394 111837.204 24474.947 30234.374 58618.290 8375.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.409485E+12 282647.013 27-FEB-14:00 36851.394 111837.204 27942.109 7646.233 98027.355 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.472695E+12 290539.686 29-MAR-14:00 36851.394 111837.204 32789.222 20536.259 79855.554 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.475104E+12 381229.328 21-APR-15:00 36851.394 111837.204 37245.442 39544.860 125333.723 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.526649E+12 407023.562 18-MAY-15:20 36851.394 111837.204 52428.161 30396.556 140442.968 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.565864E+12 420973.220 13-JUN-16:00 36851.394 111837.204 53180.559 30591.505 140442.968 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.606617E+12 427411.445 20-JUL-15:00 36851.394 111837.204 53381.376 29272.871 148426.296 0.000 8.069 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.605357E+12 420992.625 03-AUG-15:09 36851.394 111837.204 53381.376 28800.997 151189.075 0.000 8.069 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.514094E+12 404666.984 20-SEP-15:20 36851.394 111837.204 53290.474 30106.492 141127.052 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.497106E+12 381499.748 10-OCT-13:39 36851.394 111837.204 37881.320 42359.076 130803.855 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.462912E+12 318558.505 03-NOV-14:00 36851.394 111837.204 33753.523 20229.652 93304.832 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.422101E+12 278865.318 13-DEC-17:10 36851.394 111837.204 25016.802 30124.790 50904.992 8375.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.599902E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.409485E+12 278865.318   36851.394 111837.204 24474.947 7646.233 50904.992 0.000 8.069 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.606617E+12 427411.445   36851.394 111837.204 53381.376 42359.076 151189.075 8375.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS

For: Meter

Timestamp: 2015-09-13 14:22:44

ELECTRICITY:BUILDING [J] ELECTRICITY:BUILDING {Maximum}[W] ELECTRICITY:BUILDING {TIMESTAMP} GAS:BUILDING [J] GAS:BUILDING {Maximum}[W] GAS:BUILDING {TIMESTAMP}
January 0.202389E+12 148688.60 02-JAN-09:09 0.158619E+11 9905.77 02-JAN-06:10
February 0.183577E+12 148688.60 01-FEB-09:09 0.143713E+11 9905.77 01-FEB-06:10
March 0.212124E+12 148688.60 01-MAR-09:09 0.163897E+11 9905.77 01-MAR-06:10
April 0.196088E+12 148688.60 03-APR-08:09 0.153698E+11 9905.77 03-APR-05:10
May 0.207257E+12 148688.60 01-MAY-08:09 0.161258E+11 9905.77 01-MAY-05:10
June 0.204231E+12 148688.60 01-JUN-08:09 0.158049E+11 9905.77 01-JUN-05:10
July 0.199114E+12 148688.60 03-JUL-08:09 0.156907E+11 9905.77 03-JUL-05:10
August 0.212124E+12 148688.60 01-AUG-08:09 0.163897E+11 9905.77 01-AUG-05:10
September 0.196088E+12 148688.60 01-SEP-08:09 0.153698E+11 9905.77 01-SEP-05:10
October 0.202389E+12 148688.60 02-OCT-08:09 0.158619E+11 9905.77 02-OCT-05:10
November 0.197772E+12 148688.60 01-NOV-08:09 0.154482E+11 9905.77 01-NOV-05:10
December 0.199114E+12 148688.60 01-DEC-09:09 0.156907E+11 9905.77 01-DEC-06:10
             
Annual Sum or Average 0.241227E+13     0.188374E+12    
Minimum of Months 0.183577E+12 148688.60   0.143713E+11 9905.77  
Maximum of Months 0.212124E+12 148688.60   0.163897E+11 9905.77  



Table of Contents

Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY

For: Meter

Timestamp: 2015-09-13 14:22:44

INTERIORLIGHTS:ELECTRICITY [J] TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] EXTERIORLIGHTS:ELECTRICITY [J] GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [Invalid/Undefined] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] COGENERATION:ELECTRICITY [Invalid/Undefined]
January 0.465507E+11 0.00 0.125022E+11 0.155839E+12 0.00 0.461729E+11 0.915327E+09 0.703560E+11 0.789158E+11 0.00 0.297836E+11 0.00 0.00 0.00
February 0.423275E+11 0.00 0.108188E+11 0.141249E+12 0.00 0.424313E+11 0.826929E+09 0.591743E+11 0.827611E+11 0.00 0.298961E+11 0.00 0.00 0.00
March 0.500442E+11 0.00 0.113213E+11 0.162080E+12 0.00 0.477144E+11 0.916198E+09 0.639582E+11 0.109357E+12 0.00 0.273042E+11 0.00 0.00 0.00
April 0.451430E+11 0.00 0.103214E+11 0.150945E+12 0.00 0.475962E+11 0.886151E+09 0.592276E+11 0.136120E+12 0.00 0.248653E+11 0.00 0.00 0.00
May 0.482974E+11 0.00 0.100902E+11 0.158960E+12 0.00 0.548969E+11 0.898093E+09 0.503840E+11 0.182544E+12 0.00 0.205790E+11 0.00 0.00 0.00
June 0.480542E+11 0.00 0.945705E+10 0.156177E+12 0.00 0.622554E+11 0.800046E+09 0.524313E+11 0.210930E+12 0.00 0.257593E+11 0.00 0.00 0.00
July 0.453862E+11 0.00 0.992940E+10 0.153727E+12 0.00 0.645823E+11 0.750477E+09 0.665687E+11 0.222425E+12 0.00 0.432474E+11 0.00 0.00 0.00
August 0.500442E+11 0.00 0.103967E+11 0.162080E+12 0.00 0.685293E+11 0.747935E+09 0.562488E+11 0.230760E+12 0.00 0.265500E+11 0.00 0.00 0.00
September 0.451430E+11 0.00 0.106832E+11 0.150945E+12 0.00 0.568643E+11 0.862358E+09 0.435557E+11 0.190236E+12 0.00 0.158044E+11 0.00 0.00 0.00
October 0.465507E+11 0.00 0.117082E+11 0.155839E+12 0.00 0.512854E+11 0.914423E+09 0.570140E+11 0.152126E+12 0.00 0.216685E+11 0.00 0.00 0.00
November 0.457252E+11 0.00 0.119143E+11 0.152047E+12 0.00 0.465971E+11 0.885716E+09 0.651275E+11 0.110639E+12 0.00 0.299760E+11 0.00 0.00 0.00
December 0.453862E+11 0.00 0.126178E+11 0.153727E+12 0.00 0.453136E+11 0.915327E+09 0.596891E+11 0.875974E+11 0.00 0.168544E+11 0.00 0.00 0.00
                             
Annual Sum or Average 0.558652E+12 0.00 0.131761E+12 0.185361E+13 0.00 0.634239E+12 0.103190E+11 0.703735E+12 0.179441E+13 0.00 0.312288E+12 0.00 0.00 0.00
Minimum of Months 0.423275E+11 0.00 0.945705E+10 0.141249E+12 0.00 0.424313E+11 0.747935E+09 0.435557E+11 0.789158E+11 0.00 0.158044E+11 0.00 0.00 0.00
Maximum of Months 0.500442E+11 0.00 0.126178E+11 0.162080E+12 0.00 0.685293E+11 0.916198E+09 0.703560E+11 0.230760E+12 0.00 0.432474E+11 0.00 0.00 0.00



Table of Contents

Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS

For: Meter

Timestamp: 2015-09-13 14:22:44

INTERIOREQUIPMENT:GAS [J] EXTERIOREQUIPMENT:GAS [Invalid/Undefined] HEATING:GAS [J] COOLING:GAS [Invalid/Undefined] WATERSYSTEMS:GAS [J] COGENERATION:GAS [Invalid/Undefined]
January 0.158619E+11 0.00 0.478846E+11 0.00 0.948517E+10 0.00
February 0.143713E+11 0.00 0.417109E+11 0.00 0.841983E+10 0.00
March 0.163897E+11 0.00 0.444106E+11 0.00 0.915376E+10 0.00
April 0.153698E+11 0.00 0.412924E+11 0.00 0.752052E+10 0.00
May 0.161258E+11 0.00 0.380354E+11 0.00 0.706982E+10 0.00
June 0.158049E+11 0.00 0.264548E+11 0.00 0.632077E+10 0.00
July 0.156907E+11 0.00 0.189890E+11 0.00 0.588574E+10 0.00
August 0.163897E+11 0.00 0.235049E+11 0.00 0.655889E+10 0.00
September 0.153698E+11 0.00 0.349502E+11 0.00 0.669376E+10 0.00
October 0.158619E+11 0.00 0.377484E+11 0.00 0.776116E+10 0.00
November 0.154482E+11 0.00 0.360649E+11 0.00 0.846663E+10 0.00
December 0.156907E+11 0.00 0.596485E+11 0.00 0.908487E+10 0.00
             
Annual Sum or Average 0.188374E+12 0.00 0.450695E+12 0.00 0.924209E+11 0.00
Minimum of Months 0.143713E+11 0.00 0.189890E+11 0.00 0.588574E+10 0.00
Maximum of Months 0.163897E+11 0.00 0.596485E+11 0.00 0.948517E+10 0.00



Table of Contents

Report: PEAK ENERGY END-USE - ELECTRICITY

For: Meter

Timestamp: 2015-09-13 14:22:44

INTERIORLIGHTS:ELECTRICITY {Maximum}[W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] FANS:ELECTRICITY {Maximum}[W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum}[W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum}[W] HEATING:ELECTRICITY {TIMESTAMP}
January 36851.39 02-JAN-07:10 0.00 8375.00 01-JAN-00:10 111837.20 02-JAN-09:09 0.00 30651.85 25-JAN-15:09 342.72 01-JAN-08:09 117672.87 02-JAN-05:10
February 36851.39 01-FEB-07:10 0.00 8375.00 01-FEB-00:10 111837.20 01-FEB-09:09 0.00 29450.13 23-FEB-15:30 342.72 01-FEB-00:10 113122.78 21-FEB-05:10
March 36851.39 01-MAR-07:10 0.00 8375.00 01-MAR-00:10 111837.20 01-MAR-09:09 0.00 33024.78 31-MAR-15:30 342.72 01-MAR-00:10 111095.57 06-MAR-05:10
April 36851.39 03-APR-06:10 0.00 8375.00 01-APR-00:10 111837.20 03-APR-08:09 0.00 38219.47 20-APR-15:30 342.72 01-APR-00:10 106298.47 10-APR-04:10
May 36851.39 01-MAY-06:10 0.00 8375.00 01-MAY-00:10 111837.20 01-MAY-08:09 0.00 53368.38 19-MAY-16:30 342.72 01-MAY-00:10 93590.49 15-MAY-04:10
June 36851.39 01-JUN-06:10 0.00 8375.00 01-JUN-00:10 111837.20 01-JUN-08:09 0.00 53381.38 09-JUN-14:20 342.72 01-JUN-00:10 68881.68 26-JUN-04:10
July 36851.39 03-JUL-06:10 0.00 8375.00 01-JUL-00:10 111837.20 03-JUL-08:09 0.00 53381.38 12-JUL-15:20 342.72 01-JUL-00:10 65531.60 05-JUL-04:10
August 36851.39 01-AUG-06:10 0.00 8375.00 01-AUG-00:10 111837.20 01-AUG-08:09 0.00 53381.38 01-AUG-14:39 342.72 01-AUG-00:10 60055.44 06-AUG-14:00
September 36851.39 01-SEP-06:10 0.00 8375.00 01-SEP-00:10 111837.20 01-SEP-08:09 0.00 53367.45 07-SEP-16:10 342.72 01-SEP-00:10 64072.42 05-SEP-04:10
October 36851.39 02-OCT-06:10 0.00 8375.00 01-OCT-00:10 111837.20 02-OCT-08:09 0.00 43292.92 06-OCT-14:00 342.72 01-OCT-07:10 105016.21 30-OCT-04:10
November 36851.39 01-NOV-06:10 0.00 8375.00 01-NOV-00:10 111837.20 01-NOV-08:09 0.00 34203.08 02-NOV-14:30 342.72 01-NOV-00:10 111003.65 20-NOV-05:10
December 36851.39 01-DEC-07:10 0.00 8375.00 01-DEC-00:10 111837.20 01-DEC-09:09 0.00 28671.44 13-DEC-14:00 342.72 01-DEC-00:10 112065.42 11-DEC-05:10
                             
Annual Sum or Average     0.00         0.00            
Minimum of Months 36851.39   0.00 8375.00   111837.20   0.00 28671.44   342.72   60055.44  
Maximum of Months 36851.39   0.00 8375.00   111837.20   0.00 53381.38   342.72   117672.87  



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-13 14:22:44

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.441035E+12 285404.380 24-JAN-17:00 36851.394 111837.204 24474.947 30234.374 58618.290 8375.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.409485E+12 282647.013 27-FEB-14:00 36851.394 111837.204 27942.109 7646.233 98027.355 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.472695E+12 290539.686 29-MAR-14:00 36851.394 111837.204 32789.222 20536.259 79855.554 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.475104E+12 381229.328 21-APR-15:00 36851.394 111837.204 37245.442 39544.860 125333.723 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.526649E+12 407023.562 18-MAY-15:20 36851.394 111837.204 52428.161 30396.556 140442.968 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.565864E+12 420973.220 13-JUN-16:00 36851.394 111837.204 53180.559 30591.505 140442.968 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.606617E+12 427411.445 20-JUL-15:00 36851.394 111837.204 53381.376 29272.871 148426.296 0.000 8.069 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.605357E+12 420992.625 03-AUG-15:09 36851.394 111837.204 53381.376 28800.997 151189.075 0.000 8.069 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.514094E+12 404666.984 20-SEP-15:20 36851.394 111837.204 53290.474 30106.492 141127.052 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.497106E+12 381499.748 10-OCT-13:39 36851.394 111837.204 37881.320 42359.076 130803.855 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.462912E+12 318558.505 03-NOV-14:00 36851.394 111837.204 33753.523 20229.652 93304.832 0.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.422101E+12 278865.318 13-DEC-17:10 36851.394 111837.204 25016.802 30124.790 50904.992 8375.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.599902E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.409485E+12 278865.318   36851.394 111837.204 24474.947 7646.233 50904.992 0.000 8.069 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.606617E+12 427411.445   36851.394 111837.204 53381.376 42359.076 151189.075 8375.000 342.720 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-13 14:22:44

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.732316E+11 81081.054 09-JAN-05:30 0.000 4952.884 0.000 76128.170 1488.000 1488.000 74640.170
February 0.645020E+11 70181.282 09-FEB-06:49 0.000 9905.768 0.000 60275.514 1488.000 1488.000 58787.514
March 0.699540E+11 63347.060 11-MAR-05:30 0.000 2971.730 0.000 60375.330 1488.000 1488.000 58887.330
April 0.641827E+11 67868.889 10-APR-04:40 0.000 4952.884 0.000 62916.004 1488.000 1488.000 61428.004
May 0.612310E+11 59771.781 01-MAY-04:30 0.000 4952.884 0.000 54818.896 1488.000 1488.000 53330.896
June 0.485804E+11 48077.658 05-JUN-04:30 0.000 4952.884 0.000 43124.774 1488.000 1488.000 41636.774
July 0.405655E+11 42954.659 28-JUL-04:30 0.000 4952.884 0.000 38001.775 1488.000 1488.000 36513.775
August 0.464535E+11 46923.663 21-AUG-04:30 0.000 4952.884 0.000 41970.779 1488.000 1488.000 40482.779
September 0.570137E+11 51828.944 25-SEP-04:30 0.000 4952.884 0.000 46876.060 1488.000 1488.000 45388.060
October 0.613715E+11 58929.468 23-OCT-04:19 0.000 4952.884 0.000 53976.584 1488.000 1488.000 52488.584
November 0.599798E+11 63760.275 06-NOV-05:30 0.000 4952.884 0.000 58807.391 1488.000 1488.000 57319.391
December 0.844241E+11 80941.359 30-DEC-06:19 0.000 2971.730 0.000 77969.628 1488.000 1488.000 76481.628
                     
Annual Sum or Average 0.731490E+12     0.000   0.000        
Minimum of Months 0.405655E+11 42954.659   0.000 2971.730 0.000 38001.775 1488.000 1488.000 36513.775
Maximum of Months 0.844241E+11 81081.054   0.000 9905.768 0.000 77969.628 1488.000 1488.000 76481.628