Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:46
Tabular Output Report in Format: HTML
Building: HotelLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2020-06-03 19:46:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 11450.21 | 1009.25 | 1009.25 |
Net Site Energy | 11450.21 | 1009.25 | 1009.25 |
Total Source Energy | 23567.15 | 2077.26 | 2077.26 |
Net Source Energy | 23567.15 | 2077.26 | 2077.26 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 11345.29 |
Net Conditioned Building Area | 11345.29 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2026.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 801.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 826.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 182.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1658.19 | 1788.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 972.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 512.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 207.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 90.76 | 2279.80 | 0.00 | 0.00 | 0.00 | 22864.31 |
Refrigeration | 61.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 5355.32 | 6094.90 | 0.00 | 0.00 | 0.00 | 22864.31 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 2026.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 801.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 826.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 182.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 872.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 762.04 | 1198.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 14.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 8.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 590.21 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 21.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 512.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 41.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 207.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 90.76 | 2279.80 | 0.00 | 0.00 | 0.00 | 18749.60 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4114.71 | |
Refrigeration | General | 7.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 33.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 127.53 | 379.54 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 255.57 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 472.03 | 537.22 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 88.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 127.53 | 379.54 | 0.00 | 0.00 | 0.00 | 2.02 |
Other | 255.57 | 157.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 472.03 | 537.22 | 0.00 | 0.00 | 0.00 | 2.02 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 5355.315 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 5355.315 | 100.00 |
Total On-Site and Utility Electric Sources | 5355.315 | 100.00 |
Total Electricity End Uses | 5355.315 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 298.52 | 5.99 |
Air to Air Heat Recovery for Heating | 4683.72 | 94.01 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4982.24 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22864.31 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22864.31 | 100.00 |
Total Water End Uses | 22864.31 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 271.00 |
Time Setpoint Not Met During Occupied Cooling | 316.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 8029.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneHeatingSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ZoneElectricSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |SpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |PeakSpaceGainsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | MECH_FLR_1 | STORAGE_FLR_1 | CORRIDOR_FLR_3 | CORRIDOR_FLR_6 |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |ComfortReportSimple55Monthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |OccupantComfortDataSummaryMonthly
| BASEMENT PEOPLE | RETAIL_1_FLR_1 PEOPLE | RETAIL_2_FLR_1 PEOPLE | LAUNDRY_FLR_1 PEOPLE | CAFE_FLR_1 PEOPLE | LOBBY_FLR_1 PEOPLE | ROOM_1_FLR_3 PEOPLE | ROOM_2_FLR_3 PEOPLE | ROOM_3_MULT19_FLR_3 PEOPLE | ROOM_4_MULT19_FLR_3 PEOPLE | ROOM_5_FLR_3 PEOPLE | ROOM_6_FLR_3 PEOPLE | ROOM_1_FLR_6 PEOPLE | ROOM_2_FLR_6 PEOPLE | ROOM_3_MULT9_FLR_6 PEOPLE | BANQUET_FLR_6 PEOPLE | DINING_FLR_6 PEOPLE | KITCHEN_FLR_6 PEOPLE |ChillerReportMonthly
| COOLSYS1 CHILLER |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |WindowReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowEnergyReportMonthly
| RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | CAFE_FLR_1_WALL_SOUTH_WINDOW | LOBBY_FLR_1_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | ROOM_1_FLR_3_WALL_WEST_WINDOW | ROOM_2_FLR_3_WALL_NORTH_WINDOW | ROOM_2_FLR_3_WALL_WEST_WINDOW | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | ROOM_5_FLR_3_WALL_EAST_WINDOW | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | ROOM_6_FLR_3_WALL_NORTH_WINDOW | ROOM_6_FLR_3_WALL_EAST_WINDOW | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | ROOM_1_FLR_6_WALL_WEST_WINDOW | ROOM_2_FLR_6_WALL_NORTH_WINDOW | ROOM_2_FLR_6_WALL_WEST_WINDOW | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | BANQUET_FLR_6_WALL_NORTH_WINDOW | DINING_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_NORTH_WINDOW | KITCHEN_FLR_6_WALL_EAST_WINDOW | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER | SHW BOOSTER WATER HEATER | SWH LAUNDRY |DaylightingReportMonthly
| LOBBY_FLR_1_DAYLCTRL | CAFE_FLR_1_DAYLCTRL | DINING_FLR_6_DAYLCTRL | BANQUET_FLR_6_DAYLCTRL |CoilReportMonthly
| BASEMENT VAV BOX REHEAT COIL | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | MECH_FLR_1 VAV BOX REHEAT COIL | STORAGE_FLR_1 VAV BOX REHEAT COIL | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | CAFE_FLR_1 VAV BOX REHEAT COIL | LOBBY_FLR_1 VAV BOX REHEAT COIL | ROOM_1_FLR_3 FAN COILHEAT COIL | ROOM_2_FLR_3 FAN COILHEAT COIL | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | ROOM_5_FLR_3 FAN COILHEAT COIL | ROOM_6_FLR_3 FAN COILHEAT COIL | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | ROOM_1_FLR_6 FAN COILHEAT COIL | ROOM_2_FLR_6 FAN COILHEAT COIL | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | BANQUET_FLR_6 VAV BOX REHEAT COIL | DINING_FLR_6 VAV BOX REHEAT COIL | KITCHEN_FLR_6 VAV BOX REHEAT COIL | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | VAV WITH REHEAT_HEATC | FLR_3_DOAS_HEATC | ROOM_1_FLR_3 FAN COILCOOL COIL | ROOM_2_FLR_3 FAN COILCOOL COIL | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | ROOM_5_FLR_3 FAN COILCOOL COIL | ROOM_6_FLR_3 FAN COILCOOL COIL | ROOM_1_FLR_6 FAN COILCOOL COIL | ROOM_2_FLR_6 FAN COILCOOL COIL | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | VAV WITH REHEAT_COOLC | FLR_3_DOAS_COOLC |PlantLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |FanReportMonthly
| FLR_3_DOAS_FAN | VAV WITH REHEAT_FAN | LAUNDRY_FLR_1 EXHAUST FAN | LOBBY_FLR_1 DUMMY EXHAUST FAN | DINING_FLR_6 DUMMY EXHAUST FAN | BANQUET_FLR_6 DUMMY EXHAUST FAN | KITCHEN_FLR_6 EXHAUST FAN | ROOM_1_FLR_3 FAN COILFAN | ROOM_2_FLR_3 FAN COILFAN | ROOM_3_MULT19_FLR_3 FAN COILFAN | ROOM_4_MULT19_FLR_3 FAN COILFAN | ROOM_5_FLR_3 FAN COILFAN | ROOM_6_FLR_3 FAN COILFAN | ROOM_1_FLR_6 FAN COILFAN | ROOM_2_FLR_6 FAN COILFAN | ROOM_3_MULT9_FLR_6 FAN COILFAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SWHSYS1 PUMP | COOLSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 | HEATSYS1 | COOLSYS1 |ZoneTemperatureOscillationReportMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentLoadsMonthly
| VAV WITH REHEAT | FLR_3_DOAS |AirLoopSystemComponentEnergyUseMonthly
| VAV WITH REHEAT | FLR_3_DOAS |MechanicalVentilationLoadsMonthly
| BASEMENT | RETAIL_1_FLR_1 | RETAIL_2_FLR_1 | MECH_FLR_1 | STORAGE_FLR_1 | LAUNDRY_FLR_1 | CAFE_FLR_1 | LOBBY_FLR_1 | ROOM_1_FLR_3 | ROOM_2_FLR_3 | ROOM_3_MULT19_FLR_3 | ROOM_4_MULT19_FLR_3 | ROOM_5_FLR_3 | ROOM_6_FLR_3 | CORRIDOR_FLR_3 | ROOM_1_FLR_6 | ROOM_2_FLR_6 | ROOM_3_MULT9_FLR_6 | BANQUET_FLR_6 | DINING_FLR_6 | KITCHEN_FLR_6 | CORRIDOR_FLR_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:46 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 4559.59 | 1873.43 | 406.47 | 1873.22 | 406.47 |
Above Ground Wall Area [m2] | 4025.82 | 1662.30 | 350.71 | 1662.10 | 350.71 |
Window Opening Area [m2] | 1214.08 | 432.93 | 85.84 | 609.46 | 85.84 |
Gross Window-Wall Ratio [%] | 26.63 | 23.11 | 21.12 | 32.54 | 21.12 |
Above Ground Window-Wall Ratio [%] | 30.16 | 26.04 | 24.48 | 36.67 | 24.48 |
Total | |
Gross Roof Area [m2] | 1978.84 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 1978.83 | Yes | Yes | 4826.41 | 1.00 | 0.00 | 533.77 | 0.00 | 0.00 | 8.5035 | 18.58 | 5.3800 |
RETAIL_1_FLR_1 | 67.07 | Yes | Yes | 265.76 | 1.00 | 68.84 | 0.00 | 23.30 | 23.30 | 11.4097 | 6.19 | 10.7600 |
RETAIL_2_FLR_1 | 77.67 | Yes | Yes | 307.76 | 1.00 | 26.57 | 0.00 | 0.00 | 0.00 | 11.4097 | 6.19 | 10.7600 |
MECH_FLR_1 | 164.24 | Yes | Yes | 650.80 | 1.00 | 62.80 | 0.00 | 0.00 | 0.00 | 10.2257 | 5.3800 | |
STORAGE_FLR_1 | 94.76 | Yes | Yes | 375.47 | 1.00 | 36.23 | 0.00 | 0.00 | 0.00 | 4.9514 | 2.6900 | |
LAUNDRY_FLR_1 | 78.04 | Yes | Yes | 309.22 | 1.00 | 85.75 | 0.00 | 0.00 | 0.00 | 4.6285 | 9.29 | 597.5300 |
CAFE_FLR_1 | 188.86 | Yes | Yes | 748.35 | 1.00 | 152.17 | 0.00 | 65.62 | 65.62 | 7.6424 | 1.33 | 5.3800 |
LOBBY_FLR_1 | 1308.19 | Yes | Yes | 5183.56 | 1.00 | 434.79 | 0.00 | 85.24 | 85.24 | 11.4097 | 3.10 | 8.0700 |
ROOM_1_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT19_FLR_3 | 24.52 | Yes | Yes | 74.75 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_4_MULT19_FLR_3 | 24.53 | Yes | Yes | 74.77 | 76.00 | 11.15 | 0.00 | 3.68 | 3.68 | 8.2882 | 16.35 | 10.5200 |
ROOM_5_FLR_3 | 39.02 | Yes | Yes | 118.94 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
ROOM_6_FLR_3 | 39.02 | Yes | Yes | 118.93 | 4.00 | 39.95 | 0.00 | 13.18 | 13.18 | 8.2882 | 26.01 | 6.7500 |
CORRIDOR_FLR_3 | 389.40 | Yes | Yes | 1186.91 | 4.00 | 48.31 | 0.00 | 15.94 | 15.94 | 7.1042 | 0.0000 | |
ROOM_1_FLR_6 | 39.02 | Yes | Yes | 118.94 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 8.2882 | 26.01 | 6.7500 |
ROOM_2_FLR_6 | 39.02 | Yes | Yes | 118.93 | 1.00 | 39.95 | 0.00 | 13.19 | 13.19 | 8.2882 | 26.01 | 6.7500 |
ROOM_3_MULT9_FLR_6 | 24.53 | Yes | Yes | 74.77 | 9.00 | 20.44 | 0.00 | 6.75 | 6.75 | 8.2882 | 16.35 | 10.5200 |
BANQUET_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 7.6424 | 1.33 | 67.8200 |
DINING_FLR_6 | 331.66 | Yes | Yes | 1010.89 | 1.00 | 97.55 | 0.00 | 32.21 | 32.21 | 7.6424 | 1.33 | 67.8200 |
KITCHEN_FLR_6 | 103.30 | Yes | Yes | 314.87 | 1.00 | 87.33 | 0.00 | 26.38 | 26.38 | 11.4097 | 4.65 | 2934.4875 |
CORRIDOR_FLR_6 | 412.12 | Yes | Yes | 1256.16 | 1.00 | 85.47 | 0.00 | 28.22 | 28.22 | 7.1042 | 0.0000 | |
Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 8.4749 | 7.60 | 41.0709 | |||
Conditioned Total | 11345.29 | 35184.81 | 4025.82 | 533.77 | 1214.08 | 1214.08 | 8.4749 | 7.60 | 41.0709 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 26-JUL-19:10 | 02-FEB-20:00 | - | - | - | 02-JAN-21:10 |
Heating | 0.00 | 711544.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 179836.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 73514.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 86439.81 | 89710.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 50287.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 22941.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 9924.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 3777.20 | 175083.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 2394.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 432378.24 | 976339.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 711544.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 179836.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 73514.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 56456.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 29240.64 | 49984.07 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInFreezer | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ReachInRefrigerator | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Laundry | 0.00 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 1248.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 48888.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 150.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 22941.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3262.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 9924.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 3777.20 | 175083.63 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 241.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LowTempRefrigeration | 1061.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
MedTempRefrigeration | 1091.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2196.45 | 0.00 | 0.00 | 0.00 |
Cooling | 2538.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2616.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 578.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 5251.48 | 1939.12 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 3079.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1623.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 132.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 658.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 287.43 | 2471.30 | 0.00 | 0.00 | 0.00 |
Refrigeration | 193.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 16960.28 | 6606.87 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 193.60 | 0.00 | 0.00 | 0.00 |
Cooling | 223.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 230.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 58.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 217.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1494.92 | 582.35 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 193.60 | 0.00 | 0.00 | 0.00 |
Cooling | 223.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 230.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 50.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 462.88 | 170.92 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 271.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 11.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 58.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25.34 | 217.83 | 0.00 | 0.00 | 0.00 |
Refrigeration | 17.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1494.92 | 582.35 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
BASEMENT VAV BOX COMPONENT | 2.52 | 0.597524 | 0.547000 | 1.38 | 1.00 | 0.500000 | 0.000638 | 0.000188 | 1.38 | 16.70 | 0.008000 |
RETAIL_1_FLR_1 VAV BOX COMPONENT | 0.318021 | 0.160708 | 0.547000 | 0.173957 | 0.547000 | 0.500000 | 0.002371 | 0.000117 | 0.194764 | 16.70 | 0.008000 |
RETAIL_2_FLR_1 VAV BOX COMPONENT | 0.228909 | 0.258547 | 0.547000 | 0.125213 | 0.689458 | 0.500000 | 0.001474 | 0.000039 | 0.125213 | 16.70 | 0.008000 |
MECH_FLR_1 VAV BOX COMPONENT | 0.226893 | 0.551597 | 0.547000 | 0.124110 | 1.00 | 0.500000 | 0.000691 | 0.000057 | 0.124110 | 16.70 | 0.008000 |
STORAGE_FLR_1 VAV BOX COMPONENT | 0.096712 | 0.746615 | 0.547000 | 0.052901 | 1.00 | 0.500000 | 0.000510 | 0.000040 | 0.065893 | 16.70 | 0.008000 |
LAUNDRY_FLR_1 VAV BOX COMPONENT | 3.41 | 0.017460 | 0.547000 | 1.86 | 0.547000 | 0.500000 | 0.021822 | 0.000266 | 1.86 | 16.70 | 0.008000 |
CAFE_FLR_1 VAV BOX COMPONENT | 1.32 | 0.108787 | 0.547000 | 0.723620 | 0.547000 | 0.500000 | 0.003502 | 0.000330 | 0.723620 | 16.70 | 0.008000 |
LOBBY_FLR_1 VAV BOX COMPONENT | 4.75 | 0.209892 | 0.547000 | 2.60 | 0.559711 | 0.500000 | 0.001815 | 0.000803 | 2.60 | 16.70 | 0.008000 |
CORRIDOR_FLR_3 VAV BOX COMPONENT | 1.19 | 1.00 | 0.547000 | 0.649237 | 1.00 | 0.500000 | 0.000381 | 0.000330 | 0.649237 | 16.70 | 0.008000 |
BANQUET_FLR_6 VAV BOX COMPONENT | 2.10 | 0.120404 | 0.547000 | 1.15 | 0.547000 | 0.500000 | 0.003164 | 0.000302 | 1.15 | 16.70 | 0.008000 |
DINING_FLR_6 VAV BOX COMPONENT | 2.20 | 0.114679 | 0.547000 | 1.21 | 0.547000 | 0.500000 | 0.003322 | 0.000311 | 1.21 | 16.70 | 0.008000 |
KITCHEN_FLR_6 VAV BOX COMPONENT | 2.35 | 0.700000 | 0.547000 | 1.29 | 0.547000 | 0.500000 | 0.011380 | 0.000210 | 1.29 | 16.70 | 0.008000 |
CORRIDOR_FLR_6 VAV BOX COMPONENT | 0.606882 | 0.517463 | 0.547000 | 0.331964 | 1.00 | 0.500000 | 0.000736 | 0.000225 | 0.372567 | 16.70 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
BASEMENT VAV BOX REHEAT COIL | 8488.41 | 0.000188 | 152.09 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5313.76 | 0.000117 | 115.17 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1768.86 | 0.000039 | 34.57 |
MECH_FLR_1 VAV BOX REHEAT COIL | 2601.38 | 0.000057 | 53.39 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | 1797.71 | 0.000040 | 38.96 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12018.94 | 0.000266 | 216.09 |
CAFE_FLR_1 VAV BOX REHEAT COIL | 14937.48 | 0.000330 | 305.81 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | 36335.23 | 0.000803 | 709.57 |
ROOM_1_FLR_3 FAN COILHEAT COIL | 7782.72 | 0.000172 | 177.19 |
ROOM_2_FLR_3 FAN COILHEAT COIL | 7803.59 | 0.000172 | 177.66 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 43866.13 | 0.000969 | 998.69 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 44237.99 | 0.000977 | 1007.15 |
ROOM_5_FLR_3 FAN COILHEAT COIL | 7746.17 | 0.000171 | 176.36 |
ROOM_6_FLR_3 FAN COILHEAT COIL | 7766.95 | 0.000172 | 176.83 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 14935.38 | 0.000330 | 311.69 |
ROOM_1_FLR_6 FAN COILHEAT COIL | 2383.36 | 0.000053 | 54.26 |
ROOM_2_FLR_6 FAN COILHEAT COIL | 2395.33 | 0.000053 | 54.53 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 11381.29 | 0.000251 | 259.11 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | 13661.37 | 0.000302 | 261.89 |
DINING_FLR_6 VAV BOX REHEAT COIL | 14092.73 | 0.000311 | 269.47 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9508.32 | 0.000210 | 172.80 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10166.01 | 0.000225 | 220.35 |
VAV WITH REHEAT_HEATC | 312531.81 | 0.006905 | 3979.38 |
FLR_3_DOAS_HEATC | 30467.96 | 0.000673 | 387.94 |
Design Size Maximum Air Flow Rate [m3/s] | User-Specified Maximum Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 DIRECT AIR | 1.17 | 0.061733 |
ROOM_2_FLR_3 DIRECT AIR | 1.15 | 0.061733 |
ROOM_3_MULT19_FLR_3 DIRECT AIR | 5.97 | 0.836953 |
ROOM_4_MULT19_FLR_3 DIRECT AIR | 6.08 | 0.836953 |
ROOM_5_FLR_3 DIRECT AIR | 1.05 | 0.061733 |
ROOM_6_FLR_3 DIRECT AIR | 1.04 | 0.061733 |
ROOM_1_FLR_6 DIRECT AIR | 0.303533 | 0.015433 |
ROOM_2_FLR_6 DIRECT AIR | 0.298537 | 0.015433 |
ROOM_3_MULT9_FLR_6 DIRECT AIR | 1.17 | 0.099113 |
Design Size Maximum Supply Air Flow Rate [m3/s] | Design Size Maximum Hot Water Flow [m3/s] | Design Size Maximum Cold Water Flow [m3/s] | |
ROOM_1_FLR_3 FAN COIL | 1.17 | 0.000172 | 0.000367 |
ROOM_2_FLR_3 FAN COIL | 1.15 | 0.000172 | 0.000361 |
ROOM_3_MULT19_FLR_3 FAN COIL | 5.97 | 0.000969 | 0.001848 |
ROOM_4_MULT19_FLR_3 FAN COIL | 6.08 | 0.000977 | 0.002002 |
ROOM_5_FLR_3 FAN COIL | 1.05 | 0.000171 | 0.000331 |
ROOM_6_FLR_3 FAN COIL | 1.04 | 0.000172 | 0.000329 |
ROOM_1_FLR_6 FAN COIL | 0.303533 | 0.000053 | 0.000095 |
ROOM_2_FLR_6 FAN COIL | 0.298537 | 0.000053 | 0.000094 |
ROOM_3_MULT9_FLR_6 FAN COIL | 1.17 | 0.000251 | 0.000377 |
Design Size Maximum Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILFAN | 1.17 |
ROOM_2_FLR_3 FAN COILFAN | 1.15 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | 5.97 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | 6.08 |
ROOM_5_FLR_3 FAN COILFAN | 1.05 |
ROOM_6_FLR_3 FAN COILFAN | 1.04 |
ROOM_1_FLR_6 FAN COILFAN | 0.303533 |
ROOM_2_FLR_6 FAN COILFAN | 0.298537 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | 1.17 |
Design Size Design Water Flow Rate [m3/s] | User-Specified Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | Design Size Design Coil Load [W] | Design Size Design Air Flow Rate [m3/s] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | 0.000367 | 1.17 | 0.008688 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_3 FAN COILCOOL COIL | 0.000361 | 1.15 | 0.008691 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 0.001848 | 5.97 | 0.008628 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 0.002002 | 6.08 | 0.008863 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_5_FLR_3 FAN COILCOOL COIL | 0.000331 | 1.05 | 0.008712 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_6_FLR_3 FAN COILCOOL COIL | 0.000329 | 1.04 | 0.008714 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_1_FLR_6 FAN COILCOOL COIL | 0.000095 | 0.303533 | 0.008681 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_2_FLR_6 FAN COILCOOL COIL | 0.000094 | 0.298537 | 0.008684 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 0.000377 | 1.17 | 0.008788 | 21.71 | 6.70 | 12.80 | 0.008500 | ||
VAV WITH REHEAT_COOLC | 0.019715 | 0.012838 | 27.99 | 6.70 | 10.90 | 0.008683 | 689355.67 | 21.04 | |
FLR_3_DOAS_COOLC | 0.002508 | 0.015344 | 31.20 | 6.70 | 10.91 | 0.008683 | 87700.73 | 2.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT | 11.66 | 11.66 | 21.32 | 11.66 | 21.04 | 21.04 | 0.300000 | 0.554262 | 21.04 |
FLR_3_DOAS | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 0.300000 | 1.00 | 2.05 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV WITH REHEAT_OA_CONTROLLER | 21.04 | |
FLR_3_DOAS_OA_CONTROLLER | 2.05 | 2.05 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV WITH REHEAT HEAT RECOVERY | 11.66 |
FLR_3_DOAS HEAT RECOVERY | 2.05 |
Design Size Maximum Flow Rate [m3/s] | |
VAV WITH REHEAT_FAN | 21.04 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV WITH REHEAT_COOLC_CONTROLLER | 0.019715 | 0.000024 |
VAV WITH REHEAT_HEATC_CONTROLLER | 0.006905 | |
FLR_3_DOAS_COOLC_CONTROLLER | 0.002508 | 0.000190 |
FLR_3_DOAS_HEATC_CONTROLLER | 0.000673 |
User-Specified Maximum Flow Rate [m3/s] | |
FLR_3_DOAS_FAN | 2.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.028028 | 5361.38 |
HEATSYS1 PUMP | 0.013786 | 3522.22 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000375 | 0.045004 |
HEATSYS1 | 0.013786 | 1.65 |
COOLSYS1 | 0.028028 | 3.36 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SWHSYS1 PUMP | 0.000375 | 47.91 |
COOLSYS1 PUMP | 0.028028 | 1787.13 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000375 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 623988.89 | 623988.89 | 0.013786 |
Design Size Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER | 0.028028 | 979998.81 | 980593.89 | 111.79 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
RETAIL_1_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
CAFE_FLR_1_CEILING | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
LOBBY_FLR_1_CEILING_2 | ROOM_1_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH | ROOM_1_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH | |
Possible Shadow Receivers | |
RETAIL_1_FLR_1_WALL_SOUTH | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | |
RETAIL_2_FLR_1_WALL_WEST | RETAIL_2_FLR_1_WALL_WEST_DOOR | |
STORAGE_FLR_1_WALL_NORTH | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | |
LAUNDRY_FLR_1_WALL_EAST | LAUNDRY_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_EAST | CAFE_FLR_1_WALL_EAST_DOOR | |
CAFE_FLR_1_WALL_SOUTH | CAFE_FLR_1_WALL_SOUTH_WINDOW | |
LOBBY_FLR_1_WALL_1_NORTH | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | |
LOBBY_FLR_1_WALL_1_SOUTH | LOBBY_FLR_1_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_SOUTH | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_3_WALL_WEST | ROOM_1_FLR_3_WALL_WEST_WINDOW | |
ROOM_2_FLR_3_WALL_NORTH | ROOM_2_FLR_3_WALL_NORTH_WINDOW | |
ROOM_2_FLR_3_WALL_WEST | ROOM_2_FLR_3_WALL_WEST_WINDOW | |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_4_MULT19_FLR_3_WALL_NORTH | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | |
ROOM_5_FLR_3_WALL_EAST | ROOM_5_FLR_3_WALL_EAST_WINDOW | |
ROOM_5_FLR_3_WALL_SOUTH | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | |
ROOM_6_FLR_3_WALL_NORTH | ROOM_6_FLR_3_WALL_NORTH_WINDOW | |
ROOM_6_FLR_3_WALL_EAST | ROOM_6_FLR_3_WALL_EAST_WINDOW | |
CORRIDOR_FLR_3_WALL_1_NORTH | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_NORTH | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_3_WALL_1_SOUTH | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_3_WALL_2_SOUTH | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_SOUTH | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | |
ROOM_1_FLR_6_WALL_WEST | ROOM_1_FLR_6_WALL_WEST_WINDOW | |
ROOM_2_FLR_6_WALL_NORTH | ROOM_2_FLR_6_WALL_NORTH_WINDOW | |
ROOM_2_FLR_6_WALL_WEST | ROOM_2_FLR_6_WALL_WEST_WINDOW | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | |
BANQUET_FLR_6_WALL_NORTH | BANQUET_FLR_6_WALL_NORTH_WINDOW | |
DINING_FLR_6_WALL_NORTH | DINING_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_NORTH | KITCHEN_FLR_6_WALL_NORTH_WINDOW | |
KITCHEN_FLR_6_WALL_EAST | KITCHEN_FLR_6_WALL_EAST_WINDOW | |
KITCHEN_FLR_6_WALL_1_SOUTH | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | |
CORRIDOR_FLR_6_WALL_1_NORTH | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_NORTH | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | |
CORRIDOR_FLR_6_WALL_2_SOUTH | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | HotelLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | DOE-2 |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 22 | 235 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 41.45 | 11.51 | -1.22 | 1 | 1 | 1 | 0.00 | 86.56 | 0.00 | 22.86 | -2.44 | 0.00 | 2.44 | 4826.41 | TARP | DOE-2 | 1978.83 | 0.00 | 0.00 | 0.00 | 13 | 0 | 0 | Yes |
2 | RETAIL_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 2.90 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 265.76 | TARP | DOE-2 | 67.07 | 68.84 | 45.54 | 23.30 | 6 | 1 | 0 | Yes |
3 | RETAIL_2_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 5.79 | 9.14 | 1.98 | 1 | 1 | 1 | 0.00 | 11.58 | 5.79 | 12.50 | 0.00 | 3.96 | 3.96 | 307.76 | TARP | DOE-2 | 77.67 | 26.57 | 24.62 | 0.00 | 6 | 1 | 0 | Yes |
4 | MECH_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 61.87 | 17.68 | 1.98 | 1 | 1 | 1 | 53.95 | 69.80 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 650.80 | TARP | DOE-2 | 164.24 | 62.80 | 62.80 | 0.00 | 6 | 0 | 0 | Yes |
5 | STORAGE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 74.37 | 17.68 | 1.98 | 1 | 1 | 1 | 69.80 | 78.94 | 12.50 | 22.86 | 0.00 | 3.96 | 3.96 | 375.47 | TARP | DOE-2 | 94.76 | 36.23 | 28.80 | 0.00 | 6 | 1 | 0 | Yes |
6 | LAUNDRY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 14.33 | 1.98 | 1 | 1 | 1 | 81.99 | 86.56 | 5.79 | 22.86 | 0.00 | 3.96 | 3.96 | 309.22 | TARP | DOE-2 | 78.04 | 85.75 | 83.80 | 0.00 | 6 | 1 | 0 | Yes |
7 | CAFE_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 70.26 | 2.90 | 1.98 | 1 | 1 | 1 | 53.95 | 86.56 | 0.00 | 5.79 | 0.00 | 3.96 | 3.96 | 748.35 | TARP | DOE-2 | 188.86 | 152.17 | 84.60 | 65.62 | 7 | 2 | 0 | Yes |
8 | LOBBY_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 38.29 | 12.45 | 1.98 | 1 | 1 | 1 | 0.00 | 81.99 | 0.00 | 22.86 | 0.00 | 3.96 | 3.96 | 5183.56 | TARP | DOE-2 | 1308.19 | 434.79 | 345.64 | 85.24 | 18 | 3 | 0 | Yes |
9 | ROOM_1_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
10 | ROOM_2_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 8.53 | 1 | 4 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
11 | ROOM_3_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 8.53 | 9.14 | 8.53 | 1 | 76 | 1 | 6.71 | 10.36 | 5.79 | 12.50 | 7.01 | 10.06 | 3.05 | 74.75 | TARP | DOE-2 | 24.52 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
12 | ROOM_4_MULT19_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 12.19 | 19.51 | 8.53 | 1 | 76 | 1 | 10.36 | 14.02 | 16.15 | 22.86 | 7.01 | 10.06 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 11.15 | 7.47 | 3.68 | 6 | 1 | 0 | Yes |
13 | ROOM_5_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 10.06 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 5.79 | 14.33 | 7.01 | 10.06 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
14 | ROOM_6_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 84.28 | 18.59 | 8.53 | 1 | 4 | 1 | 81.99 | 86.56 | 14.33 | 22.86 | 7.01 | 10.06 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.77 | 13.18 | 6 | 2 | 0 | Yes |
15 | CORRIDOR_FLR_3 | 0.0 | 0.00 | 0.00 | 0.00 | 43.28 | 14.33 | 8.53 | 1 | 4 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 7.01 | 10.06 | 3.05 | 1186.91 | TARP | DOE-2 | 389.40 | 48.31 | 32.37 | 15.94 | 20 | 4 | 0 | Yes |
16 | ROOM_1_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 10.06 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 5.79 | 14.33 | 16.15 | 19.20 | 3.05 | 118.94 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
17 | ROOM_2_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 2.29 | 18.59 | 17.68 | 1 | 1 | 1 | 0.00 | 4.57 | 14.33 | 22.86 | 16.15 | 19.20 | 3.05 | 118.93 | TARP | DOE-2 | 39.02 | 39.95 | 26.76 | 13.19 | 6 | 2 | 0 | Yes |
18 | ROOM_3_MULT9_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 7.93 | 7.62 | 17.68 | 1 | 9 | 1 | 4.57 | 11.28 | 5.79 | 9.45 | 16.15 | 19.20 | 3.05 | 74.77 | TARP | DOE-2 | 24.53 | 20.44 | 13.69 | 6.75 | 6 | 1 | 0 | Yes |
19 | BANQUET_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 26.37 | 17.68 | 17.68 | 1 | 1 | 1 | 10.36 | 42.37 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
20 | DINING_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 63.55 | 17.68 | 17.68 | 1 | 1 | 1 | 47.55 | 79.55 | 12.50 | 22.86 | 16.15 | 19.20 | 3.05 | 1010.89 | TARP | DOE-2 | 331.66 | 97.55 | 65.34 | 32.21 | 6 | 1 | 0 | Yes |
21 | KITCHEN_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 82.99 | 14.11 | 17.68 | 1 | 1 | 1 | 79.55 | 86.56 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 314.87 | TARP | DOE-2 | 103.30 | 87.33 | 60.95 | 26.38 | 8 | 3 | 0 | Yes |
22 | CORRIDOR_FLR_6 | 0.0 | 0.00 | 0.00 | 0.00 | 41.51 | 13.35 | 17.68 | 1 | 1 | 1 | 4.57 | 81.99 | 5.79 | 22.86 | 16.15 | 19.20 | 3.05 | 1256.16 | TARP | DOE-2 | 412.12 | 85.47 | 57.25 | 28.22 | 15 | 3 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 1978.83 | 106.5 | 18.581 | 5.382E-002 | 8.503 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.883 | No |
2 | RETAIL_1_FLR_1 | 67.07 | 10.8 | 6.194 | 0.161 | 11.410 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.170 | No |
3 | RETAIL_2_FLR_1 | 77.67 | 12.5 | 6.194 | 0.161 | 11.410 | 10.760 | 0.000 | 0.000 | 0.000 | 0.000 | 22.170 | No |
4 | MECH_FLR_1 | 164.24 | 0.0 | N/A | 0.000 | 10.226 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 15.606 | No |
5 | STORAGE_FLR_1 | 94.76 | 0.0 | N/A | 0.000 | 4.951 | 2.690 | 0.000 | 0.000 | 0.000 | 0.000 | 7.641 | No |
6 | LAUNDRY_FLR_1 | 78.04 | 8.4 | 9.290 | 0.108 | 4.628 | 61.680 | 535.850 | 0.000 | 0.000 | 0.000 | 602.158 | No |
7 | CAFE_FLR_1 | 188.86 | 142.3 | 1.327 | 0.753 | 7.642 | 5.380 | 0.000 | 0.000 | 0.000 | 0.000 | 13.022 | No |
8 | LOBBY_FLR_1 | 1308.19 | 422.4 | 3.097 | 0.323 | 11.410 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 19.480 | No |
9 | ROOM_1_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
10 | ROOM_2_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
11 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 16.349 | 6.116E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
12 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
13 | ROOM_5_FLR_3 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
14 | ROOM_6_FLR_3 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
15 | CORRIDOR_FLR_3 | 389.40 | 0.0 | N/A | 0.000 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
16 | ROOM_1_FLR_6 | 39.02 | 1.5 | 26.015 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
17 | ROOM_2_FLR_6 | 39.02 | 1.5 | 26.012 | 3.844E-002 | 8.288 | 6.750 | 0.000 | 0.000 | 0.000 | 0.000 | 15.038 | No |
18 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 16.354 | 6.115E-002 | 8.288 | 10.520 | 0.000 | 0.000 | 0.000 | 0.000 | 18.808 | No |
19 | BANQUET_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.642 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.462 | No |
20 | DINING_FLR_6 | 331.66 | 249.9 | 1.327 | 0.753 | 7.642 | 67.820 | 0.000 | 0.000 | 0.000 | 0.000 | 75.462 | No |
21 | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.645 | 0.215 | 11.410 | 515.227 | 2419.260 | 0.000 | 0.000 | 0.000 | 2945.897 | No |
22 | CORRIDOR_FLR_6 | 412.12 | 0.0 | N/A | 0.000 | 7.104 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.104 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT PEOPLE | BLDG_OCC_SCH | BASEMENT | 1978.83 | 106.5 | 106.5 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 106 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | RETAIL_1_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 10.8 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | RETAIL_2_FLR_1 PEOPLE | BLDG_OCC_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 12.5 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 13 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | LAUNDRY_FLR_1 PEOPLE | BLDG_OCC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 8.4 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | CAFE_FLR_1 PEOPLE | BLDG_OCC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 142.3 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 142 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | LOBBY_FLR_1 PEOPLE | BLDG_OCC_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 422.4 | 0.323 | 3.097 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 422 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | ROOM_1_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | ROOM_2_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | ROOM_3_MULT19_FLR_3 PEOPLE | ALWAYS_OFF | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 1.5 | 6.116E-002 | 16.349 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | ROOM_4_MULT19_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | ROOM_5_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | ROOM_6_FLR_3 PEOPLE | GUESTROOM_OCC_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | ROOM_1_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.015 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | ROOM_2_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 1.5 | 3.844E-002 | 26.012 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | ROOM_3_MULT9_FLR_6 PEOPLE | GUESTROOM_OCC_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.5 | 6.115E-002 | 16.354 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | BANQUET_FLR_6 PEOPLE | BLDG_OCC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
17 | DINING_FLR_6 PEOPLE | BLDG_OCC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 249.9 | 0.753 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 250 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
18 | KITCHEN_FLR_6 PEOPLE | BLDG_OCC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 22.2 | 0.215 | 4.645 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 22 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_OFFICE_BSMT_SCH | BASEMENT | 1978.83 | 106.5 | 16826.961 | 8.503 | 158.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 16826.961 |
2 | RETAIL_1_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 765.267 | 11.410 | 70.668 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 765.267 |
3 | RETAIL_2_FLR_1_LIGHTS | BLDG_LIGHT_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 886.182 | 11.410 | 70.668 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 886.182 |
4 | MECH_FLR_1_LIGHTS | BLDG_LIGHT_MECHANIC_SCH | MECH_FLR_1 | 164.24 | 0.0 | 1679.504 | 10.226 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1679.504 |
5 | STORAGE_FLR_1_LIGHTS | BLDG_LIGHT_STORAGE_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 469.191 | 4.951 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 469.191 |
6 | LAUNDRY_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 361.204 | 4.628 | 43.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 361.204 |
7 | CAFE_FLR_1_LIGHTS | BLDG_LIGHT_MISC_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1443.354 | 7.642 | 10.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1443.354 |
8 | LOBBY_FLR_1_LIGHTS | BLDG_LIGHT_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 14926.070 | 11.410 | 35.333 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 14926.070 |
9 | ROOM_1_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 323.423 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.423 |
10 | ROOM_2_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 323.385 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.385 |
11 | ROOM_3_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 203.259 | 8.288 | 135.506 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.259 |
12 | ROOM_4_MULT19_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
13 | ROOM_5_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 323.423 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.423 |
14 | ROOM_6_FLR_3_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 323.385 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.385 |
15 | CORRIDOR_FLR_3_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2766.401 | 7.104 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2766.401 |
16 | ROOM_1_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 323.423 | 8.288 | 215.615 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.423 |
17 | ROOM_2_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 323.385 | 8.288 | 215.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 323.385 |
18 | ROOM_3_MULT9_FLR_6_LIGHTS | BLDG_LIGHT_GUESTROOM_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 203.314 | 8.288 | 135.543 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 203.314 |
19 | BANQUET_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 2534.651 | 7.642 | 10.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2534.651 |
20 | DINING_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | DINING_FLR_6 | 331.66 | 249.9 | 2534.651 | 7.642 | 10.143 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2534.651 |
21 | KITCHEN_FLR_6_LIGHTS | BLDG_LIGHT_MISC_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 1178.678 | 11.410 | 53.003 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1178.678 |
22 | CORRIDOR_FLR_6_LIGHTS | BLDG_LIGHT_CORRIDOR_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 2927.809 | 7.104 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2927.809 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | BASEMENT_EQUIP_SCH | BASEMENT | 1978.83 | 106.5 | 10646.106 | 5.380 | 99.964 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10646.106 |
2 | RETAIL_1_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 721.688 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 721.688 |
3 | RETAIL_2_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 835.717 | 10.760 | 66.644 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 835.717 |
4 | MECH_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | MECH_FLR_1 | 164.24 | 0.0 | 883.628 | 5.380 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 883.628 |
5 | STORAGE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 254.902 | 2.690 | N/A | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 254.902 |
6 | LAUNDRY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4813.474 | 61.680 | 573.033 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4813.474 |
7 | CAFE_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 1016.077 | 5.380 | 7.140 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1016.077 |
8 | LOBBY_FLR_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 10557.062 | 8.070 | 24.991 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 10557.062 |
9 | ROOM_1_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
10 | ROOM_2_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
11 | ROOM_3_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 257.991 | 10.520 | 171.994 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 257.991 |
12 | ROOM_4_MULT19_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
13 | ROOM_5_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_5_FLR_3 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
14 | ROOM_6_FLR_3_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_6_FLR_3 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
15 | ROOM_1_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_1_FLR_6 | 39.02 | 1.5 | 263.399 | 6.750 | 175.599 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.399 |
16 | ROOM_2_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_2_FLR_6 | 39.02 | 1.5 | 263.368 | 6.750 | 175.579 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 263.368 |
17 | ROOM_3_MULT9_FLR_6_PLUGMISC_EQUIP | GUESTROOM_EQP_SCH_ADVA | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 258.061 | 10.520 | 172.041 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 258.061 |
18 | BANQUET_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
19 | DINING_FLR_6_MISCPLUG_EQUIP | KITCHEN_ELEC_EQUIP_SCH | DINING_FLR_6 | 331.66 | 249.9 | 22493.008 | 67.820 | 90.009 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 0.000 | 6747.903 |
20 | KITCHEN_FLR_6_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 52482.799 | 508.040 | 2360.050 | 0.200 | 0.500 | 0.100 | 0.200 | Cooking | 0.000 | 15744.840 |
21 | KITCHEN_FLR_6_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 457.500 | 4.429 | 20.573 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 457.500 | 457.500 |
22 | KITCHEN_FLR_6_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_FLR_6 | 103.30 | 22.2 | 285.000 | 2.759 | 12.816 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 285.000 | 285.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LAUNDRY_FLR_1_MISCGAS_EQUIP | BLDG_EQUIP_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 41817.449 | 535.850 | 4978.268 | 0.000 | 0.500 | 0.000 | 0.500 | Laundry | 0.000 | 41817.449 |
2 | KITCHEN_FLR_6_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 249920.353 | 2419.260 | 11238.437 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 74976.106 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | OVERHEAD DOOR_CON | 2 | 1 | 1 | 0.167 | 1.761 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
3 | INTERIORFURNISHINGS | 3 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 8 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | NONRES_ROOF | 18 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
6 | NONRES_EXT_WALL | 21 | 3 | 9 | 0.167 | 0.4874 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | NONRES_FLOOR | 24 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
8 | NONRES_FLOOR_CEILING | 27 | 3 | 7 | 0.167 | 0.1901 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
9 | BASEMENT_FLOOR | 30 | 2 | 7 | 0.333 | 2.705 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_EAST_CFACTOR | 34 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_SOUTH_CFACTOR | 35 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_WEST_CFACTOR | 36 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | OVERHEAD DOOR_CON PANEL | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5677 |
3 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
8 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
9 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.884 |
11 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
12 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
13 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
14 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
15 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
16 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
17 | NONRES_FLOOR_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.000 |
18 | M10 200MM CONCRETE BLOCK BASEMENT WALL | 0.2032 | 1.326 | 1842.000 | 912.000 | 0.1532 |
19 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
20 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1010000 | 2.1010000 | 2.1010000 | |
3 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
4 | 0 | 1.7613636 | 1.7613636 | 1.7613636 | |
5 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
6 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
7 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
8 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
9 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
10 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
11 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
12 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
13 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
14 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
15 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
16 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
17 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
18 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
19 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
20 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
21 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
22 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
23 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
24 | 9 | 0.22071239E-14 | -0.25891382E-15 | -0.17018650E-09 | -0.41695020E-16 |
25 | 8 | 0.24744598E-07 | 0.66649001E-13 | 0.40731198E-03 | -0.28135460E-09 |
26 | 7 | -0.13120292E-01 | 0.33703133E-08 | -0.24350396E-01 | 0.14918252E-03 |
27 | 6 | 0.42922440 | 0.11607716E-05 | 0.49237259 | -0.50291810E-02 |
28 | 5 | -5.4235101 | 0.42968024E-04 | -4.5968048 | 0.66072313E-01 |
29 | 4 | 34.033019 | 0.34874410E-03 | 22.047808 | -0.43580094 |
30 | 3 | -113.41739 | 0.75474606E-03 | -56.824750 | 1.5468526 |
31 | 2 | 199.30218 | 0.42189037E-03 | 78.976973 | -2.9351941 |
32 | 1 | -171.96619 | 0.44777434E-04 | -55.576854 | 2.7596376 |
33 | 0 | 57.057407 | 0.25325413E-06 | 15.506813 | |
34 | 7 | -0.16359629E-14 | -0.14530353E-16 | -0.22331004E-13 | 0.54056000E-15 |
35 | 6 | 0.18262352E-10 | 0.22801053E-11 | 0.52333849E-09 | -0.18642118E-10 |
36 | 5 | -0.59540244E-07 | 0.11129510E-07 | -0.21928235E-05 | 0.17164558E-06 |
37 | 4 | 0.60861605E-04 | 0.41961443E-05 | 0.17683552E-02 | -0.28248824E-03 |
38 | 3 | -0.87523238E-02 | 0.14809838E-03 | -0.21562890 | 0.43346081E-01 |
39 | 2 | 0.12409989 | 0.64146884E-03 | 2.9009744 | -0.61915653 |
40 | 1 | -0.31397648 | 0.40472017E-03 | -7.1381115 | 1.5697592 |
41 | 0 | 0.19977219 | 0.56546383E-05 | 4.4522022 | |
42 | 7 | -0.22331004E-13 | -0.14530353E-16 | -0.16359629E-14 | 0.54056000E-15 |
43 | 6 | 0.52333849E-09 | 0.22801053E-11 | 0.18262352E-10 | -0.18642118E-10 |
44 | 5 | -0.21928235E-05 | 0.11129510E-07 | -0.59540244E-07 | 0.17164558E-06 |
45 | 4 | 0.17683552E-02 | 0.41961443E-05 | 0.60861605E-04 | -0.28248824E-03 |
46 | 3 | -0.21562890 | 0.14809838E-03 | -0.87523238E-02 | 0.43346081E-01 |
47 | 2 | 2.9009744 | 0.64146884E-03 | 0.12409989 | -0.61915653 |
48 | 1 | -7.1381115 | 0.40472017E-03 | -0.31397648 | 1.5697592 |
49 | 0 | 4.4522022 | 0.56546383E-05 | 0.19977219 | |
50 | 7 | -0.52459208E-15 | -0.63961428E-15 | -0.12292524E-09 | -0.35846135E-17 |
51 | 6 | 0.39860198E-02 | 0.96339020E-07 | 0.40499006E-03 | -0.70890431E-04 |
52 | 5 | -0.20832379 | 0.49172556E-04 | -0.20585669E-01 | 0.38489246E-02 |
53 | 4 | 3.5198270 | 0.18993977E-02 | 0.34924834 | -0.69168259E-01 |
54 | 3 | -23.366787 | 0.13311857E-01 | -2.4329538 | 0.50524779 |
55 | 2 | 64.890127 | 0.19943872E-01 | 7.3672511 | -1.5911358 |
56 | 1 | -76.040094 | 0.56792084E-02 | -9.5568013 | 2.1361271 |
57 | 0 | 31.242244 | 0.96490710E-04 | 4.3344156 | |
58 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
59 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
60 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
61 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
62 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
63 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
64 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
65 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
66 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
67 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
68 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
69 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
70 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
71 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
72 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
73 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
74 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
75 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
76 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
77 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
78 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
79 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
80 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
81 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
82 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
83 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
84 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
85 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
86 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
87 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
88 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
89 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.36_SHGC_0.4 | 31 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.441 |
2 | RESWINDOW_U_0.36_SHGC_0.4 | 32 | 1 | VerySmooth | 2.045 | 0.394 | 0.315 | 0.441 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 7 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | CAFE_FLR_1 | 1 | 0 |
2 | LOBBY_FLR_1 | 1 | 0 |
3 | BANQUET_FLR_6 | 1 | 0 |
4 | DINING_FLR_6 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | CAFE_FLR_1 | 0 | |
2 | LOBBY_FLR_1 | 0 | |
3 | BANQUET_FLR_6 | 0 | |
4 | DINING_FLR_6 | 0 |
Number of Refrigeration Compressor Racks | |
1 | 2 |
Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 1.500 |
2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 3.000 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHW BOOSTER WATER HEATER | 2.2712E-002 | 8000.0 | 1.240 | 1.1473 |
2 | WaterHeater:Mixed | SWH LAUNDRY | 1.1356 | 87921.3 | 0.536 | 0.4981 |
3 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 2.2712 | 175842.6 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
6 | BASEMENT_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
7 | BASEMENT_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
8 | BASEMENT_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
9 | BASEMENT_CEILING_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
10 | BASEMENT_CEILING_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
11 | BASEMENT_CEILING_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
12 | BASEMENT_CEILING_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
13 | BASEMENT_CEILING_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
14 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 36.17 | -999.00 | 0 | No | No |
15 | RETAIL_1_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 4 | No | No |
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 1 | No | No |
17 | RETAIL_1_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 3 | No | No |
18 | RETAIL_1_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
19 | RETAIL_1_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
20 | RETAIL_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
21 | RETAIL_1_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 17.37 | 7.72 | 0.34 | 0 | No | No |
23 | RETAIL_2_FLR_1_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
25 | RETAIL_2_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
26 | RETAIL_2_FLR_1_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
27 | RETAIL_2_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
28 | RETAIL_2_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
29 | RETAIL_2_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 6.71 | 8.49 | 0.00 | 0 | No | No |
31 | MECH_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
32 | MECH_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
33 | MECH_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
34 | MECH_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
35 | MECH_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
36 | MECH_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
37 | MECH_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 15.85 | 12.53 | 0.00 | 0 | No | No |
38 | STORAGE_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
40 | STORAGE_FLR_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
41 | STORAGE_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
42 | STORAGE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
43 | STORAGE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
44 | STORAGE_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
45 | STORAGE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 9.14 | 9.72 | 0.00 | 0 | No | No |
46 | LAUNDRY_FLR_1_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
47 | LAUNDRY_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
49 | LAUNDRY_FLR_1_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
50 | LAUNDRY_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
51 | LAUNDRY_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
52 | LAUNDRY_FLR_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 21.64 | 7.21 | 0.00 | 0 | No | No |
54 | CAFE_FLR_1_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 3 | No | No |
55 | CAFE_FLR_1_WALL_EAST_DOOR | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
56 | CAFE_FLR_1_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 4 | No | No |
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 1 | No | No |
58 | CAFE_FLR_1_WALL_1_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
59 | CAFE_FLR_1_WALL_2_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
60 | CAFE_FLR_1_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
61 | CAFE_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
62 | CAFE_FLR_1_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
63 | CAFE_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 38.40 | 9.84 | 0.43 | 0 | No | No |
64 | LOBBY_FLR_1_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
67 | LOBBY_FLR_1_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
68 | LOBBY_FLR_1_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 4 | No | No |
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 1 | No | No |
70 | LOBBY_FLR_1_WALL_1_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 3 | No | No |
71 | LOBBY_FLR_1_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
72 | LOBBY_FLR_1_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
73 | LOBBY_FLR_1_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
74 | LOBBY_FLR_1_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
75 | LOBBY_FLR_1_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
76 | LOBBY_FLR_1_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
77 | LOBBY_FLR_1_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
78 | LOBBY_FLR_1_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
79 | LOBBY_FLR_1_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
80 | LOBBY_FLR_1_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
81 | LOBBY_FLR_1_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
82 | LOBBY_FLR_1_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
83 | LOBBY_FLR_1_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
84 | LOBBY_FLR_1_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
85 | LOBBY_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.96 | 109.73 | 24.95 | 0.20 | 0 | No | No |
86 | ROOM_1_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
88 | ROOM_1_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
90 | ROOM_1_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
91 | ROOM_1_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
92 | ROOM_1_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
93 | ROOM_1_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
94 | ROOM_1_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
95 | ROOM_2_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
97 | ROOM_2_FLR_3_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
99 | ROOM_2_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
100 | ROOM_2_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
101 | ROOM_2_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
102 | ROOM_2_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
103 | ROOM_2_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
109 | ROOM_3_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
110 | ROOM_3_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 3 | No | No |
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 2 | No | No |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
117 | ROOM_4_MULT19_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
118 | ROOM_4_MULT19_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 3.66 | 4.73 | 0.33 | 0 | No | No |
120 | ROOM_5_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
122 | ROOM_5_FLR_3_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
124 | ROOM_5_FLR_3_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
125 | ROOM_5_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
126 | ROOM_5_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
127 | ROOM_5_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
128 | ROOM_5_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
129 | ROOM_6_FLR_3_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
131 | ROOM_6_FLR_3_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
133 | ROOM_6_FLR_3_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
134 | ROOM_6_FLR_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
135 | ROOM_6_FLR_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
136 | ROOM_6_FLR_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
137 | ROOM_6_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
138 | CORRIDOR_FLR_3_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 3 | No | No |
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 2 | No | No |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
147 | CORRIDOR_FLR_3_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
148 | CORRIDOR_FLR_3_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
149 | CORRIDOR_FLR_3_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
150 | CORRIDOR_FLR_3_WALL_4_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
152 | CORRIDOR_FLR_3_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
153 | CORRIDOR_FLR_3_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
154 | CORRIDOR_FLR_3_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
155 | CORRIDOR_FLR_3_WALL_4_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
156 | CORRIDOR_FLR_3_FLOOR_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
157 | CORRIDOR_FLR_3_FLOOR_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
158 | CORRIDOR_FLR_3_FLOOR_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
159 | CORRIDOR_FLR_3_CEILING_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
160 | CORRIDOR_FLR_3_CEILING_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
161 | CORRIDOR_FLR_3_CEILING_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 15.85 | 8.24 | 0.33 | 0 | No | No |
163 | ROOM_1_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
165 | ROOM_1_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
167 | ROOM_1_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
168 | ROOM_1_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
169 | ROOM_1_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
170 | ROOM_1_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
171 | ROOM_1_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
172 | ROOM_2_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
174 | ROOM_2_FLR_6_WALL_WEST | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 3 | No | No |
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | 0 | 194.63 | 84.12 | 19.20 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 2 | No | No |
176 | ROOM_2_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
177 | ROOM_2_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
178 | ROOM_2_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
179 | ROOM_2_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
180 | ROOM_2_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 13.11 | 5.95 | 0.33 | 0 | No | No |
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 3 | No | No |
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 2 | No | No |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
186 | ROOM_3_MULT9_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
187 | ROOM_3_MULT9_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 6.71 | 4.73 | 0.33 | 0 | No | No |
189 | BANQUET_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
191 | BANQUET_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
192 | BANQUET_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
193 | BANQUET_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
194 | BANQUET_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
195 | BANQUET_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
196 | BANQUET_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
197 | DINING_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 3 | No | No |
198 | DINING_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 2 | No | No |
199 | DINING_FLR_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
200 | DINING_FLR_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
201 | DINING_FLR_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
202 | DINING_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
203 | DINING_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
204 | DINING_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 32.00 | 15.66 | 0.33 | 0 | No | No |
205 | KITCHEN_FLR_6_WALL_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
207 | KITCHEN_FLR_6_WALL_EAST | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | 0 | 194.63 | 217.46 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 3 | No | No |
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 2 | No | No |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
212 | KITCHEN_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
213 | KITCHEN_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
214 | KITCHEN_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
215 | KITCHEN_FLR_6_CEILING | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
216 | KITCHEN_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.65 | 8.58 | 0.30 | 0 | No | No |
217 | CORRIDOR_FLR_6_WALL_1_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0 | 670.01 | 217.46 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 3 | No | No |
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 0 | 506.51 | 211.91 | 19.20 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 2 | No | No |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
224 | CORRIDOR_FLR_6_WALL_4_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
226 | CORRIDOR_FLR_6_WALL_1_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
227 | CORRIDOR_FLR_6_WALL_2_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
228 | CORRIDOR_FLR_6_WALL_3_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
229 | CORRIDOR_FLR_6_WALL_1_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
230 | CORRIDOR_FLR_6_WALL_2_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
231 | CORRIDOR_FLR_6_WALL_3_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
232 | CORRIDOR_FLR_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
233 | CORRIDOR_FLR_6_CEILING_1 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
234 | CORRIDOR_FLR_6_CEILING_2 | 0 | 1782.60 | 293.11 | 15.24 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 28.04 | 8.72 | 0.33 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | RETAIL_1_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_1_FLR_1 | 67.07 | 10.8 | 7.733E-002 | 1.153E-003 | 5.690E-004 | 1.047 | 1.000 | 0.000 | 0.000 | 0.000 |
2 | RETAIL_2_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | RETAIL_2_FLR_1 | 77.67 | 12.5 | 1.623E-002 | 2.089E-004 | 5.690E-004 | 0.190 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | MECH_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | MECH_FLR_1 | 164.24 | 0.0 | 3.573E-002 | 2.175E-004 | 5.690E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
4 | STORAGE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | STORAGE_FLR_1 | 94.76 | 0.0 | 2.484E-002 | 2.622E-004 | 5.690E-004 | 0.238 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | LAUNDRY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LAUNDRY_FLR_1 | 78.04 | 8.4 | 4.990E-002 | 6.394E-004 | 5.690E-004 | 0.581 | 1.000 | 0.000 | 0.000 | 0.000 |
6 | CAFE_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | CAFE_FLR_1 | 188.86 | 142.3 | 0.195 | 1.033E-003 | 5.690E-004 | 0.939 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | LOBBY_FLR_1_INFILTRATION | INFIL_QUARTER_ON_SCH | LOBBY_FLR_1 | 1308.19 | 422.4 | 0.389 | 2.975E-004 | 5.690E-004 | 0.270 | 1.000 | 0.000 | 0.000 | 0.000 |
8 | ROOM_1_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | ROOM_2_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
10 | ROOM_3_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 6.342E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | ROOM_4_MULT19_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 6.344E-003 | 2.586E-004 | 5.690E-004 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 |
12 | ROOM_5_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_5_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | ROOM_6_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_6_FLR_3 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 5.690E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
14 | CORRIDOR_FLR_3_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_3 | 389.40 | 0.0 | 2.749E-002 | 7.058E-005 | 5.690E-004 | 8.337E-002 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | ROOM_1_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_1_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
16 | ROOM_2_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_2_FLR_6 | 39.02 | 1.5 | 2.273E-002 | 5.825E-004 | 2.878E-004 | 0.688 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | ROOM_3_MULT9_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 1.163E-002 | 4.741E-004 | 2.586E-004 | 0.560 | 1.000 | 0.000 | 0.000 | 0.000 |
18 | BANQUET_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | BANQUET_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | DINING_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | DINING_FLR_6 | 331.66 | 249.9 | 5.551E-002 | 1.674E-004 | 1.293E-004 | 0.198 | 1.000 | 0.000 | 0.000 | 0.000 |
20 | KITCHEN_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | KITCHEN_FLR_6 | 103.30 | 22.2 | 4.969E-002 | 4.810E-004 | 2.606E-004 | 0.568 | 1.000 | 0.000 | 0.000 | 0.000 |
21 | CORRIDOR_FLR_6_INFILTRATION | INFIL_QUARTER_ON_SCH | CORRIDOR_FLR_6 | 412.12 | 0.0 | 4.864E-002 | 1.180E-004 | 9.775E-005 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
1 | ROOM_1_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
2 | ROOM_2_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
3 | ROOM_3_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT19_FLR_3 | 24.52 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
4 | ROOM_4_MULT19_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_4_MULT19_FLR_3 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
5 | ROOM_5_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_5_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
6 | ROOM_6_FLR_3 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_6_FLR_3 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
7 | ROOM_1_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_1_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
8 | ROOM_2_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_2_FLR_6 | 39.02 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
9 | ROOM_3_MULT9_FLR_6 SLIDING DOOR VENTILATION | Constant-0.0 | ROOM_3_MULT9_FLR_6 | 24.53 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 26.67 | 40.00 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | RETAIL_1_FLR_1 | Mixing/Well-Stirred |
3 | RETAIL_2_FLR_1 | Mixing/Well-Stirred |
4 | MECH_FLR_1 | Mixing/Well-Stirred |
5 | STORAGE_FLR_1 | Mixing/Well-Stirred |
6 | LAUNDRY_FLR_1 | Mixing/Well-Stirred |
7 | CAFE_FLR_1 | Mixing/Well-Stirred |
8 | LOBBY_FLR_1 | Mixing/Well-Stirred |
9 | ROOM_1_FLR_3 | Mixing/Well-Stirred |
10 | ROOM_2_FLR_3 | Mixing/Well-Stirred |
11 | ROOM_3_MULT19_FLR_3 | Mixing/Well-Stirred |
12 | ROOM_4_MULT19_FLR_3 | Mixing/Well-Stirred |
13 | ROOM_5_FLR_3 | Mixing/Well-Stirred |
14 | ROOM_6_FLR_3 | Mixing/Well-Stirred |
15 | CORRIDOR_FLR_3 | Mixing/Well-Stirred |
16 | ROOM_1_FLR_6 | Mixing/Well-Stirred |
17 | ROOM_2_FLR_6 | Mixing/Well-Stirred |
18 | ROOM_3_MULT9_FLR_6 | Mixing/Well-Stirred |
19 | BANQUET_FLR_6 | Mixing/Well-Stirred |
20 | DINING_FLR_6 | Mixing/Well-Stirred |
21 | KITCHEN_FLR_6 | Mixing/Well-Stirred |
22 | CORRIDOR_FLR_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 33127.78706 | 33127.78706 | 2.52353 | 2.52353 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53444E-002 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
2 | BASEMENT | Heating | 1537.09419 | 1537.09419 | 6.90744E-002 | 0.85413 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -26.20000 | 3.61342E-004 | 1978.83018 | 106.49900 | 0.85413 | 0.00000 |
3 | RETAIL_1_FLR_1 | Cooling | 4173.87094 | 4173.87094 | 0.31802 | 0.31802 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
4 | RETAIL_1_FLR_1 | Heating | 4334.71957 | 4334.71957 | 0.19476 | 0.19476 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 67.07136 | 10.82900 | 7.91874E-002 | 0.00000 |
5 | RETAIL_2_FLR_1 | Cooling | 3004.59470 | 3004.59470 | 0.22891 | 0.22891 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 30.14000 | 1.53444E-002 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
6 | RETAIL_2_FLR_1 | Heating | 1139.06965 | 1139.06965 | 5.11861E-002 | 9.16993E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 77.66889 | 12.54000 | 9.16993E-002 | 0.00000 |
7 | MECH_FLR_1 | Cooling | 2978.85496 | 2978.85496 | 0.22689 | 0.22689 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88200 | 1.53444E-002 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
8 | MECH_FLR_1 | Heating | 1977.31930 | 1977.31930 | 8.88542E-002 | 8.88542E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 164.24319 | 0.00000 | 0.00000 | 0.00000 |
9 | STORAGE_FLR_1 | Cooling | 1269.71363 | 1269.71363 | 9.67119E-002 | 9.67119E-002 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 31.20000 | 1.53444E-002 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
10 | STORAGE_FLR_1 | Heating | 1466.36204 | 1466.36204 | 6.58931E-002 | 6.58931E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 94.75927 | 0.00000 | 5.77430E-002 | 0.00000 |
11 | LAUNDRY_FLR_1 | Cooling | 44709.27482 | 44709.27482 | 3.40593 | 3.40593 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53444E-002 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
12 | LAUNDRY_FLR_1 | Heating | 2652.86849 | 2652.86849 | 0.11920 | 0.11920 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 78.03947 | 8.40000 | 0.00000 | 0.00000 |
13 | CAFE_FLR_1 | Cooling | 17347.91170 | 17347.91170 | 1.32289 | 1.32289 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53444E-002 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
14 | CAFE_FLR_1 | Heating | 11299.71439 | 11299.71439 | 0.50771 | 0.67613 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 188.86188 | 142.30000 | 0.67613 | 0.00000 |
15 | LOBBY_FLR_1 | Cooling | 62319.66773 | 62319.66773 | 4.74929 | 4.74929 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
16 | LOBBY_FLR_1 | Heating | 23271.56552 | 23271.56552 | 1.04573 | 1.89326 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 1308.18612 | 422.43500 | 1.89326 | 0.00000 |
17 | ROOM_1_FLR_3 | Cooling | 11363.33908 | 11363.33908 | 1.16650 | 1.16650 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
18 | ROOM_1_FLR_3 | Heating | 7783.05631 | 7783.05631 | 0.35178 | 0.35178 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
19 | ROOM_2_FLR_3 | Cooling | 11182.73437 | 11182.73437 | 1.14796 | 1.14796 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
20 | ROOM_2_FLR_3 | Heating | 7803.92435 | 7803.92435 | 0.35272 | 0.35272 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
21 | ROOM_3_MULT19_FLR_3 | Cooling | 58204.21536 | 58204.21536 | 5.97439 | 5.97439 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
22 | ROOM_3_MULT19_FLR_3 | Heating | 43867.05829 | 43867.05829 | 1.98280 | 1.98280 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.52384 | 1.50000 | 0.83677 | 0.00000 |
23 | ROOM_4_MULT19_FLR_3 | Cooling | 59259.96990 | 59259.96990 | 6.08324 | 6.08324 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20000 | 1.53444E-002 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
24 | ROOM_4_MULT19_FLR_3 | Heating | 44238.92096 | 44238.92096 | 1.99961 | 1.99961 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 0.83699 | 0.00000 |
25 | ROOM_5_FLR_3 | Cooling | 10192.03640 | 10192.03640 | 1.04626 | 1.04626 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53444E-002 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
26 | ROOM_5_FLR_3 | Heating | 7746.50995 | 7746.50995 | 0.35013 | 0.35013 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 6.17129E-002 | 0.00000 |
27 | ROOM_6_FLR_3 | Cooling | 10133.50916 | 10133.50916 | 1.04025 | 1.04025 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.03433 | 1.53444E-002 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
28 | ROOM_6_FLR_3 | Heating | 7767.28680 | 7767.28680 | 0.35106 | 0.35106 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 6.17056E-002 | 0.00000 |
29 | CORRIDOR_FLR_3 | Cooling | 13670.93135 | 13670.93135 | 1.04126 | 1.18691 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 31.11167 | 1.53444E-002 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
30 | CORRIDOR_FLR_3 | Heating | 11668.50667 | 11668.50667 | 0.52436 | 0.52436 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 389.40468 | 0.00000 | 0.47458 | 0.00000 |
31 | ROOM_1_FLR_6 | Cooling | 2956.84415 | 2956.84415 | 0.30353 | 0.30353 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
32 | ROOM_1_FLR_6 | Heating | 2383.46066 | 2383.46066 | 0.10773 | 0.10773 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.02202 | 1.50000 | 1.54282E-002 | 0.00000 |
33 | ROOM_2_FLR_6 | Cooling | 2908.17047 | 2908.17047 | 0.29854 | 0.29854 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53444E-002 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
34 | ROOM_2_FLR_6 | Heating | 2395.43347 | 2395.43347 | 0.10827 | 0.10827 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 39.01745 | 1.50000 | 1.54264E-002 | 0.00000 |
35 | ROOM_3_MULT9_FLR_6 | Cooling | 11368.10033 | 11368.10033 | 1.16700 | 1.16700 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53444E-002 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
36 | ROOM_3_MULT9_FLR_6 | Heating | 11381.67340 | 11381.67340 | 0.51444 | 0.51444 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 24.53055 | 1.50000 | 9.91178E-002 | 0.00000 |
37 | BANQUET_FLR_6 | Cooling | 27519.07690 | 27519.07690 | 2.09896 | 2.09896 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
38 | BANQUET_FLR_6 | Heating | 7883.26118 | 7883.26118 | 0.35425 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
39 | DINING_FLR_6 | Cooling | 28893.23314 | 28893.23314 | 2.20373 | 2.20373 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20000 | 1.53444E-002 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
40 | DINING_FLR_6 | Heating | 8026.36056 | 8026.36056 | 0.36068 | 1.18734 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 331.65745 | 249.89600 | 1.18734 | 0.00000 |
41 | KITCHEN_FLR_6 | Cooling | 30785.99180 | 30785.99180 | 2.35130 | 2.35130 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.97067 | 1.53444E-002 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
42 | KITCHEN_FLR_6 | Heating | 3049.25248 | 3049.25248 | 0.13700 | 0.36721 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -26.20000 | 3.61342E-004 | 103.30446 | 22.23800 | 0.36721 | 0.00000 |
43 | CORRIDOR_FLR_6 | Cooling | 7967.79763 | 7967.79763 | 0.60688 | 0.60688 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20000 | 1.53444E-002 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
44 | CORRIDOR_FLR_6 | Heating | 8290.83631 | 8290.83631 | 0.37257 | 0.37257 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | -26.20000 | 3.61342E-004 | 412.12471 | 0.00000 | 0.12557 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV WITH REHEAT | Cooling | Sensible | 368603.61 | 21.04062 | 21.04062 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV WITH REHEAT | Heating | Sensible | 377420.61 | 7.62274 | 7.62274 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
3 | FLR_3_DOAS | Cooling | Sensible | 43559.48 | 16.91483 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | FLR_3_DOAS | Heating | Sensible | 101559.87 | 6.11854 | 2.05120 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.52353 |
2 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.59752 |
3 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
4 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.38037 |
5 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
6 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
7 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.37631E-004 |
8 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87541E-004 |
9 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.38037 |
10 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | BASEMENT VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
12 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8488.40573 |
13 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87541E-004 |
14 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 152.09097 |
15 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.31802 |
16 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16071 |
17 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
18 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.17396 |
19 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
20 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
21 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37076E-003 |
22 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17401E-004 |
23 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19476 |
24 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
26 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5313.75922 |
27 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17401E-004 |
28 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 115.17492 |
29 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22891 |
30 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25855 |
31 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
32 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12521 |
33 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68946 |
34 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47362E-003 |
36 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.90808E-005 |
37 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12521 |
38 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | RETAIL_2_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
40 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1768.85803 |
41 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.90808E-005 |
42 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 34.57349 |
43 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.22689 |
44 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.55160 |
45 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
46 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.12411 |
47 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
49 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 6.90722E-004 |
50 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.74743E-005 |
51 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.12411 |
52 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | MECH_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
54 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2601.37898 |
55 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.74743E-005 |
56 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 53.39231 |
57 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.67119E-002 |
58 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.74662 |
59 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
60 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 5.29014E-002 |
61 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
62 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
63 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 5.10303E-004 |
64 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.97183E-005 |
65 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.58931E-002 |
66 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | STORAGE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
68 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 1797.71233 |
69 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.97183E-005 |
70 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 38.96484 |
71 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.40593 |
72 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.74596E-002 |
73 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
74 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86304 |
75 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
76 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
77 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18218E-002 |
78 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65544E-004 |
79 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.86304 |
80 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | LAUNDRY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
82 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12018.93831 |
83 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65544E-004 |
84 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 216.08596 |
85 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32289 |
86 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10879 |
87 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.72362 |
89 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
90 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50226E-003 |
92 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.30025E-004 |
93 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72362 |
94 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | CAFE_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
96 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14937.48390 |
97 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.30025E-004 |
98 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 305.81377 |
99 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.74929 |
100 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20989 |
101 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.59786 |
103 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55971 |
104 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
105 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81522E-003 |
106 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.02782E-004 |
107 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.59786 |
108 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
110 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36335.22510 |
111 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.02782E-004 |
112 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 709.57419 |
113 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16650 |
114 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
115 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16650 |
116 | Fan:OnOff | ROOM_1_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.16650 |
117 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.71950E-004 |
118 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.66783E-004 |
119 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.66783E-004 |
120 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.16650 |
121 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68827E-003 |
122 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70997 |
123 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
124 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
125 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
126 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7782.71931 |
127 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71950E-004 |
128 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.18758 |
129 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14796 |
130 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
131 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.14796 |
132 | Fan:OnOff | ROOM_2_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.14796 |
133 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.72411E-004 |
134 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.61209E-004 |
135 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.61209E-004 |
136 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.14796 |
137 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.69094E-003 |
138 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70996 |
139 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
140 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
141 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
142 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7803.58640 |
143 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72411E-004 |
144 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 177.66257 |
145 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.97439 |
146 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
147 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 5.97439 |
148 | Fan:OnOff | ROOM_3_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 5.97439 |
149 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.69169E-004 |
150 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 1.84840E-003 |
151 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 1.84840E-003 |
152 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 5.97439 |
153 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.62753E-003 |
154 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.71076 |
155 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
156 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
157 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
158 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 43866.13209 |
159 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.69169E-004 |
160 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 998.68693 |
161 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.08324 |
162 | AirTerminal:SingleDuct:Uncontrolled | ROOM_4_MULT19_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 0.83695 |
163 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.08324 |
164 | Fan:OnOff | ROOM_4_MULT19_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 6.08324 |
165 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 9.77384E-004 |
166 | ZoneHVAC:FourPipeFanCoil | ROOM_4_MULT19_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 2.00172E-003 |
167 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 2.00172E-003 |
168 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 6.08324 |
169 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.86349E-003 |
170 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70985 |
171 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
172 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
173 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
174 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 44237.98760 |
175 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.77384E-004 |
176 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1007.15139 |
177 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04626 |
178 | AirTerminal:SingleDuct:Uncontrolled | ROOM_5_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
179 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04626 |
180 | Fan:OnOff | ROOM_5_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.04626 |
181 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.71142E-004 |
182 | ZoneHVAC:FourPipeFanCoil | ROOM_5_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.31073E-004 |
183 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.31073E-004 |
184 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.04626 |
185 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.71229E-003 |
186 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70992 |
187 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
188 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
189 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
190 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7746.17436 |
191 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71142E-004 |
192 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 176.35573 |
193 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.04025 |
194 | AirTerminal:SingleDuct:Uncontrolled | ROOM_6_FLR_3 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 6.17331E-002 |
195 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.04025 |
196 | Fan:OnOff | ROOM_6_FLR_3 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.04025 |
197 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 1.71601E-004 |
198 | ZoneHVAC:FourPipeFanCoil | ROOM_6_FLR_3 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.29291E-004 |
199 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.29291E-004 |
200 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.04025 |
201 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.71366E-003 |
202 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70992 |
203 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
204 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
205 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
206 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 7766.95026 |
207 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71601E-004 |
208 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 176.82864 |
209 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.18691 |
210 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 1.00000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
212 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.64924 |
213 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
214 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
215 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81000E-004 |
216 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29979E-004 |
217 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64924 |
218 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
219 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
220 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14935.37895 |
221 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29979E-004 |
222 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 311.69069 |
223 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.30353 |
224 | AirTerminal:SingleDuct:Uncontrolled | ROOM_1_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
225 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.30353 |
226 | Fan:OnOff | ROOM_1_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.30353 |
227 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.26575E-005 |
228 | ZoneHVAC:FourPipeFanCoil | ROOM_1_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.52612E-005 |
229 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 9.52612E-005 |
230 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.30353 |
231 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68120E-003 |
232 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70999 |
233 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
234 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
235 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
236 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2383.36187 |
237 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.26575E-005 |
238 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.25963 |
239 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.29854 |
240 | AirTerminal:SingleDuct:Uncontrolled | ROOM_2_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 1.54333E-002 |
241 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.29854 |
242 | Fan:OnOff | ROOM_2_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 0.29854 |
243 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 5.29220E-005 |
244 | ZoneHVAC:FourPipeFanCoil | ROOM_2_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 9.37591E-005 |
245 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 9.37591E-005 |
246 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 0.29854 |
247 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.68385E-003 |
248 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70998 |
249 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
250 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
251 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
252 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 2395.33420 |
253 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.29220E-005 |
254 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 54.53215 |
255 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.16700 |
256 | AirTerminal:SingleDuct:Uncontrolled | ROOM_3_MULT9_FLR_6 DIRECT AIR | User-Specified Maximum Air Flow Rate [m3/s] | 9.91128E-002 |
257 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Supply Air Flow Rate [m3/s] | 1.16700 |
258 | Fan:OnOff | ROOM_3_MULT9_FLR_6 FAN COILFAN | Design Size Maximum Flow Rate [m3/s] | 1.16700 |
259 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Hot Water Flow [m3/s] | 2.51456E-004 |
260 | ZoneHVAC:FourPipeFanCoil | ROOM_3_MULT9_FLR_6 FAN COIL | Design Size Maximum Cold Water Flow [m3/s] | 3.76628E-004 |
261 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Water Flow Rate [m3/s] | 3.76628E-004 |
262 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | User-Specified Design Air Flow Rate [m3/s] | 1.16700 |
263 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Humidity Ratio | 8.78779E-003 |
264 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Air Temperature [C] | 21.70975 |
265 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Inlet Water Temperature [C] | 6.70000 |
266 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Temperature [C] | 12.80000 |
267 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Design Size Design Outlet Air Humidity Ratio | 8.50000E-003 |
268 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Rated Capacity [W] | 11381.29480 |
269 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.51456E-004 |
270 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.10579 |
271 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.09896 |
272 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12040 |
273 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
274 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.14813 |
275 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
276 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
277 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16435E-003 |
278 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01831E-004 |
279 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.14813 |
280 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
281 | AirTerminal:SingleDuct:VAV:Reheat | BANQUET_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
282 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13661.37371 |
283 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01831E-004 |
284 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 261.89228 |
285 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.20373 |
286 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11468 |
287 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
288 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.20544 |
289 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
290 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
291 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.32230E-003 |
292 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.11362E-004 |
293 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20544 |
294 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
295 | AirTerminal:SingleDuct:VAV:Reheat | DINING_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
296 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14092.73444 |
297 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.11362E-004 |
298 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 269.47431 |
299 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.35130 |
300 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.70000 |
301 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
302 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28616 |
303 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54700 |
304 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
305 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13805E-002 |
306 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.10075E-004 |
307 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28616 |
308 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
309 | AirTerminal:SingleDuct:VAV:Reheat | KITCHEN_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
310 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9508.32194 |
311 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10075E-004 |
312 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.79533 |
313 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.60688 |
314 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.51746 |
315 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54700 |
316 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33196 |
317 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
318 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
319 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.36284E-004 |
320 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24606E-004 |
321 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37257 |
322 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 16.70000 |
323 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_FLR_6 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
324 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10166.00763 |
325 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24606E-004 |
326 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.35350 |
327 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 11.66202 |
328 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 11.66202 |
329 | AirLoopHVAC | VAV WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.31996 |
330 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 11.66202 |
331 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.04062 |
332 | AirLoopHVAC | VAV WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 21.04062 |
333 | AirLoopHVAC | VAV WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
334 | AirLoopHVAC | VAV WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.55426 |
335 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05082 |
336 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05082 |
337 | AirLoopHVAC | FLR_3_DOAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05082 |
338 | AirLoopHVAC | FLR_3_DOAS | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05120 |
339 | AirLoopHVAC | FLR_3_DOAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05120 |
340 | AirLoopHVAC | FLR_3_DOAS | Adjusted Main Design Air Flow Rate [m3/s] | 2.05120 |
341 | AirLoopHVAC | FLR_3_DOAS | User Heating Air Flow Ratio [] | 0.30000 |
342 | AirLoopHVAC | FLR_3_DOAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
343 | AirLoopHVAC | VAV WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 21.04062 |
344 | AirLoopHVAC | FLR_3_DOAS | Design Supply Air Flow Rate [m3/s] | 2.05120 |
345 | Controller:OutdoorAir | VAV WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.04062 |
346 | HeatExchanger:AirToAir:SensibleAndLatent | VAV WITH REHEAT HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 11.65697 |
347 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 689355.67208 |
348 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.97155E-002 |
349 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 21.04062 |
350 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.28384E-002 |
351 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.98532 |
352 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
353 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 10.90361 |
354 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
355 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 312531.81241 |
356 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.90501E-003 |
357 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3979.37725 |
358 | Fan:VariableVolume | VAV WITH REHEAT_FAN | Design Size Maximum Flow Rate [m3/s] | 21.04062 |
359 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.97155E-002 |
360 | Controller:WaterCoil | VAV WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 2.41531E-005 |
361 | Controller:WaterCoil | VAV WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.90501E-003 |
362 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05120 |
363 | Controller:OutdoorAir | FLR_3_DOAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.05120 |
364 | HeatExchanger:AirToAir:SensibleAndLatent | FLR_3_DOAS HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.05120 |
365 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Coil Load [W] | 87700.73147 |
366 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 2.50823E-003 |
367 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 2.05120 |
368 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.53444E-002 |
369 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Air Temperature [C] | 31.20000 |
370 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.70000 |
371 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Temperature [C] | 10.91216 |
372 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.68318E-003 |
373 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Rated Capacity [W] | 30467.96244 |
374 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.73152E-004 |
375 | Coil:Heating:Water | FLR_3_DOAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 387.93976 |
376 | Fan:ConstantVolume | FLR_3_DOAS_FAN | User-Specified Maximum Flow Rate [m3/s] | 2.05120 |
377 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.50823E-003 |
378 | Controller:WaterCoil | FLR_3_DOAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.89851E-004 |
379 | Controller:WaterCoil | FLR_3_DOAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.73152E-004 |
380 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 2.80278E-002 |
381 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 5361.37596 |
382 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 3.75036E-004 |
383 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 4.50044E-002 |
384 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 3.75036E-004 |
385 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 47.90688 |
386 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 3.75036E-004 |
387 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.37863E-002 |
388 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.65435 |
389 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.37863E-002 |
390 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3522.21575 |
391 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 623988.89402 |
392 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 623988.89000 |
393 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37863E-002 |
394 | PlantLoop | COOLSYS1 | Maximum Loop Flow Rate [m3/s] | 2.80278E-002 |
395 | PlantLoop | COOLSYS1 | Plant Loop Volume [m3] | 3.36334 |
396 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 2.80278E-002 |
397 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 1787.12532 |
398 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Chilled Water Flow Rate [m3/s] | 2.80278E-002 |
399 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Capacity [W] | 979998.80665 |
400 | Chiller:Electric:EIR | COOLSYS1 CHILLER | User-Specified Reference Capacity [W] | 980593.89000 |
401 | Chiller:Electric:EIR | COOLSYS1 CHILLER | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 111.78770 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | BASEMENT VAV BOX REHEAT COIL | 8536.73 |
2 | Coil:Heating:Water | RETAIL_1_FLR_1 VAV BOX REHEAT COIL | 5344.39 |
3 | Coil:Heating:Water | RETAIL_2_FLR_1 VAV BOX REHEAT COIL | 1780.41 |
4 | Coil:Heating:Water | MECH_FLR_1 VAV BOX REHEAT COIL | 2617.36 |
5 | Coil:Heating:Water | STORAGE_FLR_1 VAV BOX REHEAT COIL | 1808.08 |
6 | Coil:Heating:Water | LAUNDRY_FLR_1 VAV BOX REHEAT COIL | 12087.14 |
7 | Coil:Heating:Water | CAFE_FLR_1 VAV BOX REHEAT COIL | 15029.38 |
8 | Coil:Heating:Water | LOBBY_FLR_1 VAV BOX REHEAT COIL | 36572.76 |
9 | Coil:Heating:Water | ROOM_1_FLR_3 FAN COILHEAT COIL | 8398.64 |
10 | Coil:Heating:Water | ROOM_2_FLR_3 FAN COILHEAT COIL | 8421.15 |
11 | Coil:Heating:Water | ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | 47337.73 |
12 | Coil:Heating:Water | ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | 47738.97 |
13 | Coil:Heating:Water | ROOM_5_FLR_3 FAN COILHEAT COIL | 8359.21 |
14 | Coil:Heating:Water | ROOM_6_FLR_3 FAN COILHEAT COIL | 8381.62 |
15 | Coil:Heating:Water | CORRIDOR_FLR_3 VAV BOX REHEAT COIL | 15024.81 |
16 | Coil:Heating:Water | ROOM_1_FLR_6 FAN COILHEAT COIL | 2571.91 |
17 | Coil:Heating:Water | ROOM_2_FLR_6 FAN COILHEAT COIL | 2584.83 |
18 | Coil:Heating:Water | ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | 12281.68 |
19 | Coil:Heating:Water | BANQUET_FLR_6 VAV BOX REHEAT COIL | 13733.31 |
20 | Coil:Heating:Water | DINING_FLR_6 VAV BOX REHEAT COIL | 14167.14 |
21 | Coil:Heating:Water | KITCHEN_FLR_6 VAV BOX REHEAT COIL | 9561.75 |
22 | Coil:Heating:Water | CORRIDOR_FLR_6 VAV BOX REHEAT COIL | 10224.61 |
23 | Coil:Heating:Water | VAV WITH REHEAT_HEATC | 190120.60 |
24 | Coil:Heating:Water | FLR_3_DOAS_HEATC | 18534.39 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | ROOM_1_FLR_3 FAN COILCOOL COIL | 19464.22 | 16297.52 | 3166.70 | 0.84 | 4561.76 | 46.27 |
2 | Coil:Cooling:Water | ROOM_2_FLR_3 FAN COILCOOL COIL | 19164.05 | 16041.51 | 3122.54 | 0.84 | 4486.57 | 45.51 |
3 | Coil:Cooling:Water | ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | 98587.44 | 83108.86 | 15478.58 | 0.84 | 23679.48 | 240.17 |
4 | Coil:Cooling:Water | ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | 104681.70 | 86053.82 | 18627.88 | 0.82 | 23080.72 | 234.10 |
5 | Coil:Cooling:Water | ROOM_5_FLR_3 FAN COILCOOL COIL | 17535.12 | 14643.52 | 2891.61 | 0.84 | 4074.36 | 41.32 |
6 | Coil:Cooling:Water | ROOM_6_FLR_3 FAN COILCOOL COIL | 17438.68 | 14560.82 | 2877.86 | 0.83 | 4049.76 | 41.07 |
7 | Coil:Cooling:Water | ROOM_1_FLR_6 FAN COILCOOL COIL | 5058.32 | 4238.66 | 819.66 | 0.84 | 1188.92 | 12.06 |
8 | Coil:Cooling:Water | ROOM_2_FLR_6 FAN COILCOOL COIL | 4977.43 | 4169.66 | 807.77 | 0.84 | 1168.64 | 11.85 |
9 | Coil:Cooling:Water | ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | 19821.81 | 16420.89 | 3400.92 | 0.83 | 4481.22 | 45.45 |
10 | Coil:Cooling:Water | VAV WITH REHEAT_COOLC | 660474.17 | 418212.32 | 242261.85 | 0.63 | 122760.91 | 1245.11 |
11 | Coil:Cooling:Water | FLR_3_DOAS_COOLC | 67246.26 | 42001.83 | 25244.43 | 0.62 | 10754.43 | 109.08 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER | 4.04 | 13.79 |
Zone Name | # Surfaces | |
1 | BASEMENT | 14 |
2 | RETAIL_1_FLR_1 | 8 |
3 | RETAIL_2_FLR_1 | 8 |
4 | MECH_FLR_1 | 7 |
5 | STORAGE_FLR_1 | 8 |
6 | LAUNDRY_FLR_1 | 8 |
7 | CAFE_FLR_1 | 10 |
8 | LOBBY_FLR_1 | 22 |
9 | ROOM_1_FLR_3 | 9 |
10 | ROOM_2_FLR_3 | 9 |
11 | ROOM_3_MULT19_FLR_3 | 8 |
12 | ROOM_4_MULT19_FLR_3 | 8 |
13 | ROOM_5_FLR_3 | 9 |
14 | ROOM_6_FLR_3 | 9 |
15 | CORRIDOR_FLR_3 | 25 |
16 | ROOM_1_FLR_6 | 9 |
17 | ROOM_2_FLR_6 | 9 |
18 | ROOM_3_MULT9_FLR_6 | 8 |
19 | BANQUET_FLR_6 | 8 |
20 | DINING_FLR_6 | 8 |
21 | KITCHEN_FLR_6 | 12 |
22 | CORRIDOR_FLR_6 | 19 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 0.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 90.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 211.13 | 211.13 | 211.13 | 180.00 | 90.00 | 86.56 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_WEST_CFACTOR | 0.354 | 0.336 | 55.76 | 55.76 | 55.76 | 270.00 | 90.00 | 22.86 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | BASEMENT_FLOOR | 2.705 | 1.632 | 1978.83 | 1978.83 | 1978.83 | 0.00 | 180.00 | 86.56 | 22.86 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | BASEMENT_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | RETAIL_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | BASEMENT_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | BASEMENT_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | BASEMENT_CEILING_4 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_CEILING_5 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
11 | BASEMENT_CEILING_6 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | CAFE_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
12 | BASEMENT_CEILING_7 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 0.00 | 32.99 | 32.99 | 0.00 | LOBBY_FLR_1_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
13 | BASEMENT_CEILING_8 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 219.63 | 219.63 | 219.63 | 90.00 | 0.00 | 14.82 | 14.82 | 0.00 | LOBBY_FLR_1_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
14 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 3957.66 | 3957.66 | 3957.66 | 0.00 | 90.00 | 3957.66 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
15 | RETAIL_1_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.59 | 45.89 | 22.59 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
16 | RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | Window | RETAIL_1_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 23.30 | 23.30 | 23.30 | 180.00 | 90.00 | 10.92 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
17 | RETAIL_1_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
18 | RETAIL_1_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | RETAIL_1_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | RETAIL_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 67.07 | 67.07 | 67.07 | 0.00 | 180.00 | 11.58 | 5.79 | 0.00 | BASEMENT_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
21 | RETAIL_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 67.07 | 67.07 | 67.07 | 180.00 | 0.00 | 11.58 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 7.62E-002 | 0.92 | 4 | ||
22 | RETAIL_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 134.14 | 134.14 | 134.14 | 0.00 | 90.00 | 134.14 | 1.00 | 0.00 | RETAIL_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
23 | RETAIL_2_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 24.62 | 26.57 | 24.62 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | RETAIL_2_FLR_1_WALL_WEST_DOOR | Door | RETAIL_2_FLR_1_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
25 | RETAIL_2_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
26 | RETAIL_2_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 0.00 | 90.00 | 11.58 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | RETAIL_2_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 90.00 | 90.00 | 6.71 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | RETAIL_2_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 77.67 | 77.67 | 77.67 | 0.00 | 180.00 | 11.58 | 6.71 | 0.00 | BASEMENT_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
29 | RETAIL_2_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 77.67 | 77.67 | 77.67 | 180.00 | 0.00 | 11.58 | 6.71 | 0.00 | RETAIL_2_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | RETAIL_2_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 155.34 | 155.34 | 155.34 | 0.00 | 90.00 | 155.34 | 1.00 | 0.00 | RETAIL_2_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
31 | MECH_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | MECH_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | MECH_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 180.00 | 90.00 | 15.85 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | MECH_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | MECH_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 164.24 | 164.24 | 164.24 | 0.00 | 180.00 | 15.85 | 10.36 | 0.00 | BASEMENT_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | MECH_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 164.24 | 164.24 | 164.24 | 180.00 | 0.00 | 15.85 | 10.36 | 0.00 | MECH_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | MECH_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 328.49 | 328.49 | 328.49 | 0.00 | 90.00 | 328.49 | 1.00 | 0.00 | MECH_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | STORAGE_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 28.80 | 36.23 | 28.80 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | Door | STORAGE_FLR_1_WALL_NORTH | CTF - ConductionTransferFunction | OVERHEAD DOOR_CON | 1.761 | 1.761 | 7.43 | 7.43 | 7.43 | 0.00 | 90.00 | 3.05 | 2.44 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | STORAGE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
41 | STORAGE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 180.00 | 90.00 | 9.14 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
42 | STORAGE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | STORAGE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 94.76 | 94.76 | 94.76 | 0.00 | 180.00 | 9.14 | 10.36 | 0.00 | BASEMENT_CEILING_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
44 | STORAGE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 94.76 | 94.76 | 94.76 | 180.00 | 0.00 | 9.14 | 10.36 | 0.00 | STORAGE_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | STORAGE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 189.52 | 189.52 | 189.52 | 0.00 | 90.00 | 189.52 | 1.00 | 0.00 | STORAGE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
46 | LAUNDRY_FLR_1_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | LAUNDRY_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.68 | 67.63 | 65.68 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | LAUNDRY_FLR_1_WALL_EAST_DOOR | Door | LAUNDRY_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
49 | LAUNDRY_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 180.00 | 90.00 | 4.57 | 3.96 | 0.00 | CAFE_FLR_1_WALL_2_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | LAUNDRY_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 270.00 | 90.00 | 17.07 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
51 | LAUNDRY_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 78.04 | 78.04 | 78.04 | 0.00 | 180.00 | 4.57 | 17.07 | 0.00 | BASEMENT_CEILING_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
52 | LAUNDRY_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 78.04 | 78.04 | 78.04 | 180.00 | 0.00 | 4.57 | 17.07 | 0.00 | LAUNDRY_FLR_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
53 | LAUNDRY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 156.08 | 156.08 | 156.08 | 0.00 | 90.00 | 156.08 | 1.00 | 0.00 | LAUNDRY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
54 | CAFE_FLR_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 21.00 | 22.95 | 21.00 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CAFE_FLR_1_WALL_EAST_DOOR | Door | CAFE_FLR_1_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | CAFE_FLR_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 63.61 | 129.23 | 63.61 | 180.00 | 90.00 | 32.61 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CAFE_FLR_1_WALL_SOUTH_WINDOW | Window | CAFE_FLR_1_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 65.62 | 65.62 | 65.62 | 180.00 | 90.00 | 30.75 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
58 | CAFE_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 0.00 | 90.00 | 28.04 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | CAFE_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 18.12 | 18.12 | 18.12 | 0.00 | 90.00 | 4.57 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | CAFE_FLR_1_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | LOBBY_FLR_1_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | CAFE_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 188.86 | 188.86 | 188.86 | 0.00 | 180.00 | 32.61 | 5.79 | 0.00 | BASEMENT_CEILING_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
62 | CAFE_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 188.86 | 188.86 | 188.86 | 180.00 | 0.00 | 32.61 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 3.86E-002 | 0.96 | 4 | ||
63 | CAFE_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 377.72 | 377.72 | 377.72 | 0.00 | 90.00 | 377.72 | 1.00 | 0.00 | CAFE_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
64 | LOBBY_FLR_1_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 209.87 | 213.77 | 209.87 | 0.00 | 90.00 | 53.95 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
66 | LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | Door | LOBBY_FLR_1_WALL_1_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
67 | LOBBY_FLR_1_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 12.08 | 12.08 | 12.08 | 0.00 | 90.00 | 3.05 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
68 | LOBBY_FLR_1_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 82.63 | 167.88 | 82.63 | 180.00 | 90.00 | 42.37 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | LOBBY_FLR_1_WALL_SOUTH_WINDOW | Window | LOBBY_FLR_1_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 85.24 | 85.24 | 85.24 | 180.00 | 90.00 | 39.95 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LOBBY_FLR_1_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | LOBBY_FLR_1_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 45.89 | 45.89 | 45.89 | 180.00 | 90.00 | 11.58 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | LOBBY_FLR_1_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.11 | 111.11 | 111.11 | 180.00 | 90.00 | 28.04 | 3.96 | 0.00 | CAFE_FLR_1_WALL_1_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | LOBBY_FLR_1_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 270.00 | 90.00 | 5.79 | 3.96 | 0.00 | RETAIL_1_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | LOBBY_FLR_1_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.57 | 26.57 | 26.57 | 270.00 | 90.00 | 6.71 | 3.96 | 0.00 | RETAIL_2_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | LOBBY_FLR_1_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 270.00 | 90.00 | 10.36 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | LOBBY_FLR_1_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 62.80 | 62.80 | 62.80 | 0.00 | 90.00 | 15.85 | 3.96 | 0.00 | MECH_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | LOBBY_FLR_1_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.23 | 36.23 | 36.23 | 0.00 | 90.00 | 9.14 | 3.96 | 0.00 | STORAGE_FLR_1_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
78 | LOBBY_FLR_1_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 41.06 | 41.06 | 41.06 | 90.00 | 90.00 | 10.36 | 3.96 | 0.00 | MECH_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | LOBBY_FLR_1_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.95 | 22.95 | 22.95 | 90.00 | 90.00 | 5.79 | 3.96 | 0.00 | CAFE_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | LOBBY_FLR_1_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 67.63 | 67.63 | 67.63 | 90.00 | 90.00 | 17.07 | 3.96 | 0.00 | LAUNDRY_FLR_1_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | LOBBY_FLR_1_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 1088.56 | 1088.56 | 1088.56 | 180.00 | 180.00 | 32.99 | 32.99 | 0.00 | BASEMENT_CEILING_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
82 | LOBBY_FLR_1_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 219.63 | 219.63 | 219.63 | 90.00 | 180.00 | 14.82 | 14.82 | 0.00 | BASEMENT_CEILING_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
83 | LOBBY_FLR_1_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 1062.83 | 1062.83 | 1062.83 | 270.00 | 0.00 | 32.60 | 32.60 | 0.00 | LOBBY_FLR_1_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 10 | ||
84 | LOBBY_FLR_1_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 245.35 | 245.35 | 245.35 | 180.00 | 0.00 | 42.37 | 5.79 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.22E-003 | 1.00 | 4 | ||
85 | LOBBY_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 2616.37 | 2616.37 | 2616.37 | 0.00 | 90.00 | 2616.37 | 1.00 | 0.00 | LOBBY_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | ROOM_1_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | ROOM_1_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | ROOM_1_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | ROOM_1_FLR_3_WALL_WEST_WINDOW | Window | ROOM_1_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | ROOM_1_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | ROOM_1_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | ROOM_1_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
93 | ROOM_1_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
94 | ROOM_1_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
95 | ROOM_2_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | ROOM_2_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
97 | ROOM_2_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | ROOM_2_FLR_3_WALL_WEST_WINDOW | Window | ROOM_2_FLR_3_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 8.58 | 8.58 | 8.58 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | ROOM_2_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | ROOM_2_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | ROOM_2_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | ROOM_2_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | ROOM_2_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT19_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.68 | 3.68 | 3.68 | 180.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | ROOM_3_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
108 | ROOM_3_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | ROOM_3_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.52 | 24.52 | 24.52 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
110 | ROOM_3_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.52 | 24.52 | 24.52 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_3_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
111 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.05 | 49.05 | 49.05 | 0.00 | 90.00 | 49.05 | 1.00 | 0.00 | ROOM_3_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
112 | ROOM_4_MULT19_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 7.47 | 11.15 | 7.47 | 0.00 | 90.00 | 3.66 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_4_MULT19_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 3.68 | 3.68 | 3.68 | 0.00 | 90.00 | 3.02 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
114 | ROOM_4_MULT19_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 180.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | ROOM_4_MULT19_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_4_MULT19_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
117 | ROOM_4_MULT19_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
118 | ROOM_4_MULT19_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 3.66 | 6.71 | 0.00 | ROOM_4_MULT19_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
119 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_4_MULT19_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
120 | ROOM_5_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | ROOM_5_FLR_3_WALL_EAST_WINDOW | Window | ROOM_5_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
122 | ROOM_5_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | ROOM_5_FLR_3_WALL_SOUTH_WINDOW | Window | ROOM_5_FLR_3_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
124 | ROOM_5_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
125 | ROOM_5_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
126 | ROOM_5_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
127 | ROOM_5_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ROOM_5_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
128 | ROOM_5_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_5_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
129 | ROOM_6_FLR_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.34 | 13.94 | 9.34 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | ROOM_6_FLR_3_WALL_NORTH_WINDOW | Window | ROOM_6_FLR_3_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
131 | ROOM_6_FLR_3_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.43 | 26.01 | 17.43 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | ROOM_6_FLR_3_WALL_EAST_WINDOW | Window | ROOM_6_FLR_3_WALL_EAST | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 8.58 | 8.58 | 8.58 | 90.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
133 | ROOM_6_FLR_3_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
134 | ROOM_6_FLR_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_4_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
135 | ROOM_6_FLR_3_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
136 | ROOM_6_FLR_3_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ROOM_6_FLR_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
137 | ROOM_6_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_6_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
138 | CORRIDOR_FLR_3_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
140 | CORRIDOR_FLR_3_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.35 | 6.50 | 4.35 | 0.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 0.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
142 | CORRIDOR_FLR_3_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 4.36 | 6.50 | 4.36 | 180.00 | 90.00 | 2.13 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
143 | CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 2.15 | 2.15 | 2.15 | 180.00 | 90.00 | 1.76 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
144 | CORRIDOR_FLR_3_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.83 | 17.65 | 11.83 | 180.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_3_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.82 | 5.82 | 5.82 | 180.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | CORRIDOR_FLR_3_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 0.00 | 90.00 | 69.50 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | CORRIDOR_FLR_3_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | CORRIDOR_FLR_3_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORRIDOR_FLR_3_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_5_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | CORRIDOR_FLR_3_WALL_4_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_6_FLR_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
151 | CORRIDOR_FLR_3_WALL_3_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 211.82 | 211.82 | 211.82 | 180.00 | 90.00 | 69.49 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_3_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
152 | CORRIDOR_FLR_3_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | CORRIDOR_FLR_3_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_3_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | CORRIDOR_FLR_3_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | CORRIDOR_FLR_3_WALL_4_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_3_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | CORRIDOR_FLR_3_FLOOR_1 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 180.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
157 | CORRIDOR_FLR_3_FLOOR_2 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 240.77 | 240.77 | 240.77 | 270.00 | 180.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_FLOOR_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | CORRIDOR_FLR_3_FLOOR_3 | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 74.32 | 74.32 | 74.32 | 90.00 | 180.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_FLOOR_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
159 | CORRIDOR_FLR_3_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
160 | CORRIDOR_FLR_3_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 240.77 | 240.77 | 240.77 | 90.00 | 0.00 | 3.66 | 65.84 | 0.00 | CORRIDOR_FLR_3_CEILING_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
161 | CORRIDOR_FLR_3_CEILING_3 | Roof | CTF - ConductionTransferFunction | NONRES_FLOOR_CEILING | 0.190 | 0.184 | 74.32 | 74.32 | 74.32 | 90.00 | 0.00 | 8.62 | 8.62 | 0.00 | CORRIDOR_FLR_3_CEILING_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
162 | CORRIDOR_FLR_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 778.81 | 778.81 | 778.81 | 0.00 | 90.00 | 778.81 | 1.00 | 0.00 | CORRIDOR_FLR_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
163 | ROOM_1_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | ROOM_1_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_1_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
165 | ROOM_1_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.54 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
166 | ROOM_1_FLR_6_WALL_WEST_WINDOW | Window | ROOM_1_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
167 | ROOM_1_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
168 | ROOM_1_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.54 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
169 | ROOM_1_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.54 | 0.00 | ROOM_1_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | ROOM_1_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.54 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
171 | ROOM_1_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.04 | 78.04 | 78.04 | 0.00 | 90.00 | 78.04 | 1.00 | 0.00 | ROOM_1_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
172 | ROOM_2_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 0.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | ROOM_2_FLR_6_WALL_NORTH_WINDOW | Window | ROOM_2_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
174 | ROOM_2_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 17.42 | 26.01 | 17.42 | 270.00 | 90.00 | 8.53 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | ROOM_2_FLR_6_WALL_WEST_WINDOW | Window | ROOM_2_FLR_6_WALL_WEST | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 8.59 | 8.59 | 8.59 | 270.00 | 90.00 | 7.04 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
176 | ROOM_2_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 26.01 | 26.01 | 26.01 | 90.00 | 90.00 | 8.53 | 3.05 | 0.00 | ROOM_2_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
177 | ROOM_2_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.94 | 13.94 | 13.94 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ROOM_1_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
178 | ROOM_2_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 39.02 | 39.02 | 39.02 | 0.00 | 180.00 | 4.57 | 8.53 | 0.00 | ROOM_2_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | ROOM_2_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 39.02 | 39.02 | 39.02 | 180.00 | 0.00 | 4.57 | 8.53 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
180 | ROOM_2_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 78.03 | 78.03 | 78.03 | 0.00 | 90.00 | 78.03 | 1.00 | 0.00 | ROOM_2_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
181 | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 13.69 | 20.44 | 13.69 | 180.00 | 90.00 | 6.71 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
182 | ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | Window | ROOM_3_MULT9_FLR_6_WALL_SOUTH | Window5 Detailed Fenestration | RESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 6.75 | 6.75 | 6.75 | 180.00 | 90.00 | 5.53 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
183 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 0.00 | 90.00 | 6.71 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | ROOM_3_MULT9_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 90.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | ROOM_3_MULT9_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | ROOM_3_MULT9_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | ROOM_3_MULT9_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 24.53 | 24.53 | 24.53 | 0.00 | 180.00 | 6.71 | 3.66 | 0.00 | ROOM_3_MULT9_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
187 | ROOM_3_MULT9_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 24.53 | 24.53 | 24.53 | 180.00 | 0.00 | 6.71 | 3.66 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
188 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 49.06 | 49.06 | 49.06 | 0.00 | 90.00 | 49.06 | 1.00 | 0.00 | ROOM_3_MULT9_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
189 | BANQUET_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
190 | BANQUET_FLR_6_WALL_NORTH_WINDOW | Window | BANQUET_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
191 | BANQUET_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
192 | BANQUET_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
193 | BANQUET_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
194 | BANQUET_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | BANQUET_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
195 | BANQUET_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
196 | BANQUET_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | BANQUET_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
197 | DINING_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 65.34 | 97.55 | 65.34 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DINING_FLR_6_WALL_NORTH_WINDOW | Window | DINING_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 32.21 | 32.21 | 32.21 | 0.00 | 90.00 | 26.40 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
199 | DINING_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
200 | DINING_FLR_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 180.00 | 90.00 | 32.00 | 3.05 | 0.00 | DINING_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DINING_FLR_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DINING_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 331.66 | 331.66 | 331.66 | 0.00 | 180.00 | 32.00 | 10.36 | 0.00 | DINING_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
203 | DINING_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 331.66 | 331.66 | 331.66 | 180.00 | 0.00 | 32.00 | 10.36 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
204 | DINING_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 663.31 | 663.31 | 663.31 | 0.00 | 90.00 | 663.31 | 1.00 | 0.00 | DINING_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
205 | KITCHEN_FLR_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 16.76 | 21.37 | 16.76 | 0.00 | 90.00 | 7.01 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
206 | KITCHEN_FLR_6_WALL_NORTH_WINDOW | Window | KITCHEN_FLR_6_WALL_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 0.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
207 | KITCHEN_FLR_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 90.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | KITCHEN_FLR_6_WALL_EAST_WINDOW | Window | KITCHEN_FLR_6_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 90.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
209 | KITCHEN_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 9.33 | 13.94 | 9.33 | 180.00 | 90.00 | 4.57 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | Window | KITCHEN_FLR_6_WALL_1_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 4.60 | 4.60 | 4.60 | 180.00 | 90.00 | 3.77 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
211 | KITCHEN_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 7.43 | 7.43 | 7.43 | 180.00 | 90.00 | 2.44 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_2_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
212 | KITCHEN_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 270.00 | 90.00 | 6.71 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_3_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | KITCHEN_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | KITCHEN_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 103.30 | 103.30 | 103.30 | 180.00 | 180.00 | 10.16 | 10.16 | 0.00 | KITCHEN_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 6 | ||
215 | KITCHEN_FLR_6_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 103.30 | 103.30 | 103.30 | 270.00 | 0.00 | 10.16 | 10.16 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
216 | KITCHEN_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 206.61 | 206.61 | 206.61 | 0.00 | 90.00 | 206.61 | 1.00 | 0.00 | KITCHEN_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
217 | CORRIDOR_FLR_6_WALL_1_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 11.82 | 17.65 | 11.82 | 0.00 | 90.00 | 5.79 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
218 | CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_1_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.83 | 5.83 | 5.83 | 0.00 | 90.00 | 4.78 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
219 | CORRIDOR_FLR_6_WALL_2_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 10.58 | 15.79 | 10.58 | 0.00 | 90.00 | 5.18 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
220 | CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_NORTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 5.21 | 5.21 | 5.21 | 0.00 | 90.00 | 4.27 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
221 | CORRIDOR_FLR_6_WALL_2_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.487 | 0.454 | 34.85 | 52.03 | 34.85 | 180.00 | 90.00 | 17.07 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
222 | CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | Window | CORRIDOR_FLR_6_WALL_2_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.36_SHGC_0.4 | N/A | 2.045 | No | 17.18 | 17.18 | 17.18 | 180.00 | 90.00 | 14.08 | 1.22 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
223 | CORRIDOR_FLR_6_WALL_3_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 97.55 | 97.55 | 97.55 | 0.00 | 90.00 | 32.00 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
224 | CORRIDOR_FLR_6_WALL_4_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 104.98 | 104.98 | 104.98 | 0.00 | 90.00 | 34.44 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_4_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
225 | CORRIDOR_FLR_6_WALL_1_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 183.95 | 183.95 | 183.95 | 180.00 | 90.00 | 60.35 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
226 | CORRIDOR_FLR_6_WALL_1_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 11.15 | 11.15 | 11.15 | 270.00 | 90.00 | 3.66 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
227 | CORRIDOR_FLR_6_WALL_2_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.88 | 40.88 | 40.88 | 270.00 | 90.00 | 13.41 | 3.05 | 0.00 | CORRIDOR_FLR_6_WALL_2_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
228 | CORRIDOR_FLR_6_WALL_3_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 270.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
229 | CORRIDOR_FLR_6_WALL_1_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | BANQUET_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
230 | CORRIDOR_FLR_6_WALL_2_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 31.59 | 31.59 | 31.59 | 90.00 | 90.00 | 10.36 | 3.05 | 0.00 | DINING_FLR_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
231 | CORRIDOR_FLR_6_WALL_3_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.44 | 20.44 | 20.44 | 90.00 | 90.00 | 6.71 | 3.05 | 0.00 | KITCHEN_FLR_6_WALL_1_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
232 | CORRIDOR_FLR_6_FLOOR | Floor | CTF - ConductionTransferFunction | NONRES_FLOOR | 0.190 | 0.182 | 412.12 | 412.12 | 412.12 | 180.00 | 180.00 | 20.30 | 20.30 | 0.00 | CORRIDOR_FLR_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
233 | CORRIDOR_FLR_6_CEILING_1 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 244.71 | 244.71 | 244.71 | 90.00 | 0.00 | 15.64 | 15.64 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
234 | CORRIDOR_FLR_6_CEILING_2 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 167.42 | 167.42 | 167.42 | 270.00 | 0.00 | 12.94 | 12.94 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 6 | ||
235 | CORRIDOR_FLR_6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 824.25 | 824.25 | 824.25 | 0.00 | 90.00 | 824.25 | 1.00 | 0.00 | CORRIDOR_FLR_6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.7393027413E-002 | 2.3234060807E-002 | Pass | Pass | 2.6331764543E-003 | 4.2829779892E-003 | Pass | Pass |
2 | RETAIL_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.6171964908E-003 | 1.3269898385E-003 | Pass | Pass | 6.4645306245E-002 | 0.1590645628 | Pass | Pass |
3 | RETAIL_2_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.8476345750E-002 | 2.7403354027E-002 | Pass | Pass | 1.5421273192E-002 | 4.1904222774E-002 | Pass | Pass |
4 | MECH_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.7475281993E-003 | 8.2834376666E-003 | Pass | Pass | 5.0228019975E-002 | 0.1020338880 | Pass | Pass |
5 | STORAGE_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3505048007E-004 | 3.3669312710E-004 | Pass | Pass | 4.9974632627E-002 | 0.1042339550 | Pass | Pass |
6 | LAUNDRY_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0019399150E-002 | 0.2148016732 | Pass | Pass | 1.8347638449E-002 | 4.9630217224E-002 | Pass | Pass |
7 | CAFE_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.8223888823E-003 | 2.7857995740E-002 | Pass | Pass | 0.2108999158 | 1.0981777970 | Pass | Pass |
8 | LOBBY_FLR_1 | RunPeriod: RUNPERIOD 1 | 2.9317544010E-002 | 4.5346566284E-002 | Pass | Pass | 1.3228464595E-002 | 3.7356050678E-002 | Pass | Pass |
9 | ROOM_1_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1875860495E-002 | 0.3105356337 | Pass | Pass | 8.7027573801E-002 | 0.2571168167 | Pass | Pass |
10 | ROOM_2_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.2099685243E-002 | 0.3156816002 | Pass | Pass | 8.5680336424E-002 | 0.2578971349 | Pass | Pass |
11 | ROOM_3_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 2.8807686403E-002 | 3.7225977394E-002 | Pass | Pass | 6.4834778436E-002 | 0.2414985788 | Pass | Pass |
12 | ROOM_4_MULT19_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.0488434991E-002 | 0.1027047291 | Pass | Pass | 1.4321999385 | 12.6332230957 | Pass | Pass |
13 | ROOM_5_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1635121911E-002 | 0.3067302927 | Pass | Pass | 8.4635125999E-002 | 0.2639385937 | Pass | Pass |
14 | ROOM_6_FLR_3 | RunPeriod: RUNPERIOD 1 | 9.1899496952E-002 | 0.3113879770 | Pass | Pass | 8.6013527913E-002 | 0.2697864627 | Pass | Pass |
15 | CORRIDOR_FLR_3 | RunPeriod: RUNPERIOD 1 | 3.4551233280E-004 | 2.6746084505E-004 | Pass | Pass | 1.7540275479E-002 | 2.0958164390E-002 | Pass | Pass |
16 | ROOM_1_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2736384503E-002 | 0.3353325285 | Pass | Pass | 0.2147452162 | 1.0312557186 | Pass | Pass |
17 | ROOM_2_FLR_6 | RunPeriod: RUNPERIOD 1 | 9.2737041672E-002 | 0.3389844764 | Pass | Pass | 0.2231344934 | 0.9088745984 | Pass | Pass |
18 | ROOM_3_MULT9_FLR_6 | RunPeriod: RUNPERIOD 1 | 7.9221894776E-002 | 0.2617012574 | Pass | Pass | 7.8764185601E-002 | 0.2054394730 | Pass | Pass |
19 | BANQUET_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.0007703724E-002 | 7.6781764080E-002 | Pass | Pass | 9.4240895535E-003 | 2.8596650068E-002 | Pass | Pass |
20 | DINING_FLR_6 | RunPeriod: RUNPERIOD 1 | 2.9186385208E-002 | 6.3794263286E-002 | Pass | Pass | 1.1273518104E-002 | 3.6837140694E-002 | Pass | Pass |
21 | KITCHEN_FLR_6 | RunPeriod: RUNPERIOD 1 | 4.3501096184E-002 | 0.1044549376 | Pass | Pass | 2.0613787266E-002 | 3.8757885770E-002 | Pass | Pass |
22 | CORRIDOR_FLR_6 | RunPeriod: RUNPERIOD 1 | 6.3246130702E-004 | 5.0115342717E-004 | Pass | Pass | 4.4479083091E-002 | 7.1886335572E-002 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 45.89 | 22.59 | 180.00 | 90.00 | S |
RETAIL_1_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 22.95 | 270.00 | 90.00 | W |
RETAIL_1_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 67.07 | 67.07 | 180.00 | 0.00 | |
RETAIL_2_FLR_1_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.57 | 24.62 | 270.00 | 90.00 | W |
MECH_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 62.80 | 62.80 | 0.00 | 90.00 | N |
STORAGE_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 36.23 | 28.80 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 18.12 | 18.12 | 0.00 | 90.00 | N |
LAUNDRY_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 67.63 | 65.68 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 22.95 | 21.00 | 90.00 | 90.00 | E |
CAFE_FLR_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 129.23 | 63.61 | 180.00 | 90.00 | S |
CAFE_FLR_1_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 188.86 | 188.86 | 180.00 | 0.00 | |
LOBBY_FLR_1_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 213.77 | 209.87 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 12.08 | 12.08 | 0.00 | 90.00 | N |
LOBBY_FLR_1_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 167.88 | 82.63 | 180.00 | 90.00 | S |
LOBBY_FLR_1_WALL_1_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 41.06 | 41.06 | 270.00 | 90.00 | W |
LOBBY_FLR_1_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 245.35 | 245.35 | 180.00 | 0.00 | |
ROOM_1_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_1_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 270.00 | 90.00 | W |
ROOM_2_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_2_FLR_3_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 270.00 | 90.00 | W |
ROOM_3_MULT19_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.14 | 567.63 | 180.00 | 90.00 | S |
ROOM_4_MULT19_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 847.37 | 567.77 | 0.00 | 90.00 | N |
ROOM_5_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.06 | 69.73 | 90.00 | 90.00 | E |
ROOM_5_FLR_3_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 180.00 | 90.00 | S |
ROOM_6_FLR_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 55.74 | 37.35 | 0.00 | 90.00 | N |
ROOM_6_FLR_3_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 104.05 | 69.71 | 90.00 | 90.00 | E |
CORRIDOR_FLR_3_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 0.00 | 90.00 | N |
CORRIDOR_FLR_3_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.02 | 17.44 | 180.00 | 90.00 | S |
CORRIDOR_FLR_3_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 70.60 | 47.31 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
ROOM_1_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_1_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_2_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 0.00 | 90.00 | N |
ROOM_2_FLR_6_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 26.01 | 17.42 | 270.00 | 90.00 | W |
ROOM_2_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 39.02 | 39.02 | 180.00 | 0.00 | |
ROOM_3_MULT9_FLR_6_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 183.96 | 123.22 | 180.00 | 90.00 | S |
ROOM_3_MULT9_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 220.77 | 220.77 | 180.00 | 0.00 | |
BANQUET_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
BANQUET_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
DINING_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 97.55 | 65.34 | 0.00 | 90.00 | N |
DINING_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 331.66 | 331.66 | 180.00 | 0.00 | |
KITCHEN_FLR_6_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 21.37 | 16.76 | 0.00 | 90.00 | N |
KITCHEN_FLR_6_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 90.00 | 90.00 | E |
KITCHEN_FLR_6_WALL_1_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 13.94 | 9.33 | 180.00 | 90.00 | S |
KITCHEN_FLR_6_CEILING | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 103.30 | 103.30 | 270.00 | 0.00 | |
CORRIDOR_FLR_6_WALL_1_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 17.65 | 11.82 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_NORTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 15.79 | 10.58 | 0.00 | 90.00 | N |
CORRIDOR_FLR_6_WALL_2_SOUTH | NONRES_EXT_WALL | 0.30 | 0.454 | 0.487 | 52.03 | 34.85 | 180.00 | 90.00 | S |
CORRIDOR_FLR_6_CEILING_1 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 244.71 | 244.71 | 90.00 | 0.00 | |
CORRIDOR_FLR_6_CEILING_2 | NONRES_ROOF | 0.23 | 0.182 | 0.186 | 167.42 | 167.42 | 270.00 | 0.00 | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.354 | 211.13 | 211.13 | 0.00 | 90.00 | N | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.354 | 55.76 | 55.76 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.354 | 211.13 | 211.13 | 180.00 | 90.00 | S | |
BASEMENT_WALL_WEST | BASEMENT_WALL_WEST_CFACTOR | 1.00 | 0.354 | 55.76 | 55.76 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 23.30 | 0.00 | 0.00 | 23.30 | 23.30 | 2.045 | 0.394 | 0.441 | No | RETAIL_1_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
CAFE_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 65.62 | 0.00 | 0.00 | 65.62 | 65.62 | 2.045 | 0.394 | 0.441 | No | CAFE_FLR_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
LOBBY_FLR_1_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 85.24 | 0.00 | 0.00 | 85.24 | 85.24 | 2.045 | 0.394 | 0.441 | No | LOBBY_FLR_1_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.045 | 0.394 | 0.441 | No | ROOM_1_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.045 | 0.394 | 0.441 | No | ROOM_1_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.045 | 0.394 | 0.441 | No | ROOM_2_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_3_WALL_WEST_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.045 | 0.394 | 0.441 | No | ROOM_2_FLR_3_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.51 | 2.045 | 0.394 | 0.441 | No | ROOM_3_MULT19_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 3.68 | 0.00 | 0.00 | 3.68 | 279.60 | 2.045 | 0.394 | 0.441 | No | ROOM_4_MULT19_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_5_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.045 | 0.394 | 0.441 | No | ROOM_5_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.045 | 0.394 | 0.441 | No | ROOM_5_FLR_3_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_6_FLR_3_WALL_NORTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 18.39 | 2.045 | 0.394 | 0.441 | No | ROOM_6_FLR_3_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_6_FLR_3_WALL_EAST_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 8.58 | 0.00 | 0.00 | 8.58 | 34.33 | 2.045 | 0.394 | 0.441 | No | ROOM_6_FLR_3_WALL_EAST | 90.00 | 90.00 | E | ||
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.59 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 2.15 | 0.00 | 0.00 | 2.15 | 8.58 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.82 | 0.00 | 0.00 | 5.82 | 23.29 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_3_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.441 | No | ROOM_1_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
ROOM_1_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.045 | 0.394 | 0.441 | No | ROOM_1_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_2_FLR_6_WALL_NORTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.441 | No | ROOM_2_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
ROOM_2_FLR_6_WALL_WEST_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 8.59 | 0.00 | 0.00 | 8.59 | 8.59 | 2.045 | 0.394 | 0.441 | No | ROOM_2_FLR_6_WALL_WEST | 270.00 | 90.00 | W | ||
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | RESWINDOW_U_0.36_SHGC_0.4 | 6.75 | 0.00 | 0.00 | 6.75 | 60.74 | 2.045 | 0.394 | 0.441 | No | ROOM_3_MULT9_FLR_6_WALL_SOUTH | 180.00 | 90.00 | S | ||
BANQUET_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.441 | No | BANQUET_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
DINING_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 32.21 | 0.00 | 0.00 | 32.21 | 32.21 | 2.045 | 0.394 | 0.441 | No | DINING_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.441 | No | KITCHEN_FLR_6_WALL_NORTH | 0.00 | 90.00 | N | ||
KITCHEN_FLR_6_WALL_EAST_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.441 | No | KITCHEN_FLR_6_WALL_EAST | 90.00 | 90.00 | E | ||
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 4.60 | 0.00 | 0.00 | 4.60 | 4.60 | 2.045 | 0.394 | 0.441 | No | KITCHEN_FLR_6_WALL_1_SOUTH | 180.00 | 90.00 | S | ||
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.83 | 0.00 | 0.00 | 5.83 | 5.83 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_6_WALL_1_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 5.21 | 0.00 | 0.00 | 5.21 | 5.21 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_6_WALL_2_NORTH | 0.00 | 90.00 | N | ||
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | NONRESWINDOW_U_0.36_SHGC_0.4 | 17.18 | 0.00 | 0.00 | 17.18 | 17.18 | 2.045 | 0.394 | 0.441 | No | CORRIDOR_FLR_6_WALL_2_SOUTH | 180.00 | 90.00 | S | ||
Total or Average | 1214.08 | 2.045 | 0.394 | 0.441 | ||||||||||||
North Total or Average | 432.93 | 2.045 | 0.394 | 0.441 | ||||||||||||
Non-North Total or Average | 781.15 | 2.045 | 0.394 | 0.441 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
RETAIL_2_FLR_1_WALL_WEST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | RETAIL_2_FLR_1_WALL_WEST |
STORAGE_FLR_1_WALL_NORTH_ROLLDOOR | OVERHEAD DOOR_CON | 1.394 | 1.761 | 7.43 | STORAGE_FLR_1_WALL_NORTH |
LAUNDRY_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LAUNDRY_FLR_1_WALL_EAST |
CAFE_FLR_1_WALL_EAST_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | CAFE_FLR_1_WALL_EAST |
LOBBY_FLR_1_WALL_1_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
LOBBY_FLR_1_WALL_1_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | LOBBY_FLR_1_WALL_1_NORTH |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
RETAIL_1_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CAFE_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LOBBY_FLR_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_3_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_5_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
ROOM_5_FLR_3_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_6_FLR_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_6_FLR_3_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
ROOM_1_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_2_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_2_FLR_6_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
BANQUET_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DINING_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
KITCHEN_FLR_6_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 8.5035 | 1978.83 | 16826.96 | LightsWired | BLDG_LIGHT_OFFICE_BSMT_SCH | 52.48 | 168.00 | 52.43 | 0.0000 | Y | 165.59 |
RETAIL_1_FLR_1_LIGHTS | RETAIL_1_FLR_1 | 11.4097 | 67.07 | 765.27 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 8.42 |
RETAIL_2_FLR_1_LIGHTS | RETAIL_2_FLR_1 | 11.4097 | 77.67 | 886.18 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 9.75 |
MECH_FLR_1_LIGHTS | MECH_FLR_1 | 10.2257 | 164.24 | 1679.50 | LightsWired | BLDG_LIGHT_MECHANIC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 18.48 |
STORAGE_FLR_1_LIGHTS | STORAGE_FLR_1 | 4.9514 | 94.76 | 469.19 | LightsWired | BLDG_LIGHT_STORAGE_SCH | 26.12 | 168.00 | 26.09 | 0.0000 | Y | 2.30 |
LAUNDRY_FLR_1_LIGHTS | LAUNDRY_FLR_1 | 4.6285 | 78.04 | 361.20 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 3.98 |
CAFE_FLR_1_LIGHTS | CAFE_FLR_1 | 7.6424 | 188.86 | 1443.35 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 39.39 | 0.0000 | Y | 10.67 |
LOBBY_FLR_1_LIGHTS | LOBBY_FLR_1 | 11.4097 | 1308.19 | 14926.07 | LightsWired | BLDG_LIGHT_SCH | 58.69 | 168.00 | 55.38 | 0.0000 | Y | 155.17 |
ROOM_1_FLR_3_LIGHTS | ROOM_1_FLR_3 | 8.2882 | 156.09 | 1293.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
ROOM_2_FLR_3_LIGHTS | ROOM_2_FLR_3 | 8.2882 | 156.07 | 1293.54 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
ROOM_3_MULT19_FLR_3_LIGHTS | ROOM_3_MULT19_FLR_3 | 8.2882 | 1863.81 | 15447.67 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 123.65 |
ROOM_4_MULT19_FLR_3_LIGHTS | ROOM_4_MULT19_FLR_3 | 8.2882 | 1864.32 | 15451.89 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 123.68 |
ROOM_5_FLR_3_LIGHTS | ROOM_5_FLR_3 | 8.2882 | 156.09 | 1293.69 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
ROOM_6_FLR_3_LIGHTS | ROOM_6_FLR_3 | 8.2882 | 156.07 | 1293.54 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 10.35 |
CORRIDOR_FLR_3_LIGHTS | CORRIDOR_FLR_3 | 7.1042 | 1557.62 | 11065.61 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 66.04 |
ROOM_1_FLR_6_LIGHTS | ROOM_1_FLR_6 | 8.2882 | 39.02 | 323.42 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.59 |
ROOM_2_FLR_6_LIGHTS | ROOM_2_FLR_6 | 8.2882 | 39.02 | 323.38 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 2.59 |
ROOM_3_MULT9_FLR_6_LIGHTS | ROOM_3_MULT9_FLR_6 | 8.2882 | 220.77 | 1829.83 | LightsWired | BLDG_LIGHT_GUESTROOM_SCH | 42.59 | 168.00 | 42.64 | 0.0000 | Y | 14.65 |
BANQUET_FLR_6_LIGHTS | BANQUET_FLR_6 | 7.6424 | 331.66 | 2534.65 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 49.22 | 0.0000 | Y | 23.42 |
DINING_FLR_6_LIGHTS | DINING_FLR_6 | 7.6424 | 331.66 | 2534.65 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 49.22 | 0.0000 | Y | 23.42 |
KITCHEN_FLR_6_LIGHTS | KITCHEN_FLR_6 | 11.4097 | 103.30 | 1178.68 | LightsWired | BLDG_LIGHT_MISC_SCH | 58.69 | 168.00 | 58.63 | 0.0000 | Y | 12.97 |
CORRIDOR_FLR_6_LIGHTS | CORRIDOR_FLR_6 | 7.1042 | 412.12 | 2927.81 | LightsWired | BLDG_LIGHT_CORRIDOR_SCH | 31.83 | 168.00 | 31.79 | 0.0000 | Y | 17.47 |
Interior Lighting Total | 8.4749 | 11345.29 | 96149.78 | 488.58 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
CAFE_FLR_1_DAYLREFPT1 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1443.35 | 562.91 |
CAFE_FLR_1_DAYLREFPT2 | CAFE_FLR_1 | CAFE_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1443.35 | 562.91 |
LOBBY_FLR_1_DAYLREFPT1 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14926.07 | 1044.82 |
LOBBY_FLR_1_DAYLREFPT2 | LOBBY_FLR_1 | LOBBY_FLR_1_DAYLCTRL | SplitFlux | Stepped | 0.07 | 14926.07 | 1044.82 |
BANQUET_FLR_6_DAYLREFPT1 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
BANQUET_FLR_6_DAYLREFPT2 | BANQUET_FLR_6 | BANQUET_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
DINING_FLR_6_DAYLREFPT1 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
DINING_FLR_6_DAYLREFPT2 | DINING_FLR_6 | DINING_FLR_6_DAYLCTRL | SplitFlux | Stepped | 0.20 | 2534.65 | 506.93 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR FACADE LIGHTING | 11632.50 | AstronomicalClock | - | 83.63 | 83.63 | 182.61 | |
Exterior Lighting Total | 11632.50 | 182.61 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 623988.89 | 0.80 | ||
COOLSYS1 CHILLER | Chiller:Electric:EIR | 980593.89 | 2.96 | 4.04 | 13.79 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
ROOM_1_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12824.89 | 19464.22 | 16297.52 | 3166.70 | 0.84 | - | 4561.76 | 46.27 |
ROOM_2_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 12629.99 | 19164.05 | 16041.51 | 3122.54 | 0.84 | - | 4486.57 | 45.51 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 64631.03 | 98587.44 | 83108.86 | 15478.58 | 0.84 | - | 23679.48 | 240.17 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 69991.72 | 104681.70 | 86053.82 | 18627.88 | 0.82 | - | 23080.72 | 234.10 |
ROOM_5_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11576.25 | 17535.12 | 14643.52 | 2891.61 | 0.84 | - | 4074.36 | 41.32 |
ROOM_6_FLR_3 FAN COILCOOL COIL | Coil:Cooling:Water | 11513.94 | 17438.68 | 14560.82 | 2877.86 | 0.83 | - | 4049.76 | 41.07 |
ROOM_1_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3330.89 | 5058.32 | 4238.66 | 819.66 | 0.84 | - | 1188.92 | 12.06 |
ROOM_2_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 3278.36 | 4977.43 | 4169.66 | 807.77 | 0.84 | - | 1168.64 | 11.85 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | Coil:Cooling:Water | 13169.13 | 19821.81 | 16420.89 | 3400.92 | 0.83 | - | 4481.22 | 45.45 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | 689355.67 | 660474.17 | 418212.32 | 242261.85 | 0.63 | - | 122760.91 | 1245.11 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | 87700.73 | 67246.26 | 42001.83 | 25244.43 | 0.62 | - | 10754.43 | 109.08 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
BASEMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 8488.41 | 8536.73 | - |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5313.76 | 5344.39 | - |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1768.86 | 1780.41 | - |
MECH_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2601.38 | 2617.36 | - |
STORAGE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 1797.71 | 1808.08 | - |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12018.94 | 12087.14 | - |
CAFE_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14937.48 | 15029.38 | - |
LOBBY_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36335.23 | 36572.76 | - |
ROOM_1_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7782.72 | 8398.64 | - |
ROOM_2_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7803.59 | 8421.15 | - |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 43866.13 | 47337.73 | - |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 44237.99 | 47738.97 | - |
ROOM_5_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7746.17 | 8359.21 | - |
ROOM_6_FLR_3 FAN COILHEAT COIL | Coil:Heating:Water | 7766.95 | 8381.62 | - |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 14935.38 | 15024.81 | - |
ROOM_1_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2383.36 | 2571.91 | - |
ROOM_2_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 2395.33 | 2584.83 | - |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | Coil:Heating:Water | 11381.29 | 12281.68 | - |
BANQUET_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 13661.37 | 13733.31 | - |
DINING_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 14092.73 | 14167.14 | - |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 9508.32 | 9561.75 | - |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | Coil:Heating:Water | 10166.01 | 10224.61 | - |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | 312531.81 | 190120.60 | - |
FLR_3_DOAS_HEATC | Coil:Heating:Water | 30467.96 | 18534.39 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
LAUNDRY_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 0.24 | 76.61 | 324.68 | 1.00 | 2.78 | General | ||
LOBBY_FLR_1 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.24 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 820.79 | 703.64 | 1.00 | 1.16 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.15 | 807.74 | 703.64 | 1.00 | 1.16 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 5.97 | 4203.80 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 6.08 | 4280.39 | 703.64 | 1.00 | 0.96 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.05 | 736.19 | 703.64 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 |
ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.04 | 731.96 | 703.64 | 1.00 | 1.19 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 |
ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 213.58 | 703.64 | 1.00 | 1.70 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 0.30 | 210.06 | 703.64 | 1.00 | 1.72 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 |
ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 0.39 | 270.90 | 1.17 | 821.14 | 703.64 | 1.00 | 1.16 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 |
BANQUET_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
DINING_FLR_6 DUMMY EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.87 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
KITCHEN_FLR_6 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 125.00 | 1.89 | 612.92 | 324.68 | 1.00 | 1.48 | General | ||
VAV WITH REHEAT_FAN | Fan:VariableVolume | 0.62 | 1389.42 | 21.04 | 47144.44 | 2240.64 | 1.00 | 1.11 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
FLR_3_DOAS_FAN | Fan:ConstantVolume | 0.58 | 622.50 | 2.05 | 2194.88 | 1070.05 | 1.00 | 1.30 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 134283.83 | 0.028028 | 5361.38 | 191287.51 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000375 | 47.91 | 127739.32 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.013786 | 3522.22 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 44761.28 | 0.028028 | 1787.13 | 63762.50 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHW BOOSTER WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 1.00 | 1.24 | 1.15 |
SWH LAUNDRY | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.54 | 0.50 |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 2.27 | 175842.60 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 33127.79 | 33127.79 | 16.74 | 2.524 | 2.524 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00923 | 26.87 | 0.01534 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4173.87 | 4173.87 | 62.23 | 0.318 | 0.318 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00943 | 30.85 | 0.01534 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 3004.59 | 3004.59 | 38.68 | 0.229 | 0.229 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00954 | 30.14 | 0.01534 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 44709.27 | 44709.27 | 572.91 | 3.406 | 3.406 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00857 | 31.20 | 0.01534 | 0.000 | 0.00 |
CAFE_FLR_1 | 17347.91 | 17347.91 | 91.86 | 1.323 | 1.323 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 23.99 | 0.01052 | 30.85 | 0.01534 | 0.676 | 0.00 |
LOBBY_FLR_1 | 62319.67 | 62319.67 | 47.64 | 4.749 | 4.749 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 23.99 | 0.01013 | 30.93 | 0.01534 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 11363.34 | 11363.34 | 291.20 | 1.166 | 1.166 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 11182.73 | 11182.73 | 286.61 | 1.148 | 1.148 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00869 | 29.36 | 0.01534 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 58204.22 | 58204.22 | 2373.37 | 5.974 | 5.974 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00863 | 30.93 | 0.01534 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 59259.97 | 59259.97 | 2415.76 | 6.083 | 6.083 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00886 | 31.20 | 0.01534 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 10192.04 | 10192.04 | 261.19 | 1.046 | 1.046 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.11 | 21.11 | 0.00871 | 25.37 | 0.01534 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 10133.51 | 10133.51 | 259.72 | 1.040 | 1.040 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 21.11 | 21.11 | 0.00871 | 25.03 | 0.01534 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2956.84 | 2956.84 | 75.77 | 0.304 | 0.304 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00868 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2908.17 | 2908.17 | 74.54 | 0.299 | 0.299 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 21.11 | 21.11 | 0.00868 | 29.36 | 0.01534 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11368.10 | 11368.10 | 463.43 | 1.167 | 1.167 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 21.11 | 21.11 | 0.00879 | 30.93 | 0.01534 | 0.099 | 0.00 |
BANQUET_FLR_6 | 27519.08 | 27519.08 | 82.97 | 2.099 | 2.099 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01058 | 31.20 | 0.01534 | 1.187 | 0.00 |
DINING_FLR_6 | 28893.23 | 28893.23 | 87.12 | 2.204 | 2.204 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 23.98 | 0.01048 | 31.20 | 0.01534 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 30785.99 | 30785.99 | 298.01 | 2.351 | 2.351 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 23.97 | 0.01003 | 25.97 | 0.01534 | 0.367 | 0.00 |
MECH_FLR_1 | 2978.85 | 2978.85 | 18.14 | 0.227 | 0.227 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00874 | 30.88 | 0.01534 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1269.71 | 1269.71 | 13.40 | 0.097 | 0.097 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00889 | 31.20 | 0.01534 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 13670.93 | 13670.93 | 35.11 | 1.041 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00867 | 31.11 | 0.01534 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 7967.80 | 7967.80 | 19.33 | 0.607 | 0.607 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00863 | 31.20 | 0.01534 | 0.126 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 1537.09 | 1537.09 | 0.78 | 0.069 | 0.854 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -26.20 | 0.00036 | 0.854 | 0.00 |
RETAIL_1_FLR_1 | 4334.72 | 4334.72 | 64.63 | 0.195 | 0.195 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00720 | -26.20 | 0.00036 | 0.079 | 0.00 |
RETAIL_2_FLR_1 | 1139.07 | 1139.07 | 14.67 | 0.051 | 0.092 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00734 | -26.20 | 0.00036 | 0.092 | 0.00 |
LAUNDRY_FLR_1 | 2652.87 | 2652.87 | 33.99 | 0.119 | 0.119 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00716 | -26.20 | 0.00036 | 0.000 | 0.00 |
CAFE_FLR_1 | 11299.71 | 11299.71 | 59.83 | 0.508 | 0.676 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00722 | -26.20 | 0.00036 | 0.676 | 0.00 |
LOBBY_FLR_1 | 23271.57 | 23271.57 | 17.79 | 1.046 | 1.893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00724 | -26.20 | 0.00036 | 1.893 | 0.00 |
ROOM_1_FLR_3 | 7783.06 | 7783.06 | 199.45 | 0.352 | 0.352 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_2_FLR_3 | 7803.92 | 7803.92 | 200.01 | 0.353 | 0.353 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_3_MULT19_FLR_3 | 43867.06 | 43867.06 | 1788.75 | 1.983 | 1.983 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00749 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_4_MULT19_FLR_3 | 44238.92 | 44238.92 | 1803.42 | 2.000 | 2.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00749 | -26.20 | 0.00036 | 0.837 | 0.00 |
ROOM_5_FLR_3 | 7746.51 | 7746.51 | 198.52 | 0.350 | 0.350 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00745 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_6_FLR_3 | 7767.29 | 7767.29 | 199.07 | 0.351 | 0.351 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00746 | -26.20 | 0.00036 | 0.062 | 0.00 |
ROOM_1_FLR_6 | 2383.46 | 2383.46 | 61.08 | 0.108 | 0.108 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_2_FLR_6 | 2395.43 | 2395.43 | 61.39 | 0.108 | 0.108 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00755 | -26.20 | 0.00036 | 0.015 | 0.00 |
ROOM_3_MULT9_FLR_6 | 11381.67 | 11381.67 | 463.98 | 0.514 | 0.514 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.11 | 21.11 | 0.00757 | -26.20 | 0.00036 | 0.099 | 0.00 |
BANQUET_FLR_6 | 7883.26 | 7883.26 | 23.77 | 0.354 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 1.187 | 0.00 |
DINING_FLR_6 | 8026.36 | 8026.36 | 24.20 | 0.361 | 1.187 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00767 | -26.20 | 0.00036 | 1.187 | 0.00 |
KITCHEN_FLR_6 | 3049.25 | 3049.25 | 29.52 | 0.137 | 0.367 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.00688 | -26.20 | 0.00036 | 0.367 | 0.00 |
MECH_FLR_1 | 1977.32 | 1977.32 | 12.04 | 0.089 | 0.089 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00719 | -26.20 | 0.00036 | 0.000 | 0.00 |
STORAGE_FLR_1 | 1466.36 | 1466.36 | 15.47 | 0.066 | 0.066 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00723 | -26.20 | 0.00036 | 0.058 | 0.00 |
CORRIDOR_FLR_3 | 11668.51 | 11668.51 | 29.96 | 0.524 | 0.524 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 21.00 | 21.00 | 0.00755 | -26.20 | 0.00036 | 0.475 | 0.00 |
CORRIDOR_FLR_6 | 8290.84 | 8290.84 | 20.12 | 0.373 | 0.373 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 21.00 | 21.00 | 0.00772 | -26.20 | 0.00036 | 0.126 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV WITH REHEAT | 21.04 | 21.04 | 7.62 | 7.62 | 21.0406 | 11.6620 | 21.0406 | 0.5543 | 0.3000 |
FLR_3_DOAS | 16.91 | 2.05 | 6.12 | 2.05 | 2.0512 | 2.0512 | 2.0512 | 1.0000 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | 8488.406 | 8488.406 | 1.380370 | 0.00018754 | 152.091 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8536.73 | 8488.41 | 1.380370 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00796685 | 49.1271 | 1537.09 | 0.00 | 8538.48 | 8538.48 |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | 5313.759 | 5313.759 | 0.194764 | 0.00011740 | 115.175 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5344.39 | 5313.76 | 0.194764 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00719525 | 44.4281 | 4334.72 | 0.00 | 5347.71 | 5347.71 |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | 1768.858 | 1768.858 | 0.125213 | 0.00003908 | 34.573 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1780.41 | 1768.86 | 0.125213 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00734336 | 45.3282 | 1139.07 | 0.00 | 1780.84 | 1780.84 |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | 2601.379 | 2601.379 | 0.124110 | 0.00005747 | 53.392 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2617.36 | 2601.38 | 0.124110 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00718590 | 44.3674 | 1977.32 | 0.00 | 2618.49 | 2618.49 |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | 1797.712 | 1797.712 | 0.065893 | 0.00003972 | 38.965 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1808.08 | 1797.71 | 0.065893 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00723162 | 44.6466 | 1466.36 | 0.00 | 1809.20 | 1809.20 |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12018.938 | 12018.938 | 1.863044 | 0.00026554 | 216.086 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12087.14 | 12018.94 | 1.863044 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00715630 | 44.1883 | 2652.87 | 0.00 | 12089.75 | 12089.75 |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | 14937.484 | 14937.484 | 0.723620 | 0.00033003 | 305.814 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15029.38 | 14937.48 | 0.723620 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00721830 | 44.5684 | 11299.71 | 0.00 | 15035.77 | 15035.77 |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 36335.225 | 36335.225 | 2.597864 | 0.00080278 | 709.574 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36572.76 | 36335.23 | 2.597864 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00724053 | 44.7012 | 23271.57 | 0.00 | 36581.53 | 36581.53 |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 12824.891 | -999.000 | 1.166497 | 0.00036678 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12824.89 | 12292.53 | 1.166497 | 21.71 | 15.24 | 0.00868827 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868827 | 53.1542 | 11363.34 | 0.00 | 13439.55 | 13439.55 |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | 7782.719 | 7782.719 | 0.351778 | 0.00017195 | 177.188 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8398.64 | 7782.72 | 0.351778 | 21.11 | 13.92 | 0.00745603 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745603 | 45.7048 | 7783.06 | 0.00 | 8401.66 | 8401.66 |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 12629.989 | -999.000 | 1.147958 | 0.00036121 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 12629.99 | 12098.60 | 1.147958 | 21.71 | 15.25 | 0.00869094 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00869094 | 53.1703 | 11182.73 | 0.00 | 13235.02 | 13235.02 |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | 7803.586 | 7803.586 | 0.352721 | 0.00017241 | 177.663 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8421.15 | 7803.59 | 0.352721 | 21.11 | 13.92 | 0.00745742 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745742 | 45.7132 | 7803.92 | 0.00 | 8424.18 | 8424.18 |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 64631.030 | -999.000 | 5.974392 | 0.00184840 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 64631.03 | 62789.14 | 5.974392 | 21.71 | 15.19 | 0.00862753 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00862753 | 52.7853 | 58204.22 | 0.00 | 67754.47 | 67754.47 |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | 43866.132 | 43866.132 | 1.982803 | 0.00096917 | 998.687 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47337.73 | 43866.13 | 1.982803 | 21.11 | 13.95 | 0.00748618 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00748618 | 45.8858 | 43867.06 | 0.00 | 47355.14 | 47355.14 |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 69991.716 | -999.000 | 6.083239 | 0.00200172 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 69991.72 | 64590.90 | 6.083239 | 21.71 | 15.39 | 0.00886349 | 12.80 | 11.67 | 0.00850000 | 31.20 | 0.01534436 | 23.10 | 0.0000 | 21.11 | 0.00886349 | 54.2109 | 59259.97 | 0.00 | 73273.92 | 69317.78 |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | 44237.988 | 44237.988 | 1.999611 | 0.00097738 | 1007.151 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47738.97 | 44237.99 | 1.999611 | 21.11 | 13.95 | 0.00749009 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00749009 | 45.9094 | 44238.92 | 0.00 | 47756.57 | 47756.57 |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 11576.252 | -999.000 | 1.046260 | 0.00033107 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | 7/21 09:00:00 | 11576.25 | 11037.27 | 1.046260 | 21.71 | 15.26 | 0.00871229 | 12.80 | 11.67 | 0.00850000 | 25.37 | 0.01534436 | 21.50 | 0.0000 | 21.11 | 0.00871229 | 53.2992 | 10192.04 | 0.00 | 12130.27 | 11922.71 |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | 7746.174 | 7746.174 | 0.350126 | 0.00017114 | 176.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8359.21 | 7746.17 | 0.350126 | 21.11 | 13.92 | 0.00745365 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745365 | 45.6903 | 7746.51 | 0.00 | 8362.21 | 8362.21 |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 11513.935 | -999.000 | 1.040253 | 0.00032929 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | 7/21 08:50:00 | 11513.94 | 10974.55 | 1.040253 | 21.71 | 15.26 | 0.00871366 | 12.80 | 11.67 | 0.00850000 | 25.03 | 0.01534436 | 21.41 | 0.0000 | 21.11 | 0.00871366 | 53.3074 | 10133.51 | 0.00 | 12064.84 | 11854.20 |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | 7766.950 | 7766.950 | 0.351065 | 0.00017160 | 176.829 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8381.62 | 7766.95 | 0.351065 | 21.11 | 13.92 | 0.00745504 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00745504 | 45.6988 | 7767.29 | 0.00 | 8384.63 | 8384.63 |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | 14935.379 | 14935.379 | 0.649237 | 0.00032998 | 311.691 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15024.81 | 14935.38 | 0.649237 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00755266 | 46.6041 | 11668.51 | 0.00 | 15032.21 | 15032.21 |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 3330.889 | -999.000 | 0.303533 | 0.00009526 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3330.89 | 3197.61 | 0.303533 | 21.71 | 15.24 | 0.00868120 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868120 | 53.1115 | 2956.84 | 0.00 | 3490.73 | 3490.73 |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | 2383.362 | 2383.362 | 0.107728 | 0.00005266 | 54.260 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2571.91 | 2383.36 | 0.107728 | 21.11 | 14.01 | 0.00754993 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00754993 | 46.2734 | 2383.46 | 0.00 | 2572.90 | 2572.90 |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 3278.365 | -999.000 | 0.298537 | 0.00009376 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | 7/21 17:20:00 | 3278.36 | 3145.35 | 0.298537 | 21.71 | 15.24 | 0.00868385 | 12.80 | 11.67 | 0.00850000 | 29.36 | 0.01534435 | 22.61 | 0.0000 | 21.11 | 0.00868385 | 53.1275 | 2908.17 | 0.00 | 3435.61 | 3435.61 |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | 2395.334 | 2395.334 | 0.108269 | 0.00005292 | 54.532 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2584.83 | 2395.33 | 0.108269 | 21.11 | 14.01 | 0.00755209 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00755209 | 46.2865 | 2395.43 | 0.00 | 2585.83 | 2585.83 |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 13169.127 | -999.000 | 1.167001 | 0.00037663 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | 7/21 13:30:00 | 13169.13 | 12351.44 | 1.167001 | 21.71 | 15.33 | 0.00878779 | 12.80 | 11.67 | 0.00850000 | 30.93 | 0.01534436 | 23.03 | 0.0000 | 21.11 | 0.00878779 | 53.7549 | 11368.10 | 0.00 | 13792.86 | 13297.59 |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | 11381.295 | 11381.295 | 0.514438 | 0.00025146 | 259.106 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12281.68 | 11381.29 | 0.514438 | 21.11 | 14.02 | 0.00756512 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.11 | 0.00756512 | 46.3649 | 11381.67 | 0.00 | 12286.46 | 12286.46 |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 13661.374 | 13661.374 | 1.148131 | 0.00030183 | 261.892 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13733.31 | 13661.37 | 1.148131 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766062 | 47.2627 | 7883.26 | 0.00 | 13738.92 | 13738.92 |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14092.734 | 14092.734 | 1.205442 | 0.00031136 | 269.474 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 14167.14 | 14092.73 | 1.205442 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766641 | 47.2985 | 8026.36 | 0.00 | 14172.81 | 14172.81 |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 9508.322 | 9508.322 | 1.286163 | 0.00021007 | 172.795 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9561.75 | 9508.32 | 1.286163 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00688205 | 42.5197 | 3049.25 | 0.00 | 9564.12 | 9564.12 |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | 10166.008 | 10166.008 | 0.372567 | 0.00022461 | 220.353 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10224.61 | 10166.01 | 0.372567 | 16.70 | 12.74 | 0.00800000 | 40.00 | 20.60 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00771512 | 47.5949 | 8290.84 | 0.00 | 10230.95 | 10230.95 |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV WITH REHEAT | 689355.672 | -999.000 | 21.040624 | 0.01971548 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 689355.67 | 425767.82 | 21.040624 | 27.99 | 20.53 | 0.01283843 | 10.90 | 10.89 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 55.4022 | 23.99 | 0.00955854 | 49.0198 | 275902.67 | 0.00 | 743913.68 | 437816.84 |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV WITH REHEAT | 312531.812 | 312531.812 | 6.312187 | 0.00690501 | 3979.377 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 190120.60 | 312531.81 | 6.312187 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 184.6740 | 21.00 | 0.00749008 | 46.2237 | 85438.53 | 0.00 | 189681.92 | 189681.92 |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | FLR_3_DOAS | 87700.731 | -999.000 | 2.051199 | 0.00250823 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 10.91 | 11.67 | 0.00868318 | 31.20 | 0.01534436 | 23.10 | 100.0000 | 21.11 | 0.00874614 | 53.5021 | 163553.62 | 0.00 | 93096.22 | 49675.25 |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoopHVAC | FLR_3_DOAS | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 0.615360 | -26.20 | -26.20 | 0.00036134 | 16.70 | 12.74 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 333.3333 | 21.11 | 0.00748874 | 45.9013 | 135367.32 | 0.00 | 18491.63 | 18491.63 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
BASEMENT VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | BASEMENT VAV BOX | BASEMENT | N/A | N/A | N/A | Yes | Yes | Yes | No | 8488.406 | 8488.406 | 1.380370 | 0.00018754 | 152.091 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.3411 | 1.360346 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8536.73 | 8488.41 | 1.0000 | 1.58543153 | 1.380370 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.18752182 | 60.00 | 49.00 | 11.00 | 0.000 | 8536.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00796685 | 21.00 | 0.00796685 | 49.1271 | 1537.09 | 0.00 | 8538.48 | 8538.48 | 1.58543153 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 21.88 | 15.17 | 0.00800000 | 42320.3 | |
RETAIL_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_1_FLR_1 VAV BOX | RETAIL_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5313.759 | 5313.759 | 0.194764 | 0.00011740 | 115.175 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 0.8396 | 0.851579 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 5344.39 | 5313.76 | 1.0000 | 0.22369712 | 0.194764 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.11738904 | 60.00 | 49.00 | 11.00 | 0.000 | 5344.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00719525 | 21.00 | 0.00719525 | 44.4281 | 4334.72 | 0.00 | 5347.71 | 5347.71 | 0.22369712 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60840.7 | |
RETAIL_2_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | RETAIL_2_FLR_1 VAV BOX | RETAIL_2_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1768.858 | 1768.858 | 0.125213 | 0.00003908 | 34.573 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 0.2797 | 0.283476 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1780.41 | 1768.86 | 1.0000 | 0.14381438 | 0.125213 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.03907677 | 60.00 | 49.00 | 11.00 | 0.000 | 1780.41 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00734336 | 21.00 | 0.00734336 | 45.3282 | 1139.07 | 0.00 | 1780.84 | 1780.84 | 0.14381438 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.74 | 17.59 | 0.00800000 | 49317.7 | |
MECH_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_FLR_1 VAV BOX | MECH_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2601.379 | 2601.379 | 0.124110 | 0.00005747 | 53.392 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 0.4112 | 0.416895 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2617.36 | 2601.38 | 1.0000 | 0.14254764 | 0.124110 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05746843 | 60.00 | 49.00 | 11.00 | 0.000 | 2617.36 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00718590 | 21.00 | 0.00718590 | 44.3674 | 1977.32 | 0.00 | 2618.49 | 2618.49 | 0.14254764 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.61 | 19.51 | 0.00800000 | 55304.0 | |
STORAGE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | STORAGE_FLR_1 VAV BOX | STORAGE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1797.712 | 1797.712 | 0.065893 | 0.00003972 | 38.965 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 0.2840 | 0.288100 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 1808.08 | 1797.71 | 1.0000 | 0.07568185 | 0.065893 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.03971421 | 60.00 | 49.00 | 11.00 | 0.000 | 1808.08 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00723162 | 21.00 | 0.00723162 | 44.6466 | 1466.36 | 0.00 | 1809.20 | 1809.20 | 0.07568185 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.04 | 21.16 | 0.00800000 | 60840.0 | |
LAUNDRY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LAUNDRY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12018.938 | 12018.938 | 1.863044 | 0.00026554 | 216.086 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.8989 | 1.926146 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12087.14 | 12018.94 | 1.0000 | 2.13981008 | 1.863044 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.26551667 | 60.00 | 49.00 | 11.00 | 0.000 | 12087.14 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00715630 | 21.00 | 0.00715630 | 44.1883 | 2652.87 | 0.00 | 12089.75 | 12089.75 | 2.13981008 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.14 | 15.26 | 0.00800000 | 42584.6 | |
CAFE_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CAFE_FLR_1 VAV BOX | CAFE_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14937.484 | 14937.484 | 0.723620 | 0.00033003 | 305.814 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 2.3611 | 2.393870 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15029.38 | 14937.48 | 1.0000 | 0.83111764 | 0.723620 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.32999179 | 60.00 | 49.00 | 11.00 | 0.000 | 15029.38 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00721830 | 21.00 | 0.00721830 | 44.5684 | 11299.71 | 0.00 | 15035.77 | 15035.77 | 0.83111764 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 34.34 | 19.42 | 0.00800000 | 55025.8 | |
LOBBY_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LOBBY_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36335.225 | 36335.225 | 2.597864 | 0.00080278 | 709.574 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 5.7455 | 5.823056 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 36572.76 | 36335.23 | 1.0000 | 2.98379208 | 2.597864 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.80270051 | 60.00 | 49.00 | 11.00 | 0.000 | 36572.76 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00724053 | 21.00 | 0.00724053 | 44.7012 | 23271.57 | 0.00 | 36581.53 | 36581.53 | 2.98379208 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 28.62 | 17.55 | 0.00800000 | 49194.8 | |
ROOM_1_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12824.891 | -999.000 | 1.166497 | 0.00036678 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9911 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.166497 | 1.33978689 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 1.3087 | 1.308639 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 12824.89 | 12292.53 | 1.0000 | 1.33978689 | 1.166497 | 21.71 | 15.24 | 0.00868827 | 43894.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.36674599 | 6.70 | 13.38 | 8.33 | 0.000 | 12824.89 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868827 | 21.11 | 0.00868827 | 53.1542 | 11363.34 | 0.00 | 13439.55 | 13439.55 | 1.33978689 | 21.71 | 15.72 | 0.00868827 | 43894.5 | 11.89 | 11.89 | 0.00868827 | 33863.4 | |
ROOM_1_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_3 FAN COIL | ROOM_1_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7782.719 | 7782.719 | 0.351778 | 0.00017195 | 177.188 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_3 FAN COILFAN | Fan:OnOff | 1.166497 | 1.33978689 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.3194 | 1.247253 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8398.64 | 7782.72 | 1.0000 | 0.40403621 | 0.351778 | 21.11 | 13.92 | 0.00745603 | 40151.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17193213 | 60.00 | 49.00 | 11.00 | 0.000 | 8398.64 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745603 | 21.11 | 0.00745603 | 45.7048 | 7783.06 | 0.00 | 8401.66 | 8401.66 | 0.40403621 | 16.60 | 12.61 | 0.00745603 | 35557.5 | 37.01 | 19.84 | 0.00745603 | 56351.8 | |
ROOM_2_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12629.989 | -999.000 | 1.147958 | 0.00036121 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9960 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.147958 | 1.31849384 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 1.2888 | 1.288752 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 12629.99 | 12098.60 | 1.0000 | 1.31849384 | 1.147958 | 21.71 | 15.25 | 0.00869094 | 43901.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.36117248 | 6.70 | 13.38 | 8.33 | 0.000 | 12629.99 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00869094 | 21.11 | 0.00869094 | 53.1703 | 11182.73 | 0.00 | 13235.02 | 13235.02 | 1.31849384 | 21.71 | 15.72 | 0.00869094 | 43901.3 | 11.88 | 11.88 | 0.00869094 | 33863.3 | |
ROOM_2_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_3 FAN COIL | ROOM_2_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7803.586 | 7803.586 | 0.352721 | 0.00017241 | 177.663 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_3 FAN COILFAN | Fan:OnOff | 1.147958 | 1.31849384 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.3229 | 1.250597 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8421.15 | 7803.59 | 1.0000 | 0.40511951 | 0.352721 | 21.11 | 13.92 | 0.00745742 | 40155.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17239312 | 60.00 | 49.00 | 11.00 | 0.000 | 8421.15 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745742 | 21.11 | 0.00745742 | 45.7132 | 7803.92 | 0.00 | 8424.18 | 8424.18 | 0.40511951 | 16.60 | 12.61 | 0.00745742 | 35561.0 | 37.01 | 19.84 | 0.00745742 | 56355.4 | |
ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 64631.030 | -999.000 | 5.974392 | 0.00184840 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8782 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.974392 | 6.86192294 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 6.5950 | 6.594888 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 64631.03 | 62789.14 | 1.0000 | 6.86192294 | 5.974392 | 21.71 | 15.19 | 0.00862753 | 43741.0 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 1.84821621 | 6.70 | 13.38 | 8.33 | 0.000 | 64631.03 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00862753 | 21.11 | 0.00862753 | 52.7853 | 58204.22 | 0.00 | 67754.47 | 67754.47 | 6.86192294 | 21.71 | 15.66 | 0.00862753 | 43741.0 | 12.04 | 11.91 | 0.00862753 | 33867.0 | |
ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT19_FLR_3 FAN COIL | ROOM_3_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 43866.132 | 43866.132 | 1.982803 | 0.00096917 | 998.687 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 5.974392 | 6.86192294 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 7.4366 | 7.029954 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47337.73 | 43866.13 | 1.0000 | 2.27735988 | 1.982803 | 21.11 | 13.95 | 0.00748618 | 40229.0 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.96906972 | 60.00 | 49.00 | 11.00 | 0.000 | 47337.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00748618 | 21.11 | 0.00748618 | 45.8858 | 43867.06 | 0.00 | 47355.14 | 47355.14 | 2.27735988 | 16.60 | 12.64 | 0.00748618 | 35633.9 | 37.01 | 19.86 | 0.00748618 | 56427.7 | |
ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 69991.716 | -999.000 | 6.083239 | 0.00200172 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3168 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.083239 | 6.98693906 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 7.1420 | 7.141887 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | 69991.72 | 64590.90 | 1.0000 | 6.98693906 | 6.083239 | 21.71 | 15.39 | 0.00886349 | 44339.7 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 2.00151264 | 6.70 | 13.38 | 8.33 | 0.000 | 69991.72 | 31.20 | 0.01534436 | 23.10 | 0.00000000 | 0.0000 | 21.11 | 0.00886349 | 21.11 | 0.00886349 | 54.2109 | 59259.97 | 0.00 | 73273.92 | 69317.78 | 6.98693906 | 21.71 | 15.87 | 0.00886349 | 44339.7 | 12.00 | 11.91 | 0.00863909 | 33852.4 | |
ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_4_MULT19_FLR_3 FAN COIL | ROOM_4_MULT19_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 44237.988 | 44237.988 | 1.999611 | 0.00097738 | 1007.151 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_4_MULT19_FLR_3 FAN COILFAN | Fan:OnOff | 6.083239 | 6.98693906 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 7.4997 | 7.089547 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 47738.97 | 44237.99 | 1.0000 | 2.29666518 | 1.999611 | 21.11 | 13.95 | 0.00749009 | 40238.9 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.97728458 | 60.00 | 49.00 | 11.00 | 0.000 | 47738.97 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00749009 | 21.11 | 0.00749009 | 45.9094 | 44238.92 | 0.00 | 47756.57 | 47756.57 | 2.29666518 | 16.60 | 12.64 | 0.00749009 | 35643.7 | 37.01 | 19.87 | 0.00749009 | 56437.6 | |
ROOM_5_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11576.252 | -999.000 | 1.046260 | 0.00033107 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0357 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.046260 | 1.20168845 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 1.1813 | 1.181230 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | unknown | unknown | unknown | 7/21 09:00:00 | 11576.25 | 11037.27 | 1.0000 | 1.20168845 | 1.046260 | 21.71 | 15.26 | 0.00871229 | 43955.5 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.33103937 | 6.70 | 13.38 | 8.33 | 0.000 | 11576.25 | 25.37 | 0.01534436 | 21.50 | 0.00000000 | 0.0000 | 21.11 | 0.00871229 | 21.11 | 0.00871229 | 53.2992 | 10192.04 | 0.00 | 12130.27 | 11922.71 | 1.20168845 | 21.71 | 15.74 | 0.00871229 | 43955.5 | 11.99 | 11.91 | 0.00864384 | 33861.2 | |
ROOM_5_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_5_FLR_3 FAN COIL | ROOM_5_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7746.174 | 7746.174 | 0.350126 | 0.00017114 | 176.356 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_5_FLR_3 FAN COILFAN | Fan:OnOff | 1.046260 | 1.20168845 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.3132 | 1.241396 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8359.21 | 7746.17 | 1.0000 | 0.40213900 | 0.350126 | 21.11 | 13.92 | 0.00745365 | 40145.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17112480 | 60.00 | 49.00 | 11.00 | 0.000 | 8359.21 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745365 | 21.11 | 0.00745365 | 45.6903 | 7746.51 | 0.00 | 8362.21 | 8362.21 | 0.40213900 | 16.60 | 12.61 | 0.00745365 | 35551.5 | 37.01 | 19.84 | 0.00745365 | 56345.8 | |
ROOM_6_FLR_3 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11513.935 | -999.000 | 1.040253 | 0.00032929 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0383 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.040253 | 1.19478823 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 1.1749 | 1.174871 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | unknown | unknown | unknown | 7/21 08:50:00 | 11513.94 | 10974.55 | 1.0000 | 1.19478823 | 1.040253 | 21.71 | 15.26 | 0.00871366 | 43959.0 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.32925735 | 6.70 | 13.38 | 8.33 | 0.000 | 11513.94 | 25.03 | 0.01534436 | 21.41 | 0.00000000 | 0.0000 | 21.11 | 0.00871366 | 21.11 | 0.00871366 | 53.3074 | 10133.51 | 0.00 | 12064.84 | 11854.20 | 1.19478823 | 21.71 | 15.74 | 0.00871366 | 43959.0 | 11.99 | 11.91 | 0.00864379 | 33861.1 | |
ROOM_6_FLR_3 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_6_FLR_3 FAN COIL | ROOM_6_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7766.950 | 7766.950 | 0.351065 | 0.00017160 | 176.829 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_6_FLR_3 FAN COILFAN | Fan:OnOff | 1.040253 | 1.19478823 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.3167 | 1.244726 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 8381.62 | 7766.95 | 1.0000 | 0.40321757 | 0.351065 | 21.11 | 13.92 | 0.00745504 | 40149.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.17158377 | 60.00 | 49.00 | 11.00 | 0.000 | 8381.62 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00745504 | 21.11 | 0.00745504 | 45.6988 | 7767.29 | 0.00 | 8384.63 | 8384.63 | 0.40321757 | 16.60 | 12.61 | 0.00745504 | 35555.0 | 37.01 | 19.84 | 0.00745504 | 56349.3 | |
CORRIDOR_FLR_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_3 VAV BOX | CORRIDOR_FLR_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14935.379 | 14935.379 | 0.649237 | 0.00032998 | 311.691 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 2.3604 | 2.393533 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 15024.81 | 14935.38 | 1.0000 | 0.74568527 | 0.649237 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.32994529 | 60.00 | 49.00 | 11.00 | 0.000 | 15024.81 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00755266 | 21.00 | 0.00755266 | 46.6041 | 11668.51 | 0.00 | 15032.21 | 15032.21 | 0.74568527 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 36.37 | 20.05 | 0.00800000 | 57093.7 | |
ROOM_1_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3330.889 | -999.000 | 0.303533 | 0.00009526 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9779 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.303533 | 0.34862441 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 0.3399 | 0.339881 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3330.89 | 3197.61 | 1.0000 | 0.34862441 | 0.303533 | 21.71 | 15.24 | 0.00868120 | 43876.6 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.09525150 | 6.70 | 13.38 | 8.33 | 0.000 | 3330.89 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868120 | 21.11 | 0.00868120 | 53.1115 | 2956.84 | 0.00 | 3490.73 | 3490.73 | 0.34862441 | 21.71 | 15.71 | 0.00868120 | 43876.6 | 11.90 | 11.90 | 0.00868120 | 33863.7 | |
ROOM_1_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_1_FLR_6 FAN COIL | ROOM_1_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2383.362 | 2383.362 | 0.107728 | 0.00005266 | 54.260 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_1_FLR_6 FAN COILFAN | Fan:OnOff | 0.303533 | 0.34862441 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 0.4040 | 0.381956 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2571.91 | 2383.36 | 1.0000 | 0.12373115 | 0.107728 | 21.11 | 14.01 | 0.00754993 | 40390.3 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05265210 | 60.00 | 49.00 | 11.00 | 0.000 | 2571.91 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00754993 | 21.11 | 0.00754993 | 46.2734 | 2383.46 | 0.00 | 2572.90 | 2572.90 | 0.12373115 | 16.60 | 12.70 | 0.00754993 | 35795.2 | 37.01 | 19.91 | 0.00754993 | 56589.6 | |
ROOM_2_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3278.365 | -999.000 | 0.298537 | 0.00009376 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9828 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.298537 | 0.34288585 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 0.3345 | 0.334521 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | unknown | unknown | unknown | 7/21 17:20:00 | 3278.36 | 3145.35 | 1.0000 | 0.34288585 | 0.298537 | 21.71 | 15.24 | 0.00868385 | 43883.3 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.09374950 | 6.70 | 13.38 | 8.33 | 0.000 | 3278.36 | 29.36 | 0.01534435 | 22.61 | 0.00000000 | 0.0000 | 21.11 | 0.00868385 | 21.11 | 0.00868385 | 53.1275 | 2908.17 | 0.00 | 3435.61 | 3435.61 | 0.34288585 | 21.71 | 15.71 | 0.00868385 | 43883.3 | 11.90 | 11.90 | 0.00868385 | 33863.6 | |
ROOM_2_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_2_FLR_6 FAN COIL | ROOM_2_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2395.334 | 2395.334 | 0.108269 | 0.00005292 | 54.532 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_2_FLR_6 FAN COILFAN | Fan:OnOff | 0.298537 | 0.34288585 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 0.4061 | 0.383874 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 2584.83 | 2395.33 | 1.0000 | 0.12435269 | 0.108269 | 21.11 | 14.01 | 0.00755209 | 40395.8 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.05291658 | 60.00 | 49.00 | 11.00 | 0.000 | 2584.83 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00755209 | 21.11 | 0.00755209 | 46.2865 | 2395.43 | 0.00 | 2585.83 | 2585.83 | 0.12435269 | 16.60 | 12.70 | 0.00755209 | 35800.7 | 37.01 | 19.91 | 0.00755209 | 56595.0 | |
ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL | COIL:COOLING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13169.127 | -999.000 | 1.167001 | 0.00037663 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1761 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.167001 | 1.34036572 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 1.3438 | 1.343765 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | unknown | unknown | unknown | 7/21 13:30:00 | 13169.13 | 12351.44 | 1.0000 | 1.34036572 | 1.167001 | 21.71 | 15.33 | 0.00878779 | 44147.2 | 12.80 | 11.67 | 0.00850000 | 34322.2 | 0.37658991 | 6.70 | 13.38 | 8.33 | 0.000 | 13169.13 | 30.93 | 0.01534436 | 23.03 | 0.00000000 | 0.0000 | 21.11 | 0.00878779 | 21.11 | 0.00878779 | 53.7549 | 11368.10 | 0.00 | 13792.86 | 13297.59 | 1.34036572 | 21.71 | 15.80 | 0.00878779 | 44147.2 | 11.99 | 11.91 | 0.00864135 | 33856.8 | |
ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:FOURPIPEFANCOIL | ROOM_3_MULT9_FLR_6 FAN COIL | ROOM_3_MULT9_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11381.295 | 11381.295 | 0.514438 | 0.00025146 | 259.106 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | ROOM_3_MULT9_FLR_6 FAN COILFAN | Fan:OnOff | 1.167001 | 1.34036572 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.9294 | 1.823958 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 12281.68 | 11381.29 | 1.0000 | 0.59086113 | 0.514438 | 21.11 | 14.02 | 0.00756512 | 40429.1 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.25143015 | 60.00 | 49.00 | 11.00 | 0.000 | 12281.68 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.11 | 0.00756512 | 21.11 | 0.00756512 | 46.3649 | 11381.67 | 0.00 | 12286.46 | 12286.46 | 0.59086113 | 16.60 | 12.72 | 0.00756512 | 35833.7 | 37.01 | 19.92 | 0.00756512 | 56627.9 | |
BANQUET_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BANQUET_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13661.374 | 13661.374 | 1.148131 | 0.00030183 | 261.892 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 2.1575 | 2.189362 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 13733.31 | 13661.37 | 1.0000 | 1.31869296 | 1.148131 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.30180057 | 60.00 | 49.00 | 11.00 | 0.000 | 13733.31 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766062 | 21.00 | 0.00766062 | 47.2627 | 7883.26 | 0.00 | 13738.92 | 13738.92 | 1.31869296 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.82 | 16.93 | 0.00800000 | 47353.3 | |
DINING_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | DINING_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14092.734 | 14092.734 | 1.205442 | 0.00031136 | 269.474 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 2.2256 | 2.258491 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 14167.14 | 14092.73 | 1.0000 | 1.38451755 | 1.205442 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.31132998 | 60.00 | 49.00 | 11.00 | 0.000 | 14167.14 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00766641 | 21.00 | 0.00766641 | 47.2985 | 8026.36 | 0.00 | 14172.81 | 14172.81 | 1.38451755 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 26.64 | 16.87 | 0.00800000 | 47171.4 | |
KITCHEN_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | KITCHEN_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9508.322 | 9508.322 | 1.286163 | 0.00021007 | 172.795 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.5021 | 1.523797 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 9561.75 | 9508.32 | 1.0000 | 1.47723037 | 1.286163 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.21005332 | 60.00 | 49.00 | 11.00 | 0.000 | 9561.75 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.67 | 0.00688205 | 21.00 | 0.00688205 | 42.5197 | 3049.25 | 0.00 | 9564.12 | 9564.12 | 1.47723037 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 22.95 | 15.56 | 0.00800000 | 43409.1 | |
CORRIDOR_FLR_6 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_FLR_6 VAV BOX | CORRIDOR_FLR_6 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10166.008 | 10166.008 | 0.372567 | 0.00022461 | 220.353 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 1.6063 | 1.629197 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:50:00 | 10224.61 | 10166.01 | 1.0000 | 0.42791359 | 0.372567 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 40.00 | 20.60 | 0.00800000 | 60796.0 | 0.22458260 | 60.00 | 49.00 | 11.00 | 0.000 | 10224.61 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 21.00 | 0.00771512 | 21.00 | 0.00771512 | 47.5949 | 8290.84 | 0.00 | 10230.95 | 10230.95 | 0.42791359 | 16.60 | 13.14 | 0.00800000 | 36934.7 | 40.05 | 21.16 | 0.00800000 | 60843.7 | |
VAV WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 689355.672 | -999.000 | 21.040624 | 0.01971548 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.7060 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 21.040624 | 24.16633182 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 70.3425 | 70.342501 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 689355.67 | 425767.82 | 1.0000 | 24.16633182 | 21.040624 | 27.99 | 20.53 | 0.01283843 | 60896.8 | 10.90 | 10.89 | 0.00868318 | 32386.7 | 19.71347377 | 6.70 | 13.38 | 8.33 | 47144.435 | 642211.24 | 31.20 | 0.01534436 | 23.10 | 11.65697000 | 55.4022 | 23.99 | 0.00972252 | 23.99 | 0.00955854 | 49.0198 | 275902.67 | 0.00 | 743913.68 | 437816.84 | 24.16633182 | 27.99 | 21.07 | 0.01283843 | 60896.8 | 10.37 | 10.36 | 0.00781259 | 30113.8 | |
VAV WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV WITH REHEAT | BASEMENT; RETAIL_1_FLR_1; RETAIL_2_FLR_1; MECH_FLR_1; STORAGE_FLR_1; LAUNDRY_FLR_1; CAFE_FLR_1; LOBBY_FLR_1; CORRIDOR_FLR_3; BANQUET_FLR_6; DINING_FLR_6; KITCHEN_FLR_6; CORRIDOR_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 312531.812 | 312531.812 | 6.312187 | 0.00690501 | 3979.377 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV WITH REHEAT_FAN | Fan:VariableVolume | 21.040624 | 24.16633182 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 29.8675 | 50.086118 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 190120.60 | 312531.81 | 1.0000 | 7.24989955 | 6.312187 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 6.90430412 | 60.00 | 49.00 | 11.00 | 0.000 | 190120.60 | -26.20 | 0.00036134 | -26.20 | 11.65697000 | 184.6740 | 20.98 | 0.00737465 | 21.00 | 0.00749008 | 46.2237 | 85438.53 | 0.00 | 189681.92 | 189681.92 | 7.24989955 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 | |
FLR_3_DOAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 87700.731 | -999.000 | 2.051199 | 0.00250823 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1033.3644 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 28.02498269 | 15.03 | 6.70 | 8.33 | 979998.81 | 8.9491 | 8.949065 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 87700.73 | 47797.05 | 1.0000 | 2.35591662 | 2.051199 | 31.20 | 23.10 | 0.01534436 | 70616.3 | 10.91 | 11.67 | 0.00868318 | 34322.2 | 2.50797395 | 6.70 | 13.38 | 8.33 | 2194.880 | 85505.85 | 31.20 | 0.01534436 | 23.10 | 2.05119905 | 100.0000 | 21.11 | 0.00875734 | 21.11 | 0.00874614 | 53.5021 | 163553.62 | 0.00 | 93096.22 | 49675.25 | 2.35591662 | 31.20 | 23.68 | 0.01534436 | 70616.3 | 10.80 | 10.78 | 0.00803355 | 31100.4 | |
FLR_3_DOAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | FLR_3_DOAS | ROOM_1_FLR_3; ROOM_2_FLR_3; ROOM_3_MULT19_FLR_3; ROOM_4_MULT19_FLR_3; ROOM_5_FLR_3; ROOM_6_FLR_3; ROOM_2_FLR_6; ROOM_3_MULT9_FLR_6; ROOM_1_FLR_6; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 30467.962 | 30467.962 | 0.615360 | 0.00067315 | 387.940 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | FLR_3_DOAS_FAN | Fan:ConstantVolume | 2.051199 | 2.35591662 | 4197.9300 | 999.8980 | 13.78486580 | 71.00 | 82.00 | 11.00 | 636546.92 | 2.9117 | 4.882773 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | 18534.39 | 30467.96 | 1.0000 | 0.70677499 | 0.615360 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 16.70 | 12.74 | 0.00800000 | 37036.7 | 0.67308373 | 60.00 | 49.00 | 11.00 | 0.000 | 18534.39 | -26.20 | 0.00036134 | -26.20 | 2.05119905 | 333.3333 | 21.11 | 0.00748934 | 21.11 | 0.00748874 | 45.9013 | 135367.32 | 0.00 | 18491.63 | 18491.63 | 0.70677499 | 16.60 | 4.51 | 0.00036134 | 17595.2 | 42.62 | 15.83 | 0.00036134 | 43758.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 21.04 | - | |||
FLR_3_DOAS_OA_CONTROLLER | DifferentialDryBulb | 2.05 | 2.05 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
BASEMENT | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_1_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
RETAIL_2_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.001181 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LAUNDRY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CAFE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.003540 | 0.000914 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
LOBBY_FLR_1 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.001447 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
BANQUET_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
DINING_FLR_6 | VAV_WITH_REHEAT_DCV | 0.009440 | 0.003580 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
KITCHEN_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.003555 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
MECH_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
STORAGE_FLR_1 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000609 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_3 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORRIDOR_FLR_6 | VAV_WITH_REHEAT_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 254.00 | 8444.83 | 251.83 |
RETAIL_1_FLR_1 | 2624.67 | 8153.33 | 2342.00 |
RETAIL_2_FLR_1 | 679.17 | 8360.17 | 591.50 |
LAUNDRY_FLR_1 | 5927.67 | 3318.33 | 2212.83 |
CAFE_FLR_1 | 2575.00 | 7026.67 | 1637.00 |
LOBBY_FLR_1 | 1194.33 | 7043.33 | 555.50 |
ROOM_1_FLR_3 | 3029.33 | 8404.50 | 2992.00 |
ROOM_2_FLR_3 | 3998.83 | 8187.50 | 3704.17 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 2512.67 | 8636.83 | 2472.33 |
ROOM_5_FLR_3 | 2984.00 | 8425.67 | 2965.67 |
ROOM_6_FLR_3 | 3731.50 | 8277.00 | 3576.33 |
ROOM_1_FLR_6 | 3536.17 | 8250.33 | 3418.33 |
ROOM_2_FLR_6 | 4508.50 | 8080.17 | 4187.00 |
ROOM_3_MULT9_FLR_6 | 2395.83 | 8318.67 | 2365.83 |
BANQUET_FLR_6 | 3364.67 | 4291.83 | 836.00 |
DINING_FLR_6 | 4219.83 | 2864.50 | 650.33 |
KITCHEN_FLR_6 | 8015.50 | 6346.33 | 5981.00 |
MECH_FLR_1 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 0.00 | 0.00 | 0.00 |
Facility | 8751.83 | 8760.00 | 8029.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 198.67 | 0.00 | 198.67 | 0.00 |
RETAIL_1_FLR_1 | 203.33 | 0.00 | 203.33 | 0.00 |
RETAIL_2_FLR_1 | 198.17 | 0.00 | 198.17 | 0.00 |
LAUNDRY_FLR_1 | 149.00 | 105.33 | 149.00 | 105.33 |
CAFE_FLR_1 | 171.67 | 0.00 | 171.67 | 0.00 |
LOBBY_FLR_1 | 179.33 | 0.00 | 179.33 | 0.00 |
ROOM_1_FLR_3 | 32.33 | 0.00 | 32.33 | 0.00 |
ROOM_2_FLR_3 | 59.50 | 3.83 | 59.50 | 3.83 |
ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 96.00 | 23.00 | 96.00 | 23.00 |
ROOM_5_FLR_3 | 49.50 | 0.00 | 49.50 | 0.00 |
ROOM_6_FLR_3 | 72.83 | 16.33 | 72.83 | 16.33 |
ROOM_1_FLR_6 | 28.83 | 1.17 | 28.83 | 1.17 |
ROOM_2_FLR_6 | 62.17 | 15.50 | 62.17 | 15.50 |
ROOM_3_MULT9_FLR_6 | 22.50 | 8.17 | 22.50 | 8.17 |
BANQUET_FLR_6 | 135.50 | 0.00 | 135.50 | 0.00 |
DINING_FLR_6 | 132.00 | 0.00 | 132.00 | 0.00 |
KITCHEN_FLR_6 | 122.00 | 174.00 | 122.00 | 174.00 |
MECH_FLR_1 | 251.50 | 0.00 | 0.00 | 0.00 |
STORAGE_FLR_1 | 290.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 349.17 | 0.00 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 273.83 | 0.00 | 0.00 | 0.00 |
Facility | 375.67 | 316.50 | 271.00 | 316.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.73 | 106.50 | 4826.41 | 1.056 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.396 | 0.276 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.487 | 0.050 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 24.514 | 0.154 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.555 | 0.249 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.87 | 422.44 | 5183.56 | 1.839 | 0.072 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.068 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.054 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.403 | 0.081 | 0.000 | 0.102 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.068 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.063 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.355 | 0.182 | 0.000 | 0.082 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.355 | 0.182 | 0.000 | 0.053 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.403 | 0.148 | 0.000 | 0.131 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.553 | 0.053 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.949 | 0.053 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 21.555 | 0.151 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.73 | 106.50 | 4826.41 | 0.984 | 0.000 | 0.000 | 0.000 |
RETAIL_1_FLR_1 | 6.28 | 10.83 | 265.76 | 2.231 | 0.004 | 0.000 | 0.000 |
RETAIL_2_FLR_1 | 7.27 | 12.54 | 307.76 | 1.393 | 0.001 | 0.000 | 0.000 |
LAUNDRY_FLR_1 | 4.87 | 8.40 | 309.22 | 19.933 | 0.002 | 0.000 | 0.000 |
CAFE_FLR_1 | 82.49 | 142.30 | 748.35 | 3.308 | 0.004 | 0.000 | 0.000 |
LOBBY_FLR_1 | 244.87 | 422.44 | 5183.56 | 1.717 | 0.001 | 0.000 | 0.000 |
ROOM_1_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT19_FLR_3 | 1.50 | 74.75 | |||||
ROOM_4_MULT19_FLR_3 | 0.95 | 1.50 | 74.77 | 0.000 | 0.001 | 0.000 | 0.000 |
ROOM_5_FLR_3 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_6_FLR_3 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_1_FLR_6 | 0.95 | 1.50 | 118.94 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_2_FLR_6 | 0.95 | 1.50 | 118.93 | 0.000 | 0.003 | 0.000 | 0.000 |
ROOM_3_MULT9_FLR_6 | 0.95 | 1.50 | 74.77 | 0.000 | 0.002 | 0.000 | 0.000 |
BANQUET_FLR_6 | 144.86 | 249.90 | 1010.89 | 3.885 | 0.001 | 0.000 | 0.000 |
DINING_FLR_6 | 144.86 | 249.90 | 1010.89 | 4.078 | 0.001 | 0.000 | 0.000 |
KITCHEN_FLR_6 | 12.89 | 22.24 | 314.87 | 13.690 | 0.002 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Surfaces by ClassTotal | Outdoors | |
Wall | 119 | 44 |
Floor | 25 | 0 |
Roof | 33 | 11 |
Internal Mass | 22 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 2 |
Conditioned Zones | 22 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
Electricity:Building | 2491.55 | 31189.19 | 17-JUN-05:00 | 161759.69 | 02-JAN-20:10 |
Electricity:Zone:BASEMENT | 308.71 | 3532.55 | 02-JAN-02:10 | 23174.34 | 02-JAN-20:10 |
InteriorLights:Electricity | 826.27 | 6846.07 | 17-JUN-05:00 | 75078.55 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BASEMENT | 165.60 | 1504.65 | 02-JAN-02:10 | 13541.81 | 02-JAN-20:10 |
LightsWired:InteriorLights:Electricity | 826.27 | 6846.07 | 17-JUN-05:00 | 75078.55 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_1_FLR_1 | 18.61 | 220.86 | 02-JAN-02:10 | 1374.34 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_1_FLR_1 | 8.42 | 76.53 | 02-JAN-02:10 | 688.74 | 02-JAN-20:10 |
Electricity:Zone:RETAIL_2_FLR_1 | 21.55 | 255.76 | 02-JAN-02:10 | 1591.50 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:RETAIL_2_FLR_1 | 9.75 | 88.62 | 02-JAN-02:10 | 797.56 | 02-JAN-20:10 |
Electricity:Zone:MECH_FLR_1 | 30.96 | 344.68 | 02-JAN-02:10 | 2351.00 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:MECH_FLR_1 | 18.48 | 167.95 | 02-JAN-02:10 | 1511.55 | 02-JAN-20:10 |
Electricity:Zone:STORAGE_FLR_1 | 5.90 | 71.86 | 02-JAN-02:10 | 430.06 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:STORAGE_FLR_1 | 2.30 | 20.88 | 02-JAN-02:10 | 187.90 | 02-JAN-20:10 |
Electricity:Zone:LAUNDRY_FLR_1 | 71.91 | 998.82 | 02-JAN-02:10 | 4897.88 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LAUNDRY_FLR_1 | 3.98 | 36.12 | 02-JAN-02:10 | 325.08 | 02-JAN-20:10 |
Electricity:Zone:CAFE_FLR_1 | 25.01 | 272.50 | 03-JUN-05:00 | 2264.29 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CAFE_FLR_1 | 10.67 | 63.51 | 01-JAN-13:10 | 1299.02 | 02-JAN-20:10 |
Electricity:Zone:LOBBY_FLR_1 | 304.18 | 3499.54 | 03-JUN-05:00 | 23462.67 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:LOBBY_FLR_1 | 155.18 | 1388.12 | 03-JUN-05:00 | 13433.46 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_3 | 20.83 | 191.12 | 02-JAN-10:10 | 1761.93 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_3 | 10.36 | 64.68 | 01-JAN-11:10 | 1034.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_3 | 20.83 | 191.09 | 02-JAN-10:10 | 1761.73 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_3 | 10.35 | 64.68 | 01-JAN-11:10 | 1034.83 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT19_FLR_3 | 318.64 | 3125.26 | 02-JAN-10:10 | 25887.17 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 123.65 | 772.38 | 01-JAN-11:10 | 12358.13 | 01-JAN-19:10 |
Electricity:Zone:ROOM_4_MULT19_FLR_3 | 318.73 | 3126.11 | 02-JAN-10:10 | 25894.25 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 123.68 | 772.59 | 01-JAN-11:10 | 12361.51 | 01-JAN-19:10 |
Electricity:Zone:ROOM_5_FLR_3 | 20.83 | 191.12 | 02-JAN-10:10 | 1761.93 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_5_FLR_3 | 10.36 | 64.68 | 01-JAN-11:10 | 1034.95 | 01-JAN-19:10 |
Electricity:Zone:ROOM_6_FLR_3 | 20.83 | 191.09 | 02-JAN-10:10 | 1761.73 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_6_FLR_3 | 10.35 | 64.68 | 01-JAN-11:10 | 1034.83 | 01-JAN-19:10 |
Electricity:Zone:CORRIDOR_FLR_3 | 66.04 | 600.08 | 02-JAN-02:10 | 5400.74 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_3 | 66.04 | 600.08 | 02-JAN-02:10 | 5400.74 | 02-JAN-20:10 |
Electricity:Zone:ROOM_1_FLR_6 | 5.21 | 47.78 | 02-JAN-10:10 | 440.48 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_1_FLR_6 | 2.59 | 16.17 | 01-JAN-11:10 | 258.74 | 01-JAN-19:10 |
Electricity:Zone:ROOM_2_FLR_6 | 5.21 | 47.77 | 02-JAN-10:10 | 440.43 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_2_FLR_6 | 2.59 | 16.17 | 01-JAN-11:10 | 258.71 | 01-JAN-19:10 |
Electricity:Zone:ROOM_3_MULT9_FLR_6 | 37.74 | 370.20 | 02-JAN-10:10 | 3066.42 | 01-JAN-21:10 |
InteriorLights:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 14.65 | 91.49 | 01-JAN-11:10 | 1463.86 | 01-JAN-19:10 |
Electricity:Zone:BANQUET_FLR_6 | 199.27 | 2401.38 | 17-JUN-05:00 | 9029.09 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:BANQUET_FLR_6 | 23.42 | 152.08 | 17-JUN-05:00 | 2281.19 | 02-JAN-20:10 |
Electricity:Zone:DINING_FLR_6 | 199.27 | 2401.38 | 17-JUN-05:00 | 9029.09 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:DINING_FLR_6 | 23.42 | 152.08 | 17-JUN-05:00 | 2281.19 | 02-JAN-20:10 |
Electricity:Zone:KITCHEN_FLR_6 | 453.81 | 6249.79 | 02-JAN-02:10 | 18934.39 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:KITCHEN_FLR_6 | 12.97 | 117.87 | 02-JAN-02:10 | 1060.81 | 02-JAN-20:10 |
Electricity:Zone:CORRIDOR_FLR_6 | 17.47 | 158.77 | 02-JAN-02:10 | 1428.96 | 02-JAN-20:10 |
InteriorLights:Electricity:Zone:CORRIDOR_FLR_6 | 17.47 | 158.77 | 02-JAN-02:10 | 1428.96 | 02-JAN-20:10 |
InteriorEquipment:Electricity | 1658.19 | 24201.97 | 02-JAN-02:10 | 89171.45 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 143.11 | 2027.90 | 02-JAN-02:10 | 9632.53 | 02-JAN-20:10 |
MiscPlug:InteriorEquipment:Electricity | 872.73 | 13712.59 | 02-JAN-02:10 | 59188.31 | 02-JAN-07:10 |
InteriorEquipment:Electricity:Zone:RETAIL_1_FLR_1 | 10.19 | 144.34 | 02-JAN-02:10 | 685.60 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:RETAIL_2_FLR_1 | 11.80 | 167.14 | 02-JAN-02:10 | 793.93 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:MECH_FLR_1 | 12.47 | 176.73 | 02-JAN-02:10 | 839.45 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:STORAGE_FLR_1 | 3.60 | 50.98 | 02-JAN-02:10 | 242.16 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LAUNDRY_FLR_1 | 67.94 | 962.69 | 02-JAN-02:10 | 4572.80 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:CAFE_FLR_1 | 14.34 | 203.22 | 02-JAN-02:10 | 965.27 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:LOBBY_FLR_1 | 149.00 | 2111.41 | 02-JAN-02:10 | 10029.21 | 02-JAN-20:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 195.00 | 2352.88 | 02-JAN-10:10 | 17646.57 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 195.05 | 2353.52 | 02-JAN-10:10 | 17651.40 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_5_FLR_3 | 10.48 | 126.43 | 02-JAN-10:10 | 948.23 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_6_FLR_3 | 10.48 | 126.42 | 02-JAN-10:10 | 948.12 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_1_FLR_6 | 2.62 | 31.61 | 02-JAN-10:10 | 237.06 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_2_FLR_6 | 2.62 | 31.60 | 02-JAN-10:10 | 237.03 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 23.10 | 278.71 | 02-JAN-10:10 | 2090.30 | 01-JAN-08:10 |
InteriorEquipment:Electricity:Zone:BANQUET_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
Cooking:InteriorEquipment:Electricity | 762.04 | 9746.88 | 01-JAN-00:10 | 29240.64 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:DINING_FLR_6 | 175.86 | 2249.30 | 01-JAN-00:10 | 6747.90 | 01-JAN-07:10 |
InteriorEquipment:Electricity:Zone:KITCHEN_FLR_6 | 433.74 | 5990.78 | 01-JAN-00:10 | 16487.34 | 01-JAN-07:10 |
ReachInFreezer:InteriorEquipment:Electricity | 14.43 | 457.50 | 01-JAN-00:10 | 457.50 | 01-JAN-00:10 |
ReachInRefrigerator:InteriorEquipment:Electricity | 8.99 | 285.00 | 01-JAN-00:10 | 285.00 | 01-JAN-00:10 |
Refrigeration:Electricity | 61.19 | 714.33 | 02-FEB-23:30 | 3258.48 | 19-MAY-07:20 |
Refrigeration:Electricity:Zone:KITCHEN_FLR_6 | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
General:Refrigeration:Electricity | 7.09 | 88.82 | 02-JAN-11:30 | 2093.44 | 01-JAN-11:10 |
Electricity:Plant | 988.47 | 2500.21 | 26-APR-03:00 | 210728.74 | 04-AUG-15:50 |
LowTempRefrigeration:Refrigeration:Electricity | 20.23 | 0.00 | 01-JAN-11:10 | 1941.43 | 09-APR-10:50 |
MedTempRefrigeration:Refrigeration:Electricity | 33.86 | 446.68 | 02-FEB-06:00 | 1195.92 | 06-JUN-13:10 |
WaterSystems:Electricity | 90.76 | 1086.65 | 19-APR-00:20 | 4749.05 | 02-FEB-07:30 |
Water Heater:WaterSystems:Electricity | 90.76 | 1086.65 | 19-APR-00:20 | 4749.05 | 02-FEB-07:30 |
Fans:Electricity | 512.52 | 11574.59 | 05-JAN-08:10 | 28770.70 | 24-OCT-21:00 |
Fans:Electricity:Zone:ROOM_1_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_4_MULT19_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_5_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_6_FLR_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_1_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_2_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity:Zone:ROOM_3_MULT9_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Electricity:HVAC | 742.23 | 13110.38 | 24-SEP-04:40 | 39988.15 | 24-OCT-21:00 |
ExteriorEquipment:Electricity | 972.26 | 6510.93 | 02-JAN-02:20 | 62594.23 | 02-JAN-07:20 |
Transformer:ExteriorEquipment:Electricity | 21.81 | 380.99 | 17-JUN-05:00 | 1300.47 | 02-JAN-21:10 |
ElectricityPurchased:Facility | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
ElectricityPurchased:Plant | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
Cogeneration:ElectricityPurchased | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
ElectricityNet:Plant | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
Cogeneration:ElectricityNet | 5355.32 | 70784.91 | 24-APR-02:20 | 432378.24 | 26-JUL-19:10 |
General:Fans:Electricity | 512.52 | 11574.59 | 05-JAN-08:10 | 28770.70 | 24-OCT-21:00 |
ExteriorLights:Electricity | 182.61 | 0.00 | 01-JAN-08:00 | 11632.50 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 182.61 | 0.00 | 01-JAN-08:00 | 11632.50 | 01-JAN-00:10 |
ElevatorLift:ExteriorEquipment:Electricity | 947.54 | 6111.10 | 01-JAN-00:10 | 61110.99 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 2.91 | 18.79 | 01-JAN-00:10 | 187.95 | 01-JAN-07:10 |
HeatRecovery:Electricity | 207.89 | 0.00 | 18-MAR-13:10 | 9924.11 | 02-JAN-06:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 801.69 | 0.00 | 01-JAN-00:10 | 203597.39 | 04-AUG-15:50 |
General:Cooling:Electricity | 801.69 | 0.00 | 01-JAN-00:10 | 203597.39 | 04-AUG-15:50 |
Pumps:Electricity | 41.93 | 47.95 | 20-MAR-10:20 | 4681.15 | 30-JAN-16:30 |
General:Pumps:Electricity | 41.93 | 47.95 | 20-MAR-10:20 | 4681.15 | 30-JAN-16:30 |
WIRED_LTG_ELECTRICITY | 29.08 | 0.00 | 01-JAN-00:10 | 2642.76 | 02-JAN-20:20 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 6094.90 | 29277.89 | 19-APR-01:10 | 976339.25 | 02-FEB-21:00 |
Gas:Building | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
InteriorEquipment:Gas | 1788.85 | 13361.90 | 02-JAN-02:10 | 104248.32 | 02-JAN-18:10 |
InteriorEquipment:Gas:Zone:LAUNDRY_FLR_1 | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Laundry:InteriorEquipment:Gas | 590.21 | 8363.49 | 02-JAN-02:10 | 39726.58 | 02-JAN-20:10 |
Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
InteriorEquipment:Gas:Zone:KITCHEN_FLR_6 | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Cooking:InteriorEquipment:Gas | 1198.64 | 4998.41 | 01-JAN-00:10 | 74976.11 | 01-JAN-16:10 |
Gas:Plant | 4306.05 | 15908.90 | 28-JUN-08:30 | 893650.30 | 03-FEB-00:50 |
WaterSystems:Gas | 2279.80 | 15908.90 | 02-JAN-16:10 | 180196.06 | 21-FEB-21:30 |
Water Heater:WaterSystems:Gas | 2279.80 | 15908.90 | 02-JAN-16:10 | 180196.06 | 21-FEB-21:30 |
Heating:Gas | 2026.25 | 0.00 | 20-MAR-11:00 | 754576.60 | 02-FEB-06:00 |
Boiler:Heating:Gas | 2026.25 | 0.00 | 20-MAR-11:00 | 754576.60 | 02-FEB-06:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 2567.61 | 0.00 | 01-JAN-00:10 | 679075.68 | 03-JUL-21:50 |
PlantLoopCoolingDemand:HVAC | 2567.61 | 0.00 | 01-JAN-00:10 | 679075.68 | 03-JUL-21:50 |
CoolingCoils:PlantLoopCoolingDemand | 2567.61 | 0.00 | 01-JAN-00:10 | 679075.68 | 03-JUL-21:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:Water | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:Water | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-18:10 |
MainsWater:Facility | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
MainsWater:Plant | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
WaterSystems:MainsWater | 22864.31 | 0.00 | 02-JAN-01:10 | 0.00 | 02-JAN-21:10 |
Water Heater:WaterSystems:MainsWater | 18749.60 | 0.00 | 02-JAN-01:10 | 0.00 | 22-MAY-18:10 |
WaterUse:WaterSystems:Water | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:40 |
WaterUse:WaterSystems:MainsWater | 4114.71 | 0.00 | 02-JAN-01:10 | 0.00 | 05-JAN-07:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 22233.24 | 148174.61 | 08-NOV-14:40 | 2833661.82 | 26-JUL-18:20 |
EnergyTransfer:Building | 4716.57 | 64603.52 | 06-JAN-11:10 | 317033.58 | 26-JUN-18:10 |
EnergyTransfer:Zone:KITCHEN_FLR_6 | 710.44 | 8550.83 | 05-FEB-04:00 | 35682.51 | 29-JUL-10:50 |
Refrigeration:EnergyTransfer | 180.01 | 982.55 | 02-FEB-04:00 | 10338.63 | 12-SEP-06:30 |
Refrigeration:EnergyTransfer:Zone:KITCHEN_FLR_6 | 90.00 | 491.28 | 02-FEB-04:00 | 5169.32 | 12-SEP-06:30 |
EnergyTransfer:Plant | 8450.29 | 20936.14 | 06-OCT-13:10 | 1560275.36 | 26-JUL-18:20 |
LowTempRefrigeration:Refrigeration:EnergyTransfer | 21.53 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
MedTempRefrigeration:Refrigeration:EnergyTransfer | 68.47 | 290.04 | 02-FEB-06:00 | 2537.77 | 06-JUN-13:10 |
PlantLoopHeatingDemand:Facility | 2364.28 | 9853.65 | 30-AUG-00:10 | 662219.32 | 02-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 847.75 | 9827.75 | 26-AUG-00:10 | 63662.39 | 17-FEB-07:10 |
WaterSystems:PlantLoopHeatingDemand | 847.75 | 9827.75 | 26-AUG-00:10 | 63662.39 | 17-FEB-07:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Zone:BASEMENT | 401.57 | 26.97 | 05-FEB-19:50 | 38439.88 | 25-NOV-21:40 |
Heating:EnergyTransfer | 344.95 | 0.00 | 12-JAN-14:40 | 118461.48 | 12-DEC-16:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.34 | 0.00 | 01-JAN-00:10 | 7601.86 | 04-FEB-11:30 |
Cooling:EnergyTransfer | 4281.61 | 13518.19 | 04-FEB-11:20 | 313417.04 | 26-JUN-18:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 401.23 | 0.00 | 31-JAN-11:50 | 38439.88 | 25-NOV-21:40 |
EnergyTransfer:Zone:RETAIL_1_FLR_1 | 35.94 | 0.01 | 23-APR-00:40 | 3946.11 | 20-OCT-12:50 |
Heating:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 7.11 | 0.00 | 02-JAN-09:40 | 2835.71 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:RETAIL_1_FLR_1 | 28.82 | 0.00 | 01-JAN-00:10 | 3946.11 | 20-OCT-12:50 |
EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.56 | 1.11 | 06-FEB-13:30 | 1828.55 | 02-FEB-06:00 |
Heating:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 0.10 | 0.00 | 01-JAN-00:10 | 1232.85 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:RETAIL_2_FLR_1 | 33.46 | 0.00 | 06-JAN-10:50 | 1828.55 | 02-FEB-06:00 |
EnergyTransfer:Zone:MECH_FLR_1 | 27.08 | 0.10 | 25-DEC-06:30 | 1993.02 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:MECH_FLR_1 | 1.10 | 0.00 | 01-JAN-00:10 | 1993.02 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:MECH_FLR_1 | 25.98 | 0.00 | 03-JAN-01:20 | 1521.06 | 30-JUN-21:00 |
EnergyTransfer:Zone:STORAGE_FLR_1 | 11.78 | 0.02 | 11-MAR-10:40 | 1183.00 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:STORAGE_FLR_1 | 2.77 | 0.00 | 12-JAN-12:40 | 1183.00 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:STORAGE_FLR_1 | 9.01 | 0.00 | 01-JAN-00:10 | 624.62 | 30-JUN-21:10 |
EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.31 | 3826.58 | 04-FEB-11:20 | 38247.46 | 26-JUN-20:00 |
Heating:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 266.47 | 04-FEB-11:20 |
Cooling:EnergyTransfer:Zone:LAUNDRY_FLR_1 | 595.31 | 3560.10 | 04-FEB-11:20 | 38247.46 | 26-JUN-20:00 |
EnergyTransfer:Zone:CAFE_FLR_1 | 186.41 | 1.79 | 16-JAN-14:30 | 14178.50 | 04-NOV-12:40 |
Heating:EnergyTransfer:Zone:CAFE_FLR_1 | 1.30 | 0.00 | 01-JAN-00:10 | 6372.60 | 20-JAN-08:00 |
Cooling:EnergyTransfer:Zone:CAFE_FLR_1 | 185.11 | 0.00 | 01-JAN-13:40 | 14178.50 | 04-NOV-12:40 |
EnergyTransfer:Zone:LOBBY_FLR_1 | 742.81 | 48.76 | 26-NOV-13:20 | 39808.23 | 02-FEB-06:00 |
Heating:EnergyTransfer:Zone:LOBBY_FLR_1 | 0.63 | 0.00 | 01-JAN-00:10 | 20113.69 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:LOBBY_FLR_1 | 742.17 | 0.00 | 06-JAN-10:50 | 39808.23 | 02-FEB-06:00 |
EnergyTransfer:Zone:ROOM_1_FLR_3 | 61.52 | 0.00 | 01-JAN-08:10 | 11307.95 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_3 | 29.55 | 0.00 | 01-JAN-08:10 | 7886.05 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_3 | 31.97 | 0.00 | 01-JAN-00:10 | 11307.95 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_3 | 57.85 | 0.00 | 01-JAN-08:10 | 10959.16 | 25-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_3 | 35.06 | 0.00 | 01-JAN-08:10 | 8077.19 | 04-FEB-19:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_3 | 22.80 | 0.00 | 01-JAN-00:10 | 10959.16 | 25-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 208.75 | 0.00 | 01-JAN-00:10 | 51289.02 | 20-OCT-12:30 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 10.84 | 0.00 | 01-JAN-00:10 | 20993.03 | 19-JAN-06:00 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT19_FLR_3 | 197.91 | 0.00 | 01-JAN-00:10 | 51289.02 | 20-OCT-12:30 |
EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 366.44 | 0.00 | 01-JAN-08:10 | 73803.58 | 18-JUN-20:20 |
Heating:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 86.86 | 0.00 | 01-JAN-08:10 | 44483.19 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_4_MULT19_FLR_3 | 279.57 | 0.00 | 01-JAN-00:10 | 73803.58 | 18-JUN-20:20 |
EnergyTransfer:Zone:ROOM_5_FLR_3 | 60.42 | 0.00 | 01-JAN-08:10 | 10030.02 | 25-JUN-08:10 |
Heating:EnergyTransfer:Zone:ROOM_5_FLR_3 | 29.57 | 0.00 | 01-JAN-08:10 | 7772.92 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_5_FLR_3 | 30.86 | 0.00 | 01-JAN-00:10 | 10030.02 | 25-JUN-08:10 |
EnergyTransfer:Zone:ROOM_6_FLR_3 | 58.25 | 0.00 | 01-JAN-08:10 | 11438.77 | 25-JUN-08:20 |
Heating:EnergyTransfer:Zone:ROOM_6_FLR_3 | 35.15 | 0.00 | 01-JAN-08:10 | 8001.55 | 04-FEB-16:10 |
Cooling:EnergyTransfer:Zone:ROOM_6_FLR_3 | 23.10 | 0.00 | 01-JAN-00:10 | 11438.77 | 25-JUN-08:20 |
EnergyTransfer:Zone:CORRIDOR_FLR_3 | 111.30 | 0.26 | 20-OCT-06:30 | 9354.67 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 36.85 | 0.00 | 02-JAN-12:10 | 9354.67 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_3 | 74.44 | 0.00 | 01-JAN-00:10 | 6729.65 | 08-SEP-14:00 |
EnergyTransfer:Zone:ROOM_1_FLR_6 | 19.51 | 0.00 | 01-JAN-08:10 | 3204.58 | 05-JUL-18:10 |
Heating:EnergyTransfer:Zone:ROOM_1_FLR_6 | 10.31 | 0.00 | 01-JAN-08:10 | 2363.13 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_1_FLR_6 | 9.20 | 0.00 | 01-JAN-00:10 | 3204.58 | 05-JUL-18:10 |
EnergyTransfer:Zone:ROOM_2_FLR_6 | 18.93 | 0.00 | 01-JAN-08:10 | 3132.37 | 25-JUN-18:10 |
Heating:EnergyTransfer:Zone:ROOM_2_FLR_6 | 12.03 | 0.00 | 01-JAN-08:10 | 2366.49 | 11-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_2_FLR_6 | 6.90 | 0.00 | 01-JAN-00:10 | 3132.37 | 25-JUN-18:10 |
EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 83.91 | 0.00 | 01-JAN-08:10 | 13867.88 | 06-SEP-15:10 |
Heating:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 29.16 | 0.00 | 01-JAN-08:10 | 10272.54 | 09-DEC-16:20 |
Cooling:EnergyTransfer:Zone:ROOM_3_MULT9_FLR_6 | 54.75 | 0.00 | 01-JAN-00:10 | 13867.88 | 06-SEP-15:10 |
EnergyTransfer:Zone:BANQUET_FLR_6 | 406.40 | 48.84 | 31-JAN-13:10 | 21726.11 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:BANQUET_FLR_6 | 0.05 | 0.00 | 01-JAN-00:10 | 4982.45 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:BANQUET_FLR_6 | 406.35 | 0.00 | 31-JAN-11:40 | 21726.11 | 26-JUN-21:10 |
EnergyTransfer:Zone:DINING_FLR_6 | 449.78 | 79.85 | 04-FEB-13:30 | 23318.22 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:DINING_FLR_6 | 0.03 | 0.00 | 01-JAN-00:10 | 4516.50 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:DINING_FLR_6 | 449.75 | 0.00 | 31-JAN-11:40 | 23318.22 | 26-JUN-21:10 |
Heating:EnergyTransfer:Zone:KITCHEN_FLR_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:KITCHEN_FLR_6 | 620.43 | 6567.39 | 05-FEB-04:00 | 30625.52 | 29-JUL-10:50 |
EnergyTransfer:Zone:CORRIDOR_FLR_6 | 68.60 | 0.17 | 03-APR-18:50 | 6787.75 | 04-FEB-11:30 |
Heating:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 16.12 | 0.00 | 02-JAN-10:30 | 6787.75 | 04-FEB-11:30 |
Cooling:EnergyTransfer:Zone:CORRIDOR_FLR_6 | 52.47 | 0.00 | 01-JAN-00:10 | 4155.50 | 30-JUN-15:30 |
WaterSystems:EnergyTransfer | 847.75 | 9827.75 | 26-AUG-00:10 | 63662.39 | 17-FEB-07:10 |
WaterUse:WaterSystems:EnergyTransfer | 847.75 | 9827.75 | 26-AUG-00:10 | 63662.39 | 17-FEB-07:10 |
EnergyTransfer:HVAC | 9066.38 | 3776.79 | 29-APR-11:50 | 980680.15 | 26-JUL-18:20 |
HeatingCoils:EnergyTransfer | 1516.53 | 0.00 | 20-MAR-11:00 | 608865.40 | 02-FEB-06:00 |
PlantLoopHeatingDemand:HVAC | 1516.53 | 0.00 | 20-MAR-11:00 | 608865.40 | 02-FEB-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 1516.53 | 0.00 | 20-MAR-11:00 | 608865.40 | 02-FEB-06:00 |
CoolingCoils:EnergyTransfer | 2567.61 | 0.00 | 01-JAN-00:10 | 679075.68 | 03-JUL-21:50 |
HeatRecoveryForHeating:EnergyTransfer | 4683.72 | 0.00 | 05-JAN-08:00 | 544746.04 | 08-DEC-21:00 |
HeatRecoveryForCooling:EnergyTransfer | 298.52 | 0.00 | 01-JAN-00:10 | 318606.84 | 04-AUG-16:00 |
Boilers:EnergyTransfer | 1512.41 | 0.00 | 20-MAR-11:00 | 605139.15 | 02-FEB-06:00 |
Chillers:EnergyTransfer | 2599.22 | 0.00 | 01-JAN-00:10 | 678863.62 | 03-JUL-21:50 |
HeatRejection:EnergyTransfer | 3400.91 | 0.00 | 01-JAN-00:10 | 857138.34 | 26-JUL-18:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.343 | -401.233 | 0.000 | 0.000 | 147.106 | 165.597 | 143.109 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.922 |
RETAIL_1_FLR_1 | 0.000 | 0.000 | 7.115 | -28.823 | 0.000 | 0.000 | 15.961 | 8.422 | 10.186 | 20.471 | 0.000 | 0.241 | 0.000 | 0.000 | -14.254 | 0.000 | -11.732 | -7.587 |
RETAIL_2_FLR_1 | 0.000 | 0.000 | 0.099 | -33.463 | 0.000 | 0.000 | 17.544 | 9.753 | 11.795 | 0.000 | 0.000 | 0.054 | 0.000 | 0.000 | 0.000 | 0.000 | -2.576 | -3.206 |
LAUNDRY_FLR_1 | 0.000 | 0.000 | 0.001 | -595.314 | 0.000 | 0.000 | 11.628 | 3.975 | 658.148 | 0.000 | 0.000 | 0.199 | 0.000 | 0.000 | 0.000 | 0.000 | -8.079 | -70.558 |
CAFE_FLR_1 | 0.000 | 0.000 | 1.305 | -185.111 | 0.000 | 0.000 | 198.125 | 10.673 | 14.341 | 56.762 | 0.000 | 0.560 | 0.000 | 0.000 | -41.933 | 0.000 | -31.053 | -23.669 |
LOBBY_FLR_1 | 0.000 | 0.000 | 0.634 | -742.176 | 0.000 | 0.000 | 575.350 | 155.176 | 149.002 | 75.144 | 0.000 | 1.246 | 0.000 | 0.000 | -56.847 | 0.000 | -63.197 | -94.331 |
ROOM_1_FLR_3 | 29.549 | -20.735 | 0.000 | -11.234 | 0.000 | 0.000 | 9.760 | 10.355 | 10.478 | 39.471 | 0.000 | 0.626 | 0.000 | 0.000 | -33.387 | 0.000 | -14.439 | -20.444 |
ROOM_2_FLR_3 | 35.059 | -11.091 | 0.000 | -11.702 | 0.000 | 0.000 | 9.630 | 10.354 | 10.477 | 28.349 | 0.000 | 0.310 | 0.000 | 0.000 | -35.660 | 0.000 | -14.795 | -20.930 |
ROOM_3_MULT19_FLR_3 | 10.834 | -185.595 | 0.006 | -12.312 | 0.000 | 0.000 | 0.000 | 123.647 | 194.997 | 228.391 | 0.000 | 0.286 | 0.001 | 0.000 | -202.749 | 0.000 | -83.870 | -73.634 |
ROOM_4_MULT19_FLR_3 | 86.863 | -123.366 | 0.000 | -156.189 | 0.000 | 0.000 | 183.679 | 123.681 | 195.050 | 67.266 | 0.000 | 3.346 | 0.000 | 0.000 | -203.203 | 0.000 | -90.437 | -86.690 |
ROOM_5_FLR_3 | 29.565 | -19.618 | 0.000 | -11.239 | 0.000 | 0.000 | 9.756 | 10.355 | 10.478 | 38.171 | 0.000 | 0.628 | 0.000 | 0.000 | -32.794 | 0.000 | -14.476 | -20.826 |
ROOM_6_FLR_3 | 35.146 | -11.528 | 0.000 | -11.570 | 0.000 | 0.000 | 9.675 | 10.354 | 10.477 | 26.992 | 0.000 | 0.345 | 0.000 | 0.000 | -34.821 | 0.000 | -14.790 | -20.280 |
ROOM_1_FLR_6 | 10.309 | -6.396 | 0.000 | -2.807 | 0.000 | 0.000 | 2.442 | 2.589 | 2.620 | 9.805 | 0.000 | 0.169 | 0.000 | 0.000 | -8.379 | 0.000 | -3.650 | -6.701 |
ROOM_2_FLR_6 | 12.032 | -3.940 | 0.000 | -2.957 | 0.000 | 0.000 | 2.398 | 2.588 | 2.619 | 7.005 | 0.000 | 0.076 | 0.000 | 0.000 | -8.979 | 0.000 | -3.722 | -7.119 |
ROOM_3_MULT9_FLR_6 | 29.162 | -36.564 | 0.000 | -18.184 | 0.000 | 0.000 | 21.873 | 14.646 | 23.098 | 52.681 | 0.000 | 1.180 | 0.000 | 0.000 | -38.919 | 0.000 | -17.860 | -31.113 |
BANQUET_FLR_6 | 0.000 | 0.000 | 0.052 | -406.354 | 0.000 | 0.000 | 322.570 | 23.417 | 175.857 | 7.011 | 0.000 | 0.126 | 0.000 | 0.000 | -26.212 | 0.000 | -9.497 | -86.968 |
DINING_FLR_6 | 0.000 | 0.000 | 0.027 | -449.752 | 0.000 | 0.000 | 320.378 | 23.417 | 175.857 | 6.752 | 0.000 | 0.118 | 0.000 | 0.000 | -26.926 | 0.000 | -9.582 | -40.288 |
KITCHEN_FLR_6 | 0.000 | 0.000 | 0.000 | -620.415 | 0.000 | 0.000 | 29.023 | 12.972 | 550.372 | 18.114 | 0.000 | 0.094 | 35.568 | 0.000 | -17.155 | 0.000 | -8.574 | 0.000 |
MECH_FLR_1 | 0.000 | 0.000 | 1.103 | -25.980 | 0.000 | 0.000 | 0.000 | 18.484 | 12.472 | 0.000 | 0.000 | 0.130 | 0.000 | 0.000 | 0.000 | 0.000 | -5.480 | -0.729 |
STORAGE_FLR_1 | 0.000 | 0.000 | 2.771 | -9.009 | 0.000 | 0.000 | 0.000 | 2.298 | 3.598 | 0.000 | 0.000 | 0.090 | 4.022 | 0.000 | 0.000 | 0.000 | -3.770 | -0.000 |
CORRIDOR_FLR_3 | 0.000 | 0.000 | 36.855 | -74.444 | 0.000 | 0.000 | 0.000 | 66.043 | 0.000 | 35.004 | 0.000 | 0.496 | 0.001 | 0.000 | -41.385 | 0.000 | -16.476 | -6.092 |
CORRIDOR_FLR_6 | 0.000 | 0.000 | 16.124 | -52.473 | 0.000 | 0.000 | 0.000 | 17.474 | 0.000 | 16.991 | 0.000 | 0.150 | 27.877 | 0.000 | -18.761 | 0.000 | -7.383 | -0.000 |
Total Facility | 278.517 | -418.833 | 66.434 | -3862.742 | 0.000 | 0.000 | 1886.899 | 826.272 | 2365.030 | 734.379 | 0.000 | 10.468 | 67.470 | 0.000 | -842.366 | 0.000 | -435.437 | -676.089 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-NOV-21:33 | 0.00 | 0.00 | 0.00 | -38793.22 | 0.00 | 0.00 | 5670.23 | 10532.52 | 8111.60 | 0.00 | 0.00 | 0.00 | 14478.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
RETAIL_1_FLR_1 | 20-OCT-12:50 | 0.00 | 0.00 | 0.00 | -3946.10 | 0.00 | 0.00 | 150.60 | 191.32 | 252.59 | 6800.61 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -51.40 | -3397.61 |
RETAIL_2_FLR_1 | 25-NOV-21:11 | 0.00 | 0.00 | 0.00 | -2297.48 | 0.00 | 0.00 | 725.41 | 620.33 | 668.57 | 0.00 | 0.00 | 0.00 | 531.17 | 0.00 | -0.00 | 0.00 | -248.00 | 0.00 |
LAUNDRY_FLR_1 | 05-JAN-21:32 | 0.00 | 0.00 | 0.00 | -40039.29 | 0.00 | 0.00 | 488.92 | 288.96 | 41967.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -801.19 | -1905.23 |
CAFE_FLR_1 | 04-NOV-12:40 | 0.00 | 0.00 | 0.00 | -14177.49 | 0.00 | 0.00 | 2968.72 | 79.38 | 355.63 | 19729.10 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -613.22 | -8342.13 |
LOBBY_FLR_1 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -54170.42 | 0.00 | 0.00 | 31424.81 | 2238.91 | 2639.27 | 0.00 | 0.00 | 0.00 | 30786.43 | 0.00 | -7014.24 | 0.00 | -5904.76 | 0.00 |
ROOM_1_FLR_3 | 20-MAY-18:01 | 0.00 | -15414.28 | 0.00 | -511.52 | 0.00 | 0.00 | 283.21 | 1034.95 | 484.65 | 4990.80 | 0.00 | 0.00 | 9331.77 | 0.00 | -0.00 | 0.00 | -199.58 | 0.00 |
ROOM_2_FLR_3 | 21-MAY-19:01 | 0.00 | -17584.05 | 0.00 | -693.17 | 0.00 | 0.00 | 231.25 | 1034.83 | 653.15 | 1619.95 | 0.00 | 0.00 | 15009.18 | 0.00 | -0.00 | 0.00 | -271.15 | 0.00 |
ROOM_3_MULT19_FLR_3 | 20-OCT-12:30 | 0.00 | -51289.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.38 | 2352.88 | 82307.02 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -727.74 | -33414.78 |
ROOM_4_MULT19_FLR_3 | 30-APR-18:01 | 0.00 | -81431.01 | 0.00 | -6923.76 | 0.00 | 0.00 | 5435.31 | 12361.51 | 9021.83 | 0.00 | 0.00 | 0.00 | 62782.93 | 0.00 | -201.35 | 0.00 | -1045.46 | 0.00 |
ROOM_5_FLR_3 | 26-APR-08:61 | 0.00 | -13564.84 | 0.00 | -495.01 | 0.00 | 0.00 | 87.14 | 452.79 | 453.05 | 9240.72 | 0.00 | 0.00 | 4390.69 | 0.00 | -0.00 | 0.00 | -564.53 | 0.00 |
ROOM_6_FLR_3 | 20-JUN-08:11 | 0.00 | -14473.09 | 0.00 | -972.32 | 0.00 | 0.00 | 66.14 | 452.74 | 452.99 | 9530.76 | 0.00 | 0.00 | 5083.23 | 0.00 | -0.00 | 0.00 | -140.45 | 0.00 |
ROOM_1_FLR_6 | 20-MAY-18:01 | 0.00 | -4017.23 | 0.00 | -128.27 | 0.00 | 0.00 | 70.80 | 258.74 | 121.16 | 1235.15 | 0.00 | 0.00 | 2510.11 | 0.00 | -0.00 | 0.00 | -50.46 | 0.00 |
ROOM_2_FLR_6 | 20-MAY-18:01 | 0.00 | -4850.03 | 0.00 | -193.24 | 0.00 | 0.00 | 50.76 | 258.71 | 121.15 | 1224.34 | 0.00 | 0.00 | 3462.98 | 0.00 | -0.00 | 0.00 | -74.67 | 0.00 |
ROOM_3_MULT9_FLR_6 | 30-JAN-16:02 | 0.00 | -14664.30 | 0.00 | -2804.73 | 0.00 | 0.00 | 539.54 | 117.11 | 441.28 | 2158.98 | 0.00 | 0.00 | 15891.27 | 0.00 | -0.00 | 0.00 | -1679.15 | 0.00 |
BANQUET_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -31306.74 | 0.00 | 0.00 | 17724.69 | 380.20 | 2249.30 | 0.00 | 0.00 | 0.00 | 14760.66 | 0.00 | -2944.57 | 0.00 | -863.54 | 0.00 |
DINING_FLR_6 | 19-JAN-01:51 | 0.00 | 0.00 | 0.00 | -33206.69 | 0.00 | 0.00 | 17469.38 | 380.20 | 2249.30 | 0.00 | 0.00 | 0.00 | 16960.67 | 0.00 | -2984.75 | 0.00 | -868.11 | 0.00 |
KITCHEN_FLR_6 | 29-JUL-10:50 | 0.00 | 0.00 | 0.00 | -30623.05 | 0.00 | 0.00 | 464.27 | 294.67 | 24259.91 | 2546.17 | 0.00 | 27.30 | 3030.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 30-JUN-21:00 | 0.00 | 0.00 | 0.00 | -1521.03 | 0.00 | 0.00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -10.76 | -607.08 |
STORAGE_FLR_1 | 30-JUN-21:10 | 0.00 | 0.00 | 0.00 | -624.60 | 0.00 | 0.00 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 326.58 | 0.00 | -0.00 | 0.00 | -5.68 | 0.00 |
CORRIDOR_FLR_3 | 08-SEP-14:00 | 0.00 | 0.00 | 0.00 | -6729.61 | 0.00 | 0.00 | 0.00 | 1500.21 | 0.00 | 7297.36 | 0.00 | 275.24 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2343.19 |
CORRIDOR_FLR_6 | 30-JUN-15:02 | 0.00 | 0.00 | 0.00 | -4162.65 | 0.00 | 0.00 | 0.00 | 396.93 | 0.00 | 1603.45 | 0.00 | 78.68 | 2083.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 26-JUN-18:02 | 0.00 | -165835.49 | 0.00 | -188260.46 | 0.00 | 0.00 | 70851.88 | 62499.10 | 120482.43 | 51607.47 | 0.00 | 4401.12 | 44253.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 04-FEB-11:21 | 0.00 | 0.00 | 8336.63 | -0.00 | 0.00 | 0.00 | 3364.22 | 3761.61 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19011.29 |
RETAIL_1_FLR_1 | 20-JAN-07:51 | 0.00 | 0.00 | 2928.20 | -0.00 | 0.00 | 0.00 | 418.77 | 382.63 | 433.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1498.75 | 0.00 | -1061.05 | -1602.81 |
RETAIL_2_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1314.62 | -0.00 | 0.00 | 0.00 | 388.01 | 221.55 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -209.50 | -2007.18 |
LAUNDRY_FLR_1 | 04-FEB-11:11 | 0.00 | 0.00 | 2513.38 | -0.00 | 0.00 | 0.00 | 265.62 | 90.30 | 16320.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -662.55 | -18527.58 |
CAFE_FLR_1 | 20-JAN-07:51 | 0.00 | 0.00 | 6998.73 | -0.00 | 0.00 | 0.00 | 5167.35 | 627.86 | 609.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4391.48 | 0.00 | -2784.19 | -6227.91 |
LOBBY_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 22430.90 | -0.00 | 0.00 | 0.00 | 12449.40 | 3209.11 | 3694.97 | 23283.25 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5230.31 | -59837.32 |
ROOM_1_FLR_3 | 02-FEB-08:05 | 8836.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.91 | 452.79 | 453.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4337.51 | 0.00 | -1835.78 | -3796.13 |
ROOM_2_FLR_3 | 02-FEB-11:03 | 9094.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.15 | 64.68 | 126.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3349.41 | 0.00 | -1640.12 | -4403.26 |
ROOM_3_MULT19_FLR_3 | 19-JAN-06:00 | 20992.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1699.24 | 3333.24 | 0.00 | 0.00 | 0.00 | 3510.60 | 0.00 | -22324.68 | 0.00 | -7210.93 | 0.00 |
ROOM_4_MULT19_FLR_3 | 03-FEB-11:01 | 49416.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2085.98 | 772.59 | 2353.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15235.52 | 0.00 | -8200.11 | -31193.23 |
ROOM_5_FLR_3 | 09-DEC-16:13 | 7994.11 | 342.17 | 0.00 | -342.17 | 0.00 | 0.00 | 149.98 | 64.68 | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3663.95 | 0.00 | -1203.66 | -3562.42 |
ROOM_6_FLR_3 | 03-FEB-18:02 | 8781.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.68 | 698.51 | 505.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4275.75 | 0.00 | -1491.70 | -4506.60 |
ROOM_1_FLR_6 | 02-FEB-08:05 | 2440.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.89 | 113.20 | 113.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1100.29 | 0.00 | -459.58 | -1164.43 |
ROOM_2_FLR_6 | 02-FEB-11:03 | 2615.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 | 16.17 | 31.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -857.60 | 0.00 | -410.43 | -1422.16 |
ROOM_3_MULT9_FLR_6 | 09-DEC-16:13 | 10490.01 | 524.99 | 0.00 | -524.99 | 0.00 | 0.00 | 341.60 | 91.49 | 487.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4095.75 | 0.00 | -1380.38 | -5934.70 |
BANQUET_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 6123.44 | -0.00 | 0.00 | 0.00 | 6917.41 | 380.20 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1421.62 | 0.00 | -780.13 | -17967.20 |
DINING_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 5780.69 | -0.00 | 0.00 | 0.00 | 6801.47 | 380.20 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1454.67 | 0.00 | -786.79 | -17468.81 |
KITCHEN_FLR_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MECH_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 2035.08 | -0.00 | 0.00 | 0.00 | 0.00 | 419.88 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -445.88 | -2318.35 |
STORAGE_FLR_1 | 04-FEB-11:21 | 0.00 | 0.00 | 1194.65 | -0.00 | 0.00 | 0.00 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -308.08 | -1027.98 |
CORRIDOR_FLR_3 | 04-FEB-11:21 | 0.00 | 0.00 | 9506.71 | -0.00 | 0.00 | 0.00 | 0.00 | 1500.21 | 0.00 | 7063.81 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1475.07 | -16595.65 |
CORRIDOR_FLR_6 | 04-FEB-11:21 | 0.00 | 0.00 | 6893.93 | -0.00 | 0.00 | 0.00 | 0.00 | 396.93 | 0.00 | 4151.67 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -619.24 | -10823.29 |
Total Facility | 04-FEB-19:02 | 36454.28 | 60864.98 | 33805.59 | -60864.98 | 0.00 | 0.00 | 71003.26 | 65247.88 | 113378.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -88426.50 | 0.00 | -34257.45 | -197205.54 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 21.3200 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 21.0406 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0512 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV WITH REHEAT | 11.6620 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 11.6620 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
FLR_3_DOAS | 2.0508 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0508 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | VAV WITH REHEAT | 0.000000 | 106.4990 | 0.000432 | 1978.83 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | 0.000000 | 10.8290 | 0.001181 | 67.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | 0.000000 | 12.5400 | 0.001181 | 77.67 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | 0.000000 | 8.4000 | 0.000000 | 78.04 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | 0.000000 | 142.3000 | 0.003580 | 188.86 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | 0.000000 | 422.4350 | 0.001447 | 1308.19 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1863.81 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.000000 | 114.0000 | 0.000449 | 1864.32 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.09 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.000000 | 6.0000 | 0.000395 | 156.07 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.000000 | 1.5000 | 0.000395 | 39.02 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.000000 | 13.5000 | 0.000449 | 220.77 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
BANQUET_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DINING_FLR_6 | VAV WITH REHEAT | 0.000000 | 249.8960 | 0.003580 | 331.66 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | 0.000000 | 22.2380 | 0.003555 | 103.30 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
MECH_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000000 | 164.24 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000609 | 94.76 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 1557.62 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | 0.000000 | 0.0000 | 0.000305 | 412.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV WITH REHEAT | 0.00 | 0.001045 | 6694.0231 | 0.0000 | 0.0000 | 0.0000 | |
FLR_3_DOAS | 0.00 | 0.000441 | 4651.2638 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5235 | 2.5235 | 1.3804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3180 | 0.3180 | 0.1740 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2289 | 0.2289 | 0.1252 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4059 | 3.4059 | 1.8630 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3229 | 1.3229 | 0.7236 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7493 | 4.7493 | 2.5979 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0990 | 2.0990 | 1.1481 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2037 | 2.2037 | 1.2054 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3513 | 2.3513 | 1.2862 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2269 | 0.2269 | 0.1241 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0967 | 0.0967 | 0.0529 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1869 | 1.1869 | 0.6492 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6069 | 0.6069 | 0.3320 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 21.3200 | 21.0406 | 21.3200 | 11.6620 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0512 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3804 | 1.3804 | 1.3804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_1_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1740 | 0.1740 | 0.1740 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
RETAIL_2_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1252 | 0.1252 | 0.1252 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LAUNDRY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8630 | 1.8630 | 1.8630 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CAFE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7236 | 0.7236 | 0.7236 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LOBBY_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5979 | 2.5979 | 2.5979 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
ROOM_1_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_4_MULT19_FLR_3 | FLR_3_DOAS | 0.8370 | 0.8370 | 0.8370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_5_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_6_FLR_3 | FLR_3_DOAS | 0.0617 | 0.0617 | 0.0617 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_1_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_2_FLR_6 | FLR_3_DOAS | 0.0154 | 0.0154 | 0.0154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
ROOM_3_MULT9_FLR_6 | FLR_3_DOAS | 0.0991 | 0.0991 | 0.0991 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
BANQUET_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1481 | 1.1481 | 1.1481 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DINING_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2054 | 1.2054 | 1.2054 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
KITCHEN_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2862 | 1.2862 | 1.2862 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
MECH_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1241 | 0.1241 | 0.1241 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
STORAGE_FLR_1 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.0529 | 0.0529 | 0.0529 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_3 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6492 | 0.6492 | 0.6492 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORRIDOR_FLR_6 | VAV WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3320 | 0.3320 | 0.3320 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV WITH REHEAT | 11.6620 | 11.6620 | 11.6620 | 11.6620 | 0.0000 | 1.0000 |
FLR_3_DOAS | 2.0508 | 2.0508 | 2.0508 | 2.0508 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:46:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 11345.29 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 1978.83 | 1978.83 | 0.00 | 168.00 |
RETAIL_1_FLR_1 | 67.07 | 67.07 | 0.00 | 168.00 |
RETAIL_2_FLR_1 | 77.67 | 77.67 | 0.00 | 168.00 |
LAUNDRY_FLR_1 | 78.04 | 78.04 | 0.00 | 168.00 |
CAFE_FLR_1 | 188.86 | 188.86 | 0.00 | 168.00 |
LOBBY_FLR_1 | 1308.19 | 1308.19 | 0.00 | 168.00 |
ROOM_1_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT19_FLR_3 | 24.52 | 24.52 | 0.00 | 0.00 |
ROOM_4_MULT19_FLR_3 | 24.53 | 24.53 | 0.00 | 168.00 |
ROOM_5_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_6_FLR_3 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_1_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_2_FLR_6 | 39.02 | 39.02 | 0.00 | 168.00 |
ROOM_3_MULT9_FLR_6 | 24.53 | 24.53 | 0.00 | 168.00 |
BANQUET_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
DINING_FLR_6 | 331.66 | 331.66 | 0.00 | 168.00 |
KITCHEN_FLR_6 | 103.30 | 103.30 | 0.00 | 168.00 |
MECH_FLR_1 | 164.24 | 164.24 | 0.00 | 0.00 |
STORAGE_FLR_1 | 94.76 | 94.76 | 0.00 | 0.00 |
CORRIDOR_FLR_3 | 389.40 | 389.40 | 0.00 | 0.00 |
CORRIDOR_FLR_6 | 412.12 | 412.12 | 0.00 | 0.00 |
Totals | 11345.29 | 11345.29 | 0.00 |
Data | |
Number of hours heating loads not met | 271.00 |
Number of hours cooling loads not met | 316.50 |
Number of hours not met | 587.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 2026.25 | 754576.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 801.69 | 203597.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 826.27 | 75078.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 182.61 | 11632.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 872.73 | 59188.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Cooking | 762.04 | 29240.64 | 1198.64 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInFreezer | 14.43 | 457.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ReachInRefrigerator | 8.99 | 285.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- Laundry | 0.00 | 0.00 | 590.21 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 21.81 | 1300.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 947.54 | 61110.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 2.91 | 187.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 512.52 | 28770.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 41.93 | 4681.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 207.89 | 9924.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 90.76 | 4749.05 | 2279.80 | 180196.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- General | 7.09 | 2093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- LowTempRefrigeration | 20.23 | 1941.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- MedTempRefrigeration | 33.86 | 1195.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 1719.37 | 5355.32 |
Natural Gas | 1788.85 | 6094.90 |
Additional | 0.00 | 0.00 |
Total | 3508.23 | 11450.21 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 72.83 |
Space Heating | 0.00 |
Space Cooling | 70.66 |
Fans (All) | 45.18 |
Service Water Heating | 8.00 |
Receptacle Equipment | 146.16 |
Miscellaneous (All) | 472.03 |
Subtotal | 472.03 |
Natural Gas [MJ/m2] | |
Space Heating | 178.60 |
Service Water Heating | 200.95 |
Miscellaneous (All) | 537.22 |
Subtotal | 537.22 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 7.22 |
Space Heating | 17.70 |
Space Cooling | 7.00 |
Fans (All) | 4.48 |
Service Water Heating | 20.70 |
Receptacle Equipment | 30.10 |
Miscellaneous | 12.80 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
BLDG_LIGHT_CORRIDOR_SCH | 1660. | 8760. |
BLDG_LIGHT_GUESTROOM_SCH | 2221. | 8760. |
BLDG_LIGHT_MECHANIC_SCH | 3061. | 8760. |
BLDG_LIGHT_MISC_SCH | 3061. | 8760. |
BLDG_LIGHT_OFFICE_BSMT_SCH | 2737. | 8760. |
BLDG_LIGHT_SCH | 3061. | 8760. |
BLDG_LIGHT_STORAGE_SCH | 1362. | 8760. |
WALKIN_OCC_LGHT_SCH | 1591. | 8760. |
EXTERIOR_LTG_SCH | 4380. | 4380. |
BASEMENT_EQUIP_SCH | 3737. | 8760. |
BLDG_EQUIP_SCH | 3924. | 8760. |
GUESTROOM_EQP_SCH_BASE | 3239. | 8760. |
GUESTROOM_EQP_SCH_ADVA | 2762. | 8760. |
LOBBY_EQP_SCH | 3292. | 8760. |
OFFICE_EQP_SCH | 4941. | 8760. |
EMPLOYEELOUNGE_EQP_SCH | 4044. | 8760. |
LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
MEETINGROOM_EQP_SCH | 1336. | 4745. |
EXERCISEROOM_EQP_SCH | 3832. | 5840. |
KITCHEN_ELEC_EQUIP_SCH | 2172. | 8760. |
KITCHEN_GAS_EQUIP_SCH | 1332. | 8760. |
KITCHEN_EXHAUST_SCH | 6205. | 6205. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_OCC_SCH | 5026. | 8760. |
GUESTROOM_OCC_SCH | 5515. | 8760. |
LOBBY_OCC_SCH | 2304. | 8760. |
OFFICE_OCC_SCH | 3954. | 8760. |
EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
MEETINGROOM_OCC_SCH | 1168. | 4745. |
LAUNDRYROOM_OCC_SCH | 427. | 2920. |
EXERCISEROOM_OCC_SCH | 5292. | 5840. |
INFIL_SCH | 8760. | 8760. |
INFIL_HALF_ON_SCH | 4380. | 8760. |
INFIL_QUARTER_ON_SCH | 2190. | 8760. |
LAUNDRY_SWH_SCH | 2555. | 2555. |
BLDG_SWH_SCH | 3301. | 8760. |
GUESTROOM_SWH_SCH | 2899. | 8760. |
LAUNDRYROOM_SWH_SCH | 2920. | 2920. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
ALWAYS_ON | 8760. | 8760. |
ALWAYS_OFF | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
VAC_GUESTROOM_VENTILATION_SCHEDULE | 365. | 365. |
MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
ROOM_1_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_4_MULT19_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_5_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_6_FLR_3 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_1_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_2_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
ROOM_3_MULT9_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
KITCHEN_FLR_6 WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
KITCHEN_FLR_6_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
FLR_3_DOAS_OAMINOAFRACSCHEDULE | 8760. | 8760. |
LAUNDRY_FLR_1 EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 8760. | 8760. |
KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 5740. | 6205. |
SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_30MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_30MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
HTGSETP_SCH | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 21.00 | 365 |
CLGSETP_SCH | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 24.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELLARGE
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.598065E+12 |
February | 0.000 | 0.424939E+12 |
March | 0.000 | 0.168865E+12 |
April | 0.000 | 0.783053E+11 |
May | 0.000 | 0.370813E+11 |
June | 0.000 | 0.243543E+11 |
July | 0.000 | 0.871449E+10 |
August | 0.000 | 0.125308E+11 |
September | 0.000 | 0.335371E+11 |
October | 0.000 | 0.586447E+11 |
November | 0.000 | 0.221303E+12 |
December | 0.000 | 0.359909E+12 |
Annual Sum or Average | 0.202625E+13 | |
Minimum of Months | 0.000 | 0.871449E+10 |
Maximum of Months | 0.000 | 0.598065E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350354E+11 | 38605.97 | 19-JAN-01:51 | -23.9 | -24.0 | 0.701965E+10 | 4712.55 | 04-JAN-22:10 | -17.1 | -17.4 |
February | 0.280399E+11 | 33783.49 | 02-FEB-06:02 | -36.7 | -36.8 | 0.567487E+10 | 4521.81 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.282899E+11 | 12967.71 | 25-MAR-15:00 | 18.90 | 10.41 | 0.692877E+10 | 4449.74 | 01-MAR-22:10 | -4.4 | -5.1 |
April | 0.264079E+11 | 13985.07 | 15-APR-21:10 | 22.52 | 16.91 | 0.637219E+10 | 4176.52 | 07-APR-21:10 | 7.17 | 3.64 |
May | 0.298178E+11 | 14348.88 | 31-MAY-21:10 | 21.80 | 16.81 | 0.652413E+10 | 4197.42 | 19-MAY-21:10 | 6.97 | 4.81 |
June | 0.324162E+11 | 15286.85 | 08-JUN-20:00 | 21.10 | 15.58 | 0.633600E+10 | 4333.16 | 05-JUN-21:10 | 11.70 | 11.34 |
July | 0.362677E+11 | 15519.71 | 12-JUL-21:00 | 21.10 | 16.84 | 0.658624E+10 | 4198.20 | 11-JUL-21:10 | 15.92 | 14.61 |
August | 0.383373E+11 | 16383.03 | 09-AUG-20:00 | 21.10 | 15.58 | 0.707332E+10 | 4498.00 | 18-AUG-21:10 | 16.02 | 13.73 |
September | 0.372506E+11 | 18874.01 | 29-SEP-21:00 | 2.80 | 1.14 | 0.738281E+10 | 4837.02 | 22-SEP-21:19 | 8.87 | 5.98 |
October | 0.382129E+11 | 20162.74 | 18-OCT-21:00 | 0.00 | -1.4 | 0.811830E+10 | 4837.05 | 31-OCT-23:19 | 0.90 | -1.2 |
November | 0.363541E+11 | 38794.11 | 25-NOV-21:33 | -24.0 | -24.4 | 0.775271E+10 | 4837.04 | 01-NOV-23:19 | 5.93 | 4.73 |
December | 0.348023E+11 | 17367.82 | 07-DEC-22:00 | -7.8 | -9.6 | 0.797710E+10 | 4836.97 | 01-DEC-22:19 | -3.7 | -4.5 |
Annual Sum or Average | 0.401232E+12 | 0.837461E+11 | ||||||||
Minimum of Months | 0.264079E+11 | 12967.71 | -36.7 | -36.8 | 0.567487E+10 | 4176.52 | -17.1 | -17.4 | ||
Maximum of Months | 0.383373E+11 | 38794.11 | 22.52 | 16.91 | 0.811830E+10 | 4837.05 | 16.02 | 14.61 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319973E+09 | 2011.29 | 12-JAN-12:30 | 1.95 | 0.37 | 0.588662E+09 | 364.18 | 18-JAN-04:00 | -5.6 | -5.8 |
February | 0.576806E+09 | 2607.26 | 08-FEB-13:20 | 2.40 | 1.27 | 0.515065E+09 | 375.34 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.122640E+10 | 2136.43 | 24-MAR-13:10 | 12.38 | 6.46 | 0.631031E+09 | 403.70 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.202214E+10 | 2947.92 | 15-APR-13:20 | 28.67 | 20.38 | 0.620207E+09 | 434.98 | 18-APR-21:10 | 16.32 | 13.38 |
May | 0.334030E+10 | 2074.95 | 31-MAY-18:40 | 26.47 | 18.89 | 0.639548E+09 | 435.02 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.404393E+10 | 2206.33 | 26-JUN-18:40 | 28.87 | 21.99 | 0.643372E+09 | 462.16 | 26-JUN-21:10 | 25.40 | 21.25 |
July | 0.460476E+10 | 2180.99 | 30-JUL-13:20 | 26.87 | 20.17 | 0.670598E+09 | 451.37 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.459968E+10 | 2428.20 | 29-AUG-13:30 | 23.60 | 16.38 | 0.680069E+09 | 449.04 | 02-AUG-21:10 | 24.32 | 21.63 |
September | 0.380155E+10 | 3795.65 | 07-SEP-12:50 | 31.52 | 18.15 | 0.651889E+09 | 470.23 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.261068E+10 | 3946.11 | 20-OCT-12:50 | 21.68 | 12.53 | 0.646439E+09 | 444.22 | 20-OCT-21:10 | 13.90 | 9.44 |
November | 0.115719E+10 | 3572.03 | 04-NOV-13:10 | 13.98 | 6.79 | 0.602780E+09 | 407.40 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.519227E+09 | 2994.65 | 03-DEC-13:00 | 5.60 | 2.40 | 0.622870E+09 | 364.17 | 12-DEC-00:10 | -20.0 | -20.3 |
Annual Sum or Average | 0.288226E+11 | 0.751253E+10 | ||||||||
Minimum of Months | 0.319973E+09 | 2011.29 | 1.95 | 0.37 | 0.515065E+09 | 364.17 | -20.0 | -20.3 | ||
Maximum of Months | 0.460476E+10 | 3946.11 | 31.52 | 21.99 | 0.680069E+09 | 470.23 | 25.40 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.198555E+10 | 2025.02 | 05-JAN-21:23 | -23.6 | -23.9 | 0.714880E+09 | 524.59 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.205055E+10 | 1828.55 | 02-FEB-06:00 | -36.7 | -36.8 | 0.639317E+09 | 538.97 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.246149E+10 | 1270.42 | 25-MAR-15:00 | 18.90 | 10.41 | 0.807702E+09 | 560.01 | 24-MAR-21:10 | 2.43 | 0.92 |
April | 0.268823E+10 | 1562.12 | 15-APR-21:10 | 22.52 | 16.91 | 0.810534E+09 | 569.51 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.314039E+10 | 1598.98 | 31-MAY-21:10 | 21.80 | 16.81 | 0.853557E+09 | 558.32 | 22-MAY-21:10 | 9.32 | 7.91 |
June | 0.337029E+10 | 1647.26 | 30-JUN-21:10 | 22.03 | 17.03 | 0.833559E+09 | 568.73 | 30-JUN-21:10 | 22.03 | 17.03 |
July | 0.365310E+10 | 1636.98 | 03-JUL-21:10 | 24.22 | 22.81 | 0.857851E+09 | 564.33 | 03-JUL-21:10 | 24.22 | 22.81 |
August | 0.362208E+10 | 1626.04 | 22-AUG-21:00 | 22.20 | 19.97 | 0.872230E+09 | 569.41 | 04-AUG-21:10 | 18.30 | 17.90 |
September | 0.322055E+10 | 1769.75 | 07-SEP-21:00 | 22.80 | 16.43 | 0.846865E+09 | 569.55 | 08-SEP-21:30 | 17.75 | 14.82 |
October | 0.284269E+10 | 1437.85 | 20-OCT-16:00 | 21.30 | 12.70 | 0.861880E+09 | 569.51 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.237239E+10 | 2297.51 | 25-NOV-21:11 | -23.7 | -24.1 | 0.776126E+09 | 568.98 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.205592E+10 | 1080.90 | 05-DEC-22:10 | -7.1 | -9.3 | 0.763429E+09 | 518.53 | 05-DEC-22:10 | -7.1 | -9.3 |
Annual Sum or Average | 0.334632E+11 | 0.963793E+10 | ||||||||
Minimum of Months | 0.198555E+10 | 1080.90 | -36.7 | -36.8 | 0.639317E+09 | 518.53 | -7.1 | -9.3 | ||
Maximum of Months | 0.365310E+10 | 2297.51 | 24.22 | 22.81 | 0.872230E+09 | 569.55 | 24.22 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.628219E+09 | 1023.14 | 19-JAN-08:00 | -28.3 | -28.5 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.936426E+09 | 1043.57 | 02-FEB-07:20 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.157418E+10 | 1124.94 | 25-MAR-15:00 | 18.90 | 10.41 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.217436E+10 | 1411.61 | 16-APR-20:00 | 23.30 | 18.48 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.285197E+10 | 1454.92 | 31-MAY-21:00 | 22.20 | 17.23 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.314975E+10 | 1521.06 | 30-JUN-21:00 | 22.20 | 17.10 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.344047E+10 | 1506.70 | 03-JUL-21:00 | 24.40 | 22.86 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.339652E+10 | 1501.79 | 03-AUG-21:10 | 24.32 | 23.15 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.294179E+10 | 1506.08 | 07-SEP-21:00 | 22.80 | 16.43 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.245673E+10 | 1260.78 | 20-OCT-15:00 | 23.30 | 13.34 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.162912E+10 | 1169.79 | 08-NOV-22:10 | 14.40 | 12.79 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.800461E+09 | 874.02 | 04-DEC-22:10 | 1.78 | 0.08 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.259800E+11 | 0.00 | ||||||||
Minimum of Months | 0.628219E+09 | 874.02 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.344047E+10 | 1521.06 | 24.40 | 23.15 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11201006.52 | 318.39 | 13-JAN-22:00 | 2.20 | 0.77 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 54525801.92 | 341.20 | 24-FEB-22:10 | 1.93 | 1.42 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.331862E+09 | 474.32 | 25-MAR-15:00 | 18.90 | 10.41 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.679042E+09 | 580.01 | 16-APR-21:10 | 21.93 | 18.00 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.116558E+10 | 594.85 | 31-MAY-21:10 | 21.80 | 16.81 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.132078E+10 | 624.62 | 30-JUN-21:10 | 22.03 | 17.03 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.145269E+10 | 620.62 | 03-JUL-21:10 | 24.22 | 22.81 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.142873E+10 | 617.55 | 03-AUG-21:10 | 24.32 | 23.15 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.121129E+10 | 617.70 | 07-SEP-21:10 | 22.43 | 16.37 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.937554E+09 | 536.86 | 20-OCT-15:00 | 23.30 | 13.34 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.391021E+09 | 462.14 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 24389881.40 | 283.15 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.900868E+10 | 0.00 | ||||||||
Minimum of Months | 11201006.52 | 283.15 | 1.93 | 0.77 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.145269E+10 | 624.62 | 24.32 | 23.15 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.476316E+11 | 40042.47 | 05-JAN-21:32 | -23.7 | -24.0 | 0.518212E+09 | 398.72 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 0.437033E+11 | 36389.51 | 24-FEB-21:00 | 2.20 | 1.49 | 0.461192E+09 | 400.50 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.492344E+11 | 36891.84 | 28-MAR-20:00 | 11.70 | 8.26 | 0.582386E+09 | 402.79 | 24-MAR-21:10 | 2.43 | 0.92 |
April | 0.487100E+11 | 37828.56 | 18-APR-20:00 | 18.30 | 15.20 | 0.559251E+09 | 404.61 | 19-APR-21:10 | 7.62 | 3.95 |
May | 0.520197E+11 | 38077.87 | 31-MAY-20:00 | 24.40 | 17.90 | 0.567912E+09 | 403.64 | 19-MAY-21:10 | 6.97 | 4.81 |
June | 0.513222E+11 | 38247.46 | 26-JUN-20:00 | 26.70 | 21.51 | 0.536981E+09 | 401.73 | 01-JUN-21:10 | 9.90 | 8.78 |
July | 0.532363E+11 | 38115.21 | 03-JUL-20:00 | 26.70 | 23.79 | 0.545818E+09 | 381.53 | 07-JUL-21:10 | 18.22 | 16.14 |
August | 0.533253E+11 | 38129.64 | 03-AUG-20:00 | 25.00 | 23.43 | 0.551802E+09 | 381.55 | 09-AUG-21:10 | 17.62 | 14.82 |
September | 0.505374E+11 | 38219.87 | 07-SEP-20:00 | 23.90 | 17.03 | 0.546283E+09 | 403.65 | 25-SEP-21:10 | 10.00 | 6.67 |
October | 0.505991E+11 | 37632.87 | 20-OCT-20:00 | 15.00 | 9.89 | 0.582832E+09 | 403.15 | 30-OCT-21:10 | 4.78 | 3.08 |
November | 0.475627E+11 | 38369.90 | 25-NOV-21:11 | -23.7 | -24.1 | 0.552114E+09 | 403.11 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.474310E+11 | 35863.22 | 04-DEC-21:00 | 1.70 | 0.04 | 0.575614E+09 | 397.06 | 01-DEC-22:10 | -3.8 | -4.6 |
Annual Sum or Average | 0.595313E+12 | 0.658040E+10 | ||||||||
Minimum of Months | 0.437033E+11 | 35863.22 | -23.7 | -24.1 | 0.461192E+09 | 381.53 | -3.8 | -4.6 | ||
Maximum of Months | 0.533253E+11 | 40042.47 | 26.70 | 23.79 | 0.582832E+09 | 404.61 | 18.22 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.817846E+10 | 8381.50 | 12-JAN-12:30 | 1.95 | 0.37 | 0.803311E+10 | 5960.68 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.988051E+10 | 10382.23 | 08-FEB-13:20 | 2.40 | 1.27 | 0.732033E+10 | 6142.33 | 24-FEB-22:40 | 1.13 | 0.60 |
March | 0.130265E+11 | 9184.37 | 25-MAR-13:40 | 15.03 | 8.60 | 0.910445E+10 | 6451.92 | 23-MAR-21:40 | 9.07 | 5.84 |
April | 0.148327E+11 | 11571.51 | 15-APR-13:00 | 28.30 | 20.27 | 0.921240E+10 | 6462.56 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.182875E+11 | 9465.26 | 31-MAY-21:20 | 21.40 | 16.39 | 0.983895E+10 | 6450.43 | 05-MAY-22:10 | 14.03 | 10.36 |
June | 0.198514E+11 | 10465.80 | 26-JUN-21:12 | 25.20 | 21.19 | 0.971169E+10 | 6462.65 | 28-JUN-21:30 | 21.95 | 17.10 |
July | 0.216170E+11 | 10210.22 | 25-JUL-21:12 | 25.93 | 21.29 | 0.100212E+11 | 6462.59 | 25-JUL-21:30 | 25.85 | 21.21 |
August | 0.216005E+11 | 10193.84 | 02-AUG-21:12 | 24.23 | 21.62 | 0.102233E+11 | 6462.73 | 18-AUG-21:30 | 15.85 | 13.69 |
September | 0.194041E+11 | 12897.31 | 16-SEP-13:00 | 28.30 | 17.99 | 0.983223E+10 | 6462.62 | 06-SEP-21:30 | 18.60 | 16.09 |
October | 0.169302E+11 | 13935.07 | 20-OCT-12:40 | 21.57 | 12.47 | 0.983014E+10 | 6461.89 | 20-OCT-23:19 | 13.90 | 9.68 |
November | 0.121886E+11 | 14178.50 | 04-NOV-12:40 | 13.53 | 6.71 | 0.868062E+10 | 6454.91 | 03-NOV-21:40 | 5.37 | 2.99 |
December | 0.931187E+10 | 12023.24 | 03-DEC-12:50 | 5.50 | 2.39 | 0.852234E+10 | 5719.63 | 01-DEC-22:40 | -3.5 | -4.3 |
Annual Sum or Average | 0.185109E+12 | 0.110331E+12 | ||||||||
Minimum of Months | 0.817846E+10 | 8381.50 | 1.95 | 0.37 | 0.732033E+10 | 5719.63 | -3.5 | -4.3 | ||
Maximum of Months | 0.216170E+11 | 14178.50 | 28.30 | 21.62 | 0.102233E+11 | 6462.73 | 25.85 | 21.21 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479026E+11 | 54172.80 | 19-JAN-01:51 | -23.9 | -24.0 | 0.252396E+11 | 18782.60 | 13-JAN-22:40 | 1.47 | 0.51 |
February | 0.470799E+11 | 39808.23 | 02-FEB-06:00 | -36.7 | -36.8 | 0.228459E+11 | 19143.49 | 24-FEB-22:30 | 1.40 | 0.87 |
March | 0.555085E+11 | 28626.64 | 24-MAR-21:10 | 2.43 | 0.92 | 0.288160E+11 | 19183.80 | 28-MAR-21:19 | 9.63 | 7.54 |
April | 0.592413E+11 | 33184.86 | 16-APR-21:10 | 21.93 | 18.00 | 0.286599E+11 | 19185.88 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.685460E+11 | 34084.62 | 31-MAY-21:10 | 21.80 | 16.81 | 0.301665E+11 | 19186.13 | 05-MAY-21:19 | 15.20 | 10.64 |
June | 0.725412E+11 | 36047.90 | 26-JUN-21:12 | 25.20 | 21.19 | 0.292146E+11 | 19186.18 | 22-JUN-21:19 | 15.60 | 12.06 |
July | 0.779798E+11 | 35179.11 | 03-JUL-21:12 | 24.03 | 22.76 | 0.298855E+11 | 19186.10 | 28-JUL-21:30 | 19.40 | 17.20 |
August | 0.776942E+11 | 35480.49 | 22-AUG-21:12 | 21.83 | 19.96 | 0.304431E+11 | 19186.20 | 24-AUG-21:19 | 15.20 | 13.98 |
September | 0.700487E+11 | 38249.74 | 07-SEP-21:10 | 22.43 | 16.37 | 0.297138E+11 | 19186.16 | 01-SEP-21:30 | 16.95 | 12.48 |
October | 0.633979E+11 | 34616.15 | 20-OCT-21:10 | 13.90 | 9.44 | 0.305629E+11 | 19185.30 | 24-OCT-23:19 | 8.70 | 5.20 |
November | 0.539381E+11 | 48297.93 | 25-NOV-21:11 | -23.7 | -24.1 | 0.276200E+11 | 19183.45 | 03-NOV-21:10 | 5.92 | 3.48 |
December | 0.482939E+11 | 24235.82 | 05-DEC-22:10 | -7.1 | -9.3 | 0.271716E+11 | 18448.52 | 05-DEC-22:40 | -6.9 | -9.1 |
Annual Sum or Average | 0.742172E+12 | 0.340339E+12 | ||||||||
Minimum of Months | 0.470799E+11 | 24235.82 | -36.7 | -36.8 | 0.228459E+11 | 18448.52 | -6.9 | -9.1 | ||
Maximum of Months | 0.779798E+11 | 54172.80 | 25.20 | 22.76 | 0.305629E+11 | 19186.20 | 19.40 | 17.20 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3925899.91 | 3665.21 | 12-JAN-16:01 | 2.62 | 1.03 | 92667901.87 | 56.69 | 25-JAN-23:10 | -17.9 | -18.2 |
February | 33844099.90 | 3859.03 | 24-FEB-16:01 | 8.12 | 5.75 | 83841170.50 | 56.69 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.118875E+09 | 3854.94 | 25-MAR-15:01 | 18.72 | 10.43 | 95186755.28 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.537239E+09 | 3881.72 | 29-APR-18:01 | 15.03 | 9.30 | 93319620.79 | 56.69 | 16-APR-03:09 | 19.32 | 16.48 |
May | 0.892994E+09 | 3981.45 | 20-MAY-18:01 | 15.22 | 8.18 | 98134691.41 | 56.70 | 30-MAY-21:19 | 19.63 | 16.88 |
June | 0.148816E+10 | 3484.08 | 15-JUN-15:01 | 20.10 | 15.76 | 95400293.38 | 56.70 | 26-JUN-22:40 | 24.07 | 20.64 |
July | 0.182990E+10 | 3490.12 | 26-JUL-15:02 | 30.00 | 25.72 | 98829280.98 | 56.70 | 14-JUL-21:10 | 22.70 | 20.22 |
August | 0.163163E+10 | 3510.24 | 30-AUG-18:01 | 20.13 | 17.18 | 98863465.85 | 56.69 | 18-AUG-21:19 | 15.93 | 13.71 |
September | 0.107475E+10 | 3855.94 | 20-SEP-18:01 | 17.23 | 10.69 | 94847278.77 | 56.70 | 07-SEP-22:10 | 20.32 | 16.00 |
October | 0.304817E+09 | 3891.29 | 19-OCT-15:01 | 18.53 | 10.63 | 96639861.77 | 56.69 | 11-OCT-21:40 | 9.90 | 5.15 |
November | 69167606.24 | 3901.48 | 04-NOV-15:01 | 14.13 | 6.69 | 91299444.23 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 7247676.12 | 3585.88 | 01-DEC-16:01 | -2.1 | -4.2 | 93087029.83 | 56.69 | 22-DEC-03:00 | -13.3 | -13.5 |
Annual Sum or Average | 0.799254E+10 | 0.113212E+10 | ||||||||
Minimum of Months | 3925899.91 | 3484.08 | -2.1 | -4.2 | 83841170.50 | 56.69 | -24.1 | -24.4 | ||
Maximum of Months | 0.182990E+10 | 3981.45 | 30.00 | 25.72 | 98863465.85 | 56.70 | 24.07 | 20.64 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 386442.97 | 563.74 | 12-JAN-16:03 | 2.62 | 1.03 | 92265778.45 | 56.69 | 27-JAN-00:00 | -11.1 | -11.4 |
February | 11083580.85 | 3658.08 | 24-FEB-16:01 | 8.12 | 5.75 | 82714343.32 | 56.69 | 28-FEB-02:00 | -16.1 | -16.6 |
March | 55988113.64 | 3771.72 | 25-MAR-15:01 | 18.72 | 10.43 | 94314318.31 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.369729E+09 | 3872.82 | 29-APR-18:01 | 15.03 | 9.30 | 94305082.98 | 77.03 | 17-APR-18:10 | 18.03 | 11.62 |
May | 0.659642E+09 | 4569.30 | 21-MAY-19:01 | 15.03 | 8.24 | 0.101860E+09 | 78.98 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.120330E+10 | 3759.23 | 23-JUN-21:11 | 19.63 | 14.24 | 0.102803E+09 | 87.44 | 08-JUN-18:10 | 22.88 | 16.37 |
July | 0.136020E+10 | 3637.66 | 18-JUL-21:11 | 19.03 | 14.53 | 0.110627E+09 | 90.90 | 06-JUL-18:10 | 25.40 | 21.36 |
August | 0.115875E+10 | 3545.46 | 08-AUG-21:11 | 16.50 | 13.52 | 0.108506E+09 | 87.70 | 18-AUG-18:10 | 23.35 | 16.96 |
September | 0.714028E+09 | 3750.02 | 24-SEP-18:01 | 11.52 | 6.10 | 98539765.49 | 81.30 | 01-SEP-18:10 | 21.42 | 14.20 |
October | 0.136000E+09 | 3785.21 | 19-OCT-15:01 | 18.53 | 10.63 | 95808657.44 | 56.69 | 20-OCT-21:19 | 13.90 | 9.46 |
November | 28977749.25 | 3773.73 | 04-NOV-15:01 | 14.13 | 6.69 | 90570852.30 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 774738.00 | 657.92 | 01-DEC-16:03 | -2.1 | -4.2 | 92404037.56 | 56.69 | 28-DEC-04:00 | -17.2 | -17.5 |
Annual Sum or Average | 0.569886E+10 | 0.116472E+10 | ||||||||
Minimum of Months | 386442.97 | 563.74 | -2.1 | -4.2 | 82714343.32 | 56.69 | -17.2 | -17.5 | ||
Maximum of Months | 0.136020E+10 | 4569.30 | 19.63 | 14.53 | 0.110627E+09 | 90.90 | 25.40 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3849240.47 | 216.88 | 30-JAN-15:05 | -24.0 | -24.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 9099715.77 | 255.65 | 02-FEB-15:05 | -28.9 | -29.2 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 47943870.14 | 397.15 | 24-MAR-13:00 | 12.20 | 6.44 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.138264E+09 | 511.20 | 15-APR-12:50 | 28.22 | 20.26 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.269545E+09 | 326.31 | 31-MAY-19:10 | 25.82 | 18.67 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.391041E+09 | 364.47 | 26-JUN-19:10 | 28.03 | 21.71 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.476588E+09 | 343.71 | 02-JUL-19:10 | 26.83 | 20.85 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.497553E+09 | 451.42 | 29-AUG-13:20 | 23.50 | 16.48 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.428453E+09 | 602.72 | 07-SEP-12:50 | 31.52 | 18.15 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.254103E+09 | 674.86 | 20-OCT-12:30 | 21.45 | 12.41 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 82237326.37 | 653.59 | 04-NOV-12:30 | 13.35 | 6.67 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 5391884.74 | 137.32 | 07-DEC-15:20 | -3.9 | -7.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.260407E+10 | 0.00 | ||||||||
Minimum of Months | 3849240.47 | 137.32 | -28.9 | -29.2 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.497553E+09 | 674.86 | 31.52 | 21.71 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7166153.99 | 627.11 | 01-JAN-09:02 | -3.2 | -3.4 | 92988026.88 | 56.69 | 13-JAN-22:10 | 2.02 | 0.71 |
February | 22892896.72 | 1043.94 | 26-FEB-09:02 | -2.0 | -3.1 | 83296896.81 | 56.69 | 24-FEB-22:10 | 1.93 | 1.42 |
March | 0.109031E+09 | 1102.46 | 25-MAR-18:02 | 14.82 | 10.04 | 95510233.56 | 56.69 | 29-MAR-21:10 | 7.70 | 7.14 |
April | 0.258605E+09 | 1162.57 | 30-APR-18:01 | 15.22 | 9.03 | 94155009.53 | 71.12 | 18-APR-21:19 | 15.93 | 13.15 |
May | 0.487564E+09 | 1133.75 | 06-MAY-18:51 | 15.00 | 9.53 | 99907771.98 | 76.17 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.648311E+09 | 1128.36 | 16-JUN-21:11 | 19.07 | 14.69 | 99812972.10 | 77.89 | 27-JUN-21:10 | 23.62 | 18.89 |
July | 0.687644E+09 | 1141.76 | 18-JUL-21:11 | 19.03 | 14.53 | 0.105746E+09 | 79.68 | 05-JUL-21:10 | 22.43 | 20.32 |
August | 0.633831E+09 | 1099.35 | 22-AUG-18:01 | 26.73 | 21.31 | 0.104620E+09 | 78.56 | 21-AUG-21:10 | 23.72 | 21.58 |
September | 0.472616E+09 | 1160.49 | 19-SEP-18:01 | 12.65 | 8.21 | 97096802.09 | 74.82 | 11-SEP-21:19 | 19.40 | 17.91 |
October | 0.234877E+09 | 1091.70 | 08-OCT-18:01 | 9.33 | 5.53 | 96490952.98 | 56.69 | 02-OCT-21:49 | 11.37 | 9.94 |
November | 0.106109E+09 | 1076.53 | 04-NOV-18:01 | 5.50 | 2.13 | 92044588.04 | 56.69 | 08-NOV-22:19 | 14.40 | 12.79 |
December | 9950091.92 | 719.40 | 03-DEC-09:02 | -1.5 | -1.7 | 93744290.81 | 56.69 | 04-DEC-22:10 | 1.78 | 0.08 |
Annual Sum or Average | 0.367860E+10 | 0.115541E+10 | ||||||||
Minimum of Months | 7166153.99 | 627.11 | -3.2 | -3.4 | 83296896.81 | 56.69 | 1.78 | 0.08 | ||
Maximum of Months | 0.687644E+09 | 1162.57 | 26.73 | 21.31 | 0.105746E+09 | 79.68 | 23.72 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3434533.19 | 658.66 | 12-JAN-09:03 | -4.1 | -4.6 | 92562646.79 | 56.69 | 31-JAN-23:00 | -23.9 | -24.2 |
February | 24043867.52 | 3344.19 | 24-FEB-09:02 | 3.07 | 0.60 | 83419148.35 | 56.69 | 01-FEB-02:20 | -27.1 | -27.3 |
March | 0.114083E+09 | 3469.35 | 24-MAR-15:01 | 12.43 | 6.31 | 95342479.24 | 56.69 | 28-MAR-21:00 | 8.90 | 7.21 |
April | 0.447966E+09 | 3515.04 | 26-APR-08:61 | 2.48 | -1.1 | 93436342.11 | 56.69 | 16-APR-01:39 | 20.00 | 16.62 |
May | 0.940885E+09 | 3449.64 | 20-MAY-18:01 | 15.22 | 8.18 | 98569608.71 | 56.69 | 31-MAY-21:19 | 21.40 | 16.39 |
June | 0.149176E+10 | 3247.89 | 11-JUN-08:61 | 24.37 | 20.61 | 95611119.70 | 56.69 | 26-JUN-22:40 | 24.07 | 20.64 |
July | 0.175292E+10 | 3220.73 | 29-JUL-08:61 | 22.48 | 19.22 | 98999864.72 | 56.69 | 03-JUL-21:00 | 23.30 | 22.56 |
August | 0.154201E+10 | 3180.60 | 02-AUG-08:62 | 22.48 | 19.67 | 99072050.34 | 56.70 | 28-AUG-21:10 | 21.70 | 20.86 |
September | 0.106497E+10 | 3446.30 | 30-SEP-15:01 | 10.92 | 3.90 | 95138255.31 | 56.69 | 06-SEP-21:19 | 18.87 | 16.25 |
October | 0.261905E+09 | 3474.69 | 24-OCT-15:01 | 15.42 | 8.78 | 96809416.87 | 56.69 | 20-OCT-21:49 | 13.90 | 9.51 |
November | 61206745.43 | 3493.37 | 04-NOV-15:01 | 14.13 | 6.69 | 91278804.17 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 9364930.22 | 2485.94 | 03-DEC-09:02 | -1.5 | -1.7 | 93013338.08 | 56.69 | 28-DEC-04:30 | -16.9 | -17.2 |
Annual Sum or Average | 0.771454E+10 | 0.113325E+10 | ||||||||
Minimum of Months | 3434533.19 | 658.66 | -4.1 | -4.6 | 83419148.35 | 56.69 | -27.1 | -27.3 | ||
Maximum of Months | 0.175292E+10 | 3515.04 | 24.37 | 20.61 | 99072050.34 | 56.70 | 24.07 | 22.56 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 574938.66 | 459.30 | 11-JAN-09:05 | -4.4 | -4.8 | 92117428.32 | 56.69 | 06-JAN-03:39 | -26.1 | -26.3 |
February | 6565408.51 | 3206.51 | 24-FEB-09:02 | 3.07 | 0.60 | 82161517.01 | 56.69 | 28-FEB-00:30 | -15.3 | -15.8 |
March | 58120198.61 | 2856.63 | 19-MAR-15:01 | 18.40 | 13.71 | 94373952.00 | 56.69 | 28-MAR-21:10 | 9.82 | 7.62 |
April | 0.310670E+09 | 3492.22 | 26-APR-08:61 | 2.48 | -1.1 | 93804120.53 | 70.69 | 18-APR-21:19 | 15.93 | 13.15 |
May | 0.759688E+09 | 3660.26 | 31-MAY-08:11 | 24.23 | 19.12 | 0.100863E+09 | 76.80 | 31-MAY-21:10 | 21.80 | 16.81 |
June | 0.124774E+10 | 3861.36 | 20-JUN-08:11 | 20.97 | 14.82 | 0.101056E+09 | 78.62 | 29-JUN-21:10 | 24.22 | 19.11 |
July | 0.136954E+10 | 3771.09 | 13-JUL-08:11 | 21.67 | 18.34 | 0.107383E+09 | 79.49 | 05-JUL-21:10 | 22.43 | 20.32 |
August | 0.115879E+10 | 3758.36 | 09-AUG-08:11 | 21.50 | 16.16 | 0.105580E+09 | 78.15 | 02-AUG-21:10 | 24.32 | 21.63 |
September | 0.739672E+09 | 3658.76 | 06-SEP-08:11 | 21.33 | 16.35 | 97560546.02 | 75.15 | 07-SEP-21:10 | 22.43 | 16.37 |
October | 0.105583E+09 | 2915.61 | 21-OCT-15:01 | 20.67 | 14.26 | 95633332.31 | 56.69 | 02-OCT-21:10 | 11.63 | 10.32 |
November | 17221808.56 | 2180.79 | 04-NOV-08:62 | 2.77 | 0.70 | 90529767.99 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 779219.35 | 622.86 | 05-DEC-09:03 | -6.6 | -8.4 | 92389513.65 | 56.69 | 16-DEC-05:49 | -14.4 | -14.9 |
Annual Sum or Average | 0.577494E+10 | 0.115345E+10 | ||||||||
Minimum of Months | 574938.66 | 459.30 | -6.6 | -8.4 | 82161517.01 | 56.69 | -26.1 | -26.3 | ||
Maximum of Months | 0.136954E+10 | 3861.36 | 24.23 | 19.12 | 0.107383E+09 | 79.49 | 24.32 | 21.63 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250215E+09 | 1106.33 | 31-JAN-04:00 | -31.1 | -31.3 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.295340E+09 | 1440.28 | 02-FEB-06:02 | -36.7 | -36.8 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.419505E+09 | 1313.65 | 19-MAR-14:30 | 18.30 | 13.67 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.113415E+10 | 1638.45 | 18-APR-15:02 | 27.75 | 20.45 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.228743E+10 | 1631.35 | 31-MAY-19:20 | 25.53 | 18.52 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.310616E+10 | 1679.09 | 30-JUN-19:20 | 25.17 | 19.00 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.367397E+10 | 1667.70 | 01-JUL-19:00 | 24.40 | 19.17 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.349097E+10 | 1658.47 | 04-AUG-15:02 | 33.90 | 25.47 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.250317E+10 | 1682.41 | 08-SEP-14:00 | 30.60 | 19.31 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.106850E+10 | 1601.93 | 20-OCT-14:40 | 23.07 | 13.23 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.335900E+09 | 1341.43 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 45813382.56 | 1019.32 | 03-DEC-13:00 | 5.60 | 2.40 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.186111E+11 | 0.00 | ||||||||
Minimum of Months | 45813382.56 | 1019.32 | -36.7 | -36.8 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.367397E+10 | 1682.41 | 33.90 | 25.47 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2717267.88 | 3768.42 | 12-JAN-16:01 | 2.62 | 1.03 | 92452613.42 | 56.69 | 15-JAN-02:39 | -14.8 | -15.5 |
February | 32728992.19 | 4004.92 | 24-FEB-16:01 | 8.12 | 5.75 | 83709299.13 | 56.69 | 03-FEB-23:19 | -28.5 | -28.7 |
March | 0.108882E+09 | 3988.10 | 24-MAR-15:01 | 12.43 | 6.31 | 94758676.55 | 56.69 | 19-MAR-23:49 | 13.48 | 11.19 |
April | 0.597257E+09 | 4029.22 | 29-APR-18:01 | 15.03 | 9.30 | 93131780.54 | 56.69 | 16-APR-03:30 | 19.15 | 16.28 |
May | 0.102675E+10 | 4145.51 | 20-MAY-18:01 | 15.22 | 8.18 | 98245778.10 | 56.70 | 24-MAY-00:00 | 11.10 | 9.84 |
June | 0.175921E+10 | 3566.01 | 17-JUN-18:02 | 23.72 | 19.21 | 95465365.85 | 56.70 | 01-JUN-04:10 | 5.50 | 5.26 |
July | 0.217388E+10 | 3653.06 | 05-JUL-18:02 | 26.52 | 21.26 | 98876342.15 | 56.70 | 24-JUL-22:10 | 19.32 | 15.82 |
August | 0.191342E+10 | 3608.23 | 21-AUG-18:02 | 26.52 | 21.93 | 98889867.29 | 56.70 | 03-AUG-22:10 | 23.90 | 22.72 |
September | 0.121948E+10 | 4012.54 | 20-SEP-18:01 | 17.23 | 10.69 | 94791383.14 | 56.70 | 11-SEP-21:10 | 19.40 | 17.91 |
October | 0.302988E+09 | 4013.53 | 24-OCT-15:01 | 15.42 | 8.78 | 96368354.14 | 56.69 | 11-OCT-21:19 | 10.50 | 5.47 |
November | 60890489.15 | 4053.08 | 04-NOV-15:01 | 14.13 | 6.69 | 90912701.70 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 5220311.81 | 3685.89 | 01-DEC-16:01 | -2.1 | -4.2 | 92755312.51 | 56.69 | 10-DEC-04:10 | -21.8 | -22.1 |
Annual Sum or Average | 0.920342E+10 | 0.113036E+10 | ||||||||
Minimum of Months | 2717267.88 | 3566.01 | -2.1 | -4.2 | 83709299.13 | 56.69 | -28.5 | -28.7 | ||
Maximum of Months | 0.217388E+10 | 4145.51 | 26.52 | 21.93 | 98889867.29 | 56.70 | 23.90 | 22.72 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87158.70 | 741.40 | 13-JAN-16:04 | 3.62 | 1.74 | 92123422.94 | 56.69 | 31-JAN-23:49 | -23.7 | -24.0 |
February | 8050127.49 | 3700.74 | 24-FEB-16:01 | 8.12 | 5.75 | 82614572.89 | 56.69 | 18-FEB-01:39 | -15.4 | -15.8 |
March | 46233591.87 | 3885.84 | 24-MAR-18:01 | 8.35 | 4.46 | 93953939.87 | 56.69 | 23-MAR-21:10 | 9.32 | 6.06 |
April | 0.416088E+09 | 4039.92 | 29-APR-18:01 | 15.03 | 9.30 | 94490820.02 | 86.18 | 17-APR-18:10 | 18.03 | 11.62 |
May | 0.785613E+09 | 5043.27 | 20-MAY-18:01 | 15.22 | 8.18 | 0.103307E+09 | 88.59 | 30-MAY-21:10 | 19.82 | 17.01 |
June | 0.148607E+10 | 4199.76 | 21-JUN-20:21 | 15.25 | 12.53 | 0.104963E+09 | 97.92 | 08-JUN-18:10 | 22.88 | 16.37 |
July | 0.171736E+10 | 4189.46 | 23-JUL-21:11 | 17.57 | 13.04 | 0.114059E+09 | 101.56 | 06-JUL-18:10 | 25.40 | 21.36 |
August | 0.144923E+10 | 3977.59 | 07-AUG-21:11 | 15.73 | 11.99 | 0.111571E+09 | 97.63 | 18-AUG-18:10 | 23.35 | 16.96 |
September | 0.843698E+09 | 4169.75 | 19-SEP-17:01 | 15.22 | 9.18 | 99632118.60 | 91.81 | 01-SEP-18:10 | 21.42 | 14.20 |
October | 0.123228E+09 | 3761.90 | 24-OCT-15:01 | 15.42 | 8.78 | 95488270.21 | 58.59 | 11-OCT-18:10 | 15.35 | 9.77 |
November | 22282110.84 | 3879.05 | 04-NOV-15:01 | 14.13 | 6.69 | 90247260.12 | 56.69 | 24-NOV-03:30 | -14.4 | -14.7 |
December | 203358.81 | 710.37 | 02-DEC-16:03 | 4.95 | 2.78 | 92259342.40 | 56.69 | 11-DEC-05:10 | -22.2 | -22.6 |
Annual Sum or Average | 0.689814E+10 | 0.117471E+10 | ||||||||
Minimum of Months | 87158.70 | 710.37 | 3.62 | 1.74 | 82614572.89 | 56.69 | -23.7 | -24.0 | ||
Maximum of Months | 0.171736E+10 | 5043.27 | 17.57 | 13.04 | 0.114059E+09 | 101.56 | 25.40 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66845862.85 | 1941.06 | 30-JAN-16:02 | -24.5 | -24.8 | 94366475.87 | 56.69 | 12-JAN-22:10 | 1.23 | -0.5 |
February | 0.114410E+09 | 1793.43 | 17-FEB-16:01 | -6.8 | -8.6 | 85791426.12 | 56.69 | 07-FEB-22:10 | 2.70 | 1.54 |
March | 0.190821E+09 | 1820.40 | 22-MAR-15:01 | 6.70 | 3.36 | 96363976.65 | 56.69 | 20-MAR-00:40 | 12.57 | 10.77 |
April | 0.377171E+09 | 1808.21 | 06-APR-15:01 | 8.30 | 3.04 | 93644301.88 | 56.69 | 15-APR-23:40 | 20.20 | 16.32 |
May | 0.599971E+09 | 1774.97 | 20-MAY-18:01 | 15.22 | 8.18 | 98361627.10 | 56.69 | 31-MAY-23:10 | 17.10 | 11.90 |
June | 0.895690E+09 | 1639.76 | 07-JUN-15:01 | 20.18 | 16.39 | 95509428.19 | 56.69 | 30-JUN-00:30 | 23.05 | 19.13 |
July | 0.107482E+10 | 1651.45 | 12-JUL-18:01 | 23.12 | 17.48 | 98815603.69 | 56.69 | 21-JUL-22:10 | 15.92 | 14.02 |
August | 0.107126E+10 | 1642.61 | 01-AUG-18:02 | 26.73 | 21.32 | 98873060.46 | 56.69 | 21-AUG-23:00 | 22.20 | 20.98 |
September | 0.880091E+09 | 1818.09 | 30-SEP-15:01 | 10.92 | 3.90 | 95149275.23 | 56.69 | 09-SEP-00:30 | 18.60 | 15.30 |
October | 0.506065E+09 | 1839.44 | 27-OCT-15:01 | 10.23 | 4.51 | 97629613.76 | 56.69 | 10-OCT-21:10 | 10.67 | 9.78 |
November | 0.187604E+09 | 1811.11 | 12-NOV-16:01 | 0.55 | -2.2 | 92683452.90 | 56.69 | 08-NOV-22:10 | 14.40 | 12.79 |
December | 0.118639E+09 | 1799.92 | 01-DEC-16:01 | -2.1 | -4.2 | 94667363.46 | 56.69 | 28-DEC-04:30 | -16.9 | -17.2 |
Annual Sum or Average | 0.608339E+10 | 0.114186E+10 | ||||||||
Minimum of Months | 66845862.85 | 1639.76 | -24.5 | -24.8 | 85791426.12 | 56.69 | -16.9 | -17.2 | ||
Maximum of Months | 0.107482E+10 | 1941.06 | 26.73 | 21.32 | 98873060.46 | 56.69 | 23.05 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280459E+11 | 31310.34 | 19-JAN-01:51 | -23.9 | -24.0 | 0.170677E+11 | 11347.89 | 17-JAN-00:20 | -3.7 | -3.8 |
February | 0.267477E+11 | 20573.77 | 02-FEB-06:00 | -36.7 | -36.8 | 0.152038E+11 | 11347.89 | 13-FEB-00:20 | -6.7 | -7.1 |
March | 0.310774E+11 | 17949.87 | 28-MAR-22:00 | 8.90 | 7.21 | 0.189306E+11 | 11348.00 | 27-MAR-00:20 | 2.60 | 1.08 |
April | 0.331022E+11 | 19742.95 | 18-APR-21:12 | 15.93 | 13.15 | 0.184209E+11 | 11348.65 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.378585E+11 | 20954.94 | 31-MAY-21:12 | 21.40 | 16.39 | 0.191004E+11 | 11348.91 | 30-MAY-21:30 | 19.45 | 16.75 |
June | 0.394222E+11 | 21813.50 | 26-JUN-21:12 | 25.20 | 21.19 | 0.185405E+11 | 11349.03 | 15-JUN-21:30 | 15.45 | 13.95 |
July | 0.415811E+11 | 21547.91 | 03-JUL-21:12 | 24.03 | 22.76 | 0.190597E+11 | 11348.95 | 07-JUL-21:30 | 18.05 | 16.10 |
August | 0.408887E+11 | 21218.73 | 03-AUG-21:12 | 24.23 | 23.04 | 0.190940E+11 | 11349.04 | 24-AUG-21:19 | 15.20 | 13.98 |
September | 0.366511E+11 | 20804.52 | 07-SEP-21:12 | 22.07 | 16.31 | 0.184349E+11 | 11348.98 | 01-SEP-21:30 | 16.95 | 12.48 |
October | 0.335651E+11 | 18388.44 | 20-OCT-22:00 | 13.90 | 9.53 | 0.190121E+11 | 11348.07 | 23-OCT-00:20 | 0.87 | -0.5 |
November | 0.297969E+11 | 22576.48 | 25-NOV-21:22 | -23.9 | -24.2 | 0.179242E+11 | 11347.90 | 13-NOV-00:20 | -2.6 | -4.3 |
December | 0.276150E+11 | 15893.78 | 04-DEC-23:00 | 2.20 | 0.30 | 0.183274E+11 | 11347.91 | 05-DEC-04:19 | 2.23 | 0.71 |
Annual Sum or Average | 0.406352E+12 | 0.219116E+12 | ||||||||
Minimum of Months | 0.267477E+11 | 15893.78 | -36.7 | -36.8 | 0.152038E+11 | 11347.89 | -6.7 | -7.1 | ||
Maximum of Months | 0.415811E+11 | 31310.34 | 25.20 | 23.04 | 0.191004E+11 | 11349.04 | 19.45 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311857E+11 | 33210.65 | 19-JAN-01:51 | -23.9 | -24.0 | 0.174263E+11 | 11347.95 | 17-JAN-00:20 | -3.7 | -3.8 |
February | 0.298952E+11 | 21604.81 | 02-FEB-06:00 | -36.7 | -36.8 | 0.154361E+11 | 11347.95 | 13-FEB-00:20 | -6.7 | -7.1 |
March | 0.349192E+11 | 20010.73 | 28-MAR-21:20 | 9.63 | 7.54 | 0.191343E+11 | 11348.06 | 27-MAR-00:20 | 2.60 | 1.08 |
April | 0.369328E+11 | 21556.79 | 18-APR-21:12 | 15.93 | 13.15 | 0.185663E+11 | 11348.66 | 18-APR-21:30 | 15.55 | 12.91 |
May | 0.418769E+11 | 22658.38 | 31-MAY-21:12 | 21.40 | 16.39 | 0.192165E+11 | 11348.91 | 30-MAY-21:30 | 19.45 | 16.75 |
June | 0.430481E+11 | 23392.36 | 26-JUN-21:12 | 25.20 | 21.19 | 0.186345E+11 | 11349.03 | 15-JUN-21:30 | 15.45 | 13.95 |
July | 0.451819E+11 | 23065.51 | 03-JUL-21:12 | 24.03 | 22.76 | 0.191549E+11 | 11348.96 | 07-JUL-21:30 | 18.05 | 16.10 |
August | 0.445186E+11 | 22847.31 | 03-AUG-21:12 | 24.23 | 23.04 | 0.192095E+11 | 11349.05 | 24-AUG-21:19 | 15.20 | 13.98 |
September | 0.403150E+11 | 22412.01 | 07-SEP-21:12 | 22.07 | 16.31 | 0.185544E+11 | 11348.99 | 01-SEP-21:30 | 16.95 | 12.48 |
October | 0.375485E+11 | 20343.37 | 02-OCT-22:00 | 11.30 | 9.84 | 0.191541E+11 | 11348.10 | 23-OCT-00:20 | 0.87 | -0.5 |
November | 0.333319E+11 | 28492.20 | 25-NOV-21:22 | -23.9 | -24.2 | 0.181599E+11 | 11347.96 | 13-NOV-00:20 | -2.6 | -4.3 |
December | 0.309950E+11 | 17932.72 | 04-DEC-23:00 | 2.20 | 0.30 | 0.186615E+11 | 11347.98 | 26-DEC-00:20 | -6.5 | -7.1 |
Annual Sum or Average | 0.449749E+12 | 0.221308E+12 | ||||||||
Minimum of Months | 0.298952E+11 | 17932.72 | -36.7 | -36.8 | 0.154361E+11 | 11347.95 | -6.7 | -7.1 | ||
Maximum of Months | 0.451819E+11 | 33210.65 | 25.20 | 23.04 | 0.192165E+11 | 11349.05 | 19.45 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.465780E+11 | 27089.01 | 29-JAN-19:32 | -23.7 | -23.9 | 0.186462E+11 | 11336.77 | 14-JAN-18:00 | -9.4 | -10.4 |
February | 0.436226E+11 | 26087.90 | 24-FEB-11:50 | 6.02 | 3.02 | 0.168188E+11 | 11361.26 | 25-FEB-18:00 | 1.70 | 0.04 |
March | 0.504126E+11 | 27835.33 | 19-MAR-10:50 | 14.13 | 10.20 | 0.188171E+11 | 11371.90 | 18-MAR-17:00 | 8.90 | 7.46 |
April | 0.511110E+11 | 29990.74 | 18-APR-10:40 | 26.33 | 20.74 | 0.182191E+11 | 11374.20 | 22-APR-17:00 | 3.90 | 1.51 |
May | 0.557451E+11 | 30246.79 | 29-MAY-10:40 | 24.63 | 18.65 | 0.188250E+11 | 11360.97 | 13-MAY-17:00 | 12.20 | 10.89 |
June | 0.558256E+11 | 30605.84 | 11-JUN-10:40 | 29.67 | 22.03 | 0.181989E+11 | 11335.66 | 03-JUN-17:00 | 14.40 | 10.98 |
July | 0.582967E+11 | 30625.52 | 29-JUL-10:50 | 26.02 | 19.78 | 0.187858E+11 | 11319.66 | 22-JUL-17:19 | 19.80 | 14.29 |
August | 0.576491E+11 | 30196.05 | 11-AUG-10:40 | 27.07 | 19.13 | 0.188014E+11 | 11319.65 | 05-AUG-17:19 | 25.03 | 17.78 |
September | 0.538972E+11 | 30357.47 | 08-SEP-10:40 | 28.33 | 18.76 | 0.182082E+11 | 11375.58 | 30-SEP-17:00 | 6.10 | 1.60 |
October | 0.523547E+11 | 28557.53 | 20-OCT-10:50 | 17.62 | 11.23 | 0.188299E+11 | 11369.29 | 28-OCT-17:00 | 7.20 | 3.19 |
November | 0.479329E+11 | 29045.67 | 25-NOV-21:22 | -23.9 | -24.2 | 0.181781E+11 | 11372.87 | 04-NOV-17:49 | 5.97 | 2.43 |
December | 0.470082E+11 | 25847.01 | 03-DEC-11:50 | 4.90 | 2.33 | 0.187821E+11 | 11353.78 | 02-DEC-18:00 | 1.10 | 0.61 |
Annual Sum or Average | 0.620434E+12 | 0.221110E+12 | ||||||||
Minimum of Months | 0.436226E+11 | 25847.01 | -23.9 | -24.2 | 0.168188E+11 | 11319.65 | -9.4 | -10.4 | ||
Maximum of Months | 0.582967E+11 | 30625.52 | 29.67 | 22.03 | 0.188299E+11 | 11375.58 | 25.03 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132656E+09 | 2124.69 | 12-JAN-12:50 | 2.12 | 0.46 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 0.438890E+09 | 2371.79 | 24-FEB-14:20 | 7.97 | 5.31 | 0.00 | 0.00 | 01-FEB-00:10 | -24.1 | -24.4 |
March | 0.190308E+10 | 3149.45 | 19-MAR-14:00 | 18.30 | 13.67 | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 | -11.9 |
April | 0.394606E+10 | 3766.38 | 18-APR-14:00 | 28.30 | 20.64 | 0.00 | 0.00 | 01-APR-00:10 | -1.2 | -2.1 |
May | 0.692600E+10 | 3886.90 | 31-MAY-15:15 | 29.43 | 19.38 | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 | 5.14 |
June | 0.824976E+10 | 4162.65 | 30-JUN-15:02 | 29.32 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 | 10.68 |
July | 0.923069E+10 | 4111.16 | 03-JUL-15:50 | 29.08 | 24.41 | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 | 15.93 |
August | 0.886242E+10 | 4129.68 | 04-AUG-15:02 | 33.90 | 25.47 | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 | 17.82 |
September | 0.685681E+10 | 4142.35 | 07-SEP-13:50 | 32.12 | 18.31 | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 | 15.67 |
October | 0.402184E+10 | 3590.78 | 20-OCT-13:50 | 22.47 | 12.93 | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 | 1.38 |
November | 0.160513E+10 | 3043.69 | 03-NOV-14:00 | 16.10 | 10.46 | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 | -0.4 |
December | 0.299675E+09 | 2264.58 | 03-DEC-13:30 | 5.60 | 2.31 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.2 |
Annual Sum or Average | 0.524730E+11 | 0.00 | ||||||||
Minimum of Months | 0.132656E+09 | 2124.69 | 2.12 | 0.46 | 0.00 | 0.00 | -24.1 | -24.4 | ||
Maximum of Months | 0.923069E+10 | 4162.65 | 33.90 | 25.47 | 0.00 | 0.00 | 18.93 | 17.82 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 624197.34 | 1227.43 | 31-JAN-11:42 | -23.1 |
February | 0.342290E+09 | 8336.59 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.342915E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.342290E+09 | 8336.59 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234572E+10 | 2928.16 | 20-JAN-07:51 | -23.3 |
February | 0.115035E+10 | 2641.12 | 04-FEB-11:21 | -23.0 |
March | 0.601299E+09 | 1483.42 | 06-MAR-04:50 | -15.7 |
April | 0.201916E+09 | 1025.93 | 03-APR-06:10 | -7.1 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 6290987.01 | 338.87 | 30-SEP-06:30 | 0.60 |
October | 23625549.15 | 446.89 | 23-OCT-06:10 | -3.0 |
November | 0.804423E+09 | 2762.71 | 26-NOV-08:51 | -23.3 |
December | 0.198114E+10 | 2335.14 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.711477E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.234572E+10 | 2928.16 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35397567.53 | 952.24 | 31-JAN-11:42 | -23.1 |
February | 59135222.75 | 1314.61 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 4436353.53 | 648.46 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 98969143.80 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 59135222.75 | 1314.61 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499900E+09 | 1517.97 | 31-JAN-11:42 | -23.1 |
February | 0.331935E+09 | 2035.07 | 04-FEB-11:21 | -23.0 |
March | 9795433.56 | 340.85 | 06-MAR-05:00 | -15.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 92159376.37 | 1164.08 | 26-NOV-09:02 | -22.7 |
December | 0.169589E+09 | 740.57 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.110338E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.499900E+09 | 2035.07 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101426E+10 | 972.64 | 31-JAN-11:42 | -23.1 |
February | 0.557511E+09 | 1194.64 | 04-FEB-11:21 | -23.0 |
March | 0.210178E+09 | 516.07 | 06-MAR-05:00 | -15.6 |
April | 33366239.02 | 256.53 | 03-APR-04:00 | -6.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.271621E+09 | 826.27 | 26-NOV-09:02 | -22.7 |
December | 0.683821E+09 | 718.27 | 11-DEC-05:00 | -22.2 |
Annual Sum or Average | 0.277076E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.101426E+10 | 1194.64 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 234208.61 | 2008.63 | 31-JAN-11:31 | -23.3 |
February | 192259.35 | 2513.66 | 04-FEB-11:11 | -23.3 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 117173.37 | 1952.89 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 543641.33 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 234208.61 | 2513.66 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511229E+09 | 6998.57 | 20-JAN-07:51 | -23.3 |
February | 0.101317E+09 | 5817.23 | 04-FEB-11:21 | -23.0 |
March | 17744538.62 | 695.08 | 01-MAR-11:08 | -4.9 |
April | 1344226.67 | 431.93 | 03-APR-08:08 | -5.9 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.107601E+09 | 6625.81 | 26-NOV-08:51 | -23.3 |
December | 0.565732E+09 | 3995.81 | 12-DEC-15:00 | -15.6 |
Annual Sum or Average | 0.130497E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.565732E+09 | 6998.57 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186479E+09 | 16070.97 | 31-JAN-11:42 | -23.1 |
February | 0.430971E+09 | 22430.66 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 16540646.18 | 12104.27 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.633990E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 0.430971E+09 | 22430.66 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206532E+10 | 2063.99 | 18-JAN-16:12 | -18.0 |
February | 0.136675E+10 | 2209.07 | 02-FEB-08:05 | -36.5 |
March | 0.728241E+09 | 2002.96 | 01-MAR-16:02 | -3.9 |
April | 0.293974E+09 | 1989.91 | 03-APR-08:62 | -5.9 |
May | 22454275.11 | 1632.88 | 02-MAY-08:61 | 4.08 |
June | 8424184.78 | 1354.96 | 04-JUN-08:03 | 11.38 |
July | 2100521.04 | 976.29 | 28-JUL-08:04 | 22.48 |
August | 1861325.07 | 1192.18 | 07-AUG-08:03 | 15.47 |
September | 52840846.41 | 1891.90 | 30-SEP-08:62 | 3.35 |
October | 0.213374E+09 | 1923.23 | 26-OCT-08:62 | 1.28 |
November | 0.920006E+09 | 2044.18 | 26-NOV-16:13 | -13.9 |
December | 0.171206E+10 | 2079.81 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.738740E+10 | |||
Minimum of Months | 1861325.07 | 976.29 | -36.5 | |
Maximum of Months | 0.206532E+10 | 2209.07 | 22.48 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242612E+10 | 2075.13 | 19-JAN-16:02 | -22.9 |
February | 0.164725E+10 | 2273.62 | 02-FEB-11:03 | -31.6 |
March | 0.860975E+09 | 1999.84 | 06-MAR-09:02 | -9.5 |
April | 0.330571E+09 | 1984.87 | 03-APR-08:62 | -5.9 |
May | 25087560.68 | 1901.97 | 02-MAY-08:61 | 4.08 |
June | 7811965.25 | 1332.00 | 04-JUN-08:03 | 11.38 |
July | 1136934.19 | 1242.91 | 24-JUL-08:13 | 19.47 |
August | 1992151.52 | 1202.51 | 11-AUG-08:13 | 21.10 |
September | 65192988.40 | 1896.71 | 30-SEP-08:62 | 3.35 |
October | 0.313334E+09 | 1931.66 | 23-OCT-08:62 | 0.70 |
November | 0.109858E+10 | 2049.09 | 26-NOV-16:13 | -13.9 |
December | 0.198669E+10 | 2077.17 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.876474E+10 | |||
Minimum of Months | 1136934.19 | 1202.51 | -31.6 | |
Maximum of Months | 0.242612E+10 | 2273.62 | 21.10 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83101589.93 | 276.22 | 19-JAN-06:00 | -27.8 |
February | 19612770.76 | 248.53 | 04-FEB-06:00 | -30.6 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 894846.73 | 92.97 | 28-NOV-05:00 | -21.7 |
December | 39022989.31 | 208.23 | 12-DEC-16:00 | -15.6 |
Annual Sum or Average | 0.142632E+09 | |||
Minimum of Months | 0.00 | 0.00 | -30.6 | |
Maximum of Months | 83101589.93 | 276.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405369E+09 | 595.84 | 31-JAN-16:01 | -20.1 |
February | 0.242764E+09 | 650.22 | 03-FEB-11:01 | -29.2 |
March | 72215947.27 | 572.69 | 23-MAR-15:03 | 16.28 |
April | 10893367.51 | 551.26 | 29-APR-15:04 | 17.02 |
May | 642396.58 | 564.92 | 20-MAY-15:04 | 16.10 |
June | 345610.41 | 481.63 | 06-JUN-15:05 | 16.28 |
July | 120226.27 | 400.61 | 10-JUL-15:06 | 18.30 |
August | 240451.93 | 420.89 | 06-AUG-15:06 | 19.22 |
September | 808900.86 | 494.68 | 30-SEP-15:03 | 10.92 |
October | 2585074.12 | 529.38 | 10-OCT-15:04 | 16.95 |
November | 0.118200E+09 | 586.66 | 25-NOV-16:02 | -18.1 |
December | 0.288752E+09 | 584.84 | 25-DEC-16:01 | -8.6 |
Annual Sum or Average | 0.114294E+10 | |||
Minimum of Months | 120226.27 | 400.61 | -29.2 | |
Maximum of Months | 0.405369E+09 | 650.22 | 19.22 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205355E+10 | 1989.29 | 19-JAN-16:02 | -22.9 |
February | 0.137528E+10 | 1995.23 | 04-FEB-19:02 | -20.0 |
March | 0.711819E+09 | 1929.14 | 01-MAR-16:02 | -3.9 |
April | 0.319653E+09 | 1909.85 | 01-APR-15:02 | -2.2 |
May | 18635394.40 | 1204.68 | 20-MAY-18:03 | 15.22 |
June | 6101950.22 | 1075.86 | 03-JUN-08:03 | 8.68 |
July | 1229144.09 | 1124.56 | 10-JUL-15:04 | 18.30 |
August | 1854542.90 | 980.71 | 06-AUG-08:04 | 12.80 |
September | 46917105.89 | 1159.46 | 25-SEP-18:03 | 11.42 |
October | 0.213804E+09 | 1841.35 | 26-OCT-08:62 | 1.28 |
November | 0.925837E+09 | 1963.84 | 26-NOV-16:13 | -13.9 |
December | 0.171664E+10 | 1998.55 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.739131E+10 | |||
Minimum of Months | 1229144.09 | 980.71 | -22.9 | |
Maximum of Months | 0.205355E+10 | 1998.55 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241390E+10 | 2018.52 | 31-JAN-16:01 | -20.1 |
February | 0.166513E+10 | 2195.27 | 03-FEB-18:02 | -27.8 |
March | 0.844843E+09 | 1933.70 | 05-MAR-19:02 | -14.0 |
April | 0.363408E+09 | 1912.13 | 03-APR-15:02 | -3.2 |
May | 22280985.18 | 1307.24 | 02-MAY-15:03 | 11.20 |
June | 6155056.26 | 1086.48 | 03-JUN-08:03 | 8.68 |
July | 764448.67 | 1088.28 | 10-JUL-15:04 | 18.30 |
August | 1499081.27 | 981.61 | 06-AUG-08:04 | 12.80 |
September | 56900811.25 | 1251.06 | 25-SEP-15:03 | 13.22 |
October | 0.310524E+09 | 1851.35 | 26-OCT-08:62 | 1.28 |
November | 0.110320E+10 | 1979.70 | 25-NOV-16:02 | -18.1 |
December | 0.199782E+10 | 2003.62 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.878643E+10 | |||
Minimum of Months | 764448.67 | 981.61 | -27.8 | |
Maximum of Months | 0.241390E+10 | 2195.27 | 18.30 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262159E+10 | 1879.91 | 31-JAN-11:42 | -23.1 |
February | 0.163711E+10 | 2376.67 | 04-FEB-11:21 | -23.0 |
March | 0.899352E+09 | 1413.62 | 06-MAR-05:00 | -15.6 |
April | 0.330363E+09 | 1078.12 | 03-APR-04:00 | -6.7 |
May | 7423714.13 | 256.52 | 02-MAY-04:50 | 2.30 |
June | 430407.72 | 84.56 | 03-JUN-04:30 | 5.30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 30746997.18 | 491.80 | 30-SEP-05:00 | 0.00 |
October | 0.155295E+09 | 569.90 | 27-OCT-04:00 | 0.00 |
November | 0.117237E+10 | 1724.42 | 26-NOV-09:02 | -22.7 |
December | 0.235894E+10 | 1535.55 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.921362E+10 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.262159E+10 | 2376.67 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277508E+10 | 2406.36 | 18-JAN-16:12 | -18.0 |
February | 0.179654E+10 | 2440.80 | 02-FEB-08:05 | -36.5 |
March | 0.107201E+10 | 2321.86 | 01-MAR-16:02 | -3.9 |
April | 0.458510E+09 | 2294.35 | 03-APR-08:62 | -5.9 |
May | 42592492.93 | 2209.45 | 02-MAY-08:61 | 4.08 |
June | 15767877.92 | 1157.92 | 04-JUN-08:03 | 11.38 |
July | 1742259.67 | 959.61 | 06-JUL-08:04 | 19.90 |
August | 1556470.74 | 1123.79 | 07-AUG-08:03 | 15.47 |
September | 95653950.07 | 2203.88 | 30-SEP-08:62 | 3.35 |
October | 0.375747E+09 | 2242.27 | 26-OCT-08:62 | 1.28 |
November | 0.132046E+10 | 2384.87 | 26-NOV-16:13 | -13.9 |
December | 0.235299E+10 | 2423.39 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.103086E+11 | |||
Minimum of Months | 1556470.74 | 959.61 | -36.5 | |
Maximum of Months | 0.277508E+10 | 2440.80 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319494E+10 | 2414.66 | 19-JAN-16:13 | -23.0 |
February | 0.213791E+10 | 2615.70 | 02-FEB-11:03 | -31.6 |
March | 0.125421E+10 | 2319.03 | 01-MAR-16:02 | -3.9 |
April | 0.507388E+09 | 2290.17 | 03-APR-08:62 | -5.9 |
May | 44609497.65 | 2211.21 | 02-MAY-08:61 | 4.08 |
June | 15532597.94 | 1199.84 | 08-JUN-08:13 | 18.33 |
July | 754979.83 | 1226.89 | 18-JUL-08:13 | 19.47 |
August | 1155279.68 | 1226.84 | 10-AUG-08:13 | 20.53 |
September | 0.113385E+09 | 2211.96 | 30-SEP-08:62 | 3.35 |
October | 0.516944E+09 | 2253.93 | 23-OCT-08:62 | 0.70 |
November | 0.155085E+10 | 2389.66 | 26-NOV-16:13 | -13.9 |
December | 0.269435E+10 | 2421.73 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.120320E+11 | |||
Minimum of Months | 754979.83 | 1199.84 | -31.6 | |
Maximum of Months | 0.319494E+10 | 2615.70 | 20.53 |
Report: ZoneHeatingSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.945038E+09 | 1151.51 | 26-JAN-16:13 | -11.5 |
February | 0.540465E+09 | 1129.57 | 28-FEB-19:02 | -15.7 |
March | 0.322946E+09 | 1130.38 | 01-MAR-16:02 | -3.9 |
April | 0.148776E+09 | 1119.93 | 02-APR-15:02 | 0.60 |
May | 6354132.28 | 833.25 | 09-MAY-15:04 | 17.62 |
June | 1380162.20 | 534.88 | 19-JUN-08:04 | 13.58 |
July | 323040.28 | 505.76 | 10-JUL-15:04 | 18.30 |
August | 682943.86 | 358.81 | 12-AUG-08:05 | 20.28 |
September | 15222494.27 | 638.27 | 29-SEP-08:62 | 5.05 |
October | 55006453.86 | 1065.57 | 26-OCT-08:62 | 1.28 |
November | 0.393575E+09 | 1141.80 | 26-NOV-16:13 | -13.9 |
December | 0.810461E+09 | 1165.56 | 09-DEC-16:13 | -19.1 |
Annual Sum or Average | 0.324023E+10 | |||
Minimum of Months | 323040.28 | 358.81 | -19.1 | |
Maximum of Months | 0.945038E+09 | 1165.56 | 20.28 |
Report: ZoneHeatingSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13486314.54 | 4712.85 | 31-JAN-11:42 | -23.1 |
February | 37676054.49 | 6123.24 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 355635.32 | 2491.14 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 51518004.35 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 37676054.49 | 6123.24 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9360886.41 | 4563.46 | 31-JAN-11:42 | -23.1 |
February | 16899758.07 | 5780.49 | 04-FEB-11:21 | -23.0 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 299787.56 | 2234.71 | 26-NOV-08:51 | -23.3 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 26560432.04 | |||
Minimum of Months | 0.00 | 0.00 | -23.3 | |
Maximum of Months | 16899758.07 | 5780.49 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:01 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:03 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:03 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544780E+10 | 5520.79 | 31-JAN-11:42 | -23.1 |
February | 0.302653E+10 | 6893.90 | 04-FEB-11:21 | -23.0 |
March | 0.120772E+10 | 3226.89 | 06-MAR-05:00 | -15.6 |
April | 0.280604E+09 | 1735.06 | 03-APR-05:00 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.15 |
September | 16167604.93 | 609.41 | 30-SEP-05:00 | 0.00 |
October | 74434440.05 | 706.62 | 08-OCT-05:00 | -0.6 |
November | 0.178528E+10 | 5089.96 | 26-NOV-09:02 | -22.7 |
December | 0.428564E+10 | 4319.05 | 10-DEC-06:00 | -22.8 |
Annual Sum or Average | 0.161242E+11 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.544780E+10 | 6893.90 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.140591E+11 | 13541.81 | 02-JAN-20:10 | 0.121516E+11 | 9632.53 | 02-JAN-20:10 |
February | 0.126941E+11 | 13541.81 | 01-FEB-20:10 | 0.109726E+11 | 9632.53 | 01-FEB-20:10 |
March | 0.141079E+11 | 13541.81 | 01-MAR-20:10 | 0.121808E+11 | 9632.53 | 01-MAR-20:10 |
April | 0.135824E+11 | 13541.81 | 03-APR-19:10 | 0.117446E+11 | 9632.53 | 03-APR-19:10 |
May | 0.140835E+11 | 13541.81 | 01-MAY-19:10 | 0.121662E+11 | 9632.53 | 01-MAY-19:10 |
June | 0.136447E+11 | 13541.81 | 01-JUN-19:10 | 0.117829E+11 | 9632.53 | 01-JUN-19:10 |
July | 0.140212E+11 | 13541.81 | 03-JUL-19:10 | 0.121279E+11 | 9632.53 | 03-JUL-19:10 |
August | 0.141079E+11 | 13541.81 | 01-AUG-19:10 | 0.121808E+11 | 9632.53 | 01-AUG-19:10 |
September | 0.135824E+11 | 13541.81 | 01-SEP-19:10 | 0.117446E+11 | 9632.53 | 01-SEP-19:10 |
October | 0.140591E+11 | 13541.81 | 02-OCT-19:10 | 0.121516E+11 | 9632.53 | 02-OCT-19:10 |
November | 0.136339E+11 | 13541.81 | 01-NOV-19:10 | 0.117774E+11 | 9632.53 | 01-NOV-19:10 |
December | 0.140212E+11 | 13541.81 | 01-DEC-20:10 | 0.121279E+11 | 9632.53 | 01-DEC-20:10 |
Annual Sum or Average | 0.165597E+12 | 0.143109E+12 | ||||
Minimum of Months | 0.126941E+11 | 13541.81 | 0.109726E+11 | 9632.53 | ||
Maximum of Months | 0.141079E+11 | 13541.81 | 0.121808E+11 | 9632.53 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.715050E+09 | 688.74 | 02-JAN-20:10 | 0.864900E+09 | 685.60 | 02-JAN-20:10 |
February | 0.645625E+09 | 688.74 | 01-FEB-20:10 | 0.780982E+09 | 685.60 | 01-FEB-20:10 |
March | 0.717530E+09 | 688.74 | 01-MAR-20:10 | 0.866978E+09 | 685.60 | 01-MAR-20:10 |
April | 0.690807E+09 | 688.74 | 03-APR-19:10 | 0.835931E+09 | 685.60 | 03-APR-19:10 |
May | 0.716290E+09 | 688.74 | 01-MAY-19:10 | 0.865939E+09 | 685.60 | 01-MAY-19:10 |
June | 0.693975E+09 | 688.74 | 01-JUN-19:10 | 0.838659E+09 | 685.60 | 01-JUN-19:10 |
July | 0.713122E+09 | 688.74 | 03-JUL-19:10 | 0.863211E+09 | 685.60 | 03-JUL-19:10 |
August | 0.717530E+09 | 688.74 | 01-AUG-19:10 | 0.866978E+09 | 685.60 | 01-AUG-19:10 |
September | 0.690807E+09 | 688.74 | 01-SEP-19:10 | 0.835931E+09 | 685.60 | 01-SEP-19:10 |
October | 0.715050E+09 | 688.74 | 02-OCT-19:10 | 0.864900E+09 | 685.60 | 02-OCT-19:10 |
November | 0.693424E+09 | 688.74 | 01-NOV-19:10 | 0.838269E+09 | 685.60 | 01-NOV-19:10 |
December | 0.713122E+09 | 688.74 | 01-DEC-20:10 | 0.863211E+09 | 685.60 | 01-DEC-20:10 |
Annual Sum or Average | 0.842233E+10 | 0.101859E+11 | ||||
Minimum of Months | 0.645625E+09 | 688.74 | 0.780982E+09 | 685.60 | ||
Maximum of Months | 0.717530E+09 | 688.74 | 0.866978E+09 | 685.60 |
Report: ZoneElectricSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.828031E+09 | 797.56 | 02-JAN-20:10 | 0.100156E+10 | 793.93 | 02-JAN-20:10 |
February | 0.747637E+09 | 797.56 | 01-FEB-20:10 | 0.904380E+09 | 793.93 | 01-FEB-20:10 |
March | 0.830902E+09 | 797.56 | 01-MAR-20:10 | 0.100396E+10 | 793.93 | 01-MAR-20:10 |
April | 0.799957E+09 | 797.56 | 03-APR-19:10 | 0.968011E+09 | 793.93 | 03-APR-19:10 |
May | 0.829467E+09 | 797.56 | 01-MAY-19:10 | 0.100276E+10 | 793.93 | 01-MAY-19:10 |
June | 0.803626E+09 | 797.56 | 01-JUN-19:10 | 0.971170E+09 | 793.93 | 01-JUN-19:10 |
July | 0.825798E+09 | 797.56 | 03-JUL-19:10 | 0.999601E+09 | 793.93 | 03-JUL-19:10 |
August | 0.830902E+09 | 797.56 | 01-AUG-19:10 | 0.100396E+10 | 793.93 | 01-AUG-19:10 |
September | 0.799957E+09 | 797.56 | 01-SEP-19:10 | 0.968011E+09 | 793.93 | 01-SEP-19:10 |
October | 0.828031E+09 | 797.56 | 02-OCT-19:10 | 0.100156E+10 | 793.93 | 02-OCT-19:10 |
November | 0.802987E+09 | 797.56 | 01-NOV-19:10 | 0.970719E+09 | 793.93 | 01-NOV-19:10 |
December | 0.825798E+09 | 797.56 | 01-DEC-20:10 | 0.999601E+09 | 793.93 | 01-DEC-20:10 |
Annual Sum or Average | 0.975309E+10 | 0.117953E+11 | ||||
Minimum of Months | 0.747637E+09 | 797.56 | 0.904380E+09 | 793.93 | ||
Maximum of Months | 0.830902E+09 | 797.56 | 0.100396E+10 | 793.93 |
Report: ZoneElectricSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156929E+10 | 1511.55 | 02-JAN-20:10 | 0.105898E+10 | 839.45 | 02-JAN-20:10 |
February | 0.141693E+10 | 1511.55 | 01-FEB-20:10 | 0.956227E+09 | 839.45 | 01-FEB-20:10 |
March | 0.157474E+10 | 1511.55 | 01-MAR-20:10 | 0.106152E+10 | 839.45 | 01-MAR-20:10 |
April | 0.151609E+10 | 1511.55 | 03-APR-19:10 | 0.102351E+10 | 839.45 | 03-APR-19:10 |
May | 0.157202E+10 | 1511.55 | 01-MAY-19:10 | 0.106025E+10 | 839.45 | 01-MAY-19:10 |
June | 0.152304E+10 | 1511.55 | 01-JUN-19:10 | 0.102685E+10 | 839.45 | 01-JUN-19:10 |
July | 0.156506E+10 | 1511.55 | 03-JUL-19:10 | 0.105691E+10 | 839.45 | 03-JUL-19:10 |
August | 0.157474E+10 | 1511.55 | 01-AUG-19:10 | 0.106152E+10 | 839.45 | 01-AUG-19:10 |
September | 0.151609E+10 | 1511.55 | 01-SEP-19:10 | 0.102351E+10 | 839.45 | 01-SEP-19:10 |
October | 0.156929E+10 | 1511.55 | 02-OCT-19:10 | 0.105898E+10 | 839.45 | 02-OCT-19:10 |
November | 0.152183E+10 | 1511.55 | 01-NOV-19:10 | 0.102637E+10 | 839.45 | 01-NOV-19:10 |
December | 0.156506E+10 | 1511.55 | 01-DEC-20:10 | 0.105691E+10 | 839.45 | 01-DEC-20:10 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | ||||
Minimum of Months | 0.141693E+10 | 1511.55 | 0.956227E+09 | 839.45 | ||
Maximum of Months | 0.157474E+10 | 1511.55 | 0.106152E+10 | 839.45 |
Report: ZoneElectricSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195080E+09 | 187.90 | 02-JAN-20:10 | 0.305485E+09 | 242.16 | 02-JAN-20:10 |
February | 0.176140E+09 | 187.90 | 01-FEB-20:10 | 0.275845E+09 | 242.16 | 01-FEB-20:10 |
March | 0.195757E+09 | 187.90 | 01-MAR-20:10 | 0.306219E+09 | 242.16 | 01-MAR-20:10 |
April | 0.188466E+09 | 187.90 | 03-APR-19:10 | 0.295253E+09 | 242.16 | 03-APR-19:10 |
May | 0.195419E+09 | 187.90 | 01-MAY-19:10 | 0.305852E+09 | 242.16 | 01-MAY-19:10 |
June | 0.189331E+09 | 187.90 | 01-JUN-19:10 | 0.296217E+09 | 242.16 | 01-JUN-19:10 |
July | 0.194554E+09 | 187.90 | 03-JUL-19:10 | 0.304889E+09 | 242.16 | 03-JUL-19:10 |
August | 0.195757E+09 | 187.90 | 01-AUG-19:10 | 0.306219E+09 | 242.16 | 01-AUG-19:10 |
September | 0.188466E+09 | 187.90 | 01-SEP-19:10 | 0.295253E+09 | 242.16 | 01-SEP-19:10 |
October | 0.195080E+09 | 187.90 | 02-OCT-19:10 | 0.305485E+09 | 242.16 | 02-OCT-19:10 |
November | 0.189180E+09 | 187.90 | 01-NOV-19:10 | 0.296079E+09 | 242.16 | 01-NOV-19:10 |
December | 0.194554E+09 | 187.90 | 01-DEC-20:10 | 0.304889E+09 | 242.16 | 01-DEC-20:10 |
Annual Sum or Average | 0.229778E+10 | 0.359769E+10 | ||||
Minimum of Months | 0.176140E+09 | 187.90 | 0.275845E+09 | 242.16 | ||
Maximum of Months | 0.195757E+09 | 187.90 | 0.306219E+09 | 242.16 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.337502E+09 | 325.08 | 02-JAN-20:10 | 0.576866E+10 | 4572.80 | 02-JAN-20:10 |
February | 0.304734E+09 | 325.08 | 01-FEB-20:10 | 0.520895E+10 | 4572.80 | 01-FEB-20:10 |
March | 0.338672E+09 | 325.08 | 01-MAR-20:10 | 0.578252E+10 | 4572.80 | 01-MAR-20:10 |
April | 0.326059E+09 | 325.08 | 03-APR-19:10 | 0.557545E+10 | 4572.80 | 03-APR-19:10 |
May | 0.338087E+09 | 325.08 | 01-MAY-19:10 | 0.577559E+10 | 4572.80 | 01-MAY-19:10 |
June | 0.327554E+09 | 325.08 | 01-JUN-19:10 | 0.559364E+10 | 4572.80 | 01-JUN-19:10 |
July | 0.336592E+09 | 325.08 | 03-JUL-19:10 | 0.575740E+10 | 4572.80 | 03-JUL-19:10 |
August | 0.338672E+09 | 325.08 | 01-AUG-19:10 | 0.578252E+10 | 4572.80 | 01-AUG-19:10 |
September | 0.326059E+09 | 325.08 | 01-SEP-19:10 | 0.557545E+10 | 4572.80 | 01-SEP-19:10 |
October | 0.337502E+09 | 325.08 | 02-OCT-19:10 | 0.576866E+10 | 4572.80 | 02-OCT-19:10 |
November | 0.327294E+09 | 325.08 | 01-NOV-19:10 | 0.559104E+10 | 4572.80 | 01-NOV-19:10 |
December | 0.336592E+09 | 325.08 | 01-DEC-20:10 | 0.575740E+10 | 4572.80 | 01-DEC-20:10 |
Annual Sum or Average | 0.397532E+10 | 0.679373E+11 | ||||
Minimum of Months | 0.304734E+09 | 325.08 | 0.520895E+10 | 4572.80 | ||
Maximum of Months | 0.338672E+09 | 325.08 | 0.578252E+10 | 4572.80 |
Report: ZoneElectricSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104804E+10 | 1299.02 | 02-JAN-20:10 | 0.121771E+10 | 965.27 | 02-JAN-20:10 |
February | 0.905989E+09 | 1299.02 | 01-FEB-20:10 | 0.109956E+10 | 965.27 | 01-FEB-20:10 |
March | 0.932048E+09 | 1299.02 | 01-MAR-20:10 | 0.122063E+10 | 965.27 | 01-MAR-20:10 |
April | 0.830748E+09 | 1299.02 | 03-APR-19:10 | 0.117692E+10 | 965.27 | 03-APR-19:10 |
May | 0.766894E+09 | 1299.02 | 01-MAY-19:10 | 0.121917E+10 | 965.27 | 01-MAY-19:10 |
June | 0.720078E+09 | 1299.02 | 01-JUN-19:10 | 0.118076E+10 | 965.27 | 01-JUN-19:10 |
July | 0.745343E+09 | 1299.02 | 03-JUL-19:30 | 0.121533E+10 | 965.27 | 03-JUL-19:10 |
August | 0.806644E+09 | 1299.02 | 01-AUG-19:30 | 0.122063E+10 | 965.27 | 01-AUG-19:10 |
September | 0.870625E+09 | 1299.02 | 01-SEP-19:10 | 0.117692E+10 | 965.27 | 01-SEP-19:10 |
October | 0.980476E+09 | 1299.02 | 02-OCT-19:10 | 0.121771E+10 | 965.27 | 02-OCT-19:10 |
November | 0.999158E+09 | 1299.02 | 01-NOV-19:10 | 0.118021E+10 | 965.27 | 01-NOV-19:10 |
December | 0.106719E+10 | 1299.02 | 01-DEC-20:10 | 0.121533E+10 | 965.27 | 01-DEC-20:10 |
Annual Sum or Average | 0.106732E+11 | 0.143409E+11 | ||||
Minimum of Months | 0.720078E+09 | 1299.02 | 0.109956E+10 | 965.27 | ||
Maximum of Months | 0.106719E+10 | 1299.02 | 0.122063E+10 | 965.27 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.134144E+11 | 13433.46 | 02-JAN-20:10 | 0.126520E+11 | 10029.21 | 02-JAN-20:10 |
February | 0.120349E+11 | 13433.46 | 01-FEB-20:10 | 0.114244E+11 | 10029.21 | 01-FEB-20:10 |
March | 0.132562E+11 | 13433.46 | 01-MAR-20:10 | 0.126824E+11 | 10029.21 | 01-MAR-20:10 |
April | 0.126592E+11 | 13433.46 | 03-APR-19:10 | 0.122282E+11 | 10029.21 | 03-APR-19:10 |
May | 0.129709E+11 | 13433.46 | 01-MAY-19:10 | 0.126672E+11 | 10029.21 | 01-MAY-19:10 |
June | 0.125139E+11 | 13433.46 | 01-JUN-19:10 | 0.122682E+11 | 10029.21 | 01-JUN-19:10 |
July | 0.128649E+11 | 13433.46 | 03-JUL-19:30 | 0.126273E+11 | 10029.21 | 03-JUL-19:10 |
August | 0.130493E+11 | 13433.46 | 01-AUG-19:30 | 0.126824E+11 | 10029.21 | 01-AUG-19:10 |
September | 0.127137E+11 | 13433.46 | 01-SEP-19:10 | 0.122282E+11 | 10029.21 | 01-SEP-19:10 |
October | 0.132912E+11 | 13433.46 | 02-OCT-19:10 | 0.126520E+11 | 10029.21 | 02-OCT-19:10 |
November | 0.129771E+11 | 13433.46 | 01-NOV-19:10 | 0.122624E+11 | 10029.21 | 01-NOV-19:10 |
December | 0.134298E+11 | 13433.46 | 01-DEC-20:10 | 0.126273E+11 | 10029.21 | 01-DEC-20:10 |
Annual Sum or Average | 0.155176E+12 | 0.149002E+12 | ||||
Minimum of Months | 0.120349E+11 | 13433.46 | 0.114244E+11 | 10029.21 | ||
Maximum of Months | 0.134298E+11 | 13433.46 | 0.126824E+11 | 10029.21 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220030E+09 | 258.74 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.198724E+09 | 258.74 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.219221E+09 | 258.74 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.213063E+09 | 258.74 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.219626E+09 | 258.74 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.212254E+09 | 258.74 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.220434E+09 | 258.74 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.219221E+09 | 258.74 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.213063E+09 | 258.74 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.220030E+09 | 258.74 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.212658E+09 | 258.74 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.220434E+09 | 258.74 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.258876E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.198724E+09 | 258.74 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.220434E+09 | 258.74 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220004E+09 | 258.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.198700E+09 | 258.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.219196E+09 | 258.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.213038E+09 | 258.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.219600E+09 | 258.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.212229E+09 | 258.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.220408E+09 | 258.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.219196E+09 | 258.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.213038E+09 | 258.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.220004E+09 | 258.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.212633E+09 | 258.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.220408E+09 | 258.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.258845E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.198700E+09 | 258.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.220408E+09 | 258.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.138280E+09 | 162.61 | 01-JAN-19:10 | 0.217935E+09 | 232.19 | 01-JAN-08:09 |
February | 0.124890E+09 | 162.61 | 01-FEB-20:10 | 0.196843E+09 | 232.19 | 01-FEB-07:10 |
March | 0.137772E+09 | 162.61 | 01-MAR-20:10 | 0.217824E+09 | 232.19 | 01-MAR-07:10 |
April | 0.133902E+09 | 162.61 | 01-APR-18:10 | 0.210923E+09 | 232.19 | 01-APR-07:10 |
May | 0.138026E+09 | 162.61 | 01-MAY-19:10 | 0.217879E+09 | 232.19 | 01-MAY-06:10 |
June | 0.133393E+09 | 162.61 | 01-JUN-19:10 | 0.210812E+09 | 232.19 | 01-JUN-06:10 |
July | 0.138534E+09 | 162.61 | 01-JUL-18:10 | 0.217991E+09 | 232.19 | 01-JUL-07:10 |
August | 0.137772E+09 | 162.61 | 01-AUG-19:10 | 0.217824E+09 | 232.19 | 01-AUG-06:10 |
September | 0.133902E+09 | 162.61 | 01-SEP-19:10 | 0.210923E+09 | 232.19 | 01-SEP-06:10 |
October | 0.138280E+09 | 162.61 | 01-OCT-18:10 | 0.217935E+09 | 232.19 | 01-OCT-07:10 |
November | 0.133648E+09 | 162.61 | 01-NOV-19:10 | 0.210867E+09 | 232.19 | 01-NOV-06:10 |
December | 0.138534E+09 | 162.61 | 01-DEC-20:10 | 0.217991E+09 | 232.19 | 01-DEC-07:10 |
Annual Sum or Average | 0.162693E+10 | 0.256575E+10 | ||||
Minimum of Months | 0.124890E+09 | 162.61 | 0.196843E+09 | 232.19 | ||
Maximum of Months | 0.138534E+09 | 162.61 | 0.217991E+09 | 232.19 |
Report: ZoneElectricSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.138318E+09 | 162.65 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.124924E+09 | 162.65 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.137810E+09 | 162.65 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.133938E+09 | 162.65 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.138064E+09 | 162.65 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.133430E+09 | 162.65 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.138572E+09 | 162.65 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.137810E+09 | 162.65 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.133938E+09 | 162.65 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.138318E+09 | 162.65 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.133684E+09 | 162.65 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.138572E+09 | 162.65 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.162738E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.124924E+09 | 162.65 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.138572E+09 | 162.65 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220030E+09 | 258.74 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.198724E+09 | 258.74 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.219221E+09 | 258.74 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.213063E+09 | 258.74 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.219626E+09 | 258.74 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.212254E+09 | 258.74 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.220434E+09 | 258.74 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.219221E+09 | 258.74 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.213063E+09 | 258.74 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.220030E+09 | 258.74 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.212658E+09 | 258.74 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.220434E+09 | 258.74 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.258876E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.198724E+09 | 258.74 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.220434E+09 | 258.74 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220004E+09 | 258.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.198700E+09 | 258.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.219196E+09 | 258.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.213038E+09 | 258.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.219600E+09 | 258.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.212229E+09 | 258.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.220408E+09 | 258.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.219196E+09 | 258.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.213038E+09 | 258.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.220004E+09 | 258.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.212633E+09 | 258.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.220408E+09 | 258.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.258845E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.198700E+09 | 258.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.220408E+09 | 258.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.140176E+10 | 1350.19 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.126566E+10 | 1350.19 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.140662E+10 | 1350.19 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.135424E+10 | 1350.19 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.140419E+10 | 1350.19 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.136045E+10 | 1350.19 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.139798E+10 | 1350.19 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.140662E+10 | 1350.19 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.135424E+10 | 1350.19 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.140176E+10 | 1350.19 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.135937E+10 | 1350.19 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.139798E+10 | 1350.19 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165109E+11 | ||||
Minimum of Months | 0.126566E+10 | 1350.19 | 0.00 | 0.00 | |
Maximum of Months | 0.140662E+10 | 1350.19 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220030E+09 | 258.74 | 01-JAN-19:10 | 0.222503E+09 | 237.06 | 01-JAN-08:09 |
February | 0.198724E+09 | 258.74 | 01-FEB-20:10 | 0.200969E+09 | 237.06 | 01-FEB-07:10 |
March | 0.219221E+09 | 258.74 | 01-MAR-20:10 | 0.222390E+09 | 237.06 | 01-MAR-07:10 |
April | 0.213063E+09 | 258.74 | 01-APR-18:10 | 0.215344E+09 | 237.06 | 01-APR-07:10 |
May | 0.219626E+09 | 258.74 | 01-MAY-19:10 | 0.222446E+09 | 237.06 | 01-MAY-06:10 |
June | 0.212254E+09 | 258.74 | 01-JUN-19:10 | 0.215230E+09 | 237.06 | 01-JUN-06:10 |
July | 0.220434E+09 | 258.74 | 01-JUL-18:10 | 0.222560E+09 | 237.06 | 01-JUL-07:10 |
August | 0.219221E+09 | 258.74 | 01-AUG-19:10 | 0.222390E+09 | 237.06 | 01-AUG-06:10 |
September | 0.213063E+09 | 258.74 | 01-SEP-19:10 | 0.215344E+09 | 237.06 | 01-SEP-06:10 |
October | 0.220030E+09 | 258.74 | 01-OCT-18:10 | 0.222503E+09 | 237.06 | 01-OCT-07:10 |
November | 0.212658E+09 | 258.74 | 01-NOV-19:10 | 0.215287E+09 | 237.06 | 01-NOV-06:10 |
December | 0.220434E+09 | 258.74 | 01-DEC-20:10 | 0.222560E+09 | 237.06 | 01-DEC-07:10 |
Annual Sum or Average | 0.258876E+10 | 0.261953E+10 | ||||
Minimum of Months | 0.198724E+09 | 258.74 | 0.200969E+09 | 237.06 | ||
Maximum of Months | 0.220434E+09 | 258.74 | 0.222560E+09 | 237.06 |
Report: ZoneElectricSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.220004E+09 | 258.71 | 01-JAN-19:10 | 0.222477E+09 | 237.03 | 01-JAN-08:09 |
February | 0.198700E+09 | 258.71 | 01-FEB-20:10 | 0.200945E+09 | 237.03 | 01-FEB-07:10 |
March | 0.219196E+09 | 258.71 | 01-MAR-20:10 | 0.222364E+09 | 237.03 | 01-MAR-07:10 |
April | 0.213038E+09 | 258.71 | 01-APR-18:10 | 0.215319E+09 | 237.03 | 01-APR-07:10 |
May | 0.219600E+09 | 258.71 | 01-MAY-19:10 | 0.222420E+09 | 237.03 | 01-MAY-06:10 |
June | 0.212229E+09 | 258.71 | 01-JUN-19:10 | 0.215205E+09 | 237.03 | 01-JUN-06:10 |
July | 0.220408E+09 | 258.71 | 01-JUL-18:10 | 0.222534E+09 | 237.03 | 01-JUL-07:10 |
August | 0.219196E+09 | 258.71 | 01-AUG-19:10 | 0.222364E+09 | 237.03 | 01-AUG-06:10 |
September | 0.213038E+09 | 258.71 | 01-SEP-19:10 | 0.215319E+09 | 237.03 | 01-SEP-06:10 |
October | 0.220004E+09 | 258.71 | 01-OCT-18:10 | 0.222477E+09 | 237.03 | 01-OCT-07:10 |
November | 0.212633E+09 | 258.71 | 01-NOV-19:10 | 0.215262E+09 | 237.03 | 01-NOV-06:10 |
December | 0.220408E+09 | 258.71 | 01-DEC-20:10 | 0.222534E+09 | 237.03 | 01-DEC-07:10 |
Annual Sum or Average | 0.258845E+10 | 0.261922E+10 | ||||
Minimum of Months | 0.198700E+09 | 258.71 | 0.200945E+09 | 237.03 | ||
Maximum of Months | 0.220408E+09 | 258.71 | 0.222534E+09 | 237.03 |
Report: ZoneElectricSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.138318E+09 | 162.65 | 01-JAN-19:10 | 0.217995E+09 | 232.26 | 01-JAN-08:09 |
February | 0.124924E+09 | 162.65 | 01-FEB-20:10 | 0.196897E+09 | 232.26 | 01-FEB-07:10 |
March | 0.137810E+09 | 162.65 | 01-MAR-20:10 | 0.217883E+09 | 232.26 | 01-MAR-07:10 |
April | 0.133938E+09 | 162.65 | 01-APR-18:10 | 0.210981E+09 | 232.26 | 01-APR-07:10 |
May | 0.138064E+09 | 162.65 | 01-MAY-19:10 | 0.217939E+09 | 232.26 | 01-MAY-06:10 |
June | 0.133430E+09 | 162.65 | 01-JUN-19:10 | 0.210869E+09 | 232.26 | 01-JUN-06:10 |
July | 0.138572E+09 | 162.65 | 01-JUL-18:10 | 0.218051E+09 | 232.26 | 01-JUL-07:10 |
August | 0.137810E+09 | 162.65 | 01-AUG-19:10 | 0.217883E+09 | 232.26 | 01-AUG-06:10 |
September | 0.133938E+09 | 162.65 | 01-SEP-19:10 | 0.210981E+09 | 232.26 | 01-SEP-06:10 |
October | 0.138318E+09 | 162.65 | 01-OCT-18:10 | 0.217995E+09 | 232.26 | 01-OCT-07:10 |
November | 0.133684E+09 | 162.65 | 01-NOV-19:10 | 0.210925E+09 | 232.26 | 01-NOV-06:10 |
December | 0.138572E+09 | 162.65 | 01-DEC-20:10 | 0.218051E+09 | 232.26 | 01-DEC-07:10 |
Annual Sum or Average | 0.162738E+10 | 0.256645E+10 | ||||
Minimum of Months | 0.124924E+09 | 162.65 | 0.196897E+09 | 232.26 | ||
Maximum of Months | 0.138572E+09 | 162.65 | 0.218051E+09 | 232.26 |
Report: ZoneElectricSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.213997E+10 | 2281.19 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.189487E+10 | 2281.19 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.201989E+10 | 2281.19 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.187228E+10 | 2281.19 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.183706E+10 | 2281.19 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.174854E+10 | 2281.19 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.180743E+10 | 2281.19 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.188108E+10 | 2281.19 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.191323E+10 | 2281.19 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.207024E+10 | 2281.19 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.205882E+10 | 2281.19 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.217372E+10 | 2281.19 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.234171E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.174854E+10 | 2281.19 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.217372E+10 | 2281.19 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.213997E+10 | 2281.19 | 02-JAN-20:10 | 0.149358E+11 | 6747.90 | 01-JAN-07:10 |
February | 0.189487E+10 | 2281.19 | 01-FEB-20:10 | 0.134904E+11 | 6747.90 | 01-FEB-07:10 |
March | 0.201989E+10 | 2281.19 | 01-MAR-20:10 | 0.149358E+11 | 6747.90 | 01-MAR-07:10 |
April | 0.187228E+10 | 2281.19 | 03-APR-19:10 | 0.144540E+11 | 6747.90 | 01-APR-06:10 |
May | 0.183706E+10 | 2281.19 | 01-MAY-19:10 | 0.149358E+11 | 6747.90 | 01-MAY-06:10 |
June | 0.174854E+10 | 2281.19 | 01-JUN-19:10 | 0.144540E+11 | 6747.90 | 01-JUN-06:10 |
July | 0.180743E+10 | 2281.19 | 03-JUL-19:30 | 0.149358E+11 | 6747.90 | 01-JUL-06:10 |
August | 0.188108E+10 | 2281.19 | 01-AUG-19:30 | 0.149358E+11 | 6747.90 | 01-AUG-06:10 |
September | 0.191323E+10 | 2281.19 | 01-SEP-19:10 | 0.144540E+11 | 6747.90 | 01-SEP-06:10 |
October | 0.207024E+10 | 2281.19 | 02-OCT-19:10 | 0.149358E+11 | 6747.90 | 01-OCT-06:10 |
November | 0.205882E+10 | 2281.19 | 01-NOV-19:10 | 0.144540E+11 | 6747.90 | 01-NOV-06:10 |
December | 0.217372E+10 | 2281.19 | 01-DEC-20:10 | 0.149358E+11 | 6747.90 | 01-DEC-07:10 |
Annual Sum or Average | 0.234171E+11 | 0.175857E+12 | ||||
Minimum of Months | 0.174854E+10 | 2281.19 | 0.134904E+11 | 6747.90 | ||
Maximum of Months | 0.217372E+10 | 2281.19 | 0.149358E+11 | 6747.90 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.110133E+10 | 1060.81 | 02-JAN-20:10 | 0.368383E+11 | 16487.34 | 01-JAN-07:10 |
February | 0.994403E+09 | 1060.81 | 01-FEB-20:10 | 0.332733E+11 | 16487.34 | 01-FEB-07:10 |
March | 0.110515E+10 | 1060.81 | 01-MAR-20:10 | 0.368383E+11 | 16487.34 | 01-MAR-07:10 |
April | 0.106399E+10 | 1060.81 | 03-APR-19:10 | 0.356500E+11 | 16487.34 | 01-APR-06:10 |
May | 0.110324E+10 | 1060.81 | 01-MAY-19:10 | 0.368383E+11 | 16487.34 | 01-MAY-06:10 |
June | 0.106887E+10 | 1060.81 | 01-JUN-19:10 | 0.356500E+11 | 16487.34 | 01-JUN-06:10 |
July | 0.109836E+10 | 1060.81 | 03-JUL-19:10 | 0.368383E+11 | 16487.34 | 01-JUL-06:10 |
August | 0.110515E+10 | 1060.81 | 01-AUG-19:10 | 0.368383E+11 | 16487.34 | 01-AUG-06:10 |
September | 0.106399E+10 | 1060.81 | 01-SEP-19:10 | 0.356500E+11 | 16487.34 | 01-SEP-06:10 |
October | 0.110133E+10 | 1060.81 | 02-OCT-19:10 | 0.368383E+11 | 16487.34 | 01-OCT-06:10 |
November | 0.106802E+10 | 1060.81 | 01-NOV-19:10 | 0.356500E+11 | 16487.34 | 01-NOV-06:10 |
December | 0.109836E+10 | 1060.81 | 01-DEC-20:10 | 0.368383E+11 | 16487.34 | 01-DEC-07:10 |
Annual Sum or Average | 0.129722E+11 | 0.433742E+12 | ||||
Minimum of Months | 0.994403E+09 | 1060.81 | 0.332733E+11 | 16487.34 | ||
Maximum of Months | 0.110515E+10 | 1060.81 | 0.368383E+11 | 16487.34 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [] | |
January | 0.148355E+10 | 1428.96 | 02-JAN-20:10 | 0.00 | 0.00 |
February | 0.133951E+10 | 1428.96 | 01-FEB-20:10 | 0.00 | 0.00 |
March | 0.148869E+10 | 1428.96 | 01-MAR-20:10 | 0.00 | 0.00 |
April | 0.143325E+10 | 1428.96 | 03-APR-19:10 | 0.00 | 0.00 |
May | 0.148612E+10 | 1428.96 | 01-MAY-19:10 | 0.00 | 0.00 |
June | 0.143982E+10 | 1428.96 | 01-JUN-19:10 | 0.00 | 0.00 |
July | 0.147955E+10 | 1428.96 | 03-JUL-19:10 | 0.00 | 0.00 |
August | 0.148869E+10 | 1428.96 | 01-AUG-19:10 | 0.00 | 0.00 |
September | 0.143325E+10 | 1428.96 | 01-SEP-19:10 | 0.00 | 0.00 |
October | 0.148355E+10 | 1428.96 | 02-OCT-19:10 | 0.00 | 0.00 |
November | 0.143868E+10 | 1428.96 | 01-NOV-19:10 | 0.00 | 0.00 |
December | 0.147955E+10 | 1428.96 | 01-DEC-20:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.174742E+11 | ||||
Minimum of Months | 0.133951E+10 | 1428.96 | 0.00 | 0.00 | |
Maximum of Months | 0.148869E+10 | 1428.96 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.195762E+11 | 0.140591E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.176991E+11 | 0.126941E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196590E+11 | 0.141079E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189781E+11 | 0.135824E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.196176E+11 | 0.140835E+11 | 0.121662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190195E+11 | 0.136447E+11 | 0.117829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195762E+11 | 0.140212E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196590E+11 | 0.141079E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.189781E+11 | 0.135824E+11 | 0.117446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195762E+11 | 0.140591E+11 | 0.121516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189367E+11 | 0.136339E+11 | 0.117774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195762E+11 | 0.140212E+11 | 0.121279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230852E+12 | 0.165597E+12 | 0.143109E+12 | ||||||
Minimum of Months | 0.176991E+11 | 0.126941E+11 | 0.109726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196590E+11 | 0.141079E+11 | 0.121808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.199054E+10 | 0.715050E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225660E+10 |
February | 0.179968E+10 | 0.645625E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169051E+10 |
March | 0.199896E+10 | 0.717530E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134992E+10 |
April | 0.192973E+10 | 0.690807E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8221209.20 | 0.895147E+09 |
May | 0.199475E+10 | 0.716290E+09 | 0.865939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12225492.82 | 0.453851E+09 |
June | 0.193394E+10 | 0.693975E+09 | 0.838659E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69040068.14 | 0.220930E+09 |
July | 0.199054E+10 | 0.713122E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64944408.47 | 0.120276E+09 |
August | 0.199896E+10 | 0.717530E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57498304.71 | 0.173661E+09 |
September | 0.192973E+10 | 0.690807E+09 | 0.835931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29137147.24 | 0.423011E+09 |
October | 0.199054E+10 | 0.715050E+09 | 0.864900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.35 | 0.892523E+09 |
November | 0.192552E+10 | 0.693424E+09 | 0.838269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133738E+10 |
December | 0.199054E+10 | 0.713122E+09 | 0.863211E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191860E+10 |
Annual Sum or Average | 0.234734E+11 | 0.842233E+10 | 0.101859E+11 | 0.241067E+09 | 0.117324E+11 | ||||
Minimum of Months | 0.179968E+10 | 0.645625E+09 | 0.780982E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120276E+09 |
Maximum of Months | 0.199896E+10 | 0.717530E+09 | 0.866978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69040068.14 | 0.225660E+10 |
Report: SpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.230505E+10 | 0.828031E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.477301E+09 |
February | 0.208403E+10 | 0.747637E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358732E+09 |
March | 0.231480E+10 | 0.830902E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292492E+09 |
April | 0.223463E+10 | 0.799957E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2168536.01 | 0.199749E+09 |
May | 0.230993E+10 | 0.829467E+09 | 0.100276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2758798.32 | 0.110125E+09 |
June | 0.223950E+10 | 0.803626E+09 | 0.971170E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14497125.33 | 57017815.07 |
July | 0.230505E+10 | 0.825798E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13822120.18 | 34769723.86 |
August | 0.231480E+10 | 0.830902E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13101338.37 | 46747710.30 |
September | 0.223463E+10 | 0.799957E+09 | 0.968011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7680993.71 | 0.100605E+09 |
October | 0.230505E+10 | 0.828031E+09 | 0.100156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11244.72 | 0.201089E+09 |
November | 0.222975E+10 | 0.802987E+09 | 0.970719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290583E+09 |
December | 0.230505E+10 | 0.825798E+09 | 0.999601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407229E+09 |
Annual Sum or Average | 0.271823E+11 | 0.975309E+10 | 0.117953E+11 | 54040156.64 | 0.257644E+10 | ||||
Minimum of Months | 0.208403E+10 | 0.747637E+09 | 0.904380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34769723.86 |
Maximum of Months | 0.231480E+10 | 0.830902E+09 | 0.100396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14497125.33 | 0.477301E+09 |
Report: SpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148942E+10 |
February | 0.139600E+10 | 0.304734E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111328E+10 |
March | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937574E+09 |
April | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 7828630.86 | 0.634215E+09 |
May | 0.154732E+10 | 0.338087E+09 | 0.577559E+10 | 0.501759E+11 | 0.00 | 0.00 | 0.00 | 9865328.39 | 0.341381E+09 |
June | 0.150015E+10 | 0.327554E+09 | 0.559364E+10 | 0.485952E+11 | 0.00 | 0.00 | 0.00 | 50603367.94 | 0.169841E+09 |
July | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 50516007.69 | 97083748.69 |
August | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 49684630.28 | 0.133227E+09 |
September | 0.149688E+10 | 0.326059E+09 | 0.557545E+10 | 0.484372E+11 | 0.00 | 0.00 | 0.00 | 30132981.90 | 0.304459E+09 |
October | 0.154405E+10 | 0.337502E+09 | 0.576866E+10 | 0.501157E+11 | 0.00 | 0.00 | 0.00 | 253334.63 | 0.628559E+09 |
November | 0.149361E+10 | 0.327294E+09 | 0.559104E+10 | 0.485726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.922728E+09 |
December | 0.154405E+10 | 0.336592E+09 | 0.575740E+10 | 0.500179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130700E+10 |
Annual Sum or Average | 0.182082E+11 | 0.397532E+10 | 0.679373E+11 | 0.590211E+12 | 0.198884E+09 | 0.807877E+10 | |||
Minimum of Months | 0.139600E+10 | 0.304734E+09 | 0.520895E+10 | 0.452532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97083748.69 |
Maximum of Months | 0.155059E+10 | 0.338672E+09 | 0.578252E+10 | 0.502361E+11 | 0.00 | 0.00 | 0.00 | 50603367.94 | 0.148942E+10 |
Report: SpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.261570E+11 | 0.104804E+10 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574157E+10 |
February | 0.236489E+11 | 0.905989E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435222E+10 |
March | 0.262677E+11 | 0.932048E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351530E+10 |
April | 0.253579E+11 | 0.830748E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19959965.22 | 0.239402E+10 |
May | 0.262123E+11 | 0.766894E+09 | 0.121917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27656862.17 | 0.132681E+10 |
June | 0.254132E+11 | 0.720078E+09 | 0.118076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160243E+09 | 0.696269E+09 |
July | 0.261570E+11 | 0.745343E+09 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149124E+09 | 0.433479E+09 |
August | 0.262677E+11 | 0.806644E+09 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132117E+09 | 0.577878E+09 |
September | 0.253579E+11 | 0.870625E+09 | 0.117692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70917507.46 | 0.122195E+10 |
October | 0.261570E+11 | 0.980476E+09 | 0.121771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242663E+10 |
November | 0.253025E+11 | 0.999158E+09 | 0.118021E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347482E+10 |
December | 0.261570E+11 | 0.106719E+10 | 0.121533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489163E+10 |
Annual Sum or Average | 0.308456E+12 | 0.106732E+11 | 0.143409E+11 | 0.560018E+09 | 0.310526E+11 | ||||
Minimum of Months | 0.236489E+11 | 0.720078E+09 | 0.109956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433479E+09 |
Maximum of Months | 0.262677E+11 | 0.106719E+10 | 0.122063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160243E+09 | 0.574157E+10 |
Report: SpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.776503E+11 | 0.134144E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115639E+11 |
February | 0.702046E+11 | 0.120349E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874484E+10 |
March | 0.779788E+11 | 0.132562E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717003E+10 |
April | 0.752779E+11 | 0.126592E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49384738.41 | 0.491156E+10 |
May | 0.778146E+11 | 0.129709E+11 | 0.126672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62003318.72 | 0.275842E+10 |
June | 0.754422E+11 | 0.125139E+11 | 0.122682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338063E+09 | 0.144996E+10 |
July | 0.776503E+11 | 0.128649E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321859E+09 | 0.901817E+09 |
August | 0.779788E+11 | 0.130493E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300244E+09 | 0.119259E+10 |
September | 0.752779E+11 | 0.127137E+11 | 0.122282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174745E+09 | 0.250950E+10 |
October | 0.776503E+11 | 0.132912E+11 | 0.126520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36394.38 | 0.497160E+10 |
November | 0.751137E+11 | 0.129771E+11 | 0.122624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711057E+10 |
December | 0.776503E+11 | 0.134298E+11 | 0.126273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991239E+10 |
Annual Sum or Average | 0.915690E+12 | 0.155176E+12 | 0.149002E+12 | 0.124634E+10 | 0.631972E+11 | ||||
Minimum of Months | 0.702046E+11 | 0.120349E+11 | 0.114244E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901817E+09 |
Maximum of Months | 0.779788E+11 | 0.134298E+11 | 0.126824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338063E+09 | 0.115639E+11 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664466E+09 |
February | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507578E+09 |
March | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393512E+09 |
April | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3132640.64 | 0.262165E+09 |
May | 0.303504E+09 | 0.219626E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3441081.58 | 0.138640E+09 |
June | 0.293842E+09 | 0.212254E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21553164.91 | 66593668.34 |
July | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20233407.49 | 35757744.96 |
August | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18793408.33 | 49897586.66 |
September | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11530851.73 | 0.122086E+09 |
October | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20913.52 | 0.258930E+09 |
November | 0.293661E+09 | 0.212658E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389419E+09 |
December | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555781E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258876E+10 | 0.261953E+10 | 78705468.21 | 0.344482E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35757744.96 |
Maximum of Months | 0.303685E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21553164.91 | 0.664466E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662666E+09 |
February | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503828E+09 |
March | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389760E+09 |
April | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2607971.98 | 0.261902E+09 |
May | 0.303504E+09 | 0.219600E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2662495.33 | 0.143317E+09 |
June | 0.293842E+09 | 0.212229E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18701315.08 | 74116437.49 |
July | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14988604.38 | 47480515.20 |
August | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14854053.77 | 59788042.22 |
September | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9975961.23 | 0.125262E+09 |
October | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11357.65 | 0.254958E+09 |
November | 0.293661E+09 | 0.212633E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386440E+09 |
December | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552710E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258845E+10 | 0.261922E+10 | 63801759.41 | 0.346223E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47480515.20 |
Maximum of Months | 0.303685E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18701315.08 | 0.662666E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.138280E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166272E+09 |
February | 0.00 | 0.124890E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139451E+09 |
March | 0.00 | 0.137772E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117159E+09 |
April | 0.00 | 0.133902E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 171430.01 | 93134212.19 |
May | 0.00 | 0.138026E+09 | 0.217879E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 131923.97 | 63112134.75 |
June | 0.00 | 0.133393E+09 | 0.210812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444753.27 | 37947239.99 |
July | 0.00 | 0.138534E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 543348.22 | 29310915.46 |
August | 0.00 | 0.137772E+09 | 0.217824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 768423.34 | 33992209.58 |
September | 0.00 | 0.133902E+09 | 0.210923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 704319.03 | 55845710.41 |
October | 0.00 | 0.138280E+09 | 0.217935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98217893.54 |
November | 0.00 | 0.133648E+09 | 0.210867E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121856E+09 |
December | 0.00 | 0.138534E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142824E+09 |
Annual Sum or Average | 0.00 | 0.162693E+10 | 0.256575E+10 | 3764197.85 | 0.109912E+10 | ||||
Minimum of Months | 0.00 | 0.124890E+09 | 0.196843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29310915.46 |
Maximum of Months | 0.00 | 0.138534E+09 | 0.217991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1444753.27 | 0.166272E+09 |
Report: SpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185759E+09 |
February | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141426E+09 |
March | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110077E+09 |
April | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 776483.34 | 73518455.72 |
May | 0.303504E+09 | 0.138064E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 820381.45 | 39209423.35 |
June | 0.293842E+09 | 0.133430E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5387977.32 | 19757951.79 |
July | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4550918.16 | 11713056.17 |
August | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4473400.60 | 15424984.55 |
September | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2975818.17 | 34646601.82 |
October | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12910.38 | 71936042.63 |
November | 0.293661E+09 | 0.133684E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109241E+09 |
December | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155487E+09 |
Annual Sum or Average | 0.357224E+10 | 0.162738E+10 | 0.256645E+10 | 18997889.42 | 0.968196E+09 | ||||
Minimum of Months | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11713056.17 |
Maximum of Months | 0.303685E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5387977.32 | 0.185759E+09 |
Report: SpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664261E+09 |
February | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507048E+09 |
March | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394710E+09 |
April | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3129884.61 | 0.262982E+09 |
May | 0.303504E+09 | 0.219626E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3428191.57 | 0.140198E+09 |
June | 0.293842E+09 | 0.212254E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21510571.79 | 67266091.45 |
July | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20197325.45 | 36199559.97 |
August | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18747230.69 | 50399363.40 |
September | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11518072.10 | 0.123037E+09 |
October | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21557.01 | 0.259796E+09 |
November | 0.293661E+09 | 0.212658E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389306E+09 |
December | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555474E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258876E+10 | 0.261953E+10 | 78552833.21 | 0.345068E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36199559.97 |
Maximum of Months | 0.303685E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21510571.79 | 0.664261E+09 |
Report: SpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662484E+09 |
February | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503036E+09 |
March | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390791E+09 |
April | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2665118.09 | 0.261986E+09 |
May | 0.303504E+09 | 0.219600E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2755673.01 | 0.143050E+09 |
June | 0.293842E+09 | 0.212229E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18800860.11 | 73058299.04 |
July | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15484007.39 | 44779987.21 |
August | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15244679.80 | 57032936.69 |
September | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10179349.66 | 0.124980E+09 |
October | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11841.07 | 0.255309E+09 |
November | 0.293661E+09 | 0.212633E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386291E+09 |
December | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552605E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258845E+10 | 0.261922E+10 | 65141529.14 | 0.345540E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44779987.21 |
Maximum of Months | 0.303685E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18800860.11 | 0.662484E+09 |
Report: SpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.664883E+09 |
February | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507934E+09 |
March | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393046E+09 |
April | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3074933.78 | 0.262555E+09 |
May | 0.303504E+09 | 0.219626E+09 | 0.222446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3357329.99 | 0.140113E+09 |
June | 0.293842E+09 | 0.212254E+09 | 0.215230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21174470.82 | 67508322.77 |
July | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19742854.44 | 36510662.52 |
August | 0.303685E+09 | 0.219221E+09 | 0.222390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18378462.40 | 50676446.86 |
September | 0.293479E+09 | 0.213063E+09 | 0.215344E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11312055.67 | 0.122776E+09 |
October | 0.303322E+09 | 0.220030E+09 | 0.222503E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19158.93 | 0.259081E+09 |
November | 0.293661E+09 | 0.212658E+09 | 0.215287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389167E+09 |
December | 0.303141E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555721E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258876E+10 | 0.261953E+10 | 77059266.03 | 0.344997E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198724E+09 | 0.200969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36510662.52 |
Maximum of Months | 0.303685E+09 | 0.220434E+09 | 0.222560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21174470.82 | 0.664883E+09 |
Report: SpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.663564E+09 |
February | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504480E+09 |
March | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389668E+09 |
April | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2528436.39 | 0.262773E+09 |
May | 0.303504E+09 | 0.219600E+09 | 0.222420E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2571939.99 | 0.146721E+09 |
June | 0.293842E+09 | 0.212229E+09 | 0.215205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18280790.53 | 77512860.70 |
July | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14447992.97 | 52319216.75 |
August | 0.303685E+09 | 0.219196E+09 | 0.222364E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14333881.07 | 64214298.42 |
September | 0.293479E+09 | 0.213038E+09 | 0.215319E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9716812.81 | 0.127484E+09 |
October | 0.303322E+09 | 0.220004E+09 | 0.222477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8863.11 | 0.254821E+09 |
November | 0.293661E+09 | 0.212633E+09 | 0.215262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386450E+09 |
December | 0.303141E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553449E+09 |
Annual Sum or Average | 0.357224E+10 | 0.258845E+10 | 0.261922E+10 | 61888716.88 | 0.348346E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.198700E+09 | 0.200945E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52319216.75 |
Maximum of Months | 0.303685E+09 | 0.220408E+09 | 0.222534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18280790.53 | 0.663564E+09 |
Report: SpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344630E+09 |
February | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264003E+09 |
March | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204385E+09 |
April | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1569728.25 | 0.135517E+09 |
May | 0.303504E+09 | 0.138064E+09 | 0.217939E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1719589.56 | 71969449.20 |
June | 0.293842E+09 | 0.133430E+09 | 0.210869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10852070.09 | 34639903.22 |
July | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10124643.72 | 18608688.75 |
August | 0.303685E+09 | 0.137810E+09 | 0.217883E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9400788.04 | 25900081.44 |
September | 0.293479E+09 | 0.133938E+09 | 0.210981E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5766680.10 | 63451679.68 |
October | 0.303322E+09 | 0.138318E+09 | 0.217995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3767.45 | 0.134785E+09 |
November | 0.293661E+09 | 0.133684E+09 | 0.210925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202510E+09 |
December | 0.303141E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288189E+09 |
Annual Sum or Average | 0.357224E+10 | 0.162738E+10 | 0.256645E+10 | 39437267.21 | 0.178859E+10 | ||||
Minimum of Months | 0.273974E+09 | 0.124924E+09 | 0.196897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18608688.75 |
Maximum of Months | 0.303685E+09 | 0.138572E+09 | 0.218051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10852070.09 | 0.344630E+09 |
Report: SpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.213997E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170736E+10 |
February | 0.415303E+11 | 0.189487E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129522E+10 |
March | 0.461292E+11 | 0.201989E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107782E+10 |
April | 0.445315E+11 | 0.187228E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5702202.81 | 0.745911E+09 |
May | 0.460320E+11 | 0.183706E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5570139.51 | 0.431998E+09 |
June | 0.446286E+11 | 0.174854E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34838560.55 | 0.234482E+09 |
July | 0.459349E+11 | 0.180743E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28663404.67 | 0.154735E+09 |
August | 0.461292E+11 | 0.188108E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 29937799.82 | 0.192399E+09 |
September | 0.445315E+11 | 0.191323E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20769134.56 | 0.382154E+09 |
October | 0.459349E+11 | 0.207024E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28660.05 | 0.739319E+09 |
November | 0.444343E+11 | 0.205882E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106056E+10 |
December | 0.459349E+11 | 0.217372E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147527E+10 |
Annual Sum or Average | 0.541686E+12 | 0.234171E+11 | 0.175857E+12 | 0.125510E+09 | 0.949723E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.174854E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154735E+09 |
Maximum of Months | 0.461292E+11 | 0.217372E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34838560.55 | 0.170736E+10 |
Report: SpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.459349E+11 | 0.213997E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171994E+10 |
February | 0.415303E+11 | 0.189487E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130422E+10 |
March | 0.461292E+11 | 0.201989E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108702E+10 |
April | 0.445315E+11 | 0.187228E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5312432.24 | 0.752467E+09 |
May | 0.460320E+11 | 0.183706E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5115562.77 | 0.437309E+09 |
June | 0.446286E+11 | 0.174854E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33220082.99 | 0.237467E+09 |
July | 0.459349E+11 | 0.180743E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26632910.65 | 0.157251E+09 |
August | 0.461292E+11 | 0.188108E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27696141.61 | 0.195415E+09 |
September | 0.445315E+11 | 0.191323E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19516003.00 | 0.386491E+09 |
October | 0.459349E+11 | 0.207024E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6952.02 | 0.746279E+09 |
November | 0.444343E+11 | 0.205882E+10 | 0.144540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107024E+10 |
December | 0.459349E+11 | 0.217372E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148803E+10 |
Annual Sum or Average | 0.541686E+12 | 0.234171E+11 | 0.175857E+12 | 0.117500E+09 | 0.958213E+10 | ||||
Minimum of Months | 0.415303E+11 | 0.174854E+10 | 0.134904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157251E+09 |
Maximum of Months | 0.461292E+11 | 0.217372E+10 | 0.149358E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33220082.99 | 0.171994E+10 |
Report: SpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154273E+10 |
February | 0.369574E+10 | 0.994403E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116325E+10 |
March | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976780E+09 |
April | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 4130835.55 | 0.674439E+09 |
May | 0.409635E+10 | 0.110324E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 3919678.46 | 0.390383E+09 |
June | 0.397146E+10 | 0.106887E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 27850526.09 | 0.206078E+09 |
July | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21168688.49 | 0.132023E+09 |
August | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 21673153.47 | 0.168685E+09 |
September | 0.396281E+10 | 0.106399E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 15183684.99 | 0.343269E+09 |
October | 0.408770E+10 | 0.110133E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.670901E+09 |
November | 0.395417E+10 | 0.106802E+10 | 0.322775E+11 | 0.295556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961957E+09 |
December | 0.408770E+10 | 0.109836E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134385E+10 |
Annual Sum or Average | 0.482041E+11 | 0.129722E+11 | 0.392709E+12 | 0.359593E+12 | 93926567.05 | 0.857434E+10 | |||
Minimum of Months | 0.369574E+10 | 0.994403E+09 | 0.301256E+11 | 0.275852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132023E+09 |
Maximum of Months | 0.410499E+10 | 0.110515E+10 | 0.333534E+11 | 0.305408E+11 | 0.00 | 0.00 | 0.00 | 27850526.09 | 0.154273E+10 |
Report: SpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104475E+10 |
February | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772031E+09 |
March | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622445E+09 |
April | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5555514.34 | 0.416230E+09 |
May | 0.00 | 0.157202E+10 | 0.106025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6767563.17 | 0.224426E+09 |
June | 0.00 | 0.152304E+10 | 0.102685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34165114.27 | 0.114412E+09 |
July | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32979286.14 | 66586171.81 |
August | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31414578.95 | 91992695.17 |
September | 0.00 | 0.151609E+10 | 0.102351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18960750.06 | 0.205797E+09 |
October | 0.00 | 0.156929E+10 | 0.105898E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 111676.51 | 0.416138E+09 |
November | 0.00 | 0.152183E+10 | 0.102637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621886E+09 |
December | 0.00 | 0.156506E+10 | 0.105691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883223E+09 |
Annual Sum or Average | 0.184842E+11 | 0.124715E+11 | 0.129954E+09 | 0.547991E+10 | |||||
Minimum of Months | 0.00 | 0.141693E+10 | 0.956227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66586171.81 |
Maximum of Months | 0.00 | 0.157474E+10 | 0.106152E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34165114.27 | 0.104475E+10 |
Report: SpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.195080E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724733E+09 |
February | 0.00 | 0.176140E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534675E+09 |
March | 0.00 | 0.195757E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429834E+09 |
April | 0.00 | 0.188466E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3865691.14 | 0.285344E+09 |
May | 0.00 | 0.195419E+09 | 0.305852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4704858.96 | 0.150678E+09 |
June | 0.00 | 0.189331E+09 | 0.296217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23672940.39 | 76861274.36 |
July | 0.00 | 0.194554E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22841075.20 | 44552997.29 |
August | 0.00 | 0.195757E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21701892.42 | 61550773.18 |
September | 0.00 | 0.188466E+09 | 0.295253E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13066640.72 | 0.138352E+09 |
October | 0.00 | 0.195080E+09 | 0.305485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 79988.34 | 0.281034E+09 |
November | 0.00 | 0.189180E+09 | 0.296079E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428764E+09 |
December | 0.00 | 0.194554E+09 | 0.304889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.613460E+09 |
Annual Sum or Average | 0.229778E+10 | 0.359769E+10 | 89933087.18 | 0.376984E+10 | |||||
Minimum of Months | 0.00 | 0.176140E+09 | 0.275845E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44552997.29 |
Maximum of Months | 0.00 | 0.195757E+09 | 0.306219E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23672940.39 | 0.724733E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.140176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.803757E+09 |
February | 0.00 | 0.126566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599616E+09 |
March | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475948E+09 |
April | 0.00 | 0.135424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4799379.51 | 0.313537E+09 |
May | 0.00 | 0.140419E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6158602.76 | 0.157909E+09 |
June | 0.00 | 0.136045E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32045235.21 | 75397993.10 |
July | 0.00 | 0.139798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32561446.44 | 38843035.46 |
August | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30568531.08 | 55506762.05 |
September | 0.00 | 0.135424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17657468.09 | 0.141548E+09 |
October | 0.00 | 0.140176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109013.20 | 0.306250E+09 |
November | 0.00 | 0.135937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472313E+09 |
December | 0.00 | 0.139798E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678383E+09 |
Annual Sum or Average | 0.165109E+11 | 0.123900E+09 | 0.411901E+10 | ||||||
Minimum of Months | 0.00 | 0.126566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38843035.46 |
Maximum of Months | 0.00 | 0.140662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32561446.44 | 0.803757E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.148355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142206E+10 |
February | 0.00 | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105181E+10 |
March | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846048E+09 |
April | 0.00 | 0.143325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6728575.93 | 0.562832E+09 |
May | 0.00 | 0.148612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7447088.76 | 0.292717E+09 |
June | 0.00 | 0.143982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40022274.52 | 0.149291E+09 |
July | 0.00 | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35845606.26 | 86431484.44 |
August | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37275895.15 | 0.115353E+09 |
September | 0.00 | 0.143325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22721218.45 | 0.262947E+09 |
October | 0.00 | 0.148355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64644.76 | 0.548445E+09 |
November | 0.00 | 0.143868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839394E+09 |
December | 0.00 | 0.147955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120559E+10 |
Annual Sum or Average | 0.174742E+11 | 0.150105E+09 | 0.738292E+10 | ||||||
Minimum of Months | 0.00 | 0.133951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86431484.44 |
Maximum of Months | 0.00 | 0.148869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40022274.52 | 0.142206E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 11501.89 | 02-JAN-00:10 | 13541.81 | 02-JAN-20:10 | 9632.53 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11501.89 | 01-FEB-00:10 | 13541.81 | 01-FEB-20:10 | 9632.53 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11501.89 | 01-MAR-00:10 | 13541.81 | 01-MAR-20:10 | 9632.53 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 11501.89 | 01-APR-00:10 | 13541.81 | 03-APR-19:10 | 9632.53 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11501.89 | 01-MAY-00:10 | 13541.81 | 01-MAY-19:10 | 9632.53 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11501.89 | 01-JUN-00:10 | 13541.81 | 01-JUN-19:10 | 9632.53 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11501.89 | 01-JUL-00:10 | 13541.81 | 03-JUL-19:10 | 9632.53 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11501.89 | 01-AUG-00:10 | 13541.81 | 01-AUG-19:10 | 9632.53 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11501.89 | 01-SEP-00:10 | 13541.81 | 01-SEP-19:10 | 9632.53 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 11501.89 | 02-OCT-00:10 | 13541.81 | 02-OCT-19:10 | 9632.53 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11501.89 | 01-NOV-00:10 | 13541.81 | 01-NOV-19:10 | 9632.53 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11501.89 | 01-DEC-00:10 | 13541.81 | 01-DEC-20:10 | 9632.53 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 11501.89 | 13541.81 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 11501.89 | 13541.81 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1169.53 | 02-JAN-00:10 | 688.74 | 02-JAN-20:10 | 685.60 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1238.69 | 30-JAN-12:30 |
February | 1169.53 | 01-FEB-00:10 | 688.74 | 01-FEB-20:10 | 685.60 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1331.79 | 02-FEB-06:00 |
March | 1169.53 | 01-MAR-00:10 | 688.74 | 01-MAR-20:10 | 685.60 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 985.25 | 06-MAR-01:00 |
April | 1169.53 | 01-APR-00:10 | 688.74 | 03-APR-19:10 | 685.60 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.23 | 15-APR-17:00 | 702.32 | 03-APR-06:00 |
May | 1169.53 | 01-MAY-00:10 | 688.74 | 01-MAY-19:10 | 685.60 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.30 | 31-MAY-13:00 | 495.32 | 03-MAY-03:00 |
June | 1169.53 | 01-JUN-00:10 | 688.74 | 01-JUN-19:10 | 685.60 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.34 | 11-JUN-15:00 | 376.76 | 03-JUN-04:00 |
July | 1169.53 | 01-JUL-00:10 | 688.74 | 03-JUL-19:10 | 685.60 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.38 | 26-JUL-15:00 | 256.63 | 23-JUL-04:00 |
August | 1169.53 | 01-AUG-00:10 | 688.74 | 01-AUG-19:10 | 685.60 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.45 | 04-AUG-16:00 | 297.74 | 07-AUG-06:00 |
September | 1169.53 | 01-SEP-00:10 | 688.74 | 01-SEP-19:10 | 685.60 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.95 | 07-SEP-14:00 | 537.13 | 30-SEP-01:00 |
October | 1169.53 | 02-OCT-00:10 | 688.74 | 02-OCT-19:10 | 685.60 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 21-OCT-15:00 | 599.66 | 23-OCT-06:00 |
November | 1169.53 | 01-NOV-00:10 | 688.74 | 01-NOV-19:10 | 685.60 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1185.57 | 26-NOV-07:00 |
December | 1169.53 | 01-DEC-00:10 | 688.74 | 01-DEC-20:10 | 685.60 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 1150.14 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1169.53 | 688.74 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.63 | |||||
Maximum of Months | 1169.53 | 688.74 | 685.60 | 0.00 | 0.00 | 0.00 | 0.00 | 217.34 | 1331.79 |
Report: PeakSpaceGainsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1354.32 | 02-JAN-00:10 | 797.56 | 02-JAN-20:10 | 793.93 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 265.94 | 31-JAN-04:00 |
February | 1354.32 | 01-FEB-00:10 | 797.56 | 01-FEB-20:10 | 793.93 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 292.77 | 02-FEB-06:00 |
March | 1354.32 | 01-MAR-00:10 | 797.56 | 01-MAR-20:10 | 793.93 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 209.19 | 06-MAR-01:00 |
April | 1354.32 | 01-APR-00:10 | 797.56 | 03-APR-19:10 | 793.93 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.69 | 15-APR-16:00 | 150.31 | 03-APR-21:00 |
May | 1354.32 | 01-MAY-00:10 | 797.56 | 01-MAY-19:10 | 793.93 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.03 | 31-MAY-13:00 | 111.66 | 03-MAY-03:00 |
June | 1354.32 | 01-JUN-00:10 | 797.56 | 01-JUN-19:10 | 793.93 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 11-JUN-15:00 | 88.73 | 01-JUN-05:00 |
July | 1354.32 | 01-JUL-00:10 | 797.56 | 03-JUL-19:10 | 793.93 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.23 | 26-JUL-15:00 | 63.25 | 24-JUL-05:00 |
August | 1354.32 | 01-AUG-00:10 | 797.56 | 01-AUG-19:10 | 793.93 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 04-AUG-15:00 | 72.45 | 07-AUG-06:00 |
September | 1354.32 | 01-SEP-00:10 | 797.56 | 01-SEP-19:10 | 793.93 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.96 | 06-SEP-14:00 | 120.59 | 30-SEP-01:00 |
October | 1354.32 | 02-OCT-00:10 | 797.56 | 02-OCT-19:10 | 793.93 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 20-OCT-15:00 | 132.74 | 23-OCT-06:00 |
November | 1354.32 | 01-NOV-00:10 | 797.56 | 01-NOV-19:10 | 793.93 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 261.26 | 26-NOV-07:00 |
December | 1354.32 | 01-DEC-00:10 | 797.56 | 01-DEC-20:10 | 793.93 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 246.19 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1354.32 | 797.56 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.25 | |||||
Maximum of Months | 1354.32 | 797.56 | 793.93 | 0.00 | 0.00 | 0.00 | 0.00 | 50.96 | 292.77 |
Report: PeakSpaceGainsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 907.20 | 02-JAN-00:10 | 325.08 | 02-JAN-20:10 | 4572.80 | 02-JAN-20:10 | 39726.58 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 821.92 | 05-JAN-21:00 |
February | 907.20 | 01-FEB-00:10 | 325.08 | 01-FEB-20:10 | 4572.80 | 01-FEB-20:10 | 39726.58 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 813.90 | 02-FEB-21:00 |
March | 907.20 | 01-MAR-00:10 | 325.08 | 01-MAR-20:10 | 4572.80 | 01-MAR-20:10 | 39726.58 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 664.48 | 05-MAR-23:00 |
April | 907.20 | 01-APR-00:10 | 325.08 | 03-APR-19:10 | 4572.80 | 03-APR-19:10 | 39726.58 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 124.44 | 15-APR-15:00 | 499.24 | 03-APR-06:10 |
May | 907.20 | 01-MAY-00:10 | 325.08 | 01-MAY-19:10 | 4572.80 | 01-MAY-19:10 | 39726.58 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 125.16 | 31-MAY-13:00 | 347.34 | 03-MAY-05:10 |
June | 907.20 | 01-JUN-00:10 | 325.08 | 01-JUN-19:10 | 4572.80 | 01-JUN-19:10 | 39726.58 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 168.72 | 11-JUN-15:00 | 273.03 | 01-JUN-05:10 |
July | 907.20 | 01-JUL-00:10 | 325.08 | 03-JUL-19:10 | 4572.80 | 03-JUL-19:10 | 39726.58 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 126.14 | 26-JUL-16:00 | 201.05 | 24-JUL-05:10 |
August | 907.20 | 01-AUG-00:10 | 325.08 | 01-AUG-19:10 | 4572.80 | 01-AUG-19:10 | 39726.58 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 176.51 | 04-AUG-15:07 | 237.23 | 07-AUG-06:00 |
September | 907.20 | 01-SEP-00:10 | 325.08 | 01-SEP-19:10 | 4572.80 | 01-SEP-19:10 | 39726.58 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 156.06 | 06-SEP-15:00 | 373.35 | 29-SEP-06:00 |
October | 907.20 | 02-OCT-00:10 | 325.08 | 02-OCT-19:10 | 4572.80 | 02-OCT-19:10 | 39726.58 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 32.71 | 20-OCT-15:00 | 434.03 | 23-OCT-06:00 |
November | 907.20 | 01-NOV-00:10 | 325.08 | 01-NOV-19:10 | 4572.80 | 01-NOV-19:10 | 39726.58 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 809.17 | 25-NOV-21:10 |
December | 907.20 | 01-DEC-00:10 | 325.08 | 01-DEC-20:10 | 4572.80 | 01-DEC-20:10 | 39726.58 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 800.83 | 08-DEC-21:00 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 201.05 | ||||||
Maximum of Months | 907.20 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 176.51 | 821.92 |
Report: PeakSpaceGainsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 15368.40 | 02-JAN-00:10 | 1299.02 | 02-JAN-20:10 | 965.27 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 3241.69 | 31-JAN-04:00 |
February | 15368.40 | 01-FEB-00:10 | 1299.02 | 01-FEB-20:10 | 965.27 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 3548.45 | 02-FEB-06:00 |
March | 15368.40 | 01-MAR-00:10 | 1299.02 | 01-MAR-20:10 | 965.27 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 2486.40 | 06-MAR-01:00 |
April | 15368.40 | 01-APR-00:10 | 1299.02 | 03-APR-19:10 | 965.27 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.72 | 15-APR-16:00 | 1784.86 | 03-APR-05:00 |
May | 15368.40 | 01-MAY-00:10 | 1299.02 | 01-MAY-19:10 | 965.27 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.41 | 31-MAY-13:00 | 1351.87 | 03-MAY-03:00 |
June | 15368.40 | 01-JUN-00:10 | 1299.02 | 01-JUN-19:10 | 965.27 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 567.03 | 11-JUN-15:00 | 1089.25 | 01-JUN-05:00 |
July | 15368.40 | 01-JUL-00:10 | 1299.02 | 03-JUL-19:30 | 965.27 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.74 | 26-JUL-15:00 | 791.96 | 24-JUL-05:00 |
August | 15368.40 | 01-AUG-00:10 | 1299.02 | 01-AUG-19:30 | 965.27 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.42 | 04-AUG-15:00 | 888.76 | 07-AUG-04:00 |
September | 15368.40 | 01-SEP-00:10 | 1299.02 | 01-SEP-19:10 | 965.27 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.61 | 07-SEP-14:00 | 1441.90 | 30-SEP-01:00 |
October | 15368.40 | 02-OCT-00:10 | 1299.02 | 02-OCT-19:10 | 965.27 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 1540.74 | 23-OCT-06:00 |
November | 15368.40 | 01-NOV-00:10 | 1299.02 | 01-NOV-19:10 | 965.27 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 3081.64 | 26-NOV-07:00 |
December | 15368.40 | 01-DEC-00:10 | 1299.02 | 01-DEC-20:10 | 965.27 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 2923.35 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 15368.40 | 1299.02 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791.96 | |||||
Maximum of Months | 15368.40 | 1299.02 | 965.27 | 0.00 | 0.00 | 0.00 | 0.00 | 567.03 | 3548.45 |
Report: PeakSpaceGainsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 45622.98 | 02-JAN-00:10 | 13433.46 | 02-JAN-20:10 | 10029.21 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 6448.46 | 31-JAN-04:00 |
February | 45622.98 | 01-FEB-00:10 | 13433.46 | 01-FEB-20:10 | 10029.21 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 7091.89 | 02-FEB-06:00 |
March | 45622.98 | 01-MAR-00:10 | 13433.46 | 01-MAR-20:10 | 10029.21 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 5103.90 | 06-MAR-01:00 |
April | 45622.98 | 01-APR-00:10 | 13433.46 | 03-APR-19:10 | 10029.21 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 825.52 | 15-APR-16:00 | 3692.33 | 03-APR-05:00 |
May | 45622.98 | 01-MAY-00:10 | 13433.46 | 01-MAY-19:10 | 10029.21 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 878.48 | 31-MAY-13:00 | 2765.03 | 03-MAY-03:00 |
June | 45622.98 | 01-JUN-00:10 | 13433.46 | 01-JUN-19:10 | 10029.21 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1213.86 | 11-JUN-15:00 | 2203.20 | 01-JUN-05:00 |
July | 45622.98 | 01-JUL-00:10 | 13433.46 | 03-JUL-19:30 | 10029.21 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 861.76 | 26-JUL-15:00 | 1598.57 | 24-JUL-05:00 |
August | 45622.98 | 01-AUG-00:10 | 13433.46 | 01-AUG-19:30 | 10029.21 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.44 | 04-AUG-15:00 | 1799.39 | 07-AUG-04:00 |
September | 45622.98 | 01-SEP-00:10 | 13433.46 | 01-SEP-19:10 | 10029.21 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1024.97 | 06-SEP-14:00 | 2983.87 | 30-SEP-01:00 |
October | 45622.98 | 02-OCT-00:10 | 13433.46 | 02-OCT-19:10 | 10029.21 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.37 | 20-OCT-15:00 | 3248.77 | 23-OCT-06:00 |
November | 45622.98 | 01-NOV-00:10 | 13433.46 | 01-NOV-19:10 | 10029.21 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6280.61 | 26-NOV-07:00 |
December | 45622.98 | 01-DEC-00:10 | 13433.46 | 01-DEC-20:10 | 10029.21 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 5940.02 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 45622.98 | 13433.46 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1598.57 | |||||
Maximum of Months | 45622.98 | 13433.46 | 10029.21 | 0.00 | 0.00 | 0.00 | 0.00 | 1220.44 | 7091.89 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 416.64 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 258.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 467.00 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 258.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.80 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 258.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 258.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:10 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 258.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 258.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 258.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 06-SEP-15:10 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 258.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 258.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.19 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 258.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.73 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 467.00 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 413.17 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 258.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 462.91 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 258.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.77 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 258.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:10 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 258.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:10 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 258.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 258.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:10 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 258.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:10 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 258.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:08 | 177.37 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 258.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.16 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 258.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 462.91 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 01-JAN-00:10 | 162.61 | 01-JAN-19:10 | 232.19 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 104.56 | 31-JAN-04:00 |
February | 0.00 | 01-FEB-00:10 | 162.61 | 01-FEB-20:10 | 232.19 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 120.85 | 02-FEB-07:10 |
March | 0.00 | 01-MAR-00:10 | 162.61 | 01-MAR-20:10 | 232.19 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 73.31 | 06-MAR-01:00 |
April | 0.00 | 01-APR-00:10 | 162.61 | 01-APR-18:10 | 232.19 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 15-APR-15:00 | 62.89 | 01-APR-05:00 |
May | 0.00 | 01-MAY-00:10 | 162.61 | 01-MAY-19:10 | 232.19 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 | 31-MAY-13:00 | 49.83 | 03-MAY-03:00 |
June | 0.00 | 01-JUN-00:10 | 162.61 | 01-JUN-19:10 | 232.19 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 | 11-JUN-15:00 | 41.42 | 01-JUN-05:00 |
July | 0.00 | 01-JUL-00:10 | 162.61 | 01-JUL-18:10 | 232.19 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.86 | 26-JUL-15:00 | 31.90 | 24-JUL-03:00 |
August | 0.00 | 01-AUG-00:10 | 162.61 | 01-AUG-19:10 | 232.19 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 04-AUG-15:00 | 35.40 | 07-AUG-06:00 |
September | 0.00 | 01-SEP-00:10 | 162.61 | 01-SEP-19:10 | 232.19 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 07-SEP-14:00 | 52.57 | 30-SEP-01:00 |
October | 0.00 | 01-OCT-00:10 | 162.61 | 01-OCT-18:10 | 232.19 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 58.20 | 23-OCT-06:00 |
November | 0.00 | 01-NOV-00:10 | 162.61 | 01-NOV-19:10 | 232.19 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 103.37 | 26-NOV-07:00 |
December | 0.00 | 01-DEC-00:10 | 162.61 | 01-DEC-20:10 | 232.19 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 94.83 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 0.00 | 162.61 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 | |||||
Maximum of Months | 0.00 | 162.61 | 232.19 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 120.85 |
Report: PeakSpaceGainsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 162.65 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 113.89 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 162.65 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 129.02 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 162.65 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 81.16 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 162.65 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.54 | 15-APR-15:10 | 57.94 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 162.65 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 | 31-MAY-15:10 | 40.95 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 162.65 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.04 | 11-JUN-15:10 | 31.20 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 162.65 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | 26-JUL-15:10 | 21.35 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 162.65 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 04-AUG-15:10 | 24.72 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 162.65 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 | 06-SEP-15:08 | 44.37 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 162.65 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.27 | 20-OCT-15:08 | 49.50 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 162.65 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 109.69 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 162.65 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 95.37 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.35 | |||||
Maximum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 129.02 |
Report: PeakSpaceGainsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 413.49 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 258.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 464.67 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 258.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.80 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 258.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.69 | 15-APR-15:10 | 207.59 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.71 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 258.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.40 | 11-JUN-15:08 | 111.81 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 258.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.46 | 26-JUL-15:10 | 76.51 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 258.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:08 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 258.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.94 | 06-SEP-15:10 | 158.99 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 258.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.38 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 258.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.19 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 258.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.74 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | |||||
Maximum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 464.67 |
Report: PeakSpaceGainsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 409.65 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 258.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 460.44 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 258.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 290.77 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 258.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.68 | 15-APR-15:07 | 207.57 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 | 31-MAY-15:10 | 146.70 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 258.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.39 | 11-JUN-15:08 | 111.80 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 258.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 26-JUL-15:10 | 76.50 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 258.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 04-AUG-15:08 | 88.58 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 258.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 06-SEP-15:08 | 158.98 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 258.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.73 | 20-OCT-15:10 | 177.37 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 258.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 394.63 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 258.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 341.71 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.50 | |||||
Maximum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.44 | 460.44 |
Report: PeakSpaceGainsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.74 | 01-JAN-19:10 | 237.06 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 416.48 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 258.74 | 01-FEB-20:10 | 237.06 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 467.09 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 258.74 | 01-MAR-20:10 | 237.06 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.33 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 258.74 | 01-APR-18:10 | 237.06 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.33 | 15-APR-15:10 | 208.08 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.74 | 01-MAY-19:10 | 237.06 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.88 | 31-MAY-15:10 | 147.18 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 258.74 | 01-JUN-19:10 | 237.06 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.24 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 258.74 | 01-JUL-18:10 | 237.06 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.09 | 26-JUL-15:10 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 258.74 | 01-AUG-19:10 | 237.06 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 04-AUG-15:10 | 89.02 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 258.74 | 01-SEP-19:10 | 237.06 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 | 06-SEP-15:10 | 159.45 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 258.74 | 01-OCT-18:10 | 237.06 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-OCT-15:10 | 177.85 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 258.74 | 01-NOV-19:10 | 237.06 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.78 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 258.74 | 01-DEC-20:10 | 237.06 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.29 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 258.74 | 237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 | 467.09 |
Report: PeakSpaceGainsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 258.71 | 01-JAN-19:10 | 237.03 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 412.46 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 258.71 | 01-FEB-20:10 | 237.03 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 462.24 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 258.71 | 01-MAR-20:10 | 237.03 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 291.30 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 258.71 | 01-APR-18:10 | 237.03 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 15-APR-15:10 | 208.06 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 258.71 | 01-MAY-19:10 | 237.03 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.87 | 31-MAY-15:10 | 147.16 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 258.71 | 01-JUN-19:10 | 237.03 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.04 | 11-JUN-15:10 | 112.23 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 258.71 | 01-JUL-18:10 | 237.03 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 26-JUL-15:10 | 76.93 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 258.71 | 01-AUG-19:10 | 237.03 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 04-AUG-15:10 | 89.01 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 258.71 | 01-SEP-19:10 | 237.03 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.57 | 06-SEP-15:10 | 159.44 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 258.71 | 01-OCT-18:10 | 237.03 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 20-OCT-15:08 | 177.84 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 258.71 | 01-NOV-19:10 | 237.03 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 395.46 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 258.71 | 01-DEC-20:10 | 237.03 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 342.26 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 | |||||
Maximum of Months | 180.00 | 258.71 | 237.03 | 0.00 | 0.00 | 0.00 | 0.00 | 79.08 | 462.24 |
Report: PeakSpaceGainsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 180.00 | 01-JAN-00:10 | 162.65 | 01-JAN-19:10 | 232.26 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 214.10 | 31-JAN-04:00 |
February | 180.00 | 01-FEB-00:10 | 162.65 | 01-FEB-20:10 | 232.26 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 241.04 | 02-FEB-08:00 |
March | 180.00 | 01-MAR-00:10 | 162.65 | 01-MAR-20:10 | 232.26 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 149.04 | 06-MAR-01:00 |
April | 180.00 | 01-APR-00:10 | 162.65 | 01-APR-18:10 | 232.26 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 15-APR-15:10 | 106.45 | 03-APR-06:00 |
May | 180.00 | 01-MAY-00:10 | 162.65 | 01-MAY-19:10 | 232.26 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.56 | 31-MAY-15:10 | 75.29 | 03-MAY-03:00 |
June | 180.00 | 01-JUN-00:10 | 162.65 | 01-JUN-19:10 | 232.26 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.39 | 11-JUN-15:10 | 57.42 | 03-JUN-04:00 |
July | 180.00 | 01-JUL-00:10 | 162.65 | 01-JUL-18:10 | 232.26 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.69 | 26-JUL-15:10 | 39.36 | 23-JUL-04:00 |
August | 180.00 | 01-AUG-00:10 | 162.65 | 01-AUG-19:10 | 232.26 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 04-AUG-15:10 | 45.54 | 07-AUG-06:00 |
September | 180.00 | 01-SEP-00:10 | 162.65 | 01-SEP-19:10 | 232.26 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 | 06-SEP-15:10 | 81.58 | 30-SEP-01:00 |
October | 180.00 | 01-OCT-00:10 | 162.65 | 01-OCT-18:10 | 232.26 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.90 | 20-OCT-15:10 | 90.99 | 23-OCT-06:00 |
November | 180.00 | 01-NOV-00:10 | 162.65 | 01-NOV-19:10 | 232.26 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 202.48 | 26-NOV-07:00 |
December | 180.00 | 01-DEC-00:10 | 162.65 | 01-DEC-20:10 | 232.26 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 175.11 | 10-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | |||||
Maximum of Months | 180.00 | 162.65 | 232.26 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 | 241.04 |
Report: PeakSpaceGainsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2281.19 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 932.30 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2281.19 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1022.87 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2281.19 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 759.98 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2281.19 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.82 | 15-APR-16:00 | 559.66 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2281.19 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.93 | 31-MAY-13:00 | 409.66 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2281.19 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.56 | 11-JUN-15:00 | 322.82 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2281.19 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.95 | 26-JUL-15:00 | 236.17 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2281.19 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.05 | 04-AUG-15:00 | 265.91 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2281.19 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.21 | 06-SEP-14:00 | 439.68 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 2281.19 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.49 | 20-OCT-15:00 | 485.40 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2281.19 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 904.82 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2281.19 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 884.22 | 08-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.17 | |||||
Maximum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 154.05 | 1022.87 |
Report: PeakSpaceGainsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 26988.77 | 02-JAN-00:10 | 2281.19 | 02-JAN-20:10 | 6747.90 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 930.16 | 31-JAN-04:00 |
February | 26988.77 | 01-FEB-00:10 | 2281.19 | 01-FEB-20:10 | 6747.90 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1019.39 | 02-FEB-06:00 |
March | 26988.77 | 01-MAR-00:10 | 2281.19 | 01-MAR-20:10 | 6747.90 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 764.80 | 06-MAR-01:00 |
April | 26988.77 | 01-APR-00:10 | 2281.19 | 03-APR-19:10 | 6747.90 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.80 | 15-APR-16:00 | 559.68 | 03-APR-06:00 |
May | 26988.77 | 01-MAY-00:10 | 2281.19 | 01-MAY-19:10 | 6747.90 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.45 | 31-MAY-13:00 | 409.66 | 03-MAY-03:00 |
June | 26988.77 | 01-JUN-00:10 | 2281.19 | 01-JUN-19:10 | 6747.90 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.63 | 11-JUN-15:00 | 322.83 | 03-JUN-04:00 |
July | 26988.77 | 01-JUL-00:10 | 2281.19 | 03-JUL-19:30 | 6747.90 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.01 | 26-JUL-15:00 | 236.17 | 23-JUL-04:00 |
August | 26988.77 | 01-AUG-00:10 | 2281.19 | 01-AUG-19:30 | 6747.90 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.90 | 04-AUG-15:00 | 265.91 | 07-AUG-06:00 |
September | 26988.77 | 01-SEP-00:10 | 2281.19 | 01-SEP-19:10 | 6747.90 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.22 | 06-SEP-14:00 | 439.69 | 30-SEP-01:00 |
October | 26988.77 | 02-OCT-00:10 | 2281.19 | 02-OCT-19:10 | 6747.90 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 20-OCT-15:00 | 485.41 | 23-OCT-06:00 |
November | 26988.77 | 01-NOV-00:10 | 2281.19 | 01-NOV-19:10 | 6747.90 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 905.04 | 26-NOV-07:00 |
December | 26988.77 | 01-DEC-00:10 | 2281.19 | 01-DEC-20:10 | 6747.90 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 884.22 | 08-DEC-24:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.17 | |||||
Maximum of Months | 26988.77 | 2281.19 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 150.90 | 1019.39 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2401.70 | 02-JAN-00:10 | 1060.81 | 02-JAN-20:10 | 14912.86 | 01-JAN-07:10 | 22492.83 | 01-JAN-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 816.12 | 05-JAN-21:13 |
February | 2401.70 | 01-FEB-00:10 | 1060.81 | 01-FEB-20:10 | 14912.86 | 01-FEB-07:10 | 22492.83 | 01-FEB-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 813.49 | 02-FEB-21:00 |
March | 2401.70 | 01-MAR-00:10 | 1060.81 | 01-MAR-20:10 | 14912.86 | 01-MAR-07:10 | 22492.83 | 01-MAR-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 663.49 | 05-MAR-24:00 |
April | 2401.70 | 01-APR-00:10 | 1060.81 | 03-APR-19:10 | 14912.86 | 01-APR-06:10 | 22492.83 | 01-APR-15:09 | 0.00 | 0.00 | 0.00 | 81.42 | 15-APR-15:40 | 500.91 | 03-APR-06:00 |
May | 2401.70 | 01-MAY-00:10 | 1060.81 | 01-MAY-19:10 | 14912.86 | 01-MAY-06:10 | 22492.83 | 01-MAY-15:09 | 0.00 | 0.00 | 0.00 | 81.87 | 31-MAY-13:00 | 353.42 | 03-MAY-05:10 |
June | 2401.70 | 01-JUN-00:10 | 1060.81 | 01-JUN-19:10 | 14912.86 | 01-JUN-06:10 | 22492.83 | 01-JUN-15:09 | 0.00 | 0.00 | 0.00 | 125.89 | 11-JUN-15:00 | 284.39 | 01-JUN-05:00 |
July | 2401.70 | 01-JUL-00:10 | 1060.81 | 03-JUL-19:10 | 14912.86 | 01-JUL-06:10 | 22492.83 | 01-JUL-15:09 | 0.00 | 0.00 | 0.00 | 82.54 | 26-JUL-15:40 | 207.37 | 24-JUL-05:00 |
August | 2401.70 | 01-AUG-00:10 | 1060.81 | 01-AUG-19:10 | 14912.86 | 01-AUG-06:10 | 22492.83 | 01-AUG-15:09 | 0.00 | 0.00 | 0.00 | 133.72 | 04-AUG-15:40 | 237.96 | 07-AUG-06:00 |
September | 2401.70 | 01-SEP-00:10 | 1060.81 | 01-SEP-19:10 | 14912.86 | 01-SEP-06:10 | 22492.83 | 01-SEP-15:09 | 0.00 | 0.00 | 0.00 | 112.49 | 06-SEP-14:40 | 374.97 | 29-SEP-23:10 |
October | 2401.70 | 02-OCT-00:10 | 1060.81 | 02-OCT-19:10 | 14912.86 | 01-OCT-06:10 | 22492.83 | 01-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 434.43 | 23-OCT-06:00 |
November | 2401.70 | 01-NOV-00:10 | 1060.81 | 01-NOV-19:10 | 14912.86 | 01-NOV-06:10 | 22492.83 | 01-NOV-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 807.67 | 25-NOV-21:07 |
December | 2401.70 | 01-DEC-00:10 | 1060.81 | 01-DEC-20:10 | 14912.86 | 01-DEC-07:10 | 22492.83 | 01-DEC-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 791.56 | 09-DEC-08:04 |
Annual Sum or Average | |||||||||||||||
Minimum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 0.00 | 207.37 | ||||||
Maximum of Months | 2401.70 | 1060.81 | 14912.86 | 22492.83 | 0.00 | 0.00 | 0.00 | 133.72 | 816.12 |
Report: PeakSpaceGainsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1511.55 | 02-JAN-20:10 | 839.45 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 593.88 | 30-JAN-08:00 |
February | 0.00 | 1511.55 | 01-FEB-20:10 | 839.45 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 651.11 | 02-FEB-07:20 |
March | 0.00 | 1511.55 | 01-MAR-20:10 | 839.45 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 455.21 | 06-MAR-01:00 |
April | 0.00 | 1511.55 | 03-APR-19:10 | 839.45 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.24 | 15-APR-16:40 | 324.51 | 03-APR-06:00 |
May | 0.00 | 1511.55 | 01-MAY-19:10 | 839.45 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.46 | 31-MAY-13:00 | 231.01 | 03-MAY-03:00 |
June | 0.00 | 1511.55 | 01-JUN-19:10 | 839.45 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.71 | 11-JUN-15:00 | 184.38 | 01-JUN-05:00 |
July | 0.00 | 1511.55 | 03-JUL-19:10 | 839.45 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.33 | 26-JUL-15:00 | 129.43 | 23-JUL-04:00 |
August | 0.00 | 1511.55 | 01-AUG-19:10 | 839.45 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.19 | 04-AUG-15:00 | 151.21 | 07-AUG-06:00 |
September | 0.00 | 1511.55 | 01-SEP-19:10 | 839.45 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.81 | 06-SEP-14:00 | 253.73 | 30-SEP-01:00 |
October | 0.00 | 1511.55 | 02-OCT-19:10 | 839.45 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 20-OCT-15:00 | 282.16 | 23-OCT-06:00 |
November | 0.00 | 1511.55 | 01-NOV-19:10 | 839.45 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 586.04 | 26-NOV-07:00 |
December | 0.00 | 1511.55 | 01-DEC-20:10 | 839.45 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 535.22 | 10-DEC-06:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.43 | ||||
Maximum of Months | 0.00 | 1511.55 | 839.45 | 0.00 | 0.00 | 0.00 | 0.00 | 114.19 | 651.11 |
Report: PeakSpaceGainsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 187.90 | 02-JAN-20:10 | 242.16 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 412.66 | 31-JAN-04:00 |
February | 0.00 | 187.90 | 01-FEB-20:10 | 242.16 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 453.59 | 02-FEB-06:02 |
March | 0.00 | 187.90 | 01-MAR-20:10 | 242.16 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 316.50 | 06-MAR-01:00 |
April | 0.00 | 187.90 | 03-APR-19:10 | 242.16 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 15-APR-17:00 | 225.62 | 03-APR-06:00 |
May | 0.00 | 187.90 | 01-MAY-19:10 | 242.16 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.39 | 31-MAY-13:00 | 159.13 | 03-MAY-03:00 |
June | 0.00 | 187.90 | 01-JUN-19:10 | 242.16 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.69 | 11-JUN-15:00 | 126.69 | 01-JUN-05:00 |
July | 0.00 | 187.90 | 03-JUL-19:10 | 242.16 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.32 | 26-JUL-15:00 | 88.10 | 23-JUL-04:00 |
August | 0.00 | 187.90 | 01-AUG-19:10 | 242.16 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.76 | 04-AUG-15:00 | 102.75 | 07-AUG-06:00 |
September | 0.00 | 187.90 | 01-SEP-19:10 | 242.16 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.56 | 06-SEP-14:00 | 172.55 | 30-SEP-01:00 |
October | 0.00 | 187.90 | 02-OCT-19:10 | 242.16 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 20-OCT-15:00 | 192.62 | 23-OCT-06:00 |
November | 0.00 | 187.90 | 01-NOV-19:10 | 242.16 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 407.93 | 26-NOV-07:00 |
December | 0.00 | 187.90 | 01-DEC-20:10 | 242.16 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 370.23 | 10-DEC-06:00 |
Annual Sum or Average | |||||||||||||
Minimum of Months | 0.00 | 187.90 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 | ||||
Maximum of Months | 0.00 | 187.90 | 242.16 | 0.00 | 0.00 | 0.00 | 0.00 | 77.76 | 453.59 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1350.19 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 469.74 | 31-JAN-04:00 |
February | 0.00 | 1350.19 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 523.11 | 02-FEB-06:02 |
March | 0.00 | 1350.19 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 350.62 | 06-MAR-01:00 |
April | 0.00 | 1350.19 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 | 15-APR-17:00 | 250.03 | 03-APR-06:00 |
May | 0.00 | 1350.19 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 | 31-MAY-13:00 | 176.45 | 03-MAY-03:00 |
June | 0.00 | 1350.19 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.99 | 11-JUN-15:00 | 134.27 | 03-JUN-04:00 |
July | 0.00 | 1350.19 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.94 | 26-JUL-15:00 | 91.59 | 23-JUL-04:00 |
August | 0.00 | 1350.19 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.30 | 04-AUG-15:00 | 106.19 | 07-AUG-06:00 |
September | 0.00 | 1350.19 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.63 | 06-SEP-15:00 | 191.30 | 30-SEP-01:00 |
October | 0.00 | 1350.19 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 | 20-OCT-15:00 | 213.51 | 23-OCT-06:00 |
November | 0.00 | 1350.19 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 454.57 | 26-NOV-07:00 |
December | 0.00 | 1350.19 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 409.23 | 08-DEC-21:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.59 | |||
Maximum of Months | 0.00 | 1350.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.30 | 523.11 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 1428.96 | 02-JAN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 793.66 | 31-JAN-04:00 |
February | 0.00 | 1428.96 | 01-FEB-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 870.15 | 02-FEB-06:00 |
March | 0.00 | 1428.96 | 01-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 621.55 | 06-MAR-01:00 |
April | 0.00 | 1428.96 | 03-APR-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.04 | 15-APR-17:00 | 443.52 | 03-APR-06:00 |
May | 0.00 | 1428.96 | 01-MAY-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.81 | 31-MAY-13:00 | 313.22 | 03-MAY-03:00 |
June | 0.00 | 1428.96 | 01-JUN-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.92 | 11-JUN-15:00 | 244.01 | 01-JUN-05:00 |
July | 0.00 | 1428.96 | 03-JUL-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.72 | 26-JUL-15:00 | 168.86 | 24-JUL-03:00 |
August | 0.00 | 1428.96 | 01-AUG-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.08 | 04-AUG-15:00 | 193.40 | 07-AUG-06:00 |
September | 0.00 | 1428.96 | 01-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.29 | 06-SEP-15:00 | 339.49 | 30-SEP-01:00 |
October | 0.00 | 1428.96 | 02-OCT-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 | 20-OCT-15:00 | 378.86 | 23-OCT-06:00 |
November | 0.00 | 1428.96 | 01-NOV-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 782.19 | 26-NOV-07:00 |
December | 0.00 | 1428.96 | 01-DEC-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 725.36 | 09-DEC-01:00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 0.00 | 1428.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.86 | |||
Maximum of Months | 0.00 | 1428.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.08 | 870.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38605.97 | 19-JAN-01:51 | 115018.92 | 22569.69 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33783.49 | 02-FEB-06:02 | 44729.58 | 30092.92 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12967.71 | 25-MAR-15:00 | 3833.96 | 3761.61 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13985.07 | 15-APR-21:10 | 8945.92 | 9027.87 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14348.88 | 31-MAY-21:10 | 11501.89 | 9027.87 | 7097.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15286.85 | 08-JUN-20:00 | 17891.83 | 27083.62 | 19265.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15519.71 | 12-JUL-21:00 | 10223.90 | 12037.17 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16383.03 | 09-AUG-20:00 | 8945.92 | 13541.81 | 9632.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18874.01 | 29-SEP-21:00 | 10223.90 | 12037.17 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20162.74 | 18-OCT-21:00 | 10223.90 | 12037.17 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 38794.11 | 25-NOV-21:33 | 26837.75 | 31597.56 | 24334.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17367.82 | 07-DEC-22:00 | 10223.90 | 12037.17 | 9125.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12967.71 | 3833.96 | 3761.61 | 3548.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38794.11 | 115018.92 | 31597.56 | 25348.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2011.29 | 12-JAN-12:30 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.32 |
February | 2607.26 | 08-FEB-13:20 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.37 |
March | 2136.43 | 24-MAR-13:10 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.07 |
April | 2947.92 | 15-APR-13:20 | 779.69 | 382.63 | 505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 100.40 | 0.00 |
May | 2074.95 | 31-MAY-18:40 | 7277.09 | 4897.71 | 5196.15 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 | 0.00 |
June | 2206.33 | 26-JUN-18:40 | 909.64 | 612.21 | 649.52 | 0.00 | 0.00 | 0.00 | 0.00 | 115.58 | 0.00 |
July | 2180.99 | 30-JUL-13:20 | 259.90 | 153.05 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 74.49 | 0.00 |
August | 2428.20 | 29-AUG-13:30 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 |
September | 3795.65 | 07-SEP-12:50 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 162.55 | 0.00 |
October | 3946.11 | 20-OCT-12:50 | 259.90 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.40 |
November | 3572.03 | 04-NOV-13:10 | 389.84 | 191.32 | 252.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.03 |
December | 2994.65 | 03-DEC-13:00 | 389.84 | 229.58 | 288.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.91 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2011.29 | 259.90 | 153.05 | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3946.11 | 7277.09 | 4897.71 | 5196.15 | 0.00 | 0.00 | 0.00 | 0.00 | 162.55 | 522.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2025.02 | 05-JAN-21:23 | 4815.36 | 2835.78 | 3008.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.28 |
February | 1828.55 | 02-FEB-06:00 | 1354.32 | 177.24 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.77 |
March | 1270.42 | 25-MAR-15:00 | 451.44 | 221.55 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 |
April | 1562.12 | 15-APR-21:10 | 1053.36 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
May | 1598.98 | 31-MAY-21:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
June | 1647.26 | 30-JUN-21:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.99 |
July | 1636.98 | 03-JUL-21:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 0.00 |
August | 1626.04 | 22-AUG-21:00 | 1203.84 | 708.95 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
September | 1769.75 | 07-SEP-21:00 | 1203.84 | 708.95 | 752.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
October | 1437.85 | 20-OCT-16:00 | 752.40 | 221.55 | 292.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 |
November | 2297.51 | 25-NOV-21:11 | 7373.52 | 4342.29 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.00 |
December | 1080.90 | 05-DEC-22:10 | 1354.32 | 531.71 | 585.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1080.90 | 451.44 | 177.24 | 250.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2297.51 | 7373.52 | 4342.29 | 4680.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 292.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1023.14 | 19-JAN-08:00 | 0.00 | 839.75 | 530.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.28 |
February | 1043.57 | 02-FEB-07:20 | 0.00 | 1679.50 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.11 |
March | 1124.94 | 25-MAR-15:00 | 0.00 | 419.88 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.98 |
April | 1411.61 | 16-APR-20:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | 0.00 |
May | 1454.92 | 31-MAY-21:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
June | 1521.06 | 30-JUN-21:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
July | 1506.70 | 03-JUL-21:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 0.00 |
August | 1501.79 | 03-AUG-21:10 | 0.00 | 1007.70 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 | 0.00 |
September | 1506.08 | 07-SEP-21:00 | 0.00 | 1343.60 | 795.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.54 |
October | 1260.78 | 20-OCT-15:00 | 0.00 | 419.88 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 0.00 |
November | 1169.79 | 08-NOV-22:10 | 0.00 | 1007.70 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.87 |
December | 874.02 | 04-DEC-22:10 | 0.00 | 1007.70 | 618.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 874.02 | 0.00 | 419.88 | 309.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1521.06 | 0.00 | 1679.50 | 1060.35 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 651.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 318.39 | 13-JAN-22:00 | 0.00 | 167.02 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.08 |
February | 341.20 | 24-FEB-22:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.40 |
March | 474.32 | 25-MAR-15:00 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 |
April | 580.01 | 16-APR-21:10 | 0.00 | 104.39 | 152.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.20 |
May | 594.85 | 31-MAY-21:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.82 |
June | 624.62 | 30-JUN-21:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
July | 620.62 | 03-JUL-21:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 10.44 | 0.00 |
August | 617.55 | 03-AUG-21:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 11.43 | 0.00 |
September | 617.70 | 07-SEP-21:10 | 0.00 | 125.27 | 178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.99 |
October | 536.86 | 20-OCT-15:00 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 0.00 |
November | 462.14 | 03-NOV-14:00 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.74 |
December | 283.15 | 03-DEC-13:00 | 0.00 | 62.63 | 101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.41 |
Annual Sum or Average | |||||||||||
Minimum of Months | 283.15 | 0.00 | 52.20 | 89.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 624.62 | 0.00 | 167.02 | 229.41 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 146.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 40042.47 | 05-JAN-21:32 | 4032.00 | 1444.82 | 21660.63 | 188178.52 | 0.00 | 0.00 | 0.00 | 0.00 | 801.19 |
February | 36389.51 | 24-FEB-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 345.86 |
March | 36891.84 | 28-MAR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 188.09 |
April | 37828.56 | 18-APR-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 82.42 |
May | 38077.87 | 31-MAY-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 5.62 | 0.00 |
June | 38247.46 | 26-JUN-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.49 | 0.00 |
July | 38115.21 | 03-JUL-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 38.01 | 0.00 |
August | 38129.64 | 03-AUG-20:00 | 1411.20 | 650.17 | 9145.60 | 79453.15 | 0.00 | 0.00 | 0.00 | 14.06 | 0.00 |
September | 38219.87 | 07-SEP-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
October | 37632.87 | 20-OCT-20:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 131.19 |
November | 38369.90 | 25-NOV-21:11 | 4939.20 | 1769.90 | 26955.46 | 234177.71 | 0.00 | 0.00 | 0.00 | 0.00 | 796.20 |
December | 35863.22 | 04-DEC-21:00 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 349.44 |
Annual Sum or Average | |||||||||||
Minimum of Months | 35863.22 | 705.60 | 325.08 | 4572.80 | 39726.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40042.47 | 4939.20 | 1769.90 | 26955.46 | 234177.71 | 0.00 | 0.00 | 0.00 | 38.49 | 801.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8381.50 | 12-JAN-12:30 | 3415.20 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1318.27 |
February | 10382.23 | 08-FEB-13:20 | 3415.20 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.41 |
March | 9184.37 | 25-MAR-13:40 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.14 |
April | 11571.51 | 15-APR-13:00 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 233.81 | 0.00 |
May | 9465.26 | 31-MAY-21:20 | 153684.00 | 8660.12 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.31 |
June | 10465.80 | 26-JUN-21:12 | 153684.00 | 8660.12 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 | 0.00 |
July | 10210.22 | 25-JUL-21:12 | 153684.00 | 8660.12 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 107.03 | 0.00 |
August | 10193.84 | 02-AUG-21:12 | 153684.00 | 8660.12 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 | 0.00 |
September | 12897.31 | 16-SEP-13:00 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 236.06 | 0.00 |
October | 13935.07 | 20-OCT-12:40 | 3415.20 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.25 |
November | 14178.50 | 04-NOV-12:40 | 5122.80 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.22 |
December | 12023.24 | 03-DEC-12:50 | 5122.80 | 95.26 | 406.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8381.50 | 3415.20 | 79.38 | 355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14178.50 | 153684.00 | 8660.12 | 7112.54 | 0.00 | 0.00 | 0.00 | 0.00 | 236.06 | 1318.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 54172.80 | 19-JAN-01:51 | 456229.80 | 22389.11 | 26392.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5904.76 |
February | 39808.23 | 02-FEB-06:00 | 45622.98 | 2985.21 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7091.89 |
March | 28626.64 | 24-MAR-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2567.52 |
April | 33184.86 | 16-APR-21:10 | 40553.76 | 7463.04 | 6334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.14 |
May | 34084.62 | 31-MAY-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.35 |
June | 36047.90 | 26-JUN-21:12 | 456229.80 | 89556.42 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 | 0.00 |
July | 35179.11 | 03-JUL-21:12 | 410606.82 | 80600.78 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 3.40 | 0.00 |
August | 35480.49 | 22-AUG-21:12 | 410606.82 | 80600.78 | 66509.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.85 |
September | 38249.74 | 07-SEP-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.77 |
October | 34616.15 | 20-OCT-21:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1152.45 |
November | 48297.93 | 25-NOV-21:11 | 248391.78 | 73137.74 | 59119.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5973.52 |
December | 24235.82 | 05-DEC-22:10 | 45622.98 | 8955.64 | 7389.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3813.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 24235.82 | 40553.76 | 2985.21 | 3167.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 54172.80 | 456229.80 | 89556.42 | 73899.43 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 | 7091.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3665.21 | 12-JAN-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.87 |
February | 3859.03 | 24-FEB-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.80 |
March | 3854.94 | 25-MAR-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.79 |
April | 3881.72 | 29-APR-18:01 | 936.00 | 2069.91 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 |
May | 3981.45 | 20-MAY-18:01 | 1170.00 | 2587.38 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 |
June | 3484.08 | 15-JUN-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 |
July | 3490.12 | 26-JUL-15:02 | 583.20 | 124.19 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 0.00 |
August | 3510.24 | 30-AUG-18:01 | 970.20 | 1607.41 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.78 |
September | 3855.94 | 20-SEP-18:01 | 970.20 | 1607.41 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 |
October | 3891.29 | 19-OCT-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 |
November | 3901.48 | 04-NOV-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.41 |
December | 3585.88 | 01-DEC-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3484.08 | 378.00 | 113.20 | 300.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3981.45 | 1170.00 | 2587.38 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 166.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 563.74 | 12-JAN-16:03 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.53 |
February | 3658.08 | 24-FEB-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.33 |
March | 3771.72 | 25-MAR-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 |
April | 3872.82 | 29-APR-18:01 | 936.00 | 2069.66 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.31 |
May | 4569.30 | 21-MAY-19:01 | 1170.00 | 2587.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.79 |
June | 3759.23 | 23-JUN-21:11 | 1800.00 | 1746.28 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 |
July | 3637.66 | 18-JUL-21:11 | 1800.00 | 1746.28 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
August | 3545.46 | 08-AUG-21:11 | 1800.00 | 1746.28 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.15 |
September | 3750.02 | 24-SEP-18:01 | 819.00 | 1810.96 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.99 |
October | 3785.21 | 19-OCT-15:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.15 |
November | 3773.73 | 04-NOV-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.09 |
December | 657.92 | 01-DEC-16:03 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 |
Annual Sum or Average | |||||||||||
Minimum of Months | 563.74 | 378.00 | 113.18 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | |
Maximum of Months | 4569.30 | 1800.00 | 2587.08 | 1632.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 216.88 | 30-JAN-15:05 | 0.00 | 20.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.33 |
February | 255.65 | 02-FEB-15:05 | 0.00 | 20.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.99 |
March | 397.15 | 24-MAR-13:00 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 |
April | 511.20 | 15-APR-12:50 | 0.00 | 10.16 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 0.00 |
May | 326.31 | 31-MAY-19:10 | 0.00 | 325.21 | 319.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 |
June | 364.47 | 26-JUN-19:10 | 0.00 | 162.61 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 | 0.00 |
July | 343.71 | 02-JUL-19:10 | 0.00 | 162.61 | 159.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 | 0.00 |
August | 451.42 | 29-AUG-13:20 | 0.00 | 20.33 | 61.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
September | 602.72 | 07-SEP-12:50 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 0.00 |
October | 674.86 | 20-OCT-12:30 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 |
November | 653.59 | 04-NOV-12:30 | 0.00 | 10.16 | 33.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 |
December | 137.32 | 07-DEC-15:20 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 137.32 | 0.00 | 10.16 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 674.86 | 0.00 | 325.21 | 319.91 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 | 105.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 627.11 | 01-JAN-09:02 | 324.00 | 227.71 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 |
February | 1043.94 | 26-FEB-09:02 | 324.00 | 227.71 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 |
March | 1102.46 | 25-MAR-18:02 | 702.00 | 975.91 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
April | 1162.57 | 30-APR-18:01 | 819.00 | 1138.56 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 |
May | 1133.75 | 06-MAY-18:51 | 1170.00 | 1626.51 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 |
June | 1128.36 | 16-JUN-21:11 | 1800.00 | 1097.90 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
July | 1141.76 | 18-JUL-21:11 | 1800.00 | 1097.90 | 877.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 |
August | 1099.35 | 22-AUG-18:01 | 970.20 | 1010.47 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 0.00 |
September | 1160.49 | 19-SEP-18:01 | 970.20 | 1010.47 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 |
October | 1091.70 | 08-OCT-18:01 | 819.00 | 1138.56 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.71 |
November | 1076.53 | 04-NOV-18:01 | 819.00 | 1138.56 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.48 |
December | 719.40 | 03-DEC-09:02 | 324.00 | 227.71 | 959.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 627.11 | 324.00 | 227.71 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1162.57 | 1800.00 | 1626.51 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 48.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 658.66 | 12-JAN-09:03 | 216.00 | 679.19 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.25 |
February | 3344.19 | 24-FEB-09:02 | 216.00 | 679.19 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.03 |
March | 3469.35 | 24-MAR-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.77 |
April | 3515.04 | 26-APR-08:61 | 252.00 | 792.39 | 792.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.13 |
May | 3449.64 | 20-MAY-18:01 | 1170.00 | 2587.38 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.18 |
June | 3247.89 | 11-JUN-08:61 | 378.00 | 422.61 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 0.00 |
July | 3220.73 | 29-JUL-08:61 | 378.00 | 422.61 | 1143.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
August | 3180.60 | 02-AUG-08:62 | 216.00 | 679.19 | 679.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
September | 3446.30 | 30-SEP-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.13 |
October | 3474.69 | 24-OCT-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.37 |
November | 3493.37 | 04-NOV-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.90 |
December | 2485.94 | 03-DEC-09:02 | 324.00 | 362.23 | 979.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 658.66 | 216.00 | 113.20 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3515.04 | 1170.00 | 2587.38 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 10.40 | 180.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 459.30 | 11-JAN-09:05 | 216.00 | 679.11 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.34 |
February | 3206.51 | 24-FEB-09:02 | 216.00 | 679.11 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.56 |
March | 2856.63 | 19-MAR-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 |
April | 3492.22 | 26-APR-08:61 | 252.00 | 792.29 | 792.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.04 |
May | 3660.26 | 31-MAY-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 |
June | 3861.36 | 20-JUN-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.11 |
July | 3771.09 | 13-JUL-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.84 |
August | 3758.36 | 09-AUG-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 |
September | 3658.76 | 06-SEP-08:11 | 360.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.41 |
October | 2915.61 | 21-OCT-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 |
November | 2180.79 | 04-NOV-08:62 | 270.00 | 301.83 | 816.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.39 |
December | 622.86 | 05-DEC-09:03 | 216.00 | 679.11 | 679.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.85 |
Annual Sum or Average | |||||||||||
Minimum of Months | 459.30 | 216.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | |
Maximum of Months | 3861.36 | 378.00 | 1131.85 | 1132.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1106.33 | 31-JAN-04:00 | 0.00 | 150.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.74 |
February | 1440.28 | 02-FEB-06:02 | 0.00 | 3000.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.11 |
March | 1313.65 | 19-MAR-14:30 | 0.00 | 300.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.52 |
April | 1638.45 | 18-APR-15:02 | 0.00 | 2250.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.41 | 0.00 |
May | 1631.35 | 31-MAY-19:20 | 0.00 | 2700.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 | 0.00 |
June | 1679.09 | 30-JUN-19:20 | 0.00 | 4050.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.52 | 0.00 |
July | 1667.70 | 01-JUL-19:00 | 0.00 | 1050.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 | 0.00 |
August | 1658.47 | 04-AUG-15:02 | 0.00 | 2250.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.29 | 0.00 |
September | 1682.41 | 08-SEP-14:00 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.81 | 0.00 |
October | 1601.93 | 20-OCT-14:40 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 0.00 |
November | 1341.43 | 03-NOV-14:00 | 0.00 | 375.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.05 |
December | 1019.32 | 03-DEC-13:00 | 0.00 | 450.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.16 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1019.32 | 0.00 | 150.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1682.41 | 0.00 | 4050.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.29 | 523.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3768.42 | 12-JAN-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.34 |
February | 4004.92 | 24-FEB-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.14 |
March | 3988.10 | 24-MAR-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.99 |
April | 4029.22 | 29-APR-18:01 | 936.00 | 2069.91 | 969.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 |
May | 4145.51 | 20-MAY-18:01 | 1170.00 | 2587.38 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.46 |
June | 3566.01 | 17-JUN-18:02 | 702.00 | 1552.43 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 | 0.00 |
July | 3653.06 | 05-JUL-18:02 | 831.60 | 1377.78 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | 0.00 |
August | 3608.23 | 21-AUG-18:02 | 831.60 | 1377.78 | 726.98 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 | 0.00 |
September | 4012.54 | 20-SEP-18:01 | 970.20 | 1607.41 | 848.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 |
October | 4013.53 | 24-OCT-15:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.92 |
November | 4053.08 | 04-NOV-15:01 | 378.00 | 113.20 | 387.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.80 |
December | 3685.89 | 01-DEC-16:01 | 680.40 | 144.89 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3566.01 | 378.00 | 113.20 | 350.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4145.51 | 1170.00 | 2587.38 | 1211.63 | 0.00 | 0.00 | 0.00 | 0.00 | 25.63 | 166.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 741.40 | 13-JAN-16:04 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.21 |
February | 3700.74 | 24-FEB-16:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.35 |
March | 3885.84 | 24-MAR-18:01 | 970.20 | 1607.22 | 848.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.10 |
April | 4039.92 | 29-APR-18:01 | 936.00 | 2069.66 | 969.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.23 |
May | 5043.27 | 20-MAY-18:01 | 1170.00 | 2587.08 | 1211.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 |
June | 4199.76 | 21-JUN-20:21 | 1602.00 | 2296.03 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.31 |
July | 4189.46 | 23-JUL-21:11 | 1386.00 | 2199.02 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 |
August | 3977.59 | 07-AUG-21:11 | 1800.00 | 1746.28 | 895.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.28 |
September | 4169.75 | 19-SEP-17:01 | 680.40 | 1222.39 | 884.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 |
October | 3761.90 | 24-OCT-15:01 | 680.40 | 144.88 | 350.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 |
November | 3879.05 | 04-NOV-15:01 | 378.00 | 113.18 | 387.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 |
December | 710.37 | 02-DEC-16:03 | 324.00 | 97.02 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 710.37 | 324.00 | 97.02 | 331.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.71 | |
Maximum of Months | 5043.27 | 1800.00 | 2587.08 | 1817.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1941.06 | 30-JAN-16:02 | 583.20 | 78.07 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.57 |
February | 1793.43 | 17-FEB-16:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.72 |
March | 1820.40 | 22-MAR-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.96 |
April | 1808.21 | 06-APR-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
May | 1774.97 | 20-MAY-18:01 | 1170.00 | 1626.51 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.56 |
June | 1639.76 | 07-JUN-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.68 |
July | 1651.45 | 12-JUL-18:01 | 970.20 | 1010.47 | 830.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 0.00 |
August | 1642.61 | 01-AUG-18:02 | 831.60 | 866.12 | 712.25 | 0.00 | 0.00 | 0.00 | 0.00 | 13.08 | 0.00 |
September | 1818.09 | 30-SEP-15:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.35 |
October | 1839.44 | 27-OCT-15:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.98 |
November | 1811.11 | 12-NOV-16:01 | 378.00 | 71.16 | 379.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.93 |
December | 1799.92 | 01-DEC-16:01 | 680.40 | 91.08 | 343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1639.76 | 378.00 | 71.16 | 294.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1941.06 | 1170.00 | 1626.51 | 1187.08 | 0.00 | 0.00 | 0.00 | 0.00 | 13.08 | 186.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 31310.34 | 19-JAN-01:51 | 269887.68 | 3801.98 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.54 |
February | 20573.77 | 02-FEB-06:00 | 26988.77 | 506.93 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.87 |
March | 17949.87 | 28-MAR-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.06 |
April | 19742.95 | 18-APR-21:12 | 215910.14 | 12166.33 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.61 |
May | 20954.94 | 31-MAY-21:12 | 269887.68 | 15207.91 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 |
June | 21813.50 | 26-JUN-21:12 | 269887.68 | 15207.91 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
July | 21547.91 | 03-JUL-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
August | 21218.73 | 03-AUG-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
September | 20804.52 | 07-SEP-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.63 |
October | 18388.44 | 20-OCT-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.01 |
November | 22576.48 | 25-NOV-21:22 | 104956.32 | 8871.28 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.97 |
December | 15893.78 | 04-DEC-23:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 15893.78 | 26988.77 | 506.93 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31310.34 | 269887.68 | 15207.91 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 1022.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 33210.65 | 19-JAN-01:51 | 269887.68 | 3801.98 | 22493.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.11 |
February | 21604.81 | 02-FEB-06:00 | 26988.77 | 506.93 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1019.39 |
March | 20010.73 | 28-MAR-21:20 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.29 |
April | 21556.79 | 18-APR-21:12 | 215910.14 | 12166.33 | 53983.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.61 |
May | 22658.38 | 31-MAY-21:12 | 269887.68 | 15207.91 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.98 |
June | 23392.36 | 26-JUN-21:12 | 269887.68 | 15207.91 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 0.00 |
July | 23065.51 | 03-JUL-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 |
August | 22847.31 | 03-AUG-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 0.00 |
September | 22412.01 | 07-SEP-21:12 | 242898.91 | 13687.12 | 60731.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.63 |
October | 20343.37 | 02-OCT-22:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.19 |
November | 28492.20 | 25-NOV-21:22 | 104956.32 | 8871.28 | 33739.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 854.15 |
December | 17932.72 | 04-DEC-23:00 | 26988.77 | 1520.79 | 6747.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 17932.72 | 26988.77 | 506.93 | 2249.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33210.65 | 269887.68 | 15207.91 | 67479.03 | 0.00 | 0.00 | 0.00 | 0.00 | 17.49 | 1019.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 27089.01 | 29-JAN-19:32 | 8005.68 | 4125.37 | 74564.28 | 74976.11 | 0.00 | 0.00 | 0.00 | 0.00 | 781.04 |
February | 26087.90 | 24-FEB-11:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 288.81 |
March | 27835.33 | 19-MAR-10:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 153.08 |
April | 29990.74 | 18-APR-10:40 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 31.31 | 0.00 |
May | 30246.79 | 29-MAY-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 7.69 | 0.00 |
June | 30605.84 | 11-JUN-10:40 | 1601.14 | 707.21 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 77.30 | 0.00 |
July | 30625.52 | 29-JUL-10:50 | 800.57 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 27.30 | 0.00 |
August | 30196.05 | 11-AUG-10:40 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 42.14 | 0.00 |
September | 30357.47 | 08-SEP-10:40 | 1067.42 | 589.34 | 29825.71 | 37488.05 | 0.00 | 0.00 | 0.00 | 59.62 | 0.00 |
October | 28557.53 | 20-OCT-10:50 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 94.67 |
November | 29045.67 | 25-NOV-21:22 | 9339.96 | 4125.37 | 74564.28 | 56232.08 | 0.00 | 0.00 | 0.00 | 0.00 | 766.34 |
December | 25847.01 | 03-DEC-11:50 | 800.57 | 353.60 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 306.68 |
Annual Sum or Average | |||||||||||
Minimum of Months | 25847.01 | 533.71 | 294.67 | 14912.86 | 18744.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30625.52 | 9339.96 | 4125.37 | 74564.28 | 74976.11 | 0.00 | 0.00 | 0.00 | 77.30 | 781.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2124.69 | 12-JAN-12:50 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.41 |
February | 2371.79 | 24-FEB-14:20 | 0.00 | 793.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.69 |
March | 3149.45 | 19-MAR-14:00 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.36 |
April | 3766.38 | 18-APR-14:00 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 | 0.00 |
May | 3886.90 | 31-MAY-15:15 | 0.00 | 793.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.09 | 0.00 |
June | 4162.65 | 30-JUN-15:02 | 0.00 | 2381.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.68 | 0.00 |
July | 4111.16 | 03-JUL-15:50 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.80 | 0.00 |
August | 4129.68 | 04-AUG-15:02 | 0.00 | 2381.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.06 | 0.00 |
September | 4142.35 | 07-SEP-13:50 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.51 | 0.00 |
October | 3590.78 | 20-OCT-13:50 | 0.00 | 793.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | 0.00 |
November | 3043.69 | 03-NOV-14:00 | 0.00 | 396.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.65 |
December | 2264.58 | 03-DEC-13:30 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2124.69 | 0.00 | 317.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4162.65 | 0.00 | 2381.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.06 | 284.41 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.399245E+12 | 263667.10 | 12-JAN-20:40 | 0.954787E+12 | 942957.51 | 30-JAN-19:30 |
February | 0.358680E+12 | 264819.10 | 24-FEB-20:49 | 0.749726E+12 | 976339.25 | 02-FEB-20:00 |
March | 0.396115E+12 | 273690.61 | 24-MAR-19:19 | 0.527787E+12 | 492453.15 | 05-MAR-19:10 |
April | 0.404854E+12 | 357799.09 | 16-APR-19:10 | 0.420622E+12 | 390573.86 | 19-APR-17:19 |
May | 0.449937E+12 | 363134.14 | 31-MAY-19:40 | 0.384150E+12 | 385499.10 | 19-MAY-19:30 |
June | 0.526639E+12 | 408738.39 | 26-JUN-19:00 | 0.353403E+12 | 389712.41 | 01-JUN-18:49 |
July | 0.592571E+12 | 432378.24 | 26-JUL-19:10 | 0.342874E+12 | 279801.91 | 10-JUL-17:10 |
August | 0.570805E+12 | 413788.42 | 03-AUG-19:19 | 0.344411E+12 | 328151.61 | 06-AUG-21:00 |
September | 0.463897E+12 | 368229.48 | 07-SEP-18:40 | 0.355639E+12 | 394857.01 | 25-SEP-19:19 |
October | 0.408820E+12 | 290856.29 | 20-OCT-19:40 | 0.396146E+12 | 392984.78 | 04-OCT-19:19 |
November | 0.385702E+12 | 279162.47 | 03-NOV-19:49 | 0.554176E+12 | 871694.55 | 25-NOV-21:40 |
December | 0.398050E+12 | 263040.56 | 11-DEC-20:49 | 0.711180E+12 | 592953.72 | 11-DEC-17:19 |
Annual Sum or Average | 0.535532E+13 | 0.609490E+13 | ||||
Minimum of Months | 0.358680E+12 | 263040.56 | 0.342874E+12 | 279801.91 | ||
Maximum of Months | 0.592571E+12 | 432378.24 | 0.954787E+12 | 976339.25 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.708650E+11 | 0.192913E+11 | 0.140828E+12 | 0.825757E+11 | 0.451436E+11 | 0.181179E+10 | 0.00 | 0.281392E+09 | 0.00 | 0.00 | 0.257380E+11 | 0.770805E+10 | 0.00 |
February | 0.637995E+11 | 0.160738E+11 | 0.127191E+12 | 0.745845E+11 | 0.398302E+11 | 0.188427E+10 | 0.00 | 0.622230E+09 | 0.00 | 0.00 | 0.232473E+11 | 0.696645E+10 | 0.00 |
March | 0.703441E+11 | 0.159272E+11 | 0.140892E+12 | 0.825780E+11 | 0.426817E+11 | 0.202556E+10 | 0.00 | 0.509022E+10 | 0.00 | 0.00 | 0.236850E+11 | 0.770495E+10 | 0.00 |
April | 0.676487E+11 | 0.134984E+11 | 0.136245E+12 | 0.799112E+11 | 0.415832E+11 | 0.312225E+10 | 0.00 | 0.310833E+11 | 0.00 | 0.00 | 0.192490E+11 | 0.746519E+10 | 0.00 |
May | 0.695313E+11 | 0.122769E+11 | 0.140860E+12 | 0.825762E+11 | 0.430916E+11 | 0.499198E+10 | 0.00 | 0.744786E+11 | 0.00 | 0.00 | 0.914318E+10 | 0.770486E+10 | 0.00 |
June | 0.671636E+11 | 0.110416E+11 | 0.136336E+12 | 0.799133E+11 | 0.420967E+11 | 0.526843E+10 | 0.00 | 0.162072E+12 | 0.00 | 0.00 | 0.101571E+11 | 0.745768E+10 | 0.00 |
July | 0.693261E+11 | 0.117674E+11 | 0.140770E+12 | 0.825736E+11 | 0.429155E+11 | 0.573596E+10 | 0.00 | 0.216832E+12 | 0.00 | 0.00 | 0.965665E+10 | 0.771342E+10 | 0.00 |
August | 0.697341E+11 | 0.132122E+11 | 0.140892E+12 | 0.825776E+11 | 0.429558E+11 | 0.559882E+10 | 0.00 | 0.193587E+12 | 0.00 | 0.00 | 0.923294E+10 | 0.770510E+10 | 0.00 |
September | 0.678249E+11 | 0.145592E+11 | 0.136245E+12 | 0.799113E+11 | 0.421735E+11 | 0.478380E+10 | 0.00 | 0.945378E+11 | 0.00 | 0.00 | 0.112929E+11 | 0.746560E+10 | 0.00 |
October | 0.705348E+11 | 0.170230E+11 | 0.140828E+12 | 0.825755E+11 | 0.439975E+11 | 0.367885E+10 | 0.00 | 0.177844E+11 | 0.00 | 0.00 | 0.194675E+11 | 0.770458E+10 | 0.00 |
November | 0.685547E+11 | 0.181816E+11 | 0.136330E+12 | 0.799127E+11 | 0.421434E+11 | 0.204090E+10 | 0.00 | 0.480530E+10 | 0.00 | 0.00 | 0.212867E+11 | 0.744981E+10 | 0.00 |
December | 0.709454E+11 | 0.197590E+11 | 0.140770E+12 | 0.825746E+11 | 0.439121E+11 | 0.982845E+09 | 0.00 | 0.514379E+09 | 0.00 | 0.00 | 0.257380E+11 | 0.771349E+10 | 0.00 |
Annual Sum or Average | 0.826272E+12 | 0.182612E+12 | 0.165819E+13 | 0.972264E+12 | 0.512525E+12 | 0.419255E+11 | 0.00 | 0.801688E+12 | 0.207894E+12 | 0.907592E+11 | |||
Minimum of Months | 0.637995E+11 | 0.110416E+11 | 0.127191E+12 | 0.745845E+11 | 0.398302E+11 | 0.982845E+09 | 0.00 | 0.281392E+09 | 0.00 | 0.00 | 0.914318E+10 | 0.696645E+10 | 0.00 |
Maximum of Months | 0.709454E+11 | 0.197590E+11 | 0.140892E+12 | 0.825780E+11 | 0.451436E+11 | 0.573596E+10 | 0.00 | 0.216832E+12 | 0.00 | 0.00 | 0.257380E+11 | 0.771349E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportINTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.151918E+12 | 0.00 | 0.598065E+12 | 0.00 | 0.204804E+12 | 0.00 | 0.00 |
February | 0.137204E+12 | 0.00 | 0.424939E+12 | 0.00 | 0.187583E+12 | 0.00 | 0.00 |
March | 0.152039E+12 | 0.00 | 0.168865E+12 | 0.00 | 0.206883E+12 | 0.00 | 0.00 |
April | 0.146956E+12 | 0.00 | 0.783053E+11 | 0.00 | 0.195361E+12 | 0.00 | 0.00 |
May | 0.151978E+12 | 0.00 | 0.370813E+11 | 0.00 | 0.195090E+12 | 0.00 | 0.00 |
June | 0.147114E+12 | 0.00 | 0.243543E+11 | 0.00 | 0.181935E+12 | 0.00 | 0.00 |
July | 0.151820E+12 | 0.00 | 0.871449E+10 | 0.00 | 0.182339E+12 | 0.00 | 0.00 |
August | 0.152039E+12 | 0.00 | 0.125308E+11 | 0.00 | 0.179841E+12 | 0.00 | 0.00 |
September | 0.146956E+12 | 0.00 | 0.335371E+11 | 0.00 | 0.175146E+12 | 0.00 | 0.00 |
October | 0.151918E+12 | 0.00 | 0.586447E+11 | 0.00 | 0.185583E+12 | 0.00 | 0.00 |
November | 0.147091E+12 | 0.00 | 0.221303E+12 | 0.00 | 0.185782E+12 | 0.00 | 0.00 |
December | 0.151820E+12 | 0.00 | 0.359909E+12 | 0.00 | 0.199451E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.178885E+13 | 0.202625E+13 | 0.227980E+13 | ||||
Minimum of Months | 0.137204E+12 | 0.00 | 0.871449E+10 | 0.00 | 0.175146E+12 | 0.00 | 0.00 |
Maximum of Months | 0.152039E+12 | 0.00 | 0.598065E+12 | 0.00 | 0.206883E+12 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 75078.55 | 02-JAN-20:10 | 11632.50 | 01-JAN-00:10 | 89171.45 | 02-JAN-07:10 | 62594.23 | 02-JAN-07:19 | 25315.59 | 05-JAN-19:10 | 4681.15 | 30-JAN-16:30 | 0.00 | 01-JAN-00:10 |
February | 75078.55 | 01-FEB-20:10 | 11632.50 | 01-FEB-00:10 | 89171.45 | 01-FEB-07:10 | 62594.23 | 01-FEB-07:19 | 23587.88 | 05-FEB-19:10 | 3552.14 | 01-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 75078.55 | 01-MAR-20:10 | 11632.50 | 01-MAR-00:10 | 89171.45 | 01-MAR-07:10 | 62594.23 | 13-MAR-06:19 | 25133.57 | 28-MAR-20:00 | 1961.46 | 05-MAR-17:30 | 0.00 | 01-MAR-00:10 |
April | 75078.55 | 03-APR-19:10 | 11632.50 | 01-APR-00:10 | 89171.45 | 03-APR-06:10 | 62594.15 | 14-APR-06:19 | 27453.83 | 19-APR-20:10 | 2496.45 | 18-APR-15:30 | 0.00 | 01-APR-00:10 |
May | 75078.55 | 01-MAY-19:10 | 11632.50 | 01-MAY-00:10 | 89171.45 | 01-MAY-06:10 | 62592.75 | 10-MAY-06:19 | 26664.65 | 22-MAY-20:49 | 2495.58 | 31-MAY-18:30 | 0.00 | 01-MAY-00:10 |
June | 75078.55 | 01-JUN-19:10 | 11632.50 | 01-JUN-00:10 | 89171.45 | 01-JUN-06:10 | 62593.19 | 13-JUN-06:19 | 27108.35 | 21-JUN-20:49 | 2806.00 | 26-JUN-18:10 | 0.00 | 01-JUN-00:10 |
July | 75078.55 | 03-JUL-19:30 | 11632.50 | 01-JUL-00:10 | 89171.45 | 03-JUL-06:10 | 62592.75 | 20-JUL-06:19 | 25196.91 | 03-JUL-18:19 | 3314.50 | 03-JUL-21:49 | 0.00 | 01-JUL-00:10 |
August | 75078.55 | 01-AUG-19:30 | 11632.50 | 01-AUG-00:10 | 89171.45 | 01-AUG-06:10 | 62593.05 | 23-AUG-06:19 | 25232.28 | 06-AUG-19:49 | 3112.24 | 21-AUG-21:30 | 0.00 | 01-AUG-00:10 |
September | 75078.55 | 01-SEP-19:10 | 11632.50 | 01-SEP-00:10 | 89171.45 | 01-SEP-06:10 | 62594.23 | 21-SEP-06:19 | 27882.89 | 25-SEP-20:00 | 2500.16 | 06-SEP-15:20 | 0.00 | 01-SEP-00:10 |
October | 75078.55 | 02-OCT-19:10 | 11632.50 | 01-OCT-00:10 | 89171.45 | 02-OCT-06:10 | 62594.23 | 02-OCT-06:19 | 28770.70 | 24-OCT-20:00 | 2502.66 | 20-OCT-15:09 | 0.00 | 01-OCT-00:10 |
November | 75078.55 | 01-NOV-19:10 | 11632.50 | 01-NOV-00:10 | 89171.45 | 01-NOV-06:10 | 62594.23 | 01-NOV-06:19 | 28423.24 | 03-NOV-20:10 | 3051.63 | 26-NOV-06:00 | 0.00 | 01-NOV-00:10 |
December | 75078.55 | 01-DEC-20:10 | 11632.50 | 01-DEC-00:10 | 89171.45 | 01-DEC-07:10 | 62594.23 | 01-DEC-07:19 | 25895.93 | 11-DEC-19:10 | 2073.68 | 10-DEC-10:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 75078.55 | 11632.50 | 89171.45 | 62592.75 | 23587.88 | 1961.46 | 0.00 | |||||||
Maximum of Months | 75078.55 | 11632.50 | 89171.45 | 62594.23 | 28770.70 | 4681.15 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum}[W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4117.76 | 12-JAN-16:10 | 0.00 | 0.00 | 9924.11 | 02-JAN-06:10 | 4746.47 | 31-JAN-07:30 | 0.00 |
February | 7876.21 | 24-FEB-16:10 | 0.00 | 0.00 | 9924.11 | 01-FEB-00:10 | 4749.05 | 02-FEB-07:30 | 0.00 |
March | 54491.70 | 25-MAR-15:09 | 0.00 | 0.00 | 9924.11 | 01-MAR-06:10 | 4738.40 | 01-MAR-19:10 | 0.00 |
April | 128792.43 | 16-APR-15:20 | 0.00 | 0.00 | 9924.11 | 03-APR-05:10 | 4738.24 | 21-APR-18:10 | 0.00 |
May | 125989.64 | 31-MAY-15:09 | 0.00 | 0.00 | 9924.11 | 01-MAY-08:09 | 4738.60 | 03-MAY-18:10 | 0.00 |
June | 182278.00 | 11-JUN-15:09 | 0.00 | 0.00 | 9924.11 | 02-JUN-08:09 | 4738.32 | 30-JUN-18:00 | 0.00 |
July | 190178.17 | 26-JUL-18:10 | 0.00 | 0.00 | 9924.11 | 01-JUL-08:30 | 4738.74 | 10-JUL-18:10 | 0.00 |
August | 203597.39 | 04-AUG-15:50 | 0.00 | 0.00 | 9924.11 | 01-AUG-08:20 | 4738.65 | 18-AUG-18:10 | 0.00 |
September | 147505.95 | 06-SEP-15:09 | 0.00 | 0.00 | 9924.11 | 01-SEP-15:09 | 4738.30 | 08-SEP-06:19 | 0.00 |
October | 92751.70 | 20-OCT-15:09 | 0.00 | 0.00 | 9924.11 | 03-OCT-18:10 | 4738.33 | 20-OCT-18:10 | 0.00 |
November | 41129.35 | 03-NOV-15:09 | 0.00 | 0.00 | 9924.11 | 01-NOV-18:10 | 4738.16 | 17-NOV-19:10 | 0.00 |
December | 4222.86 | 07-DEC-14:30 | 0.00 | 0.00 | 9924.11 | 01-DEC-16:10 | 4738.37 | 20-DEC-19:10 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 4117.76 | 0.00 | 0.00 | 9924.11 | 4738.16 | 0.00 | |||
Maximum of Months | 203597.39 | 0.00 | 0.00 | 9924.11 | 4749.05 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 263667.10 | 12-JAN-20:40 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 21328.47 | 1844.68 | 0.00 | 723.07 | 0.00 |
February | 264819.10 | 24-FEB-20:49 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 21770.02 | 1842.58 | 0.00 | 2062.81 | 0.00 |
March | 273690.61 | 24-MAR-19:19 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 23167.99 | 1851.87 | 0.00 | 9569.95 | 0.00 |
April | 357799.09 | 16-APR-19:10 | 70163.21 | 84978.71 | 11632.50 | 50255.20 | 18809.03 | 2247.71 | 0.00 | 104322.15 | 0.00 |
May | 363134.14 | 31-MAY-19:40 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 20199.72 | 2223.38 | 0.00 | 100991.65 | 0.00 |
June | 408738.39 | 26-JUN-19:00 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 24913.08 | 2764.49 | 0.00 | 141655.63 | 0.00 |
July | 432378.24 | 26-JUL-19:10 | 73514.88 | 86439.81 | 0.00 | 50287.92 | 22941.43 | 3262.21 | 0.00 | 179836.59 | 0.00 |
August | 413788.42 | 03-AUG-19:19 | 74605.52 | 86439.81 | 0.00 | 50295.46 | 24213.18 | 3019.10 | 0.00 | 159001.52 | 0.00 |
September | 368229.48 | 07-SEP-18:40 | 66693.65 | 77573.37 | 11632.50 | 50096.46 | 22657.22 | 2450.20 | 0.00 | 120138.96 | 0.00 |
October | 290856.29 | 20-OCT-19:40 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 23899.98 | 1916.41 | 0.00 | 36177.99 | 0.00 |
November | 279162.47 | 03-NOV-19:49 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 26539.79 | 1857.38 | 0.00 | 11500.39 | 0.00 |
December | 263040.56 | 11-DEC-20:49 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 22817.44 | 484.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 263040.56 | 66693.65 | 77573.37 | 0.00 | 50096.46 | 18809.03 | 484.22 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 432378.24 | 75078.55 | 86439.81 | 11632.50 | 50297.15 | 26539.79 | 3262.21 | 0.00 | 179836.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportINTERIOREQUIPMENT:GAS {Maximum}[W] | INTERIOREQUIPMENT:GAS {TIMESTAMP} | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 104248.32 | 02-JAN-18:10 | 0.00 | 718285.11 | 31-JAN-03:00 | 0.00 | 180062.92 | 30-JAN-21:40 | 0.00 |
February | 104248.32 | 01-FEB-18:10 | 0.00 | 754576.60 | 02-FEB-05:00 | 0.00 | 180196.06 | 21-FEB-21:30 | 0.00 |
March | 104248.32 | 01-MAR-18:10 | 0.00 | 233780.46 | 05-MAR-19:10 | 0.00 | 180157.48 | 01-MAR-21:19 | 0.00 |
April | 104248.32 | 01-APR-17:10 | 0.00 | 177466.75 | 03-APR-08:09 | 0.00 | 179526.11 | 03-APR-20:00 | 0.00 |
May | 104248.32 | 01-MAY-17:10 | 0.00 | 135872.11 | 17-MAY-20:19 | 0.00 | 178523.10 | 01-MAY-20:00 | 0.00 |
June | 104248.32 | 01-JUN-17:10 | 0.00 | 131252.75 | 02-JUN-21:40 | 0.00 | 177257.60 | 01-JUN-20:00 | 0.00 |
July | 104248.32 | 01-JUL-17:10 | 0.00 | 84810.81 | 23-JUL-05:40 | 0.00 | 176196.97 | 03-JUL-20:19 | 0.00 |
August | 104248.32 | 01-AUG-17:10 | 0.00 | 113900.64 | 16-AUG-06:19 | 0.00 | 175505.98 | 01-AUG-20:49 | 0.00 |
September | 104248.32 | 01-SEP-17:10 | 0.00 | 136179.15 | 25-SEP-20:10 | 0.00 | 175847.79 | 29-SEP-20:49 | 0.00 |
October | 104248.32 | 02-OCT-17:10 | 0.00 | 134033.54 | 04-OCT-19:30 | 0.00 | 176844.01 | 31-OCT-20:40 | 0.00 |
November | 104248.32 | 01-NOV-17:10 | 0.00 | 687887.38 | 26-NOV-06:00 | 0.00 | 178066.92 | 30-NOV-21:30 | 0.00 |
December | 104248.32 | 01-DEC-18:10 | 0.00 | 350609.04 | 11-DEC-16:19 | 0.00 | 179183.59 | 29-DEC-21:00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 104248.32 | 0.00 | 84810.81 | 0.00 | 175505.98 | 0.00 | |||
Maximum of Months | 104248.32 | 0.00 | 754576.60 | 0.00 | 180196.06 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 59.83 | 19.07 | 59.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 138.83 | 15.94 | 138.83 | 15.94 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.67 | 16.89 | 198.67 | 16.89 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.83 | 19.07 | 138.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 79.67 | 16.53 | 79.67 | 16.53 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99.33 | 14.73 | 99.33 | 14.73 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12.00 | 17.07 | 12.00 | 17.07 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.33 | 20.35 | 12.33 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 203.33 | 15.91 | 203.33 | 15.91 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 99.33 | 20.35 | 99.33 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 85.17 | 17.63 | 85.17 | 17.63 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 101.83 | 14.59 | 101.83 | 14.59 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.17 | 18.61 | 11.17 | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 198.17 | 16.12 | 198.17 | 16.12 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.83 | 18.61 | 101.83 | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 101.17 | 18.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 138.50 | 15.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.83 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 251.50 | 16.79 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.50 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 133.67 | 18.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 141.83 | 15.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14.67 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 290.17 | 17.04 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 141.83 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.17 | 10.28 | 68.17 | 10.28 | 2.50 | 24.62 | 2.50 | 24.62 |
February | 72.67 | 6.78 | 72.67 | 6.78 | 7.83 | 24.62 | 7.83 | 24.62 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 24.65 | 16.50 | 24.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 24.68 | 16.17 | 24.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 24.65 | 7.17 | 24.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.65 | 1.33 | 24.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 24.67 | 11.50 | 24.67 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 24.67 | 25.83 | 24.67 |
November | 8.17 | 11.64 | 8.17 | 11.64 | 11.17 | 24.65 | 11.17 | 24.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 24.60 | 5.33 | 24.60 |
Annual Sum or Average | 149.00 | 8.65 | 149.00 | 8.65 | 105.33 | 24.65 | 105.33 | 24.65 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 72.67 | 11.64 | 72.67 | 11.64 | 25.83 | 24.68 | 25.83 | 24.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 76.67 | 17.56 | 76.67 | 17.56 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.33 | 14.91 | 83.33 | 14.91 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.67 | 18.17 | 11.67 | 18.17 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 171.67 | 16.32 | 171.67 | 16.32 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.33 | 18.17 | 83.33 | 18.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 78.50 | 17.70 | 78.50 | 17.70 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90.50 | 14.41 | 90.50 | 14.41 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.33 | 18.67 | 10.33 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 179.33 | 16.09 | 179.33 | 16.09 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 90.50 | 18.67 | 90.50 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.35 | 2.00 | 20.35 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29.00 | 19.94 | 29.00 | 19.94 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.52 | 0.17 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 20.42 | 1.17 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 32.33 | 19.99 | 32.33 | 19.99 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.00 | 20.52 | 29.00 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.83 | 20.36 | 10.83 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 46.00 | 19.64 | 46.00 | 19.64 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.99 | 0.67 | 21.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.76 | 0.67 | 21.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.78 | 2.33 | 21.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.73 | 0.17 | 21.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.50 | 0.33 | 20.50 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.45 | 2.33 | 20.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 59.50 | 19.81 | 59.50 | 19.81 | 3.83 | 21.81 | 3.83 | 21.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 46.00 | 20.50 | 46.00 | 20.50 | 2.33 | 21.99 | 2.33 | 21.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.67 | 20.10 | 27.67 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 62.33 | 19.34 | 62.33 | 19.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.75 | 0.33 | 21.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.80 | 1.17 | 21.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 21.93 | 5.00 | 21.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 21.94 | 10.17 | 21.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 21.90 | 5.33 | 21.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.82 | 1.00 | 21.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.32 | 1.33 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.67 | 20.32 | 4.67 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 96.00 | 19.62 | 96.00 | 19.62 | 23.00 | 21.91 | 23.00 | 21.91 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 62.33 | 20.32 | 62.33 | 20.32 | 10.17 | 21.94 | 10.17 | 21.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 20.41 | 7.67 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40.00 | 19.67 | 40.00 | 19.67 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.47 | 0.17 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 20.41 | 1.67 | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 49.50 | 19.82 | 49.50 | 19.82 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 40.00 | 20.47 | 40.00 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.83 | 20.21 | 14.83 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55.17 | 19.36 | 55.17 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 22.15 | 0.33 | 22.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.38 | 0.67 | 22.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 22.47 | 4.17 | 22.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 22.38 | 6.17 | 22.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.21 | 3.50 | 22.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 22.00 | 1.50 | 22.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.47 | 0.50 | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.33 | 20.40 | 2.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.83 | 19.57 | 72.83 | 19.57 | 16.33 | 22.33 | 16.33 | 22.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 55.17 | 20.47 | 55.17 | 20.47 | 6.17 | 22.47 | 6.17 | 22.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 157.33 | 19.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 156.00 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 22.00 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 13.83 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 349.17 | 18.39 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 157.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 20.36 | 2.83 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23.83 | 20.03 | 23.83 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.70 | 0.17 | 21.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.71 | 0.33 | 21.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.67 | 0.17 | 21.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 20.48 | 0.17 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 20.42 | 2.00 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 28.83 | 20.09 | 28.83 | 20.09 | 1.17 | 21.74 | 1.17 | 21.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.83 | 20.48 | 23.83 | 20.48 | 0.50 | 21.80 | 0.50 | 21.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.67 | 20.29 | 13.67 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45.33 | 19.76 | 45.33 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 21.95 | 0.33 | 21.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.28 | 1.67 | 22.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.88 | 4.17 | 21.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 22.04 | 4.67 | 22.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 21.85 | 4.17 | 21.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.75 | 0.50 | 21.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 20.48 | 0.50 | 20.48 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 20.39 | 2.67 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.17 | 19.91 | 62.17 | 19.91 | 15.50 | 21.96 | 15.50 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 45.33 | 20.48 | 45.33 | 20.48 | 4.67 | 22.28 | 4.67 | 22.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 20.40 | 3.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16.67 | 20.21 | 16.67 | 20.21 | 0.33 | 21.75 | 0.33 | 21.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.71 | 0.17 | 21.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.72 | 0.50 | 21.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 21.74 | 1.33 | 21.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 21.80 | 2.50 | 21.80 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 21.92 | 2.33 | 21.92 |
November | 0.17 | 20.45 | 0.17 | 20.45 | 1.00 | 22.05 | 1.00 | 22.05 |
December | 2.50 | 20.39 | 2.50 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.50 | 20.26 | 22.50 | 20.26 | 8.17 | 21.85 | 8.17 | 21.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.67 | 20.45 | 16.67 | 20.45 | 2.50 | 22.05 | 2.50 | 22.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.33 | 16.77 | 47.33 | 16.77 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83.67 | 14.21 | 83.67 | 14.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4.50 | 18.59 | 4.50 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 135.50 | 15.25 | 135.50 | 15.25 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 83.67 | 18.59 | 83.67 | 18.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.17 | 16.75 | 46.17 | 16.75 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82.50 | 14.15 | 82.50 | 14.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 18.62 | 3.33 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 132.00 | 15.17 | 132.00 | 15.17 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 82.50 | 18.62 | 82.50 | 18.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.33 | 13.05 | 48.33 | 13.05 | 1.67 | 24.68 | 1.67 | 24.68 |
February | 64.83 | 10.44 | 64.83 | 10.44 | 7.17 | 24.71 | 7.17 | 24.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 24.72 | 29.33 | 24.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 40.00 | 24.75 | 40.00 | 24.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 24.74 | 10.83 | 24.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.73 | 4.00 | 24.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 24.74 | 17.83 | 24.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 43.67 | 24.73 | 43.67 | 24.73 |
November | 8.83 | 13.58 | 8.83 | 13.58 | 16.17 | 24.71 | 16.17 | 24.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.69 | 3.33 | 24.69 |
Annual Sum or Average | 122.00 | 11.70 | 122.00 | 11.70 | 174.00 | 24.73 | 174.00 | 24.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.83 | 13.58 | 64.83 | 13.58 | 43.67 | 24.75 | 43.67 | 24.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 124.33 | 18.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 134.17 | 14.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15.33 | 18.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.83 | 16.70 | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 134.17 | 18.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 22.24 | 95.50 | 19.73 | 95.50 | 19.73 |
February | 672.00 | 20.99 | 156.33 | 16.50 | 156.33 | 16.50 |
March | 744.00 | 22.08 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 720.00 | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 744.00 | 21.51 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 720.00 | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 744.00 | 21.62 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 744.00 | 22.27 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 688.67 | 23.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 586.83 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 593.33 | 23.59 | 2.17 | 23.98 | 0.00 | 0.00 |
December | 744.00 | 23.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8444.83 | 22.28 | 254.00 | 17.78 | 251.83 | 17.73 |
Minimum of Months | 586.83 | 20.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 23.74 | 156.33 | 23.98 | 156.33 | 19.73 |
Report: ComfortReportSimple55Monthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 739.33 | 20.57 | 617.00 | 20.42 | 617.00 | 20.42 |
February | 657.17 | 20.13 | 424.83 | 19.58 | 417.67 | 19.51 |
March | 727.50 | 21.17 | 280.67 | 21.03 | 277.67 | 21.00 |
April | 682.67 | 21.27 | 135.83 | 21.41 | 115.17 | 21.00 |
May | 736.17 | 21.29 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 650.17 | 21.50 | 30.50 | 23.29 | 0.00 | 0.00 |
July | 661.50 | 21.63 | 16.67 | 23.23 | 0.00 | 0.00 |
August | 622.83 | 21.67 | 50.00 | 23.43 | 0.00 | 0.00 |
September | 582.83 | 21.51 | 97.67 | 23.66 | 4.17 | 21.00 |
October | 667.17 | 21.29 | 58.50 | 23.32 | 12.83 | 21.00 |
November | 697.00 | 21.04 | 327.33 | 20.97 | 314.83 | 20.85 |
December | 729.00 | 21.08 | 585.67 | 20.99 | 582.67 | 20.98 |
Annual Sum or Average | 8153.33 | 21.17 | 2624.67 | 20.89 | 2342.00 | 20.55 |
Minimum of Months | 582.83 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 739.33 | 21.67 | 617.00 | 23.66 | 617.00 | 21.00 |
Report: ComfortReportSimple55Monthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.85 | 290.83 | 20.01 | 290.83 | 20.01 |
February | 672.00 | 20.54 | 148.83 | 16.61 | 148.83 | 16.61 |
March | 744.00 | 21.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 705.67 | 22.24 | 2.00 | 23.80 | 0.00 | 0.00 |
May | 723.83 | 22.41 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 654.00 | 22.41 | 16.17 | 23.81 | 0.00 | 0.00 |
July | 655.50 | 22.39 | 12.17 | 23.73 | 0.00 | 0.00 |
August | 629.67 | 22.47 | 34.83 | 23.77 | 0.00 | 0.00 |
September | 635.17 | 22.60 | 22.50 | 23.82 | 0.00 | 0.00 |
October | 732.83 | 22.58 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 719.50 | 21.90 | 51.50 | 20.47 | 51.50 | 20.47 |
December | 744.00 | 21.47 | 100.33 | 21.00 | 100.33 | 21.00 |
Annual Sum or Average | 8360.17 | 21.97 | 679.17 | 19.93 | 591.50 | 19.36 |
Minimum of Months | 629.67 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.60 | 290.83 | 23.82 | 290.83 | 21.00 |
Report: ComfortReportSimple55Monthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 407.33 | 20.11 | 379.67 | 21.15 | 183.00 | 18.62 |
February | 316.67 | 18.64 | 399.17 | 20.29 | 189.00 | 16.84 |
March | 266.67 | 22.90 | 440.83 | 23.56 | 154.50 | 24.18 |
April | 265.83 | 23.10 | 495.00 | 23.26 | 176.50 | 24.11 |
May | 280.83 | 23.37 | 558.33 | 22.90 | 222.83 | 23.98 |
June | 236.00 | 23.52 | 569.33 | 22.51 | 204.00 | 23.91 |
July | 198.67 | 23.68 | 601.33 | 22.31 | 185.00 | 23.88 |
August | 225.67 | 23.62 | 596.17 | 22.38 | 205.83 | 23.87 |
September | 260.17 | 23.38 | 522.67 | 22.87 | 205.83 | 24.00 |
October | 274.00 | 23.21 | 563.33 | 23.32 | 191.00 | 24.14 |
November | 294.00 | 22.50 | 442.83 | 23.21 | 170.83 | 23.43 |
December | 292.50 | 22.51 | 359.00 | 23.74 | 124.50 | 24.15 |
Annual Sum or Average | 3318.33 | 22.34 | 5927.67 | 22.65 | 2212.83 | 22.91 |
Minimum of Months | 198.67 | 18.64 | 359.00 | 20.29 | 124.50 | 16.84 |
Maximum of Months | 407.33 | 23.68 | 601.33 | 23.74 | 222.83 | 24.18 |
Report: ComfortReportSimple55Monthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 728.83 | 20.80 | 404.00 | 20.36 | 401.50 | 20.34 |
February | 645.33 | 20.65 | 217.67 | 18.86 | 203.67 | 18.51 |
March | 688.67 | 21.77 | 80.50 | 21.53 | 65.33 | 21.00 |
April | 584.00 | 22.00 | 76.67 | 23.35 | 9.50 | 21.89 |
May | 640.17 | 22.37 | 87.33 | 23.29 | 63.00 | 23.23 |
June | 472.00 | 22.42 | 237.00 | 23.39 | 107.83 | 23.42 |
July | 482.17 | 22.56 | 333.67 | 23.33 | 189.33 | 23.40 |
August | 432.50 | 22.68 | 385.17 | 23.44 | 180.50 | 23.51 |
September | 407.33 | 22.49 | 255.67 | 23.67 | 47.00 | 23.71 |
October | 566.67 | 22.30 | 93.83 | 23.94 | 0.00 | 0.00 |
November | 667.50 | 21.62 | 131.33 | 21.29 | 107.50 | 20.70 |
December | 711.50 | 21.33 | 272.17 | 21.12 | 261.83 | 21.00 |
Annual Sum or Average | 7026.67 | 21.82 | 2575.00 | 22.17 | 1637.00 | 21.39 |
Minimum of Months | 407.33 | 20.65 | 76.67 | 18.86 | 0.00 | 0.00 |
Maximum of Months | 728.83 | 22.68 | 404.00 | 23.94 | 401.50 | 23.71 |
Report: ComfortReportSimple55Monthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 21.20 | 165.33 | 19.43 | 165.33 | 19.43 |
February | 669.83 | 21.00 | 135.83 | 16.60 | 135.83 | 16.60 |
March | 719.17 | 22.34 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 628.33 | 22.53 | 22.00 | 23.72 | 0.00 | 0.00 |
May | 558.67 | 22.57 | 83.83 | 23.62 | 35.67 | 23.41 |
June | 423.50 | 22.35 | 150.33 | 23.62 | 20.83 | 23.32 |
July | 444.17 | 22.34 | 187.17 | 23.55 | 47.83 | 23.35 |
August | 444.17 | 22.48 | 250.50 | 23.64 | 65.33 | 23.49 |
September | 425.17 | 22.73 | 116.17 | 23.73 | 20.50 | 23.62 |
October | 603.00 | 22.88 | 8.33 | 23.96 | 0.00 | 0.00 |
November | 639.33 | 22.18 | 36.67 | 21.17 | 26.00 | 20.05 |
December | 744.00 | 21.90 | 38.17 | 21.00 | 38.17 | 21.00 |
Annual Sum or Average | 7043.33 | 22.15 | 1194.33 | 22.09 | 555.50 | 20.25 |
Minimum of Months | 423.50 | 21.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 744.00 | 22.88 | 250.50 | 23.96 | 165.33 | 23.62 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.57 | 712.17 | 20.54 | 712.17 | 20.54 |
February | 672.00 | 20.68 | 532.00 | 20.52 | 532.00 | 20.52 |
March | 743.67 | 21.00 | 391.33 | 20.70 | 391.33 | 20.70 |
April | 702.50 | 21.19 | 145.83 | 20.60 | 144.17 | 20.57 |
May | 720.00 | 21.51 | 3.00 | 21.61 | 2.67 | 21.40 |
June | 652.50 | 21.48 | 17.50 | 22.61 | 6.83 | 22.21 |
July | 647.50 | 21.48 | 22.17 | 22.72 | 5.50 | 22.06 |
August | 653.83 | 21.49 | 24.83 | 22.54 | 18.33 | 22.38 |
September | 665.67 | 21.42 | 12.83 | 21.21 | 11.33 | 21.00 |
October | 739.83 | 21.31 | 58.50 | 20.83 | 58.50 | 20.83 |
November | 719.00 | 20.88 | 422.50 | 20.63 | 422.50 | 20.63 |
December | 744.00 | 20.67 | 686.67 | 20.61 | 686.67 | 20.61 |
Annual Sum or Average | 8404.50 | 21.13 | 3029.33 | 20.64 | 2992.00 | 20.61 |
Minimum of Months | 647.50 | 20.57 | 3.00 | 20.52 | 2.67 | 20.52 |
Maximum of Months | 744.00 | 21.51 | 712.17 | 22.72 | 712.17 | 22.38 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.48 | 742.50 | 20.47 | 742.50 | 20.47 |
February | 672.00 | 20.46 | 624.33 | 20.41 | 624.33 | 20.41 |
March | 744.00 | 20.80 | 467.50 | 20.57 | 467.50 | 20.57 |
April | 692.50 | 21.15 | 198.50 | 20.95 | 183.83 | 20.64 |
May | 679.00 | 21.62 | 54.00 | 24.74 | 13.17 | 23.46 |
June | 603.17 | 21.88 | 120.17 | 24.70 | 57.33 | 24.58 |
July | 600.67 | 22.31 | 178.50 | 25.09 | 110.83 | 25.07 |
August | 609.33 | 22.10 | 175.00 | 24.47 | 105.83 | 24.11 |
September | 637.50 | 21.52 | 61.83 | 23.87 | 22.33 | 21.63 |
October | 741.33 | 21.10 | 156.83 | 20.68 | 156.83 | 20.68 |
November | 720.00 | 20.72 | 477.17 | 20.54 | 477.17 | 20.54 |
December | 744.00 | 20.51 | 742.50 | 20.51 | 742.50 | 20.51 |
Annual Sum or Average | 8187.50 | 21.18 | 3998.83 | 21.14 | 3704.17 | 20.83 |
Minimum of Months | 600.67 | 20.46 | 54.00 | 20.41 | 13.17 | 20.41 |
Maximum of Months | 744.00 | 22.31 | 742.50 | 25.09 | 742.50 | 25.07 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.63 | 632.83 | 20.54 | 632.83 | 20.54 |
February | 672.00 | 20.64 | 418.83 | 20.36 | 418.83 | 20.36 |
March | 744.00 | 21.05 | 272.83 | 20.80 | 272.83 | 20.80 |
April | 717.00 | 21.32 | 38.00 | 20.86 | 37.50 | 20.82 |
May | 732.83 | 21.66 | 9.50 | 23.36 | 7.00 | 23.10 |
June | 691.00 | 21.93 | 44.17 | 23.42 | 37.17 | 23.33 |
July | 693.17 | 22.14 | 106.00 | 23.78 | 79.67 | 23.64 |
August | 722.50 | 22.10 | 86.17 | 23.33 | 82.17 | 23.28 |
September | 712.33 | 21.70 | 1.33 | 23.25 | 1.33 | 23.25 |
October | 744.00 | 21.26 | 0.17 | 20.77 | 0.17 | 20.77 |
November | 720.00 | 20.99 | 281.83 | 20.69 | 281.83 | 20.69 |
December | 744.00 | 20.74 | 621.00 | 20.66 | 621.00 | 20.66 |
Annual Sum or Average | 8636.83 | 21.34 | 2512.67 | 20.88 | 2472.33 | 20.83 |
Minimum of Months | 672.00 | 20.63 | 0.17 | 20.36 | 0.17 | 20.36 |
Maximum of Months | 744.00 | 22.14 | 632.83 | 23.78 | 632.83 | 23.64 |
Report: ComfortReportSimple55Monthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.56 | 708.67 | 20.52 | 708.67 | 20.52 |
February | 672.00 | 20.65 | 537.83 | 20.50 | 537.83 | 20.50 |
March | 744.00 | 21.07 | 363.17 | 20.77 | 363.17 | 20.77 |
April | 704.00 | 21.24 | 167.00 | 20.65 | 166.33 | 20.64 |
May | 729.83 | 21.62 | 3.17 | 21.60 | 2.50 | 21.26 |
June | 652.33 | 21.52 | 9.33 | 22.56 | 4.33 | 22.17 |
July | 645.33 | 21.50 | 11.83 | 22.55 | 4.33 | 22.07 |
August | 659.83 | 21.53 | 19.17 | 22.38 | 15.67 | 22.28 |
September | 666.33 | 21.48 | 5.67 | 21.34 | 4.67 | 21.11 |
October | 744.00 | 21.37 | 49.17 | 20.97 | 49.17 | 20.97 |
November | 720.00 | 20.87 | 426.33 | 20.62 | 426.33 | 20.62 |
December | 744.00 | 20.65 | 682.67 | 20.60 | 682.67 | 20.60 |
Annual Sum or Average | 8425.67 | 21.16 | 2984.00 | 20.63 | 2965.67 | 20.61 |
Minimum of Months | 645.33 | 20.56 | 3.17 | 20.50 | 2.50 | 20.50 |
Maximum of Months | 744.00 | 21.62 | 708.67 | 22.56 | 708.67 | 22.28 |
Report: ComfortReportSimple55Monthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.47 | 739.17 | 20.46 | 739.17 | 20.46 |
February | 672.00 | 20.42 | 623.17 | 20.37 | 623.17 | 20.37 |
March | 744.00 | 20.86 | 449.33 | 20.64 | 449.33 | 20.64 |
April | 704.33 | 21.21 | 192.50 | 20.77 | 188.00 | 20.69 |
May | 714.33 | 21.77 | 23.67 | 23.74 | 12.33 | 23.41 |
June | 599.33 | 21.86 | 78.67 | 24.33 | 43.83 | 24.13 |
July | 567.50 | 22.08 | 155.17 | 24.26 | 91.67 | 24.13 |
August | 641.17 | 22.06 | 124.17 | 23.62 | 93.67 | 23.38 |
September | 682.33 | 21.69 | 19.50 | 23.20 | 9.00 | 21.80 |
October | 744.00 | 21.13 | 112.17 | 20.90 | 112.17 | 20.90 |
November | 720.00 | 20.71 | 477.17 | 20.52 | 477.17 | 20.52 |
December | 744.00 | 20.50 | 736.83 | 20.50 | 736.83 | 20.50 |
Annual Sum or Average | 8277.00 | 21.19 | 3731.50 | 20.89 | 3576.33 | 20.74 |
Minimum of Months | 567.50 | 20.42 | 19.50 | 20.37 | 9.00 | 20.37 |
Maximum of Months | 744.00 | 22.08 | 739.17 | 24.33 | 739.17 | 24.13 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.52 | 728.67 | 20.50 | 728.67 | 20.50 |
February | 672.00 | 20.63 | 588.50 | 20.53 | 588.50 | 20.53 |
March | 743.17 | 20.91 | 470.67 | 20.66 | 470.67 | 20.66 |
April | 696.00 | 21.13 | 221.67 | 20.70 | 214.17 | 20.62 |
May | 700.17 | 21.49 | 14.33 | 21.79 | 8.83 | 21.11 |
June | 619.33 | 21.40 | 35.50 | 22.71 | 9.33 | 21.96 |
July | 609.33 | 21.38 | 47.33 | 22.87 | 9.17 | 22.25 |
August | 616.33 | 21.39 | 48.50 | 22.59 | 21.67 | 22.04 |
September | 649.33 | 21.37 | 37.17 | 21.72 | 23.50 | 20.90 |
October | 738.67 | 21.26 | 158.83 | 20.86 | 158.83 | 20.86 |
November | 718.00 | 20.80 | 470.17 | 20.59 | 470.17 | 20.59 |
December | 744.00 | 20.60 | 714.83 | 20.57 | 714.83 | 20.57 |
Annual Sum or Average | 8250.33 | 21.06 | 3536.17 | 20.68 | 3418.33 | 20.60 |
Minimum of Months | 609.33 | 20.52 | 14.33 | 20.50 | 8.83 | 20.50 |
Maximum of Months | 744.00 | 21.49 | 728.67 | 22.87 | 728.67 | 22.25 |
Report: ComfortReportSimple55Monthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 744.00 | 20.45 | 743.67 | 20.45 | 743.67 | 20.45 |
February | 672.00 | 20.43 | 648.33 | 20.41 | 648.33 | 20.41 |
March | 744.00 | 20.73 | 526.17 | 20.55 | 526.17 | 20.55 |
April | 690.17 | 21.13 | 277.67 | 21.01 | 258.83 | 20.75 |
May | 665.50 | 21.72 | 82.00 | 24.81 | 35.00 | 24.34 |
June | 576.83 | 22.05 | 142.17 | 25.17 | 77.33 | 25.72 |
July | 578.33 | 22.66 | 211.00 | 25.58 | 143.00 | 26.07 |
August | 585.17 | 22.35 | 199.17 | 25.07 | 134.33 | 25.11 |
September | 620.33 | 21.53 | 106.67 | 23.69 | 49.17 | 22.18 |
October | 739.83 | 21.02 | 292.33 | 20.71 | 291.83 | 20.71 |
November | 720.00 | 20.65 | 535.50 | 20.52 | 535.50 | 20.52 |
December | 744.00 | 20.48 | 743.83 | 20.48 | 743.83 | 20.48 |
Annual Sum or Average | 8080.17 | 21.20 | 4508.50 | 21.27 | 4187.00 | 21.00 |
Minimum of Months | 576.83 | 20.43 | 82.00 | 20.41 | 35.00 | 20.41 |
Maximum of Months | 744.00 | 22.66 | 743.83 | 25.58 | 743.83 | 26.07 |
Report: ComfortReportSimple55Monthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 743.00 | 20.95 | 599.83 | 20.72 | 599.83 | 20.72 |
February | 661.50 | 21.05 | 399.17 | 20.72 | 399.17 | 20.72 |
March | 736.33 | 21.24 | 270.17 | 20.79 | 270.17 | 20.79 |
April | 696.33 | 21.26 | 142.67 | 20.72 | 140.50 | 20.68 |
May | 724.67 | 21.57 | 0.17 | 21.26 | 0.17 | 21.26 |
June | 670.00 | 21.54 | 10.17 | 22.10 | 10.17 | 22.10 |
July | 655.83 | 21.49 | 12.83 | 22.30 | 12.83 | 22.30 |
August | 653.00 | 21.48 | 24.50 | 21.99 | 24.00 | 21.96 |
September | 644.83 | 21.43 | 27.83 | 22.93 | 4.67 | 21.19 |
October | 691.33 | 21.37 | 21.33 | 21.37 | 17.67 | 20.97 |
November | 705.50 | 21.12 | 320.33 | 20.74 | 319.83 | 20.74 |
December | 736.33 | 20.97 | 566.83 | 20.70 | 566.83 | 20.70 |
Annual Sum or Average | 8318.67 | 21.28 | 2395.83 | 20.78 | 2365.83 | 20.75 |
Minimum of Months | 644.83 | 20.95 | 0.17 | 20.70 | 0.17 | 20.68 |
Maximum of Months | 743.00 | 21.57 | 599.83 | 22.93 | 599.83 | 22.30 |
Report: ComfortReportSimple55Monthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 708.50 | 22.21 | 111.17 | 18.81 | 111.17 | 18.81 |
February | 550.33 | 21.59 | 121.50 | 16.33 | 121.50 | 16.33 |
March | 489.17 | 23.23 | 52.83 | 23.98 | 0.00 | 0.00 |
April | 258.67 | 23.20 | 169.00 | 23.89 | 9.33 | 23.86 |
May | 151.00 | 23.45 | 440.00 | 23.89 | 71.83 | 23.98 |
June | 112.67 | 23.80 | 607.33 | 23.84 | 95.33 | 23.97 |
July | 189.00 | 23.90 | 649.33 | 23.81 | 178.83 | 23.98 |
August | 178.50 | 23.83 | 603.83 | 23.82 | 161.17 | 23.97 |
September | 178.17 | 23.23 | 403.83 | 23.86 | 53.83 | 23.96 |
October | 267.33 | 23.06 | 98.00 | 23.97 | 0.00 | 0.00 |
November | 495.83 | 22.97 | 97.17 | 23.20 | 22.33 | 20.66 |
December | 712.67 | 23.04 | 10.67 | 21.03 | 10.67 | 21.03 |
Annual Sum or Average | 4291.83 | 22.85 | 3364.67 | 23.38 | 836.00 | 22.05 |
Minimum of Months | 112.67 | 21.59 | 10.67 | 16.33 | 0.00 | 0.00 |
Maximum of Months | 712.67 | 23.90 | 649.33 | 23.98 | 178.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 636.17 | 22.31 | 101.83 | 18.74 | 99.17 | 18.60 |
February | 430.00 | 21.27 | 110.00 | 15.91 | 108.00 | 15.76 |
March | 264.33 | 23.22 | 93.67 | 23.98 | 0.00 | 0.00 |
April | 105.67 | 23.25 | 263.67 | 23.90 | 3.50 | 23.90 |
May | 50.17 | 23.98 | 616.00 | 23.85 | 48.83 | 23.99 |
June | 63.50 | 23.99 | 695.83 | 23.84 | 63.50 | 23.99 |
July | 140.67 | 23.99 | 734.00 | 23.80 | 140.67 | 23.99 |
August | 131.67 | 23.99 | 723.67 | 23.77 | 131.67 | 23.99 |
September | 67.83 | 23.66 | 530.50 | 23.87 | 42.83 | 23.99 |
October | 115.33 | 23.19 | 209.00 | 23.98 | 0.00 | 0.00 |
November | 317.50 | 22.98 | 141.67 | 23.59 | 12.17 | 19.35 |
December | 541.67 | 23.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2864.50 | 22.79 | 4219.83 | 23.50 | 650.33 | 21.71 |
Minimum of Months | 50.17 | 21.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 636.17 | 23.99 | 734.00 | 23.98 | 140.67 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 524.50 | 22.25 | 585.67 | 22.91 | 411.83 | 22.51 |
February | 493.83 | 21.72 | 560.67 | 22.16 | 439.83 | 21.72 |
March | 537.17 | 23.94 | 640.83 | 23.98 | 491.00 | 24.10 |
April | 509.17 | 24.09 | 664.00 | 23.93 | 502.50 | 24.12 |
May | 548.50 | 24.04 | 738.33 | 23.81 | 548.50 | 24.04 |
June | 540.17 | 24.00 | 720.00 | 23.70 | 540.17 | 24.00 |
July | 559.67 | 23.98 | 744.00 | 23.63 | 559.67 | 23.98 |
August | 558.33 | 23.98 | 744.00 | 23.67 | 558.33 | 23.98 |
September | 523.50 | 24.04 | 712.50 | 23.77 | 523.50 | 24.04 |
October | 519.17 | 24.12 | 696.33 | 23.94 | 519.17 | 24.12 |
November | 512.33 | 23.70 | 624.50 | 23.79 | 466.00 | 23.87 |
December | 520.00 | 23.65 | 584.67 | 23.99 | 420.50 | 24.03 |
Annual Sum or Average | 6346.33 | 23.64 | 8015.50 | 23.63 | 5981.00 | 23.75 |
Minimum of Months | 493.83 | 21.72 | 560.67 | 22.16 | 411.83 | 21.72 |
Maximum of Months | 559.67 | 24.12 | 744.00 | 23.99 | 559.67 | 24.12 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.23763 | 17.16397 | -0.2371 | 7.78075 |
February | 672.00000 | 20.98447 | 21.37195 | -0.5152 | 17.67859 |
March | 744.00000 | 22.08094 | 27.79984 | -0.2282 | 6.23605 |
April | 720.00000 | 21.61506 | 35.92224 | -0.2945 | 6.92672 |
May | 744.00000 | 21.51024 | 49.40519 | -1.3896 | 45.04416 |
June | 720.00000 | 21.53048 | 55.98719 | -1.3278 | 41.86922 |
July | 744.00000 | 21.62021 | 58.43424 | -1.2694 | 38.84503 |
August | 744.00000 | 22.26711 | 55.73212 | -1.0533 | 28.69254 |
September | 720.00000 | 23.06640 | 44.02009 | -0.8524 | 20.71046 |
October | 744.00000 | 23.78083 | 31.39097 | 0.23738 | 6.24801 |
November | 720.00000 | 23.64309 | 26.81990 | 0.17134 | 6.05069 |
December | 744.00000 | 23.58272 | 19.69700 | 0.10021 | 5.32209 |
Annual Sum or Average | 8760.00000 | 22.33613 | 37.06636 | -0.5550 | 19.30121 |
Minimum of Months | 672.00000 | 20.98447 | 17.16397 | -1.3896 | 5.32209 |
Maximum of Months | 744.00000 | 23.78083 | 58.43424 | 0.23738 | 45.04416 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_1_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.59005 | 16.55723 | -0.7423 | 18.95644 |
February | 672.00000 | 20.21079 | 20.65191 | -0.7504 | 20.74744 |
March | 744.00000 | 21.22279 | 27.28244 | -0.4407 | 10.15240 |
April | 720.00000 | 21.37995 | 34.70816 | -0.3123 | 8.59823 |
May | 744.00000 | 21.30167 | 49.00882 | -1.3300 | 42.33136 |
June | 720.00000 | 21.65556 | 55.58218 | -1.1291 | 33.20715 |
July | 744.00000 | 21.78437 | 58.70157 | -1.0434 | 29.07272 |
August | 744.00000 | 21.90713 | 57.31647 | -1.0076 | 27.95039 |
September | 720.00000 | 21.90633 | 45.43295 | -1.1125 | 34.36907 |
October | 744.00000 | 21.55812 | 33.87767 | -0.2418 | 7.93226 |
November | 720.00000 | 21.13284 | 28.85837 | -0.4651 | 11.21999 |
December | 744.00000 | 21.13676 | 20.13517 | -0.5857 | 13.36429 |
Annual Sum or Average | 8760.00000 | 21.32238 | 37.43826 | -0.7636 | 21.49402 |
Minimum of Months | 672.00000 | 20.21079 | 16.55723 | -1.3300 | 7.93226 |
Maximum of Months | 744.00000 | 21.90713 | 58.70157 | -0.2418 | 42.33136 |
Report: OccupantComfortDataSummaryMonthly
For: RETAIL_2_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.84994 | 18.72505 | -0.5609 | 13.49772 |
February | 672.00000 | 20.53570 | 22.44035 | -0.5980 | 18.07096 |
March | 744.00000 | 21.90827 | 28.60999 | -0.2315 | 6.81726 |
April | 720.00000 | 22.26960 | 35.38779 | -0.0899 | 5.88775 |
May | 744.00000 | 22.43504 | 48.01013 | -1.0044 | 26.88786 |
June | 720.00000 | 22.51298 | 54.34378 | -0.9191 | 23.51708 |
July | 744.00000 | 22.51763 | 57.14377 | -0.8897 | 22.32743 |
August | 744.00000 | 22.62907 | 56.06889 | -0.8592 | 21.22863 |
September | 720.00000 | 22.71562 | 45.55075 | -0.9118 | 23.37444 |
October | 744.00000 | 22.59502 | 34.31684 | -0.0149 | 5.34893 |
November | 720.00000 | 21.89969 | 29.84393 | -0.2258 | 7.34485 |
December | 744.00000 | 21.46554 | 22.25809 | -0.3919 | 8.59042 |
Annual Sum or Average | 8760.00000 | 22.03658 | 37.81160 | -0.5580 | 15.22016 |
Minimum of Months | 672.00000 | 20.53570 | 18.72505 | -1.0044 | 5.34893 |
Maximum of Months | 744.00000 | 22.71562 | 57.14377 | -0.0149 | 26.88786 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.40602 | 13.70357 | 0.14987 | 19.00048 |
February | 672.00000 | 20.89272 | 17.43596 | 0.07322 | 23.29731 |
March | 744.00000 | 22.82673 | 23.29373 | 0.57098 | 15.06873 |
April | 720.00000 | 22.73737 | 30.50644 | 0.61759 | 16.16013 |
May | 744.00000 | 22.46847 | 43.62505 | -0.1036 | 12.26496 |
June | 720.00000 | 22.20494 | 50.75153 | -0.1240 | 12.60912 |
July | 744.00000 | 22.05664 | 53.88816 | -0.1480 | 12.58189 |
August | 744.00000 | 22.11513 | 53.00185 | -0.1328 | 12.83059 |
September | 720.00000 | 22.40722 | 42.13728 | -0.1269 | 12.37789 |
October | 744.00000 | 22.83914 | 29.62225 | 0.64288 | 16.73315 |
November | 720.00000 | 22.62569 | 24.69487 | 0.53097 | 15.78930 |
December | 744.00000 | 22.74263 | 16.87638 | 0.47611 | 12.86805 |
Annual Sum or Average | 8760.00000 | 22.28589 | 33.38425 | 0.20301 | 15.07452 |
Minimum of Months | 672.00000 | 20.89272 | 13.70357 | -0.1480 | 12.26496 |
Maximum of Months | 744.00000 | 22.83914 | 53.88816 | 0.64288 | 23.29731 |
Report: OccupantComfortDataSummaryMonthly
For: CAFE_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.86188 | 22.33254 | -0.5793 | 14.46861 |
February | 672.00000 | 20.77621 | 25.98141 | -0.5271 | 16.67070 |
March | 744.00000 | 21.90247 | 32.44398 | -0.1955 | 7.43534 |
April | 720.00000 | 22.26795 | 39.31310 | -0.0314 | 6.95164 |
May | 744.00000 | 22.49006 | 52.09501 | -0.8737 | 22.12032 |
June | 720.00000 | 22.68390 | 58.37773 | -0.7242 | 17.30134 |
July | 744.00000 | 22.73323 | 61.23813 | -0.6661 | 15.24692 |
August | 744.00000 | 22.90321 | 59.95619 | -0.6125 | 13.90735 |
September | 720.00000 | 22.94993 | 49.13023 | -0.6935 | 17.83328 |
October | 744.00000 | 22.65593 | 38.23460 | 0.08481 | 6.62152 |
November | 720.00000 | 21.77752 | 33.83733 | -0.2269 | 8.55905 |
December | 744.00000 | 21.43682 | 25.99157 | -0.4146 | 10.04136 |
Annual Sum or Average | 8760.00000 | 22.12768 | 41.66653 | -0.4548 | 13.07184 |
Minimum of Months | 672.00000 | 20.77621 | 22.33254 | -0.8737 | 6.62152 |
Maximum of Months | 744.00000 | 22.94993 | 61.23813 | 0.08481 | 22.12032 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_FLR_1 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 21.19788 | 21.13886 | -0.4448 | 11.41460 |
February | 672.00000 | 21.00832 | 24.63813 | -0.4554 | 16.20375 |
March | 744.00000 | 22.39024 | 30.83780 | -0.0815 | 6.04065 |
April | 720.00000 | 22.67277 | 37.60763 | 0.04476 | 5.91721 |
May | 744.00000 | 22.82729 | 49.98480 | -0.8184 | 20.07905 |
June | 720.00000 | 22.82423 | 56.44635 | -0.7550 | 17.95826 |
July | 744.00000 | 22.77285 | 59.36193 | -0.7422 | 17.48820 |
August | 744.00000 | 22.90961 | 58.22557 | -0.7018 | 16.25183 |
September | 720.00000 | 23.07030 | 47.66879 | -0.7323 | 17.21776 |
October | 744.00000 | 23.06688 | 36.42454 | 0.14182 | 5.84690 |
November | 720.00000 | 22.35258 | 32.03396 | -0.0811 | 6.78108 |
December | 744.00000 | 21.90471 | 24.63724 | -0.2562 | 7.09190 |
Annual Sum or Average | 8760.00000 | 22.42461 | 40.00412 | -0.4067 | 12.33025 |
Minimum of Months | 672.00000 | 21.00832 | 21.13886 | -0.8184 | 5.84690 |
Maximum of Months | 744.00000 | 23.07030 | 59.36193 | 0.14182 | 20.07905 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.56546 | 25.29185 | -0.7795 | 18.42673 |
February | 672.00000 | 20.67611 | 29.19755 | -0.6911 | 16.20535 |
March | 744.00000 | 21.00294 | 35.28104 | -0.5207 | 11.58575 |
April | 720.00000 | 21.23845 | 41.44039 | -0.3603 | 9.01688 |
May | 744.00000 | 21.55905 | 52.13023 | -1.3069 | 41.61098 |
June | 720.00000 | 21.63269 | 55.80080 | -1.1953 | 36.42888 |
July | 744.00000 | 21.69827 | 57.72869 | -1.1285 | 33.34274 |
August | 744.00000 | 21.69065 | 57.72013 | -1.1499 | 34.33356 |
September | 720.00000 | 21.55364 | 49.47247 | -1.3108 | 42.18169 |
October | 744.00000 | 21.32398 | 41.70900 | -0.3543 | 8.34820 |
November | 720.00000 | 20.88133 | 37.24528 | -0.5640 | 12.73637 |
December | 744.00000 | 20.66736 | 28.77367 | -0.7205 | 16.59927 |
Annual Sum or Average | 8760.00000 | 21.21056 | 42.72321 | -0.8412 | 23.44200 |
Minimum of Months | 672.00000 | 20.56546 | 25.29185 | -1.3108 | 8.34820 |
Maximum of Months | 744.00000 | 21.69827 | 57.72869 | -0.3543 | 42.18169 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.47573 | 25.48018 | -0.8306 | 20.20388 |
February | 672.00000 | 20.46448 | 29.55323 | -0.7699 | 18.61941 |
March | 744.00000 | 20.80328 | 35.69295 | -0.5865 | 13.00268 |
April | 720.00000 | 21.26079 | 41.65961 | -0.3714 | 9.66190 |
May | 744.00000 | 21.87001 | 51.90674 | -1.2261 | 39.11074 |
June | 720.00000 | 22.24250 | 55.08597 | -1.0206 | 31.59278 |
July | 744.00000 | 22.66575 | 56.63640 | -0.8505 | 26.58738 |
August | 744.00000 | 22.47841 | 57.22943 | -0.9310 | 28.21197 |
September | 720.00000 | 21.83388 | 49.53458 | -1.2589 | 40.94363 |
October | 744.00000 | 21.10907 | 42.26813 | -0.4314 | 9.41512 |
November | 720.00000 | 20.71837 | 37.62640 | -0.6235 | 14.09547 |
December | 744.00000 | 20.50902 | 29.07117 | -0.7816 | 18.44990 |
Annual Sum or Average | 8760.00000 | 21.37513 | 42.71650 | -0.8070 | 22.50572 |
Minimum of Months | 672.00000 | 20.46448 | 25.48018 | -1.2589 | 9.41512 |
Maximum of Months | 744.00000 | 22.66575 | 57.22943 | -0.3714 | 40.94363 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Annual Sum or Average | 0.00000 | ||||
Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_4_MULT19_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.62630 | 24.45049 | -0.7023 | 16.00248 |
February | 672.00000 | 20.63968 | 28.26927 | -0.6609 | 15.26515 |
March | 744.00000 | 21.04774 | 34.39549 | -0.4931 | 10.40741 |
April | 720.00000 | 21.32855 | 40.35006 | -0.3579 | 8.29232 |
May | 744.00000 | 21.69209 | 49.47050 | -1.3193 | 42.03750 |
June | 720.00000 | 22.01100 | 54.15104 | -1.1542 | 34.59281 |
July | 744.00000 | 22.27547 | 57.27965 | -1.0406 | 29.97980 |
August | 744.00000 | 22.15327 | 56.69649 | -1.0940 | 31.94322 |
September | 720.00000 | 21.72431 | 48.00071 | -1.3236 | 42.37767 |
October | 744.00000 | 21.25578 | 40.52505 | -0.3798 | 8.15671 |
November | 720.00000 | 20.99068 | 35.83904 | -0.5061 | 10.94382 |
December | 744.00000 | 20.73514 | 28.13453 | -0.6469 | 14.20435 |
Annual Sum or Average | 8760.00000 | 21.37783 | 41.53776 | -0.8074 | 22.05013 |
Minimum of Months | 672.00000 | 20.62630 | 24.45049 | -1.3236 | 8.15671 |
Maximum of Months | 744.00000 | 22.27547 | 57.27965 | -0.3579 | 42.37767 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_5_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.55539 | 25.26541 | -0.7801 | 18.45557 |
February | 672.00000 | 20.64953 | 29.17144 | -0.6990 | 16.51525 |
March | 744.00000 | 21.06661 | 35.14065 | -0.5046 | 11.24624 |
April | 720.00000 | 21.28412 | 41.24399 | -0.3604 | 9.06595 |
May | 744.00000 | 21.64583 | 51.05789 | -1.2743 | 40.05973 |
June | 720.00000 | 21.67402 | 54.73548 | -1.1836 | 35.90095 |
July | 744.00000 | 21.72519 | 56.93682 | -1.1287 | 33.35856 |
August | 744.00000 | 21.72140 | 56.95219 | -1.1505 | 34.35448 |
September | 720.00000 | 21.60833 | 48.89159 | -1.2931 | 41.32061 |
October | 744.00000 | 21.37042 | 41.63883 | -0.3464 | 8.22489 |
November | 720.00000 | 20.87488 | 37.26280 | -0.5663 | 12.78212 |
December | 744.00000 | 20.65114 | 28.78029 | -0.7239 | 16.68003 |
Annual Sum or Average | 8760.00000 | 21.23902 | 42.32808 | -0.8352 | 23.20077 |
Minimum of Months | 672.00000 | 20.55539 | 25.26541 | -1.2931 | 8.22489 |
Maximum of Months | 744.00000 | 21.72519 | 56.95219 | -0.3464 | 41.32061 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_6_FLR_3 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.46706 | 25.44784 | -0.8317 | 20.28028 |
February | 672.00000 | 20.42330 | 29.52415 | -0.7815 | 19.12089 |
March | 744.00000 | 20.85764 | 35.54688 | -0.5723 | 12.57442 |
April | 720.00000 | 21.25988 | 41.56582 | -0.3819 | 9.53222 |
May | 744.00000 | 21.84708 | 51.15059 | -1.2256 | 38.10759 |
June | 720.00000 | 22.17392 | 54.65815 | -1.0395 | 31.12906 |
July | 744.00000 | 22.48219 | 57.22434 | -0.9078 | 26.18092 |
August | 744.00000 | 22.29836 | 57.45670 | -0.9910 | 28.41600 |
September | 720.00000 | 21.80294 | 49.20589 | -1.2660 | 40.33900 |
October | 744.00000 | 21.12638 | 42.23101 | -0.4305 | 9.17787 |
November | 720.00000 | 20.70973 | 37.63200 | -0.6271 | 14.18685 |
December | 744.00000 | 20.50327 | 29.06681 | -0.7840 | 18.56629 |
Annual Sum or Average | 8760.00000 | 21.33504 | 42.63118 | -0.8201 | 22.31069 |
Minimum of Months | 672.00000 | 20.42330 | 25.44784 | -1.2660 | 9.17787 |
Maximum of Months | 744.00000 | 22.48219 | 57.45670 | -0.3819 | 40.33900 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_1_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.51714 | 25.62798 | -0.8419 | 20.59139 |
February | 672.00000 | 20.62602 | 29.69298 | -0.7389 | 17.64703 |
March | 744.00000 | 20.91321 | 35.94907 | -0.5705 | 12.92306 |
April | 720.00000 | 21.20088 | 42.00667 | -0.3791 | 9.66278 |
May | 744.00000 | 21.58457 | 52.22124 | -1.2868 | 40.88244 |
June | 720.00000 | 21.64812 | 55.35462 | -1.1640 | 35.25688 |
July | 744.00000 | 21.70923 | 56.91988 | -1.0923 | 31.97798 |
August | 744.00000 | 21.69845 | 57.23972 | -1.1194 | 33.18409 |
September | 720.00000 | 21.54529 | 49.69111 | -1.3054 | 42.20720 |
October | 744.00000 | 21.26927 | 42.46546 | -0.3829 | 8.95637 |
November | 720.00000 | 20.80201 | 38.01247 | -0.6155 | 14.19540 |
December | 744.00000 | 20.59611 | 29.21414 | -0.7847 | 18.65859 |
Annual Sum or Average | 8760.00000 | 21.17903 | 42.93729 | -0.8577 | 23.87994 |
Minimum of Months | 672.00000 | 20.51714 | 25.62798 | -1.3054 | 8.95637 |
Maximum of Months | 744.00000 | 21.70923 | 57.23972 | -0.3791 | 42.20720 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_2_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.45280 | 25.80736 | -0.8894 | 22.37340 |
February | 672.00000 | 20.43233 | 30.04517 | -0.8169 | 20.15955 |
March | 744.00000 | 20.73312 | 36.36235 | -0.6348 | 14.37219 |
April | 720.00000 | 21.25316 | 42.11443 | -0.3847 | 10.51018 |
May | 744.00000 | 22.00542 | 51.58335 | -1.1709 | 37.99628 |
June | 720.00000 | 22.40582 | 53.97849 | -0.9398 | 30.68946 |
July | 744.00000 | 22.91199 | 54.59428 | -0.7365 | 26.12048 |
August | 744.00000 | 22.69895 | 55.60456 | -0.8310 | 27.12745 |
September | 720.00000 | 21.91789 | 49.36517 | -1.2239 | 40.64379 |
October | 744.00000 | 21.03909 | 43.09526 | -0.4664 | 10.25323 |
November | 720.00000 | 20.65294 | 38.39953 | -0.6743 | 15.62651 |
December | 744.00000 | 20.47966 | 29.47699 | -0.8394 | 20.46976 |
Annual Sum or Average | 8760.00000 | 21.42179 | 42.60066 | -0.8005 | 23.03743 |
Minimum of Months | 672.00000 | 20.43233 | 25.80736 | -1.2239 | 10.25323 |
Maximum of Months | 744.00000 | 22.91199 | 55.60456 | -0.3847 | 40.64379 |
Report: OccupantComfortDataSummaryMonthly
For: ROOM_3_MULT9_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 20.95711 | 27.22614 | -0.6384 | 14.95756 |
February | 672.00000 | 21.08499 | 30.80813 | -0.5432 | 12.71386 |
March | 744.00000 | 21.25674 | 36.40183 | -0.4366 | 10.36817 |
April | 720.00000 | 21.33091 | 42.11607 | -0.3436 | 8.87764 |
May | 744.00000 | 21.61506 | 51.54271 | -1.3077 | 41.74331 |
June | 720.00000 | 21.65723 | 55.72448 | -1.2188 | 37.49964 |
July | 744.00000 | 21.69876 | 57.99583 | -1.1645 | 34.96904 |
August | 744.00000 | 21.69575 | 57.08663 | -1.1698 | 35.31311 |
September | 720.00000 | 21.61884 | 49.01169 | -1.2792 | 40.91975 |
October | 744.00000 | 21.50785 | 42.15668 | -0.2745 | 7.77052 |
November | 720.00000 | 21.16622 | 38.13320 | -0.4614 | 10.98490 |
December | 744.00000 | 20.98950 | 30.51019 | -0.5988 | 14.24625 |
Annual Sum or Average | 8760.00000 | 21.38334 | 43.29510 | -0.7879 | 22.58864 |
Minimum of Months | 672.00000 | 20.95711 | 27.22614 | -1.3077 | 7.77052 |
Maximum of Months | 744.00000 | 21.69876 | 57.99583 | -0.2745 | 41.74331 |
Report: OccupantComfortDataSummaryMonthly
For: BANQUET_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.29174 | 23.14519 | -0.2029 | 9.83312 |
February | 672.00000 | 22.02671 | 26.12205 | -0.2233 | 15.53359 |
March | 744.00000 | 23.47663 | 31.75911 | 0.18601 | 6.38616 |
April | 720.00000 | 23.63123 | 37.83551 | 0.30353 | 7.40512 |
May | 744.00000 | 23.67786 | 49.29907 | -0.4624 | 9.93079 |
June | 720.00000 | 23.70518 | 55.29298 | -0.3676 | 8.22724 |
July | 744.00000 | 23.68017 | 58.05311 | -0.3434 | 7.86058 |
August | 744.00000 | 23.62581 | 57.47010 | -0.3791 | 8.47336 |
September | 720.00000 | 23.63550 | 47.96552 | -0.4880 | 10.64133 |
October | 744.00000 | 23.62913 | 37.22153 | 0.29119 | 7.09015 |
November | 720.00000 | 23.27540 | 33.12845 | 0.14097 | 6.93447 |
December | 744.00000 | 23.08031 | 26.44913 | 0.00841 | 6.04650 |
Annual Sum or Average | 8760.00000 | 23.31912 | 40.39289 | -0.1275 | 8.64500 |
Minimum of Months | 672.00000 | 22.02671 | 23.14519 | -0.4880 | 6.04650 |
Maximum of Months | 744.00000 | 23.70518 | 58.05311 | 0.30353 | 15.53359 |
Report: OccupantComfortDataSummaryMonthly
For: DINING_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.55269 | 22.33346 | -0.0998 | 9.38959 |
February | 672.00000 | 22.23965 | 25.18009 | -0.1300 | 15.53814 |
March | 744.00000 | 23.67707 | 30.64567 | 0.27677 | 7.05014 |
April | 720.00000 | 23.79053 | 36.73132 | 0.38259 | 8.39020 |
May | 744.00000 | 23.81027 | 48.17867 | -0.3601 | 7.99220 |
June | 720.00000 | 23.81584 | 54.26792 | -0.2786 | 6.86605 |
July | 744.00000 | 23.78645 | 57.04562 | -0.2586 | 6.63659 |
August | 744.00000 | 23.74868 | 56.42272 | -0.2877 | 7.01960 |
September | 720.00000 | 23.76850 | 46.91006 | -0.3884 | 8.57519 |
October | 744.00000 | 23.78534 | 36.10029 | 0.36989 | 8.04679 |
November | 720.00000 | 23.49134 | 32.07261 | 0.23458 | 7.46028 |
December | 744.00000 | 23.34725 | 25.44735 | 0.11506 | 6.07703 |
Annual Sum or Average | 8760.00000 | 23.49215 | 39.35859 | -0.0348 | 8.19833 |
Minimum of Months | 672.00000 | 22.23965 | 22.33346 | -0.3884 | 6.07703 |
Maximum of Months | 744.00000 | 23.81584 | 57.04562 | 0.38259 | 15.53814 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_FLR_6 PEOPLE
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 744.00000 | 22.64649 | 21.78937 | 0.56179 | 23.77679 |
February | 672.00000 | 22.16784 | 25.54228 | 0.50748 | 29.43180 |
March | 744.00000 | 23.77191 | 29.04538 | 0.95407 | 27.22101 |
April | 720.00000 | 23.83126 | 35.37275 | 1.05776 | 31.33352 |
May | 744.00000 | 23.80411 | 46.99218 | 0.61111 | 18.67321 |
June | 720.00000 | 23.69658 | 53.36539 | 0.66686 | 20.79034 |
July | 744.00000 | 23.63327 | 56.19325 | 0.68152 | 21.60049 |
August | 744.00000 | 23.67327 | 55.40147 | 0.66987 | 20.83255 |
September | 720.00000 | 23.76172 | 45.74945 | 0.58449 | 18.34958 |
October | 744.00000 | 23.86152 | 34.62791 | 1.05028 | 30.76702 |
November | 720.00000 | 23.59566 | 30.59661 | 0.90420 | 26.96535 |
December | 744.00000 | 23.62483 | 23.70226 | 0.81447 | 22.19900 |
Annual Sum or Average | 8760.00000 | 23.51434 | 38.26854 | 0.75684 | 24.28610 |
Minimum of Months | 672.00000 | 22.16784 | 21.78937 | 0.50748 | 18.34958 |
Maximum of Months | 744.00000 | 23.86152 | 56.19325 | 1.05776 | 31.33352 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.281392E+09 | 11126.98 | 01-JAN-09:02 | 57.89 | 0.876800E+09 | 0.00 | 0.115819E+10 | 0.24 | 3.12 | 01-JAN-09:05 | 0.00 | 0.00 |
February | 0.622230E+09 | 12989.37 | 24-FEB-16:03 | 107.08 | 0.193883E+10 | 0.00 | 0.256106E+10 | 0.50 | 3.12 | 07-FEB-09:03 | 0.00 | 0.00 |
March | 0.509022E+10 | 76041.17 | 25-MAR-15:01 | 283.99 | 0.154212E+11 | 0.00 | 0.205114E+11 | 1.18 | 3.44 | 25-MAR-15:01 | 0.00 | 0.00 |
April | 0.310833E+11 | 138422.38 | 18-APR-15:03 | 449.74 | 0.963980E+11 | 0.00 | 0.127481E+12 | 1.93 | 3.91 | 16-APR-21:13 | 0.00 | 0.00 |
May | 0.744786E+11 | 133869.91 | 31-MAY-15:03 | 728.50 | 0.226526E+12 | 0.00 | 0.301004E+12 | 2.98 | 3.94 | 29-MAY-08:13 | 0.00 | 0.00 |
June | 0.162072E+12 | 191620.99 | 11-JUN-15:03 | 710.46 | 0.526177E+12 | 0.00 | 0.688248E+12 | 3.13 | 4.12 | 11-JUN-21:12 | 0.00 | 0.00 |
July | 0.216832E+12 | 203179.61 | 26-JUL-18:03 | 744.00 | 0.734873E+12 | 0.00 | 0.951705E+12 | 3.30 | 4.21 | 06-JUL-21:13 | 0.00 | 0.00 |
August | 0.193587E+12 | 209228.33 | 04-AUG-15:03 | 744.00 | 0.641465E+12 | 0.00 | 0.835052E+12 | 3.22 | 4.19 | 28-AUG-21:13 | 0.00 | 0.00 |
September | 0.945378E+11 | 157863.60 | 06-SEP-15:03 | 682.33 | 0.285466E+12 | 0.00 | 0.380004E+12 | 2.88 | 4.08 | 11-SEP-21:12 | 0.00 | 0.00 |
October | 0.177844E+11 | 115990.98 | 20-OCT-15:02 | 545.67 | 0.536636E+11 | 0.00 | 0.714480E+11 | 2.27 | 3.78 | 20-OCT-15:02 | 0.00 | 0.00 |
November | 0.480530E+10 | 62163.89 | 03-NOV-15:01 | 261.92 | 0.148105E+11 | 0.00 | 0.196158E+11 | 1.13 | 3.12 | 01-NOV-06:30 | 0.00 | 0.00 |
December | 0.514379E+09 | 13484.36 | 02-DEC-09:02 | 89.84 | 0.160277E+10 | 0.00 | 0.211715E+10 | 0.38 | 3.12 | 01-DEC-09:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.801688E+12 | 5405.43 | 0.259922E+13 | 0.340091E+13 | 1.94 | |||||||
Minimum of Months | 0.281392E+09 | 11126.98 | 57.89 | 0.876800E+09 | 0.00 | 0.115819E+10 | 0.24 | 3.12 | 0.00 | 0.00 | ||
Maximum of Months | 0.216832E+12 | 209228.33 | 744.00 | 0.734873E+12 | 0.00 | 0.951705E+12 | 3.30 | 4.21 | 0.00 | 0.00 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.473220E+12 | 0.00 | 744.00 | 575877.88 | 31-JAN-04:03 | 0.00 | 50.30 | 60.00 | 4.34 | 0.00 | 0.28 | 0.92 | 31-JAN-04:03 |
February | 0.327750E+12 | 0.00 | 672.00 | 605139.15 | 02-FEB-06:00 | 0.00 | 50.86 | 60.00 | 3.32 | 0.00 | 0.22 | 0.97 | 02-FEB-06:00 |
March | 0.117255E+12 | 0.00 | 741.15 | 223621.05 | 05-MAR-19:02 | 0.00 | 49.91 | 59.96 | 1.09 | 0.00 | 0.07 | 0.36 | 05-MAR-19:02 |
April | 0.503283E+11 | 0.00 | 683.86 | 180687.16 | 03-APR-08:62 | 0.00 | 48.71 | 59.30 | 0.49 | 0.00 | 0.03 | 0.29 | 03-APR-08:62 |
May | 0.236532E+11 | 0.00 | 686.70 | 118136.20 | 02-MAY-18:04 | 0.00 | 43.54 | 58.69 | 0.15 | 0.00 | 0.01 | 0.19 | 02-MAY-18:04 |
June | 0.154863E+11 | 0.00 | 535.03 | 107813.65 | 05-JUN-15:05 | 0.00 | 41.79 | 55.12 | 0.09 | 0.00 | 0.01 | 0.17 | 05-JUN-15:05 |
July | 0.560437E+10 | 0.00 | 500.73 | 80263.78 | 10-JUL-15:06 | 0.00 | 40.90 | 53.72 | 0.03 | 0.00 | 0.00 | 0.13 | 10-JUL-15:06 |
August | 0.815369E+10 | 0.00 | 547.15 | 79717.67 | 06-AUG-08:04 | 0.00 | 40.93 | 54.92 | 0.04 | 0.00 | 0.00 | 0.13 | 06-AUG-08:04 |
September | 0.213430E+11 | 0.00 | 584.17 | 124820.33 | 30-SEP-15:03 | 0.00 | 44.42 | 56.63 | 0.16 | 0.00 | 0.01 | 0.20 | 30-SEP-15:03 |
October | 0.366739E+11 | 0.00 | 704.34 | 124647.75 | 30-OCT-08:05 | 0.00 | 50.33 | 59.40 | 0.38 | 0.00 | 0.02 | 0.20 | 30-OCT-08:05 |
November | 0.160207E+12 | 0.00 | 711.37 | 551729.04 | 26-NOV-07:00 | 0.00 | 49.71 | 59.81 | 1.52 | 0.00 | 0.10 | 0.88 | 26-NOV-07:00 |
December | 0.272734E+12 | 0.00 | 744.00 | 291899.84 | 09-DEC-09:04 | 0.00 | 50.12 | 60.00 | 2.50 | 0.00 | 0.16 | 0.47 | 09-DEC-09:04 |
Annual Sum or Average | 0.151241E+13 | 7854.50 | 46.77 | 58.12 | 1.16 | 0.00 | 0.08 | ||||||
Minimum of Months | 0.560437E+10 | 0.00 | 500.73 | 79717.67 | 0.00 | 40.90 | 53.72 | 0.03 | 0.00 | 0.00 | 0.13 | ||
Maximum of Months | 0.473220E+12 | 0.00 | 744.00 | 605139.15 | 0.00 | 50.86 | 60.00 | 4.34 | 0.00 | 0.28 | 0.97 |
Report: DXReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 5104448.38 | 0.00 | 1.12 | 5104448.38 | 0.00 | 0.00 | 0.00 | 0.00 | 16668.49 | 12-JAN-16:01 | 16668.49 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.101381E+09 | 0.00 | 16.52 | 0.100688E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17231.36 | 25-FEB-16:01 | 17231.36 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.343389E+09 | 0.00 | 69.84 | 0.261539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17233.49 | 25-MAR-15:01 | 17233.49 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.204048E+10 | 0.00 | 240.13 | 0.128894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17614.27 | 16-APR-08:61 | 17229.92 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.344574E+10 | 0.00 | 471.10 | 0.172318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18082.00 | 29-MAY-08:61 | 17228.67 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.645677E+10 | 0.00 | 571.28 | 0.314620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19525.22 | 26-JUN-08:61 | 15268.38 | 15-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.833058E+10 | 0.00 | 675.27 | 0.396238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19300.13 | 20-JUL-08:62 | 15376.65 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.732889E+10 | 0.00 | 672.24 | 0.330004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20805.08 | 03-AUG-08:61 | 15346.12 | 30-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.424543E+10 | 0.00 | 464.09 | 0.218719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18334.18 | 11-SEP-08:61 | 17230.20 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.983513E+09 | 0.00 | 176.20 | 0.657535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17231.95 | 19-OCT-15:01 | 17231.95 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.183221E+09 | 0.00 | 41.36 | 0.123773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17224.84 | 04-NOV-15:01 | 17224.84 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 8844247.89 | 0.00 | 1.78 | 8844247.89 | 0.00 | 0.00 | 0.00 | 0.00 | 16321.32 | 01-DEC-16:01 | 16321.32 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.334733E+11 | 3400.93 | 0.167654E+11 | ||||||||||||
Minimum of Months | 5104448.38 | 0.00 | 1.12 | 5104448.38 | 0.00 | 0.00 | 0.00 | 0.00 | 16321.32 | 15268.38 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.833058E+10 | 0.00 | 675.27 | 0.396238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20805.08 | 17233.49 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 492586.40 | 0.00 | 0.10 | 492586.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1945.57 | 12-JAN-16:03 | 1945.57 | 12-JAN-16:03 | 0.00 | 0.00 | 0.00 |
February | 28979322.97 | 0.00 | 7.26 | 28696564.76 | 0.00 | 0.00 | 0.00 | 0.00 | 16527.91 | 24-FEB-16:01 | 16527.91 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.134664E+09 | 0.00 | 36.00 | 99729849.54 | 0.00 | 0.00 | 0.00 | 0.00 | 16960.77 | 25-MAR-15:01 | 16960.77 | 25-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.127725E+10 | 0.00 | 176.89 | 0.781179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18000.53 | 16-APR-21:11 | 17245.38 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.226741E+10 | 0.00 | 369.59 | 0.984922E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19768.32 | 21-MAY-19:01 | 19768.32 | 21-MAY-19:01 | 0.00 | 0.00 | 0.00 |
June | 0.495518E+10 | 0.00 | 440.56 | 0.232954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21641.92 | 26-JUN-08:11 | 16167.38 | 23-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.575495E+10 | 0.00 | 478.67 | 0.256560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20256.98 | 20-JUL-08:11 | 15666.38 | 23-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.477314E+10 | 0.00 | 480.51 | 0.191894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22901.92 | 03-AUG-08:11 | 15442.59 | 16-AUG-21:01 | 0.00 | 0.00 | 0.00 |
September | 0.257743E+10 | 0.00 | 335.64 | 0.117277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18495.84 | 11-SEP-08:11 | 16955.18 | 24-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.348042E+09 | 0.00 | 82.41 | 0.226974E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16960.43 | 19-OCT-15:01 | 16960.43 | 19-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 61664849.53 | 0.00 | 15.09 | 40477133.42 | 0.00 | 0.00 | 0.00 | 0.00 | 16951.28 | 04-NOV-15:01 | 16951.28 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 849739.22 | 0.00 | 0.20 | 849739.22 | 0.00 | 0.00 | 0.00 | 0.00 | 2330.25 | 01-DEC-16:03 | 2330.25 | 01-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221800E+11 | 2422.92 | 0.101502E+11 | ||||||||||||
Minimum of Months | 492586.40 | 0.00 | 0.10 | 492586.40 | 0.00 | 0.00 | 0.00 | 0.00 | 1945.57 | 1945.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.575495E+10 | 0.00 | 480.51 | 0.256560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22901.92 | 19768.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.296122E+10 | 0.00 | 98.79 | 0.280351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31173.13 | 24-MAR-13:00 | 31173.13 | 24-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.101701E+11 | 0.00 | 231.57 | 0.562941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43372.66 | 15-APR-12:40 | 37339.33 | 15-APR-12:50 | 0.00 | 0.00 | 0.00 |
May | 0.209693E+11 | 0.00 | 570.22 | 0.890136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27887.25 | 31-MAY-19:05 | 18440.97 | 06-MAY-17:30 | 0.00 | 0.00 | 0.00 |
June | 0.321609E+11 | 0.00 | 637.31 | 0.124853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31671.88 | 26-JUN-17:25 | 19557.54 | 26-JUN-19:10 | 0.00 | 0.00 | 0.00 |
July | 0.402609E+11 | 0.00 | 727.48 | 0.156579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31384.47 | 26-JUL-20:12 | 17512.21 | 02-JUL-19:10 | 0.00 | 0.00 | 0.00 |
August | 0.414990E+11 | 0.00 | 730.99 | 0.173013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 37494.07 | 22-AUG-13:00 | 29302.02 | 29-AUG-13:15 | 0.00 | 0.00 | 0.00 |
September | 0.335532E+11 | 0.00 | 574.00 | 0.194733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48560.12 | 06-SEP-14:00 | 43318.35 | 07-SEP-11:40 | 0.00 | 0.00 | 0.00 |
October | 0.188283E+11 | 0.00 | 399.23 | 0.161569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53232.95 | 20-OCT-12:30 | 53232.95 | 20-OCT-12:30 | 0.00 | 0.00 | 0.00 |
November | 0.564561E+10 | 0.00 | 141.53 | 0.467299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51567.38 | 04-NOV-12:30 | 51567.38 | 04-NOV-12:30 | 0.00 | 0.00 | 0.00 |
December | 38064791.04 | 0.00 | 2.50 | 38064791.04 | 0.00 | 0.00 | 0.00 | 0.00 | 6443.50 | 07-DEC-14:40 | 6443.50 | 07-DEC-14:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206086E+12 | 4113.63 | 0.103120E+12 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.414990E+11 | 0.00 | 730.99 | 0.194733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53232.95 | 53232.95 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 44322479.05 | 0.00 | 3.61 | 44322479.05 | 0.00 | 0.00 | 0.00 | 0.00 | 45811.61 | 01-JAN-09:02 | 45811.61 | 01-JAN-09:02 | 0.00 | 0.00 | 0.00 |
February | 0.248619E+09 | 0.00 | 27.59 | 0.201234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82599.32 | 26-FEB-09:02 | 82599.32 | 26-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.368309E+10 | 0.00 | 149.75 | 0.223702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86438.08 | 25-MAR-18:02 | 86438.08 | 25-MAR-18:02 | 0.00 | 0.00 | 0.00 |
April | 0.127253E+11 | 0.00 | 293.86 | 0.808855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96347.72 | 16-APR-21:11 | 89813.20 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.310163E+11 | 0.00 | 449.94 | 0.174808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97278.56 | 29-MAY-08:11 | 87533.38 | 20-MAY-15:01 | 0.00 | 0.00 | 0.00 |
June | 0.463514E+11 | 0.00 | 457.70 | 0.274173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116715.87 | 26-JUN-08:11 | 82839.85 | 19-JUN-21:11 | 0.00 | 0.00 | 0.00 |
July | 0.504945E+11 | 0.00 | 432.73 | 0.294598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110476.59 | 20-JUL-08:11 | 83768.29 | 18-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.460792E+11 | 0.00 | 432.49 | 0.257678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125350.95 | 03-AUG-08:11 | 81479.50 | 22-AUG-18:01 | 0.00 | 0.00 | 0.00 |
September | 0.289934E+11 | 0.00 | 434.57 | 0.166300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99702.37 | 11-SEP-21:11 | 89607.17 | 19-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.954100E+10 | 0.00 | 332.33 | 0.598054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85382.82 | 12-OCT-18:03 | 85382.82 | 12-OCT-18:03 | 0.00 | 0.00 | 0.00 |
November | 0.421531E+10 | 0.00 | 150.99 | 0.183407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83920.98 | 04-NOV-18:01 | 83920.98 | 04-NOV-18:01 | 0.00 | 0.00 | 0.00 |
December | 59800660.92 | 0.00 | 4.06 | 59800660.92 | 0.00 | 0.00 | 0.00 | 0.00 | 53531.83 | 03-DEC-09:02 | 53531.83 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233452E+12 | 3169.61 | 0.135201E+12 | ||||||||||||
Minimum of Months | 44322479.05 | 0.00 | 3.61 | 44322479.05 | 0.00 | 0.00 | 0.00 | 0.00 | 45811.61 | 45811.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.504945E+11 | 0.00 | 457.70 | 0.294598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125350.95 | 89813.20 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 805101.70 | 0.00 | 0.47 | 805101.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.44 | 12-JAN-09:03 | 2334.44 | 12-JAN-09:03 | 0.00 | 0.00 | 0.00 |
February | 60781668.97 | 0.00 | 12.30 | 47707487.27 | 0.00 | 0.00 | 0.00 | 0.00 | 15117.77 | 24-FEB-09:02 | 15117.77 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.311421E+09 | 0.00 | 80.87 | 0.206314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15476.00 | 24-MAR-15:01 | 15476.00 | 24-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.167508E+10 | 0.00 | 236.61 | 0.947291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15473.95 | 30-APR-18:01 | 15473.95 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.368324E+10 | 0.00 | 521.74 | 0.179784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16173.48 | 11-MAY-15:01 | 15251.77 | 21-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.653439E+10 | 0.00 | 601.14 | 0.323793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16900.82 | 14-JUN-08:62 | 13773.10 | 11-JUN-08:61 | 0.00 | 0.00 | 0.00 |
July | 0.804552E+10 | 0.00 | 697.66 | 0.379147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17367.80 | 20-JUL-08:62 | 13807.27 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 |
August | 0.699287E+10 | 0.00 | 685.49 | 0.308336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18229.81 | 31-AUG-08:62 | 13824.35 | 05-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.423636E+10 | 0.00 | 484.37 | 0.215209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15807.03 | 10-SEP-08:62 | 15381.72 | 30-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.792166E+09 | 0.00 | 185.72 | 0.476094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15476.77 | 24-OCT-15:01 | 15476.77 | 24-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.140439E+09 | 0.00 | 45.72 | 86436775.14 | 0.00 | 0.00 | 0.00 | 0.00 | 15471.19 | 04-NOV-15:01 | 15471.19 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 12872483.48 | 0.00 | 3.71 | 12426513.88 | 0.00 | 0.00 | 0.00 | 0.00 | 10737.29 | 03-DEC-09:02 | 10737.29 | 03-DEC-09:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324859E+11 | 3555.80 | 0.158398E+11 | ||||||||||||
Minimum of Months | 805101.70 | 0.00 | 0.47 | 805101.70 | 0.00 | 0.00 | 0.00 | 0.00 | 2334.44 | 2334.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.804552E+10 | 0.00 | 697.66 | 0.379147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18229.81 | 15476.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 379129.35 | 0.00 | 0.13 | 379129.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1502.34 | 11-JAN-09:05 | 1502.34 | 11-JAN-09:05 | 0.00 | 0.00 | 0.00 |
February | 11576648.43 | 0.00 | 4.05 | 9826287.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14552.72 | 24-FEB-09:02 | 14552.72 | 24-FEB-09:02 | 0.00 | 0.00 | 0.00 |
March | 0.129574E+09 | 0.00 | 39.87 | 80185790.67 | 0.00 | 0.00 | 0.00 | 0.00 | 12806.30 | 19-MAR-15:01 | 12806.30 | 19-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.105398E+10 | 0.00 | 160.16 | 0.595416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17812.57 | 18-APR-08:11 | 15385.69 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.275404E+10 | 0.00 | 406.46 | 0.134969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18985.31 | 31-MAY-08:11 | 15310.29 | 31-MAY-08:11 | 0.00 | 0.00 | 0.00 |
June | 0.519650E+10 | 0.00 | 465.12 | 0.263054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21013.55 | 26-JUN-08:11 | 16200.16 | 20-JUN-08:11 | 0.00 | 0.00 | 0.00 |
July | 0.584531E+10 | 0.00 | 492.26 | 0.278697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20164.20 | 02-JUL-08:11 | 15889.03 | 18-JUL-08:11 | 0.00 | 0.00 | 0.00 |
August | 0.482116E+10 | 0.00 | 492.87 | 0.212100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21726.76 | 03-AUG-08:11 | 15811.33 | 09-AUG-08:11 | 0.00 | 0.00 | 0.00 |
September | 0.273397E+10 | 0.00 | 348.69 | 0.132065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18125.18 | 11-SEP-08:11 | 15405.69 | 06-SEP-08:11 | 0.00 | 0.00 | 0.00 |
October | 0.222797E+09 | 0.00 | 67.13 | 0.113796E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14426.69 | 02-OCT-15:01 | 12931.20 | 21-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 19740974.84 | 0.00 | 8.93 | 8565323.79 | 0.00 | 0.00 | 0.00 | 0.00 | 10176.51 | 04-NOV-08:62 | 10126.15 | 04-NOV-08:62 | 0.00 | 0.00 | 0.00 |
December | 785241.07 | 0.00 | 0.19 | 785241.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2174.04 | 05-DEC-09:03 | 2174.04 | 05-DEC-09:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227898E+11 | 2485.84 | 0.110178E+11 | ||||||||||||
Minimum of Months | 379129.35 | 0.00 | 0.13 | 379129.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1502.34 | 1502.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.584531E+10 | 0.00 | 492.87 | 0.278697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21726.76 | 16200.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 1130778.06 | 0.00 | 0.90 | 1125171.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4301.13 | 12-JAN-16:01 | 4301.13 | 12-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 26673673.24 | 0.00 | 14.64 | 26509574.67 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.43 | 25-FEB-16:01 | 4482.43 | 25-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 83780923.13 | 0.00 | 59.94 | 64471116.87 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.37 | 24-MAR-18:01 | 4482.37 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.583876E+09 | 0.00 | 231.58 | 0.387187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4622.70 | 16-APR-08:61 | 4482.00 | 09-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.102864E+10 | 0.00 | 473.85 | 0.548511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4752.21 | 29-MAY-08:61 | 4481.26 | 06-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.193579E+10 | 0.00 | 581.00 | 0.103512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5106.19 | 26-JUN-08:61 | 3931.65 | 04-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.249308E+10 | 0.00 | 689.91 | 0.130566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5180.53 | 20-JUL-08:62 | 3996.74 | 21-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.217616E+10 | 0.00 | 680.08 | 0.107317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5468.89 | 03-AUG-08:61 | 3992.90 | 26-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.123488E+10 | 0.00 | 452.58 | 0.701432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4852.74 | 11-SEP-08:61 | 4481.62 | 20-SEP-18:01 | 0.00 | 0.00 | 0.00 |
October | 0.258914E+09 | 0.00 | 148.19 | 0.180884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4482.34 | 29-OCT-15:02 | 4482.34 | 29-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 47323786.61 | 0.00 | 28.44 | 34816191.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4480.55 | 04-NOV-15:01 | 4480.55 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 1629422.24 | 0.00 | 0.89 | 1610723.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4210.60 | 01-DEC-16:01 | 4210.60 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.987187E+10 | 3361.99 | 0.536050E+10 | ||||||||||||
Minimum of Months | 1130778.06 | 0.00 | 0.89 | 1125171.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4210.60 | 3931.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.249308E+10 | 0.00 | 689.91 | 0.130566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5468.89 | 4482.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 72573.70 | 0.00 | 0.05 | 72573.70 | 0.00 | 0.00 | 0.00 | 0.00 | 666.22 | 13-JAN-16:04 | 666.22 | 13-JAN-16:04 | 0.00 | 0.00 | 0.00 |
February | 5208338.60 | 0.00 | 6.20 | 5146758.64 | 0.00 | 0.00 | 0.00 | 0.00 | 4206.97 | 24-FEB-16:01 | 4206.97 | 24-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 27943110.44 | 0.00 | 30.47 | 20601835.93 | 0.00 | 0.00 | 0.00 | 0.00 | 4409.06 | 24-MAR-18:01 | 4409.06 | 24-MAR-18:01 | 0.00 | 0.00 | 0.00 |
April | 0.376287E+09 | 0.00 | 171.11 | 0.241443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4769.29 | 16-APR-21:11 | 4511.74 | 29-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.724683E+09 | 0.00 | 382.06 | 0.347326E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5459.73 | 20-MAY-18:01 | 5459.73 | 20-MAY-18:01 | 0.00 | 0.00 | 0.00 |
June | 0.157252E+10 | 0.00 | 451.82 | 0.830455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5785.04 | 26-JUN-08:11 | 4549.33 | 21-JUN-20:21 | 0.00 | 0.00 | 0.00 |
July | 0.185883E+10 | 0.00 | 491.96 | 0.948259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5515.66 | 06-JUL-21:11 | 4519.02 | 23-JUL-21:11 | 0.00 | 0.00 | 0.00 |
August | 0.154583E+10 | 0.00 | 500.52 | 0.702919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6138.15 | 03-AUG-08:11 | 4327.03 | 07-AUG-21:11 | 0.00 | 0.00 | 0.00 |
September | 0.798955E+09 | 0.00 | 337.27 | 0.399966E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4951.03 | 11-SEP-21:11 | 4817.71 | 19-SEP-17:01 | 0.00 | 0.00 | 0.00 |
October | 84641743.51 | 0.00 | 66.14 | 55154659.18 | 0.00 | 0.00 | 0.00 | 0.00 | 4311.80 | 19-OCT-16:32 | 4311.80 | 19-OCT-16:32 | 0.00 | 0.00 | 0.00 |
November | 14901975.67 | 0.00 | 7.29 | 9822346.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4388.39 | 04-NOV-15:01 | 4388.39 | 04-NOV-15:01 | 0.00 | 0.00 | 0.00 |
December | 129735.95 | 0.00 | 0.08 | 129735.95 | 0.00 | 0.00 | 0.00 | 0.00 | 635.67 | 02-DEC-16:03 | 635.67 | 02-DEC-16:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701001E+10 | 2444.95 | 0.356130E+10 | ||||||||||||
Minimum of Months | 72573.70 | 0.00 | 0.05 | 72573.70 | 0.00 | 0.00 | 0.00 | 0.00 | 635.67 | 635.67 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.185883E+10 | 0.00 | 500.52 | 0.948259E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6138.15 | 5459.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.486381E+09 | 0.00 | 55.88 | 0.485438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17333.41 | 13-JAN-16:01 | 17333.41 | 13-JAN-16:01 | 0.00 | 0.00 | 0.00 |
February | 0.830773E+09 | 0.00 | 92.83 | 0.698670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17332.98 | 19-FEB-16:01 | 17332.98 | 19-FEB-16:01 | 0.00 | 0.00 | 0.00 |
March | 0.137825E+10 | 0.00 | 188.53 | 0.101121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17331.92 | 27-MAR-15:01 | 17331.92 | 27-MAR-15:01 | 0.00 | 0.00 | 0.00 |
April | 0.313322E+10 | 0.00 | 295.93 | 0.197863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17789.47 | 16-APR-08:61 | 17331.91 | 30-APR-18:01 | 0.00 | 0.00 | 0.00 |
May | 0.518806E+10 | 0.00 | 540.87 | 0.248476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18076.59 | 11-MAY-18:02 | 16912.24 | 21-MAY-18:02 | 0.00 | 0.00 | 0.00 |
June | 0.870715E+10 | 0.00 | 604.45 | 0.438090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20621.39 | 26-JUN-08:61 | 15423.46 | 07-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.111095E+11 | 0.00 | 681.76 | 0.546647E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20475.83 | 20-JUL-08:62 | 15480.73 | 12-JUL-18:01 | 0.00 | 0.00 | 0.00 |
August | 0.110055E+11 | 0.00 | 678.13 | 0.555002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21943.87 | 03-AUG-08:61 | 15432.83 | 02-AUG-18:02 | 0.00 | 0.00 | 0.00 |
September | 0.783920E+10 | 0.00 | 544.87 | 0.490331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18952.02 | 11-SEP-08:61 | 17324.84 | 30-SEP-15:01 | 0.00 | 0.00 | 0.00 |
October | 0.397872E+10 | 0.00 | 373.99 | 0.304964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17332.38 | 27-OCT-15:01 | 17332.38 | 27-OCT-15:01 | 0.00 | 0.00 | 0.00 |
November | 0.138695E+10 | 0.00 | 161.32 | 0.105684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17319.75 | 12-NOV-16:01 | 17319.75 | 12-NOV-16:01 | 0.00 | 0.00 | 0.00 |
December | 0.964015E+09 | 0.00 | 87.41 | 0.931285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17321.50 | 01-DEC-16:01 | 17321.50 | 01-DEC-16:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560077E+11 | 4305.97 | 0.319972E+11 | ||||||||||||
Minimum of Months | 0.486381E+09 | 0.00 | 55.88 | 0.485438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17319.75 | 15423.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.111095E+11 | 0.00 | 681.76 | 0.555002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21943.87 | 17333.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.450568E+10 | 0.00 | 30.83 | 0.450568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92987.48 | 19-MAR-16:00 | 92987.48 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.574084E+11 | 0.00 | 135.00 | 0.442320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 290833.28 | 16-APR-20:10 | 203608.72 | 15-APR-17:30 | 0.00 | 0.00 | 0.00 |
May | 0.143673E+12 | 0.00 | 405.58 | 0.106463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 300518.90 | 30-MAY-19:40 | 208376.84 | 31-MAY-18:10 | 0.00 | 0.00 | 0.00 |
June | 0.383642E+12 | 0.00 | 560.17 | 0.246001E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 384843.15 | 14-JUN-17:10 | 230210.66 | 26-JUN-18:10 | 0.00 | 0.00 | 0.00 |
July | 0.559000E+12 | 0.00 | 709.00 | 0.315819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 532290.37 | 03-JUL-21:50 | 227336.23 | 03-JUL-18:10 | 0.00 | 0.00 | 0.00 |
August | 0.480463E+12 | 0.00 | 669.83 | 0.280121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 492879.81 | 04-AUG-06:00 | 229068.77 | 04-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.184311E+12 | 0.00 | 402.83 | 0.155756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317972.96 | 11-SEP-19:20 | 224129.83 | 07-SEP-18:10 | 0.00 | 0.00 | 0.00 |
October | 0.147997E+11 | 0.00 | 83.67 | 0.147997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160434.60 | 20-OCT-15:10 | 160434.60 | 20-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.155089E+10 | 0.00 | 30.00 | 0.155089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42462.44 | 03-NOV-14:20 | 42462.44 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182935E+13 | 3026.92 | 0.116925E+13 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.559000E+12 | 0.00 | 709.00 | 0.315819E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 532290.37 | 230210.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 |
March | 0.213241E+09 | 0.00 | 17.33 | 0.213241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8513.13 | 19-MAR-16:00 | 8513.13 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.333047E+10 | 0.00 | 81.50 | 0.262331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28809.21 | 18-APR-17:00 | 18717.17 | 15-APR-15:01 | 0.00 | 0.00 | 0.00 |
May | 0.752309E+10 | 0.00 | 247.83 | 0.567247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29469.14 | 29-MAY-15:01 | 18622.71 | 31-MAY-15:02 | 0.00 | 0.00 | 0.00 |
June | 0.244977E+11 | 0.00 | 410.83 | 0.158155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 40676.53 | 26-JUN-08:61 | 20098.95 | 11-JUN-15:02 | 0.00 | 0.00 | 0.00 |
July | 0.373240E+11 | 0.00 | 538.67 | 0.209604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 42550.34 | 17-JUL-18:03 | 19030.82 | 06-JUL-18:02 | 0.00 | 0.00 | 0.00 |
August | 0.304210E+11 | 0.00 | 494.67 | 0.175604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47404.58 | 03-AUG-08:61 | 20393.99 | 04-AUG-15:02 | 0.00 | 0.00 | 0.00 |
September | 0.109111E+11 | 0.00 | 280.33 | 0.939871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29509.45 | 11-SEP-08:11 | 19474.49 | 06-SEP-15:02 | 0.00 | 0.00 | 0.00 |
October | 0.653299E+09 | 0.00 | 41.00 | 0.653299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15306.28 | 20-OCT-15:02 | 15306.28 | 20-OCT-15:02 | 0.00 | 0.00 | 0.00 |
November | 24313945.23 | 0.00 | 7.00 | 24313945.23 | 0.00 | 0.00 | 0.00 | 0.00 | 2177.41 | 03-NOV-15:03 | 2177.41 | 03-NOV-15:03 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114898E+12 | 2119.17 | 0.729216E+11 | ||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.373240E+11 | 0.00 | 538.67 | 0.209604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47404.58 | 20393.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 863.80 | 591.77 | 272.03 | 700.67 | 955.40 | 0.00 | 0.00 | 744.00 |
February | 931.56 | 632.07 | 299.49 | 764.74 | 762.39 | 0.00 | 0.00 | 672.00 |
March | 798.14 | 417.95 | 380.19 | 621.91 | 565.22 | 0.00 | 0.00 | 744.00 |
April | 711.24 | 325.93 | 385.30 | 543.37 | 403.64 | 0.00 | 0.00 | 720.00 |
May | 606.52 | 169.60 | 436.93 | 487.78 | 212.44 | 0.00 | 0.00 | 744.00 |
June | 578.99 | 115.55 | 463.44 | 535.21 | 128.46 | 0.00 | 0.00 | 720.00 |
July | 614.42 | 153.58 | 460.84 | 590.73 | 101.70 | 0.00 | 0.00 | 744.00 |
August | 680.89 | 235.73 | 445.16 | 688.54 | 129.43 | 0.00 | 0.00 | 744.00 |
September | 822.35 | 424.41 | 397.94 | 822.84 | 249.82 | 0.00 | 0.00 | 720.00 |
October | 886.38 | 558.94 | 327.44 | 854.31 | 413.67 | 0.00 | 0.00 | 744.00 |
November | 663.13 | 415.16 | 247.97 | 559.92 | 621.00 | 0.00 | 0.00 | 720.00 |
December | 705.87 | 534.51 | 171.36 | 626.39 | 897.59 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 737.51 | 379.87 | 357.64 | 649.13 | 451.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 578.99 | 115.55 | 171.36 | 487.78 | 101.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 931.56 | 632.07 | 463.44 | 854.31 | 955.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2432.41 | 1666.38 | 766.03 | 1957.88 | 2716.00 | 0.00 | 0.00 | 744.00 |
February | 2623.21 | 1779.87 | 843.34 | 2133.63 | 2197.95 | 0.00 | 0.00 | 672.00 |
March | 2247.50 | 1176.92 | 1070.58 | 1726.96 | 1647.83 | 0.00 | 0.00 | 744.00 |
April | 2002.79 | 917.81 | 1084.99 | 1505.44 | 1207.10 | 0.00 | 0.00 | 720.00 |
May | 1707.93 | 477.58 | 1230.35 | 1331.45 | 671.78 | 0.00 | 0.00 | 744.00 |
June | 1630.40 | 325.37 | 1305.02 | 1466.67 | 419.88 | 0.00 | 0.00 | 720.00 |
July | 1730.18 | 432.47 | 1297.71 | 1624.87 | 334.81 | 0.00 | 0.00 | 744.00 |
August | 1917.35 | 663.80 | 1253.55 | 1904.15 | 422.67 | 0.00 | 0.00 | 744.00 |
September | 2315.69 | 1195.11 | 1120.58 | 2286.11 | 775.47 | 0.00 | 0.00 | 720.00 |
October | 2495.99 | 1573.95 | 922.04 | 2375.86 | 1250.31 | 0.00 | 0.00 | 744.00 |
November | 1867.32 | 1169.06 | 698.26 | 1556.75 | 1804.02 | 0.00 | 0.00 | 720.00 |
December | 1987.68 | 1505.14 | 482.54 | 1748.89 | 2556.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2076.78 | 1069.70 | 1007.08 | 1799.90 | 1329.69 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1630.40 | 325.37 | 482.54 | 1331.45 | 334.81 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2623.21 | 1779.87 | 1305.02 | 2375.86 | 2716.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3159.84 | 2164.73 | 995.12 | 2577.74 | 3670.53 | 0.00 | 0.00 | 744.00 |
February | 3407.69 | 2312.15 | 1095.55 | 2822.43 | 2958.05 | 0.00 | 0.00 | 672.00 |
March | 2919.63 | 1528.89 | 1390.74 | 2279.05 | 2250.45 | 0.00 | 0.00 | 744.00 |
April | 2601.74 | 1192.28 | 1409.46 | 1995.44 | 1652.47 | 0.00 | 0.00 | 720.00 |
May | 2218.70 | 620.40 | 1598.30 | 1759.59 | 913.65 | 0.00 | 0.00 | 744.00 |
June | 2117.98 | 422.68 | 1695.30 | 1956.43 | 565.69 | 0.00 | 0.00 | 720.00 |
July | 2247.60 | 561.80 | 1685.80 | 2172.38 | 443.42 | 0.00 | 0.00 | 744.00 |
August | 2490.75 | 862.31 | 1628.44 | 2541.43 | 557.32 | 0.00 | 0.00 | 744.00 |
September | 3008.21 | 1552.52 | 1455.69 | 3037.60 | 1040.12 | 0.00 | 0.00 | 720.00 |
October | 3242.43 | 2044.65 | 1197.78 | 3132.30 | 1696.50 | 0.00 | 0.00 | 744.00 |
November | 2425.76 | 1518.67 | 907.08 | 2042.78 | 2469.36 | 0.00 | 0.00 | 720.00 |
December | 2582.11 | 1955.26 | 626.85 | 2302.92 | 3477.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2697.86 | 1389.60 | 1308.26 | 2382.80 | 1802.62 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 2117.98 | 422.68 | 626.85 | 1759.59 | 443.42 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3407.69 | 2312.15 | 1695.30 | 3132.30 | 3670.53 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 137.89 | 197.67 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 149.43 | 160.06 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 123.15 | 115.20 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 107.89 | 81.75 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 95.25 | 42.68 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 106.18 | 24.40 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 117.09 | 18.52 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 137.22 | 23.60 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 164.88 | 47.48 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 170.17 | 81.83 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 111.19 | 125.91 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 124.59 | 182.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 128.64 | 91.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 95.25 | 18.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 170.17 | 197.67 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 32.23 | 425.42 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 77.67 | 339.04 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 110.72 | 220.64 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 243.39 | 148.64 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 274.45 | 76.97 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 368.14 | 44.67 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 409.70 | 34.20 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 357.38 | 43.64 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 259.71 | 87.89 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 130.16 | 158.43 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 45.53 | 259.66 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 27.84 | 381.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 195.33 | 184.30 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 27.84 | 34.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 409.70 | 425.42 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.01 | 242.01 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.55 | 195.27 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 10.44 | 124.97 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.80 | 82.42 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 56.15 | 40.57 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 85.98 | 23.92 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 84.59 | 19.73 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 74.13 | 24.82 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 45.29 | 49.09 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.98 | 87.24 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 3.05 | 144.74 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 211.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 33.53 | 103.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 19.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 85.98 | 242.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 108.95 | 44.31 | 64.64 | 33.60 | 421.37 | 0.00 | 0.00 | 744.00 |
February | 158.99 | 78.28 | 80.72 | 80.37 | 334.25 | 0.00 | 0.00 | 672.00 |
March | 189.75 | 70.58 | 119.17 | 114.43 | 218.00 | 0.00 | 0.00 | 744.00 |
April | 277.50 | 137.33 | 140.17 | 245.24 | 148.17 | 0.00 | 0.00 | 720.00 |
May | 278.01 | 111.30 | 166.72 | 272.98 | 78.07 | 0.00 | 0.00 | 744.00 |
June | 325.21 | 140.59 | 184.62 | 364.03 | 47.28 | 0.00 | 0.00 | 720.00 |
July | 349.30 | 165.69 | 183.61 | 403.30 | 38.69 | 0.00 | 0.00 | 744.00 |
August | 305.02 | 139.57 | 165.45 | 353.30 | 47.63 | 0.00 | 0.00 | 744.00 |
September | 247.53 | 117.31 | 130.23 | 260.87 | 89.31 | 0.00 | 0.00 | 720.00 |
October | 173.50 | 77.51 | 95.99 | 134.92 | 156.03 | 0.00 | 0.00 | 744.00 |
November | 103.52 | 38.44 | 65.08 | 48.04 | 256.56 | 0.00 | 0.00 | 720.00 |
December | 79.69 | 37.72 | 41.98 | 29.55 | 376.82 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.65 | 96.57 | 120.07 | 195.62 | 183.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.69 | 37.72 | 41.98 | 29.55 | 38.69 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.30 | 165.69 | 184.62 | 403.30 | 421.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 136.33 | 93.39 | 42.93 | 112.79 | 142.77 | 0.00 | 0.00 | 744.00 |
February | 147.02 | 99.75 | 47.27 | 118.77 | 129.70 | 0.00 | 0.00 | 672.00 |
March | 125.96 | 65.96 | 60.00 | 94.03 | 100.53 | 0.00 | 0.00 | 744.00 |
April | 112.25 | 51.44 | 60.81 | 78.80 | 86.58 | 0.00 | 0.00 | 720.00 |
May | 95.72 | 26.77 | 68.96 | 63.49 | 53.34 | 0.00 | 0.00 | 744.00 |
June | 91.38 | 18.24 | 73.14 | 71.55 | 36.20 | 0.00 | 0.00 | 720.00 |
July | 96.97 | 24.24 | 72.73 | 80.23 | 29.94 | 0.00 | 0.00 | 744.00 |
August | 107.46 | 37.20 | 70.26 | 96.93 | 35.90 | 0.00 | 0.00 | 744.00 |
September | 129.78 | 66.98 | 62.80 | 120.77 | 59.42 | 0.00 | 0.00 | 720.00 |
October | 139.89 | 88.21 | 51.68 | 124.78 | 90.37 | 0.00 | 0.00 | 744.00 |
November | 104.65 | 65.52 | 39.13 | 82.91 | 117.23 | 0.00 | 0.00 | 720.00 |
December | 111.40 | 84.36 | 27.04 | 99.85 | 136.27 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 116.39 | 59.95 | 56.44 | 95.29 | 84.59 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 91.38 | 18.24 | 27.04 | 63.49 | 29.94 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 147.02 | 99.75 | 73.14 | 124.78 | 142.77 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 21.86 | 0.00 | 21.86 | 0.00 | 199.63 | 0.00 | 0.00 | 744.00 |
February | 27.72 | 0.00 | 27.72 | 0.31 | 160.88 | 0.00 | 0.00 | 672.00 |
March | 41.55 | 0.00 | 41.55 | 7.91 | 103.05 | 0.00 | 0.00 | 744.00 |
April | 48.15 | 0.39 | 47.76 | 21.54 | 67.07 | 0.00 | 0.00 | 720.00 |
May | 62.60 | 2.37 | 60.24 | 47.17 | 32.33 | 0.00 | 0.00 | 744.00 |
June | 73.26 | 6.78 | 66.48 | 72.18 | 18.68 | 0.00 | 0.00 | 720.00 |
July | 68.71 | 4.73 | 63.98 | 71.94 | 14.70 | 0.00 | 0.00 | 744.00 |
August | 57.57 | 1.16 | 56.41 | 62.82 | 18.86 | 0.00 | 0.00 | 744.00 |
September | 44.06 | 0.04 | 44.02 | 37.92 | 39.10 | 0.00 | 0.00 | 720.00 |
October | 32.72 | 0.00 | 32.72 | 10.83 | 71.45 | 0.00 | 0.00 | 744.00 |
November | 22.89 | 0.00 | 22.89 | 2.17 | 120.49 | 0.00 | 0.00 | 720.00 |
December | 14.85 | 0.00 | 14.85 | 0.00 | 175.48 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 43.08 | 1.29 | 41.78 | 28.07 | 84.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 14.85 | 0.00 | 14.85 | 0.00 | 14.70 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 73.26 | 6.78 | 66.48 | 72.18 | 199.63 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 26.70 | 418.99 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 57.76 | 332.04 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 114.72 | 214.74 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 195.36 | 144.53 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 300.80 | 72.31 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 374.42 | 42.06 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 392.19 | 31.78 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 329.34 | 40.55 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 265.49 | 85.11 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 109.94 | 152.71 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 32.30 | 254.81 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 17.91 | 376.52 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 185.43 | 179.80 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 17.91 | 31.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 392.19 | 418.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.44 | 116.76 | 53.68 | 137.68 | 197.49 | 0.00 | 0.00 | 744.00 |
February | 183.81 | 124.72 | 59.09 | 149.13 | 159.41 | 0.00 | 0.00 | 672.00 |
March | 157.48 | 82.47 | 75.02 | 122.21 | 114.96 | 0.00 | 0.00 | 744.00 |
April | 140.34 | 64.31 | 76.03 | 107.39 | 80.94 | 0.00 | 0.00 | 720.00 |
May | 119.68 | 33.46 | 86.21 | 93.98 | 42.63 | 0.00 | 0.00 | 744.00 |
June | 114.24 | 22.80 | 91.44 | 105.36 | 24.17 | 0.00 | 0.00 | 720.00 |
July | 121.23 | 30.30 | 90.93 | 116.54 | 18.03 | 0.00 | 0.00 | 744.00 |
August | 134.35 | 46.51 | 87.84 | 136.84 | 23.18 | 0.00 | 0.00 | 744.00 |
September | 162.26 | 83.74 | 78.52 | 163.97 | 47.15 | 0.00 | 0.00 | 720.00 |
October | 174.90 | 110.29 | 64.61 | 169.60 | 81.47 | 0.00 | 0.00 | 744.00 |
November | 130.84 | 81.92 | 48.93 | 111.07 | 125.67 | 0.00 | 0.00 | 720.00 |
December | 139.28 | 105.47 | 33.81 | 124.52 | 181.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.52 | 74.95 | 70.57 | 128.09 | 91.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.24 | 22.80 | 33.81 | 93.98 | 18.03 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.81 | 124.72 | 91.44 | 169.60 | 197.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.33 | 0.00 | 27.33 | 0.00 | 241.94 | 0.00 | 0.00 | 744.00 |
February | 34.64 | 0.00 | 34.64 | 0.45 | 194.69 | 0.00 | 0.00 | 672.00 |
March | 51.93 | 0.00 | 51.93 | 10.04 | 125.20 | 0.00 | 0.00 | 744.00 |
April | 60.18 | 0.48 | 59.70 | 25.58 | 81.53 | 0.00 | 0.00 | 720.00 |
May | 78.24 | 2.96 | 75.29 | 55.36 | 40.23 | 0.00 | 0.00 | 744.00 |
June | 91.56 | 8.47 | 83.08 | 85.55 | 23.27 | 0.00 | 0.00 | 720.00 |
July | 85.88 | 5.91 | 79.96 | 84.77 | 18.46 | 0.00 | 0.00 | 744.00 |
August | 71.96 | 1.45 | 70.51 | 74.39 | 23.55 | 0.00 | 0.00 | 744.00 |
September | 55.07 | 0.05 | 55.02 | 44.57 | 48.41 | 0.00 | 0.00 | 720.00 |
October | 40.89 | 0.00 | 40.89 | 13.62 | 86.82 | 0.00 | 0.00 | 744.00 |
November | 28.61 | 0.00 | 28.61 | 2.97 | 144.52 | 0.00 | 0.00 | 720.00 |
December | 18.55 | 0.00 | 18.55 | 0.00 | 211.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.84 | 1.62 | 52.22 | 33.30 | 102.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.55 | 0.00 | 18.55 | 0.00 | 18.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.56 | 8.47 | 83.08 | 85.55 | 241.94 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.03 | 44.69 | 64.35 | 27.31 | 414.16 | 0.00 | 0.00 | 744.00 |
February | 145.18 | 63.90 | 81.28 | 59.23 | 325.90 | 0.00 | 0.00 | 672.00 |
March | 197.18 | 78.24 | 118.94 | 117.76 | 211.36 | 0.00 | 0.00 | 744.00 |
April | 240.65 | 104.89 | 135.76 | 197.45 | 143.53 | 0.00 | 0.00 | 720.00 |
May | 304.04 | 132.96 | 171.08 | 300.61 | 73.05 | 0.00 | 0.00 | 744.00 |
June | 334.11 | 145.53 | 188.59 | 371.33 | 44.09 | 0.00 | 0.00 | 720.00 |
July | 337.78 | 155.90 | 181.88 | 387.51 | 34.95 | 0.00 | 0.00 | 744.00 |
August | 284.80 | 122.73 | 162.07 | 327.06 | 43.31 | 0.00 | 0.00 | 744.00 |
September | 255.18 | 121.04 | 134.15 | 267.08 | 85.76 | 0.00 | 0.00 | 720.00 |
October | 161.59 | 67.26 | 94.33 | 114.42 | 149.58 | 0.00 | 0.00 | 744.00 |
November | 95.58 | 31.02 | 64.56 | 33.91 | 250.80 | 0.00 | 0.00 | 720.00 |
December | 73.77 | 31.59 | 42.18 | 18.37 | 371.22 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 211.90 | 91.77 | 120.13 | 185.85 | 178.29 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 73.77 | 31.02 | 42.18 | 18.37 | 34.95 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 337.78 | 155.90 | 188.59 | 387.51 | 414.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.61 | 0.00 | 34.61 | 0.00 | 319.91 | 0.00 | 0.00 | 744.00 |
February | 43.87 | 0.00 | 43.87 | 0.40 | 252.32 | 0.00 | 0.00 | 672.00 |
March | 65.76 | 0.00 | 65.76 | 12.52 | 165.18 | 0.00 | 0.00 | 744.00 |
April | 76.21 | 0.61 | 75.60 | 35.44 | 105.81 | 0.00 | 0.00 | 720.00 |
May | 99.09 | 3.74 | 95.34 | 79.34 | 49.43 | 0.00 | 0.00 | 744.00 |
June | 115.95 | 10.73 | 105.22 | 121.32 | 27.04 | 0.00 | 0.00 | 720.00 |
July | 108.76 | 7.49 | 101.27 | 122.21 | 19.91 | 0.00 | 0.00 | 744.00 |
August | 91.13 | 1.84 | 89.29 | 106.55 | 26.59 | 0.00 | 0.00 | 744.00 |
September | 69.74 | 0.06 | 69.68 | 63.31 | 59.77 | 0.00 | 0.00 | 720.00 |
October | 51.79 | 0.00 | 51.79 | 17.61 | 113.11 | 0.00 | 0.00 | 744.00 |
November | 36.23 | 0.00 | 36.23 | 3.56 | 193.06 | 0.00 | 0.00 | 720.00 |
December | 23.50 | 0.00 | 23.50 | 0.00 | 283.67 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.18 | 2.05 | 66.13 | 47.14 | 134.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.50 | 0.00 | 23.50 | 0.00 | 19.91 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 115.95 | 10.73 | 105.22 | 122.21 | 319.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 12.76 | 0.00 | 12.76 | 0.00 | 117.93 | 0.00 | 0.00 | 744.00 |
February | 16.17 | 0.00 | 16.17 | 0.15 | 93.02 | 0.00 | 0.00 | 672.00 |
March | 24.24 | 0.00 | 24.24 | 4.61 | 60.89 | 0.00 | 0.00 | 744.00 |
April | 28.10 | 0.23 | 27.87 | 13.07 | 39.01 | 0.00 | 0.00 | 720.00 |
May | 36.53 | 1.38 | 35.15 | 29.25 | 18.22 | 0.00 | 0.00 | 744.00 |
June | 42.74 | 3.96 | 38.79 | 44.73 | 9.97 | 0.00 | 0.00 | 720.00 |
July | 40.09 | 2.76 | 37.33 | 45.05 | 7.34 | 0.00 | 0.00 | 744.00 |
August | 33.59 | 0.68 | 32.92 | 39.28 | 9.80 | 0.00 | 0.00 | 744.00 |
September | 25.71 | 0.02 | 25.69 | 23.34 | 22.04 | 0.00 | 0.00 | 720.00 |
October | 19.09 | 0.00 | 19.09 | 6.49 | 41.70 | 0.00 | 0.00 | 744.00 |
November | 13.35 | 0.00 | 13.35 | 1.31 | 71.17 | 0.00 | 0.00 | 720.00 |
December | 8.66 | 0.00 | 8.66 | 0.00 | 104.57 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 25.13 | 0.75 | 24.38 | 17.38 | 49.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 8.66 | 0.00 | 8.66 | 0.00 | 7.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 42.74 | 3.96 | 38.79 | 45.05 | 117.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 79.53 | 54.48 | 25.05 | 63.89 | 94.90 | 0.00 | 0.00 | 744.00 |
February | 85.76 | 58.19 | 27.57 | 70.40 | 75.14 | 0.00 | 0.00 | 672.00 |
March | 73.48 | 38.48 | 35.00 | 57.81 | 55.21 | 0.00 | 0.00 | 744.00 |
April | 65.48 | 30.01 | 35.47 | 51.87 | 38.46 | 0.00 | 0.00 | 720.00 |
May | 55.84 | 15.61 | 40.23 | 47.15 | 19.32 | 0.00 | 0.00 | 744.00 |
June | 53.31 | 10.64 | 42.67 | 53.14 | 10.68 | 0.00 | 0.00 | 720.00 |
July | 56.57 | 14.14 | 42.43 | 58.69 | 7.74 | 0.00 | 0.00 | 744.00 |
August | 62.69 | 21.70 | 40.98 | 67.84 | 10.15 | 0.00 | 0.00 | 744.00 |
September | 75.71 | 39.07 | 36.64 | 79.58 | 21.63 | 0.00 | 0.00 | 720.00 |
October | 81.61 | 51.46 | 30.15 | 80.72 | 38.53 | 0.00 | 0.00 | 744.00 |
November | 61.05 | 38.22 | 22.83 | 51.91 | 60.80 | 0.00 | 0.00 | 720.00 |
December | 64.99 | 49.21 | 15.78 | 57.89 | 88.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 67.90 | 34.97 | 32.93 | 61.70 | 43.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 53.31 | 10.64 | 15.78 | 47.15 | 7.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 85.76 | 58.19 | 42.67 | 80.72 | 94.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 215.85 | 147.87 | 67.98 | 173.42 | 257.58 | 0.00 | 0.00 | 744.00 |
February | 232.78 | 157.95 | 74.84 | 191.09 | 203.95 | 0.00 | 0.00 | 672.00 |
March | 199.44 | 104.44 | 95.00 | 156.91 | 149.85 | 0.00 | 0.00 | 744.00 |
April | 177.73 | 81.45 | 96.28 | 140.78 | 104.40 | 0.00 | 0.00 | 720.00 |
May | 151.56 | 42.38 | 109.18 | 127.97 | 52.43 | 0.00 | 0.00 | 744.00 |
June | 144.68 | 28.87 | 115.81 | 144.23 | 29.00 | 0.00 | 0.00 | 720.00 |
July | 153.54 | 38.38 | 115.16 | 159.30 | 21.01 | 0.00 | 0.00 | 744.00 |
August | 170.15 | 58.91 | 111.24 | 184.14 | 27.55 | 0.00 | 0.00 | 744.00 |
September | 205.49 | 106.05 | 99.44 | 216.01 | 58.70 | 0.00 | 0.00 | 720.00 |
October | 221.49 | 139.67 | 81.82 | 219.08 | 104.58 | 0.00 | 0.00 | 744.00 |
November | 165.71 | 103.74 | 61.96 | 140.90 | 165.02 | 0.00 | 0.00 | 720.00 |
December | 176.39 | 133.57 | 42.82 | 157.12 | 240.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 184.29 | 94.93 | 89.37 | 167.46 | 117.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 144.68 | 28.87 | 42.82 | 127.97 | 21.01 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 232.78 | 157.95 | 115.81 | 219.08 | 257.58 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 137.33 | 198.40 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 148.73 | 160.78 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 123.00 | 115.36 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 107.52 | 81.93 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 94.23 | 43.12 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 105.13 | 24.72 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 115.94 | 18.84 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 136.15 | 24.02 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 164.22 | 47.64 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 169.75 | 81.83 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 110.98 | 126.02 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 124.40 | 182.38 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 128.01 | 91.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 94.23 | 18.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 169.75 | 198.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 32.07 | 427.56 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 77.09 | 341.43 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 110.43 | 220.97 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 241.87 | 148.93 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 271.68 | 77.63 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 365.23 | 45.18 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 406.56 | 34.74 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 354.52 | 44.33 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 258.11 | 88.17 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 129.61 | 158.35 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 45.65 | 259.68 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 27.95 | 381.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 193.98 | 185.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 27.95 | 34.74 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 406.56 | 427.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.01 | 243.01 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.57 | 196.29 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 10.56 | 125.01 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 25.37 | 82.83 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 54.42 | 41.48 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 83.91 | 24.95 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 82.14 | 21.28 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 72.19 | 26.60 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 44.50 | 49.91 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 14.16 | 86.96 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 3.14 | 144.43 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 212.08 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 32.77 | 104.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 21.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 83.91 | 243.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 109.04 | 44.34 | 64.69 | 33.43 | 423.55 | 0.00 | 0.00 | 744.00 |
February | 159.13 | 78.34 | 80.78 | 79.95 | 336.60 | 0.00 | 0.00 | 672.00 |
March | 189.91 | 70.64 | 119.27 | 114.25 | 218.34 | 0.00 | 0.00 | 744.00 |
April | 277.72 | 137.44 | 140.28 | 243.67 | 148.73 | 0.00 | 0.00 | 720.00 |
May | 278.24 | 111.39 | 166.85 | 269.24 | 79.56 | 0.00 | 0.00 | 744.00 |
June | 325.47 | 140.70 | 184.77 | 359.82 | 49.15 | 0.00 | 0.00 | 720.00 |
July | 349.59 | 165.82 | 183.76 | 398.21 | 41.53 | 0.00 | 0.00 | 744.00 |
August | 305.27 | 139.68 | 165.59 | 348.91 | 50.61 | 0.00 | 0.00 | 744.00 |
September | 247.74 | 117.40 | 130.33 | 258.80 | 90.65 | 0.00 | 0.00 | 720.00 |
October | 173.64 | 77.57 | 96.07 | 134.88 | 155.74 | 0.00 | 0.00 | 744.00 |
November | 103.61 | 38.47 | 65.14 | 48.30 | 256.59 | 0.00 | 0.00 | 720.00 |
December | 79.76 | 37.75 | 42.01 | 29.66 | 377.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 216.82 | 96.65 | 120.17 | 193.81 | 185.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 79.76 | 37.75 | 42.01 | 29.66 | 41.53 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 349.59 | 165.82 | 184.77 | 398.21 | 423.55 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 250.17 | 171.39 | 78.79 | 194.07 | 298.13 | 0.00 | 0.00 | 744.00 |
February | 269.80 | 183.06 | 86.74 | 211.25 | 242.62 | 0.00 | 0.00 | 672.00 |
March | 231.15 | 121.05 | 110.11 | 175.23 | 173.31 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 94.40 | 111.59 | 156.65 | 120.97 | 0.00 | 0.00 | 720.00 |
May | 175.66 | 49.12 | 126.54 | 139.26 | 62.52 | 0.00 | 0.00 | 744.00 |
June | 167.69 | 33.46 | 134.22 | 157.47 | 35.08 | 0.00 | 0.00 | 720.00 |
July | 177.95 | 44.48 | 133.47 | 174.05 | 25.87 | 0.00 | 0.00 | 744.00 |
August | 197.20 | 68.27 | 128.93 | 202.16 | 33.88 | 0.00 | 0.00 | 744.00 |
September | 238.17 | 122.92 | 115.25 | 240.12 | 70.13 | 0.00 | 0.00 | 720.00 |
October | 256.71 | 161.88 | 94.83 | 244.42 | 123.38 | 0.00 | 0.00 | 744.00 |
November | 192.05 | 120.24 | 71.82 | 157.73 | 190.83 | 0.00 | 0.00 | 720.00 |
December | 204.43 | 154.80 | 49.63 | 176.43 | 274.73 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 213.60 | 110.02 | 103.58 | 185.61 | 137.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 167.69 | 33.46 | 49.63 | 139.26 | 25.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 269.80 | 183.06 | 134.22 | 244.42 | 298.13 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1854.56 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 0.65 | 1491.28 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 49.42 | 1029.15 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 158.77 | 690.87 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 367.15 | 347.06 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 586.07 | 210.35 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 591.50 | 165.73 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 515.98 | 211.10 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 300.81 | 414.41 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 69.70 | 733.72 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 11.73 | 1182.01 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1681.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 222.32 | 831.19 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 165.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 591.50 | 1854.56 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 191.43 | 0.00 | 191.43 | 0.00 | 1891.70 | 0.00 | 0.00 | 744.00 |
February | 242.69 | 0.00 | 242.69 | 0.35 | 1525.82 | 0.00 | 0.00 | 672.00 |
March | 363.77 | 0.00 | 363.77 | 43.98 | 1058.56 | 0.00 | 0.00 | 744.00 |
April | 421.58 | 3.38 | 418.20 | 149.64 | 712.72 | 0.00 | 0.00 | 720.00 |
May | 548.12 | 20.71 | 527.41 | 351.27 | 359.34 | 0.00 | 0.00 | 744.00 |
June | 641.41 | 59.37 | 582.04 | 570.60 | 219.61 | 0.00 | 0.00 | 720.00 |
July | 601.60 | 41.41 | 560.19 | 576.18 | 173.80 | 0.00 | 0.00 | 744.00 |
August | 504.10 | 10.16 | 493.94 | 501.08 | 221.10 | 0.00 | 0.00 | 744.00 |
September | 385.79 | 0.35 | 385.44 | 289.05 | 429.70 | 0.00 | 0.00 | 720.00 |
October | 286.48 | 0.00 | 286.48 | 62.11 | 756.87 | 0.00 | 0.00 | 744.00 |
November | 200.39 | 0.00 | 200.39 | 9.62 | 1214.83 | 0.00 | 0.00 | 720.00 |
December | 129.99 | 0.00 | 129.99 | 0.00 | 1719.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 377.15 | 11.33 | 365.83 | 214.11 | 853.83 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.99 | 0.00 | 129.99 | 0.00 | 173.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 641.41 | 59.37 | 582.04 | 576.18 | 1891.70 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 27.35 | 0.00 | 27.35 | 0.01 | 239.15 | 0.00 | 0.00 | 744.00 |
February | 34.67 | 0.00 | 34.67 | 0.65 | 188.34 | 0.00 | 0.00 | 672.00 |
March | 51.97 | 0.00 | 51.97 | 12.46 | 129.96 | 0.00 | 0.00 | 744.00 |
April | 60.23 | 0.48 | 59.75 | 33.58 | 85.66 | 0.00 | 0.00 | 720.00 |
May | 78.31 | 2.96 | 75.35 | 73.25 | 44.39 | 0.00 | 0.00 | 744.00 |
June | 91.63 | 8.48 | 83.15 | 108.81 | 26.83 | 0.00 | 0.00 | 720.00 |
July | 85.95 | 5.92 | 80.03 | 110.80 | 20.37 | 0.00 | 0.00 | 744.00 |
August | 72.02 | 1.45 | 70.57 | 97.66 | 25.74 | 0.00 | 0.00 | 744.00 |
September | 55.12 | 0.05 | 55.07 | 60.32 | 50.26 | 0.00 | 0.00 | 720.00 |
October | 40.93 | 0.00 | 40.93 | 18.64 | 89.47 | 0.00 | 0.00 | 744.00 |
November | 28.63 | 0.00 | 28.63 | 4.61 | 147.41 | 0.00 | 0.00 | 720.00 |
December | 18.57 | 0.00 | 18.57 | 0.00 | 216.61 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 53.88 | 1.62 | 52.26 | 43.66 | 104.97 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 18.57 | 0.00 | 18.57 | 0.00 | 20.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 91.63 | 8.48 | 83.15 | 110.80 | 239.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 218.23 | 89.44 | 128.79 | 60.88 | 825.73 | 0.00 | 0.00 | 744.00 |
February | 290.57 | 127.90 | 162.68 | 127.87 | 636.82 | 0.00 | 0.00 | 672.00 |
March | 394.65 | 156.59 | 238.06 | 249.57 | 446.38 | 0.00 | 0.00 | 744.00 |
April | 481.67 | 209.93 | 271.73 | 428.64 | 307.81 | 0.00 | 0.00 | 720.00 |
May | 608.53 | 266.12 | 342.41 | 668.59 | 163.38 | 0.00 | 0.00 | 744.00 |
June | 668.73 | 291.27 | 377.46 | 828.99 | 101.38 | 0.00 | 0.00 | 720.00 |
July | 676.06 | 312.03 | 364.04 | 872.60 | 77.22 | 0.00 | 0.00 | 744.00 |
August | 570.03 | 245.65 | 324.38 | 741.59 | 96.36 | 0.00 | 0.00 | 744.00 |
September | 510.75 | 242.25 | 268.49 | 597.43 | 182.48 | 0.00 | 0.00 | 720.00 |
October | 323.41 | 134.61 | 188.80 | 253.94 | 315.13 | 0.00 | 0.00 | 744.00 |
November | 191.31 | 62.09 | 129.22 | 76.70 | 517.98 | 0.00 | 0.00 | 720.00 |
December | 147.64 | 63.22 | 84.42 | 38.34 | 762.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 424.12 | 183.68 | 240.44 | 413.65 | 368.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 147.64 | 62.09 | 84.42 | 38.34 | 77.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 676.06 | 312.03 | 377.46 | 872.60 | 825.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 170.58 | 116.86 | 53.72 | 141.73 | 195.81 | 0.00 | 0.00 | 744.00 |
February | 183.96 | 124.82 | 59.14 | 156.30 | 155.66 | 0.00 | 0.00 | 672.00 |
March | 157.61 | 82.54 | 75.08 | 128.24 | 119.64 | 0.00 | 0.00 | 744.00 |
April | 140.45 | 64.36 | 76.09 | 117.02 | 85.15 | 0.00 | 0.00 | 720.00 |
May | 119.77 | 33.49 | 86.28 | 111.06 | 46.84 | 0.00 | 0.00 | 744.00 |
June | 114.34 | 22.82 | 91.52 | 126.20 | 28.64 | 0.00 | 0.00 | 720.00 |
July | 121.33 | 30.33 | 91.01 | 139.51 | 21.45 | 0.00 | 0.00 | 744.00 |
August | 134.46 | 46.55 | 87.91 | 158.18 | 26.80 | 0.00 | 0.00 | 744.00 |
September | 162.39 | 83.81 | 78.58 | 181.27 | 50.04 | 0.00 | 0.00 | 720.00 |
October | 175.04 | 110.38 | 64.66 | 180.25 | 85.07 | 0.00 | 0.00 | 744.00 |
November | 130.95 | 81.98 | 48.97 | 115.88 | 129.19 | 0.00 | 0.00 | 720.00 |
December | 139.39 | 105.55 | 33.84 | 127.42 | 185.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 145.64 | 75.02 | 70.62 | 140.18 | 93.89 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 114.34 | 22.82 | 33.84 | 111.06 | 21.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 183.96 | 124.82 | 91.52 | 181.27 | 195.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 34.63 | 0.00 | 34.63 | 0.00 | 323.79 | 0.00 | 0.00 | 744.00 |
February | 43.91 | 0.00 | 43.91 | 0.26 | 253.80 | 0.00 | 0.00 | 672.00 |
March | 65.82 | 0.00 | 65.82 | 11.25 | 169.15 | 0.00 | 0.00 | 744.00 |
April | 76.28 | 0.61 | 75.66 | 32.50 | 109.78 | 0.00 | 0.00 | 720.00 |
May | 99.17 | 3.75 | 95.42 | 74.07 | 52.79 | 0.00 | 0.00 | 744.00 |
June | 116.05 | 10.74 | 105.31 | 112.57 | 31.34 | 0.00 | 0.00 | 720.00 |
July | 108.85 | 7.49 | 101.35 | 112.64 | 24.67 | 0.00 | 0.00 | 744.00 |
August | 91.20 | 1.84 | 89.37 | 98.28 | 31.40 | 0.00 | 0.00 | 744.00 |
September | 69.80 | 0.06 | 69.74 | 58.23 | 64.21 | 0.00 | 0.00 | 720.00 |
October | 51.83 | 0.00 | 51.83 | 15.56 | 116.77 | 0.00 | 0.00 | 744.00 |
November | 36.26 | 0.00 | 36.26 | 2.99 | 197.28 | 0.00 | 0.00 | 720.00 |
December | 23.52 | 0.00 | 23.52 | 0.00 | 288.83 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 68.24 | 2.05 | 66.19 | 43.46 | 138.12 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 23.52 | 0.00 | 23.52 | 0.00 | 24.67 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 116.05 | 10.74 | 105.31 | 112.64 | 323.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 30.99 | 0.00 | 30.99 | 0.00 | 289.69 | 0.00 | 0.00 | 744.00 |
February | 39.29 | 0.00 | 39.29 | 0.24 | 227.08 | 0.00 | 0.00 | 672.00 |
March | 58.89 | 0.00 | 58.89 | 10.06 | 151.34 | 0.00 | 0.00 | 744.00 |
April | 68.24 | 0.55 | 67.70 | 29.08 | 98.22 | 0.00 | 0.00 | 720.00 |
May | 88.73 | 3.35 | 85.38 | 66.27 | 47.23 | 0.00 | 0.00 | 744.00 |
June | 103.83 | 9.61 | 94.22 | 100.71 | 28.04 | 0.00 | 0.00 | 720.00 |
July | 97.38 | 6.70 | 90.68 | 100.78 | 22.08 | 0.00 | 0.00 | 744.00 |
August | 81.60 | 1.64 | 79.96 | 87.93 | 28.09 | 0.00 | 0.00 | 744.00 |
September | 62.45 | 0.06 | 62.39 | 52.10 | 57.45 | 0.00 | 0.00 | 720.00 |
October | 46.37 | 0.00 | 46.37 | 13.92 | 104.48 | 0.00 | 0.00 | 744.00 |
November | 32.44 | 0.00 | 32.44 | 2.68 | 176.50 | 0.00 | 0.00 | 720.00 |
December | 21.04 | 0.00 | 21.04 | 0.00 | 258.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 61.05 | 1.83 | 59.22 | 38.88 | 123.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 21.04 | 0.00 | 21.04 | 0.00 | 22.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 103.83 | 9.61 | 94.22 | 100.78 | 289.69 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.83 | 436.27 | 200.55 | 505.66 | 767.48 | 0.00 | 0.00 | 744.00 |
February | 686.78 | 465.98 | 220.79 | 558.93 | 604.17 | 0.00 | 0.00 | 672.00 |
March | 588.42 | 308.13 | 280.29 | 454.80 | 451.67 | 0.00 | 0.00 | 744.00 |
April | 524.35 | 240.29 | 284.06 | 405.69 | 319.45 | 0.00 | 0.00 | 720.00 |
May | 447.15 | 125.03 | 322.12 | 362.69 | 165.75 | 0.00 | 0.00 | 744.00 |
June | 426.85 | 85.19 | 341.67 | 400.90 | 99.66 | 0.00 | 0.00 | 720.00 |
July | 452.98 | 113.22 | 339.75 | 442.71 | 77.33 | 0.00 | 0.00 | 744.00 |
August | 501.98 | 173.79 | 328.19 | 519.26 | 96.54 | 0.00 | 0.00 | 744.00 |
September | 606.27 | 312.89 | 293.38 | 621.02 | 186.45 | 0.00 | 0.00 | 720.00 |
October | 653.47 | 412.07 | 241.40 | 635.63 | 317.79 | 0.00 | 0.00 | 744.00 |
November | 488.88 | 306.07 | 182.81 | 408.74 | 497.42 | 0.00 | 0.00 | 720.00 |
December | 520.39 | 394.06 | 126.33 | 457.72 | 719.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 543.72 | 280.06 | 263.66 | 480.75 | 357.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 426.85 | 85.19 | 126.33 | 362.69 | 77.33 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 686.78 | 465.98 | 341.67 | 635.63 | 767.48 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: RETAIL_1_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.187666E+10 | 0.255893E+10 |
February | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.185006E+10 | 0.184438E+10 |
March | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.166573E+10 | 0.151387E+10 |
April | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.140842E+10 | 0.104624E+10 |
May | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.130647E+10 | 0.568994E+09 |
June | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.138726E+10 | 0.332980E+09 |
July | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.158220E+10 | 0.272391E+09 |
August | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.184420E+10 | 0.346667E+09 |
September | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.213281E+10 | 0.647540E+09 |
October | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.228820E+10 | 0.110798E+10 |
November | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.145132E+10 | 0.160964E+10 |
December | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.167772E+10 | 0.240409E+10 |
Annual Sum or Average | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.204710E+11 | 0.142537E+11 |
Minimum of Months | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.130647E+10 | 0.272391E+09 |
Maximum of Months | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.228820E+10 | 0.255893E+10 |
Report: WindowEnergyReportMonthly
For: CAFE_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.524397E+10 | 0.727455E+10 |
February | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.516168E+10 | 0.531729E+10 |
March | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.462548E+10 | 0.441354E+10 |
April | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.390209E+10 | 0.312880E+10 |
May | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.356615E+10 | 0.179929E+10 |
June | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.380160E+10 | 0.108834E+10 |
July | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.435205E+10 | 0.896754E+09 |
August | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.510006E+10 | 0.113209E+10 |
September | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.592559E+10 | 0.201003E+10 |
October | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.636350E+10 | 0.334883E+10 |
November | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.403510E+10 | 0.467601E+10 |
December | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.468424E+10 | 0.684763E+10 |
Annual Sum or Average | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.567615E+11 | 0.419331E+11 |
Minimum of Months | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.356615E+10 | 0.896754E+09 |
Maximum of Months | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.636350E+10 | 0.727455E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_FLR_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.690423E+10 | 0.983114E+10 |
February | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.682803E+10 | 0.715611E+10 |
March | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.610421E+10 | 0.602761E+10 |
April | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.517219E+10 | 0.428320E+10 |
May | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.471289E+10 | 0.244712E+10 |
June | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.507107E+10 | 0.146626E+10 |
July | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.581849E+10 | 0.118765E+10 |
August | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.680695E+10 | 0.149272E+10 |
September | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.787346E+10 | 0.269599E+10 |
October | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.838956E+10 | 0.454392E+10 |
November | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.529490E+10 | 0.640057E+10 |
December | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.616815E+10 | 0.931521E+10 |
Annual Sum or Average | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.751441E+11 | 0.568475E+11 |
Minimum of Months | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.471289E+10 | 0.118765E+10 |
Maximum of Months | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.838956E+10 | 0.983114E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.369331E+09 | 0.529450E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.361511E+09 | 0.387222E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.329835E+09 | 0.308558E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.279663E+09 | 0.211883E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.255129E+09 | 0.114320E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.275214E+09 | 63254871.52 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.313626E+09 | 49613004.41 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.367526E+09 | 63217384.93 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.427358E+09 | 0.123062E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.455783E+09 | 0.219185E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.288203E+09 | 0.326347E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.333696E+09 | 0.487692E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.405688E+10 | 0.288380E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.255129E+09 | 49613004.41 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.455783E+09 | 0.529450E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 86312904.36 | 0.113943E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.187898E+09 | 0.820201E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.296549E+09 | 0.590956E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.630868E+09 | 0.385279E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.735088E+09 | 0.206162E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.954226E+09 | 0.115789E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109733E+10 | 91614074.94 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.957207E+09 | 0.116875E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.673172E+09 | 0.227804E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.348616E+09 | 0.424331E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.118025E+09 | 0.673043E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 74572056.29 | 0.102064E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.615987E+10 | 0.581213E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 74572056.29 | 91614074.94 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.109733E+10 | 0.113943E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 16885.84 | 0.648195E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 1323446.87 | 0.472385E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 27958893.28 | 0.334732E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 66884686.34 | 0.213643E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.150386E+09 | 0.108667E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.222867E+09 | 62010807.72 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.226572E+09 | 52855468.50 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.198541E+09 | 66471849.57 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.117385E+09 | 0.127251E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 37431547.08 | 0.233653E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7894791.56 | 0.375160E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.567209E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.105726E+10 | 0.326224E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 52855468.50 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.226572E+09 | 0.648195E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_3_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291801E+09 | 0.118673E+09 | 0.173128E+09 | 90005958.66 | 0.112860E+10 |
February | 0.384641E+09 | 0.189369E+09 | 0.195271E+09 | 0.194431E+09 | 0.808629E+09 |
March | 0.508236E+09 | 0.189043E+09 | 0.319194E+09 | 0.306476E+09 | 0.583889E+09 |
April | 0.719270E+09 | 0.355958E+09 | 0.363312E+09 | 0.635659E+09 | 0.384053E+09 |
May | 0.744631E+09 | 0.298096E+09 | 0.446535E+09 | 0.731157E+09 | 0.209115E+09 |
June | 0.842933E+09 | 0.364399E+09 | 0.478534E+09 | 0.943575E+09 | 0.122544E+09 |
July | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.108019E+10 | 0.103626E+09 |
August | 0.816967E+09 | 0.373824E+09 | 0.443143E+09 | 0.946283E+09 | 0.127560E+09 |
September | 0.641610E+09 | 0.304061E+09 | 0.337550E+09 | 0.676168E+09 | 0.231503E+09 |
October | 0.464707E+09 | 0.207605E+09 | 0.257102E+09 | 0.361357E+09 | 0.417903E+09 |
November | 0.268334E+09 | 99641378.41 | 0.168692E+09 | 0.124520E+09 | 0.665008E+09 |
December | 0.213446E+09 | 0.101017E+09 | 0.112429E+09 | 79148644.59 | 0.100928E+10 |
Annual Sum or Average | 0.683214E+10 | 0.304546E+10 | 0.378668E+10 | 0.616897E+10 | 0.579171E+10 |
Minimum of Months | 0.213446E+09 | 99641378.41 | 0.112429E+09 | 79148644.59 | 0.103626E+09 |
Maximum of Months | 0.935567E+09 | 0.443778E+09 | 0.491790E+09 | 0.108019E+10 | 0.112860E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT19_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.302107E+09 | 0.382388E+09 |
February | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.287326E+09 | 0.313767E+09 |
March | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.251859E+09 | 0.269247E+09 |
April | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.204238E+09 | 0.224411E+09 |
May | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.170063E+09 | 0.142862E+09 |
June | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.185448E+09 | 93823946.37 |
July | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.214879E+09 | 80185750.42 |
August | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.259614E+09 | 96161880.03 |
September | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.313045E+09 | 0.154020E+09 |
October | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.334217E+09 | 0.242040E+09 |
November | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.214900E+09 | 0.303850E+09 |
December | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.267445E+09 | 0.364994E+09 |
Annual Sum or Average | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.300514E+10 | 0.266775E+10 |
Minimum of Months | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.170063E+09 | 80185750.42 |
Maximum of Months | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.334217E+09 | 0.382388E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_4_MULT19_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.534685E+09 |
February | 67056690.67 | 0.00 | 67056690.67 | 751911.60 | 0.389196E+09 |
March | 0.111280E+09 | 941.15 | 0.111279E+09 | 21183314.51 | 0.276003E+09 |
April | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 55838017.55 | 0.173857E+09 |
May | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.126330E+09 | 86594454.86 |
June | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.187087E+09 | 48420689.41 |
July | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.192691E+09 | 39369794.82 |
August | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.168248E+09 | 50523491.14 |
September | 0.114208E+09 | 102488.46 | 0.114105E+09 | 98298327.32 | 0.101359E+09 |
October | 87633982.09 | 0.00 | 87633982.09 | 29016544.80 | 0.191383E+09 |
November | 59323427.52 | 0.00 | 59323427.52 | 5631647.49 | 0.312313E+09 |
December | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.470015E+09 |
Annual Sum or Average | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.885075E+09 | 0.267372E+10 |
Minimum of Months | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 39369794.82 |
Maximum of Months | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.192691E+09 | 0.534685E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 71501099.61 | 0.112223E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.139727E+09 | 0.803282E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.307259E+09 | 0.575170E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.506374E+09 | 0.374631E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.805667E+09 | 0.193673E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.970494E+09 | 0.109009E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.105044E+10 | 85126073.71 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.882104E+09 | 0.108601E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.688149E+09 | 0.220600E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.294463E+09 | 0.409027E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 83712356.59 | 0.660458E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 47973140.33 | 0.100848E+10 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.584786E+10 | 0.567029E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 47973140.33 | 85126073.71 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.105044E+10 | 0.112223E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_5_FLR_3_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456508E+09 | 0.312742E+09 | 0.143766E+09 | 0.368758E+09 | 0.528969E+09 |
February | 0.444672E+09 | 0.301714E+09 | 0.142959E+09 | 0.360765E+09 | 0.385635E+09 |
March | 0.421805E+09 | 0.220882E+09 | 0.200923E+09 | 0.327330E+09 | 0.307916E+09 |
April | 0.363753E+09 | 0.166695E+09 | 0.197058E+09 | 0.278365E+09 | 0.209802E+09 |
May | 0.320540E+09 | 89630703.70 | 0.230909E+09 | 0.251715E+09 | 0.114173E+09 |
June | 0.296117E+09 | 59095026.19 | 0.237022E+09 | 0.273087E+09 | 62638657.23 |
July | 0.324715E+09 | 81164324.42 | 0.243550E+09 | 0.312145E+09 | 48281448.79 |
August | 0.359843E+09 | 0.124580E+09 | 0.235263E+09 | 0.366514E+09 | 62097648.64 |
September | 0.420582E+09 | 0.217060E+09 | 0.203522E+09 | 0.425011E+09 | 0.122206E+09 |
October | 0.468440E+09 | 0.295394E+09 | 0.173046E+09 | 0.454266E+09 | 0.218210E+09 |
November | 0.339149E+09 | 0.212328E+09 | 0.126821E+09 | 0.287889E+09 | 0.325725E+09 |
December | 0.373043E+09 | 0.282480E+09 | 90562310.31 | 0.333527E+09 | 0.487219E+09 |
Annual Sum or Average | 0.458917E+10 | 0.236376E+10 | 0.222540E+10 | 0.403937E+10 | 0.287287E+10 |
Minimum of Months | 0.296117E+09 | 59095026.19 | 90562310.31 | 0.251715E+09 | 48281448.79 |
Maximum of Months | 0.468440E+09 | 0.312742E+09 | 0.243550E+09 | 0.454266E+09 | 0.528969E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73189027.76 | 0.00 | 73189027.76 | 8332.67 | 0.648010E+09 |
February | 83809753.88 | 0.00 | 83809753.88 | 1080193.13 | 0.470983E+09 |
March | 0.139082E+09 | 1176.28 | 0.139080E+09 | 26878528.11 | 0.335347E+09 |
April | 0.155984E+09 | 1250863.57 | 0.154733E+09 | 66313968.61 | 0.211322E+09 |
May | 0.209564E+09 | 7918263.87 | 0.201646E+09 | 0.148270E+09 | 0.107743E+09 |
June | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.221749E+09 | 60325134.66 |
July | 0.230010E+09 | 15833083.57 | 0.214177E+09 | 0.227042E+09 | 49436064.71 |
August | 0.192732E+09 | 3884193.15 | 0.188847E+09 | 0.199254E+09 | 63076636.02 |
September | 0.142741E+09 | 128093.60 | 0.142613E+09 | 0.115530E+09 | 0.125471E+09 |
October | 0.109528E+09 | 0.00 | 0.109528E+09 | 36468332.91 | 0.232526E+09 |
November | 74144456.13 | 0.00 | 74144456.13 | 7696652.02 | 0.374604E+09 |
December | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 0.567218E+09 |
Annual Sum or Average | 0.169780E+10 | 50982791.99 | 0.164682E+10 | 0.105029E+10 | 0.324606E+10 |
Minimum of Months | 49697687.04 | 0.00 | 49697687.04 | 0.00 | 49436064.71 |
Maximum of Months | 0.237318E+09 | 21967117.95 | 0.215351E+09 | 0.227042E+09 | 0.648010E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_6_FLR_3_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292037E+09 | 0.119692E+09 | 0.172345E+09 | 73139844.74 | 0.110930E+10 |
February | 0.351213E+09 | 0.154586E+09 | 0.196627E+09 | 0.143278E+09 | 0.788409E+09 |
March | 0.528125E+09 | 0.209550E+09 | 0.318575E+09 | 0.315411E+09 | 0.566106E+09 |
April | 0.623773E+09 | 0.271871E+09 | 0.351903E+09 | 0.511801E+09 | 0.372037E+09 |
May | 0.814328E+09 | 0.356120E+09 | 0.458208E+09 | 0.805145E+09 | 0.195647E+09 |
June | 0.866020E+09 | 0.377202E+09 | 0.488818E+09 | 0.962482E+09 | 0.114279E+09 |
July | 0.904705E+09 | 0.417552E+09 | 0.487152E+09 | 0.103790E+10 | 93619130.66 |
August | 0.762810E+09 | 0.328723E+09 | 0.434087E+09 | 0.876010E+09 | 0.115995E+09 |
September | 0.661432E+09 | 0.313726E+09 | 0.347706E+09 | 0.692261E+09 | 0.222285E+09 |
October | 0.432790E+09 | 0.180140E+09 | 0.252651E+09 | 0.306455E+09 | 0.400647E+09 |
November | 0.247750E+09 | 80412113.67 | 0.167338E+09 | 87902344.08 | 0.650070E+09 |
December | 0.197575E+09 | 84600328.40 | 0.112975E+09 | 49199247.28 | 0.994285E+09 |
Annual Sum or Average | 0.668256E+10 | 0.289417E+10 | 0.378838E+10 | 0.586099E+10 | 0.562267E+10 |
Minimum of Months | 0.197575E+09 | 80412113.67 | 0.112975E+09 | 49199247.28 | 93619130.66 |
Maximum of Months | 0.904705E+09 | 0.417552E+09 | 0.488818E+09 | 0.103790E+10 | 0.110930E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92689285.68 | 0.00 | 92689285.68 | 0.00 | 0.856849E+09 |
February | 0.106140E+09 | 0.00 | 0.106140E+09 | 979564.76 | 0.610412E+09 |
March | 0.176138E+09 | 1489.68 | 0.176137E+09 | 33526052.97 | 0.442407E+09 |
April | 0.197544E+09 | 1584139.79 | 0.195960E+09 | 91865646.04 | 0.274271E+09 |
May | 0.265400E+09 | 10027981.57 | 0.255372E+09 | 0.212514E+09 | 0.132404E+09 |
June | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.314474E+09 | 70096032.72 |
July | 0.291293E+09 | 20051601.33 | 0.271241E+09 | 0.327330E+09 | 53325101.45 |
August | 0.244082E+09 | 4919085.54 | 0.239163E+09 | 0.285392E+09 | 71220818.63 |
September | 0.180773E+09 | 162222.46 | 0.180610E+09 | 0.164111E+09 | 0.154936E+09 |
October | 0.138710E+09 | 0.00 | 0.138710E+09 | 47172882.28 | 0.302945E+09 |
November | 93899275.44 | 0.00 | 93899275.44 | 9216003.92 | 0.500404E+09 |
December | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 0.759786E+09 |
Annual Sum or Average | 0.215016E+10 | 64566489.21 | 0.208559E+10 | 0.148658E+10 | 0.422906E+10 |
Minimum of Months | 62938984.89 | 0.00 | 62938984.89 | 0.00 | 53325101.45 |
Maximum of Months | 0.300548E+09 | 27819968.84 | 0.272728E+09 | 0.327330E+09 | 0.856849E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 34169108.66 | 0.00 | 34169108.66 | 0.00 | 0.315870E+09 |
February | 39127512.35 | 0.00 | 39127512.35 | 361108.13 | 0.225023E+09 |
March | 64931807.30 | 549.16 | 64931258.14 | 12359091.33 | 0.163089E+09 |
April | 72822870.96 | 583979.52 | 72238891.44 | 33865480.99 | 0.101108E+09 |
May | 97837340.20 | 3696729.23 | 94140610.97 | 78341623.70 | 48809660.99 |
June | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.115928E+09 | 25840300.11 |
July | 0.107383E+09 | 7391850.52 | 99990758.17 | 0.120667E+09 | 19657840.41 |
August | 89978876.20 | 1813378.61 | 88165497.59 | 0.105207E+09 | 26254942.77 |
September | 66640246.57 | 59801.92 | 66580444.66 | 60498199.30 | 57115726.43 |
October | 51134341.44 | 0.00 | 51134341.44 | 17389877.68 | 0.111678E+09 |
November | 34615160.99 | 0.00 | 34615160.99 | 3397400.65 | 0.184470E+09 |
December | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 0.280089E+09 |
Annual Sum or Average | 0.792636E+09 | 23801881.41 | 0.768834E+09 | 0.548016E+09 | 0.155901E+10 |
Minimum of Months | 23201915.93 | 0.00 | 23201915.93 | 0.00 | 19657840.41 |
Maximum of Months | 0.110795E+09 | 10255592.45 | 0.100539E+09 | 0.120667E+09 | 0.315870E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.213005E+09 | 0.145924E+09 | 67080677.26 | 0.171128E+09 | 0.254179E+09 |
February | 0.207482E+09 | 0.140778E+09 | 66703954.00 | 0.170321E+09 | 0.181787E+09 |
March | 0.196812E+09 | 0.103063E+09 | 93749766.36 | 0.154843E+09 | 0.147869E+09 |
April | 0.169726E+09 | 77778998.96 | 91946673.79 | 0.134440E+09 | 99697216.89 |
May | 0.149563E+09 | 41821325.16 | 0.107741E+09 | 0.126283E+09 | 51739407.46 |
June | 0.138167E+09 | 27573501.09 | 0.110594E+09 | 0.137731E+09 | 27690657.38 |
July | 0.151510E+09 | 37870946.71 | 0.113640E+09 | 0.157200E+09 | 20731308.97 |
August | 0.167901E+09 | 58128357.07 | 0.109773E+09 | 0.181713E+09 | 27187461.14 |
September | 0.196242E+09 | 0.101279E+09 | 94962720.04 | 0.206283E+09 | 56053747.96 |
October | 0.218572E+09 | 0.137830E+09 | 80742463.40 | 0.216188E+09 | 0.103204E+09 |
November | 0.158245E+09 | 99071298.74 | 59174088.99 | 0.134560E+09 | 0.157592E+09 |
December | 0.174060E+09 | 0.131804E+09 | 42256009.05 | 0.155050E+09 | 0.236960E+09 |
Annual Sum or Average | 0.214129E+10 | 0.110292E+10 | 0.103836E+10 | 0.194574E+10 | 0.136469E+10 |
Minimum of Months | 0.138167E+09 | 27573501.09 | 42256009.05 | 0.126283E+09 | 20731308.97 |
Maximum of Months | 0.218572E+09 | 0.145924E+09 | 0.113640E+09 | 0.216188E+09 | 0.254179E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_3_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.578139E+09 | 0.396068E+09 | 0.182071E+09 | 0.464477E+09 | 0.689893E+09 |
February | 0.563149E+09 | 0.382101E+09 | 0.181048E+09 | 0.462286E+09 | 0.493407E+09 |
March | 0.534189E+09 | 0.279733E+09 | 0.254456E+09 | 0.420275E+09 | 0.401348E+09 |
April | 0.460670E+09 | 0.211108E+09 | 0.249562E+09 | 0.364898E+09 | 0.270599E+09 |
May | 0.405943E+09 | 0.113512E+09 | 0.292432E+09 | 0.342757E+09 | 0.140431E+09 |
June | 0.375014E+09 | 74840121.99 | 0.300174E+09 | 0.373831E+09 | 75158108.13 |
July | 0.411230E+09 | 0.102789E+09 | 0.308441E+09 | 0.426673E+09 | 56269013.03 |
August | 0.455718E+09 | 0.157772E+09 | 0.297946E+09 | 0.493206E+09 | 73792330.60 |
September | 0.532641E+09 | 0.274893E+09 | 0.257748E+09 | 0.559894E+09 | 0.152141E+09 |
October | 0.593250E+09 | 0.374098E+09 | 0.219152E+09 | 0.586777E+09 | 0.280115E+09 |
November | 0.429510E+09 | 0.268900E+09 | 0.160611E+09 | 0.365223E+09 | 0.427737E+09 |
December | 0.472435E+09 | 0.357743E+09 | 0.114691E+09 | 0.420837E+09 | 0.643157E+09 |
Annual Sum or Average | 0.581189E+10 | 0.299356E+10 | 0.281833E+10 | 0.528113E+10 | 0.370405E+10 |
Minimum of Months | 0.375014E+09 | 74840121.99 | 0.114691E+09 | 0.342757E+09 | 56269013.03 |
Maximum of Months | 0.593250E+09 | 0.396068E+09 | 0.308441E+09 | 0.586777E+09 | 0.689893E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.367817E+09 | 0.531384E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.359817E+09 | 0.388959E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.329437E+09 | 0.308983E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.278698E+09 | 0.212368E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.252390E+09 | 0.115502E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.272489E+09 | 64071373.63 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.310537E+09 | 50463295.42 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.364660E+09 | 64329976.88 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.425648E+09 | 0.123483E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.454657E+09 | 0.219183E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.287659E+09 | 0.326642E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.333201E+09 | 0.488489E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.403701E+10 | 0.289386E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.252390E+09 | 50463295.42 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.454657E+09 | 0.531384E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_1_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 85894047.67 | 0.114519E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.186497E+09 | 0.825996E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.295776E+09 | 0.591840E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.626931E+09 | 0.386023E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.727667E+09 | 0.207913E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.946679E+09 | 0.117095E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.108894E+10 | 93058919.50 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.949535E+09 | 0.118727E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.669010E+09 | 0.228549E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.347143E+09 | 0.424126E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.118323E+09 | 0.673092E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 74851033.86 | 0.102283E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.611725E+10 | 0.583444E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 74851033.86 | 93058919.50 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.108894E+10 | 0.114519E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 29466.97 | 0.650870E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1371030.94 | 0.474857E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 28288283.81 | 0.334825E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 65764080.37 | 0.214701E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.145755E+09 | 0.111107E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.217486E+09 | 64676366.05 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.220013E+09 | 57002835.90 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.193353E+09 | 71251891.16 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.115333E+09 | 0.129369E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 37922044.64 | 0.232914E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 8147891.09 | 0.374351E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.568031E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.103346E+10 | 0.328395E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 57002835.90 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.220013E+09 | 0.650870E+09 |
Report: WindowEnergyReportMonthly
For: ROOM_2_FLR_6_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.292040E+09 | 0.118770E+09 | 0.173270E+09 | 89541221.09 | 0.113445E+10 |
February | 0.384956E+09 | 0.189524E+09 | 0.195432E+09 | 0.193411E+09 | 0.814304E+09 |
March | 0.508653E+09 | 0.189198E+09 | 0.319455E+09 | 0.306020E+09 | 0.584801E+09 |
April | 0.719860E+09 | 0.356250E+09 | 0.363610E+09 | 0.631593E+09 | 0.385498E+09 |
May | 0.745242E+09 | 0.298341E+09 | 0.446902E+09 | 0.721126E+09 | 0.213093E+09 |
June | 0.843624E+09 | 0.364698E+09 | 0.478927E+09 | 0.932661E+09 | 0.127404E+09 |
July | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.106657E+10 | 0.111230E+09 |
August | 0.817637E+09 | 0.374131E+09 | 0.443507E+09 | 0.934509E+09 | 0.135565E+09 |
September | 0.642137E+09 | 0.304310E+09 | 0.337827E+09 | 0.670819E+09 | 0.234977E+09 |
October | 0.465088E+09 | 0.207776E+09 | 0.257313E+09 | 0.361251E+09 | 0.417147E+09 |
November | 0.268554E+09 | 99723118.67 | 0.168831E+09 | 0.125194E+09 | 0.665072E+09 |
December | 0.213622E+09 | 0.101100E+09 | 0.112521E+09 | 79438831.05 | 0.101212E+10 |
Annual Sum or Average | 0.683775E+10 | 0.304796E+10 | 0.378979E+10 | 0.611213E+10 | 0.583566E+10 |
Minimum of Months | 0.213622E+09 | 99723118.67 | 0.112521E+09 | 79438831.05 | 0.111230E+09 |
Maximum of Months | 0.936335E+09 | 0.444142E+09 | 0.492193E+09 | 0.106657E+10 | 0.113445E+10 |
Report: WindowEnergyReportMonthly
For: ROOM_3_MULT9_FLR_6_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.519799E+09 | 0.798500E+09 |
February | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.511061E+09 | 0.586948E+09 |
March | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.469340E+09 | 0.464201E+09 |
April | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.406026E+09 | 0.313546E+09 |
May | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.373003E+09 | 0.167465E+09 |
June | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.408173E+09 | 90935204.97 |
July | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.466169E+09 | 69285189.29 |
August | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.541469E+09 | 90749864.11 |
September | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.622397E+09 | 0.181766E+09 |
October | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.654653E+09 | 0.330461E+09 |
November | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.408827E+09 | 0.494636E+09 |
December | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.472537E+09 | 0.735824E+09 |
Annual Sum or Average | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.585346E+10 | 0.432432E+10 |
Minimum of Months | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.373003E+09 | 69285189.29 |
Maximum of Months | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.654653E+09 | 0.798500E+09 |
Report: WindowEnergyReportMonthly
For: BANQUET_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.496726E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 1579426.63 | 0.360770E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.132369E+09 | 0.275649E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.411541E+09 | 0.179074E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.983367E+09 | 0.929553E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.151909E+10 | 0.545230E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.158428E+10 | 0.443899E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.138201E+10 | 0.565420E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.779694E+09 | 0.107416E+10 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.186682E+09 | 0.196519E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 30416539.70 | 0.306377E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.450288E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.701103E+10 | 0.262123E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.443899E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.158428E+10 | 0.496726E+10 |
Report: WindowEnergyReportMonthly
For: DINING_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.506672E+10 |
February | 0.587127E+09 | 0.00 | 0.587127E+09 | 841733.26 | 0.369126E+10 |
March | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.117806E+09 | 0.283525E+10 |
April | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.387859E+09 | 0.184736E+10 |
May | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.940840E+09 | 0.962452E+09 |
June | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.147900E+10 | 0.569232E+09 |
July | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.154323E+10 | 0.465503E+09 |
August | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.134210E+10 | 0.592197E+09 |
September | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.749205E+09 | 0.111379E+10 |
October | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.166346E+09 | 0.202721E+10 |
November | 0.519417E+09 | 0.00 | 0.519417E+09 | 24933336.88 | 0.314884E+10 |
December | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.460652E+10 |
Annual Sum or Average | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.675216E+10 | 0.269263E+11 |
Minimum of Months | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.465503E+09 |
Maximum of Months | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.154323E+10 | 0.506672E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 73249067.98 | 0.00 | 73249067.98 | 24075.95 | 0.640535E+09 |
February | 83878506.75 | 0.00 | 83878506.75 | 1578692.40 | 0.455639E+09 |
March | 0.139196E+09 | 1177.24 | 0.139195E+09 | 33366854.70 | 0.348091E+09 |
April | 0.156112E+09 | 1251889.71 | 0.154860E+09 | 87044818.73 | 0.222042E+09 |
May | 0.209736E+09 | 7924759.57 | 0.201811E+09 | 0.196183E+09 | 0.118905E+09 |
June | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.282025E+09 | 69547131.44 |
July | 0.230198E+09 | 15846072.16 | 0.214352E+09 | 0.296770E+09 | 54565059.52 |
August | 0.192890E+09 | 3887379.53 | 0.189002E+09 | 0.261580E+09 | 68940479.09 |
September | 0.142858E+09 | 128198.68 | 0.142730E+09 | 0.156356E+09 | 0.130281E+09 |
October | 0.109618E+09 | 0.00 | 0.109618E+09 | 49929585.87 | 0.239627E+09 |
November | 74205280.13 | 0.00 | 74205280.13 | 11942950.89 | 0.382076E+09 |
December | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 0.580170E+09 |
Annual Sum or Average | 0.169919E+10 | 51024615.44 | 0.164817E+10 | 0.137680E+10 | 0.331042E+10 |
Minimum of Months | 49738456.27 | 0.00 | 49738456.27 | 0.00 | 54565059.52 |
Maximum of Months | 0.237513E+09 | 21985138.56 | 0.215528E+09 | 0.296770E+09 | 0.640535E+09 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.584511E+09 | 0.239563E+09 | 0.344948E+09 | 0.163067E+09 | 0.221163E+10 |
February | 0.702953E+09 | 0.309404E+09 | 0.393549E+09 | 0.309335E+09 | 0.154061E+10 |
March | 0.105704E+10 | 0.419414E+09 | 0.637627E+09 | 0.668435E+09 | 0.119559E+10 |
April | 0.124848E+10 | 0.544148E+09 | 0.704333E+09 | 0.111102E+10 | 0.797848E+09 |
May | 0.162988E+10 | 0.712773E+09 | 0.917103E+09 | 0.179074E+10 | 0.437598E+09 |
June | 0.173334E+10 | 0.754970E+09 | 0.978368E+09 | 0.214874E+10 | 0.262781E+09 |
July | 0.181076E+10 | 0.835731E+09 | 0.975034E+09 | 0.233718E+10 | 0.206833E+09 |
August | 0.152676E+10 | 0.657939E+09 | 0.868824E+09 | 0.198626E+10 | 0.258095E+09 |
September | 0.132385E+10 | 0.627922E+09 | 0.695933E+09 | 0.154854E+10 | 0.472986E+09 |
October | 0.866230E+09 | 0.360550E+09 | 0.505680E+09 | 0.680146E+09 | 0.844053E+09 |
November | 0.495872E+09 | 0.160945E+09 | 0.334927E+09 | 0.198799E+09 | 0.134260E+10 |
December | 0.395447E+09 | 0.169327E+09 | 0.226119E+09 | 0.102694E+09 | 0.204143E+10 |
Annual Sum or Average | 0.133751E+11 | 0.579269E+10 | 0.758245E+10 | 0.130450E+11 | 0.116121E+11 |
Minimum of Months | 0.395447E+09 | 0.160945E+09 | 0.226119E+09 | 0.102694E+09 | 0.206833E+09 |
Maximum of Months | 0.181076E+10 | 0.835731E+09 | 0.978368E+09 | 0.233718E+10 | 0.221163E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_FLR_6_WALL_1_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.456883E+09 | 0.312999E+09 | 0.143884E+09 | 0.379610E+09 | 0.524469E+09 |
February | 0.445037E+09 | 0.301961E+09 | 0.143076E+09 | 0.378125E+09 | 0.376568E+09 |
March | 0.422151E+09 | 0.221063E+09 | 0.201088E+09 | 0.343475E+09 | 0.320441E+09 |
April | 0.364051E+09 | 0.166831E+09 | 0.197220E+09 | 0.303305E+09 | 0.220717E+09 |
May | 0.320803E+09 | 89704231.76 | 0.231098E+09 | 0.297459E+09 | 0.125449E+09 |
June | 0.296360E+09 | 59143504.48 | 0.237217E+09 | 0.327117E+09 | 74230623.53 |
July | 0.324981E+09 | 81230907.13 | 0.243750E+09 | 0.373670E+09 | 57455005.75 |
August | 0.360138E+09 | 0.124682E+09 | 0.235456E+09 | 0.423682E+09 | 71778256.11 |
September | 0.420927E+09 | 0.217238E+09 | 0.203689E+09 | 0.469854E+09 | 0.129702E+09 |
October | 0.468824E+09 | 0.295637E+09 | 0.173188E+09 | 0.482775E+09 | 0.227841E+09 |
November | 0.339427E+09 | 0.212502E+09 | 0.126925E+09 | 0.300372E+09 | 0.334850E+09 |
December | 0.373349E+09 | 0.282712E+09 | 90636602.61 | 0.341272E+09 | 0.497390E+09 |
Annual Sum or Average | 0.459293E+10 | 0.236570E+10 | 0.222723E+10 | 0.442071E+10 | 0.296089E+10 |
Minimum of Months | 0.296360E+09 | 59143504.48 | 90636602.61 | 0.297459E+09 | 57455005.75 |
Maximum of Months | 0.468824E+09 | 0.312999E+09 | 0.243750E+09 | 0.482775E+09 | 0.524469E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_1_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 92765322.83 | 0.00 | 92765322.83 | 0.00 | 0.867226E+09 |
February | 0.106227E+09 | 0.00 | 0.106227E+09 | 637782.82 | 0.613995E+09 |
March | 0.176283E+09 | 1490.90 | 0.176281E+09 | 30122757.24 | 0.453050E+09 |
April | 0.197706E+09 | 1585439.33 | 0.196121E+09 | 84247692.13 | 0.284540E+09 |
May | 0.265617E+09 | 10036207.97 | 0.255581E+09 | 0.198398E+09 | 0.141401E+09 |
June | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.291770E+09 | 81240132.77 |
July | 0.291532E+09 | 20068050.55 | 0.271464E+09 | 0.301704E+09 | 66084241.89 |
August | 0.244283E+09 | 4923120.89 | 0.239360E+09 | 0.263230E+09 | 84094159.49 |
September | 0.180921E+09 | 162355.54 | 0.180758E+09 | 0.150923E+09 | 0.166426E+09 |
October | 0.138824E+09 | 0.00 | 0.138824E+09 | 41665366.44 | 0.312759E+09 |
November | 93976305.19 | 0.00 | 93976305.19 | 7753572.75 | 0.511341E+09 |
December | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 0.773614E+09 |
Annual Sum or Average | 0.215192E+10 | 64619455.98 | 0.208730E+10 | 0.137045E+10 | 0.435577E+10 |
Minimum of Months | 62990616.54 | 0.00 | 62990616.54 | 0.00 | 66084241.89 |
Maximum of Months | 0.300795E+09 | 27842790.80 | 0.272952E+09 | 0.301704E+09 | 0.867226E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_NORTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 82997485.82 | 0.00 | 82997485.82 | 0.00 | 0.775898E+09 |
February | 95041552.99 | 0.00 | 95041552.99 | 570626.71 | 0.549343E+09 |
March | 0.157721E+09 | 1333.91 | 0.157719E+09 | 26950945.04 | 0.405346E+09 |
April | 0.176888E+09 | 1418498.57 | 0.175470E+09 | 75376729.36 | 0.254579E+09 |
May | 0.237649E+09 | 8979433.30 | 0.228670E+09 | 0.177507E+09 | 0.126512E+09 |
June | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.261048E+09 | 72685854.60 |
July | 0.260835E+09 | 17954960.87 | 0.242880E+09 | 0.269936E+09 | 59125821.61 |
August | 0.218561E+09 | 4404734.91 | 0.214156E+09 | 0.235513E+09 | 75239363.13 |
September | 0.161871E+09 | 145260.12 | 0.161725E+09 | 0.135031E+09 | 0.148902E+09 |
October | 0.124206E+09 | 0.00 | 0.124206E+09 | 37278161.22 | 0.279826E+09 |
November | 84080956.33 | 0.00 | 84080956.33 | 6937150.92 | 0.457499E+09 |
December | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 0.692138E+09 |
Annual Sum or Average | 0.192533E+10 | 57815272.11 | 0.186752E+10 | 0.122615E+10 | 0.389709E+10 |
Minimum of Months | 56357943.29 | 0.00 | 56357943.29 | 0.00 | 59125821.61 |
Maximum of Months | 0.269122E+09 | 24911050.42 | 0.244211E+09 | 0.269936E+09 | 0.775898E+09 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_FLR_6_WALL_2_SOUTH_WINDOW
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170568E+10 | 0.116852E+10 | 0.537162E+09 | 0.135436E+10 | 0.205561E+10 |
February | 0.166146E+10 | 0.112731E+10 | 0.534145E+09 | 0.135217E+10 | 0.146161E+10 |
March | 0.157601E+10 | 0.825294E+09 | 0.750720E+09 | 0.121813E+10 | 0.120976E+10 |
April | 0.135911E+10 | 0.622831E+09 | 0.736281E+09 | 0.105154E+10 | 0.828016E+09 |
May | 0.119765E+10 | 0.334893E+09 | 0.862759E+09 | 0.971431E+09 | 0.443953E+09 |
June | 0.110640E+10 | 0.220800E+09 | 0.885601E+09 | 0.103913E+10 | 0.258316E+09 |
July | 0.121325E+10 | 0.303259E+09 | 0.909991E+09 | 0.118576E+10 | 0.207131E+09 |
August | 0.134450E+10 | 0.465474E+09 | 0.879028E+09 | 0.139078E+10 | 0.258569E+09 |
September | 0.157145E+10 | 0.811014E+09 | 0.760433E+09 | 0.160969E+10 | 0.483274E+09 |
October | 0.175026E+10 | 0.110370E+10 | 0.646561E+09 | 0.170246E+10 | 0.851158E+09 |
November | 0.126718E+10 | 0.793333E+09 | 0.473848E+09 | 0.105945E+10 | 0.128931E+10 |
December | 0.139382E+10 | 0.105545E+10 | 0.338373E+09 | 0.122595E+10 | 0.192744E+10 |
Annual Sum or Average | 0.171468E+11 | 0.883188E+10 | 0.831490E+10 | 0.151609E+11 | 0.112741E+11 |
Minimum of Months | 0.110640E+10 | 0.220800E+09 | 0.338373E+09 | 0.971431E+09 | 0.207131E+09 |
Maximum of Months | 0.175026E+10 | 0.116852E+10 | 0.909991E+09 | 0.170246E+10 | 0.205561E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 700.67 | 955.40 | 863.80 | 591.77 | 272.03 | 0.00 | 0.00 |
February | 764.74 | 762.39 | 931.56 | 632.07 | 299.49 | 0.00 | 0.00 |
March | 621.91 | 565.22 | 798.14 | 417.95 | 380.19 | 0.00 | 0.00 |
April | 543.37 | 403.64 | 711.24 | 325.93 | 385.30 | 0.00 | 0.00 |
May | 487.78 | 212.44 | 606.52 | 169.60 | 436.93 | 0.00 | 0.00 |
June | 535.21 | 128.46 | 578.99 | 115.55 | 463.44 | 0.00 | 0.00 |
July | 590.73 | 101.70 | 614.42 | 153.58 | 460.84 | 0.00 | 0.00 |
August | 688.54 | 129.43 | 680.89 | 235.73 | 445.16 | 0.00 | 0.00 |
September | 822.84 | 249.82 | 822.35 | 424.41 | 397.94 | 0.00 | 0.00 |
October | 854.31 | 413.67 | 886.38 | 558.94 | 327.44 | 0.00 | 0.00 |
November | 559.92 | 621.00 | 663.13 | 415.16 | 247.97 | 0.00 | 0.00 |
December | 626.39 | 897.59 | 705.87 | 534.51 | 171.36 | 0.00 | 0.00 |
Annual Sum or Average | 649.13 | 451.98 | 737.51 | 379.87 | 357.64 | 0.00 | 0.00 |
Minimum of Months | 487.78 | 101.70 | 578.99 | 115.55 | 171.36 | 0.00 | 0.00 |
Maximum of Months | 854.31 | 955.40 | 931.56 | 632.07 | 463.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1957.88 | 2716.00 | 2432.41 | 1666.38 | 766.03 | 0.00 | 0.00 |
February | 2133.63 | 2197.95 | 2623.21 | 1779.87 | 843.34 | 0.00 | 0.00 |
March | 1726.96 | 1647.83 | 2247.50 | 1176.92 | 1070.58 | 0.00 | 0.00 |
April | 1505.44 | 1207.10 | 2002.79 | 917.81 | 1084.99 | 0.00 | 0.00 |
May | 1331.45 | 671.78 | 1707.93 | 477.58 | 1230.35 | 0.00 | 0.00 |
June | 1466.67 | 419.88 | 1630.40 | 325.37 | 1305.02 | 0.00 | 0.00 |
July | 1624.87 | 334.81 | 1730.18 | 432.47 | 1297.71 | 0.00 | 0.00 |
August | 1904.15 | 422.67 | 1917.35 | 663.80 | 1253.55 | 0.00 | 0.00 |
September | 2286.11 | 775.47 | 2315.69 | 1195.11 | 1120.58 | 0.00 | 0.00 |
October | 2375.86 | 1250.31 | 2495.99 | 1573.95 | 922.04 | 0.00 | 0.00 |
November | 1556.75 | 1804.02 | 1867.32 | 1169.06 | 698.26 | 0.00 | 0.00 |
December | 1748.89 | 2556.61 | 1987.68 | 1505.14 | 482.54 | 0.00 | 0.00 |
Annual Sum or Average | 1799.90 | 1329.69 | 2076.78 | 1069.70 | 1007.08 | 0.00 | 0.00 |
Minimum of Months | 1331.45 | 334.81 | 1630.40 | 325.37 | 482.54 | 0.00 | 0.00 |
Maximum of Months | 2375.86 | 2716.00 | 2623.21 | 1779.87 | 1305.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2577.74 | 3670.53 | 3159.84 | 2164.73 | 995.12 | 0.00 | 0.00 |
February | 2822.43 | 2958.05 | 3407.69 | 2312.15 | 1095.55 | 0.00 | 0.00 |
March | 2279.05 | 2250.45 | 2919.63 | 1528.89 | 1390.74 | 0.00 | 0.00 |
April | 1995.44 | 1652.47 | 2601.74 | 1192.28 | 1409.46 | 0.00 | 0.00 |
May | 1759.59 | 913.65 | 2218.70 | 620.40 | 1598.30 | 0.00 | 0.00 |
June | 1956.43 | 565.69 | 2117.98 | 422.68 | 1695.30 | 0.00 | 0.00 |
July | 2172.38 | 443.42 | 2247.60 | 561.80 | 1685.80 | 0.00 | 0.00 |
August | 2541.43 | 557.32 | 2490.75 | 862.31 | 1628.44 | 0.00 | 0.00 |
September | 3037.60 | 1040.12 | 3008.21 | 1552.52 | 1455.69 | 0.00 | 0.00 |
October | 3132.30 | 1696.50 | 3242.43 | 2044.65 | 1197.78 | 0.00 | 0.00 |
November | 2042.78 | 2469.36 | 2425.76 | 1518.67 | 907.08 | 0.00 | 0.00 |
December | 2302.92 | 3477.90 | 2582.11 | 1955.26 | 626.85 | 0.00 | 0.00 |
Annual Sum or Average | 2382.80 | 1802.62 | 2697.86 | 1389.60 | 1308.26 | 0.00 | 0.00 |
Minimum of Months | 1759.59 | 443.42 | 2117.98 | 422.68 | 626.85 | 0.00 | 0.00 |
Maximum of Months | 3132.30 | 3670.53 | 3407.69 | 2312.15 | 1695.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 129.76 | 582.73 | 279.39 | 161.07 | 118.31 | 0.00 | 0.00 |
February | 195.87 | 467.87 | 342.80 | 202.99 | 139.81 | 0.00 | 0.00 |
March | 224.26 | 326.24 | 347.24 | 153.05 | 194.19 | 0.00 | 0.00 |
April | 347.70 | 226.81 | 417.83 | 201.64 | 216.19 | 0.00 | 0.00 |
May | 368.54 | 118.49 | 397.69 | 144.76 | 252.93 | 0.00 | 0.00 |
June | 473.94 | 68.69 | 439.45 | 163.38 | 276.06 | 0.00 | 0.00 |
July | 526.62 | 52.55 | 470.54 | 195.99 | 274.54 | 0.00 | 0.00 |
August | 494.32 | 66.96 | 439.37 | 186.08 | 253.29 | 0.00 | 0.00 |
September | 423.38 | 134.16 | 409.80 | 201.05 | 208.75 | 0.00 | 0.00 |
October | 295.47 | 235.41 | 348.40 | 187.80 | 160.60 | 0.00 | 0.00 |
November | 142.22 | 371.07 | 234.37 | 120.36 | 114.01 | 0.00 | 0.00 |
December | 125.77 | 536.49 | 218.97 | 143.18 | 75.79 | 0.00 | 0.00 |
Annual Sum or Average | 312.90 | 264.68 | 362.17 | 171.53 | 190.64 | 0.00 | 0.00 |
Minimum of Months | 125.77 | 52.55 | 218.97 | 120.36 | 75.79 | 0.00 | 0.00 |
Maximum of Months | 526.62 | 582.73 | 470.54 | 202.99 | 276.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.36 | 653.12 | 136.27 | 44.31 | 91.96 | 0.00 | 0.00 |
February | 67.42 | 516.02 | 193.64 | 78.28 | 115.36 | 0.00 | 0.00 |
March | 117.99 | 336.10 | 241.68 | 70.58 | 171.10 | 0.00 | 0.00 |
April | 267.77 | 227.32 | 337.68 | 137.81 | 199.86 | 0.00 | 0.00 |
May | 328.47 | 117.99 | 356.26 | 114.25 | 242.00 | 0.00 | 0.00 |
June | 448.96 | 70.15 | 416.76 | 149.06 | 267.70 | 0.00 | 0.00 |
July | 487.28 | 57.82 | 435.18 | 171.60 | 263.58 | 0.00 | 0.00 |
August | 427.08 | 72.09 | 376.98 | 141.02 | 235.96 | 0.00 | 0.00 |
September | 304.89 | 137.15 | 302.60 | 117.36 | 185.25 | 0.00 | 0.00 |
October | 145.52 | 239.90 | 214.39 | 77.51 | 136.88 | 0.00 | 0.00 |
November | 46.00 | 396.21 | 132.13 | 38.44 | 93.69 | 0.00 | 0.00 |
December | 22.31 | 581.35 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Annual Sum or Average | 224.74 | 282.69 | 270.48 | 98.19 | 172.30 | 0.00 | 0.00 |
Minimum of Months | 22.31 | 57.82 | 98.25 | 37.72 | 60.53 | 0.00 | 0.00 |
Maximum of Months | 487.28 | 653.12 | 435.18 | 171.60 | 267.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 112.79 | 142.77 | 136.33 | 93.39 | 42.93 | 0.00 | 0.00 |
February | 118.77 | 129.70 | 147.02 | 99.75 | 47.27 | 0.00 | 0.00 |
March | 94.03 | 100.53 | 125.96 | 65.96 | 60.00 | 0.00 | 0.00 |
April | 78.80 | 86.58 | 112.25 | 51.44 | 60.81 | 0.00 | 0.00 |
May | 63.49 | 53.34 | 95.72 | 26.77 | 68.96 | 0.00 | 0.00 |
June | 71.55 | 36.20 | 91.38 | 18.24 | 73.14 | 0.00 | 0.00 |
July | 80.23 | 29.94 | 96.97 | 24.24 | 72.73 | 0.00 | 0.00 |
August | 96.93 | 35.90 | 107.46 | 37.20 | 70.26 | 0.00 | 0.00 |
September | 120.77 | 59.42 | 129.78 | 66.98 | 62.80 | 0.00 | 0.00 |
October | 124.78 | 90.37 | 139.89 | 88.21 | 51.68 | 0.00 | 0.00 |
November | 82.91 | 117.23 | 104.65 | 65.52 | 39.13 | 0.00 | 0.00 |
December | 99.85 | 136.27 | 111.40 | 84.36 | 27.04 | 0.00 | 0.00 |
Annual Sum or Average | 95.29 | 84.59 | 116.39 | 59.95 | 56.44 | 0.00 | 0.00 |
Minimum of Months | 63.49 | 29.94 | 91.38 | 18.24 | 27.04 | 0.00 | 0.00 |
Maximum of Months | 124.78 | 142.77 | 147.02 | 99.75 | 73.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 199.63 | 21.86 | 0.00 | 21.86 | 0.00 | 0.00 |
February | 0.31 | 160.88 | 27.72 | 0.00 | 27.72 | 0.00 | 0.00 |
March | 7.91 | 103.05 | 41.55 | 0.00 | 41.55 | 0.00 | 0.00 |
April | 21.54 | 67.07 | 48.15 | 0.39 | 47.76 | 0.00 | 0.00 |
May | 47.17 | 32.33 | 62.60 | 2.37 | 60.24 | 0.00 | 0.00 |
June | 72.18 | 18.68 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
July | 71.94 | 14.70 | 68.71 | 4.73 | 63.98 | 0.00 | 0.00 |
August | 62.82 | 18.86 | 57.57 | 1.16 | 56.41 | 0.00 | 0.00 |
September | 37.92 | 39.10 | 44.06 | 0.04 | 44.02 | 0.00 | 0.00 |
October | 10.83 | 71.45 | 32.72 | 0.00 | 32.72 | 0.00 | 0.00 |
November | 2.17 | 120.49 | 22.89 | 0.00 | 22.89 | 0.00 | 0.00 |
December | 0.00 | 175.48 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Annual Sum or Average | 28.07 | 84.78 | 43.08 | 1.29 | 41.78 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 14.70 | 14.85 | 0.00 | 14.85 | 0.00 | 0.00 |
Maximum of Months | 72.18 | 199.63 | 73.26 | 6.78 | 66.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 128.15 | 580.26 | 279.47 | 161.45 | 118.02 | 0.00 | 0.00 |
February | 176.56 | 461.12 | 328.99 | 188.62 | 140.37 | 0.00 | 0.00 |
March | 228.64 | 321.42 | 354.66 | 160.70 | 193.96 | 0.00 | 0.00 |
April | 298.88 | 221.60 | 380.99 | 169.20 | 211.79 | 0.00 | 0.00 |
May | 391.49 | 111.64 | 423.71 | 166.42 | 257.29 | 0.00 | 0.00 |
June | 478.21 | 64.66 | 448.36 | 168.32 | 280.03 | 0.00 | 0.00 |
July | 507.76 | 48.84 | 459.01 | 186.20 | 272.81 | 0.00 | 0.00 |
August | 464.84 | 62.39 | 419.15 | 169.24 | 249.91 | 0.00 | 0.00 |
September | 427.64 | 130.44 | 417.44 | 204.78 | 212.67 | 0.00 | 0.00 |
October | 275.91 | 230.54 | 336.48 | 177.54 | 158.94 | 0.00 | 0.00 |
November | 129.47 | 366.58 | 226.43 | 112.94 | 113.49 | 0.00 | 0.00 |
December | 115.40 | 531.39 | 213.04 | 137.05 | 75.99 | 0.00 | 0.00 |
Annual Sum or Average | 302.59 | 259.97 | 357.42 | 166.73 | 190.70 | 0.00 | 0.00 |
Minimum of Months | 115.40 | 48.84 | 213.04 | 112.94 | 75.99 | 0.00 | 0.00 |
Maximum of Months | 507.76 | 580.26 | 459.01 | 204.78 | 280.03 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 15.50 | 644.30 | 136.36 | 44.69 | 91.67 | 0.00 | 0.00 |
February | 45.57 | 506.48 | 179.82 | 63.90 | 115.92 | 0.00 | 0.00 |
March | 119.10 | 327.87 | 249.11 | 78.24 | 170.87 | 0.00 | 0.00 |
April | 218.95 | 220.97 | 300.83 | 105.37 | 195.46 | 0.00 | 0.00 |
May | 354.06 | 111.37 | 382.28 | 135.92 | 246.36 | 0.00 | 0.00 |
June | 456.31 | 66.79 | 425.67 | 154.00 | 271.67 | 0.00 | 0.00 |
July | 471.93 | 53.07 | 423.65 | 161.81 | 261.85 | 0.00 | 0.00 |
August | 400.74 | 66.14 | 356.76 | 124.18 | 232.58 | 0.00 | 0.00 |
September | 309.22 | 131.74 | 310.25 | 121.09 | 189.17 | 0.00 | 0.00 |
October | 122.54 | 230.91 | 202.48 | 67.26 | 135.22 | 0.00 | 0.00 |
November | 30.83 | 389.27 | 124.19 | 31.02 | 93.16 | 0.00 | 0.00 |
December | 11.79 | 576.42 | 92.32 | 31.59 | 60.74 | 0.00 | 0.00 |
Annual Sum or Average | 213.97 | 276.05 | 265.74 | 93.39 | 172.35 | 0.00 | 0.00 |
Minimum of Months | 11.79 | 53.07 | 92.32 | 31.02 | 60.74 | 0.00 | 0.00 |
Maximum of Months | 471.93 | 644.30 | 425.67 | 161.81 | 271.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.25 | 729.26 | 342.74 | 202.36 | 140.39 | 0.00 | 0.00 |
February | 215.33 | 577.72 | 378.60 | 216.14 | 162.46 | 0.00 | 0.00 |
March | 220.94 | 420.21 | 362.93 | 142.92 | 220.01 | 0.00 | 0.00 |
April | 240.08 | 286.61 | 347.52 | 112.29 | 235.23 | 0.00 | 0.00 |
May | 283.15 | 138.85 | 343.02 | 63.12 | 279.90 | 0.00 | 0.00 |
June | 361.95 | 75.23 | 356.68 | 54.20 | 302.48 | 0.00 | 0.00 |
July | 384.52 | 55.26 | 358.95 | 62.76 | 296.19 | 0.00 | 0.00 |
August | 397.58 | 73.86 | 357.56 | 83.12 | 274.44 | 0.00 | 0.00 |
September | 381.78 | 161.66 | 376.66 | 145.21 | 231.44 | 0.00 | 0.00 |
October | 317.92 | 291.94 | 373.98 | 191.13 | 182.85 | 0.00 | 0.00 |
November | 173.72 | 466.08 | 276.34 | 141.96 | 134.37 | 0.00 | 0.00 |
December | 172.21 | 674.04 | 273.53 | 182.78 | 90.76 | 0.00 | 0.00 |
Annual Sum or Average | 277.49 | 328.08 | 345.51 | 132.70 | 212.81 | 0.00 | 0.00 |
Minimum of Months | 172.21 | 55.26 | 273.53 | 54.20 | 90.76 | 0.00 | 0.00 |
Maximum of Months | 397.58 | 729.26 | 378.60 | 216.14 | 302.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 128.90 | 585.47 | 279.62 | 161.20 | 118.41 | 0.00 | 0.00 |
February | 194.37 | 470.76 | 343.09 | 203.16 | 139.93 | 0.00 | 0.00 |
March | 223.81 | 326.72 | 347.52 | 153.17 | 194.35 | 0.00 | 0.00 |
April | 345.71 | 227.18 | 418.18 | 201.81 | 216.37 | 0.00 | 0.00 |
May | 364.67 | 119.51 | 398.02 | 144.88 | 253.14 | 0.00 | 0.00 |
June | 469.93 | 69.46 | 439.81 | 163.52 | 276.29 | 0.00 | 0.00 |
July | 522.30 | 53.38 | 470.92 | 196.15 | 274.77 | 0.00 | 0.00 |
August | 490.34 | 68.02 | 439.73 | 186.24 | 253.50 | 0.00 | 0.00 |
September | 421.10 | 134.59 | 410.13 | 201.21 | 208.92 | 0.00 | 0.00 |
October | 294.57 | 235.40 | 348.68 | 187.95 | 160.73 | 0.00 | 0.00 |
November | 142.24 | 371.31 | 234.56 | 120.46 | 114.10 | 0.00 | 0.00 |
December | 125.97 | 537.88 | 219.15 | 143.30 | 75.85 | 0.00 | 0.00 |
Annual Sum or Average | 310.90 | 265.69 | 362.46 | 171.67 | 190.80 | 0.00 | 0.00 |
Minimum of Months | 125.97 | 53.38 | 219.15 | 120.46 | 75.85 | 0.00 | 0.00 |
Maximum of Months | 522.30 | 585.47 | 470.92 | 203.16 | 276.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 23.24 | 656.36 | 136.38 | 44.34 | 92.04 | 0.00 | 0.00 |
February | 67.05 | 519.42 | 193.80 | 78.34 | 115.46 | 0.00 | 0.00 |
March | 117.95 | 336.49 | 241.88 | 70.64 | 171.24 | 0.00 | 0.00 |
April | 265.63 | 228.15 | 337.95 | 137.92 | 200.03 | 0.00 | 0.00 |
May | 322.87 | 120.26 | 356.55 | 114.35 | 242.20 | 0.00 | 0.00 |
June | 442.64 | 73.02 | 417.11 | 149.18 | 267.92 | 0.00 | 0.00 |
July | 479.69 | 62.15 | 435.53 | 171.74 | 263.79 | 0.00 | 0.00 |
August | 420.55 | 76.67 | 377.29 | 141.14 | 236.15 | 0.00 | 0.00 |
September | 301.90 | 139.17 | 302.85 | 117.45 | 185.40 | 0.00 | 0.00 |
October | 145.65 | 239.32 | 214.57 | 77.57 | 137.00 | 0.00 | 0.00 |
November | 46.44 | 396.01 | 132.24 | 38.47 | 93.76 | 0.00 | 0.00 |
December | 22.49 | 582.79 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Annual Sum or Average | 222.14 | 284.74 | 270.70 | 98.27 | 172.44 | 0.00 | 0.00 |
Minimum of Months | 22.49 | 62.15 | 98.33 | 37.75 | 60.58 | 0.00 | 0.00 |
Maximum of Months | 479.69 | 656.36 | 435.53 | 171.74 | 267.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 194.07 | 298.13 | 250.17 | 171.39 | 78.79 | 0.00 | 0.00 |
February | 211.25 | 242.62 | 269.80 | 183.06 | 86.74 | 0.00 | 0.00 |
March | 175.23 | 173.31 | 231.15 | 121.05 | 110.11 | 0.00 | 0.00 |
April | 156.65 | 120.97 | 205.99 | 94.40 | 111.59 | 0.00 | 0.00 |
May | 139.26 | 62.52 | 175.66 | 49.12 | 126.54 | 0.00 | 0.00 |
June | 157.47 | 35.08 | 167.69 | 33.46 | 134.22 | 0.00 | 0.00 |
July | 174.05 | 25.87 | 177.95 | 44.48 | 133.47 | 0.00 | 0.00 |
August | 202.16 | 33.88 | 197.20 | 68.27 | 128.93 | 0.00 | 0.00 |
September | 240.12 | 70.13 | 238.17 | 122.92 | 115.25 | 0.00 | 0.00 |
October | 244.42 | 123.38 | 256.71 | 161.88 | 94.83 | 0.00 | 0.00 |
November | 157.73 | 190.83 | 192.05 | 120.24 | 71.82 | 0.00 | 0.00 |
December | 176.43 | 274.73 | 204.43 | 154.80 | 49.63 | 0.00 | 0.00 |
Annual Sum or Average | 185.61 | 137.12 | 213.60 | 110.02 | 103.58 | 0.00 | 0.00 |
Minimum of Months | 139.26 | 25.87 | 167.69 | 33.46 | 49.63 | 0.00 | 0.00 |
Maximum of Months | 244.42 | 298.13 | 269.80 | 183.06 | 134.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1854.56 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 0.65 | 1491.28 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 49.42 | 1029.15 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 158.77 | 690.87 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 367.15 | 347.06 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 586.07 | 210.35 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 591.50 | 165.73 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 515.98 | 211.10 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 300.81 | 414.41 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 69.70 | 733.72 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 11.73 | 1182.01 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1681.18 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 222.32 | 831.19 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 165.73 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 591.50 | 1854.56 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 1891.70 | 191.43 | 0.00 | 191.43 | 0.00 | 0.00 |
February | 0.35 | 1525.82 | 242.69 | 0.00 | 242.69 | 0.00 | 0.00 |
March | 43.98 | 1058.56 | 363.77 | 0.00 | 363.77 | 0.00 | 0.00 |
April | 149.64 | 712.72 | 421.58 | 3.38 | 418.20 | 0.00 | 0.00 |
May | 351.27 | 359.34 | 548.12 | 20.71 | 527.41 | 0.00 | 0.00 |
June | 570.60 | 219.61 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
July | 576.18 | 173.80 | 601.60 | 41.41 | 560.19 | 0.00 | 0.00 |
August | 501.08 | 221.10 | 504.10 | 10.16 | 493.94 | 0.00 | 0.00 |
September | 289.05 | 429.70 | 385.79 | 0.35 | 385.44 | 0.00 | 0.00 |
October | 62.11 | 756.87 | 286.48 | 0.00 | 286.48 | 0.00 | 0.00 |
November | 9.62 | 1214.83 | 200.39 | 0.00 | 200.39 | 0.00 | 0.00 |
December | 0.00 | 1719.88 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Annual Sum or Average | 214.11 | 853.83 | 377.15 | 11.33 | 365.83 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 173.80 | 129.99 | 0.00 | 129.99 | 0.00 | 0.00 |
Maximum of Months | 576.18 | 1891.70 | 641.41 | 59.37 | 582.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 123.35 | 1181.42 | 416.16 | 206.30 | 209.86 | 0.00 | 0.00 |
February | 220.61 | 916.61 | 509.21 | 252.71 | 256.49 | 0.00 | 0.00 |
March | 370.83 | 676.55 | 604.24 | 239.13 | 365.11 | 0.00 | 0.00 |
April | 572.56 | 471.96 | 682.35 | 274.78 | 407.57 | 0.00 | 0.00 |
May | 848.76 | 250.48 | 806.61 | 302.57 | 504.04 | 0.00 | 0.00 |
June | 1062.22 | 155.07 | 874.70 | 322.57 | 552.13 | 0.00 | 0.00 |
July | 1122.03 | 118.16 | 883.34 | 348.27 | 535.07 | 0.00 | 0.00 |
August | 996.03 | 147.49 | 776.51 | 293.65 | 482.86 | 0.00 | 0.00 |
September | 836.05 | 279.80 | 728.26 | 326.11 | 402.14 | 0.00 | 0.00 |
October | 445.59 | 482.43 | 539.38 | 244.99 | 294.39 | 0.00 | 0.00 |
November | 165.74 | 763.12 | 350.89 | 144.08 | 206.81 | 0.00 | 0.00 |
December | 105.78 | 1104.52 | 305.61 | 168.77 | 136.83 | 0.00 | 0.00 |
Annual Sum or Average | 574.40 | 543.99 | 623.64 | 260.32 | 363.33 | 0.00 | 0.00 |
Minimum of Months | 105.78 | 118.16 | 305.61 | 144.08 | 136.83 | 0.00 | 0.00 |
Maximum of Months | 1122.03 | 1181.42 | 883.34 | 348.27 | 552.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 415.54 | 1290.83 | 702.45 | 436.27 | 266.18 | 0.00 | 0.00 |
February | 491.07 | 1016.68 | 769.98 | 465.98 | 303.99 | 0.00 | 0.00 |
March | 459.04 | 755.10 | 713.12 | 308.13 | 404.99 | 0.00 | 0.00 |
April | 465.41 | 525.58 | 668.87 | 241.45 | 427.42 | 0.00 | 0.00 |
May | 502.01 | 264.76 | 635.05 | 132.13 | 502.92 | 0.00 | 0.00 |
June | 610.86 | 155.73 | 646.73 | 105.54 | 541.19 | 0.00 | 0.00 |
July | 654.34 | 122.28 | 659.21 | 127.42 | 531.79 | 0.00 | 0.00 |
August | 704.99 | 155.55 | 674.79 | 177.27 | 497.51 | 0.00 | 0.00 |
September | 730.54 | 307.30 | 738.52 | 313.01 | 425.51 | 0.00 | 0.00 |
October | 655.26 | 529.20 | 751.68 | 412.07 | 339.60 | 0.00 | 0.00 |
November | 378.34 | 835.14 | 557.58 | 306.07 | 251.51 | 0.00 | 0.00 |
December | 394.45 | 1203.61 | 564.95 | 394.06 | 170.89 | 0.00 | 0.00 |
Annual Sum or Average | 538.79 | 594.90 | 673.01 | 283.94 | 389.07 | 0.00 | 0.00 |
Minimum of Months | 378.34 | 122.28 | 557.58 | 105.54 | 170.89 | 0.00 | 0.00 |
Maximum of Months | 730.54 | 1290.83 | 769.98 | 465.98 | 541.19 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187666E+10 | 0.255893E+10 | 0.231361E+10 | 0.158500E+10 | 0.728615E+09 | 0.00 | 0.00 |
February | 0.185006E+10 | 0.184438E+10 | 0.225363E+10 | 0.152910E+10 | 0.724523E+09 | 0.00 | 0.00 |
March | 0.166573E+10 | 0.151387E+10 | 0.213773E+10 | 0.111944E+10 | 0.101829E+10 | 0.00 | 0.00 |
April | 0.140842E+10 | 0.104624E+10 | 0.184352E+10 | 0.844818E+09 | 0.998704E+09 | 0.00 | 0.00 |
May | 0.130647E+10 | 0.568994E+09 | 0.162451E+10 | 0.454254E+09 | 0.117026E+10 | 0.00 | 0.00 |
June | 0.138726E+10 | 0.332980E+09 | 0.150074E+10 | 0.299497E+09 | 0.120124E+10 | 0.00 | 0.00 |
July | 0.158220E+10 | 0.272391E+09 | 0.164567E+10 | 0.411346E+09 | 0.123433E+10 | 0.00 | 0.00 |
August | 0.184420E+10 | 0.346667E+09 | 0.182370E+10 | 0.631377E+09 | 0.119233E+10 | 0.00 | 0.00 |
September | 0.213281E+10 | 0.647540E+09 | 0.213154E+10 | 0.110007E+10 | 0.103146E+10 | 0.00 | 0.00 |
October | 0.228820E+10 | 0.110798E+10 | 0.237408E+10 | 0.149708E+10 | 0.877006E+09 | 0.00 | 0.00 |
November | 0.145132E+10 | 0.160964E+10 | 0.171883E+10 | 0.107609E+10 | 0.642735E+09 | 0.00 | 0.00 |
December | 0.167772E+10 | 0.240409E+10 | 0.189060E+10 | 0.143163E+10 | 0.458975E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.204710E+11 | 0.142537E+11 | 0.232582E+11 | 0.119797E+11 | 0.112785E+11 | 0.00 | 0.00 |
Minimum of Months | 0.130647E+10 | 0.272391E+09 | 0.150074E+10 | 0.299497E+09 | 0.458975E+09 | 0.00 | 0.00 |
Maximum of Months | 0.228820E+10 | 0.255893E+10 | 0.237408E+10 | 0.158500E+10 | 0.123433E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.524397E+10 | 0.727455E+10 | 0.651498E+10 | 0.446324E+10 | 0.205173E+10 | 0.00 | 0.00 |
February | 0.516168E+10 | 0.531729E+10 | 0.634606E+10 | 0.430585E+10 | 0.204021E+10 | 0.00 | 0.00 |
March | 0.462548E+10 | 0.441354E+10 | 0.601971E+10 | 0.315228E+10 | 0.286743E+10 | 0.00 | 0.00 |
April | 0.390209E+10 | 0.312880E+10 | 0.519124E+10 | 0.237895E+10 | 0.281228E+10 | 0.00 | 0.00 |
May | 0.356615E+10 | 0.179929E+10 | 0.457452E+10 | 0.127915E+10 | 0.329538E+10 | 0.00 | 0.00 |
June | 0.380160E+10 | 0.108834E+10 | 0.422599E+10 | 0.843364E+09 | 0.338262E+10 | 0.00 | 0.00 |
July | 0.435205E+10 | 0.896754E+09 | 0.463411E+10 | 0.115832E+10 | 0.347578E+10 | 0.00 | 0.00 |
August | 0.510006E+10 | 0.113209E+10 | 0.513543E+10 | 0.177792E+10 | 0.335752E+10 | 0.00 | 0.00 |
September | 0.592559E+10 | 0.201003E+10 | 0.600226E+10 | 0.309773E+10 | 0.290453E+10 | 0.00 | 0.00 |
October | 0.636350E+10 | 0.334883E+10 | 0.668526E+10 | 0.421567E+10 | 0.246959E+10 | 0.00 | 0.00 |
November | 0.403510E+10 | 0.467601E+10 | 0.484010E+10 | 0.303020E+10 | 0.180990E+10 | 0.00 | 0.00 |
December | 0.468424E+10 | 0.684763E+10 | 0.532381E+10 | 0.403137E+10 | 0.129244E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.567615E+11 | 0.419331E+11 | 0.654935E+11 | 0.337340E+11 | 0.317594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.356615E+10 | 0.896754E+09 | 0.422599E+10 | 0.843364E+09 | 0.129244E+10 | 0.00 | 0.00 |
Maximum of Months | 0.636350E+10 | 0.727455E+10 | 0.668526E+10 | 0.446324E+10 | 0.347578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.690423E+10 | 0.983114E+10 | 0.846332E+10 | 0.579801E+10 | 0.266532E+10 | 0.00 | 0.00 |
February | 0.682803E+10 | 0.715611E+10 | 0.824389E+10 | 0.559355E+10 | 0.265035E+10 | 0.00 | 0.00 |
March | 0.610421E+10 | 0.602761E+10 | 0.781994E+10 | 0.409499E+10 | 0.372496E+10 | 0.00 | 0.00 |
April | 0.517219E+10 | 0.428320E+10 | 0.674371E+10 | 0.309039E+10 | 0.365332E+10 | 0.00 | 0.00 |
May | 0.471289E+10 | 0.244712E+10 | 0.594257E+10 | 0.166169E+10 | 0.428088E+10 | 0.00 | 0.00 |
June | 0.507107E+10 | 0.146626E+10 | 0.548980E+10 | 0.109558E+10 | 0.439422E+10 | 0.00 | 0.00 |
July | 0.581849E+10 | 0.118765E+10 | 0.601997E+10 | 0.150473E+10 | 0.451524E+10 | 0.00 | 0.00 |
August | 0.680695E+10 | 0.149272E+10 | 0.667122E+10 | 0.230961E+10 | 0.436160E+10 | 0.00 | 0.00 |
September | 0.787346E+10 | 0.269599E+10 | 0.779728E+10 | 0.402413E+10 | 0.377315E+10 | 0.00 | 0.00 |
October | 0.838956E+10 | 0.454392E+10 | 0.868453E+10 | 0.547639E+10 | 0.320814E+10 | 0.00 | 0.00 |
November | 0.529490E+10 | 0.640057E+10 | 0.628756E+10 | 0.393640E+10 | 0.235116E+10 | 0.00 | 0.00 |
December | 0.616815E+10 | 0.931521E+10 | 0.691593E+10 | 0.523697E+10 | 0.167896E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.751441E+11 | 0.568475E+11 | 0.850797E+11 | 0.438224E+11 | 0.412573E+11 | 0.00 | 0.00 |
Minimum of Months | 0.471289E+10 | 0.118765E+10 | 0.548980E+10 | 0.109558E+10 | 0.167896E+10 | 0.00 | 0.00 |
Maximum of Months | 0.838956E+10 | 0.983114E+10 | 0.868453E+10 | 0.579801E+10 | 0.451524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.347543E+09 | 0.156078E+10 | 0.748309E+09 | 0.431415E+09 | 0.316894E+09 | 0.00 | 0.00 |
February | 0.473859E+09 | 0.113187E+10 | 0.829313E+09 | 0.491083E+09 | 0.338230E+09 | 0.00 | 0.00 |
March | 0.600660E+09 | 0.873789E+09 | 0.930041E+09 | 0.409925E+09 | 0.520116E+09 | 0.00 | 0.00 |
April | 0.901251E+09 | 0.587883E+09 | 0.108302E+10 | 0.522652E+09 | 0.560370E+09 | 0.00 | 0.00 |
May | 0.987098E+09 | 0.317363E+09 | 0.106517E+10 | 0.387727E+09 | 0.677444E+09 | 0.00 | 0.00 |
June | 0.122844E+10 | 0.178049E+09 | 0.113905E+10 | 0.423494E+09 | 0.715557E+09 | 0.00 | 0.00 |
July | 0.141049E+10 | 0.140762E+09 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
August | 0.132400E+10 | 0.179359E+09 | 0.117681E+10 | 0.498404E+09 | 0.678406E+09 | 0.00 | 0.00 |
September | 0.109740E+10 | 0.347740E+09 | 0.106219E+10 | 0.521121E+09 | 0.541072E+09 | 0.00 | 0.00 |
October | 0.791398E+09 | 0.630514E+09 | 0.933147E+09 | 0.503000E+09 | 0.430148E+09 | 0.00 | 0.00 |
November | 0.368640E+09 | 0.961802E+09 | 0.607482E+09 | 0.311969E+09 | 0.295513E+09 | 0.00 | 0.00 |
December | 0.336874E+09 | 0.143694E+10 | 0.586489E+09 | 0.383497E+09 | 0.202992E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.986766E+10 | 0.834685E+10 | 0.114213E+11 | 0.540923E+10 | 0.601208E+10 | 0.00 | 0.00 |
Minimum of Months | 0.336874E+09 | 0.140762E+09 | 0.586489E+09 | 0.311969E+09 | 0.202992E+09 | 0.00 | 0.00 |
Maximum of Months | 0.141049E+10 | 0.156078E+10 | 0.126028E+10 | 0.524942E+09 | 0.735340E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 62558474.85 | 0.174933E+10 | 0.364990E+09 | 0.118673E+09 | 0.246317E+09 | 0.00 | 0.00 |
February | 0.163098E+09 | 0.124836E+10 | 0.468450E+09 | 0.189369E+09 | 0.279081E+09 | 0.00 | 0.00 |
March | 0.316013E+09 | 0.900199E+09 | 0.647318E+09 | 0.189044E+09 | 0.458274E+09 | 0.00 | 0.00 |
April | 0.694065E+09 | 0.589218E+09 | 0.875254E+09 | 0.357208E+09 | 0.518045E+09 | 0.00 | 0.00 |
May | 0.879787E+09 | 0.316027E+09 | 0.954195E+09 | 0.306014E+09 | 0.648181E+09 | 0.00 | 0.00 |
June | 0.116371E+10 | 0.181824E+09 | 0.108025E+10 | 0.386366E+09 | 0.693885E+09 | 0.00 | 0.00 |
July | 0.130513E+10 | 0.154856E+09 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
August | 0.114388E+10 | 0.193090E+09 | 0.100970E+10 | 0.377708E+09 | 0.631991E+09 | 0.00 | 0.00 |
September | 0.790281E+09 | 0.355482E+09 | 0.784351E+09 | 0.304189E+09 | 0.480163E+09 | 0.00 | 0.00 |
October | 0.389769E+09 | 0.642536E+09 | 0.574235E+09 | 0.207605E+09 | 0.366630E+09 | 0.00 | 0.00 |
November | 0.119228E+09 | 0.102698E+10 | 0.342478E+09 | 99641378.41 | 0.242837E+09 | 0.00 | 0.00 |
December | 59755225.58 | 0.155709E+10 | 0.263144E+09 | 0.101017E+09 | 0.162127E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.708728E+10 | 0.891499E+10 | 0.852994E+10 | 0.309645E+10 | 0.543350E+10 | 0.00 | 0.00 |
Minimum of Months | 59755225.58 | 0.154856E+09 | 0.263144E+09 | 99641378.41 | 0.162127E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130513E+10 | 0.174933E+10 | 0.116558E+10 | 0.459611E+09 | 0.705966E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302107E+09 | 0.382388E+09 | 0.365134E+09 | 0.250144E+09 | 0.114990E+09 | 0.00 | 0.00 |
February | 0.287326E+09 | 0.313767E+09 | 0.355667E+09 | 0.241323E+09 | 0.114344E+09 | 0.00 | 0.00 |
March | 0.251859E+09 | 0.269247E+09 | 0.337377E+09 | 0.176670E+09 | 0.160706E+09 | 0.00 | 0.00 |
April | 0.204238E+09 | 0.224411E+09 | 0.290945E+09 | 0.133329E+09 | 0.157615E+09 | 0.00 | 0.00 |
May | 0.170063E+09 | 0.142862E+09 | 0.256381E+09 | 71690305.69 | 0.184690E+09 | 0.00 | 0.00 |
June | 0.185448E+09 | 93823946.37 | 0.236847E+09 | 47266620.90 | 0.189580E+09 | 0.00 | 0.00 |
July | 0.214879E+09 | 80185750.42 | 0.259720E+09 | 64918548.99 | 0.194801E+09 | 0.00 | 0.00 |
August | 0.259614E+09 | 96161880.03 | 0.287817E+09 | 99643893.91 | 0.188173E+09 | 0.00 | 0.00 |
September | 0.313045E+09 | 0.154020E+09 | 0.336399E+09 | 0.173613E+09 | 0.162786E+09 | 0.00 | 0.00 |
October | 0.334217E+09 | 0.242040E+09 | 0.374678E+09 | 0.236269E+09 | 0.138409E+09 | 0.00 | 0.00 |
November | 0.214900E+09 | 0.303850E+09 | 0.271265E+09 | 0.169828E+09 | 0.101436E+09 | 0.00 | 0.00 |
December | 0.267445E+09 | 0.364994E+09 | 0.298375E+09 | 0.225939E+09 | 72435442.79 | 0.00 | 0.00 |
Annual Sum or Average | 0.300514E+10 | 0.266775E+10 | 0.367060E+10 | 0.189064E+10 | 0.177997E+10 | 0.00 | 0.00 |
Minimum of Months | 0.170063E+09 | 80185750.42 | 0.236847E+09 | 47266620.90 | 72435442.79 | 0.00 | 0.00 |
Maximum of Months | 0.334217E+09 | 0.382388E+09 | 0.374678E+09 | 0.250144E+09 | 0.194801E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.534685E+09 | 58558983.50 | 0.00 | 58558983.50 | 0.00 | 0.00 |
February | 751911.60 | 0.389196E+09 | 67056690.67 | 0.00 | 67056690.67 | 0.00 | 0.00 |
March | 21183314.51 | 0.276003E+09 | 0.111280E+09 | 941.15 | 0.111279E+09 | 0.00 | 0.00 |
April | 55838017.55 | 0.173857E+09 | 0.124804E+09 | 1000823.50 | 0.123803E+09 | 0.00 | 0.00 |
May | 0.126330E+09 | 86594454.86 | 0.167674E+09 | 6335450.78 | 0.161338E+09 | 0.00 | 0.00 |
June | 0.187087E+09 | 48420689.41 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
July | 0.192691E+09 | 39369794.82 | 0.184032E+09 | 12668145.87 | 0.171364E+09 | 0.00 | 0.00 |
August | 0.168248E+09 | 50523491.14 | 0.154206E+09 | 3107766.42 | 0.151098E+09 | 0.00 | 0.00 |
September | 98298327.32 | 0.101359E+09 | 0.114208E+09 | 102488.46 | 0.114105E+09 | 0.00 | 0.00 |
October | 29016544.80 | 0.191383E+09 | 87633982.09 | 0.00 | 87633982.09 | 0.00 | 0.00 |
November | 5631647.49 | 0.312313E+09 | 59323427.52 | 0.00 | 59323427.52 | 0.00 | 0.00 |
December | 0.00 | 0.470015E+09 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.885075E+09 | 0.267372E+10 | 0.135842E+10 | 40791640.04 | 0.131763E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 39369794.82 | 39763419.80 | 0.00 | 39763419.80 | 0.00 | 0.00 |
Maximum of Months | 0.192691E+09 | 0.534685E+09 | 0.189880E+09 | 17576023.85 | 0.172304E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.343237E+09 | 0.155418E+10 | 0.748545E+09 | 0.432434E+09 | 0.316111E+09 | 0.00 | 0.00 |
February | 0.427127E+09 | 0.111555E+10 | 0.795886E+09 | 0.456300E+09 | 0.339586E+09 | 0.00 | 0.00 |
March | 0.612401E+09 | 0.860898E+09 | 0.949929E+09 | 0.430432E+09 | 0.519498E+09 | 0.00 | 0.00 |
April | 0.774697E+09 | 0.574391E+09 | 0.987526E+09 | 0.438565E+09 | 0.548961E+09 | 0.00 | 0.00 |
May | 0.104856E+10 | 0.299027E+09 | 0.113487E+10 | 0.445751E+09 | 0.689117E+09 | 0.00 | 0.00 |
June | 0.123952E+10 | 0.167592E+09 | 0.116214E+10 | 0.436297E+09 | 0.725840E+09 | 0.00 | 0.00 |
July | 0.135998E+10 | 0.130803E+09 | 0.122942E+10 | 0.498717E+09 | 0.730702E+09 | 0.00 | 0.00 |
August | 0.124502E+10 | 0.167097E+09 | 0.112265E+10 | 0.453303E+09 | 0.669350E+09 | 0.00 | 0.00 |
September | 0.110845E+10 | 0.338094E+09 | 0.108201E+10 | 0.530786E+09 | 0.551228E+09 | 0.00 | 0.00 |
October | 0.738984E+09 | 0.617491E+09 | 0.901231E+09 | 0.475534E+09 | 0.425696E+09 | 0.00 | 0.00 |
November | 0.335586E+09 | 0.950167E+09 | 0.586899E+09 | 0.292740E+09 | 0.294159E+09 | 0.00 | 0.00 |
December | 0.309077E+09 | 0.142328E+10 | 0.570618E+09 | 0.367081E+09 | 0.203537E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.954263E+10 | 0.819857E+10 | 0.112717E+11 | 0.525794E+10 | 0.601379E+10 | 0.00 | 0.00 |
Minimum of Months | 0.309077E+09 | 0.130803E+09 | 0.570618E+09 | 0.292740E+09 | 0.203537E+09 | 0.00 | 0.00 |
Maximum of Months | 0.135998E+10 | 0.155418E+10 | 0.122942E+10 | 0.530786E+09 | 0.730702E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 41524403.39 | 0.172568E+10 | 0.365226E+09 | 0.119692E+09 | 0.245534E+09 | 0.00 | 0.00 |
February | 0.110244E+09 | 0.122528E+10 | 0.435023E+09 | 0.154586E+09 | 0.280437E+09 | 0.00 | 0.00 |
March | 0.318994E+09 | 0.878157E+09 | 0.667206E+09 | 0.209551E+09 | 0.457655E+09 | 0.00 | 0.00 |
April | 0.567520E+09 | 0.572762E+09 | 0.779757E+09 | 0.273121E+09 | 0.506636E+09 | 0.00 | 0.00 |
May | 0.948307E+09 | 0.298283E+09 | 0.102389E+10 | 0.364038E+09 | 0.659854E+09 | 0.00 | 0.00 |
June | 0.118275E+10 | 0.173121E+09 | 0.110334E+10 | 0.399169E+09 | 0.704169E+09 | 0.00 | 0.00 |
July | 0.126403E+10 | 0.142141E+09 | 0.113471E+10 | 0.433385E+09 | 0.701329E+09 | 0.00 | 0.00 |
August | 0.107334E+10 | 0.177146E+09 | 0.955542E+09 | 0.332608E+09 | 0.622934E+09 | 0.00 | 0.00 |
September | 0.801506E+09 | 0.341472E+09 | 0.804173E+09 | 0.313854E+09 | 0.490319E+09 | 0.00 | 0.00 |
October | 0.328208E+09 | 0.618457E+09 | 0.542318E+09 | 0.180140E+09 | 0.362178E+09 | 0.00 | 0.00 |
November | 79913905.14 | 0.100899E+10 | 0.321895E+09 | 80412113.67 | 0.241483E+09 | 0.00 | 0.00 |
December | 31575722.18 | 0.154388E+10 | 0.247273E+09 | 84600328.40 | 0.162673E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.674791E+10 | 0.870537E+10 | 0.838036E+10 | 0.294516E+10 | 0.543520E+10 | 0.00 | 0.00 |
Minimum of Months | 31575722.18 | 0.142141E+09 | 0.247273E+09 | 80412113.67 | 0.162673E+09 | 0.00 | 0.00 |
Maximum of Months | 0.126403E+10 | 0.172568E+10 | 0.113471E+10 | 0.433385E+09 | 0.704169E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.472067E+09 | 0.195325E+10 | 0.918002E+09 | 0.541992E+09 | 0.376010E+09 | 0.00 | 0.00 |
February | 0.520932E+09 | 0.139761E+10 | 0.915899E+09 | 0.522880E+09 | 0.393019E+09 | 0.00 | 0.00 |
March | 0.591771E+09 | 0.112548E+10 | 0.972071E+09 | 0.382798E+09 | 0.589274E+09 | 0.00 | 0.00 |
April | 0.622299E+09 | 0.742903E+09 | 0.900763E+09 | 0.291055E+09 | 0.609707E+09 | 0.00 | 0.00 |
May | 0.758402E+09 | 0.371891E+09 | 0.918743E+09 | 0.169058E+09 | 0.749685E+09 | 0.00 | 0.00 |
June | 0.938165E+09 | 0.194985E+09 | 0.924524E+09 | 0.140489E+09 | 0.784035E+09 | 0.00 | 0.00 |
July | 0.102990E+10 | 0.148011E+09 | 0.961416E+09 | 0.168104E+09 | 0.793313E+09 | 0.00 | 0.00 |
August | 0.106488E+10 | 0.197815E+09 | 0.957681E+09 | 0.222633E+09 | 0.735048E+09 | 0.00 | 0.00 |
September | 0.989568E+09 | 0.419028E+09 | 0.976296E+09 | 0.376394E+09 | 0.599902E+09 | 0.00 | 0.00 |
October | 0.851512E+09 | 0.781927E+09 | 0.100167E+10 | 0.511928E+09 | 0.489739E+09 | 0.00 | 0.00 |
November | 0.450270E+09 | 0.120808E+10 | 0.716270E+09 | 0.367971E+09 | 0.348299E+09 | 0.00 | 0.00 |
December | 0.461251E+09 | 0.180536E+10 | 0.732636E+09 | 0.489548E+09 | 0.243088E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.875101E+10 | 0.103463E+11 | 0.108960E+11 | 0.418485E+10 | 0.671112E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450270E+09 | 0.148011E+09 | 0.716270E+09 | 0.140489E+09 | 0.243088E+09 | 0.00 | 0.00 |
Maximum of Months | 0.106488E+10 | 0.195325E+10 | 0.100167E+10 | 0.541992E+09 | 0.793313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.345255E+09 | 0.156812E+10 | 0.748923E+09 | 0.431769E+09 | 0.317154E+09 | 0.00 | 0.00 |
February | 0.470219E+09 | 0.113886E+10 | 0.829993E+09 | 0.491486E+09 | 0.338508E+09 | 0.00 | 0.00 |
March | 0.599463E+09 | 0.875074E+09 | 0.930804E+09 | 0.410261E+09 | 0.520543E+09 | 0.00 | 0.00 |
April | 0.896078E+09 | 0.588840E+09 | 0.108391E+10 | 0.523081E+09 | 0.560830E+09 | 0.00 | 0.00 |
May | 0.976733E+09 | 0.320092E+09 | 0.106604E+10 | 0.388045E+09 | 0.678000E+09 | 0.00 | 0.00 |
June | 0.121805E+10 | 0.180050E+09 | 0.113998E+10 | 0.423841E+09 | 0.716144E+09 | 0.00 | 0.00 |
July | 0.139892E+10 | 0.142969E+09 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
August | 0.131333E+10 | 0.182192E+09 | 0.117778E+10 | 0.498813E+09 | 0.678963E+09 | 0.00 | 0.00 |
September | 0.109148E+10 | 0.348855E+09 | 0.106306E+10 | 0.521548E+09 | 0.541516E+09 | 0.00 | 0.00 |
October | 0.788985E+09 | 0.630494E+09 | 0.933913E+09 | 0.503412E+09 | 0.430500E+09 | 0.00 | 0.00 |
November | 0.368693E+09 | 0.962445E+09 | 0.607981E+09 | 0.312225E+09 | 0.295756E+09 | 0.00 | 0.00 |
December | 0.337396E+09 | 0.144066E+10 | 0.586970E+09 | 0.383812E+09 | 0.203158E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.980461E+10 | 0.837864E+10 | 0.114307E+11 | 0.541366E+10 | 0.601701E+10 | 0.00 | 0.00 |
Minimum of Months | 0.337396E+09 | 0.142969E+09 | 0.586970E+09 | 0.312225E+09 | 0.203158E+09 | 0.00 | 0.00 |
Maximum of Months | 0.139892E+10 | 0.156812E+10 | 0.126132E+10 | 0.525373E+09 | 0.735943E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 62238881.19 | 0.175798E+10 | 0.365289E+09 | 0.118770E+09 | 0.246519E+09 | 0.00 | 0.00 |
February | 0.162201E+09 | 0.125658E+10 | 0.468835E+09 | 0.189524E+09 | 0.279310E+09 | 0.00 | 0.00 |
March | 0.315926E+09 | 0.901243E+09 | 0.647849E+09 | 0.189199E+09 | 0.458650E+09 | 0.00 | 0.00 |
April | 0.688522E+09 | 0.591364E+09 | 0.875972E+09 | 0.357501E+09 | 0.518470E+09 | 0.00 | 0.00 |
May | 0.864783E+09 | 0.322102E+09 | 0.954978E+09 | 0.306265E+09 | 0.648713E+09 | 0.00 | 0.00 |
June | 0.114733E+10 | 0.189265E+09 | 0.108114E+10 | 0.386683E+09 | 0.694454E+09 | 0.00 | 0.00 |
July | 0.128481E+10 | 0.166457E+09 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
August | 0.112641E+10 | 0.205364E+09 | 0.101053E+10 | 0.378018E+09 | 0.632509E+09 | 0.00 | 0.00 |
September | 0.782532E+09 | 0.360726E+09 | 0.784995E+09 | 0.304438E+09 | 0.480556E+09 | 0.00 | 0.00 |
October | 0.390097E+09 | 0.640984E+09 | 0.574706E+09 | 0.207776E+09 | 0.366931E+09 | 0.00 | 0.00 |
November | 0.120380E+09 | 0.102646E+10 | 0.342759E+09 | 99723118.67 | 0.243036E+09 | 0.00 | 0.00 |
December | 60234400.38 | 0.156095E+10 | 0.263360E+09 | 0.101100E+09 | 0.162260E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.700546E+10 | 0.897948E+10 | 0.853694E+10 | 0.309899E+10 | 0.543795E+10 | 0.00 | 0.00 |
Minimum of Months | 60234400.38 | 0.166457E+09 | 0.263360E+09 | 99723118.67 | 0.162260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.128481E+10 | 0.175798E+10 | 0.116653E+10 | 0.459988E+09 | 0.706545E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519799E+09 | 0.798500E+09 | 0.670062E+09 | 0.459043E+09 | 0.211020E+09 | 0.00 | 0.00 |
February | 0.511061E+09 | 0.586948E+09 | 0.652690E+09 | 0.442855E+09 | 0.209835E+09 | 0.00 | 0.00 |
March | 0.469340E+09 | 0.464201E+09 | 0.619124E+09 | 0.324210E+09 | 0.294914E+09 | 0.00 | 0.00 |
April | 0.406026E+09 | 0.313546E+09 | 0.533916E+09 | 0.244674E+09 | 0.289242E+09 | 0.00 | 0.00 |
May | 0.373003E+09 | 0.167465E+09 | 0.470488E+09 | 0.131560E+09 | 0.338928E+09 | 0.00 | 0.00 |
June | 0.408173E+09 | 90935204.97 | 0.434641E+09 | 86739625.34 | 0.347901E+09 | 0.00 | 0.00 |
July | 0.466169E+09 | 69285189.29 | 0.476616E+09 | 0.119133E+09 | 0.357483E+09 | 0.00 | 0.00 |
August | 0.541469E+09 | 90749864.11 | 0.528177E+09 | 0.182858E+09 | 0.345319E+09 | 0.00 | 0.00 |
September | 0.622397E+09 | 0.181766E+09 | 0.617330E+09 | 0.318600E+09 | 0.298730E+09 | 0.00 | 0.00 |
October | 0.654653E+09 | 0.330461E+09 | 0.687576E+09 | 0.433580E+09 | 0.253996E+09 | 0.00 | 0.00 |
November | 0.408827E+09 | 0.494636E+09 | 0.497802E+09 | 0.311655E+09 | 0.186148E+09 | 0.00 | 0.00 |
December | 0.472537E+09 | 0.735824E+09 | 0.547551E+09 | 0.414624E+09 | 0.132927E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.585346E+10 | 0.432432E+10 | 0.673597E+10 | 0.346953E+10 | 0.326644E+10 | 0.00 | 0.00 |
Minimum of Months | 0.373003E+09 | 69285189.29 | 0.434641E+09 | 86739625.34 | 0.132927E+09 | 0.00 | 0.00 |
Maximum of Months | 0.654653E+09 | 0.798500E+09 | 0.687576E+09 | 0.459043E+09 | 0.357483E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.496726E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 1579426.63 | 0.360770E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.132369E+09 | 0.275649E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.411541E+09 | 0.179074E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.983367E+09 | 0.929553E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.151909E+10 | 0.545230E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.158428E+10 | 0.443899E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.138201E+10 | 0.565420E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.779694E+09 | 0.107416E+10 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.186682E+09 | 0.196519E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 30416539.70 | 0.306377E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.450288E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.701103E+10 | 0.262123E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.443899E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.158428E+10 | 0.496726E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.506672E+10 | 0.512724E+09 | 0.00 | 0.512724E+09 | 0.00 | 0.00 |
February | 841733.26 | 0.369126E+10 | 0.587127E+09 | 0.00 | 0.587127E+09 | 0.00 | 0.00 |
March | 0.117806E+09 | 0.283525E+10 | 0.974333E+09 | 8240.37 | 0.974325E+09 | 0.00 | 0.00 |
April | 0.387859E+09 | 0.184736E+10 | 0.109274E+10 | 8762896.07 | 0.108398E+10 | 0.00 | 0.00 |
May | 0.940840E+09 | 0.962452E+09 | 0.146810E+10 | 55471216.06 | 0.141263E+10 | 0.00 | 0.00 |
June | 0.147900E+10 | 0.569232E+09 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
July | 0.154323E+10 | 0.465503E+09 | 0.161133E+10 | 0.110918E+09 | 0.150041E+10 | 0.00 | 0.00 |
August | 0.134210E+10 | 0.592197E+09 | 0.135018E+10 | 27210626.09 | 0.132297E+10 | 0.00 | 0.00 |
September | 0.749205E+09 | 0.111379E+10 | 0.999969E+09 | 897356.79 | 0.999072E+09 | 0.00 | 0.00 |
October | 0.166346E+09 | 0.202721E+10 | 0.767296E+09 | 0.00 | 0.767296E+09 | 0.00 | 0.00 |
November | 24933336.88 | 0.314884E+10 | 0.519417E+09 | 0.00 | 0.519417E+09 | 0.00 | 0.00 |
December | 0.00 | 0.460652E+10 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.675216E+10 | 0.269263E+11 | 0.118939E+11 | 0.357159E+09 | 0.115367E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.465503E+09 | 0.348156E+09 | 0.00 | 0.348156E+09 | 0.00 | 0.00 |
Maximum of Months | 0.154323E+10 | 0.506672E+10 | 0.166253E+10 | 0.153890E+09 | 0.150864E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.330369E+09 | 0.316431E+10 | 0.111464E+10 | 0.552562E+09 | 0.562081E+09 | 0.00 | 0.00 |
February | 0.533693E+09 | 0.221747E+10 | 0.123187E+10 | 0.611366E+09 | 0.620503E+09 | 0.00 | 0.00 |
March | 0.993225E+09 | 0.181207E+10 | 0.161839E+10 | 0.640478E+09 | 0.977909E+09 | 0.00 | 0.00 |
April | 0.148409E+10 | 0.122332E+10 | 0.176864E+10 | 0.712232E+09 | 0.105641E+10 | 0.00 | 0.00 |
May | 0.227332E+10 | 0.670885E+09 | 0.216042E+10 | 0.810402E+09 | 0.135001E+10 | 0.00 | 0.00 |
June | 0.275326E+10 | 0.401943E+09 | 0.226721E+10 | 0.836098E+09 | 0.143111E+10 | 0.00 | 0.00 |
July | 0.300525E+10 | 0.316475E+09 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
August | 0.266776E+10 | 0.395049E+09 | 0.207979E+10 | 0.786509E+09 | 0.129328E+10 | 0.00 | 0.00 |
September | 0.216703E+10 | 0.725247E+09 | 0.188764E+10 | 0.845288E+09 | 0.104235E+10 | 0.00 | 0.00 |
October | 0.119347E+10 | 0.129214E+10 | 0.144467E+10 | 0.656187E+09 | 0.788485E+09 | 0.00 | 0.00 |
November | 0.429598E+09 | 0.197801E+10 | 0.909504E+09 | 0.373447E+09 | 0.536057E+09 | 0.00 | 0.00 |
December | 0.283317E+09 | 0.295834E+10 | 0.818534E+09 | 0.452039E+09 | 0.366494E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.181144E+11 | 0.171553E+11 | 0.196673E+11 | 0.820941E+10 | 0.114578E+11 | 0.00 | 0.00 |
Minimum of Months | 0.283317E+09 | 0.316475E+09 | 0.818534E+09 | 0.373447E+09 | 0.366494E+09 | 0.00 | 0.00 |
Maximum of Months | 0.300525E+10 | 0.316431E+10 | 0.236594E+10 | 0.932807E+09 | 0.143314E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111299E+10 | 0.345736E+10 | 0.188144E+10 | 0.116852E+10 | 0.712925E+09 | 0.00 | 0.00 |
February | 0.118799E+10 | 0.245956E+10 | 0.186272E+10 | 0.112731E+10 | 0.735414E+09 | 0.00 | 0.00 |
March | 0.122950E+10 | 0.202245E+10 | 0.191002E+10 | 0.825297E+09 | 0.108472E+10 | 0.00 | 0.00 |
April | 0.120634E+10 | 0.136232E+10 | 0.173371E+10 | 0.625835E+09 | 0.110787E+10 | 0.00 | 0.00 |
May | 0.134459E+10 | 0.709120E+09 | 0.170092E+10 | 0.353908E+09 | 0.134701E+10 | 0.00 | 0.00 |
June | 0.158336E+10 | 0.403650E+09 | 0.167632E+10 | 0.273554E+09 | 0.140276E+10 | 0.00 | 0.00 |
July | 0.175258E+10 | 0.327513E+09 | 0.176562E+10 | 0.341282E+09 | 0.142433E+10 | 0.00 | 0.00 |
August | 0.188826E+10 | 0.416631E+09 | 0.180735E+10 | 0.474802E+09 | 0.133254E+10 | 0.00 | 0.00 |
September | 0.189355E+10 | 0.796510E+09 | 0.191424E+10 | 0.811322E+09 | 0.110292E+10 | 0.00 | 0.00 |
October | 0.175506E+10 | 0.141740E+10 | 0.201329E+10 | 0.110370E+10 | 0.909592E+09 | 0.00 | 0.00 |
November | 0.980669E+09 | 0.216467E+10 | 0.144524E+10 | 0.793333E+09 | 0.651906E+09 | 0.00 | 0.00 |
December | 0.105650E+10 | 0.322374E+10 | 0.151317E+10 | 0.105545E+10 | 0.457722E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.169914E+11 | 0.187609E+11 | 0.212240E+11 | 0.895431E+10 | 0.122697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.980669E+09 | 0.327513E+09 | 0.144524E+10 | 0.273554E+09 | 0.457722E+09 | 0.00 | 0.00 |
Maximum of Months | 0.189355E+10 | 0.345736E+10 | 0.201329E+10 | 0.116852E+10 | 0.142433E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.3 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.42 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.29 | 8.94 | 5.14 | 4.69 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.70 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.86 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 16.99 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.23 | 8.10 | 4.97 | 3.17 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.70 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.4 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.18 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.86 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.61 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.92 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.10 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.68 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.80 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.66 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.30 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.17 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.34 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.46 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.93 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.66 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.0 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.87 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.92 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.93 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.92 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.80 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.63 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.17 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.83 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.03 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.93 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.93 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.63 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.87 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.92 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.34 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.63 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.78 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.78 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.63 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.510410E+11 | -.799003E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.153483E+10 | 58.97 | 0.00 | 0.00 |
February | 0.477362E+11 | -.736368E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.143310E+10 | 58.96 | 0.00 | 0.00 |
March | 0.519837E+11 | -.807679E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154098E+10 | 58.96 | 0.00 | 0.00 |
April | 0.470194E+11 | -.750940E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.151020E+10 | 58.96 | 0.00 | 0.00 |
May | 0.436283E+11 | -.729930E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.156647E+10 | 59.00 | 0.00 | 0.00 |
June | 0.371692E+11 | -.659499E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.151690E+10 | 59.04 | 0.00 | 0.00 |
July | 0.342528E+11 | -.642936E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.156772E+10 | 59.14 | 0.00 | 0.00 |
August | 0.324360E+11 | -.626339E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.154285E+10 | 59.19 | 0.00 | 0.00 |
September | 0.321817E+11 | -.613817E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.145837E+10 | 59.13 | 0.00 | 0.00 |
October | 0.366340E+11 | -.665941E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147602E+10 | 59.11 | 0.00 | 0.00 |
November | 0.402608E+11 | -.689050E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.143006E+10 | 59.01 | 0.00 | 0.00 |
December | 0.468297E+11 | -.760502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.147840E+10 | 58.96 | 0.00 | 0.00 |
Annual Sum or Average | 0.501173E+12 | -.848200E+12 | 8760.00 | -.180559E+11 | 59.04 | |||||
Minimum of Months | 0.321817E+11 | -.807679E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.156772E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.519837E+11 | -.613817E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.143006E+10 | 59.19 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHW BOOSTER WATER HEATER
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.770796E+10 | -.754277E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -165186695.2 | 81.21 | 0.00 | 0.00 |
February | 0.696639E+10 | -.681598E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -150415916.2 | 81.21 | 0.00 | 0.00 |
March | 0.770483E+10 | -.754282E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162012340.2 | 81.21 | 0.00 | 0.00 |
April | 0.746522E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156626333.9 | 81.21 | 0.00 | 0.00 |
May | 0.770472E+10 | -.754280E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161927040.8 | 81.21 | 0.00 | 0.00 |
June | 0.745753E+10 | -.730054E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156999655.3 | 81.21 | 0.00 | 0.00 |
July | 0.771326E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162412788.0 | 81.21 | 0.00 | 0.00 |
August | 0.770511E+10 | -.754281E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162298577.8 | 81.21 | 0.00 | 0.00 |
September | 0.746541E+10 | -.730859E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156819348.5 | 81.21 | 0.00 | 0.00 |
October | 0.770455E+10 | -.754279E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -161760273.6 | 81.21 | 0.00 | 0.00 |
November | 0.744971E+10 | -.729245E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -157263796.1 | 81.21 | 0.00 | 0.00 |
December | 0.771328E+10 | -.755085E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162426401.6 | 81.21 | 0.00 | 0.00 |
Annual Sum or Average | 0.907580E+11 | -.888418E+11 | 8760.00 | -.191615E+10 | 81.21 | |||||
Minimum of Months | 0.696639E+10 | -.755085E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -165186695.2 | 81.21 | 0.00 | 0.00 |
Maximum of Months | 0.771328E+10 | -.681598E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -150415916.2 | 81.21 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.795288E+11 | -.783572E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.117155E+10 | 61.10 | 0.00 | 0.00 |
February | 0.719849E+11 | -.709037E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.108121E+10 | 60.70 | 0.00 | 0.00 |
March | 0.796036E+11 | -.784354E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.116815E+10 | 60.84 | 0.00 | 0.00 |
April | 0.767462E+11 | -.755804E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.116585E+10 | 61.58 | 0.00 | 0.00 |
May | 0.788393E+11 | -.776004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.123895E+10 | 62.61 | 0.00 | 0.00 |
June | 0.758285E+11 | -.745986E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122990E+10 | 63.69 | 0.00 | 0.00 |
July | 0.779758E+11 | -.766823E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.129346E+10 | 64.53 | 0.00 | 0.00 |
August | 0.777973E+11 | -.765120E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128531E+10 | 64.91 | 0.00 | 0.00 |
September | 0.753662E+11 | -.741513E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.121491E+10 | 64.72 | 0.00 | 0.00 |
October | 0.781888E+11 | -.769763E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121256E+10 | 64.01 | 0.00 | 0.00 |
November | 0.761148E+11 | -.749661E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.114873E+10 | 63.02 | 0.00 | 0.00 |
December | 0.791411E+11 | -.779859E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.115518E+10 | 61.91 | 0.00 | 0.00 |
Annual Sum or Average | 0.927115E+12 | -.912750E+12 | 8760.00 | -.143658E+11 | 62.81 | |||||
Minimum of Months | 0.719849E+11 | -.784354E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.129346E+10 | 60.70 | 0.00 | 0.00 |
Maximum of Months | 0.796036E+11 | -.709037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.108121E+10 | 64.91 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: LOBBY_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.87 | 0.86 | 01-JAN-09:39 | 6525.69 | 38.06 | 207.17 | 251.67 | 4383.61 | 37.53 | 209.33 | 220.00 |
February | 226.83 | 0.87 | 0.86 | 01-FEB-07:00 | 7911.00 | 37.86 | 221.67 | 258.83 | 1677.87 | 29.11 | 210.67 | 234.83 |
March | 334.33 | 0.87 | 0.86 | 01-MAR-08:09 | 4416.89 | 26.21 | 207.33 | 331.50 | 762.43 | 22.39 | 240.00 | 286.17 |
April | 285.17 | 0.87 | 0.86 | 01-APR-07:30 | 1634.66 | 20.93 | 127.50 | 352.50 | 667.08 | 22.66 | 225.83 | 286.00 |
May | 428.67 | 0.87 | 0.86 | 01-MAY-06:49 | 1344.88 | 20.04 | 96.50 | 402.17 | 526.89 | 21.76 | 284.83 | 335.83 |
June | 400.67 | 0.87 | 0.86 | 01-JUN-06:10 | 1369.74 | 20.42 | 148.67 | 403.33 | 549.16 | 22.15 | 288.50 | 338.50 |
July | 414.00 | 0.87 | 0.86 | 01-JUL-06:10 | 1408.54 | 20.76 | 169.50 | 413.67 | 568.79 | 22.49 | 314.33 | 349.67 |
August | 410.83 | 0.87 | 0.86 | 01-AUG-06:40 | 1579.52 | 20.50 | 150.17 | 384.00 | 620.08 | 22.21 | 310.17 | 332.83 |
September | 326.50 | 0.87 | 0.86 | 01-SEP-06:40 | 2674.55 | 23.16 | 192.00 | 337.50 | 736.60 | 22.80 | 251.67 | 294.83 |
October | 325.17 | 0.87 | 0.86 | 01-OCT-07:10 | 6864.04 | 33.82 | 296.67 | 310.50 | 933.91 | 23.79 | 247.83 | 280.33 |
November | 254.83 | 0.87 | 0.86 | 01-NOV-07:49 | 4666.61 | 33.34 | 239.50 | 253.83 | 2243.62 | 30.79 | 229.17 | 223.67 |
December | 186.17 | 0.87 | 0.86 | 01-DEC-08:09 | 5656.22 | 38.16 | 180.50 | 227.50 | 5023.83 | 39.14 | 180.83 | 176.33 |
Annual Sum or Average | 3807.33 | 0.87 | 3372.36 | 26.11 | 2237.17 | 3927.00 | 1248.08 | 25.09 | 2993.17 | 3359.00 | ||
Minimum of Months | 186.17 | 0.87 | 0.86 | 1344.88 | 20.04 | 96.50 | 227.50 | 526.89 | 21.76 | 180.83 | 176.33 | |
Maximum of Months | 428.67 | 0.87 | 0.86 | 7911.00 | 38.16 | 296.67 | 413.67 | 5023.83 | 39.14 | 314.33 | 349.67 |
Report: DaylightingReportMonthly
For: CAFE_FLR_1_DAYLCTRL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.24 | 0.22 | 01-JAN-09:39 | 7057.13 | 38.14 | 207.17 | 259.67 | 4914.05 | 37.50 | 204.17 | 238.50 |
February | 226.83 | 0.25 | 0.22 | 01-FEB-07:49 | 8434.32 | 37.93 | 222.00 | 266.00 | 2196.78 | 28.83 | 205.67 | 249.83 |
March | 334.33 | 0.25 | 0.22 | 01-MAR-07:40 | 4798.02 | 26.42 | 207.50 | 341.67 | 1140.05 | 22.50 | 243.33 | 314.00 |
April | 285.17 | 0.26 | 0.22 | 01-APR-06:00 | 2002.13 | 21.13 | 125.67 | 362.67 | 1033.36 | 22.71 | 238.17 | 332.50 |
May | 428.67 | 0.26 | 0.22 | 01-MAY-06:40 | 1587.61 | 20.58 | 151.83 | 416.67 | 768.69 | 22.12 | 310.83 | 379.33 |
June | 400.67 | 0.26 | 0.22 | 01-JUN-05:30 | 1611.35 | 20.95 | 192.17 | 416.17 | 789.85 | 22.50 | 314.33 | 383.00 |
July | 414.00 | 0.25 | 0.22 | 01-JUL-05:49 | 1666.98 | 21.23 | 212.33 | 426.00 | 826.25 | 22.78 | 335.33 | 392.50 |
August | 410.83 | 0.26 | 0.22 | 01-AUG-05:00 | 1864.72 | 20.91 | 194.17 | 396.00 | 904.15 | 22.46 | 325.33 | 368.00 |
September | 326.50 | 0.25 | 0.22 | 01-SEP-06:19 | 3060.02 | 23.31 | 183.17 | 346.33 | 1120.56 | 22.85 | 269.83 | 320.33 |
October | 325.17 | 0.25 | 0.22 | 01-OCT-06:49 | 7279.98 | 33.98 | 298.17 | 317.00 | 1349.91 | 23.80 | 241.00 | 299.67 |
November | 254.83 | 0.25 | 0.22 | 01-NOV-07:40 | 5025.80 | 33.45 | 241.33 | 261.83 | 2602.94 | 30.83 | 229.17 | 241.67 |
December | 186.17 | 0.25 | 0.22 | 01-DEC-07:00 | 6151.40 | 38.25 | 180.50 | 238.50 | 5514.93 | 39.21 | 180.83 | 210.67 |
Annual Sum or Average | 3807.33 | 0.25 | 3722.89 | 26.40 | 2416.00 | 4048.50 | 1597.15 | 25.24 | 3098.00 | 3730.00 | ||
Minimum of Months | 186.17 | 0.24 | 0.22 | 1587.61 | 20.58 | 125.67 | 238.50 | 768.69 | 22.12 | 180.83 | 210.67 | |
Maximum of Months | 428.67 | 0.26 | 0.22 | 8434.32 | 38.25 | 298.17 | 426.00 | 5514.93 | 39.21 | 335.33 | 392.50 |
Report: DaylightingReportMonthly
For: DINING_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.60 | 01-JAN-10:09 | 469.18 | 15.66 | 0.00 | 233.83 | 228.82 | 19.15 | 0.50 | 137.33 |
February | 226.83 | 0.66 | 0.60 | 01-FEB-09:30 | 481.61 | 15.89 | 0.00 | 245.17 | 236.98 | 19.33 | 0.50 | 162.50 |
March | 334.33 | 0.63 | 0.60 | 01-MAR-08:20 | 676.68 | 17.16 | 0.00 | 332.00 | 303.25 | 20.36 | 30.67 | 269.67 |
April | 285.17 | 0.62 | 0.60 | 01-APR-07:19 | 768.99 | 18.31 | 0.00 | 362.33 | 366.06 | 21.52 | 141.33 | 304.33 |
May | 428.67 | 0.62 | 0.60 | 01-MAY-06:40 | 908.16 | 18.39 | 4.17 | 422.83 | 396.83 | 22.39 | 232.67 | 386.67 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1102.21 | 21.37 | 67.17 | 424.50 | 510.96 | 24.44 | 305.00 | 397.67 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1030.14 | 20.92 | 54.17 | 432.00 | 477.15 | 23.60 | 306.67 | 405.83 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:00 | 847.18 | 18.46 | 4.50 | 398.00 | 384.88 | 21.84 | 231.00 | 370.00 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:19 | 679.83 | 17.84 | 0.00 | 340.50 | 326.71 | 21.04 | 98.33 | 293.50 |
October | 325.17 | 0.64 | 0.60 | 01-OCT-07:40 | 551.10 | 16.36 | 0.00 | 299.33 | 254.44 | 19.67 | 0.00 | 226.67 |
November | 254.83 | 0.66 | 0.60 | 01-NOV-08:30 | 482.83 | 15.45 | 0.00 | 240.17 | 213.77 | 18.75 | 0.00 | 143.50 |
December | 186.17 | 0.70 | 0.60 | 02-DEC-09:39 | 332.73 | 14.25 | 0.00 | 203.33 | 168.74 | 17.87 | 0.00 | 49.17 |
Annual Sum or Average | 3807.33 | 0.63 | 747.73 | 17.95 | 130.00 | 3934.00 | 345.21 | 21.26 | 1346.67 | 3146.83 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 332.73 | 14.25 | 0.00 | 203.33 | 168.74 | 17.87 | 0.00 | 49.17 | |
Maximum of Months | 428.67 | 0.70 | 0.60 | 1102.21 | 21.37 | 67.17 | 432.00 | 510.96 | 24.44 | 306.67 | 405.83 |
Report: DaylightingReportMonthly
For: BANQUET_FLR_6_DAYLCTRL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.66 | 0.60 | 01-JAN-10:09 | 469.18 | 15.66 | 0.00 | 233.83 | 228.82 | 19.15 | 0.50 | 137.33 |
February | 226.83 | 0.66 | 0.60 | 01-FEB-09:30 | 481.61 | 15.89 | 0.00 | 245.17 | 236.98 | 19.33 | 0.50 | 162.50 |
March | 334.33 | 0.63 | 0.60 | 01-MAR-08:20 | 676.68 | 17.16 | 0.00 | 332.00 | 303.25 | 20.36 | 30.67 | 269.67 |
April | 285.17 | 0.62 | 0.60 | 01-APR-07:19 | 768.99 | 18.31 | 0.00 | 362.33 | 366.06 | 21.52 | 141.33 | 304.33 |
May | 428.67 | 0.62 | 0.60 | 01-MAY-06:40 | 908.16 | 18.39 | 4.17 | 422.83 | 396.83 | 22.39 | 232.67 | 386.67 |
June | 400.67 | 0.61 | 0.60 | 01-JUN-04:00 | 1102.21 | 21.37 | 67.17 | 424.50 | 510.96 | 24.44 | 305.00 | 397.67 |
July | 414.00 | 0.61 | 0.60 | 01-JUL-05:40 | 1030.14 | 20.92 | 54.17 | 432.00 | 477.15 | 23.60 | 306.67 | 405.83 |
August | 410.83 | 0.62 | 0.60 | 01-AUG-05:00 | 847.18 | 18.46 | 4.50 | 398.00 | 384.88 | 21.84 | 231.00 | 370.00 |
September | 326.50 | 0.62 | 0.60 | 01-SEP-06:19 | 679.83 | 17.84 | 0.00 | 340.50 | 326.71 | 21.04 | 98.33 | 293.50 |
October | 325.17 | 0.64 | 0.60 | 01-OCT-07:40 | 551.10 | 16.36 | 0.00 | 299.33 | 254.44 | 19.67 | 0.00 | 226.67 |
November | 254.83 | 0.66 | 0.60 | 01-NOV-08:30 | 482.83 | 15.45 | 0.00 | 240.17 | 213.77 | 18.75 | 0.00 | 143.50 |
December | 186.17 | 0.70 | 0.60 | 02-DEC-09:39 | 332.73 | 14.25 | 0.00 | 203.33 | 168.74 | 17.87 | 0.00 | 49.17 |
Annual Sum or Average | 3807.33 | 0.63 | 747.73 | 17.95 | 130.00 | 3934.00 | 345.21 | 21.26 | 1346.67 | 3146.83 | ||
Minimum of Months | 186.17 | 0.61 | 0.60 | 332.73 | 14.25 | 0.00 | 203.33 | 168.74 | 17.87 | 0.00 | 49.17 | |
Maximum of Months | 428.67 | 0.70 | 0.60 | 1102.21 | 21.37 | 67.17 | 432.00 | 510.96 | 24.44 | 306.67 | 405.83 |
Report: CoilReportMonthly
For: BASEMENT VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.220685E+10 | 7780.62 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.383210E+10 | 8190.68 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.560639E+09 | 5798.85 | 16-APR-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.777837E+09 | 5298.16 | 29-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.588451E+09 | 3111.91 | 26-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81264266.38 | 1944.67 | 02-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138931E+09 | 7616.49 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.818607E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383210E+10 | 8190.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.582297E+10 | 4651.78 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418128E+10 | 4906.63 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.247316E+10 | 2572.69 | 06-MAR-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145917E+10 | 2114.85 | 03-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.400715E+09 | 1067.82 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182042E+09 | 828.41 | 03-JUN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 66857702.31 | 474.12 | 10-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35519944.85 | 368.67 | 20-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.351068E+09 | 1430.40 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.901753E+09 | 1538.43 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280315E+10 | 4550.26 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.446819E+10 | 3258.89 | 09-DEC-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.231459E+11 | |||||||
Minimum of Months | 35519944.85 | 368.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.582297E+10 | 4906.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: RETAIL_2_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.887464E+09 | 1634.95 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710622E+09 | 1722.72 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38344729.84 | 420.12 | 01-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7797971.98 | 274.45 | 03-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167803E+09 | 1599.89 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.230036E+09 | 756.49 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204207E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.887464E+09 | 1722.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.260224E+10 | 2415.46 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184448E+10 | 2546.77 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.626156E+09 | 1118.32 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168585E+09 | 743.56 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737513E+09 | 2363.10 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146206E+10 | 1517.51 | 11-DEC-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744103E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260224E+10 | 2546.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: STORAGE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.215472E+10 | 1478.43 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153080E+10 | 1559.04 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.788046E+09 | 847.78 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.319754E+09 | 588.61 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5250679.03 | 136.57 | 02-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4313119.24 | 181.53 | 30-SEP-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41819954.92 | 235.33 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.820569E+09 | 1446.30 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.154677E+10 | 1036.83 | 12-DEC-18:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721204E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.215472E+10 | 1559.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LAUNDRY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.351712E+10 | 11019.59 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.365585E+10 | 11600.78 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.335597E+09 | 2490.51 | 19-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466156E+09 | 3404.65 | 16-APR-16:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.906633E+09 | 4200.65 | 31-MAY-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.184315E+10 | 6445.97 | 26-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.255326E+10 | 6359.41 | 07-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.221832E+10 | 6270.21 | 04-AUG-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118061E+10 | 6359.36 | 11-SEP-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239098E+09 | 2372.84 | 01-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.775943E+09 | 10787.00 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439076E+09 | 3018.28 | 11-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181308E+11 | |||||||
Minimum of Months | 0.239098E+09 | 2372.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365585E+10 | 11600.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAFE_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.876611E+10 | 13866.58 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.640940E+10 | 14619.90 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145793E+10 | 5226.41 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.789263E+09 | 4963.47 | 03-APR-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14119415.28 | 1651.10 | 02-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 43272835.91 | 1218.29 | 05-JUN-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 26333653.81 | 1170.77 | 10-JUL-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5116862.29 | 624.71 | 31-AUG-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 54287771.29 | 1610.01 | 27-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104187E+09 | 2498.86 | 26-OCT-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.250029E+10 | 13566.15 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.448046E+10 | 8515.47 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246508E+11 | |||||||
Minimum of Months | 5116862.29 | 624.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.876611E+10 | 14619.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.140201E+11 | 33581.73 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129121E+11 | 35384.10 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.378697E+09 | 7225.85 | 01-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75642373.49 | 4403.83 | 03-APR-11:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243372E+10 | 32861.83 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.273971E+10 | 14738.51 | 12-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.325599E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140201E+11 | 35384.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.872278E+10 | 8315.32 | 17-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.604268E+10 | 8315.72 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332000E+10 | 8315.01 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148006E+10 | 8314.76 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195268E+09 | 6808.36 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82866356.40 | 5274.45 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10154874.42 | 4228.79 | 28-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9747023.70 | 4839.47 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.348678E+09 | 8076.98 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123618E+10 | 8158.63 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410029E+10 | 8315.16 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.713281E+10 | 8316.24 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.326815E+11 | |||||||
Minimum of Months | 9747023.70 | 4228.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.872278E+10 | 8316.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100659E+11 | 8285.31 | 09-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.710750E+10 | 8285.55 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.387128E+10 | 8284.73 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163928E+10 | 8284.46 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.203662E+09 | 7983.22 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80554501.26 | 5189.46 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5394871.54 | 5006.90 | 24-JUL-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9317312.54 | 4919.03 | 11-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.411020E+09 | 8074.72 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168644E+10 | 8170.23 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.480925E+10 | 8284.85 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.819184E+10 | 8285.96 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.380815E+11 | |||||||
Minimum of Months | 5394871.54 | 4919.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100659E+11 | 8285.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.587612E+10 | 19915.74 | 19-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139108E+10 | 17879.10 | 04-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61945594.55 | 6513.28 | 28-NOV-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.274428E+10 | 14973.42 | 12-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100734E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.587612E+10 | 19915.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.423663E+11 | 45857.45 | 08-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.291273E+11 | 46219.74 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106666E+11 | 45363.93 | 05-MAR-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298585E+10 | 44502.36 | 03-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109704E+09 | 43459.08 | 20-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 41454461.70 | 38120.64 | 06-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14255513.54 | 34443.41 | 10-JUL-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 32300489.32 | 36287.88 | 06-AUG-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.258145E+09 | 38774.38 | 30-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185365E+10 | 42348.67 | 11-OCT-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145951E+11 | 45856.73 | 27-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299227E+11 | 45860.54 | 13-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131973E+12 | |||||||
Minimum of Months | 14255513.54 | 34443.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.423663E+11 | 46219.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.869743E+10 | 7983.11 | 16-JAN-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.609959E+10 | 7983.40 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326680E+10 | 7982.57 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159259E+10 | 7982.28 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164425E+09 | 4848.51 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68439572.51 | 4434.24 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7263938.18 | 4566.76 | 10-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13400168.05 | 4222.56 | 30-AUG-18:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.322548E+09 | 4575.60 | 25-SEP-18:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124437E+10 | 7794.47 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.412858E+10 | 7982.70 | 30-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.717691E+10 | 7982.59 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327824E+11 | |||||||
Minimum of Months | 7263938.18 | 4222.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.869743E+10 | 7983.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100483E+11 | 7980.44 | 16-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.719291E+10 | 8077.79 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381467E+10 | 7979.83 | 02-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178816E+10 | 7979.64 | 21-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.182262E+09 | 5146.77 | 02-MAY-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67722472.73 | 4475.83 | 03-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4283911.63 | 4583.57 | 10-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10576041.60 | 4076.18 | 06-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381624E+09 | 4941.44 | 25-SEP-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169190E+10 | 7825.84 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.485054E+10 | 7982.06 | 20-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.825985E+10 | 7981.09 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382928E+11 | |||||||
Minimum of Months | 4283911.63 | 4076.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100483E+11 | 8077.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.236748E+11 | 13888.80 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.185204E+11 | 14646.95 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130252E+11 | 9724.46 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.829282E+10 | 8388.16 | 03-APR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424441E+10 | 5108.08 | 02-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.221807E+10 | 4436.55 | 03-JUN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133789E+10 | 3293.22 | 10-JUL-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164809E+10 | 3428.84 | 26-AUG-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.355330E+10 | 6048.45 | 30-SEP-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.784602E+10 | 6363.94 | 27-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146035E+11 | 13586.64 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.200251E+11 | 9746.64 | 08-DEC-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118990E+12 | |||||||
Minimum of Months | 0.133789E+10 | 3293.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.236748E+11 | 14646.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.285406E+10 | 2404.55 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.192644E+10 | 2405.06 | 23-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.116766E+10 | 2404.73 | 14-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.533448E+09 | 2404.49 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75346953.66 | 2333.51 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30402776.94 | 1187.13 | 04-JUN-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2114670.76 | 1034.39 | 06-JUL-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2625117.86 | 1148.50 | 07-AUG-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135144E+09 | 2365.82 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476154E+09 | 2391.63 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141444E+10 | 2404.72 | 10-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239934E+10 | 2404.72 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110172E+11 | |||||||
Minimum of Months | 2114670.76 | 1034.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.285406E+10 | 2405.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324822E+10 | 2397.35 | 13-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.224967E+10 | 2399.94 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134905E+10 | 2397.50 | 14-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.583785E+09 | 2397.27 | 02-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75473488.34 | 2332.78 | 02-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29986332.27 | 1253.07 | 08-JUN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 920469.05 | 1288.43 | 18-JUL-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1446287.70 | 1298.30 | 10-AUG-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154189E+09 | 2366.46 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.626079E+09 | 2396.73 | 27-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163954E+10 | 2398.31 | 15-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272435E+10 | 2397.50 | 14-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126827E+11 | |||||||
Minimum of Months | 920469.05 | 1253.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324822E+10 | 2399.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.959983E+10 | 10547.47 | 17-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.601207E+10 | 10546.90 | 22-FEB-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357541E+10 | 10545.79 | 02-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182557E+10 | 10546.38 | 02-APR-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166834E+09 | 7643.21 | 09-MAY-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54656127.35 | 5184.79 | 19-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4867398.28 | 5018.40 | 10-JUL-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11240405.21 | 3912.61 | 12-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.267604E+09 | 6266.88 | 29-SEP-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.886314E+09 | 10211.17 | 26-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.421310E+10 | 10546.51 | 17-NOV-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797318E+10 | 10546.98 | 31-DEC-16:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345907E+11 | |||||||
Minimum of Months | 4867398.28 | 3912.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.959983E+10 | 10547.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BANQUET_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373670E+10 | 12584.61 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405073E+10 | 13257.25 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.512451E+09 | 12315.88 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14065446.04 | 921.16 | 11-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.831395E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405073E+10 | 13257.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DINING_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.374750E+10 | 12979.54 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.405026E+10 | 13672.93 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511537E+09 | 12702.51 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.830929E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405026E+10 | 13672.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: KITCHEN_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238812E+10 | 8724.78 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.260558E+10 | 9185.98 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339438E+09 | 8540.26 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17339.58 | 28.90 | 10-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533315E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.260558E+10 | 9185.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_FLR_6 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125028E+11 | 8887.20 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906041E+10 | 9374.04 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.501587E+10 | 5307.08 | 06-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241850E+10 | 3818.42 | 03-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.301609E+09 | 1990.51 | 03-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79921254.83 | 1196.95 | 03-JUN-04:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3179010.18 | 307.94 | 12-JUL-04:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.550682E+09 | 2695.83 | 30-SEP-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204319E+10 | 2793.47 | 27-OCT-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.596477E+10 | 8693.27 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.954971E+10 | 6226.25 | 09-DEC-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.474907E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.125028E+11 | 9374.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.271148E+12 | 311463.42 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.177566E+12 | 325255.18 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.599113E+11 | 120175.51 | 05-MAR-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229949E+11 | 72758.29 | 30-APR-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158612E+11 | 80917.81 | 17-MAY-20:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101096E+11 | 77963.36 | 01-JUN-19:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149781E+10 | 45594.23 | 23-JUL-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.417245E+10 | 64358.09 | 06-AUG-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133426E+11 | 83783.17 | 25-SEP-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158148E+11 | 81157.88 | 04-OCT-19:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.846387E+11 | 305829.61 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144869E+12 | 162975.14 | 08-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.821926E+12 | |||||||
Minimum of Months | 0.149781E+10 | 45594.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.271148E+12 | 325255.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FLR_3_DOAS_HEATC
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.161893E+11 | 31339.03 | 31-JAN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109497E+11 | 32737.04 | 02-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.232508E+10 | 6978.78 | 06-MAR-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.437202E+09 | 3910.68 | 03-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12817.22 | 0.29 | 24-MAY-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13003.92 | 0.29 | 24-JUN-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14745.14 | 0.29 | 15-JUL-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17470.68 | 0.29 | 01-AUG-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 295258.74 | 188.70 | 30-SEP-01:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21307579.82 | 1120.05 | 23-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380887E+10 | 30768.44 | 26-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.689066E+10 | 11600.94 | 09-DEC-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406225E+11 | |||||||
Minimum of Months | 12817.22 | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.161893E+11 | 32737.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: ROOM_1_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 5104448.38 | 5104448.38 | 16668.49 | 12-JAN-16:01 | 16668.49 | 0.00 |
February | 0.00 | 0.00 | 0.101381E+09 | 0.100688E+09 | 17231.36 | 25-FEB-16:01 | 17231.36 | 0.00 |
March | 0.00 | 0.00 | 0.343389E+09 | 0.261539E+09 | 17233.49 | 25-MAR-15:01 | 17233.49 | 0.05 |
April | 0.00 | 0.00 | 0.204048E+10 | 0.128894E+10 | 17614.27 | 16-APR-08:61 | 13478.46 | 0.25 |
May | 0.00 | 0.00 | 0.344574E+10 | 0.172318E+10 | 18082.00 | 29-MAY-08:61 | 13149.34 | 0.59 |
June | 0.00 | 0.00 | 0.645677E+10 | 0.314620E+10 | 19525.22 | 26-JUN-08:61 | 12014.15 | 0.79 |
July | 0.00 | 0.00 | 0.833058E+10 | 0.396238E+10 | 19300.13 | 20-JUL-08:62 | 11647.34 | 0.91 |
August | 0.00 | 0.00 | 0.732889E+10 | 0.330004E+10 | 20805.08 | 03-AUG-08:61 | 10921.28 | 0.90 |
September | 0.00 | 0.00 | 0.424543E+10 | 0.218719E+10 | 18334.18 | 11-SEP-08:61 | 12896.36 | 0.61 |
October | 0.00 | 0.00 | 0.983513E+09 | 0.657535E+09 | 17231.95 | 19-OCT-15:01 | 17231.95 | 0.18 |
November | 0.00 | 0.00 | 0.183221E+09 | 0.123773E+09 | 17224.84 | 04-NOV-15:01 | 17224.84 | 0.04 |
December | 0.00 | 0.00 | 8844247.89 | 8844247.89 | 16321.32 | 01-DEC-16:01 | 16321.32 | 0.00 |
Annual Sum or Average | 0.334733E+11 | 0.167654E+11 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 5104448.38 | 5104448.38 | 16321.32 | 10921.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.833058E+10 | 0.396238E+10 | 20805.08 | 17233.49 | 0.91 |
Report: CoilReportMonthly
For: ROOM_2_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 492586.40 | 492586.40 | 1945.57 | 12-JAN-16:03 | 1945.57 | 0.00 |
February | 0.00 | 0.00 | 28979322.97 | 28696564.76 | 16527.91 | 24-FEB-16:01 | 16527.91 | 0.00 |
March | 0.00 | 0.00 | 0.134664E+09 | 99729849.54 | 16960.77 | 25-MAR-15:01 | 16960.77 | 0.03 |
April | 0.00 | 0.00 | 0.127725E+10 | 0.781179E+09 | 18000.53 | 16-APR-21:11 | 13935.19 | 0.18 |
May | 0.00 | 0.00 | 0.226741E+10 | 0.984922E+09 | 19768.32 | 21-MAY-19:01 | 19768.32 | 0.47 |
June | 0.00 | 0.00 | 0.495518E+10 | 0.232954E+10 | 21641.92 | 26-JUN-08:11 | 11546.46 | 0.61 |
July | 0.00 | 0.00 | 0.575495E+10 | 0.256560E+10 | 20256.98 | 20-JUL-08:11 | 10971.04 | 0.64 |
August | 0.00 | 0.00 | 0.477314E+10 | 0.191894E+10 | 22901.92 | 03-AUG-08:11 | 10252.44 | 0.65 |
September | 0.00 | 0.00 | 0.257743E+10 | 0.117277E+10 | 18495.84 | 11-SEP-08:11 | 12519.19 | 0.45 |
October | 0.00 | 0.00 | 0.348042E+09 | 0.226974E+09 | 16960.43 | 19-OCT-15:01 | 16960.43 | 0.08 |
November | 0.00 | 0.00 | 61664849.53 | 40477133.42 | 16951.28 | 04-NOV-15:01 | 16951.28 | 0.02 |
December | 0.00 | 0.00 | 849739.22 | 849739.22 | 2330.25 | 01-DEC-16:03 | 2330.25 | 0.00 |
Annual Sum or Average | 0.221800E+11 | 0.101502E+11 | 0.26 | |||||
Minimum of Months | 0.00 | 0.00 | 492586.40 | 492586.40 | 1945.57 | 1945.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.575495E+10 | 0.256560E+10 | 22901.92 | 19768.32 | 0.65 |
Report: CoilReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.296122E+10 | 0.280351E+10 | 31173.13 | 24-MAR-13:00 | 31173.13 | 0.02 |
April | 0.00 | 0.00 | 0.101701E+11 | 0.562941E+10 | 43372.66 | 15-APR-12:40 | 37157.00 | 0.24 |
May | 0.00 | 0.00 | 0.209693E+11 | 0.890136E+10 | 27887.25 | 31-MAY-19:05 | 15815.14 | 0.64 |
June | 0.00 | 0.00 | 0.321609E+11 | 0.124853E+11 | 31671.88 | 26-JUN-17:25 | 19428.40 | 0.89 |
July | 0.00 | 0.00 | 0.402609E+11 | 0.156579E+11 | 31384.47 | 26-JUL-20:12 | 17282.90 | 0.98 |
August | 0.00 | 0.00 | 0.414990E+11 | 0.173013E+11 | 37494.07 | 22-AUG-13:00 | 25468.79 | 0.98 |
September | 0.00 | 0.00 | 0.335532E+11 | 0.194733E+11 | 48560.12 | 06-SEP-14:00 | 42977.33 | 0.68 |
October | 0.00 | 0.00 | 0.188283E+11 | 0.161569E+11 | 53232.95 | 20-OCT-12:30 | 53232.95 | 0.17 |
November | 0.00 | 0.00 | 0.564561E+10 | 0.467299E+10 | 51567.38 | 04-NOV-12:30 | 51567.38 | 0.09 |
December | 0.00 | 0.00 | 38064791.04 | 38064791.04 | 6443.50 | 07-DEC-14:40 | 6443.50 | 0.00 |
Annual Sum or Average | 0.206086E+12 | 0.103120E+12 | 0.39 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.414990E+11 | 0.194733E+11 | 53232.95 | 53232.95 | 0.98 |
Report: CoilReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 44322479.05 | 44322479.05 | 45811.61 | 01-JAN-09:02 | 45811.61 | 0.00 |
February | 0.00 | 0.00 | 0.248619E+09 | 0.201234E+09 | 82599.32 | 26-FEB-09:02 | 82599.32 | 0.01 |
March | 0.00 | 0.00 | 0.368309E+10 | 0.223702E+10 | 86438.08 | 25-MAR-18:02 | 86438.08 | 0.12 |
April | 0.00 | 0.00 | 0.127253E+11 | 0.808855E+10 | 96347.72 | 16-APR-21:11 | 73462.91 | 0.26 |
May | 0.00 | 0.00 | 0.310163E+11 | 0.174808E+11 | 97278.56 | 29-MAY-08:11 | 72781.52 | 0.56 |
June | 0.00 | 0.00 | 0.463514E+11 | 0.274173E+11 | 116715.87 | 26-JUN-08:11 | 60905.13 | 0.64 |
July | 0.00 | 0.00 | 0.504945E+11 | 0.294598E+11 | 110476.59 | 20-JUL-08:11 | 59573.39 | 0.58 |
August | 0.00 | 0.00 | 0.460792E+11 | 0.257678E+11 | 125350.95 | 03-AUG-08:11 | 53423.44 | 0.58 |
September | 0.00 | 0.00 | 0.289934E+11 | 0.166300E+11 | 99702.37 | 11-SEP-21:11 | 72020.87 | 0.55 |
October | 0.00 | 0.00 | 0.954100E+10 | 0.598054E+10 | 85382.82 | 12-OCT-18:03 | 85382.82 | 0.27 |
November | 0.00 | 0.00 | 0.421531E+10 | 0.183407E+10 | 83920.98 | 04-NOV-18:01 | 83920.98 | 0.17 |
December | 0.00 | 0.00 | 59800660.92 | 59800660.92 | 53531.83 | 03-DEC-09:02 | 53531.83 | 0.00 |
Annual Sum or Average | 0.233452E+12 | 0.135201E+12 | 0.31 | |||||
Minimum of Months | 0.00 | 0.00 | 44322479.05 | 44322479.05 | 45811.61 | 45811.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.504945E+11 | 0.294598E+11 | 125350.95 | 86438.08 | 0.64 |
Report: CoilReportMonthly
For: ROOM_5_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 805101.70 | 805101.70 | 2334.44 | 12-JAN-09:03 | 2334.44 | 0.00 |
February | 0.00 | 0.00 | 60781668.97 | 47707487.27 | 15117.77 | 24-FEB-09:02 | 15117.77 | 0.01 |
March | 0.00 | 0.00 | 0.311421E+09 | 0.206314E+09 | 15476.00 | 24-MAR-15:01 | 15476.00 | 0.06 |
April | 0.00 | 0.00 | 0.167508E+10 | 0.947291E+09 | 15473.95 | 30-APR-18:01 | 15473.95 | 0.26 |
May | 0.00 | 0.00 | 0.368324E+10 | 0.179784E+10 | 16173.48 | 11-MAY-15:01 | 11589.85 | 0.66 |
June | 0.00 | 0.00 | 0.653439E+10 | 0.323793E+10 | 16900.82 | 14-JUN-08:62 | 10477.05 | 0.83 |
July | 0.00 | 0.00 | 0.804552E+10 | 0.379147E+10 | 17367.80 | 20-JUL-08:62 | 10438.40 | 0.94 |
August | 0.00 | 0.00 | 0.699287E+10 | 0.308336E+10 | 18229.81 | 31-AUG-08:62 | 9599.06 | 0.92 |
September | 0.00 | 0.00 | 0.423636E+10 | 0.215209E+10 | 15807.03 | 10-SEP-08:62 | 12187.36 | 0.64 |
October | 0.00 | 0.00 | 0.792166E+09 | 0.476094E+09 | 15476.77 | 24-OCT-15:01 | 15476.77 | 0.18 |
November | 0.00 | 0.00 | 0.140439E+09 | 86436775.14 | 15471.19 | 04-NOV-15:01 | 15471.19 | 0.05 |
December | 0.00 | 0.00 | 12872483.48 | 12426513.88 | 10737.29 | 03-DEC-09:02 | 10737.29 | 0.00 |
Annual Sum or Average | 0.324859E+11 | 0.158398E+11 | 0.38 | |||||
Minimum of Months | 0.00 | 0.00 | 805101.70 | 805101.70 | 2334.44 | 2334.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.804552E+10 | 0.379147E+10 | 18229.81 | 15476.77 | 0.94 |
Report: CoilReportMonthly
For: ROOM_6_FLR_3 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 379129.35 | 379129.35 | 1502.34 | 11-JAN-09:05 | 1502.34 | 0.00 |
February | 0.00 | 0.00 | 11576648.43 | 9826287.49 | 14552.72 | 24-FEB-09:02 | 14552.72 | 0.00 |
March | 0.00 | 0.00 | 0.129574E+09 | 80185790.67 | 12806.30 | 19-MAR-15:01 | 12806.30 | 0.03 |
April | 0.00 | 0.00 | 0.105398E+10 | 0.595416E+09 | 17812.57 | 18-APR-08:11 | 14600.01 | 0.18 |
May | 0.00 | 0.00 | 0.275404E+10 | 0.134969E+10 | 18985.31 | 31-MAY-08:11 | 15310.29 | 0.52 |
June | 0.00 | 0.00 | 0.519650E+10 | 0.263054E+10 | 21013.55 | 26-JUN-08:11 | 14036.20 | 0.65 |
July | 0.00 | 0.00 | 0.584531E+10 | 0.278697E+10 | 20164.20 | 02-JUL-08:11 | 15041.15 | 0.66 |
August | 0.00 | 0.00 | 0.482116E+10 | 0.212100E+10 | 21726.76 | 03-AUG-08:11 | 11829.88 | 0.66 |
September | 0.00 | 0.00 | 0.273397E+10 | 0.132065E+10 | 18125.18 | 11-SEP-08:11 | 13620.56 | 0.47 |
October | 0.00 | 0.00 | 0.222797E+09 | 0.113796E+09 | 14426.69 | 02-OCT-15:01 | 11960.16 | 0.07 |
November | 0.00 | 0.00 | 19740974.84 | 8565323.79 | 10176.51 | 04-NOV-08:62 | 10126.15 | 0.01 |
December | 0.00 | 0.00 | 785241.07 | 785241.07 | 2174.04 | 05-DEC-09:03 | 2174.04 | 0.00 |
Annual Sum or Average | 0.227898E+11 | 0.110178E+11 | 0.27 | |||||
Minimum of Months | 0.00 | 0.00 | 379129.35 | 379129.35 | 1502.34 | 1502.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.584531E+10 | 0.278697E+10 | 21726.76 | 15310.29 | 0.66 |
Report: CoilReportMonthly
For: ROOM_1_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1130778.06 | 1125171.81 | 4301.13 | 12-JAN-16:01 | 4301.13 | 0.00 |
February | 0.00 | 0.00 | 26673673.24 | 26509574.67 | 4482.43 | 25-FEB-16:01 | 4482.43 | 0.00 |
March | 0.00 | 0.00 | 83780923.13 | 64471116.87 | 4482.37 | 24-MAR-18:01 | 4482.37 | 0.04 |
April | 0.00 | 0.00 | 0.583876E+09 | 0.387187E+09 | 4622.70 | 16-APR-08:61 | 3451.38 | 0.24 |
May | 0.00 | 0.00 | 0.102864E+10 | 0.548511E+09 | 4752.21 | 29-MAY-08:61 | 3377.98 | 0.59 |
June | 0.00 | 0.00 | 0.193579E+10 | 0.103512E+10 | 5106.19 | 26-JUN-08:61 | 3097.72 | 0.81 |
July | 0.00 | 0.00 | 0.249308E+10 | 0.130566E+10 | 5180.53 | 20-JUL-08:62 | 2913.66 | 0.93 |
August | 0.00 | 0.00 | 0.217616E+10 | 0.107317E+10 | 5468.89 | 03-AUG-08:61 | 2786.84 | 0.91 |
September | 0.00 | 0.00 | 0.123488E+10 | 0.701432E+09 | 4852.74 | 11-SEP-08:61 | 3293.50 | 0.60 |
October | 0.00 | 0.00 | 0.258914E+09 | 0.180884E+09 | 4482.34 | 29-OCT-15:02 | 4482.34 | 0.15 |
November | 0.00 | 0.00 | 47323786.61 | 34816191.26 | 4480.55 | 04-NOV-15:01 | 4480.55 | 0.03 |
December | 0.00 | 0.00 | 1629422.24 | 1610723.70 | 4210.60 | 01-DEC-16:01 | 4210.60 | 0.00 |
Annual Sum or Average | 0.987187E+10 | 0.536050E+10 | 0.36 | |||||
Minimum of Months | 0.00 | 0.00 | 1130778.06 | 1125171.81 | 4210.60 | 2786.84 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.249308E+10 | 0.130566E+10 | 5468.89 | 4482.43 | 0.93 |
Report: CoilReportMonthly
For: ROOM_2_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 72573.70 | 72573.70 | 666.22 | 13-JAN-16:04 | 666.22 | 0.00 |
February | 0.00 | 0.00 | 5208338.60 | 5146758.64 | 4206.97 | 24-FEB-16:01 | 4206.97 | 0.00 |
March | 0.00 | 0.00 | 27943110.44 | 20601835.93 | 4409.06 | 24-MAR-18:01 | 4409.06 | 0.02 |
April | 0.00 | 0.00 | 0.376287E+09 | 0.241443E+09 | 4769.29 | 16-APR-21:11 | 3756.65 | 0.18 |
May | 0.00 | 0.00 | 0.724683E+09 | 0.347326E+09 | 5459.73 | 20-MAY-18:01 | 5459.73 | 0.49 |
June | 0.00 | 0.00 | 0.157252E+10 | 0.830455E+09 | 5785.04 | 26-JUN-08:11 | 3038.31 | 0.63 |
July | 0.00 | 0.00 | 0.185883E+10 | 0.948259E+09 | 5515.66 | 06-JUL-21:11 | 4154.26 | 0.66 |
August | 0.00 | 0.00 | 0.154583E+10 | 0.702919E+09 | 6138.15 | 03-AUG-08:11 | 2675.43 | 0.67 |
September | 0.00 | 0.00 | 0.798955E+09 | 0.399966E+09 | 4951.03 | 11-SEP-21:11 | 3529.19 | 0.45 |
October | 0.00 | 0.00 | 84641743.51 | 55154659.18 | 4311.80 | 19-OCT-16:32 | 4311.80 | 0.06 |
November | 0.00 | 0.00 | 14901975.67 | 9822346.29 | 4388.39 | 04-NOV-15:01 | 4388.39 | 0.01 |
December | 0.00 | 0.00 | 129735.95 | 129735.95 | 635.67 | 02-DEC-16:03 | 635.67 | 0.00 |
Annual Sum or Average | 0.701001E+10 | 0.356130E+10 | 0.27 | |||||
Minimum of Months | 0.00 | 0.00 | 72573.70 | 72573.70 | 635.67 | 635.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.185883E+10 | 0.948259E+09 | 6138.15 | 5459.73 | 0.67 |
Report: CoilReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILCOOL COIL
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.486381E+09 | 0.485438E+09 | 17333.41 | 13-JAN-16:01 | 17333.41 | 0.00 |
February | 0.00 | 0.00 | 0.830773E+09 | 0.698670E+09 | 17332.98 | 19-FEB-16:01 | 17332.98 | 0.06 |
March | 0.00 | 0.00 | 0.137825E+10 | 0.101121E+10 | 17331.92 | 27-MAR-15:01 | 17331.92 | 0.14 |
April | 0.00 | 0.00 | 0.313322E+10 | 0.197863E+10 | 17789.47 | 16-APR-08:61 | 13516.03 | 0.32 |
May | 0.00 | 0.00 | 0.518806E+10 | 0.248476E+10 | 18076.59 | 11-MAY-18:02 | 12580.19 | 0.69 |
June | 0.00 | 0.00 | 0.870715E+10 | 0.438090E+10 | 20621.39 | 26-JUN-08:61 | 11569.24 | 0.84 |
July | 0.00 | 0.00 | 0.111095E+11 | 0.546647E+10 | 20475.83 | 20-JUL-08:62 | 11039.67 | 0.92 |
August | 0.00 | 0.00 | 0.110055E+11 | 0.555002E+10 | 21943.87 | 03-AUG-08:61 | 10458.02 | 0.91 |
September | 0.00 | 0.00 | 0.783920E+10 | 0.490331E+10 | 18952.02 | 11-SEP-08:61 | 12854.24 | 0.72 |
October | 0.00 | 0.00 | 0.397872E+10 | 0.304964E+10 | 17332.38 | 27-OCT-15:01 | 17332.38 | 0.36 |
November | 0.00 | 0.00 | 0.138695E+10 | 0.105684E+10 | 17319.75 | 12-NOV-16:01 | 17319.75 | 0.15 |
December | 0.00 | 0.00 | 0.964015E+09 | 0.931285E+09 | 17321.50 | 01-DEC-16:01 | 17321.50 | 0.01 |
Annual Sum or Average | 0.560077E+11 | 0.319972E+11 | 0.43 | |||||
Minimum of Months | 0.00 | 0.00 | 0.486381E+09 | 0.485438E+09 | 17319.75 | 10458.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111095E+11 | 0.555002E+10 | 21943.87 | 17333.41 | 0.92 |
Report: CoilReportMonthly
For: VAV WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.450568E+10 | 0.450568E+10 | 92987.48 | 19-MAR-16:00 | 92987.48 | 0.02 |
April | 0.00 | 0.00 | 0.574084E+11 | 0.442320E+11 | 290833.28 | 16-APR-20:10 | 176672.00 | 0.15 |
May | 0.00 | 0.00 | 0.143673E+12 | 0.106463E+12 | 300518.90 | 30-MAY-19:40 | 181806.18 | 0.45 |
June | 0.00 | 0.00 | 0.383642E+12 | 0.246001E+12 | 384843.15 | 14-JUN-17:10 | 156760.12 | 0.78 |
July | 0.00 | 0.00 | 0.559000E+12 | 0.315819E+12 | 532290.37 | 03-JUL-21:50 | 187841.89 | 0.95 |
August | 0.00 | 0.00 | 0.480463E+12 | 0.280121E+12 | 492879.81 | 04-AUG-06:00 | 159454.77 | 0.89 |
September | 0.00 | 0.00 | 0.184311E+12 | 0.155756E+12 | 317972.96 | 11-SEP-19:20 | 185432.06 | 0.48 |
October | 0.00 | 0.00 | 0.147997E+11 | 0.147997E+11 | 160434.60 | 20-OCT-15:10 | 160434.60 | 0.05 |
November | 0.00 | 0.00 | 0.155089E+10 | 0.155089E+10 | 42462.44 | 03-NOV-14:20 | 42462.44 | 0.03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.182935E+13 | 0.116925E+13 | 0.32 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.559000E+12 | 0.315819E+12 | 532290.37 | 187841.89 | 0.95 |
Report: CoilReportMonthly
For: FLR_3_DOAS_COOLC
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.213241E+09 | 0.213241E+09 | 8513.13 | 19-MAR-16:00 | 8513.13 | 0.01 |
April | 0.00 | 0.00 | 0.333047E+10 | 0.262331E+10 | 28809.21 | 18-APR-17:00 | 17117.99 | 0.10 |
May | 0.00 | 0.00 | 0.752309E+10 | 0.567247E+10 | 29469.14 | 29-MAY-15:01 | 14681.02 | 0.29 |
June | 0.00 | 0.00 | 0.244977E+11 | 0.158155E+11 | 40676.53 | 26-JUN-08:61 | 18440.94 | 0.57 |
July | 0.00 | 0.00 | 0.373240E+11 | 0.209604E+11 | 42550.34 | 17-JUL-18:03 | 17070.23 | 0.72 |
August | 0.00 | 0.00 | 0.304210E+11 | 0.175604E+11 | 47404.58 | 03-AUG-08:61 | 18642.63 | 0.66 |
September | 0.00 | 0.00 | 0.109111E+11 | 0.939871E+10 | 29509.45 | 11-SEP-08:11 | 15607.07 | 0.35 |
October | 0.00 | 0.00 | 0.653299E+09 | 0.653299E+09 | 15306.28 | 20-OCT-15:02 | 15306.28 | 0.03 |
November | 0.00 | 0.00 | 24313945.23 | 24313945.23 | 2177.41 | 03-NOV-15:03 | 2177.41 | 0.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.114898E+12 | 0.729216E+11 | 0.23 | |||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.373240E+11 | 0.209604E+11 | 47404.58 | 18642.63 | 0.72 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 31415.12 | 64790.88 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 32041.30 | 65233.53 | 21-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 31752.80 | 65113.59 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 30567.50 | 63302.57 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28792.84 | 60316.27 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 26917.72 | 56358.47 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 25330.11 | 52724.91 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 24629.18 | 50624.68 | 01-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 25017.37 | 51712.22 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 26239.55 | 55018.82 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 28109.49 | 58907.05 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 29986.60 | 62311.88 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 28378.22 | ||||
Minimum of Months | 0.00 | 0.00 | 24629.18 | 50624.68 | ||
Maximum of Months | 0.00 | 0.00 | 32041.30 | 65233.53 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 176680.10 | 575877.88 | 31-JAN-04:03 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 135478.81 | 605139.15 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 43778.10 | 223621.05 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19416.76 | 180687.16 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8831.11 | 118136.20 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 5974.65 | 107813.65 | 05-JUN-15:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 2092.43 | 80263.78 | 10-JUL-15:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 3044.24 | 79717.67 | 06-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 8234.20 | 124820.33 | 30-SEP-15:03 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 13692.48 | 124647.75 | 30-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 61808.18 | 551729.04 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 101827.17 | 291899.84 | 09-DEC-09:04 |
Annual Sum or Average | 0.00 | 47958.18 | ||||
Minimum of Months | 0.00 | 0.00 | 2092.43 | 79717.67 | ||
Maximum of Months | 0.00 | 0.00 | 176680.10 | 605139.15 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 327.36 | 34670.91 | 01-JAN-09:02 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 801.43 | 40473.98 | 24-FEB-16:03 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 5757.60 | 261620.13 | 25-MAR-15:01 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 37190.58 | 475730.28 | 18-APR-15:03 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84575.02 | 464042.06 | 31-MAY-18:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 203000.36 | 589831.84 | 11-JUN-15:03 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 274370.09 | 712951.97 | 26-JUL-18:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 239495.57 | 689003.38 | 21-AUG-21:13 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 110133.45 | 487640.23 | 06-SEP-15:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20035.70 | 438801.11 | 20-OCT-15:02 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 5713.92 | 192063.46 | 03-NOV-15:01 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 598.41 | 42016.34 | 02-DEC-09:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 82420.66 | 0.00 | ||||
Minimum of Months | 327.36 | 34670.91 | 0.00 | 0.00 | ||
Maximum of Months | 274370.09 | 712951.97 | 0.00 | 0.00 |
Report: FanReportMonthly
For: FLR_3_DOAS_FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.270916E+10 | 0.73 | 1298.89 | 01-JAN-03:00 | 0.92 |
February | 0.244698E+10 | 0.73 | 1298.89 | 01-FEB-00:01 | 0.93 |
March | 0.270916E+10 | 0.73 | 1298.89 | 01-MAR-00:15 | 0.92 |
April | 0.262177E+10 | 0.73 | 1298.89 | 01-APR-08:62 | 0.92 |
May | 0.270916E+10 | 0.72 | 1298.89 | 01-MAY-15:02 | 0.92 |
June | 0.262177E+10 | 0.72 | 1298.89 | 01-JUN-08:62 | 0.92 |
July | 0.270916E+10 | 0.72 | 1298.89 | 01-JUL-08:11 | 0.91 |
August | 0.270916E+10 | 0.72 | 1298.89 | 01-AUG-08:11 | 0.91 |
September | 0.262177E+10 | 0.72 | 1298.89 | 01-SEP-08:12 | 0.91 |
October | 0.270916E+10 | 0.73 | 1298.89 | 01-OCT-15:01 | 0.92 |
November | 0.262177E+10 | 0.73 | 1298.89 | 03-NOV-15:01 | 0.92 |
December | 0.270916E+10 | 0.73 | 1298.89 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.318982E+11 | 0.73 | |||
Minimum of Months | 0.244698E+10 | 0.72 | 1298.89 | 0.91 | |
Maximum of Months | 0.270916E+10 | 0.73 | 1298.89 | 0.93 |
Report: FanReportMonthly
For: VAV WITH REHEAT_FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333180E+11 | 0.86 | 19327.63 | 12-JAN-22:00 | 1.11 |
February | 0.308187E+11 | 0.87 | 19774.14 | 24-FEB-21:10 | 1.12 |
March | 0.358702E+11 | 0.89 | 21697.94 | 23-MAR-21:00 | 1.18 |
April | 0.351541E+11 | 0.90 | 23362.26 | 19-APR-21:00 | 1.24 |
May | 0.359624E+11 | 0.89 | 22489.54 | 22-MAY-21:00 | 1.21 |
June | 0.336794E+11 | 0.87 | 22387.40 | 01-JUN-21:00 | 1.20 |
July | 0.338169E+11 | 0.86 | 17942.99 | 10-JUL-21:00 | 1.05 |
August | 0.341915E+11 | 0.86 | 19163.62 | 16-AUG-21:00 | 1.09 |
September | 0.345417E+11 | 0.88 | 24185.17 | 25-SEP-21:00 | 1.26 |
October | 0.374739E+11 | 0.91 | 25227.18 | 24-OCT-21:00 | 1.30 |
November | 0.347038E+11 | 0.89 | 24793.39 | 03-NOV-20:10 | 1.29 |
December | 0.344326E+11 | 0.87 | 20362.78 | 04-DEC-22:00 | 1.14 |
Annual Sum or Average | 0.413963E+12 | 0.88 | |||
Minimum of Months | 0.308187E+11 | 0.86 | 17942.99 | 1.05 | |
Maximum of Months | 0.374739E+11 | 0.91 | 25227.18 | 1.30 |
Report: FanReportMonthly
For: LAUNDRY_FLR_1 EXHAUST FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.205205E+09 | 0.28 | 76.61 | 01-JAN-00:10 | 0.28 |
February | 0.185347E+09 | 0.28 | 76.61 | 01-FEB-00:01 | 0.28 |
March | 0.205205E+09 | 0.28 | 76.61 | 01-MAR-00:03 | 0.28 |
April | 0.198586E+09 | 0.28 | 76.61 | 01-APR-00:10 | 0.28 |
May | 0.205205E+09 | 0.28 | 76.61 | 01-MAY-00:03 | 0.28 |
June | 0.198586E+09 | 0.28 | 76.61 | 01-JUN-00:05 | 0.28 |
July | 0.205205E+09 | 0.28 | 76.61 | 01-JUL-00:10 | 0.28 |
August | 0.205205E+09 | 0.28 | 76.61 | 01-AUG-00:10 | 0.28 |
September | 0.198586E+09 | 0.28 | 76.61 | 01-SEP-00:10 | 0.28 |
October | 0.205205E+09 | 0.28 | 76.61 | 01-OCT-00:05 | 0.28 |
November | 0.198586E+09 | 0.28 | 76.61 | 01-NOV-00:05 | 0.28 |
December | 0.205205E+09 | 0.28 | 76.61 | 01-DEC-00:03 | 0.28 |
Annual Sum or Average | 0.241613E+10 | 0.28 | |||
Minimum of Months | 0.185347E+09 | 0.28 | 76.61 | 0.28 | |
Maximum of Months | 0.205205E+09 | 0.28 | 76.61 | 0.28 |
Report: FanReportMonthly
For: LOBBY_FLR_1 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | -0.0 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | -0.0 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | -0.0 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | -0.0 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | -0.0 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | -0.0 | 0.00 | 01-DEC-00:03 | -0.0 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: DINING_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | -0.0 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | -0.0 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: BANQUET_FLR_6 DUMMY EXHAUST FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 |
March | 0.00 | -0.0 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 |
July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:05 | 0.00 |
November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_FLR_6 EXHAUST FAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.116283E+10 | 0.20 | 612.92 | 01-JAN-07:05 | 0.28 |
February | 0.105030E+10 | 0.20 | 612.92 | 01-FEB-07:03 | 0.28 |
March | 0.116283E+10 | 0.20 | 612.92 | 01-MAR-07:05 | 0.28 |
April | 0.112532E+10 | 0.20 | 612.92 | 01-APR-06:10 | 0.28 |
May | 0.116283E+10 | 0.20 | 612.92 | 01-MAY-06:05 | 0.28 |
June | 0.112532E+10 | 0.20 | 612.92 | 01-JUN-06:05 | 0.28 |
July | 0.116283E+10 | 0.20 | 612.92 | 01-JUL-06:05 | 0.28 |
August | 0.116283E+10 | 0.20 | 612.92 | 01-AUG-06:05 | 0.28 |
September | 0.112532E+10 | 0.20 | 612.92 | 01-SEP-06:05 | 0.28 |
October | 0.116283E+10 | 0.20 | 612.92 | 01-OCT-06:05 | 0.28 |
November | 0.112532E+10 | 0.20 | 612.92 | 01-NOV-06:05 | 0.28 |
December | 0.116283E+10 | 0.20 | 612.92 | 01-DEC-07:05 | 0.28 |
Annual Sum or Average | 0.136914E+11 | 0.20 | |||
Minimum of Months | 0.105030E+10 | 0.20 | 612.92 | 0.28 | |
Maximum of Months | 0.116283E+10 | 0.20 | 612.92 | 0.28 |
Report: FanReportMonthly
For: ROOM_1_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.688428E+09 | 0.54 | 820.79 | 01-JAN-09:02 | 0.60 |
February | 0.499587E+09 | 0.50 | 820.79 | 01-FEB-04:00 | 0.61 |
March | 0.274411E+09 | 0.45 | 820.79 | 01-MAR-09:02 | 0.60 |
April | 0.226080E+09 | 0.47 | 820.79 | 01-APR-08:62 | 0.60 |
May | 0.181279E+09 | 0.48 | 820.79 | 01-MAY-15:02 | 0.60 |
June | 0.280413E+09 | 0.52 | 820.79 | 01-JUN-08:62 | 0.60 |
July | 0.337650E+09 | 0.54 | 820.79 | 01-JUL-08:61 | 0.60 |
August | 0.297925E+09 | 0.54 | 820.79 | 01-AUG-08:61 | 0.60 |
September | 0.229189E+09 | 0.51 | 820.79 | 01-SEP-15:01 | 0.60 |
October | 0.176729E+09 | 0.45 | 820.79 | 01-OCT-15:01 | 0.60 |
November | 0.325537E+09 | 0.47 | 820.79 | 03-NOV-15:01 | 0.60 |
December | 0.517078E+09 | 0.51 | 820.79 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.403430E+10 | 0.50 | |||
Minimum of Months | 0.176729E+09 | 0.45 | 820.79 | 0.60 | |
Maximum of Months | 0.688428E+09 | 0.54 | 820.79 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.798492E+09 | 0.57 | 807.74 | 01-JAN-09:02 | 0.60 |
February | 0.562896E+09 | 0.53 | 807.74 | 01-FEB-02:00 | 0.61 |
March | 0.295459E+09 | 0.46 | 807.74 | 01-MAR-09:02 | 0.60 |
April | 0.202068E+09 | 0.43 | 807.74 | 01-APR-08:62 | 0.60 |
May | 0.130274E+09 | 0.39 | 807.74 | 01-MAY-15:02 | 0.60 |
June | 0.214745E+09 | 0.41 | 807.74 | 01-JUN-08:62 | 0.60 |
July | 0.226709E+09 | 0.39 | 807.74 | 01-JUL-08:11 | 0.60 |
August | 0.190310E+09 | 0.39 | 807.74 | 01-AUG-08:11 | 0.59 |
September | 0.158974E+09 | 0.41 | 807.74 | 01-SEP-15:01 | 0.60 |
October | 0.178603E+09 | 0.42 | 807.74 | 01-OCT-15:01 | 0.60 |
November | 0.370076E+09 | 0.48 | 807.74 | 03-NOV-15:01 | 0.60 |
December | 0.573515E+09 | 0.55 | 807.74 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.390212E+10 | 0.45 | |||
Minimum of Months | 0.130274E+09 | 0.39 | 807.74 | 0.59 | |
Maximum of Months | 0.798492E+09 | 0.57 | 807.74 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.437439E+09 | 0.17 | 1077.30 | 19-JAN-06:00 | 0.61 |
February | 99480349.75 | 0.04 | 1008.97 | 04-FEB-06:00 | 0.61 |
March | 0.116013E+09 | 0.08 | 989.57 | 24-MAR-13:00 | 0.60 |
April | 0.362248E+09 | 0.19 | 1290.41 | 15-APR-12:50 | 0.60 |
May | 0.758540E+09 | 0.46 | 855.23 | 31-MAY-19:05 | 0.60 |
June | 0.105975E+10 | 0.53 | 947.10 | 26-JUN-19:10 | 0.60 |
July | 0.128727E+10 | 0.59 | 899.08 | 02-JUL-19:10 | 0.60 |
August | 0.133791E+10 | 0.59 | 1146.56 | 29-AUG-13:15 | 0.60 |
September | 0.116024E+10 | 0.48 | 2043.33 | 07-SEP-12:40 | 0.60 |
October | 0.675517E+09 | 0.32 | 1944.73 | 20-OCT-12:30 | 0.60 |
November | 0.215974E+09 | 0.12 | 1894.42 | 04-NOV-12:30 | 0.60 |
December | 0.220715E+09 | 0.10 | 906.23 | 12-DEC-16:00 | 0.61 |
Annual Sum or Average | 0.773110E+10 | 0.31 | |||
Minimum of Months | 99480349.75 | 0.04 | 855.23 | 0.60 | |
Maximum of Months | 0.133791E+10 | 0.59 | 2043.33 | 0.61 |
Report: FanReportMonthly
For: ROOM_4_MULT19_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.330017E+10 | 0.48 | 4280.39 | 01-JAN-16:02 | 0.60 |
February | 0.240980E+10 | 0.46 | 4280.39 | 01-FEB-00:01 | 0.61 |
March | 0.106060E+10 | 0.42 | 4280.39 | 01-MAR-09:02 | 0.60 |
April | 0.900651E+09 | 0.40 | 4280.39 | 01-APR-08:62 | 0.60 |
May | 0.132220E+10 | 0.37 | 4280.39 | 01-MAY-08:61 | 0.60 |
June | 0.191616E+10 | 0.38 | 4280.39 | 01-JUN-08:62 | 0.60 |
July | 0.202078E+10 | 0.35 | 4280.39 | 01-JUL-08:11 | 0.60 |
August | 0.182024E+10 | 0.35 | 4280.39 | 01-AUG-08:11 | 0.60 |
September | 0.127462E+10 | 0.38 | 4280.39 | 01-SEP-08:12 | 0.60 |
October | 0.716644E+09 | 0.42 | 4280.39 | 01-OCT-08:61 | 0.60 |
November | 0.136027E+10 | 0.43 | 4280.39 | 01-NOV-15:01 | 0.60 |
December | 0.218983E+10 | 0.45 | 4280.39 | 01-DEC-16:01 | 0.60 |
Annual Sum or Average | 0.202920E+11 | 0.41 | |||
Minimum of Months | 0.716644E+09 | 0.35 | 4280.39 | 0.60 | |
Maximum of Months | 0.330017E+10 | 0.48 | 4280.39 | 0.61 |
Report: FanReportMonthly
For: ROOM_5_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.661897E+09 | 0.54 | 736.19 | 01-JAN-09:02 | 0.60 |
February | 0.468329E+09 | 0.49 | 736.19 | 01-FEB-02:15 | 0.61 |
March | 0.250271E+09 | 0.45 | 736.19 | 01-MAR-09:02 | 0.60 |
April | 0.204274E+09 | 0.47 | 736.19 | 01-APR-08:62 | 0.60 |
May | 0.181890E+09 | 0.51 | 736.19 | 01-MAY-08:61 | 0.60 |
June | 0.271182E+09 | 0.54 | 736.19 | 01-JUN-08:62 | 0.60 |
July | 0.311813E+09 | 0.57 | 736.19 | 01-JUL-08:61 | 0.60 |
August | 0.273114E+09 | 0.56 | 736.19 | 01-AUG-08:61 | 0.60 |
September | 0.218254E+09 | 0.52 | 736.19 | 01-SEP-08:62 | 0.60 |
October | 0.159091E+09 | 0.46 | 736.19 | 01-OCT-08:61 | 0.60 |
November | 0.310688E+09 | 0.47 | 736.19 | 03-NOV-15:01 | 0.60 |
December | 0.486068E+09 | 0.51 | 736.19 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.379687E+10 | 0.51 | |||
Minimum of Months | 0.159091E+09 | 0.45 | 736.19 | 0.60 | |
Maximum of Months | 0.661897E+09 | 0.57 | 736.19 | 0.61 |
Report: FanReportMonthly
For: ROOM_6_FLR_3 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.762950E+09 | 0.57 | 731.96 | 01-JAN-09:02 | 0.60 |
February | 0.543713E+09 | 0.52 | 731.96 | 01-FEB-00:12 | 0.61 |
March | 0.274499E+09 | 0.45 | 731.96 | 01-MAR-09:02 | 0.60 |
April | 0.190673E+09 | 0.43 | 731.96 | 01-APR-08:62 | 0.60 |
May | 0.145143E+09 | 0.42 | 731.96 | 01-MAY-08:61 | 0.60 |
June | 0.223202E+09 | 0.43 | 731.96 | 01-JUN-08:62 | 0.60 |
July | 0.235096E+09 | 0.40 | 731.96 | 01-JUL-08:11 | 0.60 |
August | 0.194058E+09 | 0.40 | 731.96 | 01-AUG-08:11 | 0.59 |
September | 0.160015E+09 | 0.43 | 731.96 | 01-SEP-08:12 | 0.60 |
October | 0.162807E+09 | 0.42 | 731.96 | 01-OCT-08:61 | 0.60 |
November | 0.352880E+09 | 0.49 | 731.96 | 09-NOV-16:02 | 0.60 |
December | 0.549079E+09 | 0.56 | 731.96 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.379412E+10 | 0.46 | |||
Minimum of Months | 0.145143E+09 | 0.40 | 731.96 | 0.59 | |
Maximum of Months | 0.762950E+09 | 0.57 | 731.96 | 0.61 |
Report: FanReportMonthly
For: ROOM_1_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.210128E+09 | 0.56 | 213.58 | 01-JAN-09:02 | 0.60 |
February | 0.142277E+09 | 0.52 | 213.58 | 01-FEB-03:50 | 0.61 |
March | 82776649.47 | 0.46 | 213.58 | 01-MAR-09:02 | 0.60 |
April | 67672635.05 | 0.48 | 213.58 | 01-APR-08:62 | 0.60 |
May | 54875568.39 | 0.50 | 213.58 | 01-MAY-15:02 | 0.60 |
June | 85024375.14 | 0.53 | 213.58 | 01-JUN-08:62 | 0.60 |
July | 0.102355E+09 | 0.56 | 213.58 | 01-JUL-08:61 | 0.60 |
August | 89226166.35 | 0.55 | 213.58 | 01-AUG-08:61 | 0.59 |
September | 68154253.82 | 0.51 | 213.58 | 01-SEP-15:01 | 0.60 |
October | 53891622.78 | 0.45 | 213.58 | 01-OCT-15:01 | 0.60 |
November | 0.102622E+09 | 0.49 | 213.58 | 03-NOV-15:01 | 0.60 |
December | 0.155900E+09 | 0.53 | 213.58 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.121490E+10 | 0.51 | |||
Minimum of Months | 53891622.78 | 0.45 | 213.58 | 0.59 | |
Maximum of Months | 0.210128E+09 | 0.56 | 213.58 | 0.61 |
Report: FanReportMonthly
For: ROOM_2_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.237602E+09 | 0.59 | 210.06 | 01-JAN-09:02 | 0.60 |
February | 0.160879E+09 | 0.55 | 210.06 | 01-FEB-01:40 | 0.61 |
March | 90371640.12 | 0.49 | 210.06 | 01-MAR-09:02 | 0.60 |
April | 60662943.11 | 0.44 | 210.06 | 01-APR-08:62 | 0.60 |
May | 40915230.65 | 0.42 | 210.06 | 01-MAY-15:02 | 0.60 |
June | 68866015.61 | 0.42 | 210.06 | 01-JUN-08:62 | 0.60 |
July | 74266351.11 | 0.40 | 210.06 | 01-JUL-08:11 | 0.60 |
August | 61646191.47 | 0.40 | 210.06 | 01-AUG-08:11 | 0.59 |
September | 49269232.10 | 0.42 | 210.06 | 01-SEP-15:01 | 0.60 |
October | 54375754.67 | 0.42 | 210.06 | 01-OCT-15:01 | 0.60 |
November | 0.114445E+09 | 0.51 | 210.06 | 01-NOV-08:62 | 0.60 |
December | 0.176194E+09 | 0.58 | 210.06 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.118949E+10 | 0.47 | |||
Minimum of Months | 40915230.65 | 0.40 | 210.06 | 0.59 | |
Maximum of Months | 0.237602E+09 | 0.59 | 210.06 | 0.61 |
Report: FanReportMonthly
For: ROOM_3_MULT9_FLR_6 FAN COILFAN
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.651282E+09 | 0.50 | 821.14 | 01-JAN-09:02 | 0.60 |
February | 0.441965E+09 | 0.48 | 821.14 | 01-FEB-05:05 | 0.61 |
March | 0.289914E+09 | 0.49 | 821.14 | 01-MAR-09:02 | 0.60 |
April | 0.269077E+09 | 0.49 | 821.14 | 01-APR-15:02 | 0.60 |
May | 0.236885E+09 | 0.50 | 821.14 | 01-MAY-08:61 | 0.60 |
June | 0.352260E+09 | 0.53 | 821.14 | 01-JUN-08:62 | 0.60 |
July | 0.425408E+09 | 0.55 | 821.14 | 01-JUL-08:61 | 0.60 |
August | 0.422628E+09 | 0.55 | 821.14 | 01-AUG-08:61 | 0.59 |
September | 0.367383E+09 | 0.53 | 821.14 | 01-SEP-08:62 | 0.60 |
October | 0.268811E+09 | 0.50 | 821.14 | 01-OCT-08:61 | 0.60 |
November | 0.341447E+09 | 0.48 | 821.14 | 01-NOV-15:01 | 0.60 |
December | 0.533949E+09 | 0.52 | 821.14 | 01-DEC-09:02 | 0.60 |
Annual Sum or Average | 0.460101E+10 | 0.51 | |||
Minimum of Months | 0.236885E+09 | 0.48 | 821.14 | 0.59 | |
Maximum of Months | 0.651282E+09 | 0.55 | 821.14 | 0.61 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.131087E+10 | 0.117979E+10 | 3477.60 | 19-JAN-06:00 | 3129.84 | 3129.84 | 49.95 | 13.52 |
February | 0.107902E+10 | 0.971119E+09 | 3445.88 | 04-FEB-06:00 | 3101.29 | 3101.29 | 49.68 | 13.48 |
March | 63776451.70 | 57398806.53 | 253.07 | 05-MAR-24:00 | 227.77 | 227.77 | 50.23 | 4.49 |
April | 18520382.12 | 16668343.91 | 125.28 | 03-APR-08:62 | 112.75 | 112.75 | 46.63 | 3.23 |
May | 3495333.74 | 3145800.36 | 41.68 | 02-MAY-18:04 | 37.52 | 37.52 | 44.79 | 1.86 |
June | 2128833.79 | 1915950.41 | 31.73 | 01-JUN-15:05 | 28.56 | 28.56 | 44.55 | 1.60 |
July | 461382.16 | 415243.95 | 12.23 | 10-JUL-15:06 | 11.01 | 11.01 | 39.36 | 0.93 |
August | 785106.20 | 706595.58 | 13.64 | 06-AUG-22:10 | 12.28 | 12.28 | 44.31 | 0.99 |
September | 4186255.94 | 3767630.34 | 42.25 | 30-SEP-15:03 | 38.02 | 38.02 | 44.05 | 1.87 |
October | 11190292.70 | 10071263.43 | 48.66 | 30-OCT-08:05 | 43.79 | 43.79 | 45.20 | 2.02 |
November | 0.225338E+09 | 0.202805E+09 | 3003.73 | 26-NOV-07:00 | 2703.35 | 2703.35 | 49.66 | 12.77 |
December | 0.276219E+09 | 0.248597E+09 | 676.83 | 09-DEC-09:02 | 609.15 | 609.15 | 50.32 | 6.93 |
Annual Sum or Average | 0.299600E+10 | 0.269640E+10 | ||||||
Minimum of Months | 461382.16 | 415243.95 | 12.23 | 11.01 | 11.01 | 39.36 | 0.93 | |
Maximum of Months | 0.131087E+10 | 0.117979E+10 | 3477.60 | 3129.84 | 3129.84 | 50.32 | 13.52 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 149588.94 | 134630.05 | 15.35 | 16-JAN-09:02 | 13.81 | 13.81 | 6.71 | 1.69 |
February | 449650.73 | 404685.65 | 34.33 | 25-FEB-09:02 | 30.89 | 30.89 | 6.71 | 2.73 |
March | 6345294.02 | 5710764.62 | 214.15 | 19-MAR-15:01 | 192.74 | 192.74 | 6.71 | 7.02 |
April | 86057640.42 | 77451876.38 | 704.20 | 18-APR-15:03 | 633.78 | 633.78 | 6.71 | 12.09 |
May | 0.173258E+09 | 0.155933E+09 | 723.97 | 31-MAY-18:02 | 651.57 | 651.57 | 6.71 | 12.24 |
June | 0.571286E+09 | 0.514157E+09 | 1049.26 | 26-JUN-18:02 | 944.33 | 944.33 | 6.71 | 14.36 |
July | 0.820546E+09 | 0.738491E+09 | 1538.83 | 26-JUL-18:02 | 1384.95 | 1384.95 | 6.71 | 16.88 |
August | 0.683088E+09 | 0.614779E+09 | 1353.27 | 21-AUG-21:11 | 1217.94 | 1217.94 | 6.71 | 16.00 |
September | 0.265546E+09 | 0.238991E+09 | 741.61 | 06-SEP-15:03 | 667.45 | 667.45 | 6.71 | 12.37 |
October | 28676620.73 | 25808958.65 | 826.51 | 20-OCT-15:02 | 743.86 | 743.86 | 6.71 | 12.96 |
November | 6283979.86 | 5655581.87 | 215.64 | 05-NOV-15:01 | 194.08 | 194.08 | 6.71 | 7.05 |
December | 297616.28 | 267854.66 | 28.93 | 03-DEC-09:02 | 26.04 | 26.04 | 6.71 | 2.47 |
Annual Sum or Average | 0.264198E+10 | 0.237779E+10 | ||||||
Minimum of Months | 149588.94 | 134630.05 | 15.35 | 13.81 | 13.81 | 6.71 | 1.69 | |
Maximum of Months | 0.820546E+09 | 0.738491E+09 | 1538.83 | 1384.95 | 1384.95 | 6.71 | 16.88 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.128314E+09 | 38494137.67 | 47.91 | 01-JAN-00:10 | 14.37 | 14.37 | 47.41 | 0.37 |
February | 0.115896E+09 | 34768898.54 | 47.91 | 01-FEB-00:01 | 14.37 | 14.37 | 46.49 | 0.37 |
March | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAR-00:03 | 14.37 | 14.37 | 47.37 | 0.37 |
April | 0.124175E+09 | 37252391.29 | 47.91 | 01-APR-00:10 | 14.37 | 14.37 | 51.11 | 0.37 |
May | 0.128314E+09 | 38494137.67 | 47.91 | 01-MAY-00:03 | 14.37 | 14.37 | 50.02 | 0.37 |
June | 0.124175E+09 | 37252391.29 | 47.91 | 01-JUN-00:05 | 14.37 | 14.37 | 50.76 | 0.37 |
July | 0.128314E+09 | 38494137.67 | 47.91 | 01-JUL-00:10 | 14.37 | 14.37 | 52.02 | 0.37 |
August | 0.128314E+09 | 38494137.67 | 47.91 | 01-AUG-00:10 | 14.37 | 14.37 | 52.57 | 0.37 |
September | 0.124175E+09 | 37252391.29 | 47.91 | 01-SEP-00:10 | 14.37 | 14.37 | 52.00 | 0.37 |
October | 0.128314E+09 | 38494137.67 | 47.91 | 01-OCT-00:05 | 14.37 | 14.37 | 51.70 | 0.37 |
November | 0.124175E+09 | 37252391.29 | 47.91 | 01-NOV-00:05 | 14.37 | 14.37 | 51.92 | 0.37 |
December | 0.128314E+09 | 38494137.67 | 47.91 | 01-DEC-00:03 | 14.37 | 14.37 | 48.35 | 0.37 |
Annual Sum or Average | 0.151079E+10 | 0.453237E+09 | ||||||
Minimum of Months | 0.115896E+09 | 34768898.54 | 47.91 | 14.37 | 14.37 | 46.49 | 0.37 | |
Maximum of Months | 0.128314E+09 | 38494137.67 | 47.91 | 14.37 | 14.37 | 52.57 | 0.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.372452E+09 | 0.335207E+09 | 1787.13 | 01-JAN-09:02 | 1608.41 | 1608.41 | 6.99 | 28.02 |
February | 0.688901E+09 | 0.620011E+09 | 1787.13 | 01-FEB-16:02 | 1608.41 | 1608.41 | 6.77 | 28.02 |
March | 0.182712E+10 | 0.164441E+10 | 1787.13 | 01-MAR-19:05 | 1608.41 | 1608.41 | 6.76 | 28.02 |
April | 0.289350E+10 | 0.260415E+10 | 1787.13 | 01-APR-08:62 | 1608.41 | 1608.41 | 6.96 | 28.02 |
May | 0.468691E+10 | 0.421822E+10 | 1787.13 | 01-MAY-00:03 | 1608.41 | 1608.41 | 6.77 | 28.02 |
June | 0.457084E+10 | 0.411376E+10 | 1787.13 | 01-JUN-00:05 | 1608.41 | 1608.41 | 7.30 | 28.02 |
July | 0.478664E+10 | 0.430797E+10 | 1787.13 | 01-JUL-00:10 | 1608.41 | 1608.41 | 8.43 | 28.02 |
August | 0.478664E+10 | 0.430797E+10 | 1787.13 | 01-AUG-00:10 | 1608.41 | 1608.41 | 9.09 | 28.02 |
September | 0.438989E+10 | 0.395091E+10 | 1787.13 | 01-SEP-00:10 | 1608.41 | 1608.41 | 7.98 | 28.02 |
October | 0.351066E+10 | 0.315960E+10 | 1787.13 | 01-OCT-06:05 | 1608.41 | 1608.41 | 6.72 | 28.02 |
November | 0.168511E+10 | 0.151660E+10 | 1787.13 | 01-NOV-05:03 | 1608.41 | 1608.41 | 6.74 | 28.02 |
December | 0.578015E+09 | 0.520214E+09 | 1787.13 | 01-DEC-09:03 | 1608.41 | 1608.41 | 6.80 | 28.02 |
Annual Sum or Average | 0.347767E+11 | 0.312990E+11 | ||||||
Minimum of Months | 0.372452E+09 | 0.335207E+09 | 1787.13 | 1608.41 | 1608.41 | 6.72 | 28.02 | |
Maximum of Months | 0.478664E+10 | 0.430797E+10 | 1787.13 | 1608.41 | 1608.41 | 9.09 | 28.02 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 47.41 | 59.76 | 31415.12 | 64790.88 | 31-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 46.49 | 58.98 | 32041.30 | 65233.53 | 21-FEB-07:15 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 47.37 | 59.27 | 31752.80 | 65113.59 | 01-MAR-07:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 51.11 | 59.94 | 30567.50 | 63302.57 | 03-APR-06:15 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 50.02 | 59.91 | 28792.84 | 60316.27 | 01-MAY-06:15 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 50.76 | 58.32 | 26917.72 | 56358.47 | 01-JUN-06:15 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 52.02 | 59.00 | 25330.11 | 52724.91 | 03-JUL-06:10 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 52.57 | 59.28 | 24629.18 | 50624.68 | 01-AUG-06:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 52.00 | 58.56 | 25017.37 | 51712.22 | 29-SEP-07:00 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 51.70 | 59.49 | 26239.55 | 55018.82 | 31-OCT-06:15 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 51.92 | 59.89 | 28109.49 | 58907.05 | 30-NOV-07:15 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 48.35 | 59.88 | 29986.60 | 62311.88 | 29-DEC-07:15 |
Annual Sum or Average | 0.00 | 28378.22 | ||||||
Minimum of Months | 0.00 | 0.00 | 46.49 | 58.32 | 24629.18 | 50624.68 | ||
Maximum of Months | 0.00 | 0.00 | 52.57 | 59.94 | 32041.30 | 65233.53 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 52.07 | 60.00 | 176680.10 | 575877.88 | 31-JAN-04:03 |
February | 0.00 | 0.00 | 01-FEB-00:01 | 50.11 | 60.00 | 135478.81 | 605139.15 | 02-FEB-06:00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 50.42 | 60.00 | 43778.10 | 223621.05 | 05-MAR-19:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 54.44 | 60.00 | 19416.76 | 180687.16 | 03-APR-08:62 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 46.47 | 60.00 | 8831.11 | 118136.20 | 02-MAY-18:04 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 45.89 | 45.89 | 5974.65 | 107813.65 | 05-JUN-15:05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 41.69 | 60.00 | 2092.43 | 80263.78 | 10-JUL-15:06 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 40.39 | 60.00 | 3044.24 | 79717.67 | 06-AUG-08:04 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 38.66 | 60.00 | 8234.20 | 124820.33 | 30-SEP-15:03 |
October | 0.00 | 0.00 | 01-OCT-00:05 | 54.14 | 60.00 | 13692.48 | 124647.75 | 30-OCT-08:05 |
November | 0.00 | 0.00 | 01-NOV-00:05 | 54.93 | 60.00 | 61808.18 | 551729.04 | 26-NOV-07:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 52.26 | 60.00 | 101827.17 | 291899.84 | 09-DEC-09:04 |
Annual Sum or Average | 0.00 | 47958.18 | ||||||
Minimum of Months | 0.00 | 0.00 | 38.66 | 45.89 | 2092.43 | 79717.67 | ||
Maximum of Months | 0.00 | 0.00 | 54.93 | 60.00 | 176680.10 | 605139.15 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 327.36 | 34670.91 | 01-JAN-09:02 | 6.99 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 801.43 | 40473.98 | 24-FEB-16:03 | 7.04 | 6.70 | 0.00 | 0.00 | 01-FEB-00:01 |
March | 5757.60 | 261620.13 | 25-MAR-15:01 | 8.93 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 37190.58 | 475730.28 | 18-APR-15:03 | 10.75 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84575.02 | 464042.06 | 31-MAY-18:03 | 10.65 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 203000.36 | 589831.84 | 11-JUN-15:03 | 11.72 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 274370.09 | 712951.97 | 26-JUL-18:03 | 12.77 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 239495.57 | 689003.38 | 21-AUG-21:13 | 12.57 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 110133.45 | 487640.23 | 06-SEP-15:03 | 10.85 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 20035.70 | 438801.11 | 20-OCT-15:02 | 10.44 | 6.70 | 0.00 | 0.00 | 01-OCT-00:05 |
November | 5713.92 | 192063.46 | 03-NOV-15:01 | 8.33 | 6.70 | 0.00 | 0.00 | 01-NOV-00:05 |
December | 598.41 | 42016.34 | 02-DEC-09:02 | 7.06 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 82420.66 | 0.00 | ||||||
Minimum of Months | 327.36 | 34670.91 | 6.99 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 274370.09 | 712951.97 | 12.77 | 6.70 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.04 | 3.31 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.04 | 3.31 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.04 | 3.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 3.13 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 3.13 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 3.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.08 | 1.68 |
February | 0.17 | 1.68 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.08 | 1.68 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 1.68 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.17 | 1.68 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.48 | 56.92 |
February | 0.25 | 56.92 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.50 | 56.92 |
July | 0.67 | 56.92 |
August | 0.33 | 56.92 |
September | 0.17 | 56.92 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 2.40 | 56.92 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.67 | 56.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.41 | 114.56 |
February | 0.08 | 126.73 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.49 | 116.62 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.41 | 126.73 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.46 | 0.62 |
February | 2.38 | 0.65 |
March | 1.84 | 0.69 |
April | 1.07 | 0.67 |
May | 1.49 | 0.71 |
June | 2.86 | 0.53 |
July | 3.47 | 0.54 |
August | 2.93 | 0.53 |
September | 1.97 | 0.49 |
October | 0.79 | 0.81 |
November | 1.97 | 0.59 |
December | 5.53 | 0.67 |
Annual Sum or Average | 30.76 | 0.61 |
Minimum of Months | 0.79 | 0.49 |
Maximum of Months | 5.53 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.99 | 0.63 |
February | 2.10 | 0.67 |
March | 1.94 | 0.65 |
April | 1.57 | 0.68 |
May | 2.53 | 0.74 |
June | 3.71 | 0.65 |
July | 4.03 | 0.58 |
August | 3.34 | 0.58 |
September | 2.18 | 0.68 |
October | 0.52 | 0.78 |
November | 2.06 | 0.54 |
December | 5.53 | 0.64 |
Annual Sum or Average | 32.48 | 0.64 |
Minimum of Months | 0.52 | 0.54 |
Maximum of Months | 5.53 | 0.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.03 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.03 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.03 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.27 | 0.63 |
February | 0.72 | 0.68 |
March | 0.31 | 0.81 |
April | 0.39 | 0.86 |
May | 2.29 | 0.80 |
June | 3.89 | 0.80 |
July | 2.96 | 0.79 |
August | 2.74 | 0.91 |
September | 1.59 | 0.81 |
October | 0.36 | 0.80 |
November | 0.78 | 0.64 |
December | 1.38 | 0.61 |
Annual Sum or Average | 21.66 | 0.76 |
Minimum of Months | 0.31 | 0.61 |
Maximum of Months | 4.27 | 0.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.42 | 0.62 |
February | 1.94 | 0.70 |
March | 1.11 | 0.70 |
April | 0.85 | 0.57 |
May | 3.15 | 0.62 |
June | 2.25 | 0.64 |
July | 2.04 | 0.67 |
August | 2.74 | 0.72 |
September | 1.56 | 0.64 |
October | 0.64 | 0.41 |
November | 1.92 | 0.60 |
December | 5.31 | 0.67 |
Annual Sum or Average | 27.92 | 0.65 |
Minimum of Months | 0.64 | 0.41 |
Maximum of Months | 5.31 | 0.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.92 | 0.60 |
February | 2.61 | 0.62 |
March | 1.31 | 0.66 |
April | 0.88 | 0.46 |
May | 2.77 | 0.57 |
June | 3.42 | 0.70 |
July | 3.40 | 0.64 |
August | 2.15 | 0.62 |
September | 1.78 | 0.57 |
October | 0.00 | 0.00 |
November | 2.17 | 0.56 |
December | 5.79 | 0.63 |
Annual Sum or Average | 30.20 | 0.62 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 5.79 | 0.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.61 | 0.55 |
February | 1.53 | 0.63 |
March | 1.71 | 0.70 |
April | 0.93 | 0.65 |
May | 1.82 | 0.63 |
June | 3.06 | 0.52 |
July | 3.54 | 0.50 |
August | 3.01 | 0.52 |
September | 1.68 | 0.48 |
October | 0.79 | 0.81 |
November | 1.51 | 0.54 |
December | 3.42 | 0.66 |
Annual Sum or Average | 25.62 | 0.58 |
Minimum of Months | 0.79 | 0.48 |
Maximum of Months | 3.54 | 0.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.35 | 0.61 |
February | 1.06 | 0.56 |
March | 2.24 | 0.64 |
April | 1.71 | 0.68 |
May | 3.25 | 0.70 |
June | 3.64 | 0.74 |
July | 4.77 | 0.63 |
August | 4.19 | 0.62 |
September | 2.76 | 0.62 |
October | 1.08 | 0.69 |
November | 1.47 | 0.52 |
December | 2.19 | 0.65 |
Annual Sum or Average | 29.71 | 0.65 |
Minimum of Months | 1.06 | 0.52 |
Maximum of Months | 4.77 | 0.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.89 | 0.63 |
February | 2.08 | 0.70 |
March | 1.38 | 0.69 |
April | 1.10 | 0.67 |
May | 2.49 | 0.67 |
June | 3.67 | 0.56 |
July | 3.56 | 0.52 |
August | 3.33 | 0.53 |
September | 1.54 | 0.63 |
October | 1.57 | 0.67 |
November | 1.36 | 0.56 |
December | 3.18 | 0.57 |
Annual Sum or Average | 28.14 | 0.60 |
Minimum of Months | 1.10 | 0.52 |
Maximum of Months | 3.67 | 0.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.51 | 112.32 |
February | 0.25 | 99.96 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.08 | 174.93 |
Annual Sum or Average | 0.85 | 114.83 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.51 | 174.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.60 | 121.07 |
February | 0.25 | 99.96 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.85 | 114.83 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.60 | 121.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.42 | 13.79 |
February | 0.25 | 9.64 |
March | 0.00 | 0.00 |
April | 0.17 | 12.23 |
May | 0.00 | 0.00 |
June | 0.17 | 20.01 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.08 | 20.01 |
October | 0.25 | 20.01 |
November | 0.08 | 20.01 |
December | 0.00 | 0.00 |
Annual Sum or Average | 1.42 | 15.44 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.42 | 20.01 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.357176E+12 | 0.00 | 0.00 | 0.333180E+11 | 0.00 | 0.00 |
February | 0.250930E+12 | 0.00 | 0.00 | 0.308187E+11 | 0.00 | 0.00 |
March | 0.840503E+11 | 0.00 | 0.450568E+10 | 0.358702E+11 | 0.00 | 0.00 |
April | 0.375532E+11 | 0.00 | 0.574084E+11 | 0.351541E+11 | 0.00 | 0.00 |
May | 0.225117E+11 | 0.00 | 0.143673E+12 | 0.359624E+11 | 0.00 | 0.00 |
June | 0.150646E+11 | 0.00 | 0.383642E+12 | 0.336794E+11 | 0.00 | 0.00 |
July | 0.556659E+10 | 0.00 | 0.559000E+12 | 0.338169E+11 | 0.00 | 0.00 |
August | 0.807950E+10 | 0.00 | 0.480463E+12 | 0.341915E+11 | 0.00 | 0.00 |
September | 0.190368E+11 | 0.00 | 0.184311E+12 | 0.345417E+11 | 0.00 | 0.00 |
October | 0.269908E+11 | 0.00 | 0.147997E+11 | 0.374739E+11 | 0.00 | 0.00 |
November | 0.116948E+12 | 0.00 | 0.155089E+10 | 0.347038E+11 | 0.00 | 0.00 |
December | 0.189824E+12 | 0.00 | 0.00 | 0.344326E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.113373E+13 | 0.00 | 0.182935E+13 | 0.413963E+12 | 0.00 | 0.00 |
Minimum of Months | 0.556659E+10 | 0.00 | 0.00 | 0.308187E+11 | 0.00 | 0.00 |
Maximum of Months | 0.357176E+12 | 0.00 | 0.559000E+12 | 0.374739E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.161893E+11 | 0.00 | 0.00 | 0.270916E+10 | 0.00 | 0.00 |
February | 0.109497E+11 | 0.00 | 0.00 | 0.244698E+10 | 0.00 | 0.00 |
March | 0.232508E+10 | 0.00 | 0.213241E+09 | 0.270916E+10 | 0.00 | 0.00 |
April | 0.437202E+09 | 0.00 | 0.333047E+10 | 0.262177E+10 | 0.00 | 0.00 |
May | 12817.22 | 0.00 | 0.752309E+10 | 0.270916E+10 | 0.00 | 0.00 |
June | 13003.92 | 0.00 | 0.244977E+11 | 0.262177E+10 | 0.00 | 0.00 |
July | 14745.14 | 0.00 | 0.373240E+11 | 0.270916E+10 | 0.00 | 0.00 |
August | 17470.68 | 0.00 | 0.304210E+11 | 0.270916E+10 | 0.00 | 0.00 |
September | 295258.74 | 0.00 | 0.109111E+11 | 0.262177E+10 | 0.00 | 0.00 |
October | 21307579.82 | 0.00 | 0.653299E+09 | 0.270916E+10 | 0.00 | 0.00 |
November | 0.380887E+10 | 0.00 | 24313945.23 | 0.262177E+10 | 0.00 | 0.00 |
December | 0.689066E+10 | 0.00 | 0.00 | 0.270916E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.406225E+11 | 0.00 | 0.114898E+12 | 0.318982E+11 | 0.00 | 0.00 |
Minimum of Months | 12817.22 | 0.00 | 0.00 | 0.244698E+10 | 0.00 | 0.00 |
Maximum of Months | 0.161893E+11 | 0.00 | 0.373240E+11 | 0.270916E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.333180E+11 | 0.00 | 0.357176E+12 | 0.790508E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308187E+11 | 0.00 | 0.250930E+12 | 0.591232E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.358702E+11 | 0.450568E+10 | 0.840503E+11 | 0.604362E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351541E+11 | 0.574084E+11 | 0.375532E+11 | 0.369550E+12 | 0.864156E+10 | 0.00 | 0.00 | 0.00 |
May | 0.359624E+11 | 0.143673E+12 | 0.225117E+11 | 0.912397E+11 | 0.100622E+11 | 0.00 | 0.00 | 0.00 |
June | 0.336794E+11 | 0.383642E+12 | 0.150646E+11 | 0.256585E+11 | 0.724952E+11 | 0.00 | 0.00 | 0.00 |
July | 0.338169E+11 | 0.559000E+12 | 0.556659E+10 | 0.264415E+10 | 0.894021E+11 | 0.00 | 0.00 | 0.00 |
August | 0.341915E+11 | 0.480463E+12 | 0.807950E+10 | 0.626736E+10 | 0.805653E+11 | 0.00 | 0.00 | 0.00 |
September | 0.345417E+11 | 0.184311E+12 | 0.190368E+11 | 0.105162E+12 | 0.156378E+11 | 0.00 | 0.00 | 0.00 |
October | 0.374739E+11 | 0.147997E+11 | 0.269908E+11 | 0.348021E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347038E+11 | 0.155089E+10 | 0.116948E+12 | 0.542855E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344326E+11 | 0.00 | 0.189824E+12 | 0.831883E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413963E+12 | 0.182935E+13 | 0.113373E+13 | 0.430938E+13 | 0.276804E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308187E+11 | 0.00 | 0.556659E+10 | 0.264415E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374739E+11 | 0.559000E+12 | 0.357176E+12 | 0.831883E+12 | 0.894021E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.270916E+10 | 0.00 | 0.161893E+11 | 0.673076E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.00 | 0.109497E+11 | 0.500371E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.213241E+09 | 0.232508E+10 | 0.512008E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.333047E+10 | 0.437202E+09 | 0.316424E+11 | 0.629111E+09 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 0.752309E+10 | 12817.22 | 0.102205E+11 | 0.579395E+09 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 0.244977E+11 | 13003.92 | 0.338770E+10 | 0.604385E+10 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 0.373240E+11 | 14745.14 | 0.480521E+09 | 0.676679E+10 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 0.304210E+11 | 17470.68 | 0.116585E+10 | 0.615189E+10 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 0.109111E+11 | 295258.74 | 0.108252E+11 | 0.154140E+10 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 0.653299E+09 | 21307579.82 | 0.307310E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 24313945.23 | 0.380887E+10 | 0.466886E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.00 | 0.689066E+10 | 0.706536E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.114898E+12 | 0.406225E+11 | 0.374341E+12 | 0.217124E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.244698E+10 | 0.00 | 12817.22 | 0.480521E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.373240E+11 | 0.161893E+11 | 0.706536E+11 | 0.676679E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV WITH REHEAT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.333180E+11 | 0.357176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.308187E+11 | 0.250930E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.358702E+11 | 0.840503E+11 | 0.450568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351541E+11 | 0.375532E+11 | 0.574084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359624E+11 | 0.225117E+11 | 0.143673E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.336794E+11 | 0.150646E+11 | 0.383642E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.338169E+11 | 0.556659E+10 | 0.559000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.341915E+11 | 0.807950E+10 | 0.480463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.345417E+11 | 0.190368E+11 | 0.184311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374739E+11 | 0.269908E+11 | 0.147997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.347038E+11 | 0.116948E+12 | 0.155089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344326E+11 | 0.189824E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.413963E+12 | 0.113373E+13 | 0.182935E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.308187E+11 | 0.556659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.374739E+11 | 0.357176E+12 | 0.559000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: FLR_3_DOAS
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.270916E+10 | 0.161893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244698E+10 | 0.109497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270916E+10 | 0.232508E+10 | 0.213241E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.262177E+10 | 0.437202E+09 | 0.333047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.270916E+10 | 12817.22 | 0.752309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.262177E+10 | 13003.92 | 0.244977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.270916E+10 | 14745.14 | 0.373240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270916E+10 | 17470.68 | 0.304210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.262177E+10 | 295258.74 | 0.109111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270916E+10 | 21307579.82 | 0.653299E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262177E+10 | 0.380887E+10 | 24313945.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270916E+10 | 0.689066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318982E+11 | 0.406225E+11 | 0.114898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.244698E+10 | 12817.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270916E+10 | 0.161893E+11 | 0.373240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.625025E+11 | 0.00 | 0.00 | 255913.72 | 0.00 | 0.147739E+11 | 0.185285E+10 | 0.00 | 1.04 |
February | 0.380759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266982E+11 | 0.00 | 0.00 | 1.04 |
March | 0.509058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
April | 0.424251E+11 | 0.00 | 0.00 | 0.00 | 0.909607E+09 | 0.00 | 0.00 | 0.00 | 1.04 |
May | 0.374915E+11 | 0.00 | 0.00 | 0.00 | 0.136105E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
June | 0.203466E+11 | 0.00 | 0.00 | 0.00 | 0.916132E+10 | 0.00 | 0.00 | 0.00 | 1.05 |
July | 0.102176E+11 | 0.00 | 0.00 | 0.00 | 0.154835E+11 | 0.00 | 0.00 | 0.00 | 1.05 |
August | 0.157518E+11 | 0.00 | 0.00 | 0.00 | 0.123815E+11 | 0.00 | 0.00 | 0.00 | 1.05 |
September | 0.212400E+11 | 0.00 | 0.00 | 9241794.33 | 0.133339E+10 | 0.00 | 0.125290E+11 | 0.00 | 1.06 |
October | 0.732342E+10 | 0.00 | 0.00 | 45236959.47 | 0.00 | 0.00 | 0.432905E+11 | 0.00 | 1.10 |
November | 0.185171E+11 | 0.00 | 0.00 | 34582977.68 | 0.00 | 0.00 | 0.377024E+11 | 0.00 | 1.09 |
December | 0.270638E+11 | 0.00 | 0.00 | 17504261.83 | 0.00 | 0.00 | 0.338203E+11 | 0.00 | 1.06 |
Annual Sum or Average | 0.351861E+12 | 0.00 | 0.00 | 0.106822E+09 | 0.406304E+11 | 0.414720E+11 | 0.129195E+12 | 0.00 | 1.06 |
Minimum of Months | 0.732342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
Maximum of Months | 0.625025E+11 | 0.00 | 0.00 | 45236959.47 | 0.154835E+11 | 0.266982E+11 | 0.432905E+11 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_1_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108082E+10 | 0.00 | 0.00 | 41272.50 | 0.00 | 0.879505E+10 | 96595369.29 | 0.00 | 2.37 |
February | 0.166940E+10 | 0.00 | 0.00 | 206945.79 | 0.00 | 0.638013E+10 | 0.132178E+09 | 0.00 | 2.38 |
March | 0.345413E+10 | 0.00 | 0.00 | 138043.08 | 0.00 | 0.280880E+10 | 0.154825E+09 | 0.00 | 2.39 |
April | 0.388266E+10 | 83018147.26 | 0.00 | 65278.53 | 34511658.58 | 0.138360E+10 | 80172188.39 | 0.00 | 2.38 |
May | 0.472339E+10 | 14321407.45 | 0.00 | 1192.81 | 0.157201E+09 | 0.00 | 1377081.34 | 0.00 | 2.39 |
June | 0.256336E+10 | 0.303115E+09 | 0.00 | 1832.00 | 0.851415E+09 | 0.00 | 764873.65 | 0.00 | 2.40 |
July | 0.128759E+10 | 0.360713E+09 | 0.00 | 58.88 | 0.159055E+10 | 0.00 | 57296.65 | 0.00 | 2.40 |
August | 0.197326E+10 | 0.429195E+09 | 0.00 | 58516.28 | 0.113145E+10 | 0.00 | 11756924.25 | 0.00 | 2.40 |
September | 0.387724E+10 | 0.140399E+09 | 0.00 | 554590.32 | 48239486.74 | 0.114391E+09 | 0.209996E+09 | 0.00 | 2.44 |
October | 0.514899E+10 | 0.00 | 0.00 | 1229792.72 | 0.00 | 0.346121E+09 | 0.666922E+09 | 0.00 | 2.43 |
November | 0.314963E+10 | 0.00 | 0.00 | 429328.38 | 0.00 | 0.349320E+10 | 0.249619E+09 | 0.00 | 2.40 |
December | 0.130843E+10 | 0.00 | 0.00 | 206354.60 | 0.00 | 0.605059E+10 | 0.219496E+09 | 0.00 | 2.37 |
Annual Sum or Average | 0.341189E+11 | 0.133076E+10 | 0.00 | 2933205.88 | 0.381337E+10 | 0.293719E+11 | 0.182376E+10 | 0.00 | 2.40 |
Minimum of Months | 0.108082E+10 | 0.00 | 0.00 | 58.88 | 0.00 | 0.00 | 57296.65 | 0.00 | 2.37 |
Maximum of Months | 0.514899E+10 | 0.429195E+09 | 0.00 | 1229792.72 | 0.159055E+10 | 0.879505E+10 | 0.666922E+09 | 0.00 | 2.44 |
Report: MechanicalVentilationLoadsMonthly
For: RETAIL_2_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.503674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214109E+10 | 0.00 | 0.00 | 1.47 |
February | 0.361501E+10 | 0.00 | 0.00 | 1531.30 | 0.00 | 0.224808E+10 | 12548514.93 | 0.00 | 1.48 |
March | 0.449889E+10 | 0.00 | 0.00 | 35289.28 | 0.00 | 0.00 | 0.118737E+09 | 0.00 | 1.49 |
April | 0.357483E+10 | 4833089.51 | 0.00 | 131969.90 | 77677281.66 | 0.00 | 0.273640E+09 | 0.00 | 1.49 |
May | 0.298668E+10 | 3328188.00 | 0.00 | 143045.36 | 0.120133E+09 | 0.00 | 0.414032E+09 | 0.00 | 1.49 |
June | 0.164650E+10 | 77696204.09 | 0.00 | 141191.08 | 0.753326E+09 | 0.00 | 0.199001E+09 | 0.00 | 1.50 |
July | 0.851498E+09 | 0.216803E+09 | 0.00 | 66473.00 | 0.118770E+10 | 0.00 | 75278184.75 | 0.00 | 1.50 |
August | 0.111767E+10 | 0.128764E+09 | 0.00 | 295478.04 | 0.994364E+09 | 0.00 | 0.310874E+09 | 0.00 | 1.50 |
September | 0.244812E+10 | 10997803.17 | 0.00 | 458082.56 | 0.109954E+09 | 0.00 | 0.575609E+09 | 0.00 | 1.49 |
October | 0.377430E+10 | 0.00 | 0.00 | 286410.58 | 0.00 | 0.00 | 0.590380E+09 | 0.00 | 1.49 |
November | 0.441269E+10 | 0.00 | 0.00 | 76518.58 | 0.00 | 0.329151E+09 | 0.184711E+09 | 0.00 | 1.48 |
December | 0.544274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
Annual Sum or Average | 0.394057E+11 | 0.442422E+09 | 0.00 | 1635989.69 | 0.324316E+10 | 0.471832E+10 | 0.275481E+10 | 0.00 | 1.49 |
Minimum of Months | 0.851498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
Maximum of Months | 0.544274E+10 | 0.216803E+09 | 0.00 | 458082.56 | 0.118770E+10 | 0.224808E+10 | 0.590380E+09 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.483609E+10 | 0.00 | 0.00 | 0.69 |
February | 0.297163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285227E+10 | 0.00 | 0.00 | 0.69 |
March | 0.438791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189073E+09 | 0.00 | 0.00 | 0.70 |
April | 0.381448E+10 | 0.00 | 0.00 | 0.00 | 81783605.79 | 0.00 | 0.00 | 0.00 | 0.69 |
May | 0.337090E+10 | 0.00 | 0.00 | 0.00 | 0.122373E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
June | 0.182939E+10 | 0.00 | 0.00 | 0.00 | 0.823703E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.918678E+09 | 0.00 | 0.00 | 0.00 | 0.139213E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.141626E+10 | 0.00 | 0.00 | 0.00 | 0.111324E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.299665E+10 | 0.00 | 0.00 | 0.00 | 0.119887E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 0.432617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
November | 0.398845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.894787E+09 | 0.00 | 0.00 | 0.69 |
December | 0.396574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142905E+10 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.362648E+11 | 0.00 | 0.00 | 0.00 | 0.365312E+10 | 0.102013E+11 | 0.00 | 0.00 | 0.69 |
Minimum of Months | 0.918678E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Maximum of Months | 0.438791E+10 | 0.00 | 0.00 | 0.00 | 0.139213E+10 | 0.483609E+10 | 0.00 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: STORAGE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 82272524.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295029E+10 | 0.00 | 0.00 | 0.51 |
February | 0.347398E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213501E+10 | 0.00 | 0.00 | 0.51 |
March | 0.966149E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984768E+09 | 0.00 | 0.00 | 0.51 |
April | 0.139396E+10 | 0.00 | 0.00 | 0.00 | 34859850.43 | 0.231946E+09 | 0.00 | 0.00 | 0.51 |
May | 0.143683E+10 | 0.00 | 0.00 | 0.00 | 52161048.64 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 0.779767E+09 | 0.00 | 0.00 | 0.00 | 0.351099E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
July | 0.391582E+09 | 0.00 | 0.00 | 0.00 | 0.593390E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.603673E+09 | 0.00 | 0.00 | 0.00 | 0.474511E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.127731E+10 | 0.00 | 0.00 | 0.00 | 51101077.97 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.184401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
November | 0.110854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.972915E+09 | 0.00 | 0.00 | 0.51 |
December | 0.191058E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210845E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.104225E+11 | 0.00 | 0.00 | 0.00 | 0.155712E+10 | 0.938338E+10 | 0.00 | 0.00 | 0.51 |
Minimum of Months | 82272524.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.184401E+10 | 0.00 | 0.00 | 0.00 | 0.593390E+09 | 0.295029E+10 | 0.00 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: LAUNDRY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.308562E+10 | 0.00 | 0.00 | 80086230.34 | 0.00 | 0.236504E+11 | 0.908260E+11 | 0.00 | 24.41 |
February | 0.150732E+10 | 0.00 | 0.00 | 72094639.70 | 0.00 | 0.249260E+11 | 0.691243E+11 | 0.00 | 24.50 |
March | 0.310200E+09 | 0.00 | 0.00 | 92741818.80 | 0.00 | 0.00 | 0.786342E+11 | 0.00 | 25.24 |
April | 0.271377E+09 | 0.120829E+10 | 0.00 | 87611794.93 | 50312945.81 | 0.00 | 0.651497E+11 | 0.00 | 24.89 |
May | 0.353436E+09 | 0.183829E+10 | 0.00 | 93349628.93 | 77753149.92 | 0.00 | 0.568544E+11 | 0.00 | 24.54 |
June | 0.215075E+09 | 0.126783E+11 | 0.00 | 60218429.56 | 0.342942E+09 | 0.00 | 0.301118E+11 | 0.00 | 23.95 |
July | 0.101979E+09 | 0.219211E+11 | 0.00 | 40233490.08 | 0.627084E+09 | 0.00 | 0.143461E+11 | 0.00 | 23.55 |
August | 0.163059E+09 | 0.174047E+11 | 0.00 | 56415402.17 | 0.452914E+09 | 0.00 | 0.228071E+11 | 0.00 | 23.80 |
September | 0.318141E+09 | 0.180166E+10 | 0.00 | 85297232.26 | 67467342.25 | 0.00 | 0.505685E+11 | 0.00 | 24.41 |
October | 0.342497E+09 | 0.00 | 0.00 | 92134936.84 | 0.00 | 0.00 | 0.744371E+11 | 0.00 | 25.14 |
November | 0.116863E+10 | 0.00 | 0.00 | 87709797.70 | 0.00 | 0.281781E+10 | 0.792251E+11 | 0.00 | 25.01 |
December | 0.673490E+09 | 0.00 | 0.00 | 91810313.32 | 0.00 | 0.00 | 0.914228E+11 | 0.00 | 24.76 |
Annual Sum or Average | 0.851082E+10 | 0.568523E+11 | 0.00 | 0.939704E+09 | 0.161847E+10 | 0.513942E+11 | 0.723507E+12 | 0.00 | 24.51 |
Minimum of Months | 0.101979E+09 | 0.00 | 0.00 | 40233490.08 | 0.00 | 0.00 | 0.143461E+11 | 0.00 | 23.55 |
Maximum of Months | 0.308562E+10 | 0.219211E+11 | 0.00 | 93349628.93 | 0.627084E+09 | 0.249260E+11 | 0.914228E+11 | 0.00 | 25.24 |
Report: MechanicalVentilationLoadsMonthly
For: CAFE_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249816E+11 | 0.00 | 0.00 | 564410.83 | 0.00 | 0.154624E+11 | 0.104036E+10 | 0.00 | 3.50 |
February | 0.187046E+11 | 0.00 | 0.00 | 1760781.18 | 0.00 | 0.129233E+11 | 0.241348E+10 | 0.00 | 3.53 |
March | 0.203873E+11 | 0.00 | 0.00 | 3291970.35 | 0.00 | 0.466599E+09 | 0.584915E+10 | 0.00 | 3.55 |
April | 0.139605E+11 | 0.414208E+09 | 0.00 | 5626522.55 | 71083207.22 | 73058495.10 | 0.820806E+10 | 0.00 | 3.54 |
May | 0.846272E+10 | 0.270512E+09 | 0.00 | 7714971.46 | 0.442981E+09 | 0.00 | 0.111834E+11 | 0.00 | 3.55 |
June | 0.410169E+10 | 0.306822E+10 | 0.00 | 6986658.34 | 0.173770E+10 | 0.00 | 0.655755E+10 | 0.00 | 3.56 |
July | 0.115872E+10 | 0.503469E+10 | 0.00 | 5813020.04 | 0.308468E+10 | 0.00 | 0.419178E+10 | 0.00 | 3.56 |
August | 0.154603E+10 | 0.398649E+10 | 0.00 | 10513998.50 | 0.250799E+10 | 0.00 | 0.670703E+10 | 0.00 | 3.57 |
September | 0.657781E+10 | 0.641573E+09 | 0.00 | 13827065.28 | 0.104498E+09 | 0.00 | 0.109296E+11 | 0.00 | 3.60 |
October | 0.113179E+11 | 0.00 | 0.00 | 13029367.05 | 0.00 | 0.00 | 0.143530E+11 | 0.00 | 3.62 |
November | 0.199322E+11 | 0.00 | 0.00 | 4811182.11 | 0.00 | 0.259322E+10 | 0.616286E+10 | 0.00 | 3.56 |
December | 0.241292E+11 | 0.00 | 0.00 | 1569324.11 | 0.00 | 0.546343E+10 | 0.195684E+10 | 0.00 | 3.51 |
Annual Sum or Average | 0.155260E+12 | 0.134157E+11 | 0.00 | 75509271.80 | 0.794893E+10 | 0.369821E+11 | 0.795531E+11 | 0.00 | 3.56 |
Minimum of Months | 0.115872E+10 | 0.00 | 0.00 | 564410.83 | 0.00 | 0.00 | 0.104036E+10 | 0.00 | 3.50 |
Maximum of Months | 0.249816E+11 | 0.503469E+10 | 0.00 | 13827065.28 | 0.308468E+10 | 0.154624E+11 | 0.143530E+11 | 0.00 | 3.62 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_FLR_1
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107172E+12 | 0.00 | 0.00 | 629417.29 | 0.00 | 0.401636E+11 | 0.158549E+10 | 0.00 | 1.82 |
February | 0.723041E+11 | 0.00 | 0.00 | 1981881.68 | 0.00 | 0.438040E+11 | 0.579505E+10 | 0.00 | 1.82 |
March | 0.765790E+11 | 0.00 | 0.00 | 9094824.61 | 0.00 | 0.00 | 0.192949E+11 | 0.00 | 1.84 |
April | 0.520881E+11 | 0.147710E+09 | 0.00 | 18566143.34 | 0.156418E+10 | 0.00 | 0.279493E+11 | 0.00 | 1.84 |
May | 0.323401E+11 | 0.130440E+09 | 0.00 | 28359414.31 | 0.243107E+10 | 0.00 | 0.383680E+11 | 0.00 | 1.85 |
June | 0.151987E+11 | 0.426927E+10 | 0.00 | 23750892.44 | 0.129826E+11 | 0.00 | 0.231216E+11 | 0.00 | 1.85 |
July | 0.558490E+10 | 0.102085E+11 | 0.00 | 15149238.06 | 0.189374E+11 | 0.00 | 0.136301E+11 | 0.00 | 1.85 |
August | 0.749239E+10 | 0.645806E+10 | 0.00 | 32193847.56 | 0.168561E+11 | 0.00 | 0.222521E+11 | 0.00 | 1.85 |
September | 0.258025E+11 | 0.716761E+09 | 0.00 | 38214818.62 | 0.179392E+10 | 0.00 | 0.373467E+11 | 0.00 | 1.85 |
October | 0.460756E+11 | 0.00 | 0.00 | 31426375.98 | 0.00 | 0.00 | 0.452255E+11 | 0.00 | 1.85 |
November | 0.753959E+11 | 0.00 | 0.00 | 13179944.18 | 0.00 | 0.544670E+10 | 0.215587E+11 | 0.00 | 1.84 |
December | 0.108650E+12 | 0.00 | 0.00 | 964857.38 | 0.00 | 0.00 | 0.427239E+10 | 0.00 | 1.82 |
Annual Sum or Average | 0.624684E+12 | 0.219307E+11 | 0.00 | 0.213512E+09 | 0.545652E+11 | 0.894143E+11 | 0.260400E+12 | 0.00 | 1.84 |
Minimum of Months | 0.558490E+10 | 0.00 | 0.00 | 629417.29 | 0.00 | 0.00 | 0.158549E+10 | 0.00 | 1.82 |
Maximum of Months | 0.108650E+12 | 0.102085E+11 | 0.00 | 38214818.62 | 0.189374E+11 | 0.438040E+11 | 0.452255E+11 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 24522083.95 | 0.00 | 0.00 | 53293.55 | 0.00 | 0.244185E+10 | 3663284.40 | 0.00 | 0.35 |
February | 33834408.68 | 0.00 | 0.00 | 478864.02 | 0.00 | 0.202461E+10 | 47038487.80 | 0.00 | 0.35 |
March | 66856201.24 | 0.00 | 0.00 | 1593049.09 | 0.00 | 0.115786E+10 | 0.229159E+09 | 0.00 | 0.36 |
April | 49959128.99 | 21802704.03 | 0.00 | 4876878.14 | 0.00 | 0.698175E+09 | 0.467045E+09 | 0.00 | 0.35 |
May | 43268201.52 | 26970643.40 | 32668.98 | 8894834.05 | 169642.25 | 0.147361E+09 | 0.775058E+09 | 8020.10 | 0.36 |
June | 15704155.00 | 0.290565E+09 | 113925.97 | 7126257.57 | 1050653.43 | 68522591.01 | 0.383644E+09 | 19829.55 | 0.36 |
July | 1910735.42 | 0.469381E+09 | 192238.37 | 5577170.84 | 190596.44 | 554467.02 | 0.194513E+09 | 39685.22 | 0.36 |
August | 275853.86 | 0.325369E+09 | 263233.40 | 7699486.00 | 3444752.44 | 620427.78 | 0.329421E+09 | 23491.51 | 0.36 |
September | 28382158.67 | 57799480.94 | 20272.57 | 7442465.65 | 91022.58 | 0.235582E+09 | 0.585552E+09 | 7704.45 | 0.36 |
October | 63913828.35 | 0.00 | 0.00 | 3705422.12 | 0.00 | 0.767438E+09 | 0.518000E+09 | 0.00 | 0.35 |
November | 51876262.79 | 0.00 | 0.00 | 829740.07 | 0.00 | 0.130077E+10 | 0.181954E+09 | 0.00 | 0.35 |
December | 38302859.04 | 0.00 | 0.00 | 100192.28 | 0.00 | 0.161076E+10 | 6779361.32 | 0.00 | 0.35 |
Annual Sum or Average | 0.418806E+09 | 0.119189E+10 | 622339.29 | 48377653.38 | 4946667.14 | 0.104541E+11 | 0.372183E+10 | 98730.83 | 0.35 |
Minimum of Months | 275853.86 | 0.00 | 0.00 | 53293.55 | 0.00 | 554467.02 | 3663284.40 | 0.00 | 0.35 |
Maximum of Months | 66856201.24 | 0.469381E+09 | 263233.40 | 8894834.05 | 3444752.44 | 0.244185E+10 | 0.775058E+09 | 39685.22 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 2319800.51 | 0.00 | 0.00 | 6777.84 | 0.00 | 0.246729E+10 | 478965.98 | 0.00 | 0.35 |
February | 15972506.45 | 0.00 | 0.00 | 180273.22 | 0.00 | 0.206829E+10 | 21517180.46 | 0.00 | 0.35 |
March | 57913671.88 | 0.00 | 0.00 | 835136.76 | 0.00 | 0.125825E+10 | 0.138470E+09 | 0.00 | 0.36 |
April | 87927322.02 | 19071501.04 | 8108.40 | 3422050.56 | 2715432.47 | 0.744511E+09 | 0.384197E+09 | 7662.12 | 0.35 |
May | 0.128646E+09 | 19616030.01 | 33136.34 | 7073180.68 | 7522023.75 | 0.144750E+09 | 0.694113E+09 | 9784.63 | 0.36 |
June | 74779987.52 | 0.253880E+09 | 129886.48 | 5092817.94 | 37731544.02 | 68743936.26 | 0.326380E+09 | 7513.19 | 0.36 |
July | 62730904.32 | 0.386879E+09 | 147847.98 | 4097106.17 | 82756106.19 | 336013.19 | 0.135391E+09 | 20987.25 | 0.36 |
August | 90726464.14 | 0.274672E+09 | 269584.55 | 5406521.91 | 54122707.66 | 658300.08 | 0.241225E+09 | 36365.33 | 0.36 |
September | 0.110958E+09 | 53074448.93 | 9738.27 | 4610456.20 | 4823265.44 | 0.269506E+09 | 0.471884E+09 | 11027.91 | 0.36 |
October | 88460962.89 | 0.00 | 0.00 | 1894848.94 | 0.00 | 0.931603E+09 | 0.331099E+09 | 0.00 | 0.35 |
November | 40795203.78 | 0.00 | 0.00 | 410131.07 | 0.00 | 0.139060E+10 | 0.103625E+09 | 0.00 | 0.35 |
December | 4777323.90 | 0.00 | 0.00 | 12302.26 | 0.00 | 0.165062E+10 | 536100.70 | 0.00 | 0.35 |
Annual Sum or Average | 0.766008E+09 | 0.100719E+10 | 598302.01 | 33041603.56 | 0.189671E+09 | 0.109952E+11 | 0.284892E+10 | 93340.43 | 0.36 |
Minimum of Months | 2319800.51 | 0.00 | 0.00 | 6777.84 | 0.00 | 336013.19 | 478965.98 | 0.00 | 0.35 |
Maximum of Months | 0.128646E+09 | 0.386879E+09 | 269584.55 | 7073180.68 | 82756106.19 | 0.246729E+10 | 0.694113E+09 | 36365.33 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.935051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167261E+09 | 0.00 | 0.00 | 0.02 |
February | 0.126794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
March | 0.711237E+09 | 0.00 | 0.00 | 802767.00 | 0.00 | 0.00 | 0.285523E+09 | 0.00 | 0.02 |
April | 0.701660E+09 | 51111750.32 | 0.00 | 612474.50 | 0.00 | 0.00 | 0.308221E+09 | 0.00 | 0.02 |
May | 0.260714E+09 | 94086954.10 | 0.00 | 789899.48 | 0.00 | 0.00 | 0.514709E+09 | 0.00 | 0.02 |
June | 0.195178E+09 | 0.361788E+09 | 0.00 | 683862.17 | 0.00 | 0.00 | 0.193880E+09 | 0.00 | 0.02 |
July | 7002900.14 | 0.579926E+09 | 0.00 | 402704.80 | 0.00 | 0.00 | 86182488.47 | 0.00 | 0.02 |
August | 0.00 | 0.509819E+09 | 0.00 | 590091.88 | 0.00 | 0.00 | 88283162.65 | 0.00 | 0.02 |
September | 0.218938E+09 | 78693715.33 | 0.00 | 1808851.40 | 0.00 | 0.00 | 0.509351E+09 | 0.00 | 0.02 |
October | 0.425832E+09 | 0.00 | 0.00 | 3523575.06 | 0.00 | 0.00 | 0.841132E+09 | 0.00 | 0.02 |
November | 0.928320E+09 | 0.00 | 0.00 | 984750.38 | 0.00 | 0.00 | 0.222526E+09 | 0.00 | 0.02 |
December | 0.740865E+09 | 0.00 | 0.00 | 4353.75 | 0.00 | 0.164039E+09 | 7260795.92 | 0.00 | 0.02 |
Annual Sum or Average | 0.639274E+10 | 0.167543E+10 | 0.00 | 10203330.41 | 0.00 | 0.331300E+09 | 0.305707E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.126794E+10 | 0.579926E+09 | 0.00 | 3523575.06 | 0.00 | 0.167261E+09 | 0.841132E+09 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_4_MULT19_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.638965E+09 | 0.00 | 0.00 | 902983.18 | 0.00 | 0.318519E+11 | 0.996768E+09 | 0.00 | 0.40 |
February | 0.726956E+09 | 0.00 | 0.00 | 3464245.54 | 0.00 | 0.246041E+11 | 0.321725E+10 | 0.00 | 0.40 |
March | 0.110377E+10 | 0.00 | 0.00 | 20026526.18 | 0.00 | 0.910549E+10 | 0.950334E+10 | 0.00 | 0.40 |
April | 0.128677E+10 | 0.220262E+09 | 555006.57 | 46890278.34 | 74761112.77 | 0.228580E+10 | 0.129216E+11 | 14133.79 | 0.40 |
May | 0.176107E+10 | 0.216892E+09 | 286067.51 | 0.105974E+09 | 0.151310E+09 | 30746423.68 | 0.113152E+11 | 20352.27 | 0.40 |
June | 0.104085E+10 | 0.337049E+10 | 541733.88 | 78431746.18 | 0.584368E+09 | 13049507.22 | 0.530749E+10 | 10541.86 | 0.40 |
July | 0.867137E+09 | 0.500050E+10 | 569112.70 | 58150100.74 | 0.136831E+10 | 1093534.94 | 0.181978E+10 | 28264.37 | 0.41 |
August | 0.125021E+10 | 0.344658E+10 | 2966372.56 | 77803009.78 | 0.101216E+10 | 2289618.03 | 0.325239E+10 | 111115.00 | 0.41 |
September | 0.151446E+10 | 0.670603E+09 | 882784.52 | 79089091.65 | 0.113690E+09 | 51523352.47 | 0.997323E+10 | 59894.60 | 0.40 |
October | 0.119492E+10 | 0.00 | 0.00 | 45618544.56 | 0.00 | 0.636628E+09 | 0.164670E+11 | 0.00 | 0.40 |
November | 0.916677E+09 | 0.00 | 0.00 | 19191053.37 | 0.00 | 0.113064E+11 | 0.857448E+10 | 0.00 | 0.40 |
December | 0.888227E+09 | 0.00 | 0.00 | 1306704.34 | 0.00 | 0.201684E+11 | 0.139271E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.131900E+11 | 0.129253E+11 | 5801077.74 | 0.536848E+09 | 0.330460E+10 | 0.100057E+12 | 0.847412E+11 | 244301.89 | 0.40 |
Minimum of Months | 0.638965E+09 | 0.00 | 0.00 | 902983.18 | 0.00 | 1093534.94 | 0.996768E+09 | 0.00 | 0.40 |
Maximum of Months | 0.176107E+10 | 0.500050E+10 | 2966372.56 | 0.105974E+09 | 0.136831E+10 | 0.318519E+11 | 0.164670E+11 | 111115.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_5_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26630107.28 | 0.00 | 0.00 | 14611.58 | 0.00 | 0.243560E+10 | 7853715.47 | 0.00 | 0.35 |
February | 34239860.82 | 0.00 | 0.00 | 311430.77 | 0.00 | 0.203165E+10 | 39759623.93 | 0.00 | 0.35 |
March | 59807158.83 | 0.00 | 0.00 | 1402826.66 | 0.00 | 0.112321E+10 | 0.271048E+09 | 0.00 | 0.36 |
April | 44437998.92 | 21785139.56 | 17478.11 | 4113350.28 | 0.00 | 0.700846E+09 | 0.470660E+09 | 86.36 | 0.35 |
May | 24615819.34 | 27107256.43 | 69470.79 | 9432559.04 | 0.00 | 0.117918E+09 | 0.822616E+09 | 4247.51 | 0.36 |
June | 12987002.55 | 0.290440E+09 | 285003.63 | 7480546.09 | 1017917.59 | 56112956.09 | 0.398416E+09 | 6358.86 | 0.36 |
July | 1785863.76 | 0.469390E+09 | 336621.26 | 5840927.20 | 61309.81 | 431785.77 | 0.194497E+09 | 16066.91 | 0.36 |
August | 156640.06 | 0.324114E+09 | 310997.67 | 7323364.67 | 4658252.29 | 669305.31 | 0.329867E+09 | 17150.26 | 0.36 |
September | 22742073.99 | 57897293.97 | 18549.13 | 7588966.18 | 0.00 | 0.212360E+09 | 0.614268E+09 | 2637.44 | 0.36 |
October | 54207956.85 | 0.00 | 0.00 | 3225849.36 | 0.00 | 0.754495E+09 | 0.541128E+09 | 0.00 | 0.35 |
November | 51279952.69 | 0.00 | 0.00 | 710132.37 | 0.00 | 0.128616E+10 | 0.197278E+09 | 0.00 | 0.35 |
December | 36045830.05 | 0.00 | 0.00 | 78451.75 | 0.00 | 0.160078E+10 | 19038787.05 | 0.00 | 0.35 |
Annual Sum or Average | 0.368936E+09 | 0.119073E+10 | 1038120.60 | 47523015.94 | 5737479.69 | 0.103202E+11 | 0.390643E+10 | 46547.34 | 0.35 |
Minimum of Months | 156640.06 | 0.00 | 0.00 | 14611.58 | 0.00 | 431785.77 | 7853715.47 | 0.00 | 0.35 |
Maximum of Months | 59807158.83 | 0.469390E+09 | 336621.26 | 9432559.04 | 4658252.29 | 0.243560E+10 | 0.822616E+09 | 17150.26 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_6_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3924760.00 | 0.00 | 0.00 | 6014.96 | 0.00 | 0.246570E+10 | 462521.28 | 0.00 | 0.35 |
February | 17194836.64 | 0.00 | 0.00 | 79213.54 | 0.00 | 0.207302E+10 | 15669298.90 | 0.00 | 0.35 |
March | 64825177.39 | 0.00 | 0.00 | 677962.17 | 0.00 | 0.124321E+10 | 0.146753E+09 | 0.00 | 0.36 |
April | 86225239.94 | 19048050.82 | 34607.91 | 2702838.88 | 2715432.47 | 0.770994E+09 | 0.360134E+09 | 4612.83 | 0.35 |
May | 0.122669E+09 | 20948126.23 | 51599.74 | 7660418.32 | 6177902.52 | 0.129071E+09 | 0.715182E+09 | 3346.23 | 0.36 |
June | 72818590.63 | 0.253759E+09 | 292107.28 | 5304380.06 | 37689480.52 | 57192412.15 | 0.339682E+09 | 8136.57 | 0.36 |
July | 62120072.06 | 0.386915E+09 | 354026.68 | 4075648.16 | 82518671.24 | 317238.76 | 0.136042E+09 | 15565.33 | 0.36 |
August | 89412643.72 | 0.270924E+09 | 471268.83 | 4918372.33 | 57684200.28 | 557094.41 | 0.243129E+09 | 21527.42 | 0.36 |
September | 0.106679E+09 | 53137267.39 | 43384.30 | 4879516.35 | 4732242.86 | 0.268627E+09 | 0.476774E+09 | 5586.00 | 0.36 |
October | 88136746.36 | 0.00 | 0.00 | 1217760.30 | 0.00 | 0.931435E+09 | 0.332268E+09 | 0.00 | 0.35 |
November | 41511400.67 | 0.00 | 0.00 | 165754.84 | 0.00 | 0.139494E+10 | 98807194.89 | 0.00 | 0.35 |
December | 4404195.10 | 0.00 | 0.00 | 11103.69 | 0.00 | 0.164966E+10 | 1870723.75 | 0.00 | 0.35 |
Annual Sum or Average | 0.759921E+09 | 0.100473E+10 | 1246994.73 | 31698983.60 | 0.191518E+09 | 0.109847E+11 | 0.286677E+10 | 58774.39 | 0.36 |
Minimum of Months | 3924760.00 | 0.00 | 0.00 | 6014.96 | 0.00 | 317238.76 | 462521.28 | 0.00 | 0.35 |
Maximum of Months | 0.122669E+09 | 0.386915E+09 | 471268.83 | 7660418.32 | 82518671.24 | 0.246570E+10 | 0.715182E+09 | 21527.42 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_3
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.598421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366190E+11 | 0.00 | 0.00 | 0.49 |
February | 0.138478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290808E+11 | 0.00 | 0.00 | 0.50 |
March | 0.747752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164653E+11 | 0.00 | 0.00 | 0.50 |
April | 0.113407E+11 | 0.00 | 0.00 | 0.00 | 0.427821E+09 | 0.861332E+10 | 0.00 | 0.00 | 0.50 |
May | 0.170732E+11 | 0.00 | 0.00 | 0.00 | 0.640151E+09 | 0.560423E+09 | 0.00 | 0.00 | 0.50 |
June | 0.949538E+10 | 0.00 | 0.00 | 0.00 | 0.430890E+10 | 74381053.58 | 0.00 | 0.00 | 0.50 |
July | 0.480573E+10 | 0.00 | 0.00 | 0.00 | 0.728244E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.740863E+10 | 0.00 | 0.00 | 0.00 | 0.582348E+10 | 0.00 | 0.00 | 0.00 | 0.50 |
September | 0.142777E+11 | 0.00 | 0.00 | 0.00 | 0.627143E+09 | 0.139821E+10 | 0.00 | 0.00 | 0.50 |
October | 0.164497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618110E+10 | 0.00 | 0.00 | 0.50 |
November | 0.695027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185946E+11 | 0.00 | 0.00 | 0.50 |
December | 0.126748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269534E+11 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.985294E+11 | 0.00 | 0.00 | 0.00 | 0.191099E+11 | 0.144540E+12 | 0.00 | 0.00 | 0.50 |
Minimum of Months | 0.598421E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.170732E+11 | 0.00 | 0.00 | 0.00 | 0.728244E+10 | 0.366190E+11 | 0.00 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_1_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3485494.76 | 0.00 | 0.00 | 11622.67 | 0.00 | 0.613178E+09 | 848775.08 | 0.00 | 0.35 |
February | 6291440.78 | 0.00 | 0.00 | 115469.66 | 0.00 | 0.512120E+09 | 7963559.08 | 0.00 | 0.35 |
March | 16041560.75 | 0.00 | 0.00 | 371271.20 | 0.00 | 0.306154E+09 | 41300231.93 | 0.00 | 0.36 |
April | 11289104.98 | 5450676.01 | 0.00 | 1302831.54 | 0.00 | 0.189110E+09 | 0.103313E+09 | 0.00 | 0.35 |
May | 8692529.99 | 6786686.39 | 7564.38 | 2443496.46 | 0.00 | 53211357.03 | 0.179298E+09 | 992.91 | 0.36 |
June | 3512386.55 | 72879778.01 | 9338.53 | 1986026.39 | 45119.83 | 23572807.82 | 89678016.71 | 3040.43 | 0.36 |
July | 446465.94 | 0.117408E+09 | 35110.34 | 1525983.55 | 0.00 | 137932.57 | 48528398.77 | 7438.72 | 0.36 |
August | 0.00 | 82229132.70 | 41322.17 | 2103654.90 | 0.00 | 131669.47 | 82268855.44 | 4711.24 | 0.36 |
September | 6650307.96 | 14475054.95 | 2838.48 | 1995189.21 | 0.00 | 76811688.90 | 0.128783E+09 | 1726.70 | 0.36 |
October | 15839382.44 | 0.00 | 0.00 | 935365.89 | 0.00 | 0.223365E+09 | 98125038.80 | 0.00 | 0.35 |
November | 10598191.09 | 0.00 | 0.00 | 194964.44 | 0.00 | 0.344709E+09 | 28354382.46 | 0.00 | 0.35 |
December | 7538702.24 | 0.00 | 0.00 | 19037.27 | 0.00 | 0.405549E+09 | 878798.26 | 0.00 | 0.35 |
Annual Sum or Average | 90385567.48 | 0.299230E+09 | 96173.91 | 13004913.19 | 45119.83 | 0.274805E+10 | 0.809339E+09 | 17910.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 11622.67 | 0.00 | 131669.47 | 848775.08 | 0.00 | 0.35 |
Maximum of Months | 16041560.75 | 0.117408E+09 | 41322.17 | 2443496.46 | 45119.83 | 0.613178E+09 | 0.179298E+09 | 7438.72 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_2_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 998.36 | 0.00 | 0.617498E+09 | 23998.60 | 0.00 | 0.35 |
February | 1677326.18 | 0.00 | 0.00 | 32053.64 | 0.00 | 0.520103E+09 | 4678021.57 | 0.00 | 0.35 |
March | 11339396.41 | 0.00 | 0.00 | 178568.90 | 0.00 | 0.329206E+09 | 23142576.71 | 0.00 | 0.36 |
April | 21149717.31 | 4769898.99 | 203.08 | 936606.73 | 678858.12 | 0.195844E+09 | 87083587.78 | 1715.82 | 0.35 |
May | 30716113.44 | 5231465.34 | 8113.00 | 2125019.39 | 1554659.09 | 51826449.43 | 0.158978E+09 | 1006.26 | 0.36 |
June | 18196896.48 | 63731685.28 | 35142.32 | 1547534.60 | 9167890.73 | 23758119.62 | 75246686.77 | 2558.47 | 0.36 |
July | 15530018.01 | 96781984.84 | 36313.04 | 1248092.18 | 20629667.81 | 62459.73 | 33798210.90 | 2927.42 | 0.36 |
August | 21757557.34 | 68897477.76 | 48626.99 | 1698316.45 | 13323902.64 | 97039.68 | 60951266.34 | 5158.71 | 0.36 |
September | 26876215.04 | 13292595.00 | 1824.11 | 1306622.16 | 1183060.71 | 81982038.02 | 0.104075E+09 | 2140.31 | 0.36 |
October | 22134725.37 | 0.00 | 0.00 | 445082.18 | 0.00 | 0.251314E+09 | 64370485.77 | 0.00 | 0.35 |
November | 8258052.98 | 0.00 | 0.00 | 85255.85 | 0.00 | 0.362036E+09 | 13477741.59 | 0.00 | 0.35 |
December | 189643.17 | 0.00 | 0.00 | 1664.60 | 0.00 | 0.413736E+09 | 58826.55 | 0.00 | 0.35 |
Annual Sum or Average | 0.177826E+09 | 0.252705E+09 | 130222.55 | 9605815.03 | 46538039.10 | 0.284746E+10 | 0.625884E+09 | 15506.99 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 998.36 | 0.00 | 62459.73 | 23998.60 | 0.00 | 0.35 |
Maximum of Months | 30716113.44 | 96781984.84 | 48626.99 | 2125019.39 | 20629667.81 | 0.617498E+09 | 0.158978E+09 | 5158.71 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: ROOM_3_MULT9_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 75268372.74 | 0.00 | 0.00 | 1261727.70 | 0.00 | 0.365699E+10 | 0.232222E+09 | 0.00 | 0.40 |
February | 0.117090E+09 | 0.00 | 0.00 | 2435295.08 | 0.00 | 0.292541E+10 | 0.336194E+09 | 0.00 | 0.40 |
March | 54173839.76 | 0.00 | 0.00 | 4274441.02 | 0.00 | 0.158672E+10 | 0.691592E+09 | 0.00 | 0.40 |
April | 41565561.42 | 35004334.97 | 0.00 | 6949700.85 | 0.00 | 0.958606E+09 | 0.951685E+09 | 0.00 | 0.40 |
May | 33030571.41 | 43639171.67 | 0.00 | 13135527.16 | 0.00 | 0.131505E+09 | 0.138702E+10 | 0.00 | 0.40 |
June | 20895577.27 | 0.466676E+09 | 89972.11 | 9735588.80 | 1634271.06 | 29055227.96 | 0.702923E+09 | 4400.95 | 0.40 |
July | 2867211.93 | 0.753990E+09 | 177037.31 | 7233702.23 | 98433.16 | 541437.42 | 0.314561E+09 | 6469.32 | 0.40 |
August | 0.00 | 0.523638E+09 | 154150.40 | 10749248.39 | 4574545.92 | 3430710.43 | 0.528507E+09 | 6196.93 | 0.40 |
September | 23174043.27 | 92977315.17 | 11001.64 | 13160292.77 | 0.00 | 0.185539E+09 | 0.115398E+10 | 52.48 | 0.40 |
October | 43614944.29 | 0.00 | 0.00 | 11029399.33 | 0.00 | 0.632886E+09 | 0.148481E+10 | 0.00 | 0.40 |
November | 54602093.10 | 0.00 | 0.00 | 4083800.17 | 0.00 | 0.169886E+10 | 0.707590E+09 | 0.00 | 0.40 |
December | 31146831.09 | 0.00 | 0.00 | 2118004.33 | 0.00 | 0.238315E+10 | 0.242214E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.497429E+09 | 0.191592E+10 | 432161.46 | 86166727.82 | 6307250.14 | 0.141927E+11 | 0.873330E+10 | 17119.67 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1261727.70 | 0.00 | 541437.42 | 0.232222E+09 | 0.00 | 0.40 |
Maximum of Months | 0.117090E+09 | 0.753990E+09 | 177037.31 | 13160292.77 | 4574545.92 | 0.365699E+10 | 0.148481E+10 | 6469.32 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: BANQUET_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.271189E+11 | 0.00 | 0.00 | 21476274.58 | 0.00 | 0.101424E+11 | 0.294155E+11 | 0.00 | 4.21 |
February | 0.110113E+11 | 0.00 | 0.00 | 26863872.26 | 0.00 | 0.179647E+11 | 0.265410E+11 | 0.00 | 4.32 |
March | 0.611890E+10 | 0.00 | 0.00 | 45738923.80 | 0.00 | 0.00 | 0.398101E+11 | 0.00 | 4.53 |
April | 0.190293E+10 | 0.708917E+09 | 0.00 | 54923767.38 | 57671371.16 | 0.00 | 0.382052E+11 | 0.00 | 4.67 |
May | 0.510196E+09 | 0.108004E+10 | 0.00 | 67264475.45 | 71102282.52 | 0.00 | 0.362585E+11 | 0.00 | 4.77 |
June | 0.216106E+09 | 0.780369E+10 | 0.00 | 49917458.85 | 0.297978E+09 | 0.00 | 0.199397E+11 | 0.00 | 4.72 |
July | 77319305.07 | 0.133811E+11 | 0.00 | 36335338.19 | 0.534376E+09 | 0.00 | 0.986495E+10 | 0.00 | 4.62 |
August | 0.163500E+09 | 0.103133E+11 | 0.00 | 46289831.14 | 0.619061E+09 | 0.00 | 0.156182E+11 | 0.00 | 4.66 |
September | 0.747611E+09 | 0.107277E+10 | 0.00 | 59199630.93 | 66414139.63 | 0.00 | 0.314686E+11 | 0.00 | 4.70 |
October | 0.144936E+10 | 0.00 | 0.00 | 55407892.84 | 0.00 | 0.00 | 0.439001E+11 | 0.00 | 4.68 |
November | 0.986020E+10 | 0.00 | 0.00 | 39839729.62 | 0.00 | 0.959585E+09 | 0.376330E+11 | 0.00 | 4.48 |
December | 0.170028E+11 | 0.00 | 0.00 | 29972778.31 | 0.00 | 0.00 | 0.342623E+11 | 0.00 | 4.25 |
Annual Sum or Average | 0.761790E+11 | 0.343598E+11 | 0.00 | 0.533230E+09 | 0.164660E+10 | 0.290666E+11 | 0.362917E+12 | 0.00 | 4.55 |
Minimum of Months | 77319305.07 | 0.00 | 0.00 | 21476274.58 | 0.00 | 0.00 | 0.986495E+10 | 0.00 | 4.21 |
Maximum of Months | 0.271189E+11 | 0.133811E+11 | 0.00 | 67264475.45 | 0.619061E+09 | 0.179647E+11 | 0.439001E+11 | 0.00 | 4.77 |
Report: MechanicalVentilationLoadsMonthly
For: DINING_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.241013E+11 | 0.00 | 0.00 | 30640785.09 | 0.00 | 0.103547E+11 | 0.365422E+11 | 0.00 | 4.51 |
February | 0.707811E+10 | 0.00 | 0.00 | 37343519.76 | 0.00 | 0.184054E+11 | 0.341584E+11 | 0.00 | 4.68 |
March | 0.203208E+10 | 0.00 | 0.00 | 60659671.08 | 0.00 | 0.00 | 0.484070E+11 | 0.00 | 4.97 |
April | 0.397360E+09 | 0.787543E+09 | 0.00 | 69818885.64 | 25765528.54 | 0.00 | 0.437817E+11 | 0.00 | 5.13 |
May | 77964784.70 | 0.119393E+10 | 0.00 | 82894115.03 | 34495200.06 | 0.00 | 0.403812E+11 | 0.00 | 5.22 |
June | 42200463.99 | 0.852239E+10 | 0.00 | 59555392.08 | 0.144008E+09 | 0.00 | 0.220030E+11 | 0.00 | 5.11 |
July | 26239769.40 | 0.146142E+11 | 0.00 | 42282765.09 | 0.312747E+09 | 0.00 | 0.107876E+11 | 0.00 | 4.97 |
August | 99543906.41 | 0.113837E+11 | 0.00 | 54598905.10 | 0.326022E+09 | 0.00 | 0.170382E+11 | 0.00 | 5.02 |
September | 0.157032E+09 | 0.116966E+10 | 0.00 | 72910068.74 | 43794799.34 | 0.00 | 0.351768E+11 | 0.00 | 5.11 |
October | 0.421104E+09 | 0.00 | 0.00 | 70859581.32 | 0.00 | 0.00 | 0.495976E+11 | 0.00 | 5.15 |
November | 0.658572E+10 | 0.00 | 0.00 | 53305590.94 | 0.00 | 0.713066E+09 | 0.454015E+11 | 0.00 | 4.89 |
December | 0.107577E+11 | 0.00 | 0.00 | 41920218.95 | 0.00 | 0.00 | 0.446480E+11 | 0.00 | 4.61 |
Annual Sum or Average | 0.517764E+11 | 0.376714E+11 | 0.00 | 0.676789E+09 | 0.886832E+09 | 0.294731E+11 | 0.427923E+12 | 0.00 | 4.95 |
Minimum of Months | 26239769.40 | 0.00 | 0.00 | 30640785.09 | 0.00 | 0.00 | 0.107876E+11 | 0.00 | 4.51 |
Maximum of Months | 0.241013E+11 | 0.146142E+11 | 0.00 | 82894115.03 | 0.326022E+09 | 0.184054E+11 | 0.495976E+11 | 0.00 | 5.22 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.424943E+10 | 0.00 | 0.00 | 99112162.84 | 0.00 | 0.117616E+11 | 0.804060E+11 | 0.00 | 20.48 |
February | 0.367239E+10 | 0.00 | 0.00 | 89654506.45 | 0.00 | 0.155396E+11 | 0.596100E+11 | 0.00 | 21.07 |
March | 0.00 | 0.00 | 0.00 | 0.116329E+09 | 0.00 | 0.00 | 0.704758E+11 | 0.00 | 22.57 |
April | 0.00 | 0.128555E+10 | 0.00 | 0.113118E+09 | 0.00 | 0.00 | 0.585404E+11 | 0.00 | 22.45 |
May | 0.00 | 0.192628E+10 | 0.00 | 0.124111E+09 | 0.00 | 0.00 | 0.497735E+11 | 0.00 | 21.95 |
June | 0.00 | 0.124075E+11 | 0.00 | 83273018.11 | 0.00 | 0.00 | 0.260130E+11 | 0.00 | 21.19 |
July | 0.00 | 0.205399E+11 | 0.00 | 53438873.50 | 0.00 | 0.00 | 0.114393E+11 | 0.00 | 20.59 |
August | 0.00 | 0.166295E+11 | 0.00 | 72974563.04 | 0.00 | 0.00 | 0.182861E+11 | 0.00 | 20.68 |
September | 0.00 | 0.186545E+10 | 0.00 | 0.113053E+09 | 0.00 | 0.00 | 0.440240E+11 | 0.00 | 21.60 |
October | 0.00 | 0.00 | 0.00 | 0.118819E+09 | 0.00 | 0.00 | 0.669479E+11 | 0.00 | 22.62 |
November | 0.239886E+09 | 0.00 | 0.00 | 0.108775E+09 | 0.00 | 0.211015E+10 | 0.705526E+11 | 0.00 | 22.00 |
December | 60438203.59 | 0.00 | 0.00 | 0.111581E+09 | 0.00 | 0.00 | 0.803378E+11 | 0.00 | 21.45 |
Annual Sum or Average | 0.822214E+10 | 0.546543E+11 | 0.00 | 0.120424E+10 | 0.00 | 0.294114E+11 | 0.636407E+12 | 0.00 | 21.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 53438873.50 | 0.00 | 0.00 | 0.114393E+11 | 0.00 | 20.48 |
Maximum of Months | 0.424943E+10 | 0.205399E+11 | 0.00 | 0.124111E+09 | 0.00 | 0.155396E+11 | 0.804060E+11 | 0.00 | 22.62 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_FLR_6
Timestamp: 2020-06-03 19:46:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.745089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182847E+11 | 0.00 | 0.00 | 0.95 |
February | 0.211780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134597E+11 | 0.00 | 0.00 | 0.96 |
March | 0.629126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595104E+10 | 0.00 | 0.00 | 0.96 |
April | 0.797796E+10 | 0.00 | 0.00 | 0.00 | 0.218751E+09 | 0.222483E+10 | 0.00 | 0.00 | 0.96 |
May | 0.901632E+10 | 0.00 | 0.00 | 0.00 | 0.327319E+09 | 0.00 | 0.00 | 0.00 | 0.97 |
June | 0.489316E+10 | 15077592.03 | 0.00 | 0.00 | 0.218812E+10 | 0.00 | 0.00 | 0.00 | 0.97 |
July | 0.245724E+10 | 0.00 | 0.00 | 0.00 | 0.372362E+10 | 0.00 | 0.00 | 0.00 | 0.97 |
August | 0.378814E+10 | 0.00 | 0.00 | 0.00 | 0.297763E+10 | 0.00 | 0.00 | 0.00 | 0.97 |
September | 0.778778E+10 | 0.00 | 0.00 | 0.00 | 0.320667E+09 | 0.227522E+09 | 0.00 | 0.00 | 0.96 |
October | 0.105147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105670E+10 | 0.00 | 0.00 | 0.96 |
November | 0.558438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747707E+10 | 0.00 | 0.00 | 0.96 |
December | 0.157671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128530E+11 | 0.00 | 0.00 | 0.95 |
Annual Sum or Average | 0.627506E+11 | 15077592.03 | 0.00 | 0.00 | 0.975611E+10 | 0.615346E+11 | 0.00 | 0.00 | 0.96 |
Minimum of Months | 0.745089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
Maximum of Months | 0.105147E+11 | 15077592.03 | 0.00 | 0.00 | 0.372362E+10 | 0.182847E+11 | 0.00 | 0.00 | 0.97 |