Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:22
Tabular Output Report in Format: HTML
Building: OutPatient HealthCare
Environment: RIYADH - SAU IWEC Data WMO#=404380
Simulation Timestamp: 2015-09-13 14:22:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 6730.51 | 1769.32 | 1769.32 |
Net Site Energy | 6730.51 | 1769.32 | 1769.32 |
Total Source Energy | 22071.31 | 5802.12 | 5802.12 |
Net Source Energy | 22071.31 | 5802.12 | 5802.12 |
Site=>Source Conversion Factor | |
Electricity | 3.546 |
Natural Gas | 1.092 |
District Cooling | 1.182 |
District Heating | 3.640 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.158 |
Fuel Oil #2 | 1.050 |
Propane | 1.151 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3804.01 |
Net Conditioned Building Area | 3804.01 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 703.73 | 450.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1794.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 558.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 131.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1853.61 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 634.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 10.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 312.29 | 0.00 | 0.00 | 0.00 | 0.00 | 116.17 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 92.42 | 0.00 | 0.00 | 0.00 | 478.84 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5999.02 | 731.49 | 0.00 | 0.00 | 0.00 | 595.01 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 450.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 703.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1794.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 558.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 131.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 1853.61 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 593.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Zone Exhaust Fans | 40.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 10.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 312.29 | 0.00 | 0.00 | 0.00 | 0.00 | 116.17 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 92.42 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.84 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 181.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 908.25 | 142.77 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 487.28 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1577.03 | 192.29 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 181.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 908.25 | 142.77 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 487.28 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1577.03 | 192.29 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 5999.02 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 5999.02 | 100.00 |
Total On-Site and Utility Electric Sources | 5999.02 | 100.00 |
Total Electricity End Uses | 5999.02 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 595.01 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 595.01 | 100.00 |
Total Water End Uses | 595.01 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 14.17 |
Time Setpoint Not Met During Occupied Cooling | 2203.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6816.33 |
Table of Contents
TopMONTHLY INDOOR TEMP
| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |OVERALL HVAC AIR SYSTEM LOADS
| AHU-1 | AHU-2 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2015.09.13 14:22 |
RunPeriod | RIYADH - SAU IWEC Data WMO#=404380 |
Weather File | RIYADH - SAU IWEC Data WMO#=404380 |
Latitude [deg] | 24.70 |
Longitude [deg] | 46.80 |
Elevation [m] | 612.00 |
Time Zone | 3.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | |
Gross Roof Area [m2] | 1373.29 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
FLOOR 1 ANESTHESIA | 10.03 | Yes | Yes | 30.58 | 1.00 | 8.36 | 2.23 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 BIO HAZ | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 CAFE | 39.02 | Yes | Yes | 118.93 | 1.00 | 18.58 | 8.92 | 8.8535 | 0.93 | 10.7600 |
FLOOR 1 CLEAN | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 CLEAN WORK | 15.33 | Yes | Yes | 46.72 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 DICTATION | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 DRESSING ROOM | 4.18 | Yes | Yes | 12.74 | 1.00 | 8.36 | 2.32 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 ELECTRICAL ROOM | 9.10 | Yes | Yes | 27.75 | 1.00 | 6.50 | 0.00 | 14.7559 | 53.8200 | |
FLOOR 1 ELEVATOR PUMP ROOM | 8.45 | Yes | Yes | 25.77 | 1.00 | 18.58 | 0.00 | 14.7559 | 5754.6154 | |
FLOOR 1 HUMID | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 IT HALL | 13.01 | Yes | Yes | 39.64 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 IT ROOM | 10.41 | Yes | Yes | 31.71 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 LOBBY | 57.79 | Yes | Yes | 176.13 | 1.00 | 20.44 | 8.92 | 12.7884 | 9.29 | 11.8400 |
FLOOR 1 LOBBY HALL | 22.30 | Yes | Yes | 67.96 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 LOBBY TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 LOCKER ROOM | 61.32 | Yes | Yes | 186.89 | 1.00 | 20.44 | 5.57 | 7.8698 | 6.19 | 32.2900 |
FLOOR 1 LOCKER ROOM HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 LOUNGE | 33.45 | Yes | Yes | 101.94 | 1.00 | 0.00 | 0.00 | 7.8698 | 6.19 | 32.2900 |
FLOOR 1 MED GAS | 5.20 | Yes | Yes | 15.86 | 1.00 | 13.94 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 MRI CONTROL ROOM | 15.61 | Yes | Yes | 47.57 | 1.00 | 4.65 | 0.00 | 3.9349 | 4.64 | 107.6400 |
FLOOR 1 MRI HALL | 13.66 | Yes | Yes | 41.63 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 MRI ROOM | 40.88 | Yes | Yes | 124.59 | 1.00 | 0.00 | 0.00 | 3.9349 | 4.64 | 107.6400 |
FLOOR 1 MRI TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 NOURISHMENT | 16.91 | Yes | Yes | 51.54 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 1 NURSE HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 NURSE JANITOR | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 NURSE STATION | 24.25 | Yes | Yes | 73.91 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 1 NURSE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 OFFICE | 44.87 | Yes | Yes | 136.77 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 OPERATING ROOM 1 | 42.74 | Yes | Yes | 130.26 | 1.00 | 39.95 | 8.92 | 21.6419 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 2 | 44.59 | Yes | Yes | 135.92 | 1.00 | 22.30 | 6.69 | 21.6419 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 3 | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 21.6419 | 4.64 | 118.3600 |
FLOOR 1 PACU | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 7.8698 | 4.64 | 32.2900 |
FLOOR 1 PRE-OP HALL | 49.05 | Yes | Yes | 149.51 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 PRE-OP ROOM 1 | 17.56 | Yes | Yes | 53.52 | 1.00 | 3.72 | 0.00 | 6.8861 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP ROOM 2 | 31.40 | Yes | Yes | 95.71 | 1.00 | 0.00 | 0.00 | 6.8861 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 1 PROCEDURE ROOM | 26.48 | Yes | Yes | 80.70 | 1.00 | 17.65 | 5.57 | 26.5606 | 4.64 | 32.2900 |
FLOOR 1 RECEPTION | 47.29 | Yes | Yes | 144.13 | 1.00 | 12.08 | 3.34 | 12.7884 | 3.10 | 11.8400 |
FLOOR 1 RECEPTION HALL | 11.89 | Yes | Yes | 36.25 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 RECOVERY ROOM | 50.17 | Yes | Yes | 152.91 | 1.00 | 41.81 | 8.92 | 7.8698 | 4.64 | 32.2900 |
FLOOR 1 SCHEDULING | 11.06 | Yes | Yes | 33.70 | 1.00 | 6.50 | 0.74 | 10.8210 | 18.58 | 11.8400 |
FLOOR 1 SCRUB | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 SOIL | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 SOIL HOLD | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 SOIL WORK | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 21.5300 |
FLOOR 1 STEP DOWN | 27.87 | Yes | Yes | 84.95 | 1.00 | 34.37 | 6.69 | 7.8698 | 4.64 | 32.2900 |
FLOOR 1 STERILE HALL | 57.23 | Yes | Yes | 174.43 | 1.00 | 7.43 | 2.23 | 9.8372 | 4.3100 | |
FLOOR 1 STERILE STORAGE | 36.79 | Yes | Yes | 112.13 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 STORAGE | 85.47 | Yes | Yes | 260.51 | 1.00 | 58.53 | 8.36 | 8.8535 | 1.0800 | |
FLOOR 1 SUB-STERILE | 18.21 | Yes | Yes | 55.50 | 1.00 | 13.01 | 2.97 | 9.8372 | 4.3100 | |
FLOOR 1 UTILITY HALL | 23.78 | Yes | Yes | 72.49 | 1.00 | 14.86 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 1 UTILITY JANITOR | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 1 UTILITY ROOM | 33.45 | Yes | Yes | 101.94 | 1.00 | 16.72 | 2.23 | 8.8535 | 1.0800 | |
FLOOR 1 VESTIBULE | 6.69 | Yes | Yes | 20.39 | 1.00 | 7.43 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 CONFERENCE | 31.22 | Yes | Yes | 95.14 | 1.00 | 37.16 | 8.92 | 12.7884 | 1.86 | 10.7600 |
FLOOR 2 CONFERENCE TOILET | 5.95 | Yes | Yes | 18.12 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 2 DICTATION | 6.50 | Yes | Yes | 19.82 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 EXAM 1 | 33.45 | Yes | Yes | 101.94 | 1.00 | 39.02 | 8.92 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 2 | 50.17 | Yes | Yes | 152.91 | 1.00 | 16.72 | 3.72 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 3 | 66.89 | Yes | Yes | 203.88 | 1.00 | 22.30 | 5.95 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 4 | 7.80 | Yes | Yes | 23.79 | 1.00 | 6.50 | 2.23 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 5 | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 6 | 20.90 | Yes | Yes | 63.71 | 1.00 | 13.94 | 4.18 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 7 | 73.58 | Yes | Yes | 224.27 | 1.00 | 22.30 | 5.57 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 8 | 25.08 | Yes | Yes | 76.46 | 1.00 | 16.72 | 5.57 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM 9 | 36.79 | Yes | Yes | 112.13 | 1.00 | 11.15 | 2.79 | 14.7559 | 4.64 | 11.8400 |
FLOOR 2 EXAM HALL 1 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 3 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 4 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 5 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 EXAM HALL 6 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 LOUNGE | 7.43 | Yes | Yes | 22.65 | 1.00 | 0.00 | 0.00 | 7.8698 | 6.19 | 32.2900 |
FLOOR 2 NURSE STATION 1 | 13.94 | Yes | Yes | 42.48 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 2 NURSE STATION 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.64 | 21.5300 |
FLOOR 2 OFFICE | 52.03 | Yes | Yes | 158.57 | 1.00 | 37.16 | 8.92 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 OFFICE HALL | 41.25 | Yes | Yes | 125.73 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 RECEPTION | 91.42 | Yes | Yes | 278.64 | 1.00 | 45.52 | 16.72 | 12.7884 | 3.10 | 11.8400 |
FLOOR 2 RECEPTION HALL | 52.40 | Yes | Yes | 159.71 | 1.00 | 6.50 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 RECEPTION TOILET | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 2 SCHEDULING 1 | 30.10 | Yes | Yes | 91.75 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 SCHEDULING 2 | 31.77 | Yes | Yes | 96.84 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 2 STORAGE 1 | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 STORAGE 2 | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 STORAGE 3 | 13.38 | Yes | Yes | 40.78 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 2 UTILITY | 11.71 | Yes | Yes | 35.68 | 1.00 | 8.36 | 2.23 | 8.8535 | 1.0800 | |
FLOOR 2 WORK | 157.01 | Yes | Yes | 478.55 | 1.00 | 24.15 | 5.57 | 10.8210 | 18.58 | 9.7803 |
FLOOR 2 WORK HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 2 WORK TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 2 X-RAY | 83.61 | Yes | Yes | 254.85 | 1.00 | 0.00 | 0.00 | 3.9349 | 4.64 | 107.6400 |
FLOOR 3 DRESSING ROOM | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 3 ELEVATOR HALL | 34.37 | Yes | Yes | 104.77 | 1.00 | 3.72 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 3 HUMID | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 10.8210 | 18.58 | 11.8400 |
FLOOR 3 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 LOCKER | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 7.8698 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE | 70.51 | Yes | Yes | 214.92 | 1.00 | 21.37 | 5.57 | 7.8698 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE TOILET | 17.84 | Yes | Yes | 54.37 | 1.00 | 11.15 | 4.18 | 8.8535 | 4.3100 | |
FLOOR 3 MECHANICAL | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 14.7559 | 53.8200 | |
FLOOR 3 MECHANICAL HALL | 27.87 | Yes | Yes | 84.95 | 1.00 | 0.00 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 3 OFFICE | 282.05 | Yes | Yes | 859.70 | 1.00 | 68.75 | 19.51 | 10.8210 | 18.58 | 11.8400 |
FLOOR 3 OFFICE HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 9.8372 | 4.3100 | |
FLOOR 3 OFFICE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 3 PHYSICAL THERAPY 1 | 120.77 | Yes | Yes | 368.12 | 1.00 | 78.97 | 28.99 | 8.8535 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY 2 | 55.00 | Yes | Yes | 167.64 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY TOILET | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.8535 | 4.3100 | |
FLOOR 3 STORAGE 1 | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 STORAGE 2 | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 TREATMENT | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 14.7559 | 4.64 | 11.8400 |
FLOOR 3 UNDEVELOPED 1 | 210.70 | Yes | Yes | 642.23 | 1.00 | 66.89 | 25.64 | 8.8535 | 11.8400 | |
FLOOR 3 UNDEVELOPED 2 | 107.02 | Yes | Yes | 326.21 | 1.00 | 52.03 | 13.38 | 8.8535 | 11.8400 | |
FLOOR 3 UTILITY | 20.07 | Yes | Yes | 61.16 | 1.00 | 0.00 | 0.00 | 8.8535 | 1.0800 | |
FLOOR 3 WORK | 53.33 | Yes | Yes | 162.54 | 1.00 | 38.09 | 8.92 | 10.8210 | 18.58 | 11.8400 |
NE STAIR | 15.61 | Yes | Yes | 142.72 | 1.00 | 97.55 | 12.02 | 9.8372 | 4.3100 | |
NW ELEVATOR | 13.01 | Yes | Yes | 118.93 | 1.00 | 75.25 | 0.00 | 9.8372 | 4.3100 | |
NW STAIR | 17.84 | Yes | Yes | 163.10 | 1.00 | 111.48 | 11.15 | 9.8372 | 4.3100 | |
SW STAIR | 8.92 | Yes | Yes | 81.55 | 1.00 | 55.74 | 1.11 | 9.8372 | 4.3100 | |
Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 10.7639 | 9.08 | 32.0039 | |||
Conditioned Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 10.7639 | 9.08 | 32.0039 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00 | 5.90 | Wetbulb [C] | 1.60 | 320.00 |
RIYADH ANN CLG .4% CONDNS DB=>MWB | 44.20 | 13.50 | 18.70 | Wetbulb [C] | 4.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
481E71 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
FLOOR 1 ANESTHESIA SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 0.00 | 180.00 | |
FLOOR 1 BIO HAZ SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
5F762C | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 18.58 | 180.00 | 90.00 | S |
FLOOR 1 CAFE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 39.02 | 90.00 | 180.00 | |
FLOOR 1 CLEAN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 CLEAN WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.33 | 180.00 | 180.00 | |
FLOOR 1 DICTATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 0.00 | 180.00 | |
84FB73 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 0.00 | 90.00 | N |
FLOOR 1 DRESSING ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 4.18 | 0.00 | 180.00 | |
7F5C82 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 ELECTRICAL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 9.10 | 0.00 | 180.00 | |
C732B0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 12.08 | 0.00 | 90.00 | N |
E02487 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 270.00 | 90.00 | W |
FLOOR 1 ELEVATOR PUMP ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.45 | 180.00 | 180.00 | |
FLOOR 1 HUMID SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
FLOOR 1 IT HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 180.00 | 180.00 | |
FLOOR 1 IT ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.41 | 90.00 | 180.00 | |
FE5A3C | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 20.44 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.79 | 90.00 | 180.00 | |
FLOOR 1 LOBBY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 22.30 | 0.00 | 180.00 | |
9D87EC | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
F629C1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 20.44 | 0.00 | 90.00 | N |
FLOOR 1 LOCKER ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 61.32 | 270.00 | 180.00 | |
FLOOR 1 LOCKER ROOM HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 180.00 | 180.00 | |
FLOOR 1 LOUNGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
E85BB5 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 7.43 | 0.00 | 90.00 | N |
577FC1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 MED GAS SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 180.00 | 180.00 | |
FLOOR 1 MED GAS ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 5.20 | 180.00 | 0.00 | |
C114C1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.65 | 0.00 | 90.00 | N |
FLOOR 1 MRI CONTROL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 180.00 | 180.00 | |
FLOOR 1 MRI HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.66 | 180.00 | 180.00 | |
FLOOR 1 MRI ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 40.88 | 90.00 | 180.00 | |
ADB8D0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 0.00 | 90.00 | N |
FLOOR 1 MRI TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 90.00 | 180.00 | |
FLOOR 1 NOURISHMENT SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.91 | 270.00 | 180.00 | |
FLOOR 1 NURSE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 270.00 | 180.00 | |
FLOOR 1 NURSE JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 NURSE STATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 24.25 | 180.00 | 180.00 | |
FLOOR 1 NURSE TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 OFFICE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.87 | 0.00 | 180.00 | |
879583 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 18.58 | 180.00 | 90.00 | S |
E326E4 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 21.37 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 42.74 | 0.00 | 180.00 | |
1D96D7 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.30 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.59 | 0.00 | 180.00 | |
FLOOR 1 OPERATING ROOM 3 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.22 | 0.00 | 180.00 | |
FLOOR 1 PACU SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 180.00 | 180.00 | |
FLOOR 1 PRE-OP HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 49.05 | 180.00 | 180.00 | |
84418A | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 3.72 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.56 | 90.00 | 180.00 | |
FLOOR 1 PRE-OP ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 31.40 | 0.00 | 180.00 | |
1535AC | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 270.00 | 180.00 | |
6D2616 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 17.65 | 0.00 | 90.00 | N |
FLOOR 1 PROCEDURE ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 26.48 | 270.00 | 180.00 | |
A5A6A3 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 12.08 | 180.00 | 90.00 | S |
FLOOR 1 RECEPTION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 47.29 | 270.00 | 180.00 | |
FLOOR 1 RECEPTION HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.89 | 0.00 | 180.00 | |
28B002 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 41.81 | 180.00 | 90.00 | S |
FLOOR 1 RECOVERY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 50.17 | 90.00 | 180.00 | |
EA6DC8 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 180.00 | 90.00 | S |
FLOOR 1 SCHEDULING SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.06 | 90.00 | 180.00 | |
FLOOR 1 SCRUB SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 7.80 | 90.00 | 180.00 | |
FLOOR 1 SOIL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 SOIL HOLD SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
FLOOR 1 SOIL WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.72 | 0.00 | 180.00 | |
B40F89 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 11.15 | 270.00 | 90.00 | W |
997723 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.23 | 180.00 | 90.00 | S |
FLOOR 1 STEP DOWN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 27.87 | 270.00 | 180.00 | |
CEC7BD | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 7.43 | 180.00 | 90.00 | S |
FLOOR 1 STERILE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.23 | 270.00 | 180.00 | |
FLOOR 1 NURSE STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 36.79 | 0.00 | 180.00 | |
8E5BB9 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 21.37 | 270.00 | 90.00 | W |
859BC1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 37.16 | 0.00 | 90.00 | N |
FLOOR 1 STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 85.47 | 270.00 | 180.00 | |
FLOOR 1 STORGE ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 85.47 | 270.00 | 0.00 | |
61E610 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.01 | 90.00 | 90.00 | E |
FLOOR 1 SUB-STERILE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 18.21 | 180.00 | 180.00 | |
529072 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 14.86 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 23.78 | 90.00 | 180.00 | |
FLOOR 1 UTILITY HALL ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 11.89 | 180.00 | 0.00 | |
FLOOR 1 UTILITY JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 3.90 | 90.00 | 180.00 | |
D95F04 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 16.72 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
3330D8 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 7.43 | 270.00 | 90.00 | W |
FLOOR 1 VESTIBULE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 6.69 | 90.00 | 180.00 | |
208CCF | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 11.15 | 90.00 | 90.00 | E |
AEF992 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 26.01 | 180.00 | 90.00 | S |
54D065 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 11.15 | 180.00 | 90.00 | S |
1775A6 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.87 | 270.00 | 90.00 | W |
97F00A | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 16.72 | 180.00 | 90.00 | S |
A497E9 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.30 | 180.00 | 90.00 | S |
88A75F | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 180.00 | 90.00 | S |
B4E619 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.23 | 90.00 | 90.00 | E |
9EC269 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.94 | 0.00 | 90.00 | N |
B316F7 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.30 | 0.00 | 90.00 | N |
9621FD | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 16.72 | 0.00 | 90.00 | N |
42CEE1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 11.15 | 0.00 | 90.00 | N |
4979C8 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 180.00 | 90.00 | S |
8CA0BF | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 180.00 | 90.00 | S |
6C95E7 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 180.00 | 90.00 | S |
F209CC | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 0.00 | 90.00 | N |
155BD6 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 0.00 | 90.00 | N |
C5EA55 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 0.00 | 90.00 | N |
8177BA | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 270.00 | 90.00 | W |
5E657E | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 0.00 | 90.00 | N |
4B1439 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 37.16 | 90.00 | 90.00 | E |
4ABC66 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 30.66 | 180.00 | 90.00 | S |
5B04CF | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 14.86 | 270.00 | 90.00 | W |
8D1BC4 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 180.00 | 90.00 | S |
4B55FA | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 90.00 | 90.00 | E |
9C3A6A | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 20.44 | 0.00 | 90.00 | N |
C52EE0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 3.72 | 0.00 | 90.00 | N |
1C33AD | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 270.00 | 90.00 | W |
6CC177 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 DRESSING ROOM ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 3.90 | 270.00 | 0.00 | |
F7D24D | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 3.72 | 0.00 | 90.00 | N |
FLOOR 3 ELEVATOR HALL ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 34.37 | 0.00 | 0.00 | |
FLOOR 3 HUMID ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 10.03 | 270.00 | 0.00 | |
FC22D1 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 0.00 | 90.00 | N |
DD2E2D | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.50 | 270.00 | 90.00 | W |
FLOOR 3 JANITOR ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 5.85 | 0.00 | 0.00 | |
FLOOR 3 LOCKER ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 11.15 | 0.00 | 0.00 | |
68A2D7 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 21.37 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 70.51 | 270.00 | 0.00 | |
CE3FEF | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 11.15 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE TOILET ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 17.84 | 0.00 | 0.00 | |
CE618F | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 23.23 | 90.00 | 90.00 | E |
FLOOR 3 MECHANICAL ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 32.52 | 0.00 | 0.00 | |
FLOOR 3 MECHANICAL HALL ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 27.87 | 0.00 | 0.00 | |
5ADC59 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 68.75 | 0.00 | 90.00 | N |
FLOOR 3 OFFICE ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 282.05 | 180.00 | 0.00 | |
D4F411 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE HALL ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 77.48 | 270.00 | 0.00 | |
B35AD6 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE TOILET ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 5.02 | 270.00 | 0.00 | |
D22917 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 18.58 | 90.00 | 90.00 | E |
C1BC97 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 60.39 | 180.00 | 90.00 | S |
FLOOR 3 PHYICAL THERAPY 1 ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 120.77 | 180.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY 2 ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 55.00 | 90.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 7.80 | 90.00 | 0.00 | |
FLOOR 3 STORAGE 1 ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 10.03 | 180.00 | 0.00 | |
FLOOR 3 STORAGE 2 ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 7.80 | 180.00 | 0.00 | |
FLOOR 3 TREATMENT ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 44.22 | 90.00 | 0.00 | |
8DA7DB | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.02 | 180.00 | 90.00 | S |
38B339 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.87 | 270.00 | 90.00 | W |
FLOOR 3 UNDEVELOPED 1 ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 210.70 | 0.00 | 0.00 | |
BE5F2F | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 14.86 | 270.00 | 90.00 | W |
1DEE26 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 37.16 | 180.00 | 90.00 | S |
FLOOR 3 UNDEVELOPED 2 ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 107.02 | 180.00 | 0.00 | |
FLOOR 3 UTILITY ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 20.07 | 0.00 | 0.00 | |
C86329 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 38.09 | 90.00 | 90.00 | E |
FLOOR 3 WORK ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 53.33 | 90.00 | 0.00 | |
DFC6F0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 19.51 | 90.00 | 90.00 | E |
88E360 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.89 | 0.00 | 90.00 | N |
E7B55F | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 11.15 | 180.00 | 90.00 | S |
NE STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 0.00 | 180.00 | |
NE STAIR ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 15.61 | 0.00 | 0.00 | |
FB3814 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 19.51 | 180.00 | 90.00 | S |
FCD12D | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 55.74 | 270.00 | 90.00 | W |
NW ELEVATOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 90.00 | 180.00 | |
NW ELEVATOR ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 13.01 | 90.00 | 0.00 | |
5507DC | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.30 | 270.00 | 90.00 | W |
2E2D0C | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.89 | 0.00 | 90.00 | N |
AF0124 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.30 | 90.00 | 90.00 | E |
NW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.84 | 270.00 | 180.00 | |
NW STAIR ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 17.84 | 270.00 | 0.00 | |
850EA7 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 33.45 | 180.00 | 90.00 | S |
270BCE | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.30 | 270.00 | 90.00 | W |
SW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.92 | 270.00 | 180.00 | |
SW STAIR ROOF | NONRES_ROOF | 0.30 | 0.351 | 0.376 | 8.92 | 180.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
78F987 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 481E71 | 180.00 | 90.00 | S | ||
D8037E | WINDOW_U_1.08_SHGC_0.25 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 5.778 | 0.306 | 0.155 | No | 5F762C | 180.00 | 90.00 | S | ||
4A8120 | WINDOW_U_1.08_SHGC_0.25 | 2.32 | 0.00 | 0.00 | 2.32 | 2.32 | 5.778 | 0.306 | 0.155 | No | 84FB73 | 0.00 | 90.00 | N | ||
AAE778 | WINDOW_U_1.08_SHGC_0.25 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 5.778 | 0.306 | 0.155 | No | FE5A3C | 270.00 | 90.00 | W | ||
3AAD8B | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | F629C1 | 0.00 | 90.00 | N | ||
8128A9 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | F629C1 | 0.00 | 90.00 | N | ||
9B1541 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 879583 | 180.00 | 90.00 | S | ||
CF850A | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 879583 | 180.00 | 90.00 | S | ||
A6BA23 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | E326E4 | 90.00 | 90.00 | E | ||
D10D28 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | E326E4 | 90.00 | 90.00 | E | ||
591336 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 1D96D7 | 90.00 | 90.00 | E | ||
38B811 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 1D96D7 | 90.00 | 90.00 | E | ||
C044D6 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 1D96D7 | 90.00 | 90.00 | E | ||
1D94BE | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 6D2616 | 0.00 | 90.00 | N | ||
18748E | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 6D2616 | 0.00 | 90.00 | N | ||
137A56 | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | A5A6A3 | 180.00 | 90.00 | S | ||
8D508E | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 28B002 | 180.00 | 90.00 | S | ||
B2D381 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 28B002 | 180.00 | 90.00 | S | ||
1DA13A | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 28B002 | 180.00 | 90.00 | S | ||
44E54A | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 28B002 | 180.00 | 90.00 | S | ||
757D10 | WINDOW_U_1.08_SHGC_0.25 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 5.778 | 0.306 | 0.155 | No | EA6DC8 | 180.00 | 90.00 | S | ||
E33BAE | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | B40F89 | 270.00 | 90.00 | W | ||
24167A | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 997723 | 180.00 | 90.00 | S | ||
2C0938 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 997723 | 180.00 | 90.00 | S | ||
8600DD | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | CEC7BD | 180.00 | 90.00 | S | ||
A1ED60 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 859BC1 | 0.00 | 90.00 | N | ||
E8D997 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 859BC1 | 0.00 | 90.00 | N | ||
88E1FC | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 859BC1 | 0.00 | 90.00 | N | ||
F83F33 | WINDOW_U_1.08_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | 61E610 | 90.00 | 90.00 | E | ||
B1F5EE | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | D95F04 | 90.00 | 90.00 | E | ||
F52F3D | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 208CCF | 90.00 | 90.00 | E | ||
80885D | WINDOW_U_1.08_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 5.778 | 0.306 | 0.155 | No | AEF992 | 180.00 | 90.00 | S | ||
FEEF06 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 54D065 | 180.00 | 90.00 | S | ||
2BE8DE | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 1775A6 | 270.00 | 90.00 | W | ||
513E2A | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 1775A6 | 270.00 | 90.00 | W | ||
BA5CD9 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 1775A6 | 270.00 | 90.00 | W | ||
1AD478 | WINDOW_U_1.08_SHGC_0.25 | 3.72 | 0.00 | 0.00 | 3.72 | 3.72 | 5.778 | 0.306 | 0.155 | No | 97F00A | 180.00 | 90.00 | S | ||
27F0AC | WINDOW_U_1.08_SHGC_0.25 | 5.95 | 0.00 | 0.00 | 5.95 | 5.95 | 5.778 | 0.306 | 0.155 | No | A497E9 | 180.00 | 90.00 | S | ||
724114 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 88A75F | 180.00 | 90.00 | S | ||
D538C4 | WINDOW_U_1.08_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | B4E619 | 90.00 | 90.00 | E | ||
5635BC | WINDOW_U_1.08_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | B4E619 | 90.00 | 90.00 | E | ||
831C1D | WINDOW_U_1.08_SHGC_0.25 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 5.778 | 0.306 | 0.155 | No | 9EC269 | 0.00 | 90.00 | N | ||
9BB95F | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | B316F7 | 0.00 | 90.00 | N | ||
C0778D | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | B316F7 | 0.00 | 90.00 | N | ||
7D2D69 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 9621FD | 0.00 | 90.00 | N | ||
2EF63B | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 9621FD | 0.00 | 90.00 | N | ||
C417C0 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 42CEE1 | 0.00 | 90.00 | N | ||
EB042B | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 4B1439 | 90.00 | 90.00 | E | ||
4C1F71 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 4B1439 | 90.00 | 90.00 | E | ||
D23C8B | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 4B1439 | 90.00 | 90.00 | E | ||
B4E4BE | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 4B1439 | 90.00 | 90.00 | E | ||
EEF55D | WINDOW_U_1.08_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 5.778 | 0.306 | 0.155 | No | 4ABC66 | 180.00 | 90.00 | S | ||
E55A57 | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | 4ABC66 | 180.00 | 90.00 | S | ||
93D018 | WINDOW_U_1.08_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 5.778 | 0.306 | 0.155 | No | 5B04CF | 270.00 | 90.00 | W | ||
DD9F5D | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | 4B55FA | 90.00 | 90.00 | E | ||
15B02B | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 9C3A6A | 0.00 | 90.00 | N | ||
820282 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 9C3A6A | 0.00 | 90.00 | N | ||
9BA05A | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 68A2D7 | 0.00 | 90.00 | N | ||
C639E8 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 68A2D7 | 0.00 | 90.00 | N | ||
A2790A | WINDOW_U_1.08_SHGC_0.25 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 5.778 | 0.306 | 0.155 | No | CE3FEF | 0.00 | 90.00 | N | ||
79FCEE | WINDOW_U_1.08_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | CE618F | 90.00 | 90.00 | E | ||
EDE617 | WINDOW_U_1.08_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | CE618F | 90.00 | 90.00 | E | ||
C61F0D | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
7248C5 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
29FA28 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
F0B23F | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
EEC10E | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
944FCE | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
C41399 | WINDOW_U_1.08_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 5.778 | 0.306 | 0.155 | No | 5ADC59 | 0.00 | 90.00 | N | ||
95BA33 | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | D22917 | 90.00 | 90.00 | E | ||
F27282 | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | D22917 | 90.00 | 90.00 | E | ||
3DB407 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | C1BC97 | 180.00 | 90.00 | S | ||
3DADE2 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | C1BC97 | 180.00 | 90.00 | S | ||
DF3E2C | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | C1BC97 | 180.00 | 90.00 | S | ||
5031C8 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | C1BC97 | 180.00 | 90.00 | S | ||
C087D0 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | 8DA7DB | 180.00 | 90.00 | S | ||
D2CA75 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | 8DA7DB | 180.00 | 90.00 | S | ||
B0FB49 | WINDOW_U_1.08_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 5.778 | 0.306 | 0.155 | No | 8DA7DB | 180.00 | 90.00 | S | ||
FE9BC9 | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | 38B339 | 270.00 | 90.00 | W | ||
9DF7DE | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | 38B339 | 270.00 | 90.00 | W | ||
D0BE44 | WINDOW_U_1.08_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 5.778 | 0.306 | 0.155 | No | 38B339 | 270.00 | 90.00 | W | ||
6B5226 | WINDOW_U_1.08_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 5.778 | 0.306 | 0.155 | No | BE5F2F | 270.00 | 90.00 | W | ||
8F59F7 | WINDOW_U_1.08_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 5.778 | 0.306 | 0.155 | No | 1DEE26 | 180.00 | 90.00 | S | ||
44F571 | WINDOW_U_1.08_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 5.778 | 0.306 | 0.155 | No | 1DEE26 | 180.00 | 90.00 | S | ||
6BD844 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | C86329 | 90.00 | 90.00 | E | ||
86D536 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | C86329 | 90.00 | 90.00 | E | ||
BAF71D | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | C86329 | 90.00 | 90.00 | E | ||
3833A2 | WINDOW_U_1.08_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 5.778 | 0.306 | 0.155 | No | C86329 | 90.00 | 90.00 | E | ||
2111A1 | WINDOW_U_1.08_SHGC_0.25 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 5.778 | 0.306 | 0.155 | No | DFC6F0 | 90.00 | 90.00 | E | ||
9BC521 | WINDOW_U_1.08_SHGC_0.25 | 5.71 | 0.00 | 0.00 | 5.71 | 5.71 | 5.778 | 0.306 | 0.155 | No | 88E360 | 0.00 | 90.00 | N | ||
142781 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | 88E360 | 0.00 | 90.00 | N | ||
E74902 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | 2E2D0C | 0.00 | 90.00 | N | ||
93BBC3 | WINDOW_U_1.08_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 5.778 | 0.306 | 0.155 | No | 2E2D0C | 0.00 | 90.00 | N | ||
C635A6 | WINDOW_U_1.08_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 5.778 | 0.306 | 0.155 | No | 850EA7 | 180.00 | 90.00 | S | ||
Total or Average | 308.29 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 97.22 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 211.08 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
71E924 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 8E5BB9 |
5E66D1 | OPAQUEDOOR | 8.100 | 8.100 | 5.95 | 529072 |
E14DAE | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | D95F04 |
84A1D5 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 3330D8 |
9CB8E5 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 88E360 |
EDE769 | OPAQUEDOOR | 8.100 | 8.100 | 2.97 | 5507DC |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 61078.37 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 169360.63 | 122577.85 | 46782.78 | 0.72 | 3.23 | |||
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 247220.17 | 193031.53 | 54188.65 | 0.78 | 3.13 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 163347.3 | 2.80 | 9.57 | N/A | 10.75 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 236650.6 | 2.65 | 9.05 | N/A | 10.22 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | Coil:Heating:Water | 1893.38 | 1875.84 | - |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | Coil:Heating:Water | 313.95 | 181.09 | - |
FLOOR 1 CAFE VAV BOX REHEAT COIL | Coil:Heating:Water | 9670.29 | 5578.07 | - |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | Coil:Heating:Water | 1222.40 | 1211.08 | - |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 1533.25 | 1519.05 | - |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Water | 768.66 | 443.38 | - |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 940.44 | 542.47 | - |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 1539.27 | 887.89 | - |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 8555.24 | 4934.88 | - |
FLOOR 1 HUMID VAV BOX REHEAT COIL | Coil:Heating:Water | 382.65 | 220.72 | - |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 680.87 | 392.74 | - |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 686.88 | 396.21 | - |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | Coil:Heating:Water | 9448.80 | 5450.31 | - |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1294.56 | 746.74 | - |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1183.36 | 1172.40 | - |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 7849.27 | 4527.66 | - |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1967.03 | 1134.63 | - |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Water | 3425.24 | 1975.77 | - |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | Coil:Heating:Water | 935.45 | 650.42 | - |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 4121.51 | 2377.39 | - |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 876.98 | 505.86 | - |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9658.33 | 5571.17 | - |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1183.36 | 1172.40 | - |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 1702.71 | 982.17 | - |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2393.10 | 1380.40 | - |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 283.28 | 163.40 | - |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | Coil:Heating:Water | 2319.06 | 1337.69 | - |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1183.36 | 1172.40 | - |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Water | 2610.16 | 1505.61 | - |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25262.37 | 25028.42 | - |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 25401.01 | 25165.77 | - |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20862.23 | 20669.03 | - |
FLOOR 1 PACU VAV BOX REHEAT COIL | Coil:Heating:Water | 1420.03 | 1406.88 | - |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2389.15 | 1378.12 | - |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2485.06 | 2462.05 | - |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4444.18 | 4403.02 | - |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1183.36 | 1172.40 | - |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9368.28 | 9281.52 | - |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Water | 5760.92 | 3323.04 | - |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 617.92 | 356.43 | - |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 8866.41 | 8784.30 | - |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | Coil:Heating:Water | 1060.84 | 611.92 | - |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | Coil:Heating:Water | 419.93 | 242.22 | - |
FLOOR 1 SOIL VAV BOX REHEAT COIL | Coil:Heating:Water | 2761.18 | 2735.61 | - |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | Coil:Heating:Water | 1227.19 | 1215.83 | - |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 3944.54 | 3908.01 | - |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | Coil:Heating:Water | 6357.95 | 6299.07 | - |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2612.93 | 1507.20 | - |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 1383.56 | 798.08 | - |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 8766.17 | 5284.15 | - |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | Coil:Heating:Water | 2241.82 | 1293.14 | - |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 2827.64 | 1631.05 | - |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 245.06 | 141.36 | - |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 3187.84 | 1838.83 | - |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | Coil:Heating:Water | 1272.96 | 734.27 | - |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2712.32 | 1.00 | |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1379.08 | 1.00 | |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Electric | 197.99 | 1.00 | |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9668.20 | 1.00 | |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7044.51 | 1.00 | |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9598.86 | 1.00 | |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1836.93 | 1.00 | |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7419.46 | 1.00 | |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3881.82 | 1.00 | |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10239.68 | 1.00 | |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4748.62 | 1.00 | |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5217.50 | 1.00 | |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 496.31 | 1.00 | |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 479.42 | 1.00 | |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 467.14 | 1.00 | |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 482.77 | 1.00 | |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 507.27 | 1.00 | |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 509.92 | 1.00 | |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 504.33 | 1.00 | |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 308.79 | 1.00 | |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 518.28 | 1.00 | |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 633.77 | 1.00 | |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2938.68 | 1.00 | |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1026.82 | 1.00 | |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Electric | 5646.07 | 1.00 | |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1408.23 | 1.00 | |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 735.88 | 1.00 | |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 785.25 | 1.00 | |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 145.02 | 1.00 | |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 260.00 | 1.00 | |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 331.66 | 1.00 | |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 641.01 | 1.00 | |
FLOOR 2 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 4182.57 | 1.00 | |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1965.16 | 1.00 | |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1163.60 | 1.00 | |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | Coil:Heating:Electric | 6930.48 | 1.00 | |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 187.00 | 1.00 | |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 979.77 | 1.00 | |
FLOOR 3 HUMID VAV BOX REHEAT COIL | Coil:Heating:Electric | 465.44 | 1.00 | |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 438.77 | 1.00 | |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | Coil:Heating:Electric | 693.53 | 1.00 | |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 4046.87 | 1.00 | |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 4137.24 | 1.00 | |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1142.19 | 1.00 | |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 11006.92 | 1.00 | |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 2418.07 | 1.00 | |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1163.60 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 27410.57 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9370.64 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1810.04 | 1.00 | |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1125.92 | 1.00 | |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 294.41 | 1.00 | |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 7749.26 | 1.00 | |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9380.21 | 1.00 | |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5036.44 | 1.00 | |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 589.21 | 1.00 | |
FLOOR 3 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 3375.34 | 1.00 | |
NE STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2714.19 | 1.00 | |
NW ELEVATOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1688.40 | 1.00 | |
NW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 3092.67 | 1.00 | |
SW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1270.70 | 1.00 | |
AHU-1_HEATC | Coil:Heating:Water | 2744.43 | 2707.41 | - |
AHU-1_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
AHU-1_EXTRAWATERHEATC | Coil:Heating:Water | 2744.43 | 2707.41 | - |
AHU-2_HEATC | Coil:Heating:Water | 43664.66 | 41558.70 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
FLOOR 1 ANESTHESIA EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 54.61 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 LOBBY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.16 | 127.44 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.42 | 323.16 | 778.12 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 NURSE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 PRE-OP TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL HOLD EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 35.39 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL WORK EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.14 | 113.76 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 CONFERENCE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.05 | 40.45 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 RECEPTION TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 WORK TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 X-RAY EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.85 | 661.02 | 778.13 | 1.00 | Zone Exhaust Fans |
FLOOR 3 LOUNGE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.15 | 121.35 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 OFFICE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 53.09 | 803.55 | 1.00 | Zone Exhaust Fans |
AHU-1_FAN | Fan:VariableVolume | 0.60 | 1389.42 | 8.15 | 18847.45 | 2313.39 | 1.00 | Fan Energy |
AHU-2_FAN | Fan:VariableVolume | 0.60 | 1389.42 | 14.21 | 32660.22 | 2298.46 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0001 | 8.07 | 127739.32 | 0.30 |
HEATSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 179352.00 | 0.0013 | 334.65 | 255487.18 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.20 | 0.81 | 0.78 | 0.28 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 163347.27 | 2.80 | 9.57 | 10.75 | 8.7592 | 3.06 | 10.46 | 6.7291 | 3.28 | 11.20 | 4.3557 | 3.39 | 11.57 | 1.9582 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 236650.55 | 2.65 | 9.05 | 10.22 | 15.2772 | 2.90 | 9.91 | 11.3107 | 3.13 | 10.69 | 7.0579 | 3.24 | 11.06 | 3.1763 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 819.64 | 819.64 | 0.065 | 0.068 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 1 CAFE | 4384.05 | 4384.05 | 0.347 | 0.347 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
FLOOR 1 CLEAN | 554.76 | 554.76 | 0.044 | 0.044 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 36.78 | 0.00412 |
FLOOR 1 CLEAN WORK | 695.82 | 695.82 | 0.055 | 0.055 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 37.54 | 0.00412 |
FLOOR 1 DICTATION | 360.30 | 360.30 | 0.028 | 0.028 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 DRESSING ROOM | 426.92 | 426.92 | 0.034 | 0.034 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 44.20 | 0.00412 |
FLOOR 1 HUMID | 179.01 | 179.01 | 0.014 | 0.014 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 IT ROOM | 322.18 | 322.18 | 0.025 | 0.025 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 LOBBY | 4288.79 | 4288.79 | 0.339 | 0.339 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 43.21 | 0.00412 |
FLOOR 1 LOCKER ROOM | 3562.46 | 3562.46 | 0.282 | 0.282 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 43.21 | 0.00412 |
FLOOR 1 LOUNGE | 1554.54 | 1554.54 | 0.123 | 0.123 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 37.92 | 0.00412 |
FLOOR 1 MRI CONTROL ROOM | 1870.50 | 1870.50 | 0.148 | 0.148 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 42.67 | 0.00412 |
FLOOR 1 MRI ROOM | 4383.17 | 4383.17 | 0.347 | 0.347 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 42.31 | 0.00412 |
FLOOR 1 NOURISHMENT | 772.75 | 772.75 | 0.061 | 0.061 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 35.92 | 0.00412 |
FLOOR 1 NURSE STATION | 1052.45 | 1052.45 | 0.083 | 0.083 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 35.92 | 0.00412 |
FLOOR 1 OFFICE | 1184.79 | 1184.79 | 0.094 | 0.094 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:40:00 | 35.92 | 0.00412 |
FLOOR 1 OPERATING ROOM 1 | 7437.79 | 7437.79 | 0.907 | 0.907 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 41.10 | 0.00412 |
FLOOR 1 OPERATING ROOM 2 | 7478.40 | 7478.40 | 0.912 | 0.912 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 39.41 | 0.00412 |
FLOOR 1 OPERATING ROOM 3 | 5948.11 | 5948.11 | 0.685 | 0.749 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 07:20:00 | 32.68 | 0.00412 |
FLOOR 1 PACU | 519.56 | 519.56 | 0.041 | 0.051 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 35.49 | 0.00412 |
FLOOR 1 PRE-OP ROOM 1 | 699.08 | 699.08 | 0.055 | 0.089 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 43.03 | 0.00412 |
FLOOR 1 PRE-OP ROOM 2 | 1115.63 | 1115.63 | 0.088 | 0.160 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 35.49 | 0.00412 |
FLOOR 1 PROCEDURE ROOM | 2313.50 | 2313.50 | 0.183 | 0.336 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
FLOOR 1 RECEPTION | 2614.11 | 2614.11 | 0.207 | 0.207 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
FLOOR 1 RECOVERY ROOM | 4024.03 | 4024.03 | 0.318 | 0.318 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 44.20 | 0.00412 |
FLOOR 1 SCHEDULING | 481.55 | 481.55 | 0.038 | 0.038 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 44.20 | 0.00412 |
FLOOR 1 SOIL | 549.28 | 549.28 | 0.043 | 0.099 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 36.78 | 0.00412 |
FLOOR 1 SOIL HOLD | 250.43 | 250.43 | 0.020 | 0.044 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 12:20:00 | 42.80 | 0.00412 |
FLOOR 1 SOIL WORK | 746.06 | 746.06 | 0.059 | 0.142 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 37.16 | 0.00412 |
FLOOR 1 STEP DOWN | 2885.67 | 2885.67 | 0.228 | 0.228 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 43.53 | 0.00412 |
FLOOR 2 CONFERENCE | 3532.85 | 3532.85 | 0.330 | 0.330 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 2 DICTATION | 266.40 | 266.40 | 0.024 | 0.024 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM 1 | 3779.25 | 3779.25 | 0.353 | 0.353 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
FLOOR 2 EXAM 2 | 2753.38 | 2753.38 | 0.257 | 0.257 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 44.20 | 0.00412 |
FLOOR 2 EXAM 3 | 3751.75 | 3751.75 | 0.350 | 0.350 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
FLOOR 2 EXAM 4 | 718.04 | 718.04 | 0.067 | 0.067 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 2 EXAM 5 | 2900.11 | 2900.11 | 0.271 | 0.271 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 40.08 | 0.00412 |
FLOOR 2 EXAM 6 | 1517.31 | 1517.31 | 0.142 | 0.142 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
FLOOR 2 EXAM 7 | 3797.12 | 3797.12 | 0.355 | 0.374 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 43.53 | 0.00412 |
FLOOR 2 EXAM 8 | 1856.12 | 1856.12 | 0.173 | 0.173 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
FLOOR 2 EXAM 9 | 2039.30 | 2039.30 | 0.190 | 0.190 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
FLOOR 2 LOUNGE | 402.34 | 402.34 | 0.038 | 0.038 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 35.06 | 0.00412 |
FLOOR 2 NURSE STATION 1 | 675.26 | 675.26 | 0.063 | 0.063 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 35.06 | 0.00412 |
FLOOR 2 NURSE STATION 2 | 825.72 | 825.72 | 0.077 | 0.077 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 35.06 | 0.00412 |
FLOOR 2 OFFICE | 3829.60 | 3829.60 | 0.358 | 0.358 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 40.08 | 0.00412 |
FLOOR 2 RECEPTION | 7355.11 | 7355.11 | 0.687 | 0.687 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 43.53 | 0.00412 |
FLOOR 2 SCHEDULING 1 | 958.92 | 958.92 | 0.090 | 0.090 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 35.06 | 0.00412 |
FLOOR 2 SCHEDULING 2 | 1061.97 | 1061.97 | 0.096 | 0.096 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 WORK | 5450.27 | 5450.27 | 0.509 | 0.509 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 43.80 | 0.00412 |
FLOOR 2 X-RAY | 9029.28 | 9029.28 | 0.843 | 0.843 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 41.19 | 0.00412 |
FLOOR 3 DRESSING ROOM | 243.70 | 243.70 | 0.023 | 0.023 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
FLOOR 3 HUMID | 606.57 | 606.57 | 0.057 | 0.057 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
FLOOR 3 LOCKER | 903.71 | 903.71 | 0.084 | 0.084 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 3 LOUNGE | 5272.68 | 5272.68 | 0.492 | 0.492 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 3 OFFICE | 14342.88 | 14342.88 | 1.339 | 1.339 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 3 PHYSICAL THERAPY 1 | 10713.34 | 10713.34 | 1.001 | 1.001 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 44.20 | 0.00412 |
FLOOR 3 PHYSICAL THERAPY 2 | 3662.89 | 3662.89 | 0.342 | 0.342 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
FLOOR 3 TREATMENT | 3029.12 | 3029.12 | 0.283 | 0.283 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 3 WORK | 4398.39 | 4398.39 | 0.411 | 0.411 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 40.76 | 0.00412 |
FLOOR 1 BIO HAZ | 146.37 | 146.37 | 0.011 | 0.011 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 ELECTRICAL ROOM | 698.77 | 698.77 | 0.055 | 0.055 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 11:50:00 | 42.22 | 0.00412 |
FLOOR 1 ELEVATOR PUMP ROOM | 3883.93 | 3883.93 | 0.307 | 0.307 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 42.09 | 0.00412 |
FLOOR 1 IT HALL | 317.23 | 317.23 | 0.024 | 0.024 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 LOBBY HALL | 608.19 | 608.19 | 0.046 | 0.046 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 LOBBY TOILET | 533.85 | 533.85 | 0.042 | 0.042 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 41.64 | 0.00412 |
FLOOR 1 LOCKER ROOM HALL | 922.08 | 922.08 | 0.071 | 0.071 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 MED GAS | 424.68 | 424.68 | 0.034 | 0.034 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 43.75 | 0.00412 |
FLOOR 1 MRI HALL | 410.93 | 410.93 | 0.031 | 0.031 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 MRI TOILET | 236.66 | 236.66 | 0.019 | 0.042 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 43.53 | 0.00412 |
FLOOR 1 NURSE HALL | 1126.64 | 1126.64 | 0.086 | 0.086 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 NURSE JANITOR | 131.79 | 131.79 | 0.010 | 0.010 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 NURSE TOILET | 155.05 | 155.05 | 0.012 | 0.042 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 PRE-OP HALL | 1123.60 | 1123.60 | 0.086 | 0.086 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 PRE-OP TOILET | 290.78 | 290.78 | 0.023 | 0.042 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 42.09 | 0.00412 |
FLOOR 1 RECEPTION HALL | 289.40 | 289.40 | 0.022 | 0.022 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 SCRUB | 195.82 | 195.82 | 0.015 | 0.015 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 STERILE HALL | 1226.26 | 1226.26 | 0.094 | 0.094 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 STERILE STORAGE | 648.42 | 648.42 | 0.050 | 0.050 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 STORAGE | 3979.45 | 3979.45 | 0.315 | 0.315 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 43.66 | 0.00412 |
FLOOR 1 SUB-STERILE | 1017.71 | 1017.71 | 0.080 | 0.080 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 40.08 | 0.00412 |
FLOOR 1 UTILITY HALL | 1283.62 | 1283.62 | 0.101 | 0.101 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 40.42 | 0.00412 |
FLOOR 1 UTILITY JANITOR | 114.02 | 114.02 | 0.009 | 0.009 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 1 UTILITY ROOM | 1447.16 | 1447.16 | 0.114 | 0.114 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 40.08 | 0.00412 |
FLOOR 1 VESTIBULE | 577.89 | 577.89 | 0.046 | 0.046 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 43.39 | 0.00412 |
FLOOR 2 CONFERENCE TOILET | 228.33 | 228.33 | 0.021 | 0.050 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM HALL 1 | 669.82 | 669.82 | 0.060 | 0.060 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM HALL 2 | 647.09 | 647.09 | 0.058 | 0.058 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM HALL 3 | 630.57 | 630.57 | 0.057 | 0.057 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM HALL 4 | 651.66 | 651.66 | 0.059 | 0.059 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM HALL 5 | 684.77 | 684.77 | 0.062 | 0.062 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 EXAM HALL 6 | 688.34 | 688.34 | 0.062 | 0.062 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 JANITOR | 657.32 | 657.32 | 0.061 | 0.061 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 41.86 | 0.00412 |
FLOOR 2 OFFICE HALL | 1386.98 | 1386.98 | 0.125 | 0.125 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 RECEPTION HALL | 1902.27 | 1902.27 | 0.171 | 0.171 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 RECEPTION TOILET | 414.89 | 414.89 | 0.037 | 0.099 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 STORAGE 1 | 195.27 | 195.27 | 0.018 | 0.018 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 STORAGE 2 | 351.06 | 351.06 | 0.032 | 0.032 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 STORAGE 3 | 448.40 | 448.40 | 0.040 | 0.040 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 UTILITY | 835.39 | 835.39 | 0.078 | 0.078 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 40.08 | 0.00412 |
FLOOR 2 WORK HALL | 2654.73 | 2654.73 | 0.239 | 0.239 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 31.29 | 0.00412 |
FLOOR 2 WORK TOILET | 325.37 | 325.37 | 0.030 | 0.042 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 41.64 | 0.00412 |
FLOOR 3 ELEVATOR HALL | 1276.81 | 1276.81 | 0.119 | 0.119 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 3 JANITOR | 459.83 | 459.83 | 0.043 | 0.043 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 42.31 | 0.00412 |
FLOOR 3 LOUNGE TOILET | 1183.81 | 1183.81 | 0.111 | 0.151 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 44.20 | 0.00412 |
FLOOR 3 MECHANICAL | 4234.85 | 4234.85 | 0.395 | 0.395 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 40.76 | 0.00412 |
FLOOR 3 MECHANICAL HALL | 1488.61 | 1488.61 | 0.139 | 0.139 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 44.20 | 0.00412 |
FLOOR 3 OFFICE HALL | 3151.17 | 3151.17 | 0.294 | 0.294 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 44.20 | 0.00412 |
FLOOR 3 OFFICE TOILET | 307.87 | 307.87 | 0.029 | 0.042 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 42.31 | 0.00412 |
FLOOR 3 PHYSICAL THERAPY TOILET | 371.02 | 371.02 | 0.035 | 0.066 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
FLOOR 3 STORAGE 1 | 440.22 | 440.22 | 0.041 | 0.041 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
FLOOR 3 STORAGE 2 | 383.70 | 383.70 | 0.036 | 0.036 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 44.20 | 0.00412 |
FLOOR 3 UNDEVELOPED 1 | 12224.07 | 12224.07 | 1.141 | 1.141 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 43.93 | 0.00412 |
FLOOR 3 UNDEVELOPED 2 | 6563.38 | 6563.38 | 0.613 | 0.613 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 43.93 | 0.00412 |
FLOOR 3 UTILITY | 767.92 | 767.92 | 0.072 | 0.072 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 44.20 | 0.00412 |
NE STAIR | 3537.30 | 3537.30 | 0.330 | 0.330 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 44.07 | 0.00412 |
NW ELEVATOR | 2200.41 | 2200.41 | 0.205 | 0.205 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 42.09 | 0.00412 |
NW STAIR | 4030.57 | 4030.57 | 0.376 | 0.376 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 43.21 | 0.00412 |
SW STAIR | 1656.05 | 1656.05 | 0.155 | 0.155 | RIYADH ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 42.67 | 0.00412 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 71.92 | 71.92 | 0.003 | 0.015 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 CAFE | 23.86 | 23.86 | 0.001 | 0.184 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 5.90 | 0.00619 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.000 | 0.018 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.000 | 0.023 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.000 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 DRESSING ROOM | 165.29 | 165.29 | 0.008 | 0.008 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.000 | 0.002 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 IT ROOM | 0.00 | 0.00 | 0.000 | 0.004 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 LOBBY | 184.67 | 184.67 | 0.008 | 0.032 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.000 | 0.042 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.000 | 0.023 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.000 | 0.024 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.000 | 0.062 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.000 | 0.014 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.000 | 0.020 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.000 | 0.019 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 0.00 | 0.000 | 0.239 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 0.00 | 0.000 | 0.249 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 0.00 | 0.000 | 0.247 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 PACU | 0.00 | 0.00 | 0.000 | 0.032 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.000 | 0.052 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.000 | 0.093 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 PROCEDURE ROOM | 0.00 | 0.00 | 0.000 | 0.108 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 RECEPTION | 0.00 | 0.00 | 0.000 | 0.050 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 RECOVERY ROOM | 42.16 | 42.16 | 0.002 | 0.161 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 5.90 | 0.00619 |
FLOOR 1 SCHEDULING | 0.00 | 0.00 | 0.000 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.000 | 0.018 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 SOIL HOLD | 0.00 | 0.00 | 0.000 | 0.008 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.000 | 0.025 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 STEP DOWN | 351.68 | 351.68 | 0.016 | 0.090 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 CONFERENCE | 888.53 | 888.53 | 0.040 | 0.049 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.000 | 0.003 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 EXAM 1 | 895.85 | 895.85 | 0.041 | 0.051 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 2 | 19.63 | 19.63 | 0.001 | 0.076 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 3 | 24.23 | 24.23 | 0.001 | 0.102 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 4 | 224.56 | 224.56 | 0.010 | 0.012 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 5 | 624.37 | 624.37 | 0.028 | 0.050 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 6 | 275.95 | 275.95 | 0.012 | 0.032 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.000 | 0.112 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 EXAM 8 | 216.99 | 216.99 | 0.010 | 0.038 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM 9 | 0.00 | 0.00 | 0.000 | 0.056 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.000 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.000 | 0.011 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.000 | 0.014 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 OFFICE | 1235.78 | 1235.78 | 0.056 | 0.056 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 RECEPTION | 850.10 | 850.10 | 0.038 | 0.098 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.000 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.000 | 0.014 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 WORK | 0.00 | 0.00 | 0.000 | 0.068 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 X-RAY | 0.00 | 0.00 | 0.000 | 0.127 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 3 DRESSING ROOM | 9.88 | 9.88 | 0.000 | 0.002 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 HUMID | 9.08 | 9.08 | 0.000 | 0.004 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | 5.90 | 0.00619 |
FLOOR 3 LOCKER | 32.75 | 32.75 | 0.001 | 0.008 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5.90 | 0.00619 |
FLOOR 3 LOUNGE | 95.48 | 95.48 | 0.004 | 0.048 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | 5.90 | 0.00619 |
FLOOR 3 OFFICE | 3463.19 | 3463.19 | 0.155 | 0.155 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 PHYSICAL THERAPY 1 | 3006.15 | 3006.15 | 0.136 | 0.184 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 PHYSICAL THERAPY 2 | 309.81 | 309.81 | 0.014 | 0.084 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 TREATMENT | 110.93 | 110.93 | 0.005 | 0.067 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 5.90 | 0.00619 |
FLOOR 3 WORK | 1557.30 | 1557.30 | 0.070 | 0.070 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 BIO HAZ | 46.20 | 46.20 | 0.002 | 0.003 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 ELEVATOR PUMP ROOM | 74.61 | 74.61 | 0.003 | 0.003 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.000 | 0.004 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.000 | 0.007 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 LOBBY TOILET | 112.88 | 112.88 | 0.005 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.000 | 0.014 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 MED GAS | 306.21 | 306.21 | 0.014 | 0.014 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.000 | 0.004 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 MRI TOILET | 47.28 | 47.28 | 0.002 | 0.002 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.000 | 0.014 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.000 | 0.003 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.000 | 0.015 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 PRE-OP TOILET | 110.13 | 110.13 | 0.005 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.004 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 SCRUB | 17.04 | 17.04 | 0.001 | 0.002 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.000 | 0.017 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.000 | 0.022 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 1 STORAGE | 2246.35 | 2246.35 | 0.101 | 0.101 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 SUB-STERILE | 381.50 | 381.50 | 0.017 | 0.017 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 UTILITY HALL | 655.78 | 655.78 | 0.030 | 0.030 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 UTILITY JANITOR | 9.82 | 9.82 | 0.000 | 0.002 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 UTILITY ROOM | 702.32 | 702.32 | 0.032 | 0.032 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 1 VESTIBULE | 172.45 | 172.45 | 0.008 | 0.008 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 CONFERENCE TOILET | 28.73 | 28.73 | 0.001 | 0.001 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM HALL 1 | 154.90 | 154.90 | 0.007 | 0.007 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM HALL 2 | 10.51 | 10.51 | 0.000 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM HALL 3 | 38.61 | 38.61 | 0.002 | 0.005 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.000 | 0.006 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 JANITOR | 292.06 | 292.06 | 0.013 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 OFFICE HALL | 192.82 | 192.82 | 0.009 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.016 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 STORAGE 1 | 21.41 | 21.41 | 0.001 | 0.003 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.000 | 0.007 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.000 | 0.008 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 UTILITY | 382.84 | 382.84 | 0.017 | 0.017 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.000 | 0.024 | RIYADH ANN HTG 99.6% CONDNS DB | 5.90 | 0.00619 | |
FLOOR 2 WORK TOILET | 182.34 | 182.34 | 0.008 | 0.008 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 ELEVATOR HALL | 683.21 | 683.21 | 0.031 | 0.031 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 JANITOR | 351.54 | 351.54 | 0.016 | 0.016 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 LOUNGE TOILET | 526.71 | 526.71 | 0.024 | 0.024 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 MECHANICAL HALL | 568.08 | 568.08 | 0.026 | 0.026 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 OFFICE HALL | 1227.52 | 1227.52 | 0.056 | 0.056 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 OFFICE TOILET | 237.67 | 237.67 | 0.011 | 0.011 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 PHYSICAL THERAPY TOILET | 47.96 | 47.96 | 0.002 | 0.002 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 STORAGE 1 | 149.60 | 149.60 | 0.007 | 0.007 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 STORAGE 2 | 144.23 | 144.23 | 0.007 | 0.007 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 UNDEVELOPED 1 | 3738.56 | 3738.56 | 0.168 | 0.168 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 UNDEVELOPED 2 | 2594.48 | 2594.48 | 0.117 | 0.117 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
FLOOR 3 UTILITY | 278.99 | 278.99 | 0.013 | 0.013 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
NE STAIR | 2094.08 | 2094.08 | 0.095 | 0.095 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
NW ELEVATOR | 1244.68 | 1244.68 | 0.056 | 0.056 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
NW STAIR | 2080.29 | 2080.29 | 0.094 | 0.094 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
SW STAIR | 994.38 | 994.38 | 0.045 | 0.045 | RIYADH ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 5.90 | 0.00619 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AHU-1 | 8.15 | 8.15 | 2.20 | 2.20 |
AHU-2 | 14.21 | 14.21 | 2.52 | 2.52 |
Report: System Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FLOOR 1 ANESTHESIA | 2688.83 | 7404.50 | 2462.67 |
FLOOR 1 CAFE | 1386.67 | 5991.83 | 340.67 |
FLOOR 1 CLEAN | 1087.50 | 7626.83 | 1004.67 |
FLOOR 1 CLEAN WORK | 2002.33 | 7694.50 | 1956.17 |
FLOOR 1 DICTATION | 227.17 | 7714.00 | 223.33 |
FLOOR 1 DRESSING ROOM | 1861.17 | 7070.50 | 1406.17 |
FLOOR 1 HUMID | 61.33 | 7674.83 | 49.00 |
FLOOR 1 IT ROOM | 402.83 | 7625.50 | 357.17 |
FLOOR 1 LOBBY | 1011.33 | 6701.17 | 321.67 |
FLOOR 1 LOCKER ROOM | 520.50 | 7172.67 | 114.00 |
FLOOR 1 LOUNGE | 332.33 | 7366.00 | 74.17 |
FLOOR 1 MRI CONTROL ROOM | 588.67 | 6551.50 | 135.33 |
FLOOR 1 MRI ROOM | 448.50 | 6406.83 | 49.83 |
FLOOR 1 NOURISHMENT | 240.50 | 7516.00 | 85.17 |
FLOOR 1 NURSE STATION | 333.33 | 7551.17 | 202.67 |
FLOOR 1 OFFICE | 115.00 | 7599.67 | 62.50 |
FLOOR 1 OPERATING ROOM 1 | 4623.67 | 7606.17 | 4486.33 |
FLOOR 1 OPERATING ROOM 2 | 5475.33 | 7669.17 | 5389.17 |
FLOOR 1 OPERATING ROOM 3 | 6501.67 | 7764.50 | 6492.67 |
FLOOR 1 PACU | 2669.83 | 7726.50 | 2641.67 |
FLOOR 1 PRE-OP ROOM 1 | 2563.50 | 7695.00 | 2512.67 |
FLOOR 1 PRE-OP ROOM 2 | 2747.83 | 7819.17 | 2747.83 |
FLOOR 1 PROCEDURE ROOM | 3448.67 | 7657.83 | 3360.00 |
FLOOR 1 RECEPTION | 546.50 | 7072.50 | 103.00 |
FLOOR 1 RECOVERY ROOM | 2561.33 | 7360.67 | 2306.33 |
FLOOR 1 SCHEDULING | 400.33 | 7515.33 | 283.50 |
FLOOR 1 SOIL | 3655.67 | 7830.00 | 3655.67 |
FLOOR 1 SOIL HOLD | 3443.17 | 7827.33 | 3443.17 |
FLOOR 1 SOIL WORK | 3780.33 | 7830.00 | 3780.33 |
FLOOR 1 STEP DOWN | 2881.67 | 7319.33 | 2539.00 |
FLOOR 2 CONFERENCE | 1671.50 | 6742.50 | 1243.00 |
FLOOR 2 DICTATION | 924.67 | 7830.00 | 924.67 |
FLOOR 2 EXAM 1 | 3586.33 | 7536.83 | 3407.67 |
FLOOR 2 EXAM 2 | 2902.50 | 7745.67 | 2890.67 |
FLOOR 2 EXAM 3 | 3277.17 | 7763.83 | 3271.33 |
FLOOR 2 EXAM 4 | 3232.17 | 7661.33 | 3190.00 |
FLOOR 2 EXAM 5 | 3284.67 | 7634.17 | 3225.33 |
FLOOR 2 EXAM 6 | 3387.50 | 7692.17 | 3357.33 |
FLOOR 2 EXAM 7 | 3264.00 | 7772.83 | 3258.83 |
FLOOR 2 EXAM 8 | 3306.00 | 7679.33 | 3269.50 |
FLOOR 2 EXAM 9 | 2845.83 | 7749.17 | 2834.17 |
FLOOR 2 LOUNGE | 613.67 | 7823.00 | 613.67 |
FLOOR 2 NURSE STATION 1 | 463.33 | 7723.83 | 458.33 |
FLOOR 2 NURSE STATION 2 | 438.50 | 7684.17 | 430.33 |
FLOOR 2 OFFICE | 1402.00 | 7333.50 | 1309.50 |
FLOOR 2 RECEPTION | 975.17 | 6901.50 | 558.67 |
FLOOR 2 SCHEDULING 1 | 349.50 | 7814.33 | 349.50 |
FLOOR 2 SCHEDULING 2 | 375.67 | 7793.17 | 375.67 |
FLOOR 2 WORK | 421.83 | 7433.67 | 371.33 |
FLOOR 2 X-RAY | 442.17 | 6699.00 | 0.00 |
FLOOR 3 DRESSING ROOM | 2236.83 | 7749.83 | 2231.67 |
FLOOR 3 HUMID | 1877.17 | 7683.67 | 1861.50 |
FLOOR 3 LOCKER | 1525.50 | 7461.17 | 1389.17 |
FLOOR 3 LOUNGE | 1561.17 | 6964.83 | 1154.33 |
FLOOR 3 OFFICE | 1628.50 | 7025.50 | 1295.33 |
FLOOR 3 PHYSICAL THERAPY 1 | 3811.83 | 7258.50 | 3496.67 |
FLOOR 3 PHYSICAL THERAPY 2 | 3976.83 | 7657.00 | 3912.17 |
FLOOR 3 TREATMENT | 3680.83 | 7630.17 | 3599.17 |
FLOOR 3 WORK | 2228.33 | 6623.33 | 1689.00 |
FLOOR 1 BIO HAZ | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.00 | 0.00 | 0.00 |
NE STAIR | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 0.00 | 0.00 | 0.00 |
NW STAIR | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.00 | 0.00 | 0.00 |
Facility | 7422.33 | 7830.00 | 6816.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FLOOR 1 ANESTHESIA | 0.00 | 559.67 | 0.00 | 559.67 |
FLOOR 1 CAFE | 0.00 | 910.00 | 0.00 | 910.00 |
FLOOR 1 CLEAN | 0.00 | 367.50 | 0.00 | 367.50 |
FLOOR 1 CLEAN WORK | 0.00 | 331.17 | 0.00 | 331.17 |
FLOOR 1 DICTATION | 0.00 | 302.83 | 0.00 | 302.83 |
FLOOR 1 DRESSING ROOM | 0.00 | 323.33 | 0.00 | 323.33 |
FLOOR 1 HUMID | 0.00 | 317.33 | 0.00 | 317.33 |
FLOOR 1 IT ROOM | 0.00 | 319.50 | 0.00 | 319.50 |
FLOOR 1 LOBBY | 0.00 | 354.83 | 0.00 | 354.83 |
FLOOR 1 LOCKER ROOM | 0.00 | 402.67 | 0.00 | 402.67 |
FLOOR 1 LOUNGE | 0.00 | 475.67 | 0.00 | 475.67 |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 994.83 | 0.00 | 994.83 |
FLOOR 1 MRI ROOM | 0.00 | 1709.17 | 0.00 | 1709.17 |
FLOOR 1 NOURISHMENT | 0.00 | 380.17 | 0.00 | 380.17 |
FLOOR 1 NURSE STATION | 0.00 | 359.00 | 0.00 | 359.00 |
FLOOR 1 OFFICE | 0.00 | 353.00 | 0.00 | 353.00 |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 1588.00 | 0.00 | 1588.00 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 1395.17 | 0.00 | 1395.17 |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 1797.83 | 0.00 | 1797.83 |
FLOOR 1 PACU | 0.00 | 296.83 | 0.00 | 296.83 |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 271.00 | 0.00 | 271.00 |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 186.17 | 0.00 | 186.17 |
FLOOR 1 PROCEDURE ROOM | 0.83 | 184.83 | 0.83 | 184.83 |
FLOOR 1 RECEPTION | 0.00 | 563.00 | 0.00 | 563.00 |
FLOOR 1 RECOVERY ROOM | 0.00 | 530.17 | 0.00 | 530.17 |
FLOOR 1 SCHEDULING | 0.00 | 327.00 | 0.00 | 327.00 |
FLOOR 1 SOIL | 0.00 | 111.50 | 0.00 | 111.50 |
FLOOR 1 SOIL HOLD | 0.00 | 138.33 | 0.00 | 138.33 |
FLOOR 1 SOIL WORK | 0.00 | 91.50 | 0.00 | 91.50 |
FLOOR 1 STEP DOWN | 0.00 | 384.50 | 0.00 | 384.50 |
FLOOR 2 CONFERENCE | 0.00 | 413.67 | 0.00 | 413.67 |
FLOOR 2 DICTATION | 4.00 | 155.00 | 4.00 | 155.00 |
FLOOR 2 EXAM 1 | 7.33 | 307.17 | 7.33 | 307.17 |
FLOOR 2 EXAM 2 | 0.00 | 327.67 | 0.00 | 327.67 |
FLOOR 2 EXAM 3 | 0.00 | 293.83 | 0.00 | 293.83 |
FLOOR 2 EXAM 4 | 7.17 | 328.17 | 7.17 | 328.17 |
FLOOR 2 EXAM 5 | 0.17 | 305.83 | 0.17 | 305.83 |
FLOOR 2 EXAM 6 | 0.00 | 315.00 | 0.00 | 315.00 |
FLOOR 2 EXAM 7 | 0.00 | 286.50 | 0.00 | 286.50 |
FLOOR 2 EXAM 8 | 0.00 | 318.17 | 0.00 | 318.17 |
FLOOR 2 EXAM 9 | 0.00 | 324.33 | 0.00 | 324.33 |
FLOOR 2 LOUNGE | 0.00 | 344.17 | 0.00 | 344.17 |
FLOOR 2 NURSE STATION 1 | 0.00 | 408.50 | 0.00 | 408.50 |
FLOOR 2 NURSE STATION 2 | 0.00 | 422.33 | 0.00 | 422.33 |
FLOOR 2 OFFICE | 3.17 | 314.50 | 3.17 | 314.50 |
FLOOR 2 RECEPTION | 0.17 | 416.50 | 0.17 | 416.50 |
FLOOR 2 SCHEDULING 1 | 0.00 | 323.83 | 0.00 | 323.83 |
FLOOR 2 SCHEDULING 2 | 0.17 | 321.50 | 0.17 | 321.50 |
FLOOR 2 WORK | 0.67 | 397.00 | 0.67 | 397.00 |
FLOOR 2 X-RAY | 0.00 | 742.67 | 0.00 | 742.67 |
FLOOR 3 DRESSING ROOM | 5.83 | 280.33 | 5.83 | 280.33 |
FLOOR 3 HUMID | 5.00 | 308.83 | 5.00 | 308.83 |
FLOOR 3 LOCKER | 0.00 | 400.00 | 0.00 | 400.00 |
FLOOR 3 LOUNGE | 0.00 | 460.33 | 0.00 | 460.33 |
FLOOR 3 OFFICE | 6.67 | 443.83 | 6.67 | 443.83 |
FLOOR 3 PHYSICAL THERAPY 1 | 3.67 | 427.67 | 3.67 | 427.67 |
FLOOR 3 PHYSICAL THERAPY 2 | 0.00 | 336.83 | 0.00 | 336.83 |
FLOOR 3 TREATMENT | 0.00 | 339.50 | 0.00 | 339.50 |
FLOOR 3 WORK | 11.67 | 407.00 | 11.67 | 407.00 |
FLOOR 1 BIO HAZ | 0.67 | 226.83 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 443.33 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.50 | 475.50 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 228.67 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 369.83 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 5.17 | 316.17 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 264.50 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 350.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 303.17 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 10.17 | 70.33 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 234.50 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 227.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 10.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 279.33 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 17.17 | 222.67 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 246.17 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.17 | 296.17 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.33 | 327.83 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 230.83 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 332.17 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 368.83 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 387.67 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.33 | 279.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 327.50 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 764.00 | 2179.33 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 5.00 | 1.33 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 6.33 | 237.17 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 6.33 | 192.50 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 9.83 | 150.50 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 6.17 | 195.50 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 5.67 | 215.50 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 5.83 | 206.83 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 1.67 | 208.17 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 5.00 | 215.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 2.33 | 208.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 3856.83 | 0.50 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 11.83 | 50.50 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 6.33 | 148.83 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 5.33 | 168.83 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 14.00 | 242.33 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 1.00 | 259.67 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 13.00 | 81.67 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 16.33 | 422.50 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 18.33 | 310.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 17.50 | 192.33 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 24.33 | 468.83 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 12.33 | 344.33 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 10.83 | 421.33 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 24.17 | 138.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 6.33 | 40.83 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 197.83 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 14.33 | 302.50 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 8.17 | 424.17 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 8.67 | 440.17 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 24.67 | 221.33 | 0.00 | 0.00 |
NE STAIR | 26.33 | 385.67 | 0.00 | 0.00 |
NW ELEVATOR | 23.17 | 287.17 | 0.00 | 0.00 |
NW STAIR | 24.17 | 366.83 | 0.00 | 0.00 |
SW STAIR | 22.00 | 358.83 | 0.00 | 0.00 |
Facility | 3860.17 | 3036.50 | 14.17 | 2203.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2015-09-13 14:22:44
AirTerminal:SingleDuct:VAV:ReheatMaximum Air Flow Rate [m3/s] | Maximum Reheat Water Flow Rate [m3/s] | Reheat Coil Sizing Air Volume Flow Rate [m3/s] | |
FLOOR 1 ANESTHESIA VAV BOX COMPONENT | 0.067956 | 0.000041 | 0.067956 |
FLOOR 1 BIO HAZ VAV BOX COMPONENT | 0.011268 | 0.000002 | 0.003380 |
FLOOR 1 CAFE VAV BOX COMPONENT | 0.347081 | 0.000062 | 0.104124 |
FLOOR 1 CLEAN VAV BOX COMPONENT | 0.043874 | 0.000026 | 0.043874 |
FLOOR 1 CLEAN WORK VAV BOX COMPONENT | 0.055031 | 0.000033 | 0.055031 |
FLOOR 1 DICTATION VAV BOX COMPONENT | 0.027588 | 0.000005 | 0.008277 |
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT | 0.033754 | 0.000006 | 0.010126 |
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT | 0.055247 | 0.000010 | 0.016574 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT | 0.307060 | 0.000055 | 0.092118 |
FLOOR 1 HUMID VAV BOX COMPONENT | 0.013734 | 0.000002 | 0.004120 |
FLOOR 1 IT HALL VAV BOX COMPONENT | 0.024438 | 0.000004 | 0.007331 |
FLOOR 1 IT ROOM VAV BOX COMPONENT | 0.024653 | 0.000004 | 0.007396 |
FLOOR 1 LOBBY VAV BOX COMPONENT | 0.339131 | 0.000061 | 0.101739 |
FLOOR 1 LOBBY HALL VAV BOX COMPONENT | 0.046464 | 0.000008 | 0.013939 |
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT | 0.281722 | 0.000051 | 0.084517 |
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT | 0.070600 | 0.000013 | 0.021180 |
FLOOR 1 LOUNGE VAV BOX COMPONENT | 0.122937 | 0.000022 | 0.036881 |
FLOOR 1 MED GAS VAV BOX COMPONENT | 0.033575 | 0.000008 | 0.013948 |
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT | 0.147927 | 0.000027 | 0.044378 |
FLOOR 1 MRI HALL VAV BOX COMPONENT | 0.031476 | 0.000006 | 0.009443 |
FLOOR 1 MRI ROOM VAV BOX COMPONENT | 0.346652 | 0.000062 | 0.103996 |
FLOOR 1 MRI TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 NOURISHMENT VAV BOX COMPONENT | 0.061113 | 0.000011 | 0.018334 |
FLOOR 1 NURSE HALL VAV BOX COMPONENT | 0.085892 | 0.000015 | 0.025768 |
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT | 0.010167 | 0.000002 | 0.003050 |
FLOOR 1 NURSE STATION VAV BOX COMPONENT | 0.083234 | 0.000015 | 0.024970 |
FLOOR 1 NURSE TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 OFFICE VAV BOX COMPONENT | 0.093683 | 0.000017 | 0.028105 |
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT | 0.906704 | 0.000544 | 0.906704 |
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT | 0.911680 | 0.000547 | 0.911680 |
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT | 0.748776 | 0.000449 | 0.748776 |
FLOOR 1 PACU VAV BOX COMPONENT | 0.050967 | 0.000031 | 0.050967 |
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT | 0.085750 | 0.000015 | 0.025725 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT | 0.089192 | 0.000054 | 0.089192 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT | 0.159508 | 0.000096 | 0.159508 |
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT | 0.042473 | 0.000025 | 0.042473 |
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT | 0.336241 | 0.000202 | 0.336241 |
FLOOR 1 RECEPTION VAV BOX COMPONENT | 0.206768 | 0.000037 | 0.062030 |
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT | 0.022178 | 0.000004 | 0.006653 |
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT | 0.318229 | 0.000191 | 0.318229 |
FLOOR 1 SCHEDULING VAV BOX COMPONENT | 0.038075 | 0.000007 | 0.011422 |
FLOOR 1 SCRUB VAV BOX COMPONENT | 0.015072 | 0.000003 | 0.004522 |
FLOOR 1 SOIL VAV BOX COMPONENT | 0.099103 | 0.000059 | 0.099103 |
FLOOR 1 SOIL HOLD VAV BOX COMPONENT | 0.044046 | 0.000026 | 0.044046 |
FLOOR 1 SOIL WORK VAV BOX COMPONENT | 0.141575 | 0.000085 | 0.141575 |
FLOOR 1 STEP DOWN VAV BOX COMPONENT | 0.228196 | 0.000137 | 0.228196 |
FLOOR 1 STERILE HALL VAV BOX COMPONENT | 0.093782 | 0.000017 | 0.028135 |
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT | 0.049658 | 0.000009 | 0.014897 |
FLOOR 1 STORAGE VAV BOX COMPONENT | 0.314631 | 0.000061 | 0.101430 |
FLOOR 1 SUB-STERILE VAV BOX COMPONENT | 0.080462 | 0.000014 | 0.024139 |
FLOOR 1 UTILITY HALL VAV BOX COMPONENT | 0.101488 | 0.000018 | 0.030446 |
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT | 0.008796 | 0.000002 | 0.002639 |
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT | 0.114416 | 0.000021 | 0.034325 |
FLOOR 1 VESTIBULE VAV BOX COMPONENT | 0.045688 | 0.000008 | 0.013707 |
FLOOR 2 CONFERENCE VAV BOX COMPONENT | 0.330009 | ||
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT | 0.050338 | ||
FLOOR 2 DICTATION VAV BOX COMPONENT | 0.024090 | ||
FLOOR 2 EXAM 1 VAV BOX COMPONENT | 0.352899 | ||
FLOOR 2 EXAM 2 VAV BOX COMPONENT | 0.257132 | ||
FLOOR 2 EXAM 3 VAV BOX COMPONENT | 0.350368 | ||
FLOOR 2 EXAM 4 VAV BOX COMPONENT | 0.067050 | ||
FLOOR 2 EXAM 5 VAV BOX COMPONENT | 0.270818 | ||
FLOOR 2 EXAM 6 VAV BOX COMPONENT | 0.141691 | ||
FLOOR 2 EXAM 7 VAV BOX COMPONENT | 0.373759 | ||
FLOOR 2 EXAM 8 VAV BOX COMPONENT | 0.173329 | ||
FLOOR 2 EXAM 9 VAV BOX COMPONENT | 0.190444 | ||
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT | 0.060387 | ||
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT | 0.058331 | ||
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT | 0.056837 | ||
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT | 0.058739 | ||
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT | 0.061719 | ||
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT | 0.062042 | ||
FLOOR 2 JANITOR VAV BOX COMPONENT | 0.061361 | ||
FLOOR 2 LOUNGE VAV BOX COMPONENT | 0.037570 | ||
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT | 0.063059 | ||
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT | 0.077110 | ||
FLOOR 2 OFFICE VAV BOX COMPONENT | 0.357549 | ||
FLOOR 2 OFFICE HALL VAV BOX COMPONENT | 0.124933 | ||
FLOOR 2 RECEPTION VAV BOX COMPONENT | 0.686958 | ||
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT | 0.171339 | ||
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT | 0.099103 | ||
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT | 0.089535 | ||
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT | 0.095541 | ||
FLOOR 2 STORAGE 1 VAV BOX COMPONENT | 0.017645 | ||
FLOOR 2 STORAGE 2 VAV BOX COMPONENT | 0.031635 | ||
FLOOR 2 STORAGE 3 VAV BOX COMPONENT | 0.040353 | ||
FLOOR 2 UTILITY VAV BOX COMPONENT | 0.077991 | ||
FLOOR 2 WORK VAV BOX COMPONENT | 0.508893 | ||
FLOOR 2 WORK HALL VAV BOX COMPONENT | 0.239101 | ||
FLOOR 2 WORK TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 2 X-RAY VAV BOX COMPONENT | 0.843233 | ||
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT | 0.022753 | ||
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT | 0.119208 | ||
FLOOR 3 HUMID VAV BOX COMPONENT | 0.056631 | ||
FLOOR 3 JANITOR VAV BOX COMPONENT | 0.042930 | ||
FLOOR 3 LOCKER VAV BOX COMPONENT | 0.084382 | ||
FLOOR 3 LOUNGE VAV BOX COMPONENT | 0.492383 | ||
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT | 0.151014 | ||
FLOOR 3 MECHANICAL VAV BOX COMPONENT | 0.395382 | ||
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT | 0.138971 | ||
FLOOR 3 OFFICE VAV BOX COMPONENT | 1.34 | ||
FLOOR 3 OFFICE HALL VAV BOX COMPONENT | 0.294207 | ||
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT | 1.00 | ||
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT | 0.342038 | ||
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT | 0.066069 | ||
FLOOR 3 STORAGE 1 VAV BOX COMPONENT | 0.041097 | ||
FLOOR 3 STORAGE 2 VAV BOX COMPONENT | 0.035821 | ||
FLOOR 3 TREATMENT VAV BOX COMPONENT | 0.282856 | ||
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT | 1.14 | ||
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT | 0.612784 | ||
FLOOR 3 UTILITY VAV BOX COMPONENT | 0.071690 | ||
FLOOR 3 WORK VAV BOX COMPONENT | 0.410678 | ||
NE STAIR VAV BOX COMPONENT | 0.330236 | ||
NW ELEVATOR VAV BOX COMPONENT | 0.205427 | ||
NW STAIR VAV BOX COMPONENT | 0.376285 | ||
SW STAIR VAV BOX COMPONENT | 0.154606 |
Design Coil Load [W] | Maximum Water Flow Rate [m3/s] | U-Factor Times Area Value [W/K] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | 1893.38 | 0.000041 | 40.82 |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | 94.18 | 0.000002 | 6.77 |
FLOOR 1 CAFE VAV BOX REHEAT COIL | 2901.09 | 0.000062 | 208.50 |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | 1222.40 | 0.000026 | 26.36 |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | 1533.25 | 0.000033 | 33.06 |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | 230.60 | 0.000005 | 16.57 |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | 282.13 | 0.000006 | 20.28 |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | 461.78 | 0.000010 | 33.19 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | 2566.57 | 0.000055 | 184.46 |
FLOOR 1 HUMID VAV BOX REHEAT COIL | 114.79 | 0.000002 | 8.25 |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | 204.26 | 0.000004 | 14.68 |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | 206.06 | 0.000004 | 14.81 |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | 2834.64 | 0.000061 | 203.73 |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | 388.37 | 0.000008 | 27.91 |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | 1183.36 | 0.000025 | 25.51 |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | 2354.78 | 0.000051 | 169.24 |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | 590.11 | 0.000013 | 42.41 |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | 1027.57 | 0.000022 | 73.85 |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | 388.62 | 0.000008 | 20.17 |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | 1236.45 | 0.000027 | 88.86 |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | 263.09 | 0.000006 | 18.91 |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | 2897.50 | 0.000062 | 208.25 |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | 1183.36 | 0.000025 | 25.51 |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | 510.81 | 0.000011 | 36.71 |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | 717.93 | 0.000015 | 51.60 |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | 84.98 | 0.000002 | 6.11 |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | 695.72 | 0.000015 | 50.00 |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | 1183.36 | 0.000025 | 25.51 |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | 783.05 | 0.000017 | 56.28 |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | 25262.37 | 0.000544 | 544.69 |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | 25401.01 | 0.000547 | 547.68 |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | 20862.23 | 0.000449 | 449.82 |
FLOOR 1 PACU VAV BOX REHEAT COIL | 1420.03 | 0.000031 | 30.62 |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | 716.74 | 0.000015 | 51.51 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | 2485.06 | 0.000054 | 53.58 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | 4444.18 | 0.000096 | 95.82 |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | 1183.36 | 0.000025 | 25.51 |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | 9368.28 | 0.000202 | 201.99 |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | 1728.27 | 0.000037 | 124.21 |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | 185.37 | 0.000004 | 13.32 |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | 8866.41 | 0.000191 | 191.17 |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | 318.25 | 0.000007 | 22.87 |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | 125.98 | 0.000003 | 9.05 |
FLOOR 1 SOIL VAV BOX REHEAT COIL | 2761.18 | 0.000059 | 59.53 |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | 1227.19 | 0.000026 | 26.46 |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | 3944.54 | 0.000085 | 85.05 |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | 6357.95 | 0.000137 | 137.09 |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | 783.88 | 0.000017 | 56.34 |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | 415.07 | 0.000009 | 29.83 |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | 2826.01 | 0.000061 | 189.01 |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | 672.55 | 0.000014 | 48.34 |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | 848.29 | 0.000018 | 60.97 |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | 73.52 | 0.000002 | 5.28 |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | 956.35 | 0.000021 | 68.73 |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | 381.89 | 0.000008 | 27.45 |
AHU-1_HEATC | 2744.43 | 0.000059 | 45.30 |
AHU-1_EXTRAWATERHEATC | 2744.43 | 0.000059 | 45.30 |
AHU-2_HEATC | 43664.66 | 0.000940 | 712.94 |
Nominal Capacity [W] | |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | 2712.32 |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | 1379.08 |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | 197.99 |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | 9668.20 |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | 7044.51 |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | 9598.86 |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | 1836.93 |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | 7419.46 |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | 3881.82 |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | 10239.68 |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | 4748.62 |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | 5217.50 |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | 496.31 |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | 479.42 |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | 467.14 |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | 482.77 |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | 507.27 |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | 509.92 |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | 504.33 |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | 308.79 |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | 518.28 |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | 633.77 |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | 2938.68 |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | 1026.82 |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | 5646.07 |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | 1408.23 |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | 0.000000 |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | 735.88 |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | 785.25 |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | 145.02 |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | 260.00 |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | 331.66 |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | 641.01 |
FLOOR 2 WORK VAV BOX REHEAT COIL | 4182.57 |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | 1965.16 |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | 1163.60 |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | 6930.48 |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | 187.00 |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | 979.77 |
FLOOR 3 HUMID VAV BOX REHEAT COIL | 465.44 |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | 438.77 |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | 693.53 |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | 4046.87 |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | 4137.24 |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | 0.000000 |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | 1142.19 |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | 11006.92 |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | 2418.07 |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | 1163.60 |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | 27410.57 |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | 9370.64 |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | 1810.04 |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | 1125.92 |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | 294.41 |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | 7749.26 |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | 9380.21 |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | 5036.44 |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | 589.21 |
FLOOR 3 WORK VAV BOX REHEAT COIL | 3375.34 |
NE STAIR VAV BOX REHEAT COIL | 2714.19 |
NW ELEVATOR VAV BOX REHEAT COIL | 1688.40 |
NW STAIR VAV BOX REHEAT COIL | 3092.67 |
SW STAIR VAV BOX REHEAT COIL | 1270.70 |
Maximum Flow Rate [m3/s] | |
AHU-1 AIR LOOP MAIN BRANCH | 8.15 |
AHU-2 AIR LOOP MAIN BRANCH | 14.21 |
Design Supply Air Flow Rate [m3/s] | |
AHU-1 | 8.15 |
AHU-2 | 14.21 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AHU-1_OA_CONTROLLER | 8.15 | 2.07 |
AHU-2_OA_CONTROLLER | 14.21 | 4.53 |
Rated High Speed Air Flow Rate [m3/s] | Rated High Speed Total Cooling Capacity (gross) [W] | Rated High Speed Sensible Heat Ratio | Rated Low Speed Air Flow Rate [m3/s] | Rated Low Speed Total Cooling Capacity (gross) [W] | |
AHU-1_COOLC DXCOIL | 8.15 | 169360.63 | 0.723768 | 2.72 | 56447.90 |
AHU-2_COOLC DXCOIL | 14.21 | 247220.17 | 0.780808 | 4.74 | 82398.48 |
Maximum Flow Rate [m3/s] | |
AHU-1_FAN | 8.15 |
AHU-2_FAN | 14.21 |
Maximum Actuated Flow [m3/s] | |
AHU-1_HEATC_CONTROLLER | 0.000059 |
AHU-1_EXTRAWATERHEATC_CONTROLLER | 0.000059 |
AHU-2_HEATC_CONTROLLER | 0.000940 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000063 | 0.047375 |
HEATSYS1 | 0.001310 | 0.982391 |
Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 0.001310 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000063 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SWHSYS1 PUMP | 0.000063 | 8.07 |
HEATSYS1 PUMP | 0.001310 | 334.65 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ANESTHESIA
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.83 | 14.02 |
February | 19.81 | 16.67 |
March | 19.82 | 20.28 |
April | 19.79 | 25.86 |
May | 19.94 | 32.05 |
June | 20.61 | 35.24 |
July | 20.95 | 36.21 |
August | 21.13 | 36.44 |
September | 20.41 | 33.05 |
October | 20.22 | 27.59 |
November | 20.04 | 21.57 |
December | 19.71 | 14.93 |
Annual Sum or Average | 20.19 | 26.21 |
Minimum of Months | 19.71 | 14.02 |
Maximum of Months | 21.13 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 BIO HAZ
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.32 | 14.02 |
February | 20.48 | 16.67 |
March | 20.79 | 20.28 |
April | 21.13 | 25.86 |
May | 21.61 | 32.05 |
June | 22.27 | 35.24 |
July | 22.49 | 36.21 |
August | 22.53 | 36.44 |
September | 21.85 | 33.05 |
October | 21.16 | 27.59 |
November | 20.71 | 21.57 |
December | 20.33 | 14.93 |
Annual Sum or Average | 21.31 | 26.21 |
Minimum of Months | 20.32 | 14.02 |
Maximum of Months | 22.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CAFE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | 14.02 |
February | 21.22 | 16.67 |
March | 21.44 | 20.28 |
April | 21.51 | 25.86 |
May | 21.90 | 32.05 |
June | 22.63 | 35.24 |
July | 22.92 | 36.21 |
August | 23.07 | 36.44 |
September | 22.41 | 33.05 |
October | 22.04 | 27.59 |
November | 21.66 | 21.57 |
December | 21.02 | 14.93 |
Annual Sum or Average | 21.92 | 26.21 |
Minimum of Months | 21.02 | 14.02 |
Maximum of Months | 23.07 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.36 | 14.02 |
February | 20.38 | 16.67 |
March | 20.44 | 20.28 |
April | 20.36 | 25.86 |
May | 20.44 | 32.05 |
June | 21.13 | 35.24 |
July | 21.39 | 36.21 |
August | 21.49 | 36.44 |
September | 20.71 | 33.05 |
October | 20.42 | 27.59 |
November | 20.46 | 21.57 |
December | 20.23 | 14.93 |
Annual Sum or Average | 20.65 | 26.21 |
Minimum of Months | 20.23 | 14.02 |
Maximum of Months | 21.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN WORK
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 14.02 |
February | 20.13 | 16.67 |
March | 20.19 | 20.28 |
April | 20.13 | 25.86 |
May | 20.22 | 32.05 |
June | 20.86 | 35.24 |
July | 21.10 | 36.21 |
August | 21.20 | 36.44 |
September | 20.45 | 33.05 |
October | 20.18 | 27.59 |
November | 20.19 | 21.57 |
December | 19.99 | 14.93 |
Annual Sum or Average | 20.40 | 26.21 |
Minimum of Months | 19.99 | 14.02 |
Maximum of Months | 21.20 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DICTATION
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 14.02 |
February | 21.51 | 16.67 |
March | 21.61 | 20.28 |
April | 21.55 | 25.86 |
May | 21.63 | 32.05 |
June | 22.15 | 35.24 |
July | 22.31 | 36.21 |
August | 22.45 | 36.44 |
September | 21.91 | 33.05 |
October | 21.62 | 27.59 |
November | 21.61 | 21.57 |
December | 21.45 | 14.93 |
Annual Sum or Average | 21.78 | 26.21 |
Minimum of Months | 21.45 | 14.02 |
Maximum of Months | 22.45 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DRESSING ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.84 | 14.02 |
February | 20.13 | 16.67 |
March | 20.62 | 20.28 |
April | 21.21 | 25.86 |
May | 21.96 | 32.05 |
June | 22.74 | 35.24 |
July | 23.09 | 36.21 |
August | 23.06 | 36.44 |
September | 22.13 | 33.05 |
October | 21.31 | 27.59 |
November | 20.62 | 21.57 |
December | 19.84 | 14.93 |
Annual Sum or Average | 21.39 | 26.21 |
Minimum of Months | 19.84 | 14.02 |
Maximum of Months | 23.09 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELECTRICAL ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | 14.02 |
February | 21.37 | 16.67 |
March | 21.60 | 20.28 |
April | 21.81 | 25.86 |
May | 22.17 | 32.05 |
June | 22.86 | 35.24 |
July | 23.19 | 36.21 |
August | 23.19 | 36.44 |
September | 22.44 | 33.05 |
October | 21.93 | 27.59 |
November | 21.62 | 21.57 |
December | 21.16 | 14.93 |
Annual Sum or Average | 22.05 | 26.21 |
Minimum of Months | 21.16 | 14.02 |
Maximum of Months | 23.19 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELEVATOR PUMP ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.20 | 14.02 |
February | 21.28 | 16.67 |
March | 21.48 | 20.28 |
April | 21.50 | 25.86 |
May | 21.76 | 32.05 |
June | 22.44 | 35.24 |
July | 22.70 | 36.21 |
August | 22.79 | 36.44 |
September | 21.90 | 33.05 |
October | 21.55 | 27.59 |
November | 21.44 | 21.57 |
December | 21.06 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.06 | 14.02 |
Maximum of Months | 22.79 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 HUMID
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.02 |
February | 21.77 | 16.67 |
March | 21.86 | 20.28 |
April | 21.82 | 25.86 |
May | 21.89 | 32.05 |
June | 22.41 | 35.24 |
July | 22.59 | 36.21 |
August | 22.70 | 36.44 |
September | 22.19 | 33.05 |
October | 21.88 | 27.59 |
November | 21.87 | 21.57 |
December | 21.71 | 14.93 |
Annual Sum or Average | 22.04 | 26.21 |
Minimum of Months | 21.71 | 14.02 |
Maximum of Months | 22.70 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | 14.02 |
February | 20.89 | 16.67 |
March | 21.07 | 20.28 |
April | 21.18 | 25.86 |
May | 21.43 | 32.05 |
June | 22.01 | 35.24 |
July | 22.19 | 36.21 |
August | 22.29 | 36.44 |
September | 21.70 | 33.05 |
October | 21.24 | 27.59 |
November | 21.05 | 21.57 |
December | 20.78 | 14.93 |
Annual Sum or Average | 21.39 | 26.21 |
Minimum of Months | 20.78 | 14.02 |
Maximum of Months | 22.29 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 14.02 |
February | 21.19 | 16.67 |
March | 21.43 | 20.28 |
April | 21.57 | 25.86 |
May | 21.88 | 32.05 |
June | 22.49 | 35.24 |
July | 22.68 | 36.21 |
August | 22.75 | 36.44 |
September | 22.12 | 33.05 |
October | 21.61 | 27.59 |
November | 21.36 | 21.57 |
December | 21.05 | 14.93 |
Annual Sum or Average | 21.77 | 26.21 |
Minimum of Months | 21.05 | 14.02 |
Maximum of Months | 22.75 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | 14.02 |
February | 21.12 | 16.67 |
March | 21.45 | 20.28 |
April | 21.70 | 25.86 |
May | 22.26 | 32.05 |
June | 22.94 | 35.24 |
July | 23.20 | 36.21 |
August | 23.25 | 36.44 |
September | 22.53 | 33.05 |
October | 21.93 | 27.59 |
November | 21.44 | 21.57 |
December | 20.81 | 14.93 |
Annual Sum or Average | 21.96 | 26.21 |
Minimum of Months | 20.81 | 14.02 |
Maximum of Months | 23.25 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | 14.02 |
February | 21.80 | 16.67 |
March | 21.97 | 20.28 |
April | 22.05 | 25.86 |
May | 22.29 | 32.05 |
June | 22.86 | 35.24 |
July | 23.10 | 36.21 |
August | 23.18 | 36.44 |
September | 22.67 | 33.05 |
October | 22.27 | 27.59 |
November | 22.05 | 21.57 |
December | 21.66 | 14.93 |
Annual Sum or Average | 22.30 | 26.21 |
Minimum of Months | 21.66 | 14.02 |
Maximum of Months | 23.18 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.72 | 14.02 |
February | 19.79 | 16.67 |
March | 19.94 | 20.28 |
April | 20.00 | 25.86 |
May | 20.27 | 32.05 |
June | 20.96 | 35.24 |
July | 21.24 | 36.21 |
August | 21.34 | 36.44 |
September | 20.40 | 33.05 |
October | 20.06 | 27.59 |
November | 19.85 | 21.57 |
December | 19.66 | 14.93 |
Annual Sum or Average | 20.27 | 26.21 |
Minimum of Months | 19.66 | 14.02 |
Maximum of Months | 21.34 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | 14.02 |
February | 21.44 | 16.67 |
March | 21.68 | 20.28 |
April | 21.84 | 25.86 |
May | 22.17 | 32.05 |
June | 22.86 | 35.24 |
July | 23.14 | 36.21 |
August | 23.14 | 36.44 |
September | 22.42 | 33.05 |
October | 21.91 | 27.59 |
November | 21.69 | 21.57 |
December | 21.28 | 14.93 |
Annual Sum or Average | 22.08 | 26.21 |
Minimum of Months | 21.28 | 14.02 |
Maximum of Months | 23.14 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.35 | 14.02 |
February | 21.43 | 16.67 |
March | 21.57 | 20.28 |
April | 21.59 | 25.86 |
May | 21.75 | 32.05 |
June | 22.28 | 35.24 |
July | 22.43 | 36.21 |
August | 22.53 | 36.44 |
September | 22.08 | 33.05 |
October | 21.70 | 27.59 |
November | 21.59 | 21.57 |
December | 21.34 | 14.93 |
Annual Sum or Average | 21.81 | 26.21 |
Minimum of Months | 21.34 | 14.02 |
Maximum of Months | 22.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOUNGE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 14.02 |
February | 21.68 | 16.67 |
March | 21.84 | 20.28 |
April | 21.90 | 25.86 |
May | 22.09 | 32.05 |
June | 22.74 | 35.24 |
July | 22.98 | 36.21 |
August | 23.04 | 36.44 |
September | 22.37 | 33.05 |
October | 21.95 | 27.59 |
November | 21.83 | 21.57 |
December | 21.58 | 14.93 |
Annual Sum or Average | 22.14 | 26.21 |
Minimum of Months | 21.58 | 14.02 |
Maximum of Months | 23.04 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MED GAS
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 14.02 |
February | 19.89 | 16.67 |
March | 20.45 | 20.28 |
April | 21.21 | 25.86 |
May | 22.20 | 32.05 |
June | 23.05 | 35.24 |
July | 23.37 | 36.21 |
August | 23.34 | 36.44 |
September | 22.37 | 33.05 |
October | 21.33 | 27.59 |
November | 20.20 | 21.57 |
December | 19.63 | 14.93 |
Annual Sum or Average | 21.40 | 26.21 |
Minimum of Months | 19.63 | 14.02 |
Maximum of Months | 23.37 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI CONTROL ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 14.02 |
February | 22.15 | 16.67 |
March | 22.34 | 20.28 |
April | 22.57 | 25.86 |
May | 22.91 | 32.05 |
June | 23.57 | 35.24 |
July | 23.91 | 36.21 |
August | 23.85 | 36.44 |
September | 23.12 | 33.05 |
October | 22.67 | 27.59 |
November | 22.40 | 21.57 |
December | 21.96 | 14.93 |
Annual Sum or Average | 22.79 | 26.21 |
Minimum of Months | 21.96 | 14.02 |
Maximum of Months | 23.91 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | 14.02 |
February | 21.40 | 16.67 |
March | 21.61 | 20.28 |
April | 21.74 | 25.86 |
May | 22.01 | 32.05 |
June | 22.56 | 35.24 |
July | 22.79 | 36.21 |
August | 22.85 | 36.44 |
September | 22.29 | 33.05 |
October | 21.86 | 27.59 |
November | 21.63 | 21.57 |
December | 21.25 | 14.93 |
Annual Sum or Average | 21.94 | 26.21 |
Minimum of Months | 21.25 | 14.02 |
Maximum of Months | 22.85 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 14.02 |
February | 22.62 | 16.67 |
March | 22.68 | 20.28 |
April | 22.77 | 25.86 |
May | 22.92 | 32.05 |
June | 23.57 | 35.24 |
July | 23.92 | 36.21 |
August | 23.86 | 36.44 |
September | 23.19 | 33.05 |
October | 22.88 | 27.59 |
November | 22.80 | 21.57 |
December | 22.44 | 14.93 |
Annual Sum or Average | 23.02 | 26.21 |
Minimum of Months | 22.44 | 14.02 |
Maximum of Months | 23.92 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | 14.02 |
February | 19.51 | 16.67 |
March | 19.60 | 20.28 |
April | 19.56 | 25.86 |
May | 19.66 | 32.05 |
June | 20.03 | 35.24 |
July | 20.22 | 36.21 |
August | 20.29 | 36.44 |
September | 19.69 | 33.05 |
October | 19.54 | 27.59 |
November | 19.51 | 21.57 |
December | 19.47 | 14.93 |
Annual Sum or Average | 19.72 | 26.21 |
Minimum of Months | 19.47 | 14.02 |
Maximum of Months | 20.29 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NOURISHMENT
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 14.02 |
February | 21.68 | 16.67 |
March | 21.78 | 20.28 |
April | 21.72 | 25.86 |
May | 21.80 | 32.05 |
June | 22.38 | 35.24 |
July | 22.59 | 36.21 |
August | 22.71 | 36.44 |
September | 22.09 | 33.05 |
October | 21.78 | 27.59 |
November | 21.78 | 21.57 |
December | 21.61 | 14.93 |
Annual Sum or Average | 21.97 | 26.21 |
Minimum of Months | 21.61 | 14.02 |
Maximum of Months | 22.71 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | 14.02 |
February | 21.12 | 16.67 |
March | 21.21 | 20.28 |
April | 21.20 | 25.86 |
May | 21.36 | 32.05 |
June | 21.92 | 35.24 |
July | 22.11 | 36.21 |
August | 22.29 | 36.44 |
September | 21.79 | 33.05 |
October | 21.46 | 27.59 |
November | 21.33 | 21.57 |
December | 21.01 | 14.93 |
Annual Sum or Average | 21.49 | 26.21 |
Minimum of Months | 21.01 | 14.02 |
Maximum of Months | 22.29 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE JANITOR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | 14.02 |
February | 21.62 | 16.67 |
March | 21.72 | 20.28 |
April | 21.70 | 25.86 |
May | 21.80 | 32.05 |
June | 22.30 | 35.24 |
July | 22.46 | 36.21 |
August | 22.56 | 36.44 |
September | 22.14 | 33.05 |
October | 21.80 | 27.59 |
November | 21.75 | 21.57 |
December | 21.55 | 14.93 |
Annual Sum or Average | 21.91 | 26.21 |
Minimum of Months | 21.55 | 14.02 |
Maximum of Months | 22.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE STATION
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 14.02 |
February | 21.54 | 16.67 |
March | 21.65 | 20.28 |
April | 21.59 | 25.86 |
May | 21.69 | 32.05 |
June | 22.28 | 35.24 |
July | 22.48 | 36.21 |
August | 22.63 | 36.44 |
September | 22.02 | 33.05 |
October | 21.71 | 27.59 |
November | 21.67 | 21.57 |
December | 21.45 | 14.93 |
Annual Sum or Average | 21.85 | 26.21 |
Minimum of Months | 21.45 | 14.02 |
Maximum of Months | 22.63 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | 14.02 |
February | 19.51 | 16.67 |
March | 19.59 | 20.28 |
April | 19.52 | 25.86 |
May | 19.56 | 32.05 |
June | 19.72 | 35.24 |
July | 19.75 | 36.21 |
August | 19.86 | 36.44 |
September | 19.55 | 33.05 |
October | 19.50 | 27.59 |
November | 19.49 | 21.57 |
December | 19.48 | 14.93 |
Annual Sum or Average | 19.58 | 26.21 |
Minimum of Months | 19.48 | 14.02 |
Maximum of Months | 19.86 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OFFICE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 14.02 |
February | 21.67 | 16.67 |
March | 21.82 | 20.28 |
April | 21.85 | 25.86 |
May | 22.01 | 32.05 |
June | 22.56 | 35.24 |
July | 22.77 | 36.21 |
August | 22.87 | 36.44 |
September | 22.33 | 33.05 |
October | 21.96 | 27.59 |
November | 21.84 | 21.57 |
December | 21.58 | 14.93 |
Annual Sum or Average | 22.07 | 26.21 |
Minimum of Months | 21.58 | 14.02 |
Maximum of Months | 22.87 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.41 | 14.02 |
February | 18.40 | 16.67 |
March | 18.39 | 20.28 |
April | 18.44 | 25.86 |
May | 18.52 | 32.05 |
June | 19.04 | 35.24 |
July | 19.39 | 36.21 |
August | 19.40 | 36.44 |
September | 18.68 | 33.05 |
October | 18.49 | 27.59 |
November | 18.43 | 21.57 |
December | 18.36 | 14.93 |
Annual Sum or Average | 18.67 | 26.21 |
Minimum of Months | 18.36 | 14.02 |
Maximum of Months | 19.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.35 | 14.02 |
February | 18.35 | 16.67 |
March | 18.37 | 20.28 |
April | 18.44 | 25.86 |
May | 18.52 | 32.05 |
June | 19.02 | 35.24 |
July | 19.35 | 36.21 |
August | 19.35 | 36.44 |
September | 18.62 | 33.05 |
October | 18.43 | 27.59 |
November | 18.37 | 21.57 |
December | 18.33 | 14.93 |
Annual Sum or Average | 18.63 | 26.21 |
Minimum of Months | 18.33 | 14.02 |
Maximum of Months | 19.35 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 3
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.47 | 14.02 |
February | 18.47 | 16.67 |
March | 18.44 | 20.28 |
April | 18.46 | 25.86 |
May | 18.53 | 32.05 |
June | 19.00 | 35.24 |
July | 19.29 | 36.21 |
August | 19.31 | 36.44 |
September | 18.62 | 33.05 |
October | 18.47 | 27.59 |
November | 18.46 | 21.57 |
December | 18.40 | 14.93 |
Annual Sum or Average | 18.66 | 26.21 |
Minimum of Months | 18.40 | 14.02 |
Maximum of Months | 19.31 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PACU
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.82 | 14.02 |
February | 19.84 | 16.67 |
March | 19.90 | 20.28 |
April | 19.84 | 25.86 |
May | 19.94 | 32.05 |
June | 20.50 | 35.24 |
July | 20.70 | 36.21 |
August | 20.85 | 36.44 |
September | 20.10 | 33.05 |
October | 19.88 | 27.59 |
November | 19.88 | 21.57 |
December | 19.75 | 14.93 |
Annual Sum or Average | 20.08 | 26.21 |
Minimum of Months | 19.75 | 14.02 |
Maximum of Months | 20.85 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | 14.02 |
February | 21.20 | 16.67 |
March | 21.37 | 20.28 |
April | 21.43 | 25.86 |
May | 21.66 | 32.05 |
June | 22.23 | 35.24 |
July | 22.41 | 36.21 |
August | 22.54 | 36.44 |
September | 22.01 | 33.05 |
October | 21.59 | 27.59 |
November | 21.42 | 21.57 |
December | 21.08 | 14.93 |
Annual Sum or Average | 21.67 | 26.21 |
Minimum of Months | 21.08 | 14.02 |
Maximum of Months | 22.54 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | 14.02 |
February | 19.68 | 16.67 |
March | 19.79 | 20.28 |
April | 19.78 | 25.86 |
May | 19.93 | 32.05 |
June | 20.52 | 35.24 |
July | 20.77 | 36.21 |
August | 20.91 | 36.44 |
September | 20.12 | 33.05 |
October | 19.84 | 27.59 |
November | 19.74 | 21.57 |
December | 19.59 | 14.93 |
Annual Sum or Average | 20.03 | 26.21 |
Minimum of Months | 19.59 | 14.02 |
Maximum of Months | 20.91 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | 14.02 |
February | 19.70 | 16.67 |
March | 19.77 | 20.28 |
April | 19.70 | 25.86 |
May | 19.79 | 32.05 |
June | 20.23 | 35.24 |
July | 20.41 | 36.21 |
August | 20.55 | 36.44 |
September | 19.88 | 33.05 |
October | 19.71 | 27.59 |
November | 19.72 | 21.57 |
December | 19.63 | 14.93 |
Annual Sum or Average | 19.90 | 26.21 |
Minimum of Months | 19.63 | 14.02 |
Maximum of Months | 20.55 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | 14.02 |
February | 19.53 | 16.67 |
March | 19.64 | 20.28 |
April | 19.64 | 25.86 |
May | 19.82 | 32.05 |
June | 20.36 | 35.24 |
July | 20.58 | 36.21 |
August | 20.76 | 36.44 |
September | 19.95 | 33.05 |
October | 19.68 | 27.59 |
November | 19.54 | 21.57 |
December | 19.48 | 14.93 |
Annual Sum or Average | 19.88 | 26.21 |
Minimum of Months | 19.48 | 14.02 |
Maximum of Months | 20.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PROCEDURE ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | 14.02 |
February | 19.51 | 16.67 |
March | 19.59 | 20.28 |
April | 19.53 | 25.86 |
May | 19.60 | 32.05 |
June | 19.94 | 35.24 |
July | 20.08 | 36.21 |
August | 20.19 | 36.44 |
September | 19.62 | 33.05 |
October | 19.50 | 27.59 |
November | 19.49 | 21.57 |
December | 19.48 | 14.93 |
Annual Sum or Average | 19.67 | 26.21 |
Minimum of Months | 19.48 | 14.02 |
Maximum of Months | 20.19 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.46 | 14.02 |
February | 21.57 | 16.67 |
March | 21.76 | 20.28 |
April | 21.84 | 25.86 |
May | 22.13 | 32.05 |
June | 22.79 | 35.24 |
July | 23.06 | 36.21 |
August | 23.17 | 36.44 |
September | 22.57 | 33.05 |
October | 22.16 | 27.59 |
November | 21.89 | 21.57 |
December | 21.41 | 14.93 |
Annual Sum or Average | 22.15 | 26.21 |
Minimum of Months | 21.41 | 14.02 |
Maximum of Months | 23.17 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 14.02 |
February | 21.33 | 16.67 |
March | 21.47 | 20.28 |
April | 21.51 | 25.86 |
May | 21.71 | 32.05 |
June | 22.25 | 35.24 |
July | 22.43 | 36.21 |
August | 22.55 | 36.44 |
September | 22.08 | 33.05 |
October | 21.69 | 27.59 |
November | 21.54 | 21.57 |
December | 21.22 | 14.93 |
Annual Sum or Average | 21.75 | 26.21 |
Minimum of Months | 21.22 | 14.02 |
Maximum of Months | 22.55 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECOVERY ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.80 | 14.02 |
February | 19.78 | 16.67 |
March | 19.80 | 20.28 |
April | 19.77 | 25.86 |
May | 19.91 | 32.05 |
June | 20.57 | 35.24 |
July | 20.91 | 36.21 |
August | 21.10 | 36.44 |
September | 20.36 | 33.05 |
October | 20.16 | 27.59 |
November | 20.00 | 21.57 |
December | 19.69 | 14.93 |
Annual Sum or Average | 20.16 | 26.21 |
Minimum of Months | 19.69 | 14.02 |
Maximum of Months | 21.10 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCHEDULING
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.05 | 14.02 |
February | 21.18 | 16.67 |
March | 21.38 | 20.28 |
April | 21.48 | 25.86 |
May | 21.83 | 32.05 |
June | 22.47 | 35.24 |
July | 22.74 | 36.21 |
August | 22.86 | 36.44 |
September | 22.24 | 33.05 |
October | 21.79 | 27.59 |
November | 21.50 | 21.57 |
December | 21.01 | 14.93 |
Annual Sum or Average | 21.80 | 26.21 |
Minimum of Months | 21.01 | 14.02 |
Maximum of Months | 22.86 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCRUB
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | 14.02 |
February | 21.08 | 16.67 |
March | 21.28 | 20.28 |
April | 21.45 | 25.86 |
May | 21.76 | 32.05 |
June | 22.34 | 35.24 |
July | 22.58 | 36.21 |
August | 22.67 | 36.44 |
September | 22.10 | 33.05 |
October | 21.64 | 27.59 |
November | 21.34 | 21.57 |
December | 20.86 | 14.93 |
Annual Sum or Average | 21.67 | 26.21 |
Minimum of Months | 20.86 | 14.02 |
Maximum of Months | 22.67 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | 14.02 |
February | 19.54 | 16.67 |
March | 19.61 | 20.28 |
April | 19.55 | 25.86 |
May | 19.60 | 32.05 |
June | 19.86 | 35.24 |
July | 19.96 | 36.21 |
August | 20.10 | 36.44 |
September | 19.61 | 33.05 |
October | 19.53 | 27.59 |
November | 19.53 | 21.57 |
December | 19.50 | 14.93 |
Annual Sum or Average | 19.66 | 26.21 |
Minimum of Months | 19.50 | 14.02 |
Maximum of Months | 20.10 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL HOLD
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | 14.02 |
February | 19.54 | 16.67 |
March | 19.63 | 20.28 |
April | 19.59 | 25.86 |
May | 19.69 | 32.05 |
June | 20.09 | 35.24 |
July | 20.25 | 36.21 |
August | 20.37 | 36.44 |
September | 19.73 | 33.05 |
October | 19.57 | 27.59 |
November | 19.54 | 21.57 |
December | 19.49 | 14.93 |
Annual Sum or Average | 19.75 | 26.21 |
Minimum of Months | 19.49 | 14.02 |
Maximum of Months | 20.37 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL WORK
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | 14.02 |
February | 19.52 | 16.67 |
March | 19.60 | 20.28 |
April | 19.53 | 25.86 |
May | 19.58 | 32.05 |
June | 19.81 | 35.24 |
July | 19.89 | 36.21 |
August | 20.03 | 36.44 |
September | 19.59 | 33.05 |
October | 19.51 | 27.59 |
November | 19.51 | 21.57 |
December | 19.48 | 14.93 |
Annual Sum or Average | 19.63 | 26.21 |
Minimum of Months | 19.48 | 14.02 |
Maximum of Months | 20.03 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STEP DOWN
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | 14.02 |
February | 19.63 | 16.67 |
March | 19.71 | 20.28 |
April | 19.71 | 25.86 |
May | 19.88 | 32.05 |
June | 20.54 | 35.24 |
July | 20.86 | 36.21 |
August | 21.02 | 36.44 |
September | 20.20 | 33.05 |
October | 19.94 | 27.59 |
November | 19.73 | 21.57 |
December | 19.56 | 14.93 |
Annual Sum or Average | 20.04 | 26.21 |
Minimum of Months | 19.56 | 14.02 |
Maximum of Months | 21.02 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 14.02 |
February | 21.26 | 16.67 |
March | 21.39 | 20.28 |
April | 21.48 | 25.86 |
May | 21.74 | 32.05 |
June | 22.32 | 35.24 |
July | 22.55 | 36.21 |
August | 22.68 | 36.44 |
September | 22.15 | 33.05 |
October | 21.73 | 27.59 |
November | 21.51 | 21.57 |
December | 21.11 | 14.93 |
Annual Sum or Average | 21.76 | 26.21 |
Minimum of Months | 21.11 | 14.02 |
Maximum of Months | 22.68 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE STORAGE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.46 | 14.02 |
February | 21.52 | 16.67 |
March | 21.62 | 20.28 |
April | 21.61 | 25.86 |
May | 21.73 | 32.05 |
June | 22.24 | 35.24 |
July | 22.39 | 36.21 |
August | 22.49 | 36.44 |
September | 22.09 | 33.05 |
October | 21.73 | 27.59 |
November | 21.66 | 21.57 |
December | 21.45 | 14.93 |
Annual Sum or Average | 21.84 | 26.21 |
Minimum of Months | 21.45 | 14.02 |
Maximum of Months | 22.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STORAGE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.66 | 14.02 |
February | 19.87 | 16.67 |
March | 20.44 | 20.28 |
April | 21.15 | 25.86 |
May | 22.06 | 32.05 |
June | 22.92 | 35.24 |
July | 23.22 | 36.21 |
August | 23.17 | 36.44 |
September | 22.21 | 33.05 |
October | 21.13 | 27.59 |
November | 20.19 | 21.57 |
December | 19.66 | 14.93 |
Annual Sum or Average | 21.32 | 26.21 |
Minimum of Months | 19.66 | 14.02 |
Maximum of Months | 23.22 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SUB-STERILE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.18 | 14.02 |
February | 20.45 | 16.67 |
March | 20.84 | 20.28 |
April | 21.26 | 25.86 |
May | 21.79 | 32.05 |
June | 22.48 | 35.24 |
July | 22.86 | 36.21 |
August | 22.85 | 36.44 |
September | 22.07 | 33.05 |
October | 21.48 | 27.59 |
November | 20.88 | 21.57 |
December | 20.09 | 14.93 |
Annual Sum or Average | 21.44 | 26.21 |
Minimum of Months | 20.09 | 14.02 |
Maximum of Months | 22.86 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.80 | 14.02 |
February | 20.02 | 16.67 |
March | 20.52 | 20.28 |
April | 21.26 | 25.86 |
May | 22.00 | 32.05 |
June | 22.80 | 35.24 |
July | 23.14 | 36.21 |
August | 23.10 | 36.44 |
September | 22.20 | 33.05 |
October | 21.23 | 27.59 |
November | 20.40 | 21.57 |
December | 19.80 | 14.93 |
Annual Sum or Average | 21.36 | 26.21 |
Minimum of Months | 19.80 | 14.02 |
Maximum of Months | 23.14 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY JANITOR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.85 | 14.02 |
February | 21.00 | 16.67 |
March | 21.22 | 20.28 |
April | 21.43 | 25.86 |
May | 21.77 | 32.05 |
June | 22.37 | 35.24 |
July | 22.60 | 36.21 |
August | 22.68 | 36.44 |
September | 22.09 | 33.05 |
October | 21.60 | 27.59 |
November | 21.26 | 21.57 |
December | 20.80 | 14.93 |
Annual Sum or Average | 21.64 | 26.21 |
Minimum of Months | 20.80 | 14.02 |
Maximum of Months | 22.68 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.09 | 14.02 |
February | 20.34 | 16.67 |
March | 20.78 | 20.28 |
April | 21.31 | 25.86 |
May | 21.93 | 32.05 |
June | 22.64 | 35.24 |
July | 22.98 | 36.21 |
August | 22.97 | 36.44 |
September | 22.21 | 33.05 |
October | 21.52 | 27.59 |
November | 20.79 | 21.57 |
December | 20.05 | 14.93 |
Annual Sum or Average | 21.47 | 26.21 |
Minimum of Months | 20.05 | 14.02 |
Maximum of Months | 22.98 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 VESTIBULE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.43 | 14.02 |
February | 19.28 | 16.67 |
March | 20.75 | 20.28 |
April | 22.82 | 25.86 |
May | 25.41 | 32.05 |
June | 27.37 | 35.24 |
July | 27.45 | 36.21 |
August | 28.31 | 36.44 |
September | 26.06 | 33.05 |
October | 23.63 | 27.59 |
November | 21.48 | 21.57 |
December | 18.56 | 14.93 |
Annual Sum or Average | 23.32 | 26.21 |
Minimum of Months | 18.43 | 14.02 |
Maximum of Months | 28.31 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.71 | 14.02 |
February | 20.80 | 16.67 |
March | 20.94 | 20.28 |
April | 21.10 | 25.86 |
May | 21.65 | 32.05 |
June | 22.19 | 35.24 |
July | 22.38 | 36.21 |
August | 22.69 | 36.44 |
September | 22.05 | 33.05 |
October | 21.56 | 27.59 |
November | 21.06 | 21.57 |
December | 20.64 | 14.93 |
Annual Sum or Average | 21.48 | 26.21 |
Minimum of Months | 20.64 | 14.02 |
Maximum of Months | 22.69 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.57 | 14.02 |
February | 19.56 | 16.67 |
March | 19.60 | 20.28 |
April | 19.53 | 25.86 |
May | 19.57 | 32.05 |
June | 19.66 | 35.24 |
July | 19.60 | 36.21 |
August | 19.78 | 36.44 |
September | 19.58 | 33.05 |
October | 19.52 | 27.59 |
November | 19.50 | 21.57 |
December | 19.56 | 14.93 |
Annual Sum or Average | 19.59 | 26.21 |
Minimum of Months | 19.50 | 14.02 |
Maximum of Months | 19.78 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 DICTATION
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | 14.02 |
February | 21.31 | 16.67 |
March | 21.38 | 20.28 |
April | 21.29 | 25.86 |
May | 21.42 | 32.05 |
June | 21.74 | 35.24 |
July | 21.74 | 36.21 |
August | 22.00 | 36.44 |
September | 21.59 | 33.05 |
October | 21.38 | 27.59 |
November | 21.31 | 21.57 |
December | 21.28 | 14.93 |
Annual Sum or Average | 21.48 | 26.21 |
Minimum of Months | 21.28 | 14.02 |
Maximum of Months | 22.00 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | 14.02 |
February | 19.52 | 16.67 |
March | 19.61 | 20.28 |
April | 19.57 | 25.86 |
May | 19.72 | 32.05 |
June | 20.08 | 35.24 |
July | 20.08 | 36.21 |
August | 20.37 | 36.44 |
September | 19.86 | 33.05 |
October | 19.59 | 27.59 |
November | 19.50 | 21.57 |
December | 19.49 | 14.93 |
Annual Sum or Average | 19.74 | 26.21 |
Minimum of Months | 19.49 | 14.02 |
Maximum of Months | 20.37 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.83 | 14.02 |
February | 19.80 | 16.67 |
March | 19.81 | 20.28 |
April | 19.72 | 25.86 |
May | 19.88 | 32.05 |
June | 20.29 | 35.24 |
July | 20.31 | 36.21 |
August | 20.69 | 36.44 |
September | 20.13 | 33.05 |
October | 19.84 | 27.59 |
November | 19.73 | 21.57 |
December | 19.80 | 14.93 |
Annual Sum or Average | 19.99 | 26.21 |
Minimum of Months | 19.72 | 14.02 |
Maximum of Months | 20.69 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 3
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.76 | 14.02 |
February | 19.72 | 16.67 |
March | 19.73 | 20.28 |
April | 19.65 | 25.86 |
May | 19.77 | 32.05 |
June | 20.12 | 35.24 |
July | 20.12 | 36.21 |
August | 20.49 | 36.44 |
September | 19.97 | 33.05 |
October | 19.74 | 27.59 |
November | 19.66 | 21.57 |
December | 19.73 | 14.93 |
Annual Sum or Average | 19.87 | 26.21 |
Minimum of Months | 19.65 | 14.02 |
Maximum of Months | 20.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 4
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.73 | 14.02 |
February | 19.68 | 16.67 |
March | 19.69 | 20.28 |
April | 19.64 | 25.86 |
May | 19.79 | 32.05 |
June | 20.17 | 35.24 |
July | 20.23 | 36.21 |
August | 20.63 | 36.44 |
September | 20.13 | 33.05 |
October | 19.93 | 27.59 |
November | 19.76 | 21.57 |
December | 19.69 | 14.93 |
Annual Sum or Average | 19.93 | 26.21 |
Minimum of Months | 19.64 | 14.02 |
Maximum of Months | 20.63 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 5
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | 14.02 |
February | 19.52 | 16.67 |
March | 19.61 | 20.28 |
April | 19.58 | 25.86 |
May | 19.75 | 32.05 |
June | 20.17 | 35.24 |
July | 20.25 | 36.21 |
August | 20.49 | 36.44 |
September | 19.82 | 33.05 |
October | 19.56 | 27.59 |
November | 19.50 | 21.57 |
December | 19.49 | 14.93 |
Annual Sum or Average | 19.77 | 26.21 |
Minimum of Months | 19.49 | 14.02 |
Maximum of Months | 20.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 6
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | 14.02 |
February | 19.55 | 16.67 |
March | 19.65 | 20.28 |
April | 19.64 | 25.86 |
May | 19.87 | 32.05 |
June | 20.38 | 35.24 |
July | 20.41 | 36.21 |
August | 20.64 | 36.44 |
September | 19.91 | 33.05 |
October | 19.61 | 27.59 |
November | 19.53 | 21.57 |
December | 19.52 | 14.93 |
Annual Sum or Average | 19.86 | 26.21 |
Minimum of Months | 19.52 | 14.02 |
Maximum of Months | 20.64 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 7
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | 14.02 |
February | 19.68 | 16.67 |
March | 19.73 | 20.28 |
April | 19.67 | 25.86 |
May | 19.83 | 32.05 |
June | 20.25 | 35.24 |
July | 20.23 | 36.21 |
August | 20.50 | 36.44 |
September | 19.89 | 33.05 |
October | 19.64 | 27.59 |
November | 19.59 | 21.57 |
December | 19.67 | 14.93 |
Annual Sum or Average | 19.87 | 26.21 |
Minimum of Months | 19.59 | 14.02 |
Maximum of Months | 20.50 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 8
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | 14.02 |
February | 19.56 | 16.67 |
March | 19.65 | 20.28 |
April | 19.64 | 25.86 |
May | 19.85 | 32.05 |
June | 20.36 | 35.24 |
July | 20.39 | 36.21 |
August | 20.61 | 36.44 |
September | 19.90 | 33.05 |
October | 19.60 | 27.59 |
November | 19.53 | 21.57 |
December | 19.54 | 14.93 |
Annual Sum or Average | 19.85 | 26.21 |
Minimum of Months | 19.53 | 14.02 |
Maximum of Months | 20.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 9
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.77 | 14.02 |
February | 19.78 | 16.67 |
March | 19.84 | 20.28 |
April | 19.78 | 25.86 |
May | 20.00 | 32.05 |
June | 20.50 | 35.24 |
July | 20.51 | 36.21 |
August | 20.78 | 36.44 |
September | 20.09 | 33.05 |
October | 19.75 | 27.59 |
November | 19.69 | 21.57 |
December | 19.76 | 14.93 |
Annual Sum or Average | 20.02 | 26.21 |
Minimum of Months | 19.69 | 14.02 |
Maximum of Months | 20.78 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.87 | 14.02 |
February | 20.98 | 16.67 |
March | 21.08 | 20.28 |
April | 21.13 | 25.86 |
May | 21.50 | 32.05 |
June | 21.94 | 35.24 |
July | 22.01 | 36.21 |
August | 22.32 | 36.44 |
September | 21.80 | 33.05 |
October | 21.42 | 27.59 |
November | 21.12 | 21.57 |
December | 20.85 | 14.93 |
Annual Sum or Average | 21.42 | 26.21 |
Minimum of Months | 20.85 | 14.02 |
Maximum of Months | 22.32 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | 14.02 |
February | 21.04 | 16.67 |
March | 21.09 | 20.28 |
April | 21.07 | 25.86 |
May | 21.36 | 32.05 |
June | 21.76 | 35.24 |
July | 21.81 | 36.21 |
August | 22.14 | 36.44 |
September | 21.67 | 33.05 |
October | 21.37 | 27.59 |
November | 21.16 | 21.57 |
December | 20.96 | 14.93 |
Annual Sum or Average | 21.37 | 26.21 |
Minimum of Months | 20.96 | 14.02 |
Maximum of Months | 22.14 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 3
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | 14.02 |
February | 20.96 | 16.67 |
March | 21.00 | 20.28 |
April | 20.95 | 25.86 |
May | 21.17 | 32.05 |
June | 21.55 | 35.24 |
July | 21.58 | 36.21 |
August | 21.91 | 36.44 |
September | 21.49 | 33.05 |
October | 21.26 | 27.59 |
November | 21.09 | 21.57 |
December | 20.89 | 14.93 |
Annual Sum or Average | 21.23 | 26.21 |
Minimum of Months | 20.89 | 14.02 |
Maximum of Months | 21.91 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 4
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.71 | 14.02 |
February | 20.86 | 16.67 |
March | 21.06 | 20.28 |
April | 21.19 | 25.86 |
May | 21.56 | 32.05 |
June | 22.01 | 35.24 |
July | 22.04 | 36.21 |
August | 22.22 | 36.44 |
September | 21.62 | 33.05 |
October | 21.17 | 27.59 |
November | 20.92 | 21.57 |
December | 20.76 | 14.93 |
Annual Sum or Average | 21.35 | 26.21 |
Minimum of Months | 20.71 | 14.02 |
Maximum of Months | 22.22 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 5
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | 14.02 |
February | 20.94 | 16.67 |
March | 21.16 | 20.28 |
April | 21.30 | 25.86 |
May | 21.69 | 32.05 |
June | 22.14 | 35.24 |
July | 22.19 | 36.21 |
August | 22.35 | 36.44 |
September | 21.76 | 33.05 |
October | 21.29 | 27.59 |
November | 21.02 | 21.57 |
December | 20.83 | 14.93 |
Annual Sum or Average | 21.46 | 26.21 |
Minimum of Months | 20.77 | 14.02 |
Maximum of Months | 22.35 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 6
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.71 | 14.02 |
February | 20.89 | 16.67 |
March | 21.11 | 20.28 |
April | 21.25 | 25.86 |
May | 21.66 | 32.05 |
June | 22.12 | 35.24 |
July | 22.17 | 36.21 |
August | 22.33 | 36.44 |
September | 21.73 | 33.05 |
October | 21.25 | 27.59 |
November | 20.96 | 21.57 |
December | 20.78 | 14.93 |
Annual Sum or Average | 21.42 | 26.21 |
Minimum of Months | 20.71 | 14.02 |
Maximum of Months | 22.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 JANITOR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.30 | 14.02 |
February | 20.54 | 16.67 |
March | 20.89 | 20.28 |
April | 21.27 | 25.86 |
May | 22.05 | 32.05 |
June | 22.63 | 35.24 |
July | 22.74 | 36.21 |
August | 22.87 | 36.44 |
September | 22.07 | 33.05 |
October | 21.37 | 27.59 |
November | 20.76 | 21.57 |
December | 20.30 | 14.93 |
Annual Sum or Average | 21.49 | 26.21 |
Minimum of Months | 20.30 | 14.02 |
Maximum of Months | 22.87 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 LOUNGE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 14.02 |
February | 21.55 | 16.67 |
March | 21.61 | 20.28 |
April | 21.55 | 25.86 |
May | 21.70 | 32.05 |
June | 22.04 | 35.24 |
July | 22.07 | 36.21 |
August | 22.32 | 36.44 |
September | 21.83 | 33.05 |
October | 21.60 | 27.59 |
November | 21.53 | 21.57 |
December | 21.52 | 14.93 |
Annual Sum or Average | 21.74 | 26.21 |
Minimum of Months | 21.52 | 14.02 |
Maximum of Months | 22.32 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 14.02 |
February | 21.63 | 16.67 |
March | 21.74 | 20.28 |
April | 21.75 | 25.86 |
May | 21.98 | 32.05 |
June | 22.38 | 35.24 |
July | 22.45 | 36.21 |
August | 22.66 | 36.44 |
September | 22.08 | 33.05 |
October | 21.75 | 27.59 |
November | 21.62 | 21.57 |
December | 21.57 | 14.93 |
Annual Sum or Average | 21.93 | 26.21 |
Minimum of Months | 21.55 | 14.02 |
Maximum of Months | 22.66 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | 14.02 |
February | 21.67 | 16.67 |
March | 21.79 | 20.28 |
April | 21.82 | 25.86 |
May | 22.07 | 32.05 |
June | 22.49 | 35.24 |
July | 22.56 | 36.21 |
August | 22.75 | 36.44 |
September | 22.17 | 33.05 |
October | 21.80 | 27.59 |
November | 21.66 | 21.57 |
December | 21.61 | 14.93 |
Annual Sum or Average | 22.00 | 26.21 |
Minimum of Months | 21.56 | 14.02 |
Maximum of Months | 22.75 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.33 | 14.02 |
February | 20.61 | 16.67 |
March | 20.92 | 20.28 |
April | 21.31 | 25.86 |
May | 21.92 | 32.05 |
June | 22.44 | 35.24 |
July | 22.68 | 36.21 |
August | 22.78 | 36.44 |
September | 22.06 | 33.05 |
October | 21.47 | 27.59 |
November | 20.86 | 21.57 |
December | 20.25 | 14.93 |
Annual Sum or Average | 21.47 | 26.21 |
Minimum of Months | 20.25 | 14.02 |
Maximum of Months | 22.78 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 14.02 |
February | 21.01 | 16.67 |
March | 21.20 | 20.28 |
April | 21.39 | 25.86 |
May | 21.78 | 32.05 |
June | 22.19 | 35.24 |
July | 22.30 | 36.21 |
August | 22.46 | 36.44 |
September | 21.91 | 33.05 |
October | 21.48 | 27.59 |
November | 21.12 | 21.57 |
December | 20.82 | 14.93 |
Annual Sum or Average | 21.54 | 26.21 |
Minimum of Months | 20.82 | 14.02 |
Maximum of Months | 22.46 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.03 | 14.02 |
February | 21.18 | 16.67 |
March | 21.36 | 20.28 |
April | 21.49 | 25.86 |
May | 22.06 | 32.05 |
June | 22.60 | 35.24 |
July | 22.76 | 36.21 |
August | 23.03 | 36.44 |
September | 22.39 | 33.05 |
October | 21.87 | 27.59 |
November | 21.41 | 21.57 |
December | 21.01 | 14.93 |
Annual Sum or Average | 21.85 | 26.21 |
Minimum of Months | 21.01 | 14.02 |
Maximum of Months | 23.03 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 14.02 |
February | 21.43 | 16.67 |
March | 21.49 | 20.28 |
April | 21.46 | 25.86 |
May | 21.70 | 32.05 |
June | 22.07 | 35.24 |
July | 22.12 | 36.21 |
August | 22.36 | 36.44 |
September | 21.90 | 33.05 |
October | 21.60 | 27.59 |
November | 21.45 | 21.57 |
December | 21.36 | 14.93 |
Annual Sum or Average | 21.69 | 26.21 |
Minimum of Months | 21.36 | 14.02 |
Maximum of Months | 22.36 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.04 | 14.02 |
February | 17.89 | 16.67 |
March | 17.68 | 20.28 |
April | 17.50 | 25.86 |
May | 17.77 | 32.05 |
June | 18.32 | 35.24 |
July | 18.45 | 36.21 |
August | 18.75 | 36.44 |
September | 18.06 | 33.05 |
October | 17.66 | 27.59 |
November | 17.65 | 21.57 |
December | 17.96 | 14.93 |
Annual Sum or Average | 17.98 | 26.21 |
Minimum of Months | 17.50 | 14.02 |
Maximum of Months | 18.75 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 14.02 |
February | 21.76 | 16.67 |
March | 21.84 | 20.28 |
April | 21.82 | 25.86 |
May | 21.98 | 32.05 |
June | 22.32 | 35.24 |
July | 22.39 | 36.21 |
August | 22.58 | 36.44 |
September | 22.11 | 33.05 |
October | 21.84 | 27.59 |
November | 21.75 | 21.57 |
December | 21.72 | 14.93 |
Annual Sum or Average | 21.99 | 26.21 |
Minimum of Months | 21.70 | 14.02 |
Maximum of Months | 22.58 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 14.02 |
February | 21.72 | 16.67 |
March | 21.79 | 20.28 |
April | 21.77 | 25.86 |
May | 21.98 | 32.05 |
June | 22.34 | 35.24 |
July | 22.41 | 36.21 |
August | 22.64 | 36.44 |
September | 22.14 | 33.05 |
October | 21.85 | 27.59 |
November | 21.73 | 21.57 |
December | 21.67 | 14.93 |
Annual Sum or Average | 21.98 | 26.21 |
Minimum of Months | 21.67 | 14.02 |
Maximum of Months | 22.64 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | 14.02 |
February | 20.76 | 16.67 |
March | 20.80 | 20.28 |
April | 20.76 | 25.86 |
May | 20.94 | 32.05 |
June | 21.30 | 35.24 |
July | 21.32 | 36.21 |
August | 21.61 | 36.44 |
September | 21.24 | 33.05 |
October | 21.01 | 27.59 |
November | 20.86 | 21.57 |
December | 20.72 | 14.93 |
Annual Sum or Average | 21.01 | 26.21 |
Minimum of Months | 20.72 | 14.02 |
Maximum of Months | 21.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | 14.02 |
February | 20.94 | 16.67 |
March | 21.12 | 20.28 |
April | 21.24 | 25.86 |
May | 21.60 | 32.05 |
June | 22.04 | 35.24 |
July | 22.08 | 36.21 |
August | 22.25 | 36.44 |
September | 21.69 | 33.05 |
October | 21.25 | 27.59 |
November | 21.00 | 21.57 |
December | 20.84 | 14.93 |
Annual Sum or Average | 21.41 | 26.21 |
Minimum of Months | 20.80 | 14.02 |
Maximum of Months | 22.25 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 3
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 14.02 |
February | 21.01 | 16.67 |
March | 21.22 | 20.28 |
April | 21.36 | 25.86 |
May | 21.74 | 32.05 |
June | 22.18 | 35.24 |
July | 22.23 | 36.21 |
August | 22.37 | 36.44 |
September | 21.82 | 33.05 |
October | 21.35 | 27.59 |
November | 21.08 | 21.57 |
December | 20.91 | 14.93 |
Annual Sum or Average | 21.51 | 26.21 |
Minimum of Months | 20.83 | 14.02 |
Maximum of Months | 22.37 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 UTILITY
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.03 | 14.02 |
February | 20.26 | 16.67 |
March | 20.60 | 20.28 |
April | 21.10 | 25.86 |
May | 21.72 | 32.05 |
June | 22.20 | 35.24 |
July | 22.42 | 36.21 |
August | 22.49 | 36.44 |
September | 21.83 | 33.05 |
October | 21.23 | 27.59 |
November | 20.47 | 21.57 |
December | 19.97 | 14.93 |
Annual Sum or Average | 21.20 | 26.21 |
Minimum of Months | 19.97 | 14.02 |
Maximum of Months | 22.49 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | 14.02 |
February | 21.49 | 16.67 |
March | 21.71 | 20.28 |
April | 21.91 | 25.86 |
May | 22.33 | 32.05 |
June | 22.80 | 35.24 |
July | 22.94 | 36.21 |
August | 23.08 | 36.44 |
September | 22.43 | 33.05 |
October | 21.95 | 27.59 |
November | 21.60 | 21.57 |
December | 21.34 | 14.93 |
Annual Sum or Average | 22.07 | 26.21 |
Minimum of Months | 21.28 | 14.02 |
Maximum of Months | 23.08 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.42 | 14.02 |
February | 21.55 | 16.67 |
March | 21.68 | 20.28 |
April | 21.74 | 25.86 |
May | 22.04 | 32.05 |
June | 22.41 | 35.24 |
July | 22.49 | 36.21 |
August | 22.67 | 36.44 |
September | 22.18 | 33.05 |
October | 21.82 | 27.59 |
November | 21.60 | 21.57 |
December | 21.46 | 14.93 |
Annual Sum or Average | 21.92 | 26.21 |
Minimum of Months | 21.42 | 14.02 |
Maximum of Months | 22.67 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.55 | 14.02 |
February | 19.59 | 16.67 |
March | 19.68 | 20.28 |
April | 19.67 | 25.86 |
May | 19.89 | 32.05 |
June | 20.20 | 35.24 |
July | 20.19 | 36.21 |
August | 20.40 | 36.44 |
September | 19.91 | 33.05 |
October | 19.67 | 27.59 |
November | 19.54 | 21.57 |
December | 19.53 | 14.93 |
Annual Sum or Average | 19.82 | 26.21 |
Minimum of Months | 19.53 | 14.02 |
Maximum of Months | 20.40 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 X-RAY
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.59 | 14.02 |
February | 22.52 | 16.67 |
March | 22.41 | 20.28 |
April | 22.31 | 25.86 |
May | 22.44 | 32.05 |
June | 22.90 | 35.24 |
July | 23.01 | 36.21 |
August | 23.25 | 36.44 |
September | 22.63 | 33.05 |
October | 22.32 | 27.59 |
November | 22.35 | 21.57 |
December | 22.58 | 14.93 |
Annual Sum or Average | 22.61 | 26.21 |
Minimum of Months | 22.31 | 14.02 |
Maximum of Months | 23.25 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 DRESSING ROOM
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | 14.02 |
February | 20.78 | 16.67 |
March | 20.92 | 20.28 |
April | 20.95 | 25.86 |
May | 21.23 | 32.05 |
June | 21.59 | 35.24 |
July | 21.61 | 36.21 |
August | 21.86 | 36.44 |
September | 21.26 | 33.05 |
October | 20.92 | 27.59 |
November | 20.73 | 21.57 |
December | 20.67 | 14.93 |
Annual Sum or Average | 21.10 | 26.21 |
Minimum of Months | 20.67 | 14.02 |
Maximum of Months | 21.86 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 ELEVATOR HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | 14.02 |
February | 20.82 | 16.67 |
March | 21.16 | 20.28 |
April | 21.53 | 25.86 |
May | 22.24 | 32.05 |
June | 22.78 | 35.24 |
July | 22.93 | 36.21 |
August | 23.12 | 36.44 |
September | 22.30 | 33.05 |
October | 21.59 | 27.59 |
November | 20.97 | 21.57 |
December | 20.52 | 14.93 |
Annual Sum or Average | 21.71 | 26.21 |
Minimum of Months | 20.47 | 14.02 |
Maximum of Months | 23.12 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 HUMID
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | 14.02 |
February | 20.88 | 16.67 |
March | 21.02 | 20.28 |
April | 21.06 | 25.86 |
May | 21.36 | 32.05 |
June | 21.75 | 35.24 |
July | 21.78 | 36.21 |
August | 22.03 | 36.44 |
September | 21.41 | 33.05 |
October | 21.04 | 27.59 |
November | 20.83 | 21.57 |
December | 20.77 | 14.93 |
Annual Sum or Average | 21.23 | 26.21 |
Minimum of Months | 20.77 | 14.02 |
Maximum of Months | 22.03 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 JANITOR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.80 | 14.02 |
February | 20.07 | 16.67 |
March | 20.48 | 20.28 |
April | 21.05 | 25.86 |
May | 22.07 | 32.05 |
June | 22.65 | 35.24 |
July | 22.78 | 36.21 |
August | 22.95 | 36.44 |
September | 22.05 | 33.05 |
October | 21.20 | 27.59 |
November | 20.32 | 21.57 |
December | 19.80 | 14.93 |
Annual Sum or Average | 21.28 | 26.21 |
Minimum of Months | 19.80 | 14.02 |
Maximum of Months | 22.95 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOCKER
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | 14.02 |
February | 20.97 | 16.67 |
March | 21.18 | 20.28 |
April | 21.32 | 25.86 |
May | 21.76 | 32.05 |
June | 22.26 | 35.24 |
July | 22.35 | 36.21 |
August | 22.56 | 36.44 |
September | 21.78 | 33.05 |
October | 21.28 | 27.59 |
November | 20.96 | 21.57 |
December | 20.83 | 14.93 |
Annual Sum or Average | 21.51 | 26.21 |
Minimum of Months | 20.81 | 14.02 |
Maximum of Months | 22.56 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | 14.02 |
February | 21.02 | 16.67 |
March | 21.27 | 20.28 |
April | 21.49 | 25.86 |
May | 22.07 | 32.05 |
June | 22.65 | 35.24 |
July | 22.78 | 36.21 |
August | 22.98 | 36.44 |
September | 22.11 | 33.05 |
October | 21.49 | 27.59 |
November | 21.05 | 21.57 |
December | 20.85 | 14.93 |
Annual Sum or Average | 21.72 | 26.21 |
Minimum of Months | 20.82 | 14.02 |
Maximum of Months | 22.98 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | 14.02 |
February | 19.50 | 16.67 |
March | 19.58 | 20.28 |
April | 19.54 | 25.86 |
May | 19.66 | 32.05 |
June | 19.97 | 35.24 |
July | 19.98 | 36.21 |
August | 20.18 | 36.44 |
September | 19.65 | 33.05 |
October | 19.50 | 27.59 |
November | 19.48 | 21.57 |
December | 19.47 | 14.93 |
Annual Sum or Average | 19.67 | 26.21 |
Minimum of Months | 19.47 | 14.02 |
Maximum of Months | 20.18 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.43 | 14.02 |
February | 21.61 | 16.67 |
March | 21.70 | 20.28 |
April | 22.08 | 25.86 |
May | 22.78 | 32.05 |
June | 23.25 | 35.24 |
July | 23.54 | 36.21 |
August | 23.61 | 36.44 |
September | 22.89 | 33.05 |
October | 22.25 | 27.59 |
November | 21.68 | 21.57 |
December | 21.38 | 14.93 |
Annual Sum or Average | 22.36 | 26.21 |
Minimum of Months | 21.38 | 14.02 |
Maximum of Months | 23.61 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.45 | 14.02 |
February | 20.74 | 16.67 |
March | 21.00 | 20.28 |
April | 21.33 | 25.86 |
May | 21.92 | 32.05 |
June | 22.43 | 35.24 |
July | 22.61 | 36.21 |
August | 22.76 | 36.44 |
September | 21.97 | 33.05 |
October | 21.37 | 27.59 |
November | 20.84 | 21.57 |
December | 20.43 | 14.93 |
Annual Sum or Average | 21.49 | 26.21 |
Minimum of Months | 20.43 | 14.02 |
Maximum of Months | 22.76 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | 14.02 |
February | 20.79 | 16.67 |
March | 21.11 | 20.28 |
April | 21.45 | 25.86 |
May | 22.13 | 32.05 |
June | 22.72 | 35.24 |
July | 22.87 | 36.21 |
August | 23.06 | 36.44 |
September | 22.16 | 33.05 |
October | 21.45 | 27.59 |
November | 20.89 | 21.57 |
December | 20.55 | 14.93 |
Annual Sum or Average | 21.65 | 26.21 |
Minimum of Months | 20.51 | 14.02 |
Maximum of Months | 23.06 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE HALL
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | 14.02 |
February | 20.98 | 16.67 |
March | 21.24 | 20.28 |
April | 21.51 | 25.86 |
May | 22.10 | 32.05 |
June | 22.63 | 35.24 |
July | 22.76 | 36.21 |
August | 23.00 | 36.44 |
September | 22.22 | 33.05 |
October | 21.60 | 27.59 |
November | 21.09 | 21.57 |
December | 20.75 | 14.93 |
Annual Sum or Average | 21.72 | 26.21 |
Minimum of Months | 20.72 | 14.02 |
Maximum of Months | 23.00 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | 14.02 |
February | 19.55 | 16.67 |
March | 19.65 | 20.28 |
April | 19.65 | 25.86 |
May | 19.89 | 32.05 |
June | 20.21 | 35.24 |
July | 20.21 | 36.21 |
August | 20.46 | 36.44 |
September | 19.90 | 33.05 |
October | 19.65 | 27.59 |
November | 19.52 | 21.57 |
December | 19.49 | 14.93 |
Annual Sum or Average | 19.81 | 26.21 |
Minimum of Months | 19.49 | 14.02 |
Maximum of Months | 20.46 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.56 | 14.02 |
February | 19.56 | 16.67 |
March | 19.61 | 20.28 |
April | 19.56 | 25.86 |
May | 19.70 | 32.05 |
June | 20.09 | 35.24 |
July | 20.14 | 36.21 |
August | 20.53 | 36.44 |
September | 19.99 | 33.05 |
October | 19.74 | 27.59 |
November | 19.61 | 21.57 |
December | 19.54 | 14.93 |
Annual Sum or Average | 19.80 | 26.21 |
Minimum of Months | 19.54 | 14.02 |
Maximum of Months | 20.53 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.55 | 14.02 |
February | 19.56 | 16.67 |
March | 19.64 | 20.28 |
April | 19.58 | 25.86 |
May | 19.69 | 32.05 |
June | 20.03 | 35.24 |
July | 20.02 | 36.21 |
August | 20.31 | 36.44 |
September | 19.77 | 33.05 |
October | 19.56 | 27.59 |
November | 19.52 | 21.57 |
December | 19.54 | 14.93 |
Annual Sum or Average | 19.73 | 26.21 |
Minimum of Months | 19.52 | 14.02 |
Maximum of Months | 20.31 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY TOILET
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | 14.02 |
February | 19.53 | 16.67 |
March | 19.60 | 20.28 |
April | 19.54 | 25.86 |
May | 19.59 | 32.05 |
June | 19.74 | 35.24 |
July | 19.70 | 36.21 |
August | 19.89 | 36.44 |
September | 19.58 | 33.05 |
October | 19.51 | 27.59 |
November | 19.49 | 21.57 |
December | 19.51 | 14.93 |
Annual Sum or Average | 19.60 | 26.21 |
Minimum of Months | 19.49 | 14.02 |
Maximum of Months | 19.89 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.67 | 14.02 |
February | 19.70 | 16.67 |
March | 19.78 | 20.28 |
April | 19.76 | 25.86 |
May | 19.96 | 32.05 |
June | 20.35 | 35.24 |
July | 20.36 | 36.21 |
August | 20.62 | 36.44 |
September | 20.02 | 33.05 |
October | 19.73 | 27.59 |
November | 19.62 | 21.57 |
December | 19.65 | 14.93 |
Annual Sum or Average | 19.94 | 26.21 |
Minimum of Months | 19.62 | 14.02 |
Maximum of Months | 20.62 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | 14.02 |
February | 20.74 | 16.67 |
March | 21.01 | 20.28 |
April | 21.27 | 25.86 |
May | 21.81 | 32.05 |
June | 22.32 | 35.24 |
July | 22.43 | 36.21 |
August | 22.62 | 36.44 |
September | 21.83 | 33.05 |
October | 21.26 | 27.59 |
November | 20.81 | 21.57 |
December | 20.50 | 14.93 |
Annual Sum or Average | 21.43 | 26.21 |
Minimum of Months | 20.46 | 14.02 |
Maximum of Months | 22.62 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 TREATMENT
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.59 | 14.02 |
February | 19.59 | 16.67 |
March | 19.67 | 20.28 |
April | 19.61 | 25.86 |
May | 19.74 | 32.05 |
June | 20.11 | 35.24 |
July | 20.10 | 36.21 |
August | 20.41 | 36.44 |
September | 19.83 | 33.05 |
October | 19.59 | 27.59 |
November | 19.55 | 21.57 |
December | 19.58 | 14.93 |
Annual Sum or Average | 19.78 | 26.21 |
Minimum of Months | 19.55 | 14.02 |
Maximum of Months | 20.41 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 1
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | 14.02 |
February | 20.85 | 16.67 |
March | 21.06 | 20.28 |
April | 21.32 | 25.86 |
May | 22.01 | 32.05 |
June | 22.57 | 35.24 |
July | 22.74 | 36.21 |
August | 23.04 | 36.44 |
September | 22.28 | 33.05 |
October | 21.63 | 27.59 |
November | 21.04 | 21.57 |
December | 20.61 | 14.93 |
Annual Sum or Average | 21.65 | 26.21 |
Minimum of Months | 20.61 | 14.02 |
Maximum of Months | 23.04 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 2
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | 14.02 |
February | 20.87 | 16.67 |
March | 21.11 | 20.28 |
April | 21.44 | 25.86 |
May | 22.26 | 32.05 |
June | 22.84 | 35.24 |
July | 23.06 | 36.21 |
August | 23.33 | 36.44 |
September | 22.58 | 33.05 |
October | 21.86 | 27.59 |
November | 21.16 | 21.57 |
December | 20.61 | 14.93 |
Annual Sum or Average | 21.82 | 26.21 |
Minimum of Months | 20.61 | 14.02 |
Maximum of Months | 23.33 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UTILITY
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.32 | 14.02 |
February | 20.56 | 16.67 |
March | 20.80 | 20.28 |
April | 21.02 | 25.86 |
May | 21.46 | 32.05 |
June | 21.86 | 35.24 |
July | 21.94 | 36.21 |
August | 22.12 | 36.44 |
September | 21.49 | 33.05 |
October | 21.02 | 27.59 |
November | 20.61 | 21.57 |
December | 20.33 | 14.93 |
Annual Sum or Average | 21.13 | 26.21 |
Minimum of Months | 20.32 | 14.02 |
Maximum of Months | 22.12 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 WORK
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.15 | 14.02 |
February | 20.42 | 16.67 |
March | 20.72 | 20.28 |
April | 21.17 | 25.86 |
May | 21.92 | 32.05 |
June | 22.48 | 35.24 |
July | 22.74 | 36.21 |
August | 22.89 | 36.44 |
September | 22.03 | 33.05 |
October | 21.30 | 27.59 |
November | 20.60 | 21.57 |
December | 20.06 | 14.93 |
Annual Sum or Average | 21.38 | 26.21 |
Minimum of Months | 20.06 | 14.02 |
Maximum of Months | 22.89 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: NE STAIR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.59 | 14.02 |
February | 19.80 | 16.67 |
March | 20.16 | 20.28 |
April | 20.86 | 25.86 |
May | 21.97 | 32.05 |
June | 22.70 | 35.24 |
July | 22.96 | 36.21 |
August | 23.00 | 36.44 |
September | 22.04 | 33.05 |
October | 21.00 | 27.59 |
November | 20.09 | 21.57 |
December | 19.60 | 14.93 |
Annual Sum or Average | 21.16 | 26.21 |
Minimum of Months | 19.59 | 14.02 |
Maximum of Months | 23.00 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: NW ELEVATOR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 14.02 |
February | 20.37 | 16.67 |
March | 20.71 | 20.28 |
April | 21.15 | 25.86 |
May | 22.07 | 32.05 |
June | 22.62 | 35.24 |
July | 22.78 | 36.21 |
August | 22.92 | 36.44 |
September | 22.24 | 33.05 |
October | 21.46 | 27.59 |
November | 20.61 | 21.57 |
December | 20.08 | 14.93 |
Annual Sum or Average | 21.43 | 26.21 |
Minimum of Months | 20.08 | 14.02 |
Maximum of Months | 22.92 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: NW STAIR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | 14.02 |
February | 19.78 | 16.67 |
March | 20.19 | 20.28 |
April | 20.96 | 25.86 |
May | 22.12 | 32.05 |
June | 22.82 | 35.24 |
July | 23.04 | 36.21 |
August | 23.07 | 36.44 |
September | 22.11 | 33.05 |
October | 21.00 | 27.59 |
November | 20.02 | 21.57 |
December | 19.60 | 14.93 |
Annual Sum or Average | 21.20 | 26.21 |
Minimum of Months | 19.58 | 14.02 |
Maximum of Months | 23.07 | 36.44 |
Report: MONTHLY INDOOR TEMP
For: SW STAIR
Timestamp: 2015-09-13 14:22:44
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.44 | 14.02 |
February | 20.63 | 16.67 |
March | 20.90 | 20.28 |
April | 21.29 | 25.86 |
May | 22.19 | 32.05 |
June | 22.78 | 35.24 |
July | 23.00 | 36.21 |
August | 23.23 | 36.44 |
September | 22.57 | 33.05 |
October | 21.85 | 27.59 |
November | 21.01 | 21.57 |
December | 20.39 | 14.93 |
Annual Sum or Average | 21.70 | 26.21 |
Minimum of Months | 20.39 | 14.02 |
Maximum of Months | 23.23 | 36.44 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-1
Timestamp: 2015-09-13 14:22:44
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.121402E+12 | 0.157021E+12 |
February | 0.109071E+12 | 0.157950E+12 |
March | 0.110699E+12 | 0.199987E+12 |
April | 0.104033E+12 | 0.229072E+12 |
May | 0.999228E+11 | 0.274394E+12 |
June | 0.108117E+12 | 0.297236E+12 |
July | 0.136308E+12 | 0.310227E+12 |
August | 0.114977E+12 | 0.313286E+12 |
September | 0.906439E+11 | 0.279350E+12 |
October | 0.101258E+12 | 0.247694E+12 |
November | 0.110730E+12 | 0.195657E+12 |
December | 0.104880E+12 | 0.174220E+12 |
Annual Sum or Average | 0.131204E+13 | 0.283609E+13 |
Minimum of Months | 0.906439E+11 | 0.157021E+12 |
Maximum of Months | 0.136308E+12 | 0.313286E+12 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-2
Timestamp: 2015-09-13 14:22:44
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.591689E+11 | 0.134144E+12 |
February | 0.520613E+11 | 0.148680E+12 |
March | 0.595482E+11 | 0.203620E+12 |
April | 0.565930E+11 | 0.247378E+12 |
May | 0.520017E+11 | 0.305138E+12 |
June | 0.492922E+11 | 0.330543E+12 |
July | 0.491549E+11 | 0.333341E+12 |
August | 0.508303E+11 | 0.351248E+12 |
September | 0.492879E+11 | 0.312482E+12 |
October | 0.546284E+11 | 0.270103E+12 |
November | 0.557977E+11 | 0.207651E+12 |
December | 0.606197E+11 | 0.150996E+12 |
Annual Sum or Average | 0.648984E+12 | 0.299532E+13 |
Minimum of Months | 0.491549E+11 | 0.134144E+12 |
Maximum of Months | 0.606197E+11 | 0.351248E+12 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2015-09-13 14:22:44
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.225228E+12 | 0.478846E+11 |
February | 0.214263E+12 | 0.417109E+11 |
March | 0.248333E+12 | 0.444106E+11 |
April | 0.267809E+12 | 0.412924E+11 |
May | 0.308404E+12 | 0.380354E+11 |
June | 0.351376E+12 | 0.264548E+11 |
July | 0.396823E+12 | 0.189890E+11 |
August | 0.382088E+12 | 0.235049E+11 |
September | 0.306461E+12 | 0.349502E+11 |
October | 0.282093E+12 | 0.377484E+11 |
November | 0.252340E+12 | 0.360649E+11 |
December | 0.209455E+12 | 0.596485E+11 |
Annual Sum or Average | 0.344467E+13 | 0.450695E+12 |
Minimum of Months | 0.209455E+12 | 0.189890E+11 |
Maximum of Months | 0.396823E+12 | 0.596485E+11 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-13 14:22:44
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.441035E+12 | 285404.380 | 24-JAN-17:00 | 36851.394 | 111837.204 | 24474.947 | 30234.374 | 58618.290 | 8375.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.409485E+12 | 282647.013 | 27-FEB-14:00 | 36851.394 | 111837.204 | 27942.109 | 7646.233 | 98027.355 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.472695E+12 | 290539.686 | 29-MAR-14:00 | 36851.394 | 111837.204 | 32789.222 | 20536.259 | 79855.554 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.475104E+12 | 381229.328 | 21-APR-15:00 | 36851.394 | 111837.204 | 37245.442 | 39544.860 | 125333.723 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.526649E+12 | 407023.562 | 18-MAY-15:20 | 36851.394 | 111837.204 | 52428.161 | 30396.556 | 140442.968 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.565864E+12 | 420973.220 | 13-JUN-16:00 | 36851.394 | 111837.204 | 53180.559 | 30591.505 | 140442.968 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.606617E+12 | 427411.445 | 20-JUL-15:00 | 36851.394 | 111837.204 | 53381.376 | 29272.871 | 148426.296 | 0.000 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.605357E+12 | 420992.625 | 03-AUG-15:09 | 36851.394 | 111837.204 | 53381.376 | 28800.997 | 151189.075 | 0.000 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.514094E+12 | 404666.984 | 20-SEP-15:20 | 36851.394 | 111837.204 | 53290.474 | 30106.492 | 141127.052 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.497106E+12 | 381499.748 | 10-OCT-13:39 | 36851.394 | 111837.204 | 37881.320 | 42359.076 | 130803.855 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.462912E+12 | 318558.505 | 03-NOV-14:00 | 36851.394 | 111837.204 | 33753.523 | 20229.652 | 93304.832 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.422101E+12 | 278865.318 | 13-DEC-17:10 | 36851.394 | 111837.204 | 25016.802 | 30124.790 | 50904.992 | 8375.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.599902E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.409485E+12 | 278865.318 | 36851.394 | 111837.204 | 24474.947 | 7646.233 | 50904.992 | 0.000 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.606617E+12 | 427411.445 | 36851.394 | 111837.204 | 53381.376 | 42359.076 | 151189.075 | 8375.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2015-09-13 14:22:44
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [J] | GAS:BUILDING {Maximum}[W] | GAS:BUILDING {TIMESTAMP} | |
January | 0.202389E+12 | 148688.60 | 02-JAN-09:09 | 0.158619E+11 | 9905.77 | 02-JAN-06:10 |
February | 0.183577E+12 | 148688.60 | 01-FEB-09:09 | 0.143713E+11 | 9905.77 | 01-FEB-06:10 |
March | 0.212124E+12 | 148688.60 | 01-MAR-09:09 | 0.163897E+11 | 9905.77 | 01-MAR-06:10 |
April | 0.196088E+12 | 148688.60 | 03-APR-08:09 | 0.153698E+11 | 9905.77 | 03-APR-05:10 |
May | 0.207257E+12 | 148688.60 | 01-MAY-08:09 | 0.161258E+11 | 9905.77 | 01-MAY-05:10 |
June | 0.204231E+12 | 148688.60 | 01-JUN-08:09 | 0.158049E+11 | 9905.77 | 01-JUN-05:10 |
July | 0.199114E+12 | 148688.60 | 03-JUL-08:09 | 0.156907E+11 | 9905.77 | 03-JUL-05:10 |
August | 0.212124E+12 | 148688.60 | 01-AUG-08:09 | 0.163897E+11 | 9905.77 | 01-AUG-05:10 |
September | 0.196088E+12 | 148688.60 | 01-SEP-08:09 | 0.153698E+11 | 9905.77 | 01-SEP-05:10 |
October | 0.202389E+12 | 148688.60 | 02-OCT-08:09 | 0.158619E+11 | 9905.77 | 02-OCT-05:10 |
November | 0.197772E+12 | 148688.60 | 01-NOV-08:09 | 0.154482E+11 | 9905.77 | 01-NOV-05:10 |
December | 0.199114E+12 | 148688.60 | 01-DEC-09:09 | 0.156907E+11 | 9905.77 | 01-DEC-06:10 |
Annual Sum or Average | 0.241227E+13 | 0.188374E+12 | ||||
Minimum of Months | 0.183577E+12 | 148688.60 | 0.143713E+11 | 9905.77 | ||
Maximum of Months | 0.212124E+12 | 148688.60 | 0.163897E+11 | 9905.77 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2015-09-13 14:22:44
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.465507E+11 | 0.00 | 0.125022E+11 | 0.155839E+12 | 0.00 | 0.461729E+11 | 0.915327E+09 | 0.703560E+11 | 0.789158E+11 | 0.00 | 0.297836E+11 | 0.00 | 0.00 | 0.00 |
February | 0.423275E+11 | 0.00 | 0.108188E+11 | 0.141249E+12 | 0.00 | 0.424313E+11 | 0.826929E+09 | 0.591743E+11 | 0.827611E+11 | 0.00 | 0.298961E+11 | 0.00 | 0.00 | 0.00 |
March | 0.500442E+11 | 0.00 | 0.113213E+11 | 0.162080E+12 | 0.00 | 0.477144E+11 | 0.916198E+09 | 0.639582E+11 | 0.109357E+12 | 0.00 | 0.273042E+11 | 0.00 | 0.00 | 0.00 |
April | 0.451430E+11 | 0.00 | 0.103214E+11 | 0.150945E+12 | 0.00 | 0.475962E+11 | 0.886151E+09 | 0.592276E+11 | 0.136120E+12 | 0.00 | 0.248653E+11 | 0.00 | 0.00 | 0.00 |
May | 0.482974E+11 | 0.00 | 0.100902E+11 | 0.158960E+12 | 0.00 | 0.548969E+11 | 0.898093E+09 | 0.503840E+11 | 0.182544E+12 | 0.00 | 0.205790E+11 | 0.00 | 0.00 | 0.00 |
June | 0.480542E+11 | 0.00 | 0.945705E+10 | 0.156177E+12 | 0.00 | 0.622554E+11 | 0.800046E+09 | 0.524313E+11 | 0.210930E+12 | 0.00 | 0.257593E+11 | 0.00 | 0.00 | 0.00 |
July | 0.453862E+11 | 0.00 | 0.992940E+10 | 0.153727E+12 | 0.00 | 0.645823E+11 | 0.750477E+09 | 0.665687E+11 | 0.222425E+12 | 0.00 | 0.432474E+11 | 0.00 | 0.00 | 0.00 |
August | 0.500442E+11 | 0.00 | 0.103967E+11 | 0.162080E+12 | 0.00 | 0.685293E+11 | 0.747935E+09 | 0.562488E+11 | 0.230760E+12 | 0.00 | 0.265500E+11 | 0.00 | 0.00 | 0.00 |
September | 0.451430E+11 | 0.00 | 0.106832E+11 | 0.150945E+12 | 0.00 | 0.568643E+11 | 0.862358E+09 | 0.435557E+11 | 0.190236E+12 | 0.00 | 0.158044E+11 | 0.00 | 0.00 | 0.00 |
October | 0.465507E+11 | 0.00 | 0.117082E+11 | 0.155839E+12 | 0.00 | 0.512854E+11 | 0.914423E+09 | 0.570140E+11 | 0.152126E+12 | 0.00 | 0.216685E+11 | 0.00 | 0.00 | 0.00 |
November | 0.457252E+11 | 0.00 | 0.119143E+11 | 0.152047E+12 | 0.00 | 0.465971E+11 | 0.885716E+09 | 0.651275E+11 | 0.110639E+12 | 0.00 | 0.299760E+11 | 0.00 | 0.00 | 0.00 |
December | 0.453862E+11 | 0.00 | 0.126178E+11 | 0.153727E+12 | 0.00 | 0.453136E+11 | 0.915327E+09 | 0.596891E+11 | 0.875974E+11 | 0.00 | 0.168544E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.558652E+12 | 0.00 | 0.131761E+12 | 0.185361E+13 | 0.00 | 0.634239E+12 | 0.103190E+11 | 0.703735E+12 | 0.179441E+13 | 0.00 | 0.312288E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.423275E+11 | 0.00 | 0.945705E+10 | 0.141249E+12 | 0.00 | 0.424313E+11 | 0.747935E+09 | 0.435557E+11 | 0.789158E+11 | 0.00 | 0.158044E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.500442E+11 | 0.00 | 0.126178E+11 | 0.162080E+12 | 0.00 | 0.685293E+11 | 0.916198E+09 | 0.703560E+11 | 0.230760E+12 | 0.00 | 0.432474E+11 | 0.00 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2015-09-13 14:22:44
INTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.158619E+11 | 0.00 | 0.478846E+11 | 0.00 | 0.948517E+10 | 0.00 |
February | 0.143713E+11 | 0.00 | 0.417109E+11 | 0.00 | 0.841983E+10 | 0.00 |
March | 0.163897E+11 | 0.00 | 0.444106E+11 | 0.00 | 0.915376E+10 | 0.00 |
April | 0.153698E+11 | 0.00 | 0.412924E+11 | 0.00 | 0.752052E+10 | 0.00 |
May | 0.161258E+11 | 0.00 | 0.380354E+11 | 0.00 | 0.706982E+10 | 0.00 |
June | 0.158049E+11 | 0.00 | 0.264548E+11 | 0.00 | 0.632077E+10 | 0.00 |
July | 0.156907E+11 | 0.00 | 0.189890E+11 | 0.00 | 0.588574E+10 | 0.00 |
August | 0.163897E+11 | 0.00 | 0.235049E+11 | 0.00 | 0.655889E+10 | 0.00 |
September | 0.153698E+11 | 0.00 | 0.349502E+11 | 0.00 | 0.669376E+10 | 0.00 |
October | 0.158619E+11 | 0.00 | 0.377484E+11 | 0.00 | 0.776116E+10 | 0.00 |
November | 0.154482E+11 | 0.00 | 0.360649E+11 | 0.00 | 0.846663E+10 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.596485E+11 | 0.00 | 0.908487E+10 | 0.00 |
Annual Sum or Average | 0.188374E+12 | 0.00 | 0.450695E+12 | 0.00 | 0.924209E+11 | 0.00 |
Minimum of Months | 0.143713E+11 | 0.00 | 0.189890E+11 | 0.00 | 0.588574E+10 | 0.00 |
Maximum of Months | 0.163897E+11 | 0.00 | 0.596485E+11 | 0.00 | 0.948517E+10 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY
For: Meter
Timestamp: 2015-09-13 14:22:44
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 36851.39 | 02-JAN-07:10 | 0.00 | 8375.00 | 01-JAN-00:10 | 111837.20 | 02-JAN-09:09 | 0.00 | 30651.85 | 25-JAN-15:09 | 342.72 | 01-JAN-08:09 | 117672.87 | 02-JAN-05:10 |
February | 36851.39 | 01-FEB-07:10 | 0.00 | 8375.00 | 01-FEB-00:10 | 111837.20 | 01-FEB-09:09 | 0.00 | 29450.13 | 23-FEB-15:30 | 342.72 | 01-FEB-00:10 | 113122.78 | 21-FEB-05:10 |
March | 36851.39 | 01-MAR-07:10 | 0.00 | 8375.00 | 01-MAR-00:10 | 111837.20 | 01-MAR-09:09 | 0.00 | 33024.78 | 31-MAR-15:30 | 342.72 | 01-MAR-00:10 | 111095.57 | 06-MAR-05:10 |
April | 36851.39 | 03-APR-06:10 | 0.00 | 8375.00 | 01-APR-00:10 | 111837.20 | 03-APR-08:09 | 0.00 | 38219.47 | 20-APR-15:30 | 342.72 | 01-APR-00:10 | 106298.47 | 10-APR-04:10 |
May | 36851.39 | 01-MAY-06:10 | 0.00 | 8375.00 | 01-MAY-00:10 | 111837.20 | 01-MAY-08:09 | 0.00 | 53368.38 | 19-MAY-16:30 | 342.72 | 01-MAY-00:10 | 93590.49 | 15-MAY-04:10 |
June | 36851.39 | 01-JUN-06:10 | 0.00 | 8375.00 | 01-JUN-00:10 | 111837.20 | 01-JUN-08:09 | 0.00 | 53381.38 | 09-JUN-14:20 | 342.72 | 01-JUN-00:10 | 68881.68 | 26-JUN-04:10 |
July | 36851.39 | 03-JUL-06:10 | 0.00 | 8375.00 | 01-JUL-00:10 | 111837.20 | 03-JUL-08:09 | 0.00 | 53381.38 | 12-JUL-15:20 | 342.72 | 01-JUL-00:10 | 65531.60 | 05-JUL-04:10 |
August | 36851.39 | 01-AUG-06:10 | 0.00 | 8375.00 | 01-AUG-00:10 | 111837.20 | 01-AUG-08:09 | 0.00 | 53381.38 | 01-AUG-14:39 | 342.72 | 01-AUG-00:10 | 60055.44 | 06-AUG-14:00 |
September | 36851.39 | 01-SEP-06:10 | 0.00 | 8375.00 | 01-SEP-00:10 | 111837.20 | 01-SEP-08:09 | 0.00 | 53367.45 | 07-SEP-16:10 | 342.72 | 01-SEP-00:10 | 64072.42 | 05-SEP-04:10 |
October | 36851.39 | 02-OCT-06:10 | 0.00 | 8375.00 | 01-OCT-00:10 | 111837.20 | 02-OCT-08:09 | 0.00 | 43292.92 | 06-OCT-14:00 | 342.72 | 01-OCT-07:10 | 105016.21 | 30-OCT-04:10 |
November | 36851.39 | 01-NOV-06:10 | 0.00 | 8375.00 | 01-NOV-00:10 | 111837.20 | 01-NOV-08:09 | 0.00 | 34203.08 | 02-NOV-14:30 | 342.72 | 01-NOV-00:10 | 111003.65 | 20-NOV-05:10 |
December | 36851.39 | 01-DEC-07:10 | 0.00 | 8375.00 | 01-DEC-00:10 | 111837.20 | 01-DEC-09:09 | 0.00 | 28671.44 | 13-DEC-14:00 | 342.72 | 01-DEC-00:10 | 112065.42 | 11-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 36851.39 | 0.00 | 8375.00 | 111837.20 | 0.00 | 28671.44 | 342.72 | 60055.44 | ||||||
Maximum of Months | 36851.39 | 0.00 | 8375.00 | 111837.20 | 0.00 | 53381.38 | 342.72 | 117672.87 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2015-09-13 14:22:44
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.441035E+12 | 285404.380 | 24-JAN-17:00 | 36851.394 | 111837.204 | 24474.947 | 30234.374 | 58618.290 | 8375.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.409485E+12 | 282647.013 | 27-FEB-14:00 | 36851.394 | 111837.204 | 27942.109 | 7646.233 | 98027.355 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.472695E+12 | 290539.686 | 29-MAR-14:00 | 36851.394 | 111837.204 | 32789.222 | 20536.259 | 79855.554 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.475104E+12 | 381229.328 | 21-APR-15:00 | 36851.394 | 111837.204 | 37245.442 | 39544.860 | 125333.723 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.526649E+12 | 407023.562 | 18-MAY-15:20 | 36851.394 | 111837.204 | 52428.161 | 30396.556 | 140442.968 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.565864E+12 | 420973.220 | 13-JUN-16:00 | 36851.394 | 111837.204 | 53180.559 | 30591.505 | 140442.968 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.606617E+12 | 427411.445 | 20-JUL-15:00 | 36851.394 | 111837.204 | 53381.376 | 29272.871 | 148426.296 | 0.000 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.605357E+12 | 420992.625 | 03-AUG-15:09 | 36851.394 | 111837.204 | 53381.376 | 28800.997 | 151189.075 | 0.000 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.514094E+12 | 404666.984 | 20-SEP-15:20 | 36851.394 | 111837.204 | 53290.474 | 30106.492 | 141127.052 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.497106E+12 | 381499.748 | 10-OCT-13:39 | 36851.394 | 111837.204 | 37881.320 | 42359.076 | 130803.855 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.462912E+12 | 318558.505 | 03-NOV-14:00 | 36851.394 | 111837.204 | 33753.523 | 20229.652 | 93304.832 | 0.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.422101E+12 | 278865.318 | 13-DEC-17:10 | 36851.394 | 111837.204 | 25016.802 | 30124.790 | 50904.992 | 8375.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.599902E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.409485E+12 | 278865.318 | 36851.394 | 111837.204 | 24474.947 | 7646.233 | 50904.992 | 0.000 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.606617E+12 | 427411.445 | 36851.394 | 111837.204 | 53381.376 | 42359.076 | 151189.075 | 8375.000 | 342.720 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2015-09-13 14:22:44
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.732316E+11 | 81081.054 | 09-JAN-05:30 | 0.000 | 4952.884 | 0.000 | 76128.170 | 1488.000 | 1488.000 | 74640.170 |
February | 0.645020E+11 | 70181.282 | 09-FEB-06:49 | 0.000 | 9905.768 | 0.000 | 60275.514 | 1488.000 | 1488.000 | 58787.514 |
March | 0.699540E+11 | 63347.060 | 11-MAR-05:30 | 0.000 | 2971.730 | 0.000 | 60375.330 | 1488.000 | 1488.000 | 58887.330 |
April | 0.641827E+11 | 67868.889 | 10-APR-04:40 | 0.000 | 4952.884 | 0.000 | 62916.004 | 1488.000 | 1488.000 | 61428.004 |
May | 0.612310E+11 | 59771.781 | 01-MAY-04:30 | 0.000 | 4952.884 | 0.000 | 54818.896 | 1488.000 | 1488.000 | 53330.896 |
June | 0.485804E+11 | 48077.658 | 05-JUN-04:30 | 0.000 | 4952.884 | 0.000 | 43124.774 | 1488.000 | 1488.000 | 41636.774 |
July | 0.405655E+11 | 42954.659 | 28-JUL-04:30 | 0.000 | 4952.884 | 0.000 | 38001.775 | 1488.000 | 1488.000 | 36513.775 |
August | 0.464535E+11 | 46923.663 | 21-AUG-04:30 | 0.000 | 4952.884 | 0.000 | 41970.779 | 1488.000 | 1488.000 | 40482.779 |
September | 0.570137E+11 | 51828.944 | 25-SEP-04:30 | 0.000 | 4952.884 | 0.000 | 46876.060 | 1488.000 | 1488.000 | 45388.060 |
October | 0.613715E+11 | 58929.468 | 23-OCT-04:19 | 0.000 | 4952.884 | 0.000 | 53976.584 | 1488.000 | 1488.000 | 52488.584 |
November | 0.599798E+11 | 63760.275 | 06-NOV-05:30 | 0.000 | 4952.884 | 0.000 | 58807.391 | 1488.000 | 1488.000 | 57319.391 |
December | 0.844241E+11 | 80941.359 | 30-DEC-06:19 | 0.000 | 2971.730 | 0.000 | 77969.628 | 1488.000 | 1488.000 | 76481.628 |
Annual Sum or Average | 0.731490E+12 | 0.000 | 0.000 | |||||||
Minimum of Months | 0.405655E+11 | 42954.659 | 0.000 | 2971.730 | 0.000 | 38001.775 | 1488.000 | 1488.000 | 36513.775 | |
Maximum of Months | 0.844241E+11 | 81081.054 | 0.000 | 9905.768 | 0.000 | 77969.628 | 1488.000 | 1488.000 | 76481.628 |