Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:43
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2020-06-03 19:43:11
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 10126.21 | 892.55 | 892.55 |
Net Site Energy | 10126.21 | 892.55 | 892.55 |
Total Source Energy | 22134.09 | 1950.95 | 1950.95 |
Net Source Energy | 22134.09 | 1950.95 | 1950.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 942.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1008.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 827.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 182.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.19 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 972.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 504.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.75 | 2038.31 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 62.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5356.35 | 4769.86 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 942.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1008.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 827.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 182.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 504.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 49.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.75 | 2038.31 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 34.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 145.71 | 262.75 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 237.32 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 472.12 | 420.43 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 89.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 145.71 | 262.75 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 237.32 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 472.12 | 420.43 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5356.349 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5356.349 | 100.00 |
Total On-Site and Utility Electric Sources | 5356.349 | 100.00 |
Total Electricity End Uses | 5356.349 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 108.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7259.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:43 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.5035 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 11.4097 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.4097 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.9514 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 7.6424 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 11.4097 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 7.6424 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 7.6424 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 7.1042 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 8.4749 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 8.4749 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-SEP-19:10 | 06-JAN-18:30 | - | - | - | 07-JUL-20:40 |
Heating | 0.00 | 130876.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 110342.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 75078.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 104248.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50290.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22422.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1784.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3709.26 | 174291.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 1831.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 363531.40 | 409416.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 130876.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 110342.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 75078.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 29272.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1251.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22422.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1784.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3709.26 | 174291.78 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 530.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1059.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1021.88 | 0.00 | 0.00 | 0.00 |
Cooling | 3194.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2621.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 579.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.48 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3079.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1598.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 155.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.42 | 2209.53 | 0.00 | 0.00 | 0.00 |
Refrigeration | 196.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16963.56 | 5170.53 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 90.07 | 0.00 | 0.00 | 0.00 |
Cooling | 281.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 194.75 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1495.21 | 455.74 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 90.07 | 0.00 | 0.00 | 0.00 |
Cooling | 281.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 231.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 51.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 13.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.33 | 194.75 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1495.21 | 455.74 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.38 | 0.634229 | 0.573000 | 1.36 | 1.00 | 0.500000 | 0.000601 | 0.000156 | 1.36 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.289257 | 0.176689 | 0.573000 | 0.165744 | 0.573000 | 0.500000 | 0.002156 | 0.000061 | 0.165744 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.223887 | 0.264346 | 0.573000 | 0.128287 | 0.704923 | 0.500000 | 0.001441 | 0.000027 | 0.128287 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.221688 | 0.564547 | 0.573000 | 0.127027 | 1.00 | 0.500000 | 0.000675 | 0.000036 | 0.127027 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.093870 | 0.769222 | 0.573000 | 0.053787 | 1.00 | 0.500000 | 0.000495 | 0.000021 | 0.053787 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.30 | 0.017998 | 0.573000 | 1.89 | 0.573000 | 0.500000 | 0.021169 | 0.000245 | 1.89 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.22 | 0.117556 | 0.573000 | 0.701469 | 0.573000 | 0.500000 | 0.003241 | 0.000190 | 0.701469 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.52 | 0.220366 | 0.573000 | 2.59 | 0.587642 | 0.500000 | 0.001729 | 0.000535 | 2.59 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.573000 | 0.680097 | 1.00 | 0.500000 | 0.000381 | 0.000203 | 0.680097 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.01 | 0.125883 | 0.573000 | 1.15 | 0.573000 | 0.500000 | 0.003027 | 0.000215 | 1.15 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.11 | 0.119921 | 0.573000 | 1.21 | 0.573000 | 0.500000 | 0.003177 | 0.000221 | 1.21 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.22 | 0.700000 | 0.573000 | 1.27 | 0.573000 | 0.500000 | 0.010739 | 0.000146 | 1.27 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.559207 | 0.561579 | 0.573000 | 0.320426 | 1.00 | 0.500000 | 0.000678 | 0.000125 | 0.320426 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 7059.17 | 0.000156 | 124.92 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2781.19 | 0.000061 | 55.14 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1222.99 | 0.000027 | 22.72 |
MECH_FLR_1 VAV BOX REHEAT COIL | 1637.22 | 0.000036 | 31.63 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 941.38 | 0.000021 | 18.76 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11090.90 | 0.000245 | 197.70 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 8604.15 | 0.000190 | 164.99 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 24195.86 | 0.000535 | 448.39 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 3698.56 | 0.000082 | 84.20 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 3699.05 | 0.000082 | 84.21 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 21431.07 | 0.000473 | 487.89 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 21477.06 | 0.000475 | 488.93 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 3697.76 | 0.000082 | 84.18 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 3698.25 | 0.000082 | 84.19 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 9195.48 | 0.000203 | 178.65 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 1145.28 | 0.000025 | 26.07 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 1147.18 | 0.000025 | 26.12 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 5545.71 | 0.000123 | 126.25 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 9716.11 | 0.000215 | 178.25 |
DINING_FLR_6 VAV BOX REHEAT COIL | 10018.32 | 0.000221 | 183.48 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6587.86 | 0.000146 | 116.58 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5658.35 | 0.000125 | 112.86 |
VAV WITH REHEAT_HEATC | 91852.51 | 0.002029 | 1446.41 |
FLR_3_DOAS_HEATC | 9426.70 | 0.000208 | 148.44 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 0.949887 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 0.928748 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.59 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 5.71 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 0.827167 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 0.819391 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.245698 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.240273 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.08 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 0.949887 | 0.000082 | 0.000297 |
ROOM_2_FLR_3 FAN COIL | 0.928748 | 0.000082 | 0.000291 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.59 | 0.000473 | 0.001714 |
ROOM_4_MULT19_FLR_3 FAN COIL | 5.71 | 0.000475 | 0.001871 |
ROOM_5_FLR_3 FAN COIL | 0.827167 | 0.000082 | 0.000260 |
ROOM_6_FLR_3 FAN COIL | 0.819391 | 0.000082 | 0.000257 |
ROOM_1_FLR_6 FAN COIL | 0.245698 | 0.000025 | 0.000077 |
ROOM_2_FLR_6 FAN COIL | 0.240273 | 0.000025 | 0.000075 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.08 | 0.000123 | 0.000344 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 0.949887 |
ROOM_2_FLR_3 FAN COILFAN | 0.928748 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.59 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 5.71 |
ROOM_5_FLR_3 FAN COILFAN | 0.827167 |
ROOM_6_FLR_3 FAN COILFAN | 0.819391 |
ROOM_1_FLR_6 FAN COILFAN | 0.245698 |
ROOM_2_FLR_6 FAN COILFAN | 0.240273 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.08 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000297 | 0.949887 | 0.008571 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000291 | 0.928748 | 0.008572 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.001714 | 5.59 | 0.008494 | 21.69 | 6.70 | 12.80 | 0.008494 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.001871 | 5.71 | 0.008740 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000260 | 0.827167 | 0.008581 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000257 | 0.819391 | 0.008582 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000077 | 0.245698 | 0.008569 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000075 | 0.240273 | 0.008570 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000344 | 1.08 | 0.008647 | 21.69 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.012471 | 0.008810 | 28.26 | 6.70 | 10.94 | 0.008436 | 436047.35 | 19.99 | |
FLR_3_DOAS_COOLC | 0.001371 | 0.008202 | 31.30 | 6.70 | 10.94 | 0.008202 | 47940.88 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.65 | 11.65 | 20.34 | 11.65 | 19.99 | 19.99 | 0.300000 | 0.583068 | 19.99 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 19.99 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 19.99 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.012471 | 0.000038 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.002029 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.001371 | 0.000347 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000208 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.019028 | 3639.83 |
HEATSYS1 PUMP | 0.005867 | 1498.82 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.005867 | 0.703982 |
COOLSYS1 | 0.019028 | 2.28 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.019028 | 1213.28 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 265528.14 | 265528.14 | 0.005867 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.019028 | 665319.96 | 665894.47 | 75.91 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.503 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.883 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.410 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.170 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.410 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.170 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 10.226 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.606 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.951 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 7.641 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.642 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.022 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 11.410 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.480 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.642 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.462 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.642 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.462 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 16826.961 | 8.503 | 158.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16826.961 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 765.267 | 11.410 | 70.668 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 765.267 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 886.182 | 11.410 | 70.668 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 886.182 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1679.504 | 10.226 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1679.504 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 469.191 | 4.951 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 469.191 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1443.354 | 7.642 | 10.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1443.354 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 14926.070 | 11.410 | 35.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14926.070 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.423 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.423 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.385 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.385 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.423 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.423 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.385 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.385 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2766.401 | 7.104 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.401 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.423 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.423 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.385 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.385 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2534.651 | 7.642 | 10.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2534.651 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2534.651 | 7.642 | 10.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2534.651 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.678 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.678 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2927.809 | 7.104 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.809 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.7800 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.2277 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.115 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.131 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
21 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
22 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
23 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
24 | 9 | -0.41768822E-14 | 0.27520919E-16 | -0.15672466E-09 | 0.83927561E-16 |
25 | 8 | 0.22856702E-07 | 0.10578700E-12 | 0.38803401E-03 | -0.25988854E-09 |
26 | 7 | -0.12546900E-01 | 0.54357740E-08 | -0.23525379E-01 | 0.14266284E-03 |
27 | 6 | 0.41364683 | 0.18861797E-05 | 0.47915075 | -0.48455579E-02 |
28 | 5 | -5.2715232 | 0.70271773E-04 | -4.4954566 | 0.64187715E-01 |
29 | 4 | 33.360936 | 0.57369956E-03 | 21.652120 | -0.42687724 |
30 | 3 | -111.98802 | 0.12481219E-02 | -56.042688 | 1.5262008 |
31 | 2 | 197.88617 | 0.70096321E-03 | 78.258916 | -2.9127067 |
32 | 1 | -171.44340 | 0.74721452E-04 | -55.366563 | 2.7504751 |
33 | 0 | 57.057407 | 0.42462867E-06 | 15.540328 | |
34 | 7 | -0.14139450E-14 | -0.18802902E-16 | -0.22311785E-13 | 0.54375338E-15 |
35 | 6 | 0.16999971E-10 | 0.27590984E-11 | 0.52267399E-09 | -0.18616555E-10 |
36 | 5 | -0.63950587E-07 | 0.13451749E-07 | -0.21905428E-05 | 0.17144787E-06 |
37 | 4 | 0.72477507E-04 | 0.50724086E-05 | 0.17668371E-02 | -0.28223350E-03 |
38 | 3 | -0.10573811E-01 | 0.17927531E-03 | -0.21549182 | 0.43318087E-01 |
39 | 2 | 0.15010112 | 0.77388015E-03 | 2.8998331 | -0.61891034 |
40 | 1 | -0.37982851 | 0.49528818E-03 | -7.1368477 | 1.5694772 |
41 | 0 | 0.24168561 | 0.34021171E-05 | 4.4521969 | |
42 | 7 | -0.22311785E-13 | -0.18802902E-16 | -0.14139450E-14 | 0.54375338E-15 |
43 | 6 | 0.52267399E-09 | 0.27590984E-11 | 0.16999971E-10 | -0.18616555E-10 |
44 | 5 | -0.21905428E-05 | 0.13451749E-07 | -0.63950587E-07 | 0.17144787E-06 |
45 | 4 | 0.17668371E-02 | 0.50724086E-05 | 0.72477507E-04 | -0.28223350E-03 |
46 | 3 | -0.21549182 | 0.17927531E-03 | -0.10573811E-01 | 0.43318087E-01 |
47 | 2 | 2.8998331 | 0.77388015E-03 | 0.15010112 | -0.61891034 |
48 | 1 | -7.1368477 | 0.49528818E-03 | -0.37982851 | 1.5694772 |
49 | 0 | 4.4521969 | 0.34021171E-05 | 0.24168561 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
59 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
60 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
61 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
62 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
63 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
64 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
65 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
66 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
67 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
68 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
69 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
70 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
71 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
72 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
73 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
74 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
75 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
76 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
77 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
78 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
79 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
80 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
81 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
82 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
83 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
84 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
85 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
86 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
87 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
88 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
89 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.45_SHGC_0.25 | 31 | 1 | VerySmooth | 2.557 | 0.252 | 0.162 | 0.276 |
2 | RESWINDOW_U_0.49_SHGC_0.25 | 32 | 1 | VerySmooth | 2.786 | 0.252 | 0.162 | 0.276 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.12702E-002 | 0.16139 | 0.61239 | 0.61239 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.11281 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 32113.39779 | 32113.39779 | 2.37748 | 2.37748 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 20:30:00 | 26.44950 | 8.20219E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 0.85413 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 | |
3 | RETAIL_1_FLR_1 | Cooling | 3906.78037 | 3906.78037 | 0.28926 | 0.28926 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.20219E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 1923.36035 | 1923.36035 | 8.39998E-002 | 8.39998E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3023.78846 | 3023.78846 | 0.22389 | 0.22389 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05400 | 8.20219E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 558.78153 | 558.78153 | 2.44046E-002 | 9.16993E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2994.81401 | 2994.81401 | 0.22169 | 0.22169 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 29.46067 | 8.20219E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 979.64568 | 979.64568 | 4.27857E-002 | 4.27857E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1268.09781 | 1268.09781 | 9.38696E-002 | 9.38696E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30000 | 8.20219E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 662.94712 | 662.94712 | 2.89540E-002 | 5.77430E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44628.72900 | 44628.72900 | 3.30398 | 3.30398 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30000 | 8.20219E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 1291.52459 | 1291.52459 | 5.64062E-002 | 5.64062E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 16520.66851 | 16520.66851 | 1.22420 | 1.22420 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.92917 | 8.20219E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 4973.47473 | 4973.47473 | 0.21721 | 0.67613 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 61077.96990 | 61077.96990 | 4.52356 | 4.52356 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.20219E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 10778.01164 | 10778.01164 | 0.47072 | 1.89326 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 9521.73737 | 9521.73737 | 0.94989 | 0.94989 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 3698.56729 | 3698.56729 | 0.16248 | 0.16248 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 9309.84131 | 9309.84131 | 0.92875 | 0.92875 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 3699.05842 | 3699.05842 | 0.16250 | 0.16250 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 56014.50797 | 56014.50797 | 5.58775 | 5.58775 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.20219E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 21431.08667 | 21431.08667 | 0.94149 | 0.94149 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 57272.39276 | 57272.39276 | 5.71368 | 5.71368 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30000 | 8.20219E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 21477.07681 | 21477.07681 | 0.94351 | 0.94351 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 8291.58766 | 8291.58766 | 0.82717 | 0.82717 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.65717 | 8.20219E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 3697.76523 | 3697.76523 | 0.16245 | 0.16245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 8213.63597 | 8213.63597 | 0.81939 | 0.81939 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.20219E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 3698.25679 | 3698.25679 | 0.16247 | 0.16247 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 12784.24315 | 12784.24315 | 0.94634 | 1.18691 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.20219E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 5673.36034 | 5673.36034 | 0.24778 | 0.47458 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2462.89815 | 2462.89815 | 0.24570 | 0.24570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 1145.28483 | 1145.28483 | 5.03131E-002 | 5.03131E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2408.51776 | 2408.51776 | 0.24027 | 0.24027 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.20219E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 1147.17758 | 1147.17758 | 5.03962E-002 | 5.03962E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 10800.64224 | 10800.64224 | 1.07750 | 1.07750 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.20219E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 5545.71351 | 5545.71351 | 0.24363 | 0.24363 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80000 | 5.05843E-003 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27083.79703 | 27083.79703 | 2.00760 | 2.00760 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.20219E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 3758.04679 | 3758.04679 | 0.16413 | 1.18734 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 28430.82936 | 28430.82936 | 2.10741 | 2.10741 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.20219E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 3764.02793 | 3764.02793 | 0.16439 | 1.18734 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 3.80000 | 5.05843E-003 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 29891.50259 | 29891.50259 | 2.21875 | 2.21875 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.49900 | 8.20219E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.36721 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80000 | 5.05843E-003 | 103.30446 | 22.23800 | 0.36721 | 0.00000 | |
43 | CORRIDOR_FLR_6 | Cooling | 7554.41028 | 7554.41028 | 0.55921 | 0.55921 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.22583 | 8.20219E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 3998.61557 | 3998.61557 | 0.17464 | 0.17464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 3.80000 | 5.05843E-003 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 366618.97 | 19.98660 | 19.98660 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 109484.82 | 7.14699 | 7.14699 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 45063.05 | 15.58461 | 2.05120 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 31422.35 | 2.87924 | 2.05120 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.37748 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.63423 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.36230 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.00729E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55964E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.36230 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7059.17427 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55964E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 124.91545 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.28926 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17669 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16574 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57300 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15633E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.14471E-005 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.16574 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2781.19258 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.14471E-005 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 55.14157 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22389 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26435 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12829 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70492 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44129E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.70205E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12829 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1222.99251 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.70205E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 22.71587 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22169 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56455 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12703 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.74877E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.61724E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12703 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1637.22163 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61724E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 31.62990 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.38696E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.76922 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.37873E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.95305E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07986E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.37873E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 941.37766 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07986E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 18.75565 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.30398 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.79983E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89318 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57300 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.11687E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.45040E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89318 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11090.90268 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45040E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 197.70477 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22420 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11756 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.70147 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57300 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24100E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.90098E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70147 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8604.14590 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.90098E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 164.98897 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.52356 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22037 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59200 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58764 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72894E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.34578E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.59200 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24195.86216 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.34578E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 448.39243 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94989 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.94989 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.94989 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.17152E-005 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.97203E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.97203E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.94989 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.57079E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 3698.56253 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.17152E-005 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.19985 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.92875 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.92875 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.92875 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.17261E-005 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.90714E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.90714E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.92875 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.57234E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 3699.05366 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.17261E-005 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.21103 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.58775 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.58775 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.58775 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.73493E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.71441E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.71441E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.58775 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.49401E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69438 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.49401E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 21431.07264 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.73493E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 487.88658 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.71368 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.71368 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.71368 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 4.74509E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.87086E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.87086E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.71368 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.74041E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69348 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 21477.06276 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.74509E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 488.93346 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.82717 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.82717 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.82717 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.16975E-005 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.59542E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.59542E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.82717 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.58115E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 3697.76047 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.16975E-005 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.18159 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.81939 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.81939 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.81939 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 8.17084E-005 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.57153E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.57153E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.81939 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.58186E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69393 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 3698.25203 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.17084E-005 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 84.19278 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.68010 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03163E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68010 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9195.47584 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03163E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.65204 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24570 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24570 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24570 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53036E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.68272E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 7.68272E-005 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.24570 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.56853E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1145.28345 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53036E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 26.07239 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.24027 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.24027 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.24027 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.53455E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 7.51615E-005 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 7.51615E-005 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.24027 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.57002E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69395 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 1147.17619 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53455E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 26.11548 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07750 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.07750 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.07750 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.22526E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.44194E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.44194E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.07750 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.64723E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.69364 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 5545.70823 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.22526E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 126.24760 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00760 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12588 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15035 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57300 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02661E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14666E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15035 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9716.11379 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14666E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 178.24537 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10741 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11992 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20755 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57300 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17709E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21343E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20755 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10018.31923 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21343E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 183.47881 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21875 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.27134 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57300 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07389E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45551E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.27134 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6587.86292 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45551E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 116.57537 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55921 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.56158 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57300 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32043 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.78444E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25014E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32043 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5658.34919 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25014E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 112.85643 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.65356 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.65356 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 20.33780 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.65356 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 19.98660 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 19.98660 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.58307 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 19.98660 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 19.98660 |
346 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 436047.34902 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.24709E-002 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 19.98660 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.80970E-003 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 28.25532 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.94340 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.43576E-003 |
354 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 91852.50895 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.02937E-003 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 1446.41341 |
357 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 19.98660 |
358 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.24709E-002 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.81841E-005 |
360 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.02937E-003 |
361 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 47940.87599 |
364 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.37110E-003 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.20219E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 31.30000 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.94135 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.20219E-003 |
371 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 9426.70388 |
372 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.08272E-004 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 148.44353 |
374 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
375 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.37110E-003 |
376 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 3.47305E-004 |
377 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.08272E-004 |
378 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 1.90281E-002 |
379 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 3639.83140 |
380 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
381 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
382 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
383 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
384 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
385 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.86652E-003 |
386 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.70398 |
387 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.86652E-003 |
388 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1498.82055 |
389 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 265528.13515 |
390 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 265528.14000 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.86652E-003 |
392 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 1.90281E-002 |
393 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 2.28337 |
394 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 1.90281E-002 |
395 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 1213.27713 |
396 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 1.90281E-002 |
397 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 665319.95817 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 665894.47000 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 75.91197 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 7099.75 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 2798.78 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1229.70 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 1645.71 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 947.29 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 11154.16 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 8649.11 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 24328.90 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 3990.93 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 3991.46 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 23125.11 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 23174.74 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 3990.07 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 3990.60 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 9255.83 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 1235.80 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 1237.84 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 5983.98 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 9770.01 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 10073.97 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 6625.73 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 5693.86 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 77201.27 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 7923.07 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 15498.30 | 13347.18 | 2151.12 | 0.86 | 3143.61 | 31.88 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 15157.82 | 13051.65 | 2106.17 | 0.86 | 3073.16 | 31.17 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 89989.43 | 78134.85 | 11854.58 | 0.87 | 18700.20 | 189.67 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 96161.36 | 81306.23 | 14855.13 | 0.85 | 18677.61 | 189.44 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 13522.17 | 11631.67 | 1890.50 | 0.86 | 2734.56 | 27.74 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 13396.83 | 11522.92 | 1873.91 | 0.86 | 2708.65 | 27.47 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 4007.10 | 3451.82 | 555.29 | 0.86 | 813.32 | 8.25 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 3919.72 | 3375.97 | 543.75 | 0.86 | 795.24 | 8.07 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 17832.40 | 15227.26 | 2605.14 | 0.85 | 3543.90 | 35.94 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 550956.32 | 373237.86 | 177718.45 | 0.68 | 129994.02 | 1318.47 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 56319.85 | 38176.26 | 18143.59 | 0.68 | 10903.30 | 110.59 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.940 | 0.824 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.228 | 0.218 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.49_SHGC_0.25 | N/A | 2.786 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.780 | 0.698 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.45_SHGC_0.25 | N/A | 2.557 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.228 | 0.216 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 8 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.1375128933E-002 | 2.1562429182E-002 | Pass | Pass | 5.9498293468E-003 | 6.6037451881E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1822125954E-002 | 3.3364197399E-002 | Pass | Pass | 6.5228785300E-002 | 7.6744730053E-002 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.1420463914E-002 | 3.0101186493E-002 | Pass | Pass | 7.7630747604E-003 | 7.5645980217E-003 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.1768967660E-002 | 1.6833830448E-002 | Pass | Pass | 1.3615773838E-002 | 2.9445529976E-002 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8266728910E-003 | 4.6636684340E-003 | Pass | Pass | 2.4476923260E-002 | 3.0189272575E-002 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.5363783782E-002 | 0.2178135314 | Pass | Pass | 1.8688436586E-002 | 4.7969692295E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.1347377757E-002 | 7.7891833058E-002 | Pass | Pass | 1.6955719797E-002 | 2.3710345747E-002 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.4786648681E-002 | 4.4114766227E-002 | Pass | Pass | 8.0333936220E-003 | 8.1706254189E-003 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.3816858038E-002 | 9.1401377675E-002 | Pass | Pass | 0.3532542044 | 1.7147433075 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.5300144921E-002 | 6.2920823673E-002 | Pass | Pass | 2.8728280465 | 32.6870365607 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 5.5525167397E-002 | 6.4079423230E-002 | Pass | Pass | 3.0171805398E-002 | 0.1366947619 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.9913091695E-002 | 0.1513717506 | Pass | Pass | 0.2419642249 | 1.0614900377 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.3880507780E-002 | 0.1912316584 | Pass | Pass | 0.2993309145 | 1.2260593288 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 4.1602716176E-002 | 0.1648545333 | Pass | Pass | 21.0325293869 | 239.6609184494 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 6.2410323030E-004 | 1.3470032894E-003 | Pass | Pass | 0.4176969073 | 2.3091435905 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.2477350567E-002 | 7.8780087438E-002 | Pass | Pass | 0.2224825171 | 1.0706830873 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.9980394347E-002 | 0.1135760841 | Pass | Pass | 0.2214176560 | 1.2866714289 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.2311214823E-002 | 0.2207418778 | Pass | Pass | 0.2969981262 | 0.8479592071 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 3.9304033104E-002 | 7.1330273628E-002 | Pass | Pass | 1.0712547864E-002 | 3.0799321315E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9585697012E-002 | 5.9043469003E-002 | Pass | Pass | 1.1756151431E-002 | 3.4208355644E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 5.1747622736E-002 | 0.1109157404 | Pass | Pass | 2.0147004806E-002 | 3.6331014929E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.7578467706E-004 | 3.6491582276E-004 | Pass | Pass | 4.7689070613E-002 | 4.5909452617E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.698 | 0.780 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.940 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.557 | 0.252 | 0.276 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.557 | 0.252 | 0.276 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.557 | 0.252 | 0.276 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.786 | 0.252 | 0.276 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.786 | 0.252 | 0.276 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.786 | 0.252 | 0.276 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.786 | 0.252 | 0.276 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.786 | 0.252 | 0.276 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.786 | 0.252 | 0.276 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.786 | 0.252 | 0.276 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.786 | 0.252 | 0.276 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.786 | 0.252 | 0.276 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.786 | 0.252 | 0.276 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.786 | 0.252 | 0.276 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.786 | 0.252 | 0.276 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.786 | 0.252 | 0.276 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.786 | 0.252 | 0.276 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.49_SHGC_0.25 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.786 | 0.252 | 0.276 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.557 | 0.252 | 0.276 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.557 | 0.252 | 0.276 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.252 | 0.276 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.557 | 0.252 | 0.276 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.557 | 0.252 | 0.276 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.45_SHGC_0.25 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.557 | 0.252 | 0.276 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.719 | 0.252 | 0.276 | ||||||||||||
North Total or Average | 432.93 | 2.727 | 0.252 | 0.276 | ||||||||||||
Non-North Total or Average | 781.15 | 2.714 | 0.252 | 0.276 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.5035 | 1978.83 | 16826.96 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.48 | 168.00 | 52.43 | 0.0000 | Y | 165.59 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 11.4097 | 67.07 | 765.27 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.42 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 11.4097 | 77.67 | 886.18 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 9.75 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 10.2257 | 164.24 | 1679.50 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.48 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.9514 | 94.76 | 469.19 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 26.12 | 168.00 | 26.09 | 0.0000 | Y | 2.30 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 4.6285 | 78.04 | 361.20 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 7.6424 | 188.86 | 1443.35 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 40.42 | 0.0000 | Y | 10.95 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 11.4097 | 1308.19 | 14926.07 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 55.56 | 0.0000 | Y | 155.68 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 8.2882 | 156.09 | 1293.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 8.2882 | 156.07 | 1293.54 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 8.2882 | 1863.81 | 15447.67 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 123.65 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 8.2882 | 1864.32 | 15451.89 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 123.68 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 8.2882 | 156.09 | 1293.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 8.2882 | 156.07 | 1293.54 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 7.1042 | 1557.62 | 11065.61 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 66.04 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 8.2882 | 39.02 | 323.42 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 8.2882 | 39.02 | 323.38 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 8.2882 | 220.77 | 1829.83 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 14.65 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 7.6424 | 331.66 | 2534.65 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 50.06 | 0.0000 | Y | 23.82 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 7.6424 | 331.66 | 2534.65 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 50.06 | 0.0000 | Y | 23.82 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.4097 | 103.30 | 1178.68 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 7.1042 | 412.12 | 2927.81 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 17.47 |
Interior Lighting Total | 8.4749 | 11345.29 | 96149.78 | 490.16 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1443.35 | 562.91 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1443.35 | 562.91 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14926.07 | 1044.82 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14926.07 | 1044.82 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11632.50 | AstronomicalClock | - | 83.75 | 83.75 | 182.88 | |
Exterior Lighting Total | 11632.50 | 182.88 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 265528.14 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 665894.47 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10391.97 | 15498.30 | 13347.18 | 2151.12 | 0.86 | - | 3143.61 | 31.88 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 10165.05 | 15157.82 | 13051.65 | 2106.17 | 0.86 | - | 3073.16 | 31.17 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 59945.64 | 89989.43 | 78134.85 | 11854.58 | 0.87 | - | 18700.20 | 189.67 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 65416.34 | 96161.36 | 81306.23 | 14855.13 | 0.85 | - | 18677.61 | 189.44 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 9075.11 | 13522.17 | 11631.67 | 1890.50 | 0.86 | - | 2734.56 | 27.74 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 8991.56 | 13396.83 | 11522.92 | 1873.91 | 0.86 | - | 2708.65 | 27.47 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 2686.33 | 4007.10 | 3451.82 | 555.29 | 0.86 | - | 813.32 | 8.25 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 2628.09 | 3919.72 | 3375.97 | 543.75 | 0.86 | - | 795.24 | 8.07 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 12035.03 | 17832.40 | 15227.26 | 2605.14 | 0.85 | - | 3543.90 | 35.94 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 436047.35 | 550956.32 | 373237.86 | 177718.45 | 0.68 | - | 129994.02 | 1318.47 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 47940.88 | 56319.85 | 38176.26 | 18143.59 | 0.68 | - | 10903.30 | 110.59 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 7059.17 | 7099.75 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2781.19 | 2798.78 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1222.99 | 1229.70 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1637.22 | 1645.71 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 941.38 | 947.29 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11090.90 | 11154.16 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8604.15 | 8649.11 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24195.86 | 24328.90 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 3698.56 | 3990.93 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 3699.05 | 3991.46 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 21431.07 | 23125.11 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 21477.06 | 23174.74 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 3697.76 | 3990.07 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 3698.25 | 3990.60 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9195.48 | 9255.83 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1145.28 | 1235.80 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 1147.18 | 1237.84 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 5545.71 | 5983.98 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9716.11 | 9770.01 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10018.32 | 10073.97 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 6587.86 | 6625.73 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 5658.35 | 5693.86 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 91852.51 | 77201.27 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 9426.70 | 7923.07 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.95 | 668.37 | 703.64 | 1.00 | 1.21 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.93 | 653.50 | 703.64 | 1.00 | 1.22 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.59 | 3931.75 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.71 | 4020.35 | 703.64 | 1.00 | 0.96 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.83 | 582.02 | 703.64 | 1.00 | 1.25 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.82 | 576.55 | 703.64 | 1.00 | 1.25 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.25 | 172.88 | 703.64 | 1.00 | 1.87 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.24 | 169.06 | 703.64 | 1.00 | 1.88 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.08 | 758.17 | 703.64 | 1.00 | 1.18 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 19.99 | 44782.75 | 2240.64 | 1.00 | 1.11 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.019028 | 3639.83 | 191287.51 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.005867 | 1498.82 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.019028 | 1213.28 | 63762.50 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 32113.40 | 32113.40 | 16.23 | 2.377 | 2.377 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 20:30:00 | 24.00 | 24.00 | 0.00925 | 26.45 | 0.00820 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 3906.78 | 3906.78 | 58.25 | 0.289 | 0.289 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00907 | 30.93 | 0.00820 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3023.79 | 3023.79 | 38.93 | 0.224 | 0.224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00942 | 30.05 | 0.00820 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44628.73 | 44628.73 | 571.87 | 3.304 | 3.304 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00854 | 31.30 | 0.00820 | 0.000 | 0.00 |
CAFE_FLR_1 | 16520.67 | 16520.67 | 87.47 | 1.224 | 1.224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 23.99 | 0.01036 | 30.93 | 0.00820 | 0.676 | 0.00 |
LOBBY_FLR_1 | 61077.97 | 61077.97 | 46.69 | 4.524 | 4.524 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 23.99 | 0.01003 | 31.00 | 0.00820 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 9521.74 | 9521.74 | 244.01 | 0.950 | 0.950 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00820 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 9309.84 | 9309.84 | 238.61 | 0.929 | 0.929 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00820 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 56014.51 | 56014.51 | 2284.08 | 5.588 | 5.588 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21.11 | 21.11 | 0.00849 | 31.00 | 0.00820 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 57272.39 | 57272.39 | 2334.74 | 5.714 | 5.714 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 21.11 | 21.11 | 0.00874 | 31.30 | 0.00820 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 8291.59 | 8291.59 | 212.48 | 0.827 | 0.827 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.11 | 21.11 | 0.00858 | 26.66 | 0.00820 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 8213.64 | 8213.64 | 210.51 | 0.819 | 0.819 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.11 | 21.11 | 0.00858 | 26.41 | 0.00820 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2462.90 | 2462.90 | 63.12 | 0.246 | 0.246 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00820 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2408.52 | 2408.52 | 61.73 | 0.240 | 0.240 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 21.11 | 21.11 | 0.00857 | 30.41 | 0.00820 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 10800.64 | 10800.64 | 440.29 | 1.077 | 1.077 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 21.11 | 21.11 | 0.00865 | 31.00 | 0.00820 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27083.80 | 27083.80 | 81.66 | 2.008 | 2.008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 23.98 | 0.01057 | 31.30 | 0.00820 | 1.187 | 0.00 |
DINING_FLR_6 | 28430.83 | 28430.83 | 85.72 | 2.107 | 2.107 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 23.98 | 0.01047 | 31.30 | 0.00820 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 29891.50 | 29891.50 | 289.35 | 2.219 | 2.219 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.97 | 0.01012 | 30.50 | 0.00820 | 0.367 | 0.00 |
MECH_FLR_1 | 2994.81 | 2994.81 | 18.23 | 0.222 | 0.222 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 24.00 | 24.00 | 0.00849 | 29.46 | 0.00820 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1268.10 | 1268.10 | 13.38 | 0.094 | 0.094 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00848 | 31.30 | 0.00820 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 12784.24 | 12784.24 | 32.83 | 0.946 | 1.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00849 | 31.30 | 0.00820 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7554.41 | 7554.41 | 18.33 | 0.559 | 0.559 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00849 | 31.23 | 0.00820 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 0.854 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.854 | 0.00 | |
RETAIL_1_FLR_1 | 1923.36 | 1923.36 | 28.68 | 0.084 | 0.084 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00743 | 3.80 | 0.00506 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 558.78 | 558.78 | 7.19 | 0.024 | 0.092 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00756 | 3.80 | 0.00506 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 1291.52 | 1291.52 | 16.55 | 0.056 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00745 | 3.80 | 0.00506 | 0.000 | 0.00 |
CAFE_FLR_1 | 4973.47 | 4973.47 | 26.33 | 0.217 | 0.676 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00744 | 3.80 | 0.00506 | 0.676 | 0.00 |
LOBBY_FLR_1 | 10778.01 | 10778.01 | 8.24 | 0.471 | 1.893 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00748 | 3.80 | 0.00506 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 3698.57 | 3698.57 | 94.78 | 0.162 | 0.162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 3699.06 | 3699.06 | 94.81 | 0.163 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 21431.09 | 21431.09 | 873.89 | 0.941 | 0.941 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 21477.08 | 21477.08 | 875.52 | 0.944 | 0.944 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00765 | 3.80 | 0.00506 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 3697.77 | 3697.77 | 94.76 | 0.162 | 0.162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 3698.26 | 3698.26 | 94.78 | 0.162 | 0.162 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00762 | 3.80 | 0.00506 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 1145.28 | 1145.28 | 29.35 | 0.050 | 0.050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00769 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 1147.18 | 1147.18 | 29.40 | 0.050 | 0.050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00769 | 3.80 | 0.00506 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 5545.71 | 5545.71 | 226.07 | 0.244 | 0.244 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.11 | 21.11 | 0.00770 | 3.80 | 0.00506 | 0.099 | 0.00 |
BANQUET_FLR_6 | 3758.05 | 3758.05 | 11.33 | 0.164 | 1.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00776 | 3.80 | 0.00506 | 1.187 | 0.00 |
DINING_FLR_6 | 3764.03 | 3764.03 | 11.35 | 0.164 | 1.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00776 | 3.80 | 0.00506 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 0.367 | 0.00 | |
MECH_FLR_1 | 979.65 | 979.65 | 5.96 | 0.043 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00747 | 3.80 | 0.00506 | 0.000 | 0.00 |
STORAGE_FLR_1 | 662.95 | 662.95 | 7.00 | 0.029 | 0.058 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00746 | 3.80 | 0.00506 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 5673.36 | 5673.36 | 14.57 | 0.248 | 0.475 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00769 | 3.80 | 0.00506 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 3998.62 | 3998.62 | 9.70 | 0.175 | 0.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00780 | 3.80 | 0.00506 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 19.99 | 19.99 | 7.15 | 7.15 | 19.9866 | 11.6536 | 19.9866 | 0.5831 | 0.3000 |
FLR_3_DOAS | 15.58 | 2.05 | 2.88 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 7059.174 | 7059.174 | 1.362297 | 0.00015596 | 124.915 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7099.75 | 7059.17 | 1.362297 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 7101.04 | 7101.04 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 2781.193 | 2781.193 | 0.165744 | 0.00006145 | 55.142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2798.78 | 2781.19 | 0.165744 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00742748 | 47.1682 | 1923.36 | 0.00 | 2799.71 | 2799.71 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1222.993 | 1222.993 | 0.128287 | 0.00002702 | 22.716 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1229.70 | 1222.99 | 0.128287 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00756267 | 48.0149 | 558.78 | 0.00 | 1230.13 | 1230.13 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 1637.222 | 1637.222 | 0.127027 | 0.00003617 | 31.630 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1645.71 | 1637.22 | 0.127027 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00747082 | 47.4387 | 979.65 | 0.00 | 1646.49 | 1646.49 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 941.378 | 941.378 | 0.053787 | 0.00002080 | 18.756 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 947.29 | 941.38 | 0.053787 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00745904 | 47.3648 | 662.95 | 0.00 | 947.63 | 947.63 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11090.903 | 11090.903 | 1.893182 | 0.00024504 | 197.705 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11154.16 | 11090.90 | 1.893182 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00744559 | 47.2810 | 1291.52 | 0.00 | 11156.47 | 11156.47 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 8604.146 | 8604.146 | 0.701469 | 0.00019010 | 164.989 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8649.11 | 8604.15 | 0.701469 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00743863 | 47.2380 | 4973.47 | 0.00 | 8652.98 | 8652.98 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 24195.862 | 24195.862 | 2.592001 | 0.00053458 | 448.392 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24328.90 | 24195.86 | 2.592001 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00747527 | 47.4668 | 10778.01 | 0.00 | 24337.07 | 24337.07 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 10391.971 | -999.000 | 0.949887 | 0.00029720 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 10391.97 | 10218.44 | 0.949887 | 21.69 | 15.42 | 0.00857079 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00820219 | 18.11 | 0.0000 | 21.11 | 0.00857079 | 53.9598 | 9521.74 | 0.00 | 10590.28 | 10590.28 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 3698.563 | 3698.563 | 0.162480 | 0.00008172 | 84.200 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3990.93 | 3698.56 | 0.162480 | 21.11 | 14.35 | 0.00762320 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00762320 | 48.0665 | 3698.57 | 0.00 | 3992.74 | 3992.74 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 10165.048 | -999.000 | 0.928748 | 0.00029071 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 10165.05 | 9991.64 | 0.928748 | 21.69 | 15.42 | 0.00857234 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00820219 | 18.11 | 0.0000 | 21.11 | 0.00857234 | 53.9695 | 9309.84 | 0.00 | 10358.96 | 10358.96 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 3699.054 | 3699.054 | 0.162502 | 0.00008173 | 84.211 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3991.46 | 3699.05 | 0.162502 | 21.11 | 14.35 | 0.00762327 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00762327 | 48.0669 | 3699.06 | 0.00 | 3993.27 | 3993.27 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 59945.643 | -999.000 | 5.587754 | 0.00171441 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | 8/21 13:20:00 | 59945.64 | 59945.64 | 5.587754 | 21.69 | 15.35 | 0.00849401 | 12.80 | 11.93 | 0.00849401 | 31.00 | 0.00820219 | 18.30 | 0.0000 | 21.11 | 0.00849401 | 53.4818 | 56014.51 | 0.00 | 61100.92 | 61100.92 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 21431.073 | 21431.073 | 0.941493 | 0.00047349 | 487.887 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23125.11 | 21431.07 | 0.941493 | 21.11 | 14.38 | 0.00765147 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00765147 | 48.2419 | 21431.09 | 0.00 | 23135.77 | 23135.77 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 65416.344 | -999.000 | 5.713678 | 0.00187086 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | 8/21 14:50:00 | 65416.34 | 61849.05 | 5.713678 | 21.69 | 15.57 | 0.00874041 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00820219 | 18.40 | 0.0000 | 21.11 | 0.00874041 | 55.0139 | 57272.39 | 0.00 | 66639.72 | 65478.75 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 21477.063 | 21477.063 | 0.943513 | 0.00047451 | 488.933 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23174.74 | 21477.06 | 0.943513 | 21.11 | 14.38 | 0.00765204 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00765204 | 48.2455 | 21477.08 | 0.00 | 23185.41 | 23185.41 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 9075.115 | -999.000 | 0.827167 | 0.00025954 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | 8/21 09:10:00 | 9075.11 | 8901.82 | 0.827167 | 21.69 | 15.43 | 0.00858115 | 12.80 | 11.93 | 0.00850000 | 26.66 | 0.00820219 | 16.85 | 0.0000 | 21.11 | 0.00858115 | 54.0242 | 8291.59 | 0.00 | 9247.89 | 9247.89 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 3697.760 | 3697.760 | 0.162445 | 0.00008170 | 84.182 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3990.07 | 3697.76 | 0.162445 | 21.11 | 14.35 | 0.00762313 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00762313 | 48.0660 | 3697.77 | 0.00 | 3991.88 | 3991.88 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 8991.560 | -999.000 | 0.819391 | 0.00025715 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | 8/21 09:00:00 | 8991.56 | 8818.37 | 0.819391 | 21.69 | 15.43 | 0.00858186 | 12.80 | 11.93 | 0.00850000 | 26.41 | 0.00820219 | 16.76 | 0.0000 | 21.11 | 0.00858186 | 54.0286 | 8213.64 | 0.00 | 9162.71 | 9162.71 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 3698.252 | 3698.252 | 0.162467 | 0.00008171 | 84.193 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3990.60 | 3698.25 | 0.162467 | 21.11 | 14.35 | 0.00762319 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00762319 | 48.0665 | 3698.26 | 0.00 | 3992.41 | 3992.41 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 9195.476 | 9195.476 | 0.680097 | 0.00020316 | 178.652 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9255.83 | 9195.48 | 0.680097 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00769305 | 48.8324 | 5673.36 | 0.00 | 9258.03 | 9258.03 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2686.327 | -999.000 | 0.245698 | 0.00007683 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2686.33 | 2642.88 | 0.245698 | 21.69 | 15.42 | 0.00856853 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00820219 | 18.11 | 0.0000 | 21.11 | 0.00856853 | 53.9458 | 2462.90 | 0.00 | 2737.62 | 2737.62 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 1145.283 | 1145.283 | 0.050313 | 0.00002530 | 26.072 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1235.80 | 1145.28 | 0.050313 | 21.11 | 14.41 | 0.00768802 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00768802 | 48.4702 | 1145.28 | 0.00 | 1236.38 | 1236.38 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2628.085 | -999.000 | 0.240273 | 0.00007516 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | 8/21 16:30:00 | 2628.09 | 2584.67 | 0.240273 | 21.69 | 15.42 | 0.00857002 | 12.80 | 11.93 | 0.00850000 | 30.41 | 0.00820219 | 18.11 | 0.0000 | 21.11 | 0.00857002 | 53.9550 | 2408.52 | 0.00 | 2678.25 | 2678.25 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 1147.176 | 1147.176 | 0.050396 | 0.00002535 | 26.115 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1237.84 | 1147.18 | 0.050396 | 21.11 | 14.41 | 0.00768851 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00768851 | 48.4733 | 1147.18 | 0.00 | 1238.42 | 1238.42 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 12035.028 | -999.000 | 1.077499 | 0.00034419 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | 8/21 13:20:00 | 12035.03 | 11624.45 | 1.077499 | 21.69 | 15.49 | 0.00864723 | 12.80 | 11.93 | 0.00850000 | 31.00 | 0.00820219 | 18.30 | 0.0000 | 21.11 | 0.00864723 | 54.4352 | 10800.64 | 0.00 | 12262.68 | 12262.68 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 5545.708 | 5545.708 | 0.243628 | 0.00012253 | 126.248 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5983.98 | 5545.71 | 0.243628 | 21.11 | 14.42 | 0.00770180 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.11 | 0.00770180 | 48.5558 | 5545.71 | 0.00 | 5986.82 | 5986.82 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9716.114 | 9716.114 | 1.150352 | 0.00021467 | 178.245 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 9770.01 | 9716.11 | 1.150352 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00776006 | 49.2528 | 3758.05 | 0.00 | 9772.96 | 9772.96 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 10018.319 | 10018.319 | 1.207546 | 0.00022134 | 183.479 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 10073.97 | 10018.32 | 1.207546 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00776009 | 49.2530 | 3764.03 | 0.00 | 10076.96 | 10076.96 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6587.863 | 6587.863 | 1.271343 | 0.00014555 | 116.575 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6625.73 | 6587.86 | 1.271343 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6626.94 | 6626.94 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 5658.349 | 5658.349 | 0.320426 | 0.00012501 | 112.856 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 5693.86 | 5658.35 | 0.320426 | 16.70 | 13.01 | 0.00800000 | 40.00 | 20.93 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00779930 | 49.4986 | 3998.62 | 0.00 | 5695.90 | 5695.90 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 436047.349 | -999.000 | 19.986602 | 0.01247090 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 436047.35 | 413367.49 | 19.986602 | 28.26 | 17.89 | 0.00880970 | 10.94 | 10.94 | 0.00843576 | 31.30 | 0.00820219 | 18.40 | 58.3239 | 23.99 | 0.00947666 | 50.0101 | 269638.11 | 0.00 | 491440.46 | 431628.26 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 91852.509 | 91852.509 | 5.995981 | 0.00202937 | 1446.413 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 77201.27 | 91852.51 | 5.995981 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.01 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 194.4131 | 21.00 | 0.00768104 | 48.7573 | 38320.63 | 0.00 | 77193.14 | 77193.14 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 47940.876 | -999.000 | 2.051199 | 0.00137110 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 47940.88 | 47940.88 | 2.051199 | 31.30 | 18.40 | 0.00820219 | 10.94 | 11.63 | 0.00820219 | 31.30 | 0.00820219 | 18.40 | 100.0000 | 21.11 | 0.00861819 | 54.2541 | 156221.45 | 0.00 | 53232.09 | 51285.66 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 9426.704 | 9426.704 | 0.615360 | 0.00020827 | 148.444 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7923.07 | 9426.70 | 0.615360 | 3.80 | 3.80 | 0.00505843 | 16.70 | 13.01 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 333.3333 | 21.11 | 0.00765202 | 48.2453 | 65539.99 | 0.00 | 7922.23 | 7922.23 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 7059.174 | 7059.174 | 1.362297 | 0.00015596 | 124.915 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 2.6211 | 2.658541 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7099.75 | 7059.17 | 1.0000 | 1.60993406 | 1.362297 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.15594792 | 60.00 | 49.00 | 11.00 | 0.000 | 7099.75 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 7101.04 | 7101.04 | 1.60993406 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2781.193 | 2781.193 | 0.165744 | 0.00006145 | 55.142 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 1.0332 | 1.047419 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 2798.78 | 2781.19 | 1.0000 | 0.19587276 | 0.165744 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.06144078 | 60.00 | 49.00 | 11.00 | 0.000 | 2798.78 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00742748 | 21.00 | 0.00742748 | 47.1682 | 1923.36 | 0.00 | 2799.71 | 2799.71 | 0.19587276 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 30.62 | 18.22 | 0.00800000 | 51228.2 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1222.993 | 1222.993 | 0.128287 | 0.00002702 | 22.716 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 0.4540 | 0.460589 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1229.70 | 1222.99 | 1.0000 | 0.15160718 | 0.128287 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.02701777 | 60.00 | 49.00 | 11.00 | 0.000 | 1229.70 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00756267 | 21.00 | 0.00756267 | 48.0149 | 558.78 | 0.00 | 1230.13 | 1230.13 | 0.15160718 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.56 | 16.14 | 0.00800000 | 45048.6 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1637.222 | 1637.222 | 0.127027 | 0.00003617 | 31.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 0.6076 | 0.616591 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1645.71 | 1637.22 | 1.0000 | 0.15011800 | 0.127027 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.03616872 | 60.00 | 49.00 | 11.00 | 0.000 | 1645.71 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00747082 | 21.00 | 0.00747082 | 47.4387 | 979.65 | 0.00 | 1646.49 | 1646.49 | 0.15011800 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.36 | 17.12 | 0.00800000 | 47902.7 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 941.378 | 941.378 | 0.053787 | 0.00002080 | 18.756 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 0.3497 | 0.354530 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 947.29 | 941.38 | 1.0000 | 0.06356463 | 0.053787 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.02079647 | 60.00 | 49.00 | 11.00 | 0.000 | 947.29 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00745904 | 21.00 | 0.00745904 | 47.3648 | 662.95 | 0.00 | 947.63 | 947.63 | 0.06356463 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.22 | 18.42 | 0.00800000 | 51842.8 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11090.903 | 11090.903 | 1.893182 | 0.00024504 | 197.705 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 4.1179 | 4.176922 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 11154.16 | 11090.90 | 1.0000 | 2.23732211 | 1.893182 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.24501495 | 60.00 | 49.00 | 11.00 | 0.000 | 11154.16 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00744559 | 21.00 | 0.00744559 | 47.2810 | 1291.52 | 0.00 | 11156.47 | 11156.47 | 2.23732211 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.49 | 15.02 | 0.00800000 | 41921.3 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8604.146 | 8604.146 | 0.701469 | 0.00019010 | 164.989 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 3.1931 | 3.240390 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8649.11 | 8604.15 | 1.0000 | 0.82898062 | 0.701469 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.19007870 | 60.00 | 49.00 | 11.00 | 0.000 | 8649.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00743863 | 21.00 | 0.00743863 | 47.2380 | 4973.47 | 0.00 | 8652.98 | 8652.98 | 0.82898062 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.84 | 16.94 | 0.00800000 | 47372.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24195.862 | 24195.862 | 2.592001 | 0.00053458 | 448.392 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 8.9817 | 9.112353 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24328.90 | 24195.86 | 1.0000 | 3.06317130 | 2.592001 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.53452348 | 60.00 | 49.00 | 11.00 | 0.000 | 24328.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00747527 | 21.00 | 0.00747527 | 47.4668 | 10778.01 | 0.00 | 24337.07 | 24337.07 | 3.06317130 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 24.39 | 16.08 | 0.00800000 | 44879.8 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10391.971 | -999.000 | 0.949887 | 0.00029720 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7727 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.949887 | 1.12255568 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 1.5620 | 1.561922 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | 10391.97 | 10218.44 | 1.0000 | 1.12255568 | 0.949887 | 21.69 | 15.42 | 0.00857079 | 43579.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.29717318 | 6.70 | 13.38 | 8.33 | 0.000 | 10391.97 | 30.41 | 0.00820219 | 18.11 | 0.00000000 | 0.0000 | 21.11 | 0.00857079 | 21.11 | 0.00857079 | 53.9598 | 9521.74 | 0.00 | 10590.28 | 10590.28 | 1.12255568 | 21.69 | 15.61 | 0.00857079 | 43579.6 | 12.45 | 12.03 | 0.00857079 | 34145.5 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3698.563 | 3698.563 | 0.162480 | 0.00008172 | 84.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.949887 | 1.12255568 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 1.4734 | 1.392908 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3990.93 | 3698.56 | 1.0000 | 0.19201575 | 0.162480 | 21.11 | 14.35 | 0.00762320 | 40577.1 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08170688 | 60.00 | 49.00 | 11.00 | 0.000 | 3990.93 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00762320 | 21.11 | 0.00762320 | 48.0665 | 3698.57 | 0.00 | 3992.74 | 3992.74 | 0.19201575 | 16.60 | 12.77 | 0.00762320 | 35980.7 | 37.01 | 19.97 | 0.00762320 | 56774.6 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10165.048 | -999.000 | 0.928748 | 0.00029071 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7756 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.928748 | 1.09757467 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 1.5278 | 1.527815 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | 10165.05 | 9991.64 | 1.0000 | 1.09757467 | 0.928748 | 21.69 | 15.42 | 0.00857234 | 43583.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.29068399 | 6.70 | 13.38 | 8.33 | 0.000 | 10165.05 | 30.41 | 0.00820219 | 18.11 | 0.00000000 | 0.0000 | 21.11 | 0.00857234 | 21.11 | 0.00857234 | 53.9695 | 9309.84 | 0.00 | 10358.96 | 10358.96 | 1.09757467 | 21.69 | 15.61 | 0.00857234 | 43583.6 | 12.45 | 12.03 | 0.00857234 | 34145.5 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3699.054 | 3699.054 | 0.162502 | 0.00008173 | 84.211 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.928748 | 1.09757467 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 1.4736 | 1.393093 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3991.46 | 3699.05 | 1.0000 | 0.19204124 | 0.162502 | 21.11 | 14.35 | 0.00762327 | 40577.2 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08171773 | 60.00 | 49.00 | 11.00 | 0.000 | 3991.46 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00762327 | 21.11 | 0.00762327 | 48.0669 | 3699.06 | 0.00 | 3993.27 | 3993.27 | 0.19204124 | 16.60 | 12.77 | 0.00762327 | 35980.9 | 37.01 | 19.97 | 0.00762327 | 56774.7 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 59945.643 | -999.000 | 5.587754 | 0.00171441 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.6299 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.587754 | 6.60348817 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 9.0100 | 9.009879 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | unknown | unknown | 8/21 13:20:00 | 59945.64 | 59945.64 | 1.0000 | 6.60348817 | 5.587754 | 21.69 | 15.35 | 0.00849401 | 43384.9 | 12.80 | 11.93 | 0.00849401 | 34322.2 | 1.71423089 | 6.70 | 13.38 | 8.33 | 0.000 | 59945.64 | 31.00 | 0.00820219 | 18.30 | 0.00000000 | 0.0000 | 21.11 | 0.00849401 | 21.11 | 0.00849401 | 53.4818 | 56014.51 | 0.00 | 61100.92 | 61100.92 | 6.60348817 | 21.69 | 15.54 | 0.00849401 | 43384.9 | 12.63 | 12.02 | 0.00849401 | 34132.1 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21431.073 | 21431.073 | 0.941493 | 0.00047349 | 487.887 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.587754 | 6.60348817 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 8.5373 | 8.071112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23125.11 | 21431.07 | 1.0000 | 1.11263583 | 0.941493 | 21.11 | 14.38 | 0.00765147 | 40649.1 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.47344506 | 60.00 | 49.00 | 11.00 | 0.000 | 23125.11 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00765147 | 21.11 | 0.00765147 | 48.2419 | 21431.09 | 0.00 | 23135.77 | 23135.77 | 1.11263583 | 16.60 | 12.80 | 0.00765147 | 36052.3 | 37.00 | 19.99 | 0.00765147 | 56846.0 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 65416.344 | -999.000 | 5.713678 | 0.00187086 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0880 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.713678 | 6.75230314 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 9.8323 | 9.832130 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | unknown | unknown | unknown | 8/21 14:50:00 | 65416.34 | 61849.05 | 1.0000 | 6.75230314 | 5.713678 | 21.69 | 15.57 | 0.00874041 | 44010.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 1.87067337 | 6.70 | 13.38 | 8.33 | 0.000 | 65416.34 | 31.30 | 0.00820219 | 18.40 | 0.00000000 | 0.0000 | 21.11 | 0.00874041 | 21.11 | 0.00874041 | 55.0139 | 57272.39 | 0.00 | 66639.72 | 65478.75 | 6.75230314 | 21.69 | 15.76 | 0.00874041 | 44010.2 | 12.20 | 12.02 | 0.00867228 | 34141.0 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21477.063 | 21477.063 | 0.943513 | 0.00047451 | 488.933 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.713678 | 6.75230314 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 8.5556 | 8.088432 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23174.74 | 21477.06 | 1.0000 | 1.11502350 | 0.943513 | 21.11 | 14.38 | 0.00765204 | 40650.6 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.47446105 | 60.00 | 49.00 | 11.00 | 0.000 | 23174.74 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00765204 | 21.11 | 0.00765204 | 48.2455 | 21477.08 | 0.00 | 23185.41 | 23185.41 | 1.11502350 | 16.60 | 12.80 | 0.00765204 | 36053.8 | 37.00 | 19.99 | 0.00765204 | 56847.4 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9075.115 | -999.000 | 0.827167 | 0.00025954 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7919 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.827167 | 0.97752859 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 1.3640 | 1.363997 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | unknown | unknown | unknown | 8/21 09:10:00 | 9075.11 | 8901.82 | 1.0000 | 0.97752859 | 0.827167 | 21.69 | 15.43 | 0.00858115 | 43605.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.25951581 | 6.70 | 13.38 | 8.33 | 0.000 | 9075.11 | 26.66 | 0.00820219 | 16.85 | 0.00000000 | 0.0000 | 21.11 | 0.00858115 | 21.11 | 0.00858115 | 54.0242 | 8291.59 | 0.00 | 9247.89 | 9247.89 | 0.97752859 | 21.69 | 15.62 | 0.00858115 | 43605.9 | 12.43 | 12.03 | 0.00858115 | 34145.5 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3697.760 | 3697.760 | 0.162445 | 0.00008170 | 84.182 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.827167 | 0.97752859 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 1.4730 | 1.392606 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3990.07 | 3697.76 | 1.0000 | 0.19197411 | 0.162445 | 21.11 | 14.35 | 0.00762313 | 40576.9 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08168917 | 60.00 | 49.00 | 11.00 | 0.000 | 3990.07 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00762313 | 21.11 | 0.00762313 | 48.0660 | 3697.77 | 0.00 | 3991.88 | 3991.88 | 0.19197411 | 16.60 | 12.77 | 0.00762313 | 35980.6 | 37.01 | 19.97 | 0.00762313 | 56774.4 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8991.560 | -999.000 | 0.819391 | 0.00025715 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7933 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.819391 | 0.96833871 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 1.3515 | 1.351439 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | unknown | unknown | unknown | 8/21 09:00:00 | 8991.56 | 8818.37 | 1.0000 | 0.96833871 | 0.819391 | 21.69 | 15.43 | 0.00858186 | 43607.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.25712644 | 6.70 | 13.38 | 8.33 | 0.000 | 8991.56 | 26.41 | 0.00820219 | 16.76 | 0.00000000 | 0.0000 | 21.11 | 0.00858186 | 21.11 | 0.00858186 | 54.0286 | 8213.64 | 0.00 | 9162.71 | 9162.71 | 0.96833871 | 21.69 | 15.62 | 0.00858186 | 43607.7 | 12.42 | 12.03 | 0.00858186 | 34145.4 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3698.252 | 3698.252 | 0.162467 | 0.00008171 | 84.193 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.819391 | 0.96833871 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 1.4732 | 1.392791 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3990.60 | 3698.25 | 1.0000 | 0.19199963 | 0.162467 | 21.11 | 14.35 | 0.00762319 | 40577.1 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.08170002 | 60.00 | 49.00 | 11.00 | 0.000 | 3990.60 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00762319 | 21.11 | 0.00762319 | 48.0665 | 3698.26 | 0.00 | 3992.41 | 3992.41 | 0.19199963 | 16.60 | 12.77 | 0.00762319 | 35980.7 | 37.01 | 19.97 | 0.00762319 | 56774.6 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9195.476 | 9195.476 | 0.680097 | 0.00020316 | 178.652 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 3.4171 | 3.463089 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 9255.83 | 9195.48 | 1.0000 | 0.80372392 | 0.680097 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.20314208 | 60.00 | 49.00 | 11.00 | 0.000 | 9255.83 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00769305 | 21.00 | 0.00769305 | 48.8324 | 5673.36 | 0.00 | 9258.03 | 9258.03 | 0.80372392 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 27.90 | 17.30 | 0.00800000 | 48453.7 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2686.327 | -999.000 | 0.245698 | 0.00007683 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7685 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.245698 | 0.29036082 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 0.4038 | 0.403757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | 2686.33 | 2642.88 | 1.0000 | 0.29036082 | 0.245698 | 21.69 | 15.42 | 0.00856853 | 43573.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.07681934 | 6.70 | 13.38 | 8.33 | 0.000 | 2686.33 | 30.41 | 0.00820219 | 18.11 | 0.00000000 | 0.0000 | 21.11 | 0.00856853 | 21.11 | 0.00856853 | 53.9458 | 2462.90 | 0.00 | 2737.62 | 2737.62 | 0.29036082 | 21.69 | 15.61 | 0.00856853 | 43573.9 | 12.46 | 12.03 | 0.00856853 | 34145.6 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1145.283 | 1145.283 | 0.050313 | 0.00002530 | 26.072 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.245698 | 0.29036082 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 0.4562 | 0.431323 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1235.80 | 1145.28 | 1.0000 | 0.05945889 | 0.050313 | 21.11 | 14.41 | 0.00768802 | 40741.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.02530106 | 60.00 | 49.00 | 11.00 | 0.000 | 1235.80 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00768802 | 21.11 | 0.00768802 | 48.4702 | 1145.28 | 0.00 | 1236.38 | 1236.38 | 0.05945889 | 16.60 | 12.84 | 0.00768802 | 36144.9 | 37.00 | 20.01 | 0.00768802 | 56938.7 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2628.085 | -999.000 | 0.240273 | 0.00007516 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.7712 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.240273 | 0.28394977 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 0.3950 | 0.395003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | unknown | unknown | unknown | 8/21 16:30:00 | 2628.09 | 2584.67 | 1.0000 | 0.28394977 | 0.240273 | 21.69 | 15.42 | 0.00857002 | 43577.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.07515384 | 6.70 | 13.38 | 8.33 | 0.000 | 2628.09 | 30.41 | 0.00820219 | 18.11 | 0.00000000 | 0.0000 | 21.11 | 0.00857002 | 21.11 | 0.00857002 | 53.9550 | 2408.52 | 0.00 | 2678.25 | 2678.25 | 0.28394977 | 21.69 | 15.61 | 0.00857002 | 43577.7 | 12.45 | 12.03 | 0.00857002 | 34145.5 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1147.176 | 1147.176 | 0.050396 | 0.00002535 | 26.115 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.240273 | 0.28394977 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 0.4570 | 0.432036 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 1237.84 | 1147.18 | 1.0000 | 0.05955716 | 0.050396 | 21.11 | 14.41 | 0.00768851 | 40743.0 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.02534287 | 60.00 | 49.00 | 11.00 | 0.000 | 1237.84 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00768851 | 21.11 | 0.00768851 | 48.4733 | 1147.18 | 0.00 | 1238.42 | 1238.42 | 0.05955716 | 16.60 | 12.84 | 0.00768851 | 36146.1 | 37.00 | 20.01 | 0.00768851 | 56939.9 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12035.028 | -999.000 | 1.077499 | 0.00034419 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9148 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.077499 | 1.27336579 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 1.8089 | 1.808874 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | unknown | unknown | unknown | 8/21 13:20:00 | 12035.03 | 11624.45 | 1.0000 | 1.27336579 | 1.077499 | 21.69 | 15.49 | 0.00864723 | 43773.5 | 12.80 | 11.93 | 0.00850000 | 34322.2 | 0.34415873 | 6.70 | 13.38 | 8.33 | 0.000 | 12035.03 | 31.00 | 0.00820219 | 18.30 | 0.00000000 | 0.0000 | 21.11 | 0.00864723 | 21.11 | 0.00864723 | 54.4352 | 10800.64 | 0.00 | 12262.68 | 12262.68 | 1.27336579 | 21.69 | 15.67 | 0.00864723 | 43773.5 | 12.26 | 12.02 | 0.00864723 | 34143.4 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5545.708 | 5545.708 | 0.243628 | 0.00012253 | 126.248 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.077499 | 1.27336579 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 2.2092 | 2.088558 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 5983.98 | 5545.71 | 1.0000 | 0.28791393 | 0.243628 | 21.11 | 14.42 | 0.00770180 | 40776.8 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.12251315 | 60.00 | 49.00 | 11.00 | 0.000 | 5983.98 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.11 | 0.00770180 | 21.11 | 0.00770180 | 48.5558 | 5545.71 | 0.00 | 5986.82 | 5986.82 | 0.28791393 | 16.60 | 12.85 | 0.00770180 | 36179.7 | 37.00 | 20.02 | 0.00770180 | 56973.5 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9716.114 | 9716.114 | 1.150352 | 0.00021467 | 178.245 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 3.6069 | 3.659165 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 9770.01 | 9716.11 | 1.0000 | 1.35946164 | 1.150352 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.21464376 | 60.00 | 49.00 | 11.00 | 0.000 | 9770.01 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00776006 | 21.00 | 0.00776006 | 49.2528 | 3758.05 | 0.00 | 9772.96 | 9772.96 | 1.35946164 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.65 | 15.81 | 0.00800000 | 44123.6 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10018.319 | 10018.319 | 1.207546 | 0.00022134 | 183.479 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 3.7191 | 3.772978 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 10073.97 | 10018.32 | 1.0000 | 1.42705161 | 1.207546 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.22131994 | 60.00 | 49.00 | 11.00 | 0.000 | 10073.97 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00776009 | 21.00 | 0.00776009 | 49.2530 | 3764.03 | 0.00 | 10076.96 | 10076.96 | 1.42705161 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 23.52 | 15.77 | 0.00800000 | 43996.1 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6587.863 | 6587.863 | 1.271343 | 0.00014555 | 116.575 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 2.4461 | 2.481041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6625.73 | 6587.86 | 1.0000 | 1.50244554 | 1.271343 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.14553593 | 60.00 | 49.00 | 11.00 | 0.000 | 6625.73 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 6626.94 | 6626.94 | 1.50244554 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 20.93 | 14.81 | 0.00800000 | 41345.5 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5658.349 | 5658.349 | 0.320426 | 0.00012501 | 112.856 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 2.1020 | 2.130979 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 5693.86 | 5658.35 | 1.0000 | 0.37867246 | 0.320426 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 40.00 | 20.93 | 0.00800000 | 60796.0 | 0.12500156 | 60.00 | 49.00 | 11.00 | 0.000 | 5693.86 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00779930 | 21.00 | 0.00779930 | 49.4986 | 3998.62 | 0.00 | 5695.90 | 5695.90 | 0.37867246 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 31.35 | 18.46 | 0.00800000 | 51976.5 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 436047.349 | -999.000 | 19.986602 | 0.01247090 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2168 | 1004.8586 | 1.1818 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 19.986602 | 23.61973982 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 65.5395 | 65.539496 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 436047.35 | 413367.49 | 1.0000 | 23.61973982 | 19.986602 | 28.26 | 17.89 | 0.00880970 | 50887.3 | 10.94 | 10.94 | 0.00843576 | 32427.3 | 12.46962682 | 6.70 | 13.38 | 8.33 | 44782.752 | 391264.60 | 31.30 | 0.00820219 | 18.40 | 11.65697000 | 58.3239 | 23.99 | 0.00966103 | 23.99 | 0.00947666 | 50.0101 | 269638.11 | 0.00 | 491440.46 | 431628.26 | 23.61973982 | 28.26 | 18.09 | 0.00880970 | 50887.3 | 10.36 | 10.35 | 0.00780490 | 30081.0 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 91852.509 | 91852.509 | 5.995981 | 0.00202937 | 1446.413 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 19.986602 | 23.61973982 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 28.5010 | 34.592383 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 77201.27 | 91852.51 | 1.0000 | 7.08592195 | 5.995981 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 2.02916193 | 60.00 | 49.00 | 11.00 | 0.000 | 77201.27 | 3.80 | 0.00505843 | 3.80 | 11.65697000 | 194.4131 | 17.41 | 0.00631120 | 21.00 | 0.00768104 | 48.7573 | 38320.63 | 0.00 | 77193.14 | 77193.14 | 7.08592195 | 16.60 | 10.13 | 0.00505843 | 29487.3 | 27.34 | 14.51 | 0.00505843 | 40381.1 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 47940.876 | -999.000 | 2.051199 | 0.00137110 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0875 | 1004.8586 | 1.1818 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.42406327 | 4197.9300 | 999.8980 | 19.02612552 | 15.03 | 6.70 | 8.33 | 665319.96 | 7.2057 | 7.205687 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 47940.88 | 47940.88 | 1.0000 | 2.42406327 | 2.051199 | 31.30 | 18.40 | 0.00820219 | 52441.9 | 10.94 | 11.63 | 0.00820219 | 33570.3 | 1.37096312 | 6.70 | 13.38 | 8.33 | 2194.880 | 45746.00 | 31.30 | 0.00820219 | 18.40 | 2.05119905 | 100.0000 | 21.11 | 0.00861546 | 21.11 | 0.00861819 | 54.2541 | 156221.45 | 0.00 | 53232.09 | 51285.66 | 2.42406327 | 31.30 | 18.60 | 0.00820219 | 52441.9 | 10.56 | 10.52 | 0.00788363 | 30482.1 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 9426.704 | 9426.704 | 0.615360 | 0.00020827 | 148.444 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.42406327 | 4197.9300 | 999.8980 | 5.86592124 | 71.00 | 82.00 | 11.00 | 270871.99 | 2.9250 | 3.550171 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7923.07 | 9426.70 | 1.0000 | 0.72721898 | 0.615360 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 16.70 | 13.01 | 0.00800000 | 37036.7 | 0.20825026 | 60.00 | 49.00 | 11.00 | 0.000 | 7923.07 | 3.80 | 0.00505843 | 3.80 | 2.05119905 | 333.3333 | 21.11 | 0.00765082 | 21.11 | 0.00765202 | 48.2453 | 65539.99 | 0.00 | 7922.23 | 7922.23 | 0.72721898 | 16.60 | 10.13 | 0.00505843 | 29487.3 | 27.34 | 14.51 | 0.00505843 | 40381.1 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 19.99 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.001447 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 0.00 | 8759.00 | 0.00 |
RETAIL_1_FLR_1 | 319.50 | 8136.33 | 24.00 |
RETAIL_2_FLR_1 | 12.67 | 8541.67 | 0.00 |
LAUNDRY_FLR_1 | 5112.50 | 3171.00 | 2040.67 |
CAFE_FLR_1 | 1566.17 | 7018.00 | 762.17 |
LOBBY_FLR_1 | 441.83 | 7310.83 | 36.00 |
ROOM_1_FLR_3 | 91.00 | 8482.17 | 91.00 |
ROOM_2_FLR_3 | 704.50 | 8070.50 | 341.00 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 114.17 | 8723.00 | 109.00 |
ROOM_5_FLR_3 | 95.83 | 8728.00 | 95.83 |
ROOM_6_FLR_3 | 405.00 | 8607.83 | 329.33 |
ROOM_1_FLR_6 | 213.00 | 8223.50 | 210.67 |
ROOM_2_FLR_6 | 1112.50 | 7788.00 | 592.67 |
ROOM_3_MULT9_FLR_6 | 23.00 | 8325.17 | 22.17 |
BANQUET_FLR_6 | 4344.50 | 3525.17 | 766.83 |
DINING_FLR_6 | 5643.00 | 1671.83 | 610.67 |
KITCHEN_FLR_6 | 8325.50 | 6509.00 | 6326.33 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8615.67 | 8760.00 | 7259.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 0.33 | 0.00 | 0.33 | 0.00 |
RETAIL_2_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | 0.00 | 7.83 | 0.00 | 7.83 |
CAFE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 0.00 | 1.50 | 0.00 | 1.50 |
ROOM_2_FLR_3 | 0.00 | 1.17 | 0.00 | 1.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 0.00 | 12.67 | 0.00 | 12.67 |
ROOM_5_FLR_3 | 0.00 | 1.00 | 0.00 | 1.00 |
ROOM_6_FLR_3 | 0.00 | 17.83 | 0.00 | 17.83 |
ROOM_1_FLR_6 | 0.00 | 4.00 | 0.00 | 4.00 |
ROOM_2_FLR_6 | 0.00 | 11.00 | 0.00 | 11.00 |
ROOM_3_MULT9_FLR_6 | 0.00 | 9.17 | 0.00 | 9.17 |
BANQUET_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | 0.00 | 64.33 | 0.00 | 64.33 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 4.50 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.17 | 0.00 | 0.00 | 0.00 |
Facility | 4.50 | 108.17 | 0.33 | 108.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.033 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.290 | 0.267 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.528 | 0.048 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.344 | 0.148 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 3.453 | 0.240 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.837 | 0.069 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.356 | 0.175 | 0.000 | 0.095 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.101 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.404 | 0.078 | 0.000 | 0.159 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.356 | 0.175 | 0.000 | 0.095 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.356 | 0.175 | 0.000 | 0.101 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.356 | 0.175 | 0.000 | 0.107 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.356 | 0.176 | 0.000 | 0.101 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.404 | 0.143 | 0.000 | 0.169 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.479 | 0.051 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.844 | 0.051 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 20.246 | 0.146 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.78 | 106.50 | 4826.41 | 1.011 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.227 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.489 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 21.789 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.54 | 142.30 | 748.35 | 3.357 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 245.04 | 422.44 | 5183.56 | 1.790 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.076 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.96 | 249.90 | 1010.89 | 4.284 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.90 | 22.24 | 314.87 | 14.443 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
Electricity:Building | 2493.14 | 31416.52 | 03-JUN-05:00 | 161759.69 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 308.71 | 3532.55 | 02-JAN-02:10 | 23174.34 | 02-JAN-20:10 |
InteriorLights:Electricity | 827.86 | 7073.40 | 03-JUN-05:00 | 75078.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.60 | 1504.65 | 02-JAN-02:10 | 13541.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 827.86 | 7073.40 | 03-JUN-05:00 | 75078.55 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.61 | 220.86 | 02-JAN-02:10 | 1374.34 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.42 | 76.53 | 02-JAN-02:10 | 688.74 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.55 | 255.76 | 02-JAN-02:10 | 1591.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.75 | 88.62 | 02-JAN-02:10 | 797.56 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.96 | 344.68 | 02-JAN-02:10 | 2351.00 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.48 | 167.95 | 02-JAN-02:10 | 1511.55 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.90 | 71.86 | 02-JAN-02:10 | 430.06 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.30 | 20.88 | 02-JAN-02:10 | 187.90 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 25.29 | 328.79 | 13-MAY-05:00 | 2264.29 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 10.95 | 63.51 | 01-JAN-13:10 | 1299.02 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 304.68 | 3569.19 | 03-JUN-05:00 | 23462.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 155.68 | 1457.78 | 03-JUN-05:00 | 13433.46 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 20.83 | 191.12 | 02-JAN-10:10 | 1761.93 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.36 | 64.68 | 01-JAN-11:10 | 1034.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 20.83 | 191.09 | 02-JAN-10:10 | 1761.73 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.35 | 64.68 | 01-JAN-11:10 | 1034.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 318.64 | 3125.26 | 02-JAN-10:10 | 25887.17 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 123.65 | 772.38 | 01-JAN-11:10 | 12358.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 318.73 | 3126.11 | 02-JAN-10:10 | 25894.25 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 123.68 | 772.59 | 01-JAN-11:10 | 12361.51 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 20.83 | 191.12 | 02-JAN-10:10 | 1761.93 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.36 | 64.68 | 01-JAN-11:10 | 1034.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 20.83 | 191.09 | 02-JAN-10:10 | 1761.73 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.35 | 64.68 | 01-JAN-11:10 | 1034.83 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 66.04 | 600.08 | 02-JAN-02:10 | 5400.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 66.04 | 600.08 | 02-JAN-02:10 | 5400.74 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.21 | 47.78 | 02-JAN-10:10 | 440.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.59 | 16.17 | 01-JAN-11:10 | 258.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.21 | 47.77 | 02-JAN-10:10 | 440.43 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.59 | 16.17 | 01-JAN-11:10 | 258.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 37.74 | 370.20 | 02-JAN-10:10 | 3066.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 14.65 | 91.49 | 01-JAN-11:10 | 1463.86 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 199.68 | 2452.07 | 27-MAY-05:00 | 9029.09 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 23.82 | 202.77 | 27-MAY-05:00 | 2281.19 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 199.68 | 2452.07 | 27-MAY-05:00 | 9029.09 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 23.82 | 202.77 | 27-MAY-05:00 | 2281.19 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 17.47 | 158.77 | 02-JAN-02:10 | 1428.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 17.47 | 158.77 | 02-JAN-02:10 | 1428.96 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.19 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 872.73 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 62.05 | 1114.61 | 03-FEB-23:30 | 3260.66 | 04-APR-07:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 1203.45 | 3298.20 | 07-JAN-04:00 | 167672.75 | 16-OCT-11:00 |
LowTempRefrigeration:Refrigeration:Electricity | 20.37 | 0.00 | 01-JAN-11:10 | 1914.36 | 02-DEC-11:50 |
MedTempRefrigeration:Refrigeration:Electricity | 34.58 | 928.34 | 07-JAN-02:40 | 1196.33 | 12-FEB-15:00 |
WaterSystems:Electricity | 90.75 | 1086.70 | 22-NOV-01:20 | 4739.17 | 05-JAN-07:10 |
Water Heater:WaterSystems:Electricity | 90.75 | 1086.70 | 22-NOV-01:20 | 4739.17 | 05-JAN-07:10 |
Fans:Electricity | 504.61 | 12858.67 | 08-JAN-08:10 | 26416.77 | 18-OCT-21:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 526.42 | 13485.05 | 13-FEB-14:40 | 27710.12 | 18-OCT-21:00 |
ExteriorEquipment:Electricity | 972.27 | 6510.93 | 02-JAN-02:20 | 62594.23 | 18-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.81 | 381.03 | 27-MAY-05:00 | 1300.47 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
ElectricityPurchased:Plant | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
Cogeneration:ElectricityPurchased | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
ElectricityNet:Plant | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
Cogeneration:ElectricityNet | 5356.35 | 66712.75 | 20-DEC-03:00 | 363531.40 | 29-SEP-19:10 |
General:Fans:Electricity | 504.61 | 12858.67 | 08-JAN-08:10 | 26416.77 | 18-OCT-21:00 |
ExteriorLights:Electricity | 182.88 | 0.00 | 01-JAN-07:00 | 11632.50 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 182.88 | 0.00 | 01-JAN-07:00 | 11632.50 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 1008.63 | 0.00 | 01-JAN-00:40 | 161033.06 | 16-OCT-11:00 |
General:Cooling:Electricity | 1008.63 | 0.00 | 01-JAN-00:40 | 161033.06 | 16-OCT-11:00 |
Pumps:Electricity | 49.12 | 111.02 | 28-FEB-15:20 | 3003.72 | 29-SEP-15:20 |
General:Pumps:Electricity | 49.12 | 111.02 | 28-FEB-15:20 | 3003.72 | 29-SEP-15:20 |
WIRED_LTG_ELECTRICITY | 29.14 | 0.00 | 01-JAN-00:10 | 2642.76 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4769.86 | 33427.23 | 17-OCT-00:10 | 409416.59 | 06-JAN-18:30 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 2981.01 | 15908.90 | 15-OCT-10:10 | 315499.11 | 29-MAR-22:50 |
WaterSystems:Gas | 2038.31 | 15908.90 | 03-JAN-16:10 | 175046.46 | 03-FEB-21:30 |
Water Heater:WaterSystems:Gas | 2038.31 | 15908.90 | 03-JAN-16:10 | 175046.46 | 03-FEB-21:30 |
Heating:Gas | 942.70 | 0.00 | 20-JAN-14:00 | 198067.45 | 08-JAN-07:00 |
Boiler:Heating:Gas | 942.70 | 0.00 | 20-JAN-14:00 | 198067.45 | 08-JAN-07:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3396.40 | 0.00 | 01-JAN-00:30 | 536223.61 | 18-AUG-15:10 |
PlantLoopCoolingDemand:HVAC | 3396.40 | 0.00 | 01-JAN-00:30 | 536223.61 | 18-AUG-15:10 |
CoolingCoils:PlantLoopCoolingDemand | 3396.40 | 0.00 | 01-JAN-00:30 | 536223.61 | 18-AUG-15:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 07-JUL-20:40 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 07-JUL-20:40 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 07-JUL-20:40 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-18:40 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 07-JUL-20:40 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 07-JUL-20:40 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 07-JUL-20:40 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 20-APR-18:40 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:10 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 18273.95 | 139109.87 | 31-MAR-10:30 | 2039410.00 | 18-AUG-15:10 |
EnergyTransfer:Building | 4947.43 | 90956.49 | 29-MAR-11:40 | 283772.71 | 29-SEP-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 733.86 | 12045.23 | 07-JAN-03:10 | 34820.36 | 15-OCT-10:40 |
Refrigeration:EnergyTransfer | 184.57 | 3944.64 | 07-JAN-02:40 | 10336.47 | 08-SEP-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 92.28 | 1972.32 | 07-JAN-02:40 | 5168.23 | 08-SEP-06:30 |
EnergyTransfer:Plant | 9283.40 | 22333.39 | 28-FEB-15:20 | 1252384.66 | 18-AUG-15:10 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.65 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 70.63 | 1735.03 | 07-JAN-02:40 | 2538.99 | 12-FEB-15:00 |
PlantLoopHeatingDemand:Facility | 1329.96 | 10652.30 | 17-OCT-00:10 | 184241.49 | 08-JAN-07:00 |
PlantLoopHeatingDemand:Plant | 683.24 | 8711.14 | 17-JUL-00:10 | 47513.53 | 03-FEB-08:00 |
WaterSystems:PlantLoopHeatingDemand | 683.24 | 8711.14 | 17-JUL-00:10 | 47513.53 | 03-FEB-08:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 414.98 | 10091.28 | 29-MAR-11:40 | 22206.19 | 08-JAN-07:00 |
Heating:EnergyTransfer | 10.66 | 0.00 | 01-JAN-08:10 | 13364.45 | 28-MAR-08:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 4844.48 | 87692.97 | 29-MAR-11:40 | 281114.74 | 29-SEP-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 414.98 | 10091.28 | 29-MAR-11:40 | 22206.19 | 08-JAN-07:00 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.88 | 0.64 | 29-MAR-08:20 | 3716.48 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 234.73 | 30-MAR-06:20 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 42.88 | 0.00 | 07-MAR-04:20 | 3716.48 | 16-OCT-12:10 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.06 | 796.64 | 29-MAR-12:10 | 1729.01 | 03-JAN-02:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 40.06 | 796.64 | 29-MAR-12:10 | 1729.01 | 03-JAN-02:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 35.69 | 329.11 | 30-MAR-04:10 | 1534.53 | 16-OCT-19:50 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 35.69 | 329.11 | 30-MAR-04:10 | 1534.53 | 16-OCT-19:50 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 14.51 | 0.77 | 30-MAR-02:00 | 624.17 | 16-OCT-19:50 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 44.34 | 30-MAR-04:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 14.51 | 0.00 | 30-MAR-02:10 | 624.17 | 16-OCT-19:50 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 611.96 | 10145.85 | 09-JAN-05:00 | 38042.07 | 29-SEP-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 611.96 | 10145.85 | 09-JAN-05:00 | 38042.07 | 29-SEP-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 226.68 | 1909.98 | 29-MAR-12:10 | 13326.90 | 19-NOV-11:00 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 226.68 | 1909.98 | 29-MAR-12:10 | 13326.90 | 19-NOV-11:00 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 845.48 | 16618.78 | 29-MAR-12:10 | 37808.56 | 09-JAN-06:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 845.48 | 16618.78 | 29-MAR-12:10 | 37808.56 | 09-JAN-06:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 41.16 | 0.00 | 01-JAN-08:10 | 9286.02 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 1.25 | 0.00 | 01-JAN-08:00 | 1923.70 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 39.91 | 0.00 | 01-JAN-00:10 | 9286.02 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 26.63 | 0.00 | 01-JAN-08:10 | 8731.76 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 2.23 | 0.00 | 01-JAN-08:10 | 2144.29 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 24.40 | 0.00 | 01-JAN-00:10 | 8731.76 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 283.54 | 0.00 | 01-JAN-00:10 | 46108.78 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 283.54 | 0.00 | 01-JAN-00:10 | 46108.78 | 16-OCT-12:10 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 365.37 | 0.00 | 01-JAN-08:10 | 63217.14 | 14-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 0.71 | 0.00 | 01-JAN-00:10 | 6965.93 | 16-MAR-15:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 364.66 | 0.00 | 01-JAN-08:10 | 63217.14 | 14-OCT-08:10 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 37.74 | 0.00 | 01-JAN-08:10 | 8757.53 | 15-OCT-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 1.39 | 0.00 | 01-JAN-07:10 | 2006.35 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 36.35 | 0.00 | 01-JAN-00:10 | 8757.53 | 15-OCT-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 26.17 | 0.00 | 01-JAN-08:10 | 9130.39 | 17-OCT-08:30 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 2.46 | 0.00 | 01-JAN-07:20 | 2074.81 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.70 | 0.00 | 01-JAN-00:10 | 9130.39 | 17-OCT-08:30 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 103.14 | 0.53 | 14-FEB-05:40 | 7108.00 | 16-OCT-13:50 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 0.26 | 0.00 | 01-JAN-07:30 | 1535.83 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 102.88 | 0.00 | 01-JAN-00:10 | 7108.00 | 16-OCT-13:50 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 11.61 | 0.00 | 01-JAN-08:10 | 2480.74 | 30-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 0.68 | 0.00 | 01-JAN-08:10 | 651.96 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.93 | 0.00 | 01-JAN-00:10 | 2480.74 | 30-SEP-15:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 8.02 | 0.00 | 01-JAN-08:10 | 2453.27 | 19-JUL-15:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 1.09 | 0.00 | 01-JAN-08:10 | 673.25 | 03-JAN-05:00 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.93 | 0.00 | 01-JAN-00:10 | 2453.27 | 19-JUL-15:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 76.12 | 0.00 | 01-JAN-08:10 | 12629.28 | 30-OCT-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 0.54 | 0.00 | 01-JAN-00:10 | 2380.93 | 30-MAR-04:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 75.58 | 0.00 | 01-JAN-00:20 | 12629.28 | 30-OCT-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 440.05 | 9277.66 | 29-MAR-11:40 | 20016.70 | 29-SEP-22:00 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 440.05 | 9277.66 | 29-MAR-11:40 | 20016.70 | 29-SEP-22:00 |
EnergyTransfer:Zone:DINING_FLR_6 | 483.58 | 10323.59 | 29-MAR-11:40 | 21797.81 | 29-SEP-21:50 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 483.58 | 10323.59 | 29-MAR-11:40 | 21797.81 | 29-SEP-21:50 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 641.57 | 9983.16 | 07-JAN-03:10 | 29826.22 | 15-OCT-10:40 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 78.20 | 2.02 | 11-JAN-04:00 | 3951.16 | 16-OCT-13:20 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 0.04 | 0.00 | 01-JAN-00:10 | 679.36 | 07-MAR-05:40 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 78.16 | 0.00 | 03-JAN-02:20 | 3951.16 | 16-OCT-13:20 |
WaterSystems:EnergyTransfer | 683.24 | 8711.14 | 17-JUL-00:10 | 47513.53 | 03-FEB-08:00 |
WaterUse:WaterSystems:EnergyTransfer | 683.24 | 8711.14 | 17-JUL-00:10 | 47513.53 | 03-FEB-08:00 |
EnergyTransfer:HVAC | 4043.13 | 5299.84 | 31-MAR-10:30 | 538360.64 | 18-AUG-15:10 |
HeatingCoils:EnergyTransfer | 646.72 | 0.00 | 20-JAN-14:00 | 157854.48 | 08-JAN-07:00 |
PlantLoopHeatingDemand:HVAC | 646.72 | 0.00 | 20-JAN-14:00 | 157854.48 | 08-JAN-07:00 |
HeatingCoils:PlantLoopHeatingDemand | 646.72 | 0.00 | 20-JAN-14:00 | 157854.48 | 08-JAN-07:00 |
CoolingCoils:EnergyTransfer | 3396.40 | 0.00 | 01-JAN-00:30 | 536223.61 | 18-AUG-15:10 |
Boilers:EnergyTransfer | 639.51 | 0.00 | 20-JAN-14:00 | 156510.15 | 08-JAN-07:00 |
Chillers:EnergyTransfer | 3429.87 | 0.00 | 01-JAN-00:40 | 545020.86 | 18-AUG-15:10 |
HeatRejection:EnergyTransfer | 4438.50 | 0.00 | 01-JAN-00:40 | 688806.02 | 18-AUG-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -414.976 | 0.000 | 0.000 | 149.587 | 165.597 | 143.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.318 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 0.003 | -42.880 | 0.000 | 0.000 | 15.851 | 8.422 | 10.186 | 18.953 | 0.000 | 0.162 | 1.477 | 0.000 | -7.904 | 0.000 | -4.269 | -0.000 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.000 | -40.063 | 0.000 | 0.000 | 17.350 | 9.753 | 11.795 | 0.000 | 0.000 | 0.039 | 2.138 | 0.000 | 0.000 | 0.000 | -1.013 | -0.000 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.000 | -611.959 | 0.000 | 0.000 | 11.731 | 3.975 | 658.148 | 0.000 | 0.000 | 0.150 | 0.000 | 0.000 | 0.000 | 0.000 | -3.094 | -58.951 |
CAFE_FLR_1 | 0.000 | 0.000 | 0.000 | -226.681 | 0.000 | 0.000 | 193.442 | 10.951 | 14.341 | 52.296 | 0.000 | 0.388 | 0.000 | 0.000 | -24.874 | 0.000 | -12.636 | -7.227 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.000 | -845.478 | 0.000 | 0.000 | 570.023 | 155.683 | 149.002 | 69.624 | 0.000 | 0.881 | 0.000 | 0.000 | -33.154 | 0.000 | -25.540 | -41.042 |
ROOM_1_FLR_3 | 1.250 | -28.519 | 0.000 | -11.394 | 0.000 | 0.000 | 9.666 | 10.355 | 10.478 | 39.632 | 0.000 | 0.218 | 0.001 | 0.000 | -18.859 | 0.000 | -6.685 | -6.144 |
ROOM_2_FLR_3 | 2.233 | -12.410 | 0.000 | -11.989 | 0.000 | 0.000 | 9.526 | 10.354 | 10.477 | 28.513 | 0.000 | 0.150 | 0.000 | 0.000 | -19.373 | 0.000 | -7.665 | -9.816 |
ROOM_3_MULT19_FLR_3 | 0.000 | -266.980 | 0.000 | -16.560 | 0.000 | 0.000 | 0.000 | 123.647 | 194.997 | 192.112 | 0.000 | 0.141 | 0.015 | 0.000 | -164.612 | 0.000 | -49.537 | -13.208 |
ROOM_4_MULT19_FLR_3 | 0.714 | -205.864 | 0.000 | -158.773 | 0.000 | 0.000 | 182.369 | 123.681 | 195.050 | 57.361 | 0.000 | 1.295 | 0.000 | 0.000 | -104.932 | 0.000 | -66.091 | -24.809 |
ROOM_5_FLR_3 | 1.390 | -24.945 | 0.000 | -11.406 | 0.000 | 0.000 | 9.660 | 10.355 | 10.478 | 36.490 | 0.000 | 0.214 | 0.001 | 0.000 | -18.354 | 0.000 | -6.715 | -7.167 |
ROOM_6_FLR_3 | 2.464 | -11.920 | 0.000 | -11.779 | 0.000 | 0.000 | 9.584 | 10.354 | 10.477 | 25.283 | 0.000 | 0.149 | 0.000 | 0.000 | -18.377 | 0.000 | -7.295 | -8.942 |
ROOM_1_FLR_6 | 0.680 | -8.075 | 0.000 | -2.853 | 0.000 | 0.000 | 2.416 | 2.589 | 2.620 | 9.735 | 0.000 | 0.055 | 0.000 | 0.000 | -4.729 | 0.000 | -1.734 | -0.703 |
ROOM_2_FLR_6 | 1.090 | -3.886 | 0.000 | -3.039 | 0.000 | 0.000 | 2.369 | 2.588 | 2.619 | 6.938 | 0.000 | 0.035 | 0.000 | 0.000 | -4.894 | 0.000 | -1.979 | -1.841 |
ROOM_3_MULT9_FLR_6 | 0.537 | -57.231 | 0.000 | -18.345 | 0.000 | 0.000 | 21.718 | 14.646 | 23.098 | 48.147 | 0.000 | 0.340 | 0.001 | 0.000 | -22.177 | 0.000 | -9.961 | -0.772 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.000 | -440.049 | 0.000 | 0.000 | 320.456 | 23.819 | 175.857 | 5.641 | 0.000 | 0.076 | 0.000 | 0.000 | -14.009 | 0.000 | -4.090 | -67.700 |
DINING_FLR_6 | 0.000 | 0.000 | 0.000 | -483.579 | 0.000 | 0.000 | 318.280 | 23.819 | 175.857 | 5.200 | 0.000 | 0.065 | 0.000 | 0.000 | -14.645 | 0.000 | -4.169 | -20.828 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -641.554 | 0.000 | 0.000 | 28.890 | 12.972 | 550.372 | 16.796 | 0.000 | 0.037 | 46.280 | 0.000 | -10.055 | 0.000 | -3.738 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 0.000 | -35.688 | 0.000 | 0.000 | 0.000 | 18.484 | 12.472 | 0.000 | 0.000 | 0.096 | 6.630 | 0.000 | 0.000 | 0.000 | -1.994 | -0.000 |
STORAGE_FLR_1 | 0.000 | 0.000 | 0.000 | -14.513 | 0.000 | 0.000 | 0.000 | 2.298 | 3.598 | 0.000 | 0.000 | 0.065 | 9.898 | 0.000 | 0.000 | 0.000 | -1.346 | 0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 0.259 | -102.883 | 0.000 | 0.000 | 0.000 | 66.043 | 0.000 | 34.077 | 0.000 | 0.338 | 28.491 | 0.000 | -20.632 | 0.000 | -5.694 | -0.001 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 0.042 | -78.161 | 0.000 | 0.000 | 0.000 | 17.474 | 0.000 | 16.230 | 0.000 | 0.103 | 56.602 | 0.000 | -9.668 | 0.000 | -2.622 | 0.000 |
Total Facility | 10.359 | -619.830 | 0.304 | -4224.603 | 0.000 | 0.000 | 1872.919 | 827.861 | 2365.030 | 663.029 | 0.000 | 4.996 | 151.534 | 0.000 | -511.247 | 0.000 | -227.866 | -312.469 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | -22202.81 | 0.00 | 0.00 | 5929.46 | 4513.94 | 4055.80 | 0.00 | 0.00 | 0.00 | 7703.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 16-OCT-12:10 | 0.00 | 0.00 | 0.00 | -3716.51 | 0.00 | 0.00 | 150.60 | 191.32 | 252.59 | 4580.75 | 0.00 | 255.29 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1714.03 |
RETAIL_2_FLR_1 | 03-JAN-01:55 | 0.00 | 0.00 | 0.00 | -1733.13 | 0.00 | 0.00 | 922.73 | 132.93 | 208.93 | 0.00 | 0.00 | 0.00 | 562.41 | 0.00 | -0.00 | 0.00 | -93.87 | 0.00 |
LAUNDRY_FLR_1 | 29-SEP-19:53 | 0.00 | 0.00 | 0.00 | -38042.22 | 0.00 | 0.00 | 408.87 | 325.08 | 44299.38 | 0.00 | 0.00 | 14.52 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7005.63 |
CAFE_FLR_1 | 19-NOV-11:00 | 0.00 | 0.00 | 0.00 | -13331.76 | 0.00 | 0.00 | 4947.96 | 95.26 | 406.43 | 13456.95 | 0.00 | 114.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5688.91 |
LOBBY_FLR_1 | 09-JAN-05:55 | 0.00 | 0.00 | 0.00 | -37927.67 | 0.00 | 0.00 | 30946.83 | 2985.21 | 3167.12 | 0.00 | 0.00 | 0.00 | 7022.83 | 0.00 | -3810.30 | 0.00 | -2384.02 | 0.00 |
ROOM_1_FLR_3 | 14-OCT-08:61 | 0.00 | -12194.67 | 0.00 | -729.02 | 0.00 | 0.00 | 130.71 | 241.49 | 653.23 | 2163.07 | 0.00 | 131.22 | 9603.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3 | 14-OCT-08:61 | 0.00 | -12215.67 | 0.00 | -757.63 | 0.00 | 0.00 | 127.19 | 241.46 | 653.15 | 1149.49 | 0.00 | 121.03 | 10680.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_3_MULT19_FLR_3 | 16-OCT-12:10 | 0.00 | -46109.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.38 | 2352.88 | 54055.79 | 0.00 | 1222.24 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -12294.08 |
ROOM_4_MULT19_FLR_3 | 14-OCT-08:61 | 0.00 | -79351.31 | 0.00 | -10782.76 | 0.00 | 0.00 | 2379.01 | 2884.36 | 12159.85 | 6081.89 | 0.00 | 567.84 | 66061.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3 | 14-OCT-08:61 | 0.00 | -10818.67 | 0.00 | -743.20 | 0.00 | 0.00 | 130.71 | 241.49 | 653.23 | 6659.94 | 0.00 | 126.13 | 3750.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3 | 17-OCT-08:11 | 0.00 | -12385.61 | 0.00 | -926.89 | 0.00 | 0.00 | 72.54 | 452.74 | 452.99 | 6436.79 | 0.00 | 43.36 | 5854.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_6 | 13-OCT-15:01 | 0.00 | -3160.93 | 0.00 | -182.86 | 0.00 | 0.00 | 58.82 | 20.70 | 50.05 | 1585.01 | 0.00 | 32.28 | 1596.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6 | 15-OCT-21:11 | 0.00 | -3170.40 | 0.00 | -185.54 | 0.00 | 0.00 | 80.29 | 219.90 | 89.55 | 0.00 | 0.00 | 0.00 | 3179.24 | 0.00 | -193.32 | 0.00 | -19.71 | 0.00 |
ROOM_3_MULT9_FLR_6 | 14-OCT-08:61 | 0.00 | -14130.77 | 0.00 | -1189.22 | 0.00 | 0.00 | 294.10 | 341.57 | 1439.98 | 4637.49 | 0.00 | 144.38 | 8462.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
BANQUET_FLR_6 | 29-SEP-21:12 | 0.00 | 0.00 | 0.00 | -20061.30 | 0.00 | 0.00 | 15645.86 | 1520.79 | 6747.90 | 0.00 | 0.00 | 7.51 | 0.00 | 0.00 | -198.84 | 0.00 | 0.00 | -3661.92 |
DINING_FLR_6 | 29-SEP-21:12 | 0.00 | 0.00 | 0.00 | -21864.92 | 0.00 | 0.00 | 15645.61 | 1520.79 | 6747.90 | 0.00 | 0.00 | 7.51 | 0.00 | 0.00 | -223.27 | 0.00 | 0.00 | -1833.63 |
KITCHEN_FLR_6 | 15-OCT-10:35 | 0.00 | 0.00 | 0.00 | -29825.68 | 0.00 | 0.00 | 464.32 | 353.60 | 24259.91 | 2137.00 | 0.00 | 108.00 | 2502.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 16-OCT-19:50 | 0.00 | 0.00 | 0.00 | -1534.53 | 0.00 | 0.00 | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -16.12 | -800.36 |
STORAGE_FLR_1 | 16-OCT-19:50 | 0.00 | 0.00 | 0.00 | -624.19 | 0.00 | 0.00 | 0.00 | 187.90 | 242.16 | 0.00 | 0.00 | 0.00 | 202.45 | 0.00 | -0.00 | 0.00 | -8.32 | 0.00 |
CORRIDOR_FLR_3 | 16-OCT-13:50 | 0.00 | 0.00 | 0.00 | -7107.95 | 0.00 | 0.00 | 0.00 | 1500.21 | 0.00 | 6297.73 | 0.00 | 338.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1028.49 |
CORRIDOR_FLR_6 | 16-OCT-13:20 | 0.00 | 0.00 | 0.00 | -3951.10 | 0.00 | 0.00 | 0.00 | 396.93 | 0.00 | 3399.32 | 0.00 | 141.43 | 13.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-OCT-08:61 | 0.00 | -170891.45 | 0.00 | -160928.99 | 0.00 | 0.00 | 48137.09 | 20470.57 | 89868.82 | 88817.46 | 0.00 | 4614.01 | 79912.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 30-MAR-06:15 | 0.00 | 0.00 | 236.28 | -0.00 | 0.00 | 0.00 | 359.18 | 382.63 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -651.83 | 0.00 | -366.25 | -393.03 |
RETAIL_2_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CAFE_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LOBBY_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_1_FLR_3 | 24-NOV-16:03 | 4826.39 | 427.76 | 0.00 | -427.76 | 0.00 | 0.00 | 250.96 | 82.80 | 200.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -275.66 | 0.00 | -618.28 | -4466.39 |
ROOM_2_FLR_3 | 17-DEC-16:03 | 4758.67 | 458.38 | 0.00 | -458.38 | 0.00 | 0.00 | 140.24 | 64.68 | 221.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -804.14 | 0.00 | -407.58 | -3973.09 |
ROOM_3_MULT19_FLR_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 16-MAR-15:05 | 25364.55 | 5802.78 | 0.00 | -5802.78 | 0.00 | 0.00 | 4804.24 | 988.92 | 3726.41 | 595.83 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13184.31 | -22295.63 |
ROOM_5_FLR_3 | 18-FEB-16:04 | 4545.81 | 425.91 | 0.00 | -425.91 | 0.00 | 0.00 | 132.35 | 64.68 | 221.25 | 671.73 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -675.65 | -4960.18 |
ROOM_6_FLR_3 | 07-FEB-16:03 | 4522.82 | 420.78 | 0.00 | -420.78 | 0.00 | 0.00 | 253.39 | 82.79 | 200.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -51.37 | 0.00 | -661.04 | -4346.75 |
ROOM_1_FLR_6 | 17-APR-15:04 | 1376.87 | 121.13 | 0.00 | -121.13 | 0.00 | 0.00 | 58.82 | 20.70 | 50.05 | 530.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -272.49 | -1764.05 |
ROOM_2_FLR_6 | 14-APR-15:04 | 1361.13 | 124.47 | 0.00 | -124.47 | 0.00 | 0.00 | 58.83 | 20.70 | 50.04 | 36.95 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -151.51 | -1376.14 |
ROOM_3_MULT9_FLR_6 | 24-NOV-16:04 | 6445.70 | 675.47 | 0.00 | -675.47 | 0.00 | 0.00 | 529.39 | 117.11 | 441.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -681.62 | 0.00 | -1294.84 | -5557.02 |
BANQUET_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 30-MAR-04:30 | 0.00 | 0.00 | 44.34 | -0.00 | 0.00 | 0.00 | 0.00 | 41.76 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -127.68 | -34.89 |
CORRIDOR_FLR_3 | 30-MAR-08:62 | 0.00 | 0.00 | 1613.47 | -0.00 | 0.00 | 0.00 | 0.00 | 2400.33 | 0.00 | 10.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -391.37 | -3633.22 |
CORRIDOR_FLR_6 | 07-MAR-05:40 | 0.00 | 0.00 | 679.35 | -0.00 | 0.00 | 0.00 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 232.75 | 0.00 | -999.94 | 0.00 | -229.70 | 0.00 |
Total Facility | 18-APR-15:04 | -71384.91 | 125668.78 | 0.00 | -125668.78 | 0.00 | 0.00 | 54191.36 | 13444.78 | 73912.59 | 29699.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20937.16 | -78925.93 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 20.3378 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 19.9866 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6536 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 11.6536 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3775 | 2.3775 | 1.3623 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2893 | 0.2893 | 0.1657 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2239 | 0.2239 | 0.1283 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3040 | 3.3040 | 1.8932 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2242 | 1.2242 | 0.7015 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.5236 | 4.5236 | 2.5920 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0076 | 2.0076 | 1.1504 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1074 | 2.1074 | 1.2075 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2187 | 2.2187 | 1.2713 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2217 | 0.2217 | 0.1270 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0939 | 0.0939 | 0.0538 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.6801 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5592 | 0.5592 | 0.3204 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 20.3378 | 19.9866 | 20.3378 | 11.6536 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3623 | 1.3623 | 1.3623 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1657 | 0.1657 | 0.1657 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1283 | 0.1283 | 0.1283 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8932 | 1.8932 | 1.8932 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7015 | 0.7015 | 0.7015 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5920 | 2.5920 | 2.5920 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1504 | 1.1504 | 1.1504 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2075 | 1.2075 | 1.2075 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2713 | 1.2713 | 1.2713 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1270 | 0.1270 | 0.1270 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0538 | 0.0538 | 0.0538 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6801 | 0.6801 | 0.6801 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3204 | 0.3204 | 0.3204 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6536 | 11.6536 | 11.6536 | 11.6536 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:43:11
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 108.17 |
Number of hours not met | 108.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 942.70 | 198067.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1008.63 | 161033.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 827.86 | 75078.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 182.88 | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.73 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.81 | 1300.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 504.61 | 26416.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 49.12 | 3003.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.75 | 4739.17 | 2038.31 | 175046.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.37 | 1914.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 34.58 | 1196.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1720.24 | 5356.35 |
Natural Gas | 1788.85 | 4769.86 |
Additional | 0.00 | 0.00 |
Total | 3509.09 | 10126.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.97 |
Space Heating | 0.00 |
Space Cooling | 88.90 |
Fans (All) | 44.48 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 472.12 |
Subtotal | 472.12 |
Natural Gas [MJ/m2] | |
Space Heating | 83.09 |
Service Water Heating | 179.66 |
Miscellaneous (All) | 420.43 |
Subtotal | 420.43 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.18 |
Space Heating | 9.31 |
Space Cooling | 9.96 |
Fans (All) | 4.98 |
Service Water Heating | 21.03 |
Receptacle Equipment | 34.04 |
Miscellaneous | 12.51 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 1660. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2737. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1362. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.153198E+12 |
February | 0.000 | 0.121889E+12 |
March | 0.000 | 0.164411E+12 |
April | 0.000 | 0.749596E+11 |
May | 0.000 | 0.690632E+11 |
June | 0.000 | 0.239838E+11 |
July | 0.000 | 0.156855E+11 |
August | 0.000 | 0.146396E+11 |
September | 0.000 | 0.184074E+11 |
October | 0.000 | 0.343242E+11 |
November | 0.000 | 0.102609E+12 |
December | 0.000 | 0.149527E+12 |
Annual Sum or Average | 0.942697E+12 | |
Minimum of Months | 0.000 | 0.146396E+11 |
Maximum of Months | 0.000 | 0.164411E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367456E+11 | 22206.19 | 08-JAN-07:00 | 1.00 | -0.2 | 0.725064E+10 | 4664.24 | 06-JAN-22:10 | 9.17 | 4.09 |
February | 0.301103E+11 | 16756.71 | 04-FEB-05:55 | 5.00 | 0.20 | 0.632232E+10 | 4532.35 | 01-FEB-22:10 | 13.00 | 11.77 |
March | 0.328690E+11 | 17574.06 | 08-MAR-02:00 | 4.00 | 3.53 | 0.685653E+10 | 4374.21 | 06-MAR-22:10 | 10.17 | 8.07 |
April | 0.318335E+11 | 14383.75 | 26-APR-07:45 | 21.33 | 16.21 | 0.649691E+10 | 4241.25 | 06-APR-21:10 | 12.17 | 11.07 |
May | 0.329342E+11 | 14226.52 | 28-MAY-10:00 | 21.00 | 15.41 | 0.666037E+10 | 4249.09 | 12-MAY-21:10 | 11.83 | 11.29 |
June | 0.321089E+11 | 14281.13 | 29-JUN-18:10 | 21.50 | 18.38 | 0.628176E+10 | 4110.92 | 01-JUN-21:10 | 13.83 | 13.26 |
July | 0.356708E+11 | 14859.82 | 19-JUL-18:50 | 21.33 | 18.46 | 0.652075E+10 | 4125.91 | 07-JUL-21:10 | 15.17 | 13.85 |
August | 0.361342E+11 | 14771.21 | 14-AUG-18:50 | 21.17 | 18.40 | 0.658511E+10 | 4152.57 | 25-AUG-21:10 | 16.08 | 16.08 |
September | 0.358712E+11 | 16247.99 | 21-SEP-21:10 | 21.17 | 19.64 | 0.665573E+10 | 4386.44 | 19-SEP-21:10 | 13.83 | 12.17 |
October | 0.381922E+11 | 16137.99 | 16-OCT-19:50 | 21.33 | 13.33 | 0.707325E+10 | 4553.25 | 27-OCT-21:10 | 13.00 | 10.71 |
November | 0.358960E+11 | 16371.78 | 29-NOV-23:00 | 7.00 | 4.65 | 0.724596E+10 | 4755.66 | 17-NOV-22:10 | 11.00 | 9.96 |
December | 0.366099E+11 | 18038.61 | 03-DEC-01:00 | 5.00 | 5.00 | 0.731535E+10 | 4728.39 | 01-DEC-22:10 | 10.83 | 10.40 |
Annual Sum or Average | 0.414976E+12 | 0.812647E+11 | ||||||||
Minimum of Months | 0.301103E+11 | 14226.52 | 1.00 | -0.2 | 0.628176E+10 | 4110.92 | 9.17 | 4.09 | ||
Maximum of Months | 0.381922E+11 | 22206.19 | 21.50 | 19.64 | 0.731535E+10 | 4755.66 | 16.08 | 16.08 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351384E+10 | 3106.58 | 14-JAN-12:40 | 25.33 | 11.67 | 0.655265E+09 | 419.75 | 20-JAN-22:10 | 13.17 | 13.17 |
February | 0.284901E+10 | 2545.01 | 02-FEB-12:40 | 19.33 | 12.34 | 0.585830E+09 | 423.94 | 01-FEB-22:10 | 13.00 | 11.77 |
March | 0.275486E+10 | 2198.59 | 11-MAR-13:10 | 24.00 | 13.62 | 0.637423E+09 | 412.71 | 24-MAR-21:10 | 13.00 | 11.77 |
April | 0.320290E+10 | 1943.62 | 08-APR-12:50 | 22.17 | 16.55 | 0.614252E+09 | 402.05 | 26-APR-21:10 | 16.00 | 15.39 |
May | 0.306569E+10 | 1794.98 | 04-MAY-12:40 | 23.33 | 16.62 | 0.626866E+09 | 402.77 | 03-MAY-21:10 | 16.00 | 14.66 |
June | 0.342372E+10 | 1765.04 | 29-JUN-18:10 | 21.50 | 18.38 | 0.610398E+09 | 397.77 | 28-JUN-21:10 | 17.00 | 16.37 |
July | 0.399658E+10 | 1830.08 | 19-JUL-18:30 | 22.00 | 18.69 | 0.634570E+09 | 405.49 | 19-JUL-21:10 | 18.00 | 17.89 |
August | 0.419351E+10 | 1904.53 | 27-AUG-12:00 | 23.00 | 18.42 | 0.646639E+09 | 410.89 | 18-AUG-21:10 | 19.00 | 17.66 |
September | 0.400470E+10 | 2940.13 | 30-SEP-13:10 | 32.00 | 16.95 | 0.633098E+09 | 460.69 | 29-SEP-21:10 | 24.58 | 13.49 |
October | 0.442690E+10 | 3716.48 | 16-OCT-12:10 | 35.68 | 17.44 | 0.674040E+09 | 463.77 | 16-OCT-21:10 | 18.33 | 11.04 |
November | 0.369211E+10 | 3397.90 | 19-NOV-12:30 | 26.50 | 15.20 | 0.640881E+09 | 427.05 | 20-NOV-22:10 | 14.00 | 12.83 |
December | 0.375590E+10 | 3197.23 | 19-DEC-12:50 | 25.83 | 11.50 | 0.663429E+09 | 429.25 | 05-DEC-22:10 | 17.17 | 9.43 |
Annual Sum or Average | 0.428797E+11 | 0.762269E+10 | ||||||||
Minimum of Months | 0.275486E+10 | 1765.04 | 19.33 | 11.50 | 0.585830E+09 | 397.77 | 13.00 | 9.43 | ||
Maximum of Months | 0.442690E+10 | 3716.48 | 35.68 | 18.69 | 0.674040E+09 | 463.77 | 24.58 | 17.89 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328801E+10 | 1733.05 | 03-JAN-01:55 | 3.00 | 2.55 | 0.824619E+09 | 554.75 | 06-JAN-22:10 | 9.17 | 4.09 |
February | 0.286429E+10 | 1578.94 | 04-FEB-05:55 | 5.00 | 0.20 | 0.756601E+09 | 563.90 | 02-FEB-22:10 | 11.00 | 8.45 |
March | 0.313211E+10 | 1616.52 | 08-MAR-02:00 | 4.00 | 3.53 | 0.824070E+09 | 553.12 | 24-MAR-21:10 | 13.00 | 11.77 |
April | 0.317962E+10 | 1458.06 | 26-APR-20:20 | 16.67 | 15.19 | 0.809442E+09 | 547.04 | 28-APR-21:10 | 14.00 | 11.20 |
May | 0.328302E+10 | 1477.11 | 04-MAY-21:10 | 17.00 | 15.07 | 0.829006E+09 | 542.04 | 19-MAY-21:10 | 12.17 | 11.62 |
June | 0.335953E+10 | 1500.75 | 29-JUN-18:30 | 20.50 | 17.88 | 0.801802E+09 | 539.96 | 30-JUN-21:10 | 16.02 | 14.99 |
July | 0.363284E+10 | 1553.90 | 19-JUL-19:00 | 21.00 | 18.35 | 0.827771E+09 | 538.96 | 26-JUL-21:10 | 17.00 | 16.26 |
August | 0.367127E+10 | 1568.28 | 18-AUG-21:10 | 19.00 | 17.66 | 0.836528E+09 | 541.82 | 25-AUG-21:10 | 16.08 | 16.08 |
September | 0.347723E+10 | 1695.05 | 29-SEP-21:10 | 24.58 | 13.49 | 0.811086E+09 | 558.64 | 29-SEP-21:10 | 24.58 | 13.49 |
October | 0.363400E+10 | 1694.67 | 16-OCT-19:50 | 21.33 | 13.33 | 0.847028E+09 | 569.50 | 17-OCT-21:10 | 18.00 | 14.86 |
November | 0.321836E+10 | 1554.11 | 29-NOV-23:00 | 7.00 | 4.65 | 0.824883E+09 | 563.76 | 22-NOV-22:10 | 11.17 | 2.65 |
December | 0.332236E+10 | 1590.25 | 03-DEC-01:00 | 5.00 | 5.00 | 0.839504E+09 | 557.48 | 28-DEC-22:19 | 9.67 | 3.82 |
Annual Sum or Average | 0.400626E+11 | 0.983234E+10 | ||||||||
Minimum of Months | 0.286429E+10 | 1458.06 | 3.00 | 0.20 | 0.756601E+09 | 538.96 | 9.17 | 2.65 | ||
Maximum of Months | 0.367127E+10 | 1733.05 | 24.58 | 18.35 | 0.847028E+09 | 569.50 | 24.58 | 16.26 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273171E+10 | 1499.93 | 06-JAN-23:00 | 5.00 | 2.02 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.247368E+10 | 1404.86 | 04-FEB-05:55 | 5.00 | 0.20 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.262478E+10 | 1356.73 | 07-MAR-23:00 | 6.00 | 5.04 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.280528E+10 | 1323.51 | 26-APR-07:45 | 21.33 | 16.21 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.297804E+10 | 1321.51 | 04-MAY-09:30 | 21.00 | 15.48 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.311879E+10 | 1387.20 | 29-JUN-18:10 | 21.50 | 18.38 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.339932E+10 | 1438.29 | 19-JUL-19:00 | 21.00 | 18.35 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.339890E+10 | 1416.68 | 19-AUG-18:50 | 21.33 | 18.21 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.316684E+10 | 1514.19 | 29-SEP-21:00 | 24.60 | 13.47 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.332004E+10 | 1534.53 | 16-OCT-19:50 | 21.33 | 13.33 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.282456E+10 | 1348.47 | 29-NOV-23:00 | 7.00 | 4.65 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.284584E+10 | 1454.60 | 03-DEC-01:00 | 5.00 | 5.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.356878E+11 | 0.00 | ||||||||
Minimum of Months | 0.247368E+10 | 1321.51 | 5.00 | 0.20 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.339932E+10 | 1534.53 | 24.60 | 18.38 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104488E+10 | 603.65 | 06-JAN-23:00 | 5.00 | 2.02 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.976235E+09 | 556.92 | 04-FEB-05:45 | 5.67 | 0.57 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.988976E+09 | 542.04 | 23-MAR-09:50 | 21.50 | 16.14 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.114439E+10 | 553.07 | 30-APR-11:00 | 26.00 | 17.27 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.122319E+10 | 558.87 | 04-MAY-09:40 | 21.33 | 15.79 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.129626E+10 | 575.77 | 30-JUN-08:35 | 21.33 | 17.66 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.142187E+10 | 588.74 | 19-JUL-18:50 | 21.33 | 18.46 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.142174E+10 | 582.44 | 19-AUG-18:50 | 21.33 | 18.21 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.131997E+10 | 617.27 | 29-SEP-21:10 | 24.58 | 13.49 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.138577E+10 | 624.17 | 16-OCT-19:50 | 21.33 | 13.33 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.115872E+10 | 570.89 | 19-NOV-13:10 | 26.67 | 14.98 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.113051E+10 | 583.84 | 03-DEC-00:45 | 5.33 | 5.33 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.145125E+11 | 0.00 | ||||||||
Minimum of Months | 0.976235E+09 | 542.04 | 5.00 | 0.57 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.142187E+10 | 624.17 | 26.67 | 18.46 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.512764E+11 | 37255.41 | 24-JAN-21:00 | 17.00 | 11.90 | 0.549621E+09 | 400.05 | 06-JAN-22:10 | 9.17 | 4.09 |
February | 0.461746E+11 | 37072.96 | 23-FEB-21:00 | 14.00 | 11.71 | 0.503867E+09 | 399.40 | 06-FEB-22:10 | 9.50 | 6.34 |
March | 0.512030E+11 | 37406.25 | 23-MAR-20:00 | 14.00 | 13.42 | 0.556517E+09 | 397.79 | 14-MAR-21:10 | 9.83 | 9.24 |
April | 0.501164E+11 | 37556.82 | 26-APR-20:00 | 17.00 | 15.07 | 0.537437E+09 | 384.83 | 06-APR-21:10 | 12.17 | 11.07 |
May | 0.518959E+11 | 37559.91 | 04-MAY-20:00 | 17.00 | 15.07 | 0.554104E+09 | 392.30 | 10-MAY-21:10 | 11.00 | 9.40 |
June | 0.508042E+11 | 37537.22 | 30-JUN-20:00 | 16.00 | 15.39 | 0.529601E+09 | 383.27 | 12-JUN-21:10 | 12.33 | 11.13 |
July | 0.528307E+11 | 37742.32 | 19-JUL-20:00 | 19.00 | 18.34 | 0.540710E+09 | 381.52 | 11-JUL-21:00 | 16.00 | 14.12 |
August | 0.530928E+11 | 37692.12 | 18-AUG-20:00 | 19.00 | 17.66 | 0.543037E+09 | 381.52 | 01-AUG-21:30 | 16.00 | 14.76 |
September | 0.507498E+11 | 38042.16 | 29-SEP-19:53 | 25.00 | 13.56 | 0.526306E+09 | 381.54 | 01-SEP-22:10 | 16.00 | 14.03 |
October | 0.525563E+11 | 37954.21 | 16-OCT-20:00 | 21.00 | 13.05 | 0.545143E+09 | 384.23 | 11-OCT-21:10 | 12.17 | 9.11 |
November | 0.499709E+11 | 37227.59 | 20-NOV-21:00 | 14.00 | 13.42 | 0.538413E+09 | 395.13 | 22-NOV-22:10 | 11.17 | 2.65 |
December | 0.512901E+11 | 37346.75 | 05-DEC-21:00 | 16.00 | 9.07 | 0.552865E+09 | 399.80 | 28-DEC-22:10 | 9.83 | 3.96 |
Annual Sum or Average | 0.611961E+12 | 0.647762E+10 | ||||||||
Minimum of Months | 0.461746E+11 | 37072.96 | 14.00 | 9.07 | 0.503867E+09 | 381.52 | 9.17 | 2.65 | ||
Maximum of Months | 0.530928E+11 | 38042.16 | 25.00 | 18.34 | 0.556517E+09 | 400.05 | 16.00 | 14.76 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194675E+11 | 12221.93 | 14-JAN-12:40 | 25.33 | 11.67 | 0.983267E+10 | 6460.60 | 20-JAN-22:00 | 14.00 | 14.00 |
February | 0.163650E+11 | 9889.20 | 04-FEB-12:30 | 21.00 | 8.23 | 0.889371E+10 | 6460.67 | 02-FEB-22:00 | 11.00 | 8.84 |
March | 0.173542E+11 | 9366.01 | 11-MAR-13:10 | 24.00 | 13.62 | 0.955367E+10 | 6387.96 | 24-MAR-21:40 | 13.00 | 11.48 |
April | 0.175771E+11 | 8420.21 | 08-APR-12:40 | 22.33 | 16.69 | 0.934383E+10 | 6248.58 | 11-APR-21:40 | 13.33 | 13.33 |
May | 0.175836E+11 | 8273.10 | 04-MAY-22:00 | 17.00 | 15.07 | 0.948123E+10 | 6193.97 | 04-MAY-22:10 | 16.83 | 15.02 |
June | 0.181180E+11 | 8170.61 | 27-JUN-22:00 | 17.00 | 16.37 | 0.922229E+10 | 6122.87 | 27-JUN-22:10 | 17.00 | 16.37 |
July | 0.198473E+11 | 8540.90 | 31-JUL-21:20 | 18.90 | 17.79 | 0.953153E+10 | 6168.70 | 19-JUL-22:10 | 18.00 | 17.35 |
August | 0.204271E+11 | 8677.99 | 18-AUG-22:00 | 19.00 | 17.66 | 0.972742E+10 | 6226.00 | 25-AUG-22:10 | 16.00 | 16.00 |
September | 0.197204E+11 | 10917.47 | 30-SEP-12:00 | 32.00 | 17.08 | 0.953589E+10 | 6462.56 | 29-SEP-21:30 | 24.55 | 13.53 |
October | 0.213028E+11 | 12803.85 | 15-OCT-12:00 | 32.00 | 16.86 | 0.100933E+11 | 6462.55 | 16-OCT-21:30 | 19.00 | 11.07 |
November | 0.190079E+11 | 13326.90 | 19-NOV-11:00 | 26.00 | 15.05 | 0.978438E+10 | 6461.44 | 20-NOV-23:19 | 14.00 | 12.83 |
December | 0.199088E+11 | 12151.28 | 16-DEC-13:00 | 26.00 | 13.28 | 0.100137E+11 | 6462.30 | 05-DEC-22:30 | 17.50 | 9.40 |
Annual Sum or Average | 0.226680E+12 | 0.115014E+12 | ||||||||
Minimum of Months | 0.163650E+11 | 8170.61 | 17.00 | 8.23 | 0.889371E+10 | 6122.87 | 11.00 | 8.84 | ||
Maximum of Months | 0.213028E+11 | 13326.90 | 32.00 | 17.79 | 0.100933E+11 | 6462.56 | 24.55 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.705793E+11 | 37926.91 | 09-JAN-05:55 | 2.00 | -0.1 | 0.292583E+11 | 19183.61 | 31-JAN-22:10 | 11.82 | 10.56 |
February | 0.613309E+11 | 33601.88 | 04-FEB-05:55 | 5.00 | 0.20 | 0.267964E+11 | 19183.60 | 21-FEB-22:10 | 10.67 | 10.13 |
March | 0.668936E+11 | 34075.91 | 08-MAR-02:00 | 4.00 | 3.53 | 0.291436E+11 | 19182.78 | 24-MAR-21:19 | 13.00 | 11.67 |
April | 0.668673E+11 | 30293.99 | 26-APR-22:00 | 16.00 | 15.39 | 0.283969E+11 | 19079.22 | 06-APR-21:30 | 12.50 | 11.39 |
May | 0.689009E+11 | 31112.39 | 04-MAY-21:10 | 17.00 | 15.07 | 0.290909E+11 | 18973.93 | 26-MAY-22:10 | 11.00 | 8.45 |
June | 0.701613E+11 | 30947.52 | 29-JUN-18:30 | 20.50 | 17.88 | 0.280649E+11 | 18717.79 | 09-JUN-21:30 | 14.00 | 13.13 |
July | 0.753520E+11 | 32208.32 | 31-JUL-21:10 | 18.95 | 17.72 | 0.287971E+11 | 18649.31 | 19-JUL-22:10 | 18.00 | 17.35 |
August | 0.761921E+11 | 32496.26 | 18-AUG-21:10 | 19.00 | 17.66 | 0.291100E+11 | 18788.68 | 25-AUG-22:10 | 16.00 | 16.00 |
September | 0.727253E+11 | 34999.63 | 29-SEP-21:10 | 24.58 | 13.49 | 0.283662E+11 | 19181.81 | 29-SEP-22:10 | 24.48 | 13.58 |
October | 0.765553E+11 | 35682.04 | 16-OCT-22:00 | 20.00 | 11.07 | 0.297350E+11 | 19185.90 | 17-OCT-21:30 | 18.00 | 14.66 |
November | 0.687308E+11 | 32647.20 | 29-NOV-23:00 | 7.00 | 4.65 | 0.291597E+11 | 19183.56 | 28-NOV-22:00 | 9.00 | 4.94 |
December | 0.711879E+11 | 32962.90 | 03-DEC-01:00 | 5.00 | 5.00 | 0.297473E+11 | 19183.57 | 21-DEC-22:10 | 10.67 | 10.67 |
Annual Sum or Average | 0.845477E+12 | 0.345666E+12 | ||||||||
Minimum of Months | 0.613309E+11 | 30293.99 | 2.00 | -0.1 | 0.267964E+11 | 18649.31 | 9.00 | 4.94 | ||
Maximum of Months | 0.765553E+11 | 37926.91 | 24.58 | 17.88 | 0.297473E+11 | 19185.90 | 24.48 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.480137E+09 | 3181.31 | 14-JAN-16:01 | 23.00 | 12.39 | 97812372.82 | 56.69 | 18-JAN-23:10 | 15.67 | 12.72 |
February | 0.413876E+09 | 3188.40 | 03-FEB-16:01 | 20.50 | 10.02 | 87981804.52 | 56.69 | 21-FEB-22:10 | 10.67 | 10.13 |
March | 0.434926E+09 | 2857.55 | 19-MAR-15:01 | 18.00 | 14.46 | 97398561.55 | 56.69 | 03-MAR-22:10 | 12.83 | 11.80 |
April | 0.788052E+09 | 2953.86 | 01-APR-18:02 | 17.83 | 8.82 | 94977102.17 | 56.69 | 26-APR-23:40 | 15.33 | 14.53 |
May | 0.760554E+09 | 2913.94 | 24-MAY-08:61 | 18.00 | 8.77 | 98078584.03 | 56.69 | 24-MAY-23:10 | 16.00 | 14.12 |
June | 0.100862E+10 | 2915.76 | 15-JUN-15:01 | 22.00 | 17.30 | 95245737.32 | 56.69 | 26-JUN-00:10 | 17.00 | 15.07 |
July | 0.135643E+10 | 2916.46 | 16-JUL-15:01 | 21.83 | 16.78 | 98674082.57 | 56.69 | 20-JUL-01:39 | 17.00 | 17.00 |
August | 0.136760E+10 | 2916.04 | 09-AUG-15:01 | 22.83 | 18.93 | 98829106.14 | 56.69 | 18-AUG-21:10 | 19.00 | 17.66 |
September | 0.111655E+10 | 2889.92 | 05-SEP-15:01 | 20.83 | 17.12 | 95367676.53 | 56.69 | 29-SEP-21:19 | 24.57 | 13.51 |
October | 0.111570E+10 | 3230.97 | 14-OCT-08:61 | 27.67 | 12.98 | 98438108.69 | 56.69 | 17-OCT-21:19 | 18.00 | 14.76 |
November | 0.594987E+09 | 3152.70 | 27-NOV-16:01 | 19.67 | 7.52 | 94907947.33 | 56.69 | 10-NOV-22:30 | 15.00 | 13.80 |
December | 0.541170E+09 | 3189.40 | 19-DEC-16:01 | 20.67 | 8.08 | 97900102.57 | 56.69 | 18-DEC-22:40 | 17.33 | 5.99 |
Annual Sum or Average | 0.997860E+10 | 0.115561E+10 | ||||||||
Minimum of Months | 0.413876E+09 | 2857.55 | 17.83 | 7.52 | 87981804.52 | 56.69 | 10.67 | 5.99 | ||
Maximum of Months | 0.136760E+10 | 3230.97 | 27.67 | 18.93 | 98829106.14 | 56.69 | 24.57 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158814E+09 | 3089.05 | 14-JAN-16:01 | 23.00 | 12.39 | 96817269.77 | 62.83 | 18-JAN-22:19 | 16.67 | 13.33 |
February | 0.187374E+09 | 3095.48 | 03-FEB-16:01 | 20.50 | 10.02 | 87341053.72 | 56.69 | 01-FEB-22:30 | 13.00 | 11.58 |
March | 0.244647E+09 | 2780.87 | 09-MAR-16:01 | 17.83 | 14.30 | 97333545.73 | 56.69 | 24-MAR-21:30 | 13.00 | 11.58 |
April | 0.532901E+09 | 2925.30 | 27-APR-18:21 | 15.00 | 13.23 | 97214604.60 | 70.65 | 26-APR-21:19 | 16.00 | 15.39 |
May | 0.600177E+09 | 2947.94 | 24-MAY-08:11 | 18.00 | 8.95 | 0.100917E+09 | 70.64 | 03-MAY-21:19 | 16.00 | 14.55 |
June | 0.742580E+09 | 2853.50 | 18-JUN-15:01 | 22.83 | 17.77 | 0.101763E+09 | 74.37 | 29-JUN-18:10 | 21.50 | 18.38 |
July | 0.957335E+09 | 2865.08 | 17-JUL-15:01 | 24.00 | 18.81 | 0.108722E+09 | 76.40 | 19-JUL-21:19 | 18.00 | 17.79 |
August | 0.917480E+09 | 2864.14 | 02-AUG-15:01 | 22.83 | 18.37 | 0.107914E+09 | 75.43 | 18-AUG-21:19 | 19.00 | 17.66 |
September | 0.718527E+09 | 2866.94 | 13-SEP-15:01 | 22.83 | 18.36 | 99768541.30 | 74.87 | 29-SEP-21:10 | 24.58 | 13.49 |
October | 0.631698E+09 | 3243.38 | 14-OCT-08:61 | 27.67 | 12.98 | 0.101882E+09 | 72.23 | 16-OCT-21:19 | 18.67 | 11.06 |
November | 0.240376E+09 | 3063.18 | 27-NOV-16:01 | 19.67 | 7.52 | 94285068.92 | 59.76 | 09-NOV-22:19 | 16.00 | 14.97 |
December | 0.168313E+09 | 3095.64 | 19-DEC-16:01 | 20.67 | 8.08 | 96865138.60 | 62.78 | 05-DEC-22:19 | 17.33 | 9.42 |
Annual Sum or Average | 0.610022E+10 | 0.119082E+10 | ||||||||
Minimum of Months | 0.158814E+09 | 2780.87 | 15.00 | 7.52 | 87341053.72 | 56.69 | 13.00 | 9.42 | ||
Maximum of Months | 0.957335E+09 | 3243.38 | 27.67 | 18.81 | 0.108722E+09 | 76.40 | 24.58 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415341E+09 | 553.98 | 14-JAN-12:20 | 25.67 | 11.73 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.260264E+09 | 478.40 | 02-FEB-12:30 | 19.50 | 11.89 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.186062E+09 | 375.07 | 11-MAR-12:50 | 24.00 | 13.80 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.191618E+09 | 253.50 | 04-APR-15:03 | 19.67 | 15.54 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.129417E+09 | 209.17 | 04-MAY-20:40 | 17.00 | 15.07 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.179901E+09 | 203.46 | 24-JUN-08:00 | 19.00 | 14.75 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.261486E+09 | 240.86 | 23-JUL-08:00 | 23.00 | 18.99 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.328253E+09 | 271.88 | 19-AUG-15:03 | 25.83 | 18.85 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.374445E+09 | 469.13 | 30-SEP-13:00 | 32.00 | 16.82 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.507058E+09 | 606.69 | 16-OCT-12:10 | 35.68 | 17.44 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.424320E+09 | 592.81 | 19-NOV-10:00 | 26.00 | 13.87 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.472649E+09 | 571.67 | 19-DEC-12:30 | 25.50 | 11.38 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.373081E+10 | 0.00 | ||||||||
Minimum of Months | 0.129417E+09 | 203.46 | 17.00 | 11.38 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.507058E+09 | 606.69 | 35.68 | 18.99 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.281331E+09 | 1077.05 | 15-JAN-16:01 | 21.83 | 10.36 | 97225673.66 | 67.53 | 17-JAN-22:19 | 17.67 | 13.74 |
February | 0.284175E+09 | 1050.13 | 03-FEB-16:01 | 20.50 | 10.02 | 87570713.98 | 57.24 | 22-FEB-04:19 | 8.67 | 7.27 |
March | 0.323559E+09 | 1066.22 | 11-MAR-09:11 | 21.00 | 12.70 | 97211259.67 | 57.26 | 12-MAR-03:00 | 8.00 | 6.06 |
April | 0.398173E+09 | 1059.90 | 01-APR-15:02 | 22.83 | 11.14 | 95090944.78 | 68.20 | 26-APR-21:19 | 16.00 | 15.39 |
May | 0.449487E+09 | 1056.32 | 24-MAY-08:11 | 18.00 | 8.95 | 98772692.43 | 68.63 | 04-MAY-21:19 | 17.00 | 15.07 |
June | 0.476720E+09 | 1025.09 | 24-JUN-08:11 | 19.67 | 15.16 | 98435104.13 | 71.43 | 28-JUN-21:19 | 17.00 | 16.37 |
July | 0.546954E+09 | 1034.62 | 04-JUL-08:11 | 20.00 | 15.15 | 0.104357E+09 | 74.58 | 19-JUL-21:19 | 18.00 | 17.79 |
August | 0.527306E+09 | 991.77 | 01-AUG-15:01 | 21.83 | 16.79 | 0.104053E+09 | 73.83 | 18-AUG-21:19 | 19.00 | 17.66 |
September | 0.449909E+09 | 987.30 | 01-SEP-15:01 | 20.67 | 15.85 | 97693229.65 | 73.46 | 29-SEP-21:10 | 24.58 | 13.49 |
October | 0.460473E+09 | 1185.99 | 14-OCT-08:61 | 27.67 | 12.98 | 0.101095E+09 | 74.39 | 04-OCT-21:19 | 21.00 | 18.97 |
November | 0.316771E+09 | 1105.10 | 19-NOV-09:11 | 24.67 | 12.98 | 94077738.37 | 63.56 | 09-NOV-22:19 | 16.00 | 14.97 |
December | 0.283246E+09 | 1083.22 | 05-DEC-09:11 | 24.67 | 12.20 | 97064061.81 | 66.11 | 05-DEC-22:19 | 17.33 | 9.42 |
Annual Sum or Average | 0.479810E+10 | 0.117265E+10 | ||||||||
Minimum of Months | 0.281331E+09 | 987.30 | 18.00 | 8.95 | 87570713.98 | 57.24 | 8.00 | 6.06 | ||
Maximum of Months | 0.546954E+09 | 1185.99 | 27.67 | 16.79 | 0.104357E+09 | 74.58 | 24.58 | 18.97 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.504742E+09 | 2803.42 | 14-JAN-16:01 | 23.00 | 12.39 | 98096001.51 | 56.69 | 20-JAN-22:30 | 13.50 | 13.50 |
February | 0.384127E+09 | 2817.30 | 01-FEB-09:01 | 22.33 | 11.83 | 88064133.94 | 56.69 | 15-FEB-22:10 | 13.83 | 12.18 |
March | 0.425559E+09 | 2534.39 | 23-MAR-15:01 | 21.83 | 17.36 | 97584131.90 | 56.69 | 23-MAR-22:10 | 12.83 | 12.37 |
April | 0.702993E+09 | 2794.27 | 02-APR-08:61 | 17.33 | 8.64 | 95178017.74 | 56.69 | 11-APR-21:49 | 13.17 | 13.17 |
May | 0.649445E+09 | 2800.76 | 24-MAY-08:61 | 18.00 | 8.77 | 98158159.84 | 56.69 | 02-MAY-22:00 | 17.00 | 15.07 |
June | 0.841696E+09 | 2540.24 | 22-JUN-08:62 | 19.33 | 15.39 | 95304704.94 | 56.69 | 23-JUN-23:10 | 17.00 | 14.50 |
July | 0.120637E+10 | 2601.55 | 23-JUL-08:61 | 23.33 | 19.10 | 98896188.72 | 56.69 | 20-JUL-01:10 | 17.00 | 17.00 |
August | 0.127337E+10 | 2533.51 | 06-AUG-08:61 | 22.33 | 18.29 | 99022161.19 | 56.69 | 18-AUG-21:10 | 19.00 | 17.66 |
September | 0.948731E+09 | 2563.33 | 11-SEP-15:01 | 22.00 | 16.75 | 95292029.08 | 56.69 | 29-SEP-23:10 | 24.38 | 13.51 |
October | 0.105405E+10 | 2890.51 | 14-OCT-08:61 | 27.67 | 12.98 | 98533154.37 | 56.69 | 17-OCT-21:19 | 18.00 | 14.76 |
November | 0.554834E+09 | 2822.12 | 27-NOV-09:01 | 21.17 | 8.38 | 95041080.65 | 56.69 | 20-NOV-22:00 | 14.00 | 12.83 |
December | 0.542355E+09 | 2840.71 | 05-DEC-09:01 | 24.33 | 11.99 | 98103885.88 | 56.69 | 04-DEC-22:19 | 17.33 | 10.06 |
Annual Sum or Average | 0.908827E+10 | 0.115727E+10 | ||||||||
Minimum of Months | 0.384127E+09 | 2533.51 | 17.33 | 8.38 | 88064133.94 | 56.69 | 12.83 | 10.06 | ||
Maximum of Months | 0.127337E+10 | 2890.51 | 27.67 | 19.10 | 99022161.19 | 56.69 | 24.38 | 17.66 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194411E+09 | 2681.14 | 14-JAN-16:01 | 23.00 | 12.39 | 96811552.09 | 61.85 | 24-JAN-22:19 | 16.00 | 11.53 |
February | 0.185939E+09 | 2769.00 | 01-FEB-09:11 | 22.67 | 11.97 | 87131171.19 | 56.69 | 15-FEB-22:10 | 13.83 | 12.18 |
March | 0.259803E+09 | 2574.25 | 23-MAR-08:11 | 17.67 | 14.22 | 97172277.63 | 56.69 | 23-MAR-21:19 | 13.67 | 13.09 |
April | 0.521862E+09 | 2941.63 | 02-APR-08:11 | 17.67 | 8.81 | 96042633.99 | 67.01 | 26-APR-21:19 | 16.00 | 15.39 |
May | 0.553896E+09 | 3065.35 | 24-MAY-08:11 | 18.00 | 8.95 | 99626012.42 | 67.74 | 04-MAY-21:19 | 17.00 | 15.07 |
June | 0.684871E+09 | 2822.27 | 14-JUN-08:11 | 19.33 | 15.52 | 99075054.97 | 68.25 | 27-JUN-21:19 | 17.00 | 16.37 |
July | 0.930207E+09 | 2874.04 | 04-JUL-08:11 | 20.00 | 15.15 | 0.105478E+09 | 72.60 | 19-JUL-21:19 | 18.00 | 17.79 |
August | 0.919549E+09 | 2701.81 | 23-AUG-08:11 | 19.67 | 15.51 | 0.105263E+09 | 71.91 | 14-AUG-21:19 | 18.67 | 17.56 |
September | 0.628076E+09 | 2766.92 | 30-SEP-08:11 | 25.77 | 15.05 | 97943727.44 | 73.64 | 29-SEP-21:10 | 24.58 | 13.49 |
October | 0.616849E+09 | 3328.13 | 17-OCT-08:11 | 27.00 | 13.09 | 0.100989E+09 | 70.74 | 16-OCT-21:19 | 18.67 | 11.06 |
November | 0.241453E+09 | 2726.37 | 27-NOV-09:12 | 21.33 | 8.47 | 93868688.91 | 58.23 | 09-NOV-22:19 | 16.00 | 14.97 |
December | 0.188321E+09 | 2982.25 | 05-DEC-09:11 | 24.67 | 12.20 | 96757411.57 | 62.54 | 05-DEC-22:19 | 17.33 | 9.42 |
Annual Sum or Average | 0.592524E+10 | 0.117616E+10 | ||||||||
Minimum of Months | 0.185939E+09 | 2574.25 | 17.67 | 8.47 | 87131171.19 | 56.69 | 13.67 | 9.42 | ||
Maximum of Months | 0.930207E+09 | 3328.13 | 27.00 | 15.52 | 0.105478E+09 | 73.64 | 24.58 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174706E+10 | 1688.49 | 18-JAN-14:30 | 23.80 | 14.80 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.137917E+10 | 1672.14 | 01-FEB-13:00 | 24.00 | 13.79 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.135261E+10 | 1614.90 | 11-MAR-14:00 | 24.00 | 12.70 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.187751E+10 | 1551.52 | 26-APR-18:06 | 18.67 | 15.37 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.190406E+10 | 1519.00 | 04-MAY-18:01 | 18.83 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.233687E+10 | 1686.31 | 29-JUN-18:04 | 21.50 | 18.38 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.289065E+10 | 1696.46 | 19-JUL-18:35 | 21.67 | 18.58 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.296950E+10 | 1688.73 | 14-AUG-18:15 | 21.67 | 18.53 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.259070E+10 | 1750.18 | 30-SEP-14:30 | 32.00 | 17.33 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.284103E+10 | 1777.00 | 16-OCT-13:50 | 32.35 | 15.97 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.194106E+10 | 1712.51 | 19-NOV-13:10 | 26.67 | 14.98 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.189040E+10 | 1692.66 | 19-DEC-13:40 | 24.00 | 10.39 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.257206E+11 | 0.00 | ||||||||
Minimum of Months | 0.135261E+10 | 1519.00 | 18.67 | 10.39 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.296950E+10 | 1777.00 | 32.35 | 18.58 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465719E+09 | 3293.46 | 14-JAN-16:01 | 23.00 | 12.39 | 97687555.99 | 56.70 | 21-JAN-02:20 | 14.00 | 13.42 |
February | 0.401614E+09 | 3297.28 | 03-FEB-16:01 | 20.50 | 10.02 | 87861753.09 | 56.69 | 22-FEB-22:10 | 12.00 | 10.34 |
March | 0.441942E+09 | 2872.00 | 21-MAR-15:01 | 16.83 | 13.88 | 97356096.27 | 56.69 | 23-MAR-21:49 | 13.17 | 12.60 |
April | 0.861684E+09 | 3083.74 | 01-APR-18:02 | 17.83 | 8.82 | 95113335.09 | 56.70 | 18-APR-23:10 | 11.83 | 10.26 |
May | 0.833457E+09 | 3016.75 | 24-MAY-08:61 | 18.00 | 8.77 | 98241430.96 | 56.69 | 30-MAY-23:00 | 12.00 | 10.34 |
June | 0.115417E+10 | 3014.16 | 29-JUN-18:01 | 21.50 | 18.38 | 95413638.38 | 56.69 | 15-JUN-23:49 | 16.00 | 14.76 |
July | 0.159400E+10 | 3010.76 | 22-JUL-18:01 | 21.67 | 18.43 | 98810795.69 | 56.69 | 31-JUL-21:19 | 18.90 | 17.79 |
August | 0.159752E+10 | 2980.73 | 05-AUG-15:01 | 22.67 | 18.31 | 98911561.77 | 56.69 | 14-AUG-21:19 | 18.67 | 17.56 |
September | 0.124783E+10 | 2956.84 | 18-SEP-15:01 | 19.83 | 15.04 | 95461944.46 | 56.70 | 19-SEP-03:39 | 13.33 | 11.99 |
October | 0.121381E+10 | 3343.78 | 13-OCT-15:01 | 27.67 | 14.82 | 98496302.67 | 56.69 | 17-OCT-21:19 | 18.00 | 14.76 |
November | 0.589345E+09 | 3256.84 | 27-NOV-16:01 | 19.67 | 7.52 | 94844065.32 | 56.70 | 12-NOV-00:40 | 16.00 | 14.97 |
December | 0.527776E+09 | 3302.20 | 19-DEC-16:01 | 20.67 | 8.08 | 97759767.39 | 56.70 | 06-DEC-23:00 | 16.00 | 10.20 |
Annual Sum or Average | 0.109289E+11 | 0.115596E+10 | ||||||||
Minimum of Months | 0.401614E+09 | 2872.00 | 16.83 | 7.52 | 87861753.09 | 56.69 | 11.83 | 10.20 | ||
Maximum of Months | 0.159752E+10 | 3343.78 | 27.67 | 18.43 | 98911561.77 | 56.70 | 18.90 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136964E+09 | 3194.09 | 14-JAN-16:01 | 23.00 | 12.39 | 96694532.65 | 63.03 | 18-JAN-22:19 | 16.67 | 13.33 |
February | 0.167852E+09 | 3197.34 | 03-FEB-16:01 | 20.50 | 10.02 | 87232473.75 | 56.70 | 17-FEB-22:40 | 12.67 | 12.30 |
March | 0.238452E+09 | 2916.85 | 23-MAR-15:01 | 21.83 | 17.36 | 97438431.69 | 59.22 | 22-MAR-18:10 | 15.50 | 14.38 |
April | 0.586211E+09 | 3298.16 | 27-APR-18:21 | 15.00 | 13.23 | 98044973.71 | 76.85 | 26-APR-18:10 | 18.67 | 15.37 |
May | 0.666139E+09 | 3144.75 | 18-MAY-18:31 | 15.00 | 12.36 | 0.101783E+09 | 74.56 | 03-MAY-21:19 | 16.00 | 14.55 |
June | 0.894394E+09 | 3081.92 | 04-JUN-18:51 | 15.00 | 13.18 | 0.104046E+09 | 81.18 | 30-JUN-18:10 | 18.83 | 16.42 |
July | 0.120922E+10 | 2926.34 | 04-JUL-21:11 | 16.67 | 14.38 | 0.112188E+09 | 83.20 | 19-JUL-18:10 | 22.67 | 18.89 |
August | 0.114468E+10 | 2879.35 | 05-AUG-15:01 | 22.67 | 18.31 | 0.110862E+09 | 80.73 | 18-AUG-21:19 | 19.00 | 17.66 |
September | 0.824184E+09 | 2911.76 | 09-SEP-15:01 | 21.83 | 18.58 | 0.101012E+09 | 76.32 | 29-SEP-21:10 | 24.58 | 13.49 |
October | 0.699650E+09 | 3355.90 | 15-OCT-21:11 | 20.33 | 11.11 | 0.102728E+09 | 74.45 | 16-OCT-21:19 | 18.67 | 11.06 |
November | 0.215779E+09 | 3159.08 | 27-NOV-16:01 | 19.67 | 7.52 | 94274624.90 | 59.01 | 09-NOV-22:19 | 16.00 | 14.97 |
December | 0.142268E+09 | 3201.23 | 19-DEC-16:01 | 20.67 | 8.08 | 96701519.90 | 62.89 | 05-DEC-22:19 | 17.33 | 9.42 |
Annual Sum or Average | 0.692579E+10 | 0.120300E+10 | ||||||||
Minimum of Months | 0.136964E+09 | 2879.35 | 15.00 | 7.52 | 87232473.75 | 56.70 | 12.67 | 9.42 | ||
Maximum of Months | 0.120922E+10 | 3355.90 | 23.00 | 18.58 | 0.112188E+09 | 83.20 | 24.58 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.837738E+09 | 1697.15 | 14-JAN-16:01 | 23.00 | 12.39 | 98669503.95 | 57.32 | 12-JAN-02:00 | 8.00 | 8.00 |
February | 0.562461E+09 | 1687.10 | 03-FEB-16:01 | 20.50 | 10.02 | 88659072.84 | 57.26 | 22-FEB-02:00 | 9.00 | 7.93 |
March | 0.464138E+09 | 1485.46 | 18-MAR-15:01 | 16.83 | 13.87 | 97968040.18 | 57.25 | 08-MAR-23:00 | 8.00 | 7.45 |
April | 0.517203E+09 | 1580.22 | 01-APR-18:02 | 17.83 | 8.82 | 95126764.35 | 56.69 | 12-APR-21:10 | 14.00 | 12.83 |
May | 0.396786E+09 | 1522.13 | 24-MAY-08:61 | 18.00 | 8.77 | 97905544.25 | 56.69 | 02-MAY-23:00 | 16.00 | 14.76 |
June | 0.496592E+09 | 1452.86 | 21-JUN-15:01 | 22.00 | 16.40 | 95040706.43 | 56.69 | 26-JUN-23:49 | 17.00 | 15.73 |
July | 0.693193E+09 | 1483.67 | 30-JUL-15:01 | 22.83 | 18.92 | 98591418.24 | 56.69 | 19-JUL-21:19 | 18.00 | 17.79 |
August | 0.807153E+09 | 1521.17 | 21-AUG-15:01 | 20.83 | 16.45 | 98808778.81 | 56.69 | 02-AUG-21:19 | 17.77 | 16.58 |
September | 0.819461E+09 | 1525.46 | 09-SEP-15:01 | 21.83 | 18.58 | 95343006.30 | 56.69 | 06-SEP-21:00 | 17.00 | 15.06 |
October | 0.104781E+10 | 1702.25 | 14-OCT-08:61 | 27.67 | 12.98 | 98699650.22 | 57.09 | 30-OCT-04:10 | 9.33 | 6.67 |
November | 0.839929E+09 | 1688.01 | 19-NOV-09:02 | 24.33 | 12.75 | 95586293.87 | 57.26 | 30-NOV-02:30 | 7.00 | 2.99 |
December | 0.915139E+09 | 1697.26 | 29-DEC-16:01 | 21.17 | 10.19 | 98731589.87 | 57.27 | 31-DEC-02:09 | 6.92 | 5.85 |
Annual Sum or Average | 0.839760E+10 | 0.115913E+10 | ||||||||
Minimum of Months | 0.396786E+09 | 1452.86 | 16.83 | 8.77 | 88659072.84 | 56.69 | 6.92 | 2.99 | ||
Maximum of Months | 0.104781E+10 | 1702.25 | 27.67 | 18.92 | 98808778.81 | 57.32 | 18.00 | 17.79 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354093E+11 | 18128.99 | 18-JAN-22:14 | 16.67 | 13.33 | 0.185079E+11 | 11348.02 | 18-JAN-22:30 | 16.50 | 13.25 |
February | 0.318710E+11 | 18047.18 | 15-FEB-23:00 | 13.00 | 11.87 | 0.169795E+11 | 11347.84 | 28-FEB-04:19 | 11.00 | 8.84 |
March | 0.356354E+11 | 18312.94 | 24-MAR-22:00 | 13.00 | 11.28 | 0.187980E+11 | 11348.02 | 29-MAR-22:19 | 5.60 | 4.83 |
April | 0.359671E+11 | 18889.71 | 26-APR-22:00 | 16.00 | 15.39 | 0.182807E+11 | 11348.78 | 26-APR-21:30 | 16.00 | 15.39 |
May | 0.375756E+11 | 19221.00 | 04-MAY-22:00 | 17.00 | 15.07 | 0.188907E+11 | 11348.79 | 03-MAY-21:30 | 16.00 | 14.44 |
June | 0.378081E+11 | 19398.89 | 27-JUN-22:00 | 17.00 | 16.37 | 0.183086E+11 | 11348.79 | 21-JUN-21:30 | 16.00 | 14.76 |
July | 0.399929E+11 | 19600.14 | 19-JUL-22:00 | 18.00 | 17.35 | 0.188422E+11 | 11348.88 | 25-JUL-21:30 | 17.00 | 16.69 |
August | 0.399551E+11 | 19479.30 | 17-AUG-21:12 | 19.00 | 17.66 | 0.189085E+11 | 11348.84 | 14-AUG-21:30 | 18.50 | 17.51 |
September | 0.374444E+11 | 20060.78 | 29-SEP-21:12 | 24.57 | 13.51 | 0.182104E+11 | 11348.63 | 29-SEP-21:30 | 24.55 | 13.53 |
October | 0.384509E+11 | 19765.55 | 16-OCT-22:00 | 20.00 | 11.07 | 0.187480E+11 | 11348.63 | 16-OCT-21:30 | 19.00 | 11.07 |
November | 0.346192E+11 | 18103.49 | 01-NOV-22:00 | 14.00 | 11.20 | 0.181393E+11 | 11347.92 | 03-NOV-03:20 | 9.67 | 6.86 |
December | 0.353195E+11 | 18332.70 | 05-DEC-23:00 | 18.00 | 9.34 | 0.186166E+11 | 11348.64 | 01-DEC-00:49 | 10.37 | 9.40 |
Annual Sum or Average | 0.440048E+12 | 0.221231E+12 | ||||||||
Minimum of Months | 0.318710E+11 | 18047.18 | 13.00 | 9.34 | 0.169795E+11 | 11347.84 | 5.60 | 4.83 | ||
Maximum of Months | 0.399929E+11 | 20060.78 | 24.57 | 17.66 | 0.189085E+11 | 11348.88 | 24.55 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389671E+11 | 20074.18 | 18-JAN-22:14 | 16.67 | 13.33 | 0.187354E+11 | 11348.06 | 06-JAN-23:19 | 5.67 | 2.20 |
February | 0.352245E+11 | 20023.73 | 15-FEB-23:00 | 13.00 | 11.87 | 0.171552E+11 | 11347.89 | 28-FEB-04:19 | 11.00 | 8.84 |
March | 0.393645E+11 | 20211.83 | 24-MAR-22:00 | 13.00 | 11.28 | 0.190083E+11 | 11348.04 | 29-MAR-22:19 | 5.60 | 4.83 |
April | 0.396537E+11 | 20796.14 | 26-APR-22:00 | 16.00 | 15.39 | 0.184484E+11 | 11348.79 | 26-APR-21:30 | 16.00 | 15.39 |
May | 0.414268E+11 | 21114.74 | 04-MAY-21:13 | 17.00 | 15.07 | 0.190661E+11 | 11348.80 | 03-MAY-21:30 | 16.00 | 14.44 |
June | 0.414966E+11 | 21276.74 | 27-JUN-22:00 | 17.00 | 16.37 | 0.184731E+11 | 11348.80 | 21-JUN-21:30 | 16.00 | 14.76 |
July | 0.437108E+11 | 21458.03 | 19-JUL-22:00 | 18.00 | 17.35 | 0.190088E+11 | 11348.89 | 25-JUL-21:30 | 17.00 | 16.69 |
August | 0.436288E+11 | 21323.44 | 17-AUG-21:12 | 19.00 | 17.66 | 0.190667E+11 | 11348.85 | 14-AUG-21:30 | 18.50 | 17.51 |
September | 0.410221E+11 | 21864.32 | 29-SEP-21:12 | 24.57 | 13.51 | 0.183764E+11 | 11348.64 | 29-SEP-21:30 | 24.55 | 13.53 |
October | 0.420411E+11 | 21444.17 | 16-OCT-22:00 | 20.00 | 11.07 | 0.189177E+11 | 11348.64 | 16-OCT-21:30 | 19.00 | 11.07 |
November | 0.381561E+11 | 20002.53 | 01-NOV-22:00 | 14.00 | 11.20 | 0.183214E+11 | 11347.96 | 03-NOV-03:20 | 9.67 | 6.86 |
December | 0.388866E+11 | 20202.80 | 05-DEC-23:00 | 18.00 | 9.34 | 0.188289E+11 | 11348.97 | 01-DEC-00:49 | 10.37 | 9.40 |
Annual Sum or Average | 0.483579E+12 | 0.223406E+12 | ||||||||
Minimum of Months | 0.352245E+11 | 20002.53 | 13.00 | 9.34 | 0.171552E+11 | 11347.89 | 5.60 | 2.20 | ||
Maximum of Months | 0.437108E+11 | 21864.32 | 24.57 | 17.66 | 0.190667E+11 | 11348.97 | 24.55 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530311E+11 | 28472.94 | 14-JAN-11:50 | 26.00 | 11.75 | 0.187743E+11 | 11364.17 | 07-JAN-18:00 | 11.00 | 9.85 |
February | 0.477879E+11 | 28153.39 | 01-FEB-11:50 | 25.50 | 14.46 | 0.169832E+11 | 11359.81 | 25-FEB-18:00 | 11.00 | 9.85 |
March | 0.531739E+11 | 28906.42 | 12-MAR-10:50 | 21.17 | 14.83 | 0.187965E+11 | 11377.21 | 04-MAR-18:49 | 9.33 | 8.67 |
April | 0.528016E+11 | 29192.70 | 30-APR-10:40 | 25.67 | 16.95 | 0.182029E+11 | 11345.46 | 22-APR-17:00 | 13.00 | 11.29 |
May | 0.545559E+11 | 28804.60 | 02-MAY-10:40 | 21.67 | 15.54 | 0.188069E+11 | 11341.24 | 13-MAY-17:00 | 14.00 | 10.67 |
June | 0.537866E+11 | 29046.18 | 25-JUN-10:40 | 23.00 | 17.25 | 0.181882E+11 | 11319.60 | 24-JUN-17:19 | 18.67 | 15.16 |
July | 0.564463E+11 | 29427.16 | 23-JUL-10:50 | 25.83 | 20.42 | 0.187769E+11 | 11319.62 | 01-JUL-17:19 | 20.33 | 16.97 |
August | 0.565261E+11 | 29273.20 | 15-AUG-10:40 | 27.00 | 20.83 | 0.187809E+11 | 11319.62 | 19-AUG-17:19 | 23.67 | 17.51 |
September | 0.537188E+11 | 29802.11 | 30-SEP-10:50 | 30.78 | 17.54 | 0.181756E+11 | 11319.89 | 02-SEP-17:00 | 16.00 | 13.57 |
October | 0.551593E+11 | 29836.03 | 15-OCT-10:40 | 31.67 | 16.40 | 0.187823E+11 | 11319.75 | 28-OCT-17:00 | 16.00 | 14.12 |
November | 0.516059E+11 | 28979.88 | 19-NOV-11:50 | 26.00 | 15.36 | 0.181941E+11 | 11354.96 | 04-NOV-17:00 | 12.00 | 9.28 |
December | 0.529779E+11 | 28273.23 | 17-DEC-11:50 | 22.67 | 9.66 | 0.187816E+11 | 11374.45 | 30-DEC-18:00 | 10.00 | 9.41 |
Annual Sum or Average | 0.641571E+12 | 0.221243E+12 | ||||||||
Minimum of Months | 0.477879E+11 | 28153.39 | 21.17 | 9.66 | 0.169832E+11 | 11319.60 | 9.33 | 8.67 | ||
Maximum of Months | 0.565261E+11 | 29836.03 | 31.67 | 20.83 | 0.188069E+11 | 11377.21 | 23.67 | 17.51 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527709E+10 | 3527.90 | 14-JAN-14:30 | 25.00 | 13.49 | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 | 8.36 |
February | 0.472566E+10 | 3459.65 | 01-FEB-13:10 | 23.17 | 14.39 | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 | 11.35 |
March | 0.504223E+10 | 3525.08 | 11-MAR-13:40 | 24.00 | 13.07 | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 | 6.61 |
April | 0.623836E+10 | 3518.71 | 26-APR-13:40 | 26.33 | 16.85 | 0.00 | 0.00 | 01-APR-00:10 | 9.63 | 8.61 |
May | 0.650632E+10 | 3528.93 | 04-MAY-12:40 | 23.33 | 16.62 | 0.00 | 0.00 | 01-MAY-00:10 | 15.20 | 14.50 |
June | 0.725733E+10 | 3517.99 | 30-JUN-15:55 | 22.70 | 17.87 | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 | 12.03 |
July | 0.830030E+10 | 3623.41 | 30-JUL-13:40 | 24.00 | 19.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 | 15.81 |
August | 0.839218E+10 | 3636.69 | 19-AUG-14:00 | 27.00 | 20.16 | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 | 17.20 |
September | 0.744089E+10 | 3919.76 | 30-SEP-14:00 | 32.00 | 17.58 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 14.82 |
October | 0.770107E+10 | 3951.16 | 16-OCT-13:20 | 33.40 | 16.45 | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 | 17.39 |
November | 0.577640E+10 | 3649.21 | 19-NOV-13:10 | 26.67 | 14.98 | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 | 11.06 |
December | 0.550323E+10 | 3577.01 | 19-DEC-13:10 | 25.50 | 11.27 | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 | 5.43 |
Annual Sum or Average | 0.781611E+11 | 0.00 | ||||||||
Minimum of Months | 0.472566E+10 | 3459.65 | 22.70 | 11.27 | 0.00 | 0.00 | 7.63 | 5.43 | ||
Maximum of Months | 0.839218E+10 | 3951.16 | 33.40 | 20.16 | 0.00 | 0.00 | 18.42 | 17.39 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 2807437.91 | 236.28 | 30-MAR-06:15 | 5.87 |
April | 16111.59 | 26.85 | 01-APR-06:10 | 7.67 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 2823549.50 | |||
Minimum of Months | 0.00 | 0.00 | 5.87 | |
Maximum of Months | 2807437.91 | 236.28 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 276152.88 | 44.34 | 30-MAR-04:30 | 4.65 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 276152.88 | |||
Minimum of Months | 0.00 | 0.00 | 4.65 | |
Maximum of Months | 276152.88 | 44.34 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72108792.82 | 1174.52 | 09-JAN-16:04 | 15.50 |
February | 45132842.24 | 1164.52 | 06-FEB-09:03 | 14.33 |
March | 83904800.38 | 1189.79 | 18-MAR-15:04 | 16.83 |
April | 12338660.17 | 1192.09 | 05-APR-18:04 | 12.83 |
May | 9887398.82 | 1170.09 | 12-MAY-15:04 | 15.83 |
June | 2090168.05 | 1172.17 | 06-JUN-15:04 | 17.83 |
July | 1553346.06 | 930.43 | 04-JUL-08:04 | 19.50 |
August | 1507555.76 | 774.49 | 22-AUG-18:04 | 17.00 |
September | 2800363.85 | 1000.57 | 21-SEP-18:04 | 19.00 |
October | 3875195.47 | 1148.66 | 25-OCT-18:04 | 18.50 |
November | 23017928.19 | 1206.60 | 24-NOV-16:03 | 15.83 |
December | 54419438.50 | 1193.57 | 11-DEC-16:04 | 13.83 |
Annual Sum or Average | 0.312636E+09 | |||
Minimum of Months | 1507555.76 | 774.49 | 12.83 | |
Maximum of Months | 83904800.38 | 1206.60 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152670E+09 | 1186.20 | 26-JAN-16:04 | 15.67 |
February | 78174062.37 | 1126.41 | 07-FEB-16:04 | 15.67 |
March | 0.109559E+09 | 1087.30 | 21-MAR-18:04 | 13.83 |
April | 14225478.77 | 1186.06 | 22-APR-18:04 | 13.00 |
May | 8730459.71 | 1142.86 | 31-MAY-15:04 | 20.67 |
June | 1937821.72 | 1048.82 | 08-JUN-15:04 | 18.00 |
July | 762430.72 | 884.43 | 09-JUL-08:14 | 17.33 |
August | 849758.85 | 1010.44 | 23-AUG-08:13 | 19.67 |
September | 1925908.50 | 898.31 | 20-SEP-08:13 | 16.67 |
October | 5435244.88 | 1020.70 | 28-OCT-08:03 | 14.67 |
November | 56686150.02 | 1185.30 | 17-NOV-16:04 | 15.67 |
December | 0.127347E+09 | 1189.70 | 17-DEC-16:03 | 16.83 |
Annual Sum or Average | 0.558304E+09 | |||
Minimum of Months | 762430.72 | 884.43 | 13.00 | |
Maximum of Months | 0.152670E+09 | 1189.70 | 20.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1358539.49 | 327.39 | 07-JAN-16:03 | 13.83 |
February | 1157429.02 | 327.10 | 18-FEB-16:04 | 15.83 |
March | 1201583.04 | 333.75 | 16-MAR-15:05 | 15.83 |
April | 796622.86 | 331.16 | 18-APR-15:04 | 16.00 |
May | 820834.48 | 331.27 | 13-MAY-15:05 | 16.17 |
June | 399574.19 | 314.18 | 01-JUN-08:14 | 17.00 |
July | 55514.18 | 269.15 | 10-JUL-08:15 | 19.67 |
August | 74009.65 | 257.87 | 31-AUG-08:15 | 21.00 |
September | 374216.98 | 316.13 | 20-SEP-08:14 | 16.67 |
October | 457639.45 | 287.40 | 18-OCT-08:14 | 22.33 |
November | 1193029.43 | 329.78 | 24-NOV-16:03 | 15.83 |
December | 1503779.65 | 326.00 | 23-DEC-09:04 | 11.33 |
Annual Sum or Average | 9392772.43 | |||
Minimum of Months | 55514.18 | 257.87 | 11.33 | |
Maximum of Months | 1503779.65 | 333.75 | 22.33 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 71906695.42 | 1127.66 | 06-JAN-16:04 | 16.67 |
February | 52832389.56 | 1136.48 | 18-FEB-16:04 | 15.83 |
March | 93608154.23 | 1134.92 | 01-MAR-16:04 | 16.83 |
April | 13848611.43 | 1116.22 | 16-APR-15:04 | 18.00 |
May | 14056831.56 | 1103.83 | 26-MAY-15:04 | 17.83 |
June | 2454497.83 | 1094.14 | 12-JUN-15:04 | 18.83 |
July | 765559.50 | 782.38 | 03-JUL-18:05 | 18.67 |
August | 686649.46 | 875.41 | 29-AUG-18:04 | 18.83 |
September | 1858338.72 | 812.07 | 18-SEP-18:03 | 15.67 |
October | 3935227.46 | 1036.99 | 25-OCT-18:04 | 18.50 |
November | 29834795.51 | 1131.82 | 17-NOV-16:04 | 15.67 |
December | 61767260.49 | 1125.72 | 20-DEC-16:04 | 16.50 |
Annual Sum or Average | 0.347555E+09 | |||
Minimum of Months | 686649.46 | 782.38 | 15.67 | |
Maximum of Months | 93608154.23 | 1136.48 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147064E+09 | 1113.85 | 26-JAN-16:03 | 15.67 |
February | 95044386.55 | 1130.68 | 07-FEB-16:03 | 15.67 |
March | 0.123624E+09 | 1110.44 | 18-MAR-15:04 | 16.83 |
April | 17993444.24 | 1109.69 | 09-APR-15:04 | 18.00 |
May | 13732505.70 | 1102.98 | 25-MAY-15:04 | 17.83 |
June | 1658677.56 | 1090.69 | 09-JUN-15:04 | 18.83 |
July | 300257.83 | 539.81 | 09-JUL-21:14 | 16.33 |
August | 285845.56 | 526.93 | 21-AUG-19:34 | 15.33 |
September | 2004360.97 | 1087.53 | 19-SEP-15:04 | 18.83 |
October | 7889024.99 | 1085.38 | 11-OCT-15:04 | 18.58 |
November | 70299077.54 | 1110.20 | 14-NOV-16:03 | 15.83 |
December | 0.136135E+09 | 1126.26 | 20-DEC-16:03 | 16.50 |
Annual Sum or Average | 0.616030E+09 | |||
Minimum of Months | 285845.56 | 526.93 | 15.33 | |
Maximum of Months | 0.147064E+09 | 1130.68 | 18.83 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13827039.98 | 277.98 | 28-JAN-08:62 | 8.67 |
February | 12789901.31 | 239.00 | 26-FEB-04:10 | 10.17 |
March | 21336718.07 | 403.37 | 30-MAR-08:62 | 9.50 |
April | 5035613.66 | 341.72 | 01-APR-06:25 | 9.00 |
May | 1380143.55 | 125.93 | 13-MAY-04:50 | 10.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 2201515.28 | 94.06 | 18-NOV-06:00 | 8.00 |
December | 8154410.39 | 186.59 | 14-DEC-05:00 | 8.00 |
Annual Sum or Average | 64725342.24 | |||
Minimum of Months | 0.00 | 0.00 | 8.00 | |
Maximum of Months | 21336718.07 | 403.37 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153637E+09 | 1256.30 | 23-JAN-16:04 | 17.50 |
February | 0.106346E+09 | 1236.23 | 25-FEB-16:03 | 11.00 |
March | 0.162071E+09 | 1276.54 | 30-MAR-08:62 | 9.50 |
April | 26984441.07 | 1376.94 | 17-APR-15:04 | 17.33 |
May | 22387333.77 | 1023.75 | 12-MAY-15:04 | 15.83 |
June | 2812891.15 | 1251.51 | 16-JUN-15:04 | 17.17 |
July | 1377254.91 | 995.62 | 04-JUL-08:04 | 19.50 |
August | 1282617.23 | 838.54 | 22-AUG-18:04 | 17.00 |
September | 2459401.63 | 1040.29 | 21-SEP-18:04 | 19.00 |
October | 10296800.81 | 1216.66 | 23-OCT-15:04 | 17.00 |
November | 62052129.67 | 1237.70 | 24-NOV-16:03 | 15.83 |
December | 0.128600E+09 | 1247.46 | 17-DEC-19:03 | 13.17 |
Annual Sum or Average | 0.680306E+09 | |||
Minimum of Months | 1282617.23 | 838.54 | 9.50 | |
Maximum of Months | 0.162071E+09 | 1376.94 | 19.50 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284622E+09 | 1298.22 | 10-JAN-09:01 | 12.67 |
February | 0.166098E+09 | 1273.25 | 09-FEB-09:01 | 11.90 |
March | 0.203446E+09 | 1275.64 | 30-MAR-08:62 | 9.50 |
April | 29073885.94 | 1361.25 | 14-APR-15:04 | 17.67 |
May | 18333548.90 | 973.65 | 08-MAY-18:04 | 14.83 |
June | 1912981.79 | 1236.93 | 08-JUN-15:04 | 18.00 |
July | 383822.45 | 701.81 | 05-JUL-08:14 | 20.33 |
August | 336318.52 | 745.86 | 23-AUG-08:13 | 19.67 |
September | 1472735.58 | 836.65 | 11-SEP-08:13 | 19.67 |
October | 14253331.95 | 1089.56 | 13-OCT-08:13 | 22.67 |
November | 0.123198E+09 | 1274.02 | 30-NOV-19:03 | 13.67 |
December | 0.246910E+09 | 1292.17 | 15-DEC-09:01 | 12.33 |
Annual Sum or Average | 0.109004E+10 | |||
Minimum of Months | 336318.52 | 701.81 | 9.50 | |
Maximum of Months | 0.284622E+09 | 1361.25 | 22.67 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7544091.54 | 413.37 | 31-JAN-19:05 | 11.83 |
February | 5838550.46 | 556.56 | 11-FEB-16:05 | 17.83 |
March | 27098022.17 | 643.57 | 20-MAR-15:05 | 15.67 |
April | 3954606.96 | 708.10 | 17-APR-15:04 | 17.33 |
May | 5302631.37 | 563.18 | 11-MAY-15:05 | 17.00 |
June | 1446824.14 | 649.55 | 08-JUN-15:04 | 18.00 |
July | 1035557.92 | 530.10 | 10-JUL-18:05 | 17.83 |
August | 646962.92 | 408.99 | 22-AUG-18:04 | 17.00 |
September | 836052.65 | 410.57 | 17-SEP-18:04 | 16.83 |
October | 878307.49 | 558.87 | 23-OCT-15:04 | 17.00 |
November | 794792.37 | 716.22 | 24-NOV-16:04 | 15.83 |
December | 4276328.46 | 436.39 | 11-DEC-19:05 | 12.00 |
Annual Sum or Average | 59652728.46 | |||
Minimum of Months | 646962.92 | 408.99 | 11.83 | |
Maximum of Months | 27098022.17 | 716.22 | 18.00 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16358318.86 | 617.31 | 09-JAN-07:35 | 5.67 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 13.23 |
March | 22272162.55 | 679.36 | 07-MAR-05:40 | 6.00 |
April | 2887.15 | 4.81 | 01-APR-05:00 | 8.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 3317968.93 | 260.21 | 13-DEC-06:00 | 6.00 |
Annual Sum or Average | 41951337.49 | |||
Minimum of Months | 0.00 | 0.00 | 5.67 | |
Maximum of Months | 22272162.55 | 679.36 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.140591E+11 | 13541.81 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.126941E+11 | 13541.81 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.141079E+11 | 13541.81 | 01-MAR-20:10 | 0.121808E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.135824E+11 | 13541.81 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.140835E+11 | 13541.81 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.136447E+11 | 13541.81 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.140212E+11 | 13541.81 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.141079E+11 | 13541.81 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.135824E+11 | 13541.81 | 01-SEP-19:10 | 0.117446E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.140591E+11 | 13541.81 | 02-OCT-19:10 | 0.121516E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.136339E+11 | 13541.81 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.140212E+11 | 13541.81 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.165597E+12 | 0.143109E+12 | ||||
Minimum of Months | 0.126941E+11 | 13541.81 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.141079E+11 | 13541.81 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.715050E+09 | 688.74 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.645625E+09 | 688.74 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.717530E+09 | 688.74 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.690807E+09 | 688.74 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.716290E+09 | 688.74 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.693975E+09 | 688.74 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.713122E+09 | 688.74 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.717530E+09 | 688.74 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.690807E+09 | 688.74 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.715050E+09 | 688.74 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.693424E+09 | 688.74 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.713122E+09 | 688.74 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.842233E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.645625E+09 | 688.74 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.717530E+09 | 688.74 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.828031E+09 | 797.56 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.747637E+09 | 797.56 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.830902E+09 | 797.56 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.799957E+09 | 797.56 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.829467E+09 | 797.56 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.803626E+09 | 797.56 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.825798E+09 | 797.56 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.830902E+09 | 797.56 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.799957E+09 | 797.56 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.828031E+09 | 797.56 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.802987E+09 | 797.56 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.825798E+09 | 797.56 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.975309E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.747637E+09 | 797.56 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.830902E+09 | 797.56 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156929E+10 | 1511.55 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.141693E+10 | 1511.55 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.157474E+10 | 1511.55 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.151609E+10 | 1511.55 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.157202E+10 | 1511.55 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.152304E+10 | 1511.55 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.156506E+10 | 1511.55 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.157474E+10 | 1511.55 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.151609E+10 | 1511.55 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.156929E+10 | 1511.55 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.152183E+10 | 1511.55 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.156506E+10 | 1511.55 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.141693E+10 | 1511.55 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.157474E+10 | 1511.55 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195080E+09 | 187.90 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176140E+09 | 187.90 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.195757E+09 | 187.90 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.188466E+09 | 187.90 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.195419E+09 | 187.90 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.189331E+09 | 187.90 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.194554E+09 | 187.90 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.195757E+09 | 187.90 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.188466E+09 | 187.90 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195080E+09 | 187.90 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189180E+09 | 187.90 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.194554E+09 | 187.90 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.229778E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.176140E+09 | 187.90 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.195757E+09 | 187.90 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304734E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338672E+09 | 325.08 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326059E+09 | 325.08 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337502E+09 | 325.08 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397532E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.304734E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.996266E+09 | 1299.02 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.875356E+09 | 1299.02 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.957745E+09 | 1299.02 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.870084E+09 | 1299.02 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.856042E+09 | 1299.02 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.822471E+09 | 1299.02 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.851615E+09 | 1299.02 | 03-JUL-19:10 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.881685E+09 | 1299.02 | 01-AUG-19:10 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.916929E+09 | 1299.02 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.978242E+09 | 1299.02 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.954278E+09 | 1299.02 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.989882E+09 | 1299.02 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.109506E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.822471E+09 | 1299.02 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.996266E+09 | 1299.02 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.133106E+11 | 13433.46 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.119788E+11 | 13433.46 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.133018E+11 | 13433.46 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.127275E+11 | 13433.46 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.131355E+11 | 13433.46 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.127149E+11 | 13433.46 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.130697E+11 | 13433.46 | 03-JUL-19:10 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.131901E+11 | 13433.46 | 01-AUG-19:10 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.128085E+11 | 13433.46 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.132980E+11 | 13433.46 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.128824E+11 | 13433.46 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.132651E+11 | 13433.46 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.155683E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.119788E+11 | 13433.46 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.133106E+11 | 13433.46 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220030E+09 | 258.74 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.198724E+09 | 258.74 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.219221E+09 | 258.74 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.213063E+09 | 258.74 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.219626E+09 | 258.74 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.212254E+09 | 258.74 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.220434E+09 | 258.74 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.219221E+09 | 258.74 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.213063E+09 | 258.74 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.220030E+09 | 258.74 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.212658E+09 | 258.74 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.220434E+09 | 258.74 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.258876E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.198724E+09 | 258.74 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.220434E+09 | 258.74 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220004E+09 | 258.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.198700E+09 | 258.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.219196E+09 | 258.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.213038E+09 | 258.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.219600E+09 | 258.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.212229E+09 | 258.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.220408E+09 | 258.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.219196E+09 | 258.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.213038E+09 | 258.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.220004E+09 | 258.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.212633E+09 | 258.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.220408E+09 | 258.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.258845E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.198700E+09 | 258.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.220408E+09 | 258.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.138280E+09 | 162.61 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.124890E+09 | 162.61 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.137772E+09 | 162.61 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.133902E+09 | 162.61 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.138026E+09 | 162.61 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.133393E+09 | 162.61 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.138534E+09 | 162.61 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.137772E+09 | 162.61 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.133902E+09 | 162.61 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.138280E+09 | 162.61 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.133648E+09 | 162.61 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.138534E+09 | 162.61 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.162693E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.124890E+09 | 162.61 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.138534E+09 | 162.61 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.138318E+09 | 162.65 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.124924E+09 | 162.65 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.137810E+09 | 162.65 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.133938E+09 | 162.65 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.138064E+09 | 162.65 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.133430E+09 | 162.65 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.138572E+09 | 162.65 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.137810E+09 | 162.65 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.133938E+09 | 162.65 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.138318E+09 | 162.65 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.133684E+09 | 162.65 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.138572E+09 | 162.65 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.162738E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.124924E+09 | 162.65 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.138572E+09 | 162.65 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220030E+09 | 258.74 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.198724E+09 | 258.74 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.219221E+09 | 258.74 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.213063E+09 | 258.74 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.219626E+09 | 258.74 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.212254E+09 | 258.74 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.220434E+09 | 258.74 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.219221E+09 | 258.74 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.213063E+09 | 258.74 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.220030E+09 | 258.74 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.212658E+09 | 258.74 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.220434E+09 | 258.74 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.258876E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.198724E+09 | 258.74 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.220434E+09 | 258.74 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220004E+09 | 258.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.198700E+09 | 258.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.219196E+09 | 258.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.213038E+09 | 258.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.219600E+09 | 258.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.212229E+09 | 258.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.220408E+09 | 258.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.219196E+09 | 258.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.213038E+09 | 258.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.220004E+09 | 258.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.212633E+09 | 258.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.220408E+09 | 258.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.258845E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.198700E+09 | 258.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.220408E+09 | 258.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.140176E+10 | 1350.19 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.126566E+10 | 1350.19 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.140662E+10 | 1350.19 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.135424E+10 | 1350.19 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.140419E+10 | 1350.19 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136045E+10 | 1350.19 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.139798E+10 | 1350.19 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.140662E+10 | 1350.19 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.135424E+10 | 1350.19 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140176E+10 | 1350.19 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.135937E+10 | 1350.19 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.139798E+10 | 1350.19 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165109E+11 | ||||
Minimum of Months | 0.126566E+10 | 1350.19 | 0.00 | 0.00 | |
Maximum of Months | 0.140662E+10 | 1350.19 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220030E+09 | 258.74 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.198724E+09 | 258.74 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.219221E+09 | 258.74 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.213063E+09 | 258.74 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.219626E+09 | 258.74 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.212254E+09 | 258.74 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.220434E+09 | 258.74 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.219221E+09 | 258.74 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.213063E+09 | 258.74 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.220030E+09 | 258.74 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.212658E+09 | 258.74 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.220434E+09 | 258.74 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.258876E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.198724E+09 | 258.74 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.220434E+09 | 258.74 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220004E+09 | 258.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.198700E+09 | 258.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.219196E+09 | 258.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.213038E+09 | 258.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.219600E+09 | 258.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.212229E+09 | 258.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.220408E+09 | 258.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.219196E+09 | 258.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.213038E+09 | 258.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.220004E+09 | 258.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.212633E+09 | 258.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.220408E+09 | 258.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.258845E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.198700E+09 | 258.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.220408E+09 | 258.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.138318E+09 | 162.65 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.124924E+09 | 162.65 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.137810E+09 | 162.65 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.133938E+09 | 162.65 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.138064E+09 | 162.65 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.133430E+09 | 162.65 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.138572E+09 | 162.65 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.137810E+09 | 162.65 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.133938E+09 | 162.65 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.138318E+09 | 162.65 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.133684E+09 | 162.65 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.138572E+09 | 162.65 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.162738E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.124924E+09 | 162.65 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.138572E+09 | 162.65 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.212870E+10 | 2281.19 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.188009E+10 | 2281.19 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.205122E+10 | 2281.19 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.190702E+10 | 2281.19 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.191524E+10 | 2281.19 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.183847E+10 | 2281.19 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.190042E+10 | 2281.19 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.195140E+10 | 2281.19 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.196525E+10 | 2281.19 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.210352E+10 | 2281.19 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.204815E+10 | 2281.19 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.212953E+10 | 2281.19 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.238190E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.183847E+10 | 2281.19 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.212953E+10 | 2281.19 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.212870E+10 | 2281.19 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.188009E+10 | 2281.19 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.205122E+10 | 2281.19 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.190702E+10 | 2281.19 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.191524E+10 | 2281.19 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.183847E+10 | 2281.19 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.190042E+10 | 2281.19 | 03-JUL-19:10 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.195140E+10 | 2281.19 | 01-AUG-19:10 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.196525E+10 | 2281.19 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.210352E+10 | 2281.19 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.204815E+10 | 2281.19 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.212953E+10 | 2281.19 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.238190E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.183847E+10 | 2281.19 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.212953E+10 | 2281.19 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994403E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110515E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106399E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110133E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129722E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994403E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.148355E+10 | 1428.96 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.133951E+10 | 1428.96 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.148869E+10 | 1428.96 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.143325E+10 | 1428.96 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.148612E+10 | 1428.96 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.143982E+10 | 1428.96 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.147955E+10 | 1428.96 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.148869E+10 | 1428.96 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.143325E+10 | 1428.96 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.148355E+10 | 1428.96 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.143868E+10 | 1428.96 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.147955E+10 | 1428.96 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.174742E+11 | ||||
Minimum of Months | 0.133951E+10 | 1428.96 | 0.00 | 0.00 | |
Maximum of Months | 0.148869E+10 | 1428.96 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140591E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126941E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.141079E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135824E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140835E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136447E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.140212E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.141079E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.135824E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.140591E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136339E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.140212E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.165597E+12 | 0.143109E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.126941E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.141079E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.715050E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3292563.84 | 0.552743E+09 |
February | 0.179968E+10 | 0.645625E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 249438.90 | 0.476320E+09 |
March | 0.199896E+10 | 0.717530E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 168369.89 | 0.552249E+09 |
April | 0.192973E+10 | 0.690807E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6459659.04 | 0.370456E+09 |
May | 0.199475E+10 | 0.716290E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2685074.06 | 0.351401E+09 |
June | 0.193394E+10 | 0.693975E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15491883.98 | 0.224365E+09 |
July | 0.199054E+10 | 0.713122E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39145411.61 | 0.150761E+09 |
August | 0.199896E+10 | 0.717530E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38947362.41 | 0.147163E+09 |
September | 0.192973E+10 | 0.690807E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20929946.80 | 0.209925E+09 |
October | 0.199054E+10 | 0.715050E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32311269.04 | 0.234366E+09 |
November | 0.192552E+10 | 0.693424E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1321859.38 | 0.465534E+09 |
December | 0.199054E+10 | 0.713122E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 919731.09 | 0.534026E+09 |
Annual Sum or Average | 0.234734E+11 | 0.842233E+10 | 0.101859E+11 | 0.161923E+09 | 0.426931E+10 | ||||
Minimum of Months | 0.179968E+10 | 0.645625E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 168369.89 | 0.147163E+09 |
Maximum of Months | 0.199896E+10 | 0.717530E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39145411.61 | 0.552743E+09 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.828031E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1430225.09 | 0.121691E+09 |
February | 0.208403E+10 | 0.747637E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 213290.79 | 0.108343E+09 |
March | 0.231480E+10 | 0.830902E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 371418.03 | 0.126388E+09 |
April | 0.223463E+10 | 0.799957E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1605643.71 | 90420619.62 |
May | 0.230993E+10 | 0.829467E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 531357.30 | 87376059.62 |
June | 0.223950E+10 | 0.803626E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2630240.50 | 58979796.87 |
July | 0.230505E+10 | 0.825798E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7233317.54 | 42781249.27 |
August | 0.231480E+10 | 0.830902E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8248747.27 | 41580397.33 |
September | 0.223463E+10 | 0.799957E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5244427.13 | 53458782.60 |
October | 0.230505E+10 | 0.828031E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9151163.83 | 57272249.52 |
November | 0.222975E+10 | 0.802987E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 931114.21 | 0.105973E+09 |
December | 0.230505E+10 | 0.825798E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1191968.20 | 0.118487E+09 |
Annual Sum or Average | 0.271823E+11 | 0.975309E+10 | 0.117953E+11 | 38782913.59 | 0.101275E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.747637E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 213290.79 | 41580397.33 |
Maximum of Months | 0.231480E+10 | 0.830902E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9151163.83 | 0.126388E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 5653220.37 | 0.374750E+09 |
February | 0.139600E+10 | 0.304734E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 1032656.98 | 0.333413E+09 |
March | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 1760816.21 | 0.395983E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 6106716.37 | 0.278536E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 2180185.86 | 0.271336E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 10100035.73 | 0.181247E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 26717086.85 | 0.128739E+09 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 31189470.08 | 0.124159E+09 |
September | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 20397702.87 | 0.158949E+09 |
October | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 34680038.46 | 0.168089E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 4503851.18 | 0.317966E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 5850752.15 | 0.360411E+09 |
Annual Sum or Average | 0.182082E+11 | 0.397532E+10 | 0.679373E+11 | 0.590211E+12 | 0.150173E+09 | 0.309358E+10 | |||
Minimum of Months | 0.139600E+10 | 0.304734E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 1032656.98 | 0.124159E+09 |
Maximum of Months | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 34680038.46 | 0.395983E+09 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.996266E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7806848.51 | 0.155437E+10 |
February | 0.236489E+11 | 0.875356E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 623431.58 | 0.135636E+10 |
March | 0.262677E+11 | 0.957745E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283400.59 | 0.154681E+10 |
April | 0.253579E+11 | 0.870084E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14662725.95 | 0.109698E+10 |
May | 0.262123E+11 | 0.856042E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6737934.98 | 0.104384E+10 |
June | 0.254132E+11 | 0.822471E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36245396.80 | 0.713380E+09 |
July | 0.261570E+11 | 0.851615E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92154041.55 | 0.523402E+09 |
August | 0.262677E+11 | 0.881685E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94264113.00 | 0.517238E+09 |
September | 0.253579E+11 | 0.916929E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48507838.44 | 0.675893E+09 |
October | 0.261570E+11 | 0.978242E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80803608.00 | 0.742078E+09 |
November | 0.253025E+11 | 0.954278E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3306649.69 | 0.135013E+10 |
December | 0.261570E+11 | 0.989882E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2405917.17 | 0.151600E+10 |
Annual Sum or Average | 0.308456E+12 | 0.109506E+11 | 0.143409E+11 | 0.387802E+09 | 0.126365E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.822471E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283400.59 | 0.517238E+09 |
Maximum of Months | 0.262677E+11 | 0.996266E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94264113.00 | 0.155437E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.133106E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28529438.64 | 0.306282E+10 |
February | 0.702046E+11 | 0.119788E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3826510.87 | 0.272137E+10 |
March | 0.779788E+11 | 0.133018E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6468375.72 | 0.315687E+10 |
April | 0.752779E+11 | 0.127275E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35368310.41 | 0.226228E+10 |
May | 0.778146E+11 | 0.131355E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12842625.07 | 0.219072E+10 |
June | 0.754422E+11 | 0.127149E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63584824.84 | 0.149816E+10 |
July | 0.776503E+11 | 0.130697E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173979E+09 | 0.109644E+10 |
August | 0.779788E+11 | 0.131901E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195711E+09 | 0.106716E+10 |
September | 0.752779E+11 | 0.128085E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117544E+09 | 0.136293E+10 |
October | 0.776503E+11 | 0.132980E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205025E+09 | 0.146952E+10 |
November | 0.751137E+11 | 0.128824E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17016989.70 | 0.266907E+10 |
December | 0.776503E+11 | 0.132651E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20765213.23 | 0.298217E+10 |
Annual Sum or Average | 0.915690E+12 | 0.155683E+12 | 0.149002E+12 | 0.880661E+09 | 0.255395E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.119788E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3826510.87 | 0.106716E+10 |
Maximum of Months | 0.779788E+11 | 0.133106E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205025E+09 | 0.315687E+10 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1106232.14 | 0.158834E+09 |
February | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 191575.80 | 0.138748E+09 |
March | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 183919.69 | 0.165434E+09 |
April | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1034892.98 | 0.114719E+09 |
May | 0.303504E+09 | 0.219626E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100566.90 | 0.111971E+09 |
June | 0.293842E+09 | 0.212254E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1358431.88 | 72304187.05 |
July | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5860336.69 | 47769024.80 |
August | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6850922.09 | 44747315.98 |
September | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6462651.20 | 64017601.17 |
October | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11287164.61 | 65654659.96 |
November | 0.293661E+09 | 0.212658E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 850219.00 | 0.132806E+09 |
December | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 944436.61 | 0.151618E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258876E+10 | 0.261953E+10 | 36231349.59 | 0.126862E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 100566.90 | 44747315.98 |
Maximum of Months | 0.303685E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11287164.61 | 0.165434E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1421276.28 | 0.154893E+09 |
February | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 258354.41 | 0.136215E+09 |
March | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 276060.92 | 0.164279E+09 |
April | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1004016.31 | 0.118233E+09 |
May | 0.303504E+09 | 0.219600E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77729.92 | 0.117078E+09 |
June | 0.293842E+09 | 0.212229E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 942784.39 | 82716427.91 |
July | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4188973.56 | 62334331.02 |
August | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5336269.37 | 57709913.40 |
September | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6118697.56 | 70572205.42 |
October | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10981420.46 | 70282258.61 |
November | 0.293661E+09 | 0.212633E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1135731.19 | 0.130375E+09 |
December | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1459162.07 | 0.148023E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258845E+10 | 0.261922E+10 | 33200476.43 | 0.131271E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 77729.92 | 57709913.40 |
Maximum of Months | 0.303685E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10981420.46 | 0.164279E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.138280E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70029736.76 |
February | 0.00 | 0.124890E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62038266.21 |
March | 0.00 | 0.137772E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71506783.86 |
April | 0.00 | 0.133902E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 584.74 | 56464943.30 |
May | 0.00 | 0.138026E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56688213.85 |
June | 0.00 | 0.133393E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44469341.81 |
July | 0.00 | 0.138534E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46042.49 | 37006056.34 |
August | 0.00 | 0.137772E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30487.59 | 35863945.52 |
September | 0.00 | 0.133902E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 657486.22 | 41341237.39 |
October | 0.00 | 0.138280E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126345.22 | 41764583.63 |
November | 0.00 | 0.133648E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 450.87 | 61992962.20 |
December | 0.00 | 0.138534E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68122452.97 |
Annual Sum or Average | 0.00 | 0.162693E+10 | 0.256575E+10 | 1861397.13 | 0.647289E+09 | ||||
Minimum of Months | 0.00 | 0.124890E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35863945.52 |
Maximum of Months | 0.00 | 0.138534E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126345.22 | 71506783.86 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 456091.78 | 43453551.77 |
February | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 84867.32 | 38168479.62 |
March | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98847.91 | 45885317.18 |
April | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 347380.13 | 31840019.86 |
May | 0.303504E+09 | 0.138064E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40989.27 | 31511504.70 |
June | 0.293842E+09 | 0.133430E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 332021.95 | 21558056.34 |
July | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1383771.76 | 15604850.22 |
August | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1743806.64 | 14544157.38 |
September | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1764316.49 | 18601203.98 |
October | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3228705.37 | 19256204.32 |
November | 0.293661E+09 | 0.133684E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 387295.21 | 36158873.54 |
December | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 478347.93 | 41383963.54 |
Annual Sum or Average | 0.357224E+10 | 0.162738E+10 | 0.256645E+10 | 10346441.77 | 0.357966E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40989.27 | 14544157.38 |
Maximum of Months | 0.303685E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3228705.37 | 45885317.18 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1080035.46 | 0.159597E+09 |
February | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 188397.58 | 0.139013E+09 |
March | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 175477.58 | 0.166219E+09 |
April | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 946376.34 | 0.115664E+09 |
May | 0.303504E+09 | 0.219626E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90234.73 | 0.112729E+09 |
June | 0.293842E+09 | 0.212254E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1176543.68 | 72675927.01 |
July | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5631106.18 | 48340518.41 |
August | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6582851.93 | 45181113.32 |
September | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6416348.94 | 64058998.76 |
October | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11252681.59 | 65957110.03 |
November | 0.293661E+09 | 0.212658E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 838522.31 | 0.133175E+09 |
December | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 933596.63 | 0.152107E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258876E+10 | 0.261953E+10 | 35312172.96 | 0.127472E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 90234.73 | 45181113.32 |
Maximum of Months | 0.303685E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11252681.59 | 0.166219E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1393377.74 | 0.154855E+09 |
February | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 229575.22 | 0.135747E+09 |
March | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 205621.43 | 0.164415E+09 |
April | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 782659.51 | 0.116712E+09 |
May | 0.303504E+09 | 0.219600E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63239.38 | 0.115479E+09 |
June | 0.293842E+09 | 0.212229E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 820969.89 | 79073848.71 |
July | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4185807.46 | 58342227.42 |
August | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5134915.62 | 54511046.79 |
September | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5986004.02 | 67847455.86 |
October | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10631141.80 | 68865947.52 |
November | 0.293661E+09 | 0.212633E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1122223.70 | 0.129190E+09 |
December | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1368176.52 | 0.147556E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258845E+10 | 0.261922E+10 | 31923712.30 | 0.129260E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 63239.38 | 54511046.79 |
Maximum of Months | 0.303685E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10631141.80 | 0.164415E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1032618.35 | 0.159634E+09 |
February | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 183657.57 | 0.139452E+09 |
March | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 167688.28 | 0.166460E+09 |
April | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 932752.91 | 0.116267E+09 |
May | 0.303504E+09 | 0.219626E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80415.34 | 0.113811E+09 |
June | 0.293842E+09 | 0.212254E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1109739.80 | 73870917.25 |
July | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5437100.17 | 49011683.01 |
August | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6418768.27 | 45770495.72 |
September | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6318816.15 | 65224019.99 |
October | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11027970.51 | 66680584.00 |
November | 0.293661E+09 | 0.212658E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 813268.53 | 0.133756E+09 |
December | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 897091.95 | 0.152394E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258876E+10 | 0.261953E+10 | 34419887.83 | 0.128233E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80415.34 | 45770495.72 |
Maximum of Months | 0.303685E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11027970.51 | 0.166460E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285210.46 | 0.155598E+09 |
February | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 238043.08 | 0.136944E+09 |
March | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 211007.11 | 0.165612E+09 |
April | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 836093.77 | 0.121000E+09 |
May | 0.303504E+09 | 0.219600E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55207.30 | 0.120087E+09 |
June | 0.293842E+09 | 0.212229E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 769172.92 | 87279979.03 |
July | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3855890.00 | 68203097.66 |
August | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4852727.93 | 62775402.08 |
September | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5929922.07 | 73798099.38 |
October | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10563907.02 | 72587010.42 |
November | 0.293661E+09 | 0.212633E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1039641.62 | 0.131437E+09 |
December | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1345793.25 | 0.148664E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258845E+10 | 0.261922E+10 | 30982616.53 | 0.134399E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55207.30 | 62775402.08 |
Maximum of Months | 0.303685E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10563907.02 | 0.165612E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 490660.36 | 82988572.48 |
February | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 89932.41 | 72557409.19 |
March | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80263.15 | 86231204.26 |
April | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 468627.71 | 59650953.51 |
May | 0.303504E+09 | 0.138064E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41486.44 | 57901092.36 |
June | 0.293842E+09 | 0.133430E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 603826.71 | 37368897.29 |
July | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2826699.64 | 24807856.96 |
August | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3289762.18 | 23295366.55 |
September | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3223979.38 | 33318374.72 |
October | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5592690.75 | 34399796.90 |
November | 0.293661E+09 | 0.133684E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 390442.88 | 69439313.39 |
December | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 442792.42 | 79272075.73 |
Annual Sum or Average | 0.357224E+10 | 0.162738E+10 | 0.256645E+10 | 17541164.04 | 0.661231E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41486.44 | 23295366.55 |
Maximum of Months | 0.303685E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5592690.75 | 86231204.26 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.212870E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3169256.65 | 0.469292E+09 |
February | 0.415303E+11 | 0.188009E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 564087.41 | 0.421640E+09 |
March | 0.461292E+11 | 0.205122E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 416617.23 | 0.496681E+09 |
April | 0.445315E+11 | 0.190702E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2163542.90 | 0.365730E+09 |
May | 0.460320E+11 | 0.191524E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 343594.25 | 0.363274E+09 |
June | 0.446286E+11 | 0.183847E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2062735.94 | 0.258671E+09 |
July | 0.459349E+11 | 0.190042E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10723703.56 | 0.196647E+09 |
August | 0.461292E+11 | 0.195140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13330355.01 | 0.187744E+09 |
September | 0.445315E+11 | 0.196525E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12129143.73 | 0.231545E+09 |
October | 0.459349E+11 | 0.210352E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25478205.25 | 0.238929E+09 |
November | 0.444343E+11 | 0.204815E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2434240.91 | 0.406457E+09 |
December | 0.459349E+11 | 0.212953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3150152.20 | 0.453297E+09 |
Annual Sum or Average | 0.541686E+12 | 0.238190E+11 | 0.175857E+12 | 75965635.05 | 0.408990E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.183847E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 343594.25 | 0.187744E+09 |
Maximum of Months | 0.461292E+11 | 0.212953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25478205.25 | 0.496681E+09 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.212870E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2523042.41 | 0.477348E+09 |
February | 0.415303E+11 | 0.188009E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 419517.11 | 0.428839E+09 |
March | 0.461292E+11 | 0.205122E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 249250.28 | 0.505018E+09 |
April | 0.445315E+11 | 0.190702E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1598072.12 | 0.372432E+09 |
May | 0.460320E+11 | 0.191524E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199111.21 | 0.370770E+09 |
June | 0.446286E+11 | 0.183847E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1197033.13 | 0.264899E+09 |
July | 0.459349E+11 | 0.190042E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8562072.63 | 0.201417E+09 |
August | 0.461292E+11 | 0.195140E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10569397.83 | 0.191726E+09 |
September | 0.445315E+11 | 0.196525E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11232060.04 | 0.237598E+09 |
October | 0.459349E+11 | 0.210352E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23679714.19 | 0.244130E+09 |
November | 0.444343E+11 | 0.204815E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1953745.16 | 0.413572E+09 |
December | 0.459349E+11 | 0.212953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2484567.95 | 0.460956E+09 |
Annual Sum or Average | 0.541686E+12 | 0.238190E+11 | 0.175857E+12 | 64667584.06 | 0.416871E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.183847E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 199111.21 | 0.191726E+09 |
Maximum of Months | 0.461292E+11 | 0.212953E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23679714.19 | 0.505018E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 604139.40 | 0.430729E+09 |
February | 0.369574E+10 | 0.994403E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 80091.45 | 0.387324E+09 |
March | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454507E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 607625.23 | 0.335808E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334625E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 43681.56 | 0.236657E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3741844.19 | 0.174272E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 4237283.55 | 0.165131E+09 |
September | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 9403077.25 | 0.212621E+09 |
October | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16659959.27 | 0.216625E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 745397.93 | 0.374654E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 451978.32 | 0.415483E+09 |
Annual Sum or Average | 0.482041E+11 | 0.129722E+11 | 0.392709E+12 | 0.359593E+12 | 36575078.17 | 0.373844E+10 | |||
Minimum of Months | 0.369574E+10 | 0.994403E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165131E+09 |
Maximum of Months | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 16659959.27 | 0.454507E+09 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3927642.06 | 0.243932E+09 |
February | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 671584.22 | 0.215448E+09 |
March | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1253348.60 | 0.256442E+09 |
April | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4215584.71 | 0.177913E+09 |
May | 0.00 | 0.157202E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1358181.08 | 0.173925E+09 |
June | 0.00 | 0.152304E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5982968.55 | 0.115752E+09 |
July | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16461770.91 | 81214525.10 |
August | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19676801.55 | 76897883.45 |
September | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13337916.89 | 0.100527E+09 |
October | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22470997.00 | 0.109231E+09 |
November | 0.00 | 0.152183E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2901150.70 | 0.208616E+09 |
December | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4037755.57 | 0.234523E+09 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | 96295701.82 | 0.199442E+10 | |||||
Minimum of Months | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 671584.22 | 76897883.45 |
Maximum of Months | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22470997.00 | 0.256442E+09 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.195080E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2679770.59 | 0.166164E+09 |
February | 0.00 | 0.176140E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 460009.45 | 0.145973E+09 |
March | 0.00 | 0.195757E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 858537.30 | 0.174370E+09 |
April | 0.00 | 0.188466E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2885626.26 | 0.119747E+09 |
May | 0.00 | 0.195419E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 916345.05 | 0.116882E+09 |
June | 0.00 | 0.189331E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4042539.58 | 77538173.73 |
July | 0.00 | 0.194554E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11135195.82 | 54114663.71 |
August | 0.00 | 0.195757E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13307458.74 | 51052795.37 |
September | 0.00 | 0.188466E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9074400.99 | 67263454.19 |
October | 0.00 | 0.195080E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15292670.70 | 73272085.31 |
November | 0.00 | 0.189180E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1965682.71 | 0.140876E+09 |
December | 0.00 | 0.194554E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2731066.70 | 0.159212E+09 |
Annual Sum or Average | 0.229778E+10 | 0.359769E+10 | 65349303.88 | 0.134647E+10 | |||||
Minimum of Months | 0.00 | 0.176140E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 460009.45 | 51052795.37 |
Maximum of Months | 0.00 | 0.195757E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15292670.70 | 0.174370E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.140176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3116578.59 | 0.181075E+09 |
February | 0.00 | 0.126566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597808.43 | 0.158681E+09 |
March | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 962943.97 | 0.190792E+09 |
April | 0.00 | 0.135424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3347821.88 | 0.128446E+09 |
May | 0.00 | 0.140419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1157562.75 | 0.124408E+09 |
June | 0.00 | 0.136045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5541547.90 | 78546737.56 |
July | 0.00 | 0.139798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15259794.57 | 51375027.13 |
August | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17589732.73 | 48620832.69 |
September | 0.00 | 0.135424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11714169.40 | 67640940.99 |
October | 0.00 | 0.140176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19502629.76 | 71843144.01 |
November | 0.00 | 0.135937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2474192.91 | 0.149382E+09 |
December | 0.00 | 0.139798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3264788.66 | 0.172639E+09 |
Annual Sum or Average | 0.165109E+11 | 84529571.56 | 0.142345E+10 | ||||||
Minimum of Months | 0.00 | 0.126566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597808.43 | 48620832.69 |
Maximum of Months | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19502629.76 | 0.190792E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.148355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4315628.01 | 0.328002E+09 |
February | 0.00 | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743142.22 | 0.287520E+09 |
March | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864196.43 | 0.344571E+09 |
April | 0.00 | 0.143325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4003842.29 | 0.236005E+09 |
May | 0.00 | 0.148612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 987904.66 | 0.228336E+09 |
June | 0.00 | 0.143982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5527873.94 | 0.147870E+09 |
July | 0.00 | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17414912.92 | 0.101614E+09 |
August | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20262659.53 | 96657996.50 |
September | 0.00 | 0.143325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15385432.75 | 0.129180E+09 |
October | 0.00 | 0.148355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26784765.83 | 0.137310E+09 |
November | 0.00 | 0.143868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3032529.29 | 0.272431E+09 |
December | 0.00 | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3791982.24 | 0.312572E+09 |
Annual Sum or Average | 0.174742E+11 | 0.103115E+09 | 0.262207E+10 | ||||||
Minimum of Months | 0.00 | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743142.22 | 96657996.50 |
Maximum of Months | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26784765.83 | 0.344571E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13541.81 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13541.81 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13541.81 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13541.81 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13541.81 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13541.81 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13541.81 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13541.81 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13541.81 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 13541.81 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13541.81 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13541.81 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 13541.81 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13541.81 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 688.74 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.41 | 15-JAN-10:00 | 478.48 | 08-JAN-07:00 |
February | 1169.53 | 01-FEB-00:10 | 688.74 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.15 | 01-FEB-12:00 | 388.45 | 04-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 688.74 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 11-MAR-11:00 | 415.78 | 08-MAR-04:00 |
April | 1169.53 | 01-APR-00:10 | 688.74 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.14 | 26-APR-13:00 | 336.98 | 01-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 688.74 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.21 | 03-MAY-12:00 | 313.59 | 15-MAY-02:00 |
June | 1169.53 | 01-JUN-00:10 | 688.74 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.94 | 29-JUN-11:00 | 239.01 | 13-JUN-04:10 |
July | 1169.53 | 01-JUL-00:10 | 688.74 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.90 | 19-JUL-11:00 | 188.63 | 06-JUL-01:00 |
August | 1169.53 | 01-AUG-00:10 | 688.74 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.87 | 14-AUG-11:00 | 164.35 | 31-AUG-04:00 |
September | 1169.53 | 01-SEP-00:10 | 688.74 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.71 | 29-SEP-11:00 | 237.32 | 20-SEP-03:00 |
October | 1169.53 | 02-OCT-00:10 | 688.74 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.13 | 16-OCT-11:00 | 288.05 | 30-OCT-04:00 |
November | 1169.53 | 01-NOV-00:10 | 688.74 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 | 19-NOV-13:00 | 353.36 | 29-NOV-23:00 |
December | 1169.53 | 01-DEC-00:10 | 688.74 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.20 | 05-DEC-10:00 | 389.49 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 688.74 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 164.35 | |||||
Maximum of Months | 1169.53 | 688.74 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 283.13 | 478.48 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 797.56 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.66 | 18-JAN-13:00 | 103.83 | 08-JAN-07:00 |
February | 1354.32 | 01-FEB-00:10 | 797.56 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.09 | 01-FEB-12:00 | 86.83 | 04-FEB-05:55 |
March | 1354.32 | 01-MAR-00:10 | 797.56 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 11-MAR-11:10 | 88.77 | 08-MAR-02:00 |
April | 1354.32 | 01-APR-00:10 | 797.56 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 26-APR-13:00 | 73.09 | 01-APR-06:00 |
May | 1354.32 | 01-MAY-00:10 | 797.56 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 | 03-MAY-12:00 | 72.41 | 19-MAY-05:00 |
June | 1354.32 | 01-JUN-00:10 | 797.56 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.11 | 29-JUN-11:00 | 57.39 | 13-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 797.56 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 | 31-JUL-12:00 | 47.64 | 06-JUL-01:00 |
August | 1354.32 | 01-AUG-00:10 | 797.56 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 | 14-AUG-11:00 | 42.12 | 28-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 797.56 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.35 | 29-SEP-11:00 | 57.87 | 20-SEP-03:00 |
October | 1354.32 | 02-OCT-00:10 | 797.56 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 16-OCT-11:00 | 69.02 | 30-OCT-03:00 |
November | 1354.32 | 01-NOV-00:10 | 797.56 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 | 19-NOV-13:00 | 83.19 | 29-NOV-23:00 |
December | 1354.32 | 01-DEC-00:10 | 797.56 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 | 16-DEC-13:00 | 86.79 | 03-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 797.56 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 42.12 | |||||
Maximum of Months | 1354.32 | 797.56 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 103.83 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 73.19 | 18-JAN-13:00 | 304.05 | 08-JAN-07:10 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 72.74 | 01-FEB-12:00 | 264.39 | 06-FEB-23:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 44.04 | 11-MAR-12:40 | 283.65 | 29-MAR-22:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 87.01 | 26-APR-13:00 | 231.67 | 15-APR-22:00 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 44.14 | 03-MAY-12:15 | 220.86 | 15-MAY-05:08 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 58.41 | 29-JUN-11:00 | 184.95 | 12-JUN-21:00 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 101.39 | 19-JUL-11:30 | 136.22 | 08-JUL-21:00 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 101.48 | 18-AUG-12:00 | 150.95 | 28-AUG-07:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 211.19 | 29-SEP-11:00 | 179.30 | 20-SEP-06:10 |
October | 907.20 | 02-OCT-00:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 224.83 | 16-OCT-11:00 | 225.58 | 12-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 87.07 | 19-NOV-13:00 | 265.28 | 23-NOV-22:00 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 73.17 | 16-DEC-13:00 | 281.18 | 12-DEC-22:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 44.04 | 136.22 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 224.83 | 304.05 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1299.02 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.90 | 15-JAN-14:00 | 1248.71 | 08-JAN-07:00 |
February | 15368.40 | 01-FEB-00:10 | 1299.02 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.35 | 01-FEB-12:00 | 1051.71 | 04-FEB-05:55 |
March | 15368.40 | 01-MAR-00:10 | 1299.02 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 | 11-MAR-11:00 | 1055.11 | 08-MAR-02:00 |
April | 15368.40 | 01-APR-00:10 | 1299.02 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.85 | 26-APR-13:00 | 863.84 | 01-APR-06:00 |
May | 15368.40 | 01-MAY-00:10 | 1299.02 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 143.42 | 03-MAY-13:00 | 880.50 | 19-MAY-05:00 |
June | 15368.40 | 01-JUN-00:10 | 1299.02 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.84 | 29-JUN-11:00 | 723.36 | 13-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1299.02 | 03-JUL-19:10 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.32 | 19-JUL-11:00 | 597.97 | 06-JUL-01:00 |
August | 15368.40 | 01-AUG-00:10 | 1299.02 | 01-AUG-19:10 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.48 | 14-AUG-11:00 | 544.74 | 28-AUG-05:00 |
September | 15368.40 | 01-SEP-00:10 | 1299.02 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 672.05 | 29-SEP-11:00 | 730.94 | 20-SEP-03:00 |
October | 15368.40 | 02-OCT-00:10 | 1299.02 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 714.56 | 16-OCT-11:00 | 873.18 | 30-OCT-03:00 |
November | 15368.40 | 01-NOV-00:10 | 1299.02 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.25 | 19-NOV-13:00 | 1000.44 | 29-NOV-23:00 |
December | 15368.40 | 01-DEC-00:10 | 1299.02 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.09 | 05-DEC-10:00 | 1036.61 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1299.02 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 | 544.74 | |||||
Maximum of Months | 15368.40 | 1299.02 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 714.56 | 1248.71 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 13433.46 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.11 | 18-JAN-13:00 | 2490.07 | 08-JAN-07:00 |
February | 45622.98 | 01-FEB-00:10 | 13433.46 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.25 | 01-FEB-12:00 | 2147.26 | 04-FEB-05:55 |
March | 45622.98 | 01-MAR-00:10 | 13433.46 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.64 | 11-MAR-11:10 | 2182.82 | 08-MAR-02:00 |
April | 45622.98 | 01-APR-00:10 | 13433.46 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 633.81 | 26-APR-13:00 | 1819.06 | 01-APR-06:00 |
May | 45622.98 | 01-MAY-00:10 | 13433.46 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.91 | 03-MAY-13:00 | 1807.35 | 19-MAY-05:00 |
June | 45622.98 | 01-JUN-00:10 | 13433.46 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.88 | 29-JUN-11:00 | 1468.15 | 13-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 13433.46 | 03-JUL-19:10 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 747.82 | 31-JUL-13:00 | 1206.32 | 06-JUL-01:00 |
August | 45622.98 | 01-AUG-00:10 | 13433.46 | 01-AUG-19:10 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 746.31 | 14-AUG-11:00 | 1079.48 | 28-AUG-05:00 |
September | 45622.98 | 01-SEP-00:10 | 13433.46 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1508.69 | 29-SEP-11:00 | 1465.39 | 20-SEP-03:00 |
October | 45622.98 | 02-OCT-00:10 | 13433.46 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.73 | 16-OCT-11:00 | 1738.75 | 27-OCT-04:50 |
November | 45622.98 | 01-NOV-00:10 | 13433.46 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.30 | 19-NOV-13:00 | 2041.92 | 29-NOV-23:00 |
December | 45622.98 | 01-DEC-00:10 | 13433.46 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.11 | 05-DEC-10:00 | 2112.62 | 03-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 13433.46 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 212.64 | 1079.48 | |||||
Maximum of Months | 45622.98 | 13433.46 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1568.73 | 2490.07 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 14-JAN-11:00 | 146.56 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 258.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 01-FEB-10:00 | 115.29 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 258.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 11-MAR-11:00 | 123.32 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 258.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 30-APR-10:00 | 100.15 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 03-MAY-10:00 | 93.26 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 258.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 30-JUN-10:00 | 71.32 | 13-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 258.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 19-JUL-10:00 | 56.51 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 258.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 15-AUG-10:00 | 51.97 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 258.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 29-SEP-10:00 | 70.82 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 258.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.23 | 16-OCT-10:01 | 85.75 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 258.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 19-NOV-10:00 | 100.61 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 258.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 05-DEC-10:00 | 115.58 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 51.97 | |||||
Maximum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.23 | 146.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 14-JAN-11:00 | 146.55 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 258.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.72 | 01-FEB-12:00 | 115.28 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 258.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 11-MAR-11:00 | 123.31 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 258.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 30-APR-10:00 | 100.14 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 03-MAY-10:00 | 93.25 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 258.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 30-JUN-10:00 | 71.31 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 258.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 | 19-JUL-10:00 | 57.95 | 10-JUL-18:02 |
August | 180.00 | 01-AUG-00:10 | 258.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 15-AUG-10:00 | 56.69 | 02-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 258.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 29-SEP-10:00 | 70.82 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 258.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | 16-OCT-10:01 | 85.75 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 258.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 19-NOV-10:00 | 100.61 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 258.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 05-DEC-10:00 | 115.57 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 56.69 | |||||
Maximum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | 146.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 162.61 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 50.29 | 08-JAN-07:00 |
February | 0.00 | 01-FEB-00:10 | 162.61 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 42.08 | 04-FEB-05:55 |
March | 0.00 | 01-MAR-00:10 | 162.61 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 43.81 | 08-MAR-02:00 |
April | 0.00 | 01-APR-00:10 | 162.61 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 26-APR-13:00 | 34.77 | 15-APR-22:00 |
May | 0.00 | 01-MAY-00:10 | 162.61 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 35.08 | 15-MAY-02:00 |
June | 0.00 | 01-JUN-00:10 | 162.61 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 29.41 | 13-JUN-04:00 |
July | 0.00 | 01-JUL-00:10 | 162.61 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 19-JUL-12:00 | 26.21 | 06-JUL-01:00 |
August | 0.00 | 01-AUG-00:10 | 162.61 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.37 | 18-AUG-12:00 | 24.41 | 24-AUG-02:00 |
September | 0.00 | 01-SEP-00:10 | 162.61 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 29-SEP-11:00 | 30.07 | 20-SEP-03:00 |
October | 0.00 | 01-OCT-00:10 | 162.61 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 16-OCT-11:00 | 34.78 | 29-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 162.61 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 19-NOV-13:00 | 39.08 | 23-NOV-22:00 |
December | 0.00 | 01-DEC-00:10 | 162.61 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 43.34 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 162.61 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.41 | |||||
Maximum of Months | 0.00 | 162.61 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 18.38 | 50.29 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 162.65 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 14-JAN-11:00 | 40.90 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 162.65 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 01-FEB-12:00 | 32.18 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 162.65 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 11-MAR-11:00 | 34.42 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 162.65 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 26-APR-13:00 | 27.95 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 162.65 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 03-MAY-10:00 | 26.11 | 14-MAY-04:40 |
June | 180.00 | 01-JUN-00:10 | 162.65 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 | 30-JUN-10:00 | 19.90 | 13-JUN-04:50 |
July | 180.00 | 01-JUL-00:10 | 162.65 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 19-JUL-10:00 | 15.77 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 162.65 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.79 | 15-AUG-10:00 | 14.98 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 162.65 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.85 | 29-SEP-10:00 | 19.77 | 20-SEP-03:20 |
October | 180.00 | 01-OCT-00:10 | 162.65 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 | 16-OCT-10:01 | 24.09 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 162.65 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 | 19-NOV-10:00 | 28.08 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 162.65 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 | 05-DEC-10:00 | 32.26 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 14.98 | |||||
Maximum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 | 40.90 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 14-JAN-11:00 | 146.56 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 258.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 01-FEB-10:00 | 115.29 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 258.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 11-MAR-11:00 | 123.32 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 258.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 30-APR-10:00 | 100.15 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 03-MAY-10:00 | 93.26 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 258.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 30-JUN-10:00 | 71.32 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 258.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 | 19-JUL-10:00 | 56.51 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 258.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 15-AUG-10:00 | 57.43 | 28-AUG-07:30 |
September | 180.00 | 01-SEP-00:10 | 258.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.04 | 29-SEP-10:00 | 70.82 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 258.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 | 16-OCT-10:00 | 85.75 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 258.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 19-NOV-10:00 | 100.61 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 258.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 05-DEC-10:00 | 115.58 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 56.51 | |||||
Maximum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 89.22 | 146.56 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 | 14-JAN-11:00 | 146.55 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 258.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 01-FEB-12:00 | 115.28 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 258.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 11-MAR-11:00 | 123.31 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 258.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 30-APR-10:00 | 100.14 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 03-MAY-10:00 | 93.25 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 258.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 26-JUN-10:00 | 71.31 | 13-JUN-05:00 |
July | 180.00 | 01-JUL-00:10 | 258.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.65 | 19-JUL-10:00 | 56.51 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 258.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 15-AUG-10:00 | 57.43 | 28-AUG-07:30 |
September | 180.00 | 01-SEP-00:10 | 258.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.03 | 29-SEP-10:00 | 70.82 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 258.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 | 16-OCT-10:00 | 85.75 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 258.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.22 | 19-NOV-10:00 | 100.61 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 258.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 05-DEC-10:00 | 115.57 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 56.51 | |||||
Maximum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.21 | 146.55 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.91 | 14-JAN-11:00 | 147.04 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 258.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 01-FEB-10:00 | 115.74 | 04-FEB-05:55 |
March | 180.00 | 01-MAR-00:10 | 258.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 11-MAR-11:00 | 123.78 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 258.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 | 30-APR-10:00 | 100.60 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 03-MAY-10:00 | 93.70 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 258.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.62 | 26-JUN-10:00 | 71.75 | 13-JUN-04:40 |
July | 180.00 | 01-JUL-00:10 | 258.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 | 19-JUL-10:00 | 56.94 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 258.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 15-AUG-10:00 | 52.21 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 258.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.68 | 29-SEP-10:00 | 71.25 | 20-SEP-03:00 |
October | 180.00 | 01-OCT-00:10 | 258.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.86 | 16-OCT-10:00 | 86.20 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 258.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 19-NOV-10:00 | 101.06 | 24-NOV-01:00 |
December | 180.00 | 01-DEC-00:10 | 258.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 05-DEC-10:00 | 116.04 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 52.21 | |||||
Maximum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 88.86 | 147.04 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.91 | 14-JAN-11:00 | 147.02 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 258.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.36 | 01-FEB-12:00 | 115.73 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 258.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 11-MAR-11:00 | 123.77 | 08-MAR-04:00 |
April | 180.00 | 01-APR-00:10 | 258.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.28 | 30-APR-10:00 | 100.59 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 03-MAY-10:00 | 93.69 | 15-MAY-02:00 |
June | 180.00 | 01-JUN-00:10 | 258.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 30-JUN-10:00 | 71.75 | 13-JUN-04:30 |
July | 180.00 | 01-JUL-00:10 | 258.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 | 19-JUL-10:00 | 66.52 | 10-JUL-18:02 |
August | 180.00 | 01-AUG-00:10 | 258.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.27 | 15-AUG-10:00 | 65.34 | 26-AUG-18:00 |
September | 180.00 | 01-SEP-00:10 | 258.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.67 | 29-SEP-10:00 | 71.25 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 258.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 | 16-OCT-10:01 | 86.19 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 258.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.83 | 19-NOV-10:00 | 101.05 | 24-NOV-00:55 |
December | 180.00 | 01-DEC-00:10 | 258.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 05-DEC-10:00 | 116.03 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 65.34 | |||||
Maximum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 89.18 | 147.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 162.65 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 14-JAN-11:00 | 75.22 | 08-JAN-07:00 |
February | 180.00 | 01-FEB-00:10 | 162.65 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 | 01-FEB-10:00 | 59.21 | 04-FEB-06:00 |
March | 180.00 | 01-MAR-00:10 | 162.65 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 | 11-MAR-11:00 | 63.32 | 08-MAR-02:00 |
April | 180.00 | 01-APR-00:10 | 162.65 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.93 | 30-APR-10:00 | 51.46 | 01-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 162.65 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 03-MAY-10:00 | 47.94 | 15-MAY-05:00 |
June | 180.00 | 01-JUN-00:10 | 162.65 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 26-JUN-10:00 | 36.71 | 13-JUN-04:10 |
July | 180.00 | 01-JUL-00:10 | 162.65 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 19-JUL-10:00 | 29.13 | 06-JUL-01:00 |
August | 180.00 | 01-AUG-00:10 | 162.65 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.58 | 15-AUG-10:00 | 27.15 | 28-AUG-07:10 |
September | 180.00 | 01-SEP-00:10 | 162.65 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 | 29-SEP-10:00 | 36.45 | 20-SEP-03:10 |
October | 180.00 | 01-OCT-00:10 | 162.65 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.46 | 16-OCT-10:00 | 44.33 | 30-OCT-04:00 |
November | 180.00 | 01-NOV-00:10 | 162.65 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 19-NOV-10:20 | 51.89 | 30-NOV-02:20 |
December | 180.00 | 01-DEC-00:10 | 162.65 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 | 05-DEC-10:00 | 59.36 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 27.15 | |||||
Maximum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 45.46 | 75.22 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2281.19 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.10 | 13-JAN-14:00 | 359.29 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2281.19 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.60 | 01-FEB-12:00 | 319.60 | 04-FEB-05:55 |
March | 26988.77 | 01-MAR-00:10 | 2281.19 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 | 11-MAR-14:00 | 329.84 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 2281.19 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.72 | 26-APR-13:00 | 287.81 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2281.19 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.37 | 03-MAY-13:00 | 278.71 | 15-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2281.19 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 29-JUN-11:00 | 224.66 | 13-JUN-04:40 |
July | 26988.77 | 01-JUL-00:10 | 2281.19 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.29 | 31-JUL-12:00 | 187.80 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 2281.19 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.62 | 14-AUG-11:00 | 170.14 | 24-AUG-02:00 |
September | 26988.77 | 01-SEP-00:10 | 2281.19 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.92 | 29-SEP-11:00 | 223.13 | 20-SEP-03:10 |
October | 26988.77 | 02-OCT-00:10 | 2281.19 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.75 | 16-OCT-11:00 | 260.14 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2281.19 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.57 | 19-NOV-13:00 | 296.80 | 23-NOV-22:00 |
December | 26988.77 | 01-DEC-00:10 | 2281.19 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.78 | 05-DEC-10:00 | 315.81 | 23-DEC-04:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 | 170.14 | |||||
Maximum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 220.75 | 359.29 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2281.19 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.76 | 13-JAN-14:00 | 361.95 | 08-JAN-07:00 |
February | 26988.77 | 01-FEB-00:10 | 2281.19 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 01-FEB-12:00 | 322.29 | 04-FEB-05:55 |
March | 26988.77 | 01-MAR-00:10 | 2281.19 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 11-MAR-14:00 | 333.36 | 08-MAR-02:00 |
April | 26988.77 | 01-APR-00:10 | 2281.19 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.37 | 26-APR-13:00 | 291.73 | 01-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2281.19 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.06 | 03-MAY-13:00 | 278.71 | 15-MAY-05:00 |
June | 26988.77 | 01-JUN-00:10 | 2281.19 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 29-JUN-11:00 | 224.67 | 13-JUN-04:40 |
July | 26988.77 | 01-JUL-00:10 | 2281.19 | 03-JUL-19:10 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.24 | 31-JUL-13:00 | 187.81 | 06-JUL-01:00 |
August | 26988.77 | 01-AUG-00:10 | 2281.19 | 01-AUG-19:10 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.70 | 17-AUG-14:00 | 170.15 | 24-AUG-02:00 |
September | 26988.77 | 01-SEP-00:10 | 2281.19 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.11 | 29-SEP-11:00 | 223.13 | 20-SEP-03:10 |
October | 26988.77 | 02-OCT-00:10 | 2281.19 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 16-OCT-11:00 | 260.15 | 30-OCT-04:00 |
November | 26988.77 | 01-NOV-00:10 | 2281.19 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.47 | 19-NOV-13:00 | 296.80 | 23-NOV-22:00 |
December | 26988.77 | 01-DEC-00:10 | 2281.19 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 | 19-DEC-13:00 | 319.07 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 170.15 | |||||
Maximum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 216.55 | 361.95 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 27.88 | 14-JAN-11:40 | 319.61 | 08-JAN-07:00 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 27.70 | 01-FEB-12:00 | 268.03 | 09-FEB-07:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.62 | 29-MAR-22:50 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 42.04 | 26-APR-13:00 | 263.03 | 01-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 244.78 | 19-MAY-05:00 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 13.25 | 29-JUN-11:00 | 201.11 | 13-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 56.38 | 19-JUL-12:00 | 147.58 | 06-JUL-01:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 56.50 | 18-AUG-12:00 | 151.84 | 28-AUG-06:10 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 166.97 | 29-SEP-11:00 | 184.08 | 20-SEP-03:30 |
October | 2401.70 | 02-OCT-00:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 180.76 | 16-OCT-11:00 | 232.58 | 12-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 42.10 | 19-NOV-13:00 | 265.72 | 23-NOV-22:00 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 27.94 | 16-DEC-13:00 | 298.63 | 22-DEC-07:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 147.58 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 180.76 | 319.61 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1511.55 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.33 | 13-JAN-14:00 | 228.21 | 08-JAN-07:00 |
February | 0.00 | 1511.55 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.72 | 01-FEB-12:00 | 179.69 | 04-FEB-05:55 |
March | 0.00 | 1511.55 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.49 | 11-MAR-11:13 | 192.10 | 08-MAR-04:00 |
April | 0.00 | 1511.55 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 | 26-APR-13:00 | 155.70 | 01-APR-06:00 |
May | 0.00 | 1511.55 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 | 03-MAY-13:00 | 148.07 | 27-MAY-03:00 |
June | 0.00 | 1511.55 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.29 | 29-JUN-11:00 | 114.94 | 13-JUN-05:00 |
July | 0.00 | 1511.55 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.29 | 31-JUL-13:00 | 94.88 | 06-JUL-01:00 |
August | 0.00 | 1511.55 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.19 | 14-AUG-11:00 | 84.42 | 28-AUG-07:00 |
September | 0.00 | 1511.55 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.20 | 29-SEP-11:00 | 114.43 | 20-SEP-03:00 |
October | 0.00 | 1511.55 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.59 | 16-OCT-11:00 | 139.66 | 29-OCT-06:00 |
November | 0.00 | 1511.55 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.89 | 19-NOV-13:00 | 169.48 | 29-NOV-23:00 |
December | 0.00 | 1511.55 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 | 16-DEC-13:00 | 182.37 | 03-DEC-01:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 | 84.42 | ||||
Maximum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 151.59 | 228.21 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 187.90 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 | 13-JAN-14:00 | 158.07 | 08-JAN-07:00 |
February | 0.00 | 187.90 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.00 | 01-FEB-12:00 | 124.80 | 04-FEB-05:55 |
March | 0.00 | 187.90 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.59 | 11-MAR-11:10 | 133.57 | 08-MAR-02:00 |
April | 0.00 | 187.90 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 26-APR-13:00 | 108.26 | 01-APR-06:00 |
May | 0.00 | 187.90 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 03-MAY-13:00 | 101.56 | 27-MAY-03:00 |
June | 0.00 | 187.90 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.57 | 29-JUN-11:00 | 78.65 | 13-JUN-05:00 |
July | 0.00 | 187.90 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 | 31-JUL-12:00 | 64.71 | 06-JUL-01:00 |
August | 0.00 | 187.90 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 14-AUG-11:00 | 56.68 | 28-AUG-07:00 |
September | 0.00 | 187.90 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.49 | 29-SEP-11:00 | 78.49 | 20-SEP-03:00 |
October | 0.00 | 187.90 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 16-OCT-11:00 | 95.05 | 29-OCT-06:00 |
November | 0.00 | 187.90 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 | 19-NOV-13:00 | 113.78 | 29-NOV-23:00 |
December | 0.00 | 187.90 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 | 16-DEC-13:00 | 125.11 | 22-DEC-07:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 187.90 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 56.68 | ||||
Maximum of Months | 0.00 | 187.90 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 158.07 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1350.19 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | 14-JAN-11:00 | 170.80 | 08-JAN-07:00 |
February | 0.00 | 1350.19 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 01-FEB-12:00 | 137.65 | 04-FEB-05:55 |
March | 0.00 | 1350.19 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 | 11-MAR-11:00 | 145.69 | 08-MAR-02:00 |
April | 0.00 | 1350.19 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.59 | 26-APR-13:00 | 118.93 | 01-APR-06:00 |
May | 0.00 | 1350.19 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.91 | 03-MAY-12:40 | 111.82 | 15-MAY-02:00 |
June | 0.00 | 1350.19 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.84 | 29-JUN-11:00 | 85.31 | 13-JUN-04:50 |
July | 0.00 | 1350.19 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.46 | 19-JUL-12:00 | 67.40 | 06-JUL-01:00 |
August | 0.00 | 1350.19 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.57 | 18-AUG-12:00 | 58.77 | 31-AUG-04:00 |
September | 0.00 | 1350.19 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.97 | 29-SEP-11:00 | 84.71 | 20-SEP-04:00 |
October | 0.00 | 1350.19 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 | 16-OCT-11:00 | 102.75 | 30-OCT-04:00 |
November | 0.00 | 1350.19 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.20 | 19-NOV-13:00 | 120.71 | 24-NOV-00:55 |
December | 0.00 | 1350.19 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 | 16-DEC-13:00 | 138.47 | 03-DEC-01:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 | 58.77 | |||
Maximum of Months | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 | 170.80 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1428.96 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.33 | 14-JAN-11:00 | 304.08 | 08-JAN-07:00 |
February | 0.00 | 1428.96 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.52 | 01-FEB-12:00 | 245.97 | 04-FEB-05:55 |
March | 0.00 | 1428.96 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 11-MAR-11:00 | 263.15 | 08-MAR-02:00 |
April | 0.00 | 1428.96 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.07 | 26-APR-13:00 | 213.56 | 01-APR-06:00 |
May | 0.00 | 1428.96 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 03-MAY-12:00 | 198.84 | 15-MAY-05:00 |
June | 0.00 | 1428.96 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.98 | 29-JUN-11:00 | 151.89 | 13-JUN-04:20 |
July | 0.00 | 1428.96 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.60 | 19-JUL-11:00 | 120.73 | 06-JUL-01:00 |
August | 0.00 | 1428.96 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.77 | 14-AUG-11:00 | 106.36 | 28-AUG-07:00 |
September | 0.00 | 1428.96 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.83 | 29-SEP-11:00 | 150.83 | 20-SEP-03:30 |
October | 0.00 | 1428.96 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.03 | 16-OCT-11:00 | 182.78 | 30-OCT-04:00 |
November | 0.00 | 1428.96 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.54 | 19-NOV-13:00 | 214.55 | 24-NOV-00:55 |
December | 0.00 | 1428.96 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.46 | 05-DEC-10:00 | 246.60 | 22-DEC-07:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1428.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 106.36 | |||
Maximum of Months | 0.00 | 1428.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.03 | 304.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 22206.19 | 08-JAN-07:00 | 8945.92 | 4513.94 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16756.71 | 04-FEB-05:55 | 23003.78 | 3009.29 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17574.06 | 08-MAR-02:00 | 11501.89 | 2256.97 | 2534.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 14383.75 | 26-APR-07:45 | 10223.90 | 12037.17 | 10139.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14226.52 | 28-MAY-10:00 | 6389.94 | 4513.94 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 14281.13 | 29-JUN-18:10 | 62621.41 | 84260.17 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14859.82 | 19-JUL-18:50 | 8945.92 | 12037.17 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14771.21 | 14-AUG-18:50 | 8945.92 | 12037.17 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16247.99 | 21-SEP-21:10 | 11501.89 | 9027.87 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16137.99 | 16-OCT-19:50 | 8945.92 | 13541.81 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16371.78 | 29-NOV-23:00 | 11501.89 | 9027.87 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18038.61 | 03-DEC-01:00 | 8945.92 | 4513.94 | 4055.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 14226.52 | 6389.94 | 2256.97 | 2534.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22206.19 | 62621.41 | 84260.17 | 63878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3106.58 | 14-JAN-12:40 | 389.84 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 30.17 | 0.00 |
February | 2545.01 | 02-FEB-12:40 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.76 |
March | 2198.59 | 11-MAR-13:10 | 389.84 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
April | 1943.62 | 08-APR-12:50 | 389.84 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
May | 1794.98 | 04-MAY-12:40 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | 0.00 |
June | 1765.04 | 29-JUN-18:10 | 6367.45 | 4285.50 | 4546.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
July | 1830.08 | 19-JUL-18:30 | 1819.27 | 1224.43 | 1299.04 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 0.00 |
August | 1904.53 | 27-AUG-12:00 | 389.84 | 229.58 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 0.00 |
September | 2940.13 | 30-SEP-13:10 | 779.69 | 382.63 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 176.05 | 0.00 |
October | 3716.48 | 16-OCT-12:10 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 255.29 | 0.00 |
November | 3397.90 | 19-NOV-12:30 | 389.84 | 229.58 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 56.31 | 0.00 |
December | 3197.23 | 19-DEC-12:50 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1765.04 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3716.48 | 6367.45 | 4285.50 | 4546.63 | 0.00 | 0.00 | 0.00 | 0.00 | 255.29 | 107.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1733.05 | 03-JAN-01:55 | 2708.64 | 265.85 | 417.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.87 |
February | 1578.94 | 04-FEB-05:55 | 2708.64 | 177.24 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.83 |
March | 1616.52 | 08-MAR-02:00 | 1354.32 | 132.93 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.77 |
April | 1458.06 | 26-APR-20:20 | 1203.84 | 708.95 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 |
May | 1477.11 | 04-MAY-21:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.79 |
June | 1500.75 | 29-JUN-18:30 | 2106.72 | 1417.89 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 |
July | 1553.90 | 19-JUL-19:00 | 2106.72 | 1417.89 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 |
August | 1568.28 | 18-AUG-21:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 |
September | 1695.05 | 29-SEP-21:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 0.00 |
October | 1694.67 | 16-OCT-19:50 | 1053.36 | 797.56 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.71 |
November | 1554.11 | 29-NOV-23:00 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.19 |
December | 1590.25 | 03-DEC-01:00 | 1053.36 | 265.85 | 334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1458.06 | 1053.36 | 132.93 | 208.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1733.05 | 2708.64 | 1417.89 | 1504.29 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 | 93.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1499.93 | 06-JAN-23:00 | 0.00 | 1007.70 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.68 |
February | 1404.86 | 04-FEB-05:55 | 0.00 | 335.90 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.69 |
March | 1356.73 | 07-MAR-23:00 | 0.00 | 1007.70 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.19 |
April | 1323.51 | 26-APR-07:45 | 0.00 | 1343.60 | 883.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
May | 1321.51 | 04-MAY-09:30 | 0.00 | 419.88 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 |
June | 1387.20 | 29-JUN-18:10 | 0.00 | 9405.22 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 |
July | 1438.29 | 19-JUL-19:00 | 0.00 | 2687.21 | 1590.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.79 |
August | 1416.68 | 19-AUG-18:50 | 0.00 | 1175.65 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.49 |
September | 1514.19 | 29-SEP-21:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 | 0.00 |
October | 1534.53 | 16-OCT-19:50 | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.12 |
November | 1348.47 | 29-NOV-23:00 | 0.00 | 1007.70 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.48 |
December | 1454.60 | 03-DEC-01:00 | 0.00 | 503.85 | 353.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1321.51 | 0.00 | 335.90 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1534.53 | 0.00 | 9405.22 | 5566.86 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 | 187.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 603.65 | 06-JAN-23:00 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.62 |
February | 556.92 | 04-FEB-05:45 | 0.00 | 41.76 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.54 |
March | 542.04 | 23-MAR-09:50 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
April | 553.07 | 30-APR-11:00 | 0.00 | 62.63 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 34.10 | 0.00 |
May | 558.87 | 04-MAY-09:40 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
June | 575.77 | 30-JUN-08:35 | 0.00 | 167.02 | 254.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 |
July | 588.74 | 19-JUL-18:50 | 0.00 | 167.02 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 |
August | 582.44 | 19-AUG-18:50 | 0.00 | 146.15 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 |
September | 617.27 | 29-SEP-21:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 | 0.00 |
October | 624.17 | 16-OCT-19:50 | 0.00 | 187.90 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.32 |
November | 570.89 | 19-NOV-13:10 | 0.00 | 41.76 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 | 0.00 |
December | 583.84 | 03-DEC-00:45 | 0.00 | 125.27 | 203.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.50 |
Annual Sum or Average | |||||||||||
Minimum of Months | 542.04 | 0.00 | 41.76 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 624.17 | 0.00 | 187.90 | 254.90 | 0.00 | 0.00 | 0.00 | 0.00 | 36.43 | 126.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37255.41 | 24-JAN-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 105.56 |
February | 37072.96 | 23-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 150.92 |
March | 37406.25 | 23-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 151.73 |
April | 37556.82 | 26-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 105.14 |
May | 37559.91 | 04-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 105.25 |
June | 37537.22 | 30-JUN-20:00 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 0.00 | 120.47 |
July | 37742.32 | 19-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.58 |
August | 37692.12 | 18-AUG-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 74.64 |
September | 38042.16 | 29-SEP-19:53 | 2822.40 | 1300.34 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 14.52 | 0.00 |
October | 37954.21 | 16-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 44.39 |
November | 37227.59 | 20-NOV-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 151.88 |
December | 37346.75 | 05-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 121.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 37072.96 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38042.16 | 2822.40 | 1300.34 | 18291.20 | 158906.31 | 0.00 | 0.00 | 0.00 | 14.52 | 151.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12221.93 | 14-JAN-12:40 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 76.22 | 0.00 |
February | 9889.20 | 04-FEB-12:30 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.74 |
March | 9366.01 | 11-MAR-13:10 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 0.00 |
April | 8420.21 | 08-APR-12:40 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.08 |
May | 8273.10 | 04-MAY-22:00 | 15368.40 | 866.01 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.03 |
June | 8170.61 | 27-JUN-22:00 | 15368.40 | 866.01 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.29 |
July | 8540.90 | 31-JUL-21:20 | 138315.60 | 7794.11 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.91 |
August | 8677.99 | 18-AUG-22:00 | 15368.40 | 866.01 | 711.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.97 |
September | 10917.47 | 30-SEP-12:00 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 444.89 | 0.00 |
October | 12803.85 | 15-OCT-12:00 | 5122.80 | 95.26 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 447.00 | 0.00 |
November | 13326.90 | 19-NOV-11:00 | 8538.00 | 95.26 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 114.07 | 0.00 |
December | 12151.28 | 16-DEC-13:00 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 114.66 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8170.61 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13326.90 | 138315.60 | 7794.11 | 6401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 447.00 | 385.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 37926.91 | 09-JAN-05:55 | 91245.96 | 5970.43 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2384.02 |
February | 33601.88 | 04-FEB-05:55 | 91245.96 | 2985.21 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2147.26 |
March | 34075.91 | 08-MAR-02:00 | 45622.98 | 2238.91 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2182.82 |
April | 30293.99 | 26-APR-22:00 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 908.53 |
May | 31112.39 | 04-MAY-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.89 |
June | 30947.52 | 29-JUN-18:30 | 70969.08 | 23881.71 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.85 |
July | 32208.32 | 31-JUL-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 535.21 |
August | 32496.26 | 18-AUG-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.94 |
September | 34999.63 | 29-SEP-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 | 0.00 |
October | 35682.04 | 16-OCT-22:00 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.01 |
November | 32647.20 | 29-NOV-23:00 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2041.92 |
December | 32962.90 | 03-DEC-01:00 | 35484.54 | 4477.82 | 4222.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2112.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 30293.99 | 35484.54 | 2238.91 | 2639.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37926.91 | 91245.96 | 23881.71 | 19002.71 | 0.00 | 0.00 | 0.00 | 0.00 | 67.35 | 2384.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3181.31 | 14-JAN-16:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 0.00 |
February | 3188.40 | 03-FEB-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 |
March | 2857.55 | 19-MAR-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.71 |
April | 2953.86 | 01-APR-18:02 | 702.00 | 1552.43 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 |
May | 2913.94 | 24-MAY-08:61 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 |
June | 2915.76 | 15-JUN-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
July | 2916.46 | 16-JUL-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
August | 2916.04 | 09-AUG-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.00 |
September | 2889.92 | 05-SEP-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
October | 3230.97 | 14-OCT-08:61 | 540.00 | 603.72 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 32.80 | 0.00 |
November | 3152.70 | 27-NOV-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 |
December | 3189.40 | 19-DEC-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.94 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2857.55 | 252.00 | 113.20 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3230.97 | 702.00 | 1552.43 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 32.80 | 31.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3089.05 | 14-JAN-16:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
February | 3095.48 | 03-FEB-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 |
March | 2780.87 | 09-MAR-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 |
April | 2925.30 | 27-APR-18:21 | 1386.00 | 2296.03 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.37 |
May | 2947.94 | 24-MAY-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.95 |
June | 2853.50 | 18-JUN-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 0.00 |
July | 2865.08 | 17-JUL-15:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 8.47 | 0.00 |
August | 2864.14 | 02-AUG-15:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 0.00 |
September | 2866.94 | 13-SEP-15:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
October | 3243.38 | 14-OCT-08:61 | 540.00 | 603.65 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 0.00 |
November | 3063.18 | 27-NOV-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
December | 3095.64 | 19-DEC-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2780.87 | 360.00 | 113.18 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3243.38 | 1386.00 | 2296.03 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 60.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 553.98 | 14-JAN-12:20 | 0.00 | 10.16 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 |
February | 478.40 | 02-FEB-12:30 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.64 |
March | 375.07 | 11-MAR-12:50 | 0.00 | 10.16 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
April | 253.50 | 04-APR-15:03 | 0.00 | 91.06 | 343.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 |
May | 209.17 | 04-MAY-20:40 | 0.00 | 144.31 | 178.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
June | 203.46 | 24-JUN-08:00 | 0.00 | 182.93 | 464.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 |
July | 240.86 | 23-JUL-08:00 | 0.00 | 91.47 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.97 |
August | 271.88 | 19-AUG-15:03 | 0.00 | 60.98 | 325.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 |
September | 469.13 | 30-SEP-13:00 | 0.00 | 10.16 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 9.55 | 0.00 |
October | 606.69 | 16-OCT-12:10 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 0.00 |
November | 592.81 | 19-NOV-10:00 | 0.00 | 37.94 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
December | 571.67 | 19-DEC-12:30 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 203.46 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 606.69 | 0.00 | 182.93 | 464.38 | 0.00 | 0.00 | 0.00 | 0.00 | 16.08 | 18.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1077.05 | 15-JAN-16:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.75 |
February | 1050.13 | 03-FEB-16:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.73 |
March | 1066.22 | 11-MAR-09:11 | 432.00 | 303.62 | 1279.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
April | 1059.90 | 01-APR-15:02 | 324.00 | 60.99 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
May | 1056.32 | 24-MAY-08:11 | 360.00 | 711.60 | 1109.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.94 |
June | 1025.09 | 24-JUN-08:11 | 486.00 | 341.57 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.32 |
July | 1034.62 | 04-JUL-08:11 | 540.00 | 379.52 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
August | 991.77 | 01-AUG-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.01 |
September | 987.30 | 01-SEP-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 |
October | 1185.99 | 14-OCT-08:61 | 540.00 | 379.52 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 0.00 |
November | 1105.10 | 19-NOV-09:11 | 486.00 | 341.57 | 1439.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.97 | 0.00 |
December | 1083.22 | 05-DEC-09:11 | 324.00 | 640.44 | 998.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4.48 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 987.30 | 324.00 | 60.99 | 325.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1185.99 | 680.40 | 711.60 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 7.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2803.42 | 14-JAN-16:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.98 | 0.00 |
February | 2817.30 | 01-FEB-09:01 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 |
March | 2534.39 | 23-MAR-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.70 |
April | 2794.27 | 02-APR-08:61 | 378.00 | 422.61 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.38 |
May | 2800.76 | 24-MAY-08:61 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 |
June | 2540.24 | 22-JUN-08:62 | 216.00 | 679.19 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.62 |
July | 2601.55 | 23-JUL-08:61 | 378.00 | 422.61 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.34 | 0.00 |
August | 2533.51 | 06-AUG-08:61 | 378.00 | 422.61 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.30 |
September | 2563.33 | 11-SEP-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 |
October | 2890.51 | 14-OCT-08:61 | 540.00 | 603.72 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 0.00 |
November | 2822.12 | 27-NOV-09:01 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 |
December | 2840.71 | 05-DEC-09:01 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2533.51 | 216.00 | 113.20 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2890.51 | 680.40 | 792.39 | 1633.07 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 36.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2681.14 | 14-JAN-16:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 6.38 | 0.00 |
February | 2769.00 | 01-FEB-09:11 | 252.00 | 792.29 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 0.00 |
March | 2574.25 | 23-MAR-08:11 | 288.00 | 905.48 | 905.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 |
April | 2941.63 | 02-APR-08:11 | 486.00 | 543.29 | 1469.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.91 |
May | 3065.35 | 24-MAY-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.85 |
June | 2822.27 | 14-JUN-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.15 |
July | 2874.04 | 04-JUL-08:11 | 540.00 | 603.65 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 |
August | 2701.81 | 23-AUG-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 |
September | 2766.92 | 30-SEP-08:11 | 540.00 | 603.65 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
October | 3328.13 | 17-OCT-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
November | 2726.37 | 27-NOV-09:12 | 216.00 | 679.11 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 |
December | 2982.25 | 05-DEC-09:11 | 324.00 | 1018.66 | 1019.23 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2574.25 | 216.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3328.13 | 540.00 | 1131.85 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 41.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1688.49 | 18-JAN-14:30 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 | 0.00 |
February | 1672.14 | 01-FEB-13:00 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 | 0.00 |
March | 1614.90 | 11-MAR-14:00 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.85 | 0.00 |
April | 1551.52 | 26-APR-18:06 | 0.00 | 8401.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
May | 1519.00 | 04-MAY-18:01 | 0.00 | 8401.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
June | 1686.31 | 29-JUN-18:04 | 0.00 | 8401.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.69 | 0.00 |
July | 1696.46 | 19-JUL-18:35 | 0.00 | 2400.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 | 0.00 |
August | 1688.73 | 14-AUG-18:15 | 0.00 | 2400.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 0.00 |
September | 1750.18 | 30-SEP-14:30 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.89 | 0.00 |
October | 1777.00 | 16-OCT-13:50 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 | 0.00 |
November | 1712.51 | 19-NOV-13:10 | 0.00 | 300.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 | 0.00 |
December | 1692.66 | 19-DEC-13:40 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1519.00 | 0.00 | 300.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1777.00 | 0.00 | 8401.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.63 | 19.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3293.46 | 14-JAN-16:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
February | 3297.28 | 03-FEB-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 |
March | 2872.00 | 21-MAR-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.88 |
April | 3083.74 | 01-APR-18:02 | 702.00 | 1552.43 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.99 |
May | 3016.75 | 24-MAY-08:61 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.32 |
June | 3014.16 | 29-JUN-18:01 | 970.20 | 1607.41 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.58 |
July | 3010.76 | 22-JUL-18:01 | 819.00 | 1811.17 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.41 |
August | 2980.73 | 05-AUG-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 | 0.00 |
September | 2956.84 | 18-SEP-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.59 |
October | 3343.78 | 13-OCT-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 0.00 |
November | 3256.84 | 27-NOV-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
December | 3302.20 | 19-DEC-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2872.00 | 252.00 | 113.20 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3343.78 | 970.20 | 1811.17 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 32.28 | 39.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3194.09 | 14-JAN-16:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 0.00 |
February | 3197.34 | 03-FEB-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 |
March | 2916.85 | 23-MAR-15:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.35 |
April | 3298.16 | 27-APR-18:21 | 1386.00 | 2296.03 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.94 |
May | 3144.75 | 18-MAY-18:31 | 1386.00 | 2296.03 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.03 |
June | 3081.92 | 04-JUN-18:51 | 1053.00 | 2328.37 | 1090.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.61 |
July | 2926.34 | 04-JUL-21:11 | 1247.40 | 1979.12 | 805.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.27 |
August | 2879.35 | 05-AUG-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
September | 2911.76 | 09-SEP-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
October | 3355.90 | 15-OCT-21:11 | 1108.80 | 1759.21 | 716.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.71 |
November | 3159.08 | 27-NOV-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
December | 3201.23 | 19-DEC-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2879.35 | 378.00 | 113.18 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3355.90 | 1386.00 | 2328.37 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 | 69.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1697.15 | 14-JAN-16:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 | 0.00 |
February | 1687.10 | 03-FEB-16:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 |
March | 1485.46 | 18-MAR-15:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.45 |
April | 1580.22 | 01-APR-18:02 | 702.00 | 975.91 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.16 |
May | 1522.13 | 24-MAY-08:61 | 252.00 | 498.12 | 776.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
June | 1452.86 | 21-JUN-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.69 |
July | 1483.67 | 30-JUL-15:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 0.00 |
August | 1521.17 | 21-AUG-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
September | 1525.46 | 09-SEP-15:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 |
October | 1702.25 | 14-OCT-08:61 | 540.00 | 379.52 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 0.00 |
November | 1688.01 | 19-NOV-09:02 | 324.00 | 227.71 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 | 0.00 |
December | 1697.26 | 29-DEC-16:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1452.86 | 252.00 | 71.16 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1702.25 | 702.00 | 975.91 | 1599.98 | 0.00 | 0.00 | 0.00 | 0.00 | 16.04 | 20.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18128.99 | 18-JAN-22:14 | 134943.84 | 7603.95 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.21 |
February | 18047.18 | 15-FEB-23:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.27 |
March | 18312.94 | 24-MAR-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.54 |
April | 18889.71 | 26-APR-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.93 |
May | 19221.00 | 04-MAY-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.71 |
June | 19398.89 | 27-JUN-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.52 |
July | 19600.14 | 19-JUL-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.49 |
August | 19479.30 | 17-AUG-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 |
September | 20060.78 | 29-SEP-21:12 | 215910.14 | 12166.33 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 0.00 |
October | 19765.55 | 16-OCT-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 |
November | 18103.49 | 01-NOV-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.53 |
December | 18332.70 | 05-DEC-23:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18047.18 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20060.78 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 189.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20074.18 | 18-JAN-22:14 | 134943.84 | 7603.95 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.21 |
February | 20023.73 | 15-FEB-23:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.27 |
March | 20211.83 | 24-MAR-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.54 |
April | 20796.14 | 26-APR-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.94 |
May | 21114.74 | 04-MAY-21:13 | 161932.61 | 9124.74 | 40487.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.80 |
June | 21276.74 | 27-JUN-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.52 |
July | 21458.03 | 19-JUL-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.50 |
August | 21323.44 | 17-AUG-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.82 |
September | 21864.32 | 29-SEP-21:12 | 215910.14 | 12166.33 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 0.00 |
October | 21444.17 | 16-OCT-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 |
November | 20002.53 | 01-NOV-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.54 |
December | 20202.80 | 05-DEC-23:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20002.53 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21864.32 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 7.51 | 189.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 28472.94 | 14-JAN-11:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.87 | 0.00 |
February | 28153.39 | 01-FEB-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 20.48 | 0.00 |
March | 28906.42 | 12-MAR-10:50 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 43.23 |
April | 29192.70 | 30-APR-10:40 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 22.97 | 0.00 |
May | 28804.60 | 02-MAY-10:40 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 |
June | 29046.18 | 25-JUN-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
July | 29427.16 | 23-JUL-10:50 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 25.34 | 0.00 |
August | 29273.20 | 15-AUG-10:40 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 42.06 | 0.00 |
September | 29802.11 | 30-SEP-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 95.27 | 0.00 |
October | 29836.03 | 15-OCT-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 108.03 | 0.00 |
November | 28979.88 | 19-NOV-11:50 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 27.69 | 0.00 |
December | 28273.23 | 17-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 28153.39 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29836.03 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 108.03 | 43.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3527.90 | 14-JAN-14:30 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 0.00 |
February | 3459.65 | 01-FEB-13:10 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.19 | 0.00 |
March | 3525.08 | 11-MAR-13:40 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 0.00 |
April | 3518.71 | 26-APR-13:40 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.33 | 0.00 |
May | 3528.93 | 04-MAY-12:40 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 0.00 |
June | 3517.99 | 30-JUN-15:55 | 0.00 | 793.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 0.00 |
July | 3623.41 | 30-JUL-13:40 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 | 0.00 |
August | 3636.69 | 19-AUG-14:00 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.46 | 0.00 |
September | 3919.76 | 30-SEP-14:00 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.53 | 0.00 |
October | 3951.16 | 16-OCT-13:20 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 | 0.00 |
November | 3649.21 | 19-NOV-13:10 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.81 | 0.00 |
December | 3577.01 | 19-DEC-13:10 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3459.65 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.04 | 0.00 | |
Maximum of Months | 3951.16 | 0.00 | 793.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.43 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.417827E+12 | 297528.35 | 17-JAN-20:10 | 0.481907E+12 | 409416.59 | 06-JAN-18:30 |
February | 0.366876E+12 | 286198.40 | 13-FEB-20:40 | 0.419184E+12 | 391265.09 | 21-FEB-20:49 |
March | 0.400733E+12 | 280931.95 | 23-MAR-19:10 | 0.493146E+12 | 406402.40 | 07-MAR-18:19 |
April | 0.412542E+12 | 299743.50 | 26-APR-19:10 | 0.390792E+12 | 357664.24 | 15-APR-21:49 |
May | 0.426936E+12 | 299128.65 | 04-MAY-19:10 | 0.393412E+12 | 361563.38 | 10-MAY-19:49 |
June | 0.452116E+12 | 312939.48 | 29-JUN-19:10 | 0.336025E+12 | 306922.72 | 12-JUN-20:49 |
July | 0.526348E+12 | 341172.75 | 31-JUL-19:10 | 0.336621E+12 | 279319.80 | 13-JUL-17:10 |
August | 0.541618E+12 | 335153.44 | 14-AUG-19:10 | 0.335755E+12 | 279224.65 | 22-AUG-17:30 |
September | 0.481127E+12 | 363531.40 | 29-SEP-19:10 | 0.329892E+12 | 281518.79 | 21-SEP-17:19 |
October | 0.497957E+12 | 343779.56 | 04-OCT-19:49 | 0.358074E+12 | 306171.98 | 11-OCT-20:49 |
November | 0.410313E+12 | 286252.87 | 10-NOV-20:49 | 0.417769E+12 | 382953.99 | 04-NOV-19:40 |
December | 0.421954E+12 | 294754.60 | 05-DEC-20:10 | 0.477284E+12 | 408667.69 | 13-DEC-18:40 |
Annual Sum or Average | 0.535635E+13 | 0.476986E+13 | ||||
Minimum of Months | 0.366876E+12 | 280931.95 | 0.329892E+12 | 279224.65 | ||
Maximum of Months | 0.541618E+12 | 363531.40 | 0.493146E+12 | 409416.59 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.706869E+11 | 0.180211E+11 | 0.140828E+12 | 0.825756E+11 | 0.428794E+11 | 0.429607E+10 | 0.00 | 0.456090E+11 | 0.00 | 0.00 | 0.00 | 0.770538E+10 | 0.00 |
February | 0.636831E+11 | 0.154038E+11 | 0.127191E+12 | 0.745844E+11 | 0.389887E+11 | 0.384081E+10 | 0.00 | 0.314789E+11 | 0.00 | 0.00 | 0.00 | 0.696255E+10 | 0.00 |
March | 0.704780E+11 | 0.157876E+11 | 0.140892E+12 | 0.825781E+11 | 0.430319E+11 | 0.429077E+10 | 0.00 | 0.307050E+11 | 0.00 | 0.00 | 0.00 | 0.770517E+10 | 0.00 |
April | 0.678258E+11 | 0.140358E+11 | 0.136245E+12 | 0.799113E+11 | 0.416009E+11 | 0.392665E+10 | 0.00 | 0.564163E+11 | 0.00 | 0.00 | 0.00 | 0.746560E+10 | 0.00 |
May | 0.699414E+11 | 0.134006E+11 | 0.140860E+12 | 0.825764E+11 | 0.427271E+11 | 0.402860E+10 | 0.00 | 0.604041E+11 | 0.00 | 0.00 | 0.00 | 0.770508E+10 | 0.00 |
June | 0.676469E+11 | 0.124235E+11 | 0.136336E+12 | 0.799136E+11 | 0.410433E+11 | 0.374310E+10 | 0.00 | 0.984101E+11 | 0.00 | 0.00 | 0.00 | 0.745780E+10 | 0.00 |
July | 0.698232E+11 | 0.130796E+11 | 0.140770E+12 | 0.825739E+11 | 0.424798E+11 | 0.420662E+10 | 0.00 | 0.160419E+12 | 0.00 | 0.00 | 0.00 | 0.771350E+10 | 0.00 |
August | 0.700906E+11 | 0.140079E+11 | 0.140892E+12 | 0.825779E+11 | 0.426328E+11 | 0.432400E+10 | 0.00 | 0.174080E+12 | 0.00 | 0.00 | 0.00 | 0.770535E+10 | 0.00 |
September | 0.680701E+11 | 0.147477E+11 | 0.136245E+12 | 0.799115E+11 | 0.410931E+11 | 0.389499E+10 | 0.00 | 0.124563E+12 | 0.00 | 0.00 | 0.00 | 0.746596E+10 | 0.00 |
October | 0.706060E+11 | 0.165275E+11 | 0.140828E+12 | 0.825755E+11 | 0.428499E+11 | 0.415362E+10 | 0.00 | 0.127450E+12 | 0.00 | 0.00 | 0.00 | 0.770532E+10 | 0.00 |
November | 0.683937E+11 | 0.171207E+11 | 0.136330E+12 | 0.799125E+11 | 0.420718E+11 | 0.407342E+10 | 0.00 | 0.498902E+11 | 0.00 | 0.00 | 0.00 | 0.744966E+10 | 0.00 |
December | 0.706150E+11 | 0.183282E+11 | 0.140770E+12 | 0.825744E+11 | 0.432079E+11 | 0.433825E+10 | 0.00 | 0.491998E+11 | 0.00 | 0.00 | 0.00 | 0.771337E+10 | 0.00 |
Annual Sum or Average | 0.827861E+12 | 0.182884E+12 | 0.165819E+13 | 0.972265E+12 | 0.504607E+12 | 0.491169E+11 | 0.00 | 0.100863E+13 | 0.907547E+11 | ||||
Minimum of Months | 0.636831E+11 | 0.124235E+11 | 0.127191E+12 | 0.745844E+11 | 0.389887E+11 | 0.374310E+10 | 0.00 | 0.307050E+11 | 0.00 | 0.00 | 0.00 | 0.696255E+10 | 0.00 |
Maximum of Months | 0.706869E+11 | 0.183282E+11 | 0.140892E+12 | 0.825781E+11 | 0.432079E+11 | 0.433825E+10 | 0.00 | 0.174080E+12 | 0.00 | 0.00 | 0.00 | 0.771350E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.153198E+12 | 0.00 | 0.176791E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.121889E+12 | 0.00 | 0.160091E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.164411E+12 | 0.00 | 0.176697E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.749596E+11 | 0.00 | 0.168876E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.690632E+11 | 0.00 | 0.172370E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.239838E+11 | 0.00 | 0.164927E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.156855E+11 | 0.00 | 0.169115E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.146396E+11 | 0.00 | 0.169077E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.184074E+11 | 0.00 | 0.164529E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.343242E+11 | 0.00 | 0.171832E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.102609E+12 | 0.00 | 0.168069E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.149527E+12 | 0.00 | 0.175937E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.942697E+12 | 0.203831E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.146396E+11 | 0.00 | 0.160091E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.164411E+12 | 0.00 | 0.176791E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 75078.55 | 02-JAN-20:10 | 11632.50 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 62594.23 | 18-JAN-07:19 | 24643.05 | 06-JAN-21:00 | 2397.21 | 08-JAN-07:49 | 0.00 | 01-JAN-00:10 |
February | 75078.55 | 01-FEB-20:10 | 11632.50 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 62593.86 | 10-FEB-07:19 | 25750.19 | 02-FEB-21:10 | 2377.62 | 09-FEB-06:30 | 0.00 | 01-FEB-00:10 |
March | 75078.55 | 01-MAR-20:10 | 11632.50 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 62594.23 | 13-MAR-06:19 | 24444.80 | 22-MAR-20:49 | 2406.25 | 30-MAR-06:19 | 0.00 | 01-MAR-00:10 |
April | 75078.55 | 03-APR-19:10 | 11632.50 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 62593.86 | 05-APR-06:19 | 24751.47 | 28-APR-18:10 | 2373.53 | 01-APR-06:19 | 0.00 | 01-APR-00:10 |
May | 75078.55 | 01-MAY-19:10 | 11632.50 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 62593.56 | 09-MAY-06:19 | 24538.78 | 10-MAY-20:19 | 2375.30 | 14-MAY-04:49 | 0.00 | 01-MAY-00:10 |
June | 75078.55 | 01-JUN-19:10 | 11632.50 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 62593.56 | 09-JUN-06:19 | 25602.32 | 14-JUN-20:10 | 2049.81 | 13-JUN-03:00 | 0.00 | 01-JUN-00:10 |
July | 75078.55 | 03-JUL-19:10 | 11632.50 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 62593.56 | 12-JUL-06:19 | 25381.48 | 07-JUL-20:00 | 2376.37 | 31-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 75078.55 | 01-AUG-19:10 | 11632.50 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 62593.86 | 21-AUG-06:19 | 24549.04 | 21-AUG-19:49 | 2475.73 | 18-AUG-15:09 | 0.00 | 01-AUG-00:10 |
September | 75078.55 | 01-SEP-19:10 | 11632.50 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 62594.23 | 18-SEP-06:19 | 23574.28 | 14-SEP-19:00 | 3003.72 | 29-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 75078.55 | 02-OCT-19:10 | 11632.50 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 62594.23 | 05-OCT-06:19 | 26416.77 | 18-OCT-20:00 | 2610.24 | 17-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 75078.55 | 01-NOV-19:10 | 11632.50 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 62594.23 | 01-NOV-06:19 | 25615.16 | 29-NOV-21:00 | 2379.38 | 30-NOV-02:30 | 0.00 | 01-NOV-00:10 |
December | 75078.55 | 01-DEC-20:10 | 11632.50 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 62594.23 | 08-DEC-07:19 | 25684.30 | 20-DEC-21:30 | 2391.76 | 22-DEC-06:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 75078.55 | 11632.50 | 89171.45 | 62593.56 | 23574.28 | 2049.81 | 0.00 | |||||||
Maximum of Months | 75078.55 | 11632.50 | 89171.45 | 62594.23 | 26416.77 | 3003.72 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 82595.67 | 14-JAN-10:00 | 0.00 | 0.00 | 0.00 | 4739.17 | 05-JAN-07:10 | 0.00 |
February | 74573.17 | 01-FEB-11:00 | 0.00 | 0.00 | 0.00 | 4738.59 | 09-FEB-07:10 | 0.00 |
March | 85676.14 | 23-MAR-15:09 | 0.00 | 0.00 | 0.00 | 4738.03 | 17-MAR-18:10 | 0.00 |
April | 83967.87 | 11-APR-15:09 | 0.00 | 0.00 | 0.00 | 4738.31 | 12-APR-18:00 | 0.00 |
May | 74985.34 | 04-MAY-15:09 | 0.00 | 0.00 | 0.00 | 4738.54 | 16-MAY-18:19 | 0.00 |
June | 97163.30 | 28-JUN-15:09 | 0.00 | 0.00 | 0.00 | 4738.37 | 13-JUN-18:00 | 0.00 |
July | 135361.10 | 19-JUL-15:09 | 0.00 | 0.00 | 0.00 | 4738.75 | 03-JUL-18:10 | 0.00 |
August | 143785.16 | 18-AUG-15:09 | 0.00 | 0.00 | 0.00 | 4738.28 | 22-AUG-06:19 | 0.00 |
September | 154498.99 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 4738.44 | 08-SEP-18:10 | 0.00 |
October | 161033.06 | 16-OCT-10:00 | 0.00 | 0.00 | 0.00 | 4738.21 | 24-OCT-06:19 | 0.00 |
November | 90108.81 | 19-NOV-10:00 | 0.00 | 0.00 | 0.00 | 4738.20 | 07-NOV-19:19 | 0.00 |
December | 85298.31 | 05-DEC-09:00 | 0.00 | 0.00 | 0.00 | 4738.28 | 15-DEC-19:10 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 74573.17 | 0.00 | 0.00 | 0.00 | 4738.03 | 0.00 | ||
Maximum of Months | 161033.06 | 0.00 | 0.00 | 0.00 | 4739.17 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 297528.35 | 17-JAN-20:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 17919.59 | 1434.64 | 0.00 | 48825.16 | 0.00 |
February | 286198.40 | 13-FEB-20:40 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 21868.95 | 1455.45 | 0.00 | 33427.68 | 0.00 |
March | 280931.95 | 23-MAR-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 23200.69 | 1355.74 | 0.00 | 26741.01 | 0.00 |
April | 299743.50 | 26-APR-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 20558.85 | 1418.65 | 0.00 | 48167.42 | 0.00 |
May | 299128.65 | 04-MAY-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 20303.27 | 1413.40 | 0.00 | 47954.94 | 0.00 |
June | 312939.48 | 29-JUN-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 20109.73 | 1547.07 | 0.00 | 61630.64 | 0.00 |
July | 341172.75 | 31-JUL-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 19303.85 | 1925.32 | 0.00 | 90318.58 | 0.00 |
August | 335153.44 | 14-AUG-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 19240.35 | 1842.25 | 0.00 | 84462.40 | 0.00 |
September | 363531.40 | 29-SEP-19:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 22422.59 | 1784.81 | 0.00 | 110342.46 | 0.00 |
October | 343779.56 | 04-OCT-19:49 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 18898.49 | 1964.54 | 0.00 | 93160.23 | 0.00 |
November | 286252.87 | 10-NOV-20:49 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 20181.40 | 1347.84 | 0.00 | 35482.62 | 0.00 |
December | 294754.60 | 05-DEC-20:10 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 19340.41 | 1361.25 | 0.00 | 45257.64 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 280931.95 | 75078.55 | 86439.81 | 11632.50 | 50290.22 | 17919.59 | 1347.84 | 0.00 | 26741.01 | 0.00 | |
Maximum of Months | 363531.40 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 23200.69 | 1964.54 | 0.00 | 110342.46 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 198067.45 | 08-JAN-06:00 | 0.00 | 175042.02 | 27-JAN-21:00 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 156296.20 | 05-FEB-05:00 | 0.00 | 175046.46 | 03-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 181466.67 | 30-MAR-02:00 | 0.00 | 174972.09 | 01-MAR-21:40 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 143220.36 | 01-APR-04:00 | 0.00 | 174711.60 | 03-APR-20:30 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 138268.12 | 19-MAY-05:19 | 0.00 | 174424.54 | 02-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 94598.59 | 13-JUN-03:00 | 0.00 | 174102.70 | 05-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 39600.67 | 06-JUL-02:00 | 0.00 | 173835.93 | 07-JUL-20:49 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 18790.33 | 19-AUG-01:49 | 0.00 | 173821.08 | 31-AUG-20:00 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 93073.17 | 20-SEP-02:00 | 0.00 | 174025.26 | 29-SEP-20:30 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 143243.31 | 12-OCT-06:10 | 0.00 | 174355.56 | 31-OCT-20:49 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 149597.85 | 30-NOV-07:19 | 0.00 | 174667.46 | 30-NOV-21:19 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 161046.17 | 24-DEC-03:00 | 0.00 | 174917.50 | 29-DEC-21:49 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 18790.33 | 0.00 | 173821.08 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 198067.45 | 0.00 | 175046.46 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.36 | 0.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.36 | 0.33 | 20.36 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.36 | 0.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.62 | 2.50 | 24.62 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.63 | 2.33 | 24.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.64 | 1.17 | 24.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.59 | 0.33 | 24.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.62 | 1.50 | 24.62 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 24.62 | 7.83 | 24.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.64 | 2.50 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.91 | 0.33 | 21.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.96 | 1.17 | 21.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.50 | 21.95 | 1.50 | 21.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.96 | 1.17 | 21.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.68 | 0.17 | 21.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.79 | 0.67 | 21.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.72 | 0.67 | 21.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.80 | 5.17 | 21.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 21.80 | 3.83 | 21.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.79 | 1.17 | 21.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.80 | 1.67 | 21.80 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 21.79 | 12.67 | 21.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 21.80 | 5.17 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.73 | 0.33 | 21.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.76 | 0.17 | 21.76 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 21.73 | 1.00 | 21.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.76 | 0.50 | 21.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.90 | 0.17 | 21.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.87 | 1.00 | 21.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 21.96 | 2.67 | 21.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.17 | 5.17 | 22.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.22 | 5.17 | 22.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.04 | 1.67 | 22.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 22.03 | 0.17 | 22.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.83 | 22.09 | 17.83 | 22.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.22 | 5.17 | 22.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.50 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.50 | 20.40 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.50 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.72 | 0.33 | 21.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.98 | 0.83 | 21.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.01 | 2.83 | 22.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.00 | 21.98 | 4.00 | 21.98 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 22.01 | 2.83 | 22.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.86 | 0.50 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.76 | 1.17 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.78 | 3.67 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 21.76 | 2.83 | 21.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.87 | 0.67 | 21.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.95 | 1.00 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.00 | 21.80 | 11.00 | 21.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 21.95 | 3.67 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.72 | 1.00 | 21.72 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.94 | 0.67 | 21.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.95 | 5.33 | 21.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.72 | 1.33 | 21.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 21.78 | 0.83 | 21.78 |
Annual Sum or Average | 0.00 | 0.00 | 9.17 | 21.88 | 9.17 | 21.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.95 | 5.33 | 21.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 24.67 | 18.17 | 24.67 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 24.63 | 11.17 | 24.63 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 24.70 | 15.83 | 24.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.60 | 0.83 | 24.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.65 | 3.00 | 24.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 24.67 | 15.33 | 24.67 |
Annual Sum or Average | 0.00 | 0.00 | 64.33 | 24.67 | 64.33 | 24.67 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 | 24.70 | 18.17 | 24.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 20.43 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 20.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 672.00 | 22.19 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 744.00 | 21.96 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.76 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.68 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.43 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.56 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 720.00 | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 744.00 | 22.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 719.00 | 22.88 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 744.00 | 22.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8759.00 | 22.04 | 0.00 | 0.00 | ||
Minimum of Months | 672.00 | 21.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 629.67 | 21.45 | 71.17 | 23.49 | 9.50 | 20.89 |
February | 607.83 | 21.39 | 29.33 | 23.46 | 3.67 | 21.00 |
March | 718.83 | 21.25 | 7.33 | 21.37 | 6.00 | 20.83 |
April | 720.00 | 21.24 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.21 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 21.38 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 683.83 | 21.49 | 13.67 | 23.83 | 0.00 | 0.00 |
October | 612.00 | 21.60 | 79.67 | 23.88 | 0.00 | 0.00 |
November | 603.50 | 21.54 | 57.50 | 23.72 | 2.33 | 21.00 |
December | 608.67 | 21.53 | 60.83 | 23.83 | 2.50 | 21.00 |
Annual Sum or Average | 8136.33 | 21.34 | 319.50 | 23.65 | 24.00 | 20.91 |
Minimum of Months | 603.50 | 21.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.60 | 79.67 | 23.88 | 9.50 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 738.00 | 22.15 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 659.33 | 22.25 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 735.33 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 700.50 | 22.18 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 741.67 | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 710.50 | 22.07 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 728.50 | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 709.33 | 22.14 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 681.50 | 22.19 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 708.33 | 22.33 | 12.50 | 23.82 | 0.00 | 0.00 |
November | 693.83 | 22.43 | 0.17 | 23.73 | 0.00 | 0.00 |
December | 734.83 | 22.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8541.67 | 22.19 | 12.67 | 23.82 | 0.00 | |
Minimum of Months | 659.33 | 22.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 741.67 | 22.43 | 12.50 | 23.82 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 332.17 | 22.43 | 375.33 | 23.19 | 162.67 | 24.00 |
February | 278.17 | 22.68 | 373.00 | 23.16 | 153.83 | 24.01 |
March | 292.33 | 22.81 | 431.33 | 23.06 | 180.67 | 23.99 |
April | 257.00 | 23.11 | 436.83 | 22.93 | 184.67 | 23.93 |
May | 254.50 | 23.10 | 426.00 | 23.00 | 181.00 | 23.94 |
June | 217.67 | 23.31 | 436.50 | 22.70 | 173.67 | 23.90 |
July | 198.00 | 23.50 | 493.50 | 22.44 | 171.17 | 23.89 |
August | 202.33 | 23.50 | 513.17 | 22.39 | 175.67 | 23.88 |
September | 211.50 | 23.32 | 450.17 | 22.60 | 169.00 | 23.90 |
October | 261.33 | 22.82 | 399.17 | 22.87 | 161.67 | 23.93 |
November | 303.00 | 22.69 | 396.67 | 23.13 | 169.33 | 23.99 |
December | 363.00 | 22.32 | 380.83 | 23.19 | 157.33 | 24.02 |
Annual Sum or Average | 3171.00 | 22.89 | 5112.50 | 22.86 | 2040.67 | 23.95 |
Minimum of Months | 198.00 | 22.32 | 373.00 | 22.39 | 153.83 | 23.88 |
Maximum of Months | 363.00 | 23.50 | 513.17 | 23.19 | 184.67 | 24.02 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 509.33 | 22.45 | 136.83 | 23.72 | 16.00 | 23.39 |
February | 486.50 | 22.35 | 88.00 | 23.54 | 11.50 | 22.74 |
March | 637.67 | 22.13 | 29.83 | 23.34 | 3.00 | 23.50 |
April | 664.50 | 22.22 | 33.00 | 23.35 | 27.33 | 23.30 |
May | 732.17 | 22.04 | 34.50 | 23.19 | 32.67 | 23.17 |
June | 701.50 | 22.05 | 109.17 | 23.08 | 109.17 | 23.08 |
July | 723.50 | 22.13 | 178.17 | 23.09 | 175.50 | 23.08 |
August | 698.33 | 22.28 | 214.50 | 23.19 | 202.67 | 23.18 |
September | 552.17 | 22.40 | 196.00 | 23.34 | 132.00 | 23.28 |
October | 397.00 | 22.43 | 233.00 | 23.61 | 40.33 | 23.38 |
November | 434.50 | 22.67 | 168.83 | 23.67 | 12.00 | 23.24 |
December | 480.83 | 22.63 | 144.33 | 23.84 | 0.00 | 0.00 |
Annual Sum or Average | 7018.00 | 22.28 | 1566.17 | 23.44 | 762.17 | 23.17 |
Minimum of Months | 397.00 | 22.04 | 29.83 | 23.08 | 0.00 | 0.00 |
Maximum of Months | 732.17 | 22.67 | 233.00 | 23.84 | 202.67 | 23.50 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 651.00 | 22.49 | 23.00 | 23.68 | 6.17 | 23.31 |
February | 574.50 | 22.54 | 22.00 | 23.76 | 2.50 | 22.76 |
March | 663.17 | 22.34 | 17.00 | 23.85 | 0.00 | 0.00 |
April | 601.00 | 22.32 | 37.33 | 23.70 | 3.17 | 23.26 |
May | 656.50 | 22.26 | 16.33 | 23.61 | 0.67 | 23.12 |
June | 610.50 | 22.17 | 42.00 | 23.51 | 8.17 | 23.16 |
July | 614.17 | 22.15 | 36.83 | 23.57 | 0.67 | 23.08 |
August | 588.83 | 22.18 | 62.17 | 23.52 | 8.00 | 23.08 |
September | 543.50 | 22.27 | 61.00 | 23.63 | 3.00 | 23.21 |
October | 584.17 | 22.53 | 56.67 | 23.77 | 3.67 | 23.70 |
November | 566.83 | 22.69 | 49.00 | 23.85 | 0.00 | 0.00 |
December | 656.67 | 22.69 | 18.50 | 23.91 | 0.00 | 0.00 |
Annual Sum or Average | 7310.83 | 22.39 | 441.83 | 23.67 | 36.00 | 23.21 |
Minimum of Months | 543.50 | 22.15 | 16.33 | 23.51 | 0.00 | 0.00 |
Maximum of Months | 663.17 | 22.69 | 62.17 | 23.91 | 8.17 | 23.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 740.67 | 21.55 | 19.33 | 21.11 | 19.33 | 21.11 |
February | 664.67 | 21.45 | 12.50 | 21.11 | 12.50 | 21.11 |
March | 735.17 | 21.41 | 13.33 | 20.56 | 13.33 | 20.56 |
April | 701.50 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 738.17 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 696.00 | 21.56 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 688.33 | 21.56 | 0.17 | 21.38 | 0.17 | 21.38 |
August | 679.67 | 21.54 | 1.17 | 21.61 | 1.17 | 21.61 |
September | 674.67 | 21.55 | 0.67 | 22.82 | 0.67 | 22.82 |
October | 712.17 | 21.57 | 0.83 | 22.15 | 0.83 | 22.15 |
November | 708.83 | 21.56 | 16.17 | 21.11 | 16.17 | 21.11 |
December | 742.33 | 21.57 | 26.83 | 21.11 | 26.83 | 21.11 |
Annual Sum or Average | 8482.17 | 21.53 | 91.00 | 21.06 | 91.00 | 21.06 |
Minimum of Months | 664.67 | 21.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.33 | 21.57 | 26.83 | 22.82 | 26.83 | 22.82 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 59.50 | 21.03 | 59.50 | 21.03 |
February | 672.00 | 21.31 | 26.67 | 21.11 | 26.67 | 21.11 |
March | 735.17 | 21.34 | 18.50 | 21.19 | 15.17 | 20.54 |
April | 665.00 | 21.60 | 22.83 | 24.60 | 0.00 | 0.00 |
May | 686.17 | 21.64 | 28.83 | 24.41 | 0.00 | 0.00 |
June | 596.00 | 21.79 | 78.50 | 24.83 | 1.83 | 23.69 |
July | 568.67 | 22.00 | 152.00 | 24.76 | 45.50 | 23.95 |
August | 584.00 | 21.99 | 148.50 | 24.48 | 56.50 | 23.64 |
September | 633.33 | 21.81 | 43.33 | 23.87 | 11.33 | 22.58 |
October | 722.17 | 21.86 | 26.67 | 22.95 | 25.33 | 22.89 |
November | 720.00 | 21.44 | 32.17 | 21.11 | 32.17 | 21.11 |
December | 744.00 | 21.35 | 67.00 | 21.08 | 67.00 | 21.08 |
Annual Sum or Average | 8070.50 | 21.60 | 704.50 | 23.50 | 341.00 | 22.06 |
Minimum of Months | 568.67 | 21.31 | 18.50 | 21.03 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.00 | 152.00 | 24.83 | 67.00 | 23.95 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.36 | 5.17 | 21.06 | 5.17 | 21.06 |
February | 672.00 | 21.34 | 6.67 | 21.12 | 6.67 | 21.12 |
March | 744.00 | 21.37 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.59 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 717.67 | 21.88 | 0.33 | 24.18 | 0.00 | 0.00 |
July | 725.67 | 22.13 | 31.17 | 23.55 | 27.00 | 23.46 |
August | 727.67 | 22.08 | 27.00 | 23.25 | 26.33 | 23.23 |
September | 720.00 | 21.81 | 4.33 | 22.87 | 4.33 | 22.87 |
October | 744.00 | 21.81 | 15.83 | 23.29 | 15.83 | 23.29 |
November | 720.00 | 21.38 | 12.50 | 21.09 | 12.50 | 21.09 |
December | 744.00 | 21.35 | 11.17 | 21.11 | 11.17 | 21.11 |
Annual Sum or Average | 8723.00 | 21.64 | 114.17 | 22.66 | 109.00 | 22.59 |
Minimum of Months | 672.00 | 21.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.13 | 31.17 | 24.18 | 27.00 | 23.46 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.60 | 20.50 | 21.11 | 20.50 | 21.11 |
February | 672.00 | 21.49 | 12.67 | 21.11 | 12.67 | 21.11 |
March | 744.00 | 21.48 | 11.17 | 20.78 | 11.17 | 20.78 |
April | 719.50 | 21.64 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 743.83 | 21.59 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 717.67 | 21.63 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 734.67 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 731.67 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 712.83 | 21.65 | 1.00 | 22.67 | 1.00 | 22.67 |
October | 743.83 | 21.66 | 1.17 | 22.23 | 1.17 | 22.23 |
November | 720.00 | 21.61 | 18.17 | 21.11 | 18.17 | 21.11 |
December | 744.00 | 21.60 | 31.17 | 21.11 | 31.17 | 21.11 |
Annual Sum or Average | 8728.00 | 21.61 | 95.83 | 21.10 | 95.83 | 21.10 |
Minimum of Months | 672.00 | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.70 | 31.17 | 22.67 | 31.17 | 22.67 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.33 | 48.83 | 21.10 | 48.83 | 21.10 |
February | 672.00 | 21.29 | 22.17 | 21.11 | 22.17 | 21.11 |
March | 743.33 | 21.38 | 16.33 | 20.70 | 16.33 | 20.70 |
April | 715.00 | 21.69 | 2.33 | 23.80 | 0.00 | 0.00 |
May | 737.50 | 21.72 | 2.33 | 23.67 | 0.00 | 0.00 |
June | 694.67 | 21.94 | 16.33 | 24.12 | 1.83 | 23.33 |
July | 688.50 | 22.20 | 78.00 | 23.95 | 48.00 | 23.67 |
August | 700.00 | 22.21 | 76.00 | 23.86 | 57.67 | 23.69 |
September | 709.50 | 21.86 | 19.00 | 23.31 | 12.17 | 22.67 |
October | 739.83 | 21.84 | 26.83 | 22.83 | 25.50 | 22.75 |
November | 719.50 | 21.37 | 37.17 | 21.10 | 37.17 | 21.10 |
December | 744.00 | 21.33 | 59.67 | 21.10 | 59.67 | 21.10 |
Annual Sum or Average | 8607.83 | 21.68 | 405.00 | 22.52 | 329.33 | 22.11 |
Minimum of Months | 672.00 | 21.29 | 2.33 | 20.70 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.21 | 78.00 | 24.12 | 59.67 | 23.69 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 731.17 | 21.51 | 49.00 | 21.10 | 49.00 | 21.10 |
February | 656.00 | 21.41 | 27.83 | 21.02 | 27.83 | 21.02 |
March | 723.50 | 21.38 | 30.17 | 20.72 | 30.17 | 20.72 |
April | 678.33 | 21.52 | 2.67 | 21.11 | 2.67 | 21.11 |
May | 717.50 | 21.53 | 0.33 | 21.68 | 0.33 | 21.68 |
June | 664.83 | 21.53 | 0.33 | 21.78 | 0.33 | 21.78 |
July | 649.17 | 21.49 | 1.00 | 21.68 | 1.00 | 21.68 |
August | 640.83 | 21.46 | 5.17 | 21.94 | 5.17 | 21.94 |
September | 645.33 | 21.49 | 5.67 | 22.25 | 4.00 | 21.90 |
October | 690.83 | 21.53 | 1.67 | 22.11 | 1.00 | 21.61 |
November | 690.50 | 21.51 | 31.17 | 21.13 | 31.17 | 21.13 |
December | 735.50 | 21.54 | 58.00 | 21.11 | 58.00 | 21.11 |
Annual Sum or Average | 8223.50 | 21.49 | 213.00 | 21.11 | 210.67 | 21.09 |
Minimum of Months | 640.83 | 21.38 | 0.33 | 20.72 | 0.33 | 20.72 |
Maximum of Months | 735.50 | 21.54 | 58.00 | 22.25 | 58.00 | 21.94 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.31 | 108.67 | 20.97 | 108.67 | 20.97 |
February | 672.00 | 21.30 | 43.83 | 20.96 | 43.83 | 20.96 |
March | 728.17 | 21.33 | 46.50 | 21.35 | 38.67 | 20.75 |
April | 627.50 | 21.56 | 49.83 | 24.52 | 4.00 | 21.59 |
May | 645.33 | 21.61 | 51.50 | 24.68 | 0.17 | 21.18 |
June | 559.83 | 21.84 | 117.00 | 25.25 | 15.83 | 25.70 |
July | 540.50 | 22.22 | 198.17 | 25.32 | 78.33 | 25.21 |
August | 543.00 | 22.09 | 194.33 | 24.94 | 81.67 | 24.38 |
September | 579.67 | 21.77 | 90.67 | 24.03 | 24.17 | 22.67 |
October | 684.67 | 21.85 | 44.17 | 23.50 | 29.50 | 23.08 |
November | 719.33 | 21.44 | 51.83 | 21.10 | 51.83 | 21.10 |
December | 744.00 | 21.33 | 116.00 | 21.02 | 116.00 | 21.02 |
Annual Sum or Average | 7788.00 | 21.61 | 1112.50 | 23.59 | 592.67 | 22.31 |
Minimum of Months | 540.50 | 21.30 | 43.83 | 20.96 | 0.17 | 20.75 |
Maximum of Months | 744.00 | 22.22 | 198.17 | 25.32 | 116.00 | 25.70 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 672.00 | 21.51 | 2.00 | 21.11 | 2.00 | 21.11 |
February | 636.33 | 21.50 | 2.83 | 21.11 | 2.83 | 21.11 |
March | 715.17 | 21.47 | 7.83 | 20.66 | 7.83 | 20.66 |
April | 716.67 | 21.62 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.55 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.59 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 743.33 | 21.67 | 0.50 | 22.08 | 0.50 | 22.08 |
August | 723.83 | 21.64 | 1.00 | 22.00 | 1.00 | 22.00 |
September | 661.50 | 21.52 | 0.17 | 21.37 | 0.17 | 21.37 |
October | 658.17 | 21.48 | 1.33 | 22.87 | 0.50 | 22.09 |
November | 658.33 | 21.55 | 3.33 | 21.11 | 3.33 | 21.11 |
December | 675.83 | 21.53 | 4.00 | 21.11 | 4.00 | 21.11 |
Annual Sum or Average | 8325.17 | 21.55 | 23.00 | 21.12 | 22.17 | 21.04 |
Minimum of Months | 636.33 | 21.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 21.67 | 7.83 | 22.87 | 7.83 | 22.09 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.83 | 22.76 | 190.50 | 23.97 | 19.83 | 23.99 |
February | 281.50 | 22.84 | 231.83 | 23.95 | 13.50 | 23.98 |
March | 274.00 | 22.68 | 296.33 | 23.94 | 3.17 | 23.99 |
April | 204.50 | 22.73 | 425.33 | 23.91 | 26.33 | 23.98 |
May | 217.00 | 22.71 | 445.33 | 23.90 | 30.00 | 23.99 |
June | 244.67 | 23.11 | 497.67 | 23.85 | 108.17 | 23.98 |
July | 274.67 | 23.37 | 544.67 | 23.80 | 165.33 | 23.98 |
August | 316.33 | 23.36 | 527.33 | 23.81 | 189.33 | 23.97 |
September | 293.00 | 23.13 | 475.67 | 23.84 | 138.17 | 23.97 |
October | 284.17 | 22.79 | 334.83 | 23.88 | 52.50 | 23.98 |
November | 320.17 | 22.81 | 241.83 | 23.93 | 20.50 | 23.83 |
December | 411.33 | 22.84 | 133.17 | 23.97 | 0.00 | 0.00 |
Annual Sum or Average | 3525.17 | 22.93 | 4344.50 | 23.88 | 766.83 | 23.97 |
Minimum of Months | 204.50 | 22.68 | 133.17 | 23.80 | 0.00 | 0.00 |
Maximum of Months | 411.33 | 23.37 | 544.67 | 23.97 | 189.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.67 | 22.80 | 310.33 | 23.93 | 13.67 | 23.99 |
February | 139.00 | 22.89 | 360.50 | 23.93 | 10.50 | 23.99 |
March | 108.00 | 22.80 | 439.83 | 23.92 | 1.67 | 23.99 |
April | 48.33 | 23.11 | 530.00 | 23.88 | 14.67 | 23.99 |
May | 44.17 | 23.38 | 554.83 | 23.89 | 22.33 | 23.99 |
June | 93.00 | 23.89 | 583.50 | 23.83 | 86.00 | 23.99 |
July | 142.33 | 23.99 | 633.83 | 23.79 | 142.33 | 23.99 |
August | 161.83 | 23.99 | 611.17 | 23.79 | 161.83 | 23.99 |
September | 118.50 | 23.86 | 567.50 | 23.82 | 108.83 | 23.99 |
October | 127.50 | 22.96 | 445.50 | 23.87 | 34.83 | 23.99 |
November | 175.50 | 22.83 | 359.83 | 23.92 | 14.00 | 23.88 |
December | 248.00 | 22.78 | 246.17 | 23.94 | 0.00 | 0.00 |
Annual Sum or Average | 1671.83 | 23.20 | 5643.00 | 23.86 | 610.67 | 23.99 |
Minimum of Months | 44.17 | 22.78 | 246.17 | 23.79 | 0.00 | 0.00 |
Maximum of Months | 265.67 | 23.99 | 633.83 | 23.94 | 161.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 574.67 | 23.80 | 647.67 | 23.86 | 520.17 | 24.05 |
February | 490.67 | 23.98 | 622.00 | 23.83 | 475.33 | 24.05 |
March | 564.83 | 23.88 | 685.67 | 23.84 | 529.50 | 24.06 |
April | 524.50 | 24.01 | 711.67 | 23.75 | 523.50 | 24.01 |
May | 545.17 | 24.00 | 735.67 | 23.73 | 544.83 | 24.00 |
June | 535.33 | 23.99 | 720.00 | 23.65 | 535.33 | 23.99 |
July | 553.33 | 23.99 | 744.00 | 23.59 | 553.33 | 23.99 |
August | 553.17 | 23.99 | 743.67 | 23.58 | 553.17 | 23.99 |
September | 531.33 | 23.99 | 714.50 | 23.62 | 531.17 | 23.99 |
October | 542.33 | 23.96 | 704.33 | 23.70 | 536.50 | 23.99 |
November | 524.17 | 23.96 | 663.50 | 23.82 | 508.67 | 24.03 |
December | 569.50 | 23.81 | 632.83 | 23.91 | 514.83 | 24.05 |
Annual Sum or Average | 6509.00 | 23.94 | 8325.50 | 23.73 | 6326.33 | 24.01 |
Minimum of Months | 490.67 | 23.80 | 622.00 | 23.58 | 475.33 | 23.99 |
Maximum of Months | 574.67 | 24.01 | 744.00 | 23.91 | 553.33 | 24.06 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.56472 | 39.86831 | -0.0090 | 5.28929 |
February | 672.00000 | 22.19036 | 43.44314 | -0.0899 | 5.39071 |
March | 744.00000 | 21.96251 | 47.70858 | -0.1214 | 5.48950 |
April | 720.00000 | 21.76155 | 52.99407 | -0.1389 | 5.58362 |
May | 744.00000 | 21.67931 | 53.02985 | -1.2970 | 40.26109 |
June | 720.00000 | 21.43334 | 59.24168 | -1.3434 | 42.63051 |
July | 744.00000 | 21.51236 | 60.00193 | -1.3002 | 40.40873 |
August | 744.00000 | 21.56236 | 59.82793 | -1.2822 | 39.50387 |
September | 720.00000 | 22.01146 | 57.12674 | -1.1388 | 32.53504 |
October | 744.00000 | 22.30297 | 46.76155 | -0.0262 | 5.26478 |
November | 720.00000 | 22.87652 | 40.82427 | 0.07465 | 5.39398 |
December | 744.00000 | 22.64492 | 34.55937 | -0.0234 | 5.37287 |
Annual Sum or Average | 8760.00000 | 22.04088 | 49.63423 | -0.5610 | 19.51926 |
Minimum of Months | 672.00000 | 21.43334 | 34.55937 | -1.3434 | 5.26478 |
Maximum of Months | 744.00000 | 22.87652 | 60.00193 | 0.07465 | 42.63051 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.80507 | 40.61670 | -0.1107 | 7.07117 |
February | 672.00000 | 21.59761 | 44.00406 | -0.1584 | 6.79960 |
March | 744.00000 | 21.31635 | 48.45233 | -0.2178 | 6.81776 |
April | 720.00000 | 21.24318 | 53.61461 | -0.1836 | 6.05247 |
May | 744.00000 | 21.07485 | 53.86554 | -1.4025 | 45.73286 |
June | 720.00000 | 21.10104 | 59.78165 | -1.3340 | 42.10364 |
July | 744.00000 | 21.20625 | 61.34035 | -1.2638 | 38.55173 |
August | 744.00000 | 21.38356 | 61.02548 | -1.1929 | 35.18760 |
September | 720.00000 | 21.58361 | 58.33525 | -1.1406 | 33.44032 |
October | 744.00000 | 21.96434 | 47.29074 | -0.0016 | 6.53419 |
November | 720.00000 | 21.88750 | 42.13983 | -0.0696 | 6.69751 |
December | 744.00000 | 21.94744 | 35.06947 | -0.1005 | 7.12855 |
Annual Sum or Average | 8760.00000 | 21.50911 | 50.48146 | -0.6007 | 20.26561 |
Minimum of Months | 672.00000 | 21.07485 | 35.06947 | -1.4025 | 6.05247 |
Maximum of Months | 744.00000 | 21.96434 | 61.34035 | -0.0016 | 45.73286 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.16521 | 41.44341 | -0.0574 | 5.61698 |
February | 672.00000 | 22.27601 | 44.10007 | -0.0198 | 5.42400 |
March | 744.00000 | 22.07443 | 48.20283 | -0.0453 | 5.55173 |
April | 720.00000 | 22.20938 | 52.50826 | 0.02127 | 5.50737 |
May | 744.00000 | 22.10707 | 52.61832 | -1.0806 | 30.29061 |
June | 720.00000 | 22.08671 | 58.05996 | -1.0436 | 28.69005 |
July | 744.00000 | 22.13517 | 59.12029 | -1.0112 | 27.23871 |
August | 744.00000 | 22.19647 | 59.00698 | -0.9886 | 26.29321 |
September | 720.00000 | 22.25534 | 57.39149 | -0.9820 | 25.99240 |
October | 744.00000 | 22.39034 | 47.49971 | 0.04822 | 5.52427 |
November | 720.00000 | 22.47002 | 42.50376 | 0.02518 | 5.44384 |
December | 744.00000 | 22.34006 | 35.98260 | -0.0478 | 5.46842 |
Annual Sum or Average | 8760.00000 | 22.22477 | 49.88714 | -0.4345 | 14.81201 |
Minimum of Months | 672.00000 | 22.07443 | 35.98260 | -1.0806 | 5.42400 |
Maximum of Months | 744.00000 | 22.47002 | 59.12029 | 0.04822 | 30.29061 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.14742 | 37.21749 | 0.53221 | 14.91780 |
February | 672.00000 | 22.27239 | 39.75094 | 0.57492 | 15.65053 |
March | 744.00000 | 22.23860 | 43.60643 | 0.59080 | 16.06786 |
April | 720.00000 | 22.19193 | 48.38735 | 0.62300 | 16.78181 |
May | 744.00000 | 22.15997 | 48.26026 | -0.1875 | 13.12944 |
June | 720.00000 | 22.03261 | 53.99395 | -0.1799 | 13.08154 |
July | 744.00000 | 21.95301 | 55.30516 | -0.1872 | 12.85010 |
August | 744.00000 | 21.95744 | 55.28531 | -0.1814 | 12.97824 |
September | 720.00000 | 22.00270 | 53.84630 | -0.1911 | 13.02263 |
October | 744.00000 | 22.02385 | 44.02782 | 0.56829 | 15.44851 |
November | 720.00000 | 22.22655 | 38.70296 | 0.56748 | 15.54103 |
December | 744.00000 | 22.18838 | 31.90874 | 0.51059 | 14.26658 |
Annual Sum or Average | 8760.00000 | 22.11498 | 45.87641 | 0.25124 | 14.46696 |
Minimum of Months | 672.00000 | 21.95301 | 31.90874 | -0.1911 | 12.85010 |
Maximum of Months | 744.00000 | 22.27239 | 55.30516 | 0.62300 | 16.78181 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.79790 | 44.78007 | 0.19210 | 6.96524 |
February | 672.00000 | 22.66469 | 47.91975 | 0.15563 | 6.43670 |
March | 744.00000 | 22.27243 | 52.23008 | 0.07189 | 6.03479 |
April | 720.00000 | 22.30319 | 56.82755 | 0.11910 | 5.81999 |
May | 744.00000 | 22.06035 | 57.26465 | -1.0176 | 27.71914 |
June | 720.00000 | 22.08215 | 62.70615 | -0.9540 | 25.14687 |
July | 744.00000 | 22.15830 | 63.91395 | -0.8961 | 22.78265 |
August | 744.00000 | 22.33822 | 63.56020 | -0.8218 | 19.98900 |
September | 720.00000 | 22.57259 | 61.21294 | -0.7516 | 17.79906 |
October | 744.00000 | 22.92343 | 51.04735 | 0.28499 | 7.60004 |
November | 720.00000 | 23.01761 | 46.01234 | 0.25737 | 7.16755 |
December | 744.00000 | 22.99337 | 39.59655 | 0.21308 | 6.96115 |
Annual Sum or Average | 8760.00000 | 22.51436 | 53.94165 | -0.2649 | 13.41875 |
Minimum of Months | 672.00000 | 22.06035 | 39.59655 | -1.0176 | 5.81999 |
Maximum of Months | 744.00000 | 23.01761 | 63.91395 | 0.28499 | 27.71914 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.63451 | 43.53594 | 0.09666 | 5.81434 |
February | 672.00000 | 22.70841 | 46.19559 | 0.12301 | 5.82455 |
March | 744.00000 | 22.47583 | 50.26263 | 0.08779 | 5.81453 |
April | 720.00000 | 22.52417 | 54.70692 | 0.13399 | 6.02370 |
May | 744.00000 | 22.40612 | 54.83900 | -0.9365 | 24.64901 |
June | 720.00000 | 22.35918 | 60.25683 | -0.9051 | 23.47658 |
July | 744.00000 | 22.35808 | 61.46450 | -0.8867 | 22.66107 |
August | 744.00000 | 22.42665 | 61.36278 | -0.8604 | 21.63921 |
September | 720.00000 | 22.54970 | 59.53801 | -0.8317 | 20.49406 |
October | 744.00000 | 22.74331 | 49.71612 | 0.17756 | 6.18707 |
November | 720.00000 | 22.90155 | 44.65365 | 0.17139 | 6.11142 |
December | 744.00000 | 22.80517 | 38.26200 | 0.10644 | 5.68808 |
Annual Sum or Average | 8760.00000 | 22.57319 | 52.08458 | -0.2963 | 12.91044 |
Minimum of Months | 672.00000 | 22.35808 | 38.26200 | -0.9365 | 5.68808 |
Maximum of Months | 744.00000 | 22.90155 | 61.46450 | 0.17756 | 24.64901 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.55693 | 46.60880 | -0.2455 | 7.13513 |
February | 672.00000 | 21.47042 | 49.62043 | -0.2502 | 7.01951 |
March | 744.00000 | 21.43281 | 53.18004 | -0.2427 | 6.97227 |
April | 720.00000 | 21.57818 | 55.39597 | -0.1531 | 6.21182 |
May | 744.00000 | 21.54434 | 55.44547 | -1.3084 | 41.47181 |
June | 720.00000 | 21.60263 | 58.92624 | -1.2340 | 37.87177 |
July | 744.00000 | 21.66910 | 59.83818 | -1.1738 | 35.16444 |
August | 744.00000 | 21.68041 | 60.38302 | -1.1656 | 34.85734 |
September | 720.00000 | 21.65471 | 58.88094 | -1.2040 | 36.65064 |
October | 744.00000 | 21.64341 | 50.91980 | -0.1404 | 6.30079 |
November | 720.00000 | 21.59133 | 47.43675 | -0.2141 | 6.86970 |
December | 744.00000 | 21.57526 | 41.33319 | -0.2648 | 7.37055 |
Annual Sum or Average | 8760.00000 | 21.58397 | 53.17132 | -0.6355 | 19.56742 |
Minimum of Months | 672.00000 | 21.43281 | 41.33319 | -1.3084 | 6.21182 |
Maximum of Months | 744.00000 | 21.68041 | 60.38302 | -0.1404 | 41.47181 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32683 | 47.91026 | -0.3374 | 7.91392 |
February | 672.00000 | 21.31423 | 50.71056 | -0.3114 | 7.48130 |
March | 744.00000 | 21.36571 | 54.07693 | -0.2748 | 7.23682 |
April | 720.00000 | 21.77902 | 55.67572 | -0.1221 | 6.50194 |
May | 744.00000 | 21.82519 | 54.95773 | -1.2297 | 38.41076 |
June | 720.00000 | 22.21670 | 57.65665 | -1.0560 | 31.57775 |
July | 744.00000 | 22.56371 | 58.62871 | -0.9124 | 26.72362 |
August | 744.00000 | 22.47859 | 60.12610 | -0.9389 | 27.30907 |
September | 720.00000 | 22.04672 | 59.91919 | -1.1077 | 32.73702 |
October | 744.00000 | 21.91492 | 52.00057 | -0.1073 | 6.31932 |
November | 720.00000 | 21.43862 | 48.96334 | -0.2828 | 7.29340 |
December | 744.00000 | 21.35213 | 42.30397 | -0.3608 | 8.19895 |
Annual Sum or Average | 8760.00000 | 21.80512 | 53.57939 | -0.5884 | 17.36511 |
Minimum of Months | 672.00000 | 21.31423 | 42.30397 | -1.2297 | 6.31932 |
Maximum of Months | 744.00000 | 22.56371 | 60.12610 | -0.1073 | 38.41076 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.35712 | 44.72894 | -0.3280 | 7.51198 |
February | 672.00000 | 21.34290 | 47.57714 | -0.3090 | 7.17794 |
March | 744.00000 | 21.36646 | 50.97277 | -0.2815 | 6.84813 |
April | 720.00000 | 21.52957 | 53.46042 | -0.2118 | 6.20965 |
May | 744.00000 | 21.59238 | 52.61058 | -1.3423 | 42.78782 |
June | 720.00000 | 21.89125 | 56.32180 | -1.2038 | 36.20589 |
July | 744.00000 | 22.16602 | 58.70361 | -1.0889 | 31.31036 |
August | 744.00000 | 22.11792 | 59.90114 | -1.1035 | 31.85626 |
September | 720.00000 | 21.81092 | 58.05021 | -1.2309 | 37.37369 |
October | 744.00000 | 21.81056 | 49.25770 | -0.1599 | 6.20583 |
November | 720.00000 | 21.37695 | 45.98657 | -0.3070 | 7.21852 |
December | 744.00000 | 21.35031 | 39.43957 | -0.3604 | 7.91197 |
Annual Sum or Average | 8760.00000 | 21.64506 | 51.42678 | -0.6626 | 19.11950 |
Minimum of Months | 672.00000 | 21.34290 | 39.43957 | -1.3423 | 6.20583 |
Maximum of Months | 744.00000 | 22.16602 | 59.90114 | -0.1599 | 42.78782 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.59922 | 46.30623 | -0.2344 | 6.98436 |
February | 672.00000 | 21.48640 | 49.63586 | -0.2506 | 6.99263 |
March | 744.00000 | 21.47574 | 52.84261 | -0.2353 | 6.90681 |
April | 720.00000 | 21.63656 | 54.91212 | -0.1484 | 6.19161 |
May | 744.00000 | 21.58659 | 55.15210 | -1.3099 | 41.52151 |
June | 720.00000 | 21.63436 | 58.93756 | -1.2426 | 38.27623 |
July | 744.00000 | 21.71337 | 59.51436 | -1.1749 | 35.22265 |
August | 744.00000 | 21.71922 | 59.78684 | -1.1637 | 34.76687 |
September | 720.00000 | 21.65982 | 59.49372 | -1.2188 | 37.29411 |
October | 744.00000 | 21.66177 | 51.10192 | -0.1393 | 6.24541 |
November | 720.00000 | 21.61248 | 47.47873 | -0.2139 | 6.78520 |
December | 744.00000 | 21.60216 | 41.30041 | -0.2592 | 7.24669 |
Annual Sum or Average | 8760.00000 | 21.61648 | 53.04276 | -0.6349 | 19.61077 |
Minimum of Months | 672.00000 | 21.47574 | 41.30041 | -1.3099 | 6.19161 |
Maximum of Months | 744.00000 | 21.71922 | 59.78684 | -0.1393 | 41.52151 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.32585 | 47.66023 | -0.3340 | 7.74078 |
February | 672.00000 | 21.28761 | 50.76025 | -0.3211 | 7.46067 |
March | 744.00000 | 21.37682 | 53.78020 | -0.2746 | 7.10676 |
April | 720.00000 | 21.70573 | 55.48185 | -0.1456 | 6.15538 |
May | 744.00000 | 21.73882 | 55.05873 | -1.2690 | 39.61406 |
June | 720.00000 | 22.01716 | 58.76103 | -1.1285 | 33.35468 |
July | 744.00000 | 22.34350 | 59.94448 | -0.9851 | 27.77605 |
August | 744.00000 | 22.31287 | 61.01742 | -0.9916 | 27.97202 |
September | 720.00000 | 21.89980 | 61.10767 | -1.1681 | 34.88408 |
October | 744.00000 | 21.85655 | 52.35245 | -0.1232 | 6.13855 |
November | 720.00000 | 21.37235 | 49.13746 | -0.3010 | 7.29011 |
December | 744.00000 | 21.33143 | 42.37824 | -0.3643 | 8.09615 |
Annual Sum or Average | 8760.00000 | 21.71717 | 53.95581 | -0.6189 | 17.85535 |
Minimum of Months | 672.00000 | 21.28761 | 42.37824 | -1.2690 | 6.13855 |
Maximum of Months | 744.00000 | 22.34350 | 61.10767 | -0.1232 | 39.61406 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.54226 | 47.25855 | -0.2580 | 7.44720 |
February | 672.00000 | 21.45131 | 50.49264 | -0.2617 | 7.29313 |
March | 744.00000 | 21.42734 | 54.03959 | -0.2490 | 7.24794 |
April | 720.00000 | 21.60996 | 55.86002 | -0.1392 | 6.34783 |
May | 744.00000 | 21.58484 | 55.85923 | -1.2867 | 40.67309 |
June | 720.00000 | 21.64525 | 58.74498 | -1.2023 | 36.65014 |
July | 744.00000 | 21.70100 | 59.15366 | -1.1378 | 33.78731 |
August | 744.00000 | 21.70078 | 59.74716 | -1.1345 | 33.68250 |
September | 720.00000 | 21.67127 | 59.05942 | -1.1813 | 35.83520 |
October | 744.00000 | 21.65400 | 51.11083 | -0.1302 | 6.41853 |
November | 720.00000 | 21.58505 | 48.11362 | -0.2197 | 7.07993 |
December | 744.00000 | 21.55803 | 41.91687 | -0.2779 | 7.67896 |
Annual Sum or Average | 8760.00000 | 21.59506 | 53.44876 | -0.6255 | 19.25096 |
Minimum of Months | 672.00000 | 21.42734 | 41.91687 | -1.2867 | 6.34783 |
Maximum of Months | 744.00000 | 21.70100 | 59.74716 | -0.1302 | 40.67309 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.31086 | 48.70485 | -0.3541 | 8.30042 |
February | 672.00000 | 21.29770 | 51.68775 | -0.3248 | 7.78351 |
March | 744.00000 | 21.38002 | 54.93440 | -0.2781 | 7.52615 |
April | 720.00000 | 21.88366 | 55.72956 | -0.0928 | 6.87885 |
May | 744.00000 | 21.92975 | 54.86820 | -1.1869 | 37.16930 |
June | 720.00000 | 22.42457 | 56.58767 | -0.9710 | 29.87332 |
July | 744.00000 | 22.84478 | 56.48581 | -0.7974 | 25.05870 |
August | 744.00000 | 22.72432 | 58.05212 | -0.8368 | 25.55338 |
September | 720.00000 | 22.18076 | 59.28941 | -1.0486 | 30.97763 |
October | 744.00000 | 22.00484 | 51.87319 | -0.0796 | 6.56462 |
November | 720.00000 | 21.44236 | 49.81788 | -0.2889 | 7.51262 |
December | 744.00000 | 21.33156 | 42.99611 | -0.3790 | 8.59217 |
Annual Sum or Average | 8760.00000 | 21.90024 | 53.41191 | -0.5545 | 16.86827 |
Minimum of Months | 672.00000 | 21.29770 | 42.99611 | -1.1869 | 6.56462 |
Maximum of Months | 744.00000 | 22.84478 | 59.28941 | -0.0796 | 37.16930 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.68496 | 45.29788 | -0.1665 | 6.82638 |
February | 672.00000 | 21.59408 | 48.63196 | -0.1971 | 6.80056 |
March | 744.00000 | 21.54120 | 52.01145 | -0.2124 | 6.90272 |
April | 720.00000 | 21.62954 | 54.99138 | -0.1566 | 6.34973 |
May | 744.00000 | 21.55021 | 55.95840 | -1.3456 | 43.33093 |
June | 720.00000 | 21.59427 | 59.97716 | -1.2794 | 40.03149 |
July | 744.00000 | 21.66739 | 61.18632 | -1.2171 | 37.18277 |
August | 744.00000 | 21.68716 | 60.47411 | -1.1931 | 36.17867 |
September | 720.00000 | 21.66679 | 57.44976 | -1.2094 | 37.08362 |
October | 744.00000 | 21.69007 | 49.56433 | -0.1125 | 6.37534 |
November | 720.00000 | 21.69847 | 45.81969 | -0.1536 | 6.69821 |
December | 744.00000 | 21.69756 | 40.54050 | -0.1819 | 7.01724 |
Annual Sum or Average | 8760.00000 | 21.64214 | 52.67084 | -0.6213 | 20.14669 |
Minimum of Months | 672.00000 | 21.54120 | 40.54050 | -1.3456 | 6.34973 |
Maximum of Months | 744.00000 | 21.69847 | 61.18632 | -0.1125 | 43.33093 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.25913 | 44.57863 | 0.26526 | 7.19963 |
February | 672.00000 | 23.42058 | 46.55616 | 0.31891 | 7.64677 |
March | 744.00000 | 23.40281 | 50.13746 | 0.34195 | 7.89558 |
April | 720.00000 | 23.47384 | 54.07811 | 0.40570 | 8.83530 |
May | 744.00000 | 23.46507 | 53.88053 | -0.5139 | 11.18816 |
June | 720.00000 | 23.46024 | 58.92022 | -0.4580 | 10.08527 |
July | 744.00000 | 23.48077 | 59.96787 | -0.4280 | 9.43735 |
August | 744.00000 | 23.45524 | 60.10537 | -0.4384 | 9.67199 |
September | 720.00000 | 23.41809 | 59.03835 | -0.4794 | 10.55851 |
October | 744.00000 | 23.38359 | 50.19815 | 0.36994 | 8.43774 |
November | 720.00000 | 23.38318 | 45.56610 | 0.30848 | 7.60841 |
December | 744.00000 | 23.30774 | 39.61070 | 0.24331 | 6.87585 |
Annual Sum or Average | 8760.00000 | 23.40883 | 51.90273 | -0.0075 | 8.79076 |
Minimum of Months | 672.00000 | 23.25913 | 39.61070 | -0.5139 | 6.87585 |
Maximum of Months | 744.00000 | 23.48077 | 60.10537 | 0.40570 | 11.18816 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.45113 | 43.45665 | 0.34815 | 8.12193 |
February | 672.00000 | 23.60098 | 45.37487 | 0.40021 | 8.74297 |
March | 744.00000 | 23.59098 | 48.92127 | 0.42523 | 9.10289 |
April | 720.00000 | 23.64171 | 52.86280 | 0.48362 | 10.15950 |
May | 744.00000 | 23.63612 | 52.65698 | -0.3998 | 8.75751 |
June | 720.00000 | 23.62549 | 57.68847 | -0.3477 | 7.97429 |
July | 744.00000 | 23.63799 | 58.77116 | -0.3226 | 7.56484 |
August | 744.00000 | 23.60843 | 58.91433 | -0.3350 | 7.76888 |
September | 720.00000 | 23.58063 | 57.80894 | -0.3714 | 8.37996 |
October | 744.00000 | 23.54218 | 49.07974 | 0.44272 | 9.54483 |
November | 720.00000 | 23.55778 | 44.42287 | 0.38750 | 8.63049 |
December | 744.00000 | 23.49208 | 38.52347 | 0.32440 | 7.71542 |
Annual Sum or Average | 8760.00000 | 23.58006 | 50.72334 | 0.08423 | 8.53423 |
Minimum of Months | 672.00000 | 23.45113 | 38.52347 | -0.3998 | 7.56484 |
Maximum of Months | 744.00000 | 23.64171 | 58.91433 | 0.48362 | 10.15950 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 23.58672 | 41.75530 | 1.03946 | 31.64879 |
February | 672.00000 | 23.70933 | 43.73343 | 1.07967 | 32.55351 |
March | 744.00000 | 23.66491 | 47.10174 | 1.09617 | 33.63861 |
April | 720.00000 | 23.73229 | 51.30932 | 1.16757 | 36.09139 |
May | 744.00000 | 23.71512 | 51.20310 | 0.56938 | 17.87073 |
June | 720.00000 | 23.64642 | 56.35873 | 0.60659 | 19.04961 |
July | 744.00000 | 23.59191 | 57.61376 | 0.62212 | 19.96970 |
August | 744.00000 | 23.58354 | 57.63623 | 0.61922 | 19.99427 |
September | 720.00000 | 23.60178 | 56.31131 | 0.58756 | 18.98390 |
October | 744.00000 | 23.61633 | 47.74586 | 1.12585 | 34.64848 |
November | 720.00000 | 23.70500 | 42.85558 | 1.08134 | 32.59898 |
December | 744.00000 | 23.61738 | 37.01127 | 1.01498 | 30.46150 |
Annual Sum or Average | 8760.00000 | 23.64679 | 49.23745 | 0.88281 | 27.25591 |
Minimum of Months | 672.00000 | 23.58354 | 37.01127 | 0.56938 | 17.87073 |
Maximum of Months | 744.00000 | 23.73229 | 57.63623 | 1.16757 | 36.09139 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.456090E+11 | 90242.60 | 14-JAN-16:01 | 647.92 | 0.141089E+12 | 0.00 | 0.186698E+12 | 2.68 | 3.99 | 15-JAN-16:01 | 0.00 | 0.00 |
February | 0.314789E+11 | 80131.70 | 01-FEB-09:11 | 614.01 | 0.957709E+11 | 0.00 | 0.127250E+12 | 2.80 | 4.05 | 01-FEB-16:01 | 0.00 | 0.00 |
March | 0.307050E+11 | 97042.67 | 23-MAR-15:03 | 642.83 | 0.956656E+11 | 0.00 | 0.126371E+12 | 2.67 | 4.13 | 22-MAR-15:03 | 0.00 | 0.00 |
April | 0.564163E+11 | 96120.25 | 11-APR-15:03 | 712.67 | 0.175056E+12 | 0.00 | 0.231472E+12 | 3.04 | 4.07 | 04-APR-15:03 | 0.00 | 0.00 |
May | 0.604041E+11 | 82422.01 | 04-MAY-15:03 | 742.79 | 0.181586E+12 | 0.00 | 0.241990E+12 | 3.02 | 4.24 | 05-MAY-15:03 | 0.00 | 0.00 |
June | 0.984101E+11 | 107089.92 | 28-JUN-15:03 | 720.00 | 0.321990E+12 | 0.00 | 0.420400E+12 | 3.16 | 4.28 | 27-JUN-21:12 | 0.00 | 0.00 |
July | 0.160419E+12 | 144742.90 | 19-JUL-15:05 | 744.00 | 0.586402E+12 | 0.00 | 0.746821E+12 | 3.54 | 4.47 | 19-JUL-21:13 | 0.00 | 0.00 |
August | 0.174080E+12 | 154750.47 | 17-AUG-15:03 | 744.00 | 0.652800E+12 | 0.00 | 0.826880E+12 | 3.67 | 4.41 | 15-AUG-21:14 | 0.00 | 0.00 |
September | 0.124563E+12 | 154498.99 | 29-SEP-13:00 | 720.00 | 0.428637E+12 | 0.00 | 0.553201E+12 | 3.31 | 4.42 | 30-SEP-21:13 | 0.00 | 0.00 |
October | 0.127450E+12 | 161340.59 | 14-OCT-15:01 | 744.00 | 0.441304E+12 | 0.00 | 0.568755E+12 | 3.30 | 4.41 | 01-OCT-21:12 | 0.00 | 0.00 |
November | 0.498902E+11 | 100616.01 | 19-NOV-09:11 | 688.97 | 0.154386E+12 | 0.00 | 0.204276E+12 | 2.94 | 4.09 | 18-NOV-16:01 | 0.00 | 0.00 |
December | 0.491998E+11 | 99401.22 | 05-DEC-09:11 | 662.81 | 0.155185E+12 | 0.00 | 0.204385E+12 | 2.76 | 4.02 | 25-DEC-16:01 | 0.00 | 0.00 |
Annual Sum or Average | 0.100863E+13 | 8384.00 | 0.342987E+13 | 0.443850E+13 | 3.07 | |||||||
Minimum of Months | 0.307050E+11 | 80131.70 | 614.01 | 0.956656E+11 | 0.00 | 0.126371E+12 | 2.67 | 3.99 | 0.00 | 0.00 | ||
Maximum of Months | 0.174080E+12 | 161340.59 | 744.00 | 0.652800E+12 | 0.00 | 0.826880E+12 | 3.67 | 4.47 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.108994E+12 | 0.00 | 735.50 | 156510.15 | 08-JAN-07:00 | 0.00 | 46.98 | 59.83 | 0.97 | 0.00 | 0.15 | 0.59 | 08-JAN-07:00 |
February | 0.831034E+11 | 0.00 | 672.00 | 123055.45 | 05-FEB-06:00 | 0.00 | 46.36 | 60.00 | 0.75 | 0.00 | 0.13 | 0.46 | 05-FEB-06:00 |
March | 0.114752E+12 | 0.00 | 744.00 | 143409.56 | 30-MAR-03:00 | 0.00 | 46.19 | 60.00 | 0.97 | 0.00 | 0.16 | 0.54 | 30-MAR-03:00 |
April | 0.474825E+11 | 0.00 | 719.30 | 112122.20 | 01-APR-05:00 | 0.00 | 43.26 | 59.98 | 0.32 | 0.00 | 0.07 | 0.42 | 01-APR-05:00 |
May | 0.443096E+11 | 0.00 | 743.16 | 101998.06 | 27-MAY-03:00 | 0.00 | 43.39 | 59.98 | 0.30 | 0.00 | 0.06 | 0.38 | 27-MAY-03:00 |
June | 0.145229E+11 | 0.00 | 700.95 | 66425.40 | 13-JUN-04:00 | 0.00 | 42.37 | 59.48 | 0.08 | 0.00 | 0.02 | 0.25 | 13-JUN-04:00 |
July | 0.948079E+10 | 0.00 | 702.38 | 31986.36 | 10-JUL-08:15 | 0.00 | 41.97 | 58.88 | 0.05 | 0.00 | 0.01 | 0.12 | 10-JUL-08:15 |
August | 0.891219E+10 | 0.00 | 711.98 | 32508.65 | 03-AUG-08:16 | 0.00 | 42.01 | 59.13 | 0.05 | 0.00 | 0.01 | 0.12 | 03-AUG-08:16 |
September | 0.112085E+11 | 0.00 | 706.40 | 64457.04 | 20-SEP-04:00 | 0.00 | 42.47 | 59.64 | 0.06 | 0.00 | 0.02 | 0.24 | 20-SEP-04:00 |
October | 0.217357E+11 | 0.00 | 697.06 | 96097.08 | 28-OCT-05:00 | 0.00 | 42.93 | 58.84 | 0.14 | 0.00 | 0.03 | 0.36 | 28-OCT-05:00 |
November | 0.693773E+11 | 0.00 | 710.58 | 112095.26 | 24-NOV-04:00 | 0.00 | 45.46 | 59.82 | 0.57 | 0.00 | 0.10 | 0.42 | 24-NOV-04:00 |
December | 0.105628E+12 | 0.00 | 739.86 | 126826.57 | 24-DEC-04:00 | 0.00 | 46.97 | 59.95 | 0.93 | 0.00 | 0.15 | 0.48 | 24-DEC-04:00 |
Annual Sum or Average | 0.639507E+12 | 8583.17 | 44.19 | 59.62 | 0.43 | 0.00 | 0.08 | ||||||
Minimum of Months | 0.891219E+10 | 0.00 | 672.00 | 31986.36 | 0.00 | 41.97 | 58.84 | 0.05 | 0.00 | 0.01 | 0.12 | ||
Maximum of Months | 0.114752E+12 | 0.00 | 744.00 | 156510.15 | 0.00 | 46.98 | 60.00 | 0.97 | 0.00 | 0.16 | 0.59 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.151968E+10 | 0.00 | 357.92 | 0.786627E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13816.76 | 21-JAN-09:01 | 13647.07 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.134124E+10 | 0.00 | 268.84 | 0.712486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13907.89 | 13-FEB-16:02 | 13643.23 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.146657E+10 | 0.00 | 286.12 | 0.661015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13497.93 | 18-MAR-15:01 | 12315.32 | 19-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.293636E+10 | 0.00 | 462.08 | 0.139396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13280.38 | 12-APR-08:62 | 13164.50 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.274934E+10 | 0.00 | 476.60 | 0.126904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13776.68 | 06-MAY-08:62 | 12816.69 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.408266E+10 | 0.00 | 557.13 | 0.175668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13936.10 | 28-JUN-08:62 | 12418.08 | 21-JUN-18:02 | 0.00 | 0.00 | 0.00 |
July | 0.597139E+10 | 0.00 | 631.87 | 0.261092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14723.05 | 30-JUL-08:61 | 12414.49 | 07-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.606892E+10 | 0.00 | 647.19 | 0.261248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14863.97 | 06-AUG-08:61 | 12360.62 | 08-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.459793E+10 | 0.00 | 605.00 | 0.199113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14556.95 | 22-SEP-15:01 | 12407.70 | 23-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.421190E+10 | 0.00 | 582.35 | 0.237721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14869.59 | 01-OCT-08:61 | 13646.82 | 13-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.199844E+10 | 0.00 | 417.98 | 0.101017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14018.89 | 12-NOV-09:02 | 13645.69 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.171439E+10 | 0.00 | 380.15 | 0.121439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13645.04 | 30-DEC-16:01 | 13645.04 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386588E+11 | 5673.23 | 0.183961E+11 | ||||||||||||
Minimum of Months | 0.134124E+10 | 0.00 | 268.84 | 0.661015E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13280.38 | 12315.32 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.606892E+10 | 0.00 | 647.19 | 0.261248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14869.59 | 13647.07 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.297911E+09 | 0.00 | 111.88 | 0.151697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13368.50 | 20-JAN-16:01 | 13343.68 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.450834E+09 | 0.00 | 151.08 | 0.205496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13470.82 | 13-FEB-16:02 | 13341.72 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.663150E+09 | 0.00 | 178.04 | 0.258143E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13544.36 | 22-MAR-18:11 | 12095.98 | 09-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.169855E+10 | 0.00 | 363.79 | 0.630592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13804.40 | 26-APR-21:11 | 12458.19 | 27-APR-18:21 | 0.00 | 0.00 | 0.00 |
May | 0.189646E+10 | 0.00 | 397.16 | 0.727788E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13433.69 | 06-MAY-08:62 | 12585.55 | 24-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.263988E+10 | 0.00 | 391.58 | 0.993353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14484.54 | 28-JUN-21:11 | 12204.23 | 04-JUN-18:51 | 0.00 | 0.00 | 0.00 |
July | 0.376103E+10 | 0.00 | 410.65 | 0.147883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15206.85 | 19-JUL-21:11 | 12101.70 | 21-JUL-15:01 | 0.00 | 0.00 | 0.00 |
August | 0.359666E+10 | 0.00 | 406.73 | 0.135152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15094.00 | 19-AUG-08:11 | 12115.17 | 02-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.249530E+10 | 0.00 | 399.49 | 0.901140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14455.22 | 30-SEP-21:11 | 12135.51 | 04-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.186843E+10 | 0.00 | 358.49 | 0.968171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14915.83 | 01-OCT-08:11 | 13673.20 | 14-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.526595E+09 | 0.00 | 212.86 | 0.223543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13432.03 | 12-NOV-16:01 | 13343.76 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.294915E+09 | 0.00 | 125.72 | 0.206239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13343.43 | 30-DEC-16:01 | 13343.43 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201897E+11 | 3507.48 | 0.809652E+10 | ||||||||||||
Minimum of Months | 0.294915E+09 | 0.00 | 111.88 | 0.151697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13343.43 | 12095.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.376103E+10 | 0.00 | 410.65 | 0.147883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15206.85 | 13673.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.317506E+11 | 0.00 | 555.31 | 0.222847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 43782.07 | 14-JAN-12:20 | 43782.07 | 14-JAN-12:20 | 0.00 | 0.00 | 0.00 |
February | 0.195777E+11 | 0.00 | 408.18 | 0.126322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38151.32 | 02-FEB-12:30 | 35870.27 | 03-FEB-12:30 | 0.00 | 0.00 | 0.00 |
March | 0.137098E+11 | 0.00 | 400.18 | 0.536383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29542.96 | 11-MAR-12:50 | 23630.09 | 11-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.142571E+11 | 0.00 | 482.14 | 0.427342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22440.23 | 04-APR-15:03 | 13048.82 | 02-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.905621E+10 | 0.00 | 448.00 | 0.206407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17830.06 | 04-MAY-20:20 | 7346.23 | 04-MAY-20:40 | 0.00 | 0.00 | 0.00 |
June | 0.136790E+11 | 0.00 | 531.83 | 0.332715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20101.83 | 30-JUN-07:00 | 7201.64 | 30-JUN-07:00 | 0.00 | 0.00 | 0.00 |
July | 0.213673E+11 | 0.00 | 648.33 | 0.596599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24024.84 | 23-JUL-08:00 | 9861.75 | 23-JUL-08:00 | 0.00 | 0.00 | 0.00 |
August | 0.273217E+11 | 0.00 | 698.62 | 0.861584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25488.05 | 19-AUG-15:03 | 12203.87 | 19-AUG-15:03 | 0.00 | 0.00 | 0.00 |
September | 0.301277E+11 | 0.00 | 685.18 | 0.120601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37162.39 | 30-SEP-12:00 | 33320.37 | 30-SEP-12:10 | 0.00 | 0.00 | 0.00 |
October | 0.397453E+11 | 0.00 | 679.19 | 0.255390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47916.58 | 16-OCT-12:10 | 47916.58 | 16-OCT-12:10 | 0.00 | 0.00 | 0.00 |
November | 0.326704E+11 | 0.00 | 575.28 | 0.213218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47221.16 | 19-NOV-10:00 | 40777.87 | 29-NOV-12:10 | 0.00 | 0.00 | 0.00 |
December | 0.360185E+11 | 0.00 | 580.16 | 0.286758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 45173.44 | 19-DEC-12:30 | 45173.44 | 19-DEC-12:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289281E+12 | 6692.39 | 0.152124E+12 | ||||||||||||
Minimum of Months | 0.905621E+10 | 0.00 | 400.18 | 0.206407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17830.06 | 7201.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.397453E+11 | 0.00 | 698.62 | 0.286758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47916.58 | 47916.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.120880E+11 | 0.00 | 336.57 | 0.620316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81368.41 | 16-JAN-09:02 | 81368.41 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.132910E+11 | 0.00 | 395.41 | 0.629443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82389.14 | 13-FEB-19:02 | 80020.21 | 03-FEB-19:01 | 0.00 | 0.00 | 0.00 |
March | 0.162000E+11 | 0.00 | 406.01 | 0.722391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79500.52 | 22-MAR-18:11 | 78677.15 | 11-MAR-09:11 | 0.00 | 0.00 | 0.00 |
April | 0.235203E+11 | 0.00 | 430.13 | 0.115094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85051.91 | 26-APR-21:11 | 79352.23 | 01-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.271603E+11 | 0.00 | 437.12 | 0.142795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 83193.43 | 02-MAY-21:11 | 78808.49 | 24-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.310440E+11 | 0.00 | 361.32 | 0.166177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89695.40 | 28-JUN-21:11 | 74788.34 | 24-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.373129E+11 | 0.00 | 365.23 | 0.208209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94617.82 | 19-JUL-21:11 | 75002.93 | 04-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.358005E+11 | 0.00 | 355.37 | 0.191503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92887.58 | 19-AUG-08:11 | 72524.93 | 01-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.285394E+11 | 0.00 | 353.38 | 0.144060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91056.19 | 22-SEP-21:12 | 72719.63 | 01-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.257614E+11 | 0.00 | 381.50 | 0.159976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93763.33 | 01-OCT-08:11 | 86806.52 | 15-OCT-07:41 | 0.00 | 0.00 | 0.00 |
November | 0.153032E+11 | 0.00 | 409.28 | 0.780717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81533.17 | 12-NOV-09:02 | 80909.24 | 19-NOV-09:11 | 0.00 | 0.00 | 0.00 |
December | 0.113167E+11 | 0.00 | 351.35 | 0.718317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80757.92 | 19-DEC-19:01 | 80757.92 | 19-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.277338E+12 | 4582.67 | 0.147493E+12 | ||||||||||||
Minimum of Months | 0.113167E+11 | 0.00 | 336.57 | 0.620316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79500.52 | 72524.93 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.373129E+11 | 0.00 | 437.12 | 0.208209E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94617.82 | 86806.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.163069E+10 | 0.00 | 375.38 | 0.954782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11893.51 | 05-JAN-09:01 | 11893.51 | 05-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.124515E+10 | 0.00 | 266.06 | 0.710204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11893.65 | 01-FEB-09:01 | 11893.65 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 |
March | 0.143793E+10 | 0.00 | 298.90 | 0.661765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11592.65 | 15-MAR-15:01 | 10687.78 | 09-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.260619E+10 | 0.00 | 455.79 | 0.124043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11888.48 | 02-APR-08:61 | 11888.48 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 |
May | 0.229402E+10 | 0.00 | 437.10 | 0.102958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12127.24 | 06-MAY-08:62 | 11884.39 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.332243E+10 | 0.00 | 541.52 | 0.142079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12291.77 | 29-JUN-08:62 | 10793.75 | 22-JUN-08:62 | 0.00 | 0.00 | 0.00 |
July | 0.529529E+10 | 0.00 | 671.98 | 0.235011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12278.07 | 12-JUL-15:01 | 10785.31 | 23-JUL-08:61 | 0.00 | 0.00 | 0.00 |
August | 0.568070E+10 | 0.00 | 685.88 | 0.251489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12423.32 | 08-AUG-08:62 | 10698.78 | 23-AUG-08:62 | 0.00 | 0.00 | 0.00 |
September | 0.380649E+10 | 0.00 | 610.16 | 0.165287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12979.59 | 22-SEP-15:01 | 10815.84 | 11-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.392439E+10 | 0.00 | 583.35 | 0.228725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13007.13 | 02-OCT-15:01 | 11894.41 | 18-OCT-08:61 | 0.00 | 0.00 | 0.00 |
November | 0.183997E+10 | 0.00 | 399.14 | 0.105018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12222.13 | 12-NOV-09:02 | 11889.98 | 30-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.171604E+10 | 0.00 | 383.34 | 0.130066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11893.94 | 23-DEC-09:01 | 11893.94 | 23-DEC-09:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347993E+11 | 5708.61 | 0.171735E+11 | ||||||||||||
Minimum of Months | 0.124515E+10 | 0.00 | 266.06 | 0.661765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11592.65 | 10687.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.568070E+10 | 0.00 | 685.88 | 0.251489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13007.13 | 11894.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.433783E+09 | 0.00 | 119.34 | 0.236465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11784.44 | 21-JAN-09:01 | 11515.30 | 04-JAN-09:01 | 0.00 | 0.00 | 0.00 |
February | 0.449643E+09 | 0.00 | 133.91 | 0.242027E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11844.19 | 01-FEB-09:11 | 11844.19 | 01-FEB-09:11 | 0.00 | 0.00 | 0.00 |
March | 0.741254E+09 | 0.00 | 177.87 | 0.337436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11713.70 | 24-MAR-15:01 | 10837.90 | 23-MAR-08:11 | 0.00 | 0.00 | 0.00 |
April | 0.174008E+10 | 0.00 | 320.11 | 0.850240E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12329.93 | 02-APR-08:11 | 12329.93 | 02-APR-08:11 | 0.00 | 0.00 | 0.00 |
May | 0.176901E+10 | 0.00 | 349.81 | 0.823028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12741.05 | 24-MAY-08:11 | 12741.05 | 24-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.237301E+10 | 0.00 | 390.84 | 0.107041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13413.41 | 30-JUN-08:11 | 11638.42 | 14-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.362074E+10 | 0.00 | 443.90 | 0.163426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14540.41 | 23-JUL-08:11 | 11766.66 | 04-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.360864E+10 | 0.00 | 439.86 | 0.160455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14658.40 | 19-AUG-08:11 | 11112.79 | 23-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.206515E+10 | 0.00 | 375.13 | 0.922413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13691.44 | 10-SEP-08:11 | 11358.19 | 03-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.181713E+10 | 0.00 | 329.12 | 0.107444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13754.84 | 15-OCT-07:41 | 13754.84 | 15-OCT-07:41 | 0.00 | 0.00 | 0.00 |
November | 0.550276E+09 | 0.00 | 172.98 | 0.276445E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12037.68 | 12-NOV-09:02 | 11672.03 | 27-NOV-09:12 | 0.00 | 0.00 | 0.00 |
December | 0.364946E+09 | 0.00 | 120.79 | 0.270113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12385.96 | 05-DEC-09:11 | 12385.96 | 05-DEC-09:11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195337E+11 | 3373.66 | 0.934184E+10 | ||||||||||||
Minimum of Months | 0.364946E+09 | 0.00 | 119.34 | 0.236465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11713.70 | 10837.90 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.362074E+10 | 0.00 | 443.90 | 0.163426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14658.40 | 13754.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.386061E+09 | 0.00 | 322.69 | 0.210642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3731.90 | 21-JAN-09:01 | 3529.43 | 03-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.346754E+09 | 0.00 | 235.61 | 0.194612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3614.47 | 13-FEB-16:02 | 3528.44 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.398688E+09 | 0.00 | 249.93 | 0.194538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3533.33 | 24-MAR-08:61 | 3139.58 | 21-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.835514E+09 | 0.00 | 443.61 | 0.424140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3629.33 | 12-APR-08:62 | 3447.65 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.787548E+09 | 0.00 | 453.32 | 0.380848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3719.95 | 06-MAY-08:62 | 3329.26 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.119962E+10 | 0.00 | 566.49 | 0.565228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3725.78 | 28-JUN-08:62 | 3214.41 | 13-JUN-18:01 | 0.00 | 0.00 | 0.00 |
July | 0.177922E+10 | 0.00 | 675.71 | 0.861505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3868.02 | 30-JUL-08:61 | 3210.96 | 19-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.179823E+10 | 0.00 | 685.68 | 0.858613E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.08 | 06-AUG-08:61 | 3212.74 | 05-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.130755E+10 | 0.00 | 629.17 | 0.613416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3880.83 | 22-SEP-08:62 | 3197.22 | 04-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.118074E+10 | 0.00 | 568.64 | 0.697318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3936.82 | 01-OCT-08:61 | 3529.25 | 13-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.517600E+09 | 0.00 | 376.48 | 0.275740E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3553.72 | 11-NOV-16:02 | 3529.21 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.433975E+09 | 0.00 | 344.12 | 0.317717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3529.71 | 05-DEC-19:01 | 3529.71 | 05-DEC-19:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109715E+11 | 5551.43 | 0.559432E+10 | ||||||||||||
Minimum of Months | 0.346754E+09 | 0.00 | 235.61 | 0.194538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3529.71 | 3139.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.179823E+10 | 0.00 | 685.68 | 0.861505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3966.08 | 3529.71 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 71646425.11 | 0.00 | 90.83 | 37793942.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3547.49 | 21-JAN-09:01 | 3451.51 | 14-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.110453E+09 | 0.00 | 119.29 | 53861920.22 | 0.00 | 0.00 | 0.00 | 0.00 | 3451.06 | 06-FEB-16:01 | 3451.06 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.181591E+09 | 0.00 | 155.11 | 76740177.30 | 0.00 | 0.00 | 0.00 | 0.00 | 3585.71 | 22-MAR-18:11 | 3104.46 | 09-MAR-16:01 | 0.00 | 0.00 | 0.00 |
April | 0.509399E+09 | 0.00 | 342.98 | 0.211029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3706.26 | 26-APR-21:11 | 3500.09 | 27-APR-18:21 | 0.00 | 0.00 | 0.00 |
May | 0.569539E+09 | 0.00 | 388.24 | 0.245110E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3625.53 | 06-MAY-08:62 | 3341.99 | 23-MAY-18:21 | 0.00 | 0.00 | 0.00 |
June | 0.848502E+09 | 0.00 | 420.72 | 0.365739E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3902.07 | 28-JUN-21:11 | 3308.11 | 04-JUN-18:51 | 0.00 | 0.00 | 0.00 |
July | 0.124938E+10 | 0.00 | 451.80 | 0.568762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4039.38 | 19-JUL-21:11 | 3147.70 | 08-JUL-20:31 | 0.00 | 0.00 | 0.00 |
August | 0.118426E+10 | 0.00 | 446.99 | 0.515746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4009.18 | 19-AUG-08:11 | 3087.38 | 05-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.760174E+09 | 0.00 | 419.43 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3830.39 | 22-SEP-08:12 | 3148.22 | 15-SEP-18:31 | 0.00 | 0.00 | 0.00 |
October | 0.559402E+09 | 0.00 | 353.59 | 0.305196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3988.46 | 01-OCT-08:11 | 3588.65 | 15-OCT-21:11 | 0.00 | 0.00 | 0.00 |
November | 0.126195E+09 | 0.00 | 170.67 | 56071364.99 | 0.00 | 0.00 | 0.00 | 0.00 | 3479.90 | 12-NOV-16:01 | 3451.70 | 22-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 67406336.63 | 0.00 | 91.87 | 50023688.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3451.47 | 30-DEC-16:01 | 3451.47 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623794E+10 | 3451.52 | 0.279156E+10 | ||||||||||||
Minimum of Months | 67406336.63 | 0.00 | 90.83 | 37793942.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3451.06 | 3087.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124938E+10 | 0.00 | 451.80 | 0.568762E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4039.38 | 3588.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.699734E+10 | 0.00 | 553.61 | 0.506764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15574.07 | 15-JAN-16:01 | 15574.07 | 15-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.451701E+10 | 0.00 | 437.36 | 0.301605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16083.37 | 11-FEB-16:03 | 15572.30 | 06-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.371950E+10 | 0.00 | 418.82 | 0.191303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15336.86 | 20-MAR-15:02 | 14196.09 | 18-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.423064E+10 | 0.00 | 537.63 | 0.187947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15246.93 | 01-APR-18:02 | 15246.93 | 01-APR-18:02 | 0.00 | 0.00 | 0.00 |
May | 0.290528E+10 | 0.00 | 459.16 | 0.111563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15861.49 | 06-MAY-15:01 | 14543.42 | 24-MAY-08:61 | 0.00 | 0.00 | 0.00 |
June | 0.417788E+10 | 0.00 | 542.81 | 0.155849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16077.00 | 27-JUN-18:01 | 13646.42 | 12-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.669138E+10 | 0.00 | 634.41 | 0.271598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16977.26 | 30-JUL-08:61 | 13800.73 | 10-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.806042E+10 | 0.00 | 667.27 | 0.343424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17138.05 | 20-AUG-08:61 | 14137.90 | 16-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.775081E+10 | 0.00 | 637.01 | 0.372304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16730.69 | 22-SEP-08:62 | 14128.95 | 09-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.931466E+10 | 0.00 | 653.39 | 0.633140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17190.03 | 05-OCT-18:01 | 15573.09 | 25-OCT-18:01 | 0.00 | 0.00 | 0.00 |
November | 0.713480E+10 | 0.00 | 588.31 | 0.497812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15940.44 | 12-NOV-09:02 | 15574.28 | 19-NOV-09:02 | 0.00 | 0.00 | 0.00 |
December | 0.754998E+10 | 0.00 | 562.18 | 0.614978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15574.08 | 30-DEC-16:01 | 15574.08 | 30-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.730497E+11 | 6691.97 | 0.418829E+11 | ||||||||||||
Minimum of Months | 0.290528E+10 | 0.00 | 418.82 | 0.111563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15246.93 | 13646.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.931466E+10 | 0.00 | 667.27 | 0.633140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17190.03 | 15574.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.798106E+11 | 0.00 | 335.50 | 0.786941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214791.90 | 14-JAN-11:50 | 214791.90 | 14-JAN-11:50 | 0.00 | 0.00 | 0.00 |
February | 0.501066E+11 | 0.00 | 278.42 | 0.472049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207179.32 | 01-FEB-12:00 | 207179.32 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.524697E+11 | 0.00 | 248.00 | 0.488638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 216365.60 | 23-MAR-15:03 | 181528.76 | 11-MAR-11:50 | 0.00 | 0.00 | 0.00 |
April | 0.114565E+12 | 0.00 | 401.75 | 0.106442E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 261015.50 | 26-APR-11:00 | 220706.74 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.123752E+12 | 0.00 | 494.67 | 0.119048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183562.29 | 04-MAY-13:00 | 178272.52 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 |
June | 0.243089E+12 | 0.00 | 665.67 | 0.189721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322114.65 | 29-JUN-11:00 | 196116.70 | 29-JUN-10:50 | 0.00 | 0.00 | 0.00 |
July | 0.468005E+12 | 0.00 | 740.83 | 0.277132E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 401572.01 | 19-JUL-12:00 | 242360.06 | 19-JUL-10:50 | 0.00 | 0.00 | 0.00 |
August | 0.524287E+12 | 0.00 | 744.00 | 0.287369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 409013.24 | 14-AUG-10:50 | 242412.42 | 14-AUG-10:50 | 0.00 | 0.00 | 0.00 |
September | 0.325816E+12 | 0.00 | 695.67 | 0.223306E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 435200.79 | 22-SEP-12:00 | 361260.35 | 29-SEP-10:50 | 0.00 | 0.00 | 0.00 |
October | 0.329391E+12 | 0.00 | 641.67 | 0.251703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 396975.38 | 01-OCT-12:00 | 381211.57 | 16-OCT-10:50 | 0.00 | 0.00 | 0.00 |
November | 0.874223E+11 | 0.00 | 381.81 | 0.828461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 227865.78 | 19-NOV-13:00 | 227865.78 | 19-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 0.888017E+11 | 0.00 | 331.50 | 0.886924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211218.95 | 16-DEC-13:00 | 211218.95 | 16-DEC-13:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248752E+13 | 5959.48 | 0.180102E+13 | ||||||||||||
Minimum of Months | 0.501066E+11 | 0.00 | 248.00 | 0.472049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183562.29 | 178272.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.524287E+12 | 0.00 | 744.00 | 0.287369E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 435200.79 | 381211.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.351486E+10 | 0.00 | 171.17 | 0.349645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20564.52 | 13-JAN-14:00 | 20564.52 | 13-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.189168E+10 | 0.00 | 130.67 | 0.183904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17577.71 | 01-FEB-10:00 | 17577.71 | 01-FEB-10:00 | 0.00 | 0.00 | 0.00 |
March | 0.212621E+10 | 0.00 | 110.00 | 0.197406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21789.55 | 22-MAR-13:00 | 17617.08 | 11-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.532087E+10 | 0.00 | 211.67 | 0.504414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22084.04 | 26-APR-13:00 | 22084.04 | 26-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.566791E+10 | 0.00 | 273.33 | 0.558001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18514.43 | 04-MAY-13:00 | 17656.84 | 03-MAY-12:15 | 0.00 | 0.00 | 0.00 |
June | 0.126650E+11 | 0.00 | 460.00 | 0.101484E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30621.91 | 29-JUN-12:15 | 17821.10 | 29-JUN-12:15 | 0.00 | 0.00 | 0.00 |
July | 0.283929E+11 | 0.00 | 581.00 | 0.167718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39897.45 | 31-JUL-12:15 | 23759.11 | 31-JUL-12:30 | 0.00 | 0.00 | 0.00 |
August | 0.324272E+11 | 0.00 | 582.67 | 0.176768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38506.98 | 14-AUG-10:00 | 22280.23 | 18-AUG-12:15 | 0.00 | 0.00 | 0.00 |
September | 0.184524E+11 | 0.00 | 518.17 | 0.130038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39498.06 | 22-SEP-12:15 | 35112.96 | 29-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.205486E+11 | 0.00 | 461.00 | 0.151787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37935.62 | 01-OCT-12:20 | 34139.72 | 16-OCT-12:20 | 0.00 | 0.00 | 0.00 |
November | 0.353985E+10 | 0.00 | 209.17 | 0.347634E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21030.69 | 19-NOV-13:15 | 21030.69 | 19-NOV-13:15 | 0.00 | 0.00 | 0.00 |
December | 0.428200E+10 | 0.00 | 177.33 | 0.428068E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20474.50 | 05-DEC-10:00 | 20474.50 | 05-DEC-10:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138829E+12 | 3886.17 | 0.984703E+11 | ||||||||||||
Minimum of Months | 0.189168E+10 | 0.00 | 110.00 | 0.183904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17577.71 | 17577.71 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.324272E+11 | 0.00 | 582.67 | 0.176768E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39897.45 | 35112.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.03 | 507.37 | 183.66 | 981.05 | 354.47 | 0.00 | 0.00 | 744.00 |
February | 545.81 | 337.77 | 208.04 | 713.69 | 322.63 | 0.00 | 0.00 | 672.00 |
March | 435.17 | 211.95 | 223.22 | 529.96 | 335.25 | 0.00 | 0.00 | 744.00 |
April | 363.79 | 140.51 | 223.28 | 418.45 | 259.71 | 0.00 | 0.00 | 720.00 |
May | 256.31 | 30.93 | 225.38 | 256.10 | 229.55 | 0.00 | 0.00 | 744.00 |
June | 224.85 | 13.08 | 211.77 | 245.59 | 165.06 | 0.00 | 0.00 | 720.00 |
July | 237.09 | 25.22 | 211.88 | 286.25 | 137.22 | 0.00 | 0.00 | 744.00 |
August | 304.55 | 94.52 | 210.03 | 387.99 | 145.39 | 0.00 | 0.00 | 744.00 |
September | 418.30 | 207.74 | 210.56 | 572.33 | 180.60 | 0.00 | 0.00 | 720.00 |
October | 547.96 | 368.02 | 179.95 | 821.52 | 208.92 | 0.00 | 0.00 | 744.00 |
November | 665.72 | 471.73 | 193.99 | 940.12 | 317.69 | 0.00 | 0.00 | 720.00 |
December | 739.48 | 563.54 | 175.93 | 1062.54 | 355.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 452.12 | 247.39 | 204.72 | 601.00 | 250.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 224.85 | 13.08 | 175.93 | 245.59 | 137.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 739.48 | 563.54 | 225.38 | 1062.54 | 355.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1945.91 | 1428.72 | 517.18 | 2725.81 | 1086.52 | 0.00 | 0.00 | 744.00 |
February | 1536.96 | 951.13 | 585.83 | 1972.31 | 1006.07 | 0.00 | 0.00 | 672.00 |
March | 1225.42 | 596.84 | 628.58 | 1460.20 | 1033.20 | 0.00 | 0.00 | 744.00 |
April | 1024.41 | 395.67 | 628.74 | 1146.18 | 820.76 | 0.00 | 0.00 | 720.00 |
May | 721.76 | 87.11 | 634.65 | 689.70 | 725.91 | 0.00 | 0.00 | 744.00 |
June | 633.15 | 36.82 | 596.33 | 657.99 | 536.56 | 0.00 | 0.00 | 720.00 |
July | 667.64 | 71.00 | 596.64 | 772.00 | 450.70 | 0.00 | 0.00 | 744.00 |
August | 857.59 | 266.17 | 591.42 | 1061.61 | 479.32 | 0.00 | 0.00 | 744.00 |
September | 1177.91 | 584.99 | 592.92 | 1582.60 | 587.76 | 0.00 | 0.00 | 720.00 |
October | 1543.03 | 1036.32 | 506.72 | 2282.22 | 668.18 | 0.00 | 0.00 | 744.00 |
November | 1874.62 | 1328.36 | 546.26 | 2606.33 | 990.80 | 0.00 | 0.00 | 720.00 |
December | 2082.32 | 1586.90 | 495.41 | 2952.21 | 1093.03 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1273.13 | 696.64 | 576.49 | 1658.28 | 788.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 633.15 | 36.82 | 495.41 | 657.99 | 450.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2082.32 | 1586.90 | 634.65 | 2952.21 | 1093.03 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2527.84 | 1855.99 | 671.85 | 3636.19 | 1428.40 | 0.00 | 0.00 | 744.00 |
February | 1996.60 | 1235.57 | 761.03 | 2625.65 | 1344.45 | 0.00 | 0.00 | 672.00 |
March | 1591.89 | 775.33 | 816.56 | 1936.79 | 1397.00 | 0.00 | 0.00 | 744.00 |
April | 1330.77 | 514.00 | 816.77 | 1519.88 | 1108.11 | 0.00 | 0.00 | 720.00 |
May | 937.61 | 113.16 | 824.45 | 903.27 | 995.15 | 0.00 | 0.00 | 744.00 |
June | 822.50 | 47.84 | 774.67 | 864.95 | 734.14 | 0.00 | 0.00 | 720.00 |
July | 867.30 | 92.24 | 775.06 | 1024.37 | 611.31 | 0.00 | 0.00 | 744.00 |
August | 1114.06 | 345.77 | 768.29 | 1417.36 | 637.37 | 0.00 | 0.00 | 744.00 |
September | 1530.17 | 759.93 | 770.23 | 2114.44 | 774.25 | 0.00 | 0.00 | 720.00 |
October | 2004.49 | 1346.23 | 658.25 | 3050.35 | 866.54 | 0.00 | 0.00 | 744.00 |
November | 2435.24 | 1725.62 | 709.62 | 3474.38 | 1303.59 | 0.00 | 0.00 | 720.00 |
December | 2705.05 | 2061.48 | 643.57 | 3938.42 | 1434.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1653.86 | 904.97 | 748.90 | 2207.77 | 1051.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 822.50 | 47.84 | 643.57 | 864.95 | 611.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2705.05 | 2061.48 | 824.45 | 3938.42 | 1434.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.35 | 100.11 | 36.24 | 195.62 | 73.23 | 0.00 | 0.00 | 744.00 |
February | 107.70 | 66.65 | 41.05 | 140.20 | 67.60 | 0.00 | 0.00 | 672.00 |
March | 85.87 | 41.82 | 44.04 | 102.97 | 72.31 | 0.00 | 0.00 | 744.00 |
April | 71.78 | 27.72 | 44.06 | 80.07 | 56.45 | 0.00 | 0.00 | 720.00 |
May | 50.57 | 6.10 | 44.47 | 46.48 | 50.87 | 0.00 | 0.00 | 744.00 |
June | 44.37 | 2.58 | 41.79 | 44.37 | 36.34 | 0.00 | 0.00 | 720.00 |
July | 46.78 | 4.98 | 41.81 | 53.20 | 29.75 | 0.00 | 0.00 | 744.00 |
August | 60.09 | 18.65 | 41.44 | 74.83 | 30.73 | 0.00 | 0.00 | 744.00 |
September | 82.54 | 40.99 | 41.55 | 112.58 | 37.43 | 0.00 | 0.00 | 720.00 |
October | 108.12 | 72.62 | 35.51 | 164.45 | 41.15 | 0.00 | 0.00 | 744.00 |
November | 131.36 | 93.08 | 38.28 | 186.96 | 64.93 | 0.00 | 0.00 | 720.00 |
December | 145.91 | 111.20 | 34.71 | 212.19 | 72.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 89.21 | 48.81 | 40.40 | 117.77 | 52.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 44.37 | 2.58 | 34.71 | 44.37 | 29.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 145.91 | 111.20 | 44.47 | 212.19 | 73.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.78 | 49.81 | 48.97 | 109.53 | 148.54 | 0.00 | 0.00 | 744.00 |
February | 117.98 | 54.53 | 63.45 | 129.29 | 132.05 | 0.00 | 0.00 | 672.00 |
March | 134.94 | 59.64 | 75.30 | 153.32 | 134.89 | 0.00 | 0.00 | 744.00 |
April | 185.97 | 96.68 | 89.28 | 244.59 | 101.51 | 0.00 | 0.00 | 720.00 |
May | 182.67 | 84.25 | 98.43 | 235.00 | 90.01 | 0.00 | 0.00 | 744.00 |
June | 193.46 | 96.60 | 96.87 | 267.61 | 63.49 | 0.00 | 0.00 | 720.00 |
July | 204.85 | 109.50 | 95.35 | 301.60 | 52.12 | 0.00 | 0.00 | 744.00 |
August | 192.23 | 104.09 | 88.14 | 285.30 | 54.94 | 0.00 | 0.00 | 744.00 |
September | 164.76 | 88.13 | 76.62 | 234.03 | 67.66 | 0.00 | 0.00 | 720.00 |
October | 126.55 | 69.34 | 57.21 | 184.12 | 79.36 | 0.00 | 0.00 | 744.00 |
November | 113.87 | 59.60 | 54.27 | 133.45 | 129.23 | 0.00 | 0.00 | 720.00 |
December | 100.16 | 53.56 | 46.61 | 113.40 | 148.05 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.48 | 77.24 | 74.24 | 199.62 | 100.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 98.78 | 49.81 | 46.61 | 109.53 | 52.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 204.85 | 109.50 | 98.43 | 301.60 | 148.54 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.60 | 0.00 | 20.60 | 12.71 | 79.46 | 0.00 | 0.00 | 744.00 |
February | 25.86 | 0.00 | 25.86 | 14.10 | 71.65 | 0.00 | 0.00 | 672.00 |
March | 31.70 | 0.00 | 31.70 | 20.70 | 74.00 | 0.00 | 0.00 | 744.00 |
April | 36.71 | 0.29 | 36.42 | 29.19 | 56.03 | 0.00 | 0.00 | 720.00 |
May | 44.16 | 2.30 | 41.86 | 34.85 | 47.85 | 0.00 | 0.00 | 744.00 |
June | 46.80 | 4.61 | 42.19 | 43.70 | 34.82 | 0.00 | 0.00 | 720.00 |
July | 44.33 | 3.75 | 40.58 | 46.72 | 30.56 | 0.00 | 0.00 | 744.00 |
August | 36.86 | 0.81 | 36.05 | 40.69 | 32.77 | 0.00 | 0.00 | 744.00 |
September | 31.12 | 0.01 | 31.12 | 33.21 | 39.27 | 0.00 | 0.00 | 720.00 |
October | 24.68 | 0.00 | 24.68 | 30.59 | 44.44 | 0.00 | 0.00 | 744.00 |
November | 22.35 | 0.00 | 22.35 | 14.79 | 70.04 | 0.00 | 0.00 | 720.00 |
December | 19.18 | 0.00 | 19.18 | 11.64 | 79.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 32.06 | 0.99 | 31.07 | 27.82 | 54.94 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.18 | 0.00 | 19.18 | 11.64 | 30.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 46.80 | 4.61 | 42.19 | 46.72 | 79.46 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.78 | 49.81 | 48.97 | 115.92 | 144.52 | 0.00 | 0.00 | 744.00 |
February | 117.98 | 54.53 | 63.45 | 133.93 | 129.29 | 0.00 | 0.00 | 672.00 |
March | 134.94 | 59.64 | 75.30 | 156.20 | 133.29 | 0.00 | 0.00 | 744.00 |
April | 185.97 | 96.68 | 89.28 | 243.96 | 101.96 | 0.00 | 0.00 | 720.00 |
May | 182.67 | 84.25 | 98.43 | 232.21 | 91.28 | 0.00 | 0.00 | 744.00 |
June | 193.46 | 96.60 | 96.87 | 261.80 | 67.23 | 0.00 | 0.00 | 720.00 |
July | 204.85 | 109.50 | 95.35 | 293.82 | 57.88 | 0.00 | 0.00 | 744.00 |
August | 192.23 | 104.09 | 88.14 | 279.90 | 60.45 | 0.00 | 0.00 | 744.00 |
September | 164.76 | 88.13 | 76.62 | 233.42 | 70.15 | 0.00 | 0.00 | 720.00 |
October | 126.55 | 69.34 | 57.21 | 186.17 | 80.79 | 0.00 | 0.00 | 744.00 |
November | 113.87 | 59.60 | 54.27 | 139.01 | 126.18 | 0.00 | 0.00 | 720.00 |
December | 100.16 | 53.56 | 46.61 | 119.94 | 143.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.48 | 77.24 | 74.24 | 200.01 | 100.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 98.78 | 49.81 | 46.61 | 115.92 | 57.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 204.85 | 109.50 | 98.43 | 293.82 | 144.52 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.06 | 80.07 | 28.99 | 141.70 | 87.79 | 0.00 | 0.00 | 744.00 |
February | 86.14 | 53.31 | 32.83 | 98.13 | 84.36 | 0.00 | 0.00 | 672.00 |
March | 68.68 | 33.45 | 35.23 | 69.28 | 87.27 | 0.00 | 0.00 | 744.00 |
April | 57.41 | 22.18 | 35.24 | 51.24 | 71.88 | 0.00 | 0.00 | 720.00 |
May | 40.45 | 4.88 | 35.57 | 23.76 | 66.06 | 0.00 | 0.00 | 744.00 |
June | 35.49 | 2.06 | 33.42 | 21.36 | 52.28 | 0.00 | 0.00 | 720.00 |
July | 37.42 | 3.98 | 33.44 | 28.18 | 45.49 | 0.00 | 0.00 | 744.00 |
August | 48.06 | 14.92 | 33.15 | 45.84 | 47.65 | 0.00 | 0.00 | 744.00 |
September | 66.02 | 32.79 | 33.23 | 76.64 | 55.26 | 0.00 | 0.00 | 720.00 |
October | 86.48 | 58.08 | 28.40 | 117.09 | 59.18 | 0.00 | 0.00 | 744.00 |
November | 105.06 | 74.45 | 30.62 | 134.66 | 80.59 | 0.00 | 0.00 | 720.00 |
December | 116.70 | 88.94 | 27.77 | 154.55 | 87.42 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 71.35 | 39.04 | 32.31 | 80.16 | 68.68 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 35.49 | 2.06 | 27.77 | 21.36 | 45.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.70 | 88.94 | 35.57 | 154.55 | 87.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.49 | 0.00 | 16.49 | 10.08 | 65.07 | 0.00 | 0.00 | 744.00 |
February | 20.69 | 0.00 | 20.69 | 11.36 | 58.50 | 0.00 | 0.00 | 672.00 |
March | 25.36 | 0.00 | 25.36 | 16.93 | 60.15 | 0.00 | 0.00 | 744.00 |
April | 29.37 | 0.23 | 29.14 | 25.58 | 43.76 | 0.00 | 0.00 | 720.00 |
May | 35.33 | 1.84 | 33.49 | 30.51 | 37.81 | 0.00 | 0.00 | 744.00 |
June | 37.45 | 3.69 | 33.76 | 38.39 | 27.00 | 0.00 | 0.00 | 720.00 |
July | 35.47 | 3.00 | 32.47 | 41.41 | 23.09 | 0.00 | 0.00 | 744.00 |
August | 29.50 | 0.65 | 28.84 | 35.95 | 24.54 | 0.00 | 0.00 | 744.00 |
September | 24.90 | 0.00 | 24.90 | 28.81 | 29.99 | 0.00 | 0.00 | 720.00 |
October | 19.75 | 0.00 | 19.75 | 25.77 | 35.08 | 0.00 | 0.00 | 744.00 |
November | 17.88 | 0.00 | 17.88 | 12.18 | 56.44 | 0.00 | 0.00 | 720.00 |
December | 15.35 | 0.00 | 15.35 | 9.32 | 64.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.65 | 0.79 | 24.86 | 23.93 | 43.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 15.35 | 0.00 | 15.35 | 9.32 | 23.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 37.45 | 3.69 | 33.76 | 41.41 | 65.07 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 55.39 | 48.28 | 110.72 | 140.57 | 0.00 | 0.00 | 744.00 |
February | 109.39 | 50.05 | 59.33 | 110.37 | 126.17 | 0.00 | 0.00 | 672.00 |
March | 133.51 | 59.64 | 73.88 | 146.48 | 128.53 | 0.00 | 0.00 | 744.00 |
April | 170.18 | 85.39 | 84.79 | 217.25 | 97.14 | 0.00 | 0.00 | 720.00 |
May | 160.28 | 66.79 | 93.49 | 199.32 | 86.95 | 0.00 | 0.00 | 744.00 |
June | 159.47 | 69.23 | 90.24 | 214.49 | 62.79 | 0.00 | 0.00 | 720.00 |
July | 180.59 | 89.71 | 90.87 | 263.70 | 52.08 | 0.00 | 0.00 | 744.00 |
August | 178.49 | 94.86 | 83.63 | 263.97 | 53.57 | 0.00 | 0.00 | 744.00 |
September | 130.32 | 59.94 | 70.38 | 179.27 | 66.06 | 0.00 | 0.00 | 720.00 |
October | 114.85 | 58.95 | 55.90 | 162.61 | 75.30 | 0.00 | 0.00 | 744.00 |
November | 104.45 | 52.88 | 51.57 | 114.09 | 123.68 | 0.00 | 0.00 | 720.00 |
December | 100.41 | 55.96 | 44.45 | 106.15 | 140.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 137.32 | 66.70 | 70.62 | 174.48 | 95.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 100.41 | 50.05 | 44.45 | 106.15 | 52.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.59 | 94.86 | 93.49 | 263.97 | 140.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.35 | 100.11 | 36.24 | 194.80 | 73.01 | 0.00 | 0.00 | 744.00 |
February | 107.70 | 66.65 | 41.05 | 139.76 | 66.98 | 0.00 | 0.00 | 672.00 |
March | 85.87 | 41.82 | 44.04 | 102.13 | 71.80 | 0.00 | 0.00 | 744.00 |
April | 71.78 | 27.72 | 44.06 | 79.10 | 55.54 | 0.00 | 0.00 | 720.00 |
May | 50.57 | 6.10 | 44.47 | 45.86 | 49.86 | 0.00 | 0.00 | 744.00 |
June | 44.37 | 2.58 | 41.79 | 43.95 | 35.19 | 0.00 | 0.00 | 720.00 |
July | 46.78 | 4.98 | 41.81 | 52.42 | 28.70 | 0.00 | 0.00 | 744.00 |
August | 60.09 | 18.65 | 41.44 | 73.97 | 29.83 | 0.00 | 0.00 | 744.00 |
September | 82.54 | 40.99 | 41.55 | 112.50 | 36.26 | 0.00 | 0.00 | 720.00 |
October | 108.12 | 72.62 | 35.51 | 164.05 | 40.55 | 0.00 | 0.00 | 744.00 |
November | 131.36 | 93.08 | 38.28 | 186.55 | 64.32 | 0.00 | 0.00 | 720.00 |
December | 145.91 | 111.20 | 34.71 | 211.57 | 72.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 89.21 | 48.81 | 40.40 | 117.16 | 51.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 44.37 | 2.58 | 34.71 | 43.95 | 28.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 145.91 | 111.20 | 44.47 | 211.57 | 73.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.60 | 0.00 | 20.60 | 12.04 | 79.05 | 0.00 | 0.00 | 744.00 |
February | 25.86 | 0.00 | 25.86 | 13.65 | 70.70 | 0.00 | 0.00 | 672.00 |
March | 31.70 | 0.00 | 31.70 | 19.97 | 73.31 | 0.00 | 0.00 | 744.00 |
April | 36.71 | 0.29 | 36.42 | 28.66 | 54.40 | 0.00 | 0.00 | 720.00 |
May | 44.16 | 2.30 | 41.86 | 35.17 | 46.63 | 0.00 | 0.00 | 744.00 |
June | 46.80 | 4.61 | 42.19 | 44.67 | 33.07 | 0.00 | 0.00 | 720.00 |
July | 44.33 | 3.75 | 40.58 | 47.31 | 28.56 | 0.00 | 0.00 | 744.00 |
August | 36.86 | 0.81 | 36.05 | 40.50 | 30.71 | 0.00 | 0.00 | 744.00 |
September | 31.12 | 0.01 | 31.12 | 33.39 | 36.94 | 0.00 | 0.00 | 720.00 |
October | 24.68 | 0.00 | 24.68 | 30.18 | 43.15 | 0.00 | 0.00 | 744.00 |
November | 22.35 | 0.00 | 22.35 | 14.41 | 68.78 | 0.00 | 0.00 | 720.00 |
December | 19.18 | 0.00 | 19.18 | 11.03 | 78.63 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 32.06 | 0.99 | 31.07 | 27.67 | 53.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.18 | 0.00 | 19.18 | 11.03 | 28.56 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 46.80 | 4.61 | 42.19 | 47.31 | 79.05 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.66 | 55.39 | 48.28 | 116.45 | 135.30 | 0.00 | 0.00 | 744.00 |
February | 109.39 | 50.05 | 59.33 | 114.92 | 122.61 | 0.00 | 0.00 | 672.00 |
March | 133.51 | 59.64 | 73.88 | 149.64 | 126.53 | 0.00 | 0.00 | 744.00 |
April | 170.18 | 85.39 | 84.79 | 218.55 | 96.94 | 0.00 | 0.00 | 720.00 |
May | 160.28 | 66.79 | 93.49 | 198.50 | 87.77 | 0.00 | 0.00 | 744.00 |
June | 159.47 | 69.23 | 90.24 | 211.68 | 65.52 | 0.00 | 0.00 | 720.00 |
July | 180.59 | 89.71 | 90.87 | 259.15 | 56.42 | 0.00 | 0.00 | 744.00 |
August | 178.49 | 94.86 | 83.63 | 260.60 | 57.44 | 0.00 | 0.00 | 744.00 |
September | 130.32 | 59.94 | 70.38 | 180.22 | 67.18 | 0.00 | 0.00 | 720.00 |
October | 114.85 | 58.95 | 55.90 | 165.16 | 75.76 | 0.00 | 0.00 | 744.00 |
November | 104.45 | 52.88 | 51.57 | 119.44 | 119.06 | 0.00 | 0.00 | 720.00 |
December | 100.41 | 55.96 | 44.45 | 112.06 | 134.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 137.32 | 66.70 | 70.62 | 175.95 | 95.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 100.41 | 50.05 | 44.45 | 112.06 | 56.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 180.59 | 94.86 | 93.49 | 260.60 | 135.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.09 | 0.00 | 26.09 | 17.63 | 94.93 | 0.00 | 0.00 | 744.00 |
February | 32.76 | 0.00 | 32.76 | 20.48 | 84.67 | 0.00 | 0.00 | 672.00 |
March | 40.14 | 0.00 | 40.14 | 30.02 | 86.90 | 0.00 | 0.00 | 744.00 |
April | 46.49 | 0.37 | 46.12 | 45.21 | 62.53 | 0.00 | 0.00 | 720.00 |
May | 55.92 | 2.91 | 53.01 | 54.77 | 53.57 | 0.00 | 0.00 | 744.00 |
June | 59.27 | 5.84 | 53.43 | 69.20 | 36.50 | 0.00 | 0.00 | 720.00 |
July | 56.14 | 4.75 | 51.39 | 75.10 | 29.50 | 0.00 | 0.00 | 744.00 |
August | 46.69 | 1.03 | 45.66 | 64.97 | 31.13 | 0.00 | 0.00 | 744.00 |
September | 39.41 | 0.01 | 39.41 | 50.81 | 40.47 | 0.00 | 0.00 | 720.00 |
October | 31.26 | 0.00 | 31.26 | 44.74 | 47.80 | 0.00 | 0.00 | 744.00 |
November | 28.30 | 0.00 | 28.30 | 21.34 | 82.06 | 0.00 | 0.00 | 720.00 |
December | 24.29 | 0.00 | 24.29 | 16.23 | 94.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.60 | 1.25 | 39.35 | 42.68 | 61.95 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.29 | 0.00 | 24.29 | 16.23 | 29.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.27 | 5.84 | 53.43 | 75.10 | 94.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 9.62 | 0.00 | 9.62 | 6.50 | 35.00 | 0.00 | 0.00 | 744.00 |
February | 12.08 | 0.00 | 12.08 | 7.55 | 31.21 | 0.00 | 0.00 | 672.00 |
March | 14.80 | 0.00 | 14.80 | 11.07 | 32.04 | 0.00 | 0.00 | 744.00 |
April | 17.14 | 0.14 | 17.00 | 16.66 | 23.05 | 0.00 | 0.00 | 720.00 |
May | 20.61 | 1.07 | 19.54 | 20.19 | 19.75 | 0.00 | 0.00 | 744.00 |
June | 21.85 | 2.15 | 19.70 | 25.51 | 13.45 | 0.00 | 0.00 | 720.00 |
July | 20.70 | 1.75 | 18.95 | 27.68 | 10.88 | 0.00 | 0.00 | 744.00 |
August | 17.21 | 0.38 | 16.83 | 23.95 | 11.48 | 0.00 | 0.00 | 744.00 |
September | 14.53 | 0.00 | 14.53 | 18.73 | 14.92 | 0.00 | 0.00 | 720.00 |
October | 11.52 | 0.00 | 11.52 | 16.49 | 17.62 | 0.00 | 0.00 | 744.00 |
November | 10.43 | 0.00 | 10.43 | 7.87 | 30.25 | 0.00 | 0.00 | 720.00 |
December | 8.95 | 0.00 | 8.95 | 5.98 | 34.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 14.97 | 0.46 | 14.51 | 15.73 | 22.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.95 | 0.00 | 8.95 | 5.98 | 10.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 21.85 | 2.15 | 19.70 | 27.68 | 35.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 63.62 | 46.71 | 16.91 | 93.66 | 31.56 | 0.00 | 0.00 | 744.00 |
February | 50.25 | 31.10 | 19.15 | 67.83 | 29.10 | 0.00 | 0.00 | 672.00 |
March | 40.06 | 19.51 | 20.55 | 50.16 | 31.06 | 0.00 | 0.00 | 744.00 |
April | 33.49 | 12.94 | 20.56 | 40.20 | 23.42 | 0.00 | 0.00 | 720.00 |
May | 23.60 | 2.85 | 20.75 | 24.70 | 21.09 | 0.00 | 0.00 | 744.00 |
June | 20.70 | 1.20 | 19.50 | 24.11 | 14.57 | 0.00 | 0.00 | 720.00 |
July | 21.83 | 2.32 | 19.51 | 28.59 | 11.49 | 0.00 | 0.00 | 744.00 |
August | 28.04 | 8.70 | 19.34 | 38.42 | 11.81 | 0.00 | 0.00 | 744.00 |
September | 38.51 | 19.13 | 19.39 | 55.52 | 14.87 | 0.00 | 0.00 | 720.00 |
October | 50.45 | 33.88 | 16.57 | 79.42 | 16.76 | 0.00 | 0.00 | 744.00 |
November | 61.29 | 43.43 | 17.86 | 89.90 | 27.64 | 0.00 | 0.00 | 720.00 |
December | 68.08 | 51.88 | 16.20 | 101.51 | 31.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 41.62 | 22.78 | 18.85 | 57.81 | 22.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 20.70 | 1.20 | 16.20 | 24.11 | 11.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 68.08 | 51.88 | 20.75 | 101.51 | 31.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 172.68 | 126.78 | 45.89 | 254.22 | 85.65 | 0.00 | 0.00 | 744.00 |
February | 136.39 | 84.40 | 51.99 | 184.10 | 78.98 | 0.00 | 0.00 | 672.00 |
March | 108.74 | 52.96 | 55.78 | 136.13 | 84.30 | 0.00 | 0.00 | 744.00 |
April | 90.91 | 35.11 | 55.79 | 109.10 | 63.57 | 0.00 | 0.00 | 720.00 |
May | 64.05 | 7.73 | 56.32 | 67.04 | 57.25 | 0.00 | 0.00 | 744.00 |
June | 56.19 | 3.27 | 52.92 | 65.45 | 39.53 | 0.00 | 0.00 | 720.00 |
July | 59.25 | 6.30 | 52.95 | 77.59 | 31.18 | 0.00 | 0.00 | 744.00 |
August | 76.10 | 23.62 | 52.48 | 104.27 | 32.05 | 0.00 | 0.00 | 744.00 |
September | 104.53 | 51.91 | 52.62 | 150.70 | 40.36 | 0.00 | 0.00 | 720.00 |
October | 136.93 | 91.96 | 44.97 | 215.55 | 45.49 | 0.00 | 0.00 | 744.00 |
November | 166.35 | 117.88 | 48.48 | 244.01 | 75.02 | 0.00 | 0.00 | 720.00 |
December | 184.78 | 140.82 | 43.96 | 275.53 | 84.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 112.98 | 61.82 | 51.16 | 156.91 | 59.75 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 56.19 | 3.27 | 43.96 | 65.45 | 31.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 184.78 | 140.82 | 56.32 | 275.53 | 85.65 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.46 | 100.19 | 36.27 | 194.26 | 73.09 | 0.00 | 0.00 | 744.00 |
February | 107.78 | 66.70 | 41.08 | 138.57 | 67.54 | 0.00 | 0.00 | 672.00 |
March | 85.94 | 41.86 | 44.08 | 101.53 | 72.54 | 0.00 | 0.00 | 744.00 |
April | 71.84 | 27.75 | 44.09 | 78.30 | 56.88 | 0.00 | 0.00 | 720.00 |
May | 50.62 | 6.11 | 44.51 | 44.73 | 51.40 | 0.00 | 0.00 | 744.00 |
June | 44.40 | 2.58 | 41.82 | 42.51 | 36.94 | 0.00 | 0.00 | 720.00 |
July | 46.82 | 4.98 | 41.84 | 51.36 | 30.39 | 0.00 | 0.00 | 744.00 |
August | 60.14 | 18.67 | 41.48 | 73.05 | 31.38 | 0.00 | 0.00 | 744.00 |
September | 82.60 | 41.02 | 41.58 | 110.73 | 37.90 | 0.00 | 0.00 | 720.00 |
October | 108.21 | 72.67 | 35.54 | 162.62 | 41.45 | 0.00 | 0.00 | 744.00 |
November | 131.46 | 93.16 | 38.31 | 185.20 | 64.94 | 0.00 | 0.00 | 720.00 |
December | 146.03 | 111.29 | 34.74 | 210.63 | 72.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 89.28 | 48.85 | 40.43 | 116.07 | 53.00 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 44.40 | 2.58 | 34.74 | 42.51 | 30.39 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 146.03 | 111.29 | 44.51 | 210.63 | 73.09 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.86 | 49.86 | 49.01 | 107.76 | 147.78 | 0.00 | 0.00 | 744.00 |
February | 118.07 | 54.57 | 63.50 | 126.96 | 131.54 | 0.00 | 0.00 | 672.00 |
March | 135.05 | 59.68 | 75.37 | 150.25 | 134.85 | 0.00 | 0.00 | 744.00 |
April | 186.12 | 96.76 | 89.36 | 239.71 | 101.95 | 0.00 | 0.00 | 720.00 |
May | 182.82 | 84.32 | 98.51 | 229.71 | 90.59 | 0.00 | 0.00 | 744.00 |
June | 193.62 | 96.68 | 96.95 | 261.75 | 64.26 | 0.00 | 0.00 | 720.00 |
July | 205.02 | 109.59 | 95.43 | 295.95 | 53.00 | 0.00 | 0.00 | 744.00 |
August | 192.39 | 104.18 | 88.22 | 280.06 | 55.93 | 0.00 | 0.00 | 744.00 |
September | 164.89 | 88.21 | 76.69 | 229.67 | 68.34 | 0.00 | 0.00 | 720.00 |
October | 126.65 | 69.39 | 57.26 | 181.15 | 79.77 | 0.00 | 0.00 | 744.00 |
November | 113.97 | 59.65 | 54.31 | 131.20 | 128.86 | 0.00 | 0.00 | 720.00 |
December | 100.25 | 53.60 | 46.65 | 111.84 | 147.14 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.61 | 77.30 | 74.30 | 195.84 | 100.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 98.86 | 49.86 | 46.65 | 107.76 | 53.00 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 205.02 | 109.59 | 98.51 | 295.95 | 147.78 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.62 | 0.00 | 20.62 | 12.56 | 78.90 | 0.00 | 0.00 | 744.00 |
February | 25.89 | 0.00 | 25.89 | 13.77 | 71.34 | 0.00 | 0.00 | 672.00 |
March | 31.72 | 0.00 | 31.72 | 19.91 | 74.09 | 0.00 | 0.00 | 744.00 |
April | 36.74 | 0.29 | 36.45 | 27.51 | 56.98 | 0.00 | 0.00 | 720.00 |
May | 44.19 | 2.30 | 41.89 | 32.65 | 48.69 | 0.00 | 0.00 | 744.00 |
June | 46.84 | 4.62 | 42.22 | 40.71 | 36.43 | 0.00 | 0.00 | 720.00 |
July | 44.37 | 3.75 | 40.61 | 43.50 | 32.86 | 0.00 | 0.00 | 744.00 |
August | 36.89 | 0.82 | 36.08 | 38.19 | 35.29 | 0.00 | 0.00 | 744.00 |
September | 31.15 | 0.01 | 31.14 | 31.49 | 40.72 | 0.00 | 0.00 | 720.00 |
October | 24.70 | 0.00 | 24.70 | 29.58 | 45.36 | 0.00 | 0.00 | 744.00 |
November | 22.37 | 0.00 | 22.37 | 14.47 | 69.84 | 0.00 | 0.00 | 720.00 |
December | 19.20 | 0.00 | 19.20 | 11.61 | 78.71 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 32.08 | 0.99 | 31.10 | 26.41 | 55.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.20 | 0.00 | 19.20 | 11.61 | 32.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 46.84 | 4.62 | 42.22 | 43.50 | 78.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.86 | 49.86 | 49.01 | 114.70 | 143.45 | 0.00 | 0.00 | 744.00 |
February | 118.07 | 54.57 | 63.50 | 131.94 | 128.57 | 0.00 | 0.00 | 672.00 |
March | 135.05 | 59.68 | 75.37 | 153.12 | 133.28 | 0.00 | 0.00 | 744.00 |
April | 186.12 | 96.76 | 89.36 | 238.33 | 103.10 | 0.00 | 0.00 | 720.00 |
May | 182.82 | 84.32 | 98.51 | 226.00 | 92.57 | 0.00 | 0.00 | 744.00 |
June | 193.62 | 96.68 | 96.95 | 254.15 | 69.93 | 0.00 | 0.00 | 720.00 |
July | 205.02 | 109.59 | 95.43 | 285.69 | 61.75 | 0.00 | 0.00 | 744.00 |
August | 192.39 | 104.18 | 88.22 | 272.61 | 64.35 | 0.00 | 0.00 | 744.00 |
September | 164.89 | 88.21 | 76.69 | 228.05 | 72.26 | 0.00 | 0.00 | 720.00 |
October | 126.65 | 69.39 | 57.26 | 182.78 | 82.26 | 0.00 | 0.00 | 744.00 |
November | 113.97 | 59.65 | 54.31 | 137.12 | 125.64 | 0.00 | 0.00 | 720.00 |
December | 100.25 | 53.60 | 46.65 | 118.95 | 142.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 151.61 | 77.30 | 74.30 | 195.60 | 101.52 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 98.86 | 49.86 | 46.65 | 114.70 | 61.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 205.02 | 109.59 | 98.51 | 285.69 | 143.45 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.14 | 146.94 | 53.19 | 279.92 | 111.58 | 0.00 | 0.00 | 744.00 |
February | 158.08 | 97.82 | 60.25 | 199.68 | 102.33 | 0.00 | 0.00 | 672.00 |
March | 126.03 | 61.38 | 64.65 | 146.67 | 108.35 | 0.00 | 0.00 | 744.00 |
April | 105.36 | 40.69 | 64.67 | 115.46 | 82.26 | 0.00 | 0.00 | 720.00 |
May | 74.23 | 8.96 | 65.27 | 68.01 | 73.26 | 0.00 | 0.00 | 744.00 |
June | 65.12 | 3.79 | 61.33 | 65.91 | 51.37 | 0.00 | 0.00 | 720.00 |
July | 68.67 | 7.30 | 61.36 | 79.38 | 41.47 | 0.00 | 0.00 | 744.00 |
August | 88.20 | 27.38 | 60.83 | 109.91 | 43.56 | 0.00 | 0.00 | 744.00 |
September | 121.15 | 60.17 | 60.98 | 162.94 | 54.34 | 0.00 | 0.00 | 720.00 |
October | 158.70 | 106.58 | 52.12 | 237.09 | 61.44 | 0.00 | 0.00 | 744.00 |
November | 192.80 | 136.62 | 56.18 | 267.67 | 98.51 | 0.00 | 0.00 | 720.00 |
December | 214.17 | 163.21 | 50.95 | 303.79 | 110.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 130.94 | 71.65 | 59.29 | 169.64 | 78.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 65.12 | 3.79 | 50.95 | 65.91 | 41.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 214.17 | 163.21 | 65.27 | 303.79 | 111.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.35 | 0.00 | 144.35 | 68.01 | 635.10 | 0.00 | 0.00 | 744.00 |
February | 181.19 | 0.00 | 181.19 | 74.79 | 592.55 | 0.00 | 0.00 | 672.00 |
March | 222.06 | 0.00 | 222.05 | 118.57 | 599.06 | 0.00 | 0.00 | 744.00 |
April | 257.16 | 2.05 | 255.11 | 186.51 | 448.68 | 0.00 | 0.00 | 720.00 |
May | 309.33 | 16.08 | 293.25 | 224.92 | 389.80 | 0.00 | 0.00 | 744.00 |
June | 327.87 | 32.32 | 295.55 | 294.74 | 282.94 | 0.00 | 0.00 | 720.00 |
July | 310.57 | 26.28 | 284.29 | 326.27 | 240.80 | 0.00 | 0.00 | 744.00 |
August | 258.25 | 5.71 | 252.55 | 282.63 | 261.57 | 0.00 | 0.00 | 744.00 |
September | 218.02 | 0.04 | 217.98 | 220.67 | 319.26 | 0.00 | 0.00 | 720.00 |
October | 172.93 | 0.00 | 172.93 | 197.75 | 366.71 | 0.00 | 0.00 | 744.00 |
November | 156.57 | 0.00 | 156.57 | 82.02 | 567.13 | 0.00 | 0.00 | 720.00 |
December | 134.37 | 0.00 | 134.37 | 61.63 | 636.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 224.57 | 6.91 | 217.66 | 178.86 | 444.23 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 134.37 | 0.00 | 134.37 | 61.63 | 240.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 327.87 | 32.32 | 295.55 | 326.27 | 636.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 144.35 | 0.00 | 144.35 | 59.45 | 661.68 | 0.00 | 0.00 | 744.00 |
February | 181.19 | 0.00 | 181.19 | 65.05 | 619.00 | 0.00 | 0.00 | 672.00 |
March | 222.06 | 0.00 | 222.05 | 106.45 | 623.52 | 0.00 | 0.00 | 744.00 |
April | 257.16 | 2.05 | 255.11 | 171.11 | 467.80 | 0.00 | 0.00 | 720.00 |
May | 309.33 | 16.08 | 293.25 | 206.31 | 406.30 | 0.00 | 0.00 | 744.00 |
June | 327.87 | 32.32 | 295.55 | 274.36 | 296.46 | 0.00 | 0.00 | 720.00 |
July | 310.57 | 26.28 | 284.29 | 306.48 | 253.27 | 0.00 | 0.00 | 744.00 |
August | 258.25 | 5.71 | 252.55 | 265.32 | 276.14 | 0.00 | 0.00 | 744.00 |
September | 218.02 | 0.04 | 217.98 | 205.71 | 337.09 | 0.00 | 0.00 | 720.00 |
October | 172.93 | 0.00 | 172.93 | 184.86 | 386.11 | 0.00 | 0.00 | 744.00 |
November | 156.57 | 0.00 | 156.57 | 72.19 | 591.65 | 0.00 | 0.00 | 720.00 |
December | 134.37 | 0.00 | 134.37 | 53.62 | 663.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 224.57 | 6.91 | 217.66 | 164.88 | 464.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 134.37 | 0.00 | 134.37 | 53.62 | 253.27 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 327.87 | 32.32 | 295.55 | 306.48 | 663.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 20.62 | 0.00 | 20.62 | 14.52 | 81.19 | 0.00 | 0.00 | 744.00 |
February | 25.89 | 0.00 | 25.89 | 15.54 | 77.47 | 0.00 | 0.00 | 672.00 |
March | 31.72 | 0.00 | 31.72 | 23.25 | 78.97 | 0.00 | 0.00 | 744.00 |
April | 36.74 | 0.29 | 36.45 | 35.66 | 59.56 | 0.00 | 0.00 | 720.00 |
May | 44.19 | 2.30 | 41.89 | 43.18 | 52.94 | 0.00 | 0.00 | 744.00 |
June | 46.84 | 4.62 | 42.22 | 55.16 | 38.22 | 0.00 | 0.00 | 720.00 |
July | 44.37 | 3.75 | 40.61 | 60.75 | 32.02 | 0.00 | 0.00 | 744.00 |
August | 36.89 | 0.82 | 36.08 | 52.83 | 33.93 | 0.00 | 0.00 | 744.00 |
September | 31.15 | 0.01 | 31.14 | 41.47 | 39.74 | 0.00 | 0.00 | 720.00 |
October | 24.70 | 0.00 | 24.70 | 36.81 | 45.84 | 0.00 | 0.00 | 744.00 |
November | 22.37 | 0.00 | 22.37 | 17.13 | 72.54 | 0.00 | 0.00 | 720.00 |
December | 19.20 | 0.00 | 19.20 | 13.40 | 81.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 32.08 | 0.99 | 31.10 | 34.26 | 57.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 19.20 | 0.00 | 19.20 | 13.40 | 32.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 46.84 | 4.62 | 42.22 | 60.75 | 81.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 207.48 | 110.86 | 96.62 | 246.84 | 285.06 | 0.00 | 0.00 | 744.00 |
February | 218.94 | 100.18 | 118.76 | 238.74 | 275.50 | 0.00 | 0.00 | 672.00 |
March | 267.23 | 119.37 | 147.86 | 314.17 | 279.43 | 0.00 | 0.00 | 744.00 |
April | 340.62 | 170.92 | 169.70 | 465.34 | 216.84 | 0.00 | 0.00 | 720.00 |
May | 320.81 | 133.69 | 187.12 | 426.40 | 199.72 | 0.00 | 0.00 | 744.00 |
June | 319.18 | 138.56 | 180.62 | 461.86 | 149.68 | 0.00 | 0.00 | 720.00 |
July | 361.45 | 179.56 | 181.89 | 567.58 | 125.49 | 0.00 | 0.00 | 744.00 |
August | 357.26 | 189.87 | 167.38 | 567.69 | 128.80 | 0.00 | 0.00 | 744.00 |
September | 260.84 | 119.98 | 140.86 | 392.74 | 148.29 | 0.00 | 0.00 | 720.00 |
October | 229.87 | 117.99 | 111.89 | 357.70 | 165.69 | 0.00 | 0.00 | 744.00 |
November | 209.06 | 105.84 | 103.22 | 251.79 | 257.31 | 0.00 | 0.00 | 720.00 |
December | 200.98 | 112.01 | 88.96 | 236.33 | 284.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 274.85 | 133.50 | 141.35 | 378.23 | 209.36 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 200.98 | 100.18 | 88.96 | 236.33 | 125.49 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 361.45 | 189.87 | 187.12 | 567.69 | 285.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.46 | 100.19 | 36.27 | 203.23 | 75.09 | 0.00 | 0.00 | 744.00 |
February | 107.78 | 66.70 | 41.08 | 145.46 | 73.96 | 0.00 | 0.00 | 672.00 |
March | 85.94 | 41.86 | 44.08 | 107.50 | 77.85 | 0.00 | 0.00 | 744.00 |
April | 71.84 | 27.75 | 44.09 | 86.37 | 61.11 | 0.00 | 0.00 | 720.00 |
May | 50.62 | 6.11 | 44.51 | 52.50 | 56.51 | 0.00 | 0.00 | 744.00 |
June | 44.40 | 2.58 | 41.82 | 52.53 | 41.45 | 0.00 | 0.00 | 720.00 |
July | 46.82 | 4.98 | 41.84 | 63.20 | 34.09 | 0.00 | 0.00 | 744.00 |
August | 60.14 | 18.67 | 41.48 | 84.33 | 35.17 | 0.00 | 0.00 | 744.00 |
September | 82.60 | 41.02 | 41.58 | 121.02 | 40.30 | 0.00 | 0.00 | 720.00 |
October | 108.21 | 72.67 | 35.54 | 172.60 | 44.82 | 0.00 | 0.00 | 744.00 |
November | 131.46 | 93.16 | 38.31 | 194.25 | 68.01 | 0.00 | 0.00 | 720.00 |
December | 146.03 | 111.29 | 34.74 | 219.72 | 74.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 89.28 | 48.85 | 40.43 | 125.19 | 56.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 44.40 | 2.58 | 34.74 | 52.50 | 34.09 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 146.03 | 111.29 | 44.51 | 219.72 | 77.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 26.12 | 0.00 | 26.12 | 15.05 | 98.38 | 0.00 | 0.00 | 744.00 |
February | 32.78 | 0.00 | 32.78 | 17.59 | 88.22 | 0.00 | 0.00 | 672.00 |
March | 40.18 | 0.00 | 40.18 | 26.71 | 90.33 | 0.00 | 0.00 | 744.00 |
April | 46.53 | 0.37 | 46.16 | 40.72 | 65.77 | 0.00 | 0.00 | 720.00 |
May | 55.97 | 2.91 | 53.06 | 50.00 | 56.36 | 0.00 | 0.00 | 744.00 |
June | 59.32 | 5.85 | 53.47 | 63.34 | 39.53 | 0.00 | 0.00 | 720.00 |
July | 56.19 | 4.75 | 51.44 | 68.14 | 33.20 | 0.00 | 0.00 | 744.00 |
August | 46.72 | 1.03 | 45.69 | 58.36 | 35.57 | 0.00 | 0.00 | 744.00 |
September | 39.45 | 0.01 | 39.44 | 45.81 | 44.39 | 0.00 | 0.00 | 720.00 |
October | 31.29 | 0.00 | 31.29 | 40.02 | 52.42 | 0.00 | 0.00 | 744.00 |
November | 28.33 | 0.00 | 28.33 | 18.31 | 85.63 | 0.00 | 0.00 | 720.00 |
December | 24.31 | 0.00 | 24.31 | 13.64 | 98.09 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 40.63 | 1.25 | 39.38 | 38.27 | 65.55 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 24.31 | 0.00 | 24.31 | 13.64 | 33.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 59.32 | 5.85 | 53.47 | 68.14 | 98.38 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 23.37 | 0.00 | 23.37 | 13.46 | 88.02 | 0.00 | 0.00 | 744.00 |
February | 29.33 | 0.00 | 29.33 | 15.74 | 78.93 | 0.00 | 0.00 | 672.00 |
March | 35.95 | 0.00 | 35.95 | 23.90 | 80.81 | 0.00 | 0.00 | 744.00 |
April | 41.63 | 0.33 | 41.30 | 36.43 | 58.85 | 0.00 | 0.00 | 720.00 |
May | 50.07 | 2.60 | 47.47 | 44.73 | 50.42 | 0.00 | 0.00 | 744.00 |
June | 53.07 | 5.23 | 47.84 | 56.67 | 35.36 | 0.00 | 0.00 | 720.00 |
July | 50.27 | 4.25 | 46.02 | 60.97 | 29.71 | 0.00 | 0.00 | 744.00 |
August | 41.80 | 0.92 | 40.88 | 52.21 | 31.83 | 0.00 | 0.00 | 744.00 |
September | 35.29 | 0.01 | 35.29 | 40.99 | 39.71 | 0.00 | 0.00 | 720.00 |
October | 27.99 | 0.00 | 27.99 | 35.81 | 46.90 | 0.00 | 0.00 | 744.00 |
November | 25.35 | 0.00 | 25.35 | 16.38 | 76.61 | 0.00 | 0.00 | 720.00 |
December | 21.75 | 0.00 | 21.75 | 12.21 | 87.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 36.35 | 1.12 | 35.23 | 34.24 | 58.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.75 | 0.00 | 21.75 | 12.21 | 29.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 53.07 | 5.23 | 47.84 | 60.97 | 88.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 509.46 | 374.05 | 135.40 | 736.05 | 261.57 | 0.00 | 0.00 | 744.00 |
February | 402.39 | 249.01 | 153.38 | 528.73 | 242.90 | 0.00 | 0.00 | 672.00 |
March | 320.83 | 156.26 | 164.57 | 388.74 | 259.37 | 0.00 | 0.00 | 744.00 |
April | 268.20 | 103.59 | 164.61 | 307.59 | 198.24 | 0.00 | 0.00 | 720.00 |
May | 188.96 | 22.81 | 166.16 | 184.17 | 178.96 | 0.00 | 0.00 | 744.00 |
June | 165.77 | 9.64 | 156.12 | 177.27 | 127.74 | 0.00 | 0.00 | 720.00 |
July | 174.79 | 18.59 | 156.20 | 209.83 | 105.08 | 0.00 | 0.00 | 744.00 |
August | 224.53 | 69.69 | 154.84 | 288.15 | 109.05 | 0.00 | 0.00 | 744.00 |
September | 308.39 | 153.16 | 155.23 | 427.78 | 131.28 | 0.00 | 0.00 | 720.00 |
October | 403.98 | 271.32 | 132.66 | 617.40 | 147.75 | 0.00 | 0.00 | 744.00 |
November | 490.79 | 347.78 | 143.02 | 704.11 | 230.77 | 0.00 | 0.00 | 720.00 |
December | 545.17 | 415.47 | 129.70 | 797.64 | 258.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 333.32 | 182.39 | 150.93 | 447.09 | 187.33 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 165.77 | 9.64 | 129.70 | 177.27 | 105.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 545.17 | 415.47 | 166.16 | 797.64 | 261.57 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185087E+10 | 0.135894E+10 | 0.491925E+09 | 0.262765E+10 | 0.949423E+09 |
February | 0.132042E+10 | 0.817125E+09 | 0.503297E+09 | 0.172656E+10 | 0.780498E+09 |
March | 0.116557E+10 | 0.567687E+09 | 0.597878E+09 | 0.141944E+10 | 0.897931E+09 |
April | 0.942948E+09 | 0.364206E+09 | 0.578742E+09 | 0.108463E+10 | 0.673180E+09 |
May | 0.686508E+09 | 82855603.57 | 0.603653E+09 | 0.685938E+09 | 0.614821E+09 |
June | 0.582802E+09 | 33895534.00 | 0.548907E+09 | 0.636561E+09 | 0.427839E+09 |
July | 0.635032E+09 | 67536201.96 | 0.567496E+09 | 0.766694E+09 | 0.367528E+09 |
August | 0.815705E+09 | 0.253170E+09 | 0.562535E+09 | 0.103919E+10 | 0.389407E+09 |
September | 0.108424E+10 | 0.538468E+09 | 0.545767E+09 | 0.148348E+10 | 0.468128E+09 |
October | 0.146767E+10 | 0.985700E+09 | 0.481969E+09 | 0.220035E+10 | 0.559578E+09 |
November | 0.172555E+10 | 0.122273E+10 | 0.502820E+09 | 0.243679E+10 | 0.823463E+09 |
December | 0.198061E+10 | 0.150940E+10 | 0.471217E+09 | 0.284590E+10 | 0.952617E+09 |
Annual Sum or Average | 0.142579E+11 | 0.780170E+10 | 0.645621E+10 | 0.189532E+11 | 0.790441E+10 |
Minimum of Months | 0.582802E+09 | 33895534.00 | 0.471217E+09 | 0.636561E+09 | 0.367528E+09 |
Maximum of Months | 0.198061E+10 | 0.150940E+10 | 0.603653E+09 | 0.284590E+10 | 0.952617E+09 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.521191E+10 | 0.382669E+10 | 0.138523E+10 | 0.730081E+10 | 0.291014E+10 |
February | 0.371822E+10 | 0.230097E+10 | 0.141725E+10 | 0.477142E+10 | 0.243389E+10 |
March | 0.328216E+10 | 0.159857E+10 | 0.168359E+10 | 0.391099E+10 | 0.276731E+10 |
April | 0.265528E+10 | 0.102558E+10 | 0.162970E+10 | 0.297090E+10 | 0.212740E+10 |
May | 0.193316E+10 | 0.233316E+09 | 0.169985E+10 | 0.184731E+10 | 0.194428E+10 |
June | 0.164113E+10 | 95447588.87 | 0.154569E+10 | 0.170552E+10 | 0.139076E+10 |
July | 0.178821E+10 | 0.190177E+09 | 0.159803E+10 | 0.206773E+10 | 0.120716E+10 |
August | 0.229697E+10 | 0.712911E+09 | 0.158406E+10 | 0.284341E+10 | 0.128382E+10 |
September | 0.305313E+10 | 0.151629E+10 | 0.153684E+10 | 0.410210E+10 | 0.152347E+10 |
October | 0.413286E+10 | 0.277567E+10 | 0.135719E+10 | 0.611269E+10 | 0.178965E+10 |
November | 0.485902E+10 | 0.344311E+10 | 0.141591E+10 | 0.675561E+10 | 0.256816E+10 |
December | 0.557728E+10 | 0.425036E+10 | 0.132692E+10 | 0.790719E+10 | 0.292758E+10 |
Annual Sum or Average | 0.401493E+11 | 0.219691E+11 | 0.181803E+11 | 0.522957E+11 | 0.248736E+11 |
Minimum of Months | 0.164113E+10 | 95447588.87 | 0.132692E+10 | 0.170552E+10 | 0.120716E+10 |
Maximum of Months | 0.557728E+10 | 0.425036E+10 | 0.169985E+10 | 0.790719E+10 | 0.292758E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.677057E+10 | 0.497108E+10 | 0.179949E+10 | 0.973916E+10 | 0.382583E+10 |
February | 0.483018E+10 | 0.298909E+10 | 0.184109E+10 | 0.635198E+10 | 0.325250E+10 |
March | 0.426371E+10 | 0.207663E+10 | 0.218707E+10 | 0.518749E+10 | 0.374174E+10 |
April | 0.344936E+10 | 0.133229E+10 | 0.211707E+10 | 0.393954E+10 | 0.287221E+10 |
May | 0.251129E+10 | 0.303091E+09 | 0.220820E+10 | 0.241932E+10 | 0.266540E+10 |
June | 0.213192E+10 | 0.123992E+09 | 0.200793E+10 | 0.224195E+10 | 0.190289E+10 |
July | 0.232298E+10 | 0.247051E+09 | 0.207593E+10 | 0.274366E+10 | 0.163733E+10 |
August | 0.298390E+10 | 0.926112E+09 | 0.205779E+10 | 0.379625E+10 | 0.170713E+10 |
September | 0.396620E+10 | 0.196975E+10 | 0.199645E+10 | 0.548064E+10 | 0.200685E+10 |
October | 0.536882E+10 | 0.360575E+10 | 0.176307E+10 | 0.817006E+10 | 0.232094E+10 |
November | 0.631215E+10 | 0.447280E+10 | 0.183935E+10 | 0.900559E+10 | 0.337891E+10 |
December | 0.724520E+10 | 0.552146E+10 | 0.172374E+10 | 0.105487E+11 | 0.384234E+10 |
Annual Sum or Average | 0.521563E+11 | 0.285391E+11 | 0.236172E+11 | 0.696243E+11 | 0.331541E+11 |
Minimum of Months | 0.213192E+10 | 0.123992E+09 | 0.172374E+10 | 0.224195E+10 | 0.163733E+10 |
Maximum of Months | 0.724520E+10 | 0.552146E+10 | 0.220820E+10 | 0.105487E+11 | 0.384234E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365202E+09 | 0.268138E+09 | 97063741.13 | 0.523950E+09 | 0.196126E+09 |
February | 0.260538E+09 | 0.161230E+09 | 99307626.30 | 0.339179E+09 | 0.163538E+09 |
March | 0.229983E+09 | 0.112013E+09 | 0.117970E+09 | 0.275790E+09 | 0.193687E+09 |
April | 0.186057E+09 | 71862951.28 | 0.114194E+09 | 0.207553E+09 | 0.146320E+09 |
May | 0.135458E+09 | 16348586.95 | 0.119109E+09 | 0.124494E+09 | 0.136240E+09 |
June | 0.114995E+09 | 6688070.10 | 0.108307E+09 | 0.115018E+09 | 94203195.48 |
July | 0.125301E+09 | 13325851.52 | 0.111975E+09 | 0.142489E+09 | 79682763.92 |
August | 0.160950E+09 | 49954094.11 | 0.110996E+09 | 0.200434E+09 | 82300999.78 |
September | 0.213935E+09 | 0.106247E+09 | 0.107688E+09 | 0.291803E+09 | 97023713.86 |
October | 0.289592E+09 | 0.194493E+09 | 95099285.37 | 0.440460E+09 | 0.110206E+09 |
November | 0.340475E+09 | 0.241261E+09 | 99213597.08 | 0.484591E+09 | 0.168294E+09 |
December | 0.390803E+09 | 0.297825E+09 | 92977895.08 | 0.568332E+09 | 0.194668E+09 |
Annual Sum or Average | 0.281329E+10 | 0.153939E+10 | 0.127390E+10 | 0.371409E+10 | 0.166229E+10 |
Minimum of Months | 0.114995E+09 | 6688070.10 | 92977895.08 | 0.115018E+09 | 79682763.92 |
Maximum of Months | 0.390803E+09 | 0.297825E+09 | 0.119109E+09 | 0.568332E+09 | 0.196126E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264577E+09 | 0.133423E+09 | 0.131154E+09 | 0.293376E+09 | 0.397838E+09 |
February | 0.285409E+09 | 0.131915E+09 | 0.153493E+09 | 0.312781E+09 | 0.319454E+09 |
March | 0.361422E+09 | 0.159729E+09 | 0.201693E+09 | 0.410664E+09 | 0.361279E+09 |
April | 0.482027E+09 | 0.250603E+09 | 0.231424E+09 | 0.633965E+09 | 0.263113E+09 |
May | 0.489272E+09 | 0.225646E+09 | 0.263626E+09 | 0.629425E+09 | 0.241086E+09 |
June | 0.501458E+09 | 0.250379E+09 | 0.251079E+09 | 0.693645E+09 | 0.164575E+09 |
July | 0.548681E+09 | 0.293289E+09 | 0.255392E+09 | 0.807819E+09 | 0.139608E+09 |
August | 0.514880E+09 | 0.278798E+09 | 0.236082E+09 | 0.764154E+09 | 0.147144E+09 |
September | 0.427052E+09 | 0.228445E+09 | 0.198607E+09 | 0.606605E+09 | 0.175381E+09 |
October | 0.338943E+09 | 0.185711E+09 | 0.153233E+09 | 0.493134E+09 | 0.212562E+09 |
November | 0.295162E+09 | 0.154495E+09 | 0.140668E+09 | 0.345910E+09 | 0.334972E+09 |
December | 0.268281E+09 | 0.143444E+09 | 0.124837E+09 | 0.303729E+09 | 0.396528E+09 |
Annual Sum or Average | 0.477717E+10 | 0.243588E+10 | 0.234129E+10 | 0.629521E+10 | 0.315354E+10 |
Minimum of Months | 0.264577E+09 | 0.131915E+09 | 0.124837E+09 | 0.293376E+09 | 0.139608E+09 |
Maximum of Months | 0.548681E+09 | 0.293289E+09 | 0.263626E+09 | 0.807819E+09 | 0.397838E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55187410.10 | 0.00 | 55187410.10 | 34048693.22 | 0.212813E+09 |
February | 62570938.96 | 0.00 | 62570938.96 | 34106882.72 | 0.173343E+09 |
March | 84898795.36 | 753.87 | 84898041.50 | 55446985.32 | 0.198211E+09 |
April | 95148727.15 | 759942.51 | 94388784.64 | 75648840.00 | 0.145239E+09 |
May | 0.118266E+09 | 6148054.32 | 0.112118E+09 | 93335066.62 | 0.128157E+09 |
June | 0.121311E+09 | 11957604.86 | 0.109354E+09 | 0.113259E+09 | 90256253.49 |
July | 0.118739E+09 | 10047152.59 | 0.108692E+09 | 0.125134E+09 | 81846809.85 |
August | 98737814.75 | 2181324.43 | 96556490.32 | 0.108974E+09 | 87760675.31 |
September | 80667879.41 | 15675.90 | 80652203.51 | 86067657.84 | 0.101792E+09 |
October | 66114501.28 | 0.00 | 66114501.28 | 81945266.06 | 0.119041E+09 |
November | 57930922.12 | 0.00 | 57930922.12 | 38331600.33 | 0.181551E+09 |
December | 51374769.97 | 0.00 | 51374769.97 | 31170708.88 | 0.212614E+09 |
Annual Sum or Average | 0.101095E+10 | 31110508.49 | 0.979838E+09 | 0.877469E+09 | 0.173262E+10 |
Minimum of Months | 51374769.97 | 0.00 | 51374769.97 | 31170708.88 | 81846809.85 |
Maximum of Months | 0.121311E+09 | 11957604.86 | 0.112118E+09 | 0.125134E+09 | 0.212813E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264577E+09 | 0.133423E+09 | 0.131154E+09 | 0.310479E+09 | 0.387092E+09 |
February | 0.285409E+09 | 0.131915E+09 | 0.153493E+09 | 0.324015E+09 | 0.312790E+09 |
March | 0.361422E+09 | 0.159729E+09 | 0.201693E+09 | 0.418368E+09 | 0.356992E+09 |
April | 0.482027E+09 | 0.250603E+09 | 0.231424E+09 | 0.632347E+09 | 0.264278E+09 |
May | 0.489272E+09 | 0.225646E+09 | 0.263626E+09 | 0.621949E+09 | 0.244482E+09 |
June | 0.501458E+09 | 0.250379E+09 | 0.251079E+09 | 0.678586E+09 | 0.174267E+09 |
July | 0.548681E+09 | 0.293289E+09 | 0.255392E+09 | 0.786959E+09 | 0.155036E+09 |
August | 0.514880E+09 | 0.278798E+09 | 0.236082E+09 | 0.749679E+09 | 0.161916E+09 |
September | 0.427052E+09 | 0.228445E+09 | 0.198607E+09 | 0.605015E+09 | 0.181817E+09 |
October | 0.338943E+09 | 0.185711E+09 | 0.153233E+09 | 0.498626E+09 | 0.216394E+09 |
November | 0.295162E+09 | 0.154495E+09 | 0.140668E+09 | 0.360324E+09 | 0.327047E+09 |
December | 0.268281E+09 | 0.143444E+09 | 0.124837E+09 | 0.321245E+09 | 0.385265E+09 |
Annual Sum or Average | 0.477717E+10 | 0.243588E+10 | 0.234129E+10 | 0.630759E+10 | 0.316738E+10 |
Minimum of Months | 0.264577E+09 | 0.131915E+09 | 0.124837E+09 | 0.310479E+09 | 0.155036E+09 |
Maximum of Months | 0.548681E+09 | 0.293289E+09 | 0.263626E+09 | 0.786959E+09 | 0.387092E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292103E+09 | 0.214468E+09 | 77635553.28 | 0.379523E+09 | 0.235124E+09 |
February | 0.208389E+09 | 0.128959E+09 | 79430304.49 | 0.237392E+09 | 0.204072E+09 |
March | 0.183949E+09 | 89592320.13 | 94357165.29 | 0.185550E+09 | 0.233738E+09 |
April | 0.148816E+09 | 57478930.01 | 91337075.93 | 0.132812E+09 | 0.186311E+09 |
May | 0.108345E+09 | 13076269.05 | 95268456.07 | 63646922.28 | 0.176944E+09 |
June | 91977834.87 | 5349392.23 | 86628442.64 | 55377538.77 | 0.135514E+09 |
July | 0.100221E+09 | 10658561.51 | 89562197.17 | 75473193.33 | 0.121830E+09 |
August | 0.128735E+09 | 39955329.25 | 88779244.96 | 0.122776E+09 | 0.127628E+09 |
September | 0.171114E+09 | 84981032.64 | 86132926.04 | 0.198659E+09 | 0.143230E+09 |
October | 0.231627E+09 | 0.155563E+09 | 76064301.16 | 0.313603E+09 | 0.158507E+09 |
November | 0.272326E+09 | 0.192970E+09 | 79355096.08 | 0.349039E+09 | 0.208897E+09 |
December | 0.312580E+09 | 0.238213E+09 | 74367526.37 | 0.413940E+09 | 0.234146E+09 |
Annual Sum or Average | 0.225018E+10 | 0.123126E+10 | 0.101892E+10 | 0.252779E+10 | 0.216594E+10 |
Minimum of Months | 91977834.87 | 5349392.23 | 74367526.37 | 55377538.77 | 0.121830E+09 |
Maximum of Months | 0.312580E+09 | 0.238213E+09 | 95268456.07 | 0.413940E+09 | 0.235124E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 44155780.40 | 0.00 | 44155780.40 | 26990771.46 | 0.174284E+09 |
February | 50063386.48 | 0.00 | 50063386.48 | 27474127.67 | 0.141525E+09 |
March | 67928039.34 | 603.17 | 67927436.17 | 45343103.99 | 0.161100E+09 |
April | 76129071.72 | 608034.59 | 75521037.12 | 66299590.36 | 0.113421E+09 |
May | 94625527.60 | 4919095.43 | 89706432.17 | 81714538.30 | 0.101272E+09 |
June | 97061928.37 | 9567351.92 | 87494576.45 | 99517415.48 | 69977307.43 |
July | 95003827.50 | 8038787.52 | 86965039.98 | 0.110913E+09 | 61844686.81 |
August | 79000722.41 | 1745290.87 | 77255431.54 | 96281718.87 | 65717033.10 |
September | 64542857.91 | 12542.38 | 64530315.53 | 74677750.35 | 77722045.27 |
October | 52898612.11 | 0.00 | 52898612.11 | 69014137.23 | 93958967.82 |
November | 46350880.95 | 0.00 | 46350880.95 | 31558320.88 | 0.146290E+09 |
December | 41105263.99 | 0.00 | 41105263.99 | 24959751.77 | 0.173573E+09 |
Annual Sum or Average | 0.808866E+09 | 24891705.89 | 0.783974E+09 | 0.754744E+09 | 0.138068E+10 |
Minimum of Months | 41105263.99 | 0.00 | 41105263.99 | 24959751.77 | 61844686.81 |
Maximum of Months | 97061928.37 | 9567351.92 | 89706432.17 | 0.110913E+09 | 0.174284E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277649E+09 | 0.148349E+09 | 0.129300E+09 | 0.296560E+09 | 0.376502E+09 |
February | 0.264631E+09 | 0.121091E+09 | 0.143540E+09 | 0.267019E+09 | 0.305219E+09 |
March | 0.357605E+09 | 0.159739E+09 | 0.197867E+09 | 0.392321E+09 | 0.344246E+09 |
April | 0.441116E+09 | 0.221343E+09 | 0.219773E+09 | 0.563114E+09 | 0.251789E+09 |
May | 0.429306E+09 | 0.178897E+09 | 0.250408E+09 | 0.533846E+09 | 0.232875E+09 |
June | 0.413350E+09 | 0.179438E+09 | 0.233913E+09 | 0.555949E+09 | 0.162764E+09 |
July | 0.483690E+09 | 0.240292E+09 | 0.243398E+09 | 0.706305E+09 | 0.139497E+09 |
August | 0.478079E+09 | 0.254085E+09 | 0.223994E+09 | 0.707028E+09 | 0.143490E+09 |
September | 0.337794E+09 | 0.155377E+09 | 0.182417E+09 | 0.464663E+09 | 0.171218E+09 |
October | 0.307616E+09 | 0.157887E+09 | 0.149729E+09 | 0.435534E+09 | 0.201686E+09 |
November | 0.270739E+09 | 0.137061E+09 | 0.133678E+09 | 0.295711E+09 | 0.320573E+09 |
December | 0.268947E+09 | 0.149895E+09 | 0.119052E+09 | 0.284316E+09 | 0.375159E+09 |
Annual Sum or Average | 0.433052E+10 | 0.210345E+10 | 0.222707E+10 | 0.550237E+10 | 0.302502E+10 |
Minimum of Months | 0.264631E+09 | 0.121091E+09 | 0.119052E+09 | 0.267019E+09 | 0.139497E+09 |
Maximum of Months | 0.483690E+09 | 0.254085E+09 | 0.250408E+09 | 0.707028E+09 | 0.376502E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365202E+09 | 0.268138E+09 | 97063741.13 | 0.521747E+09 | 0.195538E+09 |
February | 0.260538E+09 | 0.161230E+09 | 99307626.30 | 0.338099E+09 | 0.162036E+09 |
March | 0.229983E+09 | 0.112013E+09 | 0.117970E+09 | 0.273532E+09 | 0.192312E+09 |
April | 0.186057E+09 | 71862951.28 | 0.114194E+09 | 0.205037E+09 | 0.143949E+09 |
May | 0.135458E+09 | 16348586.95 | 0.119109E+09 | 0.122844E+09 | 0.133558E+09 |
June | 0.114995E+09 | 6688070.10 | 0.108307E+09 | 0.113913E+09 | 91212767.96 |
July | 0.125301E+09 | 13325851.52 | 0.111975E+09 | 0.140406E+09 | 76872482.21 |
August | 0.160950E+09 | 49954094.11 | 0.110996E+09 | 0.198126E+09 | 79888236.93 |
September | 0.213935E+09 | 0.106247E+09 | 0.107688E+09 | 0.291588E+09 | 93989581.79 |
October | 0.289592E+09 | 0.194493E+09 | 95099285.37 | 0.439397E+09 | 0.108617E+09 |
November | 0.340475E+09 | 0.241261E+09 | 99213597.08 | 0.483532E+09 | 0.166711E+09 |
December | 0.390803E+09 | 0.297825E+09 | 92977895.08 | 0.566656E+09 | 0.193575E+09 |
Annual Sum or Average | 0.281329E+10 | 0.153939E+10 | 0.127390E+10 | 0.369488E+10 | 0.163826E+10 |
Minimum of Months | 0.114995E+09 | 6688070.10 | 92977895.08 | 0.113913E+09 | 76872482.21 |
Maximum of Months | 0.390803E+09 | 0.297825E+09 | 0.119109E+09 | 0.566656E+09 | 0.195538E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55187410.10 | 0.00 | 55187410.10 | 32242686.20 | 0.211734E+09 |
February | 62570938.96 | 0.00 | 62570938.96 | 33033673.00 | 0.171032E+09 |
March | 84898795.36 | 753.87 | 84898041.50 | 53496279.63 | 0.196344E+09 |
April | 95148727.15 | 759942.51 | 94388784.64 | 74295179.19 | 0.141002E+09 |
May | 0.118266E+09 | 6148054.32 | 0.112118E+09 | 94187032.44 | 0.124897E+09 |
June | 0.121311E+09 | 11957604.86 | 0.109354E+09 | 0.115788E+09 | 85728378.31 |
July | 0.118739E+09 | 10047152.59 | 0.108692E+09 | 0.126710E+09 | 76482183.19 |
August | 98737814.75 | 2181324.43 | 96556490.32 | 0.108474E+09 | 82242940.46 |
September | 80667879.41 | 15675.90 | 80652203.51 | 86540610.09 | 95751765.63 |
October | 66114501.28 | 0.00 | 66114501.28 | 80842542.58 | 0.115577E+09 |
November | 57930922.12 | 0.00 | 57930922.12 | 37345502.87 | 0.178282E+09 |
December | 51374769.97 | 0.00 | 51374769.97 | 29536327.01 | 0.210606E+09 |
Annual Sum or Average | 0.101095E+10 | 31110508.49 | 0.979838E+09 | 0.872491E+09 | 0.168968E+10 |
Minimum of Months | 51374769.97 | 0.00 | 51374769.97 | 29536327.01 | 76482183.19 |
Maximum of Months | 0.121311E+09 | 11957604.86 | 0.112118E+09 | 0.126710E+09 | 0.211734E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.277649E+09 | 0.148349E+09 | 0.129300E+09 | 0.311886E+09 | 0.362381E+09 |
February | 0.264631E+09 | 0.121091E+09 | 0.143540E+09 | 0.278008E+09 | 0.296615E+09 |
March | 0.357605E+09 | 0.159739E+09 | 0.197867E+09 | 0.400789E+09 | 0.338889E+09 |
April | 0.441116E+09 | 0.221343E+09 | 0.219773E+09 | 0.566472E+09 | 0.251261E+09 |
May | 0.429306E+09 | 0.178897E+09 | 0.250408E+09 | 0.531655E+09 | 0.235079E+09 |
June | 0.413350E+09 | 0.179438E+09 | 0.233913E+09 | 0.548687E+09 | 0.169824E+09 |
July | 0.483690E+09 | 0.240292E+09 | 0.243398E+09 | 0.694096E+09 | 0.151121E+09 |
August | 0.478079E+09 | 0.254085E+09 | 0.223994E+09 | 0.697996E+09 | 0.153840E+09 |
September | 0.337794E+09 | 0.155377E+09 | 0.182417E+09 | 0.467118E+09 | 0.174142E+09 |
October | 0.307616E+09 | 0.157887E+09 | 0.149729E+09 | 0.442375E+09 | 0.202916E+09 |
November | 0.270739E+09 | 0.137061E+09 | 0.133678E+09 | 0.309591E+09 | 0.308616E+09 |
December | 0.268947E+09 | 0.149895E+09 | 0.119052E+09 | 0.300154E+09 | 0.360309E+09 |
Annual Sum or Average | 0.433052E+10 | 0.210345E+10 | 0.222707E+10 | 0.554883E+10 | 0.300499E+10 |
Minimum of Months | 0.264631E+09 | 0.121091E+09 | 0.119052E+09 | 0.278008E+09 | 0.151121E+09 |
Maximum of Months | 0.483690E+09 | 0.254085E+09 | 0.250408E+09 | 0.697996E+09 | 0.362381E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69891372.75 | 0.00 | 69891372.75 | 47217355.94 | 0.254271E+09 |
February | 79242146.19 | 0.00 | 79242146.19 | 49547240.55 | 0.204824E+09 |
March | 0.107519E+09 | 954.73 | 0.107518E+09 | 80404743.84 | 0.232755E+09 |
April | 0.120500E+09 | 962419.24 | 0.119537E+09 | 0.117174E+09 | 0.162072E+09 |
May | 0.149777E+09 | 7786122.88 | 0.141991E+09 | 0.146686E+09 | 0.143486E+09 |
June | 0.153633E+09 | 15143552.07 | 0.138490E+09 | 0.179365E+09 | 94595267.46 |
July | 0.150376E+09 | 12724084.82 | 0.137651E+09 | 0.201135E+09 | 79019806.27 |
August | 0.125045E+09 | 2762509.76 | 0.122283E+09 | 0.174016E+09 | 83376584.81 |
September | 0.102161E+09 | 19852.54 | 0.102141E+09 | 0.131695E+09 | 0.104894E+09 |
October | 83729844.28 | 0.00 | 83729844.28 | 0.119841E+09 | 0.128015E+09 |
November | 73365857.63 | 0.00 | 73365857.63 | 55316365.75 | 0.212712E+09 |
December | 65062904.60 | 0.00 | 65062904.60 | 43467136.29 | 0.253678E+09 |
Annual Sum or Average | 0.128030E+10 | 39399496.03 | 0.124090E+10 | 0.134587E+10 | 0.195370E+10 |
Minimum of Months | 65062904.60 | 0.00 | 65062904.60 | 43467136.29 | 79019806.27 |
Maximum of Months | 0.153633E+09 | 15143552.07 | 0.141991E+09 | 0.201135E+09 | 0.254271E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 25764853.97 | 0.00 | 25764853.97 | 17406272.52 | 93734729.03 |
February | 29211936.25 | 0.00 | 29211936.25 | 18265164.45 | 75506431.85 |
March | 39635943.43 | 351.95 | 39635591.48 | 29640517.88 | 85803177.11 |
April | 44421237.67 | 354787.58 | 44066450.09 | 43195289.74 | 59746556.77 |
May | 55213901.29 | 2870287.29 | 52343614.00 | 54074501.52 | 52894814.04 |
June | 56635538.72 | 5582540.34 | 51052998.38 | 66121195.98 | 34871732.47 |
July | 55434638.91 | 4690624.53 | 50744014.38 | 74146845.96 | 29129972.54 |
August | 46096843.00 | 1018375.49 | 45078467.51 | 64149680.89 | 30736061.51 |
September | 37660693.44 | 7318.47 | 37653374.97 | 48548106.79 | 38668355.06 |
October | 30866287.58 | 0.00 | 30866287.58 | 44178477.29 | 47191697.86 |
November | 27045692.96 | 0.00 | 27045692.96 | 20391902.89 | 78414370.62 |
December | 23984880.68 | 0.00 | 23984880.68 | 16023786.27 | 93516325.95 |
Annual Sum or Average | 0.471972E+09 | 14524285.64 | 0.457448E+09 | 0.496142E+09 | 0.720214E+09 |
Minimum of Months | 23984880.68 | 0.00 | 23984880.68 | 16023786.27 | 29129972.54 |
Maximum of Months | 56635538.72 | 5582540.34 | 52343614.00 | 74146845.96 | 93734729.03 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170402E+09 | 0.125112E+09 | 45289550.47 | 0.250867E+09 | 84522155.92 |
February | 0.121566E+09 | 75229412.69 | 46336538.25 | 0.164093E+09 | 70392131.30 |
March | 0.107309E+09 | 52264661.39 | 55044286.02 | 0.134336E+09 | 83186076.65 |
April | 86813447.28 | 33530963.48 | 53282483.80 | 0.104190E+09 | 60705770.99 |
May | 63204082.27 | 7628184.79 | 55575897.48 | 66159808.40 | 56490193.65 |
June | 53656277.55 | 3120626.56 | 50535650.99 | 62498669.40 | 37754193.18 |
July | 58464877.45 | 6217788.62 | 52247088.84 | 76570296.04 | 30770737.23 |
August | 75098724.10 | 23308379.01 | 51790345.09 | 0.102897E+09 | 31623642.90 |
September | 99821202.28 | 49574616.32 | 50246585.96 | 0.143918E+09 | 38543447.31 |
October | 0.135122E+09 | 90749476.67 | 44372943.33 | 0.212705E+09 | 44886548.84 |
November | 0.158864E+09 | 0.112571E+09 | 46292664.60 | 0.233027E+09 | 71646704.96 |
December | 0.182347E+09 | 0.138964E+09 | 43383111.17 | 0.271891E+09 | 83660068.23 |
Annual Sum or Average | 0.131267E+10 | 0.718272E+09 | 0.594397E+09 | 0.182315E+10 | 0.694182E+09 |
Minimum of Months | 53656277.55 | 3120626.56 | 43383111.17 | 62498669.40 | 30770737.23 |
Maximum of Months | 0.182347E+09 | 0.138964E+09 | 55575897.48 | 0.271891E+09 | 84522155.92 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.462505E+09 | 0.339580E+09 | 0.122925E+09 | 0.680904E+09 | 0.229410E+09 |
February | 0.329955E+09 | 0.204188E+09 | 0.125767E+09 | 0.445383E+09 | 0.191059E+09 |
March | 0.291258E+09 | 0.141857E+09 | 0.149401E+09 | 0.364616E+09 | 0.225784E+09 |
April | 0.235629E+09 | 91009893.49 | 0.144620E+09 | 0.282792E+09 | 0.164768E+09 |
May | 0.171549E+09 | 20704453.84 | 0.150844E+09 | 0.179571E+09 | 0.153326E+09 |
June | 0.145634E+09 | 8470018.79 | 0.137164E+09 | 0.169634E+09 | 0.102473E+09 |
July | 0.158686E+09 | 16876350.13 | 0.141809E+09 | 0.207827E+09 | 83518074.85 |
August | 0.203833E+09 | 63263708.26 | 0.140570E+09 | 0.279282E+09 | 85833035.21 |
September | 0.270935E+09 | 0.134556E+09 | 0.136380E+09 | 0.390623E+09 | 0.104615E+09 |
October | 0.366750E+09 | 0.246313E+09 | 0.120437E+09 | 0.577326E+09 | 0.121831E+09 |
November | 0.431190E+09 | 0.305542E+09 | 0.125648E+09 | 0.632483E+09 | 0.194464E+09 |
December | 0.494927E+09 | 0.377177E+09 | 0.117751E+09 | 0.737967E+09 | 0.227071E+09 |
Annual Sum or Average | 0.356285E+10 | 0.194954E+10 | 0.161332E+10 | 0.494841E+10 | 0.188415E+10 |
Minimum of Months | 0.145634E+09 | 8470018.79 | 0.117751E+09 | 0.169634E+09 | 83518074.85 |
Maximum of Months | 0.494927E+09 | 0.377177E+09 | 0.150844E+09 | 0.737967E+09 | 0.229410E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365502E+09 | 0.268358E+09 | 97143366.84 | 0.520309E+09 | 0.195775E+09 |
February | 0.260752E+09 | 0.161363E+09 | 99389092.77 | 0.335241E+09 | 0.163399E+09 |
March | 0.230171E+09 | 0.112105E+09 | 0.118067E+09 | 0.271926E+09 | 0.194302E+09 |
April | 0.186210E+09 | 71921903.66 | 0.114288E+09 | 0.202962E+09 | 0.147432E+09 |
May | 0.135569E+09 | 16361998.43 | 0.119207E+09 | 0.119804E+09 | 0.137674E+09 |
June | 0.115089E+09 | 6693556.62 | 0.108396E+09 | 0.110190E+09 | 95756890.52 |
July | 0.125404E+09 | 13336783.30 | 0.112067E+09 | 0.137550E+09 | 81401264.59 |
August | 0.161082E+09 | 49995073.68 | 0.111087E+09 | 0.195651E+09 | 84049374.59 |
September | 0.214110E+09 | 0.106335E+09 | 0.107776E+09 | 0.287011E+09 | 98243232.81 |
October | 0.289829E+09 | 0.194652E+09 | 95177299.55 | 0.435561E+09 | 0.111025E+09 |
November | 0.340754E+09 | 0.241459E+09 | 99294986.42 | 0.480030E+09 | 0.168335E+09 |
December | 0.391124E+09 | 0.298070E+09 | 93054168.99 | 0.564164E+09 | 0.194108E+09 |
Annual Sum or Average | 0.281560E+10 | 0.154065E+10 | 0.127495E+10 | 0.366040E+10 | 0.167150E+10 |
Minimum of Months | 0.115089E+09 | 6693556.62 | 93054168.99 | 0.110190E+09 | 81401264.59 |
Maximum of Months | 0.391124E+09 | 0.298070E+09 | 0.119207E+09 | 0.564164E+09 | 0.195775E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264794E+09 | 0.133533E+09 | 0.131261E+09 | 0.288623E+09 | 0.395806E+09 |
February | 0.285643E+09 | 0.132024E+09 | 0.153619E+09 | 0.307150E+09 | 0.318222E+09 |
March | 0.361719E+09 | 0.159860E+09 | 0.201858E+09 | 0.402428E+09 | 0.361177E+09 |
April | 0.482422E+09 | 0.250808E+09 | 0.231614E+09 | 0.621317E+09 | 0.264253E+09 |
May | 0.489673E+09 | 0.225831E+09 | 0.263842E+09 | 0.615259E+09 | 0.242646E+09 |
June | 0.501869E+09 | 0.250584E+09 | 0.251285E+09 | 0.678450E+09 | 0.166562E+09 |
July | 0.549131E+09 | 0.293530E+09 | 0.255601E+09 | 0.792661E+09 | 0.141963E+09 |
August | 0.515303E+09 | 0.279027E+09 | 0.236276E+09 | 0.750116E+09 | 0.149791E+09 |
September | 0.427403E+09 | 0.228632E+09 | 0.198770E+09 | 0.595305E+09 | 0.177149E+09 |
October | 0.339222E+09 | 0.185863E+09 | 0.153359E+09 | 0.485199E+09 | 0.213645E+09 |
November | 0.295405E+09 | 0.154621E+09 | 0.140783E+09 | 0.340072E+09 | 0.333998E+09 |
December | 0.268502E+09 | 0.143562E+09 | 0.124940E+09 | 0.299545E+09 | 0.394100E+09 |
Annual Sum or Average | 0.478108E+10 | 0.243788E+10 | 0.234321E+10 | 0.617612E+10 | 0.315931E+10 |
Minimum of Months | 0.264794E+09 | 0.132024E+09 | 0.124940E+09 | 0.288623E+09 | 0.141963E+09 |
Maximum of Months | 0.549131E+09 | 0.293530E+09 | 0.263842E+09 | 0.792661E+09 | 0.395806E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55232682.79 | 0.00 | 55232682.79 | 33648132.78 | 0.211315E+09 |
February | 62622268.69 | 0.00 | 62622268.69 | 33312686.56 | 0.172578E+09 |
March | 84968441.63 | 754.49 | 84967687.14 | 53333554.93 | 0.198455E+09 |
April | 95226781.88 | 760565.92 | 94466215.96 | 71305736.52 | 0.147684E+09 |
May | 0.118363E+09 | 6153097.85 | 0.112210E+09 | 87451386.81 | 0.130401E+09 |
June | 0.121411E+09 | 11967414.21 | 0.109443E+09 | 0.105528E+09 | 94433100.61 |
July | 0.118836E+09 | 10055394.72 | 0.108781E+09 | 0.116517E+09 | 88016948.11 |
August | 98818813.78 | 2183113.87 | 96635699.91 | 0.102277E+09 | 94511793.91 |
September | 80734054.86 | 15688.76 | 80718366.10 | 81628076.16 | 0.105552E+09 |
October | 66168737.95 | 0.00 | 66168737.95 | 79227225.47 | 0.121485E+09 |
November | 57978445.44 | 0.00 | 57978445.44 | 37500473.28 | 0.181024E+09 |
December | 51416914.99 | 0.00 | 51416914.99 | 31091085.97 | 0.210811E+09 |
Annual Sum or Average | 0.101178E+10 | 31136029.82 | 0.980642E+09 | 0.832820E+09 | 0.175627E+10 |
Minimum of Months | 51416914.99 | 0.00 | 51416914.99 | 31091085.97 | 88016948.11 |
Maximum of Months | 0.121411E+09 | 11967414.21 | 0.112210E+09 | 0.116517E+09 | 0.211315E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264794E+09 | 0.133533E+09 | 0.131261E+09 | 0.307213E+09 | 0.384217E+09 |
February | 0.285643E+09 | 0.132024E+09 | 0.153619E+09 | 0.319194E+09 | 0.311043E+09 |
March | 0.361719E+09 | 0.159860E+09 | 0.201858E+09 | 0.410116E+09 | 0.356985E+09 |
April | 0.482422E+09 | 0.250808E+09 | 0.231614E+09 | 0.617754E+09 | 0.267230E+09 |
May | 0.489673E+09 | 0.225831E+09 | 0.263842E+09 | 0.605326E+09 | 0.247939E+09 |
June | 0.501869E+09 | 0.250584E+09 | 0.251285E+09 | 0.658750E+09 | 0.181270E+09 |
July | 0.549131E+09 | 0.293530E+09 | 0.255601E+09 | 0.765205E+09 | 0.165391E+09 |
August | 0.515303E+09 | 0.279027E+09 | 0.236276E+09 | 0.730164E+09 | 0.172350E+09 |
September | 0.427403E+09 | 0.228632E+09 | 0.198770E+09 | 0.591103E+09 | 0.187308E+09 |
October | 0.339222E+09 | 0.185863E+09 | 0.153359E+09 | 0.489569E+09 | 0.220332E+09 |
November | 0.295405E+09 | 0.154621E+09 | 0.140783E+09 | 0.355410E+09 | 0.325652E+09 |
December | 0.268502E+09 | 0.143562E+09 | 0.124940E+09 | 0.318595E+09 | 0.381818E+09 |
Annual Sum or Average | 0.478108E+10 | 0.243788E+10 | 0.234321E+10 | 0.616840E+10 | 0.320153E+10 |
Minimum of Months | 0.264794E+09 | 0.132024E+09 | 0.124940E+09 | 0.307213E+09 | 0.165391E+09 |
Maximum of Months | 0.549131E+09 | 0.293530E+09 | 0.263842E+09 | 0.765205E+09 | 0.384217E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.536043E+09 | 0.393573E+09 | 0.142470E+09 | 0.749743E+09 | 0.298868E+09 |
February | 0.382417E+09 | 0.236654E+09 | 0.145764E+09 | 0.483069E+09 | 0.247555E+09 |
March | 0.337568E+09 | 0.164412E+09 | 0.173156E+09 | 0.392830E+09 | 0.290197E+09 |
April | 0.273094E+09 | 0.105480E+09 | 0.167614E+09 | 0.299263E+09 | 0.213212E+09 |
May | 0.198825E+09 | 23996440.96 | 0.174828E+09 | 0.182163E+09 | 0.196217E+09 |
June | 0.168790E+09 | 9816743.17 | 0.158973E+09 | 0.170850E+09 | 0.133161E+09 |
July | 0.183916E+09 | 19559672.65 | 0.164357E+09 | 0.212617E+09 | 0.111071E+09 |
August | 0.236243E+09 | 73322573.59 | 0.162920E+09 | 0.294372E+09 | 0.116661E+09 |
September | 0.314014E+09 | 0.155950E+09 | 0.158064E+09 | 0.422335E+09 | 0.140844E+09 |
October | 0.425063E+09 | 0.285476E+09 | 0.139587E+09 | 0.635011E+09 | 0.164568E+09 |
November | 0.499748E+09 | 0.354123E+09 | 0.145626E+09 | 0.693789E+09 | 0.255339E+09 |
December | 0.573620E+09 | 0.437148E+09 | 0.136473E+09 | 0.813670E+09 | 0.296447E+09 |
Annual Sum or Average | 0.412934E+10 | 0.225951E+10 | 0.186983E+10 | 0.534971E+10 | 0.246414E+10 |
Minimum of Months | 0.168790E+09 | 9816743.17 | 0.136473E+09 | 0.170850E+09 | 0.111071E+09 |
Maximum of Months | 0.573620E+09 | 0.437148E+09 | 0.174828E+09 | 0.813670E+09 | 0.298868E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.386614E+09 | 0.00 | 0.386614E+09 | 0.182152E+09 | 0.170105E+10 |
February | 0.438339E+09 | 0.00 | 0.438339E+09 | 0.180935E+09 | 0.143349E+10 |
March | 0.594757E+09 | 5281.20 | 0.594751E+09 | 0.317572E+09 | 0.160453E+10 |
April | 0.666562E+09 | 5323759.83 | 0.661238E+09 | 0.483444E+09 | 0.116299E+10 |
May | 0.828511E+09 | 43070053.68 | 0.785441E+09 | 0.602419E+09 | 0.104404E+10 |
June | 0.849844E+09 | 83768726.79 | 0.766075E+09 | 0.763964E+09 | 0.733374E+09 |
July | 0.831824E+09 | 70385097.24 | 0.761439E+09 | 0.873880E+09 | 0.644956E+09 |
August | 0.691705E+09 | 15281218.34 | 0.676424E+09 | 0.757009E+09 | 0.700586E+09 |
September | 0.565117E+09 | 109817.17 | 0.565007E+09 | 0.571967E+09 | 0.827518E+09 |
October | 0.463164E+09 | 0.00 | 0.463164E+09 | 0.529644E+09 | 0.982195E+09 |
November | 0.405834E+09 | 0.00 | 0.405834E+09 | 0.212599E+09 | 0.147000E+10 |
December | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.165080E+09 | 0.170450E+10 |
Annual Sum or Average | 0.708218E+10 | 0.217944E+09 | 0.686423E+10 | 0.564067E+10 | 0.140092E+11 |
Minimum of Months | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.165080E+09 | 0.644956E+09 |
Maximum of Months | 0.849844E+09 | 83768726.79 | 0.785441E+09 | 0.873880E+09 | 0.170450E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.386614E+09 | 0.00 | 0.386614E+09 | 0.159238E+09 | 0.177225E+10 |
February | 0.438339E+09 | 0.00 | 0.438339E+09 | 0.157371E+09 | 0.149749E+10 |
March | 0.594757E+09 | 5281.20 | 0.594751E+09 | 0.285114E+09 | 0.167004E+10 |
April | 0.666562E+09 | 5323759.83 | 0.661238E+09 | 0.443520E+09 | 0.121254E+10 |
May | 0.828511E+09 | 43070053.68 | 0.785441E+09 | 0.552585E+09 | 0.108823E+10 |
June | 0.849844E+09 | 83768726.79 | 0.766075E+09 | 0.711153E+09 | 0.768417E+09 |
July | 0.831824E+09 | 70385097.24 | 0.761439E+09 | 0.820880E+09 | 0.678369E+09 |
August | 0.691705E+09 | 15281218.34 | 0.676424E+09 | 0.710640E+09 | 0.739626E+09 |
September | 0.565117E+09 | 109817.17 | 0.565007E+09 | 0.533207E+09 | 0.873749E+09 |
October | 0.463164E+09 | 0.00 | 0.463164E+09 | 0.495141E+09 | 0.103415E+10 |
November | 0.405834E+09 | 0.00 | 0.405834E+09 | 0.187121E+09 | 0.153356E+10 |
December | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.143613E+09 | 0.177610E+10 |
Annual Sum or Average | 0.708218E+10 | 0.217944E+09 | 0.686423E+10 | 0.519958E+10 | 0.146445E+11 |
Minimum of Months | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.143613E+09 | 0.678369E+09 |
Maximum of Months | 0.849844E+09 | 83768726.79 | 0.785441E+09 | 0.820880E+09 | 0.177610E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 55232682.79 | 0.00 | 55232682.79 | 38887650.66 | 0.217464E+09 |
February | 62622268.69 | 0.00 | 62622268.69 | 37593934.80 | 0.187425E+09 |
March | 84968441.63 | 754.49 | 84967687.14 | 62283173.07 | 0.211508E+09 |
April | 95226781.88 | 760565.92 | 94466215.96 | 92435391.19 | 0.154391E+09 |
May | 0.118363E+09 | 6153097.85 | 0.112210E+09 | 0.115647E+09 | 0.141794E+09 |
June | 0.121411E+09 | 11967414.21 | 0.109443E+09 | 0.142983E+09 | 99076679.97 |
July | 0.118836E+09 | 10055394.72 | 0.108781E+09 | 0.162706E+09 | 85758711.27 |
August | 98818813.78 | 2183113.87 | 96635699.91 | 0.141498E+09 | 90884156.21 |
September | 80734054.86 | 15688.76 | 80718366.10 | 0.107478E+09 | 0.103011E+09 |
October | 66168737.95 | 0.00 | 66168737.95 | 98588822.33 | 0.122769E+09 |
November | 57978445.44 | 0.00 | 57978445.44 | 44410339.05 | 0.188027E+09 |
December | 51416914.99 | 0.00 | 51416914.99 | 35902395.13 | 0.217710E+09 |
Annual Sum or Average | 0.101178E+10 | 31136029.82 | 0.980642E+09 | 0.108041E+10 | 0.181982E+10 |
Minimum of Months | 51416914.99 | 0.00 | 51416914.99 | 35902395.13 | 85758711.27 |
Maximum of Months | 0.121411E+09 | 11967414.21 | 0.112210E+09 | 0.162706E+09 | 0.217710E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555714E+09 | 0.296920E+09 | 0.258794E+09 | 0.661137E+09 | 0.763511E+09 |
February | 0.529658E+09 | 0.242363E+09 | 0.287295E+09 | 0.577566E+09 | 0.666501E+09 |
March | 0.715747E+09 | 0.319716E+09 | 0.396030E+09 | 0.841465E+09 | 0.748426E+09 |
April | 0.882893E+09 | 0.443018E+09 | 0.439875E+09 | 0.120617E+10 | 0.562042E+09 |
May | 0.859255E+09 | 0.358063E+09 | 0.501192E+09 | 0.114206E+10 | 0.534929E+09 |
June | 0.827320E+09 | 0.359144E+09 | 0.468176E+09 | 0.119715E+10 | 0.387974E+09 |
July | 0.968105E+09 | 0.480944E+09 | 0.487161E+09 | 0.152021E+10 | 0.336106E+09 |
August | 0.956875E+09 | 0.508552E+09 | 0.448323E+09 | 0.152049E+10 | 0.344987E+09 |
September | 0.676094E+09 | 0.310988E+09 | 0.365107E+09 | 0.101799E+10 | 0.384361E+09 |
October | 0.615693E+09 | 0.316011E+09 | 0.299682E+09 | 0.958058E+09 | 0.443790E+09 |
November | 0.541883E+09 | 0.274327E+09 | 0.267556E+09 | 0.652635E+09 | 0.666938E+09 |
December | 0.538297E+09 | 0.300015E+09 | 0.238282E+09 | 0.632981E+09 | 0.762888E+09 |
Annual Sum or Average | 0.866753E+10 | 0.421006E+10 | 0.445747E+10 | 0.119279E+11 | 0.660245E+10 |
Minimum of Months | 0.529658E+09 | 0.242363E+09 | 0.238282E+09 | 0.577566E+09 | 0.336106E+09 |
Maximum of Months | 0.968105E+09 | 0.508552E+09 | 0.501192E+09 | 0.152049E+10 | 0.763511E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365502E+09 | 0.268358E+09 | 97143366.84 | 0.544329E+09 | 0.201124E+09 |
February | 0.260752E+09 | 0.161363E+09 | 99389092.77 | 0.351893E+09 | 0.178923E+09 |
March | 0.230171E+09 | 0.112105E+09 | 0.118067E+09 | 0.287940E+09 | 0.208510E+09 |
April | 0.186210E+09 | 71921903.66 | 0.114288E+09 | 0.223858E+09 | 0.158384E+09 |
May | 0.135569E+09 | 16361998.43 | 0.119207E+09 | 0.140620E+09 | 0.151349E+09 |
June | 0.115089E+09 | 6693556.62 | 0.108396E+09 | 0.136167E+09 | 0.107435E+09 |
July | 0.125404E+09 | 13336783.30 | 0.112067E+09 | 0.169271E+09 | 91315832.60 |
August | 0.161082E+09 | 49995073.68 | 0.111087E+09 | 0.225869E+09 | 94212564.28 |
September | 0.214110E+09 | 0.106335E+09 | 0.107776E+09 | 0.313685E+09 | 0.104464E+09 |
October | 0.289829E+09 | 0.194652E+09 | 95177299.55 | 0.462285E+09 | 0.120045E+09 |
November | 0.340754E+09 | 0.241459E+09 | 99294986.42 | 0.503503E+09 | 0.176280E+09 |
December | 0.391124E+09 | 0.298070E+09 | 93054168.99 | 0.588497E+09 | 0.200137E+09 |
Annual Sum or Average | 0.281560E+10 | 0.154065E+10 | 0.127495E+10 | 0.394792E+10 | 0.179218E+10 |
Minimum of Months | 0.115089E+09 | 6693556.62 | 93054168.99 | 0.136167E+09 | 91315832.60 |
Maximum of Months | 0.391124E+09 | 0.298070E+09 | 0.119207E+09 | 0.588497E+09 | 0.208510E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69948707.76 | 0.00 | 69948707.76 | 40306031.05 | 0.263507E+09 |
February | 79307152.05 | 0.00 | 79307152.05 | 42555365.56 | 0.213414E+09 |
March | 0.107607E+09 | 955.51 | 0.107606E+09 | 71540304.45 | 0.241928E+09 |
April | 0.120599E+09 | 963208.75 | 0.119636E+09 | 0.105535E+09 | 0.170486E+09 |
May | 0.149900E+09 | 7792510.18 | 0.142107E+09 | 0.133919E+09 | 0.150947E+09 |
June | 0.153759E+09 | 15155975.00 | 0.138603E+09 | 0.164168E+09 | 0.102452E+09 |
July | 0.150499E+09 | 12734522.95 | 0.137764E+09 | 0.182509E+09 | 88927612.32 |
August | 0.125148E+09 | 2764775.97 | 0.122383E+09 | 0.156308E+09 | 95277437.11 |
September | 0.102245E+09 | 19868.83 | 0.102225E+09 | 0.118738E+09 | 0.115054E+09 |
October | 83798531.60 | 0.00 | 83798531.60 | 0.107194E+09 | 0.140401E+09 |
November | 73426042.91 | 0.00 | 73426042.91 | 47454166.02 | 0.221952E+09 |
December | 65116278.60 | 0.00 | 65116278.60 | 36537700.18 | 0.262721E+09 |
Annual Sum or Average | 0.128135E+10 | 39431817.19 | 0.124192E+10 | 0.120676E+10 | 0.206707E+10 |
Minimum of Months | 65116278.60 | 0.00 | 65116278.60 | 36537700.18 | 88927612.32 |
Maximum of Months | 0.153759E+09 | 15155975.00 | 0.142107E+09 | 0.182509E+09 | 0.263507E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 62583373.87 | 0.00 | 62583373.87 | 36061958.70 | 0.235745E+09 |
February | 70956409.44 | 0.00 | 70956409.44 | 38074446.81 | 0.190942E+09 |
March | 96276542.82 | 854.90 | 96275687.92 | 64007381.45 | 0.216454E+09 |
April | 0.107900E+09 | 861786.52 | 0.107038E+09 | 94422886.31 | 0.152535E+09 |
May | 0.134116E+09 | 6971988.39 | 0.127144E+09 | 0.119817E+09 | 0.135053E+09 |
June | 0.137569E+09 | 13560108.26 | 0.124009E+09 | 0.146882E+09 | 91663904.60 |
July | 0.134652E+09 | 11393625.94 | 0.123258E+09 | 0.163292E+09 | 79563871.69 |
August | 0.111970E+09 | 2473655.54 | 0.109497E+09 | 0.139849E+09 | 85245083.99 |
September | 91478618.90 | 17776.71 | 91460842.19 | 0.106235E+09 | 0.102939E+09 |
October | 74974863.74 | 0.00 | 74974863.74 | 95906760.87 | 0.125617E+09 |
November | 65694558.80 | 0.00 | 65694558.80 | 42457422.15 | 0.198580E+09 |
December | 58259781.19 | 0.00 | 58259781.19 | 32690418.79 | 0.235034E+09 |
Annual Sum or Average | 0.114643E+10 | 35279796.25 | 0.111115E+10 | 0.107970E+10 | 0.184937E+10 |
Minimum of Months | 58259781.19 | 0.00 | 58259781.19 | 32690418.79 | 79563871.69 |
Maximum of Months | 0.137569E+09 | 13560108.26 | 0.127144E+09 | 0.163292E+09 | 0.235745E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.136453E+10 | 0.100186E+10 | 0.362665E+09 | 0.197144E+10 | 0.700576E+09 |
February | 0.973464E+09 | 0.602415E+09 | 0.371049E+09 | 0.127911E+10 | 0.587633E+09 |
March | 0.859298E+09 | 0.418520E+09 | 0.440778E+09 | 0.104121E+10 | 0.694704E+09 |
April | 0.695176E+09 | 0.268506E+09 | 0.426670E+09 | 0.797265E+09 | 0.513838E+09 |
May | 0.506119E+09 | 61084215.77 | 0.445035E+09 | 0.493268E+09 | 0.479338E+09 |
June | 0.429663E+09 | 24989041.45 | 0.404674E+09 | 0.459487E+09 | 0.331089E+09 |
July | 0.468169E+09 | 49790186.24 | 0.418379E+09 | 0.561996E+09 | 0.281447E+09 |
August | 0.601368E+09 | 0.186647E+09 | 0.414722E+09 | 0.771775E+09 | 0.292071E+09 |
September | 0.799338E+09 | 0.396979E+09 | 0.402360E+09 | 0.110881E+10 | 0.340282E+09 |
October | 0.108202E+10 | 0.726695E+09 | 0.355325E+09 | 0.165364E+10 | 0.395746E+09 |
November | 0.127214E+10 | 0.901438E+09 | 0.370698E+09 | 0.182506E+10 | 0.598166E+09 |
December | 0.146018E+10 | 0.111278E+10 | 0.347399E+09 | 0.213639E+10 | 0.692688E+09 |
Annual Sum or Average | 0.105115E+11 | 0.575170E+10 | 0.475975E+10 | 0.140995E+11 | 0.590758E+10 |
Minimum of Months | 0.429663E+09 | 24989041.45 | 0.347399E+09 | 0.459487E+09 | 0.281447E+09 |
Maximum of Months | 0.146018E+10 | 0.111278E+10 | 0.445035E+09 | 0.213639E+10 | 0.700576E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 981.05 | 354.47 | 691.03 | 507.37 | 183.66 | 0.00 | 0.00 |
February | 713.69 | 322.63 | 545.81 | 337.77 | 208.04 | 0.00 | 0.00 |
March | 529.96 | 335.25 | 435.17 | 211.95 | 223.22 | 0.00 | 0.00 |
April | 418.45 | 259.71 | 363.79 | 140.51 | 223.28 | 0.00 | 0.00 |
May | 256.10 | 229.55 | 256.31 | 30.93 | 225.38 | 0.00 | 0.00 |
June | 245.59 | 165.06 | 224.85 | 13.08 | 211.77 | 0.00 | 0.00 |
July | 286.25 | 137.22 | 237.09 | 25.22 | 211.88 | 0.00 | 0.00 |
August | 387.99 | 145.39 | 304.55 | 94.52 | 210.03 | 0.00 | 0.00 |
September | 572.33 | 180.60 | 418.30 | 207.74 | 210.56 | 0.00 | 0.00 |
October | 821.52 | 208.92 | 547.96 | 368.02 | 179.95 | 0.00 | 0.00 |
November | 940.12 | 317.69 | 665.72 | 471.73 | 193.99 | 0.00 | 0.00 |
December | 1062.54 | 355.67 | 739.48 | 563.54 | 175.93 | 0.00 | 0.00 |
Annual Sum or Average | 601.00 | 250.65 | 452.12 | 247.39 | 204.72 | 0.00 | 0.00 |
Minimum of Months | 245.59 | 137.22 | 224.85 | 13.08 | 175.93 | 0.00 | 0.00 |
Maximum of Months | 1062.54 | 355.67 | 739.48 | 563.54 | 225.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2725.81 | 1086.52 | 1945.91 | 1428.72 | 517.18 | 0.00 | 0.00 |
February | 1972.31 | 1006.07 | 1536.96 | 951.13 | 585.83 | 0.00 | 0.00 |
March | 1460.20 | 1033.20 | 1225.42 | 596.84 | 628.58 | 0.00 | 0.00 |
April | 1146.18 | 820.76 | 1024.41 | 395.67 | 628.74 | 0.00 | 0.00 |
May | 689.70 | 725.91 | 721.76 | 87.11 | 634.65 | 0.00 | 0.00 |
June | 657.99 | 536.56 | 633.15 | 36.82 | 596.33 | 0.00 | 0.00 |
July | 772.00 | 450.70 | 667.64 | 71.00 | 596.64 | 0.00 | 0.00 |
August | 1061.61 | 479.32 | 857.59 | 266.17 | 591.42 | 0.00 | 0.00 |
September | 1582.60 | 587.76 | 1177.91 | 584.99 | 592.92 | 0.00 | 0.00 |
October | 2282.22 | 668.18 | 1543.03 | 1036.32 | 506.72 | 0.00 | 0.00 |
November | 2606.33 | 990.80 | 1874.62 | 1328.36 | 546.26 | 0.00 | 0.00 |
December | 2952.21 | 1093.03 | 2082.32 | 1586.90 | 495.41 | 0.00 | 0.00 |
Annual Sum or Average | 1658.28 | 788.74 | 1273.13 | 696.64 | 576.49 | 0.00 | 0.00 |
Minimum of Months | 657.99 | 450.70 | 633.15 | 36.82 | 495.41 | 0.00 | 0.00 |
Maximum of Months | 2952.21 | 1093.03 | 2082.32 | 1586.90 | 634.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3636.19 | 1428.40 | 2527.84 | 1855.99 | 671.85 | 0.00 | 0.00 |
February | 2625.65 | 1344.45 | 1996.60 | 1235.57 | 761.03 | 0.00 | 0.00 |
March | 1936.79 | 1397.00 | 1591.89 | 775.33 | 816.56 | 0.00 | 0.00 |
April | 1519.88 | 1108.11 | 1330.77 | 514.00 | 816.77 | 0.00 | 0.00 |
May | 903.27 | 995.15 | 937.61 | 113.16 | 824.45 | 0.00 | 0.00 |
June | 864.95 | 734.14 | 822.50 | 47.84 | 774.67 | 0.00 | 0.00 |
July | 1024.37 | 611.31 | 867.30 | 92.24 | 775.06 | 0.00 | 0.00 |
August | 1417.36 | 637.37 | 1114.06 | 345.77 | 768.29 | 0.00 | 0.00 |
September | 2114.44 | 774.25 | 1530.17 | 759.93 | 770.23 | 0.00 | 0.00 |
October | 3050.35 | 866.54 | 2004.49 | 1346.23 | 658.25 | 0.00 | 0.00 |
November | 3474.38 | 1303.59 | 2435.24 | 1725.62 | 709.62 | 0.00 | 0.00 |
December | 3938.42 | 1434.57 | 2705.05 | 2061.48 | 643.57 | 0.00 | 0.00 |
Annual Sum or Average | 2207.77 | 1051.31 | 1653.86 | 904.97 | 748.90 | 0.00 | 0.00 |
Minimum of Months | 864.95 | 611.31 | 822.50 | 47.84 | 643.57 | 0.00 | 0.00 |
Maximum of Months | 3938.42 | 1434.57 | 2705.05 | 2061.48 | 824.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 298.11 | 214.72 | 235.13 | 149.93 | 85.21 | 0.00 | 0.00 |
February | 265.81 | 195.96 | 225.67 | 121.17 | 104.50 | 0.00 | 0.00 |
March | 253.69 | 204.60 | 220.81 | 101.46 | 119.35 | 0.00 | 0.00 |
April | 322.56 | 155.86 | 257.75 | 124.41 | 133.34 | 0.00 | 0.00 |
May | 279.23 | 138.63 | 233.25 | 90.35 | 142.90 | 0.00 | 0.00 |
June | 309.73 | 97.58 | 237.83 | 99.18 | 138.65 | 0.00 | 0.00 |
July | 353.10 | 80.17 | 251.64 | 114.48 | 137.16 | 0.00 | 0.00 |
August | 358.92 | 84.45 | 252.33 | 122.74 | 129.58 | 0.00 | 0.00 |
September | 345.32 | 103.81 | 247.29 | 129.13 | 118.17 | 0.00 | 0.00 |
October | 347.09 | 119.03 | 234.67 | 141.95 | 92.72 | 0.00 | 0.00 |
November | 315.49 | 189.25 | 245.23 | 152.68 | 92.55 | 0.00 | 0.00 |
December | 317.64 | 212.78 | 246.07 | 164.75 | 81.32 | 0.00 | 0.00 |
Annual Sum or Average | 314.18 | 149.50 | 240.69 | 126.05 | 114.64 | 0.00 | 0.00 |
Minimum of Months | 253.69 | 80.17 | 220.81 | 90.35 | 81.32 | 0.00 | 0.00 |
Maximum of Months | 358.92 | 214.72 | 257.75 | 164.75 | 142.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 126.24 | 221.58 | 119.39 | 49.81 | 69.57 | 0.00 | 0.00 |
February | 145.46 | 198.38 | 143.84 | 54.53 | 89.31 | 0.00 | 0.00 |
March | 174.23 | 204.62 | 166.64 | 59.64 | 107.00 | 0.00 | 0.00 |
April | 271.25 | 156.10 | 222.68 | 96.98 | 125.70 | 0.00 | 0.00 |
May | 266.17 | 138.24 | 226.83 | 86.54 | 140.29 | 0.00 | 0.00 |
June | 304.52 | 101.08 | 240.27 | 101.21 | 139.06 | 0.00 | 0.00 |
July | 339.67 | 87.57 | 249.19 | 113.25 | 135.93 | 0.00 | 0.00 |
August | 319.66 | 92.29 | 229.10 | 104.91 | 124.19 | 0.00 | 0.00 |
September | 264.76 | 107.56 | 195.88 | 88.14 | 107.74 | 0.00 | 0.00 |
October | 215.45 | 123.92 | 151.23 | 69.34 | 81.89 | 0.00 | 0.00 |
November | 151.09 | 193.50 | 136.22 | 59.60 | 76.62 | 0.00 | 0.00 |
December | 128.99 | 220.63 | 119.35 | 53.56 | 65.79 | 0.00 | 0.00 |
Annual Sum or Average | 226.04 | 153.58 | 183.54 | 78.23 | 105.31 | 0.00 | 0.00 |
Minimum of Months | 126.24 | 87.57 | 119.35 | 49.81 | 65.79 | 0.00 | 0.00 |
Maximum of Months | 339.67 | 221.58 | 249.19 | 113.25 | 140.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 141.70 | 87.79 | 109.06 | 80.07 | 28.99 | 0.00 | 0.00 |
February | 98.13 | 84.36 | 86.14 | 53.31 | 32.83 | 0.00 | 0.00 |
March | 69.28 | 87.27 | 68.68 | 33.45 | 35.23 | 0.00 | 0.00 |
April | 51.24 | 71.88 | 57.41 | 22.18 | 35.24 | 0.00 | 0.00 |
May | 23.76 | 66.06 | 40.45 | 4.88 | 35.57 | 0.00 | 0.00 |
June | 21.36 | 52.28 | 35.49 | 2.06 | 33.42 | 0.00 | 0.00 |
July | 28.18 | 45.49 | 37.42 | 3.98 | 33.44 | 0.00 | 0.00 |
August | 45.84 | 47.65 | 48.06 | 14.92 | 33.15 | 0.00 | 0.00 |
September | 76.64 | 55.26 | 66.02 | 32.79 | 33.23 | 0.00 | 0.00 |
October | 117.09 | 59.18 | 86.48 | 58.08 | 28.40 | 0.00 | 0.00 |
November | 134.66 | 80.59 | 105.06 | 74.45 | 30.62 | 0.00 | 0.00 |
December | 154.55 | 87.42 | 116.70 | 88.94 | 27.77 | 0.00 | 0.00 |
Annual Sum or Average | 80.16 | 68.68 | 71.35 | 39.04 | 32.31 | 0.00 | 0.00 |
Minimum of Months | 21.36 | 45.49 | 35.49 | 2.06 | 27.77 | 0.00 | 0.00 |
Maximum of Months | 154.55 | 87.79 | 116.70 | 88.94 | 35.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.08 | 65.07 | 16.49 | 0.00 | 16.49 | 0.00 | 0.00 |
February | 11.36 | 58.50 | 20.69 | 0.00 | 20.69 | 0.00 | 0.00 |
March | 16.93 | 60.15 | 25.36 | 0.00 | 25.36 | 0.00 | 0.00 |
April | 25.58 | 43.76 | 29.37 | 0.23 | 29.14 | 0.00 | 0.00 |
May | 30.51 | 37.81 | 35.33 | 1.84 | 33.49 | 0.00 | 0.00 |
June | 38.39 | 27.00 | 37.45 | 3.69 | 33.76 | 0.00 | 0.00 |
July | 41.41 | 23.09 | 35.47 | 3.00 | 32.47 | 0.00 | 0.00 |
August | 35.95 | 24.54 | 29.50 | 0.65 | 28.84 | 0.00 | 0.00 |
September | 28.81 | 29.99 | 24.90 | 0.00 | 24.90 | 0.00 | 0.00 |
October | 25.77 | 35.08 | 19.75 | 0.00 | 19.75 | 0.00 | 0.00 |
November | 12.18 | 56.44 | 17.88 | 0.00 | 17.88 | 0.00 | 0.00 |
December | 9.32 | 64.80 | 15.35 | 0.00 | 15.35 | 0.00 | 0.00 |
Annual Sum or Average | 23.93 | 43.78 | 25.65 | 0.79 | 24.86 | 0.00 | 0.00 |
Minimum of Months | 9.32 | 23.09 | 15.35 | 0.00 | 15.35 | 0.00 | 0.00 |
Maximum of Months | 41.41 | 65.07 | 37.45 | 3.69 | 33.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 301.63 | 209.69 | 240.01 | 155.50 | 84.51 | 0.00 | 0.00 |
February | 247.23 | 190.25 | 217.08 | 116.70 | 100.38 | 0.00 | 0.00 |
March | 244.82 | 196.55 | 219.38 | 101.46 | 117.92 | 0.00 | 0.00 |
April | 293.53 | 149.85 | 241.96 | 113.12 | 128.85 | 0.00 | 0.00 |
May | 242.32 | 133.95 | 210.86 | 72.90 | 137.96 | 0.00 | 0.00 |
June | 257.04 | 96.59 | 203.84 | 71.81 | 132.03 | 0.00 | 0.00 |
July | 315.48 | 80.14 | 227.37 | 94.69 | 132.68 | 0.00 | 0.00 |
August | 336.99 | 82.45 | 238.59 | 113.52 | 125.07 | 0.00 | 0.00 |
September | 290.93 | 101.48 | 212.86 | 100.94 | 111.92 | 0.00 | 0.00 |
October | 325.35 | 114.54 | 222.97 | 131.56 | 91.41 | 0.00 | 0.00 |
November | 297.43 | 184.79 | 235.81 | 145.96 | 89.85 | 0.00 | 0.00 |
December | 313.87 | 208.49 | 246.32 | 167.16 | 79.16 | 0.00 | 0.00 |
Annual Sum or Average | 289.27 | 145.50 | 226.53 | 115.51 | 111.01 | 0.00 | 0.00 |
Minimum of Months | 242.32 | 80.14 | 203.84 | 71.81 | 79.16 | 0.00 | 0.00 |
Maximum of Months | 336.99 | 209.69 | 246.32 | 167.16 | 137.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.27 | 208.14 | 124.27 | 55.39 | 68.88 | 0.00 | 0.00 |
February | 124.05 | 188.78 | 135.25 | 50.05 | 85.20 | 0.00 | 0.00 |
March | 164.45 | 194.67 | 165.21 | 59.64 | 105.57 | 0.00 | 0.00 |
April | 244.46 | 148.59 | 206.89 | 85.69 | 121.20 | 0.00 | 0.00 |
May | 232.03 | 132.77 | 204.44 | 69.09 | 135.35 | 0.00 | 0.00 |
June | 254.94 | 97.17 | 206.27 | 73.84 | 132.43 | 0.00 | 0.00 |
July | 305.43 | 83.96 | 224.92 | 93.47 | 131.46 | 0.00 | 0.00 |
August | 300.31 | 87.35 | 215.36 | 95.68 | 119.68 | 0.00 | 0.00 |
September | 212.62 | 103.15 | 161.44 | 59.95 | 101.49 | 0.00 | 0.00 |
October | 192.70 | 116.27 | 139.53 | 58.95 | 80.59 | 0.00 | 0.00 |
November | 129.00 | 182.99 | 126.80 | 52.88 | 73.92 | 0.00 | 0.00 |
December | 116.79 | 206.86 | 119.59 | 55.96 | 63.63 | 0.00 | 0.00 |
Annual Sum or Average | 200.43 | 145.68 | 169.38 | 67.69 | 101.69 | 0.00 | 0.00 |
Minimum of Months | 116.79 | 83.96 | 119.59 | 50.05 | 63.63 | 0.00 | 0.00 |
Maximum of Months | 305.43 | 208.14 | 224.92 | 95.68 | 135.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 363.27 | 238.40 | 272.01 | 173.50 | 98.52 | 0.00 | 0.00 |
February | 275.86 | 219.84 | 231.47 | 115.50 | 115.97 | 0.00 | 0.00 |
March | 226.19 | 233.11 | 203.75 | 72.48 | 131.27 | 0.00 | 0.00 |
April | 211.05 | 172.45 | 188.03 | 48.56 | 139.47 | 0.00 | 0.00 |
May | 165.84 | 150.79 | 164.18 | 14.56 | 149.62 | 0.00 | 0.00 |
June | 182.13 | 101.92 | 158.01 | 12.47 | 145.54 | 0.00 | 0.00 |
July | 207.59 | 81.68 | 157.92 | 15.12 | 142.79 | 0.00 | 0.00 |
August | 231.36 | 86.20 | 168.04 | 33.73 | 134.30 | 0.00 | 0.00 |
September | 275.74 | 110.60 | 196.98 | 71.05 | 125.93 | 0.00 | 0.00 |
October | 354.76 | 126.21 | 230.16 | 125.84 | 104.32 | 0.00 | 0.00 |
November | 357.20 | 209.06 | 266.38 | 161.31 | 105.07 | 0.00 | 0.00 |
December | 389.54 | 235.93 | 286.11 | 192.70 | 93.41 | 0.00 | 0.00 |
Annual Sum or Average | 270.14 | 163.56 | 210.17 | 86.31 | 123.86 | 0.00 | 0.00 |
Minimum of Months | 165.84 | 81.68 | 157.92 | 12.47 | 93.41 | 0.00 | 0.00 |
Maximum of Months | 389.54 | 238.40 | 286.11 | 192.70 | 149.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 295.21 | 214.06 | 235.33 | 150.05 | 85.28 | 0.00 | 0.00 |
February | 261.93 | 195.47 | 225.86 | 121.27 | 104.58 | 0.00 | 0.00 |
March | 249.13 | 204.75 | 220.99 | 101.54 | 119.45 | 0.00 | 0.00 |
April | 315.76 | 156.58 | 257.96 | 124.51 | 133.45 | 0.00 | 0.00 |
May | 272.06 | 139.61 | 233.44 | 90.42 | 143.01 | 0.00 | 0.00 |
June | 301.81 | 98.76 | 238.02 | 99.26 | 138.77 | 0.00 | 0.00 |
July | 345.42 | 81.52 | 251.84 | 114.57 | 137.27 | 0.00 | 0.00 |
August | 351.78 | 85.98 | 252.53 | 122.84 | 129.69 | 0.00 | 0.00 |
September | 339.01 | 104.86 | 247.50 | 129.23 | 118.27 | 0.00 | 0.00 |
October | 342.33 | 119.78 | 234.86 | 142.07 | 92.79 | 0.00 | 0.00 |
November | 311.60 | 189.00 | 245.43 | 152.81 | 92.62 | 0.00 | 0.00 |
December | 314.78 | 211.92 | 246.28 | 164.89 | 81.39 | 0.00 | 0.00 |
Annual Sum or Average | 308.69 | 149.96 | 240.89 | 126.16 | 114.73 | 0.00 | 0.00 |
Minimum of Months | 249.13 | 81.52 | 220.99 | 90.42 | 81.39 | 0.00 | 0.00 |
Maximum of Months | 351.78 | 214.06 | 257.96 | 164.89 | 143.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 124.79 | 219.88 | 119.48 | 49.86 | 69.63 | 0.00 | 0.00 |
February | 142.99 | 197.19 | 143.96 | 54.57 | 89.39 | 0.00 | 0.00 |
March | 170.17 | 204.51 | 166.77 | 59.69 | 107.09 | 0.00 | 0.00 |
April | 263.57 | 157.80 | 222.86 | 97.06 | 125.80 | 0.00 | 0.00 |
May | 257.62 | 140.22 | 227.01 | 86.61 | 140.40 | 0.00 | 0.00 |
June | 293.66 | 105.17 | 240.46 | 101.29 | 139.17 | 0.00 | 0.00 |
July | 328.03 | 93.44 | 249.39 | 113.35 | 136.04 | 0.00 | 0.00 |
August | 309.46 | 98.30 | 229.29 | 104.99 | 124.30 | 0.00 | 0.00 |
September | 257.34 | 110.79 | 196.04 | 88.21 | 107.83 | 0.00 | 0.00 |
October | 210.86 | 126.12 | 151.36 | 69.39 | 81.96 | 0.00 | 0.00 |
November | 148.71 | 192.60 | 136.34 | 59.65 | 76.68 | 0.00 | 0.00 |
December | 127.89 | 218.59 | 119.44 | 53.60 | 65.84 | 0.00 | 0.00 |
Annual Sum or Average | 219.99 | 155.19 | 183.69 | 78.29 | 105.40 | 0.00 | 0.00 |
Minimum of Months | 124.79 | 93.44 | 119.44 | 49.86 | 65.84 | 0.00 | 0.00 |
Maximum of Months | 328.03 | 219.88 | 249.39 | 113.35 | 140.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.92 | 111.58 | 200.14 | 146.94 | 53.19 | 0.00 | 0.00 |
February | 199.68 | 102.33 | 158.08 | 97.82 | 60.25 | 0.00 | 0.00 |
March | 146.67 | 108.35 | 126.03 | 61.38 | 64.65 | 0.00 | 0.00 |
April | 115.46 | 82.26 | 105.36 | 40.69 | 64.67 | 0.00 | 0.00 |
May | 68.01 | 73.26 | 74.23 | 8.96 | 65.27 | 0.00 | 0.00 |
June | 65.91 | 51.37 | 65.12 | 3.79 | 61.33 | 0.00 | 0.00 |
July | 79.38 | 41.47 | 68.67 | 7.30 | 61.36 | 0.00 | 0.00 |
August | 109.91 | 43.56 | 88.20 | 27.38 | 60.83 | 0.00 | 0.00 |
September | 162.94 | 54.34 | 121.15 | 60.17 | 60.98 | 0.00 | 0.00 |
October | 237.09 | 61.44 | 158.70 | 106.58 | 52.12 | 0.00 | 0.00 |
November | 267.67 | 98.51 | 192.80 | 136.62 | 56.18 | 0.00 | 0.00 |
December | 303.79 | 110.68 | 214.17 | 163.21 | 50.95 | 0.00 | 0.00 |
Annual Sum or Average | 169.64 | 78.14 | 130.94 | 71.65 | 59.29 | 0.00 | 0.00 |
Minimum of Months | 65.91 | 41.47 | 65.12 | 3.79 | 50.95 | 0.00 | 0.00 |
Maximum of Months | 303.79 | 111.58 | 214.17 | 163.21 | 65.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 68.01 | 635.10 | 144.35 | 0.00 | 144.35 | 0.00 | 0.00 |
February | 74.79 | 592.55 | 181.19 | 0.00 | 181.19 | 0.00 | 0.00 |
March | 118.57 | 599.06 | 222.06 | 0.00 | 222.05 | 0.00 | 0.00 |
April | 186.51 | 448.68 | 257.16 | 2.05 | 255.11 | 0.00 | 0.00 |
May | 224.92 | 389.80 | 309.33 | 16.08 | 293.25 | 0.00 | 0.00 |
June | 294.74 | 282.94 | 327.87 | 32.32 | 295.55 | 0.00 | 0.00 |
July | 326.27 | 240.80 | 310.57 | 26.28 | 284.29 | 0.00 | 0.00 |
August | 282.63 | 261.57 | 258.25 | 5.71 | 252.55 | 0.00 | 0.00 |
September | 220.67 | 319.26 | 218.02 | 0.04 | 217.98 | 0.00 | 0.00 |
October | 197.75 | 366.71 | 172.93 | 0.00 | 172.93 | 0.00 | 0.00 |
November | 82.02 | 567.13 | 156.57 | 0.00 | 156.57 | 0.00 | 0.00 |
December | 61.63 | 636.39 | 134.37 | 0.00 | 134.37 | 0.00 | 0.00 |
Annual Sum or Average | 178.86 | 444.23 | 224.57 | 6.91 | 217.66 | 0.00 | 0.00 |
Minimum of Months | 61.63 | 240.80 | 134.37 | 0.00 | 134.37 | 0.00 | 0.00 |
Maximum of Months | 326.27 | 636.39 | 327.87 | 32.32 | 295.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 59.45 | 661.68 | 144.35 | 0.00 | 144.35 | 0.00 | 0.00 |
February | 65.05 | 619.00 | 181.19 | 0.00 | 181.19 | 0.00 | 0.00 |
March | 106.45 | 623.52 | 222.06 | 0.00 | 222.05 | 0.00 | 0.00 |
April | 171.11 | 467.80 | 257.16 | 2.05 | 255.11 | 0.00 | 0.00 |
May | 206.31 | 406.30 | 309.33 | 16.08 | 293.25 | 0.00 | 0.00 |
June | 274.36 | 296.46 | 327.87 | 32.32 | 295.55 | 0.00 | 0.00 |
July | 306.48 | 253.27 | 310.57 | 26.28 | 284.29 | 0.00 | 0.00 |
August | 265.32 | 276.14 | 258.25 | 5.71 | 252.55 | 0.00 | 0.00 |
September | 205.71 | 337.09 | 218.02 | 0.04 | 217.98 | 0.00 | 0.00 |
October | 184.86 | 386.11 | 172.93 | 0.00 | 172.93 | 0.00 | 0.00 |
November | 72.19 | 591.65 | 156.57 | 0.00 | 156.57 | 0.00 | 0.00 |
December | 53.62 | 663.12 | 134.37 | 0.00 | 134.37 | 0.00 | 0.00 |
Annual Sum or Average | 164.88 | 464.37 | 224.57 | 6.91 | 217.66 | 0.00 | 0.00 |
Minimum of Months | 53.62 | 253.27 | 134.37 | 0.00 | 134.37 | 0.00 | 0.00 |
Maximum of Months | 306.48 | 663.12 | 327.87 | 32.32 | 295.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 454.66 | 431.41 | 364.56 | 211.05 | 153.51 | 0.00 | 0.00 |
February | 393.10 | 420.30 | 352.61 | 166.88 | 185.73 | 0.00 | 0.00 |
March | 437.18 | 428.50 | 384.89 | 161.22 | 223.67 | 0.00 | 0.00 |
April | 582.60 | 332.74 | 449.20 | 198.96 | 250.24 | 0.00 | 0.00 |
May | 518.10 | 305.19 | 415.62 | 142.09 | 273.52 | 0.00 | 0.00 |
June | 567.17 | 226.96 | 410.42 | 145.76 | 264.67 | 0.00 | 0.00 |
July | 690.12 | 190.19 | 452.64 | 188.30 | 264.34 | 0.00 | 0.00 |
August | 703.58 | 196.64 | 454.29 | 209.35 | 244.94 | 0.00 | 0.00 |
September | 553.93 | 227.03 | 374.59 | 161.01 | 213.58 | 0.00 | 0.00 |
October | 563.90 | 253.15 | 362.79 | 190.66 | 172.13 | 0.00 | 0.00 |
November | 455.15 | 389.83 | 362.89 | 198.99 | 163.90 | 0.00 | 0.00 |
December | 459.25 | 430.64 | 366.20 | 223.30 | 142.90 | 0.00 | 0.00 |
Annual Sum or Average | 532.61 | 318.83 | 396.21 | 183.34 | 212.87 | 0.00 | 0.00 |
Minimum of Months | 393.10 | 190.19 | 352.61 | 142.09 | 142.90 | 0.00 | 0.00 |
Maximum of Months | 703.58 | 431.41 | 454.29 | 223.30 | 273.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 750.63 | 434.03 | 558.94 | 374.05 | 184.89 | 0.00 | 0.00 |
February | 555.26 | 403.24 | 464.50 | 249.01 | 215.49 | 0.00 | 0.00 |
March | 437.33 | 428.49 | 396.95 | 156.26 | 240.69 | 0.00 | 0.00 |
April | 384.56 | 322.69 | 356.36 | 104.29 | 252.06 | 0.00 | 0.00 |
May | 277.38 | 284.22 | 295.00 | 28.32 | 266.68 | 0.00 | 0.00 |
June | 293.34 | 198.69 | 278.16 | 20.72 | 257.44 | 0.00 | 0.00 |
July | 336.11 | 165.17 | 281.26 | 27.60 | 253.66 | 0.00 | 0.00 |
August | 398.26 | 175.99 | 313.05 | 71.64 | 241.41 | 0.00 | 0.00 |
September | 514.53 | 215.34 | 383.13 | 153.17 | 229.96 | 0.00 | 0.00 |
October | 690.76 | 244.61 | 463.26 | 271.32 | 191.94 | 0.00 | 0.00 |
November | 729.12 | 383.34 | 544.47 | 347.78 | 196.69 | 0.00 | 0.00 |
December | 808.16 | 429.13 | 591.23 | 415.47 | 175.77 | 0.00 | 0.00 |
Annual Sum or Average | 514.66 | 306.58 | 410.30 | 184.75 | 225.55 | 0.00 | 0.00 |
Minimum of Months | 277.38 | 165.17 | 278.16 | 20.72 | 175.77 | 0.00 | 0.00 |
Maximum of Months | 808.16 | 434.03 | 591.23 | 415.47 | 266.68 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.262765E+10 | 0.949423E+09 | 0.185087E+10 | 0.135894E+10 | 0.491925E+09 | 0.00 | 0.00 |
February | 0.172656E+10 | 0.780498E+09 | 0.132042E+10 | 0.817125E+09 | 0.503297E+09 | 0.00 | 0.00 |
March | 0.141944E+10 | 0.897931E+09 | 0.116557E+10 | 0.567687E+09 | 0.597878E+09 | 0.00 | 0.00 |
April | 0.108463E+10 | 0.673180E+09 | 0.942948E+09 | 0.364206E+09 | 0.578742E+09 | 0.00 | 0.00 |
May | 0.685938E+09 | 0.614821E+09 | 0.686508E+09 | 82855603.57 | 0.603653E+09 | 0.00 | 0.00 |
June | 0.636561E+09 | 0.427839E+09 | 0.582802E+09 | 33895534.00 | 0.548907E+09 | 0.00 | 0.00 |
July | 0.766694E+09 | 0.367528E+09 | 0.635032E+09 | 67536201.96 | 0.567496E+09 | 0.00 | 0.00 |
August | 0.103919E+10 | 0.389407E+09 | 0.815705E+09 | 0.253170E+09 | 0.562535E+09 | 0.00 | 0.00 |
September | 0.148348E+10 | 0.468128E+09 | 0.108424E+10 | 0.538468E+09 | 0.545767E+09 | 0.00 | 0.00 |
October | 0.220035E+10 | 0.559578E+09 | 0.146767E+10 | 0.985700E+09 | 0.481969E+09 | 0.00 | 0.00 |
November | 0.243679E+10 | 0.823463E+09 | 0.172555E+10 | 0.122273E+10 | 0.502820E+09 | 0.00 | 0.00 |
December | 0.284590E+10 | 0.952617E+09 | 0.198061E+10 | 0.150940E+10 | 0.471217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189532E+11 | 0.790441E+10 | 0.142579E+11 | 0.780170E+10 | 0.645621E+10 | 0.00 | 0.00 |
Minimum of Months | 0.636561E+09 | 0.367528E+09 | 0.582802E+09 | 33895534.00 | 0.471217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.284590E+10 | 0.952617E+09 | 0.198061E+10 | 0.150940E+10 | 0.603653E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.730081E+10 | 0.291014E+10 | 0.521191E+10 | 0.382669E+10 | 0.138523E+10 | 0.00 | 0.00 |
February | 0.477142E+10 | 0.243389E+10 | 0.371822E+10 | 0.230097E+10 | 0.141725E+10 | 0.00 | 0.00 |
March | 0.391099E+10 | 0.276731E+10 | 0.328216E+10 | 0.159857E+10 | 0.168359E+10 | 0.00 | 0.00 |
April | 0.297090E+10 | 0.212740E+10 | 0.265528E+10 | 0.102558E+10 | 0.162970E+10 | 0.00 | 0.00 |
May | 0.184731E+10 | 0.194428E+10 | 0.193316E+10 | 0.233316E+09 | 0.169985E+10 | 0.00 | 0.00 |
June | 0.170552E+10 | 0.139076E+10 | 0.164113E+10 | 95447588.87 | 0.154569E+10 | 0.00 | 0.00 |
July | 0.206773E+10 | 0.120716E+10 | 0.178821E+10 | 0.190177E+09 | 0.159803E+10 | 0.00 | 0.00 |
August | 0.284341E+10 | 0.128382E+10 | 0.229697E+10 | 0.712911E+09 | 0.158406E+10 | 0.00 | 0.00 |
September | 0.410210E+10 | 0.152347E+10 | 0.305313E+10 | 0.151629E+10 | 0.153684E+10 | 0.00 | 0.00 |
October | 0.611269E+10 | 0.178965E+10 | 0.413286E+10 | 0.277567E+10 | 0.135719E+10 | 0.00 | 0.00 |
November | 0.675561E+10 | 0.256816E+10 | 0.485902E+10 | 0.344311E+10 | 0.141591E+10 | 0.00 | 0.00 |
December | 0.790719E+10 | 0.292758E+10 | 0.557728E+10 | 0.425036E+10 | 0.132692E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.522957E+11 | 0.248736E+11 | 0.401493E+11 | 0.219691E+11 | 0.181803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.170552E+10 | 0.120716E+10 | 0.164113E+10 | 95447588.87 | 0.132692E+10 | 0.00 | 0.00 |
Maximum of Months | 0.790719E+10 | 0.292758E+10 | 0.557728E+10 | 0.425036E+10 | 0.169985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.973916E+10 | 0.382583E+10 | 0.677057E+10 | 0.497108E+10 | 0.179949E+10 | 0.00 | 0.00 |
February | 0.635198E+10 | 0.325250E+10 | 0.483018E+10 | 0.298909E+10 | 0.184109E+10 | 0.00 | 0.00 |
March | 0.518749E+10 | 0.374174E+10 | 0.426371E+10 | 0.207663E+10 | 0.218707E+10 | 0.00 | 0.00 |
April | 0.393954E+10 | 0.287221E+10 | 0.344936E+10 | 0.133229E+10 | 0.211707E+10 | 0.00 | 0.00 |
May | 0.241932E+10 | 0.266540E+10 | 0.251129E+10 | 0.303091E+09 | 0.220820E+10 | 0.00 | 0.00 |
June | 0.224195E+10 | 0.190289E+10 | 0.213192E+10 | 0.123992E+09 | 0.200793E+10 | 0.00 | 0.00 |
July | 0.274366E+10 | 0.163733E+10 | 0.232298E+10 | 0.247051E+09 | 0.207593E+10 | 0.00 | 0.00 |
August | 0.379625E+10 | 0.170713E+10 | 0.298390E+10 | 0.926112E+09 | 0.205779E+10 | 0.00 | 0.00 |
September | 0.548064E+10 | 0.200685E+10 | 0.396620E+10 | 0.196975E+10 | 0.199645E+10 | 0.00 | 0.00 |
October | 0.817006E+10 | 0.232094E+10 | 0.536882E+10 | 0.360575E+10 | 0.176307E+10 | 0.00 | 0.00 |
November | 0.900559E+10 | 0.337891E+10 | 0.631215E+10 | 0.447280E+10 | 0.183935E+10 | 0.00 | 0.00 |
December | 0.105487E+11 | 0.384234E+10 | 0.724520E+10 | 0.552146E+10 | 0.172374E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.696243E+11 | 0.331541E+11 | 0.521563E+11 | 0.285391E+11 | 0.236172E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224195E+10 | 0.163733E+10 | 0.213192E+10 | 0.123992E+09 | 0.172374E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105487E+11 | 0.384234E+10 | 0.724520E+10 | 0.552146E+10 | 0.220820E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.798469E+09 | 0.575107E+09 | 0.629779E+09 | 0.401562E+09 | 0.228218E+09 | 0.00 | 0.00 |
February | 0.643039E+09 | 0.474071E+09 | 0.545947E+09 | 0.293146E+09 | 0.252801E+09 | 0.00 | 0.00 |
March | 0.679492E+09 | 0.548004E+09 | 0.591405E+09 | 0.271742E+09 | 0.319663E+09 | 0.00 | 0.00 |
April | 0.836064E+09 | 0.403980E+09 | 0.668084E+09 | 0.322466E+09 | 0.345618E+09 | 0.00 | 0.00 |
May | 0.747888E+09 | 0.371295E+09 | 0.624730E+09 | 0.241994E+09 | 0.382735E+09 | 0.00 | 0.00 |
June | 0.802821E+09 | 0.252936E+09 | 0.616453E+09 | 0.257067E+09 | 0.359386E+09 | 0.00 | 0.00 |
July | 0.945746E+09 | 0.214729E+09 | 0.673982E+09 | 0.306615E+09 | 0.367367E+09 | 0.00 | 0.00 |
August | 0.961339E+09 | 0.226195E+09 | 0.675831E+09 | 0.328752E+09 | 0.347079E+09 | 0.00 | 0.00 |
September | 0.895075E+09 | 0.269071E+09 | 0.640987E+09 | 0.334692E+09 | 0.306295E+09 | 0.00 | 0.00 |
October | 0.929644E+09 | 0.318817E+09 | 0.628535E+09 | 0.380203E+09 | 0.248332E+09 | 0.00 | 0.00 |
November | 0.817759E+09 | 0.490524E+09 | 0.635637E+09 | 0.395756E+09 | 0.239881E+09 | 0.00 | 0.00 |
December | 0.850771E+09 | 0.569906E+09 | 0.659085E+09 | 0.441270E+09 | 0.217815E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.990811E+10 | 0.471463E+10 | 0.759045E+10 | 0.397526E+10 | 0.361519E+10 | 0.00 | 0.00 |
Minimum of Months | 0.643039E+09 | 0.214729E+09 | 0.545947E+09 | 0.241994E+09 | 0.217815E+09 | 0.00 | 0.00 |
Maximum of Months | 0.961339E+09 | 0.575107E+09 | 0.675831E+09 | 0.441270E+09 | 0.382735E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.338112E+09 | 0.593490E+09 | 0.319765E+09 | 0.133423E+09 | 0.186341E+09 | 0.00 | 0.00 |
February | 0.351905E+09 | 0.479915E+09 | 0.347980E+09 | 0.131915E+09 | 0.216064E+09 | 0.00 | 0.00 |
March | 0.466659E+09 | 0.548048E+09 | 0.446321E+09 | 0.159730E+09 | 0.286591E+09 | 0.00 | 0.00 |
April | 0.703089E+09 | 0.404610E+09 | 0.577175E+09 | 0.251363E+09 | 0.325813E+09 | 0.00 | 0.00 |
May | 0.712913E+09 | 0.370268E+09 | 0.607538E+09 | 0.231794E+09 | 0.375744E+09 | 0.00 | 0.00 |
June | 0.789315E+09 | 0.261993E+09 | 0.622769E+09 | 0.262337E+09 | 0.360433E+09 | 0.00 | 0.00 |
July | 0.909770E+09 | 0.234560E+09 | 0.667420E+09 | 0.303336E+09 | 0.364083E+09 | 0.00 | 0.00 |
August | 0.856180E+09 | 0.247203E+09 | 0.613618E+09 | 0.280979E+09 | 0.332639E+09 | 0.00 | 0.00 |
September | 0.686267E+09 | 0.278793E+09 | 0.507720E+09 | 0.228461E+09 | 0.279260E+09 | 0.00 | 0.00 |
October | 0.577050E+09 | 0.331913E+09 | 0.405058E+09 | 0.185711E+09 | 0.219347E+09 | 0.00 | 0.00 |
November | 0.391617E+09 | 0.501558E+09 | 0.353093E+09 | 0.154495E+09 | 0.198599E+09 | 0.00 | 0.00 |
December | 0.345481E+09 | 0.590945E+09 | 0.319656E+09 | 0.143444E+09 | 0.176212E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.712836E+10 | 0.484330E+10 | 0.578811E+10 | 0.246699E+10 | 0.332113E+10 | 0.00 | 0.00 |
Minimum of Months | 0.338112E+09 | 0.234560E+09 | 0.319656E+09 | 0.131915E+09 | 0.176212E+09 | 0.00 | 0.00 |
Maximum of Months | 0.909770E+09 | 0.593490E+09 | 0.667420E+09 | 0.303336E+09 | 0.375744E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.379523E+09 | 0.235124E+09 | 0.292103E+09 | 0.214468E+09 | 77635553.28 | 0.00 | 0.00 |
February | 0.237392E+09 | 0.204072E+09 | 0.208389E+09 | 0.128959E+09 | 79430304.49 | 0.00 | 0.00 |
March | 0.185550E+09 | 0.233738E+09 | 0.183949E+09 | 89592320.13 | 94357165.29 | 0.00 | 0.00 |
April | 0.132812E+09 | 0.186311E+09 | 0.148816E+09 | 57478930.01 | 91337075.93 | 0.00 | 0.00 |
May | 63646922.28 | 0.176944E+09 | 0.108345E+09 | 13076269.05 | 95268456.07 | 0.00 | 0.00 |
June | 55377538.77 | 0.135514E+09 | 91977834.87 | 5349392.23 | 86628442.64 | 0.00 | 0.00 |
July | 75473193.33 | 0.121830E+09 | 0.100221E+09 | 10658561.51 | 89562197.17 | 0.00 | 0.00 |
August | 0.122776E+09 | 0.127628E+09 | 0.128735E+09 | 39955329.25 | 88779244.96 | 0.00 | 0.00 |
September | 0.198659E+09 | 0.143230E+09 | 0.171114E+09 | 84981032.64 | 86132926.04 | 0.00 | 0.00 |
October | 0.313603E+09 | 0.158507E+09 | 0.231627E+09 | 0.155563E+09 | 76064301.16 | 0.00 | 0.00 |
November | 0.349039E+09 | 0.208897E+09 | 0.272326E+09 | 0.192970E+09 | 79355096.08 | 0.00 | 0.00 |
December | 0.413940E+09 | 0.234146E+09 | 0.312580E+09 | 0.238213E+09 | 74367526.37 | 0.00 | 0.00 |
Annual Sum or Average | 0.252779E+10 | 0.216594E+10 | 0.225018E+10 | 0.123126E+10 | 0.101892E+10 | 0.00 | 0.00 |
Minimum of Months | 55377538.77 | 0.121830E+09 | 91977834.87 | 5349392.23 | 74367526.37 | 0.00 | 0.00 |
Maximum of Months | 0.413940E+09 | 0.235124E+09 | 0.312580E+09 | 0.238213E+09 | 95268456.07 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26990771.46 | 0.174284E+09 | 44155780.40 | 0.00 | 44155780.40 | 0.00 | 0.00 |
February | 27474127.67 | 0.141525E+09 | 50063386.48 | 0.00 | 50063386.48 | 0.00 | 0.00 |
March | 45343103.99 | 0.161100E+09 | 67928039.34 | 603.17 | 67927436.17 | 0.00 | 0.00 |
April | 66299590.36 | 0.113421E+09 | 76129071.72 | 608034.59 | 75521037.12 | 0.00 | 0.00 |
May | 81714538.30 | 0.101272E+09 | 94625527.60 | 4919095.43 | 89706432.17 | 0.00 | 0.00 |
June | 99517415.48 | 69977307.43 | 97061928.37 | 9567351.92 | 87494576.45 | 0.00 | 0.00 |
July | 0.110913E+09 | 61844686.81 | 95003827.50 | 8038787.52 | 86965039.98 | 0.00 | 0.00 |
August | 96281718.87 | 65717033.10 | 79000722.41 | 1745290.87 | 77255431.54 | 0.00 | 0.00 |
September | 74677750.35 | 77722045.27 | 64542857.91 | 12542.38 | 64530315.53 | 0.00 | 0.00 |
October | 69014137.23 | 93958967.82 | 52898612.11 | 0.00 | 52898612.11 | 0.00 | 0.00 |
November | 31558320.88 | 0.146290E+09 | 46350880.95 | 0.00 | 46350880.95 | 0.00 | 0.00 |
December | 24959751.77 | 0.173573E+09 | 41105263.99 | 0.00 | 41105263.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.754744E+09 | 0.138068E+10 | 0.808866E+09 | 24891705.89 | 0.783974E+09 | 0.00 | 0.00 |
Minimum of Months | 24959751.77 | 61844686.81 | 41105263.99 | 0.00 | 41105263.99 | 0.00 | 0.00 |
Maximum of Months | 0.110913E+09 | 0.174284E+09 | 97061928.37 | 9567351.92 | 89706432.17 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.807889E+09 | 0.561622E+09 | 0.642851E+09 | 0.416487E+09 | 0.226364E+09 | 0.00 | 0.00 |
February | 0.598105E+09 | 0.460242E+09 | 0.525168E+09 | 0.282321E+09 | 0.242847E+09 | 0.00 | 0.00 |
March | 0.655727E+09 | 0.526431E+09 | 0.587588E+09 | 0.271751E+09 | 0.315837E+09 | 0.00 | 0.00 |
April | 0.760824E+09 | 0.388410E+09 | 0.627173E+09 | 0.293206E+09 | 0.333967E+09 | 0.00 | 0.00 |
May | 0.649018E+09 | 0.358762E+09 | 0.564763E+09 | 0.195246E+09 | 0.369517E+09 | 0.00 | 0.00 |
June | 0.666239E+09 | 0.250354E+09 | 0.528345E+09 | 0.186126E+09 | 0.342220E+09 | 0.00 | 0.00 |
July | 0.844983E+09 | 0.214642E+09 | 0.608991E+09 | 0.253618E+09 | 0.355373E+09 | 0.00 | 0.00 |
August | 0.902605E+09 | 0.220828E+09 | 0.639029E+09 | 0.304040E+09 | 0.334990E+09 | 0.00 | 0.00 |
September | 0.754086E+09 | 0.263044E+09 | 0.551729E+09 | 0.261625E+09 | 0.290104E+09 | 0.00 | 0.00 |
October | 0.871417E+09 | 0.306790E+09 | 0.597208E+09 | 0.352380E+09 | 0.244828E+09 | 0.00 | 0.00 |
November | 0.770935E+09 | 0.478976E+09 | 0.611213E+09 | 0.378322E+09 | 0.232891E+09 | 0.00 | 0.00 |
December | 0.840664E+09 | 0.558426E+09 | 0.659750E+09 | 0.447720E+09 | 0.212030E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.912249E+10 | 0.458853E+10 | 0.714381E+10 | 0.364284E+10 | 0.350097E+10 | 0.00 | 0.00 |
Minimum of Months | 0.598105E+09 | 0.214642E+09 | 0.525168E+09 | 0.186126E+09 | 0.212030E+09 | 0.00 | 0.00 |
Maximum of Months | 0.902605E+09 | 0.561622E+09 | 0.659750E+09 | 0.447720E+09 | 0.369517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.327500E+09 | 0.557485E+09 | 0.332836E+09 | 0.148349E+09 | 0.184488E+09 | 0.00 | 0.00 |
February | 0.300095E+09 | 0.456701E+09 | 0.327201E+09 | 0.121091E+09 | 0.206111E+09 | 0.00 | 0.00 |
March | 0.440464E+09 | 0.521411E+09 | 0.442504E+09 | 0.159739E+09 | 0.282765E+09 | 0.00 | 0.00 |
April | 0.633642E+09 | 0.385137E+09 | 0.536265E+09 | 0.222103E+09 | 0.314162E+09 | 0.00 | 0.00 |
May | 0.621465E+09 | 0.355600E+09 | 0.547572E+09 | 0.185046E+09 | 0.362526E+09 | 0.00 | 0.00 |
June | 0.660795E+09 | 0.251872E+09 | 0.534661E+09 | 0.191395E+09 | 0.343266E+09 | 0.00 | 0.00 |
July | 0.818073E+09 | 0.224871E+09 | 0.602429E+09 | 0.250339E+09 | 0.352090E+09 | 0.00 | 0.00 |
August | 0.804338E+09 | 0.233952E+09 | 0.576817E+09 | 0.256267E+09 | 0.320550E+09 | 0.00 | 0.00 |
September | 0.551121E+09 | 0.267356E+09 | 0.418462E+09 | 0.155393E+09 | 0.263069E+09 | 0.00 | 0.00 |
October | 0.516140E+09 | 0.311416E+09 | 0.373730E+09 | 0.157887E+09 | 0.215843E+09 | 0.00 | 0.00 |
November | 0.334359E+09 | 0.474321E+09 | 0.328669E+09 | 0.137061E+09 | 0.191609E+09 | 0.00 | 0.00 |
December | 0.312817E+09 | 0.554042E+09 | 0.320322E+09 | 0.149895E+09 | 0.170427E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.632081E+10 | 0.459416E+10 | 0.534147E+10 | 0.213456E+10 | 0.320690E+10 | 0.00 | 0.00 |
Minimum of Months | 0.300095E+09 | 0.224871E+09 | 0.320322E+09 | 0.121091E+09 | 0.170427E+09 | 0.00 | 0.00 |
Maximum of Months | 0.818073E+09 | 0.557485E+09 | 0.602429E+09 | 0.256267E+09 | 0.362526E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.972976E+09 | 0.638519E+09 | 0.728563E+09 | 0.464692E+09 | 0.263871E+09 | 0.00 | 0.00 |
February | 0.667355E+09 | 0.531848E+09 | 0.559975E+09 | 0.279417E+09 | 0.280557E+09 | 0.00 | 0.00 |
March | 0.605820E+09 | 0.624352E+09 | 0.545722E+09 | 0.194123E+09 | 0.351599E+09 | 0.00 | 0.00 |
April | 0.547052E+09 | 0.446994E+09 | 0.487364E+09 | 0.125858E+09 | 0.361506E+09 | 0.00 | 0.00 |
May | 0.444181E+09 | 0.403887E+09 | 0.439744E+09 | 38989048.81 | 0.400754E+09 | 0.00 | 0.00 |
June | 0.472094E+09 | 0.264169E+09 | 0.409559E+09 | 32316737.75 | 0.377242E+09 | 0.00 | 0.00 |
July | 0.556008E+09 | 0.218767E+09 | 0.422961E+09 | 40508848.09 | 0.382452E+09 | 0.00 | 0.00 |
August | 0.619667E+09 | 0.230891E+09 | 0.450074E+09 | 90352972.52 | 0.359721E+09 | 0.00 | 0.00 |
September | 0.714729E+09 | 0.286666E+09 | 0.510578E+09 | 0.184157E+09 | 0.326420E+09 | 0.00 | 0.00 |
October | 0.950179E+09 | 0.338053E+09 | 0.616468E+09 | 0.337062E+09 | 0.279406E+09 | 0.00 | 0.00 |
November | 0.925853E+09 | 0.541871E+09 | 0.690465E+09 | 0.418113E+09 | 0.272352E+09 | 0.00 | 0.00 |
December | 0.104335E+10 | 0.631923E+09 | 0.766322E+09 | 0.516141E+09 | 0.250182E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.851926E+10 | 0.515794E+10 | 0.662780E+10 | 0.272173E+10 | 0.390606E+10 | 0.00 | 0.00 |
Minimum of Months | 0.444181E+09 | 0.218767E+09 | 0.409559E+09 | 32316737.75 | 0.250182E+09 | 0.00 | 0.00 |
Maximum of Months | 0.104335E+10 | 0.638519E+09 | 0.766322E+09 | 0.516141E+09 | 0.400754E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.790688E+09 | 0.573337E+09 | 0.630296E+09 | 0.401891E+09 | 0.228405E+09 | 0.00 | 0.00 |
February | 0.633656E+09 | 0.472886E+09 | 0.546395E+09 | 0.293386E+09 | 0.253008E+09 | 0.00 | 0.00 |
March | 0.667283E+09 | 0.548407E+09 | 0.591890E+09 | 0.271965E+09 | 0.319925E+09 | 0.00 | 0.00 |
April | 0.818439E+09 | 0.405845E+09 | 0.668632E+09 | 0.322730E+09 | 0.345902E+09 | 0.00 | 0.00 |
May | 0.728683E+09 | 0.373940E+09 | 0.625242E+09 | 0.242193E+09 | 0.383049E+09 | 0.00 | 0.00 |
June | 0.782295E+09 | 0.255974E+09 | 0.616959E+09 | 0.257278E+09 | 0.359681E+09 | 0.00 | 0.00 |
July | 0.925180E+09 | 0.218334E+09 | 0.674534E+09 | 0.306866E+09 | 0.367668E+09 | 0.00 | 0.00 |
August | 0.942216E+09 | 0.230289E+09 | 0.676385E+09 | 0.329022E+09 | 0.347363E+09 | 0.00 | 0.00 |
September | 0.878718E+09 | 0.271794E+09 | 0.641513E+09 | 0.334967E+09 | 0.306546E+09 | 0.00 | 0.00 |
October | 0.916900E+09 | 0.320811E+09 | 0.629051E+09 | 0.380515E+09 | 0.248536E+09 | 0.00 | 0.00 |
November | 0.807657E+09 | 0.489888E+09 | 0.636158E+09 | 0.396080E+09 | 0.240078E+09 | 0.00 | 0.00 |
December | 0.843098E+09 | 0.567597E+09 | 0.659625E+09 | 0.441632E+09 | 0.217994E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.973481E+10 | 0.472910E+10 | 0.759668E+10 | 0.397853E+10 | 0.361816E+10 | 0.00 | 0.00 |
Minimum of Months | 0.633656E+09 | 0.218334E+09 | 0.546395E+09 | 0.242193E+09 | 0.217994E+09 | 0.00 | 0.00 |
Maximum of Months | 0.942216E+09 | 0.573337E+09 | 0.676385E+09 | 0.441632E+09 | 0.383049E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.334244E+09 | 0.588915E+09 | 0.320027E+09 | 0.133533E+09 | 0.186494E+09 | 0.00 | 0.00 |
February | 0.345918E+09 | 0.477032E+09 | 0.348265E+09 | 0.132024E+09 | 0.216242E+09 | 0.00 | 0.00 |
March | 0.455777E+09 | 0.547768E+09 | 0.446687E+09 | 0.159861E+09 | 0.286826E+09 | 0.00 | 0.00 |
April | 0.683169E+09 | 0.409024E+09 | 0.577649E+09 | 0.251569E+09 | 0.326080E+09 | 0.00 | 0.00 |
May | 0.689998E+09 | 0.375561E+09 | 0.608037E+09 | 0.231984E+09 | 0.376053E+09 | 0.00 | 0.00 |
June | 0.761172E+09 | 0.272597E+09 | 0.623280E+09 | 0.262552E+09 | 0.360728E+09 | 0.00 | 0.00 |
July | 0.878585E+09 | 0.250271E+09 | 0.667967E+09 | 0.303585E+09 | 0.364382E+09 | 0.00 | 0.00 |
August | 0.828864E+09 | 0.263285E+09 | 0.614122E+09 | 0.281210E+09 | 0.332912E+09 | 0.00 | 0.00 |
September | 0.667031E+09 | 0.287160E+09 | 0.508137E+09 | 0.228648E+09 | 0.279489E+09 | 0.00 | 0.00 |
October | 0.564773E+09 | 0.337794E+09 | 0.405390E+09 | 0.185863E+09 | 0.219527E+09 | 0.00 | 0.00 |
November | 0.385448E+09 | 0.499214E+09 | 0.353383E+09 | 0.154621E+09 | 0.198762E+09 | 0.00 | 0.00 |
December | 0.342540E+09 | 0.585482E+09 | 0.319918E+09 | 0.143562E+09 | 0.176356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.693752E+10 | 0.489410E+10 | 0.579286E+10 | 0.246901E+10 | 0.332385E+10 | 0.00 | 0.00 |
Minimum of Months | 0.334244E+09 | 0.250271E+09 | 0.319918E+09 | 0.132024E+09 | 0.176356E+09 | 0.00 | 0.00 |
Maximum of Months | 0.878585E+09 | 0.588915E+09 | 0.667967E+09 | 0.303585E+09 | 0.376053E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.749743E+09 | 0.298868E+09 | 0.536043E+09 | 0.393573E+09 | 0.142470E+09 | 0.00 | 0.00 |
February | 0.483069E+09 | 0.247555E+09 | 0.382417E+09 | 0.236654E+09 | 0.145764E+09 | 0.00 | 0.00 |
March | 0.392830E+09 | 0.290197E+09 | 0.337568E+09 | 0.164412E+09 | 0.173156E+09 | 0.00 | 0.00 |
April | 0.299263E+09 | 0.213212E+09 | 0.273094E+09 | 0.105480E+09 | 0.167614E+09 | 0.00 | 0.00 |
May | 0.182163E+09 | 0.196217E+09 | 0.198825E+09 | 23996440.96 | 0.174828E+09 | 0.00 | 0.00 |
June | 0.170850E+09 | 0.133161E+09 | 0.168790E+09 | 9816743.17 | 0.158973E+09 | 0.00 | 0.00 |
July | 0.212617E+09 | 0.111071E+09 | 0.183916E+09 | 19559672.65 | 0.164357E+09 | 0.00 | 0.00 |
August | 0.294372E+09 | 0.116661E+09 | 0.236243E+09 | 73322573.59 | 0.162920E+09 | 0.00 | 0.00 |
September | 0.422335E+09 | 0.140844E+09 | 0.314014E+09 | 0.155950E+09 | 0.158064E+09 | 0.00 | 0.00 |
October | 0.635011E+09 | 0.164568E+09 | 0.425063E+09 | 0.285476E+09 | 0.139587E+09 | 0.00 | 0.00 |
November | 0.693789E+09 | 0.255339E+09 | 0.499748E+09 | 0.354123E+09 | 0.145626E+09 | 0.00 | 0.00 |
December | 0.813670E+09 | 0.296447E+09 | 0.573620E+09 | 0.437148E+09 | 0.136473E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.534971E+10 | 0.246414E+10 | 0.412934E+10 | 0.225951E+10 | 0.186983E+10 | 0.00 | 0.00 |
Minimum of Months | 0.170850E+09 | 0.111071E+09 | 0.168790E+09 | 9816743.17 | 0.136473E+09 | 0.00 | 0.00 |
Maximum of Months | 0.813670E+09 | 0.298868E+09 | 0.573620E+09 | 0.437148E+09 | 0.174828E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.182152E+09 | 0.170105E+10 | 0.386614E+09 | 0.00 | 0.386614E+09 | 0.00 | 0.00 |
February | 0.180935E+09 | 0.143349E+10 | 0.438339E+09 | 0.00 | 0.438339E+09 | 0.00 | 0.00 |
March | 0.317572E+09 | 0.160453E+10 | 0.594757E+09 | 5281.20 | 0.594751E+09 | 0.00 | 0.00 |
April | 0.483444E+09 | 0.116299E+10 | 0.666562E+09 | 5323759.83 | 0.661238E+09 | 0.00 | 0.00 |
May | 0.602419E+09 | 0.104404E+10 | 0.828511E+09 | 43070053.68 | 0.785441E+09 | 0.00 | 0.00 |
June | 0.763964E+09 | 0.733374E+09 | 0.849844E+09 | 83768726.79 | 0.766075E+09 | 0.00 | 0.00 |
July | 0.873880E+09 | 0.644956E+09 | 0.831824E+09 | 70385097.24 | 0.761439E+09 | 0.00 | 0.00 |
August | 0.757009E+09 | 0.700586E+09 | 0.691705E+09 | 15281218.34 | 0.676424E+09 | 0.00 | 0.00 |
September | 0.571967E+09 | 0.827518E+09 | 0.565117E+09 | 109817.17 | 0.565007E+09 | 0.00 | 0.00 |
October | 0.529644E+09 | 0.982195E+09 | 0.463164E+09 | 0.00 | 0.463164E+09 | 0.00 | 0.00 |
November | 0.212599E+09 | 0.147000E+10 | 0.405834E+09 | 0.00 | 0.405834E+09 | 0.00 | 0.00 |
December | 0.165080E+09 | 0.170450E+10 | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.564067E+10 | 0.140092E+11 | 0.708218E+10 | 0.217944E+09 | 0.686423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.165080E+09 | 0.644956E+09 | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.00 | 0.00 |
Maximum of Months | 0.873880E+09 | 0.170450E+10 | 0.849844E+09 | 83768726.79 | 0.785441E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.159238E+09 | 0.177225E+10 | 0.386614E+09 | 0.00 | 0.386614E+09 | 0.00 | 0.00 |
February | 0.157371E+09 | 0.149749E+10 | 0.438339E+09 | 0.00 | 0.438339E+09 | 0.00 | 0.00 |
March | 0.285114E+09 | 0.167004E+10 | 0.594757E+09 | 5281.20 | 0.594751E+09 | 0.00 | 0.00 |
April | 0.443520E+09 | 0.121254E+10 | 0.666562E+09 | 5323759.83 | 0.661238E+09 | 0.00 | 0.00 |
May | 0.552585E+09 | 0.108823E+10 | 0.828511E+09 | 43070053.68 | 0.785441E+09 | 0.00 | 0.00 |
June | 0.711153E+09 | 0.768417E+09 | 0.849844E+09 | 83768726.79 | 0.766075E+09 | 0.00 | 0.00 |
July | 0.820880E+09 | 0.678369E+09 | 0.831824E+09 | 70385097.24 | 0.761439E+09 | 0.00 | 0.00 |
August | 0.710640E+09 | 0.739626E+09 | 0.691705E+09 | 15281218.34 | 0.676424E+09 | 0.00 | 0.00 |
September | 0.533207E+09 | 0.873749E+09 | 0.565117E+09 | 109817.17 | 0.565007E+09 | 0.00 | 0.00 |
October | 0.495141E+09 | 0.103415E+10 | 0.463164E+09 | 0.00 | 0.463164E+09 | 0.00 | 0.00 |
November | 0.187121E+09 | 0.153356E+10 | 0.405834E+09 | 0.00 | 0.405834E+09 | 0.00 | 0.00 |
December | 0.143613E+09 | 0.177610E+10 | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.519958E+10 | 0.146445E+11 | 0.708218E+10 | 0.217944E+09 | 0.686423E+10 | 0.00 | 0.00 |
Minimum of Months | 0.143613E+09 | 0.678369E+09 | 0.359905E+09 | 0.00 | 0.359905E+09 | 0.00 | 0.00 |
Maximum of Months | 0.820880E+09 | 0.177610E+10 | 0.849844E+09 | 83768726.79 | 0.785441E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121775E+10 | 0.115550E+10 | 0.976448E+09 | 0.565278E+09 | 0.411170E+09 | 0.00 | 0.00 |
February | 0.950992E+09 | 0.101679E+10 | 0.853032E+09 | 0.403725E+09 | 0.449306E+09 | 0.00 | 0.00 |
March | 0.117093E+10 | 0.114769E+10 | 0.103089E+10 | 0.431822E+09 | 0.599065E+09 | 0.00 | 0.00 |
April | 0.151011E+10 | 0.862462E+09 | 0.116433E+10 | 0.515700E+09 | 0.648629E+09 | 0.00 | 0.00 |
May | 0.138768E+10 | 0.817426E+09 | 0.111319E+10 | 0.380578E+09 | 0.732609E+09 | 0.00 | 0.00 |
June | 0.147009E+10 | 0.588280E+09 | 0.106382E+10 | 0.377805E+09 | 0.686015E+09 | 0.00 | 0.00 |
July | 0.184841E+10 | 0.509407E+09 | 0.121234E+10 | 0.504336E+09 | 0.708009E+09 | 0.00 | 0.00 |
August | 0.188447E+10 | 0.526688E+09 | 0.121678E+10 | 0.560730E+09 | 0.656046E+09 | 0.00 | 0.00 |
September | 0.143579E+10 | 0.588472E+09 | 0.970939E+09 | 0.417338E+09 | 0.553601E+09 | 0.00 | 0.00 |
October | 0.151036E+10 | 0.678028E+09 | 0.971691E+09 | 0.510663E+09 | 0.461028E+09 | 0.00 | 0.00 |
November | 0.117975E+10 | 0.101045E+10 | 0.940615E+09 | 0.515786E+09 | 0.424829E+09 | 0.00 | 0.00 |
December | 0.123007E+10 | 0.115342E+10 | 0.980838E+09 | 0.598084E+09 | 0.382753E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.167964E+11 | 0.100546E+11 | 0.124949E+11 | 0.578185E+10 | 0.671306E+10 | 0.00 | 0.00 |
Minimum of Months | 0.950992E+09 | 0.509407E+09 | 0.853032E+09 | 0.377805E+09 | 0.382753E+09 | 0.00 | 0.00 |
Maximum of Months | 0.188447E+10 | 0.115550E+10 | 0.121678E+10 | 0.598084E+09 | 0.732609E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.201050E+10 | 0.116252E+10 | 0.149706E+10 | 0.100186E+10 | 0.495197E+09 | 0.00 | 0.00 |
February | 0.134327E+10 | 0.975522E+09 | 0.112373E+10 | 0.602415E+09 | 0.521313E+09 | 0.00 | 0.00 |
March | 0.117134E+10 | 0.114767E+10 | 0.106318E+10 | 0.418522E+09 | 0.644660E+09 | 0.00 | 0.00 |
April | 0.996790E+09 | 0.836425E+09 | 0.923675E+09 | 0.270331E+09 | 0.653344E+09 | 0.00 | 0.00 |
May | 0.742930E+09 | 0.761263E+09 | 0.790135E+09 | 75848714.34 | 0.714286E+09 | 0.00 | 0.00 |
June | 0.760327E+09 | 0.514995E+09 | 0.720991E+09 | 53705124.71 | 0.667286E+09 | 0.00 | 0.00 |
July | 0.900240E+09 | 0.442381E+09 | 0.753320E+09 | 73918335.13 | 0.679402E+09 | 0.00 | 0.00 |
August | 0.106670E+10 | 0.471360E+09 | 0.838486E+09 | 0.191885E+09 | 0.646601E+09 | 0.00 | 0.00 |
September | 0.133366E+10 | 0.558153E+09 | 0.993061E+09 | 0.397016E+09 | 0.596045E+09 | 0.00 | 0.00 |
October | 0.185012E+10 | 0.655153E+09 | 0.124079E+10 | 0.726695E+09 | 0.514099E+09 | 0.00 | 0.00 |
November | 0.188989E+10 | 0.993610E+09 | 0.141126E+10 | 0.901438E+09 | 0.509818E+09 | 0.00 | 0.00 |
December | 0.216456E+10 | 0.114939E+10 | 0.158356E+10 | 0.111278E+10 | 0.470775E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.162303E+11 | 0.966843E+10 | 0.129392E+11 | 0.582642E+10 | 0.711283E+10 | 0.00 | 0.00 |
Minimum of Months | 0.742930E+09 | 0.442381E+09 | 0.720991E+09 | 53705124.71 | 0.470775E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216456E+10 | 0.116252E+10 | 0.158356E+10 | 0.111278E+10 | 0.714286E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.60 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.19 | 7.03 | 3.12 | 2.95 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.60 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.61 | 10.61 | 2.62 | 4.75 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.64 | 10.56 | 2.92 | 6.16 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.02 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.75 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.61 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.49 | 13.65 | 2.19 | 8.98 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.71 | 9.60 | 2.71 | 7.73 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.42 | 6.22 | 2.47 | 2.40 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.80 | 3.19 | 2.50 | 0.04 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.75 | 10.02 | 2.59 | 5.48 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.80 | 3.19 | 2.19 | 0.04 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.44 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.65 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.80 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.11 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.03 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.58 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.48 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.18 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.88 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.83 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.94 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.06 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.06 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.18 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.2 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.20 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.32 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.55 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.53 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.2 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.02 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.40 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.31 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.58 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.18 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.18 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.84 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.08 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.63 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.63 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.84 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.84 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.33 | 3.77 | 8.01 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.02 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.46 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.91 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.63 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.91 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.304303E+11 | -.607882E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.152870E+10 | 59.15 | 0.00 | 0.00 |
February | 0.275532E+11 | -.549540E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.139343E+10 | 59.11 | 0.00 | 0.00 |
March | 0.298945E+11 | -.602630E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.155551E+10 | 59.19 | 0.00 | 0.00 |
April | 0.276004E+11 | -.570767E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.151522E+10 | 59.23 | 0.00 | 0.00 |
May | 0.269406E+11 | -.575056E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157268E+10 | 59.32 | 0.00 | 0.00 |
June | 0.247003E+11 | -.543671E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.153411E+10 | 59.37 | 0.00 | 0.00 |
July | 0.245497E+11 | -.552794E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.158115E+10 | 59.35 | 0.00 | 0.00 |
August | 0.245206E+11 | -.552535E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.157952E+10 | 59.36 | 0.00 | 0.00 |
September | 0.244081E+11 | -.541181E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.151216E+10 | 59.41 | 0.00 | 0.00 |
October | 0.265436E+11 | -.571634E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154664E+10 | 59.32 | 0.00 | 0.00 |
November | 0.272293E+11 | -.567739E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.147323E+10 | 59.31 | 0.00 | 0.00 |
December | 0.295556E+11 | -.599762E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.152769E+10 | 59.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.323926E+12 | -.683519E+12 | 8760.00 | -.183200E+11 | 59.28 | |||||
Minimum of Months | 0.244081E+11 | -.607882E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.158115E+10 | 59.11 | 0.00 | 0.00 |
Maximum of Months | 0.304303E+11 | -.541181E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.139343E+10 | 59.41 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770532E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162539326.6 | 81.21 | 0.00 | 0.00 |
February | 0.696247E+10 | -.681597E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146492811.6 | 81.21 | 0.00 | 0.00 |
March | 0.770513E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162317426.7 | 81.21 | 0.00 | 0.00 |
April | 0.746549E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156899717.5 | 81.21 | 0.00 | 0.00 |
May | 0.770497E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162178375.1 | 81.21 | 0.00 | 0.00 |
June | 0.745767E+10 | -.730053E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157135841.8 | 81.21 | 0.00 | 0.00 |
July | 0.771337E+10 | -.755084E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162528438.0 | 81.21 | 0.00 | 0.00 |
August | 0.770535E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162550801.0 | 81.21 | 0.00 | 0.00 |
September | 0.746585E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157258156.6 | 81.21 | 0.00 | 0.00 |
October | 0.770524E+10 | -.754278E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162459086.1 | 81.21 | 0.00 | 0.00 |
November | 0.744940E+10 | -.729243E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156973165.5 | 81.21 | 0.00 | 0.00 |
December | 0.771331E+10 | -.755086E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162448949.3 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907536E+11 | -.888418E+11 | 8760.00 | -.191178E+10 | 81.21 | |||||
Minimum of Months | 0.696247E+10 | -.755086E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -162550801.0 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771337E+10 | -.681597E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -146492811.6 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.776141E+11 | -.763253E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128875E+10 | 65.32 | 0.00 | 0.00 |
February | 0.701118E+11 | -.689387E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.117310E+10 | 65.28 | 0.00 | 0.00 |
March | 0.775530E+11 | -.762438E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.130919E+10 | 65.40 | 0.00 | 0.00 |
April | 0.749374E+11 | -.736557E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.128163E+10 | 65.70 | 0.00 | 0.00 |
May | 0.772848E+11 | -.759481E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.133669E+10 | 66.02 | 0.00 | 0.00 |
June | 0.746635E+11 | -.733541E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.130935E+10 | 66.32 | 0.00 | 0.00 |
July | 0.770708E+11 | -.757147E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.135601E+10 | 66.50 | 0.00 | 0.00 |
August | 0.770604E+11 | -.757053E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.135505E+10 | 66.52 | 0.00 | 0.00 |
September | 0.746381E+11 | -.733443E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.129386E+10 | 66.37 | 0.00 | 0.00 |
October | 0.772507E+11 | -.759308E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.131987E+10 | 66.09 | 0.00 | 0.00 |
November | 0.749002E+11 | -.736485E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.125172E+10 | 65.79 | 0.00 | 0.00 |
December | 0.775331E+11 | -.762422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129087E+10 | 65.47 | 0.00 | 0.00 |
Annual Sum or Average | 0.910618E+12 | -.895052E+12 | 8760.00 | -.155661E+11 | 65.90 | |||||
Minimum of Months | 0.701118E+11 | -.763253E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.135601E+10 | 65.28 | 0.00 | 0.00 |
Maximum of Months | 0.776141E+11 | -.689387E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117310E+10 | 66.52 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.87 | 0.86 | 01-JAN-07:30 | 7034.29 | 37.51 | 285.00 | 281.50 | 1014.27 | 27.15 | 208.50 | 265.00 |
February | 279.67 | 0.87 | 0.86 | 01-FEB-07:30 | 4892.93 | 32.23 | 218.50 | 276.83 | 670.26 | 23.85 | 186.00 | 247.67 |
March | 338.17 | 0.87 | 0.86 | 01-MAR-07:40 | 1284.77 | 20.00 | 18.00 | 322.67 | 479.66 | 21.27 | 185.00 | 268.33 |
April | 358.33 | 0.87 | 0.86 | 01-APR-07:19 | 883.85 | 19.50 | 0.00 | 335.17 | 373.39 | 21.27 | 207.33 | 274.83 |
May | 393.83 | 0.88 | 0.86 | 01-MAY-06:00 | 802.90 | 19.00 | 0.00 | 367.83 | 327.49 | 20.75 | 159.17 | 280.50 |
June | 381.00 | 0.88 | 0.86 | 01-JUN-07:10 | 694.39 | 18.81 | 0.00 | 360.33 | 292.73 | 20.57 | 122.83 | 261.00 |
July | 408.67 | 0.88 | 0.86 | 01-JUL-07:00 | 684.05 | 18.93 | 0.00 | 369.83 | 298.84 | 20.70 | 171.33 | 280.00 |
August | 390.67 | 0.88 | 0.86 | 01-AUG-07:40 | 743.97 | 19.18 | 0.00 | 356.00 | 324.49 | 20.95 | 183.17 | 283.00 |
September | 328.83 | 0.87 | 0.86 | 01-SEP-07:10 | 999.41 | 19.49 | 0.17 | 311.00 | 416.64 | 21.28 | 180.00 | 261.17 |
October | 296.17 | 0.87 | 0.86 | 01-OCT-09:39 | 3375.41 | 27.30 | 136.83 | 307.33 | 493.12 | 21.79 | 125.67 | 256.83 |
November | 300.00 | 0.87 | 0.86 | 01-NOV-06:49 | 6848.35 | 37.34 | 295.17 | 281.67 | 889.40 | 26.72 | 224.33 | 269.67 |
December | 297.00 | 0.87 | 0.86 | 01-DEC-07:19 | 6883.40 | 37.92 | 289.17 | 282.17 | 1243.03 | 28.69 | 199.33 | 267.83 |
Annual Sum or Average | 4065.67 | 0.87 | 2646.83 | 24.75 | 1242.83 | 3852.33 | 538.52 | 22.65 | 2152.67 | 3215.83 | ||
Minimum of Months | 279.67 | 0.87 | 0.86 | 684.05 | 18.81 | 0.00 | 276.83 | 292.73 | 20.57 | 122.83 | 247.67 | |
Maximum of Months | 408.67 | 0.88 | 0.86 | 7034.29 | 37.92 | 295.17 | 369.83 | 1243.03 | 28.69 | 224.33 | 283.00 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.25 | 0.22 | 01-JAN-07:19 | 7445.13 | 37.58 | 285.00 | 288.33 | 1427.04 | 26.83 | 182.67 | 276.00 |
February | 279.67 | 0.25 | 0.22 | 01-FEB-07:19 | 5219.14 | 32.32 | 218.83 | 283.17 | 996.01 | 23.87 | 181.00 | 266.33 |
March | 338.17 | 0.28 | 0.22 | 01-MAR-07:10 | 1536.39 | 20.43 | 41.67 | 331.67 | 730.30 | 21.54 | 204.33 | 303.83 |
April | 358.33 | 0.26 | 0.22 | 01-APR-06:40 | 1086.86 | 20.06 | 37.50 | 348.00 | 575.89 | 21.62 | 224.67 | 318.00 |
May | 393.83 | 0.27 | 0.22 | 01-MAY-06:30 | 946.49 | 19.80 | 5.17 | 381.33 | 470.55 | 21.33 | 248.00 | 346.17 |
June | 381.00 | 0.28 | 0.22 | 01-JUN-06:40 | 823.64 | 19.66 | 0.00 | 372.50 | 421.54 | 21.19 | 244.00 | 336.67 |
July | 408.67 | 0.28 | 0.22 | 01-JUL-06:10 | 820.62 | 19.72 | 0.50 | 380.33 | 434.99 | 21.27 | 302.50 | 350.50 |
August | 390.67 | 0.28 | 0.22 | 01-AUG-07:10 | 913.61 | 19.83 | 11.50 | 368.50 | 493.69 | 21.39 | 249.00 | 339.83 |
September | 328.83 | 0.27 | 0.22 | 01-SEP-06:49 | 1242.04 | 19.92 | 36.67 | 324.17 | 658.67 | 21.52 | 190.17 | 295.67 |
October | 296.17 | 0.26 | 0.22 | 01-OCT-09:39 | 3708.46 | 27.31 | 138.17 | 318.17 | 823.96 | 21.70 | 121.67 | 286.50 |
November | 300.00 | 0.26 | 0.22 | 01-NOV-06:40 | 7235.00 | 37.40 | 295.17 | 286.17 | 1273.16 | 26.46 | 202.17 | 277.67 |
December | 297.00 | 0.26 | 0.22 | 01-DEC-07:10 | 7311.02 | 38.00 | 289.33 | 287.83 | 1669.88 | 28.32 | 177.00 | 277.67 |
Annual Sum or Average | 4065.67 | 0.27 | 2897.43 | 25.19 | 1359.50 | 3970.17 | 788.44 | 22.86 | 2527.17 | 3674.83 | ||
Minimum of Months | 279.67 | 0.25 | 0.22 | 820.62 | 19.66 | 0.00 | 283.17 | 421.54 | 21.19 | 121.67 | 266.33 | |
Maximum of Months | 408.67 | 0.28 | 0.22 | 7445.13 | 38.00 | 295.17 | 381.33 | 1669.88 | 28.32 | 302.50 | 350.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.70 | 0.60 | 01-JAN-09:20 | 330.66 | 14.69 | 0.00 | 246.50 | 171.18 | 18.25 | 0.00 | 64.00 |
February | 279.67 | 0.67 | 0.60 | 01-FEB-10:30 | 413.53 | 15.55 | 0.00 | 259.00 | 198.41 | 18.88 | 0.00 | 129.67 |
March | 338.17 | 0.65 | 0.60 | 01-MAR-10:30 | 495.21 | 16.11 | 0.00 | 317.67 | 227.52 | 19.32 | 0.00 | 228.67 |
April | 358.33 | 0.63 | 0.60 | 01-APR-07:00 | 521.80 | 17.04 | 0.00 | 346.00 | 255.45 | 20.30 | 32.33 | 297.50 |
May | 393.83 | 0.62 | 0.60 | 01-MAY-06:40 | 701.54 | 17.98 | 12.50 | 389.50 | 315.82 | 21.18 | 93.67 | 354.83 |
June | 381.00 | 0.62 | 0.60 | 01-JUN-06:40 | 742.96 | 19.99 | 58.83 | 383.67 | 343.74 | 22.39 | 133.00 | 348.00 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:49 | 675.52 | 19.25 | 44.83 | 391.50 | 297.82 | 20.86 | 116.17 | 362.00 |
August | 390.67 | 0.63 | 0.60 | 01-AUG-07:19 | 535.22 | 17.11 | 0.00 | 372.67 | 257.32 | 20.40 | 58.00 | 330.83 |
September | 328.83 | 0.64 | 0.60 | 01-SEP-06:00 | 459.72 | 16.39 | 0.00 | 314.83 | 228.23 | 19.68 | 1.67 | 234.50 |
October | 296.17 | 0.69 | 0.60 | 01-OCT-09:39 | 342.61 | 15.05 | 0.00 | 272.83 | 173.96 | 18.49 | 0.00 | 96.17 |
November | 300.00 | 0.70 | 0.60 | 01-NOV-08:30 | 339.15 | 14.48 | 0.00 | 252.50 | 172.89 | 17.94 | 0.00 | 80.33 |
December | 297.00 | 0.71 | 0.60 | 01-DEC-09:30 | 298.24 | 14.17 | 0.00 | 239.00 | 158.80 | 17.79 | 0.00 | 44.67 |
Annual Sum or Average | 4065.67 | 0.65 | 505.35 | 16.69 | 116.17 | 3785.67 | 240.39 | 19.78 | 434.83 | 2571.17 | ||
Minimum of Months | 279.67 | 0.62 | 0.60 | 298.24 | 14.17 | 0.00 | 239.00 | 158.80 | 17.79 | 0.00 | 44.67 | |
Maximum of Months | 408.67 | 0.71 | 0.60 | 742.96 | 19.99 | 58.83 | 391.50 | 343.74 | 22.39 | 133.00 | 362.00 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.70 | 0.60 | 01-JAN-09:20 | 330.66 | 14.69 | 0.00 | 246.50 | 171.18 | 18.25 | 0.00 | 64.00 |
February | 279.67 | 0.67 | 0.60 | 01-FEB-10:30 | 413.53 | 15.55 | 0.00 | 259.00 | 198.41 | 18.88 | 0.00 | 129.67 |
March | 338.17 | 0.65 | 0.60 | 01-MAR-10:30 | 495.21 | 16.11 | 0.00 | 317.67 | 227.52 | 19.32 | 0.00 | 228.67 |
April | 358.33 | 0.63 | 0.60 | 01-APR-07:00 | 521.80 | 17.04 | 0.00 | 346.00 | 255.45 | 20.30 | 32.33 | 297.50 |
May | 393.83 | 0.62 | 0.60 | 01-MAY-06:40 | 701.54 | 17.98 | 12.50 | 389.50 | 315.82 | 21.18 | 93.67 | 354.83 |
June | 381.00 | 0.62 | 0.60 | 01-JUN-06:40 | 742.96 | 19.99 | 58.83 | 383.67 | 343.74 | 22.39 | 133.00 | 348.00 |
July | 408.67 | 0.62 | 0.60 | 01-JUL-05:49 | 675.52 | 19.25 | 44.83 | 391.50 | 297.82 | 20.86 | 116.17 | 362.00 |
August | 390.67 | 0.63 | 0.60 | 01-AUG-07:19 | 535.22 | 17.11 | 0.00 | 372.67 | 257.32 | 20.40 | 58.00 | 330.83 |
September | 328.83 | 0.64 | 0.60 | 01-SEP-06:00 | 459.72 | 16.39 | 0.00 | 314.83 | 228.23 | 19.68 | 1.67 | 234.50 |
October | 296.17 | 0.69 | 0.60 | 01-OCT-09:39 | 342.61 | 15.05 | 0.00 | 272.83 | 173.96 | 18.49 | 0.00 | 96.17 |
November | 300.00 | 0.70 | 0.60 | 01-NOV-08:30 | 339.15 | 14.48 | 0.00 | 252.50 | 172.89 | 17.94 | 0.00 | 80.33 |
December | 297.00 | 0.71 | 0.60 | 01-DEC-09:30 | 298.24 | 14.17 | 0.00 | 239.00 | 158.80 | 17.79 | 0.00 | 44.67 |
Annual Sum or Average | 4065.67 | 0.65 | 505.35 | 16.69 | 116.17 | 3785.67 | 240.39 | 19.78 | 434.83 | 2571.17 | ||
Minimum of Months | 279.67 | 0.62 | 0.60 | 298.24 | 14.17 | 0.00 | 239.00 | 158.80 | 17.79 | 0.00 | 44.67 | |
Maximum of Months | 408.67 | 0.71 | 0.60 | 742.96 | 19.99 | 58.83 | 391.50 | 343.74 | 22.39 | 133.00 | 362.00 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11893644.94 | 1035.51 | 30-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34260799.33 | 1077.97 | 04-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.763342E+09 | 3315.57 | 25-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141846E+09 | 2179.25 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35485942.46 | 1240.74 | 20-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.986828E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.763342E+09 | 3315.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.591949E+09 | 2073.94 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.532091E+09 | 1476.00 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.899275E+09 | 1979.89 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.401423E+09 | 1421.10 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.619965E+09 | 1135.16 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.402087E+09 | 679.63 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196175E+09 | 418.83 | 09-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111383E+09 | 506.11 | 06-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151025E+09 | 561.51 | 18-SEP-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146342E+09 | 662.20 | 25-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.219123E+09 | 1076.18 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.418971E+09 | 1584.53 | 13-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468981E+10 | |||||||
Minimum of Months | 0.111383E+09 | 418.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.899275E+09 | 2073.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 8124501.54 | 578.25 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3931637.55 | 181.61 | 13-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10538550.67 | 352.79 | 29-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 196493.41 | 55.28 | 01-APR-10:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81688.11 | 20.73 | 15-MAY-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 39176.86 | 26.44 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 13224.98 | 11.02 | 06-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22925273.12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10538550.67 | 578.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.182911E+09 | 1217.42 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36508242.05 | 316.20 | 13-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.171256E+09 | 1162.54 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31469863.73 | 423.18 | 01-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5859549.23 | 143.09 | 15-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81083.62 | 21.80 | 01-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 52719251.42 | 616.64 | 23-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480805E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.182911E+09 | 1217.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160584E+09 | 702.18 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54171217.45 | 241.48 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161892E+09 | 670.33 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23373654.63 | 321.50 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5881569.01 | 108.63 | 14-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 19579.26 | 8.77 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2278547.71 | 125.32 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 64925682.13 | 398.80 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473126E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161892E+09 | 702.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.249603E+10 | 8217.36 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116821E+10 | 7716.97 | 04-FEB-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.186541E+10 | 7849.01 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180364E+10 | 4639.72 | 01-APR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204761E+10 | 4671.68 | 25-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.295136E+10 | 5846.55 | 26-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.368896E+10 | 5923.45 | 29-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.383917E+10 | 6172.13 | 19-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.329997E+10 | 7172.61 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.314538E+10 | 7402.03 | 05-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140230E+10 | 6217.65 | 08-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219152E+10 | 7722.80 | 23-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298996E+11 | |||||||
Minimum of Months | 0.116821E+10 | 4639.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383917E+10 | 8217.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.150977E+09 | 4662.51 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159818E+09 | 2878.94 | 12-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304732E+09 | 4366.00 | 29-MAR-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41923724.26 | 1775.69 | 17-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.288954E+09 | 1959.74 | 09-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.269995E+09 | 2012.48 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101807E+09 | 882.90 | 17-JUL-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3898241.40 | 357.20 | 02-AUG-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 45702290.51 | 1423.75 | 18-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45209076.81 | 1240.04 | 06-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10228072.78 | 1373.53 | 11-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25664536.93 | 1836.18 | 13-DEC-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144891E+10 | |||||||
Minimum of Months | 3898241.40 | 357.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.304732E+09 | 4662.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 44152370.14 | 7556.89 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36117375.69 | 2556.83 | 13-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 37336443.55 | 6119.12 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2104846.81 | 529.57 | 17-APR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12258287.34 | 1600.87 | 28-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5227945.63 | 1021.72 | 11-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 264572.10 | 283.23 | 04-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89977.73 | 149.96 | 06-OCT-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.137552E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44152370.14 | 7556.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.600753E+09 | 4391.30 | 23-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.436200E+09 | 4499.45 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.655395E+09 | 4512.18 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131963E+09 | 4395.13 | 14-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118404E+09 | 4390.53 | 31-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 20943442.29 | 4391.19 | 06-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7963191.62 | 3790.48 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7848736.39 | 3136.76 | 22-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 14147771.75 | 3832.51 | 21-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57072167.63 | 4382.71 | 25-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265447E+09 | 4392.28 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.501812E+09 | 4390.86 | 11-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281795E+10 | |||||||
Minimum of Months | 7848736.39 | 3136.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.655395E+09 | 4512.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.106995E+10 | 4481.14 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.658314E+09 | 4490.94 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.824236E+09 | 4499.26 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151449E+09 | 4367.22 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98769111.92 | 4364.82 | 31-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15948833.31 | 4039.20 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4169394.16 | 3551.91 | 09-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4733583.52 | 3957.77 | 23-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11103992.75 | 3610.02 | 11-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78168996.39 | 3952.09 | 16-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504159E+09 | 4371.25 | 22-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.929491E+09 | 4477.75 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435049E+10 | |||||||
Minimum of Months | 4169394.16 | 3551.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106995E+10 | 4499.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171041E+10 | 25772.99 | 26-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390908E+09 | 25772.96 | 14-FEB-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.101333E+10 | 25768.56 | 09-MAR-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141264E+09 | 25758.73 | 03-APR-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 97286777.11 | 25761.29 | 18-MAY-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 49577917.60 | 25755.73 | 06-JUN-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14979711.24 | 24220.95 | 10-JUL-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16722901.80 | 24070.06 | 31-AUG-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53425369.05 | 25757.70 | 20-SEP-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69177102.86 | 25751.28 | 18-OCT-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319099E+09 | 25774.99 | 20-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109478E+10 | 25769.25 | 09-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.497096E+10 | |||||||
Minimum of Months | 14979711.24 | 24070.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171041E+10 | 25774.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.593697E+09 | 4249.04 | 23-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.498615E+09 | 4347.23 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.704252E+09 | 4339.91 | 29-MAR-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170427E+09 | 4250.33 | 23-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.175901E+09 | 4248.92 | 14-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 36287918.36 | 4246.48 | 09-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3611658.75 | 3253.24 | 03-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3243408.26 | 3582.00 | 29-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20650415.91 | 3307.26 | 07-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 67920948.34 | 4059.03 | 25-OCT-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311744E+09 | 4246.09 | 22-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.531989E+09 | 4246.47 | 02-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.311834E+10 | |||||||
Minimum of Months | 3243408.26 | 3253.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.704252E+09 | 4347.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103219E+10 | 4314.61 | 02-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.733531E+09 | 4351.80 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.885531E+09 | 4354.97 | 29-MAR-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217188E+09 | 4239.02 | 14-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166240E+09 | 4238.79 | 26-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22791187.81 | 4236.26 | 12-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1836727.85 | 2424.32 | 09-JUL-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1636594.96 | 2346.11 | 21-AUG-19:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 26920552.21 | 4237.23 | 19-SEP-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.106995E+09 | 4239.20 | 11-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.576207E+09 | 4240.42 | 14-NOV-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.961112E+09 | 4353.69 | 12-DEC-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.473218E+10 | |||||||
Minimum of Months | 1636594.96 | 2346.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103219E+10 | 4354.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.792924E+10 | 6849.39 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719248E+10 | 6430.16 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.891939E+10 | 6539.31 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.677155E+10 | 6219.76 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.733844E+10 | 5655.52 | 14-MAY-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.612477E+10 | 4394.68 | 09-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.517330E+10 | 3969.08 | 13-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.492504E+10 | 3949.13 | 24-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.538817E+10 | 4237.24 | 21-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.488342E+10 | 4576.04 | 25-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.616966E+10 | 6221.65 | 05-NOV-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.712460E+10 | 6435.22 | 03-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.779401E+11 | |||||||
Minimum of Months | 0.488342E+10 | 3949.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.891939E+10 | 6849.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.244830E+09 | 1200.79 | 16-JAN-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.186731E+09 | 1344.98 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256216E+09 | 1348.63 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60082441.02 | 1300.91 | 17-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54475197.95 | 1001.64 | 08-MAY-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9688043.96 | 1189.31 | 16-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1781218.72 | 1012.24 | 04-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1825490.28 | 846.59 | 22-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4920614.32 | 1046.55 | 21-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28950165.66 | 1160.65 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121207E+09 | 1151.43 | 09-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212464E+09 | 1167.96 | 17-DEC-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118317E+10 | |||||||
Minimum of Months | 1781218.72 | 846.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.256216E+09 | 1348.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.410910E+09 | 1342.91 | 03-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.263183E+09 | 1344.10 | 25-FEB-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311845E+09 | 1345.19 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 63959628.20 | 1291.02 | 14-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43358100.72 | 975.94 | 24-MAY-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5397357.40 | 1181.48 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 568773.11 | 792.96 | 05-JUL-08:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 532158.68 | 823.11 | 23-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3503504.52 | 878.89 | 11-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 34773063.23 | 1113.85 | 13-OCT-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206657E+09 | 1190.89 | 30-NOV-19:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364593E+09 | 1339.81 | 13-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170928E+10 | |||||||
Minimum of Months | 532158.68 | 792.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.410910E+09 | 1345.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293470E+09 | 3905.85 | 31-JAN-19:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235837E+09 | 5163.51 | 11-FEB-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595292E+09 | 6229.47 | 30-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125790E+09 | 6133.42 | 22-APR-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189308E+09 | 5311.18 | 11-MAY-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35188176.98 | 5853.05 | 08-JUN-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15243464.46 | 5022.94 | 10-JUL-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10132882.55 | 4026.25 | 21-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11938155.78 | 3985.79 | 17-SEP-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24721618.13 | 5088.72 | 23-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78509674.50 | 6126.06 | 24-NOV-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202991E+09 | 4240.09 | 06-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181842E+10 | |||||||
Minimum of Months | 10132882.55 | 3905.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595292E+09 | 6229.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.210856E+09 | 4805.84 | 09-JAN-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3729296.47 | 1183.26 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141036E+09 | 4660.75 | 30-MAR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 128509.00 | 107.13 | 05-NOV-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 39742758.17 | 3277.43 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395493E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.210856E+09 | 4805.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190697E+10 | 4220.89 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136539E+10 | 3425.33 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183156E+10 | 4029.38 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.700792E+09 | 2759.03 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.718351E+09 | 2325.18 | 14-MAY-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.322252E+09 | 1240.10 | 14-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65908537.79 | 809.55 | 14-JUL-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38345050.03 | 772.79 | 24-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.317445E+09 | 1074.13 | 20-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371765E+09 | 1431.80 | 25-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.971233E+09 | 2641.23 | 05-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157830E+10 | 3559.22 | 24-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101883E+11 | |||||||
Minimum of Months | 38345050.03 | 772.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190697E+10 | 4220.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.825317E+11 | 87415.06 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.636555E+11 | 84635.12 | 03-FEB-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.878010E+11 | 84086.84 | 14-MAR-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331254E+11 | 81776.91 | 15-APR-21:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.291894E+11 | 79249.99 | 19-MAY-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.301745E+10 | 51452.28 | 13-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136682E+09 | 14578.54 | 06-JUL-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167405E+10 | 50913.82 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114951E+11 | 78739.06 | 29-OCT-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.533429E+11 | 84064.14 | 29-NOV-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.824452E+11 | 84552.61 | 20-DEC-21:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.448414E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.878010E+11 | 87415.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.802855E+10 | 9028.71 | 08-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.644175E+10 | 8491.36 | 05-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.862931E+10 | 8628.99 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.405762E+10 | 8219.50 | 01-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.361148E+10 | 8084.76 | 19-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.639208E+09 | 5274.03 | 13-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37016963.46 | 2368.16 | 06-JUL-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17468304.78 | 904.21 | 24-AUG-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.318953E+09 | 5274.64 | 20-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143547E+10 | 7945.12 | 28-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.566040E+10 | 8220.62 | 05-NOV-02:70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.806490E+10 | 8494.40 | 03-DEC-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.469421E+11 | |||||||
Minimum of Months | 17468304.78 | 904.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.862931E+10 | 9028.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.151968E+10 | 0.786627E+09 | 13816.76 | 21-JAN-09:01 | 10866.09 | 0.38 |
February | 0.00 | 0.00 | 0.134124E+10 | 0.712486E+09 | 13907.89 | 13-FEB-16:02 | 10106.27 | 0.34 |
March | 0.00 | 0.00 | 0.146657E+10 | 0.661015E+09 | 13497.93 | 18-MAR-15:01 | 11392.17 | 0.38 |
April | 0.00 | 0.00 | 0.293636E+10 | 0.139396E+10 | 13280.38 | 12-APR-08:62 | 10336.04 | 0.63 |
May | 0.00 | 0.00 | 0.274934E+10 | 0.126904E+10 | 13776.68 | 06-MAY-08:62 | 9980.78 | 0.64 |
June | 0.00 | 0.00 | 0.408266E+10 | 0.175668E+10 | 13936.10 | 28-JUN-08:62 | 9875.86 | 0.77 |
July | 0.00 | 0.00 | 0.597139E+10 | 0.261092E+10 | 14723.05 | 30-JUL-08:61 | 10462.74 | 0.85 |
August | 0.00 | 0.00 | 0.606892E+10 | 0.261248E+10 | 14863.97 | 06-AUG-08:61 | 10243.14 | 0.87 |
September | 0.00 | 0.00 | 0.459793E+10 | 0.199113E+10 | 14556.95 | 22-SEP-15:01 | 10597.08 | 0.84 |
October | 0.00 | 0.00 | 0.421190E+10 | 0.237721E+10 | 14869.59 | 01-OCT-08:61 | 10343.46 | 0.65 |
November | 0.00 | 0.00 | 0.199844E+10 | 0.101017E+10 | 14018.89 | 12-NOV-09:02 | 9353.05 | 0.46 |
December | 0.00 | 0.00 | 0.171439E+10 | 0.121439E+10 | 13645.04 | 30-DEC-16:01 | 13645.04 | 0.26 |
Annual Sum or Average | 0.386588E+11 | 0.183961E+11 | 0.59 | |||||
Minimum of Months | 0.00 | 0.00 | 0.134124E+10 | 0.661015E+09 | 13280.38 | 9353.05 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.606892E+10 | 0.261248E+10 | 14869.59 | 13645.04 | 0.87 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.297911E+09 | 0.151697E+09 | 13368.50 | 20-JAN-16:01 | 11040.84 | 0.13 |
February | 0.00 | 0.00 | 0.450834E+09 | 0.205496E+09 | 13470.82 | 13-FEB-16:02 | 9651.53 | 0.20 |
March | 0.00 | 0.00 | 0.663150E+09 | 0.258143E+09 | 13544.36 | 22-MAR-18:11 | 11151.52 | 0.24 |
April | 0.00 | 0.00 | 0.169855E+10 | 0.630592E+09 | 13804.40 | 26-APR-21:11 | 10636.48 | 0.50 |
May | 0.00 | 0.00 | 0.189646E+10 | 0.727788E+09 | 13433.69 | 06-MAY-08:62 | 9882.85 | 0.53 |
June | 0.00 | 0.00 | 0.263988E+10 | 0.993353E+09 | 14484.54 | 28-JUN-21:11 | 10610.58 | 0.54 |
July | 0.00 | 0.00 | 0.376103E+10 | 0.147883E+10 | 15206.85 | 19-JUL-21:11 | 10523.53 | 0.55 |
August | 0.00 | 0.00 | 0.359666E+10 | 0.135152E+10 | 15094.00 | 19-AUG-08:11 | 9872.11 | 0.55 |
September | 0.00 | 0.00 | 0.249530E+10 | 0.901140E+09 | 14455.22 | 30-SEP-21:11 | 10339.75 | 0.55 |
October | 0.00 | 0.00 | 0.186843E+10 | 0.968171E+09 | 14915.83 | 01-OCT-08:11 | 9299.20 | 0.39 |
November | 0.00 | 0.00 | 0.526595E+09 | 0.223543E+09 | 13432.03 | 12-NOV-16:01 | 11006.42 | 0.25 |
December | 0.00 | 0.00 | 0.294915E+09 | 0.206239E+09 | 13343.43 | 30-DEC-16:01 | 13343.43 | 0.09 |
Annual Sum or Average | 0.201897E+11 | 0.809652E+10 | 0.38 | |||||
Minimum of Months | 0.00 | 0.00 | 0.294915E+09 | 0.151697E+09 | 13343.43 | 9299.20 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.376103E+10 | 0.147883E+10 | 15206.85 | 13343.43 | 0.55 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.317506E+11 | 0.222847E+11 | 43782.07 | 14-JAN-12:20 | 43782.07 | 0.53 |
February | 0.00 | 0.00 | 0.195777E+11 | 0.126322E+11 | 38151.32 | 02-FEB-12:30 | 34654.48 | 0.46 |
March | 0.00 | 0.00 | 0.137098E+11 | 0.536383E+10 | 29542.96 | 11-MAR-12:50 | 23630.09 | 0.52 |
April | 0.00 | 0.00 | 0.142571E+11 | 0.427342E+10 | 22440.23 | 04-APR-15:03 | 10585.87 | 0.65 |
May | 0.00 | 0.00 | 0.905621E+10 | 0.206407E+10 | 17830.06 | 04-MAY-20:20 | 7330.81 | 0.60 |
June | 0.00 | 0.00 | 0.136790E+11 | 0.332715E+10 | 20101.83 | 30-JUN-07:00 | 7201.64 | 0.74 |
July | 0.00 | 0.00 | 0.213673E+11 | 0.596599E+10 | 24024.84 | 23-JUL-08:00 | 9861.75 | 0.87 |
August | 0.00 | 0.00 | 0.273217E+11 | 0.861584E+10 | 25488.05 | 19-AUG-15:03 | 12203.87 | 0.94 |
September | 0.00 | 0.00 | 0.301277E+11 | 0.120601E+11 | 37162.39 | 30-SEP-12:00 | 33317.06 | 0.95 |
October | 0.00 | 0.00 | 0.397453E+11 | 0.255390E+11 | 47916.58 | 16-OCT-12:10 | 47916.58 | 0.71 |
November | 0.00 | 0.00 | 0.326704E+11 | 0.213218E+11 | 47221.16 | 19-NOV-10:00 | 39444.66 | 0.63 |
December | 0.00 | 0.00 | 0.360185E+11 | 0.286758E+11 | 45173.44 | 19-DEC-12:30 | 45173.44 | 0.42 |
Annual Sum or Average | 0.289281E+12 | 0.152124E+12 | 0.67 | |||||
Minimum of Months | 0.00 | 0.00 | 0.905621E+10 | 0.206407E+10 | 17830.06 | 7201.64 | 0.42 | |
Maximum of Months | 0.00 | 0.00 | 0.397453E+11 | 0.286758E+11 | 47916.58 | 47916.58 | 0.95 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.120880E+11 | 0.620316E+10 | 81368.41 | 16-JAN-09:02 | 81368.41 | 0.36 |
February | 0.00 | 0.00 | 0.132910E+11 | 0.629443E+10 | 82389.14 | 13-FEB-19:02 | 64840.90 | 0.51 |
March | 0.00 | 0.00 | 0.162000E+11 | 0.722391E+10 | 79500.52 | 22-MAR-18:11 | 64709.09 | 0.54 |
April | 0.00 | 0.00 | 0.235203E+11 | 0.115094E+11 | 85051.91 | 26-APR-21:11 | 65559.13 | 0.58 |
May | 0.00 | 0.00 | 0.271603E+11 | 0.142795E+11 | 83193.43 | 02-MAY-21:11 | 67032.12 | 0.58 |
June | 0.00 | 0.00 | 0.310440E+11 | 0.166177E+11 | 89695.40 | 28-JUN-21:11 | 65652.32 | 0.50 |
July | 0.00 | 0.00 | 0.373129E+11 | 0.208209E+11 | 94617.82 | 19-JUL-21:11 | 65322.98 | 0.49 |
August | 0.00 | 0.00 | 0.358005E+11 | 0.191503E+11 | 92887.58 | 19-AUG-08:11 | 64317.73 | 0.48 |
September | 0.00 | 0.00 | 0.285394E+11 | 0.144060E+11 | 91056.19 | 22-SEP-21:12 | 62842.42 | 0.49 |
October | 0.00 | 0.00 | 0.257614E+11 | 0.159976E+11 | 93763.33 | 01-OCT-08:11 | 60443.71 | 0.39 |
November | 0.00 | 0.00 | 0.153032E+11 | 0.780717E+10 | 81533.17 | 12-NOV-09:02 | 68734.28 | 0.46 |
December | 0.00 | 0.00 | 0.113167E+11 | 0.718317E+10 | 80757.92 | 19-DEC-19:01 | 80757.92 | 0.29 |
Annual Sum or Average | 0.277338E+12 | 0.147493E+12 | 0.47 | |||||
Minimum of Months | 0.00 | 0.00 | 0.113167E+11 | 0.620316E+10 | 79500.52 | 60443.71 | 0.29 | |
Maximum of Months | 0.00 | 0.00 | 0.373129E+11 | 0.208209E+11 | 94617.82 | 81368.41 | 0.58 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.163069E+10 | 0.954782E+09 | 11893.51 | 05-JAN-09:01 | 11893.51 | 0.39 |
February | 0.00 | 0.00 | 0.124515E+10 | 0.710204E+09 | 11893.65 | 01-FEB-09:01 | 11893.65 | 0.33 |
March | 0.00 | 0.00 | 0.143793E+10 | 0.661765E+09 | 11592.65 | 15-MAR-15:01 | 9832.13 | 0.40 |
April | 0.00 | 0.00 | 0.260619E+10 | 0.124043E+10 | 11888.48 | 02-APR-08:61 | 11888.48 | 0.61 |
May | 0.00 | 0.00 | 0.229402E+10 | 0.102958E+10 | 12127.24 | 06-MAY-08:62 | 8981.65 | 0.58 |
June | 0.00 | 0.00 | 0.332243E+10 | 0.142079E+10 | 12291.77 | 29-JUN-08:62 | 9566.10 | 0.75 |
July | 0.00 | 0.00 | 0.529529E+10 | 0.235011E+10 | 12278.07 | 12-JUL-15:01 | 9581.23 | 0.90 |
August | 0.00 | 0.00 | 0.568070E+10 | 0.251489E+10 | 12423.32 | 08-AUG-08:62 | 8879.98 | 0.92 |
September | 0.00 | 0.00 | 0.380649E+10 | 0.165287E+10 | 12979.59 | 22-SEP-15:01 | 9011.78 | 0.85 |
October | 0.00 | 0.00 | 0.392439E+10 | 0.228725E+10 | 13007.13 | 02-OCT-15:01 | 8987.63 | 0.64 |
November | 0.00 | 0.00 | 0.183997E+10 | 0.105018E+10 | 12222.13 | 12-NOV-09:02 | 8136.93 | 0.43 |
December | 0.00 | 0.00 | 0.171604E+10 | 0.130066E+10 | 11893.94 | 23-DEC-09:01 | 11893.94 | 0.26 |
Annual Sum or Average | 0.347993E+11 | 0.171735E+11 | 0.59 | |||||
Minimum of Months | 0.00 | 0.00 | 0.124515E+10 | 0.661765E+09 | 11592.65 | 8136.93 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.568070E+10 | 0.251489E+10 | 13007.13 | 11893.94 | 0.92 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.433783E+09 | 0.236465E+09 | 11784.44 | 21-JAN-09:01 | 9792.57 | 0.13 |
February | 0.00 | 0.00 | 0.449643E+09 | 0.242027E+09 | 11844.19 | 01-FEB-09:11 | 11844.19 | 0.17 |
March | 0.00 | 0.00 | 0.741254E+09 | 0.337436E+09 | 11713.70 | 24-MAR-15:01 | 9583.57 | 0.24 |
April | 0.00 | 0.00 | 0.174008E+10 | 0.850240E+09 | 12329.93 | 02-APR-08:11 | 12329.93 | 0.43 |
May | 0.00 | 0.00 | 0.176901E+10 | 0.823028E+09 | 12741.05 | 24-MAY-08:11 | 12741.05 | 0.47 |
June | 0.00 | 0.00 | 0.237301E+10 | 0.107041E+10 | 13413.41 | 30-JUN-08:11 | 10589.90 | 0.54 |
July | 0.00 | 0.00 | 0.362074E+10 | 0.163426E+10 | 14540.41 | 23-JUL-08:11 | 10987.26 | 0.60 |
August | 0.00 | 0.00 | 0.360864E+10 | 0.160455E+10 | 14658.40 | 19-AUG-08:11 | 10533.91 | 0.59 |
September | 0.00 | 0.00 | 0.206515E+10 | 0.922413E+09 | 13691.44 | 10-SEP-08:11 | 10534.49 | 0.52 |
October | 0.00 | 0.00 | 0.181713E+10 | 0.107444E+10 | 13754.84 | 15-OCT-07:41 | 13754.84 | 0.35 |
November | 0.00 | 0.00 | 0.550276E+09 | 0.276445E+09 | 12037.68 | 12-NOV-09:02 | 7946.12 | 0.20 |
December | 0.00 | 0.00 | 0.364946E+09 | 0.270113E+09 | 12385.96 | 05-DEC-09:11 | 12385.96 | 0.08 |
Annual Sum or Average | 0.195337E+11 | 0.934184E+10 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 0.364946E+09 | 0.236465E+09 | 11713.70 | 7946.12 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.362074E+10 | 0.163426E+10 | 14658.40 | 13754.84 | 0.60 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.386061E+09 | 0.210642E+09 | 3731.90 | 21-JAN-09:01 | 2607.94 | 0.33 |
February | 0.00 | 0.00 | 0.346754E+09 | 0.194612E+09 | 3614.47 | 13-FEB-16:02 | 2574.21 | 0.29 |
March | 0.00 | 0.00 | 0.398688E+09 | 0.194538E+09 | 3533.33 | 24-MAR-08:61 | 2523.40 | 0.34 |
April | 0.00 | 0.00 | 0.835514E+09 | 0.424140E+09 | 3629.33 | 12-APR-08:62 | 2503.81 | 0.60 |
May | 0.00 | 0.00 | 0.787548E+09 | 0.380848E+09 | 3719.95 | 06-MAY-08:62 | 2408.40 | 0.60 |
June | 0.00 | 0.00 | 0.119962E+10 | 0.565228E+09 | 3725.78 | 28-JUN-08:62 | 2462.32 | 0.79 |
July | 0.00 | 0.00 | 0.177922E+10 | 0.861505E+09 | 3868.02 | 30-JUL-08:61 | 2655.74 | 0.91 |
August | 0.00 | 0.00 | 0.179823E+10 | 0.858613E+09 | 3966.08 | 06-AUG-08:61 | 2564.76 | 0.92 |
September | 0.00 | 0.00 | 0.130755E+10 | 0.613416E+09 | 3880.83 | 22-SEP-08:62 | 2497.56 | 0.87 |
October | 0.00 | 0.00 | 0.118074E+10 | 0.697318E+09 | 3936.82 | 01-OCT-08:61 | 2599.18 | 0.63 |
November | 0.00 | 0.00 | 0.517600E+09 | 0.275740E+09 | 3553.72 | 11-NOV-16:02 | 2568.09 | 0.42 |
December | 0.00 | 0.00 | 0.433975E+09 | 0.317717E+09 | 3529.71 | 05-DEC-19:01 | 3529.71 | 0.24 |
Annual Sum or Average | 0.109715E+11 | 0.559432E+10 | 0.58 | |||||
Minimum of Months | 0.00 | 0.00 | 0.346754E+09 | 0.194538E+09 | 3529.71 | 2408.40 | 0.24 | |
Maximum of Months | 0.00 | 0.00 | 0.179823E+10 | 0.861505E+09 | 3966.08 | 3529.71 | 0.92 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 71646425.11 | 37793942.13 | 3547.49 | 21-JAN-09:01 | 2349.57 | 0.10 |
February | 0.00 | 0.00 | 0.110453E+09 | 53861920.22 | 3451.06 | 06-FEB-16:01 | 3451.06 | 0.15 |
March | 0.00 | 0.00 | 0.181591E+09 | 76740177.30 | 3585.71 | 22-MAR-18:11 | 3034.29 | 0.21 |
April | 0.00 | 0.00 | 0.509399E+09 | 0.211029E+09 | 3706.26 | 26-APR-21:11 | 2830.53 | 0.47 |
May | 0.00 | 0.00 | 0.569539E+09 | 0.245110E+09 | 3625.53 | 06-MAY-08:62 | 2404.28 | 0.52 |
June | 0.00 | 0.00 | 0.848502E+09 | 0.365739E+09 | 3902.07 | 28-JUN-21:11 | 2842.41 | 0.58 |
July | 0.00 | 0.00 | 0.124938E+10 | 0.568762E+09 | 4039.38 | 19-JUL-21:11 | 2921.87 | 0.61 |
August | 0.00 | 0.00 | 0.118426E+10 | 0.515746E+09 | 4009.18 | 19-AUG-08:11 | 2565.22 | 0.60 |
September | 0.00 | 0.00 | 0.760174E+09 | 0.305485E+09 | 3830.39 | 22-SEP-08:12 | 2272.48 | 0.58 |
October | 0.00 | 0.00 | 0.559402E+09 | 0.305196E+09 | 3988.46 | 01-OCT-08:11 | 2341.15 | 0.39 |
November | 0.00 | 0.00 | 0.126195E+09 | 56071364.99 | 3479.90 | 12-NOV-16:01 | 2841.86 | 0.20 |
December | 0.00 | 0.00 | 67406336.63 | 50023688.08 | 3451.47 | 30-DEC-16:01 | 3451.47 | 0.06 |
Annual Sum or Average | 0.623794E+10 | 0.279156E+10 | 0.37 | |||||
Minimum of Months | 0.00 | 0.00 | 67406336.63 | 37793942.13 | 3451.06 | 2272.48 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.124938E+10 | 0.568762E+09 | 4039.38 | 3451.47 | 0.61 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.699734E+10 | 0.506764E+10 | 15574.07 | 15-JAN-16:01 | 15574.07 | 0.60 |
February | 0.00 | 0.00 | 0.451701E+10 | 0.301605E+10 | 16083.37 | 11-FEB-16:03 | 11291.53 | 0.55 |
March | 0.00 | 0.00 | 0.371950E+10 | 0.191303E+10 | 15336.86 | 20-MAR-15:02 | 12736.24 | 0.56 |
April | 0.00 | 0.00 | 0.423064E+10 | 0.187947E+10 | 15246.93 | 01-APR-18:02 | 15246.93 | 0.73 |
May | 0.00 | 0.00 | 0.290528E+10 | 0.111563E+10 | 15861.49 | 06-MAY-15:01 | 12804.60 | 0.61 |
June | 0.00 | 0.00 | 0.417788E+10 | 0.155849E+10 | 16077.00 | 27-JUN-18:01 | 12629.54 | 0.75 |
July | 0.00 | 0.00 | 0.669138E+10 | 0.271598E+10 | 16977.26 | 30-JUL-08:61 | 11928.21 | 0.85 |
August | 0.00 | 0.00 | 0.806042E+10 | 0.343424E+10 | 17138.05 | 20-AUG-08:61 | 11806.58 | 0.90 |
September | 0.00 | 0.00 | 0.775081E+10 | 0.372304E+10 | 16730.69 | 22-SEP-08:62 | 11732.85 | 0.88 |
October | 0.00 | 0.00 | 0.931466E+10 | 0.633140E+10 | 17190.03 | 05-OCT-18:01 | 11755.26 | 0.72 |
November | 0.00 | 0.00 | 0.713480E+10 | 0.497812E+10 | 15940.44 | 12-NOV-09:02 | 11766.55 | 0.66 |
December | 0.00 | 0.00 | 0.754998E+10 | 0.614978E+10 | 15574.08 | 30-DEC-16:01 | 15574.08 | 0.45 |
Annual Sum or Average | 0.730497E+11 | 0.418829E+11 | 0.69 | |||||
Minimum of Months | 0.00 | 0.00 | 0.290528E+10 | 0.111563E+10 | 15246.93 | 11291.53 | 0.45 | |
Maximum of Months | 0.00 | 0.00 | 0.931466E+10 | 0.633140E+10 | 17190.03 | 15574.08 | 0.90 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.798106E+11 | 0.786941E+11 | 214791.90 | 14-JAN-11:50 | 214791.90 | 0.31 |
February | 0.00 | 0.00 | 0.501066E+11 | 0.472049E+11 | 207179.32 | 01-FEB-12:00 | 207179.32 | 0.30 |
March | 0.00 | 0.00 | 0.524697E+11 | 0.488638E+11 | 216365.60 | 23-MAR-15:03 | 145984.87 | 0.29 |
April | 0.00 | 0.00 | 0.114565E+12 | 0.106442E+12 | 261015.50 | 26-APR-11:00 | 209155.52 | 0.53 |
May | 0.00 | 0.00 | 0.123752E+12 | 0.119048E+12 | 183562.29 | 04-MAY-13:00 | 162104.73 | 0.64 |
June | 0.00 | 0.00 | 0.243089E+12 | 0.189721E+12 | 322114.65 | 29-JUN-11:00 | 194793.08 | 0.92 |
July | 0.00 | 0.00 | 0.468005E+12 | 0.277132E+12 | 401572.01 | 19-JUL-12:00 | 239659.84 | 1.00 |
August | 0.00 | 0.00 | 0.524287E+12 | 0.287369E+12 | 409013.24 | 14-AUG-10:50 | 242412.42 | 1.00 |
September | 0.00 | 0.00 | 0.325816E+12 | 0.223306E+12 | 435200.79 | 22-SEP-12:00 | 209120.96 | 0.93 |
October | 0.00 | 0.00 | 0.329391E+12 | 0.251703E+12 | 396975.38 | 01-OCT-12:00 | 209855.11 | 0.63 |
November | 0.00 | 0.00 | 0.874223E+11 | 0.828461E+11 | 227865.78 | 19-NOV-13:00 | 227865.78 | 0.36 |
December | 0.00 | 0.00 | 0.888017E+11 | 0.886924E+11 | 211218.95 | 16-DEC-13:00 | 211218.95 | 0.15 |
Annual Sum or Average | 0.248752E+13 | 0.180102E+13 | 0.59 | |||||
Minimum of Months | 0.00 | 0.00 | 0.501066E+11 | 0.472049E+11 | 183562.29 | 145984.87 | 0.15 | |
Maximum of Months | 0.00 | 0.00 | 0.524287E+12 | 0.287369E+12 | 435200.79 | 242412.42 | 1.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.351486E+10 | 0.349645E+10 | 20564.52 | 13-JAN-14:00 | 20564.52 | 0.16 |
February | 0.00 | 0.00 | 0.189168E+10 | 0.183904E+10 | 17577.71 | 01-FEB-10:00 | 17577.71 | 0.14 |
March | 0.00 | 0.00 | 0.212621E+10 | 0.197406E+10 | 21789.55 | 22-MAR-13:00 | 14827.52 | 0.12 |
April | 0.00 | 0.00 | 0.532087E+10 | 0.504414E+10 | 22084.04 | 26-APR-13:00 | 22084.04 | 0.27 |
May | 0.00 | 0.00 | 0.566791E+10 | 0.558001E+10 | 18514.43 | 04-MAY-13:00 | 16259.84 | 0.35 |
June | 0.00 | 0.00 | 0.126650E+11 | 0.101484E+11 | 30621.91 | 29-JUN-12:15 | 17821.10 | 0.64 |
July | 0.00 | 0.00 | 0.283929E+11 | 0.167718E+11 | 39897.45 | 31-JUL-12:15 | 23759.11 | 0.78 |
August | 0.00 | 0.00 | 0.324272E+11 | 0.176768E+11 | 38506.98 | 14-AUG-10:00 | 22136.04 | 0.78 |
September | 0.00 | 0.00 | 0.184524E+11 | 0.130038E+11 | 39498.06 | 22-SEP-12:15 | 19366.72 | 0.69 |
October | 0.00 | 0.00 | 0.205486E+11 | 0.151787E+11 | 37935.62 | 01-OCT-12:20 | 20327.67 | 0.46 |
November | 0.00 | 0.00 | 0.353985E+10 | 0.347634E+10 | 21030.69 | 19-NOV-13:15 | 21030.69 | 0.19 |
December | 0.00 | 0.00 | 0.428200E+10 | 0.428068E+10 | 20474.50 | 05-DEC-10:00 | 20474.50 | 0.06 |
Annual Sum or Average | 0.138829E+12 | 0.984703E+11 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 0.189168E+10 | 0.183904E+10 | 17577.71 | 14827.52 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.324272E+11 | 0.176768E+11 | 39897.45 | 23759.11 | 0.78 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 24005.52 | 49045.67 | 27-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 24085.80 | 49037.52 | 09-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 23747.50 | 48893.71 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23200.75 | 47898.39 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22519.04 | 46911.58 | 02-MAY-06:57 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 21939.74 | 45769.08 | 02-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21633.13 | 44797.29 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 21606.15 | 44719.10 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21788.16 | 45485.95 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 22391.72 | 46650.47 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22964.12 | 47745.47 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23614.42 | 48616.52 | 28-DEC-07:10 |
Annual Sum or Average | 0.00 | 22784.19 | ||||
Minimum of Months | 0.00 | 0.00 | 21606.15 | 44719.10 | ||
Maximum of Months | 0.00 | 0.00 | 24085.80 | 49045.67 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 40693.68 | 156510.15 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 34351.62 | 123055.45 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 42843.46 | 143409.56 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 18318.85 | 112122.20 | 01-APR-05:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16543.31 | 101998.06 | 27-MAY-03:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 5602.97 | 66425.40 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 3539.72 | 31986.36 | 10-JUL-08:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 3327.43 | 32508.65 | 03-AUG-08:16 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 4324.26 | 64457.04 | 20-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 8115.18 | 96097.08 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26765.93 | 112095.26 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 39437.09 | 126826.57 | 24-DEC-04:00 |
Annual Sum or Average | 0.00 | 20278.64 | ||||
Minimum of Months | 0.00 | 0.00 | 3327.43 | 31986.36 | ||
Maximum of Months | 0.00 | 0.00 | 42843.46 | 156510.15 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 52676.71 | 354901.85 | 14-JAN-16:01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 39587.85 | 307638.01 | 01-FEB-09:11 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 35717.43 | 400425.26 | 23-MAR-15:03 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 67537.09 | 385211.13 | 11-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 67796.46 | 325464.47 | 04-MAY-15:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 124224.67 | 437303.26 | 28-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218937.37 | 560587.14 | 31-JUL-15:05 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 243727.74 | 589430.99 | 17-AUG-15:03 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 165369.35 | 555598.41 | 21-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 164764.09 | 523241.14 | 01-OCT-15:03 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 59562.55 | 404051.30 | 18-NOV-16:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 57939.58 | 380603.16 | 05-DEC-09:11 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 108760.58 | 0.00 | ||||
Minimum of Months | 35717.43 | 307638.01 | 0.00 | 0.00 | ||
Maximum of Months | 243727.74 | 589430.99 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270916E+10 | 0.71 | 1298.89 | 01-JAN-00:10 | 0.89 |
February | 0.244698E+10 | 0.70 | 1298.89 | 01-FEB-00:03 | 0.89 |
March | 0.270916E+10 | 0.70 | 1298.89 | 01-MAR-00:03 | 0.89 |
April | 0.262177E+10 | 0.70 | 1298.89 | 01-APR-00:10 | 0.89 |
May | 0.270916E+10 | 0.70 | 1298.89 | 01-MAY-00:03 | 0.88 |
June | 0.262177E+10 | 0.70 | 1298.89 | 01-JUN-00:05 | 0.89 |
July | 0.270916E+10 | 0.70 | 1298.89 | 01-JUL-00:10 | 0.88 |
August | 0.270916E+10 | 0.70 | 1298.89 | 01-AUG-00:10 | 0.89 |
September | 0.262177E+10 | 0.70 | 1298.89 | 01-SEP-00:10 | 0.88 |
October | 0.270916E+10 | 0.70 | 1298.89 | 01-OCT-00:05 | 0.89 |
November | 0.262177E+10 | 0.70 | 1298.89 | 01-NOV-00:10 | 0.89 |
December | 0.270916E+10 | 0.71 | 1298.89 | 01-DEC-00:03 | 0.90 |
Annual Sum or Average | 0.318982E+11 | 0.70 | |||
Minimum of Months | 0.244698E+10 | 0.70 | 1298.89 | 0.88 | |
Maximum of Months | 0.270916E+10 | 0.71 | 1298.89 | 0.90 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.358482E+11 | 0.89 | 21159.20 | 06-JAN-22:00 | 1.17 |
February | 0.330836E+11 | 0.90 | 22036.34 | 02-FEB-21:10 | 1.20 |
March | 0.366135E+11 | 0.90 | 20894.24 | 06-MAR-22:00 | 1.16 |
April | 0.353374E+11 | 0.90 | 20560.44 | 06-APR-20:30 | 1.14 |
May | 0.364144E+11 | 0.89 | 20933.40 | 10-MAY-20:10 | 1.16 |
June | 0.345439E+11 | 0.88 | 20641.12 | 12-JUN-21:00 | 1.15 |
July | 0.350728E+11 | 0.87 | 18636.90 | 07-JUL-21:00 | 1.07 |
August | 0.350793E+11 | 0.87 | 18792.84 | 21-AUG-20:10 | 1.08 |
September | 0.340417E+11 | 0.88 | 19660.74 | 18-SEP-21:00 | 1.11 |
October | 0.351978E+11 | 0.88 | 20245.52 | 11-OCT-21:00 | 1.14 |
November | 0.353134E+11 | 0.90 | 21776.62 | 29-NOV-22:00 | 1.19 |
December | 0.360831E+11 | 0.89 | 21932.81 | 20-DEC-21:30 | 1.19 |
Annual Sum or Average | 0.422629E+12 | 0.89 | |||
Minimum of Months | 0.330836E+11 | 0.87 | 18636.90 | 1.07 | |
Maximum of Months | 0.366135E+11 | 0.90 | 22036.34 | 1.20 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.27 | 76.61 | 01-JAN-00:10 | 0.27 |
February | 0.185347E+09 | 0.27 | 76.61 | 01-FEB-00:03 | 0.27 |
March | 0.205205E+09 | 0.27 | 76.61 | 01-MAR-00:03 | 0.27 |
April | 0.198586E+09 | 0.27 | 76.61 | 01-APR-00:10 | 0.27 |
May | 0.205205E+09 | 0.27 | 76.61 | 01-MAY-00:03 | 0.27 |
June | 0.198586E+09 | 0.27 | 76.61 | 01-JUN-00:05 | 0.27 |
July | 0.205205E+09 | 0.27 | 76.61 | 01-JUL-00:10 | 0.27 |
August | 0.205205E+09 | 0.27 | 76.61 | 01-AUG-00:10 | 0.27 |
September | 0.198586E+09 | 0.27 | 76.61 | 01-SEP-00:10 | 0.27 |
October | 0.205205E+09 | 0.27 | 76.61 | 01-OCT-00:05 | 0.27 |
November | 0.198586E+09 | 0.27 | 76.61 | 01-NOV-00:10 | 0.27 |
December | 0.205205E+09 | 0.27 | 76.61 | 01-DEC-00:03 | 0.27 |
Annual Sum or Average | 0.241613E+10 | 0.27 | |||
Minimum of Months | 0.185347E+09 | 0.27 | 76.61 | 0.27 | |
Maximum of Months | 0.205205E+09 | 0.27 | 76.61 | 0.27 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | -0.0 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | -0.0 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.19 | 612.92 | 01-JAN-07:03 | 0.27 |
February | 0.105030E+10 | 0.19 | 612.92 | 01-FEB-07:05 | 0.27 |
March | 0.116283E+10 | 0.19 | 612.92 | 01-MAR-07:03 | 0.27 |
April | 0.112532E+10 | 0.19 | 612.92 | 01-APR-06:10 | 0.27 |
May | 0.116283E+10 | 0.19 | 612.92 | 01-MAY-06:05 | 0.27 |
June | 0.112532E+10 | 0.19 | 612.92 | 01-JUN-06:05 | 0.27 |
July | 0.116283E+10 | 0.19 | 612.92 | 01-JUL-06:05 | 0.27 |
August | 0.116283E+10 | 0.19 | 612.92 | 01-AUG-06:03 | 0.27 |
September | 0.112532E+10 | 0.19 | 612.92 | 01-SEP-06:05 | 0.27 |
October | 0.116283E+10 | 0.19 | 612.92 | 01-OCT-06:03 | 0.27 |
November | 0.112532E+10 | 0.19 | 612.92 | 01-NOV-06:05 | 0.27 |
December | 0.116283E+10 | 0.19 | 612.92 | 01-DEC-07:05 | 0.27 |
Annual Sum or Average | 0.136914E+11 | 0.19 | |||
Minimum of Months | 0.105030E+10 | 0.19 | 612.92 | 0.27 | |
Maximum of Months | 0.116283E+10 | 0.19 | 612.92 | 0.27 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151380E+09 | 0.48 | 668.37 | 01-JAN-09:01 | 0.58 |
February | 0.127799E+09 | 0.45 | 668.37 | 01-FEB-09:01 | 0.59 |
March | 0.151696E+09 | 0.45 | 668.37 | 01-MAR-16:01 | 0.58 |
April | 0.153964E+09 | 0.46 | 668.37 | 01-APR-15:02 | 0.59 |
May | 0.143959E+09 | 0.46 | 668.37 | 01-MAY-08:62 | 0.58 |
June | 0.179084E+09 | 0.47 | 668.37 | 01-JUN-15:01 | 0.58 |
July | 0.246659E+09 | 0.50 | 668.37 | 01-JUL-08:61 | 0.58 |
August | 0.248833E+09 | 0.51 | 668.37 | 01-AUG-08:62 | 0.58 |
September | 0.197476E+09 | 0.50 | 668.37 | 01-SEP-08:62 | 0.58 |
October | 0.202816E+09 | 0.50 | 668.37 | 01-OCT-08:61 | 0.58 |
November | 0.137005E+09 | 0.49 | 668.37 | 01-NOV-08:61 | 0.58 |
December | 0.154481E+09 | 0.49 | 668.37 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.209515E+10 | 0.48 | |||
Minimum of Months | 0.127799E+09 | 0.45 | 668.37 | 0.58 | |
Maximum of Months | 0.248833E+09 | 0.51 | 668.37 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140963E+09 | 0.39 | 653.50 | 02-JAN-16:02 | 0.59 |
February | 0.112086E+09 | 0.41 | 653.50 | 01-FEB-16:01 | 0.58 |
March | 0.133373E+09 | 0.41 | 653.50 | 01-MAR-16:01 | 0.58 |
April | 0.100624E+09 | 0.39 | 653.50 | 01-APR-15:02 | 0.59 |
May | 0.103326E+09 | 0.38 | 653.50 | 01-MAY-08:11 | 0.58 |
June | 0.111175E+09 | 0.33 | 653.50 | 01-JUN-08:11 | 0.58 |
July | 0.144939E+09 | 0.32 | 653.50 | 01-JUL-08:11 | 0.58 |
August | 0.137884E+09 | 0.32 | 653.50 | 01-AUG-08:11 | 0.58 |
September | 0.106834E+09 | 0.33 | 653.50 | 01-SEP-08:11 | 0.58 |
October | 0.102400E+09 | 0.34 | 653.50 | 01-OCT-08:11 | 0.58 |
November | 99711113.13 | 0.40 | 653.50 | 01-NOV-15:01 | 0.58 |
December | 0.131081E+09 | 0.40 | 653.50 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.142440E+10 | 0.37 | |||
Minimum of Months | 99711113.13 | 0.32 | 653.50 | 0.58 | |
Maximum of Months | 0.144939E+09 | 0.41 | 653.50 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110899E+10 | 0.44 | 1679.85 | 14-JAN-12:20 | 0.59 |
February | 0.701955E+09 | 0.36 | 1197.24 | 02-FEB-12:30 | 0.58 |
March | 0.521386E+09 | 0.31 | 1037.79 | 11-MAR-12:50 | 0.59 |
April | 0.544141E+09 | 0.39 | 688.33 | 04-APR-15:03 | 0.58 |
May | 0.378937E+09 | 0.35 | 578.54 | 04-MAY-20:40 | 0.58 |
June | 0.518542E+09 | 0.43 | 582.60 | 30-JUN-07:00 | 0.58 |
July | 0.746571E+09 | 0.51 | 674.43 | 31-JUL-15:05 | 0.58 |
August | 0.925259E+09 | 0.55 | 739.82 | 19-AUG-15:03 | 0.58 |
September | 0.103066E+10 | 0.55 | 1174.42 | 30-SEP-12:00 | 0.58 |
October | 0.136427E+10 | 0.53 | 2014.76 | 31-OCT-12:10 | 0.58 |
November | 0.114723E+10 | 0.47 | 2167.61 | 19-NOV-10:00 | 0.59 |
December | 0.126362E+10 | 0.46 | 2005.77 | 25-DEC-13:30 | 0.59 |
Annual Sum or Average | 0.102516E+11 | 0.45 | |||
Minimum of Months | 0.378937E+09 | 0.31 | 578.54 | 0.58 | |
Maximum of Months | 0.136427E+10 | 0.55 | 2167.61 | 0.59 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.833656E+09 | 0.38 | 4020.35 | 01-JAN-09:01 | 0.58 |
February | 0.738966E+09 | 0.39 | 4020.35 | 01-FEB-09:11 | 0.59 |
March | 0.948460E+09 | 0.40 | 4020.35 | 01-MAR-09:01 | 0.59 |
April | 0.997763E+09 | 0.36 | 4020.35 | 01-APR-08:62 | 0.59 |
May | 0.114865E+10 | 0.35 | 4020.35 | 01-MAY-08:11 | 0.58 |
June | 0.123251E+10 | 0.29 | 4020.35 | 01-JUN-08:11 | 0.58 |
July | 0.145491E+10 | 0.29 | 4020.35 | 01-JUL-08:11 | 0.58 |
August | 0.137056E+10 | 0.28 | 4020.35 | 01-AUG-08:11 | 0.58 |
September | 0.111800E+10 | 0.29 | 4020.35 | 01-SEP-08:11 | 0.58 |
October | 0.111086E+10 | 0.30 | 4020.35 | 01-OCT-08:11 | 0.58 |
November | 0.796298E+09 | 0.37 | 4020.35 | 01-NOV-08:61 | 0.58 |
December | 0.757426E+09 | 0.38 | 4020.35 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.125081E+11 | 0.34 | |||
Minimum of Months | 0.738966E+09 | 0.28 | 4020.35 | 0.58 | |
Maximum of Months | 0.145491E+10 | 0.40 | 4020.35 | 0.59 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146109E+09 | 0.48 | 582.02 | 01-JAN-09:01 | 0.58 |
February | 0.123513E+09 | 0.46 | 582.02 | 01-FEB-09:01 | 0.59 |
March | 0.144822E+09 | 0.45 | 582.02 | 01-MAR-09:01 | 0.58 |
April | 0.139725E+09 | 0.49 | 582.02 | 01-APR-08:62 | 0.58 |
May | 0.127926E+09 | 0.46 | 582.02 | 01-MAY-08:62 | 0.58 |
June | 0.144459E+09 | 0.48 | 582.02 | 01-JUN-08:62 | 0.58 |
July | 0.209163E+09 | 0.53 | 582.02 | 01-JUL-08:61 | 0.58 |
August | 0.222792E+09 | 0.54 | 582.02 | 01-AUG-08:62 | 0.58 |
September | 0.161996E+09 | 0.51 | 582.02 | 01-SEP-08:62 | 0.58 |
October | 0.187916E+09 | 0.51 | 582.02 | 01-OCT-08:61 | 0.58 |
November | 0.130862E+09 | 0.49 | 582.02 | 01-NOV-08:61 | 0.58 |
December | 0.148925E+09 | 0.49 | 582.02 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.188821E+10 | 0.49 | |||
Minimum of Months | 0.123513E+09 | 0.45 | 582.02 | 0.58 | |
Maximum of Months | 0.222792E+09 | 0.54 | 582.02 | 0.59 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.129339E+09 | 0.38 | 576.55 | 01-JAN-09:01 | 0.58 |
February | 0.108499E+09 | 0.40 | 576.55 | 01-FEB-09:11 | 0.59 |
March | 0.130362E+09 | 0.40 | 576.55 | 01-MAR-09:01 | 0.58 |
April | 0.108056E+09 | 0.39 | 576.55 | 01-APR-08:62 | 0.58 |
May | 0.104172E+09 | 0.38 | 576.55 | 01-MAY-08:11 | 0.58 |
June | 0.105635E+09 | 0.34 | 576.55 | 01-JUN-08:11 | 0.58 |
July | 0.149806E+09 | 0.35 | 576.55 | 01-JUL-08:11 | 0.58 |
August | 0.148701E+09 | 0.34 | 576.55 | 01-AUG-08:11 | 0.58 |
September | 93787822.37 | 0.33 | 576.55 | 01-SEP-08:11 | 0.58 |
October | 0.100390E+09 | 0.33 | 576.55 | 01-OCT-08:11 | 0.58 |
November | 98701393.12 | 0.38 | 576.55 | 01-NOV-08:61 | 0.58 |
December | 0.123636E+09 | 0.38 | 576.55 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.140109E+10 | 0.37 | |||
Minimum of Months | 93787822.37 | 0.33 | 576.55 | 0.58 | |
Maximum of Months | 0.149806E+09 | 0.40 | 576.55 | 0.59 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 44369301.34 | 0.48 | 172.88 | 02-JAN-16:02 | 0.59 |
February | 38537328.96 | 0.46 | 172.88 | 01-FEB-09:01 | 0.59 |
March | 45722921.61 | 0.46 | 172.88 | 01-MAR-16:01 | 0.58 |
April | 46109952.31 | 0.49 | 172.88 | 01-APR-15:02 | 0.59 |
May | 43461954.92 | 0.47 | 172.88 | 01-MAY-08:62 | 0.58 |
June | 53234210.33 | 0.50 | 172.88 | 01-JUN-15:01 | 0.58 |
July | 73864014.40 | 0.53 | 172.88 | 01-JUL-08:61 | 0.58 |
August | 73738759.12 | 0.54 | 172.88 | 01-AUG-08:62 | 0.58 |
September | 56649867.73 | 0.52 | 172.88 | 01-SEP-08:62 | 0.58 |
October | 58451177.96 | 0.51 | 172.88 | 01-OCT-08:61 | 0.58 |
November | 39461071.47 | 0.49 | 172.88 | 01-NOV-08:61 | 0.58 |
December | 44928555.30 | 0.49 | 172.88 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.618529E+09 | 0.50 | |||
Minimum of Months | 38537328.96 | 0.46 | 172.88 | 0.58 | |
Maximum of Months | 73864014.40 | 0.54 | 172.88 | 0.59 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 43333231.82 | 0.40 | 169.06 | 01-JAN-09:01 | 0.58 |
February | 34404743.79 | 0.41 | 169.06 | 01-FEB-16:01 | 0.58 |
March | 40474113.64 | 0.41 | 169.06 | 01-MAR-16:01 | 0.58 |
April | 30790695.62 | 0.41 | 169.06 | 01-APR-15:02 | 0.59 |
May | 31338414.73 | 0.39 | 169.06 | 01-MAY-08:11 | 0.58 |
June | 35344363.09 | 0.36 | 169.06 | 01-JUN-08:11 | 0.58 |
July | 48177616.92 | 0.35 | 169.06 | 01-JUL-08:11 | 0.58 |
August | 45038318.06 | 0.35 | 169.06 | 01-AUG-08:11 | 0.58 |
September | 32082730.22 | 0.35 | 169.06 | 01-SEP-08:11 | 0.58 |
October | 31005406.27 | 0.35 | 169.06 | 01-OCT-08:11 | 0.58 |
November | 30429874.39 | 0.41 | 169.06 | 01-NOV-15:01 | 0.58 |
December | 40500899.08 | 0.40 | 169.06 | 02-DEC-16:01 | 0.58 |
Annual Sum or Average | 0.442920E+09 | 0.38 | |||
Minimum of Months | 30429874.39 | 0.35 | 169.06 | 0.58 | |
Maximum of Months | 48177616.92 | 0.41 | 169.06 | 0.59 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355900E+09 | 0.53 | 758.17 | 01-JAN-09:01 | 0.58 |
February | 0.236712E+09 | 0.49 | 758.17 | 01-FEB-09:01 | 0.59 |
March | 0.224894E+09 | 0.48 | 758.17 | 01-MAR-09:01 | 0.58 |
April | 0.196656E+09 | 0.50 | 758.17 | 01-APR-08:62 | 0.59 |
May | 0.153783E+09 | 0.45 | 758.17 | 01-MAY-08:62 | 0.58 |
June | 0.173770E+09 | 0.46 | 758.17 | 01-JUN-08:62 | 0.58 |
July | 0.255643E+09 | 0.50 | 758.17 | 01-JUL-08:61 | 0.58 |
August | 0.303500E+09 | 0.52 | 758.17 | 01-AUG-08:62 | 0.58 |
September | 0.308230E+09 | 0.52 | 758.17 | 01-SEP-08:62 | 0.58 |
October | 0.416771E+09 | 0.53 | 758.17 | 01-OCT-08:61 | 0.58 |
November | 0.333026E+09 | 0.53 | 758.17 | 01-NOV-08:61 | 0.58 |
December | 0.382991E+09 | 0.53 | 758.17 | 01-DEC-09:01 | 0.58 |
Annual Sum or Average | 0.334188E+10 | 0.50 | |||
Minimum of Months | 0.153783E+09 | 0.45 | 758.17 | 0.58 | |
Maximum of Months | 0.416771E+09 | 0.53 | 758.17 | 0.59 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.121211E+10 | 0.109090E+10 | 1210.77 | 08-JAN-06:50 | 1089.69 | 1089.69 | 50.42 | 3.89 |
February | 0.972570E+09 | 0.875313E+09 | 1165.69 | 04-FEB-06:00 | 1049.12 | 1049.12 | 51.18 | 3.28 |
March | 0.128167E+10 | 0.115350E+10 | 1207.50 | 30-MAR-03:00 | 1086.75 | 1086.75 | 51.08 | 3.84 |
April | 0.539039E+09 | 0.485135E+09 | 1148.76 | 01-APR-05:00 | 1033.88 | 1033.88 | 51.30 | 3.08 |
May | 0.506747E+09 | 0.456072E+09 | 1116.35 | 14-MAY-04:30 | 1004.72 | 1004.72 | 51.20 | 2.77 |
June | 0.167127E+09 | 0.150414E+09 | 785.69 | 13-JUN-04:00 | 707.12 | 707.12 | 47.99 | 1.32 |
July | 0.110273E+09 | 99245698.52 | 353.58 | 10-JUL-08:15 | 318.22 | 318.22 | 43.94 | 0.48 |
August | 0.106138E+09 | 95524427.53 | 361.63 | 03-AUG-08:16 | 325.47 | 325.47 | 44.10 | 0.49 |
September | 0.133381E+09 | 0.120043E+09 | 768.56 | 20-SEP-04:00 | 691.70 | 691.70 | 47.95 | 1.28 |
October | 0.256262E+09 | 0.230635E+09 | 1089.87 | 12-OCT-05:00 | 980.88 | 980.88 | 51.09 | 2.56 |
November | 0.805287E+09 | 0.724758E+09 | 1147.89 | 24-NOV-04:00 | 1033.10 | 1033.10 | 51.28 | 3.07 |
December | 0.119849E+10 | 0.107864E+10 | 1176.21 | 23-DEC-06:00 | 1058.59 | 1058.59 | 51.15 | 3.42 |
Annual Sum or Average | 0.728909E+10 | 0.656018E+10 | ||||||
Minimum of Months | 0.106138E+09 | 95524427.53 | 353.58 | 318.22 | 318.22 | 43.94 | 0.48 | |
Maximum of Months | 0.128167E+10 | 0.115350E+10 | 1210.77 | 1089.69 | 1089.69 | 51.30 | 3.89 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.125683E+09 | 0.113115E+09 | 838.50 | 24-JAN-09:11 | 754.65 | 754.65 | 6.71 | 10.45 |
February | 70459731.49 | 63413758.34 | 448.63 | 01-FEB-16:01 | 403.77 | 403.77 | 6.71 | 7.98 |
March | 73020798.50 | 65718718.65 | 776.19 | 23-MAR-15:03 | 698.57 | 698.57 | 6.71 | 10.11 |
April | 0.150648E+09 | 0.135583E+09 | 670.67 | 11-APR-15:03 | 603.60 | 603.60 | 6.71 | 9.50 |
May | 0.149174E+09 | 0.134256E+09 | 640.87 | 18-MAY-15:03 | 576.79 | 576.79 | 6.71 | 9.32 |
June | 0.306984E+09 | 0.276285E+09 | 772.29 | 28-JUN-15:03 | 695.06 | 695.06 | 6.71 | 10.09 |
July | 0.718392E+09 | 0.646553E+09 | 1293.66 | 31-JUL-15:05 | 1164.29 | 1164.29 | 6.71 | 12.53 |
August | 0.839911E+09 | 0.755920E+09 | 1385.82 | 17-AUG-15:03 | 1247.24 | 1247.24 | 6.71 | 12.89 |
September | 0.492619E+09 | 0.443357E+09 | 1790.29 | 29-SEP-15:13 | 1611.26 | 1611.26 | 6.71 | 14.31 |
October | 0.519399E+09 | 0.467459E+09 | 1354.32 | 17-OCT-15:13 | 1218.89 | 1218.89 | 6.71 | 12.76 |
November | 0.134670E+09 | 0.121203E+09 | 945.38 | 18-NOV-16:01 | 850.84 | 850.84 | 6.71 | 10.99 |
December | 0.116445E+09 | 0.104800E+09 | 680.22 | 16-DEC-16:01 | 612.20 | 612.20 | 6.71 | 9.56 |
Annual Sum or Average | 0.369740E+10 | 0.332766E+10 | ||||||
Minimum of Months | 70459731.49 | 63413758.34 | 448.63 | 403.77 | 403.77 | 6.71 | 7.98 | |
Maximum of Months | 0.839911E+09 | 0.755920E+09 | 1790.29 | 1611.26 | 1611.26 | 6.71 | 14.31 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 50.19 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:03 | 14.37 | 14.37 | 49.57 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 50.28 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 53.13 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 51.60 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 52.61 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.58 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.85 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 53.71 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 52.24 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:10 | 14.37 | 14.37 | 53.32 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 50.34 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 49.57 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 53.71 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.282997E+10 | 0.254697E+10 | 1213.28 | 01-JAN-00:10 | 1091.95 | 1091.95 | 6.77 | 19.03 |
February | 0.268189E+10 | 0.241370E+10 | 1213.28 | 01-FEB-00:03 | 1091.95 | 1091.95 | 6.83 | 19.03 |
March | 0.280777E+10 | 0.252699E+10 | 1213.28 | 01-MAR-00:03 | 1091.95 | 1091.95 | 6.71 | 19.03 |
April | 0.311278E+10 | 0.280151E+10 | 1213.28 | 01-APR-00:20 | 1091.95 | 1091.95 | 6.73 | 19.03 |
May | 0.324436E+10 | 0.291993E+10 | 1213.28 | 01-MAY-00:03 | 1091.95 | 1091.95 | 7.60 | 19.03 |
June | 0.314481E+10 | 0.283033E+10 | 1213.28 | 01-JUN-00:05 | 1091.95 | 1091.95 | 6.90 | 19.03 |
July | 0.324964E+10 | 0.292468E+10 | 1213.28 | 01-JUL-00:10 | 1091.95 | 1091.95 | 8.66 | 19.03 |
August | 0.324964E+10 | 0.292468E+10 | 1213.28 | 01-AUG-00:10 | 1091.95 | 1091.95 | 9.73 | 19.03 |
September | 0.314481E+10 | 0.283033E+10 | 1213.28 | 01-SEP-00:10 | 1091.95 | 1091.95 | 7.94 | 19.03 |
October | 0.324964E+10 | 0.292468E+10 | 1213.28 | 01-OCT-00:05 | 1091.95 | 1091.95 | 9.92 | 19.03 |
November | 0.300929E+10 | 0.270836E+10 | 1213.28 | 01-NOV-00:10 | 1091.95 | 1091.95 | 7.28 | 19.03 |
December | 0.289500E+10 | 0.260550E+10 | 1213.28 | 01-DEC-00:03 | 1091.95 | 1091.95 | 6.86 | 19.03 |
Annual Sum or Average | 0.366196E+11 | 0.329577E+11 | ||||||
Minimum of Months | 0.268189E+10 | 0.241370E+10 | 1213.28 | 1091.95 | 1091.95 | 6.71 | 19.03 | |
Maximum of Months | 0.324964E+10 | 0.292468E+10 | 1213.28 | 1091.95 | 1091.95 | 9.92 | 19.03 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 50.19 | 59.90 | 24005.52 | 49045.67 | 27-JAN-07:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 49.57 | 58.29 | 24085.80 | 49037.52 | 09-FEB-07:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.28 | 59.14 | 23747.50 | 48893.71 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 53.13 | 59.52 | 23200.75 | 47898.39 | 03-APR-07:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 51.60 | 58.21 | 22519.04 | 46911.58 | 02-MAY-06:57 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 52.61 | 58.77 | 21939.74 | 45769.08 | 02-JUN-06:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.58 | 58.38 | 21633.13 | 44797.29 | 03-JUL-06:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.85 | 58.64 | 21606.15 | 44719.10 | 31-AUG-06:15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 53.71 | 59.70 | 21788.16 | 45485.95 | 29-SEP-06:15 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 52.24 | 58.99 | 22391.72 | 46650.47 | 31-OCT-06:10 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 53.32 | 59.55 | 22964.12 | 47745.47 | 30-NOV-07:50 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 50.34 | 58.97 | 23614.42 | 48616.52 | 28-DEC-07:10 |
Annual Sum or Average | 0.00 | 22784.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 49.57 | 58.21 | 21606.15 | 44719.10 | ||
Maximum of Months | 0.00 | 0.00 | 53.71 | 59.90 | 24085.80 | 49045.67 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 51.13 | 60.00 | 40693.68 | 156510.15 | 08-JAN-07:00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 44.58 | 60.00 | 34351.62 | 123055.45 | 05-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 51.04 | 60.00 | 42843.46 | 143409.56 | 30-MAR-03:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 50.91 | 60.00 | 18318.85 | 112122.20 | 01-APR-05:00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 42.11 | 60.00 | 16543.31 | 101998.06 | 27-MAY-03:00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 40.97 | 60.00 | 5602.97 | 66425.40 | 13-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 40.28 | 60.00 | 3539.72 | 31986.36 | 10-JUL-08:15 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 39.83 | 60.00 | 3327.43 | 32508.65 | 03-AUG-08:16 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 40.37 | 60.00 | 4324.26 | 64457.04 | 20-SEP-04:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 40.20 | 60.00 | 8115.18 | 96097.08 | 28-OCT-05:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 40.28 | 60.00 | 26765.93 | 112095.26 | 24-NOV-04:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.24 | 60.00 | 39437.09 | 126826.57 | 24-DEC-04:00 |
Annual Sum or Average | 0.00 | 20278.64 | ||||||
Minimum of Months | 0.00 | 0.00 | 39.83 | 60.00 | 3327.43 | 31986.36 | ||
Maximum of Months | 0.00 | 0.00 | 51.13 | 60.00 | 42843.46 | 156510.15 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 52676.71 | 354901.85 | 14-JAN-16:01 | 11.15 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 39587.85 | 307638.01 | 01-FEB-09:11 | 10.56 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 35717.43 | 400425.26 | 23-MAR-15:03 | 11.72 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 67537.09 | 385211.13 | 11-APR-15:03 | 11.53 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 67796.46 | 325464.47 | 04-MAY-15:03 | 10.78 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 124224.67 | 437303.26 | 28-JUN-15:03 | 12.19 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 218937.37 | 560587.14 | 31-JUL-15:05 | 13.74 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 243727.74 | 589430.99 | 17-AUG-15:03 | 14.10 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 165369.35 | 555598.41 | 21-SEP-15:03 | 13.68 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 164764.09 | 523241.14 | 01-OCT-15:03 | 13.27 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 59562.55 | 404051.30 | 18-NOV-16:01 | 11.77 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 57939.58 | 380603.16 | 05-DEC-09:11 | 11.48 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 108760.58 | 0.00 | ||||||
Minimum of Months | 35717.43 | 307638.01 | 10.56 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 243727.74 | 589430.99 | 14.10 | 6.70 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.06 | 4.20 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.06 | 4.20 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.06 | 4.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 56.92 |
February | 0.08 | 56.92 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.58 | 56.92 |
July | 1.25 | 56.92 |
August | 1.50 | 56.92 |
September | 0.50 | 56.92 |
October | 0.58 | 56.92 |
November | 0.08 | 56.92 |
December | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 56.92 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.50 | 56.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.33 | 0.43 |
February | 1.25 | 0.54 |
March | 1.54 | 0.71 |
April | 2.14 | 0.75 |
May | 2.72 | 0.77 |
June | 1.65 | 0.74 |
July | 2.21 | 0.48 |
August | 3.31 | 0.54 |
September | 4.31 | 0.70 |
October | 4.04 | 0.60 |
November | 1.82 | 0.49 |
December | 1.57 | 0.44 |
Annual Sum or Average | 27.89 | 0.61 |
Minimum of Months | 1.25 | 0.43 |
Maximum of Months | 4.31 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.29 | 0.67 |
March | 0.69 | 0.77 |
April | 1.36 | 0.70 |
May | 1.36 | 0.64 |
June | 1.91 | 0.66 |
July | 3.84 | 0.52 |
August | 3.46 | 0.57 |
September | 1.74 | 0.72 |
October | 1.96 | 0.60 |
November | 0.11 | 0.81 |
December | 0.10 | 0.81 |
Annual Sum or Average | 16.81 | 0.62 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.84 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.03 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.03 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.03 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.14 | 0.79 |
February | 0.43 | 0.76 |
March | 1.25 | 0.81 |
April | 1.42 | 0.79 |
May | 1.19 | 0.70 |
June | 0.26 | 0.66 |
July | 1.35 | 1.06 |
August | 0.93 | 1.22 |
September | 1.43 | 0.76 |
October | 2.17 | 0.88 |
November | 0.58 | 0.81 |
December | 0.74 | 0.80 |
Annual Sum or Average | 11.89 | 0.86 |
Minimum of Months | 0.14 | 0.66 |
Maximum of Months | 2.17 | 1.22 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.81 | 0.46 |
February | 2.78 | 0.48 |
March | 2.08 | 0.51 |
April | 2.39 | 0.59 |
May | 1.65 | 0.60 |
June | 2.99 | 0.68 |
July | 5.99 | 0.62 |
August | 5.07 | 0.65 |
September | 2.75 | 0.65 |
October | 3.45 | 0.58 |
November | 2.61 | 0.42 |
December | 3.28 | 0.52 |
Annual Sum or Average | 37.84 | 0.57 |
Minimum of Months | 1.65 | 0.42 |
Maximum of Months | 5.99 | 0.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.15 | 0.65 |
February | 0.42 | 0.65 |
March | 0.88 | 0.58 |
April | 1.73 | 0.52 |
May | 1.01 | 0.51 |
June | 0.90 | 0.48 |
July | 2.00 | 0.43 |
August | 1.94 | 0.46 |
September | 1.37 | 0.54 |
October | 1.84 | 0.55 |
November | 0.50 | 0.65 |
December | 0.60 | 0.77 |
Annual Sum or Average | 13.34 | 0.53 |
Minimum of Months | 0.15 | 0.43 |
Maximum of Months | 2.00 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.38 | 0.41 |
February | 1.85 | 0.60 |
March | 1.76 | 0.69 |
April | 2.29 | 0.68 |
May | 1.78 | 0.74 |
June | 1.32 | 0.60 |
July | 2.94 | 0.45 |
August | 2.69 | 0.45 |
September | 3.47 | 0.69 |
October | 4.08 | 0.61 |
November | 1.87 | 0.48 |
December | 1.46 | 0.42 |
Annual Sum or Average | 26.90 | 0.58 |
Minimum of Months | 1.32 | 0.41 |
Maximum of Months | 4.08 | 0.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 0.68 |
February | 0.60 | 0.74 |
March | 1.13 | 0.75 |
April | 1.54 | 0.63 |
May | 2.03 | 0.66 |
June | 2.03 | 0.66 |
July | 3.79 | 0.49 |
August | 4.04 | 0.56 |
September | 2.60 | 0.72 |
October | 2.28 | 0.65 |
November | 0.33 | 0.69 |
December | 0.26 | 0.81 |
Annual Sum or Average | 20.85 | 0.62 |
Minimum of Months | 0.22 | 0.49 |
Maximum of Months | 4.04 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.31 | 0.77 |
February | 3.06 | 0.72 |
March | 2.62 | 0.67 |
April | 2.10 | 0.66 |
May | 0.57 | 0.59 |
June | 1.74 | 0.70 |
July | 5.19 | 0.62 |
August | 5.22 | 0.62 |
September | 3.53 | 0.66 |
October | 2.96 | 0.73 |
November | 3.47 | 0.72 |
December | 4.08 | 0.73 |
Annual Sum or Average | 37.85 | 0.68 |
Minimum of Months | 0.57 | 0.59 |
Maximum of Months | 5.22 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 99.96 |
February | 0.00 | 0.00 |
March | 0.17 | 99.96 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 99.96 |
September | 0.17 | 99.96 |
October | 0.25 | 99.96 |
November | 0.08 | 149.94 |
December | 0.42 | 99.96 |
Annual Sum or Average | 1.33 | 103.08 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.42 | 149.94 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 99.96 |
February | 0.00 | 0.00 |
March | 0.08 | 99.96 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 99.96 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 99.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.08 | 20.01 |
May | 0.08 | 20.01 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.08 | 20.01 |
Annual Sum or Average | 0.25 | 20.01 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.08 | 20.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.962135E+11 | 0.00 | 0.798106E+11 | 0.358482E+11 | 0.00 | 0.00 |
February | 0.742079E+11 | 0.00 | 0.501066E+11 | 0.330836E+11 | 0.00 | 0.00 |
March | 0.102143E+12 | 0.00 | 0.524697E+11 | 0.366135E+11 | 0.00 | 0.00 |
April | 0.429138E+11 | 0.00 | 0.114565E+12 | 0.353374E+11 | 0.00 | 0.00 |
May | 0.402611E+11 | 0.00 | 0.123752E+12 | 0.364144E+11 | 0.00 | 0.00 |
June | 0.138566E+11 | 0.00 | 0.243089E+12 | 0.345439E+11 | 0.00 | 0.00 |
July | 0.950494E+10 | 0.00 | 0.468005E+12 | 0.350728E+11 | 0.00 | 0.00 |
August | 0.895332E+10 | 0.00 | 0.524287E+12 | 0.350793E+11 | 0.00 | 0.00 |
September | 0.108764E+11 | 0.00 | 0.325816E+12 | 0.340417E+11 | 0.00 | 0.00 |
October | 0.200874E+11 | 0.00 | 0.329391E+12 | 0.351978E+11 | 0.00 | 0.00 |
November | 0.621178E+11 | 0.00 | 0.874223E+11 | 0.353134E+11 | 0.00 | 0.00 |
December | 0.939417E+11 | 0.00 | 0.888017E+11 | 0.360831E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.575078E+12 | 0.00 | 0.248752E+13 | 0.422629E+12 | 0.00 | 0.00 |
Minimum of Months | 0.895332E+10 | 0.00 | 0.501066E+11 | 0.330836E+11 | 0.00 | 0.00 |
Maximum of Months | 0.102143E+12 | 0.00 | 0.524287E+12 | 0.366135E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.802855E+10 | 0.00 | 0.351486E+10 | 0.270916E+10 | 0.00 | 0.00 |
February | 0.644175E+10 | 0.00 | 0.189168E+10 | 0.244698E+10 | 0.00 | 0.00 |
March | 0.862931E+10 | 0.00 | 0.212621E+10 | 0.270916E+10 | 0.00 | 0.00 |
April | 0.405762E+10 | 0.00 | 0.532087E+10 | 0.262177E+10 | 0.00 | 0.00 |
May | 0.361148E+10 | 0.00 | 0.566791E+10 | 0.270916E+10 | 0.00 | 0.00 |
June | 0.639208E+09 | 0.00 | 0.126650E+11 | 0.262177E+10 | 0.00 | 0.00 |
July | 37016963.46 | 0.00 | 0.283929E+11 | 0.270916E+10 | 0.00 | 0.00 |
August | 17468304.78 | 0.00 | 0.324272E+11 | 0.270916E+10 | 0.00 | 0.00 |
September | 0.318953E+09 | 0.00 | 0.184524E+11 | 0.262177E+10 | 0.00 | 0.00 |
October | 0.143547E+10 | 0.00 | 0.205486E+11 | 0.270916E+10 | 0.00 | 0.00 |
November | 0.566040E+10 | 0.00 | 0.353985E+10 | 0.262177E+10 | 0.00 | 0.00 |
December | 0.806490E+10 | 0.00 | 0.428200E+10 | 0.270916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.469421E+11 | 0.00 | 0.138829E+12 | 0.318982E+11 | 0.00 | 0.00 |
Minimum of Months | 17468304.78 | 0.00 | 0.189168E+10 | 0.244698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.862931E+10 | 0.00 | 0.324272E+11 | 0.270916E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.358482E+11 | 0.798106E+11 | 0.962135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330836E+11 | 0.501066E+11 | 0.742079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366135E+11 | 0.524697E+11 | 0.102143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353374E+11 | 0.114565E+12 | 0.429138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364144E+11 | 0.123752E+12 | 0.402611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.345439E+11 | 0.243089E+12 | 0.138566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350728E+11 | 0.468005E+12 | 0.950494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350793E+11 | 0.524287E+12 | 0.895332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340417E+11 | 0.325816E+12 | 0.108764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351978E+11 | 0.329391E+12 | 0.200874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.353134E+11 | 0.874223E+11 | 0.621178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360831E+11 | 0.888017E+11 | 0.939417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.422629E+12 | 0.248752E+13 | 0.575078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.330836E+11 | 0.501066E+11 | 0.895332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.366135E+11 | 0.524287E+12 | 0.102143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270916E+10 | 0.351486E+10 | 0.802855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.189168E+10 | 0.644175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.212621E+10 | 0.862931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.532087E+10 | 0.405762E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 0.566791E+10 | 0.361148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 0.126650E+11 | 0.639208E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 0.283929E+11 | 37016963.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 0.324272E+11 | 17468304.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 0.184524E+11 | 0.318953E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 0.205486E+11 | 0.143547E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 0.353985E+10 | 0.566040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.428200E+10 | 0.806490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.138829E+12 | 0.469421E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244698E+10 | 0.189168E+10 | 17468304.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.324272E+11 | 0.862931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.358482E+11 | 0.962135E+11 | 0.798106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330836E+11 | 0.742079E+11 | 0.501066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366135E+11 | 0.102143E+12 | 0.524697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353374E+11 | 0.429138E+11 | 0.114565E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364144E+11 | 0.402611E+11 | 0.123752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.345439E+11 | 0.138566E+11 | 0.243089E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.350728E+11 | 0.950494E+10 | 0.468005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350793E+11 | 0.895332E+10 | 0.524287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.340417E+11 | 0.108764E+11 | 0.325816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.351978E+11 | 0.200874E+11 | 0.329391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.353134E+11 | 0.621178E+11 | 0.874223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360831E+11 | 0.939417E+11 | 0.888017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.422629E+12 | 0.575078E+12 | 0.248752E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.330836E+11 | 0.895332E+10 | 0.501066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.366135E+11 | 0.102143E+12 | 0.524287E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.270916E+10 | 0.802855E+10 | 0.351486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.644175E+10 | 0.189168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.862931E+10 | 0.212621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.405762E+10 | 0.532087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 0.361148E+10 | 0.566791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 0.639208E+09 | 0.126650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 37016963.46 | 0.283929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 17468304.78 | 0.324272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 0.318953E+09 | 0.184524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 0.143547E+10 | 0.205486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 0.566040E+10 | 0.353985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.806490E+10 | 0.428200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.469421E+11 | 0.138829E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.244698E+10 | 17468304.78 | 0.189168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.862931E+10 | 0.324272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.513386E+11 | 0.00 | 0.00 | 57592.36 | 0.214311E+09 | 0.00 | 0.670684E+09 | 0.00 | 1.03 |
February | 0.464867E+11 | 0.00 | 0.00 | 0.00 | 41407022.01 | 0.00 | 0.00 | 0.00 | 1.03 |
March | 0.536350E+11 | 0.00 | 0.00 | 0.00 | 0.115789E+09 | 0.00 | 0.00 | 0.00 | 1.03 |
April | 0.404222E+11 | 0.00 | 0.00 | 0.00 | 0.378723E+09 | 0.00 | 0.00 | 0.00 | 1.03 |
May | 0.404290E+11 | 0.00 | 0.00 | 0.00 | 76932429.23 | 0.00 | 0.00 | 0.00 | 1.03 |
June | 0.268982E+11 | 0.00 | 0.00 | 0.00 | 0.235994E+10 | 0.00 | 0.00 | 0.00 | 1.03 |
July | 0.129829E+11 | 0.00 | 0.00 | 0.00 | 0.100735E+11 | 0.00 | 0.00 | 0.00 | 1.03 |
August | 0.969331E+10 | 0.00 | 0.00 | 0.00 | 0.126060E+11 | 0.00 | 0.00 | 0.00 | 1.04 |
September | 0.211992E+11 | 0.00 | 0.00 | 0.00 | 0.467047E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
October | 0.257608E+11 | 0.00 | 0.00 | 0.00 | 0.641073E+10 | 0.00 | 0.00 | 0.00 | 1.04 |
November | 0.414897E+11 | 0.00 | 0.00 | 976952.16 | 0.125126E+09 | 0.00 | 0.461857E+10 | 0.00 | 1.03 |
December | 0.499620E+11 | 0.00 | 0.00 | 150186.68 | 0.103143E+09 | 0.00 | 0.890859E+09 | 0.00 | 1.03 |
Annual Sum or Average | 0.420298E+12 | 0.00 | 0.00 | 1184731.20 | 0.371761E+11 | 0.00 | 0.618012E+10 | 0.00 | 1.03 |
Minimum of Months | 0.969331E+10 | 0.00 | 0.00 | 0.00 | 41407022.01 | 0.00 | 0.00 | 0.00 | 1.03 |
Maximum of Months | 0.536350E+11 | 0.00 | 0.00 | 976952.16 | 0.126060E+11 | 0.00 | 0.461857E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.577920E+10 | 18698371.00 | 0.00 | 1177857.59 | 10133761.78 | 76743061.43 | 0.486507E+09 | 0.00 | 2.28 |
February | 0.541776E+10 | 4291172.46 | 0.00 | 554945.83 | 832504.57 | 0.00 | 0.238741E+09 | 0.00 | 2.28 |
March | 0.634031E+10 | 4689978.65 | 0.00 | 54689.69 | 9397457.14 | 0.163375E+09 | 21773746.18 | 0.00 | 2.28 |
April | 0.491593E+10 | 0.00 | 0.00 | 0.00 | 46077363.70 | 2042254.31 | 0.00 | 0.00 | 2.28 |
May | 0.491880E+10 | 0.00 | 0.00 | 0.00 | 9359990.23 | 0.00 | 0.00 | 0.00 | 2.28 |
June | 0.327258E+10 | 0.00 | 0.00 | 0.00 | 0.287123E+09 | 0.00 | 0.00 | 0.00 | 2.28 |
July | 0.157957E+10 | 0.00 | 0.00 | 0.00 | 0.122559E+10 | 0.00 | 0.00 | 0.00 | 2.28 |
August | 0.117934E+10 | 0.00 | 0.00 | 0.00 | 0.153371E+10 | 0.00 | 0.00 | 0.00 | 2.29 |
September | 0.257264E+10 | 0.134324E+09 | 0.00 | 14542.52 | 0.446267E+09 | 0.00 | 6544902.66 | 0.00 | 2.30 |
October | 0.302376E+10 | 0.400189E+09 | 0.00 | 385479.80 | 0.445963E+09 | 0.00 | 0.110699E+09 | 0.00 | 2.33 |
November | 0.523842E+10 | 18504217.50 | 0.00 | 1262446.94 | 336042.00 | 0.00 | 0.384180E+09 | 0.00 | 2.30 |
December | 0.576621E+10 | 14318123.60 | 0.00 | 1779944.31 | 678438.42 | 0.00 | 0.440101E+09 | 0.00 | 2.31 |
Annual Sum or Average | 0.500045E+11 | 0.595015E+09 | 0.00 | 5229906.69 | 0.401548E+10 | 0.242160E+09 | 0.168855E+10 | 0.00 | 2.29 |
Minimum of Months | 0.117934E+10 | 0.00 | 0.00 | 0.00 | 336042.00 | 0.00 | 0.00 | 0.00 | 2.28 |
Maximum of Months | 0.634031E+10 | 0.400189E+09 | 0.00 | 1779944.31 | 0.153371E+10 | 0.163375E+09 | 0.486507E+09 | 0.00 | 2.33 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.454732E+10 | 0.00 | 0.00 | 79575.82 | 20181649.32 | 0.00 | 0.350318E+09 | 0.00 | 1.52 |
February | 0.397689E+10 | 0.00 | 0.00 | 128216.86 | 3899291.33 | 0.00 | 0.400628E+09 | 0.00 | 1.53 |
March | 0.480857E+10 | 0.00 | 0.00 | 59609.29 | 10903795.24 | 0.00 | 0.242169E+09 | 0.00 | 1.53 |
April | 0.349651E+10 | 0.00 | 0.00 | 85476.42 | 35664271.81 | 0.00 | 0.309960E+09 | 0.00 | 1.53 |
May | 0.359040E+10 | 0.00 | 0.00 | 38319.39 | 7244712.13 | 0.00 | 0.216751E+09 | 0.00 | 1.53 |
June | 0.237417E+10 | 0.00 | 0.00 | 36267.62 | 0.222236E+09 | 0.00 | 0.158790E+09 | 0.00 | 1.53 |
July | 0.114424E+10 | 3914710.36 | 0.00 | 38606.95 | 0.944705E+09 | 0.00 | 78319001.78 | 0.00 | 1.53 |
August | 0.811682E+09 | 3918662.59 | 0.00 | 68520.37 | 0.118319E+10 | 0.00 | 0.101067E+09 | 0.00 | 1.53 |
September | 0.178985E+10 | 3472839.92 | 0.00 | 114845.74 | 0.436344E+09 | 0.00 | 0.206352E+09 | 0.00 | 1.54 |
October | 0.205862E+10 | 4561446.98 | 0.00 | 281204.27 | 0.599136E+09 | 0.00 | 0.367079E+09 | 0.00 | 1.53 |
November | 0.370356E+10 | 0.00 | 0.00 | 208990.40 | 11783108.13 | 0.00 | 0.638327E+09 | 0.00 | 1.52 |
December | 0.431413E+10 | 0.00 | 0.00 | 144510.41 | 9712955.68 | 0.00 | 0.474543E+09 | 0.00 | 1.52 |
Annual Sum or Average | 0.366159E+11 | 15867659.85 | 0.00 | 1284143.54 | 0.348500E+10 | 0.00 | 0.354430E+10 | 0.00 | 1.53 |
Minimum of Months | 0.811682E+09 | 0.00 | 0.00 | 36267.62 | 3899291.33 | 0.00 | 78319001.78 | 0.00 | 1.52 |
Maximum of Months | 0.480857E+10 | 4561446.98 | 0.00 | 281204.27 | 0.118319E+10 | 0.00 | 0.638327E+09 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.484961E+10 | 0.00 | 0.00 | 0.00 | 19983412.53 | 0.00 | 0.00 | 0.00 | 0.71 |
February | 0.433464E+10 | 0.00 | 0.00 | 0.00 | 3860990.06 | 0.00 | 0.00 | 0.00 | 0.71 |
March | 0.500119E+10 | 0.00 | 0.00 | 0.00 | 10796691.35 | 0.00 | 0.00 | 0.00 | 0.71 |
April | 0.376916E+10 | 0.00 | 0.00 | 0.00 | 35313955.03 | 0.00 | 0.00 | 0.00 | 0.71 |
May | 0.376979E+10 | 0.00 | 0.00 | 0.00 | 7173550.04 | 0.00 | 0.00 | 0.00 | 0.71 |
June | 0.250812E+10 | 0.00 | 0.00 | 0.00 | 0.220053E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
July | 0.121059E+10 | 0.00 | 0.00 | 0.00 | 0.939302E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 0.903851E+09 | 0.00 | 0.00 | 0.00 | 0.117545E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 0.197671E+10 | 0.00 | 0.00 | 0.00 | 0.435497E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.240206E+10 | 0.00 | 0.00 | 0.00 | 0.597767E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
November | 0.429944E+10 | 0.00 | 0.00 | 0.00 | 11667367.07 | 0.00 | 0.00 | 0.00 | 0.71 |
December | 0.474178E+10 | 0.00 | 0.00 | 0.00 | 9617548.96 | 0.00 | 0.00 | 0.00 | 0.71 |
Annual Sum or Average | 0.397670E+11 | 0.00 | 0.00 | 0.00 | 0.346648E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
Minimum of Months | 0.903851E+09 | 0.00 | 0.00 | 0.00 | 3860990.06 | 0.00 | 0.00 | 0.00 | 0.71 |
Maximum of Months | 0.500119E+10 | 0.00 | 0.00 | 0.00 | 0.117545E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.204730E+10 | 0.00 | 0.00 | 0.00 | 8461598.74 | 6169974.78 | 0.00 | 0.00 | 0.52 |
February | 0.183542E+10 | 0.00 | 0.00 | 0.00 | 1634863.34 | 0.00 | 0.00 | 0.00 | 0.52 |
March | 0.210361E+10 | 0.00 | 0.00 | 0.00 | 4571655.10 | 14053044.33 | 0.00 | 0.00 | 0.52 |
April | 0.159598E+10 | 0.00 | 0.00 | 0.00 | 14953027.52 | 0.00 | 0.00 | 0.00 | 0.52 |
May | 0.159625E+10 | 0.00 | 0.00 | 0.00 | 3037504.32 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 0.106202E+10 | 0.00 | 0.00 | 0.00 | 93177108.11 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.512601E+09 | 0.00 | 0.00 | 0.00 | 0.397730E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.382719E+09 | 0.00 | 0.00 | 0.00 | 0.497721E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.837002E+09 | 0.00 | 0.00 | 0.00 | 0.184403E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.101711E+10 | 0.00 | 0.00 | 0.00 | 0.253113E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.182052E+10 | 0.00 | 0.00 | 0.00 | 4940326.30 | 0.00 | 0.00 | 0.00 | 0.52 |
December | 0.200782E+10 | 0.00 | 0.00 | 0.00 | 4072369.52 | 0.00 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.168183E+11 | 0.00 | 0.00 | 0.00 | 0.146782E+10 | 20223019.10 | 0.00 | 0.00 | 0.52 |
Minimum of Months | 0.382719E+09 | 0.00 | 0.00 | 0.00 | 1634863.34 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.210361E+10 | 0.00 | 0.00 | 0.00 | 0.497721E+09 | 14053044.33 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104914E+10 | 0.291740E+09 | 0.00 | 84841474.63 | 6087785.16 | 0.00 | 0.793679E+11 | 0.00 | 24.38 |
February | 0.785476E+09 | 54478714.92 | 0.00 | 77604216.03 | 3064539.81 | 0.00 | 0.715080E+11 | 0.00 | 24.70 |
March | 0.721979E+09 | 0.147173E+09 | 0.00 | 84393951.34 | 13737807.85 | 0.00 | 0.827506E+11 | 0.00 | 24.77 |
April | 0.596320E+09 | 0.499498E+09 | 0.00 | 86614793.55 | 26812994.93 | 0.00 | 0.620557E+11 | 0.00 | 24.51 |
May | 0.595726E+09 | 0.104750E+09 | 0.00 | 93394244.75 | 2162659.03 | 0.00 | 0.618733E+11 | 0.00 | 24.46 |
June | 0.311679E+09 | 0.300303E+10 | 0.00 | 85300770.13 | 0.283730E+09 | 0.00 | 0.409099E+11 | 0.00 | 24.21 |
July | 0.106184E+09 | 0.130368E+11 | 0.00 | 62089794.27 | 0.119919E+10 | 0.00 | 0.193485E+11 | 0.00 | 23.92 |
August | 65574838.31 | 0.161498E+11 | 0.00 | 55409589.58 | 0.155526E+10 | 0.00 | 0.146637E+11 | 0.00 | 24.01 |
September | 0.269883E+09 | 0.617960E+10 | 0.00 | 73901625.60 | 0.367291E+09 | 0.00 | 0.320191E+11 | 0.00 | 24.16 |
October | 0.272783E+09 | 0.870414E+10 | 0.00 | 67996457.82 | 0.384388E+09 | 0.00 | 0.389119E+11 | 0.00 | 24.02 |
November | 0.598345E+09 | 0.170508E+09 | 0.00 | 83362875.96 | 3379549.99 | 0.00 | 0.710665E+11 | 0.00 | 24.56 |
December | 0.649083E+09 | 0.135537E+09 | 0.00 | 85187222.53 | 7800911.22 | 0.00 | 0.784255E+11 | 0.00 | 24.45 |
Annual Sum or Average | 0.602218E+10 | 0.484770E+11 | 0.00 | 0.940097E+09 | 0.385290E+10 | 0.00 | 0.652901E+12 | 0.00 | 24.34 |
Minimum of Months | 65574838.31 | 54478714.92 | 0.00 | 55409589.58 | 2162659.03 | 0.00 | 0.146637E+11 | 0.00 | 23.92 |
Maximum of Months | 0.104914E+10 | 0.161498E+11 | 0.00 | 93394244.75 | 0.155526E+10 | 0.00 | 0.827506E+11 | 0.00 | 24.77 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.988900E+10 | 87926577.47 | 0.00 | 13100637.35 | 28850964.08 | 0.00 | 0.169538E+11 | 0.00 | 3.44 |
February | 0.929912E+10 | 18136999.34 | 0.00 | 9874873.19 | 3184134.08 | 0.00 | 0.146467E+11 | 0.00 | 3.45 |
March | 0.157976E+11 | 40473293.31 | 0.00 | 5138959.75 | 19148123.33 | 0.00 | 0.118148E+11 | 0.00 | 3.44 |
April | 0.927592E+10 | 19906019.31 | 0.00 | 5443282.02 | 0.175104E+09 | 0.00 | 0.115327E+11 | 0.00 | 3.44 |
May | 0.100515E+11 | 0.00 | 0.00 | 4440643.00 | 39613729.97 | 0.00 | 0.107616E+11 | 0.00 | 3.44 |
June | 0.556431E+10 | 0.00 | 0.00 | 5126904.54 | 0.121517E+10 | 0.00 | 0.828089E+10 | 0.00 | 3.45 |
July | 0.218185E+10 | 0.179419E+09 | 0.00 | 5443136.41 | 0.500759E+10 | 0.00 | 0.449781E+10 | 0.00 | 3.45 |
August | 0.114150E+10 | 0.373552E+09 | 0.00 | 6632385.38 | 0.611749E+10 | 0.00 | 0.384311E+10 | 0.00 | 3.45 |
September | 0.326800E+10 | 0.990038E+09 | 0.00 | 8347763.84 | 0.142892E+10 | 0.00 | 0.764040E+10 | 0.00 | 3.47 |
October | 0.335846E+10 | 0.220898E+10 | 0.00 | 12177542.45 | 0.122181E+10 | 0.00 | 0.992501E+10 | 0.00 | 3.48 |
November | 0.596941E+10 | 73923218.98 | 0.00 | 15815390.24 | 1422210.59 | 0.00 | 0.178394E+11 | 0.00 | 3.47 |
December | 0.853761E+10 | 57362673.82 | 0.00 | 17166207.41 | 1236864.09 | 0.00 | 0.177400E+11 | 0.00 | 3.46 |
Annual Sum or Average | 0.843342E+11 | 0.404972E+10 | 0.00 | 0.108708E+09 | 0.152595E+11 | 0.00 | 0.135476E+12 | 0.00 | 3.45 |
Minimum of Months | 0.114150E+10 | 0.00 | 0.00 | 4440643.00 | 1236864.09 | 0.00 | 0.384311E+10 | 0.00 | 3.44 |
Maximum of Months | 0.157976E+11 | 0.220898E+10 | 0.00 | 17166207.41 | 0.611749E+10 | 0.00 | 0.178394E+11 | 0.00 | 3.48 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.620829E+11 | 0.00 | 0.00 | 15624834.47 | 0.407763E+09 | 0.00 | 0.369155E+11 | 0.00 | 1.83 |
February | 0.493216E+11 | 0.00 | 0.00 | 17647010.75 | 78783848.69 | 0.00 | 0.392651E+11 | 0.00 | 1.84 |
March | 0.656023E+11 | 0.00 | 0.00 | 13120264.34 | 0.220307E+09 | 0.00 | 0.364398E+11 | 0.00 | 1.84 |
April | 0.396279E+11 | 0.00 | 0.00 | 14167314.12 | 0.720584E+09 | 0.00 | 0.372680E+11 | 0.00 | 1.84 |
May | 0.429168E+11 | 0.00 | 0.00 | 11321252.42 | 0.146377E+09 | 0.00 | 0.339948E+11 | 0.00 | 1.84 |
June | 0.275539E+11 | 0.00 | 0.00 | 10041082.12 | 0.449019E+10 | 0.00 | 0.236144E+11 | 0.00 | 1.84 |
July | 0.136897E+11 | 0.281172E+09 | 0.00 | 8642419.35 | 0.188854E+11 | 0.00 | 0.110038E+11 | 0.00 | 1.84 |
August | 0.655301E+10 | 0.337587E+09 | 0.00 | 10985308.65 | 0.236475E+11 | 0.00 | 0.118792E+11 | 0.00 | 1.84 |
September | 0.181788E+11 | 0.424736E+09 | 0.00 | 16082914.80 | 0.846162E+10 | 0.00 | 0.221401E+11 | 0.00 | 1.85 |
October | 0.190628E+11 | 0.171337E+10 | 0.00 | 23104468.32 | 0.104841E+11 | 0.00 | 0.300298E+11 | 0.00 | 1.84 |
November | 0.382175E+11 | 59048444.54 | 0.00 | 26266338.03 | 0.179025E+09 | 0.00 | 0.497310E+11 | 0.00 | 1.84 |
December | 0.532434E+11 | 0.00 | 0.00 | 21106325.58 | 0.196247E+09 | 0.00 | 0.436942E+11 | 0.00 | 1.83 |
Annual Sum or Average | 0.436051E+12 | 0.281591E+10 | 0.00 | 0.188110E+09 | 0.679179E+11 | 0.00 | 0.375976E+12 | 0.00 | 1.84 |
Minimum of Months | 0.655301E+10 | 0.00 | 0.00 | 8642419.35 | 78783848.69 | 0.00 | 0.110038E+11 | 0.00 | 1.83 |
Maximum of Months | 0.656023E+11 | 0.171337E+10 | 0.00 | 26266338.03 | 0.236475E+11 | 0.00 | 0.497310E+11 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 17002579.73 | 3089287.81 | 2358.20 | 5407135.27 | 929080.96 | 0.755300E+09 | 0.102141E+10 | 2997.76 | 0.35 |
February | 35240238.07 | 1788187.26 | 0.00 | 4904588.02 | 0.00 | 0.540245E+09 | 0.972555E+09 | 0.00 | 0.36 |
March | 47053249.78 | 2012516.94 | 0.00 | 5241018.88 | 618445.26 | 0.762393E+09 | 0.983378E+09 | 0.00 | 0.36 |
April | 28304468.92 | 5547722.72 | 0.00 | 9606216.73 | 1848909.62 | 0.135692E+09 | 0.106566E+10 | 0.00 | 0.36 |
May | 31338509.87 | 1413324.30 | 0.00 | 10144385.70 | 1405930.70 | 0.123643E+09 | 0.107803E+10 | 0.00 | 0.36 |
June | 13121613.76 | 35064739.68 | 0.00 | 10832647.73 | 9898160.24 | 2082376.76 | 0.688889E+09 | 0.00 | 0.36 |
July | 787895.02 | 0.218322E+09 | 40556.48 | 9544319.92 | 13732615.10 | 990879.38 | 0.306304E+09 | 5945.94 | 0.36 |
August | 0.00 | 0.297591E+09 | 95389.93 | 7564808.84 | 9800934.65 | 829727.38 | 0.228690E+09 | 15436.62 | 0.36 |
September | 2537092.97 | 97796858.29 | 13889.92 | 9371758.15 | 4665851.69 | 2410266.64 | 0.532112E+09 | 2052.03 | 0.36 |
October | 5992586.41 | 0.185587E+09 | 102096.50 | 7380168.72 | 3525282.25 | 56136277.55 | 0.763583E+09 | 14199.74 | 0.36 |
November | 16129398.85 | 3161088.80 | 0.00 | 6570326.67 | 313184.61 | 0.386004E+09 | 0.110829E+10 | 0.00 | 0.35 |
December | 17082083.02 | 4721527.41 | 10578.74 | 5959715.55 | 375163.64 | 0.704653E+09 | 0.103505E+10 | 2646.13 | 0.35 |
Annual Sum or Average | 0.214590E+09 | 0.856094E+09 | 264869.76 | 92527090.18 | 47113558.72 | 0.347038E+10 | 0.978395E+10 | 43278.21 | 0.36 |
Minimum of Months | 0.00 | 1413324.30 | 0.00 | 4904588.02 | 0.00 | 829727.38 | 0.228690E+09 | 0.00 | 0.35 |
Maximum of Months | 47053249.78 | 0.297591E+09 | 102096.50 | 10832647.73 | 13732615.10 | 0.762393E+09 | 0.110829E+10 | 15436.62 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 91140594.62 | 1375400.66 | 7541.61 | 2077352.78 | 2636110.02 | 0.111099E+10 | 0.594913E+09 | 4672.44 | 0.35 |
February | 79411111.63 | 635664.87 | 0.00 | 2511240.65 | 1151621.87 | 0.808361E+09 | 0.662662E+09 | 900.53 | 0.36 |
March | 81351748.42 | 664605.17 | 0.00 | 3324794.18 | 1966357.03 | 0.927890E+09 | 0.785499E+09 | 0.00 | 0.36 |
April | 0.118163E+09 | 4068798.02 | 52.85 | 6703700.37 | 3327157.48 | 0.153840E+09 | 0.960560E+09 | 624.00 | 0.36 |
May | 0.157253E+09 | 1375235.26 | 0.00 | 7777215.04 | 1444019.74 | 0.102843E+09 | 0.975283E+09 | 0.00 | 0.36 |
June | 0.231663E+09 | 31116615.52 | 0.00 | 7635955.71 | 13846284.41 | 2029406.33 | 0.473597E+09 | 0.00 | 0.36 |
July | 0.172785E+09 | 0.178433E+09 | 47537.92 | 6193922.70 | 53612105.53 | 716988.70 | 0.137931E+09 | 7981.65 | 0.36 |
August | 0.139994E+09 | 0.234727E+09 | 104573.84 | 4187182.75 | 72655991.39 | 473068.22 | 92430493.16 | 14900.23 | 0.36 |
September | 0.177477E+09 | 75105009.05 | 75848.64 | 5437978.90 | 27293638.35 | 1744264.64 | 0.361772E+09 | 4155.89 | 0.36 |
October | 0.173102E+09 | 0.143068E+09 | 178265.25 | 3627034.00 | 45961823.32 | 87407922.97 | 0.568956E+09 | 20325.87 | 0.36 |
November | 0.109380E+09 | 2499695.66 | 18172.30 | 2915514.36 | 951546.81 | 0.654363E+09 | 0.750332E+09 | 4858.64 | 0.35 |
December | 0.104457E+09 | 3936667.10 | 24158.67 | 2087274.32 | 1142452.34 | 0.107189E+10 | 0.584306E+09 | 6637.80 | 0.35 |
Annual Sum or Average | 0.163618E+10 | 0.677005E+09 | 456151.07 | 54479165.76 | 0.225989E+09 | 0.492255E+10 | 0.694824E+10 | 65057.05 | 0.36 |
Minimum of Months | 79411111.63 | 635664.87 | 0.00 | 2077352.78 | 951546.81 | 473068.22 | 92430493.16 | 0.00 | 0.35 |
Maximum of Months | 0.231663E+09 | 0.234727E+09 | 178265.25 | 7777215.04 | 72655991.39 | 0.111099E+10 | 0.975283E+09 | 20325.87 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 94121369.92 | 3144248.17 | 0.00 | 3762588.71 | 0.00 | 0.00 | 0.913184E+09 | 0.00 | 0.02 |
February | 0.411880E+09 | 0.00 | 0.00 | 2124789.63 | 0.00 | 0.00 | 0.648078E+09 | 0.00 | 0.02 |
March | 0.613546E+09 | 4975565.11 | 0.00 | 1338573.02 | 0.00 | 0.00 | 0.520679E+09 | 0.00 | 0.02 |
April | 0.375125E+09 | 1234527.67 | 0.00 | 927632.08 | 0.00 | 0.00 | 0.432452E+09 | 0.00 | 0.02 |
May | 0.729463E+09 | 0.00 | 0.00 | 151156.37 | 0.00 | 0.00 | 0.130613E+09 | 0.00 | 0.02 |
June | 0.451039E+09 | 801471.85 | 0.00 | 128234.16 | 5103559.21 | 0.00 | 86244787.51 | 0.00 | 0.02 |
July | 0.126831E+09 | 0.236480E+09 | 0.00 | 76387.86 | 22306469.38 | 0.00 | 32574791.29 | 0.00 | 0.02 |
August | 4430421.42 | 0.382953E+09 | 0.00 | 109456.84 | 1211768.97 | 0.00 | 28887720.95 | 0.00 | 0.02 |
September | 0.00 | 0.139389E+09 | 0.00 | 1297629.42 | 0.00 | 0.00 | 0.187628E+09 | 0.00 | 0.02 |
October | 54995953.24 | 0.202614E+09 | 0.00 | 2100118.34 | 4646486.61 | 0.00 | 0.279310E+09 | 0.00 | 0.02 |
November | 52789781.29 | 248987.17 | 0.00 | 3361282.41 | 0.00 | 0.00 | 0.874812E+09 | 0.00 | 0.02 |
December | 0.126685E+09 | 113872.17 | 0.00 | 3991274.15 | 0.00 | 0.00 | 0.899313E+09 | 0.00 | 0.02 |
Annual Sum or Average | 0.304091E+10 | 0.971955E+09 | 0.00 | 19369123.01 | 33268284.17 | 0.00 | 0.503378E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 76387.86 | 0.00 | 0.00 | 28887720.95 | 0.00 | 0.02 |
Maximum of Months | 0.729463E+09 | 0.382953E+09 | 0.00 | 3991274.15 | 22306469.38 | 0.00 | 0.913184E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122846E+10 | 18604560.75 | 162391.27 | 58179382.09 | 35739303.64 | 0.153759E+09 | 0.229513E+11 | 45761.80 | 0.40 |
February | 0.107662E+10 | 8474523.36 | 136200.79 | 59984956.87 | 15613219.23 | 0.106968E+09 | 0.198106E+11 | 19569.65 | 0.40 |
March | 0.110293E+10 | 8726397.58 | 282324.93 | 69964413.66 | 26659066.05 | 0.136365E+09 | 0.230682E+11 | 1723.09 | 0.40 |
April | 0.160200E+10 | 51683609.38 | 235129.51 | 89429155.00 | 48347392.25 | 43619795.96 | 0.150664E+11 | 14391.08 | 0.40 |
May | 0.213580E+10 | 15141678.51 | 0.00 | 0.104270E+09 | 23080630.08 | 34469389.10 | 0.145797E+11 | 0.00 | 0.40 |
June | 0.314908E+10 | 0.367256E+09 | 8288.83 | 0.106448E+09 | 0.242311E+09 | 14466956.56 | 0.642267E+10 | 12738.49 | 0.40 |
July | 0.234515E+10 | 0.204168E+10 | 241292.46 | 88968605.90 | 0.110479E+10 | 1285186.76 | 0.187086E+10 | 18122.40 | 0.41 |
August | 0.189798E+10 | 0.278194E+10 | 570216.12 | 61702399.33 | 0.138645E+10 | 1012828.20 | 0.125360E+10 | 38641.61 | 0.41 |
September | 0.240616E+10 | 0.950373E+09 | 712212.92 | 75263357.08 | 0.438240E+09 | 10343838.40 | 0.491653E+10 | 38793.23 | 0.41 |
October | 0.234684E+10 | 0.179101E+10 | 4086856.14 | 65173178.36 | 0.770301E+09 | 16607596.41 | 0.886611E+10 | 77141.21 | 0.40 |
November | 0.148293E+10 | 25777763.32 | 350405.71 | 64698973.19 | 20957447.18 | 82472684.13 | 0.189366E+11 | 17164.59 | 0.40 |
December | 0.141618E+10 | 53500324.08 | 240659.89 | 57165850.90 | 15488902.48 | 0.118973E+09 | 0.223063E+11 | 48267.72 | 0.40 |
Annual Sum or Average | 0.221901E+11 | 0.811417E+10 | 7025978.57 | 0.901249E+09 | 0.412797E+10 | 0.720345E+09 | 0.160049E+12 | 332314.86 | 0.40 |
Minimum of Months | 0.107662E+10 | 8474523.36 | 0.00 | 57165850.90 | 15488902.48 | 1012828.20 | 0.125360E+10 | 0.00 | 0.40 |
Maximum of Months | 0.314908E+10 | 0.278194E+10 | 4086856.14 | 0.106448E+09 | 0.138645E+10 | 0.153759E+09 | 0.230682E+11 | 77141.21 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 18965929.24 | 3089287.81 | 1076.71 | 6566622.42 | 929080.96 | 0.731920E+09 | 0.104166E+10 | 4279.24 | 0.35 |
February | 35222344.45 | 1787286.74 | 0.00 | 5030783.79 | 0.00 | 0.597925E+09 | 0.914767E+09 | 900.53 | 0.36 |
March | 45455743.47 | 2630962.20 | 0.00 | 5531317.98 | 0.00 | 0.777797E+09 | 0.969281E+09 | 0.00 | 0.36 |
April | 21579759.67 | 7373610.39 | 22919.54 | 8913993.50 | 0.00 | 0.189651E+09 | 0.101912E+10 | 102.42 | 0.36 |
May | 29502582.28 | 1713224.94 | 0.00 | 9114286.82 | 1106030.06 | 0.193457E+09 | 0.101108E+10 | 0.00 | 0.36 |
June | 12156448.77 | 42930818.08 | 0.00 | 9888403.54 | 2032081.85 | 10424711.43 | 0.682456E+09 | 0.00 | 0.36 |
July | 501477.96 | 0.229099E+09 | 0.00 | 9201409.43 | 3001780.28 | 562261.60 | 0.307362E+09 | 0.00 | 0.36 |
August | 0.00 | 0.307196E+09 | 0.00 | 7653625.39 | 306193.29 | 590449.37 | 0.228841E+09 | 0.00 | 0.36 |
September | 2745500.41 | 97490446.76 | 35755.00 | 8270963.12 | 4949704.04 | 6588136.09 | 0.528827E+09 | 2746.13 | 0.36 |
October | 6078470.76 | 0.185177E+09 | 74619.84 | 7832930.80 | 3973161.11 | 79886721.32 | 0.739294E+09 | 3845.13 | 0.36 |
November | 17157094.20 | 3161088.80 | 0.00 | 6885125.35 | 313184.61 | 0.433886E+09 | 0.105906E+10 | 0.00 | 0.35 |
December | 21289245.24 | 4792136.89 | 8291.19 | 6694444.31 | 304554.16 | 0.730483E+09 | 0.100428E+10 | 4933.67 | 0.35 |
Annual Sum or Average | 0.210655E+09 | 0.886441E+09 | 142662.28 | 91583906.44 | 16915770.37 | 0.375317E+10 | 0.950604E+10 | 16807.11 | 0.36 |
Minimum of Months | 0.00 | 1713224.94 | 0.00 | 5030783.79 | 0.00 | 562261.60 | 0.228841E+09 | 0.00 | 0.35 |
Maximum of Months | 45455743.47 | 0.307196E+09 | 74619.84 | 9888403.54 | 4949704.04 | 0.777797E+09 | 0.105906E+10 | 4933.67 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 91098554.04 | 1377936.86 | 3069.03 | 2524581.67 | 2636110.02 | 0.107213E+10 | 0.633365E+09 | 6608.82 | 0.35 |
February | 79899389.97 | 625075.86 | 7955.63 | 2458191.78 | 1151621.87 | 0.885672E+09 | 0.584916E+09 | 3533.91 | 0.36 |
March | 81675143.61 | 664605.17 | 0.00 | 3573805.44 | 1966357.03 | 0.958395E+09 | 0.754422E+09 | 0.00 | 0.36 |
April | 0.118278E+09 | 4999343.44 | 22628.87 | 6577083.39 | 2374266.95 | 0.232344E+09 | 0.882068E+09 | 393.09 | 0.36 |
May | 0.155640E+09 | 1670845.75 | 0.00 | 7449271.93 | 1148409.25 | 0.185390E+09 | 0.894677E+09 | 0.00 | 0.36 |
June | 0.231004E+09 | 36919641.59 | 0.00 | 7098232.03 | 8043258.33 | 9274903.23 | 0.467548E+09 | 0.00 | 0.36 |
July | 0.172563E+09 | 0.184125E+09 | 0.00 | 5841838.40 | 47975402.44 | 450690.92 | 0.138771E+09 | 0.00 | 0.36 |
August | 0.139994E+09 | 0.250782E+09 | 0.00 | 3926030.51 | 56720187.96 | 338084.94 | 92826628.68 | 0.00 | 0.36 |
September | 0.177233E+09 | 79300380.59 | 111391.98 | 4811601.96 | 23063021.22 | 13633668.30 | 0.350753E+09 | 3858.14 | 0.36 |
October | 0.173102E+09 | 0.146242E+09 | 326991.24 | 4235811.60 | 42641181.77 | 0.131914E+09 | 0.523841E+09 | 18508.75 | 0.36 |
November | 0.109380E+09 | 1982145.13 | 14819.14 | 2907209.96 | 1469817.88 | 0.684939E+09 | 0.719764E+09 | 7491.27 | 0.35 |
December | 0.104457E+09 | 3931352.23 | 29203.08 | 2239578.85 | 1142452.34 | 0.104204E+10 | 0.614007E+09 | 6908.26 | 0.35 |
Annual Sum or Average | 0.163432E+10 | 0.712620E+09 | 516058.97 | 53643237.52 | 0.190332E+09 | 0.521652E+10 | 0.665696E+10 | 47302.23 | 0.36 |
Minimum of Months | 79899389.97 | 625075.86 | 0.00 | 2239578.85 | 1142452.34 | 338084.94 | 92826628.68 | 0.00 | 0.35 |
Maximum of Months | 0.231004E+09 | 0.250782E+09 | 326991.24 | 7449271.93 | 56720187.96 | 0.107213E+10 | 0.894677E+09 | 18508.75 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209784E+11 | 0.00 | 0.00 | 0.00 | 0.106990E+09 | 0.498613E+10 | 0.00 | 0.00 | 0.52 |
February | 0.206624E+11 | 0.00 | 0.00 | 0.00 | 20671538.56 | 0.254508E+10 | 0.00 | 0.00 | 0.52 |
March | 0.212823E+11 | 0.00 | 0.00 | 0.00 | 57804920.04 | 0.549381E+10 | 0.00 | 0.00 | 0.52 |
April | 0.196993E+11 | 0.00 | 0.00 | 0.00 | 0.189069E+09 | 0.480596E+09 | 0.00 | 0.00 | 0.52 |
May | 0.197591E+11 | 0.00 | 0.00 | 0.00 | 38406811.21 | 0.424218E+09 | 0.00 | 0.00 | 0.52 |
June | 0.134283E+11 | 0.00 | 0.00 | 0.00 | 0.117815E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.648142E+10 | 0.00 | 0.00 | 0.00 | 0.502897E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.483917E+10 | 0.00 | 0.00 | 0.00 | 0.629328E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.105832E+11 | 0.00 | 0.00 | 0.00 | 0.233163E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
October | 0.128605E+11 | 0.00 | 0.00 | 0.00 | 0.320041E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
November | 0.220533E+11 | 0.00 | 0.00 | 0.00 | 62466472.29 | 0.965708E+09 | 0.00 | 0.00 | 0.52 |
December | 0.223837E+11 | 0.00 | 0.00 | 0.00 | 51491853.44 | 0.300352E+10 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.195011E+12 | 0.00 | 0.00 | 0.00 | 0.185593E+11 | 0.178991E+11 | 0.00 | 0.00 | 0.52 |
Minimum of Months | 0.483917E+10 | 0.00 | 0.00 | 0.00 | 20671538.56 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.223837E+11 | 0.00 | 0.00 | 0.00 | 0.629328E+10 | 0.549381E+10 | 0.00 | 0.00 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4033054.29 | 817017.30 | 0.00 | 1255454.30 | 188279.83 | 0.245462E+09 | 0.199029E+09 | 634.05 | 0.35 |
February | 7989815.13 | 447046.82 | 0.00 | 1170221.24 | 0.00 | 0.204090E+09 | 0.174986E+09 | 0.00 | 0.36 |
March | 11060361.86 | 657740.55 | 0.00 | 1311752.62 | 0.00 | 0.244208E+09 | 0.192937E+09 | 0.00 | 0.36 |
April | 5073239.30 | 1849158.09 | 0.00 | 2566635.04 | 0.00 | 63948953.29 | 0.238228E+09 | 0.00 | 0.36 |
May | 7178659.47 | 656208.41 | 0.00 | 2739093.66 | 48605.34 | 58576028.12 | 0.242295E+09 | 0.00 | 0.36 |
June | 2405948.60 | 11109542.20 | 0.00 | 2956562.84 | 131182.78 | 6152103.14 | 0.167217E+09 | 0.00 | 0.36 |
July | 0.00 | 58016040.17 | 8513.78 | 2637807.15 | 0.00 | 204749.72 | 76564165.80 | 626.04 | 0.36 |
August | 0.00 | 76850188.66 | 22813.78 | 2054298.33 | 0.00 | 182459.09 | 57034416.88 | 2576.08 | 0.36 |
September | 385734.99 | 24697221.43 | 3425.01 | 2492310.92 | 918456.06 | 1966057.77 | 0.131764E+09 | 560.48 | 0.36 |
October | 1344586.70 | 46882422.63 | 17468.80 | 1865981.93 | 403912.85 | 33708026.41 | 0.171355E+09 | 3255.63 | 0.36 |
November | 3327689.40 | 790272.20 | 0.00 | 1564602.95 | 78296.15 | 0.149930E+09 | 0.224425E+09 | 0.00 | 0.35 |
December | 4329799.08 | 1274172.76 | 2831.94 | 1390266.93 | 0.00 | 0.231976E+09 | 0.202990E+09 | 474.28 | 0.35 |
Annual Sum or Average | 47128888.82 | 0.224047E+09 | 55053.32 | 24004987.93 | 1768733.01 | 0.124040E+10 | 0.207882E+10 | 8126.55 | 0.36 |
Minimum of Months | 0.00 | 447046.82 | 0.00 | 1170221.24 | 0.00 | 182459.09 | 57034416.88 | 0.00 | 0.35 |
Maximum of Months | 11060361.86 | 76850188.66 | 22813.78 | 2956562.84 | 918456.06 | 0.245462E+09 | 0.242295E+09 | 3255.63 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22973055.58 | 352236.54 | 56.37 | 456270.94 | 652355.65 | 0.343970E+09 | 82379597.81 | 1282.62 | 0.35 |
February | 19891274.66 | 158916.22 | 0.00 | 577691.58 | 287905.47 | 0.257593E+09 | 0.110174E+09 | 225.13 | 0.36 |
March | 20619917.44 | 166151.29 | 0.00 | 834848.02 | 491589.26 | 0.284294E+09 | 0.143768E+09 | 0.00 | 0.36 |
April | 29410320.52 | 1307992.27 | 701.39 | 1842140.40 | 540462.43 | 66278971.64 | 0.212285E+09 | 1.99 | 0.36 |
May | 38457146.92 | 651811.31 | 0.00 | 2182029.71 | 53002.45 | 47225237.40 | 0.222925E+09 | 0.00 | 0.36 |
June | 56986576.91 | 9537451.73 | 0.00 | 2282336.77 | 1703273.25 | 4291085.26 | 0.115171E+09 | 0.00 | 0.36 |
July | 43026108.11 | 46585869.97 | 15913.62 | 1901417.66 | 11422372.59 | 85315.24 | 34393881.66 | 1023.81 | 0.36 |
August | 34998488.27 | 63397481.08 | 20052.73 | 1260937.47 | 13456263.68 | 60689.52 | 22951059.04 | 1781.03 | 0.36 |
September | 44098947.80 | 21420657.59 | 18919.98 | 1520370.44 | 4179004.26 | 2316976.52 | 88671501.85 | 1081.15 | 0.36 |
October | 43275377.18 | 38765325.20 | 48483.06 | 937968.86 | 8488308.56 | 44850806.04 | 0.119209E+09 | 4943.09 | 0.36 |
November | 27415537.80 | 664851.38 | 5263.97 | 657630.68 | 197959.24 | 0.212401E+09 | 0.138773E+09 | 493.76 | 0.35 |
December | 26091151.04 | 1002657.95 | 4438.74 | 454802.10 | 268327.00 | 0.320123E+09 | 94017505.01 | 2055.28 | 0.35 |
Annual Sum or Average | 0.407244E+09 | 0.184011E+09 | 113829.87 | 14908444.63 | 41740823.84 | 0.158349E+10 | 0.138472E+10 | 12887.88 | 0.36 |
Minimum of Months | 19891274.66 | 158916.22 | 0.00 | 454802.10 | 53002.45 | 60689.52 | 22951059.04 | 0.00 | 0.35 |
Maximum of Months | 56986576.91 | 63397481.08 | 48483.06 | 2282336.77 | 13456263.68 | 0.343970E+09 | 0.222925E+09 | 4943.09 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7724665.01 | 6414962.55 | 3231.20 | 18343209.89 | 41072.90 | 0.372073E+09 | 0.249035E+10 | 840.68 | 0.40 |
February | 42195969.84 | 2870942.33 | 0.00 | 13084987.72 | 0.00 | 0.246688E+09 | 0.219129E+10 | 0.00 | 0.40 |
March | 52074730.23 | 4224021.12 | 0.00 | 11225993.52 | 0.00 | 0.668863E+09 | 0.215464E+10 | 0.00 | 0.40 |
April | 17961782.59 | 11875325.00 | 0.00 | 13405880.01 | 0.00 | 0.101295E+09 | 0.185698E+10 | 0.00 | 0.40 |
May | 46910707.48 | 2750590.00 | 0.00 | 11522487.08 | 1775736.02 | 0.191034E+09 | 0.174643E+10 | 0.00 | 0.40 |
June | 19620837.50 | 67280189.28 | 11141.44 | 12395236.95 | 4896714.43 | 3928371.02 | 0.111187E+10 | 83.79 | 0.40 |
July | 1093418.60 | 0.365823E+09 | 60378.96 | 11515938.46 | 6752773.09 | 2188415.52 | 0.495154E+09 | 2363.55 | 0.40 |
August | 0.00 | 0.493636E+09 | 58529.02 | 10354812.90 | 0.00 | 1752269.25 | 0.368533E+09 | 2090.60 | 0.40 |
September | 2477196.71 | 0.157897E+09 | 0.00 | 14183804.25 | 6632799.49 | 3038986.85 | 0.857598E+09 | 0.00 | 0.41 |
October | 5410794.64 | 0.301146E+09 | 63589.07 | 14934837.41 | 2593935.25 | 6051710.89 | 0.131114E+10 | 3368.73 | 0.40 |
November | 4480737.68 | 5330370.12 | 0.00 | 18378086.84 | 247590.76 | 24621588.58 | 0.238805E+10 | 0.00 | 0.40 |
December | 9013988.74 | 8203991.94 | 0.00 | 19458257.77 | 0.00 | 0.187977E+09 | 0.261364E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.208965E+09 | 0.142745E+10 | 196869.70 | 0.168804E+09 | 22940621.95 | 0.180951E+10 | 0.195857E+11 | 8747.34 | 0.40 |
Minimum of Months | 0.00 | 2750590.00 | 0.00 | 10354812.90 | 0.00 | 1752269.25 | 0.368533E+09 | 0.00 | 0.40 |
Maximum of Months | 52074730.23 | 0.493636E+09 | 63589.07 | 19458257.77 | 6752773.09 | 0.668863E+09 | 0.261364E+10 | 3368.73 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.403933E+10 | 95966605.74 | 0.00 | 45417480.54 | 85002249.21 | 0.00 | 0.426335E+11 | 0.00 | 4.38 |
February | 0.183385E+10 | 27601949.94 | 0.00 | 45325738.77 | 7362996.52 | 0.00 | 0.411702E+11 | 0.00 | 4.51 |
March | 0.226865E+10 | 70291363.86 | 0.00 | 50465615.11 | 27482971.07 | 0.00 | 0.470441E+11 | 0.00 | 4.51 |
April | 0.111573E+10 | 0.253714E+09 | 0.00 | 55220406.99 | 66087314.67 | 0.00 | 0.370680E+11 | 0.00 | 4.56 |
May | 0.114565E+10 | 53912145.75 | 0.00 | 59605448.06 | 11051189.91 | 0.00 | 0.371600E+11 | 0.00 | 4.57 |
June | 0.533218E+09 | 0.159252E+10 | 0.00 | 58929559.48 | 0.401048E+09 | 0.00 | 0.247465E+11 | 0.00 | 4.52 |
July | 0.120299E+09 | 0.714268E+10 | 0.00 | 51194346.58 | 0.139544E+10 | 0.00 | 0.119569E+11 | 0.00 | 4.47 |
August | 87803160.21 | 0.868543E+10 | 0.00 | 45168449.89 | 0.198625E+10 | 0.00 | 0.900480E+10 | 0.00 | 4.46 |
September | 0.486459E+09 | 0.323150E+10 | 0.00 | 51353532.90 | 0.738362E+09 | 0.00 | 0.189720E+11 | 0.00 | 4.45 |
October | 0.609292E+09 | 0.478273E+10 | 0.00 | 44420783.73 | 0.686499E+09 | 0.00 | 0.232887E+11 | 0.00 | 4.44 |
November | 0.174436E+10 | 88015571.94 | 0.00 | 47854718.53 | 17643561.91 | 0.00 | 0.411127E+11 | 0.00 | 4.49 |
December | 0.248678E+10 | 59458973.57 | 0.00 | 46197283.69 | 27637102.71 | 0.00 | 0.435769E+11 | 0.00 | 4.40 |
Annual Sum or Average | 0.164714E+11 | 0.260838E+11 | 0.00 | 0.601153E+09 | 0.544987E+10 | 0.00 | 0.377734E+12 | 0.00 | 4.48 |
Minimum of Months | 87803160.21 | 27601949.94 | 0.00 | 44420783.73 | 7362996.52 | 0.00 | 0.900480E+10 | 0.00 | 4.38 |
Maximum of Months | 0.403933E+10 | 0.868543E+10 | 0.00 | 59605448.06 | 0.198625E+10 | 0.00 | 0.470441E+11 | 0.00 | 4.57 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191355E+10 | 0.164741E+09 | 0.00 | 59747325.77 | 25224946.88 | 0.00 | 0.487528E+11 | 0.00 | 4.73 |
February | 0.869764E+09 | 28974268.80 | 0.00 | 59264450.64 | 7729071.35 | 0.00 | 0.461065E+11 | 0.00 | 4.90 |
March | 0.875095E+09 | 78262895.55 | 0.00 | 65830698.15 | 24372601.87 | 0.00 | 0.528959E+11 | 0.00 | 4.89 |
April | 0.480136E+09 | 0.313099E+09 | 0.00 | 71709909.89 | 22602747.05 | 0.00 | 0.413675E+11 | 0.00 | 4.95 |
May | 0.488860E+09 | 65625435.27 | 0.00 | 77298788.94 | 2567759.54 | 0.00 | 0.414949E+11 | 0.00 | 4.96 |
June | 0.243564E+09 | 0.195891E+10 | 0.00 | 73434777.05 | 0.134922E+09 | 0.00 | 0.274196E+11 | 0.00 | 4.89 |
July | 72224840.46 | 0.846040E+10 | 0.00 | 60750783.63 | 0.541818E+09 | 0.00 | 0.131242E+11 | 0.00 | 4.81 |
August | 65464642.68 | 0.104334E+11 | 0.00 | 52059115.47 | 0.797017E+09 | 0.00 | 0.987378E+10 | 0.00 | 4.81 |
September | 0.249197E+09 | 0.376866E+10 | 0.00 | 63254753.78 | 0.416382E+09 | 0.00 | 0.210010E+11 | 0.00 | 4.80 |
October | 0.364002E+09 | 0.533046E+10 | 0.00 | 55188593.04 | 0.451926E+09 | 0.00 | 0.257093E+11 | 0.00 | 4.78 |
November | 0.941881E+09 | 0.104602E+09 | 0.00 | 62366018.48 | 6310522.26 | 0.00 | 0.458753E+11 | 0.00 | 4.87 |
December | 0.103072E+10 | 76357092.91 | 0.00 | 60825287.41 | 15069242.22 | 0.00 | 0.491003E+11 | 0.00 | 4.76 |
Annual Sum or Average | 0.759446E+10 | 0.307835E+11 | 0.00 | 0.761731E+09 | 0.244594E+10 | 0.00 | 0.422721E+12 | 0.00 | 4.84 |
Minimum of Months | 65464642.68 | 28974268.80 | 0.00 | 52059115.47 | 2567759.54 | 0.00 | 0.987378E+10 | 0.00 | 4.73 |
Maximum of Months | 0.191355E+10 | 0.104334E+11 | 0.00 | 77298788.94 | 0.797017E+09 | 0.00 | 0.528959E+11 | 0.00 | 4.96 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.274399E+09 | 0.00 | 0.120801E+09 | 0.00 | 0.00 | 0.641977E+11 | 0.00 | 20.27 |
February | 4434658.19 | 54883309.82 | 0.00 | 0.110779E+09 | 0.00 | 0.00 | 0.589778E+11 | 0.00 | 20.81 |
March | 18302452.35 | 0.149830E+09 | 0.00 | 0.118820E+09 | 0.00 | 0.00 | 0.676464E+11 | 0.00 | 20.84 |
April | 0.00 | 0.500162E+09 | 0.00 | 0.125995E+09 | 0.00 | 0.00 | 0.501943E+11 | 0.00 | 20.60 |
May | 0.00 | 99240190.34 | 0.00 | 0.136321E+09 | 0.00 | 0.00 | 0.497276E+11 | 0.00 | 20.44 |
June | 0.00 | 0.312042E+10 | 0.00 | 0.113684E+09 | 0.00 | 0.00 | 0.318836E+11 | 0.00 | 20.02 |
July | 0.00 | 0.135406E+11 | 0.00 | 74320977.22 | 0.00 | 0.00 | 0.145698E+11 | 0.00 | 19.76 |
August | 0.00 | 0.168393E+11 | 0.00 | 59738621.75 | 0.00 | 0.00 | 0.109074E+11 | 0.00 | 19.76 |
September | 0.00 | 0.609701E+10 | 0.00 | 95257236.74 | 0.00 | 0.00 | 0.248861E+11 | 0.00 | 19.91 |
October | 0.00 | 0.827385E+10 | 0.00 | 89812990.00 | 0.00 | 0.00 | 0.302446E+11 | 0.00 | 19.73 |
November | 4423141.11 | 0.164484E+09 | 0.00 | 0.120387E+09 | 0.00 | 0.00 | 0.576760E+11 | 0.00 | 20.52 |
December | 8582233.02 | 0.133727E+09 | 0.00 | 0.121700E+09 | 0.00 | 0.00 | 0.632929E+11 | 0.00 | 20.34 |
Annual Sum or Average | 35742484.67 | 0.492479E+11 | 0.00 | 0.128762E+10 | 0.00 | 0.00 | 0.524204E+12 | 0.00 | 20.25 |
Minimum of Months | 0.00 | 54883309.82 | 0.00 | 59738621.75 | 0.00 | 0.00 | 0.109074E+11 | 0.00 | 19.73 |
Maximum of Months | 18302452.35 | 0.168393E+11 | 0.00 | 0.136321E+09 | 0.00 | 0.00 | 0.676464E+11 | 0.00 | 20.84 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:43:11
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114075E+11 | 0.00 | 0.00 | 0.00 | 50408131.19 | 0.825642E+09 | 0.00 | 0.00 | 0.92 |
February | 0.109341E+11 | 0.00 | 0.00 | 0.00 | 9739342.21 | 0.00 | 0.00 | 0.00 | 0.93 |
March | 0.118582E+11 | 0.00 | 0.00 | 0.00 | 27234639.37 | 0.757250E+09 | 0.00 | 0.00 | 0.93 |
April | 0.950352E+10 | 0.00 | 0.00 | 0.00 | 89079403.98 | 4186265.28 | 0.00 | 0.00 | 0.93 |
May | 0.950930E+10 | 0.00 | 0.00 | 0.00 | 18095270.30 | 0.00 | 0.00 | 0.00 | 0.93 |
June | 0.632673E+10 | 0.00 | 0.00 | 0.00 | 0.555082E+09 | 0.00 | 0.00 | 0.00 | 0.93 |
July | 0.305371E+10 | 0.00 | 0.00 | 0.00 | 0.236939E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
August | 0.227996E+10 | 0.00 | 0.00 | 0.00 | 0.296506E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
September | 0.498626E+10 | 0.00 | 0.00 | 0.00 | 0.109854E+10 | 0.00 | 0.00 | 0.00 | 0.94 |
October | 0.605919E+10 | 0.00 | 0.00 | 0.00 | 0.150787E+10 | 0.00 | 0.00 | 0.00 | 0.93 |
November | 0.108453E+11 | 0.00 | 0.00 | 0.00 | 29430917.72 | 0.00 | 0.00 | 0.00 | 0.93 |
December | 0.117551E+11 | 0.00 | 0.00 | 0.00 | 24260254.29 | 0.206035E+09 | 0.00 | 0.00 | 0.92 |
Annual Sum or Average | 0.985190E+11 | 0.00 | 0.00 | 0.00 | 0.874419E+10 | 0.179311E+10 | 0.00 | 0.00 | 0.93 |
Minimum of Months | 0.227996E+10 | 0.00 | 0.00 | 0.00 | 9739342.21 | 0.00 | 0.00 | 0.00 | 0.92 |
Maximum of Months | 0.118582E+11 | 0.00 | 0.00 | 0.00 | 0.296506E+10 | 0.825642E+09 | 0.00 | 0.00 | 0.94 |