Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:21

Tabular Output Report in Format: HTML

Building: OutPatient HealthCare

Environment: Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2015-09-13 14:22:46


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 6679.35 1755.87 1755.87
Net Site Energy 6679.35 1755.87 1755.87
Total Source Energy 21156.55 5561.65 5561.65
Net Source Energy 21156.55 5561.65 5561.65


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.546
Natural Gas 1.092
District Cooling 1.182
District Heating 3.640
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.158
Fuel Oil #2 1.050
Propane 1.151
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 3804.01
Net Conditioned Building Area 3804.01
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 296.50 745.00 0.00 0.00 0.00 0.00
Cooling 2214.81 0.00 0.00 0.00 0.00 0.00
Interior Lighting 558.65 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 131.78 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1853.61 188.37 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 580.59 0.00 0.00 0.00 0.00 0.00
Pumps 10.92 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 2.16 0.00 0.00 0.00 0.00 0.80
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 96.96 0.00 0.00 0.00 478.84
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 5649.02 1030.34 0.00 0.00 0.00 479.65
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Boiler 0.00 745.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
  Other 296.50 0.00 0.00 0.00 0.00 0.00
Cooling General 2214.81 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 558.65 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 131.78 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 1853.61 188.37 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Fan Energy 539.74 0.00 0.00 0.00 0.00 0.00
  Zone Exhaust Fans 40.85 0.00 0.00 0.00 0.00 0.00
Pumps General 10.92 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 2.16 0.00 0.00 0.00 0.00 0.80
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 96.96 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 478.84
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 181.50 0.00 0.00 0.00 0.00 0.00
HVAC 816.24 221.34 0.00 0.00 0.00 0.13
Other 487.28 49.52 0.00 0.00 0.00 0.00
Total 1485.02 270.86 0.00 0.00 0.00 0.13


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 181.50 0.00 0.00 0.00 0.00 0.00
HVAC 816.24 221.34 0.00 0.00 0.00 0.13
Other 487.28 49.52 0.00 0.00 0.00 0.00
Total 1485.02 270.86 0.00 0.00 0.00 0.13


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 5649.02 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 5649.02 100.00
     
Total On-Site and Utility Electric Sources 5649.02 100.00
Total Electricity End Uses 5649.02 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 479.65 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 479.65 100.00
Total Water End Uses 479.65 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 13.17
Time Setpoint Not Met During Occupied Cooling 1087.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 7595.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |

OVERALL HVAC AIR SYSTEM LOADS

| AHU-1 | AHU-2 |

OVERALL HVAC SYSTEM ENERGY

| Meter |

COMPONENTS OF PEAK ELECTRICAL DEMAND

| Meter |

ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS

| Meter |

BUILDING ENERGY PERFORMANCE - ELECTRICITY

| Meter |

BUILDING ENERGY PERFORMANCE - NATURAL GAS

| Meter |

PEAK ENERGY END-USE - ELECTRICITY

| Meter |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:21
RunPeriod Miami Intl Ap FL USA TMY3 WMO#=722020
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [m] 11.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 308.29 97.22 57.97 114.08 39.02
Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1553.34 473.81 302.86 473.81 302.86
Window Opening Area [m2] 308.29 97.22 57.97 114.08 39.02
Window-Wall Ratio [%] 19.85 20.52 19.14 24.08 12.88


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1373.29
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
FLOOR 1 ANESTHESIA 10.03 Yes Yes 30.58 1.00 8.36 2.23 14.7559 4.64 21.5300
FLOOR 1 BIO HAZ 5.20 Yes Yes 15.86 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 CAFE 39.02 Yes Yes 118.93 1.00 18.58 8.92 8.8535 0.93 10.7600
FLOOR 1 CLEAN 11.71 Yes Yes 35.68 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 CLEAN WORK 15.33 Yes Yes 46.72 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 DICTATION 11.71 Yes Yes 35.68 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 DRESSING ROOM 4.18 Yes Yes 12.74 1.00 8.36 2.32 10.8210 18.58 11.8400
FLOOR 1 ELECTRICAL ROOM 9.10 Yes Yes 27.75 1.00 6.50 0.00 14.7559   53.8200
FLOOR 1 ELEVATOR PUMP ROOM 8.45 Yes Yes 25.77 1.00 18.58 0.00 14.7559   5754.6154
FLOOR 1 HUMID 5.02 Yes Yes 15.29 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 IT HALL 13.01 Yes Yes 39.64 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 IT ROOM 10.41 Yes Yes 31.71 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 LOBBY 57.79 Yes Yes 176.13 1.00 20.44 8.92 12.7884 9.29 11.8400
FLOOR 1 LOBBY HALL 22.30 Yes Yes 67.96 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 LOBBY TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 1 LOCKER ROOM 61.32 Yes Yes 186.89 1.00 20.44 5.57 7.8698 6.19 32.2900
FLOOR 1 LOCKER ROOM HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 LOUNGE 33.45 Yes Yes 101.94 1.00 0.00 0.00 7.8698 6.19 32.2900
FLOOR 1 MED GAS 5.20 Yes Yes 15.86 1.00 13.94 0.00 8.8535   1.0800
FLOOR 1 MRI CONTROL ROOM 15.61 Yes Yes 47.57 1.00 4.65 0.00 3.9349 4.64 107.6400
FLOOR 1 MRI HALL 13.66 Yes Yes 41.63 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 MRI ROOM 40.88 Yes Yes 124.59 1.00 0.00 0.00 3.9349 4.64 107.6400
FLOOR 1 MRI TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 1 NOURISHMENT 16.91 Yes Yes 51.54 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 1 NURSE HALL 46.08 Yes Yes 140.45 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 NURSE JANITOR 5.02 Yes Yes 15.29 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 NURSE STATION 24.25 Yes Yes 73.91 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 1 NURSE TOILET 5.02 Yes Yes 15.29 1.00 0.00 0.00 8.8535   4.3100
FLOOR 1 OFFICE 44.87 Yes Yes 136.77 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 1 OPERATING ROOM 1 42.74 Yes Yes 130.26 1.00 39.95 8.92 21.6419 4.64 118.3600
FLOOR 1 OPERATING ROOM 2 44.59 Yes Yes 135.92 1.00 22.30 6.69 21.6419 4.64 118.3600
FLOOR 1 OPERATING ROOM 3 44.22 Yes Yes 134.79 1.00 0.00 0.00 21.6419 4.64 118.3600
FLOOR 1 PACU 10.03 Yes Yes 30.58 1.00 0.00 0.00 7.8698 4.64 32.2900
FLOOR 1 PRE-OP HALL 49.05 Yes Yes 149.51 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 PRE-OP ROOM 1 17.56 Yes Yes 53.52 1.00 3.72 0.00 6.8861 9.29 21.5300
FLOOR 1 PRE-OP ROOM 2 31.40 Yes Yes 95.71 1.00 0.00 0.00 6.8861 9.29 21.5300
FLOOR 1 PRE-OP TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 1 PROCEDURE ROOM 26.48 Yes Yes 80.70 1.00 17.65 5.57 26.5606 4.64 32.2900
FLOOR 1 RECEPTION 47.29 Yes Yes 144.13 1.00 12.08 3.34 12.7884 3.10 11.8400
FLOOR 1 RECEPTION HALL 11.89 Yes Yes 36.25 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 RECOVERY ROOM 50.17 Yes Yes 152.91 1.00 41.81 8.92 7.8698 4.64 32.2900
FLOOR 1 SCHEDULING 11.06 Yes Yes 33.70 1.00 6.50 0.74 10.8210 18.58 11.8400
FLOOR 1 SCRUB 7.80 Yes Yes 23.79 1.00 0.00 0.00 9.8372   4.3100
FLOOR 1 SOIL 11.71 Yes Yes 35.68 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 SOIL HOLD 5.20 Yes Yes 15.86 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 SOIL WORK 16.72 Yes Yes 50.97 1.00 0.00 0.00 14.7559 4.64 21.5300
FLOOR 1 STEP DOWN 27.87 Yes Yes 84.95 1.00 34.37 6.69 7.8698 4.64 32.2900
FLOOR 1 STERILE HALL 57.23 Yes Yes 174.43 1.00 7.43 2.23 9.8372   4.3100
FLOOR 1 STERILE STORAGE 36.79 Yes Yes 112.13 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 STORAGE 85.47 Yes Yes 260.51 1.00 58.53 8.36 8.8535   1.0800
FLOOR 1 SUB-STERILE 18.21 Yes Yes 55.50 1.00 13.01 2.97 9.8372   4.3100
FLOOR 1 UTILITY HALL 23.78 Yes Yes 72.49 1.00 14.86 0.00 9.8372   4.3100
FLOOR 1 UTILITY JANITOR 3.90 Yes Yes 11.89 1.00 0.00 0.00 8.8535   1.0800
FLOOR 1 UTILITY ROOM 33.45 Yes Yes 101.94 1.00 16.72 2.23 8.8535   1.0800
FLOOR 1 VESTIBULE 6.69 Yes Yes 20.39 1.00 7.43 0.00 9.8372   4.3100
FLOOR 2 CONFERENCE 31.22 Yes Yes 95.14 1.00 37.16 8.92 12.7884 1.86 10.7600
FLOOR 2 CONFERENCE TOILET 5.95 Yes Yes 18.12 1.00 0.00 0.00 8.8535   4.3100
FLOOR 2 DICTATION 6.50 Yes Yes 19.82 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 2 EXAM 1 33.45 Yes Yes 101.94 1.00 39.02 8.92 14.7559 4.64 11.8400
FLOOR 2 EXAM 2 50.17 Yes Yes 152.91 1.00 16.72 3.72 14.7559 4.64 11.8400
FLOOR 2 EXAM 3 66.89 Yes Yes 203.88 1.00 22.30 5.95 14.7559 4.64 11.8400
FLOOR 2 EXAM 4 7.80 Yes Yes 23.79 1.00 6.50 2.23 14.7559 4.64 11.8400
FLOOR 2 EXAM 5 32.52 Yes Yes 99.11 1.00 23.23 5.95 14.7559 4.64 11.8400
FLOOR 2 EXAM 6 20.90 Yes Yes 63.71 1.00 13.94 4.18 14.7559 4.64 11.8400
FLOOR 2 EXAM 7 73.58 Yes Yes 224.27 1.00 22.30 5.57 14.7559 4.64 11.8400
FLOOR 2 EXAM 8 25.08 Yes Yes 76.46 1.00 16.72 5.57 14.7559 4.64 11.8400
FLOOR 2 EXAM 9 36.79 Yes Yes 112.13 1.00 11.15 2.79 14.7559 4.64 11.8400
FLOOR 2 EXAM HALL 1 16.72 Yes Yes 50.97 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 2 16.72 Yes Yes 50.97 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 3 16.72 Yes Yes 50.97 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 4 18.39 Yes Yes 56.07 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 5 18.39 Yes Yes 56.07 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 EXAM HALL 6 18.39 Yes Yes 56.07 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 8.8535   1.0800
FLOOR 2 LOUNGE 7.43 Yes Yes 22.65 1.00 0.00 0.00 7.8698 6.19 32.2900
FLOOR 2 NURSE STATION 1 13.94 Yes Yes 42.48 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 2 NURSE STATION 2 16.72 Yes Yes 50.97 1.00 0.00 0.00 9.8372 4.64 21.5300
FLOOR 2 OFFICE 52.03 Yes Yes 158.57 1.00 37.16 8.92 10.8210 18.58 11.8400
FLOOR 2 OFFICE HALL 41.25 Yes Yes 125.73 1.00 0.00 0.00 9.8372   4.3100
FLOOR 2 RECEPTION 91.42 Yes Yes 278.64 1.00 45.52 16.72 12.7884 3.10 11.8400
FLOOR 2 RECEPTION HALL 52.40 Yes Yes 159.71 1.00 6.50 0.00 9.8372   4.3100
FLOOR 2 RECEPTION TOILET 11.71 Yes Yes 35.68 1.00 0.00 0.00 8.8535   4.3100
FLOOR 2 SCHEDULING 1 30.10 Yes Yes 91.75 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 2 SCHEDULING 2 31.77 Yes Yes 96.84 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 2 STORAGE 1 5.20 Yes Yes 15.86 1.00 0.00 0.00 8.8535   1.0800
FLOOR 2 STORAGE 2 11.15 Yes Yes 33.98 1.00 0.00 0.00 8.8535   1.0800
FLOOR 2 STORAGE 3 13.38 Yes Yes 40.78 1.00 0.00 0.00 8.8535   1.0800
FLOOR 2 UTILITY 11.71 Yes Yes 35.68 1.00 8.36 2.23 8.8535   1.0800
FLOOR 2 WORK 157.01 Yes Yes 478.55 1.00 24.15 5.57 10.8210 18.58 9.7803
FLOOR 2 WORK HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 9.8372   4.3100
FLOOR 2 WORK TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 2 X-RAY 83.61 Yes Yes 254.85 1.00 0.00 0.00 3.9349 4.64 107.6400
FLOOR 3 DRESSING ROOM 3.90 Yes Yes 11.89 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 3 ELEVATOR HALL 34.37 Yes Yes 104.77 1.00 3.72 0.00 9.8372   4.3100
FLOOR 3 HUMID 10.03 Yes Yes 30.58 1.00 0.00 0.00 10.8210 18.58 11.8400
FLOOR 3 JANITOR 5.85 Yes Yes 17.84 1.00 14.86 0.00 8.8535   1.0800
FLOOR 3 LOCKER 11.15 Yes Yes 33.98 1.00 0.00 0.00 7.8698 6.19 32.2900
FLOOR 3 LOUNGE 70.51 Yes Yes 214.92 1.00 21.37 5.57 7.8698 6.19 32.2900
FLOOR 3 LOUNGE TOILET 17.84 Yes Yes 54.37 1.00 11.15 4.18 8.8535   4.3100
FLOOR 3 MECHANICAL 32.52 Yes Yes 99.11 1.00 23.23 5.95 14.7559   53.8200
FLOOR 3 MECHANICAL HALL 27.87 Yes Yes 84.95 1.00 0.00 0.00 9.8372   4.3100
FLOOR 3 OFFICE 282.05 Yes Yes 859.70 1.00 68.75 19.51 10.8210 18.58 11.8400
FLOOR 3 OFFICE HALL 77.48 Yes Yes 236.16 1.00 5.57 0.00 9.8372   4.3100
FLOOR 3 OFFICE TOILET 5.02 Yes Yes 15.29 1.00 5.57 0.00 8.8535   4.3100
FLOOR 3 PHYSICAL THERAPY 1 120.77 Yes Yes 368.12 1.00 78.97 28.99 8.8535 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY 2 55.00 Yes Yes 167.64 1.00 0.00 0.00 8.8535 4.64 16.1500
FLOOR 3 PHYSICAL THERAPY TOILET 7.80 Yes Yes 23.79 1.00 0.00 0.00 8.8535   4.3100
FLOOR 3 STORAGE 1 10.03 Yes Yes 30.58 1.00 0.00 0.00 8.8535   1.0800
FLOOR 3 STORAGE 2 7.80 Yes Yes 23.79 1.00 0.00 0.00 8.8535   1.0800
FLOOR 3 TREATMENT 44.22 Yes Yes 134.79 1.00 0.00 0.00 14.7559 4.64 11.8400
FLOOR 3 UNDEVELOPED 1 210.70 Yes Yes 642.23 1.00 66.89 25.64 8.8535   11.8400
FLOOR 3 UNDEVELOPED 2 107.02 Yes Yes 326.21 1.00 52.03 13.38 8.8535   11.8400
FLOOR 3 UTILITY 20.07 Yes Yes 61.16 1.00 0.00 0.00 8.8535   1.0800
FLOOR 3 WORK 53.33 Yes Yes 162.54 1.00 38.09 8.92 10.8210 18.58 11.8400
NE STAIR 15.61 Yes Yes 142.72 1.00 97.55 12.02 9.8372   4.3100
NW ELEVATOR 13.01 Yes Yes 118.93 1.00 75.25 0.00 9.8372   4.3100
NW STAIR 17.84 Yes Yes 163.10 1.00 111.48 11.15 9.8372   4.3100
SW STAIR 8.92 Yes Yes 81.55 1.00 55.74 1.11 9.8372   4.3100
Total 3804.01     11932.15   1553.34 308.29 10.7639 9.08 32.0039
Conditioned Total 3804.01     11932.15   1553.34 308.29 10.7639 9.08 32.0039
Unconditioned Total 0.00     0.00   0.00 0.00      
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 8.70 0.00 8.70 Wetbulb [C] 3.80 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 33.20 6.70 25.30 Wetbulb [C] 4.50 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
481E71 NONRES_EXT_WALL 0.30 0.704 0.787 8.36 180.00 90.00 S
FLOOR 1 ANESTHESIA SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 10.03 0.00 180.00  
FLOOR 1 BIO HAZ SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.20 0.00 180.00  
5F762C NONRES_EXT_WALL 0.30 0.704 0.787 18.58 180.00 90.00 S
FLOOR 1 CAFE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 39.02 90.00 180.00  
FLOOR 1 CLEAN SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.71 90.00 180.00  
FLOOR 1 CLEAN WORK SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.33 180.00 180.00  
FLOOR 1 DICTATION SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.71 0.00 180.00  
84FB73 NONRES_EXT_WALL 0.30 0.704 0.787 8.36 0.00 90.00 N
FLOOR 1 DRESSING ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 4.18 0.00 180.00  
7F5C82 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 90.00 90.00 E
FLOOR 1 ELECTRICAL ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 9.10 0.00 180.00  
C732B0 NONRES_EXT_WALL 0.30 0.704 0.787 12.08 0.00 90.00 N
E02487 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 270.00 90.00 W
FLOOR 1 ELEVATOR PUMP ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 8.45 180.00 180.00  
FLOOR 1 HUMID SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 0.00 180.00  
FLOOR 1 IT HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 13.01 180.00 180.00  
FLOOR 1 IT ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 10.41 90.00 180.00  
FE5A3C NONRES_EXT_WALL 0.30 0.704 0.787 20.44 270.00 90.00 W
FLOOR 1 LOBBY SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 57.79 90.00 180.00  
FLOOR 1 LOBBY HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 22.30 0.00 180.00  
9D87EC NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 1 LOBBY TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 0.00 180.00  
F629C1 NONRES_EXT_WALL 0.30 0.704 0.787 20.44 0.00 90.00 N
FLOOR 1 LOCKER ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 61.32 270.00 180.00  
FLOOR 1 LOCKER ROOM HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 46.08 180.00 180.00  
FLOOR 1 LOUNGE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 33.45 180.00 180.00  
E85BB5 NONRES_EXT_WALL 0.30 0.704 0.787 7.43 0.00 90.00 N
577FC1 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 90.00 90.00 E
FLOOR 1 MED GAS SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.20 180.00 180.00  
FLOOR 1 MED GAS ROOF NONRES_ROOF 0.30 0.351 0.376 5.20 180.00 0.00  
C114C1 NONRES_EXT_WALL 0.30 0.704 0.787 4.65 0.00 90.00 N
FLOOR 1 MRI CONTROL ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.61 180.00 180.00  
FLOOR 1 MRI HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 13.66 180.00 180.00  
FLOOR 1 MRI ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 40.88 90.00 180.00  
ADB8D0 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
FLOOR 1 MRI TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 90.00 180.00  
FLOOR 1 NOURISHMENT SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 16.91 270.00 180.00  
FLOOR 1 NURSE HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 46.08 270.00 180.00  
FLOOR 1 NURSE JANITOR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 180.00 180.00  
FLOOR 1 NURSE STATION SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 24.25 180.00 180.00  
FLOOR 1 NURSE TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 180.00 180.00  
FLOOR 1 OFFICE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 44.87 0.00 180.00  
879583 NONRES_EXT_WALL 0.30 0.704 0.787 18.58 180.00 90.00 S
E326E4 NONRES_EXT_WALL 0.30 0.704 0.787 21.37 90.00 90.00 E
FLOOR 1 OPERATING ROOM 1 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 42.74 0.00 180.00  
1D96D7 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 90.00 90.00 E
FLOOR 1 OPERATING ROOM 2 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 44.59 0.00 180.00  
FLOOR 1 OPERATING ROOM 3 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 44.22 0.00 180.00  
FLOOR 1 PACU SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 10.03 180.00 180.00  
FLOOR 1 PRE-OP HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 49.05 180.00 180.00  
84418A NONRES_EXT_WALL 0.30 0.704 0.787 3.72 270.00 90.00 W
FLOOR 1 PRE-OP ROOM 1 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 17.56 90.00 180.00  
FLOOR 1 PRE-OP ROOM 2 SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 31.40 0.00 180.00  
1535AC NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 1 PRE-OP TOILET SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.02 270.00 180.00  
6D2616 NONRES_EXT_WALL 0.30 0.704 0.787 17.65 0.00 90.00 N
FLOOR 1 PROCEDURE ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 26.48 270.00 180.00  
A5A6A3 NONRES_EXT_WALL 0.30 0.704 0.787 12.08 180.00 90.00 S
FLOOR 1 RECEPTION SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 47.29 270.00 180.00  
FLOOR 1 RECEPTION HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.89 0.00 180.00  
28B002 NONRES_EXT_WALL 0.30 0.704 0.787 41.81 180.00 90.00 S
FLOOR 1 RECOVERY ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 50.17 90.00 180.00  
EA6DC8 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 180.00 90.00 S
FLOOR 1 SCHEDULING SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.06 90.00 180.00  
FLOOR 1 SCRUB SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 7.80 90.00 180.00  
FLOOR 1 SOIL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 11.71 90.00 180.00  
FLOOR 1 SOIL HOLD SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 5.20 0.00 180.00  
FLOOR 1 SOIL WORK SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 16.72 0.00 180.00  
B40F89 NONRES_EXT_WALL 0.30 0.704 0.787 11.15 270.00 90.00 W
997723 NONRES_EXT_WALL 0.30 0.704 0.787 23.23 180.00 90.00 S
FLOOR 1 STEP DOWN SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 27.87 270.00 180.00  
CEC7BD NONRES_EXT_WALL 0.30 0.704 0.787 7.43 180.00 90.00 S
FLOOR 1 STERILE HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 57.23 270.00 180.00  
FLOOR 1 NURSE STORAGE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 36.79 0.00 180.00  
8E5BB9 NONRES_EXT_WALL 0.30 0.704 0.787 21.37 270.00 90.00 W
859BC1 NONRES_EXT_WALL 0.30 0.704 0.787 37.16 0.00 90.00 N
FLOOR 1 STORAGE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 85.47 270.00 180.00  
FLOOR 1 STORGE ROOF NONRES_ROOF 0.30 0.351 0.376 85.47 270.00 0.00  
61E610 NONRES_EXT_WALL 0.30 0.704 0.787 13.01 90.00 90.00 E
FLOOR 1 SUB-STERILE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 18.21 180.00 180.00  
529072 NONRES_EXT_WALL 0.30 0.704 0.787 14.86 90.00 90.00 E
FLOOR 1 UTILITY HALL SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 23.78 90.00 180.00  
FLOOR 1 UTILITY HALL ROOF NONRES_ROOF 0.30 0.351 0.376 11.89 180.00 0.00  
FLOOR 1 UTILITY JANITOR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 3.90 90.00 180.00  
D95F04 NONRES_EXT_WALL 0.30 0.704 0.787 16.72 90.00 90.00 E
FLOOR 1 UTILITY ROOM SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 33.45 180.00 180.00  
3330D8 NONRES_EXT_WALL 0.30 0.704 0.787 7.43 270.00 90.00 W
FLOOR 1 VESTIBULE SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 6.69 90.00 180.00  
208CCF NONRES_EXT_WALL 0.30 0.704 0.787 11.15 90.00 90.00 E
AEF992 NONRES_EXT_WALL 0.30 0.704 0.787 26.01 180.00 90.00 S
54D065 NONRES_EXT_WALL 0.30 0.704 0.787 11.15 180.00 90.00 S
1775A6 NONRES_EXT_WALL 0.30 0.704 0.787 27.87 270.00 90.00 W
97F00A NONRES_EXT_WALL 0.30 0.704 0.787 16.72 180.00 90.00 S
A497E9 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 180.00 90.00 S
88A75F NONRES_EXT_WALL 0.30 0.704 0.787 6.50 180.00 90.00 S
B4E619 NONRES_EXT_WALL 0.30 0.704 0.787 23.23 90.00 90.00 E
9EC269 NONRES_EXT_WALL 0.30 0.704 0.787 13.94 0.00 90.00 N
B316F7 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 0.00 90.00 N
9621FD NONRES_EXT_WALL 0.30 0.704 0.787 16.72 0.00 90.00 N
42CEE1 NONRES_EXT_WALL 0.30 0.704 0.787 11.15 0.00 90.00 N
4979C8 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 180.00 90.00 S
8CA0BF NONRES_EXT_WALL 0.30 0.704 0.787 5.57 180.00 90.00 S
6C95E7 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 180.00 90.00 S
F209CC NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
155BD6 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
C5EA55 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 0.00 90.00 N
8177BA NONRES_EXT_WALL 0.30 0.704 0.787 6.50 270.00 90.00 W
5E657E NONRES_EXT_WALL 0.30 0.704 0.787 8.36 0.00 90.00 N
4B1439 NONRES_EXT_WALL 0.30 0.704 0.787 37.16 90.00 90.00 E
4ABC66 NONRES_EXT_WALL 0.30 0.704 0.787 30.66 180.00 90.00 S
5B04CF NONRES_EXT_WALL 0.30 0.704 0.787 14.86 270.00 90.00 W
8D1BC4 NONRES_EXT_WALL 0.30 0.704 0.787 6.50 180.00 90.00 S
4B55FA NONRES_EXT_WALL 0.30 0.704 0.787 8.36 90.00 90.00 E
9C3A6A NONRES_EXT_WALL 0.30 0.704 0.787 20.44 0.00 90.00 N
C52EE0 NONRES_EXT_WALL 0.30 0.704 0.787 3.72 0.00 90.00 N
1C33AD NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
6CC177 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 3 DRESSING ROOM ROOF NONRES_ROOF 0.30 0.351 0.376 3.90 270.00 0.00  
F7D24D NONRES_EXT_WALL 0.30 0.704 0.787 3.72 0.00 90.00 N
FLOOR 3 ELEVATOR HALL ROOF NONRES_ROOF 0.30 0.351 0.376 34.37 0.00 0.00  
FLOOR 3 HUMID ROOF NONRES_ROOF 0.30 0.351 0.376 10.03 270.00 0.00  
FC22D1 NONRES_EXT_WALL 0.30 0.704 0.787 8.36 0.00 90.00 N
DD2E2D NONRES_EXT_WALL 0.30 0.704 0.787 6.50 270.00 90.00 W
FLOOR 3 JANITOR ROOF NONRES_ROOF 0.30 0.351 0.376 5.85 0.00 0.00  
FLOOR 3 LOCKER ROOF NONRES_ROOF 0.30 0.351 0.376 11.15 0.00 0.00  
68A2D7 NONRES_EXT_WALL 0.30 0.704 0.787 21.37 0.00 90.00 N
FLOOR 3 LOUNGE ROOF NONRES_ROOF 0.30 0.351 0.376 70.51 270.00 0.00  
CE3FEF NONRES_EXT_WALL 0.30 0.704 0.787 11.15 0.00 90.00 N
FLOOR 3 LOUNGE TOILET ROOF NONRES_ROOF 0.30 0.351 0.376 17.84 0.00 0.00  
CE618F NONRES_EXT_WALL 0.30 0.704 0.787 23.23 90.00 90.00 E
FLOOR 3 MECHANICAL ROOF NONRES_ROOF 0.30 0.351 0.376 32.52 0.00 0.00  
FLOOR 3 MECHANICAL HALL ROOF NONRES_ROOF 0.30 0.351 0.376 27.87 0.00 0.00  
5ADC59 NONRES_EXT_WALL 0.30 0.704 0.787 68.75 0.00 90.00 N
FLOOR 3 OFFICE ROOF NONRES_ROOF 0.30 0.351 0.376 282.05 180.00 0.00  
D4F411 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 3 OFFICE HALL ROOF NONRES_ROOF 0.30 0.351 0.376 77.48 270.00 0.00  
B35AD6 NONRES_EXT_WALL 0.30 0.704 0.787 5.57 270.00 90.00 W
FLOOR 3 OFFICE TOILET ROOF NONRES_ROOF 0.30 0.351 0.376 5.02 270.00 0.00  
D22917 NONRES_EXT_WALL 0.30 0.704 0.787 18.58 90.00 90.00 E
C1BC97 NONRES_EXT_WALL 0.30 0.704 0.787 60.39 180.00 90.00 S
FLOOR 3 PHYICAL THERAPY 1 ROOF NONRES_ROOF 0.30 0.351 0.376 120.77 180.00 0.00  
FLOOR 3 PHYSICAL THERAPY 2 ROOF NONRES_ROOF 0.30 0.351 0.376 55.00 90.00 0.00  
FLOOR 3 PHYSICAL THERAPY TOILET ROOF NONRES_ROOF 0.30 0.351 0.376 7.80 90.00 0.00  
FLOOR 3 STORAGE 1 ROOF NONRES_ROOF 0.30 0.351 0.376 10.03 180.00 0.00  
FLOOR 3 STORAGE 2 ROOF NONRES_ROOF 0.30 0.351 0.376 7.80 180.00 0.00  
FLOOR 3 TREATMENT ROOF NONRES_ROOF 0.30 0.351 0.376 44.22 90.00 0.00  
8DA7DB NONRES_EXT_WALL 0.30 0.704 0.787 39.02 180.00 90.00 S
38B339 NONRES_EXT_WALL 0.30 0.704 0.787 27.87 270.00 90.00 W
FLOOR 3 UNDEVELOPED 1 ROOF NONRES_ROOF 0.30 0.351 0.376 210.70 0.00 0.00  
BE5F2F NONRES_EXT_WALL 0.30 0.704 0.787 14.86 270.00 90.00 W
1DEE26 NONRES_EXT_WALL 0.30 0.704 0.787 37.16 180.00 90.00 S
FLOOR 3 UNDEVELOPED 2 ROOF NONRES_ROOF 0.30 0.351 0.376 107.02 180.00 0.00  
FLOOR 3 UTILITY ROOF NONRES_ROOF 0.30 0.351 0.376 20.07 0.00 0.00  
C86329 NONRES_EXT_WALL 0.30 0.704 0.787 38.09 90.00 90.00 E
FLOOR 3 WORK ROOF NONRES_ROOF 0.30 0.351 0.376 53.33 90.00 0.00  
DFC6F0 NONRES_EXT_WALL 0.30 0.704 0.787 19.51 90.00 90.00 E
88E360 NONRES_EXT_WALL 0.30 0.704 0.787 66.89 0.00 90.00 N
E7B55F NONRES_EXT_WALL 0.30 0.704 0.787 11.15 180.00 90.00 S
NE STAIR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.61 0.00 180.00  
NE STAIR ROOF NONRES_ROOF 0.30 0.351 0.376 15.61 0.00 0.00  
FB3814 NONRES_EXT_WALL 0.30 0.704 0.787 19.51 180.00 90.00 S
FCD12D NONRES_EXT_WALL 0.30 0.704 0.787 55.74 270.00 90.00 W
NW ELEVATOR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 13.01 90.00 180.00  
NW ELEVATOR ROOF NONRES_ROOF 0.30 0.351 0.376 13.01 90.00 0.00  
5507DC NONRES_EXT_WALL 0.30 0.704 0.787 22.30 270.00 90.00 W
2E2D0C NONRES_EXT_WALL 0.30 0.704 0.787 66.89 0.00 90.00 N
AF0124 NONRES_EXT_WALL 0.30 0.704 0.787 22.30 90.00 90.00 E
NW STAIR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 17.84 270.00 180.00  
NW STAIR ROOF NONRES_ROOF 0.30 0.351 0.376 17.84 270.00 0.00  
850EA7 NONRES_EXT_WALL 0.30 0.704 0.787 33.45 180.00 90.00 S
270BCE NONRES_EXT_WALL 0.30 0.704 0.787 22.30 270.00 90.00 W
SW STAIR SLAB EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 8.92 270.00 180.00  
SW STAIR ROOF NONRES_ROOF 0.30 0.351 0.376 8.92 180.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
78F987 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 481E71 180.00 90.00 S
D8037E WINDOW_U_1.08_SHGC_0.25 8.92 0.00 0.00 8.92 8.92 5.778 0.306 0.155     No 5F762C 180.00 90.00 S
4A8120 WINDOW_U_1.08_SHGC_0.25 2.32 0.00 0.00 2.32 2.32 5.778 0.306 0.155     No 84FB73 0.00 90.00 N
AAE778 WINDOW_U_1.08_SHGC_0.25 8.92 0.00 0.00 8.92 8.92 5.778 0.306 0.155     No FE5A3C 270.00 90.00 W
3AAD8B WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No F629C1 0.00 90.00 N
8128A9 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No F629C1 0.00 90.00 N
9B1541 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 879583 180.00 90.00 S
CF850A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 879583 180.00 90.00 S
A6BA23 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No E326E4 90.00 90.00 E
D10D28 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No E326E4 90.00 90.00 E
591336 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1D96D7 90.00 90.00 E
38B811 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1D96D7 90.00 90.00 E
C044D6 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1D96D7 90.00 90.00 E
1D94BE WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 6D2616 0.00 90.00 N
18748E WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 6D2616 0.00 90.00 N
137A56 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No A5A6A3 180.00 90.00 S
8D508E WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
B2D381 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
1DA13A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
44E54A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 28B002 180.00 90.00 S
757D10 WINDOW_U_1.08_SHGC_0.25 0.74 0.00 0.00 0.74 0.74 5.778 0.306 0.155     No EA6DC8 180.00 90.00 S
E33BAE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No B40F89 270.00 90.00 W
24167A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 997723 180.00 90.00 S
2C0938 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 997723 180.00 90.00 S
8600DD WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No CEC7BD 180.00 90.00 S
A1ED60 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 859BC1 0.00 90.00 N
E8D997 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 859BC1 0.00 90.00 N
88E1FC WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 859BC1 0.00 90.00 N
F83F33 WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No 61E610 90.00 90.00 E
B1F5EE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No D95F04 90.00 90.00 E
F52F3D WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 208CCF 90.00 90.00 E
80885D WINDOW_U_1.08_SHGC_0.25 6.69 0.00 0.00 6.69 6.69 5.778 0.306 0.155     No AEF992 180.00 90.00 S
FEEF06 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 54D065 180.00 90.00 S
2BE8DE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1775A6 270.00 90.00 W
513E2A WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1775A6 270.00 90.00 W
BA5CD9 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 1775A6 270.00 90.00 W
1AD478 WINDOW_U_1.08_SHGC_0.25 3.72 0.00 0.00 3.72 3.72 5.778 0.306 0.155     No 97F00A 180.00 90.00 S
27F0AC WINDOW_U_1.08_SHGC_0.25 5.95 0.00 0.00 5.95 5.95 5.778 0.306 0.155     No A497E9 180.00 90.00 S
724114 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 88A75F 180.00 90.00 S
D538C4 WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No B4E619 90.00 90.00 E
5635BC WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No B4E619 90.00 90.00 E
831C1D WINDOW_U_1.08_SHGC_0.25 4.18 0.00 0.00 4.18 4.18 5.778 0.306 0.155     No 9EC269 0.00 90.00 N
9BB95F WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No B316F7 0.00 90.00 N
C0778D WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No B316F7 0.00 90.00 N
7D2D69 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9621FD 0.00 90.00 N
2EF63B WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9621FD 0.00 90.00 N
C417C0 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 42CEE1 0.00 90.00 N
EB042B WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
4C1F71 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
D23C8B WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
B4E4BE WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B1439 90.00 90.00 E
EEF55D WINDOW_U_1.08_SHGC_0.25 6.69 0.00 0.00 6.69 6.69 5.778 0.306 0.155     No 4ABC66 180.00 90.00 S
E55A57 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 4ABC66 180.00 90.00 S
93D018 WINDOW_U_1.08_SHGC_0.25 6.69 0.00 0.00 6.69 6.69 5.778 0.306 0.155     No 5B04CF 270.00 90.00 W
DD9F5D WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No 4B55FA 90.00 90.00 E
15B02B WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9C3A6A 0.00 90.00 N
820282 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 9C3A6A 0.00 90.00 N
9BA05A WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 68A2D7 0.00 90.00 N
C639E8 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 68A2D7 0.00 90.00 N
A2790A WINDOW_U_1.08_SHGC_0.25 4.18 0.00 0.00 4.18 4.18 5.778 0.306 0.155     No CE3FEF 0.00 90.00 N
79FCEE WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No CE618F 90.00 90.00 E
EDE617 WINDOW_U_1.08_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No CE618F 90.00 90.00 E
C61F0D WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
7248C5 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
29FA28 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
F0B23F WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
EEC10E WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
944FCE WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
C41399 WINDOW_U_1.08_SHGC_0.25 2.79 0.00 0.00 2.79 2.79 5.778 0.306 0.155     No 5ADC59 0.00 90.00 N
95BA33 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No D22917 90.00 90.00 E
F27282 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No D22917 90.00 90.00 E
3DB407 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
3DADE2 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
DF3E2C WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
5031C8 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No C1BC97 180.00 90.00 S
C087D0 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 8DA7DB 180.00 90.00 S
D2CA75 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 8DA7DB 180.00 90.00 S
B0FB49 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No 8DA7DB 180.00 90.00 S
FE9BC9 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 38B339 270.00 90.00 W
9DF7DE WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 38B339 270.00 90.00 W
D0BE44 WINDOW_U_1.08_SHGC_0.25 3.34 0.00 0.00 3.34 3.34 5.778 0.306 0.155     No 38B339 270.00 90.00 W
6B5226 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No BE5F2F 270.00 90.00 W
8F59F7 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No 1DEE26 180.00 90.00 S
44F571 WINDOW_U_1.08_SHGC_0.25 4.46 0.00 0.00 4.46 4.46 5.778 0.306 0.155     No 1DEE26 180.00 90.00 S
6BD844 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
86D536 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
BAF71D WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
3833A2 WINDOW_U_1.08_SHGC_0.25 2.23 0.00 0.00 2.23 2.23 5.778 0.306 0.155     No C86329 90.00 90.00 E
2111A1 WINDOW_U_1.08_SHGC_0.25 0.74 0.00 0.00 0.74 0.74 5.778 0.306 0.155     No DFC6F0 90.00 90.00 E
9BC521 WINDOW_U_1.08_SHGC_0.25 5.71 0.00 0.00 5.71 5.71 5.778 0.306 0.155     No 88E360 0.00 90.00 N
142781 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 88E360 0.00 90.00 N
E74902 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 2E2D0C 0.00 90.00 N
93BBC3 WINDOW_U_1.08_SHGC_0.25 5.57 0.00 0.00 5.57 5.57 5.778 0.306 0.155     No 2E2D0C 0.00 90.00 N
C635A6 WINDOW_U_1.08_SHGC_0.25 1.11 0.00 0.00 1.11 1.11 5.778 0.306 0.155     No 850EA7 180.00 90.00 S
Total or Average           308.29 5.778 0.306 0.155              
North Total or Average           97.22 5.778 0.306 0.155              
Non-North Total or Average           211.08 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
71E924 OPAQUEDOOR 8.100 8.100 2.97 8E5BB9
5E66D1 OPAQUEDOOR 8.100 8.100 5.95 529072
E14DAE OPAQUEDOOR 8.100 8.100 2.97 D95F04
84A1D5 OPAQUEDOOR 8.100 8.100 2.97 3330D8
9CB8E5 OPAQUEDOOR 8.100 8.100 2.97 88E360
EDE769 OPAQUEDOOR 8.100 8.100 2.97 5507DC



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
HEATSYS1 BOILER Boiler:HotWater 61863.63 0.80    


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed   179435.55 121313.36 58122.19 0.68 3.23    
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed   277039.65 187301.86 89737.79 0.68 3.13    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed 174151.7 2.87 9.80 N/A 10.89
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed 268881.6 2.79 9.52 N/A 10.59
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL Coil:Heating:Water 2034.24 2015.09 -
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL Coil:Heating:Water 260.74 150.34 -
FLOOR 1 CAFE VAV BOX REHEAT COIL Coil:Heating:Water 8618.35 4969.41 -
FLOOR 1 CLEAN VAV BOX REHEAT COIL Coil:Heating:Water 1199.91 1188.62 -
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL Coil:Heating:Water 1553.94 1539.31 -
FLOOR 1 DICTATION VAV BOX REHEAT COIL Coil:Heating:Water 751.20 433.15 -
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Water 629.03 362.70 -
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 1445.39 833.42 -
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL Coil:Heating:Water 7951.03 4584.63 -
FLOOR 1 HUMID VAV BOX REHEAT COIL Coil:Heating:Water 372.91 215.02 -
FLOOR 1 IT HALL VAV BOX REHEAT COIL Coil:Heating:Water 617.89 356.28 -
FLOOR 1 IT ROOM VAV BOX REHEAT COIL Coil:Heating:Water 636.31 366.90 -
FLOOR 1 LOBBY VAV BOX REHEAT COIL Coil:Heating:Water 8668.18 4998.14 -
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL Coil:Heating:Water 1215.71 700.99 -
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1271.40 1259.43 -
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL Coil:Heating:Water 6962.83 4014.82 -
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL Coil:Heating:Water 1840.58 1061.30 -
FLOOR 1 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Water 3314.26 1911.03 -
FLOOR 1 MED GAS VAV BOX REHEAT COIL Coil:Heating:Water 725.14 549.56 -
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL Coil:Heating:Water 3939.03 2271.28 -
FLOOR 1 MRI HALL VAV BOX REHEAT COIL Coil:Heating:Water 808.75 466.33 -
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL Coil:Heating:Water 9520.25 5489.45 -
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1271.40 1259.43 -
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL Coil:Heating:Water 1670.85 963.43 -
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL Coil:Heating:Water 2164.36 1247.99 -
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 269.84 155.59 -
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL Coil:Heating:Water 2257.50 1301.69 -
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1271.40 1259.43 -
FLOOR 1 OFFICE VAV BOX REHEAT COIL Coil:Heating:Water 2482.67 1431.53 -
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 23766.35 23542.64 -
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 24810.60 24577.06 -
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL Coil:Heating:Water 22414.34 22203.35 -
FLOOR 1 PACU VAV BOX REHEAT COIL Coil:Heating:Water 1525.68 1511.32 -
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL Coil:Heating:Water 2204.16 1270.94 -
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL Coil:Heating:Water 2669.94 2644.81 -
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL Coil:Heating:Water 4774.82 4729.87 -
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL Coil:Heating:Water 1271.40 1259.43 -
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL Coil:Heating:Water 10065.26 9970.52 -
FLOOR 1 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Water 5191.59 2993.51 -
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Water 573.30 330.57 -
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 7628.41 7556.60 -
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL Coil:Heating:Water 882.80 509.03 -
FLOOR 1 SCRUB VAV BOX REHEAT COIL Coil:Heating:Water 358.87 206.93 -
FLOOR 1 SOIL VAV BOX REHEAT COIL Coil:Heating:Water 2966.60 2938.68 -
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL Coil:Heating:Water 1318.49 1306.08 -
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL Coil:Heating:Water 4238.01 4198.11 -
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL Coil:Heating:Water 5253.76 5204.31 -
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL Coil:Heating:Water 2254.72 1300.09 -
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 1306.31 753.23 -
FLOOR 1 STORAGE VAV BOX REHEAT COIL Coil:Heating:Water 6501.28 4301.32 -
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL Coil:Heating:Water 2036.85 1174.46 -
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL Coil:Heating:Water 2481.78 1431.01 -
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL Coil:Heating:Water 210.72 121.50 -
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL Coil:Heating:Water 2814.94 1623.12 -
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL Coil:Heating:Water 1057.58 609.81 -
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL Coil:Heating:Electric   2209.25 1.00
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   0.00 1.00
FLOOR 2 DICTATION VAV BOX REHEAT COIL Coil:Heating:Electric   189.25 1.00
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL Coil:Heating:Electric   8257.60 1.00
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL Coil:Heating:Electric   7501.02 1.00
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL Coil:Heating:Electric   10001.36 1.00
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL Coil:Heating:Electric   1443.29 1.00
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL Coil:Heating:Electric   6885.51 1.00
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL Coil:Heating:Electric   3125.42 1.00
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL Coil:Heating:Electric   11001.49 1.00
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL Coil:Heating:Electric   3812.08 1.00
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL Coil:Heating:Electric   5500.75 1.00
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL Coil:Heating:Electric   448.68 1.00
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL Coil:Heating:Electric   438.14 1.00
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL Coil:Heating:Electric   423.60 1.00
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL Coil:Heating:Electric   444.00 1.00
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL Coil:Heating:Electric   466.49 1.00
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL Coil:Heating:Electric   467.58 1.00
FLOOR 2 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric   400.50 1.00
FLOOR 2 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric   301.16 1.00
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL Coil:Heating:Electric   504.32 1.00
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL Coil:Heating:Electric   616.23 1.00
FLOOR 2 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric   2699.48 1.00
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric   942.17 1.00
FLOOR 2 RECEPTION VAV BOX REHEAT COIL Coil:Heating:Electric   4859.62 1.00
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1334.95 1.00
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   0.00 1.00
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL Coil:Heating:Electric   717.38 1.00
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL Coil:Heating:Electric   757.47 1.00
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric   132.53 1.00
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric   241.21 1.00
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL Coil:Heating:Electric   307.70 1.00
FLOOR 2 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric   586.02 1.00
FLOOR 2 WORK VAV BOX REHEAT COIL Coil:Heating:Electric   3699.38 1.00
FLOOR 2 WORK HALL VAV BOX REHEAT COIL Coil:Heating:Electric   1871.67 1.00
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1250.17 1.00
FLOOR 2 X-RAY VAV BOX REHEAT COIL Coil:Heating:Electric   6873.07 1.00
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL Coil:Heating:Electric   164.95 1.00
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL Coil:Heating:Electric   854.95 1.00
FLOOR 3 HUMID VAV BOX REHEAT COIL Coil:Heating:Electric   410.05 1.00
FLOOR 3 JANITOR VAV BOX REHEAT COIL Coil:Heating:Electric   381.06 1.00
FLOOR 3 LOCKER VAV BOX REHEAT COIL Coil:Heating:Electric   616.50 1.00
FLOOR 3 LOUNGE VAV BOX REHEAT COIL Coil:Heating:Electric   3600.39 1.00
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   4445.05 1.00
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL Coil:Heating:Electric   0.00 1.00
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL Coil:Heating:Electric   954.33 1.00
FLOOR 3 OFFICE VAV BOX REHEAT COIL Coil:Heating:Electric   9435.21 1.00
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL Coil:Heating:Electric   2146.14 1.00
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1250.17 1.00
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL Coil:Heating:Electric   22414.35 1.00
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL Coil:Heating:Electric   8267.45 1.00
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL Coil:Heating:Electric   1944.71 1.00
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL Coil:Heating:Electric   940.63 1.00
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL Coil:Heating:Electric   244.79 1.00
FLOOR 3 TREATMENT VAV BOX REHEAT COIL Coil:Heating:Electric   6869.66 1.00
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL Coil:Heating:Electric   7877.16 1.00
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL Coil:Heating:Electric   4132.36 1.00
FLOOR 3 UTILITY VAV BOX REHEAT COIL Coil:Heating:Electric   483.20 1.00
FLOOR 3 WORK VAV BOX REHEAT COIL Coil:Heating:Electric   3108.71 1.00
NE STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   2334.28 1.00
NW ELEVATOR VAV BOX REHEAT COIL Coil:Heating:Electric   1375.97 1.00
NW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   2311.61 1.00
SW STAIR VAV BOX REHEAT COIL Coil:Heating:Electric   1111.03 1.00
AHU-1_HEATC Coil:Heating:Water -699.94 0.00 -
AHU-1_EXTRAELECHEATC Coil:Heating:Electric   10000000.00 1.00
AHU-1_EXTRAWATERHEATC Coil:Heating:Water -699.94 0.00 -
AHU-2_HEATC Coil:Heating:Water 54951.10 51293.71 -


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
FLOOR 1 ANESTHESIA EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.07 54.61 803.55 1.00 Zone Exhaust Fans
FLOOR 1 LOBBY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.16 127.44 803.55 1.00 Zone Exhaust Fans
FLOOR 1 MRI ROOM EXHAUST FAN Fan:ZoneExhaust 0.16 124.50 0.42 323.16 778.12 1.00 Zone Exhaust Fans
FLOOR 1 MRI TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 NURSE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 PRE-OP TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 1 SOIL EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.10 79.63 803.55 1.00 Zone Exhaust Fans
FLOOR 1 SOIL HOLD EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 35.39 803.55 1.00 Zone Exhaust Fans
FLOOR 1 SOIL WORK EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.14 113.76 803.55 1.00 Zone Exhaust Fans
FLOOR 2 CONFERENCE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.05 40.45 803.55 1.00 Zone Exhaust Fans
FLOOR 2 RECEPTION TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.10 79.63 803.55 1.00 Zone Exhaust Fans
FLOOR 2 WORK TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 2 X-RAY EXHAUST FAN Fan:ZoneExhaust 0.16 124.50 0.85 661.02 778.13 1.00 Zone Exhaust Fans
FLOOR 3 LOUNGE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.15 121.35 803.55 1.00 Zone Exhaust Fans
FLOOR 3 OFFICE TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.04 34.13 803.55 1.00 Zone Exhaust Fans
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN Fan:ZoneExhaust 0.31 249.10 0.07 53.09 803.55 1.00 Zone Exhaust Fans
AHU-1_FAN Fan:VariableVolume 0.60 1389.42 7.23 16716.23 2313.39 1.00 Fan Energy
AHU-2_FAN Fan:VariableVolume 0.60 1389.42 11.16 25642.53 2298.46 1.00 Fan Energy


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0001 8.07 127739.32 0.30
HEATSYS1 PUMP Pump:ConstantSpeed Intermittent 179352.00 0.0013 338.95 255487.18 0.90


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 0.76 58614.20 0.81 0.78 0.28


VAV DX Cooling Standard Rating Details

DX Cooling Coil Type Assocated Fan Net Cooling Capacity [W] COP [W/W] EER [Btu/W-h] IEER [Btu/W-h] Supply Air Flow 100% [kg/s] COP 75% Capacity [W/W] EER 75% Capacity [Btu/W-h] Supply Air Flow 75% [kg/s] COP 50% Capacity [W/W] EER 50% Capacity [Btu/W-h] Supply Air Flow 50% [kg/s] COP 25% Capacity [W/W] EER 25% Capacity [Btu/W-h] Supply Air Flow 25% [kg/s]
AHU-1_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed None 174151.66 2.87 9.80 10.89 8.3468 3.11 10.62 6.6189 3.30 11.26 4.4920 3.42 11.69 1.9486
AHU-2_COOLC DXCOIL Coil:Cooling:DX:TwoSpeed None 268881.58 2.79 9.52 10.59 12.8870 3.03 10.33 10.2192 3.21 10.96 6.9354 3.33 11.36 3.0086
Indoor-coil-only unit ratings per ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2, with supply fan specific power at 365 {W/1000cfm} (773.3 {W/(m3/s)})


Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FLOOR 1 ANESTHESIA 667.19 667.19 0.049 0.068 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 1 CAFE 3917.44 3917.44 0.288 0.288 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20 0.01715
FLOOR 1 CLEAN 546.05 546.05 0.040 0.040 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 29.52 0.01715
FLOOR 1 CLEAN WORK 682.63 682.63 0.050 0.052 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 29.89 0.01715
FLOOR 1 DICTATION 354.10 354.10 0.025 0.025 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 DRESSING ROOM 286.23 286.23 0.021 0.021 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.20 0.01715
FLOOR 1 HUMID 175.33 175.33 0.012 0.012 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 IT ROOM 300.76 300.76 0.021 0.021 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 LOBBY 3944.92 3944.92 0.290 0.290 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.15 0.01715
FLOOR 1 LOCKER ROOM 3168.58 3168.58 0.233 0.233 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70 0.01715
FLOOR 1 LOUNGE 1508.30 1508.30 0.111 0.111 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 30.08 0.01715
FLOOR 1 MRI CONTROL ROOM 1792.62 1792.62 0.132 0.132 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.82 0.01715
FLOOR 1 MRI ROOM 4332.46 4332.46 0.318 0.318 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 31.70 0.01715
FLOOR 1 NOURISHMENT 760.37 760.37 0.056 0.056 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 29.30 0.01715
FLOOR 1 NURSE STATION 1027.32 1027.32 0.075 0.075 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 29.30 0.01715
FLOOR 1 OFFICE 1130.01 1130.01 0.083 0.083 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 29.30 0.01715
FLOOR 1 OPERATING ROOM 1 7014.97 7014.97 0.794 0.794 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 31.32 0.01715
FLOOR 1 OPERATING ROOM 2 7323.74 7323.74 0.829 0.829 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 30.82 0.01715
FLOOR 1 OPERATING ROOM 3 5906.18 5906.18 0.632 0.749 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 07:20:00 27.48 0.01715
FLOOR 1 PACU 508.03 508.03 0.037 0.051 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:40:00 29.09 0.01715
FLOOR 1 PRE-OP ROOM 1 650.38 650.38 0.048 0.089 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 32.26 0.01715
FLOOR 1 PRE-OP ROOM 2 1092.32 1092.32 0.080 0.160 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:30:00 28.88 0.01715
FLOOR 1 PROCEDURE ROOM 1947.89 1947.89 0.143 0.336 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 33.13 0.01715
FLOOR 1 RECEPTION 2362.08 2362.08 0.173 0.173 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20 0.01715
FLOOR 1 RECOVERY ROOM 3350.09 3350.09 0.246 0.255 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 1 SCHEDULING 401.78 401.78 0.029 0.029 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 1 SOIL 540.11 540.11 0.040 0.099 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 29.70 0.01715
FLOOR 1 SOIL HOLD 238.93 238.93 0.018 0.044 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 32.33 0.01715
FLOOR 1 SOIL WORK 728.98 728.98 0.054 0.142 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 29.70 0.01715
FLOOR 1 STEP DOWN 2390.36 2390.36 0.176 0.176 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 32.35 0.01715
FLOOR 2 CONFERENCE 2884.35 2884.35 0.250 0.250 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:50:00 32.22 0.01715
FLOOR 2 DICTATION 255.38 255.38 0.021 0.021 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM 1 3235.47 3235.47 0.281 0.281 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 32.35 0.01715
FLOOR 2 EXAM 2 2419.46 2419.46 0.210 0.255 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 2 EXAM 3 3274.01 3274.01 0.284 0.340 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 2 EXAM 4 565.58 565.58 0.049 0.049 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20 0.01715
FLOOR 2 EXAM 5 2698.12 2698.12 0.234 0.234 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 30.99 0.01715
FLOOR 2 EXAM 6 1217.82 1217.82 0.106 0.106 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.82 0.01715
FLOOR 2 EXAM 7 3344.47 3344.47 0.290 0.374 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.82 0.01715
FLOOR 2 EXAM 8 1493.83 1493.83 0.130 0.130 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 31.82 0.01715
FLOOR 2 EXAM 9 1793.14 1793.14 0.155 0.187 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 32.35 0.01715
FLOOR 2 LOUNGE 393.49 393.49 0.034 0.034 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.67 0.01715
FLOOR 2 NURSE STATION 1 658.87 658.87 0.057 0.057 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.67 0.01715
FLOOR 2 NURSE STATION 2 805.08 805.08 0.070 0.070 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.67 0.01715
FLOOR 2 OFFICE 3526.62 3526.62 0.306 0.306 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 30.99 0.01715
FLOOR 2 RECEPTION 6346.81 6346.81 0.550 0.550 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 32.35 0.01715
FLOOR 2 SCHEDULING 1 937.38 937.38 0.081 0.081 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 28.67 0.01715
FLOOR 2 SCHEDULING 2 1028.53 1028.53 0.086 0.086 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 WORK 4833.53 4833.53 0.419 0.419 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.20 0.01715
FLOOR 2 X-RAY 8979.09 8979.09 0.778 0.778 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 3 DRESSING ROOM 215.48 215.48 0.019 0.019 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 3 HUMID 535.66 535.66 0.046 0.046 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 3 LOCKER 805.24 805.24 0.070 0.070 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 3 LOUNGE 4703.81 4703.81 0.408 0.408 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 3 OFFICE 12328.48 12328.48 1.068 1.068 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 3 PHYSICAL THERAPY 1 8784.46 8784.46 0.761 0.761 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.20 0.01715
FLOOR 3 PHYSICAL THERAPY 2 3239.20 3239.20 0.281 0.281 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20 0.01715
FLOOR 3 TREATMENT 2691.58 2691.58 0.233 0.233 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 3 WORK 4061.97 4061.97 0.352 0.352 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 31.32 0.01715
FLOOR 1 BIO HAZ 121.59 121.59 0.009 0.009 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 ELECTRICAL ROOM 657.85 657.85 0.048 0.048 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 32.11 0.01715
FLOOR 1 ELEVATOR PUMP ROOM 3735.23 3735.23 0.266 0.266 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 IT HALL 288.51 288.51 0.021 0.021 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 LOBBY HALL 574.95 574.95 0.041 0.041 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 LOBBY TOILET 485.29 485.29 0.036 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 1 LOCKER ROOM HALL 865.27 865.27 0.061 0.061 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 MED GAS 329.99 329.99 0.024 0.024 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:40:00 32.69 0.01715
FLOOR 1 MRI HALL 381.40 381.40 0.027 0.027 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 MRI TOILET 177.64 177.64 0.013 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 33.00 0.01715
FLOOR 1 NURSE HALL 1020.98 1020.98 0.072 0.072 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 NURSE JANITOR 125.94 125.94 0.009 0.009 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 NURSE TOILET 146.00 146.00 0.010 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 PRE-OP HALL 1039.23 1039.23 0.074 0.074 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 PRE-OP TOILET 240.64 240.64 0.018 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 1 RECEPTION HALL 269.24 269.24 0.019 0.019 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 SCRUB 167.61 167.61 0.012 0.012 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 STERILE HALL 1059.64 1059.64 0.075 0.075 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 STERILE STORAGE 614.17 614.17 0.044 0.044 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 STORAGE 2959.15 2959.15 0.217 0.217 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 32.44 0.01715
FLOOR 1 SUB-STERILE 927.03 927.03 0.068 0.068 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 30.99 0.01715
FLOOR 1 UTILITY HALL 1129.61 1129.61 0.083 0.083 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 31.16 0.01715
FLOOR 1 UTILITY JANITOR 98.14 98.14 0.007 0.007 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 1 UTILITY ROOM 1281.21 1281.21 0.094 0.094 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 30.99 0.01715
FLOOR 1 VESTIBULE 481.32 481.32 0.035 0.035 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 32.44 0.01715
FLOOR 2 CONFERENCE TOILET 208.05 208.05 0.017 0.050 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM HALL 1 608.03 608.03 0.051 0.051 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM HALL 2 593.79 593.79 0.050 0.050 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM HALL 3 573.93 573.93 0.048 0.048 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM HALL 4 601.38 601.38 0.050 0.050 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM HALL 5 632.22 632.22 0.053 0.053 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 EXAM HALL 6 633.69 633.69 0.053 0.053 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 JANITOR 523.12 523.12 0.045 0.045 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 2 OFFICE HALL 1277.33 1277.33 0.107 0.107 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 RECEPTION HALL 1810.82 1810.82 0.151 0.151 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 RECEPTION TOILET 390.07 390.07 0.033 0.099 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 STORAGE 1 179.04 179.04 0.015 0.015 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 STORAGE 2 327.25 327.25 0.027 0.027 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 STORAGE 3 417.39 417.39 0.035 0.035 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 UTILITY 765.64 765.64 0.066 0.066 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 30.99 0.01715
FLOOR 2 WORK HALL 2538.96 2538.96 0.212 0.212 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 06:20:00 26.79 0.01715
FLOOR 2 WORK TOILET 270.17 270.17 0.023 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 3 ELEVATOR HALL 1117.20 1117.20 0.097 0.097 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.20 0.01715
FLOOR 3 JANITOR 350.91 350.91 0.030 0.030 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 3 LOUNGE TOILET 893.91 893.91 0.077 0.151 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20 0.01715
FLOOR 3 MECHANICAL 4012.47 4012.47 0.348 0.348 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 31.32 0.01715
FLOOR 3 MECHANICAL HALL 1246.72 1246.72 0.108 0.108 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 33.03 0.01715
FLOOR 3 OFFICE HALL 2804.46 2804.46 0.243 0.243 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 33.20 0.01715
FLOOR 3 OFFICE TOILET 258.13 258.13 0.022 0.042 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
FLOOR 3 PHYSICAL THERAPY TOILET 317.06 317.06 0.027 0.066 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 3 STORAGE 1 368.65 368.65 0.032 0.032 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20 0.01715
FLOOR 3 STORAGE 2 319.80 319.80 0.028 0.028 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 33.20 0.01715
FLOOR 3 UNDEVELOPED 1 10293.41 10293.41 0.892 0.892 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.80 0.01715
FLOOR 3 UNDEVELOPED 2 5399.90 5399.90 0.468 0.468 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.80 0.01715
FLOOR 3 UTILITY 631.23 631.23 0.055 0.055 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 33.20 0.01715
NE STAIR 2293.38 2293.38 0.199 0.199 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 12:40:00 32.69 0.01715
NW ELEVATOR 1742.69 1742.69 0.151 0.151 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.59 0.01715
NW STAIR 2754.88 2754.88 0.239 0.239 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715
SW STAIR 1204.28 1204.28 0.104 0.104 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 31.93 0.01715


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FLOOR 1 ANESTHESIA 44.58 44.58 0.002 0.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 CAFE 8.12 8.12 0.000 0.184 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70 0.00699
FLOOR 1 CLEAN 0.00 0.00 0.000 0.018 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 CLEAN WORK 0.00 0.00 0.000 0.023 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 DICTATION 0.00 0.00 0.000 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 DRESSING ROOM 147.27 147.27 0.006 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 HUMID 0.00 0.00 0.000 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 IT ROOM 0.00 0.00 0.000 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 LOBBY 62.92 62.92 0.003 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:40:00 8.70 0.00699
FLOOR 1 LOCKER ROOM 0.00 0.00 0.000 0.042 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 LOUNGE 0.00 0.00 0.000 0.023 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 MRI CONTROL ROOM 0.00 0.00 0.000 0.024 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 MRI ROOM 0.00 0.00 0.000 0.062 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 NOURISHMENT 0.00 0.00 0.000 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 NURSE STATION 0.00 0.00 0.000 0.020 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 OFFICE 0.00 0.00 0.000 0.019 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 OPERATING ROOM 1 0.00 0.00 0.000 0.239 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 OPERATING ROOM 2 0.00 0.00 0.000 0.249 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 OPERATING ROOM 3 0.00 0.00 0.000 0.247 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 PACU 0.00 0.00 0.000 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 PRE-OP ROOM 1 0.00 0.00 0.000 0.052 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 PRE-OP ROOM 2 0.00 0.00 0.000 0.093 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 PROCEDURE ROOM 0.00 0.00 0.000 0.108 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 RECEPTION 0.00 0.00 0.000 0.050 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 RECOVERY ROOM 28.70 28.70 0.001 0.161 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70 0.00699
FLOOR 1 SCHEDULING 0.00 0.00 0.000 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 SOIL 0.00 0.00 0.000 0.018 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 SOIL HOLD 0.00 0.00 0.000 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 SOIL WORK 0.00 0.00 0.000 0.025 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 STEP DOWN 275.87 275.87 0.012 0.090 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 CONFERENCE 815.50 815.50 0.034 0.049 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 DICTATION 0.00 0.00 0.000 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 EXAM 1 833.61 833.61 0.035 0.051 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM 2 0.00 0.00 0.000 0.076 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 EXAM 3 2.55 2.55 0.000 0.102 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70 0.00699
FLOOR 2 EXAM 4 193.27 193.27 0.008 0.012 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM 5 521.92 521.92 0.022 0.050 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM 6 209.19 209.19 0.009 0.032 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM 7 0.00 0.00 0.000 0.112 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 EXAM 8 131.59 131.59 0.006 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM 9 0.00 0.00 0.000 0.056 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 LOUNGE 0.00 0.00 0.000 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 NURSE STATION 1 0.00 0.00 0.000 0.011 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 NURSE STATION 2 0.00 0.00 0.000 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 OFFICE 1145.51 1145.51 0.048 0.048 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 RECEPTION 604.79 604.79 0.025 0.098 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 SCHEDULING 1 0.00 0.00 0.000 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 SCHEDULING 2 0.00 0.00 0.000 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 WORK 0.00 0.00 0.000 0.068 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 X-RAY 0.00 0.00 0.000 0.127 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 3 DRESSING ROOM 15.17 15.17 0.001 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 HUMID 19.06 19.06 0.001 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 LOCKER 12.62 12.62 0.001 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:40:00 8.70 0.00699
FLOOR 3 LOUNGE 0.00 0.00 0.000 0.048 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 3 OFFICE 1438.69 1438.69 0.061 0.122 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 PHYSICAL THERAPY 1 2427.69 2427.69 0.101 0.184 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 PHYSICAL THERAPY 2 367.00 367.00 0.015 0.084 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 TREATMENT 122.41 122.41 0.005 0.067 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 WORK 1289.52 1289.52 0.054 0.054 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 BIO HAZ 30.66 30.66 0.001 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 ELEVATOR PUMP ROOM 72.11 72.11 0.003 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 IT HALL 0.00 0.00 0.000 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 LOBBY HALL 0.00 0.00 0.000 0.007 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 LOBBY TOILET 97.70 97.70 0.004 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.000 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 MED GAS 282.45 282.45 0.012 0.012 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 MRI HALL 0.00 0.00 0.000 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 MRI TOILET 38.94 38.94 0.002 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 NURSE HALL 0.00 0.00 0.000 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 NURSE JANITOR 0.00 0.00 0.000 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 PRE-OP HALL 0.00 0.00 0.000 0.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 PRE-OP TOILET 96.98 96.98 0.004 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 RECEPTION HALL 0.00 0.00 0.000 0.004 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 SCRUB 1.80 1.80 0.000 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:40:00 8.70 0.00699
FLOOR 1 STERILE HALL 0.00 0.00 0.000 0.017 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 STERILE STORAGE 0.00 0.00 0.000 0.022 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 1 STORAGE 1964.06 1964.06 0.082 0.082 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 SUB-STERILE 337.31 337.31 0.014 0.014 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 UTILITY HALL 552.86 552.86 0.023 0.023 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 UTILITY JANITOR 2.50 2.50 0.000 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 UTILITY ROOM 609.38 609.38 0.026 0.026 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 1 VESTIBULE 150.10 150.10 0.006 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 CONFERENCE TOILET 11.59 11.59 0.000 0.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM HALL 1 78.95 78.95 0.003 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 EXAM HALL 2 0.00 0.00 0.000 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 EXAM HALL 3 0.69 0.69 0.000 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:10:00 8.70 0.00699
FLOOR 2 EXAM HALL 4 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 EXAM HALL 5 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 EXAM HALL 6 0.00 0.00 0.000 0.006 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 JANITOR 284.68 284.68 0.012 0.012 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 OFFICE HALL 83.83 83.83 0.004 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 RECEPTION HALL 0.00 0.00 0.000 0.016 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 STORAGE 1 5.75 5.75 0.000 0.003 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 STORAGE 2 0.00 0.00 0.000 0.007 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 STORAGE 3 0.00 0.00 0.000 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 UTILITY 360.12 360.12 0.015 0.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 2 WORK HALL 0.00 0.00 0.000 0.024 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   8.70 0.00699
FLOOR 2 WORK TOILET 167.53 167.53 0.007 0.007 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 ELEVATOR HALL 440.28 440.28 0.019 0.019 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 JANITOR 305.63 305.63 0.013 0.013 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 LOUNGE TOILET 402.53 402.53 0.017 0.017 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 MECHANICAL HALL 502.12 502.12 0.021 0.021 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 OFFICE HALL 644.55 644.55 0.027 0.027 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 OFFICE TOILET 199.79 199.79 0.008 0.008 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 PHYSICAL THERAPY TOILET 54.25 54.25 0.002 0.002 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 STORAGE 1 157.93 157.93 0.007 0.007 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 STORAGE 2 115.15 115.15 0.005 0.005 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 UNDEVELOPED 1 2320.05 2320.05 0.097 0.128 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 UNDEVELOPED 2 2052.00 2052.00 0.086 0.086 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
FLOOR 3 UTILITY 286.92 286.92 0.012 0.012 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
NE STAIR 1877.45 1877.45 0.079 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
NW ELEVATOR 1111.04 1111.04 0.047 0.047 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
NW STAIR 1862.62 1862.62 0.079 0.079 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699
SW STAIR 895.36 895.36 0.038 0.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:20:00 8.70 0.00699


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
AHU-1 7.23 7.23 2.16 2.16
AHU-2 11.16 11.16 2.28 2.28



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FLOOR 1 ANESTHESIA 3365.00 7828.83 3365.00
FLOOR 1 CAFE 1022.50 6888.17 583.33
FLOOR 1 CLEAN 1629.67 7830.00 1629.67
FLOOR 1 CLEAN WORK 2689.33 7830.00 2689.33
FLOOR 1 DICTATION 230.83 7830.00 230.83
FLOOR 1 DRESSING ROOM 528.83 7743.83 523.17
FLOOR 1 HUMID 56.50 7830.00 56.50
FLOOR 1 IT ROOM 227.67 7830.00 227.67
FLOOR 1 LOBBY 334.50 7403.00 168.00
FLOOR 1 LOCKER ROOM 80.17 7683.67 60.00
FLOOR 1 LOUNGE 59.00 7801.83 59.00
FLOOR 1 MRI CONTROL ROOM 167.50 7328.17 79.67
FLOOR 1 MRI ROOM 108.50 7213.33 45.00
FLOOR 1 NOURISHMENT 143.67 7830.00 143.67
FLOOR 1 NURSE STATION 221.17 7830.00 221.17
FLOOR 1 OFFICE 49.17 7830.00 49.17
FLOOR 1 OPERATING ROOM 1 4340.67 7830.00 4340.67
FLOOR 1 OPERATING ROOM 2 5157.50 7830.00 5157.50
FLOOR 1 OPERATING ROOM 3 7447.00 7830.00 7447.00
FLOOR 1 PACU 3354.83 7830.00 3354.83
FLOOR 1 PRE-OP ROOM 1 3436.50 7830.00 3436.50
FLOOR 1 PRE-OP ROOM 2 3556.67 7830.00 3556.67
FLOOR 1 PROCEDURE ROOM 3333.00 7830.00 3333.00
FLOOR 1 RECEPTION 134.67 7569.83 72.00
FLOOR 1 RECOVERY ROOM 2876.33 7756.17 2871.17
FLOOR 1 SCHEDULING 173.67 7830.00 173.67
FLOOR 1 SOIL 3967.50 7830.00 3967.50
FLOOR 1 SOIL HOLD 3937.83 7830.00 3937.83
FLOOR 1 SOIL WORK 4002.67 7830.00 4002.67
FLOOR 1 STEP DOWN 3016.50 7741.83 2994.00
FLOOR 2 CONFERENCE 1402.50 6561.17 693.33
FLOOR 2 DICTATION 779.33 7830.00 779.33
FLOOR 2 EXAM 1 3321.17 7590.17 3158.17
FLOOR 2 EXAM 2 2899.50 7757.00 2884.83
FLOOR 2 EXAM 3 3118.83 7766.83 3107.50
FLOOR 2 EXAM 4 2853.33 7438.17 2638.33
FLOOR 2 EXAM 5 3245.83 7510.67 3081.17
FLOOR 2 EXAM 6 2806.83 7576.33 2661.67
FLOOR 2 EXAM 7 3146.67 7794.83 3143.83
FLOOR 2 EXAM 8 2717.33 7544.83 2540.17
FLOOR 2 EXAM 9 2725.33 7735.83 2701.50
FLOOR 2 LOUNGE 571.67 7798.67 571.00
FLOOR 2 NURSE STATION 1 331.67 7596.83 271.67
FLOOR 2 NURSE STATION 2 326.67 7525.00 214.33
FLOOR 2 OFFICE 634.83 7523.83 542.17
FLOOR 2 RECEPTION 832.67 6785.83 212.00
FLOOR 2 SCHEDULING 1 203.33 7747.33 201.83
FLOOR 2 SCHEDULING 2 202.67 7736.67 200.00
FLOOR 2 WORK 325.17 7359.67 134.33
FLOOR 2 X-RAY 1088.00 6260.33 0.00
FLOOR 3 DRESSING ROOM 1295.50 7674.83 1248.83
FLOOR 3 HUMID 1009.00 7558.50 888.17
FLOOR 3 LOCKER 856.83 7291.33 522.33
FLOOR 3 LOUNGE 1093.17 6740.00 352.50
FLOOR 3 OFFICE 924.17 6939.00 403.83
FLOOR 3 PHYSICAL THERAPY 1 3790.50 6929.33 3123.17
FLOOR 3 PHYSICAL THERAPY 2 3601.67 7530.00 3401.17
FLOOR 3 TREATMENT 3357.50 7463.17 3107.17
FLOOR 3 WORK 1548.50 6772.17 1004.00
FLOOR 1 BIO HAZ 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.00 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 0.00 0.00 0.00
FLOOR 1 LOBBY TOILET 0.00 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00
FLOOR 1 MED GAS 0.00 0.00 0.00
FLOOR 1 MRI HALL 0.00 0.00 0.00
FLOOR 1 MRI TOILET 0.00 0.00 0.00
FLOOR 1 NURSE HALL 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.00 0.00
FLOOR 1 STERILE HALL 0.00 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00
FLOOR 1 STORAGE 0.00 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 0.00 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.00 0.00
FLOOR 1 VESTIBULE 0.00 0.00 0.00
FLOOR 2 CONFERENCE TOILET 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 0.00 0.00 0.00
FLOOR 2 EXAM HALL 2 0.00 0.00 0.00
FLOOR 2 EXAM HALL 3 0.00 0.00 0.00
FLOOR 2 EXAM HALL 4 0.00 0.00 0.00
FLOOR 2 EXAM HALL 5 0.00 0.00 0.00
FLOOR 2 EXAM HALL 6 0.00 0.00 0.00
FLOOR 2 JANITOR 0.00 0.00 0.00
FLOOR 2 OFFICE HALL 0.00 0.00 0.00
FLOOR 2 RECEPTION HALL 0.00 0.00 0.00
FLOOR 2 RECEPTION TOILET 0.00 0.00 0.00
FLOOR 2 STORAGE 1 0.00 0.00 0.00
FLOOR 2 STORAGE 2 0.00 0.00 0.00
FLOOR 2 STORAGE 3 0.00 0.00 0.00
FLOOR 2 UTILITY 0.00 0.00 0.00
FLOOR 2 WORK HALL 0.00 0.00 0.00
FLOOR 2 WORK TOILET 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 0.00 0.00 0.00
FLOOR 3 JANITOR 0.00 0.00 0.00
FLOOR 3 LOUNGE TOILET 0.00 0.00 0.00
FLOOR 3 MECHANICAL 0.00 0.00 0.00
FLOOR 3 MECHANICAL HALL 0.00 0.00 0.00
FLOOR 3 OFFICE HALL 0.00 0.00 0.00
FLOOR 3 OFFICE TOILET 0.00 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 0.00 0.00
FLOOR 3 STORAGE 2 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 1 0.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 0.00 0.00 0.00
FLOOR 3 UTILITY 0.00 0.00 0.00
NE STAIR 0.00 0.00 0.00
NW ELEVATOR 0.00 0.00 0.00
NW STAIR 0.00 0.00 0.00
SW STAIR 0.00 0.00 0.00
Facility 7828.00 7830.00 7595.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FLOOR 1 ANESTHESIA 0.00 4.00 0.00 4.00
FLOOR 1 CAFE 0.00 492.67 0.00 492.67
FLOOR 1 CLEAN 0.00 90.50 0.00 90.50
FLOOR 1 CLEAN WORK 0.00 26.67 0.00 26.67
FLOOR 1 DICTATION 0.00 5.50 0.00 5.50
FLOOR 1 DRESSING ROOM 0.00 102.67 0.00 102.67
FLOOR 1 HUMID 0.00 32.33 0.00 32.33
FLOOR 1 IT ROOM 0.00 24.83 0.00 24.83
FLOOR 1 LOBBY 0.00 56.50 0.00 56.50
FLOOR 1 LOCKER ROOM 0.00 189.33 0.00 189.33
FLOOR 1 LOUNGE 0.00 170.67 0.00 170.67
FLOOR 1 MRI CONTROL ROOM 0.00 339.83 0.00 339.83
FLOOR 1 MRI ROOM 0.00 359.17 0.00 359.17
FLOOR 1 NOURISHMENT 0.00 100.33 0.00 100.33
FLOOR 1 NURSE STATION 0.00 71.17 0.00 71.17
FLOOR 1 OFFICE 0.00 71.50 0.00 71.50
FLOOR 1 OPERATING ROOM 1 0.00 319.50 0.00 319.50
FLOOR 1 OPERATING ROOM 2 0.00 265.83 0.00 265.83
FLOOR 1 OPERATING ROOM 3 0.00 245.33 0.00 245.33
FLOOR 1 PACU 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 1 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP ROOM 2 0.00 0.00 0.00 0.00
FLOOR 1 PROCEDURE ROOM 1.17 0.00 1.17 0.00
FLOOR 1 RECEPTION 0.00 228.83 0.00 228.83
FLOOR 1 RECOVERY ROOM 0.00 155.67 0.00 155.67
FLOOR 1 SCHEDULING 0.00 37.17 0.00 37.17
FLOOR 1 SOIL 0.00 0.00 0.00 0.00
FLOOR 1 SOIL HOLD 0.50 0.00 0.50 0.00
FLOOR 1 SOIL WORK 0.00 0.00 0.00 0.00
FLOOR 1 STEP DOWN 0.00 86.83 0.00 86.83
FLOOR 2 CONFERENCE 0.17 692.50 0.17 692.50
FLOOR 2 DICTATION 8.83 107.33 8.83 107.33
FLOOR 2 EXAM 1 0.17 217.83 0.17 217.83
FLOOR 2 EXAM 2 0.00 253.50 0.00 253.50
FLOOR 2 EXAM 3 0.00 228.67 0.00 228.67
FLOOR 2 EXAM 4 0.17 564.67 0.17 564.67
FLOOR 2 EXAM 5 0.00 334.50 0.00 334.50
FLOOR 2 EXAM 6 0.00 453.17 0.00 453.17
FLOOR 2 EXAM 7 0.00 185.50 0.00 185.50
FLOOR 2 EXAM 8 0.00 481.83 0.00 481.83
FLOOR 2 EXAM 9 0.00 271.67 0.00 271.67
FLOOR 2 LOUNGE 0.00 406.50 0.00 406.50
FLOOR 2 NURSE STATION 1 0.00 599.83 0.00 599.83
FLOOR 2 NURSE STATION 2 0.00 630.83 0.00 630.83
FLOOR 2 OFFICE 2.00 281.50 2.00 281.50
FLOOR 2 RECEPTION 0.00 600.67 0.00 600.67
FLOOR 2 SCHEDULING 1 0.17 410.33 0.17 410.33
FLOOR 2 SCHEDULING 2 0.17 387.83 0.17 387.83
FLOOR 2 WORK 0.67 556.50 0.67 556.50
FLOOR 2 X-RAY 0.00 926.83 0.00 926.83
FLOOR 3 DRESSING ROOM 8.00 314.00 8.00 314.00
FLOOR 3 HUMID 4.83 373.50 4.83 373.50
FLOOR 3 LOCKER 0.00 581.50 0.00 581.50
FLOOR 3 LOUNGE 0.00 715.50 0.00 715.50
FLOOR 3 OFFICE 2.50 608.00 2.50 608.00
FLOOR 3 PHYSICAL THERAPY 1 0.00 697.33 0.00 697.33
FLOOR 3 PHYSICAL THERAPY 2 0.00 468.33 0.00 468.33
FLOOR 3 TREATMENT 0.00 478.50 0.00 478.50
FLOOR 3 WORK 5.50 465.17 5.50 465.17
FLOOR 1 BIO HAZ 2.17 0.00 0.00 0.00
FLOOR 1 ELECTRICAL ROOM 0.00 101.33 0.00 0.00
FLOOR 1 ELEVATOR PUMP ROOM 0.00 194.33 0.00 0.00
FLOOR 1 IT HALL 0.00 0.00 0.00 0.00
FLOOR 1 LOBBY HALL 0.00 84.00 0.00 0.00
FLOOR 1 LOBBY TOILET 3.00 0.67 0.00 0.00
FLOOR 1 LOCKER ROOM HALL 0.00 0.00 0.00 0.00
FLOOR 1 MED GAS 0.00 32.50 0.00 0.00
FLOOR 1 MRI HALL 0.00 5.33 0.00 0.00
FLOOR 1 MRI TOILET 3.50 0.00 0.00 0.00
FLOOR 1 NURSE HALL 0.00 0.00 0.00 0.00
FLOOR 1 NURSE JANITOR 0.00 0.00 0.00 0.00
FLOOR 1 NURSE TOILET 10.00 0.00 0.00 0.00
FLOOR 1 PRE-OP HALL 0.00 0.00 0.00 0.00
FLOOR 1 PRE-OP TOILET 11.33 0.00 0.00 0.00
FLOOR 1 RECEPTION HALL 0.00 0.00 0.00 0.00
FLOOR 1 SCRUB 0.00 0.83 0.00 0.00
FLOOR 1 STERILE HALL 0.00 26.67 0.00 0.00
FLOOR 1 STERILE STORAGE 0.00 0.00 0.00 0.00
FLOOR 1 STORAGE 1.17 62.67 0.00 0.00
FLOOR 1 SUB-STERILE 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY HALL 0.00 2.33 0.00 0.00
FLOOR 1 UTILITY JANITOR 0.00 0.00 0.00 0.00
FLOOR 1 UTILITY ROOM 0.00 0.00 0.00 0.00
FLOOR 1 VESTIBULE 340.50 2414.33 0.00 0.00
FLOOR 2 CONFERENCE TOILET 4681.17 0.00 0.00 0.00
FLOOR 2 EXAM HALL 1 8.00 147.50 0.00 0.00
FLOOR 2 EXAM HALL 2 9.00 109.67 0.00 0.00
FLOOR 2 EXAM HALL 3 10.17 69.33 0.00 0.00
FLOOR 2 EXAM HALL 4 7.33 150.33 0.00 0.00
FLOOR 2 EXAM HALL 5 6.00 182.67 0.00 0.00
FLOOR 2 EXAM HALL 6 6.50 174.00 0.00 0.00
FLOOR 2 JANITOR 2.17 146.67 0.00 0.00
FLOOR 2 OFFICE HALL 5.83 152.17 0.00 0.00
FLOOR 2 RECEPTION HALL 4.50 169.50 0.00 0.00
FLOOR 2 RECEPTION TOILET 4271.67 0.00 0.00 0.00
FLOOR 2 STORAGE 1 28.00 0.83 0.00 0.00
FLOOR 2 STORAGE 2 7.00 94.00 0.00 0.00
FLOOR 2 STORAGE 3 5.50 133.67 0.00 0.00
FLOOR 2 UTILITY 8.83 111.83 0.00 0.00
FLOOR 2 WORK HALL 1.67 253.50 0.00 0.00
FLOOR 2 WORK TOILET 4.67 0.00 0.00 0.00
FLOOR 3 ELEVATOR HALL 6.67 442.83 0.00 0.00
FLOOR 3 JANITOR 8.50 241.83 0.00 0.00
FLOOR 3 LOUNGE TOILET 6.00 14.67 0.00 0.00
FLOOR 3 MECHANICAL 3.83 694.17 0.00 0.00
FLOOR 3 MECHANICAL HALL 5.67 400.67 0.00 0.00
FLOOR 3 OFFICE HALL 4.17 476.33 0.00 0.00
FLOOR 3 OFFICE TOILET 14.83 2.17 0.00 0.00
FLOOR 3 PHYSICAL THERAPY TOILET 3.00 0.00 0.00 0.00
FLOOR 3 STORAGE 1 0.00 186.00 0.00 0.00
FLOOR 3 STORAGE 2 7.67 316.33 0.00 0.00
FLOOR 3 UNDEVELOPED 1 2.83 526.00 0.00 0.00
FLOOR 3 UNDEVELOPED 2 2.33 585.83 0.00 0.00
FLOOR 3 UTILITY 17.67 192.00 0.00 0.00
NE STAIR 19.33 606.33 0.00 0.00
NW ELEVATOR 18.17 190.33 0.00 0.00
NW STAIR 18.00 473.00 0.00 0.00
SW STAIR 11.50 471.50 0.00 0.00
Facility 4708.67 2594.33 13.17 1087.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2015-09-13 14:22:46

AirTerminal:SingleDuct:VAV:Reheat

Maximum Air Flow Rate [m3/s] Maximum Reheat Water Flow Rate [m3/s] Reheat Coil Sizing Air Volume Flow Rate [m3/s]
FLOOR 1 ANESTHESIA VAV BOX COMPONENT 0.067956 0.000044 0.067956
FLOOR 1 BIO HAZ VAV BOX COMPONENT 0.008710 0.000002 0.002613
FLOOR 1 CAFE VAV BOX COMPONENT 0.287906 0.000056 0.086372
FLOOR 1 CLEAN VAV BOX COMPONENT 0.040084 0.000026 0.040084
FLOOR 1 CLEAN WORK VAV BOX COMPONENT 0.051911 0.000033 0.051911
FLOOR 1 DICTATION VAV BOX COMPONENT 0.025095 0.000005 0.007528
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT 0.021013 0.000004 0.006304
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT 0.048285 0.000009 0.014485
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT 0.265613 0.000051 0.079684
FLOOR 1 HUMID VAV BOX COMPONENT 0.012457 0.000002 0.003737
FLOOR 1 IT HALL VAV BOX COMPONENT 0.020641 0.000004 0.006192
FLOOR 1 IT ROOM VAV BOX COMPONENT 0.021257 0.000004 0.006377
FLOOR 1 LOBBY VAV BOX COMPONENT 0.289570 0.000056 0.086871
FLOOR 1 LOBBY HALL VAV BOX COMPONENT 0.040612 0.000008 0.012184
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT 0.042473 0.000027 0.042473
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT 0.232601 0.000045 0.069780
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT 0.061487 0.000012 0.018446
FLOOR 1 LOUNGE VAV BOX COMPONENT 0.110717 0.000021 0.033215
FLOOR 1 MED GAS VAV BOX COMPONENT 0.024224 0.000008 0.011965
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT 0.131588 0.000025 0.039476
FLOOR 1 MRI HALL VAV BOX COMPONENT 0.027017 0.000005 0.008105
FLOOR 1 MRI ROOM VAV BOX COMPONENT 0.318035 0.000061 0.095410
FLOOR 1 MRI TOILET VAV BOX COMPONENT 0.042473 0.000027 0.042473
FLOOR 1 NOURISHMENT VAV BOX COMPONENT 0.055817 0.000011 0.016745
FLOOR 1 NURSE HALL VAV BOX COMPONENT 0.072303 0.000014 0.021691
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT 0.009014 0.000002 0.002704
FLOOR 1 NURSE STATION VAV BOX COMPONENT 0.075414 0.000015 0.022624
FLOOR 1 NURSE TOILET VAV BOX COMPONENT 0.042473 0.000027 0.042473
FLOOR 1 OFFICE VAV BOX COMPONENT 0.082936 0.000016 0.024881
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT 0.793942 0.000512 0.793942
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT 0.828826 0.000534 0.828826
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT 0.748776 0.000483 0.748776
FLOOR 1 PACU VAV BOX COMPONENT 0.050967 0.000033 0.050967
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT 0.073633 0.000014 0.022090
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT 0.089192 0.000057 0.089192
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT 0.159508 0.000103 0.159508
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT 0.042473 0.000027 0.042473
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT 0.336241 0.000217 0.336241
FLOOR 1 RECEPTION VAV BOX COMPONENT 0.173431 0.000034 0.052029
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT 0.019152 0.000004 0.005746
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT 0.254836 0.000164 0.254836
FLOOR 1 SCHEDULING VAV BOX COMPONENT 0.029491 0.000006 0.008847
FLOOR 1 SCRUB VAV BOX COMPONENT 0.011988 0.000002 0.003597
FLOOR 1 SOIL VAV BOX COMPONENT 0.099103 0.000064 0.099103
FLOOR 1 SOIL HOLD VAV BOX COMPONENT 0.044046 0.000028 0.044046
FLOOR 1 SOIL WORK VAV BOX COMPONENT 0.141575 0.000091 0.141575
FLOOR 1 STEP DOWN VAV BOX COMPONENT 0.175508 0.000113 0.175508
FLOOR 1 STERILE HALL VAV BOX COMPONENT 0.075321 0.000015 0.022596
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT 0.043639 0.000008 0.013092
FLOOR 1 STORAGE VAV BOX COMPONENT 0.217183 0.000053 0.082328
FLOOR 1 SUB-STERILE VAV BOX COMPONENT 0.068043 0.000013 0.020413
FLOOR 1 UTILITY HALL VAV BOX COMPONENT 0.082907 0.000016 0.024872
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT 0.007039 0.000001 0.002112
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT 0.094036 0.000018 0.028211
FLOOR 1 VESTIBULE VAV BOX COMPONENT 0.035330 0.000007 0.010599
FLOOR 2 CONFERENCE VAV BOX COMPONENT 0.250187    
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT 0.050338    
FLOOR 2 DICTATION VAV BOX COMPONENT 0.021431    
FLOOR 2 EXAM 1 VAV BOX COMPONENT 0.280539    
FLOOR 2 EXAM 2 VAV BOX COMPONENT 0.254836    
FLOOR 2 EXAM 3 VAV BOX COMPONENT 0.339781    
FLOOR 2 EXAM 4 VAV BOX COMPONENT 0.049034    
FLOOR 2 EXAM 5 VAV BOX COMPONENT 0.233925    
FLOOR 2 EXAM 6 VAV BOX COMPONENT 0.106182    
FLOOR 2 EXAM 7 VAV BOX COMPONENT 0.373759    
FLOOR 2 EXAM 8 VAV BOX COMPONENT 0.129510    
FLOOR 2 EXAM 9 VAV BOX COMPONENT 0.186879    
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT 0.050811    
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT 0.049617    
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT 0.047971    
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT 0.050280    
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT 0.052828    
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT 0.052951    
FLOOR 2 JANITOR VAV BOX COMPONENT 0.045355    
FLOOR 2 LOUNGE VAV BOX COMPONENT 0.034105    
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT 0.057111    
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT 0.069784    
FLOOR 2 OFFICE VAV BOX COMPONENT 0.305702    
FLOOR 2 OFFICE HALL VAV BOX COMPONENT 0.106696    
FLOOR 2 RECEPTION VAV BOX COMPONENT 0.550327    
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT 0.151176    
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT 0.099103    
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT 0.081239    
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT 0.085780    
FLOOR 2 STORAGE 1 VAV BOX COMPONENT 0.015008    
FLOOR 2 STORAGE 2 VAV BOX COMPONENT 0.027316    
FLOOR 2 STORAGE 3 VAV BOX COMPONENT 0.034846    
FLOOR 2 UTILITY VAV BOX COMPONENT 0.066364    
FLOOR 2 WORK VAV BOX COMPONENT 0.418936    
FLOOR 2 WORK HALL VAV BOX COMPONENT 0.211957    
FLOOR 2 WORK TOILET VAV BOX COMPONENT 0.042473    
FLOOR 2 X-RAY VAV BOX COMPONENT 0.778340    
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT 0.018680    
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT 0.096819    
FLOOR 3 HUMID VAV BOX COMPONENT 0.046437    
FLOOR 3 JANITOR VAV BOX COMPONENT 0.030414    
FLOOR 3 LOCKER VAV BOX COMPONENT 0.069815    
FLOOR 3 LOUNGE VAV BOX COMPONENT 0.407726    
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT 0.151014    
FLOOR 3 MECHANICAL VAV BOX COMPONENT 0.347733    
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT 0.108073    
FLOOR 3 OFFICE VAV BOX COMPONENT 1.07    
FLOOR 3 OFFICE HALL VAV BOX COMPONENT 0.243040    
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT 0.042473    
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT 0.761494    
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT 0.280874    
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT 0.066069    
FLOOR 3 STORAGE 1 VAV BOX COMPONENT 0.031957    
FLOOR 3 STORAGE 2 VAV BOX COMPONENT 0.027722    
FLOOR 3 TREATMENT VAV BOX COMPONENT 0.233386    
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT 0.892049    
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT 0.467969    
FLOOR 3 UTILITY VAV BOX COMPONENT 0.054720    
FLOOR 3 WORK VAV BOX COMPONENT 0.352046    
NE STAIR VAV BOX COMPONENT 0.198792    
NW ELEVATOR VAV BOX COMPONENT 0.151052    
NW STAIR VAV BOX COMPONENT 0.238792    
SW STAIR VAV BOX COMPONENT 0.104386    


Coil:Heating:Water

Design Coil Load [W] Maximum Water Flow Rate [m3/s] U-Factor Times Area Value [W/K]
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL 2034.24 0.000044 43.86
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL 78.22 0.000002 5.62
FLOOR 1 CAFE VAV BOX REHEAT COIL 2585.50 0.000056 185.82
FLOOR 1 CLEAN VAV BOX REHEAT COIL 1199.91 0.000026 25.87
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL 1553.94 0.000033 33.50
FLOOR 1 DICTATION VAV BOX REHEAT COIL 225.36 0.000005 16.20
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL 188.71 0.000004 13.56
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL 433.62 0.000009 31.16
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL 2385.31 0.000051 171.43
FLOOR 1 HUMID VAV BOX REHEAT COIL 111.87 0.000002 8.04
FLOOR 1 IT HALL VAV BOX REHEAT COIL 185.37 0.000004 13.32
FLOOR 1 IT ROOM VAV BOX REHEAT COIL 190.89 0.000004 13.72
FLOOR 1 LOBBY VAV BOX REHEAT COIL 2600.45 0.000056 186.90
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL 364.71 0.000008 26.21
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL 1271.40 0.000027 27.41
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL 2088.85 0.000045 150.13
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL 552.18 0.000012 39.69
FLOOR 1 LOUNGE VAV BOX REHEAT COIL 994.28 0.000021 71.46
FLOOR 1 MED GAS VAV BOX REHEAT COIL 358.18 0.000008 15.64
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL 1181.71 0.000025 84.93
FLOOR 1 MRI HALL VAV BOX REHEAT COIL 242.62 0.000005 17.44
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL 2856.08 0.000061 205.27
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL 1271.40 0.000027 27.41
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL 501.26 0.000011 36.03
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL 649.31 0.000014 46.67
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL 80.95 0.000002 5.82
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL 677.25 0.000015 48.67
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL 1271.40 0.000027 27.41
FLOOR 1 OFFICE VAV BOX REHEAT COIL 744.80 0.000016 53.53
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL 23766.35 0.000512 512.43
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL 24810.60 0.000534 534.95
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL 22414.34 0.000483 483.28
FLOOR 1 PACU VAV BOX REHEAT COIL 1525.68 0.000033 32.90
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL 661.25 0.000014 47.52
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL 2669.94 0.000057 57.57
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL 4774.82 0.000103 102.95
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL 1271.40 0.000027 27.41
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL 10065.26 0.000217 217.02
FLOOR 1 RECEPTION VAV BOX REHEAT COIL 1557.48 0.000034 111.94
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL 171.99 0.000004 12.36
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL 7628.41 0.000164 164.48
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL 264.84 0.000006 19.03
FLOOR 1 SCRUB VAV BOX REHEAT COIL 107.66 0.000002 7.74
FLOOR 1 SOIL VAV BOX REHEAT COIL 2966.60 0.000064 63.96
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL 1318.49 0.000028 28.43
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL 4238.01 0.000091 91.38
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL 5253.76 0.000113 113.28
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL 676.42 0.000015 48.61
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL 391.89 0.000008 28.17
FLOOR 1 STORAGE VAV BOX REHEAT COIL 2464.45 0.000053 140.18
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL 611.05 0.000013 43.92
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL 744.53 0.000016 53.51
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL 63.22 0.000001 4.54
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL 844.48 0.000018 60.69
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL 317.27 0.000007 22.80
AHU-1_HEATC -699.9 0.000000 1.00
AHU-1_EXTRAWATERHEATC -699.9 0.000000 1.00
AHU-2_HEATC 54951.10 0.001183 892.02


Coil:Heating:Electric

Nominal Capacity [W]
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL 2209.25
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL 0.000000
FLOOR 2 DICTATION VAV BOX REHEAT COIL 189.25
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL 8257.60
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL 7501.02
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL 10001.36
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL 1443.29
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL 6885.51
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL 3125.42
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL 11001.49
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL 3812.08
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL 5500.75
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL 448.68
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL 438.14
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL 423.60
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL 444.00
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL 466.49
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL 467.58
FLOOR 2 JANITOR VAV BOX REHEAT COIL 400.50
FLOOR 2 LOUNGE VAV BOX REHEAT COIL 301.16
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL 504.32
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL 616.23
FLOOR 2 OFFICE VAV BOX REHEAT COIL 2699.48
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL 942.17
FLOOR 2 RECEPTION VAV BOX REHEAT COIL 4859.62
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL 1334.95
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL 0.000000
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL 717.38
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL 757.47
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL 132.53
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL 241.21
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL 307.70
FLOOR 2 UTILITY VAV BOX REHEAT COIL 586.02
FLOOR 2 WORK VAV BOX REHEAT COIL 3699.38
FLOOR 2 WORK HALL VAV BOX REHEAT COIL 1871.67
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL 1250.17
FLOOR 2 X-RAY VAV BOX REHEAT COIL 6873.07
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL 164.95
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL 854.95
FLOOR 3 HUMID VAV BOX REHEAT COIL 410.05
FLOOR 3 JANITOR VAV BOX REHEAT COIL 381.06
FLOOR 3 LOCKER VAV BOX REHEAT COIL 616.50
FLOOR 3 LOUNGE VAV BOX REHEAT COIL 3600.39
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL 4445.05
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL 0.000000
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL 954.33
FLOOR 3 OFFICE VAV BOX REHEAT COIL 9435.21
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL 2146.14
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL 1250.17
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL 22414.35
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL 8267.45
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL 1944.71
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL 940.63
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL 244.79
FLOOR 3 TREATMENT VAV BOX REHEAT COIL 6869.66
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL 7877.16
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL 4132.36
FLOOR 3 UTILITY VAV BOX REHEAT COIL 483.20
FLOOR 3 WORK VAV BOX REHEAT COIL 3108.71
NE STAIR VAV BOX REHEAT COIL 2334.28
NW ELEVATOR VAV BOX REHEAT COIL 1375.97
NW STAIR VAV BOX REHEAT COIL 2311.61
SW STAIR VAV BOX REHEAT COIL 1111.03


Branch

Maximum Flow Rate [m3/s]
AHU-1 AIR LOOP MAIN BRANCH 7.23
AHU-2 AIR LOOP MAIN BRANCH 11.16


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
AHU-1 7.23
AHU-2 11.16


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
AHU-1_OA_CONTROLLER 7.23 2.07
AHU-2_OA_CONTROLLER 11.16 5.55


Coil:Cooling:DX:TwoSpeed

Rated High Speed Air Flow Rate [m3/s] Rated High Speed Total Cooling Capacity (gross) [W] Rated High Speed Sensible Heat Ratio Rated Low Speed Air Flow Rate [m3/s] Rated Low Speed Total Cooling Capacity (gross) [W]
AHU-1_COOLC DXCOIL 7.23 179435.55 0.676083 2.41 59805.87
AHU-2_COOLC DXCOIL 11.16 277039.65 0.676083 3.72 92337.32


Fan:VariableVolume

Maximum Flow Rate [m3/s]
AHU-1_FAN 7.23
AHU-2_FAN 11.16


Controller:WaterCoil

Maximum Actuated Flow [m3/s]
AHU-1_HEATC_CONTROLLER 0.000000
AHU-1_EXTRAWATERHEATC_CONTROLLER 0.000000
AHU-2_HEATC_CONTROLLER 0.001183


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SWHSYS1 0.000063 0.047375
HEATSYS1 0.001327 0.995021


Boiler:HotWater

Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 0.001327


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000063


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SWHSYS1 PUMP 0.000063 8.07
HEATSYS1 PUMP 0.001327 338.95



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 ANESTHESIA

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.56 19.42
February 19.57 20.87
March 19.64 21.57
April 19.56 24.11
May 19.58 26.41
June 19.66 27.68
July 19.61 28.13
August 19.74 27.97
September 19.68 27.49
October 19.60 26.35
November 19.57 23.59
December 19.55 20.30
     
Annual Sum or Average 19.61 24.51
Minimum of Months 19.55 19.42
Maximum of Months 19.74 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 BIO HAZ

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.51 19.42
February 20.66 20.87
March 20.91 21.57
April 21.10 24.11
May 21.28 26.41
June 21.68 27.68
July 21.71 28.13
August 21.67 27.97
September 21.56 27.49
October 21.10 26.35
November 20.83 23.59
December 20.60 20.30
     
Annual Sum or Average 21.14 24.51
Minimum of Months 20.51 19.42
Maximum of Months 21.71 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 CAFE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.09 19.42
February 21.21 20.87
March 21.39 21.57
April 21.35 24.11
May 21.42 26.41
June 21.74 27.68
July 21.78 28.13
August 21.93 27.97
September 21.85 27.49
October 21.58 26.35
November 21.35 23.59
December 21.19 20.30
     
Annual Sum or Average 21.49 24.51
Minimum of Months 21.09 19.42
Maximum of Months 21.93 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 CLEAN

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.92 19.42
February 19.95 20.87
March 20.08 21.57
April 19.98 24.11
May 20.01 26.41
June 20.29 27.68
July 20.26 28.13
August 20.43 27.97
September 20.24 27.49
October 19.98 26.35
November 19.95 23.59
December 19.92 20.30
     
Annual Sum or Average 20.08 24.51
Minimum of Months 19.92 19.42
Maximum of Months 20.43 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 CLEAN WORK

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.73 19.42
February 19.75 20.87
March 19.86 21.57
April 19.77 24.11
May 19.80 26.41
June 20.01 27.68
July 19.98 28.13
August 20.13 27.97
September 19.97 27.49
October 19.77 26.35
November 19.73 23.59
December 19.71 20.30
     
Annual Sum or Average 19.85 24.51
Minimum of Months 19.71 19.42
Maximum of Months 20.13 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 DICTATION

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.28 19.42
February 21.33 20.87
March 21.45 21.57
April 21.38 24.11
May 21.40 26.41
June 21.67 27.68
July 21.62 28.13
August 21.74 27.97
September 21.64 27.49
October 21.40 26.35
November 21.36 23.59
December 21.31 20.30
     
Annual Sum or Average 21.47 24.51
Minimum of Months 21.28 19.42
Maximum of Months 21.74 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 DRESSING ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 19.42
February 20.75 20.87
March 21.06 21.57
April 21.32 24.11
May 21.64 26.41
June 21.98 27.68
July 22.06 28.13
August 21.98 27.97
September 21.88 27.49
October 21.48 26.35
November 21.08 23.59
December 20.66 20.30
     
Annual Sum or Average 21.37 24.51
Minimum of Months 20.48 19.42
Maximum of Months 22.06 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 ELECTRICAL ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.26 19.42
February 21.35 20.87
March 21.54 21.57
April 21.63 24.11
May 21.73 26.41
June 22.00 27.68
July 22.07 28.13
August 22.02 27.97
September 21.96 27.49
October 21.67 26.35
November 21.47 23.59
December 21.29 20.30
     
Annual Sum or Average 21.67 24.51
Minimum of Months 21.26 19.42
Maximum of Months 22.07 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 ELEVATOR PUMP ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.04 19.42
February 21.11 20.87
March 21.31 21.57
April 21.25 24.11
May 21.35 26.41
June 21.53 27.68
July 21.47 28.13
August 21.60 27.97
September 21.42 27.49
October 21.24 26.35
November 21.17 23.59
December 21.05 20.30
     
Annual Sum or Average 21.30 24.51
Minimum of Months 21.04 19.42
Maximum of Months 21.60 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 HUMID

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.52 19.42
February 21.59 20.87
March 21.70 21.57
April 21.65 24.11
May 21.66 26.41
June 21.96 27.68
July 21.94 28.13
August 22.03 27.97
September 21.94 27.49
October 21.67 26.35
November 21.63 23.59
December 21.57 20.30
     
Annual Sum or Average 21.74 24.51
Minimum of Months 21.52 19.42
Maximum of Months 22.03 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 IT HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 19.42
February 20.88 20.87
March 21.06 21.57
April 21.09 24.11
May 21.18 26.41
June 21.52 27.68
July 21.51 28.13
August 21.57 27.97
September 21.46 27.49
October 21.11 26.35
November 20.98 23.59
December 20.86 20.30
     
Annual Sum or Average 21.17 24.51
Minimum of Months 20.80 19.42
Maximum of Months 21.57 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 IT ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.10 19.42
February 21.21 20.87
March 21.42 21.57
April 21.48 24.11
May 21.58 26.41
June 21.89 27.68
July 21.91 28.13
August 21.92 27.97
September 21.82 27.49
October 21.48 26.35
November 21.32 23.59
December 21.18 20.30
     
Annual Sum or Average 21.53 24.51
Minimum of Months 21.10 19.42
Maximum of Months 21.92 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOBBY

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.94 19.42
February 21.15 20.87
March 21.44 21.57
April 21.61 24.11
May 21.70 26.41
June 21.96 27.68
July 22.05 28.13
August 22.04 27.97
September 21.94 27.49
October 21.61 26.35
November 21.29 23.59
December 21.09 20.30
     
Annual Sum or Average 21.57 24.51
Minimum of Months 20.94 19.42
Maximum of Months 22.05 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOBBY HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.64 19.42
February 21.75 20.87
March 21.91 21.57
April 21.94 24.11
May 21.96 26.41
June 22.26 27.68
July 22.32 28.13
August 22.35 27.97
September 22.30 27.49
October 22.02 26.35
November 21.86 23.59
December 21.75 20.30
     
Annual Sum or Average 22.01 24.51
Minimum of Months 21.64 19.42
Maximum of Months 22.35 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOBBY TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.59 19.42
February 19.62 20.87
March 19.76 21.57
April 19.71 24.11
May 19.75 26.41
June 19.83 27.68
July 19.76 28.13
August 19.87 27.97
September 19.75 27.49
October 19.66 26.35
November 19.62 23.59
December 19.58 20.30
     
Annual Sum or Average 19.71 24.51
Minimum of Months 19.58 19.42
Maximum of Months 19.87 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOCKER ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.39 19.42
February 21.49 20.87
March 21.67 21.57
April 21.72 24.11
May 21.85 26.41
June 22.16 27.68
July 22.21 28.13
August 22.21 27.97
September 22.10 27.49
October 21.78 26.35
November 21.62 23.59
December 21.47 20.30
     
Annual Sum or Average 21.81 24.51
Minimum of Months 21.39 19.42
Maximum of Months 22.21 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOCKER ROOM HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.28 19.42
February 21.36 20.87
March 21.50 21.57
April 21.49 24.11
May 21.52 26.41
June 21.87 27.68
July 21.87 28.13
August 21.94 27.97
September 21.85 27.49
October 21.54 26.35
November 21.44 23.59
December 21.35 20.30
     
Annual Sum or Average 21.59 24.51
Minimum of Months 21.28 19.42
Maximum of Months 21.94 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 LOUNGE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.49 19.42
February 21.57 20.87
March 21.72 21.57
April 21.72 24.11
May 21.78 26.41
June 22.06 27.68
July 22.10 28.13
August 22.13 27.97
September 22.02 27.49
October 21.73 26.35
November 21.64 23.59
December 21.55 20.30
     
Annual Sum or Average 21.79 24.51
Minimum of Months 21.49 19.42
Maximum of Months 22.13 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MED GAS

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.96 19.42
February 20.31 20.87
March 20.74 21.57
April 21.18 24.11
May 21.53 26.41
June 21.95 27.68
July 22.12 28.13
August 21.81 27.97
September 21.80 27.49
October 21.22 26.35
November 20.62 23.59
December 20.10 20.30
     
Annual Sum or Average 21.11 24.51
Minimum of Months 19.96 19.42
Maximum of Months 22.12 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI CONTROL ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.92 19.42
February 22.02 20.87
March 22.19 21.57
April 22.28 24.11
May 22.38 26.41
June 22.68 27.68
July 22.86 28.13
August 22.79 27.97
September 22.65 27.49
October 22.32 26.35
November 22.14 23.59
December 22.00 20.30
     
Annual Sum or Average 22.35 24.51
Minimum of Months 21.92 19.42
Maximum of Months 22.86 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.31 19.42
February 21.42 20.87
March 21.60 21.57
April 21.64 24.11
May 21.72 26.41
June 22.03 27.68
July 22.05 28.13
August 22.08 27.97
September 22.01 27.49
October 21.70 26.35
November 21.55 23.59
December 21.41 20.30
     
Annual Sum or Average 21.71 24.51
Minimum of Months 21.31 19.42
Maximum of Months 22.08 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.17 19.42
February 22.25 20.87
March 22.36 21.57
April 22.37 24.11
May 22.39 26.41
June 22.66 27.68
July 22.81 28.13
August 22.80 27.97
September 22.67 27.49
October 22.40 26.35
November 22.30 23.59
December 22.24 20.30
     
Annual Sum or Average 22.45 24.51
Minimum of Months 22.17 19.42
Maximum of Months 22.81 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 MRI TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.58 21.57
April 19.51 24.11
May 19.53 26.41
June 19.58 27.68
July 19.48 28.13
August 19.58 27.97
September 19.51 27.49
October 19.48 26.35
November 19.48 23.59
December 19.47 20.30
     
Annual Sum or Average 19.51 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.58 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NOURISHMENT

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.41 19.42
February 21.47 20.87
March 21.59 21.57
April 21.53 24.11
May 21.54 26.41
June 21.79 27.68
July 21.76 28.13
August 21.88 27.97
September 21.76 27.49
October 21.53 26.35
November 21.50 23.59
December 21.45 20.30
     
Annual Sum or Average 21.60 24.51
Minimum of Months 21.41 19.42
Maximum of Months 21.88 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.99 19.42
February 21.05 20.87
March 21.16 21.57
April 21.09 24.11
May 21.11 26.41
June 21.43 27.68
July 21.40 28.13
August 21.53 27.97
September 21.47 27.49
October 21.21 26.35
November 21.12 23.59
December 21.04 20.30
     
Annual Sum or Average 21.22 24.51
Minimum of Months 20.99 19.42
Maximum of Months 21.53 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE JANITOR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.40 19.42
February 21.47 20.87
March 21.60 21.57
April 21.57 24.11
May 21.58 26.41
June 21.94 27.68
July 21.93 28.13
August 22.02 27.97
September 21.93 27.49
October 21.61 26.35
November 21.54 23.59
December 21.47 20.30
     
Annual Sum or Average 21.67 24.51
Minimum of Months 21.40 19.42
Maximum of Months 22.02 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE STATION

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.30 19.42
February 21.35 20.87
March 21.48 21.57
April 21.41 24.11
May 21.42 26.41
June 21.68 27.68
July 21.63 28.13
August 21.76 27.97
September 21.66 27.49
October 21.44 26.35
November 21.39 23.59
December 21.33 20.30
     
Annual Sum or Average 21.49 24.51
Minimum of Months 21.30 19.42
Maximum of Months 21.76 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 NURSE TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.58 21.57
April 19.51 24.11
May 19.53 26.41
June 19.57 27.68
July 19.47 28.13
August 19.58 27.97
September 19.51 27.49
October 19.48 26.35
November 19.48 23.59
December 19.47 20.30
     
Annual Sum or Average 19.51 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.58 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OFFICE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.52 19.42
February 21.61 20.87
March 21.75 21.57
April 21.73 24.11
May 21.76 26.41
June 22.06 27.68
July 22.08 28.13
August 22.13 27.97
September 22.05 27.49
October 21.78 26.35
November 21.68 23.59
December 21.60 20.30
     
Annual Sum or Average 21.81 24.51
Minimum of Months 21.52 19.42
Maximum of Months 22.13 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OPERATING ROOM 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.32 19.42
February 18.32 20.87
March 18.33 21.57
April 18.32 24.11
May 18.32 26.41
June 18.38 27.68
July 18.51 28.13
August 18.50 27.97
September 18.41 27.49
October 18.33 26.35
November 18.32 23.59
December 18.32 20.30
     
Annual Sum or Average 18.36 24.51
Minimum of Months 18.32 19.42
Maximum of Months 18.51 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OPERATING ROOM 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.32 19.42
February 18.32 20.87
March 18.32 21.57
April 18.32 24.11
May 18.32 26.41
June 18.36 27.68
July 18.48 28.13
August 18.46 27.97
September 18.37 27.49
October 18.32 26.35
November 18.32 23.59
December 18.32 20.30
     
Annual Sum or Average 18.35 24.51
Minimum of Months 18.32 19.42
Maximum of Months 18.48 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 OPERATING ROOM 3

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.32 19.42
February 18.32 20.87
March 18.32 21.57
April 18.32 24.11
May 18.32 26.41
June 18.35 27.68
July 18.44 28.13
August 18.43 27.97
September 18.36 27.49
October 18.32 26.35
November 18.32 23.59
December 18.32 20.30
     
Annual Sum or Average 18.35 24.51
Minimum of Months 18.32 19.42
Maximum of Months 18.44 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PACU

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.57 19.42
February 19.59 20.87
March 19.68 21.57
April 19.60 24.11
May 19.62 26.41
June 19.71 27.68
July 19.64 28.13
August 19.77 27.97
September 19.66 27.49
October 19.58 26.35
November 19.57 23.59
December 19.56 20.30
     
Annual Sum or Average 19.63 24.51
Minimum of Months 19.56 19.42
Maximum of Months 19.77 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.07 19.42
February 21.17 20.87
March 21.31 21.57
April 21.32 24.11
May 21.36 26.41
June 21.70 27.68
July 21.68 28.13
August 21.77 27.97
September 21.69 27.49
October 21.38 26.35
November 21.26 23.59
December 21.14 20.30
     
Annual Sum or Average 21.41 24.51
Minimum of Months 21.07 19.42
Maximum of Months 21.77 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP ROOM 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.52 19.42
February 19.54 20.87
March 19.63 21.57
April 19.57 24.11
May 19.59 26.41
June 19.66 27.68
July 19.57 28.13
August 19.69 27.97
September 19.61 27.49
October 19.55 26.35
November 19.53 23.59
December 19.51 20.30
     
Annual Sum or Average 19.58 24.51
Minimum of Months 19.51 19.42
Maximum of Months 19.69 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP ROOM 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.51 19.42
February 19.53 20.87
March 19.61 21.57
April 19.54 24.11
May 19.56 26.41
June 19.62 27.68
July 19.52 28.13
August 19.64 27.97
September 19.56 27.49
October 19.52 26.35
November 19.51 23.59
December 19.50 20.30
     
Annual Sum or Average 19.55 24.51
Minimum of Months 19.50 19.42
Maximum of Months 19.64 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PRE-OP TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.59 21.57
April 19.52 24.11
May 19.55 26.41
June 19.59 27.68
July 19.50 28.13
August 19.62 27.97
September 19.53 27.49
October 19.50 26.35
November 19.49 23.59
December 19.47 20.30
     
Annual Sum or Average 19.53 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.62 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 PROCEDURE ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.49 19.42
February 19.51 20.87
March 19.59 21.57
April 19.52 24.11
May 19.54 26.41
June 19.58 27.68
July 19.48 28.13
August 19.59 27.97
September 19.52 27.49
October 19.49 26.35
November 19.49 23.59
December 19.48 20.30
     
Annual Sum or Average 19.53 24.51
Minimum of Months 19.48 19.42
Maximum of Months 19.59 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 RECEPTION

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.45 19.42
February 21.56 20.87
March 21.72 21.57
April 21.71 24.11
May 21.76 26.41
June 22.07 27.68
July 22.12 28.13
August 22.20 27.97
September 22.13 27.49
October 21.84 26.35
November 21.68 23.59
December 21.55 20.30
     
Annual Sum or Average 21.82 24.51
Minimum of Months 21.45 19.42
Maximum of Months 22.20 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 RECEPTION HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 19.42
February 21.26 20.87
March 21.41 21.57
April 21.39 24.11
May 21.42 26.41
June 21.78 27.68
July 21.78 28.13
August 21.87 27.97
September 21.79 27.49
October 21.47 26.35
November 21.35 23.59
December 21.26 20.30
     
Annual Sum or Average 21.50 24.51
Minimum of Months 21.17 19.42
Maximum of Months 21.87 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 RECOVERY ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.70 19.42
February 19.71 20.87
March 19.76 21.57
April 19.63 24.11
May 19.64 26.41
June 19.78 27.68
July 19.79 28.13
August 19.95 27.97
September 19.88 27.49
October 19.78 26.35
November 19.74 23.59
December 19.69 20.30
     
Annual Sum or Average 19.76 24.51
Minimum of Months 19.63 19.42
Maximum of Months 19.95 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SCHEDULING

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.13 19.42
February 21.25 20.87
March 21.39 21.57
April 21.41 24.11
May 21.47 26.41
June 21.78 27.68
July 21.79 28.13
August 21.87 27.97
September 21.83 27.49
October 21.56 26.35
November 21.38 23.59
December 21.24 20.30
     
Annual Sum or Average 21.51 24.51
Minimum of Months 21.13 19.42
Maximum of Months 21.87 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SCRUB

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.04 19.42
February 21.16 20.87
March 21.33 21.57
April 21.40 24.11
May 21.46 26.41
June 21.79 27.68
July 21.82 28.13
August 21.83 27.97
September 21.78 27.49
October 21.47 26.35
November 21.27 23.59
December 21.07 20.30
     
Annual Sum or Average 21.45 24.51
Minimum of Months 21.04 19.42
Maximum of Months 21.83 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SOIL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.58 21.57
April 19.51 24.11
May 19.53 26.41
June 19.57 27.68
July 19.47 28.13
August 19.58 27.97
September 19.51 27.49
October 19.48 26.35
November 19.48 23.59
December 19.47 20.30
     
Annual Sum or Average 19.51 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.58 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SOIL HOLD

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.58 21.57
April 19.51 24.11
May 19.54 26.41
June 19.59 27.68
July 19.49 28.13
August 19.60 27.97
September 19.52 27.49
October 19.49 26.35
November 19.48 23.59
December 19.47 20.30
     
Annual Sum or Average 19.52 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.60 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SOIL WORK

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.58 21.57
April 19.51 24.11
May 19.53 26.41
June 19.57 27.68
July 19.47 28.13
August 19.58 27.97
September 19.51 27.49
October 19.48 26.35
November 19.48 23.59
December 19.47 20.30
     
Annual Sum or Average 19.51 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.58 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STEP DOWN

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.58 19.42
February 19.62 20.87
March 19.70 21.57
April 19.63 24.11
May 19.64 26.41
June 19.74 27.68
July 19.75 28.13
August 19.88 27.97
September 19.78 27.49
October 19.68 26.35
November 19.61 23.59
December 19.58 20.30
     
Annual Sum or Average 19.68 24.51
Minimum of Months 19.58 19.42
Maximum of Months 19.88 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STERILE HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.20 19.42
February 21.28 20.87
March 21.40 21.57
April 21.41 24.11
May 21.46 26.41
June 21.79 27.68
July 21.81 28.13
August 21.86 27.97
September 21.82 27.49
October 21.54 26.35
November 21.38 23.59
December 21.26 20.30
     
Annual Sum or Average 21.52 24.51
Minimum of Months 21.20 19.42
Maximum of Months 21.86 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STERILE STORAGE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.33 19.42
February 21.40 20.87
March 21.53 21.57
April 21.50 24.11
May 21.51 26.41
June 21.90 27.68
July 21.90 28.13
August 21.98 27.97
September 21.90 27.49
October 21.56 26.35
November 21.47 23.59
December 21.40 20.30
     
Annual Sum or Average 21.62 24.51
Minimum of Months 21.33 19.42
Maximum of Months 21.98 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 STORAGE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.05 19.42
February 20.32 20.87
March 20.76 21.57
April 21.21 24.11
May 21.55 26.41
June 21.97 27.68
July 22.13 28.13
August 21.89 27.97
September 21.78 27.49
October 21.18 26.35
November 20.67 23.59
December 20.21 20.30
     
Annual Sum or Average 21.15 24.51
Minimum of Months 20.05 19.42
Maximum of Months 22.13 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 SUB-STERILE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.42 19.42
February 20.63 20.87
March 20.90 21.57
April 21.14 24.11
May 21.26 26.41
June 21.58 27.68
July 21.65 28.13
August 21.54 27.97
September 21.53 27.49
October 21.18 26.35
November 20.80 23.59
December 20.42 20.30
     
Annual Sum or Average 21.09 24.51
Minimum of Months 20.42 19.42
Maximum of Months 21.65 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 UTILITY HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.09 19.42
February 20.30 20.87
March 20.69 21.57
April 21.16 24.11
May 21.40 26.41
June 21.79 27.68
July 21.89 28.13
August 21.71 27.97
September 21.65 27.49
October 21.10 26.35
November 20.61 23.59
December 20.22 20.30
     
Annual Sum or Average 21.05 24.51
Minimum of Months 20.09 19.42
Maximum of Months 21.89 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 UTILITY JANITOR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.97 19.42
February 21.09 20.87
March 21.28 21.57
April 21.37 24.11
May 21.45 26.41
June 21.80 27.68
July 21.83 28.13
August 21.83 27.97
September 21.77 27.49
October 21.43 26.35
November 21.22 23.59
December 21.01 20.30
     
Annual Sum or Average 21.42 24.51
Minimum of Months 20.97 19.42
Maximum of Months 21.83 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 UTILITY ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.39 19.42
February 20.62 20.87
March 20.93 21.57
April 21.23 24.11
May 21.41 26.41
June 21.79 27.68
July 21.88 28.13
August 21.74 27.97
September 21.72 27.49
October 21.30 26.35
November 20.86 23.59
December 20.45 20.30
     
Annual Sum or Average 21.20 24.51
Minimum of Months 20.39 19.42
Maximum of Months 21.88 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 1 VESTIBULE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.92 19.42
February 20.89 20.87
March 20.93 21.57
April 22.03 24.11
May 23.00 26.41
June 23.50 27.68
July 23.66 28.13
August 23.92 27.97
September 23.36 27.49
October 22.77 26.35
November 21.78 23.59
December 20.13 20.30
     
Annual Sum or Average 22.16 24.51
Minimum of Months 19.92 19.42
Maximum of Months 23.92 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 CONFERENCE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.00 19.42
February 21.11 20.87
March 21.25 21.57
April 21.30 24.11
May 21.43 26.41
June 21.85 27.68
July 21.99 28.13
August 22.05 27.97
September 22.02 27.49
October 21.69 26.35
November 21.30 23.59
December 21.06 20.30
     
Annual Sum or Average 21.51 24.51
Minimum of Months 21.00 19.42
Maximum of Months 22.05 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 CONFERENCE TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.46 19.42
February 17.41 20.87
March 17.46 21.57
April 17.35 24.11
May 17.42 26.41
June 17.94 27.68
July 18.10 28.13
August 18.14 27.97
September 17.96 27.49
October 17.57 26.35
November 17.41 23.59
December 17.43 20.30
     
Annual Sum or Average 17.64 24.51
Minimum of Months 17.35 19.42
Maximum of Months 18.14 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 DICTATION

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 19.42
February 21.24 20.87
March 21.38 21.57
April 21.28 24.11
May 21.29 26.41
June 21.56 27.68
July 21.53 28.13
August 21.65 27.97
September 21.52 27.49
October 21.33 26.35
November 21.26 23.59
December 21.22 20.30
     
Annual Sum or Average 21.37 24.51
Minimum of Months 21.18 19.42
Maximum of Months 21.65 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.51 19.42
February 19.55 20.87
March 19.66 21.57
April 19.65 24.11
May 19.68 26.41
June 19.83 27.68
July 19.88 28.13
August 20.00 27.97
September 19.82 27.49
October 19.65 26.35
November 19.54 23.59
December 19.51 20.30
     
Annual Sum or Average 19.69 24.51
Minimum of Months 19.51 19.42
Maximum of Months 20.00 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.66 19.42
February 19.67 20.87
March 19.77 21.57
April 19.68 24.11
May 19.72 26.41
June 19.96 27.68
July 19.98 28.13
August 20.14 27.97
September 19.99 27.49
October 19.77 26.35
November 19.67 23.59
December 19.67 20.30
     
Annual Sum or Average 19.81 24.51
Minimum of Months 19.66 19.42
Maximum of Months 20.14 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 3

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.62 19.42
February 19.63 20.87
March 19.72 21.57
April 19.64 24.11
May 19.67 26.41
June 19.89 27.68
July 19.90 28.13
August 20.05 27.97
September 19.92 27.49
October 19.73 26.35
November 19.64 23.59
December 19.63 20.30
     
Annual Sum or Average 19.75 24.51
Minimum of Months 19.62 19.42
Maximum of Months 20.05 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 4

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.88 19.42
February 19.87 20.87
March 19.89 21.57
April 19.79 24.11
May 19.85 26.41
June 20.19 27.68
July 20.26 28.13
August 20.45 27.97
September 20.39 27.49
October 20.15 26.35
November 19.96 23.59
December 19.88 20.30
     
Annual Sum or Average 20.05 24.51
Minimum of Months 19.79 19.42
Maximum of Months 20.45 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 5

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.51 19.42
February 19.54 20.87
March 19.63 21.57
April 19.61 24.11
May 19.68 26.41
June 19.98 27.68
July 20.07 28.13
August 20.10 27.97
September 19.88 27.49
October 19.62 26.35
November 19.53 23.59
December 19.50 20.30
     
Annual Sum or Average 19.72 24.51
Minimum of Months 19.50 19.42
Maximum of Months 20.10 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 6

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.61 19.42
February 19.65 20.87
March 19.77 21.57
April 19.78 24.11
May 19.96 26.41
June 20.41 27.68
July 20.47 28.13
August 20.50 27.97
September 20.23 27.49
October 19.84 26.35
November 19.69 23.59
December 19.61 20.30
     
Annual Sum or Average 19.96 24.51
Minimum of Months 19.61 19.42
Maximum of Months 20.50 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 7

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.58 19.42
February 19.60 20.87
March 19.69 21.57
April 19.63 24.11
May 19.69 26.41
June 19.93 27.68
July 19.94 28.13
August 20.03 27.97
September 19.83 27.49
October 19.64 26.35
November 19.58 23.59
December 19.58 20.30
     
Annual Sum or Average 19.73 24.51
Minimum of Months 19.58 19.42
Maximum of Months 20.03 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 8

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.63 19.42
February 19.67 20.87
March 19.79 21.57
April 19.78 24.11
May 19.97 26.41
June 20.43 27.68
July 20.48 28.13
August 20.51 27.97
September 20.25 27.49
October 19.86 26.35
November 19.71 23.59
December 19.64 20.30
     
Annual Sum or Average 19.98 24.51
Minimum of Months 19.63 19.42
Maximum of Months 20.51 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM 9

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.67 19.42
February 19.69 20.87
March 19.80 21.57
April 19.74 24.11
May 19.83 26.41
June 20.16 27.68
July 20.18 28.13
August 20.27 27.97
September 20.04 27.49
October 19.77 26.35
November 19.68 23.59
December 19.68 20.30
     
Annual Sum or Average 19.88 24.51
Minimum of Months 19.67 19.42
Maximum of Months 20.27 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.96 19.42
February 21.07 20.87
March 21.22 21.57
April 21.22 24.11
May 21.25 26.41
June 21.51 27.68
July 21.55 28.13
August 21.63 27.97
September 21.55 27.49
October 21.34 26.35
November 21.13 23.59
December 21.04 20.30
     
Annual Sum or Average 21.29 24.51
Minimum of Months 20.96 19.42
Maximum of Months 21.63 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.00 19.42
February 21.07 20.87
March 21.19 21.57
April 21.12 24.11
May 21.15 26.41
June 21.42 27.68
July 21.43 28.13
August 21.54 27.97
September 21.47 27.49
October 21.28 26.35
November 21.13 23.59
December 21.07 20.30
     
Annual Sum or Average 21.24 24.51
Minimum of Months 21.00 19.42
Maximum of Months 21.54 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 3

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.93 19.42
February 20.98 20.87
March 21.08 21.57
April 20.99 24.11
May 21.02 26.41
June 21.30 27.68
July 21.29 28.13
August 21.42 27.97
September 21.35 27.49
October 21.18 26.35
November 21.04 23.59
December 20.98 20.30
     
Annual Sum or Average 21.13 24.51
Minimum of Months 20.93 19.42
Maximum of Months 21.42 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 4

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.88 19.42
February 21.01 20.87
March 21.22 21.57
April 21.25 24.11
May 21.38 26.41
June 21.70 27.68
July 21.72 28.13
August 21.73 27.97
September 21.56 27.49
October 21.27 26.35
November 21.10 23.59
December 20.97 20.30
     
Annual Sum or Average 21.32 24.51
Minimum of Months 20.88 19.42
Maximum of Months 21.73 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 5

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.97 19.42
February 21.11 20.87
March 21.33 21.57
April 21.36 24.11
May 21.51 26.41
June 21.84 27.68
July 21.87 28.13
August 21.87 27.97
September 21.69 27.49
October 21.39 26.35
November 21.21 23.59
December 21.08 20.30
     
Annual Sum or Average 21.44 24.51
Minimum of Months 20.97 19.42
Maximum of Months 21.87 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 EXAM HALL 6

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 19.42
February 21.07 20.87
March 21.29 21.57
April 21.33 24.11
May 21.47 26.41
June 21.81 27.68
July 21.85 28.13
August 21.84 27.97
September 21.67 27.49
October 21.35 26.35
November 21.17 23.59
December 21.04 20.30
     
Annual Sum or Average 21.40 24.51
Minimum of Months 20.92 19.42
Maximum of Months 21.85 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 JANITOR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.76 19.42
February 20.99 20.87
March 21.33 21.57
April 21.53 24.11
May 21.78 26.41
June 22.09 27.68
July 22.16 28.13
August 22.08 27.97
September 21.93 27.49
October 21.57 26.35
November 21.21 23.59
December 20.91 20.30
     
Annual Sum or Average 21.53 24.51
Minimum of Months 20.76 19.42
Maximum of Months 22.16 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 LOUNGE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.37 19.42
February 21.43 20.87
March 21.56 21.57
April 21.49 24.11
May 21.51 26.41
June 21.80 27.68
July 21.83 28.13
August 21.91 27.97
September 21.75 27.49
October 21.52 26.35
November 21.44 23.59
December 21.39 20.30
     
Annual Sum or Average 21.58 24.51
Minimum of Months 21.37 19.42
Maximum of Months 21.91 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 NURSE STATION 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.55 19.42
February 21.64 20.87
March 21.81 21.57
April 21.79 24.11
May 21.84 26.41
June 22.19 27.68
July 22.26 28.13
August 22.29 27.97
September 22.10 27.49
October 21.81 26.35
November 21.69 23.59
December 21.61 20.30
     
Annual Sum or Average 21.88 24.51
Minimum of Months 21.55 19.42
Maximum of Months 22.29 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 NURSE STATION 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.59 19.42
February 21.70 20.87
March 21.87 21.57
April 21.86 24.11
May 21.93 26.41
June 22.29 27.68
July 22.38 28.13
August 22.40 27.97
September 22.19 27.49
October 21.88 26.35
November 21.76 23.59
December 21.68 20.30
     
Annual Sum or Average 21.96 24.51
Minimum of Months 21.59 19.42
Maximum of Months 22.40 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 OFFICE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.72 19.42
February 20.88 20.87
March 21.16 21.57
April 21.35 24.11
May 21.49 26.41
June 21.82 27.68
July 21.97 28.13
August 21.81 27.97
September 21.73 27.49
October 21.39 26.35
November 21.03 23.59
December 20.71 20.30
     
Annual Sum or Average 21.34 24.51
Minimum of Months 20.71 19.42
Maximum of Months 21.97 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 OFFICE HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.01 19.42
February 21.14 20.87
March 21.36 21.57
April 21.43 24.11
May 21.52 26.41
June 21.84 27.68
July 21.90 28.13
August 21.87 27.97
September 21.75 27.49
October 21.46 26.35
November 21.23 23.59
December 21.05 20.30
     
Annual Sum or Average 21.46 24.51
Minimum of Months 21.01 19.42
Maximum of Months 21.90 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 RECEPTION

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.28 19.42
February 21.44 20.87
March 21.64 21.57
April 21.72 24.11
May 21.80 26.41
June 22.14 27.68
July 22.32 28.13
August 22.36 27.97
September 22.26 27.49
October 21.94 26.35
November 21.58 23.59
December 21.41 20.30
     
Annual Sum or Average 21.82 24.51
Minimum of Months 21.28 19.42
Maximum of Months 22.36 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 RECEPTION HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.32 19.42
February 21.40 20.87
March 21.55 21.57
April 21.50 24.11
May 21.52 26.41
June 21.80 27.68
July 21.83 28.13
August 21.91 27.97
September 21.79 27.49
October 21.56 26.35
November 21.44 23.59
December 21.39 20.30
     
Annual Sum or Average 21.59 24.51
Minimum of Months 21.32 19.42
Maximum of Months 21.91 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 RECEPTION TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.42 19.42
February 17.39 20.87
March 17.46 21.57
April 17.36 24.11
May 17.43 26.41
June 17.96 27.68
July 18.14 28.13
August 18.17 27.97
September 17.96 27.49
October 17.56 26.35
November 17.39 23.59
December 17.44 20.30
     
Annual Sum or Average 17.64 24.51
Minimum of Months 17.36 19.42
Maximum of Months 18.17 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 SCHEDULING 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.64 19.42
February 21.74 20.87
March 21.88 21.57
April 21.84 24.11
May 21.85 26.41
June 22.14 27.68
July 22.20 28.13
August 22.25 27.97
September 22.09 27.49
October 21.85 26.35
November 21.76 23.59
December 21.71 20.30
     
Annual Sum or Average 21.91 24.51
Minimum of Months 21.64 19.42
Maximum of Months 22.25 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 SCHEDULING 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.60 19.42
February 21.70 20.87
March 21.83 21.57
April 21.80 24.11
May 21.81 26.41
June 22.10 27.68
July 22.17 28.13
August 22.23 27.97
September 22.08 27.49
October 21.84 26.35
November 21.73 23.59
December 21.67 20.30
     
Annual Sum or Average 21.88 24.51
Minimum of Months 21.60 19.42
Maximum of Months 22.23 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 STORAGE 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.59 19.42
February 20.64 20.87
March 20.74 21.57
April 20.66 24.11
May 20.69 26.41
June 21.02 27.68
July 21.03 28.13
August 21.15 27.97
September 21.06 27.49
October 20.85 26.35
November 20.71 23.59
December 20.63 20.30
     
Annual Sum or Average 20.82 24.51
Minimum of Months 20.59 19.42
Maximum of Months 21.15 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 STORAGE 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.95 19.42
February 21.08 20.87
March 21.28 21.57
April 21.33 24.11
May 21.44 26.41
June 21.79 27.68
July 21.82 28.13
August 21.82 27.97
September 21.66 27.49
October 21.35 26.35
November 21.18 23.59
December 21.04 20.30
     
Annual Sum or Average 21.40 24.51
Minimum of Months 20.95 19.42
Maximum of Months 21.82 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 STORAGE 3

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.04 19.42
February 21.19 20.87
March 21.41 21.57
April 21.46 24.11
May 21.59 26.41
June 21.94 27.68
July 21.98 28.13
August 21.97 27.97
September 21.80 27.49
October 21.48 26.35
November 21.30 23.59
December 21.16 20.30
     
Annual Sum or Average 21.53 24.51
Minimum of Months 21.04 19.42
Maximum of Months 21.98 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 UTILITY

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.36 19.42
February 20.57 20.87
March 20.88 21.57
April 21.15 24.11
May 21.28 26.41
June 21.58 27.68
July 21.70 28.13
August 21.53 27.97
September 21.47 27.49
October 21.15 26.35
November 20.74 23.59
December 20.36 20.30
     
Annual Sum or Average 21.07 24.51
Minimum of Months 20.36 19.42
Maximum of Months 21.70 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 WORK

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.55 19.42
February 21.70 20.87
March 21.94 21.57
April 22.02 24.11
May 22.13 26.41
June 22.50 27.68
July 22.64 28.13
August 22.59 27.97
September 22.40 27.49
October 22.06 26.35
November 21.83 23.59
December 21.69 20.30
     
Annual Sum or Average 22.09 24.51
Minimum of Months 21.55 19.42
Maximum of Months 22.64 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 WORK HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.48 19.42
February 21.60 20.87
March 21.79 21.57
April 21.80 24.11
May 21.84 26.41
June 22.14 27.68
July 22.21 28.13
August 22.23 27.97
September 22.09 27.49
October 21.83 26.35
November 21.67 23.59
December 21.59 20.30
     
Annual Sum or Average 21.86 24.51
Minimum of Months 21.48 19.42
Maximum of Months 22.23 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 WORK TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.52 19.42
February 19.55 20.87
March 19.67 21.57
April 19.62 24.11
May 19.66 26.41
June 19.74 27.68
July 19.69 28.13
August 19.77 27.97
September 19.66 27.49
October 19.57 26.35
November 19.53 23.59
December 19.51 20.30
     
Annual Sum or Average 19.63 24.51
Minimum of Months 19.51 19.42
Maximum of Months 19.77 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 2 X-RAY

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 19.42
February 22.34 20.87
March 22.40 21.57
April 22.35 24.11
May 22.38 26.41
June 22.85 27.68
July 23.01 28.13
August 23.05 27.97
September 22.82 27.49
October 22.46 26.35
November 22.34 23.59
December 22.34 20.30
     
Annual Sum or Average 22.56 24.51
Minimum of Months 22.31 19.42
Maximum of Months 23.05 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 DRESSING ROOM

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 19.42
February 20.91 20.87
March 21.09 21.57
April 21.10 24.11
May 21.19 26.41
June 21.46 27.68
July 21.50 28.13
August 21.54 27.97
September 21.35 27.49
October 21.09 26.35
November 20.95 23.59
December 20.86 20.30
     
Annual Sum or Average 21.16 24.51
Minimum of Months 20.81 19.42
Maximum of Months 21.54 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 ELEVATOR HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.95 19.42
February 21.18 20.87
March 21.50 21.57
April 21.71 24.11
May 21.91 26.41
June 22.31 27.68
July 22.54 28.13
August 22.35 27.97
September 22.17 27.49
October 21.74 26.35
November 21.36 23.59
December 21.13 20.30
     
Annual Sum or Average 21.74 24.51
Minimum of Months 20.95 19.42
Maximum of Months 22.54 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 HUMID

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.91 19.42
February 21.01 20.87
March 21.20 21.57
April 21.22 24.11
May 21.31 26.41
June 21.60 27.68
July 21.66 28.13
August 21.70 27.97
September 21.50 27.49
October 21.22 26.35
November 21.06 23.59
December 20.97 20.30
     
Annual Sum or Average 21.28 24.51
Minimum of Months 20.91 19.42
Maximum of Months 21.70 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 JANITOR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.28 19.42
February 20.57 20.87
March 20.95 21.57
April 21.29 24.11
May 21.59 26.41
June 21.93 27.68
July 22.15 28.13
August 21.90 27.97
September 21.77 27.49
October 21.33 26.35
November 20.84 23.59
December 20.44 20.30
     
Annual Sum or Average 21.26 24.51
Minimum of Months 20.28 19.42
Maximum of Months 22.15 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 LOCKER

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.07 19.42
February 21.19 20.87
March 21.42 21.57
April 21.49 24.11
May 21.64 26.41
June 22.01 27.68
July 22.15 28.13
August 22.10 27.97
September 21.86 27.49
October 21.51 26.35
November 21.28 23.59
December 21.15 20.30
     
Annual Sum or Average 21.58 24.51
Minimum of Months 21.07 19.42
Maximum of Months 22.15 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 LOUNGE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.16 19.42
February 21.30 20.87
March 21.55 21.57
April 21.67 24.11
May 21.89 26.41
June 22.38 27.68
July 22.59 28.13
August 22.46 27.97
September 22.21 27.49
October 21.76 26.35
November 21.44 23.59
December 21.26 20.30
     
Annual Sum or Average 21.81 24.51
Minimum of Months 21.16 19.42
Maximum of Months 22.59 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 LOUNGE TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.48 19.42
February 19.50 20.87
March 19.58 21.57
April 19.52 24.11
May 19.56 26.41
June 19.66 27.68
July 19.66 28.13
August 19.70 27.97
September 19.57 27.49
October 19.49 26.35
November 19.48 23.59
December 19.47 20.30
     
Annual Sum or Average 19.56 24.51
Minimum of Months 19.47 19.42
Maximum of Months 19.70 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 MECHANICAL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 19.42
February 21.84 20.87
March 21.93 21.57
April 22.17 24.11
May 22.45 26.41
June 22.84 27.68
July 23.18 28.13
August 22.92 27.97
September 22.82 27.49
October 22.35 26.35
November 21.98 23.59
December 21.76 20.30
     
Annual Sum or Average 22.33 24.51
Minimum of Months 21.75 19.42
Maximum of Months 23.18 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 MECHANICAL HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.90 19.42
February 21.07 20.87
March 21.34 21.57
April 21.52 24.11
May 21.71 26.41
June 22.09 27.68
July 22.28 28.13
August 22.12 27.97
September 21.96 27.49
October 21.56 26.35
November 21.22 23.59
December 20.98 20.30
     
Annual Sum or Average 21.57 24.51
Minimum of Months 20.90 19.42
Maximum of Months 22.28 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 OFFICE

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.98 19.42
February 21.18 20.87
March 21.48 21.57
April 21.66 24.11
May 21.90 26.41
June 22.37 27.68
July 22.60 28.13
August 22.42 27.97
September 22.19 27.49
October 21.73 26.35
November 21.37 23.59
December 21.14 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 20.98 19.42
Maximum of Months 22.60 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 OFFICE HALL

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.08 19.42
February 21.28 20.87
March 21.54 21.57
April 21.70 24.11
May 21.84 26.41
June 22.23 27.68
July 22.45 28.13
August 22.32 27.97
September 22.15 27.49
October 21.76 26.35
November 21.42 23.59
December 21.23 20.30
     
Annual Sum or Average 21.75 24.51
Minimum of Months 21.08 19.42
Maximum of Months 22.45 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 OFFICE TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.50 19.42
February 19.53 20.87
March 19.64 21.57
April 19.61 24.11
May 19.64 26.41
June 19.73 27.68
July 19.73 28.13
August 19.77 27.97
September 19.65 27.49
October 19.55 26.35
November 19.51 23.59
December 19.49 20.30
     
Annual Sum or Average 19.61 24.51
Minimum of Months 19.49 19.42
Maximum of Months 19.77 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 PHYSICAL THERAPY 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.66 19.42
February 19.66 20.87
March 19.71 21.57
April 19.68 24.11
May 19.75 26.41
June 20.13 27.68
July 20.26 28.13
August 20.36 27.97
September 20.23 27.49
October 19.93 26.35
November 19.73 23.59
December 19.64 20.30
     
Annual Sum or Average 19.90 24.51
Minimum of Months 19.64 19.42
Maximum of Months 20.36 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 PHYSICAL THERAPY 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.57 19.42
February 19.58 20.87
March 19.68 21.57
April 19.65 24.11
May 19.73 26.41
June 20.05 27.68
July 20.11 28.13
August 20.20 27.97
September 19.98 27.49
October 19.71 26.35
November 19.60 23.59
December 19.56 20.30
     
Annual Sum or Average 19.79 24.51
Minimum of Months 19.56 19.42
Maximum of Months 20.20 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 PHYSICAL THERAPY TOILET

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.49 19.42
February 19.51 20.87
March 19.59 21.57
April 19.53 24.11
May 19.56 26.41
June 19.62 27.68
July 19.56 28.13
August 19.65 27.97
September 19.55 27.49
October 19.50 26.35
November 19.49 23.59
December 19.48 20.30
     
Annual Sum or Average 19.55 24.51
Minimum of Months 19.48 19.42
Maximum of Months 19.65 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 STORAGE 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.75 19.42
February 19.80 20.87
March 19.94 21.57
April 19.93 24.11
May 20.02 26.41
June 20.33 27.68
July 20.39 28.13
August 20.43 27.97
September 20.23 27.49
October 19.93 26.35
November 19.80 23.59
December 19.76 20.30
     
Annual Sum or Average 20.03 24.51
Minimum of Months 19.75 19.42
Maximum of Months 20.43 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 STORAGE 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.88 19.42
February 21.06 20.87
March 21.33 21.57
April 21.48 24.11
May 21.65 26.41
June 22.02 27.68
July 22.17 28.13
August 22.06 27.97
September 21.87 27.49
October 21.50 26.35
November 21.20 23.59
December 21.01 20.30
     
Annual Sum or Average 21.52 24.51
Minimum of Months 20.88 19.42
Maximum of Months 22.17 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 TREATMENT

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.61 19.42
February 19.62 20.87
March 19.73 21.57
April 19.70 24.11
May 19.79 26.41
June 20.13 27.68
July 20.19 28.13
August 20.29 27.97
September 20.06 27.49
October 19.76 26.35
November 19.64 23.59
December 19.60 20.30
     
Annual Sum or Average 19.84 24.51
Minimum of Months 19.60 19.42
Maximum of Months 20.29 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 UNDEVELOPED 1

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.02 19.42
February 21.22 20.87
March 21.42 21.57
April 21.61 24.11
May 21.73 26.41
June 22.09 27.68
July 22.34 28.13
August 22.26 27.97
September 22.16 27.49
October 21.79 26.35
November 21.37 23.59
December 21.17 20.30
     
Annual Sum or Average 21.68 24.51
Minimum of Months 21.02 19.42
Maximum of Months 22.34 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 UNDEVELOPED 2

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.10 19.42
February 21.33 20.87
March 21.55 21.57
April 21.78 24.11
May 21.93 26.41
June 22.32 27.68
July 22.63 28.13
August 22.52 27.97
September 22.47 27.49
October 22.06 26.35
November 21.54 23.59
December 21.29 20.30
     
Annual Sum or Average 21.88 24.51
Minimum of Months 21.10 19.42
Maximum of Months 22.63 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 UTILITY

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.68 19.42
February 20.85 20.87
March 21.10 21.57
April 21.23 24.11
May 21.36 26.41
June 21.65 27.68
July 21.73 28.13
August 21.66 27.97
September 21.53 27.49
October 21.23 26.35
November 20.96 23.59
December 20.77 20.30
     
Annual Sum or Average 21.23 24.51
Minimum of Months 20.68 19.42
Maximum of Months 21.73 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FLOOR 3 WORK

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.53 19.42
February 20.70 20.87
March 20.99 21.57
April 21.23 24.11
May 21.43 26.41
June 21.84 27.68
July 22.11 28.13
August 21.84 27.97
September 21.72 27.49
October 21.28 26.35
November 20.87 23.59
December 20.54 20.30
     
Annual Sum or Average 21.26 24.51
Minimum of Months 20.53 19.42
Maximum of Months 22.11 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: NE STAIR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.19 19.42
February 20.46 20.87
March 20.78 21.57
April 21.19 24.11
May 21.72 26.41
June 22.30 27.68
July 22.59 28.13
August 22.22 27.97
September 22.09 27.49
October 21.43 26.35
November 20.82 23.59
December 20.30 20.30
     
Annual Sum or Average 21.35 24.51
Minimum of Months 20.19 19.42
Maximum of Months 22.59 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: NW ELEVATOR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 19.42
February 20.74 20.87
March 21.10 21.57
April 21.38 24.11
May 21.59 26.41
June 21.89 27.68
July 22.11 28.13
August 21.94 27.97
September 21.86 27.49
October 21.44 26.35
November 20.94 23.59
December 20.65 20.30
     
Annual Sum or Average 21.35 24.51
Minimum of Months 20.48 19.42
Maximum of Months 22.11 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: NW STAIR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.13 19.42
February 20.44 20.87
March 20.84 21.57
April 21.32 24.11
May 21.82 26.41
June 22.33 27.68
July 22.61 28.13
August 22.25 27.97
September 22.06 27.49
October 21.42 26.35
November 20.83 23.59
December 20.30 20.30
     
Annual Sum or Average 21.37 24.51
Minimum of Months 20.13 19.42
Maximum of Months 22.61 28.13



Table of Contents

Report: MONTHLY INDOOR TEMP

For: SW STAIR

Timestamp: 2015-09-13 14:22:46

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 19.42
February 21.15 20.87
March 21.40 21.57
April 21.64 24.11
May 21.81 26.41
June 22.20 27.68
July 22.48 28.13
August 22.37 27.97
September 22.40 27.49
October 21.97 26.35
November 21.41 23.59
December 21.11 20.30
     
Annual Sum or Average 21.74 24.51
Minimum of Months 20.92 19.42
Maximum of Months 22.48 28.13



Table of Contents

Report: OVERALL HVAC AIR SYSTEM LOADS

For: AHU-1

Timestamp: 2015-09-13 14:22:46

AIR SYSTEM TOTAL HEATING ENERGY [J] AIR SYSTEM TOTAL COOLING ENERGY [J]
January 0.770401E+11 0.240936E+12
February 0.679019E+11 0.231439E+12
March 0.735852E+11 0.277277E+12
April 0.692351E+11 0.301550E+12
May 0.701651E+11 0.375576E+12
June 0.640938E+11 0.407383E+12
July 0.655461E+11 0.421918E+12
August 0.649550E+11 0.428584E+12
September 0.640297E+11 0.402162E+12
October 0.694415E+11 0.382328E+12
November 0.697178E+11 0.317936E+12
December 0.759048E+11 0.268897E+12
     
Annual Sum or Average 0.831616E+12 0.405598E+13
Minimum of Months 0.640297E+11 0.231439E+12
Maximum of Months 0.770401E+11 0.428584E+12



Table of Contents

Report: OVERALL HVAC AIR SYSTEM LOADS

For: AHU-2

Timestamp: 2015-09-13 14:22:46

AIR SYSTEM TOTAL HEATING ENERGY [J] AIR SYSTEM TOTAL COOLING ENERGY [J]
January 0.527327E+11 0.224807E+12
February 0.476024E+11 0.234327E+12
March 0.519638E+11 0.276825E+12
April 0.494821E+11 0.314174E+12
May 0.496497E+11 0.391936E+12
June 0.461925E+11 0.421441E+12
July 0.462619E+11 0.424882E+12
August 0.478432E+11 0.441260E+12
September 0.458901E+11 0.409952E+12
October 0.488504E+11 0.385269E+12
November 0.493880E+11 0.324051E+12
December 0.527795E+11 0.242466E+12
     
Annual Sum or Average 0.588636E+12 0.409139E+13
Minimum of Months 0.458901E+11 0.224807E+12
Maximum of Months 0.527795E+11 0.441260E+12



Table of Contents

Report: OVERALL HVAC SYSTEM ENERGY

For: Meter

Timestamp: 2015-09-13 14:22:46

ELECTRICITY:HVAC [J] HEATING:GAS [J]
January 0.201887E+12 0.708721E+11
February 0.194417E+12 0.624168E+11
March 0.225024E+12 0.666248E+11
April 0.239144E+12 0.631082E+11
May 0.283840E+12 0.632636E+11
June 0.297925E+12 0.551308E+11
July 0.306432E+12 0.557942E+11
August 0.313326E+12 0.545258E+11
September 0.292957E+12 0.554167E+11
October 0.281922E+12 0.626668E+11
November 0.244984E+12 0.637367E+11
December 0.212197E+12 0.714430E+11
     
Annual Sum or Average 0.309406E+13 0.744999E+12
Minimum of Months 0.194417E+12 0.545258E+11
Maximum of Months 0.313326E+12 0.714430E+11



Table of Contents

Report: COMPONENTS OF PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-13 14:22:46

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.417776E+12 311484.025 02-JAN-13:00 36851.394 111837.204 28896.008 3882.575 129669.822 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.389680E+12 300304.667 02-FEB-13:00 36851.394 111837.204 25701.298 8708.518 116859.231 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.449403E+12 309393.400 13-MAR-14:00 36851.394 111837.204 26175.182 7851.277 126331.322 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.446420E+12 324194.868 14-APR-14:00 36851.394 111837.204 40510.878 130.140 134518.230 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.502054E+12 326854.288 22-MAY-13:20 36851.394 111837.204 38544.637 685.926 138588.104 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.512485E+12 328179.490 08-JUN-13:00 36851.394 111837.204 43115.658 0.000 136028.212 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.516306E+12 337231.796 27-JUL-15:00 36851.394 111837.204 44077.649 0.000 144118.527 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.536745E+12 334015.197 23-AUG-12:00 36851.394 111837.204 43396.152 0.000 141583.425 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.500620E+12 330773.503 20-SEP-13:00 36851.394 111837.204 43541.978 0.000 138195.905 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.496966E+12 327522.872 03-OCT-14:00 36851.394 111837.204 41471.413 0.000 137015.839 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.455623E+12 324545.494 30-NOV-17:30 36851.394 111837.204 37728.775 779.945 128626.153 8375.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.424940E+12 310724.479 08-DEC-15:00 36851.394 111837.204 33638.771 3053.275 124996.812 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.564902E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.389680E+12 300304.667   36851.394 111837.204 25701.298 0.000 116859.231 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.536745E+12 337231.796   36851.394 111837.204 44077.649 8708.518 144118.527 8375.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS

For: Meter

Timestamp: 2015-09-13 14:22:46

ELECTRICITY:BUILDING [J] ELECTRICITY:BUILDING {Maximum}[W] ELECTRICITY:BUILDING {TIMESTAMP} GAS:BUILDING [J] GAS:BUILDING {Maximum}[W] GAS:BUILDING {TIMESTAMP}
January 0.202389E+12 148688.60 02-JAN-09:09 0.158619E+11 9905.77 02-JAN-06:10
February 0.183577E+12 148688.60 01-FEB-09:09 0.143713E+11 9905.77 01-FEB-06:10
March 0.212124E+12 148688.60 01-MAR-09:09 0.163897E+11 9905.77 01-MAR-06:10
April 0.196088E+12 148688.60 03-APR-08:09 0.153698E+11 9905.77 03-APR-05:10
May 0.207257E+12 148688.60 01-MAY-08:09 0.161258E+11 9905.77 01-MAY-05:10
June 0.204231E+12 148688.60 01-JUN-08:09 0.158049E+11 9905.77 01-JUN-05:10
July 0.199114E+12 148688.60 03-JUL-08:09 0.156907E+11 9905.77 03-JUL-05:10
August 0.212124E+12 148688.60 01-AUG-08:09 0.163897E+11 9905.77 01-AUG-05:10
September 0.196088E+12 148688.60 01-SEP-08:09 0.153698E+11 9905.77 01-SEP-05:10
October 0.202389E+12 148688.60 02-OCT-08:09 0.158619E+11 9905.77 02-OCT-05:10
November 0.197772E+12 148688.60 01-NOV-08:09 0.154482E+11 9905.77 01-NOV-05:10
December 0.199114E+12 148688.60 01-DEC-09:09 0.156907E+11 9905.77 01-DEC-06:10
             
Annual Sum or Average 0.241227E+13     0.188374E+12    
Minimum of Months 0.183577E+12 148688.60   0.143713E+11 9905.77  
Maximum of Months 0.212124E+12 148688.60   0.163897E+11 9905.77  



Table of Contents

Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY

For: Meter

Timestamp: 2015-09-13 14:22:46

INTERIORLIGHTS:ELECTRICITY [J] TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] EXTERIORLIGHTS:ELECTRICITY [J] GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [Invalid/Undefined] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] COGENERATION:ELECTRICITY [Invalid/Undefined]
January 0.465507E+11 0.00 0.125726E+11 0.155839E+12 0.00 0.437613E+11 0.926850E+09 0.329377E+11 0.124554E+12 0.00 0.634296E+09 0.00 0.00 0.00
February 0.423275E+11 0.00 0.108490E+11 0.141249E+12 0.00 0.400561E+11 0.837338E+09 0.287533E+11 0.124946E+12 0.00 0.661941E+09 0.00 0.00 0.00
March 0.500442E+11 0.00 0.113264E+11 0.162080E+12 0.00 0.458091E+11 0.927722E+09 0.303962E+11 0.148310E+12 0.00 0.508677E+09 0.00 0.00 0.00
April 0.451430E+11 0.00 0.102912E+11 0.150945E+12 0.00 0.450952E+11 0.897303E+09 0.274559E+11 0.166593E+12 0.00 0.00 0.00 0.00 0.00
May 0.482974E+11 0.00 0.100299E+11 0.158960E+12 0.00 0.492605E+11 0.927286E+09 0.246921E+11 0.209888E+12 0.00 0.00 0.00 0.00 0.00
June 0.480542E+11 0.00 0.943192E+10 0.156177E+12 0.00 0.537054E+11 0.897739E+09 0.173584E+11 0.226861E+12 0.00 0.00 0.00 0.00 0.00
July 0.453862E+11 0.00 0.983392E+10 0.153727E+12 0.00 0.560244E+11 0.926850E+09 0.161368E+11 0.234270E+12 0.00 0.00 0.00 0.00 0.00
August 0.500442E+11 0.00 0.103666E+11 0.162080E+12 0.00 0.571329E+11 0.927722E+09 0.171809E+11 0.239013E+12 0.00 0.00 0.00 0.00 0.00
September 0.451430E+11 0.00 0.106781E+11 0.150945E+12 0.00 0.523450E+11 0.897303E+09 0.180777E+11 0.222535E+12 0.00 0.00 0.00 0.00 0.00
October 0.465507E+11 0.00 0.117284E+11 0.155839E+12 0.00 0.489474E+11 0.926850E+09 0.239645E+11 0.209010E+12 0.00 0.00 0.00 0.00 0.00
November 0.457252E+11 0.00 0.119696E+11 0.152047E+12 0.00 0.447574E+11 0.896868E+09 0.276000E+11 0.172472E+12 0.00 0.154802E+09 0.00 0.00 0.00
December 0.453862E+11 0.00 0.127032E+11 0.153727E+12 0.00 0.436948E+11 0.926850E+09 0.319418E+11 0.136363E+12 0.00 0.197184E+09 0.00 0.00 0.00
                             
Annual Sum or Average 0.558652E+12 0.00 0.131781E+12 0.185361E+13 0.00 0.580590E+12 0.109167E+11 0.296495E+12 0.221481E+13 0.00 0.215690E+10 0.00 0.00 0.00
Minimum of Months 0.423275E+11 0.00 0.943192E+10 0.141249E+12 0.00 0.400561E+11 0.837338E+09 0.161368E+11 0.124554E+12 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.500442E+11 0.00 0.127032E+11 0.162080E+12 0.00 0.571329E+11 0.927722E+09 0.329377E+11 0.239013E+12 0.00 0.661941E+09 0.00 0.00 0.00



Table of Contents

Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS

For: Meter

Timestamp: 2015-09-13 14:22:46

INTERIOREQUIPMENT:GAS [J] EXTERIOREQUIPMENT:GAS [Invalid/Undefined] HEATING:GAS [J] COOLING:GAS [Invalid/Undefined] WATERSYSTEMS:GAS [J] COGENERATION:GAS [Invalid/Undefined]
January 0.158619E+11 0.00 0.708721E+11 0.00 0.872081E+10 0.00
February 0.143713E+11 0.00 0.624168E+11 0.00 0.786266E+10 0.00
March 0.163897E+11 0.00 0.666248E+11 0.00 0.896697E+10 0.00
April 0.153698E+11 0.00 0.631082E+11 0.00 0.790527E+10 0.00
May 0.161258E+11 0.00 0.632636E+11 0.00 0.806870E+10 0.00
June 0.158049E+11 0.00 0.551308E+11 0.00 0.775164E+10 0.00
July 0.156907E+11 0.00 0.557942E+11 0.00 0.729191E+10 0.00
August 0.163897E+11 0.00 0.545258E+11 0.00 0.801791E+10 0.00
September 0.153698E+11 0.00 0.554167E+11 0.00 0.756316E+10 0.00
October 0.158619E+11 0.00 0.626668E+11 0.00 0.808272E+10 0.00
November 0.154482E+11 0.00 0.637367E+11 0.00 0.825062E+10 0.00
December 0.156907E+11 0.00 0.714430E+11 0.00 0.847921E+10 0.00
             
Annual Sum or Average 0.188374E+12 0.00 0.744999E+12 0.00 0.969616E+11 0.00
Minimum of Months 0.143713E+11 0.00 0.545258E+11 0.00 0.729191E+10 0.00
Maximum of Months 0.163897E+11 0.00 0.714430E+11 0.00 0.896697E+10 0.00



Table of Contents

Report: PEAK ENERGY END-USE - ELECTRICITY

For: Meter

Timestamp: 2015-09-13 14:22:46

INTERIORLIGHTS:ELECTRICITY {Maximum}[W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] FANS:ELECTRICITY {Maximum}[W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum}[W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum}[W] HEATING:ELECTRICITY {TIMESTAMP}
January 36851.39 02-JAN-07:10 0.00 8375.00 01-JAN-00:10 111837.20 02-JAN-09:09 0.00 29172.53 02-JAN-14:09 347.02 01-JAN-08:09 97835.12 02-JAN-05:10
February 36851.39 01-FEB-07:10 0.00 8375.00 01-FEB-00:10 111837.20 01-FEB-09:09 0.00 31151.69 22-FEB-15:30 347.02 01-FEB-00:10 96143.29 06-FEB-05:10
March 36851.39 01-MAR-07:10 0.00 8375.00 01-MAR-00:10 111837.20 01-MAR-09:09 0.00 32144.49 30-MAR-15:30 347.02 01-MAR-00:10 88499.14 20-MAR-04:10
April 36851.39 03-APR-06:10 0.00 8375.00 01-APR-00:10 111837.20 03-APR-08:09 0.00 40528.13 14-APR-15:09 347.02 01-APR-00:10 83038.75 03-APR-04:10
May 36851.39 01-MAY-06:10 0.00 8375.00 01-MAY-00:10 111837.20 01-MAY-08:09 0.00 40800.35 31-MAY-13:20 347.02 01-MAY-00:10 93021.38 01-MAY-04:10
June 36851.39 01-JUN-06:10 0.00 8375.00 01-JUN-00:10 111837.20 01-JUN-08:09 0.00 43604.01 08-JUN-16:40 347.02 01-JUN-00:10 72061.69 19-JUN-04:10
July 36851.39 03-JUL-06:10 0.00 8375.00 01-JUL-00:10 111837.20 03-JUL-08:09 0.00 44086.79 28-JUL-15:30 347.02 01-JUL-00:10 64816.54 03-JUL-04:10
August 36851.39 01-AUG-06:10 0.00 8375.00 01-AUG-00:10 111837.20 01-AUG-08:09 0.00 43869.62 23-AUG-14:00 347.02 01-AUG-00:10 65485.07 28-AUG-04:10
September 36851.39 01-SEP-06:10 0.00 8375.00 01-SEP-00:10 111837.20 01-SEP-08:09 0.00 43756.41 22-SEP-14:20 347.02 01-SEP-00:10 78460.05 05-SEP-04:10
October 36851.39 02-OCT-06:10 0.00 8375.00 01-OCT-00:10 111837.20 02-OCT-08:09 0.00 41487.99 03-OCT-14:50 347.02 01-OCT-07:10 76434.35 16-OCT-04:10
November 36851.39 01-NOV-06:10 0.00 8375.00 01-NOV-00:10 111837.20 01-NOV-08:09 0.00 38817.05 03-NOV-16:00 347.02 01-NOV-00:10 96032.06 13-NOV-05:10
December 36851.39 01-DEC-07:10 0.00 8375.00 01-DEC-00:10 111837.20 01-DEC-09:09 0.00 33638.77 08-DEC-15:00 347.02 01-DEC-00:10 95755.91 18-DEC-05:10
                             
Annual Sum or Average     0.00         0.00            
Minimum of Months 36851.39   0.00 8375.00   111837.20   0.00 29172.53   347.02   64816.54  
Maximum of Months 36851.39   0.00 8375.00   111837.20   0.00 44086.79   347.02   97835.12  



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2015-09-13 14:22:46

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.417776E+12 311484.025 02-JAN-13:00 36851.394 111837.204 28896.008 3882.575 129669.822 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.389680E+12 300304.667 02-FEB-13:00 36851.394 111837.204 25701.298 8708.518 116859.231 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.449403E+12 309393.400 13-MAR-14:00 36851.394 111837.204 26175.182 7851.277 126331.322 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.446420E+12 324194.868 14-APR-14:00 36851.394 111837.204 40510.878 130.140 134518.230 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.502054E+12 326854.288 22-MAY-13:20 36851.394 111837.204 38544.637 685.926 138588.104 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.512485E+12 328179.490 08-JUN-13:00 36851.394 111837.204 43115.658 0.000 136028.212 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.516306E+12 337231.796 27-JUL-15:00 36851.394 111837.204 44077.649 0.000 144118.527 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.536745E+12 334015.197 23-AUG-12:00 36851.394 111837.204 43396.152 0.000 141583.425 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.500620E+12 330773.503 20-SEP-13:00 36851.394 111837.204 43541.978 0.000 138195.905 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.496966E+12 327522.872 03-OCT-14:00 36851.394 111837.204 41471.413 0.000 137015.839 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.455623E+12 324545.494 30-NOV-17:30 36851.394 111837.204 37728.775 779.945 128626.153 8375.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.424940E+12 310724.479 08-DEC-15:00 36851.394 111837.204 33638.771 3053.275 124996.812 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.564902E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.389680E+12 300304.667   36851.394 111837.204 25701.298 0.000 116859.231 0.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.536745E+12 337231.796   36851.394 111837.204 44077.649 8708.518 144118.527 8375.000 347.022 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2015-09-13 14:22:46

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC [Invalid/Undefined] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.954548E+11 71431.489 17-JAN-05:10 0.000 4952.884 0.000 66478.605 1488.000 1488.000 64990.605
February 0.846508E+11 99152.117 04-FEB-08:30 0.000 4952.884 0.000 94199.232 1488.000 1488.000 92711.232
March 0.919815E+11 96645.947 16-MAR-06:19 0.000 9905.768 0.000 86740.179 1488.000 1488.000 85252.179
April 0.863833E+11 61210.066 03-APR-04:10 0.000 4952.884 0.000 56257.182 1488.000 1488.000 54769.182
May 0.874581E+11 63195.633 01-MAY-04:10 0.000 4952.884 0.000 58242.749 1488.000 1488.000 56754.749
June 0.786873E+11 54795.071 19-JUN-04:30 0.000 4952.884 0.000 49842.187 1488.000 1488.000 48354.187
July 0.787769E+11 53607.912 24-JUL-04:30 0.000 4952.884 0.000 48655.028 1488.000 1488.000 47167.028
August 0.789334E+11 53973.829 07-AUG-04:30 0.000 4952.884 0.000 49020.945 1488.000 1488.000 47532.945
September 0.783496E+11 55938.245 05-SEP-04:30 0.000 4952.884 0.000 50985.361 1488.000 1488.000 49497.361
October 0.866115E+11 60153.363 16-OCT-04:30 0.000 4952.884 0.000 55200.479 1488.000 1488.000 53712.479
November 0.874355E+11 83751.115 27-NOV-06:30 0.000 9905.768 0.000 73845.347 1488.000 1488.000 72357.347
December 0.956129E+11 95658.469 15-DEC-06:30 0.000 9905.768 0.000 85752.700 1488.000 1488.000 84264.700
                     
Annual Sum or Average 0.103034E+13     0.000   0.000        
Minimum of Months 0.783496E+11 53607.912   0.000 4952.884 0.000 48655.028 1488.000 1488.000 47167.028
Maximum of Months 0.956129E+11 99152.117   0.000 9905.768 0.000 94199.232 1488.000 1488.000 92711.232