Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:44
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:44:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10772.98 | 949.56 | 949.56 |
Net Site Energy | 10772.98 | 949.56 | 949.56 |
Total Source Energy | 24352.35 | 2146.47 | 2146.47 |
Net Source Energy | 24352.35 | 2146.47 | 2146.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 771.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1250.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 911.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 245.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.19 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 981.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 568.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 71.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 245.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2127.54 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 61.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 6084.70 | 4688.28 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 771.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1250.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 911.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 245.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 31.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 568.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 71.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 245.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.75 | 2127.54 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 101.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 174.57 | 255.56 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 259.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 536.32 | 413.24 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 101.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 174.57 | 255.56 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 259.76 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 536.32 | 413.24 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 6084.704 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 6084.704 | 100.00 |
Total On-Site and Utility Electric Sources | 6084.704 | 100.00 |
Total Electricity End Uses | 6084.704 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 792.52 | 20.60 |
Air to Air Heat Recovery for Heating | 3055.19 | 79.40 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3847.71 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 7.33 |
Time Setpoint Not Met During Occupied Cooling | 490.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7538.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:44 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.8264 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 13.5625 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 13.5625 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 6.7813 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 6.4583 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 9.5799 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 11.4097 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7952 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7952 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7952 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 9.7952 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7952 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 9.7952 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 9.7952 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 9.7952 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 9.7952 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 9.5799 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 9.5799 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 13.0243 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 7.1042 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 9.3646 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 9.3646 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-19:10 | 14-JAN-17:19 | - | - | - | 20-APR-20:49 |
Heating | 0.00 | 198062.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 195571.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 83314.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 15665.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 89612.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50828.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 26085.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3800.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3529.89 | 172843.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1869.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 477311.61 | 460517.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 198062.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 195571.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 83314.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 15665.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 14636.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1789.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 26085.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3800.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3529.89 | 172843.42 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 535.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1092.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 836.73 | 0.00 | 0.00 | 0.00 |
Cooling | 3959.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2885.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 778.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.48 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3108.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1800.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 225.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 777.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 2306.25 | 0.00 | 0.00 | 0.00 |
Refrigeration | 195.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 19270.26 | 5082.09 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.75 | 0.00 | 0.00 | 0.00 |
Cooling | 348.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 254.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 274.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 203.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1698.53 | 447.95 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 73.75 | 0.00 | 0.00 | 0.00 |
Cooling | 348.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 254.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 68.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 274.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 158.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 68.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 203.28 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1698.53 | 447.95 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.48 | 0.608579 | 0.580000 | 1.44 | 1.00 | 0.500000 | 0.000626 | 0.000168 | 1.44 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.317449 | 0.160997 | 0.580000 | 0.184121 | 0.580000 | 0.500000 | 0.002367 | 0.000093 | 0.184121 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.235540 | 0.251268 | 0.580000 | 0.136613 | 0.670047 | 0.500000 | 0.001516 | 0.000036 | 0.136613 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.226726 | 0.552002 | 0.580000 | 0.131501 | 1.00 | 0.500000 | 0.000690 | 0.000050 | 0.131501 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.110216 | 0.655139 | 0.580000 | 0.063925 | 1.00 | 0.500000 | 0.000582 | 0.000034 | 0.063925 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.26 | 0.072319 | 0.580000 | 1.89 | 0.580000 | 0.500000 | 0.020906 | 0.000267 | 1.89 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.28 | 0.112804 | 0.580000 | 0.739949 | 0.580000 | 0.500000 | 0.003378 | 0.000272 | 0.739949 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.58 | 0.217535 | 0.580000 | 2.66 | 0.580094 | 0.500000 | 0.001751 | 0.000703 | 2.66 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.580000 | 0.688405 | 1.00 | 0.500000 | 0.000381 | 0.000287 | 0.688405 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.06 | 0.122396 | 0.580000 | 1.20 | 0.580000 | 0.500000 | 0.003113 | 0.000270 | 1.20 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.17 | 0.116652 | 0.580000 | 1.26 | 0.580000 | 0.500000 | 0.003266 | 0.000280 | 1.26 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.25 | 0.700000 | 0.580000 | 1.30 | 0.580000 | 0.500000 | 0.010888 | 0.000193 | 1.30 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.613039 | 0.512266 | 0.580000 | 0.355563 | 1.00 | 0.500000 | 0.000744 | 0.000178 | 0.355563 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7584.04 | 0.000168 | 134.20 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4218.71 | 0.000093 | 87.22 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1628.80 | 0.000036 | 31.03 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2268.59 | 0.000050 | 45.03 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1541.98 | 0.000034 | 32.18 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12082.81 | 0.000267 | 216.36 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 12325.88 | 0.000272 | 243.72 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 31805.17 | 0.000703 | 606.15 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 6132.89 | 0.000135 | 139.63 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 6153.57 | 0.000136 | 140.10 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 34814.30 | 0.000769 | 792.61 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 35219.04 | 0.000778 | 801.83 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 6093.07 | 0.000135 | 138.72 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 6113.69 | 0.000135 | 139.19 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13001.14 | 0.000287 | 260.92 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1844.05 | 0.000041 | 41.98 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1854.22 | 0.000041 | 42.21 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 8781.88 | 0.000194 | 199.93 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 12232.33 | 0.000270 | 228.51 |
DINING_FLR_6 VAV BOX REHEAT COIL | 12665.34 | 0.000280 | 236.23 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8754.67 | 0.000193 | 157.31 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8054.90 | 0.000178 | 166.20 |
VAV WITH REHEAT_HEATC | 203929.56 | 0.004506 | 2861.81 |
FLR_3_DOAS_HEATC | 20392.24 | 0.000451 | 286.17 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.11 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.10 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 6.09 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 6.41 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 1.01 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 1.00 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.292651 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.287932 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.18 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.11 | 0.000135 | 0.000455 |
ROOM_2_FLR_3 FAN COIL | 1.10 | 0.000136 | 0.000448 |
ROOM_3_MULT19_FLR_3 FAN COIL | 6.09 | 0.000769 | 0.002443 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.41 | 0.000778 | 0.002716 |
ROOM_5_FLR_3 FAN COIL | 1.01 | 0.000135 | 0.000414 |
ROOM_6_FLR_3 FAN COIL | 1.00 | 0.000135 | 0.000411 |
ROOM_1_FLR_6 FAN COIL | 0.292651 | 0.000041 | 0.000119 |
ROOM_2_FLR_6 FAN COIL | 0.287932 | 0.000041 | 0.000117 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.18 | 0.000194 | 0.000493 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.11 |
ROOM_2_FLR_3 FAN COILFAN | 1.10 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 6.09 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 6.41 |
ROOM_5_FLR_3 FAN COILFAN | 1.01 |
ROOM_6_FLR_3 FAN COILFAN | 1.00 |
ROOM_1_FLR_6 FAN COILFAN | 0.292651 |
ROOM_2_FLR_6 FAN COILFAN | 0.287932 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.18 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000455 | 1.11 | 0.008670 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000448 | 1.10 | 0.008673 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.002443 | 6.09 | 0.008602 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002716 | 6.41 | 0.008813 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000414 | 1.01 | 0.008689 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000411 | 1.00 | 0.008690 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000119 | 0.292651 | 0.008662 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000117 | 0.287932 | 0.008665 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000493 | 1.18 | 0.008752 | 21.68 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.024507 | 0.012276 | 28.75 | 6.70 | 10.99 | 0.008281 | 686141.74 | 20.51 | |
FLR_3_DOAS_COOLC | 0.003079 | 0.014097 | 32.10 | 6.70 | 10.99 | 0.008281 | 86208.04 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 12.05 | 12.05 | 20.77 | 12.05 | 20.51 | 20.51 | 0.300000 | 0.587261 | 20.51 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 20.51 | 12.05 |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 12.05 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 20.51 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.024507 | 0.000019 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.004506 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.003079 | 0.000155 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000451 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.035203 | 6733.85 |
HEATSYS1 PUMP | 0.010152 | 2593.69 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.010152 | 1.22 |
COOLSYS1 | 0.035203 | 4.22 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.035203 | 2244.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 459492.86 | 459492.86 | 0.010152 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.035203 | 985583.23 | 986168.01 | 112.42 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.826 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.206 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 13.563 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 24.323 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 10.226 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.606 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 6.781 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 9.471 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 6.458 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 603.988 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 9.580 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 14.960 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 11.410 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.480 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 9.795 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 16.545 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 9.795 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 20.315 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.580 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.400 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 9.580 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 77.400 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 13.024 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2947.512 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 17465.960 | 8.826 | 164.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 17465.960 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 909.657 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 909.657 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1053.386 | 13.563 | 84.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1053.386 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1679.504 | 10.226 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1679.504 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 642.588 | 6.781 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 642.588 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 504.006 | 6.458 | 60.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 504.006 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1809.274 | 9.580 | 12.715 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1809.274 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 14926.070 | 11.410 | 35.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14926.070 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 240.215 | 9.795 | 160.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.215 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 240.281 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.281 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2766.401 | 7.104 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.401 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 382.227 | 9.795 | 254.818 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.227 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 382.182 | 9.795 | 254.788 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 382.182 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 240.281 | 9.795 | 160.187 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 240.281 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 3177.239 | 9.580 | 12.714 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3177.239 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 3177.239 | 9.580 | 12.714 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 3177.239 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1345.472 | 13.024 | 60.503 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1345.472 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2927.809 | 7.104 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.809 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 2.841 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3522 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3520 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.8390000 | 2.8390000 | 2.8390000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 2.8409091 | 2.8409091 | 2.8409091 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
25 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
26 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
27 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
28 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
29 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
30 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
31 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
32 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
33 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
34 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
35 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
36 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
37 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
38 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
39 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
40 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
41 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
42 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
43 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
44 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
45 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
46 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
47 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
48 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
49 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
59 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
60 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
61 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
62 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
63 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
64 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
65 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
66 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
67 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
68 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
69 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
70 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
71 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
72 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
73 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
74 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
75 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
76 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
77 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
78 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
79 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
80 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
81 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
82 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
83 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
84 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
85 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
86 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
87 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
88 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
89 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.42_SHGC_0.4 | 31 | 1 | VerySmooth | 2.387 | 0.394 | 0.315 | 0.441 |
2 | RESWINDOW_U_0.42_SHGC_0.4 | 32 | 1 | VerySmooth | 2.387 | 0.394 | 0.315 | 0.441 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.02786E-002 | 0.31435 | 0.47495 | 0.47495 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.12239 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 34084.80891 | 34084.80891 | 2.47769 | 2.47769 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 29.21400 | 1.40969E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 4366.17699 | 4366.17699 | 0.31745 | 0.31745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 3248.85005 | 3248.85005 | 0.13931 | 0.13931 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3239.83463 | 3239.83463 | 0.23554 | 0.23554 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.40969E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 908.75252 | 908.75252 | 3.89694E-002 | 9.16993E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 3119.32779 | 3119.32779 | 0.22673 | 0.22673 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 31.45867 | 1.40969E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1575.69378 | 1575.69378 | 6.75692E-002 | 6.75692E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1516.35450 | 1516.35450 | 0.11022 | 0.11022 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.40969E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1205.11889 | 1205.11889 | 5.16779E-002 | 5.77430E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44885.37211 | 44885.37211 | 3.26294 | 3.26294 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2112.62157 | 2112.62157 | 9.05901E-002 | 0.23597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 78.03947 | 8.40000 | 0.23597 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17532.77808 | 17532.77808 | 1.27577 | 1.27577 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.40969E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 8427.94834 | 8427.94834 | 0.36138 | 0.67613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 63012.98538 | 63012.98538 | 4.58242 | 4.58242 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 17800.54581 | 17800.54581 | 0.76332 | 1.89326 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11367.56815 | 11367.56815 | 1.11355 | 1.11355 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 6132.97118 | 6132.97118 | 0.26453 | 0.26453 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11193.29832 | 11193.29832 | 1.09648 | 1.09648 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 6153.65785 | 6153.65785 | 0.26542 | 0.26542 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 62203.68722 | 62203.68722 | 6.09290 | 6.09290 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 34814.79483 | 34814.79483 | 1.50170 | 1.50170 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 65391.84264 | 65391.84264 | 6.40567 | 6.40567 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.40969E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 35219.53825 | 35219.53825 | 1.51915 | 1.51915 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10302.43529 | 10302.43529 | 1.00922 | 1.00922 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.40969E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 6093.15197 | 6093.15197 | 0.26281 | 0.26281 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10222.17338 | 10222.17338 | 1.00135 | 1.00135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 6113.77528 | 6113.77528 | 0.26370 | 0.26370 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 14440.79236 | 14440.79236 | 1.04960 | 1.18691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 31.80400 | 1.40969E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 9371.24396 | 9371.24396 | 0.40187 | 0.47458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2987.49796 | 2987.49796 | 0.29265 | 0.29265 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1844.07022 | 1844.07022 | 7.95395E-002 | 7.95395E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2939.32221 | 2939.32221 | 0.28793 | 0.28793 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1854.24552 | 1854.24552 | 7.99784E-002 | 7.99784E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 12059.27269 | 12059.27269 | 1.18133 | 1.18133 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 8781.97557 | 8781.97557 | 0.37879 | 0.37879 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | -10.70000 | 1.50390E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 28369.78069 | 28369.78069 | 2.06479 | 2.06479 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 5916.83875 | 5916.83875 | 0.25373 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 29767.23234 | 29767.23234 | 2.16647 | 2.16647 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.40969E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 6038.86521 | 6038.86521 | 0.25896 | 1.18734 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | -10.70000 | 1.50390E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30865.75163 | 30865.75163 | 2.24956 | 2.24956 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.40969E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 1898.02419 | 1898.02419 | 8.13782E-002 | 0.36721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 8434.35789 | 8434.35789 | 0.61304 | 0.61304 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 32.10000 | 1.40969E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 6179.59507 | 6179.59507 | 0.26500 | 0.26500 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -10.70000 | 1.50390E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 395776.87 | 20.51271 | 20.51271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 248449.36 | 7.49725 | 7.49725 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 47879.59 | 17.68034 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 67974.13 | 4.61562 | 2.05120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.47769 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.60858 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.43706 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.26048E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67560E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.43706 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7584.03886 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67560E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 134.20318 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31745 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16100 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18412 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36650E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.32072E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18412 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4218.70633 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.32072E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 87.22295 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.23554 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25127 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13661 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67005 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51631E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.59862E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13661 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1628.79513 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.59862E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.02608 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22673 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55200 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.13150 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.90215E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.01217E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.13150 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2268.58861 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.01217E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 45.02621 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.11022 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.65514 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 6.39251E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.81556E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.40683E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.39251E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1541.98467 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.40683E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 32.18396 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.26294 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.23194E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89250 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.09057E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.66955E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89250 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12082.81168 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66955E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.35509 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27577 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11280 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73995 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37753E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72325E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73995 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12325.88075 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72325E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 243.71715 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.58242 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21754 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.65780 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58009 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75144E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.02696E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.65780 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31805.17188 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.02696E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 606.15067 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.11355 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.11355 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.11355 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.35499E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.54709E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.54709E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.11355 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67030E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68267 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6132.88682 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35499E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 139.62758 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09648 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.09648 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.09648 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.35956E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.48071E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.48071E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.09648 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.67307E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68267 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6153.57319 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35956E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 140.09846 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.09290 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.09290 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 6.09290 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.69179E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.44282E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.44282E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 6.09290 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.60215E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68340 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 34814.29892 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.69179E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 792.61318 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.40567 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.40567 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 6.40567 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 7.78122E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.71574E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.71574E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 6.40567 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.81330E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68256 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 35219.03696 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.78122E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 801.82617 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00922 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.00922 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.00922 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.34619E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.14160E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.14160E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.00922 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68895E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68264 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6093.06813 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.34619E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 138.72121 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00135 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.00135 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.00135 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.35075E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.11087E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.11087E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.00135 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69036E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68263 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 6113.69113 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35075E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 139.19064 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68841 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.87244E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68841 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13001.13841 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.87244E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 260.91799 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29265 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29265 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.29265 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.07419E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.19245E-004 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.19245E-004 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.29265 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.66225E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68269 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1844.04562 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.07419E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 41.98206 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.28793 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.28793 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.28793 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.09667E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.17409E-004 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.17409E-004 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.28793 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.66502E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68269 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1854.22078 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.09667E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 42.21367 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.18133 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.18133 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.18133 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.94025E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 4.92960E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 4.92960E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.18133 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.75232E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.68247 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 8781.88242 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.94025E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 199.93012 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.06479 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12240 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.19758 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11284E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70258E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.19758 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12232.33378 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70258E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 228.50611 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.16647 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11665 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.25655 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.26612E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79825E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.25655 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12665.33627 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79825E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 236.23313 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.24956 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.30475 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58000 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08880E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.93424E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30475 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8754.67284 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.93424E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 157.31244 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61304 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51227 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58000 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35556 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.43754E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77963E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35556 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8054.90260 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77963E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 166.20223 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 12.04632 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.04632 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.76952 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 12.04632 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 20.51271 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 20.51271 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.58726 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 20.51271 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 20.51271 |
346 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 12.05026 |
347 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 12.05026 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 686141.73880 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.45074E-002 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 20.51271 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.22765E-002 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.75393 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.98849 |
355 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 203929.55784 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.50557E-003 |
358 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 2861.81367 |
359 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 20.51271 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.45074E-002 |
361 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.94305E-005 |
362 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50557E-003 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
365 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 86208.04375 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 3.07915E-003 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.40969E-002 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 32.10000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.99443 |
373 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 20392.24032 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 4.50542E-004 |
376 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 286.17133 |
377 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.07915E-003 |
379 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.54650E-004 |
380 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.50542E-004 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 3.52027E-002 |
382 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 6733.84611 |
383 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
384 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
386 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
387 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
388 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.01519E-002 |
389 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.21823 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.01519E-002 |
391 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 2593.68879 |
392 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 459492.86394 |
393 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 459492.86000 |
394 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.01519E-002 |
395 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 3.52027E-002 |
396 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 4.22433 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 3.52027E-002 |
398 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 2244.61537 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 3.52027E-002 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 985583.22705 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 986168.01000 |
402 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 112.42315 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7627.55 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 4244.20 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1637.33 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2282.87 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1551.10 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12151.27 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 12404.83 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 31971.76 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 6617.78 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 6640.10 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 37566.87 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 38003.55 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 6574.82 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 6597.07 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 13081.87 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 1989.80 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2000.77 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 9475.98 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 12298.93 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 12734.37 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 8804.09 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 8103.65 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 144678.54 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 14467.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 18709.73 | 15068.19 | 3641.53 | 0.81 | 2096.59 | 21.26 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 18431.78 | 14841.64 | 3590.14 | 0.81 | 2065.33 | 20.95 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 101157.37 | 81838.07 | 19319.30 | 0.81 | 11351.65 | 115.13 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 110261.57 | 87995.36 | 22266.21 | 0.80 | 12323.60 | 124.99 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 17011.46 | 13683.76 | 3327.69 | 0.80 | 1905.58 | 19.33 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 16883.02 | 13579.21 | 3303.81 | 0.80 | 1891.14 | 19.18 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4910.21 | 3956.61 | 953.60 | 0.81 | 550.32 | 5.58 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4833.36 | 3893.97 | 939.38 | 0.81 | 541.68 | 5.49 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 20128.63 | 16125.39 | 4003.24 | 0.80 | 2252.08 | 22.84 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 657123.52 | 427120.57 | 230002.95 | 0.65 | 96370.74 | 977.45 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67743.86 | 43600.34 | 24143.52 | 0.64 | 9176.64 | 93.07 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.419 | 0.394 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.42_SHGC_0.4 | N/A | 2.387 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.6838521619E-002 | 2.1802768393E-002 | Pass | Pass | 2.4517096786E-003 | 4.0002901962E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6724804853E-003 | 1.5042018450E-002 | Pass | Pass | 0.2038169638 | 0.6695769622 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.0897199686E-003 | 1.8240270365E-002 | Pass | Pass | 2.2941311592E-002 | 4.7302003549E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1174831035E-004 | 4.6788222084E-004 | Pass | Pass | 0.5741854700 | 2.3113110157 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.8523405965E-004 | 4.6145985296E-004 | Pass | Pass | 1.8531241767E-002 | 2.2152545339E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.5653637057E-002 | 0.2236163486 | Pass | Pass | 1.8432397894E-002 | 5.0232991787E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9519282468E-002 | 6.9851720139E-002 | Pass | Pass | 9.8692181047E-002 | 0.1967366447 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7575288849E-002 | 3.9313170295E-002 | Pass | Pass | 1.8602406096E-002 | 4.7885526226E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.3947494126E-002 | 0.2964995253 | Pass | Pass | 0.5588883353 | 3.1061972671 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2647860218E-002 | 0.3115591596 | Pass | Pass | 0.2603804093 | 1.3311532386 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.1660776958E-002 | 5.3014643903E-002 | Pass | Pass | 0.2337705120 | 0.7739330268 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.7827709757E-002 | 0.1667374773 | Pass | Pass | 0.1674253394 | 0.6635819279 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 7.5902755575E-002 | 0.2488346421 | Pass | Pass | 0.1995496819 | 0.6819998696 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 8.1782714458E-002 | 0.2757838741 | Pass | Pass | 0.2727606435 | 1.2563049462 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.0010873496E-003 | 6.2033812615E-003 | Pass | Pass | 2.0085041848E-002 | 3.6510065722E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2654050126E-002 | 0.3190295065 | Pass | Pass | 0.2954551747 | 1.3519245229 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2644894256E-002 | 0.3283269825 | Pass | Pass | 0.1290351912 | 0.4343856331 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.5860139524E-002 | 0.2113081296 | Pass | Pass | 0.1597314402 | 0.6458722647 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.0325841463E-002 | 9.5036754417E-002 | Pass | Pass | 7.3093642729E-003 | 1.8399008009E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.5152179379E-002 | 8.3884346300E-002 | Pass | Pass | 7.3967188155E-003 | 1.9074397804E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7121469314E-002 | 0.1250446592 | Pass | Pass | 2.1116346922E-002 | 3.6549423907E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 8.7826677872E-004 | 6.6466640624E-004 | Pass | Pass | 0.1501385284 | 0.4284847487 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.419 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.387 | 0.394 | 0.441 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.387 | 0.394 | 0.441 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.387 | 0.394 | 0.441 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.387 | 0.394 | 0.441 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.387 | 0.394 | 0.441 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.387 | 0.394 | 0.441 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.387 | 0.394 | 0.441 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.387 | 0.394 | 0.441 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.387 | 0.394 | 0.441 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.387 | 0.394 | 0.441 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.387 | 0.394 | 0.441 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.387 | 0.394 | 0.441 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.387 | 0.394 | 0.441 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.394 | 0.441 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.387 | 0.394 | 0.441 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.394 | 0.441 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.387 | 0.394 | 0.441 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.42_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.387 | 0.394 | 0.441 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.387 | 0.394 | 0.441 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.387 | 0.394 | 0.441 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.394 | 0.441 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.387 | 0.394 | 0.441 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.387 | 0.394 | 0.441 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.42_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.387 | 0.394 | 0.441 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.387 | 0.394 | 0.441 | ||||||||||||
North Total or Average | 432.93 | 2.387 | 0.394 | 0.441 | ||||||||||||
Non-North Total or Average | 781.15 | 2.387 | 0.394 | 0.441 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.993 | 2.841 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.992 | 2.839 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.8264 | 1978.83 | 17465.96 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.48 | 168.00 | 52.43 | 0.0000 | Y | 171.88 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 13.5625 | 67.07 | 909.66 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 10.01 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 13.5625 | 77.67 | 1053.39 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 11.59 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 10.2257 | 164.24 | 1679.50 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.48 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 6.7813 | 94.76 | 642.59 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 26.12 | 168.00 | 26.09 | 0.0000 | Y | 3.15 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 6.4583 | 78.04 | 504.01 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 5.55 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 9.5799 | 188.86 | 1809.27 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 39.60 | 0.0000 | Y | 13.45 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 11.4097 | 1308.19 | 14926.07 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 55.41 | 0.0000 | Y | 155.26 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 9.7952 | 156.09 | 1528.91 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 12.24 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 9.7952 | 156.07 | 1528.73 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 12.24 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 9.7952 | 1863.81 | 18256.33 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 146.13 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 9.7952 | 1864.32 | 18261.33 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 146.17 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 9.7952 | 156.09 | 1528.91 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 12.24 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 9.7952 | 156.07 | 1528.73 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 12.24 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 7.1042 | 1557.62 | 11065.61 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 66.04 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 9.7952 | 39.02 | 382.23 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 3.06 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 9.7952 | 39.02 | 382.18 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 3.06 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 9.7952 | 220.77 | 2162.53 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 17.31 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 9.5799 | 331.66 | 3177.24 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 49.31 | 0.0000 | Y | 29.41 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 9.5799 | 331.66 | 3177.24 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 49.31 | 0.0000 | Y | 29.41 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 13.0243 | 103.30 | 1345.47 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 14.81 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 7.1042 | 412.12 | 2927.81 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 17.47 |
Interior Lighting Total | 9.3646 | 11345.29 | 106243.67 | 521.11 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1809.27 | 705.62 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1809.27 | 705.62 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14926.07 | 1044.82 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14926.07 | 1044.82 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3177.24 | 635.45 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3177.24 | 635.45 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3177.24 | 635.45 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 3177.24 | 635.45 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 15665.55 | AstronomicalClock | - | 83.64 | 83.64 | 245.96 | |
Exterior Lighting Total | 15665.55 | 245.96 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 459492.86 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 986168.01 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12730.89 | 18709.73 | 15068.19 | 3641.53 | 0.81 | - | 2096.59 | 21.26 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12545.03 | 18431.78 | 14841.64 | 3590.14 | 0.81 | - | 2065.33 | 20.95 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 68393.78 | 101157.37 | 81838.07 | 19319.30 | 0.81 | - | 11351.65 | 115.13 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 76034.98 | 110261.57 | 87995.36 | 22266.21 | 0.80 | - | 12323.60 | 124.99 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11595.58 | 17011.46 | 13683.76 | 3327.69 | 0.80 | - | 1905.58 | 19.33 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11509.55 | 16883.02 | 13579.21 | 3303.81 | 0.80 | - | 1891.14 | 19.18 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3338.60 | 4910.21 | 3956.61 | 953.60 | 0.81 | - | 550.32 | 5.58 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3287.19 | 4833.36 | 3893.97 | 939.38 | 0.81 | - | 541.68 | 5.49 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 13801.82 | 20128.63 | 16125.39 | 4003.24 | 0.80 | - | 2252.08 | 22.84 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 686141.74 | 657123.52 | 427120.57 | 230002.95 | 0.65 | - | 96370.74 | 977.45 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 86208.04 | 67743.86 | 43600.34 | 24143.52 | 0.64 | - | 9176.64 | 93.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7584.04 | 7627.55 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4218.71 | 4244.20 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1628.80 | 1637.33 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2268.59 | 2282.87 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1541.98 | 1551.10 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12082.81 | 12151.27 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12325.88 | 12404.83 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31805.17 | 31971.76 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6132.89 | 6617.78 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6153.57 | 6640.10 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 34814.30 | 37566.87 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 35219.04 | 38003.55 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6093.07 | 6574.82 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 6113.69 | 6597.07 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13001.14 | 13081.87 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1844.05 | 1989.80 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1854.22 | 2000.77 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 8781.88 | 9475.98 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12232.33 | 12298.93 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 12665.34 | 12734.37 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8754.67 | 8804.09 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 8054.90 | 8103.65 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 203929.56 | 144678.54 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 20392.24 | 14467.35 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | General | |||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.11 | 783.54 | 703.64 | 1.00 | 1.17 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.10 | 771.52 | 703.64 | 1.00 | 1.17 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 6.09 | 4287.19 | 703.64 | 1.00 | 0.96 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 6.41 | 4507.26 | 703.64 | 1.00 | 0.95 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.01 | 710.12 | 703.64 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.00 | 704.59 | 703.64 | 1.00 | 1.20 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 205.92 | 703.64 | 1.00 | 1.73 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.29 | 202.60 | 703.64 | 1.00 | 1.74 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.18 | 831.22 | 703.64 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 20.51 | 45961.57 | 2240.64 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.035203 | 6733.85 | 191287.51 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.010152 | 2593.69 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.035203 | 2244.62 | 63762.50 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 34084.81 | 34084.81 | 17.22 | 2.478 | 2.478 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 24.00 | 24.00 | 0.00921 | 29.21 | 0.01410 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4366.18 | 4366.18 | 65.10 | 0.317 | 0.317 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00933 | 31.85 | 0.01410 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3239.83 | 3239.83 | 41.71 | 0.236 | 0.236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00945 | 31.46 | 0.01410 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44885.37 | 44885.37 | 575.16 | 3.263 | 3.263 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00856 | 32.10 | 0.01410 | 0.236 | 0.00 |
CAFE_FLR_1 | 17532.78 | 17532.78 | 92.83 | 1.276 | 1.276 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01046 | 31.85 | 0.01410 | 0.676 | 0.00 |
LOBBY_FLR_1 | 63012.99 | 63012.99 | 48.17 | 4.582 | 4.582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01010 | 31.92 | 0.01410 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 11367.57 | 11367.57 | 291.31 | 1.114 | 1.114 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00867 | 31.26 | 0.01410 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11193.30 | 11193.30 | 286.88 | 1.096 | 1.096 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00867 | 31.16 | 0.01410 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 62203.69 | 62203.69 | 2536.46 | 6.093 | 6.093 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00860 | 31.92 | 0.01410 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 65391.84 | 65391.84 | 2665.73 | 6.406 | 6.406 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00881 | 32.10 | 0.01410 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10302.44 | 10302.44 | 264.02 | 1.009 | 1.009 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 21.11 | 21.11 | 0.00869 | 28.24 | 0.01410 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10222.17 | 10222.17 | 261.99 | 1.001 | 1.001 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00869 | 28.03 | 0.01410 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2987.50 | 2987.50 | 76.56 | 0.293 | 0.293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 21.11 | 21.11 | 0.00866 | 31.26 | 0.01410 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2939.32 | 2939.32 | 75.33 | 0.288 | 0.288 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 21.11 | 21.11 | 0.00867 | 31.16 | 0.01410 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 12059.27 | 12059.27 | 491.60 | 1.181 | 1.181 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00875 | 31.92 | 0.01410 | 0.099 | 0.00 |
BANQUET_FLR_6 | 28369.78 | 28369.78 | 85.54 | 2.065 | 2.065 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01051 | 32.10 | 0.01410 | 1.187 | 0.00 |
DINING_FLR_6 | 29767.23 | 29767.23 | 89.75 | 2.166 | 2.166 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.98 | 0.01042 | 32.10 | 0.01410 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 30865.75 | 30865.75 | 298.78 | 2.250 | 2.250 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.97 | 0.01010 | 31.43 | 0.01410 | 0.367 | 0.00 |
MECH_FLR_1 | 3119.33 | 3119.33 | 18.99 | 0.227 | 0.227 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 24.00 | 24.00 | 0.00870 | 31.46 | 0.01410 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1516.35 | 1516.35 | 16.00 | 0.110 | 0.110 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00878 | 32.10 | 0.01410 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 14440.79 | 14440.79 | 37.08 | 1.050 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00864 | 31.80 | 0.01410 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8434.36 | 8434.36 | 20.47 | 0.613 | 0.613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00860 | 32.10 | 0.01410 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 3248.85 | 3248.85 | 48.44 | 0.139 | 0.139 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00713 | -10.70 | 0.00150 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 908.75 | 908.75 | 11.70 | 0.039 | 0.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00732 | -10.70 | 0.00150 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2112.62 | 2112.62 | 27.07 | 0.091 | 0.236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00714 | -10.70 | 0.00150 | 0.236 | 0.00 |
CAFE_FLR_1 | 8427.95 | 8427.95 | 44.62 | 0.361 | 0.676 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00715 | -10.70 | 0.00150 | 0.676 | 0.00 |
LOBBY_FLR_1 | 17800.55 | 17800.55 | 13.61 | 0.763 | 1.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00719 | -10.70 | 0.00150 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 6132.97 | 6132.97 | 157.17 | 0.265 | 0.265 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00743 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 6153.66 | 6153.66 | 157.72 | 0.265 | 0.265 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00743 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 34814.79 | 34814.79 | 1419.63 | 1.502 | 1.502 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 35219.54 | 35219.54 | 1435.74 | 1.519 | 1.519 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00747 | -10.70 | 0.00150 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 6093.15 | 6093.15 | 156.15 | 0.263 | 0.263 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00743 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 6113.78 | 6113.78 | 156.69 | 0.264 | 0.264 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00743 | -10.70 | 0.00150 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1844.07 | 1844.07 | 47.26 | 0.080 | 0.080 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00752 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1854.25 | 1854.25 | 47.52 | 0.080 | 0.080 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00752 | -10.70 | 0.00150 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 8781.98 | 8781.98 | 358.00 | 0.379 | 0.379 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 21.11 | 21.11 | 0.00754 | -10.70 | 0.00150 | 0.099 | 0.00 |
BANQUET_FLR_6 | 5916.84 | 5916.84 | 17.84 | 0.254 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 1.187 | 0.00 |
DINING_FLR_6 | 6038.87 | 6038.87 | 18.21 | 0.259 | 1.187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 21.00 | 21.00 | 0.00763 | -10.70 | 0.00150 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 1898.02 | 1898.02 | 18.37 | 0.081 | 0.367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00615 | -10.70 | 0.00150 | 0.367 | 0.00 |
MECH_FLR_1 | 1575.69 | 1575.69 | 9.59 | 0.068 | 0.068 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00717 | -10.70 | 0.00150 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1205.12 | 1205.12 | 12.72 | 0.052 | 0.058 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00723 | -10.70 | 0.00150 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 9371.24 | 9371.24 | 24.07 | 0.402 | 0.475 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 6179.60 | 6179.60 | 14.99 | 0.265 | 0.265 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00768 | -10.70 | 0.00150 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 20.51 | 20.51 | 7.50 | 7.50 | 20.5127 | 12.0463 | 20.5127 | 0.5873 | 0.3000 |
FLR_3_DOAS | 17.68 | 2.05 | 4.62 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7584.039 | 7584.039 | 1.437058 | 0.00016756 | 134.203 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7627.55 | 7584.04 | 1.437058 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7629.02 | 7629.02 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 4218.706 | 4218.706 | 0.184121 | 0.00009321 | 87.223 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4244.20 | 4218.71 | 0.184121 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00713013 | 46.1394 | 3248.85 | 0.00 | 4246.45 | 4246.45 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1628.795 | 1628.795 | 0.136613 | 0.00003599 | 31.026 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1637.33 | 1628.80 | 0.136613 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00732465 | 47.3805 | 908.75 | 0.00 | 1638.07 | 1638.07 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2268.589 | 2268.589 | 0.131501 | 0.00005012 | 45.026 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2282.87 | 2268.59 | 0.131501 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716572 | 46.3642 | 1575.69 | 0.00 | 2283.68 | 2283.68 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1541.985 | 1541.985 | 0.063925 | 0.00003407 | 32.184 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1551.10 | 1541.98 | 0.063925 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00723271 | 46.7928 | 1205.12 | 0.00 | 1551.98 | 1551.98 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12082.812 | 12082.812 | 1.892505 | 0.00026695 | 216.355 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12151.27 | 12082.81 | 1.892505 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00713587 | 46.1746 | 2112.62 | 0.00 | 12154.11 | 12154.11 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 12325.881 | 12325.881 | 0.739949 | 0.00027233 | 243.717 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12404.83 | 12325.88 | 0.739949 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00715068 | 46.2706 | 8427.95 | 0.00 | 12409.00 | 12409.00 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 31805.172 | 31805.172 | 2.657805 | 0.00070270 | 606.151 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31971.76 | 31805.17 | 2.657805 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00719201 | 46.5326 | 17800.55 | 0.00 | 31986.16 | 31986.16 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12730.893 | -999.000 | 1.113552 | 0.00045471 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 12730.89 | 12217.55 | 1.113552 | 21.68 | 15.69 | 0.00867030 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01409687 | 22.87 | 0.0000 | 21.11 | 0.00867030 | 55.5873 | 11367.57 | 0.00 | 12751.92 | 12051.46 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 6132.887 | 6132.887 | 0.264531 | 0.00013550 | 139.628 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6617.78 | 6132.89 | 0.264531 | 21.11 | 14.35 | 0.00743236 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00743236 | 47.7444 | 6132.97 | 0.00 | 6620.63 | 6620.63 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12545.034 | -999.000 | 1.096481 | 0.00044807 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 12545.03 | 12031.27 | 1.096481 | 21.68 | 15.69 | 0.00867307 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00867307 | 55.6048 | 11193.30 | 0.00 | 12565.74 | 11868.16 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 6153.573 | 6153.573 | 0.265423 | 0.00013596 | 140.098 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6640.10 | 6153.57 | 0.265423 | 21.11 | 14.35 | 0.00743415 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00743415 | 47.7557 | 6153.66 | 0.00 | 6642.96 | 6642.96 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 68393.781 | -999.000 | 6.092900 | 0.00244282 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 68393.78 | 66712.49 | 6.092900 | 21.68 | 15.63 | 0.00860215 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01409688 | 23.05 | 0.0000 | 21.11 | 0.00860215 | 55.1541 | 62203.69 | 0.00 | 68509.03 | 65743.38 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 34814.299 | 34814.299 | 1.501696 | 0.00076918 | 792.613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37566.87 | 34814.30 | 1.501696 | 21.11 | 14.38 | 0.00746683 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00746683 | 47.9615 | 34814.79 | 0.00 | 37583.41 | 37583.41 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 76034.977 | -999.000 | 6.405666 | 0.00271574 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 76034.98 | 70579.04 | 6.405666 | 21.68 | 15.81 | 0.00881330 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | 0.0000 | 21.11 | 0.00881330 | 56.4912 | 65391.84 | 0.00 | 76155.76 | 69751.04 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 35219.037 | 35219.037 | 1.519154 | 0.00077812 | 801.826 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 38003.55 | 35219.04 | 1.519154 | 21.11 | 14.39 | 0.00747233 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00747233 | 47.9964 | 35219.54 | 0.00 | 38020.34 | 38020.34 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11595.581 | -999.000 | 1.009215 | 0.00041416 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | 7/21 09:10:00 | 11595.58 | 11079.08 | 1.009215 | 21.68 | 15.70 | 0.00868895 | 12.80 | 12.09 | 0.00850000 | 28.24 | 0.01409687 | 22.02 | 0.0000 | 21.11 | 0.00868895 | 55.7053 | 10302.44 | 0.00 | 11614.63 | 10931.23 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 6093.068 | 6093.068 | 0.262813 | 0.00013462 | 138.721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6574.82 | 6093.07 | 0.262813 | 21.11 | 14.35 | 0.00742898 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00742898 | 47.7229 | 6093.15 | 0.00 | 6577.65 | 6577.65 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11509.549 | -999.000 | 1.001353 | 0.00041109 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 11509.55 | 10993.23 | 1.001353 | 21.68 | 15.70 | 0.00869036 | 12.80 | 12.09 | 0.00850000 | 28.03 | 0.01409688 | 21.96 | 0.0000 | 21.11 | 0.00869036 | 55.7142 | 10222.17 | 0.00 | 11528.45 | 10846.74 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 6113.691 | 6113.691 | 0.263703 | 0.00013507 | 139.191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6597.07 | 6113.69 | 0.263703 | 21.11 | 14.35 | 0.00743078 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00743078 | 47.7343 | 6113.78 | 0.00 | 6599.91 | 6599.91 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 13001.138 | 13001.138 | 0.688405 | 0.00028724 | 260.918 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13081.87 | 13001.14 | 0.688405 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00753994 | 48.7560 | 9371.24 | 0.00 | 13087.16 | 13087.16 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3338.597 | -999.000 | 0.292651 | 0.00011924 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 3338.60 | 3210.09 | 0.292651 | 21.68 | 15.68 | 0.00866225 | 12.80 | 12.09 | 0.00850000 | 31.26 | 0.01409687 | 22.87 | 0.0000 | 21.11 | 0.00866225 | 55.5364 | 2987.50 | 0.00 | 3344.12 | 3166.10 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1844.046 | 1844.046 | 0.079539 | 0.00004074 | 41.982 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1989.80 | 1844.05 | 0.079539 | 21.11 | 14.43 | 0.00752088 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00752088 | 48.3062 | 1844.07 | 0.00 | 1990.70 | 1990.70 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3287.194 | -999.000 | 0.287932 | 0.00011741 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | 7/21 16:50:00 | 3287.19 | 3158.59 | 0.287932 | 21.68 | 15.68 | 0.00866502 | 12.80 | 12.09 | 0.00850000 | 31.16 | 0.01409687 | 22.84 | 0.0000 | 21.11 | 0.00866502 | 55.5539 | 2939.32 | 0.00 | 3292.63 | 3115.43 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1854.221 | 1854.221 | 0.079978 | 0.00004097 | 42.214 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2000.77 | 1854.22 | 0.079978 | 21.11 | 14.43 | 0.00752336 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00752336 | 48.3219 | 1854.25 | 0.00 | 2001.69 | 2001.69 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13801.821 | -999.000 | 1.181326 | 0.00049296 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 13801.82 | 12992.93 | 1.181326 | 21.68 | 15.76 | 0.00875232 | 12.80 | 12.09 | 0.00850000 | 31.92 | 0.01409688 | 23.05 | 0.0000 | 21.11 | 0.00875232 | 56.1062 | 12059.27 | 0.00 | 13824.10 | 12830.38 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 8781.882 | 8781.882 | 0.378794 | 0.00019402 | 199.930 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 9475.98 | 8781.88 | 0.378794 | 21.11 | 14.45 | 0.00753563 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.11 | 0.00753563 | 48.3993 | 8781.98 | 0.00 | 9480.33 | 9480.33 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12232.334 | 12232.334 | 1.197580 | 0.00027026 | 228.506 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12298.93 | 12232.33 | 1.197580 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00762677 | 49.3112 | 5916.84 | 0.00 | 12303.62 | 12303.62 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12665.336 | 12665.336 | 1.256551 | 0.00027983 | 236.233 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12734.37 | 12665.34 | 1.256551 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00763390 | 49.3569 | 6038.87 | 0.00 | 12739.16 | 12739.16 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 8754.673 | 8754.673 | 1.304747 | 0.00019342 | 157.312 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8804.09 | 8754.67 | 1.304747 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00615167 | 39.8757 | 1898.02 | 0.00 | 8806.26 | 8806.26 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 8054.903 | 8054.903 | 0.355563 | 0.00017796 | 166.202 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 8103.65 | 8054.90 | 0.355563 | 16.70 | 13.18 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00768394 | 49.6761 | 6179.60 | 0.00 | 8107.88 | 8107.88 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 686141.739 | -999.000 | 20.512710 | 0.02450739 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 686141.74 | 437040.33 | 20.512710 | 28.75 | 20.89 | 0.01227645 | 10.99 | 10.99 | 0.00828082 | 32.10 | 0.01409687 | 23.10 | 58.7453 | 23.99 | 0.00952590 | 51.1949 | 281979.37 | 0.00 | 746313.53 | 466497.82 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 203929.558 | 203929.558 | 6.153813 | 0.00450557 | 2861.814 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 144678.54 | 203929.56 | 6.153813 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 195.8178 | 21.00 | 0.00742772 | 48.0400 | 64011.40 | 0.00 | 144508.02 | 144508.02 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 86208.044 | -999.000 | 2.051199 | 0.00307915 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86208.04 | 50755.10 | 2.051199 | 32.10 | 23.10 | 0.01409687 | 10.99 | 12.09 | 0.00828082 | 32.10 | 0.01409687 | 23.10 | 100.0000 | 21.11 | 0.00871028 | 55.8389 | 179877.06 | 0.00 | 92230.31 | 54243.56 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 14467.35 | 20392.24 | 0.615360 | -10.70 | -10.70 | 0.00150390 | 16.70 | 13.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 333.3333 | 21.11 | 0.00746990 | 47.9810 | 107007.72 | 0.00 | 14450.29 | 14450.29 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7584.039 | 7584.039 | 1.437058 | 0.00016756 | 134.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.6272 | 1.650524 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 7627.55 | 7584.04 | 1.0000 | 1.72963607 | 1.437058 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.16754298 | 60.00 | 49.00 | 11.00 | 0.000 | 7627.55 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 7629.02 | 7629.02 | 1.72963607 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4218.706 | 4218.706 | 0.184121 | 0.00009321 | 87.223 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 0.9054 | 0.918122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4244.20 | 4218.71 | 1.0000 | 0.22160667 | 0.184121 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.09319765 | 60.00 | 49.00 | 11.00 | 0.000 | 4244.20 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00713013 | 21.00 | 0.00713013 | 46.1394 | 3248.85 | 0.00 | 4246.45 | 4246.45 | 0.22160667 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.39 | 19.75 | 0.00800000 | 56096.8 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1628.795 | 1628.795 | 0.136613 | 0.00003599 | 31.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 0.3493 | 0.354477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1637.33 | 1628.80 | 1.0000 | 0.16442725 | 0.136613 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03598257 | 60.00 | 49.00 | 11.00 | 0.000 | 1637.33 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00732465 | 21.00 | 0.00732465 | 47.3805 | 908.75 | 0.00 | 1638.07 | 1638.07 | 0.16442725 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.37 | 16.78 | 0.00800000 | 46897.0 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2268.589 | 2268.589 | 0.131501 | 0.00005012 | 45.026 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 0.4870 | 0.493716 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2282.87 | 2268.59 | 1.0000 | 0.15827410 | 0.131501 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.05011658 | 60.00 | 49.00 | 11.00 | 0.000 | 2282.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00716572 | 21.00 | 0.00716572 | 46.3642 | 1575.69 | 0.00 | 2283.68 | 2283.68 | 0.15827410 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 30.75 | 18.26 | 0.00800000 | 51363.4 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1541.985 | 1541.985 | 0.063925 | 0.00003407 | 32.184 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 0.3309 | 0.335584 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1551.10 | 1541.98 | 1.0000 | 0.07693993 | 0.063925 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.03406479 | 60.00 | 49.00 | 11.00 | 0.000 | 1551.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00723271 | 21.00 | 0.00723271 | 46.7928 | 1205.12 | 0.00 | 1551.98 | 1551.98 | 0.07693993 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 36.38 | 20.06 | 0.00800000 | 57106.1 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12082.812 | 12082.812 | 1.892505 | 0.00026695 | 216.355 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 2.5923 | 2.629597 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12151.27 | 12082.81 | 1.0000 | 2.27780896 | 1.892505 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26692773 | 60.00 | 49.00 | 11.00 | 0.000 | 12151.27 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00713587 | 21.00 | 0.00713587 | 46.1746 | 2112.62 | 0.00 | 12154.11 | 12154.11 | 2.27780896 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.83 | 15.15 | 0.00800000 | 42270.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12325.881 | 12325.881 | 0.739949 | 0.00027233 | 243.717 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 2.6464 | 2.682497 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12404.83 | 12325.88 | 1.0000 | 0.89059867 | 0.739949 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27229749 | 60.00 | 49.00 | 11.00 | 0.000 | 12404.83 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00715068 | 21.00 | 0.00715068 | 46.2706 | 8427.95 | 0.00 | 12409.00 | 12409.00 | 0.89059867 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 30.26 | 18.10 | 0.00800000 | 50868.1 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31805.172 | 31805.172 | 2.657805 | 0.00070270 | 606.151 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 6.8208 | 6.921799 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31971.76 | 31805.17 | 1.0000 | 3.19892038 | 2.657805 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.70262473 | 60.00 | 49.00 | 11.00 | 0.000 | 31971.76 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00719201 | 21.00 | 0.00719201 | 46.5326 | 17800.55 | 0.00 | 31986.16 | 31986.16 | 3.19892038 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.41 | 16.79 | 0.00800000 | 46933.8 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12730.893 | -999.000 | 1.113552 | 0.00045471 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9576 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.113552 | 1.34026554 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 1.2917 | 1.291687 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | 12730.89 | 12217.55 | 1.0000 | 1.34026554 | 1.113552 | 21.68 | 15.69 | 0.00867030 | 43821.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.45466311 | 6.70 | 11.72 | 6.67 | 0.000 | 12730.89 | 31.26 | 0.01409687 | 22.87 | 0.00000000 | 0.0000 | 21.11 | 0.00867030 | 21.11 | 0.00867030 | 55.5873 | 11367.57 | 0.00 | 12751.92 | 12051.46 | 1.34026554 | 21.68 | 15.69 | 0.00867030 | 43821.0 | 12.88 | 12.09 | 0.00846330 | 34306.5 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6132.887 | 6132.887 | 0.264531 | 0.00013550 | 139.628 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.113552 | 1.34026554 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.4118 | 1.334708 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6617.78 | 6132.89 | 1.0000 | 0.31838776 | 0.264531 | 21.11 | 14.35 | 0.00743236 | 40091.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13548482 | 60.00 | 49.00 | 11.00 | 0.000 | 6617.78 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00743236 | 21.11 | 0.00743236 | 47.7444 | 6132.97 | 0.00 | 6620.63 | 6620.63 | 0.31838776 | 16.60 | 12.59 | 0.00743236 | 35497.6 | 37.01 | 19.82 | 0.00743236 | 56291.8 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12545.034 | -999.000 | 1.096481 | 0.00044807 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9628 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.096481 | 1.31971880 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 1.2729 | 1.272830 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 12545.03 | 12031.27 | 1.0000 | 1.31971880 | 1.096481 | 21.68 | 15.69 | 0.00867307 | 43828.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.44802547 | 6.70 | 11.72 | 6.67 | 0.000 | 12545.03 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00867307 | 21.11 | 0.00867307 | 55.6048 | 11193.30 | 0.00 | 12565.74 | 11868.16 | 1.31971880 | 21.68 | 15.69 | 0.00867307 | 43828.0 | 12.87 | 12.09 | 0.00846372 | 34306.5 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6153.573 | 6153.573 | 0.265423 | 0.00013596 | 140.098 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.096481 | 1.31971880 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.4166 | 1.339210 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6640.10 | 6153.57 | 1.0000 | 0.31946169 | 0.265423 | 21.11 | 14.35 | 0.00743415 | 40096.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13594181 | 60.00 | 49.00 | 11.00 | 0.000 | 6640.10 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00743415 | 21.11 | 0.00743415 | 47.7557 | 6153.66 | 0.00 | 6642.96 | 6642.96 | 0.31946169 | 16.60 | 12.59 | 0.00743415 | 35502.1 | 37.01 | 19.82 | 0.00743415 | 56296.3 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 68393.781 | -999.000 | 6.092900 | 0.00244282 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8310 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.092900 | 7.33338384 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 6.9394 | 6.939293 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 68393.78 | 66712.49 | 1.0000 | 7.33338384 | 6.092900 | 21.68 | 15.63 | 0.00860215 | 43648.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.44257258 | 6.70 | 11.72 | 6.67 | 0.000 | 68393.78 | 31.92 | 0.01409688 | 23.05 | 0.00000000 | 0.0000 | 21.11 | 0.00860215 | 21.11 | 0.00860215 | 55.1541 | 62203.69 | 0.00 | 68509.03 | 65743.38 | 7.33338384 | 21.68 | 15.63 | 0.00860215 | 43648.6 | 12.90 | 12.09 | 0.00845279 | 34306.5 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34814.299 | 34814.299 | 1.501696 | 0.00076918 | 792.613 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.092900 | 7.33338384 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 8.0144 | 7.576679 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37566.87 | 34814.30 | 1.0000 | 1.80743320 | 1.501696 | 21.11 | 14.38 | 0.00746683 | 40179.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.76910093 | 60.00 | 49.00 | 11.00 | 0.000 | 37566.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00746683 | 21.11 | 0.00746683 | 47.9615 | 34814.79 | 0.00 | 37583.41 | 37583.41 | 1.80743320 | 16.60 | 12.62 | 0.00746683 | 35584.8 | 37.01 | 19.85 | 0.00746683 | 56378.6 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 76034.977 | -999.000 | 6.405666 | 0.00271574 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2235 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.405666 | 7.70982719 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 7.7147 | 7.714575 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 76034.98 | 70579.04 | 1.0000 | 7.70982719 | 6.405666 | 21.68 | 15.81 | 0.00881330 | 44184.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 2.71546547 | 6.70 | 11.72 | 6.67 | 0.000 | 76034.98 | 32.10 | 0.01409687 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00881330 | 21.11 | 0.00881330 | 56.4912 | 65391.84 | 0.00 | 76155.76 | 69751.04 | 7.70982719 | 21.68 | 15.82 | 0.00881330 | 44184.3 | 12.82 | 12.09 | 0.00848428 | 34306.5 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35219.037 | 35219.037 | 1.519154 | 0.00077812 | 801.826 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.405666 | 7.70982719 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 8.1076 | 7.664763 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 38003.55 | 35219.04 | 1.0000 | 1.82844573 | 1.519154 | 21.11 | 14.39 | 0.00747233 | 40193.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.77804221 | 60.00 | 49.00 | 11.00 | 0.000 | 38003.55 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00747233 | 21.11 | 0.00747233 | 47.9964 | 35219.54 | 0.00 | 38020.34 | 38020.34 | 1.82844573 | 16.60 | 12.63 | 0.00747233 | 35598.8 | 37.01 | 19.85 | 0.00747233 | 56392.6 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11595.581 | -999.000 | 1.009215 | 0.00041416 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9923 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.009215 | 1.21468613 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 1.1765 | 1.176498 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | unknown | unknown | unknown | 7/21 09:10:00 | 11595.58 | 11079.08 | 1.0000 | 1.21468613 | 1.009215 | 21.68 | 15.70 | 0.00868895 | 43868.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.41411730 | 6.70 | 11.72 | 6.67 | 0.000 | 11595.58 | 28.24 | 0.01409687 | 22.02 | 0.00000000 | 0.0000 | 21.11 | 0.00868895 | 21.11 | 0.00868895 | 55.7053 | 10302.44 | 0.00 | 11614.63 | 10931.23 | 1.21468613 | 21.68 | 15.71 | 0.00868895 | 43868.3 | 12.87 | 12.09 | 0.00846612 | 34306.5 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6093.068 | 6093.068 | 0.262813 | 0.00013462 | 138.721 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.009215 | 1.21468613 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.4027 | 1.326042 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6574.82 | 6093.07 | 1.0000 | 0.31632058 | 0.262813 | 21.11 | 14.35 | 0.00742898 | 40083.2 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13460516 | 60.00 | 49.00 | 11.00 | 0.000 | 6574.82 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00742898 | 21.11 | 0.00742898 | 47.7229 | 6093.15 | 0.00 | 6577.65 | 6577.65 | 0.31632058 | 16.60 | 12.58 | 0.00742898 | 35489.0 | 37.01 | 19.82 | 0.00742898 | 56283.3 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11509.549 | -999.000 | 1.001353 | 0.00041109 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9949 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.001353 | 1.20522353 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 1.1678 | 1.167769 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 11509.55 | 10993.23 | 1.0000 | 1.20522353 | 1.001353 | 21.68 | 15.70 | 0.00869036 | 43871.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.41104482 | 6.70 | 11.72 | 6.67 | 0.000 | 11509.55 | 28.03 | 0.01409688 | 21.96 | 0.00000000 | 0.0000 | 21.11 | 0.00869036 | 21.11 | 0.00869036 | 55.7142 | 10222.17 | 0.00 | 11528.45 | 10846.74 | 1.20522353 | 21.68 | 15.71 | 0.00869036 | 43871.9 | 12.87 | 12.09 | 0.00846633 | 34306.5 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6113.691 | 6113.691 | 0.263703 | 0.00013507 | 139.191 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.001353 | 1.20522353 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.4074 | 1.330530 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 6597.07 | 6113.69 | 1.0000 | 0.31739122 | 0.263703 | 21.11 | 14.35 | 0.00743078 | 40087.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13506076 | 60.00 | 49.00 | 11.00 | 0.000 | 6597.07 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00743078 | 21.11 | 0.00743078 | 47.7343 | 6113.78 | 0.00 | 6599.91 | 6599.91 | 0.31739122 | 16.60 | 12.58 | 0.00743078 | 35493.6 | 37.01 | 19.82 | 0.00743078 | 56287.8 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13001.138 | 13001.138 | 0.688405 | 0.00028724 | 260.918 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 2.7909 | 2.829454 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13081.87 | 13001.14 | 1.0000 | 0.82856100 | 0.688405 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.28721496 | 60.00 | 49.00 | 11.00 | 0.000 | 13081.87 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00753994 | 21.00 | 0.00753994 | 48.7560 | 9371.24 | 0.00 | 13087.16 | 13087.16 | 0.82856100 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 32.09 | 18.70 | 0.00800000 | 52729.8 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3338.597 | -999.000 | 0.292651 | 0.00011924 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9427 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.292651 | 0.35223336 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 0.3387 | 0.338737 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | 3338.60 | 3210.09 | 1.0000 | 0.35223336 | 0.292651 | 21.68 | 15.68 | 0.00866225 | 43800.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11923255 | 6.70 | 11.72 | 6.67 | 0.000 | 3338.60 | 31.26 | 0.01409687 | 22.87 | 0.00000000 | 0.0000 | 21.11 | 0.00866225 | 21.11 | 0.00866225 | 55.5364 | 2987.50 | 0.00 | 3344.12 | 3166.10 | 0.35223336 | 21.68 | 15.68 | 0.00866225 | 43800.6 | 12.88 | 12.09 | 0.00846208 | 34306.5 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1844.046 | 1844.046 | 0.079539 | 0.00004074 | 41.982 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.292651 | 0.35223336 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 0.4245 | 0.401322 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 1989.80 | 1844.05 | 1.0000 | 0.09573334 | 0.079539 | 21.11 | 14.43 | 0.00752088 | 40316.6 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.04073778 | 60.00 | 49.00 | 11.00 | 0.000 | 1989.80 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752088 | 21.11 | 0.00752088 | 48.3062 | 1844.07 | 0.00 | 1990.70 | 1990.70 | 0.09573334 | 16.60 | 12.67 | 0.00752088 | 35721.7 | 37.01 | 19.89 | 0.00752088 | 56515.9 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3287.194 | -999.000 | 0.287932 | 0.00011741 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9478 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.287932 | 0.34655336 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 0.3335 | 0.333522 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | unknown | unknown | unknown | 7/21 16:50:00 | 3287.19 | 3158.59 | 1.0000 | 0.34655336 | 0.287932 | 21.68 | 15.68 | 0.00866502 | 43807.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.11739677 | 6.70 | 11.72 | 6.67 | 0.000 | 3287.19 | 31.16 | 0.01409687 | 22.84 | 0.00000000 | 0.0000 | 21.11 | 0.00866502 | 21.11 | 0.00866502 | 55.5539 | 2939.32 | 0.00 | 3292.63 | 3115.43 | 0.34655336 | 21.68 | 15.69 | 0.00866502 | 43807.6 | 12.88 | 12.09 | 0.00846250 | 34306.5 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1854.221 | 1854.221 | 0.079978 | 0.00004097 | 42.214 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.287932 | 0.34655336 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 0.4268 | 0.403536 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 2000.77 | 1854.22 | 1.0000 | 0.09626158 | 0.079978 | 21.11 | 14.43 | 0.00752336 | 40322.9 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.04096256 | 60.00 | 49.00 | 11.00 | 0.000 | 2000.77 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00752336 | 21.11 | 0.00752336 | 48.3219 | 1854.25 | 0.00 | 2001.69 | 2001.69 | 0.09626158 | 16.60 | 12.68 | 0.00752336 | 35728.0 | 37.01 | 19.89 | 0.00752336 | 56522.2 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13801.821 | -999.000 | 1.181326 | 0.00049296 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1101 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.181326 | 1.42183814 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 1.4004 | 1.400345 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 13801.82 | 12992.93 | 1.0000 | 1.42183814 | 1.181326 | 21.68 | 15.76 | 0.00875232 | 44029.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | 0.49290957 | 6.70 | 11.72 | 6.67 | 0.000 | 13801.82 | 31.92 | 0.01409688 | 23.05 | 0.00000000 | 0.0000 | 21.11 | 0.00875232 | 21.11 | 0.00875232 | 56.1062 | 12059.27 | 0.00 | 13824.10 | 12830.38 | 1.42183814 | 21.68 | 15.76 | 0.00875232 | 44029.2 | 12.85 | 12.09 | 0.00847551 | 34306.5 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8781.882 | 8781.882 | 0.378794 | 0.00019402 | 199.930 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.181326 | 1.42183814 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 2.0216 | 1.911212 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 9475.98 | 8781.88 | 1.0000 | 0.45591439 | 0.378794 | 21.11 | 14.45 | 0.00753563 | 40354.3 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.19400517 | 60.00 | 49.00 | 11.00 | 0.000 | 9475.98 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.11 | 0.00753563 | 21.11 | 0.00753563 | 48.3993 | 8781.98 | 0.00 | 9480.33 | 9480.33 | 0.45591439 | 16.60 | 12.69 | 0.00753563 | 35759.0 | 37.01 | 19.90 | 0.00753563 | 56553.1 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12232.334 | 12232.334 | 1.197580 | 0.00027026 | 228.506 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 2.6238 | 2.662138 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12298.93 | 12232.33 | 1.0000 | 1.44140169 | 1.197580 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27023090 | 60.00 | 49.00 | 11.00 | 0.000 | 12298.93 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00762677 | 21.00 | 0.00762677 | 49.3112 | 5916.84 | 0.00 | 12303.62 | 12303.62 | 1.44140169 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.97 | 16.28 | 0.00800000 | 45470.6 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12665.336 | 12665.336 | 1.256551 | 0.00027983 | 236.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 2.7167 | 2.756373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:40:00 | 12734.37 | 12665.34 | 1.0000 | 1.51237906 | 1.256551 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.27979658 | 60.00 | 49.00 | 11.00 | 0.000 | 12734.37 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00763390 | 21.00 | 0.00763390 | 49.3569 | 6038.87 | 0.00 | 12739.16 | 12739.16 | 1.51237906 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.86 | 16.25 | 0.00800000 | 45358.0 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8754.673 | 8754.673 | 1.304747 | 0.00019342 | 157.312 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.8782 | 1.905290 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 8804.09 | 8754.67 | 1.0000 | 1.57038679 | 1.304747 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.19340407 | 60.00 | 49.00 | 11.00 | 0.000 | 8804.09 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.46 | 0.00615167 | 21.00 | 0.00615167 | 39.8757 | 1898.02 | 0.00 | 8806.26 | 8806.26 | 1.57038679 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.10 | 15.25 | 0.00800000 | 42542.4 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8054.903 | 8054.903 | 0.355563 | 0.00017796 | 166.202 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 1.7288 | 1.752998 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 8103.65 | 8054.90 | 1.0000 | 0.42795336 | 0.355563 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.17794508 | 60.00 | 49.00 | 11.00 | 0.000 | 8103.65 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00768394 | 21.00 | 0.00768394 | 49.6761 | 6179.60 | 0.00 | 8107.88 | 8107.88 | 0.42795336 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 35.18 | 19.68 | 0.00800000 | 55880.4 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 686141.739 | -999.000 | 20.512710 | 0.02450739 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1027.6613 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 20.512710 | 24.68899495 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 69.6178 | 69.617838 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 686141.74 | 437040.33 | 1.0000 | 24.68899495 | 20.512710 | 28.75 | 20.89 | 0.01227645 | 60252.0 | 10.99 | 10.99 | 0.00828082 | 32473.3 | 24.50489310 | 6.70 | 11.72 | 6.67 | 45961.570 | 640180.17 | 32.10 | 0.01409687 | 23.10 | 12.05026000 | 58.7453 | 23.99 | 0.00968387 | 23.99 | 0.00952590 | 51.1949 | 281979.37 | 0.00 | 746313.53 | 466497.82 | 24.68899495 | 28.75 | 20.90 | 0.01227645 | 60252.0 | 10.37 | 10.32 | 0.00777936 | 30023.4 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 203929.558 | 203929.558 | 6.153813 | 0.00450557 | 2861.814 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 20.512710 | 24.68899495 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 30.8654 | 44.381442 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 144678.54 | 203929.56 | 1.0000 | 7.40669849 | 6.153813 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 4.50511478 | 60.00 | 49.00 | 11.00 | 0.000 | 144678.54 | -10.70 | 0.00150390 | -10.70 | 12.05026000 | 195.8178 | 18.58 | 0.00634117 | 21.00 | 0.00742772 | 48.0400 | 64011.40 | 0.00 | 144508.02 | 144508.02 | 7.40669849 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 86208.044 | -999.000 | 2.051199 | 0.00307915 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1031.0454 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 35.19915822 | 13.37 | 6.70 | 6.67 | 985583.23 | 8.7469 | 8.746907 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 86208.04 | 50755.10 | 1.0000 | 2.46881288 | 2.051199 | 32.10 | 23.10 | 0.01409687 | 68352.0 | 10.99 | 12.09 | 0.00828082 | 34322.2 | 3.07883747 | 6.70 | 11.72 | 6.67 | 2194.880 | 84013.16 | 32.10 | 0.01409687 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00871509 | 21.11 | 0.00871028 | 55.8389 | 179877.06 | 0.00 | 92230.31 | 54243.56 | 2.46881288 | 32.10 | 23.11 | 0.01409687 | 68352.0 | 10.79 | 10.73 | 0.00799347 | 30993.8 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 20392.240 | 20392.240 | 0.615360 | 0.00045054 | 286.171 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.46881288 | 4197.9300 | 999.8980 | 10.15089776 | 71.00 | 82.00 | 11.00 | 468740.34 | 3.0864 | 4.437988 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:10:00 | 14467.35 | 20392.24 | 1.0000 | 0.74064386 | 0.615360 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 16.70 | 13.18 | 0.00800000 | 37036.7 | 0.45049567 | 60.00 | 49.00 | 11.00 | 0.000 | 14467.35 | -10.70 | 0.00150390 | -10.70 | 2.05119905 | 333.3333 | 21.11 | 0.00746812 | 21.11 | 0.00746990 | 47.9810 | 107007.72 | 0.00 | 14450.29 | 14450.29 | 0.74064386 | 16.60 | 5.98 | 0.00150390 | 20487.9 | 35.96 | 14.43 | 0.00150390 | 39998.4 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 12.05 | 20.51 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 10.00 | 8432.50 | 0.00 |
RETAIL_1_FLR_1 | 1448.83 | 8018.67 | 1107.50 |
RETAIL_2_FLR_1 | 61.83 | 8591.00 | 48.00 |
LAUNDRY_FLR_1 | 5191.67 | 3022.50 | 1816.83 |
CAFE_FLR_1 | 1555.83 | 6513.17 | 239.50 |
LOBBY_FLR_1 | 271.83 | 7808.17 | 5.50 |
ROOM_1_FLR_3 | 3062.50 | 7881.33 | 2646.50 |
ROOM_2_FLR_3 | 3572.33 | 8031.00 | 3216.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2128.33 | 8655.17 | 2088.50 |
ROOM_5_FLR_3 | 2825.00 | 7953.50 | 2591.50 |
ROOM_6_FLR_3 | 3344.00 | 8107.17 | 3140.33 |
ROOM_1_FLR_6 | 3790.17 | 7728.67 | 3215.00 |
ROOM_2_FLR_6 | 4158.83 | 7840.33 | 3674.33 |
ROOM_3_MULT9_FLR_6 | 2198.00 | 7792.67 | 1904.33 |
BANQUET_FLR_6 | 3102.50 | 3583.50 | 211.17 |
DINING_FLR_6 | 4301.67 | 2020.17 | 110.17 |
KITCHEN_FLR_6 | 7887.33 | 6423.83 | 6139.17 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8720.17 | 8760.00 | 7538.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 126.33 | 0.00 | 126.33 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.50 | 15.17 | 0.50 | 15.17 |
ROOM_2_FLR_3 | 1.67 | 13.83 | 1.67 | 13.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 5.50 | 44.67 | 5.50 | 44.67 |
ROOM_5_FLR_3 | 0.83 | 33.83 | 0.83 | 33.83 |
ROOM_6_FLR_3 | 2.67 | 31.33 | 2.67 | 31.33 |
ROOM_1_FLR_6 | 0.50 | 32.67 | 0.50 | 32.67 |
ROOM_2_FLR_6 | 2.33 | 27.83 | 2.33 | 27.83 |
ROOM_3_MULT9_FLR_6 | 1.33 | 45.50 | 1.33 | 45.50 |
BANQUET_FLR_6 | 0.00 | 2.50 | 0.00 | 2.50 |
DINING_FLR_6 | 0.00 | 4.00 | 0.00 | 4.00 |
KITCHEN_FLR_6 | 0.00 | 360.17 | 0.00 | 360.17 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 7.33 | 490.33 | 7.33 | 490.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.040 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.411 | 0.270 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.542 | 0.049 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 22.980 | 0.150 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 3.458 | 0.243 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.787 | 0.070 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.178 | 0.000 | 0.073 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.177 | 0.000 | 0.073 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.536 | 0.079 | 0.000 | 0.135 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.473 | 0.178 | 0.000 | 0.088 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.473 | 0.177 | 0.000 | 0.084 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.473 | 0.178 | 0.000 | 0.072 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.473 | 0.178 | 0.000 | 0.074 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.537 | 0.145 | 0.000 | 0.167 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.347 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.690 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 19.626 | 0.148 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 0.701 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 1.512 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 0.984 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 13.902 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 2.261 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.269 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.453 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.452 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.514 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.454 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.452 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.453 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.452 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.516 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.334 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 3.271 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 10.611 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
Electricity:Building | 2576.48 | 31831.39 | 03-JUN-05:00 | 169995.81 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 314.99 | 3589.69 | 02-JAN-02:10 | 23688.59 | 02-JAN-20:10 |
InteriorLights:Electricity | 911.20 | 7488.27 | 03-JUN-05:00 | 83314.66 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 171.89 | 1561.78 | 02-JAN-02:10 | 14056.06 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 911.20 | 7488.27 | 03-JUN-05:00 | 83314.66 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 20.20 | 235.30 | 02-JAN-02:10 | 1504.29 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 10.01 | 90.97 | 02-JAN-02:10 | 818.69 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 23.39 | 272.48 | 02-JAN-02:10 | 1741.98 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 11.59 | 105.34 | 02-JAN-02:10 | 948.05 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.96 | 344.68 | 02-JAN-02:10 | 2351.00 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.48 | 167.95 | 02-JAN-02:10 | 1511.55 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 6.74 | 79.57 | 02-JAN-02:10 | 499.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 3.15 | 28.59 | 02-JAN-02:10 | 257.34 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 73.48 | 1013.10 | 02-JAN-02:10 | 5026.41 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 5.55 | 50.40 | 02-JAN-02:10 | 453.61 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 27.79 | 290.06 | 20-MAY-05:00 | 2593.62 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 13.45 | 79.61 | 01-JAN-13:10 | 1628.35 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 304.26 | 3499.54 | 20-MAY-05:00 | 23462.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 155.26 | 1388.12 | 20-MAY-05:00 | 13433.46 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 22.72 | 202.88 | 02-JAN-10:10 | 1950.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 12.24 | 76.45 | 01-JAN-11:10 | 1223.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 22.71 | 202.85 | 02-JAN-10:10 | 1949.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 12.24 | 76.44 | 01-JAN-11:10 | 1222.98 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 341.13 | 3265.69 | 02-JAN-10:10 | 28134.10 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 146.13 | 912.82 | 01-JAN-11:10 | 14605.07 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 341.22 | 3266.59 | 02-JAN-10:10 | 28141.80 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 146.17 | 913.07 | 01-JAN-11:10 | 14609.06 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 22.72 | 202.88 | 02-JAN-10:10 | 1950.11 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 12.24 | 76.45 | 01-JAN-11:10 | 1223.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 22.71 | 202.85 | 02-JAN-10:10 | 1949.88 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 12.24 | 76.44 | 01-JAN-11:10 | 1222.98 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 66.04 | 600.08 | 02-JAN-02:10 | 5400.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 66.04 | 600.08 | 02-JAN-02:10 | 5400.74 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.68 | 50.72 | 02-JAN-10:10 | 487.53 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 3.06 | 19.11 | 01-JAN-11:10 | 305.78 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.68 | 50.71 | 02-JAN-10:10 | 487.47 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 3.06 | 19.11 | 01-JAN-11:10 | 305.75 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 40.41 | 386.83 | 02-JAN-10:10 | 3332.58 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 17.31 | 108.13 | 01-JAN-11:10 | 1730.02 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 205.27 | 2439.94 | 03-JUN-05:00 | 9607.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 29.41 | 190.63 | 03-JUN-05:00 | 2859.51 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 205.27 | 2439.94 | 03-JUN-05:00 | 9607.42 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 29.41 | 190.63 | 03-JUN-05:00 | 2859.51 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 455.64 | 6266.47 | 02-JAN-02:10 | 18984.42 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 14.81 | 134.55 | 02-JAN-02:10 | 1210.92 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 17.47 | 158.77 | 02-JAN-02:10 | 1428.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 17.47 | 158.77 | 02-JAN-02:10 | 1428.96 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.19 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 872.73 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.66 | 1114.64 | 11-FEB-23:30 | 3337.30 | 02-MAY-06:30 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1466.71 | 2782.21 | 18-OCT-03:00 | 212479.69 | 20-JUL-20:20 |
LowTempRefrigeration:Refrigeration:Electricity | 20.34 | 0.00 | 01-JAN-11:10 | 1977.66 | 03-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.23 | 930.35 | 06-FEB-04:10 | 1239.55 | 27-OCT-08:30 |
WaterSystems:Electricity | 90.75 | 1086.75 | 11-OCT-00:40 | 4738.63 | 12-MAY-19:00 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.75 | 11-OCT-00:40 | 4738.63 | 12-MAY-19:00 |
Fans:Electricity | 568.37 | 14150.65 | 15-JUN-05:20 | 42141.70 | 08-OCT-21:10 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 845.10 | 15040.38 | 17-SEP-05:30 | 53487.77 | 08-OCT-21:10 |
ExteriorEquipment:Electricity | 981.58 | 6672.62 | 02-JAN-02:20 | 63148.86 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 31.13 | 542.64 | 03-JUN-05:00 | 1861.72 | 17-MAY-20:10 |
ElectricityPurchased:Facility | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
ElectricityPurchased:Plant | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
Cogeneration:ElectricityPurchased | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
ElectricityNet:Plant | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
Cogeneration:ElectricityNet | 6084.70 | 77868.89 | 25-APR-02:50 | 477311.61 | 04-AUG-19:10 |
General:Fans:Electricity | 568.37 | 14150.65 | 15-JUN-05:20 | 42141.70 | 08-OCT-21:10 |
ExteriorLights:Electricity | 245.96 | 0.00 | 01-JAN-07:30 | 15665.55 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 245.96 | 0.00 | 01-JAN-07:30 | 15665.55 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 245.59 | 0.00 | 02-MAR-15:40 | 10206.30 | 01-JAN-09:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1250.09 | 0.00 | 01-JAN-00:10 | 202385.68 | 20-JUL-20:20 |
General:Cooling:Electricity | 1250.09 | 0.00 | 01-JAN-00:10 | 202385.68 | 20-JUL-20:20 |
Pumps:Electricity | 71.31 | 59.65 | 06-OCT-11:50 | 4195.06 | 20-JUL-20:40 |
General:Pumps:Electricity | 71.31 | 59.65 | 06-OCT-11:50 | 4195.06 | 20-JUL-20:40 |
WIRED_LTG_ELECTRICITY | 32.07 | 0.00 | 01-JAN-00:10 | 2932.68 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4688.28 | 34717.28 | 11-SEP-00:10 | 460517.77 | 14-JAN-17:20 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 2899.43 | 18467.44 | 20-JUL-08:20 | 393753.78 | 05-FEB-24:00 |
WaterSystems:Gas | 2127.54 | 18467.44 | 14-APR-10:40 | 184164.32 | 03-MAR-22:00 |
Water Heater:WaterSystems:Gas | 2127.54 | 18467.44 | 14-APR-10:40 | 184164.32 | 03-MAR-22:00 |
Heating:Gas | 771.89 | 0.00 | 07-APR-17:20 | 236840.16 | 14-JAN-16:20 |
Boiler:Heating:Gas | 771.89 | 0.00 | 07-APR-17:20 | 236840.16 | 14-JAN-16:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4190.95 | 0.00 | 01-JAN-00:10 | 756350.00 | 03-AUG-21:20 |
PlantLoopCoolingDemand:HVAC | 4190.95 | 0.00 | 01-JAN-00:10 | 756350.00 | 03-AUG-21:20 |
CoolingCoils:PlantLoopCoolingDemand | 4190.95 | 0.00 | 01-JAN-00:10 | 756350.00 | 03-AUG-21:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:50 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:50 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:50 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 23-JAN-19:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:50 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:50 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-20:50 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 23-JAN-19:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 18-JAN-08:00 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 18-JAN-08:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 24819.80 | 157787.71 | 17-APR-13:10 | 3053489.24 | 20-JUL-20:20 |
EnergyTransfer:Building | 5142.86 | 81056.53 | 03-JAN-13:00 | 336294.55 | 01-AUG-19:00 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 725.75 | 10692.62 | 06-FEB-04:00 | 35663.07 | 08-JUL-10:50 |
Refrigeration:EnergyTransfer | 182.32 | 3902.73 | 08-OCT-22:10 | 10473.76 | 20-OCT-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 91.16 | 1951.36 | 08-OCT-22:10 | 5236.88 | 20-OCT-06:30 |
EnergyTransfer:Plant | 11098.98 | 20780.79 | 06-OCT-11:50 | 1754322.87 | 20-JUL-20:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.59 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 69.56 | 1741.04 | 06-FEB-04:10 | 2668.64 | 27-OCT-08:30 |
PlantLoopHeatingDemand:Facility | 1283.96 | 9827.70 | 06-AUG-00:10 | 242798.29 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 744.65 | 8649.33 | 14-AUG-00:10 | 56384.83 | 09-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 744.65 | 8649.33 | 14-AUG-00:10 | 56384.83 | 09-FEB-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 433.62 | 5008.44 | 25-MAR-17:30 | 23060.46 | 26-OCT-20:40 |
Heating:EnergyTransfer | 159.48 | 0.00 | 17-JAN-11:10 | 98579.22 | 14-JAN-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 26.59 | 03-APR-17:10 |
Cooling:EnergyTransfer | 4892.22 | 69459.06 | 08-JAN-16:00 | 333597.86 | 01-AUG-19:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 433.62 | 5008.44 | 25-MAR-17:30 | 23060.46 | 26-OCT-20:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 39.49 | 0.03 | 21-APR-02:40 | 3714.46 | 04-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 1.96 | 0.00 | 01-JAN-08:50 | 1588.21 | 06-FEB-07:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 37.53 | 0.00 | 01-JAN-00:10 | 3714.46 | 04-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.31 | 339.40 | 08-JAN-16:00 | 1895.04 | 24-AUG-19:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 40.09 | 07-NOV-08:20 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 39.31 | 339.40 | 08-JAN-16:00 | 1895.04 | 24-AUG-19:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 31.33 | 0.54 | 12-FEB-17:20 | 1701.71 | 24-AUG-19:00 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.08 | 0.00 | 01-JAN-00:50 | 481.02 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 31.26 | 0.00 | 01-JAN-00:10 | 1701.71 | 24-AUG-19:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 13.05 | 0.03 | 13-JAN-13:20 | 802.49 | 24-AUG-19:00 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.91 | 0.00 | 03-JAN-19:20 | 592.20 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 12.14 | 0.00 | 01-JAN-00:10 | 802.49 | 24-AUG-19:00 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.54 | 8486.95 | 03-NOV-02:30 | 38428.61 | 04-AUG-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 602.54 | 8486.95 | 03-NOV-02:30 | 38428.61 | 04-AUG-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 217.22 | 5.42 | 27-FEB-09:30 | 13243.64 | 30-SEP-12:30 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 1395.80 | 14-JAN-17:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 217.17 | 0.00 | 02-JAN-07:10 | 13243.64 | 30-SEP-12:30 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 814.39 | 7759.95 | 08-JAN-16:00 | 38238.63 | 08-OCT-20:50 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 215.56 | 07-NOV-08:20 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 814.39 | 7759.95 | 08-JAN-16:00 | 38238.63 | 08-OCT-20:50 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 52.80 | 0.34 | 22-APR-20:40 | 11825.07 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 15.63 | 0.00 | 01-JAN-08:10 | 6289.56 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 37.17 | 0.00 | 01-JAN-00:10 | 11825.07 | 07-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 52.27 | 0.04 | 04-FEB-08:50 | 11074.14 | 22-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 19.78 | 0.00 | 01-JAN-08:10 | 6378.66 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 32.50 | 0.00 | 01-JAN-00:10 | 11074.14 | 22-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 385.10 | 12.61 | 27-FEB-13:10 | 52743.29 | 04-OCT-12:00 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 4.89 | 0.00 | 01-JAN-08:00 | 15350.42 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 380.22 | 0.00 | 01-JAN-00:10 | 52743.29 | 04-OCT-12:00 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 413.38 | 0.07 | 14-MAR-16:40 | 73349.18 | 29-MAY-21:30 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 33.23 | 0.00 | 01-JAN-08:10 | 37184.49 | 02-JAN-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 380.15 | 0.00 | 01-JAN-00:10 | 73349.18 | 29-MAY-21:30 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 52.93 | 0.08 | 20-NOV-08:00 | 12050.97 | 22-AUG-08:20 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 15.47 | 0.00 | 01-JAN-08:10 | 6343.87 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.46 | 0.00 | 01-JAN-00:10 | 12050.97 | 22-AUG-08:20 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 52.05 | 0.02 | 25-JAN-12:00 | 11907.15 | 22-AUG-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 19.46 | 0.00 | 01-JAN-08:10 | 6430.66 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 32.60 | 0.00 | 01-JAN-00:10 | 11907.15 | 22-AUG-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 114.75 | 0.09 | 27-OCT-04:20 | 8006.46 | 24-AUG-19:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 18.61 | 0.00 | 05-JAN-12:50 | 4306.64 | 02-JAN-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 96.14 | 0.00 | 01-JAN-00:10 | 8006.46 | 24-AUG-19:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 16.67 | 0.02 | 26-NOV-15:30 | 3218.06 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 5.65 | 0.00 | 01-JAN-08:10 | 1976.91 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.02 | 0.00 | 01-JAN-00:10 | 3218.06 | 07-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 16.68 | 0.01 | 17-OCT-04:20 | 3116.44 | 07-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.97 | 0.00 | 01-JAN-08:10 | 1977.10 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 9.71 | 0.00 | 01-JAN-00:10 | 3116.44 | 07-SEP-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 84.41 | 0.23 | 23-JAN-21:30 | 13833.70 | 04-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 12.54 | 0.00 | 01-JAN-08:10 | 8796.05 | 14-JAN-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 71.87 | 0.00 | 01-JAN-00:10 | 13833.70 | 04-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 434.52 | 5830.04 | 29-NOV-12:00 | 22482.24 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 434.52 | 5830.04 | 29-NOV-12:00 | 22482.24 | 04-AUG-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 477.75 | 6736.03 | 29-NOV-12:00 | 24084.30 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 477.75 | 6736.03 | 29-NOV-12:00 | 24084.30 | 04-AUG-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 634.59 | 8625.84 | 03-NOV-02:30 | 30600.22 | 08-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 72.83 | 0.10 | 27-DEC-07:50 | 4637.62 | 24-AUG-19:00 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 4.24 | 0.00 | 01-JAN-10:10 | 2993.91 | 02-JAN-06:00 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 68.59 | 0.00 | 01-JAN-00:10 | 4637.62 | 24-AUG-19:00 |
WaterSystems:EnergyTransfer | 744.65 | 8649.33 | 14-AUG-00:10 | 56384.83 | 09-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 744.65 | 8649.33 | 14-AUG-00:10 | 56384.83 | 09-FEB-07:10 |
EnergyTransfer:HVAC | 8577.97 | 4045.91 | 05-APR-11:10 | 978094.80 | 20-JUL-20:30 |
HeatingCoils:EnergyTransfer | 539.31 | 0.00 | 07-APR-17:20 | 197747.37 | 14-JAN-16:10 |
PlantLoopHeatingDemand:HVAC | 539.31 | 0.00 | 07-APR-17:20 | 197747.37 | 14-JAN-16:10 |
HeatingCoils:PlantLoopHeatingDemand | 539.31 | 0.00 | 07-APR-17:20 | 197747.37 | 14-JAN-16:10 |
CoolingCoils:EnergyTransfer | 4190.95 | 0.00 | 01-JAN-00:10 | 756350.00 | 03-AUG-21:20 |
HeatRecoveryForHeating:EnergyTransfer | 3055.19 | 0.00 | 02-MAR-15:40 | 492707.98 | 06-FEB-03:00 |
HeatRecoveryForCooling:EnergyTransfer | 792.52 | 0.00 | 01-JAN-00:10 | 309237.98 | 08-JUL-12:00 |
Boilers:EnergyTransfer | 530.03 | 0.00 | 07-APR-17:20 | 193291.14 | 14-JAN-16:20 |
Chillers:EnergyTransfer | 4241.53 | 0.00 | 01-JAN-00:10 | 759606.48 | 03-AUG-21:20 |
HeatRejection:EnergyTransfer | 5491.61 | 0.00 | 01-JAN-00:10 | 959870.72 | 20-JUL-20:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -433.623 | 0.000 | 0.000 | 147.072 | 171.886 | 143.109 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -28.444 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 1.962 | -37.530 | 0.000 | 0.000 | 15.848 | 10.011 | 10.186 | 22.101 | 0.000 | 0.520 | 0.000 | 0.000 | -10.706 | 0.000 | -7.582 | -4.810 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -39.312 | 0.000 | 0.000 | 17.611 | 11.593 | 11.795 | 0.000 | 0.000 | 0.110 | 0.000 | 0.000 | 0.000 | 0.000 | -1.672 | -0.126 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -602.542 | 0.000 | 0.000 | 11.644 | 5.547 | 658.148 | 0.000 | 0.000 | 0.382 | 0.000 | 0.000 | 0.000 | 0.000 | -5.348 | -67.830 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.051 | -217.168 | 0.000 | 0.000 | 196.521 | 13.449 | 14.341 | 61.173 | 0.000 | 1.116 | 0.000 | 0.000 | -32.281 | 0.000 | -20.468 | -16.734 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -814.394 | 0.000 | 0.000 | 576.024 | 155.261 | 149.002 | 81.631 | 0.000 | 2.459 | 0.000 | 0.000 | -43.561 | 0.000 | -41.607 | -64.816 |
ROOM_1_FLR_3 | 15.628 | -20.350 | 0.000 | -16.819 | 0.000 | 0.000 | 9.549 | 12.238 | 10.478 | 42.569 | 0.000 | 0.640 | 0.000 | 0.000 | -24.725 | 0.000 | -10.079 | -19.129 |
ROOM_2_FLR_3 | 19.775 | -16.017 | 0.000 | -16.477 | 0.000 | 0.000 | 9.588 | 12.236 | 10.477 | 31.019 | 0.000 | 0.645 | 0.000 | 0.000 | -25.571 | 0.000 | -9.885 | -15.789 |
ROOM_3_MULT19_FLR_3 | 4.886 | -134.373 | 0.000 | -245.841 | 0.000 | 0.000 | 0.000 | 146.128 | 194.997 | 261.795 | 0.000 | 6.387 | 0.000 | 0.000 | -139.541 | 0.000 | -70.836 | -23.602 |
ROOM_4_MULT19_FLR_3 | 33.233 | -159.427 | 0.000 | -220.701 | 0.000 | 0.000 | 183.225 | 146.168 | 195.050 | 82.261 | 0.000 | 6.799 | 0.000 | 0.000 | -144.954 | 0.000 | -63.065 | -58.590 |
ROOM_5_FLR_3 | 15.474 | -20.699 | 0.000 | -16.755 | 0.000 | 0.000 | 9.584 | 12.238 | 10.478 | 42.035 | 0.000 | 0.669 | 0.000 | 0.000 | -24.274 | 0.000 | -10.058 | -18.693 |
ROOM_6_FLR_3 | 19.458 | -16.176 | 0.000 | -16.419 | 0.000 | 0.000 | 9.621 | 12.236 | 10.477 | 30.140 | 0.000 | 0.677 | 0.000 | 0.000 | -24.783 | 0.000 | -9.832 | -15.400 |
ROOM_1_FLR_6 | 5.653 | -6.771 | 0.000 | -4.244 | 0.000 | 0.000 | 2.375 | 3.059 | 2.620 | 10.509 | 0.000 | 0.154 | 0.000 | 0.000 | -6.246 | 0.000 | -2.560 | -4.549 |
ROOM_2_FLR_6 | 6.971 | -5.541 | 0.000 | -4.163 | 0.000 | 0.000 | 2.385 | 3.059 | 2.619 | 7.630 | 0.000 | 0.155 | 0.000 | 0.000 | -6.451 | 0.000 | -2.524 | -4.140 |
ROOM_3_MULT9_FLR_6 | 12.540 | -44.412 | 0.000 | -27.456 | 0.000 | 0.000 | 21.458 | 17.309 | 23.098 | 56.795 | 0.000 | 0.906 | 0.000 | 0.000 | -29.241 | 0.000 | -13.683 | -17.315 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -434.527 | 0.000 | 0.000 | 320.724 | 29.410 | 175.857 | 8.454 | 0.000 | 0.251 | 0.000 | 0.000 | -20.205 | 0.000 | -6.424 | -73.540 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -477.751 | 0.000 | 0.000 | 318.314 | 29.410 | 175.857 | 8.120 | 0.000 | 0.236 | 0.000 | 0.000 | -20.962 | 0.000 | -6.508 | -26.716 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -634.571 | 0.000 | 0.000 | 28.936 | 14.808 | 550.372 | 19.192 | 0.000 | 0.200 | 40.865 | 0.000 | -13.955 | 0.000 | -5.847 | -0.002 |
MECH_FLR_1 | 0.000 | 0.000 | 0.077 | -31.256 | 0.000 | 0.000 | 0.000 | 18.484 | 12.472 | 0.000 | 0.000 | 0.265 | 3.451 | 0.000 | 0.000 | 0.000 | -3.493 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.913 | -12.140 | 0.000 | 0.000 | 0.000 | 3.147 | 3.598 | 0.000 | 0.000 | 0.189 | 6.687 | 0.000 | 0.000 | 0.000 | -2.394 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 18.611 | -96.137 | 0.000 | 0.000 | 0.000 | 66.043 | 0.000 | 40.439 | 0.000 | 0.949 | 10.945 | 0.000 | -30.298 | 0.000 | -10.552 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 4.245 | -68.587 | 0.000 | 0.000 | 0.000 | 17.474 | 0.000 | 19.227 | 0.000 | 0.318 | 45.956 | 0.000 | -13.899 | 0.000 | -4.734 | -0.000 |
Total Facility | 133.618 | -423.766 | 25.859 | -4468.414 | 0.000 | 0.000 | 1880.481 | 911.197 | 2365.030 | 825.092 | 0.000 | 24.025 | 107.905 | 0.000 | -611.651 | 0.000 | -309.151 | -460.228 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 27-OCT-22:03 | 0.00 | 0.00 | 0.00 | -32125.83 | 0.00 | 0.00 | 6595.35 | 4685.35 | 4055.80 | 0.00 | 0.00 | 0.00 | 16789.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 03-DEC-12:44 | 0.00 | 0.00 | 0.00 | -3747.57 | 0.00 | 0.00 | 225.90 | 272.90 | 288.68 | 6377.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -392.17 | -3025.28 |
RETAIL_2_FLR_1 | 08-OCT-22:00 | 0.00 | 0.00 | 0.00 | -2259.65 | 0.00 | 0.00 | 727.59 | 526.69 | 501.43 | 0.00 | 0.00 | 0.00 | 591.95 | 0.00 | -0.00 | 0.00 | -88.00 | 0.00 |
LAUNDRY_FLR_1 | 26-OCT-21:20 | 0.00 | 0.00 | 0.00 | -46015.20 | 0.00 | 0.00 | 527.38 | 302.40 | 32641.65 | 0.00 | 0.00 | 0.00 | 12805.44 | 0.00 | -0.00 | 0.00 | -261.68 | 0.00 |
CAFE_FLR_1 | 03-DEC-12:44 | 0.00 | 0.00 | 0.00 | -15201.14 | 0.00 | 0.00 | 2968.59 | 119.41 | 406.43 | 17875.76 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -994.81 | -5174.24 |
LOBBY_FLR_1 | 26-OCT-21:20 | 0.00 | 0.00 | 0.00 | -60378.59 | 0.00 | 0.00 | 26467.17 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 22603.91 | 0.00 | -3094.07 | 0.00 | -1944.00 | 0.00 |
ROOM_1_FLR_3 | 27-MAY-21:11 | 0.00 | -13740.20 | 0.00 | -752.85 | 0.00 | 0.00 | 312.75 | 1039.66 | 358.22 | 0.00 | 0.00 | 0.00 | 13648.33 | 0.00 | -742.94 | 0.00 | -122.97 | 0.00 |
ROOM_2_FLR_3 | 27-MAY-21:11 | 0.00 | -13470.54 | 0.00 | -746.60 | 0.00 | 0.00 | 314.89 | 1039.54 | 358.18 | 0.00 | 0.00 | 0.00 | 13353.43 | 0.00 | -728.22 | 0.00 | -120.68 | 0.00 |
ROOM_3_MULT19_FLR_3 | 04-OCT-12:00 | 0.00 | -41911.43 | 0.00 | -10830.37 | 0.00 | 0.00 | 0.00 | 912.82 | 2352.88 | 72920.30 | 0.00 | 147.48 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23591.67 |
ROOM_4_MULT19_FLR_3 | 27-MAY-21:11 | 0.00 | -78581.78 | 0.00 | -9581.41 | 0.00 | 0.00 | 6348.59 | 12417.70 | 6668.31 | 0.00 | 0.00 | 0.00 | 66504.06 | 0.00 | -3211.60 | 0.00 | -563.87 | 0.00 |
ROOM_5_FLR_3 | 22-AUG-08:11 | 0.00 | -13987.22 | 0.00 | -1091.56 | 0.00 | 0.00 | 59.39 | 535.12 | 453.05 | 10153.05 | 0.00 | 0.00 | 3881.30 | 0.00 | -0.00 | 0.00 | -3.13 | 0.00 |
ROOM_6_FLR_3 | 22-AUG-08:11 | 0.00 | -13788.38 | 0.00 | -1083.64 | 0.00 | 0.00 | 60.16 | 535.05 | 452.99 | 9945.18 | 0.00 | 0.00 | 3878.97 | 0.00 | -0.00 | 0.00 | -0.33 | 0.00 |
ROOM_1_FLR_6 | 09-APR-17:31 | 0.00 | -3916.96 | 0.00 | -199.83 | 0.00 | 0.00 | 44.59 | 259.91 | 126.43 | 779.40 | 0.00 | 0.00 | 2981.20 | 0.00 | -0.00 | 0.00 | -74.73 | 0.00 |
ROOM_2_FLR_6 | 25-AUG-21:11 | 0.00 | -3681.18 | 0.00 | -239.00 | 0.00 | 0.00 | 87.96 | 206.38 | 89.55 | 0.00 | 0.00 | 0.00 | 3733.10 | 0.00 | -174.30 | 0.00 | -22.51 | 0.00 |
ROOM_3_MULT9_FLR_6 | 25-AUG-21:11 | 0.00 | -15299.55 | 0.00 | -1517.06 | 0.00 | 0.00 | 816.21 | 1167.76 | 789.67 | 0.00 | 0.00 | 0.00 | 14876.91 | 0.00 | -734.84 | 0.00 | -99.10 | 0.00 |
BANQUET_FLR_6 | 27-OCT-22:03 | 0.00 | 0.00 | 0.00 | -29328.15 | 0.00 | 0.00 | 14910.03 | 953.17 | 6747.90 | 0.00 | 0.00 | 0.00 | 8284.82 | 0.00 | -1264.29 | 0.00 | -303.48 | 0.00 |
DINING_FLR_6 | 11-APR-22:30 | 0.00 | 0.00 | 0.00 | -32092.33 | 0.00 | 0.00 | 15640.46 | 953.17 | 6747.90 | 0.00 | 0.00 | 0.00 | 10298.83 | 0.00 | -1271.54 | 0.00 | -276.48 | 0.00 |
KITCHEN_FLR_6 | 20-DEC-11:34 | 0.00 | 0.00 | 0.00 | -36457.34 | 0.00 | 0.00 | 309.52 | 336.37 | 24259.91 | 724.29 | 0.00 | 0.00 | 11068.34 | 0.00 | -0.00 | 0.00 | -241.07 | 0.00 |
MECH_FLR_1 | 18-OCT-08:18 | 0.00 | 0.00 | 0.00 | -1969.54 | 0.00 | 0.00 | 0.00 | 671.80 | 441.81 | 0.00 | 0.00 | 0.00 | 1017.20 | 0.00 | -0.00 | 0.00 | -161.28 | 0.00 |
STORAGE_FLR_1 | 18-OCT-08:18 | 0.00 | 0.00 | 0.00 | -912.51 | 0.00 | 0.00 | 0.00 | 114.38 | 127.45 | 0.00 | 0.00 | 0.00 | 778.25 | 0.00 | -0.00 | 0.00 | -107.56 | 0.00 |
CORRIDOR_FLR_3 | 24-AUG-19:00 | 0.00 | 0.00 | 0.00 | -8005.99 | 0.00 | 0.00 | 0.00 | 4800.66 | 0.00 | 763.49 | 0.00 | 251.75 | 2190.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 19-FEB-12:42 | 0.00 | 0.00 | 0.00 | -5219.71 | 0.00 | 0.00 | 0.00 | 476.32 | 0.00 | 3950.42 | 0.00 | 0.00 | 999.36 | 0.00 | -0.00 | 0.00 | -206.39 | 0.00 |
Total Facility | 18-AUG-21:11 | 0.00 | -161238.61 | 0.00 | -207802.83 | 0.00 | 0.00 | 87832.00 | 55846.84 | 95722.11 | 99.91 | 0.00 | 645.56 | 132622.38 | 0.00 | -3718.94 | 0.00 | -8.42 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 03-APR-17:03 | 0.00 | 0.00 | 265.88 | -0.00 | 0.00 | 0.00 | 4201.44 | 9370.71 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20935.68 |
RETAIL_1_FLR_1 | 06-FEB-07:10 | 0.00 | 0.00 | 1589.57 | -0.00 | 0.00 | 0.00 | 360.23 | 454.83 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1353.95 | 0.00 | -891.84 | -591.86 |
RETAIL_2_FLR_1 | 07-NOV-08:17 | 0.00 | 0.00 | 120.26 | -0.00 | 0.00 | 0.00 | 386.18 | 421.35 | 417.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -77.88 | -1267.77 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | 14-JAN-17:00 | 0.00 | 0.00 | 1395.84 | -0.00 | 0.00 | 0.00 | 3528.60 | 452.32 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3609.12 | 0.00 | -1788.23 | -335.04 |
LOBBY_FLR_1 | 07-NOV-08:17 | 0.00 | 0.00 | 646.67 | -0.00 | 0.00 | 0.00 | 12677.13 | 5134.57 | 5278.53 | 7972.72 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1932.29 | -29777.33 |
ROOM_1_FLR_3 | 14-JAN-16:13 | 7017.63 | 375.41 | 0.00 | -375.41 | 0.00 | 0.00 | 148.24 | 76.45 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2790.70 | 0.00 | -819.73 | -3853.15 |
ROOM_2_FLR_3 | 14-JAN-16:13 | 7009.46 | 373.88 | 0.00 | -373.88 | 0.00 | 0.00 | 148.26 | 76.44 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2809.67 | 0.00 | -819.04 | -3826.67 |
ROOM_3_MULT19_FLR_3 | 02-JAN-05:00 | 15350.57 | 3439.67 | 0.00 | -3439.67 | 0.00 | 0.00 | 0.00 | 1095.38 | 3333.24 | 0.00 | 0.00 | 0.00 | 3473.25 | 0.00 | -18035.98 | 0.00 | -5216.46 | 0.00 |
ROOM_4_MULT19_FLR_3 | 02-JAN-16:02 | 39216.97 | 3720.38 | 0.00 | -3720.38 | 0.00 | 0.00 | 5585.69 | 1168.72 | 3726.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -13080.96 | 0.00 | -4117.46 | -32499.38 |
ROOM_5_FLR_3 | 14-JAN-16:13 | 6776.99 | 369.52 | 0.00 | -369.52 | 0.00 | 0.00 | 148.42 | 76.45 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2838.50 | 0.00 | -817.32 | -3567.30 |
ROOM_6_FLR_3 | 14-JAN-16:13 | 6783.04 | 368.05 | 0.00 | -368.05 | 0.00 | 0.00 | 148.45 | 76.44 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2857.19 | 0.00 | -816.65 | -3555.32 |
ROOM_1_FLR_6 | 14-JAN-16:13 | 2044.27 | 91.72 | 0.00 | -91.72 | 0.00 | 0.00 | 37.20 | 19.11 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -696.76 | 0.00 | -204.57 | -1254.57 |
ROOM_2_FLR_6 | 14-JAN-16:13 | 2042.26 | 91.07 | 0.00 | -91.07 | 0.00 | 0.00 | 37.29 | 19.11 | 55.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -701.77 | 0.00 | -204.28 | -1247.90 |
ROOM_3_MULT9_FLR_6 | 14-JAN-16:13 | 9065.81 | 570.74 | 0.00 | -570.74 | 0.00 | 0.00 | 337.31 | 108.13 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3251.07 | 0.00 | -936.50 | -5811.41 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 02-JAN-05:00 | 0.00 | 0.00 | 481.03 | -0.00 | 0.00 | 0.00 | 0.00 | 167.95 | 176.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -412.34 | -413.37 |
STORAGE_FLR_1 | 02-JAN-05:00 | 0.00 | 0.00 | 592.22 | -0.00 | 0.00 | 0.00 | 0.00 | 28.59 | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -285.80 | -385.99 |
CORRIDOR_FLR_3 | 02-JAN-06:00 | 0.00 | 0.00 | 4306.73 | -0.00 | 0.00 | 0.00 | 0.00 | 1200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 66.10 | 0.00 | -4340.93 | 0.00 | -1232.07 | 0.00 |
CORRIDOR_FLR_6 | 02-JAN-06:00 | 0.00 | 0.00 | 2993.96 | -0.00 | 0.00 | 0.00 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1950.96 | 0.00 | -550.40 | -810.15 |
Total Facility | 14-JAN-16:13 | 17492.76 | 86027.20 | 9664.31 | -86027.20 | 0.00 | 0.00 | 33284.73 | 15296.54 | 74838.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65782.03 | 0.00 | -23236.91 | -61557.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.7695 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 20.5127 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 12.0463 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 12.0463 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.003024 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001080 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4777 | 2.4777 | 1.4371 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3174 | 0.3174 | 0.1841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2355 | 0.2355 | 0.1366 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2629 | 3.2629 | 1.8925 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2758 | 1.2758 | 0.7399 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5824 | 4.5824 | 2.6578 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0648 | 2.0648 | 1.1976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1665 | 2.1665 | 1.2566 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2496 | 2.2496 | 1.3047 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2267 | 0.2267 | 0.1315 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1102 | 0.1102 | 0.0639 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.6884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6130 | 0.6130 | 0.3556 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.7695 | 20.5127 | 20.7695 | 12.0463 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4371 | 1.4371 | 1.4371 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1841 | 0.1841 | 0.1841 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1366 | 0.1366 | 0.1366 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8925 | 1.8925 | 1.8925 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7399 | 0.7399 | 0.7399 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6578 | 2.6578 | 2.6578 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1976 | 1.1976 | 1.1976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2566 | 1.2566 | 1.2566 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3047 | 1.3047 | 1.3047 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1315 | 0.1315 | 0.1315 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0639 | 0.0639 | 0.0639 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6884 | 0.6884 | 0.6884 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3556 | 0.3556 | 0.3556 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 12.0463 | 12.0463 | 12.0463 | 12.0463 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:44:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 7.33 |
Number of hours cooling loads not met | 490.33 |
Number of hours not met | 497.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 771.89 | 236840.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1250.09 | 202385.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 911.20 | 83314.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 245.96 | 15665.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.73 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 31.13 | 1861.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 568.37 | 42141.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 71.31 | 4195.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 245.59 | 10206.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4738.63 | 2127.54 | 184164.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.34 | 1977.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.23 | 1239.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.85 | 6084.70 |
Natural Gas | 1788.85 | 4688.28 |
Additional | 0.00 | 0.00 |
Total | 3508.70 | 10772.98 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 80.32 |
Space Heating | 0.00 |
Space Cooling | 110.19 |
Fans (All) | 50.10 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 536.32 |
Subtotal | 536.32 |
Natural Gas [MJ/m2] | |
Space Heating | 68.04 |
Service Water Heating | 187.53 |
Miscellaneous (All) | 413.24 |
Subtotal | 413.24 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.46 |
Space Heating | 7.17 |
Space Cooling | 11.60 |
Fans (All) | 5.28 |
Service Water Heating | 20.59 |
Receptacle Equipment | 32.00 |
Miscellaneous | 14.91 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 1660. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2737. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1362. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 0. | 0. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 18.89 | 365 | 18.89 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 23.33 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2013
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.177406E+12 |
February | 0.000 | 0.159950E+12 |
March | 0.000 | 0.771297E+11 |
April | 0.000 | 0.542046E+11 |
May | 0.000 | 0.270118E+11 |
June | 0.000 | 0.158804E+11 |
July | 0.000 | 0.120009E+11 |
August | 0.000 | 0.906389E+10 |
September | 0.000 | 0.148822E+11 |
October | 0.000 | 0.320309E+11 |
November | 0.000 | 0.798406E+11 |
December | 0.000 | 0.112486E+12 |
Annual Sum or Average | 0.771887E+12 | |
Minimum of Months | 0.000 | 0.906389E+10 |
Maximum of Months | 0.000 | 0.177406E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348186E+11 | 22520.79 | 21-JAN-20:06 | 7.12 | 6.40 | 0.759726E+10 | 4768.25 | 20-JAN-22:10 | 3.72 | 3.02 |
February | 0.298709E+11 | 22740.65 | 19-FEB-12:42 | 8.22 | 4.20 | 0.660028E+10 | 4701.12 | 01-FEB-22:10 | 4.90 | 2.78 |
March | 0.318951E+11 | 22701.20 | 12-MAR-08:62 | 7.62 | 3.91 | 0.711256E+10 | 4469.95 | 01-MAR-22:10 | 5.50 | 4.48 |
April | 0.308960E+11 | 20716.64 | 22-APR-23:00 | 8.90 | 6.03 | 0.660611E+10 | 4479.88 | 04-APR-21:10 | 8.40 | 6.25 |
May | 0.325587E+11 | 19333.45 | 01-MAY-06:24 | 8.60 | 5.45 | 0.644649E+10 | 4250.90 | 01-MAY-21:49 | 9.90 | 5.25 |
June | 0.348169E+11 | 16074.38 | 22-JUN-20:00 | 26.70 | 16.74 | 0.610877E+10 | 3999.33 | 02-JUN-21:10 | 15.60 | 9.68 |
July | 0.388619E+11 | 16220.29 | 13-JUL-21:00 | 27.20 | 23.26 | 0.632808E+10 | 3967.51 | 13-JUL-21:10 | 27.12 | 23.29 |
August | 0.411773E+11 | 17815.40 | 24-AUG-19:00 | 29.40 | 16.42 | 0.659670E+10 | 4141.38 | 25-AUG-21:10 | 22.52 | 14.67 |
September | 0.405458E+11 | 20205.72 | 24-SEP-05:45 | 10.10 | 8.59 | 0.679994E+10 | 4601.95 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.416431E+11 | 32124.71 | 27-OCT-22:03 | 7.20 | 3.55 | 0.779891E+10 | 4906.54 | 27-OCT-22:10 | 7.20 | 3.55 |
November | 0.388907E+11 | 27229.02 | 01-NOV-22:26 | 9.40 | 5.08 | 0.782725E+10 | 4949.11 | 16-NOV-22:10 | 8.98 | 7.33 |
December | 0.376465E+11 | 23601.81 | 16-DEC-12:14 | 8.17 | 3.13 | 0.795769E+10 | 4837.08 | 19-DEC-23:10 | 4.60 | 3.30 |
Annual Sum or Average | 0.433622E+12 | 0.837800E+11 | ||||||||
Minimum of Months | 0.298709E+11 | 16074.38 | 7.12 | 3.13 | 0.610877E+10 | 3967.51 | 3.72 | 2.78 | ||
Maximum of Months | 0.416431E+11 | 32124.71 | 29.40 | 23.26 | 0.795769E+10 | 4949.11 | 27.12 | 23.29 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817458E+09 | 3291.09 | 17-JAN-12:50 | 9.90 | 5.45 | 0.623602E+09 | 367.91 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.994810E+09 | 3201.45 | 19-FEB-12:42 | 8.22 | 4.20 | 0.565793E+09 | 364.14 | 06-FEB-23:00 | -8.3 | -10.3 |
March | 0.177620E+10 | 3605.43 | 07-MAR-13:33 | 9.80 | 4.87 | 0.633679E+09 | 413.83 | 03-MAR-22:10 | 10.50 | 6.38 |
April | 0.240280E+10 | 2572.65 | 07-APR-12:40 | 26.33 | 16.04 | 0.612471E+09 | 422.92 | 07-APR-21:10 | 19.22 | 13.75 |
May | 0.358805E+10 | 2190.71 | 30-MAY-15:10 | 28.30 | 17.25 | 0.632472E+09 | 413.38 | 30-MAY-21:10 | 19.32 | 15.30 |
June | 0.467380E+10 | 2386.61 | 19-JUN-19:20 | 31.13 | 22.28 | 0.628905E+09 | 458.99 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.542853E+10 | 2409.79 | 08-JUL-12:40 | 31.47 | 25.92 | 0.673274E+09 | 458.63 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.563547E+10 | 2763.59 | 30-AUG-12:00 | 26.70 | 14.62 | 0.699766E+09 | 478.55 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.468284E+10 | 3482.80 | 30-SEP-12:40 | 20.40 | 12.34 | 0.643532E+09 | 460.05 | 01-SEP-21:10 | 26.60 | 18.07 |
October | 0.436653E+10 | 3714.46 | 04-OCT-12:10 | 24.50 | 18.62 | 0.672702E+09 | 439.97 | 04-OCT-21:10 | 17.12 | 15.79 |
November | 0.194493E+10 | 3185.62 | 29-NOV-12:43 | 8.30 | 4.79 | 0.612164E+09 | 413.38 | 02-NOV-21:10 | 12.62 | 7.04 |
December | 0.121829E+10 | 3747.73 | 03-DEC-12:44 | 8.22 | 3.54 | 0.627164E+09 | 367.38 | 04-DEC-22:19 | 7.97 | 7.49 |
Annual Sum or Average | 0.375297E+11 | 0.762552E+10 | ||||||||
Minimum of Months | 0.817458E+09 | 2190.71 | 8.22 | 3.54 | 0.565793E+09 | 364.14 | -8.3 | -10.3 | ||
Maximum of Months | 0.563547E+10 | 3747.73 | 31.47 | 25.92 | 0.699766E+09 | 478.55 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248974E+10 | 1929.40 | 21-JAN-20:06 | 7.12 | 6.40 | 0.767616E+09 | 526.41 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 0.230437E+10 | 2062.29 | 19-FEB-12:42 | 8.22 | 4.20 | 0.697239E+09 | 518.02 | 02-FEB-22:10 | -2.3 | -5.7 |
March | 0.284403E+10 | 2081.33 | 12-MAR-08:62 | 7.62 | 3.91 | 0.810472E+09 | 554.05 | 28-MAR-21:10 | 8.22 | 5.84 |
April | 0.299157E+10 | 2108.42 | 11-APR-22:30 | 7.75 | 1.07 | 0.793814E+09 | 562.60 | 11-APR-21:49 | 8.48 | 1.27 |
May | 0.349298E+10 | 1955.00 | 14-MAY-23:43 | 10.10 | 7.31 | 0.815821E+09 | 544.74 | 01-MAY-21:49 | 9.90 | 5.25 |
June | 0.386198E+10 | 1804.24 | 19-JUN-21:10 | 28.72 | 20.61 | 0.788107E+09 | 544.29 | 19-JUN-21:10 | 28.72 | 20.61 |
July | 0.419887E+10 | 1825.19 | 10-JUL-21:10 | 27.12 | 20.10 | 0.823462E+09 | 550.94 | 10-JUL-21:10 | 27.12 | 20.10 |
August | 0.426445E+10 | 1895.04 | 24-AUG-19:00 | 29.40 | 16.42 | 0.847404E+09 | 560.11 | 04-AUG-21:10 | 31.55 | 23.91 |
September | 0.379769E+10 | 1820.47 | 01-SEP-21:10 | 26.60 | 18.07 | 0.797058E+09 | 553.70 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.356643E+10 | 2259.63 | 08-OCT-22:00 | 6.70 | 3.55 | 0.855409E+09 | 569.68 | 18-OCT-21:19 | 8.87 | 6.06 |
November | 0.281854E+10 | 2131.27 | 05-NOV-22:01 | 7.20 | 4.44 | 0.787591E+09 | 566.55 | 07-NOV-22:10 | 8.22 | 6.90 |
December | 0.268139E+10 | 1983.35 | 16-DEC-12:14 | 8.17 | 3.13 | 0.787210E+09 | 529.93 | 18-DEC-22:10 | 2.20 | 0.94 |
Annual Sum or Average | 0.393120E+11 | 0.957120E+10 | ||||||||
Minimum of Months | 0.230437E+10 | 1804.24 | 6.70 | 1.07 | 0.697239E+09 | 518.02 | -2.3 | -5.7 | ||
Maximum of Months | 0.426445E+10 | 2259.63 | 29.40 | 20.61 | 0.855409E+09 | 569.68 | 31.55 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120007E+10 | 1712.70 | 21-JAN-20:06 | 7.12 | 6.40 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.102719E+10 | 1187.77 | 19-FEB-12:42 | 8.22 | 4.20 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.193956E+10 | 1818.41 | 28-MAR-22:45 | 7.30 | 4.60 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.240231E+10 | 1835.34 | 11-APR-22:30 | 7.75 | 1.07 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.305413E+10 | 1723.92 | 14-MAY-23:43 | 10.10 | 7.31 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.353759E+10 | 1595.69 | 22-JUN-20:00 | 26.70 | 16.74 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.390388E+10 | 1644.15 | 10-JUL-21:00 | 27.20 | 20.20 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.392225E+10 | 1701.71 | 24-AUG-19:00 | 29.40 | 16.42 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.341507E+10 | 1609.93 | 24-SEP-05:45 | 10.10 | 8.59 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.305202E+10 | 1969.56 | 18-OCT-08:18 | 7.57 | 4.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.213825E+10 | 1887.36 | 05-NOV-22:01 | 7.20 | 4.44 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.166343E+10 | 1616.42 | 20-DEC-11:34 | 8.90 | 5.15 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.312558E+11 | 0.00 | ||||||||
Minimum of Months | 0.102719E+10 | 1187.77 | 7.12 | 1.07 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.392225E+10 | 1969.56 | 29.40 | 20.20 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111286E+09 | 458.83 | 24-JAN-07:30 | 10.85 | 10.85 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 80585102.86 | 433.20 | 19-FEB-12:34 | 8.13 | 4.19 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.446786E+09 | 839.55 | 28-MAR-22:45 | 7.30 | 4.60 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.855474E+09 | 844.54 | 11-APR-22:30 | 7.75 | 1.07 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.134994E+10 | 799.15 | 14-MAY-23:43 | 10.10 | 7.31 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.167905E+10 | 746.96 | 19-JUN-21:10 | 28.72 | 20.61 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.187833E+10 | 768.55 | 10-JUL-21:10 | 27.12 | 20.10 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.188290E+10 | 802.49 | 24-AUG-19:00 | 29.40 | 16.42 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.159581E+10 | 745.33 | 01-SEP-21:10 | 26.60 | 18.07 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.139170E+10 | 912.52 | 18-OCT-08:18 | 7.57 | 4.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.660106E+09 | 860.54 | 05-NOV-22:01 | 7.20 | 4.44 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.208302E+09 | 505.39 | 03-DEC-12:44 | 8.22 | 3.54 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.121403E+11 | 0.00 | ||||||||
Minimum of Months | 80585102.86 | 433.20 | 7.20 | 1.07 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.188290E+10 | 912.52 | 29.40 | 20.61 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482742E+11 | 39629.07 | 24-JAN-20:26 | 8.60 | 6.55 | 0.569242E+09 | 403.35 | 24-JAN-22:10 | 6.60 | 4.00 |
February | 0.436225E+11 | 36006.63 | 17-FEB-21:00 | 1.10 | -0.7 | 0.513407E+09 | 396.53 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.496985E+11 | 39555.39 | 28-MAR-19:57 | 9.40 | 6.52 | 0.575488E+09 | 462.27 | 28-MAR-21:10 | 8.22 | 5.84 |
April | 0.489751E+11 | 41241.94 | 12-APR-20:40 | 8.33 | 1.80 | 0.552432E+09 | 486.37 | 04-APR-21:10 | 8.40 | 6.25 |
May | 0.521219E+11 | 38760.80 | 01-MAY-20:47 | 9.40 | 5.23 | 0.553240E+09 | 435.96 | 01-MAY-21:00 | 10.00 | 5.26 |
June | 0.516426E+11 | 38277.26 | 19-JUN-20:00 | 30.00 | 21.99 | 0.520278E+09 | 381.53 | 08-JUN-21:10 | 18.22 | 13.29 |
July | 0.538749E+11 | 38266.18 | 10-JUL-20:00 | 28.30 | 20.23 | 0.532264E+09 | 381.52 | 11-JUL-21:30 | 22.80 | 17.56 |
August | 0.542729E+11 | 38428.61 | 04-AUG-20:00 | 32.20 | 24.20 | 0.536605E+09 | 381.58 | 25-AUG-21:10 | 22.52 | 14.67 |
September | 0.511959E+11 | 38401.37 | 14-SEP-19:44 | 26.28 | 17.15 | 0.523448E+09 | 381.70 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.518190E+11 | 46013.45 | 26-OCT-21:20 | 8.13 | 3.60 | 0.561296E+09 | 486.99 | 27-OCT-21:30 | 7.20 | 3.62 |
November | 0.482735E+11 | 42067.01 | 16-NOV-21:00 | 8.30 | 6.69 | 0.555055E+09 | 493.47 | 16-NOV-22:10 | 8.98 | 7.33 |
December | 0.487705E+11 | 40865.69 | 17-DEC-19:37 | 7.07 | 2.96 | 0.571423E+09 | 421.01 | 04-DEC-21:10 | 8.72 | 7.92 |
Annual Sum or Average | 0.602542E+12 | 0.656418E+10 | ||||||||
Minimum of Months | 0.436225E+11 | 36006.63 | 1.10 | -0.7 | 0.513407E+09 | 381.52 | 2.02 | 0.23 | ||
Maximum of Months | 0.542729E+11 | 46013.45 | 32.20 | 24.20 | 0.575488E+09 | 493.47 | 22.80 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121884E+11 | 12739.12 | 17-JAN-12:50 | 9.90 | 5.45 | 0.871697E+10 | 6288.53 | 24-JAN-03:49 | 10.17 | 10.17 |
February | 0.119052E+11 | 13477.45 | 19-FEB-12:34 | 8.13 | 4.19 | 0.794865E+10 | 5898.60 | 22-FEB-22:40 | 2.20 | -0.7 |
March | 0.151187E+11 | 14493.59 | 07-MAR-13:33 | 9.80 | 4.87 | 0.931811E+10 | 6461.80 | 15-MAR-21:00 | 8.90 | 2.75 |
April | 0.160927E+11 | 11387.34 | 11-APR-22:30 | 7.75 | 1.07 | 0.916230E+10 | 6460.86 | 28-APR-23:10 | 10.00 | 7.19 |
May | 0.192119E+11 | 10549.27 | 17-MAY-03:05 | 10.00 | 8.82 | 0.954328E+10 | 6461.58 | 16-MAY-00:10 | 10.40 | 7.20 |
June | 0.216995E+11 | 10852.23 | 19-JUN-21:10 | 28.72 | 20.61 | 0.936089E+10 | 6461.97 | 19-JUN-22:19 | 27.43 | 20.23 |
July | 0.239925E+11 | 10787.90 | 10-JUL-21:10 | 27.12 | 20.10 | 0.988328E+10 | 6462.60 | 07-JUL-21:30 | 26.95 | 23.78 |
August | 0.245996E+11 | 11769.84 | 04-AUG-21:10 | 31.55 | 23.91 | 0.101962E+11 | 6462.69 | 22-AUG-21:30 | 25.00 | 15.24 |
September | 0.219458E+11 | 13243.64 | 30-SEP-12:30 | 20.30 | 12.31 | 0.958563E+10 | 6462.69 | 14-SEP-21:30 | 23.60 | 16.81 |
October | 0.212597E+11 | 13517.83 | 28-OCT-11:45 | 9.32 | 3.49 | 0.102058E+11 | 6564.40 | 27-OCT-22:10 | 7.20 | 3.55 |
November | 0.153252E+11 | 13166.04 | 18-NOV-12:32 | 7.20 | 3.87 | 0.904632E+10 | 6460.63 | 02-NOV-21:00 | 11.70 | 6.74 |
December | 0.138274E+11 | 15202.13 | 03-DEC-12:44 | 8.22 | 3.54 | 0.896723E+10 | 6087.88 | 04-DEC-22:40 | 8.13 | 7.50 |
Annual Sum or Average | 0.217167E+12 | 0.111935E+12 | ||||||||
Minimum of Months | 0.119052E+11 | 10549.27 | 7.20 | 1.07 | 0.794865E+10 | 5898.60 | 2.20 | -0.7 | ||
Maximum of Months | 0.245996E+11 | 15202.13 | 31.55 | 23.91 | 0.102058E+11 | 6564.40 | 27.43 | 23.78 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541896E+11 | 39088.13 | 21-JAN-20:06 | 7.12 | 6.40 | 0.274909E+11 | 18777.75 | 19-JAN-23:10 | 5.60 | 1.05 |
February | 0.500769E+11 | 42755.83 | 19-FEB-12:42 | 8.22 | 4.20 | 0.249658E+11 | 18378.48 | 22-FEB-23:10 | 2.20 | -0.6 |
March | 0.598567E+11 | 42336.60 | 28-MAR-22:45 | 7.30 | 4.60 | 0.289420E+11 | 19185.89 | 28-MAR-21:10 | 8.22 | 5.84 |
April | 0.621705E+11 | 42553.48 | 11-APR-22:30 | 7.75 | 1.07 | 0.282283E+11 | 19185.52 | 11-APR-21:49 | 8.48 | 1.27 |
May | 0.716485E+11 | 39468.88 | 17-MAY-03:05 | 10.00 | 8.82 | 0.289219E+11 | 19184.19 | 16-MAY-00:10 | 10.40 | 7.20 |
June | 0.780973E+11 | 36094.66 | 19-JUN-21:10 | 28.72 | 20.61 | 0.277315E+11 | 18804.49 | 19-JUN-22:10 | 27.62 | 20.12 |
July | 0.845532E+11 | 36457.20 | 10-JUL-21:10 | 27.12 | 20.10 | 0.288758E+11 | 18993.96 | 10-JUL-22:10 | 26.52 | 19.57 |
August | 0.855134E+11 | 37752.22 | 04-AUG-21:10 | 31.55 | 23.91 | 0.295621E+11 | 19182.05 | 17-AUG-21:30 | 27.50 | 21.04 |
September | 0.773593E+11 | 36531.26 | 30-SEP-05:20 | 10.77 | 9.64 | 0.281433E+11 | 19183.30 | 29-SEP-21:10 | 13.30 | 10.90 |
October | 0.737827E+11 | 60378.86 | 26-OCT-21:20 | 8.13 | 3.60 | 0.302971E+11 | 19608.21 | 27-OCT-22:10 | 7.20 | 3.55 |
November | 0.597032E+11 | 43518.79 | 05-NOV-22:01 | 7.20 | 4.44 | 0.282434E+11 | 19186.12 | 07-NOV-22:19 | 8.13 | 6.86 |
December | 0.574389E+11 | 41472.01 | 16-DEC-12:14 | 8.17 | 3.13 | 0.282632E+11 | 18930.41 | 04-DEC-22:40 | 8.13 | 7.50 |
Annual Sum or Average | 0.814390E+12 | 0.339665E+12 | ||||||||
Minimum of Months | 0.500769E+11 | 36094.66 | 7.12 | 1.07 | 0.249658E+11 | 18378.48 | 2.20 | -0.6 | ||
Maximum of Months | 0.855134E+11 | 60378.86 | 31.55 | 23.91 | 0.302971E+11 | 19608.21 | 27.62 | 21.04 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 61393729.88 | 3254.41 | 17-JAN-16:01 | 9.45 | 4.57 | 93441065.50 | 56.69 | 14-JAN-04:19 | -6.9 | -7.5 |
February | 77650437.98 | 3240.81 | 02-FEB-16:01 | 4.13 | -1.9 | 84872276.10 | 56.69 | 06-FEB-23:00 | -8.3 | -10.3 |
March | 0.256459E+09 | 3324.44 | 07-MAR-16:01 | 7.93 | 4.56 | 95695986.72 | 60.17 | 27-MAR-20:30 | 15.25 | 11.54 |
April | 0.488499E+09 | 3579.09 | 09-APR-17:31 | 15.37 | 13.32 | 94521368.50 | 77.60 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.876635E+09 | 3623.22 | 27-MAY-21:11 | 19.23 | 10.67 | 0.102455E+09 | 87.93 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.141827E+10 | 3466.36 | 20-JUN-21:11 | 20.93 | 17.06 | 0.105612E+09 | 89.16 | 26-JUN-21:10 | 22.20 | 19.61 |
July | 0.185230E+10 | 3427.50 | 04-JUL-21:11 | 21.50 | 18.54 | 0.109405E+09 | 90.81 | 05-JUL-21:10 | 22.70 | 21.96 |
August | 0.201536E+10 | 3612.43 | 25-AUG-21:11 | 22.23 | 14.65 | 0.108953E+09 | 91.54 | 10-AUG-21:10 | 23.30 | 21.47 |
September | 0.117884E+10 | 3606.42 | 10-SEP-21:11 | 17.43 | 10.25 | 0.102954E+09 | 89.78 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.826392E+09 | 3380.20 | 30-OCT-16:01 | 15.32 | 7.98 | 0.101137E+09 | 76.34 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.166623E+09 | 3283.58 | 02-NOV-15:01 | 16.60 | 8.89 | 91949173.17 | 56.69 | 03-NOV-21:40 | 12.80 | 10.26 |
December | 74355539.18 | 3199.70 | 17-DEC-16:01 | 9.82 | 4.15 | 93874023.64 | 56.69 | 22-DEC-04:19 | -3.5 | -6.1 |
Annual Sum or Average | 0.929278E+10 | 0.118487E+10 | ||||||||
Minimum of Months | 61393729.88 | 3199.70 | 4.13 | -1.9 | 84872276.10 | 56.69 | -8.3 | -10.3 | ||
Maximum of Months | 0.201536E+10 | 3623.22 | 22.23 | 18.54 | 0.109405E+09 | 91.54 | 23.80 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35550024.00 | 1266.97 | 17-JAN-16:01 | 9.45 | 4.57 | 92737604.99 | 56.69 | 05-JAN-03:39 | -7.2 | -9.0 |
February | 38459844.88 | 2331.48 | 20-FEB-16:01 | 7.12 | 4.39 | 83942249.32 | 56.69 | 13-FEB-02:49 | -8.2 | -10.3 |
March | 0.161918E+09 | 3206.12 | 11-MAR-16:01 | 11.20 | 5.38 | 94696274.09 | 57.25 | 27-MAR-20:30 | 15.25 | 11.54 |
April | 0.396224E+09 | 3455.90 | 09-APR-17:31 | 15.37 | 13.32 | 93924345.93 | 74.50 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.829043E+09 | 3554.25 | 27-MAY-21:11 | 19.23 | 10.67 | 0.102171E+09 | 87.27 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.138345E+10 | 3425.94 | 22-JUN-21:11 | 25.73 | 16.09 | 0.105496E+09 | 88.86 | 26-JUN-21:10 | 22.20 | 19.61 |
July | 0.179868E+10 | 3367.74 | 04-JUL-21:11 | 21.50 | 18.54 | 0.109246E+09 | 90.45 | 05-JUL-21:10 | 22.70 | 21.96 |
August | 0.185729E+10 | 3475.88 | 28-AUG-21:11 | 19.80 | 14.66 | 0.108354E+09 | 90.22 | 10-AUG-21:10 | 23.30 | 21.47 |
September | 0.980583E+09 | 3439.84 | 10-SEP-21:11 | 17.43 | 10.25 | 0.101686E+09 | 87.13 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.512325E+09 | 3214.96 | 30-OCT-15:01 | 16.52 | 8.25 | 99294721.47 | 72.16 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 89200680.96 | 3064.59 | 03-NOV-15:02 | 16.83 | 10.86 | 90928881.07 | 56.69 | 03-NOV-21:30 | 12.80 | 10.23 |
December | 41374246.92 | 610.81 | 25-DEC-16:03 | 9.40 | 7.15 | 92847546.03 | 56.69 | 23-DEC-00:20 | 3.17 | 2.67 |
Annual Sum or Average | 0.812410E+10 | 0.117532E+10 | ||||||||
Minimum of Months | 35550024.00 | 610.81 | 7.12 | 4.39 | 83942249.32 | 56.69 | -8.2 | -10.3 | ||
Maximum of Months | 0.185729E+10 | 3554.25 | 25.73 | 18.54 | 0.109246E+09 | 90.45 | 23.80 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.129455E+09 | 195.93 | 19-JAN-14:10 | 9.32 | 3.66 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.172044E+09 | 338.67 | 03-FEB-12:30 | -1.4 | -4.9 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.237363E+09 | 421.74 | 03-MAR-13:30 | 14.70 | 8.31 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.279773E+09 | 491.85 | 08-APR-12:30 | 23.60 | 16.17 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.366641E+09 | 426.56 | 30-MAY-16:40 | 26.50 | 18.20 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.527066E+09 | 497.37 | 25-JUN-21:00 | 26.70 | 19.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.740144E+09 | 561.43 | 21-JUL-18:00 | 26.70 | 22.65 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.807336E+09 | 544.15 | 01-AUG-19:01 | 26.60 | 22.51 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.619380E+09 | 631.25 | 28-SEP-12:30 | 23.05 | 14.06 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.616917E+09 | 693.99 | 04-OCT-12:00 | 24.40 | 18.64 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.294977E+09 | 602.37 | 02-NOV-12:30 | 15.30 | 8.09 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.211771E+09 | 509.41 | 17-DEC-12:30 | 12.20 | 4.70 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.500287E+10 | 0.00 | ||||||||
Minimum of Months | 0.129455E+09 | 195.93 | -1.4 | -4.9 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.807336E+09 | 693.99 | 26.70 | 22.65 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80689108.52 | 695.94 | 22-JAN-09:02 | 5.10 | 4.57 | 94037010.53 | 56.69 | 19-JAN-22:10 | 5.60 | 1.05 |
February | 66017610.72 | 723.84 | 20-FEB-09:02 | 5.87 | 1.95 | 84906163.39 | 56.69 | 01-FEB-22:10 | 4.90 | 2.78 |
March | 0.180521E+09 | 1007.91 | 28-MAR-18:01 | 10.00 | 6.78 | 95200590.18 | 56.69 | 27-MAR-21:10 | 14.13 | 10.86 |
April | 0.344077E+09 | 1078.56 | 07-APR-21:11 | 19.03 | 13.69 | 93217571.58 | 70.40 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.553637E+09 | 1160.04 | 27-MAY-21:11 | 19.23 | 10.67 | 99391672.43 | 77.80 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.722046E+09 | 1154.47 | 04-JUN-08:11 | 22.57 | 12.57 | 0.100906E+09 | 81.63 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.897138E+09 | 1112.74 | 04-JUL-21:11 | 21.50 | 18.54 | 0.106527E+09 | 83.52 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.861380E+09 | 1157.32 | 28-AUG-21:11 | 19.80 | 14.66 | 0.104902E+09 | 82.87 | 03-AUG-21:10 | 26.02 | 24.78 |
September | 0.605648E+09 | 1136.37 | 01-SEP-21:11 | 26.50 | 17.93 | 98729672.72 | 80.05 | 05-SEP-21:10 | 23.90 | 20.41 |
October | 0.401929E+09 | 1052.13 | 25-OCT-21:11 | 16.83 | 7.69 | 97275930.49 | 68.65 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.196902E+09 | 979.57 | 02-NOV-18:02 | 13.80 | 7.35 | 92057793.13 | 56.69 | 01-NOV-21:10 | 9.90 | 5.48 |
December | 91934576.18 | 787.55 | 25-DEC-09:02 | 10.50 | 10.21 | 94223296.80 | 56.69 | 19-DEC-22:10 | 5.40 | 2.50 |
Annual Sum or Average | 0.500192E+10 | 0.116137E+10 | ||||||||
Minimum of Months | 66017610.72 | 695.94 | 5.10 | 1.95 | 84906163.39 | 56.69 | 4.90 | 1.05 | ||
Maximum of Months | 0.897138E+09 | 1160.04 | 26.50 | 18.54 | 0.106527E+09 | 83.52 | 26.02 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70635690.90 | 2078.04 | 19-JAN-09:02 | 4.97 | 3.19 | 93437915.74 | 56.69 | 14-JAN-05:49 | -7.7 | -8.3 |
February | 84758247.65 | 2861.74 | 25-FEB-09:02 | -2.0 | -5.2 | 84969088.25 | 56.69 | 07-FEB-00:10 | -8.4 | -10.4 |
March | 0.234249E+09 | 2964.59 | 11-MAR-09:02 | 5.87 | 1.43 | 95574328.39 | 56.69 | 03-MAR-22:19 | 10.40 | 6.33 |
April | 0.510885E+09 | 3302.54 | 08-APR-08:11 | 20.57 | 15.12 | 94177097.03 | 74.46 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.935308E+09 | 3733.58 | 30-MAY-08:11 | 25.37 | 16.09 | 0.101489E+09 | 80.02 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.135812E+10 | 3688.46 | 26-JUN-08:11 | 24.27 | 18.52 | 0.103041E+09 | 82.00 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.183039E+10 | 3612.93 | 14-JUL-07:31 | 27.23 | 20.74 | 0.108242E+09 | 83.18 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.200195E+10 | 3769.99 | 22-AUG-08:11 | 27.07 | 18.46 | 0.107595E+09 | 85.06 | 03-AUG-21:10 | 26.02 | 24.78 |
September | 0.122233E+10 | 3591.71 | 06-SEP-08:11 | 24.47 | 18.71 | 0.101506E+09 | 83.54 | 05-SEP-21:10 | 23.90 | 20.41 |
October | 0.814274E+09 | 3009.33 | 30-OCT-15:01 | 16.52 | 8.25 | 0.100224E+09 | 72.93 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.205753E+09 | 2974.22 | 02-NOV-15:01 | 16.60 | 8.89 | 92131997.94 | 56.69 | 02-NOV-21:40 | 12.07 | 6.86 |
December | 95372464.73 | 2864.12 | 17-DEC-09:02 | 6.05 | 2.93 | 93934804.50 | 56.69 | 28-DEC-00:20 | 0.77 | 0.30 |
Annual Sum or Average | 0.936402E+10 | 0.117632E+10 | ||||||||
Minimum of Months | 70635690.90 | 2078.04 | -2.0 | -5.2 | 84969088.25 | 56.69 | -8.4 | -10.4 | ||
Maximum of Months | 0.200195E+10 | 3769.99 | 27.23 | 20.74 | 0.108242E+09 | 85.06 | 26.02 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34941556.62 | 721.02 | 30-JAN-09:03 | -3.0 | -4.7 | 92758267.37 | 56.69 | 01-JAN-02:20 | -4.2 | -5.7 |
February | 40609720.31 | 2564.42 | 25-FEB-09:02 | -2.0 | -5.2 | 84022846.90 | 56.69 | 08-FEB-03:30 | -5.5 | -7.7 |
March | 0.146901E+09 | 2908.86 | 29-MAR-08:62 | 4.60 | 2.26 | 94543927.08 | 56.69 | 27-MAR-21:10 | 14.13 | 10.86 |
April | 0.419661E+09 | 3237.87 | 08-APR-08:11 | 20.57 | 15.12 | 93578685.58 | 71.79 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.886682E+09 | 3710.24 | 30-MAY-08:11 | 25.37 | 16.09 | 0.101265E+09 | 79.61 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.132265E+10 | 3675.10 | 22-JUN-08:11 | 24.80 | 16.37 | 0.102959E+09 | 81.46 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.177637E+10 | 3583.37 | 14-JUL-07:31 | 27.23 | 20.74 | 0.108100E+09 | 82.72 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.184205E+10 | 3718.31 | 22-AUG-08:11 | 27.07 | 18.46 | 0.107096E+09 | 84.11 | 03-AUG-21:10 | 26.02 | 24.78 |
September | 0.101884E+10 | 3527.90 | 03-SEP-08:11 | 21.67 | 15.05 | 0.100388E+09 | 81.11 | 05-SEP-21:10 | 23.90 | 20.41 |
October | 0.505976E+09 | 2828.01 | 16-OCT-08:62 | 14.37 | 11.79 | 98181015.88 | 69.07 | 05-OCT-21:19 | 18.90 | 17.68 |
November | 0.111057E+09 | 2543.97 | 04-NOV-08:62 | 12.57 | 9.41 | 91109473.51 | 56.69 | 03-NOV-21:19 | 12.80 | 10.19 |
December | 43539371.85 | 1385.23 | 17-DEC-09:02 | 6.05 | 2.93 | 92908962.83 | 56.69 | 05-DEC-04:19 | 6.50 | 5.29 |
Annual Sum or Average | 0.814927E+10 | 0.116691E+10 | ||||||||
Minimum of Months | 34941556.62 | 721.02 | -3.0 | -5.2 | 84022846.90 | 56.69 | -5.5 | -7.7 | ||
Maximum of Months | 0.184205E+10 | 3718.31 | 27.23 | 20.74 | 0.108100E+09 | 84.11 | 26.02 | 24.78 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 78154170.31 | 1204.43 | 17-JAN-13:55 | 11.10 | 5.13 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.139666E+09 | 1296.63 | 19-FEB-12:42 | 8.22 | 4.20 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.575353E+09 | 1425.63 | 03-MAR-14:10 | 15.00 | 8.57 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.127196E+10 | 1786.71 | 08-APR-11:50 | 24.13 | 16.16 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.250272E+10 | 1824.30 | 30-MAY-08:30 | 25.55 | 16.29 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.378895E+10 | 1845.85 | 20-JUN-19:20 | 22.23 | 17.07 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.444716E+10 | 1847.32 | 10-JUL-18:40 | 29.27 | 20.19 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.452392E+10 | 2001.61 | 24-AUG-19:00 | 29.40 | 16.42 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.339913E+10 | 1853.81 | 07-SEP-21:10 | 23.80 | 21.51 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.254249E+10 | 1817.64 | 04-OCT-14:00 | 24.40 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.573823E+09 | 1566.96 | 04-NOV-12:40 | 17.80 | 12.64 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.191042E+09 | 1363.97 | 03-DEC-12:44 | 8.22 | 3.54 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.240344E+11 | 0.00 | ||||||||
Minimum of Months | 78154170.31 | 1204.43 | 8.22 | 3.54 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.452392E+10 | 2001.61 | 29.40 | 21.51 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50092775.23 | 3413.90 | 17-JAN-16:01 | 9.45 | 4.57 | 93095280.64 | 56.69 | 31-JAN-05:00 | -8.3 | -10.5 |
February | 70272731.74 | 3400.71 | 02-FEB-16:01 | 4.13 | -1.9 | 84555163.57 | 56.69 | 13-FEB-02:30 | -8.1 | -10.2 |
March | 0.259848E+09 | 3483.63 | 07-MAR-16:01 | 7.93 | 4.56 | 95545910.57 | 68.69 | 27-MAR-18:10 | 18.80 | 14.34 |
April | 0.543551E+09 | 4116.86 | 09-APR-17:31 | 15.37 | 13.32 | 94914297.85 | 87.90 | 07-APR-21:10 | 19.22 | 13.75 |
May | 0.104202E+10 | 3832.53 | 17-MAY-20:01 | 15.50 | 13.03 | 0.104096E+09 | 98.24 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.177160E+10 | 3921.33 | 04-JUN-21:11 | 17.60 | 12.57 | 0.108785E+09 | 99.73 | 26-JUN-21:10 | 22.20 | 19.61 |
July | 0.228983E+10 | 3876.96 | 04-JUL-21:11 | 21.50 | 18.54 | 0.111939E+09 | 102.33 | 05-JUL-21:10 | 22.70 | 21.96 |
August | 0.244875E+10 | 4035.70 | 25-AUG-21:11 | 22.23 | 14.65 | 0.111435E+09 | 103.85 | 10-AUG-21:10 | 23.30 | 21.47 |
September | 0.142060E+10 | 3861.17 | 03-SEP-21:11 | 21.50 | 16.81 | 0.105367E+09 | 99.67 | 06-SEP-21:10 | 22.70 | 20.80 |
October | 0.909796E+09 | 3629.13 | 30-OCT-16:01 | 15.32 | 7.98 | 0.102059E+09 | 82.44 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.149391E+09 | 3436.91 | 02-NOV-15:01 | 16.60 | 8.89 | 91621179.82 | 56.69 | 02-NOV-21:30 | 12.25 | 6.92 |
December | 60165473.15 | 3381.71 | 17-DEC-16:01 | 9.82 | 4.15 | 93480503.46 | 56.69 | 08-DEC-04:19 | 4.27 | 1.19 |
Annual Sum or Average | 0.110159E+11 | 0.119689E+10 | ||||||||
Minimum of Months | 50092775.23 | 3381.71 | 4.13 | -1.9 | 84555163.57 | 56.69 | -8.3 | -10.5 | ||
Maximum of Months | 0.244875E+10 | 4116.86 | 22.23 | 18.54 | 0.111939E+09 | 103.85 | 23.30 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21691925.48 | 741.16 | 20-JAN-16:03 | 6.93 | 3.70 | 92519520.18 | 56.69 | 16-JAN-05:30 | -4.7 | -6.2 |
February | 27086674.66 | 1902.36 | 20-FEB-16:01 | 7.12 | 4.39 | 83719828.53 | 56.69 | 15-FEB-04:49 | -7.1 | -8.2 |
March | 0.153193E+09 | 3356.99 | 11-MAR-16:01 | 11.20 | 5.38 | 94487227.49 | 61.00 | 27-MAR-18:10 | 18.80 | 14.34 |
April | 0.433361E+09 | 3886.79 | 09-APR-17:31 | 15.37 | 13.32 | 94197135.06 | 80.39 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.985956E+09 | 3748.95 | 12-MAY-18:51 | 15.00 | 12.45 | 0.103873E+09 | 97.69 | 31-MAY-21:10 | 20.48 | 17.57 |
June | 0.173477E+10 | 3850.21 | 04-JUN-21:11 | 17.60 | 12.57 | 0.108731E+09 | 99.62 | 26-JUN-21:10 | 22.20 | 19.61 |
July | 0.223392E+10 | 3810.96 | 04-JUL-21:11 | 21.50 | 18.54 | 0.111781E+09 | 102.11 | 05-JUL-21:10 | 22.70 | 21.96 |
August | 0.227791E+10 | 3920.18 | 25-AUG-21:11 | 22.23 | 14.65 | 0.110832E+09 | 102.43 | 10-AUG-21:10 | 23.30 | 21.47 |
September | 0.118546E+10 | 3719.92 | 03-SEP-21:11 | 21.50 | 16.81 | 0.103999E+09 | 96.54 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.551033E+09 | 3364.35 | 04-OCT-15:02 | 23.72 | 19.11 | 0.100059E+09 | 76.63 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 72737464.48 | 3215.79 | 03-NOV-15:02 | 16.83 | 10.86 | 90617648.33 | 56.69 | 03-NOV-22:10 | 12.80 | 10.38 |
December | 27883557.82 | 558.12 | 15-DEC-16:04 | 4.32 | 0.71 | 92533704.40 | 56.69 | 22-DEC-04:19 | -3.5 | -6.1 |
Annual Sum or Average | 0.970501E+10 | 0.118735E+10 | ||||||||
Minimum of Months | 21691925.48 | 558.12 | 4.32 | 0.71 | 83719828.53 | 56.69 | -7.1 | -8.2 | ||
Maximum of Months | 0.227791E+10 | 3920.18 | 23.72 | 19.11 | 0.111781E+09 | 102.43 | 23.80 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163165E+09 | 1652.69 | 17-JAN-16:01 | 9.45 | 4.57 | 94989349.53 | 56.69 | 17-JAN-22:19 | 2.20 | 1.87 |
February | 0.204685E+09 | 1646.22 | 02-FEB-16:01 | 4.13 | -1.9 | 86628617.54 | 56.69 | 17-FEB-22:10 | 2.02 | 0.23 |
March | 0.321100E+09 | 1648.56 | 15-MAR-15:02 | 14.90 | 6.01 | 96519589.58 | 60.38 | 27-MAR-20:30 | 15.25 | 11.54 |
April | 0.402430E+09 | 1712.41 | 07-APR-21:11 | 19.03 | 13.69 | 94517124.23 | 80.82 | 07-APR-21:19 | 19.03 | 13.69 |
May | 0.609203E+09 | 1741.85 | 27-MAY-21:11 | 19.23 | 10.67 | 0.101112E+09 | 81.94 | 31-MAY-21:19 | 20.37 | 17.53 |
June | 0.935866E+09 | 1738.29 | 22-JUN-21:11 | 25.73 | 16.09 | 0.103033E+09 | 90.14 | 15-JUN-21:10 | 23.40 | 21.81 |
July | 0.128423E+10 | 1689.51 | 30-JUL-21:11 | 23.13 | 21.99 | 0.108844E+09 | 88.52 | 21-JUL-21:10 | 25.60 | 23.68 |
August | 0.141611E+10 | 1868.51 | 25-AUG-21:11 | 22.23 | 14.65 | 0.108137E+09 | 92.64 | 31-AUG-21:10 | 24.35 | 20.86 |
September | 0.104526E+10 | 1797.39 | 10-SEP-21:11 | 17.43 | 10.25 | 0.103183E+09 | 94.30 | 07-SEP-21:10 | 23.80 | 21.51 |
October | 0.989646E+09 | 1736.93 | 30-OCT-16:01 | 15.32 | 7.98 | 0.101837E+09 | 81.90 | 04-OCT-21:19 | 17.03 | 15.77 |
November | 0.353745E+09 | 1654.37 | 02-NOV-15:01 | 16.60 | 8.89 | 93604662.86 | 56.69 | 03-NOV-21:10 | 12.80 | 10.16 |
December | 0.260261E+09 | 1647.13 | 17-DEC-16:01 | 9.82 | 4.15 | 95578549.50 | 56.69 | 18-DEC-22:10 | 2.20 | 0.94 |
Annual Sum or Average | 0.798570E+10 | 0.118798E+10 | ||||||||
Minimum of Months | 0.163165E+09 | 1646.22 | 4.13 | -1.9 | 86628617.54 | 56.69 | 2.02 | 0.23 | ||
Maximum of Months | 0.141611E+10 | 1868.51 | 25.73 | 21.99 | 0.108844E+09 | 94.30 | 25.60 | 23.68 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.306493E+11 | 22692.40 | 24-JAN-05:28 | 10.55 | 10.55 | 0.184474E+11 | 11797.46 | 24-JAN-03:49 | 10.17 | 10.17 |
February | 0.275689E+11 | 19833.46 | 19-FEB-12:42 | 8.22 | 4.20 | 0.166551E+11 | 11347.95 | 17-FEB-04:19 | 1.50 | -1.3 |
March | 0.332190E+11 | 27344.97 | 06-MAR-23:35 | 8.17 | 4.34 | 0.189107E+11 | 12570.17 | 07-MAR-00:10 | 7.62 | 3.80 |
April | 0.346567E+11 | 29039.87 | 11-APR-22:30 | 7.75 | 1.07 | 0.183067E+11 | 12291.71 | 17-APR-22:40 | 7.80 | 7.59 |
May | 0.391733E+11 | 23812.23 | 15-MAY-01:08 | 10.22 | 7.16 | 0.188791E+11 | 11994.76 | 04-MAY-03:30 | 10.00 | 9.66 |
June | 0.411045E+11 | 22105.27 | 19-JUN-21:10 | 28.72 | 20.61 | 0.182597E+11 | 11349.09 | 02-JUN-21:19 | 15.60 | 9.68 |
July | 0.440220E+11 | 22094.75 | 10-JUL-21:10 | 27.12 | 20.10 | 0.188550E+11 | 11348.92 | 11-JUL-21:30 | 22.80 | 17.56 |
August | 0.438678E+11 | 22482.24 | 04-AUG-21:10 | 31.55 | 23.91 | 0.189612E+11 | 11348.98 | 25-AUG-21:30 | 21.95 | 14.63 |
September | 0.394862E+11 | 21347.81 | 01-SEP-21:12 | 26.50 | 17.93 | 0.181063E+11 | 11484.51 | 29-SEP-23:00 | 11.10 | 9.60 |
October | 0.372330E+11 | 29335.54 | 27-OCT-22:03 | 7.20 | 3.55 | 0.187914E+11 | 12308.14 | 27-OCT-21:30 | 7.20 | 3.62 |
November | 0.321917E+11 | 28984.53 | 05-NOV-22:01 | 7.20 | 4.44 | 0.181512E+11 | 12088.54 | 16-NOV-22:10 | 8.98 | 7.33 |
December | 0.313518E+11 | 21308.08 | 25-DEC-10:17 | 9.43 | 9.43 | 0.186385E+11 | 11425.50 | 04-DEC-22:19 | 7.97 | 7.49 |
Annual Sum or Average | 0.434524E+12 | 0.220962E+12 | ||||||||
Minimum of Months | 0.275689E+11 | 19833.46 | 7.20 | 1.07 | 0.166551E+11 | 11347.95 | 1.50 | -1.3 | ||
Maximum of Months | 0.440220E+11 | 29335.54 | 31.55 | 23.91 | 0.189612E+11 | 12570.17 | 22.80 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341610E+11 | 25461.36 | 24-JAN-00:14 | 10.00 | 10.00 | 0.187635E+11 | 11899.77 | 23-JAN-23:40 | 10.20 | 10.09 |
February | 0.306864E+11 | 21413.34 | 19-FEB-12:42 | 8.22 | 4.20 | 0.169447E+11 | 11348.02 | 27-FEB-00:20 | -0.9 | -4.5 |
March | 0.370569E+11 | 30554.64 | 06-MAR-23:35 | 8.17 | 4.34 | 0.191099E+11 | 12713.44 | 07-MAR-00:10 | 7.62 | 3.80 |
April | 0.384611E+11 | 32095.73 | 11-APR-22:30 | 7.75 | 1.07 | 0.184865E+11 | 12410.50 | 17-APR-22:40 | 7.80 | 7.59 |
May | 0.430731E+11 | 25142.59 | 16-MAY-00:10 | 10.40 | 7.20 | 0.190579E+11 | 12034.76 | 04-MAY-03:30 | 10.00 | 9.66 |
June | 0.446597E+11 | 23874.29 | 19-JUN-21:10 | 28.72 | 20.61 | 0.184169E+11 | 11349.09 | 02-JUN-21:19 | 15.60 | 9.68 |
July | 0.475160E+11 | 23704.85 | 07-JUL-22:00 | 28.30 | 24.27 | 0.189989E+11 | 11348.93 | 11-JUL-21:30 | 22.80 | 17.56 |
August | 0.473074E+11 | 24084.30 | 04-AUG-21:10 | 31.55 | 23.91 | 0.190899E+11 | 11348.99 | 25-AUG-21:30 | 21.95 | 14.63 |
September | 0.429951E+11 | 24110.43 | 24-SEP-05:03 | 10.50 | 8.73 | 0.182949E+11 | 11532.38 | 29-SEP-23:00 | 11.10 | 9.60 |
October | 0.409788E+11 | 31257.62 | 27-OCT-22:40 | 7.20 | 3.34 | 0.189620E+11 | 12370.33 | 27-OCT-21:30 | 7.20 | 3.62 |
November | 0.358476E+11 | 27966.27 | 05-NOV-22:10 | 7.20 | 4.44 | 0.183631E+11 | 12219.19 | 16-NOV-22:10 | 8.98 | 7.33 |
December | 0.350048E+11 | 24983.20 | 17-DEC-19:37 | 7.07 | 2.96 | 0.188839E+11 | 11548.60 | 04-DEC-22:19 | 7.97 | 7.49 |
Annual Sum or Average | 0.477748E+12 | 0.223372E+12 | ||||||||
Minimum of Months | 0.306864E+11 | 21413.34 | 7.07 | 1.07 | 0.169447E+11 | 11348.02 | -0.9 | -4.5 | ||
Maximum of Months | 0.475160E+11 | 32095.73 | 31.55 | 24.27 | 0.191099E+11 | 12713.44 | 22.80 | 17.56 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487533E+11 | 31276.97 | 19-JAN-15:20 | 8.70 | 3.36 | 0.187870E+11 | 11366.61 | 17-JAN-16:49 | 7.25 | 3.30 |
February | 0.442074E+11 | 30112.35 | 20-FEB-14:30 | 8.60 | 4.57 | 0.169641E+11 | 11354.93 | 18-FEB-18:00 | 2.80 | 1.19 |
March | 0.513050E+11 | 33178.69 | 11-MAR-17:36 | 8.37 | 5.02 | 0.188194E+11 | 11557.53 | 25-MAR-17:40 | 7.40 | 7.07 |
April | 0.515653E+11 | 31396.56 | 02-APR-17:56 | 7.80 | 2.83 | 0.182169E+11 | 11474.33 | 22-APR-17:49 | 10.60 | 7.07 |
May | 0.558512E+11 | 30364.15 | 01-MAY-06:24 | 8.60 | 5.45 | 0.187986E+11 | 11349.95 | 13-MAY-17:00 | 12.80 | 8.06 |
June | 0.560476E+11 | 31323.73 | 01-JUN-18:05 | 27.70 | 16.08 | 0.181523E+11 | 11319.53 | 03-JUN-17:19 | 18.13 | 13.48 |
July | 0.590937E+11 | 30600.22 | 08-JUL-10:50 | 30.82 | 25.25 | 0.187410E+11 | 11319.53 | 29-JUL-17:19 | 24.80 | 20.15 |
August | 0.593002E+11 | 31567.53 | 25-AUG-17:04 | 26.52 | 14.93 | 0.187533E+11 | 11319.57 | 12-AUG-17:19 | 27.97 | 24.46 |
September | 0.550462E+11 | 30279.22 | 04-SEP-10:40 | 25.60 | 17.72 | 0.181579E+11 | 11319.57 | 23-SEP-17:19 | 15.93 | 10.25 |
October | 0.545164E+11 | 34418.13 | 18-OCT-08:18 | 7.57 | 4.00 | 0.188061E+11 | 11428.23 | 28-OCT-17:40 | 8.67 | 2.85 |
November | 0.494090E+11 | 33919.39 | 17-NOV-07:30 | 7.75 | 7.24 | 0.182055E+11 | 11357.22 | 18-NOV-18:00 | 5.00 | 1.73 |
December | 0.494934E+11 | 36464.16 | 20-DEC-11:34 | 8.90 | 5.15 | 0.187957E+11 | 11356.65 | 16-DEC-18:00 | 6.70 | 2.69 |
Annual Sum or Average | 0.634589E+12 | 0.221198E+12 | ||||||||
Minimum of Months | 0.442074E+11 | 30112.35 | 7.57 | 2.83 | 0.169641E+11 | 11319.53 | 2.80 | 1.19 | ||
Maximum of Months | 0.593002E+11 | 36464.16 | 30.82 | 25.25 | 0.188194E+11 | 11557.53 | 27.97 | 24.46 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.882431E+09 | 4665.77 | 19-JAN-15:20 | 8.70 | 3.36 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.102800E+10 | 5219.80 | 19-FEB-12:42 | 8.22 | 4.20 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.299689E+10 | 4872.60 | 11-MAR-17:36 | 8.37 | 5.02 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.487568E+10 | 4304.29 | 19-APR-17:15 | 8.53 | 4.53 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.755038E+10 | 4401.83 | 14-MAY-23:43 | 10.10 | 7.31 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.959555E+10 | 4407.28 | 19-JUN-14:40 | 33.67 | 23.40 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.108008E+11 | 4544.17 | 10-JUL-14:00 | 32.80 | 20.87 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.108098E+11 | 4637.62 | 24-AUG-19:00 | 29.40 | 16.42 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.878375E+10 | 4384.58 | 01-SEP-13:50 | 31.02 | 17.49 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.699616E+10 | 4840.73 | 08-OCT-22:00 | 6.70 | 3.55 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.297217E+10 | 4552.35 | 06-NOV-10:00 | 8.90 | 4.98 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.129566E+10 | 4905.01 | 16-DEC-12:14 | 8.17 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.685873E+11 | 0.00 | ||||||||
Minimum of Months | 0.882431E+09 | 4304.29 | 6.70 | 3.13 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.108098E+11 | 5219.80 | 33.67 | 23.40 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 10855.23 | 54.28 | 07-MAR-11:57 | 8.30 |
April | 19885.93 | 265.87 | 03-APR-17:03 | 7.62 |
May | 14277.04 | 237.95 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 45018.21 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 19885.93 | 265.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.753923E+09 | 1583.66 | 02-JAN-07:20 | -11.5 |
February | 0.594063E+09 | 1589.89 | 06-FEB-07:10 | -13.2 |
March | 0.139017E+09 | 726.10 | 18-MAR-06:20 | -1.7 |
April | 22515740.85 | 336.14 | 01-APR-06:05 | 2.38 |
May | 13896.73 | 231.61 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 440692.92 | 348.40 | 08-OCT-20:40 | 7.97 |
November | 91715535.66 | 819.42 | 23-NOV-06:00 | -3.9 |
December | 0.359851E+09 | 887.83 | 31-DEC-06:00 | -1.7 |
Annual Sum or Average | 0.196154E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.753923E+09 | 1589.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18881.29 | 31.15 | 18-JAN-07:52 | 8.90 |
February | 8865.28 | 51.92 | 19-FEB-12:33 | 8.13 |
March | 7644.80 | 35.91 | 07-MAR-11:57 | 8.30 |
April | 23724.71 | 63.48 | 23-APR-06:16 | 8.67 |
May | 1114.72 | 18.58 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 1404.12 | 4.68 | 08-OCT-20:40 | 7.97 |
November | 57610.17 | 120.26 | 07-NOV-08:17 | 7.57 |
December | 18439.34 | 59.83 | 25-DEC-17:20 | 8.30 |
Annual Sum or Average | 137684.44 | |||
Minimum of Months | 0.00 | 0.00 | 7.57 | |
Maximum of Months | 57610.17 | 120.26 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32161785.04 | 481.02 | 02-JAN-05:00 | -12.2 |
February | 43666531.86 | 444.40 | 06-FEB-05:00 | -13.3 |
March | 266386.37 | 166.07 | 07-MAR-11:57 | 8.30 |
April | 279877.25 | 203.21 | 23-APR-06:16 | 8.67 |
May | 7501.90 | 125.03 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 250460.45 | 247.49 | 08-OCT-20:40 | 7.97 |
November | 388314.50 | 273.04 | 07-NOV-08:17 | 7.57 |
December | 160037.21 | 175.29 | 17-DEC-18:10 | 8.22 |
Annual Sum or Average | 77180894.59 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 43666531.86 | 481.02 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358753E+09 | 592.20 | 02-JAN-05:00 | -12.2 |
February | 0.356501E+09 | 591.48 | 06-FEB-05:00 | -13.3 |
March | 52142150.61 | 250.39 | 23-MAR-04:00 | -5.0 |
April | 1591854.12 | 101.98 | 23-APR-06:16 | 8.67 |
May | 4956.29 | 82.60 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 279092.92 | 183.90 | 08-OCT-20:40 | 7.97 |
November | 39625479.93 | 278.49 | 24-NOV-05:00 | -3.9 |
December | 0.104203E+09 | 349.33 | 31-DEC-18:00 | -5.0 |
Annual Sum or Average | 0.913101E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.358753E+09 | 592.20 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44467616.01 | 1395.80 | 14-JAN-17:00 | -6.1 |
February | 5501772.13 | 626.82 | 06-FEB-07:05 | -13.2 |
March | 21123.40 | 281.65 | 26-MAR-07:44 | 8.12 |
April | 201198.01 | 425.55 | 02-APR-17:54 | 7.80 |
May | 46823.57 | 780.39 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 84184.88 | 349.69 | 07-NOV-08:17 | 7.57 |
December | 915888.68 | 355.63 | 25-DEC-17:20 | 8.30 |
Annual Sum or Average | 51238606.69 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 44467616.01 | 1395.80 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 129336.42 | 646.68 | 07-NOV-08:17 | 7.57 |
December | 10212.04 | 34.04 | 25-DEC-17:20 | 8.30 |
Annual Sum or Average | 139548.46 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 129336.42 | 646.68 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109527E+10 | 1754.41 | 14-JAN-16:13 | -6.1 |
February | 0.907202E+09 | 1726.81 | 06-FEB-19:02 | -8.2 |
March | 0.402721E+09 | 1707.04 | 16-MAR-15:02 | 0.68 |
April | 0.164196E+09 | 1674.75 | 21-APR-15:02 | 7.30 |
May | 8937323.62 | 850.22 | 13-MAY-08:04 | 13.40 |
June | 683650.74 | 805.95 | 11-JUN-15:04 | 18.90 |
July | 171965.03 | 401.55 | 11-JUL-08:14 | 23.17 |
August | 281519.14 | 634.98 | 26-AUG-08:14 | 22.23 |
September | 1941667.06 | 973.58 | 10-SEP-08:13 | 19.27 |
October | 32175637.91 | 1552.77 | 31-OCT-15:02 | 13.30 |
November | 0.455364E+09 | 1703.41 | 25-NOV-16:02 | 4.32 |
December | 0.838009E+09 | 1720.02 | 11-DEC-16:02 | 1.10 |
Annual Sum or Average | 0.390695E+10 | |||
Minimum of Months | 171965.03 | 401.55 | -8.2 | |
Maximum of Months | 0.109527E+10 | 1754.41 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131368E+10 | 1752.37 | 14-JAN-16:13 | -6.1 |
February | 0.117052E+10 | 1739.29 | 06-FEB-09:13 | -11.8 |
March | 0.515812E+09 | 1708.26 | 16-MAR-15:02 | 0.68 |
April | 0.189986E+09 | 1674.07 | 21-APR-15:02 | 7.30 |
May | 9834789.40 | 868.89 | 13-MAY-08:04 | 13.40 |
June | 657558.81 | 773.55 | 11-JUN-15:04 | 18.90 |
July | 165269.83 | 401.17 | 11-JUL-08:14 | 23.17 |
August | 284999.30 | 665.17 | 19-AUG-08:14 | 22.40 |
September | 2239993.80 | 937.98 | 19-SEP-21:04 | 15.50 |
October | 65316767.39 | 1585.53 | 29-OCT-08:62 | 6.88 |
November | 0.605337E+09 | 1706.93 | 25-NOV-16:02 | 4.32 |
December | 0.106995E+10 | 1717.24 | 11-DEC-16:02 | 1.10 |
Annual Sum or Average | 0.494378E+10 | |||
Minimum of Months | 165269.83 | 401.17 | -11.8 | |
Maximum of Months | 0.131368E+10 | 1752.37 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 45206537.73 | 201.98 | 02-JAN-05:00 | -12.2 |
February | 8421889.54 | 137.89 | 07-FEB-06:00 | -9.4 |
March | 907598.05 | 57.74 | 01-MAR-06:00 | 3.90 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10.40 |
December | 9759779.66 | 123.98 | 31-DEC-06:00 | -1.7 |
Annual Sum or Average | 64295804.97 | |||
Minimum of Months | 0.00 | 0.00 | -12.2 | |
Maximum of Months | 45206537.73 | 201.98 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.146037E+09 | 516.01 | 02-JAN-16:02 | -6.0 |
February | 0.148528E+09 | 514.10 | 07-FEB-16:02 | -4.0 |
March | 24646268.31 | 496.76 | 16-MAR-15:02 | 0.68 |
April | 1822888.73 | 474.44 | 21-APR-15:02 | 7.30 |
May | 711276.80 | 311.82 | 13-MAY-18:05 | 12.70 |
June | 83872.28 | 261.24 | 06-JUN-15:05 | 18.98 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 16633.41 | 79.99 | 22-AUG-18:07 | 27.62 |
September | 362686.31 | 260.42 | 30-SEP-15:03 | 19.22 |
October | 1146651.35 | 464.26 | 28-OCT-15:02 | 10.60 |
November | 31650156.08 | 502.23 | 24-NOV-16:02 | 1.20 |
December | 82263986.84 | 508.76 | 31-DEC-16:02 | -3.1 |
Annual Sum or Average | 0.437269E+09 | |||
Minimum of Months | 0.00 | 0.00 | -6.0 | |
Maximum of Months | 0.148528E+09 | 516.01 | 27.62 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108861E+10 | 1694.25 | 14-JAN-16:13 | -6.1 |
February | 0.883843E+09 | 1664.74 | 06-FEB-19:02 | -8.2 |
March | 0.426059E+09 | 1653.05 | 16-MAR-15:02 | 0.68 |
April | 0.166443E+09 | 1623.85 | 21-APR-15:02 | 7.30 |
May | 10193244.65 | 881.22 | 15-MAY-15:04 | 17.40 |
June | 434195.73 | 711.80 | 07-JUN-21:14 | 23.53 |
July | 37469.04 | 259.46 | 24-JUL-08:15 | 22.43 |
August | 40848.67 | 235.19 | 07-AUG-08:15 | 20.57 |
September | 1505170.45 | 851.50 | 27-SEP-21:14 | 19.80 |
October | 35256395.70 | 1420.50 | 31-OCT-15:02 | 13.30 |
November | 0.428785E+09 | 1650.42 | 25-NOV-16:02 | 4.32 |
December | 0.827267E+09 | 1664.63 | 11-DEC-16:02 | 1.10 |
Annual Sum or Average | 0.386848E+10 | |||
Minimum of Months | 37469.04 | 235.19 | -8.2 | |
Maximum of Months | 0.108861E+10 | 1694.25 | 23.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130195E+10 | 1695.76 | 14-JAN-16:13 | -6.1 |
February | 0.114006E+10 | 1676.88 | 06-FEB-16:13 | -7.0 |
March | 0.545796E+09 | 1657.25 | 16-MAR-15:02 | 0.68 |
April | 0.193147E+09 | 1626.20 | 21-APR-15:02 | 7.30 |
May | 11661373.08 | 872.11 | 01-MAY-18:03 | 12.43 |
June | 473297.66 | 706.51 | 07-JUN-21:14 | 23.53 |
July | 41565.77 | 298.37 | 24-JUL-08:15 | 22.43 |
August | 55909.53 | 210.19 | 07-AUG-08:15 | 20.57 |
September | 1987046.57 | 767.86 | 16-SEP-15:04 | 19.40 |
October | 68993387.76 | 1535.80 | 31-OCT-15:02 | 13.30 |
November | 0.558369E+09 | 1658.66 | 23-NOV-16:02 | 1.52 |
December | 0.104184E+10 | 1672.84 | 31-DEC-16:02 | -3.1 |
Annual Sum or Average | 0.486438E+10 | |||
Minimum of Months | 41565.77 | 210.19 | -7.0 | |
Maximum of Months | 0.130195E+10 | 1695.76 | 23.53 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145849E+10 | 1076.66 | 02-JAN-06:00 | -11.7 |
February | 0.111798E+10 | 1069.03 | 06-FEB-06:00 | -12.8 |
March | 0.438354E+09 | 891.03 | 17-MAR-04:00 | -1.7 |
April | 0.148229E+09 | 637.82 | 19-APR-17:20 | 8.53 |
May | 2725940.76 | 227.08 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 9440223.21 | 591.25 | 08-OCT-20:40 | 7.97 |
November | 0.450927E+09 | 957.85 | 24-NOV-05:00 | -3.9 |
December | 0.102663E+10 | 992.73 | 31-DEC-23:40 | -8.1 |
Annual Sum or Average | 0.465277E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.145849E+10 | 1076.66 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152117E+10 | 2044.27 | 14-JAN-16:13 | -6.1 |
February | 0.128217E+10 | 2001.93 | 06-FEB-16:13 | -7.0 |
March | 0.608496E+09 | 1969.30 | 31-MAR-18:01 | 7.80 |
April | 0.260821E+09 | 1932.79 | 21-APR-15:02 | 7.30 |
May | 17974396.27 | 893.52 | 13-MAY-08:04 | 13.40 |
June | 253666.09 | 847.58 | 03-JUN-08:13 | 17.03 |
July | 40262.54 | 554.55 | 11-JUL-08:14 | 23.17 |
August | 86101.88 | 440.96 | 23-AUG-08:14 | 22.40 |
September | 2605009.95 | 1119.57 | 10-SEP-08:13 | 19.27 |
October | 64076399.46 | 1813.77 | 31-OCT-15:02 | 13.30 |
November | 0.686491E+09 | 1961.47 | 25-NOV-16:02 | 4.32 |
December | 0.120842E+10 | 1989.25 | 11-DEC-16:02 | 1.10 |
Annual Sum or Average | 0.565261E+10 | |||
Minimum of Months | 40262.54 | 440.96 | -7.0 | |
Maximum of Months | 0.152117E+10 | 2044.27 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179159E+10 | 2042.26 | 14-JAN-16:13 | -6.1 |
February | 0.160203E+10 | 2030.51 | 06-FEB-16:13 | -7.0 |
March | 0.755478E+09 | 1973.35 | 16-MAR-15:02 | 0.68 |
April | 0.295770E+09 | 1932.07 | 21-APR-15:02 | 7.30 |
May | 19919730.18 | 967.52 | 09-MAY-21:14 | 19.43 |
June | 269475.76 | 862.74 | 03-JUN-08:13 | 17.03 |
July | 46729.22 | 594.14 | 11-JUL-08:14 | 23.17 |
August | 228932.45 | 642.09 | 26-AUG-08:14 | 22.23 |
September | 2627447.36 | 1006.05 | 10-SEP-08:13 | 19.27 |
October | 0.116208E+09 | 1846.79 | 29-OCT-08:62 | 6.88 |
November | 0.885455E+09 | 1977.35 | 17-NOV-19:01 | 7.62 |
December | 0.150171E+10 | 1988.49 | 11-DEC-16:02 | 1.10 |
Annual Sum or Average | 0.697134E+10 | |||
Minimum of Months | 46729.22 | 594.14 | -7.0 | |
Maximum of Months | 0.179159E+10 | 2042.26 | 23.17 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440700E+09 | 1007.30 | 14-JAN-16:13 | -6.1 |
February | 0.318069E+09 | 987.81 | 27-FEB-16:02 | 0.60 |
March | 0.148767E+09 | 979.76 | 16-MAR-15:02 | 0.68 |
April | 61676776.86 | 963.11 | 21-APR-15:02 | 7.30 |
May | 2023091.62 | 395.56 | 25-MAY-08:03 | 15.78 |
June | 149650.55 | 462.89 | 04-JUN-08:14 | 22.57 |
July | 143.78 | 1.92 | 23-JUL-08:18 | 24.60 |
August | 22858.88 | 206.40 | 08-AUG-08:14 | 21.83 |
September | 274347.01 | 283.04 | 30-SEP-08:05 | 14.18 |
October | 3188593.99 | 375.56 | 28-OCT-08:04 | 6.28 |
November | 0.118048E+09 | 956.30 | 28-NOV-16:02 | 9.32 |
December | 0.300377E+09 | 988.18 | 11-DEC-16:02 | 1.10 |
Annual Sum or Average | 0.139330E+10 | |||
Minimum of Months | 143.78 | 1.92 | -6.1 | |
Maximum of Months | 0.440700E+09 | 1007.30 | 24.60 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.157865E+10 | 2993.91 | 02-JAN-06:00 | -11.7 |
February | 0.142528E+10 | 2989.02 | 06-FEB-06:00 | -12.8 |
March | 0.255641E+09 | 1565.31 | 23-MAR-05:00 | -5.0 |
April | 20724748.07 | 563.90 | 23-APR-06:16 | 8.67 |
May | 27518.84 | 458.65 | 01-MAY-06:26 | 8.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 |
October | 4210710.93 | 1095.15 | 08-OCT-20:40 | 7.97 |
November | 0.261302E+09 | 1720.62 | 23-NOV-06:00 | -3.9 |
December | 0.698860E+09 | 1677.81 | 31-DEC-24:00 | -8.3 |
Annual Sum or Average | 0.424470E+10 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.157865E+10 | 2993.91 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.145930E+11 | 14056.06 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.131761E+11 | 14056.06 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.146436E+11 | 14056.06 | 01-MAR-20:10 | 0.121808E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.140982E+11 | 14056.06 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.146183E+11 | 14056.06 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.141629E+11 | 14056.06 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.145536E+11 | 14056.06 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.146436E+11 | 14056.06 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.140982E+11 | 14056.06 | 01-SEP-19:10 | 0.117446E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.145930E+11 | 14056.06 | 02-OCT-19:10 | 0.121516E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.141516E+11 | 14056.06 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.145536E+11 | 14056.06 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.171886E+12 | 0.143109E+12 | ||||
Minimum of Months | 0.131761E+11 | 14056.06 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.146436E+11 | 14056.06 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.849965E+09 | 818.69 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.767441E+09 | 818.69 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.852913E+09 | 818.69 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.821148E+09 | 818.69 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.851439E+09 | 818.69 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.824914E+09 | 818.69 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.847673E+09 | 818.69 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.852913E+09 | 818.69 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.821148E+09 | 818.69 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.849965E+09 | 818.69 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.824259E+09 | 818.69 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.847673E+09 | 818.69 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.100115E+11 | 0.101859E+11 | ||||
Minimum of Months | 0.767441E+09 | 818.69 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.852913E+09 | 818.69 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.984263E+09 | 948.05 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.888700E+09 | 948.05 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.987676E+09 | 948.05 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.950892E+09 | 948.05 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.985970E+09 | 948.05 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.955253E+09 | 948.05 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.981609E+09 | 948.05 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.987676E+09 | 948.05 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.950892E+09 | 948.05 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.984263E+09 | 948.05 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.954495E+09 | 948.05 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.981609E+09 | 948.05 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.115933E+11 | 0.117953E+11 | ||||
Minimum of Months | 0.888700E+09 | 948.05 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.987676E+09 | 948.05 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156929E+10 | 1511.55 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.141693E+10 | 1511.55 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.157474E+10 | 1511.55 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.151609E+10 | 1511.55 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.157202E+10 | 1511.55 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.152304E+10 | 1511.55 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.156506E+10 | 1511.55 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.157474E+10 | 1511.55 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.151609E+10 | 1511.55 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.156929E+10 | 1511.55 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.152183E+10 | 1511.55 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.156506E+10 | 1511.55 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.141693E+10 | 1511.55 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.157474E+10 | 1511.55 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.267175E+09 | 257.34 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.241235E+09 | 257.34 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.268102E+09 | 257.34 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.258117E+09 | 257.34 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.267639E+09 | 257.34 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.259301E+09 | 257.34 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.266455E+09 | 257.34 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.268102E+09 | 257.34 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.258117E+09 | 257.34 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.267175E+09 | 257.34 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.259095E+09 | 257.34 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.266455E+09 | 257.34 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.314697E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.241235E+09 | 257.34 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.268102E+09 | 257.34 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.470933E+09 | 453.61 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.425210E+09 | 453.61 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.472566E+09 | 453.61 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.454966E+09 | 453.61 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.471750E+09 | 453.61 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.457053E+09 | 453.61 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.469663E+09 | 453.61 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.472566E+09 | 453.61 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.454966E+09 | 453.61 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.470933E+09 | 453.61 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.456690E+09 | 453.61 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.469663E+09 | 453.61 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.554696E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.425210E+09 | 453.61 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.472566E+09 | 453.61 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.130878E+10 | 1628.35 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.111949E+10 | 1628.35 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.117601E+10 | 1628.35 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.105681E+10 | 1628.35 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.992337E+09 | 1628.35 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.928388E+09 | 1628.35 | 01-JUN-19:19 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.963904E+09 | 1628.35 | 03-JUL-19:19 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.104936E+10 | 1628.35 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.110279E+10 | 1628.35 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.122474E+10 | 1628.35 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.122845E+10 | 1628.35 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.129799E+10 | 1628.35 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.134491E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.928388E+09 | 1628.35 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.130878E+10 | 1628.35 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134157E+11 | 13433.46 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.120147E+11 | 13433.46 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.132669E+11 | 13433.46 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.126805E+11 | 13433.46 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.129981E+11 | 13433.46 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.125564E+11 | 13433.46 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.129229E+11 | 13433.46 | 03-JUL-19:19 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.130911E+11 | 13433.46 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.127362E+11 | 13433.46 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.132783E+11 | 13433.46 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.129383E+11 | 13433.46 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.133620E+11 | 13433.46 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.155261E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.120147E+11 | 13433.46 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.134157E+11 | 13433.46 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260035E+09 | 305.78 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.234855E+09 | 305.78 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.259080E+09 | 305.78 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.251801E+09 | 305.78 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.259557E+09 | 305.78 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.250846E+09 | 305.78 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.260513E+09 | 305.78 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.259080E+09 | 305.78 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.251801E+09 | 305.78 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.260035E+09 | 305.78 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.251323E+09 | 305.78 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.260513E+09 | 305.78 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.305944E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.234855E+09 | 305.78 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.260513E+09 | 305.78 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260005E+09 | 305.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.234828E+09 | 305.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.259049E+09 | 305.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.251772E+09 | 305.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.259527E+09 | 305.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.250816E+09 | 305.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.260483E+09 | 305.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.259049E+09 | 305.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.251772E+09 | 305.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.260005E+09 | 305.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.251294E+09 | 305.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.260483E+09 | 305.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.305908E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.234828E+09 | 305.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.260483E+09 | 305.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163422E+09 | 192.17 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.147597E+09 | 192.17 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.162822E+09 | 192.17 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.158247E+09 | 192.17 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.163122E+09 | 192.17 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.157647E+09 | 192.17 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.163723E+09 | 192.17 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.162822E+09 | 192.17 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.158247E+09 | 192.17 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.163422E+09 | 192.17 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.157947E+09 | 192.17 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.163723E+09 | 192.17 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.192274E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.147597E+09 | 192.17 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.163723E+09 | 192.17 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163467E+09 | 192.22 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.147638E+09 | 192.22 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.162866E+09 | 192.22 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.158291E+09 | 192.22 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.163167E+09 | 192.22 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.157690E+09 | 192.22 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.163767E+09 | 192.22 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.162866E+09 | 192.22 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.158291E+09 | 192.22 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.163467E+09 | 192.22 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.157990E+09 | 192.22 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.163767E+09 | 192.22 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.192327E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.147638E+09 | 192.22 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.163767E+09 | 192.22 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260035E+09 | 305.78 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.234855E+09 | 305.78 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.259080E+09 | 305.78 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.251801E+09 | 305.78 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.259557E+09 | 305.78 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.250846E+09 | 305.78 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.260513E+09 | 305.78 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.259080E+09 | 305.78 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.251801E+09 | 305.78 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.260035E+09 | 305.78 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.251323E+09 | 305.78 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.260513E+09 | 305.78 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.305944E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.234855E+09 | 305.78 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.260513E+09 | 305.78 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260005E+09 | 305.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.234828E+09 | 305.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.259049E+09 | 305.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.251772E+09 | 305.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.259527E+09 | 305.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.250816E+09 | 305.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.260483E+09 | 305.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.259049E+09 | 305.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.251772E+09 | 305.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.260005E+09 | 305.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.251294E+09 | 305.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.260483E+09 | 305.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.305908E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.234828E+09 | 305.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.260483E+09 | 305.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.140176E+10 | 1350.19 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.126566E+10 | 1350.19 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.140662E+10 | 1350.19 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.135424E+10 | 1350.19 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.140419E+10 | 1350.19 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136045E+10 | 1350.19 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.139798E+10 | 1350.19 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.140662E+10 | 1350.19 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.135424E+10 | 1350.19 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140176E+10 | 1350.19 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.135937E+10 | 1350.19 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.139798E+10 | 1350.19 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165109E+11 | ||||
Minimum of Months | 0.126566E+10 | 1350.19 | 0.00 | 0.00 | |
Maximum of Months | 0.140662E+10 | 1350.19 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260035E+09 | 305.78 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.234855E+09 | 305.78 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.259080E+09 | 305.78 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.251801E+09 | 305.78 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.259557E+09 | 305.78 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.250846E+09 | 305.78 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.260513E+09 | 305.78 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.259080E+09 | 305.78 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.251801E+09 | 305.78 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.260035E+09 | 305.78 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.251323E+09 | 305.78 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.260513E+09 | 305.78 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.305944E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.234855E+09 | 305.78 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.260513E+09 | 305.78 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.260005E+09 | 305.75 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.234828E+09 | 305.75 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.259049E+09 | 305.75 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.251772E+09 | 305.75 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.259527E+09 | 305.75 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.250816E+09 | 305.75 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.260483E+09 | 305.75 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.259049E+09 | 305.75 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.251772E+09 | 305.75 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.260005E+09 | 305.75 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.251294E+09 | 305.75 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.260483E+09 | 305.75 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.305908E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.234828E+09 | 305.75 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.260483E+09 | 305.75 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163467E+09 | 192.22 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.147638E+09 | 192.22 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.162866E+09 | 192.22 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.158291E+09 | 192.22 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.163167E+09 | 192.22 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.157690E+09 | 192.22 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.163767E+09 | 192.22 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.162866E+09 | 192.22 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.158291E+09 | 192.22 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.163467E+09 | 192.22 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.157990E+09 | 192.22 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.163767E+09 | 192.22 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.192327E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.147638E+09 | 192.22 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.163767E+09 | 192.22 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.267801E+10 | 2859.51 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.235630E+10 | 2859.51 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.254018E+10 | 2859.51 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.236047E+10 | 2859.51 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.233322E+10 | 2859.51 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.222536E+10 | 2859.51 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.230001E+10 | 2859.51 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.239509E+10 | 2859.51 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.240969E+10 | 2859.51 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.257758E+10 | 2859.51 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.254991E+10 | 2859.51 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.268416E+10 | 2859.51 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.294100E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.222536E+10 | 2859.51 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.268416E+10 | 2859.51 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.267801E+10 | 2859.51 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.235630E+10 | 2859.51 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.254018E+10 | 2859.51 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.236047E+10 | 2859.51 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.233322E+10 | 2859.51 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.222536E+10 | 2859.51 | 01-JUN-19:19 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.230001E+10 | 2859.51 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.239509E+10 | 2859.51 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.240969E+10 | 2859.51 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.257758E+10 | 2859.51 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.254991E+10 | 2859.51 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.268416E+10 | 2859.51 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.294100E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.222536E+10 | 2859.51 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.268416E+10 | 2859.51 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.125718E+10 | 1210.92 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.113512E+10 | 1210.92 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.126154E+10 | 1210.92 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.121456E+10 | 1210.92 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.125936E+10 | 1210.92 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.122013E+10 | 1210.92 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.125379E+10 | 1210.92 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.126154E+10 | 1210.92 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.121456E+10 | 1210.92 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.125718E+10 | 1210.92 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.121916E+10 | 1210.92 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.125379E+10 | 1210.92 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.148079E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.113512E+10 | 1210.92 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.126154E+10 | 1210.92 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.148355E+10 | 1428.96 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.133951E+10 | 1428.96 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.148869E+10 | 1428.96 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.143325E+10 | 1428.96 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.148612E+10 | 1428.96 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.143982E+10 | 1428.96 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.147955E+10 | 1428.96 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.148869E+10 | 1428.96 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.143325E+10 | 1428.96 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.148355E+10 | 1428.96 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.143868E+10 | 1428.96 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.147955E+10 | 1428.96 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.174742E+11 | ||||
Minimum of Months | 0.133951E+10 | 1428.96 | 0.00 | 0.00 | |
Maximum of Months | 0.148869E+10 | 1428.96 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.145930E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.131761E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.146436E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.140982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.146183E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.141629E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.145536E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.146436E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.140982E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.145930E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.141516E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.145536E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.171886E+12 | 0.143109E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.131761E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.146436E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.849965E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135788E+10 |
February | 0.179968E+10 | 0.767441E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130826E+10 |
March | 0.199896E+10 | 0.852913E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64893.30 | 0.104858E+10 |
April | 0.192973E+10 | 0.821148E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2032046.26 | 0.656283E+09 |
May | 0.199475E+10 | 0.851439E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16471466.02 | 0.348948E+09 |
June | 0.193394E+10 | 0.824914E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84564046.15 | 70860465.75 |
July | 0.199054E+10 | 0.847673E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200343E+09 | 3616987.38 |
August | 0.199896E+10 | 0.852913E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179176E+09 | 23515049.04 |
September | 0.192973E+10 | 0.821148E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37137024.00 | 0.153002E+09 |
October | 0.199054E+10 | 0.849965E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 608075.14 | 0.522393E+09 |
November | 0.192552E+10 | 0.824259E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897501E+09 |
December | 0.199054E+10 | 0.847673E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119131E+10 |
Annual Sum or Average | 0.234734E+11 | 0.100115E+11 | 0.101859E+11 | 0.520397E+09 | 0.758215E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.767441E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3616987.38 |
Maximum of Months | 0.199896E+10 | 0.852913E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200343E+09 | 0.135788E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.984263E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290013E+09 |
February | 0.208403E+10 | 0.888700E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278914E+09 |
March | 0.231480E+10 | 0.987676E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9298.17 | 0.229121E+09 |
April | 0.223463E+10 | 0.950892E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 709576.94 | 0.148779E+09 |
May | 0.230993E+10 | 0.985970E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3734599.60 | 84156209.90 |
June | 0.223950E+10 | 0.955253E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17331177.13 | 21258713.99 |
July | 0.230505E+10 | 0.981609E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39618873.94 | 2163387.64 |
August | 0.231480E+10 | 0.987676E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38854552.74 | 8115090.35 |
September | 0.223463E+10 | 0.950892E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8884619.84 | 37438202.50 |
October | 0.230505E+10 | 0.984263E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 636472.44 | 0.117004E+09 |
November | 0.222975E+10 | 0.954495E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197865E+09 |
December | 0.230505E+10 | 0.981609E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256981E+09 |
Annual Sum or Average | 0.271823E+11 | 0.115933E+11 | 0.117953E+11 | 0.109779E+09 | 0.167181E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.888700E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2163387.64 |
Maximum of Months | 0.231480E+10 | 0.987676E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39618873.94 | 0.290013E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940133E+09 |
February | 0.139600E+10 | 0.425210E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898213E+09 |
March | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50939.91 | 0.736105E+09 |
April | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 2569066.05 | 0.478447E+09 |
May | 0.154732E+10 | 0.471750E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 11950774.10 | 0.266589E+09 |
June | 0.150015E+10 | 0.457053E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 57404993.36 | 65744550.08 |
July | 0.154405E+10 | 0.469663E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.135151E+09 | 6854811.52 |
August | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.136643E+09 | 21228162.41 |
September | 0.149688E+10 | 0.454966E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 34020768.11 | 0.115390E+09 |
October | 0.154405E+10 | 0.470933E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 3838062.11 | 0.355379E+09 |
November | 0.149361E+10 | 0.456690E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634416E+09 |
December | 0.154405E+10 | 0.469663E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829549E+09 |
Annual Sum or Average | 0.182082E+11 | 0.554696E+10 | 0.679373E+11 | 0.590211E+12 | 0.381628E+09 | 0.534805E+10 | |||
Minimum of Months | 0.139600E+10 | 0.425210E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6854811.52 |
Maximum of Months | 0.155059E+10 | 0.472566E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.136643E+09 | 0.940133E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.130878E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350074E+10 |
February | 0.236489E+11 | 0.111949E+10 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337814E+10 |
March | 0.262677E+11 | 0.117601E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13174.16 | 0.278196E+10 |
April | 0.253579E+11 | 0.105681E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4343115.64 | 0.180448E+10 |
May | 0.262123E+11 | 0.992337E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37203317.58 | 0.103763E+10 |
June | 0.254132E+11 | 0.928388E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184391E+09 | 0.285653E+09 |
July | 0.261570E+11 | 0.963904E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416381E+09 | 43307705.66 |
August | 0.262677E+11 | 0.104936E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397037E+09 | 0.118201E+09 |
September | 0.253579E+11 | 0.110279E+10 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75086653.84 | 0.508204E+09 |
October | 0.261570E+11 | 0.122474E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1485907.47 | 0.149775E+10 |
November | 0.253025E+11 | 0.122845E+10 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240366E+10 |
December | 0.261570E+11 | 0.129799E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310878E+10 |
Annual Sum or Average | 0.308456E+12 | 0.134491E+11 | 0.143409E+11 | 0.111594E+10 | 0.204685E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.928388E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43307705.66 |
Maximum of Months | 0.262677E+11 | 0.130878E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416381E+09 | 0.350074E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.134157E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.712494E+10 |
February | 0.702046E+11 | 0.120147E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684524E+10 |
March | 0.779788E+11 | 0.132669E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85965.40 | 0.566157E+10 |
April | 0.752779E+11 | 0.126805E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14436995.25 | 0.370875E+10 |
May | 0.778146E+11 | 0.129981E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83300525.36 | 0.214241E+10 |
June | 0.754422E+11 | 0.125564E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391233E+09 | 0.587737E+09 |
July | 0.776503E+11 | 0.129229E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882962E+09 | 83616260.06 |
August | 0.779788E+11 | 0.130911E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883738E+09 | 0.234039E+09 |
September | 0.752779E+11 | 0.127362E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192274E+09 | 0.998786E+09 |
October | 0.776503E+11 | 0.132783E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10491813.98 | 0.295287E+10 |
November | 0.751137E+11 | 0.129383E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492197E+10 |
December | 0.776503E+11 | 0.133620E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634463E+10 |
Annual Sum or Average | 0.915690E+12 | 0.155261E+12 | 0.149002E+12 | 0.245852E+10 | 0.416066E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.120147E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83616260.06 |
Maximum of Months | 0.779788E+11 | 0.134157E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883738E+09 | 0.712494E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.260035E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391715E+09 |
February | 0.273974E+09 | 0.234855E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378531E+09 |
March | 0.303685E+09 | 0.259080E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305004E+09 |
April | 0.293479E+09 | 0.251801E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 408790.04 | 0.195723E+09 |
May | 0.303504E+09 | 0.259557E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2879079.46 | 0.114444E+09 |
June | 0.293842E+09 | 0.250846E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18294162.93 | 34918083.77 |
July | 0.303141E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49296291.41 | 5959654.49 |
August | 0.303685E+09 | 0.259080E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52004364.09 | 12698966.26 |
September | 0.293479E+09 | 0.251801E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9324144.09 | 53446736.13 |
October | 0.303322E+09 | 0.260035E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 248658.86 | 0.150634E+09 |
November | 0.293661E+09 | 0.251323E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258846E+09 |
December | 0.303141E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342846E+09 |
Annual Sum or Average | 0.357224E+10 | 0.305944E+10 | 0.261953E+10 | 0.132455E+09 | 0.224477E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.234855E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5959654.49 |
Maximum of Months | 0.303685E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52004364.09 | 0.391715E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.260005E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388464E+09 |
February | 0.273974E+09 | 0.234828E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374432E+09 |
March | 0.303685E+09 | 0.259049E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300786E+09 |
April | 0.293479E+09 | 0.251772E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 510658.80 | 0.193673E+09 |
May | 0.303504E+09 | 0.259527E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2905777.14 | 0.113662E+09 |
June | 0.293842E+09 | 0.250816E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18322549.51 | 34723658.98 |
July | 0.303141E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49378901.74 | 5813551.15 |
August | 0.303685E+09 | 0.259049E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52274511.59 | 12036237.22 |
September | 0.293479E+09 | 0.251772E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9593336.94 | 50976464.80 |
October | 0.303322E+09 | 0.260005E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 360881.77 | 0.145357E+09 |
November | 0.293661E+09 | 0.251294E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254587E+09 |
December | 0.303141E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338486E+09 |
Annual Sum or Average | 0.357224E+10 | 0.305908E+10 | 0.261922E+10 | 0.133347E+09 | 0.221300E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.234828E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5813551.15 |
Maximum of Months | 0.303685E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52274511.59 | 0.388464E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.163422E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104948E+09 |
February | 0.00 | 0.147597E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105474E+09 |
March | 0.00 | 0.162822E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87604724.80 |
April | 0.00 | 0.158247E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 121901.36 | 58039019.98 |
May | 0.00 | 0.163122E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 689041.95 | 37374821.18 |
June | 0.00 | 0.157647E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3962178.13 | 11994257.44 |
July | 0.00 | 0.163723E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10534419.45 | 2115756.33 |
August | 0.00 | 0.162822E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11535800.80 | 4564300.40 |
September | 0.00 | 0.158247E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1856906.01 | 18802828.82 |
October | 0.00 | 0.163422E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46867.79 | 49132429.77 |
November | 0.00 | 0.157947E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76678441.71 |
December | 0.00 | 0.163723E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95640476.04 |
Annual Sum or Average | 0.00 | 0.192274E+10 | 0.256575E+10 | 28747115.49 | 0.652368E+09 | ||||
Minimum of Months | 0.00 | 0.147597E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2115756.33 |
Maximum of Months | 0.00 | 0.163723E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11535800.80 | 0.105474E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.163467E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109708E+09 |
February | 0.273974E+09 | 0.147638E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105435E+09 |
March | 0.303685E+09 | 0.162866E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1316.24 | 84660814.85 |
April | 0.293479E+09 | 0.158291E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 231627.15 | 53914445.29 |
May | 0.303504E+09 | 0.163167E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 962968.58 | 30386598.79 |
June | 0.293842E+09 | 0.157690E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5623500.87 | 7922134.52 |
July | 0.303141E+09 | 0.163767E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14443339.04 | 1014130.85 |
August | 0.303685E+09 | 0.162866E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15516223.45 | 2620062.70 |
September | 0.293479E+09 | 0.158291E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3187960.59 | 13082506.39 |
October | 0.303322E+09 | 0.163467E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 258678.16 | 39506165.35 |
November | 0.293661E+09 | 0.157990E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72146813.69 |
December | 0.303141E+09 | 0.163767E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95814769.26 |
Annual Sum or Average | 0.357224E+10 | 0.192327E+10 | 0.256645E+10 | 40225614.07 | 0.616211E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.147638E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014130.85 |
Maximum of Months | 0.303685E+09 | 0.163767E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15516223.45 | 0.109708E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.260035E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391716E+09 |
February | 0.273974E+09 | 0.234855E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378872E+09 |
March | 0.303685E+09 | 0.259080E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 601.36 | 0.305551E+09 |
April | 0.293479E+09 | 0.251801E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 466319.85 | 0.196102E+09 |
May | 0.303504E+09 | 0.259557E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2822084.66 | 0.113962E+09 |
June | 0.293842E+09 | 0.250846E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18379095.96 | 31996852.20 |
July | 0.303141E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49282831.26 | 5064226.15 |
August | 0.303685E+09 | 0.259080E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51751080.74 | 11685449.92 |
September | 0.293479E+09 | 0.251801E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9395196.93 | 51931401.09 |
October | 0.303322E+09 | 0.260035E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 240583.35 | 0.149631E+09 |
November | 0.293661E+09 | 0.251323E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259467E+09 |
December | 0.303141E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342983E+09 |
Annual Sum or Average | 0.357224E+10 | 0.305944E+10 | 0.261953E+10 | 0.132338E+09 | 0.223896E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.234855E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5064226.15 |
Maximum of Months | 0.303685E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 51751080.74 | 0.391716E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.260005E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388540E+09 |
February | 0.273974E+09 | 0.234828E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374658E+09 |
March | 0.303685E+09 | 0.259049E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5047.10 | 0.301315E+09 |
April | 0.293479E+09 | 0.251772E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 498731.17 | 0.194084E+09 |
May | 0.303504E+09 | 0.259527E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2835227.06 | 0.113341E+09 |
June | 0.293842E+09 | 0.250816E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18433772.68 | 31889884.86 |
July | 0.303141E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49395571.80 | 4961434.09 |
August | 0.303685E+09 | 0.259049E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52073675.73 | 11215040.21 |
September | 0.293479E+09 | 0.251772E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9639848.24 | 49879403.11 |
October | 0.303322E+09 | 0.260005E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 319641.50 | 0.143991E+09 |
November | 0.293661E+09 | 0.251294E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255276E+09 |
December | 0.303141E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338597E+09 |
Annual Sum or Average | 0.357224E+10 | 0.305908E+10 | 0.261922E+10 | 0.133202E+09 | 0.220775E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.234828E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4961434.09 |
Maximum of Months | 0.303685E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 52073675.73 | 0.388540E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.260035E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391611E+09 |
February | 0.273974E+09 | 0.234855E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378444E+09 |
March | 0.303685E+09 | 0.259080E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305447E+09 |
April | 0.293479E+09 | 0.251801E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 385473.51 | 0.197405E+09 |
May | 0.303504E+09 | 0.259557E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2758326.81 | 0.118296E+09 |
June | 0.293842E+09 | 0.250846E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17654347.63 | 39918709.06 |
July | 0.303141E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47595380.00 | 8972321.21 |
August | 0.303685E+09 | 0.259080E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50612608.58 | 15784192.88 |
September | 0.293479E+09 | 0.251801E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8875310.31 | 57745463.15 |
October | 0.303322E+09 | 0.260035E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219077.03 | 0.153130E+09 |
November | 0.293661E+09 | 0.251323E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258803E+09 |
December | 0.303141E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342638E+09 |
Annual Sum or Average | 0.357224E+10 | 0.305944E+10 | 0.261953E+10 | 0.128101E+09 | 0.226820E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.234855E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8972321.21 |
Maximum of Months | 0.303685E+09 | 0.260513E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50612608.58 | 0.391611E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.260005E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388907E+09 |
February | 0.273974E+09 | 0.234828E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374741E+09 |
March | 0.303685E+09 | 0.259049E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301082E+09 |
April | 0.293479E+09 | 0.251772E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 433191.49 | 0.195181E+09 |
May | 0.303504E+09 | 0.259527E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2764680.28 | 0.117698E+09 |
June | 0.293842E+09 | 0.250816E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17660934.97 | 39837876.84 |
July | 0.303141E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47624566.49 | 8794745.00 |
August | 0.303685E+09 | 0.259049E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50769914.53 | 15052593.91 |
September | 0.293479E+09 | 0.251772E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8986789.24 | 55330340.74 |
October | 0.303322E+09 | 0.260005E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 285633.19 | 0.147832E+09 |
November | 0.293661E+09 | 0.251294E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254603E+09 |
December | 0.303141E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338576E+09 |
Annual Sum or Average | 0.357224E+10 | 0.305908E+10 | 0.261922E+10 | 0.128526E+09 | 0.223764E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.234828E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8794745.00 |
Maximum of Months | 0.303685E+09 | 0.260483E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 50769914.53 | 0.388907E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.163467E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204316E+09 |
February | 0.273974E+09 | 0.147638E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197854E+09 |
March | 0.303685E+09 | 0.162866E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158672E+09 |
April | 0.293479E+09 | 0.158291E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 209846.88 | 0.101379E+09 |
May | 0.303504E+09 | 0.163167E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1441525.11 | 58349199.81 |
June | 0.293842E+09 | 0.157690E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9203717.03 | 16367436.56 |
July | 0.303141E+09 | 0.163767E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24662954.80 | 2774576.85 |
August | 0.303685E+09 | 0.162866E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26097744.95 | 6102888.78 |
September | 0.293479E+09 | 0.158291E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4547137.25 | 28065204.13 |
October | 0.303322E+09 | 0.163467E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 105795.53 | 78639627.18 |
November | 0.293661E+09 | 0.157990E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136183E+09 |
December | 0.303141E+09 | 0.163767E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179388E+09 |
Annual Sum or Average | 0.357224E+10 | 0.192327E+10 | 0.256645E+10 | 66268721.55 | 0.116809E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.147638E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2774576.85 |
Maximum of Months | 0.303685E+09 | 0.163767E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26097744.95 | 0.204316E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.267801E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107931E+10 |
February | 0.415303E+11 | 0.235630E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102974E+10 |
March | 0.461292E+11 | 0.254018E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861659E+09 |
April | 0.445315E+11 | 0.236047E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1376890.20 | 0.578821E+09 |
May | 0.460320E+11 | 0.233322E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6802524.18 | 0.354838E+09 |
June | 0.446286E+11 | 0.222536E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36308610.26 | 0.118276E+09 |
July | 0.459349E+11 | 0.230001E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88645822.45 | 26918752.87 |
August | 0.461292E+11 | 0.239509E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97724460.06 | 48461756.61 |
September | 0.445315E+11 | 0.240969E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18783538.27 | 0.175262E+09 |
October | 0.459349E+11 | 0.257758E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1313185.75 | 0.446397E+09 |
November | 0.444343E+11 | 0.254991E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744918E+09 |
December | 0.459349E+11 | 0.268416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959385E+09 |
Annual Sum or Average | 0.541686E+12 | 0.294100E+11 | 0.175857E+12 | 0.250955E+09 | 0.642398E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.222536E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26918752.87 |
Maximum of Months | 0.461292E+11 | 0.268416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97724460.06 | 0.107931E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.267801E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109144E+10 |
February | 0.415303E+11 | 0.235630E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104066E+10 |
March | 0.461292E+11 | 0.254018E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870711E+09 |
April | 0.445315E+11 | 0.236047E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1182084.98 | 0.586494E+09 |
May | 0.460320E+11 | 0.233322E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6024173.01 | 0.361765E+09 |
June | 0.446286E+11 | 0.222536E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33601119.01 | 0.122020E+09 |
July | 0.459349E+11 | 0.230001E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83961504.36 | 27943507.15 |
August | 0.461292E+11 | 0.239509E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93456522.19 | 49551176.60 |
September | 0.445315E+11 | 0.240969E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16825928.74 | 0.180615E+09 |
October | 0.459349E+11 | 0.257758E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1013568.17 | 0.453409E+09 |
November | 0.444343E+11 | 0.254991E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.753905E+09 |
December | 0.459349E+11 | 0.268416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.969647E+09 |
Annual Sum or Average | 0.541686E+12 | 0.294100E+11 | 0.175857E+12 | 0.236065E+09 | 0.650816E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.222536E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27943507.15 |
Maximum of Months | 0.461292E+11 | 0.268416E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93456522.19 | 0.109144E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986797E+09 |
February | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939526E+09 |
March | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785852E+09 |
April | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 620527.09 | 0.530828E+09 |
May | 0.409635E+10 | 0.125936E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4085553.17 | 0.324000E+09 |
June | 0.397146E+10 | 0.122013E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 26610424.02 | 0.101277E+09 |
July | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 74815509.81 | 15326218.49 |
August | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 81551113.82 | 34602291.02 |
September | 0.396281E+10 | 0.121456E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 11779314.47 | 0.158223E+09 |
October | 0.408770E+10 | 0.125718E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 109881.08 | 0.412045E+09 |
November | 0.395417E+10 | 0.121916E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682667E+09 |
December | 0.408770E+10 | 0.125379E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875506E+09 |
Annual Sum or Average | 0.482041E+11 | 0.148079E+11 | 0.392709E+12 | 0.359593E+12 | 0.199572E+09 | 0.584665E+10 | |||
Minimum of Months | 0.369574E+10 | 0.113512E+10 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15326218.49 |
Maximum of Months | 0.410499E+10 | 0.126154E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 81551113.82 | 0.986797E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624451E+09 |
February | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599661E+09 |
March | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36562.58 | 0.480029E+09 |
April | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1962354.17 | 0.304883E+09 |
May | 0.00 | 0.157202E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8941102.07 | 0.167645E+09 |
June | 0.00 | 0.152304E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41198488.66 | 38034846.63 |
July | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94104271.08 | 2734313.78 |
August | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93308772.59 | 13803213.00 |
September | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23617057.79 | 70625464.25 |
October | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203803.69 | 0.232356E+09 |
November | 0.00 | 0.152183E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413568E+09 |
December | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545334E+09 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | 0.265372E+09 | 0.349313E+10 | |||||
Minimum of Months | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2734313.78 |
Maximum of Months | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94104271.08 | 0.624451E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.267175E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433182E+09 |
February | 0.00 | 0.241235E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416256E+09 |
March | 0.00 | 0.268102E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25422.49 | 0.330934E+09 |
April | 0.00 | 0.258117E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1406070.97 | 0.207655E+09 |
May | 0.00 | 0.267639E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6314105.44 | 0.111506E+09 |
June | 0.00 | 0.259301E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29414238.92 | 23905596.48 |
July | 0.00 | 0.266455E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66994824.74 | 1563345.56 |
August | 0.00 | 0.268102E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66233822.70 | 8645886.09 |
September | 0.00 | 0.258117E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17265339.27 | 45761532.85 |
October | 0.00 | 0.267175E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1602944.12 | 0.153946E+09 |
November | 0.00 | 0.259095E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282598E+09 |
December | 0.00 | 0.266455E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377650E+09 |
Annual Sum or Average | 0.314697E+10 | 0.359769E+10 | 0.189257E+09 | 0.239360E+10 | |||||
Minimum of Months | 0.00 | 0.241235E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1563345.56 |
Maximum of Months | 0.00 | 0.268102E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66994824.74 | 0.433182E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.140176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479777E+09 |
February | 0.00 | 0.126566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461218E+09 |
March | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25933.02 | 0.366981E+09 |
April | 0.00 | 0.135424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1553178.53 | 0.229738E+09 |
May | 0.00 | 0.140419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7114811.98 | 0.122269E+09 |
June | 0.00 | 0.136045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35866570.92 | 24108441.45 |
July | 0.00 | 0.139798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85477688.56 | 1149176.33 |
August | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83988993.27 | 7266777.18 |
September | 0.00 | 0.135424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21503284.17 | 48299532.12 |
October | 0.00 | 0.140176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1841136.26 | 0.165738E+09 |
November | 0.00 | 0.135937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312605E+09 |
December | 0.00 | 0.139798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418867E+09 |
Annual Sum or Average | 0.165109E+11 | 0.237372E+09 | 0.263802E+10 | ||||||
Minimum of Months | 0.00 | 0.126566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1149176.33 |
Maximum of Months | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85477688.56 | 0.479777E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.148355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853007E+09 |
February | 0.00 | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.819671E+09 |
March | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35508.26 | 0.654681E+09 |
April | 0.00 | 0.143325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2017690.41 | 0.413135E+09 |
May | 0.00 | 0.148612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9123692.04 | 0.225125E+09 |
June | 0.00 | 0.143982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47732184.00 | 50161242.51 |
July | 0.00 | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115309E+09 | 3332041.58 |
August | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114657E+09 | 17077748.10 |
September | 0.00 | 0.143325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27509460.14 | 91835605.00 |
October | 0.00 | 0.148355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1657856.23 | 0.304159E+09 |
November | 0.00 | 0.143868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557543E+09 |
December | 0.00 | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744513E+09 |
Annual Sum or Average | 0.174742E+11 | 0.318043E+09 | 0.473424E+10 | ||||||
Minimum of Months | 0.00 | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3332041.58 |
Maximum of Months | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115309E+09 | 0.853007E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 14056.06 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 14056.06 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 14056.06 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 14056.06 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 14056.06 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 14056.06 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 14056.06 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 14056.06 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 14056.06 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 14056.06 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 14056.06 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 14056.06 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 14056.06 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 14056.06 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 818.69 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 887.67 | 02-JAN-05:00 |
February | 1169.53 | 01-FEB-00:10 | 818.69 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 915.50 | 06-FEB-03:00 |
March | 1169.53 | 01-MAR-00:10 | 818.69 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.75 | 27-MAR-16:00 | 676.95 | 23-MAR-06:00 |
April | 1169.53 | 01-APR-00:10 | 818.69 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.57 | 08-APR-10:00 | 477.36 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 818.69 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.30 | 30-MAY-13:00 | 370.67 | 01-MAY-05:00 |
June | 1169.53 | 01-JUN-00:10 | 818.69 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.19 | 19-JUN-12:00 | 185.43 | 03-JUN-03:00 |
July | 1169.53 | 01-JUL-00:10 | 818.69 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.11 | 07-JUL-12:00 | 63.96 | 02-JUL-05:00 |
August | 1169.53 | 01-AUG-00:10 | 818.69 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.47 | 24-AUG-16:00 | 144.69 | 08-AUG-05:00 |
September | 1169.53 | 01-SEP-00:10 | 818.69 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.26 | 01-SEP-14:00 | 270.26 | 24-SEP-06:00 |
October | 1169.53 | 02-OCT-00:10 | 818.69 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 25-OCT-12:30 | 480.22 | 09-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 818.69 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 659.29 | 24-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 818.69 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 767.79 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 818.69 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.96 | |||||
Maximum of Months | 1169.53 | 818.69 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 310.19 | 915.50 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 948.05 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 187.28 | 02-JAN-05:00 |
February | 1354.32 | 01-FEB-00:10 | 948.05 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 192.42 | 06-FEB-03:00 |
March | 1354.32 | 01-MAR-00:10 | 948.05 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.47 | 27-MAR-15:55 | 146.07 | 23-MAR-06:00 |
April | 1354.32 | 01-APR-00:10 | 948.05 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.51 | 07-APR-13:00 | 104.82 | 03-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 948.05 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 | 30-MAY-13:00 | 83.26 | 01-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 948.05 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.81 | 19-JUN-12:00 | 45.81 | 03-JUN-03:00 |
July | 1354.32 | 01-JUL-00:10 | 948.05 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.85 | 07-JUL-12:00 | 17.75 | 02-JUL-03:00 |
August | 1354.32 | 01-AUG-00:10 | 948.05 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.25 | 24-AUG-15:00 | 36.88 | 08-AUG-05:00 |
September | 1354.32 | 01-SEP-00:10 | 948.05 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.63 | 01-SEP-14:00 | 64.68 | 30-SEP-04:05 |
October | 1354.32 | 02-OCT-00:10 | 948.05 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 | 25-OCT-11:00 | 108.04 | 29-OCT-07:00 |
November | 1354.32 | 01-NOV-00:10 | 948.05 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 141.01 | 24-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 948.05 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 163.47 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 948.05 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.75 | |||||
Maximum of Months | 1354.32 | 948.05 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 70.81 | 192.42 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 453.61 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 614.19 | 02-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 453.61 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 627.54 | 06-FEB-07:20 |
March | 907.20 | 01-MAR-00:10 | 453.61 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 18.11 | 27-MAR-15:55 | 480.34 | 23-MAR-06:10 |
April | 907.20 | 01-APR-00:10 | 453.61 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 84.28 | 07-APR-13:00 | 352.75 | 03-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 453.61 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 132.59 | 30-MAY-13:00 | 270.54 | 01-MAY-05:20 |
June | 907.20 | 01-JUN-00:10 | 453.61 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 224.82 | 19-JUN-12:00 | 152.48 | 02-JUN-06:20 |
July | 907.20 | 01-JUL-00:10 | 453.61 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 186.76 | 07-JUL-12:00 | 69.96 | 01-JUL-22:00 |
August | 907.20 | 01-AUG-00:10 | 453.61 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 185.59 | 24-AUG-16:00 | 108.77 | 08-AUG-05:10 |
September | 907.20 | 01-SEP-00:10 | 453.61 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 146.14 | 01-SEP-14:00 | 208.31 | 24-SEP-06:20 |
October | 907.20 | 02-OCT-00:10 | 453.61 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 59.56 | 04-OCT-13:00 | 355.67 | 29-OCT-07:00 |
November | 907.20 | 01-NOV-00:10 | 453.61 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 472.25 | 24-NOV-07:10 |
December | 907.20 | 01-DEC-00:10 | 453.61 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 536.13 | 31-DEC-23:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 | ||||||
Maximum of Months | 907.20 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 224.82 | 627.54 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1628.35 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2252.33 | 02-JAN-05:00 |
February | 15368.40 | 01-FEB-00:10 | 1628.35 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2314.04 | 06-FEB-03:00 |
March | 15368.40 | 01-MAR-00:10 | 1628.35 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27-MAR-16:00 | 1749.26 | 23-MAR-04:30 |
April | 15368.40 | 01-APR-00:10 | 1628.35 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.21 | 08-APR-10:00 | 1253.58 | 01-APR-04:00 |
May | 15368.40 | 01-MAY-00:10 | 1628.35 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.46 | 30-MAY-13:00 | 1024.11 | 01-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1628.35 | 01-JUN-19:19 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 800.88 | 19-JUN-12:00 | 589.28 | 03-JUN-03:05 |
July | 15368.40 | 01-JUL-00:10 | 1628.35 | 03-JUL-19:19 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.90 | 07-JUL-12:00 | 241.84 | 01-JUL-23:30 |
August | 15368.40 | 01-AUG-00:10 | 1628.35 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 593.95 | 24-AUG-15:00 | 487.51 | 08-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1628.35 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.25 | 01-SEP-14:00 | 829.36 | 30-SEP-03:55 |
October | 15368.40 | 02-OCT-00:10 | 1628.35 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.48 | 25-OCT-11:40 | 1274.34 | 29-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 1628.35 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 1696.82 | 24-NOV-06:00 |
December | 15368.40 | 01-DEC-00:10 | 1628.35 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1937.72 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1628.35 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.84 | |||||
Maximum of Months | 15368.40 | 1628.35 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 800.88 | 2314.04 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 13433.46 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4556.78 | 02-JAN-05:00 |
February | 45622.98 | 01-FEB-00:10 | 13433.46 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4701.75 | 06-FEB-03:00 |
March | 45622.98 | 01-MAR-00:10 | 13433.46 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.29 | 27-MAR-15:55 | 3598.23 | 23-MAR-04:40 |
April | 45622.98 | 01-APR-00:10 | 13433.46 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.71 | 07-APR-13:00 | 2589.38 | 03-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 13433.46 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 979.33 | 30-MAY-13:00 | 2104.14 | 01-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 13433.46 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.09 | 19-JUN-12:00 | 1185.83 | 03-JUN-03:00 |
July | 45622.98 | 01-JUL-00:10 | 13433.46 | 03-JUL-19:19 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1354.83 | 07-JUL-12:00 | 479.47 | 02-JUL-03:00 |
August | 45622.98 | 01-AUG-00:10 | 13433.46 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.36 | 24-AUG-15:00 | 977.40 | 08-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 13433.46 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1013.54 | 01-SEP-14:00 | 1654.23 | 30-SEP-04:05 |
October | 45622.98 | 02-OCT-00:10 | 13433.46 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.27 | 25-OCT-11:00 | 2659.31 | 29-OCT-07:00 |
November | 45622.98 | 01-NOV-00:10 | 13433.46 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 3490.47 | 24-NOV-06:00 |
December | 45622.98 | 01-DEC-00:10 | 13433.46 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3998.79 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 13433.46 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.47 | |||||
Maximum of Months | 45622.98 | 13433.46 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.09 | 4701.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 305.78 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 305.78 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 305.78 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 200.16 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 305.78 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.47 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 305.78 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-16:00 | 110.09 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 305.78 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19-JUN-12:00 | 66.51 | 02-JUN-19:00 |
July | 180.00 | 01-JUL-00:10 | 305.78 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-JUL-15:10 | 41.01 | 01-JUL-20:00 |
August | 180.00 | 01-AUG-00:10 | 305.78 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 305.78 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 305.78 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:10 | 142.33 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 305.78 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 194.98 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 305.78 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.89 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 305.78 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.01 | |||||
Maximum of Months | 180.00 | 305.78 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 305.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.54 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 305.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.71 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 305.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 200.15 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 305.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.46 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 305.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-16:00 | 110.08 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 305.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 66.35 | 02-JUN-19:00 |
July | 180.00 | 01-JUL-00:10 | 305.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 10-JUL-15:10 | 40.79 | 01-JUL-20:00 |
August | 180.00 | 01-AUG-00:10 | 305.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 305.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 305.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 25-OCT-11:00 | 142.32 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 305.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 194.96 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 305.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.87 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 305.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.79 | |||||
Maximum of Months | 180.00 | 305.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.71 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 192.17 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 68.64 | 02-JAN-05:00 |
February | 0.00 | 01-FEB-00:10 | 192.17 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 70.75 | 06-FEB-03:00 |
March | 0.00 | 01-MAR-00:10 | 192.17 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 53.84 | 23-MAR-06:00 |
April | 0.00 | 01-APR-00:10 | 192.17 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | 07-APR-13:00 | 38.66 | 12-APR-06:20 |
May | 0.00 | 01-MAY-00:10 | 192.17 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 30-MAY-13:00 | 31.44 | 01-MAY-05:10 |
June | 0.00 | 01-JUN-00:10 | 192.17 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 19-JUN-12:00 | 18.80 | 03-JUN-03:00 |
July | 0.00 | 01-JUL-00:10 | 192.17 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 07-JUL-12:00 | 9.33 | 02-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 192.17 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 24-AUG-15:00 | 15.88 | 08-AUG-05:00 |
September | 0.00 | 01-SEP-00:10 | 192.17 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.21 | 01-SEP-14:00 | 25.42 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 192.17 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.07 | 04-OCT-13:00 | 42.30 | 29-OCT-07:00 |
November | 0.00 | 01-NOV-00:10 | 192.17 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 53.13 | 24-NOV-08:00 |
December | 0.00 | 01-DEC-00:10 | 192.17 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 58.53 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 192.17 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | |||||
Maximum of Months | 0.00 | 192.17 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 24.26 | 70.75 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 192.22 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 73.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 192.22 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 75.56 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 192.22 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.19 | 27-MAR-15:55 | 55.86 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 192.22 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.32 | 08-APR-10:00 | 39.48 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 192.22 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 30-MAY-15:50 | 30.72 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 192.22 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 19-JUN-12:00 | 15.51 | 03-JUN-03:00 |
July | 180.00 | 01-JUL-00:10 | 192.22 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 10-JUL-15:10 | 8.16 | 01-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 192.22 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | 24-AUG-15:10 | 12.17 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 192.22 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.73 | 01-SEP-15:08 | 22.48 | 24-SEP-05:53 |
October | 180.00 | 01-OCT-00:10 | 192.22 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 | 25-OCT-11:00 | 39.72 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 192.22 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 54.42 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 192.22 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 63.32 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 192.22 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | |||||
Maximum of Months | 180.00 | 192.22 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 | 75.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 305.78 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.56 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 305.78 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.73 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 305.78 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.07 | 27-MAR-15:55 | 200.17 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 305.78 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.47 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 305.78 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 | 30-MAY-16:00 | 110.09 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 305.78 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19-JUN-12:00 | 62.96 | 03-JUN-08:10 |
July | 180.00 | 01-JUL-00:10 | 305.78 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.74 | 10-JUL-15:08 | 29.67 | 01-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 305.78 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.51 | 24-AUG-15:10 | 43.62 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 305.78 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.95 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 305.78 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:08 | 142.34 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 305.78 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 194.98 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 305.78 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.88 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 305.78 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | |||||
Maximum of Months | 180.00 | 305.78 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 270.73 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 305.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 263.54 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 305.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 270.70 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 305.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.20 | 27-MAR-15:55 | 200.15 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 305.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 08-APR-10:00 | 141.46 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 305.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.18 | 30-MAY-15:50 | 110.08 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 305.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 19-JUN-12:00 | 62.80 | 03-JUN-08:10 |
July | 180.00 | 01-JUL-00:10 | 305.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.73 | 10-JUL-15:08 | 29.68 | 01-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 305.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.50 | 24-AUG-15:08 | 43.61 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 305.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.94 | 01-SEP-15:10 | 80.56 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 305.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 04-OCT-15:10 | 142.32 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 305.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 194.96 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 305.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 226.87 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 305.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.68 | |||||
Maximum of Months | 180.00 | 305.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.94 | 270.70 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 305.78 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 264.09 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 305.78 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 271.25 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 305.78 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 200.68 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 305.78 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 08-APR-10:00 | 141.95 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 305.78 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 | 30-MAY-16:00 | 110.55 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 305.78 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 19-JUN-12:00 | 76.91 | 02-JUN-19:00 |
July | 180.00 | 01-JUL-00:10 | 305.78 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 10-JUL-15:10 | 52.41 | 01-JUL-20:00 |
August | 180.00 | 01-AUG-00:10 | 305.78 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 24-AUG-16:00 | 48.47 | 28-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 305.78 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.34 | 01-SEP-15:10 | 81.01 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 305.78 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 | 04-OCT-15:10 | 142.82 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 305.78 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 195.48 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 305.78 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.40 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 305.78 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.47 | |||||
Maximum of Months | 180.00 | 305.78 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 86.58 | 271.25 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 305.75 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 264.08 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 305.75 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 271.24 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 305.75 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 200.65 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 305.75 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 08-APR-10:00 | 141.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 305.75 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 | 30-MAY-16:00 | 110.54 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 305.75 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 19-JUN-12:00 | 77.04 | 02-JUN-19:00 |
July | 180.00 | 01-JUL-00:10 | 305.75 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 10-JUL-15:10 | 52.45 | 01-JUL-20:00 |
August | 180.00 | 01-AUG-00:10 | 305.75 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 | 24-AUG-15:10 | 46.19 | 28-AUG-21:00 |
September | 180.00 | 01-SEP-00:10 | 305.75 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 01-SEP-15:10 | 81.01 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 305.75 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 04-OCT-15:10 | 142.81 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 305.75 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 195.46 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 305.75 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 227.38 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 305.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.19 | |||||
Maximum of Months | 180.00 | 305.75 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 | 271.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 192.22 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 135.11 | 02-JAN-05:00 |
February | 180.00 | 01-FEB-00:10 | 192.22 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 138.77 | 06-FEB-03:00 |
March | 180.00 | 01-MAR-00:10 | 192.22 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 102.66 | 23-MAR-06:00 |
April | 180.00 | 01-APR-00:10 | 192.22 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 08-APR-10:00 | 72.62 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 192.22 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 30-MAY-16:00 | 56.56 | 01-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 192.22 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 19-JUN-12:00 | 28.66 | 03-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 192.22 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 10-JUL-15:10 | 16.43 | 01-JUL-21:10 |
August | 180.00 | 01-AUG-00:10 | 192.22 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 | 24-AUG-16:00 | 22.54 | 08-AUG-05:00 |
September | 180.00 | 01-SEP-00:10 | 192.22 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 | 14-SEP-16:00 | 41.45 | 24-SEP-06:00 |
October | 180.00 | 01-OCT-00:10 | 192.22 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 | 25-OCT-10:00 | 73.07 | 09-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 192.22 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 100.01 | 24-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 192.22 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 116.34 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 192.22 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 | |||||
Maximum of Months | 180.00 | 192.22 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | 138.77 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2859.51 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 686.80 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2859.51 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 703.95 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2859.51 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 540.79 | 23-MAR-04:30 |
April | 26988.77 | 01-APR-00:10 | 2859.51 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.39 | 07-APR-13:00 | 399.20 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2859.51 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.73 | 30-MAY-13:00 | 321.44 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2859.51 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.82 | 19-JUN-12:00 | 186.63 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2859.51 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.30 | 07-JUL-12:00 | 88.13 | 01-JUL-23:10 |
August | 26988.77 | 01-AUG-00:10 | 2859.51 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.17 | 24-AUG-15:00 | 157.45 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2859.51 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.96 | 01-SEP-14:00 | 245.76 | 24-SEP-05:57 |
October | 26988.77 | 02-OCT-00:10 | 2859.51 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 | 25-OCT-11:00 | 401.13 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2859.51 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 526.14 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2859.51 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 609.55 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2859.51 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.13 | |||||
Maximum of Months | 26988.77 | 2859.51 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 217.82 | 703.95 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2859.51 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 691.26 | 02-JAN-05:00 |
February | 26988.77 | 01-FEB-00:10 | 2859.51 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 708.42 | 06-FEB-03:00 |
March | 26988.77 | 01-MAR-00:10 | 2859.51 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 543.71 | 23-MAR-06:00 |
April | 26988.77 | 01-APR-00:10 | 2859.51 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.22 | 07-APR-13:00 | 399.21 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2859.51 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.91 | 30-MAY-13:00 | 321.45 | 01-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2859.51 | 01-JUN-19:19 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 | 19-JUN-12:00 | 186.64 | 03-JUN-03:10 |
July | 26988.77 | 01-JUL-00:10 | 2859.51 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.33 | 07-JUL-12:00 | 90.72 | 02-JUL-05:10 |
August | 26988.77 | 01-AUG-00:10 | 2859.51 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.86 | 24-AUG-15:00 | 157.45 | 08-AUG-05:00 |
September | 26988.77 | 01-SEP-00:10 | 2859.51 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.33 | 01-SEP-14:00 | 246.79 | 24-SEP-06:15 |
October | 26988.77 | 02-OCT-00:10 | 2859.51 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.78 | 25-OCT-11:00 | 401.66 | 09-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2859.51 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 530.16 | 24-NOV-06:00 |
December | 26988.77 | 01-DEC-00:10 | 2859.51 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 609.56 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2859.51 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.72 | |||||
Maximum of Months | 26988.77 | 2859.51 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 | 708.42 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1210.92 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 617.33 | 02-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1210.92 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 629.85 | 06-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1210.92 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 486.75 | 23-MAR-06:00 |
April | 2401.70 | 01-APR-00:10 | 1210.92 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 38.35 | 07-APR-13:00 | 357.24 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1210.92 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 86.73 | 30-MAY-13:00 | 284.65 | 01-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1210.92 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 179.95 | 19-JUN-12:00 | 163.25 | 03-JUN-05:10 |
July | 2401.70 | 01-JUL-00:10 | 1210.92 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 141.54 | 07-JUL-12:00 | 79.01 | 02-JUL-05:20 |
August | 2401.70 | 01-AUG-00:10 | 1210.92 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 140.57 | 24-AUG-15:50 | 135.11 | 08-AUG-05:10 |
September | 2401.70 | 01-SEP-00:10 | 1210.92 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 101.08 | 01-SEP-14:00 | 241.18 | 24-SEP-05:57 |
October | 2401.70 | 02-OCT-00:10 | 1210.92 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 13.49 | 04-OCT-13:00 | 359.46 | 09-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1210.92 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 475.32 | 24-NOV-07:00 |
December | 2401.70 | 01-DEC-00:10 | 1210.92 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 545.60 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 | ||||||
Maximum of Months | 2401.70 | 1210.92 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 179.95 | 629.85 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1511.55 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 412.34 | 02-JAN-05:00 |
February | 0.00 | 1511.55 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 423.64 | 06-FEB-03:00 |
March | 0.00 | 1511.55 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 27-MAR-15:55 | 312.77 | 23-MAR-06:00 |
April | 0.00 | 1511.55 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.60 | 07-APR-13:00 | 220.55 | 03-APR-06:00 |
May | 0.00 | 1511.55 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.99 | 30-MAY-13:00 | 171.31 | 01-MAY-05:00 |
June | 0.00 | 1511.55 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 19-JUN-12:00 | 91.11 | 03-JUN-03:00 |
July | 0.00 | 1511.55 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 | 07-JUL-12:00 | 33.44 | 02-JUL-03:00 |
August | 0.00 | 1511.55 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.56 | 24-AUG-15:00 | 73.25 | 08-AUG-05:00 |
September | 0.00 | 1511.55 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.22 | 01-SEP-14:00 | 128.09 | 24-SEP-06:00 |
October | 0.00 | 1511.55 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.07 | 04-OCT-13:00 | 225.57 | 09-OCT-06:00 |
November | 0.00 | 1511.55 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 304.61 | 24-NOV-07:00 |
December | 0.00 | 1511.55 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 354.74 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.44 | ||||
Maximum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 156.29 | 423.64 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 257.34 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 285.80 | 02-JAN-05:00 |
February | 0.00 | 257.34 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 294.38 | 06-FEB-03:00 |
March | 0.00 | 257.34 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 27-MAR-15:55 | 217.46 | 23-MAR-06:00 |
April | 0.00 | 257.34 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 | 07-APR-13:00 | 153.35 | 03-APR-06:00 |
May | 0.00 | 257.34 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.27 | 30-MAY-13:00 | 119.08 | 01-MAY-05:00 |
June | 0.00 | 257.34 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.37 | 19-JUN-12:00 | 61.37 | 03-JUN-03:00 |
July | 0.00 | 257.34 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.95 | 07-JUL-12:00 | 21.70 | 02-JUL-03:00 |
August | 0.00 | 257.34 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.49 | 24-AUG-15:00 | 49.17 | 08-AUG-05:00 |
September | 0.00 | 257.34 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.75 | 01-SEP-14:00 | 87.15 | 24-SEP-05:57 |
October | 0.00 | 257.34 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.74 | 25-OCT-11:00 | 154.28 | 09-OCT-06:00 |
November | 0.00 | 257.34 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 211.80 | 24-NOV-07:00 |
December | 0.00 | 257.34 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 246.64 | 31-DEC-24:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 257.34 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | ||||
Maximum of Months | 0.00 | 257.34 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 107.37 | 294.38 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1350.19 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 313.45 | 02-JAN-05:00 |
February | 0.00 | 1350.19 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 323.34 | 06-FEB-03:00 |
March | 0.00 | 1350.19 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 27-MAR-16:00 | 241.02 | 23-MAR-06:00 |
April | 0.00 | 1350.19 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 07-APR-13:00 | 170.06 | 03-APR-06:00 |
May | 0.00 | 1350.19 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.96 | 30-MAY-13:00 | 132.15 | 01-MAY-05:00 |
June | 0.00 | 1350.19 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 19-JUN-12:00 | 66.26 | 03-JUN-05:00 |
July | 0.00 | 1350.19 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.81 | 07-JUL-12:00 | 23.10 | 02-JUL-05:00 |
August | 0.00 | 1350.19 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 | 24-AUG-16:00 | 51.80 | 08-AUG-05:00 |
September | 0.00 | 1350.19 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.96 | 01-SEP-14:00 | 96.45 | 24-SEP-06:00 |
October | 0.00 | 1350.19 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.77 | 25-OCT-11:00 | 171.11 | 09-OCT-06:00 |
November | 0.00 | 1350.19 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 234.74 | 24-NOV-07:00 |
December | 0.00 | 1350.19 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 273.10 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | |||
Maximum of Months | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.60 | 323.34 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1428.96 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 560.12 | 02-JAN-05:00 |
February | 0.00 | 1428.96 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 577.29 | 06-FEB-03:00 |
March | 0.00 | 1428.96 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.82 | 27-MAR-15:55 | 427.59 | 23-MAR-06:00 |
April | 0.00 | 1428.96 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.41 | 08-APR-10:00 | 301.99 | 03-APR-06:00 |
May | 0.00 | 1428.96 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.32 | 30-MAY-13:00 | 234.83 | 01-MAY-05:00 |
June | 0.00 | 1428.96 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.55 | 19-JUN-12:00 | 119.73 | 03-JUN-03:00 |
July | 0.00 | 1428.96 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.82 | 07-JUL-12:00 | 41.76 | 02-JUL-05:00 |
August | 0.00 | 1428.96 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.64 | 24-AUG-16:00 | 93.45 | 08-AUG-05:00 |
September | 0.00 | 1428.96 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.35 | 14-SEP-14:00 | 171.76 | 24-SEP-05:57 |
October | 0.00 | 1428.96 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.18 | 25-OCT-11:00 | 303.81 | 09-OCT-06:00 |
November | 0.00 | 1428.96 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 416.49 | 24-NOV-07:00 |
December | 0.00 | 1428.96 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 484.76 | 31-DEC-24:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1428.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.76 | |||
Maximum of Months | 0.00 | 1428.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.55 | 577.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22520.79 | 21-JAN-20:06 | 76679.28 | 109324.90 | 81116.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22740.65 | 19-FEB-12:42 | 23003.78 | 28112.12 | 24334.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22701.20 | 12-MAR-08:62 | 25559.76 | 18741.41 | 16223.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20716.64 | 22-APR-23:00 | 44729.58 | 23426.76 | 20279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 19333.45 | 01-MAY-06:24 | 51119.52 | 78089.21 | 60837.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16074.38 | 22-JUN-20:00 | 8945.92 | 14056.06 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16220.29 | 13-JUL-21:00 | 51119.52 | 62471.37 | 45627.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17815.40 | 24-AUG-19:00 | 8945.92 | 12494.27 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20205.72 | 24-SEP-05:45 | 17891.83 | 9370.71 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32124.71 | 27-OCT-22:03 | 46007.57 | 18741.41 | 16223.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 27229.02 | 01-NOV-22:26 | 57509.46 | 23426.76 | 20279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23601.81 | 16-DEC-12:14 | 38339.64 | 39044.61 | 35488.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 16074.38 | 8945.92 | 9370.71 | 8111.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32124.71 | 76679.28 | 109324.90 | 81116.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3291.09 | 17-JAN-12:50 | 1039.58 | 909.66 | 1010.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.56 |
February | 3201.45 | 19-FEB-12:42 | 2339.06 | 1637.38 | 1732.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.11 |
March | 3605.43 | 07-MAR-13:33 | 2079.17 | 1819.31 | 2020.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.39 |
April | 2572.65 | 07-APR-12:40 | 259.90 | 227.41 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 | 0.00 |
May | 2190.71 | 30-MAY-15:10 | 3898.44 | 1364.49 | 1515.54 | 0.00 | 0.00 | 0.00 | 0.00 | 133.20 | 0.00 |
June | 2386.61 | 19-JUN-19:20 | 909.64 | 818.69 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 176.52 | 0.00 |
July | 2409.79 | 08-JUL-12:40 | 389.84 | 227.41 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 182.26 | 0.00 |
August | 2763.59 | 30-AUG-12:00 | 519.79 | 454.83 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 66.82 | 0.00 |
September | 3482.80 | 30-SEP-12:40 | 389.84 | 227.41 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.34 |
October | 3714.46 | 04-OCT-12:10 | 259.90 | 227.41 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 11.52 | 0.00 |
November | 3185.62 | 29-NOV-12:43 | 1819.27 | 1591.90 | 1768.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.70 |
December | 3747.73 | 03-DEC-12:44 | 2728.91 | 1910.28 | 2020.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.17 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2190.71 | 259.90 | 227.41 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3747.73 | 3898.44 | 1910.28 | 2020.73 | 0.00 | 0.00 | 0.00 | 0.00 | 182.26 | 392.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1929.40 | 21-JAN-20:06 | 9028.80 | 7373.71 | 6685.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.05 |
February | 2062.29 | 19-FEB-12:42 | 2708.64 | 1896.10 | 2005.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.03 |
March | 2081.33 | 12-MAR-08:62 | 3009.60 | 1264.06 | 1337.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.24 |
April | 2108.42 | 11-APR-22:30 | 4062.96 | 948.05 | 1002.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.91 |
May | 1955.00 | 14-MAY-23:43 | 7373.52 | 2212.11 | 2340.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.49 |
June | 1804.24 | 19-JUN-21:10 | 1354.32 | 632.03 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 | 0.00 |
July | 1825.19 | 10-JUL-21:10 | 1354.32 | 632.03 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.84 | 0.00 |
August | 1895.04 | 24-AUG-19:00 | 1053.36 | 842.71 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 | 0.00 |
September | 1820.47 | 01-SEP-21:10 | 1354.32 | 632.03 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.39 | 0.00 |
October | 2259.63 | 08-OCT-22:00 | 7223.04 | 3160.16 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 |
November | 2131.27 | 05-NOV-22:01 | 8426.88 | 2212.11 | 2340.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.79 |
December | 1983.35 | 16-DEC-12:14 | 4514.40 | 2633.47 | 2925.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1804.24 | 1053.36 | 632.03 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2259.63 | 9028.80 | 7373.71 | 6685.74 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 | 88.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1712.70 | 21-JAN-20:06 | 0.00 | 11756.53 | 7069.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.78 |
February | 1187.77 | 19-FEB-12:42 | 0.00 | 3023.11 | 2120.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.29 |
March | 1818.41 | 28-MAR-22:45 | 0.00 | 1007.70 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.55 |
April | 1835.34 | 11-APR-22:30 | 0.00 | 1511.55 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.16 |
May | 1723.92 | 14-MAY-23:43 | 0.00 | 3526.96 | 2474.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.10 |
June | 1595.69 | 22-JUN-20:00 | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.20 | 0.00 |
July | 1644.15 | 10-JUL-21:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 44.73 | 0.00 |
August | 1701.71 | 24-AUG-19:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 | 0.00 |
September | 1609.93 | 24-SEP-05:45 | 0.00 | 1007.70 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.12 |
October | 1969.56 | 18-OCT-08:18 | 0.00 | 6718.02 | 4418.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.28 |
November | 1887.36 | 05-NOV-22:01 | 0.00 | 3526.96 | 2474.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.61 |
December | 1616.42 | 20-DEC-11:34 | 0.00 | 4198.76 | 3092.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1187.77 | 0.00 | 1007.70 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1969.56 | 0.00 | 11756.53 | 7069.03 | 0.00 | 0.00 | 0.00 | 0.00 | 71.06 | 166.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 458.83 | 24-JAN-07:30 | 0.00 | 285.94 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.83 |
February | 433.20 | 19-FEB-12:34 | 0.00 | 600.47 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.93 |
March | 839.55 | 28-MAR-22:45 | 0.00 | 171.56 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.55 |
April | 844.54 | 11-APR-22:30 | 0.00 | 257.34 | 305.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.47 |
May | 799.15 | 14-MAY-23:43 | 0.00 | 600.47 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.24 |
June | 746.96 | 19-JUN-21:10 | 0.00 | 171.56 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 0.00 |
July | 768.55 | 10-JUL-21:10 | 0.00 | 171.56 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 33.66 | 0.00 |
August | 802.49 | 24-AUG-19:00 | 0.00 | 228.75 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 0.00 |
September | 745.33 | 01-SEP-21:10 | 0.00 | 171.56 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 31.82 | 0.00 |
October | 912.52 | 18-OCT-08:18 | 0.00 | 1143.75 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.56 |
November | 860.54 | 05-NOV-22:01 | 0.00 | 600.47 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.10 |
December | 505.39 | 03-DEC-12:44 | 0.00 | 600.47 | 713.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 433.20 | 0.00 | 171.56 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 912.52 | 0.00 | 1143.75 | 1274.51 | 0.00 | 0.00 | 0.00 | 0.00 | 51.71 | 110.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39629.07 | 24-JAN-20:26 | 3528.00 | 2268.03 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 264.14 |
February | 36006.63 | 17-FEB-21:00 | 705.60 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 386.76 |
March | 39555.39 | 28-MAR-19:57 | 2822.40 | 1814.42 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 0.00 | 255.72 |
April | 41241.94 | 12-APR-20:40 | 3225.60 | 1612.82 | 17328.51 | 150542.82 | 0.00 | 0.00 | 0.00 | 0.00 | 280.01 |
May | 38760.80 | 01-MAY-20:47 | 2419.20 | 1209.61 | 12996.38 | 112907.11 | 0.00 | 0.00 | 0.00 | 0.00 | 251.21 |
June | 38277.26 | 19-JUN-20:00 | 705.60 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 87.98 | 0.00 |
July | 38266.18 | 10-JUL-20:00 | 705.60 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 63.25 | 0.00 |
August | 38428.61 | 04-AUG-20:00 | 705.60 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 119.23 | 0.00 |
September | 38401.37 | 14-SEP-19:44 | 3528.00 | 2268.03 | 22864.00 | 198632.88 | 0.00 | 0.00 | 0.00 | 35.08 | 0.00 |
October | 46013.45 | 26-OCT-21:20 | 9072.00 | 3024.04 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 0.00 | 261.68 |
November | 42067.01 | 16-NOV-21:00 | 4939.20 | 3175.24 | 32009.60 | 278086.04 | 0.00 | 0.00 | 0.00 | 0.00 | 274.44 |
December | 40865.69 | 17-DEC-19:37 | 1814.40 | 1058.41 | 11552.34 | 100361.88 | 0.00 | 0.00 | 0.00 | 0.00 | 283.19 |
Annual Sum or Average | |||||||||||
Minimum of Months | 36006.63 | 705.60 | 453.61 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 46013.45 | 9072.00 | 3175.24 | 33694.32 | 292722.14 | 0.00 | 0.00 | 0.00 | 119.23 | 386.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12739.12 | 17-JAN-12:50 | 13660.80 | 398.04 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874.93 |
February | 13477.45 | 19-FEB-12:34 | 35859.60 | 835.88 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.12 |
March | 14493.59 | 07-MAR-13:33 | 27321.60 | 796.08 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.30 |
April | 11387.34 | 11-APR-22:30 | 46105.20 | 1628.35 | 1219.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 944.59 |
May | 10549.27 | 17-MAY-03:05 | 30736.80 | 361.85 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.31 |
June | 10852.23 | 19-JUN-21:10 | 15368.40 | 1085.56 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 272.07 | 0.00 |
July | 10787.90 | 10-JUL-21:10 | 15368.40 | 1085.56 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 180.42 | 0.00 |
August | 11769.84 | 04-AUG-21:10 | 15368.40 | 1085.56 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 | 0.00 |
September | 13243.64 | 30-SEP-12:30 | 5122.80 | 99.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.34 |
October | 13517.83 | 28-OCT-11:45 | 10245.60 | 199.02 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 867.44 |
November | 13166.04 | 18-NOV-12:32 | 20491.20 | 398.04 | 1422.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.52 |
December | 15202.13 | 03-DEC-12:44 | 35859.60 | 835.88 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 994.81 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10549.27 | 5122.80 | 99.51 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15202.13 | 46105.20 | 1628.35 | 2845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 | 1046.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39088.13 | 21-JAN-20:06 | 304153.20 | 104482.49 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1929.55 |
February | 42755.83 | 19-FEB-12:42 | 91245.96 | 23105.56 | 25336.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1779.33 |
March | 42336.60 | 28-MAR-22:45 | 91245.96 | 8955.64 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2012.60 |
April | 42553.48 | 11-APR-22:30 | 136868.94 | 13433.46 | 12668.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.93 |
May | 39468.88 | 17-MAY-03:05 | 91245.96 | 2985.21 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1598.61 |
June | 36094.66 | 19-JUN-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 567.96 | 0.00 |
July | 36457.20 | 10-JUL-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 372.45 | 0.00 |
August | 37752.22 | 04-AUG-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 858.18 | 0.00 |
September | 36531.26 | 30-SEP-05:20 | 70969.08 | 8955.64 | 8445.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1528.44 |
October | 60378.86 | 26-OCT-21:20 | 456229.80 | 89556.42 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.00 |
November | 43518.79 | 05-NOV-22:01 | 283876.32 | 31344.75 | 29559.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2012.96 |
December | 41472.01 | 16-DEC-12:14 | 152076.60 | 32091.05 | 36949.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1776.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 36094.66 | 45622.98 | 2985.21 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60378.86 | 456229.80 | 104482.49 | 84456.50 | 0.00 | 0.00 | 0.00 | 0.00 | 858.18 | 2012.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3254.41 | 17-JAN-16:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.41 |
February | 3240.81 | 02-FEB-16:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.58 |
March | 3324.44 | 07-MAR-16:01 | 777.60 | 195.70 | 400.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.89 |
April | 3579.09 | 09-APR-17:31 | 972.00 | 2599.14 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.09 |
May | 3623.22 | 27-MAY-21:11 | 1386.00 | 2599.14 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
June | 3466.36 | 20-JUN-21:11 | 1800.00 | 2064.03 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 |
July | 3427.50 | 04-JUL-21:11 | 1386.00 | 2599.14 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.29 |
August | 3612.43 | 25-AUG-21:11 | 1800.00 | 2064.03 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 |
September | 3606.42 | 10-SEP-21:11 | 1386.00 | 2599.14 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 |
October | 3380.20 | 30-OCT-16:01 | 777.60 | 214.05 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 |
November | 3283.58 | 02-NOV-15:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.97 |
December | 3199.70 | 17-DEC-16:01 | 378.00 | 133.78 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3199.70 | 378.00 | 133.78 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | |
Maximum of Months | 3623.22 | 1800.00 | 2599.14 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1266.97 | 17-JAN-16:01 | 680.40 | 171.22 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.56 |
February | 2331.48 | 20-FEB-16:01 | 378.00 | 133.76 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.81 |
March | 3206.12 | 11-MAR-16:01 | 378.00 | 133.76 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.14 |
April | 3455.90 | 09-APR-17:31 | 972.00 | 2598.84 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.18 |
May | 3554.25 | 27-MAY-21:11 | 1386.00 | 2598.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 |
June | 3425.94 | 22-JUN-21:11 | 1800.00 | 2063.78 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 0.00 |
July | 3367.74 | 04-JUL-21:11 | 1386.00 | 2598.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.92 |
August | 3475.88 | 28-AUG-21:11 | 1800.00 | 2063.78 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.10 |
September | 3439.84 | 10-SEP-21:11 | 1386.00 | 2598.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 |
October | 3214.96 | 30-OCT-15:01 | 680.40 | 171.22 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.61 |
November | 3064.59 | 03-NOV-15:02 | 583.20 | 146.76 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 |
December | 610.81 | 25-DEC-16:03 | 324.00 | 114.65 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 610.81 | 324.00 | 114.65 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3554.25 | 1800.00 | 2598.84 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 12.95 | 100.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 195.93 | 19-JAN-14:10 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.99 |
February | 338.67 | 03-FEB-12:30 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.60 |
March | 421.74 | 03-MAR-13:30 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.12 |
April | 491.85 | 08-APR-12:30 | 0.00 | 12.01 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
May | 426.56 | 30-MAY-16:40 | 0.00 | 16.82 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
June | 497.37 | 25-JUN-21:00 | 0.00 | 192.17 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | 0.00 |
July | 561.43 | 21-JUL-18:00 | 0.00 | 129.72 | 123.84 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 | 0.00 |
August | 544.15 | 01-AUG-19:01 | 0.00 | 1345.20 | 1119.68 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 0.00 |
September | 631.25 | 28-SEP-12:30 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 693.99 | 04-OCT-12:00 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
November | 602.37 | 02-NOV-12:30 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
December | 509.41 | 17-DEC-12:30 | 0.00 | 12.01 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 195.93 | 0.00 | 12.01 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 693.99 | 0.00 | 1345.20 | 1119.68 | 0.00 | 0.00 | 0.00 | 0.00 | 6.27 | 51.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 695.94 | 22-JAN-09:02 | 324.00 | 269.11 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.97 |
February | 723.84 | 20-FEB-09:02 | 270.00 | 224.26 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
March | 1007.91 | 28-MAR-18:01 | 970.20 | 1194.19 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.34 |
April | 1078.56 | 07-APR-21:11 | 1800.00 | 1297.52 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 |
May | 1160.04 | 27-MAY-21:11 | 1386.00 | 1633.91 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
June | 1154.47 | 04-JUN-08:11 | 540.00 | 448.52 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 1112.74 | 04-JUL-21:11 | 1386.00 | 1633.91 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.25 |
August | 1157.32 | 28-AUG-21:11 | 1800.00 | 1297.52 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.54 |
September | 1136.37 | 01-SEP-21:11 | 1800.00 | 1297.52 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
October | 1052.13 | 25-OCT-21:11 | 1260.00 | 908.26 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.98 |
November | 979.57 | 02-NOV-18:02 | 831.60 | 1023.60 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.63 |
December | 787.55 | 25-DEC-09:02 | 270.00 | 224.26 | 799.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 695.94 | 270.00 | 224.26 | 614.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1160.04 | 1800.00 | 1633.91 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 32.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2078.04 | 19-JAN-09:02 | 216.00 | 802.68 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.99 |
February | 2861.74 | 25-FEB-09:02 | 324.00 | 428.09 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.84 |
March | 2964.59 | 11-MAR-09:02 | 324.00 | 428.09 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.78 |
April | 3302.54 | 08-APR-08:11 | 540.00 | 713.49 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 |
May | 3733.58 | 30-MAY-08:11 | 360.00 | 1337.79 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 |
June | 3688.46 | 26-JUN-08:11 | 360.00 | 1337.79 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.75 |
July | 3612.93 | 14-JUL-07:31 | 774.00 | 1337.79 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 0.00 |
August | 3769.99 | 22-AUG-08:11 | 360.00 | 1337.79 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 3591.71 | 06-SEP-08:11 | 360.00 | 1337.79 | 1132.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
October | 3009.33 | 30-OCT-15:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.32 |
November | 2974.22 | 02-NOV-15:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.20 |
December | 2864.12 | 17-DEC-09:02 | 324.00 | 428.09 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2078.04 | 216.00 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3769.99 | 774.00 | 1337.79 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 | 179.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 721.02 | 30-JAN-09:03 | 216.00 | 802.58 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.96 |
February | 2564.42 | 25-FEB-09:02 | 324.00 | 428.04 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.88 |
March | 2908.86 | 29-MAR-08:62 | 216.00 | 802.58 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.21 |
April | 3237.87 | 08-APR-08:11 | 540.00 | 713.41 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 |
May | 3710.24 | 30-MAY-08:11 | 360.00 | 1337.64 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.60 |
June | 3675.10 | 22-JUN-08:11 | 360.00 | 1337.64 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.12 |
July | 3583.37 | 14-JUL-07:31 | 774.00 | 1337.64 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 0.00 |
August | 3718.31 | 22-AUG-08:11 | 360.00 | 1337.64 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
September | 3527.90 | 03-SEP-08:11 | 540.00 | 713.41 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
October | 2828.01 | 16-OCT-08:62 | 216.00 | 802.58 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.96 |
November | 2543.97 | 04-NOV-08:62 | 270.00 | 356.70 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.66 |
December | 1385.23 | 17-DEC-09:02 | 324.00 | 428.04 | 979.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.13 |
Annual Sum or Average | |||||||||||
Minimum of Months | 721.02 | 216.00 | 356.70 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3718.31 | 774.00 | 1337.64 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.15 | 183.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1204.43 | 17-JAN-13:55 | 0.00 | 1500.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 |
February | 1296.63 | 19-FEB-12:42 | 0.00 | 2700.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.14 |
March | 1425.63 | 03-MAR-14:10 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.69 |
April | 1786.71 | 08-APR-11:50 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 0.00 |
May | 1824.30 | 30-MAY-08:30 | 0.00 | 4200.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 0.00 |
June | 1845.85 | 20-JUN-19:20 | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 0.00 |
July | 1847.32 | 10-JUL-18:40 | 0.00 | 1200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.09 | 0.00 |
August | 2001.61 | 24-AUG-19:00 | 0.00 | 1200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.94 | 0.00 |
September | 1853.81 | 07-SEP-21:10 | 0.00 | 900.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 0.00 |
October | 1817.64 | 04-OCT-14:00 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.39 | 0.00 |
November | 1566.96 | 04-NOV-12:40 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.74 |
December | 1363.97 | 03-DEC-12:44 | 0.00 | 3150.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.05 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1204.43 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2001.61 | 0.00 | 4200.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.94 | 112.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3413.90 | 17-JAN-16:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.02 |
February | 3400.71 | 02-FEB-16:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.34 |
March | 3483.63 | 07-MAR-16:01 | 777.60 | 195.70 | 400.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.33 |
April | 4116.86 | 09-APR-17:31 | 972.00 | 2599.14 | 1264.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.73 |
May | 3832.53 | 17-MAY-20:01 | 1602.00 | 2713.81 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.95 |
June | 3921.33 | 04-JUN-21:11 | 1386.00 | 2599.14 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 |
July | 3876.96 | 04-JUL-21:11 | 1386.00 | 2599.14 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.66 |
August | 4035.70 | 25-AUG-21:11 | 1800.00 | 2064.03 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 |
September | 3861.17 | 03-SEP-21:11 | 1386.00 | 2599.14 | 895.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.01 |
October | 3629.13 | 30-OCT-16:01 | 777.60 | 214.05 | 1011.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 |
November | 3436.91 | 02-NOV-15:01 | 680.40 | 171.24 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 |
December | 3381.71 | 17-DEC-16:01 | 378.00 | 133.78 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3381.71 | 378.00 | 133.78 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 | |
Maximum of Months | 4116.86 | 1800.00 | 2713.81 | 1817.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 741.16 | 20-JAN-16:03 | 680.40 | 171.22 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.42 |
February | 1902.36 | 20-FEB-16:01 | 378.00 | 133.76 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.07 |
March | 3356.99 | 11-MAR-16:01 | 378.00 | 133.76 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.71 |
April | 3886.79 | 09-APR-17:31 | 972.00 | 2598.84 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 |
May | 3748.95 | 12-MAY-18:51 | 1386.00 | 2713.49 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 |
June | 3850.21 | 04-JUN-21:11 | 1386.00 | 2598.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.93 |
July | 3810.96 | 04-JUL-21:11 | 1386.00 | 2598.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.38 |
August | 3920.18 | 25-AUG-21:11 | 1800.00 | 2063.78 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 |
September | 3719.92 | 03-SEP-21:11 | 1386.00 | 2598.84 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.68 |
October | 3364.35 | 04-OCT-15:02 | 583.20 | 146.76 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 0.00 |
November | 3215.79 | 03-NOV-15:02 | 583.20 | 146.76 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.31 |
December | 558.12 | 15-DEC-16:04 | 680.40 | 171.22 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.33 |
Annual Sum or Average | |||||||||||
Minimum of Months | 558.12 | 378.00 | 133.76 | 300.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3920.18 | 1800.00 | 2713.49 | 1264.17 | 0.00 | 0.00 | 0.00 | 0.00 | 6.53 | 123.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1652.69 | 17-JAN-16:01 | 680.40 | 107.65 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
February | 1646.22 | 02-FEB-16:01 | 680.40 | 107.65 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 |
March | 1648.56 | 15-MAR-15:02 | 583.20 | 92.27 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
April | 1712.41 | 07-APR-21:11 | 1800.00 | 1297.52 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.57 |
May | 1741.85 | 27-MAY-21:11 | 1386.00 | 1633.91 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
June | 1738.29 | 22-JUN-21:11 | 1800.00 | 1297.52 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 0.00 |
July | 1689.51 | 30-JUL-21:11 | 1386.00 | 1633.91 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
August | 1868.51 | 25-AUG-21:11 | 1800.00 | 1297.52 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 |
September | 1797.39 | 10-SEP-21:11 | 1386.00 | 1633.91 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 |
October | 1736.93 | 30-OCT-16:01 | 777.60 | 134.56 | 990.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 |
November | 1654.37 | 02-NOV-15:01 | 680.40 | 107.65 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 |
December | 1647.13 | 17-DEC-16:01 | 378.00 | 84.10 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1646.22 | 378.00 | 84.10 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1868.51 | 1800.00 | 1633.91 | 990.96 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 69.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22692.40 | 24-JAN-05:28 | 134943.84 | 3177.24 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.93 |
February | 19833.46 | 19-FEB-12:42 | 53977.54 | 3431.42 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.49 |
March | 27344.97 | 06-MAR-23:35 | 269887.68 | 9531.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.92 |
April | 29039.87 | 11-APR-22:30 | 80966.30 | 2859.51 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.50 |
May | 23812.23 | 15-MAY-01:08 | 161932.61 | 1906.34 | 13495.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.58 |
June | 22105.27 | 19-JUN-21:10 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.76 | 0.00 |
July | 22094.75 | 10-JUL-21:10 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 49.68 | 0.00 |
August | 22482.24 | 04-AUG-21:10 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 0.00 |
September | 21347.81 | 01-SEP-21:12 | 269887.68 | 19063.43 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 | 0.00 |
October | 29335.54 | 27-OCT-22:03 | 107955.07 | 3812.69 | 26991.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.48 |
November | 28984.53 | 05-NOV-22:01 | 167930.11 | 6672.20 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.00 |
December | 21308.08 | 25-DEC-10:17 | 44981.28 | 2096.98 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.69 |
Annual Sum or Average | |||||||||||
Minimum of Months | 19833.46 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29335.54 | 269887.68 | 19063.43 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 | 303.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25461.36 | 24-JAN-00:14 | 215910.14 | 5083.58 | 17994.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.67 |
February | 21413.34 | 19-FEB-12:42 | 53977.54 | 3431.42 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.44 |
March | 30554.64 | 06-MAR-23:35 | 269887.68 | 9531.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.46 |
April | 32095.73 | 11-APR-22:30 | 80966.30 | 2859.51 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.48 |
May | 25142.59 | 16-MAY-00:10 | 134943.84 | 2382.93 | 11246.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.18 |
June | 23874.29 | 19-JUN-21:10 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 75.75 | 0.00 |
July | 23704.85 | 07-JUL-22:00 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 0.00 |
August | 24084.30 | 04-AUG-21:10 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 0.00 |
September | 24110.43 | 24-SEP-05:03 | 146938.85 | 6672.20 | 39362.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.30 |
October | 31257.62 | 27-OCT-22:40 | 161932.61 | 5719.03 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.31 |
November | 27966.27 | 05-NOV-22:10 | 167930.11 | 6672.20 | 47235.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.81 |
December | 24983.20 | 17-DEC-19:37 | 53977.54 | 6672.20 | 20243.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.10 |
Annual Sum or Average | |||||||||||
Minimum of Months | 21413.34 | 26988.77 | 1906.34 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32095.73 | 269887.68 | 9531.72 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 120.84 | 302.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31276.97 | 19-JAN-15:20 | 4803.41 | 2018.21 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 0.00 | 222.01 |
February | 30112.35 | 20-FEB-14:30 | 1601.14 | 807.28 | 44738.57 | 33739.25 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 |
March | 33178.69 | 11-MAR-17:36 | 6671.40 | 1681.84 | 74564.28 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 253.03 |
April | 31396.56 | 02-APR-17:56 | 5337.12 | 3363.68 | 74564.28 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 290.62 |
May | 30364.15 | 01-MAY-06:24 | 10674.24 | 6727.36 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 234.02 |
June | 31323.73 | 01-JUN-18:05 | 11207.95 | 6458.26 | 89477.13 | 89971.33 | 0.00 | 0.00 | 0.00 | 51.12 | 0.00 |
July | 30600.22 | 08-JUL-10:50 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 98.36 | 0.00 |
August | 31567.53 | 25-AUG-17:04 | 6671.40 | 4036.41 | 74564.28 | 112464.16 | 0.00 | 0.00 | 0.00 | 32.10 | 0.00 |
September | 30279.22 | 04-SEP-10:40 | 1601.14 | 807.28 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 22.48 | 0.00 |
October | 34418.13 | 18-OCT-08:18 | 5337.12 | 5381.89 | 149128.56 | 112464.16 | 0.00 | 0.00 | 0.00 | 0.00 | 246.80 |
November | 33919.39 | 17-NOV-07:30 | 7471.97 | 4709.15 | 104389.99 | 78724.91 | 0.00 | 0.00 | 0.00 | 0.00 | 235.54 |
December | 36464.16 | 20-DEC-11:34 | 5337.12 | 3363.68 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 0.00 | 241.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 30112.35 | 800.57 | 336.37 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36464.16 | 11207.95 | 6727.36 | 149128.56 | 187440.26 | 0.00 | 0.00 | 0.00 | 98.36 | 290.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4665.77 | 19-JAN-15:20 | 0.00 | 2381.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.16 |
February | 5219.80 | 19-FEB-12:42 | 0.00 | 2857.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.39 |
March | 4872.60 | 11-MAR-17:36 | 0.00 | 1984.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.84 |
April | 4304.29 | 19-APR-17:15 | 0.00 | 1905.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.18 |
May | 4401.83 | 14-MAY-23:43 | 0.00 | 3334.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.88 |
June | 4407.28 | 19-JUN-14:40 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.62 | 0.00 |
July | 4544.17 | 10-JUL-14:00 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.23 | 0.00 |
August | 4637.62 | 24-AUG-19:00 | 0.00 | 1270.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 0.00 |
September | 4384.58 | 01-SEP-13:50 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.04 | 0.00 |
October | 4840.73 | 08-OCT-22:00 | 0.00 | 4763.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.04 |
November | 4552.35 | 06-NOV-10:00 | 0.00 | 3810.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.22 |
December | 4905.01 | 16-DEC-12:14 | 0.00 | 3969.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4304.29 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5219.80 | 0.00 | 4763.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.62 | 228.04 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.422654E+12 | 283743.91 | 23-JAN-20:49 | 0.522025E+12 | 460517.77 | 14-JAN-17:19 |
February | 0.379919E+12 | 280543.40 | 23-FEB-20:00 | 0.472564E+12 | 444586.92 | 06-FEB-17:10 |
March | 0.420898E+12 | 300897.80 | 27-MAR-19:10 | 0.421393E+12 | 355398.15 | 01-MAR-18:00 |
April | 0.420371E+12 | 343916.18 | 07-APR-19:10 | 0.381607E+12 | 360767.86 | 14-APR-16:49 |
May | 0.478966E+12 | 363946.26 | 31-MAY-19:19 | 0.358598E+12 | 290921.12 | 01-MAY-19:49 |
June | 0.622850E+12 | 447322.26 | 19-JUN-19:30 | 0.330426E+12 | 282156.45 | 06-JUN-17:40 |
July | 0.740947E+12 | 467658.10 | 20-JUL-20:19 | 0.332356E+12 | 287320.95 | 11-JUL-17:40 |
August | 0.704297E+12 | 477311.61 | 04-AUG-19:10 | 0.328511E+12 | 287269.31 | 22-AUG-16:30 |
September | 0.567356E+12 | 404129.99 | 06-SEP-19:00 | 0.326122E+12 | 287215.28 | 26-SEP-17:10 |
October | 0.490286E+12 | 363320.82 | 05-OCT-19:10 | 0.359058E+12 | 368516.22 | 26-OCT-20:00 |
November | 0.412121E+12 | 295296.78 | 06-NOV-20:40 | 0.402740E+12 | 383003.54 | 12-NOV-18:40 |
December | 0.424038E+12 | 286804.25 | 04-DEC-20:49 | 0.452878E+12 | 410998.34 | 31-DEC-17:00 |
Annual Sum or Average | 0.608470E+13 | 0.468828E+13 | ||||
Minimum of Months | 0.379919E+12 | 280543.40 | 0.326122E+12 | 282156.45 | ||
Maximum of Months | 0.740947E+12 | 477311.61 | 0.522025E+12 | 460517.77 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.781580E+11 | 0.254534E+11 | 0.140828E+12 | 0.833671E+11 | 0.490837E+11 | 0.450738E+10 | 0.00 | 0.120836E+10 | 0.00 | 0.00 | 0.271631E+11 | 0.770514E+10 | 0.00 |
February | 0.702935E+11 | 0.213459E+11 | 0.127191E+12 | 0.752992E+11 | 0.439196E+11 | 0.417471E+10 | 0.00 | 0.144592E+10 | 0.00 | 0.00 | 0.246322E+11 | 0.696274E+10 | 0.00 |
March | 0.775808E+11 | 0.213741E+11 | 0.140892E+12 | 0.833704E+11 | 0.482087E+11 | 0.487299E+10 | 0.00 | 0.628031E+10 | 0.00 | 0.00 | 0.253939E+11 | 0.770481E+10 | 0.00 |
April | 0.746361E+11 | 0.184227E+11 | 0.136245E+12 | 0.806767E+11 | 0.466486E+11 | 0.536402E+10 | 0.00 | 0.278549E+11 | 0.00 | 0.00 | 0.179814E+11 | 0.746521E+10 | 0.00 |
May | 0.767244E+11 | 0.170316E+11 | 0.140860E+12 | 0.833677E+11 | 0.473045E+11 | 0.650667E+10 | 0.00 | 0.855470E+11 | 0.00 | 0.00 | 0.864895E+10 | 0.770516E+10 | 0.00 |
June | 0.741194E+11 | 0.154243E+11 | 0.136336E+12 | 0.806797E+11 | 0.454825E+11 | 0.716699E+10 | 0.00 | 0.233700E+12 | 0.00 | 0.00 | 0.173709E+11 | 0.745822E+10 | 0.00 |
July | 0.765483E+11 | 0.164112E+11 | 0.140770E+12 | 0.833640E+11 | 0.487306E+11 | 0.814010E+10 | 0.00 | 0.327900E+12 | 0.00 | 0.00 | 0.261122E+11 | 0.771400E+10 | 0.00 |
August | 0.769882E+11 | 0.181219E+11 | 0.140892E+12 | 0.833698E+11 | 0.491537E+11 | 0.780391E+10 | 0.00 | 0.292977E+12 | 0.00 | 0.00 | 0.220049E+11 | 0.770585E+10 | 0.00 |
September | 0.748362E+11 | 0.196916E+11 | 0.136245E+12 | 0.806769E+11 | 0.453130E+11 | 0.681429E+10 | 0.00 | 0.179275E+12 | 0.00 | 0.00 | 0.119321E+11 | 0.746604E+10 | 0.00 |
October | 0.777357E+11 | 0.226994E+11 | 0.140828E+12 | 0.833668E+11 | 0.485246E+11 | 0.638997E+10 | 0.00 | 0.833031E+11 | 0.00 | 0.00 | 0.144655E+11 | 0.770494E+10 | 0.00 |
November | 0.754866E+11 | 0.240341E+11 | 0.136330E+12 | 0.806787E+11 | 0.474015E+11 | 0.487723E+10 | 0.00 | 0.805555E+10 | 0.00 | 0.00 | 0.227556E+11 | 0.744930E+10 | 0.00 |
December | 0.780898E+11 | 0.259515E+11 | 0.140770E+12 | 0.833654E+11 | 0.486030E+11 | 0.468905E+10 | 0.00 | 0.254023E+10 | 0.00 | 0.00 | 0.271328E+11 | 0.771312E+10 | 0.00 |
Annual Sum or Average | 0.911197E+12 | 0.245962E+12 | 0.165819E+13 | 0.981582E+12 | 0.568374E+12 | 0.713073E+11 | 0.00 | 0.125009E+13 | 0.245594E+12 | 0.907545E+11 | |||
Minimum of Months | 0.702935E+11 | 0.154243E+11 | 0.127191E+12 | 0.752992E+11 | 0.439196E+11 | 0.417471E+10 | 0.00 | 0.120836E+10 | 0.00 | 0.00 | 0.864895E+10 | 0.696274E+10 | 0.00 |
Maximum of Months | 0.781580E+11 | 0.259515E+11 | 0.140892E+12 | 0.833704E+11 | 0.491537E+11 | 0.814010E+10 | 0.00 | 0.327900E+12 | 0.00 | 0.00 | 0.271631E+11 | 0.771400E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.177406E+12 | 0.00 | 0.192700E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.159950E+12 | 0.00 | 0.175411E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.771297E+11 | 0.00 | 0.192225E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.542046E+11 | 0.00 | 0.180447E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.270118E+11 | 0.00 | 0.179608E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.158804E+11 | 0.00 | 0.167432E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.120009E+11 | 0.00 | 0.168535E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.906389E+10 | 0.00 | 0.167408E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.148822E+11 | 0.00 | 0.164284E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.320309E+11 | 0.00 | 0.175109E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.798406E+11 | 0.00 | 0.175808E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.112486E+12 | 0.00 | 0.188571E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.771887E+12 | 0.212754E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.906389E+10 | 0.00 | 0.164284E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.177406E+12 | 0.00 | 0.192700E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 83314.66 | 02-JAN-20:10 | 15665.55 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 63148.86 | 02-JAN-07:19 | 27445.62 | 18-JAN-19:00 | 3778.37 | 19-JAN-16:10 | 0.00 | 01-JAN-00:10 |
February | 83314.66 | 01-FEB-20:10 | 15665.55 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 63148.86 | 01-FEB-07:19 | 26496.47 | 06-FEB-19:10 | 3977.70 | 06-FEB-09:00 | 0.00 | 01-FEB-00:10 |
March | 83314.66 | 01-MAR-20:10 | 15665.55 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 63148.86 | 13-MAR-06:19 | 31296.20 | 28-MAR-20:30 | 3473.33 | 06-MAR-23:00 | 0.00 | 01-MAR-00:10 |
April | 83314.66 | 03-APR-19:10 | 15665.55 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 63147.71 | 14-APR-06:19 | 30782.77 | 11-APR-20:00 | 3596.31 | 05-APR-06:00 | 0.00 | 01-APR-00:10 |
May | 83314.66 | 01-MAY-19:10 | 15665.55 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 63147.71 | 04-MAY-06:19 | 29583.36 | 01-MAY-21:30 | 3523.07 | 01-MAY-00:40 | 0.00 | 01-MAY-00:10 |
June | 83314.66 | 01-JUN-19:19 | 15665.55 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 63146.84 | 21-JUN-06:19 | 29358.63 | 01-JUN-19:19 | 4042.18 | 24-JUN-21:19 | 0.00 | 01-JUN-00:10 |
July | 83314.66 | 03-JUL-19:30 | 15665.55 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 63147.10 | 24-JUL-06:19 | 28927.90 | 11-JUL-18:19 | 4195.06 | 20-JUL-20:40 | 0.00 | 01-JUL-00:10 |
August | 83314.66 | 01-AUG-19:10 | 15665.55 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 63146.84 | 07-AUG-06:19 | 31992.22 | 24-AUG-20:19 | 4094.69 | 16-AUG-21:30 | 0.00 | 01-AUG-00:10 |
September | 83314.66 | 01-SEP-19:10 | 15665.55 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 63148.46 | 27-SEP-06:19 | 26555.35 | 07-SEP-21:30 | 3792.92 | 07-SEP-21:49 | 0.00 | 01-SEP-00:10 |
October | 83314.66 | 02-OCT-19:10 | 15665.55 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 63148.86 | 10-OCT-06:19 | 42141.70 | 08-OCT-21:10 | 3611.56 | 10-OCT-05:40 | 0.00 | 01-OCT-00:10 |
November | 83314.66 | 01-NOV-19:10 | 15665.55 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 63148.86 | 01-NOV-06:19 | 38558.13 | 06-NOV-21:00 | 3742.65 | 17-NOV-17:49 | 0.00 | 01-NOV-00:10 |
December | 83314.66 | 01-DEC-20:10 | 15665.55 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 63148.86 | 01-DEC-07:19 | 28834.01 | 04-DEC-20:49 | 3601.84 | 12-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 83314.66 | 15665.55 | 89171.45 | 63146.84 | 26496.47 | 3473.33 | 0.00 | |||||||
Maximum of Months | 83314.66 | 15665.55 | 89171.45 | 63148.86 | 42141.70 | 4195.06 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 5360.83 | 17-JAN-16:10 | 0.00 | 0.00 | 10206.30 | 01-JAN-09:09 | 4738.27 | 27-JAN-19:10 | 0.00 |
February | 8016.13 | 03-FEB-12:39 | 0.00 | 0.00 | 10206.30 | 01-FEB-09:09 | 4738.35 | 13-FEB-19:10 | 0.00 |
March | 74328.24 | 27-MAR-12:00 | 0.00 | 0.00 | 10206.30 | 01-MAR-09:09 | 4738.32 | 08-MAR-19:10 | 0.00 |
April | 100760.66 | 07-APR-15:09 | 0.00 | 0.00 | 10206.30 | 01-APR-15:09 | 4738.44 | 24-APR-06:00 | 0.00 |
May | 125875.34 | 31-MAY-15:09 | 0.00 | 0.00 | 10206.30 | 01-MAY-07:10 | 4738.63 | 12-MAY-18:00 | 0.00 |
June | 183209.24 | 19-JUN-18:10 | 0.00 | 0.00 | 10206.30 | 01-JUN-15:09 | 4738.43 | 19-JUN-06:00 | 0.00 |
July | 202385.68 | 20-JUL-20:19 | 0.00 | 0.00 | 10206.30 | 01-JUL-15:09 | 4738.51 | 06-JUL-06:10 | 0.00 |
August | 197982.83 | 03-AUG-21:19 | 0.00 | 0.00 | 10206.30 | 01-AUG-10:09 | 4738.30 | 28-AUG-06:00 | 0.00 |
September | 161664.03 | 07-SEP-21:49 | 0.00 | 0.00 | 10206.30 | 01-SEP-10:09 | 4738.32 | 11-SEP-06:30 | 0.00 |
October | 122121.18 | 05-OCT-15:09 | 0.00 | 0.00 | 10206.30 | 02-OCT-15:09 | 4738.32 | 12-OCT-18:10 | 0.00 |
November | 55489.65 | 10-NOV-09:00 | 0.00 | 0.00 | 10206.30 | 01-NOV-22:40 | 4738.33 | 17-NOV-07:30 | 0.00 |
December | 13738.12 | 18-DEC-10:00 | 0.00 | 0.00 | 10206.30 | 01-DEC-09:09 | 4738.32 | 28-DEC-19:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 5360.83 | 0.00 | 0.00 | 10206.30 | 4738.27 | 0.00 | |||
Maximum of Months | 202385.68 | 0.00 | 0.00 | 10206.30 | 4738.63 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 283743.91 | 23-JAN-20:49 | 83314.66 | 86439.81 | 15665.55 | 50840.12 | 25547.77 | 2795.94 | 0.00 | 2391.14 | 0.00 |
February | 280543.40 | 23-FEB-20:00 | 83314.66 | 86439.81 | 15665.55 | 50840.12 | 23224.25 | 2732.38 | 0.00 | 1822.84 | 0.00 |
March | 300897.80 | 27-MAR-19:10 | 83314.66 | 86439.81 | 15665.55 | 50829.12 | 19547.32 | 2366.02 | 0.00 | 36612.47 | 0.00 |
April | 343916.18 | 07-APR-19:10 | 83314.66 | 86439.81 | 15665.55 | 50829.12 | 19279.82 | 2567.99 | 0.00 | 80218.63 | 0.00 |
May | 363946.26 | 31-MAY-19:19 | 83314.66 | 86439.81 | 15665.55 | 50838.52 | 20148.98 | 2634.72 | 0.00 | 89718.76 | 0.00 |
June | 447322.26 | 19-JUN-19:30 | 83314.66 | 86439.81 | 15665.55 | 50840.12 | 26232.48 | 3495.99 | 0.00 | 164915.28 | 0.00 |
July | 467658.10 | 20-JUL-20:19 | 74006.85 | 88218.55 | 15665.55 | 38629.77 | 28222.58 | 4137.46 | 0.00 | 202385.68 | 0.00 |
August | 477311.61 | 04-AUG-19:10 | 83314.66 | 86439.81 | 15665.55 | 50828.50 | 26085.37 | 3800.76 | 0.00 | 195571.72 | 0.00 |
September | 404129.99 | 06-SEP-19:00 | 83314.66 | 86439.81 | 15665.55 | 50840.12 | 20113.43 | 3129.64 | 0.00 | 129535.03 | 0.00 |
October | 363320.82 | 05-OCT-19:10 | 83314.66 | 86439.81 | 15665.55 | 50829.12 | 19527.35 | 2626.17 | 0.00 | 90229.48 | 0.00 |
November | 295296.78 | 06-NOV-20:40 | 83314.66 | 86439.81 | 15665.55 | 50840.12 | 32142.64 | 2682.92 | 0.00 | 7781.50 | 0.00 |
December | 286804.25 | 04-DEC-20:49 | 83314.66 | 86439.81 | 15665.55 | 50840.12 | 28834.01 | 2792.85 | 0.00 | 2279.43 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 280543.40 | 74006.85 | 86439.81 | 15665.55 | 38629.77 | 19279.82 | 2366.02 | 0.00 | 1822.84 | 0.00 | |
Maximum of Months | 477311.61 | 83314.66 | 88218.55 | 15665.55 | 50840.12 | 32142.64 | 4137.46 | 0.00 | 202385.68 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 236840.16 | 14-JAN-16:19 | 0.00 | 182091.30 | 24-JAN-18:30 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 232828.34 | 06-FEB-09:09 | 0.00 | 180324.15 | 14-FEB-21:40 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 130678.02 | 17-MAR-08:09 | 0.00 | 184164.32 | 03-MAR-21:00 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 140846.72 | 05-APR-06:00 | 0.00 | 182132.55 | 04-APR-17:40 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 106593.16 | 01-MAY-00:40 | 0.00 | 178435.99 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 42048.90 | 10-JUN-10:30 | 0.00 | 177368.78 | 01-JUN-20:30 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 21167.41 | 19-JUL-01:19 | 0.00 | 176446.22 | 03-JUL-20:30 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 43910.20 | 30-AUG-15:50 | 0.00 | 176191.57 | 31-AUG-20:40 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 72249.44 | 24-SEP-05:30 | 0.00 | 176719.59 | 29-SEP-20:40 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 128296.81 | 28-OCT-21:10 | 0.00 | 179666.44 | 30-OCT-20:00 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 141737.31 | 05-NOV-21:19 | 0.00 | 181009.12 | 17-NOV-18:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 178283.32 | 31-DEC-23:00 | 0.00 | 181909.78 | 19-DEC-18:19 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 21167.41 | 0.00 | 176191.57 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 236840.16 | 0.00 | 184164.32 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 24.84 | 12.00 | 24.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.60 | 4.50 | 24.60 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 24.88 | 22.33 | 24.88 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 25.08 | 34.33 | 25.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.14 | 2.83 | 25.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 25.08 | 14.67 | 25.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 25.11 | 23.17 | 25.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 24.88 | 12.50 | 24.88 |
Annual Sum or Average | 0.00 | 0.00 | 126.33 | 24.99 | 126.33 | 24.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 25.14 | 34.33 | 25.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.41 | 0.33 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.87 | 0.83 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.92 | 2.33 | 21.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.92 | 5.50 | 21.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.88 | 5.17 | 21.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.92 | 1.33 | 21.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.46 | 0.50 | 20.46 | 15.17 | 21.90 | 15.17 | 21.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.55 | 0.33 | 20.55 | 5.50 | 21.92 | 5.50 | 21.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.48 | 1.00 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.67 | 20.49 | 0.67 | 20.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 21.94 | 2.17 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 21.90 | 5.50 | 21.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 21.84 | 4.33 | 21.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.84 | 1.17 | 21.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 20.48 | 1.67 | 20.48 | 13.83 | 21.88 | 13.83 | 21.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 20.49 | 1.00 | 20.49 | 5.50 | 21.94 | 5.50 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.18 | 2.00 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.33 | 20.27 | 2.33 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.88 | 1.17 | 21.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 21.98 | 8.33 | 21.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 22.06 | 21.00 | 22.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 21.99 | 11.00 | 21.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.98 | 3.17 | 21.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.52 | 0.50 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.45 | 0.67 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.50 | 20.28 | 5.50 | 20.28 | 44.67 | 22.02 | 44.67 | 22.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 20.52 | 2.33 | 20.52 | 21.00 | 22.06 | 21.00 | 22.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 20.45 | 0.67 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.53 | 0.17 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.81 | 0.33 | 21.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.24 | 2.67 | 22.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 22.24 | 4.50 | 22.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 22.12 | 10.83 | 22.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 22.21 | 10.83 | 22.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.20 | 4.00 | 22.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.77 | 0.67 | 21.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 20.46 | 0.83 | 20.46 | 33.83 | 22.17 | 33.83 | 22.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.53 | 0.67 | 20.53 | 10.83 | 22.24 | 10.83 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.48 | 1.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.00 | 20.52 | 1.00 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.76 | 0.33 | 21.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 22.24 | 2.67 | 22.24 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 22.21 | 4.83 | 22.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 22.14 | 10.50 | 22.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 22.24 | 9.33 | 22.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.20 | 3.33 | 22.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.68 | 0.33 | 21.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 20.54 | 0.17 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 20.50 | 2.67 | 20.50 | 31.33 | 22.18 | 31.33 | 22.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.54 | 1.50 | 20.54 | 10.50 | 22.24 | 10.50 | 22.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.42 | 0.50 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.78 | 0.50 | 21.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.00 | 2.83 | 22.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.05 | 5.83 | 22.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 22.04 | 9.33 | 22.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 22.02 | 9.33 | 22.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 22.00 | 4.00 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.74 | 0.83 | 21.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.50 | 20.42 | 0.50 | 20.42 | 32.67 | 22.01 | 32.67 | 22.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 20.42 | 0.50 | 20.42 | 9.33 | 22.05 | 9.33 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.48 | 1.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.83 | 20.48 | 0.83 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.03 | 2.33 | 22.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 22.04 | 6.00 | 22.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 22.05 | 9.00 | 22.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 21.99 | 8.00 | 21.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 22.00 | 2.33 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 20.48 | 2.33 | 20.48 | 27.83 | 22.02 | 27.83 | 22.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.48 | 1.50 | 20.48 | 9.00 | 22.05 | 9.00 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 20.44 | 0.83 | 20.44 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 20.55 | 0.17 | 20.55 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.89 | 0.33 | 21.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.86 | 1.00 | 21.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 21.94 | 5.67 | 21.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 22.05 | 14.17 | 22.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 22.00 | 12.67 | 22.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 21.99 | 8.17 | 21.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 21.85 | 3.17 | 21.85 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.79 | 0.33 | 21.79 |
December | 0.33 | 20.54 | 0.33 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 20.48 | 1.33 | 20.48 | 45.50 | 21.99 | 45.50 | 21.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 20.55 | 0.83 | 20.55 | 14.17 | 22.05 | 14.17 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.77 | 0.50 | 24.77 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.71 | 0.67 | 24.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.78 | 0.83 | 24.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.64 | 0.50 | 24.64 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 24.73 | 2.50 | 24.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.78 | 0.83 | 24.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.90 | 0.50 | 24.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.78 | 1.00 | 24.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.78 | 1.33 | 24.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.70 | 1.00 | 24.70 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 24.77 | 4.00 | 24.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.90 | 1.33 | 24.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 24.96 | 30.33 | 24.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 24.79 | 8.83 | 24.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 24.93 | 64.83 | 24.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 90.00 | 25.02 | 90.00 | 25.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 24.79 | 8.33 | 24.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.59 | 0.33 | 24.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.93 | 0.50 | 24.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | 25.11 | 53.83 | 25.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 72.17 | 25.01 | 72.17 | 25.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 24.99 | 31.00 | 24.99 |
Annual Sum or Average | 0.00 | 0.00 | 360.17 | 25.00 | 360.17 | 25.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 90.00 | 25.11 | 90.00 | 25.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 742.50 | 23.06 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 672.00 | 22.65 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 744.00 | 22.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.40 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.27 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.60 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 22.24 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 619.00 | 23.25 | 5.33 | 23.94 | 0.00 | 0.00 |
November | 532.00 | 23.70 | 4.67 | 23.98 | 0.00 | 0.00 |
December | 731.00 | 23.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8432.50 | 22.31 | 10.00 | 23.96 | 0.00 | |
Minimum of Months | 532.00 | 21.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 23.70 | 5.33 | 23.98 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 732.17 | 21.10 | 337.17 | 21.02 | 334.83 | 21.00 |
February | 654.33 | 21.14 | 309.33 | 21.00 | 309.33 | 21.00 |
March | 714.33 | 21.19 | 103.00 | 21.17 | 97.33 | 21.00 |
April | 707.67 | 21.21 | 21.50 | 21.86 | 14.67 | 21.00 |
May | 744.00 | 21.20 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 707.33 | 21.41 | 3.33 | 23.25 | 0.00 | 0.00 |
July | 661.17 | 21.71 | 20.50 | 23.18 | 0.00 | 0.00 |
August | 511.67 | 21.78 | 115.67 | 23.50 | 0.00 | 0.00 |
September | 602.50 | 21.47 | 67.17 | 23.76 | 0.00 | 0.00 |
October | 586.33 | 21.58 | 101.00 | 23.83 | 0.00 | 0.00 |
November | 682.83 | 21.20 | 92.17 | 21.39 | 80.00 | 21.00 |
December | 714.33 | 21.13 | 278.00 | 21.07 | 271.33 | 21.00 |
Annual Sum or Average | 8018.67 | 21.33 | 1448.83 | 21.63 | 1107.50 | 21.00 |
Minimum of Months | 511.67 | 21.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.78 | 337.17 | 23.83 | 334.83 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.50 | 24.33 | 21.00 | 24.33 | 21.00 |
February | 672.00 | 21.55 | 22.67 | 21.00 | 22.67 | 21.00 |
March | 744.00 | 21.94 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.98 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 712.33 | 21.95 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 712.83 | 22.08 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 674.50 | 22.26 | 10.33 | 23.70 | 0.00 | 0.00 |
September | 700.17 | 22.08 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 704.17 | 22.47 | 3.50 | 23.66 | 0.00 | 0.00 |
November | 719.00 | 22.04 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 21.74 | 1.00 | 21.00 | 1.00 | 21.00 |
Annual Sum or Average | 8591.00 | 21.97 | 61.83 | 21.60 | 48.00 | 21.00 |
Minimum of Months | 672.00 | 21.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.47 | 24.33 | 23.70 | 24.33 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 330.67 | 22.49 | 384.67 | 23.54 | 138.83 | 24.18 |
February | 287.33 | 22.42 | 305.33 | 23.68 | 115.67 | 24.14 |
March | 277.33 | 22.85 | 438.00 | 23.46 | 155.50 | 24.21 |
April | 268.50 | 22.98 | 448.67 | 23.30 | 162.00 | 24.24 |
May | 276.50 | 22.87 | 424.67 | 22.96 | 173.50 | 23.96 |
June | 205.50 | 23.11 | 420.00 | 22.48 | 149.17 | 23.91 |
July | 183.17 | 23.36 | 513.00 | 22.17 | 149.00 | 23.90 |
August | 186.67 | 23.39 | 538.00 | 22.17 | 154.83 | 23.89 |
September | 221.33 | 23.01 | 415.17 | 22.62 | 151.67 | 23.92 |
October | 253.33 | 23.14 | 489.00 | 22.96 | 175.83 | 24.04 |
November | 259.33 | 22.97 | 431.17 | 23.45 | 155.00 | 24.22 |
December | 272.83 | 22.66 | 384.00 | 23.59 | 135.83 | 24.19 |
Annual Sum or Average | 3022.50 | 22.90 | 5191.67 | 22.98 | 1816.83 | 24.06 |
Minimum of Months | 183.17 | 22.42 | 305.33 | 22.17 | 115.67 | 23.89 |
Maximum of Months | 330.67 | 23.39 | 538.00 | 23.68 | 175.83 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 717.33 | 21.50 | 95.67 | 21.26 | 87.50 | 21.00 |
February | 636.00 | 21.60 | 68.33 | 21.46 | 57.67 | 21.00 |
March | 685.33 | 21.97 | 25.50 | 23.91 | 0.00 | 0.00 |
April | 664.33 | 22.09 | 19.50 | 23.47 | 0.00 | 0.00 |
May | 699.50 | 22.13 | 26.33 | 23.04 | 18.33 | 22.89 |
June | 517.33 | 22.02 | 68.83 | 23.35 | 3.17 | 22.90 |
July | 336.67 | 22.07 | 238.67 | 23.33 | 0.00 | 0.00 |
August | 186.83 | 22.10 | 402.50 | 23.40 | 2.17 | 23.82 |
September | 369.67 | 22.12 | 223.83 | 23.48 | 7.67 | 22.92 |
October | 374.33 | 22.68 | 301.33 | 23.68 | 46.00 | 23.53 |
November | 628.17 | 21.99 | 44.33 | 23.82 | 1.67 | 22.68 |
December | 697.67 | 21.72 | 41.00 | 22.88 | 15.33 | 21.00 |
Annual Sum or Average | 6513.17 | 21.95 | 1555.83 | 23.24 | 239.50 | 21.76 |
Minimum of Months | 186.83 | 21.50 | 19.50 | 21.26 | 0.00 | 0.00 |
Maximum of Months | 717.33 | 22.68 | 402.50 | 23.91 | 87.50 | 23.82 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.00 | 4.83 | 21.00 | 4.83 | 21.00 |
February | 672.00 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 729.33 | 22.41 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 679.00 | 22.44 | 0.83 | 23.65 | 0.00 | 0.00 |
May | 688.50 | 22.30 | 4.50 | 23.60 | 0.00 | 0.00 |
June | 638.67 | 22.17 | 9.67 | 23.58 | 0.00 | 0.00 |
July | 579.33 | 22.21 | 49.83 | 23.59 | 0.00 | 0.00 |
August | 517.83 | 22.33 | 84.17 | 23.64 | 0.00 | 0.00 |
September | 602.67 | 22.33 | 31.00 | 23.63 | 0.00 | 0.00 |
October | 540.83 | 22.79 | 80.17 | 23.70 | 0.67 | 23.63 |
November | 673.17 | 22.52 | 6.83 | 23.88 | 0.00 | 0.00 |
December | 742.83 | 22.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7808.17 | 22.31 | 271.83 | 23.60 | 5.50 | 21.32 |
Minimum of Months | 517.83 | 22.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.79 | 84.17 | 23.88 | 4.83 | 23.63 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.72 | 591.33 | 20.60 | 591.33 | 20.60 |
February | 672.00 | 20.83 | 538.00 | 20.71 | 538.00 | 20.71 |
March | 741.33 | 21.07 | 256.83 | 20.69 | 254.67 | 20.65 |
April | 685.67 | 21.23 | 88.67 | 21.27 | 72.33 | 20.44 |
May | 668.83 | 21.60 | 48.50 | 25.31 | 3.67 | 25.74 |
June | 565.67 | 22.12 | 162.17 | 24.67 | 83.83 | 24.41 |
July | 567.00 | 22.25 | 206.33 | 24.45 | 136.67 | 24.49 |
August | 537.83 | 21.99 | 165.33 | 24.76 | 66.83 | 24.82 |
September | 579.50 | 21.88 | 109.00 | 24.70 | 44.17 | 24.34 |
October | 655.50 | 21.57 | 65.17 | 23.33 | 23.83 | 21.78 |
November | 720.00 | 21.02 | 268.83 | 20.68 | 268.83 | 20.68 |
December | 744.00 | 20.82 | 562.33 | 20.69 | 562.33 | 20.69 |
Annual Sum or Average | 7881.33 | 21.37 | 3062.50 | 21.65 | 2646.50 | 21.16 |
Minimum of Months | 537.83 | 20.72 | 48.50 | 20.60 | 3.67 | 20.44 |
Maximum of Months | 744.00 | 22.25 | 591.33 | 25.31 | 591.33 | 25.74 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 671.17 | 20.50 | 671.17 | 20.50 |
February | 672.00 | 20.60 | 637.50 | 20.57 | 637.50 | 20.57 |
March | 741.83 | 20.86 | 354.50 | 20.55 | 352.67 | 20.53 |
April | 695.33 | 21.15 | 113.67 | 20.85 | 103.33 | 20.45 |
May | 675.17 | 21.57 | 46.17 | 25.26 | 3.67 | 25.68 |
June | 569.50 | 22.10 | 158.50 | 24.66 | 80.50 | 24.32 |
July | 574.17 | 22.24 | 203.67 | 24.43 | 136.50 | 24.43 |
August | 565.83 | 22.00 | 159.50 | 24.65 | 65.17 | 24.59 |
September | 625.50 | 21.85 | 88.00 | 24.56 | 42.00 | 24.03 |
October | 703.67 | 21.42 | 78.67 | 21.70 | 62.50 | 21.03 |
November | 720.00 | 20.79 | 362.67 | 20.51 | 362.67 | 20.51 |
December | 744.00 | 20.59 | 698.33 | 20.56 | 698.33 | 20.56 |
Annual Sum or Average | 8031.00 | 21.26 | 3572.33 | 21.32 | 3216.00 | 20.94 |
Minimum of Months | 565.83 | 20.56 | 46.17 | 20.50 | 3.67 | 20.45 |
Maximum of Months | 744.00 | 22.24 | 698.33 | 25.26 | 698.33 | 25.68 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.79 | 471.00 | 20.63 | 471.00 | 20.63 |
February | 672.00 | 20.78 | 504.50 | 20.68 | 504.50 | 20.68 |
March | 744.00 | 21.00 | 185.17 | 20.70 | 185.17 | 20.70 |
April | 720.00 | 21.20 | 19.67 | 20.76 | 19.67 | 20.76 |
May | 733.33 | 21.53 | 5.50 | 24.09 | 0.00 | 0.00 |
June | 705.67 | 22.04 | 92.33 | 23.47 | 85.17 | 23.41 |
July | 715.17 | 22.27 | 150.83 | 23.85 | 137.83 | 23.81 |
August | 704.17 | 22.06 | 73.00 | 23.76 | 60.17 | 23.72 |
September | 708.83 | 21.80 | 41.50 | 23.44 | 40.17 | 23.43 |
October | 744.00 | 21.31 | 11.00 | 21.69 | 11.00 | 21.69 |
November | 720.00 | 21.00 | 159.17 | 20.67 | 159.17 | 20.67 |
December | 744.00 | 20.84 | 414.67 | 20.64 | 414.67 | 20.64 |
Annual Sum or Average | 8655.17 | 21.38 | 2128.33 | 21.18 | 2088.50 | 21.12 |
Minimum of Months | 672.00 | 20.78 | 5.50 | 20.63 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.27 | 504.50 | 24.09 | 504.50 | 23.81 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.72 | 580.50 | 20.61 | 580.50 | 20.61 |
February | 672.00 | 20.84 | 523.17 | 20.73 | 523.17 | 20.73 |
March | 744.00 | 21.11 | 248.17 | 20.69 | 248.17 | 20.69 |
April | 707.17 | 21.35 | 71.33 | 20.49 | 70.50 | 20.45 |
May | 694.83 | 21.72 | 26.67 | 24.72 | 3.50 | 25.37 |
June | 587.83 | 22.10 | 130.33 | 23.89 | 96.33 | 23.66 |
July | 548.33 | 22.20 | 190.50 | 24.30 | 146.33 | 24.27 |
August | 491.17 | 21.86 | 155.83 | 24.50 | 63.00 | 24.53 |
September | 611.50 | 21.96 | 81.00 | 24.11 | 47.00 | 23.87 |
October | 688.67 | 21.65 | 26.17 | 22.16 | 21.67 | 21.87 |
November | 720.00 | 21.06 | 243.50 | 20.67 | 243.50 | 20.67 |
December | 744.00 | 20.82 | 547.83 | 20.69 | 547.83 | 20.69 |
Annual Sum or Average | 7953.50 | 21.40 | 2825.00 | 21.43 | 2591.50 | 21.15 |
Minimum of Months | 491.17 | 20.72 | 26.17 | 20.49 | 3.50 | 20.45 |
Maximum of Months | 744.00 | 22.20 | 580.50 | 24.72 | 580.50 | 25.37 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 661.83 | 20.50 | 661.83 | 20.50 |
February | 672.00 | 20.61 | 630.00 | 20.57 | 630.00 | 20.57 |
March | 744.00 | 20.89 | 337.50 | 20.62 | 337.50 | 20.62 |
April | 717.50 | 21.27 | 98.17 | 20.55 | 97.50 | 20.53 |
May | 695.83 | 21.69 | 26.00 | 24.71 | 3.50 | 25.38 |
June | 602.33 | 22.12 | 127.33 | 23.89 | 93.00 | 23.65 |
July | 551.17 | 22.19 | 189.50 | 24.26 | 144.67 | 24.23 |
August | 524.67 | 21.92 | 135.83 | 24.39 | 61.67 | 24.42 |
September | 650.00 | 21.92 | 71.83 | 23.91 | 46.00 | 23.68 |
October | 741.67 | 21.47 | 59.83 | 21.22 | 58.50 | 21.18 |
November | 720.00 | 20.83 | 327.50 | 20.53 | 327.50 | 20.53 |
December | 744.00 | 20.60 | 678.67 | 20.55 | 678.67 | 20.55 |
Annual Sum or Average | 8107.17 | 21.29 | 3344.00 | 21.16 | 3140.33 | 20.95 |
Minimum of Months | 524.67 | 20.56 | 26.00 | 20.50 | 3.50 | 20.50 |
Maximum of Months | 744.00 | 22.19 | 678.67 | 24.71 | 678.67 | 25.38 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.65 | 660.33 | 20.58 | 660.33 | 20.58 |
February | 672.00 | 20.76 | 593.33 | 20.67 | 593.33 | 20.67 |
March | 740.33 | 21.02 | 317.00 | 20.67 | 313.83 | 20.62 |
April | 678.67 | 21.22 | 158.83 | 21.39 | 134.33 | 20.73 |
May | 648.83 | 21.71 | 72.33 | 25.64 | 21.67 | 26.60 |
June | 540.50 | 22.47 | 212.33 | 25.05 | 124.00 | 25.50 |
July | 549.83 | 22.52 | 264.83 | 24.69 | 157.17 | 25.29 |
August | 520.50 | 22.27 | 229.17 | 24.86 | 94.33 | 25.96 |
September | 544.83 | 22.01 | 165.17 | 24.97 | 63.33 | 25.49 |
October | 625.17 | 21.53 | 133.50 | 22.96 | 69.33 | 21.65 |
November | 720.00 | 20.96 | 350.17 | 20.63 | 350.17 | 20.63 |
December | 744.00 | 20.74 | 633.17 | 20.65 | 633.17 | 20.65 |
Annual Sum or Average | 7728.67 | 21.41 | 3790.17 | 21.82 | 3215.00 | 21.36 |
Minimum of Months | 520.50 | 20.65 | 72.33 | 20.58 | 21.67 | 20.58 |
Maximum of Months | 744.00 | 22.52 | 660.33 | 25.64 | 660.33 | 26.60 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.51 | 707.83 | 20.49 | 707.83 | 20.49 |
February | 672.00 | 20.55 | 656.67 | 20.53 | 656.67 | 20.53 |
March | 741.17 | 20.81 | 422.17 | 20.54 | 419.83 | 20.52 |
April | 685.50 | 21.12 | 190.33 | 21.08 | 169.50 | 20.60 |
May | 654.33 | 21.68 | 71.50 | 25.54 | 20.83 | 26.11 |
June | 541.17 | 22.45 | 208.17 | 25.07 | 121.67 | 25.47 |
July | 552.50 | 22.52 | 253.50 | 24.72 | 159.17 | 25.24 |
August | 531.33 | 22.20 | 205.33 | 24.92 | 86.67 | 25.72 |
September | 575.50 | 21.93 | 131.00 | 24.94 | 56.00 | 24.99 |
October | 678.83 | 21.40 | 144.83 | 21.92 | 108.67 | 21.09 |
November | 720.00 | 20.73 | 444.50 | 20.51 | 444.50 | 20.51 |
December | 744.00 | 20.53 | 723.00 | 20.52 | 723.00 | 20.52 |
Annual Sum or Average | 7840.33 | 21.29 | 4158.83 | 21.52 | 3674.33 | 21.13 |
Minimum of Months | 531.33 | 20.51 | 71.50 | 20.49 | 20.83 | 20.49 |
Maximum of Months | 744.00 | 22.52 | 723.00 | 25.54 | 723.00 | 26.11 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.67 | 21.03 | 420.67 | 20.71 | 420.67 | 20.71 |
February | 672.00 | 21.22 | 357.33 | 20.82 | 357.33 | 20.82 |
March | 732.67 | 21.25 | 169.50 | 20.72 | 169.50 | 20.72 |
April | 696.67 | 21.36 | 52.83 | 20.99 | 47.00 | 20.51 |
May | 705.00 | 21.70 | 17.00 | 24.43 | 1.83 | 23.05 |
June | 598.17 | 22.11 | 125.00 | 23.89 | 108.17 | 23.80 |
July | 574.83 | 22.31 | 190.67 | 24.35 | 164.67 | 24.33 |
August | 518.67 | 21.93 | 149.67 | 24.59 | 70.17 | 24.45 |
September | 522.33 | 21.84 | 128.67 | 24.19 | 51.50 | 24.33 |
October | 591.00 | 21.53 | 92.83 | 23.56 | 19.67 | 23.01 |
November | 704.67 | 21.31 | 126.50 | 20.85 | 126.50 | 20.85 |
December | 737.00 | 21.13 | 367.33 | 20.76 | 367.33 | 20.76 |
Annual Sum or Average | 7792.67 | 21.52 | 2198.00 | 21.87 | 1904.33 | 21.50 |
Minimum of Months | 518.67 | 21.03 | 17.00 | 20.71 | 1.83 | 20.51 |
Maximum of Months | 739.67 | 22.31 | 420.67 | 24.59 | 420.67 | 24.45 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 570.33 | 22.96 | 15.00 | 24.01 | 0.00 | 0.00 |
February | 551.17 | 22.99 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 383.67 | 23.03 | 67.67 | 23.99 | 0.00 | 0.00 |
April | 257.00 | 22.90 | 206.83 | 23.94 | 2.17 | 23.99 |
May | 211.33 | 22.82 | 366.17 | 23.89 | 39.00 | 23.99 |
June | 138.17 | 22.95 | 499.50 | 23.78 | 50.83 | 23.98 |
July | 16.00 | 22.40 | 604.50 | 23.72 | 0.50 | 23.90 |
August | 47.67 | 22.85 | 574.00 | 23.76 | 12.50 | 23.99 |
September | 195.50 | 22.67 | 402.83 | 23.83 | 34.83 | 23.96 |
October | 325.50 | 23.00 | 264.50 | 23.88 | 65.67 | 23.97 |
November | 375.67 | 22.97 | 93.00 | 23.98 | 5.67 | 23.98 |
December | 511.50 | 23.02 | 8.50 | 24.00 | 0.00 | 0.00 |
Annual Sum or Average | 3583.50 | 22.95 | 3102.50 | 23.82 | 211.17 | 23.98 |
Minimum of Months | 16.00 | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 570.33 | 23.03 | 604.50 | 24.01 | 65.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 408.67 | 23.03 | 61.50 | 23.99 | 0.00 | 0.00 |
February | 423.17 | 23.10 | 15.83 | 23.99 | 0.00 | 0.00 |
March | 198.33 | 23.04 | 199.83 | 23.97 | 0.00 | 0.00 |
April | 101.83 | 23.01 | 347.00 | 23.93 | 0.50 | 24.00 |
May | 66.00 | 23.21 | 526.50 | 23.87 | 24.50 | 23.99 |
June | 31.00 | 23.17 | 607.17 | 23.74 | 14.50 | 23.99 |
July | 0.67 | 22.40 | 720.00 | 23.69 | 0.00 | 0.00 |
August | 1.50 | 23.99 | 683.50 | 23.72 | 1.50 | 23.99 |
September | 77.83 | 22.87 | 522.50 | 23.79 | 19.67 | 23.99 |
October | 153.50 | 23.18 | 363.67 | 23.85 | 44.83 | 23.99 |
November | 217.50 | 23.03 | 205.67 | 23.97 | 4.67 | 23.99 |
December | 340.17 | 23.04 | 48.50 | 23.99 | 0.00 | 0.00 |
Annual Sum or Average | 2020.17 | 23.06 | 4301.67 | 23.80 | 110.17 | 23.99 |
Minimum of Months | 0.67 | 22.40 | 15.83 | 23.69 | 0.00 | 0.00 |
Maximum of Months | 423.17 | 23.99 | 720.00 | 23.99 | 44.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 555.50 | 23.80 | 598.67 | 24.02 | 474.00 | 24.11 |
February | 513.17 | 23.71 | 530.33 | 24.01 | 425.33 | 24.07 |
March | 537.17 | 24.08 | 646.17 | 24.02 | 509.50 | 24.19 |
April | 515.83 | 24.21 | 666.33 | 23.97 | 513.33 | 24.22 |
May | 545.83 | 24.02 | 716.17 | 23.74 | 545.83 | 24.02 |
June | 532.33 | 23.98 | 682.83 | 23.58 | 531.83 | 23.98 |
July | 549.33 | 23.98 | 707.00 | 23.54 | 549.33 | 23.98 |
August | 549.67 | 23.98 | 716.17 | 23.54 | 549.67 | 23.98 |
September | 525.00 | 23.98 | 679.83 | 23.63 | 525.00 | 23.98 |
October | 535.67 | 24.12 | 703.33 | 23.84 | 534.17 | 24.13 |
November | 519.67 | 24.10 | 632.33 | 24.02 | 494.83 | 24.20 |
December | 544.67 | 23.90 | 608.17 | 24.02 | 486.33 | 24.12 |
Annual Sum or Average | 6423.83 | 23.99 | 7887.33 | 23.82 | 6139.17 | 24.08 |
Minimum of Months | 513.17 | 23.71 | 530.33 | 23.54 | 425.33 | 23.98 |
Maximum of Months | 555.50 | 24.21 | 716.17 | 24.02 | 549.67 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.06094 | 27.32737 | 0.02534 | 5.22613 |
February | 672.00000 | 22.64965 | 23.61030 | -0.1036 | 5.39616 |
March | 744.00000 | 22.34252 | 33.22151 | -0.1208 | 5.48556 |
April | 720.00000 | 21.94845 | 40.67339 | -0.1710 | 5.83212 |
May | 744.00000 | 21.40258 | 49.37439 | -1.4154 | 46.43001 |
June | 720.00000 | 21.22126 | 56.66219 | -1.4200 | 46.63185 |
July | 744.00000 | 21.27170 | 58.70275 | -1.3773 | 44.36115 |
August | 744.00000 | 21.60471 | 56.44747 | -1.2662 | 38.65873 |
September | 720.00000 | 22.23886 | 51.83232 | -1.0732 | 29.61105 |
October | 744.00000 | 23.32608 | 42.34317 | 0.20784 | 6.13149 |
November | 720.00000 | 23.74754 | 32.96859 | 0.24522 | 6.37826 |
December | 744.00000 | 23.55859 | 26.67556 | 0.14975 | 5.58659 |
Annual Sum or Average | 8760.00000 | 22.36289 | 41.75902 | -0.5292 | 20.58345 |
Minimum of Months | 672.00000 | 21.22126 | 23.61030 | -1.4200 | 5.22613 |
Maximum of Months | 744.00000 | 23.74754 | 58.70275 | 0.24522 | 46.63185 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.14206 | 28.40433 | -0.4862 | 10.75582 |
February | 672.00000 | 21.20949 | 23.61401 | -0.4719 | 10.65825 |
March | 744.00000 | 21.29303 | 33.61679 | -0.3488 | 8.57085 |
April | 720.00000 | 21.24796 | 40.93962 | -0.2902 | 7.49210 |
May | 744.00000 | 21.19523 | 49.11066 | -1.3577 | 43.55657 |
June | 720.00000 | 21.43594 | 56.96884 | -1.1654 | 34.24317 |
July | 744.00000 | 21.84871 | 59.47112 | -0.9788 | 26.25130 |
August | 744.00000 | 22.23268 | 55.91339 | -0.8550 | 22.32638 |
September | 720.00000 | 21.79345 | 53.23676 | -1.0616 | 31.16427 |
October | 744.00000 | 22.03133 | 44.53558 | 0.00553 | 7.17918 |
November | 720.00000 | 21.33382 | 36.02527 | -0.3172 | 8.31398 |
December | 744.00000 | 21.24104 | 28.33190 | -0.4304 | 9.96555 |
Annual Sum or Average | 8760.00000 | 21.50331 | 42.62248 | -0.6472 | 18.41538 |
Minimum of Months | 672.00000 | 21.14206 | 23.61401 | -1.3577 | 7.17918 |
Maximum of Months | 744.00000 | 22.23268 | 59.47112 | 0.00553 | 43.55657 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.49892 | 29.92060 | -0.3223 | 7.61449 |
February | 672.00000 | 21.54969 | 25.29322 | -0.3338 | 7.69336 |
March | 744.00000 | 21.93967 | 34.45099 | -0.1736 | 6.08423 |
April | 720.00000 | 22.05651 | 41.05175 | -0.0958 | 5.66696 |
May | 744.00000 | 21.98289 | 48.65005 | -1.1361 | 32.76319 |
June | 720.00000 | 21.96538 | 55.72000 | -1.0725 | 29.82578 |
July | 744.00000 | 22.13782 | 57.77841 | -0.9892 | 26.22725 |
August | 744.00000 | 22.37159 | 55.57769 | -0.9179 | 23.40673 |
September | 720.00000 | 22.11515 | 53.21544 | -1.0385 | 28.37875 |
October | 744.00000 | 22.52601 | 44.94952 | 0.06425 | 5.47013 |
November | 720.00000 | 22.04581 | 36.57170 | -0.1326 | 5.90948 |
December | 744.00000 | 21.73949 | 29.67018 | -0.2585 | 6.73022 |
Annual Sum or Average | 8760.00000 | 21.99716 | 42.83808 | -0.5350 | 15.52336 |
Minimum of Months | 672.00000 | 21.49892 | 25.29322 | -1.1361 | 5.47013 |
Maximum of Months | 744.00000 | 22.52601 | 57.77841 | 0.06425 | 32.76319 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.60858 | 24.51087 | 0.50363 | 13.72656 |
February | 672.00000 | 22.58194 | 20.28877 | 0.47240 | 13.01107 |
March | 744.00000 | 22.67540 | 29.29347 | 0.57900 | 15.45349 |
April | 720.00000 | 22.55982 | 36.18248 | 0.61273 | 16.40124 |
May | 744.00000 | 22.16245 | 44.21171 | -0.2055 | 13.21594 |
June | 720.00000 | 21.86963 | 51.65761 | -0.2282 | 13.27905 |
July | 744.00000 | 21.80933 | 54.11132 | -0.2180 | 12.90675 |
August | 744.00000 | 21.84898 | 52.71060 | -0.2029 | 12.94260 |
September | 720.00000 | 21.95027 | 49.53457 | -0.2233 | 13.12636 |
October | 744.00000 | 22.37092 | 41.41923 | 0.62347 | 16.60416 |
November | 720.00000 | 22.67571 | 31.55682 | 0.59629 | 15.85896 |
December | 744.00000 | 22.65896 | 24.50467 | 0.52674 | 14.02372 |
Annual Sum or Average | 8760.00000 | 22.31269 | 38.43739 | 0.23494 | 14.21739 |
Minimum of Months | 672.00000 | 21.80933 | 20.28877 | -0.2282 | 12.90675 |
Maximum of Months | 744.00000 | 22.67571 | 54.11132 | 0.62347 | 16.60416 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.57819 | 33.84752 | -0.2884 | 7.86316 |
February | 672.00000 | 21.71039 | 29.13387 | -0.2604 | 7.65551 |
March | 744.00000 | 22.10374 | 38.41702 | -0.0814 | 6.36443 |
April | 720.00000 | 22.18407 | 45.04840 | -0.0042 | 6.00409 |
May | 744.00000 | 22.19095 | 52.55370 | -0.9630 | 25.42281 |
June | 720.00000 | 22.32042 | 59.69052 | -0.8111 | 19.78904 |
July | 744.00000 | 22.63272 | 61.85896 | -0.6558 | 14.81616 |
August | 744.00000 | 22.95430 | 59.10802 | -0.5458 | 12.18610 |
September | 720.00000 | 22.69966 | 56.39597 | -0.6893 | 16.84535 |
October | 744.00000 | 23.12871 | 47.99376 | 0.32615 | 8.46808 |
November | 720.00000 | 22.20042 | 40.44713 | -0.0367 | 6.49010 |
December | 744.00000 | 21.85225 | 33.53558 | -0.1976 | 7.10686 |
Annual Sum or Average | 8760.00000 | 22.30053 | 46.60263 | -0.3510 | 11.60895 |
Minimum of Months | 672.00000 | 21.57819 | 29.13387 | -0.9630 | 6.00409 |
Maximum of Months | 744.00000 | 23.12871 | 61.85896 | 0.32615 | 25.42281 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.99753 | 32.26373 | -0.1751 | 6.30002 |
February | 672.00000 | 22.05921 | 27.74462 | -0.1819 | 6.24203 |
March | 744.00000 | 22.43823 | 36.73482 | -0.0232 | 5.61113 |
April | 720.00000 | 22.50753 | 43.22787 | 0.04463 | 5.67251 |
May | 744.00000 | 22.38707 | 50.75696 | -0.9572 | 25.34316 |
June | 720.00000 | 22.30000 | 57.96104 | -0.9096 | 23.36216 |
July | 744.00000 | 22.45373 | 60.14673 | -0.8277 | 20.22992 |
August | 744.00000 | 22.65060 | 58.03882 | -0.7675 | 18.16168 |
September | 720.00000 | 22.50919 | 55.31189 | -0.8538 | 21.21142 |
October | 744.00000 | 22.99241 | 47.04506 | 0.21903 | 6.42755 |
November | 720.00000 | 22.59681 | 38.67342 | 0.03300 | 5.71170 |
December | 744.00000 | 22.28291 | 31.95627 | -0.0985 | 5.76494 |
Annual Sum or Average | 8760.00000 | 22.43381 | 45.08847 | -0.3759 | 12.53836 |
Minimum of Months | 672.00000 | 21.99753 | 27.74462 | -0.9572 | 5.61113 |
Maximum of Months | 744.00000 | 22.99241 | 60.14673 | 0.21903 | 25.34316 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.72047 | 32.77293 | -0.6452 | 14.32603 |
February | 672.00000 | 20.82543 | 27.41554 | -0.6345 | 14.05085 |
March | 744.00000 | 21.08402 | 37.86811 | -0.4526 | 10.05841 |
April | 720.00000 | 21.37166 | 44.77603 | -0.3039 | 8.30644 |
May | 744.00000 | 21.89793 | 51.45165 | -1.1942 | 37.84837 |
June | 720.00000 | 22.55469 | 56.60786 | -0.8720 | 26.00183 |
July | 744.00000 | 22.59946 | 59.34435 | -0.8105 | 23.74764 |
August | 744.00000 | 22.53836 | 55.63369 | -0.8381 | 24.73969 |
September | 720.00000 | 22.31306 | 55.08540 | -0.9929 | 30.01201 |
October | 744.00000 | 21.83306 | 48.69492 | -0.1198 | 7.20198 |
November | 720.00000 | 21.02193 | 41.12945 | -0.4688 | 10.27747 |
December | 744.00000 | 20.81785 | 32.79188 | -0.6036 | 13.16502 |
Annual Sum or Average | 8760.00000 | 21.63610 | 45.39967 | -0.6616 | 18.34262 |
Minimum of Months | 672.00000 | 20.72047 | 27.41554 | -1.1942 | 7.20198 |
Maximum of Months | 744.00000 | 22.59946 | 59.34435 | -0.1198 | 37.84837 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55745 | 33.03546 | -0.7055 | 16.08302 |
February | 672.00000 | 20.59552 | 27.73258 | -0.7192 | 16.43155 |
March | 744.00000 | 20.86755 | 38.25532 | -0.5248 | 11.39799 |
April | 720.00000 | 21.25489 | 45.13821 | -0.3424 | 8.63344 |
May | 744.00000 | 21.85492 | 51.60041 | -1.2140 | 38.61845 |
June | 720.00000 | 22.54222 | 56.72272 | -0.8799 | 26.18846 |
July | 744.00000 | 22.58674 | 59.59536 | -0.8192 | 23.92630 |
August | 744.00000 | 22.48720 | 56.25253 | -0.8688 | 25.40861 |
September | 720.00000 | 22.16060 | 56.10202 | -1.0636 | 32.32321 |
October | 744.00000 | 21.54715 | 50.46231 | -0.2133 | 7.41861 |
November | 720.00000 | 20.79338 | 41.63006 | -0.5466 | 11.85546 |
December | 744.00000 | 20.59414 | 33.16241 | -0.6816 | 15.22428 |
Annual Sum or Average | 8760.00000 | 21.49194 | 45.91118 | -0.7149 | 19.48081 |
Minimum of Months | 672.00000 | 20.55745 | 27.73258 | -1.2140 | 7.41861 |
Maximum of Months | 744.00000 | 22.58674 | 59.59536 | -0.2133 | 38.61845 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.79123 | 31.38807 | -0.5902 | 12.76678 |
February | 672.00000 | 20.78201 | 26.25632 | -0.6239 | 13.55505 |
March | 744.00000 | 20.99590 | 36.68193 | -0.4766 | 9.98470 |
April | 720.00000 | 21.20492 | 43.54516 | -0.3547 | 7.88377 |
May | 744.00000 | 21.56623 | 49.71965 | -1.3447 | 43.14168 |
June | 720.00000 | 22.08230 | 57.15217 | -1.0902 | 31.74463 |
July | 744.00000 | 22.33693 | 60.23047 | -0.9735 | 27.57004 |
August | 744.00000 | 22.15947 | 56.73423 | -1.0616 | 30.63108 |
September | 720.00000 | 21.82749 | 54.95253 | -1.2149 | 37.12472 |
October | 744.00000 | 21.30969 | 49.10688 | -0.2858 | 7.15841 |
November | 720.00000 | 21.00186 | 39.74837 | -0.4566 | 9.66000 |
December | 744.00000 | 20.84099 | 31.51847 | -0.5701 | 12.06993 |
Annual Sum or Average | 8760.00000 | 21.41207 | 44.85999 | -0.7543 | 20.31489 |
Minimum of Months | 672.00000 | 20.78201 | 26.25632 | -1.3447 | 7.15841 |
Maximum of Months | 744.00000 | 22.33693 | 60.23047 | -0.2858 | 43.14168 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.72004 | 32.75676 | -0.6434 | 14.24985 |
February | 672.00000 | 20.84368 | 27.36932 | -0.6267 | 13.79659 |
March | 744.00000 | 21.11069 | 37.85526 | -0.4510 | 9.94102 |
April | 720.00000 | 21.38739 | 44.63286 | -0.2997 | 7.99901 |
May | 744.00000 | 21.87427 | 51.33908 | -1.1971 | 37.21349 |
June | 720.00000 | 22.38564 | 57.87868 | -0.9290 | 26.25772 |
July | 744.00000 | 22.55113 | 60.08763 | -0.8244 | 23.37670 |
August | 744.00000 | 22.49637 | 56.05357 | -0.8502 | 24.21601 |
September | 720.00000 | 22.22357 | 55.54613 | -1.0169 | 29.80244 |
October | 744.00000 | 21.77829 | 48.96729 | -0.1348 | 6.84210 |
November | 720.00000 | 21.05507 | 41.02312 | -0.4543 | 10.03863 |
December | 744.00000 | 20.82444 | 32.77142 | -0.5988 | 13.04584 |
Annual Sum or Average | 8760.00000 | 21.60873 | 45.62610 | -0.6691 | 18.09500 |
Minimum of Months | 672.00000 | 20.72004 | 27.36932 | -1.1971 | 6.84210 |
Maximum of Months | 744.00000 | 22.55113 | 60.08763 | -0.1348 | 37.21349 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56087 | 33.01381 | -0.7032 | 16.03816 |
February | 672.00000 | 20.60752 | 27.68306 | -0.7126 | 16.24578 |
March | 744.00000 | 20.89287 | 38.20703 | -0.5238 | 11.20852 |
April | 720.00000 | 21.27640 | 44.95806 | -0.3371 | 8.29608 |
May | 744.00000 | 21.84070 | 51.47293 | -1.2144 | 37.93610 |
June | 720.00000 | 22.37658 | 57.95990 | -0.9362 | 26.48778 |
July | 744.00000 | 22.53913 | 60.32879 | -0.8330 | 23.59322 |
August | 744.00000 | 22.45286 | 56.63245 | -0.8786 | 24.94027 |
September | 720.00000 | 22.09577 | 56.36535 | -1.0813 | 32.10229 |
October | 744.00000 | 21.47498 | 50.42848 | -0.2342 | 7.14462 |
November | 720.00000 | 20.83004 | 41.52289 | -0.5301 | 11.49431 |
December | 744.00000 | 20.59940 | 33.13500 | -0.6767 | 15.13701 |
Annual Sum or Average | 8760.00000 | 21.46729 | 46.07969 | -0.7219 | 19.23899 |
Minimum of Months | 672.00000 | 20.56087 | 27.68306 | -1.2144 | 7.14462 |
Maximum of Months | 744.00000 | 22.53913 | 60.32879 | -0.2342 | 37.93610 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.65014 | 33.20411 | -0.6965 | 15.85921 |
February | 672.00000 | 20.75516 | 27.74753 | -0.6859 | 15.58400 |
March | 744.00000 | 21.04356 | 38.33815 | -0.4805 | 10.87062 |
April | 720.00000 | 21.40345 | 45.11774 | -0.3012 | 8.88877 |
May | 744.00000 | 22.05052 | 51.39266 | -1.1256 | 36.42864 |
June | 720.00000 | 22.81168 | 55.02699 | -0.7514 | 24.53459 |
July | 744.00000 | 22.79861 | 57.50763 | -0.7031 | 22.45107 |
August | 744.00000 | 22.72440 | 54.14470 | -0.7361 | 23.58943 |
September | 720.00000 | 22.51804 | 54.27842 | -0.8991 | 28.54306 |
October | 744.00000 | 21.90669 | 48.51005 | -0.1003 | 7.79997 |
November | 720.00000 | 20.95688 | 41.68673 | -0.5060 | 11.24865 |
December | 744.00000 | 20.74282 | 33.23184 | -0.6535 | 14.56438 |
Annual Sum or Average | 8760.00000 | 21.70210 | 45.11351 | -0.6364 | 18.38703 |
Minimum of Months | 672.00000 | 20.65014 | 27.74753 | -1.1256 | 7.79997 |
Maximum of Months | 744.00000 | 22.81168 | 57.50763 | -0.1003 | 36.42864 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51493 | 33.44237 | -0.7533 | 17.61605 |
February | 672.00000 | 20.54747 | 28.05994 | -0.7685 | 18.03688 |
March | 744.00000 | 20.81965 | 38.75436 | -0.5570 | 12.30870 |
April | 720.00000 | 21.28037 | 45.44657 | -0.3427 | 9.13349 |
May | 744.00000 | 22.01864 | 51.51124 | -1.1429 | 37.01487 |
June | 720.00000 | 22.80685 | 55.09302 | -0.7569 | 24.61322 |
July | 744.00000 | 22.78708 | 57.77811 | -0.7108 | 22.56675 |
August | 744.00000 | 22.67565 | 54.71634 | -0.7664 | 24.01816 |
September | 720.00000 | 22.37770 | 55.25402 | -0.9685 | 30.28116 |
October | 744.00000 | 21.62265 | 50.40973 | -0.1969 | 7.88244 |
November | 720.00000 | 20.73124 | 42.20843 | -0.5865 | 12.93859 |
December | 744.00000 | 20.53455 | 33.59841 | -0.7308 | 16.75564 |
Annual Sum or Average | 8760.00000 | 21.56543 | 45.62265 | -0.6898 | 19.44402 |
Minimum of Months | 672.00000 | 20.51493 | 28.05994 | -1.1429 | 7.88244 |
Maximum of Months | 744.00000 | 22.80685 | 57.77811 | -0.1969 | 37.01487 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.04104 | 33.67512 | -0.5290 | 11.96855 |
February | 672.00000 | 21.22022 | 28.40243 | -0.4909 | 11.32556 |
March | 744.00000 | 21.28411 | 38.60912 | -0.3839 | 9.20274 |
April | 720.00000 | 21.44007 | 45.27858 | -0.2842 | 7.88991 |
May | 744.00000 | 21.81812 | 51.49604 | -1.2324 | 38.53298 |
June | 720.00000 | 22.34815 | 57.43462 | -0.9488 | 27.11524 |
July | 744.00000 | 22.57096 | 59.75345 | -0.8238 | 23.49218 |
August | 744.00000 | 22.49175 | 55.45758 | -0.8573 | 24.52187 |
September | 720.00000 | 22.35534 | 53.85334 | -0.9541 | 28.03470 |
October | 744.00000 | 21.93583 | 47.77005 | -0.0582 | 7.14957 |
November | 720.00000 | 21.35206 | 41.48744 | -0.3440 | 8.53307 |
December | 744.00000 | 21.15472 | 33.57476 | -0.4749 | 10.95072 |
Annual Sum or Average | 8760.00000 | 21.75405 | 45.66386 | -0.6159 | 17.43748 |
Minimum of Months | 672.00000 | 21.04104 | 28.40243 | -1.2324 | 7.14957 |
Maximum of Months | 744.00000 | 22.57096 | 59.75345 | -0.0582 | 38.53298 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.18918 | 33.17489 | 0.11793 | 6.20316 |
February | 672.00000 | 23.16984 | 29.13173 | 0.08534 | 5.99104 |
March | 744.00000 | 23.46459 | 37.16719 | 0.24518 | 6.81200 |
April | 720.00000 | 23.51954 | 43.03062 | 0.32818 | 7.70156 |
May | 744.00000 | 23.47091 | 49.95057 | -0.5122 | 11.24599 |
June | 720.00000 | 23.44015 | 56.56435 | -0.4290 | 9.58746 |
July | 744.00000 | 23.52739 | 58.40833 | -0.3613 | 8.22754 |
August | 744.00000 | 23.52415 | 57.18446 | -0.3742 | 8.48275 |
September | 720.00000 | 23.35054 | 55.04562 | -0.4975 | 11.07678 |
October | 744.00000 | 23.43573 | 47.87147 | 0.35424 | 8.18643 |
November | 720.00000 | 23.42662 | 39.24939 | 0.24911 | 6.92882 |
December | 744.00000 | 23.31691 | 32.97245 | 0.15666 | 6.17583 |
Annual Sum or Average | 8760.00000 | 23.40454 | 45.07123 | -0.0539 | 8.06009 |
Minimum of Months | 672.00000 | 23.16984 | 29.13173 | -0.5122 | 5.99104 |
Maximum of Months | 744.00000 | 23.52739 | 58.40833 | 0.35424 | 11.24599 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.43905 | 32.14815 | 0.21894 | 6.70551 |
February | 672.00000 | 23.41958 | 28.18059 | 0.18579 | 6.35913 |
March | 744.00000 | 23.65475 | 36.05649 | 0.33154 | 7.68298 |
April | 720.00000 | 23.69449 | 41.91515 | 0.41006 | 8.82979 |
May | 744.00000 | 23.64007 | 48.81226 | -0.3994 | 8.83912 |
June | 720.00000 | 23.58929 | 55.45847 | -0.3285 | 7.77170 |
July | 744.00000 | 23.65607 | 57.38790 | -0.2712 | 6.88000 |
August | 744.00000 | 23.64502 | 56.20345 | -0.2875 | 7.11496 |
September | 720.00000 | 23.51770 | 53.91979 | -0.3901 | 8.82402 |
October | 744.00000 | 23.59447 | 46.76461 | 0.42929 | 9.28443 |
November | 720.00000 | 23.62371 | 38.14920 | 0.33690 | 7.82547 |
December | 744.00000 | 23.53261 | 31.90383 | 0.24957 | 6.76655 |
Annual Sum or Average | 8760.00000 | 23.58501 | 43.99976 | 0.03962 | 7.74538 |
Minimum of Months | 672.00000 | 23.41958 | 28.18059 | -0.3994 | 6.35913 |
Maximum of Months | 744.00000 | 23.69449 | 57.38790 | 0.42929 | 9.28443 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.66860 | 30.59474 | 0.90240 | 25.65766 |
February | 672.00000 | 23.62735 | 26.67812 | 0.87146 | 24.51547 |
March | 744.00000 | 23.80997 | 34.63829 | 1.01565 | 29.85877 |
April | 720.00000 | 23.85422 | 40.76282 | 1.10536 | 33.62719 |
May | 744.00000 | 23.68138 | 47.74430 | 0.57377 | 18.47585 |
June | 720.00000 | 23.47951 | 54.53868 | 0.60254 | 20.91372 |
July | 744.00000 | 23.42685 | 56.73633 | 0.63199 | 22.25522 |
August | 744.00000 | 23.45933 | 55.43428 | 0.63884 | 22.22170 |
September | 720.00000 | 23.51757 | 52.75109 | 0.57457 | 19.74094 |
October | 744.00000 | 23.76796 | 45.47108 | 1.13693 | 35.01569 |
November | 720.00000 | 23.82005 | 36.80571 | 1.02633 | 30.26607 |
December | 744.00000 | 23.71234 | 30.45253 | 0.92668 | 26.20549 |
Annual Sum or Average | 8760.00000 | 23.65212 | 42.81083 | 0.83364 | 25.73499 |
Minimum of Months | 672.00000 | 23.42685 | 26.67812 | 0.57377 | 18.47585 |
Maximum of Months | 744.00000 | 23.85422 | 56.73633 | 1.13693 | 35.01569 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.120836E+10 | 10813.73 | 17-JAN-19:04 | 263.11 | 0.376517E+10 | 0.00 | 0.497353E+10 | 1.10 | 3.12 | 20-JAN-21:10 | 0.00 | 0.00 |
February | 0.144592E+10 | 16090.35 | 20-FEB-09:02 | 259.53 | 0.450539E+10 | 0.00 | 0.595131E+10 | 1.20 | 3.12 | 16-FEB-10:50 | 0.00 | 0.00 |
March | 0.628031E+10 | 83234.31 | 27-MAR-15:02 | 450.74 | 0.190477E+11 | 0.00 | 0.253280E+11 | 1.88 | 3.53 | 27-MAR-15:02 | 0.00 | 0.00 |
April | 0.278549E+11 | 106488.02 | 07-APR-15:02 | 558.40 | 0.819372E+11 | 0.00 | 0.109792E+12 | 2.37 | 3.63 | 10-APR-08:12 | 0.00 | 0.00 |
May | 0.855470E+11 | 130538.40 | 31-MAY-15:03 | 733.71 | 0.255009E+12 | 0.00 | 0.340556E+12 | 2.96 | 4.16 | 18-MAY-15:02 | 0.00 | 0.00 |
June | 0.233700E+12 | 190872.67 | 19-JUN-18:03 | 720.00 | 0.812405E+12 | 0.00 | 0.104611E+13 | 3.38 | 4.31 | 13-JUN-21:13 | 0.00 | 0.00 |
July | 0.327900E+12 | 213648.56 | 20-JUL-20:13 | 744.00 | 0.117014E+13 | 0.00 | 0.149804E+13 | 3.56 | 4.24 | 15-JUL-08:13 | 0.00 | 0.00 |
August | 0.292977E+12 | 207623.29 | 03-AUG-21:13 | 744.00 | 0.991626E+12 | 0.00 | 0.128460E+13 | 3.34 | 4.24 | 06-AUG-21:13 | 0.00 | 0.00 |
September | 0.179275E+12 | 169479.25 | 13-SEP-21:13 | 719.36 | 0.600251E+12 | 0.00 | 0.779526E+12 | 3.21 | 4.23 | 09-SEP-21:12 | 0.00 | 0.00 |
October | 0.833031E+11 | 133625.91 | 05-OCT-15:02 | 700.73 | 0.270434E+12 | 0.00 | 0.353737E+12 | 2.95 | 4.24 | 23-OCT-21:12 | 0.00 | 0.00 |
November | 0.805555E+10 | 60306.68 | 10-NOV-09:03 | 449.96 | 0.244908E+11 | 0.00 | 0.325463E+11 | 1.94 | 3.12 | 03-NOV-17:03 | 0.00 | 0.00 |
December | 0.254023E+10 | 13738.12 | 18-DEC-11:00 | 357.86 | 0.791518E+10 | 0.00 | 0.104554E+11 | 1.50 | 3.12 | 17-DEC-16:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.125009E+13 | 6701.40 | 0.424153E+13 | 0.549161E+13 | 2.46 | |||||||
Minimum of Months | 0.120836E+10 | 10813.73 | 259.53 | 0.376517E+10 | 0.00 | 0.497353E+10 | 1.10 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.327900E+12 | 213648.56 | 744.00 | 0.117014E+13 | 0.00 | 0.149804E+13 | 3.56 | 4.31 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.127939E+12 | 0.00 | 744.00 | 197013.41 | 02-JAN-09:05 | 0.00 | 51.22 | 60.00 | 1.31 | 0.00 | 0.10 | 0.43 | 02-JAN-09:05 |
February | 0.114727E+12 | 0.00 | 672.00 | 196915.73 | 06-FEB-09:02 | 0.00 | 51.43 | 60.00 | 1.25 | 0.00 | 0.10 | 0.43 | 06-FEB-09:02 |
March | 0.507575E+11 | 0.00 | 743.89 | 139316.40 | 26-MAR-21:03 | 0.00 | 50.52 | 60.00 | 0.55 | 0.00 | 0.04 | 0.30 | 26-MAR-21:03 |
April | 0.356980E+11 | 0.00 | 701.95 | 138739.15 | 22-APR-15:02 | 0.00 | 46.99 | 59.53 | 0.34 | 0.00 | 0.03 | 0.30 | 22-APR-15:02 |
May | 0.173326E+11 | 0.00 | 682.43 | 89505.69 | 19-MAY-15:05 | 0.00 | 43.46 | 58.74 | 0.11 | 0.00 | 0.01 | 0.19 | 19-MAY-15:05 |
June | 0.992994E+10 | 0.00 | 562.64 | 100446.25 | 06-JUN-15:05 | 0.00 | 43.86 | 56.53 | 0.06 | 0.00 | 0.01 | 0.22 | 06-JUN-15:05 |
July | 0.762951E+10 | 0.00 | 501.17 | 22768.59 | 24-JUL-08:15 | 0.00 | 43.77 | 54.47 | 0.05 | 0.00 | 0.01 | 0.05 | 24-JUL-08:15 |
August | 0.583643E+10 | 0.00 | 489.82 | 30980.57 | 22-AUG-18:07 | 0.00 | 44.18 | 54.42 | 0.04 | 0.00 | 0.00 | 0.07 | 22-AUG-18:07 |
September | 0.945374E+10 | 0.00 | 591.61 | 97462.43 | 23-SEP-15:04 | 0.00 | 42.80 | 56.95 | 0.06 | 0.00 | 0.01 | 0.21 | 23-SEP-15:04 |
October | 0.210594E+11 | 0.00 | 657.97 | 128522.74 | 08-OCT-21:52 | 0.00 | 44.84 | 57.99 | 0.17 | 0.00 | 0.02 | 0.28 | 08-OCT-21:52 |
November | 0.532432E+11 | 0.00 | 714.06 | 144243.92 | 13-NOV-16:02 | 0.00 | 50.23 | 59.90 | 0.58 | 0.00 | 0.04 | 0.31 | 13-NOV-16:02 |
December | 0.764211E+11 | 0.00 | 743.94 | 144498.91 | 31-DEC-16:03 | 0.00 | 51.85 | 60.00 | 0.88 | 0.00 | 0.06 | 0.31 | 31-DEC-16:03 |
Annual Sum or Average | 0.530028E+12 | 7805.48 | 47.07 | 58.20 | 0.44 | 0.00 | 0.04 | ||||||
Minimum of Months | 0.583643E+10 | 0.00 | 489.82 | 22768.59 | 0.00 | 42.80 | 54.42 | 0.04 | 0.00 | 0.00 | 0.05 | ||
Maximum of Months | 0.127939E+12 | 0.00 | 744.00 | 197013.41 | 0.00 | 51.85 | 60.00 | 1.31 | 0.00 | 0.10 | 0.43 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 27780306.12 | 0.00 | 7.02 | 26975974.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14568.56 | 17-JAN-16:01 | 14568.56 | 17-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 76859816.80 | 0.00 | 13.81 | 76716955.60 | 0.00 | 0.00 | 0.00 | 0.00 | 14507.89 | 02-FEB-16:01 | 14507.89 | 02-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.571324E+09 | 0.00 | 98.61 | 0.507538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15238.61 | 27-MAR-15:02 | 14609.57 | 29-MAR-15:02 | 0.00 | 0.00 | 0.00 |
April | 0.129206E+10 | 0.00 | 227.85 | 0.817434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16446.91 | 27-APR-17:41 | 15439.18 | 09-APR-17:31 | 0.00 | 0.00 | 0.00 |
May | 0.251251E+10 | 0.00 | 386.46 | 0.140912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19020.67 | 31-MAY-21:11 | 15533.09 | 27-MAY-21:11 | 0.00 | 0.00 | 0.00 |
June | 0.505381E+10 | 0.00 | 429.52 | 0.263038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20985.38 | 24-JUN-21:11 | 14759.16 | 22-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.741070E+10 | 0.00 | 495.85 | 0.396816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22853.10 | 19-JUL-21:11 | 14529.16 | 04-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.787397E+10 | 0.00 | 516.81 | 0.456547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23858.93 | 03-AUG-21:11 | 15344.93 | 25-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.382114E+10 | 0.00 | 417.76 | 0.192696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21003.09 | 13-SEP-21:11 | 15522.31 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.252970E+10 | 0.00 | 399.49 | 0.136159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18630.47 | 05-OCT-21:11 | 14888.60 | 30-OCT-16:01 | 0.00 | 0.00 | 0.00 |
November | 0.235673E+09 | 0.00 | 81.62 | 0.150496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14615.91 | 03-NOV-15:02 | 14615.91 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 36824993.70 | 0.00 | 12.04 | 35962186.21 | 0.00 | 0.00 | 0.00 | 0.00 | 14380.36 | 17-DEC-16:01 | 14380.36 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314423E+11 | 3086.83 | 0.174768E+11 | ||||||||||||
Minimum of Months | 27780306.12 | 0.00 | 7.02 | 26975974.99 | 0.00 | 0.00 | 0.00 | 0.00 | 14380.36 | 14380.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.787397E+10 | 0.00 | 516.81 | 0.456547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23858.93 | 15533.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2593194.02 | 0.00 | 1.31 | 2204372.47 | 0.00 | 0.00 | 0.00 | 0.00 | 5015.55 | 17-JAN-16:01 | 5015.55 | 17-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 9713260.03 | 0.00 | 4.49 | 9709424.64 | 0.00 | 0.00 | 0.00 | 0.00 | 10303.11 | 20-FEB-16:01 | 10303.11 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.280358E+09 | 0.00 | 53.58 | 0.250194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14668.47 | 27-MAR-15:02 | 14304.04 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.947073E+09 | 0.00 | 184.20 | 0.585482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16113.63 | 27-APR-17:41 | 14907.35 | 09-APR-17:31 | 0.00 | 0.00 | 0.00 |
May | 0.231822E+10 | 0.00 | 374.40 | 0.128352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18671.45 | 31-MAY-21:11 | 15216.87 | 27-MAY-21:11 | 0.00 | 0.00 | 0.00 |
June | 0.489299E+10 | 0.00 | 422.62 | 0.254037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20644.66 | 24-JUN-21:11 | 14603.80 | 22-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.716008E+10 | 0.00 | 493.99 | 0.381167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22461.31 | 19-JUL-21:11 | 14250.62 | 04-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.714448E+10 | 0.00 | 506.22 | 0.404379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22699.68 | 03-AUG-21:11 | 14803.47 | 28-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.294028E+10 | 0.00 | 365.68 | 0.139258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20576.00 | 13-SEP-21:11 | 14818.76 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.120086E+10 | 0.00 | 266.02 | 0.571096E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18015.21 | 05-OCT-21:11 | 14390.46 | 17-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 49727465.18 | 0.00 | 21.84 | 31778433.16 | 0.00 | 0.00 | 0.00 | 0.00 | 13912.06 | 03-NOV-15:02 | 13912.06 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 2944014.92 | 0.00 | 0.74 | 2522530.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.91 | 25-DEC-16:03 | 2091.24 | 08-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269493E+11 | 2695.10 | 0.145249E+11 | ||||||||||||
Minimum of Months | 2593194.02 | 0.00 | 0.74 | 2204372.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2116.91 | 2091.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.716008E+10 | 0.00 | 506.22 | 0.404379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22699.68 | 15216.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.104942E+09 | 0.00 | 7.85 | 0.104942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7351.47 | 19-JAN-14:10 | 7351.47 | 19-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.725578E+09 | 0.00 | 24.48 | 0.725578E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18648.17 | 03-FEB-12:30 | 18648.17 | 03-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.160738E+10 | 0.00 | 58.04 | 0.160738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25144.40 | 03-MAR-13:30 | 25144.40 | 03-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.352546E+10 | 0.00 | 103.45 | 0.228464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30395.50 | 08-APR-12:20 | 23021.64 | 08-APR-12:30 | 0.00 | 0.00 | 0.00 |
May | 0.595662E+10 | 0.00 | 262.49 | 0.331097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24787.02 | 30-MAY-16:40 | 15696.45 | 30-MAY-16:40 | 0.00 | 0.00 | 0.00 |
June | 0.177568E+11 | 0.00 | 469.50 | 0.655774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43904.42 | 25-JUN-18:30 | 24166.88 | 25-JUN-21:00 | 0.00 | 0.00 | 0.00 |
July | 0.382742E+11 | 0.00 | 657.79 | 0.153539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59515.45 | 22-JUL-17:02 | 32834.30 | 21-JUL-18:00 | 0.00 | 0.00 | 0.00 |
August | 0.416441E+11 | 0.00 | 677.00 | 0.207331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60103.82 | 03-AUG-20:20 | 31111.86 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 0.260375E+11 | 0.00 | 500.56 | 0.145031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51183.24 | 07-SEP-16:20 | 34153.74 | 30-SEP-11:10 | 0.00 | 0.00 | 0.00 |
October | 0.272829E+11 | 0.00 | 457.78 | 0.199350E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45975.50 | 04-OCT-12:00 | 43492.14 | 30-OCT-12:50 | 0.00 | 0.00 | 0.00 |
November | 0.576764E+10 | 0.00 | 134.71 | 0.507193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39864.65 | 02-NOV-12:30 | 39864.65 | 02-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 0.259430E+10 | 0.00 | 58.74 | 0.259430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32047.56 | 17-DEC-12:30 | 32047.56 | 17-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171277E+12 | 3412.37 | 0.927826E+11 | ||||||||||||
Minimum of Months | 0.104942E+09 | 0.00 | 7.85 | 0.104942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7351.47 | 7351.47 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.416441E+11 | 0.00 | 677.00 | 0.207331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60103.82 | 43492.14 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.588108E+09 | 0.00 | 52.18 | 0.293214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53663.37 | 22-JAN-09:02 | 47019.90 | 22-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.321566E+09 | 0.00 | 34.92 | 0.290462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 54382.50 | 20-FEB-09:02 | 54382.50 | 20-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.361984E+10 | 0.00 | 189.97 | 0.237584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78448.67 | 28-MAR-18:01 | 78448.67 | 28-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.132431E+11 | 0.00 | 359.21 | 0.764857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86923.02 | 30-APR-18:03 | 79694.84 | 07-APR-21:11 | 0.00 | 0.00 | 0.00 |
May | 0.284110E+11 | 0.00 | 424.92 | 0.174013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105013.73 | 31-MAY-21:11 | 85859.86 | 27-MAY-21:11 | 0.00 | 0.00 | 0.00 |
June | 0.426123E+11 | 0.00 | 333.00 | 0.270702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124645.52 | 24-JUN-21:11 | 84819.22 | 04-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.590264E+11 | 0.00 | 388.55 | 0.380133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135342.13 | 19-JUL-21:11 | 82446.21 | 11-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.537936E+11 | 0.00 | 389.61 | 0.352900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135778.92 | 03-AUG-21:11 | 84681.02 | 28-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.320783E+11 | 0.00 | 338.02 | 0.190541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 123678.57 | 07-SEP-21:11 | 83845.33 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.172207E+11 | 0.00 | 382.28 | 0.935282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105248.75 | 05-OCT-21:11 | 80825.73 | 25-OCT-21:11 | 0.00 | 0.00 | 0.00 |
November | 0.477364E+10 | 0.00 | 226.55 | 0.259931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79317.62 | 11-NOV-09:02 | 77028.58 | 02-NOV-18:02 | 0.00 | 0.00 | 0.00 |
December | 0.581960E+09 | 0.00 | 63.73 | 0.441090E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 61594.22 | 25-DEC-09:02 | 54481.62 | 25-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256270E+12 | 3182.92 | 0.159830E+12 | ||||||||||||
Minimum of Months | 0.321566E+09 | 0.00 | 34.92 | 0.290462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53663.37 | 47019.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.590264E+11 | 0.00 | 424.92 | 0.380133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135778.92 | 85859.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 54466418.15 | 0.00 | 14.00 | 50182604.73 | 0.00 | 0.00 | 0.00 | 0.00 | 9401.98 | 19-JAN-09:02 | 9401.98 | 19-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 89859644.05 | 0.00 | 19.87 | 89635074.04 | 0.00 | 0.00 | 0.00 | 0.00 | 12851.80 | 25-FEB-09:02 | 12851.80 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.468748E+09 | 0.00 | 92.80 | 0.412677E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13263.85 | 11-MAR-09:02 | 13263.85 | 11-MAR-09:02 | 0.00 | 0.00 | 0.00 |
April | 0.138903E+10 | 0.00 | 247.32 | 0.880443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14748.61 | 08-APR-08:11 | 13888.60 | 08-APR-08:11 | 0.00 | 0.00 | 0.00 |
May | 0.281111E+10 | 0.00 | 407.10 | 0.171205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17736.02 | 31-MAY-08:11 | 15527.37 | 30-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.479931E+10 | 0.00 | 441.15 | 0.254441E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19941.53 | 25-JUN-08:11 | 15365.74 | 22-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.736256E+10 | 0.00 | 503.21 | 0.395745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20532.26 | 19-JUL-21:11 | 14962.90 | 14-JUL-07:31 | 0.00 | 0.00 | 0.00 |
August | 0.783865E+10 | 0.00 | 523.68 | 0.457343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21564.67 | 03-AUG-21:11 | 15633.18 | 22-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.403689E+10 | 0.00 | 435.87 | 0.219843E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19199.59 | 07-SEP-21:11 | 14929.82 | 03-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.250730E+10 | 0.00 | 392.34 | 0.145664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16926.29 | 25-OCT-08:11 | 13271.50 | 30-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.372377E+09 | 0.00 | 95.31 | 0.248842E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13171.70 | 02-NOV-15:01 | 13171.70 | 02-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 0.104392E+09 | 0.00 | 26.29 | 97860616.29 | 0.00 | 0.00 | 0.00 | 0.00 | 12871.95 | 17-DEC-09:02 | 12871.95 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318347E+11 | 3198.94 | 0.182221E+11 | ||||||||||||
Minimum of Months | 54466418.15 | 0.00 | 14.00 | 50182604.73 | 0.00 | 0.00 | 0.00 | 0.00 | 9401.98 | 9401.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.783865E+10 | 0.00 | 523.68 | 0.457343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21564.67 | 15633.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 4219185.98 | 0.00 | 2.11 | 2541162.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2583.94 | 30-JAN-09:03 | 2583.94 | 30-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 17102630.46 | 0.00 | 5.73 | 17029984.80 | 0.00 | 0.00 | 0.00 | 0.00 | 11510.51 | 25-FEB-09:02 | 11510.51 | 25-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.214816E+09 | 0.00 | 52.78 | 0.182877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12975.28 | 29-MAR-08:62 | 12975.28 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 |
April | 0.105073E+10 | 0.00 | 189.54 | 0.657994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14593.12 | 08-APR-08:11 | 13613.19 | 08-APR-08:11 | 0.00 | 0.00 | 0.00 |
May | 0.261144E+10 | 0.00 | 373.17 | 0.158929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17605.30 | 31-MAY-08:11 | 15414.33 | 30-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.463470E+10 | 0.00 | 437.49 | 0.246058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19421.72 | 25-JUN-08:11 | 15295.19 | 22-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.710148E+10 | 0.00 | 502.01 | 0.378450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20337.86 | 19-JUL-21:11 | 14851.73 | 11-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.709951E+10 | 0.00 | 520.13 | 0.403790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20675.85 | 03-AUG-21:11 | 15408.02 | 22-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.314014E+10 | 0.00 | 376.19 | 0.166064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18854.51 | 07-SEP-21:11 | 14737.76 | 03-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.125076E+10 | 0.00 | 235.28 | 0.663391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16490.40 | 25-OCT-08:11 | 12637.07 | 16-OCT-08:62 | 0.00 | 0.00 | 0.00 |
November | 0.110279E+09 | 0.00 | 39.80 | 58143156.93 | 0.00 | 0.00 | 0.00 | 0.00 | 11616.68 | 04-NOV-08:62 | 11394.78 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 7466233.97 | 0.00 | 3.94 | 6339347.55 | 0.00 | 0.00 | 0.00 | 0.00 | 5716.22 | 17-DEC-09:02 | 5716.22 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.272426E+11 | 2738.17 | 0.151212E+11 | ||||||||||||
Minimum of Months | 4219185.98 | 0.00 | 2.11 | 2541162.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2583.94 | 2583.94 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.710148E+10 | 0.00 | 520.13 | 0.403790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20675.85 | 15414.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 7425390.75 | 0.00 | 5.95 | 7278455.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3833.70 | 17-JAN-16:01 | 3833.70 | 17-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 21333287.77 | 0.00 | 13.75 | 21333287.77 | 0.00 | 0.00 | 0.00 | 0.00 | 3834.20 | 20-FEB-16:01 | 3834.20 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.157999E+09 | 0.00 | 93.28 | 0.141656E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4052.76 | 27-MAR-15:02 | 3836.90 | 29-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.393115E+09 | 0.00 | 227.22 | 0.259895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4562.20 | 09-APR-17:31 | 4437.86 | 09-APR-17:31 | 0.00 | 0.00 | 0.00 |
May | 0.817100E+09 | 0.00 | 399.95 | 0.490926E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5288.33 | 31-MAY-21:11 | 4145.17 | 17-MAY-20:01 | 0.00 | 0.00 | 0.00 |
June | 0.167466E+10 | 0.00 | 453.06 | 0.961326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5729.16 | 24-JUN-21:11 | 4218.19 | 04-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.237031E+10 | 0.00 | 504.91 | 0.139650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6109.04 | 22-JUL-08:11 | 4116.86 | 04-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.246586E+10 | 0.00 | 524.00 | 0.156146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5896.92 | 05-AUG-21:11 | 4296.82 | 25-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.123495E+10 | 0.00 | 426.12 | 0.691442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5814.37 | 13-SEP-21:11 | 4110.47 | 03-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.742035E+09 | 0.00 | 387.71 | 0.418696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5079.85 | 05-OCT-21:11 | 4011.22 | 30-OCT-16:01 | 0.00 | 0.00 | 0.00 |
November | 55247639.35 | 0.00 | 66.02 | 38198397.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3837.20 | 03-NOV-15:02 | 3837.20 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 7217890.30 | 0.00 | 8.10 | 7021997.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3820.39 | 17-DEC-16:01 | 3820.39 | 17-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.994726E+10 | 3110.09 | 0.599574E+10 | ||||||||||||
Minimum of Months | 7217890.30 | 0.00 | 5.95 | 7021997.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3820.39 | 3820.39 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.246586E+10 | 0.00 | 524.00 | 0.156146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6109.04 | 4437.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 517710.64 | 0.00 | 0.81 | 463648.50 | 0.00 | 0.00 | 0.00 | 0.00 | 671.09 | 20-JAN-16:03 | 671.09 | 20-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 1198557.75 | 0.00 | 2.93 | 1198557.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2011.25 | 20-FEB-16:01 | 2011.25 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 71934629.16 | 0.00 | 52.07 | 63747057.50 | 0.00 | 0.00 | 0.00 | 0.00 | 3878.73 | 27-MAR-15:02 | 3765.22 | 11-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.286991E+09 | 0.00 | 181.73 | 0.185344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4335.67 | 27-APR-17:41 | 4189.72 | 09-APR-17:31 | 0.00 | 0.00 | 0.00 |
May | 0.758573E+09 | 0.00 | 381.22 | 0.451074E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5191.62 | 31-MAY-21:11 | 4047.37 | 17-MAY-20:01 | 0.00 | 0.00 | 0.00 |
June | 0.163241E+10 | 0.00 | 451.18 | 0.934291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5633.73 | 24-JUN-21:11 | 4135.29 | 04-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.230772E+10 | 0.00 | 503.99 | 0.135002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6012.24 | 22-JUL-08:11 | 4038.80 | 04-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.227262E+10 | 0.00 | 521.03 | 0.139676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5779.71 | 05-AUG-21:11 | 4170.66 | 25-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.974900E+09 | 0.00 | 387.48 | 0.508983E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5700.18 | 13-SEP-21:11 | 3957.45 | 03-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.359430E+09 | 0.00 | 256.82 | 0.174516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4903.03 | 05-OCT-21:11 | 3775.06 | 17-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 11228918.98 | 0.00 | 15.89 | 7436723.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3674.98 | 03-NOV-15:02 | 3674.98 | 03-NOV-15:02 | 0.00 | 0.00 | 0.00 |
December | 386009.54 | 0.00 | 0.42 | 316604.62 | 0.00 | 0.00 | 0.00 | 0.00 | 475.84 | 15-DEC-16:04 | 475.84 | 15-DEC-16:04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.867790E+10 | 2755.56 | 0.507415E+10 | ||||||||||||
Minimum of Months | 386009.54 | 0.00 | 0.42 | 316604.62 | 0.00 | 0.00 | 0.00 | 0.00 | 475.84 | 475.84 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.230772E+10 | 0.00 | 521.03 | 0.139676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6012.24 | 4189.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.861060E+09 | 0.00 | 94.68 | 0.855737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15653.85 | 17-JAN-16:01 | 15653.85 | 17-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.115015E+10 | 0.00 | 150.47 | 0.114996E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15655.25 | 20-FEB-16:01 | 15655.25 | 20-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.192684E+10 | 0.00 | 222.35 | 0.171358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16668.49 | 27-MAR-15:02 | 15664.14 | 28-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.245126E+10 | 0.00 | 305.36 | 0.159270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16498.77 | 27-APR-18:02 | 15754.25 | 07-APR-21:11 | 0.00 | 0.00 | 0.00 |
May | 0.387267E+10 | 0.00 | 442.48 | 0.219225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19830.65 | 31-MAY-21:11 | 16134.05 | 27-MAY-21:11 | 0.00 | 0.00 | 0.00 |
June | 0.741613E+10 | 0.00 | 438.55 | 0.423782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23495.54 | 25-JUN-18:41 | 15928.95 | 22-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.114711E+11 | 0.00 | 498.13 | 0.692979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25726.08 | 19-JUL-21:11 | 15273.44 | 30-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.123749E+11 | 0.00 | 521.30 | 0.823259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24655.72 | 03-AUG-21:11 | 17000.83 | 25-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.826343E+10 | 0.00 | 454.97 | 0.535642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23723.65 | 13-SEP-21:11 | 16689.35 | 10-SEP-21:11 | 0.00 | 0.00 | 0.00 |
October | 0.793432E+10 | 0.00 | 514.43 | 0.574069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20414.18 | 05-OCT-21:11 | 16431.62 | 30-OCT-16:01 | 0.00 | 0.00 | 0.00 |
November | 0.220793E+10 | 0.00 | 238.04 | 0.178036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15873.37 | 02-NOV-16:21 | 15873.37 | 02-NOV-16:21 | 0.00 | 0.00 | 0.00 |
December | 0.161845E+10 | 0.00 | 155.04 | 0.161026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15650.60 | 03-DEC-16:01 | 15650.60 | 03-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615482E+11 | 4035.80 | 0.413921E+11 | ||||||||||||
Minimum of Months | 0.861060E+09 | 0.00 | 94.68 | 0.855737E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15650.60 | 15273.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.123749E+11 | 0.00 | 521.30 | 0.823259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25726.08 | 17000.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.201056E+09 | 0.00 | 165.61 | 0.201056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9134.79 | 03-JAN-19:50 | 9134.79 | 03-JAN-19:50 | 0.00 | 0.00 | 0.00 |
February | 0.201457E+09 | 0.00 | 160.37 | 0.201457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8457.16 | 20-FEB-15:10 | 8457.16 | 20-FEB-15:10 | 0.00 | 0.00 | 0.00 |
March | 0.615827E+10 | 0.00 | 251.35 | 0.543803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 198079.43 | 27-MAR-13:00 | 158928.29 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.469006E+11 | 0.00 | 317.41 | 0.456488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 242699.92 | 09-APR-11:00 | 211784.48 | 07-APR-17:00 | 0.00 | 0.00 | 0.00 |
May | 0.176108E+12 | 0.00 | 559.43 | 0.142368E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310082.71 | 31-MAY-17:20 | 214957.20 | 29-MAY-09:00 | 0.00 | 0.00 | 0.00 |
June | 0.616653E+12 | 0.00 | 717.06 | 0.355162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 483967.24 | 24-JUN-18:10 | 283644.03 | 22-JUN-18:15 | 0.00 | 0.00 | 0.00 |
July | 0.880013E+12 | 0.00 | 744.00 | 0.471883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 483525.10 | 05-JUL-20:20 | 251033.01 | 11-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.730032E+12 | 0.00 | 744.00 | 0.459545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 462863.82 | 03-AUG-20:00 | 317504.55 | 24-AUG-18:50 | 0.00 | 0.00 | 0.00 |
September | 0.443509E+12 | 0.00 | 676.02 | 0.292075E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 466634.99 | 22-SEP-17:50 | 265056.86 | 14-SEP-19:10 | 0.00 | 0.00 | 0.00 |
October | 0.179768E+12 | 0.00 | 458.34 | 0.107593E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310626.32 | 25-OCT-09:30 | 186986.53 | 25-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.702257E+10 | 0.00 | 211.38 | 0.607917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122410.17 | 10-NOV-08:00 | 80096.49 | 04-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.357819E+09 | 0.00 | 243.42 | 0.357819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20247.55 | 17-DEC-20:08 | 20247.55 | 17-DEC-20:08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308692E+13 | 5248.39 | 0.188655E+13 | ||||||||||||
Minimum of Months | 0.201056E+09 | 0.00 | 160.37 | 0.201056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8457.16 | 8457.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.880013E+12 | 0.00 | 744.00 | 0.471883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 483967.24 | 317504.55 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.689690E+09 | 0.00 | 19.92 | 0.589293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32556.26 | 27-MAR-13:00 | 25905.04 | 27-MAR-15:55 | 0.00 | 0.00 | 0.00 |
April | 0.635838E+10 | 0.00 | 144.75 | 0.619782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40026.89 | 09-APR-11:00 | 31034.94 | 07-APR-17:00 | 0.00 | 0.00 | 0.00 |
May | 0.234222E+11 | 0.00 | 446.00 | 0.197232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53223.86 | 31-MAY-16:30 | 32702.30 | 30-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.997309E+11 | 0.00 | 707.83 | 0.561107E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84544.35 | 24-JUN-17:00 | 37421.98 | 19-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.141708E+12 | 0.00 | 744.00 | 0.763736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85046.07 | 26-JUL-16:50 | 35627.71 | 07-JUL-12:00 | 0.00 | 0.00 | 0.00 |
August | 0.113160E+12 | 0.00 | 744.00 | 0.724159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84761.84 | 03-AUG-20:00 | 35434.01 | 24-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.687130E+11 | 0.00 | 641.83 | 0.452750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78954.67 | 13-SEP-21:00 | 33393.67 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.244480E+11 | 0.00 | 337.83 | 0.148072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 52097.26 | 24-OCT-14:00 | 28767.57 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.604784E+09 | 0.00 | 33.00 | 0.540997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12356.39 | 10-NOV-08:00 | 10811.57 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478835E+12 | 3819.17 | 0.292034E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.141708E+12 | 0.00 | 744.00 | 0.763736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85046.07 | 37421.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.64 | 458.46 | 240.18 | 607.51 | 693.33 | 0.00 | 0.00 | 744.00 |
February | 924.91 | 614.83 | 310.07 | 797.00 | 694.15 | 0.00 | 0.00 | 672.00 |
March | 819.44 | 451.21 | 368.23 | 677.67 | 496.73 | 0.00 | 0.00 | 744.00 |
April | 651.97 | 263.73 | 388.24 | 495.16 | 341.99 | 0.00 | 0.00 | 720.00 |
May | 559.93 | 114.57 | 445.36 | 459.67 | 186.46 | 0.00 | 0.00 | 744.00 |
June | 528.68 | 81.36 | 447.32 | 543.56 | 74.11 | 0.00 | 0.00 | 720.00 |
July | 550.12 | 92.77 | 457.35 | 641.15 | 22.54 | 0.00 | 0.00 | 744.00 |
August | 736.83 | 271.73 | 465.10 | 803.02 | 52.31 | 0.00 | 0.00 | 744.00 |
September | 777.78 | 390.55 | 387.22 | 818.71 | 130.90 | 0.00 | 0.00 | 720.00 |
October | 1099.54 | 689.70 | 409.84 | 1157.19 | 300.20 | 0.00 | 0.00 | 744.00 |
November | 761.08 | 456.59 | 304.49 | 711.38 | 480.78 | 0.00 | 0.00 | 720.00 |
December | 754.69 | 535.99 | 218.70 | 699.39 | 624.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 737.75 | 367.20 | 370.54 | 700.81 | 339.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 528.68 | 81.36 | 218.70 | 459.67 | 22.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1099.54 | 689.70 | 465.10 | 1157.19 | 694.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1967.33 | 1291.00 | 676.33 | 1691.10 | 2008.69 | 0.00 | 0.00 | 744.00 |
February | 2604.47 | 1731.32 | 873.15 | 2217.92 | 2011.95 | 0.00 | 0.00 | 672.00 |
March | 2307.48 | 1270.58 | 1036.90 | 1882.67 | 1484.25 | 0.00 | 0.00 | 744.00 |
April | 1835.89 | 742.64 | 1093.25 | 1363.83 | 1049.47 | 0.00 | 0.00 | 720.00 |
May | 1576.72 | 322.61 | 1254.11 | 1252.50 | 597.97 | 0.00 | 0.00 | 744.00 |
June | 1488.73 | 229.11 | 1259.62 | 1487.05 | 261.99 | 0.00 | 0.00 | 720.00 |
July | 1549.09 | 261.23 | 1287.87 | 1756.82 | 100.48 | 0.00 | 0.00 | 744.00 |
August | 2074.87 | 765.17 | 1309.70 | 2221.90 | 187.45 | 0.00 | 0.00 | 744.00 |
September | 2190.16 | 1099.77 | 1090.40 | 2270.91 | 438.76 | 0.00 | 0.00 | 720.00 |
October | 3096.22 | 1942.15 | 1154.08 | 3221.08 | 939.72 | 0.00 | 0.00 | 744.00 |
November | 2143.16 | 1285.72 | 857.44 | 1971.26 | 1440.46 | 0.00 | 0.00 | 720.00 |
December | 2125.17 | 1509.32 | 615.85 | 1945.67 | 1828.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2077.44 | 1034.02 | 1043.42 | 1939.77 | 1023.61 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1488.73 | 229.11 | 615.85 | 1252.50 | 100.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3096.22 | 1942.15 | 1309.70 | 3221.08 | 2011.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2555.67 | 1677.08 | 878.59 | 2234.23 | 2742.43 | 0.00 | 0.00 | 744.00 |
February | 3383.36 | 2249.09 | 1134.27 | 2938.86 | 2727.24 | 0.00 | 0.00 | 672.00 |
March | 2997.55 | 1650.56 | 1346.99 | 2499.01 | 2016.52 | 0.00 | 0.00 | 744.00 |
April | 2384.93 | 964.73 | 1420.20 | 1811.27 | 1431.18 | 0.00 | 0.00 | 720.00 |
May | 2048.25 | 419.09 | 1629.17 | 1670.27 | 807.49 | 0.00 | 0.00 | 744.00 |
June | 1933.94 | 297.62 | 1636.32 | 2001.22 | 340.72 | 0.00 | 0.00 | 720.00 |
July | 2012.36 | 339.35 | 1673.01 | 2378.95 | 121.17 | 0.00 | 0.00 | 744.00 |
August | 2695.37 | 994.00 | 1701.37 | 3009.73 | 228.05 | 0.00 | 0.00 | 744.00 |
September | 2845.15 | 1428.66 | 1416.49 | 3048.23 | 562.24 | 0.00 | 0.00 | 720.00 |
October | 4022.17 | 2522.96 | 1499.21 | 4298.18 | 1228.07 | 0.00 | 0.00 | 744.00 |
November | 2784.09 | 1670.23 | 1113.86 | 2606.85 | 1964.11 | 0.00 | 0.00 | 720.00 |
December | 2760.71 | 1960.70 | 800.02 | 2570.65 | 2496.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2698.72 | 1343.25 | 1355.46 | 2588.51 | 1381.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1933.94 | 297.62 | 800.02 | 1670.27 | 121.17 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4022.17 | 2522.96 | 1701.37 | 4298.18 | 2742.43 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.85 | 90.46 | 47.39 | 121.04 | 138.95 | 0.00 | 0.00 | 744.00 |
February | 182.50 | 121.31 | 61.18 | 158.71 | 139.62 | 0.00 | 0.00 | 672.00 |
March | 161.69 | 89.03 | 72.66 | 134.69 | 100.23 | 0.00 | 0.00 | 744.00 |
April | 128.64 | 52.04 | 76.60 | 97.66 | 69.43 | 0.00 | 0.00 | 720.00 |
May | 110.48 | 22.61 | 87.88 | 87.85 | 39.45 | 0.00 | 0.00 | 744.00 |
June | 104.32 | 16.05 | 88.26 | 102.70 | 17.16 | 0.00 | 0.00 | 720.00 |
July | 108.55 | 18.30 | 90.24 | 125.17 | 5.46 | 0.00 | 0.00 | 744.00 |
August | 145.39 | 53.62 | 91.77 | 160.89 | 10.72 | 0.00 | 0.00 | 744.00 |
September | 153.47 | 77.06 | 76.40 | 161.65 | 26.89 | 0.00 | 0.00 | 720.00 |
October | 216.95 | 136.09 | 80.87 | 230.78 | 58.09 | 0.00 | 0.00 | 744.00 |
November | 150.17 | 90.09 | 60.08 | 142.37 | 94.54 | 0.00 | 0.00 | 720.00 |
December | 148.91 | 105.76 | 43.15 | 140.01 | 123.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.57 | 72.45 | 73.11 | 138.60 | 68.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.32 | 16.05 | 43.15 | 87.85 | 5.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 216.95 | 136.09 | 91.77 | 230.78 | 139.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.46 | 42.07 | 60.39 | 43.98 | 284.23 | 0.00 | 0.00 | 744.00 |
February | 150.50 | 66.05 | 84.45 | 75.24 | 288.10 | 0.00 | 0.00 | 672.00 |
March | 223.56 | 103.62 | 119.95 | 162.34 | 185.25 | 0.00 | 0.00 | 744.00 |
April | 242.80 | 103.76 | 139.04 | 208.84 | 126.23 | 0.00 | 0.00 | 720.00 |
May | 283.60 | 107.79 | 175.81 | 284.14 | 70.27 | 0.00 | 0.00 | 744.00 |
June | 309.86 | 125.03 | 184.83 | 355.15 | 30.30 | 0.00 | 0.00 | 720.00 |
July | 289.90 | 108.93 | 180.98 | 366.46 | 9.68 | 0.00 | 0.00 | 744.00 |
August | 320.77 | 148.31 | 172.46 | 404.90 | 19.44 | 0.00 | 0.00 | 744.00 |
September | 228.24 | 99.65 | 128.59 | 249.01 | 49.73 | 0.00 | 0.00 | 720.00 |
October | 226.45 | 110.31 | 116.14 | 211.31 | 110.61 | 0.00 | 0.00 | 744.00 |
November | 106.64 | 31.16 | 75.49 | 51.61 | 189.97 | 0.00 | 0.00 | 720.00 |
December | 94.21 | 40.67 | 53.53 | 40.67 | 257.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.37 | 90.82 | 124.55 | 205.41 | 134.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.21 | 31.16 | 53.53 | 40.67 | 9.68 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 320.77 | 148.31 | 184.83 | 404.90 | 288.10 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.52 | 0.00 | 26.52 | 0.47 | 157.92 | 0.00 | 0.00 | 744.00 |
February | 36.29 | 0.00 | 36.29 | 1.65 | 162.71 | 0.00 | 0.00 | 672.00 |
March | 50.34 | 0.00 | 50.34 | 12.00 | 104.73 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 0.25 | 60.33 | 30.19 | 68.81 | 0.00 | 0.00 | 720.00 |
May | 80.57 | 2.94 | 77.63 | 61.86 | 36.27 | 0.00 | 0.00 | 744.00 |
June | 84.99 | 4.51 | 80.48 | 88.07 | 15.53 | 0.00 | 0.00 | 720.00 |
July | 82.50 | 3.21 | 79.29 | 104.83 | 4.98 | 0.00 | 0.00 | 744.00 |
August | 72.96 | 0.96 | 71.99 | 94.37 | 9.88 | 0.00 | 0.00 | 744.00 |
September | 54.94 | 0.03 | 54.91 | 52.86 | 26.09 | 0.00 | 0.00 | 720.00 |
October | 47.51 | 0.00 | 47.51 | 29.36 | 59.37 | 0.00 | 0.00 | 744.00 |
November | 33.32 | 0.00 | 33.32 | 6.81 | 103.38 | 0.00 | 0.00 | 720.00 |
December | 23.13 | 0.00 | 23.13 | 0.40 | 142.51 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.58 | 1.00 | 53.58 | 40.51 | 73.85 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.13 | 0.00 | 23.13 | 0.40 | 4.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.99 | 4.51 | 80.48 | 104.83 | 162.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.46 | 42.07 | 60.39 | 46.51 | 280.40 | 0.00 | 0.00 | 744.00 |
February | 150.50 | 66.05 | 84.45 | 79.17 | 283.06 | 0.00 | 0.00 | 672.00 |
March | 223.56 | 103.62 | 119.95 | 167.23 | 182.44 | 0.00 | 0.00 | 744.00 |
April | 242.80 | 103.76 | 139.04 | 211.82 | 124.93 | 0.00 | 0.00 | 720.00 |
May | 283.60 | 107.79 | 175.81 | 285.38 | 69.83 | 0.00 | 0.00 | 744.00 |
June | 309.86 | 125.03 | 184.83 | 355.76 | 30.07 | 0.00 | 0.00 | 720.00 |
July | 289.90 | 108.93 | 180.98 | 367.16 | 9.50 | 0.00 | 0.00 | 744.00 |
August | 320.77 | 148.31 | 172.46 | 406.89 | 18.77 | 0.00 | 0.00 | 744.00 |
September | 228.24 | 99.65 | 128.59 | 252.67 | 48.05 | 0.00 | 0.00 | 720.00 |
October | 226.45 | 110.31 | 116.14 | 218.10 | 107.31 | 0.00 | 0.00 | 744.00 |
November | 106.64 | 31.16 | 75.49 | 55.74 | 186.10 | 0.00 | 0.00 | 720.00 |
December | 94.21 | 40.67 | 53.53 | 43.80 | 252.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.37 | 90.82 | 124.55 | 208.45 | 131.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.21 | 31.16 | 53.53 | 43.80 | 9.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 320.77 | 148.31 | 184.83 | 406.89 | 283.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 110.26 | 72.35 | 37.91 | 96.08 | 109.41 | 0.00 | 0.00 | 744.00 |
February | 145.97 | 97.03 | 48.94 | 124.66 | 114.66 | 0.00 | 0.00 | 672.00 |
March | 129.32 | 71.21 | 58.11 | 106.32 | 84.85 | 0.00 | 0.00 | 744.00 |
April | 102.89 | 41.62 | 61.27 | 76.95 | 59.99 | 0.00 | 0.00 | 720.00 |
May | 88.37 | 18.08 | 70.29 | 68.42 | 36.20 | 0.00 | 0.00 | 744.00 |
June | 83.44 | 12.84 | 70.60 | 82.21 | 16.08 | 0.00 | 0.00 | 720.00 |
July | 86.82 | 14.64 | 72.18 | 99.30 | 5.94 | 0.00 | 0.00 | 744.00 |
August | 116.29 | 42.88 | 73.40 | 127.61 | 10.22 | 0.00 | 0.00 | 744.00 |
September | 122.75 | 61.64 | 61.11 | 127.74 | 25.91 | 0.00 | 0.00 | 720.00 |
October | 173.53 | 108.85 | 64.68 | 181.60 | 54.34 | 0.00 | 0.00 | 744.00 |
November | 120.11 | 72.06 | 48.06 | 110.33 | 82.94 | 0.00 | 0.00 | 720.00 |
December | 119.11 | 84.59 | 34.52 | 109.73 | 102.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.43 | 57.95 | 58.48 | 109.23 | 58.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 83.44 | 12.84 | 34.52 | 68.42 | 5.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 173.53 | 108.85 | 73.40 | 181.60 | 114.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.22 | 0.00 | 21.22 | 0.20 | 132.08 | 0.00 | 0.00 | 744.00 |
February | 29.04 | 0.00 | 29.04 | 1.10 | 134.69 | 0.00 | 0.00 | 672.00 |
March | 40.28 | 0.00 | 40.28 | 9.47 | 85.82 | 0.00 | 0.00 | 744.00 |
April | 48.47 | 0.20 | 48.27 | 25.27 | 55.92 | 0.00 | 0.00 | 720.00 |
May | 64.46 | 2.35 | 62.11 | 52.60 | 28.55 | 0.00 | 0.00 | 744.00 |
June | 68.00 | 3.61 | 64.39 | 75.53 | 11.16 | 0.00 | 0.00 | 720.00 |
July | 66.01 | 2.57 | 63.44 | 88.46 | 3.21 | 0.00 | 0.00 | 744.00 |
August | 58.37 | 0.77 | 57.60 | 80.67 | 6.63 | 0.00 | 0.00 | 744.00 |
September | 43.96 | 0.02 | 43.93 | 45.33 | 19.67 | 0.00 | 0.00 | 720.00 |
October | 38.01 | 0.00 | 38.01 | 25.16 | 46.59 | 0.00 | 0.00 | 744.00 |
November | 26.66 | 0.00 | 26.66 | 5.09 | 86.83 | 0.00 | 0.00 | 720.00 |
December | 18.51 | 0.00 | 18.51 | 0.21 | 119.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 43.67 | 0.80 | 42.87 | 34.32 | 60.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.51 | 0.00 | 18.51 | 0.20 | 3.21 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 68.00 | 3.61 | 64.39 | 88.46 | 134.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.18 | 41.23 | 61.95 | 40.60 | 278.89 | 0.00 | 0.00 | 744.00 |
February | 160.18 | 74.60 | 85.59 | 79.72 | 277.35 | 0.00 | 0.00 | 672.00 |
March | 205.70 | 87.42 | 118.28 | 141.83 | 185.77 | 0.00 | 0.00 | 744.00 |
April | 246.25 | 108.09 | 138.16 | 209.33 | 121.78 | 0.00 | 0.00 | 720.00 |
May | 297.25 | 118.44 | 178.81 | 299.59 | 67.51 | 0.00 | 0.00 | 744.00 |
June | 276.02 | 99.96 | 176.06 | 315.14 | 27.85 | 0.00 | 0.00 | 720.00 |
July | 276.86 | 99.66 | 177.20 | 351.68 | 8.57 | 0.00 | 0.00 | 744.00 |
August | 312.35 | 140.92 | 171.44 | 393.71 | 17.28 | 0.00 | 0.00 | 744.00 |
September | 233.68 | 105.28 | 128.40 | 253.93 | 46.51 | 0.00 | 0.00 | 720.00 |
October | 211.10 | 95.56 | 115.54 | 190.64 | 106.68 | 0.00 | 0.00 | 744.00 |
November | 130.75 | 50.25 | 80.50 | 74.78 | 183.80 | 0.00 | 0.00 | 720.00 |
December | 102.23 | 48.25 | 53.99 | 45.38 | 250.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.30 | 89.24 | 124.06 | 200.53 | 130.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.23 | 41.23 | 53.99 | 40.60 | 8.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 312.35 | 140.92 | 178.81 | 393.71 | 278.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.85 | 90.46 | 47.39 | 120.71 | 138.75 | 0.00 | 0.00 | 744.00 |
February | 182.50 | 121.31 | 61.18 | 157.91 | 139.29 | 0.00 | 0.00 | 672.00 |
March | 161.69 | 89.03 | 72.66 | 133.83 | 99.26 | 0.00 | 0.00 | 744.00 |
April | 128.64 | 52.04 | 76.60 | 96.72 | 68.71 | 0.00 | 0.00 | 720.00 |
May | 110.48 | 22.61 | 87.88 | 86.69 | 38.35 | 0.00 | 0.00 | 744.00 |
June | 104.32 | 16.05 | 88.26 | 103.17 | 15.56 | 0.00 | 0.00 | 720.00 |
July | 108.55 | 18.30 | 90.24 | 125.05 | 4.66 | 0.00 | 0.00 | 744.00 |
August | 145.39 | 53.62 | 91.77 | 160.31 | 9.65 | 0.00 | 0.00 | 744.00 |
September | 153.47 | 77.06 | 76.40 | 161.20 | 25.73 | 0.00 | 0.00 | 720.00 |
October | 216.95 | 136.09 | 80.87 | 230.40 | 56.89 | 0.00 | 0.00 | 744.00 |
November | 150.17 | 90.09 | 60.08 | 141.58 | 94.61 | 0.00 | 0.00 | 720.00 |
December | 148.91 | 105.76 | 43.15 | 139.55 | 123.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.57 | 72.45 | 73.11 | 138.07 | 67.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.32 | 16.05 | 43.15 | 86.69 | 4.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 216.95 | 136.09 | 91.77 | 230.40 | 139.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.52 | 0.00 | 26.52 | 0.39 | 157.98 | 0.00 | 0.00 | 744.00 |
February | 36.29 | 0.00 | 36.29 | 1.50 | 162.93 | 0.00 | 0.00 | 672.00 |
March | 50.34 | 0.00 | 50.34 | 11.39 | 103.99 | 0.00 | 0.00 | 744.00 |
April | 60.58 | 0.25 | 60.33 | 29.38 | 68.30 | 0.00 | 0.00 | 720.00 |
May | 80.57 | 2.94 | 77.63 | 60.92 | 35.46 | 0.00 | 0.00 | 744.00 |
June | 84.99 | 4.51 | 80.48 | 88.90 | 14.32 | 0.00 | 0.00 | 720.00 |
July | 82.50 | 3.21 | 79.29 | 104.86 | 4.36 | 0.00 | 0.00 | 744.00 |
August | 72.96 | 0.96 | 71.99 | 93.86 | 8.96 | 0.00 | 0.00 | 744.00 |
September | 54.94 | 0.03 | 54.91 | 52.29 | 25.04 | 0.00 | 0.00 | 720.00 |
October | 47.51 | 0.00 | 47.51 | 28.82 | 57.84 | 0.00 | 0.00 | 744.00 |
November | 33.32 | 0.00 | 33.32 | 6.37 | 103.82 | 0.00 | 0.00 | 720.00 |
December | 23.13 | 0.00 | 23.13 | 0.32 | 142.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.58 | 1.00 | 53.58 | 40.19 | 73.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.13 | 0.00 | 23.13 | 0.32 | 4.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 84.99 | 4.51 | 80.48 | 104.86 | 162.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.18 | 41.23 | 61.95 | 41.86 | 273.87 | 0.00 | 0.00 | 744.00 |
February | 160.18 | 74.60 | 85.59 | 81.95 | 270.52 | 0.00 | 0.00 | 672.00 |
March | 205.70 | 87.42 | 118.28 | 145.89 | 182.10 | 0.00 | 0.00 | 744.00 |
April | 246.25 | 108.09 | 138.16 | 212.05 | 120.32 | 0.00 | 0.00 | 720.00 |
May | 297.25 | 118.44 | 178.81 | 300.71 | 67.04 | 0.00 | 0.00 | 744.00 |
June | 276.02 | 99.96 | 176.06 | 315.74 | 27.65 | 0.00 | 0.00 | 720.00 |
July | 276.86 | 99.66 | 177.20 | 352.38 | 8.41 | 0.00 | 0.00 | 744.00 |
August | 312.35 | 140.92 | 171.44 | 395.61 | 16.67 | 0.00 | 0.00 | 744.00 |
September | 233.68 | 105.28 | 128.40 | 257.19 | 44.80 | 0.00 | 0.00 | 720.00 |
October | 211.10 | 95.56 | 115.54 | 196.97 | 102.66 | 0.00 | 0.00 | 744.00 |
November | 130.75 | 50.25 | 80.50 | 78.13 | 179.33 | 0.00 | 0.00 | 720.00 |
December | 102.23 | 48.25 | 53.99 | 46.85 | 244.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.30 | 89.24 | 124.06 | 202.95 | 127.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 102.23 | 41.23 | 53.99 | 41.86 | 8.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 312.35 | 140.92 | 178.81 | 395.61 | 273.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.59 | 0.00 | 33.59 | 0.20 | 214.22 | 0.00 | 0.00 | 744.00 |
February | 45.96 | 0.00 | 45.96 | 1.48 | 219.18 | 0.00 | 0.00 | 672.00 |
March | 63.75 | 0.00 | 63.75 | 14.45 | 137.56 | 0.00 | 0.00 | 744.00 |
April | 76.72 | 0.31 | 76.40 | 41.14 | 87.95 | 0.00 | 0.00 | 720.00 |
May | 102.03 | 3.72 | 98.31 | 87.94 | 43.01 | 0.00 | 0.00 | 744.00 |
June | 107.64 | 5.71 | 101.93 | 128.68 | 14.07 | 0.00 | 0.00 | 720.00 |
July | 104.48 | 4.07 | 100.41 | 151.97 | 2.59 | 0.00 | 0.00 | 744.00 |
August | 92.39 | 1.22 | 91.17 | 136.48 | 8.03 | 0.00 | 0.00 | 744.00 |
September | 69.58 | 0.04 | 69.54 | 76.64 | 27.74 | 0.00 | 0.00 | 720.00 |
October | 60.16 | 0.00 | 60.16 | 40.56 | 72.88 | 0.00 | 0.00 | 744.00 |
November | 42.20 | 0.00 | 42.20 | 7.98 | 139.39 | 0.00 | 0.00 | 720.00 |
December | 29.30 | 0.00 | 29.30 | 0.24 | 194.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 69.12 | 1.26 | 67.85 | 57.70 | 96.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.30 | 0.00 | 29.30 | 0.20 | 2.59 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.64 | 5.71 | 101.93 | 151.97 | 219.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.38 | 0.00 | 12.38 | 0.07 | 78.97 | 0.00 | 0.00 | 744.00 |
February | 16.94 | 0.00 | 16.94 | 0.55 | 80.80 | 0.00 | 0.00 | 672.00 |
March | 23.50 | 0.00 | 23.50 | 5.33 | 50.71 | 0.00 | 0.00 | 744.00 |
April | 28.28 | 0.12 | 28.17 | 15.16 | 32.42 | 0.00 | 0.00 | 720.00 |
May | 37.61 | 1.37 | 36.24 | 32.42 | 15.86 | 0.00 | 0.00 | 744.00 |
June | 39.68 | 2.11 | 37.57 | 47.44 | 5.19 | 0.00 | 0.00 | 720.00 |
July | 38.51 | 1.50 | 37.02 | 56.02 | 0.96 | 0.00 | 0.00 | 744.00 |
August | 34.06 | 0.45 | 33.61 | 50.31 | 2.96 | 0.00 | 0.00 | 744.00 |
September | 25.65 | 0.01 | 25.63 | 28.25 | 10.23 | 0.00 | 0.00 | 720.00 |
October | 22.18 | 0.00 | 22.18 | 14.95 | 26.87 | 0.00 | 0.00 | 744.00 |
November | 15.56 | 0.00 | 15.56 | 2.94 | 51.38 | 0.00 | 0.00 | 720.00 |
December | 10.80 | 0.00 | 10.80 | 0.09 | 71.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.48 | 0.47 | 25.01 | 21.27 | 35.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.80 | 0.00 | 10.80 | 0.07 | 0.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 39.68 | 2.11 | 37.57 | 56.02 | 80.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 64.32 | 42.21 | 22.11 | 56.22 | 67.97 | 0.00 | 0.00 | 744.00 |
February | 85.15 | 56.61 | 28.55 | 74.05 | 67.68 | 0.00 | 0.00 | 672.00 |
March | 75.44 | 41.54 | 33.90 | 63.69 | 47.70 | 0.00 | 0.00 | 744.00 |
April | 60.02 | 24.28 | 35.74 | 47.35 | 32.22 | 0.00 | 0.00 | 720.00 |
May | 51.55 | 10.55 | 41.00 | 44.60 | 16.83 | 0.00 | 0.00 | 744.00 |
June | 48.67 | 7.49 | 41.18 | 54.17 | 5.48 | 0.00 | 0.00 | 720.00 |
July | 50.65 | 8.54 | 42.11 | 65.69 | 0.98 | 0.00 | 0.00 | 744.00 |
August | 67.84 | 25.02 | 42.82 | 81.78 | 3.02 | 0.00 | 0.00 | 744.00 |
September | 71.61 | 35.96 | 35.65 | 79.96 | 10.09 | 0.00 | 0.00 | 720.00 |
October | 101.23 | 63.50 | 37.73 | 110.92 | 25.57 | 0.00 | 0.00 | 744.00 |
November | 70.07 | 42.04 | 28.03 | 66.87 | 45.67 | 0.00 | 0.00 | 720.00 |
December | 69.48 | 49.35 | 20.13 | 65.31 | 60.53 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.92 | 33.81 | 34.11 | 67.56 | 31.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 48.67 | 7.49 | 20.13 | 44.60 | 0.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 101.23 | 63.50 | 42.82 | 110.92 | 67.97 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 174.58 | 114.56 | 60.02 | 152.60 | 184.48 | 0.00 | 0.00 | 744.00 |
February | 231.12 | 153.64 | 77.48 | 200.99 | 183.71 | 0.00 | 0.00 | 672.00 |
March | 204.77 | 112.75 | 92.01 | 172.88 | 129.47 | 0.00 | 0.00 | 744.00 |
April | 162.92 | 65.90 | 97.02 | 128.51 | 87.46 | 0.00 | 0.00 | 720.00 |
May | 139.92 | 28.63 | 111.29 | 121.05 | 45.67 | 0.00 | 0.00 | 744.00 |
June | 132.11 | 20.33 | 111.78 | 147.02 | 14.86 | 0.00 | 0.00 | 720.00 |
July | 137.47 | 23.18 | 114.29 | 178.29 | 2.65 | 0.00 | 0.00 | 744.00 |
August | 184.12 | 67.90 | 116.22 | 221.98 | 8.20 | 0.00 | 0.00 | 744.00 |
September | 194.36 | 97.59 | 96.76 | 217.03 | 27.39 | 0.00 | 0.00 | 720.00 |
October | 274.76 | 172.35 | 102.41 | 301.06 | 69.42 | 0.00 | 0.00 | 744.00 |
November | 190.18 | 114.10 | 76.09 | 181.51 | 123.96 | 0.00 | 0.00 | 720.00 |
December | 188.59 | 133.94 | 54.65 | 177.25 | 164.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.35 | 91.76 | 92.59 | 183.37 | 86.26 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 132.11 | 20.33 | 54.65 | 121.05 | 2.65 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 274.76 | 172.35 | 116.22 | 301.06 | 184.48 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.96 | 90.54 | 47.43 | 120.65 | 138.90 | 0.00 | 0.00 | 744.00 |
February | 182.65 | 121.41 | 61.23 | 158.15 | 139.71 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 89.10 | 72.72 | 134.03 | 100.57 | 0.00 | 0.00 | 744.00 |
April | 128.75 | 52.08 | 76.67 | 96.84 | 70.09 | 0.00 | 0.00 | 720.00 |
May | 110.57 | 22.62 | 87.95 | 86.02 | 40.87 | 0.00 | 0.00 | 744.00 |
June | 104.40 | 16.07 | 88.33 | 100.20 | 19.37 | 0.00 | 0.00 | 720.00 |
July | 108.63 | 18.32 | 90.32 | 122.72 | 6.88 | 0.00 | 0.00 | 744.00 |
August | 145.51 | 53.66 | 91.85 | 158.99 | 12.22 | 0.00 | 0.00 | 744.00 |
September | 153.59 | 77.12 | 76.47 | 159.80 | 28.86 | 0.00 | 0.00 | 720.00 |
October | 217.13 | 136.20 | 80.93 | 229.23 | 59.12 | 0.00 | 0.00 | 744.00 |
November | 150.30 | 90.17 | 60.13 | 141.89 | 94.28 | 0.00 | 0.00 | 720.00 |
December | 149.03 | 105.85 | 43.19 | 139.69 | 123.60 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.69 | 72.51 | 73.17 | 137.32 | 69.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.40 | 16.07 | 43.19 | 86.02 | 6.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 217.13 | 136.20 | 91.85 | 229.23 | 139.71 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.55 | 42.11 | 60.44 | 43.92 | 284.28 | 0.00 | 0.00 | 744.00 |
February | 150.62 | 66.10 | 84.52 | 74.76 | 288.66 | 0.00 | 0.00 | 672.00 |
March | 223.75 | 103.70 | 120.05 | 160.83 | 185.60 | 0.00 | 0.00 | 744.00 |
April | 243.00 | 103.85 | 139.15 | 206.25 | 126.96 | 0.00 | 0.00 | 720.00 |
May | 283.84 | 107.88 | 175.96 | 279.28 | 72.20 | 0.00 | 0.00 | 744.00 |
June | 310.11 | 125.13 | 184.98 | 348.68 | 33.67 | 0.00 | 0.00 | 720.00 |
July | 290.14 | 109.02 | 181.13 | 360.53 | 11.98 | 0.00 | 0.00 | 744.00 |
August | 321.03 | 148.43 | 172.60 | 399.94 | 21.88 | 0.00 | 0.00 | 744.00 |
September | 228.43 | 99.73 | 128.69 | 244.86 | 52.93 | 0.00 | 0.00 | 720.00 |
October | 226.64 | 110.40 | 116.23 | 208.71 | 112.32 | 0.00 | 0.00 | 744.00 |
November | 106.73 | 31.18 | 75.55 | 51.33 | 189.54 | 0.00 | 0.00 | 720.00 |
December | 94.28 | 40.71 | 53.58 | 40.69 | 256.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.55 | 90.90 | 124.65 | 202.57 | 135.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.28 | 31.18 | 53.58 | 40.69 | 11.98 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.03 | 148.43 | 184.98 | 399.94 | 288.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.54 | 0.00 | 26.54 | 0.51 | 157.81 | 0.00 | 0.00 | 744.00 |
February | 36.32 | 0.00 | 36.32 | 1.68 | 162.95 | 0.00 | 0.00 | 672.00 |
March | 50.38 | 0.00 | 50.38 | 11.88 | 104.91 | 0.00 | 0.00 | 744.00 |
April | 60.63 | 0.25 | 60.38 | 29.42 | 69.22 | 0.00 | 0.00 | 720.00 |
May | 80.63 | 2.94 | 77.69 | 59.56 | 37.46 | 0.00 | 0.00 | 744.00 |
June | 85.06 | 4.51 | 80.55 | 85.01 | 17.42 | 0.00 | 0.00 | 720.00 |
July | 82.56 | 3.21 | 79.35 | 101.83 | 6.27 | 0.00 | 0.00 | 744.00 |
August | 73.02 | 0.96 | 72.05 | 92.05 | 11.28 | 0.00 | 0.00 | 744.00 |
September | 54.98 | 0.03 | 54.95 | 51.03 | 27.96 | 0.00 | 0.00 | 720.00 |
October | 47.55 | 0.00 | 47.55 | 28.64 | 60.19 | 0.00 | 0.00 | 744.00 |
November | 33.35 | 0.00 | 33.35 | 6.86 | 102.85 | 0.00 | 0.00 | 720.00 |
December | 23.15 | 0.00 | 23.15 | 0.44 | 141.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.62 | 1.00 | 53.62 | 39.34 | 74.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.44 | 6.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.06 | 4.51 | 80.55 | 101.83 | 162.95 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 102.55 | 42.11 | 60.44 | 46.50 | 280.55 | 0.00 | 0.00 | 744.00 |
February | 150.62 | 66.10 | 84.52 | 78.91 | 283.73 | 0.00 | 0.00 | 672.00 |
March | 223.75 | 103.70 | 120.05 | 166.14 | 182.59 | 0.00 | 0.00 | 744.00 |
April | 243.00 | 103.85 | 139.15 | 209.43 | 125.47 | 0.00 | 0.00 | 720.00 |
May | 283.84 | 107.88 | 175.96 | 280.44 | 71.76 | 0.00 | 0.00 | 744.00 |
June | 310.11 | 125.13 | 184.98 | 349.21 | 33.48 | 0.00 | 0.00 | 720.00 |
July | 290.14 | 109.02 | 181.13 | 361.19 | 11.79 | 0.00 | 0.00 | 744.00 |
August | 321.03 | 148.43 | 172.60 | 401.90 | 21.17 | 0.00 | 0.00 | 744.00 |
September | 228.43 | 99.73 | 128.69 | 248.41 | 51.02 | 0.00 | 0.00 | 720.00 |
October | 226.64 | 110.40 | 116.23 | 215.82 | 108.54 | 0.00 | 0.00 | 744.00 |
November | 106.73 | 31.18 | 75.55 | 55.79 | 185.46 | 0.00 | 0.00 | 720.00 |
December | 94.28 | 40.71 | 53.58 | 44.04 | 252.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 215.55 | 90.90 | 124.65 | 205.73 | 133.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 94.28 | 31.18 | 53.58 | 44.04 | 11.79 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.03 | 148.43 | 184.98 | 401.90 | 283.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.34 | 132.78 | 69.56 | 170.60 | 211.14 | 0.00 | 0.00 | 744.00 |
February | 267.87 | 178.07 | 89.80 | 223.86 | 212.69 | 0.00 | 0.00 | 672.00 |
March | 237.32 | 130.68 | 106.64 | 192.37 | 151.01 | 0.00 | 0.00 | 744.00 |
April | 188.82 | 76.38 | 112.44 | 141.00 | 103.12 | 0.00 | 0.00 | 720.00 |
May | 162.17 | 33.18 | 128.99 | 129.04 | 57.05 | 0.00 | 0.00 | 744.00 |
June | 153.12 | 23.56 | 129.55 | 153.35 | 23.47 | 0.00 | 0.00 | 720.00 |
July | 159.32 | 26.87 | 132.46 | 185.54 | 7.48 | 0.00 | 0.00 | 744.00 |
August | 213.40 | 78.70 | 134.70 | 237.82 | 14.93 | 0.00 | 0.00 | 744.00 |
September | 225.26 | 113.11 | 112.15 | 235.05 | 40.54 | 0.00 | 0.00 | 720.00 |
October | 318.45 | 199.75 | 118.70 | 333.09 | 87.97 | 0.00 | 0.00 | 744.00 |
November | 220.42 | 132.24 | 88.19 | 201.78 | 145.32 | 0.00 | 0.00 | 720.00 |
December | 218.57 | 155.23 | 63.34 | 197.84 | 188.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.66 | 106.35 | 107.32 | 200.11 | 103.02 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 153.12 | 23.56 | 63.34 | 129.04 | 7.48 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 318.45 | 199.75 | 134.70 | 333.09 | 212.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.79 | 0.00 | 185.79 | 0.17 | 1338.79 | 0.00 | 0.00 | 744.00 |
February | 254.25 | 0.00 | 254.25 | 3.16 | 1358.47 | 0.00 | 0.00 | 672.00 |
March | 352.66 | 0.01 | 352.65 | 54.05 | 905.71 | 0.00 | 0.00 | 744.00 |
April | 424.37 | 1.73 | 422.64 | 177.72 | 609.40 | 0.00 | 0.00 | 720.00 |
May | 564.40 | 20.60 | 543.80 | 402.48 | 323.11 | 0.00 | 0.00 | 744.00 |
June | 595.42 | 31.60 | 563.82 | 614.95 | 144.98 | 0.00 | 0.00 | 720.00 |
July | 577.93 | 22.50 | 555.43 | 722.46 | 58.75 | 0.00 | 0.00 | 744.00 |
August | 511.09 | 6.75 | 504.35 | 649.33 | 93.67 | 0.00 | 0.00 | 744.00 |
September | 384.87 | 0.22 | 384.65 | 360.46 | 238.76 | 0.00 | 0.00 | 720.00 |
October | 332.81 | 0.00 | 332.81 | 181.94 | 511.85 | 0.00 | 0.00 | 744.00 |
November | 233.43 | 0.00 | 233.43 | 27.68 | 920.94 | 0.00 | 0.00 | 720.00 |
December | 162.06 | 0.00 | 162.06 | 0.45 | 1232.43 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 382.33 | 6.99 | 375.34 | 268.08 | 640.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 162.06 | 0.00 | 162.06 | 0.17 | 58.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 595.42 | 31.60 | 563.82 | 722.46 | 1358.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 185.79 | 0.00 | 185.79 | 0.07 | 1380.77 | 0.00 | 0.00 | 744.00 |
February | 254.25 | 0.00 | 254.25 | 2.13 | 1399.00 | 0.00 | 0.00 | 672.00 |
March | 352.66 | 0.01 | 352.65 | 47.53 | 936.61 | 0.00 | 0.00 | 744.00 |
April | 424.37 | 1.73 | 422.64 | 165.34 | 632.76 | 0.00 | 0.00 | 720.00 |
May | 564.40 | 20.60 | 543.80 | 383.33 | 337.83 | 0.00 | 0.00 | 744.00 |
June | 595.42 | 31.60 | 563.82 | 595.23 | 155.72 | 0.00 | 0.00 | 720.00 |
July | 577.93 | 22.50 | 555.43 | 703.74 | 66.87 | 0.00 | 0.00 | 744.00 |
August | 511.09 | 6.75 | 504.35 | 631.48 | 101.98 | 0.00 | 0.00 | 744.00 |
September | 384.87 | 0.22 | 384.65 | 344.86 | 254.93 | 0.00 | 0.00 | 720.00 |
October | 332.81 | 0.00 | 332.81 | 170.52 | 532.98 | 0.00 | 0.00 | 744.00 |
November | 233.43 | 0.00 | 233.43 | 23.90 | 955.02 | 0.00 | 0.00 | 720.00 |
December | 162.06 | 0.00 | 162.06 | 0.28 | 1271.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 382.33 | 6.99 | 375.34 | 257.49 | 664.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 162.06 | 0.00 | 162.06 | 0.07 | 66.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 595.42 | 31.60 | 563.82 | 703.74 | 1399.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.54 | 0.00 | 26.54 | 0.22 | 178.42 | 0.00 | 0.00 | 744.00 |
February | 36.32 | 0.00 | 36.32 | 1.15 | 181.65 | 0.00 | 0.00 | 672.00 |
March | 50.38 | 0.00 | 50.38 | 10.43 | 119.64 | 0.00 | 0.00 | 744.00 |
April | 60.63 | 0.25 | 60.38 | 32.35 | 81.04 | 0.00 | 0.00 | 720.00 |
May | 80.63 | 2.94 | 77.69 | 70.59 | 43.60 | 0.00 | 0.00 | 744.00 |
June | 85.06 | 4.51 | 80.55 | 105.09 | 18.68 | 0.00 | 0.00 | 720.00 |
July | 82.56 | 3.21 | 79.35 | 124.04 | 6.63 | 0.00 | 0.00 | 744.00 |
August | 73.02 | 0.96 | 72.05 | 111.74 | 10.98 | 0.00 | 0.00 | 744.00 |
September | 54.98 | 0.03 | 54.95 | 64.49 | 29.24 | 0.00 | 0.00 | 720.00 |
October | 47.55 | 0.00 | 47.55 | 32.87 | 65.79 | 0.00 | 0.00 | 744.00 |
November | 33.35 | 0.00 | 33.35 | 5.98 | 121.08 | 0.00 | 0.00 | 720.00 |
December | 23.15 | 0.00 | 23.15 | 0.23 | 162.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 54.62 | 1.00 | 53.62 | 46.91 | 84.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.15 | 0.00 | 23.15 | 0.22 | 6.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.06 | 4.51 | 80.55 | 124.04 | 181.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 206.52 | 82.52 | 123.99 | 81.73 | 622.81 | 0.00 | 0.00 | 744.00 |
February | 320.61 | 149.30 | 171.30 | 160.77 | 606.34 | 0.00 | 0.00 | 672.00 |
March | 411.70 | 174.97 | 236.73 | 288.65 | 425.44 | 0.00 | 0.00 | 744.00 |
April | 492.87 | 216.34 | 276.53 | 435.52 | 290.31 | 0.00 | 0.00 | 720.00 |
May | 594.95 | 237.06 | 357.89 | 635.37 | 164.41 | 0.00 | 0.00 | 744.00 |
June | 552.45 | 200.07 | 352.38 | 690.26 | 72.06 | 0.00 | 0.00 | 720.00 |
July | 554.14 | 199.47 | 354.67 | 775.24 | 25.99 | 0.00 | 0.00 | 744.00 |
August | 625.17 | 282.04 | 343.13 | 857.62 | 41.75 | 0.00 | 0.00 | 744.00 |
September | 467.70 | 210.72 | 256.99 | 560.57 | 107.64 | 0.00 | 0.00 | 720.00 |
October | 422.51 | 191.26 | 231.25 | 411.29 | 237.13 | 0.00 | 0.00 | 744.00 |
November | 261.70 | 100.57 | 161.12 | 154.61 | 419.28 | 0.00 | 0.00 | 720.00 |
December | 204.62 | 96.56 | 108.05 | 92.05 | 559.16 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 426.92 | 178.61 | 248.31 | 430.49 | 295.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 204.62 | 82.52 | 108.05 | 81.73 | 25.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 625.17 | 282.04 | 357.89 | 857.62 | 622.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.96 | 90.54 | 47.43 | 120.30 | 155.34 | 0.00 | 0.00 | 744.00 |
February | 182.65 | 121.41 | 61.23 | 158.22 | 152.68 | 0.00 | 0.00 | 672.00 |
March | 161.82 | 89.10 | 72.72 | 135.76 | 113.05 | 0.00 | 0.00 | 744.00 |
April | 128.75 | 52.08 | 76.67 | 100.94 | 81.18 | 0.00 | 0.00 | 720.00 |
May | 110.57 | 22.62 | 87.95 | 96.24 | 46.18 | 0.00 | 0.00 | 744.00 |
June | 104.40 | 16.07 | 88.33 | 118.61 | 20.05 | 0.00 | 0.00 | 720.00 |
July | 108.63 | 18.32 | 90.32 | 143.82 | 7.02 | 0.00 | 0.00 | 744.00 |
August | 145.51 | 53.66 | 91.85 | 178.88 | 11.35 | 0.00 | 0.00 | 744.00 |
September | 153.59 | 77.12 | 76.47 | 175.39 | 29.35 | 0.00 | 0.00 | 720.00 |
October | 217.13 | 136.20 | 80.93 | 239.40 | 63.87 | 0.00 | 0.00 | 744.00 |
November | 150.30 | 90.17 | 60.13 | 143.14 | 108.34 | 0.00 | 0.00 | 720.00 |
December | 149.03 | 105.85 | 43.19 | 139.78 | 138.86 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.69 | 72.51 | 73.17 | 145.90 | 76.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 104.40 | 16.07 | 43.19 | 96.24 | 7.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 217.13 | 136.20 | 91.85 | 239.40 | 155.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 33.61 | 0.00 | 33.61 | 0.10 | 220.07 | 0.00 | 0.00 | 744.00 |
February | 46.00 | 0.00 | 46.00 | 1.09 | 225.07 | 0.00 | 0.00 | 672.00 |
March | 63.81 | 0.00 | 63.80 | 12.43 | 142.26 | 0.00 | 0.00 | 744.00 |
April | 76.78 | 0.31 | 76.47 | 37.88 | 91.68 | 0.00 | 0.00 | 720.00 |
May | 102.12 | 3.73 | 98.39 | 82.49 | 45.99 | 0.00 | 0.00 | 744.00 |
June | 107.73 | 5.72 | 102.01 | 120.33 | 17.38 | 0.00 | 0.00 | 720.00 |
July | 104.56 | 4.07 | 100.49 | 138.94 | 5.07 | 0.00 | 0.00 | 744.00 |
August | 92.47 | 1.22 | 91.25 | 124.12 | 11.13 | 0.00 | 0.00 | 744.00 |
September | 69.63 | 0.04 | 69.59 | 70.72 | 31.27 | 0.00 | 0.00 | 720.00 |
October | 60.21 | 0.00 | 60.21 | 36.53 | 76.87 | 0.00 | 0.00 | 744.00 |
November | 42.23 | 0.00 | 42.23 | 6.73 | 144.29 | 0.00 | 0.00 | 720.00 |
December | 29.32 | 0.00 | 29.32 | 0.17 | 199.87 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 69.17 | 1.26 | 67.91 | 52.98 | 100.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 29.32 | 0.00 | 29.32 | 0.10 | 5.07 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 107.73 | 5.72 | 102.01 | 138.94 | 225.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.07 | 0.00 | 30.07 | 0.09 | 196.90 | 0.00 | 0.00 | 744.00 |
February | 41.16 | 0.00 | 41.16 | 0.98 | 201.37 | 0.00 | 0.00 | 672.00 |
March | 57.09 | 0.00 | 57.09 | 11.12 | 127.28 | 0.00 | 0.00 | 744.00 |
April | 68.70 | 0.28 | 68.42 | 33.89 | 82.02 | 0.00 | 0.00 | 720.00 |
May | 91.36 | 3.33 | 88.03 | 73.80 | 41.15 | 0.00 | 0.00 | 744.00 |
June | 96.38 | 5.12 | 91.27 | 107.66 | 15.55 | 0.00 | 0.00 | 720.00 |
July | 93.55 | 3.64 | 89.91 | 124.31 | 4.54 | 0.00 | 0.00 | 744.00 |
August | 82.73 | 1.09 | 81.64 | 111.05 | 9.96 | 0.00 | 0.00 | 744.00 |
September | 62.30 | 0.04 | 62.27 | 63.28 | 27.97 | 0.00 | 0.00 | 720.00 |
October | 53.87 | 0.00 | 53.87 | 32.68 | 68.78 | 0.00 | 0.00 | 744.00 |
November | 37.79 | 0.00 | 37.79 | 6.02 | 129.09 | 0.00 | 0.00 | 720.00 |
December | 26.23 | 0.00 | 26.23 | 0.15 | 178.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.89 | 1.13 | 60.76 | 47.40 | 89.67 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 26.23 | 0.00 | 26.23 | 0.09 | 4.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 96.38 | 5.12 | 91.27 | 124.31 | 201.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.06 | 337.99 | 177.07 | 442.53 | 557.03 | 0.00 | 0.00 | 744.00 |
February | 681.87 | 453.28 | 228.60 | 583.28 | 553.19 | 0.00 | 0.00 | 672.00 |
March | 604.12 | 332.65 | 271.47 | 500.17 | 394.37 | 0.00 | 0.00 | 744.00 |
April | 480.65 | 194.43 | 286.22 | 368.55 | 269.60 | 0.00 | 0.00 | 720.00 |
May | 412.80 | 84.46 | 328.34 | 341.84 | 144.93 | 0.00 | 0.00 | 744.00 |
June | 389.76 | 59.98 | 329.78 | 409.54 | 54.73 | 0.00 | 0.00 | 720.00 |
July | 405.57 | 68.39 | 337.18 | 487.87 | 15.41 | 0.00 | 0.00 | 744.00 |
August | 543.22 | 200.33 | 342.89 | 618.77 | 33.83 | 0.00 | 0.00 | 744.00 |
September | 573.40 | 287.93 | 285.48 | 621.62 | 91.61 | 0.00 | 0.00 | 720.00 |
October | 810.62 | 508.47 | 302.15 | 871.81 | 215.83 | 0.00 | 0.00 | 744.00 |
November | 561.10 | 336.61 | 224.48 | 525.54 | 376.93 | 0.00 | 0.00 | 720.00 |
December | 556.39 | 395.15 | 161.23 | 514.62 | 496.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 543.89 | 270.72 | 273.18 | 523.82 | 265.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 389.76 | 59.98 | 161.23 | 341.84 | 15.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 810.62 | 508.47 | 342.89 | 871.81 | 557.03 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187124E+10 | 0.122794E+10 | 0.643298E+09 | 0.162716E+10 | 0.185701E+10 |
February | 0.223753E+10 | 0.148740E+10 | 0.750132E+09 | 0.192811E+10 | 0.167929E+10 |
March | 0.219478E+10 | 0.120852E+10 | 0.986255E+09 | 0.181507E+10 | 0.133045E+10 |
April | 0.168989E+10 | 0.683582E+09 | 0.100631E+10 | 0.128345E+10 | 0.886442E+09 |
May | 0.149971E+10 | 0.306852E+09 | 0.119286E+10 | 0.123118E+10 | 0.499404E+09 |
June | 0.137034E+10 | 0.210887E+09 | 0.115945E+10 | 0.140890E+10 | 0.192091E+09 |
July | 0.147343E+10 | 0.248468E+09 | 0.122497E+10 | 0.171725E+10 | 60366130.01 |
August | 0.197353E+10 | 0.727800E+09 | 0.124573E+10 | 0.215082E+10 | 0.140095E+09 |
September | 0.201599E+10 | 0.101231E+10 | 0.100368E+10 | 0.212209E+10 | 0.339286E+09 |
October | 0.294500E+10 | 0.184729E+10 | 0.109771E+10 | 0.309942E+10 | 0.804048E+09 |
November | 0.197273E+10 | 0.118348E+10 | 0.789250E+09 | 0.184389E+10 | 0.124617E+10 |
December | 0.202137E+10 | 0.143560E+10 | 0.585767E+09 | 0.187324E+10 | 0.167137E+10 |
Annual Sum or Average | 0.232656E+11 | 0.115801E+11 | 0.116854E+11 | 0.221006E+11 | 0.107060E+11 |
Minimum of Months | 0.137034E+10 | 0.210887E+09 | 0.585767E+09 | 0.123118E+10 | 60366130.01 |
Maximum of Months | 0.294500E+10 | 0.184729E+10 | 0.124573E+10 | 0.309942E+10 | 0.185701E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.526929E+10 | 0.345781E+10 | 0.181148E+10 | 0.452945E+10 | 0.538007E+10 |
February | 0.630074E+10 | 0.418842E+10 | 0.211232E+10 | 0.536560E+10 | 0.486730E+10 |
March | 0.618035E+10 | 0.340312E+10 | 0.277723E+10 | 0.504255E+10 | 0.397541E+10 |
April | 0.475863E+10 | 0.192492E+10 | 0.283371E+10 | 0.353504E+10 | 0.272023E+10 |
May | 0.422310E+10 | 0.864076E+09 | 0.335902E+10 | 0.335469E+10 | 0.160160E+10 |
June | 0.385879E+10 | 0.593843E+09 | 0.326494E+10 | 0.385443E+10 | 0.679080E+09 |
July | 0.414909E+10 | 0.699668E+09 | 0.344942E+10 | 0.470546E+10 | 0.269133E+09 |
August | 0.555733E+10 | 0.204944E+10 | 0.350789E+10 | 0.595115E+10 | 0.502065E+09 |
September | 0.567690E+10 | 0.285060E+10 | 0.282631E+10 | 0.588620E+10 | 0.113726E+10 |
October | 0.829292E+10 | 0.520184E+10 | 0.309108E+10 | 0.862733E+10 | 0.251694E+10 |
November | 0.555507E+10 | 0.333260E+10 | 0.222247E+10 | 0.510950E+10 | 0.373366E+10 |
December | 0.569205E+10 | 0.404257E+10 | 0.164948E+10 | 0.521129E+10 | 0.489793E+10 |
Annual Sum or Average | 0.655143E+11 | 0.326089E+11 | 0.329054E+11 | 0.611727E+11 | 0.322807E+11 |
Minimum of Months | 0.385879E+10 | 0.593843E+09 | 0.164948E+10 | 0.335469E+10 | 0.269133E+09 |
Maximum of Months | 0.829292E+10 | 0.520184E+10 | 0.350789E+10 | 0.862733E+10 | 0.538007E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.684511E+10 | 0.449189E+10 | 0.235322E+10 | 0.598417E+10 | 0.734533E+10 |
February | 0.818502E+10 | 0.544100E+10 | 0.274403E+10 | 0.710969E+10 | 0.659774E+10 |
March | 0.802863E+10 | 0.442085E+10 | 0.360778E+10 | 0.669335E+10 | 0.540104E+10 |
April | 0.618173E+10 | 0.250058E+10 | 0.368115E+10 | 0.469480E+10 | 0.370963E+10 |
May | 0.548604E+10 | 0.112248E+10 | 0.436356E+10 | 0.447364E+10 | 0.216279E+10 |
June | 0.501278E+10 | 0.771436E+09 | 0.424135E+10 | 0.518715E+10 | 0.883140E+09 |
July | 0.538991E+10 | 0.908909E+09 | 0.448100E+10 | 0.637177E+10 | 0.324531E+09 |
August | 0.721928E+10 | 0.266233E+10 | 0.455695E+10 | 0.806126E+10 | 0.610817E+09 |
September | 0.737462E+10 | 0.370309E+10 | 0.367153E+10 | 0.790101E+10 | 0.145733E+10 |
October | 0.107730E+11 | 0.675749E+10 | 0.401548E+10 | 0.115122E+11 | 0.328926E+10 |
November | 0.721636E+10 | 0.432923E+10 | 0.288712E+10 | 0.675695E+10 | 0.509098E+10 |
December | 0.739430E+10 | 0.525153E+10 | 0.214277E+10 | 0.688522E+10 | 0.668793E+10 |
Annual Sum or Average | 0.851068E+11 | 0.423608E+11 | 0.427459E+11 | 0.816313E+11 | 0.435605E+11 |
Minimum of Months | 0.501278E+10 | 0.771436E+09 | 0.214277E+10 | 0.447364E+10 | 0.324531E+09 |
Maximum of Months | 0.107730E+11 | 0.675749E+10 | 0.455695E+10 | 0.115122E+11 | 0.734533E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369222E+09 | 0.242291E+09 | 0.126932E+09 | 0.324206E+09 | 0.372157E+09 |
February | 0.441497E+09 | 0.293485E+09 | 0.148012E+09 | 0.383958E+09 | 0.337770E+09 |
March | 0.433061E+09 | 0.238459E+09 | 0.194602E+09 | 0.360750E+09 | 0.268454E+09 |
April | 0.333440E+09 | 0.134881E+09 | 0.198560E+09 | 0.253140E+09 | 0.179970E+09 |
May | 0.295915E+09 | 60546334.37 | 0.235369E+09 | 0.235285E+09 | 0.105654E+09 |
June | 0.270387E+09 | 41610922.52 | 0.228776E+09 | 0.266207E+09 | 44490098.26 |
July | 0.290729E+09 | 49026188.83 | 0.241703E+09 | 0.335267E+09 | 14617740.82 |
August | 0.389405E+09 | 0.143605E+09 | 0.245800E+09 | 0.430924E+09 | 28715910.62 |
September | 0.397784E+09 | 0.199743E+09 | 0.198041E+09 | 0.419001E+09 | 69706398.30 |
October | 0.581090E+09 | 0.364496E+09 | 0.216594E+09 | 0.618110E+09 | 0.155598E+09 |
November | 0.389247E+09 | 0.233517E+09 | 0.155730E+09 | 0.369035E+09 | 0.245049E+09 |
December | 0.398845E+09 | 0.283265E+09 | 0.115580E+09 | 0.374991E+09 | 0.331857E+09 |
Annual Sum or Average | 0.459062E+10 | 0.228493E+10 | 0.230570E+10 | 0.437087E+10 | 0.215404E+10 |
Minimum of Months | 0.270387E+09 | 41610922.52 | 0.115580E+09 | 0.235285E+09 | 14617740.82 |
Maximum of Months | 0.581090E+09 | 0.364496E+09 | 0.245800E+09 | 0.618110E+09 | 0.372157E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274439E+09 | 0.112682E+09 | 0.161757E+09 | 0.117785E+09 | 0.761270E+09 |
February | 0.364088E+09 | 0.159789E+09 | 0.204299E+09 | 0.182012E+09 | 0.696983E+09 |
March | 0.598796E+09 | 0.277523E+09 | 0.321273E+09 | 0.434811E+09 | 0.496161E+09 |
April | 0.629334E+09 | 0.268953E+09 | 0.360381E+09 | 0.541305E+09 | 0.327194E+09 |
May | 0.759606E+09 | 0.288709E+09 | 0.470897E+09 | 0.761051E+09 | 0.188210E+09 |
June | 0.803149E+09 | 0.324077E+09 | 0.479072E+09 | 0.920553E+09 | 78528618.75 |
July | 0.776478E+09 | 0.291750E+09 | 0.484729E+09 | 0.981523E+09 | 25922925.91 |
August | 0.859147E+09 | 0.397227E+09 | 0.461921E+09 | 0.108449E+10 | 52073045.39 |
September | 0.591596E+09 | 0.258296E+09 | 0.333300E+09 | 0.645443E+09 | 0.128891E+09 |
October | 0.606525E+09 | 0.295462E+09 | 0.311063E+09 | 0.565976E+09 | 0.296267E+09 |
November | 0.276418E+09 | 80756499.71 | 0.195662E+09 | 0.133767E+09 | 0.492408E+09 |
December | 0.252323E+09 | 0.108939E+09 | 0.143384E+09 | 0.108940E+09 | 0.689638E+09 |
Annual Sum or Average | 0.679190E+10 | 0.286416E+10 | 0.392774E+10 | 0.647765E+10 | 0.423355E+10 |
Minimum of Months | 0.252323E+09 | 80756499.71 | 0.143384E+09 | 0.108940E+09 | 25922925.91 |
Maximum of Months | 0.859147E+09 | 0.397227E+09 | 0.484729E+09 | 0.108449E+10 | 0.761270E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71032979.27 | 0.00 | 71032979.27 | 1253635.36 | 0.422969E+09 |
February | 87798621.79 | 0.00 | 87798621.79 | 3995929.10 | 0.393616E+09 |
March | 0.134831E+09 | 2680.57 | 0.134829E+09 | 32151474.22 | 0.280510E+09 |
April | 0.157017E+09 | 640006.32 | 0.156377E+09 | 78257352.64 | 0.178359E+09 |
May | 0.215787E+09 | 7874871.82 | 0.207913E+09 | 0.165692E+09 | 97154337.65 |
June | 0.220304E+09 | 11691944.98 | 0.208612E+09 | 0.228267E+09 | 40258836.73 |
July | 0.220959E+09 | 8600659.13 | 0.212359E+09 | 0.280771E+09 | 13339267.19 |
August | 0.195406E+09 | 2579465.32 | 0.192826E+09 | 0.252767E+09 | 26450930.43 |
September | 0.142400E+09 | 80917.76 | 0.142319E+09 | 0.137025E+09 | 67629190.23 |
October | 0.127242E+09 | 0.00 | 0.127242E+09 | 78628802.35 | 0.159003E+09 |
November | 86368820.55 | 0.00 | 86368820.55 | 17639066.67 | 0.267969E+09 |
December | 61959633.27 | 0.00 | 61959633.27 | 1076435.90 | 0.381694E+09 |
Annual Sum or Average | 0.172111E+10 | 31470545.90 | 0.168964E+10 | 0.127752E+10 | 0.232895E+10 |
Minimum of Months | 61959633.27 | 0.00 | 61959633.27 | 1076435.90 | 13339267.19 |
Maximum of Months | 0.220959E+09 | 11691944.98 | 0.212359E+09 | 0.280771E+09 | 0.422969E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274439E+09 | 0.112682E+09 | 0.161757E+09 | 0.124561E+09 | 0.751014E+09 |
February | 0.364088E+09 | 0.159789E+09 | 0.204299E+09 | 0.191524E+09 | 0.684783E+09 |
March | 0.598796E+09 | 0.277523E+09 | 0.321273E+09 | 0.447896E+09 | 0.488651E+09 |
April | 0.629334E+09 | 0.268953E+09 | 0.360381E+09 | 0.549026E+09 | 0.323816E+09 |
May | 0.759606E+09 | 0.288709E+09 | 0.470897E+09 | 0.764366E+09 | 0.187026E+09 |
June | 0.803149E+09 | 0.324077E+09 | 0.479072E+09 | 0.922126E+09 | 77930922.26 |
July | 0.776478E+09 | 0.291750E+09 | 0.484729E+09 | 0.983401E+09 | 25438187.05 |
August | 0.859147E+09 | 0.397227E+09 | 0.461921E+09 | 0.108981E+10 | 50267253.70 |
September | 0.591596E+09 | 0.258296E+09 | 0.333300E+09 | 0.654925E+09 | 0.124542E+09 |
October | 0.606525E+09 | 0.295462E+09 | 0.311063E+09 | 0.584161E+09 | 0.287413E+09 |
November | 0.276418E+09 | 80756499.71 | 0.195662E+09 | 0.144467E+09 | 0.482362E+09 |
December | 0.252323E+09 | 0.108939E+09 | 0.143384E+09 | 0.117303E+09 | 0.676852E+09 |
Annual Sum or Average | 0.679190E+10 | 0.286416E+10 | 0.392774E+10 | 0.657357E+10 | 0.416009E+10 |
Minimum of Months | 0.252323E+09 | 80756499.71 | 0.143384E+09 | 0.117303E+09 | 25438187.05 |
Maximum of Months | 0.859147E+09 | 0.397227E+09 | 0.484729E+09 | 0.108981E+10 | 0.751014E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.295319E+09 | 0.193794E+09 | 0.101525E+09 | 0.257349E+09 | 0.293031E+09 |
February | 0.353127E+09 | 0.234741E+09 | 0.118386E+09 | 0.301588E+09 | 0.277382E+09 |
March | 0.346380E+09 | 0.190729E+09 | 0.155651E+09 | 0.284778E+09 | 0.227260E+09 |
April | 0.266699E+09 | 0.107883E+09 | 0.158816E+09 | 0.199452E+09 | 0.155499E+09 |
May | 0.236685E+09 | 48427436.58 | 0.188257E+09 | 0.183244E+09 | 96967757.43 |
June | 0.216267E+09 | 33282119.10 | 0.182985E+09 | 0.213096E+09 | 41669400.76 |
July | 0.232537E+09 | 39213152.63 | 0.193324E+09 | 0.265976E+09 | 15901967.92 |
August | 0.311462E+09 | 0.114861E+09 | 0.196601E+09 | 0.341802E+09 | 27361583.57 |
September | 0.318164E+09 | 0.159763E+09 | 0.158401E+09 | 0.331106E+09 | 67160459.05 |
October | 0.464780E+09 | 0.291539E+09 | 0.173240E+09 | 0.486406E+09 | 0.145534E+09 |
November | 0.311336E+09 | 0.186777E+09 | 0.124559E+09 | 0.285978E+09 | 0.214970E+09 |
December | 0.319013E+09 | 0.226567E+09 | 92445660.92 | 0.293897E+09 | 0.273323E+09 |
Annual Sum or Average | 0.367177E+10 | 0.182758E+10 | 0.184419E+10 | 0.344467E+10 | 0.183606E+10 |
Minimum of Months | 0.216267E+09 | 33282119.10 | 92445660.92 | 0.183244E+09 | 15901967.92 |
Maximum of Months | 0.464780E+09 | 0.291539E+09 | 0.196601E+09 | 0.486406E+09 | 0.293031E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 56833916.07 | 0.00 | 56833916.07 | 540713.45 | 0.353751E+09 |
February | 70248208.00 | 0.00 | 70248208.00 | 2666890.76 | 0.325831E+09 |
March | 0.107879E+09 | 2144.74 | 0.107877E+09 | 25377738.12 | 0.229852E+09 |
April | 0.125630E+09 | 512072.92 | 0.125118E+09 | 65495615.05 | 0.144957E+09 |
May | 0.172653E+09 | 6300732.54 | 0.166352E+09 | 0.140889E+09 | 76464430.09 |
June | 0.176266E+09 | 9354795.85 | 0.166911E+09 | 0.195786E+09 | 28919991.15 |
July | 0.176791E+09 | 6881439.35 | 0.169909E+09 | 0.236943E+09 | 8596596.83 |
August | 0.156345E+09 | 2063845.80 | 0.154281E+09 | 0.216070E+09 | 17754886.54 |
September | 0.113935E+09 | 64742.79 | 0.113870E+09 | 0.117486E+09 | 50981188.74 |
October | 0.101807E+09 | 0.00 | 0.101807E+09 | 67378220.37 | 0.124787E+09 |
November | 69104215.38 | 0.00 | 69104215.38 | 13198621.23 | 0.225057E+09 |
December | 49574277.10 | 0.00 | 49574277.10 | 550345.09 | 0.320333E+09 |
Annual Sum or Average | 0.137707E+10 | 25179774.00 | 0.135189E+10 | 0.108238E+10 | 0.190729E+10 |
Minimum of Months | 49574277.10 | 0.00 | 49574277.10 | 540713.45 | 8596596.83 |
Maximum of Months | 0.176791E+09 | 9354795.85 | 0.169909E+09 | 0.236943E+09 | 0.353751E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276359E+09 | 0.110431E+09 | 0.165927E+09 | 0.108737E+09 | 0.746982E+09 |
February | 0.387514E+09 | 0.180460E+09 | 0.207053E+09 | 0.192863E+09 | 0.670975E+09 |
March | 0.550936E+09 | 0.234143E+09 | 0.316792E+09 | 0.379866E+09 | 0.497555E+09 |
April | 0.638279E+09 | 0.280168E+09 | 0.358111E+09 | 0.542573E+09 | 0.315660E+09 |
May | 0.796159E+09 | 0.317237E+09 | 0.478921E+09 | 0.802426E+09 | 0.180819E+09 |
June | 0.715441E+09 | 0.259097E+09 | 0.456344E+09 | 0.816843E+09 | 72195561.94 |
July | 0.741547E+09 | 0.266926E+09 | 0.474621E+09 | 0.941934E+09 | 22958164.74 |
August | 0.836605E+09 | 0.377432E+09 | 0.459174E+09 | 0.105451E+10 | 46290320.22 |
September | 0.605692E+09 | 0.272886E+09 | 0.332806E+09 | 0.658178E+09 | 0.120564E+09 |
October | 0.565403E+09 | 0.255942E+09 | 0.309461E+09 | 0.510609E+09 | 0.285723E+09 |
November | 0.338905E+09 | 0.130247E+09 | 0.208658E+09 | 0.193819E+09 | 0.476409E+09 |
December | 0.273816E+09 | 0.129221E+09 | 0.144595E+09 | 0.121540E+09 | 0.671685E+09 |
Annual Sum or Average | 0.672665E+10 | 0.281419E+10 | 0.391246E+10 | 0.632390E+10 | 0.410782E+10 |
Minimum of Months | 0.273816E+09 | 0.110431E+09 | 0.144595E+09 | 0.108737E+09 | 22958164.74 |
Maximum of Months | 0.836605E+09 | 0.377432E+09 | 0.478921E+09 | 0.105451E+10 | 0.746982E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369222E+09 | 0.242291E+09 | 0.126932E+09 | 0.323300E+09 | 0.371639E+09 |
February | 0.441497E+09 | 0.293485E+09 | 0.148012E+09 | 0.382024E+09 | 0.336982E+09 |
March | 0.433061E+09 | 0.238459E+09 | 0.194602E+09 | 0.358439E+09 | 0.265867E+09 |
April | 0.333440E+09 | 0.134881E+09 | 0.198560E+09 | 0.250696E+09 | 0.178107E+09 |
May | 0.295915E+09 | 60546334.37 | 0.235369E+09 | 0.232196E+09 | 0.102724E+09 |
June | 0.270387E+09 | 41610922.52 | 0.228776E+09 | 0.267419E+09 | 40330372.54 |
July | 0.290729E+09 | 49026188.83 | 0.241703E+09 | 0.334934E+09 | 12481418.92 |
August | 0.389405E+09 | 0.143605E+09 | 0.245800E+09 | 0.429369E+09 | 25840598.43 |
September | 0.397784E+09 | 0.199743E+09 | 0.198041E+09 | 0.417824E+09 | 66680022.34 |
October | 0.581090E+09 | 0.364496E+09 | 0.216594E+09 | 0.617094E+09 | 0.152374E+09 |
November | 0.389247E+09 | 0.233517E+09 | 0.155730E+09 | 0.366970E+09 | 0.245230E+09 |
December | 0.398845E+09 | 0.283265E+09 | 0.115580E+09 | 0.373783E+09 | 0.331474E+09 |
Annual Sum or Average | 0.459062E+10 | 0.228493E+10 | 0.230570E+10 | 0.435405E+10 | 0.212973E+10 |
Minimum of Months | 0.270387E+09 | 41610922.52 | 0.115580E+09 | 0.232196E+09 | 12481418.92 |
Maximum of Months | 0.581090E+09 | 0.364496E+09 | 0.245800E+09 | 0.617094E+09 | 0.371639E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71032979.27 | 0.00 | 71032979.27 | 1036653.01 | 0.423121E+09 |
February | 87798621.79 | 0.00 | 87798621.79 | 3625850.11 | 0.394155E+09 |
March | 0.134831E+09 | 2680.57 | 0.134829E+09 | 30502749.57 | 0.278540E+09 |
April | 0.157017E+09 | 640006.32 | 0.156377E+09 | 76155073.00 | 0.177029E+09 |
May | 0.215787E+09 | 7874871.82 | 0.207913E+09 | 0.163174E+09 | 94982474.38 |
June | 0.220304E+09 | 11691944.98 | 0.208612E+09 | 0.230421E+09 | 37110318.81 |
July | 0.220959E+09 | 8600659.13 | 0.212359E+09 | 0.280857E+09 | 11668896.32 |
August | 0.195406E+09 | 2579465.32 | 0.192826E+09 | 0.251405E+09 | 23998611.89 |
September | 0.142400E+09 | 80917.76 | 0.142319E+09 | 0.135547E+09 | 64904812.29 |
October | 0.127242E+09 | 0.00 | 0.127242E+09 | 77190398.93 | 0.154926E+09 |
November | 86368820.55 | 0.00 | 86368820.55 | 16519777.43 | 0.269105E+09 |
December | 61959633.27 | 0.00 | 61959633.27 | 869257.03 | 0.382009E+09 |
Annual Sum or Average | 0.172111E+10 | 31470545.90 | 0.168964E+10 | 0.126730E+10 | 0.231155E+10 |
Minimum of Months | 61959633.27 | 0.00 | 61959633.27 | 869257.03 | 11668896.32 |
Maximum of Months | 0.220959E+09 | 11691944.98 | 0.212359E+09 | 0.280857E+09 | 0.423121E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276359E+09 | 0.110431E+09 | 0.165927E+09 | 0.112120E+09 | 0.733544E+09 |
February | 0.387514E+09 | 0.180460E+09 | 0.207053E+09 | 0.198251E+09 | 0.654453E+09 |
March | 0.550936E+09 | 0.234143E+09 | 0.316792E+09 | 0.390754E+09 | 0.487748E+09 |
April | 0.638279E+09 | 0.280168E+09 | 0.358111E+09 | 0.549638E+09 | 0.311881E+09 |
May | 0.796159E+09 | 0.317237E+09 | 0.478921E+09 | 0.805427E+09 | 0.179563E+09 |
June | 0.715441E+09 | 0.259097E+09 | 0.456344E+09 | 0.818391E+09 | 71679342.97 |
July | 0.741547E+09 | 0.266926E+09 | 0.474621E+09 | 0.943823E+09 | 22534077.31 |
August | 0.836605E+09 | 0.377432E+09 | 0.459174E+09 | 0.105959E+10 | 44640502.31 |
September | 0.605692E+09 | 0.272886E+09 | 0.332806E+09 | 0.666644E+09 | 0.116125E+09 |
October | 0.565403E+09 | 0.255942E+09 | 0.309461E+09 | 0.527557E+09 | 0.274969E+09 |
November | 0.338905E+09 | 0.130247E+09 | 0.208658E+09 | 0.202515E+09 | 0.464823E+09 |
December | 0.273816E+09 | 0.129221E+09 | 0.144595E+09 | 0.125486E+09 | 0.654578E+09 |
Annual Sum or Average | 0.672665E+10 | 0.281419E+10 | 0.391246E+10 | 0.640020E+10 | 0.401654E+10 |
Minimum of Months | 0.273816E+09 | 0.110431E+09 | 0.144595E+09 | 0.112120E+09 | 22534077.31 |
Maximum of Months | 0.836605E+09 | 0.377432E+09 | 0.478921E+09 | 0.105959E+10 | 0.733544E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 89958786.31 | 0.00 | 89958786.31 | 527862.85 | 0.573766E+09 |
February | 0.111191E+09 | 0.00 | 0.111191E+09 | 3581586.77 | 0.530239E+09 |
March | 0.170755E+09 | 3394.77 | 0.170752E+09 | 38696714.27 | 0.368447E+09 |
April | 0.198852E+09 | 810527.62 | 0.198042E+09 | 0.106627E+09 | 0.227976E+09 |
May | 0.273281E+09 | 9973028.28 | 0.263308E+09 | 0.235539E+09 | 0.115198E+09 |
June | 0.279001E+09 | 14807110.60 | 0.264193E+09 | 0.333537E+09 | 36481772.75 |
July | 0.279831E+09 | 10892192.11 | 0.268939E+09 | 0.407047E+09 | 6944126.75 |
August | 0.247469E+09 | 3266730.08 | 0.244202E+09 | 0.365546E+09 | 21505244.20 |
September | 0.180340E+09 | 102477.24 | 0.180238E+09 | 0.198643E+09 | 71902269.64 |
October | 0.161143E+09 | 0.00 | 0.161143E+09 | 0.108625E+09 | 0.195209E+09 |
November | 0.109381E+09 | 0.00 | 0.109381E+09 | 20679831.12 | 0.361299E+09 |
December | 78467966.10 | 0.00 | 78467966.10 | 651318.43 | 0.520360E+09 |
Annual Sum or Average | 0.217967E+10 | 39855460.70 | 0.213982E+10 | 0.181970E+10 | 0.302933E+10 |
Minimum of Months | 78467966.10 | 0.00 | 78467966.10 | 527862.85 | 6944126.75 |
Maximum of Months | 0.279831E+09 | 14807110.60 | 0.268939E+09 | 0.407047E+09 | 0.573766E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 33162533.53 | 0.00 | 33162533.53 | 194592.10 | 0.211514E+09 |
February | 40989759.54 | 0.00 | 40989759.54 | 1320321.18 | 0.195468E+09 |
March | 62947521.07 | 1251.45 | 62946269.62 | 14265211.19 | 0.135825E+09 |
April | 73305102.21 | 298794.04 | 73006308.17 | 39306999.13 | 84041343.99 |
May | 0.100743E+09 | 3676471.18 | 97066309.93 | 86829304.56 | 42466823.56 |
June | 0.102851E+09 | 5458514.08 | 97392637.47 | 0.122956E+09 | 13448692.03 |
July | 0.103157E+09 | 4015313.02 | 99141995.32 | 0.150054E+09 | 2559892.65 |
August | 91227314.35 | 1204251.97 | 90023062.38 | 0.134755E+09 | 7927723.47 |
September | 66480944.15 | 37777.35 | 66443166.80 | 73228155.17 | 26506153.83 |
October | 59404151.36 | 0.00 | 59404151.36 | 40043561.33 | 71961941.57 |
November | 40322240.98 | 0.00 | 40322240.98 | 7623442.04 | 0.133190E+09 |
December | 28926541.41 | 0.00 | 28926541.41 | 240102.94 | 0.191826E+09 |
Annual Sum or Average | 0.803517E+09 | 14692373.10 | 0.788825E+09 | 0.670817E+09 | 0.111674E+10 |
Minimum of Months | 28926541.41 | 0.00 | 28926541.41 | 194592.10 | 2559892.65 |
Maximum of Months | 0.103157E+09 | 5458514.08 | 99141995.32 | 0.150054E+09 | 0.211514E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172278E+09 | 0.113052E+09 | 59225872.13 | 0.150588E+09 | 0.182046E+09 |
February | 0.206001E+09 | 0.136939E+09 | 69061666.91 | 0.179143E+09 | 0.163741E+09 |
March | 0.202065E+09 | 0.111264E+09 | 90800538.83 | 0.170600E+09 | 0.127765E+09 |
April | 0.155582E+09 | 62934711.94 | 92647121.25 | 0.122722E+09 | 83522113.25 |
May | 0.138073E+09 | 28250675.63 | 0.109822E+09 | 0.119451E+09 | 45072296.51 |
June | 0.126162E+09 | 19415488.77 | 0.106746E+09 | 0.140398E+09 | 14192497.33 |
July | 0.135653E+09 | 22875422.15 | 0.112778E+09 | 0.175937E+09 | 2615834.68 |
August | 0.181695E+09 | 67005630.63 | 0.114689E+09 | 0.219052E+09 | 8093165.36 |
September | 0.185604E+09 | 93199279.81 | 92405158.22 | 0.207261E+09 | 26161447.61 |
October | 0.271134E+09 | 0.170073E+09 | 0.101062E+09 | 0.297091E+09 | 68499578.84 |
November | 0.181621E+09 | 0.108958E+09 | 72663060.32 | 0.173339E+09 | 0.118376E+09 |
December | 0.186100E+09 | 0.132170E+09 | 53929189.00 | 0.174916E+09 | 0.162130E+09 |
Annual Sum or Average | 0.214197E+10 | 0.106614E+10 | 0.107583E+10 | 0.213050E+10 | 0.100221E+10 |
Minimum of Months | 0.126162E+09 | 19415488.77 | 53929189.00 | 0.119451E+09 | 2615834.68 |
Maximum of Months | 0.271134E+09 | 0.170073E+09 | 0.114689E+09 | 0.297091E+09 | 0.182046E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.467597E+09 | 0.306846E+09 | 0.160751E+09 | 0.408726E+09 | 0.494109E+09 |
February | 0.559128E+09 | 0.371680E+09 | 0.187447E+09 | 0.486229E+09 | 0.444427E+09 |
March | 0.548445E+09 | 0.301993E+09 | 0.246451E+09 | 0.463043E+09 | 0.346779E+09 |
April | 0.422281E+09 | 0.170818E+09 | 0.251463E+09 | 0.333094E+09 | 0.226696E+09 |
May | 0.374758E+09 | 76678112.22 | 0.298080E+09 | 0.324214E+09 | 0.122335E+09 |
June | 0.342429E+09 | 52697607.87 | 0.289731E+09 | 0.381070E+09 | 38521340.77 |
July | 0.368190E+09 | 62088574.78 | 0.306102E+09 | 0.477528E+09 | 7099910.39 |
August | 0.493157E+09 | 0.181867E+09 | 0.311290E+09 | 0.594553E+09 | 21966506.20 |
September | 0.503768E+09 | 0.252962E+09 | 0.250807E+09 | 0.562549E+09 | 71007520.02 |
October | 0.735914E+09 | 0.461612E+09 | 0.274302E+09 | 0.806367E+09 | 0.185922E+09 |
November | 0.492957E+09 | 0.295735E+09 | 0.197222E+09 | 0.470478E+09 | 0.321296E+09 |
December | 0.505112E+09 | 0.358738E+09 | 0.146375E+09 | 0.474758E+09 | 0.440053E+09 |
Annual Sum or Average | 0.581374E+10 | 0.289371E+10 | 0.292002E+10 | 0.578261E+10 | 0.272021E+10 |
Minimum of Months | 0.342429E+09 | 52697607.87 | 0.146375E+09 | 0.324214E+09 | 7099910.39 |
Maximum of Months | 0.735914E+09 | 0.461612E+09 | 0.311290E+09 | 0.806367E+09 | 0.494109E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369525E+09 | 0.242489E+09 | 0.127036E+09 | 0.323146E+09 | 0.372023E+09 |
February | 0.441859E+09 | 0.293726E+09 | 0.148133E+09 | 0.382594E+09 | 0.337991E+09 |
March | 0.433416E+09 | 0.238655E+09 | 0.194762E+09 | 0.358986E+09 | 0.269355E+09 |
April | 0.333714E+09 | 0.134991E+09 | 0.198723E+09 | 0.251005E+09 | 0.181669E+09 |
May | 0.296158E+09 | 60596003.23 | 0.235562E+09 | 0.230408E+09 | 0.109455E+09 |
June | 0.270609E+09 | 41645057.81 | 0.228964E+09 | 0.259710E+09 | 50209869.38 |
July | 0.290968E+09 | 49066407.20 | 0.241902E+09 | 0.328705E+09 | 18440203.11 |
August | 0.389725E+09 | 0.143723E+09 | 0.246002E+09 | 0.425847E+09 | 32722473.60 |
September | 0.398110E+09 | 0.199907E+09 | 0.198204E+09 | 0.414212E+09 | 74816393.59 |
October | 0.581567E+09 | 0.364795E+09 | 0.216771E+09 | 0.613966E+09 | 0.158346E+09 |
November | 0.389567E+09 | 0.233709E+09 | 0.155858E+09 | 0.367786E+09 | 0.244382E+09 |
December | 0.399172E+09 | 0.283498E+09 | 0.115675E+09 | 0.374135E+09 | 0.331058E+09 |
Annual Sum or Average | 0.459439E+10 | 0.228680E+10 | 0.230759E+10 | 0.433050E+10 | 0.218047E+10 |
Minimum of Months | 0.270609E+09 | 41645057.81 | 0.115675E+09 | 0.230408E+09 | 18440203.11 |
Maximum of Months | 0.581567E+09 | 0.364795E+09 | 0.246002E+09 | 0.613966E+09 | 0.372023E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274664E+09 | 0.112774E+09 | 0.161890E+09 | 0.117642E+09 | 0.761423E+09 |
February | 0.364386E+09 | 0.159920E+09 | 0.204466E+09 | 0.180867E+09 | 0.698335E+09 |
March | 0.599288E+09 | 0.277751E+09 | 0.321537E+09 | 0.430763E+09 | 0.497107E+09 |
April | 0.629850E+09 | 0.269174E+09 | 0.360676E+09 | 0.534603E+09 | 0.329077E+09 |
May | 0.760229E+09 | 0.288945E+09 | 0.471284E+09 | 0.748015E+09 | 0.193383E+09 |
June | 0.803808E+09 | 0.324343E+09 | 0.479465E+09 | 0.903784E+09 | 87271387.83 |
July | 0.777115E+09 | 0.291989E+09 | 0.485127E+09 | 0.965640E+09 | 32082138.34 |
August | 0.859852E+09 | 0.397553E+09 | 0.462300E+09 | 0.107120E+10 | 58611636.22 |
September | 0.592081E+09 | 0.258508E+09 | 0.333573E+09 | 0.634676E+09 | 0.137197E+09 |
October | 0.607022E+09 | 0.295704E+09 | 0.311318E+09 | 0.559017E+09 | 0.300843E+09 |
November | 0.276645E+09 | 80822747.87 | 0.195822E+09 | 0.133043E+09 | 0.491279E+09 |
December | 0.252530E+09 | 0.109028E+09 | 0.143502E+09 | 0.108979E+09 | 0.688231E+09 |
Annual Sum or Average | 0.679747E+10 | 0.286651E+10 | 0.393096E+10 | 0.638823E+10 | 0.427484E+10 |
Minimum of Months | 0.252530E+09 | 80822747.87 | 0.143502E+09 | 0.108979E+09 | 32082138.34 |
Maximum of Months | 0.859852E+09 | 0.397553E+09 | 0.485127E+09 | 0.107120E+10 | 0.761423E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71091250.78 | 0.00 | 71091250.78 | 1361509.11 | 0.422686E+09 |
February | 87870646.91 | 0.00 | 87870646.91 | 4070056.79 | 0.394200E+09 |
March | 0.134942E+09 | 2682.76 | 0.134939E+09 | 31814089.86 | 0.280999E+09 |
April | 0.157146E+09 | 640531.34 | 0.156505E+09 | 76253814.16 | 0.179431E+09 |
May | 0.215965E+09 | 7881331.93 | 0.208083E+09 | 0.159527E+09 | 0.100336E+09 |
June | 0.220484E+09 | 11701536.40 | 0.208783E+09 | 0.220347E+09 | 45156372.58 |
July | 0.221141E+09 | 8607714.63 | 0.212533E+09 | 0.272741E+09 | 16788504.30 |
August | 0.195566E+09 | 2581581.37 | 0.192984E+09 | 0.246542E+09 | 30209760.22 |
September | 0.142517E+09 | 80984.14 | 0.142436E+09 | 0.132268E+09 | 72475790.96 |
October | 0.127346E+09 | 0.00 | 0.127346E+09 | 76712391.23 | 0.161200E+09 |
November | 86439672.74 | 0.00 | 86439672.74 | 17785340.20 | 0.266578E+09 |
December | 62010461.52 | 0.00 | 62010461.52 | 1189984.26 | 0.380105E+09 |
Annual Sum or Average | 0.172252E+10 | 31496362.59 | 0.169102E+10 | 0.124061E+10 | 0.235016E+10 |
Minimum of Months | 62010461.52 | 0.00 | 62010461.52 | 1189984.26 | 16788504.30 |
Maximum of Months | 0.221141E+09 | 11701536.40 | 0.212533E+09 | 0.272741E+09 | 0.422686E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.274664E+09 | 0.112774E+09 | 0.161890E+09 | 0.124545E+09 | 0.751435E+09 |
February | 0.364386E+09 | 0.159920E+09 | 0.204466E+09 | 0.190904E+09 | 0.686389E+09 |
March | 0.599288E+09 | 0.277751E+09 | 0.321537E+09 | 0.444997E+09 | 0.489062E+09 |
April | 0.629850E+09 | 0.269174E+09 | 0.360676E+09 | 0.542833E+09 | 0.325228E+09 |
May | 0.760229E+09 | 0.288945E+09 | 0.471284E+09 | 0.751137E+09 | 0.192193E+09 |
June | 0.803808E+09 | 0.324343E+09 | 0.479465E+09 | 0.905150E+09 | 86771894.28 |
July | 0.777115E+09 | 0.291989E+09 | 0.485127E+09 | 0.967398E+09 | 31586382.76 |
August | 0.859852E+09 | 0.397553E+09 | 0.462300E+09 | 0.107644E+10 | 56703114.39 |
September | 0.592081E+09 | 0.258508E+09 | 0.333573E+09 | 0.643870E+09 | 0.132251E+09 |
October | 0.607022E+09 | 0.295704E+09 | 0.311318E+09 | 0.578048E+09 | 0.290714E+09 |
November | 0.276645E+09 | 80822747.87 | 0.195822E+09 | 0.144599E+09 | 0.480714E+09 |
December | 0.252530E+09 | 0.109028E+09 | 0.143502E+09 | 0.117967E+09 | 0.675538E+09 |
Annual Sum or Average | 0.679747E+10 | 0.286651E+10 | 0.393096E+10 | 0.648789E+10 | 0.419859E+10 |
Minimum of Months | 0.252530E+09 | 80822747.87 | 0.143502E+09 | 0.117967E+09 | 31586382.76 |
Maximum of Months | 0.859852E+09 | 0.397553E+09 | 0.485127E+09 | 0.107644E+10 | 0.751435E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541944E+09 | 0.355634E+09 | 0.186310E+09 | 0.456926E+09 | 0.565523E+09 |
February | 0.648029E+09 | 0.430777E+09 | 0.217251E+09 | 0.541566E+09 | 0.514540E+09 |
March | 0.635647E+09 | 0.350010E+09 | 0.285637E+09 | 0.515237E+09 | 0.404462E+09 |
April | 0.489423E+09 | 0.197978E+09 | 0.291446E+09 | 0.365478E+09 | 0.267300E+09 |
May | 0.434344E+09 | 88869854.15 | 0.345474E+09 | 0.345617E+09 | 0.152803E+09 |
June | 0.396874E+09 | 61076473.97 | 0.335798E+09 | 0.397494E+09 | 60822361.24 |
July | 0.426732E+09 | 71960595.08 | 0.354772E+09 | 0.496944E+09 | 20029496.34 |
August | 0.571569E+09 | 0.210784E+09 | 0.360785E+09 | 0.636982E+09 | 39999158.29 |
September | 0.583867E+09 | 0.293183E+09 | 0.290684E+09 | 0.609260E+09 | 0.105083E+09 |
October | 0.852923E+09 | 0.535007E+09 | 0.317916E+09 | 0.892148E+09 | 0.235627E+09 |
November | 0.571337E+09 | 0.342756E+09 | 0.228581E+09 | 0.523023E+09 | 0.376671E+09 |
December | 0.585425E+09 | 0.415776E+09 | 0.169648E+09 | 0.529885E+09 | 0.506095E+09 |
Annual Sum or Average | 0.673811E+10 | 0.335381E+10 | 0.338430E+10 | 0.631056E+10 | 0.324895E+10 |
Minimum of Months | 0.396874E+09 | 61076473.97 | 0.169648E+09 | 0.345617E+09 | 20029496.34 |
Maximum of Months | 0.852923E+09 | 0.535007E+09 | 0.360785E+09 | 0.892148E+09 | 0.565523E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497620E+09 | 0.00 | 0.497620E+09 | 467538.78 | 0.358582E+10 |
February | 0.615071E+09 | 0.00 | 0.615071E+09 | 7645669.59 | 0.328640E+10 |
March | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.144774E+09 | 0.242584E+10 |
April | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.460652E+09 | 0.157957E+10 |
May | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.107800E+10 | 0.865426E+09 |
June | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.159396E+10 | 0.375785E+09 |
July | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.193503E+10 | 0.157348E+09 |
August | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.173917E+10 | 0.250893E+09 |
September | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.934313E+09 | 0.618856E+09 |
October | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.487310E+09 | 0.137095E+10 |
November | 0.605055E+09 | 0.00 | 0.605055E+09 | 71758166.10 | 0.238707E+10 |
December | 0.434057E+09 | 0.00 | 0.434057E+09 | 1207482.65 | 0.330094E+10 |
Annual Sum or Average | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.845430E+10 | 0.202049E+11 |
Minimum of Months | 0.434057E+09 | 0.00 | 0.434057E+09 | 467538.78 | 0.157348E+09 |
Maximum of Months | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.193503E+10 | 0.358582E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.497620E+09 | 0.00 | 0.497620E+09 | 192470.31 | 0.369825E+10 |
February | 0.615071E+09 | 0.00 | 0.615071E+09 | 5145552.07 | 0.338447E+10 |
March | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.127300E+09 | 0.250862E+10 |
April | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.428554E+09 | 0.164011E+10 |
May | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.102670E+10 | 0.904857E+09 |
June | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.154284E+10 | 0.403620E+09 |
July | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.188490E+10 | 0.179098E+09 |
August | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.169137E+10 | 0.273150E+09 |
September | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.893889E+09 | 0.660790E+09 |
October | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.456721E+09 | 0.142754E+10 |
November | 0.605055E+09 | 0.00 | 0.605055E+09 | 61948083.97 | 0.247542E+10 |
December | 0.434057E+09 | 0.00 | 0.434057E+09 | 757642.52 | 0.340623E+10 |
Annual Sum or Average | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.812031E+10 | 0.209621E+11 |
Minimum of Months | 0.434057E+09 | 0.00 | 0.434057E+09 | 192470.31 | 0.179098E+09 |
Maximum of Months | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.188490E+10 | 0.369825E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 71091250.78 | 0.00 | 71091250.78 | 580743.72 | 0.477876E+09 |
February | 87870646.91 | 0.00 | 87870646.91 | 2779388.99 | 0.439438E+09 |
March | 0.134942E+09 | 2682.76 | 0.134939E+09 | 27932277.03 | 0.320447E+09 |
April | 0.157146E+09 | 640531.34 | 0.156505E+09 | 83840743.87 | 0.210049E+09 |
May | 0.215965E+09 | 7881331.93 | 0.208083E+09 | 0.189059E+09 | 0.116766E+09 |
June | 0.220484E+09 | 11701536.40 | 0.208783E+09 | 0.272391E+09 | 48417630.05 |
July | 0.221141E+09 | 8607714.63 | 0.212533E+09 | 0.332225E+09 | 17752588.32 |
August | 0.195566E+09 | 2581581.37 | 0.192984E+09 | 0.299285E+09 | 29411355.34 |
September | 0.142517E+09 | 80984.14 | 0.142436E+09 | 0.167150E+09 | 75793287.72 |
October | 0.127346E+09 | 0.00 | 0.127346E+09 | 88029525.56 | 0.176204E+09 |
November | 86439672.74 | 0.00 | 86439672.74 | 15500718.06 | 0.313849E+09 |
December | 62010461.52 | 0.00 | 62010461.52 | 606168.76 | 0.436102E+09 |
Annual Sum or Average | 0.172252E+10 | 31496362.59 | 0.169102E+10 | 0.147938E+10 | 0.266211E+10 |
Minimum of Months | 62010461.52 | 0.00 | 62010461.52 | 580743.72 | 17752588.32 |
Maximum of Months | 0.221141E+09 | 11701536.40 | 0.212533E+09 | 0.332225E+09 | 0.477876E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.553131E+09 | 0.221028E+09 | 0.332103E+09 | 0.218901E+09 | 0.166814E+10 |
February | 0.775608E+09 | 0.361191E+09 | 0.414417E+09 | 0.388927E+09 | 0.146685E+10 |
March | 0.110270E+10 | 0.468638E+09 | 0.634059E+09 | 0.773125E+09 | 0.113949E+10 |
April | 0.127751E+10 | 0.560756E+09 | 0.716758E+09 | 0.112887E+10 | 0.752492E+09 |
May | 0.159351E+10 | 0.634950E+09 | 0.958560E+09 | 0.170178E+10 | 0.440368E+09 |
June | 0.143195E+10 | 0.518583E+09 | 0.913372E+09 | 0.178915E+10 | 0.186780E+09 |
July | 0.148421E+10 | 0.534252E+09 | 0.949954E+09 | 0.207640E+10 | 69600206.04 |
August | 0.167446E+10 | 0.755429E+09 | 0.919036E+09 | 0.229704E+10 | 0.111814E+09 |
September | 0.121229E+10 | 0.546180E+09 | 0.666111E+09 | 0.145300E+10 | 0.278996E+09 |
October | 0.113165E+10 | 0.512267E+09 | 0.619386E+09 | 0.110160E+10 | 0.635128E+09 |
November | 0.678317E+09 | 0.260689E+09 | 0.417628E+09 | 0.400759E+09 | 0.108678E+10 |
December | 0.548042E+09 | 0.258636E+09 | 0.289406E+09 | 0.246537E+09 | 0.149766E+10 |
Annual Sum or Average | 0.134634E+11 | 0.563260E+10 | 0.783079E+10 | 0.135761E+11 | 0.933409E+10 |
Minimum of Months | 0.548042E+09 | 0.221028E+09 | 0.289406E+09 | 0.218901E+09 | 69600206.04 |
Maximum of Months | 0.167446E+10 | 0.755429E+09 | 0.958560E+09 | 0.229704E+10 | 0.166814E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.369525E+09 | 0.242489E+09 | 0.127036E+09 | 0.322219E+09 | 0.416075E+09 |
February | 0.441859E+09 | 0.293726E+09 | 0.148133E+09 | 0.382765E+09 | 0.369358E+09 |
March | 0.433416E+09 | 0.238655E+09 | 0.194762E+09 | 0.363624E+09 | 0.302800E+09 |
April | 0.333714E+09 | 0.134991E+09 | 0.198723E+09 | 0.261645E+09 | 0.210431E+09 |
May | 0.296158E+09 | 60596003.23 | 0.235562E+09 | 0.257765E+09 | 0.123694E+09 |
June | 0.270609E+09 | 41645057.81 | 0.228964E+09 | 0.307436E+09 | 51963466.31 |
July | 0.290968E+09 | 49066407.20 | 0.241902E+09 | 0.385215E+09 | 18792538.52 |
August | 0.389725E+09 | 0.143723E+09 | 0.246002E+09 | 0.479099E+09 | 30392266.88 |
September | 0.398110E+09 | 0.199907E+09 | 0.198204E+09 | 0.454611E+09 | 76062437.98 |
October | 0.581567E+09 | 0.364795E+09 | 0.216771E+09 | 0.641217E+09 | 0.171068E+09 |
November | 0.389567E+09 | 0.233709E+09 | 0.155858E+09 | 0.371028E+09 | 0.280821E+09 |
December | 0.399172E+09 | 0.283498E+09 | 0.115675E+09 | 0.374391E+09 | 0.371912E+09 |
Annual Sum or Average | 0.459439E+10 | 0.228680E+10 | 0.230759E+10 | 0.460102E+10 | 0.242337E+10 |
Minimum of Months | 0.270609E+09 | 41645057.81 | 0.115675E+09 | 0.257765E+09 | 18792538.52 |
Maximum of Months | 0.581567E+09 | 0.364795E+09 | 0.246002E+09 | 0.641217E+09 | 0.416075E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 90032583.51 | 0.00 | 90032583.51 | 278109.52 | 0.589449E+09 |
February | 0.111283E+09 | 0.00 | 0.111283E+09 | 2642735.72 | 0.544493E+09 |
March | 0.170896E+09 | 3397.55 | 0.170892E+09 | 33291995.43 | 0.381035E+09 |
April | 0.199015E+09 | 811192.53 | 0.198204E+09 | 98173173.26 | 0.237624E+09 |
May | 0.273505E+09 | 9981209.60 | 0.263524E+09 | 0.220943E+09 | 0.123186E+09 |
June | 0.279229E+09 | 14819257.53 | 0.264410E+09 | 0.311904E+09 | 45055765.23 |
July | 0.280061E+09 | 10901127.46 | 0.269159E+09 | 0.372144E+09 | 13585496.84 |
August | 0.247672E+09 | 3269409.92 | 0.244403E+09 | 0.332437E+09 | 29815921.12 |
September | 0.180488E+09 | 102561.31 | 0.180386E+09 | 0.183318E+09 | 81042553.33 |
October | 0.161276E+09 | 0.00 | 0.161276E+09 | 97836023.78 | 0.205893E+09 |
November | 0.109470E+09 | 0.00 | 0.109470E+09 | 17435952.81 | 0.373990E+09 |
December | 78532336.87 | 0.00 | 78532336.87 | 458066.45 | 0.535337E+09 |
Annual Sum or Average | 0.218146E+10 | 39888155.91 | 0.214157E+10 | 0.167086E+10 | 0.316051E+10 |
Minimum of Months | 78532336.87 | 0.00 | 78532336.87 | 278109.52 | 13585496.84 |
Maximum of Months | 0.280061E+09 | 14819257.53 | 0.269159E+09 | 0.372144E+09 | 0.589449E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 80552493.60 | 0.00 | 80552493.60 | 248825.64 | 0.527377E+09 |
February | 99564990.69 | 0.00 | 99564990.69 | 2364465.66 | 0.487160E+09 |
March | 0.152901E+09 | 3039.80 | 0.152898E+09 | 29786474.45 | 0.340913E+09 |
April | 0.178060E+09 | 725777.03 | 0.177334E+09 | 87835910.09 | 0.212603E+09 |
May | 0.244706E+09 | 8930226.05 | 0.235776E+09 | 0.197679E+09 | 0.110215E+09 |
June | 0.249828E+09 | 13258845.86 | 0.236569E+09 | 0.279062E+09 | 40311563.87 |
July | 0.250571E+09 | 9753280.05 | 0.240818E+09 | 0.332959E+09 | 12154995.49 |
August | 0.221593E+09 | 2925153.44 | 0.218668E+09 | 0.297432E+09 | 26676417.60 |
September | 0.161484E+09 | 91761.99 | 0.161392E+09 | 0.164016E+09 | 72509079.53 |
October | 0.144294E+09 | 0.00 | 0.144294E+09 | 87534261.17 | 0.184213E+09 |
November | 97943574.05 | 0.00 | 97943574.05 | 15600013.04 | 0.334610E+09 |
December | 70263179.36 | 0.00 | 70263179.36 | 409833.79 | 0.478946E+09 |
Annual Sum or Average | 0.195176E+10 | 35688084.23 | 0.191607E+10 | 0.149493E+10 | 0.282769E+10 |
Minimum of Months | 70263179.36 | 0.00 | 70263179.36 | 248825.64 | 12154995.49 |
Maximum of Months | 0.250571E+09 | 13258845.86 | 0.240818E+09 | 0.332959E+09 | 0.527377E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.137955E+10 | 0.905285E+09 | 0.474263E+09 | 0.118526E+10 | 0.149195E+10 |
February | 0.164959E+10 | 0.109657E+10 | 0.553025E+09 | 0.141106E+10 | 0.133827E+10 |
March | 0.161807E+10 | 0.890969E+09 | 0.727103E+09 | 0.133967E+10 | 0.105628E+10 |
April | 0.124585E+10 | 0.503962E+09 | 0.741890E+09 | 0.955280E+09 | 0.698814E+09 |
May | 0.110564E+10 | 0.226223E+09 | 0.879422E+09 | 0.915581E+09 | 0.388187E+09 |
June | 0.101026E+10 | 0.155473E+09 | 0.854791E+09 | 0.106152E+10 | 0.141864E+09 |
July | 0.108627E+10 | 0.183180E+09 | 0.903090E+09 | 0.130670E+10 | 41272126.15 |
August | 0.145496E+10 | 0.536561E+09 | 0.918397E+09 | 0.165731E+10 | 90601173.89 |
September | 0.148626E+10 | 0.746312E+09 | 0.739953E+09 | 0.161123E+10 | 0.237462E+09 |
October | 0.217116E+10 | 0.136189E+10 | 0.809272E+09 | 0.233505E+10 | 0.578088E+09 |
November | 0.145437E+10 | 0.872504E+09 | 0.581864E+09 | 0.136221E+10 | 0.977007E+09 |
December | 0.149023E+10 | 0.105838E+10 | 0.431849E+09 | 0.137835E+10 | 0.132883E+10 |
Annual Sum or Average | 0.171522E+11 | 0.853731E+10 | 0.861492E+10 | 0.165192E+11 | 0.836862E+10 |
Minimum of Months | 0.101026E+10 | 0.155473E+09 | 0.431849E+09 | 0.915581E+09 | 41272126.15 |
Maximum of Months | 0.217116E+10 | 0.136189E+10 | 0.918397E+09 | 0.233505E+10 | 0.149195E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 607.51 | 693.33 | 698.64 | 458.46 | 240.18 | 0.00 | 0.00 |
February | 797.00 | 694.15 | 924.91 | 614.83 | 310.07 | 0.00 | 0.00 |
March | 677.67 | 496.73 | 819.44 | 451.21 | 368.23 | 0.00 | 0.00 |
April | 495.16 | 341.99 | 651.97 | 263.73 | 388.24 | 0.00 | 0.00 |
May | 459.67 | 186.46 | 559.93 | 114.57 | 445.36 | 0.00 | 0.00 |
June | 543.56 | 74.11 | 528.68 | 81.36 | 447.32 | 0.00 | 0.00 |
July | 641.15 | 22.54 | 550.12 | 92.77 | 457.35 | 0.00 | 0.00 |
August | 803.02 | 52.31 | 736.83 | 271.73 | 465.10 | 0.00 | 0.00 |
September | 818.71 | 130.90 | 777.78 | 390.55 | 387.22 | 0.00 | 0.00 |
October | 1157.19 | 300.20 | 1099.54 | 689.70 | 409.84 | 0.00 | 0.00 |
November | 711.38 | 480.78 | 761.08 | 456.59 | 304.49 | 0.00 | 0.00 |
December | 699.39 | 624.02 | 754.69 | 535.99 | 218.70 | 0.00 | 0.00 |
Annual Sum or Average | 700.81 | 339.49 | 737.75 | 367.20 | 370.54 | 0.00 | 0.00 |
Minimum of Months | 459.67 | 22.54 | 528.68 | 81.36 | 218.70 | 0.00 | 0.00 |
Maximum of Months | 1157.19 | 694.15 | 1099.54 | 689.70 | 465.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1691.10 | 2008.69 | 1967.33 | 1291.00 | 676.33 | 0.00 | 0.00 |
February | 2217.92 | 2011.95 | 2604.47 | 1731.32 | 873.15 | 0.00 | 0.00 |
March | 1882.67 | 1484.25 | 2307.48 | 1270.58 | 1036.90 | 0.00 | 0.00 |
April | 1363.83 | 1049.47 | 1835.89 | 742.64 | 1093.25 | 0.00 | 0.00 |
May | 1252.50 | 597.97 | 1576.72 | 322.61 | 1254.11 | 0.00 | 0.00 |
June | 1487.05 | 261.99 | 1488.73 | 229.11 | 1259.62 | 0.00 | 0.00 |
July | 1756.82 | 100.48 | 1549.09 | 261.23 | 1287.87 | 0.00 | 0.00 |
August | 2221.90 | 187.45 | 2074.87 | 765.17 | 1309.70 | 0.00 | 0.00 |
September | 2270.91 | 438.76 | 2190.16 | 1099.77 | 1090.40 | 0.00 | 0.00 |
October | 3221.08 | 939.72 | 3096.22 | 1942.15 | 1154.08 | 0.00 | 0.00 |
November | 1971.26 | 1440.46 | 2143.16 | 1285.72 | 857.44 | 0.00 | 0.00 |
December | 1945.67 | 1828.68 | 2125.17 | 1509.32 | 615.85 | 0.00 | 0.00 |
Annual Sum or Average | 1939.77 | 1023.61 | 2077.44 | 1034.02 | 1043.42 | 0.00 | 0.00 |
Minimum of Months | 1252.50 | 100.48 | 1488.73 | 229.11 | 615.85 | 0.00 | 0.00 |
Maximum of Months | 3221.08 | 2011.95 | 3096.22 | 1942.15 | 1309.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2234.23 | 2742.43 | 2555.67 | 1677.08 | 878.59 | 0.00 | 0.00 |
February | 2938.86 | 2727.24 | 3383.36 | 2249.09 | 1134.27 | 0.00 | 0.00 |
March | 2499.01 | 2016.52 | 2997.55 | 1650.56 | 1346.99 | 0.00 | 0.00 |
April | 1811.27 | 1431.18 | 2384.93 | 964.73 | 1420.20 | 0.00 | 0.00 |
May | 1670.27 | 807.49 | 2048.25 | 419.09 | 1629.17 | 0.00 | 0.00 |
June | 2001.22 | 340.72 | 1933.94 | 297.62 | 1636.32 | 0.00 | 0.00 |
July | 2378.95 | 121.17 | 2012.36 | 339.35 | 1673.01 | 0.00 | 0.00 |
August | 3009.73 | 228.05 | 2695.37 | 994.00 | 1701.37 | 0.00 | 0.00 |
September | 3048.23 | 562.24 | 2845.15 | 1428.66 | 1416.49 | 0.00 | 0.00 |
October | 4298.18 | 1228.07 | 4022.17 | 2522.96 | 1499.21 | 0.00 | 0.00 |
November | 2606.85 | 1964.11 | 2784.09 | 1670.23 | 1113.86 | 0.00 | 0.00 |
December | 2570.65 | 2496.99 | 2760.71 | 1960.70 | 800.02 | 0.00 | 0.00 |
Annual Sum or Average | 2588.51 | 1381.29 | 2698.72 | 1343.25 | 1355.46 | 0.00 | 0.00 |
Minimum of Months | 1670.27 | 121.17 | 1933.94 | 297.62 | 800.02 | 0.00 | 0.00 |
Maximum of Months | 4298.18 | 2742.43 | 4022.17 | 2522.96 | 1701.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 148.09 | 406.25 | 240.32 | 132.53 | 107.78 | 0.00 | 0.00 |
February | 212.01 | 405.78 | 333.00 | 187.37 | 145.63 | 0.00 | 0.00 |
March | 290.46 | 278.91 | 385.25 | 192.65 | 192.61 | 0.00 | 0.00 |
April | 304.15 | 193.31 | 371.44 | 155.80 | 215.64 | 0.00 | 0.00 |
May | 370.24 | 107.96 | 394.09 | 130.40 | 263.69 | 0.00 | 0.00 |
June | 457.06 | 46.67 | 414.17 | 141.08 | 273.09 | 0.00 | 0.00 |
July | 491.41 | 14.91 | 398.45 | 127.23 | 271.22 | 0.00 | 0.00 |
August | 565.53 | 29.90 | 466.16 | 201.92 | 264.23 | 0.00 | 0.00 |
September | 410.01 | 75.97 | 381.71 | 176.71 | 204.99 | 0.00 | 0.00 |
October | 440.06 | 166.68 | 443.40 | 246.40 | 197.00 | 0.00 | 0.00 |
November | 185.57 | 276.10 | 256.82 | 121.25 | 135.57 | 0.00 | 0.00 |
December | 163.03 | 363.74 | 243.12 | 146.43 | 96.69 | 0.00 | 0.00 |
Annual Sum or Average | 337.46 | 196.01 | 360.94 | 163.28 | 197.66 | 0.00 | 0.00 |
Minimum of Months | 148.09 | 14.91 | 240.32 | 121.25 | 96.69 | 0.00 | 0.00 |
Maximum of Months | 565.53 | 406.25 | 466.16 | 246.40 | 273.09 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.73 | 432.07 | 128.98 | 42.07 | 86.91 | 0.00 | 0.00 |
February | 72.16 | 437.11 | 186.79 | 66.05 | 120.74 | 0.00 | 0.00 |
March | 172.56 | 280.50 | 273.91 | 103.62 | 170.29 | 0.00 | 0.00 |
April | 239.91 | 191.64 | 303.38 | 104.01 | 199.37 | 0.00 | 0.00 |
May | 346.37 | 105.22 | 364.17 | 110.73 | 253.44 | 0.00 | 0.00 |
June | 443.45 | 45.22 | 394.85 | 129.54 | 265.31 | 0.00 | 0.00 |
July | 471.89 | 14.38 | 372.40 | 112.14 | 260.26 | 0.00 | 0.00 |
August | 501.14 | 28.52 | 393.73 | 149.27 | 244.45 | 0.00 | 0.00 |
September | 304.96 | 73.57 | 283.18 | 99.68 | 183.49 | 0.00 | 0.00 |
October | 245.33 | 164.55 | 273.96 | 110.31 | 163.64 | 0.00 | 0.00 |
November | 59.47 | 286.41 | 139.96 | 31.16 | 108.81 | 0.00 | 0.00 |
December | 38.14 | 389.16 | 117.34 | 40.67 | 76.67 | 0.00 | 0.00 |
Annual Sum or Average | 245.90 | 202.71 | 269.95 | 91.82 | 178.13 | 0.00 | 0.00 |
Minimum of Months | 38.14 | 14.38 | 117.34 | 31.16 | 76.67 | 0.00 | 0.00 |
Maximum of Months | 501.14 | 437.11 | 394.85 | 149.27 | 265.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 96.08 | 109.41 | 110.26 | 72.35 | 37.91 | 0.00 | 0.00 |
February | 124.66 | 114.66 | 145.97 | 97.03 | 48.94 | 0.00 | 0.00 |
March | 106.32 | 84.85 | 129.32 | 71.21 | 58.11 | 0.00 | 0.00 |
April | 76.95 | 59.99 | 102.89 | 41.62 | 61.27 | 0.00 | 0.00 |
May | 68.42 | 36.20 | 88.37 | 18.08 | 70.29 | 0.00 | 0.00 |
June | 82.21 | 16.08 | 83.44 | 12.84 | 70.60 | 0.00 | 0.00 |
July | 99.30 | 5.94 | 86.82 | 14.64 | 72.18 | 0.00 | 0.00 |
August | 127.61 | 10.22 | 116.29 | 42.88 | 73.40 | 0.00 | 0.00 |
September | 127.74 | 25.91 | 122.75 | 61.64 | 61.11 | 0.00 | 0.00 |
October | 181.60 | 54.34 | 173.53 | 108.85 | 64.68 | 0.00 | 0.00 |
November | 110.33 | 82.94 | 120.11 | 72.06 | 48.06 | 0.00 | 0.00 |
December | 109.73 | 102.05 | 119.11 | 84.59 | 34.52 | 0.00 | 0.00 |
Annual Sum or Average | 109.23 | 58.22 | 116.43 | 57.95 | 58.48 | 0.00 | 0.00 |
Minimum of Months | 68.42 | 5.94 | 83.44 | 12.84 | 34.52 | 0.00 | 0.00 |
Maximum of Months | 181.60 | 114.66 | 173.53 | 108.85 | 73.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.20 | 132.08 | 21.22 | 0.00 | 21.22 | 0.00 | 0.00 |
February | 1.10 | 134.69 | 29.04 | 0.00 | 29.04 | 0.00 | 0.00 |
March | 9.47 | 85.82 | 40.28 | 0.00 | 40.28 | 0.00 | 0.00 |
April | 25.27 | 55.92 | 48.47 | 0.20 | 48.27 | 0.00 | 0.00 |
May | 52.60 | 28.55 | 64.46 | 2.35 | 62.11 | 0.00 | 0.00 |
June | 75.53 | 11.16 | 68.00 | 3.61 | 64.39 | 0.00 | 0.00 |
July | 88.46 | 3.21 | 66.01 | 2.57 | 63.44 | 0.00 | 0.00 |
August | 80.67 | 6.63 | 58.37 | 0.77 | 57.60 | 0.00 | 0.00 |
September | 45.33 | 19.67 | 43.96 | 0.02 | 43.93 | 0.00 | 0.00 |
October | 25.16 | 46.59 | 38.01 | 0.00 | 38.01 | 0.00 | 0.00 |
November | 5.09 | 86.83 | 26.66 | 0.00 | 26.66 | 0.00 | 0.00 |
December | 0.21 | 119.60 | 18.51 | 0.00 | 18.51 | 0.00 | 0.00 |
Annual Sum or Average | 34.32 | 60.48 | 43.67 | 0.80 | 42.87 | 0.00 | 0.00 |
Minimum of Months | 0.20 | 3.21 | 18.51 | 0.00 | 18.51 | 0.00 | 0.00 |
Maximum of Months | 88.46 | 134.69 | 68.00 | 3.61 | 64.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 146.73 | 403.07 | 241.03 | 131.69 | 109.34 | 0.00 | 0.00 |
February | 220.26 | 399.27 | 342.68 | 195.91 | 146.77 | 0.00 | 0.00 |
March | 271.13 | 280.51 | 367.38 | 176.45 | 190.93 | 0.00 | 0.00 |
April | 302.88 | 187.34 | 374.89 | 160.13 | 214.76 | 0.00 | 0.00 |
May | 384.39 | 103.97 | 407.73 | 141.05 | 266.69 | 0.00 | 0.00 |
June | 417.73 | 42.84 | 380.34 | 116.01 | 264.32 | 0.00 | 0.00 |
July | 476.64 | 13.14 | 385.41 | 117.96 | 267.44 | 0.00 | 0.00 |
August | 553.68 | 26.60 | 457.74 | 194.53 | 263.21 | 0.00 | 0.00 |
September | 414.25 | 71.37 | 387.14 | 182.34 | 204.80 | 0.00 | 0.00 |
October | 419.39 | 161.92 | 428.05 | 231.65 | 196.41 | 0.00 | 0.00 |
November | 210.97 | 273.03 | 280.92 | 140.34 | 140.58 | 0.00 | 0.00 |
December | 170.22 | 359.83 | 251.14 | 154.00 | 97.14 | 0.00 | 0.00 |
Annual Sum or Average | 333.23 | 192.43 | 358.87 | 161.69 | 197.18 | 0.00 | 0.00 |
Minimum of Months | 146.73 | 13.14 | 241.03 | 116.01 | 97.14 | 0.00 | 0.00 |
Maximum of Months | 553.68 | 403.07 | 457.74 | 231.65 | 267.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 34.27 | 423.87 | 129.70 | 41.23 | 88.47 | 0.00 | 0.00 |
February | 69.19 | 419.20 | 196.47 | 74.60 | 121.88 | 0.00 | 0.00 |
March | 151.51 | 280.33 | 256.04 | 87.42 | 168.62 | 0.00 | 0.00 |
April | 237.97 | 185.16 | 306.83 | 108.34 | 198.49 | 0.00 | 0.00 |
May | 360.81 | 101.68 | 377.82 | 121.38 | 256.43 | 0.00 | 0.00 |
June | 404.30 | 41.63 | 361.01 | 104.47 | 256.54 | 0.00 | 0.00 |
July | 457.18 | 12.70 | 359.36 | 102.87 | 256.49 | 0.00 | 0.00 |
August | 489.33 | 25.48 | 385.31 | 141.88 | 243.43 | 0.00 | 0.00 |
September | 308.34 | 68.70 | 288.62 | 105.31 | 183.30 | 0.00 | 0.00 |
October | 223.35 | 158.07 | 258.60 | 95.56 | 163.05 | 0.00 | 0.00 |
November | 78.71 | 277.36 | 164.07 | 50.25 | 113.82 | 0.00 | 0.00 |
December | 38.22 | 378.06 | 125.36 | 48.25 | 77.12 | 0.00 | 0.00 |
Annual Sum or Average | 238.94 | 196.46 | 267.88 | 90.24 | 177.64 | 0.00 | 0.00 |
Minimum of Months | 34.27 | 12.70 | 125.36 | 41.23 | 77.12 | 0.00 | 0.00 |
Maximum of Months | 489.33 | 423.87 | 385.31 | 141.88 | 256.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.20 | 516.75 | 284.87 | 156.77 | 128.10 | 0.00 | 0.00 |
February | 243.93 | 518.24 | 379.18 | 210.24 | 168.94 | 0.00 | 0.00 |
March | 252.22 | 361.32 | 367.46 | 154.29 | 213.17 | 0.00 | 0.00 |
April | 231.76 | 239.67 | 327.94 | 90.61 | 237.33 | 0.00 | 0.00 |
May | 285.23 | 120.59 | 331.11 | 44.27 | 286.84 | 0.00 | 0.00 |
June | 376.74 | 39.04 | 328.10 | 35.64 | 292.46 | 0.00 | 0.00 |
July | 451.89 | 7.09 | 331.11 | 37.29 | 293.82 | 0.00 | 0.00 |
August | 490.51 | 22.16 | 378.42 | 94.59 | 283.83 | 0.00 | 0.00 |
September | 401.76 | 75.33 | 361.19 | 133.60 | 227.58 | 0.00 | 0.00 |
October | 465.31 | 192.56 | 458.33 | 235.84 | 222.49 | 0.00 | 0.00 |
November | 245.97 | 347.07 | 318.01 | 156.13 | 161.88 | 0.00 | 0.00 |
December | 213.13 | 460.97 | 298.17 | 183.28 | 114.88 | 0.00 | 0.00 |
Annual Sum or Average | 320.58 | 240.19 | 346.87 | 127.30 | 219.57 | 0.00 | 0.00 |
Minimum of Months | 180.20 | 7.09 | 284.87 | 35.64 | 114.88 | 0.00 | 0.00 |
Maximum of Months | 490.51 | 518.24 | 458.33 | 235.84 | 293.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 147.68 | 406.29 | 240.51 | 132.64 | 107.87 | 0.00 | 0.00 |
February | 210.92 | 406.39 | 333.27 | 187.52 | 145.75 | 0.00 | 0.00 |
March | 288.18 | 279.48 | 385.57 | 192.80 | 192.76 | 0.00 | 0.00 |
April | 300.56 | 194.52 | 371.75 | 155.93 | 215.82 | 0.00 | 0.00 |
May | 363.23 | 110.99 | 394.41 | 130.50 | 263.91 | 0.00 | 0.00 |
June | 447.78 | 51.94 | 414.51 | 141.20 | 273.31 | 0.00 | 0.00 |
July | 482.86 | 18.47 | 398.78 | 127.34 | 271.44 | 0.00 | 0.00 |
August | 558.51 | 33.67 | 466.54 | 202.09 | 264.45 | 0.00 | 0.00 |
September | 403.76 | 80.89 | 382.02 | 176.86 | 205.16 | 0.00 | 0.00 |
October | 435.83 | 169.33 | 443.77 | 246.60 | 197.17 | 0.00 | 0.00 |
November | 184.89 | 275.49 | 257.03 | 121.35 | 135.68 | 0.00 | 0.00 |
December | 162.96 | 363.15 | 243.32 | 146.55 | 96.77 | 0.00 | 0.00 |
Annual Sum or Average | 333.24 | 198.05 | 361.23 | 163.41 | 197.82 | 0.00 | 0.00 |
Minimum of Months | 147.68 | 18.47 | 240.51 | 121.35 | 96.77 | 0.00 | 0.00 |
Maximum of Months | 558.51 | 406.39 | 466.54 | 246.60 | 273.31 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 40.83 | 432.19 | 129.09 | 42.11 | 86.99 | 0.00 | 0.00 |
February | 72.01 | 438.09 | 186.94 | 66.10 | 120.84 | 0.00 | 0.00 |
March | 171.24 | 280.73 | 274.13 | 103.70 | 170.43 | 0.00 | 0.00 |
April | 236.59 | 192.44 | 303.62 | 104.10 | 199.53 | 0.00 | 0.00 |
May | 339.00 | 108.22 | 364.47 | 110.82 | 253.65 | 0.00 | 0.00 |
June | 433.77 | 50.44 | 395.17 | 129.65 | 265.53 | 0.00 | 0.00 |
July | 462.89 | 17.94 | 372.71 | 112.23 | 260.48 | 0.00 | 0.00 |
August | 493.73 | 32.23 | 394.05 | 149.39 | 244.66 | 0.00 | 0.00 |
September | 298.60 | 78.15 | 283.41 | 99.76 | 183.65 | 0.00 | 0.00 |
October | 242.12 | 166.39 | 274.18 | 110.40 | 163.78 | 0.00 | 0.00 |
November | 59.62 | 285.27 | 140.08 | 31.18 | 108.90 | 0.00 | 0.00 |
December | 38.59 | 388.23 | 117.44 | 40.71 | 76.73 | 0.00 | 0.00 |
Annual Sum or Average | 241.96 | 204.55 | 270.17 | 91.90 | 178.27 | 0.00 | 0.00 |
Minimum of Months | 38.59 | 17.94 | 117.44 | 31.18 | 76.73 | 0.00 | 0.00 |
Maximum of Months | 493.73 | 438.09 | 395.17 | 149.39 | 265.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 170.60 | 211.14 | 202.34 | 132.78 | 69.56 | 0.00 | 0.00 |
February | 223.86 | 212.69 | 267.87 | 178.07 | 89.80 | 0.00 | 0.00 |
March | 192.37 | 151.01 | 237.32 | 130.68 | 106.64 | 0.00 | 0.00 |
April | 141.00 | 103.12 | 188.82 | 76.38 | 112.44 | 0.00 | 0.00 |
May | 129.04 | 57.05 | 162.17 | 33.18 | 128.99 | 0.00 | 0.00 |
June | 153.35 | 23.47 | 153.12 | 23.56 | 129.55 | 0.00 | 0.00 |
July | 185.54 | 7.48 | 159.32 | 26.87 | 132.46 | 0.00 | 0.00 |
August | 237.82 | 14.93 | 213.40 | 78.70 | 134.70 | 0.00 | 0.00 |
September | 235.05 | 40.54 | 225.26 | 113.11 | 112.15 | 0.00 | 0.00 |
October | 333.09 | 87.97 | 318.45 | 199.75 | 118.70 | 0.00 | 0.00 |
November | 201.78 | 145.32 | 220.42 | 132.24 | 88.19 | 0.00 | 0.00 |
December | 197.84 | 188.95 | 218.57 | 155.23 | 63.34 | 0.00 | 0.00 |
Annual Sum or Average | 200.11 | 103.02 | 213.66 | 106.35 | 107.32 | 0.00 | 0.00 |
Minimum of Months | 129.04 | 7.48 | 153.12 | 23.56 | 63.34 | 0.00 | 0.00 |
Maximum of Months | 333.09 | 212.69 | 318.45 | 199.75 | 134.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.17 | 1338.79 | 185.79 | 0.00 | 185.79 | 0.00 | 0.00 |
February | 3.16 | 1358.47 | 254.25 | 0.00 | 254.25 | 0.00 | 0.00 |
March | 54.05 | 905.71 | 352.66 | 0.01 | 352.65 | 0.00 | 0.00 |
April | 177.72 | 609.40 | 424.37 | 1.73 | 422.64 | 0.00 | 0.00 |
May | 402.48 | 323.11 | 564.40 | 20.60 | 543.80 | 0.00 | 0.00 |
June | 614.95 | 144.98 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
July | 722.46 | 58.75 | 577.93 | 22.50 | 555.43 | 0.00 | 0.00 |
August | 649.33 | 93.67 | 511.09 | 6.75 | 504.35 | 0.00 | 0.00 |
September | 360.46 | 238.76 | 384.87 | 0.22 | 384.65 | 0.00 | 0.00 |
October | 181.94 | 511.85 | 332.81 | 0.00 | 332.81 | 0.00 | 0.00 |
November | 27.68 | 920.94 | 233.43 | 0.00 | 233.43 | 0.00 | 0.00 |
December | 0.45 | 1232.43 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Annual Sum or Average | 268.08 | 640.69 | 382.33 | 6.99 | 375.34 | 0.00 | 0.00 |
Minimum of Months | 0.17 | 58.75 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Maximum of Months | 722.46 | 1358.47 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.07 | 1380.77 | 185.79 | 0.00 | 185.79 | 0.00 | 0.00 |
February | 2.13 | 1399.00 | 254.25 | 0.00 | 254.25 | 0.00 | 0.00 |
March | 47.53 | 936.61 | 352.66 | 0.01 | 352.65 | 0.00 | 0.00 |
April | 165.34 | 632.76 | 424.37 | 1.73 | 422.64 | 0.00 | 0.00 |
May | 383.33 | 337.83 | 564.40 | 20.60 | 543.80 | 0.00 | 0.00 |
June | 595.23 | 155.72 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
July | 703.74 | 66.87 | 577.93 | 22.50 | 555.43 | 0.00 | 0.00 |
August | 631.48 | 101.98 | 511.09 | 6.75 | 504.35 | 0.00 | 0.00 |
September | 344.86 | 254.93 | 384.87 | 0.22 | 384.65 | 0.00 | 0.00 |
October | 170.52 | 532.98 | 332.81 | 0.00 | 332.81 | 0.00 | 0.00 |
November | 23.90 | 955.02 | 233.43 | 0.00 | 233.43 | 0.00 | 0.00 |
December | 0.28 | 1271.74 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Annual Sum or Average | 257.49 | 664.71 | 382.33 | 6.99 | 375.34 | 0.00 | 0.00 |
Minimum of Months | 0.07 | 66.87 | 162.06 | 0.00 | 162.06 | 0.00 | 0.00 |
Maximum of Months | 703.74 | 1399.00 | 595.42 | 31.60 | 563.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 160.74 | 915.06 | 371.02 | 173.06 | 197.97 | 0.00 | 0.00 |
February | 268.14 | 888.66 | 539.57 | 270.72 | 268.86 | 0.00 | 0.00 |
March | 422.62 | 645.91 | 623.90 | 264.07 | 359.83 | 0.00 | 0.00 |
April | 562.27 | 445.99 | 682.24 | 268.67 | 413.57 | 0.00 | 0.00 |
May | 799.35 | 251.35 | 786.15 | 262.63 | 523.52 | 0.00 | 0.00 |
June | 912.98 | 109.81 | 741.92 | 220.65 | 521.26 | 0.00 | 0.00 |
July | 1042.99 | 39.52 | 745.34 | 221.00 | 524.34 | 0.00 | 0.00 |
August | 1147.93 | 63.77 | 843.70 | 336.67 | 507.03 | 0.00 | 0.00 |
September | 798.82 | 164.59 | 676.28 | 287.87 | 388.41 | 0.00 | 0.00 |
October | 679.63 | 362.86 | 687.19 | 327.46 | 359.73 | 0.00 | 0.00 |
November | 286.92 | 631.89 | 445.34 | 190.74 | 254.60 | 0.00 | 0.00 |
December | 191.60 | 820.38 | 376.80 | 202.41 | 174.39 | 0.00 | 0.00 |
Annual Sum or Average | 608.57 | 442.51 | 627.23 | 252.12 | 375.11 | 0.00 | 0.00 |
Minimum of Months | 160.74 | 39.52 | 371.02 | 173.06 | 174.39 | 0.00 | 0.00 |
Maximum of Months | 1147.93 | 915.06 | 843.70 | 336.67 | 524.34 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 398.62 | 929.90 | 578.75 | 337.99 | 240.76 | 0.00 | 0.00 |
February | 534.59 | 928.87 | 769.03 | 453.28 | 315.75 | 0.00 | 0.00 |
March | 516.64 | 656.83 | 725.01 | 332.65 | 392.36 | 0.00 | 0.00 |
April | 439.60 | 442.59 | 626.13 | 195.02 | 431.11 | 0.00 | 0.00 |
May | 496.69 | 230.63 | 606.28 | 91.52 | 514.76 | 0.00 | 0.00 |
June | 636.35 | 86.49 | 593.87 | 70.81 | 523.06 | 0.00 | 0.00 |
July | 750.85 | 24.75 | 603.68 | 76.10 | 527.58 | 0.00 | 0.00 |
August | 853.80 | 54.79 | 718.42 | 202.64 | 515.78 | 0.00 | 0.00 |
September | 755.40 | 150.64 | 705.34 | 288.00 | 417.33 | 0.00 | 0.00 |
October | 937.23 | 357.70 | 924.71 | 508.47 | 416.23 | 0.00 | 0.00 |
November | 517.14 | 629.16 | 641.12 | 336.61 | 304.51 | 0.00 | 0.00 |
December | 469.25 | 829.13 | 611.94 | 395.15 | 216.79 | 0.00 | 0.00 |
Annual Sum or Average | 609.69 | 440.74 | 674.96 | 273.11 | 401.84 | 0.00 | 0.00 |
Minimum of Months | 398.62 | 24.75 | 578.75 | 70.81 | 216.79 | 0.00 | 0.00 |
Maximum of Months | 937.23 | 929.90 | 924.71 | 508.47 | 527.58 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162716E+10 | 0.185701E+10 | 0.187124E+10 | 0.122794E+10 | 0.643298E+09 | 0.00 | 0.00 |
February | 0.192811E+10 | 0.167929E+10 | 0.223753E+10 | 0.148740E+10 | 0.750132E+09 | 0.00 | 0.00 |
March | 0.181507E+10 | 0.133045E+10 | 0.219478E+10 | 0.120852E+10 | 0.986255E+09 | 0.00 | 0.00 |
April | 0.128345E+10 | 0.886442E+09 | 0.168989E+10 | 0.683582E+09 | 0.100631E+10 | 0.00 | 0.00 |
May | 0.123118E+10 | 0.499404E+09 | 0.149971E+10 | 0.306852E+09 | 0.119286E+10 | 0.00 | 0.00 |
June | 0.140890E+10 | 0.192091E+09 | 0.137034E+10 | 0.210887E+09 | 0.115945E+10 | 0.00 | 0.00 |
July | 0.171725E+10 | 60366130.01 | 0.147343E+10 | 0.248468E+09 | 0.122497E+10 | 0.00 | 0.00 |
August | 0.215082E+10 | 0.140095E+09 | 0.197353E+10 | 0.727800E+09 | 0.124573E+10 | 0.00 | 0.00 |
September | 0.212209E+10 | 0.339286E+09 | 0.201599E+10 | 0.101231E+10 | 0.100368E+10 | 0.00 | 0.00 |
October | 0.309942E+10 | 0.804048E+09 | 0.294500E+10 | 0.184729E+10 | 0.109771E+10 | 0.00 | 0.00 |
November | 0.184389E+10 | 0.124617E+10 | 0.197273E+10 | 0.118348E+10 | 0.789250E+09 | 0.00 | 0.00 |
December | 0.187324E+10 | 0.167137E+10 | 0.202137E+10 | 0.143560E+10 | 0.585767E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.221006E+11 | 0.107060E+11 | 0.232656E+11 | 0.115801E+11 | 0.116854E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123118E+10 | 60366130.01 | 0.137034E+10 | 0.210887E+09 | 0.585767E+09 | 0.00 | 0.00 |
Maximum of Months | 0.309942E+10 | 0.185701E+10 | 0.294500E+10 | 0.184729E+10 | 0.124573E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.452945E+10 | 0.538007E+10 | 0.526929E+10 | 0.345781E+10 | 0.181148E+10 | 0.00 | 0.00 |
February | 0.536560E+10 | 0.486730E+10 | 0.630074E+10 | 0.418842E+10 | 0.211232E+10 | 0.00 | 0.00 |
March | 0.504255E+10 | 0.397541E+10 | 0.618035E+10 | 0.340312E+10 | 0.277723E+10 | 0.00 | 0.00 |
April | 0.353504E+10 | 0.272023E+10 | 0.475863E+10 | 0.192492E+10 | 0.283371E+10 | 0.00 | 0.00 |
May | 0.335469E+10 | 0.160160E+10 | 0.422310E+10 | 0.864076E+09 | 0.335902E+10 | 0.00 | 0.00 |
June | 0.385443E+10 | 0.679080E+09 | 0.385879E+10 | 0.593843E+09 | 0.326494E+10 | 0.00 | 0.00 |
July | 0.470546E+10 | 0.269133E+09 | 0.414909E+10 | 0.699668E+09 | 0.344942E+10 | 0.00 | 0.00 |
August | 0.595115E+10 | 0.502065E+09 | 0.555733E+10 | 0.204944E+10 | 0.350789E+10 | 0.00 | 0.00 |
September | 0.588620E+10 | 0.113726E+10 | 0.567690E+10 | 0.285060E+10 | 0.282631E+10 | 0.00 | 0.00 |
October | 0.862733E+10 | 0.251694E+10 | 0.829292E+10 | 0.520184E+10 | 0.309108E+10 | 0.00 | 0.00 |
November | 0.510950E+10 | 0.373366E+10 | 0.555507E+10 | 0.333260E+10 | 0.222247E+10 | 0.00 | 0.00 |
December | 0.521129E+10 | 0.489793E+10 | 0.569205E+10 | 0.404257E+10 | 0.164948E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.611727E+11 | 0.322807E+11 | 0.655143E+11 | 0.326089E+11 | 0.329054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.335469E+10 | 0.269133E+09 | 0.385879E+10 | 0.593843E+09 | 0.164948E+10 | 0.00 | 0.00 |
Maximum of Months | 0.862733E+10 | 0.538007E+10 | 0.829292E+10 | 0.520184E+10 | 0.350789E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598417E+10 | 0.734533E+10 | 0.684511E+10 | 0.449189E+10 | 0.235322E+10 | 0.00 | 0.00 |
February | 0.710969E+10 | 0.659774E+10 | 0.818502E+10 | 0.544100E+10 | 0.274403E+10 | 0.00 | 0.00 |
March | 0.669335E+10 | 0.540104E+10 | 0.802863E+10 | 0.442085E+10 | 0.360778E+10 | 0.00 | 0.00 |
April | 0.469480E+10 | 0.370963E+10 | 0.618173E+10 | 0.250058E+10 | 0.368115E+10 | 0.00 | 0.00 |
May | 0.447364E+10 | 0.216279E+10 | 0.548604E+10 | 0.112248E+10 | 0.436356E+10 | 0.00 | 0.00 |
June | 0.518715E+10 | 0.883140E+09 | 0.501278E+10 | 0.771436E+09 | 0.424135E+10 | 0.00 | 0.00 |
July | 0.637177E+10 | 0.324531E+09 | 0.538991E+10 | 0.908909E+09 | 0.448100E+10 | 0.00 | 0.00 |
August | 0.806126E+10 | 0.610817E+09 | 0.721928E+10 | 0.266233E+10 | 0.455695E+10 | 0.00 | 0.00 |
September | 0.790101E+10 | 0.145733E+10 | 0.737462E+10 | 0.370309E+10 | 0.367153E+10 | 0.00 | 0.00 |
October | 0.115122E+11 | 0.328926E+10 | 0.107730E+11 | 0.675749E+10 | 0.401548E+10 | 0.00 | 0.00 |
November | 0.675695E+10 | 0.509098E+10 | 0.721636E+10 | 0.432923E+10 | 0.288712E+10 | 0.00 | 0.00 |
December | 0.688522E+10 | 0.668793E+10 | 0.739430E+10 | 0.525153E+10 | 0.214277E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.816313E+11 | 0.435605E+11 | 0.851068E+11 | 0.423608E+11 | 0.427459E+11 | 0.00 | 0.00 |
Minimum of Months | 0.447364E+10 | 0.324531E+09 | 0.501278E+10 | 0.771436E+09 | 0.214277E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115122E+11 | 0.734533E+10 | 0.107730E+11 | 0.675749E+10 | 0.455695E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.396657E+09 | 0.108809E+10 | 0.643661E+09 | 0.354972E+09 | 0.288689E+09 | 0.00 | 0.00 |
February | 0.512889E+09 | 0.981673E+09 | 0.805584E+09 | 0.453274E+09 | 0.352310E+09 | 0.00 | 0.00 |
March | 0.777977E+09 | 0.747031E+09 | 0.103186E+10 | 0.515982E+09 | 0.515875E+09 | 0.00 | 0.00 |
April | 0.788345E+09 | 0.501064E+09 | 0.962774E+09 | 0.403834E+09 | 0.558940E+09 | 0.00 | 0.00 |
May | 0.991643E+09 | 0.289171E+09 | 0.105552E+10 | 0.349255E+09 | 0.706266E+09 | 0.00 | 0.00 |
June | 0.118471E+10 | 0.120969E+09 | 0.107354E+10 | 0.365688E+09 | 0.707848E+09 | 0.00 | 0.00 |
July | 0.131619E+10 | 39942805.16 | 0.106721E+10 | 0.340776E+09 | 0.726432E+09 | 0.00 | 0.00 |
August | 0.151470E+10 | 80080435.78 | 0.124855E+10 | 0.540832E+09 | 0.707721E+09 | 0.00 | 0.00 |
September | 0.106275E+10 | 0.196906E+09 | 0.989380E+09 | 0.458039E+09 | 0.531341E+09 | 0.00 | 0.00 |
October | 0.117867E+10 | 0.446446E+09 | 0.118761E+10 | 0.659958E+09 | 0.527656E+09 | 0.00 | 0.00 |
November | 0.480999E+09 | 0.715655E+09 | 0.665665E+09 | 0.314274E+09 | 0.351392E+09 | 0.00 | 0.00 |
December | 0.436665E+09 | 0.974229E+09 | 0.651168E+09 | 0.392204E+09 | 0.258964E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106422E+11 | 0.618126E+10 | 0.113825E+11 | 0.514909E+10 | 0.623343E+10 | 0.00 | 0.00 |
Minimum of Months | 0.396657E+09 | 39942805.16 | 0.643661E+09 | 0.314274E+09 | 0.258964E+09 | 0.00 | 0.00 |
Maximum of Months | 0.151470E+10 | 0.108809E+10 | 0.124855E+10 | 0.659958E+09 | 0.726432E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109088E+09 | 0.115726E+10 | 0.345472E+09 | 0.112682E+09 | 0.232790E+09 | 0.00 | 0.00 |
February | 0.174570E+09 | 0.105745E+10 | 0.451886E+09 | 0.159789E+09 | 0.292097E+09 | 0.00 | 0.00 |
March | 0.462190E+09 | 0.751304E+09 | 0.733628E+09 | 0.277526E+09 | 0.456102E+09 | 0.00 | 0.00 |
April | 0.621837E+09 | 0.496729E+09 | 0.786351E+09 | 0.269593E+09 | 0.516757E+09 | 0.00 | 0.00 |
May | 0.927709E+09 | 0.281831E+09 | 0.975394E+09 | 0.296583E+09 | 0.678810E+09 | 0.00 | 0.00 |
June | 0.114941E+10 | 0.117209E+09 | 0.102345E+10 | 0.335769E+09 | 0.687683E+09 | 0.00 | 0.00 |
July | 0.126390E+10 | 38502580.94 | 0.997438E+09 | 0.300350E+09 | 0.697088E+09 | 0.00 | 0.00 |
August | 0.134225E+10 | 76385142.33 | 0.105455E+10 | 0.399806E+09 | 0.654747E+09 | 0.00 | 0.00 |
September | 0.790468E+09 | 0.190689E+09 | 0.733996E+09 | 0.258377E+09 | 0.475619E+09 | 0.00 | 0.00 |
October | 0.657104E+09 | 0.440731E+09 | 0.733766E+09 | 0.295462E+09 | 0.438304E+09 | 0.00 | 0.00 |
November | 0.154152E+09 | 0.742376E+09 | 0.362787E+09 | 80756499.71 | 0.282030E+09 | 0.00 | 0.00 |
December | 0.102161E+09 | 0.104233E+10 | 0.314283E+09 | 0.108939E+09 | 0.205344E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.775483E+10 | 0.639279E+10 | 0.851301E+10 | 0.289563E+10 | 0.561737E+10 | 0.00 | 0.00 |
Minimum of Months | 0.102161E+09 | 38502580.94 | 0.314283E+09 | 80756499.71 | 0.205344E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134225E+10 | 0.115726E+10 | 0.105455E+10 | 0.399806E+09 | 0.697088E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.257349E+09 | 0.293031E+09 | 0.295319E+09 | 0.193794E+09 | 0.101525E+09 | 0.00 | 0.00 |
February | 0.301588E+09 | 0.277382E+09 | 0.353127E+09 | 0.234741E+09 | 0.118386E+09 | 0.00 | 0.00 |
March | 0.284778E+09 | 0.227260E+09 | 0.346380E+09 | 0.190729E+09 | 0.155651E+09 | 0.00 | 0.00 |
April | 0.199452E+09 | 0.155499E+09 | 0.266699E+09 | 0.107883E+09 | 0.158816E+09 | 0.00 | 0.00 |
May | 0.183244E+09 | 96967757.43 | 0.236685E+09 | 48427436.58 | 0.188257E+09 | 0.00 | 0.00 |
June | 0.213096E+09 | 41669400.76 | 0.216267E+09 | 33282119.10 | 0.182985E+09 | 0.00 | 0.00 |
July | 0.265976E+09 | 15901967.92 | 0.232537E+09 | 39213152.63 | 0.193324E+09 | 0.00 | 0.00 |
August | 0.341802E+09 | 27361583.57 | 0.311462E+09 | 0.114861E+09 | 0.196601E+09 | 0.00 | 0.00 |
September | 0.331106E+09 | 67160459.05 | 0.318164E+09 | 0.159763E+09 | 0.158401E+09 | 0.00 | 0.00 |
October | 0.486406E+09 | 0.145534E+09 | 0.464780E+09 | 0.291539E+09 | 0.173240E+09 | 0.00 | 0.00 |
November | 0.285978E+09 | 0.214970E+09 | 0.311336E+09 | 0.186777E+09 | 0.124559E+09 | 0.00 | 0.00 |
December | 0.293897E+09 | 0.273323E+09 | 0.319013E+09 | 0.226567E+09 | 92445660.92 | 0.00 | 0.00 |
Annual Sum or Average | 0.344467E+10 | 0.183606E+10 | 0.367177E+10 | 0.182758E+10 | 0.184419E+10 | 0.00 | 0.00 |
Minimum of Months | 0.183244E+09 | 15901967.92 | 0.216267E+09 | 33282119.10 | 92445660.92 | 0.00 | 0.00 |
Maximum of Months | 0.486406E+09 | 0.293031E+09 | 0.464780E+09 | 0.291539E+09 | 0.196601E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 540713.45 | 0.353751E+09 | 56833916.07 | 0.00 | 56833916.07 | 0.00 | 0.00 |
February | 2666890.76 | 0.325831E+09 | 70248208.00 | 0.00 | 70248208.00 | 0.00 | 0.00 |
March | 25377738.12 | 0.229852E+09 | 0.107879E+09 | 2144.74 | 0.107877E+09 | 0.00 | 0.00 |
April | 65495615.05 | 0.144957E+09 | 0.125630E+09 | 512072.92 | 0.125118E+09 | 0.00 | 0.00 |
May | 0.140889E+09 | 76464430.09 | 0.172653E+09 | 6300732.54 | 0.166352E+09 | 0.00 | 0.00 |
June | 0.195786E+09 | 28919991.15 | 0.176266E+09 | 9354795.85 | 0.166911E+09 | 0.00 | 0.00 |
July | 0.236943E+09 | 8596596.83 | 0.176791E+09 | 6881439.35 | 0.169909E+09 | 0.00 | 0.00 |
August | 0.216070E+09 | 17754886.54 | 0.156345E+09 | 2063845.80 | 0.154281E+09 | 0.00 | 0.00 |
September | 0.117486E+09 | 50981188.74 | 0.113935E+09 | 64742.79 | 0.113870E+09 | 0.00 | 0.00 |
October | 67378220.37 | 0.124787E+09 | 0.101807E+09 | 0.00 | 0.101807E+09 | 0.00 | 0.00 |
November | 13198621.23 | 0.225057E+09 | 69104215.38 | 0.00 | 69104215.38 | 0.00 | 0.00 |
December | 550345.09 | 0.320333E+09 | 49574277.10 | 0.00 | 49574277.10 | 0.00 | 0.00 |
Annual Sum or Average | 0.108238E+10 | 0.190729E+10 | 0.137707E+10 | 25179774.00 | 0.135189E+10 | 0.00 | 0.00 |
Minimum of Months | 540713.45 | 8596596.83 | 49574277.10 | 0.00 | 49574277.10 | 0.00 | 0.00 |
Maximum of Months | 0.236943E+09 | 0.353751E+09 | 0.176791E+09 | 9354795.85 | 0.169909E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.393001E+09 | 0.107959E+10 | 0.645581E+09 | 0.352722E+09 | 0.292859E+09 | 0.00 | 0.00 |
February | 0.532853E+09 | 0.965923E+09 | 0.829010E+09 | 0.473946E+09 | 0.355065E+09 | 0.00 | 0.00 |
March | 0.726196E+09 | 0.751314E+09 | 0.983997E+09 | 0.472602E+09 | 0.511394E+09 | 0.00 | 0.00 |
April | 0.785077E+09 | 0.485575E+09 | 0.971719E+09 | 0.415049E+09 | 0.556670E+09 | 0.00 | 0.00 |
May | 0.102954E+10 | 0.278461E+09 | 0.109207E+10 | 0.377784E+09 | 0.714290E+09 | 0.00 | 0.00 |
June | 0.108277E+10 | 0.111033E+09 | 0.985829E+09 | 0.300708E+09 | 0.685120E+09 | 0.00 | 0.00 |
July | 0.127663E+10 | 35197096.60 | 0.103228E+10 | 0.315952E+09 | 0.716325E+09 | 0.00 | 0.00 |
August | 0.148299E+10 | 71238797.11 | 0.122601E+10 | 0.521037E+09 | 0.704974E+09 | 0.00 | 0.00 |
September | 0.107375E+10 | 0.184990E+09 | 0.100348E+10 | 0.472629E+09 | 0.530847E+09 | 0.00 | 0.00 |
October | 0.112330E+10 | 0.433692E+09 | 0.114649E+10 | 0.620438E+09 | 0.526055E+09 | 0.00 | 0.00 |
November | 0.546835E+09 | 0.707684E+09 | 0.728152E+09 | 0.363764E+09 | 0.364388E+09 | 0.00 | 0.00 |
December | 0.455928E+09 | 0.963764E+09 | 0.672661E+09 | 0.412486E+09 | 0.260175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105089E+11 | 0.606846E+10 | 0.113173E+11 | 0.509912E+10 | 0.621816E+10 | 0.00 | 0.00 |
Minimum of Months | 0.393001E+09 | 35197096.60 | 0.645581E+09 | 0.300708E+09 | 0.260175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.148299E+10 | 0.107959E+10 | 0.122601E+10 | 0.620438E+09 | 0.716325E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 91798043.97 | 0.113531E+10 | 0.347392E+09 | 0.110431E+09 | 0.236960E+09 | 0.00 | 0.00 |
February | 0.167392E+09 | 0.101412E+10 | 0.475312E+09 | 0.180460E+09 | 0.294852E+09 | 0.00 | 0.00 |
March | 0.405813E+09 | 0.750844E+09 | 0.685767E+09 | 0.234146E+09 | 0.451621E+09 | 0.00 | 0.00 |
April | 0.616823E+09 | 0.479941E+09 | 0.795296E+09 | 0.280808E+09 | 0.514488E+09 | 0.00 | 0.00 |
May | 0.966392E+09 | 0.272336E+09 | 0.101195E+10 | 0.325112E+09 | 0.686834E+09 | 0.00 | 0.00 |
June | 0.104793E+10 | 0.107911E+09 | 0.935745E+09 | 0.270789E+09 | 0.664956E+09 | 0.00 | 0.00 |
July | 0.122450E+10 | 34021088.42 | 0.962507E+09 | 0.275527E+09 | 0.686980E+09 | 0.00 | 0.00 |
August | 0.131061E+10 | 68254204.19 | 0.103201E+10 | 0.380011E+09 | 0.652000E+09 | 0.00 | 0.00 |
September | 0.799220E+09 | 0.178059E+09 | 0.748092E+09 | 0.272966E+09 | 0.475125E+09 | 0.00 | 0.00 |
October | 0.598233E+09 | 0.423380E+09 | 0.692644E+09 | 0.255942E+09 | 0.436703E+09 | 0.00 | 0.00 |
November | 0.204024E+09 | 0.718917E+09 | 0.425273E+09 | 0.130247E+09 | 0.295026E+09 | 0.00 | 0.00 |
December | 0.102360E+09 | 0.101259E+10 | 0.335775E+09 | 0.129221E+09 | 0.206554E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.753510E+10 | 0.619568E+10 | 0.844776E+10 | 0.284566E+10 | 0.560210E+10 | 0.00 | 0.00 |
Minimum of Months | 91798043.97 | 34021088.42 | 0.335775E+09 | 0.110431E+09 | 0.206554E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131061E+10 | 0.113531E+10 | 0.103201E+10 | 0.380011E+09 | 0.686980E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.482656E+09 | 0.138406E+10 | 0.762996E+09 | 0.419897E+09 | 0.343098E+09 | 0.00 | 0.00 |
February | 0.590127E+09 | 0.125373E+10 | 0.917310E+09 | 0.508619E+09 | 0.408690E+09 | 0.00 | 0.00 |
March | 0.675538E+09 | 0.967750E+09 | 0.984212E+09 | 0.413262E+09 | 0.570950E+09 | 0.00 | 0.00 |
April | 0.600731E+09 | 0.621217E+09 | 0.850020E+09 | 0.234862E+09 | 0.615158E+09 | 0.00 | 0.00 |
May | 0.763956E+09 | 0.322996E+09 | 0.886854E+09 | 0.118578E+09 | 0.768276E+09 | 0.00 | 0.00 |
June | 0.976520E+09 | 0.101204E+09 | 0.850442E+09 | 92378721.32 | 0.758063E+09 | 0.00 | 0.00 |
July | 0.121034E+10 | 18988753.87 | 0.886832E+09 | 99871502.06 | 0.786961E+09 | 0.00 | 0.00 |
August | 0.131377E+10 | 59360462.43 | 0.101355E+10 | 0.253344E+09 | 0.760205E+09 | 0.00 | 0.00 |
September | 0.104137E+10 | 0.195263E+09 | 0.936194E+09 | 0.346301E+09 | 0.589893E+09 | 0.00 | 0.00 |
October | 0.124628E+10 | 0.515748E+09 | 0.122760E+10 | 0.631684E+09 | 0.595911E+09 | 0.00 | 0.00 |
November | 0.637562E+09 | 0.899602E+09 | 0.824281E+09 | 0.404693E+09 | 0.419588E+09 | 0.00 | 0.00 |
December | 0.570846E+09 | 0.123465E+10 | 0.798606E+09 | 0.490908E+09 | 0.307699E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101097E+11 | 0.757456E+10 | 0.109389E+11 | 0.401440E+10 | 0.692449E+10 | 0.00 | 0.00 |
Minimum of Months | 0.482656E+09 | 18988753.87 | 0.762996E+09 | 92378721.32 | 0.307699E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131377E+10 | 0.138406E+10 | 0.122760E+10 | 0.631684E+09 | 0.786961E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.395554E+09 | 0.108821E+10 | 0.644189E+09 | 0.355264E+09 | 0.288926E+09 | 0.00 | 0.00 |
February | 0.510267E+09 | 0.983132E+09 | 0.806245E+09 | 0.453646E+09 | 0.352599E+09 | 0.00 | 0.00 |
March | 0.771859E+09 | 0.748572E+09 | 0.103270E+10 | 0.516406E+09 | 0.516298E+09 | 0.00 | 0.00 |
April | 0.779049E+09 | 0.504187E+09 | 0.963564E+09 | 0.404165E+09 | 0.559399E+09 | 0.00 | 0.00 |
May | 0.972867E+09 | 0.297282E+09 | 0.105639E+10 | 0.349541E+09 | 0.706846E+09 | 0.00 | 0.00 |
June | 0.116064E+10 | 0.134629E+09 | 0.107442E+10 | 0.365988E+09 | 0.708429E+09 | 0.00 | 0.00 |
July | 0.129329E+10 | 49471627.32 | 0.106808E+10 | 0.341055E+09 | 0.727028E+09 | 0.00 | 0.00 |
August | 0.149591E+10 | 90191271.58 | 0.124958E+10 | 0.541276E+09 | 0.708301E+09 | 0.00 | 0.00 |
September | 0.104655E+10 | 0.209672E+09 | 0.990192E+09 | 0.458415E+09 | 0.531777E+09 | 0.00 | 0.00 |
October | 0.116734E+10 | 0.453543E+09 | 0.118859E+10 | 0.660500E+09 | 0.528089E+09 | 0.00 | 0.00 |
November | 0.479235E+09 | 0.714067E+09 | 0.666211E+09 | 0.314531E+09 | 0.351680E+09 | 0.00 | 0.00 |
December | 0.436485E+09 | 0.972659E+09 | 0.651703E+09 | 0.392526E+09 | 0.259177E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105090E+11 | 0.624562E+10 | 0.113919E+11 | 0.515331E+10 | 0.623855E+10 | 0.00 | 0.00 |
Minimum of Months | 0.395554E+09 | 49471627.32 | 0.644189E+09 | 0.314531E+09 | 0.259177E+09 | 0.00 | 0.00 |
Maximum of Months | 0.149591E+10 | 0.108821E+10 | 0.124958E+10 | 0.660500E+09 | 0.727028E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.109367E+09 | 0.115758E+10 | 0.345755E+09 | 0.112774E+09 | 0.232981E+09 | 0.00 | 0.00 |
February | 0.174210E+09 | 0.105983E+10 | 0.452257E+09 | 0.159920E+09 | 0.292337E+09 | 0.00 | 0.00 |
March | 0.458662E+09 | 0.751911E+09 | 0.734230E+09 | 0.277754E+09 | 0.456476E+09 | 0.00 | 0.00 |
April | 0.613241E+09 | 0.498813E+09 | 0.786996E+09 | 0.269815E+09 | 0.517181E+09 | 0.00 | 0.00 |
May | 0.907987E+09 | 0.289853E+09 | 0.976194E+09 | 0.296827E+09 | 0.679367E+09 | 0.00 | 0.00 |
June | 0.112432E+10 | 0.130750E+09 | 0.102429E+10 | 0.336045E+09 | 0.688247E+09 | 0.00 | 0.00 |
July | 0.123981E+10 | 48048841.95 | 0.998256E+09 | 0.300597E+09 | 0.697659E+09 | 0.00 | 0.00 |
August | 0.132240E+10 | 86326381.10 | 0.105542E+10 | 0.400134E+09 | 0.655284E+09 | 0.00 | 0.00 |
September | 0.773972E+09 | 0.202560E+09 | 0.734598E+09 | 0.258589E+09 | 0.476009E+09 | 0.00 | 0.00 |
October | 0.648498E+09 | 0.445652E+09 | 0.734368E+09 | 0.295704E+09 | 0.438664E+09 | 0.00 | 0.00 |
November | 0.154525E+09 | 0.739433E+09 | 0.363085E+09 | 80822747.87 | 0.282262E+09 | 0.00 | 0.00 |
December | 0.103361E+09 | 0.103985E+10 | 0.314541E+09 | 0.109028E+09 | 0.205512E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.763035E+10 | 0.645060E+10 | 0.851999E+10 | 0.289801E+10 | 0.562198E+10 | 0.00 | 0.00 |
Minimum of Months | 0.103361E+09 | 48048841.95 | 0.314541E+09 | 80822747.87 | 0.205512E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132240E+10 | 0.115758E+10 | 0.105542E+10 | 0.400134E+09 | 0.697659E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.456926E+09 | 0.565523E+09 | 0.541944E+09 | 0.355634E+09 | 0.186310E+09 | 0.00 | 0.00 |
February | 0.541566E+09 | 0.514540E+09 | 0.648029E+09 | 0.430777E+09 | 0.217251E+09 | 0.00 | 0.00 |
March | 0.515237E+09 | 0.404462E+09 | 0.635647E+09 | 0.350010E+09 | 0.285637E+09 | 0.00 | 0.00 |
April | 0.365478E+09 | 0.267300E+09 | 0.489423E+09 | 0.197978E+09 | 0.291446E+09 | 0.00 | 0.00 |
May | 0.345617E+09 | 0.152803E+09 | 0.434344E+09 | 88869854.15 | 0.345474E+09 | 0.00 | 0.00 |
June | 0.397494E+09 | 60822361.24 | 0.396874E+09 | 61076473.97 | 0.335798E+09 | 0.00 | 0.00 |
July | 0.496944E+09 | 20029496.34 | 0.426732E+09 | 71960595.08 | 0.354772E+09 | 0.00 | 0.00 |
August | 0.636982E+09 | 39999158.29 | 0.571569E+09 | 0.210784E+09 | 0.360785E+09 | 0.00 | 0.00 |
September | 0.609260E+09 | 0.105083E+09 | 0.583867E+09 | 0.293183E+09 | 0.290684E+09 | 0.00 | 0.00 |
October | 0.892148E+09 | 0.235627E+09 | 0.852923E+09 | 0.535007E+09 | 0.317916E+09 | 0.00 | 0.00 |
November | 0.523023E+09 | 0.376671E+09 | 0.571337E+09 | 0.342756E+09 | 0.228581E+09 | 0.00 | 0.00 |
December | 0.529885E+09 | 0.506095E+09 | 0.585425E+09 | 0.415776E+09 | 0.169648E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.631056E+10 | 0.324895E+10 | 0.673811E+10 | 0.335381E+10 | 0.338430E+10 | 0.00 | 0.00 |
Minimum of Months | 0.345617E+09 | 20029496.34 | 0.396874E+09 | 61076473.97 | 0.169648E+09 | 0.00 | 0.00 |
Maximum of Months | 0.892148E+09 | 0.565523E+09 | 0.852923E+09 | 0.535007E+09 | 0.360785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 467538.78 | 0.358582E+10 | 0.497620E+09 | 0.00 | 0.497620E+09 | 0.00 | 0.00 |
February | 7645669.59 | 0.328640E+10 | 0.615071E+09 | 0.00 | 0.615071E+09 | 0.00 | 0.00 |
March | 0.144774E+09 | 0.242584E+10 | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.00 | 0.00 |
April | 0.460652E+09 | 0.157957E+10 | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.00 | 0.00 |
May | 0.107800E+10 | 0.865426E+09 | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.00 | 0.00 |
June | 0.159396E+10 | 0.375785E+09 | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.00 | 0.00 |
July | 0.193503E+10 | 0.157348E+09 | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.00 | 0.00 |
August | 0.173917E+10 | 0.250893E+09 | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.00 | 0.00 |
September | 0.934313E+09 | 0.618856E+09 | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.00 | 0.00 |
October | 0.487310E+09 | 0.137095E+10 | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.00 | 0.00 |
November | 71758166.10 | 0.238707E+10 | 0.605055E+09 | 0.00 | 0.605055E+09 | 0.00 | 0.00 |
December | 1207482.65 | 0.330094E+10 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.845430E+10 | 0.202049E+11 | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.00 | 0.00 |
Minimum of Months | 467538.78 | 0.157348E+09 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.193503E+10 | 0.358582E+10 | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 192470.31 | 0.369825E+10 | 0.497620E+09 | 0.00 | 0.497620E+09 | 0.00 | 0.00 |
February | 5145552.07 | 0.338447E+10 | 0.615071E+09 | 0.00 | 0.615071E+09 | 0.00 | 0.00 |
March | 0.127300E+09 | 0.250862E+10 | 0.944558E+09 | 18778.64 | 0.944539E+09 | 0.00 | 0.00 |
April | 0.428554E+09 | 0.164011E+10 | 0.109998E+10 | 4483549.59 | 0.109550E+10 | 0.00 | 0.00 |
May | 0.102670E+10 | 0.904857E+09 | 0.151169E+10 | 55167234.08 | 0.145653E+10 | 0.00 | 0.00 |
June | 0.154284E+10 | 0.403620E+09 | 0.154333E+10 | 81907652.62 | 0.146142E+10 | 0.00 | 0.00 |
July | 0.188490E+10 | 0.179098E+09 | 0.154793E+10 | 60251720.42 | 0.148767E+10 | 0.00 | 0.00 |
August | 0.169137E+10 | 0.273150E+09 | 0.136891E+10 | 18070385.21 | 0.135084E+10 | 0.00 | 0.00 |
September | 0.893889E+09 | 0.660790E+09 | 0.997579E+09 | 566867.54 | 0.997012E+09 | 0.00 | 0.00 |
October | 0.456721E+09 | 0.142754E+10 | 0.891388E+09 | 0.00 | 0.891388E+09 | 0.00 | 0.00 |
November | 61948083.97 | 0.247542E+10 | 0.605055E+09 | 0.00 | 0.605055E+09 | 0.00 | 0.00 |
December | 757642.52 | 0.340623E+10 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.812031E+10 | 0.209621E+11 | 0.120572E+11 | 0.220466E+09 | 0.118367E+11 | 0.00 | 0.00 |
Minimum of Months | 192470.31 | 0.179098E+09 | 0.434057E+09 | 0.00 | 0.434057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188490E+10 | 0.369825E+10 | 0.154793E+10 | 81907652.62 | 0.148767E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.430519E+09 | 0.245091E+10 | 0.993748E+09 | 0.463517E+09 | 0.530230E+09 | 0.00 | 0.00 |
February | 0.648675E+09 | 0.214985E+10 | 0.130534E+10 | 0.654917E+09 | 0.650420E+09 | 0.00 | 0.00 |
March | 0.113196E+10 | 0.173001E+10 | 0.167106E+10 | 0.707295E+09 | 0.963760E+09 | 0.00 | 0.00 |
April | 0.145739E+10 | 0.115601E+10 | 0.176837E+10 | 0.696388E+09 | 0.107199E+10 | 0.00 | 0.00 |
May | 0.214098E+10 | 0.673205E+09 | 0.210563E+10 | 0.703427E+09 | 0.140220E+10 | 0.00 | 0.00 |
June | 0.236644E+10 | 0.284618E+09 | 0.192305E+10 | 0.571929E+09 | 0.135112E+10 | 0.00 | 0.00 |
July | 0.279353E+10 | 0.105840E+09 | 0.199631E+10 | 0.591926E+09 | 0.140439E+10 | 0.00 | 0.00 |
August | 0.307461E+10 | 0.170809E+09 | 0.225976E+10 | 0.901733E+09 | 0.135802E+10 | 0.00 | 0.00 |
September | 0.207053E+10 | 0.426623E+09 | 0.175292E+10 | 0.746168E+09 | 0.100675E+10 | 0.00 | 0.00 |
October | 0.182033E+10 | 0.971877E+09 | 0.184057E+10 | 0.877062E+09 | 0.963503E+09 | 0.00 | 0.00 |
November | 0.743702E+09 | 0.163787E+10 | 0.115432E+10 | 0.494398E+09 | 0.659925E+09 | 0.00 | 0.00 |
December | 0.513170E+09 | 0.219730E+10 | 0.100922E+10 | 0.542133E+09 | 0.467091E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.191918E+11 | 0.139549E+11 | 0.197803E+11 | 0.795089E+10 | 0.118294E+11 | 0.00 | 0.00 |
Minimum of Months | 0.430519E+09 | 0.105840E+09 | 0.993748E+09 | 0.463517E+09 | 0.467091E+09 | 0.00 | 0.00 |
Maximum of Months | 0.307461E+10 | 0.245091E+10 | 0.225976E+10 | 0.901733E+09 | 0.140439E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106766E+10 | 0.249064E+10 | 0.155013E+10 | 0.905285E+09 | 0.644848E+09 | 0.00 | 0.00 |
February | 0.129327E+10 | 0.224712E+10 | 0.186044E+10 | 0.109657E+10 | 0.763873E+09 | 0.00 | 0.00 |
March | 0.138378E+10 | 0.175926E+10 | 0.194187E+10 | 0.890975E+09 | 0.105089E+10 | 0.00 | 0.00 |
April | 0.113943E+10 | 0.114718E+10 | 0.162293E+10 | 0.505499E+09 | 0.111743E+10 | 0.00 | 0.00 |
May | 0.133033E+10 | 0.617713E+09 | 0.162386E+10 | 0.245134E+09 | 0.137872E+10 | 0.00 | 0.00 |
June | 0.164942E+10 | 0.224175E+09 | 0.153932E+10 | 0.183552E+09 | 0.135577E+10 | 0.00 | 0.00 |
July | 0.201108E+10 | 66289148.57 | 0.161690E+10 | 0.203834E+09 | 0.141307E+10 | 0.00 | 0.00 |
August | 0.228682E+10 | 0.146740E+09 | 0.192422E+10 | 0.542756E+09 | 0.138147E+10 | 0.00 | 0.00 |
September | 0.195799E+10 | 0.390447E+09 | 0.182824E+10 | 0.746506E+09 | 0.108173E+10 | 0.00 | 0.00 |
October | 0.251027E+10 | 0.958052E+09 | 0.247673E+10 | 0.136189E+10 | 0.111484E+10 | 0.00 | 0.00 |
November | 0.134042E+10 | 0.163079E+10 | 0.166178E+10 | 0.872504E+09 | 0.789278E+09 | 0.00 | 0.00 |
December | 0.125685E+10 | 0.222075E+10 | 0.163903E+10 | 0.105838E+10 | 0.580644E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.192273E+11 | 0.138992E+11 | 0.212854E+11 | 0.861288E+10 | 0.126726E+11 | 0.00 | 0.00 |
Minimum of Months | 0.106766E+10 | 66289148.57 | 0.153932E+10 | 0.183552E+09 | 0.580644E+09 | 0.00 | 0.00 |
Maximum of Months | 0.251027E+10 | 0.249064E+10 | 0.247673E+10 | 0.136189E+10 | 0.141307E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.366451E+11 | -.716262E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.151086E+10 | 59.22 | 0.00 | 0.00 |
February | 0.338514E+11 | -.653670E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.138102E+10 | 59.24 | 0.00 | 0.00 |
March | 0.357706E+11 | -.707930E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154228E+10 | 59.25 | 0.00 | 0.00 |
April | 0.307730E+11 | -.649680E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.151375E+10 | 59.38 | 0.00 | 0.00 |
May | 0.267419E+11 | -.624676E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.159602E+10 | 59.60 | 0.00 | 0.00 |
June | 0.212143E+11 | -.561633E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.156279E+10 | 59.87 | 0.00 | 0.00 |
July | 0.186172E+11 | -.549995E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.162288E+10 | 60.11 | 0.00 | 0.00 |
August | 0.178092E+11 | -.542690E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.161451E+10 | 60.24 | 0.00 | 0.00 |
September | 0.188930E+11 | -.540723E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.152688E+10 | 60.00 | 0.00 | 0.00 |
October | 0.234620E+11 | -.595384E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.152337E+10 | 59.78 | 0.00 | 0.00 |
November | 0.276059E+11 | -.621338E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.144639E+10 | 59.52 | 0.00 | 0.00 |
December | 0.333476E+11 | -.686203E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.149532E+10 | 59.35 | 0.00 | 0.00 |
Annual Sum or Average | 0.324731E+12 | -.745018E+12 | 8760.00 | -.183361E+11 | 59.63 | |||||
Minimum of Months | 0.178092E+11 | -.716262E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.162288E+10 | 59.22 | 0.00 | 0.00 |
Maximum of Months | 0.366451E+11 | -.540723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.138102E+10 | 60.24 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770509E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162301759.6 | 81.21 | 0.00 | 0.00 |
February | 0.696266E+10 | -.681596E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146699438.1 | 81.21 | 0.00 | 0.00 |
March | 0.770471E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161900836.5 | 81.21 | 0.00 | 0.00 |
April | 0.746515E+10 | -.730860E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156552950.1 | 81.21 | 0.00 | 0.00 |
May | 0.770508E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162273920.0 | 81.21 | 0.00 | 0.00 |
June | 0.745811E+10 | -.730052E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157591285.6 | 81.21 | 0.00 | 0.00 |
July | 0.771383E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162989877.7 | 81.21 | 0.00 | 0.00 |
August | 0.770569E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162899625.0 | 81.21 | 0.00 | 0.00 |
September | 0.746606E+10 | -.730858E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157485232.8 | 81.21 | 0.00 | 0.00 |
October | 0.770480E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162017790.3 | 81.21 | 0.00 | 0.00 |
November | 0.744909E+10 | -.729245E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156643007.5 | 81.21 | 0.00 | 0.00 |
December | 0.771304E+10 | -.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162177956.2 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907533E+11 | -.888418E+11 | 8760.00 | -.191153E+10 | 81.21 | |||||
Minimum of Months | 0.696266E+10 | -.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162989877.7 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771383E+10 | -.681596E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146699438.1 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.786903E+11 | -.774878E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120248E+10 | 62.95 | 0.00 | 0.00 |
February | 0.711406E+11 | -.700486E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.109205E+10 | 62.76 | 0.00 | 0.00 |
March | 0.786002E+11 | -.773721E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122813E+10 | 63.09 | 0.00 | 0.00 |
April | 0.757246E+11 | -.745001E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122454E+10 | 63.93 | 0.00 | 0.00 |
May | 0.777801E+11 | -.764672E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131287E+10 | 64.96 | 0.00 | 0.00 |
June | 0.748447E+11 | -.735404E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.130422E+10 | 65.93 | 0.00 | 0.00 |
July | 0.770350E+11 | -.756690E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.136599E+10 | 66.59 | 0.00 | 0.00 |
August | 0.769529E+11 | -.755918E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.136107E+10 | 66.76 | 0.00 | 0.00 |
September | 0.746289E+11 | -.733410E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128794E+10 | 66.39 | 0.00 | 0.00 |
October | 0.774806E+11 | -.762069E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.127367E+10 | 65.58 | 0.00 | 0.00 |
November | 0.754341E+11 | -.742428E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.119128E+10 | 64.59 | 0.00 | 0.00 |
December | 0.783876E+11 | -.771812E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120643E+10 | 63.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.916700E+12 | -.901649E+12 | 8760.00 | -.150507E+11 | 64.77 | |||||
Minimum of Months | 0.711406E+11 | -.774878E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.136599E+10 | 62.76 | 0.00 | 0.00 |
Maximum of Months | 0.786903E+11 | -.700486E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.109205E+10 | 66.76 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.87 | 0.86 | 01-JAN-07:49 | 6295.74 | 37.26 | 197.00 | 252.00 | 3007.56 | 34.06 | 191.00 | 193.50 |
February | 216.00 | 0.87 | 0.86 | 01-FEB-07:49 | 9218.39 | 37.89 | 208.33 | 263.33 | 1307.57 | 27.58 | 211.00 | 232.17 |
March | 275.00 | 0.87 | 0.86 | 01-MAR-06:00 | 4457.36 | 26.07 | 176.00 | 331.00 | 809.55 | 22.98 | 217.67 | 278.33 |
April | 261.17 | 0.87 | 0.86 | 01-APR-14:39 | 1586.40 | 20.80 | 109.00 | 349.00 | 646.91 | 22.55 | 210.33 | 291.00 |
May | 372.00 | 0.87 | 0.86 | 01-MAY-06:10 | 1435.48 | 20.53 | 182.17 | 402.50 | 570.28 | 22.25 | 254.67 | 337.50 |
June | 351.83 | 0.87 | 0.86 | 01-JUN-05:00 | 1361.22 | 20.43 | 143.50 | 393.67 | 549.60 | 22.18 | 262.67 | 331.33 |
July | 365.17 | 0.87 | 0.86 | 01-JUL-06:19 | 1517.77 | 20.59 | 165.17 | 401.33 | 601.37 | 22.33 | 281.00 | 334.50 |
August | 389.17 | 0.87 | 0.86 | 01-AUG-06:19 | 1625.20 | 20.86 | 200.67 | 378.00 | 658.07 | 22.59 | 315.33 | 333.33 |
September | 285.33 | 0.87 | 0.86 | 01-SEP-06:40 | 1808.53 | 20.98 | 130.50 | 332.17 | 730.60 | 22.75 | 242.67 | 283.17 |
October | 305.50 | 0.87 | 0.86 | 01-OCT-14:39 | 9175.04 | 36.28 | 288.50 | 313.17 | 1118.53 | 25.29 | 280.33 | 286.83 |
November | 240.83 | 0.87 | 0.86 | 01-NOV-06:00 | 6248.25 | 36.71 | 235.17 | 261.83 | 1661.27 | 30.20 | 227.33 | 234.00 |
December | 211.17 | 0.87 | 0.86 | 01-DEC-07:40 | 5845.70 | 38.25 | 208.00 | 251.33 | 4516.13 | 38.23 | 207.67 | 212.83 |
Annual Sum or Average | 3472.67 | 0.87 | 3785.31 | 26.69 | 2244.00 | 3929.33 | 1168.89 | 25.21 | 2901.67 | 3348.50 | ||
Minimum of Months | 199.50 | 0.87 | 0.86 | 1361.22 | 20.43 | 109.00 | 251.33 | 549.60 | 22.18 | 191.00 | 193.50 | |
Maximum of Months | 389.17 | 0.87 | 0.86 | 9218.39 | 38.25 | 288.50 | 402.50 | 4516.13 | 38.23 | 315.33 | 337.50 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.25 | 0.22 | 01-JAN-07:49 | 6774.69 | 37.33 | 197.00 | 261.50 | 3487.01 | 34.00 | 193.50 | 228.17 |
February | 216.00 | 0.25 | 0.22 | 01-FEB-07:40 | 9766.57 | 37.97 | 208.50 | 271.17 | 1855.06 | 27.21 | 202.00 | 250.17 |
March | 275.00 | 0.25 | 0.22 | 01-MAR-06:00 | 4905.30 | 26.17 | 168.83 | 339.33 | 1255.54 | 22.94 | 235.67 | 311.50 |
April | 261.17 | 0.26 | 0.22 | 01-APR-06:30 | 1932.53 | 21.05 | 110.83 | 360.83 | 992.05 | 22.64 | 255.50 | 327.67 |
May | 372.00 | 0.25 | 0.22 | 01-MAY-05:49 | 1684.38 | 21.06 | 189.00 | 415.00 | 818.19 | 22.60 | 288.50 | 379.50 |
June | 351.83 | 0.26 | 0.22 | 01-JUN-05:30 | 1599.22 | 20.98 | 187.50 | 409.00 | 786.69 | 22.54 | 297.50 | 368.33 |
July | 365.17 | 0.25 | 0.22 | 01-JUL-05:30 | 1771.25 | 21.12 | 206.67 | 418.83 | 853.80 | 22.68 | 309.50 | 374.83 |
August | 389.17 | 0.26 | 0.22 | 01-AUG-05:49 | 1944.87 | 21.19 | 211.17 | 387.83 | 976.68 | 22.76 | 330.67 | 363.50 |
September | 285.33 | 0.26 | 0.22 | 01-SEP-06:10 | 2208.43 | 21.09 | 127.50 | 343.83 | 1129.25 | 22.73 | 250.33 | 312.50 |
October | 305.50 | 0.24 | 0.22 | 01-OCT-14:39 | 9722.62 | 36.34 | 279.00 | 318.67 | 1664.20 | 25.08 | 285.67 | 302.83 |
November | 240.83 | 0.25 | 0.22 | 01-NOV-06:49 | 6694.84 | 36.78 | 235.17 | 269.50 | 2103.71 | 30.08 | 234.17 | 252.83 |
December | 211.17 | 0.26 | 0.22 | 01-DEC-07:30 | 6322.01 | 38.30 | 208.00 | 258.50 | 4990.14 | 38.23 | 205.50 | 237.17 |
Annual Sum or Average | 3472.67 | 0.25 | 4162.64 | 26.95 | 2329.17 | 4054.00 | 1544.85 | 25.29 | 3088.50 | 3709.00 | ||
Minimum of Months | 199.50 | 0.24 | 0.22 | 1599.22 | 20.98 | 110.83 | 258.50 | 786.69 | 22.54 | 193.50 | 228.17 | |
Maximum of Months | 389.17 | 0.26 | 0.22 | 9766.57 | 38.30 | 279.00 | 418.83 | 4990.14 | 38.23 | 330.67 | 379.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.60 | 01-JAN-08:00 | 475.74 | 15.54 | 0.00 | 238.50 | 229.42 | 18.95 | 0.00 | 134.00 |
February | 216.00 | 0.65 | 0.60 | 01-FEB-08:50 | 489.01 | 16.23 | 0.00 | 252.17 | 250.68 | 19.68 | 0.17 | 174.17 |
March | 275.00 | 0.63 | 0.60 | 01-MAR-07:30 | 670.45 | 17.56 | 0.00 | 329.50 | 323.29 | 20.79 | 66.50 | 258.33 |
April | 261.17 | 0.62 | 0.60 | 01-APR-14:39 | 738.68 | 18.14 | 0.00 | 358.67 | 356.21 | 21.36 | 121.50 | 309.67 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:49 | 1014.43 | 18.82 | 0.00 | 420.33 | 453.11 | 22.71 | 264.67 | 380.00 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-04:00 | 1126.27 | 19.93 | 29.00 | 413.50 | 489.51 | 23.73 | 283.33 | 381.00 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 1131.92 | 18.87 | 0.00 | 422.67 | 488.27 | 23.38 | 291.50 | 382.17 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:40 | 897.17 | 18.57 | 0.00 | 390.17 | 415.11 | 21.79 | 267.67 | 361.17 |
September | 285.33 | 0.63 | 0.60 | 01-SEP-06:19 | 676.92 | 17.77 | 0.00 | 337.33 | 330.73 | 21.01 | 97.00 | 283.00 |
October | 305.50 | 0.63 | 0.60 | 01-OCT-14:39 | 612.31 | 17.33 | 0.00 | 304.50 | 313.72 | 20.68 | 26.00 | 257.00 |
November | 240.83 | 0.65 | 0.60 | 01-NOV-07:30 | 534.59 | 16.09 | 0.00 | 252.50 | 250.60 | 19.41 | 0.00 | 172.00 |
December | 211.17 | 0.69 | 0.60 | 01-DEC-09:09 | 376.73 | 14.67 | 0.00 | 228.00 | 189.34 | 18.22 | 0.00 | 91.50 |
Annual Sum or Average | 3472.67 | 0.63 | 778.21 | 17.75 | 29.00 | 3947.83 | 360.83 | 21.30 | 1418.33 | 3184.00 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 376.73 | 14.67 | 0.00 | 228.00 | 189.34 | 18.22 | 0.00 | 91.50 | |
Maximum of Months | 389.17 | 0.69 | 0.60 | 1131.92 | 19.93 | 29.00 | 422.67 | 489.51 | 23.73 | 291.50 | 382.17 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.60 | 01-JAN-08:00 | 475.74 | 15.54 | 0.00 | 238.50 | 229.42 | 18.95 | 0.00 | 134.00 |
February | 216.00 | 0.65 | 0.60 | 01-FEB-08:50 | 489.01 | 16.23 | 0.00 | 252.17 | 250.68 | 19.68 | 0.17 | 174.17 |
March | 275.00 | 0.63 | 0.60 | 01-MAR-07:30 | 670.45 | 17.56 | 0.00 | 329.50 | 323.29 | 20.79 | 66.50 | 258.33 |
April | 261.17 | 0.62 | 0.60 | 01-APR-14:39 | 738.68 | 18.14 | 0.00 | 358.67 | 356.21 | 21.36 | 121.50 | 309.67 |
May | 372.00 | 0.61 | 0.60 | 01-MAY-05:49 | 1014.43 | 18.82 | 0.00 | 420.33 | 453.11 | 22.71 | 264.67 | 380.00 |
June | 351.83 | 0.61 | 0.60 | 01-JUN-04:00 | 1126.27 | 19.93 | 29.00 | 413.50 | 489.51 | 23.73 | 283.33 | 381.00 |
July | 365.17 | 0.61 | 0.60 | 01-JUL-04:00 | 1131.92 | 18.87 | 0.00 | 422.67 | 488.27 | 23.38 | 291.50 | 382.17 |
August | 389.17 | 0.62 | 0.60 | 01-AUG-05:40 | 897.17 | 18.57 | 0.00 | 390.17 | 415.11 | 21.79 | 267.67 | 361.17 |
September | 285.33 | 0.63 | 0.60 | 01-SEP-06:19 | 676.92 | 17.77 | 0.00 | 337.33 | 330.73 | 21.01 | 97.00 | 283.00 |
October | 305.50 | 0.63 | 0.60 | 01-OCT-14:39 | 612.31 | 17.33 | 0.00 | 304.50 | 313.72 | 20.68 | 26.00 | 257.00 |
November | 240.83 | 0.65 | 0.60 | 01-NOV-07:30 | 534.59 | 16.09 | 0.00 | 252.50 | 250.60 | 19.41 | 0.00 | 172.00 |
December | 211.17 | 0.69 | 0.60 | 01-DEC-09:09 | 376.73 | 14.67 | 0.00 | 228.00 | 189.34 | 18.22 | 0.00 | 91.50 |
Annual Sum or Average | 3472.67 | 0.63 | 778.21 | 17.75 | 29.00 | 3947.83 | 360.83 | 21.30 | 1418.33 | 3184.00 | ||
Minimum of Months | 199.50 | 0.61 | 0.60 | 376.73 | 14.67 | 0.00 | 228.00 | 189.34 | 18.22 | 0.00 | 91.50 | |
Maximum of Months | 389.17 | 0.69 | 0.60 | 1131.92 | 19.93 | 29.00 | 422.67 | 489.51 | 23.73 | 291.50 | 382.17 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97242985.05 | 2921.92 | 10-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147452E+10 | 5180.67 | 28-MAY-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241778E+10 | 5061.22 | 18-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117599E+10 | 3695.46 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27081922.96 | 1725.64 | 01-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.519261E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.241778E+10 | 5180.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324805E+10 | 2746.22 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.264291E+10 | 2746.22 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183344E+10 | 2268.27 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117928E+10 | 2089.31 | 23-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.645570E+09 | 1884.81 | 01-MAY-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.224096E+09 | 586.13 | 04-JUN-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 55727182.18 | 497.22 | 01-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28479885.95 | 405.86 | 07-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.281738E+09 | 1759.90 | 24-SEP-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272306E+09 | 1766.39 | 02-OCT-04:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155546E+10 | 2444.86 | 27-NOV-07:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254283E+10 | 2098.23 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145099E+11 | |||||||
Minimum of Months | 28479885.95 | 405.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324805E+10 | 2746.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123011E+09 | 581.39 | 03-JAN-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 92494736.71 | 479.46 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8487324.52 | 281.36 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2571385.79 | 464.35 | 18-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4192058.52 | 105.60 | 25-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3630911.86 | 163.49 | 12-JUN-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4141232.85 | 159.54 | 17-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5896420.38 | 339.13 | 26-NOV-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 45109569.44 | 386.03 | 11-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289535E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123011E+09 | 581.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114958E+10 | 1344.03 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112141E+10 | 1307.03 | 06-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.460433E+09 | 1001.26 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146390E+09 | 865.86 | 18-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40736368.53 | 232.83 | 25-MAY-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3237101.98 | 106.45 | 12-JUN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6206918.92 | 177.53 | 26-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.263947E+09 | 994.65 | 26-NOV-09:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671303E+09 | 1131.11 | 16-DEC-12:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386325E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.114958E+10 | 1344.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136445E+10 | 1003.95 | 02-JAN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129267E+10 | 1003.95 | 06-FEB-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744168E+09 | 764.74 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.341182E+09 | 601.83 | 18-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102119E+09 | 445.65 | 04-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8057140.94 | 99.45 | 06-JUN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24406849.06 | 409.33 | 24-SEP-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14881541.51 | 210.41 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.497578E+09 | 698.76 | 24-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101599E+10 | 768.15 | 31-DEC-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540549E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.136445E+10 | 1003.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595885E+09 | 4673.64 | 24-JAN-02:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.580512E+09 | 8750.79 | 19-FEB-11:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.564771E+09 | 8543.28 | 28-MAR-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109638E+10 | 8610.75 | 25-APR-04:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213687E+10 | 8544.10 | 17-MAY-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.472946E+10 | 7871.89 | 30-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.536116E+10 | 8070.23 | 24-JUL-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.495127E+10 | 7711.73 | 12-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.398195E+10 | 7871.90 | 22-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177375E+10 | 8534.30 | 02-OCT-04:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.510077E+09 | 8659.75 | 03-NOV-03:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537629E+09 | 6019.24 | 19-DEC-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268197E+11 | |||||||
Minimum of Months | 0.510077E+09 | 4673.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.536116E+10 | 8750.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225561E+10 | 6250.12 | 14-JAN-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147464E+10 | 5489.91 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.850272E+09 | 5457.49 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.450555E+09 | 4865.91 | 18-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.266237E+09 | 3129.17 | 04-MAY-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.114817E+09 | 1583.60 | 07-JUN-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6245665.05 | 687.98 | 18-JUL-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2901987.36 | 646.70 | 06-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126120E+09 | 1945.96 | 27-SEP-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 32323913.44 | 1360.09 | 31-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466635E+09 | 5997.65 | 27-NOV-07:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140554E+10 | 5123.09 | 11-DEC-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.745190E+10 | |||||||
Minimum of Months | 2901987.36 | 646.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.225561E+10 | 6250.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103080E+10 | 9717.24 | 08-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.600301E+09 | 7396.37 | 27-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72964551.20 | 4398.77 | 17-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8383547.48 | 1571.29 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8237089.36 | 1625.36 | 24-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29959826.89 | 2270.68 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34100255.79 | 2257.44 | 17-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39128142.48 | 5619.53 | 26-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.387712E+09 | 6488.88 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221159E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103080E+10 | 9717.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486368E+10 | 7070.49 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405732E+10 | 7067.44 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206390E+10 | 7065.82 | 17-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.951346E+09 | 7059.46 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111065E+09 | 3522.94 | 13-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3659762.00 | 3503.34 | 11-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1165997.79 | 2063.15 | 11-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1682266.76 | 2947.14 | 26-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18563581.98 | 4185.35 | 10-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.245002E+09 | 6759.67 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226088E+10 | 7065.59 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386595E+10 | 7067.00 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184442E+11 | |||||||
Minimum of Months | 1165997.79 | 2063.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486368E+10 | 7070.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.573618E+10 | 7055.30 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510119E+10 | 7052.21 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.255092E+10 | 7050.95 | 09-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108100E+10 | 7051.75 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120747E+09 | 3608.43 | 13-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3500742.16 | 3385.19 | 11-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1163007.82 | 2063.94 | 11-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1916396.13 | 3065.19 | 19-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26935549.28 | 3895.82 | 19-SEP-21:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444808E+09 | 6871.87 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.291797E+10 | 7050.98 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.480258E+10 | 7051.85 | 29-DEC-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227889E+11 | |||||||
Minimum of Months | 1163007.82 | 2063.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.573618E+10 | 7055.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535383E+10 | 17664.58 | 02-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120011E+10 | 12988.72 | 07-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133356E+09 | 7190.34 | 01-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148161E+10 | 11982.27 | 31-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.816890E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.535383E+10 | 17664.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184846E+11 | 40583.20 | 08-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.181650E+11 | 40575.24 | 09-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.599327E+10 | 40052.24 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.116253E+10 | 39277.39 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87099398.90 | 26600.32 | 16-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12518378.95 | 24776.81 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 517440.58 | 5483.08 | 17-JUL-08:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5388971.01 | 13401.38 | 22-AUG-18:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54294581.52 | 24774.99 | 30-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.435921E+09 | 38863.14 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.580148E+10 | 40229.32 | 24-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132382E+11 | 40427.45 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.634409E+11 | |||||||
Minimum of Months | 517440.58 | 5483.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184846E+11 | 40583.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.484821E+10 | 6833.71 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.397533E+10 | 6830.56 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.216321E+10 | 6829.08 | 08-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.956303E+09 | 6826.00 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129395E+09 | 3756.70 | 15-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2890557.72 | 3253.45 | 07-JUN-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 270240.98 | 1514.37 | 24-JUL-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 363532.66 | 1411.58 | 07-AUG-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15755839.88 | 3743.29 | 27-SEP-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272686E+09 | 6153.33 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.214905E+10 | 6828.66 | 25-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382648E+10 | 6830.12 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183399E+11 | |||||||
Minimum of Months | 270240.98 | 1411.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.484821E+10 | 6833.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.571152E+10 | 6833.13 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.500164E+10 | 6829.95 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268143E+10 | 6828.48 | 08-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109089E+10 | 6830.53 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143096E+09 | 3660.01 | 01-MAY-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3055553.43 | 3236.76 | 07-JUN-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 308656.23 | 1664.86 | 24-JUL-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 501925.96 | 1319.96 | 07-AUG-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24613988.58 | 3401.38 | 16-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.481560E+09 | 6644.30 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272812E+10 | 6828.68 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471060E+10 | 6831.48 | 25-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225773E+11 | |||||||
Minimum of Months | 308656.23 | 1319.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.571152E+10 | 6833.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174987E+11 | 9236.51 | 21-JAN-20:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148358E+11 | 8463.72 | 06-FEB-18:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116968E+11 | 9503.44 | 12-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.827846E+10 | 9326.45 | 25-APR-04:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541707E+10 | 8233.09 | 04-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.233375E+10 | 3909.31 | 07-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110297E+10 | 3700.71 | 01-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.739250E+09 | 3338.13 | 07-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.327548E+10 | 7813.24 | 24-SEP-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.445355E+10 | 8410.12 | 02-OCT-04:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114458E+11 | 9473.94 | 27-NOV-07:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154043E+11 | 9217.06 | 25-DEC-07:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.964819E+11 | |||||||
Minimum of Months | 0.739250E+09 | 3338.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174987E+11 | 9503.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.162966E+10 | 2040.72 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137774E+10 | 2039.94 | 28-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.720674E+09 | 2040.04 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.337019E+09 | 2039.95 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41305767.32 | 923.75 | 13-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 421589.11 | 904.87 | 03-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78504.02 | 659.15 | 11-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 180248.98 | 552.71 | 23-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5944262.65 | 1186.44 | 10-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99134057.06 | 1985.48 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.796625E+09 | 2041.04 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133009E+10 | 2040.01 | 30-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.633887E+10 | |||||||
Minimum of Months | 78504.02 | 552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.162966E+10 | 2041.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189732E+10 | 2037.82 | 24-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169255E+10 | 2037.02 | 28-FEB-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.874778E+09 | 2037.13 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.378394E+09 | 2037.03 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44618777.37 | 1034.74 | 09-MAY-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 445694.70 | 920.27 | 03-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95492.05 | 698.50 | 11-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 336892.24 | 742.64 | 26-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8438457.71 | 1079.68 | 10-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167461E+09 | 2003.60 | 31-OCT-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.100932E+10 | 2038.13 | 26-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162479E+10 | 2037.09 | 30-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.769855E+10 | |||||||
Minimum of Months | 95492.05 | 698.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189732E+10 | 2038.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.479886E+10 | 9198.14 | 03-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.353965E+10 | 9194.28 | 28-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.198228E+10 | 9190.52 | 16-MAR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.952406E+09 | 9167.07 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81211391.02 | 3990.32 | 25-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2452826.27 | 4875.86 | 04-JUN-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 167464.47 | 935.30 | 23-JUL-08:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 546559.54 | 2681.56 | 08-AUG-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7106018.22 | 3131.22 | 26-SEP-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.107560E+09 | 3801.51 | 28-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.162201E+10 | 9112.37 | 28-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348237E+10 | 9192.27 | 12-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165766E+11 | |||||||
Minimum of Months | 167464.47 | 935.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.479886E+10 | 9198.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 196556.81 | 618.65 | 28-MAR-02:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2046414.77 | 2507.84 | 25-APR-01:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 316804.65 | 1056.02 | 17-MAY-03:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 257402.30 | 145.78 | 30-JUN-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 119539.75 | 145.78 | 24-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16884.96 | 28.14 | 24-AUG-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 238034.28 | 188.94 | 22-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71036.92 | 236.79 | 16-OCT-01:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3262674.45 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2046414.77 | 2507.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.691628E+10 | 5243.03 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.606651E+10 | 5244.05 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365764E+10 | 4391.71 | 01-MAR-07:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.188327E+10 | 3962.65 | 25-APR-04:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.699753E+09 | 3234.34 | 01-MAY-06:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66125898.65 | 829.73 | 13-JUN-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 9127673.10 | 545.54 | 01-JUL-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.364411E+09 | 3273.62 | 24-SEP-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.831643E+09 | 3599.02 | 02-OCT-04:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.350779E+10 | 4549.48 | 27-NOV-07:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.565070E+10 | 4127.83 | 25-DEC-07:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.296532E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.691628E+10 | 5244.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379986E+11 | 101241.97 | 17-JAN-16:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.392419E+11 | 108450.50 | 06-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122784E+11 | 109738.39 | 06-MAR-23:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159494E+11 | 101085.35 | 02-APR-17:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.601852E+10 | 88233.97 | 01-MAY-06:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.111327E+09 | 30537.01 | 04-JUN-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17781094.48 | 7167.53 | 11-JUL-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156871E+09 | 33574.44 | 30-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131079E+10 | 58105.37 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117407E+11 | 121016.05 | 08-OCT-20:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163904E+11 | 110873.65 | 07-NOV-08:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112216E+11 | 100599.56 | 25-DEC-18:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152436E+12 | |||||||
Minimum of Months | 17781094.48 | 7167.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.392419E+11 | 121016.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457239E+10 | 10729.05 | 02-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.452831E+10 | 11775.20 | 06-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458246E+09 | 4326.16 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16001.95 | 0.41 | 23-APR-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 51770.71 | 0.41 | 24-MAY-21:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26037.46 | 0.41 | 09-JUN-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 12636.51 | 0.42 | 09-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19967.56 | 32.04 | 08-AUG-17:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34368.24 | 0.41 | 03-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76067.93 | 73.16 | 12-OCT-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311821E+09 | 3834.26 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.746831E+09 | 7375.30 | 31-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106178E+11 | |||||||
Minimum of Months | 12636.51 | 0.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457239E+10 | 11775.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 27780306.12 | 26975974.99 | 14568.56 | 17-JAN-16:01 | 14568.56 | 0.00 |
February | 0.00 | 0.00 | 76859816.80 | 76716955.60 | 14507.89 | 02-FEB-16:01 | 14507.89 | 0.00 |
March | 0.00 | 0.00 | 0.571324E+09 | 0.507538E+09 | 15238.61 | 27-MAR-15:02 | 12639.73 | 0.04 |
April | 0.00 | 0.00 | 0.129206E+10 | 0.817434E+09 | 16446.91 | 27-APR-17:41 | 14903.47 | 0.24 |
May | 0.00 | 0.00 | 0.251251E+10 | 0.140912E+10 | 19020.67 | 31-MAY-21:11 | 14310.76 | 0.47 |
June | 0.00 | 0.00 | 0.505381E+10 | 0.263038E+10 | 20985.38 | 24-JUN-21:11 | 11166.38 | 0.59 |
July | 0.00 | 0.00 | 0.741070E+10 | 0.396816E+10 | 22853.10 | 19-JUL-21:11 | 11269.30 | 0.67 |
August | 0.00 | 0.00 | 0.787397E+10 | 0.456547E+10 | 23858.93 | 03-AUG-21:11 | 11109.45 | 0.69 |
September | 0.00 | 0.00 | 0.382114E+10 | 0.192696E+10 | 21003.09 | 13-SEP-21:11 | 11660.84 | 0.57 |
October | 0.00 | 0.00 | 0.252970E+10 | 0.136159E+10 | 18630.47 | 05-OCT-21:11 | 12225.92 | 0.40 |
November | 0.00 | 0.00 | 0.235673E+09 | 0.150496E+09 | 14615.91 | 03-NOV-15:02 | 14615.91 | 0.07 |
December | 0.00 | 0.00 | 36824993.70 | 35962186.21 | 14380.36 | 17-DEC-16:01 | 14380.36 | 0.00 |
Annual Sum or Average | 0.314423E+11 | 0.174768E+11 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 27780306.12 | 26975974.99 | 14380.36 | 11109.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.787397E+10 | 0.456547E+10 | 23858.93 | 14903.47 | 0.69 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2593194.02 | 2204372.47 | 5015.55 | 17-JAN-16:01 | 5015.55 | 0.00 |
February | 0.00 | 0.00 | 9713260.03 | 9709424.64 | 10303.11 | 20-FEB-16:01 | 10303.11 | 0.00 |
March | 0.00 | 0.00 | 0.280358E+09 | 0.250194E+09 | 14668.47 | 27-MAR-15:02 | 11943.66 | 0.02 |
April | 0.00 | 0.00 | 0.947073E+09 | 0.585482E+09 | 16113.63 | 27-APR-17:41 | 14523.98 | 0.20 |
May | 0.00 | 0.00 | 0.231822E+10 | 0.128352E+10 | 18671.45 | 31-MAY-21:11 | 14021.98 | 0.45 |
June | 0.00 | 0.00 | 0.489299E+10 | 0.254037E+10 | 20644.66 | 24-JUN-21:11 | 10946.31 | 0.58 |
July | 0.00 | 0.00 | 0.716008E+10 | 0.381167E+10 | 22461.31 | 19-JUL-21:11 | 11036.54 | 0.66 |
August | 0.00 | 0.00 | 0.714448E+10 | 0.404379E+10 | 22699.68 | 03-AUG-21:11 | 11322.73 | 0.68 |
September | 0.00 | 0.00 | 0.294028E+10 | 0.139258E+10 | 20576.00 | 13-SEP-21:11 | 11360.34 | 0.50 |
October | 0.00 | 0.00 | 0.120086E+10 | 0.571096E+09 | 18015.21 | 05-OCT-21:11 | 11606.84 | 0.28 |
November | 0.00 | 0.00 | 49727465.18 | 31778433.16 | 13912.06 | 03-NOV-15:02 | 13912.06 | 0.02 |
December | 0.00 | 0.00 | 2944014.92 | 2522530.34 | 2116.91 | 25-DEC-16:03 | 970.62 | 0.00 |
Annual Sum or Average | 0.269493E+11 | 0.145249E+11 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 2593194.02 | 2204372.47 | 2116.91 | 970.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.716008E+10 | 0.404379E+10 | 22699.68 | 14523.98 | 0.68 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104942E+09 | 0.104942E+09 | 7351.47 | 19-JAN-14:10 | 7351.47 | 0.00 |
February | 0.00 | 0.00 | 0.725578E+09 | 0.725578E+09 | 18648.17 | 03-FEB-12:30 | 18648.17 | 0.00 |
March | 0.00 | 0.00 | 0.160738E+10 | 0.160738E+10 | 25144.40 | 03-MAR-13:30 | 25144.40 | 0.00 |
April | 0.00 | 0.00 | 0.352546E+10 | 0.228464E+10 | 30395.50 | 08-APR-12:20 | 22957.28 | 0.09 |
May | 0.00 | 0.00 | 0.595662E+10 | 0.331097E+10 | 24787.02 | 30-MAY-16:40 | 15696.45 | 0.21 |
June | 0.00 | 0.00 | 0.177568E+11 | 0.655774E+10 | 43904.42 | 25-JUN-18:30 | 20923.63 | 0.61 |
July | 0.00 | 0.00 | 0.382742E+11 | 0.153539E+11 | 59515.45 | 22-JUL-17:02 | 30237.30 | 0.88 |
August | 0.00 | 0.00 | 0.416441E+11 | 0.207331E+11 | 60103.82 | 03-AUG-20:20 | 28943.65 | 0.91 |
September | 0.00 | 0.00 | 0.260375E+11 | 0.145031E+11 | 51183.24 | 07-SEP-16:20 | 28979.92 | 0.64 |
October | 0.00 | 0.00 | 0.272829E+11 | 0.199350E+11 | 45975.50 | 04-OCT-12:00 | 34978.75 | 0.39 |
November | 0.00 | 0.00 | 0.576764E+10 | 0.507193E+10 | 39864.65 | 02-NOV-12:30 | 39864.65 | 0.06 |
December | 0.00 | 0.00 | 0.259430E+10 | 0.259430E+10 | 32047.56 | 17-DEC-12:30 | 32047.56 | 0.00 |
Annual Sum or Average | 0.171277E+12 | 0.927826E+11 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 0.104942E+09 | 0.104942E+09 | 7351.47 | 7351.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.416441E+11 | 0.207331E+11 | 60103.82 | 39864.65 | 0.91 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.588108E+09 | 0.293214E+09 | 53663.37 | 22-JAN-09:02 | 47019.90 | 0.04 |
February | 0.00 | 0.00 | 0.321566E+09 | 0.290462E+09 | 54382.50 | 20-FEB-09:02 | 54382.50 | 0.01 |
March | 0.00 | 0.00 | 0.361984E+10 | 0.237584E+10 | 78448.67 | 28-MAR-18:01 | 78448.67 | 0.14 |
April | 0.00 | 0.00 | 0.132431E+11 | 0.764857E+10 | 86923.02 | 30-APR-18:03 | 71538.96 | 0.38 |
May | 0.00 | 0.00 | 0.284110E+11 | 0.174013E+11 | 105013.73 | 31-MAY-21:11 | 78032.31 | 0.51 |
June | 0.00 | 0.00 | 0.426123E+11 | 0.270702E+11 | 124645.52 | 24-JUN-21:11 | 65267.02 | 0.45 |
July | 0.00 | 0.00 | 0.590264E+11 | 0.380133E+11 | 135342.13 | 19-JUL-21:11 | 63203.94 | 0.52 |
August | 0.00 | 0.00 | 0.537936E+11 | 0.352900E+11 | 135778.92 | 03-AUG-21:11 | 64118.26 | 0.52 |
September | 0.00 | 0.00 | 0.320783E+11 | 0.190541E+11 | 123678.57 | 07-SEP-21:11 | 68712.54 | 0.46 |
October | 0.00 | 0.00 | 0.172207E+11 | 0.935282E+10 | 105248.75 | 05-OCT-21:11 | 66523.57 | 0.35 |
November | 0.00 | 0.00 | 0.477364E+10 | 0.259931E+10 | 79317.62 | 11-NOV-09:02 | 76521.04 | 0.21 |
December | 0.00 | 0.00 | 0.581960E+09 | 0.441090E+09 | 61594.22 | 25-DEC-09:02 | 54481.62 | 0.02 |
Annual Sum or Average | 0.256270E+12 | 0.159830E+12 | 0.30 | |||||
Minimum of Months | 0.00 | 0.00 | 0.321566E+09 | 0.290462E+09 | 53663.37 | 47019.90 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.590264E+11 | 0.380133E+11 | 135778.92 | 78448.67 | 0.52 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 54466418.15 | 50182604.73 | 9401.98 | 19-JAN-09:02 | 9401.98 | 0.00 |
February | 0.00 | 0.00 | 89859644.05 | 89635074.04 | 12851.80 | 25-FEB-09:02 | 12851.80 | 0.00 |
March | 0.00 | 0.00 | 0.468748E+09 | 0.412677E+09 | 13263.85 | 11-MAR-09:02 | 13263.85 | 0.04 |
April | 0.00 | 0.00 | 0.138903E+10 | 0.880443E+09 | 14748.61 | 08-APR-08:11 | 13888.60 | 0.27 |
May | 0.00 | 0.00 | 0.281111E+10 | 0.171205E+10 | 17736.02 | 31-MAY-08:11 | 14761.18 | 0.49 |
June | 0.00 | 0.00 | 0.479931E+10 | 0.254441E+10 | 19941.53 | 25-JUN-08:11 | 12224.51 | 0.60 |
July | 0.00 | 0.00 | 0.736256E+10 | 0.395745E+10 | 20532.26 | 19-JUL-21:11 | 9917.70 | 0.68 |
August | 0.00 | 0.00 | 0.783865E+10 | 0.457343E+10 | 21564.67 | 03-AUG-21:11 | 9891.58 | 0.70 |
September | 0.00 | 0.00 | 0.403689E+10 | 0.219843E+10 | 19199.59 | 07-SEP-21:11 | 10956.47 | 0.60 |
October | 0.00 | 0.00 | 0.250730E+10 | 0.145664E+10 | 16926.29 | 25-OCT-08:11 | 11659.83 | 0.40 |
November | 0.00 | 0.00 | 0.372377E+09 | 0.248842E+09 | 13171.70 | 02-NOV-15:01 | 13171.70 | 0.09 |
December | 0.00 | 0.00 | 0.104392E+09 | 97860616.29 | 12871.95 | 17-DEC-09:02 | 12871.95 | 0.00 |
Annual Sum or Average | 0.318347E+11 | 0.182221E+11 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 54466418.15 | 50182604.73 | 9401.98 | 9401.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.783865E+10 | 0.457343E+10 | 21564.67 | 14761.18 | 0.70 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 4219185.98 | 2541162.96 | 2583.94 | 30-JAN-09:03 | 2583.94 | 0.00 |
February | 0.00 | 0.00 | 17102630.46 | 17029984.80 | 11510.51 | 25-FEB-09:02 | 11510.51 | 0.00 |
March | 0.00 | 0.00 | 0.214816E+09 | 0.182877E+09 | 12975.28 | 29-MAR-08:62 | 12975.28 | 0.02 |
April | 0.00 | 0.00 | 0.105073E+10 | 0.657994E+09 | 14593.12 | 08-APR-08:11 | 13613.19 | 0.22 |
May | 0.00 | 0.00 | 0.261144E+10 | 0.158929E+10 | 17605.30 | 31-MAY-08:11 | 14644.83 | 0.46 |
June | 0.00 | 0.00 | 0.463470E+10 | 0.246058E+10 | 19421.72 | 25-JUN-08:11 | 12377.93 | 0.60 |
July | 0.00 | 0.00 | 0.710148E+10 | 0.378450E+10 | 20337.86 | 19-JUL-21:11 | 9782.08 | 0.67 |
August | 0.00 | 0.00 | 0.709951E+10 | 0.403790E+10 | 20675.85 | 03-AUG-21:11 | 10144.62 | 0.70 |
September | 0.00 | 0.00 | 0.314014E+10 | 0.166064E+10 | 18854.51 | 07-SEP-21:11 | 10614.75 | 0.51 |
October | 0.00 | 0.00 | 0.125076E+10 | 0.663391E+09 | 16490.40 | 25-OCT-08:11 | 11139.32 | 0.25 |
November | 0.00 | 0.00 | 0.110279E+09 | 58143156.93 | 11616.68 | 04-NOV-08:62 | 11394.78 | 0.04 |
December | 0.00 | 0.00 | 7466233.97 | 6339347.55 | 5716.22 | 17-DEC-09:02 | 5716.22 | 0.00 |
Annual Sum or Average | 0.272426E+11 | 0.151212E+11 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 4219185.98 | 2541162.96 | 2583.94 | 2583.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.710148E+10 | 0.403790E+10 | 20675.85 | 14644.83 | 0.70 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7425390.75 | 7278455.89 | 3833.70 | 17-JAN-16:01 | 3833.70 | 0.00 |
February | 0.00 | 0.00 | 21333287.77 | 21333287.77 | 3834.20 | 20-FEB-16:01 | 3834.20 | 0.00 |
March | 0.00 | 0.00 | 0.157999E+09 | 0.141656E+09 | 4052.76 | 27-MAR-15:02 | 3394.47 | 0.04 |
April | 0.00 | 0.00 | 0.393115E+09 | 0.259895E+09 | 4562.20 | 09-APR-17:31 | 4437.86 | 0.24 |
May | 0.00 | 0.00 | 0.817100E+09 | 0.490926E+09 | 5288.33 | 31-MAY-21:11 | 4035.85 | 0.48 |
June | 0.00 | 0.00 | 0.167466E+10 | 0.961326E+09 | 5729.16 | 24-JUN-21:11 | 3015.63 | 0.62 |
July | 0.00 | 0.00 | 0.237031E+10 | 0.139650E+10 | 6109.04 | 22-JUL-08:11 | 2887.08 | 0.68 |
August | 0.00 | 0.00 | 0.246586E+10 | 0.156146E+10 | 5896.92 | 05-AUG-21:11 | 3190.84 | 0.70 |
September | 0.00 | 0.00 | 0.123495E+10 | 0.691442E+09 | 5814.37 | 13-SEP-21:11 | 3147.14 | 0.59 |
October | 0.00 | 0.00 | 0.742035E+09 | 0.418696E+09 | 5079.85 | 05-OCT-21:11 | 3324.64 | 0.40 |
November | 0.00 | 0.00 | 55247639.35 | 38198397.20 | 3837.20 | 03-NOV-15:02 | 3837.20 | 0.06 |
December | 0.00 | 0.00 | 7217890.30 | 7021997.71 | 3820.39 | 17-DEC-16:01 | 3820.39 | 0.00 |
Annual Sum or Average | 0.994726E+10 | 0.599574E+10 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 7217890.30 | 7021997.71 | 3820.39 | 2887.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.246586E+10 | 0.156146E+10 | 6109.04 | 4437.86 | 0.70 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 517710.64 | 463648.50 | 671.09 | 20-JAN-16:03 | 671.09 | 0.00 |
February | 0.00 | 0.00 | 1198557.75 | 1198557.75 | 2011.25 | 20-FEB-16:01 | 2011.25 | 0.00 |
March | 0.00 | 0.00 | 71934629.16 | 63747057.50 | 3878.73 | 27-MAR-15:02 | 3176.59 | 0.02 |
April | 0.00 | 0.00 | 0.286991E+09 | 0.185344E+09 | 4335.67 | 27-APR-17:41 | 4003.20 | 0.20 |
May | 0.00 | 0.00 | 0.758573E+09 | 0.451074E+09 | 5191.62 | 31-MAY-21:11 | 3955.79 | 0.47 |
June | 0.00 | 0.00 | 0.163241E+10 | 0.934291E+09 | 5633.73 | 24-JUN-21:11 | 2954.38 | 0.62 |
July | 0.00 | 0.00 | 0.230772E+10 | 0.135002E+10 | 6012.24 | 22-JUL-08:11 | 2839.38 | 0.68 |
August | 0.00 | 0.00 | 0.227262E+10 | 0.139676E+10 | 5779.71 | 05-AUG-21:11 | 3130.10 | 0.70 |
September | 0.00 | 0.00 | 0.974900E+09 | 0.508983E+09 | 5700.18 | 13-SEP-21:11 | 3055.95 | 0.53 |
October | 0.00 | 0.00 | 0.359430E+09 | 0.174516E+09 | 4903.03 | 05-OCT-21:11 | 3118.50 | 0.28 |
November | 0.00 | 0.00 | 11228918.98 | 7436723.88 | 3674.98 | 03-NOV-15:02 | 3674.98 | 0.01 |
December | 0.00 | 0.00 | 386009.54 | 316604.62 | 475.84 | 15-DEC-16:04 | 475.84 | 0.00 |
Annual Sum or Average | 0.867790E+10 | 0.507415E+10 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 386009.54 | 316604.62 | 475.84 | 475.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.230772E+10 | 0.139676E+10 | 6012.24 | 4003.20 | 0.70 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.861060E+09 | 0.855737E+09 | 15653.85 | 17-JAN-16:01 | 15653.85 | 0.00 |
February | 0.00 | 0.00 | 0.115015E+10 | 0.114996E+10 | 15655.25 | 20-FEB-16:01 | 15655.25 | 0.00 |
March | 0.00 | 0.00 | 0.192684E+10 | 0.171358E+10 | 16668.49 | 27-MAR-15:02 | 14207.29 | 0.11 |
April | 0.00 | 0.00 | 0.245126E+10 | 0.159270E+10 | 16498.77 | 27-APR-18:02 | 14023.18 | 0.32 |
May | 0.00 | 0.00 | 0.387267E+10 | 0.219225E+10 | 19830.65 | 31-MAY-21:11 | 14715.34 | 0.54 |
June | 0.00 | 0.00 | 0.741613E+10 | 0.423782E+10 | 23495.54 | 25-JUN-18:41 | 13429.60 | 0.60 |
July | 0.00 | 0.00 | 0.114711E+11 | 0.692979E+10 | 25726.08 | 19-JUL-21:11 | 11853.66 | 0.67 |
August | 0.00 | 0.00 | 0.123749E+11 | 0.823259E+10 | 24655.72 | 03-AUG-21:11 | 13011.44 | 0.70 |
September | 0.00 | 0.00 | 0.826343E+10 | 0.535642E+10 | 23723.65 | 13-SEP-21:11 | 12879.27 | 0.62 |
October | 0.00 | 0.00 | 0.793432E+10 | 0.574069E+10 | 20414.18 | 05-OCT-21:11 | 13610.29 | 0.49 |
November | 0.00 | 0.00 | 0.220793E+10 | 0.178036E+10 | 15873.37 | 02-NOV-16:21 | 15873.37 | 0.18 |
December | 0.00 | 0.00 | 0.161845E+10 | 0.161026E+10 | 15650.60 | 03-DEC-16:01 | 15650.60 | 0.01 |
Annual Sum or Average | 0.615482E+11 | 0.413921E+11 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 0.861060E+09 | 0.855737E+09 | 15650.60 | 11853.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.123749E+11 | 0.823259E+10 | 25726.08 | 15873.37 | 0.70 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.201056E+09 | 0.201056E+09 | 9134.79 | 03-JAN-19:50 | 9134.79 | 0.03 |
February | 0.00 | 0.00 | 0.201457E+09 | 0.201457E+09 | 8457.16 | 20-FEB-15:10 | 8457.16 | 0.01 |
March | 0.00 | 0.00 | 0.615827E+10 | 0.543803E+10 | 198079.43 | 27-MAR-13:00 | 131600.32 | 0.11 |
April | 0.00 | 0.00 | 0.469006E+11 | 0.456488E+11 | 242699.92 | 09-APR-11:00 | 152246.97 | 0.27 |
May | 0.00 | 0.00 | 0.176108E+12 | 0.142368E+12 | 310082.71 | 31-MAY-17:20 | 166597.34 | 0.54 |
June | 0.00 | 0.00 | 0.616653E+12 | 0.355162E+12 | 483967.24 | 24-JUN-18:10 | 176850.06 | 0.92 |
July | 0.00 | 0.00 | 0.880013E+12 | 0.471883E+12 | 483525.10 | 05-JUL-20:20 | 194748.80 | 1.00 |
August | 0.00 | 0.00 | 0.730032E+12 | 0.459545E+12 | 462863.82 | 03-AUG-20:00 | 218515.90 | 0.98 |
September | 0.00 | 0.00 | 0.443509E+12 | 0.292075E+12 | 466634.99 | 22-SEP-17:50 | 164193.20 | 0.86 |
October | 0.00 | 0.00 | 0.179768E+12 | 0.107593E+12 | 310626.32 | 25-OCT-09:30 | 159354.72 | 0.49 |
November | 0.00 | 0.00 | 0.702257E+10 | 0.607917E+10 | 122410.17 | 10-NOV-08:00 | 45181.51 | 0.07 |
December | 0.00 | 0.00 | 0.357819E+09 | 0.357819E+09 | 20247.55 | 17-DEC-20:08 | 20247.55 | 0.02 |
Annual Sum or Average | 0.308692E+13 | 0.188655E+13 | 0.44 | |||||
Minimum of Months | 0.00 | 0.00 | 0.201056E+09 | 0.201056E+09 | 8457.16 | 8457.16 | 0.01 | |
Maximum of Months | 0.00 | 0.00 | 0.880013E+12 | 0.471883E+12 | 483967.24 | 218515.90 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.689690E+09 | 0.589293E+09 | 32556.26 | 27-MAR-13:00 | 21428.09 | 0.02 |
April | 0.00 | 0.00 | 0.635838E+10 | 0.619782E+10 | 40026.89 | 09-APR-11:00 | 24732.29 | 0.16 |
May | 0.00 | 0.00 | 0.234222E+11 | 0.197232E+11 | 53223.86 | 31-MAY-16:30 | 29613.41 | 0.44 |
June | 0.00 | 0.00 | 0.997309E+11 | 0.561107E+11 | 84544.35 | 24-JUN-17:00 | 29126.02 | 0.92 |
July | 0.00 | 0.00 | 0.141708E+12 | 0.763736E+11 | 85046.07 | 26-JUL-16:50 | 29591.34 | 1.00 |
August | 0.00 | 0.00 | 0.113160E+12 | 0.724159E+11 | 84761.84 | 03-AUG-20:00 | 32735.12 | 0.99 |
September | 0.00 | 0.00 | 0.687130E+11 | 0.452750E+11 | 78954.67 | 13-SEP-21:00 | 30595.02 | 0.83 |
October | 0.00 | 0.00 | 0.244480E+11 | 0.148072E+11 | 52097.26 | 24-OCT-14:00 | 26079.44 | 0.42 |
November | 0.00 | 0.00 | 0.604784E+09 | 0.540997E+09 | 12356.39 | 10-NOV-08:00 | 4465.67 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.478835E+12 | 0.292034E+12 | 0.40 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.141708E+12 | 0.763736E+11 | 85046.07 | 32735.12 | 1.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 27933.69 | 59477.65 | 18-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 28177.97 | 57940.30 | 14-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 27563.68 | 64704.55 | 06-MAR-07:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25989.92 | 60998.98 | 23-APR-07:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 23927.92 | 58235.14 | 02-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21852.23 | 48213.98 | 01-JUN-06:30 |
July | 0.51 | 726.37 | 29-JUL-03:00 | 20340.68 | 45054.77 | 03-JUL-06:30 |
August | 2.85 | 989.32 | 08-AUG-03:00 | 19860.29 | 44896.90 | 30-AUG-17:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20846.74 | 49715.31 | 30-SEP-07:12 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 22547.84 | 56828.21 | 27-OCT-20:41 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 24689.56 | 59619.68 | 26-NOV-22:21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 26612.81 | 60439.93 | 25-DEC-08:50 |
Annual Sum or Average | 0.29 | 24171.87 | ||||
Minimum of Months | 0.00 | 0.00 | 19860.29 | 44896.90 | ||
Maximum of Months | 2.85 | 989.32 | 28177.97 | 64704.55 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47766.99 | 197013.41 | 02-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 47423.70 | 196915.73 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 18950.68 | 139316.40 | 26-MAR-21:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13772.39 | 138739.15 | 22-APR-15:02 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6471.25 | 89505.69 | 19-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3831.00 | 100446.25 | 06-JUN-15:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2848.53 | 22768.59 | 24-JUL-08:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 2179.07 | 30980.57 | 22-AUG-18:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 3647.28 | 97462.43 | 23-SEP-15:04 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 7862.67 | 128522.74 | 08-OCT-21:52 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 20541.35 | 144243.92 | 13-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 28532.39 | 144498.91 | 31-DEC-16:03 |
Annual Sum or Average | 0.00 | 16807.08 | ||||
Minimum of Months | 0.00 | 0.00 | 2179.07 | 22768.59 | ||
Maximum of Months | 0.00 | 0.00 | 47766.99 | 197013.41 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1405.75 | 33694.82 | 17-JAN-19:04 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1862.35 | 50136.42 | 20-FEB-09:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 7111.58 | 293691.98 | 27-MAR-15:02 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 31611.56 | 356748.99 | 07-APR-15:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 95209.60 | 488997.43 | 31-MAY-21:13 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 313428.03 | 763815.44 | 24-JUN-21:13 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 436880.15 | 802198.63 | 20-JUL-20:13 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 370230.62 | 798988.11 | 03-AUG-21:13 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 231578.31 | 699170.24 | 06-SEP-21:13 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 100968.54 | 538742.40 | 05-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 9448.60 | 182205.09 | 10-NOV-09:03 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 2955.19 | 42807.03 | 18-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 134497.93 | 0.00 | ||||
Minimum of Months | 1405.75 | 33694.82 | 0.00 | 0.00 | ||
Maximum of Months | 436880.15 | 802198.63 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.587767E+10 | 0.88 | 2194.47 | 03-JAN-09:03 | 0.87 |
February | 0.530887E+10 | 0.88 | 2194.47 | 03-FEB-09:05 | 0.88 |
March | 0.587767E+10 | 0.88 | 2194.47 | 09-MAR-16:05 | 0.88 |
April | 0.568807E+10 | 0.88 | 2194.47 | 01-APR-08:62 | 0.88 |
May | 0.587767E+10 | 0.87 | 2194.47 | 05-MAY-18:03 | 0.87 |
June | 0.568807E+10 | 0.87 | 2194.47 | 01-JUN-15:20 | 0.87 |
July | 0.587767E+10 | 0.87 | 2194.47 | 02-JUL-15:10 | 0.87 |
August | 0.587767E+10 | 0.87 | 2194.47 | 01-AUG-15:20 | 0.87 |
September | 0.568807E+10 | 0.87 | 2194.47 | 01-SEP-15:30 | 0.87 |
October | 0.587767E+10 | 0.87 | 2194.47 | 04-OCT-15:03 | 0.87 |
November | 0.568807E+10 | 0.88 | 2194.47 | 02-NOV-16:21 | 0.88 |
December | 0.587767E+10 | 0.88 | 2194.47 | 06-DEC-19:03 | 0.88 |
Annual Sum or Average | 0.692049E+11 | 0.87 | |||
Minimum of Months | 0.530887E+10 | 0.87 | 2194.47 | 0.87 | |
Maximum of Months | 0.587767E+10 | 0.88 | 2194.47 | 0.88 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.375402E+11 | 0.89 | 24106.87 | 03-JAN-19:07 | 1.22 |
February | 0.337626E+11 | 0.89 | 20195.96 | 23-FEB-21:10 | 1.10 |
March | 0.386472E+11 | 0.90 | 35100.34 | 15-MAR-21:27 | 1.55 |
April | 0.375765E+11 | 0.90 | 33251.03 | 11-APR-21:40 | 1.50 |
May | 0.373640E+11 | 0.88 | 33556.12 | 01-MAY-21:55 | 1.51 |
June | 0.343925E+11 | 0.85 | 20212.17 | 22-JUN-19:20 | 1.09 |
July | 0.353977E+11 | 0.85 | 18648.84 | 11-JUL-18:05 | 1.04 |
August | 0.356443E+11 | 0.85 | 22948.06 | 24-AUG-18:50 | 1.18 |
September | 0.345345E+11 | 0.86 | 23430.19 | 30-SEP-00:03 | 1.20 |
October | 0.380710E+11 | 0.89 | 41311.69 | 27-OCT-21:43 | 1.72 |
November | 0.379046E+11 | 0.91 | 40745.04 | 01-NOV-23:10 | 1.70 |
December | 0.379263E+11 | 0.89 | 28391.25 | 04-DEC-20:00 | 1.35 |
Annual Sum or Average | 0.438761E+12 | 0.88 | |||
Minimum of Months | 0.337626E+11 | 0.85 | 18648.84 | 1.04 | |
Maximum of Months | 0.386472E+11 | 0.91 | 41311.69 | 1.72 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:03 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.26 | 76.61 | 01-MAY-00:03 | 0.26 |
June | 0.198586E+09 | 0.26 | 76.61 | 01-JUN-00:10 | 0.26 |
July | 0.205205E+09 | 0.26 | 76.61 | 01-JUL-00:10 | 0.26 |
August | 0.205205E+09 | 0.26 | 76.61 | 01-AUG-00:10 | 0.26 |
September | 0.198586E+09 | 0.26 | 76.61 | 01-SEP-00:10 | 0.26 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:03 | 0.26 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:02 | 0.26 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.26 | 76.61 | 0.26 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:05 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:05 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:03 | 0.26 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.26 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.26 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:03 | 0.26 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:10 | 0.26 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.26 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.376216E+09 | 0.45 | 783.54 | 01-JAN-09:02 | 0.58 |
February | 0.324365E+09 | 0.44 | 783.54 | 01-FEB-09:02 | 0.58 |
March | 0.225533E+09 | 0.42 | 783.54 | 01-MAR-16:01 | 0.58 |
April | 0.173385E+09 | 0.41 | 783.54 | 01-APR-08:62 | 0.58 |
May | 0.157678E+09 | 0.37 | 783.54 | 01-MAY-15:01 | 0.58 |
June | 0.233375E+09 | 0.34 | 783.54 | 01-JUN-08:11 | 0.57 |
July | 0.323659E+09 | 0.38 | 783.54 | 01-JUL-08:11 | 0.57 |
August | 0.359013E+09 | 0.40 | 783.54 | 01-AUG-08:11 | 0.57 |
September | 0.185732E+09 | 0.35 | 783.54 | 01-SEP-08:11 | 0.57 |
October | 0.162970E+09 | 0.40 | 783.54 | 02-OCT-15:02 | 0.57 |
November | 0.218376E+09 | 0.41 | 783.54 | 01-NOV-15:02 | 0.58 |
December | 0.316498E+09 | 0.44 | 783.54 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.305680E+10 | 0.40 | |||
Minimum of Months | 0.157678E+09 | 0.34 | 783.54 | 0.57 | |
Maximum of Months | 0.376216E+09 | 0.45 | 783.54 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.428970E+09 | 0.49 | 771.52 | 01-JAN-09:02 | 0.58 |
February | 0.388363E+09 | 0.48 | 771.52 | 01-FEB-09:02 | 0.58 |
March | 0.241439E+09 | 0.41 | 771.52 | 01-MAR-09:02 | 0.58 |
April | 0.164938E+09 | 0.40 | 771.52 | 01-APR-08:62 | 0.58 |
May | 0.148307E+09 | 0.36 | 771.52 | 01-MAY-15:01 | 0.58 |
June | 0.226020E+09 | 0.34 | 771.52 | 01-JUN-08:11 | 0.57 |
July | 0.312714E+09 | 0.38 | 771.52 | 01-JUL-08:11 | 0.57 |
August | 0.327030E+09 | 0.39 | 771.52 | 01-AUG-08:11 | 0.57 |
September | 0.147343E+09 | 0.31 | 771.52 | 01-SEP-08:11 | 0.57 |
October | 0.118772E+09 | 0.35 | 771.52 | 02-OCT-15:02 | 0.57 |
November | 0.250860E+09 | 0.42 | 771.52 | 01-NOV-08:62 | 0.57 |
December | 0.369235E+09 | 0.47 | 771.52 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.312399E+10 | 0.40 | |||
Minimum of Months | 0.118772E+09 | 0.31 | 771.52 | 0.57 | |
Maximum of Months | 0.428970E+09 | 0.49 | 771.52 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.477556E+09 | 0.18 | 1125.49 | 02-JAN-05:00 | 0.58 |
February | 0.159279E+09 | 0.08 | 934.32 | 07-FEB-06:00 | 0.58 |
March | 0.105368E+09 | 0.05 | 1086.03 | 03-MAR-13:30 | 0.58 |
April | 0.183544E+09 | 0.08 | 1174.18 | 08-APR-12:30 | 0.57 |
May | 0.348188E+09 | 0.20 | 983.43 | 30-MAY-16:40 | 0.57 |
June | 0.770056E+09 | 0.37 | 1213.28 | 25-JUN-21:00 | 0.57 |
July | 0.143198E+10 | 0.50 | 1968.93 | 20-JUL-20:00 | 0.57 |
August | 0.164134E+10 | 0.52 | 1383.02 | 03-AUG-20:20 | 0.57 |
September | 0.112673E+10 | 0.40 | 2388.00 | 30-SEP-12:40 | 0.58 |
October | 0.125329E+10 | 0.35 | 2241.55 | 04-OCT-12:00 | 0.57 |
November | 0.298115E+09 | 0.11 | 2213.93 | 04-NOV-12:30 | 0.57 |
December | 0.278530E+09 | 0.11 | 1313.96 | 17-DEC-12:30 | 0.58 |
Annual Sum or Average | 0.807397E+10 | 0.25 | |||
Minimum of Months | 0.105368E+09 | 0.05 | 934.32 | 0.57 | |
Maximum of Months | 0.164134E+10 | 0.52 | 2388.00 | 0.58 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163622E+10 | 0.42 | 4507.26 | 01-JAN-09:02 | 0.58 |
February | 0.155243E+10 | 0.42 | 4507.26 | 01-FEB-09:02 | 0.58 |
March | 0.896642E+09 | 0.40 | 4507.26 | 01-MAR-16:01 | 0.58 |
April | 0.890618E+09 | 0.39 | 4507.26 | 01-APR-15:02 | 0.58 |
May | 0.139347E+10 | 0.33 | 4507.26 | 01-MAY-08:62 | 0.58 |
June | 0.191473E+10 | 0.27 | 4507.26 | 01-JUN-08:11 | 0.57 |
July | 0.266366E+10 | 0.30 | 4507.26 | 01-JUL-08:11 | 0.57 |
August | 0.245950E+10 | 0.30 | 4507.26 | 01-AUG-08:11 | 0.57 |
September | 0.145484E+10 | 0.27 | 4507.26 | 01-SEP-08:11 | 0.57 |
October | 0.912586E+09 | 0.34 | 4507.26 | 01-OCT-08:62 | 0.57 |
November | 0.894106E+09 | 0.40 | 4507.26 | 02-NOV-18:02 | 0.58 |
December | 0.128747E+10 | 0.41 | 4507.26 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.179563E+11 | 0.35 | |||
Minimum of Months | 0.890618E+09 | 0.27 | 4507.26 | 0.57 | |
Maximum of Months | 0.266366E+10 | 0.42 | 4507.26 | 0.58 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.352739E+09 | 0.45 | 710.12 | 01-JAN-09:02 | 0.58 |
February | 0.297707E+09 | 0.44 | 710.12 | 01-FEB-16:02 | 0.58 |
March | 0.212419E+09 | 0.41 | 710.12 | 01-MAR-09:02 | 0.58 |
April | 0.169839E+09 | 0.42 | 710.12 | 01-APR-08:62 | 0.58 |
May | 0.173153E+09 | 0.39 | 710.12 | 01-MAY-08:62 | 0.57 |
June | 0.227359E+09 | 0.35 | 710.12 | 01-JUN-08:11 | 0.57 |
July | 0.325444E+09 | 0.39 | 710.12 | 01-JUL-08:11 | 0.57 |
August | 0.363138E+09 | 0.40 | 710.12 | 01-AUG-08:11 | 0.57 |
September | 0.201052E+09 | 0.36 | 710.12 | 01-SEP-08:11 | 0.57 |
October | 0.163410E+09 | 0.40 | 710.12 | 02-OCT-08:62 | 0.57 |
November | 0.202702E+09 | 0.41 | 710.12 | 01-NOV-15:02 | 0.58 |
December | 0.295573E+09 | 0.44 | 710.12 | 01-DEC-16:02 | 0.58 |
Annual Sum or Average | 0.298453E+10 | 0.40 | |||
Minimum of Months | 0.163410E+09 | 0.35 | 710.12 | 0.57 | |
Maximum of Months | 0.363138E+09 | 0.45 | 710.12 | 0.58 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.409075E+09 | 0.49 | 704.59 | 01-JAN-09:02 | 0.58 |
February | 0.363827E+09 | 0.48 | 704.59 | 01-FEB-09:02 | 0.58 |
March | 0.231279E+09 | 0.41 | 704.59 | 01-MAR-09:02 | 0.58 |
April | 0.161427E+09 | 0.40 | 704.59 | 01-APR-08:62 | 0.58 |
May | 0.162946E+09 | 0.37 | 704.59 | 01-MAY-08:62 | 0.57 |
June | 0.219489E+09 | 0.35 | 704.59 | 01-JUN-08:11 | 0.57 |
July | 0.314428E+09 | 0.39 | 704.59 | 01-JUL-08:11 | 0.57 |
August | 0.330817E+09 | 0.40 | 704.59 | 01-AUG-08:11 | 0.57 |
September | 0.158795E+09 | 0.32 | 704.59 | 01-SEP-08:11 | 0.57 |
October | 0.117930E+09 | 0.34 | 704.59 | 02-OCT-08:62 | 0.57 |
November | 0.226807E+09 | 0.42 | 704.59 | 05-NOV-08:62 | 0.57 |
December | 0.343195E+09 | 0.47 | 704.59 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.304001E+10 | 0.40 | |||
Minimum of Months | 0.117930E+09 | 0.32 | 704.59 | 0.57 | |
Maximum of Months | 0.409075E+09 | 0.49 | 704.59 | 0.58 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115400E+09 | 0.48 | 205.92 | 01-JAN-09:02 | 0.58 |
February | 99700988.70 | 0.46 | 205.92 | 01-FEB-09:02 | 0.58 |
March | 67507562.48 | 0.43 | 205.92 | 01-MAR-09:02 | 0.58 |
April | 52579838.03 | 0.42 | 205.92 | 01-APR-08:62 | 0.58 |
May | 50336637.78 | 0.38 | 205.92 | 01-MAY-15:01 | 0.58 |
June | 77597309.15 | 0.36 | 205.92 | 01-JUN-08:11 | 0.57 |
July | 0.105501E+09 | 0.39 | 205.92 | 01-JUL-08:11 | 0.57 |
August | 0.114116E+09 | 0.40 | 205.92 | 01-AUG-08:11 | 0.57 |
September | 59025553.88 | 0.36 | 205.92 | 01-SEP-08:11 | 0.57 |
October | 47910891.00 | 0.41 | 205.92 | 02-OCT-15:02 | 0.57 |
November | 65813405.96 | 0.43 | 205.92 | 01-NOV-08:62 | 0.57 |
December | 95434710.19 | 0.46 | 205.92 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.950923E+09 | 0.41 | |||
Minimum of Months | 47910891.00 | 0.36 | 205.92 | 0.57 | |
Maximum of Months | 0.115400E+09 | 0.48 | 205.92 | 0.58 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134296E+09 | 0.52 | 202.60 | 01-JAN-09:02 | 0.58 |
February | 0.120129E+09 | 0.51 | 202.60 | 01-FEB-09:02 | 0.58 |
March | 71675403.29 | 0.43 | 202.60 | 01-MAR-09:02 | 0.58 |
April | 49577742.07 | 0.41 | 202.60 | 01-APR-08:62 | 0.58 |
May | 47414462.94 | 0.37 | 202.60 | 01-MAY-15:01 | 0.58 |
June | 75756890.03 | 0.36 | 202.60 | 01-JUN-08:11 | 0.57 |
July | 0.102701E+09 | 0.39 | 202.60 | 01-JUL-08:11 | 0.57 |
August | 0.105567E+09 | 0.40 | 202.60 | 01-AUG-08:11 | 0.57 |
September | 47936041.30 | 0.33 | 202.60 | 01-SEP-08:11 | 0.57 |
October | 35758092.14 | 0.36 | 202.60 | 02-OCT-15:02 | 0.57 |
November | 76022904.49 | 0.45 | 202.60 | 01-NOV-08:62 | 0.57 |
December | 0.110982E+09 | 0.50 | 202.60 | 01-DEC-09:02 | 0.58 |
Annual Sum or Average | 0.977816E+09 | 0.42 | |||
Minimum of Months | 35758092.14 | 0.33 | 202.60 | 0.57 | |
Maximum of Months | 0.134296E+09 | 0.52 | 202.60 | 0.58 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.367375E+09 | 0.46 | 831.22 | 01-JAN-16:02 | 0.58 |
February | 0.306748E+09 | 0.47 | 831.22 | 02-FEB-16:01 | 0.58 |
March | 0.263949E+09 | 0.45 | 831.22 | 01-MAR-16:01 | 0.58 |
April | 0.214197E+09 | 0.43 | 831.22 | 01-APR-15:02 | 0.58 |
May | 0.213352E+09 | 0.38 | 831.22 | 01-MAY-15:01 | 0.58 |
June | 0.333715E+09 | 0.35 | 831.22 | 01-JUN-08:11 | 0.57 |
July | 0.507069E+09 | 0.38 | 831.22 | 01-JUL-08:11 | 0.57 |
August | 0.563129E+09 | 0.40 | 831.22 | 01-AUG-08:11 | 0.57 |
September | 0.385088E+09 | 0.37 | 831.22 | 01-SEP-08:11 | 0.57 |
October | 0.395260E+09 | 0.44 | 831.22 | 01-OCT-08:62 | 0.57 |
November | 0.252176E+09 | 0.44 | 831.22 | 01-NOV-15:02 | 0.58 |
December | 0.334116E+09 | 0.46 | 831.22 | 01-DEC-19:02 | 0.58 |
Annual Sum or Average | 0.413617E+10 | 0.42 | |||
Minimum of Months | 0.213352E+09 | 0.35 | 831.22 | 0.57 | |
Maximum of Months | 0.563129E+09 | 0.47 | 831.22 | 0.58 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.225200E+10 | 0.202680E+10 | 1883.61 | 02-JAN-07:05 | 1695.25 | 1695.25 | 50.52 | 4.41 |
February | 0.196014E+10 | 0.176412E+10 | 1919.62 | 06-FEB-07:05 | 1727.66 | 1727.66 | 50.44 | 4.69 |
March | 0.109202E+10 | 0.982817E+09 | 1492.19 | 06-MAR-23:56 | 1342.97 | 1342.97 | 49.00 | 2.66 |
April | 0.659610E+09 | 0.593649E+09 | 1526.06 | 20-APR-15:02 | 1373.46 | 1373.46 | 50.74 | 2.77 |
May | 0.236585E+09 | 0.212927E+09 | 1253.62 | 01-MAY-06:26 | 1128.25 | 1128.25 | 53.62 | 2.02 |
June | 0.128703E+09 | 0.115833E+09 | 842.82 | 06-JUN-15:05 | 758.54 | 758.54 | 40.05 | 1.20 |
July | 0.103840E+09 | 93456412.45 | 264.59 | 24-JUL-08:15 | 238.13 | 238.13 | 43.57 | 0.33 |
August | 81340617.00 | 73206555.30 | 405.86 | 22-AUG-18:07 | 365.28 | 365.28 | 45.82 | 0.52 |
September | 0.118285E+09 | 0.106456E+09 | 859.53 | 23-SEP-15:04 | 773.58 | 773.58 | 41.10 | 1.23 |
October | 0.344295E+09 | 0.309865E+09 | 1522.80 | 18-OCT-08:04 | 1370.52 | 1370.52 | 49.86 | 2.76 |
November | 0.110151E+10 | 0.991357E+09 | 1497.29 | 26-NOV-23:55 | 1347.56 | 1347.56 | 53.32 | 2.67 |
December | 0.166560E+10 | 0.149904E+10 | 1691.43 | 31-DEC-24:00 | 1522.29 | 1522.29 | 50.21 | 3.37 |
Annual Sum or Average | 0.974392E+10 | 0.876953E+10 | ||||||
Minimum of Months | 81340617.00 | 73206555.30 | 264.59 | 238.13 | 238.13 | 40.05 | 0.33 | |
Maximum of Months | 0.225200E+10 | 0.202680E+10 | 1919.62 | 1727.66 | 1727.66 | 53.62 | 4.69 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 1010436.85 | 909393.17 | 27.51 | 28-JAN-09:02 | 24.76 | 24.76 | 6.71 | 2.64 |
February | 1504691.11 | 1354222.00 | 52.89 | 20-FEB-09:02 | 47.60 | 47.60 | 6.71 | 3.84 |
March | 10361635.83 | 9325472.25 | 281.71 | 27-MAR-15:02 | 253.54 | 253.54 | 6.71 | 9.02 |
April | 68005651.00 | 61205085.90 | 684.36 | 07-APR-15:02 | 615.93 | 615.93 | 6.71 | 13.56 |
May | 0.212953E+09 | 0.191657E+09 | 826.58 | 28-MAY-15:02 | 743.92 | 743.92 | 6.71 | 14.74 |
June | 0.109607E+10 | 0.986461E+09 | 1804.07 | 24-JUN-21:12 | 1623.66 | 1623.66 | 6.71 | 20.60 |
July | 0.189597E+10 | 0.170637E+10 | 1946.07 | 20-JUL-20:12 | 1751.46 | 1751.46 | 6.71 | 21.27 |
August | 0.158228E+10 | 0.142405E+10 | 1875.81 | 16-AUG-21:12 | 1688.23 | 1688.23 | 6.71 | 20.94 |
September | 0.758953E+09 | 0.683057E+09 | 1528.47 | 06-SEP-21:12 | 1375.62 | 1375.62 | 6.71 | 19.21 |
October | 0.255031E+09 | 0.229528E+09 | 1173.96 | 24-OCT-15:02 | 1056.56 | 1056.56 | 6.71 | 17.17 |
November | 15628986.94 | 14066088.25 | 178.38 | 04-NOV-15:01 | 160.54 | 160.54 | 6.71 | 7.23 |
December | 3376945.54 | 3039250.99 | 44.87 | 20-DEC-09:03 | 40.38 | 40.38 | 6.71 | 3.50 |
Annual Sum or Average | 0.590114E+10 | 0.531103E+10 | ||||||
Minimum of Months | 1010436.85 | 909393.17 | 27.51 | 24.76 | 24.76 | 6.71 | 2.64 | |
Maximum of Months | 0.189597E+10 | 0.170637E+10 | 1946.07 | 1751.46 | 1751.46 | 6.71 | 21.27 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:03 | 14.37 | 14.37 | 47.71 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 48.41 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 48.39 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.65 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 43.01 | 0.06 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:10 | 14.37 | 14.37 | 53.62 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 53.50 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 54.70 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 54.12 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:03 | 14.37 | 14.37 | 53.11 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:02 | 14.37 | 14.37 | 46.73 | 0.06 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 49.33 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 43.01 | 0.06 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 54.70 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.212605E+10 | 0.191345E+10 | 2244.62 | 01-JAN-09:03 | 2020.15 | 2020.15 | 6.74 | 35.20 |
February | 0.209717E+10 | 0.188745E+10 | 2244.62 | 01-FEB-00:03 | 2020.15 | 2020.15 | 6.71 | 35.20 |
March | 0.364229E+10 | 0.327806E+10 | 2244.62 | 01-MAR-00:03 | 2020.15 | 2020.15 | 6.71 | 35.20 |
April | 0.451223E+10 | 0.406100E+10 | 2244.62 | 01-APR-01:10 | 2020.15 | 2020.15 | 6.71 | 35.20 |
May | 0.592881E+10 | 0.533593E+10 | 2244.62 | 01-MAY-00:03 | 2020.15 | 2020.15 | 6.76 | 35.20 |
June | 0.581804E+10 | 0.523624E+10 | 2244.62 | 01-JUN-00:10 | 2020.15 | 2020.15 | 8.35 | 35.20 |
July | 0.601198E+10 | 0.541078E+10 | 2244.62 | 01-JUL-00:10 | 2020.15 | 2020.15 | 9.35 | 35.20 |
August | 0.601198E+10 | 0.541078E+10 | 2244.62 | 01-AUG-00:10 | 2020.15 | 2020.15 | 9.44 | 35.20 |
September | 0.581288E+10 | 0.523159E+10 | 2244.62 | 01-SEP-00:10 | 2020.15 | 2020.15 | 9.21 | 35.20 |
October | 0.566233E+10 | 0.509610E+10 | 2244.62 | 01-OCT-00:03 | 2020.15 | 2020.15 | 6.84 | 35.20 |
November | 0.363592E+10 | 0.327233E+10 | 2244.62 | 01-NOV-00:02 | 2020.15 | 2020.15 | 6.73 | 35.20 |
December | 0.289176E+10 | 0.260258E+10 | 2244.62 | 01-DEC-00:03 | 2020.15 | 2020.15 | 6.71 | 35.20 |
Annual Sum or Average | 0.541514E+11 | 0.487363E+11 | ||||||
Minimum of Months | 0.209717E+10 | 0.188745E+10 | 2244.62 | 2020.15 | 2020.15 | 6.71 | 35.20 | |
Maximum of Months | 0.601198E+10 | 0.541078E+10 | 2244.62 | 2020.15 | 2020.15 | 9.44 | 35.20 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 47.71 | 59.95 | 27933.69 | 59477.65 | 18-JAN-07:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 48.41 | 59.82 | 28177.97 | 57940.30 | 14-FEB-07:20 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 48.39 | 58.81 | 27563.68 | 64704.55 | 06-MAR-07:12 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.65 | 58.96 | 25989.92 | 60998.98 | 23-APR-07:10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 43.01 | 58.19 | 23927.92 | 58235.14 | 02-MAY-06:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 53.62 | 60.14 | 21852.23 | 48213.98 | 01-JUN-06:30 |
July | 0.51 | 726.37 | 29-JUL-03:00 | 60.46 | 66.22 | 20340.68 | 45054.77 | 03-JUL-06:30 |
August | 2.85 | 989.32 | 08-AUG-03:00 | 60.63 | 66.36 | 19860.29 | 44896.90 | 30-AUG-17:09 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 54.12 | 60.08 | 20846.74 | 49715.31 | 30-SEP-07:12 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 53.11 | 60.29 | 22547.84 | 56828.21 | 27-OCT-20:41 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 46.73 | 59.15 | 24689.56 | 59619.68 | 26-NOV-22:21 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 49.33 | 59.03 | 26612.81 | 60439.93 | 25-DEC-08:50 |
Annual Sum or Average | 0.29 | 24171.87 | ||||||
Minimum of Months | 0.00 | 0.00 | 43.01 | 58.19 | 19860.29 | 44896.90 | ||
Maximum of Months | 2.85 | 989.32 | 60.63 | 66.36 | 28177.97 | 64704.55 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 50.40 | 60.00 | 47766.99 | 197013.41 | 02-JAN-09:05 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 51.49 | 60.00 | 47423.70 | 196915.73 | 06-FEB-09:02 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 53.81 | 60.00 | 18950.68 | 139316.40 | 26-MAR-21:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.73 | 60.00 | 13772.39 | 138739.15 | 22-APR-15:02 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 50.32 | 60.00 | 6471.25 | 89505.69 | 19-MAY-15:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 47.53 | 60.00 | 3831.00 | 100446.25 | 06-JUN-15:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 42.03 | 60.00 | 2848.53 | 22768.59 | 24-JUL-08:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 41.72 | 60.00 | 2179.07 | 30980.57 | 22-AUG-18:07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 41.54 | 60.00 | 3647.28 | 97462.43 | 23-SEP-15:04 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 41.42 | 60.00 | 7862.67 | 128522.74 | 08-OCT-21:52 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 49.54 | 60.00 | 20541.35 | 144243.92 | 13-NOV-16:02 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 53.36 | 60.00 | 28532.39 | 144498.91 | 31-DEC-16:03 |
Annual Sum or Average | 0.00 | 16807.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 41.42 | 60.00 | 2179.07 | 22768.59 | ||
Maximum of Months | 0.00 | 0.00 | 53.81 | 60.00 | 47766.99 | 197013.41 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1405.75 | 33694.82 | 17-JAN-19:04 | 6.93 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1862.35 | 50136.42 | 20-FEB-09:02 | 7.04 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 7111.58 | 293691.98 | 27-MAR-15:02 | 8.69 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 31611.56 | 356748.99 | 07-APR-15:02 | 9.12 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 95209.60 | 488997.43 | 31-MAY-21:13 | 10.01 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 313428.03 | 763815.44 | 24-JUN-21:13 | 11.88 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 436880.15 | 802198.63 | 20-JUL-20:13 | 12.14 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 370230.62 | 798988.11 | 03-AUG-21:13 | 12.12 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 231578.31 | 699170.24 | 06-SEP-21:13 | 11.44 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 100968.54 | 538742.40 | 05-OCT-15:02 | 10.35 | 6.70 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 9448.60 | 182205.09 | 10-NOV-09:03 | 7.93 | 6.70 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 2955.19 | 42807.03 | 18-DEC-11:00 | 6.99 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 134497.93 | 0.00 | ||||||
Minimum of Months | 1405.75 | 33694.82 | 6.93 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 436880.15 | 802198.63 | 12.14 | 6.70 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.08 | 9.75 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.04 | 2.17 |
December | 0.14 | 4.55 |
Annual Sum or Average | 0.26 | 5.81 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.14 | 9.75 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.06 | 5.02 |
May | 0.17 | 8.78 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.22 | 7.84 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 8.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 5.08 | 4.14 |
February | 0.28 | 2.27 |
March | 10.60 | 4.77 |
April | 21.44 | 5.20 |
May | 10.04 | 6.36 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.36 | 3.75 |
September | 3.61 | 7.12 |
October | 23.55 | 5.46 |
November | 18.53 | 5.09 |
December | 4.65 | 4.26 |
Annual Sum or Average | 98.13 | 5.27 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 23.55 | 7.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.41 | 114.62 |
February | 0.00 | 0.00 |
March | 0.89 | 107.39 |
April | 2.50 | 90.33 |
May | 1.16 | 78.93 |
June | 1.50 | 56.92 |
July | 1.67 | 56.92 |
August | 1.58 | 56.92 |
September | 1.44 | 65.40 |
October | 1.92 | 91.15 |
November | 1.19 | 91.90 |
December | 0.28 | 74.00 |
Annual Sum or Average | 14.53 | 77.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.50 | 114.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.17 | 295.70 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.17 | 295.70 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 295.70 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 295.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.04 | 0.65 |
February | 3.14 | 0.66 |
March | 0.85 | 0.78 |
April | 0.88 | 0.70 |
May | 1.95 | 0.65 |
June | 3.54 | 0.66 |
July | 6.25 | 0.69 |
August | 6.19 | 0.71 |
September | 3.24 | 0.60 |
October | 1.26 | 0.54 |
November | 0.43 | 0.81 |
December | 1.72 | 0.72 |
Annual Sum or Average | 33.51 | 0.67 |
Minimum of Months | 0.43 | 0.54 |
Maximum of Months | 6.25 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.10 | 0.63 |
February | 3.11 | 0.63 |
March | 0.56 | 0.66 |
April | 0.87 | 0.73 |
May | 1.81 | 0.66 |
June | 3.18 | 0.72 |
July | 5.87 | 0.70 |
August | 5.03 | 0.76 |
September | 1.53 | 0.81 |
October | 0.35 | 0.75 |
November | 0.71 | 0.67 |
December | 2.60 | 0.63 |
Annual Sum or Average | 29.71 | 0.69 |
Minimum of Months | 0.35 | 0.63 |
Maximum of Months | 5.87 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 0.00 |
October | 0.00 | 0.00 |
November | 0.08 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.44 | 0.65 |
February | 1.19 | 0.65 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.08 | 0.80 |
June | 1.60 | 1.00 |
July | 3.85 | 1.02 |
August | 3.17 | 1.05 |
September | 0.74 | 1.18 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.14 | 0.45 |
Annual Sum or Average | 12.23 | 0.95 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.85 | 1.18 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.12 | 0.68 |
February | 1.93 | 0.70 |
March | 0.00 | 0.00 |
April | 1.04 | 0.42 |
May | 2.31 | 0.49 |
June | 2.50 | 0.56 |
July | 3.48 | 0.79 |
August | 2.58 | 0.85 |
September | 2.68 | 0.58 |
October | 1.91 | 0.39 |
November | 0.39 | 0.77 |
December | 1.29 | 0.74 |
Annual Sum or Average | 23.25 | 0.64 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.48 | 0.85 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.00 | 0.62 |
February | 3.10 | 0.59 |
March | 0.50 | 0.81 |
April | 0.88 | 0.46 |
May | 2.12 | 0.48 |
June | 2.49 | 0.56 |
July | 3.97 | 0.79 |
August | 3.99 | 0.71 |
September | 2.32 | 0.53 |
October | 0.06 | 0.30 |
November | 0.62 | 0.72 |
December | 1.79 | 0.71 |
Annual Sum or Average | 25.84 | 0.64 |
Minimum of Months | 0.06 | 0.30 |
Maximum of Months | 4.00 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.40 | 0.63 |
February | 2.72 | 0.64 |
March | 1.16 | 0.80 |
April | 1.00 | 0.66 |
May | 2.31 | 0.57 |
June | 3.82 | 0.64 |
July | 5.66 | 0.78 |
August | 5.75 | 0.79 |
September | 3.31 | 0.64 |
October | 1.72 | 0.55 |
November | 0.72 | 0.81 |
December | 1.94 | 0.73 |
Annual Sum or Average | 33.53 | 0.70 |
Minimum of Months | 0.72 | 0.55 |
Maximum of Months | 5.75 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.87 | 0.58 |
February | 1.69 | 0.59 |
March | 1.44 | 0.69 |
April | 1.08 | 0.72 |
May | 2.38 | 0.57 |
June | 3.95 | 0.65 |
July | 5.74 | 0.78 |
August | 6.03 | 0.74 |
September | 2.74 | 0.66 |
October | 0.48 | 0.73 |
November | 1.28 | 0.60 |
December | 3.04 | 0.63 |
Annual Sum or Average | 32.74 | 0.68 |
Minimum of Months | 0.48 | 0.57 |
Maximum of Months | 6.03 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.96 | 0.59 |
February | 0.94 | 0.55 |
March | 0.95 | 0.64 |
April | 0.64 | 0.46 |
May | 1.37 | 0.54 |
June | 2.97 | 0.66 |
July | 5.72 | 0.71 |
August | 4.46 | 0.74 |
September | 2.12 | 0.76 |
October | 1.76 | 0.55 |
November | 1.42 | 0.49 |
December | 0.96 | 0.55 |
Annual Sum or Average | 25.26 | 0.65 |
Minimum of Months | 0.64 | 0.46 |
Maximum of Months | 5.72 | 0.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.66 | 125.58 |
February | 0.00 | 0.00 |
March | 1.22 | 143.38 |
April | 2.07 | 159.12 |
May | 0.57 | 138.36 |
June | 1.17 | 99.96 |
July | 1.00 | 99.96 |
August | 0.75 | 99.96 |
September | 1.00 | 99.96 |
October | 1.80 | 129.65 |
November | 2.15 | 111.26 |
December | 0.42 | 81.63 |
Annual Sum or Average | 12.80 | 122.17 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 2.15 | 159.12 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.02 | 158.13 |
February | 0.00 | 0.00 |
March | 1.30 | 137.90 |
April | 2.76 | 175.63 |
May | 1.25 | 183.81 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.25 | 99.96 |
October | 0.89 | 155.78 |
November | 3.32 | 132.08 |
December | 0.53 | 80.23 |
Annual Sum or Average | 11.31 | 150.17 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.32 | 183.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.63 | 10.22 |
February | 0.41 | 5.36 |
March | 11.37 | 11.43 |
April | 19.53 | 13.24 |
May | 9.18 | 16.19 |
June | 0.08 | 20.01 |
July | 0.00 | 0.00 |
August | 0.40 | 13.27 |
September | 3.26 | 17.38 |
October | 22.41 | 12.72 |
November | 23.08 | 12.67 |
December | 5.34 | 10.08 |
Annual Sum or Average | 99.69 | 12.86 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 23.08 | 20.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.721810E+11 | 0.00 | 0.201056E+09 | 0.375402E+11 | 0.00 | 0.00 |
February | 0.679492E+11 | 0.00 | 0.201457E+09 | 0.337626E+11 | 0.00 | 0.00 |
March | 0.321677E+11 | 0.00 | 0.615827E+10 | 0.386472E+11 | 0.00 | 0.00 |
April | 0.294352E+11 | 0.00 | 0.469006E+11 | 0.375765E+11 | 0.00 | 0.00 |
May | 0.168141E+11 | 0.00 | 0.176108E+12 | 0.373640E+11 | 0.00 | 0.00 |
June | 0.100425E+11 | 0.00 | 0.616653E+12 | 0.343925E+11 | 0.00 | 0.00 |
July | 0.772912E+10 | 0.00 | 0.880013E+12 | 0.353977E+11 | 0.00 | 0.00 |
August | 0.590587E+10 | 0.00 | 0.730032E+12 | 0.356443E+11 | 0.00 | 0.00 |
September | 0.940959E+10 | 0.00 | 0.443509E+12 | 0.345345E+11 | 0.00 | 0.00 |
October | 0.191192E+11 | 0.00 | 0.179768E+12 | 0.380710E+11 | 0.00 | 0.00 |
November | 0.346827E+11 | 0.00 | 0.702257E+10 | 0.379046E+11 | 0.00 | 0.00 |
December | 0.388827E+11 | 0.00 | 0.357819E+09 | 0.379263E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.344319E+12 | 0.00 | 0.308692E+13 | 0.438761E+12 | 0.00 | 0.00 |
Minimum of Months | 0.590587E+10 | 0.00 | 0.201056E+09 | 0.337626E+11 | 0.00 | 0.00 |
Maximum of Months | 0.721810E+11 | 0.00 | 0.880013E+12 | 0.386472E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.457239E+10 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
February | 0.452831E+10 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
March | 0.458246E+09 | 0.00 | 0.689690E+09 | 0.587767E+10 | 0.00 | 0.00 |
April | 16001.95 | 0.00 | 0.635838E+10 | 0.568807E+10 | 0.00 | 0.00 |
May | 51770.71 | 0.00 | 0.234222E+11 | 0.587767E+10 | 0.00 | 0.00 |
June | 26037.46 | 0.00 | 0.997309E+11 | 0.568807E+10 | 0.00 | 0.00 |
July | 12636.51 | 0.00 | 0.141708E+12 | 0.587767E+10 | 0.00 | 0.00 |
August | 19967.56 | 0.00 | 0.113160E+12 | 0.587767E+10 | 0.00 | 0.00 |
September | 34368.24 | 0.00 | 0.687130E+11 | 0.568807E+10 | 0.00 | 0.00 |
October | 76067.93 | 0.00 | 0.244480E+11 | 0.587767E+10 | 0.00 | 0.00 |
November | 0.311821E+09 | 0.00 | 0.604784E+09 | 0.568807E+10 | 0.00 | 0.00 |
December | 0.746831E+09 | 0.00 | 0.00 | 0.587767E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106178E+11 | 0.00 | 0.478835E+12 | 0.692049E+11 | 0.00 | 0.00 |
Minimum of Months | 12636.51 | 0.00 | 0.00 | 0.530887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.457239E+10 | 0.00 | 0.141708E+12 | 0.587767E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.375402E+11 | 0.201056E+09 | 0.721810E+11 | 0.564621E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337626E+11 | 0.201457E+09 | 0.679492E+11 | 0.556488E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386472E+11 | 0.615827E+10 | 0.321677E+11 | 0.395236E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375765E+11 | 0.469006E+11 | 0.294352E+11 | 0.167468E+12 | 0.381758E+09 | 0.00 | 0.00 | 0.00 |
May | 0.373640E+11 | 0.176108E+12 | 0.168141E+11 | 0.236825E+11 | 0.559295E+10 | 0.00 | 0.00 | 0.00 |
June | 0.343925E+11 | 0.616653E+12 | 0.100425E+11 | 68506366.53 | 0.927541E+11 | 0.00 | 0.00 | 0.00 |
July | 0.353977E+11 | 0.880013E+12 | 0.772912E+10 | 0.00 | 0.297053E+12 | 0.00 | 0.00 | 0.00 |
August | 0.356443E+11 | 0.730032E+12 | 0.590587E+10 | 270529.00 | 0.222343E+12 | 0.00 | 0.00 | 0.00 |
September | 0.345345E+11 | 0.443509E+12 | 0.940959E+10 | 0.381398E+10 | 0.460274E+11 | 0.00 | 0.00 | 0.00 |
October | 0.380710E+11 | 0.179768E+12 | 0.191192E+11 | 0.798755E+11 | 0.308736E+10 | 0.00 | 0.00 | 0.00 |
November | 0.379046E+11 | 0.702257E+10 | 0.346827E+11 | 0.296811E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379263E+11 | 0.357819E+09 | 0.388827E+11 | 0.500245E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438761E+12 | 0.308692E+13 | 0.344319E+12 | 0.258831E+13 | 0.667239E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.337626E+11 | 0.201056E+09 | 0.590587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386472E+11 | 0.880013E+12 | 0.721810E+11 | 0.564621E+12 | 0.297053E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.587767E+10 | 0.00 | 0.457239E+10 | 0.978133E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.00 | 0.452831E+10 | 0.960633E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.689690E+09 | 0.458246E+09 | 0.700226E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 0.635838E+10 | 16001.95 | 0.339142E+11 | 0.130198E+09 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 0.234222E+11 | 51770.71 | 0.718057E+10 | 0.103790E+10 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 0.997309E+11 | 26037.46 | 0.141177E+09 | 0.152005E+11 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 0.141708E+12 | 12636.51 | 59216.46 | 0.548877E+11 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 0.113160E+12 | 19967.56 | 89689645.99 | 0.443684E+11 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 0.687130E+11 | 34368.24 | 0.140749E+10 | 0.905967E+10 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 0.244480E+11 | 76067.93 | 0.177788E+11 | 0.594113E+09 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.604784E+09 | 0.311821E+09 | 0.556918E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.00 | 0.746831E+09 | 0.867774E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.478835E+12 | 0.106178E+11 | 0.466880E+12 | 0.125279E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.530887E+10 | 0.00 | 12636.51 | 59216.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.141708E+12 | 0.457239E+10 | 0.978133E+11 | 0.548877E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.375402E+11 | 0.721810E+11 | 0.201056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337626E+11 | 0.679492E+11 | 0.201457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386472E+11 | 0.321677E+11 | 0.615827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.375765E+11 | 0.294352E+11 | 0.469006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.373640E+11 | 0.168141E+11 | 0.176108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.343925E+11 | 0.100425E+11 | 0.616653E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.353977E+11 | 0.772912E+10 | 0.880013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.356443E+11 | 0.590587E+10 | 0.730032E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345345E+11 | 0.940959E+10 | 0.443509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.380710E+11 | 0.191192E+11 | 0.179768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.379046E+11 | 0.346827E+11 | 0.702257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379263E+11 | 0.388827E+11 | 0.357819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438761E+12 | 0.344319E+12 | 0.308692E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.337626E+11 | 0.590587E+10 | 0.201056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.386472E+11 | 0.721810E+11 | 0.880013E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.587767E+10 | 0.457239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530887E+10 | 0.452831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.587767E+10 | 0.458246E+09 | 0.689690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.568807E+10 | 16001.95 | 0.635838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.587767E+10 | 51770.71 | 0.234222E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.568807E+10 | 26037.46 | 0.997309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.587767E+10 | 12636.51 | 0.141708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.587767E+10 | 19967.56 | 0.113160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.568807E+10 | 34368.24 | 0.687130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.587767E+10 | 76067.93 | 0.244480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.568807E+10 | 0.311821E+09 | 0.604784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587767E+10 | 0.746831E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692049E+11 | 0.106178E+11 | 0.478835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.530887E+10 | 12636.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.587767E+10 | 0.457239E+10 | 0.141708E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.457406E+11 | 0.00 | 0.00 | 2313736.02 | 0.00 | 0.00 | 0.579654E+10 | 0.00 | 1.01 |
February | 0.465607E+11 | 0.00 | 0.00 | 126228.58 | 0.00 | 0.00 | 0.556679E+09 | 0.00 | 1.02 |
March | 0.492870E+11 | 0.00 | 0.00 | 0.00 | 8783044.48 | 0.00 | 0.00 | 0.00 | 1.01 |
April | 0.453709E+11 | 0.00 | 0.00 | 0.00 | 56526729.72 | 0.00 | 0.00 | 0.00 | 1.02 |
May | 0.358029E+11 | 0.00 | 583883.51 | 0.00 | 0.811560E+09 | 0.00 | 0.00 | 7362.36 | 1.06 |
June | 0.698933E+10 | 0.00 | 0.00 | 0.00 | 0.193568E+11 | 0.00 | 0.00 | 0.00 | 1.06 |
July | 0.223485E+09 | 0.00 | 0.00 | 0.00 | 0.381527E+11 | 0.00 | 0.00 | 0.00 | 1.04 |
August | 0.366242E+10 | 0.00 | 0.00 | 0.00 | 0.241780E+11 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 0.171199E+11 | 0.00 | 0.00 | 4377.97 | 0.103421E+11 | 0.00 | 79447864.95 | 0.00 | 1.07 |
October | 0.207416E+11 | 32225466.47 | 0.00 | 20326768.62 | 0.176696E+10 | 0.00 | 0.180249E+11 | 0.00 | 1.06 |
November | 0.128494E+11 | 0.00 | 0.00 | 47416624.69 | 0.00 | 0.00 | 0.386773E+11 | 0.00 | 1.05 |
December | 0.217702E+11 | 0.00 | 0.00 | 18878711.81 | 0.00 | 0.00 | 0.284867E+11 | 0.00 | 1.03 |
Annual Sum or Average | 0.306118E+12 | 32225466.47 | 583883.51 | 89066447.70 | 0.946734E+11 | 0.00 | 0.916215E+11 | 7362.36 | 1.04 |
Minimum of Months | 0.223485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 |
Maximum of Months | 0.492870E+11 | 32225466.47 | 583883.51 | 47416624.69 | 0.381527E+11 | 0.00 | 0.386773E+11 | 7362.36 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274295E+10 | 0.00 | 0.00 | 231660.79 | 0.00 | 0.371524E+10 | 0.158948E+09 | 0.00 | 2.35 |
February | 0.286541E+10 | 0.00 | 0.00 | 175521.40 | 0.00 | 0.298280E+10 | 0.190519E+09 | 0.00 | 2.36 |
March | 0.479914E+10 | 0.00 | 0.00 | 469668.81 | 1125312.58 | 0.123613E+10 | 0.303898E+09 | 0.00 | 2.34 |
April | 0.537272E+10 | 2100819.40 | 0.00 | 37902.25 | 5145292.07 | 0.419848E+09 | 20454347.90 | 0.00 | 2.38 |
May | 0.458718E+10 | 0.00 | 0.00 | 0.00 | 0.104055E+09 | 0.00 | 0.00 | 0.00 | 2.47 |
June | 0.895496E+09 | 63627736.09 | 0.00 | 0.00 | 0.241643E+10 | 0.00 | 0.00 | 0.00 | 2.46 |
July | 28612970.48 | 0.520689E+09 | 0.00 | 333.59 | 0.436756E+10 | 0.00 | 20282.10 | 0.00 | 2.43 |
August | 0.459015E+09 | 0.115999E+10 | 0.00 | 51116.79 | 0.193822E+10 | 0.00 | 10180517.62 | 0.00 | 2.44 |
September | 0.211819E+10 | 0.216582E+09 | 0.00 | 492218.41 | 0.111378E+10 | 0.00 | 90288390.40 | 0.00 | 2.49 |
October | 0.429750E+10 | 0.149838E+09 | 0.00 | 1488521.60 | 97818135.07 | 0.00 | 0.659628E+09 | 0.00 | 2.48 |
November | 0.518176E+10 | 0.00 | 0.00 | 461447.86 | 0.00 | 0.867444E+09 | 0.312047E+09 | 0.00 | 2.36 |
December | 0.356037E+10 | 0.00 | 0.00 | 583452.20 | 0.00 | 0.252809E+10 | 0.317149E+09 | 0.00 | 2.37 |
Annual Sum or Average | 0.369084E+11 | 0.211282E+10 | 0.00 | 3991843.71 | 0.100441E+11 | 0.117496E+11 | 0.206313E+10 | 0.00 | 2.41 |
Minimum of Months | 28612970.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 |
Maximum of Months | 0.537272E+10 | 0.115999E+10 | 0.00 | 1488521.60 | 0.436756E+10 | 0.371524E+10 | 0.659628E+09 | 0.00 | 2.49 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
February | 0.447920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.51 |
March | 0.460964E+10 | 0.00 | 0.00 | 17775.42 | 834957.07 | 0.00 | 75801917.43 | 0.00 | 1.50 |
April | 0.419280E+10 | 0.00 | 0.00 | 34952.60 | 5373693.92 | 0.00 | 0.120334E+09 | 0.00 | 1.53 |
May | 0.328608E+10 | 1224683.67 | 0.00 | 26585.82 | 75982175.35 | 0.00 | 0.117479E+09 | 0.00 | 1.59 |
June | 0.644433E+09 | 37360916.19 | 0.00 | 15992.09 | 0.180278E+10 | 0.00 | 19989159.14 | 0.00 | 1.58 |
July | 21230191.98 | 0.200313E+09 | 0.00 | 386.65 | 0.342666E+10 | 0.00 | 14909.74 | 0.00 | 1.56 |
August | 0.325392E+09 | 0.278511E+09 | 0.00 | 61990.23 | 0.201996E+10 | 0.00 | 22713018.48 | 0.00 | 1.57 |
September | 0.155264E+10 | 48945791.99 | 0.00 | 39149.02 | 0.934225E+09 | 0.00 | 82367788.94 | 0.00 | 1.59 |
October | 0.323375E+10 | 3501108.19 | 0.00 | 256945.15 | 0.167538E+09 | 0.00 | 0.399681E+09 | 0.00 | 1.56 |
November | 0.457015E+10 | 0.00 | 0.00 | 52549.63 | 0.00 | 0.00 | 0.133395E+09 | 0.00 | 1.51 |
December | 0.472253E+10 | 0.00 | 0.00 | 7.92 | 0.00 | 0.00 | 1156171.08 | 0.00 | 1.51 |
Annual Sum or Average | 0.365374E+11 | 0.569856E+09 | 0.00 | 506334.54 | 0.843336E+10 | 0.00 | 0.972933E+09 | 0.00 | 1.54 |
Minimum of Months | 21230191.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 |
Maximum of Months | 0.489958E+10 | 0.278511E+09 | 0.00 | 256945.15 | 0.342666E+10 | 0.00 | 0.399681E+09 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.422307E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493153E+09 | 0.00 | 0.00 | 0.68 |
February | 0.372885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582739E+09 | 0.00 | 0.00 | 0.69 |
March | 0.451012E+10 | 0.00 | 0.00 | 0.00 | 803711.51 | 0.00 | 0.00 | 0.00 | 0.68 |
April | 0.415176E+10 | 0.00 | 0.00 | 0.00 | 5172600.83 | 0.00 | 0.00 | 0.00 | 0.69 |
May | 0.327622E+10 | 0.00 | 0.00 | 0.00 | 74317642.44 | 0.00 | 0.00 | 0.00 | 0.72 |
June | 0.639573E+09 | 0.00 | 0.00 | 0.00 | 0.177128E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 20450444.79 | 0.00 | 0.00 | 0.00 | 0.349124E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
August | 0.335138E+09 | 0.00 | 0.00 | 0.00 | 0.221246E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
September | 0.157386E+10 | 0.00 | 0.00 | 0.00 | 0.946379E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.349603E+10 | 0.00 | 0.00 | 0.00 | 0.164639E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
November | 0.452755E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
December | 0.454692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.350295E+11 | 0.00 | 0.00 | 0.00 | 0.866630E+10 | 0.107589E+10 | 0.00 | 0.00 | 0.70 |
Minimum of Months | 20450444.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
Maximum of Months | 0.454692E+10 | 0.00 | 0.00 | 0.00 | 0.349124E+10 | 0.582739E+09 | 0.00 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.768588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152406E+10 | 0.00 | 0.00 | 0.58 |
February | 0.611686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148425E+10 | 0.00 | 0.00 | 0.58 |
March | 0.169564E+10 | 0.00 | 0.00 | 0.00 | 390698.83 | 0.496813E+09 | 0.00 | 0.00 | 0.57 |
April | 0.197722E+10 | 0.00 | 0.00 | 0.00 | 2514495.65 | 41025281.05 | 0.00 | 0.00 | 0.58 |
May | 0.159263E+10 | 0.00 | 0.00 | 0.00 | 36127162.08 | 0.00 | 0.00 | 0.00 | 0.61 |
June | 0.310908E+09 | 0.00 | 0.00 | 0.00 | 0.861053E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 9941334.38 | 0.00 | 0.00 | 0.00 | 0.169716E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.162917E+09 | 0.00 | 0.00 | 0.00 | 0.107552E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.765084E+09 | 0.00 | 0.00 | 0.00 | 0.460052E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.169948E+10 | 0.00 | 0.00 | 0.00 | 80033931.38 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.189466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306264E+09 | 0.00 | 0.00 | 0.58 |
December | 0.127562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.934722E+09 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.127644E+11 | 0.00 | 0.00 | 0.00 | 0.421285E+10 | 0.478714E+10 | 0.00 | 0.00 | 0.59 |
Minimum of Months | 9941334.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.197722E+10 | 0.00 | 0.00 | 0.00 | 0.169716E+10 | 0.152406E+10 | 0.00 | 0.00 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.975096E+09 | 0.00 | 0.00 | 94462574.80 | 0.00 | 0.00 | 0.746318E+11 | 0.00 | 22.88 |
February | 0.835389E+09 | 0.00 | 0.00 | 78846140.05 | 0.00 | 0.00 | 0.680944E+11 | 0.00 | 23.03 |
March | 0.725350E+09 | 11566651.34 | 0.00 | 0.101644E+09 | 0.00 | 0.00 | 0.721580E+11 | 0.00 | 22.90 |
April | 0.110720E+10 | 71651331.24 | 0.00 | 0.110959E+09 | 2794883.60 | 0.00 | 0.658065E+11 | 0.00 | 23.16 |
May | 0.130846E+10 | 0.104421E+10 | 0.00 | 86587631.07 | 56102203.66 | 0.00 | 0.502874E+11 | 0.00 | 23.57 |
June | 0.103934E+09 | 0.257900E+11 | 0.00 | 28045075.96 | 0.840269E+09 | 0.00 | 0.970329E+10 | 0.00 | 22.88 |
July | 8811097.38 | 0.507625E+11 | 0.00 | 1295517.39 | 0.165273E+10 | 0.00 | 0.285474E+09 | 0.00 | 22.35 |
August | 55353054.46 | 0.322995E+11 | 0.00 | 17970830.16 | 0.111137E+10 | 0.00 | 0.485725E+10 | 0.00 | 22.56 |
September | 0.626730E+09 | 0.138159E+11 | 0.00 | 51533153.67 | 0.427310E+09 | 0.00 | 0.235271E+11 | 0.00 | 23.10 |
October | 0.137185E+10 | 0.224906E+10 | 0.00 | 98487419.64 | 0.179543E+09 | 0.00 | 0.540807E+11 | 0.00 | 23.31 |
November | 0.119575E+10 | 0.00 | 0.00 | 0.110131E+09 | 0.00 | 0.00 | 0.718452E+11 | 0.00 | 23.01 |
December | 0.612178E+09 | 0.00 | 0.00 | 95318547.35 | 0.00 | 0.00 | 0.724029E+11 | 0.00 | 23.02 |
Annual Sum or Average | 0.892610E+10 | 0.126044E+12 | 0.00 | 0.875280E+09 | 0.427012E+10 | 0.00 | 0.567680E+12 | 0.00 | 22.98 |
Minimum of Months | 8811097.38 | 0.00 | 0.00 | 1295517.39 | 0.00 | 0.00 | 0.285474E+09 | 0.00 | 22.35 |
Maximum of Months | 0.137185E+10 | 0.507625E+11 | 0.00 | 0.110959E+09 | 0.165273E+10 | 0.00 | 0.746318E+11 | 0.00 | 23.57 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.234568E+11 | 0.00 | 0.00 | 1884597.92 | 0.00 | 0.561690E+09 | 0.258057E+10 | 0.00 | 3.36 |
February | 0.211387E+11 | 0.00 | 0.00 | 2006197.22 | 0.00 | 0.222513E+09 | 0.293273E+10 | 0.00 | 3.38 |
March | 0.178786E+11 | 2946899.44 | 0.00 | 5461555.53 | 1575536.14 | 0.00 | 0.762957E+10 | 0.00 | 3.36 |
April | 0.155295E+11 | 19497815.58 | 0.00 | 4253650.50 | 9621659.36 | 0.00 | 0.783360E+10 | 0.00 | 3.41 |
May | 0.985251E+10 | 86132759.41 | 0.00 | 5061937.48 | 0.332048E+09 | 0.00 | 0.858039E+10 | 0.00 | 3.54 |
June | 0.121239E+10 | 0.469478E+10 | 0.00 | 2940136.44 | 0.527288E+10 | 0.00 | 0.238351E+10 | 0.00 | 3.53 |
July | 24664965.99 | 0.122260E+11 | 0.00 | 249540.09 | 0.742073E+10 | 0.00 | 90158897.84 | 0.00 | 3.48 |
August | 0.372933E+09 | 0.945028E+10 | 0.00 | 4156772.62 | 0.301925E+10 | 0.00 | 0.150950E+10 | 0.00 | 3.51 |
September | 0.307884E+10 | 0.321737E+10 | 0.00 | 9321616.99 | 0.210847E+10 | 0.00 | 0.579663E+10 | 0.00 | 3.56 |
October | 0.567191E+10 | 0.778998E+09 | 0.00 | 22029370.09 | 0.181028E+09 | 0.00 | 0.143827E+11 | 0.00 | 3.56 |
November | 0.173139E+11 | 0.00 | 0.00 | 6780656.68 | 0.00 | 0.00 | 0.828705E+10 | 0.00 | 3.39 |
December | 0.211657E+11 | 0.00 | 0.00 | 4134734.73 | 0.00 | 47846255.68 | 0.459480E+10 | 0.00 | 3.41 |
Annual Sum or Average | 0.136697E+12 | 0.304760E+11 | 0.00 | 68280766.28 | 0.183456E+11 | 0.832050E+09 | 0.666013E+11 | 0.00 | 3.46 |
Minimum of Months | 24664965.99 | 0.00 | 0.00 | 249540.09 | 0.00 | 0.00 | 90158897.84 | 0.00 | 3.36 |
Maximum of Months | 0.234568E+11 | 0.122260E+11 | 0.00 | 22029370.09 | 0.742073E+10 | 0.561690E+09 | 0.143827E+11 | 0.00 | 3.56 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.905649E+11 | 0.00 | 0.00 | 1574552.41 | 0.00 | 0.00 | 0.475452E+10 | 0.00 | 1.74 |
February | 0.826473E+11 | 0.00 | 0.00 | 1164158.78 | 0.00 | 0.00 | 0.449411E+10 | 0.00 | 1.75 |
March | 0.747422E+11 | 0.00 | 0.00 | 8411970.65 | 16244029.86 | 0.00 | 0.164586E+11 | 0.00 | 1.74 |
April | 0.626971E+11 | 0.00 | 0.00 | 12296828.66 | 0.104545E+09 | 0.00 | 0.213096E+11 | 0.00 | 1.77 |
May | 0.475728E+11 | 64972424.57 | 0.00 | 9272479.22 | 0.143708E+10 | 0.00 | 0.186539E+11 | 0.00 | 1.84 |
June | 0.803652E+10 | 0.689363E+10 | 0.00 | 3121709.40 | 0.289063E+11 | 0.00 | 0.488695E+10 | 0.00 | 1.83 |
July | 0.146801E+09 | 0.183828E+11 | 0.00 | 301149.17 | 0.521796E+11 | 0.00 | 0.266228E+09 | 0.00 | 1.80 |
August | 0.277660E+10 | 0.143340E+11 | 0.00 | 6090542.14 | 0.303859E+11 | 0.00 | 0.399087E+10 | 0.00 | 1.81 |
September | 0.201237E+11 | 0.547042E+10 | 0.00 | 9407375.69 | 0.136571E+11 | 0.00 | 0.116904E+11 | 0.00 | 1.84 |
October | 0.366630E+11 | 0.322788E+09 | 0.00 | 36623788.60 | 0.300477E+10 | 0.00 | 0.344068E+11 | 0.00 | 1.81 |
November | 0.700092E+11 | 0.00 | 0.00 | 14202490.76 | 0.00 | 0.00 | 0.216274E+11 | 0.00 | 1.75 |
December | 0.817305E+11 | 0.00 | 0.00 | 3406776.16 | 0.00 | 0.00 | 0.101650E+11 | 0.00 | 1.75 |
Annual Sum or Average | 0.577711E+12 | 0.454687E+11 | 0.00 | 0.105874E+09 | 0.129692E+12 | 0.00 | 0.152704E+12 | 0.00 | 1.79 |
Minimum of Months | 0.146801E+09 | 0.00 | 0.00 | 301149.17 | 0.00 | 0.00 | 0.266228E+09 | 0.00 | 1.74 |
Maximum of Months | 0.905649E+11 | 0.183828E+11 | 0.00 | 36623788.60 | 0.521796E+11 | 0.00 | 0.344068E+11 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.338459E+09 | 0.00 | 0.00 | 287123.08 | 0.00 | 0.122951E+10 | 30471170.05 | 0.00 | 0.47 |
February | 0.351465E+09 | 0.00 | 0.00 | 535854.99 | 0.00 | 0.111627E+10 | 53581878.58 | 0.00 | 0.47 |
March | 0.420053E+09 | 0.00 | 0.00 | 2877468.30 | 96024.89 | 0.882992E+09 | 0.331277E+09 | 0.00 | 0.47 |
April | 0.379336E+09 | 1104259.30 | 0.00 | 5631211.67 | 1908525.16 | 0.513862E+09 | 0.593192E+09 | 0.00 | 0.47 |
May | 0.342860E+09 | 15806460.69 | 16136.88 | 8669061.50 | 9643078.07 | 78328492.14 | 0.812437E+09 | 178.28 | 0.47 |
June | 0.100379E+09 | 0.530087E+09 | 306912.73 | 3756059.81 | 0.171746E+09 | 108395.79 | 0.139686E+09 | 17025.39 | 0.48 |
July | 2136163.78 | 0.100125E+10 | 296088.83 | 72868.62 | 0.331290E+09 | 887.48 | 1389728.69 | 7711.98 | 0.48 |
August | 34075828.02 | 0.739946E+09 | 97926.85 | 2617032.88 | 0.174288E+09 | 14052.03 | 53584131.53 | 9977.22 | 0.48 |
September | 0.188923E+09 | 0.242636E+09 | 271779.81 | 5353492.25 | 0.130122E+09 | 9436042.15 | 0.367638E+09 | 9897.04 | 0.47 |
October | 0.315187E+09 | 60068927.32 | 47621.42 | 7610743.83 | 15324626.50 | 0.173232E+09 | 0.780566E+09 | 6382.04 | 0.47 |
November | 0.436830E+09 | 0.00 | 0.00 | 1425937.93 | 0.00 | 0.891757E+09 | 0.290604E+09 | 0.00 | 0.47 |
December | 0.378195E+09 | 0.00 | 0.00 | 377675.21 | 0.00 | 0.113391E+10 | 62957739.82 | 0.00 | 0.47 |
Annual Sum or Average | 0.328790E+10 | 0.259090E+10 | 1036466.52 | 39214530.08 | 0.834418E+09 | 0.602943E+10 | 0.351738E+10 | 51171.94 | 0.47 |
Minimum of Months | 2136163.78 | 0.00 | 0.00 | 72868.62 | 0.00 | 887.48 | 1389728.69 | 0.00 | 0.47 |
Maximum of Months | 0.436830E+09 | 0.100125E+10 | 306912.73 | 8669061.50 | 0.331290E+09 | 0.122951E+10 | 0.812437E+09 | 17025.39 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262531E+09 | 0.00 | 0.00 | 47192.69 | 0.00 | 0.132815E+10 | 8000818.73 | 0.00 | 0.47 |
February | 0.266182E+09 | 0.00 | 0.00 | 111541.06 | 0.00 | 0.123291E+10 | 22655260.38 | 0.00 | 0.47 |
March | 0.444113E+09 | 0.00 | 0.00 | 1490161.11 | 96024.89 | 0.100199E+10 | 0.189603E+09 | 0.00 | 0.47 |
April | 0.398718E+09 | 738976.71 | 0.00 | 4450059.42 | 2273807.75 | 0.568287E+09 | 0.520566E+09 | 0.00 | 0.47 |
May | 0.354063E+09 | 15725979.99 | 0.00 | 8150057.16 | 9739873.93 | 88954242.14 | 0.791127E+09 | 0.00 | 0.47 |
June | 0.100940E+09 | 0.526984E+09 | 318207.57 | 3660342.44 | 0.174839E+09 | 108395.79 | 0.139220E+09 | 16131.36 | 0.48 |
July | 2136163.78 | 0.998504E+09 | 281826.07 | 71830.15 | 0.334048E+09 | 887.48 | 1390767.16 | 7307.94 | 0.48 |
August | 34301035.58 | 0.735281E+09 | 126272.87 | 2365881.10 | 0.178926E+09 | 39312.34 | 53584815.44 | 9006.48 | 0.48 |
September | 0.205678E+09 | 0.237443E+09 | 307085.35 | 4046437.63 | 0.135273E+09 | 10124288.03 | 0.351502E+09 | 16874.45 | 0.47 |
October | 0.389963E+09 | 37220014.76 | 29038.35 | 4326727.06 | 38194854.03 | 0.296185E+09 | 0.586119E+09 | 3650.14 | 0.47 |
November | 0.430754E+09 | 0.00 | 0.00 | 402514.30 | 0.00 | 0.106027E+10 | 0.129194E+09 | 0.00 | 0.47 |
December | 0.320440E+09 | 0.00 | 0.00 | 46336.55 | 0.00 | 0.125053E+10 | 4426605.15 | 0.00 | 0.47 |
Annual Sum or Average | 0.320982E+10 | 0.255190E+10 | 1062430.22 | 29169080.68 | 0.873391E+09 | 0.683754E+10 | 0.279739E+10 | 52970.37 | 0.47 |
Minimum of Months | 2136163.78 | 0.00 | 0.00 | 46336.55 | 0.00 | 887.48 | 1390767.16 | 0.00 | 0.47 |
Maximum of Months | 0.444113E+09 | 0.998504E+09 | 318207.57 | 8150057.16 | 0.334048E+09 | 0.132815E+10 | 0.791127E+09 | 16874.45 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164036E+11 | 0.00 | 0.00 | 1137604.49 | 0.00 | 0.485718E+10 | 0.412998E+09 | 0.00 | 0.53 |
February | 0.183127E+11 | 0.00 | 0.00 | 3466368.84 | 0.00 | 0.134202E+10 | 0.974522E+09 | 0.00 | 0.53 |
March | 0.195843E+11 | 1301866.23 | 0.00 | 9410709.30 | 0.00 | 0.187890E+09 | 0.241485E+10 | 0.00 | 0.53 |
April | 0.170137E+11 | 40846101.86 | 0.00 | 14940356.98 | 0.00 | 0.00 | 0.319959E+10 | 0.00 | 0.54 |
May | 0.999827E+10 | 0.306472E+09 | 0.00 | 31363527.65 | 38783708.22 | 0.00 | 0.681288E+10 | 0.00 | 0.54 |
June | 0.149800E+10 | 0.887777E+10 | 0.00 | 19799942.40 | 0.641786E+09 | 0.00 | 0.178929E+10 | 0.00 | 0.54 |
July | 0.00 | 0.178388E+11 | 0.00 | 1413443.53 | 0.231354E+09 | 0.00 | 47389122.42 | 0.00 | 0.54 |
August | 0.182085E+09 | 0.123789E+11 | 0.00 | 22131403.01 | 17369025.61 | 0.00 | 0.101991E+10 | 0.00 | 0.54 |
September | 0.277654E+10 | 0.492006E+10 | 0.00 | 48615808.67 | 0.137458E+09 | 0.00 | 0.492099E+10 | 0.00 | 0.54 |
October | 0.574690E+10 | 0.100585E+10 | 0.00 | 88823467.84 | 17032412.13 | 0.00 | 0.114718E+11 | 0.00 | 0.54 |
November | 0.167314E+11 | 0.00 | 0.00 | 28655179.69 | 0.00 | 0.00 | 0.521162E+10 | 0.00 | 0.54 |
December | 0.174225E+11 | 0.00 | 0.00 | 13355154.50 | 0.00 | 0.158609E+10 | 0.233727E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.125670E+12 | 0.453700E+11 | 0.00 | 0.283113E+09 | 0.108378E+10 | 0.797318E+10 | 0.406131E+11 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1137604.49 | 0.00 | 0.00 | 47389122.42 | 0.00 | 0.53 |
Maximum of Months | 0.195843E+11 | 0.178388E+11 | 0.00 | 88823467.84 | 0.641786E+09 | 0.485718E+10 | 0.114718E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.570018E+10 | 0.00 | 0.00 | 7182308.33 | 0.00 | 0.112990E+11 | 0.466855E+10 | 0.00 | 0.53 |
February | 0.560315E+10 | 0.00 | 0.00 | 4156331.12 | 0.00 | 0.114633E+11 | 0.356203E+10 | 0.00 | 0.53 |
March | 0.625985E+10 | 0.00 | 0.00 | 26309112.89 | 1301866.23 | 0.380369E+10 | 0.121066E+11 | 0.00 | 0.53 |
April | 0.567924E+10 | 5215795.29 | 0.00 | 65376359.12 | 35630306.57 | 0.182457E+09 | 0.143011E+11 | 0.00 | 0.54 |
May | 0.525006E+10 | 0.144768E+09 | 220293.90 | 0.101492E+09 | 0.200266E+09 | 35982366.19 | 0.114550E+11 | 900.37 | 0.54 |
June | 0.142867E+10 | 0.585362E+10 | 80637.12 | 42374035.72 | 0.366584E+10 | 1686548.64 | 0.183436E+10 | 19675.88 | 0.54 |
July | 28961236.54 | 0.121498E+11 | 0.00 | 897652.65 | 0.592027E+10 | 0.00 | 18943676.77 | 0.00 | 0.54 |
August | 0.485966E+09 | 0.854211E+10 | 10789.78 | 26079013.68 | 0.385415E+10 | 330169.82 | 0.711754E+09 | 10470.93 | 0.54 |
September | 0.290154E+10 | 0.254853E+10 | 2420445.39 | 56243664.93 | 0.250654E+10 | 13756839.63 | 0.477461E+10 | 18657.84 | 0.54 |
October | 0.547904E+10 | 0.323062E+09 | 2661844.82 | 66781033.59 | 0.697084E+09 | 65732112.76 | 0.116960E+11 | 79837.79 | 0.54 |
November | 0.624252E+10 | 0.00 | 0.00 | 32887112.66 | 0.00 | 0.348561E+10 | 0.122106E+11 | 0.00 | 0.54 |
December | 0.592867E+10 | 0.00 | 0.00 | 8138731.83 | 0.00 | 0.912835E+10 | 0.629402E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.509879E+11 | 0.295671E+11 | 5394011.00 | 0.437918E+09 | 0.168811E+11 | 0.394800E+11 | 0.836337E+11 | 129542.81 | 0.54 |
Minimum of Months | 28961236.54 | 0.00 | 0.00 | 897652.65 | 0.00 | 0.00 | 18943676.77 | 0.00 | 0.53 |
Maximum of Months | 0.625985E+10 | 0.121498E+11 | 2661844.82 | 0.101492E+09 | 0.592027E+10 | 0.114633E+11 | 0.143011E+11 | 79837.79 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.344455E+09 | 0.00 | 0.00 | 285485.38 | 0.00 | 0.121022E+10 | 43773351.02 | 0.00 | 0.47 |
February | 0.361065E+09 | 0.00 | 0.00 | 464558.09 | 0.00 | 0.108990E+10 | 70423598.98 | 0.00 | 0.47 |
March | 0.430601E+09 | 0.00 | 0.00 | 2393935.57 | 96024.89 | 0.890777E+09 | 0.313427E+09 | 0.00 | 0.47 |
April | 0.357243E+09 | 2042213.00 | 0.00 | 5848019.27 | 970571.45 | 0.499073E+09 | 0.629856E+09 | 0.00 | 0.47 |
May | 0.295878E+09 | 16500483.05 | 15150.40 | 9528813.82 | 8949055.71 | 0.100933E+09 | 0.835955E+09 | 1164.76 | 0.47 |
June | 93016394.36 | 0.531475E+09 | 265862.05 | 4260334.48 | 0.170405E+09 | 111952.54 | 0.146540E+09 | 11434.28 | 0.48 |
July | 2136163.78 | 0.101193E+10 | 99615.85 | 73625.99 | 0.320809E+09 | 0.00 | 1389858.79 | 1598.42 | 0.48 |
August | 33864150.46 | 0.747211E+09 | 73799.10 | 2762611.56 | 0.167056E+09 | 20317.47 | 53643964.97 | 664.80 | 0.48 |
September | 0.173019E+09 | 0.244621E+09 | 206763.36 | 6429388.18 | 0.128201E+09 | 8776835.07 | 0.383126E+09 | 10527.79 | 0.47 |
October | 0.305066E+09 | 62111568.79 | 44544.29 | 7616086.25 | 13286805.49 | 0.197093E+09 | 0.766820E+09 | 4638.71 | 0.47 |
November | 0.441410E+09 | 0.00 | 0.00 | 1995263.77 | 0.00 | 0.854389E+09 | 0.322823E+09 | 0.00 | 0.47 |
December | 0.380685E+09 | 0.00 | 0.00 | 575972.84 | 0.00 | 0.110472E+10 | 89461701.53 | 0.00 | 0.47 |
Annual Sum or Average | 0.321844E+10 | 0.261589E+10 | 705735.05 | 42234095.21 | 0.809773E+09 | 0.595601E+10 | 0.365724E+10 | 30028.76 | 0.47 |
Minimum of Months | 2136163.78 | 0.00 | 0.00 | 73625.99 | 0.00 | 0.00 | 1389858.79 | 0.00 | 0.47 |
Maximum of Months | 0.441410E+09 | 0.101193E+10 | 265862.05 | 9528813.82 | 0.320809E+09 | 0.121022E+10 | 0.835955E+09 | 11434.28 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249758E+09 | 0.00 | 0.00 | 52925.32 | 0.00 | 0.133554E+10 | 13382062.63 | 0.00 | 0.47 |
February | 0.267173E+09 | 0.00 | 0.00 | 127486.50 | 0.00 | 0.123067E+10 | 23888755.26 | 0.00 | 0.47 |
March | 0.440180E+09 | 0.00 | 0.00 | 1213569.30 | 96024.89 | 0.100316E+10 | 0.192645E+09 | 0.00 | 0.47 |
April | 0.402323E+09 | 1109023.42 | 0.00 | 4587486.94 | 1903761.03 | 0.558803E+09 | 0.526308E+09 | 0.00 | 0.47 |
May | 0.319467E+09 | 16468565.83 | 15374.74 | 8903007.04 | 8980972.93 | 0.113248E+09 | 0.800677E+09 | 940.42 | 0.47 |
June | 93107026.87 | 0.527439E+09 | 331748.35 | 4159954.73 | 0.174373E+09 | 109995.31 | 0.146552E+09 | 12271.34 | 0.48 |
July | 2136163.78 | 0.100952E+10 | 99447.03 | 72594.52 | 0.323216E+09 | 0.00 | 1390890.27 | 1767.24 | 0.48 |
August | 33973201.96 | 0.742508E+09 | 94114.45 | 2517255.48 | 0.171739E+09 | 6212.10 | 53794374.92 | 920.65 | 0.48 |
September | 0.194467E+09 | 0.241321E+09 | 262186.49 | 5030639.15 | 0.131443E+09 | 9279168.30 | 0.362574E+09 | 12447.84 | 0.47 |
October | 0.400496E+09 | 35010454.43 | 265656.20 | 4097491.77 | 40163628.01 | 0.319866E+09 | 0.552135E+09 | 7818.64 | 0.47 |
November | 0.426657E+09 | 0.00 | 0.00 | 701891.41 | 0.00 | 0.101044E+10 | 0.182820E+09 | 0.00 | 0.47 |
December | 0.314766E+09 | 0.00 | 0.00 | 94902.82 | 0.00 | 0.124108E+10 | 19503616.16 | 0.00 | 0.47 |
Annual Sum or Average | 0.314450E+10 | 0.257338E+10 | 1068527.25 | 31559204.97 | 0.851917E+09 | 0.682219E+10 | 0.287567E+10 | 36166.13 | 0.47 |
Minimum of Months | 2136163.78 | 0.00 | 0.00 | 52925.32 | 0.00 | 0.00 | 1390890.27 | 0.00 | 0.47 |
Maximum of Months | 0.440180E+09 | 0.100952E+10 | 331748.35 | 8903007.04 | 0.323216E+09 | 0.133554E+10 | 0.800677E+09 | 12447.84 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.222044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224689E+11 | 0.00 | 0.00 | 0.49 |
February | 0.362228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189488E+11 | 0.00 | 0.00 | 0.49 |
March | 0.108885E+11 | 0.00 | 0.00 | 0.00 | 4207410.01 | 0.127219E+11 | 0.00 | 0.00 | 0.49 |
April | 0.156144E+11 | 0.00 | 0.00 | 0.00 | 27078438.34 | 0.612000E+10 | 0.00 | 0.00 | 0.50 |
May | 0.168213E+11 | 0.00 | 0.00 | 0.00 | 0.389051E+09 | 0.329615E+09 | 0.00 | 0.00 | 0.52 |
June | 0.334815E+10 | 0.00 | 0.00 | 0.00 | 0.927263E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
July | 0.107058E+09 | 0.00 | 0.00 | 0.00 | 0.182766E+11 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.175444E+10 | 0.00 | 0.00 | 0.00 | 0.115822E+11 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.823914E+10 | 0.00 | 0.00 | 0.00 | 0.495427E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.174159E+11 | 0.00 | 0.00 | 0.00 | 0.861880E+09 | 0.885707E+09 | 0.00 | 0.00 | 0.51 |
November | 0.107733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129283E+11 | 0.00 | 0.00 | 0.49 |
December | 0.449354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193095E+11 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.952984E+11 | 0.00 | 0.00 | 0.00 | 0.453679E+11 | 0.937127E+11 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 0.107058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.174159E+11 | 0.00 | 0.00 | 0.00 | 0.182766E+11 | 0.224689E+11 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 70009445.45 | 0.00 | 0.00 | 70632.88 | 0.00 | 0.324183E+09 | 5419814.13 | 0.00 | 0.47 |
February | 75671354.14 | 0.00 | 0.00 | 132276.47 | 0.00 | 0.294337E+09 | 10323474.81 | 0.00 | 0.47 |
March | 97209096.81 | 209.06 | 0.00 | 770727.48 | 23797.17 | 0.237568E+09 | 73752218.73 | 0.00 | 0.47 |
April | 88935713.44 | 416262.92 | 0.00 | 1612121.06 | 336933.20 | 0.144937E+09 | 0.137520E+09 | 0.00 | 0.47 |
May | 77782368.39 | 4018833.62 | 3739.85 | 2618687.83 | 2343551.07 | 31604199.78 | 0.198568E+09 | 338.94 | 0.47 |
June | 24374853.51 | 0.136925E+09 | 32188.19 | 1189408.88 | 38580889.61 | 29353.14 | 35388610.75 | 816.18 | 0.48 |
July | 534040.94 | 0.254267E+09 | 2598.46 | 19053.48 | 78940941.33 | 221.87 | 346595.85 | 111.56 | 0.48 |
August | 8497240.57 | 0.187820E+09 | 14704.04 | 777978.84 | 40749806.73 | 6701.95 | 13290839.76 | 555.87 | 0.48 |
September | 45834876.44 | 62672876.66 | 55919.35 | 1618992.78 | 30529506.36 | 3122214.07 | 92261732.54 | 1570.58 | 0.47 |
October | 76883885.43 | 15186143.18 | 12327.60 | 2035156.14 | 3662245.27 | 59752955.03 | 0.180477E+09 | 1173.26 | 0.47 |
November | 0.104165E+09 | 0.00 | 0.00 | 322299.91 | 0.00 | 0.241969E+09 | 58697989.23 | 0.00 | 0.47 |
December | 83138610.82 | 0.00 | 0.00 | 81807.91 | 0.00 | 0.301987E+09 | 8652362.89 | 0.00 | 0.47 |
Annual Sum or Average | 0.753037E+09 | 0.661307E+09 | 121477.50 | 11249143.66 | 0.195168E+09 | 0.163950E+10 | 0.814699E+09 | 4566.40 | 0.47 |
Minimum of Months | 534040.94 | 0.00 | 0.00 | 19053.48 | 0.00 | 221.87 | 346595.85 | 0.00 | 0.47 |
Maximum of Months | 0.104165E+09 | 0.254267E+09 | 55919.35 | 2618687.83 | 78940941.33 | 0.324183E+09 | 0.198568E+09 | 1570.58 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 41504884.67 | 0.00 | 0.00 | 7592.82 | 0.00 | 0.357316E+09 | 854196.40 | 0.00 | 0.47 |
February | 50224647.80 | 0.00 | 0.00 | 16813.18 | 0.00 | 0.326368E+09 | 3854435.69 | 0.00 | 0.47 |
March | 0.101773E+09 | 0.00 | 0.00 | 378985.21 | 24006.22 | 0.266551E+09 | 40597080.40 | 0.00 | 0.47 |
April | 95692628.99 | 260389.85 | 0.00 | 1262943.62 | 492806.26 | 0.155401E+09 | 0.120649E+09 | 0.00 | 0.47 |
May | 82062047.87 | 4014251.94 | 3774.08 | 2474728.01 | 2348132.75 | 33923814.04 | 0.192113E+09 | 304.71 | 0.47 |
June | 24502216.98 | 0.136396E+09 | 45765.96 | 1167008.33 | 39096761.37 | 39855.51 | 35273145.47 | 830.32 | 0.48 |
July | 534040.94 | 0.253799E+09 | 10286.72 | 18796.69 | 79401156.28 | 221.87 | 346852.64 | 174.98 | 0.48 |
August | 8524458.92 | 0.186794E+09 | 19514.95 | 713396.34 | 41770262.08 | 3776.25 | 13331129.60 | 1814.13 | 0.48 |
September | 49866624.57 | 61215533.13 | 53768.87 | 1246449.80 | 31989121.44 | 3449112.81 | 88275628.63 | 1449.52 | 0.47 |
October | 96188524.12 | 11111051.65 | 11395.62 | 1146977.78 | 7738208.06 | 90878236.95 | 0.130935E+09 | 1233.99 | 0.47 |
November | 93869299.21 | 0.00 | 0.00 | 87294.31 | 0.00 | 0.290064E+09 | 21133567.64 | 0.00 | 0.47 |
December | 58432325.89 | 0.00 | 0.00 | 5222.66 | 0.00 | 0.335135E+09 | 287290.24 | 0.00 | 0.47 |
Annual Sum or Average | 0.703174E+09 | 0.653590E+09 | 144506.19 | 8526208.76 | 0.202860E+09 | 0.185913E+10 | 0.647650E+09 | 5807.65 | 0.47 |
Minimum of Months | 534040.94 | 0.00 | 0.00 | 5222.66 | 0.00 | 221.87 | 287290.24 | 0.00 | 0.47 |
Maximum of Months | 0.101773E+09 | 0.253799E+09 | 53768.87 | 2474728.01 | 79401156.28 | 0.357316E+09 | 0.192113E+09 | 1814.13 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.489211E+09 | 0.00 | 0.00 | 3696673.12 | 0.00 | 0.160054E+10 | 0.473318E+09 | 0.00 | 0.53 |
February | 0.427285E+09 | 0.00 | 0.00 | 4535752.28 | 0.00 | 0.133620E+10 | 0.675327E+09 | 0.00 | 0.54 |
March | 0.502518E+09 | 154168.37 | 0.00 | 8255646.03 | 0.00 | 0.101741E+10 | 0.110035E+10 | 0.00 | 0.53 |
April | 0.530585E+09 | 3548258.12 | 0.00 | 9958063.73 | 1288780.26 | 0.560127E+09 | 0.129478E+10 | 0.00 | 0.54 |
May | 0.501388E+09 | 25683243.47 | 24451.07 | 13322867.46 | 15176100.32 | 45868156.46 | 0.143393E+10 | 1742.99 | 0.54 |
June | 0.157649E+09 | 0.854388E+09 | 87413.76 | 5610033.37 | 0.272835E+09 | 305888.37 | 0.228064E+09 | 5340.60 | 0.54 |
July | 3429620.12 | 0.161539E+10 | 44975.35 | 116866.51 | 0.524452E+09 | 0.00 | 2232764.61 | 6.29 | 0.54 |
August | 54534077.60 | 0.119818E+10 | 501.16 | 4408748.60 | 0.269796E+09 | 2461.36 | 86017372.12 | 1550.16 | 0.54 |
September | 0.281146E+09 | 0.400319E+09 | 228077.89 | 12253204.67 | 0.198368E+09 | 1770285.28 | 0.622137E+09 | 1782.82 | 0.54 |
October | 0.370786E+09 | 0.101838E+09 | 48046.54 | 21746801.46 | 19244181.18 | 78331341.91 | 0.157871E+10 | 1035.56 | 0.54 |
November | 0.531595E+09 | 0.00 | 0.00 | 9260211.93 | 0.00 | 0.866682E+09 | 0.119437E+10 | 0.00 | 0.54 |
December | 0.464112E+09 | 0.00 | 0.00 | 6337748.92 | 0.00 | 0.135337E+10 | 0.705559E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.431424E+10 | 0.419950E+10 | 433465.76 | 99502618.07 | 0.130116E+10 | 0.686060E+10 | 0.939480E+10 | 11458.41 | 0.54 |
Minimum of Months | 3429620.12 | 0.00 | 0.00 | 116866.51 | 0.00 | 0.00 | 2232764.61 | 0.00 | 0.53 |
Maximum of Months | 0.531595E+09 | 0.161539E+10 | 228077.89 | 21746801.46 | 0.524452E+09 | 0.160054E+10 | 0.157871E+10 | 5340.60 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114706E+11 | 0.00 | 0.00 | 37248303.18 | 0.00 | 0.00 | 0.329782E+11 | 0.00 | 4.17 |
February | 0.990562E+10 | 0.00 | 0.00 | 30991867.48 | 0.00 | 0.00 | 0.303975E+11 | 0.00 | 4.17 |
March | 0.512445E+10 | 7319398.21 | 0.00 | 53703578.21 | 0.00 | 0.00 | 0.389583E+11 | 0.00 | 4.28 |
April | 0.242304E+10 | 43749732.45 | 0.00 | 67925290.90 | 3357127.30 | 0.00 | 0.393291E+11 | 0.00 | 4.45 |
May | 0.735044E+09 | 0.636369E+09 | 0.00 | 66574549.97 | 44536912.75 | 0.00 | 0.321307E+11 | 0.00 | 4.57 |
June | 0.100691E+09 | 0.156066E+11 | 0.00 | 24545740.00 | 0.948287E+09 | 0.00 | 0.613232E+10 | 0.00 | 4.40 |
July | 1332722.40 | 0.317773E+11 | 0.00 | 1265708.63 | 0.116439E+10 | 0.00 | 0.190271E+09 | 0.00 | 4.33 |
August | 40156319.44 | 0.200726E+11 | 0.00 | 16871033.59 | 0.915751E+09 | 0.00 | 0.315905E+10 | 0.00 | 4.38 |
September | 0.556049E+09 | 0.791706E+10 | 0.00 | 39021054.89 | 0.860738E+09 | 0.00 | 0.147221E+11 | 0.00 | 4.42 |
October | 0.161919E+10 | 0.125671E+10 | 0.00 | 65093869.10 | 0.247517E+09 | 0.00 | 0.331899E+11 | 0.00 | 4.46 |
November | 0.582926E+10 | 0.00 | 0.00 | 56005649.95 | 0.00 | 0.00 | 0.384940E+11 | 0.00 | 4.32 |
December | 0.882696E+10 | 0.00 | 0.00 | 40589236.46 | 0.00 | 0.00 | 0.342154E+11 | 0.00 | 4.21 |
Annual Sum or Average | 0.466324E+11 | 0.773177E+11 | 0.00 | 0.499836E+09 | 0.418458E+10 | 0.00 | 0.303897E+12 | 0.00 | 4.35 |
Minimum of Months | 1332722.40 | 0.00 | 0.00 | 1265708.63 | 0.00 | 0.00 | 0.190271E+09 | 0.00 | 4.17 |
Maximum of Months | 0.114706E+11 | 0.317773E+11 | 0.00 | 67925290.90 | 0.116439E+10 | 0.00 | 0.393291E+11 | 0.00 | 4.57 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.641522E+10 | 0.00 | 0.00 | 51699060.92 | 0.00 | 0.00 | 0.415683E+11 | 0.00 | 4.49 |
February | 0.603575E+10 | 0.00 | 0.00 | 42991607.64 | 0.00 | 0.00 | 0.373804E+11 | 0.00 | 4.49 |
March | 0.175655E+10 | 7679819.36 | 0.00 | 71428057.67 | 0.00 | 0.00 | 0.463977E+11 | 0.00 | 4.67 |
April | 0.682578E+09 | 48922244.57 | 0.00 | 88948606.61 | 526942.23 | 0.00 | 0.449876E+11 | 0.00 | 4.85 |
May | 0.291734E+09 | 0.684364E+09 | 0.00 | 83549848.21 | 33489077.81 | 0.00 | 0.355430E+11 | 0.00 | 4.94 |
June | 57161185.04 | 0.170936E+11 | 0.00 | 29287178.82 | 0.579765E+09 | 0.00 | 0.670742E+10 | 0.00 | 4.72 |
July | 1398348.19 | 0.343728E+11 | 0.00 | 1409772.58 | 0.745530E+09 | 0.00 | 0.202715E+09 | 0.00 | 4.62 |
August | 24513891.02 | 0.218033E+11 | 0.00 | 19274097.22 | 0.528773E+09 | 0.00 | 0.341804E+10 | 0.00 | 4.67 |
September | 0.315885E+09 | 0.900518E+10 | 0.00 | 48192146.65 | 0.326273E+09 | 0.00 | 0.162659E+11 | 0.00 | 4.74 |
October | 0.602595E+09 | 0.138441E+10 | 0.00 | 81709031.16 | 0.201911E+09 | 0.00 | 0.373665E+11 | 0.00 | 4.83 |
November | 0.191215E+10 | 0.00 | 0.00 | 75743980.97 | 0.00 | 0.00 | 0.463938E+11 | 0.00 | 4.69 |
December | 0.280011E+10 | 0.00 | 0.00 | 56469526.32 | 0.00 | 0.00 | 0.440078E+11 | 0.00 | 4.57 |
Annual Sum or Average | 0.208956E+11 | 0.844003E+11 | 0.00 | 0.650703E+09 | 0.241627E+10 | 0.00 | 0.360239E+12 | 0.00 | 4.69 |
Minimum of Months | 1398348.19 | 0.00 | 0.00 | 1409772.58 | 0.00 | 0.00 | 0.202715E+09 | 0.00 | 4.49 |
Maximum of Months | 0.641522E+10 | 0.343728E+11 | 0.00 | 88948606.61 | 0.745530E+09 | 0.00 | 0.463977E+11 | 0.00 | 4.94 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25266389.44 | 0.00 | 0.00 | 0.125569E+09 | 0.00 | 0.00 | 0.650328E+11 | 0.00 | 19.69 |
February | 18963745.08 | 0.00 | 0.00 | 0.103624E+09 | 0.00 | 0.00 | 0.596062E+11 | 0.00 | 19.88 |
March | 6209891.42 | 10097298.66 | 0.00 | 0.138932E+09 | 0.00 | 0.00 | 0.634837E+11 | 0.00 | 20.06 |
April | 28067293.97 | 73760700.89 | 0.00 | 0.154875E+09 | 0.00 | 0.00 | 0.574202E+11 | 0.00 | 20.18 |
May | 18048865.29 | 0.106096E+10 | 0.00 | 0.123658E+09 | 0.00 | 0.00 | 0.426698E+11 | 0.00 | 20.16 |
June | 156184.58 | 0.224668E+11 | 0.00 | 39390007.49 | 5449298.21 | 0.00 | 0.764160E+10 | 0.00 | 18.95 |
July | 0.00 | 0.444176E+11 | 0.00 | 1965150.72 | 3767084.35 | 0.00 | 0.221955E+09 | 0.00 | 18.62 |
August | 0.00 | 0.290429E+11 | 0.00 | 23376728.20 | 3973493.18 | 0.00 | 0.365871E+10 | 0.00 | 18.87 |
September | 22906093.44 | 0.118314E+11 | 0.00 | 78442622.92 | 4656699.28 | 0.00 | 0.195230E+11 | 0.00 | 19.21 |
October | 17795022.94 | 0.223748E+10 | 0.00 | 0.134886E+09 | 389752.86 | 0.00 | 0.469335E+11 | 0.00 | 19.91 |
November | 50399399.31 | 0.00 | 0.00 | 0.148745E+09 | 0.00 | 0.00 | 0.630367E+11 | 0.00 | 20.00 |
December | 5363098.40 | 0.00 | 0.00 | 0.127041E+09 | 0.00 | 0.00 | 0.632046E+11 | 0.00 | 19.98 |
Annual Sum or Average | 0.193176E+09 | 0.111141E+12 | 0.00 | 0.120050E+10 | 18236327.88 | 0.00 | 0.492433E+12 | 0.00 | 19.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1965150.72 | 0.00 | 0.00 | 0.221955E+09 | 0.00 | 18.62 |
Maximum of Months | 50399399.31 | 0.444176E+11 | 0.00 | 0.154875E+09 | 5449298.21 | 0.00 | 0.650328E+11 | 0.00 | 20.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:44:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.472635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802574E+10 | 0.00 | 0.00 | 0.96 |
February | 0.438781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727018E+10 | 0.00 | 0.00 | 0.96 |
March | 0.998933E+10 | 0.00 | 0.00 | 0.00 | 2173135.39 | 0.220546E+10 | 0.00 | 0.00 | 0.95 |
April | 0.108180E+11 | 0.00 | 0.00 | 0.00 | 13986065.68 | 0.407791E+09 | 0.00 | 0.00 | 0.97 |
May | 0.885849E+10 | 0.00 | 0.00 | 0.00 | 0.200946E+09 | 0.00 | 0.00 | 0.00 | 1.01 |
June | 0.172933E+10 | 0.00 | 0.00 | 0.00 | 0.478933E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
July | 55295444.83 | 0.00 | 0.00 | 0.00 | 0.943988E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
August | 0.906171E+09 | 0.00 | 0.00 | 0.00 | 0.598222E+10 | 0.00 | 0.00 | 0.00 | 1.00 |
September | 0.425553E+10 | 0.00 | 0.00 | 0.00 | 0.255889E+10 | 0.00 | 0.00 | 0.00 | 1.01 |
October | 0.938385E+10 | 0.00 | 0.00 | 0.00 | 0.445163E+09 | 68965604.00 | 0.00 | 0.00 | 0.99 |
November | 0.999654E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224538E+10 | 0.00 | 0.00 | 0.96 |
December | 0.617696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611733E+10 | 0.00 | 0.00 | 0.96 |
Annual Sum or Average | 0.712837E+11 | 0.00 | 0.00 | 0.00 | 0.234326E+11 | 0.263409E+11 | 0.00 | 0.00 | 0.98 |
Minimum of Months | 55295444.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
Maximum of Months | 0.108180E+11 | 0.00 | 0.00 | 0.00 | 0.943988E+10 | 0.802574E+10 | 0.00 | 0.00 | 1.01 |